Bard Air Conditioner (357-93-E)

12 pages·372 KB·Air Conditioner·PDF·ENDEFRITNLJA
Bard Air Conditioner (357-93-E)
Table of Contents 25 sections THE WALL-MOUNT™ AIR CONDITIONERS - WL (60HZ) · with LEFT SIDE CONTROL PANEL · Engineered Features · MEA# 357-93-E · … ShowHide
Page 1 of the Bard Air Conditioner (357-93-E) user manual — Ventilation System Packages
Page 1 · click to enlarge
Page 1
Bard Air Conditioner (357-93-E) — THE WALL-MOUNT™ AIR CONDITIONERS - WL (60HZ) diagram (page 1)
Fig. 1

THE WALL-MOUNT™ AIR CONDITIONERS - WL (60HZ)

with LEFT SIDE CONTROL PANEL

WL - SERIES Refrigerant 22 60Hz 1.5 to 6 Ton (18,300 to 67,000 Btuh) Left Side Control Panel

Bard Air Conditioner (357-93-E) — THE WALL-MOUNT™ AIR CONDITIONERS - WL (60HZ) diagram (page 1)
Fig. 2

The Bard Wall-Mount Air Conditioner with Left Side Control Panel is designed to provide complete service access (i.e. compressor, electric heat strip and electrical controls) when two units are mounted side by side with minimal space between. The left side unit is the ideal product for telecommunication and over-the-road medical and communication vans requiring two wall-mount air conditioners be mounted side by side by using a WL (left side access) unit and a WA (right side access) unit on the same building. Factory or field installed accessories are also available to meet specific job requirements.

Engineered Features

Aluminum Finned Copper Coils: Grooved tubing and enhanced louvered fin for maximum heat transfer and energy efficiency.

One Inch, Disposable Air Filters: Are standard equipment. Optional one inch washable filters available and filter racks permit the addition of 2" pleated filter. Factory or field installed.

Twin Blowers: Move air quietly. Most models feature multispeed blower motors providing airflow adjustment for high and low static operation. Motor overload protection is standard on all models.

Built-in Circuit Breakers: Standard on all single (230/208 volt) and three phase (230/208 volt) equipment. Toggle disconnects are standard on all three phase (460 volt) equipment.

Air Conditioner Compressor: Reciprocating compressors with crankcase heater and dual discharge muffler are standard on 1.5 and 2 ton models.

Slope Top: Standard feature for water run-off.

Top Rain Flashing: Standard feature on all models.

Scroll Compressors eliminate need for crankcase heater. Standard on 2.5 to 5 ton, and available on 2 ton models.

Full Length Mounting Brackets: Built into cabinet for improved appearance and easy installation. NOTE: Bottom mounting bracket included to assist in installation.

MEA# 357-93-E

Phase Rotation Monitor: Standard on all 3 phase scroll compressors. Protects against reverse rotation if power supply is not properly connected. Not required on reciprocating compressors.

Auto-Reset High Pressure Switch: Built-in lock-out circuit resets from the room thermostat. Provides commercial quality protection to the compressor.

Ventilation System Packages

All packages are designed to meet your specific ventilation requirements utilizing one of five ventilation options for the product. The ventilation package is mounted within the unit eliminating the need for an exterior mounted hood or damper assembly on the unit. All assemblies can be factory installed, installed in the field at time of installation or as a retrofit system after installation.

Standard - Barometric

Galvanized 20 Gauge Zinc Coated Steel Cabinet: Cleaned, rinsed, sealed and dried before the polyurethane primer is applied. The cabinet is handsomely finished with a baked on textured enamel, which allows it to withstand 1000 hours of salt spray tests per ASTM B117-03.

Auto-Reset Low Pressure Switch: Built-in lock-out circuit and low pressure timed bypass circuit. Resets from room thermostat.

Optional - Motorized

Compressor Control Module: Built-in off-delay timer adjustable from 30 second to 5-minutes. 2-minute on-delay if power interrupt. 120-second bypass for low pressure control, and both soft and manual lockouts for high and low pressure controls. Alarm output for alarm relay.

Optional - Blank off Plate

Optional - Commercial

  • Room Ventilator with Exhaust
  • CRV - Spring Return
  • CRVP - Power Return

Electrical Components: Are easily accessible for routine inspection and maintenance through a left side, service panel opening. Features a lockable, hinged access cover to the circuit breaker or pull disconnect switch.

Optional - Economizer w/Exhaust

Low Ambient Control: Permits cooling operation down to 0°F outdoor ambient.

Electric Heat Strips: Features an automatic limit and thermal cut-off safety control. Heater packages can be factory installed for all 1.5 through 6 ton models.

Alarm Relay: Dry contacts for remote alarm capability on manual high or low pressure controls.

  • Complies with efficiency requirements of ASHRAE/IESNA 90.1-2004.
  • Certified to ARI Standard 390-2003 for SPVU (Single Package Vertical Units).
  • Commercial Product - Not intended for Residential application.

