NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES-003.
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
Some configurations are classified under IEC 62040-2 as “Class-A UPS for Unrestricted Sales Distribution.” For these configurations, the following applies:

Powerware, ABM, and Powerware Hot Sync are registered trademarks and X-Slot and LanSafe are trademarks of Eaton Power Quality Corporation. Greenlee is a registered trademark of Greenlee Textron.
ECopyright 2004–2006 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.

Units that are labeled with a CE mark comply with the following harmonized standards and EU directives:
S EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits 93/68/EEC, Amending Directive 73/23/EEC 89/336/EEC, Council Directive relating to electromagnetic compatibility 92/31/EEC, Amending Directive 89/336/EEC relating to EMC
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC Declaration of Conformity, contact:
Eaton Power Quality Oy Koskelontie 13 FIN-02920 Espoo Finland Phone: +358-9-452 661 Fax: +358-9-452 665 68

The following are examples of symbols used on the UPS or accessories to alert you to important information:
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed.
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead-acid batteries and must be disposed of properly. For more information, contact your local recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.


A parallel system with up to three uninterruptible power supplies (UPSs) can be installed to provide a parallel capacity and/or redundant system. This load sharing system provides more capacity than a single UPS and can provide backup, depending on the load and configuration. In addition, when one UPS is taken out of service for maintenance or is not operating properly, a redundant UPS continues to supply uninterrupted power to the critical load. A parallel Powerware® Hot Sync® Contoller Area Network (CAN) Bridge Card provides connectivity for system metering and operational mode control. The parallel system consists of two or three UPSs, each with a CAN Bridge Card and a parallel tie cabinet.
Figure 1 shows the Powerware 9155 UPS and an optional Extended Battery Module (EBM).
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 1

EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 2

IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference.
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
WARNING S This UPS contains its own energy source (batteries). The UPS output may carry live voltage even when the UPS is not connected to an AC supply. S To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95% maximum). S To reduce the risk of fire, connect only to a circuit provided with 100 amperes maximum branch circuit overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70. S Output overcurrent protection and disconnect switch must be provided by others.
CAUTION S Batteries can present a risk of electrical shock or burn from high short circuit current. Observe proper precautions. Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions. Keep unauthorized personnel away from batteries. S Proper disposal of batteries is required. Refer to your local codes for disposal requirements. S Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 3

EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 6

This chapter describes:
S Floor loading and clearances
S Unloading the cabinet(s)
The instructions are intended for the chief operator/system supervisor, electrical consultants, and installation electricians. Local regulations and electrical code must be followed during the UPS installation.
If any equipment has been damaged during shipment, keep the shipping and packing materials for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of receipt of the equipment; 2) Send a copy of the damage claim within 15 days to your service representative.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 7
S Equipment inspection

Floor Loading
When planning the installation, consider the UPS weight for floor loading. The strength of the installation surface must be adequate for point and distributed loadings. The approximate weights are shown in the following table.
Standard Model Floor Loadings (2-High/3-High Cabinets)
Powerware 9155 Maximum Weight (lb)
Distributed Loading (lb/ft2)
2-High UPS 352 88 166
3-High UPS 590 148 278
3-High UPS with Isolation Transformer
2-High EBM 480 120 226
3-High EBM 710 178 335
The following clearances are recommended for the Powerware 9155 UPS:
From Front of Cabinet 36” (91.4 cm) working space
From Back of Cabinet 6” (15.2 cm)
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 8
Point Loading · (lb/in2) · 558 140 263

Unloading the Cabinet(s)
The following tools are required for unloading the cabinet(s):
S 15 mm wrench or socket
S 7 mm nutdriver or socket
The UPS and Extended Battery Module (EBM) are heavy (see page 8). Unloading the cabinets requires at least two people to safely remove the cabinets from the pallet.
To remove the UPS or EBM from the shipping pallet:

EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 9

Press and release the handle latch at the bottom of the cover and then lift the cover up and off the cabinet.
If needed, adjust the leveling feet to release the bracket.

