children and pets are not present in the room.
The fireplace may only be installed by a qualified installer/dealer. We strongly recommend that these installation instructions be read properly. This appliance complies with the guidelines for European Gas Appliances (GAD) and carries the CE marking. 2 Security notices.
3.1 Minimum distances around the fireplace
Determine the final spot, keeping a minimum distance of 30cm from. the side walls on
3.2 Requirements for drainage channel and exits
For the supply and disposal you must always use the drainage materials prescribed by Faber International BV. Only with the use of these materials can Faber International BV guarantee a good working environment. The outer surface of the concentric drain material can be +/- 150°C. When passing through a flammable wall or ceiling, provide insulation and protection. And keep a sufficient distance. Make sure that the concentric drain material is held every 2 metres at large discharge lengths, so that the weight of the material does not rest on the fireplace. You should never start on the device with a short-term concentric drain material
The apparatus must be installed and inspected annually in accordance with this installation requirement, as well as the applicable national and local requirements. Check that the data on the plate match the local gas type and pressure. The settings and the construction of the fireplace must not be changed! Do not place any extra imitation wood or glow material on the burner or in the combustion chamber. The device is for atmosphere and heating purposes. This means that all surfaces, including the glass, can become very hot (hotter than 100°C) except for this form the underside of the fireplace and control buttons. Do not place combustible materials within 0.5 m of the radiation part of the fireplace. The natural air circulation of the fireplace makes moisture and non-hardened volatile components from paint, building materials and floor coverings etc. sucked in. These constituents can be placed as soot on cold surfaces. Therefore, do not light the fireplace shortly after a renovation. The first time the fireplace lit a few hours at its highest stand, so that paint would have the chance to harden out. Ensure sufficient ventilation to remove any vapours released. We recommend that you be as little present in space as possible during this process. Please note:
3.3 Entirely The combined supply and disposal can pass through both the façade and the roof. Check that the exit you want meets local requirements regarding discomfort and ventilation openings. For proper operation, the exit shall be at least 0,5m from: Angles of the building. Rooftops and balconies. Roof edges. (excluding the ridge edge)
all transport containers have been removed.
1 Introduction · 3 Requirements for installation

3.4 Existing chimney You can also connect the fireplace to an existing chimney. The existing chimney then functions as an air supply and a flexible stainless steel pipe pulled through the chimney drains the exhaust gases.The flexible stainless-steel tube of Ø 100mm must have a CE mark up to 6000 The chimney shall then meet the following conditions:
4.4 Installation of the fireplace Please take into account the Installation requirements (see chapter 3) (Check the load capacity of the wall to which the fireplace is placed. the weight of the fireplace approximately 86 kg.)
Mount the hanging bracket on the wall (fig. 1.2 ) Place the fireplace on the bracket and fasten it with 4 bolts and nuts (fig. 1.3) Place the protective plate for the glass block and receiver underneath the device (fig.1.4)
The passage of the chimney canal must be at least 150 x 150mm. No more than one appliance must be connected to a chimney The chimney shall be in good condition:
4.5 Mounting of flue gas drainage materials
In the case of a passage through the wall or ceiling, the hole shall be at least 5 mm larger than the diameter of the drain material. Horizontal sections should be installed on a bulkhead towards the fireplace (3 degrees). Build the system from the fireplace. If this is not possible, a sliding intersection can be used. The 1⁄2 meter short pipe is used to fit the drainage system. Always make sure the inner pipe is 2 cm longer than the outer pipe. The facade and roof throughput are also shortable. These parts need to be secured with a parking lot. A recessed flue gas drain can not isolate but ventilate. (approx.100cm2) 5 Remove from glass.
o No leakage and o Good cleaning For more information about the connections to existing chimney channels, see manual .
4 Preparation and installation instruction
4.1 Gas connection The gas connection must comply with local standards. We recommend a gas connection of Ø 15mm directly from the gas meter to the device, with in close proximity to the appliance a shut-off valve which is always accessible. Position the gas connection so that it is easily accessible, and for service the burner unit can be dismantled at any time.
4.2 Electrical connection If an adapter is used for the power supply, a wall socket 230VAC .50Hz must be mounted near the fireplace.
4.3 Preparation of the fireplace
Remove the fireplace from its packaging. Please note that the gas supply lines underneath the device are not damaged. Clear a place, if you will. safe storage of list and glass. Delete if necessary the list and glass, and take the packed parts from the fireplace. Prepare the gas connection on the gas control block.

