User’s Guide

Omega TX82B — User’s Guide diagram (page 1)
Fig. 1 · User’s Guide
Omega TX82B — User’s Guide diagram (page 1)
Fig. 2 · User’s Guide

www.omega.com e-mail: [email protected]

TX82B Panel Mounted Current Loop Indicator

Page 2 of the Omega TX82B user manual — Servicing Europe:
Page 2 · click to enlarge
Page 2

OMEGAnet

® On-Line Service www.omega.com

Internet e-mail [email protected]

Servicing North America:

USA: One Omega Drive, P.O. Box 4047 ISO 9001 Certified Stamford CT 06907-0047 TEL: (203) 359-1660 FAX: (203) 359-7700 e-mail: info@omega.com Canada: 976 Bergar Laval (Quebec) H7L 5A1 TEL: (514) 856-6928 FAX: (514) 856-6886 e-mail: [email protected]

For immediate technical or application assistance:

USA and Canada: Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA® Customer Service: 1-800-622-2378 / 1-800-622-BEST® Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN®

Mexico and TEL(001)800-TC-OMEGA ® FAX: (001) 203-359-7807 Latin America: En Español: (001) 203-359-7803 e-mail: espanol@ omega.com

Servicing Europe:

Benelux: Postbus 8034, 1180 LA Amstelveen, The Netherlands TEL: +31 20 3472121 FAX: +31 20 6434643 Toll Free in Benelux: 0800 0993344 e-mail: [email protected] Czech Republic: Frystatska 184, 733 01 Karviná TEL: +420 59 6311899 FAX: +420 59 6311114 e-mail: [email protected] France: 11, rue Jacques Cartier, 78280 Guyancourt TEL: +33 1 61 37 29 00 FAX: +33 1 30 57 54 27 Toll Free in France: 0800 466 342 e-mail: [email protected] Germany/Austria: Daimlerstrasse 26, D-75392 Deckenpfronn, Germany TEL: +49 7056 9398-0 FAX: +49 7056 9398-29 Toll Free in Germany: 0800 639 7678 e-mail: [email protected] United Kingdom: One Omega Drive ISO 9002 Certified River Bend Technology Centre Northbank, Irlam Manchester M44 5BD United Kingdom TEL: +44 161 777 6611 FAX: +44 161 777 6622 Toll Free in England: 0800 488 488 e-mail: sales@omega.co.uk

® · ®

Page 3 of the Omega TX82B user manual — OMEGAnet
Page 3 · click to enlarge
Page 3
Page 3 of the Omega TX82B user manual — OMEGAnet
Page 4 of the Omega TX82B user manual — QTY DESCRIPTION
Page 4 · click to enlarge
Page 4

UNPACKING INSTRUCTIONS

Remove the Packing List and verify that you have received all equipment, including the following:

QTY DESCRIPTION

1 Current Loop Meter Indicator with all applicable connnectors attached.

1 Factory Setup Label

If you have any questions about the shipment, use the phone number for the Customer Service Department nearest you.

When you receive the shipment, inspect the container and equipment for signs of damage. Note any evidence of rough handling in transit. Immediately report any damage to the shipping agent.

The carrier will not honor damage claims unless all shipping material is saved for inspection. After examining and removing contents, save packing material and carton in the event reshipment is necessary.

1 Owner's Manual

Page 5 of the Omega TX82B user manual — 1.0 GENERAL INFORMATION
Page 5 · click to enlarge
Page 5

1.0 GENERAL INFORMATION

Model TX82B two-wire current-loop indicator accepts 1-5 mA, 4-20 mA, or 10-50 mA process signals and digitally displays the process variable in percentage or engineering units of such measurements as pressure, flow, temperature and level. No separate power supply or power connections are required, since the TX82B obtains operating power directly from the current loop with a voltage drop of less than 2.5 V. It can tolerate current overdrives up to 200 mA forward and 1000 mA reverse.

The compact TX82B circuit is mounted in a black polycarbonate case with the standard 1/8 DIN panel-mount bezel and a depth of less than 110 mm (4.33 in). Five 12.7 mm (0.5 in) high liquid crystal 7-segment digits are used to display ±1999 active counts plus one or two dummy right-hand zeros.

