Sunline™2000 series convertible package rooftop mod- els have two independent refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof.
Cooling only, cooling with gas heat and cooling with electric heat models are available with a wide variety of factory- mounted options and field-installed accessories to make them suitable for almost every application.

All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging.
Every unit is completely piped, wired, charged and tested at the factory to simplify field installation and to provide years of dependable operation. Powder paint cabinets pro- vide an exceptionally durable finish with the 750 hour salt spray process per ASTM-B117 test standard.
All models (including those with an economizer) are suit- able for either bottom or horizontal duct connections. Mod- els with power exhaust are suitable for bottom duct connections only. For bottom duct, you remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, you replace the supply and return air panels on the rear of the unit with a side duct flange accessory.
D2CE / D2CG 300 CONSTANT VOLUME 25 NOMINAL TONS 8.5 EER SUNLINE 2000 ™



A fixed outdoor air intake assembly is shipped in the return air compartment of all units ordered without an economizer or motorized outdoor air damper option. The assembly includes a rain hood with a damper that can be set for 10, 15 or 25% outdoor air. With bottom duct connections, the intake damper assembly should be mounted over the opening in the return air panel. With horizontal ductwork, it should be mounted on the return air duct.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. A high speed drive accessory is available for applications with a higher CFM and/or static pressure requirement.
Interlocked outdoor and return air dampers are posi- tioned by a fully modulating, spring return damper actu- ator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers. As the outdoor air intake dampers open, the return air dampers close. The changeover from compressor to economizer cool- ing is determined by one or two solid state enthalpy controls.
All compressors include internal pressure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/ loss of charge switch. The unit control circuit includes two 75 VA transformers, two 24-volt circuit breakers and a relay board with two compressor lockout circuits, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of addi- tional field controls.
On single enthalpy, an outdoor air sensor determines when the outdoor air is cool and dry enough to provide “free” cooling. On differential enthalpy, one sensor monitors the outdoor air while a second sensor moni- tors the return air. Whenever the outdoor air is cooler and drier than the return air, the unit will switch to econ- omizer operation. For either option, the first compres- sor stage can provide additional cooling during economizer operation if the room thermostat calls for second stage.
All 208/230 and 460-volt models are ETL approved. All 208/230 and 575-volt models are CGA approved.
All models include a 1-year limited warranty on the complete unit. Compressors and electric heater ele- ments carry an additional 4-year warranty. Aluminized steel tubular heat exchangers carry an additional 9- year warranty.
The dampers and controls are installed and wired at the factory. Only the accessory rain hood needs to be assembled and installed in the field.
All gas heat models are built with two heating sections for two equal stages of capacity control. Each section includes a durable heat exchanger with aluminized steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.
These economizer options can be used on all duct con- figurations.
Both the single and differential economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the condi- tioned space from being over-pressurized during econ- omizer operation.
The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.
All electric heat models are wired for a single power source and include a bank of nickel chromium ele- ments mounted at the discharge of the supply air blower to provide a high velocity and uniform distribu- tion of air across the heating elements. Every element is fully protected against excessive current and temper- ature by fuses and two thermal limit switches.
The exhaust fan, motor and controls are installed and wired at the factory. Only the back-draft damper assembly needs to be field installed and the accessory rain hoods need to be assembled and installed in the field.
The power exhaust option can only be used on bottom duct configurations.
The power supply wiring can be routed into the control box through a threaded pipe connection in the base pan of the unit or through a knockout in the wiring panel on the front of the unit.
Interlocked outdoor and return air dampers are con- trolled by a 2-position, spring return damper actuator. The outdoor damper will open to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower shuts down.
All internal factory wiring is color coded and numbered for ease in servicing and troubleshooting.
The damper and controls are installed and wired at the factory. Only the accessory rain hood needs to be assembled in the field.
This damper option can be used on all duct configura- tions.

Two solid state timers prevent the compressors from short-cycling. Once a compressor is de-energized, it will remain de-energized for approximately five min- utes.
Includes a slide-in/plug-in damper assembly with fully modulating spring-return monitor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide “free” cooling.
Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
Power exhaust is not available as a field installed option.
Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.
Includes a slide-in / plug-in damper assembly with fully modulating spring-return monitor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
One inch flanges replace the supply and return air pan- els on the rear of the unit to accommodate horizontal duct connections. These flanges can also be used indi- vidually for bottom supply/horizontal return or horizon- tal supply/bottom return. They cannot be used on units with power exhaust.
This enthalpy system contains one sensor that moni- tors the outdoor air and one sensor that monitors the return air. The logic module compares these two val- ues and modulates the dampers providing the maxi- mum efficiency of economizer system.
This damper accessory can be used to relieve internal air pressure on units with an economizer but no power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
Power exhaust is not available as a field installed option.
Includes a slide-in/plug-in damper assembly with a 2-position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.
A rain hood accessory must be used on units with an economizer, a motorized damper, or a combined econ- omizer with power exhaust option. These accessories include all the hood panels, the necessary components and hardware for field assembly.
The rain hood is painted to match the basic unit and must be field assembled before installing.
Power exhaust is not available as a field installed option.
A smaller blower pulley and a shorter belt increase the speed of the supply air blower for applications with a higher CFM and/or static pressure requirement.
Fourteen inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly. They're designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger sup- ports.
An autotransformer and a thermostat maintain stable system operation by reducing the speed of the con- denser fan motor at low outdoor temperatures. The kit

