Mitsubishi Electronics P32

13 pages·2 MB·Air Conditioner·PDF·ENDEFRITNLJA
Mitsubishi Electronics P32
Table of Contents 42 sections Contents · 1. Safety precautions · 1.1. Before installation and electric work · Symbols used in the text · … ShowHide
Contentsp.61. Safety precautionsp.61.1. Before installation and electric workp.6Symbols used in the textp.61.2. Precautions for devices that use R410A or R407C refrigerantp.61.3. Before getting installedp.71.5. Before starting the test runp.71.4. Before getting installed (moved) - electrical workp.72. Indoor unit accessoriesp.73. Selecting an installation sitep.73.2. Securing installation and service spacep.83.3. Combining indoor units with outdoor unitsp.84. Fixing hanging boltsp.84.1 Fixing hanging boltsp.8Hanging structurep.86.1. Refrigerant pipe and drain pipe specificationsp.96.2. Refrigerant pipe, drain pipep.97. Connecting refrigerant pipes and drain pipesp.97.1. Refrigerant piping workp.97.2. Drain piping workp.9Cautions On Refrigerant Pipingp.97.3. Confirming drain dischargep.10SWE SWEp.10OFF ON OFF ONp.108. Duct workp.109. Electrical wiringp.10Precautions on electrical wiringp.10Types of control cablesp.109.1. Power supply wiringp.119.3. Connecting electrical connectionsp.119.2. Connecting remote controller, indoor and outdoor transmission cablesp.119.4. External I/O specificationsp.129.5. Selecting the external static pressurep.12A SWA B SWCp.12C SW1 D SW11p.12E SW12 F SW14p.129.6. Setting addressesp.129.7. Sensing room temperature with the built-in sensor in a remote controllerp.12This product is designed and intended for use in the residential, commer-p.13The product at hand is based on the following EU regulations:p.13Please be sure to put the contact address/telephone number onp.13KB79H130H01p.13
Page 2 of the Mitsubishi Electronics P32 user manual
Page 2 · click to enlarge
Page 2
Mitsubishi Electronics P32 diagram (page 2)
Fig. 1

G Service space (viewed from the direction of arrow)

ModelABCDE PEFY-P15,20,25,32VMS1(L)-E700752798660800 PEFY-P40,50VMS1(L)-E9009529988601000 PEFY-P63VMS1(L)-E110011521198 10601200
55.15.2 [Fig. 5.1.1] [Fig. 5.1.2] C D A D B C E C Nuts (field supply) A Unit body D Washers (accessory) B Lifting machine E M10 hanging bolt (field supply)[Fig. 5.2.1] A A Indoor unit’s bottom surface

C Drain pipe (O.D. ø32) * only on the PEFY-P·VMS1-E model

Page 3 of the Mitsubishi Electronics P32 user manual
Page 3 · click to enlarge
Page 3
77.1 [Fig. 7.1.1] [Fig. 7.1.3] A B C A A Cut here B Remove brazed cap A Thermal insulation [Fig. 7.1.2] D E B Pull out insulation A C Wrap with damp cloth D Return to original position A Cool by a wet cloth E Ensure that there is no gap here F Wrap with insulating tape F 7.2 [Fig. 7.2.1] Max. 20m 1.5-2m C Max. 300mm Correct piping Wrong piping N B A Insulation (9 mm or more) B B Downward slope (1/100 or more) A J C Support metal K F K Air bleeder L Raised L O M Odor trap Grouped piping D O. D. ø32 PVC TUBE B M E Make it as large as possible. About 10 cm. F Indoor unit D E D D G Make the piping size large for grouped piping. H Downward slope (1/100 or more) F F F I O. D. ø38 PVC TUBE for grouped piping. G (9 mm or more insulation) PEFY-P·VMS1-E model H I J Up to 550 mm N Drain hose (accessory) O Horizontal or slightly upgradient [Fig. 7.2.2] [Fig. 7.2.3] K J I F G A B F G A B 35 25 25 H 5 25 H C D E E D E I C A Indoor unit A Indoor unit B Insulation pipe (long) (accessory) B Insulation pipe (short) (accessory) C Tie band (accessory) C Tie band (accessory) D Visible part D Band fixing part E Insertion margin E Insertion margin F Drain hose (accessory) F Drain hose (accessory) G Drain pipe (O.D. ø32 PVC TUBE, field supply) G Drain pipe (O.D. ø32 PVC TUBE, field supply) H Insulating material (field supply) H Insulating material (field supply) I Tie band (accessory) I Max.145 ± 5 mm J Max.180 ± 5 mm K To be gap free. The joint section of the insulation material meet must be at the top.
Mitsubishi Electronics P32 diagram (page 3)
Fig. 2
Page 4 of the Mitsubishi Electronics P32 user manual
Page 4 · click to enlarge
Page 4
Mitsubishi Electronics P32 diagram (page 4)
Fig. 3
99.19.2 [Fig. 9.1.1] A B D E C A Switch 16 A B Overcurrent protection 16 A C Indoor unit D Total operating current be less than 16 A E Pull box
Page 5 of the Mitsubishi Electronics P32 user manual
Page 5 · click to enlarge
Page 5
Mitsubishi Electronics P32 diagram (page 5)
Fig. 4

