This Relay Interface Card (p/n 1014018) provides potential free true relay interface for AS/400 and other relay connected computers and industrial applications. This relay interface uses a 15-pin D-sub connector and this Relay Interface Card is installed in the slot on rear panel of the UPS.
The UPS does not have to be shut down when installing this Relay Interface Card. 1. Remove the cover on the option slot on the back of UPS to install the Relay Interface Card. 2. Put the Relay Interface Card into the slot and attach it to the rear panel by using the screws removed.

The following information is available from the Relay Interface Card:



1018946 Rev. A 1/2

Table 1. Relay information available.

* Normally closed (NC) /open (NO) connection state when the Relay Interface Card is not powered.
** The shutdown pin (15) needs minimum of 5 seconds high level signal (connection to +12VDC) to perform the UPS shutdown.
The relay contacts are rated for maximum 1A/30VAC or 200mA/60VDC. All relay outputs are galvanically isolated from the other circuits of the UPS (IEC 950, EN 50091-1).
The Relay Interface Card shut down functionality depends on the jumper (JP1, JP2 & JP3) selected on the board and on the UPS mode (Normal or On Battery). The functions are described in table 2.
Table 2. Shut down options.

1018946 Rev. A 2/2