Industrial Ethernet OSM/ESM
Introduction 1
Functions 2
Operating Instructions
Network Topologies with OSM/ESM
Interfaces, Displays and Operator Controls
Installation, Commissioning 5
Firmware Update 6
Technical Specifications 7
Standards and Approvals 8
Glossary 9
References 10
Index 11
Release 05/2003
C79000-Z8976-C068-10

This document contains notices which you should observe to ensure your own personal safety, as well as to protect the product and connected equipment. These notices are highlighted in the manual by a warning triangle and are marked as follows according to the level of danger:
! Danger indicates that death or severe personal injury will result if proper precautions are not taken.
! Warning indicates that death or severe personal injury can result if proper precautions are not taken.
! Caution with warning triangle indicates that minor personal injury can result if proper precautions are not taken.
Copyright Siemens AG 2000/02, All rights reserved The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility or design, are reserved.
Disclaimer We have checked the contents of this manual for agreement with the hardware and software described. Since deviations cannot be precluded entirely, we cannot guarantee full agreement. However, the data in this manual are reviewed regularly and any necessary corrections included in subsequent editions. Suggestions for improvement are welcome.
Siemens AG Automation and Drives Postfach 48 48, D-90327 Nuernberg
C79000-Z8976-C068-10 © Siemens AG 2001/2003 Technical data subject to change.
Siemens Aktiengesellschaft Printed in the Federal Republic of Germany

SIMATIC, SIMATIC NET, SINEC and SIMATIC NET Networking for Industry® are registered trademarks of Siemens AG.
Third parties using for their own purposes any other names in this document which refer to trademarks might infringe upon the rights of the trademark owners.
Before you use the product described here, read the safety instructions below thoroughly.
Only qualified personnel should be allowed to install and work on this equipment . Qualified persons are defined as persons who are authorized to commission, to ground, and to tag circuits, equipment, and systems in accordance with established safety practices and standards.
Please note the following regarding the correct usage of hardware products:
Caution This device and its components may only be used for the applications described in the catalog or the technical description, and only in connection with devices or components from other manufacturers which have been approved or recommended by Siemens. This product can only function correctly and safely if it is transported, stored, set up, and installed correctly, and operated and maintained as recommended. Before you use the supplied sample programs or programs you have written yourself, make certain that no injury to persons nor damage to equipment can result in your plant or process. EU Directive: Do not start up until you have established that the machine on which you intend to run this component complies with the directive 89/392/EEC.

Please note the following regarding the correct usage of software products:
Caution This software may only be used for the applications described in the catalog or the technical description, and only in connection with devices or software products from other manufacturers which have been approved or recommended by Siemens. Before you use the supplied sample programs or programs you have written yourself, make certain that no injury to persons nor damage to equipment can result in your plant or process.
Before putting the product into operation, note the following warning:
Copyright Siemens AG 2000/02, All rights reserved The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility or design, are reserved.
Disclaimer We have checked the contents of this manual for agreement with the hardware and software described. Since deviations cannot be precluded entirely, we cannot guarantee full agreement. However, the data in this manual are reviewed regularly and any necessary corrections included in subsequent editions. Suggestions for improvement are welcome.
Siemens AG Automation and Drives Postfach 48 48, D-90327 Nuernberg
C79000-Z8976-C068-10 © Siemens AG 2001/2003 Technical data subject to change.
Siemens Aktiengesellschaft Printed in the Federal Republic of Germany

These Operating Instructions provide you with support during configuration, commissioning, and troubleshooting of networks with Industrial Ethernet OSMs (Optical Switch Module) and Industrial Ethernet ESMs (Electrical Switch Module).
The OSM/ESM includes the following components:
Preface

These operating instructions are valid for the following devices:
The OSM/ESM Network Management manual /1/ describes how to operate the OSM/ESM with network management.
The "SIMATIC NET Industrial Twisted Pair and Fiber Optic Networks" manual /2/ contains further information if you want to connect the OSM/ESM to other SIMATIC NET network components (for example OLM, ELM) or if you want to connect entire network segments to an OSM/ESM.
The "Triaxial Networks for Industrial Ethernet" manual /3/ contains instructions on creating triaxial networks that you can connect via an ELM to an OSM/ESM.
To help you to find the information you require more quickly, the manual includes not only the table of contents but also the following sections in the Appendix:
Preface

To help you to find specific information quickly, these operating instructions include the following parts:
These Operating Instructions are intended for staff involved in configuration, commissioning, and troubleshooting networks with Industrial Ethernet OSMs (Optical Switch Module) and Industrial Ethernet ESMs (Electrical Switch Module).
Only qualified personnel should be allowed to install and work on this equipment. Qualified personnel as referred to in the operating instructions or in the warning notes are defined as persons who are familiar with the installation, assembly, startup and operation of this product and who possess the relevant qualifications for their work, e.g.:
The OSM /ESM meets the requirements for the CE mark. You will find detailed information on the existing approvals and certifications in the Appendix in this manual.
Preface


The switching technology of the Industrial Ethernet OSM Version 2/ESM (Optical/Electrical Switching Module) allows the structuring of Ethernet networks with large spans and large numbers of nodes. It simplifies network configuration and network expansions. The OSM Version 2/ESM are simply called OSM/ESM in the rest of this manual.
The OSMs have both electrical ports and additional FO ports via which several of these devices can be interconnected to form an optical bus or ring configuration. ESMs only have electrical ports.
DTEs, other OSMs/ESMs or complete network segments operating at 10 or 100 Mbps can be connected to the electrical autonegotiation (autosensing) ports of the OSM/ESM. The transmission rate is detected automatically.
To increase availability, ring configurations can be created with OSMs or ESMs. To do this, OSMs or ESMs are first connected together to form a bus using their ring ports. The ends of the bus are closed to form a ring by an OSM or ESM operating in the Redundancy Manager mode (RM mode).
The OSM or ESM operating in the RM mode monitors the attached bus and allows a connection through it if it detects an interruption on the attached bus; in other words, it reestablishes a function bus. Reconfiguration is completed within 0.3s. An OSM/ESM is switched over to the RM mode using a DIP switch on the device.
The redundant standby coupling allows the redundant coupling of OSM/ESM or OLM rings. To do this, two OSM/ESMs (one operating in standby mode) are connected via their standby-sync ports.
With the ITP variants of the OSM/ESM, the DTEs are connected using sub-D female connectors. This connector technology allows direct links over distances up to 100 m. With the TP variants, the DTEs are connected using RJ-45 jacks.
The Version 2 OSMs are compatible with the previous OSM variants (6GK 1105- 0AA00) and ORM (6GK1105-1AA00) and can, for example, be mixed with these in an optical ring.
This manual describes the functions of the OSM/ESM available without using network management. The OSM/ESM Network Management user manual /1/ describes the additional options available if you use network management. You will find this manual on the CD accompanying every OSM/ESM or you can download the manual from the Web in Siemens Customer Support under entry number 8677203: http://www4.ad.siemens.de/view/cs/de/8677203
Introduction