E Use PG bushing to keep the weight of the cable and external force from being applied to the power supply terminal connector. Use a cable tie to secure the cable.

P Transmission line to the remote controller, terminal bed for indoor unit and BC controller

D The earth wire from two cables are connected together to the S terminal. (Dead-end connection)

E Insulation tape (To keep the earth wire of the shielded cable from coming in contact with the transmis- sion terminal)

Page 6 of the Mitsubishi Electronics P32 user manual — Table of Contents
Page 6 · Contents
Contents

Contents

Contentsp.61. Safety precautionsp.61.1. Before installation and electric workp.6Symbols used in the textp.61.2. Precautions for devices that use R410A or R407C refrigerantp.61.3. Before getting installedp.71.5. Before starting the test runp.71.4. Before getting installed (moved) - electrical workp.72. Indoor unit accessoriesp.73. Selecting an installation sitep.73.2. Securing installation and service spacep.83.3. Combining indoor units with outdoor unitsp.84. Fixing hanging boltsp.84.1 Fixing hanging boltsp.8Hanging structurep.86.1. Refrigerant pipe and drain pipe specificationsp.96.2. Refrigerant pipe, drain pipep.97. Connecting refrigerant pipes and drain pipesp.97.1. Refrigerant piping workp.97.2. Drain piping workp.9Cautions On Refrigerant Pipingp.97.3. Confirming drain dischargep.10SWE SWEp.10OFF ON OFF ONp.108. Duct workp.109. Electrical wiringp.10Precautions on electrical wiringp.10Types of control cablesp.109.1. Power supply wiringp.119.3. Connecting electrical connectionsp.119.2. Connecting remote controller, indoor and outdoor transmission cablesp.119.4. External I/O specificationsp.129.5. Selecting the external static pressurep.12A SWA B SWCp.12C SW1 D SW11p.12E SW12 F SW14p.129.6. Setting addressesp.129.7. Sensing room temperature with the built-in sensor in a remote controllerp.12This product is designed and intended for use in the residential, commer-p.13The product at hand is based on the following EU regulations:p.13Please be sure to put the contact address/telephone number onp.13KB79H130H01p.13
Page 7 of the Mitsubishi Electronics P32 user manual — 3. Selecting an installation site
Page 7 · click to enlarge
Page 7
  • Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections. - The refrigerator oil will degrade if it is mixed with a large amount of mineral oil.
  • Use liquid refrigerant to fill the system. - If gas refrigerant is used to seal the system, the composition of the refriger-
  • Install the power cable so that tension is not applied to the cable. - Tension may cause the cable to break and generate heat and cause a fire.
  • Install an leak circuit breaker, as required. - If an leak circuit breaker is not installed, electric shock may result.
  • Use power line cables of sufficient current carrying capacity and rating. - Cables that are too small may leak, generate heat, and cause a fire.
  • Use only a circuit breaker and fuse of the specified capacity. - A fuse or circuit breaker of a larger capacity or a steel or copper wire may

ant in the cylinder will change and performance may drop. • Do not use a refrigerant other than R410A or R407C. - If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may

cause the refrigerator oil to deteriorate. • Use a vacuum pump with a reverse flow check valve. - The vacuum pump oil may flow back into the refrigerant cycle and cause the

