INSTALLATION INSTRUCTIONS

CHDM DEHUMIDIFICATION MODULE

for use with

CH3S1 CH4S1 CH5S1

Bard Heat Pump (CH4S1) — INSTALLATION INSTRUCTIONS diagram (page 1)
Fig. 1

Bard Manufacturing Company, Inc. Bryan, Ohio 43506

Manual2100-506D Supersedes: 2100-506C File: Volume III Tab 17 Date: 12-05-11

Since 1914...Moving ahead just as planned.

Page 2 of the Bard Heat Pump (CH4S1) user manual — INSTALLATION INSTRUCTIONS
Page 2 · click to enlarge
Page 2
Page 2 of the Bard Heat Pump (CH4S1) user manual — INSTALLATION INSTRUCTIONS
Page 3 of the Bard Heat Pump (CH4S1) user manual — FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
Page 3 · click to enlarge
Page 3

Getting Other Information and Publications

These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.

FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:

ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721

National Electrical Code ANSI/NFPA 70

Standard for the Installation ANSI/NFPA 90A of Air Conditioning and Ventilating Systems

ANSI American National Standards Institute 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286

Standard for Warm Air ANSI/NFPA 90B Heating and Air Conditioning Systems

Load Calculation for ACCA Manual J Residential Winter and Summer Air Conditioning

ASHRAE American Society of Heating, Refrigerating,

and Air Conditioning Engineers, Inc. 1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478

Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection

NFPA National Fire Protection Association Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057

Page 4 of the Bard Heat Pump (CH4S1) user manual — WARNING
Page 4 · click to enlarge
Page 4

DESCRIPTION

While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way and are not intended as a step-by-step procedure with which the mechanically inclined owner can install the package. See Page 3 for information on codes and standards.

The CHDM dehumidifier is designed to be used with Bard 3 through 5 ton CH heat pump models. It will be installed in the outdoor section of the CH unit. The dehumidifier incorporates a complete refrigeration system. It will share the high & low voltage control from the CH control panel. The CHDM is for use in CH*S Series units with or without CHERV or CHCRV. The CHDM cannot be used in units equipped with economizers CHEIFM.

The dehumidifier is shipped in one carton and contains the electrical harness, miscellaneous hardware and installation instructions. Where local regulations are at a variance with instructions, installer should adhere to local codes.

SHIPPING DAMAGE

INSTALLATION

If a shipment is damaged or the piece count does not agree with the quantity shown on the freight bill, the buyer/receiver should make note on all copies of the freight company’s delivery receipt of any damages and/ or shortages at the time of delivery. The receiving agent and the freight company’s agent should both sign the delivery receipt and the bill of lading. It is preferred, that both signatures are obtained at the time of delivery. If at all possible at the time of delivery, photograph the noted damages as evidence to support a freight claim.

DEHUMIDIFIER: Unpack the dehumidifier. Set aside the sheet metal duct for now. Facing the outdoor section of the CH model, on the right-hand side, there is a long, narrow access panel. Remove this panel and set aside. (See Page 11, Figure 4.)

Remove the fill plate located in the bottom of this compartment by unscrewing the four screws. Remove the 1½" knockout and clear the insulation hole. Place fill plate back in the unit. With a marker, trace the 1½" hole onto the screen below. Remove the fill plate again and cut out marked hole. Place fill plate back into unit and reattach with four screws.

The damage and/or shortage notation on the delivery receipt does not constitute a claim. It is the recipient’s responsibility to initiate the claim process by requesting an inspection and requesting a claim number from the freight carrier. Save all noted freight bills, bills of lading, delivery receipts, packing sheets and invoices for documentation that will be required to support an itemized claim.

Place the dehumidifier in this opening by placing the wedge end of the cabinet in first and slide all the way back (see Figure 4).

IMPORTANT

For concealed damage you must immediately notify the delivering freight carrier by phone and request an inspection. Many freight carriers will not honor concealed damage claim beyond 48 hours from the time of delivery or if the product has been moved to another location other than the ship to address. Most freight carriers will challenge claims written after a two-week period.

Make sure cabinet insulation does not tear!

WIRING: Remove the knockout in the back of the CH control panel and insert bushing (see Figure 2). Route high and low voltage wires into the CH control panel through the bushing. Connect per Figures 1 & 2. Connect a humidistat (field-supplied) per the low voltage connection diagram in the CH Literature.

GENERAL

The CH Dehumidifier equipment covered in this manual should be installed by trained, experienced service and installation technicians.

