Homeowner's Installation and Operating Manual
For Models: ODSR36A ODSR42A

For use in U.S./Canada Underwriter's Laboratories Report No. MH6018
20006811 3/06 Rev. 4 DO NOT DISCARD THIS MANUAL - Retain for future use.


PLEASE READ THIS MANUAL BEFORE INSTALLING AND USING FIREPLACE.
Do not install a solid fuel burning insert or other products not specified for use with this fireplace. These fireplaces are not approved for installation in mobile homes. This fireplace is not designed to be water tight. Therefore, when installing this unit against an exte- rior wall, the wall must be finished before setting unit in place.
The ODSR Series "A" fireplaces are clean-faced, solid fuel, woodburning fireplaces.
Majestic Fireplaces and component parts have been highly tested and will operate safely when installed in accordance with instructions provided in this manual. Carefully read and understand all instructions before beginning installation.
Proposition 65 Warning: Fuels used in gas, wood- burning or oil fired appliances, and the products of combustion of such fuels, contain chemicals known to the State of California to cause cancer, birth defects and other reproductive harm. California Health & Safety Code Sec. 25249.6
If you notice any damage to fireplace or component parts, immediately report damage to your Majestic Fireplaces dealer.
Only use CFM Corporation components or the warranty will be voided and a fire hazard may be created.
CFM Corporation warranty will be voided by and CFM Corporation disclaims any responsibility for the following actions:
The fireplace should not be located in areas that create drafts (ie: frequently opened doors and central heating air inlets/outlets) that hamper the normal flow of air into the fire.
If you plan to install a gas log, the gas line should be installed before framing the fireplace. The gas line must be installed by a certified gas line installer.
There are three methods of cleaning the polished stain- less steel of your outdoor fireplace;
Any such action may possibly cause a fire hazard. Consult local building codes to ensure that you are in compliance before installing the fireplace. Fireplaces must be vented to the out-of-doors. WARNING: To avoid the risk of damaging fireplace materials and increasing the risk of spreading a fire, do not use the fireplace to cook or warm food. Do not obstruct or modify air inlets/outlets in any manner. Do not install combustible materials on any of the fireplace surround. Burn only solid wood fuel or gas logs.
Regardless of which method is used, remember that any- thing with too much abrasive may dull the finish.
20006811


Fig. 1 ODSR36A specifications and framing.

Fig. 2 ODSR42A specifications and framing.
20006811


Chase Installation Insulation methods shown are optional for cold climate, not a requirement for unit operation.
Outside Air Cover Plate Metal Safety Strips (1, 2 or 3 pieces)
Fig. 3 Fireplace and chase parts identification.


CHIMNEY FLUE EXIT
RISE
CHIMNEY SECTION
IWF282
ELBOW
30˚ RETURN
ELBOW
A
G
30˚ OFFSET
D
ELBOW
E 6 FT.
30˚ RETURN
SKCS8 SUPPORT
H
ELBOW
OFFSET
H
30˚ OFFSET
B
ELBOW
HEARTH FLOOR
Example 1 Example 2 Example 3
Illustration Key
The following safety rules apply to offset installations (letters correspond with il- lustration above):
C. The chimney cannot be more than 30˚ (45˚ in Canada) from the vertical plane in any installation*.
A. Height of the chimney is measured from the hearth to the chimney exit. ODSR36A ODSR42A Maximum: 90'0" 90'0" Minimum: Without Elbows 12' 6" 12' 6" With 2 Elbows* 14' 6" 14' 6" With 4 Elbows* 21' 0" 21' 0"
D. The maximum length of the angled run of the total chimney system is 20 feet. (G plus H cannot exceed 20 feet.)
E. A chimney support (Model SKCS8) is required every 6 feet of angled run of chimney. Chimney supports are required for every 30 feet and 60 feet (SK8 pipe) or 20 feet and 40 feet (3-wall pipe) of ver- tical chimney height above the hearth.
B. Do not use more than 4 elbows per chimney.
Determine the offset distance of your chimney arrangement from the centerline of the fireplace to the centerline of the chimney where it is to pass through the first ceiling.
Attach the straps of the return (top) elbow to a structural framing member.
The offset (first) elbow of any pair does not have straps.
* In Canada, two (2) SK845 are allowed.
Fig. 5 Chimney system requirements.
20006811