  • result in a general unit failure or fire.
  • Do not wash the air conditioner units. - Washing them may cause an electric shock.
  • Be careful that the installation base is not damaged by long use. - If the damage is left uncorrected, the unit may fall and cause personal injury

refrigerator oil to deteriorate. • Do not use the following tools that are used with conventional refriger- ants. (Gauge manifold, charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge, refrigerant recovery equipment) - If the conventional refrigerant and refrigerator oil are mixed in the R410A or

or property damage. • Install the drain piping according to this Installation Manual to ensure proper drainage. Wrap thermal insulation around the pipes to prevent condensation. - Improper drain piping may cause water leakage and damage to furniture

R407C, the refrigerant may deteriorated. - If water is mixed in the R410A or R407C, the refrigerator oil may deteriorate. - Since R410A or R407C does not contain any chlorine, gas leak detectors for

and other possessions. • Be very careful about product transportation. - Only one person should not carry the product if it weighs more than 20 kg. - Some products use PP bands for packaging. Do not use any PP bands for a

GB D F E I NL P GR RU TR CZ SV HG PO

  • conventional refrigerants will not react to it.
  • Do not use a charging cylinder. - Using a charging cylinder may cause the refrigerant to deteriorate.
  • Be especially careful when managing the tools. - If dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deterio-

means of transportation. It is dangerous. - Do not touch the heat exchanger fins. Doing so may cut your fingers. - When transporting the outdoor unit, suspend it at the specified positions on

rate.

the unit base. Also support the outdoor unit at four points so that it cannot slip sideways. • Safely dispose of the packing materials. - Packing materials, such as nails and other metal or wooden parts, may cause

1.3. Before getting installed

  • Caution:
  • Do not install the unit where combustible gas may leak. - If the gas leaks and accumulates around the unit, an explosion may result.
  • Do not use the air conditioner where food, pets, plants, precision instruments, or artwork are kept. - The quality of the food, etc. may deteriorate.
  • Do not use the air conditioner in special environments. - Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of

stabs or other injuries. - Tear apart and throw away plastic packaging bags so that children will not

play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.

1.5. Before starting the test run

the air conditioner or damage its parts. • When installing the unit in a hospital, communication station, or similar place, provide sufficient protection against noise. - The inverter equipment, private power generator, high-frequency medical

  • result in severe damage to internal parts. Keep the power switch turned on during the operational season.
  • Do not touch the switches with wet fingers. - Touching a switch with wet fingers can cause electric shock.
  • Do not touch the refrigerant pipes during and immediately after operation. - During and immediately after operation, the refrigerant pipes are may be hot

equipment, or radio communication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air condi- tioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting. • Do not install the unit on a structure that may cause leakage. - When the room humidity exceeds 80% or when the drain pipe is clogged,

  • and may be cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes.
  • Do not operate the air conditioner with the panels and guards removed. - Rotating, hot, or high-voltage parts can cause injuries.
  • Do not turn off the power immediately after stopping operation. - Always wait at least five minutes before turning off the power. Otherwise,

condensation may drip from the indoor unit. Perform collective drainage work together with the outdoor unit, as required. • The indoor models should be installed the ceiling over than 2.5 m from floor.

1.4. Before getting installed (moved) - electrical work

water leakage and trouble may occur.

telephone ground lines. Improper grounding may result in electric shock.

2. Indoor unit accessories

The unit is provided with the following accessories:

Part No.AccessoriesQtyPart No. Accessories Qty 6 Short pipe (ø12.7-ø15.88) : Model P50 only. 1 7 Short pipe (ø6.35-ø9.52) : Model P50 only. 1 8 Installation manual 1 9 Operation manual 1Part No.AccessoriesQty 1Insulation pipe (long)16Short pipe (ø12.7-ø15.88) : Model P50 only.1 2Insulation pipe (short)17Short pipe (ø6.35-ø9.52) : Model P50 only.1 3Tie band38Installation manual1 4Drain hose19Operation manual1 5Washer8

3. Selecting an installation site

  • Select a site with sturdy fixed surface sufficiently durable against the weight of unit.
  • Select a site where refrigerant piping can easily be led to the outside.
  • Select a site which allows the supply air to be distributed fully in room.
  • Before installing unit, the routing to carry in unit to the installation site should be determined.
  • Do not install unit at a site with oil splashing or steam in much quantity.
  • Do not install unit at a site where combustible gas may generate, flow in, stagnate or leak.
  • Select a site where the unit is not affected by entering air.
  • Select a site where the flow of supply and return air is not blocked.
  • Do not install unit at a site where equipment generating high frequency waves (a high frequency wave welder for example) is provided.
Page 8 of the Mitsubishi Electronics P32 user manual — Hanging structure
Page 8 · click to enlarge
Page 8
  • Do not install unit at a site where fire detector is located at the supply air side. (Fire detector may operate erroneously due to the heated air supplied during heating operation.)