Fresh Air Damper · Fresh Air Damper

Page 2 of the Bard Air Conditioner (357-93-E) user manual — THE WALL-MOUNT™ AIR CONDITIONERS - WL (60HZ)
Page 2 · click to enlarge
Page 2
Capacity and Efficiency Ratings 1 MODELSWL182WL242WL253WL302WL372WL423WL484WL602WL702-AWL701-B,C 18,300 9.20 10.2024,000 9.20 10.5023,000 9.80 11.0030,000 9.30 10.6036,000 9.20 10.0042,000 9.20 10.6047,500 9.60 11.0057,500 8.70 10.2064,000 9.00 10.00

1 Capacity is certified in accordance with ARI Standard 390-2003 and tested in accordance with ARI Standard 210/240-2003. 2 EER = Energy Efficiency Ratio and is certified in accordance with ARI Standard 390-2003. 3 SEER = Seasonal Energy Efficiency Ratio and is tested in accordance with ARI Standard 210/240-2003. All ratings based on fresh air intake being 100% closed (no outside air introduction).

Specifications 1-1/2 through 3 Ton MODELSWL182-AWL242-AWL242-BWL253-AWL253-BWL302-AWL302-BWL302-CWL372-AWL372-BWL372-C ElectricalRating--60Hz230/208-1230/208-1230/208-3230/208-1230/208-3230/208-1230/208-3460-3230/208-1230/208-3460-3 OperatingVoltageRange197-253197-253197-253197-253197-253197-253197-253414-506197-253197-253414-506 Compressor--CircuitA Voltage230/208230/208230/208230/208230/208230/208230/208460230/208230/208460 RatedLoadAmps7.0/8.09.5/10.06.6/6.98.6/9.56.5/7.012.2/12.98.4/8.44.216.5/17.310.5/11.05.2 BranchCircuitSelectionCurrent9.010.07.010.37.114.19.04.517.311.05.5 LockRotorAmps CompressorType49/49 Recip.56/56 Recip.51/51 Recip.54/54 Scroll45/45 Scroll73/73 Scroll63/63 Scroll32 Scroll100/100 Scroll77/77 Scroll37 Scroll FanMotor&Condenser FanMotor--HP--RPM FanMotor--Amps Fan--DIA/CFM1/5-1075 1.2 18"-16001/5-1075 1.2 18"-16001/5-1075 1.2 18"-16001/5-1075 1.2 18"-16001/5-1075 1.2 18"-16001/5-1075 1.5 20"-21001/5-1075 1.5 20"-21001/5-1075 1.4 20"-21001/5-1075 1.5 20"-19001/5-1075 1.5 20"-19001/5-1075 1.4 20"-1900 BlowerMotor&Evap. BlowerMotor--HP-RPM-SPD BlowerMotor--Amps CFMCooling&E.S.P. w/Filter(Rated-WetCoil) FilterSizes(inches)STD.1/6-1100-1 1.0 650-.40 16x25x11/6-1100-1 1.0 800-.20 16x25x11/6-1100-1 1.0 800-.20 16x25x11/6-1100-1 1.0 800-.20 16x25x11/6-1100-1 1.0 800-.20 16x25x11/3-1100-2 2.2 1000-.40 16x30x11/3-1100-2 2.2 1000-.40 16x30x11/3-1100-2 1.1 1000-.40 16x30x11/3-1100-2 2.2 1100-.30 16x30x11/3-1100-2 2.2 1100-.30 16x30x11/3-1100-2 1.1 1100-.30 16x30x1 ShippingWeight--LBS.300300300300300355355355355355355
Specifications 3-1/2 Ton through 6 Ton MODELSWL423-AWL423-BWL423-CWL484-AWL484-BWL484-CWL602-AWL602-BWL602-CWL702-AWL701-BWL701-C ElectricalRating--60Hz230/208-1230/208-3460-3230/208-1230/208-3460-3230/208-1230/208-3460-3230/208-1230/208-3460-3 OperatingVoltageRange197-253197-253414-506197-253197-253414-506197-253197-253414-506197-253197-253414-506 Compressor--CircuitA Voltage230/208230/208460230/208230/208460230/208230/208460230/208230/208460 RatedLoadAmps19.3/21.011.8/11.86.120.2/20.911.9/13.36.226.0/28.518.1/18.46.829.1/31.020.5/21.510.2 BranchCircuitSelectionCurrent21.012.56.521.812.96.529.019.09.032.022.010.2 LockRotorAmps CompressorType127/127 Scroll88/88 Scroll42 Scroll131/131 Scroll91/91 Scroll46 Scroll148/148 Scroll137/137 Scroll62 Scroll176/176 Scroll150/156 Scroll75 Scroll FanMotor&Condenser FanMotor--HP-RPM-SPD FanMotor--Amps Fan--DIA/CFM1/3-850-2 2.5 24"-26001/3-850-2 2.5 24"-26001/3-850-1 1.3 24"-26001/3-850-2 2.5 24"-26001/3-850-2 2.5 24"-26001/3-850-1 1.3 24"-26001/3-850-2 2.5 24"-26001/3-850-2 2.5 24"-26001/3-850-1 1.3 24"-26001/3-850-2 2.5 24"-26001/3-850-2 2.5 24"-26001/3-850-1 1.3 24"-2600 BlowerMotor&Evap. BlowerMotor--HP-RPM-SPD BlowerMotor--Amps CFMCooling&E.S.P. w/Filter(Rated-WetCoil) FilterSizes(inches)STD.1/2-1070-2 3.3 1400-.30 20x30x11/2-1070-2 3.3 1400-.30 20x30x11/2-1070-2 1.9 1400-.30 20x30x11/2-1070-2 3.3 1550-.20 20x30x11/2-1070-2 3.3 1550-.20 20x30x11/2-1070-2 1.9 1550-.20 20x30x11/2-1070-2 3.3 1700-.30 20x30x11/2-1070-2 3.3 1700-.30 20x30x11/2-1070-2 1.9 1700-.30 20x30x11/2-1070-2 3.3 1800-.20 20x30x11/2-1070-2 3.3 1800-.20 20x30x11/2-1070-2 1.9 1800-.20 20x30x1 ShippingWeight--LBS.500500500500500500500500500520520520
Page 3 of the Bard Air Conditioner (357-93-E) user manual — Ventilation System Packages
Page 3 · click to enlarge
Page 3

