RETAIN THESE INSTRUCTIONS
STANDARD SERIES
FOR FUTURE REFERENCE
MODELS
This appliance may be installed in an after- market permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convert- ible for use with other gases, unless a certi- fied kit is used.
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors or liquids in the vicin- ity of this or any other appliance.
POUR VOTRE SÉCURITÉ: Ne pas entreposer ni utiliser d'essence ni d'autre vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
WH Report No. J20006722
L'installation et service doit être exécuté par un qualifié installeur, agence de service ou le fournisseur de gaz.


Millivolt appliances may be fitted at time of manufacture with either a Honeywell millivolt gas control valve or as SIT millivolt gas control valve. Both valves have been tested with and approved for use with these appliances and are listed accordingly.
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning are similar to the flu with headaches, dizziness and/or nausea. If you have these signs, obtain fresh air immedi- ately. Turn off the gas supply to the appliance and have it serviced by a qualified profes- sional, as it may not be operating correctly.
These appliances are equipped with an inte- gral combustion air door and actuator arm. Combustion air kits are optional and must be installed before removing the securing screw allowing the movement of the combustion air actuator arm (see Step 7).
Test gage connections are provided on the front of the millivolt gas control valve (iden- tified IN for the inlet and OUT for the mani- fold side). A ¹⁄₈" NPT test gage connection is provided at the inlet and outlet side of the electronic gas control valve.
WARNING: B-VENT APPLIANCES ARE NOT DESIGNED TO OPERATE IN NEGATIVELY PRESSURED ENVIRONMENTS (PRESSURE WITHIN THE HOME IS LESS THAN PRES- SURES OUTSIDE). SIGNIFICANT NEGA- TIVELY PRESSURED ENVIRONMENTS CAUSED BY WEATHER, HOME DESIGN, OR OTHER DEVICES MAY IMPACT THE OPERATION OF THESE APPLIANCES. NEGATIVE PRESSURES MAY RESULT IN POOR FLAME APPEARANCE, SOOTING, DAMAGE TO PROPERTY AND/OR SEVERE PERSONAL INJURY. DO NOT OPERATE THESE APPLIANCES IN NEGATIVELY PRES- SURED ENVIRONMENTS.
Minimum inlet gas pressure to the appliance is 5.0 inches water column (1.24 kPa) for natural gas and 11 inches water column (2.74 kPa) for propane for the purpose of input adjustment.
Maximum inlet gas supply pressure to the appliance is 10.5 inches water column (2.61 kPa) for natural gas and 13.0 inches water column (3.23 kPa) for propane.
In selecting the location, the aesthetic and functional use of the appliance are primary concerns. However, vent system routing to the exterior and access to the fuel supply are also important. Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies. Consider- ation should be given to traffic ways, furniture, draperies, etc., due to elevated surface tem- peratures. The location should also be free of electrical, plumbing or other heating/air con- ditioning ducting.
The appliance must be isolated from the gas supply piping system (by closing its indi- vidual manual shut-off valve) during any pressure testing of the gas supply piping system at test pressures equal to or less than ¹⁄₂ psig (3.5 kPa).
The appliance and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at pressures in excess of ¹⁄₂ psig (3.5 kPa).
These appliances must not be connected to a chimney or flue serving a separate solid fuel burning appliance.
The appliance should be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materi- als. However, if installed on combustible ma- terials, such as carpeting, vinyl tile, etc., a metal or wood barrier covering the entire bot- tom surface must be used.
Do not place clothing or other materials on or near this appliance.
These appliances may be used for bedroom installations in the United States and are listed accordingly. These units may not be installed in bedrooms in Canada.
Minimum clearance to combustibles for the appliance is as follows: sides and back - 0" (0 mm), floor - 0" (0 mm), adjacent wall - 0" (0 mm), ceiling - 64" (1626 mm).
Typical Locations


