TYPE: AUC-18UX4SGAA AUC-24UX4SZEA AUC-36UX4SAEA AUC-48UX6SPFA AUC-60UX6SPFA
AUC-18HR4SUAA AUC-24HR4SZGA AUC-36HR6SAGA AUC-48HR6SPHA AUC-60HR6SPHA
AUC-18UR4SZAA1 AUC-24UR4SAEA1 AUC-36UR4SAEA1
AUC-18CR4FUAA AUC-42CR4FEHA
Thank you for buying this air conditioner. Please read these instructions carefully before installing and using this device, save it for later use.

We warmly welcome you as a user of our product! We thank you for your trust in us. Read this manual carefully before installation. Keep this manual safe for later use after installation.
Little space for installation is needed. Self-recovering after power failure. If the power supply is restored after a malfunction, all settings are still active and the air conditioner works according to the original settings.
The interior unit can easily be installed in the ceiling space.
Highly efficient and environmentally friendly new coolant R410A. R410A protects the environment and can not harm the ozone layer.
Self-diagnostic function in case of malfunction. If there is something wrong with the air conditioner, the microprocessor will examine the malfunction and then it can be read on screen for convenience in maintenance.
On and off 24-hour timer. This timer can be set to automatically switch on or off the unit per day.
Silent operation. The excellent fan design ensures a quiet and even airflow with little noise.
* NOTE: Use coolant R22 for an integrated air conditioner only for cooling.
On/off integrated air conditioner
AUC-18UX4SGAA AUC-24UX4SZEA AUC-36UX4SAEA AUC-48UX6SPFA AUC-60UX6SPFA
AUC-18HR4SUAA AUC-24HR4SZGA AUC-36HR6SAGA AUC-48HR6SPHA AUC-60HR6SPHA
New DC inverter integrated air conditioner (high-efficiency model)
Only cool integrated air conditioner
AUC-18UR4SZAA1 AUC-24UR4SAEA1 AUC-36UR4SAEA1
AUC-18CR4FUAA
AUC-42CR4FEHA

Immediate danger of serious personal injury or death.
Danger or unsafe actions that can lead to serious personal injury or death.
Dangerous or unsafe actions that CAN lead to personal injury or damage to products and property.
LET OP

DC inverter integrated model (18 k, 24 k, 36 k)
This manual shall be considered as part of the air conditioning equipment and must be kept near the apparatus.
NOTE: Heating and an electric heating function are not available for cooling only models.

The standard use of the unit is explained in these instructions. Therefore, use of the unit, other than as specified in these instructions, is not recommended. If necessary, contact the local representative.
●

Equipment components
2.1 Stand-up function
2.2 Sleep function
2.3 Timer Function
2.4 Valve setting
4.1 Remote control H1
4.1.1 Operating status 17 17 17
4.1.2 Airflow control 18 18 18
4.1.3 Smart stand 19 19 19
4.1.4 Clock setting 19 19 19
4.1.5 Timer Mode 20 20 20
4.1.6 Sleep Mode 21 21
4.1.7 Super-stand 21 21
4.2 Remote control J1
4.2.1 Operating status
4.2.2 Airflow control
4.2.3 Smart Stand
4.2.4 Clock setting
4.2.5 Timer mode
4.2.6 Sleep Mode
4.2.7 Super-stand
4.3 Remote control E4-07
4.3.1 Operating status
4.3.2 Control of airflow
4.3.3 Smart stand
4.3.4 Clock setting
4.3.5 Timer mode
4.3.6 Sleep Mode
4.3.7 Super-stand

37 37 37 8. Clean Filter
9. Problem solving
3.1 The first check
3.2 Installation (for 24 k, 36 k, 42 k, 48 k, 60 k)
3.3 Installation (for 18 k)
4.1 The first check
4.2 Installation
4.3 Length of lead between indoor and outdoor units
5.1 Leading material
5.2 Connection of the pipes
7. Electrical wiring
7.1 General control
56 7.2 Connection of electrical wiring
8. Test twist
9. General

The symbols in this manual have the following meanings:
Don't do this.
Follow this instruction for sure.
A function of the device instead of. A mistake.
Earthing is necessary.
Beware of such a situation.

There shall be a protection switch to disable the device in the cases specified below.
Install the air conditioner in a place that can carry the weight, so that the unit works quieter.
If the air conditioner is operating for a longer period of time in the COLD or DROGEN mode with an open door or window and the relative humidity is more than 85%, condensation of the air outlet may drizzle.
Characteristics of protection Inspection
After a longer period of use, the air conditioner must be checked for the following components: Overheating of power cable and plug or even burning smell. Abnormal noise or vibration when used. Water leakage from the inside unit. Metal casing is under power.
The security device shall enter into force in the following case:
When disabling the device and rebooting it immediately or changing program while working: you will have to wait 3 minutes.
Turn off the air conditioner if problems above occur. It is recommended to carry out a detailed inspection after 5 years of use, even if none of the problems mentioned above occur.
Functions in the heating mode
At the start of the heating function, air flow from inside unit is slowed down for 2-5 minutes.
In heating mode, the device is automatically thawed for better efficiency. This procedure normally takes 2-10 minutes. During thawing, the fan stops working. After thawing, the device automatically returns to heating mode.
It is difficult to increase the room temperature when the outside temperature is very low. In this case, also use other heaters together with the air conditioner.
Noise Control Operating conditions · Preheating · Decommissioning

Interior unit


24 k, 36 k, 42 k, 48 k, 60 k


18 k, 24 k, 36 k
42 k, 48 k, 60 k
Please note: The images above are for reference only, specifications depend on the product materials.
18 k

Wired remote control Wireless remote control


T IMER O FF S ET T IMER A
The remote control is used to operate the built-in display screen and wired remote control. Please note: There are different types of remote controls, there are specific models for certain applications.
The wired remote control is used for the direct operation of the built-in unit in the inner unit.

This lights up during thawing. This lights up when the defrosting is done.
This light up when the filter needs cleaning.
This sounds like the signal from the remote control was received.
This lightens up when the timer is in use. This light up when the timer is complete.
Clean filter is reset when the button is pressed.
This lightens up during operation. It will go off completely when the SLAP mode is set.

The images in this manual are based on the view of a standard model. This may cause the shape to differ from the air conditioner you have chosen.
Display screen · Undo Filter Timer

1. Introduction Wired Remote

1 Sensor room temperature: In the remote control, a temperature sensor is set to measure room temperature and this value is sent to the inner unit. If the inner unit does not connect to the remote control, the internal unit will switch to the temperature sensor incorporated into the interior unit.
2 Wireless receiver With this receiver you can use an additional wireless remote control to operate the inner unit. 3 ON/OFF button Press this button to turn the unit on or off. 4 Stand-chooser button Press this button for the selection of COOLS, UNSCHOOLS , VENTILATE, HEAT or AUTO-RUN.
In the COELEN position, the air conditioner will cool the room.
In the ONTV CHART mode, humidity in space is reduced.
In the VENTILEREN position, the air conditioner adjusts the temperature of the room with a gentle flow of air.
In the position WAITING, the air conditioner will warm up the room.
In the AUTO-RUN mode, the air conditioner shall operate according to room temperature. (This position is not available for 18 k and 24 k DC inverter integrated air conditioners except the high-efficiency models.)
Press this button to activate sleep mode and . . Press again to disable sleep mode. Press this button for 3 seconds to activate the Timer function. Press again 5 seconds to disable the Timer function. For the Timer functions, see chapter introduction Timer function.
6 VENTILATOR NELTY button: (setting of the valve is described on page. 8.) Press this button to change the current fan speed. You can choose between . . (automatic fan speed), .
7 TEMP selector: Press both buttons simultaneously to set the desired room temperature. If you have pressed both buttons, .TEMPERATURE .SET appears on the LCD screen, press . .to lower the set temperature and to increase the set temperatures.


Screen area for indicating the state in which the unit works.
Display fan speed.
Display valve direction (for built-in type unit only).
Display area for the position in which the unit is currently operating.
Display Timer setting.