Hang the top edge of the cover on the cabinet first, then lower the bottom edge and snap into place.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 10
M10 Bolts · M10 Bolts · M4 Screws

If needed, adjust the leveling feet so that the cabinet will roll.


EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 11

EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 12

The Powerware 9155 has the following power connections:
S 2-phase (L1 and L2), neutral, and ground connection for rectifier/bypass input
S 2-phase (L1 and L2), neutral, and ground connection for load output
The nominal input/output voltages are:
S 100/200, 110/220, or 120/240 Vac with 180° phase displacement
S 120/208 or 127/220 Vac with 120° phase displacement
Output overcurrent protection and disconnect switch must be provided by others.
Figure 14 on page 22 shows a oneline diagram of the parallel UPS system.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 13

WARNING
Only qualified service personnel (such as a licensed electrician) should perform the UPS installation and initial startup. Risk of electrical shock.
To hardwire the parallel system:
Compare the circuit breaker ratings and wire sizes to the ones in the following wiring table:
UPS Capacity Input Circuit Breaker Rating Minimum Wire Size*
8 kVA 60A 4 AWG (21.2 mm2)
10 kVA 80A 3 AWG (26.7 mm2)
12 kVA 100A 2 AWG (33.6 mm2)
15 kVA 100A 2 AWG (33.6 mm2)
*Use only 75°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16. Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long service runs. Follow local requirements.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 14



EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 15
Internal Cover


EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 16


UPS Wiring Access Cover
See Table 2 for specifications and Figure 10 for a detailed view of the UPS terminal block.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 17
Battery Connector · Conduit Landing

Input Ground TB1-1 8 AWG p
L1 TB1-3 100A 3 AWG 25 lb in 2” access hole for Neutral TB1-4 3 AWG 25 lb in (2.83 Nm)
2 access hole for 1-1/2” conduit
Output L1 TB1-6 3 AWG p
Neutral TB1-7 3 AWG 25 lb in 2” access hole for L2 TB1-8 3 AWG 25 lb in (2.83 Nm)
2 access hole for 1-1/2” conduit
Ground TB1-9 8 AWG
*Use only 75°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16.
1 2 3 4 5 6 7 8 9
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 18


EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 19
Ground


EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 20


EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 21
Line 1

Figure 14. Parallel Wiring Diagram
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 22

This section describes the Powerware Hot Sync CAN Bridge Card.
For other options, such as additional X-Slott cards, Powerware LanSafet Power Management Software, remote emergency power-off (REPO), relay output contacts, or programmable signal inputs, refer to the Powerware 9155 UPS (8–15 kVA) User’s Guide.
Figure 15 shows the location of the communication options and control terminals on the UPS.

X-Slot Communication Bay #1
X-Slot Communication Bay #2
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 23

Powerware Hot Sync CAN Bridge Card
The Powerware Hot Sync CAN Bridge Card, shown in Figure 16, can be installed to provide connectivity for operational mode control and metering of a parallel system at any UPS in the system.

To install the Powerware Hot Sync CAN Bridge Card:
Press and release the handle latch at the bottom of each cover and then lift the cover up and off the cabinet (see Figure 17).

EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 24

Otherwise, remove the X-Slot communication bay cover and retain the screws.
S If only two UPSs are paralleled, then set both cards to Pins 1 and 2.
S For three paralleled UPSs, set the cards of the first and last UPS to Pins 1 and 2; set the card for the middle UPS to Pins 2 and 3.
Jumper J7 - Pins 1 and 2 Jumper J7 - Pins 2 and 3

EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 25

S Connect SHIELD Pin 10 on all cards together.
S Connect CAN H Pin 9 and CAN L Pin 8 (twisted pair) on all cards together.
S Connect COM Pin 4 and NC Pin 3 (twisted pair) on all cards together.
S Connect COM Pin 4 to Signal Input 2 Pin 1 on each UPS.
S Connect NC Pin 3 to Signal Input 2 Pin 2 on each UPS.
If polarity or wiring is not correct, the parallel system does not operate normally. For example, when shutting down one UPS, the remaining UPS transfers the load to bypass instead of supporting the load. Verify all CAN Bridge Card wiring is correct for proper operation.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 26




EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 27

With wire cutters, cut either side of the tab and twist down to remove the tab (see Figure 20).

EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 28

Hang the top edge of the cover on the cabinet first, then lower the bottom edge and snap into place. Be sure the cables fit in the access holes in the covers.

EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 29

EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 30

To stabilize the cabinet(s):
S For one cabinet, see Figure 23.
S For two cabinets, see Figure 24.
S For three cabinets, see Figure 25.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 31

S “Extended Battery Module Installation” on page 35 to install optional EBMs.
S “Operation” on page 39 to start up the parallel UPS system.


EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 32




EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 33

EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 34

To install the optional EBM:
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 35


EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 36
EBM Cable

Press and release the handle latch at the bottom of the cover and then lift the cover up and off the cabinet.
Hang the top edge of the cover on the cabinet first, then lower the bottom edge and snap into place.

EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 37

EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 38

This chapter contains information on how to use the Powerware 9155, including front panel operation, UPS startup and shutdown, and configuring the UPS for Extended Battery Modules (EBMs).
The UPS has a four-button graphical LCD with backlight. It provides useful information about the UPS itself, load status, events, measurements, and settings (see Figure 28).
Power On Indicator (green) On Battery Indicator (yellow)
Bypass Indicator (yellow) Alarm Indicator (red)
Control Buttons for the LCD Menu Options
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 39

The following table shows the indicator status and description.
On The UPS is operating normally.
Green Flashing S The UPS is starting up or is shut down and waiting for power to return. S A new information message is active. S Bypass is not available.
Off The UPS is turned off and will not turn on automatically.
On The UPS is in Battery mode.
On The UPS is in Bypass mode.
On The UPS has an active alarm.
Flashing There is a new UPS alarm condition. See “Troubleshooting” on page 55 for additional information.
Press and hold the first button on the left for approximately five seconds to select the language menu. This action is possible from any LCD menu screen.
As the default or after 15 minutes of inactivity, the LCD displays the selectable startup screen. The default is the Eaton Powerware logo and can be changed to the Mimic screen in the User Settings menu.
The backlit LCD automatically dims after a long period of inactivity. Press any button to restore the screen.
Use the two middle buttons ( and ) to scroll through the menu structure. Press the button to enter a submenu. Press the button to select an option. Press the ESC button to cancel or return to the previous menu.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 40

The following table shows the basic menu structure.
Main Menu Submenu Display Information or Menu Function
UPS Status System normal / Battery floating UPS in Parallel mode / Parallel Unit Number x / Units on CAN Bus / Units on load
Event Log Displays up to 100 events and alarms
Measurements Parallel System Voltage [by unit] / Voltage [Parallel total] / Output Voltage: L-N / Output Voltage L-L / Output Current / Output Frequency / Output Power
Output L-N and L-L / Current / Frequency / Power
Battery Voltage / Current / Runtime
Input L-N and L-L / Current / Frequency
Bypass L-N and L-L / Frequency
Control Go to Bypass Mode Transfers the UPS system to internal Bypass mode When this command is active, the option changes to Go to Normal Mode.
Start Battery Test Initiates a battery test
Display Test Four different selectable tests for the front panel functions: the LEDs cycle through, the alarm beep sounds, the backlight turns off and on, and the pixels scroll through to test the LCD.
Settings User Settings See Table 4 for detail.
Service Settings This screen is password-protected.
Identification UPS Type / Part Number / Serial Number / Firmware / Display / CAN Bridge
Turn UPS ON/OFF ON and OFF Options UPS Off / System On / System Off
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 41

