RWF40... complete with housing
The RWF40... is a universal digital boiler temperature / pressure controller with functions designed specifically for the control of heat generating plant. The RWF40... and this Data Sheet are intended for use by OEMs which integrate the controller in their products!
The controller is supplied complete with housing for flush panel mounting. The RWF40... is matched to the controlled variable and the required setpoint range by mak- ing parameter settings. The control parameters can be set and optimized while the burner is running. All settings are made with 4 buttons located on the unit front and are directly displayed. LEDs on the front indicate the following operating states:
- Control ON / OFF
- Positioning pulses ON or OFF for driving the burner´s air damper when using modulating burner control, or stage I / stage II when using 2-stage burner control
- «2-stage» operating mode
- Position of the configurable contact «K6»
- Manual control ON / OFF During operation, the digital display above the LEDs shows the setpoint (green), the actual value (red) and – when making parameter settings – the relevant parameters.
HVAC Products

89 / 336 EEC NE21, EN 50 081 part 1 and EN 50 082 part 2
Conformity to EEC directives - Electromagnetic compatibility EMC (immunity) - Electromagnetic compatibility EMC NAMUR recommentation
The unit contains electrical and electronic components and must not be disposed of together with household waste. Local and currently valid legislation must be observed.
2/10

Controller with RWF40.000A97 - 3-position output - housing - fixing material and seal Controller with RWF40.001A97 - 3-position output - analog output - housing - fixing material and seal Controller with RWF40.002B97 - 3-position output - analog output - RS-485 port - housing - fixing material and seal Packaging variants (20 pieces, without documentation) RWF40.010A97 RWF40.011A97
Adapter frame for replacing the RWF32... ARG40
Bracket ARG41 For mounting the RWF40... on 35 mm DIN rails to DIN 46277
Dummy cover AVA10.200/109 For covering a panel cutout for the RWF40...

Accessories · 3/10

Mains voltage AC 110...240 V +10 % / -10 % Mains frequency 48...63 Hz Safety class II to DIN 0631 Mounting position optional Terminals for 2 x 1.5 mm² or 1 x 2.5 mm² Power consumption max. 10 VA Safety extra low-voltage DC 24 V Contact rating of the control outputs
2 A / AC 24...240 V 0.1 A / AC 24...240 V Weight complete with housing approx. 760 g Recommended actuator running time 15...60 s Degree of protection of housing
(relays «K1...K3») - Up to 2 x 105 switching cycles - Up to 107 switching cycles
IP 65, EN 60529 IP 20, EN 60529 Storage DIN EN 60 721-3-1 Temperature range -20...+60 °C Humidity < 75 % r.h. Transport Temperature range -40...+70 °C Humidity < 75 % r.h. Operation Temperature range -20...+50 °C Humidity < 75 % r.h. Condensation, formation of ice and ingress of water are not permitted!
- Front - Base
General controller data · Environmental conditions · 4/10

The RWF40... provides the following functions: - One digital PID controller with a 3-position or analog output (optional)
- To control 2-stage burners, the RWF40... can be switched over to provide 2- position control - Automatic thermostat (or pressurestat) function in low-fire operation
- One shift controller for weather-dependent setpoint shifting
- One minimum limiter and one maximum limiter for the boiler temperature or the boiler pressure - One limit thermostat to DIN 3440 (output 1)
- One potential-free configurable contact
- Manual operating mode
- Communication via serial port (option)
Power supply measuring transducer
DC 24 V, 30 mA (short-circuit proof)
RS-485 MOD bus protocol AC 110 ...240 V +10%/-10%, 48...63 Hz, max. 10 VA

In low-fire operation, the RWF40... operates like a control thermostat or pressurestat. This means that it operates as a 2-position controller maintaining the required setpoint by switching the burner on and off. The switching differential for 2-position operation can be adjusted within a wide range. If the demand for heat increases, the controller switches to high-fire operation only when an adjustable limit is exceeded. This function is aimed at optimizing the burner´s switching ratio. In that case, the RWF40... operates as a 2-position controller with adjustable switching thresholds. Using the relays of the 3-position output, the RWF40... drives the actuator to the 1st and 2nd output stage. In this operating mode, the optional analog output switches between the minimum signal for the 1st stage and the maximum output signal for the 2nd stage.
High-fire operation, 2-stage control
In that case, the RWF40... operates as a PID / PI controller with a 3-position output without position feedback signals or, optionally, with a modulating output. By making use of its self-setting facility, the RWF40... is able to determine the PID / PI control parameters, or the parameters can be set manually.
High-fire operation, modulating control
Using a potential-free contact, the RWF40... can be switched from the modulating mode to 2-stage operation.
Binary input 1 (change- over of operating mode)
In the case «setpoint shifting» is configured, the current setpoint is shifted by an adjust- able amount. Configuration of «setpoint changeover» provides changeover between 2 setpoints adjusted on the RWF40... If analog input 2 is configured for an «external set- point», changeover is provided between the setpoint adjusted on the RWF40... and an external setpoint.
Binary input 2 (setpoint shifting or setpoint changeover)
Potential-free contact «K6» can be assigned a number of functions. Example: Limit value supervision
4 buttons on the unit front are used to operate and program the RWF40... During op- eration and programming, the 7-segment displays show the parameter values and pa- rameter names.
The controller´s standard configuration ex works is such that when connecting a QAC22… outside sensor, automatic changeover to weather-dependent setpoint shifting takes place. The signal delivered by the QAC2... outside sensor must not be fed parallel to sev- eral RWF40...!

Function of the controller when used for burner control (cont´d)
To acquire the actual value, a number of sensors can be connected to the RWF40...
Analog input 1 (actual value sensor)

¹) Only RWF40.0X2B97 The power provided for the measuring transducers is DC 24 V / 30 mA. Feeding a signal to analog input 2, the controller´s setpoint can be influenced. The influence can be scaled. The following signals can be used: - Input signals DC 0...1 V, DC 0...10 V, 0...20 mA, 4...20 mA - 1 kΩ potentiometer in a 2-wire circuit
Analog input 2 (external setpoint shift or external setpoint)
7/10

Temperature and pressure control on a dual-fuel burner. Burner control and supervision are provided by burner control type LAL... or LFL... DC 24 V at terminals «G+» and «G-» is used for powering the QBE... pressure sensor!

L N G1+ M1B9 M9 XB6 M6 Q14 Y1 Y2 D1 Q

L N G+ M1 XU6 M6 Q14 Y1 Y2 D1 Q
a Limit switch for air damper position OPEN QAE... Immersion temperature sensor
BS Operation selector QBE... Pressure sensor
1 = firing on gas RV Gas control damper
(modulating burner control) S1 Internal / external setpoint switch (E)
2 = firing on oil SQ... Actuator of burner´s air damper and gas
(2-stage burner control) control damper
BV... Fuel valve ST Connections for burner control´s start
BSG... Remote setpoint adjuster (active when control loop
«S1» is closed) v Auxiliary switch for the release of the
L... Burner control 2nd fuel valve depending on the air damper
LK Burner´s air damper position
m (MIN) Auxiliary switch for controlling low-fire z End switch for the fully CLOSED
operation position of the air damper
QAC... Outside sensor for weather-dependent





© 2005 Siemens Building Technologies Production GmbH Subject to change!