BR/BC Series Woodburning Fireplace
Homeowner's Installation and Operating Manual

For use in U.S./Canada Underwriter's Laboratories Report No. MH6018
DO NOT DISCARD THIS MANUAL: Retain for future use.
7412944 6/05 Rev. 16


CHIMNEY FLUE EXI T
RISE
CHIMNEY SECTION
30˚ RETURN
ELBOW
B G
A
G
30˚ OFFSET
D
E 6 FT.
RISE
30˚ RETURN
SKCS8 SUPPORT
H
ELBOW
OFFSET
H
30˚ OFFSET
B
ELBOW
HEARTH FLOOR
Example 1 Example 2 Example 3
Illustration Key
C. The chimney cannot be more than 30˚ (45˚ in Canada) from the vertical plane in any installation*.
The following safety rules apply to offset installations (letters correspond with illustration above):
D. The maximum length of the angled run of the total chimney system is 20 feet. (G plus H cannot exceed 20 feet.)
A. Height of the chimney is measured from the hearth to the chimney exit. BR/BC36 BR/BC42 Maximum: 90'0" 90'0" Minimum: Without Elbows 12' 6" 12' 6" With 2 Elbows* 14' 6" 14' 6" With 4 Elbows* 21' 0" 21' 0"
E. A chimney support (Model SKCS8) is required every 6 feet of angled run of chimney. Chimney supports are required for every 30 feet and 60 feet (SK8 pipe) or 20 feet and 40 feet (3-wall pipe) of ver- tical chimney height above the hearth.
Determine the offset distance of your chimney arrangement from the centerline of the fireplace to the centerline of the chimney where it is to pass through the first ceiling.
B. Do not use more than 4 elbows per chimney.
Attach the straps of the return (top) elbow to a structural framing member.
The offset (first) elbow of any pair does not have straps.
* In Canada, two (2) SK845 are allowed.
Fig. 6. Chimney system requirements.
7412944

Preplanning an installation is very important to ensure safety and to save time and money. An installer must predetermine where a fireplace will be set and how the chimney system will be run.
Major U.S. building codes specify a minimum chimney height above the roof top. The “Ten Foot Rule” is a fire safety rule and not a draft rule. To ensure proper draft, it is recommended that you always meet or exceed the “Ten Foot Rule,” especially when installing a termination on a high pitch roof. (Fig. 8)
A fireplace may only be mounted on the following sur- faces:
The key points of the "Ten Foot Rule" are:
1. If the horizontal distance from the chimney to the peak of the roof is 10' (3m) or less, the top of the chimney must be at least 2' (610mm) above the peak of the roof, but never less than 3' (914mm) in height above the highest point where it passes through the roof. 2. If a horizontal distance from the chimney to the peak of the roof is more than 10' (3m), a chimney height reference point is established on the surface of the roof a distance of 10' (3m) from the chimney in a horizontal plane. The top of the chimney must be at least 2' (610mm) above the reference point, but never less than 3' (914mm) in height above the high- est point where it passes through the roof.
The fireplace must be spaced 1/2" (13mm) from a com- bustible back wall and 1/2" (13mm) from a combustible side wall or support. (Page 14, Fig. 20)
INSTALLED
LT MODEL SK 2 WALL CHIMNEY
LENGTH
(LT)
(L1)
SK81 SK818 SK83 SK84
11¹⁄₂" 17¹⁄₂" 35¹⁄₂" 47¹⁄₂"
10¹⁄₂" 16¹⁄₂" 34¹⁄₂" 46¹⁄₂"
2' Min.
3' Min.
2' Min.
3' Min.
Fig. 7 Installed lengths of chimney sections.
Determine how the chimney will be run, length of run and chimney components required to complete the job. (Fig. 6) Never install a chimney below minimum heights.
In planning a chimney system, it is important to know:
Fig. 8 Ten Foot Rule illustration.
1. The height of a chimney is measured from the hearth to the exit point on the termination. 2. A chimney cannot be offset more than 30° from a vertical plane. 3. A chimney may run straight up or it may be neces- sary to offset it to avoid obstructions. 4. The maximum length of an angled run (total chimney system) is 20' (6 m). 5. No more than 2 offsets (4 total 30° elbows in U.S./or 2 total 45° elbows in Canada) per fireplace may be used. 6. A guy wire stabilizer is required for chimneys extend- ing more than 6' (1.8 m) above a roof line.