User Settings
The following table displays the options that can be changed by the user.
Table 4. User Settings
Description Available Settings Default Setting
Set Date and Time Set Month Date: mm/dd/yyyy Time: 24:00
01/01/2003 00:00
Display Contrast Adjust contrast with up/down arrow buttons Moderate
Relay Config Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or [X-Slot 2-1/2/3/4] Setup: [empty] [On Battery] [summary alarm] [On Bypass] [UPS ok] [custom]
Alarm 1: empty X-Slots (1 or 2) #1: UPS ok #2: On Bypass #3: Summary Alarm #4: On Battery
Signal Inputs [empty] [Logic] Signal Input must be wired to the CAN Bridge Card (see Figure 19 on page 27). For more information, refer to “Programmable Signal Inputs” in the Powerware 9155 UPS (8–15 kVA) User’s Guide.
Parallel Operation Settings Parallel Unit Number: [Single Unit] [Unit #1] [Unit #2] [Unit #3]
Redundant Mode Capacity Mode
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 42

Table 4. User Settings (continued)
Default Setting Available Settings Description
Modem Config Modem Installation
Set Modem Call Events Event #0 Call modem: no
Set Modem Init String ATZ0
Set Modem Call Command None
Set Modem Communication Password None
Start Screen Eaton Powerware logo Mimic screen
User Password Enabled/Disabled If Enabled is selected, the password is USER.
Audible Alarms Normal Sound/Disabled Normal Sound
Battery Charging ABM cycling/constant ABM cycling
Automatic Battery Tests Enabled/Disabled Enabled automatically runs the battery test once a month.
Full Power Battery Test Enabled/Disabled Enabled
Number of Battery Strings 0 through 22 (see “Configuring the UPS for EBMs” on page 49)
2 strings for UPS-32 models 4 strings for UPS-64 models
Battery Capacity 1 through 65535 watts per cell 34 W/cell
Battery Low Alarm Level 1.750 through 1.950 volts per cell 1.880 V/cell
Set Nominal Output Voltage 120V/240V 120V/208V 110V/220V 100V/200V 127V/220V
Bypass Voltage High Limit +1 through +20% (1% increments) 120V +10%
Bypass Voltage Low Limit -1 through -20% (1% increments) 120V -15%
Nominal Output Frequency 50 Hz or 60 Hz 60 Hz
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 43

Table 4. User Settings (continued)
Default Setting Available Settings Description
Synchronization Window ±0.5 through ±3.0 Hz (0.1 Hz increments)
±2.0 Hz
Unsynchronized Transfer to Bypass Allowed/Not Allowed Not Allowed
Output Frequency Slew Rate 0.1 though 5 hertz per second (0.1 Hz increments)
0.5 Hz/s
Usage of Bypass Enabled/Disabled Enabled
Transfer to Bypass When Overload After a delay/Immediately After a delay
Automatic Start Delay -1 through 32767 seconds (-1 means disabled)
Control Commands from X-Slot1 Allowed/Disabled Allowed
Control Commands from X-Slot2/Serv Allowed/Disabled Allowed
X-Slot Signal Input Activation Delay 0 through 65 seconds 5s
Input signal delayed shutdown delay 1 through 65535 seconds 120s
Site Wiring Fault Notice Enabled/Disabled Enabled
Reset Custom Event Settings 0 through 32 Total: 0/32
Auto Output Configuration Enabled/Disabled Enabled for initial startup Disabled after initial startup
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 44
0s

Parallel UPS Startup
WARNING
Only qualified service personnel (such as a licensed electrician) should perform the UPS installation and initial startup. Risk of electrical shock.
Verify that UPS installation has been carried out correctly and the UPS ground has been connected.
To start up the parallel system:
The indicator flashes on each UPS.
The indicator stops flashing on each UPS.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 45

S Press any button on the front panel display to activate the menu options.
S Using the button, scroll to the Settings menu, and then press the button twice to select the User Settings menu.
S Using the button, scroll to the Parallel Operation Settings option and press the button.
S Press the button to select the Parallel Unit Number option.
S Use the button to scroll the Unit number to identify the UPS number of the parallel system (Unit #1, Unit #2, or Unit #3).
S Press the button to save the setting.
S Use the button to scroll to the Parallel Operation Mode option and press the button to enter the menu.
S Use the button to scroll the desired option (either Redundant Mode or Capacity Mode).
S Press the button to save the setting.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 46

