EN
Bard logo
Official user manual

Bard W12A2-A

17 pages·358 KB·Air Conditioner·PDF·ENDEFRITNLJA
Bard W12A2-A
Table of Contents 63 sections INSTALLATION INSTRUCTIONS · WALL MOUNTED PACKAGE AIR CONDITIONERS · Model: W12A2-A W12A1-K · GETTING OTHER INFORMATION and PUBLICATIONS · … ShowHide
INSTALLATION INSTRUCTIONSp.1WALL MOUNTED PACKAGE AIR CONDITIONERSp.1Model: W12A2-A W12A1-Kp.1GETTING OTHER INFORMATION and PUBLICATIONSp.3For more information, contact these publishers:p.3WALL MOUNT GENERAL INFORMATIONp.4AIR CONDITIONER WALL MOUNT MODEL NOMENCLATUREp.4MODEL NUMBERp.4AIR CONDITIONERp.4TABLE 1 ELECTRIC HEAT TABLEp.4FIGURE 1 UNIT DIMENSIONSp.5MIS-2608 Ap.5TABLE 2 ELECTRICAL HEAT SPECIFICATIONSp.6SHIPPING DAMAGEp.6GENERALp.6DUCT WORKp.7FRESH AIR INTAKEp.7CONDENSATE DRAINp.7FILTERSp.7FIGURE 2 FRESH AIR DAMPERp.7WALL MOUNTING INFORMATIONp.8MOUNTING THE UNITp.8FIGURE 4 WALL MOUNTING INSTRUCTIONSp.10FIGURE 5 WALL MOUNTING INSTRUCTIONSp.10FIGURE 6 COMMON WALL-MOUNTING INSTALLATIONSp.11WIRING – MAIN POWERp.12WIRING – LOW VOLTAGE WIRINGp.12Tap Range 240 253 - 216 208 220 - 187p.12START UPp.13GENERAL:p.13WARNINGp.13SAFETY PRACTICES:p.13TOPPING OFF SYSTEM CHARGEp.13IMPORTANT INSTALLER NOTEp.14High Pressure Switch and Lockout Sequencep.14SERVICE HINTSp.14Low Pressure Switch, Bypass and Lockout Sequencep.14HIGH & LOW PRESSURE SWITCHp.14SEQUENCE OF OPERATIONp.14Alarm Relay Outputp.14COMPRESSOR CONTROL MODULEp.14Adjustable Delay on Make and Break Timerp.14ADJUSTMENTSp.15PRESSURE SERVICE PORTSp.15Adjustable Delay on Make and Delay on Break Timerp.15Typical Settings for Dual Unit Installation:p.15TROUBLESHOOTINGp.16FAN BLADE SETTING DIMENSIONSp.16TABLE 4 INDOOR BLOWERp.16PERFORMANCE CFM @ 230V / 115Vp.16FIGURE 7 FAN BLADE SETTING DIMENSIONp.16CFMp.16ESPp.16TABLE 3 FAN BLADE DIMENSIONp.16TABLE 6 MAXIMUM ESP OF OPERATIONp.16ELECTRIC HEAT ONLYp.16W12A2-A00p.16R-410A REFRIGERANT CHARGEp.16A03 A05p.16W12A1-K00p.16K02p.16TABLE 7 PRESSURE TABLEp.17TABLE 8 OPTIONAL FIELD INSTALLED ACCESSORIESp.17
Page 1 of the Bard W12A2-A user manual — INSTALLATION INSTRUCTIONS
Page 1 · click to enlarge
Page 1

INSTALLATION INSTRUCTIONS

WALL MOUNTED PACKAGE AIR CONDITIONERS

Model: W12A2-A W12A1-K

Bard W12A2-A — INSTALLATION INSTRUCTIONS diagram (page 1)
Fig. 1

Bard Manufacturing Company, Inc. Bryan, Ohio 43506

Manual2100-509E Supersedes: 2100-509D File: Volume III Tab 16 Date: 08-20-12

Since 1914 Moving ahead just as planned.