(This position is not available for 18 k and 24 k DC inverter integrated air conditioners with the exception of high-efficiency models).

T IMER O FF

2.1 Stand-up function
2.1.1 Press the Stand-Selection button . . to select operating condition:
Autom. stand (this position is not available for 18 k and 24 k DC inverter integrated air conditioners with the exception of high-efficiency models)
2.1.2 Press the ON/OFF . . button to switch on or off the unit. 2.1.3 Pressure on TEMPUS. INSTITUTION . . The temperature range can be set from 18 to 32 °C. 2.1.4 Press the VENTILATOR button . . to set the desired fan speed. Of course you can automatically set ventilation and the inner unit will automatically choose speed by the difference between room temperature and set temperature. 2.1.5 The unit can be turned off by pressing the ON/OFF button .
NOTE: The temperature setting is not available in the ventilation mode.

2.2 Sleep function

Press the timer/sleep button once to activate sleep mode and the sleeping sign . . Press the timer/sleep button again to break this position and the sleep sign will disappear on the LCD screen. NOTE: During the ventilation and car position, sleep function is not available.

2.3 Timer Function
2.3.1 The timer OF 1 You can turn off the timer when the inner unit is working. By holding the TIMER/SLAP button pressed for 3 seconds, the timer will appear on the LCD screen and the ACTIVE OFF symbol will flash. 2 You can adjust the time when the unit automatically switches off by pressing the . . The time can be set from 0.5 to 24 (or 12) hours in steps of 30 minutes. 3 Once you have set the time, press the TIMER/SLAP button for another 3 seconds or wait 5 seconds to activate the timer, the .TIMER OFF-Tip Stopping the flashing and the timers work. 4 If you want to turn off the ACTIVE TIMER OFF, press the TIMER/SLAP button for 3 seconds to activate the timer. Press . . After 5 seconds, .TIMER OFF'S automatically broken down.
2.3.2 The TIMER ON 1 mode You can turn on the timer when the inner unit is not working. By holding the TIMER/SLAP button for 3 seconds, the timer will appear on the LCD screen and the . 2 You can adjust the time when the unit automatically switches on by pressing the . . The time can be set from 0.5 to 24 (or 12) hours in steps of 30 minutes. 3 Once you have set the time, press the TIMER/SLAP button for another 3 seconds or wait 5 seconds to activate the timer, the .TIMER ON-SHAKE indication stops blinking and the timers work. 4 If you want to turn off the ON-Sheet Timer, press the TIMER/SLEEP button for 3 seconds to activate the timer. Press . . After 5 seconds, .TIMER ON .She is automatically broken down.

2.4 Setting valve When the air conditioner is on, press . . 2 seconds on . If you want to stop the swing, press . . and the valve stops turning for 2 seconds.

3. Installation Wired Remote Control
Before installing the wired remote control, please note:


The wired remote control must be installed by a qualified installer
in accordance with the installation drawings. For installation, the power must be switched off. Do not install the wired remote control directly in the air current or at heating. The installation process is as follows. 1 Insert a flat screwdriver into the openings at the bottom (2 pieces). Be careful not to damage the circuit board by screwdriver. 2 Remove the back plate. 3 Use two screws (Ø 4x16) to mount the metal back plate in the right place and then connect the wiring for communication. 4 Click the top of the back plate. 5 Then click the bottom on the back plate.


The remote control sends signals to the system.
ON/OFF KNOP The device will start up as soon as it gets power and if it works, it can be turned off when this button is pressed.
Stand-KNOP Press this button to select the operating mode.
VENTILATOR KNOP For selecting the fan speed in the sequence autom., high, gem. Or low.
SPACE TERMERATURE INTELOPING For adjusting space temperature, timer and actual time.
SLIM-KNOP (not available for this model) For the direct input of fuzzy logic, independent whether the unit is on or off.
SHOWER-KNOP (not available for this model) To start the swivel of the horizontal valve or stop and set it to the desired direction of airflow up/down.
SLEEP KNOP To set or disable sleep mode. DIMMER-KNOP (not available for this model) The brightness of the screen is reduced every time the button is pressed and after four pushes the image disappears.
I FEEL-Button To set or disable the I FEel mode. Press this button for 5 seconds to disable the I FEEL mode. (In the I FEEL mode, the air conditioner works with the temperature sensor that is in the remote control instead of. The unit. When using the I FEEL mode, the remote control must be located in a location where the signal can easily be received through the inner unit.) TEMP SCHAKEL-KNOP (not available for this model) Specifies the set temperature flashing when the button is pressed. Indicates the indoor temperature when pressing the button again. The indication can be terminated by pressing the button again.
KNOP KLOCK To set the current time.
ON/OFF TIMER button To set or disable the timer.
SUPER-KNOP (not available for heating mode) To set or disable the fast cooling. (Fast cooling works with a high fan speed and an automatic temperature setting of 18 °C.)
ZACHT-KNOP (not available for this model) To limit the maximum power consumption, so that you can use the unit together with other electrical devices if there is not enough current.
DEMPEN-KNOP To set or disable the DEMPE mode.
SHOWER-KNOP (not available for this model) To start the swivel of the vertical valve or stop and set it to the desired direction of airflow left/right. *Not all remote control models have this button.
Symbols shown on the LCD display:
Autom. fan speed
Set view timer Display current time
Gem. fan speed
Aborting view I FEEL
NOTE: Each position with the relevant functions is explained in more detail on the following pages.

Battery application

Remove the battery cover in the direction of the arrow. Place new batteries and ensure that the (+) and (-) of the batteries are correctly fitted. Replace the lid by sliding it back into the right position.
NOTE: Use 2 LR03 AAA (1.5 volts) batteries. Do not use rechargeable batteries. Replace the batteries with new ones of the same type when the screen becomes vague.
Point the remote to the receiver of the signal to control the air conditioner. The remote control can operate the air conditioner up to a distance of 8 m if it is directed towards the receiver of the indoor unit.

R UN TIME R FILTE R DE FR OS T
T IMER O FF S ET T IMER A
24 k, 36 k, 42 k, 48 k, 60 k
Remote control · Usage


Each time the stand button is pressed, the operating condition changes in order:
The heating mode is not available for air conditioners that can only cool.
Each time the VENTILATOR button is pressed, the fan speed changes in order:
In the stand ONLY VENTILATE are only "High, Gem. and Low" available. In the DROGEN mode, fan speed is automatically set to Low and the VENTILATOR button does not work in this case.
Press once to increase temperature setting by 1 °C
Press once to lower the temperature setting by 1 °C
Range of available temperature setting
18 °C ~ 32 °C
NOTE: The heating mode is not available for models that can only cool.
The positions SHOW, SLIM, TIMER ON, TIMEER OFF, KLOK, SLEEP and SUPER are explained on the following pages.
When changing the position while the unit is working, it does not always react immediately. Then wait three minutes. In the heating mode, air will not flow directly from the unit. After 2-5 minutes, the air flow starts when the temperature of the heat exchanger has risen. Always wait 3 minutes before restarting the device.
Operating conditions

Control of the direction of airflow
Control of the direction of airflow

The horizontal and vertical airflow is automatically adjusted to a certain angle depending on the operating state after the unit has been switched on.
The direction of the airflow can also be adjusted to your own requirements by pressing the "SWING" and "SWING" buttons on the remote control.
*HEAT ONLY VENT.

I FEEL SOFT 4
SWING
DIMMER SMART
SLEEP
Note: Vertical airflow control is not available for cassette models.
MUTE TEP SWITCH
Control of vertical airflow (with remote control)

Use the remote control to set alternate angles or, if desired, certain current corners.
Once the "SWING" button is pressed, the horizontal air valve will automatically swivel up and down.
By pressing the "SWING" button again, the air valve will swivel to the desired angle.
Control horizontal airflow (with remote control)
Use the remote control to set alternate angles or, if desired, certain current corners.
Once the "SWING" button is pressed, the vertical air valve will automatically swivel left and right.
By pressing the "SWING" button again, the air valve will swivel to the desired angle.
Do not adjust the horizontal and vertical air valves manually, otherwise a malfunction may occur. If this occurs, you must turn off the unit first, then restore power supply and then restore the power supply.
It is better not to hold the horizontal air valve too long in its downward position during the positions COELING or DROGEN, to prevent the dripping of condensation.

