![Page 3 of the Mitsubishi Electronics QD73A1 user manual — [Design Precautions]](/cdn/reader/93/9329f02fdd44666247391cf41b744ad321d7bf007b6e21b29cf69df64d6062b3/images/page-3.webp?w=400)
Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle the product correctly. The precautions given in this manual are concerned with this product only. For the safety precautions of the programmable controller system, refer to the user’s manual for the CPU module used.
In this manual, the safety precautions are classified into two levels: " WARNING" and " CAUTION".
Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in minor or moderate injury or property damage.
Under some circumstances, failure to observe the precautions given under " CAUTION" may lead to serious consequences. Observe the precautions of both levels because they are important for personal and system safety.
Make sure that the end users read this manual and then keep the manual in a safe place for future reference.
WARNING
a servo amplifier whose control cannot be stopped through Servo ON signal, satisfy the following. • Analog voltage must be 0V (motor stop) to power off the programmable controller. (2) Emergency stop circuits, protection circuits, and protective interlock circuits for conflicting
operations (such as forward/reverse rotations or upper/lower limit positioning) must be configured external to the programmable controller. (3) OPR (Original Point Return) is controlled by two kinds of data: OPR direction and OPR speed.
Deceleration starts when the near-point dog turns on. If an incorrect OPR direction is set, motion control may continue without deceleration. To prevent machine damage caused by this, configure an interlock circuit external to the programmable controller. ●Do not write any data to the "system area" of the buffer memory in the intelligent function module. Also, do not use any "use prohibited" signal as an output signal from the CPU module to the intelligent function module. Doing so may cause malfunction of the programmable controller system.
![Page 4 of the Mitsubishi Electronics QD73A1 user manual — [Installation Precautions]](/cdn/reader/93/9329f02fdd44666247391cf41b744ad321d7bf007b6e21b29cf69df64d6062b3/images/page-4.webp?w=400)
CAUTION

WARNING
![Page 6 of the Mitsubishi Electronics QD73A1 user manual — [Disposal Precaution]](/cdn/reader/93/9329f02fdd44666247391cf41b744ad321d7bf007b6e21b29cf69df64d6062b3/images/page-6.webp?w=400)
WARNING
CAUTION
CAUTION

i) where any problem, fault or failure occurring in the PRODUCT, if any, shall not lead to any major or serious accident; and ii) where the backup and fail-safe function are systematically or automatically provided outside of the PRODUCT for the case of any problem, fault or failure occurring in the PRODUCT.
(2) The PRODUCT has been designed and manufactured for the purpose of being used in general
industries. MITSUBISHI SHALL HAVE NO RESPONSIBILITY OR LIABILITY (INCLUDING, BUT NOT LIMITED TO ANY AND ALL RESPONSIBILITY OR LIABILITY BASED ON CONTRACT, WARRANTY, TORT, PRODUCT LIABILITY) FOR ANY INJURY OR DEATH TO PERSONS OR LOSS OR DAMAGE TO PROPERTY CAUSED BY the PRODUCT THAT ARE OPERATED OR USED IN APPLICATION NOT INTENDED OR EXCLUDED BY INSTRUCTIONS, PRECAUTIONS, OR WARNING CONTAINED IN MITSUBISHI'S USER, INSTRUCTION AND/OR SAFETY MANUALS, TECHNICAL BULLETINS AND GUIDELINES FOR the PRODUCT. ("Prohibited Application") Prohibited Applications include, but not limited to, the use of the PRODUCT in; • Nuclear Power Plants and any other power plants operated by Power companies, and/or any
other cases in which the public could be affected if any problem or fault occurs in the PRODUCT. • Railway companies or Public service purposes, and/or any other cases in which establishment of
a special quality assurance system is required by the Purchaser or End User. • Aircraft or Aerospace, Medical applications, Train equipment, transport equipment such as
Elevator and Escalator, Incineration and Fuel devices, Vehicles, Manned transportation, Equipment for Recreation and Amusement, and Safety devices, handling of Nuclear or Hazardous Materials or Chemicals, Mining and Drilling, and/or other applications where there is a significant risk of injury to the public or property.
Notwithstanding the above, restrictions Mitsubishi may in its sole discretion, authorize use of the PRODUCT in one or more of the Prohibited Applications, provided that the usage of the PRODUCT is limited only for the specific applications agreed to by Mitsubishi and provided further that no special quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are required. For details, please contact the Mitsubishi representative in your region.

Thank you for purchasing the Mitsubishi MELSEC-Q series programmable controllers.
This manual describes the operating procedure, system configuration, parameter settings, functions, programming,
and troubleshooting of the QD73A1 positioning module (hereafter abbreviated as QD73A1).
Before using this product, please read this manual and the relevant manuals carefully and develop familiarity with the
functions and performance of the MELSEC-Q series programmable controller to handle the product correctly.
When applying the program examples introduced in this manual to an actual system, ensure the applicability and
confirm that it will not cause system control problems.
QnUCPU Users Manual (Function Explanation, Program Fundamentals)
Qn(H)/QnPH/QnPRHCPU User's Manual (Function Explanation, Program Fundamentals)
Page 275, Appendix 4

DIRECTIVES
To ensure that Mitsubishi programmable controllers maintain EMC and Low Voltage Directives when incorporated
into other machinery or equipment, certain measures may be necessary. Please refer to one of the following
manuals.
(This manual is included with the CPU module or base unit.)
The CE mark on the side of the programmable controller indicates compliance with EMC and Low Voltage
Directives.
To ensure that this product maintains EMC and Low Voltage Directives, please refer to Page 64, Section 4.6.1.

<manual number (model code)> Description
QCPU User's Manual (Hardware Design, Maintenance and
Specifications of the hardware (CPU modules, power supply modules,
base units, extension cables, and memory cards), system maintenance
and inspection, troubleshooting, and error codes
QnUCPU Users Manual (Function Explanation, Program
Functions, methods, and devices for programming Qn(H)/QnPH/QnPRHCPU User's Manual (Function
(4) Operating manual
Manual name
<manual number (model code)> Description
GX Works2 Version1 Operating Manual (Common)
System configuration, parameter settings, and online operations (common
to Simple project and Structured project) of GX Works2
GX Developer Version 8 Operating Manual
Operating methods of GX Developer, such as programming, printing,



In this manual, pages are organized and the symbols are used as shown below.
The following illustration is for explanation purpose only, and should not be referred to as an actual documentation.

[ ] is used for items in the menu bar and the project window.
*1 The mouse operation example is provided below.

[Online] [Write to PLC...] Select [Online] on the menu bar, and then select [Write to PLC...].
A window selected in the view selection area is displayed.
Select [Project] from the view selection area to open the Project window.
In the Project window, expand [Parameter] and select [PLC Parameter].

The following symbols are used to represent buffer memory areas in this manual. Serial numbers fit in "*".
Symbol indicating positioning parameter and OPR parameter item
Pr.*
Symbol indicating positioning data item
Da.*
Md.*
Symbol indicating monitor data item
Cd.*
Symbol indicating control data item
Symbol Description

Unless otherwise specified, this manual uses the following terms.
QD73A1 The abbreviation for the QD73A1 positioning module
QCPU Another term for the MELSEC-Q series CPU module
Redundant CPU A generic term for the Q12PRHCPU and Q25PRHCPU
External input The abbreviation for input from connectors for external devices
External output The abbreviation for output to connectors for external devices
Programming tool Generic term for GX Works2 and GX Developer
GX Works2 The product name of the software package for the MELSEC programmable
Buffer memory The memory of an intelligent function module used to store data (such as setting
values and monitored values) for communication with a CPU module
For terms related to positioning, refer to the following.
Page 278, Appendix 5
The product package contains the following.
QD73A1 QD73A1 positioning module 1
QD73A1-U-HW Before Using the Product 1
controllers GX Developer

CHAPTER 1 OVERVIEW
The QD73A1 possesses a deviation counter and D/A converter inside as in the following figure.
PLG
Parameter data Positioning data OPR parameters
Feedback pulses from the pulse generator (PLG) may be input to the QD73A1 via the drive unit*1 or directly*2 depending on the servomotor to be used. Check which method applies in the manual for the servomotor or drive unit to be used.
A system with the QD73A1 operates as follows.
Once a command pulse train for positioning is output, pulses are accumulated in the deviation counter. The
integrated value of pulses (accumulated pulses) is converted into DC analog voltage by a D/A converter, then
turns into a speed command to a servomotor. The speed command from a drive unit starts servomotor rotation.
Once the servomotor starts rotating, feedback pulses that are proportional to the number of rotations are
generated by a pulse generator (PLG) attached to the servomotor. The generated feedback pulses are
subtracted from the accumulated pulses in the deviation counter. The deviation counter continues to rotate the
servomotor, maintaining a constant amount of accumulated pulse.
Stop Once the command pulse output from the QD73A1 stops, the accumulated pulses in the deviation counter
decrease, so does the speed. When there is no more accumulated pulse, the servomotor stops.
The rotation speed of a servomotor is proportional to command pulse frequency, while the rotation degree of the
servomotor is proportional to the output command pulse amount. By setting feed per pulse beforehand, analog voltage
that is proportional to the number of pulses in a pulse train is output, and a workpiece can be moved to the set position.

inside
This module converts command pulse for positioning into analog voltage inside, then outputs a speed command
to a servo amplifier.
A servo amplifier does not require an extra module to convert pulse input into analog voltage; a standard servo
amplifier can be used.
This module handles up to 1Mpulse/s of pulse input from an encoder. Servomotor control that uses high-speed
input pulse signals from a high-resolution encoder improves the accuracy of positioning.
The following control can be executed.
Zero/gain adjustment can be performed through a sequence program. Therefore, the adjustment can be
performed without using a switch or checking a LED, saving man-hour.
(Note that zero/gain adjustment can also be performed using switches on the front of the QD73A1.)
Sequence programming is reduced since initial settings and the auto refresh setting can be configured on the
screen. In addition, the setting status and operating status of the module can be checked easily.

1.2 Signal Transmission Between the QD73A1 and Others
The following figure shows signal transmission between the QD73A1 and a CPU module, and a drive unit.
Y2D
Near-point dog signal (DOG)
Upper limit signal (FLS)
Lower limit signal (RLS) Speed-position switching command signal
OPR start complete signal
Positioning start complete signal
Phase-Z pulse (Zero signal)
Y2C
Speed-position switching enable signal
Speed-position mode restart signal
Servo READY signal (READY)
Servo ON signal (SVON)
Y29
X1A
1.2 Signal Transmission Between the QD73A1 and Others
X1D
Upper limit signal/Lower limit signal
X1B
WDT error, H/W error signal
writing request signal Zero/gain adjustment data
X2A
Zero/gain adjustment change request signal
Zero/gain adjustment change complete flag
Y1C
Set value change request signal
Set value change complete flag
Operating status of the speed-position

The CPU module and the QD73A1 transmit control signals and data to each other through the base unit.
Control signal Signals that indicate the QD73A1's status or
are related to commands are transmitted. Page 30, Section 3.4
Data is written to or read from the buffer
memory in the QD73A1 by application
Page 73, CHAPTER 5
instructions of the CPU module.
Control signals are transmitted between the drive unit and the QD73A1, and speed commands (analog voltage)
are output from the QD73A1 to the drive unit.
For details, refer to the following.
Page 40, Section 3.5
Data

CHAPTER 2 SYSTEM CONFIGURATION
This chapter describes the system configuration of the QD73A1.
This section describes applicable systems.
For the applicable CPU modules and base units, and the number of mountable modules, refer to the user’s
manual for the CPU module used.
number of mounted modules.
Select the power supply capacity according to the modules to be used.
If the power supply capacity is insufficient, change the combination of the modules.
Modules can be mounted on any slot within the number of available slots.
For an applicable MELSECNET/H remote I/O station and base units, and the number of mountable modules,
refer to the Q Corresponding MELSECNET/H Network System Reference Manual (Remote I/O network).
2.1 Applicable Systems
The function version of the first released QD73A1 is B, and the module supports multiple CPU systems.
When using the QD73A1 in a multiple CPU system, refer to the following.
QCPU User's Manual (Multiple CPU System)
Write intelligent function module parameters to only the control CPU of the QD73A1.
The QD73A1 does not support online module change.

The following table lists systems that use the QD73A1 and applicable software packages.
A programming tool is required to use the QD73A1.
GX Developer*1 GX Works2
Single CPU system Version 7 or later
Multiple CPU system Version 8 or later
Single CPU system Version 4 or later
Multiple CPU system Version 6 or later
Version 8.68W or later Multiple CPU system
Version 7.10L or later Multiple CPU system
Q12PRH/Q25PRHCPU Redundant system Version 8.45X or later
Version 8.76E or later Multiple CPU system
Refer to the GX Works2 Version 1 Operating Manual
Version 8.48A or later Multiple CPU system
(Common).
Version 8.76E or later Multiple CPU system
Version 8.62Q or later Multiple CPU system
Version 8.68W or later Multiple CPU system
Version 8.76E or later Multiple CPU system
CPU modules other than the above
N/A Multiple CPU system
When mounted on a MELSECNET/H remote I/O station Version 6 or later
*1 When using GX Developer, configure the initial settings and auto refresh settings with the sequence program.
PROGRAMMING ( Page 111, CHAPTER 7)

2.2 How to Check the Function Version and Serial Number

The function version and serial number of the QD73A1 can be checked on the rating plate, front part of the module, or
The rating plate is on the side of the QD73A1.

The function version and serial number on the rating plate are also shown on the front part (bottom part) of the
2.2 How to Check the Function Version and Serial Number
module.

The function version and serial number can be checked on the "Product Information List" window.
[Diagnostics] [System Monitor...] button

product. • The serial number displayed on the product information list of a programming tool indicates the function
information of the product. The function information of the product is updated when a new function is added.

CHAPTER 3 SPECIFICATIONS
This chapter describes performance specifications, I/O signals from/to the CPU module, and buffer memory
specifications of the QD73A1.
For general specifications of the QD73A1, refer to the following.
QCPU User's Manual (Hardware Design, Maintenance and Inspection)
The following table lists performance specifications of the QD73A1.
Number of occupied I/O points 48 points (I/O assignment: empty 16 points and intelligent 32 points)
Number of control axes 1 axis
Setting method Sequence program
Mode Position control mode
Speed-position control switch mode
Position command -2147483648 to 2147483647 (pulse) (signed 32-bit binary)
Speed command 1 to 4000000 (pulse/s)
Acceleration Automatic trapezoidal acceleration/deceleration
3.1 Performance Specifications
In-position range 1 to 20479 (pulse)
Error correction function None
Speed command output 0 to ±10VDC (Adjustable to set in the range of ±5 to ±10VDC)
Connectable encoder type Open collector, TTL, or differential output
Multiplication setting The number of input feedback pulses can be multiplied by 4, 2, 1, or 1/2.
OPR control With OP address change
An OPR method and OPR direction can be set with the switch setting.
JOG operation JOG operation can be started by inputting a JOG start signal.
Internal current consumption (5VDC) 0.52A
External supply voltage/current terminal block No external power supply
External dimensions 98(H)mm × 55.2(W)mm × 90(D)mm
Weight 0.20kg
(from a start request to analog output start)

Set initial settings and auto refresh settings of the QD73A1 so that the number of parameters, including those of other
intelligent function modules, does not exceed the number of parameters that can be set in the CPU module.
For the maximum number of parameters that can be set in the CPU module, refer to the following.
QCPU User's Manual (Hardware Design, Maintenance and Inspection)
For a QD73A1, the following number of parameters can be set.
(2) Checking method
The maximum number of parameter settings and the number of parameter settings set for the intelligent function
module can be checked on the following.
Project window [Intelligent Function Module] Right-click
[Intelligent Function Module Parameter List...]



3.3 List of Functions
This section introduces the functions of the QD73A1.
Major positioning functions are as follows.
A workpiece is returned to an original point following an OPR start
command, and the current value is corrected as an OP address after the
completion of OPR.
Positioning is executed from the current position to a specified position at
Section 9.6.1
a specified speed.
Positioning is executed to the address specified with " Positioning
Da.2
address P1" at " Positioning speed V1", then to the address
Da.3
Section 9.6.1
specified with " Positioning address P2" at " Positioning
Da.4 Da.5
speed V2" by one positioning start signal.
Operation starts according to the positioning speed set beforehand by
one positioning start signal, then the operation switches to position
control by Speed-position switching command signal (CHANGE).
If the operation stopped by Stop signal after the input of Speed-position
switching command signal (CHANGE), the positioning can be continued
Section 9.6.2
by requesting a restart.
In addition, the positioning address (movement amount) can be changed
if it is before the input of Speed-position switching command signal
(CHANGE).
3.3 List of Functions
Positioning is executed in the specified direction at specified speed while
a JOG operation command is on. Turning on the signal starts operation
at a specified speed and speed control operation can be continued until a
stop signal is input.
Sub functions compensate or limit control, or add functions at the execution of major positioning functions.
Electronic gear function This function controls moving distance and speed by
multiplying command pulse output of the QD73A1. Page 209, Section 11.1
This function limits command speed to the value set in
Page 211, Section 11.2
" Speed limit value".
Pr.5
This function controls operation not to execute positioning
when a command that moves the workpiece outside the
Page 213, Section 11.3
specified stroke limit range is given.
This function decelerates and stops operation according to the
detection on limit switches placed at the upper and lower
Page 215, Section 11.4
stroke limits.

This function changes the value set in " Current feed
Md.1
Page 217, Section 11.5
value" to a specified value.
Speed change function This function changes speed during major positioning control
or JOG operation. Page 218, Section 11.6
This function clears the accumulated pulses in the deviation
counter. When the servomotor power was turned off due to an
emergency stop during positioning, clearing the accumulated
Page 220, Section 11.7
pulses in the deviation counter prevents servomotor rotation
at power recovery.
This function turns on In-position signal (X16) while the
accumulated pulse amount in the deviation counter is within
the specified in-position range (1 to 20479pulse). In-position
Page 221, Section 11.8
signal (X16) can be used as the signal right before positioning
completion.
Multiplication setting This function multiplies the feedback pulse frequency from the
pulse generator by 4, 2, 1, or 1/2. Page 104, Section 6.2.3
This function outputs an alert and immediately stops the
positioning when the accumulated pulses reached the amount
specified by the user before the pulses exceed the amount set
Page 223, Section 11.9
in "Accumulated pulse setting" in the switch setting and an
excessive error occurs.
Common functions can be used regardless of control method when necessary.
Zero/gain adjustment This function adjusts analog output voltage. Page 59, Section 4.5
This function monitors the module information, switch setting
information, and external I/O signal information. The module's
Module status monitor function
detailed information can be displayed on the system monitor of GX
Works2.
Error history function This function monitors the QD73A1's error history stored in the
buffer memory.
This function reports errors that occurred in the QD73A1 to the CPU
Module error collection function
module. The error information is held in the CPU module memory as
a module error history.
Error clear function This function allows the user to clear errors on the system monitor. Page 240, Section

(4) Combination of main function and sub function

: Always used together, : Can be used together, ×: Cannot be used together

This section describes I/O signals of the QD73A1.
This section describes I/O signal assignment and use of each signal.
The first half of the I/O assignment is empty 16 points, and the second half is intelligent 32 points. When the module is
mounted on the slot No.0 and 1 of a main base unit, the device No.Xn0 becomes X10. Although, when the slot No.0 is
set as empty 0 point in the I/O assignment setting of GX Works2, the device No.Xn0 becomes X0 (n=0).
Device numbers used in this manual are for the case when the QD73A1 is mounted on the slot No.0 and 1 and when
the slot No.0 is empty 16 points.
Input signal (CPU module QD73A1) Input signal (CPU module QD73A1)
X10 WDT error, H/W error signal X20 OPR start complete signal
X11 QD73A1 READY signal X21 Absolute positioning start complete signal
X12 OPR request signal X22 Forward start complete signal
X13 OPR complete signal X23 Reverse start complete signal
X14 BUSY signal X24 Synchronization flag
X15 Positioning complete signal X25
X16 In-position signal X26
X17 Excessive error signal X27
X18 Error detection signal X28
X19 Overflow signal X29
X1A Underflow signal X2A Zero/gain adjustment data writing complete
X1B Servo READY signal X2B Zero/gain adjustment change complete flag
X1C Near-point dog signal X2C Set value change complete flag
X1D External stop signal X2D Operating status of the speed-position
X1E Upper limit signal X2E
Use prohibited X1F Lower limit signal X2F
If a "Use prohibited" area is turned on/off through a sequence program, the QD73A1's function cannot be guaranteed.
Use prohibited · flag · control switch mode

(2) Output signal list
Output signal (CPU module QD73A1) Output signal (CPU module QD73A1)
Y10
Y20 OPR start signal
Y11 Y21 Absolute positioning start signal
Y12 Y22 Forward start signal
Y13 Y23 Reverse start signal
Y14 Y24 Forward JOG start signal
Y15 Y25 Reverse JOG start signal
Y16 Y26 Speed-position mode restart signal
Y17 Y27 Stop signal
Y18 Y28 Error reset signal
Y19 Y29 Overflow reset signal
Y1A Zero/gain adjustment data writing request
signal Y2A Underflow reset signal
Y1B Zero/gain adjustment change request
signal Y2B Use prohibited
Y1C Set value change request signal Y2C Speed-position switching enable signal
Y2D PLC READY signal
Use prohibited Y1F Y2F
If a "Use prohibited" area is turned on/off through a sequence program, the QD73A1's function cannot be guaranteed.
3.4 I/O Signals from/to the CPU Module 3.4.1 I/O signal list
Use prohibited · Use prohibited

This signal turns on when a watchdog timer error is detected through the self-diagnostic function of the QD73A1.
In this case, Servo ON signal (SVON) turns off and analog output becomes 0.
When PLC READY signal (Y2D) is turned on through a sequence program, fixed parameters are checked and
this signal turns on.
When PLC READY signal (Y2D) is turned off, this signal turns off.
PLC READY signal (Y2D)
ON
QD73A1 READY signal (X11)
Executed by the QD73A1
Use this signal as an interlock in sequence programs.
This signal turns on at any of the following timing.
(only when "0: Clear the deviation counter when the servo ready signal is OFF." is selected for "Deviation
counter clear setting" in the switch setting)
This signal turns off when OPR is completed.
When PLC READY signal (Y2D) is turned on (rising edge), this signal does not turn on.
This signal turns on when OPR is completed.
This signal does not turn on if operation stopped during OPR.
This signal turns off when JOG operation or major positioning control is started.
In the count method, this signal turns off when OPR starts.
This signal turns off when Servo READY signal (READY) turns off (only when "0: Clear the deviation counter
when the servo ready signal is OFF." is selected for "Deviation counter clear setting" in the switch setting)
This signal turns on when major positioning control, JOG operation, or OPR starts.
This signal turns off when command pulse output is completed.
If positioning is started while BUSY signal (X14) is on, the error "BUSY signal ON at start" (error code: 81) occurs.

(6) Positioning complete signal (X15)
This signal turns on when major positioning control is completed (completion of command pulse output).
This signal turns off when the next positioning (major positioning control, OPR, or JOG operation) starts.
If major positioning control was cancelled during its operation, this signal does not turn on.
For the operation in case of cancellation of major positioning control, refer to the following.
Page 230, Section 12.1
This signal turns on while the accumulated pulse amount in the deviation counter is within the set range of
" In-position range" (1 to ±20479) after deceleration started.
Pr.8
This signal turns off when positioning starts.
In-position set values Accumulated pulses
(X16)
OFF
A A
A: In-position range
Accumulated pulse amount are checked being compared with " In-position range" at the following timing.
Pr.8
3.4 I/O Signals from/to the CPU Module 3.4.2 Details of input signals
This signal turns on when accumulated pulse amount exceeds the accumulated pulse setting range.
In this case, the QD73A1's status is as follows.
Md.2 Md.1
When PLC READY signal (Y2D) is turned on, this signal turns off.
Excessive error signal (X17)
ON
PLC READY signal (Y2D)
Executed by the QD73A1
Even if this signal turns on, Error detection signal (X18) does not turn on.
For the accumulated pulse setting range, refer to the following.
Page 102, Section 6.2.2
t · In-position signal

When a major or minor error occurs, the corresponding error code is stored in the buffer memory, and this signal
turns on.
When Error reset signal (Y28) is turned on, this signal turns off.
Error detection signal (X18)
ON
Error reset signal (Y28)
Executed by the QD73A1
This signal turns on when " Current feed value" exceeds 2147483647.
Md.1
When Overflow reset signal (Y29) is turned on, this signal turns off.
OFF
ON
Overflow reset signal (Y29)
Executed by the QD73A1
In case of an overflow, " Current feed value" changes as follows: 2147483647 -2147483648
Md.1
This signal turns on when " Current feed value" becomes less than -2147483648.
Md.1
When Underflow reset signal (Y2A) is turned on, this signal turns off.
OFF
ON
Underflow reset signal (Y2A)
Executed by the QD73A1
In case of an underflow, " Current feed value" changes as follows: -2147483648 2147483647
Md.1
This signal indicates the on/off status of Servo READY signal (READY).
This signal indicates the on/off status of Near-point dog signal (DOG).
This signal indicates the on/off status of Stop signal (STOP).
This signal indicates the on/off status of Upper limit signal (FLS).
This signal indicates the on/off status of Lower limit signal (RLS).
Overflow signal (X19) · Underflow signal (X1A)

(17)OPR start complete signal (X20)
This signal turns on when OPR process starts after OPR start signal (Y20) was turned on.
When OPR start signal (Y20) is turned off after the start of OPR, this signal turns off.
This signal turns on when positioning process starts after Absolute positioning start signal (Y21) was turned on.
When Absolute positioning start signal (Y21) is turned off after the start of the positioning, this signal turns off.
This signal turns on when positioning process starts after Forward start signal (Y22) was turned on.
When Forward start signal (Y22) is turned off after the start of the positioning, this signal turns off.
This signal turns on when positioning process starts after Reverse start signal (Y23) was turned on.
When Reverse start signal (Y23) is turned off after the start of the positioning, this signal turns off.
This signal turns on when the CPU module becomes accessible to the QD73A1 after the power was turned off
then on, or after the CPU module was reset.
When the module synchronization setting of the CPU module is set to asynchronous, use this signal as an
interlock to access the QD73A1 from a sequence program.
This signal turns on when zero/gain adjustment value writing to the QD73A1 is completed after Zero/gain
3.4 I/O Signals from/to the CPU Module 3.4.2 Details of input signals
adjustment data writing request signal (Y1A) was turned on.
When Zero/gain adjustment data writing request signal (Y1A) is turned off, this signal turns off.
Zero/gain adjustment data writing complete flag (X2A)
ON
Zero/gain adjustment data writing request signal (Y1A)
Executed in a sequence program Executed by the QD73A1
Use this signal as an interlock condition to turn on/off Zero/gain adjustment data writing request signal (Y1A)
when writing the zero/gain adjustment value to the QD73A1.
For details on zero/gain adjustment, refer to the following.
Page 59, Section 4.5

This signal turns on when zero adjustment and gain adjustment were switched after Zero/gain adjustment
change request signal (Y1B) was turned on.
When Zero/gain adjustment change request signal (Y1B) is turned off, this signal turns off.
Cd.10
OFF
ON
OFF
Executed in a sequence program Executed by the QD73A1
Use this signal as an interlock condition to turn on/off Zero/gain adjustment change request signal (Y1B) when
changing " Zero/gain adjustment specification".
Cd.10
For details on zero/gain adjustment, refer to the following.
Page 59, Section 4.5
This signal turns on when the analog output value of zero/gain adjustment was changed after Set value change
request signal (Y1C) was turned on.
When Set value change request signal (Y1C) is turned off, this signal turns off.
Set value change complete flag
(X2C)
ON
Set value change request signal
(Y1C)
Executed by the QD73A1 Executed in a sequence program
Use this signal as an interlock condition to turn on/off Set value change request signal (Y1C) when performing
zero/gain adjustment.
For details on zero/gain adjustment, refer to the following.
Page 59, Section 4.5
This signal indicates the operating status in the speed-position control switch mode.
This signal is on during speed control.
This signal is off during position control.