Page 2 of the Bard W12A2-A user manual — INSTALLATION INSTRUCTIONS
Page 2 · click to enlarge
Page 2
Page 2 of the Bard W12A2-A user manual — INSTALLATION INSTRUCTIONS
Page 3 of the Bard W12A2-A user manual — For more information, contact these publishers:
Page 3 · click to enlarge
Page 3

GETTING OTHER INFORMATION and PUBLICATIONS

These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.

For more information, contact these publishers:

ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721

National Electrical Code ANSI/NFPA 70

Standard for the Installation of ANSI/NFPA 90A Air Conditioning and Ventilating Systems

ANSI American National Standards Institute 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286

Standard for Warm Air Heating ANSI/NFPA 90B and Air Conditioning Systems

ASHRAE American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc. 1791 Tullie Circle, NE Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478

Load Calculation for ACCA Manual J Residential Winter and Summer Air Conditioning

Duct Design for ACCA Manual D Residential Winter and Summer Air Conditioning and Equipment Selection

NFPA National Fire Protection Association Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-355 Fax: (617) 984-7057

Manufactured under the following U.S. patent numbers:

5,485,878 and 5,301,744

Page 4 of the Bard W12A2-A user manual — TABLE 1 ELECTRIC HEAT TABLE
Page 4 · click to enlarge
Page 4

WALL MOUNT GENERAL INFORMATION

AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE

W 12 A 2 – A 00 X J

MODEL NUMBER

REVISIONS CONTROL MODULES E - Low Ambient Control J - Telecommunication VOLTS & PHASE A - 230/208/60/1 K - 115/60/1

CAPACITY 12 - 1 Ton

AIR CONDITIONER

KW 00 - No KW 02 - 2.2 KW 03 - 3.6 KW 05 - 5.0 KW

COIL OPTIONS X - Standard Coils

COLOR OPTIONS X - Beige 4 - Buckeye Gray OUTLET OPTIONS X - Front

VENTILATION OPTIONS X - Barometric Fresh Air Damper (Standard) B - Blank-off Plate E - Economizer (Internal) - Fully Modulating with Exhaust V - Commercial Ventilator - Motorized with Exhaust

FILTER OPTIONS X - 1-Inch Throwaway (Standard) P - 2-Inch Pleated

TABLE 1 ELECTRIC HEAT TABLE

Models KWW12A2-AW12A1-K 240V208V120V Aj BTUAj BTUAj BTU 0218.37,985 0315.012,76013.09,705 0520.817,54018.113,275

j With blower watts included

Page 5 of the Bard W12A2-A user manual — MIS-2608 A
Page 5 · click to enlarge
Page 5

FIGURE 1 UNIT DIMENSIONS

Bard W12A2-A — FIGURE 1 UNIT DIMENSIONS diagram (page 5)
Fig. 2
Bard W12A2-A — FIGURE 1 UNIT DIMENSIONS diagram (page 5)
Fig. 3

Return air opening is in lower Return air opening is in upper

Bard W12A2-A — FIGURE 1 UNIT DIMENSIONS diagram (page 5)
Fig. 4
Bard W12A2-A — FIGURE 1 UNIT DIMENSIONS diagram (page 5)
Fig. 5

Heater and Filter Access

is Blow Thru Condenser Airflow

Front View Right Side View

( * ) Position of return air flanges are interchangeable between two positions. Factory built at 5 inches. Note: Maintain a minimum of 20 inches clearance on right side to allow access to control panel and allow proper airflow to outdoor condenser coil. Allow 15 inches on left side.

MIS-2608 A

(*) Position of return air flanges are interchangeable between two positions. Factory built at 5 inches. NOTE: Maintain a minimum of 20 inches clearance on right side to allow access to control panel and allow proper airflow to outdoor condenser coil. Allow 15 inches on left side.