WARNING

Open and lock unit disconnect switch before installing this accessory to prevent injury or death due to electrical shock or contact with moving parts. Turn thermostat to OFF.

Page 5 of the Bard Heat Pump (CH4S1) user manual — PRESSURE SERVICE PORTS
Page 5 · click to enlarge
Page 5

DRAIN: Connect a drain trap to the drain fitting under the bottom of the dehumidifier section of the unit. The drain connection is a ¾" female pipe fitting. The use of a trap is required to ensure proper drainage.

HIGH PRESSURE SWITCH AND LOCKOUT SEQUENCE

If the high pressure switch opens, the compressor contactor will de-energize immediately. The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay on break time has expired. If the high pressure switch opens again in the same operating cycle, the unit will go into manual lockout. Recycling the wall humidistat resets the manual lockout.

AIR CHANNEL ASSEMBLY: (See Figure 3.) Remove cover plate in unit and cut out the insulation. On CH3S1 models, the duct extension is to be removed and a new piece of foam (supplied) added to the bottom of the air channel assembly. Slide the air channel assembly into the unit and position the assembly to the left until the angle hits the side of the inner back. Secure the angle with three self-drilling screws. Secure the top with one screw.

LOW PRESSURE SWITCH BYPASS & LOCKOUT SEQUENCE

SEQUENCE OF OPERATION

If the low pressure switch opens for more than 120 seconds, the compressor contactor will de-energize and go into a soft lockout. Regardless the state of the low pressure switch, the contactor will re-energize after the delay on make time delay has expired. If the low pressure switch remains open longer than 120 seconds, the unit will go into manual lockout. Recycling the wall humidistat resets the manual lockout.

Dehumidification – Circuit DH makes at the humidistat pulling in the compressor contactor, starting the compressor and the dehumidifier blower motor. The “G” (indoor motor) is automatically completed on call for dehumidification (Relay #2).

The dehumidifier may operate alone or run simultaneously with the first stage of the CH unit. When the CH unit switches to second stage, the operation of the dehumidifier will be locked out (Relay #1).

The Compressor Control Module is an anti-short cycle/ lockout timer with high and low pressure switch monitoring.

FREEZE STAT OPERATION: The freeze stat operation will open at 32° and de-energize the compressor and fan. The compressor and fan will restart after the coil defrosts and the freeze stat warms to 57°.

On initial power up or any time power is interrupted to the unit, the delay on make period begins, which will be two minutes. When the delay on make is complete and the high pressure and low pressure are closed, the compressor contactor is energized. Upon shutdown, the delay or break timer starts and prevents restart until the delay on break and delay on make have expired.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on the unit, so the system operating pressures can be observed. To gain access to these pressure ports, remove the long narrow panel on the right-hand side of the outdoor section of the CH unit. See Figure 4.

During routine operation of the unit with no power interruption, the compressor will operate on demand with no delay.

Reference the pressure table located on the front lower panel and Table 2 within this manual.

Page 6 of the Bard Heat Pump (CH4S1) user manual — TABLE 1 CH DEHUMIDIFIER PERFORMANCE
Page 6 · click to enlarge
Page 6

TABLE 1 CH DEHUMIDIFIER PERFORMANCE

Dry Bulb Temp FWaterRemovallb./hr(PPD) RelativeHumidity%Rh 50556065707580 651.0(24.0)1.3(31.2)1.5(36.0)1.7(40.8)2.0(48.0)2.2(52.8)2.4(57.6) 701.2(28.8)1.5(36.0)1.8(43.2)2.0(48.0)2.3(55.2)2.6(62.4)2.8(67.2) 751.4(33.6)1.7(40.8)2.0(48.0)2.4(57.6)2.7(64.8)3.0(72.0)3.3(79.2) 801.7(40.8)2.0(46.0)2.4(57.6)2.7(64.8)2.8(67.2)3.4(81.6)3.7(88.8) 852.0(48.0)2.3(55.2)2.8(67.2)3.1(74.4)3.5(84.0)3.9(93.6)4.3(103.2) 902.2(52.8)2.7(64.8)3.1(74.4)3.6(86.4)4.0(96.0)44(105.6)4.8(115.2)

tin u H C e h t o t s n o itid n o c ria n r u t e r e h t e r a H R % d n a F e r u t a r e p m e T blu B y r D :s e t o N