3.4.3 Details of output signals
(1) Zero/gain adjustment data writing request signal (Y1A)
Turn on this signal to write the zero/gain adjustment value to the QD73A1.
For the on/off timing of this signal, refer to the detail of Zero/gain adjustment data writing complete flag (X2A).
( Page 35, Section 3.4.2 (22))
For details on zero/gain adjustment, refer to the following.
Page 59, Section 4.5
Turn on this signal to change zero adjustment and gain adjustment.
For the on/off timing of this signal, refer to the detail of Zero/gain adjustment change complete flag (X2B).
( Page 36, Section 3.4.2 (23))
For details on zero/gain adjustment, refer to the following.
Page 59, Section 4.5
Turn on/off this signal to increase/decrease the analog output value at zero/gain adjustment.
The analog output is increased/decreased according to the value set in " Zero/gain adjustment value
Cd.11
specification".
For the on/off timing of this signal, refer to the detail of Set value change complete flag (X2C). ( Page 36,
Section 3.4.2 (24))
For details on zero/gain adjustment, refer to the following.
Page 59, Section 4.5
3.4 I/O Signals from/to the CPU Module 3.4.3 Details of output signals
Turn on this signal to start OPR.
Turn on this signal to start absolute system positioning (position control mode).
Turn on this signal to start positioning in the address increasing direction.
The following table describes the consequence of turning on this signal for each type of positioning (major
positioning control).
Starts in the address increasing direction (incremental system) Two-phase trapezoidal
Speed-position control switch mode Starts in the address increasing direction
Positioning control · Position control mode · positioning control

Turn on this signal to start positioning in the address decreasing direction.
The following table describes the consequence of turning on this signal for each type of positioning (major
positioning control).
Starts in the address decreasing direction (incremental system) Two-phase trapezoidal
Speed-position control switch mode Starts in the address decreasing direction
Turn on this signal to start JOG operation in the address increasing direction.
The JOG operation continues while this signal is on.
The JOG operation decelerates and stops when this signal is turned off.
Turn on this signal to start JOG operation in the address decreasing direction.
The JOG operation continues while this signal is on.
The JOG operation decelerates and stops when this signal is turned off.
Turn on this signal to restart positioning if it stopped due to Stop signal in the speed-position control switch mode.
Turn on this signal to decelerate and stop OPR operation, major positioning operation, or JOG operation.
If this signal is turned on during OPR, Error detection signal (X18) turns on.
Turn on this signal to clear the following buffer memory data to 0 when Error detection signal (X18) is on.
Md.3
Md.4
When this signal is turned on, Error detection signal (X18) turns off.
Turn on this signal to turn off Overflow signal (X19) when it is on.
For the on/off timing of this signal, refer to the detail of Overflow signal (X19). ( Page 34, Section 3.4.2 (10))
Positioning control · Position control mode · positioning control

(14)Underflow reset signal (Y2A)
Turn on this signal to turn off Underflow signal (X1A) when it is on.
For the on/off timing of this signal, refer to the detail of Underflow signal (X1A). ( Page 34, Section 3.4.2 (11))
Use this signal to enable/disable Speed-position switching command signal (CHANGE) in the speed-position
control switch mode.
Turn on this signal to enable Speed-position switching command signal (CHANGE). Turn off this signal to disable
Speed-position switching command signal (CHANGE).
This signal notifies the QD73A1 that the CPU module is operating normally.
This signal needs to be turned on beforehand to start OPR, major positioning, or JOG operation.
This signal needs to be turned off beforehand to write fixed parameters and OPR parameters.
When this signal is turned on, the QD73A1 performs the following.
When this signal is turned off while BUSY signal (X14) is on, the QD73A1 processes a deceleration stop.
When this signal is turned on while BUSY signal (X14) is on, the QD73A1 does not perform the operations 1 to 3
above.
Deceleration followed by PLC READY signal (Y2D) OFF
Even when PLC READY signal (Y2D) is turned on, the operations 1 to 3 are not performed.
3.4 I/O Signals from/to the CPU Module 3.4.3 Details of output signals
PLC READY signal (Y2D)
QD73A1 READY signal (X11)
ON
OFF
Executed by the QD73A1
BUSY signal (X14)

This section describes I/O interfaces between the QD73A1 and external devices.
This section describes electrical specifications of I/O interfaces between the QD73A1 and external devices.
ON
ON
OFF
OFF
Pulse
Signal name
range/Current
voltage
current
voltage
current
frequency
consumption
Supply power Input common 5 to 24VDC/
Max.60mA
Servo READY signal (READY)
Near-point dog signal (DOG)
4.75 to 26.4VDC 3V or
2.5mA or
higher 1V or lower 0.1mA or
Upper limit signal (FLS)
Lower limit signal (RLS)
Phase-A feedback pulse (PULSE A)
10.8 to 14VDC 4V or
2.7mA or
higher 1V or lower 0.1mA or
Phase-B feedback pulse (PULSE B)
Phase-Z feedback pulse (PULSE Z)
Phase-A feedback pulse (PULSE A)
4.5 to 5.5VDC 2.8V or
higher 0.8V or
Phase-B feedback pulse (PULSE B)
Phase-Z feedback pulse (PULSE Z)
Phase-A feedback pulse (PULSE A)
RS-422-A differential line receiver
Phase-B feedback pulse (PULSE B)
(Equivalent of AM26LS32 (Manufactured by Texas
Phase-Z feedback pulse (PULSE Z)
Instruments Inc.))
*1 The following table shows the pulse width and phase difference depending on pulse frequency.
5 s or more
2.5 s or more 2.5 s or more
When the phase A leads the
1.25 s or more
phase B, the positioning
1 s or more
increases.
0.5 s or more 0.5 s or more
0.25 s or more

(2) Output specifications
Max.
voltage/current Output method Load
Load
voltage
Leakage
voltage
current
drop at
current at OFF
ON
Servo ON signal (SVON) Open collector 4.75 to
26.4VDC Max.30mA*1 1.0V or
lower 0.1mA or lower
(analog signal) 0 to ±10VDC/10mA
*1 The load current of Servo ON signal (SVON) is 30mA at the maximum. When using a miniature relay, take the load current into consideration.
3.5 Specifications of I/O Interfaces with External Devices 3.5.1 Electrical specifications of I/O signals
Speed command signal

The following table shows signal layouts on external device connectors.
name Pin arrangement Pin number Signal name
1 Near-point dog signal (DOG)
5 Power supply (5 to 24V)
CONT.
6 Lower limit signal (RLS)
7 Upper limit signal (FLS)
8 Speed-position switching command signal (CHANGE)
Viewed from the front
9 Stop signal (STOP)
1 Servo READY signal (READY) (+ side)
2 Servo READY signal (READY) (- side)
3 Servo ON signal (SVON) (+ side)
4 Servo ON signal (SVON) (- side)
5 Phase-B feedback pulse (PULSE B) (+ side)
6 Phase-Z feedback pulse (PULSE Z) (+ side)
7 Phase-Z feedback pulse (PULSE Z) (- side)
10 Phase-B feedback pulse (PULSE B) (- side)
11 Phase-A feedback pulse (PULSE A) (- side)
13 Phase-A feedback pulse (PULSE A) (+ side)
Viewed from the front
14 Speed command signal (- side)
15 Speed command signal (+ side)

3.5.3 List of I/O signal details
This section describes details of signals that are input or output through external device connectors on the QD73A1.
Pin
number Signal detail
name
Phase-A feedback pulse (PULSE A)
input.
Phase-B feedback pulse (PULSE B)
increases at the rising and falling edges of each phase.
Phase-Z feedback pulse (PULSE Z)
decreases at the rising and falling edges of each phase.
Phase-A feedback pulse (PULSE A)
Phase-B feedback pulse (PULSE B)
Phase-Z feedback pulse (PULSE Z)
address -1
Upper limit signal (FLS)
limit position.
Lower limit signal (RLS) 6
limit position.
3.5 Specifications of I/O Interfaces with External Devices 3.5.3 List of I/O signal details
Near-point dog signal (DOG) 1
OPR.
CONT.
Stop signal (STOP) 9
in execution. Once this signal was turned on, the operation
does not restart even if this signal is turned off.
signal (CHANGE) 8 Input this signal to switch control during the speed-position control
switch mode.
This power supply is common to the following signals.
Power supply (5 to 24V) 5

Pin
number Signal detail
name
Servo READY signal (READY)
system does not operate even if this signal is turned on again.
Servo READY signal (READY)
(- side) 2 This line is common to Servo READY signal (READY).
servomotor.
Servo ON signal (SVON) (+ side) 3
at a system startup.
excessive error or by the QD73A1's self-diagnosis on its
hardware.
Servo ON signal (SVON) (- side) 4 This line is common to Servo ON signal (SVON).
Speed command signal (+ side) 15 The analog voltage converted from digital accumulated pulse
amount is output.
Speed command signal (- side) 14 This line is common to Speed command signal.
(+ side)

3.5.4 I/O interface internal circuit
This section shows internal circuits of external device interfaces on the QD73A1 in schematic diagrams.

Pin No. Internal circuit External wiring Signal name Remark
3.5 Specifications of I/O Interfaces with External Devices 3.5.4 I/O interface internal circuit
*1 When input impedance of the servo amplifier is low, analog output level may become low due to this resistance. If that causes a problem, perform gain adjustment again with the servo amplifier being connected.


Pin No. Internal circuit External wiring Signal name Remark

3.6 Memory Configuration and Use
There are two memories in the QD73A1.
: Data setting and storage, : No data setting and storage
Data in this memory cannot be backed up. Data are erased if the power is turned off.
Area that can be accessed directly from the CPU module using sequence programs
Data in this memory can be backed up. Data are kept even if the power is turned off.
Area used to back up zero/gain adjustment data
The following table describes each memory area.
Area name Description Reference
Parameter area Area used to set and store parameters for positioning, such as positioning parameters and OPR parameters
Page 75, Section 5.2 Page 79, Section 5.3
3.6 Memory Configuration and Use
Monitor data area Area where operating statuses of a positioning system are stored Page 85, Section 5.5
Control data area Area used to set and store data to operate or control a positioning system Page 89, Section 5.6
Positioning data area Area used to set and store positioning data Page 82, Section 5.4
Zero/gain adjustment data area Area used to set and store data for zero adjustment and gain adjustment –
Reference value storage area for accumulated pulse error detection function
Area used to store the reference value for the accumulated pulse error detection function –

This section lists the buffer memory addresses of the QD73A1.
For details on the buffer memory, refer to the following.
Page 73, CHAPTER 5
Do not write data to system areas and area where data cannot be written from sequence programs in the buffer memory. Writing data to these areas may cause malfunction.
Read/
Memory
Address
Address
Data
type *1 Name
value
Write
area
Reference
(decimal)
(hexadecimal)
0 0 H
Stroke limit upper limit 2147483647 R/W
Pr.1
Section 5.2
2 2H Stroke limit lower limit 0 R/W 3 3H
Pr.2
4 4H Numerator of command pulse
Pr.3
1 R/W Page 77,
multiplication for electronic gear
Section 5.2
(2) 5 5H Denominator of command pulse
Pr.4
multiplication for electronic gear
19 13 H
20 14 H
Pr.5
Speed limit value 200000 R/W
Section 5.2
22 16H Acceleration time 300 R/W Page 78,
Pr.6
Section 5.2
(4) 23 17H Deceleration time 300 R/W
Pr.7
24 18H In-position range 5 R/W
Section 5.2
Pr.8
25 19H Positioning mode 0 R/W
Pr.9
Section 5.2
39 27 H


90 5AH Current value change request 0 R/W

Read/
Memory
Address
Address
Data
type *1 Name
Reference
value
Write
area
(decimal)
(hexadecimal)
100 64 H
Md.1
Current feed value 0 R
102 66H Actual current value 0 R 103 67H
Md.2
104 68H Error code (ERR.1) 0 R
Md.3
105 69H Error code (ERR.2) 0 R
Md.4
106 6AH Deviation counter value
Md.5
108 6CH Movement amount after near-
Md.6
110 6EH Speed-position switching
Md.7
111 6FH Control mode 0 R
Md.8
112 70H Zero/gain execution status 0 R
Md.9
113 71H Zero/gain adjustment status 0 R
Md.10
114 72H Feedrate 0 R 115 73H
Md.11
116 74H Deviation counter value (pulse) 0 R 117 75H
Section 5.5
Md.21
118 76H Movement amount after near-
Md.22
point dog ON (absolute value)
Md.12
121 79H Error occurrence
Md.13
122 7AH Error occurrence
Md.14
123 7BH Error occurrence
Md.15
Error code and error
record 0 R 125 7DH
data structure as record
128 80 H
Error code and error
record 0 R 129 81H
data structure as record

Default
Read/
Memory
Address
Address
Data
type *1 Name
Reference
value
Write
area
(decimal)
(hexadecimal)
132 84 H
Error code and error
data structure as record
135 87 H
136 88 H
Error code and error
record 0 R 137 89H
data structure as record
140 8C H
Error code and error
record 0 R 141 8DH
data structure as record
144 90 H
Error code and error
record 0 R 145 91H
data structure as record
148 94 H
Section 5.5
Error code and error
record 0 R 149 95H
data structure as record
152 98 H
Error code and error
3.7 List of Buffer Memory Addresses
record 0 R 153 99H
data structure as record
156 9C H
Error code and error
record 0 R 157 9DH
data structure as record
160 A0 H
Error code and error
record 0 R 161 A1H
data structure as record

Read/
Memory
Address
Address
Data
type *1 Name
Reference
value
Write
area
(decimal)
(hexadecimal)
164 A4 H
Error code and error
data structure as record
167 A7 H
168 A8 H
Error code and error
record 0 R 169 A9H
data structure as record
172 AC H
Error code and error
record 0 R 173 ADH
data structure as record
Section 5.5
176 B0 H
Error code and error
record 0 R 177 B1H
data structure as record
180 B4 H
Error code and error
record 0 R 181 B5H
data structure as record
184 B8H Error history pointer 0 R
Md.16
199 C7 H
200 C8 H
Md.17
201 C9 H
202 CAH Minimum accumulated pulse
Md.18
Section 5.5
204 CCH Accumulated pulse error
Md.19
205 CDH Reference value measurement
Md.20
206 CE H
300 12C H


411 19BH Reference value write request 0 R/W
*1 For types of data, refer to the following.
Page 73, Section 5.1 *2 Default values are set after the power was turned off and on or the CPU module was reset. *3 This column indicates whether the data can be read from or written to the buffer memory area through sequence programs. R: Readable W: Writable *4 For the memory configuration, refer to the following.

BEFORE OPERATION
This chapter describes the procedure prior to operation, part names, zero/gain adjustment, and wiring method of the
QD73A1.
This section describes the handling precautions for the QD73A1.
Failure to do so may cause the module to fail or malfunction.
block to/from the module more than 50 times (IEC 61131-2 compliant) respectively.
Exceeding the limit may cause malfunction.
manual for the CPU module used.
Failure to do so may result in electric shock, fire, malfunction, or damage to or deterioration of the product.
insert the module fixing projection(s) into the hole(s) in the base unit and press the module until it snaps into
place.
Incorrect mounting may cause malfunction, failure or drop of the module.
When using the programmable controller in an environment of frequent vibrations, fix the module with a
screw.
Undertightening can cause drop of the screw, short circuit or malfunction.
Overtightening can damage the screw and/or module, resulting in drop, short circuit, or malfunction.
Module fixing screw (M3 screw)*1 0.36 to 0.48N • m
Connector screw (M2.6 screw) 0.20 to 0.29N • m
*1 The module can be easily fixed onto the base unit using the hook at the top of the module. However, it is recommended to secure the module with the module fixing screw if the module is subject to significant vibration. • Do not directly touch any conductive parts and electronic components of the module.
Doing so can cause malfunction or failure of the module.
fire, failure, or malfunction.

4.2 Settings and Procedure Before Operation
This section shows the procedure before operating the QD73A1.

Mounting the module Mount the QD73A1 on a specified slot.
Zero/gain adjustment Adjust a gain using a switch on the front part of the QD73A1, or I/O signals and the buffer memory.
Operation check of the drive unit Check the operation of the drive unit with forward/ reverse JOG operations in the factory default status.
Initial setting Create a sequence program in which initial settings are configured.
Initial setting Configure the initial setting using GX Works2.
Auto refresh setting Configure the auto refresh setting using GX Works2.
Programming and debugging Create and check a sequence program.

This section describes the part names of the QD73A1.

Indicates the operating status or error status of the QD73A1
Indicates the status of pulses on an encoder input phase A, B, or Z
BUSY LED Indicates the status of BUSY signal (X14) or writing of zero adjustment
Page 61, Section 4.5 (4) UP/DOWN switch A switch to adjust an analog output voltage value

Number Name Description Reference
Page 69, Section 4.6.3 6) CONT. connector A connector for external control devices
Page 61, Section 4.5 (4)
(DIP switch 1 and 2 are off as the factory default.)
4.3 Part Names
(a)

The LEDs on the front of the QD73A1 indicate the statuses of the module and axis control.

If the RUN LED does not turn on even after the power was turned off and
on, the module may be broken. Replace the module with another module.
Read out the error code, and take the corrective action described in the
The LED turns off when the positioning is completed.
Pulses are input through the pulse input terminals (phase A, B, and Z).
The LED turns off when the zero adjustment is completed.
The LED turns off when the gain adjustment is completed.
The zero adjustment value and the gain adjustment value are being
The LED turns off when writing of the zero adjustment value and gain

4.5 Zero/gain Adjustment
Zero/gain adjustment is a process to adjust analog output voltage according to accumulated pulse amount.
Adjust the analog output voltage value according to the analog speed command input of the drive unit used.
Adjust analog output voltage using the check pins on the front of the QD73A1.
For the position of check pins, refer to the following.
Page 56, Section 4.3
Adjust the analog output voltage of when accumulated pulse amount is "0". The voltage is adjusted to 0V as the
factory default. Zero adjustment may vary when the module is connected to a servomotor. In that case, perform
zero adjustment again. If the module is used with its zero adjustment being off, the connected servomotor rotates
a little when the power is turned on.
Adjust the analog output voltage of when accumulated pulse amount is the maximum. In the factory default
setting, adjustment is made so that the analog output voltage becomes 10V when accumulated pulse amount is
the default value.
Adjust a gain value according to the rated speed command voltage of the drive unit used. The gain value can be
adjusted within the range of 5 to 10V.
When changing the accumulated pulse amount at the gain value output from the default value, set the
accumulated pulse amount by referring to the following reference values.
Excessive
Accumulated
Reference value for the setting
4.5 Zero/gain Adjustment
error
pulse setting
When the gain value
When the gain value
value
is 5V
is 10V
Initial setting The initial setting is same as the case where [Selection 4] is set.
[Selection 1] -3700 to 3700 3480 -2500 to -2000
[Selection 2] -7400 to 7400 6960 -5000 to -4000
[Selection 3] -11100 to 11100 10440 -7500 to -6000
[Selection 4] -14800 to 14800 13920 -10000 to -8000
[Selection 5] -37000 to 37000 34800 -25000 to -20000
[Selection 6] -74000 to 74000 69600 -50000 to -40000
[Selection 7] -111000 to 111000 104400 -75000 to -60000
[Selection 8] -148000 to 148000 139200 -100000 to -80000

Gain adjustment can be performed in the following two methods.
Follow the procedure below.
1 Change the operation mode to the zero/gain adjustment mode.
2 Set "Accumulated pulse setting" in the switch setting according to the necessary accumulated pulse amount.
3 Adjust the voltage to be the necessary voltage value between the check pins.
Follow the procedure below.
1 Change the operation mode to the zero/gain adjustment mode.
2 Set "Accumulated pulse setting" in the switch setting according to the necessary accumulated pulse amount. (Do not
specify amount that exceeds the setting range.)
Write the accumulated pulse amount using a sequence program.
[When one of the selections 1 to 4 is specified in "Accumulated pulse setting"]
Set the specified accumulated pulse amount in " Analog output adjustment area 1".
Cd.5
Accumulated pulse amount write command
[When one of the selections 5 to 8 is specified in "Accumulated pulse setting"]
Set the specified accumulated pulse amount in " Analog output adjustment area 2".
Cd.9
Accumulated pulse amount write command
4 Adjust the voltage to be the necessary voltage value between the check pins.
When performing zero/gain adjustment, satisfy the following two conditions.
In case of positive accumulated pulse amount (Gain value) - (Zero value) 5.0V
In case of negative accumulated pulse amount (Gain value) - (Zero value) -5.0V

(4) Setting method
The following are the procedures for zero adjustment and gain adjustment.
Set the servomotor in the servo-lock status.
Is the ERR.LED off?*3
Turn on both DIP switch 1 and 2 on the lower part of the module, then turn on the power.*1
Specify gain adjustment by changing the SELECT/SET switch to SELECT, while checking the GAIN LED. (Zero/gain adjustment switches every time when the switch is set to SELECT.)
Check that the module is in the zero/gain adjustment mode on the RUN LED. (The LED flashes in the zero/gain adjustment mode.)
GAIN
Configure "Accumulated pulse setting" in the switch setting, and write it to the CPU module.
Turn off then on the power, or reset the CPU module.
Adjust the voltage to be the gain value between check pins using the UP/DOWN switch. (Holding the switch increases the adjustment amount.)
Specify zero adjustment by changing the SELECT/SET switch to SELECT, while checking the ZERO LED. (Zero/gain adjustment switches every time when the switch is set to SELECT.)
4.5 Zero/gain Adjustment
Set the SELECT/SET switch to the SET side and check that the BUSY LED turns on. After the BUSY LED turned off, set the SELECT/SET switch back to the center.*2
ON
NO
Is the ERR.LED off?*3
YES
Adjust the voltage to be 0V between check pins using the UP/DOWN switch. (Holding the switch increases the adjustment amount.)
Turn off the power, then turn off both DIP switch 1 and 2 on the lower part of the module.
Set the SELECT/SET switch to the SET side and check that the BUSY LED turns on. After the BUSY LED turned off, set the SELECT/SET switch back to the center.*2
*1 The operation mode cannot be switched to the zero/gain adjustment mode if the power is turned on ahead of turning on DIP switch 1 and 2. *2 The zero adjustment value and gain adjustment value are recorded in the flash ROM inside the QD73A1 by setting the SELECT/SET switch on the SET side, and they are not erased even at a power-off. *3 If an error occurs in the zero/gain adjustment mode, the ERR. LED turns on. If the ERR. LED is on, turn on Error reset signal (Y28) then perform zero/gain adjustment again.

Write the adjustment amount of the voltage between check pins to " Cd.11 Zero/gain adjustment value specification".
Write the adjustment amount of the voltage between check pins to " Cd.11 Zero/gain adjustment value specification".
Set the servomotor in the servo-lock status.
Turn on the power.
Turn on Set value change request signal (Y1C).
Turn on Set value change request signal (Y1C).
Configure the following items in the switch setting, and write them to the CPU module. "Accumulated pulse setting": Set accumulated pulse amount. "Zero/gain adjustment mode/Normal mode setting": Select "Zero/gain adjustment mode"
Check that Set value change complete flag (X2C) turned on following the change of voltage between check pins. Then, turn off Set value change request signal (Y1C). (Check that Set value change complete flag (X2C) is off after turning off Set value change request signal (Y1C).)
Check that Set value change complete flag (X2C) turned on following the change of voltage between check pins. Then, turn off Set value change request signal (Y1C). (Check that Set value change complete flag (X2C) is off after turning off Set value change request signal (Y1C).)
Turn off then on the power, or reset the CPU module.
Is the voltage between check pins equal to
Is the voltage between check pins 0V?
Check that " Md.9 Zero/gain execution status" is "2: In the zero/gain adjustment mode (switch setting)".
YES
Turn on Zero/gain adjustment data writing request signal (Y1A).*1
Set " Cd.10 Zero/gain adjustment specification to "1: Zero adjustment".
Set " Cd.10 Zero/gain adjustment specification to "2: Gain adjustment".
Check that Zero/gain adjustment data writing complete flag (X2A) is on.
Turn on Zero/gain adjustment change request signal (Y1B).
Turn on Zero/gain adjustment change request signal (Y1B).
Turn off Zero/gain adjustment data writing request signal (Y1A).
Check that Zero/gain adjustment change complete flag (X2B) is on.
Check that Zero/gain adjustment change complete flag (X2B) is on.
Check that Zero/gain adjustment data writing complete flag (X2A) is off.
Turn off Zero/gain adjustment change request signal (Y1B).
Turn off Zero/gain adjustment change request signal (Y1B).
Check that Zero/gain adjustment change complete flag (X2B) is off.
Check that Zero/gain adjustment change complete flag (X2B) is off.
Is the ERR.LED off?*2
Check that " Md.10 Zero/gain adjustment status" is "1: Adjusting zero".
Check that " Md.10 Zero/gain adjustment status" is "2: Adjusting gain".
Change "Zero/gain adjustment mode/ Normal mode setting" to Normal mode" in the switch setting.
*1 The zero adjustment value and gain adjustment value are recorded in the flash ROM inside the QD73A1 by turning on Zero/gain adjustment data writing request signal (Y1A), and they are not erased even at a power-off. *2 If an error occurs in the zero/gain adjustment mode, the ERR. LED turns on. If the ERR. LED is on, turn on Error reset signal (Y28) then perform zero/gain adjustment again.

(5) Restoring the zero/gain adjustment value of the factory default
Writing "1" in " Factory default zero/gain adjustment value restoration request" restores the zero/gain
Cd.12
adjustment value of the factory default. Once the restoration was completed, the QD73A1 sets "0" in
" Factory default zero/gain adjustment value restoration request".
Cd.12
Once the restoration was completed, analog output voltage becomes 0V and the QD73A1 sets "1: Adjusting
zero" in " Zero/gain adjustment status".
Md.10
Cd.12
adjustment mode.
Setting item Setting range Default value Execution condition
address
(decimal)
The module must be in
Cd.12
mode.
Zero value and gain value of the factory default are set as below.
4.5 Zero/gain Adjustment

This section describes precautions on wiring the QD73A1 and external devices, and connection of external device
connectors.
This section describes the precautions on wiring.
must be correctly soldered. Incomplete soldering or crimping may result in malfunction.
a fire, failure, or malfunction.
entering the module during wiring. Do not remove the film during wiring.
Remove it for heat dissipation before system operation.
Tighten the connector screws within the specified torque range.
Undertightening can cause short circuit, fire, or malfunction.
Overtightening can damage the screw and/or module, resulting in drop, short circuit, fire, or malfunction.
Connector screw (M2.6 screw) 0.20 to 0.29N • m
Disconnect the cable holding the connector.
Pulling a cable connected to the module or the drive unit can cause malfunction.
Such action can also damage the module, drive unit, or cable.
circuit lines, power cables, or load circuit lines of a device other than the programmable controller. Keep a
distance of 100mm or more between them.
Failure to do so may result in malfunction due to noise, surges, and induction.
resulting in damage to the module, drive unit, or cables, or malfunction due to poor contact.

100mm) to a power cable.
Ground the shields of shielded cables to the control panel securely on the module side.
AD75CK cable clamp (manufactured by Mitsubishi Electric).
(Ground the shield parts at a point within 20 to 30cm from the module.)

For details on the AD75CK, refer to the following.
AD75CK-type Cable Clamping Instruction Manual
the specifications of the drive unit. Review the specifications of the drive unit to be used.

depends on the specifications of the encoder. Review the specifications of the encoder to be used. Use
shielded twisted pair cable for the connection with the encoder.
ON signal externally. If Servo ON signal is not connected, the motor may rotate even in case of a CPU error.

This section describes precautions when connecting an encoder.
The deviation counter in the QD73A1 counts up and down.
An addition/subtraction switchover can be processed through the phases of feedback pulses.
When "0: Positive voltage is output when the positioning address increases." is set for "Rotation direction setting"
in the switch setting.
When feedback pulses are input with the phase A leading the
phase B by 90°, the number of command pulses is subtracted.
This input method is for counting positive command pulses when
the speed command is positive voltage (when the motor is rotating
forward).
When feedback pulses are input with the phase B leading the
phase A by 90°, the number of command pulses is added.
This input method is for counting negative command pulses when
the speed command is negative voltage (when the motor is
rotating reverse).
If the sequence of the phase A and phase B is reversed, the number of command pulses and feedback pulses
are counted together. This can cause an excessive error of accumulated pulses, resulting in the stop of the
control.
setting" in the switch setting, the count process (positive or negative) of the feedback pulses varies depending
on "Feed back pulse addition/subtraction setting" of the switch setting as shown below.
Switch setting Feedback pulse
When the phase A
When the phase B
"Rotation direction setting" "Feed back pulse
proceeds 90 degrees than
proceeds 90 degrees than
When the phase A proceeds 90 degrees
When the phase B proceeds 90 degrees
Rotation direction setting When 0 is set: DIR = 1 When 1 is set: DIR = -1
- (subtraction) + (addition)
+ (addition) - (subtraction)
- (subtraction) + (addition)

For details on "Rotation direction setting" in the switch setting, refer to the following.
Page 101, Section 6.2.1
The connection between the QD73A1 and the encoder varies depending on "Rotation direction setting" and
"Feed back pulse addition/subtraction setting" of the switch setting.
Ex. When the rotation directions of the motor and encoder are as below and the motor rotates forward when
positive voltage is applied to the servo amplifier

Suppose the condition of the feedback pulses from the
in case of forward run.
Connection Rotation direction
Feed back pulse
setting
addition/subtraction setting
directions of the motor
and the encoder are the
address increases.
directions of the motor
and the encoder are
4.6 Wiring 4.6.2 Precautions when connecting an encoder
directions of the motor
and the encoder are the
proceeds 90 degrees than
phase B.
directions of the motor
and the encoder are
address increases.
directions of the motor
and the encoder are the
proceeds 90 degrees than
phase B.
directions of the motor
and the encoder are

The following table shows the connection between the QD73A1 and each type of encoder.
Set the output type of the encoder to be used in "Encoder I/F setting" of the switch setting.
For details on "Encoder I/F setting" in the switch setting, refer to the following.
Page 100, Section 6.2
QD73A1
Open collector output type Open collector output
TTL output type TTL output
Differential output type Differential output
Encoder · Encoder · Encoder

4.6.3 External device connectors
This section describes the assemblage of an external device connector and its connection method.
The following connectors are required to connect the QD73A1 and external devices.
The connectors are composed of the following parts.