The chimney system is supported by the fireplace for vertical chimney heights less than 30' (9m) above the hearth. Chimney supports are required if the vertical height exceeds 30' (9m) with SK8 chimneys or 20' (6m) with 3-wall chimneys. Locate chimney supports at ceiling holes or other structural framing at 30' (9m) (SK8) or 20' (6m) (3-wall) heights. Spacing between chimney supports must not exceed 30' (9m) (SK8) or 20' (6m) (3-wall). Use Chimney Support Model SKCS8. (NOTE: The SKCS8 can not be mounted directly to the fireplace.) Support provided by elbow straps fulfills the support requirement only if they are spaced as previously described. (A chimney support is 2¹⁄₂" (64mm) long when installed.)
for Cold Climates
If you live in a cold climate, it is not required but highly recommended that you insulate fireplace enclosure to eliminate cold air penetration as much as possible.
Insulate base of fireplace with a noncombustible insulation rated for a minimum of 300°F. Insulating is very important for outside wall installations over a concrete slab. If fireplace is installed on a platform, insulation should be placed on top of the platform before fireplace is set. (Fig. 10)
When a fireplace is installed in a chase or on a outside wall, enclosure should be treated like any outside wall in a home. Insulation should be installed on the inside wall as well as the outside wall(s). In a chase, it is also a good idea to install a firestop at the first ceiling level above the fireplace and enclose the chase with sheeting material. Insulation may then be installed above sheeting material to assure the space around the fireplace is totally protected. (Fig. 5)
Angled chimney runs require a support every 6' (1.8m) in addition to the elbow straps. Chimney supports are used for this function. (Fig. 9)
A chase is a vertical box-like structure which encloses the fireplace and/or chimney. Chases are typically built on the outside of the house with fireplace opening cut into the outer wall of a room. (Page 5, Fig. 5)
When installing the chimney, DO NOT caulk between outer pipe and firestop. It is vital that some air be al- lowed to flow through this very thin gap.
If you need help in determining fireplace location or how the chimney system should be run, contact your Majestic Fireplaces dealer for assistance.
Fig. 9 Chimney support installation
Chimney Sup- port Strap · 7412944

Option For Circulating Models Only —
Framing can be constructed before or after the fire- place is set in place, however, most installers build the frame before setting the fireplace.
Frame fireplace with 2 x 4 lumber or heavier materials. Refer to framing dimensions in Figures 1, 2, 3 or 4 for basic fireplace specifications.
Once fireplace is secured, complete wiring the fan kit. Remove knockout in the center of the back of the EB1 and install listed cable clamps. Feed electrical wire through listed cable clamp leaving approximately 6" (152 mm) of wire exposed through the EB1. Se- cure listed cable clamp to the wire.
Attach white wire from power source to one (1) wire of receptacle and secure with nut. Attach black wire from power source to the other wire of receptacle and secure with nut. Be sure nuts are secured tightly.
(for Circulator Models)
Secure EB1 assembly to inside of electrical box coverplate using two screws. Attach cover to face of the EB1 while being careful to position excess wire completely within the EB1, then attach coverplate to fireplace.
If a circulating fireplace is to be installed, run the 120 VAC, 60 Hz wiring to the left side of installation. Wiring must be completed before the fireplace is secured and finish material applied.
Remove the cover plate and electrical knock-out on the lower left side of the fireplace and set aside. Follow the instructions on Page 10 for proper wiring and installa- tion of the EB1.
Refer to optional Model FK12 fan kit assembly instal- lation instructions for field installation.
If the fan kit is not being installed with the fireplace, it is highly recommended that 120 VAC supply be made available since someone may elect to install a blower at a later date.
Since you have already preplanned the chimney run, you should know exactly how the installation is to be accomplished — how much pipe is required, the num- ber of elbows, if any, and type of termination to be used.
NOTE: Fireplaces may use CFM Corporation Model SK8, or Model S (three wall) chimney systems. The BR/BC Series Fireplace will accept the SK8 chimney system as is; but a TWABR adapter collar is required when using the Model S (triple wall) chimney system. The installation procedure described in this manual applies only to the SK8 system. Either chimney system may be used, but may not be mixed.
Fig. 10 Insulating between platform and fireplace.