Preplanning an installation is very important to ensure safety and to save time and money. An installer must predetermine where a fireplace will be set and how the chimney system will be run.
The Ten Foot Rule
A fireplace may only be mounted on the following sur- faces:
Major U.S. building codes specify a minimum chimney height above the roof top. The “Ten Foot Rule” is a fire safety rule and not a draft rule. To ensure proper draft, it is recommended that you always meet or exceed the “Ten Foot Rule,” especially when installing a termination on a high pitch roof. (Fig. 7)
The fireplace must be spaced 1/2" (13 mm) from a combustible back wall and 1/2" (13 mm) from a com- bustible side wall or support. (Page 12, Fig. 19)
The key points of the "Ten Foot Rule" are:
1. If the horizontal distance from the chimney to the peak of the roof is 10' (3 m) or less, the top of the chimney must be at least 2' (610 mm) above the peak of the roof, but never less than 3' (914 mm) in height above the highest point where it passes through the roof. 2. If a horizontal distance from the chimney to the peak of the roof is more than 10' (3 m), a chimney height reference point is established on the surface of the roof a distance of 10' (3 m) from the chimney in a horizontal plane. The top of the chimney must be at least 2' (610 mm) above the reference point, but never less than 3' (614 mm) in height above the high- est point where it passes through the roof.
INSTALLED
LT MODEL SK 2 WALL CHIMNEY
LENGTH
(LT)
(L1)
SK81 SK818 SK83 SK84
1156O" 1756O" 3556O" 4756O"
1056O" 1656O" 3456O" 4656O"
Fig. 6 Installed lengths of chimney sections.
Determine how the chimney will be run, length of run and chimney components required to complete the job. (Fig. 5) Never install a chimney below minimum heights.
2' Min.
3' Min.
2' Min.
In planning a chimney system, it is important to know:
3' Min.
AC246 Fig. 7 Ten Foot Rule illustration.

The chimney system is supported by the fireplace for vertical chimney heights less than 30' (9 m) above the hearth. Chimney supports are required if the vertical height exceeds 30' (9 m) with SK8 chimneys or 20' (6 m) with 3-wall chimneys. Locate chimney supports at ceil- ing holes or other structural framing at 30' (9 m) (SK8) or 20' (6 m) (3-wall) heights. Spacing between chimney supports must not exceed 30' (9 m) (SK8) or 20' (6 m) (3-wall). Use Chimney Support Model SKCS8. (NOTE: The SKCS8 can not be mounted directly to the fireplace.) Support provided by elbow straps fulfills the support requirement only if they are spaced as previ- ously described. (A chimney support is 2¹⁄₂" (64 mm) long when installed.)
for Cold Climates
If you live in a cold climate, it is not required but highly recommended that you insulate fireplace enclosure to eliminate cold air penetration as much as possible.
Insulate base of fireplace with a noncombustible insulation rated for a minimum of 300°F. Insulating is very important for outside wall installations over a concrete slab. If fireplace is installed on a platform, insulation should be placed on top of the platform before fireplace is set. (Fig. 9)
Angled chimney runs require a support every 6' (1.8 m) in addition to the elbow straps. Chimney supports are used for this function. (Fig. 8)
When a fireplace is installed in a chase or on an outside wall, enclosure should be treated like any outside wall in a home. Insulation should be installed on the inside wall as well as the outside wall(s). In a chase, it is also a good idea to install a firestop at the first ceiling level above the fireplace and enclose the chase with sheeting material. Insulation may then be installed above sheeting material to assure the space around the fireplace is totally protected. (Fig. 3)
A chase is a vertical boxlike structure which encloses the fireplace and/or chimney. Chases are typically built on the outside of the house with fireplace opening cut into the outer wall of a room. (Page 4, Fig. 3)
If you need help in determining fireplace location or how the chimney system should be run, contact your Majes- tic Fireplaces dealer for assistance.
When installing the chimney, DO NOT caulk be- tween outer pipe and firestop. It is vital that some air be allowed to flow through this very thin gap.

Fig. 8 Chimney support installation
Fig. 9 Insulating between platform and fireplace.