Protective tube (For a 15-pin connector only)
Cover A Cover B Wire clamp
Assemble the connectors as follows.
pin connector only).

4.6 Wiring 4.6.3 External device connectors
Wrap the wires with

a protective seal.
contacts the wire clamp.
(To the next page)

(From the previous page)

part with the wire clamp using the screws A.


using the screws B and nuts.

(2) Wiring connectors
The figure below shows the pin arrangement on the connectors.
Wire pins correctly according to the signal assigned to each pin number.
For details on the signal assigned to each pin number, refer to the following.
Page 43, Section 3.5.3
from the wire side
15-pin connector Applies to the SERVO. connector
9-pin connector Applies to the CONT. connector
The applicable wire size is 0.3mm2 or less. If thicker wires are used, the wire clamp cannot be attached.
Solder the wires to the pins.
4.6 Wiring 4.6.3 External device connectors
Strip parts of wire jackets properly to avoid a short circuit due to wire chips or solder chips.
If the signal line is exposed, malfunction may occur due to static electricity. Cover and protect the connector
pins with heat shrinkable insulation tubes.

Pin arrangement viewed · Soldering · Wire

The following table lists applicable 9-pin connector and 15-pin connector. When wiring, use applicable wire and
an appropriate tightening torque.
Model Tightening torque Diameter Type Material Temperature
rating
17JE-23090-02(D8A)
(manufactured by DDK Ltd.)
0.20 to 0.29N • m 28 to
24AWG Stranded Copper 75°C or more 15-pin connector for
(manufactured by DDK Ltd.)
To contact the manufacturer regarding the connectors, refer to the following.
http://www.ddknet.co.jp/English/index.html

CHAPTER 5 DATA USED FOR POSITIONING
This chapter describes parameters and data used for positioning.
The parameters and data required to carry out control with the QD73A1 include "setting data", "monitor data", and
"control data" shown below.
Setting data (Data to be set beforehand according to the machinery and application)
Set parameters that are fixed beforehand depending on the mechanical system.
( to Pr.13 )
Pr.1
If a setting of fixed parameters is outside the setting range, default values will be set to all of the fixed parameters for the control. Note
( to Pr.9 ) Pr.1
Set parameters that vary depending on each positioning control.
If a setting of variable parameters is outside the setting range, a default value will be set to only the corresponding parameter for the control. Note
Set data for OPR.
( to Pr.13 ) Pr.10
Positioning data Positioning data
Set start data for major positioning control.
( to Da.5 ) Da.1
5.1 Types of Data
Monitor data (Data that indicates the control status. The data can be monitored when necessary.)
Monitoring area Monitor data such as a current position, error codes, and error history.
( to Md.22 ) Md.1

Control data (Data for the user to control the positioning system)
Set data for operation and data for current value change or speed change during operation.
( to , , to to Cd.4 Cd.6 Cd.8 Cd.13 Cd.20 ) Cd.1
data area Set data for zero/gain adjustment.
( , Cd.9 Cd.12 to ) Cd.5
Set control data using sequence programs.
Control change area · Zero/gain adjustment

5.2 Positioning Parameters
This section describes the details of positioning parameters.
Item Setting range Default value
Stroke limit upper limit
Pr.1
5.2 (1) Stroke limit lower limit 0pulse 2
Pr.2
Pr.3
electronic gear (CMX) 1 to 9999
(Satisfy the following condition.
5.2 (2) Denominator of
Pr.4
Speed limit value 10 to 4000000pulse/s
(Set in the unit of 10pulse/s.) 200000pulse/s 20
Pr.5
5.2 (3)
2 to 9999ms 300ms 22 Page 78,
Pr.6
Pr.7
5.2 (4) Deceleration time 23
Pr.8
In-position range 1 to 20479pulse 5pulse 24
5.2 Positioning Parameters
5.2 (5)
Pr.9
5.2 (6)

Pr.1 Pr.2
Set the upper and lower limits of the workpiece moving range.

For details on the stroke limit function, refer to the following.
Page 213, Section 11.3
Pr.1 Pr.2

(2) Numerator of command pulse multiplication for electronic gear,
Pr.3
Pr.4
Set the numerator (CMX) and denominator (CDV) of command pulse multiplication for electronic gear.

For details on the electronic gear function, refer to the following.
Page 209, Section 11.1
When the positioning speed value that is multiplied by the set value of electronic gear exceeds " Speed limit value", the limit value is ignored. On the other hand, if the speed exceeds 4Mpulse/s, the error "Outside the command frequency range" (error code: 104) occurs. In this case, the speed is 4Mpulse/s, resulting in a positioning error.
Pr.5
5.2 Positioning Parameters
Pr.5
Set the upper limit speed of major positioning control or JOG operation. If command speed that is faster than this
limit is specified, the speed is limited to this value.
Pr.5

Pr.6 Pr.7

Pr.5
Pr.8
Set the accumulated pulse amount where In-position signal (X16) turns on.
In-position signal (X16) can be used as the signal right before Positioning complete signal (X15).
For details on the in-position function, refer to the following.
Page 221, Section 11.8
Pr.9
Select a control mode of major positioning from the position control mode or the speed-position control switch
mode.
If a value other than 0 and 1 is set, the error "Positioning mode Outside the setting range" (error code: 14) occurs. Although, the QD73A1 checks the setting range only for the start by Forward start signal (Y22) or Reverse start signal (Y23). For the start by the following signals, the above error does not occur even if the set value is outside the setting range.

5.3 OPR Parameters
This section describes the details of OPR parameters.
Item Setting range Default value
OP address -2147483648 to
41 Page 79, Section 5.3 (1)
Pr.10
OPR speed 1 to 4000000pulse/s 10000pulse/s 42
Pr.11
43 Page 79, Section 5.3 (2)
Creep speed 1 to 4000000pulse/s 1000pulse/s 44
45 Page 80, Section 5.3 (3)
Pr.12
Setting for the movement
amount after near-point dog ON 0 to 2147483647pulse 75pulse 46
47 Page 81, Section 5.3 (4)
Pr.13
The set data of OPR parameters are activated when PLC READY signal (Y2D) is turned on, and the error check is executed when OPR start signal (Y20) is turned on.
For details on OPR control, refer to the following.
Page 178, CHAPTER 8
Pr.10
Set the address that is the reference point of major positioning control.
Upon completion of OPR, the set value is stored in the current value monitor (" Current feed value" and
Md.1
5.3 OPR Parameters
" Actual current value").
Md.2
Pr.11
Set the speed of OPR control.
Satisfy the following condition when setting the speed.
Creep speed OPR speed Speed limit value
Pr.12 Pr.11 Pr.5
If the OPR speed exceeds " Speed limit value", the error "OPR speed Outside the setting range" (error
Pr.5
code: 20) occurs, and the OPR is not executed.

Pr.12
Once the near-point dog turns on, the control decelerates from " OPR speed" and stops. Set the speed of
Pr.11
right before the stop, which is a creep speed.
Pr.11
Pr.12
OFF
(DOG)
Satisfy the following condition when setting the speed.
Creep speed OPR speed Speed limit value
Pr.12 Pr.11 Pr.5
If the creep speed exceeds " OPR speed", the error "Creep speed Outside the setting range" (error code:
Pr.11

(4) Setting for the movement amount after near-point dog ON
Pr.13
When the OPR method is the count method, set the movement amount from the position where Near-point dog
signal (X1C) turns on to the original point. Set a value equal to or greater than the deceleration distance from the
OPR speed to the creep speed.
Deceleration distance (pulse) =
(OPR speed + Creep speed) (pulse/s)
Actual deceleration time (ms)
The following are the setting precautions.


When the position where the near-point dog turns on is set near the center of Zero signals, " Setting for the movement amount after near-point dog ON" should be an integral multiple of pulses per one servomotor rotation. Then the position moved after the near-point dog ON does not overlap with Zero signal. For instance, when the number of pulses per one servomotor rotation is 2000, set 2000 pulses.

This section describes the details of positioning data.
Item Setting range Default value
control 301 Page 82, Section 5.4 (1)
Da.1
Absolute system:
Da.2
303 Page 83, Section 5.4 (2)
Incremental system:
Positioning speed V1 1 to 4000000pulse/s 0pulse/s 304
305 Page 84, Section 5.4 (3)
Da.3
Absolute system:
307 Page 84, Section 5.4 (4)
Da.4
Incremental system:
Positioning speed V2 1 to 4000000pulse/s 0pulse/s 308
Da.5
309 Page 84, Section 5.4 (5)
Positioning data can be set any time, but the error check is executed when a positioning start signal (Y21 to Y23) is turned on.
For details on positioning control, two-phase trapezoidal positioning control, and speed-position control switch mode,
refer to the following.
Page 185, CHAPTER 9
Da.1
Select a control pattern of major positioning from "positioning control" or "two-phase trapezoidal positioning
control".
When 0 is set in b0, positioning control is specified, and when 1 is set in b0, two-phase trapezoidal positioning
control is specified.
b15 b0 b1 to
Values in b1 to b15 are ignored.

(2) Positioning address P1
Da.2
Set the address that is the destination of major positioning control. The setting range depends on the type of
major positioning control.
If the specified positioning address is outside the stroke range, the error "Positioning address Outside the setting
range" (error code: 30) occurs, and the positioning does not start.
When the absolute system is selected, set an absolute address (movement amount from the OP).
Stop position (positioning start address)
To execute two-phase trapezoidal positioning control in the absolute system, the positioning direction from
" Positioning address P1" to " Positioning address P2" and the positioning direction from the
Da.2 Da.4
current value to " Positioning address P1" must be the same.
Da.2
If not, the error "Two-phase trapezoidal positioning address error" (error code: 31) occurs, and the two-phase
trapezoidal positioning control does not start.
When the incremental system is selected, set movement amount from the current value.
Stop position (positioning start address)
5.4 Positioning Data
-30000 30000 (Movement amount) (Movement amount)
Moving in negative direction
Moving in positive direction
Set movement amount of after the shift from speed control to position control.

Da.3
Set the command speed of major positioning control. Set a value equal to or less than " Speed limit value".
Pr.5
If the value exceeds " Speed limit value", the error "Positioning speed Outside the setting range" (error
Pr.5
code: 32) occurs, and the command speed is limited to " Speed limit value".
Pr.5
If the specified positioning speed is 0, the error "Positioning speed Outside the setting range" (error code: 32)
occurs, and the positioning does not start.
Da.4
This setting is enabled only for two-phase trapezoidal positioning control.
Set the destination address of after the move to the address set to " Positioning address P1".
Da.2
For details on " Positioning address P1", refer to the following.
Da.2
Page 83, Section 5.4 (2)
Da.5
This setting is enabled only for two-phase trapezoidal positioning control.
Set the command speed to move to the address set to " Positioning address P2".
Da.4
The setting condition is the same as that of " Positioning speed V1". ( Page 84, Section 5.4 (3))
Da.3

5.5 Monitor Data
This section describes the details of monitor data.
memory
Item Description Default value
address
(decimal)
motor position during operation)
Md.1
Pr.10
function, the changed value is stored. ( Page 217, Section 11.5)
feedback pulses is stored as an actual current value (the number of
Md.2
feedback pulses). (Actual current value = Current feed value -
Accumulated pulses in the deviation counter)
the error code is overwritten.)
Error code (ERR.1)
Md.3
to 0.
For details on error codes, refer to the following.
Page 250, Section 14.3
5.5 Monitor Data
the error code is overwritten.)
Md.4
Error code (ERR.2)
to 0.
For details on error codes, refer to the following.
Page 250, Section 14.3
Md.5
stored as a deviation counter value.
dog ON to the OPR completion is stored. (Movement amount:
Movement amount to OPR completion using near-point dog ON as
"0".) The stored value varies depending on feedback pulses input at
the OPR as shown below. When the phase A proceeds 90 degrees than phase B: positive
Md.6
value When the phase B proceeds 90 degrees than phase A: negative
count method. (Use the value as a reference value for OPR
adjustment.)

memory
Item Description Default value
address
(decimal)
The on/off status of Speed-position switching command signal
(CHANGE) is stored.
Md.7
The control mode under the speed-position control switch mode is
stored.
Md.8
The execution status of the zero/gain adjustment mode is stored.
Md.9
The status of zero/gain adjustment is stored.
Md.10
(May be different from the actual motor speed during operation)
Md.11
An error code is stored.
Md.12
For details on error codes, refer to the following.
Page 250, Section 14.3
The time (year: month) of error detection is stored in BCD code.
The data can be monitored in hexadecimal.
2 0 4 1
b8 b7 b0 b15
Error occurrence (Year:
0 0 0 1 0 0 1 0 1 0 0
Md.13
0 to 9 0 to 1 0 to 9 0 to 9
00 to 99 (Year) 01 to 12 (Month)
5.5 (1)
The time (day: hour) of error detection is stored in BCD code.
The data can be monitored in hexadecimal.
1 1 0 2
b8 b7 b0 b15
Error occurrence (Day:
Md.14
0 0 1 0 1 0 0 0 1 0
0 to 9 0 to 2 0 to 9 0 to 3
01 to 31 (Day) 00 to 23 (Hour)

Buffer
memory
Item Description Default value
address
(decimal)
The time (minute: second) of error detection is stored in BCD code.
The data can be monitored in hexadecimal.
5 0 8 1
b8 b7 b0 b15
0 0 0 1 0 1 0 1 0 1 0 0 0
Md.15
0 to 9 0 to 5 0 to 9 0 to 5
5.5 (1)
00 to 59 (Minute) 00 to 59 (Second)
15 is stored.
Md.16
cleared to 0.
[When the accumulated pulse error detection function is being executed]
Md.17
The reference value that is kept in the flash ROM of the QD73A1 is
displayed.
[When the reference value is being measured]
The maximum/minimum accumulated pulse values are stored when the
pulse value 0 pulse 202
Md.18
positioning is executed in the address increasing/decreasing direction.
0 is stored.
The status of the accumulated pulse error detection function is
5.5 Monitor Data
displayed.
Md.19
The status of the reference value measurement is displayed.
Check that this area stores 1 before writing data in the flash ROM.
Md.20
This area becomes 0 at the following timing.
Cd.18
and the error detection starts
CMX/CDV" and "Number of feedback pulses × Multiplication" is stored
Md.21
as a deviation counter value.
dog ON to the OPR completion is stored as an absolute value.
Md.22
near-point dog ON as "0".)
count method. (Use the value as a reference value for OPR
adjustment.)

184 Md.16
Stores the pointer number that is next to the one for the latest error history record.
Pointer No.
Pointer No. 0
120 Md.12
A set of buffer memory data is organized as an error history record with a pointer number.
Ex.
Pointer No.0 = Buffer memory addresses 120 to 123 Pointer No.1 = Buffer memory addresses 124 to 127 Pointer No.2 = Buffer memory addresses 128 to 131
Pointer No.15 = Buffer memory addresses 180 to 183 Error history records are stored from the pointer No.1 up to No.15. After 16 records are stored, the next record will be assigned the pointer No.0. (The new record replaces the older record.)

5.6 Control Data
This section describes the details of control data.
Item Description Setting range Default
memory
value
address
(decimal)
changing the current value.
" Current value change request"
Cd.7
Cd.1
changes the value in " Current feed
Md.1
value".
For details on the current value change
function, refer to the following.
Page 217, Section 11.5
speed.
0 to " Speed limit
" Speed change request" executes
Cd.8
Pr.5
Cd.2
the speed change.
For details on the speed change function,
refer to the following.
Page 218, Section 11.6
5.6 Control Data
Pr.5
value", the error "JOG speed Outside the
the speed is limited to " Speed limit
Pr.5
value".
1 to 4000000pulse/s 0pulse/s 84
Cd.3
attempted, the error "JOG speed Outside
and the operation does not start.
For details on JOG operation, refer to the
following.
Page 200, CHAPTER 10

Item Description Setting range Default
memory
value
address
(decimal)
pulses in the deviation counter.
other than "1" is set, the command is
ignored.
is stored automatically.
counter was cleared, check that this area
stores "0" and no error is detected before
the start.
Cd.4
" Actual current value" changes to the
Md.2
value in " Current feed value".
Md.1
(X14) is on. Check that BUSY signal (X14)
is off before writing data. If data writing is
attempted while BUSY signal (X14) is on,
the error "Deviation counter clear error"
(error code: 114) occurs.
For details on the deviation counter clear
function, refer to the following.
Page 220, Section 11.7
specific accumulated pulse amount.
pulse setting" in the switch
setting.
adjustment mode.
range (Unit:
of the selections 1 to 4 is set in
"Accumulated pulse setting" in the switch
Selection 1 -3700 to
setting. (When one of the selections 5 to 8 is
Cd.5 Cd.9
set, use " Analog output adjustment
Selection 2 -7400 to
area 2".)
Selection 3 -11100 to
error "Analog output adjustment area 1
Outside the setting range" (error code: 125)
occurs.
For details on zero/gain adjustment, refer to
the following.
Page 59, Section 4.5
of after a switchover to position control in
the speed-position control switch mode.
Speed-position switching command signal
1 to 2147483647pulse 0pulse 88
(CHANGE).
Cd.6
operation starts.
For details on the Speed-position control
switch mode, refer to the following.
Page 195, Section 9.6.2

Buffer
Item Description Setting range Default
memory
value
address
(decimal)
change.
Cd.1
"1" in this area. If a value other than "1" is
set, the setting is ignored.
accepted, "0" is stored automatically.
requested while BUSY signal (X14) is on.
Cd.7
Check that BUSY signal (X14) is off before
requesting a current value change.
BUSY signal (X14) is on, the error "Current
occurs.
For details on the current value change
function, refer to the following.
Page 217, Section 11.5
Cd.2
"1" in this area. If a value other than "1" is
set, the setting is ignored.
stored automatically.
" New speed value" exceeding
Cd.2
5.6 Control Data
Cd.8
" Speed limit value", the error "New
Pr.5
speed value Outside the setting range"
the change is limited to " Speed limit
Pr.5
value".
For details on the speed change function,
refer to the following.
Page 218, Section 11.6
specific accumulated pulse amount.
pulse setting" in the switch
setting.
adjustment mode.
range (Unit:
to 8 is set in "Accumulated pulse setting" in
the switch setting. (When one of the
Selection 5 -37000 to
selections 1 to 4 is set, use " Analog
Cd.5
Cd.9
output adjustment area 1".)
Selection 6 -74000 to
error "Analog output adjustment area 2
Selection 7 -111000 to
Outside the setting range" (error code: 126)
occurs.
For details on zero/gain adjustment, refer to
Selection 8 -148000 to
the following.
Page 59, Section 4.5

Item Description Setting range Default
memory
value
address
(decimal)
adjustment".
using switches on the front of the QD73A1,
the set value is ignored.
Cd.10
error "Zero/gain adjustment setting error"
(error code: 123) occurs.
For details on zero/gain adjustment, refer to
the following.
Page 59, Section 4.5
the analog output value during zero/gain
adjustment.
adjustment amount when Set value change
request signal (Y1C) is turned on and off.
Ex.
When 1000 is set, the analog output
value can be adjusted by approximately
Cd.11
-3000 to 3000 0 95
using switches on the front of the QD73A1,
the set value is ignored.
error "Zero/gain adjustment value error"
(error code: 124) occurs.
For details on zero/gain adjustment, refer to
the following.
Page 59, Section 4.5
value and gain adjustment value to the
factory default.
Cd.12
adjustment mode.
adjustment value 0 96
ignored.
restored, "0" is stored automatically.

Buffer
Item Description Setting range Default
memory
value
address
(decimal)
The difference between the reference value
(maximum value) and the judgment value
(alert output accumulated pulses (maximum
value)) is set.
The relation between this setting and the
judgment value is as follows.
[If " Accumulated pulse setting value
Cd.17
selection" is set to 0]
Cd.17
Alert output accumulated pulses (maximum
selection" is set to 0:
value) = reference value (maximum value) +
1 to 148000 pulse
Cd.13
Alert output accumulated pulse setting
Cd.17
Cd.13
selection" is set to 1:
[If " Accumulated pulse setting value
Cd.17
selection" is set to 1]
are the value after the
Alert output accumulated pulses (maximum
decimal point.)
value) = reference value (maximum value) +
( Alert output accumulated pulse setting
Cd.13
value (maximum value) - 1000) × reference
value (maximum value) 1000
For details on the accumulated pulse error
detection function, refer to the following.
5.6 Control Data
Page 223, Section 11.9

Item Description Setting range Default
memory
value
address
(decimal)
The difference between the reference value
(maximum value) and the judgment value
(immediate stop accumulated pulses
(maximum value)) is set.
The relation between this setting and the
judgment value is as follows.
[If " Accumulated pulse setting value
Cd.17
selection" is set to 0]
Cd.17
Immediate stop accumulated pulses
(maximum value) = reference value
selection" is set to 0:
(maximum value) + Immediate stop
Cd.14
1 to 148000 pulse
accumulated pulse setting value (maximum
Cd.17
Cd.14
selection" is set to 1:
[If " Accumulated pulse setting value
Cd.17
selection" is set to 1]
are the value after the
Immediate stop accumulated pulses
decimal point.)
(maximum value) = reference value
(maximum value) + ( Immediate stop
Cd.14
accumulated pulse setting value (maximum
value) - 1000) × reference value (maximum
For details on the accumulated pulse error
detection function, refer to the following.
Page 223, Section 11.9

Buffer
Item Description Setting range Default
memory
value
address
(decimal)
The difference between the reference value
(minimum value) and the judgment value (alert
output accumulated pulses (minimum value))
is set.
The relation between this setting and the
judgment value is as follows.
[If " Accumulated pulse setting value
Cd.17
selection" is set to 0]
Cd.17
Alert output accumulated pulses (minimum
selection" is set to 0:
value) = reference value (minimum value) +
-148000 to -1 pulse
Cd.15
Alert output accumulated pulse setting
Cd.17
Cd.15
selection" is set to 1:
[If " Accumulated pulse setting value
Cd.17
selection" is set to 1]
are the value after the
Alert output accumulated pulses (minimum
decimal point.)
value) = reference value (minimum value) +
( Alert output accumulated pulse setting
Cd.15
value (minimum value) - 1000) × reference
value (minimum value) 1000
For details on the accumulated pulse error
detection function, refer to the following.
5.6 Control Data
Page 223, Section 11.9

Item Description Setting range Default
memory
value
address
(decimal)
The difference between the reference value
(minimum value) and the judgment value
(immediate stop accumulated pulses
(minimum value)) is set.
The relation between this setting and the
judgment value is as follows.
[If " Accumulated pulse setting value
Cd.17
selection" is set to 0]
Cd.17
Immediate stop accumulated pulses
selection" is set to 0:
(minimum value) = reference value (minimum
-148000 to -1 pulse
value) + Immediate stop accumulated
Cd.16
Cd.17
pulse setting value (minimum value)
Cd.16
selection" is set to 1:
[If " Accumulated pulse setting value
Cd.17
selection" is set to 1]
are the value after the
Immediate stop accumulated pulses
decimal point.)
(minimum value) = reference value (minimum
value) + ( Immediate stop accumulated
Cd.16
pulse setting value (minimum value) - 1000) ×
reference value (minimum value) 1000
For details on the accumulated pulse error
detection function, refer to the following.
Page 223, Section 11.9
Cd.13
accumulated pulse setting value (maximum
value)" to " Immediate stop
Cd.16
accumulated pulse setting value (minimum
value)" is selected.
is regarded as 0.
Cd.17
maximum/minimum reference values are
set to 0, the error "Accumulated pulse error
the accumulated pulse error detection
function does not operate.
For details on the accumulated pulse error
detection function, refer to the following.
Page 223, Section 11.9

Buffer
Item Description Setting range Default
memory
value
address
(decimal)
pulse error detection function.
pulse error detection function is executed.
However, if the reference value has never
been measured, the error "Accumulated
occurs and the function does not operate.
is regarded as 0.
Cd.18 Cd.19
to 1, the function does not operate even if
this area is set to 1. (This request is ignored
and after " Measurement start
Cd.19
request" is set to 0, the function is
executed.)
For details on the accumulated pulse error
detection function, refer to the following.
Page 223, Section 11.9
pulses used as the reference value to detect
an error.
values are measured.
5.6 Control Data
is regarded as 0.
Cd.18
request" is set to 1, the value is not
Cd.19
measured even if this area is set to 1. (This
request is ignored and after
" Accumulated pulse error detection
Cd.18
request" is set to 0, the function is
executed.)
For details on the accumulated pulse error
detection function, refer to the following.
Page 223, Section 11.9

Item Description Setting range Default
memory
value
address
(decimal)
reference value in the flash ROM of the
QD73A1.
measured reference value is saved in the
flash ROM.
Md.20
measurement flag" is set to 1, the value is
written to the flash ROM. If
" Reference value measurement flag"
Md.20
Cd.20
is set to the value other than 1, the error
"Reference value write error" (error code:
value saving in the flash ROM is completed.
This process is the same when an error
occurs and the value is not written.
For details on the accumulated pulse error
detection function, refer to the following.
Page 223, Section 11.9
Reference value write · request 411 · request

CHAPTER 6 VARIOUS SETTINGS
This chapter describes setting procedures of the QD73A1.
Open the "New Module" window.
Project window [Intelligent Function Module] Right-click [New Module...]

6.1 Adding a Module
Module Type Set "QD70 Type Positioning Module".
Module Name Set the name of the module to mount.
Base No. Set the base unit where the module is mounted.
Mounted Slot No. Set the slot No. where the module is mounted.
The start I/O number (hexadecimal) of the module is set, according to the mounted
slot No. Any start I/O number can be set.
Title setting Title Set any title.

Configure settings related to the drive unit and encoder that are connected to the QD73A1.
Open the "Switch Setting" window.
Project window [Intelligent Function Module] Module name [Switch Setting]

Set the rotation direction in which
positioning address increases.
positioning addresses increase.
Section 6.2.1
positioning address increases.
address increases.
Select the maximum accumulated
pulse amount that can be counted
Section 6.2.2
in the deviation counter.
Set the multiplication rate of
feedback pulses from the pulse
Section 6.2.3
generator (PLG).
Set the direction in which OPR is
executed.
Section 6.2.4
setting Select an OPR method. • Near-point dog method
Section 6.2.5
Select an encoder output type
from open collector, TTL, or
Section 4.6.2
differential output.
Set resolution of analog voltage
12-bit resolution Page 105,
to be output as a speed
Section 6.2.7
command.

Item Description Setting value Default value Reference
Set whether to add or subtract the
feedback pulses to/from the
degrees than phase B.
deviation counter when the phase
Section 6.2.8
A of feedback pulse proceeds 90
degrees than phase B.
phase B.
degrees than phase B.
Set whether to clear the deviation
ready signal is OFF.
counter when Servo READY
Section 6.2.9
signal turns off.
servo ready signal is OFF.
is OFF.
Select the zero/gain adjustment
Section 4.5
mode or the normal mode.
Set the direction in which positioning addresses increase.
The rotation direction of a motor depends on the polarity of the voltage to be applied to the servo amplifier.
For details, refer to the manual for the servo amplifier.
For connection between the QD73A1 and an encoder, refer to the following.
Page 66, Section 4.6.2
6.2 Switch Setting 6.2.1 Rotation direction setting

Select the maximum accumulated pulse amount that can be counted in the deviation counter.
When a servomotor is used, "maximum accumulated pulse amount" obtained by the following formula generates.
Position loop gain (s-1)
Configure this setting so that "maximum accumulated pulse amount" stays within the accumulated pulse setting
range.
Position loop gain is a parameter to be set on the servomotor side. It effects operation in case of a servomotor
stop and pulse amount in the deviation counter during operation.
Low Accumulated amount is large, and adjustment time at a stop becomes long.
High Overshoot becomes large at a stop, or vibration tends to occur during a stop.
Position loop gain is adjusted to 20 to 30s-1 normally. Make fine adjustment if necessary.
For details, refer to the manual for the servomotor.
Maximum accumulated · Speed command (pulse/s) · pulse amount =

(b) Accumulated pulse amount and analog output voltage from the QD73A1
The analog output voltage from the QD73A1 is controlled in proportion to accumulated pulse amount.
Selection 2 Selection 3 Selection 4 Analog output voltage Gain adjustment value
3700* 3480 6960 7400* 10440 11100* 13920 14800*
If the accumulated pulse exceeds the amount marked *, an excessive error occurs.
Selection 6 Selection 7 Selection 8 Analog output voltage
6.2 Switch Setting 6.2.2 Accumulated pulse setting
34800 69600 104400 139200
37000* 74000* 111000* 148000*
If the accumulated pulse exceeds the amount marked *, an excessive error occurs.
The following is an example of selecting an option in "Accumulated pulse setting".
pulse = = Maximum speed
If the number of accumulated pulses is 133333, "-148000 to 148000 pulse" should be selected in
"Accumulated pulse setting" so that analog output voltage will not be saturated.