Gas Vent Rule – Gas vent caps are not permit- ted within 8 feet (2.4 mm) of a vertical wall or similar obstruction. Gas vent caps that are located 8' or more from a portion of a building which extends at an angle greater than 45° upward from the horizontal may terminate in accordance with Table 1 (Figure 3 ), provided that in no case shall any discharge opening on the cap be less than 2' (610 mm) horizontally from the roof surface (National Fuel Gas Code ANSI Z223.1 (NFPA 54) 7.6.2) (CAN/CGA B149).
Roof Pitch is X/12
Minimum Height from Roof to Lowest Discharge Opening
Multiple Terminations – These appliances may vent adjacent to and at the same level with any other gas appliances (including direct-vent appliances) provided that there is at least 2 ft. (0.6m) between the proximal edges of the vent caps. These appliances may be vented adja- cent to a chimney vent servicing a solid fuel fireplace provided the B-vent cap is at least 2 ft. (0.6m) away from the nearest point of the chimney opening.
Table 1

Back Wall of Chase/Enclosure
The fireplace may be installed directly on a combustible floor or raised on a platform of an appropriate height. Do not place fireplace on carpeting, vinyl or other soft floor coverings. It may, however, be placed on flat wood, ply- wood, particle board or other hard surfaces. Be sure fireplace rests on a solid continuous floor or platform with appropriate framing for sup- port and so that no cold air can enter the room from under the fireplace.
H
F
G
A E
Rough Framing Face (Unfinished Shown)
The fireplace may be positioned and then the framing built around it, or the framing may be constructed and the fireplace positioned into the opening.
Usually, no special floor support is needed for the fireplace, however, to be certain:
Back Wall of Chase/Enclosure
Rough Framing Face (Unfinished Shown)
If you plan to raise the fireplace and hearth extension, build the platform assembly then position fireplace and hearth extension on top. Secure the platform to the floor to prevent possible shifting.
The typical sequence of installation follows, however, each installation is unique resulting in variations to those described.
Back Wall of Chase/Enclosure
G
Rough Framing Face (Unfinished Shown)
If the appliance is to be elevated above floor level, a solid continuous platform must be constructed.
The header may rest on the top metal spacers, but must not be notched to fit around them.
Consult all local codes.

Step 2. Route gas line (Figure 8) using tech- niques and materials prescribed by local and/ or national codes. It is recommended that a gas line of ¹⁄₂" or greater diameter be used to allow full gas volume to the fireplace. Undue pressure loss will occur if the pipe is too small. The appliance, as set up at the factory, is best suited for use with a gas line routed from the right side. The gas line may however be alter- nately routed from the left side.
4” Type B Vent
Fireplace should be secured to side framing members using provided nailing flanges. Use 8d nails (see Figure 9 ).
When rigid pipe is used, an ANSI approved manual shut-off valve and union must be in- stalled upstream of the fireplace.
1 - Vertical - Minimum overall height of the vent system and appliance without an offset must be 12' (3.66 m) 2 - With Offset - Minimum overall height of the vent system and appliance must be 15' (4.57 m) when an offset up to 60 degrees from the vertical is used. There must be a minimum vertical vent height of 2 ft. (0.6 m) above the appliance collar before the offset can be applied. 3 - With Offset, when using the optional, 36GEP or 36GEP-BB, non-operable glass doors - Minimum overall height of the vent system and appliance must be 12' (3.66 m) when an offset up to 60 degrees from the vertical is used. The lower part of the offset may start at the appli- ance flue collar.
Ensure that a sediment trap is installed in the existing gas line, if not, install a sediment trap upstream to prevent moisture and contaminants from passing through trap to the appliance con- trols and burners. Failure to do so could prevent the appliance from operating reliably.
An external regulator must be used on all pro- pane (L.P.G.) heaters to reduce the supply tank pressure to 13" w.c. (maximum). Any copper tubing used to supply propane (L.P.G.) from the tank must be internally tinned.
Maximum overall height of the vent system and appliance should not exceed 40 feet (12.19 m).
Install the B-vent system in accordance with the vent manufacturer's instructions.
All appliances are equipped with a gas flex line and shutoff valve attached directly to the gas control valve. To quickly and easily complete the gas line routing, use the gas flex line kit.
SIDE
5 ³⁄₄" (146 mm)
15 ft. Minimum
12 ft. Minimum
12 ft. Minimum 60* degrees Maximum
Offset 2 ft. Minimum To Offset
2 ¹⁄₄" (57 mm)
Back View Of Appliance
Back View Of Appliance
Back View Of Appliance
Refer to fireplace drawings and specifications on pages 4 and 5 for framing dimensions and details. Framing header may be positioned di- rectly on the fireplace top spacers.
*This Vent Configuration Allowable Only WithThe Following Optional Non-Operable Glass Doors installed:

A. Millivolt Wiring – Units may be fitted at the factory with either a Honeywell millivolt gas control valve or an SIT millivolt gas control valve. Both valves have been tested with and approved for use with these appliances and are listed accordingly. Refer to Figure 12 for wiring of Honeywell systems and Figure 13 for wiring of SIT systems.
B. Electronic Wiring – The electronic appliance must be connected to the main power supply. To install:
The gas control valve is located in the lower control compartment. To access the valve re- move the removable access panel and set aside (Figure 15 ).
The gas valve has been set in place and has been pre-wired at the factory. No additional wiring is required unless the optional wall switch or optional remote control kit is to be installed. Locate the optional wall switch or optional remote control in the desired loca- tion and connect the millivolt wire (see Fig- ures 12 and 13 ).
CAUTION: DO NOT CONNECT THE WALL SWITCH TO A 120V POWER SUPPLY. IMPORTANT: Ground lead must be connected to the green screw located on the outlet box. See Figure 14 . Failure to do so will result in a potential safety hazard. The appliance must be electrically grounded in accordance with local codes or, in the absence of local codes, the National Electrical Code, ANSI/NFPA 70- (latest edition). (In Canada, the current CSA C22-1 Canadian Electrical Code.)
The millivolt control valve has a ³⁄₈" (10 mm) NPT thread inlet port. The electronic control valve has a ¹⁄₂" (13 mm) NPT thread inlet port and is fitted with a ¹⁄₂" x ³⁄₈" (13 mm x 10 mm) NPT fitting. Both the millivolt and elec- tronic models are fitted with a gas flex line and shutoff valve, ³⁄₈" NPT. Plan the connections accordingly.
Honeywell Millivolt Wiring Diagram
If any of the original wire as supplied must be replaced, it must be replaced with Type AWM 105°C – 18 GA. wire.
BK
TH
BK
TH
Gas Controls on Valve
TPTH
Electronic Wiring Diagram (Honeywell)
(Optional ON/OFF Switch Wiring)
TP
OPT. ACCESSORY
BK
CONTROL PILOT ASSEMBLY
SWITCH
IGNITER
BK
BK
120 VAC.
* For Wall Switch Attachment Only.
R
Figure 12 Figure 15
G
Secure all joints tightly using appropriate tools and sealing compounds (ensure propane resis- tant compounds are used in propane applica- tions). Turn on gas supply and test for gas leaks using a soapy water solution. Never use an open flame to check for leaks.
SIT Millivolt Wiring Diagram
If any of the original wire as supplied must be replaced, it must be replaced with Type AWM 105°C – 18 GA. wire.
B
Transf.
BK
TH TP TH
A. Mix a 50% dish soap, 50% water solution.
BL
TP
R
B. Light the appliance (refer to the lighting instructions provided in the Homeowner's Care and Operation Instructions).
BK WHT BK BK
BK
OPTIONAL ON/OFF SWITCH
LIMIT SWITCH
C. Brush all joints and connections with the soapy water solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the gas control knob to the “OFF” position. Either tighten or refasten the leaking connec- tion and retest as described above.
OR WALL SWITCH
* For Wall Switch Attachment Only.
Factory Wired Field Wired
Figure 13 Figure 14