Possible Attachments
The OSM ITP62 allows attachment of up to 6 DTEs or network segments using the ITP connector. By coupling an OSM via ports 7 and 8 it is possible to create optical bus and ring structures. The OSM TP62 can be coupled with other OSM TP62, OSM TP22, OSM ITP53, OSM ITP62, and OSM BC08 modules via the optical ports.
The OSM ITP62 also has eight digital inputs. The states of the inputs are available in a management information base (MIB) and can be read using an SNMP get request. Depending on the configuration of the device, changes at these inputs can also trigger the sending of E-mails, SNMP traps and/or entries in the log of the OSM. The use of these functions is described in the OSM/ESM Network Management User Manual /1/.



Introduction

Introduction

Possible Attachments
The OSM ITP62-LD allows attachment of up to six DTEs or network segments using the ITP connector. By coupling an other OSM ITP62-LD modules via ports 7 and 8 it is possible to create optical bus and ring structures.
The OSM ITP62-LD also has eight digital inputs. The states of the inputs are available in a management information base (MIB) and can be read using an SNMP get request. Depending on the configuration of the device, changes at these inputs can also trigger the sending of E-mails, SNMP traps and/or entries in the log of the OSM. The use of these functions is described in the OSM/ESM Network Management User Manual /1/.








Introduction

Properties of the OSM ITP62-LD
Electrical ports 6 x 10/100 Mbps autonegotiation/autocrossover ports
ITP connectors (sub-D 9-pin female)
Optical ports 2 x 100 Mbps FO ports (full duplex)
Maximum distance between two OSMs 26 km (monomode fiber)
Maximum ring span with 50 OSM ITP62-LD
Digital Inputs 8 x DC 24V
Introduction · BFOC female connectors · 1300 km

Possible Attachments
The OSM ITP53 allows attachment of up to five DTEs or network segments using the ITP connector. By coupling an OSM via ports 7 and 8 it is possible to create optical bus and ring structures. The OSM TP53 can be coupled with other OSM TP53, OSM TP62, OSM ITP22, OSM ITP62, and OSM BC08 modules via the optical ports.
The additional FO port of the OSM ITP53 (port 1) also allows redundant coupling of rings via fiber-optic cable (see Section 3.3).
The OSM ITP53 also has eight digital inputs. The states of the inputs are available in a management information base (MIB) and can be read using an SNMP get request. Depending on the configuration of the device, changes at these inputs can also trigger the sending of E-mails, SNMP traps and/or entries in the log of the OSM. The use of these functions is described in the OSM/ESM Network Management User Manual /1/.


Introduction

Properties of the OSM ITP53
Electrical ports 5 x 10/100 Mbps autonegotiation/autocrossover ports
ITP connectors (sub-D 9-pin female)
Optical ports 3 x 100 Mbps FO ports (full duplex)
Maximum distance between two OSMs 3000 m
Maximum ring span with 50 OSMs 150 km
Digital Inputs 8 x DC 24V
Introduction · BFOC female connectors

Possible Attachments
The ESM ITP80 allows attachment of up to eight DTEs or network segments with ITP connectors (sub-D9 female). By coupling further ESMs to ports 7 and 8 it is possible to create optical bus and ring structures.
The ESM ITP80 also has eight digital inputs. The states of the inputs are available in a management information base (MIB) and can be read using an SNMP get request. Depending on the configuration of the device, changes at these inputs can also trigger the sending of E-mails, SNMP traps and/or entries in the log of the ESM. The use of these functions is described in the OSM/ESM Network Management User Manual /1/.


Introduction

Properties of the ESM ITP80
Electrical ports 8 x 10/100 Mbps autonegotiation/autocrossover ports
ITP connectors (sub-D 9-pin female)
Maximum distance between two ESMs 100 m
Maximum ring span with 50 ESMs 5 km
Digital Inputs 8 x DC 24V
Introduction

Possible Attachments
The OSM TP62 allows attachment of up to 6 DTEs or network segments with TP connectors. By coupling an OSM via ports 7 and 8 it is possible to create optical bus and ring structures. The OSM TP62 can be linked with other OSM TP62, OSM TP22, OSM ITP53, OSM ITP62, and OSM BC08 modules via the optical ports.
The OSM TP62 also has eight digital inputs. The states of the inputs are available in a management information base (MIB) and can be read using an SNMP get request. Depending on the configuration of the device, changes at these inputs can also trigger the sending of E-mails, SNMP traps and/or entries in the log of the OSM. The use of this function is described in the OSM/ESM Network Management User Manual /1/.



Introduction

Properties of the OSM TP62
Electrical ports 6 x 10/100 Mbps autonegotiation/autocrossover ports
TP connectors (RJ-45 jacks)
Optical ports 2 x 100 Mbps FO ports (full duplex)
Maximum distance between two ESMs 3000 m (multimode graded-index fiber)
Maximum ring span with 50 OSMs 150 km
Digital Inputs 8 x 24 V dc
Introduction · BFOC sockets

Possible Attachments
The ESM TP80 allows attachment of up to 8 DTEs or network segments with TP connectors (RJ-45 jack). By linking further ESMs to ports 7 and 8 of the ESM TP80 it is possible to create bus and ring structures.
The ESM TP80 also has eight digital inputs. The states of the inputs are available in a management information base (MIB) and can be read using an SNMP get request. Depending on the configuration of the device, changes at these inputs can also trigger the sending of E-mails, SNMP traps and/or entries in the log of the ESM. The use of this function is described in the OSM/ESM Network Management User Manual /1/.