3.2. Securing installation and service space

  • Select the optimum direction of supply airflow according to the configuration of the room and the installation position.
  • When special chemical product may scatter around such as site chemical plants and hospitals, full investigation is required before installing unit. (The plastic components may be damaged depending on the chemical product applied.)
  • As the piping and wiring are connected at the bottom and side surfaces, and the maintenance is made at the same surfaces, allow a proper space properly. For the efficient suspension work and safety, provide a space as much as possible.
  • If the unit is run for long hours when the air above the ceiling is at high temperature/high humidity (due point above 26 ° C), due condensation may be produced in the indoor unit. When operating the units in this condition, add insulation material (10-20 mm) to the entire surface of the indoor unit to avoid due condensation.

A Access door B Electrical parts box

C Air inlet D Air outlet

E Ceiling surface F Service space (viewed from the side)

3.1. Install the indoor unit on a ceiling strong enough to sustain its weight

G Service space (viewed from the direction of arrow)

1 600 mm or more 2 100 mm or more

3 10 mm or more 4 300 mm or more

3.3. Combining indoor units with outdoor units

GB D F E I NL P GR RU TR CZ SV HG PO

For combining indoor units with outdoor units, refer to the outdoor unit installation manual.

4. Fixing hanging bolts

4.1 Fixing hanging bolts

  • If necessary, reinforce the hanging bolts with anti-quake supporting members as countermeasures against earthquakes. * Use M10 for hanging bolts and anti-quake supporting members (field supply).

A Center of gravity

(Give site of suspension strong structure.)

Hanging structure

  • Ceiling: The ceiling structure varies from building to one another. For detailed information, consult your construction company.

Center of gravity and Product Weight

Model nameWLXYZProduct Weight (kg) PEFY-P15VMS1(L)-E62575226333810519 PEFY-P20VMS1(L)-E62575226333810519 PEFY-P25VMS1(L)-E62575226333810519 PEFY-P32VMS1(L)-E62575227534010420 PEFY-P40VMS1(L)-E62595228042210424 PEFY-P50VMS1(L)-E62595228042210424 PEFY-P63VMS1(L)-E625115228551110428 5. Installing the unit 5.1. Hanging the unit body 5.2. Confirming the unit’s position and fixs Bring the indoor unit to an installation site as it is packed. ing hanging bolts s To hang the indoor unit, use a lifting machine to lift and pass through the hanging bolts. s Use the gage supplied with the panel to confirm that the unit body and hanging bolts are positioned in place. If they are not positioned in place, [Fig. 5.1.1] (P.2) it may result in dew drops due to wind leak. Be sure to check the positional A Unit body relationship. B Lifting machine s Use a level to check that the surface indicated by A is at level. Ensure [Fig. 5.1.2] (P.2) that the hanging bolt nuts are tightened to fix the hanging bolts. s To ensure that drain is discharged, be sure to hang the unit at level using C Nuts (field supply) a level. D Washers (accessory) E M10 hanging bolt (field supply) [Fig. 5.2.1] (P.2) A Indoor unit’s bottom surface Caution: Install the unit in horizontal position. If the side with drain port is installed higher, water leakage may be caused. 6. Refrigerant pipe and drain pipe specifications To avoid dew drops, provide sufficient antisweating and insulating work to the re1 Select the thickness of insulating material by pipe size. frigerant and drain pipes. Pipe size Insulating material’s thickness When using commercially available refrigerant pipes, be sure to wind commer6.4 mm to 25.4 mm More than 10 mm cially available insulating material (with a heat-resisting temperature of more than 100 °C and thickness given below) onto both liquid and gas pipes. 28.6 mm to 38.1 mm More than 15 mm Pipe sizeInsulating material’s thickness 6.4 mm to 25.4 mmMore than 10 mm 28.6 mm to 38.1 mmMore than 15 mm

2 If the unit is used on the highest story of a building and under conditions of high temperature and humidity, it is necessary to use pipe size and insulating material’s thickness more than those given in the table above.