D. When the gas lines are tested and leak free, observe the individual tongues of flame on the burner. Make sure all ports are open and pro- ducing flame evenly across the burner. If any ports are blocked, or partially blocked, clean out the ports.
After completing the installation of the optional combustion air vent system the actuator arm must be put in service and tested to ensure proper operation before completing any enclo- sure around the firebox. Failure to do so may result in extensive and costly rework.
Locate the actuator arm along the right side of the appliance firebox opening and refer to Figure 18. After completing the installation of the Outside Combustion Air Kit remove and discard the actuator arm locking screw.
¹ ₂" x ³ ₈" Flare Shut-Off Valve
³ ₈" NPT Flare Fitting (Remove Before Hard Piping)
Alternate “Hard Piping” (may be required in some areas, consult local codes.)
Remove Locking Screw and “Pop” Actuator to the Left Before Initial Use
Pull Forward to Open, Push Back to Close
Outside Air Actuator

To operate, push the end of the actuator to the left as shown in Figure 18, until it "pops" free of its "locked" position. Pull the actuator forward to open the combustion air door, and push it back to close. To "lock" the combustion air door closed, ensure the actuator is pushed all the way back then push the end of the actuators to the right until the step in the actuator moves behind the appliance front face within the slotted opening.
Subsequent lightings of the appliance will not require such purging. Inspect the pilot flame (remove logs, if necessary, handling care- fully).
This appliance is equipped with a manually- reset blocked flue safety switch. Refer to Figure 21 for its location. If during appliance operation, the flame goes out (independently of the burner on/off wall switch), it may be due to the operation of this safety limit switch. First allow the appliance to cool. Then reset the safety switch by pushing the red reset button on the back of the switch.
Operate the actuator through several cycles including the "lock" position. Ensuring proper operation and freedom of movement. Return the actuator arm to the locked position.
To access the blocked flue safety switch, re- move the limit switch bracket, with switch and low voltage wires attached. Push the red reset button and then reinstall limit switch bracket.
When first lighting the appliance, it will take a few minutes for the line to purge itself of air. Once purging is complete, the pilot and burner will light and operate as indicated in the in- struction manual.
To provide increased access to the lower con- trol compartment, you may chose to remove the front log. To do so, undo the twists in the wires securing the log from below to each of the grate tines. After removal of the log, cut the wires off closely to log before reinstalling it. These wires are only required for shipping. To place the front log, position it, centered, on the log rack in the cradel area provided.
The appliance should then relight and remain lit. If this does not occur, turn off the appli- ance and call a qualified service technician.


Reset
Limit Switch
Limit Switch Bracket
APPLIANCE OPERATION
Lintel Extension
Bracket Screw

3/8 To 1/2 Inch (9 mm to 13 mm)
No smoke or soot should be present. If sooting conditions exist, the air shutter opening on the main burner can be adjusted. Normally, the more offsets in the vent system, the greater the need for the air shutter to be opened further.
The pilot flame should be steady, not lifting or floating. Flame should be blue in color with traces of orange at the outer edge.
The top ³⁄₈" (9 mm) at the pilot generator (thermopile) should be engulfed in the pilot flame. The flame should project 1" (25 mm) beyond the hood at all three ports (Figure 22 ).
³⁄₈" Min (9 mm)
To adjust the flame, position the air shutter to the nominal setting (Figure 24 ). Allow the burner to operate for at least 30 minutes. Observe the flame continuously. If it appears weak or sooty as previously described, adjust the air shutter open or closed until desired effect is achieved.
Flame Appearance and Sooting
Proper flame appearance is a matter of taste. Generally most people prefer the warm glow of a yellow to orange flame. Appliances operated with air shutter openings that are too large, or with long vertical vent runs, will exhibit flames that are blue and transparent. These weak, blue and transparent flames are termed anemic.
Replace the front log if removed for pilot inspection.
If the air shutter opening is too small sooting may develop. Sooting is indicated by black puffs developing at the tips of very long orange flames. Sooting results in black deposits form- ing on the logs, appliance inside surfaces and on exterior surfaces adjacent to the vent termi- nation. Sooting is caused by incomplete com- bustion in the flames and a lack of combustion air entering the air shutter opening.
To light the burner; turn “ON” the remote wall switch and rotate the gas valve control knob counterclockwise to the “ON” position (“ON” will be to the left hand side of the valve).
Nominal Air Shutter Settings Natural Gas - ¹⁄₁₆" (1.59 mm) Open Propane Gas - ¹⁄₄" (6.35 mm) Open
To light the burner, turn ‘ON’ the optional remote wall switch and turn the gas control switch to the “ON” position. Ensure the ignitor lights the pilot. The pilot flame should engulf the flame rod as shown in Figure 23.
To achieve a warm yellow to orange flame with an orange body that does not soot, the shutter opening must be adjusted between these two extremes.
When satisfied that the appliance operates prop- erly, proceed to finish the installation. Leave the control knob/lever in “ON” position and turn the remote switch “OFF.” Replace the refractory access panel.