Introduction

Properties of the ESM TP80
Electrical ports 8 x 10/100 Mbps autonegotiation ports
TP connectors (RJ-45 jacks)
Maximum distance between two ESM TP80 modules
Maximum ring span with 50 ESM TP80 modules
Digital Inputs 8 x DC 24V

Possible Attachments
The OSM BC08 allows you to connect up to 8 DTEs or network components over FO ports and is suitable particularly in environments in which the data lines run through areas with high levels of electromagnetic interference (for example, in the vicinity of power supply cables).
The OSM BC08 can be coupled with other OSM BC08, OSM ITP62, OSM TP62, OSM TP22, and OSM ITP53 over the optical ports 7 and 8 to form a redundant fiber-optic ring, a fiber-optic star, or a fiber-optic linear bus.
The OSM BC08 also has eight digital inputs. The states of the inputs are available in a management information base (MIB) and can be read using an SNMP get request. Depending on the configuration of the device, changes at these inputs can also trigger the sending of E-mails, SNMP traps and/or entries in the log of the OSM. The use of these functions is described in the OSM/ESM Network Management User Manual /1/.



Introduction

Properties of the OSM BC08
Ports 8 x 100 Mbps FO ports (full duplex) BFOC female connectors
Maximum distance between two OSMs 3000 m (multimode graded-index fiber)
Maximum ring span with 50 OSMs 150 km
Digital Inputs 8 x DC 24V
Introduction

Possible Attachments
The OSM TP22 allows attachment of up to 2 DTEs or network segments with TP connectors. By coupling an OSM via ports 3 and 4 it is possible to create optical bus and ring structures. The OSM TP22 can be coupled with other OSM TP22, OSM TP62, OSM ITP53, OSM ITP62, and OSM BC08 modules via the optical ports.
The OSM TP22 also has four digital inputs. The states of the inputs are available in a management information base (MIB) and can be read using an SNMP get request. Depending on the configuration of the device, changes at these inputs can also trigger the sending of E-mails, SNMP traps and/or entries in the log of the OSM. The use of these functions is described in the OSM/ESM Network Management User Manual /1/.



Introduction

Properties of the OSM TP22
Electrical ports 2 x 10/100 Mbps autonegotiation/autocrossover ports
with TP connectors (RJ-45 jacks)
Optical ports 2 x 100 Mbps FO ports (full duplex)
Maximum distance between two OSMs 3000 m (multimode graded-index fiber)
Maximum ring span with 50 OSMs 150 km
Digital Inputs 4 x DC 24V
Introduction · BFOC female connectors

Possible Attachments
The ESM TP40 allows attachment of up to 4 DTEs or network segments with TP connectors (RJ-45 jack). By coupling further ESMs via ports 3 and 4 it is possible to create bus and ring structures.
The ESM TP40 also has four digital inputs. The states of the inputs are available in a management information base (MIB) and can be read using an SNMP get request. Depending on the configuration of the device, changes at these inputs can also trigger the sending of E-mails, SNMP traps and/or entries in the log of the ESM. The use of these functions is described in the OSM/ESM Network Management User Manual /1/.


Introduction

Properties of the ESM TP40
Ports 4 x 10/100 Mbps autonegotiation/autocrossover ports
with TP connectors (RJ-45 jacks)
Maximum distance between two ESMs 100 m
Maximum ring span with 50 ESMs 5 km
Digital Inputs 4 x DC 24V
Introduction

This chapter discusses the general functions of the OSM/ESM, in particular the properties of the switching technology.
By filtering the data traffic based on the Ethernet (MAC) address of the DTEs, local data traffic remains local, only data intended for nodes in another network segment are passed on by the OSM or ESM. This reduces the data traffic in the network segments and lowers the network load in the network segments.
OSMs and ESMs store the data received at the ports and the direct it to the destination address. The restriction of the network span resulting from collision detection (CSMA/CD) ends at the OSM/ESM port. With multimode graded-index fibers, a total network span of up to 150 km and more can be achieved without problems. With the OSM ITP62-LD, the monomode fibers allow a network span of up to 1300 km.
OSMs and ESMs only pass on valid data. Invalid packets are discarded so that bad packets within a network segment have no effect on any other segment attached to the OSM/ESM.
By evaluating the source addresses in the data packets, OSMs/ESMs automatically learn the addresses of the DTEs attached via a particular port. If an OSM/ESM receives a data packet, it directs this packet only to the port via which the appropriate DTE can be obtained.
An OSM/ESM can learn up to 7000 addresses.
Functions

An OSM/ESM monitors the age of the addresses it has learnt - address entries that exceed a certain age (aging time, default setting on the OSM/ESM 40 seconds) are deleted again by the OSM/ESM. If a packet with a source address matching the address entry is received before the aging time elapses, the address entry is retained and the age of the address is set to 0 again. When the OSM/ESM is restarted, the address entries are also deleted. If a packet is received by an OSM/ESM for which there is no address entry, the OSM/ESM distributes it to all ports.
The electrical ports of the OSM/ESM are set to autonegotiation mode as default (autosensing).
They automatically detect the transmission rate (10 or 100 Mbps) at which the attached device or attached network segment operates and set themselves to this rate. If the partner device also supports the autonegotiation mode, the devices further negotiate whether they will exchange data with each other in the half duplex or full duplex mode.
As a result of the automatic adaptation to the transmission rate of the attached DTEs, existing network segments operating at 10 or 100 Mbps can be interconnected simply using OSMs/ESMs.
OSMs/ESMs support frames with VLAN tags according to IEEE 802.1Q.
VLAN tags are additional information entered in the frame header. This additional information includes a priority field according to IEEE 802.1D. This field can have values from 0 through 7 and allows frames to be assigned a priority from 0 (lowest priority) through 7 (highest priority).
Frames with priority 0 through 3 are processed with low priority in the OSMs/ESMs and frames with priority 4 through 7 are processed with high priority. Frames with a non-learned unicast destination address are an exception. These are always handled with low priority.
Functions

Frames with a priority higher than 3 can have a negative effect on the redundancy functions of OSMs/ESMs so that the reconfiguration time of maximum 0.3 seconds can no longer be guaranteed and higher failover times result.
Functions


Network Topologies with OSM/ESM
With OSMs or ESMs, bus structures can be implemented . The cascading depth and total span of a network are limited only by the monitoring times of the communication connections. These times must always be set higher than the signal delay of the transmission path.