Press the SLIM button and the unit will start the SlimME mode (fuzzy logic control) directly, whether on or off. In this mode, the temperature and fan speed are automatically set based on actual room temperature.
Operating condition and temperature are determined by the indoor temperature

Lower than T-3 °C
T
T-3 °C ≤ Interior ≤ T+3 °C
T
Higher than T+3 °C
T
Models for cooling only

SWING
DIMMER SMART
SLEEP
T+3 °C or less
T
SWING
MUTE TEP SWITCH
T Higher than T+3 °C
I FEEL SOFT

The SLIM button is not active in the SUPER mode. NOTE: Temperature, airflow and direction are automatically controlled in the SLIMME mode. However, the remote control can set a reduction or increase of 7 °C if you are not feeling comfortable yet.
What can you do in SLIMME mode?
Uncomfortable due to incorrect air flow
Fan speed changes between high, gem. and down, every time the button is pressed.
Uncomfortable due to incorrect direction of flow
Pressure once, the horizontal air valve swells to change the direction of the airflow. Press again and the swing stops.
Uncomfortable due to incorrect direction of flow
Pressure once, the vertical air valve swells to change the direction of the airflow. Press again and the swing stops.
The actual time can be changed by pressing the KLOK button and then using the and buttons for the right time. Press KLOK again and the time is set.

It is very useful to set the timer with the TIMER ON buttons when you leave in the morning, so that at home a comfortable room temperature can be reached. You can also turn off the timer at night to enjoy a good night's sleep with the TIMER OFF button.
The TIMER ON button can be used to set the timer programming as desired, so that the unit is enabled at your preferred time.
Press the TIMER ON button, "12:00 ON" flashes on the LCD screen, then press or select your desired enable time.
Press the button once to increase or decrease time by 1 minute. Press the or button for 5 seconds to increase or decrease time settings by 10 minutes. Press the button or push for a longer time to increase or decrease the timing by 1 hour.
NOTE: If you do not set the time within 5 seconds after pressing the TIMER ON button, the remote control will automatically exit the TIMEr ON mode.
Once the desired time is displayed on the LCD screen, press the TIMER ON button to confirm it. There's a beeping sound. "ON" stops blinking. The TIMER view on the inner unit lights up.
After the set timer is shown for 5 seconds, the time will be displayed on the LCD screen of the remote control instead of. the set timer.
Press the TIMER ON button again, a beep clicks and the view disappears as a sign that TIMER is disabled.
NOTE: Setting TIMER OFF goes the same way. This allows you to automatically disable the unit at your desired time.


The SLEEP mode can be set at the positions COOL, HEAR or DROGEN. The function ensures a more comfortable environment during sleep. In SLAP mode:
will stop the unit automatically after it has been working for 8 hours.
NOTE: The heating mode is not available for air conditioners that can only cool.
(not available in heating mode)

The SUPER mode is used to quickly switch on or off cooling. Fast cooling works with a high fan speed, automatically changing the set temperature to 18 °C.
The SUPER mode can be set when the device is working or on.
In the SUPER mode, you can adjust the direction of the airflow or timer. If you want to disable the SUPER mode, press one of the following buttons: SUPER, STAND, VENTILATE, ON/OFF or TEMPERATURE INSTITUTION.
NOTE: The SLEEP and SLIM buttons are not available in SUPER mode. The SUPER button is not active in the HEAR position. The device will continue to operate in SUPER mode with a set temperature of 18 °C if you do not break it down by pressing one of the buttons specified above.
SUPER mode · SUPER position


The remote control sends signals to the system.
ON/OFF KNOP The device will start up as soon as it gets power and if it works, it can be turned off when this button is pressed.
Stand-KNOP Press this button to select the operating mode.
VENTILATOR KNOP For selecting the fan speed in the sequence autom., high, gem. Or low.
SPACE TERMERATURE INTELOPING For adjusting space temperature, timer and actual time..
SLIM-KNOP (not available for this model) For the direct input of fuzzy logic, independent whether the unit is on or off.
SHOWER-KNOP (not available for this model) To start the swivel of the horizontal valve or stop and set it to the desired direction of airflow up/down.
SLEEP KNOP To set or disable sleep mode. I FEEL-Button To set or disable the I FEel mode. Press this button for 5 seconds to disable the I FEEL mode. (In the I FEEL mode, the air conditioner works with the temperature sensor that is in the remote control instead of. The unit. When using the I FEEL mode, the remote control shall be located in a location where the signal can easily be received through the internal unit.)
* Note: some remote control models do not have buttons in the square with dotted line.
KNOP KLOCK To set the current time.
DIMMER KNOP The brightness of the screen is reduced every time the button is pressed and after four pushes, the image disappears.
ON/OFF TIMER button To set or disable the timer.
SUPER-KNOP For setting or turning off the fast cooling/heating. (Fast cooling works with a high fan speed and an automatic temperature setting of 18 °C. Fast heating works with an automatic fan speed and a 32 °C temperature setting.)
SHOWER-KNOP (not available for this model) To start the swivel of the vertical valve or stop and set it to the desired direction of airflow left/right.
Symbols shown on the LCD display:
Autom. fan speed
Set view timer Display current time
Gem. fan speed
NOTE: Each position with the relevant functions is explained in more detail on the following pages.


Battery application
Remove the battery cover in the direction of the arrow. Place new batteries and ensure that the (+) and (-) of the batteries are correctly fitted. Replace the lid by sliding it back into the right position.
Use 2 LR03 AAA (1.5 volts) batteries. Do not use rechargeable batteries. Replace the batteries with new ones of the same type when the screen becomes vague.
Point the remote to the receiver of the signal to control the air conditioner. The remote control can operate the air conditioner up to a distance of 8 m if it is directed towards the receiver of the indoor unit.

T IMER O FF S ET T IMER A
24 k, 36 k, 42 k, 48 k, 60 k
Remote control · Usage


Each time the stand button is pressed, the operating condition changes in order:
The heating mode is not available for air conditioners that can only cool.
Each time the VENTILATOR button is pressed, the fan speed changes in order:
In the stand ONLY VENTILATE are only "High, Gem. and Low" available. In the DROGEN mode, fan speed is automatically set to Low and the VENTILATOR button does not work in this case.
Press once to increase temperature setting by 1 °C
Press once to lower the temperature setting by 1 °C
NOTE: The heating mode is not available for models that can only cool.
The positions SHOW, SLIM, TIMER ON, TIMEER OFF, KLOK, SLEEP and SUPER are explained on the following pages.
When changing the position while the unit is working, it does not always react immediately. Then wait three minutes. In the heating mode, air will not flow directly from the unit. After 2-5 minutes, the air flow starts when the temperature of the heat exchanger has risen. Always wait 3 minutes before restarting the device.
Operating conditions

Control of the direction of airflow
Control of the direction of airflow
The horizontal and vertical airflow is automatically adjusted to a certain angle depending on the operating state after the unit has been switched on.






The direction of the airflow can also be adjusted to your own requirements by pressing the "SWING" and "SWING" buttons on the remote control.
ON
OFF
OFF
COOLING, DRYING
*HEAT ONLY VENT.
MODE FAN
Control of vertical airflow (with remote control)
SLEEP SUPER
Use the remote control to set alternate angles or, if desired, certain current corners.
SWING 4
TIMER ON TIMER OFF CLOCK
Once the "SWING" button is pressed, the horizontal air valve will automatically swivel up and down.
By pressing the "SWING" button again, the air valve will swivel to the desired angle.
Control horizontal airflow (with remote control)
Use the remote control to set alternate angles or, if desired, certain current corners.
Once the "SWING" button is pressed, the vertical air valve will automatically swivel left and right.
By pressing the "SWING" button again, the air valve will swivel to the desired angle.
Do not adjust the horizontal and vertical air valves manually, otherwise a malfunction may occur. If this occurs, you must turn off the unit first, then restore power supply and then restore the power supply.
It is better not to hold the horizontal air valve in its downward position for too long during the positions COELEN or DROGEN, to prevent the dripping of condensation.

