Front Coverp.1Manual Numberp.3Table of Contentsp.5Related manualsp.16Generic Names and Abbreviations Used in Manualsp.231. Introductionp.251.1 Programming Language in PLCsp.251.1.1 Types of programming languagesp.251.1.2 Applicability of programming languages in programming softwarep.261.1.3 Compatibility among programsp.262. Overview (Sequence Program)p.272.1 Introduction of Convenient Functionsp.272.1.1 Convenient functions for input processingp.272.1.2 Convenient functions for output processingp.282.1.3 Functions for supporting sequence controlp.282.2 Introduction of Applied Instructionsp.292.2.1 Major applied instructionsp.292.3 Analog/Positioning Special Controlp.312.4 Link and Communicationp.312.5 Introduction of Devices Constructing PLCp.322.5.1 Relationship among devicesp.322.5.2 Device listp.332.6 Program Memory and Devicesp.352.6.1 Memory structurep.352.6.2 Memory operations and latched (battery or EEPROM backed) devices (power ON/OFF and RUN/STOP)p.382.6.3 Types of backup methods against power failurep.442.6.4 Change between general devices and latched (battery backed) devicesp.452.6.5 How to initialize devices (battery backed)p.452.7 Types and Setting of Parametersp.462.7.1 Parameter listp.462.7.2 Parameter initial values and available tools for changing parameter valuesp.472.7.3 Memory capacity setting rangep.502.7.4 Compatible optional memory modelp.512.7.5 Keyword (entry code)p.522.7.6 Special unit initial value settingp.602.7.7 Positioning instruction settingp.602.7.8 Built-in CC-Link/LT Setup (dedicated to FX3UC-32MT-LT-2)p.602.7.9 Parameter settingsp.603. Instruction Listp.723.1 Basic Instructionsp.723.2 Step Ladder Instructionsp.743.3 Applied Instructions ... in Ascending Order of FNC Numberp.744. Devices in Detailp.854.1 Device Number Listp.854.2 I/O Relays [X, Y]p.914.2.1 Numbers of I/O relaysp.914.2.2 Functions and rolesp.924.2.3 Operation timing of I/O relaysp.934.3 Auxiliary Relay [M]p.944.3.1 Numbers of auxiliary relaysp.944.3.2 Functions and operation examplesp.944.4 State Relay [S]p.964.4.1 Numbers of state relaysp.964.4.2 Functions and operation examplesp.974.5 Timer [T]p.994.5.1 Numbers of timersp.994.5.2 Functions and operation examplesp.994.5.3 Set value specification methodp.1014.5.4 Cautions on routinesp.1014.5.5 Details on timer operation and timer accuracyp.1014.5.6 Program examples [off-delay timer and flicker timer]p.1024.5.7 Handling timers as numeric devicesp.1034.6 Counter [C]p.1044.6.1 Numbers of countersp.1044.6.2 Features of countersp.1044.6.3 Related devices (to specify counting direction) [32-bit counter]p.1054.6.4 Functions and operation examplesp.1054.6.5 Set value specification methodp.1064.6.6 Response speed of countersp.1074.6.7 Handling counters as numeric devicesp.1074.7 High-Speed Counter [C] (FX3S/FX3G/FX3GC PLCs)p.1094.7.1 Types and device numbers of high-speed countersp.1094.7.2 Input assignment for high-speed countersp.1114.7.3 Handling of high-speed countersp.1124.7.4 Current value update timing and comparison of current valuep.1124.7.5 Related devicesp.1124.7.6 Assignment of counter input terminal and switching of functionp.1134.7.7 Response frequency of high-speed countersp.1144.7.8 Cautions on usep.1164.8 High-Speed Counter [C] (FX3U/FX3UC PLC)p.1184.8.1 Types and device numbers of high-speed countersp.1184.8.2 Input assignment for high-speed countersp.1204.8.3 Handling of high-speed countersp.1214.8.4 Current value update timing and comparison of current valuep.1234.8.5 Related devicesp.1244.8.6 Changing the logic of external reset input signalp.1254.8.7 Assignment of counter input terminal and switching of functionp.1254.8.8 How to use 2-phase 2-count input counters C251 to C255 with 4 edge countingp.1264.8.9 Conditions for hardware counters to be handled as software countersp.1274.8.10 Response frequency of high-speed countersp.1284.8.11 Cautions on usep.1304.9 Data Register and File Register [D]p.1324.9.1 Numbers of data registers and file registersp.1324.9.2 Structures of data registers and file registersp.1334.9.3 Functions and operation examples of data registersp.1344.9.4 Functions and operation examples of file registersp.1364.9.5 Cautions on using file registersp.1394.10 Extension Register [R] and Extension File Register [ER]p.1404.10.1 Numbers of extension registers and extension file registersp.1404.10.2 Data storage destination and access methodp.1404.10.3 Structures of extension registers and extension file registersp.1414.10.4 Initialization of extension registers and extension file registersp.1414.10.5 Functions and operation examples of extension registersp.1424.10.6 Functions and operation examples of extension file registersp.1434.10.7 Cautions on using extension file registersp.1454.10.8 Registration of data in extension registers and extension file registersp.1464.11 Index Register [V and Z]p.1504.11.1 Numbers of index registersp.1504.11.2 Functions and structuresp.1504.11.3 Indexing of devicesp.1504.12 Pointer [P and I]p.1514.12.1 Numbers of pointersp.1514.12.2 Functions and operation examples of pointers for branchp.1514.12.3 Functions and operation examples of pointers for interruptp.1525. How to Specify Devices and Constants to Instructionsp.1555.1 Numeric Values Handled in PLC (Octal, Decimal, Hexadecimal and Real Numbers)p.1555.1.1 Types of numeric valuesp.1555.1.2 Conversion of numeric valuesp.1565.1.3 Handling of numeric values in floating point operationsp.1575.2 Specification of Constants K, H and E (Decimal, Hexadecimal and Real Number)p.1595.2.1 Constant K (decimal number)p.1595.2.2 Constant H (hexadecimal number)p.1595.2.3 Constant E (real number)p.1595.3 Character Stringsp.1605.3.1 Character string constant ("ABC")p.1605.3.2 Character string datap.1605.4 Specification of Digits for Bit Devices (Kn[ ]***)p.1615.5 Bit Specification of a Word Device (D[ ].b)p.1625.6 Direct Specification of Buffer Memory (U[ ]\G[ ])p.1625.7 Indexingp.1635.7.1 Indexing in basic instructionsp.1635.7.2 Indexing in applied instructionsp.1645.7.3 Indexing example for instruction with limited number of use.p.1666. What to Understand before Programmingp.1686.1 How to Read Explanation of Instructionsp.1686.2 Cautions on Creation of Fundamental Programsp.1716.2.1 Programming procedure and execution orderp.1716.2.2 Double output (double coil) operation and countermeasuresp.1726.2.3 Circuits which cannot be programmed and countermeasuresp.1736.3 I/O Processing and Response Delayp.1736.4 Mutual Relationship Among Program Flow Control Instructionsp.1746.5 General Rules for Applied Instructionsp.1766.5.1 Expression and operation type of applied instructionsp.1766.5.2 Handling of general flagsp.1786.5.3 Handling of operation error flagp.1806.5.4 Handling functions of extension flagp.1806.5.5 Limitation in the number of instructions and limitation in simultaneous instruction instancesp.1816.6 Symbolic information storage and block passwordp.1826.6.1 Storage of symbolic informationp.1826.6.2 Block passwordp.1827. Basic Instructionp.1837.1 LD, LDIp.1857.2 OUTp.1877.3 AND, ANIp.1907.4 OR, ORIp.1937.5 LDP, LDF, ANDP, ANDF, ORP, ORFp.1967.6 ORBp.2027.7 ANBp.2037.8 MPS, MRD, MPPp.2047.9 MC, MCRp.2077.10 INVp.2107.11 MEP, MEFp.2117.12 PLS, PLFp.2137.13 SET, RSTp.2167.14 NOPp.2197.15 ENDp.2207.16 Number of Instruction Steps and Specified Devicesp.2218. Program Flow – FNC 00 to FNC 09p.2228.1 FNC 00 – CJ / Conditional Jumpp.2238.1.1 CJ instruction and operations of contact and coilp.2278.1.2 Relationship between master control instruction and jump instructionp.2298.2 FNC 01 – CALL / Call Subroutinep.2308.2.1 Cautions on subroutines and interrupt routinesp.2328.3 FNC 02 – SRET / Subroutine Returnp.2348.4 FNC 03 – IRET / Interrupt Returnp.2358.5 FNC 04 – EI / Enable Interruptp.2378.6 FNC 05 – DI / Disable Interruptp.2388.7 FNC 06 – FEND / Main Routine Program Endp.2398.8 FNC 07 – WDT / Watchdog Timer Refreshp.2418.9 FNC 08 – FOR / Start a FOR/NEXT Loopp.2438.10 FNC 09 – NEXT / End a FOR/NEXT Loopp.2449. Move and Compare – FNC 10 to FNC 19p.2469.1 FNC 10 – CMP / Comparep.2479.2 FNC 11 – ZCP / Zone Comparep.2499.3 FNC 12 – MOV / Movep.2519.4 FNC 13 – SMOV / Shift Movep.2549.5 FNC 14 – CML / Complementp.2569.6 FNC 15 – BMOV / Block Movep.2589.6.1 Function of transfer between file registers and data registersp.2609.7 FNC 16 – FMOV / Fill Movep.2629.8 FNC 17 – XCH / Exchangep.2649.9 FNC 18 – BCD / Conversion to Binary Coded Decimalp.2669.10 FNC 19 – BIN / Conversion to Binaryp.26910. Arithmetic and Logical Operation (+, -, ×,÷ ) – FNC 20 to FNC 29p.27210.1 FNC 20 – ADD / Additionp.27310.2 FNC 21 – SUB / Subtractionp.27510.3 FNC 22 – MUL / Multiplicationp.27710.4 FNC 23 – DIV / Divisionp.28010.5 FNC 24 – INC / Incrementp.28310.6 FNC 25 – DEC / Decrementp.28510.7 FNC 26 – WAND / Logical Word ANDp.28610.8 FNC 27 – WOR / Logical Word ORp.28810.9 FNC 28 – WXOR / Logical Exclusive ORp.29010.10 FNC 29 – NEG / Negationp.29211. Rotation and Shift Operation – FNC 30 to FNC 39p.29411.1 FNC 30 – ROR / Rotation Rightp.29511.2 FNC 31 – ROL / Rotation Leftp.29711.3 FNC 32 – RCR / Rotation Right with Carryp.29911.4 FNC 33 – RCL / Rotation Left with Carryp.30111.5 FNC 34 – SFTR / Bit Shift Rightp.30311.6 FNC 35 – SFTL / Bit Shift Leftp.30511.6.1 Replacement of SFT instruction in F1 and F2 Seriesp.30711.7 FNC 36 – WSFR / Word Shift Rightp.30811.8 FNC 37 – WSFL / Word Shift Leftp.31011.9 FNC 38 – SFWR / Shift Write [FIFO/FILO Control]p.31211.10 FNC 39 – SFRD / Shift Read [FIFO Control]p.31512. Data Operation – FNC 40 to FNC 49p.31712.1 FNC 40 – ZRST / Zone Resetp.31812.2 FNC 41 – DECO / Decodep.32212.3 FNC 42 – ENCO / Encodep.32512.4 FNC 43 – SUM / Sum of Active Bitsp.32712.5 FNC 44 – BON / Check Specified Bit Statusp.33012.6 FNC 45 – MEAN / Meanp.33212.7 FNC 46 – ANS / Timed Annunciator Setp.33412.8 FNC 47 – ANR / Annunciator Resetp.33612.9 FNC 48 – SQR / Square Rootp.33712.10 FNC 49 – FLT / Conversion to Floating Pointp.33813. High-Speed Processing – FNC 50 to FNC 59p.34013.1 FNC 50 – REF / Refreshp.34113.1.1 What should be understood before using the REF instructionp.34413.2 FNC 51 – REFF / Refresh and Filter Adjustp.34513.2.1 What should be understood before using REFF instructionp.34713.3 FNC 52 – MTR / Input Matrixp.34813.3.1 Operation and cautions for the MTR instructionp.35113.4 FNC 53 – HSCS / High-Speed Counter Setp.35213.4.1 Common cautions on using instructions for high-speed counterp.35513.5 FNC 54 – HSCR / High-Speed Counter Resetp.35813.6 FNC 55 – HSZ / High-Speed Counter Zone Comparep.36113.6.1 Program in which comparison result is set to ON when power is turned ON [ZCP (FNC 11) instruction]p.36513.6.2 Table high-speed comparison mode (M8130)p.36713.6.3 Frequency control mode (HSZ and PLSY instructions) (M8132)p.37013.7 FNC 56 – SPD / Speed Detectionp.37313.8 FNC 57 – PLSY / Pulse Y Outputp.37713.9 FNC 58 – PWM / Pulse Width Modulationp.38213.10 FNC 59 – PLSR / Acceleration/Deceleration Setupp.38514. Handy Instruction – FNC 60 to FNC 69p.39014.1 FNC 60 – IST / Initial Statep.39114.1.1 IST instruction equivalent circuitp.39314.1.2 Example of IST instruction introduction (example of workpiece transfer mechanism)p.39414.2 FNC 61 – SER / Search a Data Stackp.40114.3 FNC 62 – ABSD / Absolute Drum Sequencerp.40414.4 FNC 63 – INCD / Incremental Drum Sequencerp.40714.5 FNC 64 – TTMR / Teaching Timerp.40914.6 FNC 65 – STMR / Special Timerp.41114.7 FNC 66 – ALT / Alternate Statep.41314.8 FNC 67 – RAMP / Ramp Variable Valuep.41514.9 FNC 68 – ROTC / Rotary Table Controlp.41714.10 FNC 69 – SORT / SORT Tabulated Datap.42015. External FX I/O Device – FNC 70 to FNC 79p.42315.1 FNC 70 – TKY / Ten Key Inputp.42415.2 FNC 71 – HKY / Hexadecimal Inputp.42715.3 FNC 72 – DSW / Digital Switch (Thumbwheel Input)p.43115.4 FNC 73 – SEGD / Seven Segment Decoderp.43415.5 FNC 74 – SEGL / Seven Segment With Latchp.43615.5.1 How to select a seven-segment display unitp.43915.5.2 How to select parameter "n" based on seven-segment display specificationsp.43915.6 FNC 75 – ARWS / Arrow Switchp.44115.7 FNC 76 – ASC / ASCII Code Data Inputp.44515.8 FNC 77 – PR / Print (ASCII Code)p.44715.9 FNC 78 – FROM / Read From A Special Function Blockp.45015.9.1 Common items between FROM instruction and TO instruction (details)p.45315.10 FNC 79 – TO / Write To A Special Function Blockp.45516. External FX Device – FNC 80 to FNC 89p.45716.1 FNC 80 – RS / Serial Communicationp.45816.2 FNC 81 – PRUN / Parallel Run (Octal Mode)p.46016.3 FNC 82 – ASCI / Hexadecimal to ASCII Conversionp.46216.4 FNC 83 – HEX / ASCII to Hexadecimal Conversionp.46516.5 FNC 84 – CCD / Check Codep.46816.6 FNC 85 - VRRD / Volume Readp.47116.7 FNC 86 - VRSC / Volume Scalep.47316.8 FNC 87 – RS2 / Serial Communication 2p.47516.9 FNC 88 – PID / PID Control Loopp.47817. Data Transfer 2 – FNC100 to FNC109p.48217.1 FNC102 – ZPUSH/Batch Store of Index Registerp.48317.2 FNC103 – ZPOP/Batch POP of Index Registerp.48618. Floating Point – FNC110 to FNC139p.48718.1 FNC110 – ECMP / Floating Point Comparep.48918.2 FNC111 – EZCP / Floating Point Zone Comparep.49018.3 FNC112 – EMOV / Floating Point Movep.49218.4 FNC116 – ESTR / Floating Point to Character String Conversionp.49318.5 FNC117 – EVAL / Character String to Floating Point Conversionp.49918.6 FNC118 – EBCD / Floating Point to Scientific Notation Conversionp.50418.7 FNC119 – EBIN / Scientific Notation to Floating Point Conversionp.50518.8 FNC120 – EADD / Floating Point Additionp.50718.9 FNC121 – ESUB / Floating Point Subtractionp.50818.10 FNC122 – EMUL / Floating Point Multiplicationp.50918.11 FNC123 – EDIV / Floating Point Divisionp.51018.12 FNC124 – EXP / Floating Point Exponentp.51118.13 FNC125 – LOGE / Floating Point Natural Logarithmp.51318.14 FNC126 – LOG10 / Floating Point Common Logarithmp.51518.15 FNC127 – ESQR / Floating Point Square Rootp.51718.16 FNC128 – ENEG / Floating Point Negationp.51818.17 FNC129 – INT / Floating Point to Integer Conversionp.51918.18 FNC130 – SIN / Floating Point Sinep.52118.19 FNC131 – COS / Floating Point Cosinep.52218.20 FNC132 – TAN / Floating Point Tangentp.52318.21 FNC133 – ASIN / Floating Point Arc Sinep.52418.22 FNC134 – ACOS / Floating Point Arc Cosinep.52618.23 FNC135 – ATAN / Floating Point Arc Tangentp.52818.24 FNC136 – RAD / Floating Point Degrees to Radians Conversionp.53018.25 FNC137 – DEG / Floating Point Radians to Degrees Conversionp.53219. Data Operation 2 – FNC140 to FNC149p.53319.1 FNC140 – WSUM / Sum of Word Datap.53419.2 FNC141 – WTOB / WORD to BYTEp.53619.3 FNC142 – BTOW / BYTE to WORDp.53819.4 FNC143 – UNI / 4-bit Linking of Word Datap.54019.5 FNC144 – DIS / 4-bit Grouping of Word Datap.54219.6 FNC147 – SWAP / Byte Swapp.54419.7 FNC149 – SORT2 / Sort Tabulated Data 2p.54520. Positioning Control – FNC150 to FNC159p.54920.1 FNC150 – DSZR / Dog Search Zero Returnp.55020.2 FNC151 – DVIT / Interrupt Positioningp.55220.3 FNC152 – TBL / Batch Data Positioning Modep.55420.4 FNC155 – ABS / Absolute Current Value Readp.55520.5 FNC156 – ZRN / Zero Returnp.55620.6 FNC157 – PLSV / Variable Speed Pulse Outputp.55820.7 FNC158 – DRVI / Drive to Incrementp.56020.8 FNC159 – DRVA / Drive to Absolutep.56221. Real Time Clock Control – FNC160 to FNC169p.56421.1 FNC160 – TCMP / RTC Data Comparep.56521.2 FNC161 – TZCP / RTC Data Zone Comparep.56721.3 FNC162 – TADD / RTC Data Additionp.56921.4 FNC163 – TSUB / RTC Data Subtractionp.57121.5 FNC164 – HTOS / Hour to Second Conversionp.57321.6 FNC165 – STOH / Second to Hour Conversionp.57521.7 FNC166 – TRD / Read RTC datap.57721.8 FNC167 – TWR / Set RTC datap.57821.9 FNC169 – HOUR / Hour Meterp.58022. External Device – FNC170 to FNC179p.58222.1 FNC170 – GRY / Decimal to Gray Code Conversionp.58322.2 FNC171 – GBIN / Gray Code to Decimal Conversionp.58422.3 FNC176 – RD3A / Read form Dedicated Analog Blockp.58522.4 FNC177 – WR3A / Write to Dedicated Analog Blockp.58623. Introduction of Alternate Instructions – FNC180p.58723.1 Instruction correspondence tablep.58724. Others – FNC181 to FNC189p.58824.1 FNC182 – COMRD / Read Device Comment Datap.58924.2 FNC184 – RND / Random Number Generationp.59124.3 FNC186 – DUTY / Timing Pulse Generationp.59224.4 FNC188 – CRC / Cyclic Redundancy Checkp.59424.5 FNC189 – HCMOV / High-Speed Counter Movep.59825. Block Data Operation – FNC190 to FNC199p.60225.1 FNC192 – BK+ / Block Data Additionp.60325.2 NFC193 – BK– / Block Data Subtractionp.60625.3 FNC194~199 – BKCMP=, >, <, < >, <=, >= / Block Data Comparep.60926. Character String Control – FNC200 to FNC209p.61326.1 FNC200 – STR / BIN to Character String Conversionp.61426.2 FNC201 – VAL / Character String to BIN Conversionp.61926.3 FNC202 – $+ / Link Character Stringsp.62426.4 FNC203 – LEN / Character String Length Detectionp.62626.5 FNC204 – RIGHT / Extracting Character String Data from the Rightp.62826.6 FNC205 – LEFT / Extracting Character String Data from the Leftp.63026.7 FNC206 – MIDR / Random Selection of Character Stringsp.63226.8 FNC207 – MIDW / Random Replacement of Character Stringsp.63526.9 FNC208 – INSTR / Character string searchp.63826.10 FNC209 – $MOV / Character String Transferp.64027. Data Operation 3 – FNC210 to FNC219p.64227.1 FNC210 – FDEL / Deleting Data from Tablesp.64327.2 FNC211 – FINS / Inserting Data to Tablesp.64527.3 FNC212 – POP / Shift Last Data Read [FILO Control]p.64727.4 FNC213 – SFR / Bit Shift Right with Carryp.65027.5 FNC214 – SFL / Bit Shift Left with Carryp.65228. Data Comparison – FNC220 to FNC249p.65428.1 FNC224~230 – LD =, >, <, <>, <=, >= / Data Comparisonp.65628.2 FNC232~238 – AND=, >, <, < >, <=, >= / Data Comparisonp.65828.3 FNC240~246 – OR=, >, <, < >, <=, >= / Data Comparisonp.66029. Data Table Operation – FNC250 to FNC269p.66229.1 FNC256 – LIMIT / Limit Controlp.66329.2 FNC257 – BAND / Dead Band Controlp.66629.3 FNC258 – ZONE / Zone Controlp.66929.4 FNC259 – SCL / Scaling (Coordinate by Point Data)p.67229.5 FNC260 – DABIN / Decimal ASCII to BIN Conversionp.67629.6 FNC261 – BINDA / BIN to Decimal ASCII Conversionp.67929.7 FNC269 – SCL2 / Scaling 2 (Coordinate by X/Y Data)p.68230. External Device Communication – FNC270 to FNC276p.68630.1 FNC270 – IVCK / Inverter Status Checkp.68730.2 FNC271 – IVDR / Inverter Drivep.68930.3 FNC272 – IVRD / Inverter Parameter Readp.69130.4 FNC273 – IVWR / Inverter Parameter Writep.69330.5 FNC274 – IVBWR / Inverter Parameter Block Writep.69530.6 FNC275 – IVMC / Inverter Multi Commandp.69730.7 FNC276 - MODBUS Read/Write Instructionp.69930.7.1 Command Code and Command Parametersp.70031. Data Transfer 3 – FNC277 to FNC279p.70331.1 FNC278 – RBFM / Divided BFM Readp.70431.1.1 Common items between RBFM (FNC278) instruction and WBFM (FNC279) instructionp.70531.2 FNC279 – WBFM / Divided BFM Writep.70832. High-Speed Processing 2 – FNC280 to FNC289p.71032.1 FNC280 – HSCT / High-Speed Counter Compare With Data Tablep.71133. Extension File Register Control – FNC290 to FNC299p.71633.1 FNC290 – LOADR / Load From ERp.71733.2 FNC291 – SAVER / Save to ERp.72033.3 FNC292 – INITR / Initialize R and ERp.72833.4 FNC293 – LOGR / Logging R and ERp.73133.5 FNC294 – RWER / Rewrite to ERp.73533.6 FNC295 – INITER / Initialize ERp.74034. FX3U-CF-ADP Applied Instructions – FNC300 to FNC305p.74334.1 FNC300 – FLCRT / File create·checkp.74434.1.1 Detailed explanation of setting datap.74534.2 FNC301 – FLDEL / File delete·CF card formatp.74634.2.1 Detailed explanation of setting datap.74734.3 FNC302 – FLWR / Data writep.74834.3.1 Detailed explanation of setting datap.75034.4 FNC303 – FLRD / Data readp.75134.4.1 Detailed explanation of setting datap.75234.5 FNC304 – FLCMD / FX3U-CF-ADP commandp.75334.5.1 Detailed explanation of setting datap.75434.6 FNC305 – FLSTRD / FX3U-CF-ADP status readp.75534.6.1 Detailed explanation of setting datap.75635. SFC Program and Step Ladderp.75835.1 SFC Programp.75835.1.1 Outlinep.75835.1.2 Explanation of function and operationp.75835.1.3 SFC program creating procedurep.76035.1.4 Handling and role of initial state relayp.76335.1.5 Latched (battery backed) type state relaysp.76335.1.6 Role of the RET instructionp.76435.1.7 Preliminary knowledge for creating SFC programp.76435.1.8 SFC flow formatsp.77035.1.9 Program of branch/recombination state relaysp.77335.1.10 Rule for creating branch circuitp.77435.1.11 Program examplesp.77835.2 Step Ladderp.78735.2.1 Outlinep.78735.2.2 Explanation of function and operationp.78735.2.3 Expression of step ladderp.78935.2.4 Creation of step ladder program (SFC program -> STL program)p.79035.2.5 Preliminary knowledge for creating step ladder programsp.79135.2.6 Program with state relays in branches and recombinationp.79435.2.7 Program examplesp.79836. Interrupt Function and Pulse Catch Functionp.80436.1 Outlinep.80436.2 Common Itemsp.80536.2.1 How to disable interrupt functionp.80536.2.2 Related itemsp.80636.2.3 Cautions on use (common)p.80636.3 Input Interrupt (Interrupt Triggered by External Signal) [Without Delay Function]p.80936.3.1 Input interrupt (interrupt triggered by external signal) [without delay function]p.80936.3.2 Examples of practical programs (programs to measure short pulse width)p.81336.4 Input interrupt (Interrupt by External Signal) [With Delay Function]p.81536.5 Timer Interrupt (Interrupt in Constant Cycle)p.81536.5.1 Timer interrupt (interrupt in constant cycle)p.81536.5.2 Examples of practical program (timer interrupt programs using applied instruction)p.81736.6 Counter Interrupt - Interrupt Triggered by Counting Up of High-Speed Counterp.82036.7 Pulse Catch Function [M8170 to M8177]p.82136.8 Pulse width/Pulse period measurement function [M8075 to M8079, D8074 to D8097]p.82237. Operation of Special Devices (M8000 -, D8000 -)p.82637.1 Special Device List (M8000 -, D8000 -)p.82637.1.1 Special Auxiliary Relay (M8000 to M8511)p.82637.1.2 Special Data Register (D8000 to D8511)p.84437.2 Supplement of Special Devices (M8000 - and D8000 -)p.86637.2.1 RUN monitor and initial pulse [M8000 to M8003]p.86637.2.2 Watchdog timer [D8000]p.86737.2.3 Battery voltage low detection [M8005 and M8006]p.86737.2.4 Power failure detection time [D8008, M8008 and M8007]p.86837.2.5 Scan time (monitor) [D8010 to D8012]p.86837.2.6 Internal clock [M8011 to M8014]p.86837.2.7 Real time clock [M8015 to M8019 and D8013 to D8019]p.86937.2.8 How to set real time clockp.87037.2.9 Input filter adjustment [D8020]p.87237.2.10 Battery [BATT (BAT)] LED and [ALM] LED OFF command [M8030]p.87337.2.11 Built-in analog volume [D8030 and D8031]p.87437.2.12 Clear command [M8031 and M8032]p.87437.2.13 Memory hold stop [M8033] (output hold in STOP mode)p.87437.2.14 All outputs disable [M8034]p.87537.2.15 Individual operation for RUN/STOP input [M8035 to M8037]p.87537.2.16 Constant scan mode [M8039 and D8039]p.87637.2.17 State control in program with STL instruction/SFC chart [M8040]p.87637.2.18 Analog expansion boards [M8260 to M8279 and D8260 to D8279]p.87737.2.19 Analog special adapters [M8260 to M8299 and D8260 to D8299]p.87938. Error Check Method and Error Code Listp.88638.1 States and Colors of LEDs PLC Operation Statusp.88638.1.1 POWER (POW) LED [lit, flickering or unlit]p.88738.1.2 RUN LED [lit or unlit]p.88738.1.3 BATT (BAT) LED [lit or unlit] [FX3U/FX3UC]p.88738.1.4 ALM LED [lit or unlit] [FX3G/FX3GC]p.88738.1.5 ERROR (ERR) LED [lit, flickering or unlit]p.88838.1.6 L RUN LED [FX3UC-32MT-LT(-2)]p.88838.1.7 L ERR LED [FX3UC-32MT-LT(-2)]p.88938.2 Error Code Check Method and Indicationp.89038.2.1 Error code check method by display modulep.89038.2.2 Error code check method by GX Works2p.89138.2.3 Error indicationp.89238.3 Supplementary Explanation of Devices for Error Detectionp.89338.3.1 Error detection (M8060 to/D8060 to)p.89338.3.2 Operations of special devices for error detectionp.89438.3.3 Error detection timingp.89438.4 Error Code List and Actionp.895Appendix A: Programming Tool Applicability and Version Upgrade Historyp.903Appendix A-1 Programming Tool Applicabilityp.903Appendix A-1-1 Programming tool applicabilityp.903Appendix A-1-2 Cautions on writing during RUNp.906Appendix A-1-3 Precautions on Use of (Built-in USB) Programming Portp.910Appendix A-1-4 Cautions on using transparent function by way of USB in GOT1000 Seriesp.911Appendix A-1-5 Cautions on using transparent (2-port) function of GOT-F900 Seriesp.912Appendix A-2 Peripheral product applicability (except programming tools)p.913Appendix A-2-1 Peripheral product applicabilityp.913Appendix A-3 Version Upgrade Historyp.915Appendix A-3-1 Manufacturer's serial number check methodp.915Appendix A-3-2 Version checkp.916Appendix A-3-3 Version upgrade history [FX3S]p.916Appendix A-3-4 Version upgrade history [FX3G]p.916Appendix A-3-5 Version upgrade history [FX3GC]p.917Appendix A-3-6 Version upgrade history [FX3U]p.917Appendix A-3-7 Version upgrade history [FX3UC]p.917Appendix B: Instruction Execution Timep.919Appendix B-1 Basic Instruction Execution Timep.919Appendix B-2 Step Ladder Instruction Execution Timep.927Appendix B-3 Label (P/I) Execution Timep.927Appendix B-4 Applied Instruction Execution Timep.928Appendix B-5 Execution Time of Pulse Generation Instruction P in Each Applied Instructionp.943Appendix B-6 Execution Time on Combination of Applicable Devices and Indexingp.946Appendix B-6-1 Basic instruction (LD/LDI/AND/ANI/OR/ORI) execution timep.946Appendix B-6-2 Applied instruction execution timep.946Appendix C: Applied Instruction List [by Instruction Type/in Alphabetic Order]p.950Appendix C-1 Applied instructions [by instruction type]p.950Appendix C-2 Applied instructions [in alphabetical order]p.954Appendix D: Discontinued modelsp.957Warrantyp.959Revised Historyp.960Back Coverp.964
Page 1 of the Mitsubishi Electronics MELSEC FX3S user manual — PROGRAMMING MANUAL
Page 1 · click to enlarge
Page 1
Mitsubishi Electronics MELSEC FX3S — Front Cover diagram (page 1)
Fig. 1 · Front Cover

FX3S/FX3G/FX3GC/FX3U/FX3UC SERIES PROGRAMMABLE CONTROLLERS

PROGRAMMING MANUAL

Basic & Applied Instruction Edition

Page 2 of the Mitsubishi Electronics MELSEC FX3S user manual — Front Cover
Page 2 · click to enlarge
Page 2
Page 2 of the Mitsubishi Electronics MELSEC FX3S user manual — Front Cover
Page 3 of the Mitsubishi Electronics MELSEC FX3S user manual — © 2005 MITSUBISHI ELECTRIC CORPORATION
Page 3 · click to enlarge
Page 3

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programmable Controllers

Programming Manual - Basic & Applied Instruction Edition

Manual No. Revision DateJY997D16601 N 9/2013 Manual No.JY997D16601 RevisionN Date9/2013

Foreword

This manual contains text, diagrams and explanations which will guide the reader through the safe and correct installation, use, and operation of the FX3S/FX3G/FX3GC/FX3U/FX3UC Series programmable controller. It should be read and understood before attempting to install or use the unit. Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward it to the end user.

This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.

© 2005 MITSUBISHI ELECTRIC CORPORATION

Page 4 of the Mitsubishi Electronics MELSEC FX3S user manual — Registration
Page 4 · click to enlarge
Page 4

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

Outline Precautions

  • This manual provides information for the use of the FX 3S /FX 3G /FX 3GC /FX 3U /FX 3UC Series Programmable Controllers. The manual has been written to be used by trained and competent personnel. The definition of such a person or persons is as follows;
1. Any engineer who is responsible for the planning, design and construction of automatic equipment using the product associated with this manual should be of a competent nature, trained and qualified to the local and national standards required to fulfill that role. These engineers should be fully aware of all aspects of safety with regards to automated equipment.
2. Any commissioning or service engineer must be of a competent nature, trained and qualified to the local and national standards required to fulfill that job. These engineers should also be trained in the use and maintenance of the completed product. This includes being completely familiar with all associated documentation for the said product. All maintenance should be carried out in accordance with established safety practices.
3. All operators of the completed equipment should be trained to use that product in a safe and coordinated manner in compliance to established safety practices. The operators should also be familiar with documentation which is connected with the actual operation of the completed equipment. Note: The term 'completed equipment' refers to a third party constructed device which contains or uses

the product associated with this manual

  • This product has been manufactured as a general-purpose part for general industries, and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life.
  • Before using the product for special purposes such as nuclear power, electric power, aerospace, medicine or passenger movement vehicles, consult with Mitsubishi Electric.
  • This product has been manufactured under strict quality control. However when installing the product where major accidents or losses could occur if the product fails, install appropriate backup or failsafe functions in the system.
  • When combining this product with other products, please confirm the standard and the code, or regulations with which the user should follow. Moreover, please confirm the compatibility of this product to the system, machine, and apparatus with which a user is using.
  • If in doubt at any stage during the installation of the product, always consult a professional electrical engineer who is qualified and trained to the local and national standards. If in doubt about the operation or use, please consult the nearest Mitsubishi Electric representative.
  • Since the examples indicated by this manual, technical bulletin, catalog, etc. are used as a reference, please use it after confirming the function and safety of the equipment and system. Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples.
  • This manual content, specification etc. may be changed without a notice for improvement.
  • The information in this manual has been carefully checked and is believed to be accurate; however, you have noticed a doubtful point, a doubtful error, etc., please contact the nearest Mitsubishi Electric representative.

Registration

  • Microsoft ® , Windows ® and Excel ® are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or other countries.
  • CompactFlash is a trademark of SanDisk Corporation in the United States and other countries.
  • Ethernet is a trademark of Xerox Corporation.
  • MODBUS ® is a registered trademark of Schneider Electric SA.
  • The company name and the product name to be described in this manual are the registered trademarks or trademarks of each company.
Page 5 of the Mitsubishi Electronics MELSEC FX3S user manual — Table of Contents
Page 5 · Contents
Contents

Contents

Front Coverp.1Manual Numberp.3Table of Contentsp.5Related manualsp.16Generic Names and Abbreviations Used in Manualsp.231. Introductionp.251.1 Programming Language in PLCsp.251.1.1 Types of programming languagesp.251.1.2 Applicability of programming languages in programming softwarep.261.1.3 Compatibility among programsp.262. Overview (Sequence Program)p.272.1 Introduction of Convenient Functionsp.272.1.1 Convenient functions for input processingp.272.1.2 Convenient functions for output processingp.282.1.3 Functions for supporting sequence controlp.282.2 Introduction of Applied Instructionsp.292.2.1 Major applied instructionsp.292.3 Analog/Positioning Special Controlp.312.4 Link and Communicationp.312.5 Introduction of Devices Constructing PLCp.322.5.1 Relationship among devicesp.322.5.2 Device listp.332.6 Program Memory and Devicesp.352.6.1 Memory structurep.352.6.2 Memory operations and latched (battery or EEPROM backed) devices (power ON/OFF and RUN/STOP)p.382.6.3 Types of backup methods against power failurep.442.6.4 Change between general devices and latched (battery backed) devicesp.452.6.5 How to initialize devices (battery backed)p.452.7 Types and Setting of Parametersp.462.7.1 Parameter listp.462.7.2 Parameter initial values and available tools for changing parameter valuesp.472.7.3 Memory capacity setting rangep.502.7.4 Compatible optional memory modelp.512.7.5 Keyword (entry code)p.522.7.6 Special unit initial value settingp.602.7.7 Positioning instruction settingp.602.7.8 Built-in CC-Link/LT Setup (dedicated to FX3UC-32MT-LT-2)p.602.7.9 Parameter settingsp.603. Instruction Listp.723.1 Basic Instructionsp.723.2 Step Ladder Instructionsp.743.3 Applied Instructions ... in Ascending Order of FNC Numberp.744. Devices in Detailp.854.1 Device Number Listp.854.2 I/O Relays [X, Y]p.914.2.1 Numbers of I/O relaysp.914.2.2 Functions and rolesp.924.2.3 Operation timing of I/O relaysp.934.3 Auxiliary Relay [M]p.944.3.1 Numbers of auxiliary relaysp.944.3.2 Functions and operation examplesp.944.4 State Relay [S]p.964.4.1 Numbers of state relaysp.964.4.2 Functions and operation examplesp.974.5 Timer [T]p.994.5.1 Numbers of timersp.994.5.2 Functions and operation examplesp.994.5.3 Set value specification methodp.1014.5.4 Cautions on routinesp.1014.5.5 Details on timer operation and timer accuracyp.1014.5.6 Program examples [off-delay timer and flicker timer]p.1024.5.7 Handling timers as numeric devicesp.1034.6 Counter [C]p.1044.6.1 Numbers of countersp.1044.6.2 Features of countersp.1044.6.3 Related devices (to specify counting direction) [32-bit counter]p.1054.6.4 Functions and operation examplesp.1054.6.5 Set value specification methodp.1064.6.6 Response speed of countersp.1074.6.7 Handling counters as numeric devicesp.1074.7 High-Speed Counter [C] (FX3S/FX3G/FX3GC PLCs)p.1094.7.1 Types and device numbers of high-speed countersp.1094.7.2 Input assignment for high-speed countersp.1114.7.3 Handling of high-speed countersp.1124.7.4 Current value update timing and comparison of current valuep.1124.7.5 Related devicesp.1124.7.6 Assignment of counter input terminal and switching of functionp.1134.7.7 Response frequency of high-speed countersp.1144.7.8 Cautions on usep.1164.8 High-Speed Counter [C] (FX3U/FX3UC PLC)p.1184.8.1 Types and device numbers of high-speed countersp.1184.8.2 Input assignment for high-speed countersp.1204.8.3 Handling of high-speed countersp.1214.8.4 Current value update timing and comparison of current valuep.1234.8.5 Related devicesp.1244.8.6 Changing the logic of external reset input signalp.1254.8.7 Assignment of counter input terminal and switching of functionp.1254.8.8 How to use 2-phase 2-count input counters C251 to C255 with 4 edge countingp.1264.8.9 Conditions for hardware counters to be handled as software countersp.1274.8.10 Response frequency of high-speed countersp.1284.8.11 Cautions on usep.1304.9 Data Register and File Register [D]p.1324.9.1 Numbers of data registers and file registersp.1324.9.2 Structures of data registers and file registersp.1334.9.3 Functions and operation examples of data registersp.1344.9.4 Functions and operation examples of file registersp.1364.9.5 Cautions on using file registersp.1394.10 Extension Register [R] and Extension File Register [ER]p.1404.10.1 Numbers of extension registers and extension file registersp.1404.10.2 Data storage destination and access methodp.1404.10.3 Structures of extension registers and extension file registersp.1414.10.4 Initialization of extension registers and extension file registersp.1414.10.5 Functions and operation examples of extension registersp.1424.10.6 Functions and operation examples of extension file registersp.1434.10.7 Cautions on using extension file registersp.1454.10.8 Registration of data in extension registers and extension file registersp.1464.11 Index Register [V and Z]p.1504.11.1 Numbers of index registersp.1504.11.2 Functions and structuresp.1504.11.3 Indexing of devicesp.1504.12 Pointer [P and I]p.1514.12.1 Numbers of pointersp.1514.12.2 Functions and operation examples of pointers for branchp.1514.12.3 Functions and operation examples of pointers for interruptp.1525. How to Specify Devices and Constants to Instructionsp.1555.1 Numeric Values Handled in PLC (Octal, Decimal, Hexadecimal and Real Numbers)p.1555.1.1 Types of numeric valuesp.1555.1.2 Conversion of numeric valuesp.1565.1.3 Handling of numeric values in floating point operationsp.1575.2 Specification of Constants K, H and E (Decimal, Hexadecimal and Real Number)p.1595.2.1 Constant K (decimal number)p.1595.2.2 Constant H (hexadecimal number)p.1595.2.3 Constant E (real number)p.1595.3 Character Stringsp.1605.3.1 Character string constant ("ABC")p.1605.3.2 Character string datap.1605.4 Specification of Digits for Bit Devices (Kn[ ]***)p.1615.5 Bit Specification of a Word Device (D[ ].b)p.1625.6 Direct Specification of Buffer Memory (U[ ]\G[ ])p.1625.7 Indexingp.1635.7.1 Indexing in basic instructionsp.1635.7.2 Indexing in applied instructionsp.1645.7.3 Indexing example for instruction with limited number of use.p.1666. What to Understand before Programmingp.1686.1 How to Read Explanation of Instructionsp.1686.2 Cautions on Creation of Fundamental Programsp.1716.2.1 Programming procedure and execution orderp.1716.2.2 Double output (double coil) operation and countermeasuresp.1726.2.3 Circuits which cannot be programmed and countermeasuresp.1736.3 I/O Processing and Response Delayp.1736.4 Mutual Relationship Among Program Flow Control Instructionsp.1746.5 General Rules for Applied Instructionsp.1766.5.1 Expression and operation type of applied instructionsp.1766.5.2 Handling of general flagsp.1786.5.3 Handling of operation error flagp.1806.5.4 Handling functions of extension flagp.1806.5.5 Limitation in the number of instructions and limitation in simultaneous instruction instancesp.1816.6 Symbolic information storage and block passwordp.1826.6.1 Storage of symbolic informationp.1826.6.2 Block passwordp.1827. Basic Instructionp.1837.1 LD, LDIp.1857.2 OUTp.1877.3 AND, ANIp.1907.4 OR, ORIp.1937.5 LDP, LDF, ANDP, ANDF, ORP, ORFp.1967.6 ORBp.2027.7 ANBp.2037.8 MPS, MRD, MPPp.2047.9 MC, MCRp.2077.10 INVp.2107.11 MEP, MEFp.2117.12 PLS, PLFp.2137.13 SET, RSTp.2167.14 NOPp.2197.15 ENDp.2207.16 Number of Instruction Steps and Specified Devicesp.2218. Program Flow – FNC 00 to FNC 09p.2228.1 FNC 00 – CJ / Conditional Jumpp.2238.1.1 CJ instruction and operations of contact and coilp.2278.1.2 Relationship between master control instruction and jump instructionp.2298.2 FNC 01 – CALL / Call Subroutinep.2308.2.1 Cautions on subroutines and interrupt routinesp.2328.3 FNC 02 – SRET / Subroutine Returnp.2348.4 FNC 03 – IRET / Interrupt Returnp.2358.5 FNC 04 – EI / Enable Interruptp.2378.6 FNC 05 – DI / Disable Interruptp.2388.7 FNC 06 – FEND / Main Routine Program Endp.2398.8 FNC 07 – WDT / Watchdog Timer Refreshp.2418.9 FNC 08 – FOR / Start a FOR/NEXT Loopp.2438.10 FNC 09 – NEXT / End a FOR/NEXT Loopp.2449. Move and Compare – FNC 10 to FNC 19p.2469.1 FNC 10 – CMP / Comparep.2479.2 FNC 11 – ZCP / Zone Comparep.2499.3 FNC 12 – MOV / Movep.2519.4 FNC 13 – SMOV / Shift Movep.2549.5 FNC 14 – CML / Complementp.2569.6 FNC 15 – BMOV / Block Movep.2589.6.1 Function of transfer between file registers and data registersp.2609.7 FNC 16 – FMOV / Fill Movep.2629.8 FNC 17 – XCH / Exchangep.2649.9 FNC 18 – BCD / Conversion to Binary Coded Decimalp.2669.10 FNC 19 – BIN / Conversion to Binaryp.26910. Arithmetic and Logical Operation (+, -, ×,÷ ) – FNC 20 to FNC 29p.27210.1 FNC 20 – ADD / Additionp.27310.2 FNC 21 – SUB / Subtractionp.27510.3 FNC 22 – MUL / Multiplicationp.27710.4 FNC 23 – DIV / Divisionp.28010.5 FNC 24 – INC / Incrementp.28310.6 FNC 25 – DEC / Decrementp.28510.7 FNC 26 – WAND / Logical Word ANDp.28610.8 FNC 27 – WOR / Logical Word ORp.28810.9 FNC 28 – WXOR / Logical Exclusive ORp.29010.10 FNC 29 – NEG / Negationp.29211. Rotation and Shift Operation – FNC 30 to FNC 39p.29411.1 FNC 30 – ROR / Rotation Rightp.29511.2 FNC 31 – ROL / Rotation Leftp.29711.3 FNC 32 – RCR / Rotation Right with Carryp.29911.4 FNC 33 – RCL / Rotation Left with Carryp.30111.5 FNC 34 – SFTR / Bit Shift Rightp.30311.6 FNC 35 – SFTL / Bit Shift Leftp.30511.6.1 Replacement of SFT instruction in F1 and F2 Seriesp.30711.7 FNC 36 – WSFR / Word Shift Rightp.30811.8 FNC 37 – WSFL / Word Shift Leftp.31011.9 FNC 38 – SFWR / Shift Write [FIFO/FILO Control]p.31211.10 FNC 39 – SFRD / Shift Read [FIFO Control]p.31512. Data Operation – FNC 40 to FNC 49p.31712.1 FNC 40 – ZRST / Zone Resetp.31812.2 FNC 41 – DECO / Decodep.32212.3 FNC 42 – ENCO / Encodep.32512.4 FNC 43 – SUM / Sum of Active Bitsp.32712.5 FNC 44 – BON / Check Specified Bit Statusp.33012.6 FNC 45 – MEAN / Meanp.33212.7 FNC 46 – ANS / Timed Annunciator Setp.33412.8 FNC 47 – ANR / Annunciator Resetp.33612.9 FNC 48 – SQR / Square Rootp.33712.10 FNC 49 – FLT / Conversion to Floating Pointp.33813. High-Speed Processing – FNC 50 to FNC 59p.34013.1 FNC 50 – REF / Refreshp.34113.1.1 What should be understood before using the REF instructionp.34413.2 FNC 51 – REFF / Refresh and Filter Adjustp.34513.2.1 What should be understood before using REFF instructionp.34713.3 FNC 52 – MTR / Input Matrixp.34813.3.1 Operation and cautions for the MTR instructionp.35113.4 FNC 53 – HSCS / High-Speed Counter Setp.35213.4.1 Common cautions on using instructions for high-speed counterp.35513.5 FNC 54 – HSCR / High-Speed Counter Resetp.35813.6 FNC 55 – HSZ / High-Speed Counter Zone Comparep.36113.6.1 Program in which comparison result is set to ON when power is turned ON [ZCP (FNC 11) instruction]p.36513.6.2 Table high-speed comparison mode (M8130)p.36713.6.3 Frequency control mode (HSZ and PLSY instructions) (M8132)p.37013.7 FNC 56 – SPD / Speed Detectionp.37313.8 FNC 57 – PLSY / Pulse Y Outputp.37713.9 FNC 58 – PWM / Pulse Width Modulationp.38213.10 FNC 59 – PLSR / Acceleration/Deceleration Setupp.38514. Handy Instruction – FNC 60 to FNC 69p.39014.1 FNC 60 – IST / Initial Statep.39114.1.1 IST instruction equivalent circuitp.39314.1.2 Example of IST instruction introduction (example of workpiece transfer mechanism)p.39414.2 FNC 61 – SER / Search a Data Stackp.40114.3 FNC 62 – ABSD / Absolute Drum Sequencerp.40414.4 FNC 63 – INCD / Incremental Drum Sequencerp.40714.5 FNC 64 – TTMR / Teaching Timerp.40914.6 FNC 65 – STMR / Special Timerp.41114.7 FNC 66 – ALT / Alternate Statep.41314.8 FNC 67 – RAMP / Ramp Variable Valuep.41514.9 FNC 68 – ROTC / Rotary Table Controlp.41714.10 FNC 69 – SORT / SORT Tabulated Datap.42015. External FX I/O Device – FNC 70 to FNC 79p.42315.1 FNC 70 – TKY / Ten Key Inputp.42415.2 FNC 71 – HKY / Hexadecimal Inputp.42715.3 FNC 72 – DSW / Digital Switch (Thumbwheel Input)p.43115.4 FNC 73 – SEGD / Seven Segment Decoderp.43415.5 FNC 74 – SEGL / Seven Segment With Latchp.43615.5.1 How to select a seven-segment display unitp.43915.5.2 How to select parameter "n" based on seven-segment display specificationsp.43915.6 FNC 75 – ARWS / Arrow Switchp.44115.7 FNC 76 – ASC / ASCII Code Data Inputp.44515.8 FNC 77 – PR / Print (ASCII Code)p.44715.9 FNC 78 – FROM / Read From A Special Function Blockp.45015.9.1 Common items between FROM instruction and TO instruction (details)p.45315.10 FNC 79 – TO / Write To A Special Function Blockp.45516. External FX Device – FNC 80 to FNC 89p.45716.1 FNC 80 – RS / Serial Communicationp.45816.2 FNC 81 – PRUN / Parallel Run (Octal Mode)p.46016.3 FNC 82 – ASCI / Hexadecimal to ASCII Conversionp.46216.4 FNC 83 – HEX / ASCII to Hexadecimal Conversionp.46516.5 FNC 84 – CCD / Check Codep.46816.6 FNC 85 - VRRD / Volume Readp.47116.7 FNC 86 - VRSC / Volume Scalep.47316.8 FNC 87 – RS2 / Serial Communication 2p.47516.9 FNC 88 – PID / PID Control Loopp.47817. Data Transfer 2 – FNC100 to FNC109p.48217.1 FNC102 – ZPUSH/Batch Store of Index Registerp.48317.2 FNC103 – ZPOP/Batch POP of Index Registerp.48618. Floating Point – FNC110 to FNC139p.48718.1 FNC110 – ECMP / Floating Point Comparep.48918.2 FNC111 – EZCP / Floating Point Zone Comparep.49018.3 FNC112 – EMOV / Floating Point Movep.49218.4 FNC116 – ESTR / Floating Point to Character String Conversionp.49318.5 FNC117 – EVAL / Character String to Floating Point Conversionp.49918.6 FNC118 – EBCD / Floating Point to Scientific Notation Conversionp.50418.7 FNC119 – EBIN / Scientific Notation to Floating Point Conversionp.50518.8 FNC120 – EADD / Floating Point Additionp.50718.9 FNC121 – ESUB / Floating Point Subtractionp.50818.10 FNC122 – EMUL / Floating Point Multiplicationp.50918.11 FNC123 – EDIV / Floating Point Divisionp.51018.12 FNC124 – EXP / Floating Point Exponentp.51118.13 FNC125 – LOGE / Floating Point Natural Logarithmp.51318.14 FNC126 – LOG10 / Floating Point Common Logarithmp.51518.15 FNC127 – ESQR / Floating Point Square Rootp.51718.16 FNC128 – ENEG / Floating Point Negationp.51818.17 FNC129 – INT / Floating Point to Integer Conversionp.51918.18 FNC130 – SIN / Floating Point Sinep.52118.19 FNC131 – COS / Floating Point Cosinep.52218.20 FNC132 – TAN / Floating Point Tangentp.52318.21 FNC133 – ASIN / Floating Point Arc Sinep.52418.22 FNC134 – ACOS / Floating Point Arc Cosinep.52618.23 FNC135 – ATAN / Floating Point Arc Tangentp.52818.24 FNC136 – RAD / Floating Point Degrees to Radians Conversionp.53018.25 FNC137 – DEG / Floating Point Radians to Degrees Conversionp.53219. Data Operation 2 – FNC140 to FNC149p.53319.1 FNC140 – WSUM / Sum of Word Datap.53419.2 FNC141 – WTOB / WORD to BYTEp.53619.3 FNC142 – BTOW / BYTE to WORDp.53819.4 FNC143 – UNI / 4-bit Linking of Word Datap.54019.5 FNC144 – DIS / 4-bit Grouping of Word Datap.54219.6 FNC147 – SWAP / Byte Swapp.54419.7 FNC149 – SORT2 / Sort Tabulated Data 2p.54520. Positioning Control – FNC150 to FNC159p.54920.1 FNC150 – DSZR / Dog Search Zero Returnp.55020.2 FNC151 – DVIT / Interrupt Positioningp.55220.3 FNC152 – TBL / Batch Data Positioning Modep.55420.4 FNC155 – ABS / Absolute Current Value Readp.55520.5 FNC156 – ZRN / Zero Returnp.55620.6 FNC157 – PLSV / Variable Speed Pulse Outputp.55820.7 FNC158 – DRVI / Drive to Incrementp.56020.8 FNC159 – DRVA / Drive to Absolutep.56221. Real Time Clock Control – FNC160 to FNC169p.56421.1 FNC160 – TCMP / RTC Data Comparep.56521.2 FNC161 – TZCP / RTC Data Zone Comparep.56721.3 FNC162 – TADD / RTC Data Additionp.56921.4 FNC163 – TSUB / RTC Data Subtractionp.57121.5 FNC164 – HTOS / Hour to Second Conversionp.57321.6 FNC165 – STOH / Second to Hour Conversionp.57521.7 FNC166 – TRD / Read RTC datap.57721.8 FNC167 – TWR / Set RTC datap.57821.9 FNC169 – HOUR / Hour Meterp.58022. External Device – FNC170 to FNC179p.58222.1 FNC170 – GRY / Decimal to Gray Code Conversionp.58322.2 FNC171 – GBIN / Gray Code to Decimal Conversionp.58422.3 FNC176 – RD3A / Read form Dedicated Analog Blockp.58522.4 FNC177 – WR3A / Write to Dedicated Analog Blockp.58623. Introduction of Alternate Instructions – FNC180p.58723.1 Instruction correspondence tablep.58724. Others – FNC181 to FNC189p.58824.1 FNC182 – COMRD / Read Device Comment Datap.58924.2 FNC184 – RND / Random Number Generationp.59124.3 FNC186 – DUTY / Timing Pulse Generationp.59224.4 FNC188 – CRC / Cyclic Redundancy Checkp.59424.5 FNC189 – HCMOV / High-Speed Counter Movep.59825. Block Data Operation – FNC190 to FNC199p.60225.1 FNC192 – BK+ / Block Data Additionp.60325.2 NFC193 – BK– / Block Data Subtractionp.60625.3 FNC194~199 – BKCMP=, >, <, < >, <=, >= / Block Data Comparep.60926. Character String Control – FNC200 to FNC209p.61326.1 FNC200 – STR / BIN to Character String Conversionp.61426.2 FNC201 – VAL / Character String to BIN Conversionp.61926.3 FNC202 – $+ / Link Character Stringsp.62426.4 FNC203 – LEN / Character String Length Detectionp.62626.5 FNC204 – RIGHT / Extracting Character String Data from the Rightp.62826.6 FNC205 – LEFT / Extracting Character String Data from the Leftp.63026.7 FNC206 – MIDR / Random Selection of Character Stringsp.63226.8 FNC207 – MIDW / Random Replacement of Character Stringsp.63526.9 FNC208 – INSTR / Character string searchp.63826.10 FNC209 – $MOV / Character String Transferp.64027. Data Operation 3 – FNC210 to FNC219p.64227.1 FNC210 – FDEL / Deleting Data from Tablesp.64327.2 FNC211 – FINS / Inserting Data to Tablesp.64527.3 FNC212 – POP / Shift Last Data Read [FILO Control]p.64727.4 FNC213 – SFR / Bit Shift Right with Carryp.65027.5 FNC214 – SFL / Bit Shift Left with Carryp.65228. Data Comparison – FNC220 to FNC249p.65428.1 FNC224~230 – LD =, >, <, <>, <=, >= / Data Comparisonp.65628.2 FNC232~238 – AND=, >, <, < >, <=, >= / Data Comparisonp.65828.3 FNC240~246 – OR=, >, <, < >, <=, >= / Data Comparisonp.66029. Data Table Operation – FNC250 to FNC269p.66229.1 FNC256 – LIMIT / Limit Controlp.66329.2 FNC257 – BAND / Dead Band Controlp.66629.3 FNC258 – ZONE / Zone Controlp.66929.4 FNC259 – SCL / Scaling (Coordinate by Point Data)p.67229.5 FNC260 – DABIN / Decimal ASCII to BIN Conversionp.67629.6 FNC261 – BINDA / BIN to Decimal ASCII Conversionp.67929.7 FNC269 – SCL2 / Scaling 2 (Coordinate by X/Y Data)p.68230. External Device Communication – FNC270 to FNC276p.68630.1 FNC270 – IVCK / Inverter Status Checkp.68730.2 FNC271 – IVDR / Inverter Drivep.68930.3 FNC272 – IVRD / Inverter Parameter Readp.69130.4 FNC273 – IVWR / Inverter Parameter Writep.69330.5 FNC274 – IVBWR / Inverter Parameter Block Writep.69530.6 FNC275 – IVMC / Inverter Multi Commandp.69730.7 FNC276 - MODBUS Read/Write Instructionp.69930.7.1 Command Code and Command Parametersp.70031. Data Transfer 3 – FNC277 to FNC279p.70331.1 FNC278 – RBFM / Divided BFM Readp.70431.1.1 Common items between RBFM (FNC278) instruction and WBFM (FNC279) instructionp.70531.2 FNC279 – WBFM / Divided BFM Writep.70832. High-Speed Processing 2 – FNC280 to FNC289p.71032.1 FNC280 – HSCT / High-Speed Counter Compare With Data Tablep.71133. Extension File Register Control – FNC290 to FNC299p.71633.1 FNC290 – LOADR / Load From ERp.71733.2 FNC291 – SAVER / Save to ERp.72033.3 FNC292 – INITR / Initialize R and ERp.72833.4 FNC293 – LOGR / Logging R and ERp.73133.5 FNC294 – RWER / Rewrite to ERp.73533.6 FNC295 – INITER / Initialize ERp.74034. FX3U-CF-ADP Applied Instructions – FNC300 to FNC305p.74334.1 FNC300 – FLCRT / File create·checkp.74434.1.1 Detailed explanation of setting datap.74534.2 FNC301 – FLDEL / File delete·CF card formatp.74634.2.1 Detailed explanation of setting datap.74734.3 FNC302 – FLWR / Data writep.74834.3.1 Detailed explanation of setting datap.75034.4 FNC303 – FLRD / Data readp.75134.4.1 Detailed explanation of setting datap.75234.5 FNC304 – FLCMD / FX3U-CF-ADP commandp.75334.5.1 Detailed explanation of setting datap.75434.6 FNC305 – FLSTRD / FX3U-CF-ADP status readp.75534.6.1 Detailed explanation of setting datap.75635. SFC Program and Step Ladderp.75835.1 SFC Programp.75835.1.1 Outlinep.75835.1.2 Explanation of function and operationp.75835.1.3 SFC program creating procedurep.76035.1.4 Handling and role of initial state relayp.76335.1.5 Latched (battery backed) type state relaysp.76335.1.6 Role of the RET instructionp.76435.1.7 Preliminary knowledge for creating SFC programp.76435.1.8 SFC flow formatsp.77035.1.9 Program of branch/recombination state relaysp.77335.1.10 Rule for creating branch circuitp.77435.1.11 Program examplesp.77835.2 Step Ladderp.78735.2.1 Outlinep.78735.2.2 Explanation of function and operationp.78735.2.3 Expression of step ladderp.78935.2.4 Creation of step ladder program (SFC program -> STL program)p.79035.2.5 Preliminary knowledge for creating step ladder programsp.79135.2.6 Program with state relays in branches and recombinationp.79435.2.7 Program examplesp.79836. Interrupt Function and Pulse Catch Functionp.80436.1 Outlinep.80436.2 Common Itemsp.80536.2.1 How to disable interrupt functionp.80536.2.2 Related itemsp.80636.2.3 Cautions on use (common)p.80636.3 Input Interrupt (Interrupt Triggered by External Signal) [Without Delay Function]p.80936.3.1 Input interrupt (interrupt triggered by external signal) [without delay function]p.80936.3.2 Examples of practical programs (programs to measure short pulse width)p.81336.4 Input interrupt (Interrupt by External Signal) [With Delay Function]p.81536.5 Timer Interrupt (Interrupt in Constant Cycle)p.81536.5.1 Timer interrupt (interrupt in constant cycle)p.81536.5.2 Examples of practical program (timer interrupt programs using applied instruction)p.81736.6 Counter Interrupt - Interrupt Triggered by Counting Up of High-Speed Counterp.82036.7 Pulse Catch Function [M8170 to M8177]p.82136.8 Pulse width/Pulse period measurement function [M8075 to M8079, D8074 to D8097]p.82237. Operation of Special Devices (M8000 -, D8000 -)p.82637.1 Special Device List (M8000 -, D8000 -)p.82637.1.1 Special Auxiliary Relay (M8000 to M8511)p.82637.1.2 Special Data Register (D8000 to D8511)p.84437.2 Supplement of Special Devices (M8000 - and D8000 -)p.86637.2.1 RUN monitor and initial pulse [M8000 to M8003]p.86637.2.2 Watchdog timer [D8000]p.86737.2.3 Battery voltage low detection [M8005 and M8006]p.86737.2.4 Power failure detection time [D8008, M8008 and M8007]p.86837.2.5 Scan time (monitor) [D8010 to D8012]p.86837.2.6 Internal clock [M8011 to M8014]p.86837.2.7 Real time clock [M8015 to M8019 and D8013 to D8019]p.86937.2.8 How to set real time clockp.87037.2.9 Input filter adjustment [D8020]p.87237.2.10 Battery [BATT (BAT)] LED and [ALM] LED OFF command [M8030]p.87337.2.11 Built-in analog volume [D8030 and D8031]p.87437.2.12 Clear command [M8031 and M8032]p.87437.2.13 Memory hold stop [M8033] (output hold in STOP mode)p.87437.2.14 All outputs disable [M8034]p.87537.2.15 Individual operation for RUN/STOP input [M8035 to M8037]p.87537.2.16 Constant scan mode [M8039 and D8039]p.87637.2.17 State control in program with STL instruction/SFC chart [M8040]p.87637.2.18 Analog expansion boards [M8260 to M8279 and D8260 to D8279]p.87737.2.19 Analog special adapters [M8260 to M8299 and D8260 to D8299]p.87938. Error Check Method and Error Code Listp.88638.1 States and Colors of LEDs PLC Operation Statusp.88638.1.1 POWER (POW) LED [lit, flickering or unlit]p.88738.1.2 RUN LED [lit or unlit]p.88738.1.3 BATT (BAT) LED [lit or unlit] [FX3U/FX3UC]p.88738.1.4 ALM LED [lit or unlit] [FX3G/FX3GC]p.88738.1.5 ERROR (ERR) LED [lit, flickering or unlit]p.88838.1.6 L RUN LED [FX3UC-32MT-LT(-2)]p.88838.1.7 L ERR LED [FX3UC-32MT-LT(-2)]p.88938.2 Error Code Check Method and Indicationp.89038.2.1 Error code check method by display modulep.89038.2.2 Error code check method by GX Works2p.89138.2.3 Error indicationp.89238.3 Supplementary Explanation of Devices for Error Detectionp.89338.3.1 Error detection (M8060 to/D8060 to)p.89338.3.2 Operations of special devices for error detectionp.89438.3.3 Error detection timingp.89438.4 Error Code List and Actionp.895Appendix A: Programming Tool Applicability and Version Upgrade Historyp.903Appendix A-1 Programming Tool Applicabilityp.903Appendix A-1-1 Programming tool applicabilityp.903Appendix A-1-2 Cautions on writing during RUNp.906Appendix A-1-3 Precautions on Use of (Built-in USB) Programming Portp.910Appendix A-1-4 Cautions on using transparent function by way of USB in GOT1000 Seriesp.911Appendix A-1-5 Cautions on using transparent (2-port) function of GOT-F900 Seriesp.912Appendix A-2 Peripheral product applicability (except programming tools)p.913Appendix A-2-1 Peripheral product applicabilityp.913Appendix A-3 Version Upgrade Historyp.915Appendix A-3-1 Manufacturer's serial number check methodp.915Appendix A-3-2 Version checkp.916Appendix A-3-3 Version upgrade history [FX3S]p.916Appendix A-3-4 Version upgrade history [FX3G]p.916Appendix A-3-5 Version upgrade history [FX3GC]p.917Appendix A-3-6 Version upgrade history [FX3U]p.917Appendix A-3-7 Version upgrade history [FX3UC]p.917Appendix B: Instruction Execution Timep.919Appendix B-1 Basic Instruction Execution Timep.919Appendix B-2 Step Ladder Instruction Execution Timep.927Appendix B-3 Label (P/I) Execution Timep.927Appendix B-4 Applied Instruction Execution Timep.928Appendix B-5 Execution Time of Pulse Generation Instruction P in Each Applied Instructionp.943Appendix B-6 Execution Time on Combination of Applicable Devices and Indexingp.946Appendix B-6-1 Basic instruction (LD/LDI/AND/ANI/OR/ORI) execution timep.946Appendix B-6-2 Applied instruction execution timep.946Appendix C: Applied Instruction List [by Instruction Type/in Alphabetic Order]p.950Appendix C-1 Applied instructions [by instruction type]p.950Appendix C-2 Applied instructions [in alphabetical order]p.954Appendix D: Discontinued modelsp.957Warrantyp.959Revised Historyp.960Back Coverp.964
Page 16 of the Mitsubishi Electronics MELSEC FX3S user manual — 09R519
Page 16 · click to enlarge
Page 16

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

Related manuals

For detailed explanation of programming (basic instructions, applied instructions and step ladder instructions) in FX3S/ FX3G/FX3GC/FX3U/FX3UC PLCs, refer to this manual. For hardware information on the PLC main unit, special extension units, etc., refer to each associated manual. For acquiring manuals, contact the representative you have purchased the product from.

~ Essential manual { Manual required depending on application U Manual with additional manual for detailed explanation

Manual name Manual number Contents Model name

Manuals for PLC main unit

„FX3S PLC main unit

I/O specifications, wiring and installation of the PLC main unit FX3S extracted from the FX3S Series User’s Manual - Hardware Edition. For detailed explanation, refer to the FX3S Series User’s Manual - Hardware Edition.

U Supplied with product

FX3S Series Hardware Manual JY997D48301

I/O specifications, built-in analog specifications, wiring and installation of the PLC main unit FX3S- 30M /E -2AD extracted from the FX3S Series User’s Manual - Hardware Edition. For detailed explanation, refer to the FX3S Series User’s Manual - Hardware Edition.

U Supplied with product

FX3S-30M /E -2AD Hardware Manual JY997D51701

Details about the hardware including I/O specifications, wiring, installation and maintenance of the FX3S PLC main unit.

FX3S Series User’s Manual - Hardware Edition JY997D48601

09R535

„FX3G PLC main unit

I/O specifications, wiring and installation of the PLC main unit FX3G extracted from the FX3G Series User’s Manual - Hardware Edition. For detailed explanation, refer to the FX3G Series User’s Manual - Hardware Edition.

U Supplied with product

FX3G Series Hardware Manual JY997D46001

Details about the hardware including I/O specifications, wiring, installation and maintenance of the FX3G PLC main unit.

FX3G Series User’s Manual - Hardware Edition JY997D31301

09R521

„FX3GC PLC main unit

I/O specifications, wiring and installation of the PLC main unit FX3GC extracted from the FX3GC Series User’s Manual - Hardware Edition. For detailed explanation, refer to the FX3GC Series User’s Manual - Hardware Edition.

U Supplied with product

FX3GC Series Hardware Manual JY997D45201

FX3GC Series User’s Manual - Hardware Edition JY997D45401

Details about the hardware including I/O specifications, wiring, installation and maintenance of the FX3GC PLC main unit.

09R533

„FX3U PLC main unit

I/O specifications, wiring and installation of the PLC main unit FX3U extracted from the FX3U Series User’s Manual - Hardware Edition. For detailed explanation, refer to the FX3U Series User’s Manual - Hardware Edition.

U Supplied with product

FX3U Series Hardware Manual JY997D50301

Details about the hardware including I/O specifications, wiring, installation and maintenance of the FX3U PLC main unit.

FX3U Series User’s Manual - Hardware Edition JY997D16501

09R516

„FX3UC PLC main unit For detailed explanation, refer to the FX3UC Series User’s Manual - Hardware Edition.

U Supplied with product

FX3UC (D, DS, DSS) Series Hardware Manual JY997D50501

I/O specifications, wiring and installation of the PLC main unit FX3UC (D, DS, DSS) extracted from the FX3UC Series User’s Manual - Hardware Edition.

I/O specifications, wiring and installation of the PLC main unit FX3UC-32MT-LT-2 extracted from the FX3UC Series User’s Manual - Hardware Edition.

U Supplied with product

FX3UC-32MT-LT-2 Hardware Manual JY997D31601

Details about the hardware including I/O specifications, wiring, installation and maintenance of the FX3UC PLC main unit.

FX3UC Series User’s Manual - Hardware Edition JY997D28701

09R519

Show 19 more labels / short text on this page
Related manuals · code · − · − · ~ Additional · Manual · − · ~ Additional · Manual · − · ~ Additional · Manual · − · ~ Additional · Manual · − · − · ~ Additional · Manual
Page 17 of the Mitsubishi Electronics MELSEC FX3S user manual — 09R715
Page 17 · click to enlarge
Page 17

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

~ Essential manual { Manual required depending on application U Manual with additional manual for detailed explanation

Manual name Manual number Contents Model name

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition (this manual)

Items related to programming in PLCs including explanation of basic instructions, applied instructions and various devices in FX3S/FX3G/ FX3GC/FX3U/FX3UC PLCs.

JY997D16601

09R517

MELSEC-Q/L/F Structured Programming Manual (Fundamentals)

SH-080782ENG Programming methods, specifications, functions,

etc. required to create structured programs 13JW06

FXCPU Structured Programming Manual [Device & Common]

JY997D26001 Devices, parameters, etc. provided in structured projects of GX Works2 09R925

FXCPU Structured Programming Manual [Basic & Applied Instruction]

JY997D34701 Sequence instructions provided in structured projects of GX Works2 09R926

FXCPU Structured Programming Manual [Application Functions]

JY997D34801 Application functions provided in structured projects of GX Works2 09R927

{ Supplied with product

FX INPUT AND OUTPUT TERMINAL BLOCKS JY992D50401 Terminal block handling procedures. −

Manuals for communication control

FX Series User’s Manual - Data Communication Edition JY997D16901

Details about N : N Network, parallel link, computer link and non-protocol communication (RS instruction and FX2N-232IF).

09R715

FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - MODBUS Serial Communication Edition

JY997D26201 Explains the MODBUS serial communication network in FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs. 09R626

„Communication via RS-232C/RS-422/RS-485/USB

When using each product, refer to the User’s Manual - Hardware Edition of the PLC main unit to which each product is connected and the FX Series User’s Manual - Communication Control Edition. Refer to the FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - MODBUS Serial Communication Edition for MODBUS communication.

U Supplied with product

FX3U-USB-BD User’s Manual JY997D13501

Items about the system configuration of USB communication expansion board and the driver installation method.

U Supplied with product

FX3G-232-BD Installation Manual JY997D32001 Handling procedures of the RS-232C communication expansion board. −

U Supplied with product

FX3U-232-BD Installation Manual JY997D12901 Handling procedures of the RS-232C communication expansion board. −

U Supplied with product

FX3U-232ADP-MB Installation Manual JY997D26401 Handling procedures of the RS-232C communication special adapter. −

U Supplied with product

FX3U-232ADP Installation Manual JY997D13701 Handling procedures of the RS-232C communication special adapter. −

U Supplied with product

FX2N-232IF Hardware Manual JY992D73501 Handling procedures of the RS-232C communication special function block. −

U Supplied with product

FX3G-422-BD Installation Manual JY997D32101 Handling procedures of the RS-422 communication expansion board. −

U Supplied with product

FX3U-422-BD Installation Manual JY997D13101 Handling procedures of the RS-422 communication expansion board. −

U Supplied with product

FX3G-485-BD Installation Manual JY997D32201 Handling procedures of the RS-485 communication expansion board. −

U Supplied with product

FX3G-485-BD-RJ Installation Manual JY997D51501 Handling procedures of the RS-485 communication expansion board. −

U Supplied with product

FX3U-485-BD Installation Manual JY997D13001 Handling procedures of the RS-485 communication expansion board. −

U Supplied with product

FX3U-485ADP-MB Installation Manual JY997D26301 Handling procedures of the RS-485 communication special adapter. −

U Supplied with product

FX3U-485ADP Installation Manual JY997D13801 Handling procedures of the RS-485 communication special adapter. −

U Supplied with product

FX-485PC-IF Hardware Manual JY992D81801 Handling procedures of the RS-232C/RS-485 conversion interface. −

Show 20 more labels / short text on this page
Related manuals · code · „Programming · ~ Additional · Manual · { Additional · Manual · { Additional · Manual · { Additional · Manual · { Additional · Manual · „Terminal block · „Common · { Additional · Manual · { Additional · Manual · −
Page 18 of the Mitsubishi Electronics MELSEC FX3S user manual — JY997D16701
Page 18 · click to enlarge
Page 18

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

~ Essential manual { Manual required depending on application U Manual with additional manual for detailed explanation

Manual name Manual number Contents Model name

„Ethernet, CC-Link, MELSEC I/O LINK and AS-i system

When using each product, refer also to the User’s Manual - Hardware Edition of the PLC main unit to which each product is connected.

Describes installation specifications for the FX3U-ENET-ADP Ethernet communication special adapter extracted from the FX3U-ENET-ADP User's Manual. For details, refer to FX3U-ENET-ADP User's Manual.

U Supplied with product

FX3U-ENET-ADP Installation Manual JY997D47401

FX3U-ENET-ADP User’s Manual JY997D45801 Describes Ethernet communication special adapter details. 09R725

Handling procedures of the CC-Link master special function block. For use, refer to the FX3U-16CCL-M User’s Manual.

U Supplied with product

FX3U-16CCL-M Installation Manual JY997D43401

FX3U-16CCL-M User’s Manual JY997D43601 Details about the CC-Link master special function block. 09R724

Handling procedures of the CC-Link master special function block. For use, refer to the FX2N-16CCL-M User’s Manual.

U Supplied with product

FX2N-16CCL-M Hardware Manual JY992D93201

FX2N-16CCL-M User’s Manual JY992D93101 Details about the CC-Link master special function block. 09R710

Handling procedures of the CC-Link interface special function block. For use, refer to the FX3U-64CCL User’s Manual.

U Supplied with product

FX3U-64CCL Installation Manual JY997D29801

FX3U-64CCL User’s Manual JY997D30401 Handling procedures of the CC-Link interface special function block. 09R718

{ Supplied with product

FX2N-32CCL User’s Manual JY992D71801 Handling procedures of the CC-Link remote device station special function block. 09R711

Remote I/O station, remote device station and intelligent device station for CC-Link

{ Supplied with product

As for the remote I/O station, remote device station and intelligent device station for CC-Link, refer to each manual and the related data.

Handling procedures of the CC-Link/LT master special function block. For use, refer to the FX2N-64CL-M User’s Manual [Detailed Volume].

FX2N-64CL-M User’s Manual [Hardware Volume]

U Supplied with product

JY997D05401

FX2N-64CL-M User’s Manual [Detailed Volume]

JY997D08501 Details about the CC-Link/LT master special function block. −

Remote I/O station, remote device station, power supply adapter and dedicated power supply for CC-Link/LT

As for the remote I/O station, remote device station, power supply adapter and dedicated power supply for CC-Link/LT, refer to each manual and the related data.

{ Supplied with product

{ Supplied with product

FX2N-16LNK-M User's Manual JY992D73701 Handling procedure of the master special function block for the MELSEC I/O LINK 09R709

{ Supplied with product

FX2N-32ASI-M User’s Manual JY992D76901 Handling procedure of the master special function block for the AS-i system. −

Manuals for analog control

FX3S/FX3G/FX3GC/FX3U/FX3UC User’s Manual - Analog Control Edition

Details about the analog special function block (FX3U-4AD, FX3U-4DA, FX3UC-4AD), analog special adapter (FX3U-∗∗∗∗-ADP) and analog expansion board (FX3G-∗∗∗-BD).

JY997D16701

09R619

„Analog input, temperature input and temperature control

When using each product, refer also to the User’s Manual - Hardware Edition of the PLC main unit to which each product is connected.

Handling procedures of the 2-channel analog input expansion board. For use, refer to the FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - Analog Control Edition.

U Supplied with product

FX3G-2AD-BD Installation Manual JY997D33501

{ Supplied with product

FX2N-2AD User’s Guide JY992D74701 Handling procedures of the 2-channel analog input special function block. −

Handling procedures of the 4-channel analog input special function block. For use, refer to the FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - Analog Control Edition.

U Supplied with product

FX3U-4AD Installation Manual JY997D20701

Handling procedures of the 4-channel analog input special adapter. For use, refer to the FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - Analog Control Edition.

U Supplied with product

FX3U-4AD-ADP Installation Manual JY997D13901

Show 23 more labels / short text on this page
Related manuals · code · − · { Additional · Manual · − · { Additional · Manual · − · { Additional · Manual · − · { Additional · Manual · − · { Additional · Manual · „Common · { Additional · Manual · − · − · −
Page 19 of the Mitsubishi Electronics MELSEC FX3S user manual — Related manuals
Page 19 · click to enlarge
Page 19

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

~ Essential manual { Manual required depending on application U Manual with additional manual for detailed explanation

Manual name Manual number Contents Model name

Handling procedures of the 4-channel analog input special function block. For use, refer to the FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - Analog Control Edition.

U Supplied with product

FX3UC-4AD Installation Manual JY997D14901

{ Supplied with product

FX2N-4AD User’s Guide JY992D65201 Handling procedures of the 4-channel analog input special function block. −

{ Supplied with product

FX2NC-4AD User’s Manual JY997D07801 Handling procedures of the 4-channel analog input special function block. −

{ Supplied with product

FX2N-8AD User’s Manual JY992D86001 Handling procedures of the 8-channel analog input (and thermocouple input) special function block. 09R608

Handling procedures of the 4-channel Pt100 temperature sensor input special adapter. For use, refer to the FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - Analog Control Edition.

U Supplied with product

FX3U-4AD-PT-ADP User’s Manual JY997D14701

Handling procedures of the 4-channel Pt100 temperature sensor input special adaptor. For use, refer to the FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - Analog Control Edition.

U Supplied with product

FX3U-4AD-PTW-ADP User’s Manual JY997D29101

{ Supplied with product

FX2N-4AD-PT User’s Guide JY992D65601 Handling procedures of the 4-channel Pt100 temperature sensor input special function block. −

Handling procedures of the 4-channel Pt1000/Ni1000 temperature sensor input special adaptor. For use, refer to the FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - Analog Control Edition.

U Supplied with product

FX3U-4AD-PNK-ADP User’s Manual JY997D29201

Handling procedures of the 4-channel thermocouple input special adapter. For use, refer to the FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - Analog Control Edition.

U Supplied with product

FX3U-4AD-TC-ADP User’s Manual JY997D14801

{ Supplied with product

FX2N-4AD-TC User’s Guide JY992D65501 Handling procedures of the 4-channel thermocouple input special function block. −

Handling procedures of the 4-channel temperature control special function block. For use, refer to the FX3U-4LC User’s Manual

U Supplied with product

FX3U-4LC Installation Manual JY997D38901

FX3U-4LC User’s Manual JY997D39101 Detail about the 4-channel temperature control special function block. 09R625

Handling procedures of the 2-channel temperature control special function block. For use, refer to the FX2N-2LC User’s Manual.

U Supplied with product

FX2N-2LC User’s Guide JY992D85601

FX2N-2LC User’s Manual JY992D85801 Details about the 2-channel temperature control special function block. 09R607

When using each product, refer also to the User’s Manual - Hardware Edition of the PLC main unit to which each product is connected.

Handling procedures of the 1-channel analog output expansion board. For use, refer to the FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - Analog Control Edition.

U Supplied with product

FX3G-1DA-BD Installation Manual JY997D33601

{ Supplied with product

FX2N-2DA User’s Guide JY992D74901 Handling procedures of the 2-channel analog output special function block. −

Handling procedures of the 4-channel analog output special function block. For use, refer to the FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - Analog Control Edition.

U Supplied with product

FX3U-4DA Installation Manual JY997D20801

Handling procedures of the 4-channel analog output special adapter. For use, refer to the FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - Analog Control Edition.

U Supplied with product

FX3U-4DA-ADP User’s Manual JY997D14001

{ Supplied with product

FX2N-4DA User’s Guide JY992D65901 Handling procedures of the 4-channel analog output special function block. −

{ Supplied with product

FX2NC-4DA User’s Manual JY997D07601 Handling procedures of the 4-channel analog output special function block. −

Show 17 more labels / short text on this page
Related manuals · code · − · − · − · − · − · − · { Additional · Manual · − · { Additional · Manual · „Analog output · − · − · −
Page 20 of the Mitsubishi Electronics MELSEC FX3S user manual — Related manuals
Page 20 · click to enlarge
Page 20

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

~ Essential manual { Manual required depending on application U Manual with additional manual for detailed explanation

Manual name Manual number Contents Model name

„Analog I/O (mixed)

When using each product, refer also to the User’s Manual - Hardware Edition of the PLC main unit to which each product is connected.

Handling procedures of the 2-channel analog input/ 1-channel analog output special adapter. For use, refer to the FX3S/FX3G/FX3GC/FX3U/FX3UC Series User's Manual - Analog Control Edition.

U Supplied with product

FX3U-3A-ADP User’s Manual JY997D35601

{ Supplied with product

FX0N-3A User’s Guide JY992D49001 Handling procedures of the 2-channel analog input/ 1-channel analog output special function block. −

{ Supplied with product

FX2N-5A Users Manual JY997D11401 Handling procedures of the 4-channel analog input/ 1-channel analog output special function block. 09R616

Manuals for high-speed counter

When using each product, refer also to the User’s Manual - Hardware Edition of the PLC main unit to which each product is connected.

U Supplied with product

FX3U-4HSX-ADP Installation Manual JY997D16301 Handling procedure of the special high-speed input adapter. −

{ Supplied with product

FX3U-2HC User’s Manual JY997D36701 Handling procedure of the 2-channel high-speed counter special function block. −

FX2N-1HC User’s Guide JY992D65401 Handling procedures of the 1-channel high-speed counter special function block. −

{ Supplied with product

{ Supplied with product

FX2NC-1HC User’s Manual JY997D30701 Handling procedures of the 1-channel high-speed counter special function block. −

Manuals for positioning control

FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - Positioning Edition

JY997D16801 Details about the positioning function built in the FX3S/FX3G/FX3GC/FX3U/FX3UC Series. 09R620

„Pulse output and positioning

When using each product, refer also to the User’s Manual - Hardware Edition of the PLC main unit to which each product is connected.

Handling procedure of the special high-speed output adapter. For use, refer to the FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - Positioning Edition.

U Supplied with product

FX3U-2HSY-ADP Installation Manual JY997D16401

Handling procedures of the 1-axis pulse output block. For use, refer to the FX3U-1PG User’s Manual.

U Supplied with product

FX3U-1PG Installation Manual JY997D47101

FX3U-1PG User’s Manual JY997D47301 Details about the 1-axis pulse output block. 09R629

U Supplied with product

FX2N-1PG-E Installation Manual JY997D50601

Handling procedures of the 1-axis pulse output block. For use, refer to the FX2N/FX-1PG User’s Manual.

FX2N/FX-1PG User’s Manual JY992D65301 Handling procedures of the 1-axis pulse output block. 09R610

Handling procedures of the 1-axis pulse output block. For use, refer to the FX2N-10PG User’s Manual.

U Supplied with product

FX2N-10PG Installation Manual JY992D91901

FX2N-10PG User’s Manual JY992D93401 Details about the 1-axis pulse output block. 09R611

Handling procedures of the 1-axis positioning special extension unit. For use, refer to the FX2N-10GM/FX2N-20GM Hardware/Programming Manual

U Supplied with product

FX2N-10GM User’s Guide JY992D77701

Handling procedures of the 2-axis positioning special extension unit. For use, refer to the FX2N-10GM/FX2N-20GM Hardware/Programming Manual

U Supplied with product

FX2N-20GM User’s Guide JY992D77601

FX2N-10GM, FX2N-20GM Hardware/Programming Manual

JY992D77801 Details on the 1-axis/2-axis positioning special function unit. 09R612

Show 21 more labels / short text on this page
Related manuals · code · − · „High-speed counter · „Common · { Additional · Manual · − · − · { Additional · Manual · − · { Additional · Manual · − · { Additional · Manual · − · − · { Additional · Manual
Page 21 of the Mitsubishi Electronics MELSEC FX3S user manual — Related manuals
Page 21 · click to enlarge
Page 21

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

~ Essential manual { Manual required depending on application U Manual with additional manual for detailed explanation

Manual name Manual number Contents Model name

„Programmable cam switch

When using each product, refer also to the User’s Manual - Hardware Edition of the PLC main unit to which each product is connected.

{ Supplied with product

FX2N-1RM-E-SET User’s Manual JY992D71101 Handling procedures of the programmable cam switch special extension unit. 09R614

Manuals for FX3U-20SSC-H positioning Block

U Supplied with product

FX3U-20SSC-H Installation Manual JY997D21101

Handling procedures of the 2-axis positioning special function block. For use, refer to the FX3U-20SSC-H User's Manual.

FX3U-20SSC-H User's Manual JY997D21301 Describes FX3U-20SSC-H Positioning block details. 09R622

{ Supplied with product

FX Configurator-FP Operation Manual JY997D21801 Describes operation details of FX Configurator-FP Configuration Software. 09R916

Manuals for FX3U-CF-ADP CF card special adapter

Describes installation specifications for the FX3U-CF-ADP CF card special adapter extracted from the FX3U-CF-ADP User's Manual. For details, refer to FX3U-CF-ADP User's Manual.

U Supplied with product

FX3U-CF-ADP Installation Manual JY997D35201

FX3U-CF-ADP User's Manual JY997D35401 Describes details of the FX3U-CF-ADP CF card special adapter. 09R720

Describes FX-30P specification extracted from the FX-30P Operation manual. For details, refer to FX-30P Operation manual.

U Supplied with product

FX-30P Installation Manual JY997D34201

FX-30P Operation Manual JY997D34401 Describes Handy Programming Panel FX-30P details. 09R924

When using each product, refer also to the User’s Manual - Hardware Edition of the PLC main unit to which each product is connected.

U Supplied with product

FX3S-CNV-ADP Installation Manual JY997D48801 Handling procedures of the conversion adapter for special adapter connection. −

U Supplied with product

FX3G-CNV-ADP Installation Manual JY997D32301 Handling procedures of the conversion adapter for special adapter connection. −

U Supplied with product

FX3U-CNV-BD Installation Manual JY997D13601 Handling procedures of the connector conversion expansion board for special adapter connection. −

U Supplied with product

FX3G-4EX-BD User's Manual JY997D51301 Handling procedures of the 4 points input expansion board. −

U Supplied with product

FX3G-2EYT-BD User's Manual JY997D51401 Handling procedures of the 2 points transistor output expansion board. −

When using each product, refer also to the FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic and Applied Instruction Edition.

U Supplied with product

FX3G-8AV-BD Installation Manual JY997D33701 Handling procedures of the 8-channel analog volume expansion board. −

U Supplied with product

FX3U-8AV-BD User's Manual JY997D40901 Handling procedures of the 8-channel analog volume expansion board. −

„Battery (maintenance option)

U Supplied with product FX3U-32BL Battery JY997D14101 Battery life and handling procedures. −

U Supplied with product

FX3G-5DM Installation Manual JY997D33801 Procedures for mounting and handling the display module. −

U Supplied with product

FX3U-7DM User's Manual JY997D17101 Procedures for mounting and handling the display module. −

„Display module holder

U Supplied with product

FX3U-7DM-HLD User's Manual JY997D15401 Procedures for mounting and handling the display module holder. −

Show 16 more labels / short text on this page
Related manuals · code · { Additional · Manual · { Additional · Manual · Manuals for FX-30P · − · { Additional · Manual · Other manuals · „Connector conversion · „Input extension · „Output extension · „Analog volume · „Display module
Page 22 of the Mitsubishi Electronics MELSEC FX3S user manual — Related manuals
Page 22 · click to enlarge
Page 22

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

~ Essential manual { Manual required depending on application U Manual with additional manual for detailed explanation

Manual name Manual number Contents Model name

Memory cassette FX3G-EEPROM-32L Installation Manual

U Supplied with product

JY997D32401 Specifications and operating procedures of the memory cassette. −

U Supplied with product

FX3U-FLROM-16/64/64L/1M Hardware Manual JY997D12801 Specifications and operating procedures of the memory cassette. −

„Extension power supply unit

U Supplied with product

FX3U-1PSU-5V Installation Manual JY997D22501 Specifications and operating procedures of the extension power supply unit. −

U Supplied with product

FX3UC-1PS-5V Installation Manual JY997D12201 Specifications and operating procedures of the FX3UC-1PS-5V. −

Related manuals · code · „Memory cassette

Page 23 of the Mitsubishi Electronics MELSEC FX3S user manual — CF-ADP FX 3U -CF-ADP
Page 23 · click to enlarge
Page 23

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

Generic Names and Abbreviations Used in Manuals

Generic Names and Abbreviations Used in Manuals

FX3S Series Generic name of FX3S Series PLCs

FX3S PLC or main unit Generic name of FX3S Series PLC main units

FX3G Series Generic name of FX3G Series PLCs

FX3G PLC or main unit Generic name of FX3G Series PLC main units

FX3GC Series Generic name of FX3GC Series PLCs

FX3GC PLC or main unit Generic name of FX3GC Series PLC main units

FX3U Series Generic name of FX3U Series PLCs

FX3U PLC or main unit Generic name of FX3U Series PLC main units

FX3UC Series Generic name of FX3UC Series PLCs

FX3UC PLC or main unit Generic name of FX3UC Series PLC main units

FX2N Series Generic name of FX2N Series PLCs

FX2NC Series Generic name of FX2NC Series PLCs

FX1S Series Generic name of FX1S Series PLCs

FX1N Series Generic name of FX1N Series PLCs

FX1NC Series Generic name of FX1NC Series PLCs

Generic name of expansion boards (The models shown below): FX3G-4EX-BD, FX3G-2EYT-BD, FX3G-232-BD, FX3G-422-BD, FX3G-485-BD, FX3G-485-BD-RJ, FX3G-2AD-BD, FX3G-1DA-BD, FX3G-8AV-BD, FX3U-232-BD, FX3U-422-BD, FX3U-485-BD, FX3U-USB-BD, FX3U-8AV-BD and FX3U-CNV-BD

Generic name of special high-speed I/O adapters, special communication adapters, CF card special analog adapters, and special analog adapters Connectable equipment may vary depending on the main unit. For connectable equipment, refer to the User’s Manual - Hardware Edition of the main unit.

Special high-speed I/O adapter Generic name of special high-speed I/O adapters (The models shown below): FX3U-2HSY-ADP and FX3U-4HSX-ADP

Special communication adapter Generic name of special communication adapters (The models shown below): FX3U-232ADP(-MB), FX3U-485ADP(-MB) and FX3U-ENET-ADP

CF card special adapter Generic name of CF card special adapters:

CF-ADP FX 3U -CF-ADP

Generic name of special analog adapters (The models shown below): FX3U-4AD-ADP, FX3U-4DA-ADP, FX3U-3A-ADP, FX3U-4AD-PT-ADP, FX3U-4AD-PTW-ADP, FX3U-4AD-PNK-ADP and FX3U-4AD-TC-ADP

Connector conversion adapter Generic name of special adapter connection conversion adapter (The models shown below): FX3S-CNV-ADP and FX3G-CNV-ADP

Generic name of I/O extension equipment and special extension equipment Connectable equipment may vary depending on the main unit. For connectable equipment, refer to the User’s Manual - Hardware Edition of the main unit.

Generic name of FX2N Series I/O extension units, FX2N Series I/O extension blocks, FX2N Series I/O extension blocks, and FX0N Series I/O extension blocks Connectable equipment may vary depending on the main unit. For connectable equipment, refer to the User’s Manual - Hardware Edition of the main unit.

Generic name of special extension units and special function blocks Connectable equipment may vary depending on the main unit. For connectable equipment, refer to the User’s Manual - Hardware Edition of the main unit.

Special function unit/block or special extension equipment

Special extension unit Generic name of special extension units

Special function block Generic name of special function blocks

Open field networks CC-Link and CC-Link/LT

CC-Link equipment Generic name of CC-Link master station and CC-Link remote stations

CC-Link master (station) Generic name of CC-Link master station (having following model name): FX3U-16CCL-M, FX2N-16CCL-M

CC-Link remote station Generic name of remote I/O stations and remote device stations

CC-Link intelligent device station Generic name of CC-Link interface block (having following model name): FX3U-64CCL

Show 10 more labels / short text on this page
Abbreviation/generic name Name · Programmable controllers · Expansion boards · Expansion board · Special adapters · Special adapter · Special analog adapter · Extension equipment · Extension equipment · I/O extension equipment
Page 24 of the Mitsubishi Electronics MELSEC FX3S user manual — MELSEC I/O LINK
Page 24 · click to enlarge
Page 24

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

Generic Names and Abbreviations Used in Manuals

CC-Link/LT equipment Generic name of CC-Link/LT master station, CC-Link/LT remote I/O stations, CC-Link/LT remote device stations, power supply adapters, and dedicated power supplies

CC-Link/LT master Generic name of built-in type CC-Link/LT master and (additional) CC-Link/LT master

Built-in type CC-Link/LT master Generic name of built-in type CC-Link/LT master built in FX3UC-32MT-LT(-2)

(Additional) CC-Link/LT master Generic name of CC-Link/LT master station (having following model name): FX2N-64CL-M

Power supply adapter Generic name of units connected to supply the power to the CC-Link/LT system

Dedicated power supply Generic name of power supplies connected to supply the power to the CC-Link/LT system

AS-i master Generic name of AS-i system master station (having following model name): FX2N-32ASI-M

MELSEC I/O LINK

MELSEC I/O LINK master Generic name of MELSEC I/O LINK master station (having following model name): FX2N-16LNK-M

Ethernet adapter Generic name of Ethernet communication special adapter (having following model name): FX3U-ENET-ADP

Extension power supply unit FX3UC-1PS-5V (for FX3GC, FX3UC series), FX3U-1PSU-5V (for FX3G, FX3U series)

Memory cassette FX3G-EEPROM-32L, FX3U-FLROM-16, FX3U-FLROM-64, FX3U-FLROM-64L, and FX3U-FLROM-1M

Battery FX3U-32BL

Peripheral equipment Generic name of programming software, handy programming panels, and display units

Programming tool Generic name of programming software and handy programming panels

Programming software Generic name of programming software

GX Works2 Abbreviation of programming software packages SW DNC-GXW2-J and SW DNC-GXW2-E

GX Developer Abbreviation of programming software packages SW D5C-GPPW-J and SW D5C-GPPW-E

FX-PCS/WIN(-E) Abbreviation of programming software packages FX-PCS/WIN and FX-PCS/WIN-E

Handy programming panel (HPP) Generic name of programming panels FX-30P, FX-20P(-E) and FX-10P(-E)

RS-232C/RS-422 converter FX-232AW, FX-232AWC, and FX-232AWC-H

RS-232C/RS-485 converter FX-485PC-IF-SET and FX-485PC-IF

GOT1000 Series Generic name of GT16, GT15, GT14, GT11 and GT10

GOT-900 Series Generic name of GOT-A900 and GOT-F900 Series

GOT-A900 Series Generic name of GOT-A900 Series

GOT-F900 Series Generic name of GOT-F900 Series

ET-940 Series Generic name of ET-940 Series

FX3S Hardware Edition FX3S Series User’s Manual - Hardware Edition

FX3G Hardware Edition FX3G Series User’s Manual - Hardware Edition

FX3GC Hardware Edition FX3GC Series User’s Manual - Hardware Edition

FX3U Hardware Edition FX3U Series User’s Manual - Hardware Edition

FX3UC Hardware Edition FX3UC Series User’s Manual - Hardware Edition

Programming Manual FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

Data Communication Edition FX Series User’s Manual - Data Communication Edition

MODBUS Communication Edition FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - MODBUS Serial Communication Edition

Analog Control Edition FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - Analog Control Edition

Positioning Control Edition FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - Positioning Edition

ENET-ADP Manual FX3U-ENET-ADP User’s Manual

CF-ADP Manual FX3U-CF-ADP User’s Manual

FX-30P Manual FX-30P Operation Manual

Show 9 more labels / short text on this page
Abbreviation/generic name Name · AS-i system · Ethernet · Options · Peripheral equipment · Programming tools · USB/RS-422 converter FX-USB-AW · Display units · Manuals
Page 25 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. SFC (STL <step ladder>) programming
Page 25 · click to enlarge
Page 25

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

1.1 Programming Language in PLCs 1

1. Introduction

This chapter explains basic items related to programming in FX3S, FX3G, FX3GC, FX3U and FX3UC programmable controllers (PLCs).

1.1 Programming Language in PLCs

This section explains the features of programming in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs.

1.1.1 Types of programming languages

FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs support the following six types of programming languages:

1. List programming

1. Features In this method, sequence instructions are input in the form of instruction words such as "LD", "AND" and "OUT". This input method is the basis of sequence programs. 2) Example of list display

Step Instruction Device number

0000 LD X000

0001 OR Y005

0002 ANI X002

Specified the Device & Constant

0003 OUT Y005

2. Circuit programming

1. Features In a circuit program, a sequence circuit is drawn on the graphic screen by sequence formats and device numbers. Because a sequence circuit is expressed with contact symbols and coil symbols, the contents of a program can be understood easily. In the circuit display status, the PLC operations can be monitored.
2. Example of circuit display

Y005

Y005

The above list program is expressed in

the circuit diagram.

3. SFC (STL <step ladder>) programming

1. Features In an SFC (sequential function chart) program, sequences can be designed in accordance with the flow of machine operations.
2. Compatibility between SFC programs and other programs SFC programs can be converted into another program format. And when list programs and circuit programs are created according to certain rules, they can be converted inversely into SFC programs.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 11 more labels / short text on this page
1 Introduction · Introduction · Overview · Instruction List · Devices in Detail · … · … · … · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 26 of the Mitsubishi Electronics MELSEC FX3S user manual — 1.1.3 Compatibility among programs
Page 26 · click to enlarge
Page 26

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

1.1 Programming Language in PLCs

4. ST (structured text)

1. Features The ST language is a text language with a similar grammatical structure to the C language. The ST language can describe control achieved by syntax using selective branches with conditional statements and repetition by repetitive statements in the same way as high-level languages such as the C language. By using the ST language, you can create simple programs that are easy to understand.

5. Structured ladder

1. Features The structured ladder language is a graphic language developed based on the relay ladder programming technique. The structured ladder language is a graphic language for writing programs using ladder symbols such as contact, coils, functions, and function blocks. Since it can be understood intuitively, it is commonly used for the sequence programming. A circuit always starts from the bus line located on the left side.

6. FBD (Function Block Diagram)

1. Features The FBD (function block diagram) language is a graphic language for writing programs using parts for special processing (functions and function blocks), variables and constants. You can create programs easily by connecting parts along the flow of data and signals, and improve the programming efficiency.

1.1.2 Applicability of programming languages in programming software

The table below shows the applicability of programming languages in GX Works2 and GX Developer:

Programming Language GX Works2 GX Developer

List programming – 3

Circuit programming 3 3

SFC programming 3 3

ST 3 –

Structured ladder/FBD 3 –

1.1.3 Compatibility among programs

All sequence programs created by list programming, circuit programming or SFC programming are stored in the form of instruction words (contents at the time of list programming) in the program memory inside the PLC.

  • Programs created by these three types of input methods can be converted mutually, and then displayed and edited as shown in the figure below.

It is not possible to display or edit sequence programs created using ST, structured ladder or FBD programming by converting them from the form of instruction words (contents at the time of list programming). For displaying and editing such sequence programs using ST, structured ladder or FBD programming, the symbolic information (data indicating the program configuration such as structure and labels) is required.

→ Refer to the GX Works2 Version 1 Operating Manual (Common) for the details on symbolic information.

1 Introduction · List · Circuit SFC

Page 27 of the Mitsubishi Electronics MELSEC FX3S user manual — 4. "Pulse catch" function *6
Page 27 · click to enlarge
Page 27

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.1 Introduction of Convenient Functions 1

2. Overview (Sequence Program)

This chapter explains the basic functions of FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs. This chapter includes not only the features of PLCs but also introduction of representative functions, parameters and memory to utilize the functions of PLCs. Read this chapter before designing sequences.

2.1 Introduction of Convenient Functions

FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs have the following instruction functions.

2.1.1 Convenient functions for input processing

1. "High-speed counter" function of 1-phase or 2-phase for counting high-speed inputs *1

High-speed counters can count regardless of the scan time because they process high-speed pulses from specific input relays as interrupts. The counting result can be immediately handled as high-speed counter output interrupts by specific program processing and high-speed counter counted values by comparison instructions dedicated to high-speed counters.

  • 1-phase high-speed counters - FX 3S /FX 3G /FX 3GC PLCs: up to 60 kHz - FX 3U /FX 3UC PLCs: up to 100 kHz (200 kHz when a special high-speed input adapter *2 is used)
  • 2-phase high-speed counters - FX 3S /FX 3G /FX 3GC PLCs: up to 30 kHz - FX 3U /FX 3UC PLCs: up to 50 kHz (100 kHz when a special high-speed input adapter *2 is used) *1. This function is supported only for DC input type.

Specified the Device & Constant

*2. Can only be connected to the FX3U PLC.

→ Related instructionsHigh-speed counter compare; HSCS (FNC 53), HSCR (FNC 54),

HSZ (FNC 55) and HSCT (FNC280)

If the number of high-speed counters is insufficient, FX3U-2HC can be connected.

By extending hardware counters in the FX3U-2HC*3, high-speed pulses at up to 200 kHz can be received (except 2 and 4 edge count).

*3. Can only be connected to the FX3U/FX3UC PLCs.

→ For details, refer to FX3U-2HC User's Manual.

2. "I/O refresh" function for receiving the latest input information The input terminal information of the PLC in the batch refresh method is input all at once by the input image memory before step 0. The output information is output at one time when END instruction is executed. I/O refresh instruction can get the latest input information and immediately output the operation result during sequence operation.
→ Related instructionRefresh REF (FNC 50)
3. "Input filter adjustment" function for changing the time constant of input relays *4

Input relays in the main unit are equipped with a C-R filter of approximately 10 ms as countermeasures against

chattering and noise in input signals. Because a digital filter is adopted for the input relays X000 to X017*5, however, the filter value can be changed in sequence programs.

*4. This function is supported only for DC input type.

*5. X000 to X007 in the FX3G/FX3GC PLCs.

→ Related instructionRefresh and filter adjust instruction REFF (FNC 51)

4. "Pulse catch" function *6

FNC10-FNC19 Move & Compare

The pulse catch function is provided as a method to receive short-time pulse signals. The pulse catch function monitors signals from specific input relays, and sets special auxiliary relays in the interrupt processing as soon as signals are input. The pulse catch function can be used in a wide range of applications because even narrow pulses can be easily received. When complicated operations should be processed with high priority as interrupt by using specific trigger signals, the "interrupt" function described later is suitable.

FNC20-FNC29 Arith. & Logic Operation

*6. This function is supported only for DC input type.

→ Refer to Section 36.7.

Show 7 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 28 of the Mitsubishi Electronics MELSEC FX3S user manual — Interrupt Positioning DVIT (FNC151), ZRN (FNC156),
Page 28 · click to enlarge
Page 28

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.1 Introduction of Convenient Functions

5. Three types of "interrupt" functions for receiving short-period pulses and priority processing → Refer to Chapter 36.
1. Input interrupt *1

Signals from specific input relays are monitored. At the rising edge or falling edge of the monitored input, a specified interrupt routine is executed with highest priority.

2. Timer interrupt Specified interrupt routines are executed with highest priority at every specified time.
3. Counter interrupt *1*2

Depending on the present value of a high-speed counter, a specified interrupt routine is executed with highest priority.

*1. This function is supported only for DC input type.

*2. This function is supported only in FX3U/FX3UC PLCs.

6. Pulse width/Pulse period measurement function *3

The pulse width or pulse period of pulses input from input terminals (X000, X001, X003 and X004) of the main unit can be measured in units of 10µs. The pulse width/pulse period measurement function is available in a wide range of applications because the pulse width or pulse period can be easily taken in accordance with the setting of special auxiliary relays. The input signal delay time can be measured using two or more input terminals.

→ Refer to Section 36.8.

*3. This function is supported only in FX3G/FX3GC PLCs.

2.1.2 Convenient functions for output processing

1. "I/O refresh" function for outputting the latest input information The input terminal information of the PLC in the batch refresh method is input at one time by the input image memory before operation in the step 0. The output information is output at one time when END instruction is executed. I/O refresh instruction can get the latest input information and immediately output the operation result during sequence operation.
→ Related instructionRefresh REF (FNC 50)
2. "Pulse output" function for pulse train output control → Related instructions: Pulse Y Output PLSY (FNC 57) and

Acceleration/Deceleration Setup PLSR (FNC 59)

3. "Positioning" function for positioning control → Related instructions: DOG Search Zero Return DSZR (FNC150),

Interrupt Positioning DVIT (FNC151), ZRN (FNC156),

Variable Speed Pulse Output PLSV (FNC157),

Drive to Increment DRVI (FNC158) and

Drive to Absolute DRVA (FNC159)

2.1.3 Functions for supporting sequence control

1. "Constant scan" mode for making the operation cycle of the PLC constant The operation cycle in the PLC adopting the cyclic operation method varies depending on the contents of the program execution. In the constant scan mode (M8039 and D8039), the operation cycle can be made constant. As a result, instructions executed in synchronization with the operation can be processed in a constant cycle.
2. "All outputs disable" mode for turning OFF all output signals When the special auxiliary relay M8034 is driven, the output latch memory is cleared. Accordingly, all output relays (Y) turn OFF while the PLC is continuing its operation. However, the status of output relays (Y) in each device image memory is not cleared. As a result, when devices are monitored using a programming tool, they may be regarded as the ON status.
3. "Memory hold stop" function for holding the output status during the RUN mode even in the STOP mode When the special auxiliary relay M8033 is driven, the PLC stops and holds the output status during the RUN mode.
Page 29 of the Mitsubishi Electronics MELSEC FX3S user manual — Chapter 22, Chapter 24, Chapter 28 and
Page 29 · click to enlarge
Page 29

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.2 Introduction of Applied Instructions 1

4. Registration of "entry code" for protecting programs The entry code can be registered to prevent erroneous read/incorrect write protection of created sequence programs. With regard to online operations from GX Works2, GX Developer (Ver. 8.24A or later) and handy programming panels, the program protection level can be set by the entry code specification method. In this case, such specification that "changes of a program are disabled, but monitoring and changes of present values are enabled" is available.

→ Refer to the manual of the used programming tool.