1 Fiber-optic cable (FOC) 3 TP cord 9/RJ-45 4 ITP standard cable 9/15

Network Topologies with OSM/ESM
Apart from OSM ITP62-LD modules, all listed OSM variants can be used in any combination in a bus consisting of OSMs. OSM ITP62-LD modules can only be coupled with other OSM ITP62-LD modules via the optical ports (monomode fiber).

2 ITP XP standard cable 9/9 3 TP cord 9/RJ-45 4 ITP standard cable 9/15
In a bus consisting of ESMs, both ESM ITP80 modules and ESM TP80 modules can be used. TP and ITP variants can be connected together using the Industrial Ethernet FastConnect cabling system.

Network Topologies with OSM/ESM
With the aid of an OSM functioning as the redundancy manager (RM), both ends of an optical bus made up of OSMs can be closed to form a redundant optical ring. The OSMs are connected together using ports 7 and 8.
The RM monitors the OSM bus connected to it, closes the bus if it detects and interruption and therefore reestablishes a functioning bus configuration. A maximum of 50 OSMs are permitted in an optical ring. This allows reconfiguration time of less than 0.3 s to be achieved. The RM mode is activated on the OSM using a DIP switch (Section 4.2.4.1).

OSM ITP 62 OSM ITP 62 OSM TP 62 OSM TP 62
OSM ITP 62 OSM ITP 62 OSM ITP 62
A redundant electrical ring can be established using ESMs in the same way. To achieve this the ESMs must be connected together using ports 7 and 8. One device must be switched to the redundancy manager mode. With ESMs and a maximum of 50 devices in the ring, a reconfiguration time of less than 0.3 s can also be achieved.

Network Topologies with OSM/ESM

ESM ITP 80 ESM ITP 80 ESM ITP 80 ESM ITP 80
ESM ITP 80 ESM ITP 80 ESM ITP 80 ESM ITP 80

Network Topologies with OSM/ESM
The standby-sync port of an OSM/ESM with 8 ports allows the connection of two Industrial Ethernet OSMs or ESMs with one operating as standby master (DIP switch "Stby off") and the other as standby slave (DIP switch "Stby on"). With this mode, pairs of OSMs/ESMs can be used for redundant coupling of OSM/ESM or OLM rings.
With network management, the OSM/ESM can also be configured so that several rings or networks can be interconnected at the same time with two OSMs/ESMs (see OSM/ESM Network Management, User Manual /1/).

Network Topologies with OSM/ESM

OSM ITP 62 OSM ITP 62 OSM ITP 62 OSM ITP 62 OSM ITP 62 OSM ITP 62 OSM ITP 62
OSM ITP 62 OSM ITP 62 OSM ITP 62 OSM ITP 62 OSM ITP 62 OSM ITP 62

Network Topologies with OSM/ESM
The connection between two network segments is on two separate paths. Two of the OSMs/ESMs in a ring are connected together via a connecting cable (ITP-XP standard cable 9/9 with a maximum length of 40 m) and inform each other of their operating states. One of these OSMs/ESMs is assigned the redundant function using the DIP switch setting "Stby on" (standby slave). The other OSM takes over the function of the standby master (DIP switch setting "Stby off").
Immediately following the failure of the main transmission path, the standby slave enables the redundant path. If the main path is OK again, the standby master informs the standby slave. The main path is enabled and the redundant path disabled again. The reconfiguration time of the redundant ring coupling is less than 0.3 s.
On the standby master and standby slave only port 1 (standby port) can be used for the coupling to the neighboring ring. Ports 2 - 6 can be used just as normal OSM ports.
With network management, it is also possible to configure ports other than port 1 as standby ports (see also OSM/ESM Network Management User Manual /1/).
A standby master or standby slave can adopt the function of a redundancy manager at the same time.
When replacing a standby master during operation, the following order is necessary to prevent an interruption on the network:
When replacing a standby slave, no special measures are necessary. You must simply make sure that the standby master is active.

Network Topologies with OSM/ESM
The OSM ITP53 allows a redundant coupling of rings with FO transmission paths. This allows rings far apart from each to be connected.

1 Fiber-optic cable (FOC) 2 ITP XP standard cable 9/9

Network Topologies with OSM/ESM
Version 2 OSMs can be operated at the same time in the ring with the OSM (6GK 1105-0AA00) and ORM (6GK 1105-1AA00) here called OSM/ORM Version 1. Make sure that only one device can adopt the redundancy manager function in the ring; in other words, only one ORM or only one OSM Version 2 operating in the RM mode.


Network Topologies with OSM/ESM

1 Fiber-optic cable (FOC)

Network Topologies with OSM/ESM
In a redundant coupling of rings, make sure that the standby master and standby slave are either both of the type OSM Version 1 or both of the type OSM Version 2.

OSM ITP 62 OSM ITP 62 OSM ITP 62
1 Fiber-optic cable (FOC) 2 ITP XP standard cable 9/9

Network Topologies with OSM/ESM

1 Fiber-optic cable (FOC) 2 ITP XP standard cable 9/9
Figure 16 also shows how an existing ring with Version 1 OSMs can be connected to a ring with Version 2 OSMs.

Network Topologies with OSM/ESM
A network segment can be connected to each of the ports of an OSM/ESM.
The Ethernet Planning Rules:
need only be maintained as previously in each individual segment (see also "SIMATIC NET Industrial Twisted Pair and Fiber Optic Networks" manual).
The coupling of network segments via OSM has further advantages:

Network Topologies with OSM/ESM

1 Fiber-optic cable (FOC) 2 ITP XP standard cable 9/9


Interfaces, Displays and Operator Controls
This chapter describes the properties of ITP and the TP ports.
In the ITP variant of the OSM/ESM, the DTEs are attached via sub-D female connectors. The casings of the connectors are electrically connected to the casing of the OSM. A screw locking mechanism holds the connectors firmly in place.
RD + Pin 1
Pin 6 RD -
n.c. Pin 2
Pin 7 n.c. Pin 8 n.c. Pin 9 TD -
n.c. Pin 3
n.c. Pin 4
TD + Pin 5
With OSM TP62, OSM TP22, ESM TP40, and ESM TP80 modules, the DTEs are connected via RJ-45 jacks with MDI-X assignment (Medium Dependent Interface Crossover).

