INTERBUS S

Technical description, installation and configuration
750-132 Version 2.2.1

Copyright 1997-2001 by WAGO Kontakttechnik GmbH All rights reserved.
WAGO Kontakttechnik GmbH Hansastraße 27 D-32423 Minden
Technical Support Phone: +49 (0) 571/8 87 – 5 55 Fax: +49 (0) 571/8 87 – 4 30
Every conceivable measure has been taken to ensure the correctness and com- pleteness of this documentation. However, as errors can never be fully ex- cluded we would appreciate any information or ideas at any time.
We wish to point out that the software and hardware terms as well as the trademarks of companies used and/or mentioned in the present manual are generally trademark or patent protected.
ii • General · Modular I/O System



The WAGO I/O SYSTEM consists of various components which are capable of providing modular and application specific fieldbus nodes for various fieldbusses.

I11.1 Setting up a fieldbus node with the WAGO I/O SYSTEM
General remark: A fieldbus node consists in principle of a fieldbus coupler at the front end, a number of special function modules and a termination module which is placed at the other end.
Interbus / Introduction

Assembly of the WAGO I/O System All components of the system can be snapped directly on a carrier rail according to EN 50022 (DIN 35). When snapping the analog or digital components onto the rail, no special sequence must be observed. The secure positioning and connection of the individual function modules and the coupler is provided by a snap-in system. This snap-in system provides automatic interlocking onto the DIN rail assembly. It is always possible to remove a function module or the Buscoupler from the assembly by pulling the orange pull-tab.
Please note, that the power supply of the field side as well as the data transmission are interrupted. It has to be ensured that the interruption of PE will not put personnel or equipment in danger.
With a CAGE CLAMP, conductors with a cross section of 0.08 to 2.5mm2 /AWG 18-14 can be connected. Vibration proof, fast and maintenance-free. You simply introduce a screwdriver or an operating tool into the operating slot under the clamping unit. The CAGE CLAMP spring is pressed down. You can now introduce the wire into the clamping unit. Withdraw the operating tool and the conductor is automatically clamped.
Interbus / Introduction

The clamping force adjusts automatically to the conductor cross section. The flat clamping face of the CAGE CLAMP spring presses the conductor against the current bar without damage. Any deformation or movement of the conductor is compensated, thus eliminating the risk of a loose connection. The contact point between conductor and CAGE CLAMP is well protected against corrosive deterioration. This connection is made fast and, furthermore, it is maintenance-free. There is no need for costly periodical examination of the connections.
The supply modules of the WAGO I/O system are partly equipped with a fuse holder. This fuse holder can be pulled out in order to break the circuit of the following modules. To do so, you first have to insert a screwdriver into one of the slots on both sides in order to pull out the front side of the fuse holder.
The front side now being hinged down makes it possible to remove or to insert the fuse. After that, you lift up the front side again and push the fuse holder back into its original position.
Interbus / Introduction



The 750-304 Interbus coupler consists of two major electronic sub systems:
left side: This housing contains the electronics for the coupling to the bus, the processor and the fieldbus connection. (ill. 2.1)
right side: This housing contains the DC to DC converter and power distribution for the internal K bus, local processor and external 24 V DC connections to other discrete I/O modules. Illustration 2.2 identifies the 24 V DC connection points to supply voltage to I/O modules. Illustration 2.3 identifies the ground connection.
INTERBUS S / Buscoupler




The nominal operating voltage of the Buscoupler and the control electronics in the function modules is 5 V DC. The supply is connected to the first two CAGE CLAMPS at the top of the coupler as seen in Ill. 3.
The 24 V DC supply voltage is generated by an internal voltage regulator (DC/DC converter) and fed to the electronics (5 V DC). The electrical isolation of the external bus system is made by utilizing an optocoupler.
Please note that the power supply for the control electronics in the function modules is made automatically by the data contacts of the following module when it is snapped on the assembly (ill. 3.1). The power supply to the attached I/O modules is provided by gold-plated self-cleaning slide contacts. If an attached module is taken out of the existing configuration, the connection via the K bus is broken and the coupler is able to detect this.
INTERBUS S / Buscoupler




The connection of the supply voltage is electrically isolated from the internal electronics. Two CAGE CLAMPS are always connected by a power contact. By this way, the power supply is taken to different points of the configuration.
It is possible to supply the following at the termination points (Ill. 4):
The voltage is automatically supplied when the function modules are snapped together. Self-cleaning power jumper contacts (P.J.C.s) ensure safe connections (Ill. 4). Female contacts (current supply) are integrated in the buscoupler and I/O housings. The male contacts on the buscoupler and I/O housings supply the voltage to the I/O modules when inserted together from left to right.
The ground (earth) contact makes first and breaks last conforming to electrical standards and can be used as protective grounding.
Depending on the I/O function, some modules do not have P.J.C.s. It is important to note this when assembling a node. Many modules require field side power, many do not. Please review the circuit diagrams of the individual modules. An additional power supply module may be necessary.
INTERBUS S / Buscoupler

When using the supply module 750-601/602, the field supply from the bus coupler is interrupted. From that point a new power supply connection is necessary to provide DC to any additional I/O modules.
INTERBUS S / Buscoupler



Fieldbus connection:
The Interbus interface is normally provided by D SUB connection according to US Standard EIA RS485 for data transmission by wires.

PIN cable PIN Incoming D-SUB (IN) /DO 6 green 6 /DO DO 1 yellow 1 DO /DI 7 pink 7 /DI DI 2 gray 2 DI COM 3 brown 3 COM 5 commoning wire 9 commoning wire
The connection point of the D SUB connector is lowered in such a way that after a connector is installed placement in an 80mm high switchbox is possible.
INTERBUS S / Buscoupler

The configuration interface used for the communication with WAGO-I/O-CHECK or for firmware upload is located behind the cover flap.
The communication cable (750-920) is connected to the 4-pole header.
INTERBUS 7a WAGO-I/O-SYSTEM 750
Configuration Interface · Configuration interface




750-304 750-324 Number of function modules 256 on request Number of I/O points 4096 on request Transmission medium shielded Cu-cable (5 x 0.25 mm²) max. bus length 400 m Baud rate 500 kBaud
INTEBUS S / Enclosure and specifications

750-324 digital Number of function modules 64 32 Digital peripheral signals 256 64 Analog peripheral signals 32 --- Configuration possibility via PC or control --- Bus connection 2 D-SUB with protection against vibration Voltage supply 24V DC (-15%/+20%) Input current 105 mA typ; 900 mA max. 85 mA typ.; 500 mA max. Internal current 400 mA 400 mA Power jumper contacts blade / spring contact slide contact, self-cleaning Maximum current supplied to K-Bus for internal module use
750-304 dig.+analog
1.75 A on request
Voltage power jumper contacts 24 V DC Current power jumper contacts 10A DC Data contacts slide contacts, 1.5 u hard gold-plated
self-cleaning Voltage drop via data contacts
marker cards 8 x 47mm Wire connection CAGE CLAMP; 0.08mm2 -2.5mm2 /AWG 28 -14 Mounting position any position Type of protection IP 20 Isolation 500 V system / power supply Operating temperature 0°C...+55°C Dimensions (mm) W x H x L 51 x 65* x 100 (*from upper edge of the carrier rail)
INTEBUS S / Enclosure and specifications


The Interbus S buscoupler with no. 750-304/000-001 has the possibility of extented diagnostic functions. The technical data is the same as 750-304. Different from the standard buscoupler, a word for diagnostic messages is put into the input data process image and a word for the control of the diagnostic input is put into the output data process image. The maximum number of input and output modules is reduced by the additional diagnostic function because Interbus S transmits only 31 words of a process image.
Order of the diagnostic status word:
Bit of the status word
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
error error code (s. table) Channel Module
The error code is shown in the following table:
Error code Description 0 unknown fault 5 defective fuse 10 broken wire 15 short circuit

Channel: This is the location for the fault input of a module. The counting is done in the same way as numbering channels. Module: This is the number of the module. Counting starts at the fieldbus coupler. The first module attached to the coupler is module 0.
The diagnostic control word is for diagnostic actions. E.g. error messages can be cleared in this way.
Order of the diagnostic control word:
Bit of the control word
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
The actions are coded as follows:
Actions Description 0x00 (0) no action 0x01 (1) Acknowledge diagnostic control word 0x80 (128) Clears all error messages in the buffer

INTEBUS S / Enclosure and specifications
Actions

The Interbus S system (DIN 19245 part 1.2) is set up as a data ring with a central master slave access procedure. All modules are understood as one logical module. Each partner receives data at its input and sends it to the next partner at its output. There is no addressing with a data frame because each partner knows by special control signals (CLOCK, RESET, SELECT, CONTROL) where it is placed in the ring. So there is no bus address. „Addressing“ is done via the physical place in the system.
Interbus S has the structure of a spatially distributed shift register. Each cycle is input and output at the same time. While the master gives output data to the shift register, it gets input data from the other end of the ring.
Each part of Interbus S has an ID register. This register keeps information about the type of module, the number of I/O registers and the status and error information.
Interbus S has two general operating modes:
The operation of the master is carried out in most cases via a central controller like a PLC, PC or NC. Connection to the remote stations is made via master cards.
Common master modules are:
- Phoenix IBS S5 DCB/I-T
- Phoenix IBS S5 DSC/I-T
- Phoenix 100 CB-T
- Hilscher CIF 30 (via Synergetic Micro Systems in USA)
INTERBUS S / Interbus S

In order to make the connection between a PLC or PC and the remote stations, the master cards must be configured with the individual station data.
For this, the following software packages are available. For example, the following are available from Phoenix:
- IBS CMD SWT
INTERBUS S / Interbus S


5.1 Identification Code
In the ID cycle which is carried out for the initialization of the Interbus system, the users connected users are identified by their function and their byte length. The Interbus S coupler identifies its length after being started in the initialization phase of the bus modules and forms a corresponding ID code. To this effect each slave has an implemented identification register (ID register) comprising 2 bytes.
A 2 byte wide data unit is called a word. It enables the encoding of 65536 different states. In Interbus S, different types of users and data widths are called for the coding. This enables the master to find out what type the device belongs to, which means for example, recognizing either frequency inverters or I/O units, like the In Interbus S the manufacturers of device types are not recognized. The structure of the ID code is explained below as well as the significance of the individual bits of the ID code.
The length information can be coded from 0 to 32 words:

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
data direction I, O, I/O
-In the ID registers, the device group is coded in the lowest value (LSB) 8 bits (ID 0 to 7). -In the following 5 bits (ID 8 to 12), the data width is coded. The 3 bits with the highest value (MSB) (ID 13 to 15) are used for management functions. Via these bits, dynamic fault messages are transferred during operation. These bits are not defined by the hardware.
INTERBUS S / Configuration


Due to the combined use of digital, analog and special functions on one fieldbus station and with the given structure of the Interbus ID codes, it is impossible to manage with one ID code. The WAGO Interbus S buscoupler is identified as a digital slave with variable length!

Inputs 1, 0x1 x 2, 0x2 x 3, 0x3 x x 49, 0x31 - x 50, 0x32 - x 51, 0x33 - - x x [x]: ID code given []: is not possible [-]: when mixed with digital Table 3: ID codes for the WAGO Interbus S buscoupler
For the master, it is important to know how many data registers each user assigns in the Interbus S system. If a user has, for example, 16 bits of input and 32 bits of output, he assigns 2 words in the bus because there are 2 words of output. In this case the higher value of data width is decisive. The data width is coded by the bits ID 8 to ID 12 as shown in section 5.1. The following table shows the register widths depending on the function modules connected to a WAGO Interbus S buscoupler. Possible values for data length are::
Data length Buscoupler Remarks 0 Words x 1 Nibble Busmaster supports only Generation 4. 1 Byte Starting with SPS-Firmware 3.20 or PC-driver 2.0 3 Nibble Busmaster supports only Generation 4 1 Word x 3 Nibble Busmaster supports only Generation 4 3 Byte Starting with SPS-Firmware 3.20 or PC-driver 2.0 2 Words x 5 Nibble Busmaster supports only Generation 4 5 Byte Starting with SPS-Firmware 3.20 or PC-driver 2.0 3 Words x 4 Words x 5 Words x 6 Words x, ab WF Starting with SPS-Firmware 3.20 or PC-driver 2.0 7 Words x, ab WF Starting with SPS-Firmware 3.20 or PC-driver 2.0 8 Words x 9 Words x 10 Words xx Starting with SPS-Firmware 3.20 or PC-driver 2.0 12 Words xx Starting with SPS-Firmware 3.20 or PC-driver 2.0 14 Words xx Starting with SPS-Firmware 3.20 or PC-driver 2.0 16 Words xx Starting with SPS-Firmware 3.20 or PC-driver 2.0 24 Words xx Starting with SPS-Firmware 3.20 or PC-driver 2.0 32 Words xx Starting with SPS-Firmware 3.20 or PC-driver 2.0 [x]: is used [xx]: is used and firmware 3.20 or PC driver 2.0 or later is combined
INTERBUS S / Configuration

In the following chapter the configuration package IBS CMD configuration software is presented in short form. This procedure facilitates operation of the WAGO Interbus buscoupler.
Further and specific information is given in the respective operating instructions of the different software packages.
Please pay attention that the corresponding interfacing and the function extended should be selected.
The following menu is obtained via the key OK and the password allocated at the program installation.

This is the first menu for further configuration. From this point the configuration can be made automatically or manually.
INTERBUS S / Configuration


If the complete fieldbus system with all stations and the master interface is operational, automatic configuration of the connected stations can be called up via the menu „bus structure“. Then the communications are started automatically and the configuration is determined and set.
INTERBUS S / Configuration


For manual configuration, the menu item „bus structure“ in the configuration screen must be selected. You will then see Ill. 12.
The corresponding ID code of table 3 and the length of the process data channel must be indicated in the selected submenu. The length is dependent on the module with the largest data length.
INTERBUS S / Configuration


With the finalization of the entries via the key OK, a menu for the definition of the user will appear.
INTERBUS S / Configuration


INTERBUS S / Configuration

After all data has been entered and stored via OK, the station created with the WAGO Interbus coupler is then integrated into the fieldbus system being set up.
This station is displayed via the bus structure that has now been integrated:

INTERBUS S / Configuration



The Interbus S station is composed as follows:
Function module Process image inputs Process image outputs 1; Digital input PI 32.0 1; Digital Input PI 32.1 2; Digital Input PI 32.2 2; Digital Input PI 32.3 3; Voltage supply 4; Analog Input PI 20 4; Analog Input PI 22 5; Voltage supply 6; Digital Output PI28.0 6; Digital Output PI28.1 7; Digital Output PI28.2 7; Digital Output PI28.3 8; Digital Output PI28.4 8; Digital Output PI28.5 9; Digital Output PI28.6 9; Digital Output PI28.7 10; Voltage supply 11; Analog Output PI 20 11; Analog Output PI 22 12; Analog Input PI 24 12; Analog Input PI 26 13; Analog Output PI 24 13; Analog Output PI 26 14; Analog Input PI 28 14; Analog Input PI 30 15; Voltage supply 16; Digital Output PI29.0 16; Digital Output PI29.1 17; End module Table 5: Assignment of the process image
INTERBUS S / Configuration

The addresses indicated in the table results from the master configuration started in the basic address. By the internal structure of the Interbus coupler, the process image is divided as follows:
O0 Output data word orientated data Ox Ox+1 bit orientated data Ox+y
I0 Input data word orientated data Ix Ix+1 bit orientated data Ix+y
Due to this division, the first addresses allocated in the configuration are reserved for the analog inputs and outputs. The counting direction is from left to right and starts with the first analog channel next to the bus coupler.