5. Addition of "comments" for a sequence program By setting parameters, the device comment area (where Katakana, Kanji and alphanumeric characters are available) can be secured in the program memory.

→ Refer to the manual of the used programming tool.

6. Writing programs in the RUN mode Programs can be changed while the PLC is operating (RUN mode). By this function, programs can be adjusted and changed efficiently without stopping the machine.

→ Refer to the manual of the used programming tool.

7. Symbolic information storage The FX 3U /FX 3UC PLCs Ver. 3.00 or later can store symbolic information (data indicating the program configuration such as structure and labels). By using this function, you can read the symbolic information from the PLC, and edit labels, function blocks, etc. GX Works2 Ver. 1.62Q or later is required to store symbolic information.

→ Refer to the GX Works2 Version 1 Operating Manual (Common) for the details on symbolic information.

2.2 Introduction of Applied Instructions

1. Excellent fundamental performance FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs are equipped with not only fundamental applied functions for data transfer, data comparison, arithmetic operations, logical operations, data rotation, and data shift but also high-speed processing instructions for I/O refresh, interrupt, comparison dedicated to high-speed counters, and high-speed pulse output as well as initial state instructions by which standard operations for machine control are made into packages in the SFC control. In this way, FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs have the specifications offering fundamental functions, high- speed processing, and good operability.

Specified the Device & Constant

2. Advanced control easily available In addition, FX PLCs offer many handy instructions by which complicated sequence control is made into packages to mitigate the load for creating sequence programs and save the number of I/O points. FX PLCs also offer floating point arithmetic operations and PID operations to cope with more advanced control.

2.2.1 Major applied instructions

This subsection introduces representative ones among many applied instructions.

1. Program flow

  • Zone compare (ZCP/FNC 11)
  • Conditional jump (CJ/FNC 00)
  • High-speed counter compare (FNC 53 to FNC 55)
  • High-speed counter compare with data table (HSCT/FNC280)
  • Call subroutine (CALL/FNC 01)
  • Enable interrupt (EI/FNC 04)
  • Disable interrupt (DI/FNC 05)
  • Move (MOV/FNC 12)
  • Floating point move (EMOV/FNC112)
  • Start a FOR/NEXT loop (FOR/FNC 08)

→ Refer to Chapter 8.

  • High-speed counter move (HCMOV/FNC189)
  • Conversion to binary-coded decimal (BCD/FNC 18)

2. Move and compare

  • Conversion to binary (BIN/FNC 19)
  • Compare (CMP/FNC 10)

FNC10-FNC19 Move & Compare

  • Decimal to gray code conversion (FNC170) and gray code to decimal conversion (FNC171)
  • Data comparison (FNC224 to FNC246)
  • Floating point compare (ECMP/FNC110 and EZCP/FNC111)

→ Refer to Chapter 9, Chapter 13, Chapter 18,

Chapter 22, Chapter 24, Chapter 28 and

Chapter 32.

FNC20-FNC29 Arith. & Logic Operation

Show 7 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 30 of the Mitsubishi Electronics MELSEC FX3S user manual — 6. High-speed processing
Page 30 · click to enlarge
Page 30

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.2 Introduction of Applied Instructions

3. Arithmetic and logical operations

7. Handy instructions and instructions for external devices

  • Addition (ADD/FNC 20)
  • Subtraction (SUB/FNC 21)
  • Initial state (IST/FNC 60)
  • Teaching timer (TTMR/FNC 64)
  • Multiplication (MUL/FNC 22)
  • Division (DIV/FNC 23)
  • Alternate state (ALT/FNC 66)
  • Increment (INC/FNC 24)
  • Ramp variable value (RAMP/FNC 67)
  • Square root (SQR/FNC 48)
  • Rotary table control (ROTC/FNC 68)
  • Ten-key input (TKY/FNC 70)
  • Trigonometry (FNC130 to FNC135)
  • Conversion from/to floating point (FNC 49, FNC118, FNC119 and FNC129)
  • Digital switch (thumbwheel input) (DSW/FNC 72)
  • Seven-segment decoder (SEGD/FNC 73)
  • Floating point arithmetic operations (FNC120 to FNC123)
  • Seven-segment with latch (SEGL/FNC 74)
  • ASCII code data input (ASC/FNC 76)
  • Floating point square root (ESQR/FNC127)
  • BFM Read, BFM Write (FNC 78, FNC 79, FNC278, and FNC279)

→ Refer to Chapter 10, Chapter 12 and

Chapter 18.

  • Serial communication (FNC 80 and FNC 87)

4. Rotation and shift operation

  • Analog volume (FNC 85 and FNC 86)
  • Rotation right (ROR/FNC 30)
  • Inverter communication (FNC270 to FNC275)
  • Rotation left (ROL/FNC 31)
  • MODBUS communication (ADPRW/FNC276)
  • Rotation right with carry (RCR/FNC 32)
  • Hexadecimal to ASCII conversion (ASCI/FNC 82)
  • Rotation left with carry (RCL/FNC 33)
  • ASCII to hexadecimal conversion (HEX/FNC 83)
  • Bit shift right (SFTR/FNC 34)
  • Cyclic redundancy check (CRC/FNC188)
  • Bit shift left (SFTL/FNC 35)
  • Random number generation (RND/FNC184)
  • Word shift right (WSFR/FNC 36)
  • Real time clock control (FNC160 to FNC167)
  • Word shift left (WSFL/FNC 37)
  • Hour meter (HOUR/FNC 169)

→ Refer to Chapter 11.

  • Timing pulse generation (DUTY/FNC186)

5. Data operation

  • Logging R and ER (LOGR/FNC293) → Refer to Chapter 14, Chapter 15, Chapter 16,
  • Zone reset (ZRST/FNC 40)

Chapter 21, Chapter 24, Chapter 30,

  • Decode (DECO/FNC 41)

Chapter 31 and Chapter 33.

  • Encode (ENCO/FNC 42)

8. Complicated control

  • Sum of active bits (SUM/FNC 43)
  • Search a data stack (SER/FNC 61)
  • Mean (MEAN/FNC 45)
  • Word to byte (WTOB/FNC141) and byte to word (BTOW/FNC142)
  • Sort tabulated data (FNC 69 and FNC149)
  • PID control loop (PID/FNC 88)

→ Refer to Chapter 14, Chapter 16 and

  • 4-bit linking/grouping of word data (FNC143 and FNC144)

Chapter 19.

  • Limit control (LIMIT/FNC256)

9. Positioning control

  • Dead band control (BAND/FNC257)
  • Dog search zero return (DSZR/FNC150)
  • Zone control (ZONE/FNC258)
  • Interrupt positioning (DVIT/FNC151)
  • Block data operation (FNC192 to FNC199)
  • Batch data positioning mode (TBL/FNC152)
  • Character string control (FNC200 to FNC209) → Refer to Chapter 12, Chapter 19, Chapter 25,
  • Absolute present value read (ABS/FNC155)
  • Zero return (ZRN/FNC156)

Chapter 26 and Chapter 29.

  • Variable speed pulse output (PLSV/FNC157)

6. High-speed processing

  • Drive to increment (DRVI/FNC158)
  • Refresh (REF/FNC 50)
  • Drive to absolute (DRVA/FNC159)
  • Refresh and filter adjust (REFF/FNC 51)

→ Refer to Chapter 20. → Refer to the Positioning Control Manual.

  • Speed detection (SPD/FNC 56)
  • Pulse Y output (PLSY/FNC 57)
  • Pulse ramp (PLSR/FNC 59)

→ Refer to Chapter 13.

Page 31 of the Mitsubishi Electronics MELSEC FX3S user manual — → Refer to the FX 3UC Hardware Edition for the
Page 31 · click to enlarge
Page 31

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.3 Analog/Positioning Special Control 1

2.3 Analog/Positioning Special Control

For details, refer to the manual of each product.

1. Analog I/O control

  • Pulse output block (controlled by sequence program)
  • Analog input
  • Positioning unit (controlled by instructions dedicated to positioning)
  • Analog output
  • Pt100 temperature sensor input
  • Cam switch (resolver detection)
  • Thermocouple temperature sensor input

3. High-speed counter

  • Block dedicated to temperature control
  • High-speed counter (hardware counter equipped with multiplication function)

2. Positioning control

  • SSCNET ΙΙΙ - Positioning Block.

2.4 Link and Communication

FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs support the following communication functions:

1. CC-Link The CC-Link system can be constructed with an FX3G/FX3GC/FX3U/FX3UC PLCs working as the master station. An A or QnA PLC can work as the master station, and FX PLCs can be connected as remote device stations. A Q PLC can work as the master station, and FX PLCs can be connected to remote device stations or intelligent device stations. The CC-Link is an open network allowing connection of not only FX PLCs but also inverters, AC servo systems, and sensors.

6. N : N Network Up to eight FX 3S /FX 3G /FX 3GC /FX 3U /FX 3UC PLCs are connected, and data is automatically transferred among them.

→ Refer to the Data Communication Edition.

7. Parallel link Two PLCs are connected, and data is automatically transferred between them.

Specified the Device & Constant

→ Refer to the Data Communication Edition.

8. Computer link A computer such as personal computer works as the master station, up to sixteen FX and A PLCs are connected to the master station, the master station directly specifies devices in the PLC, and then data is transferred. Protocols in the computer link support the formats 1 and formats 4. By using MX Component and MX Sheet, monitoring and logging for the PLC system can be easily set by

→ Refer to the respective product manual.

2. CC-Link/LT The CC-Link/LT system can be constructed with an FX 3G /FX 3GC /FX 3U /FX 3UC PLCs working as the master station. General X (input) and Y (output) devices are assigned to remote I/O units, and operated by programs for general-purpose I/O.

Excel®.

→ Refer to the FX 3UC Hardware Edition for the

→ Refer to the Data Communication Edition. → For MX Component and MX Sheet, refer to the

built-in type CC-Link/LT master. → Refer to the product manual for the

respective product manual.

FX2N-64CL-M.

9. Non-protocol communication Non-protocol serial communication is available between an FX PLCs and interface equipment in accordance with RS-232C/RS-485 such as bar code reader, printer, personal computer and measuring instrument.
3. MELSEC I/O LINK The MELSEC I/O LINK is a remote I/O system whose master station is an FX 3U /FX 3UC (D, DS, DSS) PLCs. Units for MELSEC I/O LINK remote I/O system (A PLCs) can be used as remote units.

→ Refer to the Data Communication Edition.

→ Refer to the respective product manual.

10.Inverter communication An FX PLCs can control up to eight inverters via communication in accordance with RS-485.

4. AS-i system A network system at the actuator or sensor level can be constructed with an FX 3U /FX 3UC PLCs working as the master station in the AS-i system.

FNC10-FNC19 Move & Compare

→ Refer to the Data Communication Edition.

→ Refer to the respective product manual.

11.MODBUS communication MODBUS serial communication is available between an FX PLCs and interface equipment in accordance with RS-232C/RS-485.

5. Ethernet communication An FX PLC can be connected to the host system such as personal computer or workstation via Ethernet (100BASE-TX or 10BASE-T) using TCP/IP, UDP/IP or UDP communication protocol.

→ Refer to the MODBUS Serial Communication

FNC20-FNC29 Arith. & Logic Operation

Edition.

→ Refer to the respective product manual.

Show 7 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 32 of the Mitsubishi Electronics MELSEC FX3S user manual — 4 1 2 3
Page 32 · click to enlarge
Page 32

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.5 Introduction of Devices Constructing PLC

2.5 Introduction of Devices Constructing PLC

Many relays, timers, and counters are built into an FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs, with many NO (normally open) contacts and NC (normally closed) contacts. These contacts and coils are connected to make a sequence circuit. A PLC is also equipped with data registers (D) and extension data registers (R) functioning as memory devices to store numeric data values.

2.5.1 Relationship among devices

Arrows show transfer of signals.

Input terminal or input connector

Input relay: X Input relays function as receiving ports when the PLC receives signals from external input switches. The assigned device mnemonic is "X". The PLC has built-in input relays in accordance with its size.

4 1 2 3

Counter: C There are many counters inside the PLC. The assigned device mnemonic is "C".

Auxiliary relay: M There are many auxiliary relays inside the PLC. The assigned device mnemonic is "M".

Output relay: Y Output relays function as ports when the PLC drives external loads. There are many output relays inside the PLC. The assigned device mnemonic is "Y".

Timer: T There are many timers inside the PLC. The assigned device mnemonic is "T".

State relay: S There are many state relays inside the PLC. The assigned device mnemonic is "S".

Contact for external output from output relay (one normally open contact) The PLC has built-in output contacts in accordance with its size.

Output terminal or output connector

Page 33 of the Mitsubishi Electronics MELSEC FX3S user manual — 7. Extension registers (R) and extension file registers (ER)
Page 33 · click to enlarge
Page 33

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.5 Introduction of Devices Constructing PLC 1

2.5.2 Device list

1. Input relays (X) and output relays (Y) → Refer to Section 4.2.
5. Counters (C) The following types of counters are provided, and can be used in accordance with the purpose or application.
  • Input relay and output relay numbers are assigned to each main unit in octal "X000 to X007, X010 to X017 …, Y000 to Y007, Y010 to Y017 …" The input relay (X) numbers and output relay (Y) numbers in extension units and extension blocks are also sequential numbers in octal respectively in the order of connection to the main unit.
1. For latched (battery or EEPROM backed) counters

→ Refer to Section 4.6. Counters are provided for internal signals of the PLC, and their response speed is usually tens of Hz or less. - 16-bit counter: Provided for up-counting, counting range: 1 to 32767 - 32-bit counter: Provided for up-counting and down-counting, counting range: −2,147,483,648 to +2,147,483,647

  • A digital filter is applied to the input filter of specific input relays, and the filter value can be changed by a program. Accordingly, for a purpose requiring high-speed receiving, assign such input relay numbers. (Refer to explanation of filter adjustment, input interrupt, high-speed counter, various applied instructions, etc.)
2. For latched (battery or EEPROM backed) highspeed counters
2. Auxiliary relays (M) → Refer to Section 4.3.

→ Refer to Section 4.7 or 4.8. High-speed counters can execute counting at several kHz regardless of operations in the PLC. - 32-bit counter: Provided for up-counting and down-counting, counting range: −2,147,483,648 to +2,147,483,647 (1- phase 1-counting, 1-phase 2-counting and 2-phase 2-counting), assigned to specific input relays

  • Relays built into the PLC are auxiliary relays, and are used for programs. Different from I/O relays, auxiliary relays cannot receive external inputs or directly drive external loads.
  • There are latched (battery or EEPROM backed) type relays whose ON/OFF status is stored even if the PLC turns OFF.

Specified the Device & Constant

3. State relays (S) → Refer to Section 4.4.

6. Data registers (D) → Refer to Section 4.9. Data registers store numeric data values. All data registers in FX PLCs are 16-bit type (whose most significant bit is positive or negative). When two consecutive registers are combined, they can handle 32-bit numeric value (whose most significant bit is positive or negative). (For the numeric value range, refer to "Counter" on the previous page.) In the same way as other devices, data registers are classified into general type and latched type (battery or EEPROM backed).

  • State relays are used in the step ladder or as process numbers in the SFC expression.
  • When a state relay is not used as a process number, it can be programmed as a general contact/coil in the same way as an auxiliary relay.
  • State relays can be used as annunciators for external fault diagnosis.
4. Timers (T) → Refer to Section 4.5.
  • A timer adds and counts clock pulses of 1, 10 or 100 ms, and turns its output contact ON or OFF when the counted result reaches a specified set value. A timer can count from 0.001 to 3276.7 seconds depending on the clock pulse.

7. Extension registers (R) and extension file registers (ER)

→ Refer to Section 4.10. Extension registers (R) are the extended form of data registers (D). They are protected by the battery against power failure in FX3U/FX3UC PLCs. In FX3G/FX3GC PLCs, general type devices can be protected against power failure when the optional battery is connected. In FX3G/FX3GC/FX3U/FX3UC PLCs, the contents of extension registers (R) can be stored in extension file registers (ER). In FX3U/FX3UC PLCs, extension file registers (ER) can only be used while a memory cassette is mounted.

  • In the FX 3S PLC, 100 ms timers T32 to T62 are changed to 10 ms timers when the special auxiliary relay M8028 is driven in the program.
  • The timers T192 to T199 are dedicated to subroutines and interrupt routines. The timers T250 to T255 (T132 to T137 in FX 3S PLC) are retentive type base clock timers for 100 ms pulses. This means that the present value is retained even after the timer coil drive input turns OFF. And when the drive input turns ON again, a retentive type timer will continue its counting from where it left off.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 7 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 34 of the Mitsubishi Electronics MELSEC FX3S user manual — 2.5.2 Device list
Page 34 · click to enlarge
Page 34

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.5 Introduction of Devices Constructing PLC

8. Index registers (V)(Z) → Refer to Section 4.11. Among registers, there are index type registers V and Z used for modification. A data register V or Z is added to another device as follows: [In the case of "V0, Z0 = 5"] D100V0 = D105, C20Z0 = C25 ← Device number + V or Z value Data registers and index registers are used for indirectly specifying the set value of timers and counters, or used in applied instructions.
9. Pointers (P)(I) → Refer to Section 4.12. Pointers are classified into branch pointers and interrupt pointers.
  • A branch pointer (P) specifies the jump destination of the conditional jump CJ (FNC 00) or the call subroutine CALL (FNC 01) instruction.
  • An interrupt pointer (I) specifies the routine of an input interrupt, timer interrupt or counter interrupt.

10.Constants (K)(H)(E) → Refer to Chapter 5. Constant numerical values used in the PLC, "K" indicates a decimal integer value, "H" indicates a hexadecimal value, and "E" indicates a real number (floating point data). Constants are used as set values or present values of timers and counters, or operands for applied instructions.

Page 35 of the Mitsubishi Electronics MELSEC FX3S user manual — (EEPROM)
Page 35 · click to enlarge
Page 35

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.6 Program Memory and Devices 1

2.6 Program Memory and Devices

2.6.1 Memory structure

1. In FX 3S PLC FX 3S PLC are equipped with the EEPROM memory as standard.
1. When using the built-in memory (without attached memory cassette)

Built-in device memory (RAM, EEPROM)

Contact image memory · Input relay (X) · Output relay (Y) · Auxiliary relay (M) · State relay (S) Timer contact, time counting coil, and reset coil (T) Counter contact, counting coil, and reset coil (C)

· Data register (D) · Timer present value register (T)

Counter present value register (C) Index register (V, Z)

(EEPROM)

Specified the Device & Constant

2. When using an attached memory cassette (without using the built-in program memory)

Built-in device memory (RAM, EEPROM)

[Bit device memory] [Data memory]

Contact image memory · Input relay (X) · Output relay (Y) · Auxiliary relay (M) · State relay (S) Timer contact, time counting coil, and reset coil (T) Counter contact, counting coil, and reset coil (C)

· Data register (D) · Timer present value register (T) · Counter present value register (C) · Index register (V, Z)

(EEPROM)

(EEPROM)

The PLC automatically recognizes attachment of a memory cassette (when the power is turned ON), and disconnects the built-on program memory. (The priority is given to the memory cassette.)

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 26 more labels / short text on this page
Introduction · Overview · CPU System ROM · Instruction List · [Bit device memory] · [Data memory] · · · · Devices in Detail · Built-in program memory · (EEPROM) Memory cassette · Parameter · Sequence program · Comment · Not attached · File register (D) · Before Programming · CPU System ROM · Basic Instruction · Memory cassette · FNC00-FNC09 Program Flow · Built-in program memory · Parameter · Sequence program · Not used · Comment · File register (D)
Page 36 of the Mitsubishi Electronics MELSEC FX3S user manual — (EEPROM)
Page 36 · click to enlarge
Page 36

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.6 Program Memory and Devices

2. In FX 3G /FX 3GC PLCs FX 3G /FX 3GC PLCs are equipped with the EEPROM memory as standard.
1. When using the built-in memory (without attached memory cassette)
Mitsubishi Electronics MELSEC FX3S — 2.6 Program Memory and Devices diagram (page 36)
Fig. 2 · 2.6 Program Memory and Devices

Contact image memory · Input relay (X) · Output relay (Y) · Auxiliary relay (M) · State relay (S) Timer contact, time counting coil, and reset coil (T) Counter contact, counting coil, and reset coil (C) · Extension register (R)

· Data register (D) · Timer present value register (T) · Counter present value register (C) · Index register (V, Z)

2. When using an attached memory cassette *1 (without using the built-in program memory)

Built-in device memory (RAM, EEPROM)

[Bit device memory] [Data memory]

Contact image memory · Input relay (X) · Output relay (Y) · Auxiliary relay (M) · State relay (S) Timer contact, time counting coil, and reset coil (T) Counter contact, counting coil, and reset coil (C)

· Data register (D) · Timer present value register (T) · Counter present value register (C) · Index register (V, Z)

· Extension register (R)

Transfer and initialization by instructions

(EEPROM)

(EEPROM)

The PLC automatically recognizes attachment of a memory cassette (when the power is turned ON), and disconnects the built-on program memory. (The priority is given to the memory cassette.)

Extension file register (ER)

*1. A memory cassette can be connected only to FX3G PLC.

Show 9 more labels / short text on this page
CPU System ROM · Memory cassette · Built-in program memory · Parameter · Sequence program · Not used · Comment · File register (D) · Special setting
Page 37 of the Mitsubishi Electronics MELSEC FX3S user manual — (RAM)
Page 37 · click to enlarge
Page 37

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.6 Program Memory and Devices 1

3. In FX 3U /FX 3UC PLCs FX 3U /FX 3UC PLCs are equipped with the RAM memory as standard. By mounting a memory cassette, the memory type can be changed.
1. When using the built-in memory (without attached memory cassette)

Built-in device memory (RAM)

Contact image memory · Input relay (X) · Output relay (Y) · Auxiliary relay (M) · State relay (S) Timer contact, time counting coil, and reset coil (T) Counter contact, counting coil, and reset coil (C) · Extension register (R)

· Data register (D) · Timer present value register (T) · Counter present value register (C) · Index register (V, Z)

(RAM)

Specified the Device & Constant

2. When using an attached memory cassette (does not use the built-in program memory)

Built-in device memory (RAM)

[Bit device memory] [Data memory]

· Data register (D) · Timer present value register (T) · Counter present value register (C) · Index register (V, Z)

Contact image memory · Input relay (X) · Output relay (Y) · Auxiliary relay (M) · State relay (S) Timer contact, time counting coil, and reset coil (T) Counter contact, counting coil, and reset coil (C)

· Extension register (R)

Transfer and initialization by instructions

(RAM)

FNC10-FNC19 Move & Compare

The PLC automatically recognizes attachment of a memory cassette (when the power is turned ON), and disconnects the built-on program memory. (Priority is given to the memory cassette.)

Extension file register (ER)

*1. Supported in Ver. 3.00 or later.

FNC20-FNC29 Arith. & Logic Operation

Show 32 more labels / short text on this page
Introduction · CPU System ROM · Overview · [Bit device memory] · [Data memory] · Instruction List · Memory cassette · Built-in program memory · (Flash memory) · Devices in Detail · Parameter · Sequence program · Comment · Not attached · File register (D) · Special setting · Symbolic information*1 · Before Programming · CPU System ROM · Basic Instruction · FNC00-FNC09 Program Flow · Memory cassette · (Flash memory) · Built-in program memory · Parameter · Sequence program · Comment · Not used · File register (D) · Special setting · Symbolic information · *1
Page 38 of the Mitsubishi Electronics MELSEC FX3S user manual — 2.6.2 Memory operations and latched (battery or EEPROM backed) devices (power ON/OFF and RUN/STOP)
Page 38 · click to enlarge
Page 38

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.6 Program Memory and Devices

2.6.2 Memory operations and latched (battery or EEPROM backed) devices (power ON/OFF and RUN/STOP)

1. Backup operation The operations of the data memory, bit device memory and program memory in FX 3S /FX 3G /FX 3GC /FX 3U /FX 3UC PLCs are classified as shown below: 1) Types of program memory

Item Power OFF Power OFF→ON STOP→RUN RUN→STOP

Parameter Does not change.*2

Sequence program Does not change.*2

Does not change.*2

Can be secured by parameter setting.

File register Does not change.*2

Special setting Does not change.*2

Symbolic information*1 Does not change.*2

*1. Symbolic information is supported in the FX3U/FX3UC PLCs Ver. 3.00 or later.

*2. The contents of the program memory and device values are not backed up correctly in FX3U/FX3UC PLCs when the battery voltage becomes lower than the holding voltage if a memory cassette is not attached.

2. Types of word device memory a) FX 3S PLC

Item Power OFF Power OFF→ON STOP→RUN RUN→STOP

Does not change. Cleared.

General type Cleared.

Does not change while M8033 is ON.

Latched (EEPROM backed) type Does not change.

File type Does not change.

Special type Cleared. Set to initial

values.*3 Does not change.*3

Index register (V, Z) V, Z Cleared. Does not change.

Does not change. Cleared.

For 100 ms Cleared.

Does not change while M8033 is ON.

Does not change. Cleared.

For 10 ms Cleared.

Does not change while M8033 is ON.

Timer present value register (T)

Does not change. Cleared.

For 1 ms Cleared.

Does not change while M8033 is ON.

Retentive type for 100 ms (EEPROM backed) Does not change.

Retentive type for 1 ms (EEPROM backed) Does not change.

Does not change. Cleared.

General type Cleared.

Does not change while M8033 is ON.

Counter present value register (C)

Latched (EEPROM backed) type Does not change.

High-speed type (EEPROM backed) Does not change.

Clock data Present value Does not change.*4

*3. Some devices are cleared when the PLC status switches from STOP to RUN.

→ For special data registers, refer to Chapter 37. *4. The clock data is held by the electricity charged in the large-capacity capacitor built in the PLC. When the voltage of the large-capacity capacitor becomes low, the clock data is not held correctly. The capacitor can hold the clock data for 10 days (when the ambient temperature is 25°C) in the full charge state (achieved by powering ON the PLC for 30 minutes or more).

Comment · Data register (D)

Page 39 of the Mitsubishi Electronics MELSEC FX3S user manual — 2.6 Program Memory and Devices 1
Page 39 · click to enlarge
Page 39

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.6 Program Memory and Devices 1

b) FX3G/FX3GC PLCs

Item Power OFF Power OFF→ON STOP→RUN RUN→STOP

General type Cleared.*1 Does not change. Cleared.

Does not change while M8033 is ON.

Latched (EEPROM backed) type Does not change.

File type Does not change.

Special type Cleared. Set to initial

values.*2 Does not change.*2

Extension register (R) General type Cleared.*1 Does not change.

Extension file register (ER) File type Does not change.

Index register (V, Z) V, Z Cleared. Does not change.

Does not change. Cleared.

For 100 ms Cleared.

Does not change while M8033 is ON.

Does not change. Cleared.

For 10 ms Cleared.

Does not change while M8033 is ON.

Timer present value register (T)

Does not change. Cleared.

For 1 ms Cleared.

Does not change while M8033 is ON.

Retentive type for 100 ms (EEPROM backed) Does not change.

Retentive type for 1 ms (EEPROM backed) Does not change.

Does not change. Cleared.

General type Cleared.

Does not change while M8033 is ON.

Specified the Device & Constant

Counter present value register (C)

Latched (EEPROM backed) type Does not change.

High-speed type (EEPROM backed) Does not change.

Clock data Present value Does not change.*3

*1. These registers can be changed from the general type to the latched (battery backed) type by the parameter setting when the optional battery is installed. *2. Some devices are cleared when the PLC status switches from STOP to RUN.

→ For special data registers, refer to Chapter 37. *3. The clock data is held by the electricity charged in the large-capacity capacitor built in the PLC. When the voltage of the large-capacity capacitor becomes low, the clock data is not held correctly. The capacitor can hold the clock data for 10 days (when the ambient temperature is 25°C) in the full charge state (achieved by powering ON the PLC for 30 minutes or more). The clock data is backed up by the battery when the optional battery is installed and the battery mode is selected in the parameter setting.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 8 more labels / short text on this page
Introduction · Data register (D) · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 40 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 40 · click to enlarge
Page 40

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.6 Program Memory and Devices

c) FX3U/FX3UC PLCs

Item Power OFF Power OFF→ON STOP→RUN RUN→STOP

Does not change. Cleared.

General type Cleared.

Does not change while M8033 is ON.

Latched (battery backed) type Does not change.*1

File type Does not change.*2

Special type Cleared. Set to initial

values.*3 Does not change.*3

Extension register (R) Latched (battery backed) type Does not change.*1

(ER)*4 File type Does not change.

Index register (V, Z) V, Z Cleared. Does not change.

Does not change. Cleared.

For 100 ms Cleared.

Does not change while M8033 is ON.

Does not change. Cleared.

For 10 ms Cleared.

Timer present value register (T)

Does not change while M8033 is ON.

Retentive type for 100 ms (battery backed) Does not change.*1

Retentive type for 1 ms (battery backed) Does not change.*1

Does not change. Cleared.

General type Cleared.

Does not change while M8033 is ON.

Counter present value register (C)

Latched (battery backed) type Does not change.*1

High-speed type (battery backed) Does not change.*1

Clock data Present value Does not change.*1

*1. Device values are not backed up correctly when the battery voltage becomes lower than the holding voltage. *2. The contents of the program memory and device values are not backed up correctly when the battery voltage becomes lower than the holding voltage if a memory cassette is not attached. *3. Some devices are cleared when the PLC status switches from STOP to RUN.

→ For special data registers, refer to Chapter 37. *4. An optional memory cassette is required.

Caution

Programs (when a memory cassette is not attached), latched (battery backed) type device values and clock data is not backed up correctly when the battery voltage becomes low due to expiration of the battery life or another reason. In such a case, clear latched (battery backed) type devices, transfer programs again (when a memory cassette is not attached), and then set initial values and clock data if necessary.

→ For a rough guide to the life and replacement of the battery, refer to the PLC User’s Manual

[Hardware Edition]. → For the latched type device initialization method, refer to Subsection 2.6.5.

Data register (D) · Extension file register

Page 41 of the Mitsubishi Electronics MELSEC FX3S user manual — 2.6 Program Memory and Devices 1
Page 41 · click to enlarge
Page 41

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.6 Program Memory and Devices 1

3. Types of bit device memory a) FX 3S PLC

Item Power OFF Power OFF→ON STOP→RUN RUN→STOP

change. Cleared.

Input relay (X) Cleared.

Does not change while M8033 is

ON.

change. Cleared.

Output relay (Y) Cleared.

Does not change while M8033 is

ON.

Contact image memory (X, Y, M, S)

change. Cleared.

General type auxiliary relay (M) Cleared.

Does not change while M8033 is

ON.

Latched (EEPROM backed) type auxiliary relay (M) Does not change.

Special type auxiliary relay (M) Cleared. Set to initial

values.*1 Does not change.*1

General type state relay (S) Cleared. Does not change.

Latched (EEPROM backed) type state relay (S) Does not change.

change. Cleared.

For 100 ms Cleared.

Does not change while M8033 is

Specified the Device & Constant

ON.

change. Cleared.

For 10 ms Cleared.

Timer contact Time counting coil Reset coil (T)

Does not change while M8033 is

ON.

change. Cleared.

For 1 ms Cleared.

Does not change while M8033 is

ON.

Retentive type for 100 ms Does not change.

Retentive type for 1 ms Does not change.

change. Cleared.

General type Cleared.

Counter contact Counting coil Reset coil (C)

Does not change while M8033 is

ON.

Latched (EEPROM backed) type Does not change.

High-speed type Does not change.

*1. Some devices are cleared when the PLC status switches from STOP to RUN.

→ For special data registers, refer to Chapter 37.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 14 more labels / short text on this page
Introduction · Does not · Overview · Does not · Does not · Instruction List · Devices in Detail · Does not · Does not · Does not · Before Programming · Does not · Basic Instruction · FNC00-FNC09 Program Flow
Page 42 of the Mitsubishi Electronics MELSEC FX3S user manual — 2.6.2 Memory operations and latched (battery or EEPROM backed) devices (power ON/OFF and RUN/STOP)
Page 42 · click to enlarge
Page 42

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.6 Program Memory and Devices

b) FX3G/FX3GC PLCs

Item Power OFF Power OFF→ON STOP→RUN RUN→STOP

change. Cleared.

Input relay (X) Cleared.

Does not change while M8033 is

ON.

change. Cleared.

Output relay (Y) Cleared.

Does not change while M8033 is

ON.

change. Cleared.

Contact image memory (X, Y, M, S)

General type auxiliary relay (M) Cleared.*1

Does not change while M8033 is

ON.

Latched (EEPROM backed) type auxiliary relay (M) Does not change.

Special type auxiliary relay (M) Cleared. Set to initial

values.*2 Does not change.*2

General type state relay (S) Cleared.*1 Does not change.

Latched (EEPROM backed) type state relay (S) Does not change.

Annunciator (S) Does not change.

change. Cleared.

For 100 ms Cleared.

Does not change while M8033 is

ON.

change. Cleared.

For 10 ms Cleared.

Timer contact Time counting coil Reset coil (T)

Does not change while M8033 is

ON.

change. Cleared.

For 1 ms Cleared.

Does not change while M8033 is

ON.

Retentive type for 100 ms Does not change.

Retentive type for 1 ms Does not change.

change. Cleared.

Counter contact Counting coil Reset coil (C)

General type Cleared.

Does not change while M8033 is

ON.

Latched (EEPROM backed) type Does not change.

High-speed type Does not change.

*1. These registers can be changed from the general type to the latched (battery backed) type by the parameter setting when the optional battery is installed.

*2. Some devices are cleared when the PLC status switches from STOP to RUN.

→ For special data registers, refer to Chapter 37.

Show 7 more labels / short text on this page
Does not · Does not · Does not · Does not · Does not · Does not · Does not
Page 43 of the Mitsubishi Electronics MELSEC FX3S user manual — 2.6 Program Memory and Devices 1
Page 43 · click to enlarge
Page 43

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.6 Program Memory and Devices 1

c) FX3U/FX3UC PLCs

Item Power OFF Power OFF→ON STOP→RUN RUN→STOP

change. Cleared.

Input relay (X) Cleared.

Does not change while M8033 is

ON.

change. Cleared.

Output relay (Y) Cleared.

Does not change while M8033 is

ON.

change. Cleared.

General type auxiliary relay (M) Cleared.

Does not change while M8033 is

Contact image memory (X, Y, M, S)

ON.

Latched (battery backed) type auxiliary relay (M) Does not change.

Special type auxiliary relay (M) Cleared. Set to initial

values.*1 Does not change.*1

change. Cleared.

General type state relay (S) Cleared.

Does not change while M8033 is

ON.

Latched (battery backed) type state relay (S) Does not change.

Annunciator (S) Does not change.

Specified the Device & Constant

change. Cleared.

For 100 ms Cleared.

Does not change while M8033 is

ON.

Timer contact Time counting coil Reset coil (T)

change. Cleared.

For 10 ms Cleared.

Does not change while M8033 is

ON.

Retentive type for 100 ms Does not change.

Retentive type for 1 ms Does not change.

change. Cleared.

General type Cleared.

Counter contact Counting coil Reset coil (C)

Does not change while M8033 is

ON.

Latched (battery backed) type Does not change.

High-speed type Does not change.

*1. Some devices are cleared when the PLC status switches from STOP to RUN.

→ For special auxiliary relay names and definitions, refer to Chapter 37.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 14 more labels / short text on this page
Introduction · Does not · Overview · Does not · Does not · Instruction List · Devices in Detail · Does not · Does not · Does not · Before Programming · Does not · Basic Instruction · FNC00-FNC09 Program Flow
Page 44 of the Mitsubishi Electronics MELSEC FX3S user manual — 2. Memory cassette backup method a) FX 3S /FX 3G PLCs
Page 44 · click to enlarge
Page 44

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.6 Program Memory and Devices

2.6.3 Types of backup methods against power failure

There are the following types of latch (battery backup) for the program memory and built-in PLC devices.

1. Battery backup method a) FX 3G /FX 3GC PLCs

Latched contents The optional battery backs up the RAM memory built in the PLC and clock data.

Maintenance The battery life is around 5 years, (when the ambient temperature is 25°C). For replacement information, refer to the Users Manual [Hardware Edition] of each PLC.

b) FX3U/FX3UC PLCs

Latched contents The battery backs up the RAM memory built in the PLC, latched (battery backed) type devices and clock data.

Maintenance The battery life is around 5 years, (when the ambient temperature is 25°C). For replacement information, refer to the Users Manual [Hardware Edition] of each PLC.

1. When the battery voltage becomes low, sequence programs and other latched (battery backed) contents are lost. 2) When an optional memory cassette (flash memory) is mounted, it is not necessary to back up sequence programs by the battery.

2. Memory cassette backup method a) FX 3S /FX 3G PLCs

Latched contents The EEPROM memory built in the memory cassette backs up sequence programs.

Maintenance Maintenance is not necessary.

b) FX3U/FX3UC PLCs

Latched contents 1) The flash memory built into the memory cassette backs up sequence programs. 2) A battery is required to back up latched (battery backed) devices and clock data from failure.

Maintenance Maintenance is not necessary.

3. EEPROM memory (built in PLC) backup method a) FX 3S /FX 3G /FX 3GC PLCs

Latched contents The EEPROM memory built in the PLC backs up latched (EEPROM backed) type devices and sequence programs.

Maintenance Maintenance is not necessary.

Show 5 more labels / short text on this page
Item Description · Item Description · Item Description · Item Description · Item Description
Page 45 of the Mitsubishi Electronics MELSEC FX3S user manual — D200 FNC 40
Page 45 · click to enlarge
Page 45

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.6 Program Memory and Devices 1

2.6.4 Change between general devices and latched (battery backed) devices

1. When using latched (battery backed) type devices as non-latch type devices In FX 3U /FX 3UC PLCs, some latched (battery backed) type devices can be changed into non-latch type devices by the parameter settings. Devices dedicated to latched type cannot be changed into non-latch type devices even by the parameter settings. Such devices can be handled as non-latch type devices by clearing all latched (battery backed) type devices by the initial pulse (M8002) in a program.
2. When using non-latch type devices as latched (battery backed) type devices In FX 3U /FX 3UC PLCs, non-latch type devices can be changed into latched (battery backed) type devices by the parameter settings. In FX 3G /FX 3GC PLCs, non-latched type devices can be changed to latched (battery backed) type devices when the optional battery is installed and the battery mode is selected in the parameter setting.

2.6.5 How to initialize devices (battery backed)

Latched type devices can be initialized by clearing the entire PLC memory using peripheral equipment, clearing all latched memory using the special auxiliary relay M8032, or executing the ZRST instruction. This subsection describes two major methods.

1. M8032 (latch memory all clear)

When M8032 is turned ON, all latched type devices*1 (including reset coils of timers and counters) are cleared. M8032 can be turned ON and OFF using the forced ON/OFF operation from peripheral equipment or within the sequence program. Note that latched type devices cannot be turned ON while M8032 is ON. When turning ON M8032 within the sequence program, note that latched type devices are cleared during END processing after M8032 is turned ON. Program example: This program clears all latched type devices.

Specified the Device & Constant

M8002

M8032

→ For details, refer to Subsection 37.2.12.

*1. Includes general type devices in FX3G/FX3GC PLCs whose type is changed to the latched (battery backed) type when the optional battery is installed.

2. ZRST (FNC 40) instruction (zone reset) The ZRST instruction can clear multiple devices all at once. (Because only a limited device range can be specified for the ZRST instruction, only a part of the latched type devices can be cleared at a time.) Program example: This program clears latched (battery backed) type devices in the ranges shown in the table below in FX 3U /FX 3UC PLCs.

M500 FNC 40

ZRST M7679

Latched (battery backed) type device range

S500 FNC 40

ZRST S4095

T246 FNC 40

ZRST T255

C100 FNC 40

ZRST C199

C220 FNC 40

ZRST C255

FNC10-FNC19 Move & Compare

D200 FNC 40

ZRST D7999

→ For details on the ZRST (FNC 40) instruction, refer to Section 12.1. → For details on latched type devices, refer to Subsection 2.6.2 and Chapter 4.

FNC20-FNC29 Arith. & Logic Operation

Show 14 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Initial pulse · Before Programming · Basic Instruction · Clear input · Auxiliary relay M500~M7679 · State S500~S4095 · Timer T246~T255 · FNC00-FNC09 Program Flow · Counter C100~C199, C220~C255 · Data register D200~D7999
Page 46 of the Mitsubishi Electronics MELSEC FX3S user manual — 2.7.1 Parameter list
Page 46 · click to enlarge
Page 46

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters

2.7 Types and Setting of Parameters

Setting of parameters means setting the environment where the PLC operates. Almost all FX PLC can be used with factory default values. However, when it is necessary to attach a memory cassette, set the comment capacity, set the communication condition for serial ports, etc., the parameter settings must be changed using a programming tool such as personal computer. Some items cannot be set depending on the used PLC or programming tool. Refer to the manual of the used PLC and programming tool for details.

2.7.1 Parameter list

The following items may be set in the parameter settings.

This parameter specifies the maximum value for the number of steps to which a sequence program can be input. 1) The upper limit is determined by the capacity of the built-in memory or optional memory. 2) The program memory, file register, comment area, and other special setting capacities are contained in this memory capacity.

This parameter incorporates comments into the program memory. 1) Because comments remain in the PLC, the contents can be easily understood at the time of maintenance. 2) Up to 50 comments can be input when one block is specified, but the comment area requires 500 steps in the memory capacity.

This parameter incorporates data registers into the program memory. 1) A sequence program and control data such as machining set values can be handled together, which is convenient. 2) Up to 500 file registers can be created when one block is specified, but the file registers require 500 steps in the memory capacity.

1) This parameter sets whether or not the special unit/block initial value setting function is used. When this function is used, this function requires 4000 steps (8 blocks) in the memory capacity. 2) This parameter sets whether or not the positioning setting (constants and setting table) in TBL (FNC152) instruction is used. When this setting is used, this setting requires 9000 steps (18 blocks) in the memory capacity. 3) This parameter sets whether or not the built-in CC-Link/LT function is used. When this function is used, this function requires 500 steps (1 block) in the memory capacity.

Other special setting capacity

Device setting Latch range setting

This parameter enables to change the latched (battery backed) device range and the non-latch device range inside the PLC.

This setting is not written to the PLC. When the I/O range is set according to the system configuration, however, inputs and outputs are checked by the program check in GX Developer.

This parameter sets the initial values of the buffer memory (BFM) for each special unit/block number. It is necessary to set the memory capacity.

This parameter sets the transmission speed, point mode and station information. The memory capacity setting is required to set the station information.

This parameter sets the PLC operation mode without a battery. When the baterryless mode is set, detection of battery voltage low level error is stopped automatically, and consequently, contents of latched devices becomes inconsistent and are initialized automatically.

This parameter sets the PLC operation mode with a battery. When the check box "Use Battery" is checked, general type devices are changed to latched (battery backed) type devices.

This parameter automatically sends a specified AT command as an initialization command to a modem connected to the serial port.

RUN terminal input setting This parameter sets whether one input terminal in the PLC is used for RUN input.

RUN terminal input number

This parameter specifies the input number of the RUN input described above. X000 to X017 (Up to the built-in input number of main unit)

Show 14 more labels / short text on this page
Classification Item Description · Memory capacity · Comment area · Memory capacity · File register · I/O assignment setting · I/O assignment setting · Special unit setting · Special unit setting · Built-in CC-Link/LT Setup · Batteryless mode · Battery mode · PLC system setting · Modem initialization
Page 47 of the Mitsubishi Electronics MELSEC FX3S user manual — FX-30P GOT1000 *1
Page 47 · click to enlarge
Page 47

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters 1

This parameter sets the communication setting of the serial port.

Serial port operation setting

Setting of communication format (D8120, D8400 and D8420) Setting of station number (D8121 and D8421) Setting of timeout check (D8129, D8409 and D8429)

This parameter sets interrupt inputs for the maximum speed, bias speed, creep speed, zero return speed, acceleration time, deceleration time, and the DVIT instruction. It is necessary to set the memory capacity.

Detailed setting This parameter sets the operation table. It is necessary to set the memory capacity.

Ethernet port setting Special parameters are used in special adapters, special function blocks, etc. They are stored in the main unit. Network parameter

This parameter sets protection to prevent erroneous read/incorrect write protection of a sequence program. The entry code (8 characters), 2nd entry code (8 characters) and the customer keyword (16 characters) can each be specified in characters in the ranges of A to F and 0 to 9. In addition, a permanent PLC lock can be specified.

Program title This parameter enables a character string to be set as the program title.

2.7.2 Parameter initial values and available tools for changing parameter values

1) FX 3S PLC

Item GX Works2 Initial value

Programming tool Display unit

FX-30P GOT1000 *1

Specified the Device & Constant

Program capacity (steps) 4000 4000 4000

Refer to Subsection 2.7.3.

Comment capacity (blocks) 24 0 –

File register capacity (blocks) 0 0 0

Program title Not registered

Entry code Not registered Not registered –

Refer to Subsection 2.7.1.

Modem initialization Not set NONE –

RUN terminal input OFF INVALID OFF

Serial port operation setting Not set No –

*1. Parameter values can not be changed by the GT1020 and GT1030.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 19 more labels / short text on this page
Classification Item Description · Introduction · PLC system setting · Constant setting · Positioning instruction setting · Overview · Special parameters · Instruction List · Keyword · Others · Devices in Detail · Setting · range · 4000 16000 · Memory · capacity · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 48 of the Mitsubishi Electronics MELSEC FX3S user manual — (X0) OFF –
Page 48 · click to enlarge
Page 48

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters

2. FX 3G /FX 3GC PLCs

Programming tool Display unit

FX-10P

Item GX Works2 Initial value

(-E) *2

FX-PCS/

GOT 1000 *3

GOT-F900

FX-30P

FX-20P

WIN(-E) *2

(-E) *2

Program capacity (steps) 8000 8000

8000 2000 8000 8000 8000

Comment capacity (blocks) 0 – –

File register capacity (blocks) 0

Positioning instruction setting Not used Not used –

Program title Not registered

– – Not registered – –

Entry code Not registered

Not registered – –

Battery mode OFF OFF No – OFF – –

Modem initialization Not set Not set NONE – Not set – –

RUN terminal input OFF OFF INVALID Not used Not used

(X0) OFF –

Serial port operation setting Not set Not set No – Not set – –

*1. In the case of FX3GC PLC, select "FX3G" as the PLC type.

*2. These programming tools are not applicable to FX3G/FX3GC PLCs. The initial values in FX1N PLC are shown above.

*3. Parameter values can not be changed by the GT1020 and GT1030.

*4. Parameter values can be changed only by the F940WGOT, F94 GOT and F94 handy GOT.

Show 12 more labels / short text on this page
GX Developer · Setting · Initial value*1 · range · Series*2*4 · Refer to Subsection · Memory capacity · Not registered · Not registered · Not registered · Not registered · Refer to Subsection
Page 49 of the Mitsubishi Electronics MELSEC FX3S user manual — (X0) OFF –
Page 49 · click to enlarge
Page 49

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters 1

3. FX 3U /FX 3UC PLCs

Programming tool Display unit

GX Developer Initial value

FX-10P

Item GX Works2 Initial value

(-E) *2

FX-PCS/

GOT 1000 *3

GOT-F900

FX-30P

WIN(-E)

FX-20P

(-E) *2

Program capacity (steps) 16000 16000*1

8000 2000 8000 16000 8000

Comment capacity (blocks) 0 – –

File register capacity (blocks) 0

value setting*5 Not used Not used –

setting*5 Not used Not used –

Setup*6 Not used Not used –

Auxiliary relay [M] 500 to 1023 500 to 1023 0 to 1023 500 to 1023

Latch range (battery backed)

State relay [S] 500 to 999 500 to 999 0 to 999 500 to 999

Counter [C] (16 bits) 100 to 199 100 to 199 0 to 199 100 to 199

Counter [C] (32 bits) 220 to 255 220 to 255 200 to 255 220 to 255

Data register [D] 200 to 511 200 to 511 0 to 511 200 to 511

Program title Not registered

– – Not registered – –

Specified the Device & Constant

Entry code Not registered

Not registered – –

Batteryless mode OFF OFF No – OFF – –

Modem initialization Not set Not set NONE – Not set – –

RUN terminal input OFF OFF INVALID Not used Not used

(X0) OFF –

Serial port operation setting Not set Not set No – Not set – –

*1. The initial value is 8000 steps in GX Developer Ver. 8.18U to Ver. 8.22Y.

*2. These programming tools are not applicable to FX3U/FX3UC PLCs. The initial values in FX2N PLC are shown above.

*3. Parameter values can not be changed by the GT1020 and GT1030.

*4. Parameter values can be changed only by the F940WGOT, F94 GOT and F94 handy GOT.

*5. GX Developer Ver. 8.24A or later is applicable.

*6. This item is supported only in the FX3UC-32MT-LT-2, and can be set using GX Developer Ver. 8.68W or later.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 21 more labels / short text on this page
Introduction · Setting · range · Series*4 · *2 · Overview · Refer to Subsection · Memory capacity · Special unit initial · Instruction List · Positioning instruction · Built-in CC-Link/LT · Devices in Detail · Not registered · Not registered · Not registered · Not registered · Refer to Subsection · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 50 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 50 · click to enlarge
Page 50

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters

2.7.3 Memory capacity setting range

Cautions on setting the memory capacity

  • After changing the memory capacity setting, make sure to write both the programs and parameters to the PLC. If only the parameters are written to the PLC, program errors (such as parameter error, circuit error and grammar error) may occur in the PLC.
  • When one block is set in each capacity setting, the memory capacity is reduced by 500 steps. Each setting should satisfy the following expression:
1. Comment capacity setting >
4. Positioning instruction setting + + +
2. File register capacity setting
3. Special unit initial
5. Built-in CC-Link/LT
1. With regard to the comment capacity, up to 50 device comments can be set in one block. 2) With regard to the file register capacity, up to 500 (16-bit) file registers can be set in one block. 3) In the special unit initial value setting, 8 blocks (4000 steps) are used. 4) In the positioning instruction setting, 18 blocks (9000 steps) are used. 5) In the built-in CC-Link/LT setup, 1 block (500 steps) are used.

1. FX 3S PLC

~ Built-in memory capacity 3 Can be set by changing parameter

File register capacity setting

setting UnitStep
UnitBlock
UnitBlock

2000 3 0 to 3 0 to 3

4000 3 0 to 7 0 to 4

16000 ~ 20 to 24 0 to 4

Caution

When the memory capacity of the FX3S is 16,000 steps, the program capacity is fixed to 4,000 steps, and the total of the comment capacity and the file register capacity is limited to 12,000 steps (24 blocks). The comment capacity is automatically set when the file register capacity is set.

2. FX 3G /FX 3GC PLCs

~ Built-in memory capacity 3 Can be set by changing parameter

File register capacity setting

setting UnitStep
UnitBlock
UnitBlock
UnitBlock

2000 3 0 to 3 0 to 3 –

4000 3 0 to 7 0 to 7 –

8000 3 0 to 15 0 to 14 –

16000 3 0 to 31 0 to 14 18

32000 ~ 0 to 63 0 to 14 18

Caution

FX3G/FX3GC PLCs operate in the extension mode when the program capacity is 16,001 steps or more, and operate in the standard mode when the program capacity is 16,000 steps or less. The instruction execution time is longer in the extension mode than in the standard mode.

Example: Time required to execute the basic instruction "LD" Standard mode: 0.21 µs Extension mode: 0.42 µs

Show 9 more labels / short text on this page
Memory capacity · Setup + · setting range · value setting · Memory capacity · Comment capacity setting · Memory capacity · Comment capacity setting · Built-in positioning setting
Page 51 of the Mitsubishi Electronics MELSEC FX3S user manual — 2. FX 3U /FX 3UC PLCs
Page 51 · click to enlarge
Page 51

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters 1

3. FX 3U /FX 3UC PLCs

~ Built-in memory capacity 3 Can be set by changing parameter

File register capacity setting

setting UnitStep
setting UnitBlock
UnitBlock
UnitBlock
UnitBlock
UnitBlock

2000 3 0 to 3 0 to 3 – – 1

4000 3 0 to 7 0 to 7 – – 1

8000 3 0 to 15 0 to 14 8 – 1

16000 3 0 to 31 0 to 14 8 18 1

32000 3 0 to 63 0 to 14 8 18 1

64000 ~ 0 to 127 0 to 14 8 18 1

Caution

  • The FX 3U /FX 3UC PLCs can store symbolic information in the following capacity: - The FX 3U -FLROM-1M (memory cassette) has an area dedicated to the storage of symbolic information, and can store up to 1300 kB. - When storing the symbolic information in any memory cassette other than the FX 3U -FLROM-1M or to the built-in memory, make sure that amount of the symbolic information to be stored does not exceed the available memory capacity. It is recommended to use the FX 3U -FLROM-1M when there is a large amount of symbolic information to be stored.

Symbolic information capacity = Maximum capacity of memory cassette - Memory capacity set by parameters

It is possible to check the symbolic information capacity using the memory capacity calculation (offline) of GX Works2.

→ Refer to the GX Works2 Version 1 Operating Manual (Common) for details.

  • When symbolic information is stored, it is deleted if the memory capacity set by parameters is changed. After changing the memory capacity, write the symbolic information again.

Specified the Device & Constant

2.7.4 Compatible optional memory model

1. FX 3S /FX 3G PLCs

Model name Maximum number of

steps Memory type Allowable number of

times of writing Remarks

FX 3G -EEPROM-32L 32000 *1 EEPROM

memory 10000 times Write-protect switch and loader function are provided.

*1. The FX3S Series PLC can hold 16,000 steps of memory, but user program capacity is limited to 4,000 steps.

2. FX 3U /FX 3UC PLCs

Model name Maximum number of

steps Memory type Allowable number of

times of writing Remarks

FX3U-FLROM-64 64000 Flash memory 10000 times Write-protect switch is provided.

FX3U-FLROM-16*2 16000 Flash memory 10000 times Write-protect switch is provided.

FX3U-FLROM-64L*2 64000 Flash memory 10000 times Write-protect switch and loader function are provided.

FX3U-FLROM-1M*3 64000 Flash memory 10000 times Write-protect switch and there is an area (1300 kB) dedicated to the storage of symbolic information.

*2. Can be used with FX3UC PLCs Ver. 2.20 or later.

*3. Ver. 3.00 or later is applicable.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 13 more labels / short text on this page
Introduction · Memory capacity · Comment capacity · Special unit initial · Built-in positioning setting · Built-in CC-Link/LT Setup · value setting · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 52 of the Mitsubishi Electronics MELSEC FX3S user manual — GOT 1000 GOT-
Page 52 · click to enlarge
Page 52

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters

2.7.5 Keyword (entry code)

By registering the entry code in a PLC, the functions of programming tools, display modules, and display units to change programs, monitor devices, and the current value changing function in the PLC can be restricted (access restriction).

→ For the operations and restricted functions of display modules,

refer to the PLC main unit Hardware Edition. → For the operations and restricted functions of display units,

refer to the respective display unit manual.

1. Differences in operations caused by the entry code type The operations to change, cancel (delete) and reset the registered entry code vary depending on the entry code type.

Registered entry code Entered entry code Change Cancel Disable Outline

PLC lock – The permanent PLC lock cannot be changed, canceled or reset.

Entry code Entry code 3 3 3 The entry code can be changed, canceled and reset.

Entry code + Second entry

Entry code + Second entry code 3 3 3 The entry code and second entry code can be changed, canceled and reset.

Entry code + Second entry

Entry code + Second entry code 3 3 3 The entry code, second entry code and customer entry code can be changed, canceled and reset.

Customer keyword – – 3 The entry code can be reset.

2. Correspondence between PLC and peripheral equipment

FX-10P

Applicable PLC GX Works2

GOT 1000 GOT-

(-E) FX-20P

FX-PCS /WIN(-E)

F900 FX-30P

(-E)

FX3S/FX3G/FX3GC (From first product)

Permanent PLC lock – –

Ver. 1.08J

Ver. 8.72A

Not applicable Applicable Not applicable

FX3U/FX3UC (Ver. 2.61 or later)

Entry code 0 to 9 and A to F 8 FX3S/FX3G/FX3GC/

Ver. 1.08J

Ver. 2.00A

FX3U/FX3UC (From first product)

FX3S/FX3G/FX3GC (From first product)

8 (16 total including entry code)

0 to 9 and A to F

Ver. 1.08J

Ver. 8.24A

or later Applicable Not applicable Applicable Not applicable

FX3U/FX3UC (Ver. 2.20 or later)

FX3S/FX3G/FX3GC (From first product)

0 to 9 and A to F 16

Ver. 1.08J

Ver. 8.72A

or later Applicable Not applicable Applicable Not applicable

FX3U/FX3UC (Ver. 2.61 or later)

The security provided by the entry code, second entry code and customer keyword is limited, and is not always perfect.

Show 24 more labels / short text on this page
Permanent · code · code + Customer · keyword · Number of · Available characters · GX Developer · registered characters · Not applicable · Not applicable · or later · or later · Only reset · of entry · or later Applicable · Applicable Applicable Applicable · or later · code is allowed · Second entry code · Not applicable · or later · Customer keyword · Not applicable · or later
Page 53 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution on registering the entry code
Page 53 · click to enlarge
Page 53

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters 1

3. Entry code setting and access restriction

Setting status Peripheral equipment and access restriction

The programming tool performs the following operations in accordance with the selected registration condition: Once the permanent PLC lock is set, it cannot be reset. To reset the permanent PLC lock or write programs again to the PLC, all-clear the PLC memory.

When the permanent PLC lock is selected

Write prohibited 3 – 3 3

Read and write prohibited – – 3 3

All online operations prohibited –

The programming tool performs the following operations in accordance with the selected registration condition: It is not possible to cancel the entry code using the customer keyword.

When the customer keyword is set

Write prohibited 3 – 3 3

Read and write prohibited – – 3 3

All online operations prohibited –

The programming tool performs the following operations in accordance with the selected registration condition:

When both the entry code and second entry code are set

Write prohibited 3 – 3 3

Read and write prohibited – – 3 3

Specified the Device & Constant

All online operations prohibited –

1. When using handy programming panel FX-10P(-E)/FX-20P(-E) The programming tool performs the following operations in accordance with the head character of the entry code (in 8 characters):

All operations prohibited A,D to F,0 to 9 –

When only the entry code is set

Read/Incorrect write protection B – – 3 3

Erroneous write prohibited C 3 – 3 3

2. When using any programming tool or data access unit other than the FX-10P(-E)/FX-20P(-E) Read/Incorrect write protection is set for all entry codes.

When no entry code is set All operations are enabled.

Caution on selecting the permanent PLC lock

  • Once the permanent PLC lock is set, it cannot be reset. To reset the permanent PLC lock or write programs again to the PLC, all-clear the PLC memory.

Caution on registering the entry code

  • The entry codes are provided to restrict access from peripheral equipment to programs created by the user. Take care to save/remember the entry codes. If a registered entry code is forgotten, the online operations from the programming tool to the PLC are disabled depending on the programming tool type and the contents of the registered entry code.

FNC10-FNC19 Move & Compare

  • In an FX 3U /FX 3UC PLC whose version is earlier than Ver. 2.61, do not use a memory cassette where the customer keyword and permanent PLC lock are set. If a memory cassette where the permanent PLC lock is set is used in an FX 3U /FX 3UC PLC whose version is earlier than Ver. 2.61, the PLC does not function normally. If the PLC memory is cleared or the keyword is canceled in an FX 3U /FX 3UC PLC whose version is earlier than Ver. 2.61 for a memory cassette where the customer keyword and permanent PLC lock are set, access restrictions set by the keyword may not be able to be removed normally.

FNC20-FNC29 Arith. & Logic Operation

Show 24 more labels / short text on this page
Introduction · Program · Monitoring Present value · Registration condition · Overview · change Read Write · Instruction List · Program · Monitoring Present value · Registration condition · change Read Write · Devices in Detail · Program · Monitoring Present value · Registration condition · change Read Write · Program · Head character · Monitoring Present value · of entry code · change Read Write · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 54 of the Mitsubishi Electronics MELSEC FX3S user manual — Registering and changing the entry codes
Page 54 · click to enlarge
Page 54

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters

Registering and changing the entry codes

This section explains the operating procedure of GX Works2, GX Developer.

→ For the entry code registration/change procedure in FX-10P(-E), FX-20P(-E), FX-30P,

and FX-PCS/WIN(-E), refer to the manual of each product.

1. Set the PLC to the STOP mode.
2. Open New keyword registration dialog box.
  • GX Works2 Select [Online] → [Password/Keyword] → [New...] to open New Keyword Registration dialog box.
  • GX Developer Select [Online] → [Keyword setup] → [Register...] to open New keyword register dialog box.
3. Set the function selection, keyword input, protection level. The setting method is different between GX Works2 and GX Developer.
  • GX Works2
Mitsubishi Electronics MELSEC FX3S — Registering and changing the entry codes diagram (page 54)
Fig. 3 · Registering and changing the entry codes

Set item Contents of setting Remarks

When "Permanent PLC lock" is selected, it cannot be reset. To reset the permanent PLC lock or write programs again to the PLC, all-clear the PLC memory. To use two keywords, select "Keyword Protection(16 digits)".

  • Select one of the following.
  • Keyword Protection(16 digits)
  • Keyword Protection(8 digits)
  • Permanent PLC Lock

Keyword(16 digits) Input 16 characters. Available characters are A to F and 0 to 9.

Set 8 characters in the first field, and set 8 characters in the second field.

Keyword(8 digits) Input 8 characters. Available characters are A to F and 0 to 9. Set 8 characters in the first field.

Retype Keyword Set the same keyword. This input is required for confirmation.

Put a check mark in the check box "Customer keyword is used(16 digits)". Set 8 characters in the former area, and set 8 characters in the latter area.

Customer Keyword Input 16 characters. Available characters are A to F and 0 to 9.

Retype Keyword Set a same keyword. This input is required for confirmation.

  • Select one of the following.
  • Read/Write Protection
  • Write Protection
  • All Online Operation Protection

To select "Protection Level", set "Keyword Protection(16 digits)" or "Permanent PLC Lock" in "Function Selection".

Function Selection · Keyword Input · Protection Level

Page 55 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution on registering the entry code
Page 55 · click to enlarge
Page 55

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters 1

  • GX Developer
Mitsubishi Electronics MELSEC FX3S — 2.7 Types and Setting of Parameters 1 diagram (page 55)
Fig. 4 · 2.7 Types and Setting of Parameters 1

Set item Contents of setting Remarks

When "Permanent PLC lock" is selected, it cannot be reset. To reset the permanent PLC lock or write programs again to the PLC, all-clear the PLC memory.

  • Select one of the following.
  • Keyword Protection
  • Permanent PLC Lock

Keyword Input 8 characters. Available characters are A to F and 0 to 9. -

2nd Keyword Input 8 characters. Available characters are A to F and 0 to 9.

Before setting the second entry code, set the entry code first.

Customer keyword Input 16 characters. Available characters are A to F and 0 to 9.

Before setting the customer keyword, set the entry code and second entry code first.

Specified the Device & Constant

  • Select one of the following:
  • Read/Write protection
  • Write protection
  • All online operation protection

Before setting the protection level, set the second entry code or select "Permanent PLC lock" in "Function selection".

Caution on registering the entry code

The entry codes are provided to restrict access from peripheral equipment to programs created by the users. Keep the entry codes carefully. If a registered entry codes is forgotten, the online operations from a programming tool to the PLC are disabled depending on the programming tool type and the contents of the registered entry code.

4. Register the keyword to the PLC.
  • GX Works2 Click the [Execute] button to register the keyword to the PLC. When "Permanent PLC Lock" is selected, however, the following dialog box appears when the [Execute] button is clicked. Click the [OK] button to register protection to the PLC.
Mitsubishi Electronics MELSEC FX3S — Caution on registering the entry code diagram (page 55)
Fig. 5 · Caution on registering the entry code

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 10 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Function Selection · Keyword Input · Protection level · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 56 of the Mitsubishi Electronics MELSEC FX3S user manual — 2.7.5 Keyword (entry code)
Page 56 · click to enlarge
Page 56

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters

  • GX Developer Click [Execution] button to open Keyword confirmation dialog box. Enter the same keyword again, and click the [OK] button to register the keyword to the PLC.
Mitsubishi Electronics MELSEC FX3S — 2.7.5 Keyword (entry code) diagram (page 56)
Fig. 6 · 2.7.5 Keyword (entry code)

When "Permanent PLC Lock" is selected, however, the following dialog box appears when the [Execute] button is clicked. Click the [OK] button to register protection to the PLC.

Mitsubishi Electronics MELSEC FX3S — 2.7.5 Keyword (entry code) diagram (page 56)
Fig. 7 · 2.7.5 Keyword (entry code)
Page 57 of the Mitsubishi Electronics MELSEC FX3S user manual — Reading/writing a program from/to a PLC with the entry codes registered
Page 57 · click to enlarge
Page 57

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters 1

Reading/writing a program from/to a PLC with the entry codes registered

This section explains the operating procedure of GX Works2, GX Developer.

→ For the program reading/writing procedure in FX-10P(-E), FX-20P(-E), FX-30P, and FX-PCS/WIN(-E),

refer to the manual of each product.

1. Select [Online] → [Read from PLC...]/[Write to PLC...] to open Input current keyword dialog box.
2. Input the keyword (8 digits, 16 digits), 2nd keyword or customer keyword currently registered in the PLC. The setting method is different between GX Works2 and GX Developer.
  • GX Works2
Mitsubishi Electronics MELSEC FX3S — Reading/writing a program from/to a PLC with the entry codes registered diagram (page 57)
Fig. 8 · Reading/writing a program from/to a PLC with the ent…

Set item Contents of setting Remarks

Enter only the first 8 digits when "Keyword Protection (8 digits)" is registered. When the customer keyword is set, 16 characters for the customer keyword are available.

Keyword Input 16 characters. Available characters are A to F and 0 to 9.

  • GX Developer

Specified the Device & Constant

Mitsubishi Electronics MELSEC FX3S — Reading/writing a program from/to a PLC with the entry codes registered diagram (page 57)
Fig. 9 · Reading/writing a program from/to a PLC with the ent…

Set item Contents of setting Remarks

Keyword Input 8 characters. Available characters are A to F and 0 to 9.

When cancelling the keyword using the customer keyword instead of entering the keyword, enter the former 8 characters of the customer keyword.

2nd Keyword Input 8 characters. Available characters are A to F and 0 to 9.

When cancelling the 2nd keyword using the customer keyword instead of entering the 2nd keyword, enter the latter 8 characters of the customer keyword.

3. Click [Execution] button to verify the keywords you have input with the keywords currently registered in the PLC.
  • When the entry code inputs are verified, the PLC executes "Read from PLC" or "Write to PLC".
  • When the entry code inputs are not verified, the PLC does not execute "Read from PLC" or "Write to PLC".

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 7 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 58 of the Mitsubishi Electronics MELSEC FX3S user manual — Canceling the entry codes
Page 58 · click to enlarge
Page 58

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters

Canceling the entry codes

This section explains the operating procedure of GX Works2, GX Developer.

→ For the entry code canceling (deletion) procedure in FX-10P(-E), FX-20P(-E), FX-30P, and FX-PCS/WIN(-E),

refer to the manual of each product.

1. Set the PLC to the STOP mode.
2. Open Keyword cancel dialog box.
  • GX Works2 Select [Online] → [Password/Keyword] → [Delete...] to open Keyword Delete dialog box.
  • GX Developer Select [Online] → [Keyword setup] → [Delete...] to open Keyword cancel dialog box.
3. Input the keyword (8 digits, 16 digits) and 2nd keyword currently registered in the PLC. The setting method is different between GX Works2 and GX Developer.
  • GX Works2
Mitsubishi Electronics MELSEC FX3S — Canceling the entry codes diagram (page 58)
Fig. 10 · Canceling the entry codes

Set item Contents of setting Remarks

Keyword Input 16 characters. Available characters are A to F and 0 to 9.

Enter only the first 8 digits when "Keyword Protection (8 digits)" is registered. It is not possible to cancel the keyword using the customer keyword.

  • GX Developer
Mitsubishi Electronics MELSEC FX3S — Canceling the entry codes diagram (page 58)
Fig. 11 · Canceling the entry codes

Set item Contents of setting Remarks

Keyword Input 8 characters. Available characters are A to F and 0 to 9.

It is not possible to cancel the keyword using the customer keyword. 2nd Keyword Input 8 characters. Available characters are A to F and 0 to 9.

4. Click [Execution] button to verify the entry codes you have input with the entry codes currently registered in the PLC.
  • When the entry code inputs are verified, the PLC executes "Keyword Cancel".
  • When the entry code inputs are not verified, the PLC does not execute "Keyword Cancel".
Page 59 of the Mitsubishi Electronics MELSEC FX3S user manual — Resetting the entry codes, and validating the reset entry codes (Keyword Protect)
Page 59 · click to enlarge
Page 59

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters 1

Resetting the entry codes, and validating the reset entry codes (Keyword Protect)

This section explains the operating procedure of GX Works2, GX Developer.

→ For the entry code reset procedure in FX-10P(-E), FX-20P(-E), FX-30P, and FX-PCS/WIN(-E),

refer to the manual of each product.

1. Open Keyword disable dialog box.
  • GX Works2 Select [Online] → [Password/Keyword] → [Disable...] to open Keyword Disable dialog box.
  • GX Developer Select [Online] → [Keyword setup] → [Disable...] to open Keyword Disable dialog box.
2. Input the keyword (8 digits, 16 digits), 2nd keyword or customer keyword currently registered in the PLC. The setting method is different between GX Works2 and GX Developer.
  • GX Works2
Mitsubishi Electronics MELSEC FX3S — Resetting the entry codes, and validating the reset entry codes (Keyword Protect) diagram (page 59)
Fig. 12 · Resetting the entry codes, and validating the reset…

Set item Contents of setting Remarks

Specified the Device & Constant

Enter only the first 8 digits when "Keyword Protection (8 digits)" is registered. When cancelling the keyword using the customer keyword instead of entering the keyword, enter the former 8 characters of the customer keyword.

Keyword Disable Keyword Input 16 characters. Available characters are A to F and 0 to 9.

Keyword Protect Reset entry codes are made valid again. -

  • GX Developer
Mitsubishi Electronics MELSEC FX3S — Resetting the entry codes, and validating the reset entry codes (Keyword Protect) diagram (page 59)
Fig. 13 · Resetting the entry codes, and validating the reset…

Set item Contents of setting Remarks

When the customer keyword is set in the FX3S/ FX3G/FX3GC/FX3U/FX3UC PLCs, its former 8 characters are available.

Keyword Input 8 characters. Available characters are A to F and 0 to 9.

When the customer keyword is set in the FX3S/ FX3G/FX3GC/FX3U/FX3UC PLCs, its latter 8 characters are available.

FNC10-FNC19 Move & Compare

2nd Keyword Input 8 characters. Available characters are A to F and 0 to 9.

Keyword Protect Reset entry codes are made valid again. -

3. Click [Execution] button to reset the entry codes or validate the reset entry codes again.

FNC20-FNC29 Arith. & Logic Operation

Show 8 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow · Keyword Disable
Page 60 of the Mitsubishi Electronics MELSEC FX3S user manual — 2.7.9 Parameter settings
Page 60 · click to enlarge
Page 60

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters

2.7.6 Special unit initial value setting

The initial values of the buffer memory (BFM) in special function units/blocks connected to an FX3UC PLC Ver.2.20 or later and FX3U PLC can be set as a parameter in GX Works2 or GX Developer. When this parameter is used, it is not necessary to execute initial setting in a user program for special function units/ blocks requiring initial setting. The special unit initial value setting uses 4000 steps (8 blocks) in the memory capacity.

→ For the setting procedure, refer to Subsection 2.7.9. → For GX Developer, refer to the GX Developer Version 8 Operating Manual.

2.7.7 Positioning instruction setting

In the positioning instruction setting available in all FX3UC PLC Ver. 2.20 or later and FX3G/FX3GC/FX3U PLCs, constants can be set in the table for the TBL (FNC152) instruction. Make sure to set this parameter when using TBL (FNC152) instruction. The positioning instruction setting for TBL (FNC152) instruction uses 9000 steps (18 blocks) in the memory capacity.

→ For details on TBL (FNC152) instruction, refer to the Positioning Control Manual. → For the setting procedure, refer to the Positioning Control Manual or Subsection 2.7.9.

→ For GX Developer, refer to the GX Developer Version 8 Operating Manual.

2.7.8 Built-in CC-Link/LT Setup (dedicated to FX 3UC -32MT-LT-2)

The set item "Built-in CC-Link/LT Setup" is dedicated to the FX3UC-32MT-LT-2. The CC-Link/LT setting (transmission speed, point mode and station information) is available in the parameter setting using GX Works2 or GX Developer. The built-in CC-Link/LT setup uses 500 steps (1 block) in the memory capacity.

→ For the setting procedure, refer to the FX3UC Hardware Edition or Subsection 2.7.9.

→ For GX Developer, refer to the GX Developer Version 8 Operating Manual.

2.7.9 Parameter settings

This subsection explains the parameter setting procedures by GX Works2.

→ For network parameter setting, refer to the GX Works2 Version 1 Operating Manual (Common).

→ For Ethernet adapter setting, refer to FX3U-ENET-ADP User's Manual. 1 Opening the parameter setting screen

In the project view area provided on the navigation window, double-click [Parameter] → [PLC parameter]. If the navigation window is not displayed, select [View] → [Docking Window] → [Navigation] from the menu bar.

Mitsubishi Electronics MELSEC FX3S — 2.7.9 Parameter settings diagram (page 60)
Fig. 14 · 2.7.9 Parameter settings
Page 61 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 61 · click to enlarge
Page 61

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters 1

2 Setting memory capacity

Mitsubishi Electronics MELSEC FX3S — 2.7 Types and Setting of Parameters 1 diagram (page 61)
Fig. 15 · 2.7 Types and Setting of Parameters 1

Set item Contents of setting Setting range

Memory Capacity Set the program memory capacity.

Comments Capacity Set the capacity of comments to be stored in the PLC. 50 device comments/block (500 steps)

The symbolic information capacity when the built-in memory or a memory cassette is used is displayed here based on the "Memory Capacity" value. Press the [Check Other Items] button to display the symbolic information capacity when a memory cassette is used.

Refer to Subsection 2.7.2 or Sub- section 2.7.3

Specified the Device & Constant

File Register Capacity Set the file register capacity. 500 file registers/block (500 steps)

Program Capacity The number of steps available for sequence program is displayed here.

Special Function Memory Capacity

Set whether "Special Function Block Settings", "Positioning Instruction Settings", "Built-in CC-Link/LT Settings" should be enabled. –

Special Function Block Settings Selects the initial value setting function for special function unit/block. –

Positioning Instruction Settings Validates the TBL (FNC152) instruction setting function. –

Built-in CC-Link/LT Settings Validates the CC-Link/LT station information setting function. –

Caution

  • When the memory capacity of the FX 3S is 16,000 steps, the program capacity is fixed to 4,000 steps, and the total of the comment capacity and the file register capacity is limited to 12,000 steps (24 blocks). The comment capacity is automatically set when the file register capacity is set.
  • FX 3G /FX 3GC PLCs operate in the extension mode when the program capacity is 16,001 steps or more, and operate in the standard mode when the program capacity is 16,000 steps or less. The instruction execution time is longer in the extension mode than in the standard mode.

Example: Time required to execute the basic instruction "LD" Standard mode: 0.21 µs Extension mode: 0.42 µs

  • In FX 3U /FX 3UC PLCs, when symbolic information is stored, it is deleted if the memory capacity set by parameters is changed. After changing the memory capacity, write the symbolic information again.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 8 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Symbolic Information Capacity · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 62 of the Mitsubishi Electronics MELSEC FX3S user manual — 4 Setting the PLC name
Page 62 · click to enlarge
Page 62

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters

3 Setting devices

1. Click [Device] tab, and set devices.
Mitsubishi Electronics MELSEC FX3S — 3 Setting devices diagram (page 62)
Fig. 16 · 3 Setting devices

Set item Contents of setting Setting range

Supplemental Relay Set the latched (battery backed) auxiliary relay range. Initial value: 500 to 1023 0 to 1023

State Set the latched (battery backed) state relay range. Initial value: 500 to 999 0 to 999

Timer The setting displayed here cannot be changed. –

Counter (16bit) Set the latched (battery backed) 16-bit counter range. Initial value: 100 to 199 0 to 199

Counter (32bit) Set the latched (battery backed) 32-bit counter range. Initial value: 220 to 255 200 to 255

Data Register Set the data register range (battery backed). Initial value: 200 to 511 0 to 511

Extended Register All extension registers are latched (battery backed). This setting is fixed, and cannot be changed. –

4 Setting the PLC name

1. Click [PLC Name] tab, and input the program title.
Mitsubishi Electronics MELSEC FX3S — 4 Setting the PLC name diagram (page 62)
Fig. 17 · 4 Setting the PLC name

Set item Contents of setting Setting range

Title Input the program title in up to 32 half-width characters (or 16 full-width characters).

32 half-width characters (or 16 full-width characters)

Page 63 of the Mitsubishi Electronics MELSEC FX3S user manual — 2.7 Types and Setting of Parameters 1
Page 63 · click to enlarge
Page 63

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters 1

5 Setting special function block

1. Click the [Special Function Block] tab, and then set the special function unit/block and built-in CC-Link/LT. In order to use the "Special Function Block" field, the "Special Function Block Settings" box in the [Memory Capacity] tab must be checked first. When setting the station information in "Built-in CC-Link/LT Setting", it is necessary to put a check mark to "Built-in CC-Link/LT Settings" on the [Memory Capacity] tab.
Mitsubishi Electronics MELSEC FX3S — 2.7 Types and Setting of Parameters 1 diagram (page 63)
Fig. 18 · 2.7 Types and Setting of Parameters 1

Specified the Device & Constant

Set item Contents of setting Setting range

Unit No. This is the unit number of each special function unit/block. –

32 half-width characters (or 16 full-width

Unit Name Set the name of each special function unit/block whose initial values are to be set.

Special Function Block Settings (It is necessary to set the memory capacity.)

Up This button moves the cursor to the upper line (transposes the upper line). –

Down This button moves the cursor to the lower line (transposes the lower line). –

This button displays Special Function Block Settings dialog box of the selected unit number.

→Refer to the next page.

Delete This button deletes the setting of the selected unit number. –

Delete All This button deletes all existing setting in "Special Unit" field. –

Read PLC Data This button reads "Special Unit" field from the connected PLC. –

Setting This button displays the Built-in CC-Link/LT Setting dialog box. –

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 10 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · characters) · Setting · Basic Instruction · Built-in CC-Link/LT Setting · FNC00-FNC09 Program Flow
Page 64 of the Mitsubishi Electronics MELSEC FX3S user manual — 2.7.6 Special unit initial value setting
Page 64 · click to enlarge
Page 64

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters

2. On Special Function Block Settings dialog box, set the initial values of special function units/ blocks.
Mitsubishi Electronics MELSEC FX3S — 2.7.6 Special unit initial value setting diagram (page 64)
Fig. 19 · 2.7.6 Special unit initial value setting

Set item Contents of setting Setting range

Unit No. tab Select the unit number of a special function unit/block to be set. –

32 half-width characters (or 16 full-width char-

Unit Name Set the name of a special function unit/block whose initial values are to be set.

This column indicates the order of initial value setting in the selected unit number. Numbers 1 to 98 can be set.

No.

Address Set the buffer memory address (BFM number) in a decimal value whose initial value is to be set. *1

This column is displayed when device comments are registered. On the above screen, "Input mode of CH1 to CH4" is registered as the device comment for "U0\G0" (unit No. 0, BFM#0).

Set a value to be set as the initial value of the buffer memory address (BFM number). Set the data length and type of the set value in "Size/Type" column.

Select the size and type of a value set to the buffer memory among the following: 16bit/DEC 32bit/DEC 16bit/HEX 32bit/HEX

Insert This button inserts a line in the currently selected position. –

Delete This button deletes the currently selected line. –

Up This button moves the cursor to the upper line (transposes the upper line). –

Down This button moves the cursor to the lower line (transposes the lower line). –

Check the Identification Code Before Initializing

Check mark this box to check the model code of the special function unit/block before initialization. –

Identification Code Set the model code of the special function unit/block *3

*1. Input buffer memory addresses (BFM numbers) that in the connected special function unit/block hold.

*2. To each buffer memory address (BFM number), set a value within the allowed range in the connected special function unit/block.

*3. Refer to the manual of the connected special function unit/block.

3. Click [OK] button to finish the setting and close Special Function Block Settings dialog box.
Show 5 more labels / short text on this page
acters) · Comment · Value · *2 · Size/Type
Page 65 of the Mitsubishi Electronics MELSEC FX3S user manual — 2.7 Types and Setting of Parameters 1
Page 65 · click to enlarge
Page 65

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters 1

6 Set the Built-in CC-Link/LT

1. Set the built-in CC-Link/LT on the Built-in CC-Link/LT Setting dialog box.
Mitsubishi Electronics MELSEC FX3S — 2.7 Types and Setting of Parameters 1 diagram (page 65)
Fig. 20 · 2.7 Types and Setting of Parameters 1

Set item Contents of setting Setting range

Select one of the following supported built-in CC-Link/LT transmission rates: 2.5Mbps 625kbps 156kbps

Select one of the following supported point modes: 16-point mode 4-point mode –

Specified the Device & Constant

Station No. This item indicates the station number of the built-in CC-Link/LT module. Station numbers 1 to 64 are available. –

Select one of the following station type: Remote I/O station (Input) Remote I/O station (Output) Remote I/O station (Input/Output)

Remote device station*1

I/O Points Select one of the following supported I/O point counts for each remote

I/O and remote device station1 to 16, 32, 48, 64 *2 1 to 16, 32, 48, 64 *2

Specify Reserved Station Select whether or not the Built-in CC-Link/LT station is specified as a reserved station. –

Up This button moves the cursor to the upper line (transposes the upper line). –

Down This button moves the cursor to the lower line (transposes the lower line). –

Insert Row This button inserts a line in the currently selected position. –

Delete Row This button deletes the currently selected line. –

Read Buffer Memory Click this button to read the transmission rate, point mode and station information of the built-in CC-Link/LT module. –

*1. Select 16-point mode when using remote device stations. Remote device stations cannot be set in 4-point mode. Only station numbers 40 to 64 are available for remote device stations.

*2. The station numbers 32, 48 and 64 are available when a remote device station is selected in Station type.

2. Click the [OK] button to finish the setup and close the Built-in CC-Link/LT setup dialog box.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 10 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Transmission Speed · Point Mode · Station Type · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 66 of the Mitsubishi Electronics MELSEC FX3S user manual — 1) FX 3S /FX 3U /FX 3UC PLC
Page 66 · click to enlarge
Page 66

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters

7 Setting the PLC system (1)

Click on the [PLC System(1)] tab to setup "Battery Less Mode", "Battery Mode", "MODEM Initialized", and "RUN Terminal Input".

1) FX 3S /FX 3U /FX 3UC PLC

Mitsubishi Electronics MELSEC FX3S — 1) FX 3S /FX 3U /FX 3UC PLC diagram (page 66)
Fig. 21
2. FX 3G /FX 3GC PLCs
Mitsubishi Electronics MELSEC FX3S — 1) FX 3S /FX 3U /FX 3UC PLC diagram (page 66)
Fig. 22

Set item Contents of setting Setting range

Select this to operate the PLC without using the battery. When a check mark is put here, the battery error indicator lamp is automatically turned off and devices in the latched (battery backed) area are automatically cleared.

Battery Less Mode*1

Battery Mode*2 Select this item to operate the PLC with the battery. –

MODEM Initialized Set this item to automatically initialize a connected modem when the PLC power is turned ON. –

RUN Terminal Input Set this item to use an input terminal (X) to switch the PLC between STOP and RUN.

X000 to X017*3

*1. This area can be set only in FX3U/FX3UC PLCs. *2. This area can be set only in FX3G/FX3GC PLCs. *3. Up to the built-in input number of main unit.

None

Page 67 of the Mitsubishi Electronics MELSEC FX3S user manual — 2.7 Types and Setting of Parameters 1
Page 67 · click to enlarge
Page 67

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters 1

8 Setting the PLC system (2)

1. Click [PLC System(2)] tab.
2. Only when a latch (battery backed) area for a serial port exists through an extended PLC, select a channel to be set and put a check mark next to "Operate Communication Setting". When not performing the communication setting for a serial port, do not put a check mark next to "Operate Communication Setting".
Mitsubishi Electronics MELSEC FX3S — 2.7 Types and Setting of Parameters 1 diagram (page 67)
Fig. 23 · 2.7 Types and Setting of Parameters 1

Specified the Device & Constant

Set item Contents of setting Setting range

Channel selection Select a channel in which a serial port is set. CH1,CH2*1

Check mark this box when using the selected serial port in "computer link", "non- protocol communication" or "inverter communication". Do not put a check mark when transferring and monitoring sequence programs in GX Works2 or when using the selected serial port in N : N Network, parallel link, MODBUS communication or FX3U-ENET-ADP.

Set each item in accordance with application.

→ For details on each item, refer to the Data Communication Edition manual.

Time Out Judge Time

*1. Ch2 is not available in FX3S PLC.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 22 more labels / short text on this page
Introduction · Overview · Channel selection · Instruction List · Devices in Detail · Operate Communication Setting · Before Programming · Protocol · Data length · Parity · Stop Bit · Transmission Speed · Basic Instruction · Header · Terminator · Control Line · H/W Type · Control Mode · Sum Check · FNC00-FNC09 Program Flow · Transmission Control Procedure · Station Number Setting
Page 68 of the Mitsubishi Electronics MELSEC FX3S user manual — 9 Setting positioning
Page 68 · click to enlarge
Page 68

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters

9 Setting positioning

1. Click [Positioning] tab. In order to use the [Positioning] tab, the "Positioning Instruction Settings" box in the [Memory Capacity] tab must be checked first.
2. Set the positioning constants in TBL (FNC152) instruction. → For TBL (FNC152) instruction, refer to the Positioning Control Manual.
Mitsubishi Electronics MELSEC FX3S — 9 Setting positioning diagram (page 68)
Fig. 24 · 9 Setting positioning
Page 69 of the Mitsubishi Electronics MELSEC FX3S user manual — 2.7 Types and Setting of Parameters 1
Page 69 · click to enlarge
Page 69

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters 1

Set item Contents of setting Set range

Bias Speed [Hz] Set the bias speed for each set of output pulses. Initial value: 0

1/10 or less of the maximum speed

Max. Speed [Hz] Set the maximum speed for each set of output pulses. Initial value: 100,000 *1

Creep Speed [Hz] Set the creep speed in DSZR (FNC150) instruction for each set of output pulses. Initial value: 1000 10 to 32767*2

Set the zero point return speed in DSZR (FNC150) instruction for each set of output pulses. Initial value: 50000

Zero Return Speed [Hz]

Acceleration Time [ms] Set the acceleration time for each set of output pulses. Initial value: 100 50 to 5000

Deceleration Time [ms] Set the deceleration time for each set of output pulses. Initial value: 100 50 to 5000

Set the interrupt input*3 for DVIT (FNC151) instruction for each set of output pulses. Specify a user interrupt command device (M) for a pulse output destination device not used in DVIT instruction. Initial setting: Setting range: Pulse output destination Y000: X000 X000 to X007, M8460 Pulse output destination Y001: X001 X000 to X007, M8461 Pulse output destination Y002: X002 X000 to X007, M8462

Interruption Input of DVIT

As shown on the left

Pulse output destination Y003 *6X003 X000 to X007, M8463

Y0 Setting for Fixed pulse output destination terminal Y000. –

Y1 Setting for Fixed pulse output destination terminal Y001. –

Y2*5 Setting for Fixed pulse output destination terminal Y002. –

Y3*6 Setting for Fixed pulse output destination terminal Y003. –

This button displays "Positioning instruction settings" dialog box for setting the table used in TBL (FNC152) instruction.

Specified the Device & Constant

→For the setting procedure, refer to the next page.

*1. The setting range is from 10 to 100,000 Hz in FX3G/FX3GC/FX3U/FX3UC PLCs. The setting range is from 10 to 200,000 Hz in FX3U PLC when the pulse output destination is the high-speed output special adapter.

*2. The creep speed should satisfy the relationship "Bias speed ≤ Creep speed ≤ Maximum speed".

*3. An interrupt input set here cannot be used jointly with a high-speed counter, input interrupt, pulse catch input, input in SPD (FNC 67) instruction, or interrupt input in DVIT (FNC151) instruction.

*4. This area can be set only in FX3U/FX3UC PLCs.

*5. Y002 is not set in FX3G PLC (14-point and 24-point type) and FX3GC PLC.

*6. Note that this item can only be set if two high-speed output special adapters are connected to the FX3U PLC.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 10 more labels / short text on this page
Introduction · Overview · *1 · Instruction List · Instruction*4 · Devices in Detail · Individual Setting · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 70 of the Mitsubishi Electronics MELSEC FX3S user manual — FX 3G /FX 3GC :
Page 70 · click to enlarge
Page 70

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters

3. Click [Individual setting] button to display Positioning Instruction Settings dialog box. In this dialog box, set the positioning table for each pulse output destination.
Mitsubishi Electronics MELSEC FX3S — 2.7.6 Special unit initial value setting diagram (page 70)
Fig. 25 · 2.7.6 Special unit initial value setting

Set item Contents of setting Setting range

Y0 Set the positioning table for the pulse output destination Y000. –

Y1 Set the positioning table for the pulse output destination Y001. –

Y2*1 Set the positioning table for the pulse output destination Y002. –

Y3*2 Set the positioning table for the pulse output destination Y003. –

Set the relay number of the rotation direction output signal. Initial setting: Pulse output destination Y000: Y010 Pulse output destination Y001: Y011

FX 3U /FX 3UC :

Pulse output destination Y002 *1Y012
Pulse output destination Y003 *2Y013

FX 3G /FX 3GC :

→Refer to the Positioning Control Manual.

Set the head number of devices storing the set data (pulse number and frequency). 1600 devices (FX3U and FX3UC) or 1200 devices (FX3G and FX3GC) are occupied starting from the head device number set here regardless of the number of axes. Initial setting: R0

FX 3U /FX 3UC :

D0 to D6400 R0 to R31168

FX 3G /FX 3GC :

D0 to D6400 R0 to R22800

→Refer to the Positioning Control Manual.

No. This column shows the table number. Numbers 1 to 100 can be set. –

Select the positioning type among the following:

DDVIT (Interrupt positioning instruction)*3

DPLSV (Variable speed output pulse instruction) DDRVI (Relative positioning instruction) DDRVA (Absolute positioning instruction)

→Refer to the Positioning Control Manual.

Set the pulse number output by the operation (instruction) set in "Positioning Instruction" column.

Refer to the Positioning Control

→Refer to the Positioning Control Manual.

Manual.

Set the speed (pulse frequency) output by the operation (instruction) set in "Positioning Instruction" column.

Refer to the Positioning Control

→Refer to the Positioning Control Manual.

Manual.

Up This button transposes the selected line to the upper line. –

Down This button transposes the selected line to the lower line. –

Insert Row This button inserts a line in the currently selected position. –

Delete Row This button deletes the currently selected line. –

Delete all Rows This button deletes the entire setting of the positioning table for the selected pulse output destination. –

Show 7 more labels / short text on this page
Y000 to Y357 · Rotation Direction Signal · Y000 to Y177 · Head Address · Positioning Instruction · Pulse (Pls) · Frequency [Hz]
Page 71 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 71 · click to enlarge
Page 71

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

2 Overview (Sequence Program)

2.7 Types and Setting of Parameters 1

Set item Contents of setting Setting range

A check mark here means not to transfer the positioning setting when PLC turns ON. Check mark this box when changing the positioning setting from a display unit, etc., and then using the changed contents even after restoring power. In this case, set a latched (battery backed) type device to "Head Address".

Positioning table settings will not be initialized when the PLC is powered on

This button writes the contents of the positioning table created here to up to 1600 devices (FX3U and FX3UC) or 1200 devices (FX3G and FX3GC) starting from "Head Address".

This button reads the contents of the existing positioning table from all pulse output destinations, up to 1600 devices (FX3U and FX3UC) or 1200 devices (FX3G and FX3GC) starting from "Head Address", but does not read device numbers without the "positioning instruction" setting.

*1. Y002 is not set in FX3G PLC (14-point and 24-point type) and FX3GC PLC.

*2. Note that this item can only be set if two high-speed output special adapters are connected to the FX3U PLC.

*3. This area can be set only in FX3U/FX3UC PLCs. 10 Transferring parameters (and sequence program) to the PLC

1. Select [Online] → [Write to PLC...] from the menu bar to display the online data operation dialog box.
Mitsubishi Electronics MELSEC FX3S — 2.7 Types and Setting of Parameters 1 diagram (page 71)
Fig. 26 · 2.7 Types and Setting of Parameters 1

Specified the Device & Constant

2. Check mark the "Parameter" box, and click [Execute] button. The selected contents are transferred to the PLC. The transferred parameters become valid when the PLC switches from RUN to STOP. When the communication setting is changed in step 8 [PLC System(2)], cycle the PLC power.

Caution

After changing the memory capacity, make sure to write both the programs and parameters to the PLC. If only the parameters are written to the PLC, program errors (such as parameter error, circuit error and grammar error) may occur in the PLC.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 9 more labels / short text on this page
Introduction · Write · Overview · Read · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 72 of the Mitsubishi Electronics MELSEC FX3S user manual — 3.1 Basic Instructions
Page 72 · click to enlarge
Page 72

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

3.1 Basic Instructions

3. Instruction List

This chapter introduces a list of instructions available in programming.

3.1 Basic Instructions

The basic instructions are provided in the following series. The table below shows differences in applicable devices.

Mitsubishi Electronics MELSEC FX3S — 3.1 Basic Instructions diagram (page 72)
Fig. 27 · 3.1 Basic Instructions

Applicable PLC FX3S FX3G FX3GC FX3U FX3UC FX1S FX1N FX1NC FX2N FX2NC

Basic instructions other than MEP and MEF instructions 3

MEP and MEF instructions 3 3 3 Ver. 2.30

Absence/presence of applicable devices (D . b) – – – 3 3 –

Absence/presence of applicable devices (R) – 3 –

Mnemonic Name Symbol Function Applicable devices Reference

Initial logical operation contact type NO (normally open)

X,Y,M,S,D .b,T,C Section 7.1

Initial logical operation contact type NC (normally closed)

X,Y,M,S,D .b,T,C Section 7.1

LDP Load Pulse Initial logical operation of Rising edge pulse X,Y,M,S,D .b,T,C Section 7.5

LDF Load Falling Pulse Initial logical operation of Falling/trailing edge pulse X,Y,M,S,D .b,T,C Section 7.5

AND AND Serial connection of NO (normally open) contacts X,Y,M,S,D .b,T,C Section 7.3

ANI AND Inverse Serial connection of NC (normally closed) contacts X,Y,M,S,D .b,T,C Section 7.3

ANDP AND Pulse Serial connection of Rising edge pulse X,Y,M,S,D .b,T,C Section 7.5

ANDF AND Falling Pulse Serial connection of Falling/trailing edge pulse X,Y,M,S,D .b,T,C Section 7.5

OR OR Parallel connection of NO (normally open) contacts X,Y,M,S,D .b,T,C Section 7.4

ORI OR Inverse Parallel connection of NC (normally closed) contacts X,Y,M,S,D .b,T,C Section 7.4

ORP OR Pulse Parallel connection of Rising edge pulse X,Y,M,S,D .b,T,C Section 7.5

ORF OR Falling Pulse Parallel connection of Falling/trailing edge pulse X,Y,M,S,D .b,T,C Section 7.5

Show 16 more labels / short text on this page
3 Instruction List · Contact Instruction · Applicable devices · LD Load · Applicable devices · LDI Load Inverse · Applicable devices · Applicable devices · Applicable devices · Applicable devices · Applicable devices · Applicable devices · Applicable devices · Applicable devices · Applicable devices · Applicable devices
Page 73 of the Mitsubishi Electronics MELSEC FX3S user manual — END
Page 73 · click to enlarge
Page 73

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

3.1 Basic Instructions 1

Mnemonic Name Symbol Function Applicable devices Reference

ANB AND Block Serial connection of multiple parallel circuits – Section 7.7

ORB OR Block Parallel connection of multiple contact circuits – Section 7.6

Stores the current result of the internal PLC operations

MPS Memory Point Store

Section 7.8

MPS

Reads the current result of the internal PLC operations

MRD

Section 7.8

Pops (recalls and removes) the currently stored result

MPP

Section 7.8

INV

Invert the current result of the internal PLC operations

– Section 7.10

Conversion of operation result to leading edge pulse

MEP MEP

– Section 7.11

MEF MEF Conversion of operation result to trailing edge pulse – Section 7.11

Specified the Device & Constant

OUT OUT Final logical operation type coil drive Y,M,S,D .b,T,C Section 7.2

SET SET SET Bit device latch ON Y,M,S,D .b Section 7.13

RST Reset RESET Bit device OFF Y,M,S,D .b,T,C, D,R,V,Z Section 7.13

PLS Pulse Rising edge pulse Y,M Section 7.12

PLF Pulse Falling Falling/trailing edge pulse Y,M Section 7.12

MC Master Control Denotes the start of a master control block Y,M Section 7.9

Applicable devices MC N

MCR Master Control Reset

Denotes the end of a master control block – Section 7.9

MCR N

NOP No Operation No operation or null step – Section 7.14

END END Program END, I/O refresh and Return to Step 0 – Section 7.15

FNC10-FNC19 Move & Compare

END

FNC20-FNC29 Arith. & Logic Operation

Show 21 more labels / short text on this page
3 Instruction List · Introduction · Connection Instruction · Overview · MRD Memory Read · Instruction List · MPP Memory POP · INV Inverse · Devices in Detail · Out Instruction · Applicable devices · SET Applicable devices · Before Programming · RST Applicable devices · PLS Applicable devices · Basic Instruction · PLF Applicable devices · Master Control Instruction · FNC00-FNC09 Program Flow · Other Instruction · End Instruction
Page 74 of the Mitsubishi Electronics MELSEC FX3S user manual — D S MOV
Page 74 · click to enlarge
Page 74

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

3.2 Step Ladder Instructions

3.2 Step Ladder Instructions

Mitsubishi Electronics MELSEC FX3S — 3.2 Step Ladder Instructions diagram (page 74)
Fig. 28 · 3.2 Step Ladder Instructions

STL Step Ladder Starts step ladder S Chapter 35

3.3 Applied Instructions ... in Ascending Order of FNC Number

Applied instructions such as Arithmetic operation, Rotation and Shift, Handy instructions etc. are used especially when numeric data is handled. *1: The instruction is provided in the FX2N/FX2NC Series Ver. 3.00 or later. *7: The instruction is provided in the FX3U/FX3UC Series Ver. 2.61 or later. *2: The function is changed in the FX3UC Series Ver. 1.30 or later. *8: The instruction is provided in the FX3G Series Ver. 1.40 or later. *3: The instruction is provided in the FX3UC Series Ver. 1.30 or later. *9: The instruction is provided in the FX3U/FX3UC Series Ver. 2.70 or later. *4: The function is changed in the FX3UC Series Ver. 2.20 or later. *10: The instruction is provided in the FX3G Series Ver. 1.30 or later. *5: The instruction is provided in the FX3UC Series Ver. 2.20 or later *11: The instruction is provided in the FX3U/FX3UC Series Ver. 2.40 or later. *6: The instruction is provided in the FX3G Series Ver. 1.10 or later..