The TX82B displays from -1999 to 1999 counts with the option of one or two dummy right-hand “0” digits. Zero suppression or elevation capability exceeds full scale. Program jumpers are used to scale the readout for percentage or engineering-unit display. Both zero and span are fine-tuned with multiturn potentiometers accessible through the display board, requiring lens removal for readjustment.

When removed from its case, the TX82B can be programmed with gas-tight jumpers for three input ranges (1-5, 4-20 or 10-50 mA), four coarse zero ranges, four decimal-point locations and the dummy right-hand zeros. Two additional jumpers are provided to reverse the span slope so that increasing the input can cause a reading decrease; thus a 4-20 mA input can be programmed to produce a 2000 to -18000 reading when one dummy right-hand zero is also used.

Page 6 of the Omega TX82B user manual — 2.3 CONVERSION
Page 6 · click to enlarge
Page 6

2.0 SPECIFICATIONS

2.1 INPUT

Current 1-5 mA, 4-20 mA or 10-50 mA

Protection 200 mA max forward and 1000 mA max reverse

Voltage Drop 2.5 V max forward and 1.2 V max reverse

Span Range 100 to 2000 counts continuous adjustment with a multiturn potentiometer

Zero Range The multiturn zero potentiometer can displace the displayed reading by ±500 counts from the center of each of the four overlapping zero ranges, provided that the resultant is within the ±1999 count display capability.

Span Slope Positive or Negative

at 50/60 Hz 46 dB minimum

2.2 ACCURACY AT 25°C

Maximum error ±0.1% R ±1 count

Zero tempco ±0.1 ct/K typ, ±0.3 ct/K max

Span tempco ±0.005%S/K typ, ±0.015%S/K max

2.3 CONVERSION

Technique Dual-slope, average value with autozero correction

Polarity Determined automatically at the end of input integration period

Input integration period 100 milliseconds (nominal value)

Reading rate 2.5/second

Normal Mode Rejection

Page 7 of the Omega TX82B user manual — 2.6 MECHANICAL
Page 7 · click to enlarge
Page 7

2.4 DISPLAY

Color Black digits with white background

Symbols -1.8.8.8.0.0, 12.7 mm (0.5 in) height

Overrange Three least-significant digits blank

Extra digits One or two dummy right-hand zeros, jumper-selectable

Decimal points Four positions, jumper-selectable

Lifetime (to 2:1 contrast ratio) More than 30,000 hours

Temperature derating 2:1 for each 10°C above 60°C

Humidity derating 2:1 for each 10%RH above 60%RH

2.5 ENVIRONMENT

Standard operating temp 0 to 55°C

Extended operating temp option

(conformally coated) -40 to +85°C

Humidity To 95% at 40°C

Bezel cover option Splash-proof

2.6 MECHANICAL

Weight 170 g (6 oz)

Case material Black polycarbonate, 94V-0 flammability rating

Bezel (HxWxT) 48 x 96 x 7.67 mm

with mounting hardware Less than 110 mm

Panel cutout (HxW) 45 x 92 mm

Electrical connections 3-terminal screw clamp connector

Wire size 0.13 mm2 - 2.5 mm2 (AWG 26-14)

Show 4 more labels / short text on this page
Type 7-segment LCD · Polarity Minus sign · Case size · Depth behind bezel
Page 8 of the Omega TX82B user manual — 3.0 MECHANICAL ASSEMBLY AND INSTALLATION
Page 8 · click to enlarge
Page 8

3.0 MECHANICAL ASSEMBLY AND INSTALLATION

3.1 SAFETY CONSIDERATIONS

To ensure safe operation, follow the guidelines below:

VISUAL INSPECTION: Do not attempt to operate the instrument if damage is found.

SIGNAL WIRING: Insert the proper plus and minus signal wires into the plug-in screw-clamp connector terminals marked plus and minus. Ensure that the wires are securely clamped in the plug-in connector by rotating the screws in the plug–in connector clockwise but do not exceed a torque of .5 newton-meter (.37 pound-foot). Then plug the connector firmly into the socket located on the rear panel of the meter.