3 If there are customer’s specifications, simply follow them.

Page 9 of the Mitsubishi Electronics P32 user manual — Cautions On Refrigerant Piping
Page 9 · click to enlarge
Page 9

6.1. Refrigerant pipe and drain pipe specifications

Model ItemR410AR407C or R22 15·20·25·32·40·506315·20·25·32·4050·63* Refrigerant pipe (Brazing connection)Liquid pipeø 6.35ø 9.52ø 6.35ø 9.52 Gas pipeø 12.7ø 15.88ø 12.7ø 15.88 Drain pipeO.D. ø 32O.D. ø 32

* When the Models P50 are used with R22 or R407C, use the supplied short pipes.

6.2. Refrigerant pipe, drain pipe

A Refrigerant pipe (liquid pipe)HP
B Refrigerant pipe (gas pipe)LP

C Drain pipe (O.D. ø32) * only on the PEFY-P·VMS1-E model

D Drain pipe (O.D. ø32, spontaneous draining)

7. Connecting refrigerant pipes and drain pipes

GB D F E I NL P GR RU TR CZ SV HG PO

7.1. Refrigerant piping work

  • Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. - If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and

This piping work must be done in accordance with the installation manuals for both outdoor unit and BC controller (simultaneous cooling and heating series R2).

  • the compressor may fail.
  • Use Suniso 4GS or 3GS (small amount) refrigerator oil to coat the flare and flange connection part. (For models using R22)
  • Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections. (For models using R410A or R407C) - The refrigerant used in the unit is highly hygroscopic and mixes with water
  • Series R2 is designed to operate in a system that the refrigerant pipe from an outdoor unit is received by BC controller and branches at the BC controller to connect between indoor units.
  • For constraints on pipe length and allowable difference of elevation, refer to the outdoor unit manual.

and will degrade the refrigerator oil.

  • The method of pipe connection is brazing connection.

7.2. Drain piping work

  • Ensure that the drain piping is downward (pitch of more than 1/100) to the outdoor (discharge) side. Do not provide any trap or irregularity on the way.
1. Cut the tip of the indoor unit piping, remove the gas, and then remove the brazed cap.
  • Ensure that any cross-wise drain piping is less than 20 m (excluding the difference of elevation). If the drain piping is long, provide metal braces to prevent it from waving. Never provide any air vent pipe. Otherwise drain may be ejected.
  • Use a hard vinyl chloride pipe O.D. ø32 for drain piping.

B Remove brazed cap

  • Ensure that collected pipes are 10 cm lower than the unit body’s drain port.
2. Pull out the thermal insulation on the site refrigerant piping, braze the unit piping, and replace the insulation in its original position. Wrap the piping with insulating tape.
  • Do not provide any odor trap at the drain discharge port.
  • Put the end of the drain piping in a position where no odor is generated.
  • Do not put the end of the drain piping in any drain where ionic gases are generated.

A Insulation (9 mm or more)

A Cool by a wet cloth • Pay strict attention when wrapping the copper piping since wrapping the piping may cause condensation instead of preventing it.

B Downward slope (1/100 or more)

A Thermal insulation B Pull out insulation

M Odor trap Grouped piping

C Wrap with damp cloth D Return to original position

E Ensure that there is no gap here F Wrap with insulating tape

D O. D. ø32 PVC TUBE

E Make it as large as possible. About 10 cm.

Cautions On Refrigerant Piping

s Be sure to use non-oxidative brazing for brazing to ensure that no for-

G Make the piping size large for grouped piping.

eign matter or moisture enter into the pipe. s Be sure to apply refrigerating machine oil over the flare connection seat-

H Downward slope (1/100 or more)

I O. D. ø38 PVC TUBE for grouped piping. (9 mm or more insulation) PEFY-P·VMS1-E model

ing surface and tighten the connection using a double spanner. s Provide a metal brace to support the refrigerant pipe so that no load is

J Up to 550 mm

imparted to the indoor unit end pipe. This metal brace should be pro- vided 50 cm away from the indoor unit’s flare connection.

N Drain hose (accessory)

O Horizontal or slightly upgradient

1. Insert the drain hose (accessory) into the drain port (insertion margin: 25mm). (The drain hose must not be bent more than 45 ° to prevent the hose from breaking or clogging.) (Attach the hose with glue for the hard vinyl chloride pipe, and fix it with the band (small, accessory).)

function and result in severe damage.