FX 3GC

No. Mnemonic Symbol Function

FX 3S

FX 3G

FX 3U

FX 3UC

FX 1S

FX 1N

FX 1NC

FX 2N

FX 2NC

00 CJ Conditional Jump 3 Section 8.1

01 CALL Call Subroutine 3 Section 8.2

02 SRET Subroutine Return 3 Section 8.3

SRET

03 IRET Interrupt Return 3 Section 8.4

IRET

04 EI Enable Interrupt 3 Section 8.5

EI

05 DI Disable Interrupt 3 Section 8.6

DI

06 FEND Main Routine Program End 3 Section 8.7

FEND

07 WDT Watchdog Timer Refresh 3 Section 8.8

WDT

08 FOR Start a FOR/NEXT Loop 3 Section 8.9

FOR S

09 NEXT End a FOR/NEXT Loop 3 Section

NEXT

10 CMP Compare 3 Section 9.1

CMP S1 S2 D

11 ZCP Zone Compare 3 Section 9.2

ZCP S2 S D S1

12 MOV Move 3 Section 9.3

D S MOV

Show 7 more labels / short text on this page
3 Instruction List · Applicable PLC · Reference · Program Flow · Pn CJ · Pn CALL · Move and Compare
Page 75 of the Mitsubishi Electronics MELSEC FX3S user manual — D NEG
Page 75 · click to enlarge
Page 75

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

3.3 Applied Instructions ... in Ascending Order of FNC Number 1

FX 3GC

FX 3UC

No. Mnemonic Symbol Function

FX 3S

FX 3G

FX 3U

FX 1NC

FX 2NC

FX 1S

FX 1N

FX 2N

13 SMOV Shift Move 3 – – – 3 3 Section 9.4

SMOV S D n m1 m2

14 CML Complement 3 – – – 3 3 Section 9.5

D S CML

15 BMOV Block Move 3 Section 9.6

n BMOV S D

16 FMOV Fill Move 3 – – – 3 3 Section 9.7

n FMOV S D

17 XCH Exchange – – – 3 3 – – – 3 3 Section 9.8

D2 D1 XCH

18 BCD Conversion to Binary Coded Decimal 3 Section 9.9

D S BCD

19 BIN Conversion to Binary 3 Section

D S BIN

Arithmetic and Logical Operation (+, –, ×, ÷)

20 ADD Addition 3 Section

ADD S2 D S1

Specified the Device & Constant

21 SUB Subtraction 3 Section

SUB S2 D S1

22 MUL Multiplication 3 Section

MUL S2 D S1

23 DIV Division 3 Section

DIV S2 D S1

24 INC Increment 3 Section

D INC

25 DEC Decrement 3 Section

D DEC

26 WAND Logical Word AND 3 Section

D WAND S2 S1

27 WOR Logical Word OR 3 Section

D WOR S2 S1

28 WXOR Logical Exclusive OR 3 Section

D WXOR S2 S1

29 NEG Negation – – – 3 3 – – – 3 3 Section

D NEG

Rotation and Shift Operation

30 ROR Rotation Right 3 – – – 3 3 Section

FNC10-FNC19 Move & Compare

31 ROL Rotation Left 3 – – – 3 3 Section

32 RCR Rotation Right with Carry – – – 3 3 – – – 3 3 Section

33 RCL Rotation Left with Carry – – – 3 3 – – – 3 3 Section

FNC20-FNC29 Arith. & Logic Operation

Show 15 more labels / short text on this page
3 Instruction List · Applicable PLC · Introduction · Reference · Move and Compare · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow · n D ROR · n D ROL · n D RCR · n D RCL
Page 76 of the Mitsubishi Electronics MELSEC FX3S user manual — HSCR S2 D S1
Page 76 · click to enlarge
Page 76

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

3.3 Applied Instructions ... in Ascending Order of FNC Number

FX 3GC

FX 3UC

No. Mnemonic Symbol Function

FX 3S

FX 3G

FX 3U

FX 1NC

FX 2NC

FX 1S

FX 1N

FX 2N

Rotation and Shift Operation

34 SFTR Bit Shift Right 3 Section

n2 n1 D S SFTR

35 SFTL Bit Shift Left 3 Section

n2 n1 D S SFTL

36 WSFR Word Shift Right 3 – – – 3 3 Section

n2 n1 D S WSFR

37 WSFL Word Shift Left 3 – – – 3 3 Section

n2 n1 D S WSFL

38 SFWR Shift write [FIFO/FILO control] 3 Section

n SFWR D S

39 SFRD Shift Read [FIFO Control] 3 Section

n SFRD D S

40 ZRST Zone Reset 3 Section

D2 D1 ZRST

41 DECO Decode 3 Section

n DECO D S

42 ENCO Encode 3 Section

n ENCO D S

43 SUM Sum of Active Bits 3 – – – 3 3 Section

D S SUM

44 BON Check Specified Bit Status 3 – – – 3 3 Section

BON D n S

45 MEAN Mean 3 – – – 3 3 Section

MEAN D n S

46 ANS Timed Annunciator Set – 3 – – – 3 3 Section

ANS m D S

47 ANR Annunciator Reset – 3 – – – 3 3 Section

ANR

48 SQR Square Root – – – 3 3 – – – 3 3 Section

D S SQR

49 FLT Conversion to Floating Point 3 *6 3 3 3 – – – 3 3 Section

D S FLT

50 REF Refresh 3 Section

51 REFF Refresh and Filter Adjust – – – 3 3 – – – 3 3 Section

52 MTR Input Matrix 3 Section

n MTR D2 D1 S

53 HSCS High-speed Counter Set 3 Section

HSCS S2 D S1

54 HSCR High-speed Counter Reset 3 Section

HSCR S2 D S1

Show 7 more labels / short text on this page
3 Instruction List · Applicable PLC · Reference · Data Operation · High-speed Processing · n D REF · n REFF
Page 77 of the Mitsubishi Electronics MELSEC FX3S user manual — D S SEGD
Page 77 · click to enlarge
Page 77

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

3.3 Applied Instructions ... in Ascending Order of FNC Number 1

FX 3GC

FX 3UC

No. Mnemonic Symbol Function

FX 3S

FX 3G

FX 3U

FX 1NC

FX 2NC

FX 1S

FX 1N

FX 2N

55 HSZ High-speed Counter Zone Compare 3 – – – 3 3 Section

D HSZ S S2 S1

56 SPD Speed Detection 3 Section

SPD S2 D S1

57 PLSY Pulse Y Output 3 Section

PLSY S2 D S1

58 PWM Pulse Width Modulation 3 Section

PWM S2 D S1

59 PLSR Acceleration/Deceleration Setup 3 Section

D PLSR S3 S2 S1

60 IST Initial State 3 Section

IST D1 D2 S

61 SER Search a Data Stack 3 – – – 3 3 Section

n SER D S2 S1

62 ABSD Absolute Drum Sequencer 3 Section

n ABSD D S2 S1

Specified the Device & Constant

63 INCD Incremental Drum Sequencer 3 Section

n INCD D S2 S1

64 TTMR Teaching Timer – – – 3 3 – – – 3 3 Section

65 STMR Special Timer – – – 3 3 – – – 3 3 Section

STMR m D S

66 ALT Alternate State 3 Section

D ALT

67 RAMP Ramp Variable Value 3 Section

n RAMP D S2 S1

68 ROTC Rotary Table Control – – – 3 3 – – – 3 3 Section

D ROTC m2 m1 S

69 SORT SORT Tabulated Data – – – 3 3 – – – 3 3 Section

n SORT D m2 m1 S

External FX I/O Device

70 TKY Ten Key Input – – – 3 3 – – – 3 3 Section

TKY D1 D2 S

71 HKY Hexadecimal Input – – – 3 3 – – – 3 3 Section

D3 HKY D2 D1 S

72 DSW Digital Switch (Thumbwheel Input) 3 Section

n DSW D2 D1 S

FNC10-FNC19 Move & Compare

73 SEGD Seven Segment Decoder – – – 3 3 – – – 3 3 Section

D S SEGD

74 SEGL Seven Segment With Latch 3 Section

SEGL D n S

FNC20-FNC29 Arith. & Logic Operation

Show 13 more labels / short text on this page
3 Instruction List · Applicable PLC · Introduction · Reference · High-speed Processing · Overview · Instruction List · Handy Instruction · Devices in Detail · n D TTMR · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 78 of the Mitsubishi Electronics MELSEC FX3S user manual — D S EVAL
Page 78 · click to enlarge
Page 78

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

3.3 Applied Instructions ... in Ascending Order of FNC Number

FX 3GC

FX 3UC

No. Mnemonic Symbol Function

FX 3S

FX 3G

FX 3U

FX 1NC

FX 2NC

FX 1S

FX 1N

FX 2N

75 ARWS Arrow Switch – – – 3 3 – – – 3 3 Section

n ARWS D2 D1 S

76 ASC ASCII Code Data Input – – – 3 3 – – – 3 3 Section

D ASC S

77 PR Print (ASCII Code) – – – 3 3 – – – 3 3 Section

D S PR

78 FROM Read From A Special Function Block – 3 – 3 Section

n FROM D m2 m1

79 TO Write To A Special Function Block – 3 – 3 Section

n TO S m2 m1

80 RS Serial Communication 3 Section

n RS D m S

81 PRUN Parallel Run (Octal Mode) 3 Section

D S PRUN

82 ASCI Hexadecimal to ASCII Conversion 3 Section

ASCI D n S

83 HEX ASCII to Hexadecimal Conversion 3 Section

HEX D n S

84 CCD Check Code 3 Section

CCD D n S

85 VRRD Volume Read 3 *6 – *9 *9 3 3 – 3 – Section

D S VRRD

86 VRSC Volume Scale 3 *6 – *9 *9 3 3 – 3 – Section

D S VRSC

87 RS2 Serial Communication 2 3 – Section

n1 RS2 n D m S

88 PID PID Control Loop 3 Section

D PID S3 S2 S1

102 ZPUSH Batch Store of Index Register – – – 3 *5 – Section

ZPUSH D

103 ZPOP Batch POP of Index Register – – – 3 *5 – Section

ZPOP D

110 ECMP Floating Point Compare 3 *6 3 3 3 – – – 3 3 Section

ECMP S2 D S1

111 EZCP Floating Point Zone Compare – – – 3 3 – – – 3 3 Section

D EZCP S S2 S1

112 EMOV Floating Point Move 3 *6 3 3 3 – Section

D S EMOV

116 ESTR Floating Point to Character String Conversion – – – 3 3 – Section

ESTR S2 D S1

117 EVAL Character String to Floating Point Conversion – – – 3 3 – Section

D S EVAL

Show 6 more labels / short text on this page
3 Instruction List · Applicable PLC · Reference · External FX Device · Data Transfer 2 · Floating Point
Page 79 of the Mitsubishi Electronics MELSEC FX3S user manual — D S DEG
Page 79 · click to enlarge
Page 79

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

3.3 Applied Instructions ... in Ascending Order of FNC Number 1

FX 3GC

FX 3UC

No. Mnemonic Symbol Function

FX 3S

FX 3G

FX 3U

FX 1NC

FX 2NC

FX 1S

FX 1N

FX 2N

118 EBCD Floating Point to Scientific Notation Conversion – – – 3 3 – – – 3 3 Section

D S EBCD

119 EBIN Scientific Notation to Floating Point Conversion – – – 3 3 – – – 3 3 Section

D S EBIN

120 EADD Floating Point Addition 3 *6 3 3 3 – – – 3 3 Section

D S2 EADD S1

121 ESUB Floating Point Subtraction 3 *6 3 3 3 – – – 3 3 Section

D S2 ESUB S1

122 EMUL Floating Point Multiplication 3 *6 3 3 3 – – – 3 3 Section

D S2 EMUL S1

123 EDIV Floating Point Division 3 *6 3 3 3 – – – 3 3 Section

D S2 EDIV S1

124 EXP Floating Point Exponent – – – 3 3 – Section

D S EXP

125 LOGE Floating Point Natural Logarithm – – – 3 3 – Section

D S LOGE

126 LOG10 Floating Point Common Logarithm – – – 3 3 – Section

D S LOG10

Specified the Device & Constant

127 ESQR Floating Point Square Root 3 *6 3 3 3 – – – 3 3 Section

D S ESQR

128 ENEG Floating Point Negation – – – 3 3 – Section

D ENEG

129 INT Floating Point to Integer Conversion 3 *6 3 3 3 – – – 3 3 Section

D S INT

130 SIN Floating Point Sine – – – 3 3 – – – 3 3 Section

D S SIN

131 COS Floating Point Cosine – – – 3 3 – – – 3 3 Section

D S COS

132 TAN Floating Point Tangent – – – 3 3 – – – 3 3 Section

D S TAN

133 ASIN Floating Point Arc Sine – – – 3 3 – Section

D S ASIN

134 ACOS Floating Point Arc Cosine – – – 3 3 – Section

D S ACOS

135 ATAN Floating Point Arc Tangent – – – 3 3 – Section

D S ATAN

136 RAD Floating Point Degrees to Radians Conversion – – – 3 3 – Section

D S RAD

FNC10-FNC19 Move & Compare

137 DEG Floating Point Radians to Degrees Conversion – – – 3 3 – Section

D S DEG

140 WSUM Sum of Word Data – – – 3 *5 – Section

WSUM n D S

FNC20-FNC29 Arith. & Logic Operation

141 WTOB WORD to BYTE – – – 3 *5 – Section

WTOB n D S

Show 12 more labels / short text on this page
3 Instruction List · Applicable PLC · Introduction · Reference · Floating Point · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow · Data Operation 2
Page 80 of the Mitsubishi Electronics MELSEC FX3S user manual — D2 HOUR D1 S
Page 80 · click to enlarge
Page 80

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

3.3 Applied Instructions ... in Ascending Order of FNC Number

FX 3GC

FX 3UC

No. Mnemonic Symbol Function

FX 3S

FX 3G

FX 3U

FX 1NC

FX 2NC

FX 1S

FX 1N

FX 2N

142 BTOW BYTE to WORD – – – 3 *5 – Section

BTOW n D S

143 UNI 4-bit Linking of Word Data – – – 3 *5 – Section

UNI n D S

144 DIS 4-bit Grouping of Word Data – – – 3 *5 – Section

DIS n D S

147 SWAP Byte Swap – – – 3 3 – – – 3 3 Section

S SWAP

149 SORT2 Sort Tabulated Data 2 – – – 3 *5 – Section

SORT2 n m2 m1 S D

150 DSZR DOG Search Zero Return 3 *4 – Section

D2 DSZR D1 S2 S1

151 DVIT Interrupt Positioning – – – 3 *2, 4 – Section

D2 DVIT D1 S2 S1

152 TBL Batch Data Positioning Mode – 3 3 3 *5 – Section

155 ABS Absolute Current Value Read 3 *1 *1 Section

D2 D1 ABS S

156 ZRN Zero Return 3 *4 3 3 3 – – Section

D S3 ZRN S2 S1

157 PLSV Variable Speed Pulse Output 3 – – Section

PLSV D1 D2 S

158 DRVI Drive to Increment 3 – – Section

DRVI D1 D2 S2 S1

159 DRVA Drive to Absolute 3 – – Section

DRVA D1 D2 S2 S1

Real Time Clock Control

160 TCMP RTC Data Compare 3 Section

TCMP S D S3 S2 S1

161 TZCP RTC Data Zone Compare 3 Section

TZCP S D S2 S1

162 TADD RTC Data Addition 3 Section

D TADD S2 S1

163 TSUB RTC Data Subtraction 3 Section

D TSUB S2 S1

164 HTOS Hour to Second Conversion – – – 3 3 – Section

D S HTOS

165 STOH Second to Hour Conversion – – – 3 3 – Section

D S STOH

166 TRD Read RTC data 3 Section

D TRD

167 TWR Set RTC data 3 Section

S TWR

169 HOUR Hour Meter 3 *1 *1 Section

D2 HOUR D1 S

Show 6 more labels / short text on this page
3 Instruction List · Applicable PLC · Reference · Data Operation 2 · Positioning Control · n TBL D
Page 81 of the Mitsubishi Electronics MELSEC FX3S user manual — VAL D1 D2 S
Page 81 · click to enlarge
Page 81

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

3.3 Applied Instructions ... in Ascending Order of FNC Number 1

FX 3GC

FX 3UC

No. Mnemonic Symbol Function

FX 3S

FX 3G

FX 3U

FX 1NC

FX 2NC

FX 1S

FX 1N

FX 2N

170 GRY Decimal to Gray Code Conversion 3 – – – 3 3 Section

D S GRY

171 GBIN Gray Code to Decimal Conversion 3 – – – 3 3 Section

D S GBIN

176 RD3A Read form Dedicated Analog Block – 3 – 3 3 *1 *1 Section

D RD3A m2 m1

177 WR3A Write to Dedicated Analog Block – 3 – 3 3 *1 *1 Section

S WR3A m2 m1

180 EXTR External ROM Function (FX2N/FX2NC) – *1 *1 –

SD3 EXTR SD2 SD1 S

182 COMRD Read Device Comment Data – – – 3 *5 – Section

COMRD D S

184 RND Random Number Generation – – – 3 3 – Section

RND D

186 DUTY Timing Pulse Generation – – – 3 *5 – Section

DUTY D n2 n1

Specified the Device & Constant

188 CRC Cyclic Redundancy Check – – – 3 3 – Section

n CRC D S

189 HCMOV High-speed Counter Move – – – 3 *4 – Section

n HCMOV D S

192 BK+ Block Data Addition – – – 3 *5 – Section

n D S2 S1 BK+

193 BK- Block Data Subtraction – – – 3 *5 – Section

n D S2 S1 BK-

– – – 3 *5 – Section

194 BKCMP=

n D S2 S1 BKCMP= S1 S2

– – – 3 *5 – Section

195 BKCMP>

n D S2 S1 BKCMP> S1 S2

– – – 3 *5 – Section

196 BKCMP<

n D S2 S1 BKCMP< S1 S2

– – – 3 *5 – Section

197 BKCMP<>

n D S2 S1 BKCMP S1 S2

– – – 3 *5 – Section

198 BKCMP<=

n D S2 S1 BKCMP

– – – 3 *5 – Section

199 BKCMP>=

n D S2 S1 BKCMP>= S1 S2

FNC10-FNC19 Move & Compare

200 STR BIN to Character String Conversion – – – 3 *5 – Section

STR S2 D S1

201 VAL Character String to BIN Conversion – – – 3 *5 – Section

VAL D1 D2 S

FNC20-FNC29 Arith. & Logic Operation

Show 27 more labels / short text on this page
3 Instruction List · Applicable PLC · Introduction · Reference · External Device · Overview · Instruction List · Extension Function · Others · Devices in Detail · Block Data Operation · Before Programming · Block Data Compare · Basic Instruction · = · Block Data Compare · > · Block Data Compare · < · FNC00-FNC09 Program Flow · Block Data Compare · ≠ · Block Data Compare · ≤ · Block Data Compare · ≥ · Character String Control
Page 82 of the Mitsubishi Electronics MELSEC FX3S user manual — 233 AND>
Page 82 · click to enlarge
Page 82

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

3.3 Applied Instructions ... in Ascending Order of FNC Number

FX 3GC

FX 3UC

No. Mnemonic Symbol Function

FX 3S

FX 3G

FX 3U

FX 1NC

FX 2NC

FX 1S

FX 1N

FX 2N

202 $+ Link Character Strings – – – 3 3 – Section

D $+ S2 S1

203 LEN Character String Length Detection – – – 3 3 – Section

D S LEN

204 RIGHT Extracting Character String Data from the Right – – – 3 3 – Section

n RIGHT D S

205 LEFT Extracting Character String Data from the Left – – – 3 3 – Section

n LEFT D S

206 MIDR Random Selection of Character Strings – – – 3 3 – Section

S2 MIDR D S1

207 MIDW Random Replacement of Character Strings – – – 3 3 – Section

S2 MIDW D S1

208 INSTR Character string search – – – 3 *5 – Section

INSTR S2 n S1 D

209 $MOV Character String Transfer – – – 3 3 – Section

D S $MOV

210 FDEL Deleting Data from Tables – – – 3 *5 – Section

FDEL D n S

211 FINS Inserting Data to Tables – – – 3 *5 – Section

FINS D n S

212 POP Shift Last Data Read [FILO Control] – – – 3 3 – Section

n POP D S

213 SFR Bit Shift Right with Carry – – – 3 3 – Section

214 SFL Bit Shift Left with Carry – – – 3 3 – Section

224 LD=

3 Section

S2 S1 LD= S 1 S 2

225 LD>

3 Section

S2 S1 LD> S 1 S 2

3 Section

226 LD<

S2 S1 LD< S 1 S 2

3 Section

228 LD<>

S2 S1 LD<> S 1 S 2

3 Section

229 LD<=

S2 S1 LD <= S 1 S 2

3 Section

230 LD>=

S2 S1 LD >= S 1 S 2

3 Section

232 AND=

AND= S2 S1 S 1 S 2

3 Section

233 AND>

AND> S2 S1 S 1 S 2

Show 24 more labels / short text on this page
3 Instruction List · Applicable PLC · Reference · Character String Control · Data Operation 3 · n D SFR · n D SFL · Data Comparison · Load Compare · = · Load Compare · > · Load Compare · < · Load Compare · ≠ · Load Compare · ≤ · Load Compare · ≥ · AND Compare · = · AND Compare · >
Page 83 of the Mitsubishi Electronics MELSEC FX3S user manual — D SCL2 S2 S1
Page 83 · click to enlarge
Page 83

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

3.3 Applied Instructions ... in Ascending Order of FNC Number 1

FX 3GC

FX 3UC

No. Mnemonic Symbol Function

FX 3S

FX 3G

FX 3U

FX 1NC

FX 2NC

FX 1S

FX 1N

FX 2N

3 Section

234 AND<

AND< S2 S1 S 1 S 2

3 Section

236 AND<>

AND<> S2 S1 S 1 S 2

3 Section

237 AND<=

AND <= S2 S1 S 1 S 2

3 Section

238 AND>=

AND >= S2 S1 S 1 S 2

3 Section

240 OR=

S2 S1 OR= S 1 S 2

3 Section

241 OR>

S2 S1 OR> S 1 S 2

3 Section

242 OR<

S2 S1 OR< S 1 S 2

Specified the Device & Constant

244 OR<>

3 Section

S2 S1 OR<> S 1 S 2

245 OR<=

3 Section

S2 S1 OR <= S 1 S 2

246 OR>=

3 Section

S2 S1 OR >= S 1 S 2

256 LIMIT Limit Control – – – 3 3 – Section

D LIMIT S3 S2 S1

257 BAND Dead Band Control – – – 3 3 – Section

D BAND S3 S2 S1

258 ZONE Zone Control – – – 3 3 – Section

D ZONE S3 S2 S1

259 SCL Scaling (Coordinate by Point Data) – – – 3 3 – Section

D SCL S2 S1

260 DABIN Decimal ASCII to BIN Conversion – – – 3 *5 – Section

DABIN D S

261 BINDA BIN to Decimal ASCII Conversion – – – 3 *5 – Section

BINDA D S

FNC10-FNC19 Move & Compare

269 SCL2 Scaling 2 (Coordinate by X/Y Data) – – – 3 *3 – Section

D SCL2 S2 S1

270 IVCK Inverter Status Check 3 *6 3 3 3 – Section

n IVCK D S2 S1

FNC20-FNC29 Arith. & Logic Operation

Show 33 more labels / short text on this page
3 Instruction List · Applicable PLC · Introduction · Reference · Data Comparison · AND Compare · < · Overview · AND Compare · ≠ · AND Compare · ≤ · AND Compare · Instruction List · ≥ · OR Compare · = · OR Compare · Devices in Detail · > · OR Compare · < · OR Compare · ≠ · OR Compare · ≤ · Before Programming · OR Compare · ≥ · Data Table Operation · Basic Instruction · FNC00-FNC09 Program Flow · External Device Communication
Page 84 of the Mitsubishi Electronics MELSEC FX3S user manual — ADPRW S S1 S2 S3 S4/D
Page 84 · click to enlarge
Page 84

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

3.3 Applied Instructions ... in Ascending Order of FNC Number

FX 3GC

FX 3UC

No. Mnemonic Symbol Function

FX 3S

FX 3G

FX 3U

FX 1NC

FX 2NC

FX 1S

FX 1N

FX 2N

271 IVDR Inverter Drive 3 *6 3 3 3 – Section

n IVDR S3 S2 S1

272 IVRD Inverter Parameter Read 3 *6 3 3 3 – Section

n IVRD D S2 S1

273 IVWR Inverter Parameter Write 3 *6 3 3 3 – Section

n IVWR S3 S2 S1

274 IVBWR Inverter Parameter Block Write – – – 3 3 – Section

n IVBWR S3 S2 S1

275 IVMC Inverter Multi Command 3 *8 3 *9 *9 – Section

n IVMC D S3 S2 S1

276 ADPRW MODBUS Read / Write 3 * 10 3 * 11 * 11 – Section

ADPRW S S1 S2 S3 S4/D

278 RBFM Divided BFM Read – – – 3 *5 – Section

RBFM n1 n2 D m2 m1

279 WBFM Divided BFM Write – – – 3 *5 – Section

WBFM n1 n2 S m2 m1

280 HSCT High-speed Counter Compare With Data Table – – – 3 3 – Section

n HSCT D S2 m S1

Extension File Register Control

290 LOADR Load From ER – 3 – Section

291 SAVER Save to ER – – – 3 3 – Section

D SAVER m S

292 INITR Initialize R and ER – – – 3 3 – Section

293 LOGR Logging R and ER – – – 3 3 – Section

D2 LOGR n D1 m S

294 RWER Rewrite to ER – 3 3 3 *3 – Section

295 INITER Initialize ER – – – 3 *3 – Section

FX3U-CF-ADP Applied Instructions

300 FLCRT File create / check – – – *7 *7 – Section

n FLCRT S3 S2 S1

301 FLDEL File delete / CF card format – – – *7 *7 – Section

n FLDEL S2 S1

302 FLWR Data write – – – *7 *7 – Section

n FLWR D S3 S2 S1

303 FLRD Data read – – – *7 *7 – Section

n FLRD D2 D1 S2 S1

304 FLCMD FX3U-CF-ADP command – – – *7 *7 – Section

305 FLSTRD FX3U-CF-ADP status read – – – *7 *7 – Section

n FLSTRD D S

Show 11 more labels / short text on this page
3 Instruction List · Applicable PLC · Reference · External Device Communication · Data Transfer 3 · High-speed Processing 2 · n S LOADR · n S INITR · n RWER S · n S INITER · n S FLCMD
Page 85 of the Mitsubishi Electronics MELSEC FX3S user manual — 1) FX 3S PLC
Page 85 · click to enlarge
Page 85

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.1 Device Number List 1

4. Devices in Detail

This chapter explains how numeric values are handled in the PLC as well as the roles and functions of various built-in devices including I/O relays, auxiliary relays, state relays, counters and data registers. The following content provides a basis for handling the PLC.

4.1 Device Number List

Device numbers are assigned as shown below. For input relay numbers and output relay numbers when I/O extension equipment and special extension equipment are connected to the PLC main unit, refer to the Hardware Edition.

1) FX 3S PLC

Device name Description Reference

Input relay X000 to X017 16 points Device numbers are octal. Section 4.2 Output relay Y000 to Y015 14 points

General type M0 to M383 384 points

Section 4.3 EEPROM keep type M384 to M511 128 points

General type M512 to M1535 1024 points

Special type*1 M8000 to M8511 512 points Chapter 37

Specified the Device & Constant

Initial state type (EEPROM keep) S0 to S9 10 points

Section 4.4 EEPROM keep type S10 to S127 118 points

General type S128 to S255 128 points

100 ms T0 to T31 32 points 0.1 to 3,276.7 sec

100 ms/10 ms T32 to T62 31 points 0.1 to 3,276.7 sec/0.01 to 327.67 sec They can be switched from 100 ms to 10 ms by driving the special auxiliary relay M8028.

1 ms T63 to T127 65 points 0.001 to 32.767 sec

Section 4.5

Retentive type for 1 ms (EEPROM keep) T128 to T131 4 points 0.001 to 32.767 sec

Retentive type for 100 ms (EEPROM keep) T132 to T137 6 points 0.1 to 3,276.7 sec

General type up counter (16 bits) C0 to C15 16 points Counts 0 to 32,767

Section 4.6 EEPROM keep type up counter (16 bits) C16 to C31 16 points Counts 0 to 32,767

General type bi-directional counter (32 bits)

C200 to C234 35 points −2,147,483,648 to +2,147,483,647 counts

*1. For applicable functions, refer to Chapter 37. For handling of the latched area, refer to Section 2.6.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 12 more labels / short text on this page
Introduction · Overview · Instruction List · I/O relay · Devices in Detail · Auxiliary relay · State relay · Timer (on-delay timer) · Before Programming · Basic Instruction · Counter · FNC00-FNC09 Program Flow
Page 86 of the Mitsubishi Electronics MELSEC FX3S user manual — 4. Devices in Detail
Page 86 · click to enlarge
Page 86

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.1 Device Number List

Device name Description Reference

1-phase 1-counting input Bi-directional (32 bits) (EEPROM keep)

−2,147,483,648 to +2,147,483,647 counts Software counter 1 phase: 60 kHz × 2 points, 10 kHz × 4 points 2 phases: 30 kHz × 1 point, 5 kHz × 1 point

Section 4.7 1-phase 2-counting input Bi-directional (32 bits) (EEPROM keep)

2-phase 2-counting input Bi-directional (32 bits) (EEPROM keep)

Data register (32 bits when used in pair form)

General type (16 bits) D0 to D127 128 points

EEPROM keep type (16 bits) D128 to D255 128 points

General type (16 bits) D256 to D2999 2744 points

Section 4.9

Among 2000 latched type data registers backed up by the EEPROM, D1000 and later can be set as file registers in units of 500 points by the parameter setting.

EEPROM keep type (16 bits) <file register> D1000 to D2999 2000 points

Special type (16 bits)*1 D8000 to D8511 512 points Chapter 37

Index type (16 bits) V0 to V7, Z0 to Z7 16 points Section 4.11

For jump and branch call P0 to P255 256 points For CJ and CALL instructions

Section 4.12 Input interrupt I0 to I5 6 points

Timer interrupt I6 to I8 3 points

For master control N0 to N7 8 points For MC instruction

16 bits −32,768 to +32,767

32 bits −2,147,483,648 to +2,147,483,647

16 bits 0 to FFFF

32 bits 0 to FFFFFFFF

Real number (E) 32 bits −1.0 × 2128 to −1.0 × 2−126, 0, 1.0 × 2−126 to 1.0 × 2128

Both the decimal point expression and the exponent expression are available.

*1. For applicable functions, refer to Chapter 37. For handling of the latched area, refer to Section 2.6.

Show 10 more labels / short text on this page
High-speed counter · C235 to C245 · C246 to C250 · C251 to C255 · Pointer · Nesting · Constant · Decimal (K) · Hexadecimal (H) · Chapter 5
Page 87 of the Mitsubishi Electronics MELSEC FX3S user manual — 4.1 Device Number List 1
Page 87 · click to enlarge
Page 87

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.1 Device Number List 1

2. FX 3G /FX 3GC PLCs

Device name Description Reference

Input relay X000 to X177 128 points Device numbers are octal. The total number of inputs and outputs is 128. Section 4.2 Output relay Y000 to Y177 128 points

General type M0 to M383 384 points

Section 4.3 EEPROM keep type M384 to M1535 1152 points

General type*1 M1536 to M7679*2 6144 points

Special type*3 M8000 to M8511 512 points Chapter 37

Initial state type (EEPROM keep) S0 to S9 10 points

Section 4.4 EEPROM keep type S10 to S899 890 points

Annunciator type (EEPROM keep) S900 to S999 100 points

General type*1 S1000 to S4095 3096 points

100 ms T0 to T191 192 points 0.1 to 3,276.7 sec

100 ms [for subroutine or interrupt routine] T192 to T199 8 points 0.1 to 3,276.7sec

10 ms T200 to T245 46 points 0.01 to 327.67 sec

Retentive type for 1 ms (EEPROM keep) T246 to T249 4 points 0.001 to 32.767 sec

Section 4.5

Specified the Device & Constant

Retentive type for 100 ms (EEPROM keep) T250 to T255 6 points 0.1 to 3,276.7 sec

1 ms T256 to T319 64 points 0.001 to 32.767 sec

General type up counter (16 bits) C0 to C15 16 points Counts 0 to 32,767

EEPROM keep type up counter (16 bits) C16 to C199 184 points Counts 0 to 32,767

Section 4.6

General type bi-directional counter (32 bits) C200 to C219 20 points −2,147,483,648 to +2,147,483,647 counts

EEPROM keep bi-directional counter (32 bits) C220 to C234 15 points −2,147,483,648 to +2,147,483,647 counts

1-phase 1-counting input Bi- directional (32 bits) (EEPROM keep)

−2,147,483,648 to +2,147,483,647 counts Software counter 1 phase: 60 kHz × 4 points, 10 kHz × 2 points 2 phases: 30 kHz × 2 points, 5 kHz × 1 point

Section 4.7 1-phase 2-counting input Bi- directional (32 bits) (EEPROM keep)

2-phase 2-counting input Bi- directional (32 bits) (EEPROM keep)

*1. When the optional battery is installed, general type devices can be changed to latched (battery backed) type devices by the parameter setting. However, the latched range cannot be set.

*2. Operation varies when M2800 to M3071 are used in the LDP, LDF, ANDP, ANDF, ORP and ORF instructions. Refer to Section 7.5 for the details.

FNC10-FNC19 Move & Compare

*3. For applicable functions, refer to Chapter 37. For handling of the latched area, refer to Section 2.6.

FNC20-FNC29 Arith. & Logic Operation

Show 16 more labels / short text on this page
Introduction · I/O relay · Auxiliary relay · Overview · State relay · Instruction List · Devices in Detail · Timer (on-delay timer) · Counter · Before Programming · High-speed counter · Basic Instruction · C235 to C245 · C246 to C250 · FNC00-FNC09 Program Flow · C251 to C255
Page 88 of the Mitsubishi Electronics MELSEC FX3S user manual — 4. Devices in Detail
Page 88 · click to enlarge
Page 88

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.1 Device Number List

Device name Description Reference

Data register (32 bits when used in pair form)

General type (16 bits) D0 to D127 128 points

EEPROM keep type (16 bits) D128 to D1099 972 points

General type (16 bits)*1 D1100 to D7999 6900 points

Section 4.9

Among 7000 latched type data registers backed up by the EEPROM, D1000 and later can be set as file registers in units of 500 points by the parameter setting.

EEPROM keep type (16 bits) <file register> D1000 to D7999 7000 points

Special type (16 bits)*2 D8000 to D8511 512 points Chapter 37

Index type (16 bits) V0 to V7, Z0 to Z7 16 points Section 4.11

Extension register/Extension file register

(16 bits)*1 R0 to R23999 24000 points

Section 4.10 Extension file register (16 bits) (EEPROM keep)

ER0 to ER23999 24000 points

For jump and branch call P0 to P2047 2048 points For CJ and CALL instructions

Section 4.12 Input interrupt I0 to I5 6 points

Timer interrupt I6 to I8 3 points

For master control N0 to N7 8 points For MC instruction

16 bits −32,768 to +32,767

32 bits −2,147,483,648 to +2,147,483,647

16 bits 0 to FFFF

32 bits 0 to FFFFFFFF

Real number (E)*3 32 bits −1.0 × 2128 to −1.0 × 2−126, 0, 1.0 × 2−126 to 1.0 × 2128

Both the decimal point expression and the exponent expression are available.

*1. When the optional battery is installed, general type devices can be changed to latched (battery backed) type devices by the parameter setting. However, the latched range cannot be set.

*2. For applicable functions, refer to Chapter 37. For handling of the latched area, refer to Section 2.6.

*3. Available in Ver. 1.10 or later.

Show 7 more labels / short text on this page
Extension register · Pointer · Nesting · Constant · Decimal (K) · Hexadecimal (H) · Chapter 5
Page 89 of the Mitsubishi Electronics MELSEC FX3S user manual — 4.1 Device Number List 1
Page 89 · click to enlarge
Page 89

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.1 Device Number List 1

3. FX 3U /FX 3UC PLCs

Device name Description Reference

Input relay X000 to X367*1 248 points Device numbers are octal. The total number of inputs and outputs is 256. Section 4.2 Output relay Y000 to Y367*1 248 points

General type [variable] M0 to M499 500 points The setting can be changed between the latched (battery backed) type and the non-latched type using parameters. Section 4.3 Latched (battery backed) type [variable] M500 to M1023 524 points

Latched (battery backed) type [fixed] M1024 to M7679*2 6656 points

Special type*3 M8000 to M8511 512 points Chapter 37

Initial state (general type [variable]) S0 to S9 10 points

General type [variable] S10 to S499 490 points

The setting can be changed between the latched (battery backed) type and the non-latched type using parameters. Section 4.4

Latched (battery backed) type [variable] S500 to S899 400 points

Annunciator (latched (battery backed) type [variable])

S900 to S999 100 points

Latched (battery backed) type [fixed] S1000 to S4095 3096 points

100 ms T0 to T191 192 points 0.1 to 3,276.7 sec

Specified the Device & Constant

100 ms [for subroutine or interrupt routine] T192 to T199 8 points 0.1 to 3,276.7 sec

10 ms T200 to T245 46 points 0.01 to 327.67 sec

Section 4.5

Retentive type for 1 ms T246 to T249 4 points 0.001 to 32.767 sec

Retentive type for 100 ms T250 to T255 6 points 0.1 to 3,276.7 sec

1 ms T256 to T511 256 points 0.001 to 32.767 sec

General type up counter (16 bits) [variable] C0 to C99 100 points Counts 0 to 32,767 The setting can be changed between the latched (battery backed) type and the non-latched type using parameters.

Latched (battery backed) type up counter (16 bits) [variable]

C100 to C199 100 points

General type bi-directional counter (32 bits) [variable]

Section 4.6

C200 to C219 20 points −2,147,483,648 to +2,147,483,647 counts The setting can be changed between the latched (battery backed) type and the non-latched type using parameters.

Latched (battery backed) type bi-directional counter (32 bits) [variable]

C220 to C234 15 points

*1. Available device numbers vary depending on the PLC. For details, refer to Section 4.2.

*2. Operation varies when M2800 to M3071 are used in the LDP, LDF, ANDP, ANDF, ORP and ORF instructions. Refer to Section 7.5 for the details.

*3. For supported functions, refer to Chapter 37. For handling of the latched (battery backed) area, refer to Section 2.6.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 12 more labels / short text on this page
Introduction · I/O relay · Auxiliary relay · Overview · Instruction List · State relay · Devices in Detail · Timer (on-delay timer) · Before Programming · Counter · Basic Instruction · FNC00-FNC09 Program Flow
Page 90 of the Mitsubishi Electronics MELSEC FX3S user manual — 4. Devices in Detail
Page 90 · click to enlarge
Page 90

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.1 Device Number List

Device name Description Reference

8 points maximum can be used among C235 to C255 [latched (battery backed) type]. The setting can be changed between the latched (battery backed) type and the non-latch type using parameters. −2,147,483,648 to +2,147,483,647 counts

1-phase 1-counting input Bi-directional (32 bits) C235 to C245

1-phase 2-counting input Bi-directional (32 bits) C246 to C250

1 phase: 100 kHz × 6 points, 10 kHz × 2 points 2 phases: 50 kHz (1 edge count), 50 kHz (4 edge count) Software counter 1 phase: 40 kHz 2 phases: 40 kHz (1 edge count), 10 kHz (4 edge count)

Section 4.8

2-phase 2-counting input Bi-directional (32 bits) C251 to C255

Data register (32 bits when used in pair form)

General type (16 bits) [variable] D0 to D199 200 points The setting can be changed between the latched (battery backed) type and the non-latched type using parameters.

latched (battery backed) type (16 bits) [variable]

D200 to D511 312 points

Section 4.9

latched (battery backed) type (16 bits) [fixed] <file register>

D512 to D7999

7488 points

Among the 7488 fixed latched (battery backed) type data registers, D1000 and later can be set as file registers in units of 500 points.

Special type (16 bits)*2 D8000 to D8511 512 points Chapter 37

Index type (16 bits) V0 to V7, Z0 to Z7 16 points Section 4.11

Extension register/Extension file register

Extension register (16 bits) R0 to R32767 32768 points latched (battery backed)

Section 4.10 Extension file register (16 bits) ER0 to ER32767 32768 points Available only while a memory cassette is mounted

For jump and branch call P0 to P4095 4096 points For CJ and CALL instructions

Section 4.12 Input interrupt Input delay interrupt I0 to I5 6 points

Timer interrupt I6 to I8 3 points

Counter interrupt I010 to I060 6 points For HSCS instruction

For master control N0 to N7 8 points For MC instruction

16 bits −32768 to +32767

32 bits −2,147,483,648 to +2,147,483,647

16 bits 0 to FFFF

32 bits 0 to FFFFFFFF

Real number (E) 32 bits −1.0 × 2128 to −1.0 × 2−126, 0, 1.0 × 2−126 to 1.0 × 2128

Both the decimal point expression and the exponent expression are available.

Specify characters by quotation marks. In a constant of an instruction, up to 32 half-width characters are available.

Character string (" ") Character string

*1. When the FX3U-4HSX-ADP is connected to an FX3U PLC, the maximum input frequency is set as follows: 1 phase: 200 kHz 2 phases: 100 kHz (1 edge count). 100 kHz (4 edge count)

*2. For supported functions, refer to Chapter 37. For handling of the latched (battery backed) area, refer to Section 2.6.

Show 8 more labels / short text on this page
High-speed counter · Hardware counter*1 · Pointer · Nesting · Constant · Decimal (K) · Hexadecimal (H) · Chapter 5
Page 91 of the Mitsubishi Electronics MELSEC FX3S user manual — FX 3UC -32MT-LT(-2) PLC
Page 91 · click to enlarge
Page 91

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.2 I/O Relays [X, Y] 1

4.2 I/O Relays [X, Y]

Some input relays and output relays are secured in the main unit, and others are assigned to extension devices according to the connection order. Because I/O replays are numbered in octal, numeric values such as "8" and "9" do not exist.

4.2.1 Numbers of I/O relays

The table below shows input relay (X) and output relays (Y) numbering (Relay numbers are assigned in octal.

name FX3S-10M FX3S-14M FX3S-20M FX3S-30M

FX 3S PLC

total Input X000 to X005

6 points X000 to X007

8 points X000 to X013

12 points X000 to X017

Output Y000 to Y003

4 points Y000 to Y005

6 points Y000 to Y007

8 points Y000 to Y015

name FX3G-14M FX3G-24M FX3G-40M FX3G-60M When extended

FX 3G PLC

total Input X000 to X007

8 points X000 to X015

14 points(16)*1 X000 to X027

24 points X000 to X043

36 points(40)*1 X000 to X177

Output Y000 to Y005

6 points(8)*1 Y000 to Y011

10 points(16)*1 Y000 to Y017

16 points Y000 to Y027

24 points Y000 to Y177

FX 3GC -32MT/

FX 3GC PLC

total Input X000 to X017

16 points X000 to X177

Specified the Device & Constant

Output Y000 to Y017

16 points Y000 to Y177

name FX3U-16M FX3U-32M FX3U-48M FX3U-64M FX3U-80M FX3U-128M When extended

FX 3U PLC

total Input X000 to X007

8 points X000 to X017

16 points X000 to X027

24 points X000 to X037

32 points X000 to X047

40 points X000 to X077

64 points X000 to X367

Output Y000 to Y007

8 points Y000 to Y017

16 points Y000 to Y027

24 points Y000 to Y037

32 points Y000 to Y047

40 points Y000 to Y077

64 points Y000 to Y367

name FX3UC-16M FX3UC-32M FX3UC-64M FX3UC-96M When extended

256 points in total Input X000 to X007

8 points X000 to X017

16 points X000 to X037

32 points X000 to X057

48 points X000 to X367

FX 3UC (D, DS, DSS) PLC

Output Y000 to Y007

8 points Y000 to Y017

16 points Y000 to Y037

32 points Y000 to Y057

48 points Y000 to Y367

FX 3UC -32MT-LT

total Input X000 to X017

16 points X000 to X357

FX 3UC -32MT-LT(-2) PLC

Output Y000 to Y017

16 points Y000 to Y357

*1. A number inside ( ) indicates the number of occupied points. The difference from the number of valid points is unused.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 35 more labels / short text on this page
Introduction · Overview · Model · 30 points in · 16 points · Instruction List · 14 points · Model · 128 points in · 128 points · Devices in Detail · 128 points · Model · D(SS) When extended · name · 128 points in · 128 points · 128 points · Model · 256 points in · 248 points · Before Programming · 248 points · ) · Model · 248 points · Basic Instruction · 248 points · Model · (-2) When extended · name · 256 points in · 240 points · FNC00-FNC09 Program Flow · 240 points
Page 92 of the Mitsubishi Electronics MELSEC FX3S user manual — COM1
Page 92 · click to enlarge
Page 92

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.2 I/O Relays [X, Y]

4.2.2 Functions and roles

Examples of terminal names and wiring (sink input) are for the FX3U Series PLC.

COM1

S/S

Y000

Y000

Y000

Y000

Y000

PLC

The PLC receives signals from external switches through input terminals. An input relay (X) connected to an input terminal inside the PLC is an electronic relay isolated optically, and has many NO contacts and NC contacts. These contacts can be arbitrarily used inside the PLC. These input relays cannot be driven by the program.

The PLC outputs signals to external loads through output terminals. Contacts for external output (output devices such as relay contacts, triacs and transistors) of output relays are connected to output terminals inside the PLC. An output relay has many electronic NO contacts and NC contacts. These contacts can be arbitrarily used inside the PLC. Differences in operations between external output contacts (output devices) and internal contacts are explained on the next page.

Show 9 more labels / short text on this page
External power · supply · X001 Program example · Input signal · Load · NO contact · Input terminal · Output terminal · NC contact
Page 93 of the Mitsubishi Electronics MELSEC FX3S user manual — Y000
Page 93 · click to enlarge
Page 93

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.2 I/O Relays [X, Y] 1

4.2.3 Operation timing of I/O relays

The PLC executes sequence control by repeatedly executing the following processing procedure. In this batch I/O method, not only are there driving times of input filters and output devices but also response delays caused by operation cycles. (Refer to Section 6.3.)

1. 2) 3) 6) indicate the processing order.
1. Read-in

Input processing Before executing a program, the PLC reads the ON/ OFF status of all input terminals inside the PLC into the input image memory. Even if inputs change while the program is executed, the contents of the input image memory remain unchanged, but the changes in inputs are read during the input processing in the next cycle. Even if an input contact changes from ON to OFF or from OFF to ON, its ON/OFF status is judged after the response delay (approximately 10 ms) caused by the input filter. (When the input filter is a digital type input terminal , its value can be overwritten by a sequence program.)

2. Read-out

Program processing The PLC reads the ON/OFF status of each device from the input image memory and other device image memories according to the contents of instructions in the program memory, executes operations in sequence from step 0, and then writes the operation result to the image memory. Accordingly, the contents of the image memory for each device change as the program is executed. The operation of a contact inside an output relay is determined by the contents of the output image memory.

Y000

3. Write
4. Readout

Specified the Device & Constant

M 0

Y000

5. Write

Repeated operation [The time required for a cyclic operation is called operation cycle (scan time).]

6. Output

Output processing When execution of all instructions is finished, the ON/OFF status of the image memory of outputs (Y) is transferred to the output latch memory. This is the actual output of the PLC. External output contacts inside the PLC operate after the response delay time of the output devices.

Y000

Y001

Y002

The above method is called the batch I/O method (or refresh method).

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 22 more labels / short text on this page
Introduction · Input processing · Overview · Input terminal · Input · Image · Memory · Instruction List · Devices in Detail · Program processing · Device · Image · Memory · Auxiliary relay · Before Programming · Output processing · Basic Instruction · Output terminal · Output · Latch · Memory · FNC00-FNC09 Program Flow
Page 94 of the Mitsubishi Electronics MELSEC FX3S user manual — M100
Page 94 · click to enlarge
Page 94

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.3 Auxiliary Relay [M]

4.3 Auxiliary Relay [M]

There are many auxiliary relays inside the PLC. Coils of auxiliary relays are driven by contacts of various devices inside the PLC in the same way as output relays. Auxiliary relays have many electronically NO contacts and NC contacts which can be used arbitrarily inside the PLC. However, external loads cannot be driven directly by these contacts. External loads should be driven by output relays.

4.3.1 Numbers of auxiliary relays

The table below shows auxiliary relay (M) numbers. (Numbers are assigned in decimal.)

1. FX 3S PLC

General type Fixed latched (EEPROM keep) type General type Special type

384 points M384 to M511

128 points M512 to M1535

1024 points M8000 to M8511

2. FX 3G /FX 3GC PLCs

General type Fixed latched (EEPROM keep) type General type Special type

384 points M384 to M1535

1152 points M1536 to M7679

6144 points*1 M8000 to M8511

3. FX 3U /FX 3UC PLCs

General type Latched (battery backed) type

Fixed latched (battery backed) type Special type

500 points*2 M500 to M1023

524 points*3 M1024 to M7679

6656 points*4 M8000 to M8511

*1. These registers can be changed to the latched (battery backed) type by the parameter setting when the optional battery is used. However, the latched range cannot be set.

*2. This area is not latched (battery backed). It can be changed to a latched (battery backed) area by setting the parameters.

*3. This area is latched (battery backed). It can be changed to a non-latched (non-battery-backed) area by setting the parameters.

*4. The characteristics of latch (battery backup) cannot be changed in the parameters.

When N : N Network or parallel link is used, some auxiliary relays are occupied for the link.

→ Refer to the Data Communication Edition manual.

4.3.2 Functions and operation examples

1. General type All of general type auxiliary relays turn OFF when the PLC turns OFF. When the ON/OFF status of auxiliary relays just before power failure is required in control, use latched (battery backed) type auxiliary relays.

M100

M100

M100

Show 9 more labels / short text on this page
M0 to M383 · 512 points · M0 to M383 · 512 points · M0 to M499 · 512 points · NO contact · NC contact · Auxiliary relay circuit
Page 95 of the Mitsubishi Electronics MELSEC FX3S user manual — M8002
Page 95 · click to enlarge
Page 95

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.3 Auxiliary Relay [M] 1

2. Latched (battery backed) type When the power is turned OFF while the PLC is operating, all of the output relays and general type auxiliary relays turn OFF. When restoring the power again, all of the output relays and general type auxiliary relays remain OFF except those whose input condition is ON. In some output relays and auxiliary relays, however, the ON/OFF status just before power failure should be stored and then replicated when restoring the power, depending on control targets. In such a case, use latched (battery backed) type auxiliary relays. In FX3U/FX3UC PLCs, latched (battery backed) type devices are backed up by the battery built into the PLC. In FX3S/FX3G/FX3GC PLCs, latched type devices are backed up by the EEPROM built into the PLC. When the optional battery is installed in FX3G/FX3GC PLCs, the battery backs up some general type devices.

→ For details on backup method against power failure,

refer to Section 2.6. The figure on the left shows an operation example of M600 (latched [battery backed] type device) in a self-holding circuit. When X000 turns ON and M600 turns ON in this circuit, M600 holds its operation by itself even if X000 is opened. Because M600 is a latched (battery backed) type device, it remains activated when the operation is restarted even after X000 has turned OFF due to power failure. If an NC contact of X001 is opened when the operation is restarted, however, M600 is deactivated.

M600

M600

PLC Backup against power failure

SET M600

The figure on the left shows a circuit using the SET and RST instructions.

RST M600

Specified the Device & Constant

PLC Backup against power failure

1. Application example of latched (battery backed) type auxiliary relays

In some cases, the table should be restarted in the same direction as the direction selected just before power failure.

Left limit Limit switch

LS1 (X000) Right limit Limit switch

LS2 (X001)

Table in reciprocating motion

X000 = ON (at the left limit) → M600 = ON→ The table is driven rightward. → The power is turned OFF. → The table is stopped in an intermediate position. → The table is restarted (M600 = ON). → X001 = ON (at the right limit) → M600 = OFF, M601 = ON → The table is driven leftward.

M600 Rightward drive command

M600

M601 Leftward drive command

M601

FNC10-FNC19 Move & Compare

2. Method for using a fixed latched (battery backed) type auxiliary relay as a general type auxiliary relay When using a fixed latched (battery backed) type auxiliary relay as a general type auxiliary relay, provide a reset circuit shown in the figure below around the head step in the program. Ex. FX 3U /FX 3UC PLCs

M8002

ZRST M1024 M1999

FNC20-FNC29 Arith. & Logic Operation

M1024 to M1999 are initialized.

Show 11 more labels / short text on this page
Introduction · Overview · Instruction List · (self-holding circuit) · Devices in Detail · (set/reset circuit) · Before Programming · Basic Instruction · Motor with brake · FNC00-FNC09 Program Flow · Initial pulse
Page 96 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. FX 3U /FX 3UC PLCs
Page 96 · click to enlarge
Page 96

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.4 State Relay [S]

4.4 State Relay [S]

State relays (S) are important devices to program stepping type process control simply, and combined with the step ladder instruction STL. State relays can be used in the SFC (sequential function chart) programming method.

→ For programming by the step ladder instruction and SFC method, refer to Chapter 35.

4.4.1 Numbers of state relays

The table below shows state relay (S) numbers. (Numbers are assigned in decimal.)

1. FX 3S PLC

Initial state type (EEPROM keep)

Fixed latched (EEPROM keep) type General type

S0 to S9 10 points S10 to S127

118 points S128 to S255

2. FX 3G /FX 3GC PLCs

Initial state type (EEPROM keep)

Fixed latched (EEPROM keep) type

(EEPROM keep) General type

S0 to S9 10 points S10 to S899

890 points S900 to S999

100 points S1000 to S4095

3. FX 3U /FX 3UC PLCs

Initial state type General type Latched (battery backed) type

Fixed latched (battery backed) type Annunciator type

10 points*2 S0 to S499

500 points*2 S500 to S899

400 points*3 S1000 to S4095

3096 points*4 S900 to S999

*1. These registers can be changed to the latched (battery backed) type by the parameter setting when the optional battery is used. However, the latched range cannot be set.

*2. This area is not latched (battery backed). It can be changed to a latched (battery backed) area by setting the parameters.

*3. This area is latched (battery backed). It can be changed to a non-latched (non-battery-backed) area by setting the parameters.

*4. The characteristics of latch (battery backup) cannot be changed in the parameters.

Show 5 more labels / short text on this page
128 points · Annunciator type · 3096 points*1 · S0 to S9 · 100 points*3
Page 97 of the Mitsubishi Electronics MELSEC FX3S user manual — M8002
Page 97 · click to enlarge
Page 97

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.4 State Relay [S] 1

4.4.2 Functions and operation examples

1. General type In the stepping type process control shown in the left figure, when the start signal X000 turns ON, the state relay S20 is set (turned ON) and the solenoid valve Y000 for moving down turns on. When the lower limit switch X001 turns ON the state relay S21 is set (turned ON) and the solenoid valve Y001 for clamping turns on. When the clamp confirmation limit switch X002 turns ON, the state relay S22 is set (turned ON). When the operation proceeds to the next step, the state relay in the preceding step is automatically reset (turned OFF).

TRAN

Y000

TRAN

Y001

When the PLC turns OFF, all of general type state relays are turned OFF. When the ON/OFF status just before power failure is required, use latched (battery backed) type state relays.

TRAN

Y002

TRAN

State relays have many NO contacts and NC contacts in the same way as auxiliary relays, and such contacts can be used arbitrarily in sequence programs. When state relays (S) are not used for step ladder instructions, they can be used in general sequences in the same way as auxiliary relays (M) (as shown in the figure on the right).

Specified the Device & Constant

M30

Y005

2. Latched (battery backed) type

  • Latched (battery backed) type state relays store their ON/OFF status even if the power is shut down while the PLC is operating, so the operation can be restarted from the last point in the process. In FX 3U /FX 3UC PLCs, latched (battery backed) type devices are backed up by the battery built into the PLC. In FX 3S /FX 3G /FX 3GC PLCs, latched type devices are backed up by the EEPROM built into the PLC. When the optional battery is installed in FX 3G /FX 3GC PLCs, the battery backs up some general type devices.

→ For details on backup against power failure, refer to Chapter 2.6.

  • When using latched (battery backed) type state relays as general type state relays, provide a reset circuit shown in the right figure around the head step in the program.

Ex. FX3U/FX3UC PLCs

M8002

ZRST S1000 S1200 0

S1000 to S1200 are initialized.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 20 more labels / short text on this page
Introduction · Initial state · Start X000 · Overview · Start · Moving down · Lower limit · Lower limit · Instruction List · Clamping · Clamping · Clamping · Moving up · Devices in Detail · Upper limit · Upper limit · Before Programming · Basic Instruction · Initial pulse · FNC00-FNC09 Program Flow
Page 98 of the Mitsubishi Electronics MELSEC FX3S user manual — ANRP
Page 98 · click to enlarge
Page 98

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.4 State Relay [S]

3. Annunciator type Annunciator type state relays can be used as outputs for external fault diagnosis.

For example, when an external fault diagnosis circuit shown in the figure below is created and the contents of the special data register D8049 are monitored, the smallest number out of the active state relays S900 to S999 is stored in D8049. If two or more faults have occurred, the smallest state number having a fault is displayed at first. When the fault is cleared, the next smallest state number having a fault is stored.

M8000

When the special auxiliary relay M8049 is driven, monitoring becomes valid. •

M8049

Y000 X000 FNC 46

If the forward end detection input X000 is not activated within 1 second after the forward output Y000 is driven, S900 is activated.

ANS T 0 K 10 S900

X002 FNC 46

If both the upper limit detection input X001 and the lower limit detection input X002 are deactivated at the same time for 2 seconds or more, S901 is activated.

ANS T 1 K 20 S901

X003 X004 FNC 46

In a machine whose tact time is less than 10 seconds, if the switch X004 which is designed to be activated during one-cycle operation of the machine is not activated while the continuous operation mode input X003 is ON, S902 is activated.

ANS T 2 K100 S902

M8048

Y010

When any annunciator among S900 to S999 turns ON, the special auxiliary relay M8048 is activated and the fault display output Y010 is activated.

X005 FNC 47

The state relays activated by the external fault diagnosis program can be turned OFF by the reset button X005. Every time X005 is set to ON, the active annunciator with the smallest number is reset in turn.

ANRP

While the special auxiliary relay M8049 is not driven, annunciator type state relays can be used as latched (battery backed) type state relays in sequence programs in the same way as general type state relays. In the SFC programming mode in the FX-PCS/WIN(-E), however, S900 to S999 cannot be programmed as a processes flow in SFC diagrams.

Show 6 more labels / short text on this page
RUN monitor · • · • · • · • · •
Page 99 of the Mitsubishi Electronics MELSEC FX3S user manual — T32 K100
Page 99 · click to enlarge
Page 99

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.5 Timer [T] 1

4.5 Timer [T]

Timers add and count clock pulses of 1 ms, 10 ms, 100 ms, etc. inside the PLC. When the counted value reaches a specified set value, the output contact of the timer turns on. A set value can be directly specified by a constant (K) in the program memory, or indirectly specified by the contents of a data register (D).

4.5.1 Numbers of timers

The table below shows timer (T) numbers. (The numbers are assigned in decimal.) 1. FX3S PLC

For 100 ms pulses

pulses 0.1 to 3276.7 sec 0.01 to 327.67 sec

For 1 ms pulses 0.001 to 32.767 sec

1 ms pulses 0.001 to 32.767 sec

100 ms pulses 0.1 to 3276.7 sec

0 to 255 (numeric value)

0.1 to 3276.7 sec

2 built-in points*2

63 points T32 to T62

31 points T63 to T127

4 points Latched type*1

6 points Latched type*1

Stored in D8030 and

2. FX 3G /FX 3GC PLCs

For 100 ms pulses

0.1 to 3276.7 sec For 10 ms pulses 0.01 to 327.67 sec

For 1 ms pulses 0.001 to 32.767 sec

1 ms pulses 0.001 to 32.767 sec

100 ms pulses 0.1 to 3276.7 sec

0 to 255 (numeric value)

200 points Routine program

2 built-in points*3

4 points for Interrupt execution

6 points Latched type*1

Stored in D8030 and

type T192 to T199

Specified the Device & Constant

3. FX 3U /FX 3UC PLCs

For 100 ms pulses

0.1 to 3276.7 sec For 10 ms pulses 0.01 to 327.67 sec

For 1 ms pulses 0.001 to 32.767 sec

1 ms pulses*4

100 ms pulses*4

0.001 to 32.767 sec

0.1 to 3276.7 sec

200 points Routine program type

4 points for Interrupt execution

6 points Latched (battery

Timer numbers not used for timers can be used as data registers for storing numeric values.

*1. In FX3S/FX3G/FX3GC PLCs, retentive type timers are backed up by the EEPROM memory. *2. This function is not supported in the FX3S-30M /E -2AD PLC. *3. This function is supported only in FX3G PLC. *4. In FX3U/FX3UC PLCs, retentive type timers are backed up by the battery. 4.5.2 Functions and operation examples

1. General type When the drive input X000 of the timer coil T200 turns ON, the current value counter for T200 adds and counts clock pulses of 10 ms. When the counted value becomes equivalent to the set value K123, the output contact of the timer turns on. In other words, the output contact turns on 1.23 seconds after the coil is driven. When the drive input X000 turns OFF or when the power is turned off the timer is reset and the output contact returns.

T200 T200

K123

Set value (constant) A data register can be specified also.

Y000

1.23 sec

FNC10-FNC19 Move & Compare

Y000

[The program of 100 ms/10 ms type timer of the FX3S PLC]

M8000

For FX3S, driving M8028 ON, timers T32 to T62 are changed to 10 ms resolution.

M8028

FNC20-FNC29 Arith. & Logic Operation

T32 K100

Show 43 more labels / short text on this page
Introduction · Overview · For 100/10 ms · Retentive type for · Retentive type for · Potentiometer type · Instruction List · T128 to T131 · T132 to T137 · T0 to T62 · 65 points · Retentive type for · Retentive type for · Potentiometer type · Devices in Detail · T0 to T199 · T246 to T249 · T250 to T255 · T200 to T245 · T256 to T319 · 46 points · 64 points · Latched type*1 · Retentive type for · Retentive type for · T0 to T199 · T246 to T249 · T250 to T255 · T200 to T245 · T256 to T511 · 46 points · 256 points · Before Programming · Latched (battery · backed) type*4 · backed) type*4 · T192 to T199 · Basic Instruction · FNC00-FNC09 Program Flow · Set value X000 · Current value · RUN monitor · 1-second timer
Page 100 of the Mitsubishi Electronics MELSEC FX3S user manual — T10 D08030
Page 100 · click to enlarge
Page 100

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.5 Timer [T]

2. Retentive type When the drive input X001 of the timer coil T250 turns ON, the current value counter for T250 adds and counts clock pulses of 100 ms. When the counted value becomes equivalent to the set value K345, the output contact of the timer turns on. Even if the drive input X001 turns OFF or the power is turned off during counting, the timer continues counting when the operation restarts. The retentive operating time is 34.5 seconds. When the reset input X002 turns ON, the timer is reset and the output contact is returned.

Mitsubishi Electronics MELSEC FX3S — 4.5 Timer [T] diagram (page 100)
Fig. 29 · 4.5 Timer [T]

Set value (constant) A data register can be specified also. X002

t2 t1 Retentive time t1 + t2 = 34.5 sec

3. Potentiometer type

1. When variable analog potentiometers built in the FX 3S /FX 3G PLCs are used *1

Values of variable analog potentiometers built in FX3S/FX3G PLCs as standard are stored as numeric data ranging from 0 to 255 in the following special registers in accordance with the scale position. An obtained numeric value can be specified as the indirectly specified value for a timer to make a variable potentiometer type analog timer.

T10 D08030

This register stores the value (0 to 255) of variable analog potentiometer.

0 to 25.5 sec

Mitsubishi Electronics MELSEC FX3S — T10 D08030 diagram (page 100)
Fig. 30
  • VR1 → D8030 (Integer from 0 to 255)
  • VR2 → D8031 (Integer from 0 to 255)

"D8030 (VR2) value x 2" is transferred to D0 (D1).

The set value range can be changed (up to 32,767) by multiplying the register value by "n".

*1. This function is not supported in the FX3S-30M /E -2AD PLC.

2. When variable analog potentiometers (expansion board) are used

The value of a variable analog potentiometer board which can be built in an FX3S/FX3G/FX3U/FX3UC- 32MT-LT(-2) PLC can be obtained as numeric data ranging from 0 to 255 in accordance with the scale position. An obtained numeric value can be specified as the indirectly specified value for a timer to make a variable potentiometer type analog timer. Use the FNC 85 (VRRD) instruction to take the value of a variable analog potentiometer into the PLC.

Mitsubishi Electronics MELSEC FX3S — T10 D08030 diagram (page 100)
Fig. 31

→ For FNC 85 (VRRD), refer to Section 16.6. Use the FNC 86 (VRSC) instruction to take the value of a variable analog potentiometer as a numeric value ranging from 0 to 10.

The analog value of the potentiometer No. 0 is converted into binary 8-bit data, and a numeric value ranging from 0 to 255 is transferred to D0. In this application example, the value of D0 is used as the set value of a timer.

→ For FNC 86 (VRSC), refer to Section 16.7.

[Basic example]

Page 101 of the Mitsubishi Electronics MELSEC FX3S user manual — T 0
Page 101 · click to enlarge
Page 101

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.5 Timer [T] 1

4.5.3 Set value specification method

1. Specifying a constant (K) T10 is a 100 ms (0.1 sec) type timer. When the constant "100" is specified, T10 works as a 10second timer (0.1 sec × 100 = 10 sec).

Constant (decimal integer) 10-second timer

T10 K100

2. Indirectly specifying a data register Turns on when T10 reaches the indirectly specified value of the defined data register, previously set by a digital switch. Note that the set value of a latched (battery backed) type register is not held correctly sometimes when the battery voltage becomes low.

X001 FNC 12

MOV K100 D 5

D5 = K100 10-second timer

T10 D 5

4.5.4 Cautions on routines

1) Use timers T192 to T199 in subroutines and interrupt routines. These timers execute counting when a coil instruction or END instruction is executed. When such a timer reaches the set value, its output contact turns on when a coil instruction or END instruction is executed. Because general type timers execute counting only when a coil instruction is executed (Refer to "4.5.5 Details on timer operation and timer accuracy" below), they do not execute counting and do not operate normally if they are used in subroutines or interrupt routines in which a coil instruction is executed only in a certain condition.

2. When a retentive timer for 1 ms pulses (T246 to T249) is used in a subroutine or interrupt routine, note that its output contact turns on when the first coil instruction is executed after the retentive timer has reached the set value.

Specified the Device & Constant

4.5.5 Details on timer operation and timer accuracy

A timer (except interrupt execution type) starts counting when a coil is driven, and its output contact turns on when the first coil instruction is executed after the timer has reached timeout.

Counting operation (If the operation cycle is long, it automatically counts two or more clocks.) Contact is not

Input processing X010 = OFF→ON

activated at this point

T 0 Contact is activated

T 0

K12

1.2 sec time-

T 0

Y010 ON

Y010

2nd cycle "n"th cycle "n+1"th cycle

As shown in the above operation diagram, the accuracy of operation of the timer contact after the coil is driven until the contact turns on is shown in the following outline:

α : 0.001 sec (timer for 1 ms), 0.01 sec (timer for 10 ms) or 0.1 sec (timer for 100 ms) T : Timer set value (sec) T0: Operation cycle (sec) T

If the contact is programmed before the timer coil, "+2T0" is obtained in the worst case. When the timer set value is "0", the output contact turns on when a coil instruction is executed in the next cycle. An interrupt execution type timer for 1 ms pulses counts clock pulses of 1 ms as an interrupt processing after a coil instruction has been executed.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 11 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Timer starts counting · Basic Instruction · out · 1st cycle · FNC00-FNC09 Program Flow · +T0 −α
Page 102 of the Mitsubishi Electronics MELSEC FX3S user manual — Flicker timer
Page 102 · click to enlarge
Page 102

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.5 Timer [T]

4.5.6 Program examples [off-delay timer and flicker timer]

Off-delay timer

Mitsubishi Electronics MELSEC FX3S — 4.5.6 Program examples [off-delay timer and flicker timer] diagram (page 102)
Fig. 32 · 4.5.6 Program examples [off-delay timer and flicker…

Flicker timer (blink)

Mitsubishi Electronics MELSEC FX3S — Flicker timer (blink) diagram (page 102)
Fig. 33 · Flicker timer (blink)

In addition, the flicker operation can be performed by the ALT (FNC 66) instruction.

Multi-timer by the applied instruction STMR (FNC 65) <FX3U/FX3UC PLC>

By this instruction, off-delay timers, one-shot timers and flicker timers can be easily created.

→ For details, refer to Section 14.6.

Off-delay timer and one-shot timer

Mitsubishi Electronics MELSEC FX3S — Off-delay timer and one-shot timer diagram (page 102)
Fig. 34 · Off-delay timer and one-shot timer

A value specified by "m" becomes the set value of the timer specified by . 10-second in this example.

M1 is a one-shot timer after "ON → OFF" operation. •

M2 and M3 are provided for a flicker timer, and connected as shown in the program example for flicker timer (below).

Flicker timer

Mitsubishi Electronics MELSEC FX3S — Flicker timer diagram (page 102)
Fig. 35 · Flicker timer

When M3 is connected as shown in the left figure, M2 and M1 become flicker outputs. •

When X000 is set to OFF, M0, M1 and M3 are turned OFF and T10 is reset after the set time. •

Do not use the timers here in other general circuits again. •

In addition, the timer time can be set according to the switch input time by the teaching timer instruction TTMR (FNC 64).

Page 103 of the Mitsubishi Electronics MELSEC FX3S user manual — 1. Structure of timer present value register
Page 103 · click to enlarge
Page 103

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.5 Timer [T] 1

4.5.7 Handling timers as numeric devices

In timers, the output contact operating in accordance with the set value is used in some cases, and the present value is used as numeric data for control in other cases. The figures below show the structure of the timer present value registers. When a timer number is specified in an operand of an applied instruction, the timer is handled as a device storing 16-bit or 32-bit data in the same way as data registers.

1. Structure of timer present value register

1. 16-bit

Low order 16 bits Available numeric value range 16-bit : 0 to 32,767 32-bit : -2,147,483,648 to +2,147,483,647

1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0

Sign 0Positive number 1: Negative number

1 2 4 8 16 32 64 128 256 512 1024 2048 4096 8192 16384

*1 The sign is valid only when a timer is handled as a substitute for data register.

2. 32-bit

High order 32 bits

0 1 0 1

1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0

Sign 0Positive number 1: Negative number

32768 65536 131,072 262,144 524,288 1,048,576 2,097,152 4,194,304 8,388,608 16,777,216 33,554,432 67,108,864 134,217,728 268,435,456 536,870,912 1,073,741,824

1 2 4 8 16 32 64 128 256 512 1024 2048 4096 8192 16384

Specified the Device & Constant

2. Use examples in applied instructions For the full use of timers as numeric devices, refer to the explanation of applied instructions later.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 12 more labels / short text on this page
Introduction · Overview · High order · b15 · *1 b0 · Instruction List · Devices in Detail · Low order · b31 b0 · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 104 of the Mitsubishi Electronics MELSEC FX3S user manual — 4.6.2 Features of counters
Page 104 · click to enlarge
Page 104

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.6 Counter [C]

4.6 Counter [C]

4.6.1 Numbers of counters

The table below shows counter (C) numbers. (Numbers are assigned in decimal.)

1. FX 3S PLC → For high-speed counters, refer to Section 4.7.
16-bit up counter Counting range0 to 32767

32-bit bi-directional counter Counting range: −2,147,483,648 to +2,147,483,647

General type Fixed latched (EEPROM keep) type General type

16 points C16 to C31

16 points C200 to C234

2. FX 3G /FX 3GC PLCs → For high-speed counters, refer to Section 4.7.
16-bit up counter Counting range0 to 32767

32-bit bi-directional counter Counting range: −2,147,483,648 to +2,147,483,647

General type Fixed latched (EEPROM keep) type General type Fixed latched (EEPROM keep) type

16 points C16 to C199

184 points C200 to C219

20 points C220 to C234

3. FX 3U /FX 3UC PLCs → For high-speed counters, refer to Section 4.8.
16-bit up counter Counting range0 to 32767

32-bit bi-directional counter Counting range: −2,147,483,648 to +2,147,483,647

Latched (battery backed) type (protected by battery against

Latched (battery backed) type (protected by battery against

100 points*1 C100 to C199

100 points*2 C200 to C219

20 points*1 C220 to C234

*1. This area is not latched (battery backed). It can be changed to a latched (battery backed) area by setting the parameters.

*2. This area is latched (battery backed). It can be changed to a non-latched (non-battery-backed) area by setting the parameters.

Counter numbers not used as counters can be converted as data registers for storing numeric values.

4.6.2 Features of counters

The table below shows the features of 16-bit counters and 32-bit counters. They can be used in accordance with the operating condition such as the counting direction switching and counting range, etc.

Item 16-bit counter 32-bit counter

Counting direction Up-counting Up-counting and down-counting can be switched (as shown in Subsection 4.6.3)

Set value 1 to 32767 −2,147,483,648 to +2,147,483,647

Set value specification Constant (K) or data register Constant (K) or a pair of data registers

Current value change Does not change after counting up Changes even after counting up (ring counter)

Output contact Latches after counting up Latches (in up-counting), or reset (in down-counting)

Reset operation When RST instruction is executed, current value of counter is reset to "0" and output contact returns

Current value register 16 bits 32 bits

Show 10 more labels / short text on this page
C0 to C15 · 35 points · C0 to C15 · 15 points · General type · General type · power failure) · power failure) · C0 to C99 · 15 points*2
Page 105 of the Mitsubishi Electronics MELSEC FX3S user manual — Y000
Page 105 · click to enlarge
Page 105

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.6 Counter [C] 1

4.6.3 Related devices (to specify counting direction) [32-bit counter]

When an auxiliary relay for switching the counting direction is set to ON, the counter executes down-counting, and when set to OFF, the counter executes up-counting.

Counter No.

Counter No.

Counter No.

Counter No.

C200 M8200 C209 M8209 C218 M8218 C227 M8227

C201 M8201 C210 M8210 C219 M8219 C228 M8228

C202 M8202 C211 M8211 C220 M8220 C229 M8229

C203 M8203 C212 M8212 C221 M8221 C230 M8230

C204 M8204 C213 M8213 C222 M8222 C231 M8231

C205 M8205 C214 M8214 C223 M8223 C232 M8232

C206 M8206 C215 M8215 C224 M8224 C233 M8233

C207 M8207 C216 M8216 C225 M8225 C234 M8234

C208 M8208 C217 M8217 C226 M8226

4.6.4 Functions and operation examples

1. General type and latched (battery backed) type 16-bit up counters

  • The valid set range of 16-bit binary up counter is from K1 to K32767 (decimal constant). K0 provides the same operation as K1, and the output contact turns on at the first counting.
  • In general type counters, the counter value is cleared when the PLC turns off. In latch type counters, however, the counter value just before power failure is stored (backed up by the battery); The counter value in the subsequent operations can be added to the last counter value.

Specified the Device & Constant

  • Every time the coil C0 is driven by the counting input X011, the current value of the counter increases. When a coil instruction is executed 10 times, the output contact turns on. After that, the current value of the counter does not change even if the counting input X011 turns on after that. When the RST input X010 turns ON and then RST instruction is executed, the current value of the counter is reset to "0" and the output contact returns.

RST C 0

K10

0 1 2 3 4 5 6 7 8 9 10

Set value (constant) It can be specified indirectly also.

Y000

Y000

  • The counter set value can be set by a constant (K) as shown above, or indirectly specified by a data register number. For example, when D10 is specified and the contents of D10 are "123", it is equivalent to "K123".
  • If data beyond the set value is written to the current value register by MOV instruction, etc., the OUT coil turns ON and the current value register becomes the set value when the next counting input is received.
  • For latched (battery backed) type counters, the current value, output contact operation and reset status are backed up against power failure. In FX 3U /FX 3UC PLCs, latched type counters are backed up by the battery built into the PLC. In FX 3S /FX 3G /FX 3GC PLCs, latched type counters are backed up by the EEPROM built into the PLC.

FNC10-FNC19 Move & Compare

→ For details on backup methods against power failure, refer to Section 2.6.

FNC20-FNC29 Arith. & Logic Operation

Show 20 more labels / short text on this page
Introduction · Counting · Counting · Counting · Counting · direction switching · direction switching · direction switching · direction switching · relay · relay · relay · relay · Overview · Instruction List · Devices in Detail · Before Programming · Current value · Basic Instruction · FNC00-FNC09 Program Flow
Page 106 of the Mitsubishi Electronics MELSEC FX3S user manual — C 0 K100
Page 106 · click to enlarge
Page 106

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.6 Counter [C]

2. General type and latched (battery backed) type 32-bit bi-directional counters The valid set range of 32-bit binary bi-directional counters is from − 2,147,483,648 to +2,147,483,647 (decimal constant). The counting direction (up or down) is specified by special auxiliary relays M8200 to M8234.
  • When M8 UUU is driven for C UUU , a counter executes down-counting. When M8 UUU is not driven, a counter executes up-counting. (Refer to the previous page.)
  • The set value (positive or negative) can be specified by a constant (K) or the contents of data registers (D). When data registers are used, 32-bit data composed of paired serial devices are treated as set values. For example, when D0 is specified, D1 and D0 provide a 32-bit set value.
  • When the coil C200 is driven by the counting input X014, a counter starts up-counting or down-counting. When the current value of a counter increases from " − 6" to " − 5", the output contact is set. When the current value decreases from " − 5" to " − 6", the output contact is reset.
Mitsubishi Electronics MELSEC FX3S — 4.6.5 Set value specification method diagram (page 106)
Fig. 36 · 4.6.5 Set value specification method

0 1 2 3 4 5 4 3 2 1 0

−1−2−3−4−5−6−7−8

When output has been already activated. −7−6−5−4−3

Set value (constant) It can be specified indirectly also.

  • The current value increases or decreases regardless of the operation of the output contact. When a counter executes up-counting from "+2,147,483,647", the counter value becomes " − 2,147,483,648". In the same way, when a counter executes down-counting from " − 2,147,483,648", the counter value becomes "+2,147,483,647". (This type of counter is called ring counter.)
  • When the reset input X013 turns ON and then RST instruction is executed, the current value of the counter is reset to "0" and the output contact returns.
  • For latched (battery backed) type counters, the current value, output contact operation and reset status are backed up against power failure. In FX 3U /FX 3UC PLCs, latched type counters are backed up by the battery built into the PLC. In FX 3S /FX 3G /FX 3GC PLCs, latched type counters are backed up by the EEPROM built into the PLC.

→ For details on backup methods against power failure, refer to Section 2.6.

  • A 32-bit counter can be used as a 32-bit data register. 32-bit counters cannot be handled as target devices in 16-bit applied instructions.
  • If data beyond the set value is written to the current value register by DMOV instruction, etc., the counter continues counting and the contact does not change when the next counting input is received.

4.6.5 Set value specification method

1. 16-bit counter

1. Specification by constant (K)
Constant (decimal constant)1 to 32767 100 counts

C 0 K100

2. Indirect specification (D)
Mitsubishi Electronics MELSEC FX3S — C 0 K100 diagram (page 106)
Fig. 37

Counts to the indirectly specified value of the defined data register, previously set by a digital switch. Note that the set value of a latched (battery backed) type register is not held correctly sometimes when the battery voltage becomes low.

Page 107 of the Mitsubishi Electronics MELSEC FX3S user manual — 1. Structure of register storing current value of counter
Page 107 · click to enlarge
Page 107

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.6 Counter [C] 1

2. 32-bit counter

1. Specification by constant (K)
Constant (decimal constant)− 2,147,483,648 to +2,147,483,647 43210 counts

C200 K43,210

2. Indirect specification (D)

X001 FNC 12

Pairs of data registers are used for indirect specification. Use a 32-bit instruction for writing the set value, and make sure that the latter of paired registers (D6 in this example) does not overlap with other programs because it is not shown in ladder format.

DMOV K43210 D5(D6)

C200 D5(D6)

4.6.6 Response speed of counters

Counters execute counting by cyclic operating for contact operations of internal signals X, Y, M, S, C, etc. inside the PLC. For example, when X011 is specified as counting input, its ON duration and OFF duration should be longer than the scan time of the PLC (which is tens of Hz or less usually). On the other hand, high-speed counters described later execute counting as an interrupt processing for specific input, and can execute counting at 5 k to 6 kHz regardless of the scan time.

→ For high-speed counters, refer to Section 4.7 or 4.8.

4.6.7 Handling counters as numeric devices

Specified the Device & Constant

Counters use output contacts operating in accordance with the set value or use the counter value (current value) as numeric data for control. The figure below shows the structure of the current value register of a counter. When a counter number is specified in an operand of an applied instruction in execution, the counter is handled as a device storing 16-bit or 32-bit data in the same way as data register. A 32-bit counter is handled as 32-bit data.

1. Structure of register storing current value of counter

1. 16-bit

Low order 16 bits Available numeric value range 16-bit counter: 0 to 32767 32-bit counter: −2,147,483,648 to +2,147,483,647

1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0

1 2 4 8 16 32 64 128 256 512 1024 2048 4096 8192 16384

Sign 0Positive number 1: Negative number

*1. The sign is valid only when a counter is handled as a substitute for data register.

2. 32-bit

Low order 32 bits

1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0

0 1 0 1

32768 65536 131,072 262,144 524,288 1,048,576 2,097,152 4,194,304 8,388,608 16,777,216 33,554,432 67,108,864 134,217,728 268,435,456 536,870,912 1,073,741,824

1 2 4 8 16 32 64 128 256 512 1024 2048 4096 8192 16384

Sign 0Positive number 1: Negative number

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 13 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · High order · *1 b0 · b15 · Basic Instruction · FNC00-FNC09 Program Flow · High order · b31 · b0
Page 108 of the Mitsubishi Electronics MELSEC FX3S user manual — 4.6.6 Response speed of counters
Page 108 · click to enlarge
Page 108

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.6 Counter [C]

2. Examples in applied instructions For the full use of counters as numeric devices, refer to the explanation of applied instructions later.
Mitsubishi Electronics MELSEC FX3S — 4.6.6 Response speed of counters diagram (page 108)
Fig. 38 · 4.6.6 Response speed of counters

A decimal integer "100" is compared with C30 (current value), and the result is output to M0 to M2.

The contents of C10 (current value) are converted into BCD, and output to Y000 to Y007. (Seven-segment display unit is controlled.)

C5 (current value) is multiplied by 2, and transferred to (D5, D4).

C 200 (current value) is transferred to (D1, D0).

C200 (current value) is compared with a decimal integer zone 100 to 20000, and the result is output to M10 and M12.

*1. Make sure to use 32-bit operation instructions for 32-bit counters.

3. Caution on simultaneous instances of the ZRST instruction and a counter The ZRST instruction resets also the last stage and reset state of T and C coils. Accordingly, if the drive contact of X000 is ON in the following program, the counter executes counting after the ZRST instruction is executed.
Mitsubishi Electronics MELSEC FX3S — 4.6.6 Response speed of counters diagram (page 108)
Fig. 39 · 4.6.6 Response speed of counters

Counting is executed when X000 is ON. OUT instruction

Program in the following way to disable counting after execution of the ZRST instruction:

Mitsubishi Electronics MELSEC FX3S — 4.6.6 Response speed of counters diagram (page 108)
Fig. 40 · 4.6.6 Response speed of counters
Page 109 of the Mitsubishi Electronics MELSEC FX3S user manual — 4. Cautions on counterpart equipment connected to high-speed counter inputs
Page 109 · click to enlarge
Page 109

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.7 High-Speed Counter [C] (FX3S/FX3G/FX3GC PLCs) 1

4.7 High-Speed Counter [C] (FX 3S /FX 3G /FX 3GC PLCs)

4.7.1 Types and device numbers of high-speed counters

1. Types of high-speed counters The main unit has built-in 32-bit high-speed bi-directional counters (1-phase 1-count, 1-phase 2-count and 2-phase 2count). Some high-speed counters are capable of using an external reset input terminal and an external start input terminal (for counting start).
2. Classification of high-speed counters according to counting method These types of counters execute counting as CPU interrupt processing. Observe both the restriction in response frequency for each counter and the restriction in total frequency when using high-speed counters.

→ For the limitation of response frequency depending on the total frequency, refer to Subsection 4.7.7.

3. Types of high-speed counters and input signal forms The table below shows the types (1-phase 1-count, 1-phase 2-count and 2-phase 2-count) and input signals (waveforms) of high-speed counters.

Input signal form Counting direction

Down-count or up-count is specified by turning on or off M8235 to M8245. ON: Down-counting OFF: Up-counting

UP/DOWN

A counter executes up-count or down- count as shown on the left. The counting direction can be checked with M8246 to M8250. ON: Down-counting OFF: Up-counting

UP

−1 −1 −1

Specified the Device & Constant

DOWN

A counter automatically executes up- count or down-count according to changes in the input status of the A/B phase as shown on the left. The counting direction can be checked with M8251 to M8255. ON: Down-counting OFF: Up-counting

−1 −1

4. Cautions on counterpart equipment connected to high-speed counter inputs

General-purpose inputs X000 to X007 are used for high-speed counter inputs. An encoder*1 adopting the output method shown in the table below can be connected depending on the connected terminal. Encoders adopting the voltage output method and absolute encoders cannot be connected to high-speed counter inputs.

→ For the wiring, refer to the Hardware Edition of the main unit.

Output method of encoder which can be directly connected to input terminal in main unit Open collector transistor output method compatible with 24V DC

*1. A rotary encoder adopting the output method shown above may not operate correctly depending on the electrical compatibility. Check the specifications before connecting an encoder.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 18 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · 1-phase 1-count input · +1 +1 +1 · 1-phase 2-count input · A phase · A phase · 2-phase 2-count input · +1 +1 · B phase · B phase · Before Programming · Up-counting · Down-counting · Basic Instruction · FNC00-FNC09 Program Flow
Page 110 of the Mitsubishi Electronics MELSEC FX3S user manual — C248 C248(OP)
Page 110 · click to enlarge
Page 110

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.7 High-Speed Counter [C] (FX3S/FX3G/FX3GC PLCs)

5. High-speed counter device list

Classification Counter No. Data length External reset input terminal

External start input terminal

C235 C236 C237 C238 C239 C240

Not provided Not provided

C241 C242 C243

C244 C245 Provided Provided

C248(OP) *1

Not provided Not provided

C247 C248 Provided Not provided

C249 C250 Provided Provided

C253(OP) *1

Not provided Not provided

C254(OP)*2 32-bit bi-directional

C252 C253 Provided Not provided

C254 C255 Provided Provided

*1. C248 and C253 are usually used as counters having reset input, but can be used as counters C248 (OP) and C253 (OP) not having reset input when used together with special auxiliary relays M8388 and M8392.

→ For the method to switch the counter function, refer to Subsection 4.7.6.

*2. C254 is usually used as a counter having reset input and start input, but can be used as a counter C254 (OP) not having reset input or start input when used together with special auxiliary relays M8388 and M8395. This function is supported only in FX3G/FX3GC PLCs.

→ For the method to switch the counter function, refer to Subsection 4.7.6.

Notation of high-speed counter devices

In some high-speed counters in FX3S/FX3G/FX3GC PLCs, the input terminal assignment is changed over when used together with special auxiliary relays. Such high-speed counter devices are classified below. Note that description as (OP) is not available in programming.

Standard Device Numbers Switched Device Numbers

C248 C248(OP)

C253 C253(OP)

C254 C254(OP)

Show 9 more labels / short text on this page
1-phase 1-count input · 32-bit bi-directional · counter · Provided Not provided · 32-bit bi-directional · 1-phase 2-count input · counter · 2-phase 2-count input · counter
Page 111 of the Mitsubishi Electronics MELSEC FX3S user manual — Restriction to overlap input numbers
Page 111 · click to enlarge
Page 111

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.7 High-Speed Counter [C] (FX3S/FX3G/FX3GC PLCs) 1

4.7.2 Input assignment for high-speed counters

Inputs X000 to X007 are assigned as shown in the table below according to each high-speed counter number. When a high-speed counter is used, the filter constant of a corresponding input number in the main unit automatically changes.

  • FX 3S PLC X000, X001: 10 µ s X002, X003, X004, X005, X006, X007: 50 µ s
  • FX 3G /FX 3GC PLCs X000, X001, X003, X004: 10 µ s X002, X005, X006, X007: 50 µ s Input terminals not used for high-speed counters, however, can be used as general inputs.

→ For the input specifications of the main unit, refer to the Hardware Edition of the main unit.

Counter No. Input terminal assignment

X000 X001 X002 X003 X004 X005 X006 X007

C235 U/D

C236 U/D

C237 U/D

C238 U/D

C239 U/D

C240 U/D

C241 U/D R

C242 U/D R

C243 U/D R

C244 U/D R S

C245 U/D R S

Specified the Device & Constant

C246 U D

C247 U D R

C248 U D R

C248(OP) U D

C249 U D R S

C250 U D R S

C251 A B

C252 A B R

C253 A B R

C253(OP) A B

C254 A B R S

C254(OP) A B

C255 A B R S

U: Up-counting input D: Down-counting input A: A phase input B: B phase input R: External reset input S: External start input

Restriction to overlap input numbers

Inputs X000 to X007 are used for high-speed counters, input interrupt, pulse catch, SPD/ZRN/DSZR instructions and general-purpose inputs. When assigning functions, there should be no overlap between those input terminals.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 10 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · 1-phase 1-count input · 1-phase 2-count input · Before Programming · 2-phase 2-count input · Basic Instruction · FNC00-FNC09 Program Flow
Page 112 of the Mitsubishi Electronics MELSEC FX3S user manual — C235 M8235
Page 112 · click to enlarge
Page 112

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.7 High-Speed Counter [C] (FX3S/FX3G/FX3GC PLCs)

4.7.3 Handling of high-speed counters

High-speed counters in FX3G/FX3GC PLCs operate in the same way as high-speed counters in FX3U/FX3UC PLCs. For details, refer to Subsection 4.8.3.

4.7.4 Current value update timing and comparison of current value

1. Current value update timing When pulses are input to an input terminal for a high-speed counter, the high-speed counter executes up-counting or down-counting. The current values of devices are updated when counting is input.

2. Comparison of the Current value The following two methods are available to compare and output the current value of a high-speed counter. 1) Using the comparison instruction (CMP), zone comparison instruction (ZCP) or comparison contact instruction Use the comparison instruction (CMP), band comparison instruction (ZCP) or contact comparison instruction if the comparison result is necessary at counting. Use these instructions only when high-speed processing is not required because these instructions are processed in the operation cycle of the PLC, and operation delay is generated before the comparison output result is obtained. If it is necessary to execute comparison to update an output contact with the high-speed counter's changing value, use comparison instructions for high-speed counters HSCS, HSCR and HSZ.

2) Using comparison instructions for high-speed counters (HSCS, HSCR or HSZ) The comparison instructions for high-speed counters (HSCS, HSCR and HSZ) execute a comparison and output the comparison result during high-speed counting. These instructions have limitations on the number of simultaneously driven instructions as shown in the following table. When an output relay is specified for the comparison result, the comparison result is directly updated at the ON/ OFF status of the output regardless of the output refresh by END instruction. Mechanical operation delay (about 10 ms) cannot be avoided in a relay output type PLC. Use a transistor output type PLC.

Instruction Limitation in number of instructions driven at same time

HSCS

HSZ

4.7.5 Related devices

1. Devices used to switch the counting direction of 1-phase 1-count input counters

Type Counter No. Specifying device Up-counting Down-counting

C235 M8235

C236 M8236

C237 M8237

C238 M8238

C239 M8239

C240 M8240

OFF ON

C241 M8241

C242 M8242

C243 M8243

C244 M8244

C245 M8245

6 instructions HSCR · 1-phase 1-counting input

Page 113 of the Mitsubishi Electronics MELSEC FX3S user manual — M8388
Page 113 · click to enlarge
Page 113

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.7 High-Speed Counter [C] (FX3S/FX3G/FX3GC PLCs) 1

2. Devices used to check the counting direction of 1-phase 2-count input counters and 2-phase 2-count input counters

Type Counter No. Monitoring device OFF ON

C246 M8246

C247 M8247

C248 M8248

C249 M8249

C250 M8250

C251 M8251

C252 M8252

C253 M8253

C254 M8254

C255 M8255

3. Devices used to switch the high-speed counter function

Device No. Name Description

M8388 Contact for changing function of high-speed counter Changes the function of high-speed counter.

M8392 Function switching device

Switches the function of C248 and C253. (For details, refer to Subsection 4.7.6.)

M8395 Switches the function of C254. (For details, refer to Subsection 4.7.6.)

4.7.6 Assignment of counter input terminal and switching of function

When the counters C248, C253 and C254 are combined with the following special auxiliary relays, the allocation of the input terminals and functions are changed. In a program, put a special auxiliary relay just before a target counter.

Specified the Device & Constant

Counter No. When using assignment of counter input terminal and

switching of function Description

M8388

M8392

C248(OP) • Reset input is not provided.

K {{{

M8388

M8392

C253(OP) • Reset input is not provided.

K {{{

  • The input count (2-phase 2-count) changes as follows: Phase A: Changes from X000 to X006. Phase B: Changes from X001 to X007.
  • Reset input is not provided.
  • Start input is not provided.

M8388

M8395

C254(OP)

K {{{

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 10 more labels / short text on this page
Introduction · 1-phase 2-counting input · Overview · Up-counting Down-counting · 2-phase 2-counting input · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 114 of the Mitsubishi Electronics MELSEC FX3S user manual — In FX 3G /FX 3GC PLCs
Page 114 · click to enlarge
Page 114

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.7 High-Speed Counter [C] (FX3S/FX3G/FX3GC PLCs)

4.7.7 Response frequency of high-speed counters

1. Response frequency and overall frequency When any of the following functions/instructions is used, the overall frequency is restricted regardless of the operand of the instruction. Consider this restriction when examining the system or creating programs, and observe the specified overall frequency range.
  • When two or more high-speed counters are used
  • When the HSCS, HSCR, HSZ, PLSY, PLSR, DSZR, TBL *1 , ZRN, PLSV, DRVI or DRVA instruction is used
  • When the pulse width/pulse period measurement function is used. *1

*1. This function is supported only in FX3G/FX3GC PLCs.

In FX 3S PLC

Overall frequency determined by condition of used instruction

Counter type Response frequency

When HSCS, HSCR or HSZ

When HSCS, HSCR or HSZ instruction is

instruction is not used

C235, C236, C241 60kHz

C237, C238, C239, C240, C242, C243, C244, C245

C247, C248, C248(OP), C249, C250

- Number of positioned axes*2

- Number of positioned axes*2 x 5 kHz

C252, C253, C254, C253(OP), C255 5kHz

*2. Number of axes used in the following positioning instructions: PLSY (FNC 57), PLSR (FNC 59), DSZR (FNC150), ZRN (FNC156), PLSV (FNC157), DRVI (FNC158), DRVA (FNC159)

In FX 3G /FX 3GC PLCs

Overall frequency determined by condition of used instruction

Counter type Response frequency

When HSCS, HSCR or HSZ

When HSCS, HSCR or HSZ instruction is

instruction is not used

C235, C236, C238, C239, C241 60kHz

C237, C240, C242, C243, C244, C245 10kHz

- (Number of positioned axes*3

- (Number of positioned axes*3 x 5 kHz)

C247, C248, C249,C250 10kHz

+ Number of pulse width/period

- (Number of pulse width/period

measurement inputs x 20 kHz)

C252, C253, C254, C254(OP), C255 5kHz

*3. Number of axes used in the following positioning instructions: PLSY (FNC 57), PLSR (FNC 59), DSZR (FNC150), TBL (FNC152), ZRN (FNC156), PLSV (FNC157), DRVI (FNC158), DRVA (FNC159)

2. Calculation of the total frequency Obtain the overall frequency using the following expression:

Total frequency ≥ [(Sum of used frequency of 1-phase counters) + (Sum of used frequency of 2-phase counters)]

Show 21 more labels / short text on this page
used · 1-phase 1-counting input · 10kHz · C246 60kHz · 200 kHz · 1-phase 2-counting input · 60 kHz · 10kHz · x 40 kHz · C251 30kHz · 2-phase 2-counting input · used · 1-phase 1-counting input · 200 kHz · 60 kHz · C246, C248(OP) 60kHz · 1-phase 2-counting input · measurement inputs) · x 40 kHz · 2-phase 2-counting input · C251, C253(OP) 30kHz
Page 115 of the Mitsubishi Electronics MELSEC FX3S user manual — Total 100kHz ≤ 120kHz(Overall frequency)
Page 115 · click to enlarge
Page 115

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.7 High-Speed Counter [C] (FX3S/FX3G/FX3GC PLCs) 1

3. Calculation example Example1: When the HSCS, HSCR or HSZ instruction is not used, and the instructions related to the number of

positioning axes (DRVI instruction [Y000], DRVA instruction [Y001]) are used in the FX3G PLC

Overall frequency200 kHz - (2 axes x 40 kHz) = 120 kHz

C235(1-phase 1-counting) 50 kHz is input.

C236(1-phase 1-counting) 50 kHz is input.

C237(1-phase 1-counting) 10 kHz is input.

C253(2-phase 2-counting) 5 kHz is input.

Total 115kHz ≤ 120kHz(Overall frequency)

Example2: When the HSCS, HSCR or HSZ instruction is not used, and instructions related to the number of

positioning axes (DRVI instruction [Y000]) and the number of pulse width/pulse period measurement inputs [X003] are used in the FX3G PLC

Overall frequency200 kHz - (1 axes + 1 input) x 40 kHz = 120 kHz

C235(1-phase 1-counting) 50 kHz is input.

C236(1-phase 1-counting) 50 kHz is input.

Total 100kHz ≤ 120kHz(Overall frequency)

Specified the Device & Constant

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 7 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 116 of the Mitsubishi Electronics MELSEC FX3S user manual — 4.7.8 Cautions on use
Page 116 · click to enlarge
Page 116

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.7 High-Speed Counter [C] (FX3S/FX3G/FX3GC PLCs)

4.7.8 Cautions on use

  • For a contact to drive the coil of a high-speed counter, use a contact which is normally ON during high-speed counting.
Mitsubishi Electronics MELSEC FX3S — 4.7.8 Cautions on use diagram (page 116)
Fig. 41 · 4.7.8 Cautions on use

Program a contact which is normally ON during counting.

If a number of input relay for counting is specified, high-speed counter cannot execute accurate counting.

  • If the operation of a high-speed counter is triggered by a device such as a switch, the counter may malfunction due to extra noise from switch chattering or contact bounce.
  • The input filter of an input terminal for a high-speed counter in the main unit is automatically set to 10 µ s or 50 µ s. Accordingly, it is not necessary to use special data register D8020 (input filter adjustment). The input filter for input relays not being used for high-speed counters remains at 10 ms (initial value).
  • The inputs X000 to X007 are used for high-speed counters, input interrupt, pulse catch, SPD/DSZR/ZRN instructions and general-purpose inputs. There should be no overlap between each input number.
  • When a counting pulse is not provided, none of the high-speed counter output contacts will turn ON, even if the PLC executes an instruction where "present value = set value".
  • Counting may be started or stopped for a high-speed counter when the output coil (OUT C***) is set to ON or OFF. Program this output coil in the main routine. If the output coil is programmed in a step ladder (SFC) circuit, subroutine or interrupt routine, counting cannot be started or stopped until the step ladder or routine is executed.
  • Make sure that the signal speed for high-speed counters does not exceed the response frequency described above. If an input signal exceeds the response frequency, a WDT error may occur, or the communication functions such as a parallel link may malfunction.
  • The response frequency changes depending on the number of used counters, but the input filter value is fixed to 10 µ s or 50 µ s. Note that noise above the response frequency may be counted depending on the filter value of the used input.
  • When a high-speed counter is reset by the RST instruction, it cannot count until the RST instruction is set to OFF.
1. Program example

RST C235 C235 is reset while X010 turns ON.

2. Timing chart
Mitsubishi Electronics MELSEC FX3S — 4.7.8 Cautions on use diagram (page 116)
Fig. 42 · 4.7.8 Cautions on use

Current value of C235 1 2 3 The current value does not change even if pulses are input because the C235 reset instruction is valid.

"RST C235" is set to ON because the contact turns ON.

"RST C235" is set to OFF because the contact turns OFF.

Page 117 of the Mitsubishi Electronics MELSEC FX3S user manual — RST C235
Page 117 · click to enlarge
Page 117

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.7 High-Speed Counter [C] (FX3S/FX3G/FX3GC PLCs) 1

  • Write the following program to "reset only the current value of a high-speed counter (and does not turn OFF the contact)".
1. Program example

X010 *1

FNC 12 DMOV K0 C235 The current value of C235 is cleared (to "0").

*1. When the driving contact is the continuous execution type, the current value of the counter is reset to "0" at each scan while X010 remains ON.

2. Timing chart

Current value of C235 1 2 3

Because X010 turns ON, "FNC 12 DMOV" is executed. The current value of C235 is reset to "0".

Because the driving contact is the pulse execution type, C235 executes counting normally after that.

  • Write the following program to "turn OFF the contact and reset the current value of a high-speed counter".
1. Program example

Specified the Device & Constant

X010 *2

RST C235 - - - - - A

M8001

RST C235 - B RUN Monitor (normally OFF)

*2. When the driving contact is the continuous execution type, the current value of the counter is reset to "0" and the counter reset status is cleared at each scan while X010 remains ON.

2. Timing chart

1 2 3 4

Current value of C235 1 2 3

Because the reset instruction is deactivated, C235 executes counting.

RST C235

Counter reset instruction is deactivated (part B in above program).

Counter is reset (part A in above program).

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 7 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 118 of the Mitsubishi Electronics MELSEC FX3S user manual — 4. Cautions on counterpart equipment connected to high-speed counter inputs
Page 118 · click to enlarge
Page 118

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.8 High-Speed Counter [C] (FX3U/FX3UC PLC)

4.8 High-Speed Counter [C] (FX 3U /FX 3UC PLC)

High-speed counter only available in DC input type main units.

4.8.1 Types and device numbers of high-speed counters

1. Types of high-speed counters The main unit has built-in 32-bit high-speed bi-directional counters (1-phase 1-count, 1-phase 2-count and 2-phase 2count). These high-speed counters are classified into hardware type or software type according to the counting method. Some high-speed counters are capable of using an external reset input terminal and an external start input terminal (for counting start).

2. Classification of high-speed counters according to counting method

  • Hardware counters: These types of counters execute counting by hardware, but may be switched to software counters depending on the operating condition.

→ For the condition handled as software counters, refer to Subsection 4.8.9.

  • Software counters: These types of counters execute counting as CPU interrupt processing. It is necessary to use each software counter within both limitations of maximum response frequency and total frequency. → For the limitation of response frequency depending on the total frequency, refer to Subsection 4.8.10.
3. Types of high-speed counters and input signal forms The table below shows the types (1-phase 1-count, 1-phase 2-count and 2-phase 2-count) and input signals (waveforms) of high-speed counters.
Mitsubishi Electronics MELSEC FX3S — 2. Classification of high-speed counters according to counting method diagram (page 118)
Fig. 43 · 2. Classification of high-speed counters according t…

Down-count or up-count is specified by turning on or off M8235 to M8245. ON: Down-counting OFF: Up-counting

A counter executes up-count or down- count as shown on the left. The counting direction can be checked with M8246 to M8250. ON: Down-counting OFF: Up-counting

1 edge count A counter automatically executes up- count or down-count according to changes in the input status of the A/B phase as shown on the left. The counting direction can be checked with M8251 to M8255. ON: Down-counting OFF: Up-counting

4. Cautions on counterpart equipment connected to high-speed counter inputs

General-purpose inputs X000 to X007 are used for high-speed counter inputs. An encoder*1 adopting the output method shown in the table below can be connected depending on the connected terminal. Encoders adopting the voltage output method and absolute encoders cannot be connected to high-speed counter inputs.

→ For the wiring, refer to the Hardware Edition of the main unit.

Output method of encoder which can be directly connected to input terminal in main unit Open collector transistor output method compatible with 24V DC

Output method of encoder which can be directly connected to input terminal in FX3U-4HSX-ADP

Differential line driver output method (output voltage: 5V DC or less)

*1. A rotary encoder adopting the output method shown above may not operate correctly depending on the electrical compatibility. Check the specifications before connecting an encoder.

Page 119 of the Mitsubishi Electronics MELSEC FX3S user manual — C244 C244(OP) C248 C248(OP)
Page 119 · click to enlarge
Page 119

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.8 High-Speed Counter [C] (FX3U/FX3UC PLC) 1

5. High-speed counter device list

Classification Counter No. Edge count Data length External reset input terminal

External start input terminal

C235 *2

C236 *2

C237 *2

C238 *2

Not provided Not provided

C239 *2

C240 *2

C244(OP) *3

C245(OP) *3 −

C241 C242 C243

− Provided*5 Not provided

C244 *3

C245*3 − Provided*5 Provided

Hardware counter*1 C246*2

C248(OP) *2*3 −

Not provided Not provided

C248*3 − Provided*5 Not provided

C249 C250 − Provided*5 Provided

C251 *2 1 *4

Not provided 4*4

C253*2 1*4 Provided*5 4*4

C252 1*4 Provided*5

Not provided 4*4

Specified the Device & Constant

C253(OP)*6 1*4 Not provided 4*4

C254 C255

1*4 Provided*5 Provided 4*4

*1. They are handled as software counters depending on the operating condition. When they are handled as software counters, they have limitations on both maximum response frequency and total frequency.

→ For the condition handled as software counters, refer to Subsection 4.8.9.

→ For the total frequency, refer to Subsection 4.8.10.

*2. Cautions on wiring should be considered for these high-speed counters.

→ For the wiring, refer to the Hardware Edition of the main unit.

*3. C244, C245 and C248 are usually used as software counters, but can be used as hardware counters C244 (OP), C245 (OP) and C248 (OP) by combining a special auxiliary relay (M8388, M8390 to M8392).

→ For the method to switch the counter function, refer to Subsection 4.8.7.

*4. 2-phase 2-input counter is usually 1 edge count counter, but can be used as a 4 edge count counter by combining a special auxiliary relay (M8388, M8198 or M8199).

→ For the method to use a 2-phase 2-input 4 edge count counter, refer to Subsection 4.8.8.

*5. The external reset input is usually reset by turning ON, but can be changed to be reset by turning OFF by combining special auxiliary relays (M8388 and M8389).

→ For the method to change the logic of the external reset input, refer to Subsection 4.8.6.

*6. The counter C253 is usually used as a hardware counter, but can be used as the counter C253 (OP) not equipped with reset input by combining special auxiliary relays (M8388 and M8392). In this case, C253 (OP) is handled as a software counter.

Notation of high-speed counter devices

For some high-speed counters in FX3U and FX3UC PLCs, the assignment of input terminals will switch when special auxiliary relays are used. Such high-speed counter devices are classified below. Note that description as (OP) is not available in programming.

FNC10-FNC19 Move & Compare

Standard Device Numbers Switched Device Numbers Standard Device Numbers Switched Device Numbers

C244 C244(OP) C248 C248(OP)

C245 C245(OP) C253 C253(OP)

FNC20-FNC29 Arith. & Logic Operation

Show 23 more labels / short text on this page
Introduction · − · Hardware counter*1 · Overview · 32-bit bi-directional · 1-phase 1-count input · counter · Software counter · Instruction List · 32-bit bi-directional · 1-phase 2-count input · counter · Software counter · Devices in Detail · Not provided · Hardware counter*1 · 32-bit bi-directional · 2-phase 2-count input · counter · Software counter · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 120 of the Mitsubishi Electronics MELSEC FX3S user manual — 4.8.2 Input assignment for high-speed counters
Page 120 · click to enlarge
Page 120

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.8 High-Speed Counter [C] (FX3U/FX3UC PLC)

4.8.2 Input assignment for high-speed counters

Inputs X000 to X007 are assigned as shown in the table below according to each high-speed counter number. When a high-speed counter is used, the filter constant of a corresponding input number in the main unit automatically changes (X000 to X005: 5 µs, X006 and X007: 50 µs). Input terminals not used for high-speed counters, however, can be used as general inputs. When FX3U-4HSX-ADP unit is connected to an FX3U PLC, input terminals inside bold-line frames in the table below are assigned to the first FX3U-4HSX-ADP unit, and other input terminals are assigned to the second FX3U-4HSX-ADP unit.

→ For the input specifications of the FX3U-4HSX-ADP, refer to the FX3U Hardware Edition. → For the input specifications of the main unit, refer to the Hardware Edition of the main unit.

Mitsubishi Electronics MELSEC FX3S — 4.8.2 Input assignment for high-speed counters diagram (page 120)
Fig. 44 · 4.8.2 Input assignment for high-speed counters

H/W: Hardware counter S/W: Software counter U: Up-counting input D: Down-counting input A: A phase input B: B phase input R: External reset input S: External start input

*1. Cautions on wiring should be considered for these high-speed counters.

→ For the wiring, refer to the Hardware Edition of the main unit.

*2. Hardware counters are switched to software counters when a comparison set/reset instruction for high-speed counter (DHSCS, DHSCR, DHSZ or DHSCT) is used. The counter C253 is switched to a software counter when the logic of the external reset input signal is reversed.

→ For the condition under which it is handled as a software counter, refer to Subsection 4.8.9.

*3. When a special auxiliary relay is driven in a program, the input terminals and their associated functions are switched.

→ For the method to use a software counter as a hardware counter, refer to Subsection 4.8.7.

*4. In a 2-phase 2-count input counter, the edge count is usually 1. But the edge count can be set to 4 by combining a special auxiliary relay.

→ For the method on how to use a 2-phase 2-count input counter with on edge count of 4,

refer to Subsection 4.8.8.

Page 121 of the Mitsubishi Electronics MELSEC FX3S user manual — C244 D0(D1)
Page 121 · click to enlarge
Page 121

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.8 High-Speed Counter [C] (FX3U/FX3UC PLC) 1

Restriction to overlap input numbers

  • Inputs X000 to X007 are used for high-speed counters, input interrupt, pulse catch, SPD/ZRN/DSZR/DVIT instructions and general-purpose inputs. When assigning functions, there should be no overlap between those input terminals.
  • Since the FX 3U -4HSX-ADP and FX 3UC PLC main unit share the same assigned input terminal numbers, only one of them may be used in operation. If both input terminals are used, intended operation is not enabled because the inputs of the FX 3U -4HSX-ADP and PLC main unit operate in an "OR" relationship.

4.8.3 Handling of high-speed counters

1. 1-phase 1-count input

  • C235 counts "OFF → ON" of the input X000 while X012 is ON.
  • When X011 turns ON and then RST instruction is executed, C235 is reset.
  • The counting direction of the counters C235 to C245 is switched to down-count or up-count when M8235 to M8245 turns ON or OFF.

C235 K-5

  • C244 immediately starts counting when the input X006 turns ON while X012 is ON. The counting input is X000. In this example, the set value is indirectly specified by the contents of data registers (D1 and D0).
  • A high-speed counter can be reset using X011 in a sequence as shown in the figure, but C244 immediately reset without any program when X001 is closed. So a program with X011 is not necessary.
  • The counting direction of the counters C235 to C245 is switched to down-count or up-count when M8235 to M8245 turns ON or OFF.

Specified the Device & Constant

C244 D0(D1)

Set value is (D1, D0)

Operation example The counter C235 shown above operates as follows:

Up counting Down counting Up counting

0 1 2 3 4 5 4 3 2 1 0

−1−2−3−4−5−6−7−8

When output has already been activated

−4−3

−7−6−5

When counting with input X000, C235 executes up-count or down-count as an interrupt.

  • When the current value of a counter increases from " − 6" to " − 5", the output contact is set. When the current value decreases from " − 5" to " − 6", the output contact is reset.
  • The current value increases or decreases regardless of the operation of the output contact. When a counter executes up-count from "+2,147,483,647", the counter value becomes " − 2,147,483,648". In the same way, when a counter executes down-count from " − 2,147,483,648", the counter value becomes "+2,147,483,647". (This type of counter is called a ring counter.)
  • When the reset input X011 turns ON and RST instruction is executed, the current value of the counter is reset to "0" and the output contact is restored.
  • In a latch type high-speed counter, the current value, output contact operation and reset status of the counter are latched (battery backed) by the backup battery built in the PLC.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 16 more labels / short text on this page
Introduction · Overview · M8235 Down/up count · Instruction List · RST C235 Reset · Devices in Detail · M8244 Down/up count · RST C244 Reset · Before Programming · Reset input · Start input · Basic Instruction · Counting input · C235 Current value · FNC00-FNC09 Program Flow · C235 output contact
Page 122 of the Mitsubishi Electronics MELSEC FX3S user manual — 4.8.3 Handling of high-speed counters
Page 122 · click to enlarge
Page 122

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.8 High-Speed Counter [C] (FX3U/FX3UC PLC)

2. 1-phase 2-count input These counters are 32-bit binary bi-directional counters, and the operation of the output contact for the current value is equivalent to that in 1-phase 1-count input type high-speed counters described above.
Mitsubishi Electronics MELSEC FX3S — 4.8.3 Handling of high-speed counters diagram (page 122)
Fig. 45 · 4.8.3 Handling of high-speed counters
  • While X012 is ON, C246 executes up-count when the input X000 turns from OFF to ON, and executes down-count when the input X001 turns from OFF to ON.
  • The up/down-count operation of C246 to C250 can be checked with M8246 to M8250. ON status: Down-counting OFF status: Up-counting
  • While X012 is ON, C249 immediately starts counting when the input X006 turns ON. The up-count input is X000, and the down-count input is X001.
  • A high-speed counter can be reset by X011 in a sequence as shown in the figure, but C249 is immediately reset without any program when X002 is closed. So a program with X011 is not necessary.
  • The up/down-count operation of C246 to C250 can be checked with M8246 to M8250. ON status: Down-counting OFF status: Up-counting
3. 2-phase 2-count input These counters are 32-bit binary bi-directional counters, and the operation of the output contact for the current value is equivalent to that in 1-phase high-speed counters described above.
  • While X012 is ON, C251 counts the operation of the inputs X000 (A phase) and X001 (B phase) as interrupt. When X011 turns ON a RST instruction is executed and C251 is reset.
Mitsubishi Electronics MELSEC FX3S — 4.8.3 Handling of high-speed counters diagram (page 122)
Fig. 46 · 4.8.3 Handling of high-speed counters
  • When the current value becomes equivalent to or larger than the set value, Y002 turns ON. When the current value becomes equivalent to or smaller than the set value, Y002 turns OFF.
  • Y003 turns ON (for down-count) or OFF (for up-count) according to the counting direction.
  • When X006 turns ON while X012 is ON, C254 immediately starts counting. Its counting inputs are X000 (A phase) and X001 (B phase).
  • In addition to reset by X011 in a sequence, C254 is reset immediately when X002 turns ON.
  • When the current value becomes equivalent to or larger than the set value (D1, D0), Y004 turns ON. When the current value becomes equivalent to or smaller than the set value, Y004 turns OFF.
  • Y005 turns ON (for down-count) or OFF (for up-count) according to the counting direction.
Page 123 of the Mitsubishi Electronics MELSEC FX3S user manual — HSZ *2
Page 123 · click to enlarge
Page 123

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.8 High-Speed Counter [C] (FX3U/FX3UC PLC) 1

  • A 2-phase encoder generates outputs for the A phase and B phase by a phase difference of 90 ° . With these outputs, a high-speed counter automatically executes up-count and down-count as shown in the figure below. - When the counter is operating at the 1 edge count

−1 −1

- When the counter is operating at the 4 edge count

+1

−1

+1

−1

  • The down/up-count operation of C251 to C255 can be checked with M8251 to M8255. ON status: Down-counting OFF status: Up-counting

4.8.4 Current value update timing and comparison of current value

1. Current value update timing A high-speed counter executes up-count or down-count when a pulse is input to its input terminal, but the current value is updated at the timing shown in the table below. When using the current value of a hardware counter in a MOV, CMP or applied instruction such as the comparison instruction, special care must be taken since the current value update timing is affected by the ladder scans as shown in the table.

