Powerware
User’s Guide
1000-3000 VA
02/15/01

The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC Declaration of Conformity, contact:
Powerware Corporation Koskelontie 13 FIN-02920 Espoo Finland Phone: +358-9-452661 Fax: +358-9-452-66395
Some configurations are classified under EN50091-2 as “Class-A UPS for Unrestricted Sales Distribution.” For these configurations, the following applies:
Powerware is a registered trademark and Advanced Battery Management (ABM) is a trademark of Powerware Corporation.
.Copyright 1999 Powerware Corporation, Raleigh, NC. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Powerware Corporation.

(2000 VA - 3000 VA)
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES-003.
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
(1000 VA - 1500 VA)
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
NOTE This equipment has been tested and found to comply with the limits for a Class B device pursuant to Part 15 of FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a residential environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

The following are examples of symbols used on the UPS to alert you to important information:
Risk of Electric Shock
Do Not Open Cover
Do not remove cover (or back) No user-serviceable parts inside
Refer servicing to the factory
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed.
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. The UPS may contain sealed, lead-acid batteries. Batteries must be recycled.


1 Powerware 5119 –One of the Best! 1
2 Installation 3
Inspecting the Equipment 3 Safety Precautions 3 Installing the UPS 4 UPS Rear Panels 7 3 Operation 11
Turning the UPS On 11 Starting the UPS on Battery 11 Turning the UPS Off 11 Standby Mode 11 UPS Front Panel 12 AC Input LEDs 13 Battery Charge LEDs 13 Load Level LEDs 14 Initiating the Self-Test 14 4 Configuration 15
Why Change Factory Defaults? 15 Nominal Input Voltage 15 Other Settings 15 Configuration Mode 15 5 UPS Maintenance 19
UPS and Battery Care 19 Storing the UPS and Batteries 19 When to Replace Batteries 19 Replacing Batteries 20 How to Replace External Batteries 21 How to Replace Internal Batteries 22 Testing New Batteries 23 Recycling the Used Battery 24
i Powerware® 5119 User’s Guide : www.powerware.com

6 Additional UPS Features 25
Communication Port Configurations 25 Communication Indicator 25 Pin Out 26 Network Transient Protector 27 Load Segments 27 Option Modules 27 7 Specifications 29
8 Troubleshooting 33
Audible Alarms and UPS Conditions 33 Silencing an Audible Alarm 33 Service and Support 35
ii Powerware® 5119 User’s Guide : www.powerware.com
Table of Contents


C H A P T E R 1 POWERWARE 5119 – ONE OF THE BEST!
The Powerware9 5119 uninterruptible power system (UPS) protects your sensitive electronic equipment from basic power problems such as power failures, power sags, power surges, brownouts, and line noise.
Power outages can occur when you least expect it and power quality can be erratic. These power problems have the potential to corrupt critical data, destroy unsaved work sessions, and damage hardware — causing hours of lost productivity and expensive repairs.
With the Powerware 5119, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. The Powerware 5119’s flexibility to handle an array of network devices makes it the perfect choice to protect your LANs, servers, and workstations.

Because an integral part of power protection is power management software, the Powerware 5119 comes fully equipped with a communication port, serial cable, and a CD containing both LanSafe III for networked systems and FailSafe III for standalone systems.

Powerware 5119 – One of the Best!
Providing outstanding performance and reliability, the Powerware 5119’s unique benefits include the following:
: Advanced Battery Management (ABMZ) doubles battery service life,
optimizes recharge time, and provides a warning up to 60 days before the end of useful battery life.
: Buck and Double Boost regulation ensures consistent voltage to your
load by correcting voltage fluctuations without using battery power.
: Hot-swappable batteries simplify maintenance by allowing you to
replace batteries safely without powering down the critical load.
: Network Transient Protector guards your modem, fax machine, and
other network communications equipment from surges.
: Start-on-battery compatibility allows you to power up the UPS even
if utility power is not available.
: Optional power communication cards provide enhanced
communication capabilities for increased power protection and longer battery backup times.
: The Powerware 5119 is backed by worldwide agency approvals.