  • Caution:
  • Use refrigerant piping made of C1220 (Cu-DHP) phosphorus deoxidized copper as specified in the JIS H3300 “Copper and copper alloy seamless pipes and tubes”. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shaving particles, oils, moisture, or any other contaminant.
  • Never use existing refrigerant piping. - The large amount of chlorine in conventional refrigerant and refrigerator oil
2. Attach the drain pipe (O.D. ø32 PVC TUBE, field supply). (Attach the pipe with glue for the hard vinyl chloride pipe, and fix it with the band (small, accessory).)
3. Perform insulation work on the drain pipe (O.D. ø32 PVC TUBE) and on the socket (including elbow).
4. Check the drainage. (Refer to [Fig. 7.3.1])

in the existing piping will cause the new refrigerant to deteriorate.

5. Attach the insulating material (accessory), and fix it with the band (large, accessory) to insulate the drain port.
Show 8 more labels / short text on this page
A Cut here · Correct piping · Wrong piping · C Support metal · K Air bleeder · L Raised · F Indoor unit · [PEFY-P·VMS1-E model]
Page 10 of the Mitsubishi Electronics P32 user manual — Types of control cables
Page 10 · click to enlarge
Page 10

[Fig. 7.2.2] (P.3) * only on the PEFY-P·VMS1-E model

7.3. Confirming drain discharge

s Make sure that the drain-up mechanism operates normally for discharge

B Insulation pipe (long) (accessory)

and that there is no water leakage from the connections.

C Tie band (accessory)

  • Be sure to confirm the above in a period of heating operation.
  • Be sure to confirm the above before ceiling work is done in the case of a new construction.

F Drain hose (accessory)

G Drain pipe (O.D. ø32 PVC TUBE, field supply)

1. Remove the water supply port cover on the same side as the indoor unit piping.

H Insulating material (field supply)

I Tie band (accessory)

2. Fill water into the feed water pump using a feed water tank. In filling, be sure to put the end of the pump or tank in a drain pan. (If the insertion is incomplete, water may flow over the machine.)

J Max.180 ± 5 mm

K To be gap free. The joint section of the insulation material meet must be at the top.

3. Perform the test run in cooling mode, or turn on the switch SWE on the controller circuit board. (The drain pump and the fan are forced to operate without any remote controller operation.) Make sure using a transparent hose that drain is discharged.
1. Insert the drain hose (accessory) into the drain port. (The drain hose must not be bent more than 45 ° to prevent the hose from breaking or clogging.) The connecting part between the indoor unit and the drain hose may be disconnected at the maintenance. Fix the part with the accessory band, not be adhered.

SWE SWE

GB D F E I NL P GR RU TR CZ SV HG PO

OFF ON OFF ON

4. After confirmation, cancel the test run mode, and turn off the main power. When the switch SWE has been turned on, turn it off, and attach the water supply port cover into its original position.
2. Attach the drain pipe (O.D. ø32 PVC TUBE, field supply). (Attach the pipe with glue for the hard vinyl chloride pipe, and fix it with the band (small, accessory).)

SWE SWE

3. Perform insulation work on the drain pipe (O.D. ø32 PVC TUBE) and on the socket (including elbow).

OFF ON OFF ON

[Fig. 7.2.3] (P.3) * only on the PEFY-P·VMS1L-E model

A Insert pump's end 2 to 4 cm.

B Remove the water supply port.

B Insulation pipe (short) (accessory)

C About 2000 cc

C Tie band (accessory)

D Band fixing part

F Drain hose (accessory)

G Drain pipe (O.D. ø32 PVC TUBE, field supply)

H Insulating material (field supply)

I Max.145 ± 5 mm

8. Duct work

  • When connecting ducts, insert a canvas duct between the main body and the duct.

A Air inlet B Air outlet

  • Use non-combustible duct components.

C Access door D Ceiling surface

  • Install sufficient thermal insulation to prevent condensation forming on outlet duct flanges and outlet ducts.

E Canvas duct F Air filter

9. Electrical wiring

Precautions on electrical wiring

6. Be sure to connect control cables to the indoor unit, remote controller, and the outdoor unit.
7. Put the unit to the ground on the outdoor unit side.
8. Select control cables from the conditions given in page 11 .
1. Be sure to install an earth leakage breaker to the power.
2. Install the unit to prevent that any of the control circuit cables (remote controller, transmission cables) is brought in direct contact with the power cable outside the unit.

