Models W17A to W60A 1.5 to 5 Ton (16,400 to 55,000 Btuh) Right Side Control Panel 60Hz
R-410A
The Bard Wall-Mount Air Conditioner is a self contained energy efficient system, which is designed to offer maximum indoor comfort at a minimal cost without using valuable indoor floor space or outside ground space. This unit is the ideal product for versatile applications such as: new construction, modular offices, school modernization, telecommunication structures, portable structures or correctional facilities. Factory or field installed accessories are available to meet specific job requirements.

Aluminum Finned Copper Coils: Grooved tubing and enhanced louvered fin for maximum heat transfer and energy efficiency.
Electrical Components: Are easily accessible for routine inspection and maintenance through a right side, service panel opening. Features a lockable, hinged access cover to the circuit breaker or toggle disconnect switch.
Twin Blowers: Move air quietly. Most models feature multispeed blower motors providing airflow adjustment for high and low static operation. Motor overload protection is standard on all models.
Electric Heat Strips: Features an automatic limit and thermal cut-off safety control. Heater packages can be factory or field installed for all 1½ through 5 ton models.
Air Conditioner Compressor: Scroll Compressors eliminate need for crankcase heater. Standard on 1½ to 5 ton.
Filter Service Door: Separate service door provides easy access for filter change.
R-410A Refrigerant: Designed with R-410A (HFC) non- ozone depleting refrigerant in compliance with the Montreal protocol and 2010 EPA requirements.
One Inch, Disposable Air Filters: Are standard equipment. Optional one inch washable filters available and filter racks permit the addition of 2" pleated filter. Factory or field installed.
Phase Rotation Monitor: Standard on all 3 phase scroll compressors. Protects against reverse rotation if power supply is not properly connected.
Condenser Fan and Motor Shroud Assembly: Slides out for easy access.
Liquid Line Filter Drier: Standard on all units. Protects system against moisture.
Barometric Fresh Air Damper: Standard on all units. Allows up to 25% outside fresh air. Optional ventilation packages available.
Compressor Control Module: Standard on all units. Built-in off-delay timer adjustable from 30 seconds to 5 minutes. 2-minute on-delay if power interrupt. 120-second bypass for low pressure control, and both soft and manual lockouts for high and low pressure controls. Alarm output for alarm relay.
Galvanized 20 Gauge Zinc Coated Steel Cabinet: Cleaned, rinsed, sealed and dried before the polyurethane primer is applied. The cabinet is handsomely finished with a baked on textured enamel, which allows it to withstand 1000 hours of salt spray tests per ASTM B117-03.
Built-in Circuit Breakers: Standard on all electric heat versions of single (230/208 volt) and three phase (230/208 volt) equipment. Toggle disconnects are standard on all electric heat versions of three phase (460 volt) equipment.
High & Low Pressure Switches are Auto-Reset: Standard on all units. Built-in lockout circuit resets from the room thermostat. Provides commercial quality protection to the compressor.
Foil Faced Insulation: Standard on all units.
Slope Top: Standard feature for water run-off.
Full Length Mounting Brackets: Built into cabinet for improved appearance and easy installation. NOTE: Bottom mounting bracket included to assist in installation.
Top Rain Flashing: Standard feature on all models.


1 Capacity is certified in accordance with ANSI/ARI Standard 390-2003. 2 EER = Energy Efficiency Ratio and is certified in accordance with ANSI/ARI Standard 390-2003. All ratings based on fresh air intake being 100% closed (no outside air introduction).

Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. All units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilation packages can be built-in at the factory or field-installed at a later date.

BAROMETRIC FRESH AIR DAMPER - BFAD STANDARD The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The damper opens during blower operation and closes when the blower is off. Adjustable blade stops allow different amounts of outside air to be introduced into the building and can be easily locked closed if required.
BLANK OFF PLATE - BOP OPTIONAL A blank off plate is installed on the inside of the service door. It covers the air inlet openings, which restricts any outside air from entering the unit. The blank off plate should be utilized in applications where outside air is not required to be mixed with the conditioned air.

MOTORIZED FRESH AIR DAMPER - MFAD OPTIONAL The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The two position damper can be fully open or closed. The damper blade is powered open by a 24VAC motor with spring return on power loss. The damper can be controlled by indoor blower operation or can be field connected to be managed based on building occupancy.