INTERBUS S / Configuration


After configuration of the master connection and electrical installation of the fieldbus node/station, operation of the system can begin.
After power to the Buscoupler and I/O modules has been applied, the Buscoupler verifies all internal functions, components and the communication interface by an internal diagnostic routine. Then the function modules and the existing configuration is determined. At the same time a hidden file is stored. It consists of an input and an output area which is located on the fieldbus RAM of the log chip. During the power up phase the ‘I/O ERR’ LED flashes with an increased frequency. After a faultless power up the fieldbus coupler enters the state ‘fieldbus start’. The green LED ‘RUN’ indicates that the Bus is operating normally. In case of a fault the red ‘I/O ERR’ LED will continue flashing. By counting the number and frequency of flashes the fault can be easily identified quickly and accurately. A varying number of flashes and frequencies defines the fault. The table below describes the fault condition based on the counted number of ‘I/O ERR’ LED flashes.

N (N>0) error in comparison of tables: module N (programmed configuration), passive modules like supply terminal blocks do not count
3 0 modules have identified error in fieldbus commands
4 0 data error on fieldbus or fieldbus break at the coupler
5 N filedbus error in register communications with module N
N (0<N<65) error in 1st configuration byte Table 5: Diagnosis LEDs - on buscoupler
INTERBUS S / Startup

After elimination of the fault, the buscoupler can only be set to the normal working condition by another POWER ON sequence. The green I/O LED flashes when accessing the I/O modules internal data channels. After being switched on, the buscoupler queries the configuration of the bus modules but does not carry out a data exchange with the I/O modules. This means that the red I/O LED will extinguish after a faultless startup. The green I/O LED will indicate when data is being exchanged by the Interbus network.
Status and error diagnostics:
The fieldbus LEDs show the state of the bus system. The functions of Interbus S are shown by the LEDs „READY“, „BA“, „RC“ and „RD“.

on off off on Field bus off error in cable or master
search error in cable or master off no function ; no voltage
INTERBUS S / Startup

This chapter describes the general conditions for error-free running of the
The following declarations concern modules which are transported and stored in the original package.
Condition allowed values Free fall ≤ 1m Temperature -40° to +70° C Relative humidity 5 to 95% (without condensation)
The modules of the are not allowed to be operated without taking suitable actions - in places with strong conditions e.g. very dusty rooms or corroding atmosphere - in place with high concentrations of ionisation
The temperature should be in a range between 0° C and +55° C. The relative humidity should be in a range of 5 to 95% (without condensation). The modules should be placed horizontal for better heat dissipation.
The concentration of SO2 must be below 25 ppm with a relative humidity of < 75%. The concentration of H2S must be below 10 ppm with the same humidity.
The mechanical conditions are given as sinusoidal oscillations.
Frequency range (Hz) continuous sometimes 10 ≤ f < 57 0.0375 mm amplitude 0.075mm amplitude 57 ≤ f ≤ 150 0.5 g constant acceleration 1 g constant acceleration
For stronger impulses and oscillations, the acceleration and the amplitude should be reduced by suitable actions. The following table shows the type of test for the mechanical conditions.
INTERBUS / General conditions

Test for Test sequence Remarks Oscillations Test for oscillations IEC 68, part 2-6
Type of oscillation: sweep with a rate of change of 1 octave per minute 10 Hz ≤ f < 57 Hz, const. amplitude 0,075mm 57 Hz ≤ f ≤ 150 Hz, const. acceleration 1 g period of oscillation: 10 sweep per axis in each of the 3 vertical axes Impulse Test for impulses IEC 68, part 2-27
Type of impulse: half sinusoidal Intensity of impulses: 15 g peak value, 11 ms maintenance time route of impulses: 2 impulses in each of the 3 vertical axes
The class of protection is IP2X (IEC 529), i.e. protection against touch with a standard test object. There is also protection against solid bodies greater than 12 mm. There is no special protection against water.
INTERBUS / General conditions

Method of measurement Disturbance Interference with narrow-band conducted disturbance
Interference with impulse groups EN 50082-2, B Discharge of static electricity EN 50082-2, B Interference with electromagnetic fields EN 50082-2, A Interference field strength EN 55011
These requests for electromagnetic compatibility are fulfilled by all modules of (except for 750-630 and 750-631).
If non-stabilized power supply is used for the supply of the buscoupler, it must be stabilized by a capacity ( 200 µF per 1 A load current). For the a filter module has been developed (288-824). This module serves as a filter module for non-stabilized 24 V DC power supplies if the specified voltage deviation is not met. Reasons for the deviations may be voltage jumps in the primary circuit, overloads in the secondary circuit or the switching of undampened inductances and capacitances.
The modules of have passed the conformance test of UL. Look for listing mark on product. The Profibus coupler 750-301 and 750-303 are certified of PNO with Z00241 and Z00242. The Interbus coupler 750-304 has passed the relevant tests in accordance with the Interbus conformance requirements (number 111). The DeviceNet coupler 750-306 has succesfully passed through the conformance test of Open DeviceNet Vendors Association Europe.
INTERBUS / General conditions


Digital Inputs (24 V AC/DC, 120 V AC, 230 V AC, 48 V DC) PN: 750-400...415


The supply is applied by a series-connected termination to each I/O module for the respective operating voltage. Power connections are made automatically from module to module when snapped onto the DIN rail. Attention: The lowest power jumper contact is not carried out for some modules (e.g. 4-channel)! A module which needs all contacts (e.g. 2 channel digital) may not be connected to the right hand side of modules which do not have 3 power jumper contacts (e.g. 4 channel modules). All 2-channel digital inputs are 4-conductor devices allowing the direct connection of 4- conductor sensors with the terminations V+, 0V, ground and signal. The 4-channel digital inputs are suitable for the direct connection of two 3-conductor sensors (V+, 0V, signal). The power distribution module 750-614 is available for the connection of more sensors to V+ and 0V. The modules 750-408 and 750-409 are low-side switching. A 2-wire proximity switch can be connected to the modules 750-410 and 750-411. RC filters are series-connected to the 5, 24 and 48 V versions for noise rejection and switch debouncing. They are available with time constants of 3.0 ms and 0.2 ms. The standard numerical assignment for bus operations is from left to right, starting with the LSB. The positions of the different I/O modules in the configured node/station are selectable by the user. A block type configuration is not necessary. The Input module can be connected to all buscouplers of the WAGOÇI/OÇSYSTEM.
Digital Inputs 750-400...415

Item Number 750- 400 401 402 403 Number of inputs 2 4 Input filter 3 ms 0.2 ms 3 ms 0.2 ms Nominal voltage 24V DC (-15%/+20%) Signal voltage (0) -3V...+5V DC (std. EN 61131 Typ 1) Signal voltage (1) 15V...30V DC (std. EN 61131 Typ 1) Input current (internal) 2.5 mA max. 5 mA max. Input current (field side) 5 mA typ. Isolation 500 V system/power supply Internal bit width 2 4 Configuration no address or configutation adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 to 2.5mm2
Dimensions (mm) WxHxL 12 x 64* x 100 (*from upper edge of carrier rail)
Item Number 750- 405 406 410* 411* Number of inputs 2 2 Input filter 10 ms 3 ms 0.2 ms Nominal voltage 230 V AC (-15%/+10%)
24V DC (-15%/+20%))
Signal voltage (0) 0 V...40 V AC
-3 V ... +5 V DC (std.
EN 61131 Type 2) Signal voltage (1) 79 V...1.1 UN AC
11 V ... 30 V DC (std. EN 61131 Type 2) Input current (internal) 2 mA 2.5 mA max. Input current (field side) 6.5 mA typ. 4.5 mA typ. 8 mA typ. Isolation 4 kV system/power supply 500 V system/power supply Internal bit width 2 Configuration no address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 to 2.5mm2
Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail)
*) 2 - wire proximity switch, current without load max. 2 mA
Digital Inputs 750-400...415

Item Number 750- 408 409 412 413 Number of inputs 4 2 Input filter 3 ms 0,2 ms 3 ms 0,2 ms Nominal voltage 24V DC (-15% / +20%) 48 V DC (-15% / +20%) Signal voltage (0) 15 V...30 V DC -6 V ... +10 V DC Signal voltage (1) -3 V...5 V DC 34 V ... 60 V DC Input current (internal) 10 mA max. 5 mA max. Input current (field side) 3.5 mA typ. Isolation 500 V system/power supply Internal bit width 4 2 Configuration no address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0,08 to 2,5 mm2
Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail)
Item Number 750- 414 415 Number of inputs 4 4 Input filter / Conversion time
0.2 ms 20 ms
Nominal voltage 5 V DC 24 V AC/DC (-15%/+20%) Signal voltage (0) 0...0.8 V DC -3...+5 V DC
0...+5 V AC Signal voltage (1) 2.4 V...5 V DC 11 ... 30 V DC 10 ... 27 V AC Input current (internal) 5 mA 10 mA Input current (field side) 50 µA typ. 7.5 mA DC 7.6 9.5 mA AC Isolation 500 V system/power supply 500V system/power supply 50 V channel/channel Internal bit width 4 4 Configuration no address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0,08 to 2,5 mm2
Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail)
Digital Inputs 750-400...415


Counter modules PN 750-404, 750-404/000-001, 750-404/000-002 750-404/000-003, 750-404/000-004 Up/Down Counter 100 kHz, 750-404
The described configuration is counter with up/down input.
The following description is preliminary and is applicable to the factory configuration.
The counter module is able to run with all WAGOÇI/OÇSYSTEM bus-couplers (except for the economy type).
Counter Module 750-404 1
:$*2⇓,2⇓6<67(0


Number of outputs 2 Output current 0.5 A Number of counter 1 Input current (internal) 70 mA Nominal voltage 24 V DC (-15% +20%) Signal voltage (0) -3V +5V DC Signal voltage (1) +15V...+30V DC Switching rate 100 kHz 10 kHz max. Output current 5 mA typ. Counter size 32 Bit Isolation 500 V system/power supply Bit width 32 Bit (8 Bit verification; 8 bit not used) Configuration none, optional with software parameter Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 to 2.5mm2
Size (mm)WxHxD 12 x 64* x 100 (*from upper edge of the carrier rail)
Counter Module 750-404 2
:$*2⇓,2⇓6<67(0


The counter begins processing with pulses at the CLOCK input. The changes from 0 V to 24 V are counted.
The counter counts up, if the input U/D is set at 24 V. With an open circuit input or 0 V the counter counts backwards.
The two bottom contacts each include another output. These outputs are activated through bits in the control byte.
The control byte has the following bits:

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 x Set Counter Block Counter Output value at output O2
The status byte has the following bits:

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
With the control and status-byte the following tasks are possible:
Set the counter: Put Bit 5 into the control byte. The counter with the 32 bit value is loaded into output bytes 0-3. As long as the bits are set, the counter can stop and information is stored. The ensuing data of the counter will be conveyed to the status byte.
Blocking the counter: Bit 4 is set into the control byte, then the count process is suppressed. Bit 4 in the status byte communicates the suppression of the counter.
Set the outputs: Bits 2 and 3 set the additional two outputs of the counter module.
The result of the counter is in binary.
Counter Module 750-404 3
:$*2⇓,2⇓6<67(0

The counter is set with “Set Counter” to the value 0x0000.0000 - 0X1X.XXXX, 0x00, 0x00, 0x00, 0x00 are carried over as output value
(carry over the control-byte and the new counter position), -wait until the input value is 0X1X.XXXX, 0x00, 0x00, 0x00, 0x00
(the status-byte shows the loading feedback) , -carry over 0x00, 0x00 as output value (release counter). Wait for the first and further counting pulse -the input value is XX00.XXXX, 0x00, 0x00, 0x00, 0x00 (no counting pulse received) -the input value is XX00.XXXX, 0x00, 0x00, 0x00, 0x01 (1 counting pulse received) -the input value is XX00.XXXX, 0x00, 0x00, 0x00, 0x02 (2 counting pulses received) - -the input value is XX00.XXXX, 0xFF, 0xFF, 0xFF, 0xFF (maximum counting position is reached) -the input value is XX00.XXXX, 0x00, 0x00, 0x00, 0x00 (a further counting pulse causes an overflow) -the input value is XX00.XXXX, 0x00, 0x00, 0x00 0x01, (a further counting pulse is received)
Counter Module 750-404 4
:$*2⇓,2⇓6<67(0



The counter module also can be ordered as counter with enable input (750-404/000- 001).
The counter begins processing with pulses at the CLOCK input. The changes from 0 V to 24 V are counted. The counter counts down if the input U/D is set at 24 V. With an open circuit input or 0 V the counter counts up.
The data format of the module is 4 bytes data and a control/status byte. The module is a 32 Bit counter. The ID Code os 180 (0xB4). The format of input and output data is the same as 750-404.
The counter module is able to run with all WAGOÇI/OÇSYSTEM bus-couplers (except for the economy type).
Counter Module 750-404 5
:$*2⇓,2⇓6<67(0



The counter module also can be ordered as peak time counter with 750-404/000-002.
This description is only intended for hardware version X 0 0 0 1-. The serial number can be found on the right side of the module.
The counter begins processing with pulses at the CLOCK input. The changes from 0 V to 24 V are counted. The counter counts up if the input U/D is set at 24 V. With an open circuit input or 0 V the counter counts backwards.
The two bottom contacts each include another output. These outputs are activated through bits in the control byte.
The counter module is able to run with all WAGOÇI/OÇSYSTEM bus-couplers (except for the economy type).
Counter Module 750-404 6
:$*2⇓,2⇓6<67(0


The counter begins processing with pulses at the CLOCK input for a special time span. The time span is predefined as 10 s. The state of the counter is stored in the processs image until the next period. After the recording the counting starts again at 0.
The activation of the counting and the synchronisation with the SPS is made by a handshake in the control and status byte.
The end of thre counting period and thus the new process data is signaled by a toggel bit in the status byte.
The control byte has the following bits:

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
The status byte has the following bits:

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Counter Module 750-404 7
:$*2⇓,2⇓6<67(0



The counter module 750-404/000-003 measures the period of the 24 V DC input signal at the CLOCK terminal and converts it into a corresponding frequency value. The measurement is enabled if the GATE terminal is an open circuit input or 0V. To disable processing, the GATE input is to be set to 24 V DC.
The terminals O1 and O2 work as binary outputs. Each output can be activated via specific bits in the CONTROL byte.
The high states of the input and output channels are each indicated by a LED. To recognize low frequency or near zero frequency signals, the maximum time between two data updates is parameterizable.
Counter Module 750-404 8
:$*2⇓,2⇓6<67(0
Status CLOCK · power jumper contacts

Item-No.: 750- 404/000-003 Supply Voltage 24V DC (-15%/+20%) Input Voltage (low) -3V - 5V DC Input Voltage (high) 15V - 30V DC Input Current 5mA typ. at 24V DC Min. Pulse Width 10µs Output Current 0.5A (short circuit protection) Voltage Drop 0.6V DC max. at 0.5A Frequency Range: Integration time = 1 period 0.1 - 100Hz, Resolution 0.001Hz Integration time = 4 periods 1 - 1,000Hz, Resolution 0.01Hz Integration time = 16 periods 10 - 10,000Hz, Resolution 0.1Hz (1Hz) Measuring Error: Range 0.1 - 100 Hz < ± 0.05% Range 1 - 1000Hz < ± 0.05 % Range 10 - 10000Hz < ± 0.2 % Data Format: Process Image 5 Byte In- and Output Internal Bit Width 8 Bit CONTROL/STATUS + 32 Bit DATA Input Current (internal) 80mA max. at 5V DC Operating Temperature 0°C +55°C Wire Connection CAGE CLAMP; 0.08 to 2.5mm2
Size (mm) WxHxD 12 x 64* x 100 (*from upper edge of carrier rail)
Frequency Range: Integration time = 1 period 0.1 - 8,000Hz, Resolution 0.001Hz Integration time = 4 periods 0.25 - 32,000Hz, Resolution 0.01Hz Integration time = 16 periods 1 - 100,000Hz, Resolution 0.1Hz (1Hz) Measuring Error: Range 0.1 - 8000Hz < ± 1% Range 0.25 - 32000Hz < ± 1.5 % Range 1 - 100000Hz < ± 1.5 %
Counter Module 750-404 9
:$*2⇓,2⇓6<67(0


The counter module acquires the time between one or more rising edges of the CLOCK input signal and calculates the frequency of the applied signal. The calculation and process image update are initiated every 1st, every 4th or every 16th
rising edge depending on the integration time selected via the CONTROL byte. The first detection of a rising edge starts the cyclic period measurement and cannot provide a valid frequency value. In this case the module will send 0xFFFFFFFFH for input information. The same input value is returned when a static high or static low signal is applied to the CLOCK input. If there are no signal changes seen at the CLOCK input, the module can be forced to update the process image after defined parameterizable time spans. In this state the module will send the non valid value 0xFFFFFFFFH too. The following figures illustrate a process data cycle.