. bl 4 0 . 1 = r e t a w f o tn ip e n O

Page 7 of the Bard Heat Pump (CH4S1) user manual — Capacitor for Compressor/Blower Motor: Part #8552-085, 15/5 MFD 370V
Page 7 · click to enlarge
Page 7

TABLE 2 CHARGING PRESSURE LABEL

SYSTEM REFRIGERANT PRESSURE CHART

Return Air TemperaturePressureRelative Humidity % 50% RH55% RH60% RH65% RH70% RH75% RH80% RH 70° DBLow Side969798100102104106 High Side248253258261265269273 75° DBLow Side110112114116117118120 High Side270276282288294298303 80° DBLow Side115119123127132136140 High Side297306315324333342351 85° DBLow Side120127134141148153158 High Side342349356363370375380

Low Side pressure: ±2° Table is based upon rated CFM (airflow) across the Evaporator Coil. If there is any doubt as to the correct operating charge being in the system, the charge should be removed, system

High Side Pressure:±5°

evacuated, and recharged to serial plate instructions.

Capacitor for Compressor/Blower Motor: Part #8552-085, 15/5 MFD 370V

7961-679

Page 8 of the Bard Heat Pump (CH4S1) user manual — 4056-213
Page 8 · click to enlarge
Page 8

Unit Control Panel

Term. Block

TAPE OFF

G

S

DH

R

R

Y1

T1

T2

HPC

F

H

R

ALR

Y

MINUTES

5 4 3 2

LPC 1

WARNING

! USE COPPER CONDUCTORS ONLY SUITABLE FOR AT LEAST

75° C.

! DANGER

*ELECTRICAL SHOCK HAZARD

*DISCONNECT POWER BEFORE

SERVICING.

Wire Identification numbers for Bard use only. 99

4056-213

Show 50 more labels / short text on this page
Overload · Low Voltage · 16 15 14 · 230/208-60-1 · Low · High · Freeze · Pressure · Pressure Control · Thermo- · stat C · Control · Fan · Red · Motor · Black · Green · Compressor · Red · Red · Black/White · Brown · Black · Red · Purple/White · Ground · Relay #2 · Purple · Contactor · Blk/White · Orange · Yellow · Yellow · Blue Red/White · Blue · Black · Yellow · Yellow · Black · Black · Black/White · Relay #1 4 · Black/White · Yellow · Run · Capacitor · 1 Compressor · Control · Module · Red/White
Page 9 of the Bard Heat Pump (CH4S1) user manual — MIS-2454 C
Page 9 · click to enlarge
Page 9

Run wires to terminal block

Run wires to terminal block

Route green ground wire

for 460 Volt unit control panel to ground lug

for 230 Volt unit control panel

Remove knockout and insert strain relief bushing from opposite side of panel. Run wires into

close.

Insert wires through bushing

Wire Routing Instructions

Low Voltage Wiring Connections

High Voltage Wiring Connections

Orange NOT USED (TAPE OFF)

230 Volt Single Phase Connection

230 Volt 3 Phase Connection

L3 L2 L2

To "L1" To "Y1"

460 Volt 3 Phase Connection

240 Volt Supply From

MIS-2454 C

Show 28 more labels / short text on this page
Control · Panel · bushing and · and attach to · Dehumidifier · low voltage · terminal block · Black/White · To "C" · Red/White · Black · Black · Red · Red · To "R" · To "L2" · To "L3" · Purple · Purple/White · To "L1" · To "DH" · Black · To "L2" · Step Down Transformer · To "L1" · (See Wiring Diagram) · Red · Terminal Block 64
Page 10 of the Bard Heat Pump (CH4S1) user manual — 5(029((;7(16,21)25&+681,7 6((3$*(2),16758&7,210$18$/
Page 10 · click to enlarge
Page 10

6&5(:

326,7,21$1*/( 72/()7$66+2:1

6&5(:6

$,5&+$11(/$66 < '(+80,',),(5$66

5(029((;7(16,21)25&+681,7 6((3$*(2),16758&7,210$18$/

6&5(:6

Show 6 more labels / short text on this page
5(029(3/$7( · 6(/)7$33,1* · '8&7(;7(16,21 · $,5&+$11(/$66 < 0$,13$5772%(86(' · 21$//02'(/6 · 0,6
Page 11 of the Bard Heat Pump (CH4S1) user manual — MIS-2456
Page 11 · click to enlarge
Page 11

Ø1.500 Drain

Drain Tube (must have trap)

