Faber Triple Premium M

24 pages·3.3 MB·Fireplace·PDF·ENDEFRITNLJA
Faber Triple Premium M
Table of Contents 38 sections Triple Premium M · NL NL · Installation instructions · 1.3 1.4 · … ShowHide
Page 1 of the Faber Triple Premium M user manual — NL NL
Page 1 · click to enlarge
Page 1

Triple Premium M

Faber Triple Premium M — Triple Premium M diagram (page 1)
Fig. 1 · Triple Premium M
Faber Triple Premium M — Triple Premium M diagram (page 1)
Fig. 2 · Triple Premium M

NL NL

Installation instructions

Faber Triple Premium M — NL NL diagram (page 1)
Fig. 3

40011403-1301

Page 2 of the Faber Triple Premium M user manual — 1.5 1.6
Page 2 · click to enlarge
Page 2
Faber Triple Premium M — 1.3 1.4 diagram (page 2)
Fig. 4
Faber Triple Premium M — 1.3 1.4 diagram (page 2)
Fig. 5

1.1 1.2

Faber Triple Premium M — 1.3 1.4 diagram (page 2)
Fig. 6
Faber Triple Premium M — 1.3 1.4 diagram (page 2)
Fig. 7

1.3 1.4

Faber Triple Premium M — 1.3 1.4 diagram (page 2)
Fig. 8
Faber Triple Premium M — 1.3 1.4 diagram (page 2)
Fig. 9

1.5 1.6

1 <

Page 3 of the Faber Triple Premium M user manual — 2.4 2.5
Page 3 · click to enlarge
Page 3
Faber Triple Premium M — 1.7 1.8 diagram (page 3)
Fig. 10
Faber Triple Premium M — 1.7 1.8 diagram (page 3)
Fig. 11

1.7 1.8

Faber Triple Premium M — 1.7 1.8 diagram (page 3)
Fig. 12
Faber Triple Premium M — 1.7 1.8 diagram (page 3)
Fig. 13
Faber Triple Premium M — 1.7 1.8 diagram (page 3)
Fig. 14

A

B

2.2 2.3

Faber Triple Premium M — A diagram (page 3)
Fig. 15
Faber Triple Premium M — A diagram (page 3)
Fig. 16

2.4 2.5

2 <

Page 4 of the Faber Triple Premium M user manual — 3.0 3.1
Page 4 · click to enlarge
Page 4
Faber Triple Premium M — 2.6 2.7 diagram (page 4)
Fig. 17
Faber Triple Premium M — 2.6 2.7 diagram (page 4)
Fig. 18

2.6 2.7

Faber Triple Premium M — 2.6 2.7 diagram (page 4)
Fig. 19
Faber Triple Premium M — 2.6 2.7 diagram (page 4)
Fig. 20

2.8 2.9

Faber Triple Premium M — 2.8 2.9 diagram (page 4)
Fig. 21
Faber Triple Premium M — 2.8 2.9 diagram (page 4)
Fig. 22

3.0 3.1

3 <

Page 5 of the Faber Triple Premium M user manual — A
Page 5 · click to enlarge
Page 5
Faber Triple Premium M — 3.2 3.3 diagram (page 5)
Fig. 23
Faber Triple Premium M — 3.2 3.3 diagram (page 5)
Fig. 24

3.2 3.3

Faber Triple Premium M — 3.2 3.3 diagram (page 5)
Fig. 25

A

4 <

Page 6 of the Faber Triple Premium M user manual — 5 <
Page 6 · click to enlarge
Page 6
Faber Triple Premium M — 5 < diagram (page 6)
Fig. 26
Faber Triple Premium M — 5 < diagram (page 6)
Fig. 27
Faber Triple Premium M — 5 < diagram (page 6)
Fig. 28
Faber Triple Premium M — 5 < diagram (page 6)
Fig. 29
Faber Triple Premium M — 5 < diagram (page 6)
Fig. 30

5 <

Page 7 of the Faber Triple Premium M user manual — 6 <
Page 7 · click to enlarge
Page 7

