Modular I/O System

INTERBUS S

Quatech INTERBUS S — Modular I/O System diagram (page 1)
Fig. 1 · Modular I/O System

Manual

Technical description, installation and configuration

750-132 Version 2.2.1

Page 2 of the Quatech INTERBUS S user manual — INTERBUS S
Page 2 · click to enlarge
Page 2

Copyright 1997-2001 by WAGO Kontakttechnik GmbH All rights reserved.

WAGO Kontakttechnik GmbH Hansastraße 27 D-32423 Minden

Phone+49 (0) 571/8 87 – 0 Fax: +49 (0) 571/8 87 – 1 69
E-Mailinfo@ wago.com
Webhttp://www.wago.com

Technical Support Phone: +49 (0) 571/8 87 – 5 55 Fax: +49 (0) 571/8 87 – 4 30

E-Mailsupport@ wago.com

Every conceivable measure has been taken to ensure the correctness and com- pleteness of this documentation. However, as errors can never be fully ex- cluded we would appreciate any information or ideas at any time.

We wish to point out that the software and hardware terms as well as the trademarks of companies used and/or mentioned in the present manual are generally trademark or patent protected.

INTERBUS S

ii • General · Modular I/O System

Page 7 of the Quatech INTERBUS S user manual — The WAGO I/O System
Page 7 · click to enlarge
Page 7
Quatech INTERBUS S — The WAGO I/O System diagram (page 7)
Fig. 2 · The WAGO I/O System

The WAGO I/O SYSTEM consists of various components which are capable of providing modular and application specific fieldbus nodes for various fieldbusses.

Quatech INTERBUS S — The WAGO I/O System diagram (page 7)
Fig. 3 · The WAGO I/O System

I11.1 Setting up a fieldbus node with the WAGO I/O SYSTEM

General remark: A fieldbus node consists in principle of a fieldbus coupler at the front end, a number of special function modules and a termination module which is placed at the other end.

1. Buscoupler The Buscoupler forms the link between the fieldbus and the field devices with their I/O functions. All control functions required for the faultless operation of the I/O functions are carried out by the coupler. The connection to different fieldbus systems is established by each of the corresponding Buscouplers, e.g. for PROFIBUS, INTERBUS S, II/O LIGHTBUS, CAN, ModBus etc. In this way a change of the fieldbus system is possible.
2. Function modules In the function modules, the incoming process data ais converted. Corresponding to the different requirements, special function modules are available for a variety of functions. There are digital and analog inputs and outputs and modules for special functions. The modules are described in the following chapters.
3. Termination module A termination module is needed for faultless operation of the node. The termination module is always placed as the last module in order to obtain a termination of the fieldbus node. This module has no I/O function.

Interbus / Introduction

Page 8 of the Quatech INTERBUS S user manual — The WAGO I/O System
Page 8 · click to enlarge
Page 8

Assembly of the WAGO I/O System All components of the system can be snapped directly on a carrier rail according to EN 50022 (DIN 35). When snapping the analog or digital components onto the rail, no special sequence must be observed. The secure positioning and connection of the individual function modules and the coupler is provided by a snap-in system. This snap-in system provides automatic interlocking onto the DIN rail assembly. It is always possible to remove a function module or the Buscoupler from the assembly by pulling the orange pull-tab.

Please note, that the power supply of the field side as well as the data transmission are interrupted. It has to be ensured that the interruption of PE will not put personnel or equipment in danger.

With a CAGE CLAMP, conductors with a cross section of 0.08 to 2.5mm2 /AWG 18-14 can be connected. Vibration proof, fast and maintenance-free. You simply introduce a screwdriver or an operating tool into the operating slot under the clamping unit. The CAGE CLAMP spring is pressed down. You can now introduce the wire into the clamping unit. Withdraw the operating tool and the conductor is automatically clamped.

Interbus / Introduction

Page 9 of the Quatech INTERBUS S user manual — The WAGO I/O System
Page 9 · click to enlarge
Page 9

The clamping force adjusts automatically to the conductor cross section. The flat clamping face of the CAGE CLAMP spring presses the conductor against the current bar without damage. Any deformation or movement of the conductor is compensated, thus eliminating the risk of a loose connection. The contact point between conductor and CAGE CLAMP is well protected against corrosive deterioration. This connection is made fast and, furthermore, it is maintenance-free. There is no need for costly periodical examination of the connections.

The supply modules of the WAGO I/O system are partly equipped with a fuse holder. This fuse holder can be pulled out in order to break the circuit of the following modules. To do so, you first have to insert a screwdriver into one of the slots on both sides in order to pull out the front side of the fuse holder.

The front side now being hinged down makes it possible to remove or to insert the fuse. After that, you lift up the front side again and push the fuse holder back into its original position.

Interbus / Introduction

Page 10 of the Quatech INTERBUS S user manual — 2.1 Buscoupler - Hardware
Page 10 · click to enlarge
Page 10
Quatech INTERBUS S — Buscoupler - INTERBUS S diagram (page 10)
Fig. 4 · Buscoupler - INTERBUS S

2.1 Buscoupler - Hardware

Quatech INTERBUS S — 2.1 Buscoupler - Hardware diagram (page 10)
Fig. 5 · 2.1 Buscoupler - Hardware
Ill. 2The INTERBUS buscoupler

The 750-304 Interbus coupler consists of two major electronic sub systems:

left side: This housing contains the electronics for the coupling to the bus, the processor and the fieldbus connection. (ill. 2.1)

right side: This housing contains the DC to DC converter and power distribution for the internal K bus, local processor and external 24 V DC connections to other discrete I/O modules. Illustration 2.2 identifies the 24 V DC connection points to supply voltage to I/O modules. Illustration 2.3 identifies the ground connection.

INTERBUS S / Buscoupler

Page 11 of the Quatech INTERBUS S user manual — Supply Voltage - Electronics
Page 11 · click to enlarge
Page 11
Quatech INTERBUS S — Supply Voltage - Electronics diagram (page 11)
Fig. 6 · Supply Voltage - Electronics
Quatech INTERBUS S — Supply Voltage - Electronics diagram (page 11)
Fig. 7 · Supply Voltage - Electronics
Quatech INTERBUS S — Supply Voltage - Electronics diagram (page 11)
Fig. 8 · Supply Voltage - Electronics
Ill. 3Termination points for the power supply and the internal electronics

The nominal operating voltage of the Buscoupler and the control electronics in the function modules is 5 V DC. The supply is connected to the first two CAGE CLAMPS at the top of the coupler as seen in Ill. 3.

The 24 V DC supply voltage is generated by an internal voltage regulator (DC/DC converter) and fed to the electronics (5 V DC). The electrical isolation of the external bus system is made by utilizing an optocoupler.

Please note that the power supply for the control electronics in the function modules is made automatically by the data contacts of the following module when it is snapped on the assembly (ill. 3.1). The power supply to the attached I/O modules is provided by gold-plated self-cleaning slide contacts. If an attached module is taken out of the existing configuration, the connection via the K bus is broken and the coupler is able to detect this.

INTERBUS S / Buscoupler

Page 12 of the Quatech INTERBUS S user manual — Supply Voltage - Field Side
Page 12 · click to enlarge
Page 12
Quatech INTERBUS S — Supply Voltage - Field Side diagram (page 12)
Fig. 9 · Supply Voltage - Field Side
Quatech INTERBUS S — Supply Voltage - Field Side diagram (page 12)
Fig. 10 · Supply Voltage - Field Side
Quatech INTERBUS S — Supply Voltage - Field Side diagram (page 12)
Fig. 11 · Supply Voltage - Field Side
Ill. 4Termination points for the supply voltage - Field side

The connection of the supply voltage is electrically isolated from the internal electronics. Two CAGE CLAMPS are always connected by a power contact. By this way, the power supply is taken to different points of the configuration.

It is possible to supply the following at the termination points (Ill. 4):

Volts24 V DC - Amps: 10 A DC

The voltage is automatically supplied when the function modules are snapped together. Self-cleaning power jumper contacts (P.J.C.s) ensure safe connections (Ill. 4). Female contacts (current supply) are integrated in the buscoupler and I/O housings. The male contacts on the buscoupler and I/O housings supply the voltage to the I/O modules when inserted together from left to right.

The ground (earth) contact makes first and breaks last conforming to electrical standards and can be used as protective grounding.

Depending on the I/O function, some modules do not have P.J.C.s. It is important to note this when assembling a node. Many modules require field side power, many do not. Please review the circuit diagrams of the individual modules. An additional power supply module may be necessary.

INTERBUS S / Buscoupler

Page 13 of the Quatech INTERBUS S user manual — Supply Voltage - Field Side
Page 13 · click to enlarge
Page 13

When using the supply module 750-601/602, the field supply from the bus coupler is interrupted. From that point a new power supply connection is necessary to provide DC to any additional I/O modules.

INTERBUS S / Buscoupler

Page 14 of the Quatech INTERBUS S user manual — Bus connection and station (node) address
Page 14 · click to enlarge
Page 14
Quatech INTERBUS S — Bus connection and station (node) address diagram (page 14)
Fig. 12 · Bus connection and station (node) address
Quatech INTERBUS S — Bus connection and station (node) address diagram (page 14)
Fig. 13 · Bus connection and station (node) address
Ill. 5Bus connection

Fieldbus connection:

The Interbus interface is normally provided by D SUB connection according to US Standard EIA RS485 for data transmission by wires.

Quatech INTERBUS S — Bus connection and station (node) address diagram (page 14)
Fig. 14 · Bus connection and station (node) address

PIN cable PIN Incoming D-SUB (IN) /DO 6 green 6 /DO DO 1 yellow 1 DO /DI 7 pink 7 /DI DI 2 gray 2 DI COM 3 brown 3 COM 5 commoning wire 9 commoning wire

Table 1Wire connection Interbus S

The connection point of the D SUB connector is lowered in such a way that after a connector is installed placement in an 80mm high switchbox is possible.

INTERBUS S / Buscoupler

Page 15 of the Quatech INTERBUS S user manual — Configuration Interface
Page 15 · click to enlarge
Page 15

The configuration interface used for the communication with WAGO-I/O-CHECK or for firmware upload is located behind the cover flap.

Fig. X-1Configuration interface g01xx06e

The communication cable (750-920) is connected to the 4-pole header.

INTERBUS 7a WAGO-I/O-SYSTEM 750

Configuration Interface · Configuration interface

Page 16 of the Quatech INTERBUS S user manual — SYSTEM DATA:
Page 16 · click to enlarge
Page 16
Quatech INTERBUS S — The Enclosure and Specifications diagram (page 16)
Fig. 15 · The Enclosure and Specifications
Quatech INTERBUS S — The Enclosure and Specifications diagram (page 16)
Fig. 16 · The Enclosure and Specifications

SYSTEM DATA:

Quatech INTERBUS S — SYSTEM DATA: diagram (page 16)
Fig. 17

750-304 750-324 Number of function modules 256 on request Number of I/O points 4096 on request Transmission medium shielded Cu-cable (5 x 0.25 mm²) max. bus length 400 m Baud rate 500 kBaud

INTEBUS S / Enclosure and specifications

Page 17 of the Quatech INTERBUS S user manual — TECHNICAL DATA:
Page 17 · click to enlarge
Page 17

TECHNICAL DATA:

750-324 digital Number of function modules 64 32 Digital peripheral signals 256 64 Analog peripheral signals 32 --- Configuration possibility via PC or control --- Bus connection 2 D-SUB with protection against vibration Voltage supply 24V DC (-15%/+20%) Input current 105 mA typ; 900 mA max. 85 mA typ.; 500 mA max. Internal current 400 mA 400 mA Power jumper contacts blade / spring contact slide contact, self-cleaning Maximum current supplied to K-Bus for internal module use

750-304 dig.+analog

1.75 A on request

Voltage power jumper contacts 24 V DC Current power jumper contacts 10A DC Data contacts slide contacts, 1.5 u hard gold-plated

self-cleaning Voltage drop via data contacts

marker cards 8 x 47mm Wire connection CAGE CLAMP; 0.08mm2 -2.5mm2 /AWG 28 -14 Mounting position any position Type of protection IP 20 Isolation 500 V system / power supply Operating temperature 0°C...+55°C Dimensions (mm) W x H x L 51 x 65* x 100 (*from upper edge of the carrier rail)

INTEBUS S / Enclosure and specifications

Page 18 of the Quatech INTERBUS S user manual — The Enclosure and Specifications
Page 18 · click to enlarge
Page 18
Quatech INTERBUS S — The Enclosure and Specifications diagram (page 18)
Fig. 18 · The Enclosure and Specifications

The Interbus S buscoupler with no. 750-304/000-001 has the possibility of extented diagnostic functions. The technical data is the same as 750-304. Different from the standard buscoupler, a word for diagnostic messages is put into the input data process image and a word for the control of the diagnostic input is put into the output data process image. The maximum number of input and output modules is reduced by the additional diagnostic function because Interbus S transmits only 31 words of a process image.

Order of the diagnostic status word:

Bit of the status word

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

error error code (s. table) Channel Module

The error code is shown in the following table:

Error code Description 0 unknown fault 5 defective fuse 10 broken wire 15 short circuit

Quatech INTERBUS S — The Enclosure and Specifications diagram (page 18)
Fig. 19 · The Enclosure and Specifications

Channel: This is the location for the fault input of a module. The counting is done in the same way as numbering channels. Module: This is the number of the module. Counting starts at the fieldbus coupler. The first module attached to the coupler is module 0.

The diagnostic control word is for diagnostic actions. E.g. error messages can be cleared in this way.

Order of the diagnostic control word:

Bit of the control word

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

The actions are coded as follows:

Actions Description 0x00 (0) no action 0x01 (1) Acknowledge diagnostic control word 0x80 (128) Clears all error messages in the buffer

Quatech INTERBUS S — The Enclosure and Specifications diagram (page 18)
Fig. 20 · The Enclosure and Specifications

INTEBUS S / Enclosure and specifications

Actions

Page 19 of the Quatech INTERBUS S user manual — 4.1 Master Cards (Scanners, Host Controllers)
Page 19 · click to enlarge
Page 19

4 INTERBUS S

The Interbus S system (DIN 19245 part 1.2) is set up as a data ring with a central master slave access procedure. All modules are understood as one logical module. Each partner receives data at its input and sends it to the next partner at its output. There is no addressing with a data frame because each partner knows by special control signals (CLOCK, RESET, SELECT, CONTROL) where it is placed in the ring. So there is no bus address. „Addressing“ is done via the physical place in the system.

Interbus S has the structure of a spatially distributed shift register. Each cycle is input and output at the same time. While the master gives output data to the shift register, it gets input data from the other end of the ring.

Each part of Interbus S has an ID register. This register keeps information about the type of module, the number of I/O registers and the status and error information.

Interbus S has two general operating modes:

1. ID cycle The interface module of all devices connected to the bus system reads out the ID register in the ID cycle and builds up the process image with the aid of this information. The cycle serves as an initialization and is carried out on request.
2. Data cycle Within the data cycle all input data from the registers is transferred from all devices into the master card (Host Controller) and all output data from the master card (Host controller) to the devices.

4.1 Master Cards (Scanners, Host Controllers)

The operation of the master is carried out in most cases via a central controller like a PLC, PC or NC. Connection to the remote stations is made via master cards.

Common master modules are:

- Phoenix IBS S5 DCB/I-T

- Phoenix IBS S5 DSC/I-T

- Phoenix 100 CB-T

- Hilscher CIF 30 (via Synergetic Micro Systems in USA)

INTERBUS S / Interbus S

Page 20 of the Quatech INTERBUS S user manual — - IBS SYS SWT
Page 20 · click to enlarge
Page 20

4.2 Configuration software

In order to make the connection between a PLC or PC and the remote stations, the master cards must be configured with the individual station data.

For this, the following software packages are available. For example, the following are available from Phoenix:

- IBS SYS SWT

- IBS CMD SWT

INTERBUS S / Interbus S

Page 21 of the Quatech INTERBUS S user manual — 5 Configuration of the fieldbus node in the master
Page 21 · click to enlarge
Page 21
Quatech INTERBUS S — Configuration of the fieldbus node in the master diagram (page 21)
Fig. 21 · Configuration of the fieldbus node in the master

5 Configuration of the fieldbus node in the master

5.1 Identification Code

In the ID cycle which is carried out for the initialization of the Interbus system, the users connected users are identified by their function and their byte length. The Interbus S coupler identifies its length after being started in the initialization phase of the bus modules and forms a corresponding ID code. To this effect each slave has an implemented identification register (ID register) comprising 2 bytes.

A 2 byte wide data unit is called a word. It enables the encoding of 65536 different states. In Interbus S, different types of users and data widths are called for the coding. This enables the master to find out what type the device belongs to, which means for example, recognizing either frequency inverters or I/O units, like the In Interbus S the manufacturers of device types are not recognized. The structure of the ID code is explained below as well as the significance of the individual bits of the ID code.

The length information can be coded from 0 to 32 words:

Quatech INTERBUS S — 5 Configuration of the fieldbus node in the master diagram (page 21)
Fig. 22 · 5 Configuration of the fieldbus node in the master

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

data direction I, O, I/O

Table 2Structure of the Interbus ID code

-In the ID registers, the device group is coded in the lowest value (LSB) 8 bits (ID 0 to 7). -In the following 5 bits (ID 8 to 12), the data width is coded. The 3 bits with the highest value (MSB) (ID 13 to 15) are used for management functions. Via these bits, dynamic fault messages are transferred during operation. These bits are not defined by the hardware.

INTERBUS S / Configuration

Page 22 of the Quatech INTERBUS S user manual — ID Code for WAGO I/O System
Page 22 · click to enlarge
Page 22
Quatech INTERBUS S — ID Code for WAGO I/O System diagram (page 22)
Fig. 23 · ID Code for WAGO I/O System

Due to the combined use of digital, analog and special functions on one fieldbus station and with the given structure of the Interbus ID codes, it is impossible to manage with one ID code. The WAGO Interbus S buscoupler is identified as a digital slave with variable length!

Quatech INTERBUS S — ID Code for WAGO I/O System diagram (page 22)
Fig. 24 · ID Code for WAGO I/O System

Inputs 1, 0x1 x 2, 0x2 x 3, 0x3 x x 49, 0x31 - x 50, 0x32 - x 51, 0x33 - - x x [x]: ID code given []: is not possible [-]: when mixed with digital Table 3: ID codes for the WAGO Interbus S buscoupler

For the master, it is important to know how many data registers each user assigns in the Interbus S system. If a user has, for example, 16 bits of input and 32 bits of output, he assigns 2 words in the bus because there are 2 words of output. In this case the higher value of data width is decisive. The data width is coded by the bits ID 8 to ID 12 as shown in section 5.1. The following table shows the register widths depending on the function modules connected to a WAGO Interbus S buscoupler. Possible values for data length are::

Data length Buscoupler Remarks 0 Words x 1 Nibble Busmaster supports only Generation 4. 1 Byte Starting with SPS-Firmware 3.20 or PC-driver 2.0 3 Nibble Busmaster supports only Generation 4 1 Word x 3 Nibble Busmaster supports only Generation 4 3 Byte Starting with SPS-Firmware 3.20 or PC-driver 2.0 2 Words x 5 Nibble Busmaster supports only Generation 4 5 Byte Starting with SPS-Firmware 3.20 or PC-driver 2.0 3 Words x 4 Words x 5 Words x 6 Words x, ab WF Starting with SPS-Firmware 3.20 or PC-driver 2.0 7 Words x, ab WF Starting with SPS-Firmware 3.20 or PC-driver 2.0 8 Words x 9 Words x 10 Words xx Starting with SPS-Firmware 3.20 or PC-driver 2.0 12 Words xx Starting with SPS-Firmware 3.20 or PC-driver 2.0 14 Words xx Starting with SPS-Firmware 3.20 or PC-driver 2.0 16 Words xx Starting with SPS-Firmware 3.20 or PC-driver 2.0 24 Words xx Starting with SPS-Firmware 3.20 or PC-driver 2.0 32 Words xx Starting with SPS-Firmware 3.20 or PC-driver 2.0 [x]: is used [xx]: is used and firmware 3.20 or PC driver 2.0 or later is combined

INTERBUS S / Configuration

Page 23 of the Quatech INTERBUS S user manual — 5.3.1 CMD Software Package
Page 23 · click to enlarge
Page 23

5.3 IBS CMD configuration software

In the following chapter the configuration package IBS CMD configuration software is presented in short form. This procedure facilitates operation of the WAGO Interbus buscoupler.

Further and specific information is given in the respective operating instructions of the different software packages.

5.3.1 CMD Software Package

Please pay attention that the corresponding interfacing and the function extended should be selected.

The following menu is obtained via the key OK and the password allocated at the program installation.

Quatech INTERBUS S — 5.3.1 CMD Software Package diagram (page 23)
Fig. 25 · 5.3.1 CMD Software Package
Ill. 10First menu configuration

This is the first menu for further configuration. From this point the configuration can be made automatically or manually.

INTERBUS S / Configuration

Page 24 of the Quatech INTERBUS S user manual — IBS CMD configuration software
Page 24 · click to enlarge
Page 24
1. Automatic configuration
Quatech INTERBUS S — IBS CMD configuration software diagram (page 24)
Fig. 26 · IBS CMD configuration software
Ill. 11Automatic configuration

If the complete fieldbus system with all stations and the master interface is operational, automatic configuration of the connected stations can be called up via the menu „bus structure“. Then the communications are started automatically and the configuration is determined and set.

INTERBUS S / Configuration

Page 25 of the Quatech INTERBUS S user manual — IBS CMD configuration software
Page 25 · click to enlarge
Page 25
2. Ident code
Quatech INTERBUS S — IBS CMD configuration software diagram (page 25)
Fig. 27 · IBS CMD configuration software
Ill. 12Insertion of the WAGO I/O System via the Ident code

For manual configuration, the menu item „bus structure“ in the configuration screen must be selected. You will then see Ill. 12.

The corresponding ID code of table 3 and the length of the process data channel must be indicated in the selected submenu. The length is dependent on the module with the largest data length.

INTERBUS S / Configuration

Page 26 of the Quatech INTERBUS S user manual — IBS CMD configuration software
Page 26 · click to enlarge
Page 26
Quatech INTERBUS S — IBS CMD configuration software diagram (page 26)
Fig. 28 · IBS CMD configuration software
Ill. 13Insertion of the ID code and the data length

With the finalization of the entries via the key OK, a menu for the definition of the user will appear.