Determine offset distance of your chimney arrangement from centerline of fireplace to centerline of chimney where it is to pass through ceiling.
To mark the centerline of the flue, put the fireplace in final position and measure out from the wall: 8¹⁄₄" (210mm)
Locate center point of the chimney on ceiling as though a straight up chimney arrangement is to be used. Mea- sure your offset dimension from straight up chimney center point on ceiling.
Mark a spot on the ceiling directly above the fireplace. Draw a line parallel to the back wall through this mark. (Fig. 11)
Using a plumb bob positioned directly over center point of fireplace flue collar, mark the ceiling to establish the chimney center point. (Fig. 11)
The size of the hole in ceiling will vary with the angle at which the chimney passes through ceiling.

Drive a nail up through ceiling at marked chimney center point. Go to floor above and see where hole will be cut. Check to see where existing ceiling joists and other possible obstructions are located...i.e. wiring, plumbing etc... If necessary, re-position chimney and/or fireplace to avoid obstructions.
Cover fireplace collar opening and cut proper sized chimney hole in chimney. The SK8 pipe allows you to run pipe through a typical 16” on center joist without cutting joists.
Frame the ceiling chimney hole as shown in Figure 12. It is good practice to use framing lumber that is the same size as the ceiling joists; this is a requirement at attic level.

A "SK" Series framing = 14¹⁄₂" X 14¹⁄₂" (368 x 368mm) B "S" Series framing = 17¹⁄₂" X 17¹⁄₂" (445 x 445mm)
Each offset requires two (2) elbows. The second elbow is equipped with support straps. It is very important to install the second elbow in each offset as close to the ceiling or support as possible so that the elbow straps can be secured to framing members to help support the weight of the chimney.
Fig. 12 Typical frame for ceiling chimney hole.
7412944

The following table gives firestop spacer model num- bers:
An outside air kit is installed in all BR/BC Series Fire- places. If desired, or if local codes mandate the use of an air kit, then an AK-MST is required to complete the installation (from air kit to the outdoors). If the outside air kit is to be used, the AK-MST MUST be installed BE- FORE the fireplace is enclosed. Refer to the AK-MST instructions for field installation.
Fig. 13 Ceiling chimney hole sizes necessary for installing firestop spacer.
The inside dimension of the frame must be the same as the hole size selected from Figure 13 in order to provide the required 1¹⁄₂" (38 mm) of air space between the outside diameter of the chimney and the edges of the framed ceiling hole.
Metal Safety Strip (1,2 or 3 pieces)
Securing the Fireplace
Slide fireplace into position.
¹⁄₂" (13mm) Min. Overlap 1¹⁄₂" (38mm)
Plat- Form Hearth Ext.
Lift the fireplace front slightly and slide the metal safety strips under front bottom edge about 1¹⁄₂" (38 mm), al- lowing the remainder to extend in front of firebox. Over- lap strips at least 1/2" (13 mm) to provide a positive joint. (Flat safety strips are packed with fireplace.) (Fig. 14)
Fig. 14 Safety strip installation.
Safety strips are used to ensure that any combustible materials in front of the fireplace are protected even though a noncombustible hearth extension is required.
If fireplace is to be elevated above the floor, a “Z” shaped metal safety strip must be fabricated and used to protect combustible surfaces in front of the fireplace. This “Z” shaped safety strip is not provided but must be fabricated of metal with each horizontal leg at least 1¹⁄₂" (38mm) wide and equal in length to the metals strips provided with the fireplace.
Fig. 15 Fasten fireplace in position.
Four (4) nailing flanges are supplied with the fireplace (found on the fireplace hearth). To level the box and secure it firmly in place, remove the nailing flanges from the hearth and install at the sides of the fireplace as shown in Figure 15.


Start by attaching the first chimney section to the collar on top of the fireplace.
Install the pipe as pictured in Figure 16. When you get a good lock, you will hear the pipe clearly snap together. Once sections are snap-locked in place, it is extremely difficult to get them apart. Make sure the pipe is firmly snapped and locked together as each pipe section is mounted.
When installing elbows, only outer pipe will snap- lock. Middle pipes simply slide into position. Be sure to always attach straps on upper elbow to a structural framing member. (Fig. 17)
Continue installing the pipe as required until pipe is installed up through the ceiling. At this point, you must install a firestop spacer.
in the Ceiling Hole
A firestop spacer is used to keep pipe spaced properly and required for safety.
Nail the firestop spacer (at each corner) to the framing members of the ceiling hole. NOTE: A firestop spacer is not required at the roof.
Hole sizes listed in Figure 13 for angled firestop spac- ers provide minimum required air space to chimney pipe for ceiling thickness up to 8" (203mm). When combined thickness of ceiling material, ceiling joists and flooring material exceeds 8" (203mm), adjustments must be made in framing to assure that minimum air spaces to chimney are maintained.
Figure 18 shows different installation procedures for both an area that is an attic and an area that is not an attic.
Fig. 17 Attach straps to a structural framing member.
If the area above the ceiling is not an attic, position the firestop spacer with the flange on the ceiling side and the angled portion ex- tending up into the hole.