Framing can be constructed before or after the fireplace is set in place, however, most installers build the frame before setting the fireplace.
Frame fireplace with 2 x 4 lumber or heavier materials. Refer to framing dimensions in Figures 1, 2, 3 or 4 for basic fireplace specifications.
Since you have already preplanned the chimney run, you should know exactly how the installation is to be accomplished — how much pipe is required, the num- ber of elbows, if any, and type of termination to be used.
NOTE: Fireplaces may use CFM Corporation model SK8, or Model S (three wall) chimney systems. The ODSR Series "A" Fireplace will accept the SK8 chimney system as is; but a TWABR adapter collar is required when using the Model S (triple wall) chimney system. The installation procedure described in this manual ap- plies only to the SK8 system. Either chimney system may be used, but may not be mixed.
To mark the centerline of the flue, put the fireplace in final position and measure out from the wall: 9¹⁄₄" (235mm). Mark a spot on the ceiling directly above the fireplace. Draw a line parallel to the back wall through this mark. (Fig. 10)
Fig. 10 Locate centerline of chimney with plumb line.
Determine offset distance of your chimney arrangement from centerline of fireplace to centerline of chimney where it is to pass through ceiling.
Using a plumb bob positioned directly over center point of fireplace flue collar, mark the ceiling to establish the chimney center point. (Fig. 10)
Locate center point of the chimney on ceiling as though a straight up chimney arrangement is to be used. Mea- sure your offset dimension from straight up chimney center point on ceiling.
Ceiling Chimney Hole/ Possible Obstructions
In order to clear an obstruction, it may be necessary to offset chimney from vertical. This is accomplished by using CFM Corporation elbows. Use the 30° Offset Elbow table on Page 5 to determine proper offset and parts required.
The size of the hole in ceiling will vary with the angle at which the chimney passes through ceiling.
Drive a nail up through ceiling at marked chimney cen- ter point. Go to floor above and see where hole will be cut. Check to see where existing ceiling joists and other possible obstructions are located...i.e. wiring, plumbing etc... If necessary, reposition chimney and/or fireplace to avoid obstructions.
Each offset requires two (2) elbows. The second elbow is equipped with support straps. It is very important to install the second elbow in each offset as close to the ceiling or support as possible so that the elbow straps can be secured to framing members to help support the weight of the chimney.
20006811

Cover fireplace collar opening and cut proper sized chimney hole in chimney. The SK8 pipe allows you to run pipe through a typical 16” on center joist without cutting joists.
Metal Safety Strips (1, 2 or 3 pieces)
Frame the ceiling chimney hole as shown in Figure 12. It is good practice to use framing lumber that is the same size as the ceiling joists; this is a requirement at attic level.
"Z" Safety Strip (not sup- plied)
1/2" Min. Overlap
The following table gives firestop spacer model num- bers:
Plat- form Hearth Ext.
Angle of Chimney at Ceiling
Fig. 13 Safety strip installation.
Size of Chimney Vertical 30° 8" Flue SKFS2A SKFS6A "SK" Series 14¹⁄₂" x 14¹⁄₂" 14¹⁄₂" x 25¹⁄₂" (368mm x 368mm) (368mm x 648mm) 8" Flue FS2A FS6A "S" Series 3-Wall 17¹⁄₂" x 17¹⁄₂" 17⁷⁄₈" x 29⁵⁄₈" (445mm x 445mm) (454mm x 753mm)
lap strips at least 1/2" (13 mm) to provide a positive joint. (Flat safety strips are packed with fireplace.) (Fig. 13)
Safety strips are used to ensure that any combustible materials in front of the fireplace are protected even though a noncombustible hearth extension is required.
If fireplace is to be elevated above the floor, a “Z” shaped metal safety strip must be fabricated and used to protect combustible surfaces in front of the fireplace. This “Z” shaped safety strip is not provided but must be fabricated of metal with each horizontal leg at least 1¹⁄₂" (38mm) wide and equal in length to the metals strips provided with the fireplace.
Fig. 11 Ceiling chimney hole sizes necessary for installing firestop spacer.
The inside dimension of the frame must be the same as the hole size selected from Figure 11 in order to provide required the 1¹⁄₂" (38mm) of air space between the outside diameter of the chimney and the edges of the framed ceiling hole.

Four (4) nailing flanges are incorporated on each corner of the surround. Bend the nailing flanges out, level the box, then secure it firmly in place by nailing the flanges to the framing members as shown in Figure 14.