This section explains:
: Equipment inspection
: Safety precautions
: UPS installation
: UPS rear panels
If any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of receipt of the equipment; 2) Send a copy of the damage claim within 15 days to your service representative.
Read the following before you install the UPS.

carry live voltage even when the UPS is not connected to an AC supply.
: Do not remove or unplug the input cord when the UPS is turned on. This removes
the safety ground from the UPS and the equipment connected to the UPS.
: To reduce the risk of fire or electric shock, install this UPS in a temperature and
humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40C (104F). Do not operate near water or excessive humidity (95% max).
: The sum of earth leakage current from the load connected to the UPS must not
exceed 1.5 mA.
The following steps explain how to install the UPS. Figure 3 on page 6 shows a typical installation only. See “UPS Rear Panels” on page 7 for the rear panel of each model.
Some power management software has a Load Segment feature that allows you to control UPS output receptacles. If you plan to use this feature, read the appropriate sections of your power management software manual before you install the UPS.
Installation

Customer-supplied power cords must correctly rated for the UPS (see “Specifications” on page 29). You can also use the power cord from the largest load if it is correctly rated.
The UPS conducts a self-test and enters Standby mode. If a red Site Wiring Fault or Battery Service indicator stays on, see Table 11 on page 33.
Site Wiring Fault Indicator
NOTE Low voltage models may not recognize 50-Hz outlets. If the UPS does not start when connected to a 50-Hz outlet, unplug the UPS. Press and hold the On button for 3 seconds to start the UPS on battery and reconfigure the nominal input voltage to either 100V or 110V (see ”Configuration Mode” on page 15). Turn the UPS off. Wait for 30 seconds. Then plug the UPS into the outlet.
DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of the heating elements.
The installation is complete. To learn how to operate the UPS, see “Operation” on page 11. To change the factory-set defaults, see “Configuration” on page 15.
Installation · Battery Service Indicator


Connect equipment to UPS Connect communication cable from computer to UPS (optional)
Connect battery to UPS (if applicable)
Installation

This section shows the rear panels of all Powerware 5119 models.
Installation


Installation


10A, IEC-320 Input Connector
Load Segment 1 (Three IEC-320 Receptacles)
Load Segment 2 (Three IEC-320 Receptacles)
Network Transient Protector Load Segment 3 (Three IEC-320 Receptacles)

16A, IEC-320 Input Connector
Load Segment 1 (Three IEC-320 Receptacles)
Load Segment 2 (Three IEC-320 Receptacles)
Network Transient Protector Load Segment 3 (Three IEC-320 Receptacles)

Installation

This section describes:
: Turning the UPS on and off
: Starting the UPS on battery
: Standby mode
: The UPS front panel and LEDs
: Initiating the self-test
After the UPS is connected to a power source, it conducts a self-test and enters Standby mode. To turn on the UPS, press the On button on the front panel (shown in Figure 10). The Power On indicator illuminates indicating that power is available from the rear receptacles.
Starting the UPS on Battery To turn on the UPS without using utility power, press and hold the On button for three seconds. When the UPS starts on battery, it does not conduct a self-test to conserve battery power.
To turn off the UPS, press the Off

The UPS front panel LEDs indicate how the UPS is operating and also alert you of potential power problems. Figure 10 shows the UPS front panel indicators and controls.
AC Input LEDs Load Level LEDs
Site Wiring Fault Indicator

AC Input LEDs The AC Input LEDs show information about the utility power coming into the UPS (see Figure 11).
Normal Utility Input (Buck and Single Boost)
Double Boost is on
The second LED indicates that the UPS is operating normally from utility power. The UPS is providing consistent voltage with the Buck and Single Boost feature.
The third LED indicates that the UPS is using the Double Boost feature to automatically correct voltage fluctuations.
If any AC Input LEDs are red, see page 34 for more information.
Operation

Load Level LEDs The front panel displays the total load current or watts plugged into the UPS (see Figure 13).
Each LED represents 1/3 of a full load rating. When the UPS is approximately fully loaded (66-100%), all three LEDs illuminate. If the load is 33-66% of UPS capacity, the third and fourth LED illuminate. The last LED illuminates if the load is between 5% and 33%.
If any Load Level LEDs are red, see page 35 for more information.
Press and hold the button for three seconds to initiate the self-test. During the test, individual LEDs illuminate as various parts of the UPS are checked. If the UPS finds a problem, an LED indicates where the problem is. For more information, see “Troubleshooting” on page 33.
Operation · 33-66% 5-33% 66-100%