Press the SLIM button and the unit will start the SlimME mode (fuzzy logic control) directly, whether on or off. In this mode, the temperature and fan speed are automatically set based on actual room temperature.



Operating condition and temperature are determined by the indoor temperature



OFF
Lower than T-3 °C
T
T-3 °C ≤ Interior ≤ T+3 °C
T
ON/OFF
Higher than T+3 °C
T
Models for cooling only
SWING
SLEEP SUPER
T+3 °C or less
T
SMART FAELE DIMMER
T Higher than T+3 °C
TIMER ON TIMER OFF CLOCK
SWING
The SLIM button is not active in the SUPER mode. NOTE: Temperature, airflow and direction are automatically controlled in the SLIMME mode. However, the remote control can set a reduction or increase of 7 °C if you are not feeling comfortable yet.
What can you do in SLIMME mode?
Uncomfortable due to incorrect air flow
Fan speed changes between high, gem. and down, every time the button is pressed.
Uncomfortable due to incorrect direction of flow
Pressure once, the horizontal air valve swells to change the direction of the airflow. Press again and the swing stops.
Uncomfortable due to incorrect direction of flow
Pressure once, the vertical air valve swells to change the direction of the airflow. Press again and the swing stops.
The actual time can be changed by pressing the KLOK button and then using the and buttons for the right time. Press KLOK again and the time is set.

It is very useful to set the timer with the TIMER ON buttons when you leave in the morning, so that at home a comfortable room temperature can be reached. You can also turn off the timer at night to enjoy a good night's sleep with the TIMER OFF button.
The TIMER ON button can be used to set the timer programming as desired, so that the unit is enabled at your preferred time.
Press the TIMER ON button, "12:00 ON" flashes on the LCD screen, then press or select your desired enable time.

Press the button once to increase or decrease time by 1 minute. Press the or button for 5 seconds to increase or decrease time settings by 10 minutes. Press the button or push for a longer time to increase or decrease the timing by 1 hour.
NOTE: If you do not set the time within 10 seconds after pressing the TIMER ON button, the remote control will automatically exit the TIMEr ON mode.
Once the desired time is displayed on the LCD screen, press the TIMER ON button to confirm it. There's a beeping sound. "ON" stops blinking. The TIMER view on the inner unit lights up.
After the set timer is shown for 5 seconds, the time will be displayed on the LCD screen of the remote control instead of. the set timer.
Press the TIMER ON button again, a beep clicks and the view disappears as a sign that TIMER is disabled.
NOTE: Setting TIMER OFF goes the same way. This allows you to automatically disable the unit at your desired time.


The SLEEP mode can be set at the positions COOL, HEAR or DROGEN. The function ensures a more comfortable environment during sleep. In SLAP mode:
will stop the unit automatically after it has been working for 8 hours.
NOTE: The heating mode is not available for air conditioners that can only cool.
The SUPER mode is used to quickly switch on or off cooling. Fast cooling works with a high fan speed, automatically changing the set temperature to 18 °C. Fast heating works with an automatic fan speed, automatically changing the set temperature to 32 °C.
OFF
The SUPER mode can be set when the device is working or on.
In the SUPER mode, you can adjust the direction of the airflow or timer. To disable the SUPER mode, press one of the following buttons: SUPER, STAND, VENTILATE, ON/OFF, SLEEP or TEMPERATURE INSTITUTION.
OFF
NOTE: The SLIM button is not available in SUPER mode. The device will continue to work in SUPER mode if you do not break it down by pressing one of the buttons specified above.

The remote control sends signals to the system.

ON/OFF KNOP The device will start up as soon as it gets power and if it works, it can be turned off when this button is pressed.
Stand-KNOP Press this button to select the operating mode.
VENTILATOR KNOP For selecting the fan speed in the sequence autom., high, gem. Or low.
SPACE TERMERATURE INTELOPING For adjusting space temperature, timer and actual time.
SLIM-KNOP For the direct input of fuzzy logic, independent whether the unit is on or off.
SHOWER-KNOP To start the swivel of the horizontal valve or stop and adjust it to the desired direction of airflow up/down.
SLEEP KNOP To set or disable sleep mode.
I FEEL-Button To set or disable the I FEel mode.
10 SUPER-KNOP To set or disable the fast cooling. (Fast cooling works with a high fan speed and an automatic temperature setting of 18 °C.)
KNOP KLOCK To set the current time.
ON/OFF TIMER button To set or disable the timer.
Symbols shown on the LCD display:
Shipping signal Display cooling
Autom. fan speed
Set view timer Display current time
Gem. fan speed
Display heating Display set temperature
NOTE: When you put the batteries in your remote control for the first time, all indications appear on the LCD screen for a few seconds and then the "Cow" and "warming" indications are displayed sequentially, allowing you to choose "Heating" models and "Coulding" only for cooling models. Each position with the relevant functions is explained on the following pages.


Battery application
Remove the battery cover in the direction of the arrow. Place new batteries and ensure that the (+) and (-) of the batteries are correctly fitted. Replace the lid by sliding it back into the right position.
Remove the battery cover in the direction of the arrow. Place new batteries and ensure that the (+) and (-) of the batteries are correctly fitted. Replace the lid by sliding it back into the right position.
Use 2 LR03 AAA (1.5 volts) batteries. Do not use rechargeable batteries. Replace the batteries with new ones of the same type when the screen becomes vague.
Point the remote to the wired remote control to control the air conditioner. The remote control can operate the wired remote up to 8 m distance, if it is directed towards the receiver of the wire-wired remote.

T IMER O FF S ET T IMER A
24 k, 36 k, 42 k, 48 k, 60 k
Remote control · Usage


Each time the stand button is pressed, the operating condition changes in order:
The heating mode is not available for air conditioners that can only cool.
Each time the VENTILATOR button is pressed, the fan speed changes in order:
In the stand ONLY VENTILATE are only "High, Gem. and Low" available. In the DROGEN mode, the fan speed is automatically on Autom. set, the VENTILATOR button does not work in this case.
Press once to increase temperature setting by 1 °C
Press once to lower the temperature setting by 1 °C
NOTE: The heating mode is not available for models that can only cool.

Press the button, once the unit receives the signal, the inner unit will be switched on.
The positions SHOW, SLIM, TIMER ON, TIMEER OFF, SLEEP, KLOCK and SUPER are explained on the following pages.
When changing the position while the unit is working, it does not always react immediately. Then wait three minutes. In the heating mode, air will not flow directly from the unit. After 2-5 minutes, the air flow starts when the temperature of the heat exchanger has risen. Always wait 3 minutes before restarting the device.
Operating conditions

Control of the direction of airflow
Control of the direction of airflow

The vertical airflow is automatically adjusted to a certain angle depending on the operating state after the unit has been switched on.

The direction of the airflow can also be adjusted to your own requirements by pressing the SWING button on the remote control.
OFF
COOLING, DRYING
SUPER
SMART
*HEAT ONLY VENT.
TIMER ON
SWING
TIMER OFF
SLEEP
SWING
CLOCK
I FEEL
*The heating mode is only available for heat pump models.
Control of vertical airflow (with remote control)
Use the remote control to set alternate angles or, if desired, certain current corners.
By pressing the SWING button, the horizontal air valve will automatically swivel up and down.
By pressing the SWING button again, the air valve will swivel to the desired angle.
Do not adjust the horizontal valve manually, otherwise a malfunction may occur. If this occurs, you must turn off the unit first, then restore power supply and then restore the power supply.
It is better not to hold the horizontal air valve in its downward position for too long during the positions COELEN or DROGEN, to prevent the dripping of condensation.

Press the SLIM button and the unit will start the SlimME mode (fuzzy logic control) directly, whether on or off. In this mode, the temperature and fan speed are automatically set based on actual room temperature.

The SLIM button is not active in the SUPER mode. NOTE: Temperature, airflow and direction are automatically controlled in the SLIMME mode. However, the remote control can set a reduction or increase of 7 °C if you are not feeling comfortable yet.