0" (0 mm) Clearance to Combustible Side Wall
The following accessory items are available for use in the installation of this appliance.
Max. Projection 12" (305 mm)
Complete finished interior wall. To install the appliance facing flush with the finished wall, position framework to accommodate the thick- ness of the finished wall (Figure 25 ). This figure also indicates vertical installation clear- ances to combustible mantels. Figure 26 also shows an example of a combustible mantel shelf projecting a maximum of 12" (305 mm) from the wall, and which must be installed a minimum distance of 15 ³⁄₄" (400 mm) from the top of the firebox opening.
Outside Air Kits Models FOAK-4 and FOAK-4LD
Outside Air kits are available with duct (FOAK-4) and without duct (FOAK-4LD) for use if outside combustion air is required or desired. If model FOAK-4LD is used it must be used in conjunction with locally purchased, non-combustible Class 1 or Class 0 flexible duct.
Min. to Ceiling
15 ³⁄₄ " Min. (400 mm)
A hearth extension is not required with this appliance. Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation re- quirements.
If you live in a cold climate, seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level.
Outside Combustion Air Kits (with duct) 81L87 FOAK-4 (without duct) 81L88 FOAK-4LD
13 14 15 15³⁄₄
Min. Height of Mantel
8 9 10 11 12
Wall Switch Kit 85L87 FWSK
0 0 1¹⁄₂
1 2 3 4 5 6 7 8 9 10 11 12
Max.Length of Mantels Three mantels are shown (dark gray elongated rectangles)- one, 1¹⁄₂ in. long at a min. of 6 in. above the fireplace opening; the second, 8 in. long at a min. of 12 in. above the fireplace opening; the third, 12 in. long at a min. of 15 ³⁄₄ in. above the fireplace opening;
for any mantels between these three in length, they must be located
within the lighter gray shaded area.

