with LEFT SIDE CONTROL PANEL
WL - SERIES Refrigerant 22 60Hz 1.5 to 6 Ton (18,300 to 67,000 Btuh) Left Side Control Panel

The Bard Wall-Mount Air Conditioner with Left Side Control Panel is designed to provide complete service access (i.e. compressor, electric heat strip and electrical controls) when two units are mounted side by side with minimal space between. The left side unit is the ideal product for telecommunication and over-the-road medical and communication vans requiring two wall-mount air conditioners be mounted side by side by using a WL (left side access) unit and a WA (right side access) unit on the same building. Factory or field installed accessories are also available to meet specific job requirements.
Aluminum Finned Copper Coils: Grooved tubing and enhanced louvered fin for maximum heat transfer and energy efficiency.
One Inch, Disposable Air Filters: Are standard equipment. Optional one inch washable filters available and filter racks permit the addition of 2" pleated filter. Factory or field installed.
Twin Blowers: Move air quietly. Most models feature multispeed blower motors providing airflow adjustment for high and low static operation. Motor overload protection is standard on all models.
Built-in Circuit Breakers: Standard on all single (230/208 volt) and three phase (230/208 volt) equipment. Toggle disconnects are standard on all three phase (460 volt) equipment.
Air Conditioner Compressor: Reciprocating compressors with crankcase heater and dual discharge muffler are standard on 1.5 and 2 ton models.
Slope Top: Standard feature for water run-off.
Top Rain Flashing: Standard feature on all models.
Scroll Compressors eliminate need for crankcase heater. Standard on 2.5 to 5 ton, and available on 2 ton models.
Full Length Mounting Brackets: Built into cabinet for improved appearance and easy installation. NOTE: Bottom mounting bracket included to assist in installation.
Phase Rotation Monitor: Standard on all 3 phase scroll compressors. Protects against reverse rotation if power supply is not properly connected. Not required on reciprocating compressors.
Auto-Reset High Pressure Switch: Built-in lock-out circuit resets from the room thermostat. Provides commercial quality protection to the compressor.
All packages are designed to meet your specific ventilation requirements utilizing one of five ventilation options for the product. The ventilation package is mounted within the unit eliminating the need for an exterior mounted hood or damper assembly on the unit. All assemblies can be factory installed, installed in the field at time of installation or as a retrofit system after installation.
Standard - Barometric
Galvanized 20 Gauge Zinc Coated Steel Cabinet: Cleaned, rinsed, sealed and dried before the polyurethane primer is applied. The cabinet is handsomely finished with a baked on textured enamel, which allows it to withstand 1000 hours of salt spray tests per ASTM B117-03.
Auto-Reset Low Pressure Switch: Built-in lock-out circuit and low pressure timed bypass circuit. Resets from room thermostat.
Optional - Motorized
Compressor Control Module: Built-in off-delay timer adjustable from 30 second to 5-minutes. 2-minute on-delay if power interrupt. 120-second bypass for low pressure control, and both soft and manual lockouts for high and low pressure controls. Alarm output for alarm relay.
Optional - Blank off Plate
Optional - Commercial
Electrical Components: Are easily accessible for routine inspection and maintenance through a left side, service panel opening. Features a lockable, hinged access cover to the circuit breaker or pull disconnect switch.
Optional - Economizer w/Exhaust
Low Ambient Control: Permits cooling operation down to 0°F outdoor ambient.
Electric Heat Strips: Features an automatic limit and thermal cut-off safety control. Heater packages can be factory installed for all 1.5 through 6 ton models.
Alarm Relay: Dry contacts for remote alarm capability on manual high or low pressure controls.
Fresh Air Damper · Fresh Air Damper

1 Capacity is certified in accordance with ARI Standard 390-2003 and tested in accordance with ARI Standard 210/240-2003. 2 EER = Energy Efficiency Ratio and is certified in accordance with ARI Standard 390-2003. 3 SEER = Seasonal Energy Efficiency Ratio and is tested in accordance with ARI Standard 210/240-2003. All ratings based on fresh air intake being 100% closed (no outside air introduction).

Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. All units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilation packages can be built-in at the factory, or field-installed at a later date.

BAROMETRIC FRESH AIR DAMPER - BFAD STANDARD The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The damper opens during blower operation and closes when the blower is off. Adjustable blade stops allow different amounts of outside air to be introduced into the building and can be easily locked closed if required.
BLANK OFF PLATE - BOP OPTIONAL A blank off plate is installed on the inside of the service door. It covers the air inlet openings which restricts any outside air from entering the unit. The blank off plate should be utilized in applications where outside air is not required to be mixed with the conditioned air.
Barometric Fresh Air Damper

MOTORIZED FRESH AIR DAMPER - MFAD OPTIONAL The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The two position damper can be fully open or closed. The damper blade is powered open by a 24VAC motor with spring return on power loss. The damper can be controlled by indoor blower operation or can be field connected to be managed based on building occupancy.
Motorized Fresh Air Damper

COMMERCIAL ROOM VENTILATOR - CRV OPTIONAL The built-in commercial room ventilator is internally mounted behind the service door and allows outside ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings. It includes a built-in exhaust air damper.
The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air quality by providing fresh air intake and exhaust capability through the CRV. The damper can be easily adjusted to control the amount of fresh air supplied into the building. The CRV can be controlled by indoor blower operation or field controlled based on room occupancy. Two versions available (except on 1.5 and 2-ton models). The CRV and CRVS are power open - spring return on power loss, and CRVP is power open and power return. Complies with ANSI/ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality”.