If accumulated pulse amount exceeds an upper limit value (values marked * in Page 103, Section 6.2.2 (1) (b)),
an excessive error occurs and the following conditions occur in the system.
To reset an excessive error, turn off and on PLC READY signal (Y2D).
Set the multiplication rate of feedback pulses from the pulse generator (PLG).
This setting multiplies the feedback pulse count by 4, 2, 1, or 1/2. Use this setting to change movement amount per
pulse by 1/4, 1/2, 1, or 2.

Set the direction in which OPR is executed.
For OPR control, refer to the following.
Page 178, CHAPTER 8

OPR (Original Point Return) is controlled by two kinds of data: OPR direction and OPR speed. Deceleration starts when the near-point dog
turns on. If an incorrect OPR direction is set, motion control may continue without deceleration. To prevent machine damage caused by
this, configure an interlock circuit external to the programmable controller.
Select an OPR method.
For OPR control, refer to the following.
Page 178, CHAPTER 8

6.2.6 Encoder I/F setting
Select an encoder output type from open collector, TTL, or differential output.
For connection between the QD73A1 and an encoder, refer to the following.
Page 66, Section 4.6.2
Set resolution of analog voltage to be output as a speed command.
The default value of "Analog voltage resolution setting" is "12-bit resolution". When the analog voltage resolution of the connected drive unit is higher than 12 bits and the motor rotates even with a tiny voltage, the resolution can be set higher (14 bits or 16 bits). In that way, fine control can be achieved.
6.2 Switch Setting 6.2.6 Encoder I/F setting

Set whether to add or subtract the feedback pulses to/from the deviation counter when the phase A of feedback pulse
proceeds 90 degrees than phase B.
This setting becomes enabled only when "1: Negative voltage is output when the positioning address increases." is set
for "Rotation direction setting" in the switch setting. If "0: Positive voltage is output when the positioning address
increases." is set, the setting value of "Feed back pulse addition/subtraction setting" is ignored.
For the connection between the QD73A1 and the encoder, refer to the following.
Page 66, Section 4.6.2
When the feedback pulses are input, the feedback pulses are added or subtracted to/from the deviation counter (when
"Multiplication setting" is 4).
(1) When a feedback pulse whose phase A is ahead of phase B by 90° is input
0 1 2 3 4 5...
0 -1 -2 -3 -4 -5...
(2) When a feedback pulse whose phase B is ahead of phase A by 90° is input
0 -1 -2 -3 -4 -5...
0 1 2 3 4 5...

6.2.9 Deviation counter clear setting
Set whether to clear the deviation counter when Servo READY signal turns off.
If "0: Clear the deviation counter when the servo ready signal is OFF." is set, the deviation counter is cleared and OPR
request signal turns on when Servo READY signal turns off. After Servo READY signal is turned on, execute OPR
before executing the positioning control.
If "1: Do not clear the deviation counter when the servo ready signal is OFF." is set, the deviation counter is not cleared
when Servo READY signal turns off. OPR request signal does not turn on as well. When turning on Servo READY
signal after that, ensure the system safety in advance because turning on the signal may cause a sudden rotation of
the motor.
The current feed value and the position of the controlled object may not match. Execute the OPR.
0 Actual current value
OPR request signal (X12)
6.2 Switch Setting 6.2.9 Deviation counter clear setting
(2) When "1: Do not clear the deviation counter when the servo ready signal is OFF." is set
Current feed value 0
0 Actual current value
0 5 0 5→0
2 3 4 1
OPR request signal (X12)
Analog output 0V 5) 4) 3) 2) 1) 0V 5)→1)
The motor may rotate suddenly. Ensure the safety before turning on Servo READY signal.
1): Voltage corresponds to one pulse is output.

Set positioning parameters and OPR parameters.
Setting parameters on the screen omits the parameter setting in a sequence program.
Open the "Parameter" window.
Project window [Intelligent Function Module] Module name [Parameter]

For "Positioning mode", double-click the item to display the pull-down list. Select an option.
Double-click the item to set, and input the setting value.
For details on setting values, refer to the following.
Stroke limit upper limit 2147483647 pulse Page 76, Section 5.2 (1) Stroke limit lower limit 0 pulse
Numerator of command pulse
multiplication for electronic gear 1
Page 77, Section 5.2 (2) Denominator of command pulse
multiplication for electronic gear 1
Speed limit value 200000 pulse/s Page 77, Section 5.2 (3)
Acceleration time 300 ms Page 78, Section 5.2 (4) Deceleration time 300 ms
In-position range 5 pulse Page 78, Section 5.2 (5)
OP address 0 pulse Page 79, Section 5.3 (1)
OPR speed 10000 pulse/s Page 79, Section 5.3 (2)
Creep speed 1000 pulse/s Page 80, Section 5.3 (3)
Setting for the movement amount after
near-point dog ON 75 pulse Page 81, Section 5.3 (4)
Fixed parameter · Variable parameter · OPR parameter

6.4 Positioning Data Setting
Set positioning data.
Setting positioning data on the screen omits the positioning data setting in a sequence program.
Open the "Positioning_Axis_#1_Data" window.
Project window [Intelligent Function Module] Module name [Positioning_Axis_#1_Data]

For details on setting values, refer to the following.
Page 82, Section 5.4 (1)
Positioning address P1 Page 83, Section 5.4 (2)
Positioning speed V1 Page 84, Section 5.4 (3)
Positioning address P2 Page 84, Section 5.4 (4)
6.4 Positioning Data Setting
Positioning speed V2 Page 84, Section 5.4 (5)
Positioning pattern · None (empty)

This function transfers data in the buffer memory to specified devices.
The auto refresh setting omits data reading/writing through a program.
Open the "Auto_Refresh" window.
Project window [Intelligent Function Module] Module name
[Auto_Refresh] 2. Click the item to set, and input the destination device for auto refresh.


CHAPTER 7 PROGRAMMING
This chapter describes sequence programs of the QD73A1.
When applying the program examples introduced in this chapter to the actual system, ensure the applicability and
confirm that they will not cause system control problems.
At a power-on or operation start, execute OPR to confirm the original point (OP). When an OPR request is
issued, take the OPR into consideration.
Use a high-performance near-point dog signal. If Near-point dog signal is not input upon OPR, the workpiece
continues to move at the OPR speed.
By setting a stroke limit upper limit and lower limit of the QD73A1, an overrun can be prevented.
limit switch" to ensure the safety of the entire system. It is recommended to establish an external circuit through
which the motor's power turns off when a limit switch turns on.
7.1 Precautions on Programming
Check that proper values are set in " Stroke limit upper limit" and " Stroke limit lower limit".
Pr.1 Pr.2
Establish an emergency stop circuit outside the programmable controllers.
Turn off PLC READY signal (Y2D) at error detection.
Pr.5
Check that a proper value is set.
Cd.3
Do not set a large value at the beginning; start operation at lower speed.

There are following ways of communication with the QD73A1 using a sequence program.
The sequence programs introduced in this chapter uses intelligent function module devices. When using the
FROM/TO instruction, change the sequence program as shown below.
When an intelligent function module device is used as the destination side in a circuit using the BMOVP instruction, change
the instruction to the TOP instruction.

When an intelligent function module device is used in a circuit using a comparison instruction, change the instruction to the
FROM instruction and a comparison instruction.

For intelligent function module devices, refer to the following.
The user's manual (Function Explanation, Program Fundamentals) for the CPU module used.
For details on the instructions used in programs in this chapter, refer to the following.
MELSEC-Q/L Programming Manual (Common Instruction)

(10)I/O number assignment for the QD73A1
The QD73A1 occupies 48 I/O points of 2 slots.
Set the first half to "Empty 16 points" and the second half to "Intelligent 32 points" in GX Works2.

When executing the FROM/TO instruction on the QD73A1, use the I/O number assigned to the second half (slot)
of the QD73A1.
At the I/O assignment in GX Works2, the 16 points in the first half can be saved by setting the first half to
"Empty 0 point".

When executing the FROM/TO instruction on the QD73A1, use the I/O number assigned to the second half
(slot) of the QD73A1.
7.1 Precautions on Programming

Follow the procedure below when creating programs that execute positioning using the QD73A1.
Page 117, Section 7.3.1
Create a program for parameter setting.
Page 149, Section 7.4.1
Create a program for one of the following.
Page 119, Section 7.3.2
Page 151, Section 7.4.2
Create programs for the following depending on the control to be
Page 125, Section 7.3.3
executed.
Page 133, Section 7.3.4
Page 135, Section 7.3.5
Page 157, Section 7.4.3
Page 167, Section 7.4.4
Page 170, Section 7.4.5
Create programs for the following depending on the control to be
executed.
Page 137, Section 7.3.6
Page 172, Section 7.4.6
Page 141, Section 7.3.7
Create a program for stopping control.
Page 177, Section 7.4.7

7.3 When Using the Module in a Standard System Configuration
This section introduces program examples where the following system configuration applies.

7.3 When Using the Module in a Standard System Configuration
Rotation direction setting Set this item according to the system to be used.
Accumulated pulse setting Set this item according to the system to be used.
Multiplication setting Set this item according to the system to be used.
OPR direction setting Set this item according to the system to be used.
OPR method setting Set the near-point dog method or the count method.
Encoder I/F setting Set this item according to the system to be used.
Analog voltage resolution setting Set this item according to the system to be used.
Feed back pulse addition/subtraction setting Set this item according to the system to be used.
Deviation counter clear setting Set this item according to the system to be used.
Zero/gain adjustment mode/Normal mode setting Set "Normal mode".

Write the set parameters to the CPU module, then reset the CPU module or turn off and on the power supply of
the programmable controller.
[Online] [Write to PLC...]
or Power off on
Refer to Page 30, Section 3.4.1. I/O signals used in program examples are assigned as in the list on Page 30,
Section 3.4.1.
Refer to the following.
Parameter setting program Page 117, Section 7.3.1
Near-point dog method OPR program Page 119, Section 7.3.2 (1)
Count method OPR program Page 122, Section 7.3.2 (2)
Positioning control program Page 125, Section 7.3.3 (1)
Two-phase trapezoidal positioning control program Page 127, Section 7.3.3 (2)
Speed-position control switch mode program Page 129, Section 7.3.3 (3)
Speed control operation program Page 131, Section 7.3.3 (4)
Fixed-feed operation program Page 133, Section 7.3.4
JOG operation program Page 135, Section 7.3.5
Current value change program Page 137, Section 7.3.6 (1)
Speed change program Page 138, Section 7.3.6 (2)
Deviation counter clearing program Page 140, Section 7.3.6 (3)
Stop program during positioning Page 141, Section 7.3.7

7.3.1 Parameter setting program
This program sets fixed parameters and variable parameters.

Parameters described in this section can be set through GX Works2 also. ( Page 108, Section 6.3) The sequence program in this section is unnecessary when the parameters were set through GX Works2.


7.3 When Using the Module in a Standard System Configuration 7.3.1 Parameter setting program
D4 Numerator of command pulse multiplication for electronic gear
D5 Denominator of command pulse multiplication for electronic gear


SM402 Turns on for one scan once the CPU module is in the RUN status

Numerator of command pulse multiplication for electronic gear (1)
Denominator of command pulse multiplication for electronic gear (1)

7.3.2 OPR program
Programs in this section execute OPR in the near-point dog method or the count method.
This program executes OPR in the near-point dog method. Suppose that fixed parameters and variable
parameters are already set. ( Page 117, Section 7.3.1)
signal (Y2D) turns on.
Pr.10
Pr.11
Pr.12
Before executing the program, set "Near-point dog method" to "OPR method setting".
Project window [Intelligent Function Module] [QD73A1] [Switch Setting]

7.3 When Using the Module in a Standard System Configuration 7.3.2 OPR program
OP address 100pulse · OPR speed 5000pulse/s · Creep speed 500pulse/s

Servo READY signal (READY) ON
Stop signal (STOP) OFF
Upper limit signal (FLS) ON
Lower limit signal (RLS) ON
Near-point dog signal (DOG) OFF
WDT error, H/W error signal (X10) OFF
QD73A1 READY signal (X11) OFF
OPR complete signal (X13) OFF
BUSY signal (X14) OFF
Excessive error signal (X17) OFF
Error detection signal (X18) OFF
OPR start complete signal (X20) OFF
Synchronization flag (X24) ON
OPR start signal (Y20) OFF
Stop signal (Y27) OFF
PLC READY signal (Y2D) OFF
Buffer memory OPR parameters No error
D20 OP address (lower 16 bits)
D21 OP address (upper 16 bits)
D22 OPR speed (lower 16 bits)
D23 OPR speed (upper 16 bits)
D24 Creep speed (lower 16 bits)
D25 Creep speed (upper 16 bits)
M0 Fixed parameter setting memory
M34 OPR parameter setting memory
M37 OPR command pulse
SM402 Turns on for one scan once the CPU module is in the RUN status

(e) Program example

*1 OPR parameters can be set through GX Works2 also. ( Page 108, Section 6.3) The sequence program that sets OPR parameters is unnecessary when the parameters were set through GX Works2.
7.3 When Using the Module in a Standard System Configuration 7.3.2 OPR program

This program executes OPR in the count method. Suppose that fixed parameters and variable parameters are
already set. ( Page 117, Section 7.3.1)
signal (Y2D) turns on.
Pr.10
Pr.11
Pr.12
Setting for the movement amount after near-point dog
Pr.13
Before executing the program, set "Count method" to "OPR method setting".
Project window [Intelligent Function Module] [QD73A1] [Switch Setting]


(c) Execution condition
Check item Condition
Servo READY signal (READY) ON
Stop signal (STOP) OFF
Upper limit signal (FLS) ON
Lower limit signal (RLS) ON
WDT error, H/W error signal (X10) OFF
QD73A1 READY signal (X11) OFF
BUSY signal (X14) OFF
Excessive error signal (X17) OFF
Error detection signal (X18) OFF
OPR start complete signal (X20) OFF
Synchronization flag (X24) ON
OPR start signal (Y20) OFF
Stop signal (Y27) OFF
PLC READY signal (Y2D) OFF
Buffer memory OPR parameters No error
D20 OP address (lower 16 bits)
D21 OP address (upper 16 bits)
D22 OPR speed (lower 16 bits)
D23 OPR speed (upper 16 bits)
7.3 When Using the Module in a Standard System Configuration 7.3.2 OPR program
D24 Creep speed (lower 16 bits)
D25 Creep speed (upper 16 bits)
D26 Movement amount after near-point dog ON (lower 16 bits)
D27 Movement amount after near-point dog ON (upper 16 bits)
M0 Fixed parameter setting memory
M34 OPR parameter setting memory
M37 OPR command pulse
SM402 Turns on for one scan once the CPU module is in the RUN status


*1 OPR parameters can be set through GX Works2 also. ( Page 108, Section 6.3) The sequence program that sets OPR parameters is unnecessary when the parameters were set through GX Works2.

7.3.3 Major positioning control program
Programs in this section execute major positioning control.
This program executes positioning control in the absolute system. Suppose that the parameter setting and OPR
were completed. ( Page 117, Section 7.3.1, Page 119, Section 7.3.2)
Da.1
Positioning address P1 100000pulse
Da.2
Positioning speed V1 10000pulse/s
Da.3
Servo READY signal (READY) ON
Stop signal (STOP) OFF
Upper limit signal (FLS) ON
Lower limit signal (RLS) ON
WDT error, H/W error signal (X10) OFF
7.3 When Using the Module in a Standard System Configuration 7.3.3 Major positioning control program
QD73A1 READY signal (X11) ON
BUSY signal (X14) OFF
Excessive error signal (X17) OFF
Error detection signal (X18) OFF
Absolute positioning start complete signal
Synchronization flag (X24) ON
Absolute positioning start signal (Y21) OFF
Stop signal (Y27) OFF
PLC READY signal (Y2D) ON
When the positioning speed is set
exceeding " Speed limit
Pr.5
Buffer memory Positioning data No error
value", the positioning is executed
at " Speed limit value".
Pr.5
External I/O · signal · I/O signal



*1 Positioning data can be set through GX Works2 also. ( Page 109, Section 6.4) The sequence program that sets positioning data is unnecessary when the data were set through GX Works2.

(2) Two-phase trapezoidal positioning control program
This program executes two-phase trapezoidal positioning control in the absolute system. Suppose that the
parameter setting and OPR were completed. ( Page 117, Section 7.3.1, Page 119, Section 7.3.2)
Da.1
Positioning address P1 100000pulse
Da.2
Positioning speed V1 10000pulse/s
Da.3
Da.4
Positioning address P2 150000pulse
Da.5
Positioning speed V2 12000pulse/s
system.
The execution condition is the same as that of positioning control program. ( Page 125, Section 7.3.3 (1)
X35 Positioning data write command
X36 Two-phase trapezoidal positioning control start command
7.3 When Using the Module in a Standard System Configuration 7.3.3 Major positioning control program
D31 Positioning address P1 (lower 16 bits)
D32 Positioning address P1 (upper 16 bits)
D33 Positioning speed V1 (lower 16 bits)
D34 Positioning speed V1 (upper 16 bits)
D35 Positioning address P2 (lower 16 bits)
D36 Positioning address P2 (upper 16 bits)
D37 Positioning speed V2 (lower 16 bits)
D38 Positioning speed V2 (upper 16 bits)
M43 Two-phase trapezoidal positioning control start command pulse
(b)) · D30 Positioning pattern


*1 Positioning data can be set through GX Works2 also. ( Page 109, Section 6.4) The sequence program that sets positioning data is unnecessary when the data were set through GX Works2.

(3) Speed-position control switch mode program
This program switches the positioning mode to the "speed-position control switch mode". Suppose that the
parameter setting and OPR were completed. ( Page 117, Section 7.3.1, Page 119, Section 7.3.2)
Da.2
Positioning address P1 5000pulse
Positioning speed V1 1000pulse/s
Da.3
control following an external control switch command.
signal input.
Servo READY signal (READY) ON
Stop signal (STOP) OFF
Upper limit signal (FLS) ON
Lower limit signal (RLS) ON
QD73A1 READY signal (X11) ON
BUSY signal (X14) OFF
Excessive error signal (X17) OFF
7.3 When Using the Module in a Standard System Configuration 7.3.3 Major positioning control program
Error detection signal (X18) OFF
Forward start complete signal (X22) OFF
Synchronization flag (X24) ON
Forward start signal (Y22) OFF
Reverse start signal (Y23) OFF
Speed-position mode restart signal (Y26) OFF
Stop signal (Y27) OFF
Speed-position switching enable signal
PLC READY signal (Y2D) ON
When the positioning speed is set
exceeding " Speed limit
Pr.5
Buffer memory Positioning data No error
value", the positioning is executed
at " Speed limit value".
Pr.5
External I/O · signal · I/O signal



Command the start of the speed-position control switch mode.
Command the restart of the speed-position control switch mode.
*1 Variable parameters and positioning data can be set through GX Works2 also. ( Page 108, Section 6.3, Page 109, Section 6.4) The sequence program that sets variable parameters and positioning data is unnecessary when the data were set through GX Works2.

(4) Speed control operation program
This program executes speed control using the speed control function of the speed-position control switch mode.
Suppose that parameters are already set. ( Page 117, Section 7.3.1)
Da.3
Positioning speed V1 1000pulse/s
starts speed control of reverse run.
Servo READY signal (READY) ON
Stop signal (STOP) OFF
Upper limit signal (FLS) ON
Lower limit signal (RLS) ON
QD73A1 READY signal (X11) ON
BUSY signal (X14) OFF
Excessive error signal (X17) OFF
Error detection signal (X18) OFF
Forward start complete signal (X22) OFF
Reverse start complete signal (X23) OFF
7.3 When Using the Module in a Standard System Configuration 7.3.3 Major positioning control program
Synchronization flag (X24) ON
Forward start signal (Y22) OFF
Reverse start signal (Y23) OFF
Speed-position mode restart signal (Y26) OFF
Stop signal (Y27) OFF
Speed-position switching enable signal
PLC READY signal (Y2D) ON
When the positioning speed is set
exceeding " Speed limit
Pr.5
Buffer memory Positioning data No error
value", the positioning is executed
at " Speed limit value".
Pr.5
External I/O · signal · I/O signal



*1 Variable parameters and positioning data can be set through GX Works2 also. ( Page 108, Section 6.3, Page 109, Section 6.4) The sequence program that sets variable parameters and positioning data is unnecessary when the data were set through GX Works2.

7.3.4 Fixed-feed operation program
This program executes positioning in the address increasing direction according to the specified movement amount
and speed. Execute fixed-feed operation by turning on Fixed-feed start command repeatedly. Use the current value
change function and positioning start in the absolute system. Suppose that parameter setting and OPR were
completed. ( Page 117, Section 7.3.1, Page 119, Section 7.3.2)
Positioning address P1 20000pulse
Da.2
Positioning speed V1 1000pulse/s
Da.3
Servo READY signal (READY) ON
Stop signal (STOP) OFF
Upper limit signal (FLS) ON
Lower limit signal (RLS) ON
QD73A1 READY signal (X11) ON
BUSY signal (X14) OFF
Excessive error signal (X17) OFF
7.3 When Using the Module in a Standard System Configuration 7.3.4 Fixed-feed operation program
Error detection signal (X18) OFF
Absolute positioning start complete signal
Synchronization flag (X24) ON
Absolute positioning start signal (Y21) OFF
Stop signal (Y27) OFF
PLC READY signal (Y2D) ON
When the positioning speed is set
exceeding " Speed limit
Pr.5
Buffer memory Positioning data No error
value", the positioning is executed
at " Speed limit value".
Pr.5
External I/O · signal · I/O signal



*1 Positioning data can be set through GX Works2 also. ( Page 109, Section 6.4) The sequence program that sets positioning data is unnecessary when the data were set through GX Works2.

7.3.5 JOG operation program
This program executes JOG operation while a JOG start command is on. Suppose that parameters are already set.
( Page 117, Section 7.3.1)
Cd.3
reverse JOG operation.
Servo READY signal (READY) ON
Stop signal (STOP) OFF
Upper limit signal (FLS) ON
Lower limit signal (RLS) ON
QD73A1 READY signal (X11) ON
BUSY signal (X14) OFF
External stop signal (X1D) OFF
Synchronization flag (X24) ON
Forward JOG start signal (Y24) OFF
7.3 When Using the Module in a Standard System Configuration 7.3.5 JOG operation program
Reverse JOG start signal (Y25) OFF
Stop signal (Y27) OFF
PLC READY signal (Y2D) ON
When " JOG speed" is set
Cd.3
exceeding " Speed limit
Buffer memory JOG speed No error
Pr.5
Cd.3
value", the operation is executed at
" Speed limit value".
Pr.5
X42 JOG speed write command
X43 Forward JOG command
X44 Reverse JOG command
D72 JOG speed (lower 16 bits)
D73 JOG speed (upper 16 bits)



7.3.6 Control change program
(1) Current value change program
This program changes the current value to "0".
As X45 is turned on, the current value is changed.
New current value 0pulse
Cd.1

7.3 When Using the Module in a Standard System Configuration 7.3.6 Control change program

This program changes positioning speed.
As X46 is turned on, positioning speed is changed.
Cd.2
New speed value 50000pulse/s
Servo READY signal (READY) ON
Stop signal (STOP) OFF
Upper limit signal (FLS) ON
Lower limit signal (RLS) ON
WDT error, H/W error signal (X10) OFF
QD73A1 READY signal (X11) ON
BUSY signal (X14) ON
Excessive error signal (X17) OFF
Error detection signal (X18) OFF
Synchronization flag (X24) ON
Stop signal (Y27) OFF
PLC READY signal (Y2D) ON
When " New speed value" is
Cd.2
set exceeding " Speed limit
Pr.5
Buffer memory New speed value No error
Cd.2
value", the operation is executed at
" Speed limit value".
Pr.5
X46 Speed change command
D102 New speed value (lower 16 bits)
D103 New speed value (upper 16 bits)
D91 Speed change request

(d) Program example


7.3 When Using the Module in a Standard System Configuration 7.3.6 Control change program

This program clears the deviation counter to 0.
As X47 is turned on, the deviation counter is cleared to 0.
Cd.4




7.3.7 Stop program during positioning
This program stops the positioning in execution.
As X3A is turned on, the module stops the positioning in execution.
(c) Program example
Turn on Stop signal.
Turn off Stop signal.
7.3 When Using the Module in a Standard System Configuration 7.3.7 Stop program during positioning
X3A Stop command

This section introduces program examples of when the QD73A1 is used in a MELSECNET/H remote I/O network.
For details on a MELSECNET/H remote I/O network, refer to the following.
Q Corresponding MELSECNET/H Network System Reference Manual (Remote I/O network)


(2) Setting on the master station
Select "QCPU (Q mode)" for "PLC Series", and select the CPU module used for "PLC Type".
[Project] [New...]

Project window [Parameter] [Network Parameter]

7.4 When Using the Module in a Remote I/O Network
[Ethernet/CC IE/MELSECNET]

Project window [Parameter] [Network Parameter]

Project window [Parameter] [Network Parameter]
[Ethernet/CC IE/MELSECNET] button "Switch Screens"

Project window [Parameter] [Network Parameter]

turn off and on the power supply of the programmable controller.
[Online] [Write to PLC...]
or Power off on
[Ethernet/CC IE/MELSECNET] button · "XY Setting" · [Ethernet/CC IE/MELSECNET] button

(3) Setting on the remote I/O station
Select "QCPU (Q mode)" for "PLC Series", and select "QJ72LP25/QJ72BR15(RemoteI/O)" for "PLC Type".
[Project] [New...]

Project window [Intelligent Function Module] Right-click [New Module...]

7.4 When Using the Module in a Remote I/O Network

Project window [Intelligent Function Module] [QD73A1] [Switch Setting]

Rotation direction setting Set this item according to the system to be used.
Accumulated pulse setting Set this item according to the system to be used.
Multiplication setting Set this item according to the system to be used.
OPR direction setting Set this item according to the system to be used.
OPR method setting Set the near-point dog method or the count method.
Encoder I/F setting Set this item according to the system to be used.
Analog voltage resolution setting Set this item according to the system to be used.
Feed back pulse addition/subtraction setting Set this item according to the system to be used.
Deviation counter clear setting Set this item according to the system to be used.
Zero/gain adjustment mode/Normal mode setting Set "Normal mode".
[Online] [Write to PLC...]
RESET Press the switch in this direction for a while.

(4) I/O signals of the QD73A1
The following is the I/O signal assignment viewed from the master station side.
Input signal (CPU module QD73A1) Input signal (CPU module QD73A1)
X1020 WDT error, H/W error signal X1030 OPR start complete signal
X1021 QD73A1 READY signal X1031 Absolute positioning start complete signal
X1022 OPR request signal X1032 Forward start complete signal
X1023 OPR complete signal X1033 Reverse start complete signal
X1024 BUSY signal X1034 Synchronization flag
X1025 Positioning complete signal X1035
X1026 In-position signal X1036
X1027 Excessive error signal X1037
X1028 Error detection signal X1038
X1029 Overflow signal X1039
X102A Underflow signal X103A Zero/gain adjustment data writing complete
X102B Servo READY signal X103B Zero/gain adjustment change complete flag
X102C Near-point dog signal X103C Set value change complete flag
X102D External stop signal X103D Operating status of the speed-position
X102E Upper limit signal X103E
Use prohibited X102F Lower limit signal X103F
7.4 When Using the Module in a Remote I/O Network
Output signal (CPU module QD73A1) Output signal (CPU module QD73A1)
Y1020
Y1030 OPR start signal
Y1021 Y1031 Absolute positioning start signal
Y1022 Y1032 Forward start signal
Y1023 Y1033 Reverse start signal
Y1024 Y1034 Forward JOG start signal
Y1025 Y1035 Reverse JOG start signal
Y1026 Y1036 Speed-position mode restart signal
Y1027 Y1037 Stop signal
Y1028 Y1038 Error reset signal
Y1029 Y1039 Overflow reset signal
Y102A Zero/gain adjustment data writing request
signal Y103A Underflow reset signal
Y102B Zero/gain adjustment change request
signal Y103B Use prohibited
Y102C Set value change request signal Y103C Speed-position switching enable signal
Y103D PLC READY signal
Use prohibited Y102F Y103F
If a "Use prohibited" area is turned on/off through a sequence program, the QD73A1's function cannot be guaranteed.

For programs introduced in Page 149, Section 7.4.1 to Page 177, Section 7.4.7, make interlocks using data link
status of the own station and the other station as shown below.

Programs described in Page 149, Section 7.4.1, Page 177, Section 7.4.7
Refer to the following.