Types of control cables

1. Wiring transmission cables
  • Types of transmission cables
3. Ensure that there is no slack on all wire connections.

Design wiring in accordance with the following table .

4. Some cables (power, remote controller, transmission cables) above the ceiling may be bitten by mouses. Use as many metal pipes as possible to insert the cables into them for protection.
  • Cable diameter

More than 1.25 mm2

5. Never connect the power cable to leads for the transmission cables. Otherwise the cables would be broken.
Show 11 more labels / short text on this page
A Indoor unit · D Visible part · E Insertion margin · [PEFY-P·VMS1L-E model] · A Indoor unit · D Water · E Filling port · E Insertion margin · F Screw · <Indoor board> · G Inlet grille
Page 11 of the Mitsubishi Electronics P32 user manual — 9.2. Connecting remote controller, indoor and outdoor transmission cables
Page 11 · click to enlarge
Page 11
System configurationFor a single-refrigerant systemFor a multi-refrigerant system Transmission cable lengthLess than 120 mMore than 120 mRegardless of length Facility example (for noise judgment)Residence or independent store without noiseBuilding, clinic, hospital or communications station without noise supposedly generated from inverter equipment, private power generator, high-frequency medical equipment, radio-used communications equipment and so onAll facilities Types of transmission cablesVCTF, VCTFK, CVV, CVS, VVR, VVF, VCT or shielding wire CVVS or CPEVSShielding wire CVVS or CPEVS LengthLess than 120 mLess than 200 m
2. Remote controller cables
MA remote controllerM-NET remote controller Types of cablesSheathed 2-core cable (unshielded) CVVSheathed 2-core cable (unshielded) CVV Cable diameter0.3 to 1.25 mm20.3 to 1.25 mm2 LengthLess than 200 mAdd any portion in excess of 10 m to within the longest allowable transmission cable length 200 m (Shielding portion is more than 1.25 mm2)

GB D F E I NL P GR RU TR CZ SV HG PO

9.1. Power supply wiring

  • Power supply cords of appliances shall not be lighter than design 245 IEC 57 or 227 IEC 57.

9.3. Connecting electrical connections

  • A switch with at least 3 mm contact separation in each pole shall be provided by the Air conditioner installation.

Please identify the model name of the operation manual attached on the terminal bed box cover with that shown on the rating name plate.

Power cable sizemore than 1.5 mm 2
1. Remove the screw (2pcs) holding the cover to dismount the cover.

A Switch 16 A B Overcurrent protection 16 A

A Screw holding cover (2pcs) B Cover

D Total operating current be less than 16 A

2. Open knockout holes (Recommend to use a screwdriver or the like for this work.)

[Selecting non-fuse breaker (NF) or earth leakage breaker (NV)] To select NF or NV instead of a combination of Class B fuse with switch, use the following:

A Terminal bed box B Knockout hole

  • In the case of Class B fuse rated 15 A or 20 A, NF model name (MITSUBISHI): NF30-CS (15 A) (20 A) NV model name (MITSUBISHI): NV30-CA (15 A) (20 A) Use an earth leakage breaker with a sensitivity of less than 30 mA 0.1 s.
3. Fix power source wiring to terminal bed box by using buffer bushing for tensile force. (PG connection or the like.) Connect transmission wiring to transmission terminal bed through the knockout hole of terminal bed box using ordinary bushing.

E Use PG bushing to keep the weight of the cable and external force from being applied to the power supply terminal connector. Use a cable tie to secure the cable.

F Power source wiring G Tensile force

H Use ordinary bushing I Transmission wiring

9.2. Connecting remote controller, indoor and outdoor transmission cables

4. Connect the power source, Earth, transmission and remote controller wiring. The dismounting of the terminal bed box is not needed.
  • Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)

The “S” on indoor unit TB5 is a shielding wire connection. For specifications about the connecting cables, refer to the outdoor unit installation manual.

J Power source terminal bed K Terminal bed for indoor transmission

L Terminal bed for remote controller M To 1-phase power source

N Transmission line DC 30 V

  • Install a remote controller following the manual supplied with the remote controller.

O Terminal bed for outdoor transmission line (TB3)

P Transmission line to the remote controller, terminal bed for indoor unit and BC controller

  • Connect the “1” and “2” on indoor unit TB15 to a MA remote controller. (Nonpolarized 2-wire)
  • Connect the “M1” and “M2” on indoor unit TB5 to a M-NET remote controller. (Non-polarized 2-wire)

A Terminal bed B Round terminal

  • Connect the remote controller’s transmission cable within 10 m using a 0.75 mm 2

core cable. If the distance is more than 10 m, use a 1.25 mm2 junction cable.