(integration time = 1 period)

(integration time = 4 periods)
Counter Module 750-404 10
:$*2⇓,2⇓6<67(0



E 5(*B5(4 79'5(4 6(7B4 6(7B4 5$1*(B6(/ 5(4 5$1*(B6(/ 5(4 5(*B5(4 15':5 5(*B$

5(*B5(4 $FFHVVWRWKHUHJLVWHUVWUXFWXUHLVUHTXHVWHGEEFRQWDLQWKHDGGUHVVRIWKHUHJLVWHU 5(*B$$ 5HJLVWHUDGGUHVV 79'5(4 5HTXHVWWRFKDQJHWKHPD[LPXPWLPHZLWKRXWYDOLGGDWD 6(7B4 &RQWURO2XWSXW4 4RII 4RQ 6(7B4 &RQWURO2XWSXW4 4RII 4RQ 5$1*(B6(/5(4 6HOHFWLRQRIWKHLQWHJUDWLRQWLPHDQGWKHUHSUHVHQWDWLRQRIPHDVXUHGIUHTXHQF\YDOXH 5$1*(B6(/5(4 6HOHFWLRQRIWKHLQWHJUDWLRQWLPHDQGWKHUHSUHVHQWDWLRQRIPHDVXUHGIUHTXHQF\YDOXH

E 5(*B$&. 67B*$7( 79'$&. 67B4 67B4 5$1*(B6(/ $&.
5$1*(B6(/ $&. 5(*B$&. 5(*B$

5(*B$&. $FNQRZOHGJPHQWWRWKHUHJLVWHUUHTXHVWEEFRQWDLQWKHDGGUHVVRIWKHUHJLVWHU 5(*B$$ 5HJLVWHUDGGUHVV 67B*$7( 6WDWHRI*$7(LQSXW HQDEOHG GLVDEOHG 79'$&. $FNQRZOHGJPHQW79'FKDQJHG 67B$ 6WDWHRIRXWSXW4 67B$ 6WDWHRIRXWSXW4 5$1*(B6(/$&. $FNQRZOHGJPHQWWR5DQJH6HOHFWLRQ)UHTXHQF\YDOXHVDUHYDOLG 5$1*(B6(/$&. $FNQRZOHGJPHQWWR5DQJH6HOHFWLRQ)UHTXHQF\YDOXHVDUHYDOLG
CONTROL Byte · STATUS Byte · Counter 750-404

The input data contain the CLOCK frequency as a binary value. The representation depends on the RANGE_SEL bits in the CONTROL byte. Even the method of measuring is selected via these bits. The following table illustrates the different modes.
,QWHJUDWLRQRYHUSHULRG )UHTXHQF\LQ+] ,QWHJUDWLRQRYHUSHULRGV )UHTXHQF\LQ+] ,QWHJUDWLRQRYHUSHULRGV )UHTXHQF\LQ+] ,QWHJUDWLRQRYHUSHULRGV )UHTXHQF\LQ+]
number of periods to be integrated
If the gate is enabled the input data contains the last valid frequency value. In this state the application cannot request a new range.
The valid frequency range stretches from 0.1 Hz (100D) up to 10 kHz (100000D). To recognize static CLOCK signals, a watchdog timer is implemented. The default value for the timer is 10s. The timer resets on every Power On. The application is able to change the watchdog time during operation by using the CONTROL byte. This can be initiated by writing the corresponding value into the output bytes OUTPUT_DATA 1 and OUTPUT_DATA 0 before setting the TVD REQ bit in the CONTROL byte. The success of the parameter transfer is acknowledged by the module via the TVD ACK bit in the STATUS information.
Attention: The range of the watchdog timer stretches from 0 to 16383ms (0x0000H to 0x3FFFH) in steps of 1ms per digit. Values which raise the permitted range of the watchdog timer are masked with 0x3FFF. If the maximum possible frequency of the different ranges is raised (see the table with maximum frequency ratings), the module will return the non valid data 0xFFFFFFFFH.
actual frequency · Counter 750-404


Output value of the control unit:
Byte Identification D15-D0 Control Byte Output Byte 1 D31-D16 Output Byte 0 Output Byte 3 D47-D32 Output Byte 2

Input value of the control unit:

Byte Identification D15-D0 Status Byte Input Byte 1 D31-D16 Input Byte 0 Input Byte 3 D2D47-D32 Input Byte 2
The input-bytes 0 to 3 form the 32 bit counter-output. In the output-bytes 0 to 3 the initial value of the counter can be set.
Counter 750-404


The power supply is provided by a series-connected supply module for the respective operating voltage. Power connections are made automatically from module to module via the internal P.J.C.s when snapped onto the DIN rail. Attention: The lowest power jumper contact is not carried out for some modules (e.g. 4-channel)! A module which needs all contacts (e.g. 2 channel digital) may not be connected to the right hand side of modules which do not have 3 power jumper contacts (e.g. 4 channel modules). For the digital outputs (without diagnostic) four-conductor devices (V+; 0 V; signal; ground) are standard. In case of 12 mm wide 4-channel digital output modules it is not possible to use 4-conductor devices. 4 signal outputs, 2xV+ and 2x0V are provided. All digital outputs are short-circuit protected. In case of overloads a supply module with fuse (750-601) must be connected on the line side to protect the output modules. The module 750-516 is low-side switching. The indicated output values have been determined for 100% duty cycle. However, in case of the 2 A versions it is possible to operate single channels at higher load currents, however always verify that the total current does not exceed 3.5 A per module. Example: 2x2A (standard); 1x3.0A; 1x0.5A (total current: 3.5 A) The standard numerical assignment for bus operations is from left to right, starting with the LSB. The positions of the different I/O modules in the configured node/station are selectable by the user. A block type configuration is not necessary.The Output module can be connected to all buscouplers of the WAGOÇI/OÇSYSTEM.
Digital Outputs 750-501...504,516, 519


Item Number 750- 501 502 Number of outputs 2 Kind of load resistive, inductive, lamps Nominal voltage 24V DC (-15% / +20%) Output current (DC) 0,5 A 2 A Current consumption (internal)

Isolation 500 V system / power supply Internal bit width 2 Configuration without address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0,08 to 2,5mm2
Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail)

Item Number 750- 504 516*) Number of outputs 4 Kind of load resistive, inductive, lamps Nominal voltage 24V DC (-15% / +20%) Output current (DC) 0,5 A Current consumption (internal)
Isolation 500 V system / power supply Internal bit width 4 Configuration without address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0,08 to 2,5mm2
Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail) *) low-side switching Item Number 750- 519 Number of outputs 4 Kind of load resistive, inductive, lamps Nominal voltage 5 V DC Output current (DC) 20 mA Current consumption (internal)

Isolation 500 V system / power supply Internal bit width 4 Configuration without address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0,08 to 2,5mm2
Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail)
Digital Outputs 750-501...504,516, 519


Technical description: The power supply is provided by a series-connected supply module for the respective operating voltage. Power connections are made automatically from module to module via the internal P.J.C.s when snapped onto the DIN rail. Attention: The lowest power jumper contact is not carried out for some modules (e.g. 4-channel)! A module which needs all contacts (e.g. 2 channel digital) may not be connected to the right hand side of modules which do not have 3 power jumper contacts (e.g. 4 channel modules). Using the digital outputs with diagnostic bit outputs (750-506) allows verification of the I/O channel by the connected bus. Example: a short-circuit at the output or an open circuit will set the appropriate error bit true indicating I/O failure. In this configuration the function module includes 2 digital outputs and 2 separate digital inputs. For the digital outputs with diagnostic four-conductor devices (V+; 0V; signal; ground) are standard. All digital outputs are short-circuit protected. In case of overloads a supply module with fuse (750-601) must be connected on the line side to protect the output modules. The standard numerical assignment for bus operations is from left to right, starting with the LSB. The positions of the different I/O modules in the configured node/station are selectable by the user. A block type configuration is not necessary. When using I/O modules with diagnostics, the existing inputs must be considered accordingly in the configuration of the Node/station. The Output module can be connected to all buscouplers of the WAGOÇI/OÇSYSTEM.
Digital Outputs 750-506


Item Number 750- 506 Number of outputs 2 Current consumption (internal) 15 mA Nominal voltage 24V DC (-15%/+20%) Kind of load resistive, inductive, lamps Output current (DC) 0.5 A Diagnostics open circuit, overload Current consumption (internal) 15 mA typ. + load Isolation 500 V system / power supply Internal bit width 4 in, 4 out Configuration without address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 to 2.5mm2

Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of carrier rail)
The output bits control the state of the outputs.
Bit 3 Bit 2 Bit 1 Bit 0 function no function no function controls O2 controls O1
The input bits show the state of the outputs.

Bit 3 Bit 2 Bit 1 Bit 0 function diagnostics O2 diagnostics O2 diagnostics O1
short circuit 1 0 1 0 power supply too low*
*The diagnostic bits refer to a hysteresis: If the voltage of the field side is higher than 11V in the falling circle, they are switched on. If the voltage is lower than 15,5 V in the growing circle, they are switched off.
Digital Outputs 750-506



The power supply for the solid state relay module is connected by a series-connected supply module for the respective operating voltage of 230 V. Power connections are made automatically from module to module via the internal P.J.C.s when snapped onto the DIN rail. Attention: The lowest power jumper contact is not carried out for some modules (e.g. 4-channel)! A module which needs all contacts (e.g. 2 channel digital) may not be connected to the right hand side of modules which do not have 3 power jumper contacts (e.g. 4 channel modules). The power supply of the control side is not made via the power jumper contacts but directly from the electronics. The respective output contacts of the switching element are therefore always positioned at the field side. One termination point of these contacts must be directly connected to the power supply. For the digital outputs four-conductor devices (V+; 0V; signal; ground) are standard. All digital outputs are short-circuit protected. In case of overloads a supply module with fuse (750-609) must be connected on the line side to protect the output modules. The standard numerical assignment for Bus operation is from left to right, starting with the LSB. The positions of the different inputs in the configured station are via the user’s choice. A block type assembly is not necessary. The Output module can be connected to all buscouplers of the WAGOÇI/OÇSYSTEM.
Digital Outputs 750-509


Item Number 750- 509 Number of outputs 2 Current consumption (internal) 10 mA Switching voltage 0 V...230 V AC/DC Switched current 300 mA AC max. Speed of operation 1.65 ms typ., 5 ms max. Volume resistance 2.1 Ω typ., 3.2 Ω max. Impulse current 0.5 A (20 s), 1.5 A (0.1 s) Overvoltage protection >+/- 380 V (suppressor diode) Isolation 1.5 kV system / power supply Internal bit width 2 Configuration without address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 to 2.5mm2
Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail)
Digital Outputs 750-509



This description is for hard and software version X 2 B 0 2- . The part number is displayed on the right side of the module.
The initial pre-programmed base frequency is for 250 Hz. The resolution is 10 Bits and the pulsewidth is modulated. Attention: The lowest power jumper contact is not carried out for some modules (e.g. 4-channel)! A module which needs all contacts (e.g. 2 channel digital) may not be connected to the right hand side of modules which do not have 3 power jumper contacts (e.g. 4 channel modules).
The following description is preliminary and is applicable to the factory configuration.
The pulsewidth output module 750-511 produces a binary modulated signal of 24 V. The connection of the consuming device should be made via the „O“ and 0 V (common) contacts of the module. The distribution of the 24 V DC is made via the power jumper contacts. If galvanic isolation is desired, a new power feed via a 750-602 is required.
The PWM module can be connected to all buscouplers of the WAGOÇI/OÇSYSTEM (except for the economy type).
Pulsewidth Module 750-511


Part Number 750- 511 Number of outputs 2 Current consumption (internal) 70 mA typical (internal) Nominal voltage 24V DC (-15% +20%) Load type ohmic, inductive Output current 0.1 A, short circuit protected Pulse frequency 1 Hz...20kHz Duty cycle 0%...100% (Ton > 750 ns, Toff > 500 ns) Resolution 10 Bit max. Isolation 500 V system/power Supply Configuration none, optional with software parameter Current Consumption (field side)
15 mA typ.
Internal bit width per channel 16 Bit Data + 8 Bit Control/Status Operating temperature 0°C +55°C Wire connections CAGE CLAMP; 0.08 to 2.5mm2
Dimension (mm)BxHxT 12 x 64* x 100 (*from upper edge of the carrier rail) Preset Frequency 250 Hz Switching Frequency
Pulsewidth Module 750-511


The programming of the on/off times occur with the resolution of 10 bits. The five LSB of the 16 bit value can be zeros or one. The MSB will hold the sign and is preset to the null state.