A "SK" Series framing = 14¹⁄₂" X 14¹⁄₂" (368 x 368mm) B "S" Series framing = 17¹⁄₂" X 17¹⁄₂" (445 x 445mm)
Fig. 12 Typical frame for ceiling chimney hole.
Securing the Fireplace
Slide fireplace into position.
Fig. 14 Fasten fireplace in position.
Lift the fireplace front slightly and slide the metal safety strips under front bottom edge about 1¹⁄₂" (38 mm), al- lowing the remainder to extend in front of firebox. Over-
Fire- place · 20006811


An outside air kit is not installed in all ODSR Series "A" Fireplaces. If desired, or if local codes mandate the use of an air kit, then an AKU1 is required . If the outside air kit is to be used, the AKU1 MUST be installed BEFORE the fireplace is enclosed. Refer to the AKU1 instructions for field installation.
Start by attaching the first chimney section to the collar on top of the fireplace.
Install the pipe as pictured in Figure 15. When you get a good lock, you will hear the pipe clearly snap together. Once sections are snap-locked in place, it is extremely difficult to get them apart. Make sure the pipe is firmly snapped and locked together as each pipe section is mounted.
Fig. 16 Attach straps to a structural framing member.

Hole sizes listed in Figure 11 for angled firestop spac- ers provide minimum required air space to chimney pipe for ceiling thickness up to 8" (203 mm). When combined thickness of ceiling material, ceiling joists and flooring material exceeds 8" (203 mm), adjustments must be made in framing to assure that minimum air spaces to chimney are maintained.
Figure 17 shows different installation procedures for both an area that is an attic and an area that is not an attic.
If the area above the ceiling is not an attic, position the firestop spacer with the flange on the ceiling side and the angled portion extending up into the hole.
If the area above the ceiling is an attic, position the firestop spacer with the flange on the top of the framed hole and the angled portion extending down into the hole.
Fig. 15 Install pipe, listening for the snap-lock to fasten.
When installing elbows, only outer pipe will snap- lock. Middle pipes simply slide into position. Be sure to always attach straps on upper elbow to a structural framing member. (Fig. 16)
Firestop spacers are not available for nor are they required on vertical walls.
DO NOT put any sealant around the area where the outer pipe slides through the firestop spacer. If you seal this area, it may cause a fire hazard.
Continue installing the pipe as required until pipe is installed up through the ceiling. At this point, you must install a firestop spacer.
Installing the Firestop Spacer
for Insulation Shield
in the Ceiling Hole
In Canada, an attic insulation shield is required to pre- vent attic insulation from contacting the chimney sec- tion. Framing dimensions for the chimney hole should measure 14¹⁄₂" x 14¹⁄₂" (368 x 368 mm). An attic shield MUST be installed on top of attic joists (above the floor level). (Fig. 18)
A firestop spacer is used to keep pipe spaced properly and required for safety.
Nail the firestop spacer (at each corner) to the framing members of the ceiling hole. NOTE: A firestop spacer is not required at the roof.
20006811

Chimney Supports
If chimney supports are required, they are installed the same as elbows. Nail chimney support straps to adja- cent structural framing, as shown on, Page 7, Figure 8. Bend straps as necessary and make sure they are secure so they will support the weight of the chimney. A chimney support is 2¹⁄₂" (64 mm) long when installed. Consider this dimension when determining how many straight chimney sections are needed.
Additional Ceilings
If you encounter additional ceilings, repeat same steps required for first ceiling installation. Refer to firestop illustration on Figure 17.
Run pipe to roofline. Since chimney system must be vented to the out-of-doors, you must use an approved CFM Corporation termination.
If a chase is used, refer to the installation manual pro- vided with the termination cap.
Fig. 17 Installing firestop spacer.
Install the attic insulation shield with the flanges on its base extending down into the framing hole. Nail each corner of attic insulation shield to the framing members of the ceiling hole using 8d nails. Attic shields are not required at the roof.
Use same procedure detailed in locating centerpoint of the flue system.
Drive a nail up through roof at the center point. This will determine center point on outside of the roof.
Size of roof hole varies with the type of chimney termination installed. Refer to installation instructions provided with CFM Corporation chimney termination to find correct size of roof hole.
There must be a 1¹⁄₂ (38 mm) air space between out- ermost portion of chimney sections and any adjacent combustible surfaces. (Combustible surfaces include burnable materials such as: ceiling members, joists, flooring, combustible insulation and roof structures.)
Mark an outline of the roof hole around the center of the point nail. NOTE: Hole dimensions given in the chim- ney top installation instructions are horizontal dimen- sions; therefore, the hole size must be marked on the roof accordingly.
Fig. 18 Attic shield installlation (Canadian requirement).
Cover the opening of the installed chimney so debris cannot get into the system.
Continue attaching pipe sections to complete system to next level always being careful that the pipe is firmly snapped locked in place before proceeding to next pipe section.