1 Introduction The fireplace may only be installed by a qualified installer/dealer. We strongly recommend that these installation instructions be read properly. This appliance complies with the guidelines for European Gas Appliances (GAD) and carries the CE marking. 2 Security notices. The apparatus must be installed and inspected annually in accordance with this installation requirement, as well as the applicable national and local requirements. Check that the data on the plate match the local gas type and pressure. The settings and the construction of the fireplace must not be changed! Do not place any extra imitation wood or glow material on the burner or in the combustion chamber. The device is for atmosphere and heating purposes. This means that all surfaces, including the glass, can become very hot (hotter than 100°C) except for this form the underside of the fireplace and control knobs. Do not place combustible materials within 0.5 m of the radiation part of the fireplace. The natural air circulation of the fireplace makes moisture and non-hardened volatile components from paint, building materials and floor coverings etc. sucked in. These constituents can be placed as soot on cold surfaces. Therefore, do not light the fireplace shortly after a renovation. The first time the fireplace lit a few hours at its highest stand, so that paint would have the chance to harden out. Ensure sufficient ventilation to remove any vapours released. We recommend that you be as little present in space as possible during this process. Please note:

2 children and pets are not present in the room. 3 Installation requirements

3.1 Fireplace

This device must be built into a new bosom to build. For flexible gas pipes, the control block is mounted on the right side of the fireplace for transport reasons. unscrew it and mount it at a distance of max. 30 cm behind the control hatch. The receiver in a transporter A (see fig. 4) is attached to the side of the control block support, can now be moved on top of the line block. The transporter can be omitted.

3.2 Booze

The bosom must be made of non-combustible material. The space above the fireplace should always be ventilated by means of: the grids or a similar alternative with minimum free passage of 200cm2 Use special decorative plaster for finishing (min. 100°C resistant) or glass fibre wallpaper for discoloration and cracks etc. to be avoided. Minimum drying time 24 hours per mm finish. The bosom structure shall not rest on the built-in frame of the fireplace.

3.3 Requirements for drainage channel and exits

For the supply and disposal you must always use the drainage materials prescribed by Faber International BV. Only with the use of these materials can Faber International BV guarantee a good working environment. The outer surface of the concentric drain material can be +/- 150°C. Provide through a flammable wall or ceiling

1 all transport containers have been removed.

6 <

Page 8 of the Faber Triple Premium M user manual — 7 <
Page 8 · click to enlarge
Page 8

insulation and protection structures. And keep a sufficient distance. Make sure that the concentric drain material is held every 2 metres at large discharge lengths, so that the weight of the material does not rest on the fireplace. You should never start on the device with a short-term concentric drain material

Clear a place, if you will. safe storage of list and glass. Delete if necessary the list and glass, and take the packed parts from the fireplace. Prepare the gas connection on the gas control block.

4.4 Installation of the fireplace Takes into account the Installation requirements (see Chapter 3)

4.4.1 Floor standing Set the device in place and adjust height with the struts if necessary. Adjust height and adjust the fireplace. (see Fig. 1.4)

3.4 Ends The combined supply and disposal can pass through both the façade and the roof. Check that the exit you want meets local requirements regarding discomfort and ventilation openings. For proper operation, the exit shall be at least 0,5m from: Angles of the building. Rooftops and balconies. Roof edges. (except the ridge edge) 4 Preparation and installation instruction

Large height adjustment:

o with the extendable leg, or with long legs supplied. Precisely:

o with the swivel-adjustable legs.

4.4.2 hanging on the wall The device can be attached to the wall by hanging. supplied suspension bracket (see Fig. 1.5

4.5 Mounting of flue gas drainage materials

In the case of a passage through the wall or ceiling, the hole shall be at least 5 mm larger than the diameter of the drain material. Horizontal sections should be installed on a bulkhead towards the fireplace (3 degrees). Build the system from the fireplace. If this is not possible, a sliding intersection can be used. The 1⁄2 meter short pipe is used to fit the drainage system. Always make sure the inner pipe is 2 cm longer than the outer pipe. The facade and roof throughput are also shortable. These parts need to be secured with a parking lot. A recessed flue gas drain can not isolate but ventilate. (approx. 100cm2)

4.1 Gas connection The gas connection must comply with the local standards. We recommend a gas connection of Ø 15mm directly from the gas meter to the device, with in close proximity to the appliance a shut-off valve which is always accessible. Position the gas connection so that it is easily accessible, and for service the burner unit can be dismantled at any time.

4.2 Electrical connection If an adapter is used for the power supply, a wall socket 230VAC .50Hz must be mounted near the fireplace.

4.3 Preparation of the fireplace

Remove the fireplace from its packaging. Please note that the gas supply lines underneath the device are not damaged.