AVERTISSEMENT: CET ÉQUIPEMENT DE CONVERSION SERA INSTALLÉ PAR UNE AGENCE QUALIFIÉE DE SERVICE CONFORMÉMENT AUX INSTRUCTIONS DU FABRICANT ET TOUTES EXIGENCES ET CODES APPLICABLES DE L'AUTORISÉS AVOIR LA JURIDICTION. SI L'INFORMATION DANS CETTE INSTRUCTION N'EST PAS SUIVIE EXACTEMENT, UN FEU, EXPLOSION OU PRODUCTION DE PROTOXYDE DE CARBONE PEUT RÉSULTER LE DOMMAGES CAUSER DE PROPRIÉTÉ, PERTE OU BLESSURE PERSONNELLE DE VIE. L'AGENCE QUALIFIÉE DE SERVICE EST ESPONSABLE DE L'INSTALLATION PROPRE DE CET ÉQUIPMENT. L'INSTALLATION N'EST PAS PROPRE ET COMPLÉTE JUSQU'À L'OPÉRATION DE L'APPAREIL CONVERTI EST CHÉQUE SUIVANT LES CRITÈRES ÉTABLIS DANS LES INSTRUCTIONS DE PROPRIÉTAIRE PROVISIONNÉES AVEC L'ÉQUIPEMENT.
WARNING: THIS CONVERSION KIT SHALL BE IN- STALLED BY A QUALIFIED SERVICE AGENCY IN ACCORDANCE WITH THE MANUFACTURER'S IN- STRUCTIONS AND ALL APPLICABLE CODES AND REQUIREMENTS OF THE AUTHORIZED AGENCY HAV- ING JURISDICTION. IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE, EXPLOSION OR PRODUCTION OF CARBON MONOXIDE MAY RESULT CAUSING PROPERTY DAM- AGE, PERSONAL INJURY OR LOSS OF LIFE. THE INSTALLATION IS NOT PROPER AND COMPLETE UNTIL THE OPERATION OF THE CONVERTED APPLI- ANCE IS CHECKED AS SPECIFIED IN THE OWNER INSTRUCTIONS SUPPLIED WITH THE KIT.
THE CONVERSION SHALL BE CARRIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN1-B149.1 AND .2 INSTALLATION CODE.
Invert the flip cap so that the letters associated with the desired gas type are positioned closest to the valve body. NG is for natural gas and LP is for propane. Tighten the flip cap by turning it clock- wise. Replace the black thread-protecting cap.
LA CONVERSION DEVRA ÊTRE EFFECTUÉE CONFORMÉMENT AUX RECOMMANDATIONS DES AUTORITÉS PROVINCIALES AYANT JURIDICTION ET CONFORMÉMENT AUX EXIGENCES DU CODE D'INSTALLATION CAN1- B149.1 ET.2.
Gas conversion kits are available to adapt your appliance from the use of one type of gas to the use of another. These kits contain all the nec- essary components needed to complete the task including labeling that must be affixed to ensure safe operation.
Kit part numbers are listed below and the follow- ing steps detail the conversion procedure.
Ensure the rubber gasket installed on the back of the replacement pressure regulator is prop- erly positioned and install the new pressure regulator using the new screws supplied with the kit. Tighten screws to 25 In. lb. torque.
Honeywell 75L28 — Natural to Propane 75L27 — Propane to Natural
SIT H2021 — Natural to Propane H2022 — Propane to Natural
75L29 — Natural to Propane 75L26 — Propane to Natural

See Figure 30 and replace the pilot orifice as follows: Remove the ignitor assembly retainer clip, and carefully remove the ignitor assembly. Exercise extreme care to prevent damage to or breakage of the ignitor assembly. Remove the screw securing the pilot assembly to its mounting bracket. Back off the flare nut at the end of the pilot gas line to free the pilot assem- bly from the gas line. Remove the pilot orifice and replace it with the one provided with the conversion kit. Reinstall the pilot assembly by reversing the steps detailed here.
Step 8. Honeywell Electronic Valves - See Figure 31 and the instructions provided with the kit. Remove the slotted cap screw, o-ring, pressure-regulating adjusting screw and spring. Retain all parts for possible later use. Install new components from the kit. Black cap and red spring for propane gas units. Silver cap and stainless steel spring fro natural gas units. Before installing the cap, attach manometer to the manifold side pressure test fitting and adjust screw until pressure reads 3.5 inches water column (0.87 kPa) for natural gas, and 10.0 inches water column (2.49 kPa) for propane gas.
When reinstalling the ignitor assembly, use extreme care to prevent damage and break- age. Do not apply any leverage to the ignitor assembly while restoring the retainer clip to its original position.
Inlet Pressure Test Port
ON
OFF
PSI
Manifold Pressure Test Port
NATURAL GAS
INPUT BTU/HR – 15,000
MANIFOLD PRESSURE – 3.5"
ORIFICE SIZE – #49 (0.073)
PROPANE/LPG
INPUT BTU/HR – 15,000
MANIFOLD PRESSURE – 10"
ORIFICE SIZE – (0.045)





The manufacturer reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information.
Printed in U.S.A. © 2002 by Lennox Hearth Products P/N 700,003M REV. H 05/2004
LHP 1110 West Taft Avenue • Orange, CA 92865