Instruction/ maintenance manual of the product SCC4-38 Sterling Plumbing
Go to page of 61
SCC4-38 Conveying Systems 4-Pump 38-Station Controllers Operation, Installation, and Service Manual Sterling 5200 W. Clinton Ave. Milwaukee, WI 53223 Tel.
Page 2 of 60 Write down your unit serial number(s) Model # Serial # here for future reference ___ _____________ ________________ ________________ ________________ ________________ ________________ ________________ ________________ Performance figures stated in this manual are based on a standard atmosphere of 59°F (15°C) at 29.
Please note that our address and phone information has changed. Please reference this page for updat ed contact information. These manuals are obsolet e and are provided only for their technical information , data and capacities.
Page 3 of 60 Table of Contents 1 General Information .......................................................................... 9 1-1 Equipment Function...................................................................................... 9 1-2 Necessary Documents .
Page 4 of 60 5-2-2 Setting Up Stations ......................................................................... 24 5-2-2-1 Setting Up a Single Station ....................................................... 25 5-2-3 Setting Up Pumps .................
Page 5 of 60 11-3 Warranty ..................................................................................................... 56 12 Safety Tag Information ................................................................... 57 12-1 Controller Safety Tags .
Page 6 of 60 Charts and Figures 1 SCC4/38 Controller with 6" Display ................................................................... 11 2 6” Default “Station Status” Screen Before Setup ............................................. 22 3 6” “System Setup” Screen Before Setup .
Page 7 of 60 Safety Considerations Sterling SCC conveying systems are designed to provide safe and reliable operation when installed and operated within design specifications, following national and local safety codes.
Page 8 of 60 Sterling “SCC4-38” Conveying Systems 4-Pump 38-Station Controller This controller is manufactured by Sterling, Inc. at the ACS-Wood Dale facility: ACS, Inc.
Page 9 of 60 1 General Information 1-1 Equipment Function Sterling conveying systems create vacuum for conveying pelletized or granular material in a central material handling system. A typical use is an in-plant distribution system for plastic processing plants.
Page 10 of 60 Use the minimum effective amount of vinyl flex hose to maximize material line efficiency. Keep material lines as straight as possible. Refer to the Sterling SPD/SPC Product Manual (Sterling Part No. A0571050) for installation recommendations.
Page 11 of 60 Figure 1: SCC4/38 Controller with 6" Display 24 ” 30 ” 6 ” * De p th dimension is 10”.
Page 12 of 60 2 Safety 2-1 W ork Rules The installation, operation, and maintenance of this equipment must be conducted in accordance with all appli- cable work and safety codes for the installation location. This may include, but is not limited to OSHA, NEC, CSA, SPI, and any other local, national, and international regulations.
Page 13 of 60 DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. This word will be limited to the most serious situations. The term IMPORTANT emphasizes areas where equipment damage could result, or provi des additional information to make a step or procedure easier to understand.
Page 14 of 60 Hold daily equipment inspections in addition to regular maintenance checks. You will keep your equipment safe for production and exhibit your commitment to safety. Please read and use this ma nual as a guide to equipment safety. This manual contains safety warnings throughout, specific to each function and point of operation.
Page 15 of 60 2-7 Safety Devices This section includes information on safety devices and procedures that are inherent to the SCC4/38 Controller. This manual is not intended to supersede or alter safety standards established by the us er of this equipment.
Page 16 of 60 guarding a motor, and the safety switch fails, the motor should not be able to run. 2-7-3 Safety Device Lock-Outs Some safety devices disconnect electrical energy from a circuit. The safety devices that are used in the SCC4-38 Controller are primarily concerned with electrical power disconnection.
Page 17 of 60 3 Shipping Information 3-1 Unp acking and Inspection You should inspect your Sterling SCC4-38 controller for any possible shipping damage. If the container and packing materials are in re-usable condition, save them for reshipment if necessary.
Page 18 of 60 Hold the damaged goods with the container and packing materials for possible inspection by postal authorities. 3-4 United Parcel Service Shipment ; Contact your local UPS office regarding damage and insurance claims. ; Retain the container and packing.
Page 19 of 60 4 Installation 4-1 Inst alling the Sterling Control Panel Note: Before you mount the panel, consider how you run wiring to the vacuum hoppers, the filter chamber atmospheric valve (if so equipped) and the pump motor starter(s), vacuum switch(es), and vent valve(s).
Page 20 of 60 3. Make sure that the solenoid and the proximity switch (if supplied) on vacuum hoppers are the same voltage (24 VDC) as the SCC control panel voltage.
Page 21 of 60 5 Using the Standard 6” Touch Screen 5-1 Introduction This chapter gives the procedures for configuring your SCC 4-38 controller. Configuration of your SCC4-38 controller includes setting the number of stations and pumps, setting variables such as convey time and blow-back interval, and setting up passwords.
Page 22 of 60 Figure 2: 6” Default “Station Status” Screen Before Setup 1. At the “Station Status” screen (Figure 2) or at the “Pump Status” screen, touch the SYSTEM SETUP button. The “Menu” screen opens. Figure 3: 6” “System Setup” Screen Before Setup 2.