INTERBUS S / Configuration

Page 27 of the Quatech INTERBUS S user manual — IBS CMD configuration software
Page 27 · click to enlarge
Page 27
Quatech INTERBUS S — IBS CMD configuration software diagram (page 27)
Fig. 29 · IBS CMD configuration software
Ill. 14Description of user

INTERBUS S / Configuration

Page 28 of the Quatech INTERBUS S user manual — IBS CMD configuration software
Page 28 · click to enlarge
Page 28

After all data has been entered and stored via OK, the station created with the WAGO Interbus coupler is then integrated into the fieldbus system being set up.

This station is displayed via the bus structure that has now been integrated:

Quatech INTERBUS S — IBS CMD configuration software diagram (page 28)
Fig. 30 · IBS CMD configuration software

INTERBUS S / Configuration

Page 29 of the Quatech INTERBUS S user manual — Example of an application
Page 29 · click to enlarge
Page 29
Quatech INTERBUS S — Example of an application diagram (page 29)
Fig. 31 · Example of an application
Quatech INTERBUS S — Example of an application diagram (page 29)
Fig. 32 · Example of an application
Ill. 19Example of an application

The Interbus S station is composed as follows:

Function module Process image inputs Process image outputs 1; Digital input PI 32.0 1; Digital Input PI 32.1 2; Digital Input PI 32.2 2; Digital Input PI 32.3 3; Voltage supply 4; Analog Input PI 20 4; Analog Input PI 22 5; Voltage supply 6; Digital Output PI28.0 6; Digital Output PI28.1 7; Digital Output PI28.2 7; Digital Output PI28.3 8; Digital Output PI28.4 8; Digital Output PI28.5 9; Digital Output PI28.6 9; Digital Output PI28.7 10; Voltage supply 11; Analog Output PI 20 11; Analog Output PI 22 12; Analog Input PI 24 12; Analog Input PI 26 13; Analog Output PI 24 13; Analog Output PI 26 14; Analog Input PI 28 14; Analog Input PI 30 15; Voltage supply 16; Digital Output PI29.0 16; Digital Output PI29.1 17; End module Table 5: Assignment of the process image

INTERBUS S / Configuration

Page 30 of the Quatech INTERBUS S user manual — Example of an application
Page 30 · click to enlarge
Page 30

The addresses indicated in the table results from the master configuration started in the basic address. By the internal structure of the Interbus coupler, the process image is divided as follows:

O0 Output data word orientated data Ox Ox+1 bit orientated data Ox+y

I0 Input data word orientated data Ix Ix+1 bit orientated data Ix+y

Due to this division, the first addresses allocated in the configuration are reserved for the analog inputs and outputs. The counting direction is from left to right and starts with the first analog channel next to the bus coupler.

Quatech INTERBUS S — Example of an application diagram (page 30)
Fig. 33 · Example of an application
Ill. 21Definition inputs/outputs

INTERBUS S / Configuration

Page 31 of the Quatech INTERBUS S user manual — Buscoupler startup and troubleshooting
Page 31 · click to enlarge
Page 31
Quatech INTERBUS S — Buscoupler startup and troubleshooting diagram (page 31)
Fig. 34 · Buscoupler startup and troubleshooting

After configuration of the master connection and electrical installation of the fieldbus node/station, operation of the system can begin.

After power to the Buscoupler and I/O modules has been applied, the Buscoupler verifies all internal functions, components and the communication interface by an internal diagnostic routine. Then the function modules and the existing configuration is determined. At the same time a hidden file is stored. It consists of an input and an output area which is located on the fieldbus RAM of the log chip. During the power up phase the ‘I/O ERR’ LED flashes with an increased frequency. After a faultless power up the fieldbus coupler enters the state ‘fieldbus start’. The green LED ‘RUN’ indicates that the Bus is operating normally. In case of a fault the red ‘I/O ERR’ LED will continue flashing. By counting the number and frequency of flashes the fault can be easily identified quickly and accurately. A varying number of flashes and frequencies defines the fault. The table below describes the fault condition based on the counted number of ‘I/O ERR’ LED flashes.

Quatech INTERBUS S — Buscoupler startup and troubleshooting diagram (page 31)
Fig. 35 · Buscoupler startup and troubleshooting

N (N>0) error in comparison of tables: module N (programmed configuration), passive modules like supply terminal blocks do not count

3 0 modules have identified error in fieldbus commands

4 0 data error on fieldbus or fieldbus break at the coupler

5 N filedbus error in register communications with module N

N (0<N<65) error in 1st configuration byte Table 5: Diagnosis LEDs - on buscoupler

INTERBUS S / Startup

Page 32 of the Quatech INTERBUS S user manual — Buscoupler startup and troubleshooting
Page 32 · click to enlarge
Page 32

After elimination of the fault, the buscoupler can only be set to the normal working condition by another POWER ON sequence. The green I/O LED flashes when accessing the I/O modules internal data channels. After being switched on, the buscoupler queries the configuration of the bus modules but does not carry out a data exchange with the I/O modules. This means that the red I/O LED will extinguish after a faultless startup. The green I/O LED will indicate when data is being exchanged by the Interbus network.

Status and error diagnostics:

The fieldbus LEDs show the state of the bus system. The functions of Interbus S are shown by the LEDs „READY“, „BA“, „RC“ and „RD“.

Quatech INTERBUS S — Buscoupler startup and troubleshooting diagram (page 32)
Fig. 36 · Buscoupler startup and troubleshooting

on off off on Field bus off error in cable or master

search error in cable or master off no function ; no voltage

Table 7Diagnostic LEDs - fieldbus

INTERBUS S / Startup

Page 33 of the Quatech INTERBUS S user manual — 7.2 Mechanical and climatic conditions
Page 33 · click to enlarge
Page 33

7 General conditions

This chapter describes the general conditions for error-free running of the

7.1 Transporting and storing conditions

The following declarations concern modules which are transported and stored in the original package.

Condition allowed values Free fall ≤ 1m Temperature -40° to +70° C Relative humidity 5 to 95% (without condensation)

7.2 Mechanical and climatic conditions

The modules of the are not allowed to be operated without taking suitable actions - in places with strong conditions e.g. very dusty rooms or corroding atmosphere - in place with high concentrations of ionisation

The temperature should be in a range between 0° C and +55° C. The relative humidity should be in a range of 5 to 95% (without condensation). The modules should be placed horizontal for better heat dissipation.

The concentration of SO2 must be below 25 ppm with a relative humidity of < 75%. The concentration of H2S must be below 10 ppm with the same humidity.

The mechanical conditions are given as sinusoidal oscillations.

Frequency range (Hz) continuous sometimes 10 ≤ f < 57 0.0375 mm amplitude 0.075mm amplitude 57 ≤ f ≤ 150 0.5 g constant acceleration 1 g constant acceleration

For stronger impulses and oscillations, the acceleration and the amplitude should be reduced by suitable actions. The following table shows the type of test for the mechanical conditions.

INTERBUS / General conditions

Page 34 of the Quatech INTERBUS S user manual — 7.3 Class of protection and degree of protection
Page 34 · click to enlarge
Page 34

Test for Test sequence Remarks Oscillations Test for oscillations IEC 68, part 2-6

Type of oscillation: sweep with a rate of change of 1 octave per minute 10 Hz ≤ f < 57 Hz, const. amplitude 0,075mm 57 Hz ≤ f ≤ 150 Hz, const. acceleration 1 g period of oscillation: 10 sweep per axis in each of the 3 vertical axes Impulse Test for impulses IEC 68, part 2-27

Type of impulse: half sinusoidal Intensity of impulses: 15 g peak value, 11 ms maintenance time route of impulses: 2 impulses in each of the 3 vertical axes

7.3 Class of protection and degree of protection

The class of protection is IP2X (IEC 529), i.e. protection against touch with a standard test object. There is also protection against solid bodies greater than 12 mm. There is no special protection against water.

INTERBUS / General conditions

Page 35 of the Quatech INTERBUS S user manual — 7.6 Certificates
Page 35 · click to enlarge
Page 35

7.4 Electromagnetic compatibility

Method of measurement Disturbance Interference with narrow-band conducted disturbance

EN 50082-2, A

Interference with impulse groups EN 50082-2, B Discharge of static electricity EN 50082-2, B Interference with electromagnetic fields EN 50082-2, A Interference field strength EN 55011

These requests for electromagnetic compatibility are fulfilled by all modules of (except for 750-630 and 750-631).

7.5 Power supply

If non-stabilized power supply is used for the supply of the buscoupler, it must be stabilized by a capacity ( 200 µF per 1 A load current). For the a filter module has been developed (288-824). This module serves as a filter module for non-stabilized 24 V DC power supplies if the specified voltage deviation is not met. Reasons for the deviations may be voltage jumps in the primary circuit, overloads in the secondary circuit or the switching of undampened inductances and capacitances.

7.6 Certificates

The modules of have passed the conformance test of UL. Look for listing mark on product. The Profibus coupler 750-301 and 750-303 are certified of PNO with Z00241 and Z00242. The Interbus coupler 750-304 has passed the relevant tests in accordance with the Interbus conformance requirements (number 111). The DeviceNet coupler 750-306 has succesfully passed through the conformance test of Open DeviceNet Vendors Association Europe.

INTERBUS / General conditions

Page 36 of the Quatech INTERBUS S user manual — Technical description
Page 36 · click to enlarge
Page 36
Quatech INTERBUS S — Digital Inputs diagram (page 36)
Fig. 37 · Digital Inputs

Digital Inputs (24 V AC/DC, 120 V AC, 230 V AC, 48 V DC) PN: 750-400...415

Quatech INTERBUS S — Digital Inputs diagram (page 36)
Fig. 38 · Digital Inputs
Quatech INTERBUS S — Digital Inputs diagram (page 36)
Fig. 39 · Digital Inputs

Technical description

The supply is applied by a series-connected termination to each I/O module for the respective operating voltage. Power connections are made automatically from module to module when snapped onto the DIN rail. Attention: The lowest power jumper contact is not carried out for some modules (e.g. 4-channel)! A module which needs all contacts (e.g. 2 channel digital) may not be connected to the right hand side of modules which do not have 3 power jumper contacts (e.g. 4 channel modules). All 2-channel digital inputs are 4-conductor devices allowing the direct connection of 4- conductor sensors with the terminations V+, 0V, ground and signal. The 4-channel digital inputs are suitable for the direct connection of two 3-conductor sensors (V+, 0V, signal). The power distribution module 750-614 is available for the connection of more sensors to V+ and 0V. The modules 750-408 and 750-409 are low-side switching. A 2-wire proximity switch can be connected to the modules 750-410 and 750-411. RC filters are series-connected to the 5, 24 and 48 V versions for noise rejection and switch debouncing. They are available with time constants of 3.0 ms and 0.2 ms. The standard numerical assignment for bus operations is from left to right, starting with the LSB. The positions of the different I/O modules in the configured node/station are selectable by the user. A block type configuration is not necessary. The Input module can be connected to all buscouplers of the WAGOÇI/OÇSYSTEM.

Digital Inputs 750-400...415

Page 37 of the Quatech INTERBUS S user manual — 79 V...1.1 U N AC
Page 37 · click to enlarge
Page 37

Technical Data:

Item Number 750- 400 401 402 403 Number of inputs 2 4 Input filter 3 ms 0.2 ms 3 ms 0.2 ms Nominal voltage 24V DC (-15%/+20%) Signal voltage (0) -3V...+5V DC (std. EN 61131 Typ 1) Signal voltage (1) 15V...30V DC (std. EN 61131 Typ 1) Input current (internal) 2.5 mA max. 5 mA max. Input current (field side) 5 mA typ. Isolation 500 V system/power supply Internal bit width 2 4 Configuration no address or configutation adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 to 2.5mm2

Dimensions (mm) WxHxL 12 x 64* x 100 (*from upper edge of carrier rail)

Item Number 750- 405 406 410* 411* Number of inputs 2 2 Input filter 10 ms 3 ms 0.2 ms Nominal voltage 230 V AC (-15%/+10%)

120 V AC (- 15%/+10%)

24V DC (-15%/+20%))

Signal voltage (0) 0 V...40 V AC

0 V..20 V AC

-3 V ... +5 V DC (std.

EN 61131 Type 2) Signal voltage (1) 79 V...1.1 UN AC

11 V ... 30 V DC (std. EN 61131 Type 2) Input current (internal) 2 mA 2.5 mA max. Input current (field side) 6.5 mA typ. 4.5 mA typ. 8 mA typ. Isolation 4 kV system/power supply 500 V system/power supply Internal bit width 2 Configuration no address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 to 2.5mm2

79 V...1.1 U N AC

Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail)

*) 2 - wire proximity switch, current without load max. 2 mA

Digital Inputs 750-400...415

Page 38 of the Quatech INTERBUS S user manual — Digital Inputs
Page 38 · click to enlarge
Page 38

Item Number 750- 408 409 412 413 Number of inputs 4 2 Input filter 3 ms 0,2 ms 3 ms 0,2 ms Nominal voltage 24V DC (-15% / +20%) 48 V DC (-15% / +20%) Signal voltage (0) 15 V...30 V DC -6 V ... +10 V DC Signal voltage (1) -3 V...5 V DC 34 V ... 60 V DC Input current (internal) 10 mA max. 5 mA max. Input current (field side) 3.5 mA typ. Isolation 500 V system/power supply Internal bit width 4 2 Configuration no address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0,08 to 2,5 mm2

Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail)

Item Number 750- 414 415 Number of inputs 4 4 Input filter / Conversion time

0.2 ms 20 ms

Nominal voltage 5 V DC 24 V AC/DC (-15%/+20%) Signal voltage (0) 0...0.8 V DC -3...+5 V DC

0...+5 V AC Signal voltage (1) 2.4 V...5 V DC 11 ... 30 V DC 10 ... 27 V AC Input current (internal) 5 mA 10 mA Input current (field side) 50 µA typ. 7.5 mA DC 7.6 9.5 mA AC Isolation 500 V system/power supply 500V system/power supply 50 V channel/channel Internal bit width 4 4 Configuration no address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0,08 to 2,5 mm2

Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail)

Digital Inputs 750-400...415

Page 39 of the Quatech INTERBUS S user manual — Technical Description:
Page 39 · click to enlarge
Page 39
Quatech INTERBUS S — 750-404 diagram (page 39)
Fig. 40

Counter modules PN 750-404, 750-404/000-001, 750-404/000-002 750-404/000-003, 750-404/000-004 Up/Down Counter 100 kHz, 750-404

Technical Description:

The described configuration is counter with up/down input.

The following description is preliminary and is applicable to the factory configuration.

The counter module is able to run with all WAGOÇI/OÇSYSTEM bus-couplers (except for the economy type).

Counter Module 750-404 1

:$*2⇓,2⇓6<67(0

Page 40 of the Quatech INTERBUS S user manual — 750-404
Page 40 · click to enlarge
Page 40
Quatech INTERBUS S — 750-404 diagram (page 40)
Fig. 41
Item Number750404, 404/000-001 404/000-004 404/000-002

Number of outputs 2 Output current 0.5 A Number of counter 1 Input current (internal) 70 mA Nominal voltage 24 V DC (-15% +20%) Signal voltage (0) -3V +5V DC Signal voltage (1) +15V...+30V DC Switching rate 100 kHz 10 kHz max. Output current 5 mA typ. Counter size 32 Bit Isolation 500 V system/power supply Bit width 32 Bit (8 Bit verification; 8 bit not used) Configuration none, optional with software parameter Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 to 2.5mm2

Size (mm)WxHxD 12 x 64* x 100 (*from upper edge of the carrier rail)

Counter Module 750-404 2

:$*2⇓,2⇓6<67(0

Page 41 of the Quatech INTERBUS S user manual — 750-404
Page 41 · click to enlarge
Page 41
Quatech INTERBUS S — 750-404 diagram (page 41)
Fig. 42

The counter begins processing with pulses at the CLOCK input. The changes from 0 V to 24 V are counted.

The counter counts up, if the input U/D is set at 24 V. With an open circuit input or 0 V the counter counts backwards.

The two bottom contacts each include another output. These outputs are activated through bits in the control byte.

The control byte has the following bits:

Quatech INTERBUS S — 750-404 diagram (page 41)
Fig. 43

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

0 x Set Counter Block Counter Output value at output O2

The status byte has the following bits:

Quatech INTERBUS S — 750-404 diagram (page 41)
Fig. 44

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

With the control and status-byte the following tasks are possible:

Set the counter: Put Bit 5 into the control byte. The counter with the 32 bit value is loaded into output bytes 0-3. As long as the bits are set, the counter can stop and information is stored. The ensuing data of the counter will be conveyed to the status byte.

Blocking the counter: Bit 4 is set into the control byte, then the count process is suppressed. Bit 4 in the status byte communicates the suppression of the counter.

Set the outputs: Bits 2 and 3 set the additional two outputs of the counter module.

The result of the counter is in binary.

Counter Module 750-404 3

:$*2⇓,2⇓6<67(0

Page 42 of the Quatech INTERBUS S user manual — An example:
Page 42 · click to enlarge
Page 42

An example:

The counter is set with “Set Counter” to the value 0x0000.0000 - 0X1X.XXXX, 0x00, 0x00, 0x00, 0x00 are carried over as output value

(carry over the control-byte and the new counter position), -wait until the input value is 0X1X.XXXX, 0x00, 0x00, 0x00, 0x00

(the status-byte shows the loading feedback) , -carry over 0x00, 0x00 as output value (release counter). Wait for the first and further counting pulse -the input value is XX00.XXXX, 0x00, 0x00, 0x00, 0x00 (no counting pulse received) -the input value is XX00.XXXX, 0x00, 0x00, 0x00, 0x01 (1 counting pulse received) -the input value is XX00.XXXX, 0x00, 0x00, 0x00, 0x02 (2 counting pulses received) - -the input value is XX00.XXXX, 0xFF, 0xFF, 0xFF, 0xFF (maximum counting position is reached) -the input value is XX00.XXXX, 0x00, 0x00, 0x00, 0x00 (a further counting pulse causes an overflow) -the input value is XX00.XXXX, 0x00, 0x00, 0x00 0x01, (a further counting pulse is received)

Counter Module 750-404 4

:$*2⇓,2⇓6<67(0

Page 43 of the Quatech INTERBUS S user manual — 750-404
Page 43 · click to enlarge
Page 43
Quatech INTERBUS S — 750-404 diagram (page 43)
Fig. 45
Quatech INTERBUS S — 750-404 diagram (page 43)
Fig. 46

The counter module also can be ordered as counter with enable input (750-404/000- 001).

The counter begins processing with pulses at the CLOCK input. The changes from 0 V to 24 V are counted. The counter counts down if the input U/D is set at 24 V. With an open circuit input or 0 V the counter counts up.

The data format of the module is 4 bytes data and a control/status byte. The module is a 32 Bit counter. The ID Code os 180 (0xB4). The format of input and output data is the same as 750-404.

The counter module is able to run with all WAGOÇI/OÇSYSTEM bus-couplers (except for the economy type).

Counter Module 750-404 5

:$*2⇓,2⇓6<67(0

Page 44 of the Quatech INTERBUS S user manual — 750-404
Page 44 · click to enlarge
Page 44
Quatech INTERBUS S — 750-404 diagram (page 44)
Fig. 47
Quatech INTERBUS S — 750-404 diagram (page 44)
Fig. 48

The counter module also can be ordered as peak time counter with 750-404/000-002.

This description is only intended for hardware version X 0 0 0 1-. The serial number can be found on the right side of the module.

The counter begins processing with pulses at the CLOCK input. The changes from 0 V to 24 V are counted. The counter counts up if the input U/D is set at 24 V. With an open circuit input or 0 V the counter counts backwards.

The two bottom contacts each include another output. These outputs are activated through bits in the control byte.

The counter module is able to run with all WAGOÇI/OÇSYSTEM bus-couplers (except for the economy type).

Counter Module 750-404 6

:$*2⇓,2⇓6<67(0

Page 45 of the Quatech INTERBUS S user manual — 750-404
Page 45 · click to enlarge
Page 45
Quatech INTERBUS S — 750-404 diagram (page 45)
Fig. 49

The counter begins processing with pulses at the CLOCK input for a special time span. The time span is predefined as 10 s. The state of the counter is stored in the processs image until the next period. After the recording the counting starts again at 0.

The activation of the counting and the synchronisation with the SPS is made by a handshake in the control and status byte.

The end of thre counting period and thus the new process data is signaled by a toggel bit in the status byte.

The control byte has the following bits:

Quatech INTERBUS S — 750-404 diagram (page 45)
Fig. 50

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

The status byte has the following bits:

Quatech INTERBUS S — 750-404 diagram (page 45)
Fig. 51

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Counter Module 750-404 7

:$*2⇓,2⇓6<67(0

Page 46 of the Quatech INTERBUS S user manual — Technical Description
Page 46 · click to enlarge
Page 46
Quatech INTERBUS S — 750-404 diagram (page 46)
Fig. 52
Quatech INTERBUS S — 750-404 diagram (page 46)
Fig. 53

Technical Description

The counter module 750-404/000-003 measures the period of the 24 V DC input signal at the CLOCK terminal and converts it into a corresponding frequency value. The measurement is enabled if the GATE terminal is an open circuit input or 0V. To disable processing, the GATE input is to be set to 24 V DC.

The terminals O1 and O2 work as binary outputs. Each output can be activated via specific bits in the CONTROL byte.

The high states of the input and output channels are each indicated by a LED. To recognize low frequency or near zero frequency signals, the maximum time between two data updates is parameterizable.

Counter Module 750-404 8

:$*2⇓,2⇓6<67(0

Status CLOCK · power jumper contacts

Page 47 of the Quatech INTERBUS S user manual — Technical Data:
Page 47 · click to enlarge
Page 47

Technical Data:

Item-No.: 750- 404/000-003 Supply Voltage 24V DC (-15%/+20%) Input Voltage (low) -3V - 5V DC Input Voltage (high) 15V - 30V DC Input Current 5mA typ. at 24V DC Min. Pulse Width 10µs Output Current 0.5A (short circuit protection) Voltage Drop 0.6V DC max. at 0.5A Frequency Range: Integration time = 1 period 0.1 - 100Hz, Resolution 0.001Hz Integration time = 4 periods 1 - 1,000Hz, Resolution 0.01Hz Integration time = 16 periods 10 - 10,000Hz, Resolution 0.1Hz (1Hz) Measuring Error: Range 0.1 - 100 Hz < ± 0.05% Range 1 - 1000Hz < ± 0.05 % Range 10 - 10000Hz < ± 0.2 % Data Format: Process Image 5 Byte In- and Output Internal Bit Width 8 Bit CONTROL/STATUS + 32 Bit DATA Input Current (internal) 80mA max. at 5V DC Operating Temperature 0°C +55°C Wire Connection CAGE CLAMP; 0.08 to 2.5mm2

Size (mm) WxHxD 12 x 64* x 100 (*from upper edge of carrier rail)

Frequency Range: Integration time = 1 period 0.1 - 8,000Hz, Resolution 0.001Hz Integration time = 4 periods 0.25 - 32,000Hz, Resolution 0.01Hz Integration time = 16 periods 1 - 100,000Hz, Resolution 0.1Hz (1Hz) Measuring Error: Range 0.1 - 8000Hz < ± 1% Range 0.25 - 32000Hz < ± 1.5 % Range 1 - 100000Hz < ± 1.5 %

Counter Module 750-404 9

:$*2⇓,2⇓6<67(0

Page 48 of the Quatech INTERBUS S user manual — 750-404
Page 48 · click to enlarge
Page 48
Quatech INTERBUS S — 750-404 diagram (page 48)
Fig. 54

The counter module acquires the time between one or more rising edges of the CLOCK input signal and calculates the frequency of the applied signal. The calculation and process image update are initiated every 1st, every 4th or every 16th

rising edge depending on the integration time selected via the CONTROL byte. The first detection of a rising edge starts the cyclic period measurement and cannot provide a valid frequency value. In this case the module will send 0xFFFFFFFFH for input information. The same input value is returned when a static high or static low signal is applied to the CLOCK input. If there are no signal changes seen at the CLOCK input, the module can be forced to update the process image after defined parameterizable time spans. In this state the module will send the non valid value 0xFFFFFFFFH too. The following figures illustrate a process data cycle.