Cut and frame the hole. It is good practice to use fram- ing lumber that is the same size as the rafters. Install the frame securely because the chimney top and flash- ing anchored to the frame must be able to withstand heavy winds.

Combustible framing material MUST NOT penetrate AIR SPACE (shaded areas).
Since you have already preplanned the height of your termination according to the Ten Foot Rule, continue to install pipe to the predetermined height.
Check the chimney top installation instructions for details on how high above the roof top the chimney sections (all pipes) should extend.
or Termination
Follow the installation instructions provided with the chimney termination you have selected.
Refer to Page 4, Figure 3 for an illustration of a typical chase installation.
Only noncombustible material may be applied as facing to the black fireplace surround.
Fig. 19 Minimum clearances to combustibles.
Finish the wall with material of your choice. Do not install a combustible mantel shelf less than 12" (305 mm) from the top of the fireplace opening. Do not install a mantel face plate less than 6" (159 mm) from top of fireplace opening. (Fig. 21) If a combus- tible material is used below a flat mantel shelf, consult your local building codes for minimum clearance from top of fireplace opening to bottom of mantel shelf.
Often a decorative surround or vertical portion of the mantel is desired. If this is constructed of any combus- tible material it must be within the safe zone indicated in Figure 22.
All joints (top, bottom and sides) where wall or deco- rative facing material meets fireplace surround must be completely sealed with a noncombustible material. (Figs. 20 and 21)
20006811


* Minimum width from top of surround to bottom of screen rail
Combustible materials are permitted within a shaded area shown in Figure 23 titled Minimum Wall Clearances.
*12" from top of fireplace opening for radiant models.
**6" from top of fireplace opening for radiant models. (Noncombustible material must separate the black face surround of the fireplace and any combustible mantel material.)
Fig. 21 Combustible mantel clearances.
20006811

Hearth Installation
Adjacent combustible side walls that are within the minimum dimensions shown in Figure 22 of fireplace opening must be protected with CFM Corporation Wall Shield Model SP40 or a specifically built wall shield described below.
A hearth extension is required to protect a combustible floor in front of the fireplace. Refer to Figure 22 for mini- mum dimensions and mounting detail.
The special wall shield design described in Figure 20 is an alternate method of adding protection to side walls and can be used in place of the SP40 with the same wall clearances specified for the SP40. Rt must =1.85 minimum.
The hearth extension described in Figure 22 must be a durable noncombustible material with a minimum (total) Rt value of 1.09; refer to Figure 23 for examples. The overall height (above a combustible floor), depth and width must be as indicated, with the extension centered to the fireplace opening.
The top of insulation must be covered with a noncom- bustible decorative covering or a piece of .018” mini- mum sheet metal, to protect hearth extension material. (Fig. 22)
Secure the hearth extension to the floor to prevent shifting, using trim molding or other similar means at three (3) outer edges. Seal crack between the fireplace hearth and hearth extension with a noncombustible material. (Figs. 22 and 24)
Minimum Hearth Extension Dimensions (for On-Site Construction)
WITH Noncombustible Surround Facing
WITHOUT Noncombustible Surround Facing
Shaded area starts 1/2" away from edge of unit.
4" BRICK (Example material)
E E D
F **
FIREBOX OPENING
Seal cracks between the fireplace and hearth extension with noncombustible material
May install noncombustible decorative covering OR.018" min. sheet metal FIREPLACE HEARTH
A - Min. clearance to combustible perpendicular wall
B - Min. clearance to combustible perpendicular wall when using noncombustible wall shield*
4" MIN.
Combustible material permitted within shaded area.
* Noncombustible wall shield requires 1" CFM Corporation EH2416 insulation (minimum R Value = 1.85) between decorative noncombustible rigid covering and combustible wall. Minimum height and width is 40" x 40". ** Dimension/degree of angle will vary depending on thickness of noncombustible surround facing.
MINIMUM INSULATION VALUE "R"
Safety strips must overlap ¹⁄₂" minimum
A B C D E F G H J ODSR36A 16" 12" 48° 41° 18" 14" 7³⁄₄" 16" 48" 406 mm 305 mm 457 mm 356 mm 197 mm 406 mm 1219 mm ODSR42A 20" 12" 42° 35° 18" 14" 11¹⁄₂" 20" 61¹⁄₂" 508 mm 305 mm 457 mm 356 mm 292 mm 508 mm 1562 mm
Fig. 22 Combustible side wall protection and hearth extension dimensions.
4" · 20006811