S Press the button on the front panel display and then press the button to select the TURN UPS ON/OFF menu.
S Press the button to select the UPS Off option; press the button.
S Confirm the selection. Press and hold the button for three seconds, until the UPS stops beeping.
S Switch the UPS battery circuit breaker to the OFF position.
The UPS is disconnected from the batteries and is on logic power only.
If the indicator is flashing, do not proceed until all alarms are clear. Check the UPS status from the front panel to view the active alarms. Correct the alarms and restart if necessary.
If all UPSs appear in the list, press the ESC button until the Eaton Powerware logo appears.
If any UPS is missing, verify the Powerware Hot Sync CAN Bridge Card connections and recheck the status from the UPS front panel.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 47

The UPS goes to Bypass mode for five seconds, and then the
indicator illuminates. Each UPS should be in Normal mode.
S Using the button, scroll to the Settings menu and then press the button twice to select the User Settings menu.
S Using the button, scroll to the Parallel Operation Settings option and press the button.
S Using the button, scroll to the Start Auto Calibration option and press the button to select the option. Press and hold the button for a second to begin the process.
S Using the button, scroll to the Measurements menu and press the button twice to select the Parallel System menu.
S Select and view the voltage meter options.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 48

Configuring the UPS for EBMs
To ensure maximum battery runtime, configure the UPS for the correct number of EBMs:
All 2-High UPS and EBM Cabinets* Number of Strings
UPS + 2 EBMs 10
UPS + 3 EBMs 14
UPS + 4 EBMs 18
All 3-High UPS and EBM Cabinets* Number of Strings
UPS + 2 EBMs 16
UPS + 3 EBMs 22
*UPS-32 models contain 2 strings; EBM-64 models contain 4 strings. UPS-64 models contain 4 strings; EBM-96 models contain 6 strings.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 49

Parallel System Shutdown
To remove power to the parallel UPS system output:
The UPS removes power to the parallel UPS system output.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 50

Individual UPS Shutdown
To shut down a single UPS in the parallel system:
The input contactor opens.
The UPS is disconnected from the batteries and is on logic power only.
If you are shutting down all the UPSs in a parallel system, repeat Steps 2 through 6 for each UPS then remove utility power.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 51

Restarting the Parallel System
To restart the parallel system:
The indicator flashes on each UPS.
The indicator stops flashing on each UPS.
If the indicator is flashing, do not proceed until all alarms are clear. Check the UPS status from the front panel to view the active alarms. Correct the alarms and restart if necessary.
The UPS goes to Bypass mode for five seconds, and then the
indicator illuminates. Each UPS should be in Normal mode.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 52

To switch the parallel UPS to maintenance bypass from Normal mode:
S Using the button on the front panel display, scroll to the Control menu option and press the button.
S Press the button to select the Go to Bypass Mode option.
The and indicators illuminate, indicating the UPS system is operating in Bypass mode.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 53

To return to Normal mode from maintenance bypass:
In a parallel capacity system (2+0 or 2+1), apply utility to the minimum number of UPSs required for capacity.
S Using the button on the front panel display, scroll to the Control menu option and press the button.
S Press the button to select the Go to Bypass Mode option.
The and indicators illuminate, indicating the UPS system is operating in Bypass mode.
S Press the button to select the Go to Normal Mode option.
S Each UPS should go to Normal mode.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 54