Value Hex. Dec. 100 1023 0111 1111 1111 1111 7F FF 32767
100 1023 0111 1111 1111 0000 7F E0 32752
50 511 0011 1111 1111 1111 3F FF 16383
25 255 0001 1111 1111 1111 1F FF 8191
12.5 127 0000 0001 0000 0000 01 00 256
0.1955 2 0000 0000 0100 0000 00 40 16
0.0977 1 0000 0000 0010 0000 00 20 32
0 0 0000 0000 0001 1111 00 1F 31

Ill. 1: On/Off time relationships for Table 1.
Pulsewidth Module 750-511


The process image of the 750-511 appears with 6 bytes of input and 6 bytes of output data. The byte allocation for the preset duty cycle has the following modes of formation: Output values:

Function D0 Control Byte D1 Output Byte 1 D2 Output Byte 0 D3 reserved D4 Output Byte 3 D5 Output Byte 2 Input values:

Function D0 Status Byte D1 Input Byte 1 D2 Input Byte 0 D3 reserved D4 Input Byte 3 D5 Input Byte 2 Out(In)put byte 0 Low Byte Out(In)put byte 1 High Byte
Pulsewidth Module 750-511



The power supply for the relay coils is not made via the power jumper contacts but directly from the electronics. The respective output contacts of the switching element are therefore always positioned at the field side. Attention: The lowest power jumper contact is not carried out for some modules (e.g. 4-channel)! A module which needs all contacts (e.g. 2 channel digital) may not be connected to the right hand side of modules which do not have 3 power jumper contacts (e.g. 4 channel modules). Version 1: non-floating (750-512) The power supply is made via a series-connected supply terminal block for the respective operating voltage. Power connections are made automatically from module to module when snapped onto the DIN rail. One termination point of these contacts must be directly connected to the power supply. Version 2: isolated outputs (750-513, 750-514) These I/O modules are not provided with integrated power jumper contacts. Care should be taken to supply each isolated module with separate power supply connections. The standard numerical assignment for Bus operation is from left to right, starting with the LSB. The positions of the different inputs in the configured station are via the user’s choice. A block type configuration is not necessary. The output module can be connected to all buscouplers of the WAGOÇI/OÇSYSTEM.
Digital Outputs 750-512-514,517


Item Number 750- 512 513 Type of contact 2 make contacts Current consumption (internal) 100 mA max. Switching voltage 30 V DC; 250V AC Switching power 60 W; 500 VA cos

Switching current 2 A AC/ DC Isolation 4 kV system/power supply Internal bit width 2 Configuration without address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 to 2.5mm2
Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail)

Type of contact 2 changeover Current consumption (internal) 70 mA max. 80 mA max. Switching voltage 30 V DC; 125 V AC 250 V AC Switching power 30 W; 62.5 VA 1500 VA* Switching current 0.5 A AC/ 1 A DC 1 A AC Isolation 1.5 kV system/power supply
4 kV system/ power supply Internal bit width 2 Configuration without address or configuration adjustment Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 to 2.5mm2
Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail) *ohmic load 1)in design
Digital Outputs 750-512-514,517

Relays in the modules 750-512 and 750-513:
6 Z L WFKHG FXUUHQW>$@
AC ohmic DC ohmic
AC inductive, cosϕ=0.4
7\SLFDOHOHFWULFDOOLIHWLPH
1,E+06
1 X P E HU RIVZ L WFKHV
30 V DC ohmic 120 V AC ohmic 250 V AC ohmic 30 V DC inductive, L/R = 0.7ms
120 V AC inductive, cosϕ=0.4
250 V AC inductive, cosϕ=0.4


2 Channel Analog Inputs 0-20 mA / 4-20 mA (Differential Inputs) PN 750-452, 454, 750-482, 750-484

This description is only intended for hardware version X 2 A 0 0 -. The serial number can be found on the right side of the module.
The input channels are differential inputs and they have a common ground potential. The inputs are connected to +I and -I. The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail.
These I/O modules are not provided with integrated power jumper contacts. The power supply is made by the data contacts with a DC-DC converter. The modules can work self-supporting.
The input module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type)
Analog Inputs 750-452, 454,482,484


Item Number 750- 452 454 482 484 Number of channels 2 2 Nominal voltage via system voltage Current consumption (internal)

Voltage 35 V max. Signal current 0-20mA 4-20mA 0-20mA 4-20mA Resistance 50 Ω typ. Resolution 12 Bit Isolation 500 V System/Power supply Conversion time 2 ms typ. Bit width per channel 16 Bit Data, 8 Bit Control/Status Operating temperature 0°C +55°C Configuration none, optional via software parameter Wire connection CAGE CLAMP; 0.08 to 2.5mm2
12 x 64* x 100 (*from upper edge of the carrier rail)
Analog Inputs 750-452, 454,482,484


All analog values will be shown in a unit numerical format. The resolution is 12 Bits. The following table will explain the numerical format. (750-452, 454). The 3 least significant Bits are not taken into account.

Hex. Dec. 20 20 0111 1111 1111 1000 7F F8 32760
10 12 0100 0000 0000 0000 40 00 16384
5 8 0010 0000 0000 0000 20 00 8192
2.5 6 0001 0000 0000 0000 10 00 4096
0.156 4.125 0000 0001 0000 0000 01 00 256
0.01 4.0078 0000 0000 0001 0000 00 10 16
0.005 4.0039 0000 0000 0000 1000 00 08 8
0 4 0000 0000 0000 0111 00 07 7
Analog Inputs 750-452, 454,482,484


In addition to the full 16 bit indication of the measured value it is possible to use the ‘Siemens format’. The measured value is represented by the most significant 12 Bits. The 3 least significant Bits are reserved for diagnostic and status purposes. (750-482, 484)

> 20 0101 0000 0000 1 50 01 20481
20 0101 0000 0000 50 00 20480
16 0100 0000 0000 40 00 16384
12 0011 0000 0000 30 00 12288
8 0010 0000 0000 20 00 8192
4.0078 0001 0000 0000 1 0 0 0 10 08 4104
4 0001 0000 0000 10 00 4096
4 0001 0000 0000 0 0 1 1 10 03 4099
Analog Inputs 750-452, 454,482,484


> 20 0100 0000 0000 1 40 01 16385
20 0100 0000 0000 40 00 16384
10 0010 0000 0000 20 00 8192
5 0001 0000 0000 10 00 4096
2.5 0000 1000 00008 00 2048
1.25 0000 0100 00004 00 1024
0.625 0000 0010 00002 00 512
0.0976 0000 0000 0000 1 00 08 8
0 0000 0000 00000 00 0
If you have questions about the formatting of this data, please contact WAGO for I/O System technical support.
Analog Inputs 750-452, 454,482,484



This description is only intended for hardware version X 2 A 0 0 -. The serial number can be found on the right side of the module.
The input channels are differential inputs and they have a common ground potential.
The inputs are connected to +I and -I. The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail.
These I/O modules are not provided with integrated power jumper contacts. The power supply is made by the data contacts with a DC-DC converter. The modules can work self-supporting.
The input module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type)
Analog Inputs 750-456


Item Number 750- 456, 456/000-001 Number of channels 2 Nominal voltage via system voltage (DC DC converter) Current consumption (internal)

Overvoltage protection 35 V max. Signal voltage +/- 10 V Resistance 570 kΩ Resolution 12 Bit Isolation 500 V System/Power supply Conversion time 2 ms typ. Bit width per channel 16 Bit Data, 8 Bit Control/Status Operating temperature 0°C +55°C Configuration none, optional via software parameter Wire connection CAGE CLAMP; 0.08 to 2.5mm2
12 x 64* x 100 (*from upper edge of the carrier rail)
Analog Inputs 750-456


All analog values will be shown in a unit numerical format. The resolution is 12 Bits and the 3 LSBs are not taken into account. The following table will explain the numerical format.

> 10 V 0111 1111 1111 1111 7F FF 32767 42
10 0111 1111 1111 XXXX 7F FX 32760 0
5 0100 0000 0000 XXXX 40 0X 16384 0
2,5 0010 0000 0000 XXXX 20 0X 8192 0
1,25 0001 0000 0000 XXXX 10 0X 4096 0
0,0781 0000 0001 0000 XXXX 01 0X 256 0
0,0049 0000 0000 0001 XXXX 00 1X 16 0
0 0000 0000 0000 XXXX 00 0X 0 0
-2,5 1110 0000 0000 XXXX E0 0X 57344 0
-5 1100 0000 0000 XXXX C0 0X 49152 0
-7,5 1010 0000 0000 XXXX A0 0X 40960 0
-10 1000 0000 0000 XXXX 80 0X 32768 0
< -10 V 1000 0000 0000 0000 80 00 32768 41
Analog Inputs 750-456


In addition to the full 16 bit indication of the measured value it is possible to use the Siemens format. The measured value is represented by the most significant 12 Bits. The 3 least significant bits are reserved for diagnostic and status purposes. (750-456/000- 001).

>10 0111 1111 1111 1 0 0 1 7F F9 32761
10 0111 1111 1111 1 0 0 0 7F F8 32760
5 0110 0000 0000 60 00 24576
2,5 0101 0000 0000 50 00 20480
1,25 0100 1000 0000 48 00 18432
0,0049 0100 0000 0000 1 0 0 0 40 08 16392
0 0100 0000 0000 40 00 16384
-2,5 0011 0000 0000 1 0 0 0 30 08 12296
-5 0010 0000 0000 20 00 8192
-7,5 0001 0000 0000 10 00 4096
-10 0000 0000 0000 1 00 00 8
If you hve questions about the formatting of this data, please contact WAGO for the I/O System technical support.
Analog Inputs 750-456



This description is only intended for hardware version X 3 A 0 2 -. The serial number can be found on the right side of the module.
The described configuration is PT 100. The following description is preliminary and is applicable only to the factory configuration.
The inputs are connected to +I and -I. The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail. Attention: The lowest power jumper contact is not carried out for some modules (e.g. 4-channel)! A module which needs all contacts (e.g. 2 channel digital) may not be connected to the right hand side of modules which do not have 3 power jumper contacts (e.g. 4 channel modules).
These I/O modules are not provided with integrated power jumper contacts. The power supply is made by the data contacts with a DC-DC converter. The modules can work self-supporting. The PT100 module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type)
Input for PT100 750-461, 481


Item Number 750- 461, 481, 461/000-002, 461/000-003 Number of inputs 2 Input current (internal) 65 mA Voltage supply via system voltage Sensor types PT100, PT 200, PT 500, PT1000, Ni100, Ni120, Ni1000 Wire connection 2-conductor, 3-conductor (presetting) Temperature range PT: -200°C..+850°C Ni:-60°C...250°C Resolution 0.1°C over the whole area Isolation DC/DC 400V system / power supply Measuring current 0.5mA type
Bit width per channel 16 bits: data; 8 bits: control/status Configuration none, optional via software parameter Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 to 2.5mm2
Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail) Presetting 3-conductor PT100
The function module 750-461 allows the direct connection of PT- or Ni-resistance sensors. The module is suitable for 2- or 3-wire RTDs. Connection is made according to the above wiring diagram.
Linearization is accomplished over the entire measurement range by a microprocessor. The temperature ranges of the above listed RTD types is available to the user. The temperature ranges of the sensors are represented with a resolution of 1 bit per 0.1° C in one word (16 bits). Resulting from this, 0°C corresponds to the hexadecimal value 0000 and 100°C is 03E8 (dez.1000). Temperatures below 0° are represented in two’s complement with a leading ‘1’.
The function module works in the defined temperature range for the PT100 sensors of -200°C to +850°C. The voltage resolution is represented with 16 bits. An A/D converter and processor converts the voltage value to a numerical value proportional to the temperature of the selected resistance temperature sensor.
A short circuit or an interruption of the RTD wire is transmitted to the bus module and indicated by the red error LED. The green LED identifies that the module is communicating properly with the connected Buscoupler.
Input for PT100 750-461, 481


All temperature values will be shown in a unit numerical format. If the mode ‘DEFAULT’ is selected each bit corresponds to 0.1°C. The possible numerical range refers to the standardized temperature range of the used sensors. The following table will explain the numerical format on a preset PT100. In the third column the numerical format for PT1000 (750-461/000-003) is explained.

850 390.481 1384,998 0010 0001 0011 0100 2134 8500
100 138.506 1099,299 0000 0011 1110 1000 03E8 1000
25.5 109.929 1000,391 0000 0000 1111 1111 00FF 255
0.1 100.039 1000 0000 0000 0000 0001 0001 1
0 100 999,619 0000 0
-0.1 99.970 901,929 1111 FFFF -1
-25.5 90.389 184,936 1111 1111 0000 0001 FF01 -255
Input for PT100 750-461, 481
Table 1


All temperature values will be shown in a unit numerical format. Each bit corresponds to 0.1°C. The following table will explain the numerical format for 750-461/000-002.

Hex. Dez. 10 0000 0000 0110 0100 00 64 100
Input for PT100 750-461, 481


In addition to the full 16 bit indication of the measured value it is possible to use the ‘Siemens format’. The measured value is represented by the most significant 12 Bits. The 4 least significant Bits are reserved for diagnostic and status purposes. (750-481)

>400 1111 1111 1111 1 0 0 1 FF F9 65529
883 400 0111 1111 1111 1 0 0 0 7F F8 32866
560 300 0110 0000 0000 60 00 24576
266 200 0100 0000 0000 40 00 16384
0 100 0010 0000 0000 20 00 8192
-125 50 0001 0000 0000 10 00 4096
-185 25 0000 0101 0000 500 1280
-200 20 0000 0100 0000 400 1024
If you have questions about the formatting of this data, please contact WAGO for I/O System technical support.
Input for PT100 750-461, 481



This description is only intended for hardware version X 2 A 0 1 -. The serial number can be found on the right side of the module.
The following description is preliminary and is applicable only to the factory configuration.
The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail.
These I/O modules are not provided with integrated power jumper contacts. The power supply is made by the data contacts with a DC-DC converter. The modules can work self-supporting. Attention: The lowest power jumper contact is not carried out for some modules (e.g. 4-channel)! A module which needs all contacts (e.g. 2 channel digital) may not be connected to the right hand side of modules which do not have 3 power jumper contacts (e.g. 4 channel modules).
The thermocouple module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type)
Input for thermocouple modules 750-462,469


Item Number 750- 462, 469 Number of inputs 2 (differential input, max. +/- 3.5V) Voltage supply via system voltage Sensor types J, K, B, E, N, R, S, T, U, L, mV Messung Cold junction compensation on each module Measuring accuracy
Input current (internal) 65 mA max. Bit width per channel 16 Bit: data; 8 Bit: control/status* (detection of broken wire 750-469) Configuration none, optional via software parameter Operating temperature 0°C +55°C Connection technique CAGE CLAMP; 0.08 to 2.5mm2
Dimensions (mm)WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail) Presetting -100°C / +1370°C, Typ K
The function module 750-462 permits the direct connection of thermocouple sensors. The module is suitable for 2 or 3-wire thermocouples. For the 2-wire connection technique, connect the thermocouple wires between TC- and TC+ . For the 3-conductor technique the shield is also connected. The operation of grounded sensors is provided by means of internal electrical isolation.
The function module 750-469 alos detects a broken wire. You can find the PNs for the different sensor types for 750-462 in the following table.
The linearization is provided over the complete range by a microprocessor. The temperature ranges of the sensors are represented with a resolution of 1 bit per 0.1°C in one word (16 Bit). Thus, 0°C corresponds to the value 0000, and 25.5°C correspond to the value 0 x 00FF. Temperatures below 0°C are represented in two’s complement with a leading ‘1’.
Within the whole range of all thermocouples, the function module works like a ‘µV meter’. The voltage resolution is represented with 16 bits. A processor converts the voltage value into a numerical value proportional to the measured temperature of the selected type of thermocouple.
In order to compensate the offset voltage at the clamping point, a cold junction thermocouple compensation calculation is carried out. The circuit contains a temperature measuring sensor at the ‘CAGE CLAMP’ connection and considers the temperature offset voltage when calculating the measured value.
Input for thermocouple modules 750-462,469

L -25°C +900°C K -100°C...1370°C (Default) J -100°C...+1200°C 750-462/000-006 750-469/000-006 E -100°C...1000°C 750-462/000-008 750-469/000-008 T -100°C...+400°C 750-462/000-002 750-469/000-002 N -100°C...+1300°C 750-462/000-009 750-469/000-009 U -25°C...+600°C 750-462/000-011 750-469/000-011 B 600°C...+1800°C 750-462/000-007 750-469/000-007 R 0°C...+1700°C 750-462/000-010 750-469/000-010 S 0°C...+1700°C 750-462/000-001 750-469/000-001 mV-Meter -120 mV...+120 mV 750-462/000-003 750-469/000-003 Table 1: Temperature ranges of the connectable sensors Attention: The range of the mV Meter is 0 to 120mV at the moment! LED functions:
ON: Normal OFF: Watchdog-Timer Overflow If the PLC does not transmit processing data for 100 ms the green LED stops lightning.
Input for thermocouple modules 750-462,469


All temperature values are represented in a uniform numerical format. In the default setting (type K) one Bit corresponds to 0.1°C. The output value corresponds to the temperature range of each sensor as defined according to standards. By using a configuration tool, the output formats can be chosen. The linearization can be switched off and the building of the reference temperature can be switched off also. The following table identifies the numerical format on the default range (type K).