also includes a 1-phase motor to replace the unit's standard 3-phase condenser fan motor. Standard units can operate down to 45°F.
Provides coil guard and fastners.
*
1
+ , - .
*
3 1
-
4 5 ! ( 4
1
+ /
! " # $ $ % " ! & ' ! ' ( ! ) *
0 * 0 -
2
1
1 2 .
1
/ 0 3
3 1

*. Outside the scope of ARI Standard 340/360. EER=Energy Efficiency Rating at full load-the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt). IPLV - Integrated part load value. NOTE: All cooling is three stage.

*. At a distance of 10 ft.from the blower.
cation or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.

Air On Evapo ra tor
Air On Evapo ra tor
1These ca paci ties are gross rat ings. For net ca pac ity, de duct the heat of the sup ply air blower mo tor, MBH = 3.415 x KW. Ref er to the ap pro pri ate Blower Per form ance Ta ble for the KW of the sup ply air blower mo tor.
2These rat ings in clude the con denser fan mo tors (To tal 2.3 KW) and the com pres sor mo tors but not the sup ply air blower mo tor.
All Sen si ble Ca pac ity Nomi nal Rat ing

DCE300 - BOT TOM DUCT CON NEC TIONS (COOL ING AP PLI CA TIONS)
Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil. Refer to page 7 for additional static resistances. ESP - External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * FACTORY SETTING
DCG300 - BOT TOM DUCT CON NEC TIONS (COOL ING AP PLI CA TIONS)
ACCESSORY DRIVE:
Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil. Refer to page 7 for additional static resistances. ESP - External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * FACTORY SETTING

NOMI NAL VOLT AGE VOLT AGE KW CAP. MUL TI PLIER 208 208 1.00 240 230 0.92 480 460 0.92 600 575 0.92
OP ER AT ING WEIGHTS
MODEL SIZE (MBH) 300
300 EVAPO RA TOR
DCE (Cool ing only) 2730 DCV (Cool ing only) 2795
CEN TRIFU GAL BLOWER (Dia. x Wd. in.) 18 x 15 FAN MO TOR HP 15
DCG (Gas / Elec tric) N240 2930 N320 2970
ROWS DEEP 4 FINS PER INCH 13.5 FACE AREA (Sq. Ft.) 25.0 CON DENSER
DCV (Gas / Elec tric) N240 2995 N320 3035 Econo mizer 160 Econo mizer with Power Ex haust 245
PRO PEL LER DIA. (in.) (Each) 30 FAN MO TOR HP (Each) 1 NOM. CFM TO TAL (Each) 7200
FAN (Two Per Unit)
ROWS DEEP 3 FINS PER INCH 15 FACE AREA (Sq. Ft.) 43.3 COM PRES SOR
Op tions Mo tor ized Damper 150
COIL
18 KW 25 36 KW 30 54 KW 35 72 KW 40
Elec tric Heater (Elec/Elec only)
12.5 TON, SCROLL, HER METIC, TAN DEM (2 STAGE, 50% ea.) 2
(Qty. Per Unit)
QUAN TITY PER UNIT (16" X 20" X 2") 2 QUAN TITY PER UNIT (16" X 25" X 2") 4 QUAN TITY PER UNIT (14" X 20" X 2") 3 TO TAL FACE AREA (sq. ft.) 21.4
Roof Curb 185 Ba ro met ric Damper 45 Econo mizer/Mo tor ized Damper Rain Hood 55
Ac ces so -
Econo mizer/Power Ex haust Rain Hood 90
22 (lbs./oz.) SYS TEM NO. 1 20/8
SYS TEM NO. 2 20/0
Ba sic Unit · ries · Wood Skid 220

BLOWER
RANGE
(RPM)
QTY.
High Speed Ac cess
1All mo tors have a nomi nal speed of 1800 RPM, a 1.15 serv ice fac tor and a solid base. They can op er ate to the limit of their serv ice fac tor be cause they are lo cated in the mov ing air, up stream of any heat ing de vice.
DESCRIPTION
*Fac tory Set ting Power Ex haust mo tor is a 3/4 HP, PSC type with sleeve bear ings, a 48 frame and in her ent pro tec tion.
ELEC TRI CAL DATA - Cool ing Only Units and Units With Gas Heat
ELECTRICAL DATA - Cooling Only Units & Units With Gas Heat
MODEL NO.
**Rated in ac cor dance with ARI Stan dard 110, utili za tion range “A”.
Stan- · dard 975/1165