Show 11 more labels / short text on this page
Back View · field convertible position · factory standard position · Built-in Rain · Hood 4° Pitch · Electric Heat · Ventilation Air · Circuit Breaker · (Optional) · Entrance Electrical · Entrance Low Voltage
Page 6 of the Bard W12A2-A user manual — GENERAL
Page 6 · click to enlarge
Page 6

TABLE 2 ELECTRICAL HEAT SPECIFICATIONS

SINGLE CIRCUIT ModelsRated Volts and PhaseNo. Field Power Circuitsl Minimum Circuit Ampacityj Maximum External Fuse or Circuit Breakerk Field Power Wire Sizek Ground Wire Size W12A2-A00 A03 A05230/208-11 1 19 20 2815 20 3014 12 1014 12 10 W12A1-K00 K02115-11 120 2930 3010 1010 10

Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.

Based on 75°C copper wire. All wiring must conform to NEC and all local codes.

These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical Code (latest revision), article 310 for power conductor sizing.

SHIPPING DAMAGE

These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.

Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.

While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.

GENERAL

The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.

The refrigerant system is completely assembled and charged. All internal wiring is complete.

Size of unit for a proposed installation should be based on heat loss/gain calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.

The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return air ducts.

These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.

Page 7 of the Bard W12A2-A user manual — FIGURE 2 FRESH AIR DAMPER
Page 7 · click to enlarge
Page 7

DUCT WORK

FRESH AIR INTAKE

All duct work, supply and return must be properly sized for the design air flow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.

All units are built with fresh air inlet slots punched in the service panel.

If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position. To allow the damper to operate, the maximum and minimum blade position stops must be installed. See Figure 2.

Refer to Table 6 for maximum static pressure available for duct design.

All capacity, efficiency and cost of operation information as required for Department of Energy “Energyguide” Fact Sheets is based upon the fresh air blank-off plate in place and is recommended for maximum energy efficiency.

Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.

The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.

CONDENSATE DRAIN

Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.

This unit employs an automatic condensate disposal system consisting of a base drain pan, drain valve and fan blade with slinger ring. A plastic drain hose extends from the evaporator drain pain at the top of the unit to the base drain pan at the bottom. At temperatures above 40°, the drain valve located between the condenser coil and fan shroud is closed allowing water to build up in the base to a height of 5/8" to 3/4". The fan blade with slinger then rotates in this water and throws the water onto the condenser coil. This disposes of the water by evaporating it on the hot condenser.

Some installations may not require any return air duct. It is recommended that on this type of installation that a filter grille be located in the wall. Filters must be of sufficient size to allow a maximum velocity of 400 FPM.

installation codes may limit this cabinet to installation only in a single story structure.

FILTERS

At temperatures below 40°, the drain valve opens draining the base pan and preventing freeze ups that could damage the coil or fan blade.

A one inch throwaway filter is supplied with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the service door. A 2-inch pleated filter is also available as an optional accessory. The internal filter brackets are adjustable to accommodate the 2-inch filter by bending the metal tabs holding the 1-inch filter down. There are two tabs on each side of the filter.

FIGURE 2 FRESH AIR DAMPER

Bard W12A2-A — FIGURE 2 FRESH AIR DAMPER diagram (page 7)
Fig. 6
Page 8 of the Bard W12A2-A user manual — MOUNTING THE UNIT
Page 8 · click to enlarge
Page 8

INSTALLATION INSTRUCTIONS

WALL MOUNTING INFORMATION

4. Position unit in opening and secure with 5/16 lag

bolts; use 7/8 inch diameter flat washers on the lab bolts.

1. These units are secured by wall mounting brackets

which secure the unit to the outside wall surface at both sides.

5. Secure rain flashing to wall and caulk across entire

length of top. See Figure 3.

2. On wood frame walls, the wall construction must be

strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.

6. For additional mounting rigidity, the return air

and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.

3. Concrete block walls must be thoroughly inspected

to insure that they are capable of carrying the weight of the installed unit.

7. On side-by-side installations, maintain a minimum

MOUNTING THE UNIT

of 20 inches clearance on right side to allow access to control panel and allow proper airflow to outdoor coil. Additional clearance may be required to meet local or national codes.

1. Two holes, for the supply and return air openings,

must be cut through the wall as shown in Figure 3.

2. Locate and mark lag bolt locations, if desired. See

Figure 3.

3. Hook top rain flashing under back bend of top. Top

rain flashing is shipped attached to the back of the unit on the right side.