ECONOMIZER - EIFM OPTIONAL The built-in economizer system is internally mounted behind the service door and allows outdoor air to be introduced through the air inlet openings. The amount of outdoor air varies in response to the system controls and settings defined by the end user. It includes a built-in exhaust air damper. The economizer is designed to provide “free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running the compressor. This in turn provides lower operating costs, while extending the life of the compressor.
Manufactured under U.S. Patent Nos. 5,485,878; 5,301,744; 5,002,116; 4,924,934; 4,875,520; 4,825,936
Commercial Room Ventilator · Economizer

1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical Code (lastest version), Article 310 for power conductor sizing.
regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
the National Electrical Code and all local codes.

Total Air 0 ESP Total Air .15 ESP Total Air .3 ESP Vent Air 0 ESP Vent Air .15 ESP Vent Air .3 ESP


Total Air 0 ESP Total Air .15 ESP Total Air .3 ESP Vent Air 0 ESP Vent Air .15 ESP Vent Air .3 ESP

Total Air .15 ESP Total Air .3 ESP Vent Air 0 ESP


Total Air 0 ESP Total Air .2 ESP Total Air .4 ESP Vent Air 0 ESP Vent Air .2 ESP Vent Air .4 ESP

Total Air 0 ESP Total Air .2 ESP Total Air .4 ESP
Vent Air 0 ESP Vent Air .2 ESP Vent Air .4 ESP



Total Air 0 ESP Total Air .2 ESP Total Air .4 ESP Vent Air 0 ESP Vent Air .2 ESP Vent Air .4 ESP

Above data is with 1" standard disposable filter and 1" washable filter. For optional 2" pleated filter - reduce ESP by .15 in. See installation instructions for maximum ESP information on various KW application.
.yln o stin u V 8 0 2 / 0 3 2 n i elb alia v a e r a s r e t a e h cirtc ele e s e h T ) 1 (
.yln o stin u V 0 8 4 n i elb alia v a e r a s r e t a e h cirtc ele e s e h T ) 2 (
ELECTRIC HEAT ACCESS PANEL
ELECTRICAL CONTROL ACCESS PANEL
ELECTRICAL CONTROL ACCESS PANEL
COMPRESSOR ACCESS
COMPRESSOR ACCESS
Model WL with Left Side
Model WA with Right Side
15" · Control Panel · Control Panel


s s e c c A e c i v r e S r o f d e ri u q e R s e c n a r a e l C
o t d e ri u q e R s e c n a r a e l C m u m i n i M
w o l F ri A r e s n e d n o C e t a u q e d A d n a
s l a ir e t a M e l b it s u b m o C
S L E D O M E D I S T F E L E D I S T H G I R
S L E D O M 1 T C U D R I A Y L P P U S
T E E F E E R H T T S R I F T E N I B A C
7 3 L W , 5 2 L W , 4 2 L W , 8 1 L W " 0 2 " 5 1
0 7 L W , 0 6 L W , 8 4 L W , 2 4 L W " 0 2 " 0 2
5 2 L W , 4 2 L W , 8 1 L W " 0 " 0
7 3 L W , 0 3 L W " 4 / 1 " 0
0 7 L W , 0 6 L W , 8 4 L W , 2 4 L W " 4 / 1 " 0
1 Refer to the Installation Manual for more detailed information.
. ela c s ot t o n e r a s g n i w a r d la n o is n e m i D .s e h c n i n i e r a s n o is n e m id ll A
1 21.00 inches on model WL701

WL 37 2 A 10 X X X X X J
REVISION KW
CONTROL MODULES J - Standard on all models
CAPACITY | 18 - 1½ Ton 24 - 2 Ton 25 - 2 Ton 30 - 2½ Ton 37 - 3 Ton 42 - 3½ Ton 48 - 4 Ton 60 - 5 Ton 70 - 6 Ton
COLOR OPTIONS X - Beige (Standard) 1 - White 2 - Mesa Tan 4 - Buckeye Gray 5 - Desert Brown 8 - Dark Bronze
| COIL OPTIONS X - Standard 1 - Phenolic Coated Evaporator 2 - Phenolic Coated Condenser 3 - Phenolic Coated Evaporator and Condenser
VENTILATION OPTIONS See Table Below
VOLTS & PHASE | A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3
FILTER OPTIONS X - 1 inch Disposable (Standard) W - 1 inch Washable P - 2 inch Pleated
| OUTLET OPTIONS X - Front (Standard)
1 Low ambient control is required with economizer for low temperature compressor operation. 2 For use only with “V” Control Module and TCS22 Controller.
1 HPC: High pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note 3. 2 LPC: Low pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note 3. 3 CCM: Compressor control module has adjustable 30-second to 5-minute delay-on-break timer (which also provides a delay-on-make equal to 10% of delay- on-break setting). The module also provides the lockout feature (with 1 retry) for high and/or low pressure controls, and a 2-minute timed bypass for low pressure control. 4 LAC: Low ambient control permits cooling operation down to 0°F. 5 ALR: The alarm relay has a set of normally open and normally closed dry contacts to provide the ability to signal a condition of shutdown on either high or low pressure controls. 6 SK: Start kit can be used with all -A single phase models only. Is not used or available for -B or -C three phase models. 7 DDC: Incorporates 4 additional sensors: discharge air temperature, indoor blower airflow, compressor current, and dirty filter. These sensing devices function to input analog data such as temperature, as well as digital data such as air flow, compressor status or filter status. 8 "V" control module should be ordered in conjunction with direct digital controller (DDC) model TCS22. Refer to DDC specification sheet S3280 for more information.
Form No.

BARD MANUFACTURING CO. BRYAN, OHIO 43506 www.bardhvac.com
Due to our continuous product improvement policy, all specifications subject to change without notice.
Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
S3279 February, 2006 · Supersedes S3279-106