7 <

Page 9 of the Faber Triple Premium M user manual — 8 <
Page 9 · click to enlarge
Page 9

6 Installation of decoration material It is not permitted to add other or more materials in the combustion chamber. Make sure the watch flame is not blocked by decoration material! Do not throw all decoration material on the burner at once; it may become blocked by the dust parts.

4.6 Build a bosom. Before the bosom is placed we recommend to perform a gas fire test as described in Chapter 7 .

4.7 Booze

Make the bosom of non-combustible sheet material in combination with metal profiles or brick/cell concrete blocks. Please take into account grids and control hatch (see Fig. 1.1 and 1.2). Place a screen panel A above the grids (see fig. 1.1) of non-combustible material. Always use a bosom iron when the boss is bricked. This must not be placed directly on the fireplace. 5 glasses

6.1 Wood set

Place part of the chips on the burner and bottom. Places the wood set as prescribed (see Fig. 3.1 or the wood set card) Divide the rest of the chips on the burner and bottom. Avoid a thick layer on the burner; this will affect the fire image. Start the fireplace, as described in the user manual. Assess if the flame distribution is correct. Place the glass plate and check the fire image.

5.1 Glass removal front

Remove the cover strips A on the side. (see Fig.2.2) Remove the cover strip B at the bottom. (see Fig. 2.2) Place the suction cups on the glass. (see Fig.2.5) Remove the seal cord from the sponge. (see Fig. 2.6) Slide the glass upwards so that the bottom is released from the sponge. Now gradually remove the glass and down. (see Fig. 2.7 to 2.8)

6.2 Gravels and Grey stone

Places the pebbles on the burner and bottom Avoid a double layer; this affects the fire image. (see Fig. 3.2 and 3.3) Place the glass plate and check the fire image. 7 Installation control.

7.1 Control of ignition flame, head burner. Light the fireplace as described in the user manual. Check the ignition of a watch flame Important: Make sure that the ignition cables are not tightly but loosely underneath the device, this is necessary for proper ignition. Always remove the tie wraps Check that the watch flame is well above the head burner and is not covered by chips, a wood block or pebbles. Check the ignition of the head burner for full and small position. (the ignition must be smooth and quiet).

5.2 Glass removal side There is no need to take the glass off at the side for placing the wood set or for performing maintenance.

First remove the foreglass. Remove wood set and base plate. 2.9) Place the suction cups on the glass. Remove the seal cord from the sponge. Remove the top of the glass gradually from and forwards from the fireplace (see Fig.3.0 - 3.3) Repositioning the glass is in reverse order. Remove all fingerprints on the glass, these will burn if the fireplace is used.

8 <

Page 10 of the Faber Triple Premium M user manual — 9 <
Page 10 · click to enlarge
Page 10

7.2 Gas leak control. Check with a gas leak seeker or spray all connections and connections for any gas leakages.

If you have a CO/CO2 flue gas analyzer, it is possible to control the combustion gases and supply air. For this, two measuring pipes are located at the front of the fireplace between the built-in frame and glass plate (fig.1.7A and B) The ratio of CO2 to CO should not exceed 1:100 example: CO2 is 4% and CO is 400ppm measured on high position Is the ratio greater than 1:100 or is discharge gases in the supply air measured therefore check above points. 8 Customer instruction Advise that the appliance must be checked annually by an approved installer to ensure safe use and long life Give advice and instructions on glass maintenance and cleaning. Emphasize the risk of burning in fingerprints. Inform the customer about how the device works and the remote control, including replacing batteries and adjusting the receiver. Handed to the customer: Installation instructions User's manual Wood set Instructions card Suction cups 9 Annual maintenance

7.3 Checking of burner pressure and prepressure Measurement of prepressure:

Turn off the device valve. Rotate the measuring nipple B (see Fig. 1.6) open some blows and connect a measuring hose to the gas control block. Take this measurement at full fireplace and when the fireplace is on a watchflame. If the pressure is too high, you must not connect the device. Measure burner pressure:

Check the burner pressure only at proper prepressure. Rotate the measuring nipple A (see Fig. 1.6) open some blows and connect a measuring hose to the gas control block. The pressure shall correspond to the value indicated in the technical description of this manual. (Chapter 14) By way of derogation, contact the manufacturer. *Close all pressure gauges and check for gas leakage.