Page 9 of the Bard W12A2-A user manual — WALL MOUNTING INFORMATION
Page 9 · click to enlarge
Page 9
Bard W12A2-A — WALL MOUNTING INFORMATION diagram (page 9)
Fig. 7
Page 10 of the Bard W12A2-A user manual — FIGURE 5 WALL MOUNTING INSTRUCTIONS
Page 10 · click to enlarge
Page 10

FIGURE 4 WALL MOUNTING INSTRUCTIONS

Bard W12A2-A — FIGURE 4 WALL MOUNTING INSTRUCTIONS diagram (page 10)
Fig. 8

FIGURE 5 WALL MOUNTING INSTRUCTIONS

Bard W12A2-A — FIGURE 5 WALL MOUNTING INSTRUCTIONS diagram (page 10)
Fig. 9
Page 11 of the Bard W12A2-A user manual — FIGURE 6 COMMON WALL-MOUNTING INSTALLATIONS
Page 11 · click to enlarge
Page 11

FIGURE 6 COMMON WALL-MOUNTING INSTALLATIONS

Bard W12A2-A — FIGURE 6 COMMON WALL-MOUNTING INSTALLATIONS diagram (page 11)
Fig. 10
Page 12 of the Bard W12A2-A user manual — Tap Range 240 253 - 216 208 220 - 187
Page 12 · click to enlarge
Page 12

WIRING – MAIN POWER

WIRING – LOW VOLTAGE WIRING

Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.

230/208, 1 phase equipment use dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

Tap Range 240 253 - 216 208 220 - 187

power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

The electrical data lists fuse and wire sizes (75°C copper) for all models, including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.

The unit rating plate lists a “Maximum Time Delay Relay Fuse” of “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

For wiring size and connections, refer to Wiring Manual 2100-507.

Page 13 of the Bard W12A2-A user manual — TOPPING OFF SYSTEM CHARGE
Page 13 · click to enlarge
Page 13

START UP

THESE UNITS REQUIRE R-410A REFRIGERANT AND POLYOL ESTER OIL.

REMEMBER: When adding R-410A refrigerant, it must come out of the charging cylinder/tank as a liquid to avoid any fractionation, and to insure optimal system performance. Refer to instructions for the cylinder that is being utilized for proper method of liquid extraction.

GENERAL:

1. Use separate service equipment to avoid cross contamination of oil and refrigerants.

WARNING

2. Use recovery equipment rated for R-410A refrigerant.

Failure to conform to these practices could lead to damage, injury or death.

3. Use manifold gauges rated for R-410A (800 psi/250 psi low).
4. R-410A is a binary blend of HFC-32 and HFC-125.
5. R-410A is nearly azeotropic - similar to R-22 and R-12. Although nearly azeotropic, charge with liquid refrigerant.

SAFETY PRACTICES:

1. Never mix R-410A with other refrigerants.
2. Use gloves and safety glasses, Polyol Ester oils can be irritating to the skin, and liquid refrigerant will freeze the skin.
6. R-410A operates at 40-70% higher pressure than R-22, and systems designed for R-22 cannot withstand this higher pressure.
3. Never use air and R-410A to leak check; the mixture may become flammable.
7. R-410A has an ozone depletion potential of zero, but must be reclaimed due to its global warming potential.
4. Do not inhale R-410A – the vapor attacks the nervous system, creating dizziness, loss of coordination and slurred speech. Cardiac irregularities, unconsciousness and ultimate death can result from breathing this concentration.
8. R-410A compressors use Polyol Ester oil.
9. Polyol Ester oil is hygroscopic; it will rapidly absorb moisture and strongly hold this moisture in the oil.
10. A liquid line dryer must be used - even a deep vacuum will not separate moisture from the oil.
5. Do not burn R-410A. This decomposition produces hazardous vapors. Evacuate the area if exposed.
11. Limit atmospheric exposure to 15 minutes.
12. If compressor removal is necessary, always plug compressor immediately after removal. Purge with small amount of nitrogen when inserting plugs.
6. Use only cylinders rated DOT4BA/4BW 400.
7. Never fill cylinders over 80% of total capacity.
8. Store cylinders in a cool area, out of direct sunlight.