Near-point dog method OPR program Page 151, Section 7.4.2 (1)
Count method OPR program Page 154, Section 7.4.2 (2)
Two-phase trapezoidal positioning control program Page 159, Section 7.4.3 (2)
Speed-position control switch mode program Page 161, Section 7.4.3 (3)
Speed control operation program Page 164, Section 7.4.3 (4)
Current value change program Page 172, Section 7.4.6 (1)
Deviation counter clearing program Page 176, Section 7.4.6 (3)

7.4.1 Parameter setting program
This program sets fixed parameters and variable parameters.

Parameters described in this section can be set through GX Works2 also. ( Page 108, Section 6.3) The sequence program in this section is unnecessary when the parameters were set through GX Works2.


7.4 When Using the Module in a Remote I/O Network 7.4.1 Parameter setting program
D4 Numerator of command pulse multiplication for electronic gear
D5 Denominator of command pulse multiplication for electronic gear



Numerator of command pulse multiplication for electronic gear (1)
Denominator of command pulse multiplication for electronic gear (1)

7.4.2 OPR program
Programs in this section execute OPR in the near-point dog method or the count method.
This program executes OPR in the near-point dog method. Suppose that fixed parameters and variable
parameters are already set. ( Page 149, Section 7.4.1)
Pr.10
Pr.11
Pr.12
Before executing the program, set "Near-point dog method" to "OPR method setting".
Project window [Intelligent Function Module] [QD73A1] [Switch Setting]
7.4 When Using the Module in a Remote I/O Network 7.4.2 OPR program
OP address 100pulse · OPR speed 5000pulse/s · Creep speed 500pulse/s

Servo READY signal (READY) ON
Stop signal (STOP) OFF
Upper limit signal (FLS) ON
Lower limit signal (RLS) ON
Near-point dog signal (DOG) OFF
WDT error, H/W error signal (X1020) OFF
QD73A1 READY signal (X1021) OFF
OPR complete signal (X1023) OFF
BUSY signal (X1024) OFF
Excessive error signal (X1027) OFF
Error detection signal (X1028) OFF
OPR start complete signal (X1030) OFF
Synchronization flag (X1034) ON
OPR start signal (Y1030) OFF
Stop signal (Y1037) OFF
PLC READY signal (Y103D) OFF
Buffer memory OPR parameters No error
X22 OPR parameter setting command
D20 OP address (lower 16 bits)
D21 OP address (upper 16 bits)
D22 OPR speed (lower 16 bits)
D23 OPR speed (upper 16 bits)
D24 Creep speed (lower 16 bits)
D25 Creep speed (upper 16 bits)
M3 OPR parameter writing
M6 OPR parameter setting memory
M7 OPR command pulse
M210 Z(P).REMTO instruction completion
M211 Z(P).REMTO instruction failure
External I/O signal · I/O signal · X23 OPR command

(e) Program example

*1 OPR parameters can be set through GX Works2 also. ( Page 108, Section 6.3) The sequence program that sets OPR parameters is unnecessary when the parameters were set through GX Works2.
7.4 When Using the Module in a Remote I/O Network 7.4.2 OPR program

This program executes OPR in the count method. Suppose that fixed parameters and variable parameters are
already set. ( Page 149, Section 7.4.1)
Pr.10
Pr.11
Pr.12
Pr.13
Setting for the movement amount after near-point
Before executing the program, set "Count method" to "OPR method setting".
Project window [Intelligent Function Module] [QD73A1] [Switch Setting]

(c) Execution condition
Check item Condition
Servo READY signal (READY) ON
Stop signal (STOP) OFF
Upper limit signal (FLS) ON
Lower limit signal (RLS) ON
WDT error, H/W error signal (X1020) OFF
QD73A1 READY signal (X1021) OFF
BUSY signal (X1024) OFF
Excessive error signal (X1027) OFF
Error detection signal (X1028) OFF
OPR start complete signal (X1030) OFF
Synchronization flag (X1034) ON
OPR start signal (Y1030) OFF
Stop signal (Y1037) OFF
PLC READY signal (Y103D) OFF
Buffer memory OPR parameters No error
X22 OPR parameter setting command
D20 OP address (lower 16 bits)
D21 OP address (upper 16 bits)
7.4 When Using the Module in a Remote I/O Network 7.4.2 OPR program
D22 OPR speed (lower 16 bits)
D23 OPR speed (upper 16 bits)
D24 Creep speed (lower 16 bits)
D25 Creep speed (upper 16 bits)
D26 Movement amount after near-point dog ON (lower 16 bits)
D27 Movement amount after near-point dog ON (upper 16 bits)
M3 OPR parameter writing
M6 OPR parameter setting memory
M7 OPR command pulse
M210 Z(P).REMTO instruction completion
M211 Z(P).REMTO instruction failure
External I/O signal · I/O signal · X24 OPR command


*1 OPR parameters can be set through GX Works2 also. ( Page 108, Section 6.3) The sequence program that sets OPR parameters is unnecessary when the parameters were set through GX Works2.

7.4.3 Major positioning control program
Programs in this section execute major positioning control.
This program executes positioning control in the absolute system. Suppose that the parameter setting and OPR
were completed. ( Page 149, Section 7.4.1, Page 151, Section 7.4.2)
Da.1
Positioning address P1 100000pulse
Da.2
Positioning speed V1 10000pulse/s
Da.3
Servo READY signal (READY) ON
Stop signal (STOP) OFF
Upper limit signal (FLS) ON
Lower limit signal (RLS) ON
WDT error, H/W error signal (X1020) OFF
7.4 When Using the Module in a Remote I/O Network 7.4.3 Major positioning control program
QD73A1 READY signal (X1021) ON
BUSY signal (X1024) OFF
Excessive error signal (X1027) OFF
Error detection signal (X1028) OFF
Absolute positioning start complete signal
Synchronization flag (X1034) ON
Absolute positioning start signal (Y1031) OFF
Stop signal (Y1037) OFF
PLC READY signal (Y103D) ON
When the positioning speed is set
exceeding " Speed limit
Pr.5
Buffer memory Positioning data No error
value", the positioning is executed
at " Speed limit value".
Pr.5
External I/O · signal · I/O signal



*1 Positioning data can be set through GX Works2 also. ( Page 109, Section 6.4) The sequence program that sets positioning data is unnecessary when the data were set through GX Works2.

(2) Two-phase trapezoidal positioning control program
This program executes two-phase trapezoidal positioning control in the absolute system. Suppose that the
parameter setting and OPR were completed. ( Page 149, Section 7.4.1, Page 151, Section 7.4.2)
Da.1
Positioning address P1 100000pulse
Da.2
Positioning speed V1 10000pulse/s
Da.3
Da.4
Positioning address P2 150000pulse
Da.5
Positioning speed V2 12000pulse/s
system.
The execution condition is the same as that of positioning control program. ( Page 157, Section 7.4.3 (1)
X27 Positioning data write command
X28 Two-phase trapezoidal positioning control start command
7.4 When Using the Module in a Remote I/O Network 7.4.3 Major positioning control program
D32 Positioning address P1 (lower 16 bits)
D33 Positioning address P1 (upper 16 bits)
D34 Positioning speed V1 (lower 16 bits)
D35 Positioning speed V1 (upper 16 bits)
D36 Positioning address P2 (lower 16 bits)
D37 Positioning address P2 (upper 16 bits)
D38 Positioning speed V2 (lower 16 bits)
D39 Positioning speed V2 (upper 16 bits)
M15 Positioning data writing
M45 Two-phase trapezoidal positioning control start command pulse
M230 Z(P).REMTO instruction completion
M231 Z(P).REMTO instruction failure
(b)) · D31 Positioning pattern


*1 Positioning data can be set through GX Works2 also. ( Page 109, Section 6.4) The sequence program that sets positioning data is unnecessary when the data were set through GX Works2.

(3) Speed-position control switch mode program
This program switches the positioning mode to the "speed-position control switch mode". Suppose that the
parameter setting and OPR were completed. ( Page 149, Section 7.4.1, Page 151, Section 7.4.2)
Da.2
Positioning address P1 5000pulse
Positioning speed V1 1000pulse/s
Da.3
control following an external control switch command.
signal input.
Servo READY signal (READY) ON
Stop signal (STOP) OFF
Upper limit signal (FLS) ON
Lower limit signal (RLS) ON
QD73A1 READY signal (X1021) ON
BUSY signal (X1024) OFF
Excessive error signal (X1027) OFF
7.4 When Using the Module in a Remote I/O Network 7.4.3 Major positioning control program
Error detection signal (X1028) OFF
Forward start complete signal (X1032) OFF
Synchronization flag (X1034) ON
Forward start signal (Y1032) OFF
Reverse start signal (Y1033) OFF
Speed-position mode restart signal
Stop signal (Y1037) OFF
Speed-position switching enable signal
PLC READY signal (Y103D) ON
When the positioning speed is set
exceeding " Speed limit
Pr.5
Buffer memory Positioning data No error
value", the positioning is executed
at " Speed limit value".
Pr.5
External I/O · signal · I/O signal

X29 Variable parameter change command
X2A Positioning data write command
X2B Speed-position control positioning start command
X2D Speed-position control positioning restart command
D42 Positioning address P1 (lower 16 bits)
D43 Positioning address P1 (upper 16 bits)
D44 Positioning speed V1 (lower 16 bits)
D45 Positioning speed V1 (upper 16 bits)
M20 Variable parameter change
M21 Positioning data writing
M50 Speed-position control positioning start command pulse
M52 Speed-position control positioning restart command pulse
M240 Z(P).REMTO instruction completion
M241 Z(P).REMTO instruction failure
M242 Z(P).REMTO instruction completion
M243 Z(P).REMTO instruction failure
D40 Positioning mode

(d) Program example

Command the start of the speed-position control switch mode.
Command the restart of the speed-position control switch mode.
7.4 When Using the Module in a Remote I/O Network 7.4.3 Major positioning control program
*1 Variable parameters and positioning data can be set through GX Works2 also. ( Page 108, Section 6.3, Page 109, Section 6.4) The sequence program that sets variable parameters and positioning data is unnecessary when the data were set through GX Works2.

This program executes speed control using the speed control function of the speed-position control switch mode.
Suppose that parameters are already set. ( Page 149, Section 7.4.1)
Da.3
Positioning speed V1 1000pulse/s
speed control of reverse run.
Servo READY signal (READY) ON
Stop signal (STOP) OFF
Upper limit signal (FLS) ON
Lower limit signal (RLS) ON
QD73A1 READY signal (X1021) ON
BUSY signal (X1024) OFF
Excessive error signal (X1027) OFF
Error detection signal (X1028) OFF
Forward start complete signal (X1032) OFF
Reverse start complete signal (X1033) OFF
Synchronization flag (X1034) ON
Forward start signal (Y1032) OFF
Reverse start signal (Y1033) OFF
Speed-position mode restart signal
Stop signal (Y1037) OFF
Speed-position switching enable signal
PLC READY signal (Y103D) ON
When the positioning speed is set
exceeding " Speed limit
Pr.5
Buffer memory Positioning data No error
value", the positioning is executed
at " Speed limit value".
Pr.5
External I/O · signal · I/O signal

(c) Device used by the user
Device Description
X2E Variable parameter change command
X2F Positioning data write command
X30 Forward run command
X31 Reverse run command
D48 Positioning speed V1 (lower 16 bits)
D49 Positioning speed V1 (upper 16 bits)
M25 Variable parameter change
M26 Positioning data writing
M30 Speed control command pulse
M250 Z(P).REMTO instruction completion
M251 Z(P).REMTO instruction failure
M252 Z(P).REMTO instruction completion
M253 Z(P).REMTO instruction failure
7.4 When Using the Module in a Remote I/O Network 7.4.3 Major positioning control program
D46 Positioning mode


*1 Variable parameters and positioning data can be set through GX Works2 also. ( Page 108, Section 6.3, Page 109, Section 6.4) The sequence program that sets variable parameters and positioning data is unnecessary when the data were set through GX Works2.

7.4.4 Fixed-feed operation program
This program executes positioning in the address increasing direction according to the specified movement amount
and speed. Execute fixed-feed operation by turning on Fixed-feed start command repeatedly. Use the current value
change function and positioning start in the absolute system. Suppose that parameter setting and OPR were
completed. ( Page 149, Section 7.4.1, Page 151, Section 7.4.2)
Positioning address P1 20000pulse
Da.2
Positioning speed V1 1000pulse/s
Da.3
Servo READY signal (READY) ON
Stop signal (STOP) OFF
Upper limit signal (FLS) ON
Lower limit signal (RLS) ON
QD73A1 READY signal (X1021) ON
BUSY signal (X1024) OFF
Excessive error signal (X1027) OFF
7.4 When Using the Module in a Remote I/O Network 7.4.4 Fixed-feed operation program
Error detection signal (X1028) OFF
Absolute positioning start complete signal
Synchronization flag (X1034) ON
Absolute positioning start signal (Y1031) OFF
Stop signal (Y1037) OFF
PLC READY signal (Y103D) ON
When the positioning speed is set
exceeding " Speed limit
Pr.5
Buffer memory Positioning data No error
value", the positioning is executed
at " Speed limit value".
Pr.5
External I/O · signal · I/O signal

X32 Fixed-feed positioning data write command
X33 Fixed-feed start command
D50 Positioning address P1 (lower 16 bits)
D51 Positioning address P1 (upper 16 bits)
D52 Positioning speed V1 (lower 16 bits)
D53 Positioning speed V1 (upper 16 bits)
D100 New current value (lower 16 bits)
D101 New current value (upper 16 bits)
D104 Current value change request
D106 Current value change result check
M35 Variable parameter change
M55 Fixed-feed positioning data write command pulse
M56 Current value change result reading
M260 Z(P).REMTO instruction completion
M261 Z(P).REMTO instruction failure
M262 Z(P).REMTO instruction completion
M263 Z(P).REMTO instruction failure
M264 Z(P).REMTO instruction completion
M265 Z(P).REMTO instruction failure
M266 Z(P).REMFR instruction completion
M267 Z(P).REMFR instruction failure

(4) Program example

7.4 When Using the Module in a Remote I/O Network 7.4.4 Fixed-feed operation program
Command to check the current value change again when it is incomplete.
*1 Positioning data can be set through GX Works2 also. ( Page 109, Section 6.4) The sequence program that sets positioning data is unnecessary when the data were set through GX Works2.

This program executes JOG operation while a JOG start command is on. Suppose that parameters are already set.
( Page 149, Section 7.4.1)
Cd.3
reverse JOG operation.
Servo READY signal (READY) ON
Stop signal (STOP) OFF
Upper limit signal (FLS) ON
Lower limit signal (RLS) ON
QD73A1 READY signal (X1021) ON
BUSY signal (X1024) OFF
External stop signal (X102D) OFF
Synchronization flag (X1034) ON
Forward JOG start signal (Y1034) OFF
Reverse JOG start signal (Y1035) OFF
Stop signal (Y1037) OFF
PLC READY signal (Y103D) ON
When " JOG speed" is set
Cd.3
exceeding " Speed limit
Buffer memory JOG speed No error
Pr.5
Cd.3
value", the operation is executed at
" Speed limit value".
Pr.5
X34 JOG speed write command
X35 Forward JOG command
X36 Reverse JOG command
D55 JOG speed (lower 16 bits)
D56 JOG speed (upper 16 bits)
M60 JOG speed writing
M270 Z(P).REMTO instruction completion
M271 Z(P).REMTO instruction failure

(4) Program example


7.4 When Using the Module in a Remote I/O Network 7.4.5 JOG operation program

This program changes the current value to "0".
As X37 is turned on, the current value is changed.
New current value 0pulse
Cd.1
WDT error, H/W error signal (X1020) OFF
BUSY signal (X1024) OFF
Error detection signal (X1028) OFF
Synchronization flag (X1034) ON
X37 Current value change command
D100 New current value (lower 16 bits)
D101 New current value (upper 16 bits)
D104 Current value change request
D106 Current value change result check
M70 Variable parameter change
M71 Positioning data change
M280 Z(P).REMTO instruction completion
M281 Z(P).REMTO instruction failure
M282 Z(P).REMTO instruction completion
M283 Z(P).REMTO instruction failure
M284 Z(P).REMFR instruction completion
M285 Z(P).REMFR instruction failure
I/O signal

(d) Program example

Command to check the current value change again when it is incomplete.

7.4 When Using the Module in a Remote I/O Network 7.4.6 Control change program

This program changes positioning speed.
As X38 is turned on, positioning speed is changed.
Cd.2
New speed value 50000pulse/s
Servo READY signal (READY) ON
Stop signal (STOP) OFF
Upper limit signal (FLS) ON
Lower limit signal (RLS) ON
WDT error, H/W error signal (X1020) OFF
QD73A1 READY signal (X1021) ON
BUSY signal (X1024) ON
Excessive error signal (X1027) OFF
Error detection signal (X1028) OFF
Synchronization flag (X1034) ON
Stop signal (Y1037) OFF
PLC READY signal (Y103D) ON
When " New speed value" is
Cd.2
set exceeding " Speed limit
Pr.5
Buffer memory New speed value No error
Cd.2
value", the operation is executed at
" Speed limit value".
Pr.5
X38 Speed change command
D102 New speed value (lower 16 bits)
D103 New speed value (upper 16 bits)
D105 Speed change request
D107 Speed change result check
M76 Speed change request check
M290 Z(P).REMTO instruction completion
M291 Z(P).REMTO instruction failure
M292 Z(P).REMTO instruction completion
M293 Z(P).REMTO instruction failure
M294 Z(P).REMFR instruction completion
M295 Z(P).REMFR instruction failure

(d) Program example

Command to check the speed change again when it is incomplete.

7.4 When Using the Module in a Remote I/O Network 7.4.6 Control change program

This program clears the deviation counter to 0.
As X39 is turned on, the deviation counter is cleared to 0.
Cd.4



Read the completion of deviation counter clear from the QD73A1.
Command to check the deviation counter clear again when it is incomplete.

7.4.7 Stop program during positioning
This program stops the positioning in execution.
As X3A is turned on, the module stops the positioning in execution.
(c) Program example
Turn on Stop signal.
Turn off Stop signal.
7.4 When Using the Module in a Remote I/O Network 7.4.7 Stop program during positioning
X3A Stop command

This chapter describes OPR control.
In "OPR control", a starting point (or OP) of major positioning control is set, and positioning is executed toward the
original point. Use this control to return a machine system at a position other than its OP to the OP when the QD73A1
turned on OPR request signal (X12) at power-on, or after a positioning stop.
OPR request signal (X12) turns on at the following timings.
(only when "0: Clear the deviation counter when the servo ready signal is OFF." is selected for "Deviation
counter clear setting" in the switch setting)
The QD73A1 has two OPR methods so that an OP can be established in the optimum method (determination of
the OP position, or OPR completion) depending on the positioning system configuration or the application.
Set an OPR method in the switch setting. For the setting method, refer to the following.
Page 100, Section 6.2
As the near-point dog turns on, deceleration starts. (The speed decelerates
to " Creep speed".) After the near-point dog turned off, the OPR is
Pr.12
completed at the operation stop with the first Zero signal*1, specifying the
Section 8.2
position as the OP.
As the near-point dog turns on, deceleration starts and the machine moves at
" Creep speed". From the position where the near-point dog turned on,
Pr.12
the machine moves the distance set in " Setting for the movement
Pr.13
Section 8.3
amount after near-point dog ON". Then, the OPR is completed at the
operation stop with the first Zero signal*1.
*1 Signal that is output as a single pulse at one motor revolution (e.g. Z-phase signal output from the drive unit)
: Necessary : Necessary as required
Upper limit signal
OPR method
Near-point dog signal
(DOG) Zero signal
(FLS)/Lower limit signal
(RLS)

8.2 Near-point Dog Method
This section describes the operation overview of an OPR method, "near-point dog method".
OPR starts.
(Acceleration starts in the direction set on "OPR direction setting" in the switch setting, and the machine moves at
" OPR speed".)
Pr.11
2 As the near-point dog turns on, deceleration starts.
3 The machine decelerates to " Creep speed", and subsequently moves at the creep speed.
Pr.12
(The near-point dog must be on during the deceleration. If the near-point dog turns off during the deceleration, the
OPR is completed at the first Zero signal input after the near-point dog OFF.)
4 Output from the QD73A1 stops at the first Zero signal after the near-point dog OFF.
5 Returning operation is executed by the coasting amount after Zero signal input, then OPR complete signal (X13) turns
on and OPR request signal (X12) turns off.
As in the following figure, after the near-point dog turned off, the position of the first Zero signal from the pulse
generator becomes the OP.

Returning operation is executed by the coasting amount after Zero signal input, and the OPR is completed.
Adjust the position where the near-point dog turns off so that it is closer to the center of Zero signals. If the position overlaps with Zero signal, the OPR stop position may deviate by one servomotor rotation.

(a) Another OPR after the completion of OPR
If another OPR is attempted after the completion of OPR, the error "OPR complete signal ON at start" (error
code: 84) occurs.
If the position where the near-point dog turns off is close to Zero signal, the Zero signal may be misread,
resulting in deviation of OP by one servomotor rotation. Adjust the position where the near-point dog turns off
so that it becomes closer to the center of Zero signals.
If an OPR start is attempted from the near-point dog ON position, the error "Near-point dog signal ON at start"
(error code: 74) occurs.
Return the workpiece to a position away from the near-point dog using JOG operation, then execute OPR.
If the CPU module was reset after OPR control was completed and the near-point dog turned off, another OPR
can be started; however, the operation is executed at " OPR speed" to the position of the upper limit
Pr.11
switch (FLS) or the lower limit switch (RLS) since there is no near-point dog placed in the OPR direction.
If the workpiece moved outside the stroke limit range, the error "Outside the stroke limit range" (error code:
dog is placed on the OPR direction.

8.3 Count Method
This section describes the operation overview of an OPR method, "count method".
OPR in the count method can be executed also in case of the following.

(Acceleration starts in the direction set on "OPR direction setting" in the switch setting, and the machine moves at
2 As the near-point dog turns on, deceleration starts.
3 The machine decelerates to " Creep speed", and subsequently moves at the creep speed.
4 Output from the QD73A1 stops at the first Zero signal after the machine moved by the amount set in " Setting
5 Returning operation is executed by the coasting amount after Zero signal input, then OPR complete signal (X13) turns
As in the following figure, after the machine moved the amount set in " Setting for the movement amount
after near-point dog ON", the position of the first Zero signal from the pulse generator becomes the OP.

Pr.11 OPR speed Deceleration at the near-point dog ON
Pr.13 Setting for the movement amount after near-point dog
Returning operation is executed by the coasting amount after Zero signal input, and the OPR is completed.
Adjust Setting for the movement amount after near-point dog ON so that it is closer to the center of Zero signals. If it overlaps with Zero signal, the OPR stop position may deviate by one servomotor rotation. One servomotor

(a) Setting for the movement amount after near-point dog ON
Pr.13
If " Setting for the movement amount after near-point dog ON" is smaller than the deceleration distance
Pr.13
from " OPR speed" to " Creep speed", the error "Setting for the movement amount after near-point
Pr.11 Pr.12
dog ON Outside the setting range" (error code: 22) occurs, and the OPR does not start.
In addition, if the position after the move according to " Setting for the movement amount after near-point
Pr.13
dog ON" is close to Zero signal, the Zero signal may be misread, resulting in deviation of OP by one
servomotor rotation. Set " Setting for the movement amount after near-point dog ON" so that the position
Pr.13
after the move becomes closer to the center of Zero signals.
The operation is as follows.
1 OPR starts.
Pr.13 Setting for the movement
The workpiece moves in the direction that is
amount after near-point dog ON
opposite from the specified OPR direction at
" OPR speed".
Pr.11
3 As the near-point dog turns off, deceleration
starts.
4 After an operation stop, OPR starts in the
specified OPR direction.
As the near-point dog turns on, the
workpiece moves the amount set in
" Setting for the movement amount
Pr.13
after near-point dog ON". Then, the OPR is
completed at the first Zero signal after the
move.
If the workpiece moved outside the stroke limit range, the error "Outside the stroke limit range" (error code:
dog is placed on the OPR direction.
Near-point dog · Zero signal

8.4 Operation Timing and Processing Time of OPR Control
This section explains the operation timing and processing time of OPR control.
OFF
(Y20)
ON
OFF
(X14)
ON
OPR start complete signal
OFF
t3 OPR request signal
(X12)
OFF
ON
OFF
(X13)
*1 This is an indication of internal commands, and does not match with the actual analog output waveform.
The following values apply to t1 to t3.
0.7 to 1.2ms 0 to 0.5ms 0 to 0.5ms
8.4 Operation Timing and Processing Time of OPR Control

For the QD73A1 to execute OPR, OPR parameters must be set. If the data are not set, default values are used for
control.
The default values are set also when the power was turned off and on, or when the CPU module was reset.
The following table lists the OPR parameters to be set, setting condition, and check timing.
Setting item Setting range Default value Setting
Check timing of the
memory
condition
set data
address
(decimal)
OP address -2147483648 to
2147483647 pulse 0 pulse
Pr.10
OPR speed 1 to 4000000pulse/s 10000pulse/s 42
Pr.11
Creep speed 1 to 4000000pulse/s 1000pulse/s 44
When OPR start signal
Pr.12
(Y20) is turned on
must be off.
2147483647pulse 75 pulse 46
Pr.13
ON (set only for the

CHAPTER 9 MAJOR POSITIONING CONTROL
"Major positioning control" is executed using "variable parameters" and "positioning data" stored in the QD73A1. The
position control mode or the speed-position control switch mode is executed by setting a variable parameter
" Positioning mode" and a positioning data item " Positioning pattern" and by starting the positioning data.
Pr.9 Da.1
The following types of "major positioning control" are executed when a positioning start signal (Y21 to Y23) is turned
on.
Positioning is executed from the current
position to a specified position at a specified
speed.
Section 9.6.1 (1)
Pr.9
Da.1
Positioning is executed to the address
specified with " Positioning address
Da.2
P1" at " Positioning speed V1", then to
Da.3
the address specified with " Positioning
Da.4
9.1 Overview of Major Positioning Control
address P2" at " Positioning speed V2"
Da.5
Section 9.6.1 (2)
by one positioning start signal.
Pr.9
Da.1
Operation starts according to the positioning
speed set beforehand by one positioning start
signal, then the operation switches to position
control by Speed-position switching
command signal (CHANGE).
If the operation stopped by Stop signal after
the input of Speed-position switching
command signal (CHANGE), the positioning
Speed-position control switch mode
can be continued by requesting a restart.
Section 9.6.2
In addition, the positioning address
(movement amount) can be changed if it is
before the input of Speed-position switching
command signal (CHANGE).
Pr.9
Da.1

This section describes "positioning data" required for "major positioning control".
Positioning pattern Select a control pattern of major positioning from "positioning control" or "two-phase trapezoidal
Da.1
positioning control".
Da.2
Positioning address P1 Set the address that is the destination of major positioning control.
Da.3
Positioning speed V1 Set the command speed of major positioning control.
In two-phase trapezoidal positioning control, set the destination address of after the move to the
Da.4
address set to " Positioning address P1".
Da.2
In two-phase trapezoidal positioning control, set the command speed to move to the address set to
Da.5
" Positioning address P2".
Da.4
The settings of to depend on " Positioning mode" and " Positioning pattern".
Da.1 Da.5 Pr.9 Da.1
( Page 187, Section 9.3)
For details on "sub functions" that can be combined with major positioning control, refer to the following.
Page 29, Section 3.3 (4)
For details on each sub function, refer to the following.
Page 208, CHAPTER 11
Positioning address P2 · Positioning speed V2

9.3 Relation Between Each Control and Positioning Data
Setting items and details of positioning data depend on the settings of a positioning data item " Positioning
Da.1
pattern" and a variable parameter " Positioning mode".
Pr.9
The following table shows the positioning data setting items for each type of control.
Pr.9
0: Position control mode 1: Speed-position control
switch mode
Da.1
Da.2
Da.3
Da.4
Da.5
: Set always
: Set only for two-phase trapezoidal positioning control
: Setting not required (The setting is ignored. Use the default value or a value that does not cause an error.)
For details on each control and setting, refer to the following.
Page 190, Section 9.6
9.3 Relation Between Each Control and Positioning Data

This section describes systems to specify a position for control using positioning data.
Positioning is executed using the current address as the start address and the address set with
" Positioning address P1" as the end address.
Da.2
End point Address 100
OP (Reference point) 100 150 300
A point B point C point
Within the stroke limit range
Positioning is executed from the current address (start address) by the movement amount set in
" Positioning address P1".
Da.2
The moving direction depends on the start signal to turn on: Forward start signal (Y22) or Reverse start signal
(Y23).
End point Movement amount
Movement amount +50 Movement amount -100
OP (Reference point) 100
Within the stroke limit range

9.5 Checking the Current Value
In the QD73A1, two types of address are used to indicate position.
The two types of address, "current feed value" and "actual current value", are stored to the monitor data area.
They can be monitored when necessary.
Md.1
Md.2
0.5ms
is stored as an actual current value (the number of feedback pulses).
(Actual current value = Current feed value - Accumulated pulses in the deviation
When the value stored in " Current feed value" or " Actual current value" is used for control, the
Md.1 Md.2
update timing of the buffer memory area may be in error by 0.5ms.
9.5 Checking the Current Value
Current feed value · Actual current value · counter)

This section describes details on the position control mode (positioning control and two-phase trapezoidal positioning
control) and the speed-position control switch mode.
(a) Dwell-time function
The QD73A1 does not have the dwell-time function. When dwell-time is necessary, start the next operation
using the timer in the sequence program once the specified period of time passed after Positioning complete
signal (X15) turned on.
The QD73A1 controls the current value during positioning. If incremental system positioning or combined
positioning of incremental system and absolute system is repeated, the workpiece may move outside the
stroke limit range and an error may occur. If an error occurs, change the current value to the one within the
stroke limit range.
Refer to the following.
Page 230, CHAPTER 12

9.6.1 Position control mode
In the position control mode, positioning is executed toward the positioning address specified with positioning data at
the specified speed.
There are two types of control in the position control mode.
There are two systems to specify a positioning address: the absolute system in which a positioning end address is
specified and the incremental system in which movement amount from a start address to an end address is specified.
Specify the absolute system or the incremental system using one of the following start signals.
Absolute positioning start signal (Y21) Positioning start in the absolute system
Forward start signal (Y22) Forward start in the incremental system (address increasing)
Reverse start signal (Y23) Reverse start in the incremental system (address
Set a positioning address and positioning speed for this type of control. Absolute system positioning or
incremental system positioning is executed by a positioning start command.
The operation is as follows.
Da.2
9.6 Details of Major Positioning Control 9.6.1 Position control mode
Da.3
OFF
ON
(X14)
OFF
ON
(X15)
OFF
Executed by the QD73A1

The following table lists the positioning data to be set, setting condition, and check timing.
Setting item Setting range Default
value Setting condition Check timing
memory
of the set data
address
(decimal)
0 The data can be set anytime.
Da.1
rise (ON) of a positioning
Absolute system:
start signal (Y21 to Y23) are
used for the operation. If the
data are written when BUSY
Da.2
Incremental system:
signal (X14) is on, the data
Y23) is turned on
will be accepted at the rise
(ON) of the next positioning
V1 1 to 4000000pulse/s 0pulse/s 304
Da.3
start signal (Y21 to Y23).
Set positioning addresses (P1 and P2) and positioning speed (V1 and V2) for this type of control. Positioning of
the absolute system or the incremental system is executed first to the positioning address P1 at the positioning
speed V1, then to the positioning address P2 at the positioning speed V2 by one positioning start command.
The operation is as follows.
Positioning address P1 Da.2 Positioning address P2 Da.4
Positioning speed V1 Da.3
Positioning speed V2 Da.5
OFF
ON
(X14)
OFF
ON
(X15)
OFF
Executed by the QD73A1

(b) Deceleration distance
If the movement amount from the positioning address P1 to the positioning address P2 is less than the
deceleration distance from the positioning address P1, two-phase trapezoidal positioning control is not formed.
In this case, the deceleration from the positioning speed V1 starts before the workpiece reaches the positioning
address P1 so that the operation stops at the positioning address P2.
Positioning speed V1 Da.3
Positioning speed V1 Da.3
Da.5 Positioning speed V2
Da.5 Positioning speed V2
Deceleration stop fails.
Da.2
Da.2
Da.4
Da.4
Deceleration distance from " Positioning address P1"
Da.2
To execute two-phase trapezoidal positioning, set the positioning data so that the deceleration distance from
the positioning address P1 does not exceed the movement amount from the positioning address P1 to the
positioning address P2.
To execute two-phase trapezoidal positioning control in the absolute system, the positioning direction from
" Positioning address P1" to " Positioning address P2" and the positioning direction from the
Da.2 Da.4
current value to " Positioning address P1" must be the same.
Da.2
9.6 Details of Major Positioning Control 9.6.1 Position control mode
If not, the error "Two-phase trapezoidal positioning address error" (error code: 31) occurs, and the two-phase
trapezoidal positioning control does not start.
the positioning address P1
Da.2 Da.4
Positioning address
Address increasing
Address decreasing
P1
P2
direction
direction
10000 5000 Error Positioning executed
10000 15000 Positioning executed Error
Any value within the setting range can be set in " Positioning speed V1" and " Positioning speed
Da.3 Da.5
V2" regardless the relation between the two setting values.