This section explains:
: Why you may want to change factory defaults
: How to reconfigure options
Nominal Input Voltage When the utility power consistently fluctuates, the UPS repeatedly corrects the input voltage by switching to battery power when the nominal input range is:
: Higher than +20% of 120V or 230V nominal
: Lower than -30% of 120V or 230V nominal
: Higher than +20% and lower than -30% of 120V or 230V nominal
You can configure the UPS to more closely match the nominal input voltage by selecting a different input voltage or extending the input voltage range. See Table 1 on page 17 for a list of available options.
Other Settings You can change the UPS default configurations for alarms and shutdown parameters, including: timing for the low battery alarm, the time delay for an unconditional shutdown, alarms for loss of utility power or site fault, and controlling loads that use less than 5% of the current when the UPS is on battery. See Table 1 on page 17 for a list of available options.
When the UPS is in Configuration mode, the LEDs represent the configuration options. The control buttons (On button and button) are used to modify the UPS configuration. Figure 14 shows the LEDs and Table 1 explains the corresponding options.

If you press the On button and nothing happens, the UPS is still in Operation mode. Repeat Step 1 for one beep ONLY to enter Configuration mode, and then perform Step 2.
Repeat Steps 2 and 3 for each option.

1 Press the On button to scroll to the next option. Press the On and Test/Alarm Reset buttons simultaneously to toggle between Configuration and Operation mode. Press the Test/Alarm Reset button to toggle an option on or off.
Configuration · Power On Indicator

LED Option Power On Indicator
120/230V Nominal Input Voltage
ON (default) Nominal input voltage on low voltage models is 120V and on high voltage models is 230V; all other nominal input voltages are disabled.
OFF* 120/230V is disabled; one of the other input voltage options is selected. *This is the default for models that are factory-configured for 100V or 208V (see the rating on the UPS rear panel).
110/220V Nominal Input Voltage
ON Selecting this option changes the nominal input voltage on low voltage models to 110V and to 220V for high voltage models.
OFF (default) 110/220V is disabled; one of the other input voltage options is selected.
127/240V Nominal Input Voltage
ON Selecting this option changes the nominal input voltage on low voltage models to 127V and to 240V for high voltage models.
OFF (default) 127/240V is disabled; one of the other input voltage options is selected.
120/230V Extended Voltage Mode
ON The UPS accepts an input voltage within -35% to +20% of 120V or 230V nominal input voltage before switching to battery.
OFF (default) The UPS accepts an input voltage within -30% to +20% of 120V or 230V nominal input voltage before switching to battery.
Site Wiring Fault Alarm
ON (default) Alarm sounds when the polarity of the outlet is reversed or the ground connection is missing; have a qualified electrician repair the outlet wiring.
OFF* Alarm DOES NOT sound when the polarity of the outlet is reversed or the ground connection is missing. *Site Wiring Fault is not available for 100V or 208V models; OFF is the default.
Low Battery Alarm ON (default) Alarm sounds approximately 3 minutes before battery shutdown.
OFF Alarm sounds approximately 5 minutes before battery shutdown.
Configuration · Explanation

Explanation Power On Indicator Option LED
Shutdown Delay ON (default) 5-second delay before unconditional shutdown after the UPS receives a signal from a computer via the communication port.
OFF 180-second delay before unconditional shutdown after the UPS receives a signal from a computer via the communication port. When this LED is not enabled, the user can also create a new delay time by reconfiguring the communication port. See “Communication Port Configurations” on page 25 for more information.
AC Input Failure ON (default) Alarm sounds when there is an AC input failure.
OFF Alarm DOES NOT sound when there is an AC input failure.
Sleep Mode ON (default) When the UPS is on battery and the load is drawing less than 5% of the current, the UPS shuts down the load. This feature conserves battery power.
OFF Select this option if you want a load less than 5% of the current to be protected by battery power.
100/208V Nominal Input Voltage
ON* Selecting this option changes the nominal input voltage on low voltage models to 100V and to 208V on high voltage models. *This is the default for factory-configured 100V or 208V models (see the rating label on the UPS rear panel).
OFF (default) 100/208V is disabled; one of the other input voltage options is selected.
100/208V Extended Voltage Mode
ON Select this option to extend the input voltage within -25% to +25% of 100V or 208V nominal input voltage before switching to battery (available on units that were specifically ordered with this option).
OFF (default) The UPS accepts an input voltage within -20% to +20% of 100V or 208V nominal input voltage before switching to battery.
Reset Defaults ON (default) All factory-set defaults are active.
OFF One or more factory-set defaults have been changed.
Configuration

This section explains how to:
: Care for the UPS and batteries
: Replace the batteries
: Test new batteries
: Recycle used batteries
For the best preventive maintenance, keep the area around the UPS clean and dust-free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of 25°C (77°F).
Storing the UPS and Batteries If you store the UPS for a long period, recharge the battery every 12 months by plugging the UPS into a power outlet. The UPS charges to 90% in approximately 4 hours. However, it is recommended that the UPS charge for 24 hours after long storage.
When the Battery Service indicator illuminates, the batteries may need replacing (see Figure 10 on page 12). Conduct a self-test by pressing the
button. If the indicator stays on, contact your service representative to order new batteries.