Interfaces, Displays and Operator Controls
Link Control
OSMs/ESMs monitor the connected TP/ITP cable segments for short-circuits or wire breaks using regular link test pulses complying with the 100BASE-TX standard. OSMs/ESMs do not send data to a segment from which they are not receiving link test pulses. An unused interface is taken to be a wire break since the device without power cannot send link test pulses.
If the receive cable pair is incorrectly connected (RD+ and RD- swapped over), the polarity is automatically reversed.
The TP/ITP ports of OSM/ESM are set to the autonegotiation mode.
They automatically detect the transmission rate (10 or 100 Mbps) at which the attached device or attached network segment operates and set themselves to this rate. If the partner device also supports the autonegotiation mode, the devices further negotiate whether they will exchange data with each other in the half duplex or full duplex mode.
OSMs/ESMs with digital inputs are capable of switching over their TP/ITP ports automatically between MDI and MDI-X pinning; in other words, they can cross over the send and receive data internally, when necessary. This means that regardless of the port type of the device you are connecting and the type of Ethernet cable, a connection can be established. Crossover cables are not necessary.

Interfaces, Displays and Operator Controls
Note The autocrossover function of a TP/ITP port of the OSM/ESM is active only when it is set to the autonegotiation mode. If this is not the case, it may be necessary to replace a straight-through cable with a crossover cable. Please remember that even when using straight-through cables, an illegal loop can occur in the Ethernet network, caused, for example, by connecting two ports on an OSM/ESM. Such a loop can lead to network overload and network failure.

Interfaces, Displays and Operator Controls
The FO ports have BFOC/2.5(ST) female connectors. They monitor the connected cable for wire breaks complying with the IEEE 802.3 100 Base-FX standard. A break on the FO cable is always signaled by the port status display of the two attached OSMs (status LED of the port goes off).

Interfaces, Displays and Operator Controls
A 9-pin female connector is used on the OSMs/ESMs with 8 ports to connect the ITP XP standard cable 9/9 for the redundant standby coupling. The casing of the connector is electrically connected to the casing of the OSM/ESM. The OSM TP22 and ESM TP40 do not have a standby-sync port.
A screw locking mechanism holds the connectors firmly in place.
Stby_In + Pin 1
n.c. Pin 2
Pin 6 Stby_In -
n.c. Pin 3
Pin 7 n.c. Pin 8 n.c. Pin 9 Stby_Out -
n.c. Pin 4
Stby_Out + Pin 5

Interfaces, Displays and Operator Controls
OSM/ESM modules have an RS-232 interface. This is used for the following purposes:
− Management with the aid of the command line interpreter (CLI) including setting the IP address information (see /1/).
DSR Pin 6 Pin 1
Pin 2 RD Pin 3 TD RTS Pin 7

Interfaces, Displays and Operator Controls
The attachment of the power supply and the signaling contact is made using a 6- pin plug-in terminal block with a screw locking mechanism.
+24V
F1
M
M
F2
L2 +
+24V
! Warning Industrial Ethernet OSMs/ESMs are designed for operation with safety extra- low voltage. This means that only safety extra-low voltages (SELV) complying with IEC950/EN60950/ VDE0805 can be connected to the power supply terminals and the signaling contact. The power supply unit to supply the OSM/ESM must comply with NEC Class 2 (voltage range 18 - 32 V, current requirement 1 A) The signaling contact can carry a load of maximum 100 mA (safety extra-low voltage (SELV), DC 24V). Exceptions:

Interfaces, Displays and Operator Controls
The power supply can be connected redundantly. Both inputs are isolated. There is no load distribution. With redundant power supply, the power supply unit with the higher output voltage supplies the OSM/ESM alone.
The following is signaled via a floating signaling contact (relay contact) when contact is broken:
OSM/ESM in Normal Mode and ITP XP Standard Cable 9/9 Plugged into the Standby-Sync Port:

Interfaces, Displays and Operator Controls

Interfaces, Displays and Operator Controls
In the case of the OSMs/ESMs with digital inputs, the states of these inputs are available in a management information base (MIB) and can be read with an SNMP get request. Depending on the configuration of the device, changes at these inputs can also trigger the sending of E-mails, SNMP traps and/or entries in the log of the OSM/ESM. The use of these functions is described in the OSM/ESM Network Management User Manual /1/.
The digital inputs are attached using six-pin plug-in terminal blocks with screw locking mechanisms.

M
! Warning The input voltage must not exceed +30V DC or fall below -30V DC.

Interfaces, Displays and Operator Controls
The OSM/ESM has the following LED displays:
The status display indicates the operating mode of an OSM/ESM:
Lit The OSM/ESM has detected an error. The signaling contact opens at the same time. The signaled errors are described in Chapter 4.1.7.
Not lit No errors detected by the OSM/ESM.
This LED does not exist on the OSM TP22 and ESM TP40.
Lit The standby function is activated, the OSM/ESM is in the standby passive mode.
Not lit The standby function is deactivated.
Flashes The standby function is activated, OSM/ESM is in the standby active mode; in other words, the master OSM/ESM has failed and the standby OSM/ESM takes over data traffic.
Status Meaning · Status Meaning

Interfaces, Displays and Operator Controls
Lit The OSM/ESM is operating in the redundancy manager mode. The ring is operating free of errors in other words the redundancy manager does not allow traffic through but monitors the ring.
Not lit The OSM/ESM is not in the redundancy manager mode.
Flashes The OSM/ESM is in the redundancy manager mode and has detected a break on the ring. The OSM/ESM makes the connection between its two ring ports so that a functional bus configuration is reestablished.
Status Meaning

Interfaces, Displays and Operator Controls
The display mode of the "Power" LED can be switched over by briefly pressing the "Select/Set" button on the front panel of the OSM/ESM. The valid display mode is indicated by the display mode LEDs on the OSM/ESM.
Depending on the status of the display mode LEDs, the "Power" LED has the two following display modes:
Status of the power supplies
Power LED L1 or L2
In the following states of the display mode LEDs, the Power LEDs indicate the current status of the two voltages of the OSM/ESM:
- Lit green; in other words, power supply 1
or 2 (line 1 or line 2) is applied.
- Not lit; in other words power supply 1 or 2
(line 1 or line 2) is less than 14 V.
LED off LED off LED off
LED off LED on LED off
LED on LED off LED off
LED off LED off LED on
Display mode Meaning · Display Mode