Ventilation System Packages

Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. All units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilation packages can be built-in at the factory, or field-installed at a later date.

Bard Air Conditioner (357-93-E) — Ventilation System Packages diagram (page 3)
Fig. 3 · Ventilation System Packages

BAROMETRIC FRESH AIR DAMPER - BFAD STANDARD The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The damper opens during blower operation and closes when the blower is off. Adjustable blade stops allow different amounts of outside air to be introduced into the building and can be easily locked closed if required.

BLANK OFF PLATE - BOP OPTIONAL A blank off plate is installed on the inside of the service door. It covers the air inlet openings which restricts any outside air from entering the unit. The blank off plate should be utilized in applications where outside air is not required to be mixed with the conditioned air.

Barometric Fresh Air Damper

Bard Air Conditioner (357-93-E) — Ventilation System Packages diagram (page 3)
Fig. 4 · Ventilation System Packages

MOTORIZED FRESH AIR DAMPER - MFAD OPTIONAL The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The two position damper can be fully open or closed. The damper blade is powered open by a 24VAC motor with spring return on power loss. The damper can be controlled by indoor blower operation or can be field connected to be managed based on building occupancy.

Motorized Fresh Air Damper

Bard Air Conditioner (357-93-E) — Ventilation System Packages diagram (page 3)
Fig. 5 · Ventilation System Packages

COMMERCIAL ROOM VENTILATOR - CRV OPTIONAL The built-in commercial room ventilator is internally mounted behind the service door and allows outside ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings. It includes a built-in exhaust air damper.

The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air quality by providing fresh air intake and exhaust capability through the CRV. The damper can be easily adjusted to control the amount of fresh air supplied into the building. The CRV can be controlled by indoor blower operation or field controlled based on room occupancy. Two versions available (except on 1.5 and 2-ton models). The CRV and CRVS are power open - spring return on power loss, and CRVP is power open and power return. Complies with ANSI/ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality”.

Bard Air Conditioner (357-93-E) — Ventilation System Packages diagram (page 3)
Fig. 6 · Ventilation System Packages

ECONOMIZER - EIFM OPTIONAL The built-in economizer system is internally mounted behind the service door and allows outdoor air to be introduced through the air inlet openings. The amount of outdoor air varies in response to the system controls and settings defined by the end user. It includes a built-in exhaust air damper. The economizer is designed to provide “free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running the compressor. This in turn provides lower operating costs, while extending the life of the compressor.

  • Standard Features:
  • One Piece Construction - Easy to install with no mechanical linkage adjustment required.
  • Exhaust Air Damper - Built in with positive closed position. Provides exhaust air capability to prevent pressurization of tight buildings.
  • Actuator Motor - 24 volt, power open, spring return with built in torque limiting switch.
  • Proportioning Type Control - for maximum “free cooling” economy and comfort.
  • Moisture Eliminator & Prefilter - permanent, washable aluminum construction
  • Enthalpy Control - adjustable to monitor outdoor temperature and humidity.
  • Minimum Position Potentiometer - adjustable to control minimum damper blade position for ventilation purposes.
  • Mixed Air Sensor - to monitor outside and return air to automatically modulate damper position.