Hex. Dec. 850 35314 0010 0001 0011 0100 2134 8500
Input for thermocouple modules 750-462,469


2 Channel Analog Input 0-20 mA / 4- 20 mA single ended PN 750-465, 750-466, 750-486, 750-465/000-001

This description is only intended for hardware version X 2 A 0 1 -. The serial number can be found on the right side of the module.
The input channels are single ended and they have a common ground potential.
The inputs are connected to +I. Via 24 V / 0 V a sensor can be provided directly from the module. Power connections are made automatically from module to module when snapped onto the DIN rail.
The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail.
The input module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type)
Analog Inputs 750-465,466,486


Item Number 750- 465 465/000-001 466 486 Number of channels 2 Nominal voltage 24 V DC (-15% / +20%) via power jumper contacts Current consumption (internal)
75 mA typ.
Overvoltage protection 35 V max. Signal current 0-20mA 4-20mA Resistance 50 Ω typ. Resolution 12 Bit Isolation 500 V system/power supply Conversion time 2 ms typ. Bit width per channel 16 Bit Data, 8 Bit Control/Status Operating temperature 0°C +55°C Configuration none, optional via software parameter Wire connection CAGE CLAMP; 0.08 to 2.5mm2
12 x 64* x 100 (*from upper edge of the carrier rail)
Dimensions (mm)WxHxL · Analog Inputs 750-465,466,486


All analog values will be shown in a unit numerical format. The resolution is 12 Bits. The following table will explain the numerical format. (750-465, 466). The 3 LSBs are not taken into account.

Hex. Dec. Status LED >20,5 >20,5 0111 1111 1111 1111 7F FF 32767 42 on
20 20 0111 1111 1111 1111 7F FF 32767 0 off
10 12 0100 0000 0000 0XXX 40 00 16384 0 off
5 8 0010 0000 0000 0XXX 20 00 8192 0 off
2,5 6 0001 0000 0000 0XXX 10 00 4096 0 off
0,156 4,125 0000 0001 0000 0XXX 01 00 256 0 off
0,01 4,0078 0000 0000 0001 0XXX 00 10 16 0 off
0,005 4,0039 0000 0000 0000 1XXX 00 08 8 0 off
0 4 0000 0000 0000 0XXX 00 00 7 0 off
0 3,5 - 4 0000 0 0 0 off
0 0 - 3,5 0000 0 0 41 on (4 -20
Analog Inputs 750-465,466,486


In addition to the full 16 bit indication of the measured value it is possible to use the ‘Siemens format’. The measured value is represented by the most significant 12 Bits. The 3 least significant Bits are reserved for diagnostic and status purposes. (750- 465/000-001).

Binary value X : without meaning F : short circuit or F : open circuit Ü : overflow X F Ü
>20,5 0100 0000 0000 1 4001 16385 42 on
20 0100 0000 0000 4000 16384 0 off
10 0010 0000 0000 2000 8192 0 off
5 0001 0000 0000 1000 4096 0 off
2,5 0000 1000 0000800 2048 0 off
1,25 0000 0100 0000400 1024 0 off
0,625 0000 0010 0000200 512 0 off
0,0976 0000 0000 0000 1 0008 8 0 off
0 0000 0000 0000000 0 0 off
Analog Inputs 750-465,466,486

750-466/000-200 or 750-486:

Binary value X : without meaning F : short circuit or F : open circuit Ü : overflow X F Ü
>20,5 0101 0000 0000 1 40 01 16385 42 on
20 0101 0000 0000 50 00 20480 0 off
16 0100 0000 0000 40 00 16384 0 off
12 0011 0000 0000 30 00 12288 0 off
8 0010 0000 0000 20 00 8192 0 off
4,0078 0001 0000 0000 1 0 0 0 1008 4104 0 off
4 0001 0000 0000 1000 4096 0 off
If you have questions about the formatting of this data, please contact WAGO for I/O System technical support.
Analog Inputs 750-465,466,486


2 / 4 Channel Analog Inputs 0-10 V single ended PN 750-467, 468, 487, 488

This description is only intended for hardware version X 2 A 0 0 -. The serial number can be found on the right side of the module.
The input channels are single ended and they have a common ground potential.
The inputs are connected to +I and M. The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail.
These I/O modules are not provided with integrated power jumper contacts. The power supply is made by the data contacts with a DC-DC converter. The modules can work self-supporting.
The input module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type)
Analog Inputs 750-467,468,487,488


Item Number 750- 467 468 487 488 Number of channels 2 4 2 4 Nominal voltage via system voltage (DC DC converter) Current consumption (internal)

Overvoltage protection 35 V max. Signal voltage 0-10 V Resistance 133 kΩ typ. Resolution 12 Bit Isolation 500 V system/power supply Conversion time 2 ms typ. Bit width per channel 16 Bit Data, 8 Bit Control/Status Operating temperature 0°C +55°C Configuration none, optional via software parameter Wire connection CAGE CLAMP; 0.08 to 2.5mm2
12 x 64* x 100 (*from upper edge of the carrier rail)
Analog Inputs 750-467,468,487,488


All analog values will be shown in a unit numerical format. The resolution is 12 Bits. The following table will explain the numerical format. (750-467, 468). The 3 LSBs are not taken into account.

Hex. Dec. Status > 10 0111 1111 1111 1111 7F FF 32767 42
10 0111 1111 1111 1XXX 7F F8 32760 0
5 0100 0000 0000 0XXX 40 00 16384 0
2,5 0010 0000 0000 0XXX 20 00 8192 0
1,25 0001 0000 0000 0XXX 10 00 4096 0
0,0781 0000 0001 0000 0XXX 01 00 256 0
0,0049 0000 0000 0001 0XXX 00 10 16 0
0,0024 0000 0000 0000 1XXX 00 08 8 0
0 0000 0000 0000 0XXX 00 07 7 0
Analog Inputs 750-467,468,487,488


In addition to the full 16 bit indication of the measured value it is possible to use the ‘Siemens format’. The measured value is represented by the most significant 12 Bits. The 3 least significant Bits are reserved for diagnostic and status purposes. (750-487, 488)

>10 0101 0000 0000 1 50 01 20481 42
10 0101 0000 0000 50 00 20480 0
5 0011 0000 0000 30 00 12288 0
2,5 0010 0000 0000 20 00 8192 0
1,25 0001 1000 0000 18 00 6144 0
0,0049 0001 0000 0000 1 0 0 0 10 08 4104 0
0 0001 0000 0000 10 00 4096 0
If you have questions about the formatting of this data, please contact WAGO for I/O System technical support.
Analog Inputs 750-467,468,487,488


2 Channel Analog Input 0-20mA / 4-20mA single ended PN 750-472, 750-472/000-200, 750-474, 750-474/000-200

This description is only intended for hardware and software version X 0 2 0 2-. The serial number can be found on the right side of the module.
The input channels are single ended and they have a common ground potential. The inputs are connected to +I. Via 24 V / 0 V a sensor can be provided directly from the module. Power connections are made automatically from module to module when snapped onto the DIN rail.
The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail.
The input module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type).
Analog Inputs 750-472, 474


Item Number 750- 472 472/000-200 474 474/000-0200 Number of channels 2 Nominal voltage 24 V DC (-15% / +20%) via power jumper contacts Overvoltage protection 24 V max. Internal current 75 mA typ. Input signal 0-20mA 4-20mA Input current < 38 mA at 24 V Resistance 50 Ω Input voltage non-linear/overload protection: U=1,2 V DC+160Ω*Imess Resolution internal 16 Bit, 15 Bit via fieldbus Input filter 50 Hz Noise rejection at sampling frequency
Noise rejection below sampling frequency
Transition frequency 13 Hz Isolation 500 V system/power supply Conversion time 80 ms typ. Bit width per channel 16Bit: Data; optional 8Bit: Control/Status Configuration none, optional via software parameter Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0,08 to 2,5mm2
Dimensions (mm)WxHxL 12 x 64* x 100 *from upper edge of the carrier rail
Analog Inputs 750-472, 474
< -100 dB · < -40 dB


The resolution of 750-472 and 750-474 are 15 Bit.

Hex. Dec. Status LED >20,5 >20,5 0111 1111 1111 1111 7F FF 32767 42 on
20 20 0111 1111 1111 1111 7F FF 32767 0 off
10 12 0100 0000 0000 0000 40 00 16384 0 off
5 8 0010 0000 0000 0000 20 00 8192 0 off
2,5 6 0001 0000 0000 0000 10 00 4096 0 off
0,156 4,125 0000 0001 0000 0000 01 00 256 0 off
0,01 4,0078 0000 0000 0001 0000 00 10 16 0 off
0,005 4,0039 0000 0000 0000 1000 00 08 8 0 off
0 4 0000 00 00 7 0 off
0 3,5 - 4 0000 0 0 0 off
0 0 - 3,5 0000 0 0 41 on (4-20
Analog Inputs 750-472, 474


In addition to the full 16 Bit indication of the measured value it is possible to use the „Siemens format“. The measured value is represented by the most significant 12 Bits. The 3 least significant Bits are reserved for diagnostic and status purpose (750-472/000- 200, 750-474/000-200). The numerical format for 750-472/000-200 is equivalent to S5 463, 750-474/000-200 equivalent to S5 460/465.
Binary value X : without meaning F : short circuit or F: open circuit Ü : overflow X F Ü
Hex. Dec. Status LED
32 0111 1111 1111 1 0 0 1 7F F9 32761 42 on
31,99 0111 1111 1111 0 7F F0 32752 0 off
20,5 0101 0010 0000 1 52 00 20992 0 off
20 0101 0000 0000 50 00 20480 0 off
16 0100 0000 0000 40 00 16384 0 off
12 0011 0000 0000 30 00 12288 0 off
8 0010 0000 0000 20 00 8192 0 off
4,0078 0001 0000 0000 1 0 0 0 10 08 4104 0 off
4 0001 0000 0000 10 00 4096 0 off
3,5 0000 1110 0000 0 0 1 1 0E 00 3584 0 on
0 0000 0000 00000 00 0 0 on
Analog Inputs 750-472, 474
Input current 4-20mA

Binary value X : without meaning F : short circuit or F: open circuit Ü : overflow X F Ü
Hex. Dec. Status LED
30 0110 0000 0000 1 6001 24577 42 on
29,98 0101 1111 1111 1 0 0 0 5F F8 24568 0 on
20,5 0100 0001 1001 1 0 0 0 41 98 16762 0 on
20 0100 0000 0000 4000 16384 0 off
10 0010 0000 0000 2000 8192 0 off
5 0001 0000 0000 1000 4096 0 off
2,5 0000 1000 0000800 2048 0 off
1,25 0000 0100 0000400 1024 0 off
0,625 0000 0010 0000200 512 0 off
0,00976 0000 0000 0000 1 0008 8 0 off
0 0000 0000 0000000 0 0 off
If you have questions about the formatting of this data, please contact WAGO for I/O System technical support.
Analog Inputs 750-472, 474
Input current 0-20mA


2-Channel Analog Input ± 10 V, 16 Bit, single ended 750-476 0 -10 V, 16 Bit, single ended 750-478


750-476 2-Channel Analog Input ± 10 V, single ended
2 AI ± 10 V DC 16 Bit s.e.
750-476/000-200 2-Channel Analog Input ± 10 V, single ended with status infomation within the data word
2 AI ± 10 V DC 16 Bit s.e. S5-466

750-478 2-Channel Analog Input 0-10 V, single ended 2 AI 0-10 V DC 16 Bit s.e.
750-478/000-200 2-Channel Analog Input 0-10 V, single ended with status infomation within the data word
2 AI 0-10 V DC 16 Bit s.e. S5-466
Analog Inputs 750-476, 478
4;13614

This description is only intended for hardware and software version X 0 4 0 1 - .The serial number can be found on the right side of the module.
The input channels are single ended and they have a common ground potential.
The inputs are connected to I and 0V. The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail.
The input module can be connected to all buscouplers of the :$*2®,22®6
Analog Inputs 750-476, 478
4;13614


Item Number 750-476 750-476/000-200 750-478 750-478/000-200 Number of channels 2 Nominal voltage via system voltage (DC/DC) Overvoltage resistance 24 V max. Internal current consumption
75 mA typ.
Input signal +/- 10 V 0 - 10 V Input impedance 130 kΩ typ. Overvoltage protection 24 V protected against polarity reversal Resolution 15 Bit + sign Input filter 50 Hz Noise rejection at sampling frequency
Noise rejection below sampling frequency
Transition frequency 13 Hz Isolation 500 V system/power supply Wandlungszeit 80 ms typ. Bitwidth per channel 16Bit: Data; optional 8Bit: control/status Configuration none, optional via software parameter Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0,08 bis 2,5mm2
Dimensions (mm)WxHxL 12 x 64* x 100 * from upper edge of the carrier rail
Analog Inputs 750-476, 478
4;13614
< -100 dB · < -40 dB


All analog values will be shown in a unit numerical format. The resolution for 750-476 and 750-478 is 15 Bit plus sign.
750-476, -478 Input voltage Value Status LED 0-10V ±10V Binary Hex. Dec. (hex) error I (1,2) >11 >11 0111 1111 1111 1111 0x7FFF 32767 0x42 on

>10,5 >10,5 0111 1111 1111 1111 0x7FFF 32767 0x42 off
10 10 0111 1111 1111 1111 0x7FFF 32767 0x00 off
5 5 0100 0000 0000 0000 0x4000 16384 0x00 off
2,5 2,5 0010 0000 0000 0000 0x2000 8192 0x00 off
1,25 1,25 0001 0000 0000 0000 0x1000 4096 0x00 off
0,0781 0,0781 0000 0001 0000 0000 0x0100 256 0x00 off
0,049 0,049 0000 0000 0001 0000 0x0010 16 0x00 off
0,0003 0,0003 0000 0000 0000 0001 0x0001 1 0x00 off
0 0 0000 0x0000 0 0x00 off
-5 1100 0000 0000 0000 0xC000 49152 0x00 off
-10 1000 0000 0000 0000 0x8000 32768 0x00 off
Analog Inputs 750-476, 478
4;13614


For fieldbus master, which evaluates status information in the data word, e.g. from Siemens, a variant of the function clamp is available. The format containes the status in Bit B0 .. B2. The digitalized measuring value is placed at the position Bit B3 .. B15. The numerical format is equivalent to S5 466.
750-476/000-200 Input Value Status LED voltage
X E O*) Hex. Dec. error I (1,2)
> 11 0011 1111 1111 1 0 0 1 0x3FF9 16377 0x42 on > 10,5 0011 1111 1111 1 0 0 1 0x3FF9 16377 0x42 off 10 0011 1111 1111 1 0x3FF8 16376 0x00 off 5 0010 0000 0000x2000 8192 0x00 off 2,5 0001 0000 0000x1000 4096 0x00 off 1,25 0000 1000 0000x0800 2048 0x00 off 0,0781 0000 0000 1000x0080 128 0x00 off 0,0049 0000 0000 0000 1 0x0008 8 0x00 off 0 0000 0000 0000x0000 0 0x00 off -5 1110 0000 0000xE000 57344 0x00 off -10 1100 0000 0000xC000 49152 0x00 off < -10,5 1100 0000 0000 1 0xC001 49153 0x41 off < -11 1100 0000 0000 1 0xC001 49153 0x41 on *) X : without meaning, E : short circuit or open circuit, O : overflow
750-478/000-200 Input Value Status LED voltage
X E O*) Hex. Dec. error I (1,2)
> 11 0111 1111 1111 1 0 0 1 0x7FF9 32761 0x42 on > 10,5 0111 1111 1111 1 0 0 1 0x7FF9 32761 0x42 off 10 0111 1111 1111 1 0x7FF8 32760 0x00 off 5 0100 0000 0000x4000 16384 0x00 off 2,5 0010 0000 0000x2000 8192 0x00 off 1,25 0001 0000 0000x1000 4096 0x00 off 0,0781 0000 0001 0000x0100 256 0x00 off 0,049 0000 0000 0001 0x0010 16 0x00 off 0,024 0000 0000 0000 1 0x0008 8 0x00 off 0 0000 0000 0000x0000 0 0x00 off < -0,5 0000 0000 0000 1 0x0001 1 0x41 off < -1 0000 0000 0000 1 0x0001 1 0x41 on *) X : without meaning, E : short circuit or open circuit, O : overflow
Analog Inputs 750-476, 478
4;13614
Binary · 0-10 V Binary

Structure of the status byte:
bit 7 6 5 4 3 2 1 0 meaning 0 ERROR res. Overrange Underrange
Analog Inputs 750-476, 478
4;13614



This description is only intended for hardware version X 2 A 0 1 -. The serial number can be found on the right side of the module.
The output signal of 750-550/551 is a 0-10 V signal. Sensors may be connected to „O“ and to the common ground.
The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail.
These I/O modules are not provided with integrated power jumper contacts. The power supply is made by the data contacts with a DC-DC converter. The modules can work self-supporting.
The output module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type)
Analog Outputs 750-550,580


Item Number 750- 550, 580 Number of channels 2 Nominal voltage via system voltage (DC DC converter) Current consumption (internal)

Voltage supply via system voltage (DC-DC) Signal voltage 0-10 V Resistance > 5 kΩ Resolution 12 Bit Isolation 500 V system/power supply Bit width per channel 16 Bit Data, 8 Bit Control/Status Operating temperature 0°C +55°C Configuration none, optional via software parameter Wire connection CAGE CLAMP; 0.08 to 2.5mm2
12 x 64* x 100 (*from upper edge of the carrier rail)
The numerical format All analog values will be shown in a unit numerical format. The resolution is 12 Bits. The 3 LSBs are not taken into account. The following table will explain the numerical format. (750-550).