! " # $ % ' " ( " ) * )
$ % , - ( ! . ! / 0 1 ! / ( " $ 2 - % $ ! ( 3 . ( % 2 , - 1 4 ! " ' $ / " , - 5 " # $ 6 - , " / - " % ! . 7
! " # $ % ' " ( " ) * ) ) % ) * ) 8 9 , " # ' 6 . . ( ' $ ) * ) ) % ) * ) ) :
$ % , - ( ! . ! / 0 1 ! / ( " $ 2 - % $ ! ( 3 . ( % 2 , - 1 4 ! " ' $ / " , - 5 " # $ 6 - , " / - " % ! . 7
: $ / - 2 ' " ( ; $ # $ ( " , - ; , ' - " % $ < 6 , % $ 2 - 6 - , " ' 9 , " # ( ' , - ; ! $ ' " ( ; $ ! $ / " % , / # $ ( " $ %
$ 5 $ % " " # " ( . ! $ ' " ' , > $ " # = 9 $ % 9 , % , - ; ? " # 5 6 ' $ ' ( - 2 " # 2 , ' / - - $ / ' 9 , " / #
) * )
! $ / " % - , / = % ; % ( ( . ! $ # $ % ' " ( " ) * ) ) , - / ! 6 2 $ ' ' 6 . . ( ' $
$ % , - ( ! . ! / 0 1 ! / ( " $ 2 - % $ ! ( 3 . ( % 2 , - 1 4 ! " ' $ / " , - 5 " # $ 6 - , " / - " % ! . 7
: $ / - 2 ' " ( ; $ # $ ( " , - ; , ' - " % $ < 6 , % $ 2 - 6 - , " ' 9 , " # ( ' , - ; ! $ ' " ( ; $ $ ! $ / " % , / # $ ( " $ %
$ % , - ( ! ' ( - 2 = % 4 , 2 $ ( % $ ! ( 3 6 " = 6 " " / ! ' $ " # $ 6 " 2 % $ / - & , > $ % 2 ( = $ % 9 # $ - " # $ " # $ % ' " ( " ' 9 , " / # $ ' " " # $ ' $ " 1 . ( / 0 = ' , " , -

ECONOMIZER / MOTORIZED DAMPER, FIXED OUTDOOR INTAKE AIR AND POWER EXHAUST RAIN HOODS (See detail "Y") FIELD-SUPPLIED DISCONNECT SWITCH LOCATION
BLOWER MOTOR ACCESS
COMPRESSOR ACCESS (See detail "X")
BLOWER COMPARTMENT ACCESS (Auxiliary)
Back 24" (Less Econo mizer) 49" (With Econo mizer)
DOT PLUG (For pressure Drop Reading)
Left Side (Fil ter Ac cess) 24" (Less Econo mizer) 36" (With Econo mizer) Right Side (Cond. Coil) 36" Be low Unit1 20"
VENT AIR OUTLET HOODS
CONDENSER COILS
72" With 36" Maxi mum Hori zon tal Over hang (For Con denser Air Dis charge)
(C) GAS SUPPLY ENTRY
1U nits (ap pli ca ble in U.S.A. only) may be in stalled on com bus ti ble floors made from wood or class A, B or C roof cov er ing ma te rial. 2Units must be in stalled ou doors. Over hang ing struc tures or shrubs should not ob struct con denser air dis charge out let.
CONTROL BOX ACCESS
(B) POWER WIRING ENTRY
BOTTOM SUPPLY
AND RETURN AIR OPENINGS
RETURN AIR
RETURN
AIR
SUPPLY AIR
GAS/ELEC Mod els: A 1" clear ance must be pro vided be tween any com bus ti ble ma te rial and the sup ply air duct work for a dis tance of 3 feet from the unit.
AIR
OUTDOOR AIR
The prod ucts of com bus tion must not be al lowed to ac cu mu late within a con fined space and re cir cu late.
UNIT BASE WITH RAILS Shown separately to illustrate Bottom Duct openings, Power and Gas Piping Connection locations
(B) POWER WIRING ENTRY
Lo cate unit so that the vent air out let hood is at least:
? Three (3) feet above any forced air in let lo cated within 10 hori zon tal feet (ex -
(A) CONTROL WIRING ENTRY NOTE: For curb mounted units, refer to the curb hanger dimensions of the curb for the proper size of the supply and return air duct connections.
clud ing those in te gral to the unit).
? Four (4) feet be low, 4 hori zon tal feet from, or 1 foot above any door or grav ity
air in let into the build ing.


