® USB
OmniSmart
™ & SmartPro
Register on-line today for a chance to win
a FREE Tripp Lite product! www.tripplite.com/warranty
Important Safety Instructions 2
Quick Installation 3
Basic Operation 4
Storage & Service 7
Specifications 8
Español 9
Français 17
1111 W. 35th Street Chicago, IL 60609 USA Customer Support: (773) 869-1234 • www.tripplite.com
Copyright © 2003 Tripp Lite. All rights reserved. OmniSmart™is a trademark of Tripp Lite. SmartPro® is a registered trademark of Tripp Lite.

Quick Installation
SAVE THESE INSTRUCTIONS This manual contains instructions and warnings that should be followed during the installation, operation and storage of all Tripp Lite UPS Systems. Failure to heed these warnings will void your warranty.
Connect your UPS to an electrical outlet. Your UPS will run a self-test after it is plugged in. See Basic Operation to understand the results of its self-test.

Plug your computer, monitor and other equipment into the UPS system. Your UPS is designed to support only com- puter equipment. You will overload your UPS if you connect high power draw equipment such as household appliances or laser printers to outlets providing UPS battery backup. Select models feature special outlets (clearly labeled on the rear panel) which provide surge-only (not battery backup) protection designed for laser printers and other heavy- draw devices.
Select UPS Operating Mode.* Press the ON/OFF button to toggle your UPS between the UPS (“ ” LED lit) and the CHARGE ONLY (“ ” LED flashing) modes. Choose the operating mode based on your location:
USA, Canada & Western Europe: • Leave the UPS in the UPS mode at all times.
All other countries: • Put the UPS in the CHARGE ONLY mode when you are not using connected equipment.
(WARNING! When set to “CHARGE ONLY,” the UPS will not provide battery backup during a blackout or brownout)
*See Basic Operation section for a complete explanation of each mode.

Basic Operation continued
These connections are optional. Your UPS will function properly without these connections.
(Select models only) Your UPS has either jacks which protect against surges over a phone or network dataline or jacks which protect against surges on a phone line only. See Specifications to determine which jacks your model has.
Cold-Start Your UPS: You may “cold start” your UPS and use it as a stand-alone power source when utility power is not present, providing that the UPS battery is charged. To “cold start” your UPS, press and hold the ON/OFF button until you hear a beep (about 2 seconds), then release it. The “ ” indicator light will illuminate and AC power inverted from stored battery power will be provided at its receptacles.
Using telephone cords or network data cables as appropriate, connect your wall jack to the UPS jack marked “IN.” Connect your equipment to the UPS jack marked “OUT.” Make sure the equipment you connect to the UPS’s jacks is also protected against surges on the AC line.
Shut Down Your UPS: Press and hold the ON/OFF button when AC line power is absent (i.e. during a blackout, or when the UPS is unplugged) to deactivate your UPS.
Use the MUTE/TEST button to do two things:
USB Communications Use any USB cable to connect the USB port of your computer to the USB port of your UPS. Download the PowerAlert UPS monitoring software program appropriate for your operat- ing system from www.tripplite.com and install it on your computer.
Silence the UPS On-Battery Alarm: Press and hold this button to silence the UPS On-Battery alarm, a series of short beeps followed by a brief pause that is activated when the UPS is providing AC power from battery. Note: When the battery is nearly depleted, the Low Battery alarm—a continuous beep that cannot be silenced—will alert you to immediately shut down connected equipment.
Run a Self-Test: Your UPS performs a self-test whenever it is first plugged in. To have it run a self-test at another time, leave your con- nected equipment on. With your UPS plugged in and in the UPS mode, press and hold this button until you hear a beep (about 2 seconds) then release it.
Results of a Self-Test: All the LEDs* will be lit and the UPS will emit several short beeps as it momentarily switches to battery to test its charge and load capacity. The test will last at most 10 seconds. If the inverter is overloaded, the “ ” LED (on select models) will stay lit and the UPS will continue to beep after the test; if this happens, remove some of the load and run the self-test again. If the batteries seem weak, the “ ” LED will stay lit and the UPS will continue to beep after the test; if this happens, let UPS charge its batteries for 12 hours and repeat the test. If the condition persists, contact Tripp Lite for service. CAUTION: Do not unplug your UPS to test its batteries. This will remove safe electrical grounding and may introduce a damaging surge into your network connections.