The hot-swappable battery feature allows you to replace the UPS batteries easily without turning the UPS off or disconnecting the load.
If you prefer to remove input power to change the battery: 1) Press the Off button and then unplug the UPS; 2) Wait 60 seconds while the internal processor shuts down before you disconnect the battery.
Consider all warnings, cautions, and notes before replacing batteries.
current. The following precautions should be observed: 1) Remove watches, rings, or other metal objects; 2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of batteries.
: ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or
connectors. Attempting to alter wiring can cause injury.
UPS Maintenance

How to Replace External Batteries Use the following steps to replace external batteries:

UPS Maintenance · Battery Cabinet UPS · Battery Connector

How to Replace Internal Batteries Use the following steps to replace internal batteries:
UPS Maintenance


Red Connector from UPS
Testing New Batteries
Press and hold the button for three seconds to initiate a self-test. After the test is finished, the red Battery Service indicator should turn off and the Battery Charge LEDs should show a charge. If the Battery Service indicator stays on, check the battery connections. See the troubleshooting guide on page 33 or call your service representative if the problem persists.

Contact your local recycling or hazardous waste center for information on proper disposal of the used battery.
disposal of batteries is required. Refer to your local codes for disposal requirements.
: Do not open or mutilate the battery or batteries. Released electrolyte is harmful
to the skin and eyes. It may be toxic.
UPS Maintenance

C H A P T E R 6 ADDITIONAL UPS FEATURES
This section describes:
: UPS communication capabilities
: The Network Transient Protector
: Load segments
: Option modules
To establish communication between the UPS and a computer, connect your computer to the UPS communication port using the supplied communication cable.
When the communication cable is installed, power management software can exchange data with the UPS. The software polls the UPS for detailed information on the status of the power environment. If a power emergency occurs, the software initiates the saving of all data and an orderly shutdown of the equipment.
Communication Indicator When the UPS receives a command from the computer to establish communication, the Communication indicator on the UPS front panel illuminates (see Figure 10 on page 12). When data is transferring, the Communication indicator flashes.

Pin Out As shown in Table 2, Pins 1 and 2 operate in two modes: Basic Alarms mode and Serial Data mode. Basic Alarms mode has AC fail alarm and output shutdown. Serial Data mode is UPS Code II compliant.
The system always starts in Basic Alarms mode. When serial data is received at Pin 1, the function of Pin 1 and Pin 2 changes to Serial Data mode.
If serial data has not been received before going to battery power, serial communication is disabled until AC input power returns.
6 7 8 9
1 2 3 4 5
Table 2. Communication Port Configuration
Pin Signal Type Function
1 Basic Alarms Mode - Input: RS-232 level high (+12V) pulse 4 to 5 seconds Remote UPS off. In absence of AC power, output is turned off until normal AC power returns
Serial Data Mode - Input: RS-232 data RS-232 serial communication input. 1200 baud, 8 bits, No parity, 1 stop bit, 1 start bit
2 Basic Alarms Mode - Output: RS-232 level high (+12V) AC Input failure
Serial Data Mode - Output: RS-232 data RS-232 serial communication output. 1200 baud, 8 bits, No parity, 1 stop bit, 1 start bit
4 Signal Common Signal Common
7 Input: Relay contact or RS-232 level Remote Emergency Power-Off: UPS total output can be kept off with low signal or closing relay contact
9 Chassis Connection to chassis
Additional UPS Features

The Network Transient Protector, shown in Figure 18, is located on the rear panel and has jacks labeled IN and OUT. This feature accommodates a single RJ-45 (10BaseT) network connector.
Low voltage models can also accommodate an RJ-11 telephone connector that provides protection for modems, fax machines, or other telecommunications equipment. As with most modem equipment, it is not advisable to use this jack in digital PBX (Private Branch Exchange) environments.
Connect the input connector of the equipment you are protecting to the jack labeled IN. Connect the output connector to the jack labeled OUT.
OUT
IN
NETWORK TRANSIENT PROTECTOR
Figure 18. Network Transient Protector
Load Segments
Load segments are sets of receptacles that can be turned on individually using power management software. For example, during a power outage, you can keep key pieces of equipment running while you turn off other equipment. This feature allows you to save battery power. See your power management software manual for details.
Option modules help your UPS communicate in a variety of networking environments and are installed in the UPS option slot. See the manual that accompanies each module for more information, or contact your sales representative.
Additional UPS Features