2 x 4 Header (Do not notch at standoffs)
1.09 0.50 in.**
Seal all cracks between fireplace sur- round and wall materi- als with noncombus- tible material
0.10 5.46 in.**
R Value is for 1/2 inch. * Units of K = BTU/SQ FT/HR/˚F/IN ** Thickness of Listed Material
Fig. 23 Hearth extension material factors.
Seal crack between fireplace and hearth extension with noncom- bustible material
Alternate noncombustible materials may be used pro- viding the (total) thermal resistance (Rt value) of the al- ternate material employed is greater than or equal to R = 1.09. Thermal resistance (R) or thermal conductivity (K), may be obtained from manufacturer of the material. Factors are related by the formula K = 1/R.
Safety Strips Must be overlapped 1/2" minimum
Fig. 24 Sealing gaps.
T = given thickness R = thermal resistance for a given thickness (T) K = thermal conductivity
Noncombustible material with a lower R value may be used, provided thickness of material is sufficiently greater to maintain an equivalent (total) thermal resis- tance (Rt).
To determine the thickness required for any new mate- rial:
NEW K of new material (per inch) Thickness required = X of listed thickness K of listed material (per inch) material
T (new) = 5.0/0.458 x 0/50 in. = 5.46 in. (new required thickness).

Hole in Outer Casing
Majestic Fireplaces' fireplaces are designed to accept a 1/2" (13 mm) gas line for installation of an approved gas appliance. (CFM Corporation manufactures a wide variety of gas logs for use in Majestic Firepalces.)
1" Min.
Be sure to have the appliance installed in accordance with building codes.
Gas connection may enter from either left or right side of the fireplace.
Locate appropriate gas line in the outer casing of fire- place and remove insulation from gas line tube. (Fig. 25)
From inside the fireplace, locate the knockout on the firebrick -- be sure you are on the appropriate or "gas line" side of the fireplace. Using a flat bladed screw- driver or small chisel and hammer, carefully tap around the knockout until it loosens and falls out.
Ceramic Knockout (Both sides)
Install 1/2" (13 mm) certified gas pipe through opening. After gas pipe installation is complete, use insulation that was removed from gas line tube to repack space around the pipe. Material should be inserted from outside of the fireplace and packed tightly to totally seal between the pipe and tube.
Fig. 25 Gas line access.
BTU input of a gas appliance installed in fireplace should be rated less than 100,000 BTU/Hr.
Gas pipe installation is intended for connection to a decorative gas appliance only when (1.) incorporating an automatic shutoff device and (2.) complying with the Standard for Decorative Gas Appliances for Installa- tion in Vented Fireplaces (ANSI Z21.60) or CSA draft requirements for Gas-Fired Log Lighters for Woodburn- ing Fireplaces (Draft No. 4, August 1993).
Decorative gas appliance should be installed in accor- dance with the National Fuel Gas Code, ANSI Z223.1/ NFPA 54 (latest edition).
If installing an unvented gas log set, refer to statement below:
Only unvented gas logsets which have been found to com- ply with the Standard for Unvented Room Heaters, ANSI Z21.11.2, are to be installed in this fireplace.


CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time, without notice.
Item/Model Number ODSR36A ODSR42A 1. Damper Weld Assembly RP199 RP199 2. Damper Bracket 3030176 3030176 3. Screen Rod Assembly 20006805 20006863 4. Screen Assembly (two per fireplace) 20006583 20006861 5. Screen Pulls 20002225 20002225 6a. Firebrick - Hearth 20005621 20005421 6b. Firebrick - Rear 20005627 20005462 6c. Firebrick - Right Side 20005626 20005461 6d. Firebrick - Left Side 20005625 20005460 6e. Firebrick - Ashlip 20005619 20005418 7. Top Brick Retainers (three per fireplace) 3030172 3030172 8. Cable Clips (four per fireplace) 20006869 20006869 9. Outer Collar Assembly (SK8 Chimney) 3030143 3030143 10. Basket Grate 20006701 20002230 11. O.S.A. Assy. 20003076 20003076
20006811