Quatech INTERBUS S — 750-404 diagram (page 48)
Fig. 55
Figure 2Timing diagram for process data update sequence

(integration time = 1 period)

Quatech INTERBUS S — 750-404 diagram (page 48)
Fig. 56
Figure 3Timing diagram for process data update sequence

(integration time = 4 periods)

Counter Module 750-404 10

:$*2⇓,2⇓6<67(0

Page 49 of the Quatech INTERBUS S user manual — 750-404
Page 49 · click to enlarge
Page 49
Quatech INTERBUS S — 750-404 diagram (page 49)
Fig. 57
Quatech INTERBUS S — 750-404 diagram (page 49)
Fig. 58

E 5(*B5(4 79'5(4 6(7B4 6(7B4 5$1*(B6(/ 5(4 5$1*(B6(/ 5(4 5(*B5(4 15':5 5(*B$

Quatech INTERBUS S — 750-404 diagram (page 49)
Fig. 59

5(*B5(4 $FFHVVWRWKHUHJLVWHUVWUXFWXUHLVUHTXHVWHGEEFRQWDLQWKHDGGUHVVRIWKHUHJLVWHU 5(*B$$ 5HJLVWHUDGGUHVV 79'5(4 5HTXHVWWRFKDQJHWKHPD[LPXPWLPHZLWKRXWYDOLGGDWD 6(7B4 &RQWURO2XWSXW4 4RII 4RQ 6(7B4 &RQWURO2XWSXW4 4RII 4RQ 5$1*(B6(/5(4 6HOHFWLRQRIWKHLQWHJUDWLRQWLPHDQGWKHUHSUHVHQWDWLRQRIPHDVXUHGIUHTXHQF\YDOXH 5$1*(B6(/5(4 6HOHFWLRQRIWKHLQWHJUDWLRQWLPHDQGWKHUHSUHVHQWDWLRQRIPHDVXUHGIUHTXHQF\YDOXH

Quatech INTERBUS S — 750-404 diagram (page 49)
Fig. 60

E 5(*B$&. 67B*$7( 79'$&. 67B4 67B4 5$1*(B6(/ $&.

5$1*(B6(/ $&. 5(*B$&. 5(*B$

Quatech INTERBUS S — 750-404 diagram (page 49)
Fig. 61

5(*B$&. $FNQRZOHGJPHQWWRWKHUHJLVWHUUHTXHVWEEFRQWDLQWKHDGGUHVVRIWKHUHJLVWHU 5(*B$$ 5HJLVWHUDGGUHVV 67B*$7( 6WDWHRI*$7(LQSXW HQDEOHG GLVDEOHG 79'$&. $FNQRZOHGJPHQW79'FKDQJHG 67B$ 6WDWHRIRXWSXW4 67B$ 6WDWHRIRXWSXW4 5$1*(B6(/$&. $FNQRZOHGJPHQWWR5DQJH6HOHFWLRQ)UHTXHQF\YDOXHVDUHYDOLG 5$1*(B6(/$&. $FNQRZOHGJPHQWWR5DQJH6HOHFWLRQ)UHTXHQF\YDOXHVDUHYDOLG

CONTROL Byte · STATUS Byte · Counter 750-404

Page 50 of the Quatech INTERBUS S user manual — T Dmax = 2 *
Page 50 · click to enlarge
Page 50

Structure of Input and Output data

The input data contain the CLOCK frequency as a binary value. The representation depends on the RANGE_SEL bits in the CONTROL byte. Even the method of measuring is selected via these bits. The following table illustrates the different modes.

5$1*(B6(/ 5$1*(B6(/ 0HWKRGRIPHDVXUHPHQW 5HSUHVHQWDWLRQRIPHDVXULQJYDOXH

,QWHJUDWLRQRYHUSHULRG )UHTXHQF\LQ+] ,QWHJUDWLRQRYHUSHULRGV )UHTXHQF\LQ+] ,QWHJUDWLRQRYHUSHULRGV )UHTXHQF\LQ+] ,QWHJUDWLRQRYHUSHULRGV )UHTXHQF\LQ+]

number of periods to be integrated

T Dmax = 2 *

If the gate is enabled the input data contains the last valid frequency value. In this state the application cannot request a new range.

The valid frequency range stretches from 0.1 Hz (100D) up to 10 kHz (100000D). To recognize static CLOCK signals, a watchdog timer is implemented. The default value for the timer is 10s. The timer resets on every Power On. The application is able to change the watchdog time during operation by using the CONTROL byte. This can be initiated by writing the corresponding value into the output bytes OUTPUT_DATA 1 and OUTPUT_DATA 0 before setting the TVD REQ bit in the CONTROL byte. The success of the parameter transfer is acknowledged by the module via the TVD ACK bit in the STATUS information.

Attention: The range of the watchdog timer stretches from 0 to 16383ms (0x0000H to 0x3FFFH) in steps of 1ms per digit. Values which raise the permitted range of the watchdog timer are masked with 0x3FFF. If the maximum possible frequency of the different ranges is raised (see the table with maximum frequency ratings), the module will return the non valid data 0xFFFFFFFFH.

actual frequency · Counter 750-404

Page 51 of the Quatech INTERBUS S user manual — 750-404
Page 51 · click to enlarge
Page 51
Quatech INTERBUS S — 750-404 diagram (page 51)
Fig. 62

Output value of the control unit:

Byte Identification D15-D0 Control Byte Output Byte 1 D31-D16 Output Byte 0 Output Byte 3 D47-D32 Output Byte 2

Quatech INTERBUS S — 750-404 diagram (page 51)
Fig. 63

Input value of the control unit:

Quatech INTERBUS S — 750-404 diagram (page 51)
Fig. 64

Byte Identification D15-D0 Status Byte Input Byte 1 D31-D16 Input Byte 0 Input Byte 3 D2D47-D32 Input Byte 2

The input-bytes 0 to 3 form the 32 bit counter-output. In the output-bytes 0 to 3 the initial value of the counter can be set.

Counter 750-404

Page 52 of the Quatech INTERBUS S user manual — Digital Outputs
Page 52 · click to enlarge
Page 52
Quatech INTERBUS S — Digital Outputs diagram (page 52)
Fig. 65 · Digital Outputs

The power supply is provided by a series-connected supply module for the respective operating voltage. Power connections are made automatically from module to module via the internal P.J.C.s when snapped onto the DIN rail. Attention: The lowest power jumper contact is not carried out for some modules (e.g. 4-channel)! A module which needs all contacts (e.g. 2 channel digital) may not be connected to the right hand side of modules which do not have 3 power jumper contacts (e.g. 4 channel modules). For the digital outputs (without diagnostic) four-conductor devices (V+; 0 V; signal; ground) are standard. In case of 12 mm wide 4-channel digital output modules it is not possible to use 4-conductor devices. 4 signal outputs, 2xV+ and 2x0V are provided. All digital outputs are short-circuit protected. In case of overloads a supply module with fuse (750-601) must be connected on the line side to protect the output modules. The module 750-516 is low-side switching. The indicated output values have been determined for 100% duty cycle. However, in case of the 2 A versions it is possible to operate single channels at higher load currents, however always verify that the total current does not exceed 3.5 A per module. Example: 2x2A (standard); 1x3.0A; 1x0.5A (total current: 3.5 A) The standard numerical assignment for bus operations is from left to right, starting with the LSB. The positions of the different I/O modules in the configured node/station are selectable by the user. A block type configuration is not necessary.The Output module can be connected to all buscouplers of the WAGOÇI/OÇSYSTEM.

Digital Outputs 750-501...504,516, 519

Page 53 of the Quatech INTERBUS S user manual — Digital Outputs
Page 53 · click to enlarge
Page 53
Quatech INTERBUS S — Digital Outputs diagram (page 53)
Fig. 66 · Digital Outputs

Item Number 750- 501 502 Number of outputs 2 Kind of load resistive, inductive, lamps Nominal voltage 24V DC (-15% / +20%) Output current (DC) 0,5 A 2 A Current consumption (internal)

Quatech INTERBUS S — Digital Outputs diagram (page 53)
Fig. 67 · Digital Outputs

Isolation 500 V system / power supply Internal bit width 2 Configuration without address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0,08 to 2,5mm2

Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail)

Quatech INTERBUS S — Digital Outputs diagram (page 53)
Fig. 68 · Digital Outputs

Item Number 750- 504 516*) Number of outputs 4 Kind of load resistive, inductive, lamps Nominal voltage 24V DC (-15% / +20%) Output current (DC) 0,5 A Current consumption (internal)

Isolation 500 V system / power supply Internal bit width 4 Configuration without address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0,08 to 2,5mm2

Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail) *) low-side switching Item Number 750- 519 Number of outputs 4 Kind of load resistive, inductive, lamps Nominal voltage 5 V DC Output current (DC) 20 mA Current consumption (internal)

Quatech INTERBUS S — Digital Outputs diagram (page 53)
Fig. 69 · Digital Outputs

Isolation 500 V system / power supply Internal bit width 4 Configuration without address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0,08 to 2,5mm2

Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail)

Digital Outputs 750-501...504,516, 519

Page 54 of the Quatech INTERBUS S user manual — 750-506
Page 54 · click to enlarge
Page 54
Quatech INTERBUS S — 750-506 diagram (page 54)
Fig. 70

Technical description: The power supply is provided by a series-connected supply module for the respective operating voltage. Power connections are made automatically from module to module via the internal P.J.C.s when snapped onto the DIN rail. Attention: The lowest power jumper contact is not carried out for some modules (e.g. 4-channel)! A module which needs all contacts (e.g. 2 channel digital) may not be connected to the right hand side of modules which do not have 3 power jumper contacts (e.g. 4 channel modules). Using the digital outputs with diagnostic bit outputs (750-506) allows verification of the I/O channel by the connected bus. Example: a short-circuit at the output or an open circuit will set the appropriate error bit true indicating I/O failure. In this configuration the function module includes 2 digital outputs and 2 separate digital inputs. For the digital outputs with diagnostic four-conductor devices (V+; 0V; signal; ground) are standard. All digital outputs are short-circuit protected. In case of overloads a supply module with fuse (750-601) must be connected on the line side to protect the output modules. The standard numerical assignment for bus operations is from left to right, starting with the LSB. The positions of the different I/O modules in the configured node/station are selectable by the user. A block type configuration is not necessary. When using I/O modules with diagnostics, the existing inputs must be considered accordingly in the configuration of the Node/station. The Output module can be connected to all buscouplers of the WAGOÇI/OÇSYSTEM.

Digital Outputs 750-506

Page 55 of the Quatech INTERBUS S user manual — 750-506
Page 55 · click to enlarge
Page 55
Quatech INTERBUS S — 750-506 diagram (page 55)
Fig. 71

Item Number 750- 506 Number of outputs 2 Current consumption (internal) 15 mA Nominal voltage 24V DC (-15%/+20%) Kind of load resistive, inductive, lamps Output current (DC) 0.5 A Diagnostics open circuit, overload Current consumption (internal) 15 mA typ. + load Isolation 500 V system / power supply Internal bit width 4 in, 4 out Configuration without address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 to 2.5mm2

Quatech INTERBUS S — 750-506 diagram (page 55)
Fig. 72

Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of carrier rail)

The output bits control the state of the outputs.

Bit 3 Bit 2 Bit 1 Bit 0 function no function no function controls O2 controls O1

The input bits show the state of the outputs.

Quatech INTERBUS S — 750-506 diagram (page 55)
Fig. 73

Bit 3 Bit 2 Bit 1 Bit 0 function diagnostics O2 diagnostics O2 diagnostics O1

short circuit 1 0 1 0 power supply too low*

*The diagnostic bits refer to a hysteresis: If the voltage of the field side is higher than 11V in the falling circle, they are switched on. If the voltage is lower than 15,5 V in the growing circle, they are switched off.

Digital Outputs 750-506

Page 56 of the Quatech INTERBUS S user manual — 750-509
Page 56 · click to enlarge
Page 56
Quatech INTERBUS S — 750-509 diagram (page 56)
Fig. 74
Quatech INTERBUS S — 750-509 diagram (page 56)
Fig. 75

The power supply for the solid state relay module is connected by a series-connected supply module for the respective operating voltage of 230 V. Power connections are made automatically from module to module via the internal P.J.C.s when snapped onto the DIN rail. Attention: The lowest power jumper contact is not carried out for some modules (e.g. 4-channel)! A module which needs all contacts (e.g. 2 channel digital) may not be connected to the right hand side of modules which do not have 3 power jumper contacts (e.g. 4 channel modules). The power supply of the control side is not made via the power jumper contacts but directly from the electronics. The respective output contacts of the switching element are therefore always positioned at the field side. One termination point of these contacts must be directly connected to the power supply. For the digital outputs four-conductor devices (V+; 0V; signal; ground) are standard. All digital outputs are short-circuit protected. In case of overloads a supply module with fuse (750-609) must be connected on the line side to protect the output modules. The standard numerical assignment for Bus operation is from left to right, starting with the LSB. The positions of the different inputs in the configured station are via the user’s choice. A block type assembly is not necessary. The Output module can be connected to all buscouplers of the WAGOÇI/OÇSYSTEM.

Digital Outputs 750-509

Page 57 of the Quatech INTERBUS S user manual — 750-509
Page 57 · click to enlarge
Page 57
Quatech INTERBUS S — 750-509 diagram (page 57)
Fig. 76

Item Number 750- 509 Number of outputs 2 Current consumption (internal) 10 mA Switching voltage 0 V...230 V AC/DC Switched current 300 mA AC max. Speed of operation 1.65 ms typ., 5 ms max. Volume resistance 2.1 Ω typ., 3.2 Ω max. Impulse current 0.5 A (20 s), 1.5 A (0.1 s) Overvoltage protection >+/- 380 V (suppressor diode) Isolation 1.5 kV system / power supply Internal bit width 2 Configuration without address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 to 2.5mm2

Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail)

Digital Outputs 750-509

Page 58 of the Quatech INTERBUS S user manual — Technical Description:
Page 58 · click to enlarge
Page 58
Quatech INTERBUS S — 750-511 diagram (page 58)
Fig. 77
Quatech INTERBUS S — 750-511 diagram (page 58)
Fig. 78

Technical Description:

This description is for hard and software version X 2 B 0 2- . The part number is displayed on the right side of the module.

The initial pre-programmed base frequency is for 250 Hz. The resolution is 10 Bits and the pulsewidth is modulated. Attention: The lowest power jumper contact is not carried out for some modules (e.g. 4-channel)! A module which needs all contacts (e.g. 2 channel digital) may not be connected to the right hand side of modules which do not have 3 power jumper contacts (e.g. 4 channel modules).

The following description is preliminary and is applicable to the factory configuration.

The pulsewidth output module 750-511 produces a binary modulated signal of 24 V. The connection of the consuming device should be made via the „O“ and 0 V (common) contacts of the module. The distribution of the 24 V DC is made via the power jumper contacts. If galvanic isolation is desired, a new power feed via a 750-602 is required.

The PWM module can be connected to all buscouplers of the WAGOÇI/OÇSYSTEM (except for the economy type).

Pulsewidth Module 750-511

Page 59 of the Quatech INTERBUS S user manual — 750-511
Page 59 · click to enlarge
Page 59
Quatech INTERBUS S — 750-511 diagram (page 59)
Fig. 79

Part Number 750- 511 Number of outputs 2 Current consumption (internal) 70 mA typical (internal) Nominal voltage 24V DC (-15% +20%) Load type ohmic, inductive Output current 0.1 A, short circuit protected Pulse frequency 1 Hz...20kHz Duty cycle 0%...100% (Ton > 750 ns, Toff > 500 ns) Resolution 10 Bit max. Isolation 500 V system/power Supply Configuration none, optional with software parameter Current Consumption (field side)

15 mA typ.

Internal bit width per channel 16 Bit Data + 8 Bit Control/Status Operating temperature 0°C +55°C Wire connections CAGE CLAMP; 0.08 to 2.5mm2

Dimension (mm)BxHxT 12 x 64* x 100 (*from upper edge of the carrier rail) Preset Frequency 250 Hz Switching Frequency

Pulsewidth Module 750-511

Page 60 of the Quatech INTERBUS S user manual — 750-511
Page 60 · click to enlarge
Page 60
Quatech INTERBUS S — 750-511 diagram (page 60)
Fig. 80

The programming of the on/off times occur with the resolution of 10 bits. The five LSB of the 16 bit value can be zeros or one. The MSB will hold the sign and is preset to the null state.

Quatech INTERBUS S — 750-511 diagram (page 60)
Fig. 81

Value Hex. Dec. 100 1023 0111 1111 1111 1111 7F FF 32767

100 1023 0111 1111 1111 0000 7F E0 32752

50 511 0011 1111 1111 1111 3F FF 16383

25 255 0001 1111 1111 1111 1F FF 8191

12.5 127 0000 0001 0000 0000 01 00 256

0.1955 2 0000 0000 0100 0000 00 40 16

0.0977 1 0000 0000 0010 0000 00 20 32

0 0 0000 0000 0001 1111 00 1F 31

Table 1Value Formation
Quatech INTERBUS S — 750-511 diagram (page 60)
Fig. 82

Ill. 1: On/Off time relationships for Table 1.

Pulsewidth Module 750-511

Page 61 of the Quatech INTERBUS S user manual — 750-511
Page 61 · click to enlarge
Page 61
Quatech INTERBUS S — 750-511 diagram (page 61)
Fig. 83

The process image of the 750-511 appears with 6 bytes of input and 6 bytes of output data. The byte allocation for the preset duty cycle has the following modes of formation: Output values:

Quatech INTERBUS S — 750-511 diagram (page 61)
Fig. 84

Function D0 Control Byte D1 Output Byte 1 D2 Output Byte 0 D3 reserved D4 Output Byte 3 D5 Output Byte 2 Input values:

Quatech INTERBUS S — 750-511 diagram (page 61)
Fig. 85

Function D0 Status Byte D1 Input Byte 1 D2 Input Byte 0 D3 reserved D4 Input Byte 3 D5 Input Byte 2 Out(In)put byte 0 Low Byte Out(In)put byte 1 High Byte

Pulsewidth Module 750-511

Page 62 of the Quatech INTERBUS S user manual — 750-512...514, 517
Page 62 · click to enlarge
Page 62
Quatech INTERBUS S — 750-512...514, 517 diagram (page 62)
Fig. 86
Quatech INTERBUS S — 750-512...514, 517 diagram (page 62)
Fig. 87

The power supply for the relay coils is not made via the power jumper contacts but directly from the electronics. The respective output contacts of the switching element are therefore always positioned at the field side. Attention: The lowest power jumper contact is not carried out for some modules (e.g. 4-channel)! A module which needs all contacts (e.g. 2 channel digital) may not be connected to the right hand side of modules which do not have 3 power jumper contacts (e.g. 4 channel modules). Version 1: non-floating (750-512) The power supply is made via a series-connected supply terminal block for the respective operating voltage. Power connections are made automatically from module to module when snapped onto the DIN rail. One termination point of these contacts must be directly connected to the power supply. Version 2: isolated outputs (750-513, 750-514) These I/O modules are not provided with integrated power jumper contacts. Care should be taken to supply each isolated module with separate power supply connections. The standard numerical assignment for Bus operation is from left to right, starting with the LSB. The positions of the different inputs in the configured station are via the user’s choice. A block type configuration is not necessary. The output module can be connected to all buscouplers of the WAGOÇI/OÇSYSTEM.

Digital Outputs 750-512-514,517

Page 63 of the Quatech INTERBUS S user manual — 750-512...514, 517
Page 63 · click to enlarge
Page 63
Quatech INTERBUS S — 750-512...514, 517 diagram (page 63)
Fig. 88

Item Number 750- 512 513 Type of contact 2 make contacts Current consumption (internal) 100 mA max. Switching voltage 30 V DC; 250V AC Switching power 60 W; 500 VA cos

Quatech INTERBUS S — 750-512...514, 517 diagram (page 63)
Fig. 89

Switching current 2 A AC/ DC Isolation 4 kV system/power supply Internal bit width 2 Configuration without address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 to 2.5mm2

Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail)

Quatech INTERBUS S — 750-512...514, 517 diagram (page 63)
Fig. 90

Type of contact 2 changeover Current consumption (internal) 70 mA max. 80 mA max. Switching voltage 30 V DC; 125 V AC 250 V AC Switching power 30 W; 62.5 VA 1500 VA* Switching current 0.5 A AC/ 1 A DC 1 A AC Isolation 1.5 kV system/power supply

4 kV system/ power supply Internal bit width 2 Configuration without address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 to 2.5mm2

Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail) *ohmic load 1)in design

Digital Outputs 750-512-514,517

Page 64 of the Quatech INTERBUS S user manual — 6ZLWFKHG FXUUHQW>$@
Page 64 · click to enlarge
Page 64

Relays in the modules 750-512 and 750-513:

6ZLWFKLQJFDSDFLW\

6 Z L WFKHG FXUUHQW>$@

AC ohmic DC ohmic

AC inductive, cosϕ=0.4

6ZLWFKHG YROWDJH>9@

7\SLFDOHOHFWULFDOOLIHWLPH

1,E+06

1 X P E HU RIVZ L WFKHV

30 V DC ohmic 120 V AC ohmic 250 V AC ohmic 30 V DC inductive, L/R = 0.7ms

1,E+05

120 V AC inductive, cosϕ=0.4

1,E+04

250 V AC inductive, cosϕ=0.4

6ZLWFKHG FXUUHQW>$@

Show 5 more labels / short text on this page
DC inductive L/R=7ms · 0,1 · 10 100 1000 · 0,1 1 10 · Digital Outputs 750-512-514,517
Page 65 of the Quatech INTERBUS S user manual — Technical Description
Page 65 · click to enlarge
Page 65
Quatech INTERBUS S — Analog Inputs diagram (page 65)
Fig. 91 · Analog Inputs

2 Channel Analog Inputs 0-20 mA / 4-20 mA (Differential Inputs) PN 750-452, 454, 750-482, 750-484

Quatech INTERBUS S — Analog Inputs diagram (page 65)
Fig. 92 · Analog Inputs

Technical Description

This description is only intended for hardware version X 2 A 0 0 -. The serial number can be found on the right side of the module.