7.4 Flame Image Control Let the fireplace burn for at least 20 minutes and then check the flame image on: 1. Flame distribution 2. Color of the flames If one or both points are not acceptable check then: The wood set arrangement and/or amount of chips or pebbles on the burner. The connections of the pipe material to leakage. (in case of blue flames). Whether the right thruster is mounted. The end of the line.

9.1 Control and cleaning:

Check and clean if necessary after check/measurement:

o The flame of the watch o The burner o The combustion chamber o The glass o The logs on ift. Fracture. O The exhaust.

o Wall throughput on the right side above and correct position o Roof throughput is in a proper position Whether maximum lengths of flue gas discharge have not been exceeded.

9.2 Replace:

o If necessary, the chips/embers. o With a Propane device, the Fiber Burner blanket

9 <

Page 11 of the Faber Triple Premium M user manual — 10 <
Page 11 · click to enlarge
Page 11

9.3 Cleaning the glass Most of the attack can be removed with a dry cloth. With ceramic hotplates cleanser you can get the glass clean. Please note: avoid fingerprints on the glass. These are no longer removable after burning in! Now perform the check as described in Chapter 7 . . 10 Conversion to other gas types (e.g. propane) This can only be done by placing a suitable burner unit. Please contact your supplier. Always indicate the type and serial number of the device when ordering. 11 Calculation You can make a drain calculation using a spreadsheet. (point.13.) There is also an App. available, and can be downloaded via the code below.

horizontal plane. bends I, K and Q and the elements H,J,L, M, P and R (fig.1 and 2)

11.4 length horizontal plane The Horizontal length consists of the elements H,J,L,M,P and R (fig. 1 and 2 )

11.5 Turns 90° in the horizontal plane Horizontal curves are bends that lie entirely in the horizontal plane. (Fig.1.2 and 3 I,K and Q)

11.6 Curves 45° or 30° in the horizontal plane Horizontal curves are bends that lie entirely in the horizontal plane.

11.7 Turns 90°vertical to horizontal plane These are 90° curves which move from horizontal to vertical (Figures 2 and 3 G, O and S)

11.8 Curves 45° or 30 °vertical to horizontal plane These are the turns of 30° or 45° which allow vertical drag at an angle of 45°. (Figures 1 B and D)

Faber Triple Premium M — 11.10 Tabel 100/150mm (11.11) diagram (page 11)
Fig. 31 · 11.10 Tabel 100/150mm (11.11)

11.9 Tubes below an angle of inclination: These are the pipes placed at an angle of 30° or 45° vertically. (fig.1 C) Fill only in combination with min 2 pieces 30 or 45° turns in the vertical part.

The possibilities of drain lengths and the possible thruster are laid down in a driving table in the table is worked with Start Length (STL) Total vertical height (TVH) and Total horizontal length (THL)

11.10 Tabel 100/150mm (11.11)

See table at the correct vertical (TVH) and horizontal length (THL). In the case of a .x.x and if values are not included in the table, the combination is not permitted. adjust the TVH or THL. If a value is declared, check that the calculated STL value is not lower than the one indicated in the table. If this is the case, please adjust the STL. The value found indicates the width of the drivebar to be placed ("0" means no thruster) A 30mm barrage is mounted by default.(fig.1.8)

11.1 Start Length (STL) The first part placed on the fireplace and represented a certain value (Figures 1, 2 and 3 A,N, F) This value is shown in the upper row of the driving table (see Table 11.11)

11.2 Total Vertical Height (VH) TVH is the height difference measured from the top device to the exit, it can be measured or determined from the construction drawing. For clarification see also the TVH designation in the drawings. (fig. 1, 2 and 3: TVH)

11.3 Horizontal plane data:(THL) THL is the total horizontal length and consists of bends and pipes which are entirely in the