D The earth wire from two cables are connected together to the S terminal. (Dead- end connection)

[Fig. 9.2.1] (P.4) MA Remote controller

[Fig. 9.2.2] (P.4) M-NET Remote controller

E Insulation tape (To keep the earth wire of the shielded cable from coming in con- tact with the transmission terminal)

A Terminal block for indoor transmission cable

B Terminal block for outdoor transmission cable

5. After wiring is complete, make sure again that there is no slack on the connections, and attach the cover onto the terminal bed box in the reverse order of removal.
  • DC 9 to 13 V between 1 and 2 (MA remote controller)
  • Notes:
  • Do not pinch the cables or wires when attaching the terminal bed box cover. Doing so may cause a risk of disconnection.
  • When accommodating the terminal bed box, make sure that the connectors on the box side are not removed. If removed, it cannot operate normally.
  • DC 24 to 30 V between M1 and M2 (M-NET remote controller)

[Fig. 9.2.3] (P.4) MA Remote controller

[Fig. 9.2.4] (P.4) M-NET Remote controller

A Non-polarized B TB15

C Remote Controller D TB5

  • The MA remote controller and the M-NET remote controller cannot be used at the same time or interchangeably.
Show 7 more labels / short text on this page
<Table 1> · C Indoor unit · E Pull box · C Remove · [Shield wire connection] · C Shield wire · C Remote controller
Page 12 of the Mitsubishi Electronics P32 user manual — 9.7. Sensing room temperature with the built-in sensor in a remote controller
Page 12 · click to enlarge
Page 12

9.4. External I/O specifications

9.5. Selecting the external static pressure

As the factory setting is for use under an external static pressure of 15 Pa, no switch operation is needed when using under the standard condition.

External static pressureSwitch operation 5 PaSWA SWC 3 2 2 1 1 15 PaSWA SWC 3 2 2 1 1 35 PaSWA SWC 3 2 2 1 1 50 PaSWA SWC 3 2 2 1 1
Mitsubishi Electronics P32 — 9.5. Selecting the external static pressure diagram (page 12)
Fig. 5 · 9.5. Selecting the external static pressure

GB D F E I NL P GR RU TR CZ SV HG PO

A SWA B SWC

C SW1 D SW11

E SW12 F SW14

9.6. Setting addresses

(Be sure to operate with the main power turned OFF.)

A SWA B SWC

C SW1 D SW11

E SW12 F SW14

  • There are two types of rotary switch setting available: setting addresses 1 to 9 and over 10, and setting branch numbers. 1 How to set addresses Example: If Address is “3”, remain SW12 (for over 10) at “0”, and match SW11(for 1 to 9) with “3”. 2 How to set branch numbers SW14 (Series R2 only) The branch number assigned to each indoor unit is the port number of the BC controller to which the indoor unit is connected. Leave it to “0” on the non-R2 series of units.
  • The rotary switches are all set to “0” when shipped from the factory. These switches can be used to set unit addresses and branch numbers at will.
  • The determination of indoor unit addresses varies with the system at site. Set them referring to the Data Book.

9.7. Sensing room temperature with the built-in sensor in a remote controller

If you want to sense room temperature with the built-in sensor in a remote control- ler, set SW1-1 on the control board to “ON”. The setting of SW1-7 and SW1-8 as necessary also makes it possible to adjust the air flow at a time when the heating thermometer is OFF.

·

Page 13 of the Mitsubishi Electronics P32 user manual — KB79H130H01
Page 13 · click to enlarge
Page 13

This product is designed and intended for use in the residential, commer-

cial and light-industrial environment.

The product at hand is based on the following EU regulations:

  • Low Voltage Directive 2006/95/EC
  • Electromagnetic Compatibility Directive 89/ 336/EEC, 2004/108/EC

Please be sure to put the contact address/telephone number on

this manual before handing it to the customer.

HEAD OFFICETOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

KB79H130H01

Ask about the Mitsubishi Electronics P32

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Mitsubishi Electronics P32

Be the first to ask — other owners or our team will answer.

Original document

Mitsubishi Electronics P32 manual PDF

13 pages·2 MB·Air Conditioner·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…