Hex. Dec. 10 0111 1111 1111 1111 7F F8 32767
Analog Outputs 750-550,580


In addition to the full 16 bit indication of the measured value it is possible to use the ‘Siemens format’. The measured value is represented by the most significant 12 Bits. The 3 least significant Bits are reserved for diagnostic and status purposes. (750-580)

> 10 0101 0000 0000 XXXX 50 01 20481
If you have questions about the formatting of this data, please contact WAGO for I/O System technical support.
Analog Outputs 750-550,580


2 -Channel Analog Outputs 0-20 mA / 4-20 mA PN 750-552, 554, 584

This description is only intended for hardware version X 2 A 0 1 -. The serial number can be found on the right side of the module.
The output signal of 750-552...555, 584 is a 0-10 mA or 4-20 mA signal. Sensors may be connected to „O“ and to the common ground (0V). The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail. Power connections are made automatically from module to module when snapped onto the DIN rail. For a self-supporting function, the power supply has to be connected by an input module (e.g. 750-602).
The output module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type)
Analog Outputs 750-552, 554, 584


Item Number 750- 552 554 584 Number of channels 2 Current consumption (internal)

Nominal voltage 24 V DC (-15% /+20%) via power jumper contacts Signal current 0-20mA 4-20mA 4-20mA Resistance
12 x 64* x 100 (*from upper edge of carrier rail)
All analog values will be shown in a unit numerical format. The following table will explain the numerical format. (750-552/554). The 3 LSBs are not taken into account.

Hex. Dec. 20 20 0111 1111 1111 1111 7F FF 32767
10 12 0100 0000 0000 0000 40 00 16384
5 8 0010 0000 0000 0000 20 00 8192
2.5 6 0001 0000 0000 0000 10 00 4096
0.156 4.125 0000 0001 0000 0000 01 00 256
0.01 4.0078 0000 0000 0001 0000 00 10 16
0.005 4.0039 0000 0000 0000 1000 00 08 8
0 4 0000 0000 0000 0111 00 07 7
Analog Outputs 750-552, 554, 584


In addition to the full 16 bit indication of the measured value it is possible to use the ‘Siemens format’. The measured value is represented by the most significant 12 Bits. The 4 least significant Bits have no function. (750-584)

If you have questions about the formatting of this data, please contact WAGO for I/O System technical support.
Analog Outputs 750-552, 554, 584



This description is only intended for hardware version X 2 A 0 1 -. The serial number can be found on the right side of the module.
The output signal of 750-556 is a +/- 10 V signal. Sensors may be connected to „O“ and to the common ground (0V).
The shield is connected to „S“. The connection is made automatically when snapped onto the DIN rail. These I/O modules are not provided with integrated power jumper contacts. The power supply is made by the data contacts with a DC-DC converter. The modules can work self-supporting.
The input module can be connected to all buscouplers of the :$*2Ç,2Ç6<67(0 (except for the economy type)
Analog Outputs 750-556


Item Number 750- 556 Number of channels 2 Nominal voltage via system voltage (DC DC converter) Current consumption (internal)

Signal voltage +/- 10 V Resistance > 5 kΩ Resolution 12 Bit Isolation 500 V System/Power supply Bit width per channel 16 Bit Data, 8 Bit Control/Status Operating temperature 0°C +55°C Configuration none, optional via software parameter Wire connection CAGE CLAMP; 0.08 to 2.5mm2
12 x 64* x 100 (*from upper edge of the carrier rail)
Analog Outputs 750-556


All analog values will be shown in a unit numerical format. The resolution is 12 Bits and the 3 LSBs are ignored. The following table will explain the numerical format.

Hex. Dec. 10 0111 1111 1111 1111 7F FF 32767
Analog Outputs 750-556



After the fieldbus node is assembled with the correct buscoupler and selected I/O modules, the end module is snapped onto the assembly. It completes the internal data circuit and ensures correct data flow.
The potential multiplication module allows additional + and - voltage connection points (up to 4 additional). This eliminates external terminal blocks.
Item Number 750- 600 614 Voltage - 24 V - 230 V AC/DC Current on contacts - max. 10 mA Operating temperature 0 °C ... + 55 °C Wire connection CAGE CLAMP; 0,08 to 2,5 mm² Dimensions (mm) WxHxL 12 x 64 x 100, (from the upper edge of the carrier rail)

End module, Potential multiplication 750-600,614,616

Technical description:
Use of this module allows increased air- and creepage distances between different field voltages within a node.
There are two different types of the separation module. With PN 750-616 you get a module without printing. PN 750-616/030-000 looks like the right one in the above picture.
Item No. 750-616, 750-616/030-000 Dimensions (mm) W x H x L 12 x 64* x 100, (*from the upper edge of the carrier rail)
End module, Potential multiplication 750-600,614,616



The supply module provides I/O module power through the power jumper contacts. Maximum current supply to all connected modules is 10 A. Maximum current supply to the modules with fuse holder is 6.3 A. Should higher currents be necessary, intermediate supply modules may be added in the assembly. The modules 750-601, 609, 615, 610 and 611 are additionally equipped with a fuse holder. The change of the fuse is very easy by drawing out the fuse holder and changing the fuse. A blown fuse is indicated by a LED. The modules 750-610 and 611 send information about the status of the supply module to the fieldbus coupler through two input bits. Bit1 Bit2 Description 0 0 voltage < 15 V DC 1 0 fuse blown 0 1 fuse o.k., voltage o.k.

Using the supply modules you have to look for the allowed voltage. The following table shows the voltage for the supply modules.
The supply module 750-613 supplies the field side and te internal databus system voltage. The internal system voltage can supply 2 A max. If the sum of the internal current consumption exceeds 2 A, an additional supply module must be added.
Supply modules 750-601,602, 609,615,610,611,613


Item Number 750- 602 612 613 Voltage 24 V DC 0 - 230 V AC/DC 24 V DC (-15%/+20%) Current via contacts max. 10 A Operating temperature 0 °C ... + 55 °C Wire connection CAGE CLAMP; 0,08 to 2,5 mm² Dimensions (mm) W x H x L 12 x 64 x 100, (from the upper edge of the carrier rail) internal current 750-613: max. 2 A


Item Number 750- 601 609 615 Voltage 24 V DC 230 V AC 120 V AC Current via contacts Fuse
max. 6.3 A 5 x 20, 6.3 A Operating temperature 0 °C ... + 55 °C Wire connection CAGE CLAMP; 0,08 to 2,5 mm² Dimensions (mm) W x H x L 12 x 64 x 100, (from the upper edge of the carrier rail)

Item Number 750- 610 611 Number of inputs 2 Current consumption 5 mA Internal bitwidth 2 Voltage 24 V DC 230 V AC Current via contacts Fuse
max. 6.3 A 5 x 20, 6.3 A Operating temperature 0 °C ... + 55 °C Wire connection CAGE CLAMP; 0,08 to 2,5 mm² Dimensions (mm) W x H x L 12 x 64 x 100, (from the upper edge of the carrier rail)
Supply modules 750-601,602, 609,615,610,611,613



The binary spacer module reserves bit-addresses in the WAGO buscoupler. The number of in or outputs can be chosen by two DIP switches. 2, 4, 6 or 8 bits are possible (1, 2, 3 or 4-channel modules). A third DIP Switch chooses inputs or outputs. The kind of configuration is indicated by means of 3 LEDs even if there is no voltage applied.
The binary spacer module works like a supply module. The power supply must be made for the following modules.
Binary spacer module 750-622 1
:$*2⇓,2⇓6<67(0


Item number 750- 622 Number of in- or outputs 2, 4, 6 or 8 Nominal voltage 5 V DC internal Internal current consumption 10 mA max. Voltage (field side) 24 V DC (-15%/+20%) Current via power jumper contacts
Input current (field side) - Isolation 500 V system/power supply Internal bit width 2, 4, 6 oder 8 Configuration none, optional via software parameter Operating temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 to 2.5mm2
Dimensions (mm) WxHxL 12 x 64* x 100 (*from upper edge of the carrier rail)
The DIP switches and LEDs are used as follows. When the switch is OFF the LED is also OFF (dark green symbol). When the switch is ON the LED lightens (yellow symbol).

Binary spacer module 750-622 2
:$*2⇓,2⇓6<67(0



This technical description is only valid for hardware and software versions X 2 B 0 2 . The product series number is printed on the right side of the module.
The operational mode of the module is factory preset to discern a 24 bit absolute encoder Graycode signal transmitted at 125kHz.
The following description is preliminary and is applicable to the factory configuration.
The SSI Interface is able to run with all WAGOÇI/OÇSYSTEM bus-couplers (except for the economy type).
SSI encoder 750-630


Series 750 630 630/000-001 630/000-006 Encoder connections Data Input: D+; D-; Clock Output: CI+; CI- Current consumption (internal)
85mA typ.
Power supply 24V DC (-15%/+20%) Sensor power supply 24V DC via power jumper contacts Baud rate max. 1 MHz Data field width 32 Bit Signal output (clock) differential RS 422 Signal input (positional) differential RS 422 Output data format Graycode / Dualcode Bit width 32 Bit: Data; 8 Bit: Control/Status Configuration none, optional via software parameter Signal isolation 500 V system/power supply Temperature range 0°C +55°C Wire connection CAGE CLAMP; 0.08 x 2.5mm2
AWG 28-14 Dimensions (mm) WxHxL 12 x 64* x 100 (*from upper edge of carrier rail) Default Configuration 125 kHz 125 kHz 250 kHz Graycode Binary Graycode 24 Bit Data Resolution
24 Bit Data Resolution
24 Bit Data Resolution
SSI encoder 750-630



Input Type Function Signal D+ and Signal D- Input, RS422 Positional data from encoder, Graycode. Signal Cl+ and Signal CL- Output, RS422 Clock signal output for communications interface. +24 V DC Input 24 V DC supply voltage to module, field connection. 0 V DC Input 0 V DC supply voltage return to module, field connection.
The use of this module in conjunction with a SSI encoder provides direct positional information rather than the type of data resultant from incremental type encoders. Absolute encoders are comprised of several data disks which generate a data word which is unique through out the 360 degrees of rotation. The data format is a modified binary pattern in either Graycode or Dualcode.
The resolution of the sensor depends upon the configuration of the sensor and the physical number of revolutions in the motion profile. Since the basis of the encoder is to provide absolute positional information based upon a mechanical configuration limited to one revolution or less. The maximum resolution of this module is 24 bit.
The frequency of the data signal input to the SSI module is maintained at 125 kHz. Listed below are the recommended cable lengths for the various clock signal Baud rates.
Baud rate Maximum cable length 100 kHz 400 meters 200 kHz 200 meters 300 kHz 100 meters 400 kHz 50 meters
SSI encoder 750-630

The module is seen like an analog input with 2 x 16 Bit input data.
Inputs:
Word Data Word Designation D0 (Bit 0-15) Positional data, Input byte 1
Positional data, Input byte 0 D1 (Bit 16-31) Positional data, Input byte 3
Positional data, Input byte 2
SSI encoder 750-630



This technical description is only valid for hardware and software versions X 2 B 0 1 . The product series number is printed on the right side of the module.
The described operational mode is 4 times or quadrature sampling.
The following description is preliminary and is applicable to the factory configuration.
The Quadrature Encoder Interface is able to run with all WAGOÇI/OÇSYSTEM bus- couplers (except for the economy type).
Quadrature Encoder 750-631

Series 750- 631 631/000-001 Encoder connections A, A(inv.); B, B(inv.); Index, Index(inv.) Current consumption (internal)
Sensor supply voltage 5 V DC Data word 16 Bit Binary Maximum frequency 1 MHz Counter modes 1-2-4 times sampling Data latch word 16 Bit Commands read, reset, start Supply voltage 24 V DC (-15%/+20%) Current consumption 85mA Field (without sensor) Sensor 0.1 A (without sensor load) Bit width 1 x 32 Bit: Data; 8 Bit:Control/Status Configuration none, optional via software parameter Operational temperature 0°C +55°C Wire connection CAGE CLAMP; 0.08 x 2.5mm2
AWG 28-14 Dimensions (mm) WxHxL 24 x 64* x 100 (*from upper edge of the carrier rail) Default configuration 4 times sampling 1 time sampling
25 mA · Quadrature Encoder 750-631


The quadrature encoder interface accepts up to two input signals for the counting increment. The index pulse may also be considered should the control configuration require. There is also a Latch and Gate input available on the module for added functionality.
The quadrature encoder provides two signals that are shifted 90 degrees from each other, signals A and B. In order to achieve a better common mode noise rejection ratio, the output signals from the encoder are transmitted via a differential signal. Their complement signals, A(inv.) and B(inv.) are also transmitted. A directional determination may be made by which signal leads. If the A signal leads, the direction is considered to be forward. If the B signal leads, the direction is considered to be reverse. By exchanging the A and A(inv.) the phase relationship will be changed by 180 degrees, thus allowing the direction to be preset via the wiring configuration. Most quadrature encoders have an Index signal, or Z rev, as well as the incremental signal. This signal provides one pulse per revolution with a duration equal to an incremental pulse.
The inputs to the quadrature encoder module must be supplied from an encoder with Line Driver Outputs for proper operation. The 5 Volt DC output may be used to power the encoder. The 24 Volt DC input supply must be provided from an external power supply. The Gate and Latch inputs are 24 Volt DC.
Module Inputs and Outputs

Shield Input Shield connection for encoder wiring Sensor 0V DC Output Supply return for encoder supply Sensor +5V DC Output 5 Volt DC supply for encoder +24V DC Input 24 Volt DC supply, field connection 0V DC Input. Supply return, field connection Gate Input, 24V DC 24 Volt DC input for gate signal
Latch Input, 24V DC 24 Volt DC input for Latch signal
The Input Gate stops the counter. Only 0 V or an open connection initialize the counter. 24 V stops the counting process.
Quadrature Encoder 750-631

The input Latch controls the overtaking of the actual counter value into the Latchregister. This input is activated by teh control bit EN_LATEXT („1“). EN_LACT has to be deactivated („0“). The first change from 0 V to 24 V at the Latch input takes the actual counter value into the Latchregister. The control byte contains the information as listed below.