Manufactured under U.S. Patent Nos. 5,485,878; 5,301,744; 5,002,116; 4,924,934; 4,875,520; 4,825,936

Commercial Room Ventilator · Economizer

Page 4 of the Bard Air Conditioner (357-93-E) user manual — THE WALL-MOUNT™ AIR CONDITIONERS - WL (60HZ)
Page 4 · click to enlarge
Page 4
Electrical Specifications SingleCircuitDualCircuit ModelRated Volts andPhaseNo.Field Power Circuits3Minimum Circuit Ampacity1Maximum ExternalFuse orCkt.Brkr.2Field Power WireSize2Ground Wire3Minimum Circuit Ampacity1Maximum ExternalFuse orCkt.Brkr.2Field Power WireSize2Ground WireSize Ckt.ACkt.BCkt.ACkt.BCkt.ACkt.BCkt.ACkt.B WL182-A0Z A05 A08 A10230/208-1116 30 45 5620 30 45 6012 10 8 612 10 10 10 WL242-A0Z A05 A08 A10230/208-1117 30 45 5620 30 45 6012 10 8 612 10 10 10 WL242-B0Z B06230/208-31 113 2215 2514 1012 10 WL253-A0Z A05 A08 A10230/208-1118 30 45 5625 30 45 6010 10 8 610 WL253-B0Z B06230/208-31 114 2220 2512 1012 10 WL302-A0Z A05 A08 A10 A15230/208-11or224 31 47 57 8335 35 50 60 908 8 8 6 410 8572660306101010 WL302-B0Z B09 B15230/208-31 1 117 32 5020 35 5012 8 812 10 10 WL302-C0Z C09 C15460-31 1 110 17 2615 20 3014 12 1014 12 10 WL372-A0Z A05 A10 A15230/208-11 or228 32 58 8435 35 60 908 8 6 410 10 10 8572660306101010 WL372-B0Z B09 B15230/208-31 1 120 33 5125 35 6010 8 610 10 10 WL372-C0Z C09 C15460-31 1 111 17 2615 20 3014 10 1014 10 10 WL423-A0Z A05 A10 A15230/208-11or236 36 59 8550 50 60 908 8 6 410 10 10 8592660306101010 WL423-B0Z B09 B15230/208-31 1 125 34 5235 35 608 8 610 10 10 WL423-C0Z C09 C15460-31 1 113 17 2615 20 3014 12 1014 12 10 WL484-A0Z A05 A10 A15230/208-11or238 38 59 8550 50 60 908 8 6 410 10 10 8592660306101010 WL484-B0Z B09 B15230/208-31 1 124 34 5235 35 608 8 610 10 10 WL484-C0Z C09 C15460-31 1 112 17 2615 20 3014 12 1014 12 10 WL602-A0Z A05 A10 A15230/208-11or244 44 59 8560 60 60 908 8 6 410 10 10 8592660306101010 WL602-B0Z B09 B15230/208-31 1 132 34 5245 45 608 8 610 10 10 WL602-C0Z C09 C15460-31 1 116 17 2620 20 3012 12 1012 12 10 WL702-A0Z A05 A10 A15230/208-11or248 48 59 8560 60 60 908 8 6 410 10 10 8592660306101010 WL701-B0Z B09 B15230/208-31 1 136 36 5250 50 608 8 610 10 10 WL701-C0Z C09 C15460-31 1 117 17 2625 25 3012 12 1012 12 10

1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical Code (lastest version), Article 310 for power conductor sizing.

regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.

the National Electrical Code and all local codes.

Page 5 of the Bard Air Conditioner (357-93-E) user manual — WL18, WL24 & WL25 TOTAL AND VENTILATION AIRFLOW
Page 5 · click to enlarge
Page 5

Commercial Room Ventilator Performance Data - CRV-2

WL18, WL24 & WL25 TOTAL AND VENTILATION AIRFLOW

Total Air 0 ESP Total Air .15 ESP Total Air .3 ESP Vent Air 0 ESP Vent Air .15 ESP Vent Air .3 ESP

Page 6 of the Bard Air Conditioner (357-93-E) user manual — WL30 & WL37 LOW SPEED TOTAL AND VENTILATION AIRFLOW
Page 6 · click to enlarge
Page 6

Commercial Room Ventilator Performance Data - CRVS-3 and CRVP-3

WL30 & WL37 HIGH SPEED TOTAL AND VENTILATION AIRFLOW

Bard Air Conditioner (357-93-E) — WL30 & WL37 HIGH SPEED TOTAL AND VENTILATION AIRFLOW diagram (page 6)
Fig. 7

Total Air 0 ESP Total Air .15 ESP Total Air .3 ESP Vent Air 0 ESP Vent Air .15 ESP Vent Air .3 ESP

WL30 & WL37 LOW SPEED TOTAL AND VENTILATION AIRFLOW

Bard Air Conditioner (357-93-E) — WL30 & WL37 LOW SPEED TOTAL AND VENTILATION AIRFLOW diagram (page 6)
Fig. 8