COMMERCIAL ROOM VENTILATOR - CRV OPTIONAL The built-in commercial room ventilator is internally mounted behind the service door and allows outside ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings. It includes a built-in exhaust air damper.
The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air quality by providing fresh air intake and exhaust capability through the CRV. The damper can be easily adjusted to control the amount of fresh air supplied into the building. The CRV can be controlled by indoor blower operation or field controlled based on room occupancy. Two versions available (except on 1.5 and 2-Ton models). The CRV and CRVS are power open - spring return on power loss, and CRVP is power open and power close. Complies with ANSI/ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality”.


WALL-MOUNT ENERGY RECOVERY VENTILATOR - ERVF OPTIONAL The wall-mount energy recovery ventilator (ERV) is a highly innovative approach to meeting indoor air quality ventilation requirements as established by ANSI/ASHRAE Standard 62.1. The ERV allows from 200 to 450 CFM (depending upon model) of fresh air and exhaust through the unit while maintaining superior indoor comfort and humidity levels. In most cases this can be accomplished without increasing equipment sizing or operating costs. Heat transfer efficiency is up to 67% during summer and 75% during winter conditions.
The ERV consists of a unique “rotary energy recovery cassette” that provides effective sensible and latent heat transfer capabilities during summer and winter conditions. Various control schemes are addressed including limiting ventilation during building occupancy only.
The ERV is designed to be internally mounted behind the service door in the W**A, W**H or W**L model wall- mount units. It can be built-in at the factory or field installed as an option. ERVF-*3 and ERVF-*5 can be independently adjusted for intake and exhaust rates.


Commercial Room Ventilator Performance Data - CRVS-3 and CRVP-3


Commercial Room Ventilator Performance Data - CRV-2
W17A/W18A & W24A TOTAL AND VENTILATION AIRFLOW
A B C D E F

Commercial Room Ventilator Performance Data - CRVS-5 and CRVP-5 Commercial Room Ventilator Performance Data - CRVS-5 and CRVP-5


W60A LOW SPEED TOTAL AND VENTILATION AIRFLOW
A B C D E F


W42A & W48A LOW SPEED TOTAL AND VENTILATION AIRFLOW
A B C D E F

E C N A M R O F R E P G N I L O O C R E M M U S
) B W ° 2 6 / B D ° 5 7 S N O I TI D N O C N G I S E D R O O D N I(
E C N A M R O F R E P G N I T A E H R E T N I W 2 A - F V R E
) B D F ° 0 7 S N O I T I D N O C N G I S E D R O O D N I(
VLT = Ventilation Load - Total VLS = Ventilation Load - Sensible VLL = Ventilation Load - Latent HRT = Heat Recovery - Total HRS = Heat Recovery - Sensible HRL = Heat Recovery - Latent WVL = Winter Ventilation Load WHR= Winter Heat Recovery

E C N A M R O F R E P G N I T A E H R E T N I W 5 *- F V R E
) B D F ° 0 7 S N O I T I D N O C N G I S E D R O O D N I(
) B W ° 2 6 / B D ° 5 7 S N O I T I D N O C N G I S E D R O O D N I(
E C N A M R O F R E P G N I L O O C R E M M U S
VLS = Ventilation Load - Sensible
HRS = Heat Recovery - Sensible
VLL = Ventilation Load - Latent
VLT = Ventilation Load - Total
HRT = Heat Recovery - Total
HRL = Heat Recovery - Latent
WVL = Winter Ventilation Load
WHR= Winter Heat Recovery
E C N A M R O F R E P G N I T A E H R E T N I W 3 *- F V R E
) B W ° 2 6 / B D ° 5 7 S N O I T I D N O C N G I S E D R O O D N I(
) B D F ° 0 7 S N O I T I D N O C N G I S E D R O O D N I(
E C N A M R O F R E P G N I L O O C R E M M U S

1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing. 4 These models are available with dehumidification with hot gas reheat. Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment
Factors when more than three (3) current carrying conductors are in a raceway. * Top outlet supply option is available only factory installed and only on the selected models. IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance with the National Electrical Code & all local codes.

Above data is with 1" standard throwaway filter and 1" washable filter. For optional 2" pleated filter - reduce ESP by .15 in. See installation instructions for maximum ESP information on various KW application.
Speeds marked “bold” above are Factory Connected.
.yln o stin u V 8 0 2 / 0 3 2 n i elb alia v a e r a s r e t a e h cirtc ele e s e h T ) 1 (
.yln o stin u V 0 8 4 n i elb alia v a e r a s r e t a e h cirtc ele e s e h T ) 2 (