The following accessories for this appliance are available from your local Majestic Fireplaces distributor. Should you need additional information beyond what your distributor can furnish, contact: CFM Corporation, 2695 Meadowvale Blvd., Mississauga, Ontario, Canada L5N 8A3, Attn: Technical Services.
Glass Door — Standard Bi-Fold door set Brushed Brass finish 36GDKBBSR (ODSR36A) 42GDKBBSR (ODSR42A) Black finish 36GDKBKSR (ODSR36A) 42GDKBKSR (ODSR42A) Polished Brass finish 36GDKDBSR (ODSR36A) 42GDKDBSR (ODSR42A) Pewter finish 36GDKSSR (ODSR36A) 42GDKSSR (ODSR42A) Stainless Steel 36GDKSSSR (ODSR36A) 42GDKSSSR (ODSR42A) Outside Air Kit Complete kit for connection from fireplace AKU1 to out-of-doors Chimney Adapter Converts fireplace to 3-wall system TWABR Hearth Extension Insulation Provides hearth extension floor protection EH2416 Hearth Patch Compound Patch cracks in hearth HPC-1
Contact your Majestic Fireplaces distributor or dealer for finishing Marble and Mantels, available in a wide selection of styles.
20006811

U.S.
Model Number Description Component
Round Top Termination Top used to terminate chimney at roof. RLTSK8 (Flashing not included.) Round Top Termination - Top used to terminate chimney at chase. RLTSK8L Extended (Flashing not included.) Flashing Metal finishing required around Contemporary 8-6-12 with 8" flue: Termination to prevent rain leakage. 0-6/12 pitch 8-12-12 with 8" flue: 6/12-12/12 pitch Square Termination Top housing of simulated brick pattern S20B (R, T, W) Housing available in red, tan or white. Appropriate Must also include: adapter required. Flashing included. PLTSK8 or SLTSK8 Adapter Kit Unites Square Termination with chimney CF8CA pipe (required). Housing Extensions Extends Square Termination on steep 202036 pitched roofs. Square Chase Termination Housing used to terminate chimney through CT100 a chase top. Appropriate adapter required. (Flashing not included.) Adapter Kit Unites Square Chase Termination with chimney CTSK pipe (required). Chase Top Housing Low profile pyramid-style chimney cap used to PLTSK8 terminate chimney through a chase. Includes adapter. (Flashing not included.) Chase Top Housing Square chimney cap used to terminate chimney SLTSK8 through a chase. Terra Cotta Masonry. Includes adapter. (Flashing not included.) SK8 Chimney Sections Pipe used to build 8" (SK8) flue systems. SK81 (1' Long) SK818 (1¹⁄₂' Long) SK83 (3' Long) SK84 (4' Long) SK8 Chimney Elbows Elbow used to create an offset in an 8" SK830-2 chimney system. Only 30˚ elbows available. Packaged 2 per carton (offset and return). Firestop Required at each floor level of chimney SKFS2A — installation. (Plus attic on multi-story installation.) (8" straight flue) SKFS6A — (8" 30˚ inclined flue) Chimney Support Used to support chimney for each of: 30' vertical SKCS8 height and 6' of angled chimney run.
20006811

Canada
Model Number Description Component
Chimney Collar Enclosure Installs on the "over the chimney collar" of the CCE-SK fireplace; provides outside air to assist in cooling the chimney system. Attic Insulation Shield Used to prevent insulation from coming in AIS-SK contact with the chimney system. SK8 Chimney Sections Used to build chimney systems exposed above SK818CAN (1¹⁄₂' Long) roof. SK84CAN (4' Long) 45˚ Chimney Elbows Provides 45˚ offset and return. For Canadian SK845/2 installations only. For use with SK8 chimney only. (Maximum use of 2, or 1 pair.)
20006811