DUCT COVERS - Units are shipped with the bottom duct openings covered. An accessory flange kit is available for connecting side ducts. For bottom duct applications: 1 Remove the side panels from the supply and return air compartments to gain access to the bottom supply and return air duct covers.
2 Remove and discard the bottom duct covers. (Duct openings are closed with sheet metal covers except when the unit includes a power exhaust option. The covering consists of a heavy black paper composition.)
3 Replace the side supply and return air compartment panels.
For side duct applications; 1 Replace the side panels on the supply and return air compartments with the accessory flange kit panels.
2 Connect ductwork to the duct flanges on the rear of the unit.

@ @ - 6 " 2 % , % & = ( % " & $ - " @ @
- $ " 6 % - , % & = ( % " & $ - "
! / ( " $ 2 - $ " 6 % - , % & = ( % " & $ - " A 6 ' " . $ " % ( = = $ 2
A











Units shall be factory-assembled, single packaged, (DCG Electric Cooling/Gas Heat, DCE Electric Cooling/ Optional Electric Heat), designed for outdoor mounted installation. Units shall have minimum EER ratings of 8.5. They shall have built in field convertible duct con- nections for down discharge supply/return or horizontal discharge supply/return, and be available with factory installed options or field installed accessories.
The units shall be factory wired, piped, charged with R- 22 refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. Enclosed in each unit shall be a factory test log sheet consisting of the unit tested pressures, temperatures and amps, as tested prior to shipment.
All units shall be manufactured in a facility certified to ISO 9001 standards and the cooling performance shall be rated in accordance with DOE and ARI test proce- dures. Units shall be ETL & CGA listed, classified to ANSIZ21.47 standards, UL 1995/CAN/CSA No. 236- M90 conditions.
B. Shall have internal spring isolation and sound muf- fling to minimize vibration and noise, and be exter- nally isolated on a dedicated, independent mounting.
A. Evaporator and condenser coils shall have alumi- num plate fins mechanically bonded to seamless internally-enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.

B. Evaporator and Condenser coils shall be of the direct expansion, draw-thru, design.
resistance and allowing minimum mixed air enter- ing temperature of 25 °F.
C. Condenser coils shall be protected with factory installed coil guards
A. Balance-port thermostatic expansion valve with independent circuit feed system.
B. Filter drier/strainer to eliminate any moisture or for- eign matter.
C. Accessible service gage connections on both suc- tion and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge.
D. The refrigeration system shall provide at least 15 °F of sub-cooling at design conditions.
A. Primary and auxiliary high-temperature limit switches.
E. All Models shall have two independent circuits..
B. Induced draft motor speed sensor.
C. Flame roll out switch (manual reset).
A. Unit shall be complete with self contained low-volt- age control circuit protected by a resetable circuit breaker on the 24 volt transformer side.
D. Flame proving controls.
7 Unit shall have two independent stages of capacity.
B. Unit shall incorporate a lock-out circuit which pro- vides reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor:
If any of the above safety devices trip, an LED (light- emitting diode) indicator shall illuminate.
C. Unit shall incorporate “AUTO RESET” compressor over temperature, over current protection.
D. Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook-up.

space during normal operation. During economizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from com- pressor to economizer operation shall be provided by two integral electronic enthalpy controls - one that senses outdoor air and one that senses indoor air. Both enthalpy sensors supply input to the logic module which modulates both sets of dampers for maximum economizer savings. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/ filters shall be provided. Simultaneous economizer/ compressor operation is also possible. Dampers shall fully close on power loss.
All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bot- tom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.
Compressor- 5 Years Heat Exchanger - 10 Years Elect. Heat. Elem.- 5 Years Parts- 1 Year
1 ELECTRONIC ENTHALPY AUTOMATIC ECON- OMIZER - Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring-return damper actuator. The maximum leak- age rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be pro- vided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from com- pressor to economizer operation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/ filters shall be provided. Simultaneous economizer/ compressor operation is also possible. Dampers shall fully close on power loss.
3 MOTORIZED OUTDOOR AIR DAMPERS - Out- door and return air dampers that are interlocked and positioned by a 2-position, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit- mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the venti- lation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-ener- gized. Dampers shall fully close on power loss.
2. DUAL INPUT DIFFERENTIAL ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER - Out- door and return air dampers that are interlocked and positioned by a fully-modulating, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the mini- mum ventilation requirement of the conditioned

1 POWER EXHAUST OPTION - To work in conjunc- tion with economizers.
3. ELECTRONIC ENTHALPY ECONOMIZER











Subject to change without notice. Printed in U.S.A. CD: 6-21359 036-21359-001-B-0302 Copyright © by Unitary Products Group 2002. All rights reserved. Supersedes: 036-21359-001-A-0302