Use the ON/OFF button to do three things:
Switch your UPS’s Operating Mode: While your UPS is plugged into a live AC outlet, press the ON/OFF button and hold it until you hear a beep (about 2 seconds) to toggle between the following operat- ing modes. Choose your UPS’s operating mode based on the regional guidelines in Step 3 of the Quick Installation section.
* Depending on the condition of the incoming voltage the “VOLTAGE REGULATION” LED may or may not be lit.

Basic Operation continued
USB Port: The USB port connects your UPS to any USB workstation or server. Using this port, your UPS can communicate line-fail and low-battery status to your computer. Use with Tripp Lite software and any USB cable to automatically save open files and shut down equip- ment during a blackout. Contact Tripp Lite Customer Support or con- sult your power protection software manual for more information.
All Indicator Light descriptions apply when the UPS is plugged into an AC outlet and turned on.
LINE POWER: This green light will turn ON whenever your UPS is receiving normal AC line power. It will flash while the UPS is in CHARGE ONLY mode to indicate that the UPS will not provide battery backup during a black- out or brownout.
Battery Replacement Door: Under normal conditions, the original bat- tery in your UPS will last several years. Battery replacement should be performed only by qualified service personnel. Refer to “Battery Warnings” in the Safety section on page 2.
BATTERY POWER: This yellow light will turn ON when your UPS is pro- viding your equipment with battery power.
BATTERY CHARGE: This red light will turn ON continuously after the UPS runs a self-test to indicate that the UPS’s battery is weakly charged. If it remains lit after you have allowed the UPS to charge for twelve hours and have run a second self-test, contact Tripp Lite for service.
Power Sensitivity/Lowline Adjustment: This dial is normally set fully counterclockwise, which enables the UPS to protect against waveform distortions in its AC input. When such distortion occurs, the UPS will normally switch to providing PWM sinewave power from its battery reserves for as long as the distortion is present. In some areas with poor utility power or where the UPS’s input power comes from a backup generator, frequent brownouts and/or chronic waveform distortion could cause the UPS to switch to battery too often, draining its battery reserves. You may be able to reduce how often your UPS switches to battery due to waveform distortion or brownouts by experimenting with dif- ferent settings for this dial. As the dial is turned clockwise, the UPS becomes more tolerant of variations in its input power’s AC wave- form and reduces the voltage point at which it switches to battery. NOTE: The further the dial is adjusted clockwise, the greater the degree of waveform distortion and the lower the input voltage the UPS will allow to pass to connected equipment. When experimenting with dif- ferent settings for this dial, operate connected equipment in a safe test mode so that the effect on the equipment of any waveform distortions in the UPS’s output can be evaluatedwithout disrupting critical operations. The experiment should last long enough to assure that all expected line con- ditions are encountered.
OVERLOAD (Select models only): This red light will turn ON continuously when the UPS is providing power from battery or after the UPS runs a self-test to indicate that the UPS’s inverter is overloaded. If it lights up, immediately remove some of the equipment connected to the UPS and run a self-test. Large overloads may cause your UPS to shut down.
VOLTAGE REGULATION (Select models only): This light will turn ON when your UPS is automatically correcting high or low utility line voltage. The UPS will also click gently when this automatic voltage regu- lation is operating. These are both normal functions of your UPS, and no action is required on your part.
AC Receptacles: “UPS/Surge” receptacles are used to provide your con- nected equipment with AC line power during normal operation and bat- tery power during blackouts and brownouts. They also protect your equip- ment against damaging surges and line noise. “Surge-only” receptacles (identified on the back of select UPS models) are used to provide periph- erals with surge protection without committing precious battery power to support them during blackouts.
Automatic Voltage Regulation: During brownouts, your UPS will auto- matically correct low AC line voltage. When automatic voltage regulation is operating, your UPS may be heard to click gently. This is a normal, auto- matic operation of your UPS, and no action is required on your part.