Additional UPS Features

This section provides the following specifications for the Powerware 5119 models:
: Electrical input and output
: Weights and dimensions
: Environmental and safety
: Indicators and controls
: Battery
120V Models 230V Models
UPS Models PW5119 1000 PW5119 1500 PW5119 2000 PW5119 2400 PW5119 3000
PW5119 1000i PW5119 1500i PW5119 2000i PW5119 2400i PW5119 3000i
120V Models 230V Models
Nominal Voltage 120V default; 100, 110, 120, 127V selectable 230V default; 208, 220, 230, 240V selectable
Voltage Range -30% to +20% at full load for nominal voltage; -35% to +20% user-selectable, extended range
Nominal Frequency 60 Hz; 50/60 if 100V or 110V selected 50/60 Hz
Noise Filtering MOVs and line filter for normal and common mode noise
Connections 1000-1500 VA: 6-ft. power cord with 5-15 plug 2000 VA: 6-ft. power cord with 5-20 plug 2400-3000 VA: 6-ft. power cord with 5-30 plug

120V Models 230V Models
Power Levels (rated at nominal inputs)
PW5119 1000: 1000 VA, 670W PW5119 1500: 1440 VA, 960W PW5119 2000: 1920 VA, 1400W PW5119 2400: 2400 VA, 1600W PW5119 3000: 2880 VA, 2250W
PW5119 1000i: 1000 VA, 670W PW5119 1500i: 1500 VA, 960W PW5119 2000i: 2000 VA, 1400W PW5119 2400i: 2300 VA, 1600W PW5119 3000i: 3000 VA, 2250W
Regulation Online -10% to +6% of nominal voltage (-15% to +10% using extended range)
Regulation On-Battery (Nominal Voltage ±5%)
120V for 110, 120, 127V; 100V for 100V 230V for 220, 230, 240V; 208V for 208V
Voltage Waveform Sine wave;
120V Models 230V Models
7 x 8.8 x 17.1 inches (17.8 x 22.3 x 43.4 cm)
UPS Weights 1000 VA: 43 lb (20 kg) 1500 VA: 57 lb (26 kg) 2000 VA: 32 lb (15 kg) 2400 VA: 36 lb (16 kg) 3000 VA: 41 lb (19 kg)
7 x 8.8 x 17.1 inches (17.8 x 22.3 x 43.4 cm)
Specifications · UPS Dimensions (WxHxD) · Battery Dimensions (WxHxD)

120V Models 230V Models
Operating Temperature 0°C to 40°C (32°F to 104°F); UL tested 25°C (77°F)
Storage Temperature -20°C to 60°C (-4°F to 140°F)
Relative Humidity 5-95% noncondensing
Operating Altitude Up to 3,000 meters above sea level
Audible Noise Less than 45 dBA typical
Surge Suppression IEEE 587/ANSI C62.41 Category B
Safety Conformance UL 1778; CAN/CSA C22.2, No. 107.1 UL 1778; CAN/CSA C22.2, No. 107.1;
EN 50091-1 and IEC 60950
Safety Markings UL, CSA UL, CSA, CE
Table 8. Indicators and Controls
Serial Communication Intelligent serial communication to provide alarms with history, measured parameters, self-test, and many other features; contact your authorized dealer for UPS/computer communication software options
Interface Ergonomic Indicators: Wiring Fault, Battery Service, Communication, Operation, System Normal Bar Graphs: Input Level, Battery Charge Level, % Load
Contact Closures AC Input Failure, Low Battery
120V Models 230V Models
Configuration 1000-1500 VA: internal batteries 2000-3000 VA: external PW5119 1048BP 1000-1500 VA: internal batteries 2000-3000 VA: external PW5119 1748BP
Voltage 24 Vdc for internal; 48 Vdc for external
Type Sealed, maintenance-free, valve-regulated, lead-acid
Charging Advanced charging for faster recovery; approximately 4 hours to 90% usable capacity at nominal line and no supplementary power supply load
Monitoring Advanced monitoring for earlier failure detection and warning
Specifications