Page 23 of 60 4. Touch PUMPS ACTIVE . A keypad pops up. 5. Enter the total number of pumps (1-4) to be controlled by the system. Use CLR to erase any mistakes. Use ENT to enter the value. The keypad disappears, and the new setting appears under PUMPS ACTIVE .
Page 24 of 60 mistakes. Use ENT to enter the value. The keypad disappears and the new setting appears under STROBE SUPPRESS . 4. On the “System Setup” screen (Figure 4), touch the HORN SILENCE button. A keypad pops up. 5. Enter the number of minutes (between 0 and 99) that you want the horn to stay off.
Page 25 of 60 5-2-2-1 Setting Up a Single Station 1. Go to the “Station Status” screen if needed. To reach this screen press station status button on any screen. Figure 5: 6” “Station Status” Screen 2. On the “Station Status” screen (Figure 5), touch the icon for the station you want to setup, and hold it for several seconds.
Page 26 of 60 Figure 6: 6” “Station Operator” Screen Before Setup 3. On the “Station Operator” screen (Figure 6), touch the STATION SETUP button. The “Station Setup” screen opens. Figure 7: 6” “Station Setup” Screen 4. On the “Station Setup” screen (Figure 7), adjust settings as required.
Page 27 of 60 Touching RESET TO DEFAULTS in the lower right of the screen changes all the settings for this station back to their factory defaults. See pp.
Page 28 of 60 Figure 9: 6” Pump Setup Screen Before Setup 3. Adjust settings as required. Touching any box that appears in red (for “disabled”) toggles it to green (for “enabled”), and vice versa. Touching any box that appears in white gives you a keypad to enter a new value.
Page 29 of 60 5-2-4 Finishing Setup: Setting Up Passwords You can set up passwords for two levels of security: for operators and for setup personnel. The controller comes from the factory with neither password set. This allows every user access to all functions.
Page 30 of 60 Note: If you want to protect the operator’s functions with a password, you must also define a setup password. If you leave the setup password undefined, then all users will have access to all functions. If you want two different levels of password protection, you must make the passwords diffe rent from each other.
Page 31 of 60 To change the duration of the password, complete the following steps: 1. On the “System Setup” screen (Figure 4), touch the Operator Password Duration button or the Setup Password Duration button, depending on which password duration you want to change.
Page 32 of 60 5-3 General Operation 5-3-1 Overview Your SCC4-38 controller electrically controls valves and solenoids to convey material from a central location to individual stations as ne eded. The controller senses demands for material at the stations and responds to the demands in a timely fashion.
Page 33 of 60 Figure 10: 6” “Station Status” Screen During Operation The status of each station is color-coded. You can see an explanation of each status by using the online help. To do so from this screen, complete the following steps: 1. Touch HELP .
Page 34 of 60 Additional basic information about each station (convey time, dump delay, and pump assignment) is available at the “Station Operator” screen. See page 38 for details. Detailed configuration settings for each station are available at the “Station Setup” screen.
Page 35 of 60 The following table explains the status represented by each color at the Station Status screen. Color Label Description Gray outline Offline Pump is not enabled. The controller ignores any alarms. Green Ready Pump is off, waiting for demand from a station.
Page 36 of 60 Figure 12: 6” “Password Entry” Screen Enter the four-digit password (including any leading zeros). For example, if the password is 1, enter 0001 . Each digit appears as an “ * ” as you touch it. When you touch the fourth digit, the controller carries out your request.
Page 37 of 60 Note: For a station to be available for the system, it must be enabled at the controller’s screen and its bypass switch must be in the “Convey” position. To enable or disable a station (or pump), complete the following steps: 1. Go to the “Station Stat us” (or “Pump Status”) screen, if needed.
Page 38 of 60 5-3-2-6 Reviewing and Adjusting Basic Station Settings The Sterling controller has a “Station Operator” screen for each station, as shown below. This screen enables you to review and adjust all basic settings for the station. To reach the “Station Operator” screen, complete the following steps: 1.
Page 39 of 60 5-3-2-7 Navigating among the “Station Operator” Screens The controls at the top of the screen enable you to move among the “Station Operator” screens: • To display the screen for the next lower-numbered station (for example, to move from the screen for Station 15 to the screen for Station 14), touch PREVIOUS .
Page 40 of 60 To adjust a station’s convey time (or the unload time), complete the following steps: 1. Go to the “Station Operator” screen by touching and holding a station icon, or go to the “Station Setup” screen. 2. Touch CONVEY TIME . A keypad pops up.
Page 41 of 60 controller finishes the current convey, if any, and resumes normal operation. 5-3-3 Advanced Tasks This section describes the procedures carried out during operation that are normally reserved for setup personnel. These procedures require use of the setup password (if your facility has defined one).
Page 42 of 60 5-3-3-2 Transferring Stations to a Standby Pump If a pump fails, you can transfer all of the controller’s station assignments for that pump to a standby pump. To do this, you must disable (take offline) both the source pump and the standby pump, and the standby pump must have no stations already assigned to it.