Current value update timing

Hardware counter When OUT or HCMOV instruction is executed for the counter

Specified the Device & Constant

Software counter Every time a pulse is input

2. Comparison of the Current value The following two methods are available to compare and output the current value of a high-speed counter. 1) Using the comparison instruction (CMP), zone comparison instruction (ZCP) or comparison contact instruction When the comparison result is necessary during counting operation *1 , comparison may be executed in the main program if the HCMOV instruction is used just before the comparison instruction (CMP or ZCP) or comparison contact instruction.

*1. If it is necessary to execute comparison to update an output contact with the high-speed counter's changing value, use comparison instructions for high-speed counters (HSCS, HSCR, HSZ or HSCT).

2) Using comparison instructions for high-speed counters (HSCS, HSCR, HSZ or HSCT) The comparison instructions for high-speed counters (HSCS, HSCR, HSZ and HSCT) execute a comparison and output the comparison result during high-speed counting. These instructions have limitations on the number of simultaneously driven instructions as shown in the following table. The HSCT instruction can only be used once in any program. When an output relay is specified for the comparison result, the comparison result is directly updated at the ON/ OFF status of the output regardless of the output refresh by END instruction. Mechanical operation delay (about 10 ms) cannot be avoided in a relay output type PLC. Use a transistor output type PLC.

Instruction Limitation in number of instructions driven at same time

HSCS

32 instructions including HSCT instruction HSCR

HSZ *2

HSCT*2 Only 1 (This instruction can only be used once.)

*2. When HSZ or HSCT instruction is used, the maximum response frequency and total frequency of all software counters are affected.

FNC10-FNC19 Move & Compare

→ For the maximum response frequency and total frequency of software counters,

refer to Subsection 4.8.10.

FNC20-FNC29 Arith. & Logic Operation

Show 22 more labels / short text on this page
Introduction · A phase · A phase · +1 +1 · B phase · B phase · Up-counting · Down-counting · Overview · +1 · −1 · A phase · A phase · B phase · B phase · Up-counting · Down-counting · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 124 of the Mitsubishi Electronics MELSEC FX3S user manual — M8380 *1
Page 124 · click to enlarge
Page 124

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.8 High-Speed Counter [C] (FX3U/FX3UC PLC)

4.8.5 Related devices

1. Devices used to switch the counting direction of 1-phase 1-count input counters

Type Counter No. Specifying device Up-counting Down-counting

C235 M8235

C236 M8236

C237 M8237

C238 M8238

C239 M8239

C240 M8240

OFF ON

C241 M8241

C242 M8242

C243 M8243

C244 M8244

C245 M8245

2. Devices used to check the counting direction of 1-phase 2-count input counters and 2-phase 2-count input counters

Type Counter No. Monitoring device OFF ON

C246 M8246

C247 M8247

C248 M8248

C249 M8249

C250 M8250

C251 M8251

C252 M8252

C253 M8253

C254 M8254

C255 M8255

3. Devices used to switch the high-speed counter function

Device No. Name Description

M8388 Contact for changing function of high-speed counter Changes the function of high-speed counter.

M8389

Switches the logic of the external reset input. (For details, refer to Subsection 4.8.6.)

M8390 Switches the function of C244. (For details, refer to Subsection 4.8.7.)

M8391 Switches the function of C245. (For details, refer to Subsection 4.8.7.)

M8392 Switches the function of C248 and C253. (For details, refer to Subsection 4.8.7.)

M8198 Switches the edge count (between 1 and 4) of C251, C252 and C254. (For details, refer to Subsection 4.8.8.)

M8199 Switches the edge count (between 1 and 4) of C253, C255 and C253 (OP). (For details, refer to Subsection 4.8.8.)

4. Operation status of hardware counters and software counters

Device No. Name Description ON OFF

M8380 *1

Operation status of C235, C241, C244, C246, C247, C249, C251, C252 or C254

M8381*1 Operation status of C236

M8382*1 Operation status of C237, C242 or C245

M8383*1 Operation status of C238, C248, C248(OP), C250, C253 or C255

M8384*1 Operation status of C239 or C243

M8385*1 Operation status of C240

M8386*1 Operation status of C244(OP)

M8387*1 Operation status of C245(OP)

*1. Cleared when the PLC mode switches from STOP to RUN.

Show 7 more labels / short text on this page
1-phase 1-counting input · 1-phase 2-counting input · Up-counting Down-counting · 2-phase 2-counting input · Function switching device · Operation status flag · Software counter Hardware
Page 125 of the Mitsubishi Electronics MELSEC FX3S user manual — K {{{
Page 125 · click to enlarge
Page 125

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.8 High-Speed Counter [C] (FX3U/FX3UC PLC) 1

4.8.6 Changing the logic of external reset input signal

The counters C241 to C245, C247 to C250 and C252 to C255 are usually reset when the external reset input turns ON. By using the program shown below, the logic can be inverted so that these counters are reset when the external reset input turns OFF.

Counter No. When inverting logic of external reset input signal Description

M8388

C241 to C245 C247 to C250 C252 to C255

M8389

The logic of the external reset input is inverted so that the counters are reset when the input turns OFF. (The logic is inverted for all target counters.)

K {{{

Caution

The counter C253 is switched to a software counter when the logic of the external reset input signal is inverted.

4.8.7 Assignment of counter input terminal and switching of function

The assignment of the input terminal and the function of the software counters C244, C245, C248 and C253 are changed as shown below when combined with the following special auxiliary relays. In a program, put a special auxiliary relay just before a target counter.

Counter No. When using software counter as hardware counter Description

M8388

  • The counting input is changed from X000 to X006.
  • Reset input is not provided.
  • Start input is not provided.
  • It operates as a hardware counter.

M8390

C244(OP)

K {{{

Specified the Device & Constant

M8388

  • The counting input is changed from X002 to X007.
  • Reset input is not provided.
  • Start input is not provided.
  • It operates as a hardware counter.

M8391

C245(OP)

K {{{

M8388

M8392

  • C248(OP)
  • Reset input is not provided.
  • It operates as a hardware counter.

K {{{

M8388

M8392

  • C253(OP)
  • Reset input is not provided.
  • It operates as a software counter.

K {{{

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 7 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 126 of the Mitsubishi Electronics MELSEC FX3S user manual — 4.8.8 How to use 2-phase 2-count input counters C251 to C255 with 4 edge counting
Page 126 · click to enlarge
Page 126

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.8 High-Speed Counter [C] (FX3U/FX3UC PLC)

4.8.8 How to use 2-phase 2-count input counters C251 to C255 with 4 edge counting

For the 2-phase 2-count input counters C251 to C255, the edge count is usually set to 1. By using the programs shown in the table below, the edge count may be set to 4.

Mitsubishi Electronics MELSEC FX3S — 4.8.8 How to use 2-phase 2-count input counters C251 to C255 with 4 edge counting diagram (page 126)
Fig. 47 · 4.8.8 How to use 2-phase 2-count input counters C251…

Counter No. When using 2-phase 2-count input counters with 4 edge

Page 127 of the Mitsubishi Electronics MELSEC FX3S user manual — M8388
Page 127 · click to enlarge
Page 127

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.8 High-Speed Counter [C] (FX3U/FX3UC PLC) 1

4.8.9 Conditions for hardware counters to be handled as software counters

High-speed counters are classified into hardware counters and software counters. In some conditions, however, hardware counters are handled as software counters. In this case, use hardware counters within the range of maximum response frequency and total frequency as determined for software counters.

Conditions under which counters are handled as software counters

Hardware counter No. Condition in which hardware counters are handled as software counters

Because hardware counters execute counting at the hardware level of the FX3U/FX3UC, they can execute counting regardless of the total frequency. However, when hardware counters are handled as software counters with the following conditions, their maximum response frequency and total frequency are limited in the same way as the software counters. Use M8380 to M8387 to verify that high-speed counters are handled as hardware counters or software counters. • When DHSCS (FNC 53), DHSCR (FNC 54), DHSZ (FNC 55) or DHSCT (FNC280) instruction is used for a hardware counter number, the hardware counter is handled as a software counter. Example: C235

K {{{

C235 C236 C237 C238 C239 C240 C244(OP) C245(OP) C246 C248(OP) C251 C253

DHSCS K100 C235 Y000

In this case, C235 is handled as a software counter.

  • When an index register is used for a counter number specified in DHSCS (FNC 53), DHSCR (FNC 54), DHSZ (FNC 55) or DHSCT (FNC280) instruction, all hardware counters are handled as software counters. Example: C235Z0

Specified the Device & Constant

DHSCS K100 C235Z0 Y000

  • C253 (hardware counter) is handled as a software counter by inverting the logic using the external reset input signal logic changing function. Example: The logic of the C253 external reset input signal is inverted.

→For logic inversion of the external reset input signal, refer to Subsection 4.8.6.

M8388

M8389

K {{{

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 7 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 128 of the Mitsubishi Electronics MELSEC FX3S user manual — C251, C253
Page 128 · click to enlarge
Page 128

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.8 High-Speed Counter [C] (FX3U/FX3UC PLC)

4.8.10 Response frequency of high-speed counters

1. Response frequency of hardware counters The table below shows the maximum response frequency of hardware counters. When hardware counters are handled as software counters in some operating conditions, their maximum response frequency becomes equivalent to that of software counters, and thus hardware counters are some times subject to restrictions in total frequency.

→ For the conditions in which hardware counters are handled as software counters,

refer to the previous page.

Counter type Counter No.

Main unit FX3U-4HSX-ADP

1-phase 1-counting input C235, C236, C237, C238, C239, C240 100 kHz

200 kHz C244(OP), C245(OP) 10 kHz

1-phase 2-counting input C246, C248(OP) 100 kHz

1 edge count C251, C253

50 kHz 100 kHz

4 edge count 50 kHz 100 kHz

2. Response frequency and total frequency of software counters The table below shows the maximum response frequency and total frequency of software counters. When using the HSZ or HSCT instruction in a program, both the maximum response frequency and the total frequency are limited for all software counters without regarding the operands of the instruction. When examining a system or creating a program, consider the limitations, and use software counters within the allowable range of maximum response frequency and total frequency.

→ For the conditions handled as software counters, refer to the previous page.

1. When special analog adapters and FX 3U /FX 3UC Series special function units/blocks are not used

Response frequency and total frequency according to instructions used

When HSZ and HSCT

When only HSCT instruction is used

When only HSZ instruction is used

When both HSZ and HSCT

software counter with HSCS, HSCR,

C241, C242, C243, C244, C245

C235, C236, C237, C238, C239, C240

− C244(OP), C245(OP) × 1 10 10

40. (Number of instruc-

80− 1.5×(Num ber of instruc-

60− 1.5×(Num ber of instruc-

C247, C248, C249, C250

C246, C248(OP) × 1 40 30

1 edge count C252, C253(OP), C254, C255

×1 40 30

C251, C253

4 edge count ×4 10 7.5

ber of instruc- tion) ÷ 4

*1. When an index register is added to a counter number specified by a HSCS, HSCR, HSZ or HSCT instruction, all hardware counters are switched to software counters.

*2. The high-speed counters C244 (OP) and C245 (OP) can count up to 10 kHz.

Show 48 more labels / short text on this page
Maximum response frequency · 2-phase 2-counting input · Following · Magnifica- · instructions are not · tion for calculating · used · instructions are used · Counter type Software · total frequency · Maximum · Maximum · Maximum · Maximum · counter · Total frequency · Total frequency · Total frequency · Total frequency · HSZ or HSCT · response frequency · response frequency · response frequency · response frequency · instruction*1 · (kHz) · (kHz) · (kHz) · (kHz) · (kHz) · (kHz) · (kHz) · (kHz) · ×1 40 · 1-phase 1-counting input · 30-(Number of instruc- · 1-phase 2-counting input · tion)*2 · tion)*2 · tion) · tion) · 2- phase · 2- count- · (40-Num- · (30-Number · ing input · of instruc- · tion) ÷ 4
Page 129 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Calculation of the total frequency
Page 129 · click to enlarge
Page 129

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.8 High-Speed Counter [C] (FX3U/FX3UC PLC) 1

2. When special analog adapters and FX 3U /FX 3UC Series special function units/blocks are used

Response frequency and total frequency according to instruction use condition

When HSZ and HSCT

When only HSCT instruction is used

When only HSZ instruction is used

When both HSZ and HSCT

software counter with HSCS, HSCR,

C241, C242, C243, C244, C245

C235, C236, C237, C238, C239, C240

30. (Number of instruc-

− C244(OP), C245(OP) × 1 10 10

50− 1.5×(Num ber of instruc-

50− 1.5×(Num ber of instruc-

1-phase 2-counting input C247, C248, C249, C250

C246, C248(OP) × 1 30 25

1 edge count C252, C253(OP), C254, C255

×1 30 25

C251, C253

4 edge count ×4 7.5 6.2

ber of instruc- tion) ÷ 4

*1. When an index register is added to a counter number specified by a HSCS, HSCR, HSZ or HSCT instruction, all hardware counters are switched to software counters.

*2. The high-speed counters C244 (OP) and C245 (OP) can count up to 10 kHz.

3. Calculation of the total frequency

Total frequency ≥ Sum of "Response frequency of high-speed counter × Magnification for calculating total frequency"

Specified the Device & Constant

4. Calculation example When only HSZ instruction is used 6 times in a program, the total frequency and response frequency are calculated as follows in accordance with the columns for "When only HSZ instruction is used" shown above. This calculation example is provided for a system configuration not including special analog adapters and FX 3U /FX 3UC Series special function units/blocks.

Used high-speed counter No. Input frequency

C237 Operates as software counter 30 kHz 40 − 6 (times) = 34 kHz × 1

HSZ instruction × 6

20 kHz 40 − 6(times) = 34 kHz × 1

C253(OP) [4 edge count] 4 kHz {40 − 6(times)} ÷ 4 = 8.5 kHz × 4

1. The total frequency is calculated as follows because HSZ instruction is used 6 times: Total frequency = 80 − 1.5 × 6 = 71 kHz 2) The sum of the response frequencies of the high-speed counters being used is calculated as follows: "30 kHz × 1[C237]" + "20 kHz × 1[C241]" + "4kHz × 4[C253(OP)]" = 66 kHz ≤ 71 kHz

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 61 more labels / short text on this page
Introduction · Counter type · Magnifica- · Following · instructions are not · tion for calculating · used · instructions are used · Software · counter · total frequency · Maximum · Maximum · Maximum · Maximum · response frequency · Total frequency · response frequency · Total frequency · response frequency · Total frequency · response frequency · Total frequency · HSZ or HSCT · instruction*1 · (kHz) · (kHz) · (kHz) · (kHz) · (kHz) · (kHz) · (kHz) · (kHz) · Overview · ×1 30 · 1-phase 1-counting input · 25-(Number of instruc- · tion)*2 · tion)*2 · Instruction List · 2- phase · tion) · tion) · (30-Num- · 2- count- · (25-Number · ing input · of instruc- · tion) ÷ 4 · Devices in Detail · Magnification for · Before Programming · Maximum response frequency · Used instruction · calculating total · calculation · frequency · times C241 · Software counter · Basic Instruction · FNC00-FNC09 Program Flow
Page 130 of the Mitsubishi Electronics MELSEC FX3S user manual — 4.8.11 Cautions on use
Page 130 · click to enlarge
Page 130

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.8 High-Speed Counter [C] (FX3U/FX3UC PLC)

4.8.11 Cautions on use

  • For a contact to drive the coil of a high-speed counter, use a contact which is normally ON during high-speed counting.
Mitsubishi Electronics MELSEC FX3S — 4.8.11 Cautions on use diagram (page 130)
Fig. 48 · 4.8.11 Cautions on use

Program a contact which is normally ON during counting.

If a number of input relay for counting is specified, high-speed counter cannot execute accurate counting.

  • If the operation of a high-speed counter is triggered by a device such as a switch, the counter may malfunction due to extra noise from switch chattering or contact bounce.
  • The input filter of an input terminal for a high-speed counter in the main unit is automatically set to 5 µ s (X000 to X005) or 50 µ s (X006 and X007). Accordingly, it is not necessary to use the REFF instruction or special data register D8020 (input filter adjustment). The input filter for input relays not being used for high-speed counters remains at 10 ms (initial value).
  • The inputs X000 to X007 are used for high-speed counters, input interrupt, pulse catch, SPD/DSZR/DVIT/ZRN instructions and general-purpose inputs. There should be no overlap between each input number.
  • When a counting pulse is not provided, none of the high-speed counter output contacts will turn ON, even if the PLC executes an instruction where "present value = set value".
  • Counting may be started or stopped for a high-speed counter when the output coil (OUT C***) is set to ON or OFF. Program this output coil in the main routine. If the output coil is programmed in a step ladder (SFC) circuit, subroutine or interrupt routine, counting cannot be started or stopped until the step ladder or routine is executed.
  • Make sure that the signal speed for high-speed counters does not exceed the response frequency described above. If an input signal exceeds the response frequency, a WDT error may occur, or communication functions such as a parallel link may malfunction.
  • The response frequency changes depending on number of used counters, but the input filter value is fixed to 5 µ s (X000 to X005) or 50 µ s (X006 and X007). Note that noise above the response frequency may be counted depending on the filter value of the used input.
  • When a high-speed counter is reset by the RST instruction, it cannot count until the RST instruction is set to OFF.
1. Program example

RST C235 C235 is reset while X010 turns ON.

RST C235 C235 is reset while X010 turns ON.

2. Timing chart
Mitsubishi Electronics MELSEC FX3S — 4.8.11 Cautions on use diagram (page 130)
Fig. 49 · 4.8.11 Cautions on use

Current value of C235 1 2 3 The current value does not change even if pulses are input because the C235 reset instruction is valid.

"RST C235" is set to ON because the contact turns ON.

"RST C235" is set to OFF because the contact turns OFF.

Page 131 of the Mitsubishi Electronics MELSEC FX3S user manual — RST C235
Page 131 · click to enlarge
Page 131

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.8 High-Speed Counter [C] (FX3U/FX3UC PLC) 1

  • Write the following program to "reset only the current value of a high-speed counter (and does not turn OFF the contact)".
1. Program example

X010 *1

FNC 12 DMOV K0 C235 The current value of C235 is cleared (to "0").

*1. When the driving contact is the continuous execution type, the current value of the counter is reset to "0" at each scan while X010 remains ON.

2. Timing chart

Current value of C235 1 2 3

Because X010 turns ON, "FNC 12 DMOV" is executed. The current value of C235 is reset to "0".

Because the driving contact is the pulse execution type, C235 executes counting normally after that.

  • Write the following program to "turn OFF the contact and reset the current value of a high-speed counter".
1. Program example

Specified the Device & Constant

X010 *2

RST C235 - - - - - A

M8001

RST C235 - B RUN Monitor (normally OFF)

*2. When the driving contact is the continuous execution type, the current value of the counter is reset to "0" and the counter reset status is cleared at each scan while X010 remains ON.

2. Timing chart

1 2 3 4

Current value of C235 1 2 3

Because the reset instruction is deactivated, C235 executes counting.

RST C235

Counter reset instruction is deactivated (part B in above program).

Counter is reset (part A in above program).

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 7 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 132 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. FX 3U /FX 3UC PLCs
Page 132 · click to enlarge
Page 132

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.9 Data Register and File Register [D]

4.9 Data Register and File Register [D]

Data registers are devices for storing numeric data. File registers are handled as the initial values of data registers. Each data register or file register stores 16-bit data (whose most significant bit specifies the positive or negative sign). Two data registers combined or file registers can store 32-bit numeric data (whose most significant bit specifies the positive or negative sign).

→ For the functions and operations of file registers, refer to Subsection 4.9.4.

4.9.1 Numbers of data registers and file registers

The table below shows numbers of data registers and file registers. (Numbers are assigned in decimal.)

1. FX 3S PLC

Data registers File registers (latched (EEPROM

keep) type) General type Fixed latched (EEPROM keep) type General type Special type

128 points D128 to D255

128 points D256 to D2999

2744 points D8000 to D8511

512 points D1000*1 and later 2000 points maximum

2. FX 3G /FX 3GC PLCs

Data registers File registers (latched (EEPROM

keep) type) General type Fixed latched (EEPROM keep) type General type Special type

972 points D1100 to D7999

512 points D1000*1 and later 7000 points maximum

128 points D128 to D1099

6900 points*2 D8000 to D8511

3. FX 3U /FX 3UC PLCs

File registers (latched (battery

Latched (battery backed) type (backed up by battery against power failure)

Fixed latched (battery backed) type (backed up by battery against power failure)

backed) type) General type

200 points*3 D200 to D511

312 points*4 D512 to D7999

7488 points*1*5 D8000 to D8511

512 points D1000*1 and later 7000 points maximum

*1. Data registers D1000 and later can be used as file registers in units of 500 points by setting parameters.

*2. These registers can be changed to the latched type by the parameter setting when the optional battery is used. However, the latched range cannot be set.

*3. This area is not latched (battery backed). It can be changed to the latched (battery backed) area by setting parameters.

*4. This area is latched (battery backed). It can be changed to the non-latched (non-battery-backed) area by setting parameters.

*5. The latch (battery backup) characteristics cannot be changed using parameters.

When N : N Network or parallel link is used, some data registers are occupied for the link.

→ Refer to the Data Communication Edition.

Show 5 more labels / short text on this page
D0 to D127 · D0 to D127 · Data registers · Special type · D0 to D199
Page 133 of the Mitsubishi Electronics MELSEC FX3S user manual — 4.9.2 Structures of data registers and file registers
Page 133 · click to enlarge
Page 133

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.9 Data Register and File Register [D] 1

4.9.2 Structures of data registers and file registers

1. 16-bit type One (16-bit) data register or file register can store a numeric value ranging from -32,768 to +32,767.

Low order D 0 (16 bits)

1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0

1 2 4 8 16 32 64 128 256 512 1024 2048 4096 8192 16384

Sign 0Positive number 1: Negative number

A numeric value can be read from or written to a data register by an applied instruction usually. Or a numeric value can be directly read from or written to a data register from a display unit, display module, or programming tool.

2. 32-bit type Two serial data registers or file registers can express 32-bit data. - A data register with a larger device number handles high-order bits, and a data register with a smaller device

number handles low-order bits. - In the index type, V handles high-order bits, and Z handles low-order bits. Two data registers or file registers can store a numeric value ranging from -2,147,483,648 to +2,147,483,647.

Low order 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0

D1 (high-order 16 bits) D0 (low-order 16 bits)

0 1 0 1

32768 65536 131,072 262,144 524,288 1,048,576 2,097,152 4,194,304 8,388,608 16,777,216 33,554,432 67,108,864 134,217,728 268,435,456 536,870,912 1,073,741,824

1 2 4 8 16 32 64 128 256 512 1024 2048 4096 8192 16384

Sign 0Positive number 1: Negative number

Specified the Device & Constant

In the case of 32-bit type, when a data register or file register on the low-order side (example: D0) is specified, the subsequent number on the high-order side (example: D1) is automatically occupied. Either an odd or even device number can be specified for the low-order side, but it is recommended to specify an even device number for the low-order side under consideration of the monitoring function of display units, display modules, and programming tools.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 13 more labels / short text on this page
Introduction · High order · b15 · b0 · Overview · Instruction List · Devices in Detail · High order · b31 · b0 · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 134 of the Mitsubishi Electronics MELSEC FX3S user manual — WDT
Page 134 · click to enlarge
Page 134

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.9 Data Register and File Register [D]

4.9.3 Functions and operation examples of data registers

Data registers are devices for storing numeric data. Each data register stores 16-bit data (whose most significant bit specifies the positive or negative sign). Two data registers combined can store 32-bit numeric data (whose most significant bit specifies the positive or negative sign).

1. General type and latched (battery backed) type data registers

  • Once data is written to a data register it does not change unless other data overwrite it. When the PLC mode switches from "RUN" to "STOP" or when the power is interrupted, however, all data stored in general type data registers is cleared to "0". If the special auxiliary relay M8033 has been driven in advance, data is held even when the PLC mode switches from "RUN" to "STOP".
  • Latched (battery backed) type data registers hold their contents even when the PLC mode switches from "RUN" to "STOP" or when the power is interrupted. In FX 3U /FX 3UC PLCs, the contents of data registers are backed up by the battery built into the PLC. In FX 3S /FX 3G /FX 3GC PLCs, the contents of data registers are backed up by the EEPROM built into the PLC. When the optional battery is installed, the battery backs up the contents of some general type data registers against power failure. The contents of data registers are backed up by the battery built in the PLC.

→ For details on each backup method, refer to Section 2.6.

  • When using fixed latched (battery backed) type data registers as general type data registers, provide the following reset circuit by RST or ZRST instruction at the head step in a program.

Ex. FX3U/FX3UC PLCs

M8002

ZRST D512 D999 Data stored in D512 to D999 are cleared to "0".

→ For file registers, refer to Subsection 4.9.4.

2. Special type data registers

  • Special type data registers contain informative, special purpose data and are sometimes written to during program operation. The contents of special type data registers are cleared to their initial values when restoring the power. (Generally, these data registers are cleared to "0" at first, and then the initial values (if there are any) are written by the system ROM.)
  • For example, the watchdog timer time is set initially to D8000 by the system ROM. When changing the contents, write a desired time to D8000 by transfer instruction MOV (FNC 12).

M8002

MOV K250 D8000

The watchdog timer is set to 250 ms.

The watchdog timer is refreshed.

WDT

→ For the data backup characteristics of special data registers, refer to Section 2.6 and Chapter 37.

→ For the types and functions of special data registers, refer to Chapter 37.

Initial pulse · Initial pulse

Page 135 of the Mitsubishi Electronics MELSEC FX3S user manual — MOV T 10 C 20
Page 135 · click to enlarge
Page 135

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.9 Data Register and File Register [D] 1

3. Operation examples Data registers can be used in various control with numeric data. This section explains the operations of representative basic instructions and applied instructions among various applications. For the full use of data registers, refer to the explanation of applied instructions later.
1. Data registers in basic instructions Specifying the set value of a timer or counter

T 2 D 0

A counter or timer operates while regarding the contents of a specified data register as its set value.

C 10 D 20

2. Data registers using applied instructions Operation examples using MOV (FNC 12) instruction a) Changing the current value of a counter

MOV D 5 C 2 The current value of the counter C2 is changed to the contents stored in D5.

b) Reading the current value of a timer or counter to a data register

MOV C 10 D 4 The current value of the counter C10 is transferred to D4.

c) Storing a numeric value to data registers

Specified the Device & Constant

MOV K200 D 10

"200 (decimal value)" is transferred to D10.

"80000 (decimal value)" is transferred to D10 and D11. Because a numeric value larger than 32767 is 32-bit data, a 32-bit operation is required. When a data register on the low-order side (D10) is specified, a data register on the high-order side (D11) is automatically occupied.

DMOV K80000 D10(D11)

d) Transferring the contents of a data register to another data register

MOV D 10 D 20 The contents of D10 are transferred to D20.

3. Using unoccupied timers and counters as data registers Operation examples using MOV (FNC 12) instruction Timers and counters not in a program can be used as devices for storing 16-bit or 32-bit numeric values (data registers).

MOV K300 T 10

"300 (decimal value)" is transferred to T10.

The contents of T10 are transferred to the current value register of C20. In this case, T10 is not working as a timer, but is working as a data register.

MOV T 10 C 20

K300 C 20

FNC10-FNC19 Move & Compare

As in the case of data registers, when 16-bit timers or counters are used as 32-bit devices, two timers or two counters (example: C1 and C0) store 32-bit numeric data. One 32-bit counter (example: C200) can store 32-bit numeric data.

FNC20-FNC29 Arith. & Logic Operation

Show 9 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · 16-bit · 32-bit · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 136 of the Mitsubishi Electronics MELSEC FX3S user manual — [A]
Page 136 · click to enlarge
Page 136

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.9 Data Register and File Register [D]

4.9.4 Functions and operation examples of file registers

A file register is a device for setting the initial value of a data register with the same number. Each file register stores 16-bit data (whose most significant bit specifies the positive or negative sign). Two file registers combined can store 32-bit numeric data (whose most significant bit specifies the positive or negative sign). Up to 7000 data registers starting from D1000 can be specified as file registers by the parameter setting. The number of file registers varies depending on the model. Refer to Subsection 2.7.3 for the file register setting range.

  • In parameter settings, 1 to 14 blocks can be specified. One block secures 500 file registers, but uses the program memory area by 500 steps.
  • When some of data registers starting from D1000 are specified as file registers, the remaining data registers not specified as file registers can be used as data registers.

This section explains how to handle file registers.

1. Operation of file registers

  • The contents of the file register area [A] set inside the built-in memory or memory cassette are batch-transferred to the data memory area [B] inside the system RAM when the PLC power is turned ON or when the PLC mode switches from STOP to RUN. When data registers are specified as file registers by the parameter setting, the contents of the file register area [A] inside the program memory are transferred when the PLC power is turned ON or when the PLC mode switches from STOP to RUN. This means that the contents changed in the data memory are initialized every time when the PLC turns ON or when the PLC mode switches from STOP to RUN. When it is necessary to save data changed in the data memory using a sequence program, update the file register area [A] to the changed values by the same-number register update mode in BMOV (FNC 15) instruction described later.

RAM

When power is turned ON When PLC mode is changed from STOP to RUN

For devices D1000 and later specified as operands in applied instructions other than BMOV (FNC 15) , indirectly specified values for timers, counters or devices in RST instructions can be read from and written to the data register area [B] in the same way as general data registers.

D1000 500 points × 14 blocks maximum (7000 points maximum)

[A]

[B]

The remaining area can be used as data registers for general purpose.

  • Difference between BMOV (FNC 15) instruction and other instructions The table below shows the differences between the BMOV (FNC 15) instruction and other applied instructions.

Instruction Transferred contents Remarks

BMOV instruction Data can be read from and written to the file register area [A] inside the program memory. −

Applied instructions other than BMOV instruction

Because the data register area [B] is provided inside the system RAM in the PLC, its contents can be arbitrarily changed without being limited by the optional memory format.

Data can be read from and written to the data register area [B] inside the image memory in the same way as general data registers.

The data stored in data registers set as file registers are automatically copied from the file register area [A] to the data register area [B] when restoring the power.

  • When a file register is monitored from peripheral equipment, the data register area [B] inside the data memory is read. When "file register device current value change", "file register device forced reset" or "PLC memory all clear" is executed from peripheral equipment, the file register area [A] inside the program memory is changed, and then the data is automatically transferred to the data register area [B]. Accordingly, when file registers are to be overwritten, the program memory should be "built-in memory" or "memory cassette whose protect switch is set to OFF". (The memory cassette cannot be overwritten from peripheral equipment if its protect switch is set to ON.)
Show 13 more labels / short text on this page
Inside built-in memory · Inside system · or memory cassette · Program · Data memory · memory · Program/ comment · Data register · File register · Data register · Write · Read · Data register D7999
Page 137 of the Mitsubishi Electronics MELSEC FX3S user manual — S D
Page 137 · click to enlarge
Page 137

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.9 Data Register and File Register [D] 1

2. File register ↔ Data register

When the same file register is specified for both and in BOMV (FNC 15) instruction, this instruction specifies the same-number register update mode and executes the following operation:

S D

Read

memory or memory cassette

RAM

BMOV direction inverseOFF

OFF

M8024

S ‚ D ‚ n

FNC 15 BMOVP D1100 D1100 K400

500 points × 14 blocks maximum (7000 points maximum)

Same file register number is specified.

[A]

[B]

  • When X002 is set to ON while BMOV instruction direction reverse flag M8024 is OFF, the contents of a file register are transferred to the data register area [B] inside the data memory as shown in the figure on the left.

D1499 D1499

Write

BMOV direction inverseON

memory or memory cassette

RAM

M8024

ON

S ‚ D ‚ n

FNC 15 BMOVP D1100 D1100 K400

Specified the Device & Constant

Same file register number is specified.

500 points × 14 blocks maximum (7000 points maximum)

BMOV direction inverseOFF Always OFF during operation

M8001

M8024

[A]

[B]

D1499 D1499

  • When X003 is set to ON while BMOV instruction direction reverse flag M8024 is ON, the contents of a data register inside the data memory are written to the file register area inside the program memory as shown in the figure on the left.
  • When updating the contents of a file register in the same-number register update mode, make sure that the file

register numbers at and are equal to each other. Also make sure that the number of transfer points specified by "n" does not exceed the file register area. If the number of transfer points exceeds the file register area, an operation error occurs and the instruction is not executed.

S D

  • When and are indexed, the instruction is executed if the actual device number is within the file register area and if the number of transfer points is within the file register area also.

S D

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 30 more labels / short text on this page
Introduction · Inside built-in · Inside system · Overview · Program · Data memory · memory · Program/ comment · Data register · File register · Data register · Instruction List · Read · Data register D7999 · Devices in Detail · Inside built-in · Inside system · Program · Data memory · memory · Program/ comment · Data register · File · Data register · register · Write · Data register D7999 · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 138 of the Mitsubishi Electronics MELSEC FX3S user manual — D S
Page 138 · click to enlarge
Page 138

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.9 Data Register and File Register [D]

3. Data register → File register When a file register (D1000 or later) is specified for the destination of BMOV (FNC 15) instruction, it is possible to directly write data to the file register area [A] inside the program memory.

Write

Mitsubishi Electronics MELSEC FX3S — Write diagram (page 138)
Fig. 50 · Write

M8024

S ‚ D ‚ n OFF

X001 FNC 15 BMOVP D200 D1100 K400

  • When X001 is set to ON, data is transferred to the data register area [B] and file register area [A] as shown in the figure on the left. If data cannot be written to the file register area [A] because the protect switch of the memory cassette is ON, data is written to only the data register area [B].

Write 500 points × 14 blocks maximum (7000 points maximum)

When a file register device is specified for in a general applied instruction, data is transferred to only the data register area [B].

  • A file register can be specified for . If is

S D

the same as , the same-number register update mode is selected. → For the same-number register update mode, refer

to the previous page.

  • By controlling BMOV instruction direction reverse flag M8024 for BMOV (FNC 15) instruction, data can be transferred in both directions in one program (as shown in the figure below).
Mitsubishi Electronics MELSEC FX3S — S D diagram (page 138)
Fig. 51

← Batch transfer of data registers and writing to file register M8024(ON) :D1100 D200

Cautions on reading

When a file register (D1000 or later) is specified for the source of BMOV (FNC 15) instruction and the same number file register is not specified for the destination, the contents of the file register area [A] inside the program memory are not read.

1. When a file register is specified for the source and a data register is specified for the destination
Mitsubishi Electronics MELSEC FX3S — Cautions on reading diagram (page 138)
Fig. 52 · Cautions on reading

Batch transfer of data registers

M8024

S ‚ D ‚ n OFF

X000 FNC 15 BMOVP D1100 D200 K400

  • When X000 is set to ON, the data register area [B] is read as shown in the figure on the left.

D1100 500 points × 14 blocks maximum (7000 points maximum)

  • A file register can be specified for . If is

D S

the same as , the same-number register update mode is selected.

→ For the same-number register update mode,

refer to the previous page.

Page 139 of the Mitsubishi Electronics MELSEC FX3S user manual — S D
Page 139 · click to enlarge
Page 139

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.9 Data Register and File Register [D] 1

2. When file registers of different device numbers are specified for the source and destination

Write

memory or memory cassette

RAM

M8024

S ‚ D ‚ n OFF

X001 FNC 15 BMOVP D1100 D1400 K100

  • When X001 is set to ON, the contents of the data register area [B] are transferred to the data register area [B] and file register area [A] as shown in the figure on the left. If data cannot be written to the file register area [A] because the protect switch of the memory cassette is ON, data is written to only the data register area [B].

D1100 Write 500 points × 14 blocks maximum (7000 points maximum)

D1400 D1199

[A]

[B]

D1499 D1499

4.9.5 Cautions on using file registers

1. Cautions on using a memory cassette When changing the contents of file registers stored in the memory cassette, confirm the following conditions:
  • Set to OFF the protect switch in the memory cassette.
  • Do not turn OFF the power while the contents of file registers are changed. If the power is turned OFF during the change, the data stored in file registers may be filled with unexpected values, or a parameter error may occur.

Specified the Device & Constant

2. Execution time for writing data to file registers

  • In FX 3U /FX 3UC PLCs It takes 66 to 132 ms to write data in one continuous block (500 points) to the memory cassette (flash memory). Execution of the program is paused during this period. Because the watchdog timer is not refreshed during this period, it is necessary to take proper countermeasures such as inserting the WDT instruction into the sequence program. It takes longer time to write data to file registers stored in a memory cassette (flash memory) compared to writing data to file registers stored in the built-in memory.
  • In FX 3S /FX 3G /FX 3GC PLCs It takes 80 ms to write data in one continuous block (500 points) to file registers. Note that execution of the program is paused during this period, but the watchdog timer is automatically refreshed. The time for writing data is same between file registers stored in the built-in memory and file registers stored in a memory cassette (EEPROM).
3. Allowable number of writes to the memory Data can be written to the memory cassette up to 10,000 times, and to the memory (EEPROM) built in FX 3S /FX 3G / FX 3GC PLCs up to 20,000 times. When a continuous operation type instruction is used for data writing in a program, data is written to the memory in every operation cycle of the PLC. To prevent this, make sure to use a pulse operation type instruction (BMOVP).
4. Cautions on handling file registers in the same-number register update mode in BMOV (FNC 15) instruction
  • When updating the contents of the same number file register, make sure that the file register number at and

are equal to each other.

  • Make sure that the number of transfer points specified by "n" does not exceed the file register area.
  • If the number of transfer points specified by "n" exceeds the file register area, an operation error (M8067) occurs and the instruction is not executed.

FNC10-FNC19 Move & Compare

  • In the case of indexing

When and are indexed, the instruction is executed if the actual device number is within the file register area and the number of transfer points is within the file register area also.

S D

FNC20-FNC29 Arith. & Logic Operation

Show 18 more labels / short text on this page
Introduction · Inside built-in · Inside system · Program · Data memory · memory · Overview · Program/ comment · Data register · File register · Data register · Write · Instruction List · Data register D7999 · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 140 of the Mitsubishi Electronics MELSEC FX3S user manual — Difference in the access method
Page 140 · click to enlarge
Page 140

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.10 Extension Register [R] and Extension File Register [ER]

4.10 Extension Register [R] and Extension File Register [ER]

Extension registers (R) are the extended form of data registers (D). The contents of extension registers (R) can be stored in extension file registers (ER). In FX3U/FX3UC PLCs, extension file registers (ER) are available only while the memory cassette is attached.

4.10.1 Numbers of extension registers and extension file registers

The table below shows numbers of extension registers (R) and extension file registers (ER). (Numbers are assigned in decimal.)

1. FX 3G /FX 3GC PLCs

Extension file register (ER)

24000 points*1 ER0 to ER23999

2. FX 3U /FX 3UC PLCs

Extension register (R) (latched [battery backed] type)

Extension file register (ER)

32768 points ER0 to ER32767

*1. These registers can be changed to the latched (battery backed) type by the parameter setting when the optional battery is used. However, the latched range cannot be set.

*2. These registers are stored in the EEPROM built in the PLC, or in the EEPROM in the memory cassette when the memory cassette is attached.

*3. Available only while a memory cassette is mounted (because they are stored in the flash memory inside a memory cassette.)

4.10.2 Data storage destination and access method

Because the memory for storing data is different between extension registers and extension file registers, the access method is different as shown in the table below:

Data storage destination

Device PLC Data storage destination

FX3G/FX3GC Built-in RAM

FX3U/FX3UC Built-in RAM (latched [battery backed] area)

FX3G Built-in EEPROM or EEPROM in memory cassette

FX3GC Built-in EEPROM

FX3U/FX3UC Memory cassette (flash memory)

Difference in the access method

register Extension file register

Reading in program 3 UOnly dedicated instructions are

Writing in program 3 UOnly dedicated instructions are

Display module 3 3

Test operation in online mode of GX Works2, GX Developer 3 ×

Batch writing by GX Works2, GX Developer 3 3

Computer link function 3 ×

Show 14 more labels / short text on this page
Extension register (R) · (General type) · (file type) · R0 to R23999 · 24000 points*2 · (file type) · R0 to R32767 · 32768 points*3 · Extension register · Extension file register · Access method Extension · enabled · enabled · Data change method
Page 141 of the Mitsubishi Electronics MELSEC FX3S user manual — 1. When clearing the data using a program
Page 141 · click to enlarge
Page 141

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.10 Extension Register [R] and Extension File Register [ER] 1

4.10.3 Structures of extension registers and extension file registers

One extension register consists of 16 bits. Extension registers can be used in 16-bit and 32-bit applied instructions in the same way as data registers.

1. 16-bit type One extension register (consisting of 16 bits) can handle a numeric ranging from − 32768 to +32767.

Low order R0, ER0 (16 bits)

1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0

1 2 4 8 16 32 64 128 256 512 1024 2048 4096 8192 16384

Sign 0Positive number 1: Negative number

A numeric value is usually read from and written to an extension register by applied instructions. However, a numeric value can also be directly read from and written to an extension register from a display unit, display module, or programming tool.

2. 32-bit type Two serial extension registers (consisting of 32 bits) can express a 32-bit numeric value ranging from − 2,147,483,648 to +2,147,483,647. (A larger number register handles high-order 16 bits, and a smaller number register handles low-order 16 bits.)

Low order 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0

R1, ER1 (high-order 16 bits) R0, ER0 (low-order 16 bits)

0 1 0 1

Sign 0Positive number 1: Negative number

32768 65536 131,072 262,144 524,288 1,048,576 2,097,152 4,194,304 8,388,608 16,777,216 33,554,432 67,108,864 134,217,728 268,435,456 536,870,912 1,073,741,824

1 2 4 8 16 32 64 128 256 512 1024 2048 4096 8192 16384

Specified the Device & Constant

  • In the case of 32 bit type, when an extension register on the low-order side (example: R0) is specified, the subsequent serial number on the high-order side (example: R1) is automatically occupied. Either an odd or even device number can be specified for the low-order side, but it is recommended to specify an even device number for the convenience of the monitoring function for display units, display modules, and programming tools.

4.10.4 Initialization of extension registers and extension file registers

The contents of extension registers are backed up by the battery even when the power is turned OFF or when the PLC mode switches from STOP to RUN in FX3U/FX3UC PLCs and in FX3G/FX3GC PLCs if extension registers are changed to the latched (battery backed) type and the optional battery is installed. When initializing the contents of extension registers, clear them using a sequence program, GX Works2 or GX Developer.

1. When clearing the data using a program

  • When initializing some extension registers (R) Example: When initializing (clearing) R0 to R199

FNC 16 FMOVP K0 R0 K200 Command

  • When initializing extension registers and extension file registers in sector units Sectors are not provided for extension registers and extension file registers in FX 3G /FX 3GC PLCs. Example: When initializing R0 to R4095 and ER0 to ER4095 (initializing two sectors starting from R0 and ER0)

Ex. FX3U/FX3UC PLCs

FNC10-FNC19 Move & Compare

INITRP R0 K2 The current value in Ro to R4095 is initialized to "FFFFH".

2. When clearing the data using GX Works2 Select [Online] → [PLC Memory Operation] → [Clear PLC memory...] in GX Works2, and clear [Data device]. This operation initializes the contents of timers, counters, data registers, file registers and extension registers.

FNC20-FNC29 Arith. & Logic Operation

Show 14 more labels / short text on this page
Introduction · High order · Overview · b15 · b0 · Instruction List · Devices in Detail · High order · b31 · b0 · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow · Command FNC292
Page 142 of the Mitsubishi Electronics MELSEC FX3S user manual — MOV D 10 R 20
Page 142 · click to enlarge
Page 142

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.10 Extension Register [R] and Extension File Register [ER]

4.10.5 Functions and operation examples of extension registers

Extension registers can be used in various controls with numeric data the same as data registers. This subsection explains operations in representative basic instructions and applied instructions among various applications. For the full use of extension registers, refer to the explanation of applied instructions described later.

1. Extension registers in basic instructions

  • Specifying an extension register as the set value of a timer or counter

T 2 R 0

A counter or timer operates with regards to the contents of a specified extension register as the set value.

C 10 R 20

2. Extension registers in applied instructions Operation examples using MOV (FNC 12) instruction
  • Changing the current value of a counter

The current value of the counter C2 is changed to the contents of R5.

MOV R 5 C 2

  • Reading the current value of a counter to an extension register

The current value of the counter C10 is transferred to R4.

MOV C 10 R 4

  • Storing a numeric value to extension registers

"200 (decimal value)" is transferred to R10.

MOV K200 R 10

"80000 (decimal value)" is transferred to R10 and R11. Because a numeric value larger than 32767, the 32-bit operation (double D instruction) is required. When an extension register on the low-order side (R10) is specified, an extension register on the high-order side (R11) is automatically occupied.

DMOV K80000 R10(R11)

  • Transferring the contents of a data register to extension register

The contents of D10 are transferred to R20.

MOV D 10 R 20

16 bits · 32 bits

Page 143 of the Mitsubishi Electronics MELSEC FX3S user manual — R23999
Page 143 · click to enlarge
Page 143

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.10 Extension Register [R] and Extension File Register [ER] 1

4.10.6 Functions and operation examples of extension file registers

Extension file registers (ER) are usually used as log data storage destinations and set data storage destinations. Extension file registers can be handled only with dedicated instructions shown in the table below. When using data contents with other instructions, transfer them to an extension register of the same device number, and then use the extension register. However, extension file registers (ER) are available in FX3U/FX3UC PLCs only when the memory cassette is attached.

  • FX 3G /FX 3GC PLCs

LOADR (FNC290) This (transfer) instruction reads data of extension file registers (ER)*1 to extension registers (R).

RWER (FNC294) This (transfer) instruction writes specified extension registers (R) to extension file registers (ER)

Use this instruction to store the contents of any extension register (R) in extension file registers (ER)*1.

*1. When the memory cassette is attached, extension file registers in the memory cassette are accessed. When the memory cassette is not attached, extension file registers in the EEPROM built in the PLC are accessed.

  • FX 3U /FX 3UC PLCs

LOADR (FNC290) This (transfer) instruction reads data of extension file registers (ER)*2 to extension registers (R).

This (transfer) instruction writes data of extension registers (R) to extension file registers (ER)*2 in 2048 point (1 sector) units. Use this instruction to store newly created sectors (2048 points) of data to extension file registers

SAVER (FNC291)

(ER)*2.

This instruction initializes extension registers (R) and extension file registers (ER)*2 in 2048 point (1 sector) units.

INITR (FNC292)

Use this instruction to initialize extension registers (R) and extension file registers (ER)*2 before starting to log data by the LOGR instruction.

LOGR (FNC293) This instruction logs specified data, and writes it to extension registers (R) and extension file registers (ER)*2.

Specified the Device & Constant

This (transfer) instruction writes specified extension registers (R) to extension file registers (ER)*2.This instruction is supported in FX3UC PLC Ver. 1.30 or later. Use this instruction to store the contents of any extension register (R) to

RWER (FNC294)

extension file register (ER)*2.

This instruction initializes extension file registers (ER)*2 in 2048 point (1 sector) units. This instruction is supported

INITER (FNC295)

in FX3UC PLC Ver. 1.30 or later. Use this instruction to initialize extension file registers (ER)*2 before executing SAVER instruction.

*2. Extension file registers are only accessible when a memory cassette is mounted.

1. Relationship between extension file registers and extension registers Extension file registers and extension registers have the following positional relationship inside the PLC.

a) FX3G/FX3GC PLCs

Extension register (R) Extension file register (ER)

Available in built-in RAM

Available in attached memory cassette or built-in EEPROM*3

General-purpose device (sequence program)

RWER instruction (arbitrary number of points)

ER0 R0

LOADR instruction (point units)

FNC10-FNC19 Move & Compare

R23999

ER23999

All points are written at one time

FNC20-FNC29 Arith. & Logic Operation

GX Works2, GX Developer

*3. Memory cassette cannot be connected to FX3GC PLCs.

Show 12 more labels / short text on this page
Introduction · Overview · Instruction Description · Instruction List · Instruction Description · Devices in Detail · Before Programming · Basic Instruction · General applied instruction · FNC00-FNC09 Program Flow · Nonvolatile memory · Programming tool
Page 144 of the Mitsubishi Electronics MELSEC FX3S user manual — R30720 ER30720
Page 144 · click to enlarge
Page 144

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.10 Extension Register [R] and Extension File Register [ER]

b) FX3U/FX3UC PLCs

Extension file register (ER) Extension register (R)

Available with a memory

Available in built-in RAM

SAVER instruction (sector units) RWER instruction (point units)

R0

ER0

General-purpose device (sequence program)

R2048

ER2048

LOADR instruction (point units)

R4096

ER4096

ER6144 INITER instruction (initialization) (sector units) INITER

INITR instruction (initialization) (sector units)

All points are written at one time

R30720 ER30720

R32767

ER32767

GX Works2, GX Developer

2. Sectors of extension registers and extension file registers In FX 3U /FX 3UC PLCs, extension registers and extension file registers are divided into sectors in the data configuration. One sector consists of 2,048 devices. The table below shows the head device number in each sector. In FX 3G /FX 3GC PLCs, sectors are not provided for extension registers and extension file registers.

Sector No. Head device No. Device range Sector No. Head device No. Device range

Sector 0 R0 ER0 to ER2047, R0 to R2047 Sector 8 R16384 ER16384 to ER18431, R16384 to R18431

Sector 1 R2048 ER2048 to ER4095, R2048 to R4095 Sector 9 R18432 ER18432 to ER20479, R18432 to R20479

Sector 2 R4096 ER4096 to ER6143, R4096 to R6143 Sector 10 R20480 ER20480 to ER22527, R20480 to R22527

Sector 3 R6144 ER6144 to ER8191, R6144 to R8191 Sector 11 R22528 ER22528 to ER24575, R22528 to R24575

Sector 4 R8192 ER8192 to ER10239, R8192 to R10239 Sector 12 R24576 ER24576 to ER26623, R24576 to R26623

Sector 5 R10240 ER10240 to ER12287, R10240 to R12287 Sector 13 R26624 ER26624 to ER28671, R26624 to R28671

Sector 6 R12288 ER12288 to ER14335, R12288 to R14335 Sector 14 R28672 ER28672 to ER30719, R28672 to R30719

Sector 7 R14336 ER14336 to ER16383, R14336 to R16383 Sector 15 R30720 ER30720 to ER32767, R30720 to R32767

Show 15 more labels / short text on this page
cassette mounted · 2048 points · 2048 points · 1 sector · General applied instruction · 2048 points · 2048 points · 2048 points · 2048 points · 2048 points · LOGR instruction · 16 sectors · Nonvolatile · memory · Programming tool
Page 145 of the Mitsubishi Electronics MELSEC FX3S user manual — 4.10.7 Cautions on using extension file registers
Page 145 · click to enlarge
Page 145

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.10 Extension Register [R] and Extension File Register [ER] 1

4.10.7 Cautions on using extension file registers

1. Cautions on writing data to extension file registers (FX 3U /FX 3UC PLCs) Because extension file registers are stored in the flash memory inside a memory cassette, pay attention to the following points:
  • When writing data to extension file registers by SAVER instruction Initialize sectors to be written before executing this instruction. After initialization, store data to be written to extension registers. In FX 3UC PLC Ver. 1.30 or later, it is not necessary to initialize sectors to be written when using RWER instruction.
  • When writing data to extension file registers by LOGR instruction Initialize sectors to be written before starting to log data.
  • When using INITR instruction This instruction initializes the contents of specified extension registers and extension file registers. When initializing only extension file registers by this instruction, make sure to temporarily move the contents of extension registers to unused extension registers or unused data registers before executing this instruction. When initializing only extension file registers in FX 3UC PLC Ver. 1.30 or later, use INITER instruction.

2. Initialization of extension file registers Because the contents of extension file registers are stored in the memory cassette or built-in EEPROM, use the data clear operation in a sequence program, GX Works2 or GX Developer to initialize them. For writing data to extension file registers in FX3U/FX3UC PLCs, it is necessary to initialize the target area to be written in advance. For writing data to extension file registers in FX3G/FX3GC PLCs, it is not necessary to initialize the target area to be written in advance.

1. When initializing extension file registers in a program (required only in FX 3U /FX 3UC PLCs) a) Initializing only extension file registers in sector units [Ver. 1.30 or later]
ExampleWhen initializing ER0 to ER4095 (initializing two sectors starting from ER0)

Specified the Device & Constant

FNC295 INITERP R0 K2 The current value is initialized to "FFFFH" in ER0 to ER4095.

b) Initializing extension registers and extension file registers in sector units

Example: When initializing R0 to R4095 and ER0 to ER4095 (initializing two sectors starting from R0 and ER0)

INITRP R0 K2 The current value is initialized to "FFFFH" in R0 to R4095 and ER0 to ER4095.

2. When initializing extension file registers using GX Works2 Select [Online] → [PLC Memory Operation] → [Clear PLC memory...] in GX Works2, and clear [Data device]. This operation initializes the contents of timers, counters, data registers, file registers and extension registers.
3. Allowable number of writes to the memory Note the following cautions on access to extension file registers.
  • In FX 3U /FX 3UC PLCs Data can be written to the memory cassette (flash memory) up to 10,000 times. Every time the INITR (FNC292), RWER (FNC294) or INITER (FNC295) instruction is executed, it is counted as a write to the memory. Make sure not to exceed the allowable number of writes. When a continuous operation type instruction is used, data is written to the memory in every operation cycle of the PLC. To prevent this, make sure to use a pulse operation type instruction.

Execution of the LOADR (FNC290), SAVER (FNC291) or LOGR (FNC293) instruction is not counted as a write to the memory. However, it is necessary to initialize the writing target sector before executing the SAVER (FNC291) or LOGR (FNC293) instruction. Every time the INITR (FNC292) or INITER (FNC295) instruction is executed, it is counted as a write to the memory. Make sure not to exceed the allowable number of writes.

FNC10-FNC19 Move & Compare

  • In FX 3G /FX 3GC PLCs Data can be written to the memory cassette (EEPROM) up to 10,000 times, and to the built-in memory (EEPROM) up to 20,000 times. Every time the RWER (FNC294) instruction is executed, it is counted as a write to the memory. Make sure not to exceed the allowable number of writes. When a continuous operation type instruction is used, data is written to the memory in every operation cycle of the PLC. To prevent this, make sure to use a pulse operation type instruction. Execution of the LOADR (FNC290) instruction is not counted as a write to the memory.

FNC20-FNC29 Arith. & Logic Operation

Show 9 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Command input · Before Programming · Command input · Basic Instruction · FNC00-FNC09 Program Flow
Page 146 of the Mitsubishi Electronics MELSEC FX3S user manual — 4.10.8 Registration of data in extension registers and extension file registers
Page 146 · click to enlarge
Page 146

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.10 Extension Register [R] and Extension File Register [ER]

4.10.8 Registration of data in extension registers and extension file registers

This subsection explains the operating procedures of GX Works2.

→ For details on GX Developer operating procedures, refer to GX Developer Version 8 Operating Manual. 1 Setting the project type, PLC type and programming language

Select [Project]→[New].

Mitsubishi Electronics MELSEC FX3S — 4.10.8 Registration of data in extension registers and extension file registers diagram (page 146)
Fig. 53 · 4.10.8 Registration of data in extension registers a…
Page 147 of the Mitsubishi Electronics MELSEC FX3S user manual — 4.10 Extension Register [R] and Extension File Register [ER] 1
Page 147 · click to enlarge
Page 147

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.10 Extension Register [R] and Extension File Register [ER] 1

2 Creating the device memory

This operation is not required when using the device memory offered as the default.

1. Right-click [Device Memory] in the project data list to open the submenu.
2. Click [Add New Data] to open the New Data dialog box.
3. Input the data name, and click the [OK] button to display the dialog box for Device Memory.
Mitsubishi Electronics MELSEC FX3S — 4.10 Extension Register [R] and Extension File Register [ER] 1 diagram (page 147)
Fig. 54 · 4.10 Extension Register [R] and Extension File Regis…
Mitsubishi Electronics MELSEC FX3S — 4.10 Extension Register [R] and Extension File Register [ER] 1 diagram (page 147)
Fig. 55 · 4.10 Extension Register [R] and Extension File Regis…

Specified the Device & Constant

Mitsubishi Electronics MELSEC FX3S — 4.10 Extension Register [R] and Extension File Register [ER] 1 diagram (page 147)
Fig. 56 · 4.10 Extension Register [R] and Extension File Regis…

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 7 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 148 of the Mitsubishi Electronics MELSEC FX3S user manual — 3 Setting the data
Page 148 · click to enlarge
Page 148

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.10 Extension Register [R] and Extension File Register [ER]

3 Setting the data

1. Select [Edit] → [Input Device] to open the Input Device dialog box.
2. Set the "Device", "Range", "Display Mode" and "Register".
Mitsubishi Electronics MELSEC FX3S — 3 Setting the data diagram (page 148)
Fig. 57 · 3 Setting the data
3. Set the data.
Mitsubishi Electronics MELSEC FX3S — 3 Setting the data diagram (page 148)
Fig. 58 · 3 Setting the data
Page 149 of the Mitsubishi Electronics MELSEC FX3S user manual — 4.10 Extension Register [R] and Extension File Register [ER] 1
Page 149 · click to enlarge
Page 149

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.10 Extension Register [R] and Extension File Register [ER] 1

4 Writing (transferring) the data to the PLC

1. Select [Online] → [Write to PLC] to open the Online Data Operation dialog box.
2. Check the Device Memory to Write (transfer) the data.
Mitsubishi Electronics MELSEC FX3S — 4.10 Extension Register [R] and Extension File Register [ER] 1 diagram (page 149)
Fig. 59 · 4.10 Extension Register [R] and Extension File Regis…
3. Click the [Detail] button in the Online Data Operation dialog box to open the Device Data Detail Setting dialog box. Check the "Ext. file register".

Specified the Device & Constant

Mitsubishi Electronics MELSEC FX3S — 4.10 Extension Register [R] and Extension File Register [ER] 1 diagram (page 149)
Fig. 60 · 4.10 Extension Register [R] and Extension File Regis…

Click the blank space to change it into " ". 3

4. Click the [Execute] button in the Online Data Operation dialog box to write (transfer) to the PLC.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 7 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 150 of the Mitsubishi Electronics MELSEC FX3S user manual — 4.11.3 Indexing of devices
Page 150 · click to enlarge
Page 150

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.11 Index Register [V and Z]

4.11 Index Register [V and Z]

Index registers can be used in the same way as of data registers. But they are special registers since they can change the contents of device numbers and numeric values by program when combined with another device number or numeric value in operands of applied instructions.

4.11.1 Numbers of index registers

The table below shows numbers of index registers (V and Z). (Numbers are assigned in decimal.) When only "V" or "Z" is specified, it is handled as "V0" or "Z0" respectively.

V0 (V) to V7, Z0 (Z) to Z7

*1. The characteristics related to protection against power failure cannot be changed by parameters.

4.11.2 Functions and structures

1. 16-bit type Index registers have the same structures as data registers.

V 16 bits Z 16 bits

V0 to V7:

8 points Z0 to Z7:

2. 32-bit type Make sure to use Z0 to Z7 when indexing a device in a 32-bit applied instruction or handling a numeric value outside the 16-bit range.

This is because FX PLCs handle Z as the low-order side of a 32-bit register as shown in combinations of V and Z in the figure on the left. Even if V0 to V7 on the high-order side is specified, indexing is not executed. When index registers are specified as a 32-bit device, both V (high- order side) and Z (low-order side) are referred to at the same time. If a numeric value for another purpose remains in V (high-order side), consequently the numeric value here becomes extremely large, thus an operation error occurs. Example of writing to 32-bit index registers

V0 (high-order side) Z0 (low-order side)

V1 (high-order side) Z1 (low-order side)

V2 (high-order side) Z2 (low-order side)

V3 (high-order side) Z3 (low-order side)

V4 (high-order side) Z4 (low-order side)

V5 (high-order side) Z5 (low-order side)

V6 (high-order side) Z6 (low-order side)

DMOV K300 Z2

V7 (high-order side) Z7 (low-order side)

K300 → (V2,Z2)

Even if an index value in a 32-bit applied instruction does not exceed the 16-bit numeric range, use a 32-bit operation instruction such as DMOV for writing a numeric value to Z as shown in the above figure so that both V (high-order side) and Z (low-order side) are overwritten at the same time.

4.11.3 Indexing of devices

Available devices and the contents of indexing are as described below:

→ For indexing method and cautions, refer to Section 5.7.

Decimal devices/numeric values: M, S, T, C, D, R, KnM, KnS, P and K For example, when "V0 = K5" is specified and "D20V0" is executed, an instruction is executed for the device number D25 (D20 + 5). Constants can be indexed also. When "K30V0" is specified, an instruction is executed for decimal value K35 (30 + 5).

Octal devices: X, Y, KnX and KnY For example, when "Z1 = K8" is specified and "X0Z1" is executed, an instruction is executed for the device number X10 (X0 + 8: addition of octal value). When indexing for a device whose device number is handled in octal, a numeric value converted into octal is added for the contents of V and Z. Accordingly, note that when "Z1 = K10" is specified "X0Z1" indicates that X12 is specified, and X10 is not specified.

Hexadecimal numeric values: H For example, when "V5 = K30" is specified and a constant "H30V5" is specified, it is handled as H4E (30H + K30). When "V5 = H30" is specified and a constant "H30V5" is specified, it is handled as H60 (30H + 30H).

Show 4 more labels / short text on this page
Index type · 16 points*1 · 8 points · 32 bits
Page 151 of the Mitsubishi Electronics MELSEC FX3S user manual — FEND
Page 151 · click to enlarge
Page 151

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.12 Pointer [P and I] 1

4.12 Pointer [P and I]

4.12.1 Numbers of pointers

The table below shows numbers of pointers (P and I). (Numbers are assigned in decimal.) When using a pointer for input interrupt, an input number assigned to it cannot be used together with a "high-speed counter" or "speed detection (FNC 56)" which uses the same input range.

1. FX 3S PLC

For branch For input interrupt For timer interrupt For jump to END step

I00 (X000) I30 (X003) I10 (X001) I40 (X004) I20 (X002) I50 (X005)

I6 I7 I8 3 points

P0 to P62 P64 to P255

2. FX 3G /FX 3GC PLCs

For branch For input interrupt For timer interrupt For jump to END step

P0 to P62 P64 to P2047

I00 (X000) I30 (X003) I10 (X001) I40 (X004) I20 (X002) I50 (X005)

I6 I7 I8 3 points

3. FX 3U /FX 3UC PLCs

For branch For input interrupt/input delay

interrupt For timer interrupt For counter

interrupt For jump to END step

Specified the Device & Constant

I00 (X000) I30 (X003) I10 (X001) I40 (X004) I20 (X002) I50 (X005)

I6 I7 I8 3 points

I010 I040 I020 I050 I030 I060

P0 to P62 P64 to P4095

4.12.2 Functions and operation examples of pointers for branch

The roles and operations of pointers for branch are as described below. Because all of these pointers are combined with applied instructions, refer to the explanation of each instruction for the detailed method.

→ For details on interrupt function, refer to Chapter 36.

1. Applied instructions using pointers for branch (P)

  • CJ (FNC 00) (conditional jump)

CJ P 0

When X001 turns ON, the PLC jumps to a label position specified by CJ (FNC 00) instruction, and executes the subsequent program.

P0

  • CALL (FNC 01) call subroutine

CALL P 1

When X001 turns ON, the PLC executes a subroutine in the label position specified by CALL (FNC 01) instruction, and then returns to the original position by SRET (FNC 02) instruction.

FNC10-FNC19 Move & Compare

FEND

P1

SRET

FNC20-FNC29 Arith. & Logic Operation

Show 23 more labels / short text on this page
Introduction · Overview · P63 1 point · Instruction List · 255 points · 6 points · Devices in Detail · P63 1 point · 2047 points · 6 points · P63 1 point · 4095 points · 6 points · 6 points · Before Programming · Basic Instruction · Jump · Label · FNC00-FNC09 Program Flow · Main program · Jump · Label · Subroutine program Return
Page 152 of the Mitsubishi Electronics MELSEC FX3S user manual — Delay function of input interrupt (Only in FX 3U /FX 3UC PLCs)
Page 152 · click to enlarge
Page 152

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.12 Pointer [P and I]

  • Role of pointer P63 for jump to the END step

P63 is a special pointer for jumping to the END step when the CJ (FNC 00) instruction is executed. Note that a program error will occur when P63 is programmed as a label.

Mitsubishi Electronics MELSEC FX3S — 4.12.3 Functions and operation examples of pointers for interrupt diagram (page 152)
Fig. 61 · 4.12.3 Functions and operation examples of pointers…

→ Refer to "5. Label unnecessary for the

pointer P63" in Section 8.1.

4.12.3 Functions and operation examples of pointers for interrupt

→ For details on interrupt function, refer to Chapter 36. There are three types of pointers for interrupt. When in use, they are combined with IRET (FNC 03), EI (FNC 04) and DI (FNC 05) for interrupt return, enabling interrupt and disabling interrupt.

1. Pointers for input interrupt (delay interrupt): 6 points → For details on input interrupt function, refer to Section 36.3 and Section 36.4. The PLC can receive input signals from specific input numbers without influence of the operation cycle of the PLC. By using these input signals as triggers, the PLC executes interrupt routine programs. Because pointers for input interrupt can handle signals shorter than the operation cycle, use them for high priority processing during sequence control and for control handling short pulses.

Mitsubishi Electronics MELSEC FX3S — 4.12.3 Functions and operation examples of pointers for interrupt diagram (page 152)
Fig. 62 · 4.12.3 Functions and operation examples of pointers…

edge FX3S FX3G/FX3GC FX3U/FX3UC

10 µs or more 10 µs or more

10 µs or more X004 I401 I400 M8054*1

X005 I501 I500 M8055*1 50 µs or more

*1. Cleared when the PLC mode switches from RUN to STOP.

Non-overlap of input numbers

Inputs X000 to X007 are used for high-speed counters, input interrupt, pulse catch, SPD/ZRN/DSZR/DVIT instructions and general-purpose inputs. When assigning functions, there should be no overlap between those input terminals.

Delay function of input interrupt (Only in FX 3U /FX 3UC PLCs)

This input interrupt has a function to delay the execution of interrupt routine in units of 1ms. The delay time is specified by the following pattern program. This delay function can electrically adjust the mounting position of sensors for input interrupts without shifting the actual position.

Mitsubishi Electronics MELSEC FX3S — Delay function of input interrupt (Only in FX 3U /FX 3UC PLCs) diagram (page 152)
Fig. 63 · Delay function of input interrupt (Only in FX 3U /FX…

MOV K{{{* Delay time specifying program Make sure to describe the delay time specifying program shown on the left at the head of an interrupt routine program. Because this is a pattern program, change only the delay time [1]. Only a constant (K) or data register (D) can be used to specify the delay time*.

Page 153 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 153 · click to enlarge
Page 153

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.12 Pointer [P and I] 1

Operations

Interrupt is usually disabled in the PLC. If interrupt is enabled by EI instruction, when X000 or X001 turns ON while a program is scanned, the PLC executes the interrupt routine [1] or [2], and then returns to the main program by IRET instruction.

EI

FEND

interrupt Rising edge of X000 is detected

Make sure to program a pointer for interrupt (I***) as a label after FEND instruction. •

IRET

interrupt Rising edge of X001 is detected

IRET

END

Specified the Device & Constant

2. Pointers for timer interrupt: 3 points → For details on timer interrupt function, refer to Section 36.5. The PLC executes an interrupt routine program at every specified interrupt cycle time (10 to 99 ms). Use these pointers for control requiring cyclic processing regardless of the operation cycle of the PLC.

Input No. Interrupt cycle (ms) Interrupt disabling flag

M8056 *1

I7 M8057 *1

An integer ranging from 10 to 99 is put in " " portion of the pointer name. Ex: I610 = Timer interrupt at every 10 ms

I8 M8058 *1

*1. Cleared when the PLC mode switches from RUN to STOP.

Caution

It is recommended to set the timer interrupt time to 10 ms or more. When the timer interrupt time is set to 9 ms or less, the timer interrupt processing may not be executed at an accurate cycle in the following cases:

  • When the processing time of the interrupt program is long
  • When an instruction requiring long processing time is used in the main program

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 13 more labels / short text on this page
Introduction · • · Interrupt enabled range · Overview · Pointer for · Instruction List · Interrupt routine [1] · Pointer for · Devices in Detail · Interrupt routine [2] · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 154 of the Mitsubishi Electronics MELSEC FX3S user manual — Operations
Page 154 · click to enlarge
Page 154

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

4 Devices in Detail

4.12 Pointer [P and I]

Operations

Mitsubishi Electronics MELSEC FX3S — Operations diagram (page 154)
Fig. 64 · Operations

Timer interrupt is enabled after EI instruction. It is not necessary to program DI (disable interrupt) instruction when no zone to disable timer interrupt is needed.

"FEND" indicates the end of the main program. Make sure to describe an interrupt routine after "FEND".

The PLC executes an interrupt routine at every 20 ms. The PLC returns to main program by IRET instruction.

3. Pointers for counter interrupt: 6 points *1

→ For details on counter interrupt function, refer to Section 36.6. The PLC executes an interrupt routine based on the comparison result obtained by the comparison set instruction for high-speed counter (DHSCS instruction). Use these pointers for control requiring an interrupt routine based on the counting result from high-speed counters.

Pointer No. Interrupt disabling flag Pointer No. Interrupt disabling flag

M8059 *2 I020 I050

M8059 *2

I030 I060

*1. This function is supported only in FX3U/FX3UC PLCs.

*2. Cleared when the PLC mode switches from RUN to STOP.

Operations

Mitsubishi Electronics MELSEC FX3S — Operations diagram (page 154)
Fig. 65 · Operations

Enable interrupt after EI instruction, and describe the main program. •

Drive the coil of a high-speed counter, and specify an interrupt pointer in DHSCS (FNC 53) instruction.

When the current value of C255 changes from "999" to "1000" or from "1001" to "1000", the interrupt routine is executed. For example of interrupt program, refer to an input interrupt described above.

Page 155 of the Mitsubishi Electronics MELSEC FX3S user manual — 2. Hexadecimal numbers (HEX)
Page 155 · click to enlarge
Page 155

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

5 How to Specify Devices and Constants to Instructions

5.1 Numeric Values Handled in PLC (Octal, Decimal, Hexadecimal and Real Numbers) 1

5. How to Specify Devices and Constants to Instructions

This chapter explains how to specify sources and destinations in sequence instructions which are the basis for handling PLC instructions.

  • Specifying constants as decimal, hexadecimal and real numbers
  • Specifying digits of bit devices
  • Specifying bit positions in data registers
  • Directly specifying BFM (buffer memory) in special function units/blocks
  • Indexing with index registers

5.1 Numeric Values Handled in PLC (Octal, Decimal, Hexadecimal and Real Numbers)

FX PLCs handle five types of numeric values according to the application and purpose. This section explains the roles and functions of these numeric values.

5.1.1 Types of numeric values

1. Decimal numbers (DEC)

  • Set value (constant K) of timers and counters

Specified the Device & Constant

  • Device numbers of auxiliary relays (M), timers (T), counters (C), state relays (S), etc.
  • Numeric values in operands and instruction operations in applied instructions (constant K)

2. Hexadecimal numbers (HEX)

  • Numeric values in operands and instruction operations in applied instructions (constant H)
3. Binary numbers (BIN) For a timer, counter or data register, a numeric value is specified in decimal or hexadecimal as described above. But all of these numeric values are handled in binary format inside PLCs. When these devices are monitored in peripheral equipment, they are automatically converted into the decimal format as shown in the figure on the right (or can be converted into the hexadecimal format).

Example of decimal number input K 7 8 9

0. Positive value 1: Negative value

1 2 4 8 16 32 64 128 256 512 1024 2048 4096 8192 16384

  • Handling of negative value A negative value is expressed in complement of PLCs. For details, refer to the explanation of NEG (FNC 29)

1 0 1 0 1 0 0 0 1 1 0

Automatic conversion 1+4+16+256+512 = 789

  • instruction.

(decimal) K 7 8 9 Monitoring in programming tool

4. Octal numbers (OCT) In FX PLCs, device numbers of input relays and output relays are assigned in octal. Because "8" and "9" do not exist in octal, device numbers are carried in the way "0 to 7, 10 to 17, 70 to 77, 100 to 107".
5. Binary coded decimal (BCD) BCD format expresses each numeric value from 0 to 9 constructing each digit of a decimal number in a 4-bit binary number. Because handling of each digit is easy, this format is adopted in controlling digital switches of BCD output type and seven-segment display units.

FNC10-FNC19 Move & Compare

6. Real numbers (floating point data) FX 3S , FX 3G , FX 3GC , FX 3U and FX 3UC PLCs have the floating point operation function to achieve high accuracy operation. In floating point operations, binary floating points (real numbers) are used, and scientific notation (real numbers) are used for monitoring them.

FNC20-FNC29 Arith. & Logic Operation

Show 11 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Input from · (decimal) · keyboard · Basic Instruction · (binary) · FNC00-FNC09 Program Flow
Page 156 of the Mitsubishi Electronics MELSEC FX3S user manual — Major applications
Page 156 · click to enlarge
Page 156

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

5 How to Specify Devices and Constants to Instructions

5.1 Numeric Values Handled in PLC (Octal, Decimal, Hexadecimal and Real Numbers)

5.1.2 Conversion of numeric values

Numeric values handled in FX PLCs can be converted as shown in the table below:

Decimal number (DEC) Octal number (OCT) Hexadecimal number

(HEX) Binary number (BIN) BCD

0 0 00 0000

1 1 01 0000 0001 0000 0001

2 2 02 0000 0010 0000 0010

3 3 03 0000 0011 0000 0011

4 4 04 0000 0100 0000 0100

5 5 05 0000 0101 0000 0101

6 6 06 0000 0110 0000 0110

7 7 07 0000 0111 0000 0111

8 10 08 0000 1000 0000 1000

9 11 09 0000 1001 0000 1001

10 12 0A 0000 1010 0001 0000

11 13 0B 0000 1011 0001 0001

12 14 0C 0000 1100 0001 0010

14 16 0E 0000 1110 0001 0100

15 17 0F 0000 1111 0001 0101

16 20 10 0001 0000 0001 0110

99 143 63 0110 0011 1001 1001

Major applications

Decimal number (DEC) Octal number (OCT) Hexadecimal number

(HEX) Binary number (BIN) BCD

Constants (K) and numbers of internal devices except I/O relays

BCD digital switches and seven-segment display units

Numbers of internal I/O relays Constants (H) Processing inside PLC

Show 14 more labels / short text on this page
••• · ••• · ••• · ••• · ••• · ••• · ••• · ••• · ••• · ••• · ••• · ••• · ••• · •••
Page 157 of the Mitsubishi Electronics MELSEC FX3S user manual — Binary floating point (real number)
Page 157 · click to enlarge
Page 157

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

5 How to Specify Devices and Constants to Instructions

5.1 Numeric Values Handled in PLC (Octal, Decimal, Hexadecimal and Real Numbers) 1

5.1.3 Handling of numeric values in floating point operations

Handling of numeric values in floating point operations Binary integers are handled inside PLCs. During division of integers, the answer "40 ÷ 3 = 13 ... 1" is obtained, for example. During square root extraction operations, decimal points are ignored. In FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs, floating point operations are available to achieve higher accuracy in such operations.

Binary floating point (real number)

When handling a binary floating point (real number) in data registers, use a pair of data registers having consecutive device numbers. When D11 and D10 are used, for example, a binary floating point is handled as shown below:

D 11(b15 to b0)

D 10(b15 to b0)

27 26 25 21 20 2-1 2-2 2-3 2-21 2-22 2-23

S E7 E6 E5 E1 E0 A22 A21 A20 A2 A1 A0

b30 b31 b29 b28 b23 b24 b22 b21 b2 b1 b0 b20

23 bits in mantissa part 8 bits in exponent part

E0 to E7 = 0 or 1

A0 to A22 = 0 or 1

0 in case "b0 to b31 = 0"

Sign for mantissa part (0Positive, 1: Negative)

Specified the Device & Constant

Binary floating point (real number) = ± (20 + A22 × 2−1 + A21 × 2−2 + ... + A0 × 2−23)

× 2 (E7 × 2 + E6 × 2 + ... + E0 × 2 )/2127

ExampleA22=1 , A21=0, A20=1, A19 to A0=0, E7=1, E6 to E1=0, E0=1

Binary floating point (real number) = ± (20 + 1 × 2−1 + 0 × 2−2 + 1 × 2−3 + ... + 0 × 2−23)

× 2 (1 × 2 + 0 × 2 + ... + 1 × 2 )/2127

= ±1.625 × 2129/2127 = ±1.625 × 22

The sign bit b31 states whether data is positive or negative, but is not handled as a complement.

Number of significant figures The number of significant figures of binary floating point is approximately 7 when expressed in decimal. The binary floating point range is as follows:

- Least absolute value1175494 × 10 -44
- Most absolute value3402823 × 10 32

Handling of the zero (M8020), borrow (M8021) and carry (M8022) flags These flags operate as follows in floating point operations.

- Zero flag : 1 when the result is 0 - Borrow flag : 1 when the result does not reach the minimum unit but is not 0 - Carry flag : 1 when the absolute value of the result exceeds the available numeric value range.

Monitoring of binary floating point (real number) A programming software supporting the display of floating point such as GX Works2 and GX Developer can directly monitor binary floating point (real number). A programming tool not supporting the display of floating point can monitor binary floating point (real number) when it is converted into scientific notation (real number).

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 7 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 158 of the Mitsubishi Electronics MELSEC FX3S user manual — Scientific notation (real number)
Page 158 · click to enlarge
Page 158

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

5 How to Specify Devices and Constants to Instructions

5.1 Numeric Values Handled in PLC (Octal, Decimal, Hexadecimal and Real Numbers)

Scientific notation (real number)

Because binary floating point (real number) is difficult to understand for users, it can be converted into scientific notation (real number). But internal operations are executed using binary floating point (real number). Scientific notation (real number) is handled by a pair of data registers having serial device numbers. Different from binary floating point (real number), a data register having a smaller device number handles the mantissa part, and the other data register having a larger device number handles the exponent part. For example, when data registers D1 and D0 are used, they handle scientific notation as shown below. Data can be written to D0 and D1 by MOV instruction.

Scientific notation (real number) = [Mantissa D0] × 10 [Exponent D1] Mantissa D0 = ± (1000 to 9999) or 0 Exponent D1 = −41 to +35

The most significant bit of D0 and D1 specifies the positive or negative sign respectively, and is handled as the complement of 2 respectively. The mantissa D0 does not allow "100", for example. In the case of "100", it is handled as "1000 × 10−1". The scientific notation (real number) range is as follows:

- Minimum absolute value1175 × 10 − 41
- Maximum absolute value3402 × 10 35

Number of significant figures The number of significant figures of scientific notation is approximately 4 when expressed in decimal. The scientific notation range is as described above.

Scientific notation (real number) is valid in the following instructions:

- Conversion from binary floating point (real number) into scientific notation (real number): FNC118 ([D]EBCD) - Conversion from scientific notation (real number) into binary floating point (real number): FNC119 ([D]EBIN)

Page 159 of the Mitsubishi Electronics MELSEC FX3S user manual — 5.2.3 Constant E (real number)
Page 159 · click to enlarge
Page 159

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

5 How to Specify Devices and Constants to Instructions

5.2 Specification of Constants K, H and E (Decimal, Hexadecimal and Real Number) 1

5.2 Specification of Constants K, H and E (Decimal, Hexadecimal and Real Number)

When handling constants in a sequence program, use constant K (decimal), H (hexadecimal) or E (floating point). In peripheral equipment for programming, add "K" to a decimal number, "H" to a hexadecimal number and "E" to a floating point (real number) for operations associated with numeric values in instructions. (Examples: K100 (decimal number), H64 (hexadecimal number) and E1.23 (or E1.23 + 10) (real number)) The roles and functions of constants are described below.

5.2.1 Constant K (decimal number)

"K" indicates a decimal integer, and is mainly used to specify the set value of timers and counters and numeric values as operands in applied instructions. (Example: K1234) The decimal constant specification range is as follows:

- When word data (16 bits) is used K-32768 to K32767 - When double data (32 bits) is used ... K-2,147,483,648 to K2,147,483,647

5.2.2 Constant H (hexadecimal number)

"H" indicates a hexadecimal number, and is mainly used to specify numeric values as operands in applied instructions. (Example: H1234) When using digits 0 to 9, the bit status (1 or 0) of each bit is equivalent to the BCD code, so BCD data can be specified also. (Example: H1234 ... When specifying BCD data, specify each digit of hexadecimal number in 0 to 9.) The hexadecimal constant setting range is as follows:

Specified the Device & Constant

- When word data (16 bits) is used H0 to HFFFF (H0 to H9999 in the case of BCD data) - When double data (32 bits) is used ... H0 to HFFFFFFFF (H0 to H99999999 in the case of BCD data)

5.2.3 Constant E (real number)

"E" indicates a real number (floating point data), and is mainly used to specify numeric values as operands in applied instructions. (Example: E1.234 or E1.234 + 3)

The real number setting range is from −1.0 × 2128 to −1.0 × 2−126, 0 and 1.0 × 2−126 to 1.0 × 2128. In a sequence program, a real number can be specified in two methods, "normal expression" and "exponent expression".

- Normal expression: Specify a numeric value as it is. For example, specify "10.2345" in the form "E10.2345".

- Exponent expression: Specify a numeric value in the format "(numeric value) × 10n". For example, specify "1234" in the form "E1.234 + 3". "+3" in "E1.234 + 3" indicates "103".

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 7 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 160 of the Mitsubishi Electronics MELSEC FX3S user manual — 5.3.2 Character string data
Page 160 · click to enlarge
Page 160

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

5 How to Specify Devices and Constants to Instructions

5.3 Character Strings

5.3 Character Strings

Character strings are classified into character string constants which directly specify character strings in operands in applied instructions and character string data.

5.3.1 Character string constant ("ABC")

A device "character string" directly specifies a character string in a sequence program. Put half-width characters inside quotation marks (example: "ABCD1234") in specification. JIS8 code is available. Up to 32 characters can be specified as a character string.

5.3.2 Character string data

With regard to character string data, a specified device to the NULL code (00H) is handled as one character string in 1-byte units. When expressing (recognizing) character string data by bit devices with digit specification, however, 16 bits are required for data including the NULL code (00H) specifying the end of the character string data because the instruction length is 16 bits. (Refer to Example 2 in the step 2 below.) In the following cases, an operation error occurs in the applied instruction (error code: K6706):

  • When "00H" is not specified in the corresponding device range after the source device number specified in an applied instruction
  • When there are insufficient devices for storing character string data (including "00H" or "0000H" indicating the end of the character string data) in the destination devices specified in an applied instruction
  • 1) Character string data stored in word devices
  • Example of data which can be
  • Example of data which cannot be recognized as character string data recognized as character string data
Mitsubishi Electronics MELSEC FX3S — 5.3.2 Character string data diagram (page 160)
Fig. 66 · 5.3.2 Character string data

"00H" indicating the end of the character string can be detected.

"00H" indicating the end of character string cannot be detected from the specified device to the end device number.

  • 2) Character string data stored in bit devices with digit specification
  • Example of data which can be
  • Examples of data which cannot be recognized as character string data recognized as character string data
Mitsubishi Electronics MELSEC FX3S — 5.3.2 Character string data diagram (page 160)
Fig. 67 · 5.3.2 Character string data

"00H" indicating the end of the character string can be detected.

"00H" indicating the end of character string cannot be detected from the specified device to the end device number.

Because the data "00H" indicating the end of the character string does not reach 16 bits, the end of the character string cannot be recognized.

Page 161 of the Mitsubishi Electronics MELSEC FX3S user manual — Specification of consecutive words
Page 161 · click to enlarge
Page 161

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

5 How to Specify Devices and Constants to Instructions

5.4 Specification of Digits for Bit Devices (Kn[ ]***) 1

5.4 Specification of Digits for Bit Devices (Kn[ ]***)

Handling of bit devices

Devices which handle only the ON/OFF information such as X, Y, M and S are called bit devices. On the other hand, devices handling numeric values such as T, C, D and R are called word devices. Even bit devices can handle a numeric value when they are combined. In this case, the number of digits Kn and the head device number are combined. The number of digits is expressed in 4 bit units (digits); K1 to K4 are used for 16-bit data, and K1 to K8 are used for 32- bit data. For example, "K2M0" indicates two-digit data expressed by M0 to M7.

0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1

Sign bit (0 = Positive, 1: Negative)

K2M0

0 1 0 1 0 1 0 1

M15 M8 M7 M0

M6 M5 M12 M11 M10 M9 M4 M3 M2 M1 M14 M13

Transferred Sign bit (0 = Positive, 1: Negative)

0 1 0 1 0 1 0 1

When 16-bit data is transferred to K1M0 to K3M0, the highest-order bits are not transferred due to insufficient data length. 32-bit data is transferred in the same way. When the number of digits specified for bit devices is K1 to K3 (or K1 to K7) in a 16-bit (or 32-bit) operation, the insufficient high-order bits are always regarded as "0". It means that such data is always positive.

Specified the Device & Constant

M0 FNC 19

Two-digit BCD data expressed by X004 to X013 is converted into binary data, and then transferred to D0.

BIN K2X004 D0

A bit device number can be specified arbitrarily, but it is recommended to set the least significant digit to "0" for X or Y. (In other words, it is recommended to specify "X000, X010, X020 ... Y000, Y010, Y020 ...") For M and S, multiples of "8" are ideal, but it is recommended to specify "M0, M10, M20 ..." to prevent confusion.

Specification of consecutive words

A series of data registers starting from D1 means "D1, D2, D3, D4 " In the case of word devices with digit specification, when such word devices are handled as a series, they are specified as shown below:

  • K1X000, K1X004, K1X010, K1X014 .....
  • K2Y010, K2Y020, K2Y030 .....
  • K3M0, K3M12, M3M24, K3M36 .....
  • K4S16, K4S32, K4S48 .....

Use the above devices in digit units so that devices are not skipped. When "K4Y000" is used in a 32-bit operation, the high-order 16 bits register as "0". It is necessary to use "K8Y000" when 32-bit data is required.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 11 more labels / short text on this page
Introduction · Overview · Low order · Instruction List · Transferred · Do not change · Devices in Detail · Low order · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 162 of the Mitsubishi Electronics MELSEC FX3S user manual — 5.6 Direct Specification of Buffer Memory (U[ ]\G[ ])
Page 162 · click to enlarge
Page 162

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

5 How to Specify Devices and Constants to Instructions

5.5 Bit Specification of a Word Device (D[ ].b)

5.5 Bit Specification of a Word Device (D[ ].b)

By specifying a bit of a word device, the specified bit can be used as bit data. When specifying a bit of a word device, use a word device number and bit number (hexadecimal). (Example: D0.0 ... Indicates the bit 0 of data register (D).) Indexing is not available for both device numbers and bit numbers.

Target word deviceData register or special data register Bit number : 0 to F (hexadecimal)
Mitsubishi Electronics MELSEC FX3S — 5.5 Bit Specification of a Word Device (D[ ].b) diagram (page 162)
Fig. 68 · 5.5 Bit Specification of a Word Device (D[ ].b)

D0 F E D C B A 9 8 7 6 5 4 3 2 1 0

5.6 Direct Specification of Buffer Memory (U[ ]\G[ ])

A buffer memory (BFM) of a special function units/blocks can be specified directly. BFM is 16-bit or 32-bit word data, and is mainly used for operands in applied instructions. For specifying a BFM, specify the unit number (U) of a special function units/blocks and the BFM number (\G) consecutively. (Example: U0\G0 ... Indicates the BFM #0 in the special function units/blocks whose unit number is 0.) Indexing is available for BFM numbers. The specification range is as follows:

Unit number (U) 0 to 7 BFM number (\G) 0 to 32766

Mitsubishi Electronics MELSEC FX3S — 5.6 Direct Specification of Buffer Memory (U[ ]\G[ ]) diagram (page 162)
Fig. 69 · 5.6 Direct Specification of Buffer Memory (U[ ]\G[ ]…
Page 163 of the Mitsubishi Electronics MELSEC FX3S user manual — D0V2
Page 163 · click to enlarge
Page 163

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

5 How to Specify Devices and Constants to Instructions

5.7 Indexing 1

5.7 Indexing

The functions and structures of index registers are explained in detail in "4.11 Index Register [V and Z]". Refer to Section 4.11 in advance.

5.7.1 Indexing in basic instructions

In the case of bit devices

Bit devices [X, Y, M (except special auxiliary relays), T, and C (C0 to C199)] used in LD, LDI, AND, ANI, OR, ORI, OUT, SET, RST, PLS, and PLF instructions can be indexed with index registers. The figure shown on the right explains an indexing operation with the index register Z(0) for X000 and M0 in the LD instruction. Transfer K5 or K10 to the index register Z(0) in advance. If Z(0) is "5", "X(0+5) = X005". When X005 turns ON, Y000 turns ON and "M(0+5) = M5". When M5 turns ON, Y001 turns ON.

X030 FNC 12

MOVP K5 Z(0)

K5 → Z(0)

If Z(0) is "10", "X(0+10) = X012*1". When X012*1 turns ON, Y000 turns ON and "M(0+10) = M10". When M10 turns ON, Y001 turns ON.

K10 Z(0)

MOVP

K10 → Z(0)

*1. Refer to the caution 3) below.

X000Z(0)

  • The index registers Z0 to Z7 and V0 to V7 can be used for indexing.

Y000

  • In OUT instruction for a timer or counter, the timer number (or counter number) and the device specified for the set value can be indexed.

M0Z(0)

Cautions

Y001

Z(0)=5 : X005=ON → Y000=ON

Specified the Device & Constant

1. 32-bit counters and special auxiliary relays cannot be indexed with index registers.
M5=ON → Y001=ON Z(0)=10X012 *2 =ON → Y000=ON

M10=ON → Y001=ON

2. It is not permitted to use 16-bit counters as 32-bit counters by executing indexing.

*2 Refer to the caution 3).

3) When an octal device number of X or Y is indexed with an index register, the contents of the index register are converted into octal, and then added to the device number. For example, when the value of an index register added to the input X000 is changed in the order "K0 → K8 → K16", the device number converted into octal is added to the input X000 and the input number is changed in the order "X(000+0) = X000 → X(000+8) = X10 → X(000+16) = X20".

In the case of word devices and constants

The set value of word devices used in OUT instruction of T and C(0~199) can be indexed with index registers. The indexing operation is explained in an example in which the set value D0 of T0 used in the index register V2 indexes OUT instruction (as shown in the right figure). Transfer K0 or K10 to the index register V2 in advance. When X001 is set to ON, "D(0+0) = D0" if V2 is "0", and T0 operates with the set value D0. When X001 is set to ON, "D(0+10) = D10" if V2 is "10", and T0 operates with the set value D10.

X030 FNC 12

MOVP K0 V2

K0 → V2

K10 V2

MOVP

K10 → V2

Caution

T 0

1. When a 32-bit counter is used in OUT instruction, the set value cannot be indexed with an index register.

D0V2

V2 = 0The set value of T0 is the

present value of D0. V2 = 10 : The set value of T0 is the

present value of D10.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 7 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 164 of the Mitsubishi Electronics MELSEC FX3S user manual — In the case of word devices
Page 164 · click to enlarge
Page 164

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

5 How to Specify Devices and Constants to Instructions

5.7 Indexing

5.7.2 Indexing in applied instructions

Expression of applied instructions allowing indexing

In the explanation of applied instructions, " ‚ " is added to the source or destination symbol to indicate operands allowing indexing as shown in the figure below so that such operands can be discriminated from operands not allowing indexing.

S D

Mitsubishi Electronics MELSEC FX3S — S D diagram (page 164)
Fig. 70

In the case of bit devices

The indexing operation is explained in an example in which the comparison result M0 in CMP (FNC 10) instruction is indexed with the index register V1 (as shown in the figure on the right). Transfer K0 or K10 to the index register V1 in advance. When X001 is set to ON, "M(0+0) = M0" and the comparison result is output to M0 to M2 if V1 is "0". On the other hand, "M(0+10) = M10" and the comparison result is output to M10 to M12 if V1 is "10".

Mitsubishi Electronics MELSEC FX3S — In the case of bit devices diagram (page 164)
Fig. 71 · In the case of bit devices
  • The index registers Z0 to Z7 and V0 to V7 can be used for indexing.

V1=0 V1=10 D0>D1 →M0=ON M10=ON D0=D1 →M1=ON M11=ON D0

In the case of word devices

1. indexing operands in 16-bit instructions The indexing operation is explained in an example in which the transfer destination D0 in MOV instruction is indexed with the index register V3 (as shown in the figure on the right). Transfer K0 or K10 to the index register V3 in advance. When X001 is set to ON, "D(0+0) = D0" if V3 is "0", and K500 is transferred to D0. When X001 is set to ON, "D(0+10) = D10" if V3 is "10", and K500 is transferred to D10.

Mitsubishi Electronics MELSEC FX3S — In the case of word devices diagram (page 164)
Fig. 72 · In the case of word devices
V3=0K500 → D0 (D0+0) V3=10 : K500 → D10 (D0+10)

2. indexing operands in 32-bit instructions In a 32-bit instruction, it is also necessary to specify a 32-bit index register in the instruction. When an index register Z (Z0 to Z7) is specified in a 32-bit instruction, the specified Z and its counterpart V (V0 to V7) work together as 32-bit registers. The indexing operation is explained in an example in which the transfer destinations [D1, D0] in DMOV instruction are indexed with the index registers [V4, Z4] (as shown in the figure on the right). Transfer K0 or K10 to the index registers [V4, Z4] in advance. When X003 is set to ON, "[D(1+0), D(0+0)] = [D1, D0]" if [V4, Z4] is "0", and K69000 is transferred to [D1, D0]. When X003 is set to ON, "[D(1+10), D(0+10)] = [D11, D10]" if [V4, Z4] is "10", and K69000 is transferred to [D11, D10].

Mitsubishi Electronics MELSEC FX3S — In the case of word devices diagram (page 164)
Fig. 73 · In the case of word devices
V4,Z4=0K69000 → D1 ,D0 (D0+0) V4,Z4=10 : K69000 → D11,D10 (D0+10)
Page 165 of the Mitsubishi Electronics MELSEC FX3S user manual — MOVP
Page 165 · click to enlarge
Page 165

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

5 How to Specify Devices and Constants to Instructions

5.7 Indexing 1

Cautions

1. When even if a numeric value written to index registers does not exceed the 16-bit numeric value range (0 to 32767), make sure to overwrite both V and Z using a 32-bit instruction. If only Z is overwritten and another numeric value remains in V, the numeric value will be extremely large. Thus an operation error occurs.
2. It is not permitted to use 16-bit counters as 32-bit counters by executing indexing. When 32-bit counters are required, add Z0 to Z7 to counters C200 and later.
3. It is not permitted to index V and Z themselves.
4. Direct specification of buffer memory in special function units/blocks In the direct specification of buffer memory "U \G ", the buffer memory number can be indexed with index registers. The unit number cannot be indexed with index registers. ("U0\G0Z0" is valid, but "U0Z0\G0" is invalid.)
5. Indexing in bit digit specification It is not permitted to index "n" in "Kn" used for digit specification. ("K4M0Z0" is valid, but "K0Z0M0" is invalid.)

6) Indexing of I/O relays (octal device numbers) When octal device numbers of X, Y, KnX, and KnY are indexed with index register, the contents of an index register are converted into octal, and then added to the device number. In the example shown in the figure on the right, Y007 to Y000 are output by MOV instruction, and inputs are switched by indexing X007 to X000, X017 to X010, and X027 to X020. When rewriting the index value as "K0", "K8", "K16", the device number converted into octal is added "X000 + 0 = X000", "X000 + 8 = X10", "X000 + 16 = X20", and the input terminal working as the source is changed accordingly.

X030 FNC 12

MOVP K 0 V 3

K 0 → V 3

MOVP K 8 V 3

K 8 → V 3

MOVP K 16 V 3

K16 → V 3

X033 FNC 12

Specified the Device & Constant

MOV K2X0V3 K2Y0

V3=0 : X7 to X0 → Y7 to Y0 V3=8 : X17 to X10 → Y7 to Y0 V3=16 : X27 to X20 → Y7 to Y0

Display example of timer present value

A sequence to display the present value of the timers T0 to T9 can be programmed index registers.

M8000

Digital switch input for setting timer number X003 to X000

BIN K1X000 Z0

(X003 to X000)BCD→(Z0)BIN

PLC

BCD T 0Z0 K4Y000

(T0Z0)BIN→(Y017 to Y000)BCD

"T0Z0 = T0 to T9" according to "Z0 = 0 to 9"

Seven-segment display unit output for displaying timer current value Y017 to Y000

In the case of constants

The indexing operation is explained in an example in which the transfer destination in MOV instruction is indexed with the index register V6 (as shown in the figure on the right). Transfer K0 or K20 to the index register V6 in advance. When X005 is set to ON, "K(6+0) = K6" if V6 is "0", and K6 is transferred to D10. When X005 is set to ON, "K(6+20) = K26" if V6 is "20", and K26 is transferred to D10.

K0 V6

MOVP

FNC10-FNC19 Move & Compare

K0 → V6

K20 V6

MOVP

K20 → V6

K6V6 D10

FNC20-FNC29 Arith. & Logic Operation

MOVP

V6=0K6 (K6+0) → D10 V6=20 : K26(K6+20) → D10
Show 8 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · RUN monitor · Basic Instruction · FNC00-FNC09 Program Flow
Page 166 of the Mitsubishi Electronics MELSEC FX3S user manual — 5.7.3 Indexing example for instruction with limited number of use.
Page 166 · click to enlarge
Page 166

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

5 How to Specify Devices and Constants to Instructions

5.7 Indexing

5.7.3 Indexing example for instruction with limited number of use.

By modifying the target device numbers using index registers V and Z, the target device numbers can be changed using the program. In this way, an instruction with a limited number of uses per program can be used with multiple devices.

Example using the TKY instruction (FNC 70) Two groups of key entries (numeric keypad from 0 to 9) store the input data to D0 and D2. Although the TKY instruction (FNC 70) can only be programmed once, modifying the head device number of the input data, storage destination and pressed key information, the information can be input from the two groups of keys (numeric keypad from 0 to 9). Furthermore, even if V is changed while this instruction is being executed, this change is invalid. The change is invalid until the instruction is no longer being driven.

Mitsubishi Electronics MELSEC FX3S — 5.7.3 Indexing example for instruction with limited number of use. diagram (page 166)
Fig. 74 · 5.7.3 Indexing example for instruction with limited…
Page 167 of the Mitsubishi Electronics MELSEC FX3S user manual — 5.7 Indexing 1
Page 167 · click to enlarge
Page 167

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

5 How to Specify Devices and Constants to Instructions

5.7 Indexing 1

MEMO

Specified the Device & Constant

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 7 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 168 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 1 S 2 S 2
Page 168 · click to enlarge
Page 168

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

6 What to Understand before Programming

6.1 How to Read Explanation of Instructions

6. What to Understand before Programming

This chapter explains the I/O processing, relationship among instructions and programming method which should be understood before creating sequence programs.

6.1 How to Read Explanation of Instructions

In this manual, applied instructions are explained in the following form. For the expression methods and basic rules for applied instructions, read in advance "6.5 General rules for applied instructions" described later.

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (, , u, y) – FNC 20 to FNC 29

10.1 FNC 20 – ADD / Addition 1

Indicates applicable PLC versions.

10.1 FNC 20 – ADD / Addition

This instruction executes addition by two values to obtain the result (A + B = C).

oFor the floating point addition instruction EADD (FNC120), refer to Section 18.8.

1. Instruction format

Expression of applicable versions – → Ver. 2.20: before Ver. 2.20 – Ver. 2.20 →: Ver. 2.20 or later

Mnemonic Operation Condition P FNC 20

ADD D

Continuous Operation Pulse (Single) Operation

DADD

Continuous Operation Pulse (Single) Operation

ADDP

DADDP

2. Set data

Operand type Description Data type

Data for addition or word device number storing data 16- or 32-bit binary

Data for addition or word device number storing data 16- or 32-bit binary

Word device number storing the addition result 16- or 32-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

Specified the Device & Constant

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

3 S1 S2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (ADD and ADDP)

The contents of are added to in binary format, and the addition result is transferred to .

S 2 S 1 D

input D ‚ S1 ‚ S2 ‚ D ‚

ADD S1 ‚ S2 ‚ + o

  • The most significant bit of each data indicates the sign (positive: 0 or negative: 1), and data is added algebraically. 5 + ( 8) = 3
  • When a constant (K) is specified in or , it is automatically converted into binary format.

S 1 S 2

2. 32-bit operation (DADD and DADDP)

The contents of [ +1, ] are added to [ +1, ] in binary format, and the addition result is

S 2 S 2 S 1 S 1

transferred to [ +1, ].

D 1 D 1

input D ‚ S1 ‚ S2 ‚ D ‚ S1 ‚ S2 ‚ D ‚

DADD S1 ‚ S2 ‚ [ +1, ] + [ +1, ] o>1, ]

FNC10-FNC19 Move & Compare

  • The most significant bit of each data indicates the sign (positive: 0 or negative: 1), and data is added algebraically. 5500 + ( 8540) = 3040
  • When a constant (K) is specified in [ +1, ] or [ +1, ], it is automatically converted into binary format.

S 1 S 1 S 2 S 2

FNC20-FNC29 Arith. & Logic Operation

The above is different from the actual page, as it is provided for explanation only.

Show 21 more labels / short text on this page
Introduction · Outline · Applicable series · Overview · 16-bit Instruction · Mnemonic Operation Condition · 32-bit Instruction · 7 steps ADD · 13 steps · Instruction List · Devices in Detail · Oper- · and Type · Unit Index Con- stant · Real Number · Charac- ter String Pointer · Before Programming · Basic Instruction · Command · FNC00-FNC09 Program Flow · Command
Page 169 of the Mitsubishi Electronics MELSEC FX3S user manual — S S 1
Page 169 · click to enlarge
Page 169

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

6 What to Understand before Programming

6.1 How to Read Explanation of Instructions 1

Outline

1. Instruction format

1. The applied instruction number (FNC No.) and instruction mnemonic are indicated. The table below shows the meaning of simplified expression.

P FNC 12 MOV

No.

Dotted lines on the upper left and lower left sides indicate an independent instruction not associated with the 16-bit or 32-bit type. WDT (FNC 07)

P FNC 12 MOV D

No.

Continuous lines on the upper left side indicates that 16-bit type is available. "D" on the lower left side indicates that the 32-bit type is available. MOV (FNC 12)

P FNC 12 MOV

No.

Dotted lines on the lower left side indicate that the 32-bit type does not exist. Continuous lines on the upper left side indicate that only the 16-bit type is available. CJ (FNC 00)

Instruction name D

P FNC 12 MOV D

No.

Dotted lines on the upper left side indicate that the 16-bit type does not exist. "D" on the lower left side indicates that only the 32-bit type is available. HSCS (FNC 53)

D P FNC 12 MOV

No.

Continuous lines on the upper right side indicate that the continuous operation type is available. "P" on the lower right side indicates that the pulse operation type is available. CMP (FNC 10)

Specified the Device & Constant

P D FNC 12 MOV

No.

Dotted lines on the lower right side indicate that the pulse operation type does not exist. Continuous line on the upper right side indicate that only the continuous operation type is available.

MTR (FNC 52)

" "on the upper right side indicates that the contents of the destination change in every operation cycle when the continuous operation type is used. When operation should be executed only during the driving of an instruction, use the pulse operation type indicated by "P" on the lower right side.

D P FNC 12 MOV

No.

INC (FNC 24)

2. Set data The contents of devices that can be specified as operands in instructions and available data types are described below:
1. Contents The contents of operands in each instruction are described below.
2. Indexing of the source and destination In operands to which " ‚ " is added such as and , indexing is available. Operands not allowing indexing are expressed as and .

S S 1

S S 1

3) Data types - Bit : Bit device - 16-bit BIN : 16-bit binary code - 32-bit BIN : 32-bit binary code - 64-bit BIN : 64-bit binary code - 16/32-bit BIN : 16-bit or 32-bit binary code - 32/64-bit BIN : 32-bit or 64-bit binary code - 4-digit BCD : 4-digit (16-bit) BCD code - 8-digit BCD : 8-digit (32-bit) BCD code - 4/8-digit BCD : 4-digit (16-bit) or 8-digit (32-bit) BCD code - Character string : Character code such as ASCII code and shift JIS code - Character string (only ASCII) : ASCII code - Real number (binary) : Binary floating point - Real number (decimal) : Scientific notation

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 16 more labels / short text on this page
Introduction · Applicable instruction · Mark Description · Overview · (example) · Instruction name · Instruction List · Instruction name · Devices in Detail · Instruction name · Instruction name · Instruction name · Before Programming · Instruction name · Basic Instruction · FNC00-FNC09 Program Flow
Page 170 of the Mitsubishi Electronics MELSEC FX3S user manual — Program examples
Page 170 · click to enlarge
Page 170

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

6 What to Understand before Programming

6.1 How to Read Explanation of Instructions

Applicable devices

Devices which can be specified in operands of instructions are shown. When a device supports an instruction, "3" is added to the device.

  • 1) Bit devices
  • X : Input relay (X)
  • Y : Output relay (Y)
  • M : Auxiliary relay (M)
  • S : State relay (S) etc.
  • 2) Word devices
  • K : Decimal integer
  • H : Hexadecimal integer
  • KnX: Input relay (X) with digit specification *1
  • KnY: Output relay (Y) with digit specification *1
  • KnM: Auxiliary relay (M) with digit specification *1
  • KnS: State relay (S) with digit specification *1
  • T : Timer (T) current value
  • C : Counter (C) current value
  • D : Data register (file register)
  • V, Z: Index register
  • Modify: Availability of indexing using index register etc.

*1. Kn without specification indicates K1 to K4 for 16 bits, and K1 to K8 for 32 bits.

Explanation of function and operation

The function of each instruction is explained.

Cautions

Errors

Major errors that are possible to occur in each instruction are described. For details on errors, refer to "Chapter 38. Error Check Method and Error Code List".

Program examples

Concrete program examples using each instruction are described.

Page 171 of the Mitsubishi Electronics MELSEC FX3S user manual — (3)OR
Page 171 · click to enlarge
Page 171

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

6 What to Understand before Programming

6.2 Cautions on Creation of Fundamental Programs 1

6.2 Cautions on Creation of Fundamental Programs

This section explains cautions on programming.

6.2.1 Programming procedure and execution order

1. Contact configuration and steps Even for a sequence circuit offering the same operation, the program can be simplified and the number of steps can be saved depending on the contact configuration method.
1. It is recommended to write a circuit with many serial contacts in an upper position.

(1)LD

(1)LD

(2)AND

(5)OUT

(4)OUT

(2)LD (3)AND

(3)OR

(4)ORB

ORB instruction is not necessary

2. It is recommended to write a circuit with many parallel contacts in a left position.

(1)LD

(2)LD (1)LD

(3)AND

(5)OUT (4)ANB

(4)OUT

Specified the Device & Constant

(3)OR

(2)OR

ANB instruction is not necessary

2. Program execution and programming order A sequence program is executed "from top to bottom" and "from left to right". Code the sequence instruction list according to this rule.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 18 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Executed · Basic Instruction · FNC00-FNC09 Program Flow · (1) · (5) · (3) · (7) · (9) (10) · (2) · (6) · (4) · (8) · (11)
Page 172 of the Mitsubishi Electronics MELSEC FX3S user manual — 6.2.2 Double output (double coil) operation and countermeasures
Page 172 · click to enlarge
Page 172

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

6 What to Understand before Programming

6.2 Cautions on Creation of Fundamental Programs

6.2.2 Double output (double coil) operation and countermeasures

1. Operation of double outputs When a coil gives double outputs (double coils) in a sequence program, the priority is given to the latter one.