If the area above the ceil- ing is an attic, position the firestop spacer with the flange on the top of the framed hole and the angled portion extending down into the hole.
Fig. 18 Installing firestop spacer.
7412944

Firestop spacers are not available for nor are they re- quired on vertical walls.
DO NOT put any sealant around the area where the outer pipe slides through the firestop spacer. If you seal this area, it may cause a fire hazard.
Insulation Shield
In Canada, an attic insulation shield is required to pre- vent attic insulation from contacting the chimney sec- tion. Framing dimensions for the chimney hole should measure 14¹⁄₂" x 14¹⁄₂" (368 x 368mm). An attic shield MUST be installed on top of attic joists (above the floor level). (Fig. 19)
Install the attic insulation shield with the flanges on its base extending down into the framing hole. Nail each corner of attic insulation shield to the framing members of the ceiling hole using 8d nails. Attic shields are not required at the roof.
Fig. 19 Attic shield installlation (Canadian requirement).
Continue Installing Pipe to Complete Run
Use same procedure detailed in locating center point of the flue system.
Continue attaching pipe sections to complete system to next level always being careful that the pipe is firmly snapped locked in place before proceeding to next pipe section.
Drive a nail up through roof at the center point. This will determine center point on outside of the roof.
Chimney Supports
Size of roof hole varies with the type of chimney termination installed. Refer to installation instructions provided with the chimney termination to find correct size of roof hole.
If chimney supports are required, they are installed the same as elbows. Nail chimney support straps to ad- jacent structural framing, as shown on Figure 9, Page 8. Bend straps as necessary and make sure they are secure so they will support the weight of the chimney. A chimney support is 2¹⁄₂" (64mm) long when installed. Consider this dimension when determining how many straight chimney sections are needed.
There must be a 1¹⁄₂" (38mm) air space between out- ermost portion of chimney sections and any adjacent combustible surfaces. (Combustible surfaces include burnable materials such as: ceiling members, joists, flooring, combustible insulation and roof structures.)
Mark an outline of the roof hole around the center of the point nail. NOTE: Hole dimensions given in the chim- ney top installation instructions are horizontal dimen- sions; therefore, the hole size must be marked on the roof accordingly.
If you encounter additional ceilings, repeat same steps required for first ceiling installation. See firestop illus- tration on Page 12, Figure 18.
Cover the opening of the installed chimney so debris cannot get into the system.
Run pipe to roofline. Since chimney system must be vented to the out-of-doors, you must use an approved termination.
Cut and frame the hole. It is good practice to use fram- ing lumber that is the same size as the rafters. Install the frame securely because the chimney top and flash- ing anchored to the frame must be able to withstand heavy winds.
If a chase is used, refer to the installation manual pro- vided with the termination cap.


Since you have already preplanned the height of your termination according to the Ten Foot Rule, continue to install pipe to the predetermined height.
Combustible framing material MUST NOT penetrate AIR SPACE (shaded areas).
Check the chimney top installation instructions for details on how high above the roof top the chimney sec- tions (all pipes) should extend.
or Termination
Follow the installation instructions provided with the chimney termination you have selected.
Refer to Page 5, Figure 5 for an illustration of a typical chase installation.
Only noncombustible material may be applied as facing to the black fireplace surround.
Finish the wall with material of your choice. Do not install a combustible mantel shelf less than 12" (305mm) from the top of the fireplace opening for radiant models and 12" (305mm) from top of grille opening for circulating models. Do not install a mantel face plate less than 6" (159mm) from top of fireplace opening for radiant models and 6" (159mm) from top of grille opening for circulating models. (Fig. 22) If a combustible material is used be- low a flat mantel shelf, consult your local building codes for minimum clearance from top of fireplace opening to bottom of mantel shelf.
Fig. 20 Minimum clearances to combustibles.
Often a decorative surround or vertical portion of the mantel is desired. If this is constructed of any combus- tible material it must be within the safe zone indicated in Figure 23.
All joints (top, bottom and sides) where wall or deco- rative facing material meets fireplace surround must be completely sealed with a noncombustible material. (Figures 21 and 22)
7412944