RAIN OR MOISTURE: Do not expose the instrument to condensing moisture.

3.2 INTRINSIC SAFETY PARAMETERS FOR FM (FACTORY MUTUAL) Certificate No. 2Y4A4.AX V max=12.5 V, I max=250 mA Intrinsically Safe for Class I, II and III, Division 1, Groups, A,B,C,D,E,F and G hazardous locations. Ci=8.6 µF Li=0 mH

Page 9 of the Omega TX82B user manual — CASE
Page 9 · click to enlarge
Page 9

3.3 INSTALLATION/REMOVAL The TX82B is housed in a 1/8 DIN case. The electronic circuitry can be installed or removed from the front and is attached to the case with two M4 screws through the rear panel.

1. Remove the two thumbnuts on the rear of the case.
2. Slide the sleeve off the case (see Figure 3-1 Exploded View).
3. Verify the panel cutout dimensions in Figure 3-2 Case Dimensions. Insert the case in the panel cutout from the front and slide the sleeve on from the rear. Install the two thumbnuts to secure the sleeve to the case.

Main Board Access:

1. Case must be removed from sleeve.

THUMBNUT

2. Remove lens from case.
3. Slide main board from front of case.

CASE

ID. LABEL

REAR PANEL

SLEEVE

MAIN BOARD DISPLAY BOARD

PANEL

THREADED STUD

CONFIGURATION LABEL (BACK SIDE OF DISPLAY BOARD)

FRONT LENS

J3 B REAR CONNECTOR (P3)

FOR SIGNAL INPUT

ELECTROSTATIC RISK DO NOT RUN OR CLEAN WITH SOLVENT

Figure 3-1 Exploded View (includes rear panel)

Panel Mounting

Page 10 of the Omega TX82B user manual — PANEL CUT-OUT
Page 10 · click to enlarge
Page 10

1.89 [48.0] 3.78 [96.0] 7.9 [0.31] MAX

CASE

3.50 [88.9]

4.15 [105.4] SLEEVE

TOP VIEW SIDE VIEW

PANEL THICKNESS:

0.25 [6.4] MAX 0.03 [0.8] MIN

[45.00 +0.61/-0.00] R

[1.5] 0.06

1.772 +.024/-.000

4 PLCS

3.622 +.032/-.000 [92.00 +0.81/-0.00]

PANEL CUT-OUT

Figure 3-2. DIN Case Dimensions

4.0 SIGNAL INPUT CONNECTIONS (P3) The signal input connections for all meters are made at connector P3 as follows (see Figure 3-1):

P3 Connection Signal 1 Signal Hi 2 Signal Lo 3 No Connection

Page 11 of the Omega TX82B user manual — 5.2 FIELD CONFIGURATION CHART
Page 11 · click to enlarge
Page 11

5.0 CONFIGURATION

The standard TX82B meter is factory-configured for an input of 4-20 mA to display 00.0 to 100.0. Field configuration for input current range, decimal point location, dummy right-hand zero digit, coarse zero range selection, and reverse span slope may be done by relocating internal push-on jumpers and adjusting the span and zero potentiometers. Refer to Figure 5-1 for the span and zero potentiometers and internal jumper locations.

5.1 STANDARD SETUP Unless the customized configuration option is specified, jumpers are factory-installed at S1-H, S2-C, S1-B, S1-C and the unit is calibrated for 4-20 mA = 00.0 to 100.0.

5.2 FIELD CONFIGURATION CHART

CONFIGURATIONJUMPER INSTALLATION 1.5 mA InputNone *4-20 mA InputS1-H 10-50 mA InputS1-J *Normal Span SlopeS1-B, S1-C Reverse Span SlopeS1-A, S1-D Decimal Point 1.999 (DP1)S2-E Decimal Point 19.99 (DP2)S2-D *Decimal Point 199.9 (DP3)S2-C Decimal Point 1999. (DP4)S2-B Decimal Point 19990. (DP5)S2-F Dummy Right-Hand Zero (DRHZ)S2-A Dummy Right-Hand Zeroes (2DRHZ)S2-G, S2-H, S2-J, S2-A Zero Range -2510 to -1420 (ZR1)S1-G Zero Range -1580 to -420 (ZR2)S1-F *Zero Range -470 to +850 (ZR3)None Zero Range +760 to +2000 (ZR4)S1-E

*Standard factory setup

Page 12 of the Omega TX82B user manual — 5.0 CONFIGURATION
Page 12 · click to enlarge
Page 12
Omega TX82B — 5.0 CONFIGURATION diagram (page 12)
Fig. 3

SPAN ADJ.