Suppose that the same coil Y003 is used in two positions as shown in the figure on the right. For example, suppose the X001 is ON and X002 is OFF.

Mitsubishi Electronics MELSEC FX3S — 6.2.2 Double output (double coil) operation and countermeasures diagram (page 172)
Fig. 75 · 6.2.2 Double output (double coil) operation and coun…

In the first coil Y003, the image memory turns ON and the output Y004 turns ON also because the input X001 is ON. In the second coil Y003, however, the image memory is set to OFF because the input X002 is OFF. Accordingly, the actual output to the outside is "Y003 = OFF, Y004 = ON".

2. Countermeasures against double outputs Double outputs (double coils) do not cause illegal input (program error), but the operation is disrupted as described above. Change the program as shown in the example below.
Mitsubishi Electronics MELSEC FX3S — 6.2.2 Double output (double coil) operation and countermeasures diagram (page 172)
Fig. 76 · 6.2.2 Double output (double coil) operation and coun…

SET, RST or jump instruction can be used instead, or the same output coil can be programmed at each state by step ladder instructions. When step ladder instructions are used, if an output coil located in the main routine is also used in a state, it is handled as a double coil. It is better to avoid such programming.

Page 173 of the Mitsubishi Electronics MELSEC FX3S user manual — ON ON OFF OFF
Page 173 · click to enlarge
Page 173

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

6 What to Understand before Programming

6.3 I/O Processing and Response Delay 1

6.2.3 Circuits which cannot be programmed and countermeasures

1. Bridge circuit A circuit in which the current flows in both directions should be changed as shown in the figure on the right (so that a circuit without D and a circuit without B are connected in parallel).

A B

C E

B

F

F

A

E

A E

2. Coil connection position

  • Do not write a contact on the right side of a coil.
  • It is recommended to program a coil between contacts first. The number of steps can be saved when a coil (E) between the contacts A and B is programmed first.

A B

A

E

B

C D

E

Specified the Device & Constant

6.3 I/O Processing and Response Delay

1. Operation timing of I/O relays and response delay FX PLCs execute the I/O processing by repeating the process (1) to process (3). Accordingly, the control executed by PLCs contains not only the drive time of input filters and output devices but also the response delay caused by the operation cycle.

[Input processing] Input image memory is read

The ON/OFF status of input terminals is received at one time.

Input image is read, and operation is executed according to program.

Acquiring the latest I/O information For acquiring the latest input information or immediately outputting the operation result in the middle of the operation cycle shown above, the I/O refresh instruction is available.

Output devices are driven Batch I/O method (refresh method)

Result is transferred to

2. Short pulses cannot be received. The ON duration and OFF duration of inputs in PLCs require longer time than "PLC scan time + Input filter response delay". When the response delay of the input filter "10 ms" is considered and the scan time is supposed as "10 ms", the ON duration and OFF duration should be at least 20 ms respectively. Accordingly, PLCs cannot handle input pulses at 25 Hz (1000 / (20 + 20) = 25) or more. However, the situation can be improved by PLC special functions and applied instructions.

Convenient functions for improvement By using the following functions, PLCs can receive pulses shorter than the operation cycle:

FNC10-FNC19 Move & Compare

This "input ON" can be received

"Input ON" cannot be received

This "input OFF" cannot be received

  • High-speed counter function

ON ON OFF OFF

  • Input interrupt function
  • Pulse catch function

FNC20-FNC29 Arith. & Logic Operation

  • Input filter value adjustment function

( Time) Output processing Operation cycle

Show 24 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · (1) · Scan time (operation · (2) · [Program processing] · Image memory of · cycle) · each device is · updated · Basic Instruction · (3) · [Output processing] · output latch · memory · FNC00-FNC09 Program Flow · Program processing · Program processing · Program processing · Program processing · Input processing
Page 174 of the Mitsubishi Electronics MELSEC FX3S user manual — 6.4 Mutual Relationship Among Program Flow Control Instructions
Page 174 · click to enlarge
Page 174

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

6 What to Understand before Programming

6.4 Mutual Relationship Among Program Flow Control Instructions

6.4 Mutual Relationship Among Program Flow Control Instructions

The table below shows the mutual relationship among various program flow control instructions.

In the table below, " " indicates containment relationship, and " " indicates that zones are partially overlapped.

Mitsubishi Electronics MELSEC FX3S — 6.4 Mutual Relationship Among Program Flow Control Instructions diagram (page 174)
Fig. 77 · 6.4 Mutual Relationship Among Program Flow Control I…
Example 1MC −− CJ −− P −− MCR
Example 2MC −− CJ −− MCR −− P
Page 175 of the Mitsubishi Electronics MELSEC FX3S user manual — *2 FOR FOR NEXT NEXT
Page 175 · click to enlarge
Page 175

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

6 What to Understand before Programming

6.4 Mutual Relationship Among Program Flow Control Instructions 1

3:This combination can be used without any problem. ×:This combination is not allowed; Operation error may be occurs. U:This combination is allowed, but is better not to be used because the operation will be complicated.

P-SRET I-IRET FEND-END

The DI skip status occurs, but this is not an error.

*2 FOR FOR NEXT NEXT

The operation indicated by continuous lines is described.

The first FEND or END is valid, but the intended processes will not occur. But this is not an error.

Specified the Device & Constant

Instructions having containment relationship can be combined except some combinations as follows:

1. MC-MCR cannot be used in FOR-NEXT, STL-RET, P-SRET and I-RET.
2. STL-RET cannot be used in FOR-NEXT, P-SRET and I-IRET.
3. MC-MCR, FOR-NEXT, P-SRET and I-IRET cannot be interrupted by I, IRET, SRET, FEND, END, etc.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 17 more labels / short text on this page
Introduction · Overview · Remarks · Instruction List · *1 · Devices in Detail · *1 · *3 · Before Programming · Basic Instruction · *3 · FNC00-FNC09 Program Flow · *3 · *3 · *3 · *3 · *3
Page 176 of the Mitsubishi Electronics MELSEC FX3S user manual — Devices handled as operands
Page 176 · click to enlarge
Page 176

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

6 What to Understand before Programming

6.5 General Rules for Applied Instructions

6.5 General Rules for Applied Instructions

6.5.1 Expression and operation type of applied instructions

Instructions and operands

- Both a function number FNC 00 to FNC and a symbol (mnemonic) indicating the contents are given to each applied instruction. For example, a mnemonic "SMOV (shift move)" is assigned to FNC 13 instruction. - Some applied instructions function only with their instruction part, but many instructions consist of the instruction part and following operands.

Mitsubishi Electronics MELSEC FX3S — 6.5.1 Expression and operation type of applied instructions diagram (page 176)
Fig. 78 · 6.5.1 Expression and operation type of applied instr…

: An operand whose contents do not change by execution of the instruction is called "source", and is

indicated by this symbol.

When a device number can be indexed with index registers, the source is expressed as with addition of " ‚ ".

When there are two or more sources, they are expressed as , , etc.

S 1 S 2

: An operand whose contents change by execution of the instruction is called "destination", and

indicated by this symbol.

When indexing is allowed and there are two or more destinations, they are expressed as ,

, etc. in the same way as sources. m, n : Operands not falling under source or destination are expressed as m and n.

When indexing is allowed and there are two or more such operands, they are expressed as m1 ‚, m2 ‚, n1 ‚, n2 ‚,etc. in the same way as sources and destinations.

- In applied instructions, the program step of the instruction part always occupies 1 step, but each operand occupies 2 or 4 steps depending on whether the instruction is 16-bit type or 32-bit type.

Devices handled as operands

- Bit devices themselves such as X, Y, M and S may be handled. - Combined bit devices, KnX, KnY, KnM, KnS, etc, may be handled as numeric value data.

→ Refer to Section 5.4. - Data registers (D) and current value registers for timers (T) and counters (C) may be handled. - Though data registers (D) are the 16-bit type, two serial data registers are combined when 32-bit data is handled. For example, when a data register D0 is specified as an operand in a 32-bit instruction, D1 and D0 are combined to handle 32-bit data. (D1 handles high-order 16 bits, and D0 handles low-order 16 bits.) When current value registers for T and C are used as general data registers, they are handled in the same way. However, each of 32-bit counters C200 to C255 can handle 32-bit data, and cannot be specified as an operand in a 16-bit instruction.

Page 177 of the Mitsubishi Electronics MELSEC FX3S user manual — Instruction name D
Page 177 · click to enlarge
Page 177

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

6 What to Understand before Programming

6.5 General Rules for Applied Instructions 1

Instruction form and operation type

Applied instructions are classified into "16-bit type" or "32-bit type" by the size of handled numeric values. And by the operation type, applied instructions are classified into "continuous operation type" or "pulse operation type". Some applied instructions have every combination of this form and type, and others do not.

1. 16-bit type and 32-bit type - Applied instructions handling numeric values are classified into the 16-bit type or the 32-bit type by the bit length of the numeric value data.

Command 1 FNC 12

MOV D10 D12

This instruction transfers the contents of D10 to D12.

This instruction transfers the contents of D21 and D20 to D23 and D22.

DMOV D20 D22

- In a 32-bit type instruction, the symbol "D" is added (example: DMOV). - Either an odd or even device number can be specified, and a specified device is combined with a device having the subsequent larger number (in the case of word devices such as T, C and D). For avoiding confusion, it is recommended to specify an even device number (which will be the low-order side) for an operand in a 32-bit instruction. - 32-bit counter (C200 to C255) is regarded as 32 bits, and cannot be used as an operand in a 16-bit instruction.

2. Pulse operation type and continuous operation type

Pulse operation type

In the example shown in the figure on the right, when X000 turns from OFF to ON , the instruction is executed only once, and is not executed in any other case. When it is not necessary to continually execute an instruction, use the pulse operation type. The symbol "P" indicates the pulse operation type. "DMOVP" indicates also the pulse operation type.

X000 FNC 12

MOVP D10 D12

Specified the Device & Constant

Continuous operation type

X001 FNC 12

The figure on the right shows a continuous operation type instruction. While X001 is ON, the instruction is executed in every operation cycle.

MOV D10 D12

In the continuous operation type of some instructions such as INC (FNC 24) and DEC (FNC 25), the contents of the destination change in every operation cycle.

For applied instructions requiring attention in using the continuous operation type, the symbol " " is added to the title of the explanation of such instructions as shown in the figure below.

P FNC 12 MOV

No.

Instruction name D

In any case, instructions are not executed while the drive input X000 or X001 is OFF. And the destinations do not change except when instructions specify otherwise.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 8 more labels / short text on this page
Introduction · Overview · Command 2 · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 178 of the Mitsubishi Electronics MELSEC FX3S user manual — 6.5.2 Handling of general flags
Page 178 · click to enlarge
Page 178

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

6 What to Understand before Programming

6.5 General Rules for Applied Instructions

6.5.2 Handling of general flags

In some types of applied instructions, the following flags operate: Examples: M8020: Zero flag M8021: Borrow flag M8022: Carry flag M8029: Instruction execution complete flag M8090: Block comparison signal M8328: Instruction non-execution flag M8329: Instruction execution abnormal complete flag M8304: Zero Flag M8306:Carry Flag These flags turn ON or OFF every time various instructions turn ON, but do not change when various instructions turn OFF not driven or when errors have occurred. Because these flags turn ON or OFF in many instructions, the ON/OFF status of flags change every time such instructions are executed. Program flag contacts directly under each instruction while referring to the examples below.

1. Program containing many flags (example of instruction execution complete flag M8029) When two or more instruction execution complete flags M8029 are programmed together for applied instructions, it is difficult to determine which instruction executes which flag. For using flags in any positions other than directly under applied instructions, refer to the next page.
Mitsubishi Electronics MELSEC FX3S — 6.5.2 Handling of general flags diagram (page 178)
Fig. 79 · 6.5.2 Handling of general flags

M8029 works as a flag to indicate that execution of DSW is completed.

M8029 works as a flag to indicate that execution of DPLSY is completed.

M8029 works as a flag to indicate that execution of the second DPLSY is completed.

M8029 works as a flag to indicate that execution of DSW is completed.

M8029 works as a flag to indicate that execution of the first DPLSY is completed.

Page 179 of the Mitsubishi Electronics MELSEC FX3S user manual — 6.5.2 Handling of general flags
Page 179 · click to enlarge
Page 179

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

6 What to Understand before Programming

Mitsubishi Electronics MELSEC FX3S — 6.5.2 Handling of general flags diagram (page 179)
Fig. 80 · 6.5.2 Handling of general flags
2. Introduction of method for using flags in any positions other than directly under applied instructions When two or more applied instructions are programmed, general flags turn ON or OFF when each applied instruction turns ON. Accordingly, when using a flag in any position other than directly under an applied instruction, set to ON or OFF another device just under the applied instruction, and then use the contact of the device as the command contact.

DSW execution complete flag M8029 is changed to M100.

DPLSY execution complete flag M8029 is changed to M200.

Page 180 of the Mitsubishi Electronics MELSEC FX3S user manual — M8160
Page 180 · click to enlarge
Page 180

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

6 What to Understand before Programming

6.5 General Rules for Applied Instructions

6.5.3 Handling of operation error flag

When there is an error in the applied instruction configuration, target device or target device number range and an error occurs while operation is executed, the following flag turns ON and the error information is stored.

1. Operation error

Error detected step number storage device

Error flag Error code storage device

FX3S/FX3G/FX3GC PLCs FX3U/FX3UC PLCs

M8067 D8067 D8069 D8315, D8314

  • When an operation error has occurred, M8067 turns ON and D8067 stores the operation error code number.
  • In the FX 3U /FX 3UC PLCs, D8315 and D8314 (32 bits in total) store the step number in which the error has occurred. When the error occurrence step number is up to 32767, the error occurrence step can be checked also in D8069 (16 bits).
  • In the FX 3S /FX 3G /FX 3GC PLCs, D8069 stores the error occurrence step number.
  • If another error occurs in another step, the stored data is updated in turn to the error code and step number of the new error. (These devices are set to OFF when errors are cleared.)
  • When the PLC mode switches from STOP to RUN, these devices are cleared instantaneously, and then set to ON again if errors have not been cleared.

2. Operation error latch

Error detected step number storage device

Error flag Error code storage device

FX3S/FX3G/FX3GC PLCs FX3U/FX3UC PLCs

M8068 − D8068 D8313, D8312

  • When an operation error has occurred, M8068 turns ON.
  • In the FX 3U /FX 3UC PLCs, D8313 and D8312 (32 bits in total) store the step number in which the error has occurred. When the error occurrence step number is up to 32767, the error occurrence step can be checked also in D8068 (16 bits).
  • In the FX 3S /FX 3G /FX 3GC PLCs, D8068 stores the error occurrence step number.
  • Even if another error has occurred in another step, the stored data is not updated, and remains held until these devices are forcibly reset or until the power turns OFF.
  • When the error occurrence step is up to the 32767th step, the error occurrence step can be checked in D8068 (16 bits).

6.5.4 Handling functions of extension flag

In some applied instructions, the function can be extended by combining a specific special auxiliary relay determined for each applied instruction. An example is explained below.

- When X000 turns ON, this instruction exchanges the contents of D10 and D11 with each other.

X000 FNC 17

XCHP D10 D11

- If M8160 has been driven before the XCH instruction and the source and destination of the XCH instruction are specified to the same device, high-order 8 bits and low- order 8 bits are exchanged with each other inside the device.

Function extension flag for the XCH instruction

M8160

XCHP D10 D10

- For returning this XCH instruction to the normal XCH instruction, it is necessary to set M8160 to OFF.

M8160

When using an instruction requiring the function extension flag in an interrupt program, program DI instruction (for disabling interrupt) before driving the function extension flag, and program EI instruction (for enabling interrupt) after turning OFF the function extension flag.

Same number

Page 181 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. External device communication instructions
Page 181 · click to enlarge
Page 181

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

6 What to Understand before Programming

6.5 General Rules for Applied Instructions 1

6.5.5 Limitation in the number of instructions and limitation in simultaneous instruction instances

Limitation in the number of instructions

Some applied instructions can only be used up to the specified number of times.

Instruction name Allowable number of times of

FNC 52 (MTR) 1 MTR instruction can only be used once in program.

FNC 56 (SPD) 8 (1 instruction/1 input or less) Pay attention so that this instruction does not overlap the input numbers of in DVIT

instruction, DOG inputs in ZRN instruction, zero point signal in DSZR instruction,

input interrupt numbers and high-speed counter input numbers.

FNC 60 (IST) 1 −

FNC 69 (SORT) 1 −

FNC 70 (TKY) 1 −

FNC 71 (HKY) 1 −

FNC 75 (ARWS) 1 −

FNC 77 (PR) 2 −

FNC149 (SORT2) 2 −

FNC186 (DUTY) 5 (1 instruction/1 input or less) −

FNC280 (HSCT) 1 −

When using above instructions beyond the allowable number of times of use For instructions whose operands allow indexing, device numbers and numeric values in such instructions can be changed by index registers. By indexing, when driving multiple instances simultaneously is not required, such instruction can be used as if they were used beyond the allowable number of times.

Specified the Device & Constant

→ Refer to "Subsection 5.7.3. Indexing example for instruction with limited number of use.".

Limitation in simultaneous instances of instructions

Some applied instructions can be programmed two or more times, but the number of simultaneous instances is limited. Even in instructions not shown below, if two or more instructions are driven at the same time for the same I/O number, it is regarded as double outputs. In some combinations of instructions, the operation may be disrupted, or the instructions cannot be executed. For details, refer to the caution described in each instruction page. For combinations of instructions, refer to "6.4 Mutual Relationship Among Program Flow Control Instructions".

1. Positioning instructions Do not drive FNC 57 (PLSY), FNC 58 (PWM), FNC 59 (PLSR), FNC150 (DSZR), FNC151 (DVIT), FNC156 (ZRN), FNC157 (PLSV), FNC158 (DRVI) and FNC159 (DRVA) instructions at the same time for the same output number.

2. High-speed processing instructions

  • FX 3S /FX 3G /FX 3GC PLCs The FNC 53 (HSCS), FNC 54 (HSCR) and FNC 55 (HSZ) instructions can be driven up to 6 times in total at the same time.
  • FX 3U /FX 3UC PLCs In FNC 53 (HSCS), FNC 54 (HSCR) and FNC 55 (HSZ) instructions (including FNC280 (HSCT) instruction), make sure that up to 32 instructions are driven at the same time. [FNC280 (HSCT) instruction can only be used once.] Note that "FNC280 (HSCT) instruction", "table high-speed comparison mode of FNC 55 (HSZ) instruction)" and "frequency control mode of FNC 55 (HSZ) instruction" can each only be used once.

3. External device communication instructions

  • In FNC 80 (RS) and FNC 87 (RS2) instructions, do not drive two or more instructions at the same time for the same port.

FNC10-FNC19 Move & Compare

  • It is impossible to combine and use "FNC 80 (RS), FNC 87 (RS2)", "FNC270 (IVCK) to FNC275 (IVMC)", "FNC276 (ADPRW)", "FNC300 (FLCRT) to FNC305 (FLSTRD)" instructions for the same port.
  • In FNC270 (IVCK) to FNC275 (IVMC) instructions, two or more instructions can be driven at the same time for the same port.

FNC20-FNC29 Arith. & Logic Operation

Show 8 more labels / short text on this page
Introduction · use Remarks · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 182 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 182 · click to enlarge
Page 182

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

6 What to Understand before Programming

6.6 Symbolic information storage and block password

6.6 Symbolic information storage and block password

6.6.1 Storage of symbolic information

The FX3U/FX3UC PLC Ver. 3.00 or later can store symbolic information (data indicating the program configuration such as structure and labels). By using this function, you can read symbolic information from the PLC, and edit labels, function blocks, etc. GX Works2 Ver. 1.62Q or later is required to store symbolic information.

→ Refer to the GX Works2 Version 1 Operating Manual (Common) for the details on symbolic information.

Cautions

  • When symbolic information is stored, it is deleted if the memory capacity set by parameters is changed. After changing the memory capacity, write the symbolic information again.
  • Memory cassettes (except for the FX 3U -FLROM-1M) which save symbolic information are also supported by FX 3U /FX 3UC PLCs whose version is earlier than Ver. 3.00. In that case, the FX 3U /FX 3UC PLC operates, but the written symbolic information is invalid.
  • For writing symbolic information and changing the set values of timers and counters using a peripheral device, it is recommended to create programs with set values specified indirectly. If the set values are specified directly, programs cannot be restored from symbolic information after the set values are changed.

6.6.2 Block password

In GX Works2, program parts can be protected by setting the block password. In the FX3U/FX3UC PLC Ver. 3.00 or later, the setting "Read-protect the execution program" is available for the block password.

→ Refer to the GX Works2 Version 1 Operating Manual (Common) for the details on the block password.

Cautions

  • In the PLC written by the computer using a project including a block password for which the setting "Readprotect the execution program" is valid, restoration of programs is enabled only when the PLC stores the symbolic information. For editing programs using a peripheral device which cannot read symbolic information (only supported by GX Works2 Ver. 1.62Q or later), do not use a block password for which the setting "Read-protect the execution program" is valid.
  • When a peripheral device tries to read an execution program from the PLC that has been written to by a computer using a project including a block password for which the setting "Read-protect the execution program" is valid, a communication error occurs and reading is disabled.
  • For writing a program using a peripheral device other than GX Works2 (Ver. 1.62Q or later) to a PLC that has been written to by a computer using a project including a block password for which the setting "Readprotect the execution program" is valid, execute "Clear PLC memory" to clear programs before writing. If a program is written without executing "Clear PLC memory" in advance, the written program cannot be read.
  • It is not possible to write programs including the block password for which the setting "Read-protect the execution program" is valid to the FX 3U /FX 3UC PLC whose version is earlier than 3.00.
  • If a memory cassette which saves programs including a block password for which the setting "Readprotect the execution program" is valid is used for the FX 3U /FX 3UC PLC whose version is earlier than 3.00, the FX 3U /FX 3UC PLC does not run normally.
Page 183 of the Mitsubishi Electronics MELSEC FX3S user manual — 7. Basic Instruction
Page 183 · click to enlarge
Page 183

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7. Basic Instruction

This chapter explains types and functions of basic sequence instructions. For beginners to sequence control, we offer "Introduction Course" and "Relay Ladder Course" learning texts for reference. We can also offer the PLC learning software "Beginner Course".

Mnemonic Name Symbol Function Applicable devices Reference

Initial logical operation contact type NO (normally open)

X,Y,M,S,D .b,T,C Section 7.1

Initial logical operation contact type NC (normally closed)

X,Y,M,S,D .b,T,C Section 7.1

LDP Load Pulse Initial logical operation of rising edge pulse X,Y,M,S,D .b,T,C Section 7.5

LDF Load Falling Pulse Initial logical operation of falling/trailing edge pulse X,Y,M,S,D .b,T,C Section 7.5

AND AND Serial connection of NO (normally open) contacts X,Y,M,S,D .b,T,C Section 7.3

ANI AND Inverse Serial connection of NC (normally closed) contacts X,Y,M,S,D .b,T,C Section 7.3

Specified the Device & Constant

ANDP AND Pulse Serial connection of rising edge pulse X,Y,M,S,D .b,T,C Section 7.5

ANDF AND Falling Pulse Serial connection of falling/ trailing edge pulse X,Y,M,S,D .b,T,C Section 7.5

OR OR Parallel connection of NO (normally open) contacts X,Y,M,S,D .b,T,C Section 7.4

ORI OR Inverse Parallel connection of NC (normally closed) contacts X,Y,M,S,D .b,T,C Section 7.4

ORP OR Pulse Parallel connection of rising edge pulse X,Y,M,S,D .b,T,C Section 7.5

ORF OR Falling Pulse Parallel connection of falling/ trailing edge pulse X,Y,M,S,D .b,T,C Section 7.5

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 23 more labels / short text on this page
7 Basic Instruction · Introduction · Overview · Contact Instruction · Applicable devices · LD Load · Instruction List · Applicable devices · LDI Load Inverse · Applicable devices · Devices in Detail · Applicable devices · Applicable devices · Applicable devices · Applicable devices · Applicable devices · Before Programming · Applicable devices · Applicable devices · Basic Instruction · Applicable devices · Applicable devices · FNC00-FNC09 Program Flow
Page 184 of the Mitsubishi Electronics MELSEC FX3S user manual — END
Page 184 · click to enlarge
Page 184

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

Mnemonic Name Symbol Function Applicable devices Reference

ANB AND Block Serial connection of multiple parallel circuits − Section 7.7

ORB OR Block Parallel connection of multiple contact circuits − Section 7.6

MPS Memory Point Store

Stores the current result of the internal PLC operations

Section 7.8

MPS

MRD Memory Read Reads the current result of the initial PLC operations Section 7.8

MRD

MPP Memory POP Pops (recalls and removes) the currently stored result Section 7.8

MPP

Invert the current result of the internal PLC operations

INV

− Section 7.10

Conversion of operation result to leading edge pulse

MEP MEP

− Section 7.11

Conversion of operation result to trailing edge pulse

MEF MEF

− Section 7.11

OUT OUT Final logical operation type coil drive Y,M,S,D .b,T,C Section 7.2

SET SET Set bit device latch ON Y,M,S,D .b Section 7.13

RST Reset Reset bit device OFF Y,M,S,D .b,T,C, D,R,V,Z Section 7.13

PLS Pulse Rising edge pulse Y,M Section 7.12

PLF Pulse Falling Falling/trailing edge pulse Y,M Section 7.12

MC Master Control Denotes the start of a master control block Y,M Section 7.9

Applicable devices MC N

MCR Master Control Reset

Denotes the end of a master control block − Section 7.9

MCR N

NOP No Operation No operation or null step − Section 7.14

END END Program end, I/O refresh and return to step 0 − Section 7.15

END

Show 13 more labels / short text on this page
7 Basic Instruction · Connection Instruction · − · INV Inverse · Out Instruction · Applicable devices · SET Applicable devices · RST Applicable devices · PLS Applicable devices · PLF Applicable devices · Master Control Instruction · Other Instruction · End Instruction
Page 185 of the Mitsubishi Electronics MELSEC FX3S user manual — Y000
Page 185 · click to enlarge
Page 185

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.1 LD, LDI 1

7.1 LD, LDI

Outline

LD and LDI instructions are contacts connected to bus lines. When combined with ANB instruction described later, LD and LDI instructions can be used for the start of branches.

1. Instruction format

LD

LD

Continuous Operation Pulse (Single) Operation

LDI

LDI

Continuous Operation Pulse (Single) Operation

→ For the number of instruction steps, refer to Section 7.16.

2. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

LD 3 3 S 1 3 S 1 S

2 S 3 S 4

Specified the Device & Constant

LDI 3 3 S 1 3 S 1 S

2 S 3 S 4

S1: Special auxiliary relays (M) and 32-bit counters (C) cannot be indexed with index registers (V and Z). S2: State relays (S) cannot be indexed with index registers (V and Z). S3: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S4: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. LD instruction (initial logical operation, NO contact type)

Circuit program List program

LD OUT 0000 0001 X000 Y000

Connection to bus line

Y000

ON ON X000

ON ON Y000

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 24 more labels / short text on this page
7 Basic Instruction · Introduction · Overview · Basic Instruction · Mnemonic Operation Condition · Load · − · Instruction List · Basic Instruction · Mnemonic Operation Condition · Load Inverse · − · Devices in Detail · Instruc- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · tion · Before Programming · Basic Instruction · LD instruction · Bus line · Timing chart · FNC00-FNC09 Program Flow
Page 186 of the Mitsubishi Electronics MELSEC FX3S user manual — Errors
Page 186 · click to enlarge
Page 186

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.1 LD, LDI

2. LDI instruction (initial logical operation, NC contact type)

Circuit program List program

LDI OUT 0000 0001 X000 Y000

Connection to bus line

Y000

ON ON X000

Y000

ON ON

3. Indexing *1

Devices used in LD and LDI instructions allow indexing with index registers (V and Z). (State relays (S), special auxiliary relays (M), 32-bit counters (C), and "D .b" cannot be indexed.)

V0 to V7 and Z0 to Z7 are available in indexing. When used devices are inputs (X) and outputs (Y), values of index registers (V and Z) are converted into octal numbers, and then added. Example: When the value of V0 is 10, LD contact

Circuit program List program

LD OUT 0000 0003 X000V0 Y000

Y000

is set to ON (becomes conductive) or OFF (becomes non-conductive) by X012.

*1. This function is supported only in FX3U/FX3UC PLCs.

4. Bit specification of data register (D) A bit in data register (D) can be specified as a device used in LD and LDI instructions.

When specifying a bit in data register, input "." after a data register (D) number, and then input a bit number (0 to F) consecutively. Only 16-bit data registers are available. Specify a bit number as "0, 1, 2, ... 9, A, B, ... F" from the least significant bit. Example: In the example shown on the left, LD

Circuit program List program

LD OUT 0000 0003 D0.3 Y000

Y000

contact is set to ON (becomes conductive) or OFF (becomes non- conductive) by bit 3 of D0.

*1. This function is supported only in FX3U/FX3UC PLCs.

Errors

  • When an I/O number used in LD or LDI instruction does not exist due to indexing, M8316 (Non-existing I/O specification error) turns ON.
  • When the device number of a device (M, T or C) other than I/O used in LD or LDI instruction does not exist due to indexing, an operation error (error code: 6706) occurs.
Show 4 more labels / short text on this page
7 Basic Instruction · LDI instruction · Bus line · Timing chart
Page 187 of the Mitsubishi Electronics MELSEC FX3S user manual — M101
Page 187 · click to enlarge
Page 187

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.2 OUT 1

7.2 OUT

Outline

OUT instruction drives coils of output relays (Y), auxiliary relays (M), state relays (S), timers (T) and counters (C).

1. Instruction format

OUT

OUT

Continuous Operation Pulse (Single) Operation

OUT

→ For the number of instruction steps, refer to Section 7.16.

2. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

OUT 3 S 1 3 S 1 S

2 S 3 S 5

Set value 3 S

S1: Special auxiliary relays (M) and 32-bit counters (C) cannot be indexed with index registers (V and Z). S2: State relays (S) cannot be indexed with index registers (V and Z). S3: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S4: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S5: This function is supported only in FX3U/FX3UC PLCs.

Specified the Device & Constant

Explanation of function and operation

1. When a bit device is used A device described in OUT instruction turns ON or OFF according to the driven contact status. Parallel OUT instructions can be used consecutively as many times as necessary. In the program example shown below, OUT M100 and OUT M101 are parallel. If two or more OUT instructions are executed for the same device number, however, it results in a double output (double coil) operation.

Circuit program List program

Drive contact of OUT instruction

0000 0001 0002 0003 0004

LD OUT LDI OUT OUT

X000 Y000 X001 M100 M101

Y000

M100

Program step numbers are automatically controlled.

M101

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 19 more labels / short text on this page
7 Basic Instruction · Introduction · Overview · Basic Instruction · Mnemonic Operation Condition · − · Instruction List · Instruc- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · tion · Devices in Detail · Before Programming · Basic Instruction · OUT instruction · OUT instruction · OUT instruction · FNC00-FNC09 Program Flow
Page 188 of the Mitsubishi Electronics MELSEC FX3S user manual — 7.2 OUT
Page 188 · click to enlarge
Page 188

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.2 OUT

Mitsubishi Electronics MELSEC FX3S — 7.2 OUT diagram (page 188)
Fig. 81
2. When a timer or counter is used The set value is required after OUT instruction for the counting coil of a timer or counter. The set value can be specified directly by a decimal number (K) or indirectly using a data register (D) or extension register (R).
1. Direct specification
Mitsubishi Electronics MELSEC FX3S — 7.2 OUT diagram (page 188)
Fig. 82

The set value of a timer or counter can be specified directly by a decimal number (K).

2. Indirect specification
Mitsubishi Electronics MELSEC FX3S — 7.2 OUT diagram (page 188)
Fig. 83

The set value of a timer or counter can be set by a data register (D) or extension data register (R). At this time, the current value of the data register (D) or extension register (R) is regarded as the set value of the timer or counter. It is necessary to write the set value to a data register (D) or extension register (R) used for the set value by MOV instruction, DSW instruction or display unit before driving the timer or counter.

3. Setting range of timers and counters The table below shows the set value range of timers and counters, the actual timer constants and the number of program steps (including the set value) for OUT instruction.
Mitsubishi Electronics MELSEC FX3S — 7.2 OUT diagram (page 188)
Fig. 84

Timer/counter Setting range (Value of K or current value of D or R) Actual set value Number of steps

1 ms timer 1 to 32767 0.001 to 32.767 sec 3

10 ms timer 1 to 32767 0.01 to 327.67 sec 3 100 ms timer 0.1 to 3276.7 sec

16-bit counter 1 to 32767 Same as left 3

32-bit counter −2,147,483,648 to +2,147,483,647 Same as left 5

7 Basic Instruction

Page 189 of the Mitsubishi Electronics MELSEC FX3S user manual — Errors
Page 189 · click to enlarge
Page 189

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.2 OUT 1

3. Indexing *1

Devices used in OUT instruction can be indexed with index registers (V and Z). (State relays (S), special auxiliary relays (M), 32-bit counters (C), and "D .b" cannot be indexed.)

The index registers V0 to V7 and Z0 to Z7 are available for indexing. When a used device is an input (X) or output (Y), the value of an index register (V or Z) is converted into an octal number, and then added. Example: When the value of Z0 is "20", Y024

Circuit program List program

LD OUT 0000 0001 X000 Y000Z0 X000

Y000Z0

turns ON or OFF.

*1. This function is supported only in FX3U/FX3UC PLCs.

4. Bit specification of data register (D) *1

A bit in data register (D) can be specified as a device used in OUT instruction.

Circuit program List program

When specifying a bit in data register, input "." after a data register (D) number, and then input a bit number (0 to F) consecutively. Only 16-bit data registers are available. Specify a bit number as "0, 1, 2, ... 9, A, B, ... F" from the least significant bit. Example: In the example shown on the left, the

LD OUT 0000 0001 X000 D0.3

bit 3 of D0 turns ON or OFF when X000 turns ON or OFF.

*1. This function is supported only in FX3U/FX3UC PLCs.

Specified the Device & Constant

Caution

  • When a special internal relay (M), timer or counter is used, program steps increase as described in "Setting range of timers and counters" on the previous page.
  • Do not use the last bit number of a data register (D) or extension register (R) as the set value of a 32-bit counter.

Errors

  • When an I/O number used in OUT instruction does not exist due to indexing, M8316 (Non-existing I/O specification error) turns ON.
  • When the device number of a device (M, T or C) other than I/O used in OUT instruction does not exist due to indexing, an operation error (error code: 6706) occurs.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 8 more labels / short text on this page
7 Basic Instruction · Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 190 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 190 · click to enlarge
Page 190

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.3 AND, ANI

7.3 AND, ANI

Outline

AND and ANI instructions connect one contact in series. The number of contacts connected in series is not limited, so AND and ANI instructions can be used consecutively as many times as necessary. Output to another coil by way of a contact after the OUT instruction is called cascade output. Such a cascade output can be repeated as many times as necessary as long as the order is correct.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 190)
Fig. 85 · 1. Instruction format

→ For the number of instruction steps, refer to Section 7.16.

2. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 2. Applicable devices diagram (page 190)
Fig. 86 · 2. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

AND 3 3 S 1 3 S 1 S

ANI 3 3 S 1 3 S 1 S

S1: Special auxiliary relays (M) and 32-bit counters (C) cannot be indexed with index registers (V and Z). S2: State relays (S) cannot be indexed with index registers (V and Z). S3: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S4: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. AND instruction (serial connection of NO (normally open) contacts)

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 190)
Fig. 87 · Explanation of function and operation

7 Basic Instruction

Page 191 of the Mitsubishi Electronics MELSEC FX3S user manual — Errors
Page 191 · click to enlarge
Page 191

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.3 AND, ANI 1

2. ANI instruction (serial connection of NC (normally closed) contacts)

Circuit program List program

X000 LD ANI OUT

X002 X000 Y003

Contact connected in series

Y003

ON ON X002

ON ON X000

ON Y003

ON

3. Indexing *1

Devices used in AND and ANI instruction can be indexed with index registers (V and Z). (State relays (S), special auxiliary relays (M), 32-bit counters (C), and "D .b" cannot be indexed.)

The index registers V0 to V7 and Z0 to Z7 are available for indexing. When a used device is an input (X) or output (Y), the value of an index register (V, Z) is converted into an octal number, and then added. Example: When the value of V0 is "10", AND

Circuit program List program

Specified the Device & Constant

X000V0 LD AND OUT

X002 X000V0 Y003

Y003

contact is set to ON or OFF by X012.

*1. This function is supported only in FX3U/FX3UC PLCs.

4. Bit specification of data register (D) *1

A bit in data register (D) can be specified as a device used in AND and ANI instructions.

When specifying a bit in data register, input "." after a data register (D) number, and then input a bit number (0 to F) consecutively. Only 16-bit data registers are available. Specify a bit number as "0, 1, 2, ... 9, A, B, ... F" from the least significant bit. Example: In the example shown on the left, AND

Circuit program List program

D0.3 LD AND OUT

X002 D0.3 Y003

Y003

contact turns ON (becomes conductive) when the bit 3 of D0 turns ON.

*1. This function is supported only in FX3U/FX3UC PLCs.

Errors

  • When an I/O number used in AND or ANI instruction does not exist due to indexing, M8316 (Non-existing I/O specification error) turns ON.

FNC10-FNC19 Move & Compare

  • When the device number of a device (M, T or C) other than I/O used in AND or ANI instruction does not exist due to indexing, an operation error (error code: 6706) occurs.

FNC20-FNC29 Arith. & Logic Operation

Show 15 more labels / short text on this page
7 Basic Instruction · Introduction · ANI instruction · 0000 0001 0002 · Overview · Timing chart · LD instruction · Instruction List · ANI instruction · Devices in Detail · 0000 0001 0004 · Before Programming · Basic Instruction · 0000 0001 0004 · FNC00-FNC09 Program Flow
Page 192 of the Mitsubishi Electronics MELSEC FX3S user manual — K30
Page 192 · click to enlarge
Page 192

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.3 AND, ANI

Program examples

Circuit program List program

0000 0001 0002 0003 0004 0005 0006 0007

LD AND OUT LD ANI OUT AND OUT (SP) LD ANI OUT

X000 X001 Y003 X002 X003 Y004 X004 T0 K30 X005 T0 Y005

Contact connected in series X001

Y003

Contact connected in series

Y004

Contact connected in series

Contact connected in series

K30

T0

T0

Y005

Show 6 more labels / short text on this page
7 Basic Instruction · AND instruction · ANI instruction X003 · AND instruction · 0010 0011 0012 · ANI instruction
Page 193 of the Mitsubishi Electronics MELSEC FX3S user manual — ON ON
Page 193 · click to enlarge
Page 193

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.4 OR, ORI 1

7.4 OR, ORI

Outline

OR and ORI instructions are used to connect one contact in parallel. If two or more contacts are connected in series, use ORB instruction described later to connect such a serial circuit block to another circuit in parallel. A step containing OR or ORI instruction is connected in parallel to a preceding step containing LD or LDI instruction. There is no limitation in the number of times of parallel connection.

1. Instruction format

OR

OR

Continuous Operation Pulse (Single) Operation

OR

ORI

ORI

Continuous Operation Pulse (Single) Operation

→ For the number of instruction steps, refer to Section 7.16.

2. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

Specified the Device & Constant

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

OR 3 3 S 1 3 S 1 S

2 S 3 S 4

ORI 3 3 S 1 3 S 1 S

2 S 3 S 4

S1: Special auxiliary relays (M) and 32-bit counters (C) cannot be indexed with index registers (V and Z). S2: State relays (S) cannot be indexed with index registers (V and Z). S3: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S4: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. OR instruction (parallel connection of NO (normally open) contacts)

Circuit program List program

X000 X001 Y000 Y000

LD OR OUT

ON ON

FNC10-FNC19 Move & Compare

ON ON

ON ON

ON

Y000

FNC20-FNC29 Arith. & Logic Operation

Show 24 more labels / short text on this page
7 Basic Instruction · Introduction · Overview · Basic Instruction · Mnemonic Operation Condition · Instruction List · − · Basic Instruction · Mnemonic Operation Condition · − · OR Inverse · Devices in Detail · Instruc- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · tion · Before Programming · Basic Instruction · 0000 0001 0002 · FNC00-FNC09 Program Flow · Timing chart · LD instruction X000 · OR instruction
Page 194 of the Mitsubishi Electronics MELSEC FX3S user manual — 4. Indexing *1
Page 194 · click to enlarge
Page 194

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.4 OR, ORI

2. ORI instruction (parallel connection of NC (normally closed) contacts)

Mitsubishi Electronics MELSEC FX3S — 7.4 OR, ORI diagram (page 194)
Fig. 88
3. Relationship with ANB instruction The parallel connection by OR or ORI instruction is connected to the preceding LD or LDI instruction in principle. After ANB instruction, however, the parallel connection by OR or ORI instruction is connected to the second preceding LD or LDI instruction.
Mitsubishi Electronics MELSEC FX3S — 7.4 OR, ORI diagram (page 194)
Fig. 89

4. Indexing *1

Devices used in OR and ORI instruction can be indexed with index registers (V and Z). (State relays (S), special auxiliary relays (M), 32-bit counters, and "D .b" cannot be indexed.)

Mitsubishi Electronics MELSEC FX3S — 4. Indexing *1 diagram (page 194)
Fig. 90 · 4. Indexing *1

The index registers V0 to V7 and Z0 to Z7 are available for indexing. When the used device is an input (X) or output (Y), the value of an index register (V or Z) is converted into an octal number, and then added. Example: When the value of V0 is "10", OR

contact is set to ON (becomes conductive) or OFF (becomes non- conductive) by X013.

*1. This function is supported only in FX3U/FX3UC PLCs.

7 Basic Instruction

Page 195 of the Mitsubishi Electronics MELSEC FX3S user manual — Errors
Page 195 · click to enlarge
Page 195

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.4 OR, ORI 1

5. Bit specification of data register (D) *1

A bit in data register (D) can be specified as a device used in OR and ORI instructions.

When specifying a bit in data register, input "." after a data register (D) number, and then input a bit number (0 to F) consecutively. Only 16-bit data registers are available. Specify a bit number as "0, 1, 2, ... 9, A, B, ... F" from the least significant bit. Example: In the example shown on the left, OR

Circuit program List program

X000 D0.3 Y000 Y000

LD OR OUT

contact is set to ON (becomes conductive) or OFF (becomes non- conductive) by bit 3 of D0.

*1. This function is supported only in FX3U/FX3UC PLCs.

Errors

  • When an I/O number used in OR or ORI instruction does not exist due to indexing, M8316 (Non-existing I/O specification error) turns ON.
  • When the device number of a device (M, T or C) other than I/O used in OR or ORI instruction does not exist due to indexing, an operation error (error code: 6706) occurs.

Specified the Device & Constant

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 9 more labels / short text on this page
7 Basic Instruction · Introduction · 0000 0001 0004 · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 196 of the Mitsubishi Electronics MELSEC FX3S user manual — 2. Applicable devices
Page 196 · click to enlarge
Page 196

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.5 LDP, LDF, ANDP, ANDF, ORP, ORF

7.5 LDP, LDF, ANDP, ANDF, ORP, ORF

Outline

LDP, ANDP, and ORP instructions for contacts detect the rising edge, and become active during one operation cycle only at the rising edge of a specified bit device (that is, when the bit device turns from OFF to ON). Contact instructions LDF, ANDF and ORF detect the falling edge, and become active during one operation cycle only at the falling edge of a specified bit device (that is, when the bit device turns from ON to OFF).

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 196)
Fig. 91 · 1. Instruction format

→ For the number of instruction steps, refer to Section 7.16.

2. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 2. Applicable devices diagram (page 196)
Fig. 92 · 2. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S: This function is supported only in FX3U/FX3UC PLCs.

7 Basic Instruction

Page 197 of the Mitsubishi Electronics MELSEC FX3S user manual — 7.5 LDP, LDF, ANDP, ANDF, ORP, ORF
Page 197 · click to enlarge
Page 197

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

Mitsubishi Electronics MELSEC FX3S — 7.5 LDP, LDF, ANDP, ANDF, ORP, ORF diagram (page 197)
Fig. 93
1. LDP, ANDP, and ORP instructions (initial logical operation of rising edge pulse, serial connection of rising edge pulse, and parallel connection of rising edge pulse)

0000 LDP X000 0002 ORP X001 0004 OUT M0 0005 LD M8000 0006 ANDP X002 0008 OUT M1 M8000 X002

In the example shown above, M0 or M1 is ON during only one operation cycle when X000 to X002 turn from OFF to ON.

7 Basic Instruction

Page 198 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Bit specification of a data register (D) *1
Page 198 · click to enlarge
Page 198

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.5 LDP, LDF, ANDP, ANDF, ORP, ORF

2. LDF, ANDF, and ORF instructions (initial logical operation of falling/trailing edge pulse, serial connection of falling/trailing edge pulse, and parallel connection of falling/trailing edge pulse)
Mitsubishi Electronics MELSEC FX3S — 7.5 LDP, LDF, ANDP, ANDF, ORP, ORF diagram (page 198)
Fig. 94

0000 LDF X000 0002 ORF X001 0004 OUT M0 0005 LD M8000 0006 ANDF X002 0008 OUT M1

In the example shown above, M0 or M1 is ON during only one operation cycle when X000 to X002 turn OFF from ON.

3. Bit specification of a data register (D) *1

A bit in data register (D) can be specified as a device used in LDP, LDF, ANDP, ANDF, ORP and ORF instructions.

Mitsubishi Electronics MELSEC FX3S — 3. Bit specification of a data register (D) *1 diagram (page 198)
Fig. 95 · 3. Bit specification of a data register (D) *1

When specifying a bit in a data register, input "." after a data register (D) number, and then input a bit number (0 to F) consecutively. Only 16-bit data registers are available. Specify a bit number as "0, 1, 2, ... 9, A, B, ... F" from the least significant bit. Example: In the example shown on the left, LDP

contact turns ON (becomes conductive) or OFF (becomes non- conductive) when bit 3 of D0 turns ON or OFF.

*1. This function is supported only in FX3U/FX3UC PLCs.

7 Basic Instruction

Page 199 of the Mitsubishi Electronics MELSEC FX3S user manual — 4. Output drive side The following two circuits offer the same operation:
Page 199 · click to enlarge
Page 199

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

Mitsubishi Electronics MELSEC FX3S — 7.5 LDP, LDF, ANDP, ANDF, ORP, ORF diagram (page 199)
Fig. 96

4. Output drive side The following two circuits offer the same operation:

In each circuit, M6 is ON during only one operation cycle when X010 turns from OFF to ON.

In each circuit, MOV instruction is executed only once when X020 turns from OFF to ON.

7 Basic Instruction

Page 200 of the Mitsubishi Electronics MELSEC FX3S user manual — 7.5 LDP, LDF, ANDP, ANDF, ORP, ORF
Page 200 · click to enlarge
Page 200

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.5 LDP, LDF, ANDP, ANDF, ORP, ORF

5. Differences in the operation caused by auxiliary relay (M) numbers When an auxiliary relay (M) is specified as a device in LDP, LDF, ANDP, ANDF, ORP and ORF instructions, the operation varies depending on the device number range as shown in the figure below.

Mitsubishi Electronics MELSEC FX3S — 7.5 LDP, LDF, ANDP, ANDF, ORP, ORF diagram (page 200)
Fig. 97

After M0 is driven by X000, all contacts [1] to [4] corresponding to M0 are activated.

  • The contacts [1] to [3] detect the rising edge of M0.
  • Because of LD instruction, the contact [4] is conductive while M0 is ON.

From M2800 driven by X000, the program is divided into the upper block (block A) and the lower block (block B). In each of the blocks A and B, only the first contact which detects the rising or falling edge is activated. Because of LD instruction, the contact in the block C is conductive while M2800 is ON. By utilizing these characteristics, "transition of state by same signal" in a step ladder circuit can be efficiently programmed.

Mitsubishi Electronics MELSEC FX3S — 7.5 LDP, LDF, ANDP, ANDF, ORP, ORF diagram (page 200)
Fig. 98

7 Basic Instruction ·

Page 201 of the Mitsubishi Electronics MELSEC FX3S user manual — 2. Cautions on writing during RUN
Page 201 · click to enlarge
Page 201

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.5 LDP, LDF, ANDP, ANDF, ORP, ORF 1

Cautions

1. Cautions when the LDP, LDF, ANDP, ANDF, ORP, or ORF instruction programmed in the same step is executed two or more times within one operation cycle When LDP, LDF, ANDP, ANDF, ORP or ORF instruction programmed in the same step is executed two or more times within one operation cycle, the following operation results:

Programs executed two or more times

  • Program between FOR and NEXT instructions

FNC 08 FOR K

  • Program which executes the same subroutine program from two or more CALL instructions during one operation cycle
  • Program which jumps to a label (P) in a smaller step number by CJ instruction

FNC 09 NEXT

Operation

1. When a device turns from OFF to ON 1st time: LDP, ANDP or ORP instruction turns ON. 2nd time and later: When the device status is the same as the time when the instruction was executed last, the instruction turns OFF.
2. When a device turns OFF from ON 1st time: LDF, ANDF or ORF instruction turns ON. 2nd time and later: When the device status is the same as the time when the instruction was executed last, the instruction turns OFF.

2. Cautions on writing during RUN

1) Instructions for falling edge pulse When writing is completed during RUN for a circuit including an instruction for falling edge pulse (LDF, ANDF, or ORF instruction), the instruction for falling edge pulse is not executed regardless of the ON/OFF status of the target device of the instruction for falling edge pulse. When writing is completed during RUN for a circuit including an instruction for falling edge pulse (PLF instruction), the instruction for falling edge pulse is not executed regardless of the ON/OFF status of the operation condition device. It is necessary to set to ON the target device or operation condition device once and then set it to OFF for executing the instruction for falling edge pulse.

Specified the Device & Constant

2. Instructions for rising edge pulse When writing is completed during RUN for a circuit including an instruction for rising edge pulse, the instruction for rising edge pulse is executed if a target device of the instruction for rising edge pulse or the operation condition device is ON. Target instructions for rising edge pulse: LDP, ANDP, ORP, and pulse operation type applied instructions (such as MOVP)

Contact ON/OFF status (while writing is executed during RUN) Instruction for rising edge pulse Instruction for falling edge pulse

OFF Not executed Not executed

ON Executed*1 Not executed

*1. PLS instruction is not executed.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 8 more labels / short text on this page
7 Basic Instruction · Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 202 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 202 · click to enlarge
Page 202

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.6 ORB

7.6 ORB

Outline

A circuit in which two or more contacts are connected in series is called serial circuit block.

1. Instruction format

ORB

Continuous Operation Pulse (Single) Operation

2. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 2. Applicable devices diagram (page 202)
Fig. 99 · 2. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. ORB instruction (parallel connection of multiple contact circuits) When connecting serial circuit blocks in parallel, use LD or LDI instruction at the start of branch, and use ORB instruction at the end of branch. ORB instruction is an independent instruction not associated with any device number in the same way as ANB instruction described later. When there are many parallel circuits, ORB instruction can be used for each circuit block to connect them.
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 202)
Fig. 100 · Explanation of function and operation

Appropriate program 0000 LD X000 0001 AND X001 0002 LD X002 0003 AND X003 0004 0005 LDI X004 0006 AND X005 0007 0008 OUT Y006

Inappropriate program 0000 LD X000 0001 AND X001 0002 LD X002 0003 AND X003 0004 LDI X004 0005 AND X005 0006 0007 0008 OUT Y006

Caution

There is no limitation in the number of parallel circuits which can be connected by ORB instructions (in the case of appropriate program shown above). Though ORB instructions can be used at one time, note that the repeated use of LD or LDI instruction is limited to 8 or less (in the case of inappropriate program shown above).

Show 6 more labels / short text on this page
7 Basic Instruction · Basic Instruction · Mnemonic Operation Condition · 1 step ORB · OR Block · −
Page 203 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 203 · click to enlarge
Page 203

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.7 ANB 1

7.7 ANB

Outline

Use ANB instruction to connect a branch circuit (parallel circuit block) to the preceding circuit in series. Use LD or LDI instruction at the start of branch. After completing a parallel circuit block, connect the parallel circuit block to the preceding circuit in series by ANB instruction. When there are many parallel circuits, ANB instruction can be used in each circuit block to connect them.

1. Instruction format

ANB

Continuous Operation Pulse (Single) Operation

2. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

ANB There are no applicable devices.

Explanation of function and operation

1. ANB instruction (serial connection of multiple parallel circuits)

Specified the Device & Constant

Circuit program List program

LD

ANB

X000 X002

0000 LD X000 0001 OR X001 0002 LD X002 Branch start point 0003 AND X003 0004 LDI X004 0005 AND X005 0006 ORB Parallel block is completed. 0007 OR X006 0008 It is connected to the 0009 OR X003 preceding circuit in series. 0010 OUT Y007

Y007

X004 X005

ORB

ANB

OR instruction before ANB instruction

OR instruction after ANB instruction

Caution

There is no limitation in the number of ANB instruction. Though ANB instructions can be used at one time, note that the repeated use of LD or LDI instruction is limited to 8 or less in the same way as ORB instruction.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 19 more labels / short text on this page
7 Basic Instruction · Introduction · Overview · Basic Instruction · Mnemonic Operation Condition · 1 step ANB · AND Block · − · Instruction List · Instruc- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · tion · Devices in Detail · Before Programming · X003 Parallel block · Basic Instruction · FNC00-FNC09 Program Flow
Page 204 of the Mitsubishi Electronics MELSEC FX3S user manual — Error
Page 204 · click to enlarge
Page 204

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.8 MPS, MRD, MPP

7.8 MPS, MRD, MPP

Outline

FX3G, FX3U FX3GC and FX3UC PLCs have 11 memories called "Stack" which store the intermediate result (ON or OFF) of operations.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 204)
Fig. 101 · 1. Instruction format

2. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 2. Applicable devices diagram (page 204)
Fig. 102 · 2. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

These instructions are convenient in programming branched multi-output circuits.

1. MPS, MRD, and MPP instructions (stores the current result of the internal PLC operations, reads the current result of the internal PLC operations, and pops (recalls and removes) the currently stored result)
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 204)
Fig. 103 · Explanation of function and operation

0018 LD X004 0019 0020 AND X005 0021 OUT Y002 0022 0023 AND X006 0024 OUT Y003 0025 0026 OUT Y004 0027 0028 AND X007 0029 OUT Y005 0030 END

  • Use MPS instruction to store the intermediate result of operation, and then drive the output Y002.
  • Use MRD instruction to read the stored data, and then drive the output Y003. MRD instruction can be programmed as many times as necessary.
  • In the final output circuit, use MPP instruction instead of MRD instruction. MPP instruction reads the stored data described above, and then resets it.

Error

MPS instruction can be used two or more times. However, the difference between number of MPS instructions and the number of MPP instructions should be 11 or less, and should be 0 at the end.

7 Basic Instruction

Page 205 of the Mitsubishi Electronics MELSEC FX3S user manual — MPP
Page 205 · click to enlarge
Page 205

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.8 MPS, MRD, MPP 1

Program examples

1. Program example 1: One stack Only one stack is used in this example.

Circuit program List program

MPS

X000 X001 X002

0000 LD X000 0001 AND X001 0002 0003 AND X002 0004 OUT Y000 0005 0006 OUT Y001 0007 LD X003 0008 0009 AND X004 0010 OUT Y002 0011 0012 AND X005 0013 OUT Y003 0014 LD X006 0015 0016 AND X007 0017 OUT Y004 0018 0019 AND X010 0020 OUT Y005 0021 0022 AND X011 0023 OUT Y006 0024 0025 AND X012 0026 OUT Y007

Y000

MPS

Y001

MPP

MPP

MPS

X003 X004

Y002

MPS

Y003 X005

MPP

MPP

MPS

MPS

X006 X007

Y004

Y005 X010

MRD

Specified the Device & Constant

MRD

Y006 X011

MRD

MRD

Y007 X012

MPP

MPP

2. Program example 2: One stack with ANB and ORB instructions

Circuit program List program

MPS

X000 X001

Y000

0000 LD X000 0001 0002 LD X001 0003 OR X002 0004 ANB 0005 OUT Y000 0006 0007 LD X003 0008 AND X004 0009 LD X005 0010 AND X006 0011 ORB 0012 ANB 0013 OUT Y001 0014 0015 AND X007 0016 OUT Y002 0017 LD X010 0018 OR X011 0019 ANB 0020 OUT Y003

MPS

Y001 X004

X005 X006

MRD

MRD

Y002

MPP

Y003 X010

FNC10-FNC19 Move & Compare

MPP

FNC20-FNC29 Arith. & Logic Operation

Show 8 more labels / short text on this page
7 Basic Instruction · Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 206 of the Mitsubishi Electronics MELSEC FX3S user manual — 7.8 MPS, MRD, MPP
Page 206 · click to enlarge
Page 206

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.8 MPS, MRD, MPP

3. Program example 3: Two stacks
Mitsubishi Electronics MELSEC FX3S — 7.8 MPS, MRD, MPP diagram (page 206)
Fig. 104

0000 LD X000 0001 0002 AND X001 0003 0004 AND X002 0005 OUT Y000 0006 0007 AND X003 0008 OUT Y001 0009 0010 AND X004 0011 0012 AND X005 0013 OUT Y002 0014 0015 AND X006 0016 OUT Y003

4. Program example 4: Four stacks
Mitsubishi Electronics MELSEC FX3S — 7.8 MPS, MRD, MPP diagram (page 206)
Fig. 105

0000 LD X000 0001 0002 AND X001 0003 0004 AND X002 0005 0006 AND X003 0007 0008 AND X004

0009 OUT Y000 0010 0011 OUT Y001 0012 0013 OUT Y002 0014 0015 OUT Y003 0016 0017 OUT Y004

0000 LD X000 0001 OUT Y004 0002 AND X001 0003 OUT Y003 0004 AND X002 0005 OUT Y002 0006 AND X003 0007 OUT Y001 0008 AND X004 0009 OUT Y000

In programming a circuit on the upper side, it is necessary to MPS instruction three times. By changing the circuit on the upper side into the circuit on the lower side, the same contents can be programmed easily without MPS instruction.

7 Basic Instruction

Page 207 of the Mitsubishi Electronics MELSEC FX3S user manual — MCR N 0
Page 207 · click to enlarge
Page 207

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.9 MC, MCR 1

7.9 MC, MCR

Outline

When MC instruction is executed, the bus line (LD or LDI point) is moved to a position after MC contact. The bus line can be returned to the original position by MCR instruction. By changing a device (Y or M) number, MC instruction can be used as many times as necessary. If the same device number is used twice, however, it results in the double coil operation in the same way as OUT instruction.

1. Instruction format

MC

MC

Continuous Operation Pulse (Single) Operation

MCR

Continuous Operation Pulse (Single) Operation

→ For the number of steps of MC instruction, refer to Section 7.16.

2. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

Specified the Device & Constant

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

MC 3 S

MCR There are no applicable devices.

SExcept special auxiliary relays (M)

Explanation of function and operation

1. MC and MCR instructions (denotes the start of a master control block and denotes the end of a master control block) When MC instruction is executed, the bus line is moved to a position after MC contact. Drive instructions connected to the bus line after the MC contact execute each operation only when the MC instruction is executed, and execute each operation in the contact OFF status regardless of the contact status before drive instructions when a MC instruction is not executed. If an instruction (such as FOR/NEXT, EI and DI instruction) not requiring a contact instruction exists in a circuit using master control, such an instruction is executed regardless of the MC instruction execution command. In the program example below, the instructions from MC to MCR are executed as they are while the input X000 is ON. However, while the input X000 is OFF, each driven device offers the following operation:

Timers (except retentive type timers) and devices driven by OUT instruction: Turn OFF. Retentive type timers, counters and devices driven by SET/RST instruction: Hold the current status. The expressions of circuit programs used to explain operations are circuits (for reading or monitoring) of GX Works2 and GX Developer.

Circuit program List program

0000 LD X000 0001 MC N000 SP M100 0004 LD X001 0005 OUT Y000 0006 LD X002 0007 OUT Y001 0008 MCR N 0 ← Two-step instruction

MC N 0 M100

FNC10-FNC19 Move & Compare

N 0 M100

Y000

X002 Y001

FNC20-FNC29 Arith. & Logic Operation

MCR N 0

← Write MCR N0 instruction.

Show 24 more labels / short text on this page
7 Basic Instruction · Introduction · Overview · Basic Instruction · Mnemonic Operation Condition · Instruction List · Master Control · − · Mnemonic Operation Condition · Basic Instruction · 2 steps MCR · Master Control · − · Devices in Detail · Reset · Instruc- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · tion · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow · Three-step instruction
Page 208 of the Mitsubishi Electronics MELSEC FX3S user manual — Program examples
Page 208 · click to enlarge
Page 208

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.9 MC, MCR

Caution

1. A circuit error (Error code: 6611) occurs when an instruction connected the bus line (such as LD and LDI) is not present just after the MC instruction.
2. Cautions on writing during RUN The PLC cannot detect errors if an instruction is added between the MC instruction and the N instruction by write during RUN. The PLC can detect errors after it is set to the STOP mode once and then to the RUN mode again.

Program examples

1. When the nesting structure is not adopted
Mitsubishi Electronics MELSEC FX3S — Program examples diagram (page 208)
Fig. 106 · Program examples

0000 LD X000 0001 MC N000 SP M100 0004 LD X001 0005 OUT Y000 0006 LD X002 0007 OUT Y001 0008 MCR N000 ← Two-step instruction

←Return to the bus line ("N0" shows the

use "N0" again. There is no limitation in the number of "N0". Only in the nesting structure, increase the nest level "N" in the way "N0 → N1 ... N6 → N7" as shown in the example 2 on the next page.

7 Basic Instruction

Page 209 of the Mitsubishi Electronics MELSEC FX3S user manual — [A]
Page 209 · click to enlarge
Page 209

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.9 MC, MCR 1

2) When the nesting structure is adopted When using MC instructions inside MC instruction, increase the nest level "N" in turn in the way "N0 → N1 → N2 → N3 → N4 → N5 → N6 → N7". For returning from the nesting structure, reset the nest levels from the highest one in turn using MCR instruction in the way "N7 → N6 → N5 → N4 → N3 → N2 → N1 → N0". For example, if "MCR N5" is programmed without programming "MCR N6" and "MCR N7", the nest level is returned to 5 immediately. Available nest levels are from N0 to N7 (eight layers).

While X000 is OFF

N 0

MC N 0 M100

[A]

N 0 M100

Level N0 The bus line B is active while X000 is ON.

Y000

[B]

While X002 is OFF

N 1

MC N 1 M101

N 1 M101

Level N1 The bus line C is active while both X000 and X002 are ON.

Y001

[C]

Specified the Device & Constant

While X004 is OFF

N 2

MC N 2 M102

N 2 M102

Level N2 The bus line D is active while all of X000, X002 and X004 are ON.

Y002

MCR N 2

N 2

Y003

Level N1 The bus line returns to the status of the bus line C by "MCR N2".

[C]

MCR N 1

N 1

Y004

Level N0 The bus line returns to the status of the bus line B by "MCR N1".

[B]

FNC10-FNC19 Move & Compare

MCR N 0

N 0

Initial status The bus line returns to the initial status of the bus line A by "MCR N0". Accordingly, Y005 turns ON or OFF by turning ON or OFF of X010 regardless of X000, X002 and X004.

Y005

FNC20-FNC29 Arith. & Logic Operation

[A]

Show 9 more labels / short text on this page
7 Basic Instruction · Introduction · Overview · Circuit program · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 210 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 210 · click to enlarge
Page 210

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.10 INV

7.10 INV

Outline

1. Instruction Format INV instruction inverts the operation result up to just before INV instruction, and does not require device number specification.

INV

Continuous Operation Pulse (Single) Operation

2. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 2. Applicable devices diagram (page 210)
Fig. 107 · 2. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. INV instruction (inverts the result of operations)

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 210)
Fig. 108 · Explanation of function and operation

OFF 0 LD X000 1 INV 2 OUT Y000

In the figure above, Y000 turns ON when X000 is OFF, and Y000 turns OFF when X000 is ON. INV instruction can be used in the same position as serial contact instructions (AND, ANI, ANDP and ANDF). Different from LD, LDI, LDP and LDF instructions shown in the list, INV instruction cannot execute connection to bus lines. Different from OR, ORI, ORP and ORF instructions, INV instruction cannot be used independently in parallel to a contact instruction.

2. Operation range of INV instruction When INV instruction is used in a complicated circuit containing ORB and ANB instructions, the operation range of INV instruction is as shown in the figure below:
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 210)
Fig. 109 · Explanation of function and operation

INV instruction inverts the operation result after LD, LDI, LDP or LDF instruction located before INV instruction. Accordingly, if INV instructions are used inside ORB and ANB instructions, blocks after LD, LDI, LDP or LDF instruction seen from each INV instruction are regarded as the target of INV operation.

Show 6 more labels / short text on this page
7 Basic Instruction · Mnemonic Operation Condition · Basic Instruction · 1 step INV · Inverse · −
Page 211 of the Mitsubishi Electronics MELSEC FX3S user manual — M0 SET
Page 211 · click to enlarge
Page 211

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.11 MEP, MEF 1

7.11 MEP, MEF

Outline

MEP and MEF commands are instructions that change the operation results to pulses so that device numbers do not have to be specified.

1. MEP The operation results up to the MEP instruction become conductive when the driving contacts turn from OFF to ON. The use of MEP instructions simplifies the process of changing driving contacts to pulses when multiple contact points connect in a series.
2. MEF The operation results up to the MEF instruction become conductive when the driving contacts turn from ON to OFF. The use of MEF instructions simplifies the process of changing driving contacts to pulses when multiple contact points connect in a series.

1. Instruction format

MEP

− Continuous Operation Pulse (Single) Operation

MEP

MEP

MEF

− Continuous Operation Pulse (Single) Operation

MEF

MEF

Specified the Device & Constant

2. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

MEP There are no applicable devices.

MEF There are no applicable devices.

Explanation of function and operation

1. MEP instruction (ON during rising edge of driving contacts results)

Circuit Program List program

X000 X001

0 1 2 3

LD AND MEP SET

X000 X001

OFF

ON X000

M0 SET

M0

ON X001 OFF

ON M0 OFF

2. MEF instruction (ON during falling edge of driving contacts results)

Circuit program List program

X000 X001

0 1 2 3

LD AND MEP SET

X000 X001

ON X000

OFF

OFF

FNC10-FNC19 Move & Compare

M0 SET

M0

ON X001 OFF

OFF

ON M0 OFF

FNC20-FNC29 Arith. & Logic Operation

Show 21 more labels / short text on this page
7 Basic Instruction · Introduction · Overview · Instruction List · Basic Instruction · Mnemonic Operation Condition · Devices in Detail · 1 step · Basic Instruction · Mnemonic Operation Condition · 1 step · Instruc- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · tion · Before Programming · Basic Instruction · Timing chart · FNC00-FNC09 Program Flow · Timing chart
Page 212 of the Mitsubishi Electronics MELSEC FX3S user manual — Error
Page 212 · click to enlarge
Page 212

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.11 MEP, MEF

Caution

1. MEP and MEF instructions may not operate normally if the indexed contact is modified and changed to pulses by sub-routine programs, the FOR and NEXT instructions, etc.
2. As the MEP and MEF instructions operate using the operation results immediately before them, use at the list program as the AND instruction. The MEP and MEF instructions cannot be used at the list program as LD or OR.
3. When programmed in a branch, the MEP/MEF instruction judges the rising/falling edge based on the rung status up to just before the MEP/MEF instruction in the branch.

Circuit program List program

M0 M1

0 1 2 3

LD LD MEP OR

M0 M1

Y001 SET

M2

M2

SET 5 Y001 ANB 4

Judges the rising/falling edge based on the rung status in this range.

4. Caution on writing during RUN

1. Pulse command during rising edge of operation (MEP instruction) results After writing to the circuit with MEP instructions during RUN, the MEP instruction result turns ON (conductive) while the operation results up to the MEP instruction are ON.
2. Pulse instruction during falling edge of operation (MEF command) results After writing to the circuit with MEF instructions during RUN , the MEF instruction result turns OFF (nonconductive), regardless of the operation results up to the MEF instruction. The operation results of MEF instruction turns ON (conductive) when the operation results up to the MEF instruction turn OFF.

Operation Results up to MEP/MEF Instruction

(while writing is executed during RUN) MEP Instruction MEF Instruction

OFF OFF (non-conductive) OFF (non-conductive)

ON ON (conductive) OFF (non-conductive)

Error

  • There are no calculation errors in the MEP and MEF instructions.

7 Basic Instruction

Page 213 of the Mitsubishi Electronics MELSEC FX3S user manual — ON
Page 213 · click to enlarge
Page 213

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.12 PLS, PLF 1

7.12 PLS, PLF

Outline

When PLS instruction is executed, an applicable device is activated during only one operation cycle after a drive input turns ON. When PLF instruction is executed, an applicable device is activated during only one operation cycle after a drive input turns OFF.

1. Instruction format

PLS

− Continuous Operation Pulse (Single) Operation

PLS

PLF

− Continuous Operation Pulse (Single) Operation

PLF

→ For the number of instruction steps, refer to Section 7.16.

2. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Specified the Device & Constant

PLS 3 S 1 S 2

PLF 3 S 1 S 2

S1: Except special auxiliary relays (M) S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. PLS instruction (rising edge pulse)

Circuit program List program Timing chart

ON

0000 LD X000 0001 PLS M 0 X000

M0 PLS

ON during one operation cycle

M 0 PLS instruction

In the figure above, M0 is ON during only one operation cycle when X000 changes from OFF to ON.

2. PLF instruction (falling/trailing edge pulse)

Circuit program List program Timing chart

ON

0000 LD X000 0001 PLF M 1 X000

M1 PLF

ON during one operation

M 1 PLF instruction

In the figure above, M1 is ON during only one operation cycle when X000 changes from ON to OFF.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 20 more labels / short text on this page
7 Basic Instruction · Introduction · Overview · Basic Instruction · Mnemonic Operation Condition · Pulse · Instruction List · Mnemonic Operation Condition · Basic Instruction · Pulse Falling · Devices in Detail · Instruc- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · tion · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow · cycle
Page 214 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 214 · click to enlarge
Page 214

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.12 PLS, PLF

3. Output drive side The following two circuits result the same operation.
Mitsubishi Electronics MELSEC FX3S — 7.12 PLS, PLF diagram (page 214)
Fig. 110

In each case, M0 is ON during only one operation cycle when X000 changes from OFF to ON.

Mitsubishi Electronics MELSEC FX3S — 7.12 PLS, PLF diagram (page 214)
Fig. 111

In each case, MOV instruction is executed only once when X000 changes from OFF to ON.

Caution

1. Cautions on writing during RUN

1) Instructions for falling edge pulse When writing is completed during RUN for a circuit including an instruction for falling edge pulse (LDF, ANDF, or ORF instruction), the instruction for falling edge pulse is not executed regardless of the ON/OFF status of the target device of the instruction for falling edge pulse. When writing is completed during RUN for a circuit including an instruction for falling edge pulse (PLF instruction), the instruction for falling edge pulse is not executed regardless of the ON/OFF status of the operation condition device. It is necessary to set to ON the target device or operation condition device once and then set it to OFF for executing the instruction for falling edge pulse.

2. Instructions for rising edge pulse When writing is completed during RUN for a circuit including an instruction for rising edge pulse, the instruction for rising edge pulse is executed if a target device of the instruction for rising edge pulse or the operation condition device is ON. Target instructions for rising edge pulse: LDP, ANDP, ORP, and pulse operation type applied instructions (such as MOVP)
Mitsubishi Electronics MELSEC FX3S — Caution diagram (page 214)
Fig. 112 · Caution

Contact ON/OFF status (while writing is executed during RUN) Instruction for rising edge pulse Instruction for falling edge pulse

*1. PLS instruction is not executed.

2. Cautions on using latched (battery or EEPROM backed) type devices When PLC mode is changed in the way "RUN → STOP → RUN" while a drive input remains ON, "PLS M0" operates, but "PLS M600 (latched device)" does not operate (when the PLC mode switches from STOP to RUN) because the status of M600 is latched even while the PLC is in the STOP mode.

7 Basic Instruction

Page 215 of the Mitsubishi Electronics MELSEC FX3S user manual — M8002
Page 215 · click to enlarge
Page 215

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.12 PLS, PLF 1

3. Caution for simultaneous instances of the ZRST instruction and the PLS instruction The ZRST instruction resets the last stage for the PLS instruction and PLF instruction of the applicable device. In addition, the reset state of T and C is also reset.

M0

ZRST

M100 M0

M0 PLS

M 0

Please program in the following way to turn on M0 only once.

Specified the Device & Constant

M0

M100 M0 ZRST

M0

When the PLC mode is switched in the way "RUN → STOP → RUN (or power supply ON (RUN) → power supply OFF → power supply ON (RUN))" while a drive input remains ON, PLS M600 does not operate. However, it is possible to operate PLS M600 (latched device) by resetting once using the ZRST instruction.

M8002

M700 M600 ZRST

RUN/STOP

RUN STOP RUN

M600 PLS

M600 (latched device) PLS instruction

ON during one operation cycle

ON during one operation cycle

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 24 more labels / short text on this page
7 Basic Instruction · Introduction · Circuit program · Overview · Timing chart · one operation · one operation · Instruction List · cycle · cycle · Devices in Detail · ZRST instruction · PLS instruction · execution · execution · execution PLS instruction · ZRST instruction · execution · Circuit program · Before Programming · Circuit program · Timing chart · Basic Instruction · FNC00-FNC09 Program Flow
Page 216 of the Mitsubishi Electronics MELSEC FX3S user manual — 2. Applicable devices
Page 216 · click to enlarge
Page 216

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.13 SET, RST

7.13 SET, RST

Outline

1. Setting a bit device (SET instruction (set bit device latch ON)) When the command input turns ON, SET instruction sets to ON an output relay (Y), auxiliary relay (M), state relay (S) and bit specification (D .b) of word device. Even if the command input turns OFF after that, the device which was set to ON by SET instruction remains ON.
2. Resetting a bit device (RST instruction (reset bit device OFF)) RST instruction resets an output relay (Y), auxiliary relay (M), state relay (S), Timer (T), counter (C) or bit specification (D .b) of a word device. Use the RST instruction to reset (set to OFF) a device which was set to ON by SET instruction.

3) Clearing the present value of a word device (RST instruction reset bit device OFF)) RST instruction clears the current value of a timer (T), counter (C), data register (D), extension register (R) or index register (V)(Z). RST instruction can be used to clear to "0" the contents of a data register (D) or index register (V)(Z). (The same result can be obtained by MOV instruction which transfers the constant K0.) RST instruction can be used also to reset the current value and return the contact of retentive type timers T246 to T255. SET and RST instructions can be used for the same device as many times as necessary in an arbitrary order.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 216)
Fig. 113 · 1. Instruction format

→ For the number of instruction steps, refer to Section 7.16.

2. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 2. Applicable devices diagram (page 216)
Fig. 114 · 2. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S1: Special auxiliary relays (M) and 32-bit counters (C) cannot be indexed with index registers (V and Z). S2: Index modifiers (V and Z) are not available. S3: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S4: This function is supported only in FX3U/FX3UC PLCs.

7 Basic Instruction

Page 217 of the Mitsubishi Electronics MELSEC FX3S user manual — M8 UUU
Page 217 · click to enlarge
Page 217

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.13 SET, RST 1

Explanation of function and operation

SET instruction drives the coil for an output relay (Y), auxiliary relay (M), state relay (S) and bit specification of data register (D).

1. When using a bit device SET instructions located in parallel can be used consecutively as many times as necessary. In the program example shown below, "RST Y000" after "SET Y000" corresponds to this usage.

Circuit program List program Timing chart

ON

0 LD X000 1 SET Y000 2 LD X001 3 RST Y000

SET Y000

ON

RST Y000

Y000

ON

2. When using a word device (timer or counter) Use RST instruction to reset a counter or retentive type timer.
1. Program example of an internal counter

C0 up-counts the number of times X011 turns from OFF to ON. When the counting result reaches the set value K10, the output contact C0 is activated. Even if X011 changes from OFF to ON after that, the current value of the counter remains unchanged and the output contact remains activated. For clearing the counter and returning the output contact, X010 is set to ON. It is necessary to specify a constant K or data register number for indirect specification after OUT C instruction. In the case of latched (battery backed) type counters, the current value and the operation status/reset status of the output contact are latched even after power failure.

RST C 0

K10

Y000 C 0

Specified the Device & Constant

2. Program example of a high-speed counter

For 1-phase 1-input counters C235 to C245, use special auxiliary relays M8235 to M8245 for specifying the counting direction. X010 in ON status: Specifies down counting. X010 in OFF status: Specifies up counting. When X011 turns ON, the output contact of the counter CUUU is returned and the current value of the counter CUUU is reset to "0". In counters with reset input (C241, C242 ...), the same situation is achieved by interrupt operation when the corresponding reset input turns ON, but any program is not required for this operation. When X012 turns ON, turning ON/OFF of a counting input X000 to X005 determined according to the counter number is counted. In counters having start input (C244, C245 ...), counting is started only after the corresponding input turns ON. When the current value of a counter increases and reaches the set value (K or contents of D), the output contact is set. When the current value decreases and reaches the set value, the output contact is reset.

M8 UUU

RST C UUU

C UUU

C UUU

Y002

FNC10-FNC19 Move & Compare

As a contact driving the counting coil of a high-speed counter, program a contact which is normally ON when high- speed counting is executed. If an input relay (X000 to X005) assigned for high-speed counters is used for driving the counting coil, accurate counting cannot be achieved.

FNC20-FNC29 Arith. & Logic Operation

Show 14 more labels / short text on this page
7 Basic Instruction · Introduction · Overview · Instruction List · SET instruction · RST instruction · Devices in Detail · Before Programming · Counting direction · Sequence reset circuit · Basic Instruction · Counting coil · FNC00-FNC09 Program Flow · K or D
Page 218 of the Mitsubishi Electronics MELSEC FX3S user manual — Errors
Page 218 · click to enlarge
Page 218

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.13 SET, RST

When RST instruction for a timer or counter is executed in a jumped program, subroutine program or interrupt program, the timer or counter may be kept in the reset status and the timer or counter may be disabled. For details, refer to the following sections:

→ For a jumped program, refer to Subsection 8.1.1. → For a subroutine program, refer to Subsection 8.2.1. → For an interrupt program, refer to Subsection 36.2.3.

3. Indexing *1

Devices used in SET and RST instructions can be indexed with index registers (V)(Z). (State relays (S), special auxiliary relays (M), 32-bit counters, "D .b", and word devices cannot be indexed.)

V0 to V7 and Z0 to Z7 are available for indexing. When a used device is an input (X) or output (Y), the value of an index register (V or Z) is converted into octal, and then added. Example: When Z0 is "20", Y024 turns ON or

Circuit program List program

0000 0001 0004 0005

LD SET LD RST

X000 Y000Z0 X001 Y000Z0

Y000Z0 SET

OFF.

Y000Z0 RST

*1. This function is supported only in FX3U/FX3UC PLCs.

4. Bit specification of a data register (D) *1

A bit in data register (D) can be specified as a device used in SET or RST instruction.

When specifying a bit in data register, input "." after a data register (D) number, and then input a bit number (0 to F) consecutively. Only 16-bit data registers are available. Specify a bit number as "0, 1, 2, ... 9, A, B, ... F" from the least significant bit. Example: In the example shown on the left, when

Circuit program List program

0000 0001 0004 0005

LD SET LD RST

X000 D0.3 X001 D0.3

D0.3 SET

D0.3 RST

X000 turns ON once, the bit 3 of D0 turns ON. When X001 turns ON, the bit 3 of D0 turns OFF.

*1. This function is supported only in FX3U/FX3UC PLCs.

Caution

When SET and RST instructions are executed for an output relay (Y) in the same operation, the result of the instruction located nearest the END instruction (which specifies the end of program) is output.

Errors

  • When an I/O number used in SET or RST instruction does not exist due to indexing, M8316 (Non-existing I/O specification error) turns ON.
  • When the device number of a device (M, T or C) other than I/O used in SET or RST instruction does not exist due to indexing, an operation error (error code: 6706) occurs.

7 Basic Instruction

Page 219 of the Mitsubishi Electronics MELSEC FX3S user manual — AND → NOP ANI → NOP
Page 219 · click to enlarge
Page 219

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.14 NOP 1

7.14 NOP

Outline

NOP instruction specifies no operation. When a program is erased completely, all steps are replaced with NOP instructions. When NOP instruction is located between general instructions, PLCs ignore NOP instruction. If NOP instructions are put in the middle of a program, fluctuation of step numbers is minimized when the program is changed or added. But excessive program steps are required. Note that circuits are considerably changed if already written instructions are replaced with NOP instructions.

1. Instruction format

NOP

Continuous Operation Pulse (Single) Operation

NOP

2. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

NOP There are no applicable devices.

Explanation of function and operation

Specified the Device & Constant

1. NOP instruction (no operation or null step) NOP instruction specifies no operation. If NOP operation is written in the middle of a program, PLCs ignore it in executing the program. When an existing program is replaced with NOP instructions, it means that former instructions are deleted.

OUT → NOP (error)

AND → NOP ANI → NOP

OR → NOP Circuit is

Contact becomes short-circuit.

disconnected. ORI → NOP

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 18 more labels / short text on this page
7 Basic Instruction · Introduction · Overview · Basic Instruction · Mnemonic Operation Condition · Instruction List · 1 step · No Operation · − · Devices in Detail · Instruc- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · tion · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 220 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 220 · click to enlarge
Page 220

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.15 END

7.15 END

Outline

END instruction specifies the end of a program. (Do not write the END instruction in the middle of a program.)

1. Instruction format

END

Continuous Operation Pulse (Single) Operation

END

END

2. Applicable devices

Mitsubishi Electronics MELSEC FX3S — END diagram (page 220)
Fig. 115

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. END instruction (program end, I/O refresh and return to step 0) PLCs repeat "input processing → program execution → output processing". When END instruction is written at the end of a program, PLCs immediately execute the output processing without executing steps after END instruction. If END instruction is not written at the end of a program, PLCs execute the program until the END step, and then execute the output processing. At the first execution after the PLC mode is changed from STOP to RUN, PLCs start from END instruction. When END instruction is executed, the watchdog timer (which checks the operation cycle) is refreshed.

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 220)
Fig. 116 · Explanation of function and operation

Caution

Do not write END instruction in the middle of a program. When a program is transferred from a programming tool, all steps after END instruction are replaced with NOP (no operation) instructions.

Show 5 more labels / short text on this page
7 Basic Instruction · Basic Instruction · Mnemonic Operation Condition · 1 step · −
Page 221 of the Mitsubishi Electronics MELSEC FX3S user manual — LDP, LDF,
Page 221 · click to enlarge
Page 221

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

7.16 Number of Instruction Steps and Specified Devices 1

7.16 Number of Instruction Steps and Specified Devices

The table below shows the number of steps of basic instructions. Available devices and device ranges vary depending on the PLC. For details on devices, refer to Chapter 4. For ORB, ANB, MPS, MRD, MPP, MCR, INV, MEP, MEF, NOP and END instructions, refer to pages explaining these instructions.

LDP, LDF,

LD, LDI, AND, ANI,

OUT SET RST PLS, PLF

ANDP, ANDF, ORP,

MC

OR, ORI

ORF

X000 to X357 1 − 2 −

Y000 to Y357 1 2 2 3

M0 to M1535 1 2 2 3

M1536 to M3583 2 3

M3584 to M7679 3 4

S0 to S1023 1 2 2 2 − 2 −

S1024 to S4095 2 − 2 −

T0 to T191, T200 to T245 1 3 − 2 − 2 −

T192 to T199, T246 to T511 1 3 − 2 − 2 −

C0 to C199 1 3 − 2 − 2 −

C200 to C255 1 5 − 2 − 2 −

Special auxiliary relays M8000 to M8255 1 2 2 2 − 2 −

Specified the Device & Constant

Special auxiliary relays M8256 to M8511 2 − 2 −

X000 to X357 3 −

Y000 to Y357 3 − −

M0 to M7679 3 − −

T0 to T511 3 4 −

Bit devices with index

S0 to S4095 −

C0 to C199 3 4 − 3 − − −

C200 to C255 −

Special auxiliary relays M8000 to M8511 3 − − −

D0 to D7999, Special data registers D8000 to D8511

− − − 3 − − −

R0 to R32767 − − − 3 − − −

D0 to D7999, Special data registers D8000 to D8511, R0 to R32767

Word devices with index

−

Bit specification in word device

D .b, Special auxiliary relays D .b

3 − 3 −

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 12 more labels / short text on this page
7 Basic Instruction · Introduction · Instruction · Overview · Device · Instruction List · Bit devices · Devices in Detail · Before Programming · Basic Instruction · Word devices · FNC00-FNC09 Program Flow
Page 222 of the Mitsubishi Electronics MELSEC FX3S user manual — 8. Program Flow – FNC 00 to FNC 09
Page 222 · click to enlarge
Page 222

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8. Program Flow – FNC 00 to FNC 09

FNC 00 to FNC 09 provide instructions mainly related to control flow of sequence programs such as conditional program execution and priority processing.

Mitsubishi Electronics MELSEC FX3S — 8. Program Flow – FNC 00 to FNC 09 diagram (page 222)
Fig. 117 · 8. Program Flow – FNC 00 to FNC 09
Page 223 of the Mitsubishi Electronics MELSEC FX3S user manual — CJP
Page 223 · click to enlarge
Page 223

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.1 FNC 00 – CJ / Conditional Jump 1

8.1 FNC 00 – CJ / Conditional Jump

Outline

CJ or CJP instruction jumps to a pointer (P); The sequence program steps between CJ or CJP instruction and the pointer are not executed. CJ and CJP instructions reduce the scan time, and allow programs with double coils.

1. Instruction format

P FNC 00

Mnemonic Operation Condition Mnemonic Operation Condition 32-bit Instruction

CJ

Continuous Operation Pulse (Single) Operation

−

CJP

−

2. Set data

Operand type Description Data type

Pointer number (P) indicating the label number for the jump destination (FX3S: n=0 to 255, FX3G/FX3GC: n=0 to 2047, FX3U/FX3UC: n=0 to 4095) (P63 jumps to END instruction.)

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

Specified the Device & Constant

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 16-bit operation (CJ and CJP) While the command input is ON, CJ or CJP instruction executes a program with a specified label (pointer number).
1. In the case of CJ instruction

ON

Jumps to the pointer while the

CJ

command is ON.

CJ

Executed in every scan.

User program which is skipped and is not executed when the command turns ON

2. In the case of CJP instruction

FNC10-FNC19 Move & Compare

Jumps to the pointer only in one operation while the command is ON.

CJP

User program which is skipped and is not executed in one operation cycle

Executed in one scan.

when the command turns ON

FNC20-FNC29 Arith. & Logic Operation

Show 32 more labels / short text on this page
Introduction · Overview · 16-bit Instruction · 3 steps CJ · Instruction List · Devices in Detail · Pointer number · Pn · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Pn · Before Programming · User program · Command · Pn ‚ · Command input · Basic Instruction · Label · User program · Pn ‚ · FNC00-FNC09 Program Flow · User program · Command · ON Pn ‚ · Command input · CJP Pn · Label · User program · Pn ‚
Page 224 of the Mitsubishi Electronics MELSEC FX3S user manual — CJ P 10
Page 224 · click to enlarge
Page 224

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.1 FNC 00 – CJ / Conditional Jump

Cautions

1. Relationship between the label input position and the list program The figure below shows programming of a label. When creating a circuit program, move the cursor to the left side of the bus line in the ladder diagram, and input a label (P) at the head of the circuit block.
Mitsubishi Electronics MELSEC FX3S — Cautions diagram (page 224)
Fig. 118 · Cautions

LD X031 OUT Y010 P 20 LD X032 OUT Y011

2. Programming a label in a smaller number step than CJ instruction A label can be programmed in a smaller number step than CJ instruction. However, note that a watchdog timer error occurs when the scan time exceeds 200 ms (default setting).

CJ P 10

3. Jumping to one label from two or more CJ instructions When the pointer number in operands is same and there is one label, the following operation is caused: When X020 turns ON, the program execution jumps from CJ instruction corresponding to X020 to the label P9. When X020 turns OFF and X021 turns ON, the program execution jumps from CJ instruction corresponding to X021 to the label P9.
Mitsubishi Electronics MELSEC FX3S — CJ P 10 diagram (page 224)
Fig. 119
4. Using a label (P) two or more times When a label number (including labels for CALL instructions described later) is used two or more times, an error is caused.
Mitsubishi Electronics MELSEC FX3S — CJ P 10 diagram (page 224)
Fig. 120

Label P 10

Page 225 of the Mitsubishi Electronics MELSEC FX3S user manual — 8.1 FNC 00 – CJ / Conditional Jump 1
Page 225 · click to enlarge
Page 225

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.1 FNC 00 – CJ / Conditional Jump 1

Mitsubishi Electronics MELSEC FX3S — 8.1 FNC 00 – CJ / Conditional Jump 1 diagram (page 225)
Fig. 121 · 8.1 FNC 00 – CJ / Conditional Jump 1
5. Label unnecessary for the pointer P63 The pointer P63 specifies jump to END step. Do not program P63. If P63 is programmed, PLCs will display the error code 6507 (defective label definition) and stop.
6. When jumping to a pointer for subroutine Any label cannot be shared by CALL instruction and CJ instruction.
7. Unconditional jump if the command contact is normally ON Because M8000 is normally ON while a PLC is operating, unconditional jump is specified when M8000 is used in the following example:

User program (It is skipped, and is not executed.)

Page 226 of the Mitsubishi Electronics MELSEC FX3S user manual — PLS M0
Page 226 · click to enlarge
Page 226

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.1 FNC 00 – CJ / Conditional Jump

Program example

1. When a jump is necessary after OFF processing In one operation cycle after X023 changes from OFF to ON, the CJ P7 instruction becomes valid. By using this method, jump can be executed after all outputs between the CJ P7 instruction and the label P7 turn OFF.

PLS M0

CJ P7 M0

P7

Label · User program

Page 227 of the Mitsubishi Electronics MELSEC FX3S user manual — X007 OFF X010 OFF
Page 227 · click to enlarge
Page 227

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.1 FNC 00 – CJ / Conditional Jump 1

8.1.1 CJ instruction and operations of contact and coil

In the program example shown below, when X000 turns ON, the program execution jumps from CJ instruction in the first circuit to the label P8. While X000 is OFF, jump is not executed; The program is executed from the 1st step in turn, and then the program execution jumps from CJ instruction in the 11th circuit to the label P9. Instructions skipped by jump are not executed.

1. Circuit example 1 for explaining operations

  • Double coil operation of output Y001 While X000 is OFF, output Y001 is activated by X001. While X000 is ON, output Y001 is activated by X012. Even in a program divided by conditional jumps, if the same coil (Y000 in this case) is programmed two or more times within the jump area or outside the jump area, such a coil is handled as double coil.

CJ P 8

Y001

M 1

T 0

K 10

  • When the reset (RST) instruction for the retentive type timer T246 is located outside the jump area Even if the counting coil (OUT T246) is jumped, reset (return of the contact and clearing of the current value) is valid.

RST T246

T246

K1000

RST C 0

  • When the reset (RST) instruction for the counter C0 is located outside the jump area Even if the counting coil is jumped, reset (return of the contact and clearing of the current value) is valid.

K 20

Specified the Device & Constant

X011 FNC 12

MOV K 3 D 0

  • Operation of the routine timers T192 to T199 A routine timer continues its operation even if it is jumped after the coil is driven, and the output contact is activated.

P 8

CJ P 9

Y001

  • Operation of the high-speed counters C235 to C255 A high-speed counter continues its operation even if it is jumped after the coil is driven, and the output contact is activated.

P 9

RST T246

RST C 0

When each input changes during jump in the above program, each coil executes the following operation:

Classification Contact status before jump Coil operation during jump

Y, M, S (Y001, M1, S1)

X001, X002, X003 OFF Y001, M1 and S1 turn OFF.

X001, X002, X003 ON Y001, M1 and S1 turn ON

10 ms timer and 100 ms timer (T0) X004 OFF Timer is not activated.

X004 ON Counting is paused (, and is restarted after X000 turns OFF).

X005 OFF X006 OFF

Timer is not activated. The deactivation status is reset when X013 turns ON.

1 ms timer (T246)

X005 OFF X006 ON Counting is continued (, and the contact is activated after X000 turns OFF).

X007 OFF X010 OFF

Counting is not activated. The deactivation status is reset when X013 turns ON.

FNC10-FNC19 Move & Compare

X007 OFF X010 ON Counting is paused (, and is restarted after X000 turns OFF).

X011 OFF FNC instruction is not executed during jump. But instructions FNC 52 to FNC 58 continue their operations. X011 ON

FNC20-FNC29 Arith. & Logic Operation

Show 13 more labels / short text on this page
Introduction · Overview · 1st circuit 0 · Instruction List · Devices in Detail · Label · 11th circuit · Before Programming · Label · Basic Instruction · FNC00-FNC09 Program Flow · Counter (C0) · Applied instruction (MOV)
Page 228 of the Mitsubishi Electronics MELSEC FX3S user manual — Timing chart
Page 228 · click to enlarge
Page 228

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.1 FNC 00 – CJ / Conditional Jump

2. Circuit example 2 for explaining operations (when only an RST instruction for a timer or counter is jumped)

When X011 turns ON while the RST instruction for the counter C0 is operating (X010 is ON), the program execution jumps past the RST instruction due to the CJ (FNC 00) instruction. In this jump status, the counter C0 remains reset. Accordingly, the current value of C0 remains "0" even if X012 turns ON. To clear this reset status, it is necessary to turn OFF the RST instruction for counter C0. (Refer to the program shown below.)

Mitsubishi Electronics MELSEC FX3S — 8.1.1 CJ instruction and operations of contact and coil diagram (page 228)
Fig. 122 · 8.1.1 CJ instruction and operations of contact and c…

Timing chart

Mitsubishi Electronics MELSEC FX3S — Timing chart diagram (page 228)
Fig. 123 · Timing chart

Because C0 remains reset, its current value remains unchanged even if X012 turns ON.

Current value of C0 1 2 3 Counter is reset.

Program example for activating a timer and counter even during a jump

Mitsubishi Electronics MELSEC FX3S — Program example for activating a timer and counter even during a jump diagram (page 228)
Fig. 124 · Program example for activating a timer and counter e…

RST C0 Clears the reset status of counter C0 during jump.

Timing chart

Mitsubishi Electronics MELSEC FX3S — Timing chart diagram (page 228)
Fig. 125 · Timing chart

Current value of C0 1 2 3 Counter is reset.

*1 In the same operation cycle as the reset, the reset status of counter C0 is cleared.

Page 229 of the Mitsubishi Electronics MELSEC FX3S user manual — MCR N 0
Page 229 · click to enlarge
Page 229

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.1 FNC 00 – CJ / Conditional Jump 1

8.1.2 Relationship between master control instruction and jump instruction

The figure below shows the contents of operation and the relationship between the master control instruction. Avoid using [2], [4] and [5] because the operation will be complicated.

CJ P 0

[1] Jump from outside MC

to outside MC Jump is available arbitrarily.

MC N 0 M 1 CJ P 1

Master control Master control

[2] Jump from outside MC

to inside MC Jump is executed regardless of the MC operation. Even if M0 is OFF, M0 is regarded as ON after P1.

MC N 0 M 0

CJ P 4

P 1

inside MC to inside another MC

MCR N 0

MC N 0 M 2

[3] Jump from inside MC to

CJ P 2

inside MC Jump is disabled while M0 is OFF.

P 4

P 2

MCR N 0

[4] Jump from inside MC to

outside MC Jump is disabled while M0 is OFF. Jump is executed while M0 is ON, but MCR is invalid.

CJ P 3

Jump is enabled while M1 is ON. In circuits after jump, M2 is regarded as ON regardless of the actual ON/OFF status of M2. And the first MCR N0 is ignored.

Specified the Device & Constant

MCR N 0

P 3

P 0

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 9 more labels / short text on this page
Introduction · Overview · [5] Jump from · Instruction List · Master control · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 230 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 230 · click to enlarge
Page 230

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.2 FNC 01 – CALL / Call Subroutine

8.2 FNC 01 – CALL / Call Subroutine

Outline

This instruction calls and executes a program which should be processed commonly in a sequence program. This instruction reduces the number of program steps, and achieves efficient program design. For creating a subroutine program, FEND (FNC 06) and SRET (FNC 02) instructions are required.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 230)
Fig. 126 · 1. Instruction format

2. Set data

Operand type Description Data type

Pointer number (P) indicating the label number for the jump destination (FX3S: P0 to P62 and P64 to P255, FX3G/FX3GC: P0 to P62 and P64 to P2047, FX3U/FX3UC: P0 to P62 and P64 to P4095)

P63 is dedicated to CJ (FNC 00) instruction (for jump to END step), it cannot be used as a pointer for CALL (FNC 01) instruction.

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 230)
Fig. 127 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 16-bit operation While the command input is ON, CALL instruction is executed and the program execution jumps to a step with a label

. Then, a subroutine program with the label is executed. When SRET (FNC 02) instruction is executed, the program execution returns to the step after CALL instruction.

  • At the end of the main program, put FEND instruction.
  • Put a label (P) for CALL instruction after FEND instruction.
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 230)
Fig. 128 · Explanation of function and operation

Main program Program area from the step 0 to FEND instruction

Subroutine program Program area from a label to SRET instruction

Show 4 more labels / short text on this page
Pointer number · Pn · Pn · Pn
Page 231 of the Mitsubishi Electronics MELSEC FX3S user manual — SRET
Page 231 · click to enlarge
Page 231

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.2 FNC 01 – CALL / Call Subroutine 1

Caution

1. Using a label (P) number two or more times In CALL instructions, the same number can be used two or more times in operands (P). However, do not use a label (P) and number used in another instruction (CJ instruction).

X020 FNC 00

CJ P 9

CALLP P 9 X030

Bad

P 9

Program examples

1. Example of fundamental use (no nesting)

CALL P 10

Main program While X000 is ON, the program execution jumps to a step with the label P10.

FEND

P 10

Specified the Device & Constant

Subroutine program When SRET instruction is executed after the subroutine program has executed, the program execution returns to the original step +1.

SRET

END

2. Example of multiple CALL instructions in subroutines (multiple nesting) CALL instruction can be used up to 4 times in subroutine programs. Nesting of up to five layers is allowed.

CALLP P 11

Main program When X001 turns from OFF to ON, the program execution jumps to the label P11 only once.

FEND

P 11

Subroutine program 1 When SRET instruction is executed, the program execution returns to the main program. If X002 is ON while the subroutine program 1 is executed, the program execution jumps to a step with the label P12.

CALL P 12

SRET

P 12

Subroutine program 2 The subroutine program with P12 is executed, and then the program execution returns to the subroutine program with P11 by SRET instruction.

FNC10-FNC19 Move & Compare

SRET

END

FNC20-FNC29 Arith. & Logic Operation

Show 12 more labels / short text on this page
Introduction · Overview · Label · User program · Instruction List · Devices in Detail · Label · Before Programming · Basic Instruction · Label · FNC00-FNC09 Program Flow · Label
Page 232 of the Mitsubishi Electronics MELSEC FX3S user manual — 8.2.1 Cautions on subroutines and interrupt routines
Page 232 · click to enlarge
Page 232

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.2 FNC 01 – CALL / Call Subroutine

8.2.1 Cautions on subroutines and interrupt routines

This section explains cautions on creating programs in subroutines and interrupt routines. The explanation below is given for subroutines, but the situation also applies to interrupt routines.

1. When using timers in subroutines (or interrupt routines) Use retentive type timers T192 to T199 in subroutines. These timers execute counting when the coil instruction or END instruction is executed. After a timer reaches the set value, the output contact is activated when the coil instruction or END instruction is executed. Because general timers execute counting only when the coil instruction is executed, they do not execute counting if they are used in subroutines in which the coil instruction is executed only under some conditions.

2. When using retentive type 1 ms timers in subroutines (or interrupt routines) If a retentive type 1 ms timer is used in a subroutine, note that the output contact is activated when the first coil instruction (or subroutine) is executed after the timer reaches its set value.

3. Countermeasures against latches of devices used in subroutines (or interrupt routines) Devices which were set to ON in a subroutine are latched in the ON status even after the subroutine is finished. (Refer to the program example shown below.) When RST instruction for a timer or counter is executed, the reset status of the timer or counter is latched also. For turning OFF such a device latched in the ON status or for canceling such a timer or counter latched in the reset status, reset such a device in the main program after the subroutine is finished, or program a sequence for resetting such a device or for deactivating RST instruction in the subroutine. (Refer to the program example shown on the next page.)

Example in which outputs are latched In the following program example, the counter C0 is provided to count X001. When X000 is input, the subroutine P0 is executed only in one scan, and then the counter is reset and Y007 is output.

1. Program example
Mitsubishi Electronics MELSEC FX3S — 8.2.1 Cautions on subroutines and interrupt routines diagram (page 232)
Fig. 129 · 8.2.1 Cautions on subroutines and interrupt routines
2. Timing chart
Mitsubishi Electronics MELSEC FX3S — 8.2.1 Cautions on subroutines and interrupt routines diagram (page 232)
Fig. 130 · 8.2.1 Cautions on subroutines and interrupt routines

Because the reset instruction for C0 is valid, the current value of C0 remains unchanged even if pulses are input.

Current value of C0 1 2 3 Counter is reset.

Page 233 of the Mitsubishi Electronics MELSEC FX3S user manual — 8.2 FNC 01 – CALL / Call Subroutine 1
Page 233 · click to enlarge
Page 233

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.2 FNC 01 – CALL / Call Subroutine 1

Mitsubishi Electronics MELSEC FX3S — 8.2 FNC 01 – CALL / Call Subroutine 1 diagram (page 233)
Fig. 131 · 8.2 FNC 01 – CALL / Call Subroutine 1

RST Y007 Y007 is reset at an arbitrary timing.

The preceding RST C0 instruction is deactivated in the subroutine.

Counter reset instruction is deactivated (part B in above program). Counter is reset (part A in above program).

Page 234 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 234 · click to enlarge
Page 234

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.3 FNC 02 – SRET / Subroutine Return

8.3 FNC 02 – SRET / Subroutine Return

Outline

This instruction returns the program execution from a subroutine to the main program.

1. Instruction format

Independent Inst.

SRET

1 step SRET This instruction is the independent type, and does not require drive contact.

2. Set data

Operand type Description Data type

– There is no set data. –

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 234)
Fig. 132 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

When CALL instruction in the main program is executed, the program execution jumps to a subroutine. SRET instruction returns the program execution to the main routine.

→ Refer to Section 8.2.

Mnemonic Operation Condition · Continuous Operation

Page 235 of the Mitsubishi Electronics MELSEC FX3S user manual — 1. Types of interrupt function
Page 235 · click to enlarge
Page 235

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.4 FNC 03 – IRET / Interrupt Return 1

8.4 FNC 03 – IRET / Interrupt Return

Outline

This instruction returns the program execution from an interrupt routine to the main program.

1. Instruction format

Independent Inst.

IRET IRET

1 step This instruction is the independent type, and does not require drive contact.

2. Set data

Operand type Description Data type

– There is no set data. –

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

– There are no applicable devices.

Specified the Device & Constant

Explanation of function and operation

When an interrupt (input, timer or counter) is generated while the main program is executed, the program execution jumps to an interrupt (I) routine. IRET instruction returns the program execution to the main routine. The table below shows three types of jump to an interrupt routine.

1. Types of interrupt function

Function Interrupt No. Description Reference

Input interrupt I00* to I50* Executes the interrupt processing when an input (X) signal turns ON or OFF.

Section 36.3 and

Section 36.4

Timer interrupt I6** to I8** Executes the interrupt processing at a specified time interval (constant cycle). Section 36.5

Counter interrupt*1 I010 to I060 Executes the interrupt processing when a high-speed counter reaches it’s set value. Section 36.6

*1. This function is supported only in FX3U/FX3UC PLCs.

→ For the interrupt function, refer to Chapter 36.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 14 more labels / short text on this page
Introduction · Overview · Mnemonic Operation Condition · Continuous Operation · Instruction List · Devices in Detail · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 236 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 236 · click to enlarge
Page 236

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.4 FNC 03 – IRET / Interrupt Return

Program example

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 236)
Fig. 133 · Program example

Interrupts are usually disabled in PLCs. Use EI instruction to enable interrupts. When X000 turns ON while the main program is executed, instructions after the interrupt routine pointer I001 are executed, and the program execution returns to the original main program by IRET instruction.

The timer interrupt of the pointer I620 is executed every timer time of 20 ms, and the program execution is returned to the original main program by IRET instruction each time.

The high-speed counter interrupt of the pointer I010 is executed when the current value of a high-speed counter becomes equivalent to a value specified by DHSCS (FNC 53) instruction. The program execution returns to the original main program by IRET instruction.

Make sure to program an interrupt pointer (I***) as a label after FEND instruction.

Page 237 of the Mitsubishi Electronics MELSEC FX3S user manual — 8.5 FNC 04 – EI / Enable Interrupt 1
Page 237 · click to enlarge
Page 237

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.5 FNC 04 – EI / Enable Interrupt 1

Mitsubishi Electronics MELSEC FX3S — 8.5 FNC 04 – EI / Enable Interrupt 1 diagram (page 237)
Fig. 134 · 8.5 FNC 04 – EI / Enable Interrupt 1

Interrupts are usually disabled in PLCs. This instruction enables interrupts in PLCs. Use this instruction for using the input interrupt, timer interrupt and counter interrupt functions.

1 step This instruction is the independent type, and does not require drive contact.

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

EI instruction is the independent type, and does not require command (drive) contact.

→ For the interrupt function, refer to Chapter 36.

Page 238 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 238 · click to enlarge
Page 238

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.6 FNC 05 – DI / Disable Interrupt

8.6 FNC 05 – DI / Disable Interrupt

Outline

This instruction disables interrupts after interrupts were enabled by EI (FNC 04) instruction.

1. Instruction format

Independent Inst.

DI DI

1 step This instruction is the independent type, and does not require drive contact.

2. Set data

Operand type Description Data type

– There is no set data. –

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 238)
Fig. 135 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

DI instruction is the independent type, and does not require command (drive) contact.

→ For the interrupt function, refer to Chapter 36.

Cautions

Interrupts (requests) generated after DI instruction are processed after EI (FNC 04) instruction is executed

Mnemonic Operation Condition · Continuous Operation

Page 239 of the Mitsubishi Electronics MELSEC FX3S user manual — 8.7 FNC 06 – FEND / Main Routine Program End
Page 239 · click to enlarge
Page 239

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.7 FNC 06 – FEND / Main Routine Program End 1

Mitsubishi Electronics MELSEC FX3S — 8.7 FNC 06 – FEND / Main Routine Program End 1 diagram (page 239)
Fig. 136 · 8.7 FNC 06 – FEND / Main Routine Program End 1

8.7 FNC 06 – FEND / Main Routine Program End

This instruction indicates the end of the main program.

1 step This instruction is the independent type, and does not require drive contact.

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FEND instruction works in the same way as END instruction. When FEND instruction is executed, output processing, input processing and watchdog timer refresh are executed, and then the program execution returns to the step 0. FEND instruction is required in creating subroutine programs and interrupt programs.