Telephone/Network Protection Jacks (Select models only): These jacks protect your equipment against surges over a telephone or data line. Your UPS has either jacks which can be used with both phone and data lines, or jacks which can be used with phone lines only. See Specifications to deter- mine what kind of jacks your UPS has. Connecting your equipment to these jacks is optional. Your UPS will work properly without this connection.
Storage All connected equipment should be turned off, then disconnected from the UPS to avoid bat- tery drain. Unplug your UPS from its AC receptacle, then press and hold its ON/OFF button to deactivate it. Your UPS is now ready for storage. If you plan on storing your UPS for an extend- ed period of time, fully recharge the UPS batteries once every three months by plugging the UPS into a live AC outlet and letting the UPS charge for 4 to 6 hours. If you leave your UPS bat- teries discharged for an extended period of time, they will suffer a permanent loss of capacity.
Service If returning your UPS for service, contact your local Tripp Lite dealer or distributor. They will refer you to a service center. Please carefully pack the UPS using the ORIGINAL PACKING MATERIAL that came with the unit. Enclose a letter describing the symptoms of the problem. If the UPS is within the warranty period, enclose a copy of your sales receipt.

Manual de operación
Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
SmartPro® USB UPS Systems Model: SMART500USB SMART550USB SMART700USB Series: 163620U1 AGSM500USBKJR6 AGOM1000USBKSR6
Input Voltage/Frequency: 120V/60 Hz 120V/60 Hz 120V/60 Hz On-Line Input Voltage Range: 83 - 147 volts 83 - 147 volts 83 - 147 volts Output Capacity (VA/Watts): 500/300 550/300 700/450 Battery Runtime (Half Load/Full Load) Minutes: 17/5 17/5 20/6 Battery Recharge Time: 2-4 hrs. 2-4 hrs. 2-4 hrs. Approvals: UL, cUL, NOM, FCC-B UL, cUL, NOM, FCC-B UL, cUL, NOM, FCC-B Tel/Fax/Data Protection: 1-line tel/DSL 1-line tel/DSL 1-line tel/DSL/Ethernet
™ y SmartPro
® USB
Entrada / salida de 120V, sistemas UPS interactivos en línea
Input Voltage/Frequency: 120V/60 Hz 120V/60 Hz 120V/60 Hz 120V/60 Hz On-Line Input Voltage Range: 83-147 volts 75 - 147 volts 75 - 147 volts 75 - 147 volts Output Capacity (VA/Watts): 300/180 500/300 700/425 850/600 Battery Runtime (Half Load/Full Load) Minutes: 17/5 17/5 22/7 26/9 Battery Recharge Time: 2-4 hrs. 2-4 hrs. 2-4 hrs. 2-4 hrs. Approvals: UL, cUL, NOM, FCC-B UL, cUL, NOM, FCC-B UL, cUL, NOM, FCC-B UL, cUL, NOM, FCC-B Tel/Fax/Data Protection: 1-line tel/DSL 1-line tel/DSL 1-line tel/DSL/Ethernet None
Input Voltage/Frequency: 120V/60 Hz 120V/60 Hz 120V/60 Hz On-Line Input Voltage Range: 83 - 147 volts 75 - 147 volts 75 - 147 volts Output Capacity (VA/Watts): 1000/500 1050/705 1400/940 Battery Runtime (Half Load/Full Load) Minutes: 17/5 23/7 24/8 Battery Recharge Time: 2-4 hrs. 2-4 hrs. 2-4 hrs. Approvals: UL, cUL, NOM, FCC-B UL, cUL, NOM, FCC-B UL, cUL, NOM, FCC-B Tel/Fax/Data Protection: 1-line tel/DSL None None
ALL UNITS: Output Waveform Line Mode (filtered sinewave); Output Waveform Battery Mode (PWM sine wave); AC Surge Suppression (exceeds IEEE 587 Cat. A & B standards); AC Noise Attenuation (>40 dB at 1MHz); AC Protection Modes (H to N, H to G, N to G).
FCC RADIO/TV INTERFERENCE NOTICE: Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy, and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interfer- ence to radio or television reception, which can be determined by turning the device off and on, the user is encouraged to try to correct the interference using one or more of the following measures: reorient or relocate the receiving antenna; increase the separation between the equipment and receiver; connect the equipment into an outlet on a circuit different from that which the receiver is connected; consult the dealer or an experienced radio/television technician for help. The user must use shielded cables and connectors with this product. Any changes or modifications to this product not expressly approved by the party respon- sible for compliance could void the user's authority to operate the equipment.