Mantel Clearance - Radiant Model - No Noncombustible Facing Material
Mantel Clearance - Radiant Model - with Noncombustible Facing Material
* Minimum width from top of sur- round to bottom of screen rail
Combustible materials are permitted within a shaded area shown in Figure 23 titled Minimum Wall Clearances.
*12" from top of fireplace opening for radiant models 12" from top of grille opening for circulating models **6" from top of fireplace opening for radiant models (Noncombustible material must seperate the black face surround of the fireplace from any combustible mantel material) 6" from top of grille opening for circulating models
7412944

Hearth Installation
Adjacent combustible side walls that are within mini- mum dimensions shown in Figure 23 of the fireplace opening must be protected with CFM Corporation Wall Shield Model SP40 or a specifically built wall shield described in Figure 20.
A hearth extension is required to protect a combustible floor in front of the fireplace. Refer to Figure 23 for mini- mum dimensions and mounting detail.
The special wall shield design described in Figure 20 is an alternate method of adding protection to side walls and can be used in place of the SP40 with the same wall clearances specified for the SP40. Rt must =1.85 minimum.
The hearth extension described in Figure 23 must be a durable noncombustible material with a minimum (total) Rt value of 1.09; see Figure 24 for examples. The over- all height (above a combustible floor), depth and width must be as indicated, with the extension centered to the fireplace opening.
The top of insulation must be covered with a noncom- bustible decorative covering or a piece of .018” mini- mum sheet metal, to protect hearth extension material. (Fig. 23)
Secure the hearth extension to the floor to prevent shifting, using trim molding or other similar means at three (3) outer edges. Seal crack between the fireplace hearth and hearth extension with a noncombustible material. (Figs. 23 and 25)
Minimum Hearth Extension Dimensions (for On-Site Construction)
WITH Noncombustible Surround Facing
WITHOUT Noncombustible Surround Facing
Shaded area starts 1/2" away from edge of unit
4" Brick (Example material)
E E D
F **
Seal cracks between the fireplace and hearth extension with noncombustible material
May install noncombustible decorative covering OR.018" min. sheet metal Fireplace Hearth
A - Min. clearance to combustible perpendicular wall
B - Min. clearance to combustible perpendicular wall when using noncombustible wall shield*
4" MIN.
Combustible material permitted within shaded area.
* Noncombustible wall shield requires 1" CFM Corporation EH2416 insulation (minimum R Value = 1.85) between decorative noncombustible rigid covering and combustible wall. Minimum height and width is 40" x 40". ** Dimension/degree of angle will vary depending on thickness of noncombustible surround facing.
Minimum Insulation Value "R"
Safety strips must overlap 56O" minimum
A B C D E F G H J BR/BC36 16" 12" 48° 41° 18" 14" 9" 16" 48" 406 mm 305 mm 457 mm 356 mm 229 mm 406 mm 1219 mm BR/BC42 20" 12" 42° 35° 18" 14" 12" 20" 61¹⁄₂" 508 mm 305 mm 457 mm 356 mm 305 mm 508 mm 1562 mm
Fig. 23 Combustible side wall protection and hearth extension dimensions.

2x4" HEADER - Do not notch at standoffs.
Alternate noncombustible materials may be used pro- viding the (total) thermal resistance (Rt value) of the al- ternate material employed is greater than or equal to R = 1.09 Thermal resistance (R) or thermal conductivity (K), may be obtained from manufacturer of the material. Factors are related by the formula K = 1/R. (Fig. 24)
Seal all cracks between fireplace surround and wall materials with noncombustible material.
T = given thickness R = thermal resistance for a given thickness (T) K = thermal conductivity
Noncombustible material with a lower R value may be used, provided thickness of material is sufficiently greater to maintain an equivalent (total) thermal resis- tance (Rt).
Seal crack between fireplace and hearth extension with noncombustible material.
Safety Strips - Must be overlapped ¹⁄₂" minimum.
1.09 0.50 in.**
Fig. 25 Sealing gaps.
0.10 5.46 in.**
R Value is for 1/2 inch. * Units of K = BTU/SQ FT/HR/˚F/IN ** Thickness of Listed Material
To determine the thickness required for any new mate- rial:
NEW K of new material (per inch) thickness required = X of listed thickness K of listed material (per inch) material
Fig. 24 Hearth extension material factors.
T (new) = 5.0/0.458 x 0.50 in. = 5.46 in. (new required thickness).