Page 240 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 240 · click to enlarge
Page 240

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.7 FNC 06 – FEND / Main Routine Program End

2. In the case of CALL instruction

Mitsubishi Electronics MELSEC FX3S — 2. In the case of CALL instruction diagram (page 240)
Fig. 137 · 2. In the case of CALL instruction

Cautions

1. When FEND instruction is programmed two or more times Put a subroutine program or interrupt routine program between last FEND instruction and END instruction.
2. When CALL or CALLP instruction is used Put a label after FEND instruction. And the SRET instruction is required in every case.
3. When CALL or CALLP instruction is used If FEND instruction is executed after CALL or CALLP instruction was executed and before SRET instruction is executed, an error is caused.
4. When FOR instruction is used If FEND instruction is executed after FOR instruction was executed and before NEXT instruction is executed, an error is caused.
5. When the interrupt function (I) is used Make sure to program an interrupt label (pointer) after FEND instruction. And IRET instruction is required in every case.
Page 241 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 241 · click to enlarge
Page 241

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.8 FNC 07 – WDT / Watchdog Timer Refresh 1

8.8 FNC 07 – WDT / Watchdog Timer Refresh

Outline

This instruction refreshes the watchdog timer in a sequence program.

1. Instruction format

P FNC 07

Mnemonic Operation Condition Independent Inst.

WDT WDT Continuous Operation Pulse (Single) Operation

2. Set data

Operand type Description Data type

– There is no set data. –

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

– There are no applicable devices.

Explanation of function and operation

When the operation cycle (time until END or FEND instruction is executed after the step 0) of a PLC exceeds 200 ms, a watchdog timer error (indicating abnormal operation) occurs; The ERROR (ERR) LED lights, and the PLC stops. When the operation cycle is long, insert WDT instruction in the middle of the program to avoid the watchdog timer error.

Specified the Device & Constant

WDTP

One scan is executed.

WDT

executed.

Related device

D8000 Watchdog timer time Up to 32767 ms can be set in units of ms (initial value: 200 ms).

Cautions

1. When a watchdog timer error occurs A watchdog timer error may occur in the following cases. To avoid the error, input a program shown below near the head step to extend the watchdog timer time, or shift FROM/TO instruction execution timing.
1. Caution when many special extension devices are connected In such configuration that many special extension devices (such as positioning units, cam switches, analog units and link units) are connected, the buffer memory initialization time may become longer, thus the operation time may become longer, and a watchdog timer error may occur.

FNC10-FNC19 Move & Compare

2. Caution when many FROM/TO instructions are driven at one time When many FROM/TO instructions are executed or when many buffer memories are transferred, the scan time may become longer, and a watchdog timer error may occur.

FNC20-FNC29 Arith. & Logic Operation

3. Caution when there are many high-speed counters (software counters) When many high-speed counters are provided and high frequency are counted at one time, the operation time may become longer, and a watchdog timer error may occur.
Show 21 more labels / short text on this page
Introduction · Overview · 1 step WDTP · Instruction List · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · Devices in Detail · and Type · Command contact · Command · input · Before Programming · Command contact · Command · input · Each scan is · Basic Instruction · Device Name Description · FNC00-FNC09 Program Flow
Page 242 of the Mitsubishi Electronics MELSEC FX3S user manual — Program examples
Page 242 · click to enlarge
Page 242

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.8 FNC 07 – WDT / Watchdog Timer Refresh

2. The watchdog timer time can be changed. → For details on changing watchdog timer time, refer to Subsection 37.2.2. By overwriting the contents of D8000 (watchdog timer time), the watchdog timer detection time (initial value: 200 ms) can be changed. By inputting the program shown below, the sequence program after this insertion is monitored by a new watchdog timer time.
Mitsubishi Electronics MELSEC FX3S — 8.8 FNC 07 – WDT / Watchdog Timer Refresh diagram (page 242)
Fig. 138 · 8.8 FNC 07 – WDT / Watchdog Timer Refresh

Watchdog timer refresh If WDT (FNC 07) instruction is not programmed, the value of D8000 is valid during END processing.

Program examples

1. When the operation cycle is long and causes an error For example, by dividing a program whose operation cycle is 240 ms into two portions and inserting WDT instruction between them, the operation cycle becomes less than 200 ms in both the former half portion and the latter half portion.
Mitsubishi Electronics MELSEC FX3S — Program examples diagram (page 242)
Fig. 139 · Program examples
2. When a label (P) of CJ instruction is located in a step number smaller than the step number of CJ instruction Put WDT instruction after the label (P).

If an input relay (X) is used as the command contact, input refresh is disabled, so the program execution cannot be returned from the area between P and CJ. As the command contact, use such device that can be set to OFF in a program being jumped.

Mitsubishi Electronics MELSEC FX3S — Program examples diagram (page 242)
Fig. 140 · Program examples
3. When FOR/NEXT instruction is repeated many times Put WDT instruction between FOR and NEXT instructions.
Mitsubishi Electronics MELSEC FX3S — Program examples diagram (page 242)
Fig. 141 · Program examples
Page 243 of the Mitsubishi Electronics MELSEC FX3S user manual — Related instruction
Page 243 · click to enlarge
Page 243

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.9 FNC 08 – FOR / Start a FOR/NEXT Loop 1

8.9 FNC 08 – FOR / Start a FOR/NEXT Loop

Outline

FOR instruction specifies the number of repetition of the loop between FOR and NEXT (FNC 09) instructions.

1. Instruction format

Mnemonic Operation Condition Mnemonic Operation Condition

FOR FOR

−

2. Set data

Operand type Description Data type

Number of repetition of the loop between FOR and NEXT instructions

S S

[ = K1 to K32767] (A value from −32768 to 0 is handled as "1".)

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

Specified the Device & Constant

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

→ For details, refer to NEXT (FNC 09) instruction.

Related instruction

FOR instruction and NEXT (FNC 09) instruction are set as a pair in programming.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 17 more labels / short text on this page
Introduction · Overview · 16-bit Instruction · 32-bit Instruction · 3 steps · Continuous Operation · Instruction List · 16-bit binary · Devices in Detail · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 244 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 244 · click to enlarge
Page 244

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.10 FNC 09 – NEXT / End a FOR/NEXT Loop

8.10 FNC 09 – NEXT / End a FOR/NEXT Loop

Outline

NEXT instruction specifies the end position of the loop.

1. Instruction format

Independent Inst.

NEXT NEXT

1 step This instruction is the independent type, and does not require drive contact.

2. Set data

Operand type Description Data type

– There is no set data. –

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 244)
Fig. 142 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

The loop between FOR and NEXT instructions is repeated "n" times (which is specified by the source data). After the loop is repeated by the specified number of times, steps after NEXT instruction are executed.

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 244)
Fig. 143 · Explanation of function and operation

Related instruction

NEXT instruction and FOR (FNC 08) instruction are set as a pair in programming.

Caution

1. Limitation in the number of nesting FOR-NEXT loop can be nested up to 5 levels.
Mitsubishi Electronics MELSEC FX3S — Caution diagram (page 244)
Fig. 144 · Caution

Mnemonic Operation Condition · Continuous Operation

Page 245 of the Mitsubishi Electronics MELSEC FX3S user manual — NEXT
Page 245 · click to enlarge
Page 245

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

8 Program Flow – FNC 00 to FNC 09

8.10 FNC 09 – NEXT / End a FOR/NEXT Loop 1

Errors

1. Watchdog timer error When FOR-NEXT loop is repeated many times, the operation cycle (D8010) is too long, and a watchdog timer error may occur. In such a case, change the watchdog timer time or reset the watchdog timer.

→ For details on changing the watchdog timer time, refer to Subsection 37.2.2.

→ For resetting the watchdog timer, refer to WDT (FNC 07) instruction.

2. Examples of wrong programs The following programs are regarded as errors.

When NEXT instruction does not exist When NEXT instruction is located before FOR instruction

NEXT

FOR

FOR

NEXT

When number of FOR instructions is not equivalent to the number of NEXT instructions

When NEXT instruction is located after FEND or END instruction

FOR

FOR

FOR

FEND

NEXT

NEXT

Specified the Device & Constant

NEXT

END

NEXT

Program example

1. Program with three FOR-NEXT loops

FOR K 4

The loop [3] is repeated 4 times.

FOR D 0Z

When the data value (current value) of D0Z (D4 when Z is "4") is "6", the loop [2] is repeated 6 times.

CJ P 22

When X010 is OFF

FOR K1X000

When K1X000 is "7", the loop [1] is repeated 7 times. When X010 is ON

FNC10-FNC19 Move & Compare

NEXT

The program execution jumps to the pointer P22, and the loop [1] is skipped.

P 22

Number of times of repeating the loops [1], [2] and [3]

NEXT

X010 = ON X010 = OFF 7 × 6 × 4 =168 times 6 × 4 = 24 times 4 times

0 time 24 times 4 times

FNC20-FNC29 Arith. & Logic Operation

NEXT

Show 14 more labels / short text on this page
Introduction · Overview · Instruction List · ← Not programmed · Devices in Detail · ← Not programmed · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow · [1] [2] [3] · 7 times · 6 times · [1] [2] [3] · 4 times
Page 246 of the Mitsubishi Electronics MELSEC FX3S user manual — 9. Move and Compare – FNC 10 to FNC 19
Page 246 · click to enlarge
Page 246

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9. Move and Compare – FNC 10 to FNC 19

FNC 10 to FNC 19 provide fundamental data processing instructions such as data transfer and data comparison which are regarded as most important in applied instructions.

Mitsubishi Electronics MELSEC FX3S — 9. Move and Compare – FNC 10 to FNC 19 diagram (page 246)
Fig. 145 · 9. Move and Compare – FNC 10 to FNC 19

18 BCD Conversion to Binary Coded Decimal Section 9.9

Page 247 of the Mitsubishi Electronics MELSEC FX3S user manual — D ‚ D ‚ D ‚
Page 247 · click to enlarge
Page 247

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.1 FNC 10 – CMP / Compare 1

9.1 FNC 10 – CMP / Compare

Outline

This instruction compares two values, and outputs the result (smaller, equal or larger) to bit devices (3 points).

→ For the contact comparison instruction, refer to Chapter 28.

→ For floating point comparison, refer to Section 18.1.

1. Instruction format

Mnemonic Operation Condition P FNC 10

CMP D

Continuous Operation Pulse (Single) Operation

DCMP

Continuous Operation Pulse (Single) Operation

CMPP

DCMPP

2. Set data

Operand Type Description Data Type

Data or device number handled as comparison value 16- or 32-bit binary

Data or device number handled as comparison source 16- or 32-bit binary

Head bit device number to which comparison result is output Bit

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

Specified the Device & Constant

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S2 S3

3 S2 S3

S1: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S3: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (CMP and CMPP)

The comparison value and the comparison source are compared with each other. According to the

S 1 S 2

result (smaller, equal or larger), either one among , +1 or +2 turns ON.

D D D

  • The source data are handled as binary values.

S 1 S 2

  • Comparison is executed algebraically. Example: − 10 < 2

CMP S 1 ‚

S 2 ‚ D ‚

48 49 50 51

> S1 ‚ S2 ‚ ] ". Turns ON in the case of " [

S 1 ‚ S 2 ‚

= S1 ‚ S2 ‚ ] ". Turns ON in the case of " [

FNC10-FNC19 Move & Compare

< S1 ‚ S2 ‚ ] ". Turns ON in the case of " [

FNC20-FNC29 Arith. & Logic Operation

Even if the command input turns OFF and CMP instruction is not executed, , +1 and +2 latch the status just before the command input turns OFF from ON.

D ‚ D ‚ D ‚

Show 26 more labels / short text on this page
Introduction · Overview · 16-bit Instruction · Mnemonic Operation Condition · 32-bit Instruction · 7 steps CMP · 13 steps · Instruction List · Devices in Detail · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Before Programming · Basic Instruction · Command · Command · input · FNC00-FNC09 Program Flow · input · Latched · +1 · Latched · +2 · Latched
Page 248 of the Mitsubishi Electronics MELSEC FX3S user manual — X000 FNC 40
Page 248 · click to enlarge
Page 248

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.1 FNC 10 – CMP / Compare

2. 32-bit operation (DCMP and DCMPP)

The comparison value [ +1, ] and the comparison source [ +1, ] are compared with each other.

S 1 S 1 S 2 S 2

According to the result (smaller, equal or larger), either , +1 or +2 turns ON.

D D D

  • The source data [ +1, ] [ +1, ] are handled as binary values.

S 1 S 1 S 2 S 2

  • Comparison is executed algebraically. Example: − 125400 < 22466
Mitsubishi Electronics MELSEC FX3S — S 1 S 1 S 2 S 2 diagram (page 248)
Fig. 146

> ] ". Turns ON in the case of

+1, " [ ] S1 ‚ S1 ‚ +1, [ S2 ‚ S2 ‚

= +1, ] S1 ‚ S1 ‚ Turns ON in the case of

+1, [ S2 ‚ S2 ‚ " [ ] ".

+1, ] S1 ‚ S1 ‚ +1, [ S2 ‚ S2 ‚ " [ ] ".

Even if the command input turns OFF and DCMP instruction is not executed, , +1 and +2 latch the status just before the command input turns OFF from ON.

Caution

1. Number of occupied devices

From the device specified as , three devices are occupied. Make sure not to use those devices in another control.

Program examples

1. When comparing the current value of a counter

Mitsubishi Electronics MELSEC FX3S — Program examples diagram (page 248)
Fig. 147 · Program examples

Turns ON in the case of "K100 > C20 (Current value)" .

Turns ON in the case of "K100 = C20 (Current value)" .

Turns ON in the case of "K100 < C20 (Current value)" .

If it is necessary to clear the comparison result when the instruction is not executed, add the following contents under the above program.

1. RST instruction

RST M0

RST M1

RST M2

2. ZRST instruction

X000 FNC 40

ZRST M0 M2 M0 to M2 are reset.

Page 249 of the Mitsubishi Electronics MELSEC FX3S user manual — D ‚ D ‚ D ‚
Page 249 · click to enlarge
Page 249

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.2 FNC 11 – ZCP / Zone Compare 1

9.2 FNC 11 – ZCP / Zone Compare

Outline

This instruction compares two values (zone) with the comparison source, and outputs the result (smaller, equal or larger) to bit devices (3 points).

→ For the contact comparison instruction, refer to Chapter 28.

→ For floating point comparison, refer to Section 18.2.

1. Instruction format

Mnemonic Operation Condition P FNC 11

ZCP D

Continuous Operation Pulse (Single) Operation

DZCP

Continuous Operation Pulse (Single) Operation

ZCPP

DZCPP

2. Set data

Operand Type Description Data Type

Data or device number handled as lower comparison value 16- or 32-bit binary

Data or device number handled as upper comparison value 16- or 32-bit binary

Data or device number handled as comparison source 16- or 32-bit binary

Head bit device number to which comparison result is output Bit

3. Applicable devices

Bit Devices Word Devices Others

Specified the Device & Constant

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S2 S3

3 S2 S3

3 S2 S3

S1: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S3: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (ZCP and ZCPP)

The lower comparison value and upper comparison value are compared with the comparison source

S 1 S 2

S D D D

. According to the result (smaller, within zone or larger), either , +1 or +2 turns ON.

  • Comparison is executed algebraically. Example: − 10 < 2 < 10

S 1 ‚ S 2 ‚ S ‚

ZCP

Turns ON in the case of

S1 ‚ > S ‚ ] ". " [

FNC10-FNC19 Move & Compare

Turns ON in the case of

S1 ‚ ≤ S ‚ S2 ‚ ≤ ] ". " [

Turns ON in the case of

S ‚ S2 ‚ > ] ". " [

FNC20-FNC29 Arith. & Logic Operation

Even if the command input turns OFF and ZCP instruction is not executed, , +1 and +2 latch the status just before the command input turns OFF from ON.

D ‚ D ‚ D ‚

Show 19 more labels / short text on this page
Introduction · Overview · 16-bit Instruction · Mnemonic Operation Condition · 32-bit Instruction · 9 steps ZCP · 17 steps · Instruction List · Devices in Detail · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow · Command · input
Page 250 of the Mitsubishi Electronics MELSEC FX3S user manual — M4
Page 250 · click to enlarge
Page 250

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.2 FNC 11 – ZCP / Zone Compare

2. 32-bit operation (DZCP and DZCPP)

The lower comparison value [ +1, ] and upper comparison value [ +1, ] are compared with the

S 1 S 1 S 2 S 2

comparison source [ +1, ]. According to the result (smaller, within zone or larger), either , +1

S S D D

or +2 turns ON.

  • Comparison is executed algebraically. Example: − 125400 < 22466 < 1015444
Mitsubishi Electronics MELSEC FX3S — S S D D diagram (page 250)
Fig. 148

S1 ‚ S2 ‚ S ‚ D ‚

+1, [ S ‚ S ‚ +1, ] S1 ‚ S1 ‚ ] ". " [

+1, [ S ‚ S ‚ ] +1, ] S1 ‚ S1 ‚ ≤ +1, [ S2 ‚ S2 ‚ ] ". " [

+1, S ‚ S ‚ ] > +1, [ S2 ‚ S2 ‚ ] ". " [

Even if the command input turns OFF and DZCP instruction is not executed, , +1 and +2 latch the status just before the command input turns OFF from ON.

Cautions

1. Number of occupied devices

From the device specified as , three devices are occupied. Make sure not to use devices used in another control.

2. Upper comparison value and lower comparison value

The lower comparison value should be smaller than the upper comparison value .

S 1 S 2

1. When the lower comparison value is smaller than the upper comparison value

S 1 S 2

S1 ‚ S2 ‚ S ‚ D ‚

ZCP K100 K120 C30 M3

M 3

Turns ON in the case of "K100 > C30 (Current value)" .

M 4

Turns ON in the case of "K100 ≤ C30 (Current value) ≤ K120" .

M3

M 5

M4

Turns ON in the case of "K120 < C30 (Current value)" .

M5

2. When the lower comparison value is larger than the upper comparison value

S 1 S 2

S1 ‚ S2 ‚ S ‚ D ‚

ZCP K120 K100 C30 M3

It is handled as K120 .

M 3

Turns ON in the case of "K120 > C30 (Current value)" .

M3

M 4

Turns ON in the case of "K120 = C30 (Current value)" .

M4

M 5

M5

Turns ON in the case of "K120 < C30 (Current value)" .

Show 4 more labels / short text on this page
119 120 121 · … · 119 120 121 · …
Page 251 of the Mitsubishi Electronics MELSEC FX3S user manual — ON Y002 OFF
Page 251 · click to enlarge
Page 251

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.3 FNC 12 – MOV / Move 1

9.3 FNC 12 – MOV / Move

Outline

This instruction transfers (copies) the contents of a device to another device.

1. Instruction format

Mnemonic Operation Condition P FNC 12

MOV D

DMOV

Continuous Operation Pulse (Single) Operation

Continuous Operation Pulse (Single) Operation

MOVP

DMOVP

2. Set data

Operand Type Description Data Type

Transfer source data or device number storing data 16- or 32-bit binary

Transfer destination device number 16- or 32-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

Specified the Device & Constant

3 S1 S2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (MOV and MOVP)

The contents of the transfer source are transferred to the transfer destination .

S D

  • While the command input is OFF, the transfer destination does not change.
  • When a constant (K) is specified as the transfer source , it is automatically converted into binary.

MOV S ‚ D ‚

S ‚ D ‚

When specifying digits of a bit device (K1X000 → K1Y000) The bit device transfers a maximum of 16 points(multiple of 4).

MOV K1X000 K1Y000

:K1X000 S ‚ :K1Y000 D ‚ X3 X2 X1 X0

ON OFFOFF ON OFF Y3 Y2 Y1 Y0

ON X000

FNC10-FNC19 Move & Compare

OFF X001

OFF X002

X3 X2 X1 X0

ON OFFOFF ON ON OFFOFF ON Y3 Y2 Y1 Y0

ON X003

ON Y000 OFF

ON Y001 OFF

FNC20-FNC29 Arith. & Logic Operation

ON Y002 OFF

ON Y003

Show 25 more labels / short text on this page
Introduction · Overview · 16-bit Instruction · Mnemonic Operation Condition · 32-bit Instruction · 5 steps MOV · 9 steps · Instruction List · Devices in Detail · Oper- · and Type · Unit Index Con- stant · Real Number · Charac- ter String Pointer · Before Programming · Command · Basic Instruction · input · FNC00-FNC09 Program Flow · Command · input · ON Command contact · Before execution · Transfer · After execution
Page 252 of the Mitsubishi Electronics MELSEC FX3S user manual — S S D D
Page 252 · click to enlarge
Page 252

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.3 FNC 12 – MOV / Move

When a word device is specified The word device transfers 1 point.

Mitsubishi Electronics MELSEC FX3S — 9.3 FNC 12 – MOV / Move diagram (page 252)
Fig. 149 · 9.3 FNC 12 – MOV / Move

2. 32-bit operation (DMOV and DMOVP)

The contents of the transfer source [ +1, ] are transferred to the transfer destination [ +1, ].

S S D D

  • While the command input is OFF, the transfer destination does not change.
Mitsubishi Electronics MELSEC FX3S — S S D D diagram (page 252)
Fig. 150
  • When a constant (K) is specified as the transfer source [ +1, ], it is automatically converted into binary.

+1, [ S ‚ S ‚ ]→ +1, [ ] D ‚ D ‚

When specifying digits of a bit device (K8X000 → K8Y000) The bit device transfers a maximum of 32 points (multiple of 4).

Mitsubishi Electronics MELSEC FX3S — S S D D diagram (page 252)
Fig. 151

When a word device is specified The word device transfers 1 point.

Mitsubishi Electronics MELSEC FX3S — S S D D diagram (page 252)
Fig. 152
Page 253 of the Mitsubishi Electronics MELSEC FX3S user manual — DMOV C235 D20(D21)
Page 253 · click to enlarge
Page 253

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.3 FNC 12 – MOV / Move 1

Program examples

1. When reading the current value of a timer and counter

X001 FNC 12

MOV T 0 D 20 (Current value of T0) → (D20) The operation is the same as a counter.

2. When indirectly specifying the set value of a timer or counter As the set value of the timer T20, two values can be specified by turning ON or OFF the switch X002. For specifying more than two set values, more than one switch is required.

X002 FNC 12

(K100) → (D 10)

MOV K100 D 10

X002 FNC 12

MOV K 50 D 10 (K50) → (D 10)

M 0

T 20

When X002 is ON, D10 = K100 (10-second timer). When X002 is OFF, D10 = K50 (5-second timer). D 10

3. When transferring a bit device The program written by basic instructions shown on the right can be expressed using MOV instruction as shown below.

Y000

Y001

Specified the Device & Constant

MOV K1X000 K1Y000 M8000

Y002

Y003

4. When transferring 32-bit data Make sure to use DMOV instruction for transferring the operation result of an applied instruction (such as MUL) whose operation result is output in 32 bits, and for transferring a 32-bit numeric value or transferring the current value of a high-speed counter (C235 to C255) which is a 32-bit device.

DMOV D0(D1) D10(D11) (D 1,D 0) → (D 11,D 10)

(Current value of C235) → (D21, D20)

DMOV C235 D20(D21)

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 12 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · RUN monitor · Before Programming · Command · input · Basic Instruction · Command · input · FNC00-FNC09 Program Flow
Page 254 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Applicable devices
Page 254 · click to enlarge
Page 254

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.4 FNC 13 – SMOV / Shift Move

9.4 FNC 13 – SMOV / Shift Move

Outline

This instruction distributes and composes data in units of digit (4 bits).

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 254)
Fig. 153 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 254)
Fig. 154 · 2. Set data

Word device number storing data whose digits will be moved 16-bit binary

m1 Head digit position to be moved 16-bit binary

m2 Number of digits to be moved 16-bit binary

Word device number storing data whose digits are moved 16-bit binary

n Head digit position of movement destination 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 254)
Fig. 155 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3 3 3

3 S1 S2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Page 255 of the Mitsubishi Electronics MELSEC FX3S user manual — PLC
Page 255 · click to enlarge
Page 255

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.4 FNC 13 – SMOV / Shift Move 1

Explanation of function and operation

1. 16-bit operation (SMOV and SMOVP)

The contents of the transfer source and transfer destination are converted into 4-digit BCD (0000 to

S D

9999) respectively. "m2" digits starting from the "m1"th digit are transferred to the transfer destination starting

from the "n"th digit, converted into binary, and then stored to the transfer destination .

  • While the command input is OFF, the transfer destination does not change.
  • When the command input turns ON, only the specified digits in the transfer destination are changed. The

transfer source and unspecified digits in the transfer destination do not change.

S D

SMOV m1 m2 n S ‚ D ‚

In the case of "m1 = 4, m2 = 2, n = 3".

[1] is converted from binary into BCD.

4th digit 1st digit 2nd digit 3rd digit

[2] "m2" digits starting from the "m1"th digit are

transferred to ’ starting from the "n"th digit.

Data is automatically converted. [1]

The digits of 103 and 100 of ’ are not affected even if data is transferred from

100 101 102 103

' (4-digit BCD data)

Command contact = ON

Digits are moved. [2]

’.

' (4-digit BCD data)

[3] The composed data (BCD) is converted into

100 101 102 103

binary, and stored to .

Data is automatically converted. [3]

Do not change.

Specified the Device & Constant

2. Extension function When M8168 is set to ON first and then SMOV instruction is executed, conversion from binary to BCD is not executed. Data is moved in units of 4 bits.

M8168

SMOV D 1 K 4 K 2 D 2 K 3

M8168 X010

M8168 is used for other instructions also.

After using M8168 for SMOV instruction, return it to OFF.

Program example

The data on three-digit digital switches are composed, and stored as binary data to D2.

102 101 100

M8000

BIN K2X020 D 2

(X020 to X027) 2-digit BCD → D2 (binary)

(X000 to X003) 1-digit BCD → D1 (binary)

BIN K1X000 D 1

8 1 8 1 8 1

SMOV D 1 K 1 K 1 D 2 K 3

X003 to X000 X027 to X020

FNC10-FNC19 Move & Compare

1-digit BCD data of D1 is transferred to the 3rd digit (BCD data) of D2, and automatically converted into binary data.

PLC

Data on three digital switches connected to non-consecutive input terminals are composed.

FNC20-FNC29 Arith. & Logic Operation

Show 14 more labels / short text on this page
Introduction · Overview · Command · input · Instruction List · (16-bit binary data) · ↓ · Devices in Detail · ↓ · ↓ · (16-bit binary data) · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 256 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 256 · click to enlarge
Page 256

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.5 FNC 14 – CML / Complement

9.5 FNC 14 – CML / Complement

Outline

This instruction inverts data in units of bit, and then transfers (copies) the inverted data.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 256)
Fig. 156 · 1. Instruction format

2. Set data

Operand Type Description Data Type

Data to be inverted or word device number storing data 16- or 32-bit binary

Word device number storing inverted data 16- or 32-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 256)
Fig. 157 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (CML and CMLP)

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 256)
Fig. 158 · Explanation of function and operation

Each bit of a device specified as is inverted (from 0 to 1 or from 1 to 0), and then transferred to .

  • When a constant (K) is specified as , it is automatically converted into binary.
  • This operation is useful when a logically inverted output is required as an output from a PLC.

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 n5 b4 b3 b2 b1 b0

0 1 0 1 1 1 0 0 0 1 0 1 0 1 0 1

0 1 0 1 0 1 0 1 1 1 0 0 0 1 0 1

Page 257 of the Mitsubishi Electronics MELSEC FX3S user manual — K1Y000
Page 257 · click to enlarge
Page 257

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.5 FNC 14 – CML / Complement 1

2. 32-bit operation (DCML and DCMLP)

Each bit of devices specified as [ +1, ] is inverted (from 0 to 1 or from 1 to 0), and then transferred to

S S

[ +1, ].

D D

  • When a constant (K) is specified as [ +1, ], it is automatically converted into binary.

S S

  • This operation is useful when a logically inverted output is required as an output from a PLC.

DCML → +1, +1,

S ‚ D ‚ S ‚ S ‚ D ‚ D ‚

b31 b30 b29 b28 b27 b26 b25 to b7 b6 n5 b4 b3 b2 b1 b0

0 1 0 1 1 1 0 0 1 0 1 0 1 0 1

Sign bit (0Positive, 1: Negative)

When command contact turns ON

0 1 0 1 0 1 0 1 1 0 0 0 1 0 1

Inverted data is transferred.

Program examples

1. When receiving an inverted input The sequence program shown below can be written by CML instruction.

M 0

M 0

Specified the Device & Constant

M 1

M 1

M 2

M 2

M 3

M 3

M8000

CML K1X000 K1M0

2. When four bits are specified for a device with digit specification

S ‚ D ‚

X000 FNC 14

CML D 0 K1Y000 (D 0) → (K1Y000)

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 n5 b4 b3 b2 b1 b0

0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1

X000 = ON D 0

FNC10-FNC19 Move & Compare

Sign bit (0Positive, 1: Negative)

0 1 0 1 Y016 Y015 Y014 Y013 Y012 Y011 Y010 Y007 Y006 Y005 Y004 Y003 Y002 Y001 Y000

K1Y000

Y017

Do not change.

Inverted data is transferred.

FNC20-FNC29 Arith. & Logic Operation

Show 10 more labels / short text on this page
Introduction · Command · Overview · input · Instruction List · Devices in Detail · Before Programming · Basic Instruction · RUN monitor · FNC00-FNC09 Program Flow
Page 258 of the Mitsubishi Electronics MELSEC FX3S user manual — S D
Page 258 · click to enlarge
Page 258

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.6 FNC 15 – BMOV / Block Move

9.6 FNC 15 – BMOV / Block Move

Outline

This instruction transfers (copies) a specified number of data all at once.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 258)
Fig. 159 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 258)
Fig. 160 · 2. Set data

Transfer source data or device number storing data 16-bit binary

n Number of transferred points [n ≤ 512] 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 258)
Fig. 161 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

BMOV instruction transfers "n" points of data from to all at once.

S D

  • If the device number range is exceeded, data is transferred within the possible range.
Mitsubishi Electronics MELSEC FX3S — S D diagram (page 258)
Fig. 162

Transfer is enabled even if the transfer number range is overlapped.

To prevent overwriting before transfer of source data, data is automatically transferred in the order "[1] → [2] → [3]" according to the number overlap status.

Mitsubishi Electronics MELSEC FX3S — S D diagram (page 258)
Fig. 163
Page 259 of the Mitsubishi Electronics MELSEC FX3S user manual — 9.6 FNC 15 – BMOV / Block Move 1
Page 259 · click to enlarge
Page 259

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.6 FNC 15 – BMOV / Block Move 1

Mitsubishi Electronics MELSEC FX3S — 9.6 FNC 15 – BMOV / Block Move 1 diagram (page 259)
Fig. 164 · 9.6 FNC 15 – BMOV / Block Move 1

By controlling the direction inverse flag M8024*1 for BMOV (FNC 15) instruction, data can be transferred in two directions in one program.

D5 → D10 D6 → D11 D7 → D12

D5 ← D10 D6 ← D11 D7 ← D12

BMOV direction inverse flagOFF Normally OFF during operation

*1. M8024 is cleared when the PLC mode is changed from RUN to STOP.

When specifying digits of bit devices, specify the same number of digits for and .

Page 260 of the Mitsubishi Electronics MELSEC FX3S user manual — S D
Page 260 · click to enlarge
Page 260

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.6 FNC 15 – BMOV / Block Move

9.6.1 Function of transfer between file registers and data registers

BMOV (FNC 15) instruction has a special function for file registers (D1000 and later).

→ For details on file registers, refer to Section 4.9.

1. What are file registers In the parameters, D1000 to D7999 can be set as file registers, and written to and read from the program memory area. D1000 to D2999 in the FX 3S PLC.
1. Outline of setting File registers (D1000 to D7999) do not exist in the initial status. They are valid only when some number of file registers are secured by parameter setting in a programming tool.
2. Number of file registers In parameter setting, set 500 file registers as 1 block.

1 to 14 blocks*1 (each of which has 500 file registers) can be set. 1 block occupies 500 steps in the program memory area.

*1. 1 to 4 blocks in the FX3S PLC.

3. Difference between BMOV (FNC 15) instruction and other instructions The table below shows the difference between BMOV (FNC 15) instruction and other instructions with regard to file registers (D1000 and later).
Mitsubishi Electronics MELSEC FX3S — 9.6.1 Function of transfer between file registers and data registers diagram (page 260)
Fig. 165 · 9.6.1 Function of transfer between file registers an…

BMOV instruction Can read from and write to the file register area [A] inside the program memory. −

Can read from and write to the data register area [B] inside the program memory in the same way as general data registers.

Because the data register area [B] is provided inside the system RAM in PLCs, its contents can be arbitrarily changed regardless of the memory cassette format

When restoring the power, data registers set as file registers are automatically copied from the file register area [A] to the data register area [B].

Mitsubishi Electronics MELSEC FX3S — 9.6.1 Function of transfer between file registers and data registers diagram (page 260)
Fig. 166 · 9.6.1 Function of transfer between file registers an…

When power is turned ON When PLC mode is changed from STOP to RUN

Devices D1000 and later specified as operands in applied instructions other than BMOV (FNC 15) , indirectly specified values for timers or counters or devices in RST instruction are read from and written to the area [B] in the same way as general data registers.

D1000 500 points × 14 blocks maximum (7000 points maximum)

The remaining area can be used as general purpose data registers.

2. Cautions on use

1. When updating the contents of a file register with the same number (same-number register update mode), make

sure that the file register number is equivalent between and .

S D

2. When using file registers in the same-number register update mode, make sure that the number of transfer points specified by "n" does not exceed the file register area.
3. If the file register area is exceeded while file registers are used in the same-number register update mode, an operation error (M8067) is caused and the instruction is not executed.
4. In the case of indexing (in the same-number register update mode)

When and are indexing with index, the instruction is executed if the actual device number is within the file register area and the number of transfer points does not exceed the file register area.

S D

Page 261 of the Mitsubishi Electronics MELSEC FX3S user manual — S D
Page 261 · click to enlarge
Page 261

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.6 FNC 15 – BMOV / Block Move 1

5. Handling of the memory cassette When changing the contents of file registers secured inside the memory cassette, confirm the following conditions: - Set the protect switch of the memory cassette to OFF. - Do not turn OFF the power while the contents of file registers are changed. If the power is turned OFF during the change, the data stored in file registers may be filled with unexpected values, or a parameter error may occur.

6) Execution time for writing data to file registers - In FX3U/FX3UC PLCs It takes 66 to 132 ms to write data in one continuous block (500 points) to the memory cassette (flash memory). Execution of the program is paused during this period. Because the watchdog timer is not refreshed during this period, it is necessary to take proper countermeasures such as inserting the WDT instruction into the sequence program. It takes longer time to write data to file registers stored in a memory cassette (flash memory) compared to writing data to file registers stored in the built-in memory. - In FX3S/FX3G/FX3GC PLCs It takes 80 ms to write data in one continuous block (500 points) to file registers. Note that execution of the program is paused during this period, but the watchdog timer is automatically refreshed. The time for writing data is same between file registers stored in the built-in memory and file registers stored in a memory cassette (EEPROM).

7) Allowable number of times of writing to the memory Data can be written to the memory cassette up to 10,000 times, and to the memory (EEPROM) built in FX3S/ FX3G/FX3GC PLCs up to 20,000 times. When a continuous operation type instruction is used for data writing in a program, data is written to the memory in every operation cycle of the PLC. To prevent this, make sure to use a pulse operation type instruction (BMOVP).

8. File register operation File registers are secured inside the built-in memory or memory cassette. Different from general data registers, file registers can be read and written only by peripheral equipment or BMOV (FNC 15) instruction.

Specified the Device & Constant

9. If a file register is not specified as the destination in BMOV (FNC 15) instruction, the file register is not accessed. a) Outline of memory operation

RAM Inside built-in memory

D 0 D200

D1100 500 points × 14 blocks maximum (7000 points maximum)

[A]

[B]

When X000 is set to ON, the data register area [B] is read.

n S ‚ D ‚

X000 FNC 15 BMOVP D1100 D200 K400

FNC10-FNC19 Move & Compare

A file register can be specified as . But if the same number with is specified, the same-number register update mode is selected.

D S

However, even if a file register having different number is specified for and respectively, data cannot be transferred from the file register area to another file register area. In such a case, read the contents

S D

of a file register specified as in the same-number register update mode to the data register area [B] once, and then write the data.

FNC20-FNC29 Arith. & Logic Operation

→ For the same-number register update mode of file registers, refer to Subsection 4.9.4.

Show 19 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Inside system · or memory cassette · Program · Image memory · memory · Program/ comment · Data register · Basic Instruction · Read · File register · Data register · Data register D7999 · FNC00-FNC09 Program Flow · b) Program example
Page 262 of the Mitsubishi Electronics MELSEC FX3S user manual — S D
Page 262 · click to enlarge
Page 262

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.7 FNC 16 – FMOV / Fill Move

9.7 FNC 16 – FMOV / Fill Move

Outline

This instruction transfers same data to specified number of devices.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 262)
Fig. 167 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 262)
Fig. 168 · 2. Set data

Transfer source data or device number storing data 16- or 32-bit binary

Head word device number of transfer destination (Same data is transferred from the transfer source at one time.) 16- or 32-bit binary

n Number of transfer points [K1≤n≤K512, H1≤n≤H1FF] 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 262)
Fig. 169 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (FMOV and FMOVP)

  • The contents of are transferred to "n" devices starting from .
  • The contents will be same among all of "n" devices.
  • If the number of points specified by "n" exceeds the device number range, data is transferred within the possible range.

S D

Mitsubishi Electronics MELSEC FX3S — S D diagram (page 262)
Fig. 170
  • While the command input is OFF, the transfer destination does not change.
  • While the command input is ON, the data of the transfer source does not change.
  • When a constant (K) is specified as the transfer source , it is automatically converted into binary.
Page 263 of the Mitsubishi Electronics MELSEC FX3S user manual — X000 FNC 16
Page 263 · click to enlarge
Page 263

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.7 FNC 16 – FMOV / Fill Move 1

2. 32-bit operation (DFMOV and DFMOVP)

The contents of [ +1, ] are transferred to "n" 32-bit devices starting from [ +1, ].

S S D D

  • The contents will be the same among all of "n" 32-bit devices.
  • If the number of points specified by "n" exceeds the device number range, data is transferred within the possible range.
  • While the command input is OFF, the transfer destination [ +1, ] does not change.

D D

  • While the command input is ON, the data of the transfer source [ +1, ] does not change.

S S

  • When a constant (K) is specified as the transfer source [ +1, ], it is automatically converted into binary.

S S

X000 FNC 16 DFMOV n S ‚ D ‚

S ‚ D ‚

S ‚ D ‚

Specified the Device & Constant

Program example

1. When writing specified data to two or more devices

n S ‚ D ‚

X000 FNC 16

FMOV K 0 D 0 K 5

S ‚ D ‚

K 3 …… K 0

→

K 0 K 0 D 0

……

K 0 D 1

→

K 5 K 0

……

→

K 0 D 2

K 65 K 0

……

→

K 0 D 3

K 7 K 0

……

K100 → K 0

K 0 D 4

Values before execution are shown as examples.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 15 more labels / short text on this page
Introduction · Overview · Instruction List · +1, +1, · +3, +2 · +5, +4 · n · Devices in Detail · +7, +6 · +9, +8 · Before Programming · Before execution · After execution · Basic Instruction · FNC00-FNC09 Program Flow
Page 264 of the Mitsubishi Electronics MELSEC FX3S user manual — 2. 32-bit operation (DXCH and DXCHP)
Page 264 · click to enlarge
Page 264

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.8 FNC 17 – XCH / Exchange

9.8 FNC 17 – XCH / Exchange

Outline

This instruction exchanges data between two devices.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 264)
Fig. 171 · 1. Instruction format

2. Set data

Operand Type Description Data Type

Device number storing data to be exchanged. 16- or 32-bit binary

Device number storing data to be exchanged. 16- or 32-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 264)
Fig. 172 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

Explanation of function and operation

1. 16-bit operation (XCH and XCHP)

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 264)
Fig. 173 · Explanation of function and operation

2. 32-bit operation (DXCH and DXCHP)

Mitsubishi Electronics MELSEC FX3S — 2. 32-bit operation (DXCH and DXCHP) diagram (page 264)
Fig. 174 · 2. 32-bit operation (DXCH and DXCHP)

Data is exchanged between [ +1, ] and [ +1, ].

FNC 17 DXCHP +1, +1, D1 ‚ D2 ‚ D1 ‚ D2 ‚ D1 ‚ D2 ‚

Page 265 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 D 2
Page 265 · click to enlarge
Page 265

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.8 FNC 17 – XCH / Exchange 1

Extension function (function compatible between the FX2 Series and the FX2C Series)

When the instruction is executed while M8160 is ON, high-order 8 bits (byte) and low-order 8 bits (byte) of a word device are exchanged with each other. Because this instruction works in the same way as SWAP (FNC147) instruction, use SWAP instruction when programming a new exchange. In a 32-bit operation, high-order 8 bits (byte) and low-order 8 bits (byte) of each word device are exchanged for each other.

SWAP X000

M8160

DXCH D10 D10

M8000

M8160

High-order 8 bits Low-order 8 bits

High-order 8 bits Low-order 8 bits

Error

An operation error occurs in the following case. The error flag M8067 turns ON, and the error code is stored in D8067.

  • When M8160 is ON, and the device number is different between and

D 1 D 2

Specified the Device & Constant

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 7 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 266 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 266 · click to enlarge
Page 266

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.9 FNC 18 – BCD / Conversion to Binary Coded Decimal

9.9 FNC 18 – BCD / Conversion to Binary Coded Decimal

Outline

This instruction converts binary (BIN) data into binary-coded decimal (BCD) data. Binary data is used in operations in PLCs. Use this instruction to display numeric values on the seven-segment display unit equipped with BCD decoder.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 266)
Fig. 175 · 1. Instruction format

2. Set data

Operand Type Description Data Type

Word device number storing the conversion source (binary) data 16- or 32-bit binary

Word device number of the conversion destination (binary-coded decimal) data 16- or 32-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 266)
Fig. 176 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3 3 3

3 S1 S2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (BCD and BCDP)

This instruction converts the binary (BIN) data of into binary-coded decimal (BCD) data, and transfers the

converted BCD data to .

  • The data of can be converted if it is ranging from K0 to K9999 (BCD).
  • The table below shows digit specification for and .
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 266)
Fig. 177 · Explanation of function and operation
Page 267 of the Mitsubishi Electronics MELSEC FX3S user manual — Errors
Page 267 · click to enlarge
Page 267

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.9 FNC 18 – BCD / Conversion to Binary Coded Decimal 1

2. 32-bit operation (DBCD and DBCDP)

This instruction converts the binary (BIN) data of [ +1, ] into binary-coded decimal (BCD) data, and

S S

transfers the converted BCD data to [ +1, ].

D D

  • The data of [ +1, ] can be converted if it is ranging from K0 to K99999999 (BCD).

S S

  • The table below shows digit specification for [ +1, ] and [ +1, ].

S S D D

PLC DBCD (FNC 18)

BIN

S ‚ D ‚

DBCD

Y034 Y030 Y024 Y020 Y014 Y010 Y004 Y000 Y037 Y033 Y027 Y023 Y017 Y013 Y007 Y003

When "K8Y000" is specified

BCD

[ +1, ] Number of digits Data range

D D

K1Y000 1 0 to 9

K2Y000 2 00 to 99

K3Y000 3 000 to 999

K4Y000 4 0000 to 9999

K5Y000 5 00000 to 99999

Specified the Device & Constant

K6Y000 6 000000 to 999999

K7Y000 7 0000000 to 9999999

K8Y000 8 00000000 to 99999999

Related instruction

BIN (FNC 19) Converts binary-coded decimal (BCD) data into binary (BIN) data.

Cautions

1. When using SEGL (FNC 74) or ARWS (FNC 75) instruction Because conversion between binary-coded decimal data and binary data is automatically executed in SEGL (FNC 74) and ARWS (FNC 75) instructions, BCD instruction is not required.
2. Handling of BCD inputs and outputs Binary data is used in all operations in PLCs including arithmetic operations (+, − , × and ÷ ), increment and decrement instructions.
  • When receiving the digital switch information in the binary-coded decimal (BCD) format into a PLC, use BIN (FNC 19) instruction for converting BCD data into binary data.
  • When outputting data to the seven-segment display unit handling binary-coded decimal (BCD) data, use BCD (FNC 18) instruction for converting binary data into BCD data.

Errors

In BCD or BCDP (16-bit type) instructions, an operation error occurs when the value is outside the range from 0 to 9999.

FNC10-FNC19 Move & Compare

In DBCD or DBCDP (32-bit type) instructions, an operation error occurs when the value is outside the range from 0 to 99,999,999.

FNC20-FNC29 Arith. & Logic Operation

Show 10 more labels / short text on this page
Introduction · Command · Overview · input · Instruction List · Devices in Detail · Before Programming · Instruction Function · Basic Instruction · FNC00-FNC09 Program Flow
Page 268 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. When the seven-segment display unit has 5 to 8 digits
Page 268 · click to enlarge
Page 268

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.9 FNC 18 – BCD / Conversion to Binary Coded Decimal

Program examples

1. When the seven-segment display unit has 1 digit

Mitsubishi Electronics MELSEC FX3S — Program examples diagram (page 268)
Fig. 178 · Program examples

2. When the seven-segment display unit has 2 to 4 digits

Mitsubishi Electronics MELSEC FX3S — 2. When the seven-segment display unit has 2 to 4 digits diagram (page 268)
Fig. 179 · 2. When the seven-segment display unit has 2 to 4 di…

Output destination In the case of 2 digits: K2 In the case of 3 digits: K3 In the case of 4 digits: K4

3. When the seven-segment display unit has 5 to 8 digits

Mitsubishi Electronics MELSEC FX3S — 3. When the seven-segment display unit has 5 to 8 digits diagram (page 268)
Fig. 180 · 3. When the seven-segment display unit has 5 to 8 di…

Output destination In the case of 5 digits: K5 In the case of 6 digits: K6 In the case of 7 digits: K7 In the case of 8 digits: K8

Page 269 of the Mitsubishi Electronics MELSEC FX3S user manual — BIN
Page 269 · click to enlarge
Page 269

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.10 FNC 19 – BIN / Conversion to Binary 1

9.10 FNC 19 – BIN / Conversion to Binary

Outline

This instruction converts binary-coded decimal (BCD) data into binary (BIN) data. Use this instruction to convert a binary-coded decimal (BCD) value such as a value set by a digital switch into binary (BIN) data and to receive the converted binary data so that the data can be handled in operations in PLCs.

1. Instruction format

P FNC 19

Mnemonic Operation Condition 16-bit Instruction

BIN D

Continuous Operation Pulse (Single) Operation

DBIN

Continuous Operation Pulse (Single) Operation

BINP

DBINP

2. Set data

Operand Type Description Data Type

Word device number storing the conversion source (binary-coded decimal) data 16- or 32-bit binary

Word device number of the conversion destination (binary) 16- or 32-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Specified the Device & Constant

3 S1 S2 3 3 3

3 S1 S2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (BIN and BINP)

This instruction converts the binary-coded decimal (BCD) data of into binary (BIN) data, and transfers the

converted binary data to .

  • The data of can be converted if it is ranging from K0 to K9999 (BCD).
  • The table below shows digit specification for and .

S D

BCD

9 7 8 6 S ‚ D ‚

BIN

When "K4X000" is specified

X014 X010 X004 X000 X017 X013 X007 X003

BIN

BIN (FNC 19)

PLC

FNC10-FNC19 Move & Compare

Number of digits Data range

K1X000 1 0 to 9

K2X000 2 00 to 99

K3X000 3 000 to 999

FNC20-FNC29 Arith. & Logic Operation

K4X000 4 0000 to 9999

Show 18 more labels / short text on this page
Introduction · Overview · Mnemonic Operation Condition · 32-bit Instruction · 5 steps BIN · 9 steps · Instruction List · Devices in Detail · Oper- · and Type · Unit Index Con- stant · Real Number · Charac- ter String Pointer · Before Programming · Basic Instruction · Command · input · FNC00-FNC09 Program Flow
Page 270 of the Mitsubishi Electronics MELSEC FX3S user manual — Error
Page 270 · click to enlarge
Page 270

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.10 FNC 19 – BIN / Conversion to Binary

2. 32-bit operation (DBIN and DBINP)

This instruction converts the binary-coded decimal (BCD) data of [ +1, ] into binary (BIN) data, and

S S

transfers the converted binary data to [ +1, ].

D D

  • The data of [ +1, ] can be converted if it is ranging from 0 to 99,999,999 (BCD).

S S

Mitsubishi Electronics MELSEC FX3S — S S diagram (page 270)
Fig. 181
  • The table below shows digit specification for [ +1, ] and [ +1, ].

X034 X030 X024 X020 X014 X010 X004 X000 X037 X033 X027 X023 X017 X013 X007 X003

Mitsubishi Electronics MELSEC FX3S — S S diagram (page 270)
Fig. 182

Related instruction

BCD (FNC 18) Converts binary (BIN) data into binary-coded decimal (BCD) data.

Cautions

1. When using DSW (FNC 72) instruction Because conversion between binary-coded decimal data and binary data is automatically executed in DSW (FNC 72) instruction, BIN instruction is not required.
2. Handling of BCD inputs and outputs Binary data is used in all operations in PLCs including arithmetic operations (+, − , × and ÷ ), increment and decrement instructions.
  • When receiving the digital switch information in the binary-coded decimal (BCD) format into a PLC, use BIN (FNC 19) instruction for converting BCD data into binary data.
  • When outputting data to the seven-segment display unit handling binary-coded decimal (BCD) data, use BCD (FNC 18) instruction for converting binary data into BCD data.

Error

When the data of is not binary-coded decimal (BCD), M8067 (operation error) turns ON. But M8068 (operation error latch) does not turn ON.

Instruction Function

Page 271 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. When the digital switch has 5 to 8 digits
Page 271 · click to enlarge
Page 271

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

9 Move and Compare – FNC 10 to FNC 19

9.10 FNC 19 – BIN / Conversion to Binary 1

Mitsubishi Electronics MELSEC FX3S — 9.10 FNC 19 – BIN / Conversion to Binary 1 diagram (page 271)
Fig. 183 · 9.10 FNC 19 – BIN / Conversion to Binary 1

2. When the digital switch has 2 to 4 digits

In the case of 2 digits: K2 In the case of 3 digits: K3 In the case of 4 digits: K4

3. When the digital switch has 5 to 8 digits

K4 K3 K2 K1 K8 K7 K6 K5 FNC 19

Output destination In the case of 5 digits: K5 In the case of 6 digits: K6 In the case of 7 digits: K7 In the case of 8 digits: K8

Page 272 of the Mitsubishi Electronics MELSEC FX3S user manual — 10. Arithmetic and Logical Operation (+, -, ×,÷ ) – FNC 20 to FNC 29
Page 272 · click to enlarge
Page 272

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10. Arithmetic and Logical Operation ( + , − , × , ÷ ) – FNC 20 to FNC 29

FNC 20 to FNC 29 provide instructions for arithmetic operations and logical operations of numeric data.

Mitsubishi Electronics MELSEC FX3S — 10. Arithmetic and Logical Operation (+, -, ×,÷ ) – FNC 20 to FNC 29 diagram (page 272)
Fig. 184 · 10. Arithmetic and Logical Operation (+, -, ×,÷ ) –…

Floating point operation instructions FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs offer not only arithmetic operation instructions in binary format but also arithmetic operation instructions in the floating point format.

Mitsubishi Electronics MELSEC FX3S — 10. Arithmetic and Logical Operation (+, -, ×,÷ ) – FNC 20 to FNC 29 diagram (page 272)
Fig. 185 · 10. Arithmetic and Logical Operation (+, -, ×,÷ ) –…

For details, refer to the explanation of each instruction.

→ For the floating point operation, refer to Chapter 18.

Page 273 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 1 S 2 S 2
Page 273 · click to enlarge
Page 273

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.1 FNC 20 – ADD / Addition 1

10.1 FNC 20 – ADD / Addition

Outline

This instruction executes addition by two values to obtain the result (A + B = C).

→ For the floating point addition instruction EADD (FNC120), refer to Section 18.8.

1. Instruction format

Mnemonic Operation Condition P FNC 20

ADD D

Continuous Operation Pulse (Single) Operation

DADD

Continuous Operation Pulse (Single) Operation

ADDP

DADDP

2. Set data

Operand type Description Data type

Data for addition or word device number storing data 16- or 32-bit binary

Data for addition or word device number storing data 16- or 32-bit binary

Word device number storing the addition result 16- or 32-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

Specified the Device & Constant

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

3 S1 S2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (ADD and ADDP)

The contents of are added to in binary format, and the addition result is transferred to .

S 2 S 1 D

input D ‚ S1 ‚ S2 ‚ D ‚

ADD S1 ‚ S2 ‚ + →

  • The most significant bit of each data indicates the sign (positive: 0 or negative: 1), and data is added algebraically. 5 + ( − 8) = − 3
  • When a constant (K) is specified in or , it is automatically converted into binary format.

S 1 S 2

2. 32-bit operation (DADD and DADDP)

The contents of [ +1, ] are added to [ +1, ] in binary format, and the addition result is

S 2 S 2 S 1 S 1

transferred to [ +1, ].

D 1 D 1

input D ‚ S1 ‚ S2 ‚ D ‚ S1 ‚ S2 ‚ D ‚

FNC10-FNC19 Move & Compare

DADD S1 ‚ S2 ‚ [ +1, ] + [ +1, ] → [ +1, ]

  • The most significant bit of each data indicates the sign (positive: 0 or negative: 1), and data is added algebraically. 5500 + ( − 8540) = − 3040
  • When a constant (K) is specified in [ +1, ] or [ +1, ], it is automatically converted into binary format.

S 1 S 1 S 2 S 2

FNC20-FNC29 Arith. & Logic Operation

Show 19 more labels / short text on this page
Introduction · Overview · 16-bit Instruction · Mnemonic Operation Condition · 32-bit Instruction · 7 steps ADD · 13 steps · Instruction List · Devices in Detail · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Before Programming · Basic Instruction · Command · FNC00-FNC09 Program Flow · Command
Page 274 of the Mitsubishi Electronics MELSEC FX3S user manual — ADD D 0 K 25 D 0 X001
Page 274 · click to enlarge
Page 274

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.1 FNC 20 – ADD / Addition

Related devices

1. Relationship between the flag operation and the sign (positive or negative) of a numeric value → For the flag operations, refer to Subsection 6.5.2.

M8020 Zero ON : When the operation result is 0 OFF : When the operation result is not 0

M8021 Borrow ON : When the operation result is less than −32768 (in 16-bit operation) or −2,147,483,648 (in 32-bit operation) OFF : When the operation result is not less than −32768 (in 16-bit operation) or −2,147,483,648 (in 32-bit operation)

M8022 Carry ON : When the operation result is more than 32767 (in 16-bit operation) or 2,147,483,647 (in 32-bit operation) OFF : When the operation result is not more than 32767 (in 16-bit operation) or 2,147,483,647 (in 32-bit operation)

−2, −1, 0, −32768

−1, 0, 1

32767, 0, 1, 2

The most significant bit of data becomes "1".

The most significant bit of data becomes "0".

−2, −1, 0, −2,147,483,648

−1, 0, 1

2,147,483,647, 0, 1, 2

Cautions

1. When using a 32-bit operation instruction (DADD or DADDP) When specifying word devices, a 16-bit word device on the low-order side is specified first, and a word device with the subsequent device number is automatically set for the high-order 16 bits. To prevent number overlap, it is recommended to always specify an even number, for example.
2. When specifying the same device in the source and destination The same device number can be specified for both the source and the destination. In this case, note that the addition result changes in every operation cycle if a continuous operation type instruction (ADD or DADD) is used.

ADD D 0 K 25 D 0 X001

(D 0) + 25 → (D 0)

Program example

1. Difference between ADD instruction and INC instruction caused by a program for adding "+1" When ADD[P] is executed, "1" is added to the contents of D0 every time X001 turns from OFF to ON. ADD[P] instruction is similar to INCP instruction described later except the contents shown in the table below:
Mitsubishi Electronics MELSEC FX3S — ADD D 0 K 25 D 0 X001 diagram (page 274)
Fig. 186

Flag (zero, borrow or carry) Operates Does not operate

+(+1)= +32767→0→+1→+2→ +32767→−32768→−32767

+(−1)= ←−2←−1←0←−32768 ⎯

+(+1)= +2,147,483,647→0→+1→+2→ +2,147,483,647→−2,147,483,648→−2,147,483,647

+(−1)= ←−2←−1←0←−2,147,483,648 ⎯

Show 11 more labels / short text on this page
Device Name Description · Zero flag · Zero flag · Zero flag · Borrow flag · Carry flag · Zero flag · Zero flag · Borrow flag · Zero flag · Carry flag
Page 275 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 1 S 2 S 2
Page 275 · click to enlarge
Page 275

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.2 FNC 21 – SUB / Subtraction 1

10.2 FNC 21 – SUB / Subtraction

Outline

This instruction executes subtraction using two values to obtain the result (A − B = C).

→ For the floating point subtraction instruction ESUB (FNC121), refer to Section 18.9.

1. Instruction format

Mnemonic Operation Condition P FNC 21

SUB D

Continuous Operation Pulse (Single) Operation

Continuous Operation Pulse (Single) Operation

DSUB

SUBP

DSUBP

2. Set data

Operand type Description Data type

Data for subtraction or word device number storing data 16- or 32-bit binary

Data for subtraction or word device number storing data 16- or 32-bit binary

Word device number storing the subtraction result 16- or 32-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

Specified the Device & Constant

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

3 S1 S2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (SUB and SUBP)

The contents of are subtracted from in binary format, and the subtraction result is transferred to .

S 2 S 1 D

input D ‚ S1 ‚ S2 ‚ D ‚

SUB S1 ‚ S2 ‚ − →

  • The most significant bit of each data indicates the sign (positive: 0 or negative: 1), and data is subtracted algebraically. 5 − ( − 8) = 13
  • When a constant (K) is specified in or , it is automatically converted into binary format.

S 1 S 2

2. 32-bit operation (DSUB and DSUBP)

The contents of [ +1, ] are subtracted from [ +1, ] in binary format, and the subtraction result

S 2 S 2 S 1 S 1

is transferred to [ +1, ].

D 1 D 1

input D ‚ S1 ‚ S2 ‚ D ‚ S1 ‚ S2 ‚ D ‚

FNC10-FNC19 Move & Compare

DSUB S1 ‚ S2 ‚ [ +1, ] − [ +1, ] → [ +1, ]

  • The most significant bit of each data indicates the sign (positive: 0 or negative: 1), and data is subtracted algebraically. 5500 − ( − 8540) = 14040
  • When a constant (K) is specified in [ +1, ] or [ +1, ], it is automatically converted into binary format.

S 1 S 1 S 2 S 2

FNC20-FNC29 Arith. & Logic Operation

Show 19 more labels / short text on this page
Introduction · Overview · Mnemonic Operation Condition · 16-bit Instruction · 32-bit Instruction · 7 steps SUB · 13 steps · Instruction List · Devices in Detail · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Before Programming · Basic Instruction · Command · FNC00-FNC09 Program Flow · Command
Page 276 of the Mitsubishi Electronics MELSEC FX3S user manual — SUB D 0 K 25 D 0 X001
Page 276 · click to enlarge
Page 276

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.2 FNC 21 – SUB / Subtraction

Related devices

1. Relationship between the flag operation and the sign (positive or negative) of a numeric value → For the flag operations, refer to Subsection 6.5.2.

M8020 Zero ON : When the operation result is 0 OFF : When the operation result is other than 0

M8021 Borrow ON : When the operation result is less than −32768 (in 16-bit operation) or −2,147,483,648 (in 32-bit operation) OFF : When the operation result is not less than −32768 (in 16-bit operation) or −2,147,483,648 (in 32-bit operation)

M8022 Carry ON : When the operation result is more than 32767 (in 16-bit operation) or 2,147,483,647 (in 32-bit operation) OFF : When the operation result is not more than 32767 (in 16-bit operation) or 2,147,483,647 (in 32-bit operation)

−2, −1, 0, −32768

−1, 0, 1

32767, 0, 1, 2

The most significant bit of data becomes "1".

The most significant bit of data becomes "0".

−2, −1, 0, −2,147,483,648

−1, 0, 1

2,147,483,647, 0, 1, 2

Cautions

1. When using a 32-bit operation instruction (DSUB or DSUBP) When specifying word devices, a 16-bit word device on the low-order side is specified first, and then a word device with the subsequent device number is automatically set for the high-order 16 bits. To prevent number overlap, it is recommended to always specify an even number, for example.
2. When specifying the same device in the source and destination The same device number can be specified for both the source and the destination. In this case, note that the addition result changes in every operation cycle if a continuous operation type instruction (SUB or DSUB) is used.

SUB D 0 K 25 D 0 X001

(D 0) − 25 → (D 0)

Program example

1. Difference between the SUB instruction and the DEC instruction used by a program for subtracting "1" When SUB[P] is executed, "1" is subtracted from the contents of D0 every time X001 turns from OFF to ON. SUB[P] instruction is similar to DECP instruction described later except the contents shown in the table below:
Mitsubishi Electronics MELSEC FX3S — SUB D 0 K 25 D 0 X001 diagram (page 276)
Fig. 187

Flag (zero, borrow or carry) Operates Does not operate

−(+1)= ←−2←−1←0←−32768 −32,768→+32,767→+32,766

−(−1)= +32767→0→+1→+2→ ⎯

−(+1)= ←−2←−1←0←−2,147,483,648 −2,147,483,648→+2,147,483,647→+2,147,483,646

−(−1)= +2,147,483,647→0→+1→+2→ ⎯

Show 11 more labels / short text on this page
Device Name Description · Zero flag · Zero flag · Zero flag · Borrow flag · Carry flag · Zero flag · Zero flag · Borrow flag · Zero flag · Carry flag
Page 277 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 2
Page 277 · click to enlarge
Page 277

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.3 FNC 22 – MUL / Multiplication 1

10.3 FNC 22 – MUL / Multiplication

Outline

This instruction executes multiplication by two values to obtain the result (A x B = C).

→ For the floating point multiplication instruction EMUL (FNC122), refer to Section 18.10.

1. Instruction format

Mnemonic Operation Condition P FNC 22

MUL D

Continuous Operation Pulse (Single) Operation

DMUL

Continuous Operation Pulse (Single) Operation

MULP

DMULP

2. Set data

Operand type Description Data type

Data for multiplication or word device number storing data 16- or 32-bit binary

Data for multiplication or word device number storing data 16- or 32-bit binary

Head word device number storing the multiplication result 32- or 64-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

Specified the Device & Constant

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

3 S1 S2 S3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs. S3: Available only in 16-bit operations (Not available in 32-bit operations)

Explanation of function and operation

1. 16-bit operation (MUL and MULP)

The contents of are multiplied by in binary format, and the multiplication result is transferred to 32-bit

S 1 S 2

[ +1, ] .

D D 1

BIN BIN BIN ( ) × ( ) → ( +1, ) 16 bits 16 bits 32 bits D ‚ S1 ‚ S2 ‚ D ‚ S1 ‚ S2 ‚ D ‚

MUL

  • The most significant bit of each data indicates the sign (positive: 0 or negative: 1), and data is multiplied algebraically. 5 × ( − 8) = − 40
  • When a constant (K) is specified in or , it is automatically converted into binary format.

S 1 S 2

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 19 more labels / short text on this page
Introduction · Overview · 16-bit Instruction · Mnemonic Operation Condition · 32-bit Instruction · 7 steps MUL · 13 steps · Instruction List · Devices in Detail · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Before Programming · Basic Instruction · Command · input FNC 22 · FNC00-FNC09 Program Flow
Page 278 of the Mitsubishi Electronics MELSEC FX3S user manual — Related devices
Page 278 · click to enlarge
Page 278

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.3 FNC 22 – MUL / Multiplication

  • When a digit (K1 to K8) is specified for [ +1, ] A digit can be specified ranging from K1 to K8. For example, when K2 is specified, only the low-order 8 bits can be obtained out of the product (32 bits).

D D

Mitsubishi Electronics MELSEC FX3S — D D diagram (page 278)
Fig. 188

Y027 Y026 Y025 … Y013 Y012 Y011 Y010 Y007 Y006 Y005 Y004 Y003 Y002 Y001 Y000

0 0 0 … 0 0 1 1 0 0 0 1 1 0 1 1

2. 32-bit operation (DMUL and DMULP)

Mitsubishi Electronics MELSEC FX3S — 2. 32-bit operation (DMUL and DMULP) diagram (page 278)
Fig. 189 · 2. 32-bit operation (DMUL and DMULP)

The contents of [ +1, ] are multiplied by [ +1, ] in binary format, and the multiplication result is

transferred to 64-bit [ +3, +2, +1, ] (four word devices).

D ‚ D ‚ D ‚ D ‚ BIN BIN [ +1, ] × [ +1, ] 32 bits 32 bits

BIN → [ +3, +2, +1, ] 64 bits

  • The most significant bit of each data indicates the sign (positive: 0 or negative: 1), and data is multiplied algebraically. 5500 × ( − 8540) = − 46,970,000
  • When a constant (K) is specified in [ +1, ] or [ +1, ], it is automatically converted into binary format.

S 1 S 1 S 2 S 2

  • When a digit (K1 to K8) is specified for [ +3, +2, +1, ] The result is obtained only for low-order 32 bits, and is not obtained for high-order 32 bits. Transfer the data to word devices once, then execute the operation.

D

Mitsubishi Electronics MELSEC FX3S — D D D D diagram (page 278)
Fig. 190

DMOV D100 K8Y000 D100 is output to Y017 to Y000 D101 is output to Y037 to Y020

DMOV D102 K8Y040 D102 is output to Y057 to Y040 D103 is output to Y077 to Y060

Related devices

1. Relationship between flag operation and numeric value

M8304 Zero ON: When the operation result is 0. OFF: When the operation result is a number other than 0.

Device Name Description

Page 279 of the Mitsubishi Electronics MELSEC FX3S user manual — DMUL D 0 D 2 D 4
Page 279 · click to enlarge
Page 279

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.3 FNC 22 – MUL / Multiplication 1

Cautions

1. Devices specified in

  • In a 32-bit operation (by DMUL or DMULP), Z cannot be specified in .
2. When monitoring the operation result in a programming tool Even if word devices are used, the operation result (64 bits) cannot be monitored at one time. In such a case, floating point operation is recommended.

→ For the floating point operation, refer to Chapter 18.

Program examples

1. 16-bit operation

S1 ‚ S2 ‚

MUL D 0 D 2 D 4

(D 0) × (D 2) → (D 5,D 4) 8 9 72

2. 32-bit operation

S1 ‚ S2 ‚ D ‚

X001 FNC 22

(D 1,D 0) × (D 3,D 2) → (D 7,D 6,D 5,D 4) 1756 327 574,212

DMUL D 0 D 2 D 4

Function Changes According to Versions

Specified the Device & Constant

The function of the FNC 22 instruction varies depending on the PLC version shown in the table below.

Item Function Summary FX3S FX3G FX3GC FX3U FX3UC

Ver. 1.00

Ver. 1.00

Ver. 1.40

Ver. 2.30

Ver. 2.30

or later Zero Flag Turns M8304 ON when the operation result of MUL instruc- tion is 0.

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 12 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Compatible Versions · or later · or later · or later · or later · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 280 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 2
Page 280 · click to enlarge
Page 280

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.4 FNC 23 – DIV / Division

10.4 FNC 23 – DIV / Division

Outline

This instruction executes division by two values to obtain the result (A ÷ B = C ... ).

→ For the floating point division instruction EDIV (FNC123), refer to Section 18.11.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 280)
Fig. 191 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 280)
Fig. 192 · 2. Set data

Data for division or word device number storing data (dividend) 16- or 32-bit binary

Data for division or word device number storing data (divisor) 16- or 32-bit binary

Head word device number storing the division result (quotient and remainder) 32- or 64-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 280)
Fig. 193 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

3 S1 S2 S3 3

S1:This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2:This function is supported only in FX3U/FX3UC PLCs. S3: Available only in 16-bit operations (Not available in 32-bit operations)

Explanation of function and operation

1. 16-bit operation (DIV and DIVP)

S 1 S 2 D

indicates the dividend, indicates the divisor, the quotient is transferred to , and the remainder is

Mitsubishi Electronics MELSEC FX3S — S 1 S 2 D diagram (page 280)
Fig. 194

Dividend Divisor Quotient Remainder BIN ( ) ÷ ( ) → ( ) ... ( +1) 16 bits 16 bits 16 bits 16 bits

DIV D ‚ S1 ‚ S2 ‚

D ‚ S1 ‚ S2 ‚ D ‚

  • The most significant bit of each data indicates the sign (positive: 0 or negative: 1), and data is divided algebraically. 36 ÷ ( − 5) = − 7 (quotient) ... 1 (remainder)
  • Two devices in total starting from are occupied to store the operation result (quotient and remainder). Make sure that these two devices are not used for another control.
  • When a constant (K) is specified as or , it is automatically converted into binary format.

S 1 S 2

Page 281 of the Mitsubishi Electronics MELSEC FX3S user manual — Error
Page 281 · click to enlarge
Page 281

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.4 FNC 23 – DIV / Division 1

2. 32-bit operation (DDIV and DDIVP)

[ +1, ] indicates the dividend, [ +1, ] indicates the divisor, the quotient is transferred to

S 1 S 1 S 2 S 2

[ +1, ]), and the remainder is transferred to [ +3, +2].

D

DDIV D ‚

S 1 ‚ S 2 ‚

Dividend Divisor BIN BIN [ +1, ] ÷ [ +1, ] 32 bits 32 bits

Quotient Remainder BIN BIN → [ +1, ] ... [ +3, +2] 32 bits 32 bits

D ‚ D ‚ D ‚ D ‚ S1 ‚ S2 ‚ S1 ‚ S2 ‚

  • Four devices in total starting from are occupied to store the operation result (quotient and remainder). Make sure that these four devices are not used for another control.
  • The most significant bit of each data indicates the sign (positive: 0 or negative: 1), and data is divided algebraically. 5500 ÷ ( − 540) = − 10 (quotient) ... 100 (remainder)
  • When a constant (K) is specified in [ +1, ] or [ +1, ], it is automatically converted into binary format.

S 1 S 1 S 2 S 2

Related devices

M8304 Zero ON : When the operation result is 0. OFF : When the operation result is a number other than 0.

ONCarry flag operates when the operation result is over 32,767 (16-bit operation) or
2,147,483,647 (32-bit operation). OFFWhen the operation result is less than 32,767 (16-bit operation) or 2,147,483,647

(32-bit operation).

Specified the Device & Constant

Cautions

1. Operation result

  • The most significant bit of the quotient and remainder indicates the sign (positive: 0, negative: 1) respectively.
  • The quotient is negative when either the dividend or divisor is negative. The remainder is negative when the dividend is negative.

2. Device specified as

  • The remainder is not obtained when a bit device is specified with digit specification.
  • In a 32-bit operation (by DDIV or DDIVP), Z cannot be specified as .

Error

  • When the divisor is "0", an operation error is caused and the instruction is not executed.
  • A operation error results when the operation result is over 32,767 (16-bit operation) or 2,147,483,647 (32-bit operation). (Turns the carry flag ON.)

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 11 more labels / short text on this page
Introduction · Command · input FNC 23 · Overview · Instruction List · Devices in Detail · Device Name Description · M8306 Carry · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 282 of the Mitsubishi Electronics MELSEC FX3S user manual — DDIV D 0 D 2 D 4
Page 282 · click to enlarge
Page 282

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.4 FNC 23 – DIV / Division

Program examples

1. 16-bit operation

S 1 ‚ S 2 ‚

Dividend Divisor Quotient Remainder (D 0) ÷ (D 2) → (D 4) ... (D 5) 100 33 3 1

DIV D 0 D 2 D 4

2. 32-bit operation

S 1 ‚ S 2 ‚ D ‚

X001 FNC 23

Dividend Divisor Quotient Remainder (D 1,D 0) ÷ (D 3,D 2) → (D 5,D 4) ... (D 7,D 6) 100,000 3333 30 10

DDIV D 0 D 2 D 4

Function Changes According to Versions

The function of the FNC 23 instruction varies depending on the PLC version shown in the table below.

Mitsubishi Electronics MELSEC FX3S — DDIV D 0 D 2 D 4 diagram (page 282)
Fig. 195

Item Function Summary FX3S FX3G FX3GC FX3U FX3UC

Zero Flag Turns M8304 ON when the operation result of DIV instruction is 0.

Turns M8306 ON when the operation result of DIV instruction overflows. 16-bit operation: Only when the maximum negative value (-32,768) is divided by -1. 32-bit operation: Only when the maximum negative value (-2,147,483,648) is divided by -1.

Page 283 of the Mitsubishi Electronics MELSEC FX3S user manual — 2. Flag operations
Page 283 · click to enlarge
Page 283

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.5 FNC 24 – INC / Increment 1

10.5 FNC 24 – INC / Increment

Outline

This instruction increments the data of a specified device by "1".

1. Instruction format

Mnemonic Operation Condition P FNC 24

INC D

Continuous Operation Pulse (Single) Operation

Continuous Operation Pulse (Single) Operation

DINC

INCP

DINCP

2. Set data

Operand type Description Data type

Word device number storing data to be incremented by "1" 16- or 32-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Specified the Device & Constant

Explanation of function and operation

1. 16-bit operation (INC and INCP)

The contents of are incremented by "1", and the increment result is transferred to .

D D

INCP + 1 → D ‚ D ‚ D ‚

2. 32-bit operation (DINC and DINCP)

The contents of [ +1, ] are incremented by "1", and the increment result is transferred to [ +1,

D D D

].

DINCP D ‚ D ‚ [ +1, ] + 1 → [ + 1, ] D ‚ D ‚ D ‚

Cautions

1. Note that data is incremented in every operation cycle in a continuous operation type instruction.

2. Flag operations

1. 16-bit operation When "+32767" is incremented by "1", the result is " − 32768". Flags (zero, carry and borrow) are not activated at this time.

FNC10-FNC19 Move & Compare

2. 32-bit operation When "+2,147,483,647" is incremented by "1", the result is " − 2,147,483,648". Flags (zero, carry and borrow) are not activated at this time.

FNC20-FNC29 Arith. & Logic Operation

Show 21 more labels / short text on this page
Introduction · Overview · 16-bit Instruction · Mnemonic Operation Condition · 32-bit Instruction · 3 steps INC · 5 steps · Instruction List · Devices in Detail · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Before Programming · Command · input FNC 24 · Basic Instruction · Command · input FNC 24 · FNC00-FNC09 Program Flow
Page 284 of the Mitsubishi Electronics MELSEC FX3S user manual — CMPP K 10 Z M 0
Page 284 · click to enlarge
Page 284

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.5 FNC 24 – INC / Increment

Program example

MOVP K 0 Z

0 → (Z)

Z is cleared by the reset input X010.

M 1

The current values of counters C0 to C9 are converted into BCD format, and output to K4Y000.

(C 0Z) → (K4Y000) BIN BCD

BCDP C 0Z K4Y000

Every time X011 is set to ON, the current values of C0, C1 ... C9 are output one at a time.

INCP Z

(Z) + 1 → (Z)

When Z is "10", M1 turns ON.

CMPP K 10 Z M 0

Page 285 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 285 · click to enlarge
Page 285

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.6 FNC 25 – DEC / Decrement 1

10.6 FNC 25 – DEC / Decrement

Outline

This instruction decrements the data of a specified device by "1".

1. Instruction format

Mnemonic Operation Condition P FNC 25

DEC D

Continuous Operation Pulse (Single) Operation

Continuous Operation Pulse (Single) Operation

DDEC

DECP

DDECP

2. Set data

Operand type Description Data type

Word device number storing data to be decremented by "1" 16- or 32-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Specified the Device & Constant

Explanation of function and operation

1. 16-bit operation (DEC and DECP)

The contents of are decremented by "1", and the decremented result is transferred to .

D D

DECP D ‚ − 1 → D ‚ D ‚

2. 32-bit operation (DDEC and DDECP)

The contents of [ +1, ] are decremented by "1", and the decremented result is transferred to [ +1,

D D D

].

input FNC 25 DDECP D ‚ D ‚ [ +1, ] − 1 → [ + 1, ] D ‚ D ‚ D ‚

Cautions

1. Flag operations

1. 16-bit operation When " − 32768" is decremented by "1", the result is "+32767". Flags (zero, carry and borrow) are not activated at this time.

FNC10-FNC19 Move & Compare

2. 32-bit operation When " − 2,147,483,648" is decremented by "1", the result is "+2,147,483,647". Flags (zero, carry and borrow) are not activated at this time.

FNC20-FNC29 Arith. & Logic Operation

Show 20 more labels / short text on this page
Introduction · Overview · 16-bit Instruction · Mnemonic Operation Condition · 32-bit Instruction · 3 steps DEC · 5 steps · Instruction List · Devices in Detail · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Before Programming · Command · input FNC 25 · Basic Instruction · Command · FNC00-FNC09 Program Flow
Page 286 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 2
Page 286 · click to enlarge
Page 286

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.7 FNC 26 – WAND / Logical Word AND

10.7 FNC 26 – WAND / Logical Word AND

Outline

This instruction executes the logical product (AND) operation of two numeric values.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 286)
Fig. 196 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 286)
Fig. 197 · 2. Set data

Data used for logical product or word device number storing data 16- or 32-bit binary

Data used for logical product or word device number storing data 16- or 32-bit binary

Word device number storing the logical product result 16- or 32-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 286)
Fig. 198 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

3 S1 S2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (WAND and WANDP)

The logical product (AND) operation is executed to the contents of and in units of bit, and the result is

S 1 S 2

Mitsubishi Electronics MELSEC FX3S — S 1 S 2 diagram (page 286)
Fig. 199

S1 ‚ S2 ‚ ∧ → D ‚ S1 ‚ S2 ‚ D ‚

  • While the command input is OFF, the data of the transfer destination does not change.
  • While the command input is ON, the data of the transfer sources and do not change.
  • When a constant (K) is specified in the transfer sources and , it is automatically converted into binary format.
  • The logical product operation is executed in units of bit as shown in the table below (1 ∧ 1 = 1, 0 ∧ 1 = 0, 1 ∧ 0 = 0, 0 ∧ 0 = 0). 1: ON, 0: OFF
Mitsubishi Electronics MELSEC FX3S — S 1 S 2 diagram (page 286)
Fig. 200
Page 287 of the Mitsubishi Electronics MELSEC FX3S user manual — D D
Page 287 · click to enlarge
Page 287

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.7 FNC 26 – WAND / Logical Word AND 1

2. 32-bit operation (DAND and DANDP)

The logical product (AND) operation is executed to the contents of [ +1, ] and [ +1, ] in units of

S 1 S 1 S 2 S 2

bit, and the result is transferred to [ +1, ].

D D

S1 ‚ S2 ‚ +1, ∧ +1, → +1, D ‚ S1 ‚ S2 ‚ D ‚ S1 ‚ S2 ‚ D ‚

DAND

  • While the command input is OFF, the data of the transfer destination [ +1, ] does not change.

D D

  • While the command input is ON, the data of the transfer source [ +1, ] [ +1, ] do not change.

S 1 S 1 S 2 S 2

  • When a constant (K) is specified in the transfer source [ +1, ] [ +1, ], it is automatically converted into binary format.

S 1 S 1 S 2 S 2

  • The logical product operation is executed in units of bit as shown in the table below (1 ∧ 1 = 1, 0 ∧ 1 = 0, 1 ∧ 0 = 0, 0 ∧ 0 = 0). 1: ON, 0: OFF

D D

S 1 S 1 S 2 S 2

DAND (FNC 26) instruction

Logical operation (unitbit)

Specified the Device & Constant

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 11 more labels / short text on this page
Introduction · Command · input FNC 26 · Overview · Instruction List · +1, · +1, +1, · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 288 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 2
Page 288 · click to enlarge
Page 288

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.8 FNC 27 – WOR / Logical Word OR

10.8 FNC 27 – WOR / Logical Word OR

Outline

This instruction executes the logical sum (OR) operation of two numeric values.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 288)
Fig. 201 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 288)
Fig. 202 · 2. Set data

Data used for logical sum or word device number storing data 16- or 32-bit binary

Data used for logical sum or word device number storing data 16- or 32-bit binary

Word device number storing the logical sum result 16- or 32-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 288)
Fig. 203 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

3 S1 S2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (WOR and WORP)

The logical sum (OR) operation is executed to the contents of and in units of bit, and the result is

S 1 S 2

Mitsubishi Electronics MELSEC FX3S — S 1 S 2 diagram (page 288)
Fig. 204

S1 ‚ S2 ‚ D ‚ ∨ → S1 ‚ S2 ‚ D ‚

  • While the command input is OFF, the data of the transfer destination does not change.
  • While the command input is ON, the data of the transfer sources and do not change.
  • When a constant (K) is specified in the transfer sources and , it is automatically converted into binary format.
  • The logical sum operation is executed in units of bit as shown in the table below (1 ∨ 1 = 1, 0 ∨ 1 = 1, 0 ∨ 0 = 0, 1 ∨ 0 = 1). 1: ON, 0: OFF
Mitsubishi Electronics MELSEC FX3S — S 1 S 2 diagram (page 288)
Fig. 205
Page 289 of the Mitsubishi Electronics MELSEC FX3S user manual — D D
Page 289 · click to enlarge
Page 289

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.8 FNC 27 – WOR / Logical Word OR 1

2. 32-bit operation (DOR and DORP)

The logical sum (OR) operation is executed to the contents of [ +1, ] and [ +1, ] in units of bit,

S 1 S 1 S 2 S 2

and the result is transferred to [ +1, ].

D D

S1 ‚ S2 ‚ D ‚ +1, ∨ +1, → +1, S1 ‚ S2 ‚ D ‚ S1 ‚ S2 ‚ D ‚

DOR

  • While the command input is OFF, the data of the transfer destination [ +1, ] does not change.

D D

  • While the command input is ON, the data of the transfer source [ +1, ] [ +1, ] do not change.

S 1 S 1 S 2 S 2

  • When a constant (K) is specified in the transfer source [ +1, ] [ +1, ], it is automatically converted into binary format.

S 1 S 1 S 2 S 2

  • The logical sum operation is executed in units of bit as shown in the table below (1 ∨ 1 = 1, 0 ∨ 1 = 1, 0 ∨ 0 = 0, 1 ∨ 0 = 1). 1: ON, 0: OFF

D D

S 1 S 1 S 2 S 2

DOR (FNC 27) instruction

Logical operation (unitbit)

Specified the Device & Constant

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 11 more labels / short text on this page
Introduction · Command · input FNC 27 · Overview · Instruction List · +1, · +1, +1, · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 290 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 2
Page 290 · click to enlarge
Page 290

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.9 FNC 28 – WXOR / Logical Exclusive OR

10.9 FNC 28 – WXOR / Logical Exclusive OR

Outline

This instruction executes the exclusive logical sum (XOR) operation of two numeric values.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 290)
Fig. 206 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 290)
Fig. 207 · 2. Set data

Data used for exclusive logical sum or word device number storing data 16- or 32-bit binary

Data used for exclusive logical sum or word device number storing data 16- or 32-bit binary

Word device number storing the exclusive logical sum result 16- or 32-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 290)
Fig. 208 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

3 S1 S2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (WXOR and WXORP)

The exclusive logical sum (XOR) operation is executed to the contents of and in units of bit, and the

S 1 S 2

Mitsubishi Electronics MELSEC FX3S — S 1 S 2 diagram (page 290)
Fig. 209

S1 ‚ S2 ‚ D ‚ ∀ → S1 ‚ S2 ‚ D ‚

  • While the command input is OFF, the data of the transfer destination does not change.
  • While the command input is ON, the data of the transfer sources and do not change.
  • When a constant (K) is specified in the transfer sources and , it is automatically converted into binary format.
  • The logical exclusive sum operation is executed in units of bit as shown in the table below (1 ∀ 1 = 0, 0 ∀ 0 = 0, 1 ∀ 0 = 1, 0 ∀ 1 = 1). 1: ON, 0: OFF
Mitsubishi Electronics MELSEC FX3S — S 1 S 2 diagram (page 290)
Fig. 210
Page 291 of the Mitsubishi Electronics MELSEC FX3S user manual — X000 FNC 28
Page 291 · click to enlarge
Page 291

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.9 FNC 28 – WXOR / Logical Exclusive OR 1

2. 32-bit operation (DXOR and DXORP)

The exclusive logical sum (XOR) operation is executed to the contents of [ +1, ] and [ +1, ] in

S 1 S 1 S 2 S 2

units of bit, and the result is transferred to [ +1, ].

D D

S1 ‚ S2 ‚ D ‚ +1, ∀ +1, → +1, S1 ‚ S2 ‚ D ‚ S1 ‚ S2 ‚ D ‚

DXOR

  • While the command input is OFF, the data of the transfer destination [ +1, ] does not change.

D D

  • While the command input is ON, the data of the transfer source [ +1, ] [ +1, ] do not change.

S 1 S 1 S 2 S 2

  • When a constant (K) is specified in the transfer source [ +1, ] [ +1, ], it is automatically converted into binary format.

S 1 S 1 S 2 S 2

  • The exclusive logical sum operation is executed in units of bit as shown in the table below (1 ∀ 1 = 0, 0 ∀ 0 = 0, 1 ∀ 0 = 1, 0 ∀ 1 = 1). 1: ON, 0: OFF

D D

S 1 S 1 S 2 S 2

DXOR (FNC 28) instruction

Logical operation (unitbit)

Program example

By combining WXOR and CML (FNC 14) instructions, the exclusive logical sum not (XORNOT) operation can be executed.

Specified the Device & Constant

X000 FNC 28

WXOR D 10 D 12 D 14

CML D 14 D 14

FNC10-FNC19 Move & Compare

FNC20-FNC29 Arith. & Logic Operation

Show 11 more labels / short text on this page
Introduction · Command · input FNC 28 · Overview · Instruction List · +1, · +1, +1, · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 292 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 292 · click to enlarge
Page 292

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.10 FNC 29 – NEG / Negation

10.10 FNC 29 – NEG / Negation

Outline

This instruction obtains the complement of a numeric value (by inverting each bit and adding "1"). This instruction can be used to negate the sign of a numeric value.

→ For the Floating point negation ENEG (FNC128), refer to Section 18.16.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 292)
Fig. 211 · 1. Instruction format

2. Set data

Operand type Description Data type

Word device number which stores data for obtaining complement and will store the operation result (The operation result will be stored in the same word device number.) 16- or 32-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 292)
Fig. 212 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

Explanation of function and operation

1. 16-bit operation (NEG and NEGP)

Each bit of is inverted (0 → 1, 1 → 0), "1" is added, and then the result is stored in the original device.

NEGP D ‚ ( )+1 → D ‚ D ‚

2. 32-bit operation (DNEG and DNEGP)

Each bit of [ +1, ] is inverted (0 → 1, 1 → 0), "1" is added, and then the result is stored in the original device.

D D

input FNC 29 DNEGP

( + 1, ) +1 = ( + 1, ) D ‚ D ‚ D ‚ D ‚ D ‚

Caution

Command · input FNC 29 · Command

Page 293 of the Mitsubishi Electronics MELSEC FX3S user manual — Negative value expression and absolute value (reference)
Page 293 · click to enlarge
Page 293

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

10 Arithmetic and Logical Operation (+, −, ×, ÷) – FNC 20 to FNC 29

10.10 FNC 29 – NEG / Negation 1

Program examples

The program examples below are provided to obtain the absolute value of a negative binary value.

1. Obtaining the absolute value of a negative value using NEG instruction

M8000 FNC 44

In BON (ON bit check) instruction, M0 turns ON when the bit 15 (b15 among b0 to b15) of D10 is "1".

BON D 10 M 0 K 15 RUN monitor

M 0 FNC 29

NEGP instruction is executed for D10 only when M0 turns ON. D10 → D10

NEGP D 10

2. Obtaining the absolute value by SUB (subtraction) instruction Even if NEG instruction is not used, D30 always stores the absolute value of the difference.

CMP D 10 D 20 M 10 (D 10) > (D 20) (D10) = (D 20) (D 10) < (D 20) M 10 = ON M 11 = ON M 12 = ON

M 10

In the case of "D10 ≥ D20", D10 − D20 → D30.

SUB D 10 D 20 D 30

M 11

M 12

SUB D 20 D 10 D 30

In the case of "D10 < D20", D20 − D10 → D30.

Negative value expression and absolute value (reference)

Specified the Device & Constant

In PLCs, a negative value is expressed in 2’s complement. When the most significant bit is "1", it is a negative value, and its absolute value can be obtained by NEG instruction.

0 1 0

0 1

0

1

0 1

1 0

0 1 0

1 0 1

0 1

FNC10-FNC19 Move & Compare

1 0

1 0

The absolute value can be obtained up to 32767.

FNC20-FNC29 Arith. & Logic Operation

Show 7 more labels / short text on this page
Introduction · Overview · Instruction List · Devices in Detail · Before Programming · Basic Instruction · FNC00-FNC09 Program Flow
Page 294 of the Mitsubishi Electronics MELSEC FX3S user manual — 11. Rotation and Shift Operation – FNC 30 to FNC 39
Page 294 · click to enlarge
Page 294

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11. Rotation and Shift Operation – FNC 30 to FNC 39

FNC 30 to FNC 39 provide instructions for rotating and shifting bit data and word data in specified directions.

Mitsubishi Electronics MELSEC FX3S — 11. Rotation and Shift Operation – FNC 30 to FNC 39 diagram (page 294)
Fig. 213 · 11. Rotation and Shift Operation – FNC 30 to FNC 39
Page 295 of the Mitsubishi Electronics MELSEC FX3S user manual — M8022
Page 295 · click to enlarge
Page 295

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.1 FNC 30 – ROR / Rotation Right 11

11.1 FNC 30 – ROR / Rotation Right

FNC30-FNC39 Rotation and Shift

Outline

This instruction shifts and rotates the bit information rightward by the specified number of bits without the carry flag.

1. Instruction format

P FNC 30

Mnemonic Operation Condition 32-bit Instruction

ROR D

ROR

Continuous Operation Pulse (Single) Operation

9 steps Continuous Operation Pulse (Single) Operation

DROR

RORP

DRORP

2. Set data

Operand Type Description Data Type

Word device number storing data to be rotated rightward 16- or 32-bit binary

n Number of bits to be rotated

[n ≤ 16 (16-bit instruction), n ≤ 32 (32-bit instruction)]*1 16- or 32-bit binary

*1. Do not set a negative value to the number of bits to be rotated.

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FNC70-FNC79 External FX I/O Device

S1 S1 S1 3 3 3 S2 S3

n 3 S2 3 3

S1: In 16-bit operations, K4Y{{{, K4M{{{ and K4S{{{ are valid.

In 32-bit operations, K8Y{{{, K8M{{{ and K8S{{{ are valid. S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S3: This function is supported only in FX3U/FX3UC PLCs.

FNC80-FNC89 External FX Device

Explanation of function and operation

1. 16-bit operation (ROR and RORP) "n" bits out of 16 bits of are rotated rightward.

input FNC 30 RORP n D ‚

FNC100-FNC109 Data Transfer 2

  • The final bit is stored in the carry flag (M8022).
  • In a device with digit specification, K4 (16-bit instruction) is valid.

"n" bits (in the case of K4)

b15b14b13b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 Before execution

1 0

M8022

After the instruction is executed once

"n−1" bits

b0 to b3 (n−1) are moved.

Rightward rotation "n" bits The status of the bit "n−1" is copied.

FNC140-FNC149 Data Operation 2

High order Low order b15b14b13b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

0 1 0 Carry flag M8022

The contents of b3 are stored.

Show 22 more labels / short text on this page
FNC40-FNC49 Data Operation · 16-bit Instruction · Mnemonic Operation Condition · 5 steps · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · High order · Low order · FNC110-FNC139 Floating Point · Carry flag · After execution · Before shift · Before shift · b3 to b0 · b15 to b4 · FNC150-FNC159 Positioning Control
Page 296 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 296 · click to enlarge
Page 296

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.1 FNC 30 – ROR / Rotation Right

2. 32-bit operation (DROR and DRORP) "n" bits out of 32 bits of [ +1, ] are rotated rightward.

D D

input FNC 30 DRORP n D ‚

  • The final bit is stored in the carry flag (M8022).
  • In a device with digit specification, K8 (32-bit instruction) is valid.
Mitsubishi Electronics MELSEC FX3S — D D diagram (page 296)
Fig. 214

b15b14b13b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 1 0

1 0

The status of the bit "n−1" is copied.

"n" bits The status of the bit "n−1" is

b15b14b13b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

0 1 0

0 1 0 Carry flag M8022

Related device

→ For the carry flag use method, refer to Subsection 6.5.2.

M8022 Carry Turns ON when the bit shifted last from the lowest position is "1".

Cautions

  • In the case of continuous operation type instructions (ROR and DROR) Note that shift and rotation are executed in every scan time (operation cycle).
  • When a device with digit specification is specified as Only K4 (16-bit instruction) or K8 (32-bit instruction) is valid (examples: K4Y010 or K8M0).
  • Note that the 32-bit value [n+1, n] is valid when D or R is specified as "n" in a 32-bit instruction. In the case of "DROR D100 R0", "n" is [R1, R0].

Command · Device Name Description

Page 297 of the Mitsubishi Electronics MELSEC FX3S user manual — M8022
Page 297 · click to enlarge
Page 297

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.2 FNC 31 – ROL / Rotation Left 11

11.2 FNC 31 – ROL / Rotation Left

FNC30-FNC39 Rotation and Shift

Outline

This instruction shifts and rotates the bit information leftward by the specified number of bits without the carry flag.

1. Instruction format

P FNC 31

Mnemonic Operation Condition 32-bit Instruction

ROL D

ROL

Continuous Operation Pulse (Single) Operation

9 steps Continuous Operation Pulse (Single) Operation

DROL

ROLP

DROLP

2. Set data

Operand Type Description Data Type

Word device number storing data to be rotated leftward 16- or 32-bit binary

n Number of bits to be rotated

[n ≤ 16 (16-bit instruction), n ≤ 32 (32-bit instruction)]*1 16- or 32-bit binary

*1. Do not set a negative value to the number of bits to be rotated.

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FNC70-FNC79 External FX I/O Device

S1 S1 S1 3 3 3 S2 S3

n 3 S2 3 3

S1: In 16-bit operations, K4Y{{{, K4M{{{ and K4S{{{ are valid.

In 32-bit operations, K8Y{{{, K8M{{{ and K8S{{{ are valid. S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S3: This function is supported only in FX3U/FX3UC PLCs.

FNC80-FNC89 External FX Device

Explanation of function and operation

1. 16-bit operation (ROL and ROLP) "n" bits out of 16 bits of are rotated leftward.

input FNC 31 ROLP n D ‚

FNC100-FNC109 Data Transfer 2

  • The final bit is stored in the carry flag (M8022).
  • In a device with digit specification, K4 (16-bit instruction) is valid.

"n" bits (in the case of K4)

b15b14b13b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

M8022

1 0

After the instruction is executed once

b12 (16−n) to b15 are moved.

"n" bits The status of the bit "16−n" is copied.

FNC140-FNC149 Data Operation 2

High order Low order

b15b14b13b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 1 Carry flag M8022

1 0 1

b15 to b12 Before shift

The contents of b12 are stored.

Show 22 more labels / short text on this page
FNC40-FNC49 Data Operation · 16-bit Instruction · Mnemonic Operation Condition · 5 steps · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · and Type · Unit Index Con- stant · Real Number · Charac- ter String Pointer · Command · High order · Low order · FNC110-FNC139 Floating Point · Before execution · Carry flag · Leftward rotation · After execution · Before shift · b11 to b0 · FNC150-FNC159 Positioning Control
Page 298 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 298 · click to enlarge
Page 298

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.2 FNC 31 – ROL / Rotation Left

2. 32-bit operation (DROL and DROLP) "n" bits out of 32 bits of [ +1, ] are rotated leftward.

D D

input FNC 31 DROLP n D ‚

  • The final bit is stored in the carry flag (M8022).
  • In a device with digit specification, K8 (32-bit instruction) is valid.
Mitsubishi Electronics MELSEC FX3S — D D diagram (page 298)
Fig. 215

b15b14b13b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

1 0

1 0

The status of the bit "32−n" is copied.

b15b14b13b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

1 0 1

1 0 1

Related device

→ For the carry flag use method, refer to Subsection 6.5.2.

M8022 Carry Turns ON when the bit shifted last from the highest position is "1".

Cautions

  • In the case of continuous operation type instructions (ROL and DROL) Note that shift and rotation are executed in every scan time (operation cycle).
  • When a device with digit specification is specified as Only K4 (16-bit instruction) or K8 (32-bit instruction) is valid (examples: K4Y010 or K8M0).
  • Note that the 32-bit value [n+1, n] is valid when D or R is specified as "n" in a 32-bit instruction. In the case of "DROL D100 R0", "n" is [R1, R0].

Command · Device Name Description

Page 299 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 299 · click to enlarge
Page 299

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.3 FNC 32 – RCR / Rotation Right with Carry 11

11.3 FNC 32 – RCR / Rotation Right with Carry

FNC30-FNC39 Rotation and Shift

Outline

This instruction shifts and rotates the bit information rightward by the specified number of bits together with the carry flag.

1. Instruction format

P FNC 32

Mnemonic Operation Condition 32-bit Instruction

RCR D

RCR

Continuous Operation Pulse (Single) Operation

9 steps Continuous Operation Pulse (Single) Operation

DRCR

RCRP

DRCRP

2. Set data

Operand Type Description Data Type

Word device number storing data to be rotated rightward 16- or 32-bit binary

n Number of bits to be rotated

[n ≤ 16 (16-bit instruction), n ≤ 32 (32-bit instruction)]*1 16- or 32-bit binary

*1. Do not set a negative value to the number of bits to be rotated.

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC70-FNC79 External FX I/O Device

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S S S 3

n 3

S: In 16-bit operations, K4Y{{{, K4M{{{ and K4S{{{ are valid.

In 32-bit operations, K8Y{{{, K8M{{{ and K8S{{{ are valid.

FNC80-FNC89 External FX Device

Explanation of function and operation

1. 16-bit operation (RCR and RCRP) "n" bits out of 16 bits of and 1 bit (carry flag M8022) are rotated rightward.

input FNC 32 RCRP n D ‚

FNC100-FNC109 Data Transfer 2

"n" bits (in the case of K4)

b15b14b13b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

1 0

When M8022 is ON

After the instruction is executed once

b3 (n−1) to b0 are moved.

b3 (n−1)

b2 (n−2) to b0 and the head bit indicating the carry flag ON/OFF status are moved.

The status of the final bit b3 (bit "n−1") is stored.

High order Low order b15b14b13b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

0 0 0 1 0

Before shift b3 Carry flag M8022

FNC140-FNC149 Data Operation 2

Before shift b2 to b0

Before shift b15 to b4

Before shift Carry flag M8022

The carry flag is intervened in the rotation loop. If M8022 has been set to ON or OFF before the rotation instruction, the carry flag is transferred to the destination.

Show 21 more labels / short text on this page
FNC40-FNC49 Data Operation · 16-bit Instruction · Mnemonic Operation Condition · 5 steps · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · D Command · High order · Low order · Carry flag M8022 · Before execution · FNC110-FNC139 Floating Point · "n" bits · Rightward rotation · After execution · FNC150-FNC159 Positioning Control
Page 300 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 300 · click to enlarge
Page 300

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.3 FNC 32 – RCR / Rotation Right with Carry

2. 32-bit operation (DRCR and DRCRP) "n" bits out of 32 bits of [ +1, ] and 1 bit (carry flag M8022) are rotated rightward.
Mitsubishi Electronics MELSEC FX3S — 11.3 FNC 32 – RCR / Rotation Right with Carry diagram (page 300)
Fig. 216 · 11.3 FNC 32 – RCR / Rotation Right with Carry

b15b14b13b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 1 0

1 0 1 0 0 0

b2 (n−2) to b0 and the head bit indicating the carry flag ON/OFF status are moved.

The status of the final bit b3 (bit "n−1") is stored.

Low order b15b14b13b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

0 1 0

0 1 0

Related device

→ For the carry flag use method, refer to Subsection 6.5.2.

M8022 Carry Turns ON when the bit shifted last from the lowest position is "1".

Cautions

  • In the case of continuous operation type instructions (RCR and DRCR) Note that shift and rotation are executed every scan time (operation cycle).
  • When a device with digit specification is specified as Only K4 (16-bit instruction) or K8 (32-bit instruction) is valid (examples: K4Y010 or K8M0).
  • Note that the 32-bit value [n+1, n] is valid when D or R is specified as "n" in a 32-bit instruction. In the case of "DRCR D100 R0", "n" is [R1, R0].

Device Name Description

Page 301 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 301 · click to enlarge
Page 301

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.4 FNC 33 – RCL / Rotation Left with Carry 11

11.4 FNC 33 – RCL / Rotation Left with Carry

FNC30-FNC39 Rotation and Shift

Outline

This instruction shifts and rotates the bit information leftward by the specified number of bits together with the carry flag.

1. Instruction format

P FNC 33

Mnemonic Operation Condition 32-bit Instruction

RCL D

RCL

Continuous Operation Pulse (Single) Operation

9 steps Continuous Operation Pulse (Single) Operation

DRCL

RCLP

DRCLP

2. Set data

Operand Type Description Data Type

Word device number storing data to be rotated leftward 16- or 32-bit binary

n Number of bits to be rotated

[n ≤ 16 (16-bit instruction), n ≤ 32 (32-bit instruction)]*1 16- or 32-bit binary

*1. Do not set a negative value to the number of bits to be rotated.

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FNC70-FNC79 External FX I/O Device

S S S 3

n 3

S: In 16-bit operations, K4Y{{{, K4M{{{ and K4S{{{ are valid.

In 32-bit operations, K8Y{{{, K8M{{{ and K8S{{{ are valid.

FNC80-FNC89 External FX Device

Explanation of function and operation

1. 16-bit operation (RCL and RCLP) "n" bits out of 16 bits of and 1 bit (carry flag M8022) are rotated leftward.

input FNC 33 RCLP n D ‚

FNC100-FNC109 Data Transfer 2

"n" bits (in the case of K4)

b15b14b13b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

b15 to b12 (16−n) are moved.

1 1 1 0 1 0

After the instruction is executed once

When M8022 is ON b15 to b13 (16−n+1) and the head bit indicating the carry flag ON/OFF status are moved.

High order Low order

b15b14b13b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

The status of the final bit b12 (bit "16−n") is stored.

1 0 1

FNC140-FNC149 Data Operation 2

Before shift b15 to b13 Before shift b11 to b0

Carry flag M8022 Before shift Carry flag M8022 Before shift b12

The carry flag is intervened in the rotation loop. If M8022 has been set to ON or OFF before the rotation instruction, the carry flag is transferred to the destination.

Show 21 more labels / short text on this page
FNC40-FNC49 Data Operation · 16-bit Instruction · Mnemonic Operation Condition · 5 steps · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · D Command · High order · Low order · Before execution · FNC110-FNC139 Floating Point · Carry flag · Leftward rotation · "n" bits · After execution · FNC150-FNC159 Positioning Control
Page 302 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 302 · click to enlarge
Page 302

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.4 FNC 33 – RCL / Rotation Left with Carry

2. 32-bit operation (DRCL and DRCLP) "n" bits out of 32 bits of [ +1, ] and 1 bit (carry flag M8022) are rotated leftward.
Mitsubishi Electronics MELSEC FX3S — 11.4 FNC 33 – RCL / Rotation Left with Carry diagram (page 302)
Fig. 217 · 11.4 FNC 33 – RCL / Rotation Left with Carry

b15b14b13b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 1 1 1 0 1 0

1 0

b31 to b29 (32−n+1) and the head bit indicating the carry flag ON/OFF status are moved.

Low order b15b14b13b12b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

The status of the final bit b28 (bit "32−n") is stored.

1 0 1

1 0 1

Related device

→ For the carry flag use method, refer to Subsection 6.5.2.

M8022 Carry Turns ON when the bit shifted last from the highest position is "1".

Cautions

  • In the case of continuous operation type instructions (RCL and DRCL) Note that shift and rotation are executed every scan time (operation cycle).
  • When a device with digit specification is specified as Only K4 (16-bit instruction) or K8 (32-bit instruction) is valid (examples: K4Y010 or K8M0).
  • Note that the 32-bit value [n+1, n] is valid when D or R is specified as "n" in a 32-bit instruction. In the case of "DRCL D100 R0", "n" is [R1, R0].

Device Name Description

Page 303 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Applicable devices
Page 303 · click to enlarge
Page 303

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.5 FNC 34 – SFTR / Bit Shift Right 11

11.5 FNC 34 – SFTR / Bit Shift Right

FNC30-FNC39 Rotation and Shift

Outline

This instruction shifts bit devices of the specified bit length rightward by the specified number of bits. After shift, the bit device is transferred by "n2" bits from the most significant bit.

1. Instruction format

P FNC 34

Mnemonic Operation Condition 32-bit Instruction

SFTR

Continuous Operation Pulse (Single) Operation

SFTR

SFTRP

2. Set data

Operand Type Description Data Type

Head bit device number to be stored to the shift data after rightward shift Bit

Head bit device number to be shifted rightward Bit

n1 Bit length of the shift data n2 ≤ n1 ≤ 1024 16-bit binary

n2 Number of bits to be shifted rightward n2 ≤ n1 ≤ 1024*1 16-bit binary

*1. Do not set a negative value to the number of bits to be shifted rightward.

3. Applicable devices

Bit Devices Word Devices Others

FNC70-FNC79 External FX I/O Device

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

FNC80-FNC89 External FX Device

n2 3 S2 3 3

S1: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs.

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 16 more labels / short text on this page
FNC40-FNC49 Data Operation · 16-bit Instruction · Mnemonic Operation Condition · − · 9 steps · − · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · and Type · Unit Index Con- stant · Real Number · Charac- ter String Pointer · n1 3 3 · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 304 of the Mitsubishi Electronics MELSEC FX3S user manual — S D
Page 304 · click to enlarge
Page 304

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.5 FNC 34 – SFTR / Bit Shift Right

Explanation of function and operation

1. 16-bit operation (SFTR and SFTRP) For "n1" bits (shift register length) starting from , "n2" bits are shifted rightward ([1] and [2] shown below). After shift, "n2" bits from are transferred to "n2" bits from +n1-n2 ([3] shown below).
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 304)
Fig. 218 · Explanation of function and operation

input FNC 34 SFTRP n1 n2 D ‚ S ‚

D ‚ D ‚ D ‚ D ‚ D ‚ D ‚ D ‚

+7 D ‚ +6 +5 +4 +3 D ‚ +1

+8 D ‚ +7 +6 +5 D ‚ +4 D ‚ +3 D ‚ +2 D ‚ +1 D ‚ D ‚

+2 to before shift (n2=3) S ‚ S ‚

+8 to +3 before shift (n2=3) D ‚ D ‚

Caution

Error

If the transfer source is equivalent to the shifted device in FX3U/FX3UC PLCs, an operation error occurs (error code: K6710). An operation error does not occur in FX3S/FX3G/FX3GC PLCs.

S D

Page 305 of the Mitsubishi Electronics MELSEC FX3S user manual — S ‚ D ‚
Page 305 · click to enlarge
Page 305

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.6 FNC 35 – SFTL / Bit Shift Left 11

11.6 FNC 35 – SFTL / Bit Shift Left

FNC30-FNC39 Rotation and Shift

Outline

This instruction shifts bit devices of the specified bit length leftward by the specified number of bits. After shift, the bit device is transferred by "n2" bits from the least significant bit.