The input channels are differential inputs and they have a common ground potential. The inputs are connected to +I and -I. The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail.

These I/O modules are not provided with integrated power jumper contacts. The power supply is made by the data contacts with a DC-DC converter. The modules can work self-supporting.

The input module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type)

Analog Inputs 750-452, 454,482,484

Page 66 of the Quatech INTERBUS S user manual — Analog Inputs
Page 66 · click to enlarge
Page 66
Quatech INTERBUS S — Analog Inputs diagram (page 66)
Fig. 93 · Analog Inputs

Item Number 750- 452 454 482 484 Number of channels 2 2 Nominal voltage via system voltage Current consumption (internal)

Quatech INTERBUS S — Analog Inputs diagram (page 66)
Fig. 94 · Analog Inputs

Voltage 35 V max. Signal current 0-20mA 4-20mA 0-20mA 4-20mA Resistance 50 Ω typ. Resolution 12 Bit Isolation 500 V System/Power supply Conversion time 2 ms typ. Bit width per channel 16 Bit Data, 8 Bit Control/Status Operating temperature 0°C +55°C Configuration none, optional via software parameter Wire connection CAGE CLAMP; 0.08 to 2.5mm2

12 x 64* x 100 (*from upper edge of the carrier rail)

Analog Inputs 750-452, 454,482,484

Page 67 of the Quatech INTERBUS S user manual — Analog Inputs
Page 67 · click to enlarge
Page 67
Quatech INTERBUS S — Analog Inputs diagram (page 67)
Fig. 95 · Analog Inputs

All analog values will be shown in a unit numerical format. The resolution is 12 Bits. The following table will explain the numerical format. (750-452, 454). The 3 least significant Bits are not taken into account.

Quatech INTERBUS S — Analog Inputs diagram (page 67)
Fig. 96 · Analog Inputs

Hex. Dec. 20 20 0111 1111 1111 1000 7F F8 32760

10 12 0100 0000 0000 0000 40 00 16384

5 8 0010 0000 0000 0000 20 00 8192

2.5 6 0001 0000 0000 0000 10 00 4096

0.156 4.125 0000 0001 0000 0000 01 00 256

0.01 4.0078 0000 0000 0001 0000 00 10 16

0.005 4.0039 0000 0000 0000 1000 00 08 8

0 4 0000 0000 0000 0111 00 07 7

Analog Inputs 750-452, 454,482,484

Page 68 of the Quatech INTERBUS S user manual — Analog Inputs
Page 68 · click to enlarge
Page 68
Quatech INTERBUS S — Analog Inputs diagram (page 68)
Fig. 97 · Analog Inputs

In addition to the full 16 bit indication of the measured value it is possible to use the ‘Siemens format’. The measured value is represented by the most significant 12 Bits. The 3 least significant Bits are reserved for diagnostic and status purposes. (750-482, 484)

Quatech INTERBUS S — Analog Inputs diagram (page 68)
Fig. 98 · Analog Inputs
4-20 mA Binary value Xwithout meaning F : short circuit or F : open circuit Ü : overflow

> 20 0101 0000 0000 1 50 01 20481

20 0101 0000 0000 50 00 20480

16 0100 0000 0000 40 00 16384

12 0011 0000 0000 30 00 12288

8 0010 0000 0000 20 00 8192

4.0078 0001 0000 0000 1 0 0 0 10 08 4104

4 0001 0000 0000 10 00 4096

4 0001 0000 0000 0 0 1 1 10 03 4099

Analog Inputs 750-452, 454,482,484

Page 69 of the Quatech INTERBUS S user manual — Analog Inputs
Page 69 · click to enlarge
Page 69
Quatech INTERBUS S — Analog Inputs diagram (page 69)
Fig. 99 · Analog Inputs
0-20 mA Binary value Xwithout meaning F : short circuit open circuit Ü : overflow

> 20 0100 0000 0000 1 40 01 16385

20 0100 0000 0000 40 00 16384

10 0010 0000 0000 20 00 8192

5 0001 0000 0000 10 00 4096

2.5 0000 1000 00008 00 2048

1.25 0000 0100 00004 00 1024

0.625 0000 0010 00002 00 512

0.0976 0000 0000 0000 1 00 08 8

0 0000 0000 00000 00 0

If you have questions about the formatting of this data, please contact WAGO for I/O System technical support.

Analog Inputs 750-452, 454,482,484

Page 70 of the Quatech INTERBUS S user manual — Technical Description
Page 70 · click to enlarge
Page 70
Quatech INTERBUS S — 750-456 diagram (page 70)
Fig. 100

2 Channel Analog Inputs +/- 10 V (Differential Inputs) PN 750-456, 750-456/000-001

Quatech INTERBUS S — 2 Channel Analog Inputs +/- 10 V (Differential Inputs) PN 750-456, 750-456/000-001 diagram (page 70)
Fig. 101 · 2 Channel Analog Inputs +/- 10 V (Differential Input…

Technical Description

This description is only intended for hardware version X 2 A 0 0 -. The serial number can be found on the right side of the module.

The input channels are differential inputs and they have a common ground potential.

The inputs are connected to +I and -I. The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail.

These I/O modules are not provided with integrated power jumper contacts. The power supply is made by the data contacts with a DC-DC converter. The modules can work self-supporting.

The input module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type)

Analog Inputs 750-456

Page 71 of the Quatech INTERBUS S user manual — 750-456
Page 71 · click to enlarge
Page 71
Quatech INTERBUS S — 750-456 diagram (page 71)
Fig. 102

Item Number 750- 456, 456/000-001 Number of channels 2 Nominal voltage via system voltage (DC DC converter) Current consumption (internal)

Quatech INTERBUS S — 750-456 diagram (page 71)
Fig. 103

Overvoltage protection 35 V max. Signal voltage +/- 10 V Resistance 570 kΩ Resolution 12 Bit Isolation 500 V System/Power supply Conversion time 2 ms typ. Bit width per channel 16 Bit Data, 8 Bit Control/Status Operating temperature 0°C +55°C Configuration none, optional via software parameter Wire connection CAGE CLAMP; 0.08 to 2.5mm2

12 x 64* x 100 (*from upper edge of the carrier rail)

Analog Inputs 750-456

Page 72 of the Quatech INTERBUS S user manual — 750-456
Page 72 · click to enlarge
Page 72
Quatech INTERBUS S — 750-456 diagram (page 72)
Fig. 104

All analog values will be shown in a unit numerical format. The resolution is 12 Bits and the 3 LSBs are not taken into account. The following table will explain the numerical format.

Quatech INTERBUS S — 750-456 diagram (page 72)
Fig. 105

> 10 V 0111 1111 1111 1111 7F FF 32767 42

10 0111 1111 1111 XXXX 7F FX 32760 0

5 0100 0000 0000 XXXX 40 0X 16384 0

2,5 0010 0000 0000 XXXX 20 0X 8192 0

1,25 0001 0000 0000 XXXX 10 0X 4096 0

0,0781 0000 0001 0000 XXXX 01 0X 256 0

0,0049 0000 0000 0001 XXXX 00 1X 16 0

0 0000 0000 0000 XXXX 00 0X 0 0

-2,5 1110 0000 0000 XXXX E0 0X 57344 0

-5 1100 0000 0000 XXXX C0 0X 49152 0

-7,5 1010 0000 0000 XXXX A0 0X 40960 0

-10 1000 0000 0000 XXXX 80 0X 32768 0

< -10 V 1000 0000 0000 0000 80 00 32768 41

Analog Inputs 750-456

Page 73 of the Quatech INTERBUS S user manual — 750-456
Page 73 · click to enlarge
Page 73
Quatech INTERBUS S — 750-456 diagram (page 73)
Fig. 106

In addition to the full 16 bit indication of the measured value it is possible to use the Siemens format. The measured value is represented by the most significant 12 Bits. The 3 least significant bits are reserved for diagnostic and status purposes. (750-456/000- 001).

Quatech INTERBUS S — 750-456 diagram (page 73)
Fig. 107
Binary value Xwithout meaning F : short circuit or F : open circuit Ü : overflow

>10 0111 1111 1111 1 0 0 1 7F F9 32761

10 0111 1111 1111 1 0 0 0 7F F8 32760

5 0110 0000 0000 60 00 24576

2,5 0101 0000 0000 50 00 20480

1,25 0100 1000 0000 48 00 18432

0,0049 0100 0000 0000 1 0 0 0 40 08 16392

0 0100 0000 0000 40 00 16384

-2,5 0011 0000 0000 1 0 0 0 30 08 12296

-5 0010 0000 0000 20 00 8192

-7,5 0001 0000 0000 10 00 4096

-10 0000 0000 0000 1 00 00 8

If you hve questions about the formatting of this data, please contact WAGO for the I/O System technical support.

Analog Inputs 750-456

Page 74 of the Quatech INTERBUS S user manual — Technical description:
Page 74 · click to enlarge
Page 74
Quatech INTERBUS S — 750-461 diagram (page 74)
Fig. 108

Input for PT 100 PN 750-461, 750-461/000-002, 750-461/000-003, 750-481

Quatech INTERBUS S — Input for PT 100 PN 750-461, 750-461/000-002, 750-461/000-003, 750-481 diagram (page 74)
Fig. 109 · Input for PT 100 PN 750-461, 750-461/000-002, 750-46…

Technical description:

This description is only intended for hardware version X 3 A 0 2 -. The serial number can be found on the right side of the module.

The described configuration is PT 100. The following description is preliminary and is applicable only to the factory configuration.

The inputs are connected to +I and -I. The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail. Attention: The lowest power jumper contact is not carried out for some modules (e.g. 4-channel)! A module which needs all contacts (e.g. 2 channel digital) may not be connected to the right hand side of modules which do not have 3 power jumper contacts (e.g. 4 channel modules).

These I/O modules are not provided with integrated power jumper contacts. The power supply is made by the data contacts with a DC-DC converter. The modules can work self-supporting. The PT100 module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type)

Input for PT100 750-461, 481

Page 75 of the Quatech INTERBUS S user manual — 750-461
Page 75 · click to enlarge
Page 75
Quatech INTERBUS S — 750-461 diagram (page 75)
Fig. 110

Item Number 750- 461, 481, 461/000-002, 461/000-003 Number of inputs 2 Input current (internal) 65 mA Voltage supply via system voltage Sensor types PT100, PT 200, PT 500, PT1000, Ni100, Ni120, Ni1000 Wire connection 2-conductor, 3-conductor (presetting) Temperature range PT: -200°C..+850°C Ni:-60°C...250°C Resolution 0.1°C over the whole area Isolation DC/DC 400V system / power supply Measuring current 0.5mA type

Bit width per channel 16 bits: data; 8 bits: control/status Configuration none, optional via software parameter Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 to 2.5mm2

Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail) Presetting 3-conductor PT100

The function module 750-461 allows the direct connection of PT- or Ni-resistance sensors. The module is suitable for 2- or 3-wire RTDs. Connection is made according to the above wiring diagram.

Linearization is accomplished over the entire measurement range by a microprocessor. The temperature ranges of the above listed RTD types is available to the user. The temperature ranges of the sensors are represented with a resolution of 1 bit per 0.1° C in one word (16 bits). Resulting from this, 0°C corresponds to the hexadecimal value 0000 and 100°C is 03E8 (dez.1000). Temperatures below 0° are represented in two’s complement with a leading ‘1’.

The function module works in the defined temperature range for the PT100 sensors of -200°C to +850°C. The voltage resolution is represented with 16 bits. An A/D converter and processor converts the voltage value to a numerical value proportional to the temperature of the selected resistance temperature sensor.

A short circuit or an interruption of the RTD wire is transmitted to the bus module and indicated by the red error LED. The green LED identifies that the module is communicating properly with the connected Buscoupler.

Input for PT100 750-461, 481

Page 76 of the Quatech INTERBUS S user manual — 750-461
Page 76 · click to enlarge
Page 76
Quatech INTERBUS S — 750-461 diagram (page 76)
Fig. 111

All temperature values will be shown in a unit numerical format. If the mode ‘DEFAULT’ is selected each bit corresponds to 0.1°C. The possible numerical range refers to the standardized temperature range of the used sensors. The following table will explain the numerical format on a preset PT100. In the third column the numerical format for PT1000 (750-461/000-003) is explained.

Quatech INTERBUS S — 750-461 diagram (page 76)
Fig. 112

850 390.481 1384,998 0010 0001 0011 0100 2134 8500

100 138.506 1099,299 0000 0011 1110 1000 03E8 1000

25.5 109.929 1000,391 0000 0000 1111 1111 00FF 255

0.1 100.039 1000 0000 0000 0000 0001 0001 1

0 100 999,619 0000 0

-0.1 99.970 901,929 1111 FFFF -1

-25.5 90.389 184,936 1111 1111 0000 0001 FF01 -255

Input for PT100 750-461, 481

Table 1

Page 77 of the Quatech INTERBUS S user manual — 750-461
Page 77 · click to enlarge
Page 77
Quatech INTERBUS S — 750-461 diagram (page 77)
Fig. 113

All temperature values will be shown in a unit numerical format. Each bit corresponds to 0.1°C. The following table will explain the numerical format for 750-461/000-002.

Quatech INTERBUS S — 750-461 diagram (page 77)
Fig. 114

Hex. Dez. 10 0000 0000 0110 0100 00 64 100

Input for PT100 750-461, 481

Page 78 of the Quatech INTERBUS S user manual — 750-461
Page 78 · click to enlarge
Page 78
Quatech INTERBUS S — 750-461 diagram (page 78)
Fig. 115

In addition to the full 16 bit indication of the measured value it is possible to use the ‘Siemens format’. The measured value is represented by the most significant 12 Bits. The 4 least significant Bits are reserved for diagnostic and status purposes. (750-481)

Quatech INTERBUS S — 750-461 diagram (page 78)
Fig. 116
Ohm Binary value Xwithout meaning F : short circuit or F : open circuit Ü : overflow

>400 1111 1111 1111 1 0 0 1 FF F9 65529

883 400 0111 1111 1111 1 0 0 0 7F F8 32866

560 300 0110 0000 0000 60 00 24576

266 200 0100 0000 0000 40 00 16384

0 100 0010 0000 0000 20 00 8192

-125 50 0001 0000 0000 10 00 4096

-185 25 0000 0101 0000 500 1280

-200 20 0000 0100 0000 400 1024

If you have questions about the formatting of this data, please contact WAGO for I/O System technical support.

Input for PT100 750-461, 481

Page 79 of the Quatech INTERBUS S user manual — Technical description:
Page 79 · click to enlarge
Page 79
Quatech INTERBUS S — 750-462 diagram (page 79)
Fig. 117
Quatech INTERBUS S — 750-462 diagram (page 79)
Fig. 118

Technical description:

This description is only intended for hardware version X 2 A 0 1 -. The serial number can be found on the right side of the module.

The following description is preliminary and is applicable only to the factory configuration.

The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail.

These I/O modules are not provided with integrated power jumper contacts. The power supply is made by the data contacts with a DC-DC converter. The modules can work self-supporting. Attention: The lowest power jumper contact is not carried out for some modules (e.g. 4-channel)! A module which needs all contacts (e.g. 2 channel digital) may not be connected to the right hand side of modules which do not have 3 power jumper contacts (e.g. 4 channel modules).

The thermocouple module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type)

Input for thermocouple modules 750-462,469

Page 80 of the Quatech INTERBUS S user manual — 750-462
Page 80 · click to enlarge
Page 80
Quatech INTERBUS S — 750-462 diagram (page 80)
Fig. 119

Item Number 750- 462, 469 Number of inputs 2 (differential input, max. +/- 3.5V) Voltage supply via system voltage Sensor types J, K, B, E, N, R, S, T, U, L, mV Messung Cold junction compensation on each module Measuring accuracy

Input current (internal) 65 mA max. Bit width per channel 16 Bit: data; 8 Bit: control/status* (detection of broken wire 750-469) Configuration none, optional via software parameter Operating temperature 0°C +55°C Connection technique CAGE CLAMP; 0.08 to 2.5mm2

Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail) Presetting -100°C / +1370°C, Typ K

The function module 750-462 permits the direct connection of thermocouple sensors. The module is suitable for 2 or 3-wire thermocouples. For the 2-wire connection technique, connect the thermocouple wires between TC- and TC+ . For the 3-conductor technique the shield is also connected. The operation of grounded sensors is provided by means of internal electrical isolation.

The function module 750-469 alos detects a broken wire. You can find the PNs for the different sensor types for 750-462 in the following table.

The linearization is provided over the complete range by a microprocessor. The temperature ranges of the sensors are represented with a resolution of 1 bit per 0.1°C in one word (16 Bit). Thus, 0°C corresponds to the value 0000, and 25.5°C correspond to the value 0 x 00FF. Temperatures below 0°C are represented in two’s complement with a leading ‘1’.

Within the whole range of all thermocouples, the function module works like a ‘µV meter’. The voltage resolution is represented with 16 bits. A processor converts the voltage value into a numerical value proportional to the measured temperature of the selected type of thermocouple.

In order to compensate the offset voltage at the clamping point, a cold junction thermocouple compensation calculation is carried out. The circuit contains a temperature measuring sensor at the ‘CAGE CLAMP’ connection and considers the temperature offset voltage when calculating the measured value.

Input for thermocouple modules 750-462,469

Page 81 of the Quatech INTERBUS S user manual — Temperature Ranges of the connectable sensors:
Page 81 · click to enlarge
Page 81

Temperature Ranges of the connectable sensors:

L -25°C +900°C K -100°C...1370°C (Default) J -100°C...+1200°C 750-462/000-006 750-469/000-006 E -100°C...1000°C 750-462/000-008 750-469/000-008 T -100°C...+400°C 750-462/000-002 750-469/000-002 N -100°C...+1300°C 750-462/000-009 750-469/000-009 U -25°C...+600°C 750-462/000-011 750-469/000-011 B 600°C...+1800°C 750-462/000-007 750-469/000-007 R 0°C...+1700°C 750-462/000-010 750-469/000-010 S 0°C...+1700°C 750-462/000-001 750-469/000-001 mV-Meter -120 mV...+120 mV 750-462/000-003 750-469/000-003 Table 1: Temperature ranges of the connectable sensors Attention: The range of the mV Meter is 0 to 120mV at the moment! LED functions:

green LEDFunction

ON: Normal OFF: Watchdog-Timer Overflow If the PLC does not transmit processing data for 100 ms the green LED stops lightning.

red LEDError
ONOveror underrange or broken wire (bei 750-469) OFF: voltage is in the measuring range

Input for thermocouple modules 750-462,469

Page 82 of the Quatech INTERBUS S user manual — 750-462
Page 82 · click to enlarge
Page 82
Quatech INTERBUS S — 750-462 diagram (page 82)
Fig. 120

All temperature values are represented in a uniform numerical format. In the default setting (type K) one Bit corresponds to 0.1°C. The output value corresponds to the temperature range of each sensor as defined according to standards. By using a configuration tool, the output formats can be chosen. The linearization can be switched off and the building of the reference temperature can be switched off also. The following table identifies the numerical format on the default range (type K).

Quatech INTERBUS S — 750-462 diagram (page 82)
Fig. 121

Hex. Dec. 850 35314 0010 0001 0011 0100 2134 8500

Table 2Numerical formats

Input for thermocouple modules 750-462,469

Page 83 of the Quatech INTERBUS S user manual — Technical Description
Page 83 · click to enlarge
Page 83
Quatech INTERBUS S — 750-465, 750-466 diagram (page 83)
Fig. 122

2 Channel Analog Input 0-20 mA / 4- 20 mA single ended PN 750-465, 750-466, 750-486, 750-465/000-001

Quatech INTERBUS S — 750-465, 750-466 diagram (page 83)
Fig. 123

Technical Description

This description is only intended for hardware version X 2 A 0 1 -. The serial number can be found on the right side of the module.

The input channels are single ended and they have a common ground potential.

The inputs are connected to +I. Via 24 V / 0 V a sensor can be provided directly from the module. Power connections are made automatically from module to module when snapped onto the DIN rail.

The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail.

The input module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type)

Analog Inputs 750-465,466,486

Page 84 of the Quatech INTERBUS S user manual — 750-465, 750-466
Page 84 · click to enlarge
Page 84
Quatech INTERBUS S — 750-465, 750-466 diagram (page 84)
Fig. 124

Item Number 750- 465 465/000-001 466 486 Number of channels 2 Nominal voltage 24 V DC (-15% / +20%) via power jumper contacts Current consumption (internal)

75 mA typ.

Overvoltage protection 35 V max. Signal current 0-20mA 4-20mA Resistance 50 Ω typ. Resolution 12 Bit Isolation 500 V system/power supply Conversion time 2 ms typ. Bit width per channel 16 Bit Data, 8 Bit Control/Status Operating temperature 0°C +55°C Configuration none, optional via software parameter Wire connection CAGE CLAMP; 0.08 to 2.5mm2

12 x 64* x 100 (*from upper edge of the carrier rail)

Dimensions (mm)WxHxL · Analog Inputs 750-465,466,486

Page 85 of the Quatech INTERBUS S user manual — A)
Page 85 · click to enlarge
Page 85
Quatech INTERBUS S — 750-465, 750-466 diagram (page 85)
Fig. 125

All analog values will be shown in a unit numerical format. The resolution is 12 Bits. The following table will explain the numerical format. (750-465, 466). The 3 LSBs are not taken into account.