Hole in Outer Casing Fireplace Top View
CFM Specialty Home Products fireplaces are designed to accept a 1/2 inch gas line for installation of an ap- proved gas appliance. (CFM Specialty Home Products manufactures a wide variety of gas logs for use in CFM Specialty Home Products fireplaces.)
1" Min.
Be sure to have the appliance installed in accordance with building codes.
Gas connection may enter from either left or right side of the fireplace.
Locate appropriate gas line in the outer casing of fire- place and remove insulation from gas line tube. (Fig. 26)
Hole in Outer Casing
From inside the fireplace, locate the knockout on the firebrick -- be sure you are on the appropriate or "gas line" side of the fireplace. Using a flat bladed screw- driver or small chisel and hammer, carefully tap around the knockout until it loosens and falls out.
Ceramic Knock- out (both sides)
Install 1/2 inch certified gas pipe through opening. After gas pipe installation is complete, use insulation that was removed from gas line tube to repack space around the pipe. Material should be inserted from outside of the fireplace and packed tightly to totally seal between the pipe and tube.
Fig. 26 Gas line access.
BTU input of a gas appliance installed in fireplace should be rated less than 100,000 BTU/Hr.
Gas pipe installation is intended for connection to a decorative gas appliance only when (1.) incorporating an automatic shutoff device and (2.) complying with the Standard for Decorative Gas Appliances for Installa- tion in Vented Fireplaces (ANSI Z21.60) or CSA draft requirements for Gas-Fired Log Lighters for Woodburn- ing Fireplaces (Draft No. 4, August 1993).
Decorative gas appliance should be installed in accor- dance with the National Fuel Gas Code, ANSI Z223.1/ NFPA 54 (latest edition).
Only unvented gas log sets which have been found to comply with the Standard for Unvented Room Heaters, ANSI Z21.11.2, are to be installed in this fireplace.


CFM Specialty Home Products reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time, with out notice.
BR/BC SERIES For units: FA30C1, FA30C0, FA30R1, FA30R0, GA30C1, GA30C0, GA30R1, GA30R0, FA40C1, FA40C0, FA40R1, FA40R0, GA40C1, GA40C0, GA40R1, GA40R0
Item/Model Number BR/BC36 BR/BC42 1. Damper Blade Weld Assembly RP199 RP199 2. Damper Bracket 3030176 3030176 3. Screen Rod Assembly 3030126 3032112 4. Screen Assembly (two per fireplace) 7554338 7554340 5. Screen Pulls 7554239 7554239 6a. Firebrick - Hearth* 3030103 or 20007494 3032103 or 20007496 6b. Firebrick - Rear* 3030102 or 20007495 3032102 or 20007497 6c. Firebrick - Rt. Side* 3030160 or 20007492 3030160 or 20007492 6d. Firebrick - Lt. Side* 3030104 or 20007493 3030104 or 20007493 7. Top Brick Retainers (three per fireplace) 3030172 3030172 8. Cable Clips (four per fireplace) 7512135 7512135 9. Hearth Pan Cover (BC Only) 3031104 3031104 10. Outer Collar Assembly (SK8 Chimney) 3030143 3030143 11. Nailing Flange - Bag of 4 w/screws 2253160 2253160 12. Basket Grate 3030129 3030129 13. O.S.A. Assy. 20003076 20003076
* When ordering replacement firebrick, check the item number of the fireplace, located on the UL label inside the firebox. Item numbers with a '3' as the 3rd digit will require the firebrick listed first under the respective fireplace. Item numbers with a '4' as the 3rd digit will require the firebrick listed second under the respective fireplace.
7412944

The following accessories for this appliance are available from your local Majestic Fireplaces distributor. Should you need additional information beyond what your distributor can furnish, contact: CFM Specialty Home Products, 410 Admiral Blvd., Mississauga, Ontario, Canada L5T 2N6, Attn: Technical Services.
CAUTION: This fireplace and chimney assembly is a highly engineered system, and, as such, must be oper- ated only with CFM Specialty Home Products approved components. If you use an unapproved component to make any modifications, you may create a possible fire hazard and will void the CFM Specialty Home Products warranty. In addition, such action may void the coverage provided by the owner’s insurance.
Model Number Description Accessory
Glass Door — Standard Bi-Fold door set Brushed Brass finish 36GDKBB (BR/BC36) 42GDKBB (BR/BC42) Black finish 36GDKBK (BR/BC36) 42GDKBK (BR/BC42) Polished Brass finish 36GDKDB (BR/BC36) 42GDKDB (BR/BC42) Pewter finish 36GDKS (BR/BC36) 42GDKS (BR/BC42) Fan Kit Provides forced air flow FK12 Variable Speed Control Provides speed adjustment of fans SCVS Outside Air Termination Completes connection from air kit to out-of-doors AK-MST Hearth Extension Insulation Provides hearth extension floor protection EH2416 Grate for BR/BC36/42 Holds firewood in firebox RBBG36 Hearth Patch Compound Patch cracks in hearth HPC-1 Chimney System Adapter Converts fireplace to a 3-wall chimney system TWABR Collar
Contact your Majestic Fireplaces distributor or dealer for finishing Marble and Mantels, available in a wide selection of styles.
7412944