20006811

CFM Corporation warrants its MAJESTIC FIREPLACES® Pre- Engineered Fireplace (“Fireplace”) and the CFM Corporation sup- plied firegrate, glass doors, outside air system, fan motor, and liners to be free from defects in material or workmanship, as follows:
(2) This warranty is non-transferrable, and is made to the original owner, provided that the purchase was made through an authorized supplier of the Company. (3) The sole and exclusive remedies for breach of any warran- ties hereunder shall be for the repair, replacement or provision of a replacement part at CFM Corporation then current list price, FOB CFM Corporation factory, for any defective part as specified in paragraphs A through D. (4)CFM Corporation shall not be liable for damage from any smoking of a MAJESTIC FIREPLACES Pre-Engineered Fireplace System related to environmental geographic conditions (such as, for example, nearby structures or roof peaks, trees, hills, or moun- tains), inadequate ventilation, or negative air pressure in the place where the Fireplace system is installed, related to any mechani- cal system (such as, for example, furnaces, fans, air conditioners, clothes dryers, etc.) (5) Except as otherwise expressly specified in paragraphs A through D, NONE OF THESE WARRANTIES COVER, AND CFM CORPORATION SHALL NOT BE RESPONSIBLE FOR, ANY CON- STRUCTION, INSTALLATION, LABOR, TRANSPORTATION OR OTHER COSTS OR EXPENSES ARISING FROM A DEFECTIVE PART, ITS REPAIR OR REPLACEMENT OR OTHERWISE, NOR SHALL CFM CORPORATION IN ANY EVENT BE RESPONSIBLE FOR ANY INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAM- AGES EXCEPT TO THE EXTENT REQUIRED BY LAW. Some states do not allow the exclusion or limitation of incidental or conse- quential damages, so this exclusion or limitation may not apply to you. NO IMPLIED WARRANTIES, INCLUDING THE IMPLIED WAR- RANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTIC- ULAR PURPOSE, SHALL REMAIN IN EFFECT AFTER THE EXPI- RATION OF THE WARRANTIES SET FORTH IN PARAGRAPHS A THROUGH D. Some states do not allow limitations on how long an implied warranty lasts, so this limitation may not apply to you. In order to obtain performance of any of the above warranty obligations write to CFM Corporation at this address: CFM Corporation 2695 Meadowvale Blvd. Mississauga, Ontario, Canada L5N 8A3 Attention: Director of Warranty Services Since local building requirements may vary greatly throughout the country, users of CFM Corporation products should determine in advance whether there are any building code restrictions on the use of a specific product. CFM CORPORATION MAKES NO REP- RESENTATION OR WARRANTY REGARDING, AND SHALL NOT BE RESPONSIBLE FOR, ANY BUILDING CODE COMPLIANCE. The foregoing warranties give you specific legal rights and you may also have other rights which vary from state to state.
A. Fireplace and Chimney Components: (exclusive of CFM Corporation-supplied firegrate, glass doors, outside air system, fan motor, and liners all of which are covered by separate warranties under paragraphs B through D below): At its option for a period of thirty (30) years from the date the Fireplace is installed, CFM Corporation will; (1) For a period of five (5) years from the date the Fireplace is installed, CFM Corporation, at its option, will repair or replace any defective part without charge. (2) Thereafter, through the 10th year after the date the Fireplace is installed, if replacement parts are available, CFM Corporation will provide a replacement for any defective part without charge for the part itself. The consumer must pay for everything else other than the part. (3) Thereafter, through the 30th year after the date the Fireplace is installed, if replacement parts are available,CFM Corporation will provide a replacement for any defective part at a cost to the consumer of CFM Corporation then current list price, FOB CFM Corporation factory.
B. Firegrate, Glass Doors, Outside Air System: For a period of 90 days from the date the Fireplace is installed CFM Corporation, at its option, will provide a replacement for any defective part, without charge for the part itself, FOB CFM Corpora- tion factory, (The consumer must pay for everything else other than the part,).
C. Fan Motor: (1) For a period of one (1) year from the date the Fireplace is installed, CFM Corporation, at its option, will repair or replace any defective part without charge. (2) Thereafter, through the 30th year after the date the Fireplace is installed CFM Corporation, at its option, if replacement parts are available, will provide a replacement for any defective part at a cost to the consumer of CFM Corporation then current list price, FOB CFM Corporation factory.
D. Liners (Refractory or Metal): (1) For a period of two (2) years from the date the Fireplace is installed, CFM Corporation, at its option, will repair or replace any defective part without charge. (2) Thereafter, through the 30th year after the date the Fireplace is installed CFM Corporation, if replacement parts are available, will provide a replacement for any defective part at a cost to the consumer of CFM Corporation then current list price, FOB CFM Corporation factory. This warranty is subject to the following conditions and limitations: (1) This warranty is extended only to a Fireplace installed in the continental United States, the state of Alaska and Canada; only if and so long as the Fireplace is installed according to the installation instructions furnished with the Fireplace, and operated at all times under normal conditions, use and service according to the operative instructions furnished with the Fireplace, and only if and so long as the Fireplace is not removed from its original installation.
20006811