Control Byte Configuration Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 x CFAST_M x x CNT_SET EN_LATEXT EN_LATC 0 x Operation Mode
x x Counter Set Release Latch Release Index Pulse
Please note Bit 7 is a reserved bit and must always be set to 0. It is responsible for register communication which is not decribed in this chapter.

Bit Function CFAST_M Fast mode operation. Only the counter module function will be operable. All other control bits will be ignored. CNT_SET The counter module will be preset to a count value with a rising edge. EN_LATEXT 0=The external latch input is deactivated. 1=The module will latch in the counter data on the first rising edge. Other changes have no effect. EN_LACT 0=Latching data with the Index pulse is deactivated. 1=The Index pulse will latch in the counter data on the first rising edge. Other changes have no effect.
The status byte contains the information as listed below.
Status Byte Configuration Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 x x OVERFLOW UNDERFLOW CNTSET_ACC LATEXT_ VAL
LATC_ VAL 0 x x Counter Overflow
External Latch Ack.
Bit Function OVERFLOW The Overflow bit will be set if the counter value rolls over from 65535 to 0. This bit will automatically be reset if the counter passes through more than one third of the count range, 21845 to 21846, or if an Underflow occurs. UNDERFLOW The Underflow bit will be set if the counter value rolls back from 65535 to 0. This bit will automatically be reset if the counter passes through more than two thirds of the count range, 43690 to 43689, or if an Overflow occurs. CNTSET_ACC The Counter Set Acknowledge but is set when a valid counter value is preset to the module. LATEXT_VAL The Latch External Valid Acknowledge bit is set when a counter value is latched into the module via the Latch input. LACT_VAL The Latch Index Pulse Valid Acknowledge bit is set when a counter value is latched into the module via the Index pulse.

It is possible to process and/or check the below listed actions via the control and status bits.
Extending the 16 bit counting range: The internal counting range is 16 bits or a maximum value of 65535. Should the application require an extended count range the location-difference-integration method may be employed. This method uses the control system to store the interrogated counter value. Any new interrogated value will have the previously stored counter value subtracted from it. This value will then be added to an accumulated register value. It is assumed that the counter difference of the two interrogated values is smaller than 16 bits therefore overflows need not be considered.
Another method calculates the extended counter range via the underflow and overflow status bits. The interrogated value is either added or subtracted to the accumulation register depending upon the status of the overflow or underflow bits.
Set Counter Position: The presetting of the counter is possible via the CNT_SET bit. The desired preset is loaded into the data register and the CNT_SET bit is set from 0 to 1. The CNTSET_ACC bit will be set to 1 when the preset value is loaded into the count register.
Maintaining the Present Counter Position: The counter present value may be maintained or latched via the external Latch input. First the external latch must be enabled via the EN_LATEXT bit. Once the input is enabled, the data will be latched into the counter module upon a 0 to 1 transition. Upon completion of the latch process the external latch valid bit LATEXT_VAL will be set to 1.
Maintaining a Reference Point: The storage of a present counter value may also accomplished via the Index pulse from the encoder. First the index latch enable bit must be set, EN_LACT, to a value 1. The counter present value will be latched upon the low to high transition of the Index input. Upon completion of the data latch process the Index Latch Valid bit, LACT_VAL will be set to 1.
Quadrature Encoder 750-631


The module is seen like an analog module with 3 x 16 Bit input and output data.
Outputs:

Word function D0 (Bit 0-15) control byte set counter-Byte1 D1 (Bit 16-31) set counter-Byte0 D2 (Bit 32-47)
Inputs:

Word function D0 (Bit 0-15) Statusbyte counter byte 1 D1 (Bit 16-31) counter byte 0 D2 (Bit 32-47) Latch value-Byte1 Latch value-Byte0
Quadrature Encoder 750-631


RS232C Interface, TTY Interface -20 mA Current Loop RS485C Interface PN 750-650, 750-651, 750-653, 750-650/000-001

This technical description is only valid for hardware and software versions X 2 C 0 3 . The product series number is printed on the right side of the module.
The operational mode described below is the presetting.
The following description is preliminary and is applicable to the factory configuration. Many other operational modes are possible (please contact WAGO for the corresponding settings).
The interface module is able to run with all WAGOÇI/OÇSYSTEM buscouplers (except for the economy type).

Series 750- 650,650/000-001 651 653 Transmission channel 2 (1/1), T x D and R x D, full duplex
2, autom. Send/Receive Transmission rate 1200 - 19200 baud Bit skew < 3 % - - Bit transmission - 2 x 20 mA passive
acc. to ISO 8482/ DIN 66259 T 4 Resistance - < 500 Ω - Current consumption (internal)
50 mA max.
Transmission length max. 15 m RS 232 cable max. 1000 m twisted pair
max. 500 m twisted pair Input buffer 128 bytes Output buffer 16 bytes Voltage supply via internal system supply Isolation 500 V System/Supply Bit width internal 1 x 40 bit, 1 x 8 bit Control/Status Configuration none, parameter configuration with software Operating temperature 0 °C ... + 55 °C Wire connection CAGE CLAMP; 0,08 bis 2,5 mm² Dimensions(mm) W x H x L
12 x 64* x 100 (*from upper edge of the carrier rail)
Factory preset Baud rate Bit width internal
9600 baud 1 x 24 bit in/out, 1 x 8 bit Control/Status

The interface module is designed to operate with all WAGO I/O fieldbus couplers. The serial interface module allows the connection of RS 232-Interface devices to the WAGO I/O SYSTEM. The RS 232 Interface module can provide gateways within the fieldbus protocol. This allows serial equipment such as printers, barcode readers, and links to local operator interfaces to communicate directly by the fieldbus protocol with the PLC or PC Master. This module supports no higher level of protocol. Communication is made completely transparent to the fieldbus allowing flexibility in further applications of the serial interface module. The communication protocols are configured at the Master PLC or PC.
The 128 byte input buffer provides for high rates of data transmission. When using lower rates of transmission speed you can collect the received data, with less priority, without loosing data. The 16 byte output buffer provides for faster transmission of larger data strings.
The data transmission takes place at 9.600 baud (default value). 1 startbit, 8 databits and 1 stopbit will be transmitted. No parity is available. The user controls data via the RTS and CTS signals. These signals are generated in the module depending on the loading status of the buffers. These controls can be deactivated by means of an external jumper. RTS and CTS are to be connected.
For testing purposes the Windows 3.11 terminal emulation can be used. A cable with a 9- pole sub-D socket is required. Pin 5 is connected to input M. Pin 2 is connected to TxD and Pin 3 to RxD. RTS and CTS of the module are connected. A hardwarehandshake between terminal emulation and SPS is not possible though.



The interface module is designed to operate with all WAGO I/O fieldbus couplers. The TTY interface module allows the connection of TTY-Interface devices to the WAGO I/O SYSTEM. The TTY Interface module can provide gateways within the fieldbus protocol. This allows serial equipment such as printers, barcode readers, and links to local operator interfaces to communicate directly by the fieldbus protocol with the PLC or PC Master. This module supports no higher level of protocol. Communication is made completely transparent to the fieldbus allowing flexibility in further applications of the serial interface module. The communication protocols are configured at the Master PLC or PC.
The 128 byte input buffer provides for high rates of data transmission. When using lower rates of transmission speed you can collect the received data, with less priority, without loosing data. The 16 byte output buffer provides for faster transmission of larger data strings.
The data transmission takes place at 9600 baud (default value). 1 startbit, 8 databits and 1 stopbit will be transmitted. No parity is available. The drivers are high ohmic. The control of data is made by the user software.
The TTY Interface is passive in sending and receiving , thus having no current sources. For data conversion an active partner is needed or an additional current source has to be connected.
FXUUHQW VRXUFH



SRLQWWRSRLQWFRQQHFWLRQZLWKSDVVLYH SDUWQHUVDQGDGGLWLRQDOFXUUHQWVRXUFHV
EXVFRQQHFWLRQZLWKDFXUUHQWVRXUFH
ZLWKDFWLYHSDUWQHUV
DQGDSDVVLYHPRGXOH
RS232,TTY,RS485 750-650,651,653


The interface module is designed to operate with all WAGO I/O fieldbus couplers. The serial interface module allows the connection of RS485 or RS488-Interface devices to the WAGO I/O SYSTEM. The RS485/RS488 Interface module can provide gateways within the fieldbus protocol. This allows serial equipment such as printers, barcode readers, and links to local operator interfaces to communicate directly by the fieldbus protocol with the PLC or PC Master. This module supports no higher level of protocol. Communication is made completely transparent to the fieldbus allowing flexibility in further applications of the serial interface module. The communication protocols are configured at the Master PLC or PC.
The 128 byte input buffer provides for high rates of data transmission. When using lower rates of transmission speed you can collect the received data, with less priority, without loosing data. The 16 byte output buffer provides for faster transmission of larger data strings.
The data transmission takes place at 9,600 baud (default value). 1 startbit, 8 databits and 1 stopbit will be transmitted. No parity is available. The drivers are high ohmic. The control of data is made by the user software.
The interface module can be used for bus connections as well as for point to point connections. With bus connections, modules that are not connected to the power supply can also be wired. They do not disturb the bus connection.


RS232,TTY,RS485 750-650,651,653


The module is a combined analog input and output module with 2 x 16 bit input and output data. The transfer of the data to be transmitted and the received data is made via up to 3 output and 3 input bytes. One control byte and one status byte are used to control the floating data. Requests are indicated by a change of a bit. An assigned bit indicates execution by adopting the value of the request bit.
Up to 3 characters which have been received via interface can be stored in the input bytes 0 to 2. The output bytes will contain the characters to be sent.
The control byte consists of the following bits:

Control Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 OL2 OL1 OL0 0 IR RA TR Con- stant value must always be 0.
Frames available in output area, OL2 is always 0. eg. OL2, OL1, OL0 = 0,1,1 3 characters should be sent and put into the output.
The status byte consists of the following bits:

Status Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 IL2 IL1 IL0 BUF_F IA RR TA Con- stant value must always be 0.
Frames available in input area, IL2 is always 0. eg. IL2,IL1,IL0 = 0,1,0 2 characters were received and reside in input 0 and input 1.

The PLC is able to control transmission and reception of data by means of the control byte and the status byte.
Initialization of the module:
The transmitting and receiving of data can be done simultaneously. The initialization request has prioirity and will stop transmitting and receiving of data immediately.
Message: input buffer full (Bit 3) Input buffer is full. Data which are received now are lost.


The module is initialized.
- The initialization bit in the control byte is set.
Output byte 0 Control byte Output byte 2 Output byte 1 0x00 0000.0100 0x00 0x00
- After the initialization has been executed, the status byte will give back 000.0100.
Input byte 0 Status byte Input byte 2 Input byte 1 XX 0XXX.X0XX XX XX Module is still being reset XX 0XXX.X1XX XX XX Initialization completed
Sending of the data string “Hello”:
- The first 3 characters and the buffer length of 3 are transmitted.
Output byte 0 Control byte Output byte 2 Output byte 1 ‘H’ (0 x 48) 0011.0000 ‘l’ (0 x 6C) ‘e’ (0 x 65)
- The transmission request bit (TR) is inverted.
Output byte 0 Control byte Output byte 2 Output byte 1 ‘H’ 0011.0001 ‘l’ ‘e’
- As soon as TR=TA, the rest of the data can be sent.

Input byte 0 Status byte Input byte 2 Input byte 1 XX 0XXX.XXX 0 XX XX The data is still being transferred.
- The last 2 characters and the buffer length of 2 are transmitted.
Output byte 0 Control byte Output byte 2 Output byte 1 ‘l’ 0010.0001 XX ‘o’ (0 x 6F)
- The transmission request bit (TR) is inverted.
Output byte 0 Control byte Output byte 2 Output byte 1 ‘l’ 0010.0000 XX ‘o’

- As soon as TA = TR, the data has been transferred to the output buffer.
Input byte 0 Status byte Input byte 2 Input byte 1 XX 0XXX.XXX1 XX XX The data is still being transferred. XX 0XXX.XXX0 XX XX Data transfer completed.
Receiving the character chain “WAGO”
- As soon as RA≠RR, the input bytes contain data.
Output byte 0 Control yte Output byte 2 Output byte 1 XX 0XXX.000X XX XX
Input byte 0 Status byte Input byte 2 Input byte 1 XX 0XXX.0X0X XX XX No received data available. ‘W’ (0 x 57) 0011.0X1X ‘G’ (0 x 47) ‘A’ (0 x 41) The information is in the input bytes.
- After the 3 characters have been processed, RA is inverted.
Output byte 0 Control byte Output byte 2 Output byte 1 XX 0XXX.001X XX XX
- If RA≠RR, the receiving of additional characters will continue.
Input byte 0 Status byte Input byte 2 Input byte 1 XX 0XXX.0X1X XX XX No received data available. ‘O’ (0 x 4F) 0001.0X0X XX XX The information is in the input bytes.
- After the characters have been processed, RA is inverted.
Output byte 0 Control byte Output byte Output byte XX 0XXX.000X XX XX
0 x 23 is a hexadecimal value 0101.1001 is a binary value An X indicates that this particular value has no importance. XX indicates that the whole value has no importance.
Function Non-Function Output Status TxD Input Status RxD


The module is a combined input and output module with 2 x 16 bit input and output data.
Outputs:
Word Description D0 (bit 0-15) Output byte0 Control byte D1(bit16-31) Output byte2 Output byte1
Inputs:
Word Description D0 (bit 0-15) Input byte0 Status byte D1(bit16-31) Input byte2 Input byte1
The RS232 module is also available with a data format of 5 bytes (item-no. 750- 650/000-001).
Outputs:

Word Description D0 (bit 0-15) Control byte Output byte0 D1(bit16-31) Output byte1 Output byte2 D2(bit32-47) Output byte3 Output byte4
Inputs:

Word Description D0 (bit 0-15) Status byte Input byte0 D1(bit16-31) Input byte1 Input byte2 D2(bit32-47) Input byte3 Input byte4




This technical description is only valid for hardware and software versionx X 2 C 0 0 -. The product series number is printed on the right side of the module.
The operational mode described below is for the factory preset mode.
The following description is preliminary and is applicable to the factory configuration. Many other operational modes are possible (please contact WAGO for the corresponding settings.)
The data exchange module is able to run with all :$*2Ç,2Ç6<67(0 buscouplers (except for the economy type).
Data exchange module 750-654


Series 750- 654 Transmission channel TxD and RxD, full duplex, 2 channel Transmission rate 62500 Baud Bit transmission via 2 twisted pair with differential signals Resistance of cable 120 Ω Current Consumption (internal) 65 mA max. Transmission length max. 100 m twisted pair Input buffer 128 Byte Output buffer 16 Byte Voltage supply via internal system Isolation 500 V System/Supply Bit width internal 1 x 40 bits, 1 x 8 bits control/status Configuration none, parameter configuration with software Operating temperature 0 °C ... + 55 °C Wire connection CAGE CLAMP; 0.08 to 2.5 mm² Dimensions (mm) W x H x L 12 x 64* x 100 (*from upper edge of the carrier rail) Factory preset internal bit width 1 x 32 bits in/out, 1 x 8 bits control/status
Data exchange module 750-654


The data exchange module allows the exchange of 4 (5) bytes between different fieldbus systems via multiplexing of a serial connection. The delay which is caused by the multiplexor is < 5ms. The integrated watchdog function switches all outputs to zero if there is no valid information for more than 200 ms via the multiplex connection.
The 128 bytes input buffer provides for high rates of data transmission. When using lower rates of transmission speed you can collect the received data, with less priority, without loosing data. The 16 byte output buffer provides for faster transmission of larger data strings.
The data exchange module is connected peer-to-peer. For the wiring of the serial multiplex connection the RxD and TxD cables are crossed. The following illustrations show the peer-to-peer connection and the internal structure of the data exchange module.