U.S.
Model Number Description Component
Round Top Termination Top used to terminate chimney at roof. (Flashing not included.) RLTSK8 Round Top Termination - Top used to terminate chimney at chase. Extended (Flashing not included.) RLTSK8L Flashing Metal finishing required around Contemporary 8-6-12 with 8" flue: Termination to prevent rain leakage. 0-6/12 pitch 8-12-12 with 8" flue: 6/12-12/12 pitch Square Termination - Top housing of simulated brick pattern S20B (R,T,W) Housing available in red, tan or white. Appropriate Msut include adapter required. Flashing included. PLTSK8 or SLTSK8 Adapter Kit Unites Square Termination with chimney CF8CA pipe (required). Housing Extensions Extends Square Termination on steep 202036 pitched roofs. Square Chase Termination Housing used to terminate chimney through CT100 a chase top. Appropriate adapter required. (Flashing not included.) Adapter Kit Unites Square Chase Termination with chimney CTSK pipe (required). Chase Top Housing Low profile pyramid-style chimney cap used to PTLSK8 terminate chimney through a chase. Includes adapter. (Flashing not included.) Chase Top Housing Square chimney cap used to terminate chimney SLTSK8 through a chase. Terra Cotta Masonry. Includes adapter. (Flashing not included.) SK8 Chimney Sections Pipe used to build 8" (SK8) flue systems. SK81 (1' Long) SK818 (1¹⁄₂' Long) SK83 (3' Long) SK84 (4' Long) SK8 Chimney Elbows Elbow used to create an offset in an 8" SK830-2 chimney system. Only 30˚ elbows available. Packaged 2 per carton (offset and return). Firestop Required at each floor level of chimney SKFS2A — installation. (Plus attic on multi-story installation.) (8" straight flue) SKFS6A — (8" 30˚ inclined flue) Chimney Support Used to support chimney for each of: 30' vertical SKCS8 height and 6' of angled chimney run.
7412944

Canada
Model Number Description Component
Chimney Collar Enclosure Installs on the "over the chimney collar" of the CCE-SK fireplace; provides outside air to assist in cooling the chimney system. Attic Insulation Shield Used to prevent insulation from coming in AIS-SK contact with the chimney system. SK8 Chimney Sections Used to build chimney systems exposed above SK818CAN (1¹⁄₂' Long) roof. SK84CAN (4' Long) 45˚ Chimney Elbows Provides 45˚ offset and return. For Canadian SK845/2 installations only. For use with SK8 chimney only. (Maximum use of 2, or 1 pair.)
7412944