The following table lists the positioning data to be set, setting condition, and check timing.
Setting item Setting range Default
value Setting condition Check timing
memory
of the set data
address
(decimal)
Da.1
Absolute system:
The data can be set anytime.
Da.2
Incremental system:
rise (ON) of a positioning
start signal (Y21 to Y23) are
used for the operation. If the
V1 1 to 4000000pulse/s 0pulse/s 304
Da.3
data are written when BUSY
signal (X14) is on, the data
Y23) is turned on
Absolute system:
will be accepted at the rise
(ON) of the next positioning
start signal (Y21 to Y23).
Da.4
Incremental system:
V2 1 to 4000000pulse/s 0pulse/s 308
Da.5

9.6.2 Speed-position control switch mode
In the speed-position control switch mode, pulses that correspond to the specified positioning speed are output in the
direction specified by a start signal. Then, once Speed-position switching command signal (CHANGE) is input, the
operation switches to position control with the specified movement amount.
The speed-position control switch mode operates with the incremental system in which movement amount from a start
address to an end address is specified.
Specify a forward start or a reverse start using one of the following signals.
Forward start signal (Y22) Forward start (address increasing)
Reverse start signal (Y23) Reverse start (address decreasing)
To switch the operation from speed control to position control, Speed-position switching enable signal (Y2C) must
be turned on before inputting Speed-position switching command signal (CHANGE).
If Speed-position switching command signal (CHANGE) is input when Speed-position switching enable signal
(Y2C) is off, the speed control continues without being switched to position control. The operation switches to
position control when Speed-position switching command signal (CHANGE) is input after Speed-position
switching enable signal (Y2C) was turned on.
The operation is as follows.
Movement amount set to " Positioning address P1" Da.2
9.6 Details of Major Positioning Control 9.6.2 Speed-position control switch mode
Positioning speed V1 Da.3
Speed control Position control
(Y22, Y23)
OFF
ON
(X14)
OFF
ON
OFF
ON
OFF
ON
Speed-position switching command signal (CHANGE)
Current feed value Md.1 P1
Executed by the QD73A1

Md.1 Md.2
In " Current feed value" and " Actual current value", 0 is set at the start of the speed-position control
Md.1 Md.2
switch mode, and the settings are not updated during speed control.
They are updated once the operation switched to position control by the input of Speed-position switching
command signal (CHANGE).
In the speed-position control switch mode, operation switches to position control by an input of Speed-position
switching command signal (CHANGE) during speed control. The process from the signal input to the completion
of switchover to position control takes some time, resulting in a positioning error by pulses output during the
process.
The process time varies by approximately 2ms including the response delay of Speed-position switching
command signal (CHANGE).

Movement amount set to " Positioning address P1" Da.2
Da.2
Set " Positioning address P1" so that its setting value becomes greater than the value of the distance
Da.2
obtained using the following formula. If not, the positioning stops exceeding the specified movement amount.

Distance to decelerate from " Positioning speed V1" Da.3
switchover
A speed-position control switchover cannot be performed in two-phase trapezoidal positioning control.

Input Speed-position switching command signal (CHANGE) at the area where the speed is stable (constant speed status). When a servomotor is used, the actual movement amount after the switchover to position control is "Set movement amount + Accumulated pulse amount". If the signal is input during acceleration or deceleration, the operation stop position varies due to the variation in the accumulated pulse amount.
The following table lists the parameter and positioning data to be set, setting condition, and check timing.
Set other parameters if necessary.
Setting item Setting range Default
value Setting condition Check timing
memory
of the set data
address
(decimal)
The data can be set
anytime.
Pr.9
the rise (ON) of a
0 to 2147483647pulse 0pulse 302
Da.2
(Y22, Y23) are used for
the operation. If the data
are written when BUSY
signal (X14) is on, the
data will be accepted at
speed V1 1 to 4000000pulse/s 0pulse/s 304
Da.3
the rise (ON) of the next
(Y22, Y23).
9.6 Details of Major Positioning Control 9.6.2 Speed-position control switch mode
The movement amount for position control can be changed during speed control of the speed-position control
switch mode.
Set the new movement amount in " New speed-position movement amount" using a sequence program
Cd.6
during speed control. The value in " New speed-position movement amount" is reflected as the movement
Cd.6
amount for position control at the input of Speed-position switching command signal (CHANGE).

The operation is as follows.
v Speed control Position control
Movement amount (P1) set to " New speed-position movement amount"
Cd.6
Movement amount can be changed
Movement amount cannot be changed
Speed-position switching command signal (CHANGE)
The change after Speed-position switching command signal (CHANGE) was turned on is ignored.
Cd.6 New speed-position
P1 becomes the movement amount in position control.
Cd.6
The setting is cleared to 0 when the next operation starts.
The following table lists the data to be set, setting condition, and check timing.
Setting item Setting range Default
value Setting condition Check timing of
memory
the set data
address
(decimal)
The data can be set when
BUSY signal (X14) is on
At the input of
during speed control, and
Cd.6
besides before the input of
command signal (CHANGE).
If " New speed-position movement amount" is a value that moves the workpiece outside the stroke limit
Cd.6
range, the error "Movement outside the stroke limit range" (error code: 87) occurs at the input of Speed-
position switching command signal (CHANGE), and the set new movement amount is ignored. (The value in
" Positioning address P1" (movement amount) is used.)
Da.2
Operation can stay as speed control in the speed-position control switch mode when one of the following
conditions is satisfied.
During speed control, the stroke limit function cannot be used since " Current feed value" is not updated. A
Md.1
stroke range is from the lower limit switch (RLS) to the upper limit switch (FLS).

9.7 Operation Timing and Processing Time of Major Positioning Control
This section explains the operation timing and processing time of major positioning control.
Major positioning control*1
OFF
OFF
(X14)
OFF
ON
(X15)
OFF
ON
Positioning start complete signal
ON
OFF
(X13)
*1 This is an indication of internal commands, and does not match with the actual analog output waveform.
The following values apply to t1 to t3.
9.7 Operation Timing and Processing Time of Major Positioning Control
0.7 to 1.2ms 0 to 0.5ms 0 to 0.5ms

The QD73A1's "JOG operation" can move the workpiece without using positioning data, but according to signal inputs
and specified movement amount. Use this function for the following.
"JOG operation" moves the workpiece in the specified direction at the specified speed while Forward JOG start signal
(Y24) or Reverse JOG start signal (Y25) is on.
turned off

10.1 Operation of JOG Operation
Once JOG speed is set and while a JOG start signal is turned on through a sequence program, the QD73A1 executes
JOG operation in the specified direction by outputting analog voltage to the drive unit.
Choose forward run or reverse run using JOG start signals.
Forward JOG start signal (Y24) Address increasing direction
Reverse JOG start signal (Y25) Address decreasing direction
The following is an example of JOG operation.
1 As a JOG start signal is turned on, acceleration starts in the specified direction according to " Acceleration time".
Pr.6
BUSY signal (X14) turns on at this time.
2 As the accelerating operation reaches the speed set in " JOG speed", the move continues maintaining the
Cd.3
speed. The workpiece moves at the constant speed between 2 to 3 in the graph below.
3 As the JOG start signal is turned off, deceleration starts from the speed set in " JOG speed" according to
Cd.3
" Deceleration time".
Pr.7
4 As the speed reaches 0, the operation stops. BUSY signal (X14) turns off at this time.
JOG speed Cd.3
Deceleration according to " Deceleration time" Acceleration according to " Acceleration time"
Pr.7 Pr.6
1 2 3 4
10.1 Operation of JOG Operation
OFF
(Y2D)
ON
(X11)
OFF
ON
Forward JOG start signal
OFF
ON
Reverse JOG start signal
OFF
ON ON
(X14)
OFF
Executed by the QD73A1
Speed can be changed by writing data to the control change area of the buffer memory using a sequence
program.
For details, refer to the following.
Page 218, Section 11.6

The following figure shows the range of JOG operation.
Lower limit switch (RLS)
Upper limit switch (FLS)
0 2147483647 0 2147483647
Underflow signal (X1A) ON
Overflow signal (X19) ON
Overflow signal (X19) ON
Underflow signal (X1A) ON
Overflow signal (X19) ON
Deceleration stop Deceleration stop
JOG operation can be executed within the range between the upper limit switch (FLS) and the lower limit
switch (RLS). Note that the stroke limit upper limit and lower limit are ignored in JOG operation.
JOG operation decelerates and stops if Upper limit signal (FLS) or Lower limit signal (RLS) turned off during
the operation.
(b) When " Current feed value" exceeded the QD73A1's control range during JOG
Md.1
When the current feed value exceeded the QD73A1's control range (-2147483648 to 2147483647), Overflow
signal (X19) or Underflow signal (X1A) turns on, and " Current feed value" varies again as in the following
Md.1
figure.
Current feed value Md.1
Reset Overflow signal (X19) or Underflow signal (X1A) by turning on Overflow reset signal (Y29) or Underflow
reset signal (Y2A).
The error "Outside the stroke limit range" (error code: 100) occurs.

(d) When the upper limit switch (FLS) or the lower limit switch (RLS) turned off
The error "Upper limit signal OFF while BUSY" (error code: 91) or the error "Lower limit signal OFF while
BUSY" (error code: 92) occurs.
If operation decelerated and stopped due to the upper limit switch (FLS) or the lower limit switch (RLS), JOG
operation can be executed in the opposite direction (direction back to the normal range) after resetting the
error. (If the JOG start signal for the erroneous direction is turned on, the error occurs again.)
JOG operation possible JOG operation not possible
Upper limit signal (FLS)
or Lower limit signal (RLS)
(3) Precautions during operation
Cd.3
gradually for safe operation.
Cd.3
JOG operation does not start.
Cd.3 Pr.5
" Speed limit value", but the error "JOG speed Outside the setting range" (error code: 41) occurs.
Pr.5
10.1 Operation of JOG Operation
JOG operation · Deceleration stop · t

turned on, JOG operation starts again accelerating its speed.
Forward JOG start signal
OFF
ON
(X14)
OFF
Executed by the QD73A1
is turned on, JOG operation starts in the opposite direction after the completion of deceleration.
Forward JOG start signal
OFF
ON
Reverse JOG start signal
OFF
ON
(X14)
OFF
BUSY signal (X14) turns off for 0.5ms when switching. Executed by the QD73A1

signal (Y21 to Y23) is turned on, an error occurs and the operation does not start.
Forward JOG start signal (Y24)
ON
OFF
OPR start signal (Y20)
or Positioning start signal (Y21 to Y23)
Error code (ERR.1) Md.3
81 (BUSY signal ON at start)
Executed by the QD73A1
ON at start" (error code: 81) occurs and the operation in the opposite direction is not executed.
error "BUSY signal ON at start" (error code: 81) occurs and forward JOG operation is executed.
For details on "sub functions" that can be combined with JOG operation, refer to the following.
Page 29, Section 3.3 (4)
For details on each sub function, refer to the following.
10.1 Operation of JOG Operation
Page 208, CHAPTER 11
To directly monitor the buffer memory using GX Works2, refer to the following.
Page 89, Section 5.6
t · BUSY signal (X14)

This section explains the operation timing and processing time of JOG operation.
OFF
(Y24, Y25)
ON
OFF
(X14)
ON
(X15)
OFF
*1 This is an indication of internal commands, and does not match with the actual analog output waveform.
The following values apply to t1 to t3.
0.7 to 1.2ms 0 to 0.5ms 0 to 0.5ms

10.3 Data Setting for JOG Operation
To execute JOG operation, certain data must be set and stored in the buffer memory areas.
The following table lists the JOG data to be set, setting condition, and check timing.
Check timing
Setting item Setting range Default
memory
value Setting condition
of the set
address
data
(decimal)
JOG speed 1 to 4000000pulse/s 0pulse/s The data can be set anytime.
Cd.3
rise (ON) of a JOG start
(Set in the unit of
signal (Y24, Y25) are used
Pr.5
10pulse/s.)
for the operation. If the data
are written when BUSY
Pr.6
signal (X14) is on, the data
2 to 9999ms 300ms
will be accepted at the rise
Pr.7
(ON) of the next JOG start
signal (Y24, Y25).
10.3 Data Setting for JOG Operation

Functions referred to as "sub function" compensate or limit control, or add functions at the execution of major
positioning functions. Execute these sub functions by setting parameters or through a sequence program for them.
The following functions are referred to as "sub function".
Electronic gear function This function controls moving distance and speed by multiplying
command pulse output of the QD73A1.
Section 11.1
This function limits command speed to the value set in
" Speed limit value".
Section 11.2
Pr.5
This function controls operation not to execute positioning when
a command that moves the workpiece outside the specified
Section 11.3
stroke limit range is given.
This function decelerates and stops operation according to the
Upper limit switch (FLS)/lower limit
detection on limit switches placed at the upper and lower stroke
Section 11.4
limits.
Current value change function This function changes the value set in " Current feed
Md.1
value" to a specified value.
Section 11.5
Speed change function This function changes speed during major positioning control or
JOG operation.
Section 11.6
This function clears the accumulated pulses in the deviation
counter. When the servomotor power was turned off due to an
Deviation counter clear function
emergency stop during positioning, clearing the accumulated
Section 11.7
pulses in the deviation counter prevents servomotor rotation at
power recovery.
This function turns on In-position signal (X16) while the
accumulated pulse amount in the deviation counter is within the
specified in-position range (1 to 20479pulse). In-position signal
Section 11.8
(X16) can be used as the signal right before positioning
completion.
This function outputs an alert and immediately stops the
positioning when the accumulated pulses reached the amount
Accumulated pulse error detection
specified by the user before the pulses exceed the amount set
Section 11.9
in "Accumulated pulse setting" in the switch setting and an
excessive error occurs.

11.1 Electronic Gear Function
The "electronic gear function" controls machine movement amount per one command pulse by multiplying command
pulse output of the QD73A1.
Positioning is much more flexible with the use of this function, eliminating the process of selecting a detector according
to the machine system.
Machine movement amount per one pulse is adjusted inside the QD73A1.
Electronic gear is active on all of OPR control, major positioning control, and JOG operation.
Number of command pulses
CDV
Set numerator and denominator of command pulse multiplication for electronic gear to parameters.
Satisfy the following condition when setting a numerator (CMX) and a denominator (CDV).
If the setting range is exceeded, the error "Denominator of command pulse multiplication for electronic gear
11.1 Electronic Gear Function
Outside the setting range" (error code: 3) occurs.
When the electronic gear function is used, positioning speed and movement amount are multiplied by the
specified value.
When there are decimal pulses, the fractions are maintained inside and accumulated for the next command.
The following is an example of the use of electronic gear.
Ex. A positioning system using the following worm gear
When the electronic gear function is not used, the feed rate (movement amount per pulse) has fractions.
= = 12000 10 mm/pulse 0.000833
In this system, the fractions can be avoided using the electronic gear function and setting numerator and
= = 12 0.01mm/pulse 12000 ' 10

electronic gear that were not output during positioning before the CPU reset.
limit value, the limit value is ignored. On the other hand, if the speed exceeds 4Mpulse/s, the maximum
value of command frequency, the error "Outside the command frequency range" (error code: 104) occurs. In
this case, the speed is 4Mpulse/s, resulting in a positioning error. To avoid this case, satisfy the following
condition when setting positioning speed and electronic gear: Positioning speed × Electronic gear
The following table lists the data to be set, setting condition, and check timing.
Setting item Setting
range Default value Setting
Check timing of
memory
condition
the set data
address
(decimal)
Pr.3
signal (Y2D) is turned
must be off.
Pr.4

11.2 Speed Limit Function
The "speed limit function" limits command speed to the value set in " Speed limit value" when command speed
Pr.5
during major positioning control or JOG operation exceeds " Speed limit value".
Pr.5
This function is active on major positioning control and JOG operation.
When the value set in " Speed limit value" is exceeded in each control, command speed is limited to
Pr.5
" Speed limit value".
Pr.5
The operation of the speed limit function is as follows.
Positioning speed V1 Da.3
Speed limit value Pr.5
In the figure above, the speed set in " Speed limit value" is output since " Positioning speed V1" is
Pr.5 Da.3
faster than " Speed limit value". In this case, the movement amount that was not output because of the
Pr.5
speed limit (1 in the figure) is output later (2 in the figure), delaying the positioning completion.
11.2 Speed Limit Function
Set positioning speed and JOG speed to a value equal to or less than " Speed limit value". If " Speed
Pr.5 Pr.5
limit value" is exceeded, command speed is limited to " Speed limit value".
Pr.5
Also, set OPR speed to a value equal to or less than " Speed limit value". If " Speed limit value" is
Pr.5 Pr.5
exceeded, the error "OPR speed Outside the setting range" (error code: 20) occurs at the start of OPR.
t

The following table lists the data to be set, setting condition, and check timing.
Setting item Setting range Default value Setting condition Check timing of the
memory
set data
address
(decimal)
The data can be set
anytime.
signal (Y21 to Y23) is
the rise (ON) of a start
signal is used for the
operation. If the data is
21 Pr.5
(Set in the unit of
signal (Y24, Y25) is
10pulse/s.)
signal (X14) is on, the
data will be accepted at
(Y20) is turned on
the rise (ON) of the next
start signal.
Set " Speed limit value" in a unit of 10 pulses. If a single digit is set, the value is rounded off.
Pr.5
Ex.
For instance, if "1999" is set, the operation is executed with a speed limit value of "1990".

11.3 Stroke Limit Function
The "stroke limit function" controls operation not to execute positioning when a command that moves the workpiece
outside the specified stroke limit range is given.
This function limits the moving range of the workpiece.
The following figure shows a moving range of a workpiece when the stroke limit function is used.

The following is an example in which a moving range of a workpiece changes following a current value change.

Ex. When the current stop position is 2000 and the stroke limit upper limit is set to 5000
As the current value is changed from 2000 to 1000, " Current feed value" changes to 1000,

The following table describes stroke limit checks and processing in case of an error that are performed by the
QD73A1.
If a current value is outside the stroke limit range*1, the
The module turns on Error detection signal
module reports an error. (The module checks
(X18), and reports the error "Outside the
" Current feed value".)
stroke limit range at start" (error code: 83).
Md.1
If a positioning address setting is outside the stroke limit
The module turns on Error detection signal
range*1, the module reports an error. (The module checks
(X18), and reports the error "Positioning
address Outside the setting range" (error
" Positioning address P1".)
Da.2
code: 30).
If a current value exceeds the stroke limit range*1, the
The module turns on Error detection signal
module reports an error. (The module checks
(X18), and reports the error "Outside the
stroke limit range" (error code: 100).
" Current feed value".)
Md.1
*1 The range from " Stroke limit upper limit" to " Stroke limit lower limit"
Pr.1 Pr.2
The following table describes the corresponding stroke limit check for each control.
OPR control Stroke limit check 3 is performed.
Stroke limit check 1 and 2 are performed. Two-phase trapezoidal
Speed-position control switch mode
JOG operation Stroke limit check 3 is performed.
Current value change No stroke limit check is performed.
To execute the stroke limit function normally, OPR must be executed beforehand.
The following table lists the data to be set, setting condition, and check timing.
Setting item Setting range Default value Setting
Check timing
memory
condition
of the set data
address
(decimal)
Stroke limit upper limit
Pr.1
pulse PLC READY signal
(Y2D) must be off.
Stroke limit lower limit 0pulse 2
Pr.2
Set values as follows.
Pr.1 Pr.2
Stroke limit upper limit = Stroke limit lower limit

11.4 Upper Limit Switch (FLS)/Lower Limit Switch (RLS) Function
The "upper limit switch (FLS)/lower limit switch (RLS) function" decelerates and stops operation according to signal
inputs from limit switches that are placed at the upper and lower limits of the machine's movable range.
This function prevents the machine from being damaged by stopping the operation before the workpiece reaches the
upper or lower limit of the moving range, which is a physical limit that the QD73A1 can handle.
Normally, upper limit switch (FLS) and lower limit switch (RLS) are placed inside the stroke limits (stroke ends) of the
drive unit, so that the operation is stopped before the workpiece reaches a stroke limit (stroke end) of the drive unit.
The following figure shows the operation of the upper limit switch (FLS)/lower limit switch (RLS) function.
Lower limit Upper limit
Decelerates and stops upon detection of the lower limit switch (RLS)
Decelerates and stops upon detection of the upper limit switch (FLS)
Control range of the QD73A1
Mechanical stopper Mechanical stopper
Starts toward the lower limit direction
Starts toward the upper limit direction
Upper limit switch (FLS) Stroke limit of the drive unit
Lower limit switch (RLS)
Stroke limit of the drive unit
11.4 Upper Limit Switch (FLS)/Lower Limit Switch (RLS) Function
Moving direction · Moving direction · Drive unit

To use the upper limit switch (FLS)/lower limit switch (RLS) function, wire the QD73A1's terminals for Upper limit
signal (FLS) and Lower limit signal (RLS) as in the following figure.
FLS
RLS
COM
24VDC
When wiring the terminals, set the switch that is placed on the direction in which " Current feed value"
Md.1
increases as an upper limit switch (FLS), and the switch that is placed on the direction in which " Current
Md.1
feed value" decreases as a lower limit switch (RLS).
If the upper and lower limit switches are wired opposite, the upper limit switch (FLS)/lower limit switch (RLS)
function does not operate normally, and the motor does not stop.
limit switch (FLS) had detected overrange in the direction where " Current feed value" increases. Also,
Md.1
OPR control, major positioning control, and JOG operation cannot be started from the area where the lower
limit switch (RLS) had detected overrange in the direction where " Current feed value" decreases. To
Md.1
start operation again, move the workpiece to a position within the control range of the QD73A1 using JOG
operation.
COM terminal is open (including the case that the terminals are not wired), the QD73A1 cannot execute
positioning.
(4) When the upper limit switch (FLS)/lower limit switch (RLS) function is not used
Wire the QD73A1's terminals for Upper limit signal (FLS) and Lower limit signal (RLS) as in the following figure.
FLS
RLS
COM
24VDC

11.5 Current Value Change Function
The "current value change function" changes the value set in " Current feed value" to a specified value.
Md.1
Use this function when operation cannot be started due to a current feed value outside the stroke range, or to change
the current value.
As a new address is set in " New current value" and "1" is written in " Current value change request",
Cd.1 Cd.7
" Current feed value" changes to the value set in " New current value".
Md.1 Cd.1
" Actual current value" is equal to " Current feed value - Accumulated pulses in the deviation
Md.2 Md.1
counter". When the accumulated pulse amount in the deviation counter is 0, " Current feed value" is equal
Md.1
to " Actual current value".
Md.2
Md.1
Md.2
Md.1 Current feed value - Accumulated pulses in the deviation counter
Cd.7
change error" (error code: 110) occurs and the current value is not changed.
11.5 Current Value Change Function
The following table lists the data to be set and the condition to execute the current value change function.
Buffer memory
Setting item Setting range Default value
the current value change
address
function
(decimal)
Cd.1
2147483647pulse 0pulse BUSY signal (X14) must be
off.
Cd.7

The "speed change function" changes the speed of the operation in process to a specified speed at a specified timing.
Set a new speed value to the buffer memory and request the speed change.
The following figure shows the operation of speed changes.
Speed change to V2 Positioning in V1
Speed change to V3
(a) Speed change during two-phase trapezoidal positioning control
speed ( , ) of the next positioning data.
Da.3 Da.5
Positioning control P1 Next control P2
Cd.2
Command speed of P2
Command speed of P1
trapezoidal positioning control.
Speed cannot be changed at the following timings.
(The error "Speed change error (OPR)" (error code: 111) occurs.)
(The error "Speed change error (Positioning)" (error code: 112) occurs.)
(The error "Speed change error (JOG)" (error code: 113) occurs.)
t · New speed value · Speed change command

(c) New speed and " Speed limit value"
Pr.5
When the value set in " New speed value" exceeds " Speed limit value", the positioning is operated
Cd.2 Pr.5
at " Speed limit value".
Pr.5
To change speed successively, set an interval of 10ms or more between each speed change. If there are not
enough intervals between speed changes, the QD73A1 may not be able to follow the requests and process the
commands normally.
Cd.2
When "0" is set in " New speed value" and a speed change is requested, the axis stops. Though, BUSY
Cd.2
signal (X14) stays on. (Inputting Stop signal turns off BUSY signal (X14).)
To activate the axis again, set a value other than "0" in " New speed value" and request the speed
Cd.2
change.
Positioning start signal (Y21 to Y23)
ON
OFF
Cd.2 New speed value 1000
11.6 Speed Change Function
Cd.8 Speed change request
Executed by the QD73A1
The following table lists the data to be set and the condition to execute the speed change function.
Setting item Setting range Default value Execution condition of the speed
memory
change function
address
(decimal)
0 to " Speed limit
BUSY signal (X14) must be on. Note that
Pr.5
speed cannot be changed at the following.
Cd.2
Cd.8
turned off during JOG operation

The "deviation counter clear function" clears the accumulated pulses in the deviation counter to 0.
When the servomotor power was turned off due to an emergency stop during positioning, clearing the accumulated
pulses in the deviation counter to 0 prevents servomotor rotation at power recovery.
(a) Start after clearing deviation counter
To start positioning after clearing the deviation counter, check the following two points.
Cd.4
Md.2 Md.1
Md.2
" Current feed value".
Md.1
Md.1 Md.2
value" of before clearing the deviation counter, follow the procedure below.
1 Read out the value in " Actual current value".
Md.2
2 Write the read value to " New current value".
Cd.1
3 Clear the deviation counter.
4 Change the current value.
The following table lists the data to be set and the condition to execute the deviation counter clear function.
Buffer memory
Setting item Setting range Default value
the deviation counter
address
clear function
(decimal)
counter 0 BUSY signal (X14) must be
Cd.4
off. 86
Deviation counter clear · command

11.8 In-position Function
The "in-position function" turns on In-position signal (X16) while the accumulated pulse amount in the deviation
counter is within the specified in-position range (1 to 20479pulse) after deceleration started.
In-position signal (X16) can be used as the signal right before positioning completion.
In-position signal (X16) turns on when the accumulated pulse amount in the deviation counter becomes equal to
the value set in " In-position range" and stays on till the next start.
Pr.8
Pulse output Motor speed
OFF
Turns on when the deviation counter value (pulse) becomes the one within the set in-position range. Turns off at start.
Accumulated pulse amount is checked with the in-position range every 0.5ms.
11.8 In-position Function
(a) During speed control in the speed-position control switch mode
Accumulated pulse amount is not checked with the in-position range.
In-position signal (X16) turns off at the following timings.