ZERO ADJ.

Figure 5-1 Main Board Jumper Locations

Page 13 of the Omega TX82B user manual — 6.0 CUSTOMER CONFIGURATION AND CALIBRATION
Page 13 · click to enlarge
Page 13

6.0 CUSTOMER CONFIGURATION AND CALIBRATION

Use this procedure to determine the configuration of the TX82B customized setup. The procedure is general; customers can specify any two current inputs and their corresponding digital readings. Pin-groups are shown in Figure 5-1.

6.1 FORMULA Base all your calculations on either the 1-5, 4-20 or 10-50 mA range. 1. Determine the lowest input current, I1, which is specified by the customer:

2. Determine the highest input current, I2, which is specified by the customer:
3. Determine the reading, N1, at input current I1, which is specified by the customer.
4. Determine the reading, N2, at input current I2, which is specified by the customer:
5. Calculate the Gain, G1:

(N2 - N1) G1 = = counts per mA (I2 - I1) (If G1 is greater than 125, it is out of range for a standard unit.)

6. Calculate the Required Zero Range number, RZR:

RZR = N1 - (I1 x G1) =

7. Select the Zero Range required from the following chart where the Required Zero Range number falls between the upper and lower limits of that range:

ZR1 = -2510 to -1420 ZR2 = -1580 to -420 ZR3 = -470 to +850 ZR4 = +760 to +2000 ZR =

Show 4 more labels / short text on this page
I1 = mA · I2 = mA · N1 = counts · N2 = counts
Page 14 of the Omega TX82B user manual — 6.4 FACTORY-SETUP LABEL
Page 14 · click to enlarge
Page 14

6.2 CONFIGURATION PROCEDURES

1. Remove all push-on jumpers.
2. For an input current range of 1-5 mA, no jumper is required.

For 4-20 mA input, install a push-on jumper at S1-H.

For 10-50 mA input, install a push-on jumper at S1-J.

3. If N2 (Section 6.1) is less than N1, reverse the signal polarity by removing jumpers from S1-B and S1-C and reinstalling jumpers at S1-A and S1-D.
4. Select the zero range required (ZR1-4) and install the push-on jumper as indicated in the configuration chart (Section 5.2).
5. If a decimal point is required (DP1-5), install a push-on jumper as indicated in the configuration chart (Section 5.2).
6. If one dummy right-hand zero is required, install jumper at S2-A.
7. If two dummy right-hand zeros are required, install jumpers at S2-A, S2-G, S2-H, and S2-J.

6.3 CALIBRATION

1. Apply an input current (I1) and adjust the zero pot (Z) to read N1.
2. Apply an input current (I2) and adjust the span pot (S) to read N2.
3. Repeat steps 1 and 2 as required to set N1 and N2 to within ±1 count.

6.4 FACTORY-SETUP LABEL

The label on the meter shows the factory-configured input and display settings. If the configuration is changed, use the extra label included with the meter to indicate the new settings.

Page 15 of the Omega TX82B user manual — 7.0 WIRING DIAGRAM
Page 15 · click to enlarge
Page 15

7.0 WIRING DIAGRAM

SAFE AREA HAZARDOUS AREA

MODEL TX82B INDICATOR

SHUNT ZENER DIODE SAFETY BARRIER

SAFE AREA APPARATUS

INTERCONNECTING CABLES

EARTHED BUS BAR

NOTES:

Apparatus which is unspecified except that it must not be supplied from nor contain under normal or abnormal conditions a source of potential with respect to Earth in excess of 250V R.M.S. or 250V D.C.