Quatech INTERBUS S — 750-465, 750-466 diagram (page 85)
Fig. 126

Hex. Dec. Status LED >20,5 >20,5 0111 1111 1111 1111 7F FF 32767 42 on

20 20 0111 1111 1111 1111 7F FF 32767 0 off

10 12 0100 0000 0000 0XXX 40 00 16384 0 off

5 8 0010 0000 0000 0XXX 20 00 8192 0 off

2,5 6 0001 0000 0000 0XXX 10 00 4096 0 off

0,156 4,125 0000 0001 0000 0XXX 01 00 256 0 off

0,01 4,0078 0000 0000 0001 0XXX 00 10 16 0 off

0,005 4,0039 0000 0000 0000 1XXX 00 08 8 0 off

0 4 0000 0000 0000 0XXX 00 00 7 0 off

0 3,5 - 4 0000 0 0 0 off

0 0 - 3,5 0000 0 0 41 on (4 -20

A)

Analog Inputs 750-465,466,486

Page 86 of the Quatech INTERBUS S user manual — 750-465, 750-466
Page 86 · click to enlarge
Page 86
Quatech INTERBUS S — 750-465, 750-466 diagram (page 86)
Fig. 127

In addition to the full 16 bit indication of the measured value it is possible to use the ‘Siemens format’. The measured value is represented by the most significant 12 Bits. The 3 least significant Bits are reserved for diagnostic and status purposes. (750- 465/000-001).

Quatech INTERBUS S — 750-465, 750-466 diagram (page 86)
Fig. 128

Binary value X : without meaning F : short circuit or F : open circuit Ü : overflow X F Ü

>20,5 0100 0000 0000 1 4001 16385 42 on

20 0100 0000 0000 4000 16384 0 off

10 0010 0000 0000 2000 8192 0 off

5 0001 0000 0000 1000 4096 0 off

2,5 0000 1000 0000800 2048 0 off

1,25 0000 0100 0000400 1024 0 off

0,625 0000 0010 0000200 512 0 off

0,0976 0000 0000 0000 1 0008 8 0 off

0 0000 0000 0000000 0 0 off

Analog Inputs 750-465,466,486

Page 87 of the Quatech INTERBUS S user manual — 750-465, 750-466
Page 87 · click to enlarge
Page 87

750-466/000-200 or 750-486:

Quatech INTERBUS S — 750-465, 750-466 diagram (page 87)
Fig. 129

Binary value X : without meaning F : short circuit or F : open circuit Ü : overflow X F Ü

>20,5 0101 0000 0000 1 40 01 16385 42 on

20 0101 0000 0000 50 00 20480 0 off

16 0100 0000 0000 40 00 16384 0 off

12 0011 0000 0000 30 00 12288 0 off

8 0010 0000 0000 20 00 8192 0 off

4,0078 0001 0000 0000 1 0 0 0 1008 4104 0 off

4 0001 0000 0000 1000 4096 0 off

If you have questions about the formatting of this data, please contact WAGO for I/O System technical support.

Analog Inputs 750-465,466,486

Page 88 of the Quatech INTERBUS S user manual — Technical Description
Page 88 · click to enlarge
Page 88
Quatech INTERBUS S — 750-467, 468 diagram (page 88)
Fig. 130

2 / 4 Channel Analog Inputs 0-10 V single ended PN 750-467, 468, 487, 488

Quatech INTERBUS S — 750-467, 468 diagram (page 88)
Fig. 131

Technical Description

This description is only intended for hardware version X 2 A 0 0 -. The serial number can be found on the right side of the module.

The input channels are single ended and they have a common ground potential.

The inputs are connected to +I and M. The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail.

These I/O modules are not provided with integrated power jumper contacts. The power supply is made by the data contacts with a DC-DC converter. The modules can work self-supporting.

The input module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type)

Analog Inputs 750-467,468,487,488

Page 89 of the Quatech INTERBUS S user manual — 750-467, 468
Page 89 · click to enlarge
Page 89
Quatech INTERBUS S — 750-467, 468 diagram (page 89)
Fig. 132

Item Number 750- 467 468 487 488 Number of channels 2 4 2 4 Nominal voltage via system voltage (DC DC converter) Current consumption (internal)

Quatech INTERBUS S — 750-467, 468 diagram (page 89)
Fig. 133

Overvoltage protection 35 V max. Signal voltage 0-10 V Resistance 133 kΩ typ. Resolution 12 Bit Isolation 500 V system/power supply Conversion time 2 ms typ. Bit width per channel 16 Bit Data, 8 Bit Control/Status Operating temperature 0°C +55°C Configuration none, optional via software parameter Wire connection CAGE CLAMP; 0.08 to 2.5mm2

12 x 64* x 100 (*from upper edge of the carrier rail)

Analog Inputs 750-467,468,487,488

Page 90 of the Quatech INTERBUS S user manual — 750-467, 468
Page 90 · click to enlarge
Page 90
Quatech INTERBUS S — 750-467, 468 diagram (page 90)
Fig. 134

All analog values will be shown in a unit numerical format. The resolution is 12 Bits. The following table will explain the numerical format. (750-467, 468). The 3 LSBs are not taken into account.

Quatech INTERBUS S — 750-467, 468 diagram (page 90)
Fig. 135

Hex. Dec. Status > 10 0111 1111 1111 1111 7F FF 32767 42

10 0111 1111 1111 1XXX 7F F8 32760 0

5 0100 0000 0000 0XXX 40 00 16384 0

2,5 0010 0000 0000 0XXX 20 00 8192 0

1,25 0001 0000 0000 0XXX 10 00 4096 0

0,0781 0000 0001 0000 0XXX 01 00 256 0

0,0049 0000 0000 0001 0XXX 00 10 16 0

0,0024 0000 0000 0000 1XXX 00 08 8 0

0 0000 0000 0000 0XXX 00 07 7 0

Analog Inputs 750-467,468,487,488

Page 91 of the Quatech INTERBUS S user manual — 750-467, 468
Page 91 · click to enlarge
Page 91
Quatech INTERBUS S — 750-467, 468 diagram (page 91)
Fig. 136

In addition to the full 16 bit indication of the measured value it is possible to use the ‘Siemens format’. The measured value is represented by the most significant 12 Bits. The 3 least significant Bits are reserved for diagnostic and status purposes. (750-487, 488)

Quatech INTERBUS S — 750-467, 468 diagram (page 91)
Fig. 137
Binary value Xwithout meaning F : short circuit or F : open circuit Ü : overflow

>10 0101 0000 0000 1 50 01 20481 42

10 0101 0000 0000 50 00 20480 0

5 0011 0000 0000 30 00 12288 0

2,5 0010 0000 0000 20 00 8192 0

1,25 0001 1000 0000 18 00 6144 0

0,0049 0001 0000 0000 1 0 0 0 10 08 4104 0

0 0001 0000 0000 10 00 4096 0

If you have questions about the formatting of this data, please contact WAGO for I/O System technical support.

Analog Inputs 750-467,468,487,488

Page 92 of the Quatech INTERBUS S user manual — 750-472, 750-474
Page 92 · click to enlarge
Page 92
Quatech INTERBUS S — 750-472, 750-474 diagram (page 92)
Fig. 138

2 Channel Analog Input 0-20mA / 4-20mA single ended PN 750-472, 750-472/000-200, 750-474, 750-474/000-200

Quatech INTERBUS S — 750-472, 750-474 diagram (page 92)
Fig. 139

This description is only intended for hardware and software version X 0 2 0 2-. The serial number can be found on the right side of the module.

The input channels are single ended and they have a common ground potential. The inputs are connected to +I. Via 24 V / 0 V a sensor can be provided directly from the module. Power connections are made automatically from module to module when snapped onto the DIN rail.

The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail.

The input module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type).

Analog Inputs 750-472, 474

Page 93 of the Quatech INTERBUS S user manual — 750-472, 750-474
Page 93 · click to enlarge
Page 93
Quatech INTERBUS S — 750-472, 750-474 diagram (page 93)
Fig. 140

Item Number 750- 472 472/000-200 474 474/000-0200 Number of channels 2 Nominal voltage 24 V DC (-15% / +20%) via power jumper contacts Overvoltage protection 24 V max. Internal current 75 mA typ. Input signal 0-20mA 4-20mA Input current < 38 mA at 24 V Resistance 50 Ω Input voltage non-linear/overload protection: U=1,2 V DC+160Ω*Imess Resolution internal 16 Bit, 15 Bit via fieldbus Input filter 50 Hz Noise rejection at sampling frequency

Noise rejection below sampling frequency

Transition frequency 13 Hz Isolation 500 V system/power supply Conversion time 80 ms typ. Bit width per channel 16Bit: Data; optional 8Bit: Control/Status Configuration none, optional via software parameter Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0,08 to 2,5mm2

Dimensions (mm)WxHxL 12 x 64* x 100 *from upper edge of the carrier rail

Analog Inputs 750-472, 474

< -100 dB · < -40 dB

Page 94 of the Quatech INTERBUS S user manual — A)
Page 94 · click to enlarge
Page 94
Quatech INTERBUS S — 750-472, 750-474 diagram (page 94)
Fig. 141

The resolution of 750-472 and 750-474 are 15 Bit.

Quatech INTERBUS S — 750-472, 750-474 diagram (page 94)
Fig. 142

Hex. Dec. Status LED >20,5 >20,5 0111 1111 1111 1111 7F FF 32767 42 on

20 20 0111 1111 1111 1111 7F FF 32767 0 off

10 12 0100 0000 0000 0000 40 00 16384 0 off

5 8 0010 0000 0000 0000 20 00 8192 0 off

2,5 6 0001 0000 0000 0000 10 00 4096 0 off

0,156 4,125 0000 0001 0000 0000 01 00 256 0 off

0,01 4,0078 0000 0000 0001 0000 00 10 16 0 off

0,005 4,0039 0000 0000 0000 1000 00 08 8 0 off

0 4 0000 00 00 7 0 off

0 3,5 - 4 0000 0 0 0 off

0 0 - 3,5 0000 0 0 41 on (4-20

A)

Analog Inputs 750-472, 474

Page 95 of the Quatech INTERBUS S user manual — 750-472, 750-474
Page 95 · click to enlarge
Page 95
Quatech INTERBUS S — 750-472, 750-474 diagram (page 95)
Fig. 143

In addition to the full 16 Bit indication of the measured value it is possible to use the „Siemens format“. The measured value is represented by the most significant 12 Bits. The 3 least significant Bits are reserved for diagnostic and status purpose (750-472/000- 200, 750-474/000-200). The numerical format for 750-472/000-200 is equivalent to S5 463, 750-474/000-200 equivalent to S5 460/465.

Binary value X : without meaning F : short circuit or F: open circuit Ü : overflow X F Ü

Hex. Dec. Status LED

32 0111 1111 1111 1 0 0 1 7F F9 32761 42 on

31,99 0111 1111 1111 0 7F F0 32752 0 off

20,5 0101 0010 0000 1 52 00 20992 0 off

20 0101 0000 0000 50 00 20480 0 off

16 0100 0000 0000 40 00 16384 0 off

12 0011 0000 0000 30 00 12288 0 off

8 0010 0000 0000 20 00 8192 0 off

4,0078 0001 0000 0000 1 0 0 0 10 08 4104 0 off

4 0001 0000 0000 10 00 4096 0 off

3,5 0000 1110 0000 0 0 1 1 0E 00 3584 0 on

0 0000 0000 00000 00 0 0 on

Analog Inputs 750-472, 474

Input current 4-20mA

Page 96 of the Quatech INTERBUS S user manual — 750-472, 750-474
Page 96 · click to enlarge
Page 96

Binary value X : without meaning F : short circuit or F: open circuit Ü : overflow X F Ü

Hex. Dec. Status LED

30 0110 0000 0000 1 6001 24577 42 on

29,98 0101 1111 1111 1 0 0 0 5F F8 24568 0 on

20,5 0100 0001 1001 1 0 0 0 41 98 16762 0 on

20 0100 0000 0000 4000 16384 0 off

10 0010 0000 0000 2000 8192 0 off

5 0001 0000 0000 1000 4096 0 off

2,5 0000 1000 0000800 2048 0 off

1,25 0000 0100 0000400 1024 0 off

0,625 0000 0010 0000200 512 0 off

0,00976 0000 0000 0000 1 0008 8 0 off

0 0000 0000 0000000 0 0 off

If you have questions about the formatting of this data, please contact WAGO for I/O System technical support.

Analog Inputs 750-472, 474

Input current 0-20mA

Page 97 of the Quatech INTERBUS S user manual — Function clamp and variants
Page 97 · click to enlarge
Page 97
Quatech INTERBUS S — 750-476,750-478 diagram (page 97)
Fig. 144

2-Channel Analog Input ± 10 V, 16 Bit, single ended 750-476 0 -10 V, 16 Bit, single ended 750-478

Quatech INTERBUS S — 750-476,750-478 diagram (page 97)
Fig. 145

Function clamp and variants

Quatech INTERBUS S — Function clamp and variants diagram (page 97)
Fig. 146 · Function clamp and variants

750-476 2-Channel Analog Input ± 10 V, single ended

2 AI ± 10 V DC 16 Bit s.e.

750-476/000-200 2-Channel Analog Input ± 10 V, single ended with status infomation within the data word

2 AI ± 10 V DC 16 Bit s.e. S5-466

Quatech INTERBUS S — Function clamp and variants diagram (page 97)
Fig. 147 · Function clamp and variants

750-478 2-Channel Analog Input 0-10 V, single ended 2 AI 0-10 V DC 16 Bit s.e.

750-478/000-200 2-Channel Analog Input 0-10 V, single ended with status infomation within the data word

2 AI 0-10 V DC 16 Bit s.e. S5-466

Analog Inputs 750-476, 478

4;13614

Page 98 of the Quatech INTERBUS S user manual — Technical description
Page 98 · click to enlarge
Page 98

Technical description

This description is only intended for hardware and software version X 0 4 0 1 - .The serial number can be found on the right side of the module.

The input channels are single ended and they have a common ground potential.

The inputs are connected to I and 0V. The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail.

The input module can be connected to all buscouplers of the :$*2®,22®6

Analog Inputs 750-476, 478

4;13614

Page 99 of the Quatech INTERBUS S user manual — 750-476,750-478
Page 99 · click to enlarge
Page 99
Quatech INTERBUS S — 750-476,750-478 diagram (page 99)
Fig. 148

Item Number 750-476 750-476/000-200 750-478 750-478/000-200 Number of channels 2 Nominal voltage via system voltage (DC/DC) Overvoltage resistance 24 V max. Internal current consumption

75 mA typ.

Input signal +/- 10 V 0 - 10 V Input impedance 130 kΩ typ. Overvoltage protection 24 V protected against polarity reversal Resolution 15 Bit + sign Input filter 50 Hz Noise rejection at sampling frequency

Noise rejection below sampling frequency

Transition frequency 13 Hz Isolation 500 V system/power supply Wandlungszeit 80 ms typ. Bitwidth per channel 16Bit: Data; optional 8Bit: control/status Configuration none, optional via software parameter Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0,08 bis 2,5mm2

Dimensions (mm)WxHxL 12 x 64* x 100 * from upper edge of the carrier rail

Analog Inputs 750-476, 478

4;13614

< -100 dB · < -40 dB

Page 100 of the Quatech INTERBUS S user manual — 750-476,750-478
Page 100 · click to enlarge
Page 100
Quatech INTERBUS S — 750-476,750-478 diagram (page 100)
Fig. 149

All analog values will be shown in a unit numerical format. The resolution for 750-476 and 750-478 is 15 Bit plus sign.

750-476, -478 Input voltage Value Status LED 0-10V ±10V Binary Hex. Dec. (hex) error I (1,2) >11 >11 0111 1111 1111 1111 0x7FFF 32767 0x42 on

Quatech INTERBUS S — 750-476,750-478 diagram (page 100)
Fig. 150

>10,5 >10,5 0111 1111 1111 1111 0x7FFF 32767 0x42 off

10 10 0111 1111 1111 1111 0x7FFF 32767 0x00 off

5 5 0100 0000 0000 0000 0x4000 16384 0x00 off

2,5 2,5 0010 0000 0000 0000 0x2000 8192 0x00 off

1,25 1,25 0001 0000 0000 0000 0x1000 4096 0x00 off

0,0781 0,0781 0000 0001 0000 0000 0x0100 256 0x00 off

0,049 0,049 0000 0000 0001 0000 0x0010 16 0x00 off

0,0003 0,0003 0000 0000 0000 0001 0x0001 1 0x00 off

0 0 0000 0x0000 0 0x00 off

-5 1100 0000 0000 0000 0xC000 49152 0x00 off

-10 1000 0000 0000 0000 0x8000 32768 0x00 off

Analog Inputs 750-476, 478

4;13614

Page 101 of the Quatech INTERBUS S user manual — ±10 V
Page 101 · click to enlarge
Page 101
Quatech INTERBUS S — 750-476,750-478 diagram (page 101)
Fig. 151

For fieldbus master, which evaluates status information in the data word, e.g. from Siemens, a variant of the function clamp is available. The format containes the status in Bit B0 .. B2. The digitalized measuring value is placed at the position Bit B3 .. B15. The numerical format is equivalent to S5 466.

750-476/000-200 Input Value Status LED voltage

X E O*) Hex. Dec. error I (1,2)

±10 V

> 11 0011 1111 1111 1 0 0 1 0x3FF9 16377 0x42 on > 10,5 0011 1111 1111 1 0 0 1 0x3FF9 16377 0x42 off 10 0011 1111 1111 1 0x3FF8 16376 0x00 off 5 0010 0000 0000x2000 8192 0x00 off 2,5 0001 0000 0000x1000 4096 0x00 off 1,25 0000 1000 0000x0800 2048 0x00 off 0,0781 0000 0000 1000x0080 128 0x00 off 0,0049 0000 0000 0000 1 0x0008 8 0x00 off 0 0000 0000 0000x0000 0 0x00 off -5 1110 0000 0000xE000 57344 0x00 off -10 1100 0000 0000xC000 49152 0x00 off < -10,5 1100 0000 0000 1 0xC001 49153 0x41 off < -11 1100 0000 0000 1 0xC001 49153 0x41 on *) X : without meaning, E : short circuit or open circuit, O : overflow

750-478/000-200 Input Value Status LED voltage

X E O*) Hex. Dec. error I (1,2)

> 11 0111 1111 1111 1 0 0 1 0x7FF9 32761 0x42 on > 10,5 0111 1111 1111 1 0 0 1 0x7FF9 32761 0x42 off 10 0111 1111 1111 1 0x7FF8 32760 0x00 off 5 0100 0000 0000x4000 16384 0x00 off 2,5 0010 0000 0000x2000 8192 0x00 off 1,25 0001 0000 0000x1000 4096 0x00 off 0,0781 0000 0001 0000x0100 256 0x00 off 0,049 0000 0000 0001 0x0010 16 0x00 off 0,024 0000 0000 0000 1 0x0008 8 0x00 off 0 0000 0000 0000x0000 0 0x00 off < -0,5 0000 0000 0000 1 0x0001 1 0x41 off < -1 0000 0000 0000 1 0x0001 1 0x41 on *) X : without meaning, E : short circuit or open circuit, O : overflow

Analog Inputs 750-476, 478

4;13614

Binary · 0-10 V Binary

Page 102 of the Quatech INTERBUS S user manual — Status byte
Page 102 · click to enlarge
Page 102

Status byte

Structure of the status byte:

bit 7 6 5 4 3 2 1 0 meaning 0 ERROR res. Overrange Underrange

  • ERROR error at the input channel.
  • Overrange exceed the allowable measuring range.
  • Underrange fall below the allowable measuring range.

Analog Inputs 750-476, 478

4;13614

Page 103 of the Quatech INTERBUS S user manual — Technical Description
Page 103 · click to enlarge
Page 103
Quatech INTERBUS S — Analog Outputs diagram (page 103)
Fig. 152 · Analog Outputs

2 Channel Analog Outputs 0-10 V PN 750-550, 750-580

Quatech INTERBUS S — 2 Channel Analog Outputs 0-10 V PN 750-550, 750-580 diagram (page 103)
Fig. 153 · 2 Channel Analog Outputs 0-10 V PN 750-550, 750-580

Technical Description

This description is only intended for hardware version X 2 A 0 1 -. The serial number can be found on the right side of the module.

The output signal of 750-550/551 is a 0-10 V signal. Sensors may be connected to „O“ and to the common ground.

The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail.

These I/O modules are not provided with integrated power jumper contacts. The power supply is made by the data contacts with a DC-DC converter. The modules can work self-supporting.

The output module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type)

Analog Outputs 750-550,580

Page 104 of the Quatech INTERBUS S user manual — Analog Outputs
Page 104 · click to enlarge
Page 104
Quatech INTERBUS S — Analog Outputs diagram (page 104)
Fig. 154 · Analog Outputs

Item Number 750- 550, 580 Number of channels 2 Nominal voltage via system voltage (DC DC converter) Current consumption (internal)

Quatech INTERBUS S — Analog Outputs diagram (page 104)
Fig. 155 · Analog Outputs

Voltage supply via system voltage (DC-DC) Signal voltage 0-10 V Resistance > 5 kΩ Resolution 12 Bit Isolation 500 V system/power supply Bit width per channel 16 Bit Data, 8 Bit Control/Status Operating temperature 0°C +55°C Configuration none, optional via software parameter Wire connection CAGE CLAMP; 0.08 to 2.5mm2

12 x 64* x 100 (*from upper edge of the carrier rail)

The numerical format All analog values will be shown in a unit numerical format. The resolution is 12 Bits. The 3 LSBs are not taken into account. The following table will explain the numerical format. (750-550).

Quatech INTERBUS S — Analog Outputs diagram (page 104)
Fig. 156 · Analog Outputs

Hex. Dec. 10 0111 1111 1111 1111 7F F8 32767

Analog Outputs 750-550,580

Page 105 of the Quatech INTERBUS S user manual — Analog Outputs
Page 105 · click to enlarge
Page 105
Quatech INTERBUS S — Analog Outputs diagram (page 105)
Fig. 157 · Analog Outputs

In addition to the full 16 bit indication of the measured value it is possible to use the ‘Siemens format’. The measured value is represented by the most significant 12 Bits. The 3 least significant Bits are reserved for diagnostic and status purposes. (750-580)

Quatech INTERBUS S — Analog Outputs diagram (page 105)
Fig. 158 · Analog Outputs

> 10 0101 0000 0000 XXXX 50 01 20481

If you have questions about the formatting of this data, please contact WAGO for I/O System technical support.

Analog Outputs 750-550,580

Page 106 of the Quatech INTERBUS S user manual — Technical Description
Page 106 · click to enlarge
Page 106
Quatech INTERBUS S — 750-552, 554 diagram (page 106)
Fig. 159

2 -Channel Analog Outputs 0-20 mA / 4-20 mA PN 750-552, 554, 584

Quatech INTERBUS S — 750-552, 554 diagram (page 106)
Fig. 160

Technical Description

This description is only intended for hardware version X 2 A 0 1 -. The serial number can be found on the right side of the module.

The output signal of 750-552...555, 584 is a 0-10 mA or 4-20 mA signal. Sensors may be connected to „O“ and to the common ground (0V). The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail. Power connections are made automatically from module to module when snapped onto the DIN rail. For a self-supporting function, the power supply has to be connected by an input module (e.g. 750-602).