1. Instruction format

P FNC 35

Mnemonic Operation Condition 32-bit Instruction

SFTL

SFTL

Continuous Operation Pulse (Single) Operation

SFTLP

2. Set data

Operand Type Description Data Type

Head bit device number to be stored to the shift data after leftward shift Bit

Head bit device number to be shifted leftward Bit

n1 Bit length of the shift data n2 ≤ n1 ≤ 1024 16-bit binary

n2 Number of bits to be shifted leftward n2 ≤ n1 ≤ 1024*1 16-bit binary

*1. Do not set a negative value to the number of bits to be shifted leftward.

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC70-FNC79 External FX I/O Device

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

FNC80-FNC89 External FX Device

n2 3 S2 3 3

S1: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (SFTL and SFTLP) For "n1" bits (shift register length) starting from , "n2" bits are shifted leftward ([1] and [2] shown below). After shift, "n2" bits from are transferred to "n2" bits from ([3] shown below).

FNC100-FNC109 Data Transfer 2

S D

input FNC 35 SFTLP n1 n2 D ‚ S ‚

n2 (in the case of "n2=3")

S ‚ S ‚ S ‚

n1 (in the case of "n1=9")

+5 D ‚ +4 +3 +8 D ‚ +7 +6

D ‚ D ‚ D ‚ D ‚ D ‚ D ‚ D ‚

FNC140-FNC149 Data Operation 2

[1] Overflow (data to

[2] "n2" bits are shifted rightward (n2=3).

D ‚ D ‚ D ‚ D ‚ D ‚ D ‚ D ‚

to +5 before shift (n2=3) D ‚

S ‚ D ‚

+2 to before shift (n2=3) S ‚

Show 25 more labels / short text on this page
FNC40-FNC49 Data Operation · 16-bit Instruction · Mnemonic Operation Condition · − · 9 steps · − · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · n1 3 3 · Command · FNC110-FNC139 Floating Point · +2 · +1 · Before execution · +2 +1 · [3] Copy · be deleted) · After execution · +8 · FNC150-FNC159 Positioning Control
Page 306 of the Mitsubishi Electronics MELSEC FX3S user manual — S D
Page 306 · click to enlarge
Page 306

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.6 FNC 35 – SFTL / Bit Shift Left

Caution

Error

If the transfer source is equivalent to the shifted device in FX3U/FX3UC PLCs, an operation error occurs (error code: K6710). An operation error does not occur in FX3S/FX3G/FX3GC PLCs.

S D

Program example (conditional stepping of 1-bit data)

By setting X000 to X007 to ON in turn, Y000 to Y007 are activated in turn. If the order is wrong, activation is disabled.

Mitsubishi Electronics MELSEC FX3S — S D diagram (page 306)
Fig. 219

Bit 1 of M0 is regarded as the head input, and 8-bit shift register is constructed by S0 to S7.

*1 By using a state relay (S), the state under operation can be monitored by the dynamic monitoring function of the state relay.

Even if X000 is set to ON, Y000 is not activated.

Page 307 of the Mitsubishi Electronics MELSEC FX3S user manual — 2. FX 3S /FX 3G /FX 3GC /FX 3U /FX 3UC PLCs
Page 307 · click to enlarge
Page 307

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.6 FNC 35 – SFTL / Bit Shift Left 11

Mitsubishi Electronics MELSEC FX3S — 11.6 FNC 35 – SFTL / Bit Shift Left 11 diagram (page 307)
Fig. 220 · 11.6 FNC 35 – SFTL / Bit Shift Left 11

11.6.1 Replacement of SFT instruction in F 1 and F 2 Series

SFT instruction in F1/F2 PLCs corresponds to SFTL (FNC 35) instruction in FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs as shown below:

1. F 1 /F 2 PLCs M100: Input data M101 to M117 (octal number): 15-step shift register

2. FX 3S /FX 3G /FX 3GC /FX 3U /FX 3UC PLCs

Shift registers M101 to M115 are reset at one time.

Page 308 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 308 · click to enlarge
Page 308

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.7 FNC 36 – WSFR / Word Shift Right

11.7 FNC 36 – WSFR / Word Shift Right

Outline

This instruction shifts word devices with "n1" data length rightward by "n2" words.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 308)
Fig. 221 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 308)
Fig. 222 · 2. Set data

Head device number to be stored to the shift data after rightward shift 16-bit binary

Head word device number storing data to be shifted rightward 16-bit binary

n1 Word data length of the shift data n2 ≤ n1 ≤ 512 16-bit binary

n2 Number of words to be shifted rightward n2 ≤ n1 ≤ 512*1 16-bit binary

*1. Do not set a negative value to the number of words to be shifted rightward.

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 308)
Fig. 223 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (WSFR and WSFRP) For "n1" word devices starting from , "n2" words are shifted rightward ([1] and [2] shown below). After shift, "n2" words starting from are shifted to "n2" words starting from [ +n1-n2] ([3] shown below).
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 308)
Fig. 224 · Explanation of function and operation

input FNC 36 WSFRP n1 n2 D ‚ S ‚

D ‚ +7 +6 +5 +4 +3 D ‚ +1

D ‚ D ‚ D ‚ D ‚ D ‚ D ‚ D ‚

+8 D ‚ +7 +6 +5 D ‚ +4 +3 +2 +1

D ‚ D ‚ D ‚ D ‚ D ‚ D ‚ D ‚

Page 309 of the Mitsubishi Electronics MELSEC FX3S user manual — 11.7 FNC 36 – WSFR / Word Shift Right 11
Page 309 · click to enlarge
Page 309

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.7 FNC 36 – WSFR / Word Shift Right 11

Mitsubishi Electronics MELSEC FX3S — 11.7 FNC 36 – WSFR / Word Shift Right 11 diagram (page 309)
Fig. 225 · 11.7 FNC 36 – WSFR / Word Shift Right 11

If the transfer source is equivalent to the shifted device , an operation error occurs (error code: K6710).

X000 FNC 36 WSFRP K1X000 K1Y000 K 4 K 2

Specify the same digit for devices with digit specification.

Make sure that the number of digits is equivalent (Kn).

Y017 Y016 Y015 Y014 Y013 Y012 Y011Y010 Y007 Y006 Y005 Y004 Y003 Y002 Y001 Y000

Page 310 of the Mitsubishi Electronics MELSEC FX3S user manual — S D
Page 310 · click to enlarge
Page 310

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.8 FNC 37 – WSFL / Word Shift Left

11.8 FNC 37 – WSFL / Word Shift Left

Outline

This instruction shifts the word data information leftward by the specified number of words.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 310)
Fig. 226 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 310)
Fig. 227 · 2. Set data

Head device number to be stored to the shift data after leftward shift 16-bit binary

Head word device number storing data to be shifted leftward 16-bit binary

n1 Word data length of the shift data n2 ≤ n1 ≤ 512 16-bit binary

n2 Number of words to be shifted leftward n2 ≤ n1 ≤ 512*1 16-bit binary

*1. Do not set a negative value to the number of words to be shifted leftward.

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 310)
Fig. 228 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (WSFL and WSFLP) For "n1" word devices starting from , "n2" words are shifted leftward ([1] and [2] shown below). After shift, "n2" words starting from are shifted to "n2" words starting from ([3] shown below).

S D

input FNC 37 WSFLP n1 n2 D ‚ S ‚

Command

Page 311 of the Mitsubishi Electronics MELSEC FX3S user manual — 11.8 FNC 37 – WSFL / Word Shift Left 11
Page 311 · click to enlarge
Page 311

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.8 FNC 37 – WSFL / Word Shift Left 11

Mitsubishi Electronics MELSEC FX3S — 11.8 FNC 37 – WSFL / Word Shift Left 11 diagram (page 311)
Fig. 229 · 11.8 FNC 37 – WSFL / Word Shift Left 11

D ‚ D ‚ D ‚ D ‚ D ‚ D ‚ D ‚

D ‚ D ‚ D ‚ D ‚ D ‚ D ‚ D ‚

If the transfer source is equivalent to the shifted device , an operation error occurs (error code: K6710).

X000 FNC 37 WSFLP K1X000 K1Y000 K 4 K 2

Specify the same digit for devices with digit specification.

Make sure that the number of digits is equivalent (Kn).

Y017 Y016Y015 Y014 Y013 Y012 Y011 Y010 Y007 Y006 Y005 Y004 Y003 Y002 Y001Y000

Page 312 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Applicable devices
Page 312 · click to enlarge
Page 312

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.9 FNC 38 – SFWR / Shift Write [FIFO/FILO Control]

11.9 FNC 38 – SFWR / Shift Write [FIFO/FILO Control]

Outline

This instruction writes data for first-in first-out (FIFO) and last-in first-out (LIFO) control.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 312)
Fig. 230 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 312)
Fig. 231 · 2. Set data

Word device number storing data to be put in first 16-bit binary

Head word device number storing data (The first word device works as the pointer, and

data is stored in +1 and later) 16-bit binary

n Number of store points plus "1"*1 2 n 512 16-bit binary

*1. "+1" is required for the pointer.

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 312)
Fig. 232 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Page 313 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 313 · click to enlarge
Page 313

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.9 FNC 38 – SFWR / Shift Write [FIFO/FILO Control] 11

Explanation of function and operation

FNC30-FNC39 Rotation and Shift

1. 16-bit operation (SFWR and SFWRP) The contents of are written to "n-1" devices from +1, and "1" is added to the number of data stored in . For example, when = 0, the contents of are written to +1. When = 1, the contents of are written to +2.

S D

D S D D S

input FNC 38 SFWRP D ‚ S ‚

D ‚ D+n ... D+2 D+10 D+9 D+8 D+7 D+6 D+5 D+4 D+3 D+1

Executed at the 1st time ( = 0) D ‚

(K1) (K0)

D ‚ D+n ... D+2 D+10 D+9 D+8 D+7 D+6 D+5 D+4 D+3 S ‚

Executed at the 2nd time

D ‚ D ‚

(K2) (K1)

D ‚ D+n ... S ‚ D+10 D+9 D+8 D+7 D+6 D+5 D+4 D+3 S ‚

FNC70-FNC79 External FX I/O Device

1. When X000 turns from OFF to ON, the contents of are stored to +1. So the contents of +1 become equivalent to .

S D D

2. When the contents of are changed and then the command input is set from OFF to ON again, the new contents of are stored to +2. So the contents of +2 become equivalent to . (When the continuous operation type SFWR instruction is used, the contents are stored in each operation cycle. Use the pulse operation type SFWRP instruction in programming.)

S D D S

FNC80-FNC89 External FX Device

3. Data is stored from the right end in the same way, and the number of stored data is specified by the contents of the pointer .

Related device

→ For the carry flag use method, refer to Subsection 6.5.2.

FNC100-FNC109 Data Transfer 2

M8022 Carry When the contents of the pointer exceeds "n-1", no operation is executed (so data is not written) and the carry flag M8022 turns ON.

Related instructions

SFRD (FNC 39) Shift read (for FIFO control)

POP (FNC212) Shift last data read (for FILO control)

Caution

1. In the case of continuous operation type (SFWR) instruction Note that data is stored (overwritten) in each scan time (operation cycle).

FNC140-FNC149 Data Operation 2

Show 16 more labels / short text on this page
FNC40-FNC49 Data Operation · Command · n · n S ‚ · Before execution · FNC50-FNC59 High-Speed Processing · Pointer · FMC60-FNC69 Handy Instruction · Pointer · After execution · +1 → · Pointer · Device Name Description · FNC110-FNC139 Floating Point · Instruction Description · FNC150-FNC159 Positioning Control
Page 314 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 314 · click to enlarge
Page 314

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.9 FNC 38 – SFWR / Shift Write [FIFO/FILO Control]

Program example

1. Example of first-in first-out control → For a program example of FILO, refer to Section 27.3. In the example below, the shift write (SFWR) and shift read (SFRD) instructions are used.
1. Contents of operation - In this circuit example, a product number to be taken out now is output according to "first-in first-out" rule while products which were put into a warehouse with their product numbers registered are taken out of the warehouse. - The product number is hexadecimal, and up to 4 digits. Up to 99 products can be stored in the warehouse.
2. Program
Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 314)
Fig. 233 · Program example

Button for request to put a product into warehouse

The product number is input from X000 to X017, and transferred to D256.

Pointer D257Data register for storing the product number D258 to D356 (99 points)

Button for request to take a product out of warehouse

The product number of a product put into first is output to D357 in response to the request to put a product out of the warehouse.

The product number to be taken out is output to Y000 to Y017 in a four-digit hexadecimal number.

Page 315 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 D S 1
Page 315 · click to enlarge
Page 315

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.10 FNC 39 – SFRD / Shift Read [FIFO Control] 11

11.10 FNC 39 – SFRD / Shift Read [FIFO Control]

FNC30-FNC39 Rotation and Shift

Outline

This instruction reads data for first-in first-out control.

1. Instruction format

P FNC 39

Mnemonic Operation Condition 32-bit Instruction

SFRD

SFRD

Continuous Operation Pulse (Single) Operation

SFRDP

2. Set data

Operand Type Description Data Type

Head word device number storing data

S S

(The first word device works as the pointer, and data is stored in +1 and later.) 16-bit binary

Word device number storing data taken out first 2 ≤ n ≤ 512 16-bit binary

n Number of store points plus "1"*1 2 ≤ n ≤ 512 16-bit binary

*1. "+1" is required for the pointer.

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC70-FNC79 External FX I/O Device

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

FNC80-FNC89 External FX Device

Explanation of function and operation

1. 16-bit operation (SFRD and SFRDP) +1 written in turn by SFWR (FNC 38) instruction is transferred (read) to , and "n-1" words from +1 are shifted rightward by 1 word. "1" is subtracted from the number of data, stored in .

S 1 D S 1

FNC100-FNC109 Data Transfer 2

input FNC 39 SFRDP D ‚ S ‚

FNC140-FNC149 Data Operation 2

Show 18 more labels / short text on this page
FNC40-FNC49 Data Operation · 16-bit Instruction · Mnemonic Operation Condition · − · 7 steps · − · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · n 3 3 · Command · n · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 316 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 316 · click to enlarge
Page 316

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

11 Rotation and Shift Operation – FNC 30 to FNC 39

11.10 FNC 39 – SFRD / Shift Read [FIFO Control]

Mitsubishi Electronics MELSEC FX3S — 11.10 FNC 39 – SFRD / Shift Read [FIFO Control] diagram (page 316)
Fig. 234 · 11.10 FNC 39 – SFRD / Shift Read [FIFO Control]

S ‚ S+n ... S+2 S+10 S+9 S+8 S+7 S+6 S+5 S+4 S+3 S+1

S ‚ S+n ... S+2 S+10 S+9 S+8 S+7 S+6 S+5 S+4 S+3 S+n

S ‚ S+n ... S+10 S+9 S+8 S+7 S+6 S+5 S+4 S+3 S+n S+n

1. When the command input turns ON, the contents of +1 are transferred (read) to .
2. Accompanied by this transfer, the contents of the pointer decrease, and the data on the left side are shifted rightward by 1 word. (When the continuous operation type SFRD instruction is used, the contents are stored in turn in each operation cycle. Use the pulse operation type SFRDP instruction in programming.)

Related device

→ For the zero flag use method, refer to Subsection 6.5.2.

M8020 Zero Data is always read from +1. When the contents of the pointer become "0", the zero flag M8020 turns ON.

S S

Related instructions

SFWR (FNC 38) Shift write (for FIFO/FILO control)

POP (FNC212) Shift last data read (for FILO control)

Caution

1. Data after reading was executed The contents of +n do not change by reading.
2. In the case of continuous operation type (SFRD) instruction Data is read in turn in each scan time (operation cycle), but the contents of +n do not change.
3. When pointer is 0 Data is not processed, and the contents of do not change.

Program example

Refer to the program example provided for SFWR (FNC 38) instruction.

→ For the program example, refer to Section 11.9.

Device Name Description · Instruction Description

Page 317 of the Mitsubishi Electronics MELSEC FX3S user manual — 12. Data Operation – FNC 40 to FNC 49
Page 317 · click to enlarge
Page 317

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

Mitsubishi Electronics MELSEC FX3S — 12. Data Operation – FNC 40 to FNC 49 diagram (page 317)
Fig. 235 · 12. Data Operation – FNC 40 to FNC 49

12. Data Operation – FNC 40 to FNC 49

FNC 40 to FNC 49 provide instructions for executing complicated processing for fundamental applied instructions FNC 10 to FNC 39 and for executing special processing.

Page 318 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 D 1 D 1 D 2
Page 318 · click to enlarge
Page 318

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.1 FNC 40 – ZRST / Zone Reset

12.1 FNC 40 – ZRST / Zone Reset

Outline

This instruction resets devices located in a zone between two specified devices at one time. Use this instruction for restarting operation from the beginning after pause or after resetting control data.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 318)
Fig. 236 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 318)
Fig. 237 · 2. Set data

S1 ‚ D1 S1 ‚ D1 D2

Head bit or word device number to be reset at one time ≤ Specify same type of devices.

Last bit or word device number to be reset at one time 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 318)
Fig. 238 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (ZRST and ZRSTP)

Same type of devices from to are reset at one time.

D 1 D 1 D 1 D 2

When and are bit devices

D 1 D 1 D 1 D 2

Mitsubishi Electronics MELSEC FX3S — D 1 D 1 D 1 D 2 diagram (page 318)
Fig. 239
1. "OFF (reset)" is written to the entire range from to at one time.

ZRST Devices through are reset at one time. D2 ‚ D1 ‚ D2 ‚ D1 ‚

… +2 +9 +8 +7 +6 +5 +4 +3 +1 D1 ‚ D2 ‚ D1 ‚ D1 ‚ D1 ‚ D1 ‚ D1 ‚ D1 ‚ D1 ‚ D1 ‚ D1 ‚

OFF OFF … OFF

Page 319 of the Mitsubishi Electronics MELSEC FX3S user manual — ZRST C180 C230
Page 319 · click to enlarge
Page 319

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.1 FNC 40 – ZRST / Zone Reset 11

When and are word devices

D 1 D 1 D 1 D 2

FNC30-FNC39 Rotation and Shift

"K0" is written to the entire range from to at one time.

D 1 D 1 D 1 D 2

ZRST Devices through are reset at one time. D2 ‚ D1 ‚ D2 ‚ D1 ‚

… +2 +9 +8 +7 +6 +5 +4 +3 +1 D1 ‚ D2 ‚ D1 ‚ D1 ‚ D1 ‚ D1 ‚ D1 ‚ D1 ‚ D1 ‚ D1 ‚ D1 ‚

K0

K0 K0 … K0

Related instructions

1. RST instruction As an independent reset instruction for devices, RST instruction can be used for bit devices (Y, M and S) and word devices (T, C, D and R).

M0 is reset.

M0 RST

The current value of T0 is reset.

FNC70-FNC79 External FX I/O Device

T0 RST

D0 RST

D0 is reset.

2. FMOV (FNC 16) instruction FMOV (FNC 16) instruction is provided to write a constant (example: K0) at one time. By using this instruction, "0" can be written to word devices (KnY, KnM, KnS, T, C, D and R) at one time.

FNC80-FNC89 External FX Device

K0 K0 is written to D0 to D99 at one time. FNC 16

FMOV D0 K100

FNC100-FNC109 Data Transfer 2

Cautions

1. Caution on specifying devices

Specify same type of devices in and . The device number of should be smaller than or equal to the

D1 D1 D1 D2 D1 D1

device number of .

D 1 D 2

D1 D1 D1 D2 D1 D1

If the device number of is larger than the device number of , only one device specified in is reset.

2. When specifying high-speed counters (C235 to C255)

The ZRST instruction is handled as the 16-bit type, but 32-bit counters can be specified in and .

D 1 D 1 D 1 D 2

However, it is not possible to specify a 16-bit counter in and specify a 32-bit counter in ; and should be the same type.

D1 D1 D1 D2 D1 D1 D1 D2

FNC140-FNC149 Data Operation 2

ZRST C180 C230

ZRST C180 C199

ZRST C200 C230

Show 17 more labels / short text on this page
Command · input · FNC40-FNC49 Data Operation · Before execution · Executed · After execution · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · Example · Command · Command · input FNC 40 · input FNC 40 · 16-bit counter · 32-bit counter · FNC150-FNC159 Positioning Control
Page 320 of the Mitsubishi Electronics MELSEC FX3S user manual — M0
Page 320 · click to enlarge
Page 320

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.1 FNC 40 – ZRST / Zone Reset

3. Caution for simultaneous instances of the ZRST instruction and the PLS instruction The ZRST instruction resets the last stage for the PLS instruction and PLF instruction of the applicable device. In addition, the reset state of T and C is also reset.

M0

M100 M0

ZRST

M0 PLS

M0

Please program in the following way to turn on M0 only once.

M0

M100 M0 FNC 40

ZRST

M0

Show 14 more labels / short text on this page
Circuit program · Timing chart · one operation · one operation · cycle · cycle · ZRST instruction · PLS instruction · execution · execution · execution PLS instruction · ZRST instruction · execution · Circuit program
Page 321 of the Mitsubishi Electronics MELSEC FX3S user manual — ZRST C235 C255
Page 321 · click to enlarge
Page 321

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.1 FNC 40 – ZRST / Zone Reset 11

4. Caution on simultaneous instances of the ZRST instruction and a counter The ZRST instruction resets also the last stage and reset state of T and C coils. Accordingly, if the drive contact of X000 is ON in the following program, the counter executes counting after the ZRST instruction is executed.

FNC30-FNC39 Rotation and Shift

M0

C100 C0 FNC 40

ZRST

M0 RST

K10

ON

ON

OFF

OFF ON

M0

OFF

Current value of C0

Counting is executed when X000 is ON. OUT instruction

FNC70-FNC79 External FX I/O Device

Program in the following way to disable counting after execution of the ZRST instruction:

M0

FNC80-FNC89 External FX Device

C100 C0 FNC 40

ZRST

M0 RST

K10

FNC100-FNC109 Data Transfer 2

Program example

1. When using devices in the latch area as non-latch type devices In the program shown below, when the power to the PLC is turned ON or when the PLC mode is changed to RUN, the specified ranges of bit devices and word devices are reset at one time.

D 1 D 2

M8002 FNC 40

ZRST M500 M599 Initial pulse

M500 to M599 are reset at one time.

FNC140-FNC149 Data Operation 2

D 1 D 2

C235 to C255 are reset at one time. ("0" is written to them, and their contacts are reset.)

ZRST C235 C255

D 1 D 2

ZRST S500 S599

S500 to S599 are reset at one time.

Show 19 more labels / short text on this page
Circuit program · FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · Timing chart · cycle one operation · cycle one operation · cycle one operation · one operation · cycle · FMC60-FNC69 Handy Instruction · execution OUT instruction · ZRST instruction · OUT instruction · execution · execution · execution · Circuit program · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 322 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 S D 1 D
Page 322 · click to enlarge
Page 322

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.2 FNC 41 – DECO / Decode

12.2 FNC 41 – DECO / Decode

Outline

This instruction converts numeric data into ON bit. A bit number which is set to ON by this instruction indicates a numeric value.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 322)
Fig. 240 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 322)
Fig. 241 · 2. Set data

Data to be decoded or word device number storing data 16-bit binary

Bit or word device number storing the decoding result 16-bit binary

n Number of bits of device storing the decoding result (n = 1 to 8) (No processing is executed in the case of "n = 0".) 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 322)
Fig. 242 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (DECO and DECOP) One bit among to +2 n − 1 is set to ON according to the value.

D1 D D1 D D1 S

1. When is a bit device (1 ≤ n ≤ 8) The numeric value (expressed in 2 n , 1 ≤ n ≤ 8) of a device specified by is decoded to .

D 1 D

D 1 S D 1 D

-When all bits of are "0", the bit device turns ON. -When "n" is "8", 28 points (= 256 bits which is the maximum value) are occupied.

D 1 S D 1 D

Mitsubishi Electronics MELSEC FX3S — D 1 S D 1 D diagram (page 322)
Fig. 243

When it is Y, M or S (1 ≤ n ≤ 8)

M63 Up to M127 Up to M255 … … …

When is M0 1 0

M255 M0 M1 M2 M3 M4 M5 M6 M7 M8 M9 M10 M11 M12 M13 M14 M15

Up to 256 bits (The number of occupied bits varies depending on the specified "n" value.)

Page 323 of the Mitsubishi Electronics MELSEC FX3S user manual — 12.2 FNC 41 – DECO / Decode
Page 323 · click to enlarge
Page 323

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

Mitsubishi Electronics MELSEC FX3S — 12.2 FNC 41 – DECO / Decode diagram (page 323)
Fig. 244 · 12.2 FNC 41 – DECO / Decode
2. When is a word device (1 ≤ n ≤ 4)

The numeric value (expressed in 2n on the low-order side) of is decoded to .

-When all bits of are "0", b0 of the word device turns ON.

-In the case of "n ≤ 3", all of high-order bits of become "0" (turn OFF).

b0 b1 b2 b3 b4 b5 b6 b7 b8 b9 b10 b11 b12 b13 b14 b15

1 0 1 0 0 1

0 1

b0 b1 b2 b3 b4 b5 b6 b7 b8 b9 b10 b11 b12 b13 b14 b15

  • While the command input is OFF, the instruction is not executed. The activated decode output is held in the previous ON/OFF status.
  • When "n" is "0", the instruction executes no processing.
Page 324 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 D
Page 324 · click to enlarge
Page 324

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.2 FNC 41 – DECO / Decode

Program example

1. When setting bit devices to ON according to the value of a data register The value of D0 (whose current value is "14" in this example) is decoded to M0 to M15.
Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 324)
Fig. 245 · Program example

0 1 1 1 0 b0 1 2 3 4 5 6 7

When the value of b0 to b3 of D0 is "14"

M63 Up to M127 Up to M255 … … …

0 1 0

M255 M0 M1 M2 M3 M4 M5 M6 M7 M8 M9 M 10 M 11 M 12 M 13 M 14 M 15

Up to 256 bits (The number of occupied bits varies depending on the specified "n" value.)

  • When the value of b0 to b3 of D0 is "14 (= 0 + 2 + 4 + 8)", M14 (which is the 15th from M0) becomes "1" (turn ON).
  • When the value of D0 is "0", M0 becomes "1" (turns ON).
  • When "n" is set to "K4", either one point among M0 to M15 turns ON according to the value of D0 (0 to 15).
  • By changing "n" from K1 to K8, D0 can correspond to numeric values from 0 to 255.

However, because the device range of is occupied for decoding accordingly, such device range should not be used for another control.

D 1 D

2. Turning ON the bit out of word devices according to the contents of bit devices The value expressed by X000 to X002 is decoded to D0 (X000 and X001 are ON, and X002 is OFF in this example.).
Mitsubishi Electronics MELSEC FX3S — D 1 D diagram (page 324)
Fig. 246

0 0 0 1 0

b0 b1 b2 b3 b4 b5 b6 b7 b8 b9 b10 b11 b12 b13 b14 b15

  • When the values expressed by X000 to X002 are "3 (= 1 + 2 + 0)", b3 (which is the 4th from b0) becomes 1 (turns ON).
  • When all of X000 to X002 are "0" (OFF), b0 becomes "1" (turns ON).
Page 325 of the Mitsubishi Electronics MELSEC FX3S user manual — S ‚ = M10
Page 325 · click to enlarge
Page 325

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.3 FNC 42 – ENCO / Encode 11

12.3 FNC 42 – ENCO / Encode

FNC30-FNC39 Rotation and Shift

Outline

This instruction obtains positions in which bits are ON in data.

1. Instruction format

P FNC 42

Mnemonic Operation Condition 16-bit Instruction

ENCO − −

Continuous Operation Pulse (Single) Operation

ENCOP

2. Set data

Operand type Description Data type

S 1 ‚ S

Data to be encoded or word device number storing data 16-bit binary

Word device number storing the encoding result 16-bit binary

n Number of bits of device storing the encoding result (n = 1 to 8) (When "n" is "0", no processing is executed.) 16-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FNC70-FNC79 External FX I/O Device

S 1 ‚ S

3 S1 S2 3 3 3

3 3 3 S1 S2 3 3 3

S 2 ‚ D

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

FNC80-FNC89 External FX Device

Explanation of function and operation

1. 16-bit operation (ENCO and ENCOP)

The 2n bit of is encoded, and the result value is stored to . This instruction converts data into binary data according to a bit position in the ON status.

D 1 S D 1 D

1. When is a bit device (1 ≤ n ≤ 8)

D 1 S

FNC100-FNC109 Data Transfer 2

ON bit positions among "2n" bits (1 ≤ n ≤ 8) from are encoded to .

D 1 S D 1 D

-When "n" is "8", 28 = 256 bits (which is the maximum value) are occupied.

-The encoding result of is "0" (OFF) from the most significant bit to the low-order bit "n".

D 1 D

When it is Y, M or S

ENCO n S ‚ D ‚

(1 ≤ n ≤ 8)

M17 M16 M15 M14 M13 M12 M11 M10 When "n" is 3

7 0 1 0 1 2 (3) 4 5 6

S ‚ = M10

FNC140-FNC149 Data Operation 2

1 1 0 b15 D10 (1) (2) 4

All of them are "0".

Show 17 more labels / short text on this page
FNC40-FNC49 Data Operation · Mnemonic Operation Condition · 32-bit Instruction · 7 steps ENCO · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · n 3 3 · Command · FNC110-FNC139 Floating Point · input FNC 42 · FNC150-FNC159 Positioning Control · b0
Page 326 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 S
Page 326 · click to enlarge
Page 326

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.3 FNC 42 – ENCO / Encode

2. When is a word device (1 ≤ n ≤ 4)

D 1 S

ON bit positions among "2n" bits (1 ≤ n ≤ 4) from a device specified in are encoded to .

D 1 S D 1 D

Mitsubishi Electronics MELSEC FX3S — D 1 S D 1 D diagram (page 326)
Fig. 247

-The encoding result of is "0" (OFF) from the most significant bit to the low-order bit "n".

When it is T, C, D, R, U \G , V or Z

0 0 0 1 0 1 0 1 0 1 0 1 0 b15

0 1 2 (3) 4 5 6 7 Ignored

1 1 0 b15 (1) (2) 4

Cautions

1. When two or more bits are ON in the data The low-order side is ignored, and only the ON position on the high-order side is encoded.

D 1 S

2. While the command input is OFF The instruction is not executed. Activated encode outputs are latched in the previous ON/OFF status.
Page 327 of the Mitsubishi Electronics MELSEC FX3S user manual — K9
Page 327 · click to enlarge
Page 327

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.4 FNC 43 – SUM / Sum of Active Bits 11

12.4 FNC 43 – SUM / Sum of Active Bits

FNC30-FNC39 Rotation and Shift

Outline

This instruction counts the number of "1" (ON) bits in the data of a specified device.

1. Instruction format

Mnemonic Operation Condition P FNC 43

SUM D

Continuous Operation Pulse (Single) Operation

9 steps Continuous Operation Pulse (Single) Operation

DSUM

SUMP

DSUMP

2. Set data

Operand type Description Data type

S 1 ‚ S

Word device number storing the source data 16- or 32-bit binary

Word device number storing the result data 16- or 32-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S 1 ‚ S

3 S1 S2 3

FNC70-FNC79 External FX I/O Device

S 2 ‚ D

3 S1 S2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

FNC80-FNC89 External FX Device

1. 16-bit operation (SUM and SUMP)

The number of bits in the ON status in is counted, and stored to .

D 1 S D 1 D

  • When all bits are OFF in , the zero flag M8020 turns ON.

D 1 S

SUM S ‚ D ‚

Number of bits in the ON status in → S ‚ D ‚

FNC100-FNC109 Data Transfer 2

b0 b1 b2 b3 b4 b5 b6 b7 b8 b9 b10 b11 b12 b13 b14 b15

K21847

0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 1

1 2 3 ← 4 ← 5 ← 6 ← 7 ← 8 ← 9 (Number of "1" (ON))

K0

0

b0 b1 b2 b3 b4 b5 b6 b7 b8 b9 b10 b11 b12 b13 b14 b15

K21847

0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 1

32 16 8 4 2 1

K9

1 0 0 1 0

FNC140-FNC149 Data Operation 2

Show 20 more labels / short text on this page
FNC40-FNC49 Data Operation · Mnemonic Operation Condition · 16-bit Instruction · 32-bit Instruction · 5 steps SUM · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input FNC 43 · Word data · 16-bit data · Before execution · FNC110-FNC139 Floating Point · After execution · FNC150-FNC159 Positioning Control
Page 328 of the Mitsubishi Electronics MELSEC FX3S user manual — OFF
Page 328 · click to enlarge
Page 328

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.4 FNC 43 – SUM / Sum of Active Bits

2. 32-bit operation (DSUM and DSUMP)

The number of bits in the ON status in [ +1, ] is counted, and stored to .

D1 S D1 S D1 D

  • The number of bits in the ON status are stored in , and K0 is stored in +1.

D 1 D D 1 D

  • When all bits are OFF in [ +1, ], the zero flag M8020 turns ON.

D 1 S D 1 S

D ‚ Number of bits in the ON status in D ‚ +1,

DSUM S ‚ D ‚

[ +1, ] S ‚ S ‚

32-bit data K0 is written

b16 b17 b31 … b0 b1 b2 b3 b4 b5 b6 b7 b8 b9 b10 b11 b12 b13 b14 b15

K21847

0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 1 0

1 2 3 ← 4 ← 5 ← 6 ← 7 ← 8 ← 9 (Number of "1" (ON))

K0

K0

0

b16 b17 b31 … b0 b1 b2 b3 b4 b5 b6 b7 b8 b9 b10 b11 b12 b13 b14 b15

K21847

0

0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 1

32 16 8 4 2 1

K0

K9

1 0 0 1 0

1 0 0 1 0

3. Operation result according to the value (in 16-bit operation)

D 1 D D 1 S

M8020

flag) Bit device Word device

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 Decimal Hexadecimal

0000 0 ON

0 1 1 0001 1 OFF

0 1 0 2 0002 1 OFF

0 1 1 3 0003 2 OFF

0 1 0 0 4 0004 1 OFF

0 1 0 1 5 0005 2 OFF

0 1 1 0 6 0006 2 OFF

0 1 1 1 7 0007 3 OFF

0 1 0 0 0 8 0008 1 OFF

0 1 0 0 1 9 0009 2 OFF

0 1 0 1 0 10 000A 2 OFF

0 1 0 1 1 11 000B 3 OFF

OFF

1 0 1 1 −5 FFFB 15 OFF

1 0 0 −4 FFFC 14 OFF

1 0 1 −3 FFFD 15 OFF

1 0 −2 FFFE 15 OFF

1 −1 FFFF 16 OFF

Show 11 more labels / short text on this page
Command · input FNC 43 · → · Word data · Before execution · After execution · (zero · … · … · … · …
Page 329 of the Mitsubishi Electronics MELSEC FX3S user manual — 12.4 FNC 43 – SUM / Sum of Active Bits 11
Page 329 · click to enlarge
Page 329

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.4 FNC 43 – SUM / Sum of Active Bits 11

Mitsubishi Electronics MELSEC FX3S — 12.4 FNC 43 – SUM / Sum of Active Bits 11 diagram (page 329)
Fig. 248 · 12.4 FNC 43 – SUM / Sum of Active Bits 11

While the command input is OFF, the instruction is not executed. The output of the number of bits in the ON status is latched in the previous status.

When X000 is ON, the number of bits in the ON status in D0 is counted, and stored to D2.

The number of "1" in D0 is stored to D2. FNC 43

0

0

0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 1

0 1 0 0 1

Page 330 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 D D 1 D
Page 330 · click to enlarge
Page 330

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.5 FNC 44 – BON / Check Specified Bit Status

12.5 FNC 44 – BON / Check Specified Bit Status

Outline

This instruction checks whether a specified bit position in a specified device is ON or OFF.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 330)
Fig. 249 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 330)
Fig. 250 · 2. Set data

Word device number storing the source data 16- or 32-bit binary

n Bit position to be checked [n: 0 to 15 (16-bit instruction), 0 to 31 (32-bit instruction)] 16- or 32-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 330)
Fig. 251 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S2 S3

S1: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S3: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (BON and BONP)

The status (ON or OFF) of the bit "n" in is output to .

D 1 S D 1 D

[When the bit "n" is ON, is set to ON. When the bit "n" is OFF, is set to OFF.]

D 1 D D 1 D

  • When a constant (K) is specified as the transfer source , it is automatically converted into binary format.
Mitsubishi Electronics MELSEC FX3S — D 1 D D 1 D diagram (page 330)
Fig. 252

BON S ‚ D ‚ n S ‚ = ON/OFF status of bit "n" D ‚

b0 b1 b2 b3 b4 b5 b6 b7 b8 b9 b10 b11 b12 b13 b14 b15

0 1 0 0 1 0 1 0 1 0 0 0

K4 K5 K6 K7 K0 K1 K2 K3 K8 K9 K10 K11 K12 K13 K14 K15 D ‚

Page 331 of the Mitsubishi Electronics MELSEC FX3S user manual — M 0 = OFF
Page 331 · click to enlarge
Page 331

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.5 FNC 44 – BON / Check Specified Bit Status 11

2. 32-bit operation (DBON and DBONP)

FNC30-FNC39 Rotation and Shift

The status (ON or OFF) of the bit "n" in [ +1, ] is output to .

D1 S D1 S D1 D

[When the bit "n" is ON, is set to ON. When the bit "n" is OFF, is set to OFF.]

D 1 D D 1 D

  • When a constant (K) is specified as the transfer source [ +1, ], it is automatically converted into binary format.

D 1 S D 1 S

DBON S ‚ D ‚ n

S ‚ = ON/OFF status of bit "n" D ‚ S ‚

(n = K0 to K31)

S ‚ +1, S ‚

b16 b17 … b29 b30 b31

b0 b1 b2 b3 b4 b5 b6 b7 b8 b9 b10 b11 b12 b13 b14 b15

0 1 … 1 1 1

0 1 0 0 1 0 1 0 1 0 0 0

… K29 K30 K16 K17 K31

K4 K5 K6 K7 K0 K1 K2 K3 K8 K9 K10 K11 K12 K13 K14 K15

(OFF)

(ON)

Caution

  • Note that the 32-bit value [n+1, n] is valid when D or R is specified as "n" in a 32-bit instruction. In the case of "DBON D0 M0 R0", "n" is [R1, R0].

Program example

FNC70-FNC79 External FX I/O Device

When the bit 9 (n = 9) in D10 is "1" (ON), M0 is set to "1" (ON).

S ‚ D ‚ n

BON D 10 M 0 K 9

FNC80-FNC89 External FX Device

0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1

M 0 = ON

0 1 0 1 0 1 0 1 0 1 0 0

M 0 = OFF

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 17 more labels / short text on this page
Command · FNC40-FNC49 Data Operation · input FNC 44 · [ +1, ] · FNC50-FNC59 High-Speed Processing · ← n · bit device · n = 5 · n = 29 · FMC60-FNC69 Handy Instruction · b0 b15 · b7 b8 · n = 9 · b0 b15 · n = 9 · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 332 of the Mitsubishi Electronics MELSEC FX3S user manual — 2. 32-bit operation (DMEAN and DMEANP)
Page 332 · click to enlarge
Page 332

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.6 FNC 45 – MEAN / Mean

12.6 FNC 45 – MEAN / Mean

Outline

This instruction obtains the mean value of data.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 332)
Fig. 253 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 332)
Fig. 254 · 2. Set data

Head word device number storing data to be averaged 16- or 32-bit binary

Word device number storing the mean value result 16- or 32-bit binary

n Number of data to be averaged (n = 1 to 64) 16- or 32-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 332)
Fig. 255 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (MEAN and MEANP)

The mean value of "n" 16-bit data from is stored to .

D 1 S D 1 D

  • The sum is obtained as algebraic sum, and divided by "n".
  • The remainder is ignored.

S ‚ S ‚ S ‚ + + 1 + ……… + + n − 1

MEAN n S ‚ D ‚ n

2. 32-bit operation (DMEAN and DMEANP)

The mean value of "n" 32-bit data from [ +1, ] is stored to [ +1, ].

D1 S D1 S D1 D D1 D

  • The sum is obtained as algebraic sum, and divided by "n".
  • The remainder is ignored.
Mitsubishi Electronics MELSEC FX3S — 2. 32-bit operation (DMEAN and DMEANP) diagram (page 332)
Fig. 256 · 2. 32-bit operation (DMEAN and DMEANP)

[ + 1, ] + [ + 3, + 2] + ……… + [{ + n × 2 − 1}, { + n × 2 − 2}]

S ‚ S ‚ S ‚ S ‚ S ‚ S ‚

Command · input FNC 45

Page 333 of the Mitsubishi Electronics MELSEC FX3S user manual — 12.6 FNC 45 – MEAN / Mean
Page 333 · click to enlarge
Page 333

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

Mitsubishi Electronics MELSEC FX3S — 12.6 FNC 45 – MEAN / Mean diagram (page 333)
Fig. 257 · 12.6 FNC 45 – MEAN / Mean
  • When a device number is exceeded, "n" is handled as a smaller value in the possible range.
  • Note that the 32-bit value [n+1, n] is valid when D or R is specified as "n" in a 32-bit instruction. In the case of "DMEAN D0 D100 R0", "n" is [R1, R0].

When "n" is any value outside the range from "1" to "64", an operation error (M8067) is caused.

The data of D0, D1 and D2 are summed, divided by "3", and then stored to D10.

(D 0) + (D 1) + (D 2) FNC 45

Page 334 of the Mitsubishi Electronics MELSEC FX3S user manual — Related devices
Page 334 · click to enlarge
Page 334

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.7 FNC 46 – ANS / Timed Annunciator Set

12.7 FNC 46 – ANS / Timed Annunciator Set

Outline

This instruction sets a state relay as an annunciator (S900 to S999).

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

ANS −

2. Set data

Mitsubishi Electronics MELSEC FX3S — ANS − diagram (page 334)
Fig. 258

m Evaluation time data [m = 1 to 32767 (unit: 100 ms)] 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 334)
Fig. 259 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S 1T0 to T199 S 2 : S900 to S999

Explanation of function and operation

1. 16-bit operation

When the command input remains ON for equivalent to or longer than the evaluation time [m × 100 ms, timer ],

D 1 S

is set. When the command input remains ON for less than the evaluation time [m × 100 ms] and then turns OFF, the current

D 1 D

value of the timer for evaluation is reset and is not set. When the command input turns OFF, the timer for evaluation is reset.

D 1 S D 1 D

Mitsubishi Electronics MELSEC FX3S — D 1 S D 1 D diagram (page 334)
Fig. 260

Equivalent to or longer than evaluation time (m × 100 ms)

Related devices

Mitsubishi Electronics MELSEC FX3S — Related devices diagram (page 334)
Fig. 261 · Related devices

M8049 Enable annunciator When M8049 is set to ON, M8048 and D8049 are valid.

M8048 Annunciator ON When M8049 is ON and one of the state relays S900 to S999 is ON, M8048 turns ON.

D8049 Smallest state relay number in ON status Among S900 to S999, the smallest state relay number in the ON status is stored.

Show 4 more labels / short text on this page
Mnemonic Operation Condition · 32-bit Instruction · 7 steps ANS · Continuous Operation
Page 335 of the Mitsubishi Electronics MELSEC FX3S user manual — END
Page 335 · click to enlarge
Page 335

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.7 FNC 46 – ANS / Timed Annunciator Set 11

Program example

FNC30-FNC39 Rotation and Shift

1. Displaying a fault number using an annunciator When the program for external fault diagnosis shown below is created and the content of D8049 (smallest state relay number in the ON status) is monitored, the smallest state relay number in the ON status from S900 to S999 is displayed. If two or more faults are present at the same time, the next smallest fault number is displayed after the fault of the smallest fault number is cleared.

M8000

M8049

When M8049 turns ON, monitoring becomes valid.

Y005

X000 FNC 46

If the forward end detection input X000 does not turn ON within 1 second after the forward movement output Y005 is driven, S900 turns ON.

T 0 K 10 S900

If both the upper limit input X001 and the lower limit input X002 are OFF for 2 seconds or more due to a dog error, S901 turns ON.

T 1 K 20 S901

ANS

The switch X004 is set to ON in one operation cycle of the machine. If the switch X004 is not set to ON while the continuous operation mode input X003 is ON in the machine whose tact time is less than 10 seconds, S902 turns ON.

T 2 K100 S902

ANS

Y005 X005

M8048

FNC70-FNC79 External FX I/O Device

When one among S900 to S999 turns ON, M8048 turns ON and the fault display output Y006 turns ON.

Y006

A state relay which was set to ON by the external fault diagnosis program is set to OFF by the reset button X007. Every time X007 is set to ON, an operation state relay in the ON status with the smallest device number is reset (set to OFF) in turn.

ANRP

FNC80-FNC89 External FX Device

END

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 19 more labels / short text on this page
FNC40-FNC49 Data Operation · RUN monitor · ANS Forward · FNC50-FNC59 High-Speed Processing · Forward movement · end · Upper · Lower · limit · limit · FMC60-FNC69 Handy Instruction · Continuous · Cycle · Forward movement · Annunciator ON · Fault display · Reset · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 336 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 336 · click to enlarge
Page 336

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.8 FNC 47 – ANR / Annunciator Reset

12.8 FNC 47 – ANR / Annunciator Reset

Outline

This instruction resets an annunciator (S900 to S999) in the ON status with the smallest number.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 336)
Fig. 262 · 1. Instruction format

2. Set data

Operand type Description Data type

⎯ There is no set data. ⎯

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 336)
Fig. 263 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 16-bit operation (ANR and ANRP) When the command input turns ON, a state relay working as annunciator (S900 to S999) in the ON status is reset.
  • If two or more state relays are ON, the state relay with the smallest number is reset. When the command input is set to ON again, the state relay with the next smallest number is reset among state relays working as annunciators (S900 to S999) in the ON status.

ANRP

Related devices

Mitsubishi Electronics MELSEC FX3S — ANRP diagram (page 336)
Fig. 264

M8049 Enable annunciator When M8049 is set to ON, M8048 and D8049 are valid.

M8048 Annunciator ON When M8049 is ON and either one among the state relays S900 to S999 is ON, M8048 turns ON.

D8049 Minimum state relay number in ON status Among S900 to S999, the minimum number in the ON status is stored.

Caution

1. Execution in each operation cycle

  • When ANR instruction is used, annunciators in the ON status are reset in turn in each operation cycle.
  • When ANRP instruction is used, an annunciator in the ON status is reset only in one operation cycle (only once).

Program example

Refer to ANS (FNC 46) instruction.

→ For a program example, refer to Section 12.7.

Command · input FNC 47

Page 337 of the Mitsubishi Electronics MELSEC FX3S user manual — S ‚ D ‚
Page 337 · click to enlarge
Page 337

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.9 FNC 48 – SQR / Square Root 11

12.9 FNC 48 – SQR / Square Root

FNC30-FNC39 Rotation and Shift

Outline

This instruction obtains the square root. The ESQR (FNC127) instruction obtains the square root in floating point operation.

→ For ESQR (FNC127) instruction, refer to Section 18.15.

1. Instruction format

Mnemonic Operation Condition P FNC 48

SQR D

Continuous Operation Pulse (Single) Operation

9 steps Continuous Operation Pulse (Single) Operation

DSQR

SQRP

DSQRP

2. Set data

Operand type Description Data type

Word device number storing data whose square root is obtained 16- or 32-bit binary

S 1 ‚ S

Data register number storing the square root operation result 16- or 32-bit binary

D 1 S

: K0 to K32767 in 16-bit operation, K0 to K2,147,483,647 in 32-bit operation

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FNC70-FNC79 External FX I/O Device

S 1 ‚ S

3

3

Explanation of function and operation

FNC80-FNC89 External FX Device

1. 16-bit operation (SQR and SQRP)

The square root of the data stored in is calculated, and stored to .

D 1 S D 1 D

SQR S ‚ D ‚ S ‚ D ‚

2. 32-bit operation (DSQR and DSQRP)

FNC100-FNC109 Data Transfer 2

The square root of the data stored in [ +1, ] is calculated, and stored to [ +1, ].

D1 S D1 S D1 D D1 D Command

DSQR S ‚ D ‚ S ‚ D ‚ S ‚ → + 1, D ‚

Caution

1. Operation result

1. The obtained square root is an integer because the decimal point is ignored. When the calculated value is ignored, M8021 (borrow flag) turns ON.
2. When the calculated value is true "0", M8020 (zero flag) turns ON.

FNC140-FNC149 Data Operation 2

Program example

The square root of D10 is stored to D12. The value of D10 is "100".

S ‚ D ‚

D 10 → D 12 FNC 48

SQR D 10 D 12

100 → 10 =

Show 17 more labels / short text on this page
FNC40-FNC49 Data Operation · 16-bit Instruction · Mnemonic Operation Condition · 32-bit Instruction · 5 steps SQR · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · and Type · Unit Index Con- stant · Real Number · Charac- ter String Pointer · Command · input · input · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 338 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 338 · click to enlarge
Page 338

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.10 FNC 49 – FLT / Conversion to Floating Point

12.10 FNC 49 – FLT / Conversion to Floating Point

Outline

This instruction converts a binary integer into a binary floating point (real number).

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 338)
Fig. 265 · 1. Instruction format

2. Set data

Operand type Description Data type

S 1 ‚ S

Data register number storing binary integer 16- or 32-bit binary

Data register number storing binary floating point (real number) Real number (binary)

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 338)
Fig. 266 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (FLT and FLTP)

The binary integer data of is converted into binary floating point (real number), and stored to [ +1, ].

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 338)
Fig. 267 · Explanation of function and operation

D1 S D1 D D1 D

2. 32-bit operation (DFLT and DFLTP)

The binary integer data of [ +1, ] is converted into binary floating point (real number), and stored to

D 1 S D 1 S

Mitsubishi Electronics MELSEC FX3S — D 1 S D 1 S diagram (page 338)
Fig. 268

DFLT S ‚ D ‚ ( + 1, ) → ( +1, ) S ‚ S ‚ D ‚ D ‚

Related instruction

INT (FNC129) Inverse of the FLT instruction, converts binary floating point into binary integer.

Caution

1. It is not necessary to convert a constant (K or H) into a floating point value. The value of a K or H specified in each instruction for binary floating point (real number) operation is automatically converted into binary floating point (real number). It is not necessary to convert such a constant with the FLT instruction. (K and H cannot be specified in RAD, DEG, EXP and LOGE instructions.)

Instruction Description

Page 339 of the Mitsubishi Electronics MELSEC FX3S user manual — 12.10 FNC 49 – FLT / Conversion to Floating Point 11
Page 339 · click to enlarge
Page 339

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

12 Data Operation – FNC 40 to FNC 49

12.10 FNC 49 – FLT / Conversion to Floating Point 11

Mitsubishi Electronics MELSEC FX3S — 12.10 FNC 49 – FLT / Conversion to Floating Point 11 diagram (page 339)
Fig. 269 · 12.10 FNC 49 – FLT / Conversion to Floating Point 11
1. Arithmetic operations by binary floating point operations The sequence program shown below is constructed as follows:

(D0) ÷ (X017 to X010) 16-bit binary 2-digit BCD

(D0) → (D21, D20) BIN Binary floating point operation

(D22) → (D25, D24) BIN Binary floating point operation

DEDIV K345 K10 D26 (4) K345 ÷ K 10 → (D27, D26)

(D29, D28) × (D27, D26) → (D11, D10) Binary floating point multiplication

Page 340 of the Mitsubishi Electronics MELSEC FX3S user manual — 13. High-Speed Processing – FNC 50 to FNC 59
Page 340 · click to enlarge
Page 340

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13. High-Speed Processing – FNC 50 to FNC 59

FNC 50 to FNC 59 provide interrupt processing type high-speed instructions that execute sequence control using the latest I/O information and utilize the high-speed processing performance of the PLC.

Mitsubishi Electronics MELSEC FX3S — 13. High-Speed Processing – FNC 50 to FNC 59 diagram (page 340)
Fig. 270 · 13. High-Speed Processing – FNC 50 to FNC 59
Page 341 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 2
Page 341 · click to enlarge
Page 341

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.1 FNC 50 – REF / Refresh 11

13.1 FNC 50 – REF / Refresh

FNC30-FNC39 Rotation and Shift

Outline

This instruction immediately outputs the latest input (X) information or the current output (Y) operation result in the middle of a sequence program.

1. Instruction format

P FNC 50

Mnemonic Operation Condition 16-bit Instruction

REF − −

Continuous Operation Pulse (Single) Operation

REFP

2. Set data

Operand Type Description Data Type

Head bit device (X or Y) number to be refreshed Bit

n Number of bit devices to be refreshed 16-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

Unit Index Constant Real Number

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S 1 S 2

FNC70-FNC79 External FX I/O Device

n S3 S3

S1: X000, X010 or X020: Up to the final input number (whose least significant digit number is "0") S2: Y000, Y010 or Y020: Up to the final output number (whose least significant digit number is "0") S3: FX3S PLC: K8 (H8) or K16 (H10) FX3G/FX3GC PLCs: K8 (H8) or K16 (H10): Up to K128 (H80) (which is a multiple of 8) FX3U/FX3UC PLCs: K8 (H8) or K16 (H10): Up to K256 (H100) (which is a multiple of 8)

FNC80-FNC89 External FX Device

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 11 more labels / short text on this page
FNC40-FNC49 Data Operation · Mnemonic Operation Condition · 32-bit Instruction · 5 steps REF · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Charac- ter String Pointer · and Type · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 342 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 342 · click to enlarge
Page 342

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.1 FNC 50 – REF / Refresh

Explanation of function and operation

1. 16-bit operation (REF and REFP)

1. When refreshing outputs (Y)
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 342)
Fig. 271 · Explanation of function and operation

"n" points are refreshed from the output specified in . ("n" must be a multiple of 8.)

K8 (H8) or K16 (H10)Up to K256 (H100) (which is a multiple of 8)
Y000, Y010 or Y020Up to the final output number (whose least significant digit number is "0")

- When this instruction is executed, the output latch memory is refreshed to the output status in the specified range.

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 342)
Fig. 272 · Explanation of function and operation
2. When refreshing inputs (X)
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 342)
Fig. 273 · Explanation of function and operation

"n" points are refreshed from the input specified in . ("n" must be a multiple of 8.)

K8 (H8) or K16 (H10)Up to K256 (H100) (which is a multiple of 8)
X000, X010 or X020Up to the final input number (whose least significant digit number is "0")

- If the input information is turned ON approximately 10 ms (response delay time of the input filter) before the instruction is executed, the input image memory turns ON when the instruction is executed.

- In X000 to X017*1, the response delay time of the input filter can be changed.

*1. X000 to X007 in the FX3G/FX3GC.

→ For details, refer to "13.1.1 What should be understood before using the REF instruction".

Page 343 of the Mitsubishi Electronics MELSEC FX3S user manual — 13.1 FNC 50 – REF / Refresh
Page 343 · click to enlarge
Page 343

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

Mitsubishi Electronics MELSEC FX3S — 13.1 FNC 50 – REF / Refresh diagram (page 343)
Fig. 274 · 13.1 FNC 50 – REF / Refresh
1. Setting the number of refreshed points "n" Set a multiple of 8 such as "K8 (H8), K16 (H10) … K256 (H100)". Any other numeric value causes an error.
2. Setting the head device number Make sure that the least significant digit number is "0" such as "X000, X010, X020 … "or " Y000, Y010, Y020 … "
1. When refreshing inputs Only X010 to X017 (8 points in total) are refreshed.
2. When refreshing outputs Y000 to Y007, Y010 to Y017 and Y020 to Y027 (24 points in total) are refreshed.
Page 344 of the Mitsubishi Electronics MELSEC FX3S user manual — Target range: Y000 to highest connected output number
Page 344 · click to enlarge
Page 344

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.1 FNC 50 – REF / Refresh

13.1.1 What should be understood before using the REF instruction

1. Changing the input filter The input filter value is determined by the contents of D8020 (initial value: 10 ms). Use the MOV instruction, etc. to adjust the value in D8020, which represents the input filter value.

Target range: X000 to X017 (In inputs X020 and later, the input filter value is fixed at 10 ms and cannot be changed.) (The target range is X000 to X007 in the FX3G/FX3GC.)

2. Output response time After the REF instruction is executed, the output (Y) sets the output signal to ON after the response time shown below.

→ For details, refer to the respective PLC Hardware Edition manual.

Target range: Y000 to highest connected output number

1. Relay output type The output contact is activated after the response time of the output relay. - Y000 and higher: Approximately 10 ms
2. Transistor output type a) FX 3S PLC

- Y000 and Y001: 5 µs or less (load current = 10 mA or more, 5 to 24V DC) - Y002 and higher: 0.2 ms or less (load current = 200 mA, 24V DC) b) FX3G PLC (14-point and 24-point type)

- Y000 and Y001: 5 µs or less (load current = 10 mA or more, 5 to 24V DC) - Y002 and higher: 0.2 ms or less (load current = 200 mA, 24V DC) c) FX3G PLC (40-point and 60-point type)

- Y000, Y001 and Y002: 5 µs or less (load current = 10 mA or more, 5 to 24V DC) - Y003 and higher: 0.2 ms or less (load current = 200 mA, 24V DC) d) FX3GC PLC

- Y000 and Y001: 5 µs or less (load current = 10 mA or more, 5 to 24V DC) - Y002 and higher: 0.2 ms or less (load current = 100 mA, 24V DC) e) FX3U PLC

- Y000, Y001 and Y002: 5 µs or less (load current = 10 mA or more, 5 to 24V DC) - Y003 and higher: 0.2 ms or less (load current = 200 mA, 24V DC) f) FX3UC(D, DSS) PLCs - Y000, Y001 and Y002: 5 µs or less (load current = 10 mA or more, 5 to 24V DC) - Y003 and higher: 0.2 ms or less (load current = 100 mA, 24V DC) g) FX3UC -32MT-LT(-2) PLC

- Y000, Y001, Y002 and Y003: 5 µs or less (load current = 10 mA or more, 5 to 24V DC) - Y004 and higher: 0.2 ms or less (load current = 100 mA, 24V DC)

3. Triac output type - Y000 and higher: 1 ms or less (OFF → ON), 10 ms or less (ON → OFF).
3. When using the REF instruction between FOR and NEXT instructions or between a pointer (with a lower step number) and CJ instruction (with a higher step number) Inputs and outputs can be refreshed even when the input information or immediate output is required in the middle of a routine program during control.
4. When using the input interrupt (I) function When executing interrupt processing accompanied by I/O operations, I/O refresh can be executed in the interrupt routine to receive the latest input (X) information and give the immediate output (Y) of the operation result so that dispersion caused by the operation time is improved.
Page 345 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 345 · click to enlarge
Page 345

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.2 FNC 51 – REFF / Refresh and Filter Adjust 11

13.2 FNC 51 – REFF / Refresh and Filter Adjust

FNC30-FNC39 Rotation and Shift

Outline

The digital input filter time of the inputs X000 to X017 can be changed using this instruction or D8020. Using this instruction, the status of inputs X000 to X017 can be refreshed at an arbitrary step in the program for the specified input filter time, and then transferred to the image memory.

1. Instruction format

P FNC 51

Mnemonic Operation Condition 16-bit Instruction

REFF − −

Continuous Operation Pulse (Single) Operation

REFFP

2. Set data

Operand Type Description Data Type

n Digital input filter time [K0 to K60 (H0 to H3C) × 1 ms] 16-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

n 3 3 S S

FNC70-FNC79 External FX I/O Device

SK0 (H0) to K60 (H3C)

Explanation of function and operation

1. 16-bit operation (REFF and REFFP) 16 inputs from X000 to X017 in the image memory are refreshed at the digital input filter time [n × 1 ms].

FNC80-FNC89 External FX Device

K0 to K60 (Filter constant from 0 to 60 ms)

  • When the input turns ON "n × 1 ms" before the instruction is executed, the image memory is set to ON. When the input turns OFF "n × 1 ms" before the instruction is executed, the image memory is set to OFF.

FNC100-FNC109 Data Transfer 2

  • When the command input is ON, the REFF instruction is executed in each operation cycle.
  • When the command input is OFF, the REFF instruction is not executed, and the input filter of X000 to X017 uses the set value of D8020 (which is the value used during input processing).

FNC140-FNC149 Data Operation 2

Show 16 more labels / short text on this page
FNC40-FNC49 Data Operation · Mnemonic Operation Condition · 32-bit Instruction · 3 steps REFF · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input · REFF n · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 346 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 346 · click to enlarge
Page 346

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.2 FNC 51 – REFF / Refresh and Filter Adjust

Cautions

1. Setting the filter time "n" Set "n" within the range from K0 (H0) to K60 (H3C) [0 to 60 ms].
2. Function of the input filter A digital filter is built into the inputs X000 to X017. The filter time can be changed in 1 ms units within the range from 0 to 60 ms using applied instructions. When the filter time is set to "0", the input filter value is as follows.
Mitsubishi Electronics MELSEC FX3S — Cautions diagram (page 346)
Fig. 275 · Cautions

Input number Input filter value when set to "0"

*1. When setting the input filter time to "5 µs", perform the following actions: - Make sure that the wiring length is 5 m or less. - Connect a bleeder resistor of 1.5 kΩ (1 W or more) to the input terminal, and make sure that the load current in the open collector transistor output of the external equipment is 20 mA or more including the input current of the main unit.

*2. The filter time is fixed to 10 ms for X010 to X017 in 16-point type FX3U PLCs and 16-point type FX3UC PLCs.

Program example

1. Relationship between the program and the filter time

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 346)
Fig. 276 · Program example

When X010 is ON The image memory of X000 to X017 is refreshed with an input filter of 1 ms.

The image memory of X000 to X017 is refreshed with an input filter of 20 ms.

The image memory is refreshed with the input filter value set in D8020.

Page 347 of the Mitsubishi Electronics MELSEC FX3S user manual — 1. How to change the digital filter (executing END instruction) *1
Page 347 · click to enlarge
Page 347

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.2 FNC 51 – REFF / Refresh and Filter Adjust 11

13.2.1 What should be understood before using REFF instruction

FNC30-FNC39 Rotation and Shift

Generally, a C-R filter of approximately 10 ms is provided for inputs in PLCs as countermeasures against chattering and noise at the input contacts. A digital filter is provided for the inputs X000 to X017 in FX3U/FX3UC PLC. The digital filter value can be changed ranging from 0 to 60 ms using applied instructions.

1. How to change the digital filter (executing END instruction) *1

The input filter initial value (10 ms) for X000 to X017 is set in special data register D8020. By changing this value using the MOV instruction, etc., the input filter value for X000 to X017 which is used during execution of the END instruction can be changed.

When the command is ON

When the END instruction is executed

Digital filter Initial value10 ms

C-R filter Fixed to 10 ms

*1. This function is supported only in DC input type.

2. Instruction in which the digital filter is automatically changed Regardless of the change in the filter time executed by the REFF instruction, when the following functions and instruction are executed, the input filter value is automatically changed (to 5 µs in X000 to X005 and 50 µs in X006 and X007). However, if the digital filter is used in any other functions or instructions than the ones listed, the digital filter uses the time set in D8020. As a result, the program will not run correctly if the ON or OFF duration of the corresponding input signal is less than the input filter time.

FNC70-FNC79 External FX I/O Device

  • Input of interrupt pointer specified in the input interrupt function
  • Input used in a high-speed counter

FNC80-FNC89 External FX Device

  • Input used in the SPD (FNC 56) instruction

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 12 more labels / short text on this page
FNC40-FNC49 Data Operation · D8020 REFF instruction · FNC50-FNC59 High-Speed Processing · Input terminal · X000 to X017 · Input image · Input terminal · memory X020 and · FMC60-FNC69 Handy Instruction · later · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 348 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 348 · click to enlarge
Page 348

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.3 FNC 52 – MTR / Input Matrix

13.3 FNC 52 – MTR / Input Matrix

Outline

This instruction reads matrix input as 8-point input × "n"-point output (transistor) in the time division method.

1. Instruction format

Mnemonic Operation Condition 32-bit Instruction

MTR

Continuous Operation −

2. Set data

Operand Type Description Data Type

Input device (X) number of matrix signal input X000, X010, X020 … final input device number (Only "0" is allowed in the least significant digit of device numbers.)

Head device (Y) number of matrix signal output Y000, Y010, Y020 … final output device number (Only "0" is allowed in the least significant digit of device numbers.)

Head bit device (Y, M or S) number of ON output destination Y000, Y010, Y020 … final Y number, M000, M010, M020 … final M number or S000, S010, S020 … final S number (Only "0" is allowed in the least significant digit of device numbers.)

n Number of columns in matrix input (K2 to K8 or H2 to H8) 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 348)
Fig. 277 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 16-bit operation (MTR)

An input signal of 8 points × "n" columns is controlled in the time division method using 8 inputs and "n"

transistor outputs . Each column is read in turn, and then output to .

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 348)
Fig. 278 · Explanation of function and operation
  • For each output, the I/O processing is executed immediately in turn in interrupt at every 20 ms under consideration of the input filter response delay of 10 ms.
Show 6 more labels / short text on this page
Mnemonic Operation Condition · 16-bit Instruction · 9 steps MTR · Bit · Bit · Bit
Page 349 of the Mitsubishi Electronics MELSEC FX3S user manual — D 2 D 1
Page 349 · click to enlarge
Page 349

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.3 FNC 52 – MTR / Input Matrix 11

The figure below shows an example of the FX3U series main unit (sink input/sink output). For wiring details, refer to the Hardware Edition of each PLC.

FNC30-FNC39 Rotation and Shift

Diode 0.1A(50V) 2nd column

1st column input is received.

2nd column input is received.

S/S +1 +2 +3 +4 +5 +6 +7

S S S S S S S S

Input (X) [sink] Output (Y) [sink]

PLC

COM +1 +2 +3 +4 +5 +6 +7

D1 D1 D1 D1 D1 D1 D1 D1

are occupied.

FNC70-FNC79 External FX I/O Device

Related device

M8029 Instruction execution complete Turns ON after the first cycle operation.

Cautions

FNC80-FNC89 External FX Device

1. Number of occupied devices

1. Eight input points are occupied from the input device number specified in .
2. "n" output points are occupied from the output device number specified in .

When specifying the output in , make sure that "n" output numbers specified in does not overlap the

D 2 D 1

output specified in .

FNC100-FNC109 Data Transfer 2

2. Limitation in the number of instructions The MTR instruction can be used only once in a program.
3. Wiring One diode of 0.1 A/50 V is required for each switch.
4. Output format Use the transistor output format.
5. Cautions on writing during RUN Even if an operand device is changed by write during RUN while the MTR instruction is executed, the PLC operates using the device before change. The changed device is reflected after the command input is set to OFF once and set to ON again.

FNC140-FNC149 Data Operation 2

Show 23 more labels / short text on this page
+11 · +12 · +13 · +14 · +15 · +16 · Command contact · FNC40-FNC49 Data Operation · [1] · [5] · +1 · 1st column · +1 [2] · [4] · [6] · 20ms · M8029 (execution complete) · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · "n" points · Device Name Description · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 350 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 350 · click to enlarge
Page 350

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.3 FNC 52 – MTR / Input Matrix

Program example

n=Three outputs (Y020, Y021 and Y022) are set to ON in turn repeatedly. Every time an output is set to ON, eight inputs in the 1st, 2nd and 3rd columns are received in turn repeatedly, and stored to M30 to M37, M40 to M47 and M50 to M57 respectively. In this program example, the FX3U series main unit (sink input/sink output) is used. For wiring details, refer to the Hardware Edition of each PLC.

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 350)
Fig. 279 · Program example
Page 351 of the Mitsubishi Electronics MELSEC FX3S user manual — FX 3U -64MT/ES
Page 351 · click to enlarge
Page 351

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.3 FNC 52 – MTR / Input Matrix 11

13.3.1 Operation and cautions for the MTR instruction

FNC30-FNC39 Rotation and Shift

1. Command input

1. Setting the command input to normally Open For the MTR instruction, set the command input to normally Open.

M{{ (normally Open) FNC 52

MTR X020 Y040 M0 K8

2. Input numbers used in the MTR instruction

1. Inputs available in MTR instruction Use inputs X020 and later under normal conditions.
2. When using the inputs X000 to X017 *1

The receiving speed is higher. Because the output transistor recovery time is long and the input sensitivity is high, however, erroneous input pulses may be counted. To prevent erroneous input pulses, connect pull-up resistors (3.3 kΩ/0.5 W) to transistor outputs used in MTR instruction. For pull-up resistors, use the power supply shown in the table below.

Power supply used for pull-up resistors transistor output

AC power type PLC Service power supply

DC power type PLC Power supply for driving PLC

The figure below shows an example of the FX3U Series main unit (sink input/sink output).

FNC70-FNC79 External FX I/O Device

Refer to the previous page. 24V S/S

0V X000 X001 X002 X003 X004 X005 X006 X007

FX 3U -64MT/ES

FNC80-FNC89 External FX Device

COM5 Y020 Y021 Y022 Y023 Y024 Y025 Y026 Y027

3.3k /0.5W

FNC100-FNC109 Data Transfer 2

*1. X000 to X007 in the FX3G/FX3GC.

3. ON/OFF duration of input signals Because 64 input points (8 rows × 8 columns) are received in a cycle of 80 or 160 ms, the ON/OFF duration of each input signal should be greater than or equal to the value shown below:

When inputs X000 to X017*2 are used

When inputs X020*3 or later are used

FNC140-FNC149 Data Operation 2

80 ms 80 ms

160 ms 160 ms

*2. X000 to X007 in the FX3G/FX3GC.

*3. X010 and later in the FX3G/FX3GC.

Show 8 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Matrix circuit · Transistor output · Pull-up resistor · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 352 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 1
Page 352 · click to enlarge
Page 352

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.4 FNC 53 – HSCS / High-Speed Counter Set

13.4 FNC 53 – HSCS / High-Speed Counter Set

Outline

This instruction compares a value counted by a high-speed counter with a specified value, and immediately sets an external output (Y) if the two values are equivalent each other.

→ For the counter interrupt using HSCS instruction, refer to Section 36.6.

1. Instruction format

16-bit Instruction Mnemonic Operation Condition

Mnemonic Operation Condition 32-bit Instruction

HSCS D

13 steps DHSCS Continuous Operation

−

2. Set data

Mitsubishi Electronics MELSEC FX3S — − diagram (page 352)
Fig. 280

Data to be compared with the current data value of a high-speed counter or word device number. 32-bit binary

Device number of a high-speed counter [C235 to C255] 32-bit binary

Bit device number to be set to ON when the compared two values are equivalent to each other Bit

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 352)
Fig. 281 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S2 S3

S1: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S3: This function is supported only in FX3U/FX3UC PLCs. S4: When using the counter interrupt function in FX3U/FX3UC PLCs, specify an interrupt pointer.

→ For counter interrupt using HSCS instruction, refer to Section 36.6.

Explanation of function and operation

1. 32-bit operation (DHSCS)

When the current value of a high-speed counter (C235 to C255) specified in becomes the comparison value

[ +1, ] (for example, when the current value changes from "199" to "200" or from "201" to "200" if the

S 1 S 1

comparison value is K200), the bit device is set to ON regardless of the operation cycle. This instruction is executed after the counting processing in the high-speed counter.

Mitsubishi Electronics MELSEC FX3S — S 1 S 1 diagram (page 352)
Fig. 282

D ‚ S1 ‚ S2 ‚ D ‚ S2 ‚

Page 353 of the Mitsubishi Electronics MELSEC FX3S user manual — SET Y010 FNC229
Page 353 · click to enlarge
Page 353

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.4 FNC 53 – HSCS / High-Speed Counter Set 11

Operation When the current value of the high-speed counter C255 changes from "99" to "100" or from "101" to "100", Y010 is set to ON (output refresh).

FNC30-FNC39 Rotation and Shift

M8000

C255 K2,147,483,647

Set to ON.

FNC 53 DHSCS K100 C255 Y010 = K100 C255 Y010 →

Related instructions

The following instructions can be combined with high-speed counters:

Instruction FNC No. Instruction name

DHSCS FNC 53 High-speed counter set

DHSCR FNC 54 High-speed counter reset

DHSZ FNC 55 High-speed counter zone compare

DHCMOV FNC189 High-speed counter move

DHSCT FNC280 High-speed counter compare with data table

Cautions

1. Selection of the count comparison method

1) FX3U/FX3UC PLC When the HSCS instruction is used in FX3U/FX3UC PLCs, hardware counters (C235, C236, C237, C238, C239, C240, C244 (OP), C245 (OP), C246, C248 (OP), C251 and C253) are automatically switched to software counters, and the maximum frequency and total frequency of each counter are affected. Refer to the counting operation described below, and select according to the contents of control whether to use HSCS instruction or general-purpose comparison instruction. a) Case to select DHSCS instruction

FNC70-FNC79 External FX I/O Device

- When the output should be given when the counting result becomes equivalent to the comparison value regardless of the scan time of the PLC b) Cases to select a general-purpose comparison instruction

FNC80-FNC89 External FX Device

- When the frequency is beyond the counting performance of software counters (and below the counting performance of hardware counters) - When counting is regarded as important, but the effect of the scan time can be ignored in operations according to the counting result - When one instruction is executed in 33 or more positions at the same time

M8000 FNC189 DHCMOV C251 D100 K0

FNC100-FNC109 Data Transfer 2

SET Y010 FNC229

LDD<= K100 D100

REF Y010 K8

FNC140-FNC149 Data Operation 2

Show 11 more labels / short text on this page
RUN monitor · Comparison · Comparison · Output destination · value · source · FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 354 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 354 · click to enlarge
Page 354

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.4 FNC 53 – HSCS / High-Speed Counter Set

2. FX 3S /FX 3G /FX 3GC PLCs When the HSCS instruction is used in FX 3S /FX 3G /FX 3GC PLCs, the total frequency of each counter is affected. Refer to the counting operation described below, and select according to the contents of control whether to use the HSCS instruction or a general-purpose comparison instruction. a) Case to select the HSCS instruction

- When the output should be given if the counting result becomes equivalent to the comparison value regardless of the scan time of the PLC b) Cases to select a general-purpose comparison instruction

- When counting is regarded as important, but the effect of the scan time can be ignored in operations according to the counting result - When one instruction is executed in 7 or more positions at the same time

Mitsubishi Electronics MELSEC FX3S — 13.4 FNC 53 – HSCS / High-Speed Counter Set diagram (page 354)
Fig. 283 · 13.4 FNC 53 – HSCS / High-Speed Counter Set

2. Device specification range

Only high-speed counters (C235 to C255) can be specified as .

3. Only 32-bit operation instructions are available. Because instructions for high-speed counters are dedicated to 32 bits, make sure to input "DHSCS (FNC 53)".
4. Priority order in operation among HSCS (FNC 53), HSCR (FNC 54), and HSZ (FNC 55) instructions for the same high-speed counter

→ For details, refer to "6. Priority order in operations among HSCS (FNC 53), HSCR (FNC 54), and HSZ (FNC

55. instructions for the same high-speed counter" in Subsection 13.4.1.
5. Reset operation by an external terminal → For details, refer to "5. Reset operation by an external terminal" in Subsection 13.4.1.
6. For other cautions on using HSCS instruction, refer to the description later. → For details, refer to the next page.

Program example

With regard to the current value of a counter, different outputs (Y) are arbitrary set to ON by two values.

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 354)
Fig. 284 · Program example

FNC 53 DHSCS K100 C255 Y010 C255 = K100 → Y010 = ON

FNC 53 DHSCS K150 C255 Y011 C255 = K150 → Y011 = ON

0 … 99 100 101 … 149 150 151

Page 355 of the Mitsubishi Electronics MELSEC FX3S user manual — FNC 53 DHSCS K100 C255 Y000 M8000
Page 355 · click to enlarge
Page 355

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.4 FNC 53 – HSCS / High-Speed Counter Set 11

13.4.1 Common cautions on using instructions for high-speed counter

FNC30-FNC39 Rotation and Shift

DHSCS (FNC 53), DHSCR (FNC 54), DHSZ (FNC 55) and DHSCT (FNC280) instructions are provided for high-speed counters. This section explains common cautions for these instructions.

1. Limitation in the number of instances of each instruction in a program and number of instructions driven at the same time
1. FX 3U /FX 3UC PLCs DHSCS, DHSCR and DHSZ instructions can be used as many times as necessary in the same way as general instructions. However, the number of simultaneously driven instructions is limited. The DHSCT instruction can only be used once in any program.

Instruction Limitation in number of instructions driven at same time

DHSCS

32 instructions including DHSCT instruction DHSCR

DHSZ

DHSCT Only 1 (This instruction can only be used once.)

2. FX 3S /FX 3G /FX 3GC PLCs DHSCS, DHSCR and DHSZ instructions can be used as many times as necessary in the same way as general instructions. However, the number of simultaneously driven instructions is limited.

Instruction Limitation in number of instructions driven at same time

DHSCS

DHSZ

2. Response frequency of high-speed counters When the DHSZ or DHSCT instruction is used in FX 3U /FX 3UC PLCs, the maximum response frequency and total frequency of every software counter are limited. When the DHSCS, DHSCR or DHSZ instruction is used in FX 3S /FX 3G /FX 3GC PLCs, the total frequency of high-speed counters is limited.

FNC70-FNC79 External FX I/O Device

→ For the total frequency in FX3S/FX3G/FX3GC PLCs, refer to Subsection 4.7.7. → For the maximum response frequency and total frequency in FX3U/FX3UC PLCs, refer to Subsection 4.8.10.

FNC80-FNC89 External FX Device

3. Specification of output numbers (Y) (FX 3G /FX 3GC /FX 3U /FX 3UC PLCs) When using the same instruction for high-speed counter repeatedly or when driving two or more other instructions for high-speed counter at the same time, specify such output devices (Y) whose high-order two digits are the same (in units of 8 devices).
1. When using devices of the same number (in units of 8 devices) Example: When using Y000, specify Y000 to Y007. When using Y010, specify Y010 to Y017.

FNC100-FNC109 Data Transfer 2

2. When using two or more instructions for high-speed counter and non-consecutive output (Y) numbers A program example is shown below:

FNC 53 DHSCS K100 C255 Y000 M8000

FNC 53 DHSCS K100 C255 Y010

When C255 reaches K100, the output Y000 is driven by interrupt. Y010 is driven when END processing is executed. If interrupt drive is required, use an output number ranging from Y001 to Y007 whose high-order two digits are equivalent.

FNC140-FNC149 Data Operation 2

Show 6 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · 6 instructions DHSCR · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 356 of the Mitsubishi Electronics MELSEC FX3S user manual — C241 K9,999
Page 356 · click to enlarge
Page 356

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.4 FNC 53 – HSCS / High-Speed Counter Set

4. Caution on the counting operation when the current value is changed An instruction for the high-speed counter gives the comparison result when a pulse is input to the input (X) of the highspeed counter. However, the comparison result is not given when the current value of the high-speed counter is changed in the following method:
1. Change method (examples) a) Overwriting the contents of a word device used as the comparison value using DMOV instruction, etc. b) Resetting the current value of a high-speed counter in a program
2. Operation Even if the condition for setting the output to ON or OFF is given as the comparison result, the comparison result does not change when an instruction is simply driven.
5. Reset operation by an external terminal [M8025 *1 : HSC (external reset) mode] For a high-speed counter equipped with an external reset terminal (R) such as C241, an instruction is executed and the comparison result is output at the rising edge of the reset input signal. In FX 3S /FX 3G /FX 3GC PLCs, high-speed counters operate in the HSC (external reset) mode regardless of the status of M8025.
1. Program

If an instruction for the high-speed counter is used while M8025*1 is driven, the instruction is executed again when the current value of the high-speed counter C241 is cleared by an external reset terminal. And the comparison result is output even if a counting input is not given.

M8000

M8025 *1 External reset mode

External reset terminal for C241

C241 K9,999

FNC 54 DHSCR K0 C241 Y000

*1. M8025 is cleared when the PLC mode is changed from RUN to STOP. It is not necessary to drive M8025 in FX3S/FX3G/FX3GC PLCs.

2. Operation When the external reset input X001 turns ON while the current value of C241 is "100", for example, the current value of C241 is reset to "0". And Y000 is reset at this time even if a counting input is not given.

RUN monitor X001

Page 357 of the Mitsubishi Electronics MELSEC FX3S user manual — Y005
Page 357 · click to enlarge
Page 357

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.4 FNC 53 – HSCS / High-Speed Counter Set 11

6. Priority order in operations among HSCS (FNC 53), HSCR (FNC 54), and HSZ (FNC 55) instructions for the same high-speed counter

FNC30-FNC39 Rotation and Shift

1) FX3U/FX3UC PLCs When the same comparison value is used for the same high-speed counter in the HSCS, HSCR and HSZ instructions, reset (self-reset) of the comparison target high-speed counter for the HSCR instruction is executed with the highest priority (as shown in the table below). In this case, the comparison results do not change in HSCS, HSCR, and HSZ instructions whose comparison value is programmed to be the same as the comparison value for self-reset by HSCR instruction. To change the comparison results, set the comparison value to "K0". 2) FX3S/FX3G/FX3GC PLCs In FX3S/FX3G/FX3GC PLCs, the HSCS, HSCR and HSZ instructions are executed in the order of programming.

M8000

C235 K10000

FX 3S / FX 3G /FX 3GC /

FX 3U /FX 3UC

FX 1N /FX 1NC /

FX 1S

FX 2N /FX 2NC

FNC 53 DHSCS K500 C235 Y000

DHSCS (1) DHSCR (6) (self-reset) DHSCS (1) DHSCS (1)

FNC 53 DHSCS

DHSCS (2) DHSZ (4) DHSCS (2) DHSCS (2)

K500 C235 Y001

DHSCR (3) DHSCS (1) DHSCR (3) DHSCR (3)

DHSZ (4) DHSCS (2) DHSZ (4) (Not supported)

FNC 54 DHSCR

DHSCR (5) DHSCR (3) DHSCR (5) DHSCR (5)

K500 C235 Y002

DHSCR (6) (self-reset) DHSCR (5) DHSCR (6) (self-reset)

M8000

DHSZ K250 K500 C235

Y003

K250 K500 C235 FNC 11 DZCPP

FNC70-FNC79 External FX I/O Device

Y003

M8000

(5) FNC 54 DHSCR K500 C235

Y006

K500 C235 FNC 54 DHSCR

FNC80-FNC89 External FX Device

C235 (6)

Operation of FX3S/FX3G/FX3GC/ FX1S/FX1N/FX1NC/FX2N/FX2NC PLCs [reference]

Operation of FX 3U /FX 3UC PLCs

FNC100-FNC109 Data Transfer 2

Y000 to Y002 and Y006 do not change.*1

Y000,Y001

ON

Y003

ON ON

Y002

OFF

Present value:1

Y004

OFF

Y003

ON ON

OFF It does not change.*2

Y005

Y004

ON

*1. To change the comparison results by the instructions (1) to (3) and (5), change the comparison value "K500" in the instructions (1) to (3) and (5) to "K0". *2. To set Y005 to ON in the HSZ instruction (4), set a value smaller than the comparison value "K500". However, due to the response delay at the output, the output may not operate within the short time before the counter's present value is reset to "0".

Y005

Present value:1

FNC140-FNC149 Data Operation 2

*3. Due to the response delay at the output, the output may not operate within the short time before the counter's present value is reset to "0".

7. Timing at which the instruction is executed The comparison instruction for high-speed counter is executed at the END instruction for the scan in which the comparison instruction is driven. When the comparison value is changed, the changed comparison instruction also becomes effective at the END instruction for the scan in which the comparison instruction is driven.
Show 15 more labels / short text on this page
FNC40-FNC49 Data Operation · Processing sequence · Program sequence · FNC50-FNC59 High-Speed Processing · (1) · (2) · FMC60-FNC69 Handy Instruction · (3) · DHSCR (6) (self-reset) · Self-reset program · Present value · Present value · FNC110-FNC139 Floating Point · *3 · FNC150-FNC159 Positioning Control
Page 358 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 1
Page 358 · click to enlarge
Page 358

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.5 FNC 54 – HSCR / High-Speed Counter Reset

13.5 FNC 54 – HSCR / High-Speed Counter Reset

Outline

This instruction compares the value counted by a high-speed counter with a specified value at each count, and immediately resets an external output (Y) when both values become equivalent to each other.

1. Instruction format

16-bit Instruction Mnemonic Operation Condition

Mnemonic Operation Condition 32-bit Instruction

HSCR D

−

13 steps DHSCR Continuous Operation

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 358)
Fig. 285 · 2. Set data

Data to be compared with the current value of a high-speed counter or word device number storing the data to be compared 32-bit binary

Device number of a high-speed counter [C235 to C255] 32-bit binary

Bit device number to be reset (set to OFF) when both values become equivalent each other. Bit

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 358)
Fig. 286 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S3 S4 3

S1: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available.

S2: The same counter as can be specified also. (Refer to the program example shown later.) S3: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S4: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 32-bit operation (DHSCR)

When the current value of a high-speed counter (C235 to C255) specified in becomes the comparison value

[ +1, ] (for example, when the current value changes from "199" to "200" or from "201" to "200" if the

S 1 S 1

comparison value is K200), the bit device is reset (set to OFF) regardless of the operation cycle. In this instruction, the comparison processing is executed after the counting processing in the high-speed counter.

Mitsubishi Electronics MELSEC FX3S — S 1 S 1 diagram (page 358)
Fig. 287

Operation When the present value of the high-speed counter C255 changes (counts) from "99" to "100" or from "101" to "100", Y010 is reset (output refresh).

Mitsubishi Electronics MELSEC FX3S — S 1 S 1 diagram (page 358)
Fig. 288
Page 359 of the Mitsubishi Electronics MELSEC FX3S user manual — Y010 K8 FNC 50
Page 359 · click to enlarge
Page 359

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.5 FNC 54 – HSCR / High-Speed Counter Reset 11

Related instructions

FNC30-FNC39 Rotation and Shift

The following instructions can be combined with high-speed counters:

Instruction FNC No. Instruction name

DHSCS FNC 53 High-speed counter set

DHSCR FNC 54 High-speed counter reset

DHSZ FNC 55 High-speed counter zone compare

DHCMOV FNC189 High-speed counter move

DHSCT FNC280 High-speed counter compare with data table

Cautions

1. Selection of the count comparison method

1) FX3U/FX3UC PLCs When the HSCR instruction is used in FX3U/FX3UC PLCs, hardware counters (C235, C236, C237, C238, C239, C240, C244 (OP), C245 (OP), C246, C248 (OP), C251 and C253) are automatically switched to software counters, and the maximum frequency and total frequency of each counter are affected. Refer to the counting operation described below, and select according to the contents of control whether to use HSCR instruction or general-purpose comparison instruction. a) Case to select DHSCR instruction

- When the output should be given when the counting result becomes equivalent to the comparison value regardless of the scan time of the PLC b) Cases to select a general-purpose comparison instruction

- When the frequency is beyond the counting performance of software counters (and below the counting performance of hardware counters) - When counting is important, but the effect of the scan time can be ignored in operations depending on the counting result - When one instruction is executed in 33 or more positions at the same time

FNC70-FNC79 External FX I/O Device

M8000 FNC189 DHCMOV C251 D100 K0

RST Y010 FNC229

LDD<= K10000 D100

FNC80-FNC89 External FX Device

M8000 FNC 50

REF Y010 K8

2. FX 3S /FX 3G /FX 3GC PLCs When the HSCR instruction is used in FX 3S /FX 3G /FX 3GC PLCs, the total frequency of each counter is affected. Refer to the counting operation described below, and select according to the contents of control whether to use the HSCR instruction or a general-purpose comparison instruction. a) Case to select the HSCR instruction

FNC100-FNC109 Data Transfer 2

- When the output should be given if the counting result becomes equivalent to the comparison value regardless of the scan time of the PLC b) Cases to select a general-purpose comparison instruction

- When counting is regarded as important, but the effect of the scan time can be ignored in operations according to the counting result - When one instruction is executed in 7 or more positions at the same time

LDD<= K10000 C251 RST Y010

M8000

FNC140-FNC149 Data Operation 2

Y010 K8 FNC 50

REF

Show 5 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 360 of the Mitsubishi Electronics MELSEC FX3S user manual — M8000
Page 360 · click to enlarge
Page 360

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.5 FNC 54 – HSCR / High-Speed Counter Reset

2. Only 32-bit operation instructions are available. Because instructions for high-speed counters are dedicated to 32 bits, make sure to input "DHSCR (FNC 54)".
3. Priority order in operation among HSCS (FNC 53), HSCR (FNC 54), and HSZ (FNC 55) instructions for the same high-speed counter

→ For details, refer to "6. Priority order in operations among HSCS (FNC 53), HSCR (FNC 54), and HSZ (FNC

55. instructions for the same high-speed counter" in Subsection 13.4.1.
4. Reset operation by an external terminal → For details, refer to "5. Reset operation by an external terminal [M8025*1: HSC (external reset) mode]"

in Subsection 13.4.1.

5. Other cautions on using HSCR instruction → For details, refer Subsection 13.4.1.

Program example

1. Example of self-reset circuit When the current value of C255 becomes "400", C255 is immediately reset. Its current value becomes "0", and the output contact is set to OFF.

Reset value of DHSCR

M8000

C255 K300

FNC 54 DHSCR K400 C255 C255

Current value of C255

Output contact of C255

Show 7 more labels / short text on this page
400 Count-up value · RUN monitor · Comparison · Comparison · Output destination · value · source
Page 361 of the Mitsubishi Electronics MELSEC FX3S user manual — DHSZ
Page 361 · click to enlarge
Page 361

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.6 FNC 55 – HSZ / High-Speed Counter Zone Compare 11

13.6 FNC 55 – HSZ / High-Speed Counter Zone Compare

FNC30-FNC39 Rotation and Shift

Outline

This instruction compares the current value of a high-speed counter with two values (one zone), and outputs the comparison result to three bit devices (refresh).

→ For the table high-speed comparison mode, refer to Subsection 13.6.2.

→ For the frequency control mode, refer to Subsection 13.6.3.

1. Instruction format

16-bit Instruction Mnemonic Operation Condition

Mnemonic Operation Condition 32-bit Instruction

HSZ D

17 steps DHSZ Continuous Operation

−

2. Set data

Operand Type Description Data Type

Data to be compared with the current value of a high-speed counter or word device number storing data to be compared (comparison value 1) 32-bit binary

Data to be compared with the current value of a high-speed counter or word device number storing data to be compared (comparison value 2) 32-bit binary

Device number of a high-speed counter [C235 to C255] 32-bit binary

Head bit device number to which the comparison result is output based on upper and lower comparison values Bit

3. Applicable devices

FNC70-FNC79 External FX I/O Device

Bit Devices Word Devices Others

System User Digit Specification System User Special

Unit Index Constant Real Number

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S2 S3

FNC80-FNC89 External FX Device

3 S2 S3

S1: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S3: This function is supported only in FX3U/FX3UC PLCs.

FNC100-FNC109 Data Transfer 2

Explanation of function and operation

1. 32-bit operation (DHSZ)

The current value of a high-speed counter (C235 to C255) specified in is compared with two comparison points (comparison value 1 and comparison value 2). Based on the comparison result, "smaller than the lower comparison

value", "inside the comparison zone" or "larger than the upper comparison value", one among , +1 and

D D

+2 is set to ON regardless of the operation cycle. In this instruction, the comparison processing is executed after the count processing in the high-speed counter.

K2,147,483,647

FNC140-FNC149 Data Operation 2

Set to ON. Comparison

S 1 ‚ FNC 55

S1 ‚ D ‚ S2 ‚ S ‚ S ‚

DHSZ

S 1 ‚ S ‚

Show 24 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · and Type · Charac- ter String Pointer · FNC110-FNC139 Floating Point · Command · input · Comparison · Comparison · Output destination · value 1 · value 2 · source · > · → · ≤ ≤ · → · +1 · > · → · +2 · FNC150-FNC159 Positioning Control
Page 362 of the Mitsubishi Electronics MELSEC FX3S user manual — Related instructions
Page 362 · click to enlarge
Page 362

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.6 FNC 55 – HSZ / High-Speed Counter Zone Compare

Comparison points Make sure that the comparison value 1 and the comparison value 2 have the following relationship:

[ +1, ] ≤ [ +1, ]

S 1 S 1 S 2 S 2

Comparison point Contents (32 bits)

Comparison value 1 +1,

S 1 S 1

Comparison value 2 +1,

S 2 S 2

Operation When the current value of the high-speed counter C251 changes (counts) as shown below, the comparison result is output to one of the outputs Y000, Y001 or Y002.

Mitsubishi Electronics MELSEC FX3S — S 2 S 2 diagram (page 362)
Fig. 289

999 → 1000 ON → OFF OFF → ON OFF

999 ← 1000 OFF → ON ON → OFF OFF

999 → 1000 ON → OFF OFF → ON OFF

999 ← 1000 OFF → ON ON → OFF OFF

2000 → 2001 OFF ON → OFF OFF → ON

2000 ← 2001 OFF OFF → ON ON → OFF

2000 → 2001 OFF ON → OFF OFF → ON

2000 ← 2001 OFF OFF → ON ON → OFF

Related instructions

The following instructions can be combined with high-speed counters:

Mitsubishi Electronics MELSEC FX3S — Related instructions diagram (page 362)
Fig. 290 · Related instructions
Page 363 of the Mitsubishi Electronics MELSEC FX3S user manual — M8000
Page 363 · click to enlarge
Page 363

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.6 FNC 55 – HSZ / High-Speed Counter Zone Compare 11

Cautions

FNC30-FNC39 Rotation and Shift

1. Selection of the count comparison method

1) FX3U/FX3UC PLCs When the HSZ instruction is used in FX3U/FX3UC PLCs, hardware counters (C235, C236, C237, C238, C239, C240, C244 (OP), C245 (OP), C246, C248 (OP), C251 and C253) are automatically switched to software counters, and the maximum frequency and total frequency of each counter are affected. Refer to the counting operation described below, and select according to the contents of control whether to use the DHSZ instruction or general-purpose comparison instruction. a) Case to select the DHSZ instruction

- When the output should be given when the counting result becomes equivalent to the comparison value regardless of the scan time of the PLC b) Cases to select a general-purpose comparison instruction

- When the frequency is beyond the counting performance of software counters (and below the counting performance of hardware counters) - When counting is important, but the effect of the scan time can be ignored in operations depending on the counting result - When one instruction is executed in 33 or more positions at the same time

M8000 FNC189 DHCMOV C251 D100

K0

LDD > K10000 D100

Y010

LDD = K20000 D100

Y011

LDD < K20000 D100

FNC70-FNC79 External FX I/O Device

Y012

M8000 FNC 50

REF Y010 K8

2. FX 3S /FX 3G /FX 3GC PLCs When the HSZ instruction is used in FX 3S /FX 3G /FX 3GC PLCs, the total frequency of each counter is affected. Refer to the counting operation described below, and select according to the contents of control whether to use the HSZ instruction or a general-purpose comparison instruction. a) Case to select the HSZ instruction

FNC80-FNC89 External FX Device

- When the output should be given if the counting result becomes equivalent to the comparison value regardless of the scan time of the PLC b) Cases to select a general-purpose comparison instruction

FNC100-FNC109 Data Transfer 2

- When counting is regarded as important, but the effect of the scan time can be ignored in operations according to the counting result - When one instruction is executed in 7 or more positions at the same time

K10000

Y010

LDD>

FNC238 ANDD>=

K10000

K20000

Y011

LDD<=

K20000

Y012

LDD<

FNC140-FNC149 Data Operation 2

M8000

Y010 K8 FNC 50

REF

Show 5 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 364 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 2
Page 364 · click to enlarge
Page 364

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.6 FNC 55 – HSZ / High-Speed Counter Zone Compare

2. Device specification range

Only high-speed counters (C235 to C255) can be specified as .

3. Only 32-bit operation instructions are available. Because instructions for high-speed counters are dedicated to 32 bits, make sure to input "DHSZ (FNC 55)".
4. Caution on values set in the comparison value 1 and comparison value 2

S 1 S 2

Make sure that is smaller than or equivalent to .

S 1 S 2

5. Relationship between the comparison timing and the result output

1. The DHSZ instruction executes comparison and outputs the result only when a counting pulse is input to a highspeed counter.

(When is "1000" and is "1999", the output is set to ON as soon as the current value of C235 changes from "999" to "1000" or from "1999" to "2000".)

S 1 S 2 D

2. Because the comparison result cannot be obtained when restoring the power or when the PLC mode switches from STOP to RUN, the result is not output even if the comparison condition is provided.

→ For details, refer to "13.6.1. Program in which comparison result is set to ON when power is turned ON

[ZCP (FNC 11) instruction]".

6. Priority order in operation among HSCS (FNC 53), HSCR (FNC 54), and HSZ (FNC 55) instructions for the same high-speed counter

→ For details, refer to "6. Priority order in operations among HSCS (FNC 53), HSCR (FNC 54), and HSZ (FNC

55. instructions for the same high-speed counter" in Subsection 13.4.1.
7. Reset operation by an external terminal → For details, refer to "5. Reset operation by an external terminal [M8025*1: HSC (external reset) mode]"

in Subsection 13.4.1.

8. Number of occupied devices

1. The comparison value occupies two devices from or respectively.

S 1 S 2

2. The output occupies three devices from .

9. When an output (Y) is specified in (FX3G/FX3GC/FX3U/FX3UC) When Y 6 or Y 7 is specified as an output (Y), the refresh timing of the three outputs (Y) occupied by the DHSZ instruction is different for each output. To make the refresh timing of three points simultaneous, specify Y 0 to Y 5. Example: When Y006 is specified as an output (Y), the refresh timing is different between Y006, Y007 and Y010.

Page 365 of the Mitsubishi Electronics MELSEC FX3S user manual — DHSZ K1000 K1200 C235 Y010
Page 365 · click to enlarge
Page 365

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.6 FNC 55 – HSZ / High-Speed Counter Zone Compare 11

13.6.1 Program in which comparison result is set to ON when power is turned ON [ZCP (FNC 11) instruction]

FNC30-FNC39 Rotation and Shift

DHSZ instruction outputs the comparison result only when a counting pulse is input. Even if the current value of C235 is "0", Y010 remains OFF at the time of startup. For initializing Y010, compare the current value of C235 with K1000 and K1200 and drive Y010 by DZCPP instruction (for general zone comparison) as pulse operation only at the time of startup. Refer to the program example shown below.

Explanation of operation

The outputs Y010 to Y012 are as shown below:

Y010 = ON Y011 = ON Y012 = ON

1000 1200 Current value of C235 0

Program example

RST C235

ZRST Y010 Y012 Y010 to Y012 are reset.

C235 M8000

K9999 … pulse inputX000

FNC70-FNC79 External FX I/O Device

X010 FNC 11 DZCPP K1000 K1200 C235 Y010

Immediately after start, comparison is executed only once. K1000 > C235 :Y010 ON K1000 ≤ C235 ≤ K1200 :Y011 ON K1200 < C235 :Y012 ON

S1 ‚ D ‚ S2 ‚ S ‚

After start, comparison is executed when each pulse is input from X000. K1000 > C235 :Y010 ON K1000 ≤ C235 ≤ K1200 :Y011 ON K1200 < C235 :Y012 ON

DHSZ K1000 K1200 C235 Y010

FNC80-FNC89 External FX Device

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 7 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · RUN monitor · Start · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 366 of the Mitsubishi Electronics MELSEC FX3S user manual — Timing chart
Page 366 · click to enlarge
Page 366

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.6 FNC 55 – HSZ / High-Speed Counter Zone Compare

Timing chart

In the part [1] in the timing chart, Y010 remains OFF if the current value of a high-speed counter (C235 in the example below) is "0" when restoring the power.

1. For initializing Y010, the current value of C235 is compared with K1000 and K1200, and Y010 is driven using the DZCPP instruction (for general zone comparison) as pulse operation only upon startup.
2. The comparison result in Y010 is latched until an input pulse is input and the comparison output is driven by the DHSZ instruction.
3. According to the current value of the counter, the DHSZ instruction drives the output (A), (B) or (C).
Mitsubishi Electronics MELSEC FX3S — Timing chart diagram (page 366)
Fig. 291 · Timing chart
Page 367 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 2
Page 367 · click to enlarge
Page 367

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.6 FNC 55 – HSZ / High-Speed Counter Zone Compare 11

13.6.2 Table high-speed comparison mode (M8130)

FNC30-FNC39 Rotation and Shift

This section explains the table high-speed comparison mode (high-speed pattern output) of the DHSZ instruction. When two or more outputs should be activated at one time, use the HSCT instruction which can change up to 16 outputs.

1. Set data

Operand Type Description Data Type

Head word device number storing the data table (only data register D) 32-bit binary

Number of lines in the table (only K or H) … K1 to K128 or H1 to H80 32-bit binary

Device number of a high-speed counter [C235 to C255] 32-bit binary

M8130 (special auxiliary relay for declaring the table high-speed comparison mode) Bit

Explanation of function and operation

1. 32-bit operation (DHSZ)

When the special auxiliary relay M8130 for declaring the table high-speed comparison mode is specified as in the DHSZ instruction, the special function shown below is provided.

K2,147,483,647

FNC70-FNC79 External FX I/O Device

DHSZ M8130

S 1 S 2 S

Table high-speed comparison mode

Comparison table

FNC80-FNC89 External FX Device

Comparison data (32 bits) Output (Y) number SET/RST Table counter (D8130)

S 1 S 1 S 1 S 1

+ 1, + 2 + 3

S 1 S 1 S 1 S 1

+ 5, + 4 + 6 + 7

S 1 S 1 S 1 S 1

+ 9, + 8 + 10 + 11

FNC100-FNC109 Data Transfer 2

+ [ × 4 - 3], + [ × 4 - 4] + [ × 4 - 2] +[ × 4 - 1] − 1 ↓ Repeated from "0".

S1 S2 S1 S2 S1 S2 S1 S2 S2

1. Specify the head device number for the comparison table as .

Because one line in the comparison table uses four devices, × 4 devices are occupied from .

S 2 S 1

2. Specify the number of lines in the comparison table as .

The created table starts from the head register , and has the number of lines specified in .

S 1 S 2

3. Comparison data Make sure that the comparison data is 32 bits.
4. Output (Y) number Specify each digit of the (Y) number in hexadecimal form. Example: When specifying Y010, specify "H10".

FNC140-FNC149 Data Operation 2

When specifying Y020, specify "H20".

5. Specification of set and reset These set and reset are directly controlled as interrupt.
Show 22 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Command · input · Head device · Number · Comparison · of lines · source · 0 ↓ · 1 ↓ · 2 ↓ · … · … · … · … · FNC110-FNC139 Floating Point · Contents of setting · FNC150-FNC159 Positioning Control · Set (ON) K1/H1 · Reset (OFF) K0/H0
Page 368 of the Mitsubishi Electronics MELSEC FX3S user manual — 2. Operation
Page 368 · click to enlarge
Page 368

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.6 FNC 55 – HSZ / High-Speed Counter Zone Compare

2. Operation

Mitsubishi Electronics MELSEC FX3S — 2. Operation diagram (page 368)
Fig. 292 · 2. Operation

Output is set or reset. K1: Output is set.

Output is set or reset. K0: Output is reset.

Output is set or reset. K1: Output is set.

Output is set or reset. K0: Output is reset.

Output is set or reset. K1: Output is set.

Page 369 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 369 · click to enlarge
Page 369

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.6 FNC 55 – HSZ / High-Speed Counter Zone Compare 11

Comparison table

FNC30-FNC39 Rotation and Shift

Present value of C251

number SET/RST Table counter

D201,D200

A program to reset the counter is required.

K123

H10

K1

D205,D204

K234

H10

K0

D209,D208

K345

H11

K1

D213,D212

K456

H11

K0

4 ↓ Repeated from "0".

D217,D216

K567

H11

K1

1. When this instruction is executed, the top table in the data table is set as the comparison target data.

Y010

A program to reset the output is required.

Y011

2. When the current value of the high-speed counter C251 is equivalent to the comparison target data table, the output (Y) number specified in the table is set or reset. This output processing is directly executed regardless of completion of output refresh by END instruction.
3. "1" is added to the current value of the table counter D8130.
4. The comparison target data table is transferred to the next table.
5. The steps 2) and 3) are repeated until the current value of the table counter D8130 becomes "4". When the current value becomes "4", the program execution returns to the step 1), and the table counter D8130 is reset to "0". At this time, the complete flag M8131 turns ON.

FNC70-FNC79 External FX I/O Device

6. When the command contact is set to OFF, execution of the instruction is stopped and the table counter D8130 is reset to "0".

Cautions

FNC80-FNC89 External FX Device

1. Limitation in the number of DHSZ instructions This instruction can be programmed only once in a program. With regard to the DHSCS, DHSCR, DHSZ and DHSCT instructions used for other purposes, up to 32 instructions including the DHSZ instruction can be driven at one time.
2. When the command input is set to OFF in the middle of execution Execution of the instruction is aborted, and the table counter D8130 is reset to K0. However, outputs which have been set or reset remain in the current status.

FNC100-FNC109 Data Transfer 2

3. Output start timing After the DHSZ instruction is first executed, creation of the table is completed by END instruction. After that, the DHSZ instruction becomes valid. Accordingly, the output is activated from the second scan.
4. Current value of a high-speed counter Make sure to execute the DHSZ instruction from a point where the current value of the high-speed counter (regarded as the operation target) is smaller than the value in the 1st line in the comparison table.

FNC140-FNC149 Data Operation 2

Show 12 more labels / short text on this page
Comparison · Output (Y) · data · 0 ↓ · 1 ↓ · FNC40-FNC49 Data Operation · 2 ↓ · 3 ↓ · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 370 of the Mitsubishi Electronics MELSEC FX3S user manual — Example of table configuration and data setting
Page 370 · click to enlarge
Page 370

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.6 FNC 55 – HSZ / High-Speed Counter Zone Compare

13.6.3 Frequency control mode (HSZ and PLSY instructions) (M8132)

Mitsubishi Electronics MELSEC FX3S — 13.6.3 Frequency control mode (HSZ and PLSY instructions) (M8132) diagram (page 370)
Fig. 293 · 13.6.3 Frequency control mode (HSZ and PLSY instruct…

When the special auxiliary relay M8132 for declaring the frequency control mode is specified as in the DHSZ instruction, the special function shown below is provided if DPLSY instruction is combined.

At this time, only a data register D can be specified as , and a constant K or H can be specified as . The available range is limited to "1 ≤ K, H ≤ 128".

A high-speed counter C235 to C255 can be specified as . This function is different from the zone comparison described above. PLSY instruction is as shown on the next page, and only the pulse output can be changed by users.

1. Control example

Example of table configuration and data setting

Mitsubishi Electronics MELSEC FX3S — Example of table configuration and data setting diagram (page 370)
Fig. 294 · Example of table configuration and data setting
Mitsubishi Electronics MELSEC FX3S — Example of table configuration and data setting diagram (page 370)
Fig. 295 · Example of table configuration and data setting

Head device (32 bits) specified as S1 ‚

Page 371 of the Mitsubishi Electronics MELSEC FX3S user manual — 13.6 FNC 55 – HSZ / High-Speed Counter Zone Compare 11
Page 371 · click to enlarge
Page 371

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.6 FNC 55 – HSZ / High-Speed Counter Zone Compare 11

Mitsubishi Electronics MELSEC FX3S — 13.6 FNC 55 – HSZ / High-Speed Counter Zone Compare 11 diagram (page 371)
Fig. 296 · 13.6 FNC 55 – HSZ / High-Speed Counter Zone Compare…
Page 372 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 372 · click to enlarge
Page 372

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.6 FNC 55 – HSZ / High-Speed Counter Zone Compare

Output pulse characteristics

Mitsubishi Electronics MELSEC FX3S — Output pulse characteristics diagram (page 372)
Fig. 297 · Output pulse characteristics
1. Write prescribed data in advance to data registers constructing the table as shown in this program example.
2. The output frequency of the PLSY instruction remains in the value (D303, D302) until the current value of a high-

speed counter specified in becomes equivalent to (D301, D300). (D302 specifies low-order 16 bits. D303 specifies high-order 16 bits, but is always "0".)