Fan speed changes between high, gem. and down, every time the button is pressed.
Pressure once, the horizontal air valve swells to change the direction of the airflow. Press again and the swing stops.
The actual time can be changed by pressing the KLOK button and then using the and buttons for the right time. Press KLOK again and the time is set.
SLIMME mode

It is very useful to set the timer with the TIMER ON buttons when you leave in the morning, so that at home a comfortable room temperature can be reached. You can also turn off the timer at night to enjoy a good night's sleep with the TIMER OFF button.
The TIMER ON button can be used to set the timer programming as desired, so that the unit is enabled at your preferred time.
Press the TIMER ON button, "12:00 ON" flashes on the LCD screen, then press or select your desired enable time.
Press the button once to increase or decrease time by 1 minute. Press the or button for one and a half seconds to increase or decrease time settings by 10 minutes. Press the button or push for a longer time to increase or decrease the timing by 1 hour.
NOTE: If you do not set the time within 10 seconds after pressing the TIMER ON button, the remote control will automatically exit the TIMEr ON mode.
Once the desired time is displayed on the LCD screen, press the TIMER ON button to confirm it. There's a beeping sound. "ON" stops blinking. The TIMER view on the inner unit lights up.
After the set timer is shown for 5 seconds, the time will be displayed on the LCD screen of the remote control instead of. the set timer.
Press the TIMER ON button again, a beep clicks and the view disappears as a sign that TIMER is disabled.
NOTE: Setting TIMER OFF goes the same way. This allows you to automatically disable the unit at your desired time.


The SLEEP mode can be set at the positions COOL, HEAR, DROGEN or SLIM. The function ensures a more comfortable environment during sleep. In SLAP mode:
will stop the unit automatically after it has been working for 8 hours.
NOTE: The heating mode is not available for air conditioners that can only cool.
The SUPER mode is used to quickly switch on or off cooling. Fast cooling works with a high fan speed, automatically changing the set temperature to 18 °C.


The SUPER mode can be set when the device is working or on.
In the SUPER mode, you can adjust the direction of the airflow or timer. If you want to disable the SUPER mode, press one of the following buttons: SUPER, STAND, VENTILATE, ON/OFF or TEMPERATURE INSTITUTION.
SMART
FAN MODE
TIMER ON
SWING
TIMER OFF
SLEEP
CLOCK
I FEEL
NOTE: The SLEEP and SLIM buttons are not available in SUPER mode. The SUPER button is not active in the HEAR position. The device will continue to operate in SUPER mode with a set temperature of 18 °C if you do not break it down by pressing one of the buttons specified above.
SLEEP mode · SUPER mode ·Super mode

5. Before commissioning
Connect the power to the system about 12 hours before startup after a long period of standstill. The system shall not be restarted immediately after the power supply is connected. This can cause a malfunction in the compressor, because the compressor is not properly heated. Make sure the outside unit is not covered with snow or ice. If the unit is covered, you can remove it with hot water (± 50 °C). If the water temperature is higher than 50 °C, this can cause damage to plastic parts. If the system is restarted after a period of standstill for more than about three months, it is recommended that the system be monitored by a service company. Turn off the main switch if the system is switched off for a longer time. If the main switch is not switched off, it will continue to consume electricity because the oil heater will always work after the compressor has stopped.
3 minutes of protection after a stop from the compressor. To protect the compressor, after a stop the compressor cannot be switched on for at least 3 minutes. Five minutes of protection. The compressor must operate at least 5 minutes after it is switched on. In these 5 minutes, the compressor will not stop even if the room temperature has reached its set value unless you switch off the unit using the remote control (all units disabled by the user). Cooling function. In the cooling mode, temperature can be set between 18-32 °C. The fan of the inner unit will never stop working. It's gonna keep working even if the compressor stops. Heating function. Because the air conditioner heats through outdoor thermal extraction (with the heat pump), heating capacity can be reduced if the outside temperature is too low. If the effect of heating is not sufficient, an additional heater shall be used. Anti-freeze function in cooling. If the temperature of the air outlet in the inner unit is too low, it will work with only the fan for some time to prevent freezing or ice forming inside the heat exchanger. Prevention of cold air. The fan of the internal unit will not rotate for a few minutes after heating is switched on until the heat exchanger of the inner unit has reached an adequate temperature. The system to prevent a cold air flow is then in operation. De-shooting. If the outside temperature is too low, freezing or ice formation can occur in the heat exchanger outside which reduces heating performance. The air conditioner defrosting system will then enter into force. At the same time, the fan of the indoor unit (or in some cases runs at very low speed) stops and when a few minutes later the defrosting is ready, the heating will start again. Blowing out of residual heating air. If the air conditioner stops working normally, the fan engine will run at low speed for a while to blow out the remaining air. Self-recover after power failure If the power supply is restored following a malfunction, all settings are still active and the air conditioner works according to original settings.
Wired remote control: If the ZWENKEN button is pressed for 3 seconds, the valve starts to work. The swirling of the valve stops when the ZWENKEN button is pressed for another 3 seconds. Wireless remote control: When the ZWENKEN button is pressed, the valve starts to work. The swirling of the valve stops when the ZWENKEN button is pressed again.
Do not turn the air valve manually. If you do, the mechanism of the valve may be damaged.

8. Filter Cleaning
Do not let the system operate without an air filter so that the heat exchanger of the inner unit is not highly polluted. Turn off the main switch before removing the filter. (The last position appears again when turning on.)
8.1 Setting of the interval for cleaning filter

18 k 24 k, 36 k, 42 k, 48 k, 60 k
8.2 Taking out the filter Take out the air filter according to the following steps. Step 1 Open the air intake grid by pressing the two buttons as indicated in the arrows. Step 2 Take out the air filter from the air intake grid by holding the grate and lifting the filter after it has been detached from the hinges.


18 k 24 k, 36 k, 42 k, 48 k, 60 k
Filter

8.3 Cleaning the filter
Clean the air filter according to the following steps.
Step 1 Use a vacuum cleaner or rinse the filter with water to remove dirt from the air filter.
Do not use water warmer than approximately 40 °C.
Step 2 Dry the filter in the shade after shaking off moisture.
8.4 Reset View Filter
Press the emergency switch after the air filter has been cleaned. The display of FILTER disappears and the next period before cleaning is set.
If the drainage water in the inner unit is flooded, stop the unit and contact your supplier. If you smell white smoke or see it coming out of the unit, turn off your power supply and contact your supplier.
9.1 If problems persist. If problems persist after you have checked the following, please contact your supplier and provide the following information. (1) Model name unit (2) Description of the problem.
9.2 No action
Check that SET TEMP is set to the right temperature.
9.3 No good cooling or heating
Check that the air flow of external or internal units is blocked. Check that there is an additional heat source in the room. Check that the air filter is highly contaminated with dust. Check if windows and doors are open or not. Check that the temperature conditions are outside the scope of operation.
9.4 This is very normal
Scent from the inner unit After a longer period of time, an odour can be separated by the inside unit. Then clean the air filter and panels or let it ventilate properly. Sound due to distortion of parts During the startup or stop of the system, a abrasive sound can be heard. This is due to the thermal deformation of plastic parts. It's perfectly normal. Steam from the heat exchanger of the outer unit During thawing, ice is melted on the heat-exchanger of an external unit and thus steam is generated. Air vent condensation If cooled for a longer period of time under conditions with high humidity (higher than 27 °C/80% RV), condensation can form on the air grid. Sound flow coolant During the start-up or stopping of the system, a sound can be heard from the flow of the coolant.