The output module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type)

Analog Outputs 750-552, 554, 584

Page 107 of the Quatech INTERBUS S user manual — The numerical format
Page 107 · click to enlarge
Page 107
Quatech INTERBUS S — 750-552, 554 diagram (page 107)
Fig. 161

Item Number 750- 552 554 584 Number of channels 2 Current consumption (internal)

Quatech INTERBUS S — 750-552, 554 diagram (page 107)
Fig. 162

Nominal voltage 24 V DC (-15% /+20%) via power jumper contacts Signal current 0-20mA 4-20mA 4-20mA Resistance

12 x 64* x 100 (*from upper edge of carrier rail)

The numerical format

All analog values will be shown in a unit numerical format. The following table will explain the numerical format. (750-552/554). The 3 LSBs are not taken into account.

Quatech INTERBUS S — The numerical format diagram (page 107)
Fig. 163 · The numerical format

Hex. Dec. 20 20 0111 1111 1111 1111 7F FF 32767

10 12 0100 0000 0000 0000 40 00 16384

5 8 0010 0000 0000 0000 20 00 8192

2.5 6 0001 0000 0000 0000 10 00 4096

0.156 4.125 0000 0001 0000 0000 01 00 256

0.01 4.0078 0000 0000 0001 0000 00 10 16

0.005 4.0039 0000 0000 0000 1000 00 08 8

0 4 0000 0000 0000 0111 00 07 7

Analog Outputs 750-552, 554, 584

Page 108 of the Quatech INTERBUS S user manual — 750-552, 554
Page 108 · click to enlarge
Page 108
Quatech INTERBUS S — 750-552, 554 diagram (page 108)
Fig. 164

In addition to the full 16 bit indication of the measured value it is possible to use the ‘Siemens format’. The measured value is represented by the most significant 12 Bits. The 4 least significant Bits have no function. (750-584)

Quatech INTERBUS S — 750-552, 554 diagram (page 108)
Fig. 165

If you have questions about the formatting of this data, please contact WAGO for I/O System technical support.

Analog Outputs 750-552, 554, 584

Page 109 of the Quatech INTERBUS S user manual — Technical Description
Page 109 · click to enlarge
Page 109
Quatech INTERBUS S — 750-556 diagram (page 109)
Fig. 166

2 Channel Analog Outputs +/- 10 V PN 750-556

Quatech INTERBUS S — 2 Channel Analog Outputs +/- 10 V PN 750-556 diagram (page 109)
Fig. 167 · 2 Channel Analog Outputs +/- 10 V PN 750-556

Technical Description

This description is only intended for hardware version X 2 A 0 1 -. The serial number can be found on the right side of the module.

The output signal of 750-556 is a +/- 10 V signal. Sensors may be connected to „O“ and to the common ground (0V).

The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail. These I/O modules are not provided with integrated power jumper contacts. The power supply is made by the data contacts with a DC-DC converter. The modules can work self-supporting.

The input module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type)

Analog Outputs 750-556

Page 110 of the Quatech INTERBUS S user manual — 750-556
Page 110 · click to enlarge
Page 110
Quatech INTERBUS S — 750-556 diagram (page 110)
Fig. 168

Item Number 750- 556 Number of channels 2 Nominal voltage via system voltage (DC DC converter) Current consumption (internal)

Quatech INTERBUS S — 750-556 diagram (page 110)
Fig. 169

Signal voltage +/- 10 V Resistance > 5 kΩ Resolution 12 Bit Isolation 500 V System/Power supply Bit width per channel 16 Bit Data, 8 Bit Control/Status Operating temperature 0°C +55°C Configuration none, optional via software parameter Wire connection CAGE CLAMP; 0.08 to 2.5mm2

12 x 64* x 100 (*from upper edge of the carrier rail)

Analog Outputs 750-556

Page 111 of the Quatech INTERBUS S user manual — 750-556
Page 111 · click to enlarge
Page 111
Quatech INTERBUS S — 750-556 diagram (page 111)
Fig. 170

All analog values will be shown in a unit numerical format. The resolution is 12 Bits and the 3 LSBs are ignored. The following table will explain the numerical format.

Quatech INTERBUS S — 750-556 diagram (page 111)
Fig. 171

Hex. Dec. 10 0111 1111 1111 1111 7F FF 32767

Analog Outputs 750-556

Page 112 of the Quatech INTERBUS S user manual — Technical Data:
Page 112 · click to enlarge
Page 112
Quatech INTERBUS S — Endand supply terminal blocks diagram (page 112)
Fig. 172 · Endand supply terminal blocks

End module, Potential multiplication module, Separation module PN750-600, 750-614, 750-616, 750-616/030-000

Quatech INTERBUS S — End module, Potential multiplication module, Separation module PN750-600, 750-614, 750-616, 750-616/030-000 diagram (page 112)
Fig. 173 · End module, Potential multiplication module, Separat…

After the fieldbus node is assembled with the correct buscoupler and selected I/O modules, the end module is snapped onto the assembly. It completes the internal data circuit and ensures correct data flow.

The potential multiplication module allows additional + and - voltage connection points (up to 4 additional). This eliminates external terminal blocks.

Technical Data:

Item Number 750- 600 614 Voltage - 24 V - 230 V AC/DC Current on contacts - max. 10 mA Operating temperature 0 °C ... + 55 °C Wire connection CAGE CLAMP; 0,08 to 2,5 mm² Dimensions (mm) WxHxL 12 x 64 x 100, (from the upper edge of the carrier rail)

Quatech INTERBUS S — Technical Data: diagram (page 112)
Fig. 174 · Technical Data:

End module, Potential multiplication 750-600,614,616

Page 113 of the Quatech INTERBUS S user manual — Technical Data:
Page 113 · click to enlarge
Page 113

Separation module

Technical description:

Use of this module allows increased air- and creepage distances between different field voltages within a node.

There are two different types of the separation module. With PN 750-616 you get a module without printing. PN 750-616/030-000 looks like the right one in the above picture.

Technical Data:

Item No. 750-616, 750-616/030-000 Dimensions (mm) W x H x L 12 x 64* x 100, (*from the upper edge of the carrier rail)

End module, Potential multiplication 750-600,614,616

Page 114 of the Quatech INTERBUS S user manual — Supply modules PN750-601, 602, 609, 610, 611, 612, 613, 615
Page 114 · click to enlarge
Page 114
Quatech INTERBUS S — 750-601, 602, 609, 610, 611, 612, 613, 615 diagram (page 114)
Fig. 175

Supply modules PN750-601, 602, 609, 610, 611, 612, 613, 615

Quatech INTERBUS S — Supply modules PN750-601, 602, 609, 610, 611, 612, 613, 615 diagram (page 114)
Fig. 176 · Supply modules PN750-601, 602, 609, 610, 611, 612, 6…

The supply module provides I/O module power through the power jumper contacts. Maximum current supply to all connected modules is 10 A. Maximum current supply to the modules with fuse holder is 6.3 A. Should higher currents be necessary, intermediate supply modules may be added in the assembly. The modules 750-601, 609, 615, 610 and 611 are additionally equipped with a fuse holder. The change of the fuse is very easy by drawing out the fuse holder and changing the fuse. A blown fuse is indicated by a LED. The modules 750-610 and 611 send information about the status of the supply module to the fieldbus coupler through two input bits. Bit1 Bit2 Description 0 0 voltage < 15 V DC 1 0 fuse blown 0 1 fuse o.k., voltage o.k.

Quatech INTERBUS S — Supply modules PN750-601, 602, 609, 610, 611, 612, 613, 615 diagram (page 114)
Fig. 177 · Supply modules PN750-601, 602, 609, 610, 611, 612, 6…

Using the supply modules you have to look for the allowed voltage. The following table shows the voltage for the supply modules.

The supply module 750-613 supplies the field side and te internal databus system voltage. The internal system voltage can supply 2 A max. If the sum of the internal current consumption exceeds 2 A, an additional supply module must be added.

Supply modules 750-601,602, 609,615,610,611,613

Page 115 of the Quatech INTERBUS S user manual — 750-601, 602, 609, 610, 611, 612, 613, 615
Page 115 · click to enlarge
Page 115
Quatech INTERBUS S — 750-601, 602, 609, 610, 611, 612, 613, 615 diagram (page 115)
Fig. 178

Item Number 750- 602 612 613 Voltage 24 V DC 0 - 230 V AC/DC 24 V DC (-15%/+20%) Current via contacts max. 10 A Operating temperature 0 °C ... + 55 °C Wire connection CAGE CLAMP; 0,08 to 2,5 mm² Dimensions (mm) W x H x L 12 x 64 x 100, (from the upper edge of the carrier rail) internal current 750-613: max. 2 A

Quatech INTERBUS S — 750-601, 602, 609, 610, 611, 612, 613, 615 diagram (page 115)
Fig. 179
Quatech INTERBUS S — 750-601, 602, 609, 610, 611, 612, 613, 615 diagram (page 115)
Fig. 180

Item Number 750- 601 609 615 Voltage 24 V DC 230 V AC 120 V AC Current via contacts Fuse

max. 6.3 A 5 x 20, 6.3 A Operating temperature 0 °C ... + 55 °C Wire connection CAGE CLAMP; 0,08 to 2,5 mm² Dimensions (mm) W x H x L 12 x 64 x 100, (from the upper edge of the carrier rail)

Quatech INTERBUS S — 750-601, 602, 609, 610, 611, 612, 613, 615 diagram (page 115)
Fig. 181

Item Number 750- 610 611 Number of inputs 2 Current consumption 5 mA Internal bitwidth 2 Voltage 24 V DC 230 V AC Current via contacts Fuse

max. 6.3 A 5 x 20, 6.3 A Operating temperature 0 °C ... + 55 °C Wire connection CAGE CLAMP; 0,08 to 2,5 mm² Dimensions (mm) W x H x L 12 x 64 x 100, (from the upper edge of the carrier rail)

Supply modules 750-601,602, 609,615,610,611,613

Page 116 of the Quatech INTERBUS S user manual — Technical description
Page 116 · click to enlarge
Page 116
Quatech INTERBUS S — 750-622 diagram (page 116)
Fig. 182
Quatech INTERBUS S — 750-622 diagram (page 116)
Fig. 183

Technical description

The binary spacer module reserves bit-addresses in the WAGO buscoupler. The number of in or outputs can be chosen by two DIP switches. 2, 4, 6 or 8 bits are possible (1, 2, 3 or 4-channel modules). A third DIP Switch chooses inputs or outputs. The kind of configuration is indicated by means of 3 LEDs even if there is no voltage applied.

The binary spacer module works like a supply module. The power supply must be made for the following modules.

Binary spacer module 750-622 1

:$*2⇓,2⇓6<67(0

Page 117 of the Quatech INTERBUS S user manual — 750-622
Page 117 · click to enlarge
Page 117
Quatech INTERBUS S — 750-622 diagram (page 117)
Fig. 184

Item number 750- 622 Number of in- or outputs 2, 4, 6 or 8 Nominal voltage 5 V DC internal Internal current consumption 10 mA max. Voltage (field side) 24 V DC (-15%/+20%) Current via power jumper contacts

Input current (field side) - Isolation 500 V system/power supply Internal bit width 2, 4, 6 oder 8 Configuration none, optional via software parameter Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 to 2.5mm2

Dimensions (mm) WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail)

The DIP switches and LEDs are used as follows. When the switch is OFF the LED is also OFF (dark green symbol). When the switch is ON the LED lightens (yellow symbol).

Quatech INTERBUS S — 750-622 diagram (page 117)
Fig. 185

Binary spacer module 750-622 2

:$*2⇓,2⇓6<67(0

Page 118 of the Quatech INTERBUS S user manual — Technical Description:
Page 118 · click to enlarge
Page 118
Quatech INTERBUS S — SSI Encoder Interface diagram (page 118)
Fig. 186 · SSI Encoder Interface
Quatech INTERBUS S — SSI Encoder Interface diagram (page 118)
Fig. 187 · SSI Encoder Interface

Technical Description:

This technical description is only valid for hardware and software versions X 2 B 0 2 . The product series number is printed on the right side of the module.

The operational mode of the module is factory preset to discern a 24 bit absolute encoder Graycode signal transmitted at 125kHz.

The following description is preliminary and is applicable to the factory configuration.

The SSI Interface is able to run with all WAGOÇI/OÇSYSTEM bus-couplers (except for the economy type).

SSI encoder 750-630

Page 119 of the Quatech INTERBUS S user manual — SSI Encoder Interface
Page 119 · click to enlarge
Page 119
Quatech INTERBUS S — SSI Encoder Interface diagram (page 119)
Fig. 188 · SSI Encoder Interface

Series 750 630 630/000-001 630/000-006 Encoder connections Data Input: D+; D-; Clock Output: CI+; CI- Current consumption (internal)

85mA typ.

Power supply 24V DC (-15%/+20%) Sensor power supply 24V DC via power jumper contacts Baud rate max. 1 MHz Data field width 32 Bit Signal output (clock) differential RS 422 Signal input (positional) differential RS 422 Output data format Graycode / Dualcode Bit width 32 Bit: Data; 8 Bit: Control/Status Configuration none, optional via software parameter Signal isolation 500 V system/power supply Temperature range 0°C +55°C Wire connection CAGE CLAMP; 0.08 x 2.5mm2

AWG 28-14 Dimensions (mm) WxHxL 12 x 64* x 100 (*from upper edge of carrier rail) Default Configuration 125 kHz 125 kHz 250 kHz Graycode Binary Graycode 24 Bit Data Resolution

24 Bit Data Resolution

24 Bit Data Resolution

SSI encoder 750-630

Page 120 of the Quatech INTERBUS S user manual — SSI Encoder Interface
Page 120 · click to enlarge
Page 120
Quatech INTERBUS S — SSI Encoder Interface diagram (page 120)
Fig. 189 · SSI Encoder Interface
Quatech INTERBUS S — SSI Encoder Interface diagram (page 120)
Fig. 190 · SSI Encoder Interface

Input Type Function Signal D+ and Signal D- Input, RS422 Positional data from encoder, Graycode. Signal Cl+ and Signal CL- Output, RS422 Clock signal output for communications interface. +24 V DC Input 24 V DC supply voltage to module, field connection. 0 V DC Input 0 V DC supply voltage return to module, field connection.

The use of this module in conjunction with a SSI encoder provides direct positional information rather than the type of data resultant from incremental type encoders. Absolute encoders are comprised of several data disks which generate a data word which is unique through out the 360 degrees of rotation. The data format is a modified binary pattern in either Graycode or Dualcode.

The resolution of the sensor depends upon the configuration of the sensor and the physical number of revolutions in the motion profile. Since the basis of the encoder is to provide absolute positional information based upon a mechanical configuration limited to one revolution or less. The maximum resolution of this module is 24 bit.

The frequency of the data signal input to the SSI module is maintained at 125 kHz. Listed below are the recommended cable lengths for the various clock signal Baud rates.

Baud rate Maximum cable length 100 kHz 400 meters 200 kHz 200 meters 300 kHz 100 meters 400 kHz 50 meters

SSI encoder 750-630

Page 121 of the Quatech INTERBUS S user manual — Organization of the inand output data for Interbus
Page 121 · click to enlarge
Page 121

Organization of the inand output data for Interbus

The module is seen like an analog input with 2 x 16 Bit input data.

Inputs:

Word Data Word Designation D0 (Bit 0-15) Positional data, Input byte 1

Positional data, Input byte 0 D1 (Bit 16-31) Positional data, Input byte 3

Positional data, Input byte 2

SSI encoder 750-630

Page 122 of the Quatech INTERBUS S user manual — Technical Description:
Page 122 · click to enlarge
Page 122
Quatech INTERBUS S — Quadrature Encoder Interface diagram (page 122)
Fig. 191 · Quadrature Encoder Interface
Quatech INTERBUS S — Quadrature Encoder Interface diagram (page 122)
Fig. 192 · Quadrature Encoder Interface

Technical Description:

This technical description is only valid for hardware and software versions X 2 B 0 1 . The product series number is printed on the right side of the module.

The described operational mode is 4 times or quadrature sampling.

The following description is preliminary and is applicable to the factory configuration.

The Quadrature Encoder Interface is able to run with all WAGOÇI/OÇSYSTEM bus- couplers (except for the economy type).

Quadrature Encoder 750-631

Page 123 of the Quatech INTERBUS S user manual — Technical Data:
Page 123 · click to enlarge
Page 123

Technical Data:

Series 750- 631 631/000-001 Encoder connections A, A(inv.); B, B(inv.); Index, Index(inv.) Current consumption (internal)

Sensor supply voltage 5 V DC Data word 16 Bit Binary Maximum frequency 1 MHz Counter modes 1-2-4 times sampling Data latch word 16 Bit Commands read, reset, start Supply voltage 24 V DC (-15%/+20%) Current consumption 85mA Field (without sensor) Sensor 0.1 A (without sensor load) Bit width 1 x 32 Bit: Data; 8 Bit:Control/Status Configuration none, optional via software parameter Operational temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 x 2.5mm2

AWG 28-14 Dimensions (mm) WxHxL 24 x 64* x 100 (*from upper edge of the carrier rail) Default configuration 4 times sampling 1 time sampling

25 mA · Quadrature Encoder 750-631

Page 124 of the Quatech INTERBUS S user manual — Quadrature Encoder Interface
Page 124 · click to enlarge
Page 124
Quatech INTERBUS S — Quadrature Encoder Interface diagram (page 124)
Fig. 193 · Quadrature Encoder Interface

The quadrature encoder interface accepts up to two input signals for the counting increment. The index pulse may also be considered should the control configuration require. There is also a Latch and Gate input available on the module for added functionality.

The quadrature encoder provides two signals that are shifted 90 degrees from each other, signals A and B. In order to achieve a better common mode noise rejection ratio, the output signals from the encoder are transmitted via a differential signal. Their complement signals, A(inv.) and B(inv.) are also transmitted. A directional determination may be made by which signal leads. If the A signal leads, the direction is considered to be forward. If the B signal leads, the direction is considered to be reverse. By exchanging the A and A(inv.) the phase relationship will be changed by 180 degrees, thus allowing the direction to be preset via the wiring configuration. Most quadrature encoders have an Index signal, or Z rev, as well as the incremental signal. This signal provides one pulse per revolution with a duration equal to an incremental pulse.

The inputs to the quadrature encoder module must be supplied from an encoder with Line Driver Outputs for proper operation. The 5 Volt DC output may be used to power the encoder. The 24 Volt DC input supply must be provided from an external power supply. The Gate and Latch inputs are 24 Volt DC.

Module Inputs and Outputs

Quatech INTERBUS S — Quadrature Encoder Interface diagram (page 124)
Fig. 194 · Quadrature Encoder Interface

Shield Input Shield connection for encoder wiring Sensor 0V DC Output Supply return for encoder supply Sensor +5V DC Output 5 Volt DC supply for encoder +24V DC Input 24 Volt DC supply, field connection 0V DC Input. Supply return, field connection Gate Input, 24V DC 24 Volt DC input for gate signal

Latch Input, 24V DC 24 Volt DC input for Latch signal

The Input Gate stops the counter. Only 0 V or an open connection initialize the counter. 24 V stops the counting process.

Quadrature Encoder 750-631

Page 125 of the Quatech INTERBUS S user manual — Quadrature Encoder Interface
Page 125 · click to enlarge
Page 125

The input Latch controls the overtaking of the actual counter value into the Latchregister. This input is activated by teh control bit EN_LATEXT („1“). EN_LACT has to be deactivated („0“). The first change from 0 V to 24 V at the Latch input takes the actual counter value into the Latchregister. The control byte contains the information as listed below.

Quatech INTERBUS S — Quadrature Encoder Interface diagram (page 125)
Fig. 195 · Quadrature Encoder Interface

Control Byte Configuration Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 x CFAST_M x x CNT_SET EN_LATEXT EN_LATC 0 x Operation Mode

x x Counter Set Release Latch Release Index Pulse

Please note Bit 7 is a reserved bit and must always be set to 0. It is responsible for register communication which is not decribed in this chapter.

Quatech INTERBUS S — Quadrature Encoder Interface diagram (page 125)
Fig. 196 · Quadrature Encoder Interface

Bit Function CFAST_M Fast mode operation. Only the counter module function will be operable. All other control bits will be ignored. CNT_SET The counter module will be preset to a count value with a rising edge. EN_LATEXT 0=The external latch input is deactivated. 1=The module will latch in the counter data on the first rising edge. Other changes have no effect. EN_LACT 0=Latching data with the Index pulse is deactivated. 1=The Index pulse will latch in the counter data on the first rising edge. Other changes have no effect.

The status byte contains the information as listed below.

Status Byte Configuration Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 x x OVERFLOW UNDERFLOW CNTSET_ACC LATEXT_ VAL

LATC_ VAL 0 x x Counter Overflow

External Latch Ack.

Bit Function OVERFLOW The Overflow bit will be set if the counter value rolls over from 65535 to 0. This bit will automatically be reset if the counter passes through more than one third of the count range, 21845 to 21846, or if an Underflow occurs. UNDERFLOW The Underflow bit will be set if the counter value rolls back from 65535 to 0. This bit will automatically be reset if the counter passes through more than two thirds of the count range, 43690 to 43689, or if an Overflow occurs. CNTSET_ACC The Counter Set Acknowledge but is set when a valid counter value is preset to the module. LATEXT_VAL The Latch External Valid Acknowledge bit is set when a counter value is latched into the module via the Latch input. LACT_VAL The Latch Index Pulse Valid Acknowledge bit is set when a counter value is latched into the module via the Index pulse.

Show 4 more labels / short text on this page
Counter Underflow · Counter Set Acknowledge · Latched Data Set · Quadrature Encoder 750-631
Page 126 of the Quatech INTERBUS S user manual — Quadrature Encoder Interface
Page 126 · click to enlarge
Page 126

It is possible to process and/or check the below listed actions via the control and status bits.

Extending the 16 bit counting range: The internal counting range is 16 bits or a maximum value of 65535. Should the application require an extended count range the location-difference-integration method may be employed. This method uses the control system to store the interrogated counter value. Any new interrogated value will have the previously stored counter value subtracted from it. This value will then be added to an accumulated register value. It is assumed that the counter difference of the two interrogated values is smaller than 16 bits therefore overflows need not be considered.

Another method calculates the extended counter range via the underflow and overflow status bits. The interrogated value is either added or subtracted to the accumulation register depending upon the status of the overflow or underflow bits.

Set Counter Position: The presetting of the counter is possible via the CNT_SET bit. The desired preset is loaded into the data register and the CNT_SET bit is set from 0 to 1. The CNTSET_ACC bit will be set to 1 when the preset value is loaded into the count register.