Limited Warranty & 30 Year Protection Plan For MAJESTIC FIREPLACES® PRE-ENGINEERED Fireplace Systems
This warranty is subject to the following conditions and limitations: (1) This warranty is extended only to a Fireplace installed in the continental United States, the state of Alaska and Canada; only if and so long as the Fireplace is installed according to the installation instructions furnished with the Fireplace, and operated at all times under normal conditions, use and service according to the opera- tive instructions furnished with the Fireplace, and only if and so long as the Fireplace is not removed from its original installation. (2) This warranty is non-transferrable, and is made to the original owner, provided that the purchase was made through an authorized supplier of the Company. (3) The sole and exclusive remedies for breach of any warran- ties hereunder shall be for the repair, replacement or provision of a replacement part at CFM Specialty Home Products then current list price, FOB CFM Specialty Home Products factory, for any defec- tive part as specified in paragraphs A through D. (4)CFM Specialty Home Products shall not be liable for damage from any smoking of a MAJESTIC FIREPLACES Pre-Engineered Fireplace System related to environmental geographic conditions (such as, for example, nearby structures or roof peaks, trees, hills, or mountains), inadequate ventilation, or negative air pressure in the place where the Fireplace system is installed, related to any mechanical system (such as, for example, furnaces, fans, air condi- tioners, clothes dryers, etc.) (5) Except as otherwise expressly specified in paragraphs A through D, NONE OF THESE WARRANTIES COVER, AND CFM SPECIALTY HOME PRODUCTS SHALL NOT BE RESPONSIBLE FOR, ANY CONSTRUCTION, INSTALLATION, LABOR, TRANS- PORTATION OR OTHER COSTS OR EXPENSES ARISING FROM A DEFECTIVE PART, ITS REPAIR OR REPLACEMENT OR OTH- ERWISE, NOR SHALL CFM SPECIALTY HOME PRODUCTS IN ANY EVENT BE RESPONSIBLE FOR ANY INDIRECT, INCIDEN- TAL OR CONSEQUENTIAL DAMAGES EXCEPT TO THE EXTENT REQUIRED BY LAW. Some states do not allow the exclusion or limitation of incidental or consequential damages, so this exclusion or limitation may not apply to you. NO IMPLIED WARRANTIES, INCLUDING THE IMPLIED WAR- RANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTIC- ULAR PURPOSE, SHALL REMAIN IN EFFECT AFTER THE EXPI- RATION OF THE WARRANTIES SET FORTH IN PARAGRAPHS A THROUGH D. Some states do not allow limitations on how long an implied warranty lasts, so this limitation may not apply to you. In order to obtain performance of any of the above warranty obligations write to CFM Specialty Home Products at this address: CFM Specialty Home Products 410 Admiral Blvd. Mississauga, Ontario, Canada L5T 2N6 Attention: Director of Warranty Services Since local building requirements may vary greatly throughout the country, users of CFM Specialty Home Products products should determine in advance whether there are any building code restrictions on the use of a specific product. CFM SPECIALTY HOME PRODUCTS MAKES NO REPRESENTATION OR WAR- RANTY REGARDING, AND SHALL NOT BE RESPONSIBLE FOR, ANY BUILDING CODE COMPLIANCE. The foregoing warranties give you specific legal rights and you may also have other rights which vary from state to state.
CFM Specialty Home Products warrants its MAJESTIC FIRE- PLACES® Pre-Engineered Fireplace (“Fireplace”) and the CFM Specialty Home Products supplied firegrate, glass doors, outside air system, fan motor, and liners to be free from defects in material or workmanship, as follows:
A. Fireplace and Chimney Components: (exclusive of CFM Spe- cialty Home Products-supplied firegrate, glass doors, outside air system, fan motor, and liners all of which are covered by separate warranties under paragraphs B through D below): At its option for a period of thirty (30) years from the date the Fireplace is installed, CFM Specialty Home Products will; (1) For a period of five (5) years from the date the Fireplace is installed, CFM Specialty Home Products, at its option, will repair or replace any defective part without charge. (2) Thereafter, through the 10th year after the date the Fireplace is installed, if replacement parts are available, CFM Specialty Home Products will provide a replacement for any defective part without charge for the part itself. The consumer must pay for everything else other than the part. (3) Thereafter, through the 30th year after the date the Fireplace is installed, if replacement parts are available,CFM Specialty Home Products will provide a replacement for any defective part at a cost to the consumer of CFM Specialty Home Products then current list price, FOB CFM Specialty Home Products factory.
B. Firegrate, Glass Doors, Outside Air System: For a period of 90 days from the date the Fireplace is installed CFM Specialty Home Products, at its option, will provide a replace- ment for any defective part, without charge for the part itself, FOB CFM Specialty Home Products factory, (The consumer must pay for everything else other than the part,).
C. Fan Motor: (1) For a period of one (1) year from the date the Fireplace is installed, CFM Specialty Home Products, at its option, will repair or replace any defective part without charge. (2) Thereafter, through the 30th year after the date the Fire- place is installed CFM Specialty Home Products, at its option, if replacement parts are available, will provide a replacement for any defective part at a cost to the consumer of CFM Specialty Home Products then current list price, FOB CFM Specialty Home Prod- ucts factory.
D. Liners (Refractory or Metal): (1) For a period of two (2) years from the date the Fireplace is installed, CFM Specialty Home Products, at its option, will repair or replace any defective part without charge. (2) Thereafter, through the 30th year after the date the Fireplace is installed CFM Specialty Home Products, if replacement parts are available, will provide a replacement for any defective part at a cost to the consumer of CFM Specialty Home Products then current list price, FOB CFM Specialty Home Products factory.