Total Air .15 ESP Total Air .3 ESP Vent Air 0 ESP

Page 7 of the Bard Air Conditioner (357-93-E) user manual — WL42 & WL48 LOW SPEED TOTAL AND VENTILATION AIRFLOW
Page 7 · click to enlarge
Page 7

Commercial Room Ventilator Performance Data - CRVS-5 and CRVP-5

WL42 & WL48 HIGH SPEED TOTAL AND VENTILATION AIRFLOW

Bard Air Conditioner (357-93-E) — WL42 & WL48 HIGH SPEED TOTAL AND VENTILATION AIRFLOW diagram (page 7)
Fig. 9

Total Air 0 ESP Total Air .2 ESP Total Air .4 ESP Vent Air 0 ESP Vent Air .2 ESP Vent Air .4 ESP

WL42 & WL48 LOW SPEED TOTAL AND VENTILATION AIRFLOW

Bard Air Conditioner (357-93-E) — WL42 & WL48 LOW SPEED TOTAL AND VENTILATION AIRFLOW diagram (page 7)
Fig. 10

Total Air 0 ESP Total Air .2 ESP Total Air .4 ESP

Vent Air 0 ESP Vent Air .2 ESP Vent Air .4 ESP

Page 8 of the Bard Air Conditioner (357-93-E) user manual — WL60 & WL70 LOW SPEED TOTAL AND VENTILATION AIRFLOW
Page 8 · click to enlarge
Page 8

Commercial Room Ventilator Performance Data - CRVS-5 and CRVP-5

WL60 & WL70 HIGH SPEED TOTAL AND VENTILATION AIRFLOW

Bard Air Conditioner (357-93-E) — WL60 & WL70 HIGH SPEED TOTAL AND VENTILATION AIRFLOW diagram (page 8)
Fig. 11

WL60 & WL70 LOW SPEED TOTAL AND VENTILATION AIRFLOW

Bard Air Conditioner (357-93-E) — WL60 & WL70 LOW SPEED TOTAL AND VENTILATION AIRFLOW diagram (page 8)
Fig. 12

Total Air 0 ESP Total Air .2 ESP Total Air .4 ESP Vent Air 0 ESP Vent Air .2 ESP Vent Air .4 ESP

Page 9 of the Bard Air Conditioner (357-93-E) user manual — ELECTRIC HEAT ACCESS PANEL
Page 9 · click to enlarge
Page 9
Indoor Blower Performance - CFM at 230 or 460 Volts ESP in HO 2WL18 WL24 WL25WL30 WL37WL42 WL48WL60,WL70 Dry/WetCoilHighSpeed Dry/WetCoilLowSpeed Dry/WetCoilHighSpeed Dry/WetCoilLowSpeed Dry/WetCoilHighSpeed Dry/WetCoilLowSpeed Dry/WetCoil 01020/9751395/1315 950/9351885/1800 1650/16002200/2000 1600/1450 .1960/9051340/1270 930/9151770/1665 1550/15002100/1900 1525/1375 .2865/8001285/1190 910/8851635/1550 1450/14002000/1800 -/- .3820/7351205/1100 855/8301500/1400 1350/13001875/1700 -/- .4735/6501110/1000 800/7551370/1285 1300/11751775/1600 -/- .5615/5351005/870 -/-1250/1150 -/-1650/1475 -/-

Above data is with 1" standard disposable filter and 1" washable filter. For optional 2" pleated filter - reduce ESP by .15 in. See installation instructions for maximum ESP information on various KW application.

Electric Heat Table - Refer to Electrical Specifications for Availability by Unit Model Nominal KWAt240V(1)At208V(1)At480V(2)At460V(2) Kw1-PhAmps3-PhAmpsBtuhKw1-PhAmps3-PhAmpsBtuhKw3-PhAmpsBtuhKw3-PhAmpsBtuh 5.05.020.817,0653.7518.012,799 6.06.014.420,4784.5012.515,3596.07.220,4785.526.918,840 8.08.033.327,3046.0028.820,478 9.09.021.730,7176.7518.723,0389.010.830,7178.2810.428,260 10.010.041.734,1307.5036.125,598 15.015.062.536.151,19511.2554.131.238,39615.018.051,19513.8017.347,099

.yln o stin u V 8 0 2 / 0 3 2 n i elb alia v a e r a s r e t a e h cirtc ele e s e h T ) 1 (

.yln o stin u V 0 8 4 n i elb alia v a e r a s r e t a e h cirtc ele e s e h T ) 2 (