Interfaces, Displays and Operator Controls
With the line 1 or 2 LEDs, the fault mask indicates whether the power supplies are monitored with the signaling contact.
L1 or L2 LED
- Lit green; in other words the
corresponding power supply (line 1 or line 2) is monitored. If the power supply falls below 14 V, the signaling contact responds. - Not lit, in other words the corresponding
LED on LED on LED off
power supply (line 1 or line 2) in not monitored. If the power supply falls below 14 V this does not trigger the signaling contact.
The fault mask can be set again with the button on the front panel of the OSM/ESM (see 4.2.4.2)
The "Select/Set" button on the front panel of the OSM/ESM changes the display mode of the display mode LEDs. Using this button, a new status can be programmed for the fault mask (see 4.2.4.2)
Fault Mask · Display Mode

Interfaces, Displays and Operator Controls
The port LEDs indicate the operating states of the individual ports of the OSM/ESM. On the OSM/ESM variants with digital inputs, the state of the inputs is also indicated by the port LEDs. To allow this, the OSMs/ESMs have an additional display mode. The display mode of the port LEDs can be changed using the Select/Set button on the front panel of the OSM/ESM allowing all operating states to be displayed. The current display mode is signaled by the display mode LEDs.
(for example station turned off or cable not connected) - Lit green: Valid connection - Flashes green (once per period): Port
switched to standby - Flashes green (twice per period): Port is
LED off LED off LED off
segmented - Flashes green (three times per period):
Port is turned off - Flashes green (four times per period):
Port is mirrored - Flashes/lit yellow: Data reception on this
LED off LED on LED off

Interfaces, Displays and Operator Controls
LED on LED off LED off
The fault mask indicates whether the ports and the power supplies are monitored with the signaling contact.
words, if the port does not have a valid connection (for example cable not plugged in or attached device turned off), the signaling contact is triggered. - Not lit: The port is not monitored; in other
LED on LED on LED off
words, an invalid or valid connection at the port does not trigger the signaling contact.
The fault mask can be set again with the button on the front panel of the OSM (see 4.2.4.2)
to the corresponding digital input. This requires an input voltage of + 13 V DC to + 30 V DC. - Not lit: The logical state "0" is applied to
the corresponding digital input. This requires an input voltage of + –30 V DC to + 3 V DC.
LED off LED off LED on
The basic status "Port Status" of the display is adopted automatically after turning on the device. The device also switches automatically to this display status when the "Select/Set" button is pressed for more than a minute.

Interfaces, Displays and Operator Controls
4.2.4.1 Two-Pin DIP Switch
With the two-pin DIP switches on the upper casing of the OSM/ESM you can do the following:
Stby · off on

Interfaces, Displays and Operator Controls
4.2.4.2 "Select/Set" Button
The "Select/Set" button on the front panel of the OSM/ESM has the following functions:
When it is reset, all the settings of the OSM/ESM are set to their defaults (as set in the factory). This allows you to cancel settings made, for example, with Web-Based Management (WBM) (see also OSM/ESM Network Management, User Manual).


Installation, Commissioning, Cleaning and Maintenance
– Mounting brackets, screws and terminal block
– One or two extra terminal blocks for OSMs/ESMs with digital inputs
– CD (includes the manuals) and product information bulletin
– OSM/ESM device

Installation, Commissioning, Cleaning and Maintenance
OSMs/ESMs can be installed in several ways:

Installation, Commissioning, Cleaning and Maintenance



Installation, Commissioning, Cleaning and Maintenance

Figure 28. Removing from the Standard Rail

Installation, Commissioning, Cleaning and Maintenance




Installation, Commissioning, Cleaning and Maintenance
To install in pairs in the 19" cubicle, you require the two securing brackets supplied.


Interconnecting the devices at the rear


Installation, Commissioning, Cleaning and Maintenance
To install an OSM/ESM on a wall, follow the steps below:




Installation, Commissioning, Cleaning and Maintenance
The following table shows how to mount the device on different types of walls:
Concrete wall Use four wall plugs 6 mm in diameter and 30 mm long. (drill hole 6 mm in diameter, 45 mm deep). Use screws 4.5 mm in diameter and 40 mm long.
Use screws 4 mm in diameter and at least 15 mm long.
(min. 2 mm thick)
Sandwich type plaster wall
Use an anchoring plug with at least 4 mm diameter.
(min. 15 mm thick)
Wall Mounting · Metal wall

Installation, Commissioning, Cleaning and Maintenance
If you need to clean the OSM/ESM, use a dry cloth only.

Installation, Commissioning, Cleaning and Maintenance
If a fault develops, please send the module to your SIEMENS service department for repair. The devices are not designed for repair on site.

With the OSM/ESM it is possible to update the firmware via the serial port.
You can obtain information on the firmware updates for OSM/ESM on the Internet at http://www.siemens.de/automation/service&support specifying the keyword "OSM Firmware".
To download the firmware you require a PC with Windows 95/98/NT and the Hyperterminal program available under Accessories. The download is explained below based on the dialogs displayed in Hyperterminal.
Connect the serial port of your PC and the OSM/ESM with a normal null modem cable . Depending on the port of your PC that you select, you use a cable with a 9- pin or 25-pin sub-D female connector at the PC end and a 9-pin female connector at the OSM/ESM end.
The following table shows the pinning and the connections for both types of cable:
PC port 25-pin Female
OSM port 9-pin Female
Signal Name Pin Pin Pin Signal name
TD (Transmit Data) 2 3 2 RD
RD (Receive Data) 3 2 3 TD
RTS (Request To Send)
CTS (Clear To Send) 5 8 7 RTS
SG (Signal Ground) 7 5 5 SG
DSR (Data Set Ready) 6 6 4 DTR
DTR (Data Terminal Ready)
9-pin Female · connected to

Follow the steps outlined below in Hyperterminal:

Firmware Update

The following message then appears in the Hyperterminal window:

The following message is then displayed.
Firmware Update


The following dialog then appears displaying the progress of the download.
Firmware Update