Maintaining the Present Counter Position: The counter present value may be maintained or latched via the external Latch input. First the external latch must be enabled via the EN_LATEXT bit. Once the input is enabled, the data will be latched into the counter module upon a 0 to 1 transition. Upon completion of the latch process the external latch valid bit LATEXT_VAL will be set to 1.

Maintaining a Reference Point: The storage of a present counter value may also accomplished via the Index pulse from the encoder. First the index latch enable bit must be set, EN_LACT, to a value 1. The counter present value will be latched upon the low to high transition of the Index input. Upon completion of the data latch process the Index Latch Valid bit, LACT_VAL will be set to 1.

Quadrature Encoder 750-631

Page 127 of the Quatech INTERBUS S user manual — Quadrature Encoder Interface
Page 127 · click to enlarge
Page 127
Quatech INTERBUS S — Quadrature Encoder Interface diagram (page 127)
Fig. 197 · Quadrature Encoder Interface

The module is seen like an analog module with 3 x 16 Bit input and output data.

Outputs:

Quatech INTERBUS S — Quadrature Encoder Interface diagram (page 127)
Fig. 198 · Quadrature Encoder Interface

Word function D0 (Bit 0-15) control byte set counter-Byte1 D1 (Bit 16-31) set counter-Byte0 D2 (Bit 32-47)

Inputs:

Quatech INTERBUS S — Quadrature Encoder Interface diagram (page 127)
Fig. 199 · Quadrature Encoder Interface

Word function D0 (Bit 0-15) Statusbyte counter byte 1 D1 (Bit 16-31) counter byte 0 D2 (Bit 32-47) Latch value-Byte1 Latch value-Byte0

Quadrature Encoder 750-631

Page 128 of the Quatech INTERBUS S user manual — RS232,TTY,RS485 750-650,651,653
Page 128 · click to enlarge
Page 128
Quatech INTERBUS S — Special terminal blocks diagram (page 128)
Fig. 200 · Special terminal blocks

RS232C Interface, TTY Interface -20 mA Current Loop RS485C Interface PN 750-650, 750-651, 750-653, 750-650/000-001

Quatech INTERBUS S — Special terminal blocks diagram (page 128)
Fig. 201 · Special terminal blocks

Technical Description:

This technical description is only valid for hardware and software versions X 2 C 0 3 . The product series number is printed on the right side of the module.

The operational mode described below is the presetting.

The following description is preliminary and is applicable to the factory configuration. Many other operational modes are possible (please contact WAGO for the corresponding settings).

The interface module is able to run with all WAGOÇI/OÇSYSTEM buscouplers (except for the economy type).

RS232,TTY,RS485 750-650,651,653

Page 129 of the Quatech INTERBUS S user manual — RS232,TTY,RS485 750-650,651,653
Page 129 · click to enlarge
Page 129

Technical Data:

Series 750- 650,650/000-001 651 653 Transmission channel 2 (1/1), T x D and R x D, full duplex

2, autom. Send/Receive Transmission rate 1200 - 19200 baud Bit skew < 3 % - - Bit transmission - 2 x 20 mA passive

acc. to ISO 8482/ DIN 66259 T 4 Resistance - < 500 Ω - Current consumption (internal)

50 mA max.

Transmission length max. 15 m RS 232 cable max. 1000 m twisted pair

max. 500 m twisted pair Input buffer 128 bytes Output buffer 16 bytes Voltage supply via internal system supply Isolation 500 V System/Supply Bit width internal 1 x 40 bit, 1 x 8 bit Control/Status Configuration none, parameter configuration with software Operating temperature 0 °C ... + 55 °C Wire connection CAGE CLAMP; 0,08 bis 2,5 mm² Dimensions(mm) W x H x L

12 x 64* x 100 (*from upper edge of the carrier rail)

Factory preset Baud rate Bit width internal

9600 baud 1 x 24 bit in/out, 1 x 8 bit Control/Status

RS232,TTY,RS485 750-650,651,653

Page 130 of the Quatech INTERBUS S user manual — RS232,TTY,RS485 750-650,651,653
Page 130 · click to enlarge
Page 130

Description of RS 232:

The interface module is designed to operate with all WAGO I/O fieldbus couplers. The serial interface module allows the connection of RS 232-Interface devices to the WAGO I/O SYSTEM. The RS 232 Interface module can provide gateways within the fieldbus protocol. This allows serial equipment such as printers, barcode readers, and links to local operator interfaces to communicate directly by the fieldbus protocol with the PLC or PC Master. This module supports no higher level of protocol. Communication is made completely transparent to the fieldbus allowing flexibility in further applications of the serial interface module. The communication protocols are configured at the Master PLC or PC.

The 128 byte input buffer provides for high rates of data transmission. When using lower rates of transmission speed you can collect the received data, with less priority, without loosing data. The 16 byte output buffer provides for faster transmission of larger data strings.

FUNCTION

The data transmission takes place at 9.600 baud (default value). 1 startbit, 8 databits and 1 stopbit will be transmitted. No parity is available. The user controls data via the RTS and CTS signals. These signals are generated in the module depending on the loading status of the buffers. These controls can be deactivated by means of an external jumper. RTS and CTS are to be connected.

For testing purposes the Windows 3.11 terminal emulation can be used. A cable with a 9- pole sub-D socket is required. Pin 5 is connected to input M. Pin 2 is connected to TxD and Pin 3 to RxD. RTS and CTS of the module are connected. A hardwarehandshake between terminal emulation and SPS is not possible though.

Quatech INTERBUS S — FUNCTION diagram (page 130)
Fig. 202
Figure 2Data Word Signal

RS232,TTY,RS485 750-650,651,653

Page 131 of the Quatech INTERBUS S user manual — SRLQW WRSRLQWFRQQHFWLRQ
Page 131 · click to enlarge
Page 131
Quatech INTERBUS S — Special terminal blocks diagram (page 131)
Fig. 203 · Special terminal blocks

The interface module is designed to operate with all WAGO I/O fieldbus couplers. The TTY interface module allows the connection of TTY-Interface devices to the WAGO I/O SYSTEM. The TTY Interface module can provide gateways within the fieldbus protocol. This allows serial equipment such as printers, barcode readers, and links to local operator interfaces to communicate directly by the fieldbus protocol with the PLC or PC Master. This module supports no higher level of protocol. Communication is made completely transparent to the fieldbus allowing flexibility in further applications of the serial interface module. The communication protocols are configured at the Master PLC or PC.

The 128 byte input buffer provides for high rates of data transmission. When using lower rates of transmission speed you can collect the received data, with less priority, without loosing data. The 16 byte output buffer provides for faster transmission of larger data strings.

FUNCTION

The data transmission takes place at 9600 baud (default value). 1 startbit, 8 databits and 1 stopbit will be transmitted. No parity is available. The drivers are high ohmic. The control of data is made by the user software.

The TTY Interface is passive in sending and receiving , thus having no current sources. For data conversion an active partner is needed or an additional current source has to be connected.

FXUUHQW VRXUFH

FXUUHQW VRXUFH

Quatech INTERBUS S — FXUUHQW VRXUFH diagram (page 131)
Fig. 204
Quatech INTERBUS S — FXUUHQW VRXUFH diagram (page 131)
Fig. 205
Quatech INTERBUS S — FXUUHQW VRXUFH diagram (page 131)
Fig. 206

SRLQW WRSRLQWFRQQHFWLRQ

SRLQWWRSRLQWFRQQHFWLRQZLWKSDVVLYH SDUWQHUVDQGDGGLWLRQDOFXUUHQWVRXUFHV

EXVFRQQHFWLRQZLWKDFXUUHQWVRXUFH

ZLWKDFWLYHSDUWQHUV

DQGDSDVVLYHPRGXOH

RS232,TTY,RS485 750-650,651,653

Page 132 of the Quatech INTERBUS S user manual — SRLQWWRSRLQWFRQQHFWLRQ EXVFRQQHFWLRQ
Page 132 · click to enlarge
Page 132
Quatech INTERBUS S — Special terminal blocks diagram (page 132)
Fig. 207 · Special terminal blocks

The interface module is designed to operate with all WAGO I/O fieldbus couplers. The serial interface module allows the connection of RS485 or RS488-Interface devices to the WAGO I/O SYSTEM. The RS485/RS488 Interface module can provide gateways within the fieldbus protocol. This allows serial equipment such as printers, barcode readers, and links to local operator interfaces to communicate directly by the fieldbus protocol with the PLC or PC Master. This module supports no higher level of protocol. Communication is made completely transparent to the fieldbus allowing flexibility in further applications of the serial interface module. The communication protocols are configured at the Master PLC or PC.

The 128 byte input buffer provides for high rates of data transmission. When using lower rates of transmission speed you can collect the received data, with less priority, without loosing data. The 16 byte output buffer provides for faster transmission of larger data strings.

FUNCTION

The data transmission takes place at 9,600 baud (default value). 1 startbit, 8 databits and 1 stopbit will be transmitted. No parity is available. The drivers are high ohmic. The control of data is made by the user software.

The interface module can be used for bus connections as well as for point to point connections. With bus connections, modules that are not connected to the power supply can also be wired. They do not disturb the bus connection.

Quatech INTERBUS S — FUNCTION diagram (page 132)
Fig. 208
Quatech INTERBUS S — FUNCTION diagram (page 132)
Fig. 209

SRLQWWRSRLQWFRQQHFWLRQ EXVFRQQHFWLRQ

RS232,TTY,RS485 750-650,651,653

Page 133 of the Quatech INTERBUS S user manual — RS232,TTY,RS485 750-650,651,653
Page 133 · click to enlarge
Page 133
Quatech INTERBUS S — Special terminal blocks diagram (page 133)
Fig. 210 · Special terminal blocks

The module is a combined analog input and output module with 2 x 16 bit input and output data. The transfer of the data to be transmitted and the received data is made via up to 3 output and 3 input bytes. One control byte and one status byte are used to control the floating data. Requests are indicated by a change of a bit. An assigned bit indicates execution by adopting the value of the request bit.

Up to 3 characters which have been received via interface can be stored in the input bytes 0 to 2. The output bytes will contain the characters to be sent.

The control byte consists of the following bits:

Quatech INTERBUS S — Special terminal blocks diagram (page 133)
Fig. 211 · Special terminal blocks

Control Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 OL2 OL1 OL0 0 IR RA TR Con- stant value must always be 0.

Frames available in output area, OL2 is always 0. eg. OL2, OL1, OL0 = 0,1,1 3 characters should be sent and put into the output.

The status byte consists of the following bits:

Quatech INTERBUS S — Special terminal blocks diagram (page 133)
Fig. 212 · Special terminal blocks

Status Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 IL2 IL1 IL0 BUF_F IA RR TA Con- stant value must always be 0.

Frames available in input area, IL2 is always 0. eg. IL2,IL1,IL0 = 0,1,0 2 characters were received and reside in input 0 and input 1.

RS232,TTY,RS485 750-650,651,653

Page 134 of the Quatech INTERBUS S user manual — RS232,TTY,RS485 750-650,651,653
Page 134 · click to enlarge
Page 134

The PLC is able to control transmission and reception of data by means of the control byte and the status byte.

Initialization of the module:

  • set IR in the control byte
  • transmit/receive functions are blocked
  • output/input buffers are erased
  • serial interface module will load its configuration data
  • Transmitting data :
  • TR ≠ TA: put characters into output byte 0 to 2
  • amount of characters is specified in OL0 to OL2
  • TR is inverted and read out
  • characters are put into output buffer if TR=TA
  • Receiving data :
  • RR ≠ RA: in input byte 0 to 2 characters are available
  • amount of characters is specified in IL0 to IL2
  • charactersin IL0 to IL2 are read out
  • RA is inverted and read out
  • all characters are read when RR=RA

The transmitting and receiving of data can be done simultaneously. The initialization request has prioirity and will stop transmitting and receiving of data immediately.

Message: input buffer full (Bit 3) Input buffer is full. Data which are received now are lost.

RS232,TTY,RS485 750-650,651,653

Page 135 of the Quatech INTERBUS S user manual — RS232,TTY,RS485 750-650,651,653
Page 135 · click to enlarge
Page 135
Quatech INTERBUS S — Special terminal blocks diagram (page 135)
Fig. 213 · Special terminal blocks

The module is initialized.

- The initialization bit in the control byte is set.

Output byte 0 Control byte Output byte 2 Output byte 1 0x00 0000.0100 0x00 0x00

- After the initialization has been executed, the status byte will give back 000.0100.

Input byte 0 Status byte Input byte 2 Input byte 1 XX 0XXX.X0XX XX XX Module is still being reset XX 0XXX.X1XX XX XX Initialization completed

Sending of the data string “Hello”:

- The first 3 characters and the buffer length of 3 are transmitted.

Output byte 0 Control byte Output byte 2 Output byte 1 ‘H’ (0 x 48) 0011.0000 ‘l’ (0 x 6C) ‘e’ (0 x 65)

- The transmission request bit (TR) is inverted.

Output byte 0 Control byte Output byte 2 Output byte 1 ‘H’ 0011.0001 ‘l’ ‘e’

- As soon as TR=TA, the rest of the data can be sent.

Quatech INTERBUS S — Special terminal blocks diagram (page 135)
Fig. 214 · Special terminal blocks

Input byte 0 Status byte Input byte 2 Input byte 1 XX 0XXX.XXX 0 XX XX The data is still being transferred.

- The last 2 characters and the buffer length of 2 are transmitted.

Output byte 0 Control byte Output byte 2 Output byte 1 ‘l’ 0010.0001 XX ‘o’ (0 x 6F)

- The transmission request bit (TR) is inverted.

Output byte 0 Control byte Output byte 2 Output byte 1 ‘l’ 0010.0000 XX ‘o’

RS232,TTY,RS485 750-650,651,653

Page 136 of the Quatech INTERBUS S user manual — RS232,TTY,RS485 750-650,651,653
Page 136 · click to enlarge
Page 136

- As soon as TA = TR, the data has been transferred to the output buffer.

Input byte 0 Status byte Input byte 2 Input byte 1 XX 0XXX.XXX1 XX XX The data is still being transferred. XX 0XXX.XXX0 XX XX Data transfer completed.

Receiving the character chain “WAGO”

- As soon as RA≠RR, the input bytes contain data.

Output byte 0 Control yte Output byte 2 Output byte 1 XX 0XXX.000X XX XX

Input byte 0 Status byte Input byte 2 Input byte 1 XX 0XXX.0X0X XX XX No received data available. ‘W’ (0 x 57) 0011.0X1X ‘G’ (0 x 47) ‘A’ (0 x 41) The information is in the input bytes.

- After the 3 characters have been processed, RA is inverted.

Output byte 0 Control byte Output byte 2 Output byte 1 XX 0XXX.001X XX XX

- If RA≠RR, the receiving of additional characters will continue.

Input byte 0 Status byte Input byte 2 Input byte 1 XX 0XXX.0X1X XX XX No received data available. ‘O’ (0 x 4F) 0001.0X0X XX XX The information is in the input bytes.

- After the characters have been processed, RA is inverted.

Output byte 0 Control byte Output byte Output byte XX 0XXX.000X XX XX

0 x 23 is a hexadecimal value 0101.1001 is a binary value An X indicates that this particular value has no importance. XX indicates that the whole value has no importance.

Status IndicatorsThe 3 green LEDs have the following function:

Function Non-Function Output Status TxD Input Status RxD

RS232,TTY,RS485 750-650,651,653

Page 137 of the Quatech INTERBUS S user manual — RS232,TTY,RS485 750-650,651,653
Page 137 · click to enlarge
Page 137
Quatech INTERBUS S — Special terminal blocks diagram (page 137)
Fig. 215 · Special terminal blocks

Structure of the in and output data for Interbus

The module is a combined input and output module with 2 x 16 bit input and output data.

Outputs:

Word Description D0 (bit 0-15) Output byte0 Control byte D1(bit16-31) Output byte2 Output byte1

Inputs:

Word Description D0 (bit 0-15) Input byte0 Status byte D1(bit16-31) Input byte2 Input byte1

The RS232 module is also available with a data format of 5 bytes (item-no. 750- 650/000-001).

Outputs:

Quatech INTERBUS S — Structure of the in and output data for Interbus diagram (page 137)
Fig. 216 · Structure of the in and output data for Interbus

Word Description D0 (bit 0-15) Control byte Output byte0 D1(bit16-31) Output byte1 Output byte2 D2(bit32-47) Output byte3 Output byte4

Inputs:

Quatech INTERBUS S — Structure of the in and output data for Interbus diagram (page 137)
Fig. 217 · Structure of the in and output data for Interbus

Word Description D0 (bit 0-15) Status byte Input byte0 D1(bit16-31) Input byte1 Input byte2 D2(bit32-47) Input byte3 Input byte4

Quatech INTERBUS S — Structure of the in and output data for Interbus diagram (page 137)
Fig. 218 · Structure of the in and output data for Interbus

RS232,TTY,RS485 750-650,651,653

Page 138 of the Quatech INTERBUS S user manual — 750-654
Page 138 · click to enlarge
Page 138
Quatech INTERBUS S — 750-654 diagram (page 138)
Fig. 219
Quatech INTERBUS S — 750-654 diagram (page 138)
Fig. 220

This technical description is only valid for hardware and software versionx X 2 C 0 0 -. The product series number is printed on the right side of the module.

The operational mode described below is for the factory preset mode.

The following description is preliminary and is applicable to the factory configuration. Many other operational modes are possible (please contact WAGO for the corresponding settings.)

The data exchange module is able to run with all :$*2Ç,2Ç6<67(0 buscouplers (except for the economy type).

Data exchange module 750-654

Page 139 of the Quatech INTERBUS S user manual — 750-654
Page 139 · click to enlarge
Page 139
Quatech INTERBUS S — 750-654 diagram (page 139)
Fig. 221

Series 750- 654 Transmission channel TxD and RxD, full duplex, 2 channel Transmission rate 62500 Baud Bit transmission via 2 twisted pair with differential signals Resistance of cable 120 Ω Current Consumption (internal) 65 mA max. Transmission length max. 100 m twisted pair Input buffer 128 Byte Output buffer 16 Byte Voltage supply via internal system Isolation 500 V System/Supply Bit width internal 1 x 40 bits, 1 x 8 bits control/status Configuration none, parameter configuration with software Operating temperature 0 °C ... + 55 °C Wire connection CAGE CLAMP; 0.08 to 2.5 mm² Dimensions (mm) W x H x L 12 x 64* x 100 (*from upper edge of the carrier rail) Factory preset internal bit width 1 x 32 bits in/out, 1 x 8 bits control/status

Data exchange module 750-654

Page 140 of the Quatech INTERBUS S user manual — SHHUWRSHHUFRQQHFWLRQ
Page 140 · click to enlarge
Page 140
Quatech INTERBUS S — 750-654 diagram (page 140)
Fig. 222

The data exchange module allows the exchange of 4 (5) bytes between different fieldbus systems via multiplexing of a serial connection. The delay which is caused by the multiplexor is < 5ms. The integrated watchdog function switches all outputs to zero if there is no valid information for more than 200 ms via the multiplex connection.

The 128 bytes input buffer provides for high rates of data transmission. When using lower rates of transmission speed you can collect the received data, with less priority, without loosing data. The 16 byte output buffer provides for faster transmission of larger data strings.

The data exchange module is connected peer-to-peer. For the wiring of the serial multiplex connection the RxD and TxD cables are crossed. The following illustrations show the peer-to-peer connection and the internal structure of the data exchange module.

Quatech INTERBUS S — 750-654 diagram (page 140)
Fig. 223

SHHUWRSHHUFRQQHFWLRQ

Quatech INTERBUS S — SHHUWRSHHUFRQQHFWLRQ diagram (page 140)
Fig. 224

7 6 5 4 3 2 1 0 Input byte0

7 6 5 4 3 2 1 0 Input byte1

7 6 5 4 3 2 1 0 Input byte3

7 6 5 4 3 2 1 0 Output byte2

7 6 5 4 3 2 1 0 Output byte4

7 6 5 4 3 2 1 0 Control byte

7 6 5 4 3 2 1 0 Statusbyte

Data exchange module 750-654

Page 141 of the Quatech INTERBUS S user manual — 750-654
Page 141 · click to enlarge
Page 141
Quatech INTERBUS S — 750-654 diagram (page 141)
Fig. 225

The module is a combined special function input and output module with 1 x 32 (40) Bit input and output data. The tranfer of the data to be transmitted and the received data is made via up to 5 input and 5 output Bytes. One control byte and one status byte are used to control the floating data.

The control byte consists of the following bits:

Quatech INTERBUS S — 750-654 diagram (page 141)
Fig. 226

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

The status byte consists of the following bits:

Quatech INTERBUS S — 750-654 diagram (page 141)
Fig. 227

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Module is in timeout. All output bits are set to 0 (watchdog).

The PLC is able to control transmission and reception of data by means of the control byte and the status byte.

Control of the multiplex connection: In the process image of the transmitting buscoupler one Bit is set to „1“ for the whole time. As long as this Bit is „1“ in the receiving coupler, further input Bits can be evaluated. If the Bit is „0“ the multiplex connection has been disrupted. The further Bits are also 0 because of the watchdog.

Control of the multiplex connection with acknowledge: If the transmitting buscoupler gets an acknowledge from the receiving buscoupler, the received bit must be transfered as an output bit to the process image. The transmission is successful as long as the Bit is „1“.

Handshake: If a serial data exchange should be made with the data exchange module, the handshake can be made via „Toggle Bits“. Therefore an input bit and an output bit are reserved. As soon as those bits are different from each other, a request from the opposite module is made. As soon as the request is executed the output bit is toggled.

Data exchange module 750-654

Page 142 of the Quatech INTERBUS S user manual — Structure of the inand output data for Profibus (from firmware WH)
Page 142 · click to enlarge
Page 142
Quatech INTERBUS S — 750-654 diagram (page 142)
Fig. 228

Structure of the inand output data for Profibus (from firmware WH)

The ID 179 (hex: 0xB3), ( Data consistence over 4 Byte) is used.

Quatech INTERBUS S — Structure of the inand output data for Profibus (from firmware WH) diagram (page 142)
Fig. 229 · Structure of the inand output data for Profibus (fro…

Byte Description D0 Output byte0 D1 Output byte1 D2 Output byte2 D3 Output byte3

Quatech INTERBUS S — Structure of the inand output data for Profibus (from firmware WH) diagram (page 142)
Fig. 230 · Structure of the inand output data for Profibus (fro…

Byte Description D0 Input byte0 D1 Input byte1 D2 Input byte2 D3 Input byte3

For the ID 188 (hex.: 0xBC), Data consistence over 6 Byte is used, input and output data are now as follows:

Quatech INTERBUS S — Structure of the inand output data for Profibus (from firmware WH) diagram (page 142)
Fig. 231 · Structure of the inand output data for Profibus (fro…

Byte Description D0 Control byte D1 Output byte0 D2 Output byte1 D3 Output byte4 D4 Output byte2 D5 Output byte3

Quatech INTERBUS S — Structure of the inand output data for Profibus (from firmware WH) diagram (page 142)
Fig. 232 · Structure of the inand output data for Profibus (fro…

Byte Description D0 Statusbyte D1 Input byte0 D2 Input byte1 D3 Input byte4 D4 Input byte2 D5 Input byte3

For a S7 PLC the function code SFC14 and SFC15 must be used because the data length is more than 4.