TOPPING OFF SYSTEM CHARGE

9. Never heat cylinders above 125°F.

If a leak has occurred in the system, Bard Manufacturing recommends reclaiming, evacuating (see criteria above), and charging to the nameplate charge. If done correctly, topping off the system charge can be done without problems.

10. Never trap liquid R-410A in manifold sets, gauge lines or cylinders. R-410A expands significantly at warmer temperatures. Once a cylinder or line is full of liquid, any further rise in temperature will cause it to burst.

With R-410A, there are no significant changes in the refrigerant composition during multiple leaks and recharges. R-410A refrigerant is close to being an azeotropic blend (it behaves like a pure compound or single component refrigerant). The remaining refrigerant charge, in the system, may be used after leaks have occurred and then “top-off” the charge by utilizing the pressure charts on the inner control panel cover as a guideline.

Page 14 of the Bard W12A2-A user manual — Adjustable Delay on Make and Break Timer
Page 14 · click to enlarge
Page 14

START UP

IMPORTANT INSTALLER NOTE

During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.

For improved start up performance, wash the indoor coil with a dishwasher detergent.

High Pressure Switch and Lockout Sequence

SERVICE HINTS

If the high pressure switch opens, the compressor contactor will de-energize immediately. The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay on break time has expired. If the high pressure switch opens again in this same operating cycle the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.

1. Caution owner to maintain clean air filters at all

times. Also not to needlessly close off supply and return air registers. This reduces airflow through the system which shortens equipment service life as well as increasing operation costs.

2. The unit is equipped with a high pressure cut out

switch.

3. Check all power fuses or circuit breakers to be sure

they are the correct rating.

Low Pressure Switch, Bypass and Lockout Sequence

4. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

If the low pressure switch opens for more than 120 seconds, the compressor contactor will de-energize and go into a soft lockout. Regardless the state of the low pressure switch, the contactor will reenergize after the delay on make time delay has expired. If the low pressure switch remains open, or opens again for longer that 120 seconds, the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.

HIGH & LOW PRESSURE SWITCH

The W12Aà models are supplied with a remote reset high and low pressure switch. If tripped, this pressure switch may be reset by turning the thermostat off then back on again.

SEQUENCE OF OPERATION

HEATING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation. On a call for heating, circuit R-W1 make at the thermostat pulling in heat contact for the strip heat and blower operation.

Alarm Relay Output

Alarm terminal is output connection for applications where alarm relay is employed. This terminal is powered whenever compressor is locked out due to HPC or LPC sequences as described.

are inherently automatic reset devices. The high pressure switch and low pressure switch cut out and cut in settings are fixed by specific air conditioner or heat pump unit model. The lockout features, both soft and manual, are a function of the Compressor Control Module.

COMPRESSOR CONTROL MODULE

The compressor control module is optional on the models covered by this manual. The compressor control is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm relay output.

Adjustable Delay on Make and Break Timer

On initial power up or any time power is interrupted to the unit the delay on make period begins, which will be 2 minutes plus 10% of the delay on break setting. When the delay on make is complete and the high pressure switch (and low pressure switch if employed) is closed, the compressor contactor is energized. Upon shutdown the delay on break time starts and prevents restart until the delay on break and delay on make periods have expired.

Page 15 of the Bard W12A2-A user manual — Typical Settings for Dual Unit Installation:
Page 15 · click to enlarge
Page 15

ADJUSTMENTS

PRESSURE SERVICE PORTS

Adjustable Delay on Make and Delay on Break Timer

High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure chart can be found later in the manual covering all models. It is imperative to match the correct pressure chart to the unit by model number.

The potentiometer is used to select Delay on Break time from 30 seconds to 5 minutes. Delay of Make (DOM) timing on power up and after power interruptions is equal to 2 minutes plus 10% of Delay of Break (DOB) setting:

0.5 minute (30 seconds) DOB = 123 second DOM 1.0 minute (60 seconds) DOB = 126 second DOM 2.0 minute (120 seconds) DOB = 132 second DOM 3.0 minute (180 seconds) DOB = 138 second DOM 4.0 minute (240 seconds) DOB = 144 second DOM 5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power interruptions the compressor will operate on demand with not delay.