10 <

Page 12 of the Faber Triple Premium M user manual — STL
Page 12 · click to enlarge
Page 12
TVH p Min.Start lengte 0,1 0,2 0,5 0,5 1 1 1 THL Horizontaal (m) THL 0 1 2 3 4 5 6 0 x 0,5 x 1 0 0 0 x 1,5 0 x x 2 30 3 30 30 4 40 30 30 5 40 40 30 30 6 50 40 40 30 30 0 0 7 50 50 40 40 30 30 0 8 50 50 50 40 40 30 0 9 65 50 50 50 40 30 30 10 65 65 50 50 40 30 30 11 65 65 60 50 40 40 30 (m) 12 65 65 60 50 50 40 30 13 65 65 60 50 50 40 30 hoogte 14 65 65 60 50 50 40 30 15 65 65 60 50 50 40 30 16 65 65 60 50 50 40 30 Verticale 17 65 65 60 50 50 40 30 18 65 65 60 50 50 40 30 19 65 65 60 50 50 40 30 TVH, 20 65 65 60 50 50 40 30 21 65 65 60 50 50 40 30 22 65 65 60 50 50 40 30 23 65 65 60 50 50 40 30 24 65 65 60 50 50 40 30 25 65 65 60 50 50 40 x 26 65 65 60 50 50 x x 27 65 65 60 50 x x x 28 65 65 60 x 29 65 65 x 30 65 x Min. Start Length0,1 0,2 0,5 0,5 1 1 1 Horizontal (m)THL0123456 TVH, Vertical height (m)0xxxxxxx 0,5xxxxxxx 1000xxxx 1,500000xx 230000000 3303000000 44030300000 540403030000 6504040303000 75050404030300 85050504040300 965505050403030 1065655050403030 1165656050404030 1265656050504030 1365656050504030 1465656050504030 1565656050504030 1665656050504030 1765656050504030 1865656050504030 1965656050504030 2065656050504030 2165656050504030 2265656050504030 2365656050504030 2465656050504030 25656560505040x 266565605050xx 2765656050xxx 28656560xxxx 296565xxxxx 3065xxxxxx

STL

11 <

Page 13 of the Faber Triple Premium M user manual — 12 <
Page 13 · click to enlarge
Page 13

Fig. 12.1 Fig. 12.2 Fig 12.3

Faber Triple Premium M — 12 < diagram (page 13)
Fig. 32
Faber Triple Premium M — 12 < diagram (page 13)
Fig. 33
Faber Triple Premium M — 12 < diagram (page 13)
Fig. 34

12 <

12 example

Page 14 of the Faber Triple Premium M user manual — 13 <
Page 14 · click to enlarge
Page 14
Faber Triple Premium M — 13 < diagram (page 14)
Fig. 35

13 <

13 Sheet of accounts

Page 15 of the Faber Triple Premium M user manual — 14 <
Page 15 · click to enlarge
Page 15
Faber Triple Premium M — 14 < diagram (page 15)
Fig. 36

14 <

Page 16 of the Faber Triple Premium M user manual — 15 <
Page 16 · click to enlarge
Page 16
Diagram . .
Diagram . .

C11 C11C11 C31 C11

Load Hi kW 8.5 8.5 8.5 8,5 8.5 8.5

Connection pressure mbar 25 30 30 20 30 37 37

Small-scale dam mm 1.8 1.3 1.8 1.3 1.3 1.3

Code injection device No 36 Nr.23 Nr.36 Nr. 23 Nr. 23.

Batteries transmitter V 9. 9 9

15 <

14 Technical data

Page 17 of the Faber Triple Premium M user manual — 16 <
Page 17 · click to enlarge
Page 17
Faber Triple Premium M — 16 < diagram (page 17)
Fig. 38

16 <

15 Size drawings

Page 18 of the Faber Triple Premium M user manual — 17 <
Page 18 · click to enlarge
Page 18
Faber Triple Premium M — 17 < diagram (page 18)
Fig. 39

17 <

Page 19 of the Faber Triple Premium M user manual — 18 <
Page 19 · click to enlarge
Page 19
Faber Triple Premium M — 18 < diagram (page 19)
Fig. 40

18 <

Page 20 of the Faber Triple Premium M user manual — 19 <
Page 20 · click to enlarge
Page 20
Faber Triple Premium M — 19 < diagram (page 20)
Fig. 41

19 <

Page 21 of the Faber Triple Premium M user manual — 20 <
Page 21 · click to enlarge
Page 21

20 <

Page 22 of the Faber Triple Premium M user manual — 21 <
Page 22 · click to enlarge
Page 22

21 <

Page 23 of the Faber Triple Premium M user manual — 22 <
Page 23 · click to enlarge
Page 23

22 <

Page 24 of the Faber Triple Premium M user manual — T. +31(0)513 656500
Page 24 · click to enlarge
Page 24

Dealer info:

Faber Triple Premium M — T. +31(0)513 656500 diagram (page 24)
Fig. 42

www.faber.nl - [email protected]

Saturn 8 EN - 8448 CC Heerenveen

PO Box 219 EN 8440 AE Heerenveen

T. +31(0)513 656500

F. +31(0)513 656501

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Faber Triple Premium M

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.