The following table lists the data to be set, setting condition, and check timing.
Setting item Setting
Default
value Setting condition Check timing of
memory
range
the set data
address
(decimal)
The data can be set anytime.
start signal (Y21 to
Y23) is turned on
(ON) of a start signal is used for
the operation. If the data is
24 Pr.8
signal (Y24, Y25) is
written when BUSY signal
(X14) is on, the data will be
accepted at the rise (ON) of the
next start signal.

11.9 Accumulated Pulse Error Detection Function
The accumulated pulse error detection function outputs an alert and immediately stops the positioning when the
accumulated pulses reached the amount specified by the user before the pulses exceed the amount set in
"Accumulated pulse setting" in the switch setting and an excessive error occurs.
This function enables to detect abnormal operating status in early stages and minimize the influence on the
mechanical system.
The following figures show the operation of the accumulated pulse error detection function.
An alert occurs because the accumulated pulses have exceeded the amount of Alert output accumulated pulses (maximum value).
Positioning stops immediately because the accumulated pulses have exceeded the amount of Immediate stop accumulated pulses (maximum value). (Accumulated pulse clear)
Immediate stop accumulated pulses (maximum value)
Alert output accumulated pulses (maximum value)
Reference value (maximum value)
The accumulated pulses increase because the workpiece hit something and stopped.
11.9 Accumulated Pulse Error Detection Function
Cd.18
Accumulated pulse error detection request
ON
Start signal (Y20 to Y26)
ON
OFF
ON
Excessive error signal (X17)
ON
Error detection signal (X18) OFF
Servo ON signal (SVON)
Error code (ERR.1) Md.3
Md.21
Deviation counter value (pulse)
Executed by the QD73A1

The QD73A1 compares accumulated pulses that are output during the positioning with alert output
accumulated pulses. If accumulated pulses exceed the amount of the alert output accumulated pulses, the
error "Accumulated pulse alert" (error code: 130) occurs. (Even after the error occurs, the positioning
continues.)
The QD73A1 compares accumulated pulses that are output during the positioning with immediate stop
accumulated pulses. If accumulated pulses exceed the amount of the immediate stop accumulated pulses, the
QD73A1 performs the following processing and stops the positioning.
Turn on PLC READY signal (Y2D) to restore the positioning (In the same way as when an excessive error
occurs).
The following is the executing procedure of the accumulated pulse error detection function.
Measure the reference value.
Page 225, Section 11.9.1
Save the measured reference value in the flash ROM inside the QD73A1.
Page 225, Section 11.9.1
Set the data to use the accumulated pulse error detection function.
Page 226, Section 11.9.2
Execute the positioning.
Start · End

11.9.1 Measuring and saving the reference value in the flash ROM
Before using the accumulated pulse error detection function, the reference value needs to be measured to detect
errors.
Reference value means the maximum/minimum accumulated pulse values that are output when the QD73A1 is
operating normally.
The QD73A1 obtains the judgment value for alert output and immediate stop and carry out control using the reference
value, alert output accumulated pulse setting value, and immediate stop accumulated pulse setting value.
Executing procedure is as follows.
Cd.19
measurement. The QD73A1 monitors the status of accumulated pulses and measures the maximum/minimum values
while " Measurement start request" is set to 1. 2. Set " Reference value write request" to "1: Requested" when " Reference value
Cd.19
Cd.20 Md.20
measurement flag" is set to "1: Measured".
The QD73A1 saves the measured maximum/minimum values in the flash ROM when " Reference value write request" is set to 1.
Cd.20
11.9 Accumulated Pulse Error Detection Function 11.9.1 Measuring and saving the reference value in the flash ROM
Start signal (Y20 to Y26)
ON
OFF
ON
Cd.19
ON
Md.20
Reference value measurement flag
ON
Cd.20
Cleared to 0 by the QD73A1
Executed by the QD73A1

Set the values of " Alert output accumulated pulse setting value (maximum value)" to " Immediate stop
Cd.13 Cd.16
accumulated pulse setting value (minimum value)", and set " Accumulated pulse error detection request" to 1 to
Cd.18
execute the accumulated pulse error detection function. Set the data required for control in the sequence program.
The following table lists the data to be set, setting condition, and check timing.
Setting item Setting range Default
value Setting condition Check timing of
memory
the set data
address
(decimal)
Cd.17
setting value selection" is set
Cd.13
to 0:
1 to 148000 pulse
Cd.17
setting value selection" is set
to 1:
Cd.14
(× 10-3)
The data can be set
Cd.17
anytime.
setting value selection" is set
Cd.18
Cd.15
to 0:
-148000 to -1 pulse
from 0 to 1.)
Cd.17
setting value selection" is set
to 1:
Cd.16
(× 10-3)
Cd.17
Cd.19
Cd.18
start request" must be
set to 0.
Cd.18
Cd.19
request" must be set
to 0.
Md.20
Cd.20
flag" must be set to 1.
*1 Set both alert output accumulated pulse setting value and immediate stop accumulated pulse setting value. If either of the values is set to 0, the accumulated pulse error detection function does not operate. The error "Accumulated pulse error undetectable" (error code: 131) occurs. *2 If either of the maximum value and minimum value is set properly, the accumulated pulse error detection function operates. The error detection is not executed for the unset side. *3 Each request is detected on a cycle of 0.5ms.

(1) Alert output accumulated pulses and immediate stop accumulated pulses
Alert output accumulated pulses (accumulated pulses set to output an alert) and immediate stop accumulated
pulses (accumulated pulses set to stop the positioning immediately) are set by combining the following values.
Cd.13 Cd.15
Cd.14 Cd.16
Cd.17
(2) If " Accumulated pulse setting value selection" is set to "0: Set with pulse"
Cd.17
Alert output accumulated pulses and immediate stop accumulated pulses can be obtained as follows:
Alert output accumulated pulses = reference value + alert output accumulated pulse setting value
Immediate stop accumulated pulses = reference value + immediate stop accumulated pulse setting value
The accumulated pulse error detection function does not operate.
pulse setting value
The value of alert output accumulated pulses (maximum value) is calculated using the value of
" Immediate stop accumulated pulse setting value (maximum value)" at the following condition:
Cd.14
" Alert output accumulated pulse setting value (maximum value)" > " Immediate stop accumulated
Cd.13 Cd.14
pulse setting value (maximum value)"
11.9 Accumulated Pulse Error Detection Function 11.9.2 Setting the accumulated pulse error detection function
The value of alert output accumulated pulses (minimum value) is calculated using the value of
" Immediate stop accumulated pulse setting value (minimum value)" at the following condition:
Cd.16
" Alert output accumulated pulse setting value (minimum value)" < " Immediate stop accumulated
Cd.15 Cd.16
pulse setting value (minimum value)"
Ex. When the setting values are as follows:
Cd.13
Cd.14
Both alert output accumulated pulses and immediate stop accumulated pulses are judged by the
reference value + 1100 pulse. Thus, an alert is output and the positioning stops simultaneously.

setting value, and "Accumulated pulse setting" in the switch setting
The setting range of " Alert output accumulated pulse setting value (maximum value)" is 1 to 148000 (the
Cd.13
range of " Alert output accumulated pulse setting value (minimum value)" is -148000 to -1). However,
Cd.15
when the alert output accumulated pulses exceed the amount of "Accumulated pulse setting" in the switch
setting, an alert is output according to the setting of "Accumulated pulse setting".
The above is applicable to " Immediate stop accumulated pulse setting value (maximum value)" and
Cd.14
" Immediate stop accumulated pulse setting value (minimum value)".
Cd.16
Ex. When the measured reference value (maximum value) is 2000 and the setting values are as follows:
Cd.13
The calculated value of alert output accumulated pulses (maximum value) is 5000 (2000 + 3000).
However, the value of alert output accumulated pulses (maximum value) becomes 3700 because the
calculated value exceeds the amount of "Accumulated pulse setting"
(3) If " Accumulated pulse setting value selection" is set to "1: Set with magnification"
Cd.17
Alert output accumulated pulses and immediate stop accumulated pulses can be obtained as follows:
Alert output accumulated pulses = reference value + (Alert output accumulated pulse setting value - 1000) ×
Immediate stop accumulated pulses = reference value + (immediate stop accumulated pulse setting value -
1000) × reference value 1000
Last three digits of the setting value indicate the value after the decimal point.
Ex. When the alert output accumulated pulse setting value is 1234, the alert output accumulated pulses can
be obtained by multiplying the reference value by 1.234.
The accumulated pulse error detection function does not operate.
pulse setting value
The value of alert output accumulated pulses (maximum value) is calculated using the value of
" Immediate stop accumulated pulse setting value (maximum value)" at the following condition:
Cd.14
" Alert output accumulated pulse setting value (maximum value)" > " Immediate stop accumulated
Cd.13 Cd.14
pulse setting value (maximum value)"
The value of alert output accumulated pulses (minimum value) is calculated using the value of
" Immediate stop accumulated pulse setting value (minimum value)" at the following condition:
Cd.16
" Alert output accumulated pulse setting value (minimum value)" > " Immediate stop accumulated
Cd.15 Cd.16
pulse setting value (minimum value)"
reference value 1000

Ex. When the setting values are as follows:
Cd.13
Cd.14
Both alert output accumulated pulses and immediate stop accumulated pulses are judged by
accumulated pulses that are 1.1 times of the reference value (maximum value). Thus, an alert is output
and the positioning stops simultaneously.
setting value, and "Accumulated pulse setting" in the switch setting
The setting range of " Alert output accumulated pulse setting value (maximum value)" and " Alert
Cd.13 Cd.15
output accumulated pulse setting value (minimum value)" is 1000 to 50000 (1 to 50 times). However, when the
alert output accumulated pulses exceed the amount of "Accumulated pulse setting" in the switch setting, an
alert is output according to the setting of "Accumulated pulse setting"
The above is applicable to " Immediate stop accumulated pulse setting value (maximum value)" and
Cd.14
" Immediate stop accumulated pulse setting value (minimum value)".
Cd.16
Ex. When the measured reference value (maximum value) is 2000 and the setting values are as follows:
Cd.13
The calculated value of alert output accumulated pulses (maximum value) is 6000 (2000 + (3000 - 1000)
× 2000 1000). However, the value of alert output accumulated pulses (maximum value) becomes 3700
because the calculated value exceeds the amount of "Accumulated pulse setting"
11.9 Accumulated Pulse Error Detection Function 11.9.2 Setting the accumulated pulse error detection function

CONTROL
This chapter describes stops and restarts of control.
This section describes control stops.
The QD73A1 stops control in case of the following.
The following table describes causes of stops and the subsequent processing (except the stop in case of normal
completion of positioning).
Error Process of
Cause of stop
detection
stop
signal (X18)
(READY) turned off.*1 ON Servo READY OFF while BUSY (error code: 90)
Free run The power supply was
turned off.
The upper limit switch
Upper limit signal OFF while BUSY (error code: 91)
(FLS) turned off.
The lower limit switch
(RLS) turned off. Lower limit signal OFF while BUSY (error code: 92)
PLC READY signal OFF during operation (error code: 105)*2
(Y2D) was turned off. ON
PLC READY signal OFF during OPR (error code: 103)*3
External stop signal ON during OPR (error code: 93)*3
was input.
Stop signal (Y27) was
turned on. STOP signal ON during OPR (error code: 102)*3
*1 The operation varies as shown below depending on "Deviation counter clear setting" in the switch setting. If "0: Clear the deviation counter when the servo ready signal is OFF." is set, the analog output voltage becomes the value on which zero adjustment was made at the timing when Servo READY signal (READY) has turned off. If "1: Do not clear the deviation counter when the servo ready signal is OFF." is set, the analog output voltage equivalent to the accumulated pulses in the deviation counter is output. *2 Only during major positioning control or JOG operation *3 Only during OPR

An emergency stop circuit should be built outside the programmable controller.
If an error (a cause of a stop) occurs during OPR, a deceleration stop starts at the error occurrence.
At the completion of the deceleration stop, OPR request signal (X12) stays on. Also, OPR complete signal (X13)
does not turn on since the OPR was not completed normally.
The following figure is the timing chart of when Stop signal (Y27) is turned on during OPR.
(Y20)
OFF
ON
(X14)
OFF
ON
(X12)
OFF
12.1 Stopping Control
OFF
ON
(Y27)
OFF
ON
(X18)
OFF
Error code (ERR.1) Md.3 102 (STOP signal ON during OPR)
Executed by the QD73A1

(a) Stop before deceleration start of major positioning control or JOG operation
If an error (a cause of a stop) occurs prior to a start of deceleration during major positioning control or JOG
operation, a deceleration stop starts at the error occurrence. The deceleration speed depends on
" Deceleration time" and " Speed limit value".
Pr.7 Pr.5
Positioning complete signal (X15) does not turn on at the completion of the deceleration stop.
Also, the next positioning does not start even if the error is resolved while the start signal is on. The start signal
must be turned off and on.
The following figure is the timing chart of when Stop signal (Y27) is turned on during positioning control.
OFF
ON
Does not start even if Stop signal (Y27) is turned off
(X14)
OFF
(X15)
ON
(Y27)
OFF
OFF
(X18) *1
Executed by the QD73A1
*1 Error detection signal (X18) does not turn on in case of a stop following a change (from off to on) of Stop signal (Y27) or an input of Stop signal (STOP). Error detection signal (X18) turns on due to the following.

(b) Stop during deceleration of major positioning control or JOG operation
If an error (a cause of a stop) occurs during deceleration of major positioning control or JOG operation, the
deceleration continues and the operation stops since it is toward completion of the positioning or is following a
change (from on to off) of a JOG start signal (Y24, Y25). In case of major positioning control, Positioning
complete signal (X15) turns on at its completion.
This process is the same for a stop with an error.
The following figure is the timing chart of when Stop signal (Y27) is turned on during deceleration of positioning
control.
OFF
ON
(X14)
OFF
ON
(X15)
OFF
ON
OFF
(Y27)
(X18) *1
OFF
Executed by the QD73A1
*1 Error detection signal (X18) does not turn on in case of a stop following a change (from off to on) of Stop signal (Y27) or an input of Stop signal (STOP). Error detection signal (X18) turns on due to the following.
12.1 Stopping Control

After a deceleration stop following Stop signal, the operation of the speed-position control switch mode before the stop
can be restarted by turning on Speed-position mode restart signal (Y26).
(a) When positioning is stopped using Stop signal (Y27) or Stop signal (STOP)
The positioning before the stop can be restarted by turning on Speed-position mode restart signal (Y26).
The following figure shows the timing at which the speed-position control switch mode restarts.

Turning on Stop signal (Y27) starts deceleration. Turning on Stop signal (Y27) starts deceleration.

(b) When speed is changed during positioning
After a stop following the input of Stop signal (STOP), if Speed-position mode restart signal (Y26) is turned on,
the positioning restarts according to the positioning speed set in the positioning data. The positioning does not
restart at the new speed.
Speed control Position control Position control
Speed-position switching command signal (CHANGE)
restart signal (Y26) is turned on in a condition "Restart possible", the error "Restart error" (error code: 85)
occurs.
: Restart possible
×: Restart not possible
Pr.9
0: Position control mode 1: Speed-position control switch
mode
OPR start signal (Y20) × ×
Absolute positioning start signal
12.2 Restarting the Speed-position Control Switch Mode
Forward start signal (Y22) ×
Reverse start signal (Y23) ×
status other than stop, the error "Restart error" (error code: 85) occurs and the axis does not act.

Functions referred to as "common function" can be used regardless of control method when necessary.
Common functions can be used on GX Works2.
The "module status monitor function" monitors the module information, switch setting information, and external I/O
signal information. The module's detailed information can be displayed on the system monitor of GX Works2.
The following LED statuses are displayed.
RUN
Operating normally (same as the RUN LED)
SV RDY Servo READY signal (READY) ON
DOG Near-point dog signal (DOG) ON
STOP Stop signal (STOP) ON
FLS Upper limit signal (FLS) ON
RLS Lower limit signal (RLS) ON
CHG Speed-position switching command signal (CHANGE) ON

(2) Hardware switch information
The following switch setting statuses are displayed.
ROT DIR Rotation direction setting
ACCUM PLS Accumulated pulse setting
ZERO DIR OPR direction setting
Refer to Page 276, Appendix 4.1 (2).
OPR METHOD OPR method setting
ENC I/F Encoder I/F setting
RESOLT Analog voltage resolution setting

13.1 Module Status Monitor Function
Indicates that Servo READY signal (READY) is on.
For details on the system monitor of GX Works2, refer to the following.
GX Works2 Version1 Operating Manual (Common)
MULTI Multiplication setting

This function monitors the QD73A1's error history stored in the buffer memory.
The error history of past 16 records can be monitored. Once 16 records are stored, the next record overwrites the
oldest record. Therefore, the latest 16 errors are stored at all times.

To check the error history, the QD73A1 needs to be registered in the intelligent function module monitor window. For
how to register the module in the intelligent function module monitor window and to display the details of the history,
refer to the following.
GX Works2 Version1 Operating Manual (Intelligent Function Module)
To monitor the error history directly through the buffer memory, refer to the following.
Page 85, Section 5.5

13.3 Module Error Collection Function
Errors that occurred in the QD73A1 are collected into the CPU module.
The error information of the QD73A1 module is held in a CPU module memory as a module error history, even when
the power is turned off or the CPU module is reset.

Error history (CPU module) and error log (intelligent function module) are displayed on one screen.
Errors that are detected in the entire base system can be monitored in chronological order.
CPU 19:29 Error A1 is detected! 19:36 Error A2 is detected! 19:34 Error B1 is detected!
Time Module with error Error code 19:29 19:34 19:36
For details on the module error collection function, refer to the following.

When an error occurs, the error can be cleared on the system monitor.
By clicking the button in the system monitor, the error codes stored in " Error code (ERR.1)" and
Md.3
" Error code (ERR.2)" are cleared, and the ERR. LED turns off. This operation is the same as the one that uses
Md.4
Error reset signal (Y28).
However, the error history cannot be cleared with the button.
For the error clearing method using Error reset signal (Y28), refer to the following.
Page 38, Section 3.4.3 (12)
[Diagnostics] [System Monitor...] Error module


CHAPTER 14 TROUBLESHOOTING
This chapter describes errors that may occur in the QD73A1 and troubleshooting for them.
The error codes that occurred in the QD73A1 can be checked by the following.
Choose a method depending on the purpose and application.
Follow the procedure below.

the "System Monitor" window.
[Diagnostics] [System Monitor...]
14.1 Checking an Error on GX Works2

button.
the QD73A1, refer to the user's manual for the
module and take a corrective action.
(To the next page)

(From the previous page)
"Module's Detailed Information" window.
"Error and Solution"
(2) Checking on the "Error History" window
An error history that includes errors in the QD73A1 and other modules is displayed in a list, and it can be output
to a CSV file. The error codes and the error occurrence time can be checked even after the power was turned off
and on or the CPU module was reset.
[Diagnostics] [System Monitor...] button

Error logs of modules are displayed in a list.
(a) · (b) · (c)

(b) Error and Solution, Intelligent Module Information
"Error History List".
For the QD73A1, the following are displayed.
Current feed value The current value at the time of the error occurrence is stored.
Actual current value The actual current value at the time of the error occurrence is stored.
State of the input signal (Xn0 to XnF) The status of input signals (X0 to XF) at the time of error occurrence is stored (in
hexadecimal).
State of the input signal (X(n+1)0 to X(n+1)F) The status of input signals (X10 to X1F) at the time of error occurrence is stored (in
hexadecimal).
State of the output signal (Yn0 to YnF) The status of output signals (Y0 to YF) at the time of error occurrence is stored (in
hexadecimal).
State of the output signal (Y(n+1)0 to Y(n+1)F) The status of output signals (Y10 to Y1F) at the time of error occurrence is stored (in
hexadecimal).
WDT error H/W error signal
14.1 Checking an Error on GX Works2
The statuses of input signals (X) at the time of error occurrence are stored.
OPR start complete signal
Absolute positioning start complete signal
Forward start complete signal
Reverse start complete signal
Zero/gain adjustment data writing complete flag
Zero/gain adjustment change complete flag
Set value change complete signal
Operating status of the speed-position control

An error history is output to a CSV file.
If errors occur in the QD73A1 frequently, "*HST.LOSS*" may be displayed under "Error Code" instead of an actual error code.

If "*HST.LOSS*" is displayed frequently, set a large value for the number of errors collected per scan under the "PLC RAS" tab in "PLC Parameter". For the setting, refer to the following.
The user's manual (Function Explanation, Program Fundamentals) for the CPU module used

14.2 Troubleshooting
14.2.1 Troubleshooting procedure
This section shows the troubleshooting procedure for the QD73A1.

Check the LED on the front of the QD73A1.
Is the work operating in the set speed? NO

Is the QD73A1's zero adjustment performed properly? Perform zero adjustment. ( Page 59, Section 4.5)
Is the servo amplifier's zero adjustment performed properly? Refer to the manual for the servo amplifier, and perform zero adjustment.
Is a large value set to the gain value of the servo amplifier? Refer to the manual for the servo amplifier, and adjust the gain value of the
servo amplifier to a proper value.
Are the speed command terminal on the QD73A1 and the
servo amplifier connected properly?
Connect the speed command terminals properly.
(when the motor does not stop even though the speed
command from the QD73A1 is 0V)
Is there noise effect?
Is PLC READY signal
(Y2D) off? Turn on PLC READY signal (Y2D).
Is Servo READY signal
Read out the error code, and take the corrective action described in the error code list.
Is the ERR. LED on?
( Page 252, Section 14.3.4)
[Double-check the sequence program.]
Is the BUSY LED off?
[Check the QD73A1's status.]
The accumulated pulse amount is outside the setting range.
Is Excessive error signal
Is External stop signal
Is WDT error, H/W error
If WDT error, H/W error signal (X10) stays on even after resetting the CPU module, please consult your local
Mitsubishi representative.
Are the QD73A1 and the
Check if the QD73A1 and the drive unit are wired properly.

Check item Action
Is proper wave output
terminal is connected to an
If proper wave output is not displayed, please consult your local Mitsubishi representative. Is proper wave output
displayed when the drive
terminal is connected to an
[Double-check the parameters.]
Do the position errors occur by regular amount?
[Double-check the sequence program.]
position control switch mode.
14.2 Troubleshooting 14.2.4 When a positioning error occurs
Is the motor rotating smoothly? Check if the feedback pulse frequency is within 1Mpulse/s using an
oscilloscope.
Is there noise effect?

Are the positioning data set properly? Set proper positioning data.
Is the set positioning speed value greater than " Speed
Pr.5 Pr.5
Set a positioning speed value that is smaller than " Speed limit
value".
Calculate the maximum accumulated pulse amount, and review the
Is the accumulated pulse setting proper?
accumulated pulse setting. ( Page 102, Section 6.2.2)
Is the zero/gain adjustment proper? Perform zero/gain adjustment again. ( Page 59, Section 4.5)
Is the multiplication setting proper? Configure the multiplication setting properly. ( Page 104, Section
6.2.3)
Is the servo amplifier set properly? Refer to the manual for the servo amplifier, and set the servo amplifier
properly.
Is a speed change executed? Review the sequence program to see if the speed change is necessary.
Is proper wave output displayed when the QD73A1's speed
command terminal is connected to an oscilloscope? If proper wave output is not displayed, please consult your local Mitsubishi
representative. Is proper wave output displayed when the drive unit's
encoder output terminal is connected to an oscilloscope?
Is there an error on the servo amplifier? Refer to the manual for the servo amplifier, and check the error detail.
Is Stop signal (Y27) on? Review the sequence program to see if Stop signal (Y27) needs to be turned on.
Is Stop signal (STOP) on? Check if Stop signal (STOP) is wired properly.
The accumulated pulse amount is outside the setting range.
Is Excessive error signal (X17) on?
Check if the accumulated pulse setting is proper. ( Page 102, Section 6.2.2)
Is there noise effect?
limit value"?

14.2.7 OPR error
(1) When OPR cannot be completed
Check item Action
Does Near-point dog signal (DOG) stay off? Check if Near-point dog signal (DOG) is wired properly.
Does the speed change to the creep speed after Near-point
dog signal (DOG) turned on? The QD73A1 may be broken. Please consult your local Mitsubishi
representative. Does analog output from the QD73A1 continue after a Zero
Does Zero signal stay off? Check if Zero signal is wired properly.
If the position where the near-point dog turns off is near the position of a
Zero signal input, the Zero signal input may be misread. Adjust the position
where the near-point dog turns off to be closer to the center of Zero signals.
Do the position errors occur by regular amount?
If the position after the move according to " Setting for the movement
Pr.13
amount after near-point dog ON" is near the position of a Zero signal input,
the Zero signal input may be misread. Adjust " Setting for the
Pr.13
movement amount after near-point dog ON" so that the position after the
move becomes closer to the center of Zero signals.
Is the OPR completed near the position where Near-point
Near-point dog signal (DOG) may be chattering. Use a high-performance
14.2 Troubleshooting 14.2.7 OPR error
dog signal (DOG) turns on?
near-point dog.
Is the OPR in the near-point dog method completed even
though the near-point dog did not turn off? The contact or wiring of the near-point dog is not proper. Check the wiring.
In the near-point dog method, is the movement amount after
Near-point dog signal (DOG) may be chattering when it turns off. Use a
near-point dog ON more than that of normal OPR completion
high-performance near-point dog.
by one or more servomotor rotation?
signal input? · [Near-point dog method] · [Count method]

14.3.1 Types of errors
The errors detected in the QD73A1 are categorized into five types.
The QD73A1 checks parameters with the setting ranges at the following timings, and detects an error when a
data is outside the setting range. If an error occurs, the corresponding data must be changed to a value within the
setting range.
Fixed parameters When PLC READY signal (Y2D) is turned on
When a positioning start signal (Y21 to Y23) is turned on
When a JOG start signal (Y24, Y25) is turned on
When OPR start signal (Y20) is turned on
OPR parameters When OPR start signal (Y20) is turned on
Positioning data When a positioning start signal (Y21 to Y23) is turned on
Control change areas Before the execution of a control change
Start error is a type of errors that occur at a start of OPR control, major positioning control, or JOG operation.
Operation does not start if an error occurs.
Operation error is a type of errors that occur during OPR control, major positioning control, or JOG operation.
If an error occurs, operation decelerates and stops or continues without decelerating depending on the error
detail.
For the operation at the error occurrence, refer to the following.
( Page 252, Section 14.3.4)
Control change error is a type of errors that occur at a control change during positioning.
The data for the control change is ignored if an error occurs.
Zero/gain adjustment error is a type of errors that occur during zero/gain adjustment.
The details of the zero/gain adjustment are not reflected in the QD73A1 if an error occurs. Eliminate the error
cause, and perform zero/gain adjustment again.
Variable parameters

14.3.2 Storage of errors
When an error occurs in the QD73A1, the corresponding error code is stored in the buffer memory.
Errors are classified into ERR.1 and ERR.2 depending on the error details.
Errors caused due to sequence programs.
ERR.1 (minor errors)
Check the error code, and eliminate the error cause by correcting the sequence
program.
Hardware errors or errors caused due to control commands from external input
ERR.2 (major errors)
signals.
Check the error code, and eliminate the error cause on an external input signal.
The latest error codes are stored in the following buffer memory areas every time an error occurs, deleting the
previous error codes. When there is no error or when the errors were reset, "0" is stored.
detection signal
ERR.1 (minor errors) Error code (ERR.1) 104 Error detection signal (X18) ERR.2 (major errors) Error code (ERR.2) 105
Md.3
Md.4
14.3 Details of Errors 14.3.2 Storage of errors
Eliminate the error cause according to the corrective action described in the error code list ( Page 252, Section
14.3.4), then cancel the error status by turning on Error reset signal (Y28).
At the time, the QD73A1 operates as follows.
1 Clears " Error code (ERR.1)" to 0.
Md.3
2 Clears " Error code (ERR.2)" to 0.
Md.4
3 Turns off Error detection signal (X18).