1. Flow diagram coolant

Note: The EEV only applies to the DC inverter air conditioner, use for other air conditioners a fixed expansion valve. The accumulator only applies to the 48 k and 60 k air conditioners. The 4-way valve is only applicable for a heat pump air conditioner.
DC inverter integrated model:
On/off integrated model:
N
SI
SI
N N
N
N
Power supply 18 k/24 k/36 k
Cable power supply Cable electricity supply
N
SI
SI
N
N
SI
SI
W
U
N
N
48 k/60 k Inside unit
Integrated model only cooling
N
SI
SI
W
N N
U
N
N
36 k/42 k/48 k/60 k

water leakage, electric shocks or fire cause.) Install the unit according to instructions in this manual. (Incomplete installation can cause water leakage, electric shocks, or fire.) Use only the standard included or specified installation components. (Use of other components can cause the unit to break down, water leakage, electric shocks or fire.) Install the air conditioner on a solid base that can carry the weight of the unit. (An unsuitable substrate or faulty installation may cause injury if the unit falls.) Electrical work must be carried out in accordance with the installation manual and local regulations and guidelines for electrical wiring. (Insufficient capacity or inadequate electrical work can cause electric shocks or fire.) Make sure to use a separate electrical group. (Never use a shared power supply with another device.) Use for the wiring a cable long enough to last all length without connecting and do not use an extension cord. Do not connect any other load on the power supply, use a separate group. (If you do not, this may lead to abnormal heat development, electric shocks or fire.) Use the required types of wiring for electrical connections between indoor and outdoor units. (Connect the connecting wires firmly so that there is no external voltage on the connection blocks.) Inappropriate fitting or clamping can result in overheating of the connector block or fire. After connecting connections and the power cable, they shall be securely secured so that no forces are applied to the covers or electrical panels. (Install a wire cover, incorrect installation of this can cause overheating of the connection block, electric shocks or fire.) No other substances such as air may enter the cooling circuit when installed or moved (see type plate). (The presence of air or other undesirable substances in the cooling circuit causes an abnormal pressure increase or break, which can cause injury.) If coolant has leaked during installation work, space must be ventilated. (The coolant produces a toxic gas when exposed to flames.) When the entire installation is ready, it must be checked that no coolant leaks. (The coolant produces a toxic gas when exposed to flames.) When connecting the pipes, make sure that no air or other substances than the declared coolant enter the cooling circuit. (Otherwise this can reduce capacity, cause abnormally high pressure in the cooling circuit, explosion or injury.) Make sure to make a grounding. Do not connect the ground to a utility line, lightning distraction or phone earthing. Incorrect earthing can cause electrical shocks. (A high peak current due to lightning or other causes can cause damage to the air conditioner.) Depending on local conditions, an earth leak switch may be necessary to avoid electric shocks. (If you do not, this may lead to electric shocks.) Shut down the power supply before connecting the wiring or pipes or checking the unit. If the internal and external unit is moved, ensure that the outer unit is not tilted by more than 45°. Make sure you do not suffer any injury due to the sharp edge of the air conditioner. Install the remote. Make sure that the length of the wiring between inside unit and remote control is less than 50 m.
Do not install the air conditioner in a place where there is a risk of exposure to flammable gases. (If gas leaks and collects around the device, this can cause fire. Install the drains according to instructions in this manual. (Incorrect pipes can cause water pollution.) Turn the nuts on with a torque wrench in accordance with the prescribed procedure. (If the screw nut is tightened too tight, it may break over time and cause leakage of coolant.)

3. Installation of the internal unit
Do not install the indoor unit in an environment with light flammable substances to avoid fire or explosion.
Make sure the ceiling is strong enough. If it's not strong enough, the inner units can fall down. Do not install the indoor unit outside. If installed outside, there may be an electrical hazard or leaks.

3.1 The first check
Install the inner unit with sufficient space around it for operation and maintenance, as indicated in Fig. 3.1. Make a maintenance hatch in the ceiling at the mains connections on the unit. Check that the ceiling is sufficiently strong to hang on the inner unit. Check that the ceiling surface is flat enough for installation work.

500 mm min.
100 mm min.
Silk of connection pipes
1000 mm min. 100 mm min.
500 mm min.
Fig. 3.1 Space around the inner unit
Choose the installation location as shown in Fig. 3.2: (A) Minimum space (B) Detachment from the drain line: 1:25~ 1:100

Free space 10 to 20 mm
H height unit in lowered ceiling
24 k,36 k 248
42 k, 60 k 48 k, 298
Debris 1:25 to 1:100
Fig. 3.2 Place of installation inside unit
View the air distribution of the interior unit to space and choose a suitable location, so that an even air temperature can be achieved in the room. It is recommended to install the inner unit at an altitude of 2.3 to 3 m from floor level. If the unit is installed above 3 m, it is also recommended to increase fan speed setting or use a 3-way air outlet component (option) so that even air distribution is ensured. Do not apply light flammable components in the interior unit maintenance room. Avoid any obstacles that may disturb the air intake or flowing air.

Do not install the interior unit in a machine workshop or kitchen where oil vapours or oil mist can flow to the inside unit. The oil then falls down on the heat exchanger, reducing the performance of the inner unit and deforming or even breaking the plastic parts of the internal unit. Pay attention to the following points as the indoor unit is installed in a hospital or other building, where there are electronic waves of medical equipment, etc. • (A) Do not install the unit in a place where electromagnetic waves are directly transmitted towards the electric box or cable or switch of the remote control. (B) Install the inner unit and components as far as possible but at least 3 m away from the source of electromagnetic waves. (C) Make a steel box to mount the remote control switch. Apply a steel pipe to allow the cable of the remote control to run. Also connect the earth wire to the box and pipe. (D) Install a sound filter when the power supply emits disturbing noises. In order to avoid corrosion of the heat exchanger, the internal unit shall not be installed in an acidic or alkaline environment. If an internal unit is to be installed in a device with such environmental conditions, it is recommended that the corrosion-free type be used.
Check that the factor shown below is less than 0,3 kg/cm3. Otherwise, a dangerous situation may arise if the coolant of the outer unit leaks into the space where the inner unit is installed.
(Total amount of coolant per external unit)
(Volume of the space where the internal unit is installed) ≤ 0,3 kg/m3
For more details see the installation manual of the outdoor unit.
● · ● · ●

3.2 Installation (24 k, 36 k, 42 k, 48 k, 60k) 3.2.1 Sparing in suspended ceiling and hanging bolts. (1) Determine the final location and direction of installation of the interior unit, carefully considering the space required for pipes, wiring and maintenance. (2) Make the savings for the inner unit in the suspended ceiling and install the hanging bolts as shown in Fig. 3.3.

840 (m unit in mm) 760 dimensions of hanging bolts 4 positions of hanging bolt
Side connection pipes side connection drain pipe
Fig. 3.3 Sparing in suspended ceiling and hanging bolts
(3) Check that the ceiling is level, otherwise the drain cannot properly drain. (4) Strengthen the edges of the saving in the suspended ceiling. (5) Install the hanging bolts as shown in Figure 3.4 below.
For concrete For steel beam
150 to 160 mm Plug (100-150 kg)
Fig. 3.4 Mounting hanging bolts
3.2.2 Installation position of the inner unit
measures in mm sizes in mm


127 (see section) Liquid line)
* Indicates the size of the underside of the interior unit and the ceiling surface.
Fig. 3.5 Confirmation position Fig. 3.6 Inner unit and air vent

3.2.3 Assembly of the inner unit
(1) Mount the nuts and tails on the hanging bolts.
*tracking ring with insulation (accessory)
hanging bracket (confirmed to unit)
*Support the railings so that the surface is facing downwards with insulation.
Fig. 3.7 Mounting of nuts and following rings
(2) Lift the inner unit with a hoist and ensure that no force is applied to the condensate container. (3) Attach the inner unit with nuts and tracking rings.
Fig. 3.8 Suspension of the inner unit
NOTE: If the suspended ceiling is already installed, all pipe and wiring work in the ceiling must be completed before hanging up the interior unit.
3.2.4 Adjust the space between the inner unit and the saving in the suspended ceiling.
Check that the condensate collection bin is level-of-peas so as to avoid malfunctioning of the discharge mechanism in the inner unit. The side of the inner unit with the drain shall be approximately 5 mm lower than the other side. Turn the nuts of the hanging brackets as soon as the adjustment is complete. Apply Loctite* to the bolts and nuts to prevent loosening. If you do not, abnormal sounds may occur and the unit may fall down.
Loctite*: Treat the bolts and locking nuts. Adjust the inner unit to its correct position and check it using the control mal (supplied).
(1) The cartridge for the installation is printed on the packaging. Cut the control mould of the packing for measuring the sparring. (2) Adjust the position of the inner unit with the control mal, as shown below.