Start the download by pressing the "Set/Select" button again.
Downloading can take up to 10 minutes. After you have downloaded the firmware successfully, the device is automatically started with the new firmware. Please note the version of the new firmware on a label on the side labeling panel of the OSM/ESM.
Note During the download, do not interrupt the connection between the PC and OSM/ESM or turn off the power supply to the OSM/ESM. If the firmware could not be downloaded completely to the OSM due to a power failure, the message "Firmware in flash is faulty" appears after the device starts up. This means that the firmware must be downloaded again.
Firmware Update

Attachment of DTEs or network segments twisted pair/Industrial Twisted Pair
6 x 9-pin sub-D female connectors for OSM ITP62, OSM ITP62-LD
5 x 9-pin sub-D female connectors for OSM ITP53
8 x 9-pin sub-D female connectors for ESM ITP80
2 x RJ-45 jacks for OSM TP22
4 x RJ-45 jacks for ESM TP40
6 x RJ-45 jacks for OSM TP62
8 x RJ-45 jacks for ESM TP80
All electrical ports support 10/100 Mbps autonegotiation
OSMs/ESMs with digital inputs: The electrical ports support autocrossover.
Standby-sync port for redundant coupling of rings
1 x 9-pin sub-D female connector
(not OSM TP22, ESM TP40)
Attachment of further OSMs and DTEs via FO
2 x 2 BFOC sockets for OSM ITP 62, OSM ITP62-LD, OSM TP62, OSM TP22
3 x 2 BFOC sockets for OSM ITP 53
8 x 2 BFOC sockets for OSM BC08
(100 Mbps, 100BaseFX, full duplex)
Connector for power supply and signaling contact
1 x 6-pin plug-in terminal block
Power supply (redundant inputs decoupled)
2 sources of DC 24V (DC 18 to 32V) safety extra-low voltage (SELV)
Power supply connected over high resistance to casing (not electrically isolated).
Tested in compliance with IEC 6100-4- 5, 1995 "Surge Immunity Test" using the DEHN Blitzductor VT AD 24V, Type No. 918 402 lightning protection device
Ports

Power loss at 24 V DC 20 W
Load on the signaling contact DC 24 V / max. 100 mA safety extra- low voltage (SELV)
Current consumption at rated voltage 1000 mA
Overcurrent protection at input Non-replaceable fuse (1.6 A / 250 V / slow)
Digital Inputs Input voltage:
Inputs electrically isolated from electronics.
Technical Specifications · Ports

FO cable length between two OSMs For OSM ITP62, OSM ITP53, OSM TP62, OSM TP22:
0-3000 m (62.5/125 µm glass fiber; 1 dB/km at 1300 nm; 600 MHz*km; 6 dB max. permitted FO cable attenuation at 3 dB link power margin)
0-3000 m (50/125 µm glass fiber; 1 dB/km at 1300 nm; 600 MHz*km; 6 dB max. permitted FO cable attenuation at 3 dB link power margin)
For OSM ITP62-LD:
0-26000 m (10/125 µm single mode fiber; 0,5 dB/km at 1300 nm; 13 dB max. permitted FO cable attenuation at 2 dB link power margin)
ITP cable length 0-100 m
TP cable length 0-10 m with TP cord
up to 100 m total length when using the FastConnect cabling system
Length of the ITP XP Standard Cable 9/9 at standby-sync port 0-40 m
Bus/star structure Any (only depending on signal propagation time)
Redundant ring 50 (for reconfiguration time < 0.3 s)
Switching Properties of OSM/ESM
Number of learnable addresses Up to 7000
Aging time 40s (default)
Latency 4 µs (measured at 75% load between two ports operating at 100 Mbps)
Switching procedure Store and forward
Technical Specifications · Permitted Cable Lengths · Cascading Depth

Operating temperature 0°C to +60°C
Storage/transport temperature -40°C to +80°C
Relative humidity in operation ‹ 95% (no condensation)
Operating altitude Max. 2000 m
Noise emission EN 55081 Class A
Noise immunity EN 50082-2
Laser protection Class 1 complying with IEC 60825 -1
Dimensions (W x H x D) in mm 217 x161 x 69
Weight in g 1400
Installation options Standard rail
Installation in 19" cubicle
Only horizontal installation permitted
Degree of protection IP 20

Consignment / Order Numbers
Consignment - SIMATIC NET Industrial Ethernet OSM/ESM - Fittings for 19" cubicle installation/wall
mounting - 6-pin plug-in terminal block for power supply
and signaling contact - One to two 6-pin plug-in terminal blocks for
OSMs/ESMs with digital inputs - Documentation on the CD - Product information bulletin
Order number:
Industrial Ethernet OSM ITP62 with digital inputs
Industrial Ethernet OSM ITP62 without digital inputs
Industrial Ethernet OSM ITP62-LD with digital inputs
Industrial Ethernet OSM ITP62-LD without digital inputs
Industrial Ethernet OSM ITP53 with digital inputs
Industrial Ethernet OSM ITP53 without digital inputs
Industrial Ethernet OSM ITP80 with digital inputs
Industrial Ethernet OSM ITP80 without digital inputs
Industrial Ethernet OSM TP62 with digital inputs
Industrial Ethernet OSM TP62 without digital inputs
Industrial Ethernet OSM TP80 with digital inputs
Industrial Ethernet OSM TP80 without digital inputs
Industrial Ethernet OSM TP22 with digital inputs
Industrial Ethernet OSM TP40 with digital inputs
Industrial Ethernet OSM BC08 with digital inputs
Technical Specifications

Industrial Twisted Pair and Fiber Optic Networks Manual
Triaxial networks for Industrial Ethernet manual
Technical Specifications · Accessories

