FIELDPOINT ™ OPERATING INSTRUCTIONS AND SPECIFICATIONS FP-DO-403 and cFP-DO-403 16-Channel, 5 to 30 V Sinking Digit al Output Module These operating instructions descri be ho w to install and use the National Instruments FP-DO-403 a nd cFP-DO-40 3 digital output modules, referred to inclusi v ely as the [c]FP-DO-403.
[c]FP-DO-403 2 ni.com 2. Align the FP-DO-403 alignment slots with the guide rails o n the terminal base. 3. Press firmly to seat the FP-DO-403 on the terminal base. When the module is firmly seated, the te rminal base latch locks it into place. Figure 1.
© National Instruments Corp. 3 [c]FP-DO-403 Figure 2. Installing the cFP-DO-403 Wiring the [c]FP-DO-403 The FP-TB- x terminal base has conne ctions for each FP-DO-403 output channel and for an external supply to po wer field devices. The cFP-CB- x connector block provides the same connections for the cFP-DO-403.
[c]FP-DO-403 4 ni.com loads on the output channels, up to 2 A per channel. 1 Connect the external po wer supply to multiple V and V SUP terminals and to multiple C and COM terminals as need ed to ensure that the maximum current through any terminal is 2 A or less.
© National Instruments Corp. 5 [c]FP-DO-403 Figure 3. Wiring for Low-Current Applica tions Wiring for High-Current Applications If your application requires more than 2 A combined current through all channels of the [c]F P-DO-403, wire your application as shown in Figure 4.
[c]FP-DO-403 6 ni.com Digital Output Circuit The [c]FP-DO-403 digital output ch annels are optically isolated from the rest of the FieldPoint bank . In the ON state, a transistor is turned on between the V OUT terminal and the ex ternal supply (the C and COM terminals).
© National Instruments Corp. 7 [c]FP-DO-403 mount the flyback diode within 18 in. of the load. Figure 5 shows a flyback diode connected to an inductiv e load.
[c]FP-DO-403 8 ni.com 250 V rms Measurement Cate gory II contin uous isolation, ve rified by 2,300 V rms , 5 s dielectric withst and test. The [c]FP-DO-403 provides double insulation (compliant with IEC 61010-1) for working v oltages of 250 V rms 1 .
© National Instruments Corp. 9 [c]FP-DO-403 •D o not use the [c]FP-DO-403 as the only isolating barrier between human cont act and working v o ltages higher than 250 V rms . • Operate the [c]FP-DO-403 only at or belo w Pollution Degree 2. Pollution De gree 2 means that only nonconductive pollution occurs in most case s.
[c]FP-DO-403 10 ni.com Caution For Zone 2 applications, install a protection device across the e xternal power supply and the COM terminal. The device must pre vent the external po wer supply voltage from e xceeding 42 V if there is a transient ov ervoltage conditi on.
© National Instruments Corp. 11 [c]FP-DO-403 Power Requirements Power from network module ............ 600 mW Safety Isolat ion Voltage Isolation voltage is v erified by a dielectric withstand te st. Channel to ground Continuous .............. ......
[c]FP-DO-403 12 ni.com Safety This product is designed to meet the requirements of the following standards of safety for electric al equipment for measurement, control, and laboratory use: • IEC 61010-1, EN-61010-1 • UL 61010-1, CSA 61010-1 Note For UL and other safety certif ications, refer to the product label or visit ni.
© National Instruments Corp. 13 [c]FP-DO-403 contains the en vironmental regulat ions and directi v es with which NI complies, as well as othe r en vironmental information not included in this document.
[c]FP-DO-403 14 ni.com Where to Go for Support For more information about settin g up the FieldPoint system, refer to these National Instruments documents: • FieldPoint network module user manual • Other FieldPo int I/O m odule operating instructions • FieldPoint terminal base and connector block operating instructions Go to ni.
© 2002–2007 Nati onal Instruments Corp. All rights reserved. 373354C-01 Aug07 National Instruments, NI, n i.com, and LabVIEW are trademarks of National I nstruments Corporation. Refer to the Terms of Use section on ni.com/legal for more information about National Instruments tra demarks.
An important point after buying a device National Instruments cFP-DO-403 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought National Instruments cFP-DO-403 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data National Instruments cFP-DO-403 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, National Instruments cFP-DO-403 you will learn all the available features of the product, as well as information on its operation. The information that you get National Instruments cFP-DO-403 will certainly help you make a decision on the purchase.
If you already are a holder of National Instruments cFP-DO-403, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime National Instruments cFP-DO-403.
However, one of the most important roles played by the user manual is to help in solving problems with National Instruments cFP-DO-403. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device National Instruments cFP-DO-403 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center