Page 43 of 60 Figure 15: 6” “Transfer To Standby Pump” Screen 6. Use CLR to erase any mistakes. Use ENT to enter the value. Figure 16: 6” Transfer To Standby Pump Button Note: When you enter the second pump number, the controller checks to make sure that both pumps are offline and that the standby pump has no stations assigned to it.
Page 44 of 60 system begins using the pump. In addition, all “Station Operator” and “Station Setup” screens show the new pump assignment. Standby Pump Errors If the error message tells you to disable the source pump and/or the standby pump, touch RETURN at this screen, then PUMP STATUS at the “Pump Setup” screen.
Page 45 of 60 5-3-4 Alarms 5-3-4-1 Reviewing Alarms To review your system’s alarms, touch Alarms on any screen. The “Alarm Log” screen appears, with the newest alarm listed first. Figure 17: 6” Alarm Log Screen To scroll up and down through the list, touch DOWN or UP at the top of the screen.
Page 46 of 60 6 Maintenance No Periodic maintenance is required on this unit..
Page 47 of 60 7 Configurable Settings This section describes the proper setup of the SCC4-38 control system parameters. These parameters are operator changeable; however, these items should require setup only during the initial installation. Only authorized personnel should change them.
Page 48 of 60 Name Description Options Default Assigned to pump n Number (address) of the pump to which this station’s vacuum line is connected. 0–4 (0 = not assigned) 0 Special convey When this o.
Page 49 of 60 7-2 Options for Pump Setup Several of the items in this screen are not setup options but are instead intended for use du ring operation. These items (hour meter and transferring stations to a standby pump) are described in Chapter 5, which cover operation procedures.
Page 50 of 60 8 Troubleshooting 8-1 General T roubleshooting Problem Possible Cause Solution The control panel is not turned on. Turn on the control panel. Fuse/circuit breaker in the power drop is blown/tripped. Replace/reset. The control panel doesn’t light up at all Control power switch is broken.
Page 51 of 60 8-2 Alarms The format for all station alarms is “Station n [alarm text],” for example, “Station 12 receiver low level.” The format for all pump alarms is “Pump n [alarm text].” Any alarm that does not start with “Station” or “Pump” is a system alarm.
Page 52 of 60 9 Options The following is a list of options that your controller may be equipped with: 230/1/50 Operation Required to operate with a 230/1/50 supply voltage. Audible/visual alarm Alarm light and horn assembly that can be remote mounted and wired into the controller to indicate an alarm condition.
Page 53 of 60 10 Spare Parts List 10-1 Recommended S p are Part s List Quantity Sterling Part Number Description 1 A0569874 AB 20A Power Supply, 24VDC, #1606-XL480EP 1 A0569870 Relay Magnecraft #781XAXML 1 A0569859 Filter/Grill 1 A0540997 Fuse, MDL –1 1 A0542210 Fuse, MDL – 5 1 A0544793 Fuse, MDL – 15 5 A0542205 Fuse, MDL – 2.
Page 54 of 60 11 Technical Assistance 11-1 Cont act Information for T echnical Assist ance Parts Department Call toll-free 7am–5pm CST [ 800 ] 423-3183 or call [414] 354-0970, Fax [414] 354-6421 The.
Page 55 of 60 11-2 Returned Material Policy 11-2-1 Credit Returns 1. Prior to the return of any material, authorization must be given by Sterling. A RMS number will be assigned for the equipment to be returned. 2. Reason for requesting the return must be given.
Page 56 of 60 11-3 W arranty Sterling. warrants all equipment m anufactured by it to be free from defects in workmanship and material when used under recommended conditions.
Page 57 of 60 12 Safety Tag Information 12-1 Controller Safety T ags 12-2 Controller Identification (Serial Number) T ag (Located on the side of the controller box) 5200 W. Clinton Ave. Milwaukee, WI 53223 Tel. (414) 354-0970 Fax (414) 354-6421 SCC CONTROL PANEL Model No.
Page 58 of 60 13 Appendix Review electrical drawings supplied in the packet with the manual..
Sterling warrants all equipment manufactured by it to be free from defects in workmanship and material when used under recommended conditions. The Company’ s obligation is limited to repair or repla.
Auxiliary Equipment for the Process Industries PO Box 245018 5200 West Clinton Avenue • Milwaukee, WI 53224-9518 (414) 354-0970 • Fax (414) 354-6421 Scrap Process Heating/ Automated Material Recov.
An important point after buying a device Sterling Plumbing SCC4-38 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Sterling Plumbing SCC4-38 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Sterling Plumbing SCC4-38 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Sterling Plumbing SCC4-38 you will learn all the available features of the product, as well as information on its operation. The information that you get Sterling Plumbing SCC4-38 will certainly help you make a decision on the purchase.
If you already are a holder of Sterling Plumbing SCC4-38, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Sterling Plumbing SCC4-38.
However, one of the most important roles played by the user manual is to help in solving problems with Sterling Plumbing SCC4-38. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Sterling Plumbing SCC4-38 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center