Unit Service Access Overview

ELECTRIC HEAT ACCESS PANEL

ELECTRIC HEAT ACCESS PANEL

ELECTRICAL CONTROL ACCESS PANEL

ELECTRICAL CONTROL ACCESS PANEL

COMPRESSOR ACCESS

COMPRESSOR ACCESS

Model WL with Left Side

Model WA with Right Side

15" · Control Panel · Control Panel

Page 10 of the Bard Air Conditioner (357-93-E) user manual — Unit Service Access Overview
Page 10 · click to enlarge
Page 10
Cooling Application Data - Outdoor Temperature 1 ModelD.B./W.B. 2Cooling Capacity75oF80oF85oF90oF95oF100oF105oF110oF115oF120oF125oF WL18275/ 62TotalCooling SensibleCooling19,600 14,82518,675 14,70017,725 14,47516,825 14,19015,925 13,83015,050 13,39014,175 12,88013,325 12,30012,500 11,64011,700 10,70011,100 10,150 80/ 67TotalCooling SensibleCooling20,975 14,62520,360 14,46519,710 14,30019,020 14,13518,300 13,97017,540 13,64016,750 13,23015,920 12,72015,060 12,12514,400 11,60013,800 11,000 85/ 72TotalCooling SensibleCooling24,950 14,75023,780 14,62022,620 14,40021,460 14,09020,315 13,69019,180 13,19018,050 12,61016,930 11,93015,815 11,15514,700 10,40013,600 9,650 WL24275/ 62TotalCooling SensibleCooling24,900 19,90023,880 19,53022,870 19,14021,670 18,72020,880 18,27519,900 17,80018,920 17,30017,960 16,77017,000 16,21516,050 15,30015,050 14,300 80/ 67TotalCooling SensibleCooling26,600 19,30026,040 19,16025,420 18,97024,740 18,74024,000 18,46023,210 18,14022,350 17,77021,450 17,35020,480 16,89019,000 15,70017,550 14,400 85/ 72TotalCooling SensibleCooling31,300 19,77530,350 19,43029,260 19,04028,020 18,59026,640 18,09025,110 17,53023,440 16,92021,620 16,26020,600 15,54019,475 14,70018,400 13,900 WL25375/ 62TotalCooling SensibleCooling23,400 19,10022,600 18,70021,800 18,40021,000 17,90020,100 17,60019,200 17,10018,300 16,60017,400 16,20016,400 15,60015,400 15,10014,300 14,600 80/ 67TotalCooling SensibleCooling24,900 18,50024,600 18,30024,200 18,20023,700 17,90023,000 17,70022,300 17,40021,500 17,00020,700 16,70019,700 16,20018,600 15,80017,400 15,300 85/ 72TotalCooling SensibleCooling29,700 19,00028,800 18,60027,800 18,30026,800 17,80025,600 17,40024,400 16,90023,200 16,20022,100 15,70020,700 15,00019,400 14,30017,900 13,600 WL30275/ 62TotalCooling SensibleCooling30,900 25,70029,700 25,30028,500 24,90027,400 24,40026,100 23,90025,100 23,30024,000 22,70022,900 22,20021,900 21,50020,800 20,80019,700 20,100 80/ 67TotalCooling SensibleCooling33,000 24,90032,300 24,80031,600 24,60030,900 24,40030,000 24,10029,200 23,70028,300 23,30027,300 22,90026,300 22,30025,200 21,70024,000 21,100 85/ 72TotalCooling SensibleCooling39,300 25,50037,800 25,20036,300 24,70034,900 24,30033,400 23,70032,000 23,00030,500 22,20029,100 21,50027,700 20,60026,200 19,60024,700 18,700 WL37275/ 62TotalCooling SensibleCooling37,300 28,10035,700 27,70034,200 27,30032,800 26,80031,400 26,40030,100 25,80028,900 25,20027,800 24,50026,700 23,80025,700 22,90024,600 22,100 80/ 67TotalCooling SensibleCooling39,800 27,20038,900 27,10038,000 27,00037,000 26,80036,000 26,60035,100 26,20034,100 25,80033,100 25,30032,100 24,70031,100 24,00030,000 23,200 85/ 72TotalCooling SensibleCooling47,400 27,90045,500 27,50043,700 27,20041,800 26,60040,000 26,10038,400 25,40036,800 24,60035,200 23,70033,800 22,80032,300 21,70030,900 20,600 WL42375/ 62TotalCooling SensibleCooling43,200 35,00041,700 34,30040,100 33,50038,400 32,80036,600 32,00034,800 31,20033,000 30,20031,000 29,30029,000 28,30026,900 27,20024,700 26,100 80/ 67TotalCooling SensibleCooling46,100 33,90045,400 33,60044,500 33,20043,400 32,80042,000 32,30040,500 31,70038,900 31,00037,000 30,30034,900 29,40032,600 28,50030,100 27,500 85/ 72TotalCooling SensibleCooling54,900 34,70053,100 34,10051,100 33,40049,000 32,60046,700 31,70044,300 30,70042,000 29,60039,400 28,40036,700 27,10033,900 25,80031,000 24,400 WL48475/ 62TotalCooling SensibleCooling48,200 39,12046,300 38,52044,650 37,68043,070 37,51041,300 37,00039,340 36,13037,190 34,91034,840 33,33032,300 31,40030,900 30,00029,500 28,700 80/ 67TotalCooling SensibleCooling51,440 37,95050,440 37,80049,640 37,60048,750 37,40047,500 37,30045,890 36,74043,920 35,80041,590 34,49038,900 32,80038,100 32,05037,250 31,350 85/ 72TotalCooling SensibleCooling59,900 38,75058,650 38,25057,240 37,45055,350 37,23052,700 36,60049,700 35,57046,700 34,15043,800 32,32040,850 30,10039,100 28,70037,450 27,500 WL60275/ 62TotalCooling SensibleCooling60,350 45,17057,500 43,70054,630 42,18052,320 41,11050,000 40,00047,660 38,84045,290 37,64042,910 36,39040,500 35,100N/A N/AN/A N/A 80/ 67TotalCooling SensibleCooling64,600 43,95062,750 42,96060,690 41,83059,190 41,15057,500 40,40055,610 39,57053,540 38,66051,260 37,67048,800 36,600N/A N/AN/A N/A 85/ 72TotalCooling SensibleCooling76,800 44,90073,300 43,47069,610 41,97066,740 40,84063,800 39,60060,780 38,26057,700 36,81054,530 35,26051,300 33,600N/A N/AN/A N/A WL702-A75/ 62TotalCooling SensibleCooling66,200 50,60063,600 47,90061,000 45,40058,400 43,50055,700 42,00053,200 40,80050,700 40,10048,100 39,60045,500 39,500N/A N/AN/A N/A 80/ 67TotalCooling SensibleCooling70,700 49,10069,300 46,90067,700 45,00066,000 43,50064,000 42,40062,000 41,50059,800 41,10057,400 40,90054,800 41,100N/A N/AN/A N/A 85/ 72TotalCooling SensibleCooling84,200 50,30081,000 47,60077,700 45,20074,500 43,20071,100 41,60067,800 40,20064,500 39,20061,100 38,40057,600 37,900N/A N/AN/A N/A WL701-B,C75/ 62TotalCooling SensibleCooling69,700 49,50066,800 48,00063,900 46,60061,100 45,30058,300 44,00055,550 42,80052,800 41,60050,150 40,55047,500 39,500N/A N/AN/A N/A 80/ 67TotalCooling SensibleCooling74,550 48,05072,850 47,10071,050 46,20069,100 45,30067,000 44,45064,800 43,60062,400 42,75059,900 41,95057,250 41,150N/A N/AN/A N/A 85/ 72TotalCooling SensibleCooling88,700 49,15085,100 47,75081,550 46,35077,950 44,95074,400 43,55070,800 42,13467,250 40,70063,650 39,30060,100 37,850N/A N/AN/A N/A 1 Below 65oF (18.3C), unit requires a factory or field installed low ambient control. 2 Return air temperature.CapacityMultiplierFactors %ofRatedAirflow-10Rated+10 TotalBTUH SensibleBTUH0.975 0.9501.0 1.01.02 1.05
Page 11 of the Bard Air Conditioner (357-93-E) user manual — FRONT VIEW SIDE VIEW BACK VIEW
Page 11 · click to enlarge
Page 11