7 6 5 4 3 2 1 0 Input byte0
7 6 5 4 3 2 1 0 Input byte1
7 6 5 4 3 2 1 0 Input byte3
7 6 5 4 3 2 1 0 Output byte2
7 6 5 4 3 2 1 0 Output byte4
7 6 5 4 3 2 1 0 Control byte
7 6 5 4 3 2 1 0 Statusbyte
Data exchange module 750-654


The module is a combined special function input and output module with 1 x 32 (40) Bit input and output data. The tranfer of the data to be transmitted and the received data is made via up to 5 input and 5 output Bytes. One control byte and one status byte are used to control the floating data.
The control byte consists of the following bits:

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
The status byte consists of the following bits:

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Module is in timeout. All output bits are set to 0 (watchdog).
The PLC is able to control transmission and reception of data by means of the control byte and the status byte.
Control of the multiplex connection: In the process image of the transmitting buscoupler one Bit is set to „1“ for the whole time. As long as this Bit is „1“ in the receiving coupler, further input Bits can be evaluated. If the Bit is „0“ the multiplex connection has been disrupted. The further Bits are also 0 because of the watchdog.
Control of the multiplex connection with acknowledge: If the transmitting buscoupler gets an acknowledge from the receiving buscoupler, the received bit must be transfered as an output bit to the process image. The transmission is successful as long as the Bit is „1“.
Handshake: If a serial data exchange should be made with the data exchange module, the handshake can be made via „Toggle Bits“. Therefore an input bit and an output bit are reserved. As soon as those bits are different from each other, a request from the opposite module is made. As soon as the request is executed the output bit is toggled.
Data exchange module 750-654


The ID 179 (hex: 0xB3), ( Data consistence over 4 Byte) is used.

Byte Description D0 Output byte0 D1 Output byte1 D2 Output byte2 D3 Output byte3

Byte Description D0 Input byte0 D1 Input byte1 D2 Input byte2 D3 Input byte3
For the ID 188 (hex.: 0xBC), Data consistence over 6 Byte is used, input and output data are now as follows:

Byte Description D0 Control byte D1 Output byte0 D2 Output byte1 D3 Output byte4 D4 Output byte2 D5 Output byte3

Byte Description D0 Statusbyte D1 Input byte0 D2 Input byte1 D3 Input byte4 D4 Input byte2 D5 Input byte3
For a S7 PLC the function code SFC14 and SFC15 must be used because the data length is more than 4.
Data exchange module 750-654


The module is a combined special function input and output module with 2 x 16 Bit in- and output data.
Description Word High Low n (Bit0-Bit15) Input byte0 Input byte1 n+1 (Bit16-Bit31) Input byte2 Input byte3
Description Word High Low n (Bit0-Bit15) Output byte0 Output byte1 n+1 (Bit16-Bit31) Output byte2 Output byte3
Data exchange module 750-654
Input · Output


The module has 6 Bytes input and output data in the Poll I/O data. Consumed (Tx for the Scanner) and produced (Rx for the Scanner) data size are each 6 Byte more.

Byte Description D0 Control byte D1 Input byte1 D2 Input byte0 D3 Input byte4 D4 Input byte3 D5 Input byte2

Byte Description D0 Status byte D1 Input byte1 D2 Input byte0 D3 Input byte4 D4 Input byte3 D5 Input byte2
The module has 4 Bytes input and output data in the polled I/O data.

Byte Description D0 Input byte0 D1 Input byte1 D2 Input byte2 D3 Input byte3

Byte Description D0 Input byte0 D1 Input byte1 D2 Input byte2 D3 Input byte3
Data exchange module 750-654


The module is a combined special function input and output module with 2 x 16 Bit in- and output data.
Description Word High Low n (Bit0-Bit15) Input byte0 Input byte1 n+1 (Bit16-Bit31) Input byte2 Input byte3
Description Word High Low n (Bit0-Bit15) Output byte0 Output byte1 n+1 (Bit16-Bit31) Output byte2 Output byte3
Data exchange module 750-654
Input · Output


The module is in the list with Index 0x2400 (input) and Index 0x2500 (output). The module has 2 subindexes.
2 Byte special modules, Inputs Idx SIdx Name Type Attrib. Default Description 2400 0 special 2 byte input Unsigned8 ro none number of 2 Byte channels n Input byte0, Input byte1

0xFF 0xFF. Special input Unsigned16 ro none 255. Input channel
2 Byte special modules, Outputs Idx SIdx Name Type Attrib. Default Description 2500 0 special 2 byte output

n Output byte0, Output byte1
0xFF 0xFF. special output
Data exchange module 750-654

Mode class 4: The data is in the 2 Byte objects #BK_AI2W0_XXX, #BK_AI2W1_XXX and #BK_A02W0_XXX. Each module has 2 values.
Mux Content Description n Input byte0, Input byte1 1. and 2. Input byte n+1 Input byte2, Input byte3 3. and 4. Input byte
Mux Content Description n Output byte0, Output byte1 1. and 2. Output byte n+1 Output byte2, Output byte3 3. and 4. Output byte
Mode class 0: The description of the data is the same as for class 4 mode. The data is put into objects No.1, No.2 and No.3 (read/write 2 Byte analog).
Data exchange module 750-654
Input · Output



Content Description Word High Low n - Statusbyte Statusword n+1 Input byte0 Input byte1 1. and 2. Input byte n+2 - Input byte4 5.Input byte n+3 Input byte3 Input byte2 3. and 4. Input byte

Content Description Word High Low n - Statusbyte Statusword n+1 Output byte0 Output byte1 1. and 2. Output byte n+2 - Output byte4 5.Output byte n+3 Output byte3 Output byte2 3. and 4. Output byte
Data exchange module 750-654
Input · Output

Application in Explosive Environments • 1 Foreword
Ex-1.1 Foreword
Today’s development shows that many chemical and petrochemical companies have production plants, production, and process automation machines in operation which use gas-air, vapor-air and dust-air mixtures which can be explosive. For this reason, the electrical components used in such plants and systems must not pose a risk of explosion resulting in injury to persons or damage to property. This is backed by law, directives or regulations, on a national and international scale. WAGO-I/O-SYSTEM 750 (electrical components) is designed for use in zone 2 explosive environments. The following basic explosion protection related terms have been defined.
Primarily, explosion protection describes how to prevent the formation of an explosive atmosphere. For instance by avoiding the use of combustible liquids, reducing the concentration levels, ventilation measures, to name but a few. But there are a large number of applications, which do not allow the implementation of primary protection measures. In such cases, the secondary explosion protection comes into play. Following is a detailed description of such secondary measures.
The specifications outlined here are valid for use in Europe and are based on the following standards: EN50... of CENELEC (European Committee for Electrotechnical Standardisation). On an international scale, these are reflected by the IEC 60079-... standards of the IEC (International Electrotechnical Commission).
Explosive environments are areas in which the atmosphere can potentially become explosive. The term explosive means a special mixture of ignitable substances existing in the form of air-borne gases, fumes, mist or dust under atmospheric conditions which, when heated beyond a tolerable temperature or subjected to an electric arc or sparks, can produce explosions. Explosive zones have been created to describe the concentrations level of an explosive atmosphere. This division based on the probability of an explosion occurring is of great importance both for technical safety and feasibility reasons, knowing that the demands placed on electrical components permanently employed in an explosive environment have to be much more stringent than those placed on electrical components that are only rarely and, if at all, for short periods, subject to a dangerous explosive environment.
WAGO-I/O-SYSTEM 750 Modular I/O-System

2 • Application in Explosive Environments Classification meeting CENELEC and IEC
Explosive areas resulting from gases, fumes or mist:
Explosive areas subject to air-borne dust:
In addition, the electrical components for explosive areas are subdivided into two groups:
Group I: Group I includes electrical components for use in fire-damp endangered mine structures.
Group II: Group II includes electrical components for use in all other explosive environments. The group is further subdivided by pertinent combustible gases in the environment. Subdivision IIA, IIB and IIC takes into account that different materials/substances/gases have various ignition energy characteristic values. For this reason the three sub- groups are assigned representative types of gases:
Modular I/O-System

Application in Explosive Environments • 3 Classification meeting CENELEC and IEC

Hydrogen being commonly encountered in chemical plants, frequently the explosion group IIC is requested for maximum safety.
Moreover, the areas of use (zones) and the conditions of use (explosion groups) are subdivided into categories for the electrical operating means:

1G II Zone 0 Explosive environment by gas, fumes or mist
2G II Zone 1 Explosive environment by gas, fumes or mist
3G II Zone 2 Explosive environment by gas, fumes or mist
WAGO-I/O-SYSTEM 750 Modular I/O-System

4 • Application in Explosive Environments Classification meeting CENELEC and IEC
The maximum surface temperature for electrical components of explosion protection group I is 150 °C (danger due to coal dust deposits) or 450 °C (if there is no danger of coal dust deposit).
In line with the maximum surface temperature for all ignition protection types, the electrical components are subdivided into temperature classes, as far as electrical components of explosion protection group II are concerned. Here the temperatures refer to a surrounding temperature of 40 °C for operation and testing of the electrical components. The lowest ignition temperature of the existing explosive atmosphere must be higher than the maximum surface temperature.

T2 300 °C > 300 °C ≤ 450 °C
T3 200 °C > 200 °C ≤ 300 °C
T4 135 °C > 135 °C ≤ 200 °C
The following table represents the division and attribution of the materials to the temperature classes and material groups in percent:

Temperature classes T1 T2 T3 T4 T5 T6 Total*
94.9 % 4.9 % 0 % 0.2 % 432
* Number of classified materials
Ignition protection defines the special measures to be taken for electrical components in order to prevent the ignition of surrounding explosive atmospheres. For this reason a differentiation is made between the following types of ignition protection:
Modular I/O-System

Application in Explosive Environments • 5 Classification meeting CENELEC and IEC

EEx o EN 50 015 IEC 79-6 Oil encapsulation Zone 1 + 2
EEx p EN 50 016 IEC 79-2 Overpressure encapsulation
EEx q EN 50 017 IEC 79-5 Sand encapsulation Zone 1 + 2
EEx d EN 50 018 IEC 79-1 Pressure resistant encapsulation
EEx e EN 50 019 IEC 79-7 Increased safety Zone 1 + 2
EEx m EN 50 028 IEC 79-18 Cast encapsulation Zone 1 + 2
EEx i EN 50 020 (unit) EN 50 039 (system)
IEC 79-11 Intrinsic safety Zone 0 + 1 + 2
EEx n EN 50 021 IEC 79-15 Electrical components for zone 2 (see below)
Ignition protection “n“ describes exclusively the use of explosion protected electrical components in zone 2. This zone encompasses areas where explosive atmospheres can only be expected to occur rarely or short-term. It represents the transition between the area of zone 1, which requires an explosion protection and safe area in which for instance welding is allowed at any time.
Regulations covering these electrical components are being prepared on a world-wide scale. The standard EN 50 021 allows electrical component manufacturers to obtain certificates from the corresponding authorities for instance KEMA in the Netherlands or the PTB in Germany, certifying that the tested components meet the above mentioned standards draft.
Type “n” ignition protection additionally requires electrical components to be marked , with the following extended identification:
Further information For more detailed information please refer to the national and/or international standards, directives and regulations!
WAGO-I/O-SYSTEM 750 Modular I/O-System

6 • Application in Explosive Environments Classifications meeting the NEC 500
The following classifications according to NEC 500 (National Electric Code) are valid for North America.
The "Divisions" describe the degree of probability of whatever type of dangerous situation occurring. Here the following assignments apply:
Explosion endangered areas due to combustible gases, fumes, mist and dust:
Division 1 encompasses areas in which explosive atmospheres are to be expected occasionally (> 10 h ≤ 1000 h /year) as well as continuously and long-term (> 1000 h /year).
Division 2 encompasses areas in which explosive atmospheres can be expected rarely and short-term (>0 h ≤ 10 h /year).
Electrical components for explosion endangered areas are subdivided in three danger categories:
Class II (dust): Group E (Metal dust) Group F (Coal dust) Group G (Flour, starch and cereal dust)
Modular I/O-System

Application in Explosive Environments • 7 Classifications meeting the NEC 500
Electrical components for explosive areas are differentiated by temperature classes:

T2 300 °C > 300 °C ≤ 450 °C
T2A 280 °C > 280 °C ≤ 300 °C
T2B 260 °C > 260 °C ≤ 280 °C
T6 85 °C > 85 °C ≤ 100 °C
WAGO-I/O-SYSTEM 750 Modular I/O-System

8 • Application in Explosive Environments Identification
According to CENELEC and IEC
Explosion protection group Unit category
Community symbol for explosion protected electrical components
EEx nA II T4
Approval body and/or number of the examination certificate
E = conforming with European standards Ex = explosion protected component
n = Type of ignition Extended identification
2DI 24V DC 3.0ms
55°C max ambient LISTED 22ZA AND 22XM
Hansastr. 27 D-32423 Minden
0.08-2.5mm 2
0V 24V DI1
PATENTS PENDING II 3 G KEMA 01ATEX1024 X EEx nA II T4
op temp code T4A
Grp. A B C D
(750-400, 2 channel digital input module 24 V DC) g01xx03e

Application in Explosive Environments • 9 Identification
According to NEC 500
Area of application (zone)
Explosion protection group (condition of use category)
CL I DIV 2 Grp. ABCD optemp code T4A
Explosion group (gas group)
2DI 24V DC 3.0ms
Hansastr. 27 D-32423 Minden
0.08-2.5mm 2
LISTED 22ZA AND 22XM
0V 24V DI1
op temp code T4A
PATENTS PENDING II 3 G KEMA 01ATEX1024 X EEx nA II T4
Grp. A B C D
(750-400, 2 channel digital input module 24 V DC) g01xx04e
WAGO-I/O-SYSTEM 750 Modular I/O-System

10 • Application in Explosive Environments Installation regulations
In the Federal Republic of Germany, various national regulations for the installation in explosive areas must be taken into consideration. The basis being the ElexV complemented by the installation regulation DIN VDE 0165/2.91. The following are excerpts from additional VDE regulations:
DIN VDE 0100 installation in power plants with rated voltages up to 1000 V
DIN VDE 0101 installation in power plants with rated voltages above 1 kV
DIN VDE 0800 installation and operation in tele-communication plants including information processing equipment
DIN VDE 0185 lightning protection systems
The USA and Canada have their own regulations. The following are excerpts from these regulations:
NFPA 70 National Electrical Code Art. 500 Hazardous Locations
ANSI/ISA-RP 12.6-1987 Recommended Practice
C22.1 Canadian Electrical Code
Modular I/O-System

Application in Explosive Environments • 11 Installation regulations
Further Information Proof of certification is available on request.
Also take note of the information given on the module technical information sheet.