Data exchange module 750-654

Show 4 more labels / short text on this page
Outputs · Inputs · Outputs · Inputs
Page 143 of the Quatech INTERBUS S user manual — Structure of the inand output data for InterBus S (from firmware WF)
Page 143 · click to enlarge
Page 143
Quatech INTERBUS S — 750-654 diagram (page 143)
Fig. 233

Structure of the inand output data for InterBus S (from firmware WF)

The module is a combined special function input and output module with 2 x 16 Bit in- and output data.

Description Word High Low n (Bit0-Bit15) Input byte0 Input byte1 n+1 (Bit16-Bit31) Input byte2 Input byte3

Description Word High Low n (Bit0-Bit15) Output byte0 Output byte1 n+1 (Bit16-Bit31) Output byte2 Output byte3

Data exchange module 750-654

Input · Output

Page 144 of the Quatech INTERBUS S user manual — Structure of the inand output data for DeviceNet (from firmware 306V3.0)
Page 144 · click to enlarge
Page 144
Quatech INTERBUS S — 750-654 diagram (page 144)
Fig. 234

Structure of the inand output data for DeviceNet (from firmware 306V2.2)

The module has 6 Bytes input and output data in the Poll I/O data. Consumed (Tx for the Scanner) and produced (Rx for the Scanner) data size are each 6 Byte more.

Quatech INTERBUS S — Structure of the inand output data for DeviceNet (from firmware 306V2.2) diagram (page 144)
Fig. 235 · Structure of the inand output data for DeviceNet (fr…

Byte Description D0 Control byte D1 Input byte1 D2 Input byte0 D3 Input byte4 D4 Input byte3 D5 Input byte2

Quatech INTERBUS S — Structure of the inand output data for DeviceNet (from firmware 306V2.2) diagram (page 144)
Fig. 236 · Structure of the inand output data for DeviceNet (fr…

Byte Description D0 Status byte D1 Input byte1 D2 Input byte0 D3 Input byte4 D4 Input byte3 D5 Input byte2

Structure of the inand output data for DeviceNet (from firmware 306V3.0)

The module has 4 Bytes input and output data in the polled I/O data.

Quatech INTERBUS S — Structure of the inand output data for DeviceNet (from firmware 306V3.0) diagram (page 144)
Fig. 237 · Structure of the inand output data for DeviceNet (fr…

Byte Description D0 Input byte0 D1 Input byte1 D2 Input byte2 D3 Input byte3

Quatech INTERBUS S — Structure of the inand output data for DeviceNet (from firmware 306V3.0) diagram (page 144)
Fig. 238 · Structure of the inand output data for DeviceNet (fr…

Byte Description D0 Input byte0 D1 Input byte1 D2 Input byte2 D3 Input byte3

Data exchange module 750-654

Show 4 more labels / short text on this page
Input · Output · Input · Output
Page 145 of the Quatech INTERBUS S user manual — Structure of the inand output data for Modbus (from firmware V2.3)
Page 145 · click to enlarge
Page 145
Quatech INTERBUS S — 750-654 diagram (page 145)
Fig. 239

Structure of the inand output data for Modbus (from firmware V2.3)

The module is a combined special function input and output module with 2 x 16 Bit in- and output data.

Description Word High Low n (Bit0-Bit15) Input byte0 Input byte1 n+1 (Bit16-Bit31) Input byte2 Input byte3

Description Word High Low n (Bit0-Bit15) Output byte0 Output byte1 n+1 (Bit16-Bit31) Output byte2 Output byte3

Data exchange module 750-654

Input · Output

Page 146 of the Quatech INTERBUS S user manual — Structure of the inand output data for CanOpen (from firmware WI)
Page 146 · click to enlarge
Page 146
Quatech INTERBUS S — 750-654 diagram (page 146)
Fig. 240

Structure of the inand output data for CanOpen (from firmware WI)

The module is in the list with Index 0x2400 (input) and Index 0x2500 (output). The module has 2 subindexes.

2 Byte special modules, Inputs Idx SIdx Name Type Attrib. Default Description 2400 0 special 2 byte input Unsigned8 ro none number of 2 Byte channels n Input byte0, Input byte1

Quatech INTERBUS S — Structure of the inand output data for CanOpen (from firmware WI) diagram (page 146)
Fig. 241 · Structure of the inand output data for CanOpen (from…

0xFF 0xFF. Special input Unsigned16 ro none 255. Input channel

2 Byte special modules, Outputs Idx SIdx Name Type Attrib. Default Description 2500 0 special 2 byte output

Quatech INTERBUS S — Structure of the inand output data for CanOpen (from firmware WI) diagram (page 146)
Fig. 242 · Structure of the inand output data for CanOpen (from…

n Output byte0, Output byte1

0xFF 0xFF. special output

Data exchange module 750-654

Page 147 of the Quatech INTERBUS S user manual — Structure of the inand output data for CAL (from firmware WE)
Page 147 · click to enlarge
Page 147

Structure of the inand output data for CAL (from firmware WE)

Mode class 4: The data is in the 2 Byte objects #BK_AI2W0_XXX, #BK_AI2W1_XXX and #BK_A02W0_XXX. Each module has 2 values.

Mux Content Description n Input byte0, Input byte1 1. and 2. Input byte n+1 Input byte2, Input byte3 3. and 4. Input byte

Mux Content Description n Output byte0, Output byte1 1. and 2. Output byte n+1 Output byte2, Output byte3 3. and 4. Output byte

Mode class 0: The description of the data is the same as for class 4 mode. The data is put into objects No.1, No.2 and No.3 (read/write 2 Byte analog).

Data exchange module 750-654

Input · Output

Page 148 of the Quatech INTERBUS S user manual — Structure of the inand output data for LIGHTBUS (from firmware WD)
Page 148 · click to enlarge
Page 148
Quatech INTERBUS S — 750-654 diagram (page 148)
Fig. 243

Structure of the inand output data for LIGHTBUS (from firmware WD)

Quatech INTERBUS S — Structure of the inand output data for LIGHTBUS (from firmware WD) diagram (page 148)
Fig. 244 · Structure of the inand output data for LIGHTBUS (fro…

Content Description Word High Low n - Statusbyte Statusword n+1 Input byte0 Input byte1 1. and 2. Input byte n+2 - Input byte4 5.Input byte n+3 Input byte3 Input byte2 3. and 4. Input byte

Quatech INTERBUS S — Structure of the inand output data for LIGHTBUS (from firmware WD) diagram (page 148)
Fig. 245 · Structure of the inand output data for LIGHTBUS (fro…

Content Description Word High Low n - Statusbyte Statusword n+1 Output byte0 Output byte1 1. and 2. Output byte n+2 - Output byte4 5.Output byte n+3 Output byte3 Output byte2 3. and 4. Output byte

Data exchange module 750-654

Input · Output

Page 149 of the Quatech INTERBUS S user manual — Ex-1.3.1 Divisions
Page 149 · click to enlarge
Page 149

Application in Explosive Environments • 1 Foreword

Ex-1 Application in Explosive Environments

Ex-1.1 Foreword

Today’s development shows that many chemical and petrochemical companies have production plants, production, and process automation machines in operation which use gas-air, vapor-air and dust-air mixtures which can be explosive. For this reason, the electrical components used in such plants and systems must not pose a risk of explosion resulting in injury to persons or damage to property. This is backed by law, directives or regulations, on a national and international scale. WAGO-I/O-SYSTEM 750 (electrical components) is designed for use in zone 2 explosive environments. The following basic explosion protection related terms have been defined.

Ex-1.2 Protective measures

Primarily, explosion protection describes how to prevent the formation of an explosive atmosphere. For instance by avoiding the use of combustible liquids, reducing the concentration levels, ventilation measures, to name but a few. But there are a large number of applications, which do not allow the implementation of primary protection measures. In such cases, the secondary explosion protection comes into play. Following is a detailed description of such secondary measures.

Ex-1.3 Classification meeting CENELEC and IEC

The specifications outlined here are valid for use in Europe and are based on the following standards: EN50... of CENELEC (European Committee for Electrotechnical Standardisation). On an international scale, these are reflected by the IEC 60079-... standards of the IEC (International Electrotechnical Commission).

Ex-1.3.1 Divisions

Explosive environments are areas in which the atmosphere can potentially become explosive. The term explosive means a special mixture of ignitable substances existing in the form of air-borne gases, fumes, mist or dust under atmospheric conditions which, when heated beyond a tolerable temperature or subjected to an electric arc or sparks, can produce explosions. Explosive zones have been created to describe the concentrations level of an explosive atmosphere. This division based on the probability of an explosion occurring is of great importance both for technical safety and feasibility reasons, knowing that the demands placed on electrical components permanently employed in an explosive environment have to be much more stringent than those placed on electrical components that are only rarely and, if at all, for short periods, subject to a dangerous explosive environment.

WAGO-I/O-SYSTEM 750 Modular I/O-System

Page 150 of the Quatech INTERBUS S user manual — WAGO-I/O-SYSTEM 750
Page 150 · click to enlarge
Page 150

2 • Application in Explosive Environments Classification meeting CENELEC and IEC

Explosive areas resulting from gases, fumes or mist:

  • Zone 0 areas are subject to an explosive atmosphere (> 1000 h /year) continuously or for extended periods.
  • Zone 1 areas can expect the occasional occurrence of an explosive atmosphere (> 10 h ≤ 1000 h /year).
  • Zone 2 areas can expect the rare or short-term occurrence of an explosive atmosphere (> 0 h ≤ 10 h /year).

Explosive areas subject to air-borne dust:

  • Zone 20 areas are subject to an explosive atmosphere (> 1000 h /year) continuously or for extended periods.
  • Zone 21 areas can expect the occasional occurrence of an explosive atmosphere (> 10 h ≤ 1000 h /year).
  • Zone 22 areas can expect the rare or short-term occurrence of an explosive atmosphere (> 0 h ≤ 10 h /year).

Ex-1.3.2 Explosion protection group

In addition, the electrical components for explosive areas are subdivided into two groups:

Group I: Group I includes electrical components for use in fire-damp endangered mine structures.

Group II: Group II includes electrical components for use in all other explosive environments. The group is further subdivided by pertinent combustible gases in the environment. Subdivision IIA, IIB and IIC takes into account that different materials/substances/gases have various ignition energy characteristic values. For this reason the three sub- groups are assigned representative types of gases:

  • IIA – Propane
  • IIB – Ethylene
  • IIC – Hydrogen

WAGO-I/O-SYSTEM 750

Modular I/O-System

Page 151 of the Quatech INTERBUS S user manual — Ex-1.3.3 Unit categories
Page 151 · click to enlarge
Page 151

Application in Explosive Environments • 3 Classification meeting CENELEC and IEC

Quatech INTERBUS S — Application in Explosive Environments diagram (page 151)
Fig. 246 · Application in Explosive Environments

Hydrogen being commonly encountered in chemical plants, frequently the explosion group IIC is requested for maximum safety.

Ex-1.3.3 Unit categories

Moreover, the areas of use (zones) and the conditions of use (explosion groups) are subdivided into categories for the electrical operating means:

Quatech INTERBUS S — Ex-1.3.3 Unit categories diagram (page 151)
Fig. 247 · Ex-1.3.3 Unit categories

1G II Zone 0 Explosive environment by gas, fumes or mist

2G II Zone 1 Explosive environment by gas, fumes or mist

3G II Zone 2 Explosive environment by gas, fumes or mist

WAGO-I/O-SYSTEM 750 Modular I/O-System

Page 152 of the Quatech INTERBUS S user manual — WAGO-I/O-SYSTEM 750
Page 152 · click to enlarge
Page 152

4 • Application in Explosive Environments Classification meeting CENELEC and IEC

Ex-1.3.4 Temperature classes

The maximum surface temperature for electrical components of explosion protection group I is 150 °C (danger due to coal dust deposits) or 450 °C (if there is no danger of coal dust deposit).

In line with the maximum surface temperature for all ignition protection types, the electrical components are subdivided into temperature classes, as far as electrical components of explosion protection group II are concerned. Here the temperatures refer to a surrounding temperature of 40 °C for operation and testing of the electrical components. The lowest ignition temperature of the existing explosive atmosphere must be higher than the maximum surface temperature.

Quatech INTERBUS S — Ex-1.3.4 Temperature classes diagram (page 152)
Fig. 248 · Ex-1.3.4 Temperature classes

T2 300 °C > 300 °C ≤ 450 °C

T3 200 °C > 200 °C ≤ 300 °C

T4 135 °C > 135 °C ≤ 200 °C

The following table represents the division and attribution of the materials to the temperature classes and material groups in percent:

Quatech INTERBUS S — Ex-1.3.4 Temperature classes diagram (page 152)
Fig. 249 · Ex-1.3.4 Temperature classes

Temperature classes T1 T2 T3 T4 T5 T6 Total*

94.9 % 4.9 % 0 % 0.2 % 432

* Number of classified materials

Ex-1.3.5 Types of ignition protection

Ignition protection defines the special measures to be taken for electrical components in order to prevent the ignition of surrounding explosive atmospheres. For this reason a differentiation is made between the following types of ignition protection:

WAGO-I/O-SYSTEM 750

Modular I/O-System

Page 153 of the Quatech INTERBUS S user manual — Application in Explosive Environments
Page 153 · click to enlarge
Page 153

Application in Explosive Environments • 5 Classification meeting CENELEC and IEC

Quatech INTERBUS S — Application in Explosive Environments diagram (page 153)
Fig. 250 · Application in Explosive Environments

EEx o EN 50 015 IEC 79-6 Oil encapsulation Zone 1 + 2

EEx p EN 50 016 IEC 79-2 Overpressure encapsulation

EEx q EN 50 017 IEC 79-5 Sand encapsulation Zone 1 + 2

EEx d EN 50 018 IEC 79-1 Pressure resistant encapsulation

EEx e EN 50 019 IEC 79-7 Increased safety Zone 1 + 2

EEx m EN 50 028 IEC 79-18 Cast encapsulation Zone 1 + 2

EEx i EN 50 020 (unit) EN 50 039 (system)

IEC 79-11 Intrinsic safety Zone 0 + 1 + 2

EEx n EN 50 021 IEC 79-15 Electrical components for zone 2 (see below)

Ignition protection “n“ describes exclusively the use of explosion protected electrical components in zone 2. This zone encompasses areas where explosive atmospheres can only be expected to occur rarely or short-term. It represents the transition between the area of zone 1, which requires an explosion protection and safe area in which for instance welding is allowed at any time.

Regulations covering these electrical components are being prepared on a world-wide scale. The standard EN 50 021 allows electrical component manufacturers to obtain certificates from the corresponding authorities for instance KEMA in the Netherlands or the PTB in Germany, certifying that the tested components meet the above mentioned standards draft.

Type “n” ignition protection additionally requires electrical components to be marked , with the following extended identification:

  • A – non spark generating (function modules without relay /without switches)
  • AC – spark generating, contacts protected by seals (function modules with relays / without switches)
  • L – limited energy (function modules with switch)

Further information For more detailed information please refer to the national and/or international standards, directives and regulations!

WAGO-I/O-SYSTEM 750 Modular I/O-System

Page 154 of the Quatech INTERBUS S user manual — WAGO-I/O-SYSTEM 750
Page 154 · click to enlarge
Page 154

6 • Application in Explosive Environments Classifications meeting the NEC 500

Ex-1.4 Classifications meeting the NEC 500

The following classifications according to NEC 500 (National Electric Code) are valid for North America.

Ex-1.4.1 Divisions

The "Divisions" describe the degree of probability of whatever type of dangerous situation occurring. Here the following assignments apply:

Explosion endangered areas due to combustible gases, fumes, mist and dust:

Division 1 encompasses areas in which explosive atmospheres are to be expected occasionally (> 10 h ≤ 1000 h /year) as well as continuously and long-term (> 1000 h /year).

Division 2 encompasses areas in which explosive atmospheres can be expected rarely and short-term (>0 h ≤ 10 h /year).

Ex-1.4.2 Explosion protection groups

Electrical components for explosion endangered areas are subdivided in three danger categories:

Class I (gases and fumes)Group A (Acetylene) Group B (Hydrogen) Group C (Ethylene) Group D (Methane)

Class II (dust): Group E (Metal dust) Group F (Coal dust) Group G (Flour, starch and cereal dust)

Class III (fibers)No sub-groups

WAGO-I/O-SYSTEM 750

Modular I/O-System

Page 155 of the Quatech INTERBUS S user manual — Ex-1.4.3 Temperature classes
Page 155 · click to enlarge
Page 155

Application in Explosive Environments • 7 Classifications meeting the NEC 500

Ex-1.4.3 Temperature classes

Electrical components for explosive areas are differentiated by temperature classes:

Quatech INTERBUS S — Ex-1.4.3 Temperature classes diagram (page 155)
Fig. 251 · Ex-1.4.3 Temperature classes

T2 300 °C > 300 °C ≤ 450 °C

T2A 280 °C > 280 °C ≤ 300 °C

T2B 260 °C > 260 °C ≤ 280 °C

T6 85 °C > 85 °C ≤ 100 °C

WAGO-I/O-SYSTEM 750 Modular I/O-System

Page 156 of the Quatech INTERBUS S user manual — WAGO-I/O-SYSTEM 750
Page 156 · click to enlarge
Page 156

8 • Application in Explosive Environments Identification

Ex-1.5 Identification

Ex-1.5.1 For Europe

According to CENELEC and IEC

Explosion protection group Unit category

Community symbol for explosion protected electrical components

II 3 G KEMA 01ATEX1024 X

EEx nA II T4

Approval body and/or number of the examination certificate

E = conforming with European standards Ex = explosion protected component

n = Type of ignition Extended identification

ITEM-NO.:750-400

2DI 24V DC 3.0ms

55°C max ambient LISTED 22ZA AND 22XM

Hansastr. 27 D-32423 Minden

0.08-2.5mm 2

24V DC AWG 28-14

0V 24V DI1

PATENTS PENDING II 3 G KEMA 01ATEX1024 X EEx nA II T4

op temp code T4A

CL I DIV 2

Grp. A B C D

Fig. 1-1Example for lateral labeling of bus modules

(750-400, 2 channel digital input module 24 V DC) g01xx03e

WAGO-I/O-SYSTEM 750

Show 5 more labels / short text on this page
Temperature class · Explosion protection group · 2101--02----03 · Di2 · Modular I/O-System
Page 157 of the Quatech INTERBUS S user manual — CL I DIV 2
Page 157 · click to enlarge
Page 157

Application in Explosive Environments • 9 Identification

Ex-1.5.2 For America

According to NEC 500

Area of application (zone)

Explosion protection group (condition of use category)

CL I DIV 2 Grp. ABCD optemp code T4A

Explosion group (gas group)

ITEM-NO.:750-400

2DI 24V DC 3.0ms

Hansastr. 27 D-32423 Minden

0.08-2.5mm 2

24V DC AWG 28-14

LISTED 22ZA AND 22XM

0V 24V DI1

op temp code T4A

PATENTS PENDING II 3 G KEMA 01ATEX1024 X EEx nA II T4

CL I DIV 2

Grp. A B C D

Fig. 1-2Example for lateral labeling of bus modules

(750-400, 2 channel digital input module 24 V DC) g01xx04e

WAGO-I/O-SYSTEM 750 Modular I/O-System

Show 4 more labels / short text on this page
Temperature class · 55°C max ambient · 4100--02----03 · Di2
Page 158 of the Quatech INTERBUS S user manual — WAGO-I/O-SYSTEM 750
Page 158 · click to enlarge
Page 158

10 • Application in Explosive Environments Installation regulations

Ex-1.6 Installation regulations

In the Federal Republic of Germany, various national regulations for the installation in explosive areas must be taken into consideration. The basis being the ElexV complemented by the installation regulation DIN VDE 0165/2.91. The following are excerpts from additional VDE regulations:

DIN VDE 0100 installation in power plants with rated voltages up to 1000 V

DIN VDE 0101 installation in power plants with rated voltages above 1 kV

DIN VDE 0800 installation and operation in tele-communication plants including information processing equipment

DIN VDE 0185 lightning protection systems

The USA and Canada have their own regulations. The following are excerpts from these regulations:

NFPA 70 National Electrical Code Art. 500 Hazardous Locations

ANSI/ISA-RP 12.6-1987 Recommended Practice

C22.1 Canadian Electrical Code

WAGO-I/O-SYSTEM 750

Modular I/O-System

Page 159 of the Quatech INTERBUS S user manual — Application in Explosive Environments
Page 159 · click to enlarge
Page 159

Application in Explosive Environments • 11 Installation regulations

  • The electrical operating means are exclusively suitable for applications in explosion endangered areas (Europe Group II, Zone 2 or America: Class I, Division 2, Group A, B, C, D) or in non explosion endangered areas!
  • Ensure that only approved modules of the electrical operating means will be used. Replacement of components can jeopardize the suitability of the system in explosion endangered zones!
  • Only disconnect and/or connect electrical operating means when the voltage supply is isolated or when a non-explosive atmosphere has been ascertained!
  • Adhere to the specified data regarding voltage supply and fusing. (See data on the fuse holder)!

Further Information Proof of certification is available on request.

Also take note of the information given on the module technical information sheet.

WAGO-I/O-SYSTEM 750 Modular I/O-System

Page 160 of the Quatech INTERBUS S user manual — Application in Explosive Environments
Page 160 · click to enlarge
Page 160
  • WAGO Kontakttechnik GmbH Postfach 2880
  • D-32385 Minden Hansastraße 27
  • D-32423 Minden Phone: 05 71/8 87 – 0 Fax: 05 71/8 87 – 1 69 E-Mail: info@<a href="http://wago.com" rel="nofollow noopener" target="_blank">wago.com</a>
Internethttp://www.wago.com
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Display codes

Error codes

What the fault codes shown on the display mean and how to clear them.

CodeMeaningFix
0unknown fault p.18
5defective fuse p.18
10broken wire p.18
15short circuit p.18

Ask about the Quatech INTERBUS S

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Quatech INTERBUS S

Be the first to ask — other owners or our team will answer.

Original document

Quatech INTERBUS S manual PDF

160 pages·4.2 MB·Network Card·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…