s s e c c A e c i v r e S r o f d e ri u q e R s e c n a r a e l C

o t d e ri u q e R s e c n a r a e l C m u m i n i M

w o l F ri A r e s n e d n o C e t a u q e d A d n a

s l a ir e t a M e l b it s u b m o C

S L E D O M E D I S T F E L E D I S T H G I R

S L E D O M 1 T C U D R I A Y L P P U S

T E E F E E R H T T S R I F T E N I B A C

7 3 L W , 5 2 L W , 4 2 L W , 8 1 L W " 0 2 " 5 1

0 7 L W , 0 6 L W , 8 4 L W , 2 4 L W " 0 2 " 0 2

5 2 L W , 4 2 L W , 8 1 L W " 0 " 0

7 3 L W , 0 3 L W " 4 / 1 " 0

0 7 L W , 0 6 L W , 8 4 L W , 2 4 L W " 4 / 1 " 0

1 Refer to the Installation Manual for more detailed information.

Dimensions of BasicUnit for Architectural andInstallation Requirements (Nominal) MODELWIDTH DEP (W) (DTH HEIGH ) (H)T SUPPLY R A B CETURN B CBEFG IJK LM N OP QRST WL18 WL24 WL2533.300 17.125 70.5637.88 19.88 11.88 19.8835.0018.5025.75 20.5626.7528.06 29.2527.00 2.63 34.13 22.06 10.55 4.1912.00 5.00 WL30 WL3738.200 17.125 70.5637.88 27.88 13.88 27.8840.0018.5025.75 17.9326.7528.75 29.2527.00 2.75 39.19 22.75 9.14 4.1912.00 5.00 WL42 WL48 WL6042.075 22.432 84.8759.88 29.88 15.88 29.8843.8819.1031.66 30.0032.6826.94 34.6932.43 3.37 42.88 23.88 10.00 2.0016.00 1.88 WL7042.075 22.432 94.8759.88 29.88 15.88 29.8843.8819.1041.66 30.0042.6836.94 44.6942.43 3.37 42.88 33.88 10.00 2.0016.00 1.88