The following table describes error details and corrective actions.
Error
classification Error name Description Operation at the
Error
code
error occurrence Action
category
(decimal)
The set value in
Pr.2
Set a value within the
lower limit" is outside -
setting range, and turn
on PLC READY signal
(Y2D).
Pr.1
upper limit".
The set value in
If a setting is outside
Set a value within the
Pr.3
setting range, and turn
the error occurs and
on PLC READY signal
all of the fixed
(Y2D).
range.
the control.
The set value in
Set a value within the
Pr.4
setting range, and turn
on PLC READY signal
(Y2D).
1 to 9999, and besides
range.
ERR.1
The set value in
Set a value within the
Pr.5
setting range.
value" is outside the
setting range.
The set value in
Set a value within the
Pr.6
setting range.
time" is outside the
setting range.
The set value in
Only the setting with
Set a value within the
Pr.7
the error uses the
setting range.
time" is outside the
setting range.
control.
The set value in
Set a value within the
setting range.
Pr.8
range" is outside the
setting range.
The set value in
Set a value within the
Pr.9
setting range.
mode" is other than 0
and 1.

Error
Error
classification Error name Description Operation at the
Error
code
error occurrence Action
category
(decimal)
Set a value within the
The set value in
setting range.
Pr.11
is outside the setting
1 to " Speed limit
Pr.5
range.
Set a value within the
The set value in
setting range.
Pr.12
is outside the setting
1 to " OPR
Pr.11
range.
If a setting is outside
Set a value within the
setting range.
the OPR does not
start.
The set value in
Pr.11
" Setting for the
Pr.13
Pr.12
ON" is outside the
" Setting for the
Pr.13
setting range.
checked only in the
count method.)
point is outside the
end point within the
stroke limit range.
stroke limit range.
14.3 Details of Errors 14.3.4 Error code list
system is a negative
value at the start. The positioning does
system at the start.
not start.
control in the absolute
Do not change the
moving direction for P1
direction from P1 to
to P2 from the direction
P2 is different from the
used to reach P1.
reach P1.

Error
classification Error name Description Operation at the
Error
code
error occurrence Action
category
(decimal)
Set a value within the
setting range.
is outside the setting
range. The positioning does
1 to " Speed limit
Pr.5
not start when the
set value is 0. In
The set value in
Set a value within the
case of an error due
setting range.
Cd.2
to a set value other
value" is outside the
0 to " Speed limit
Pr.5
positioning operation.
Set a value within the
The set value in
Pr.5
setting range.
value".
Cd.3
is outside the setting
1 to " Speed limit
Pr.5
range.
wiring of the drive
unit, as well as the
connectors.
(READY) is off at the
JOG operation.
devices so that the
on.
Stop signal (STOP) is
on at the start of major
Turn off Stop signal
(STOP).
JOG operation.
not start.
(FLS) is off at the start
to a position within
the stroke limit range
using JOG operation.
operation.
wiring of the drive
unit, as well as the
(RLS) is off at the start
connectors.
operation.
devices so that the
inputs stay on.

Error
Error
classification Error name Description Operation at the
Error
code
error occurrence Action
category
(decimal)
Return the workpiece to
a position away from
(DOG) is on at the
start of OPR in the
using JOG operation or
method.
execute OPR.
signal (X11) or PLC
Turn on PLC READY
is off at the start of
signal (Y2D).
operation.
Make an interlock using
An operation start is
a sequence program so
81 BUSY signal ON
that no operation starts
BUSY signal (X14) is
on.
(X14) is on.
An operation start is
Turn off Stop signal
82 STOP signal ON
(Y27), and start the
signal (Y27) is on.
operation again.
not start.
to a position within
the stroke limit range
An operation start is
using JOG operation.
14.3 Details of Errors 14.3.4 Error code list
the stroke limit range.
a position within the
stroke limit range by
value.
(only in the near-
point dog method).
An OPR start is
to the position before
is on.
OPR.

Error
classification Error name Description Operation at the
Error
code
error occurrence Action
category
(decimal)
was turned on when
(Y22) or Reverse start
signal (Y23).
switch mode. The operation does
Start error 85 ERR.1 Restart error
not start.
was turned on in the
position control mode.
(Y22), or Reverse start
signal (Y23).
so that the workpiece is
attempted with a value
change.
stroke limit range after
the move.
stroke limit range.
Check the drive unit,
and turn on Servo
freely.
(READY).
JOG operation.
(FLS) turned off during
BUSY
Return the workpiece to
operation. The operation
a position within the
stroke limit range using
stops.
JOG operation.
JOG operation.

Error
Error
classification Error name Description Operation at the
Error
code
error occurrence Action
category
(decimal)
dog turns on in the
count method.
turns on, return the
turned on during OPR.
stops.
start OPR.
dog turns on.
Return the workpiece to
The OPR or JOG
a position within the
operation continues.
stroke limit range using
JOG operation.
operation.
102 STOP signal ON
Stop signal (Y27) was
turned on during OPR.
14.3 Details of Errors 14.3.4 Error code list
dog turns on in the
count method.
turns on, return the
PLC READY
stops.
(Y2D) was turned off
during OPR.
start OPR.
dog turns on.
The speed is limited
Change the speed to
4Mpulse/s due to the
4Mpulse/s or lower.
lower.
setting.

Error
classification Error name Description Operation at the
Error
code
error occurrence Action
category
(decimal)
PLC READY
(Y2D) was turned off
Turn on PLC READY
signal (Y2D).
stops.
operation.
Make an interlock using
(X14) is on.
a sequence program.
A speed change was
OPR.
A speed change was
attempted at the start
program so that the
before the start of
is ignored.
thereafter.
of major positioning.
A speed change was
start signal (Y24, Y25)
was turned off in JOG
operation. Make an interlock using
a sequence program.
(X14) is on.

Error
Error
classification Error name Description Operation at the
Error
code
error occurrence Action
category
(decimal)
Turn off and on the
power supply, or reset
the CPU module or the
to the flash ROM more
error.
than 25 times.
Try writing the value
again.
If the error occurs
121 Flash ROM write
again, a failure might
setting value could not
have occurred on the
be written in the flash
module. Please consult
ROM.
representative.
Set the values so that
they meet the following
equal to or greater
are not reflected.
adjustment value.
The set value in
Set a value within the
Cd.10
setting range (1, 2) in
Cd.10
specification".
range.
The set value in
14.3 Details of Errors 14.3.4 Error code list
Set a value within the
Cd.11
setting range (-3000 to
Cd.11
value specification".
range.

Error
classification Error name Description Operation at the
Error
code
error occurrence Action
category
(decimal)
Set a value within the
setting range.
setting" in the switch
The set value in
Cd.5
adjustment area 1" is
range.
selection 4:
are not reflected.
Set a value within the
setting range.
The set value in
setting" in the switch
Cd.9
adjustment area 2" is
range.

Error
Error
classification Error name Description Operation at the
Error
code
error occurrence Action
category
(decimal)
continues.
level.
unmeasured.
function.
Cd.13
Cd.13
Cd.14
Cd.16
range. Moreover,
either of the values
range.
executed.
Cd.15
Cd.17
14.3 Details of Errors 14.3.4 Error code list
selection" to 0 and
Cd.16
Cd.13
range.
Cd.16
Cd.17
selection" is set to 1
(minimum value)".
are set to 0.
Cd.20
value and then, write
was set to 1 when the
the value.
is not written to the
(Write the value when
flash ROM.
Md.20
Md.20
flag" is set to 1.)
flag" was set to 0).

Error
classification Error name Description Operation at the
Error
code
error occurrence Action
category
(decimal)
Turn off and on the
power supply or reset
written to the flash
the CPU module, or
ROM more than 25
clear the error.
times. The measured
Write the value again.
not saved in the
If the error occurs
flash ROM.
again, a failure might
134 Flash ROM write
have occurred on the
not be written in the
module. Please consult
flash ROM.
representative.
The setting for the
Set "Clear" to the CPU
QD73A1 is "Hold" on
not operate.
Mode".
Output Mode".
does not operate.
occurring on the CPU
The CPU has a
During operation:
module, and refer to the
problem.
user's manual for the
CPU module used.
stops.
900 Hardware error 1
Turn off and on the
power supply.
If the error occurs
The hardware has a
again, a failure might
problem. The system stops.
999 Hardware error 2
have occurred on the
module. Please consult
representative.

APPENDICES
Appendix 1 Functions Added or Changed
Appendix 1.1 Functions added
The following lists the functions added to the QD73A1 and corresponding product information.
(first five digits) Reference
Accumulated pulse error detection function 14082 or later Page 223, Section 11.9
Feedback pulse addition/subtraction setting
Page 106, Section 6.2.8
Deviation counter clear setting Page 107, Section 6.2.9
Deviation counter value (pulse) monitor Page 85, Section 5.5
Movement amount after near-point dog ON (absolute value) 16082 or later Page 85, Section 5.5
Appendix 1.2 Functions changed
The following lists the changed function of the QD73A1 and corresponding product information.
(first five digits) Reference
Appendix 1 Functions Added or Changed Appendix 1.1 Functions added
Switch setting 15042 or later Page 276, Appendix 4.1 (2)
The feedback pulse addition/subtraction setting and the deviation counter clear setting can be configured in the
switch setting.
(a) When the QD73A1 that does not support the changed function is used
The feedback pulse addition/subtraction setting and the deviation counter clear setting cannot be configured in
the switch setting.
15042 or later

Appendix 2.1 Example of connection with a servo amplifier manufactured by Mitsubishi Electric Corporation
DOG Near-point dog signal QD73A1
1 2 3 4 5 6 7 8 9
N.C. N.C. N.C. Power supply (5 to 24V) RLS Lower limit signal FLS Upper limit signal
CONT. connector
CHANGE Speed-position switching command signal STOP Stop signal
READY Servo READY signal (+ side) READY Servo READY signal (- side)
PULSE A Phase-A feedback pulse (+ side)
LA Encoder A-phase pulse (differential line driver) LAR Encoder A-phase pulse (differential line driver)
PULSE A Phase-A feedback pulse (- side)
PULSE B Phase-B feedback pulse (+ side)
LB Encoder B-phase pulse (differential line driver) LBR Encoder B-phase pulse (differential line driver)
PULSE B Phase-B feedback pulse (- side)
PULSE Z Phase-Z feedback pulse (+ side)
LZ Encoder Z-phase pulse (differential line driver) LZR Encoder Z-phase pulse (differential line driver)
PULSE Z Phase-Z feedback pulse (- side)
SVON Servo ON signal (- side) SVON Servo ON signal (+ side)
Speed command signal (+ side) Speed command signal (- side)
VC Analog speed command LG Control common
N.C. Analog GND N.C.
20 21 46 47
DICOM Digital I/F power supply input DICOM Digital I/F power supply input DOCOM Digital I/F common DOCOM Digital I/F common
ST1 Forward rotation start ST2 Reverse rotation start
LG Control common LG Control common
EMG Emergency stop LSP Forward rotation stroke end LSN Reverse rotation stroke end
*1 indicates use of shielded cables. Use shielded cables for wiring.
*2 indicates use of shielded twisted pair cables. Use shielded twisted pair cables for wiring.

Appendix 2.2 Example of connection with a servo amplifier manufactured by YASKAWA Electric Corporation
DOG Near-point dog signal QD73A1 CN1 -V series
1 2 3 4 5 6 7 8 9
N.C. N.C. N.C. Power supply (5 to 24V) RLS Lower limit signal FLS Upper limit signal
CONT. connector
CHANGE Speed-position switching command signal STOP Stop signal
READY Servo READY signal (+ side) READY Servo READY signal (- side)
PULSE A Phase-A feedback pulse (+ side)
A
PULSE A Phase-A feedback pulse (- side)
PULSE B Phase-B feedback pulse (+ side)
PULSE B Phase-B feedback pulse (- side)
PULSE Z Phase-Z feedback pulse (+ side)
PULSE Z Phase-Z feedback pulse (- side)
Appendix 2 Connection Examples Appendix 2.2 Example of connection with a servo amplifier manufactured by YASKAWA Electric Corporation
SVON Servo ON signal (- side) SVON Servo ON signal (+ side)
14 +24VIN
Speed command signal (+ side) Speed command signal (- side)
N.C. Analog GND N.C.
External power supply · SERVO connector

DOG Near-point dog signal QD73A1 CN1 -V series
1 2 3 4 5 6 7 8 9
N.C. N.C. N.C. Power supply (5 to 24V) RLS Lower limit signal FLS Upper limit signal
CONT. connector
CHANGE Speed-position switching command signal STOP Stop signal
READY Servo READY signal (+ side) READY Servo READY signal (- side)
PULSE A Phase-A feedback pulse (+ side)
PULSE A Phase-A feedback pulse (- side)
PULSE B Phase-B feedback pulse (+ side)
PULSE B Phase-B feedback pulse (- side)
PULSE Z Phase-Z feedback pulse (+ side)
PULSE Z Phase-Z feedback pulse (- side)
SVON Servo ON signal (- side) SVON Servo ON signal (+ side)
47 +24VIN
Speed command signal (+ side) Speed command signal (- side)
N.C. Analog GND N.C.
External power supply · SERVO connector

Appendix 3 Comparison of the QD73A1 and the AD70/A1SD70
(1) Performance specification comparison
Specifications
Item
QD73A1 AD70 A1SD70
Number of occupied I/O points 48 points (I/O assignment: empty 16 points and
32 points (special 32
points and special 32
Speed command 1 to 4000000(pulse/s) 1 to 400000(pulse/s)
In-position range 1 to 20479pulse 1 to 2047pulse
With OPR address change
With OPR address change
OPR method and OPR direction depend on the
OPR method and OPR direction depend on the
parameter setting.
switch setting.
Internal current consumption 5VDC 0.52A 5VDC 0.3A
terminal block No external power supply +15VDC 0.2A, -15VDC, 0.02A
External dimensions 98(H)mm × 55.2(W)mm × 90(D)mm 250(H)mm × 37.5(W)mm
130(H)mm × 69.5(W)mm
× 93.6(D)mm
Weight 0.20kg 0.5kg 0.4kg
Appendix 3 Comparison of the QD73A1 and the AD70/A1SD70
(from a start request to analog

Item
QD73A1 AD70 A1SD70
ERR. ERR.1/ERR.2 (Minor/major error)
None (check with X signal) SV RDY (Servo READY signal)
None (check with X signal) DOG (Near-point dog signal)
None (check with X signal) STOP (Stop signal)
None (check with X signal) FLS (Upper limit signal)
None (check with X signal) RLS (Lower limit signal)
None (check with X signal) IN-POS. (In-position)
None (check in the buffer memory) POLE (Deviation counter polarity)
None (check in the buffer memory) 2N (Deviation counter value)
None (check with Y signal) PC RDY (PLC READY signal)
None (check with X signal) ZERO (OPR request signal)
None (check with X signal) EEX (Excessive error)
None (check with X signal) WDT ERR. (Hardware error)
None (check with X signal) V-MODE (Operating status)
Zero/gain adjustment • Adjustment using the UP/DOWN switch
Mode switch Intelligent function module switch DIP switch
All the other specifications are the same.
RUN None · ZERO None · GAIN None

(2) Function comparison

amount after near-point dog ON, which is the same
Appendix 3 Comparison of the QD73A1 and the AD70/A1SD70
writing a new current value in the buffer memory.

Accumulated pulse error detection
Module status monitor function ×
Error history function ×
Module error collection function ×
Error clear function ×

Remark
Positioning execution time (BUSY signal (X14) ON to Positioning complete signal (X15) ON) of the QD73A1 and AD70/A1SD70 may be different since their internal processing methods are different. As a result, the timing when In-position signal (X16) turns on may also vary. Adjust positioning execution time using the following methods if the difference of the execution time (or the timing when In- position signal (X16) turns on) affects the system.
Pr.6 Pr.7

Appendix 3 Comparison of the QD73A1 and the AD70/A1SD70

: Usable ×: Unusable
X20 OPR start complete signal ×
X21 Absolute positioning start complete signal ×
X22 Forward start complete signal ×
X23 Reverse start complete signal ×
X24 Synchronization flag ×
X2A Zero/gain adjustment data writing complete flag ×
X2B Zero/gain adjustment change complete flag ×
X2C Set value change complete flag ×
X2D Operating status of the speed-position control
Y1A Zero/gain adjustment data writing request signal ×
Y1B Zero/gain adjustment change request signal ×
Y1C Set value change request signal ×
*1 For assignment to X/Y10 to X/Y2F
All the other I/O signals are the same.
switch mode ×

(5) Buffer memory address comparison
Buffer memory address (decimal)
Buffer memory area name
QD73A1 AD70/A1SD70
Current value change request 90
Speed change request 91
Analog output adjustment area 2
Zero/gain adjustment specification 94
Zero/gain adjustment value specification 95
Factory default zero/gain adjustment value
Zero/gain execution status 112
Zero/gain adjustment status 113
Deviation counter value (pulse)
Movement amount after near-point dog ON
Error history (0 to 16) 120 to 183
Error history pointer 184
Maximum accumulated pulse value
Appendix 3 Comparison of the QD73A1 and the AD70/A1SD70
Minimum accumulated pulse value
Accumulated pulse error detection function status 204
Reference value measurement flag 205
Positioning pattern 301 60
Alert output accumulated pulse setting value
Immediate stop accumulated pulse setting value
Alert output accumulated pulse setting value
Immediate stop accumulated pulse setting value
Accumulated pulse setting value selection 408
Accumulated pulse error detection request 409

Buffer memory area name
QD73A1 AD70/A1SD70
Measurement start request 410
Reference value write request 411
All the other buffer memory addresses are the same.
Description
put Signal name
QD73A1 AD70/A1SD70
Input Power supply Terminal block None ±15VDC (±14.55 to ±15.45V)
Phase-A feedback pulse (PULSE A)
Phase-B feedback pulse (PULSE B)
Phase-Z feedback pulse (PULSE Z)
Phase-A feedback pulse (PULSE A)
Phase-B feedback pulse (PULSE B)
Phase-Z feedback pulse (PULSE Z)
Phase-A feedback pulse (PULSE A)
Phase-B feedback pulse (PULSE B)
Phase-Z feedback pulse (PULSE Z)
All the other external I/O signals are the same.

Appendix 4 When Using GX Developer
This section describes the operating procedure of GX Developer.
When using GX Developer, configure the parameter settings and the auto refresh settings with the sequence program.
For applicable software versions, refer to the following.
Page 22, Section 2.1 (4)
Configure the following settings when using GX Developer.
I/O assignment Set the type of the module to be mounted and the I/O signal
range. Page 275, Appendix 4 (1)
Configure the switch setting of the intelligent function
module. Page 276, Appendix 4 (2)
Configure the setting on "I/O assignment" in "PLC parameter".
Parameter [PLC parameter] [I/O assignment]
Appendix 4 When Using GX Developer Appendix 4.1 Operation of GX Developer

Type Select "Intelli.".
Model name Enter the model name of the module.
Points The QD73A1 uses two slots. Select "Empty" and "0point" or "16points" for the first slot. Select "Intelli."
and "32points" for the second slot.
StartXY Enter any start I/O number of the QD73A1.
Intelligent function module · switch setting

Configure the setting on "Switch setting" in "PLC parameter".
Parameter [PLC parameter] [I/O assignment] Click the button.

Select "HEX.".
b0 Rotation direction setting
0 Positive voltage is output when the positioning address increases.
1 Negative voltage is output when the positioning address increases.
0 0 0 Fixed to 0 (Empty) When a value is set, the value is ignored.
b7 b6 b5 b4 Accumulated pulse setting (unit: pulse)*1
0 -14800 to 14800 (default value)
0 0 0 1 -3700 to 3700 [Selection 1]
0 0 1 0 -7400 to 7400 [Selection 2]
0 0 1 1 -11100 to 11100 [Selection 3]
0 1 0 0 -14800 to 14800 [Selection 4]
0 1 0 1 -37000 to 37000 [Selection 5]
0 1 1 0 -74000 to 74000 [Selection 6]
0 1 1 1 -111000 to 111000 [Selection 7]
1 0 0 0 -148000 to 148000 [Selection 8]
b9 b8 Multiplication setting
0 0 Fixed to 0 (Empty) When a value is set, the value is ignored.
b12 OPR direction setting
0 Reverse direction (address decreasing)
1 Forward direction (address increasing)
b13 OPR method setting
0 Near-point dog method
0 0 Fixed to 0 (Empty) When a value is set, the value is ignored.

Encoder I/F setting and Analog voltage resolution setting
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
0
Fixed to 0 Fixed to 0
b1 and b0: Encoder I/F setting 00 or 01: Open collector output 10: TTL output 11: Differential output
b5 and b4: Analog voltage resolution setting 00 or 01: 12-bit resolution 10: 14-bit resolution 11: 16-bit resolution
"00 or 01" means that the setting is valid with either value. When a value is set in b15 to b6, b3, or b2, the value is ignored.
b0 Feedback pulse addition/subtraction setting*2
0 Add when the phase A proceeds 90 degrees than phase B.
1 Subtract when the phase A proceeds 90 degrees than phase B.
b3 to b1 -
0 Fixed to 0 (Empty) When a value is set, the value is ignored.
b4 Deviation counter clear setting
0 Clear the deviation counter when Servo READY signal turns off.
1 Do not clear the deviation counter when Servo READY signal turns off.
b15 to b5 -
Appendix 4 When Using GX Developer Appendix 4.1 Operation of GX Developer
0 Fixed to 0 (Empty) When a value is set, the value is ignored.
Zero/gain adjustment mode/Normal mode setting
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
0
When a value is set in b11 to b0, the value is ignored.
Switch 5 Fixed to 0 (Empty) When a value is set, the value is ignored.
*1 When setting values (values in b7 to b4 of Switch 1) are 1111H to 1001H, the setting becomes the same as the one for
the default value (0000H)
*2 The setting becomes enabled only when "1: Negative voltage is output when the positioning address increases." is set for "Rotation direction setting" of Switch 1. When "0: Positive voltage is output when the positioning address increases." is set, the setting value of "Feedback pulse addition/subtraction setting" is ignored.

One of the pulse generators that converts input data into binary data (on and off)
A switch used in positioning systems, which is placed before the original point of a workpiece. When this switch
turns on, the feedrate is switched to creep speed. Therefore, there is time required for the deceleration from the
federate to the creep speed while this switch is on.
A signal that indicates the normal status of a servo amplifier. A servo amplifier is operable only when it is normal
and this signal is on.
A motor that rotates according to a command. This motor is highly responsive, therefore frequent and rapid start
and stop are available with high precision. DC and AC type motors are available as well as high power motors.
Feedback control is available with the included pulse generator that detects the number of rotations.
Pulses that are accumulated in the deviation counter inside the QD73A1. The difference between command
pulses and feedback pulses becomes accumulated pulses.
Accumulated pulses that are proportional to the command pulse frequency are constantly output while the
QD73A1 is operating. The number of accumulated pulses becomes "0" when positioning is completed.
Command pulse frequency f Accumulated pulses
The analog output voltage value from the QD73A1 is proportional to the number of accumulated pulses.

(6) Drive unit (servo amplifier)
A generic term for drive units that support analog voltage inputs. The commands that are output from the
QD73A1 are low voltage. This unit is used to amplify the energy and activate a motor. The unit, also called a
servo amplifier, is an accessory on a servomotor.
A device that generates pulses. For example, by attaching this device on a motor axis, pulses can be generated
by the rotation of the axis.
Pulses that are fed back from the encoder to the QD73A1 according to the motor's actual rotation amount
A counter that counts up and down the difference between the number of command pulses and feedback pulses.
The difference between command pulses and feedback pulses are accumulated in the deviation counter as
"accumulated pulses". The number of accumulated pulses in the deviation counter becomes "0" when positioning
is completed.
PG0 of a pulse generator (encoder), that is detected once in one rotation
A generic term for various objects being controlled, including moving objects such as tools
(rotation degree) · Appendix 5 Terms



Memo
A
Appendix 6 External Dimensions

*The manual number is given on the bottom left of the back cover.
July 2012 SH(NA)-081075ENG-A First edition
November 2012 SH(NA)-081075ENG-B The accumulated pulse error detection function is added.
September 2014 SH(NA)-081075ENG-C The feedback pulse addition/subtraction setting, deviation counter clear setting, and
deviation counter value monitor are added.
The movement amount after near-point dog ON (absolute value) is added and external
wiring diagrams are corrected.
Japanese manual version SH-081074-F
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric
Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the
contents noted in this manual.

Please confirm the following product warranty details before using this product.
If any faults or defects (hereinafter "Failure") found to be the responsibility of Mitsubishi occurs during use of the product within the gratis warranty term, the product shall be repaired at no cost via the sales representative or Mitsubishi Service Company. However, if repairs are required onsite at domestic or overseas location, expenses to send an engineer will be solely at the customer's discretion. Mitsubishi shall not be held responsible for any re-commissioning, maintenance, or testing on-site that involves replacement of the failed module. [Gratis Warranty Term] The gratis warranty term of the product shall be for one year after the date of purchase or delivery to a designated place. Note that after manufacture and shipment from Mitsubishi, the maximum distribution period shall be six (6) months, and the longest gratis warranty term after manufacturing shall be eighteen (18) months. The gratis warranty term of repair parts shall not exceed the gratis warranty term before repairs. [Gratis Warranty Range] (1) The range shall be limited to normal use within the usage state, usage methods and usage environment, etc., which follow the conditions and precautions, etc., given in the instruction manual, user's manual and caution labels on the product. (2) Even within the gratis warranty term, repairs shall be charged for in the following cases. 1. Failure occurring from inappropriate storage or handling, carelessness or negligence by the user. Failure caused by the user's hardware or software design. 2. Failure caused by unapproved modifications, etc., to the product by the user. 3. When the Mitsubishi product is assembled into a user's device, Failure that could have been avoided if functions or structures, judged as necessary in the legal safety measures the user's device is subject to or as necessary by industry standards, had been provided. 4. Failure that could have been avoided if consumable parts (battery, backlight, fuse, etc.) designated in the instruction manual had been correctly serviced or replaced. 5. Failure caused by external irresistible forces such as fires or abnormal voltages, and Failure caused by force majeure such as earthquakes, lightning, wind and water damage. 6. Failure caused by reasons unpredictable by scientific technology standards at time of shipment from Mitsubishi. 7. Any other failure found not to be the responsibility of Mitsubishi or that admitted not to be so by the user.
(1) Mitsubishi shall accept onerous product repairs for seven (7) years after production of the product is discontinued. Discontinuation of production shall be notified with Mitsubishi Technical Bulletins, etc. (2) Product supply (including repair parts) is not available after production is discontinued.
Overseas, repairs shall be accepted by Mitsubishi's local overseas FA Center. Note that the repair conditions at each FA Center may differ.
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation of damages caused by any cause found not to be the responsibility of Mitsubishi, loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products, special damages and secondary damages whether foreseeable or not, compensation for accidents, and compensation for damages to products other than Mitsubishi products, replacement by the user, maintenance of on-site equipment, start-up test run and other tasks.
The specifications given in the catalogs, manuals or technical documents are subject to change without prior notice.

Microsoft, Windows, Windows Vista, Windows NT, Windows XP, Windows Server, Visio, Excel, PowerPoint, Visual Basic,
Visual C++, and Access are either registered trademarks or trademarks of Microsoft Corporation in the United States,
Japan, and other countries.
Intel, Pentium, and Celeron are either registered trademarks or trademarks of Intel Corporation in the United States and
other countries.
Ethernet is a registered trademark of Xerox Corp.
All other company names and product names used in this manual are either trademarks or registered trademarks of their
respective companies.



HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN NAGOYA WORKS : 1-14 , YADA-MINAMI 5-CHOME , HIGASHI-KU, NAGOYA , JAPAN
When exported from Japan, this manual does not require application to the Ministry of Economy, Trade and Industry for service transaction permission.
Specifications subject to change without notice.
What the fault codes shown on the display mean and how to clear them.
| Code | Meaning | Fix | |
|---|---|---|---|
| ON*3 | Intentional stop | p.232 |
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| 0pulse | At the input of Speed-position switching command signal (CHANGE) | p.200 | |
| 1 | When PLC READY signal (Y2D) is turned on | p.212 | |
| 1 | p.212 | ||
| 2147483647 pulse | When PLC READY signal (Y2D) is turned on | p.216 | |
| 0pulse | p.216 | ||
| 0 | When accumulated pulse error detection is requested (When " Cd.18 Accumulated pulse error detection request" is changed from 0 to 1.) | p.228 | |
| 0 | p.228 | ||
| 0: Set with pulse | p.228 | ||
| 0: No request | | p.228 |