MIS-2456

Show 17 more labels / short text on this page
Filter Access · Door · Unit Right Side · Control Panel · Door · Vent Option · Door · Dehumidifier · Dehumidifier · Access Panel · Service · Ports · Hex grille pattern · (under fill plate) · Knockout · Fill Plate · Field Supplied
Page 12 of the Bard Heat Pump (CH4S1) user manual —
Page 12 · click to enlarge
Page 12

CABINET and FUNCTIONAL COMPONENTS

6(;3

Page 13 of the Bard Heat Pump (CH4S1) user manual — CHDM
Page 13 · click to enlarge
Page 13

CABINET and FUNCTIONAL COMPONENTS

CHDM

. o N g n i w a r D . o N tr a P n o it p ir c s e D

1 7 6 2 - 7 0 1 p o T r e s n e d n o C X

2 9 8 2 - 0 0 9 S ylb m e s s A r e w ol B e t elp m o C X

3 1 1 0 - 1 5 4 5 t e m m o r G 3

4 5 1 0 - 2 0 1 8 r o t o M P H 6 / 1 X

5 0 2 1 - 1 5 1 g n is u o H r e w ol B X

6 2 4 3 - 3 1 1 t e k c a r B r e w ol B 3

7 9 9 0 - 2 5 1 5 le e h W r e w ol B X

8 4 4 0 - 0 0 2 8 tn u o M r o t o M X

9 2 0 2 - 9 0 1 k c a B r e ifid i m u h e D X

0 1 8 5 3 - 7 2 1 e s a B r e ifid i m u h e D X

1 1 4 2 4 - 2 5 1 r o o D r e s n e d n o C X

2 1 8 3 0 - 8 0 4 8 t a t S - T tc e t o r P e z e e r F X

3 1 7 1 1 - 3 2 1 ylb m e s s A n a P n ia r D X

4 1 1 3 3 - 1 4 1 tr o p p u S r o s s e r p m o C X

5 1 8 1 2 - 2 1 0 1 tu N e g a C 0 2 - 4 / 1 3

6 1 4 0 3 - 0 0 0 8 r o s s e r p m o C X

7 1 5 2 4 - 3 5 1 r o o D r o t a r o p a v E X

8 1 7 2 4 - 3 5 1 S r o o D r o s s e r p m o C X

9 1 6 0 0 - 1 3 0 6 tr o P e g u a G s s a r B 2

0 2 6 2 4 - 3 5 1 S r o o D le n a P lo rtn o C X

1 2 5 1 0 - 1 0 2 5 r e ir D e n iL d iu q iL X

2 2 le n a P lo rtn o C e e S

tsiL str a P ylb m e s s A le n a P lo rtn o C X

3 2 1 1 1 - 6 0 4 8 h cti w S e r u s s e r P h g i H X

4 2 5 6 0 - 6 0 4 8 h cti w S e r u s s e r P w o L X

5 2 X B 4 3 1 - 0 6 0 5 lio C r o t a r o p a v E X

6 2 X B 9 4 1 - 1 5 0 5 lio C r e s n e d n o C X

Page 14 of the Bard Heat Pump (CH4S1) user manual — CHDM
Page 14 · click to enlarge
Page 14

CABINET and FUNCTIONAL COMPONENTS

CHDM

. o N g n i w a r D . o N tr a P n o it p ir c s e D

1 2 6 0 - 1 0 2 8 y ale R 2

2 7 1 0 - 1 1 6 8 g n ih s u B p a n S X

3 1 4 2 - 5 3 1 n o ititr a P le n a P lo rtn o C X

4 8 8 0 - 1 0 2 8 elu d o M lo rtn o C r o s s e r p m o C X

5 5 7 2 - 7 1 1 S le n a P lo rtn o C X

6 7 0 0 - 0 5 5 8 t e k c a r B r o tic a p a C X

7 5 8 0 - 2 5 5 8 r o tic a p a C X

8 6 0 0 - 1 1 6 8 la n i m r e T d n u o r G X

9 8 6 0 - 1 1 6 8 g n ih s u B f e ile R n ia rt S 2

0 1 6 0 0 - 1 0 4 8 r o tc a tn o C X

Show 11 more labels / short text on this page
· · · · · · · · · · 6(;3

Ask about the Bard Heat Pump (CH4S1)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Bard Heat Pump (CH4S1)

Be the first to ask — other owners or our team will answer.

Original document

Bard Heat Pump (CH4S1) manual PDF

14 pages·522 KB·Dehumidifier·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…