The Powerware 9155 is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are preventive alarms intended to alert the user. Use the following troubleshooting chart to determine the UPS alarm condition.
The following table describes typical alarms and conditions; check the Event Log through the control panel for a list of active alarms. If an alarm appears with a service code, please contact the Help Desk (see page 58).
Alarm or Condition Possible Cause Action
A utility failure has occurred and the UPS is in Battery mode.
The UPS is powering the equipment with battery power. Prepare your equipment for shutdown.
LED is on. 1 beep every second.
The battery is running low. Five minutes or less of battery power remains (depending on load configuration and battery charge). Save your work and turn off your equipment. When utility power is restored, the UPS restarts automatically, provides power to the load, and charges the battery.
LED is on. Continuous beep for 10 seconds.
The UPS does not recognize the internal batteries.
Verify the battery circuit breaker is in the ON position. If the condition persists, contact your service representative.
LED is on. 1 beep every second.
Power requirements exceed the UPS capacity (greater than 100% of nominal).
Remove some of the equipment from the UPS. The UPS continues to operate, but may switch to Bypass mode if the load increases. The alarm resets when the condition becomes inactive.
LED is on. 1 beep every second.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 55

Action Possible Cause Alarm or Condition
UPS internal temperature is too high or the fan has failed.
If you have an optional Maintenance Bypass Module or Power Distribution Module, turn the maintenance bypass switch to the SERVICE position. Otherwise, shut down the UPS. Clear vents and remove any heat sources. Allow the UPS to cool. Ensure the airflow around the UPS is not restricted. If the alarm disappears, turn the maintenance bypass switch back to the UPS position (or restart the UPS if you do not have a switch). If the condition persists, contact your service representative.
LED is on. 1 beep every second.
Battery test failed The batteries need service. Contact your service representative.
The UPS does not start. The main utility breaker is off. Verify that the main utility breaker is on.
If an optional isolation transformer is installed, the input circuit breaker is off.
Verify that the isolation transformer input circuit breaker is on.
The remote emergency power-off (REPO) switch is active or the REPO connector is missing.
Reset the REPO switch and restart the UPS. Verify that the REPO connector is present.
Power is not available at the UPS output receptacles.
The UPS is in Standby mode. Supply power to the connected equipment: Press any button on the front panel display to activate the menu options. Press the button on the front panel display and then press the button to select the TURN UPS ON/OFF menu. Press the button to select the System On option; press the button. Press and hold the button for three seconds, until the UPS stops beeping.
The UPS does not provide the expected backup time.
Apply utility power for 48 hours to charge the batteries. If the condition persists, contact your service representative. p
The batteries need charging or service.
Battery circuit breakers are in the OFF position.
Switch all battery circuit breakers to the ON position.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 56
Overtemperature

Action Possible Cause Alarm or Condition
Check Parallel Board The UPS is not recognizing another parallel unit.
From the UPS Status menu, select the Units on CAN Bus option and verify that all UPSs appear in the list. If any UPS is missing, verify the Powerware Hot Sync CAN Bridge Card connections and recheck the status from the UPS front panel. If all UPSs appear in the list, check the pull-chain wiring (see page 26). Set the system to internal Bypass mode (see page 53). If the condition persists, contact your service representative.
Abnormal output voltage at startup
The UPS breaker on the parallel tie cabinet was not switched to the ON position properly.
Shut down the UPS where the alarm is indicated. Switch the UPS breaker on the parallel tie cabinet to the ON position. Start up the UPS. Select the System On option through the front panel of the UPS that was turned off.
Selective Trip The Powerware Hot Sync CAN Bridge Card is not wired correctly.
Verify the CAN wiring (see page 26). Verify the pull-chain wiring (see page 26). If the condition persists, contact your service representative.
Before silencing an alarm, check the alarm condition and perform the applicable action to resolve the condition.
Press any button on the front panel display to silence the alarm. If the alarm status changes, the alarm beeps again, overriding the previous alarm silencing.
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 57

Service and Support
If you have any questions or problems with the UPS, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative.
United States: 1-800-843-9433 or 1-919-870-3028 Canada: 1-800-461-9166 ext 260 All other countries: Call your local service representative
Please have the following information ready when you call for service:
S Firmware version number
S Date of failure or problem
S Symptoms of failure or problem
S Customer return address and contact information
EATON Powerware® 9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com 58