Typical Settings for Dual Unit Installation:

Unit No. 1: DOB set at 2 minutes, and DOM is 132 seconds.

Unit No. 2: DOB set at 4 minutes, and DOM is 144 seconds.

Page 16 of the Bard W12A2-A user manual — K02
Page 16 · click to enlarge
Page 16

TROUBLESHOOTING

FAN BLADE SETTING DIMENSIONS

TABLE 4 INDOOR BLOWER

Shown in Figure 7 is the correct fan blade setting dimension for proper air delivery across the outdoor coil.

PERFORMANCE CFM @ 230V / 115V

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimension below be checked and blade adjusted in or out on the motor shaft accordingly.

Bard W12A2-A — PERFORMANCE CFM @ 230V / 115V diagram (page 16)
Fig. 11

FIGURE 7 FAN BLADE SETTING DIMENSION

530 / 500 485 / 460 440 / 425 390 / 375 325 / 300

465 / 425 415 / 400 365 / 350 315 / 300 270 / 265

Bard W12A2-A — FIGURE 7 FAN BLADE SETTING DIMENSION diagram (page 16)
Fig. 12

TABLE 5 RATED CFM AND ESP RECOMMENDED AIRFLOW RANGE

CFM

ESP

W12Aà 400 .10 500 - 300

° Rated CFM and ESP on low speed tap.

TABLE 3 FAN BLADE DIMENSION

TABLE 6 MAXIMUM ESP OF OPERATION

ELECTRIC HEAT ONLY

W12A2-A00

.35 .35 .35

R-410A REFRIGERANT CHARGE

A03 A05

W12A1-K00

.35 .35

This unit was charged at the factory with the quantity of refrigerant listed on the serial plate. AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity.

K02

Values shown are for units equipped with STD 1" throwaway filters. Derate ESP by .15 for 2" pleated filters.

The following pressure tables show nominal pressures for the units. Since many installation specific situations can affect the pressure readings, this information should only be used by certified technicians as a guide for evaluating proper system performance. They shall not be used to adjust charge. If charge is in doubt, reclaim, evacuate and recharge the unit to the serial plate charge.

Show 8 more labels / short text on this page
° Rated · ° Rated · Recommended · Model · Airflow Range · Model Dimension A · W12Aà 1/2" · Model ESP
Page 17 of the Bard W12A2-A user manual — TABLE 8 OPTIONAL FIELD INSTALLED ACCESSORIES
Page 17 · click to enlarge
Page 17

TABLE 7 PRESSURE TABLE

COOLING Air Temperature Entering Outdoor Coil °F

Bard W12A2-A — TABLE 7 PRESSURE TABLE diagram (page 17)
Fig. 13

Model Return Air Temperature Pressure 75° 80° 85° 90° 95° 100° 105° 100° 115°

75 deg. DB 62 deg. WB Low Side High Side

120 291 124 310 129 332 133 355 136 379 138 405 141 432 142 460 143 490

80 deg. DB 67 deg. WB Low Side High Side

128 298 133 318 138 340 142 364 143 387 148 415 151 443 152 472 153 503

85 deg. DB 72 deg. WB Low Side High Side

132 308 138 329 143 352 147 377 150 403 153 430 156 459 157 489 158 521

Low Side Pressure +4 PSIG High Side Pressure +10 PSIG

TABLE 8 OPTIONAL FIELD INSTALLED ACCESSORIES

Bard W12A2-A — TABLE 8 OPTIONAL FIELD INSTALLED ACCESSORIES diagram (page 17)
Fig. 14

W12Aà · Model Description

Display codes

Error codes

What the fault codes shown on the display mean and how to clear them.

CodeMeaningFix
R-12Although nearly azeotropic, charge with p.13

Ask about the Bard W12A2-A

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Bard W12A2-A

Be the first to ask — other owners or our team will answer.

Original document

Bard W12A2-A manual PDF

17 pages·358 KB·Air Conditioner·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…