6 Installation of decoration material
Measure burner pressure:
Check the burner pressure only at proper prepressure. Turn the measuring nipple A (fig.1.8) open some strokes and connect a measurement hose to the gas control block. The pressure shall correspond to the value indicated in the technical description of this manual. (Chapter 13) By way of derogation, contact the manufacturer. *Close all pressure gauges and check for gas leakage.
It is not permitted to add other or more material into the combustion chamber. Always keep the flame free of decoration material!
6.1 Places of the wood set
Place the logs. Make sure the logs are properly connected over the tube burners. (see Fig.1.9 or included wood set card). Now divide the vermiculite granules and chips into the combustion chamber. Avoid covering the aeration opening(s). Place the glass plate and check the fire image. 7 Installation control.
7.4 Flame Image Control Let the fireplace burn for at least 20 minutes and then check the flame image on: 1. Flame distribution 2. Color of flames If one or both points are not acceptable check then: The wood setup and/or the
amount of chips The connections of the pipe material
7.1 Control of ignition flame, head burner. Light the fireplace as described in the user manual. Check that the watch flame is well above the head burner and is not covered by chips, a log or pebbles. Check the ignition of the head burner for full and small position. (the ignition must be smooth and quiet).
for leakage. (in case of blue flames). Whether the right thruster is mounted. The end of the line.
o Wall throughput on the right side above and correct position o Roof throughput is in a proper position Whether maximum lengths of flue gas discharge have not been exceeded. 8 Customer instruction Advise that the appliance must be checked annually by an approved installer to ensure safe use and long life Give advice and instructions on glass maintenance and cleaning. Emphasize the risk of burning in fingerprints. Inform the customer about how the device works and the remote control, including replacing batteries and adjusting the receiver. Hand over to the customer:
7.2 Gas leak control. Check with a gas leak seeker or spray all connections and connections for any gas leakages.
7.3 Check the burner pressure and prepressure Check that the burner and pre-pressure match the data on the label plate Measurement of front pressure:
Turn off the device valve. Rotate the measuring nipple B (fig. 1.8) One blows open and connect a measuring hose to the gas control block. Take this measurement at full fireplace and when the fireplace is on a watchflame. If the pressure is too high, you must not connect it
o Installation instructions o User's manual o Woodset Map instruction 9 Annual maintenance
9.1 Control and cleaning:

Check and clean if necessary after checking: The flame The burner The combustion chamber The glass The logs on the woods. Fracture. the end of the project
The possibilities of drain lengths and the possible thruster are laid down in a driving table (see Chapter 12). This table is based on vertical and horizontal length.
For the determination of horizontal length, all lengths of drain pipes shall be added in the horizontal direction: every 90° turn in the horizontally section shall be 2 metres. every 45° bend in the horizontal section shall be 1 metre. Turns from vertical to horizontal or vice versa do not count for calculation. The roof throughput always counts for 1 meter The facade throughput is always 1 meter. If dragged below 45°, the actual vertical and horizontal lengths shall be calculated.
9.2 Replace:
If necessary, the chips/embers.
9.3 Cleaning the glass Most of the attack can be removed with a dry cloth. With ceramic hotplates cleanser you can get the glass clean. Please note: avoid fingerprints on the glass. These are no longer removable after burning in! Now perform the check as described in chapter 7. .
10 Conversion to other gas types (e.g. propane) This can only be done by placing a suitable burner unit. To do this, please contact your supplier. Always indicate the type and serial number of the device when ordering.
11.1 Points of interest:
A short pipe must never be started from the device.


11.2 Example calculations Example 1 horizontal lengths C+E = 1 + 1 2 m D = 2 m 2 m + Total 4 m vertical lengths A 1 m G 1 m Total 2 m Example 2 horizontal lengths J + L = 0,5 + 0,5 1 m K+ M = 2 + 2 m 4 m N 1 m Total 6 m Count vertical lengths H 1 m Total 1m


12 The table shows the correct vertical and horizontal length. In the case of a .x.x and if values are not included in the table, the combination is not permitted. The value found indicates the width of the drive to be placed ("0" means no thrust). A 30mm thruster is mounted as standard.



(At 15oC and 1013mbar) g/h 500 430




www.faber.nl - [email protected]
Saturn 8 EN - 8448 CC Heerenveen
PO Box 219 EN 8440 AE Heerenveen
F. +31(0)513 656501
Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.