CONSUMER INFORMATION AND FCC REQUIREMENTS (U.S. only):
EQUIPMENT ATTACHMENT LIMITATIONS (Models with the Industry Canada label in Canada only): NOTICE: The Industry Canada label identifies certified equipment. This certification means that the equip- ment meets the telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements Document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that the compliance with the above conditions might not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecom- munications company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas. Caution: Users should not attempt to make connections themselves, but should contact the appropriate electric inspection authority, or electrician, as appropriate.
Tripp Lite warrants, for the lifetime of the product, (at Tripp Lite’s option) to repair or replace (on a pro rata basis) directly connected equipment that is damaged due to power transients while properly connect- ed to Tripp Lite products offering the Ultimate Lifetime Insurance Policy. Power transients include spikes and surges on the AC power, data or telephone lines that the Tripp Lite products have been designed to protect against (as recognized by industry standards).
AC Power Line Transients: To claim damages, the Tripp Lite product must be plugged into a properly wired and grounded outlet. No extension cords or other electrical connections may be used. The installation must comply with all applicable electrical and safety codes set forth by the National Electrical Code (NEC). Except as provided above, this warranty does not cover any damage to properly connected electron- ic equipment resulting from a cause other than an “AC power transient”. If user meets all of the above requirements, Tripp Lite will repair or replace (at Tripp Lite’s option) equipment up to the specified value (See Ultimate Lifetime Insurance Policy Limits). No coverage is allowed for damage entering from telephone or data lines, unless they are separately protected, as described below.
Telephone and Data Line Transients: Tripp Lite will repair or replace directly connected equipment that is damaged by transients on telephone and/or data lines only when all such paths are protected by a Tripp Lite protection product(s) and the AC power (utility) line is simultaneously protected by a Tripp Lite power protection device (UPS, surge suppressor or line conditioner) with Ultimate Lifetime Insurance cover- age. Additional telephone and/or data line connected devices downstream must have their own telephone and/or dataline protectors.
Reimbursement dollar limits will be equal to that of the Tripp Lite power protection protector. Coverage is excluded where a suitable environment for the protection device is not provided, including, but not lim- ited to, lack of a proper safety ground. Telephone service equipment must also include a properly installed and operating “primary protection” device at the telephone service entrance (such devices are normal- ly added during telephone line installation).
All above warranties are null and void if the Tripp Lite product has been improperly installed, tampered with or altered in any way, or if the connected equipment was not used under normal operating conditions or in accordance with any labels or instructions. All claims under this warranty must be submitted in writing to Tripp Lite within 30 days of the occurrence or the claim will not be considered. This warranty does not include damage resulting from accident or misuse, and applies to the domestic (USA & Canada) use of these products only.
Tripp Lite reserves the right to determine whether the damage to the connected equipment is due to malfunction of the Tripp Lite product by requesting the equipment in question be sent to Tripp Lite for exam- ination. This policy is above and beyond, only to the extent needed, of that provided by any coverage of connected equipment provided by other sources, including, but not limited to, any manufacturer’s war- ranty and/or any extended warranties.
EXCEPT AS PROVIDED ABOVE, TRIPP LITE MAKES NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation or exclusion of implied warranties; therefore, the aforesaid limitation(s) or exclusion(s) may not apply to purchaser.
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL TRIPP LITE BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, Tripp Lite is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, costs of substitutes, claims by third parties or otherwise. Coverage also does not apply to connected medical and industrial equipment.
1111 W. 35th Street Chicago, IL 60609 EE.UU. Asistencia al cliente: +1 (773) 869-1234 • www.tripplite.com
To receive service under this warranty, you must be the original purchaser/user of the product in question. You must obtain a Returned Material Authorization (RMA) number from Tripp Lite. Products must be returned to Tripp Lite with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase.
© 2003 Tripp Lite. Todos los derechos reservados. OmniSmart™y SmartPro® son marcas registradas de Tripp Lite.