1 Below 65°F (18.3C), unit requires a factory or field installed low ambient control. 2 Return air temperature.

W 36 A 1 A 10 X X X X X X
SERIES | | CONTROL MODULES (See Chart Below) REVISION
NOMINAL CAPACITY | 17 - 1½ Ton 18 - 1½ Ton 24 - 2 Ton 30 - 2½ Ton 36 - 3 Ton 42 - 3½ Ton 48 - 4 Ton 60 - 5 Ton
| COIL OPTIONS X - Standard 1 - Phenolic Coated Evaporator 2 - Phenolic Coated Condenser 3 - Phenolic Coated Evaporator and Condenser
COLOR OPTIONS X - Beige (Standard) 1 - White 4 - Buckeye Gray 5 - Desert Brown 8 - Dark Bronze A - Aluminum S - Stainless Steel
Specialty Products 2 (Non-Standard)
VENTILATION OPTIONS (See Table Below)
VOLTS & PHASE | A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3
FILTER OPTIONS X - 1-inch Throwaway (Standard) W - 1-inch Washable P - 2-inch Pleated (MERV 8)
| OUTLET OPTIONS X - Front (Standard) T - Top (on W30A and W36A Models)
1 For 0KW and circuit breakers (230/208 Volt) or toggle disconnects (460 Volt) applications, insert 0Z in the KW field of the model number. See Page 8 for available Factory Installed KW options and Page 9 for Field Installed Heater Packages. 2 Insert “D” for dehumidification with hot gas reheat — Models W42 - 60 only. See Form 7960-572 for complete details.
1 Intake and exhaust can be independently adjusted. 2 Insert color to match unit ("X" = Beige; "4" = Buckeye Gray; etc.) 3 WMDK Door Kit must be ordered in addition to ERVF Assembly and ECONWMS & color matched to unit ("X" = Beige; "4" = Buckeye Gray; etc.) 4 Partial Full Flow (75% of Rated Cooling CFM). All ECONWMS versions have 3" deep intake hood. 5 Full Flow (100% of Rated Cooling CFM). ECONWMTÃ2 and Ã3 have 16" deep intake hood; ECONWMT-Ã5 has 18" deep intake hood. 6 Model W24A1-C only.
STD = Standard equipment for these specified models. 1 HPC. High pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note 3. 2 LPC. Low pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note 3. 3 CCM. Compressor control module has adjustable 30-second to 5-minute delay-on-break timer. On initial power-up, or any time the power is interrupted, the delay-on-make will be 2- minutes plus 10% of the delay-on-break setting. There is no delay-on-make during routine operation of the unit. The module also provides the lockout feature (with 1 retry) for high and/or low-pressure controls, and a 2-minute timed bypass for low-pressure control. 4 LAC. Low ambient control permits cooling operation down to 0°F. LAC is fan-cycling control for outdoor fan motor on all models except W17A1, which is modulating control. 5 ALR. The alarm relay has a set of normally open and normally closed dry contacts to provide the ability to signal a condition of shutdown on either high or low pressure controls. 6 SK. PTCR start kit can be used with all -A single phase models. Increases starting torque 2-3x. Not used for -B or -C three phase models. Do not use if SK111 is used. 7 SK. Start capacitor and potential relay start kit can be used with all -A single phase models. Increases starting torque 9x. Not used for -B or -C three phase models. Do not use if CMC-15 is used. 8 ODT. Outdoor thermostat is adjustable from 0 to 50°F. It is suitable for use as a compressor cut-off thermostat. 9 DDC. Incorporates 4 additional sensors: discharge air temperature, indoor blower airflow, compressor current, and dirty filter. These sensing devices function to input analog data such as temperature, as well as digital data such as airflow, compressor status or filter status. Special economizer required; consult factory. V “V” control module should be ordered in conjunction with direct digital controller (DDC) model TCS24. Refer to DDC specification sheet S3280 for more information.
Option not available for Model W18A. Use option N for Alarm Relay on Model W18A only.
TYPE Air Conditioner

s s e c c A e c i v r e S r o f d e ri u q e R s e c n a r a e l C


w o lfri A t e l n I r e s n e d n o C e t a u q e d A d n a
S L E D O M E D I S T F E L E D I S T H G I R
A 6 3 W , A 0 3 W , A 4 2 W , A 8 1 W , A 7 1 W " 5 1 " 0 2
A 0 6 W , A 8 4 W , A 2 4 W " 0 2 " 0 2
1 Refer to the Installation Manual for more detailed information.
All dimensions are in inches. Dimensional drawings are not to scale.

Equipment Building Hood ECONWMT-E2, -T2, -E3, -T3 is 16"
ECONWMT-E5, -T5 is 18"
1 Optional top outlet (factory installed only) for W30A and W36A models only.

Due to our continuous product improvement policy, all specifications subject to change without notice.
Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
Since 1914 . . . Moving ahead, just as planned.