. ela c s ot t o n e r a s g n i w a r d la n o is n e m i D .s e h c n i n i e r a s n o is n e m id ll A

FRONT VIEW SIDE VIEW BACK VIEW

1 21.00 inches on model WL701

Page 12 of the Bard Air Conditioner (357-93-E) user manual — MODEL NUMBER |
Page 12 · click to enlarge
Page 12

Air Conditioning Wall-Mount Model Nomenclature

WL 37 2 A 10 X X X X X J

MODEL NUMBER |

REVISION KW

CONTROL MODULES J - Standard on all models

CAPACITY | 18 - 1½ Ton 24 - 2 Ton 25 - 2 Ton 30 - 2½ Ton 37 - 3 Ton 42 - 3½ Ton 48 - 4 Ton 60 - 5 Ton 70 - 6 Ton

COLOR OPTIONS X - Beige (Standard) 1 - White 2 - Mesa Tan 4 - Buckeye Gray 5 - Desert Brown 8 - Dark Bronze

| COIL OPTIONS X - Standard 1 - Phenolic Coated Evaporator 2 - Phenolic Coated Condenser 3 - Phenolic Coated Evaporator and Condenser

VENTILATION OPTIONS See Table Below

VOLTS & PHASE | A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3

FILTER OPTIONS X - 1 inch Disposable (Standard) W - 1 inch Washable P - 2 inch Pleated

| OUTLET OPTIONS X - Front (Standard)

Ventilation Options ModelsWL18,WL24,WL25WL30,WL37WL42,WL48,WL60,WL70 DescriptionFactoryInstalled CodeNo.FieldInstalled PartNo.FactoryInstalled CodeNo.FieldInstalled PartNo.FactoryInstalled CodeNo.FieldInstalled PartNo. BarometricFreshAirDamper-StandardXBFAD-2XBFAD-3XBFAD-5 Blank-OffPlateBBOP-2BBOP-3BBOP-5 MotorizedFreshAirDamperMMFAD-2MMFAD-3MMFAD-5 CommercialVentilator-SpringReturnw/ExhaustVCRV-2VCRVS-3VCRVS-5 CommercialVentilator-PowerReturnw/Exhaust------PCRVP-3PCRVP-5 Economizer-FullyModulating1EEIFM-2BEEIFM-3CEEIFM-5C Economizer-FullyModulating12DN/ADN/ADN/A

1 Low ambient control is required with economizer for low temperature compressor operation. 2 For use only with “V” Control Module and TCS22 Controller.

Air ConditioningControl ModulesAll Models AVAILABLECONTROLOPTIONS HPC1LPC2CCM3LAC4ALR5SK6DDC7FactoryInstalledCodeFieldInstalledPart StandardStandardStandardStandardStandardJFactoryOnly StandardStandardStandardStandardStandardM6FactoryOnly StandardStandardStandardStandardStandardV8FactoryOnly

1 HPC: High pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note 3. 2 LPC: Low pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note 3. 3 CCM: Compressor control module has adjustable 30-second to 5-minute delay-on-break timer (which also provides a delay-on-make equal to 10% of delay- on-break setting). The module also provides the lockout feature (with 1 retry) for high and/or low pressure controls, and a 2-minute timed bypass for low pressure control. 4 LAC: Low ambient control permits cooling operation down to 0°F. 5 ALR: The alarm relay has a set of normally open and normally closed dry contacts to provide the ability to signal a condition of shutdown on either high or low pressure controls. 6 SK: Start kit can be used with all -A single phase models only. Is not used or available for -B or -C three phase models. 7 DDC: Incorporates 4 additional sensors: discharge air temperature, indoor blower airflow, compressor current, and dirty filter. These sensing devices function to input analog data such as temperature, as well as digital data such as air flow, compressor status or filter status. 8 "V" control module should be ordered in conjunction with direct digital controller (DDC) model TCS22. Refer to DDC specification sheet S3280 for more information.

Form No.

Bard Air Conditioner (357-93-E) — MODEL NUMBER | diagram (page 12)
Fig. 13

BARD MANUFACTURING CO. BRYAN, OHIO 43506 www.bardhvac.com

Due to our continuous product improvement policy, all specifications subject to change without notice.

Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.

S3279 February, 2006 · Supersedes S3279-106

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Bard Air Conditioner (357-93-E)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Bard Air Conditioner (357-93-E)

Be the first to ask — other owners or our team will answer.

Original document

Bard Air Conditioner (357-93-E) manual PDF

12 pages·372 KB·Air Conditioner·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…