Load (VA) 1000 Model 1500 Model 2000 Model 2400 Model 3000 Model
300 49 79 92 162 162
500 21 38 55 97 97
700 14 17 34 62 62
1000 8 6 24 43 43
1500 8 13 23 23
2000 8 16 16
Specifications · 2400 13 13

This section explains:
: UPS alarms and conditions
: How to silence an alarm
: Service and support
The UPS has an audible alarm feature to alert you of potential power problems. Use Table 11 to determine and resolve the UPS alarms and conditions.
Silencing an Audible Alarm To silence the alarm for an existing fault, press the button. If UPS status changes, the alarm beeps, overriding the previous alarm silencing.
Alarm or Condition Possible Cause Action
The Power On indicator is not on; the UPS will not
Push the circuit breaker button or replace the fuse (see “UPS Rear Panels” on page 7). start. The line cord is not connected. Connect the line cord.
A circuit breaker or an input fuse on the rear panel is open.
The wall outlet is dead. Have a qualified electrician test and repair the outlet.
The UPS may be unable to recognize a 100V, 50-Hz wall outlet.
See “Specifications” on page 29 to verify that your UPS accepts 100V nominal input. Unplug the UPS. Start the UPS on battery and reconfigure the nominal input voltage for 100V (see ”Configuration Mode” on page 15). Turn off the UPS for 30 seconds. Plug the UPS into the outlet.
A battery fuse or circuit breaker is open.
Contact your service representative.
The UPS switches frequently between battery and AC input.
Input voltage in your area differs from the UPS nominal.
Change the UPS input voltage to match your local voltage; see “Configuration Mode” on page 15.

Action Possible Cause Alarm or Condition
The Low Battery Alarm does not give enough warning.
The batteries need charging or service.
Plug the UPS into a wall outlet for 24 hours to charge the battery. After charging the battery, press and hold the
button for 3 seconds; then check the Battery Service indicator. If the Battery Service indicator is still on, see “UPS Maintenance” on page 19 to replace the battery.
The Low Battery Alarm is not set appropriately.
Change the alarm setting. See “Configuration Mode” on page 15.
AC input high The AC input voltage is too high. The UPS is running on battery power.
Correct the input voltage, if possible. The UPS continues to operate on battery until the battery is completely discharged. If the condition persists, the input voltage in your area may differ from the UPS nominal. Change the UPS input voltage to match your local voltage (see “Configuration Mode” on page 15).
The line voltage is too low. The UPS is running on battery power.
Correct the input voltage, if possible. The UPS continues to operate on battery until the battery is completely discharged. If the condition persists, the input voltage in your area may differ from the UPS nominal. Change the UPS input voltage to match your local voltage (see “Configuration Mode” on page 15).
Ground wire connection does not exist in the wall outlet or the line and neutral wires are reversed in the wall outlet.
Have a qualified electrician correct the wiring. To disable this alarm, see “Configuration Mode” on page 15.
The battery is running low. 3 to 5 minutes or less of battery power remains (depending on load and battery charge). Prepare for a shutdown. Save your work and turn off your equipment.

Action Possible Cause Alarm or Condition
The battery may be fully discharged because of a long storage period or failing because of age.
Plug the UPS into a wall outlet for 24 hours to charge the battery. After charging the battery, press and hold the
button for 3 seconds; then check the Battery Service indicator. If the Battery Service indicator is still on, see “UPS Maintenance” on page 19 to replace the battery.
The battery is not connected correctly.
Check connections or call your service representative.
The DC voltage is high; the alarm does not clear.
Contact your service representative.
Overload Power requirements exceed UPS capacity or the load is defective.
Remove some of the equipment from the UPS. You may need to obtain a larger capacity UPS.
If you have any questions or problems with the UPS, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative.
In the United States 1-800-365-4892 In Canada 1-800-461-9166 All other countries 1-919-870-3149
Please have the following information ready when you call the Help Desk:
: Model number
: Serial number
: Version number (if available)
: Date of failure or problem
: Symptoms of failure or problem
: Customer return address and contact information
Troubleshooting · Battery Service · Battery Service

If repair is required, you will be given a Returned Material Authorization (RMA) Number. This number must appear on the outside of the package and on the Bill Of Lading (if applicable). Use the original packaging or request packaging from the Help Desk or distributor. Units damaged in shipment as a result of improper packaging are not covered under warranty. A replacement or repair unit will be shipped, freight prepaid for all warrantied units.
Troubleshooting