10 to 35 10 to35
controlmal for measuring sparing
Cardboard with cartridge for installation
surface of flange inside unit (seen from below)
a. For a ceiling already filled with panels
Cardboard with cartridge for installation
size sparring measuring sparing
Attach the mould to the bottom of the unit
Attach the mould to the ceiling surface
Adjust the height of each corner of the unit to the ceiling
controlmal for measuring sparing
Check the sparring size on all sides
Cardboard with cartridge for installation
b. For a ceiling not yet filled with panels
The details of the installation work for the air vents shall be carried out according to the relevant air grate installation manual. Make sure that the connection of the inner unit and air vent is properly performed.

3.3.1 Location for the installation of the internal unit
Install in a place where there is no obstruction at the air outlet and air can be easily blown to any angle.
Where the drain can run above the ceiling to the other side of the wall. It is recommended to make a special disposal option.
Where the ceiling is strong enough to carry the weight of the interior unit and the strengthening of sound and vibrations is prevented.
More than 1000 mm
Keep the required space from the unit to the ceiling, floor and walls as shown in the image on the right.
Do not install anything near the air intake grate so that the air suction is not obstructed.
Keep the unit and remote control 1 m away from television and radio, etc. Keep the unit at least 1.5 m away from fluorescent lamps to prevent malfunctions.

The maximum length of the connecting line between inside and outside unit is 15 m and the maximum height difference between units is 7.5 m.
Avoid installation in places with greasy dirt or where steam is.
3.3.2 Height of ceiling panels
Normally, the ceiling plates are placed 23,5 m above the floor.
3.3.3 Installation inside unit
Measure the distance H between the base floor and the ceiling plate;
Take four hanging rods with M10 thread on both sides, as shown in the picture below (drawn with rod Ø 10).
Value of L and L1 is calculated as shown below: L1= 50 mm (if H
L= 1,5L1 + H -230 (in mm)
Turn the four nuts provided on the wire ends of the hanging rods as shown below:

Take the cardboard mould from the inner unit packaging. Do not fold the mould and use it to determine the location and direction of installation of the unit against the upper structure and in the ceiling. Press the mould firmly against the upper construction, draw out the position of holes for the keilbolten with a pencil, remove the mold and drill 8 holes for keilbotuten. The holes must be so deep that the thread of the rods is visible.
Make a spare (AxB) in the ceiling plate using the mould and make sure that the same direction of bolts is held as in the construction. Work the edges of the sparring with the aluminium U-profiles.
18 k A B Model
Mount the supplied hanging brackets with kerb bolts M8x50 against the upper structure. Make sure the keilbolten and nuts are securely attached. The open side of the hanging brackets shall be on the outside as indicated below.
Take the hanging rods with a nut at the end, insert them through the hole of the suspension bracket and turn nuts with tracking rings attached to the top of the hanger brackets.
Attach the unit to the suspension rods with the supplied nuts and tracking rings. The nuts on the bottom should be about halfway through the thread. (Please note: this should be done with at least two persons.)
Adjust the nuts at the bottom of the hanging rods so that the underside of the unit is 8-13 mm higher than the ceiling plate (as indicated above). Then adjust the corners of the bottom horizontally with a level. (The flatness must be within the range of 1:100.)


4.1 The first check The external unit must be stored in a well ventilated and dry place. Make sure the sound and air exhaust won't disturb your neighbors. Never install the outdoor unit in a place where an oil mist, salt fog or harmful gas can occur, such as steam with sulfur. Install at least 3 m away from a radiation source. Install a snow cover above the inside and outlet of the outdoor unit when installed in cold environments. Install the device in a sheltered place so that direct sunlight and high temperatures are prevented by radiation. Do not install the device in a place where dust or dirt can block the heat exchanger. Do not install the device in an easily accessible location. Do not install the device in a place where rain and wind between buildings are directly directed to the fan.
The fan can be damaged by strong winds directly directed to the part of the outer unit with the heat exchanger. Be careful with the aluminum fins, these are sharp. Only the maintenance service may handle the outside unit.
4.2 Installation (1) Use the included tracking rings to secure the device on the anchor bolts. (2) Apply the anchor bolts for attachment of the outer unit according to position as shown in Fig. 4.1 indicated. (3) Confirm the outer unit as shown in Fig. 4.2. (4) Make sure that the outer unit is securely and horizontally fixed so as not to be oblique by strong storms or earthquakes. (5) Do not drain the water to walkable areas in order to prevent slipping.


Shortly cut the bolts if they are too long, because this may cause problems in future when moving.
concrete anchor bolt (Size in mm)
Fig. 4.1 The position of the anchoring bolts Fig. 4.2 Installation of anchoring bolts
New DC inverter integrated air conditioner (high-efficiency model)
A B C D E F d 18 k 898 295 580 320 345 135 12 24 k, 36 k 948 338 580 378 413 159 15
DC inverter integrated air conditioner ON/OFF integrated air conditioning Only cooling air conditioners
A B C D E F d 18 k 798 255 608 290 316 71 12 24 k 898 295 580 320 345 135 12 36 k, 42 k, 48 k, 60 k 948 338 580 378 413 159 15

4.3 Length of guidance between indoor and outdoor units
Touv. coolant (above 5 m)
Max. Line length (L) Model
Max. Height Difference (H)
15 m 7,5 m 15 g/m
20 m 10 m 35 g/m
30 m 15 m 35 g/m
42 k, 48 k, 60 k
50 m 15 m 35 g/m
*For 24 k high-efficiency DC inverter model: Guide length between indoor and outdoor units is equal to the 36 k models.
Fig. 4.3
If the total length of pipe between 5 and 50 m (max. The length of the test is equal to or greater than 1 mm. There is no need to add extra compressor oil. (pict. 4.3)
Addition:
For 24 k/36 k/42 k/48 k/60 k Xg = 35 g/m1 x (total line length -5 m)

Use the coolant R22 or R410A in the cooling circuit (see external unit type plate). For the purpose of a leakage test or air density test, the cooling circuit shall never be filled with oxygen, acetylene or other flammable and toxic gases. These types of gases are very dangerous and can cause an explosion. It is recommended to use compressed air, nitrogen or coolant for these tests.
5.1 Materials for pipes (1) Prepare the copper lines purchased locally. (2) Determine the pipe diameter with the following table.
18 k Ø 12.7 mm
24 k/ 36 k Ø 15,88 mm
Ø 9,52 mm 42 k/ 48 k/60 k
(3) Use clean copper pipes. Make sure there's no dust and moisture in the pipe. Blow the pipes on the inside with nitrogen or dry air to remove dust or other undesirable substances before they are connected.
5.2 Connections of the pipes (1) The position of the connections to the pipes is shown in Fig. 5.1 (inside unit).

24 k, 36 k, 42 k, 48 k, 60 k
Fig. 5.1 Position of connection lines
(2) Turn the nuts with two wrenches, as in Fig. 5.2 is indicated.
Fig. 5.2 Folding nuts

(3) After connecting the cooling pipes, apply the supplied insulation material to the refrigeration lines as indicated in Fig. 5.3.
Insulation for cooling line (supplied)
Side of the unit
Insulation for cooling line (supplied)
Fig. 5.3 Insulation to pipes
Slide a cap at the end of the pipe if it is to be fed through a spar. Do not put the pipes directly on the floor without a cap or vinyl tape over the end.
(4) Tap or refill of coolant shall be carried out as described in the "Installation & Maintenance Manual" of the external unit.