The following output parameters apply; Vmax=12.5V, Imax=250mA, Ci=8.6uF, Li=0mH

The Interconnecting Cable may be a twin pair, or a pair contained in a type A or type B multicore cable provided that the peak voltage of any circuit contained within the multicore does not exceed 60 volts.

The capacitance or inductance or inductance to resistance (4/R) ratio of the Interconnecting Cable must not exceed the values specified for the barrier in use.

5 The electrical circuit in the Hazardous Area must be capable of withstanding without breakdown an A.C. test voltage of 500V R.M.S. to Earth or frame for one minute.

Figure 7-1 Wiring Diagram for TX82B Usage for FM (Factory Mutual)

+

Page 16 of the Omega TX82B user manual — 7.0 WIRING DIAGRAM
Page 16 · click to enlarge
Page 16
Page 16 of the Omega TX82B user manual — 7.0 WIRING DIAGRAM
Page 17 of the Omega TX82B user manual — 7.0 WIRING DIAGRAM
Page 17 · click to enlarge
Page 17
Page 17 of the Omega TX82B user manual — 7.0 WIRING DIAGRAM
Page 18 of the Omega TX82B user manual — 7.0 WIRING DIAGRAM
Page 18 · click to enlarge
Page 18
Page 18 of the Omega TX82B user manual — 7.0 WIRING DIAGRAM
Page 19 of the Omega TX82B user manual — 7.0 WIRING DIAGRAM
Page 19 · click to enlarge
Page 19

WARRANTY/DISCLAIMER OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 13 months from date of purchase. OMEGA Warranty adds an additional one (1) month grace period to the normal one (1) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product. If the unit should malfunction, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of being damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which wear are not warranted, including but not limited to contact points, fuses, and triacs. OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages. CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER language, and additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.

RETURN REQUESTS / INQUIRIES Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence. The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.

FOR WARRANTY RETURNS, please have the following information available BEFORE contacting OMEGA: 1. P.O. number under which the product was PURCHASED, 2. Model and serial number of the product under warranty, and 3. Repair instructions and/or specific problems relative to the product.

FOR NON-WARRANTY REPAIRS, consult OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA: 1. P.O. number to cover the COST of the repair, 2. Model and serial number of product, and 3. Repair instructions and/or specific problems relative to the product.

OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering. OMEGA is a registered trademark of OMEGA ENGINEERING, INC. © Copyright 2003 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without prior written consent of OMEGA ENGINEERING, INC.

Page 20 of the Omega TX82B user manual — M1060/0303 10579ML-99 J
Page 20 · click to enlarge
Page 20

Where Do I Find Everything I Need for

Process Measurement and Control?

OMEGA…Of Course! Shop on line at www.omega.com

TEMPERATURE Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies Wire: Thermocouple, RTD & Thermistor Calibrators & Ice Point References Recorders, Controllers & Process Monitors Infrared Pyrometers

PRESSURE, STRAIN AND FORCE Transducers & Strain Gauges Load Cells & Pressure Gauges Displacement Transducers Instrumentation & Accessories

FLOW/LEVEL Rotameters, Gas Mass Flowmeters & Flow Computers Air Velocity Indicators Turbine/Paddlewheel Systems Totalizers & Batch Controllers

pH/CONDUCTIVITY pH Electrodes, Testers & Accessories Benchtop/Laboratory Meters Controllers, Calibrators, Simulators & Pumps Industrial pH & Conductivity Equipment

DATA ACQUISITION Data Acquisition & Engineering Software Communications-Based Acquisition Systems Plug-in Cards for Apple, IBM & Compatibles Datalogging Systems Recorders, Printers & Plotters

HEATERS Heating Cable Cartridge & Strip Heaters Immersion & Band Heaters Flexible Heaters Laboratory Heaters

ENVIRONMENTAL MONITORING AND CONTROL Metering & Control Instrumentation Refractometers Pumps & Tubing Air, Soil & Water Monitors Industrial Water & Wastewater Treatment pH, Conductivity & Dissolved Oxygen Instruments

M1060/0303 10579ML-99 J

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Omega TX82B

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Omega TX82B

Be the first to ask — other owners or our team will answer.

Original document

Omega TX82B manual PDF

20 pages·379 KB·Thermometer·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…