The OSM/ESM products listed below, comply with the following standards and directives if they have the corresponding symbols on the type plate:
Industrial Ethernet OSM ITP62 with digital inputs 6GK1105-2AA10
Industrial Ethernet OSM ITP62 without digital inputs 6GK1105-2AA00
Industrial Ethernet OSM ITP62-LD with digital inputs 6GK1105-2AC10
Industrial Ethernet OSM ITP62-LD without digital inputs 6GK1105-2AC00
Industrial Ethernet OSM ITP53 with digital inputs 6GK1105-2AD10
Industrial Ethernet OSM ITP53 without digital inputs 6GK1105-2AD00
Industrial Ethernet OSM ITP80 with digital inputs 6GK1105-3AA10
Industrial Ethernet OSM ITP80 without digital inputs 6GK1105-3AA00
Industrial Ethernet OSM TP62 with digital inputs 6GK1105-2AB10
Industrial Ethernet OSM TP62 without digital inputs 6GK1105-2AB00
Industrial Ethernet OSM TP80 with digital inputs 6GK1105-3AB10
Industrial Ethernet OSM TP80 without digital inputs 6GK1105-3AB00
Industrial Ethernet OSM TP22 with digital inputs 6GK1105-2AE00
Industrial Ethernet OSM TP40 with digital inputs 6GK1105-3AC00
Industrial Ethernet OSM BC08 with digital inputs 6GK1105-4AA00
SIMATIC NET OSMs/ESMs meet the requirements of the following EU directives:
Directive 89/336/EEC “Electromagnetic Compatibility" (EMC directive)
Directive 73/23/EEC "Electrical Equipment Designed For Use Within Certain Voltage Limits" (Low Voltage Directive)
The EU declaration of conformity is available for the responsible authorities according to the above-mentioned EU directive at the following address:

Siemens Aktiengesellschaft Bereich Automatisierungs- und Antriebstechnik Industrielle Kommunikation (A&D PT2) Postfach 4848
The products are designed for use in an industrial environment:
Requirements Area of Application
Emitted Noise Noise immunity
This product is not a machine in the sense of the EU directive on machines. There is therefore no declaration of conformity for the EU directive on machines 89/392/EEC.
If the product is part of the equipment of a machine, it must be included in the procedure for obtaining the declaration of conformity by the manufacture of the machine.
C-Tick Mark, AS/NZS 2064 (Class A)
Underwriters Laboratories UL 1950 / UL 60950 (Information Technology Equipment)
Canadian Standard Association CSA C22.2 No. 60950-00

FM Hazardous (Classified) Location Electrical Equipment: Non Incendive / Class I / Division 2 / Groups A,B,C,D / T* and Non Incendive / Class I / Zone 2 / Group IIC / T4
*) Temperature Class T4 or T4A, depending on model
! Warning In hazardous areas liable to explosion, injury to persons and damage to property can occur if you close or open an electric circuit while an OSM/ESM is in operation. Do not close or open live electrical circuits unless sure that there is no risk of explosion.
Standards and Approvals

The products meet the requirements if you adhere to the installation and safety instructions contained in these Operating Instructions for SIMATIC NET Industrial Ethernet OSM/ESM and in the following documentation during installation and operation:
Standards and Approvals

Autocrossover Mechanism with which a TP port is automatically switched over between MDI and MDI-X pinning to establish a connection regardless of the port pinning of the device being connected. This makes the use of crossover cables unnecessary. The autocrossover function is available only when the port is set to autonegotiation mode.
Autonegotiation Procedure standardized by IEEE 802.3 in which the transmission parameters (for example 10/100 Mbps, full/half duplex) are negotiated automatically between the devices.
Procedure in which the module automatically detects incorrect attachment of a cable to the electrical OSM/ESM port (RD+ and RD- swapped over). The OSM then reverses the polarity automatically.
Backbone In conjunction with the OSM/ESM, this means a bus or ring structure made up of interconnected OSM or ESM modules that form the backbone of an industrial LAN.
Display Mode The display mode LEDs indicate the display mode in which the port and power LEDs and the attached input signals (OSMs/ESMs with digital inputs only) of the OSM/ESM are currently working. The display mode can be changed with the button on the front panel of the OSM/ESM.
ESM Electrical Switching Module. SIMATIC NET Ethernet switch with electrical ports
Fault Mask The fault mask specifies which ports (ports 1 - 8) and power supply terminals (line 1/2) are monitored by the signaling contact. The fault mask can be set again with the button on the front panel of the OSM/ESM.
Filtering OSMs/ESMs learn the addresses of the devices that can be accessed via a port. They redirect the packets intended for this device only via this port.
ITP Port Port with Industrial Twisted Pair (ITP) connector (sub D 9-pin female)
Auto Polarity Exchange · Autosensing See Autonegotiation

Latency The latency specifies the taken for packets to pass through the OSM/ESM. It is assumed that a received packet can be sent on immediately. The latency does not include the time necessary for the OSM/ESM to receive a packet.
Link Control OSMs/ESMs monitor the connected TP/ITP cable segments for short- circuits or wire breaks using regular link test pulses complying with the 100BASE-TX standard. OSMs/ESMs do not send data to a segment from which they are not receiving link test pulses. An unused interface is taken to be a wire break since the device without power cannot send link test pulses.
MDI-X Medium Dependent Interface Crossover RJ-45 jack with pinning of a network component
OSM Optical Switching Module. SIMATIC NET Ethernet switch with optical and electrical ports
Reconfiguration Time Time required by the OSM/ESM operating in the redundancy manager
(RM) or standby mode to reestablish a functioning configuration if a device fails or the cable is interrupted.
Mode of an OSM or ESM for forming a redundant ring structure. The RM monitors the OSM or ESM bus connected to it, closes the bus if it detects and interruption. This reestablishes a functioning bus configuration.
One and only one device can operate in the RM mode in every OSM or ESM ring.
Signaling Contact Floating relay contact via which the error states detected by the OSM/ESM can be signaled.
Standby-sync port Port of an OSM/ESM via which two OSMs or ESMs are interconnected in a redundant ring link allowing them to inform each other of their operating states (not available with the OSM TP22 and ESM TP40).
Store and forward In this switching method used on the OSM/ESM, the complete packet is read in before it is passed on by the switch. A packet is only passed on if it is error-free.
TP Port Port with a TP connector (RJ-45 jack)
Glossary · Redundancy Manager (RM)



/1/ SIMATIC NET Industrial Ethernet OSM/ESM Network Management, Release 08/2001 supplied with every device on CD and available at http://www4.ad.siemens.de/view/cs/de/8677203 on the Web.
/2/ SIMATIC NET Industrial Twisted Pair and Fiber-Optic Networks, Release 07/2002 Order numbers: 6GK1970-1BA10-0AA0 German 6GK1970-1BA10-0AA1 English 6GK1970-1BA10-0AA2 French 6GK1970-1BA10-0AA4 Italian
/3/ SINEC H1 Manual for Triaxial Networks, Release 04 Order number 6GK1970-1AA20-0AA0 (German/English)
References



Index