Make sure that there is no counter-shot in the drain line, as water can then flow back to the inside unit and leak into space when the system is switched off. Do not connect the drain to a sewage pipe or another drainage line. If the drain is connected to multiple internal units, each unit's connection position shall be higher than the discharge line and the diameter of the pipe must be sufficient for the number and size of the units. After the pipework and electrical wiring are performed, check that water is well discharged with the following procedure. Control with the float switch: (1) Turn on power supply. (2) Pour 1.8 litres of water into the condensate container. (3) Check that the water flows evenly and no water leaks. If no water is seen at the end of the drain, another 1.8 litres of water shall be poured into the drain. (4) Turn on the power supply and press the ON/OFF button.
If water is poured through the access hatch
Insert the hose between the heat exchanger and the condensate container
water (2000 to 2500 cc)
If water is poured through the air outlet
Insert the hose between the heat exchanger and the condensate container
water (2000 to 2500 cc)

(1) The position of the outlet connection is shown in Fig. 6.1.
Fig. 6.1 Position of the outlet
(2) Take a PVC pipe with an external diameter of 32 mm. (3) Attach the pipe to the drain hose with glue and the supplied hose clamp. The drain pipe shall be run with a discharge of 1:25 to 1:100.
increasing part of the counter-shot hose clamp (accessory) a (300 mm max.) c (50 mm max)

850 mm max.
Extinguish 1:25 to 1:100
drain hose (accessory) connection drainage line
PVC VP25 (third party supply)
drain pipe This drainage line shall not be connected to another pipeline
*The total length of a + b + c must be less than 1100 mm. If the drain pipe is to be raised at the connection, the pipeline shall be carried out as indicated above. (4) Isolate the drain pipe after connection to the drain hose.
Fig. 6.2 Drainage

Turn off the main switch from current to inside and outside unit before electrical wiring or periodic check-up operations are performed. Check that the fan has stopped inside and outside before electrical wiring or periodic checking is performed. Protect the wiring, drain line, electrical parts etc. against rats and other small animals. If it is not protected, rats could gnaw on unprotected parts and even start a fire. Check the points mentioned below before turning on the main switch. Fasten the screws with the following moment: M3,5: 1,2 Nm M5: 2,0~2,4 Nm
Wrap the wiring with the supplied material and close the wired saving device with the sealing material to protect it from condensation or insects. Attach the wiring firmly with the cable clamp in the inner unit. Secure the remote control wiring firmly with the cable clamp in the electric box.
7.1 General control
1) Ensure that the electrical components installed on site (main switches, fuses, wiring, connection connections and connecting blocks) are correctly selected in accordance with the electrical specifications as specified in "Technical Manual I." Make sure the components meet national standards. (2) Check that the voltage of the power supply is within ± 10% of the rated voltage. (3) Check the electrical wiring capacity. If the power supply is too low, the system cannot be started due to the loss of voltage. (4) Check that the earth wire is connected. (5) Main switch power supply - Install a multi-pole main switch with an opening of 3,5 mm or more between each phase.

7.2 Connection of electrical wiring
The connection of the electrical wiring of the inner unit is shown in Fig. 7.1. For the intermediate connection between the inner unit and the air vent, see "Air Grid Installation Manual." (1) Connect the cable of an optional remote control switch or optional extension cord via the connecting spare in the enclosure to the connections of the circuit board in the electrical box. (2) Connect the power supply and earth wires to the connection block in the electrical box. (3) Connect the wiring between inside and outside unit to the connection block in the electrical box.
wiring power supply wiring control cable remote control
Ø 32,5 (as reserve) connection saving
30x39 connection savings (for cable)
*Minimum wire diameters for power supply: see chapter 9. General.
wiring power supply wiring control cable remote control

Connection of wired remote control (optional part)
Fig. 7.1 Connection of electrical wiring for indoor unit

Only after all checkpoints have been checked can the unit be put into operation. (1) Check that the resistance of the connection to earth is more than 1 MΩ, otherwise you cannot use the unit until the point where electricity leaks has been found and repaired. (2) Check that the valve is open before using the unit. (3) Make sure that the electrical current is switched on 6 hours before the unit is switched ON.
Make sure the power and unit run properly, then switch on. Turn the device on and set it to cooling or heating depending on room temperature. Set the temperature to 18 °C for cooling mode and 32 °C to heat mode. Check that the device is working properly. The installation of the device is usually completed when the above points are executed. If you have any problems, please contact your local technical maintenance service or for more information.
Note the following when the system is running. (1) Do not touch any of the components from the gas outlet side manually, as the compressor chamber and drain pipe are heated to a temperature above 90 °C. (2) DO NOT PRESS THE BUTTON OF THE MAGNETIC SWITCH(S). This could cause a serious accident. (3) Use the remote control for operation and check that room temperature and positions are working properly. After the test, turn off the electrical current.

Use an earth leak switch, otherwise this can cause electric shock or fire. Do not use the system until all checkpoints are resolved. (1) Check that the insulation resistance is more than 1 MΩ by measuring the resistance between earth and electrical components. If not, the system should not be switched on until the point where electricity leaks has been found and repaired. (2) Check that the valves of the outside unit are fully open and then start up the system. Note the following when the system is running. (1) Do not touch any of the components from the gas outlet side manually, as the compressor chamber and drain pipe are heated to a temperature above 90 °C. (2) DO NOT PRESS THE BUTTON OF THE MAGNETIC SWITCH(S). This could cause a serious accident.
Power supply EN60 335-1 EN60 3351
dimensions of power cable off. Control cable
18 k (Integrated model only cooling) 18 k
220~240 V, 50 Hz 220~240 V, 50 Hz 3x1,5 mm2
3x1,5 mm2 5x1,5mm2 4x1,5m2
18 k (DC inverter integrated model) 18 k
220~240 V, 50 Hz
24 k 36 k (DC inverter integrated model) 36 k
220~240 V, 50 Hz
36 k (On/off integrated model)
380~418 V, 50 Hz
5x2,5mm2 5x1,5mm2
42 k/48 k/60 k
380~418 V, 50 Hz
NOTES: 1) Follow local standards and regulations when choosing the wiring. 2) The dimensions of the wiring specified in the table are determined at maximum flow rate for the unit according to European standard EN60 335-1. Use cables that are not lighter than the normal flexible cable with hard rubber mantle or regular flexible cable using polychloroprene coat (type H05RN-F). 3) Use a shielded cable for the transmitter cable and connect it to the ground. 4) If power cables are connected in series, the maximum current of each unit must be added together and then the cable is selected from the table below.
Selection according to EN60 335-1 Current i (A) Wire size (mm2)
*If the current exceeds 63A, cables must not be switched in series. 5) To comply with the standard EN 61000-3-11, the system must be connected to a power supply with an impedance of: .Zsys≤0.247 Ω (for 18 k On\From integrated model) . Zsys =0,209 Ω ("for 24 k On" from integrated model). Before connecting the product to the public electricity grid, check with local energy companies if the network meets the above requirements.

PACKAGING LIST
No. NAME NUMBER
INSIDE UNIT
INSIDE ACCESSORIES
MANUAL
PANEL
WIRED REMOTE CONTROL
MODEL: AUC-18HR4SUAA AUC-24HR4 SZGA AUC-36HR6SAGA
AUC-42CR6FEHA
AUC-48HR6SPHA AUC-60HR6SPHA AUC-18UR4SZAA1 AUC-24UR4SAEA1 AUC-36UR4SAEA1 AUC-18CR4FUAA
PACKAGING LIST
No. NAME NUMBER
INSIDE UNIT
INSIDE ACCESSORIES
MANUAL
PANEL
WIRED REMOTE CONTROL
Correct removal of this product.
This indication indicates that this product must not be disposed of with ordinary household waste throughout the EU. In order to prevent damage to the environment or health caused by uncontrolled waste disposal, it should be recycled responsibly and promote sustainable reuse of materials. Return the used device by using return and collection systems or contact the dealer where the product was purchased. They can recycle this product in an environmentally friendly way.
Climate Solutions B. V. Exclusive Hisense Importer Benelux
HS Climate Solutions B. V. Carnelian 400 3316 KC Dordrecht
e. [email protected] w. www.hs-cs.nl t. 088-4355450 f. 088-4355451
SK No 60753986 IBAN No EN92ABNA0443804362 VAT NO. EN854044954B01
Version number 20150101-EN The design and specifications can be changed without further notice. Images and diagrams are for information purposes only, and may be modified without further notice.