3. The operation in the 2nd line is started after that, and then the operation in each line is executed in turn.
4. When the operation in the last line is completed, the complete flag M8133 turns ON. The program execution returns to the 1st line, and the operation is repeated.
5. For stopping the operation in the last line, set the frequency in the last table to K0.
6. When the command input is set to OFF, the pulse output turns OFF and the table counter D8131 is reset.
7. After the DHSZ instruction is first executed, creation of the table is completed at the END instruction. The DHSZ instruction becomes valid after that.
8. Accordingly, the contact of PLS M10 is used so that the PLSY instruction is executed from the second scan after the command input has been set to ON.

Data can be written to the table in a program as shown in this example or directly using keys in peripheral equipment.

1. M8132 This is the special auxiliary relay for declaring the frequency control mode
2. D8132 In the frequency control mode, the frequency set in the table is received by D8132 sequentially according to the table counter count D8131.
3. D8134 (low-order) and D8135 (high-order) In the frequency control mode, the comparison data in the table is received sequentially according to the table counter count.

Cautions

1. The DHSZ instruction can only be used once.
2. With regard to the DHSCS (FNC 53), DHSCR (FNC 54), DHSZ (FNC 55) and DHSCT (FNC280) instructions used for other purposes, up to 32 instructions including the DHSZ instruction can be driven at one time.
3. Because the table is created when the END instruction is executed, it is necessary to delay execution of the PLSY (FNC 57) instruction until creation of the table is completed.
4. Do not change the data table while the DHSZ instruction is driven.
5. In the frequency control mode, simultaneous output to Y000 to Y001 is not permitted.
Page 373 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Applicable devices
Page 373 · click to enlarge
Page 373

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.7 FNC 56 – SPD / Speed Detection 11

13.7 FNC 56 – SPD / Speed Detection

FNC30-FNC39 Rotation and Shift

Outline

This instruction counts the input pulse for a specified period of time as interrupt input. The function of this instruction varies depending on the version.

1. Instruction format

16-bit Instruction Mnemonic Operation Condition FNC 56

Mnemonic Operation Condition 32-bit Instruction

SPD D

13 steps DSPD Continuous Operation 7 steps SPD Continuous Operation

2. Set data

Operand Type Description Data Type

Device number of pulse input (X) Bit

Time data (ms) or word device number storing the data 16- or 32-bit binary

Head word device number storing the pulse density data 16- or 32-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

Unit Index Constant Real Number

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FNC70-FNC79 External FX I/O Device

3 S2 S3

S1: Specify X000 to X007 in FX3G/FX3GC/FX3U/FX3UC PLCs.

Specify X000 to X005 in FX3S PLC. S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S3: This function is supported only in FX3U/FX3UC PLCs.

FNC80-FNC89 External FX Device

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 8 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Charac- ter String Pointer · and Type · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 374 of the Mitsubishi Electronics MELSEC FX3S user manual — D D
Page 374 · click to enlarge
Page 374

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.7 FNC 56 – SPD / Speed Detection

Explanation of function and operation

1. 16-bit operation (SPD)

The input pulse is counted only for × 1 ms. The measured value is stored in , the present value is

S 1 S 2 D

stored in +1, and the remaining time is stored in +2 (ms).

D D

By repeating this operation, the measured value will store the pulse density (which is proportional to the rotation speed).

SPD S1 ‚ D ‚ S2 ‚

1. Timing chart
Mitsubishi Electronics MELSEC FX3S — D D diagram (page 374)
Fig. 298

D ‚ + 1 counts "OFF → ON" operation of .

ms later, the counting result is stored to .

then counting of the "OFF → ON" operation of is

+ 2 is used to measure the remaining time. D ‚

2. The measured value is in proportion to the number of rotations as shown below:

t: Measurement time duration specified as (ms) S2

Command · input

Page 375 of the Mitsubishi Electronics MELSEC FX3S user manual — 13.7 FNC 56 – SPD / Speed Detection 11
Page 375 · click to enlarge
Page 375

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.7 FNC 56 – SPD / Speed Detection 11

Mitsubishi Electronics MELSEC FX3S — 13.7 FNC 56 – SPD / Speed Detection 11 diagram (page 375)
Fig. 299 · 13.7 FNC 56 – SPD / Speed Detection 11

The input pulse is counted only for [ +1, ] x 1 ms. The measured value is stored in [ +1,

], the present value is stored in [ +3, +2], and the remaining time is stored in [ +5, +4] (ms).

By repeating this operation, the measured value [ +1, ] will store the pulse density (which is proportional to the rotation speed).

DSPD S1 ‚ D ‚ S2 ‚

of . [ +1, ] ms later, the counting result is

reset, and then counting of the "OFF → ON" operation of

[ +1, ] S2‚ S2‚ ms [ +1, ] S2‚ S2‚

[ +5, +4] is used to measure the remaining

[ +1, ] S2‚ S2‚

2. The measured value [ +1, ] is in proportion to the number of rotations as shown below:

t: Measurement time duration specified as [ +1, ] (ms)

Page 376 of the Mitsubishi Electronics MELSEC FX3S user manual — Function change depending on the version
Page 376 · click to enlarge
Page 376

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.7 FNC 56 – SPD / Speed Detection

Cautions

1. Input specifications of the input

  • An input device X000 to X007 specified as cannot overlap the following functions or instructions: - High-speed counter - Input interrupt - Pulse catch - Pulse width/Pulse period - DSZR instruction - DVIT instruction - ZRN instruction
  • For one input, this instruction can only be used once.
  • The maximum input frequency of turning the inputs X000 to X007 ON and OFF is shown below: - FX 3S PLC

Used input number Maximum input frequency

- FX3G/FX3GC PLCs

Used input number Maximum input frequency

- FX3U/FX3UC PLCs

Mitsubishi Electronics MELSEC FX3S — Cautions diagram (page 376)
Fig. 300 · Cautions

X000 to X005 100 kHz*1 100 kHz*1 200 kHz X006,X007 10 kHz 10 kHz

*1. When receiving pulses within the response frequency range of 50 k to 100 kHz, perform the following actions: - Make sure that the wiring length is 5 m or less. - Connect a bleeder resistor of 1.5 kΩ (1 W or more) to the input terminal, and make sure that the load current in the open collector transistor output of the external equipment is 20 mA or more.

2. Occupied devices

1. When using the 16-bit operation

Three devices are occupied from a device specified in *2.

2. When using the 32-bit operation

Six devices are occupied from a device specified in *2.

*2. The value is updated by interrupt processing from the CPU, not every scan time (operation cycle) of the PLC.

3. When the value of the word device is changed while the SPD instruction is being executed . When the value of the word device is changed while the SPD instruction is being executed, the operation varies depending on the PLC model.

- FX3U/FX3UC PLCs The changed value of the word device is reflected on the operation at every scan time (operation cycle). - FX3S/FX3G/FX3GC PLCs The changed value of the word device is not reflected on the operation at every scan time (operation cycle), and the PLC operates using the value specified when execution of the SPD instruction started. The PLC operates using the changed value after the command input of the SPD instruction is turned OFF once and turned ON again.

Function change depending on the version

The function of the FNC 56 instruction varies depending on the PLC version shown in the table below.

Mitsubishi Electronics MELSEC FX3S — Function change depending on the version diagram (page 376)
Fig. 301 · Function change depending on the version

Item Outline of function FX3S FX3G FX3GC FX3U FX3UC

or later Addition of 32-bit instruction 32-bit operations (DSPD) are enabled.

Show 4 more labels / short text on this page
X000,X001 60 kHz · X002,X003,X004,X005 10 kHz · X000,X001,X003,X004 60 kHz · X002,X005,X006,X007 10 kHz
Page 377 of the Mitsubishi Electronics MELSEC FX3S user manual — PLSY
Page 377 · click to enlarge
Page 377

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.8 FNC 57 – PLSY / Pulse Y Output 11

13.8 FNC 57 – PLSY / Pulse Y Output

FNC30-FNC39 Rotation and Shift

Outline

This instruction generates a pulse signal.

→ For the frequency control mode, refer to Subsection 13.6.3.

1. Instruction format

16-bit Instruction Mnemonic Operation Condition

Mnemonic Operation Condition 32-bit Instruction

PLSY D

13 steps DPLSY Continuous Operation 7 steps PLSY Continuous Operation

2. Set data

Operand Type Description Data Type

Output pulse frequency 16- or 32-bit binary

Number of output pulses 16- or 32-bit binary

Device number (Y) from which pulses are output Bit

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

Unit Index Constant Real Number

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FNC70-FNC79 External FX I/O Device

3 S2 S3

3 S2 S3

S1: Specify a transistor output on the main unit or Y000 or Y001 on a special high-speed output adapter*1. S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S3: This function is supported only in FX3U/FX3UC PLCs. *1. High-speed output special adapters can be connected only to FX3U PLC.

FNC80-FNC89 External FX Device

Explanation of function and operation

1. 16-bit operation (PLSY)

FNC100-FNC109 Data Transfer 2

A pulse train of frequency is output in the quantity from the output (Y) .

S 1 S 2 D

S1 ‚ D ‚ S2 ‚ D ‚

PLSY

  • Specify the frequency in . Allowable setting range: 1 to 32767 (Hz)
  • Specify the generated pulse quantity in . Allowable setting range: 1 to 32767 (PLS)
  • Specify the output (Y) number from which pulses are to be output in . Allowable setting range: Y000, Y001

FNC140-FNC149 Data Operation 2

Show 12 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Charac- ter String Pointer · and Type · Command · input · Pulse quantity · Frequency · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 378 of the Mitsubishi Electronics MELSEC FX3S user manual — Related devices
Page 378 · click to enlarge
Page 378

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.8 FNC 57 – PLSY / Pulse Y Output

2. 32-bit operation (DPLSY)

A pulse train at the frequency [ +1, ] is output by the quantity [ +1, ] from the output (Y)

S 1 S 1 S 2 S 2

Mitsubishi Electronics MELSEC FX3S — S 1 S 1 S 2 S 2 diagram (page 378)
Fig. 302

S1 ‚ D ‚ S2 ‚ D ‚

  • Specify the frequency in [ +1, ]. - When special high-speed output adapters are used Allowable setting range: 1 to 200,000 (Hz) - When the FX 3S /FX 3G /FX 3GC /FX 3U /FX 3UC PLCs main unit is used Allowable setting range: 1 to 100,000 (Hz)
  • Specify the generated pulse quantity in [ +1, ]. Allowable setting range: 1 to 2,147,483,647 (PLS)

S 2 S 2

  • Specify the output (Y) number from which pulses are output in . Allowable setting range: Y000, Y001

→ For the method to output pulses without any limitation, refer to the program example later.

Related devices

1. Instruction execution complete flag The instruction execution complete flag M8029 used for PLSY instruction can be used also for other instructions. When using other instructions, setting the M8029 flag to ON or OFF, or using two or more PLSY instructions, make sure to use each M8029 flag just after an instruction to be monitored.

→ For the instruction execution complete flag use method, refer to Subsection 6.5.2.

M8029 Instruction execution com-

ON: Generation of specified number of pulses is completed. OFF: Generation of pulses is paused before the specified number of pulses is reached or the continuous pulse generation operation is stopped.

Mitsubishi Electronics MELSEC FX3S — Related devices diagram (page 378)
Fig. 303 · Related devices

M8029 ° Changes by DPSLY instruction corresponding to the command input 2.

Device Name Description · plete

Page 379 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Pulse output
Page 379 · click to enlarge
Page 379

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.8 FNC 57 – PLSY / Pulse Y Output 11

2. Monitoring the current number of generated pulses The number of pulses output from Y000 or Y001 is stored in the following special data registers:

FNC30-FNC39 Rotation and Shift

Description Contents of data High order

D8141 D8140 Accumulated number of pulses output from Y000

Accumulated number of pulses output from Y000 by PLSY and PLSR instructions

D8143 D8142 Accumulated number of pulses output from Y001

Accumulated number of pulses output from Y001 by PLSY and PLSR instructions

D8137 D8136 Total accumulated number of pulses output from Y000 and Y001

Total accumulated number of pulses output from Y000 and Y001 by PLSY and PLSR instructions

The contents of each data register can be cleared using the following program:

DMOV K0 Low-order device shown in

3. How to stop the pulse output

  • When the command input is set to OFF, the pulse generation is immediately stopped. When the command input is set to ON again, pulse generation operation restarts from the beginning.
  • When the special auxiliary relays (M) shown below are set to ON, the pulse output is stopped.

Description FX3S/FX3G/FX3GC FX3U/FX3UC

M8145, M8349 M8349 Immediately stops pulse output from Y000.

M8146, M8359 M8359 Immediately stops pulse output from Y001.

FNC70-FNC79 External FX I/O Device

To restart pulse output, set the device (FX3S/FX3G/FX3GC : M8145, M8146, M8349, M8359 FX3U/FX3UC : M8349, M8359) corresponding to the output signal to OFF, and then drive the pulse output instruction again.

Cautions

FNC80-FNC89 External FX Device

1. When a word device is specified as or When the value of the word device is changed while the instruction is executed, the following operation results:

S 1 S 2

  • When the data in is changed, the output frequency changes accordingly.
  • When the data in is changed, the change (new value) becomes valid the next time the instruction is driven.

2. Frequency

FNC100-FNC109 Data Transfer 2

When using transistor outputs in the main unit, set the output frequency to "100,000 Hz" or less. If the load is operated using pulses at a frequency higher than 100,000 Hz, the PLC may be damaged. Do not set the output frequency to "0".

3. Pulse output

  • Only a transistor output on the main unit or Y000 or Y001 on a special high-speed output adapter *1 can be specified

in . When using the PLSY (FNC 57) instruction with a relay output type or triac output type FX3U PLC, a special high- speed output adapter is required.

*1. High-speed output special adapters can be connected only to FX3U PLC. • The duty cycle of the pulse ON/OFF time is 50 % inside the PLC. However, 50 % may not be output depending on the frequency due to the effect of the output circuit.

FNC140-FNC149 Data Operation 2

  • The pulse output is controlled by the dedicated hardware not affected by the sequence program (operation cycle).
  • If the command input is set to OFF during continuous pulse output, the output from turns OFF.
Show 11 more labels / short text on this page
Device · Low order · FNC40-FNC49 Data Operation · Command · FNC50-FNC59 High-Speed Processing · input · table above · FMC60-FNC69 Handy Instruction · Device · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 380 of the Mitsubishi Electronics MELSEC FX3S user manual — Output operation
Page 380 · click to enlarge
Page 380

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.8 FNC 57 – PLSY / Pulse Y Output

4. Handling of pulse output terminals in FX 3S /FX 3G /FX 3GC /FX 3U /FX 3UC series main units The outputs Y000 and Y001 are the high-speed response type. When using a pulse output instruction or positioning instruction, adjust the load current of the open collector transistor output to about 10 to 100 mA (5 to 24V DC).
Mitsubishi Electronics MELSEC FX3S — 13.8 FNC 57 – PLSY / Pulse Y Output diagram (page 380)
Fig. 304 · 13.8 FNC 57 – PLSY / Pulse Y Output

When the load is smaller, connect a dummy resistor in parallel to the outside of a used output terminal (Y000 or Y001) as shown in the circuit diagram below so that the specified current shown above flows in the output transistor.

5. Cautions on using special high-speed output adapters

1. Outputs of special high-speed output adapters work as differential line drivers.
2. Set the pulse output type setting switch in a special high-speed output adapter to the "pulse chain + direction" (PLS x DIR) side. If the switch is set to the "forward rotation pulse chain reverse rotation pulse chain" (FP x RP) side, normal operations are disabled. The pulse output destination changes depending on the PLC output status as shown in the table below.
Mitsubishi Electronics MELSEC FX3S — 5. Cautions on using special high-speed output adapters diagram (page 380)
Fig. 305 · 5. Cautions on using special high-speed output adapt…

= Y000 Y004 While Y004 is ON, pulses are output from Y000 in the high-speed output adapter. While Y004 is OFF, pulses are output from Y004 in the high-speed output adapter.

= Y001 Y005 While Y005 is ON, pulses are output from Y001 in the high-speed output adapter. While Y005 is OFF, pulses are output from Y005 in the high-speed output adapter.

3. Set the pulse output type setting switch while the PLC is stopped or while the power is OFF. Do not manipulate the pulse output form setting switch while pulses are being output.
4. When special high-speed output adapters are connected, the same output numbers in the main unit are assigned as shown in the table below. Only wire the appropriate output terminals. Outputs in special high-speed output adapters and the main unit operate as shown below.

Assignment of output numbers in special high-speed output adapters

Mitsubishi Electronics MELSEC FX3S — Assignment of output numbers in special high-speed output adapters diagram (page 380)
Fig. 306 · Assignment of output numbers in special high-speed o…

switch Signal name Setting name in each positioning instruction

chain (FP) Pulse output destination Y000 Y001 Y002 Y003

chain (RP) Rotation direction signal Y004 Y005 Y006 Y007

Pulse chain Pulse output destination Y000 Y001 Y002 Y003

Output operation

Mitsubishi Electronics MELSEC FX3S — Output operation diagram (page 380)
Fig. 307 · Output operation

While instruction is activated, relevant output is ON. (LED is also ON.) Use a special high-speed adapter.

Special high-speed output adapter Operated. (LED is also operated.) Set the output frequency to "200kHz" or less.

Transistor output type main unit Operated. (LED is ON.) Set the output frequency to "100kHz" or less.

Page 381 of the Mitsubishi Electronics MELSEC FX3S user manual — DPLSY K1000 K0 Y000
Page 381 · click to enlarge
Page 381

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.8 FNC 57 – PLSY / Pulse Y Output 11

6. Others

FNC30-FNC39 Rotation and Shift

1. Types of pulse output, positioning and other relevant instructions and their target output numbers

Classification Instruction Instruction name Target output numbers

PLSY (FNC 57) Pulse Y output Y000,Y001

PLSR (FNC 59) Acceleration/deceleration setup Y000,Y001

DSZR (FNC150) DOG search zero return Y000,Y001,Y002*1,Y003*2

DVIT (FNC151)*3 Interrupt positioning Y000,Y001,Y002,Y003*2

ZRN (FNC156) Zero return Y000,Y001,Y002*1,Y003*2

PLSV (FNC157) Variable speed pulse output Y000,Y001,Y002*1,Y003*2

DRVI (FNC158) Drive to increment Y000,Y001,Y002*1,Y003*2

DRVA (FNC159) Drive to absolute Y000,Y001,Y002*1,Y003*2

High-speed processing PWM (FNC 58) Pulse width modulation Y000,Y001,Y002*1,Y003*2

*1. Y002 is not available in FX3G PLC (14-point and 24-point type) and FX3S/FX3GC PLCs.

*2. Y003 is available only when two high-speed output special adapters are connected to the FX3U PLC.

*3. This function is supported only in FX3U/FX3UC PLCs.

2) When using the same output relay (Y000 or Y001) in several instructions. While a pulse output monitor (BUSY/READY) flag is ON a pulse output instruction and positioning instruction for the same output relay cannot be executed. While a pulse output monitor flag is ON even after the instruction drive contact is set to OFF, a pulse output instruction or positioning instruction for the same output relay cannot be executed. Before executing such an instruction, wait until the pulse output monitor flag turns OFF and one or more operation cycles pass.

FNC70-FNC79 External FX I/O Device

Pulse output destination device Pulse output monitor flag

Y000 M8340

Y001 M8350

3. "Frequency control mode" in which DHSZ (FNC 55) and PLSY (FNC 57) instructions are combined can only be used once in a program.

FNC80-FNC89 External FX Device

Program example (when outputting pulses without any limitation)

When is set to K0, pulses are output without any limitation.

DPLSY K1000 K0 Y000

Y000

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 11 more labels / short text on this page
Pulse output · FNC40-FNC49 Data Operation · Positioning · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Command · No limitation (K0) · input · 1000Hz · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 382 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 382 · click to enlarge
Page 382

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.9 FNC 58 – PWM / Pulse Width Modulation

13.9 FNC 58 – PWM / Pulse Width Modulation

Outline

This instruction outputs pulses with a specified period and ON duration.

1. Instruction format

16-bit Instruction Mnemonic Operation Condition FNC 58

Mnemonic Operation Condition 32-bit Instruction

PWM

7 steps PWM Continuous Operation

−

2. Set data

Mitsubishi Electronics MELSEC FX3S — − diagram (page 382)
Fig. 308

Device number (Y) from which pulses are to be output Bit

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 382)
Fig. 309 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S2 S3

3 S2 S3

S1: Specify transistor output Y000, Y001, or Y002*1 on the main unit or Y000, Y001, Y002, or Y003 on a special high-

speed output adapter*2. S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S3: This function is supported only in FX3U/FX3UC PLCs. *1. Y002 is not available in FX3G PLC (14-point and 24-point type) and FX3S/FX3GC PLCs. *2. High-speed output special adapters can be connected only to FX3U PLC.

Explanation of function and operation

1. 16-bit operation (PWM)

Pulses whose ON pulse width is ms are output in periods of ms.

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 382)
Fig. 310 · Explanation of function and operation

PWM S1 ‚ D ‚ S2 ‚

  • Specify the pulse width "t" in . Allowable setting range: 0 to 32767 ms
  • Specify the period "T 0 " in . Allowable setting range: 1 to 32767 ms
  • Specify the output (Y) number from which pulses are to be output in . Allowable setting range: Y000, Y001, Y002, Y003
Page 383 of the Mitsubishi Electronics MELSEC FX3S user manual — Y002 M8360
Page 383 · click to enlarge
Page 383

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.9 FNC 58 – PWM / Pulse Width Modulation 11

Cautions

FNC30-FNC39 Rotation and Shift

1. Setting the pulse width and period

Make sure that the pulse width and period satisfy the relationship " ≤ ".

S 1 S 2 S 1 S 2

2. Pulse output

  • Only the following outputs can be specified in according to the system configuration.

- When using special high-speed output adapters*1: Y000, Y001, Y002*2, or Y003*2

- When transistor outputs in the main unit are used: Y000, Y001, or Y002*3

*1. High-speed output special adapters can be connected only to FX3U PLC. Use a transistor output type PLC.

*2. When specifying Y002 or Y003 on a special high-speed output adapter, a second special high-speed output adapter is required.

*3. Y002 is not available in FX3G PLC (14-point and 24-point type) and FX3S/FX3GC PLCs.

  • The pulse output is controlled by interrupt processing not affected by the sequence program (operation cycle).
  • If the command input is set to OFF, the output from turns OFF.
  • While a pulse output monitor (BUSY/READY) flag is ON, a pulse output or positioning instruction for the same output relay cannot be executed. While a pulse output monitor flag is ON even after the instruction drive contact is set to OFF, a pulse output or positioning instruction for the same output relay cannot be executed. Before executing a pulse output or positioning instruction, wait until the pulse output monitor flag turns OFF and one or more operation cycles pass.

Pulse output destination device Pulse output monitor flag

Y000 M8340

Y001 M8350

FNC70-FNC79 External FX I/O Device

Y002 M8360

Y003 M8370

3. Cautions on using special high-speed output adapters

1. Outputs of special high-speed output adapters work as differential line drivers.
2. Set the pulse output type setting switch of a special high-speed output adapter to the "pulse chain + direction" (PLS x DIR) side. If the switch is set to the "forward rotation pulse chain reverse rotation pulse chain" (FP x RP) side, normal operations are not possible. The pulse output destination changes depending on the output status as shown in the table below.

FNC80-FNC89 External FX Device

FNC100-FNC109 Data Transfer 2

= Y000 Y004 While Y004 is ON, pulses are output from Y000 on the high-speed output adapter. While Y004 is OFF, pulses are output from Y004 on the high-speed output adapter.

= Y001 Y005 While Y005 is ON, pulses are output from Y001 on the high-speed output adapter. While Y005 is OFF, pulses are output from Y005 on the high-speed output adapter.

= Y002 Y006 While Y006 is ON, pulses are output from Y002 on the high-speed output adapter. While Y006 is OFF, pulses are output from Y006 on the high-speed output adapter.

= Y003 Y007 While Y007 is ON, pulses are output from Y003 on the high-speed output adapter. While Y007 is OFF, pulses are output from Y007 on the high-speed output adapter.

3. Set the pulse output type setting switch while the PLC is stopped or while the power is OFF. Do not adjust the pulse output type setting switch while pulses are being output.

FNC140-FNC149 Data Operation 2

Show 9 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Pulse output · Output affecting · destination · operation Operation · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 384 of the Mitsubishi Electronics MELSEC FX3S user manual — Example of smoothing circuit
Page 384 · click to enlarge
Page 384

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.9 FNC 58 – PWM / Pulse Width Modulation

4. When special high-speed output adapters are connected, the same output numbers in the main unit are assigned as shown in the table below. Only wire the appropriate output terminals. Outputs in special high-speed output adapters and the main unit operate as shown below.

Assignment of output numbers in special high-speed output adapters

Mitsubishi Electronics MELSEC FX3S — Assignment of output numbers in special high-speed output adapters diagram (page 384)
Fig. 311 · Assignment of output numbers in special high-speed o…

setting switch Signal name Setting name in each positioning instruction

chain (FP) Pulse output destination Y000 Y001 Y002 Y003

chain (RP) Rotation direction signal Y004 Y005 Y006 Y007

Pulse chain Pulse output destination Y000 Y001 Y002 Y003

Output operation

Mitsubishi Electronics MELSEC FX3S — Output operation diagram (page 384)
Fig. 312 · Output operation

Do not use the PWM (FNC 58) instruction with relay-output type main units. (Considerable output response delay may be generated, chattering may occur in contacts, or the contact life may be shortened.)

Triac output type main unit Do not use the PWM (FNC 58) instruction with triac-output type main units. (Considerable output response delay may be generated.)

Special high-speed output adapter Use a transistor output type main unit.

Program example

When the contents of D10 are changed ranging from "0" to "50" in the program example shown below, the average output from Y000 will be ranging from 0 to 100%. An error will occur if the contents of D10 exceed 50. In this program example the FX3U series main unit (sink output) is used. For wiring details, refer to the Hardware Edition of each PLC.

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 384)
Fig. 313 · Program example

Example of smoothing circuit

Mitsubishi Electronics MELSEC FX3S — Example of smoothing circuit diagram (page 384)
Fig. 314 · Example of smoothing circuit

R >> P τ = P(kΩ) ° C(µF) = 470ms >> T0 The time constant of the filter should be considerably larger than the pulse cycle T0. The ripple value "∆e" in the mean output current "e" is approximately "∆e/e ≤ T0/τ"

Page 385 of the Mitsubishi Electronics MELSEC FX3S user manual — (H Z )
Page 385 · click to enlarge
Page 385

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.10 FNC 59 – PLSR / Acceleration/Deceleration Setup 11

13.10 FNC 59 – PLSR / Acceleration/Deceleration Setup

FNC30-FNC39 Rotation and Shift

Outline

This pulse output instruction has the acceleration/deceleration function.

1. Instruction format

16-bit Instruction Mnemonic Operation Condition FNC 59

Mnemonic Operation Condition 32-bit Instruction

PLSR D

17 steps DPLSR Continuous Operation 9 steps PLSR Continuous Operation

2. Set data

Operand Type Description Data Type

Maximum frequency (Hz) 16- or 32-bit binary

Total number of output pulses (PLS) 16- or 32-bit binary

Acceleration/deceleration time (ms) 16- or 32-bit binary

Device number (Y) from which pulses are to be output Bit

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

Unit Index Constant Real Number

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S2 S3

FNC70-FNC79 External FX I/O Device

3 S2 S3

3 S2 S3

S1: Specify a transistor output on the main unit or Y000 or Y001 on a special high-speed output adapter*1. S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S3: This function is supported only in FX3U/FX3UC PLCs. *1. High-speed output special adapters can be connected only to FX3U PLC.

FNC80-FNC89 External FX Device

Explanation of function and operation

1. 16-bit operation (PLSR)

FNC100-FNC109 Data Transfer 2

Pulses are output from output (Y) by the specified number with acceleration/deceleration to the

D S 2

maximum frequency over the time (ms).

S 1 S 3

Maximum frequency S1 ‚

S1 D S2 S3

PLSR

Total number of output

(H Z )

(Y000,

Y001)

(PLS)

(PLS)

: Maximum frequency (Hz) Allowable setting range: 10 to 32767 (Hz)

FNC140-FNC149 Data Operation 2

: Total number of output pulses (PLS) Allowable setting range: 1 to 32767 (PLS)

S3 ‚ Acceleration/ deceleration time S3 ‚

: Acceleration/deceleration time (ms) Allowable setting range: 50 to 5000 (ms)

: Pulse output number Allowable setting range: Y000, Y001

Show 20 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Charac- ter String Pointer · and Type · Pulse frequency (Hz) · Command · input · FNC110-FNC139 Floating Point · Maximum frequency · Acceleration/ · Output number · Total number of · deceleration · time (ms) · output pulses · pulses · Acceleration/ deceleration time · FNC150-FNC159 Positioning Control
Page 386 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Pulse output specifications
Page 386 · click to enlarge
Page 386

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.10 FNC 59 – PLSR / Acceleration/Deceleration Setup

2. 32-bit operation (DPLSR)

Pulses are output from the output (Y) by the specified number [ +1, ] with acceleration/deceleration

Mitsubishi Electronics MELSEC FX3S — 2. 32-bit operation (DPLSR) diagram (page 386)
Fig. 315 · 2. 32-bit operation (DPLSR)

to the maximum frequency [ +1, ] for the time [ +1, ](ms).

S1 ‚ D ‚ S2 ‚ S3 ‚

- When special high-speed output adapters are used Allowable setting range: 10 to 200,000 (Hz) - When the FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs main unit is used Allowable setting range: 10 to 100,000 (Hz)

[ +1, ]Total number of output pulses (PLS)

S 2 S 2

Allowable setting range1 to 2,147,483,647 (PLS)
[ +1, ]Acceleration/deceleration time (ms)

S 3 S 3

Allowable setting range50 to 5000 (ms)

: Pulse output number Allowable setting range: Y000, Y001

3. Pulse output specifications

  • Simple positioning (with the acceleration/deceleration function) The operation pattern is as shown below:
Mitsubishi Electronics MELSEC FX3S — 3. Pulse output specifications diagram (page 386)
Fig. 316 · 3. Pulse output specifications

Maximum frequency (Hz) ‚ 16-bit operation: 10 to 32767 Hz ‚ 32-bit operation: 10 to 200,000 Hz Pulse frequency (Hz)

  • Output processing The pulse output is controlled by the dedicated hardware regardless of the operation cycle.
  • Data change while the instruction is executed Even if operands are overwritten while the instruction is executed, such changes are not reflected immediately. The changes become valid the next time the instruction is driven.
Page 387 of the Mitsubishi Electronics MELSEC FX3S user manual — 2. Pulse output
Page 387 · click to enlarge
Page 387

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.10 FNC 59 – PLSR / Acceleration/Deceleration Setup 11

Related devices

FNC30-FNC39 Rotation and Shift

1. Instruction execution complete flag → For the instruction execution complete flag use method, refer to Subsection 6.5.2.

OFF: The input command is OFF, or pulses are being output. (This flag does not turn ON if the pulse output is interrupted in the middle of output.)

M8029 Instruction execution com-

ON: Output of the number of pulses set in is completed.

2. Monitoring the number of generated pulses The number of pulses output from Y000 or Y001 is stored in the following special data registers:

Description Contents of data High order

D8141 D8140 Accumulated number of pulses output from Y000

Accumulated number of pulses output from Y000 by PLSY and PLSR instructions

D8143 D8142 Accumulated number of pulses output from Y001

Accumulated number of pulses output from Y001 by PLSY and PLSR instructions

D8137 D8136 Total accumulated number of pulses output from Y000 and Y001

Total accumulated number of pulses output from Y000 and Y001 by PLSY and PLSR instructions

The contents of each data register can be cleared using the following program:

DMOV K0 Low-order device shown in

3. How to stop the pulse output

FNC70-FNC79 External FX I/O Device

  • When the command input is set to OFF, the pulse generation is immediately stopped. When the command input is set to ON again, pulse generation operation restarts from the beginning.
  • When the special auxiliary relays (M) shown below are set to ON, the pulse output is stopped.

Description FX3S/FX3G/FX3GC FX3U/FX3UC

FNC80-FNC89 External FX Device

M8145,M8349 M8349 Immediately stops pulse output from Y000.

M8146,M8359 M8359 Immediately stops pulse output from Y001.

To restart pulse output pulses again, set the device (FX3S/FX3G/FX3GC : M8145, M8146, M8349, M8359 FX3U/FX3UC : M8349, M8359) corresponding to the output signal to OFF, and then drive the pulse output instruction again.

FNC100-FNC109 Data Transfer 2

Cautions

1. Frequency

When using transistor outputs on the main unit, set the output frequency to "100,000 Hz" or less. If the load is operated using pulses at a frequency higher than 100,000 Hz from transistor outputs in the main unit, the PLC may be damaged.

2. Pulse output

  • Only a transistor output on the main unit or Y000 or Y001 on a special high-speed output adapter *1 can be specified in . *1. High-speed output special adapters can be connected only to FX 3U PLC. When using the PLSR (FNC 59) instruction with a relay output type or triac output type FX 3U PLC, a special high-speed output adapter is required.
  • The duty cycle of the pulse ON/OFF time is 50 % inside the PLC. However, 50 % may not be output depending on the frequency due to the effect of the output circuit.

FNC140-FNC149 Data Operation 2

  • The pulse output is controlled by the dedicated hardware not affected by the sequence program (operation cycle).
  • If the command input is set to OFF during continuous pulse output, the output from turns OFF.
Show 13 more labels / short text on this page
Device Name Description · plete · FNC40-FNC49 Data Operation · Device · Low order · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Command · input · above table · Device · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 388 of the Mitsubishi Electronics MELSEC FX3S user manual — Output operation
Page 388 · click to enlarge
Page 388

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.10 FNC 59 – PLSR / Acceleration/Deceleration Setup

3. Handling of pulse output terminals in FX 3S /FX 3G /FX 3GC /FX 3U /FX 3UC series main units The outputs Y000 and Y001 are the high-speed response type. When using a pulse output instruction or positioning instruction, adjust the load current of the open collector transistor output to about 10 to 100 mA (5 to 24V DC).

Operating voltage range 5 to 24V DC

Operating current range 10 to 100 mA

Output frequency 100 kHz or less

When the load is smaller, connect a dummy resistor in parallel to the outside of a used output terminal (Y000 or Y001) as shown in the circuit diagram below so that the specified current shown above flows in the output transistor.

Mitsubishi Electronics MELSEC FX3S — 13.10 FNC 59 – PLSR / Acceleration/Deceleration Setup diagram (page 388)
Fig. 317 · 13.10 FNC 59 – PLSR / Acceleration/Deceleration Setu…

4. Cautions on special high-speed output adapters

1. Outputs of special high-speed output adapters work as differential line drivers.
2. Set the pulse output type setting switch in a special high-speed output adapter to the "pulse chain + direction" (PLS x DIR) side. If the switch is set to the "forward rotation pulse chain reverse rotation pulse chain" (FP x RP) side, normal operations are disabled. The pulse output destination changes depending on the PLC output status as shown in the table below.
Mitsubishi Electronics MELSEC FX3S — 4. Cautions on special high-speed output adapters diagram (page 388)
Fig. 318 · 4. Cautions on special high-speed output adapters

= Y000 Y004 While Y004 is ON, pulses are output from Y000 in the high-speed output adapter. While Y004 is OFF, pulses are output from Y004 in the high-speed output adapter.

= Y001 Y005 While Y005 is ON, pulses are output from Y001 in the high-speed output adapter. While Y005 is OFF, pulses are output from Y005 in the high-speed output adapter.

3. Set the pulse output type setting switch while the PLC is stopped or while the power is OFF. Do not manipulate the pulse output type setting switch while pulses are being output.
4. When special high-speed output adapters are connected, the same output numbers in the main unit are assigned as shown in the table below. Only wire the appropriate output terminals. Outputs in special high-speed output adapters and the main unit operate as shown below.

Assignment of output numbers in special high-speed output adapter

Mitsubishi Electronics MELSEC FX3S — Assignment of output numbers in special high-speed output adapter diagram (page 388)
Fig. 319 · Assignment of output numbers in special high-speed o…

setting switch Signal name Setting name in each positioning instruction

chain (FP) Pulse output destination Y000 Y001 Y002 Y003

chain (RP) Rotation direction signal Y004 Y005 Y006 Y007

Pulse chain Pulse output destination Y000 Y001 Y002 Y003

Output operation

Mitsubishi Electronics MELSEC FX3S — Output operation diagram (page 388)
Fig. 320 · Output operation

While instruction is active, associated output is ON. (LED is also ON.) Use a special high-speed adapter.

Special high-speed output adapter Operated. (LED is also operated.) Set the output frequency to "200kHz" or less.

Transistor output type main unit Operated. (LED is ON.) Set the output frequency to "100kHz" or less.

Item Description

Page 389 of the Mitsubishi Electronics MELSEC FX3S user manual — Y000 M8340
Page 389 · click to enlarge
Page 389

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

13 High-Speed Processing – FNC 50 to FNC 59

13.10 FNC 59 – PLSR / Acceleration/Deceleration Setup 11

5. Others

FNC30-FNC39 Rotation and Shift

1. Types of pulse output, positioning and other relevant instructions and their target output numbers

Classification Instruction Instruction name Target output numbers

PLSY (FNC 57) Pulse Y output Y000,Y001

PLSR (FNC 59) Acceleration/deceleration setup Y000,Y001

DSZR (FNC150) DOG search zero return Y000,Y001,Y002*1,Y003*2

DVIT (FNC151)*3 Interrupt positioning Y000,Y001,Y002,Y003*2

ZRN (FNC156) Zero return Y000,Y001,Y002*1,Y003*2

PLSV (FNC157) Variable speed pulse output Y000,Y001,Y002*1,Y003*2

DRVI (FNC158) Drive to increment Y000,Y001,Y002*1,Y003*2

DRVA (FNC159) Drive to absolute Y000,Y001,Y002*1,Y003*2

High-speed processing PWM (FNC 58) Pulse width modulation Y000,Y001,Y002*1,Y003*2

*1. Y002 is not available in FX3G PLC (14-point and 24-point type) and FX3S/FX3GC PLCs.

*2. Y003 can be used only when two special high-speed output adapters are connected to an FX3U PLC.

*3. This function is supported only in FX3U/FX3UC PLCs.

2) When using the same output relay (Y000 or Y001) in several instructions. While a pulse output monitor (BUSY/READY) flag is ON, a pulse output or positioning instruction for the same output relay cannot be executed. While a pulse output monitor flag is ON, even after the instruction drive contact is set to OFF, a pulse output or positioning instruction for the same output relay cannot be executed. Before executing a pulse output or positioning instruction, wait until the pulse output monitor flag turns OFF and one or more operation cycles pass.

FNC70-FNC79 External FX I/O Device

Pulse output destination device Pulse output monitor flag

Y000 M8340

Y001 M8350

FNC80-FNC89 External FX Device

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 7 more labels / short text on this page
Pulse output · FNC40-FNC49 Data Operation · Positioning · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 390 of the Mitsubishi Electronics MELSEC FX3S user manual — 14. Handy Instruction – FNC 60 to FNC 69
Page 390 · click to enlarge
Page 390

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14. Handy Instruction – FNC 60 to FNC 69

FNC 60 to FNC 69 provide handy instructions which achieve complicated control in a minimum sequence program.

Mitsubishi Electronics MELSEC FX3S — 14. Handy Instruction – FNC 60 to FNC 69 diagram (page 390)
Fig. 321 · 14. Handy Instruction – FNC 60 to FNC 69
Page 391 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 391 · click to enlarge
Page 391

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.1 FNC 60 – IST / Initial State 11

14.1 FNC 60 – IST / Initial State

FNC30-FNC39 Rotation and Shift

Outline

This instruction automatically controls the initial state and special auxiliary relays in a step ladder program.

→ For SFC programs and step ladder, refer to Chapter 35.

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

IST −

2. Set data

Operand type Description Data type

S 1 ‚ S

Head bit device number of the selector switch in the operation mode Bit

Smallest state relay number of practical state relays in the automatic mode

D 1 D 1 D 2

( < ) Bit

Largest state relay number of practical state relays in the automatic mode

D 2 D 1 D 2

( < ) Bit

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC70-FNC79 External FX I/O Device

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S 1 ‚ S

S 2 ‚ D 1

FNC80-FNC89 External FX Device

S1: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S2: S20 to S899 and S1000 to S4095 in the FX3G, FX3GC, FX3U and FX3UC PLCs.

S20 to S255 in the FX3S PLC.

Explanation of function and operation

FNC100-FNC109 Data Transfer 2

IST S ‚ D1 ‚ D2 ‚

  • Specify the head input in the operation mode in .

Selector switches in the operation mode occupy eight devices from the head device , and the switch functions shown in the table below are assigned to each of them. When X020 is assigned as shown below, it is necessary to set X020 to X024 as rotary switches so that they do not turn ON at the same time. It is not necessary to wire unused switches, but they cannot be used for any other purpose because they are occupied by IST instruction.

Source Device number (example) Switch function X020 Individual operation

+ 1 X021 Return to zero point

+ 2 X022 Stepping

FNC140-FNC149 Data Operation 2

+ 3 X023 Cycle operation

+ 4 X024 Continuous operation

+ 5 X025 Zero return start

+ 6 X026 Automatic start

+ 7 X027 Stop

  • Specify the smallest device number of practical state relays in (for the automatic mode).
  • Specify the largest device number of practical state relays in (for the automatic mode).
Show 16 more labels / short text on this page
FNC40-FNC49 Data Operation · Mnemonic Operation Condition · 32-bit Instruction · Continuous Operation · 7 steps IST · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input FNC 60 · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 392 of the Mitsubishi Electronics MELSEC FX3S user manual — 2. Programming order of the IST instruction and STL instruction
Page 392 · click to enlarge
Page 392

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.1 FNC 60 – IST / Initial State

1. Control of devices by switch operations (occupied devices) While the command input is ON, the following devices are automatically switched and controlled. While the command input is OFF, the devices are not switched.

Device number Operation function Device number Operation function

M8040 STL transfer disable S0 Individual operation initial state

M8041*1 Transfer start S1 Zero return initial state

M8042 Start pulse S2 Automatic operation initial state

M8043*1 Zero return complete

M8045 All output reset disable

M8047*2 Enable STL monitoring

*1.Cleared when the PLC mode is changed from RUN to STOP.

*2.Set to ON when END instruction is executed.

Do not program the following state relays as general state relays;

Device number Operation function

  • Occupied for the initial state
  • S0 to S2 are used for individual operation, zero return and automatic operation as shown above.
  • S3 to S9 can be used arbitrarily.

S10 to S19 Occupied for zero return

If the devices are switched among individual operation (X020), zero return (X021) and automatic operation (X022, X023 and X024) while the zero return complete device (M8043) is OFF, all outputs are set to OFF. Automatic operation can be started again after zero return is completed.

→ For introducing IST instruction, refer to "14.1.2 Example of IST instruction introduction (example of

workpiece transfer mechanism)".

Cautions

D 1 S

1. Device specified as and switches to be used It is not necessary to use all switches for mode selection. When some switches are not used, leave the corresponding numbers in the unused status. Such numbers cannot be used for any other purpose.

2. Programming order of the IST instruction and STL instruction

  • The IST instruction should be programmed earlier than a series of STL circuit such as state relays S0 to S2.
3. State relays used for the zero return operation Use the state relays S10 to S19 for the zero return operation. In the final state in the zero return operation, set M8043 to ON, and then let it be reset to OFF by itself.
4. Limitation in the number of IST instructions The IST instruction can only be used once in a program.

S0 to S9

Page 393 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 S D 1 S
Page 393 · click to enlarge
Page 393

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.1 FNC 60 – IST / Initial State 11

14.1.1 IST instruction equivalent circuit

FNC30-FNC39 Rotation and Shift

The details on special auxiliary relays (M) and initial state relays (S0 to S9) which are automatically controlled by the IST instruction are as shown in the equivalent circuit below. (Refer to the equivalent circuit below for reference.) This equivalent circuit cannot be programmed.

1. Equivalent circuit

X024 M8041

X027 M8041 is set to ON when the start button is pressed in the automatic mode. Especially in the continuous mode, M8041 holds its status by itself, and is reset when the stop button is pressed.

M8041

start X026 Automatic start

X026 Automatic start X020

PLS

M8042

Individual operation Start pulse X025 Zero return start

M8040 is set to ON in the stepping mode, and set to OFF every time the start button is pressed. In the zero return operation or cycle operation, M8040 holds its status by itself when the stop button is pressed, and is reset when the start button is pressed.

FNC70-FNC79 External FX I/O Device

M8000

Enable STL monitoring X020 Individual

M8044

The initial state is switched according to each mode input, and M8043 is controlled at the same time. However, it is necessary to control M8044 and M8043 in user programs also.

FNC80-FNC89 External FX Device

complete X021 Zero return

M8043 RST

Zero return start Zero return complete signal is reset

M8043 M8041

Transfer start S 2

FNC100-FNC109 Data Transfer 2

*1. Because the above equivalent circuit is provided only for explanation, it cannot be actually programmed.

2. Switching of the operation mode When the operation mode is switched among the individual operation, zero return operation and automatic operation, all outputs and conventional states are reset at one time unless the machine is located in the zero point. (Reset of all outputs *2 is not executed when M8045 is driven.)

S1 M8043

Switched to X020 (individual operation)

Conventional states and corresponding outputs are reset at one time.

Automatic X022 to X024

M8045

All output reset disable

FNC140-FNC149 Data Operation 2

Switched to X021 (zero return operation)

S2 When M8045 is OFF, all outputs are reset.

Automatic X022 to X024

Even if the mode is switched from automatic operation to zero return operation while S2 is ON, state relays (except initial state relays) and outputs are not reset.

*2. All outputs: Outputs (Y) not driven by state relays and outputs (Y) driven by state relays in OUT and SET instructions

D 1 S D 1 S

Show 40 more labels / short text on this page
Continuous operation · FNC40-FNC49 Data Operation · X022 Stepping · operation · Stop · X023 Cycle · operation · Transfer · X024 Continuous · operation · *1 · FNC50-FNC59 High-Speed Processing · M8040 Individual operation · disable X021 Zero · return X027 M8042 · Stop · STL transfer · FMC60-FNC69 Handy Instruction · Start pulse · X022Stepping operation · X023Cycle · operation X027Stop · M8002 Initial pulse · M8040 Self-holding · M8047 RUN monitor · *1 · operation S 0 · M8043 Zero return · Zero point condition · *1 · *1 · X022 to X024 · Automatic operation · Zero return complete · FNC110-FNC139 Floating Point · Zero return X021 · Zero return · complete S2 · Individual operation X020 · FNC150-FNC159 Positioning Control
Page 394 of the Mitsubishi Electronics MELSEC FX3S user manual — 2. Transfer mechanism
Page 394 · click to enlarge
Page 394

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.1 FNC 60 – IST / Initial State

14.1.2 Example of IST instruction introduction (example of workpiece transfer mechanism)

1. Operation mode

Mechanism for transferring a workpiece from the point A to the point B using the robot hand

Zero return Zero return operation mode

Y003 Rightward Right limit X003

PB

Left limit X004 Y004

Upper limit X002 Moving down

PB

PB PB PB

PB

Y002 Y000

X005 X006 X007

PB PB PB

PB PB

X010 X011 X012

Pushbutton switches for individual operations of the robot hand shown in the figure on the right

Pushbutton switches for the external circuit to

Point A Point B

turn ON and OFF the load power supply

Operation mode Contents of operation

Individual operation mode Each load is turned ON and OFF by an individual pushbutton switch.

Zero return operation mode When the pushbutton switch for zero return is pressed, the machine automatically returns to the zero point.

Stepping operation mode Every time the start button is pressed, the machine performs one process.

When the start button is pressed while the machine is located at the zero point, the machine performs one cycle of automatic operation and stops at the zero point. If the stop button is pressed in the middle of one cycle, the machine stops immediately. When the start button is pressed after that, the machine performs the continuous operation from the last position, and automatically stops at the zero point.

When the start button is pressed while the machine is located at the zero point, the machine starts continuous operation. When the stop button is pressed, the machine finishes the current cycle until the zero point, and then stops at the zero point.

2. Transfer mechanism

Mitsubishi Electronics MELSEC FX3S — 2. Transfer mechanism diagram (page 394)
Fig. 322 · 2. Transfer mechanism

What is the zero point condition? Upper limit X002 is ON, left limit X004 is ON and unclamping Y001 is OFF.

The upper left position is regarded as the zero point. The machine transfers a workpiece from the left to the right in the order "moving down → clamping → moving up → rightward travel → moving down → unclamping → moving up → leftward travel". Double-solenoid type solenoid valves (with two inputs for driving and non-driving) are adopted for moving down, moving up, leftward travel and rightward travel. Single type solenoid valves (which operate only while the power is ON) are adopted for clamping.

Show 25 more labels / short text on this page
Stepping operation · Cycle operation mode · Leftward · Individual operation mode · Continuous operation mode · Power supply · Leftward · Moving up · travel Unclamping · Moving downRightward · Start X 026 · Emergency stop · travel Clamping · Moving · Lower limit X001 · up · Stop X027 · Clamping Y001 · Unclamping Y001 · Workpiece · Manual · mode · Auto- matic mode · Cycle operation mode · Continuous operation mode
Page 395 of the Mitsubishi Electronics MELSEC FX3S user manual — M8000
Page 395 · click to enlarge
Page 395

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.1 FNC 60 – IST / Initial State 11

3. Assignment of mode selection inputs For using IST instruction, it is necessary to assign inputs having consecutive device numbers as shown below for mode inputs. When using non-consecutive inputs or omitting some modes, change the layout by using an auxiliary relay as the head input for mode specification as shown in the figure below.

FNC30-FNC39 Rotation and Shift

- X020: Individual operation mode - X021: Zero return operation mode - X022: Stepping operation mode - X023: Cycle operation mode - X024: Continuous operation - X025: Zero return start - X026: Automatic mode start - X027: Stop

When only the continuous operation mode and zero return

When only the continuous operation mode and individual

When inputs do not have consecutive device numbers

operation mode are used

operation mode are used

Example: X030:Individual operation mode X035:Zero return operation mode X033:Stepping operation mode X040:Cycle operation mode X032:Continuous operation mode X034:Zero return start X026:Automatic mode start X041:Stop

ExampleX030:Zero return operation mode X031:Continuous operation mode X032:Automatic mode start zero
ExampleX030:Individual operation mode X031:Continuous operation mode X032:Automatic mode start X033:Stop

return start X033:Stop

FNC70-FNC79 External FX I/O Device

M8000

M 0 X030

M 0 Individual operation mode

M 0 Does not operate

M8000

M 1 Zero return operation mode

M 1 Zero return operation mode

M 1

FNC80-FNC89 External FX Device

M8000

M 2 Stepping operation mode

M 2 Does not operate

M 2

M 3 Cycle operation mode

M 3

M 3

M 4 Continuous operation

M 4 Continuous operation

M 4 Continuous operation

FNC100-FNC109 Data Transfer 2

M8000

M 5 Zero return start

M 5 Zero return start

M 5

M 6 Automatic mode start

M 6 Automatic mode start

M 6 Automatic mode start X033

In this example, M0 is used as the head input for mode specification.

M8000

IST M 0 S 20 S 29

FNC140-FNC149 Data Operation 2

Show 12 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Individual operation mode · RUN monitor · Does not operate · FNC110-FNC139 Floating Point · M 7 Stop · M 7 Stop · M 7 Stop · RUN monitor · FNC150-FNC159 Positioning Control
Page 396 of the Mitsubishi Electronics MELSEC FX3S user manual — 14.1.2 Example of IST instruction introduction (example of workpiece transfer mechanism)
Page 396 · click to enlarge
Page 396

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.1 FNC 60 – IST / Initial State

4. Special auxiliary relay (M) for the IST instruction Auxiliary relays (M) used in the IST instruction are classified into two types. Some auxiliary relays are automatically controlled by the IST instruction itself according to the situation. Other auxiliary relays should be controlled by a program for preparation of operation or for purpose of control.
1. Special auxiliary relays automatically controlled by the IST instruction a) M8040: STL transfer disable

When this special auxiliary relay turns ON, transfer of every state is disabled. Individual operation mode:

M8040 is always effective. Zero return operation mode and cycle operation mode:

When the stop button is pressed, the operation is held until the start button is pressed. Stepping operation mode:

M8040 is always effective except when the start button is pressed. When the start button is pressed, M8040 is not effective and transfer of states is allowed. Others: The operation is latched when the PLC mode switches from STOP to RUN, and reset when the start button is pressed. Even in the transfer disabled status, the operation is held for outputs in the states. b) M8041: Transfer start

This special auxiliary relay allows transfer from the initial state S2 to the next state. Individual operation mode and zero return operation mode:

M8041 is not effective. Stepping operation mode and cycle operation mode:

M8041 is effective only while the start button is pressed and held. Continuous operation mode:

The operation is latched when the start button is pressed, and cleared when the stop button is pressed. c) M8042: Start pulse

M8042 is activated instantaneously only when the start button is pressed. d) M8047: Enable STL monitoring

When IST instruction is executed, M8047 is set to ON. When the M8047 turns ON, STL monitoring becomes valid, and state relay numbers (S0 to S899) in the ON status are stored in turn in the ascending order of device number to the special data register D8040 to D8047. Up to eight state relay numbers in the ON status can be monitored. If either state relay is ON, the special auxiliary relay M8046 is set to ON.

2. Auxiliary relays controlled by a sequence program

→ For details on these controls, refer to the next page. a) M8043: Zero return complete

Set this special auxiliary relay (M) to ON by a user program when the machine returns to the zero point in the zero return operation mode. b) M8044: Zero point condition

Detect the zero point condition of the machine, and drive this special auxiliary relay. This signal is effective in every mode. c) M8045: All output reset disable

When the mode is switched among individual operation mode, zero return operation mode and automatic mode, all outputs and operation state relays are reset if the machine is not located at the zero point. If M8045 has been set to ON in advance, however, only operation state relays are reset.

Page 397 of the Mitsubishi Electronics MELSEC FX3S user manual — Y003 X002
Page 397 · click to enlarge
Page 397

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.1 FNC 60 – IST / Initial State 11

5. Program example

FNC30-FNC39 Rotation and Shift

1. Circuit diagram In the sequence circuit shown below, all areas except shaded areas are standard. Program the shaded areas according to the contents of control. a) Initial circuit

While the machine is operating, the operation mode can be switched arbitrarily (among stepping operation, cycle operation and continuous operation) in the automatic mode. When the operation mode is switched between the individual operation mode, zero return operation mode and automatic mode while the machine is operating, all outputs are reset once to assure safety, after which the following mode becomes valid. (While M8045 (All output reset disable) is ON, outputs are not reset at all.)

Detects that the machine is located at the zero point, and regards it as the condition to start the automatic mode.

X004 X002

Y001

M8044 Left limit Upper

IST X020 S 20 S 27 M8000

b) Individual operation mode

Programming is not required when the individual operation mode is not provided.

FNC70-FNC79 External FX I/O Device

SET Y001

Unclamping command RST Y001

Initial state for individual operation

Y002

FNC80-FNC89 External FX Device

Y000

Leftward travel command Y003

Y004 X002

Rightward travel command Y004

Y003 X002

Rightward travel Upper limit

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 20 more labels / short text on this page
FNC40-FNC49 Data Operation · Ladder block · FNC50-FNC59 High-Speed Processing · Zero point condition · limit Unclamping · Initial state · RUN monitor · FMC60-FNC69 Handy Instruction · SFC block · State number · Clamping · Clamping command · X005 Moving-up · command Y000 · Moving up · Moving-down command Y002 · Moving down · Leftward travel · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 398 of the Mitsubishi Electronics MELSEC FX3S user manual — 14.1.2 Example of IST instruction introduction (example of workpiece transfer mechanism)
Page 398 · click to enlarge
Page 398

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.1 FNC 60 – IST / Initial State

c) Zero return operation mode

Programming is not required when the zero return operation mode is not provided. It is necessary to set M8043 (zero return complete) to ON before starting the automatic mode.

Mitsubishi Electronics MELSEC FX3S — 14.1.2 Example of IST instruction introduction (example of workpiece transfer mechanism) diagram (page 398)
Fig. 323 · 14.1.2 Example of IST instruction introduction (exam…

Make sure to use the state relays S10 to S19 for the zero return operation. In the final state, drive M8043, and then reset the final state.

Page 399 of the Mitsubishi Electronics MELSEC FX3S user manual — 14.1 FNC 60 – IST / Initial State 11
Page 399 · click to enlarge
Page 399

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.1 FNC 60 – IST / Initial State 11

Mitsubishi Electronics MELSEC FX3S — 14.1 FNC 60 – IST / Initial State 11 diagram (page 399)
Fig. 324 · 14.1 FNC 60 – IST / Initial State 11

d) Automatic mode (stepping operation mode, cycle operation mode or continuous operation mode)

Page 400 of the Mitsubishi Electronics MELSEC FX3S user manual — 14.1.2 Example of IST instruction introduction (example of workpiece transfer mechanism)
Page 400 · click to enlarge
Page 400

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.1 FNC 60 – IST / Initial State

6. List program The list program for the circuit diagram shown on the previous page is as shown below:

0 LD X 004 1 AND X 002 2 ANI Y 001 3 OUT M8044 5 LD M8000 6 IST 60 (SP) X 020 (SP) S 20 (SP) S 27 13 STL S 0 14 LD X 012 15 SET Y 001 16 LD X 007 17 RST Y 001 18 LD X 005 19 ANI Y 000 20 OUT Y 002 21 LD X 010 22 ANI Y 002 23 OUT Y 000 24 LD X 006 25 AND X 002 26 ANI Y 003 27 OUT Y 004 28 LD X 011 29 AND X 002 30 ANI Y 004 31 OUT Y 003 (RET)

32 STL S 1 33 LD X 025 34 SET S 10 36 STL S 10 37 RST Y 001 38 RST Y 000 39 OUT Y 002 40 LD X 002 41 SET S 11 43 STL S 11 44 RST Y 003 45 OUT Y 004 46 LD X 004 47 SET S 12 49 STL S 12 50 SET M8043 52 LD M8043 53 RST S 12 (RET) 55 STL S 2 56 LD M8041 57 AND M8044 58 SET S 20 60 STL S 20 61 OUT Y 000 62 LD X001 63 SET S 21 65 STL S 21 66 SET Y 001 67 OUT T 0 (SP) K 10

70 LD T 0 71 SET S 22 73 STL S 22 74 OUT Y 002 75 LD X 002 76 SET S 23 78 STL S 23 79 OUT Y 003 80 LD X 003 81 SET S 24 83 STL S 24 84 OUT Y 000 85 LD X 001 86 SET S 25 88 STL S 25 89 RST Y 001 90 OUT T 1 (SP) K 10 93 LD T 1 94 SET S 26 96 STL S 26 97 OUT Y 002 98 LD X 002 99 SET S 27 101 STL S 27 102 OUT Y 004 103 LD X 004 104 OUT S 2 106 RET 107 END

Programming is not required.

Show 4 more labels / short text on this page
Initial circuit Individual · Zero return operation · Automatic mode · operation
Page 401 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 2 D
Page 401 · click to enlarge
Page 401

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.2 FNC 61 – SER / Search a Data Stack 11

14.2 FNC 61 – SER / Search a Data Stack

FNC30-FNC39 Rotation and Shift

Outline

This instruction searches for the same data, maximum value and minimum value in a data table.

1. Instruction format

Mnemonic Operation Condition P FNC 61

SER D

Continuous Operation Pulse (Single) Operation

Continuous Operation Pulse (Single) Operation

DSER

SERP

DSERP

2. Set data

Operand type Description Data type

Head device number in which same data, maximum value and minimum value are searched 16- or 32-bit binary

S 1 ‚ S 1

Data to be searched for or device number storing data 16- or 32-bit binary

Head device number storing number of same data, maximum value and minimum value detected by search 16- or 32-bit binary

n Number of data in which same data, maximum value and minimum value are searched [16-bit instruction: 1 to 256, 32-bit instruction: 1 to 128] 16- or 32-bit binary

3. Applicable devices

Bit Devices Word Devices Others

FNC70-FNC79 External FX I/O Device

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S 1 ‚ S 1

3 S1 S2 3

3 S1 S2 3

FNC80-FNC89 External FX Device

3 S1 S2 3

S 2 ‚ D

n 3 S1 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

FNC100-FNC109 Data Transfer 2

1. 16-bit operation (SER and SERP)

In "n" data starting from , same data as is searched, and the search result is stored to to

S 1 S 2 D

+4.

SER n S1 ‚ S2 ‚ D ‚

1. Contents of searched data and the search result a) When same data was detected

Five devices starting from store the number of same data, first position, last position, maximum value position and minimum value position. b) When same data was not detected

FNC140-FNC149 Data Operation 2

Five devices starting from store the number of same data, first position, last position, maximum value position and minimum value position.

In this case, however, "0" is stored in three devices starting from (which store the number of same data, first position and last position).

Show 17 more labels / short text on this page
FNC40-FNC49 Data Operation · 16-bit Instruction · Mnemonic Operation Condition · 32-bit Instruction · 9 steps SER · 17 steps · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input FNC 61 · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 402 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 D D 1 D
Page 402 · click to enlarge
Page 402

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.2 FNC 61 – SER / Search a Data Stack

2. Operation example a) Example of search result table configuration and data
Mitsubishi Electronics MELSEC FX3S — 14.2 FNC 61 – SER / Search a Data Stack diagram (page 402)
Fig. 325 · 14.2 FNC 61 – SER / Search a Data Stack

b) Search result table

Mitsubishi Electronics MELSEC FX3S — 14.2 FNC 61 – SER / Search a Data Stack diagram (page 402)
Fig. 326 · 14.2 FNC 61 – SER / Search a Data Stack

2. 32-bit operation (DSER and DSERP)

Mitsubishi Electronics MELSEC FX3S — 2. 32-bit operation (DSER and DSERP) diagram (page 402)
Fig. 327 · 2. 32-bit operation (DSER and DSERP)

In "n" data starting from [ +1, ], same data as [ +1, ] is searched, and the search result is

stored to [ +1, ] to [ +9, +8].

DSER n S1 ‚ S2 ‚ D ‚

1. Contents of searched data and the search result a) When same data was detected

Five 32-bit devices starting from [ +1, ] store the number of same data, first position, last position, maximum value position and minimum value position. b) When same data was not detected

D 1 D D 1 D

Five 32-bit devices starting from [ +1, ] store the number of same data, first position, last position, maximum value position and minimum value position.

D 1 D D 1 D

In this case, however, "0" is stored in three devices starting from [ +1, ] (which store the number of same data, first position and last position).

D 1 D D 1 D

Page 403 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 D
Page 403 · click to enlarge
Page 403

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.2 FNC 61 – SER / Search a Data Stack 11

2. Operation example a) Example of search result table configuration and data

FNC30-FNC39 Rotation and Shift

S 1 S 1

D D D

0 3 (first position)

[ + 1, ] K100000

S 1 S 1

[ + 3, + 2] K110100 1

S 1 S 1

[ + 5, + 4] K100000 2 3

S 1 S 1

[ + 7, + 6] K 98000 3

S 1 S 1

[ + 9, + 8] K123000 4

S 1 S 1

K100000

[ + 11, + 10] K 66000 5 3

S 1 S 1

[ + 13, + 12] K100000 6 3 (last position)

S 1 S 1

[ + 15, + 14] K 95000 7

S 1 S 1

[ + 17, + 16] K910000 8 3

S 1 S 1

[ + 19, + 18] K910000 9 3

S 1 S 1

b) Search result table

Device number Contents Search result item

[ + 1, ] 3 Number of same data

D D

[ + 3, + 2] 0 Same data position (first position)

D D

FNC70-FNC79 External FX I/O Device

[ + 5, + 4] 6 Same data position (last position)

D D

[ + 7, + 6] 5 Minimum value position (last position)

D D

[ + 9, + 8] 9 Maximum value position (last position)

D D

Cautions

FNC80-FNC89 External FX Device

  • Comparison of values It is executed algebraically. (example: − 10 < 2)
  • When there are two or more maximum or minimum values When there are two or more maximum or minimum values in the searched data, the last position of the max/min is stored respectively.

FNC100-FNC109 Data Transfer 2

  • Number of occupied devices

When this instruction is driven, the following number of devices are occupied for storing the search result . Make sure that such devices are not used in other controls for the machine.

D 1 D

1)In the case of 16-bit operation

D1 D D1 D D1 D D1 D D1 D

Five devices, , +1, +2, +3 and +4, are occupied.

2)In the case of 32-bit operation

Ten devices, [ +1, ], [ +3, +2], [ +5, +4], [ +7, +6] and [ +9,

D1 D D1 D D1 D D1 D D1 D D1 D D1 D D1 D D1 D

D 1 D

+8], are occupied.

  • Note that the 32-bit value [n+1, n] is valid when D or R is specified as "n" in a 32-bit instruction. In the case of "DSER D0 D100 D200 R0", "n" is [R1, R0].

FNC140-FNC149 Data Operation 2

Show 17 more labels / short text on this page
Search result · Searched data · Comparison · data Data position · Maximum · Same Minimum · Searched device · value (example) · value · value · +9, +8 · +7, +6 · FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 404 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 D
Page 404 · click to enlarge
Page 404

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.3 FNC 62 – ABSD / Absolute Drum Sequencer

14.3 FNC 62 – ABSD / Absolute Drum Sequencer

Outline

This instruction creates many output patterns corresponding to the current value of a counter.

1. Instruction format

32-bit Instruction D 17 steps DABSD Continuous Operation

Mnemonic Operation Condition 16-bit Instruction

ABSD

2. Set data

Mitsubishi Electronics MELSEC FX3S — ABSD diagram (page 404)
Fig. 328

Head device number storing the data table (with rising and falling point data) 16- or 32-bit binary

Counter number for monitoring the current value compared with the data table 16- or 32-bit binary

n Number of lines in the table and the number of output bit devices [1 ≤ n ≤ 64] 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 404)
Fig. 329 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S2 S3 3

S1: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S3: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (ABSD) In this example, outputs are controlled to ON or OFF by one rotation (0 to 360 ° using the rotation angle signal of 1 ° /pulse).

The current value of the counter is compared with the data table with "n" lines starting from (which

D 1 S 2 D 1 S 1

occupies "n" lines × 2 devices), and consecutive "n" outputs starting from are controlled to ON or OFF during one rotation.

D 1 D

Mitsubishi Electronics MELSEC FX3S — D 1 D diagram (page 404)
Fig. 330

ABSD n S1 ‚ S2 ‚ D ‚

Mnemonic Operation Condition · 9 steps ABSD · Continuous Operation

Page 405 of the Mitsubishi Electronics MELSEC FX3S user manual — S 2 ‚ X001
Page 405 · click to enlarge
Page 405

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.3 FNC 62 – ABSD / Absolute Drum Sequencer 11

1. Write the following data to to +2n-1 in advance by a transfer instruction:

D 1 S 1 D 1 S 1

FNC30-FNC39 Rotation and Shift

Rising point Falling point

Target output Data value (example) Data value (example)

S 1 S 1 D

40 + 1 140

S 1 S 1 D

+ 2 100 + 3 200 + 1

S 1 S 1 D

+ 4 160 + 5 60 + 2

+ 6 240 + 7 280 + 3

S 1 S 1 D

S 1 S 1 D

+ 2n-2 + 2n - 1 + n − 1

For example, store rising point data and falling point data alternately.

2. Output pattern

When the command input is set to ON, "n" points starting from change as shown below.

D 1 D

Each rising point/falling point can be changed respectively by overwriting the data in to +2n − 1.

D 1 S 1 D 1 S 1

FNC70-FNC79 External FX I/O Device

2. 32-bit operation (DABSD) In this example, outputs are controlled to ON or OFF by one rotation (0 to 360 ° using the rotation angle signal of 1 ° /pulse).

FNC80-FNC89 External FX Device

The present value of the counter is compared with the data table having "n" lines starting from [ +1,

D 1 S 2 D 1 S 1

] (which occupies "n" lines × 4 devices), and consecutive "n" outputs starting from are controlled to ON or OFF during one rotation.

D 1 S 1 D 1 D

input FNC 62 DABSD n S1 ‚ S2 ‚ D ‚

FNC100-FNC109 Data Transfer 2

S 2 ‚ X001

RST

K360

Rotation angle signal of 1°/pulse

FNC140-FNC149 Data Operation 2

Show 18 more labels / short text on this page
FNC40-FNC49 Data Operation · … · … · … · ⎯ · ⎯ · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · 100 200 · +1 · +2 · 240 280 · +3 · 0 z · 180 360 · Command · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 406 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Other cautions
Page 406 · click to enlarge
Page 406

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.3 FNC 62 – ABSD / Absolute Drum Sequencer

1. Write the following data to [ , +1] to [ +4n-2, +4n-1] in advance using a transfer instruction:
Mitsubishi Electronics MELSEC FX3S — 14.3 FNC 62 – ABSD / Absolute Drum Sequencer diagram (page 406)
Fig. 331 · 14.3 FNC 62 – ABSD / Absolute Drum Sequencer

D1 S1 D1 S1 D1 S1 D1 S1

[ + 1, ] 40 [ + 3, + 2] 140

S1 D

[ + 5, + 4] 100 [ + 7, + 6] 200 +1

S1 D

[ + 9, + 8] 160 [ + 11, + 10] 60 +2

S1 D

[ + 13, + 12] 240 [ + 15, + 14] 280 +3

S1 D

[ + 4n - 3, + 4n - 4] [ + 4n - 1, + 4n - 2] + n − 1

S1 D

For example, store rising point data and falling point data alternately.

2. Output pattern

When the command input is set to ON, "n" points starting from change as shown below.

D 1 D

Each rising point/falling point can be changed respectively by overwriting the data in [ +1, ] to

D 1 S 1 D 1 S 1

Mitsubishi Electronics MELSEC FX3S — D 1 S 1 D 1 S 1 diagram (page 406)
Fig. 332

Cautions

1. Specifying a high-speed counter (C235 to C255)

In DABSD instruction, a high-speed counter can be specified as . When the high-speed counter is specified, the output pattern contains response delay caused by the scan cycle with regard to the current value of a counter. When high responsivity is required in FX3U/FX3UC PLCs, use the table high-speed comparison function offered by the HSZ instruction, or use the HSCT instruction.

D 1 S 2

2. When specifying digits of a bit device as

D 1 S 1

1. Device number Specify a multiple of 16 (0, 16, 32, 64 ...).
2. Number of digits - In ABSD instruction (16-bit operation): Only K4 is available. - In DABSD instruction (32-bit operation): Only K8 is available.

3. Other cautions

  • The value "n" determines the number of target outputs (1 ≤ n ≤ 64).
  • Even if the command input is set to OFF, the ON/OFF status of outputs does not change.
Page 407 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 S 2
Page 407 · click to enlarge
Page 407

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.4 FNC 63 – INCD / Incremental Drum Sequencer 11

14.4 FNC 63 – INCD / Incremental Drum Sequencer

FNC30-FNC39 Rotation and Shift

Outline

This instruction creates many output patterns using a pair of counters.

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

INCD −

2. Set data

Operand type Description Data type

Head word device number storing the set value 16-bit binary

S 1 ‚ S 1

Head number of counters whose current value is monitored 16-bit binary

Head bit device number to be output Bit

n Number of output bit devices [1 ≤ n ≤ 64] 16-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC70-FNC79 External FX I/O Device

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S2 S3 3

S 1 ‚ S 1

S 2 ‚ D

FNC80-FNC89 External FX Device

S1: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S3: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

FNC100-FNC109 Data Transfer 2

1. 16-bit operation (INCD)

The current value of a counter is compared with the data table having "n" lines starting from (which

D 1 S 2 D 1 S 1

occupies "n" lines x 1 device). When is equivalent to the table data, the current output is reset, and the next output is set to ON. In this way, the ON/OFF status of specified outputs is controlled in turn.

D 1 S 2

INCD n S1 ‚ S2 ‚ D ‚

FNC140-FNC149 Data Operation 2

Show 18 more labels / short text on this page
FNC40-FNC49 Data Operation · Mnemonic Operation Condition · 32-bit Instruction · 9 steps INCD · Continuous Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · n 3 3 · Command · input FNC 63 · FNC110-FNC139 Floating Point · K9999 Count signal · FNC150-FNC159 Positioning Control
Page 408 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 S 2
Page 408 · click to enlarge
Page 408

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.4 FNC 63 – INCD / Incremental Drum Sequencer

Operation

Mitsubishi Electronics MELSEC FX3S — Operation diagram (page 408)
Fig. 333 · Operation
1. Timing chart Suppose that the following data is written in advance by a transfer instruction:
Mitsubishi Electronics MELSEC FX3S — Operation diagram (page 408)
Fig. 334 · Operation

+ n − 1 ⎯ + n − 1 ⎯

2. When the command contact turns ON, the output M0 turns ON.
3. When the current value of C0 reaches the comparison value D300, the output M0 is reset. "1" is added to the count value of the process counter C1, and the current value of the counter C0 is reset.
4. The next output M1 turns ON.
5. When the current value of C0 reaches the comparison value D301, the output M1 is reset. "1" is added to the count value of the process counter C1, and the current value of the counter C0 is reset.
6. The current value is compared for up to "n (K4)" outputs in the same way (1 ≤ n ≤ 64).
7. When the final process specified by "n" is finished, the execution complete flag M8029 turns ON and remains ON for one operation cycle. M8029 is used for many instructions as the instruction execution complete flag. Use M8029 as a contact just after a corresponding instruction.
8. The program execution returns to the beginning, and outputs are repeated.

Caution

1. When specifying digits of a bit device as As a device number, specify a multiple of 16 (0, 16, 32, 64 ...).

D 1 S 1

2. Number of occupied devices

Two devices are occupied from a device specified as . Make sure not to use devices used in another control.

D 1 S 2

Page 409 of the Mitsubishi Electronics MELSEC FX3S user manual — Related instruction
Page 409 · click to enlarge
Page 409

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.5 FNC 64 – TTMR / Teaching Timer 11

14.5 FNC 64 – TTMR / Teaching Timer

FNC30-FNC39 Rotation and Shift

Outline

This instruction measures the period of time in which TTMR instruction is ON. Use this instruction to adjust the set value of a timer by a pushbutton switch.

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

TTMR −

2. Set data

Operand type Description Data type

Device number storing the teaching data 16-bit binary

n Magnification by which the teaching data is multiplied [K0 to K2/H0 to H2] 16-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FNC70-FNC79 External FX I/O Device

S 2 ‚ D

n 3

Explanation of function and operation

1. 16-bit operation (TTMR) The period of time to press and hold the command input (pushbutton switch) is measured in 1-second units, multiplied

FNC80-FNC89 External FX Device

by the magnification (10n), and then transferred to .

D 1 D

TTMR n D ‚

FNC100-FNC109 Data Transfer 2

τ0 τ0

Pressing and holding time Pressing and holding time

The table below shows the actual value indicated by depending on the magnification n and the pressing and holding time t0 (unit: 1 sec).

D 1 D

K0 τ0 × 1

K1 10τ0 × 10

FNC140-FNC149 Data Operation 2

K2 100τ0 × 100

Related instruction

There is a handy instruction as follows:

HOUR (FNC169) Measures the input contact ON time in 1-hour units, and outputs alarm when the measurement result reaches a specified value.

Show 20 more labels / short text on this page
FNC40-FNC49 Data Operation · Mnemonic Operation Condition · 32-bit Instruction · Continuous Operation · 5 steps TTMR · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · Command contact · input FNC 64 · +1 · FNC110-FNC139 Floating Point · n Magnification · Instruction Description · FNC150-FNC159 Positioning Control
Page 410 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 D
Page 410 · click to enlarge
Page 410

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.5 FNC 64 – TTMR / Teaching Timer

Cautions

1. When the command contact turns OFF

D 1 D D 1 D

The current value [ +1] of the pressing and holding time is reset, and the teaching time will not change any more.

2. Number of occupied devices

Two devices are occupied from a device specified as the teaching time . Make sure that these devices are not used in other controls for the machine.

D 1 D

  • : Teaching time

D 1 D

  • +1: Current value of the pressing and holding time

D 1 D

Program example

1. Writing the teaching time to 10 types of data registers Suppose that the set value is written to D400 to D409 in advance.
Mitsubishi Electronics MELSEC FX3S — D 1 D diagram (page 410)
Fig. 335

10 timers to be set Because the timers T0 to T9 are the 100 ms type, the actual operating time (sec) is 1/10 of the teaching data.

Selecting a timer by a digital switch An input to the 1-digit digital switch connected to X000 to X003 is converted into binary format, and transferred to Z.

Measuring the teaching time The time (sec) in which X010 is pressed and held is stored to D300.

Writing the set value of a timer The teaching time (D300) is transferred to the register D400Z for setting a timer selected by the digital switch.

Page 411 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 D
Page 411 · click to enlarge
Page 411

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.6 FNC 65 – STMR / Special Timer 11

14.6 FNC 65 – STMR / Special Timer

FNC30-FNC39 Rotation and Shift

Outline

This instruction can easily make off-delay timers, one-shot timers and flicker timers.

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

STMR −

2. Set data

Operand type Description Data type

Used timer number [T0 to T199 (100 ms timer)] 16-bit binary

S 1 ‚ S

m Set value of the timer [1 to 32,767] 16-bit binary

Head bit number to which the set value is output (Four devices are occupied.) Bit

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FNC70-FNC79 External FX I/O Device

S 1 ‚ S

m 3

S 2 ‚ D

S: "D .b" cannot be indexed with index registers (V and Z).

FNC80-FNC89 External FX Device

Explanation of function and operation

1. 16-bit operation (STMR)

The value specified in "m" is handled as the set value of a timer specified in , and output to four devices starting

D 1 S

from . Create a proper program according to the purpose while referring to the example shown below.

D 1 D

FNC100-FNC109 Data Transfer 2

STMR m S ‚ D ‚

Off-delay timer and one-shot timer

When T10 is set to , and M0 is set to

D 1 S D 1 D

STMR T10 K100 M0

  • M0 [ ] : Off-delay timer which turns OFF with delay of the timer set value after the command contact

D 1 D

FNC140-FNC149 Data Operation 2

  • M1 [ +1] : One-shot timer which turns ON after the command contact turned OFF from ON, and turns OFF

D 1 D

after the timer set value

D 1 D

  • M2 [ +2] : Occupied, and can be used for flicker.
  • M3 [ +3] : Occupied.

D 1 D

Show 19 more labels / short text on this page
FNC40-FNC49 Data Operation · Mnemonic Operation Condition · 32-bit Instruction · 7 steps STMR · Continuous Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · and Type · Unit Index Con- stant · Real Number · Charac- ter String Pointer · Command · input · FNC110-FNC139 Floating Point · Command · input FNC 65 · turned OFF · FNC150-FNC159 Positioning Control
Page 412 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. When the command contact is set to OFF
Page 412 · click to enlarge
Page 412

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.6 FNC 65 – STMR / Special Timer

Mitsubishi Electronics MELSEC FX3S — 14.6 FNC 65 – STMR / Special Timer diagram (page 412)
Fig. 336 · 14.6 FNC 65 – STMR / Special Timer

Flicker

In the program shown below which turns OFF STMR instruction at the NC contact of +3, flicker is output to

D 1 D

Mitsubishi Electronics MELSEC FX3S — D 1 D diagram (page 412)
Fig. 337
  • M0 [ ] : Occupied (, and can be used for off-delay timer). (Refer to the previous page.)
  • M1 [ +1] : Flicker (NO contact) which turns ON and OFF repeatedly at the interval of timer set value
  • M2 [ +2] : Flicker (NC contact) which turns ON and OFF repeatedly at the interval of timer set value

Cautions

1. Handling of a specified timer The timer number specified in this instruction cannot be used in other general circuits (such as OUT instruction). If the timer number is used in other general circuits, the timer malfunctions.

2. Number of occupied devices

Four devices are occupied from a device specified in . Make sure that these devices are not used in other controls for the machine.

D 1 D

Mitsubishi Electronics MELSEC FX3S — D 1 D diagram (page 412)
Fig. 338

3. When the command contact is set to OFF

D1 D D1 D D1 D D1 D D1 S

, +1 and +3 will turn OFF after the set time. +2 and the timer are immediately reset.

Page 413 of the Mitsubishi Electronics MELSEC FX3S user manual — 14.7 FNC 66 – ALT / Alternate State 11
Page 413 · click to enlarge
Page 413

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.7 FNC 66 – ALT / Alternate State 11

Mitsubishi Electronics MELSEC FX3S — 14.7 FNC 66 – ALT / Alternate State 11 diagram (page 413)
Fig. 339 · 14.7 FNC 66 – ALT / Alternate State 11

This instruction alternates a bit device (from ON to OFF or from OFF to ON) when the input turns ON.

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available.

Every time the command input turns from OFF to ON, a bit device specified in is alternated (from ON to OFF or from OFF to ON).

Dividing output (by 2-step alternating output) Multi-step dividing outputs are achieved by combination of two or more ALTP instructions.

Page 414 of the Mitsubishi Electronics MELSEC FX3S user manual — M 1
Page 414 · click to enlarge
Page 414

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.7 FNC 66 – ALT / Alternate State

Caution

1. When using (continuous operation type) ALT instruction

  • When ALT instruction is used, a specified bit device is alternated in every operation cycle. To alternate a specified device by turning the command ON or OFF, use the (pulse operation type) ALTP instruction, or use a pulse operation type command contact such as LDP.

Program examples

1. Start and stop by one input

1. When the pushbutton switch X000 is pressed, the start output Y001 is set to ON.
2. When the pushbutton switch X000 is pressed again, the stop output Y000 is set to ON.
Mitsubishi Electronics MELSEC FX3S — Program examples diagram (page 414)
Fig. 340 · Program examples

2. Flicker operation

1. When the input X006 is set to ON, the contact of the timer T2 turns ON instantaneously every 5 seconds.
2. Every time the contact of T2 turns ON, the output Y007 is set to ON or OFF alternately.
Mitsubishi Electronics MELSEC FX3S — 2. Flicker operation diagram (page 414)
Fig. 341 · 2. Flicker operation

5 sec 5 sec 5 sec 5 sec 5 sec 5 sec 5 sec

3. Alternating output operation using auxiliary relays (M) (operation equivalent to ALT instruction) The circuit below is provided as an example of alternating operation using basic instructions and auxiliary relays (M) which is equivalent to ALT instruction.
1. When X000 is set to ON, M0 turns ON and remains ON for only one operation cycle.
2. When M0 turns ON for the first time, Y000 is latched. When M0 turns ON the second time, Y000 becomes unlatched.

M 1

M 0

M 1

M 0 Y000

Y000

M 0 Y000

Page 415 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 D D 1 S 1
Page 415 · click to enlarge
Page 415

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.8 FNC 67 – RAMP / Ramp Variable Value 11

14.8 FNC 67 – RAMP / Ramp Variable Value

FNC30-FNC39 Rotation and Shift

Outline

This instruction obtains the data which changes between the start value (initial value) and the end value (target value) over the specified "n" times.

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

RAMP −

2. Set data

Operand type Description Data type

S 1 ‚ S 1

Device number storing the initial value of ramp 16-bit binary

Device number storing the target value of ramp 16-bit binary

Device number storing the current value of ramp 16-bit binary

n Ramp transfer time (scan) [1 to 32, 767] 16-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC70-FNC79 External FX I/O Device

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S 1 ‚ S 1

S 2 ‚ D

n 3 S 3 3

FNC80-FNC89 External FX Device

S: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (RAMP)

When the start value and the end value have been specified and the command input is set to ON, the

D 1 S 1 D 1 S 2

value obtained by adding a value divided equally by "n" times to in every operation cycle is stored to . By combining this instruction and an analog output, the cushion start/stop command can be output.

D 1 S 1 D 1 D

FNC100-FNC109 Data Transfer 2

RAMP n S1 ‚ S2 ‚ D ‚

S 1 ‚ S 1 ‚

S 2 ‚ S 2 ‚

1. In the case of " < "
2. In the case of " > "

FNC140-FNC149 Data Operation 2

Number of scans +1

D ‚ Number of scans +1 D ‚

D 1 D

  • The number of scans ("0" to "n") is stored in +1.
  • The time from start to the end value is the operation cycle multiplied by "n" times.
  • If the command input is set to OFF in the middle of operation, execution is paused. (The present data value stored

in is held, and the number of scans stored in +1 is cleared.) When the command input is set to ON

D 1 D D 1 D

again, is cleared, and the operation is started from .

D 1 D D 1 S 1

Show 18 more labels / short text on this page
FNC40-FNC49 Data Operation · Mnemonic Operation Condition · 32-bit Instruction · 9 steps RAMP · Continuous Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input FNC 67 · FNC110-FNC139 Floating Point · "n" scans · "n" scans · FNC150-FNC159 Positioning Control
Page 416 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 D
Page 416 · click to enlarge
Page 416

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.8 FNC 67 – RAMP / Ramp Variable Value

  • After transfer is completed, the instruction execution complete flag M8029 turns ON, and the value is

D 1 D

Mitsubishi Electronics MELSEC FX3S — D 1 D diagram (page 416)
Fig. 342
  • When acquiring the operation result at a constant time interval (constant scan mode) Write a prescribed scan time (which is longer than the actual scan time) to D8039 and set M8039 to ON to select the constant scan mode in the PLC.

For example, when "20 ms" is written to D8039 and "n" is set to 100, the value will change from to

D 1 D D 1 S 1

D 1 S 2

in 2 seconds.

2. Operation of the mode flag (M8026)

In FX3U/FX3UC PLCs, the contents of are changed as follows depending on the ON/OFF status of the mode flag M8026.

D 1 D

In FX3S/FX3G/FX3GC PLCs, the contents of are same as the case "2) When M8026 is ON" below regardless of the ON/OFF status of the mode flag M8026.

D 1 D

1. When M8026 is OFF 2) When M8026 is ON
Mitsubishi Electronics MELSEC FX3S — D 1 D diagram (page 416)
Fig. 343
Mitsubishi Electronics MELSEC FX3S — D 1 D diagram (page 416)
Fig. 344

Related devices

→ For the instruction execution complete flag use method, refer to Subsection 6.5.2.

Mitsubishi Electronics MELSEC FX3S — Related devices diagram (page 416)
Fig. 345 · Related devices

M8029 Instruction execution complete Turns ON when becomes equivalent to after "n" operation cycles.

M8026*1 RAMP mode Refer to the operation of the mode flag M8026 described above.

*1. M8026 is available only in FX3U/FX3UC PLCs, and is cleared when the PLC mode switches from RUN to STOP.

Caution

1. When specifying a latched (battery backed) type device as

D 1 D

When setting PLC to the RUN mode while the command input is ON, clear in advance.

D 1 D

Page 417 of the Mitsubishi Electronics MELSEC FX3S user manual — 14.9 FNC 68 – ROTC / Rotary Table Control
Page 417 · click to enlarge
Page 417

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.9 FNC 68 – ROTC / Rotary Table Control 11

Mitsubishi Electronics MELSEC FX3S — 14.9 FNC 68 – ROTC / Rotary Table Control 11 diagram (page 417)
Fig. 346 · 14.9 FNC 68 – ROTC / Rotary Table Control 11

14.9 FNC 68 – ROTC / Rotary Table Control

This instruction is suitable for efficient control of the rotary table for putting/taking a product into/out of the rotary table.

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S: "D .b" cannot be indexed with index registers (V and Z).

Page 418 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 S D 1 D
Page 418 · click to enlarge
Page 418

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.9 FNC 68 – ROTC / Rotary Table Control

Explanation of function and operation

1. 16-bit operation (ROTC)

D 1 S D 1 D

The table rotation is controlled by "m2", and so that a product can be efficiently put into or taken out of the rotary table divided into "m1" (=10) sections as shown in the figure below.

Mitsubishi Electronics MELSEC FX3S — D 1 S D 1 D diagram (page 418)
Fig. 347

Set them in advance using a transfer instruction. + 1 Sets the port No. to be called.

+ 2 Sets the product No. to be called.

Construct an internal contact circuit in advance which is driven by the input signal (X)

Page 419 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 S
Page 419 · click to enlarge
Page 419

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.9 FNC 68 – ROTC / Rotary Table Control 11

Operation conditions

FNC30-FNC39 Rotation and Shift

The conditions required to use this instruction are as shown in the example below.

1. Rotation detection signal: X → - Provide a 2-phase switch (X000 and X001) for detecting the rotation direction (forward or backward) of the table and the switch X002 which turns ON when the product No. 0 reaches the port No. 0. - Create the sequence program shown below.

D 1 D

M0

Up-counting signal during forward rotation

M1

M2

Zero point detection switch

X000 to X002 are replaced with internal contacts of to +2. An arbitrary head device number can be specified by X or .

D D

2. Specification of a register for counting:

D 1 S

The counter detects which number of product is located at the port No. 0.

D 1 S

3. Registers specifying the calling condition: +1 and +2

D 1 S D 1 S

a) Set the port No. to be called in +1.

D 1 S

b) Set the product No. to be called in +2.

D 1 S

FNC70-FNC79 External FX I/O Device

4. Number of divisions m1 and number of low-speed sections m2 Specify the number of divisions m1 of the table, and number of low-speed sections m2.

When the above conditions are specified, forward/backward rotation and high-speed/low-speed/stop are output to

D1 D D1 D D1 D

+3 to +7 specified by the head device .

FNC80-FNC89 External FX Device

Cautions

1. Operations caused by the command input ON/OFF status

  • When the command input is set to ON and this instruction is executed, the result will be automatically output to

D 1 D D 1 D

+3 to +7.

  • When the command input is set to OFF, +3 to +7 are set to OFF accordingly.

D 1 D D 1 D

FNC100-FNC109 Data Transfer 2

2. Multiple activation of the rotation detection signal ( to +2) in one division

D 1 D D 1 D

For example, when the rotation detection signal ( to +2) is activated 10 times in one division, set a value multiplied by "10" to each division, port No. to be called and product No. to be called. As a result, an intermediate value of the division number can be set to a low-speed section.

D 1 D D 1 D

3. Zero point detection signal When the zero point detection signal (M2) turns ON while the command input is ON, the contents of the register for

D 1 D

counting are cleared to "0". This clear operation should be executed before starting the operation.

D 1 S

FNC140-FNC149 Data Operation 2

Show 10 more labels / short text on this page
FNC40-FNC49 Data Operation · 2-phase switch · A phase · +1 · B phase · +2 · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 420 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 D
Page 420 · click to enlarge
Page 420

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.10 FNC 69 – SORT / SORT Tabulated Data

14.10 FNC 69 – SORT / SORT Tabulated Data

Outline

This instruction sorts a data table consisting of data (lines) and group data (columns) based on a specified group data (column) sorted by line in ascending order. This instruction stores the group data (columns) in serial devices. On the other hand, SORT2 (FNC149) instruction stores the data (lines) in serial devices facilitating the addition of data (lines), and sorts a table in either ascending or descending order.

→ For SORT2 (FNC149) instruction, refer to Section 19.7.

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

SORT −

2. Set data

Mitsubishi Electronics MELSEC FX3S — SORT − diagram (page 420)
Fig. 348

Head device number storing the data table [which occupies m1 × m2 points]

m2 Number of group data (columns) [1 to 6]

Head device number storing the operation result [which occupies m1 × m2 points]

n Column number of the group data (column) used as the basis of sorting [1 to m2]

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 420)
Fig. 349 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 16-bit operation (SORT)

In the data table (sorting source) having (m1 × m2) points from , data lines are sorted in the ascending order based on the group data in the column No. "n", and the result is stored in the data table (sorting result) having (m1 ×

D 1 S

m2) points from .

D 1 D

→ For operation examples, refer to the next page.

Mitsubishi Electronics MELSEC FX3S — D 1 D diagram (page 420)
Fig. 350

M{{ Instruction execution complete flag for SORT instruction

Show 4 more labels / short text on this page
Mnemonic Operation Condition · 32-bit Instruction · 11 steps SORT · Continuous Operation
Page 421 of the Mitsubishi Electronics MELSEC FX3S user manual — D D D D
Page 421 · click to enlarge
Page 421

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.10 FNC 69 – SORT / SORT Tabulated Data 11

  • The data table configuration is explained in an example in which the sorting source data table has 3 lines and 4

FNC30-FNC39 Rotation and Shift

columns (m1 = K3, m2 = K4). For the sorting result data table, understand as .

D 1 S D 1 D

Column No. Number of groups (m2 = K4)

1 2 3 4

Line No. Control number Height Weight Age

1 +3 +6 +9

S

data m1 = K3

2 +1 +4 +7 +10

S

3 +2 +5 +8 +11

S

  • When the command input turns ON, data sorting is started. Data sorting is completed after "m1" scans, and the instruction execution complete flag M8029 is set to ON.

→ For the instruction execution complete flag use method, refer to Subsection 6.5.2.

2. Operation examples When the instruction is executed with "n = K2 (column No. 2)" and "n = K3 (column No. 3) for the following sorting source data, the operations shown below are acquired. It is recommended to put a serial number such as a control number in the first column so that the original line number can be estimated based on the contents.

Sorting source data

Column No. Number of groups (m2 = K4)

1 2 3 4

Line No. Control number Height Weight Age

1 + 5 + 10 + 15

S

1 150 45 20

FNC70-FNC79 External FX I/O Device

2 + 1 + 6 + 11 + 16

S

2 180 50 40

data m1 = K5

3 + 2 + 7 + 12 + 17

S

3 160 70 30

4 + 3 + 8 + 13 + 18

S

4 100 20 8

FNC80-FNC89 External FX Device

5 + 4 + 9 + 14 + 19

S

5 150 50 45

1. Sorting result when the instruction is executed with "n = K2 (column No. 2)"

Column No. 1 2 3 4

Line No. Control number Height Weight Age

FNC100-FNC109 Data Transfer 2

1 + 5 + 10 +15

D

4 100 20 8

2 + 1 + 6 + 11 + 16

D

1 150 45 20

D

3 + 2 + 7 + 12 + 17

5 150 50 45

4 + 3 + 8 + 13 + 18

D

3 160 70 30

5 + 4 + 9 + 14 + 19

D

2 180 50 40

FNC140-FNC149 Data Operation 2

Show 7 more labels / short text on this page
Number of · FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Number of · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 422 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 S
Page 422 · click to enlarge
Page 422

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

14 Handy Instruction – FNC 60 to FNC 69

14.10 FNC 69 – SORT / SORT Tabulated Data

2. Sorting result when the instruction is executed with "n = K3 (column No. 3)"
Mitsubishi Electronics MELSEC FX3S — 14.10 FNC 69 – SORT / SORT Tabulated Data diagram (page 422)
Fig. 351 · 14.10 FNC 69 – SORT / SORT Tabulated Data

2 + 1 + 6 + 11 + 16

3 + 2 + 7 + 12 + 17

4 + 3 + 8 + 13 + 18

5 + 4 + 9 + 14 + 19

Related device

→ For the instruction execution complete flag use method, refer to Subsection 6.5.2.

M8029 Instruction execution complete Turns ON when sorting is completed.

Cautions

  • Do not change the contents of operands and data while the instruction is executed.
  • Before executing the instruction again, set the command input to OFF.
  • Limitation in the number of instructions Only one instruction can be used in a program.
  • When the same device is specified in and The source data is overwritten by the data acquired by sorting.

D 1 S D 1 D

Take special care so that the contents of are not changed until execution is completed.

D 1 S

Device Name Description

Page 423 of the Mitsubishi Electronics MELSEC FX3S user manual — D S PR
Page 423 · click to enlarge
Page 423

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

FNC30-FNC39 Rotation and Shift

15. External FX I/O Device – FNC 70 to FNC 79

FNC 70 to FNC 79 provide instructions to receive data from and send data to external devices mainly using inputs and outputs in PLC. Because these instructions easily achieve complicated controls with a minimum required sequence program and external wiring, they are similar to handy instructions described in the preceding chapter. FROM and TO instructions, essential for controlling special units and special blocks, are included in this group. (In FX3U and FX3UC PLCs, transfer can be also executed using a MOV instruction.)

FNC No. Mnemonic Symbol Function Reference

70 TKY Ten Key Input Section 15.1

TKY D1 D2 S

71 HKY Hexadecimal Input Section 15.2

D3 HKY D2 D1 S

72 DSW Digital switch (thumbwheel input) Section 15.3

n DSW D2 D1 S

73 SEGD Seven Segment Decoder Section 15.4

D S SEGD

74 SEGL Seven Segment With Latch Section 15.5

SEGL D n S

FNC70-FNC79 External FX I/O Device

75 ARWS Arrow Switch Section 15.6

n ARWS D2 D1 S

76 ASC ASCII code data input Section 15.7

D ASC S

FNC80-FNC89 External FX Device

77 PR Print (ASCII Code) Section 15.8

D S PR

78 FROM Read From A Special Function Block Section 15.9

n FROM D m2 m1

79 TO Write To A Special Function Block Section

n TO S m2 m1

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 5 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 424 of the Mitsubishi Electronics MELSEC FX3S user manual — D 2 D 2
Page 424 · click to enlarge
Page 424

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.1 FNC 70 – TKY / Ten Key Input

15.1 FNC 70 – TKY / Ten Key Input

Outline

This instruction sets data for timers and counters through ten key inputs ranging from "0" to "9".

1. Instruction format

TKY D TKY

2. Set data

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 424)
Fig. 352 · 1. Instruction format

Head bit device number from which one of the ten keys is input [10 devices are occupied] Bit

Word device number storing the data 16- or 32-bit binary

Head bit device number storing the key pressing information [11 devices are occupied] Bit

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 424)
Fig. 353 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

S: "D .b" cannot be indexed with index registers (V and Z).

Explanation of function and operation

1. 16-bit operation (TKY)

D 1 S S

stores a numeric value input from to +9 connected to the ten keys. Output information for key

pressing and key sensing are output to to +10.

D 2 D 2

1. Input numeric value - When an input value is larger than "9999", it overflows from the most significant digit. - An input numeric value is stored in binary format. - When the ten keys are pressed in the order "[1] → [2] → [3] → [4]" in the figure shown on the next page, "2130"

is stored in .

Show 8 more labels / short text on this page
16-bit Instruction · Mnemonic Operation Condition · 32-bit Instruction · Mnemonic Operation Condition · 7 steps · Continuous Operation DTKY · 13 steps · Continuous Operation
Page 425 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 D 2 D 2
Page 425 · click to enlarge
Page 425

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.1 FNC 70 – TKY / Ten Key Input 11

2. Key pressing information [ to +10]

D 2 D 2

FNC30-FNC39 Rotation and Shift

- For the key pressing information, to +9 turn ON or OFF according to the pressed keys.

D 2 D 2

- For the key sensing output, +10 turns ON when any key is pressed.

TKY D1 ‚ S ‚ D2 ‚

Input form ten keys

The figure below shows an example of FX3U PLC (sink input). For wiring details, refer to the following manual.

→ FX3U Hardware Edition. → FX3UC Hardware Edition.

5 6 7 8 1 2 3 4 0 9

S ‚ 0V 24V +8

S ‚ S ‚

Output information for key

S/S

PLC

FNC70-FNC79 External FX I/O Device

[1] [2] [3] [4]

"2130" is stored in .

2. 32-bit operation (DTKY)

FNC80-FNC89 External FX Device

[ +1, ] store a numeric value input from to +9 connected to the ten keys.

D 1 D 1 S S

Output information for key pressing and key sensing are output to to +10.

D 2 D 2

1. Input numeric value [ ] - When an input value is larger than "99,999,999", it overflows from the most significant digit. - An input numeric value is stored in binary format.

FNC100-FNC109 Data Transfer 2

2. Key pressing information [ to +10]

D 2 D 2

- For the key pressing information, to +9 turn ON or OFF according to the pressed keys.

D 2 D 2

- For the key sensing output, +10 turns ON when any key is pressed.

DTKY D1 ‚ S ‚ D2 ‚

For the ten-key connection example and key pressing information, refer to the 16-bit operation (TKY) shown above.

Cautions

1. When two or more keys are pressed at the same time In such a case, only the first key pressed is valid.

FNC140-FNC149 Data Operation 2

2. When the command contact turns OFF

Though the contents of do not change, all of to +10 turn OFF.

D 1 D 2 D 2

Show 26 more labels / short text on this page
Command · input FNC 70 · [4] · +1 · [2] · FNC40-FNC49 Data Operation · +2 · [1] · +3 · [3] · Ten keys → · +9 · FNC50-FNC59 High-Speed Processing · pressing information · +9 · +1 · FMC60-FNC69 Handy Instruction · +2 · +3 · +9 · +10 · Key sensing output · Command · input FNC 70 · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 426 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Timing chart
Page 426 · click to enlarge
Page 426

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.1 FNC 70 – TKY / Ten Key Input

3. Number of occupied device

1. Ten bit devices are occupied from for connecting the ten keys. Because these devices are occupied even if the ten keys are not connected, they cannot be used for any other purpose.
2. Eleven bit devices are occupied from for outputting the key pressing information. Make sure that these devices are not used in other controls for the machine.

- to +9: Turn ON or OFF according to input of the ten keys "0" to "9".

D 2 D 2

- +10: Is ON while either one among "0" to "9" keys is pressed (key sensing output).

4. Limitation in the number of instructions The TKY or DTKY instruction can only be used once in a program. When the TKY and/or DTKY instruction need to be used two or more times, use the indexing (V, Z) function.

Program example

In the program example shown below, the input X000 is set as the head bit device, and the ten keys "0" to "9" are connected.

1. Program

D 1 ‚ S ‚ D 2 ‚

X000 D0 M10 FNC 70

TKY

2. Connection diagram This connection diagram shows an example of FX 3U PLC (sink input). For wiring details, refer to the following manual.

→ FX 3U Hardware Edition → FX 3UC Hardware Edition

Mitsubishi Electronics MELSEC FX3S — → FX 3U Hardware Edition → FX 3UC Hardware Edition diagram (page 426)
Fig. 354 · → FX 3U Hardware Edition → FX 3UC Hardware Edition

S/S X000 X001 X002 X003 X005 X004 X006 X007

3. Timing chart

Mitsubishi Electronics MELSEC FX3S — 3. Timing chart diagram (page 426)
Fig. 355 · 3. Timing chart
1. When the ten keys are pressed in the order "[1] → [2] → [3] → [4]" shown in the figure, "2130" is stored in (D0). When an input value is larger than "9999", it overflows from the most significant digit. (An input numeric value is stored in binary format in D0).
2. When X002 is pressed, M12 turns ON and remains ON until another key is pressed. Other keys work in the same way. In this way, M10 to M19 turn ON and OFF according to the inputs X000 to X011.
3. When pressing a key, the key sensing output M20 is ON only while it is pressed.
Page 427 of the Mitsubishi Electronics MELSEC FX3S user manual — D 3 D 3 D 3
Page 427 · click to enlarge
Page 427

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.2 FNC 71 – HKY / Hexadecimal Input 11

15.2 FNC 71 – HKY / Hexadecimal Input

FNC30-FNC39 Rotation and Shift

Outline

This instruction multiplexes four X-devices and four Y-devices to allow for 16 key (0 to F) 4-digit (byte) input. Keys 0 to 9 stores numerical values, and keys A to F represent function keys. When the extension function is set to ON, hexadecimal keys 0 to F all store their corresponding numerical values.

1. Instruction format

HKY D

HKY

2. Set data

Operand Type Description Data Type

Head X device number to be used (Four devices occupied.) Bit

Head Y device number to be used (Four devices occupied.) Bit

Device number storing the numerical input from the 16 keys 16- or 32-bit binary

Head bit device number storing the key pressing information (Eight devices are occupied.) Bit

3. Applicable devices

Bit Devices Word Devices Others

FNC70-FNC79 External FX I/O Device

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

FNC80-FNC89 External FX Device

S: "D .b" cannot be indexed with index registers (V and Z).

Explanation of function and operation

FNC100-FNC109 Data Transfer 2

1. 16-bit operation (HKY)

signals [ to +3] and [ to +3] connected to the 16 key input (0 to F) are scanned.

S S D 1 D 1

When a key 0 to 9 is pressed, the corresponding numeric value is shifted into from the least significant byte, and

+7 turns ON.

When a key A to F is pressed, the corresponding key press information bit [ to +5] turns ON, and +6 turns ON.

D 3 D 3 D 3

HKY D1 ‚ S ‚ D2 ‚ D3 ‚

FNC140-FNC149 Data Operation 2

Show 20 more labels / short text on this page
FNC40-FNC49 Data Operation · 16-bit Instruction · Mnemonic Operation Condition · 32-bit Instruction · Mnemonic Operation Condition · Continuous Operation DHKY · Continuous Operation · 9 steps · 17 steps · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · FNC110-FNC139 Floating Point · Command · input FNC 71 · FNC150-FNC159 Positioning Control
Page 428 of the Mitsubishi Electronics MELSEC FX3S user manual — 1. 16-bit operation (HKY)
Page 428 · click to enlarge
Page 428

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.2 FNC 71 – HKY / Hexadecimal Input

1. Input of a numeric value through keys 0 to 9: - When an input value is larger than "9999", it overflows from the most significant digit.

- The numeric value input is stored to in binary.

- The key sensing output +7 turns ON when any key 0 to 9 is pressed.

2. Key pressing information for the keys A to F:

- Six devices starting from corresponding to keys A through F turn ON.

Mitsubishi Electronics MELSEC FX3S — 15.2 FNC 71 – HKY / Hexadecimal Input diagram (page 428)
Fig. 356 · 15.2 FNC 71 – HKY / Hexadecimal Input

- The key sensing output +6 turns ON when any key A through F is pressed.

2. 32-bit operation (DHKY)

Signals [ to +3] and [ to +3] connected to the 16 key input (0 to F) are scanned.

S S D 1 D 1

When a key 0 to 9 is pressed, the corresponding numeric value is shifted into [ +1, ] from the least

D 2 D 2

significant byte, and +7 turns ON.

When a key A to F is pressed, the corresponding key press information bit [ to +5] turns ON. and

D 3 D 3

+6 turns ON.

DHKY D1 ‚ S ‚ D2 ‚ D3 ‚

1. Input of a numeric value through keys 0 to 9: - When an input value is larger than "99,999,999", it overflows from the most significant digit.

- The numeric value input is stored to [ +1, ] in binary.

D 2 D 2

- The key sensing output +7 turns ON when any key 0 to 9 is pressed.

2. Key pressing information for the keys A to F:

Six devices starting from corresponding to keys A to F turn ON.

The key sensing output +6 turns ON when any key A to F is pressed.

Extension function

When M8167 is set to ON making the extension function valid, the numerical values for keys 0 to F are stored in binary. When the extension function is valid, the function and operation are the same except for the following.

1. 16-bit operation (HKY)

Hexadecimal numerical value data input using keys 0 to F is shifted into from the least significant byte.

1. Input of a numeric value using keys 0 to F: - When the input value is larger than "FFFF", it overflows from the most significant digit. - Example:

When "1 → 2 → 3 → B → F" is input, numerical value "23BF" is stored in in binary. "1" overflows when "F" is input.

Mitsubishi Electronics MELSEC FX3S — 1. 16-bit operation (HKY) diagram (page 428)
Fig. 357 · 1. 16-bit operation (HKY)

D1 ‚ S ‚ D2 ‚ D3 ‚

Command · input FNC 71

Page 429 of the Mitsubishi Electronics MELSEC FX3S user manual — D 3 D 3
Page 429 · click to enlarge
Page 429

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.2 FNC 71 – HKY / Hexadecimal Input 11

2. 32-bit operation (DHKY)

FNC30-FNC39 Rotation and Shift

Hexadecimal numerical value data input using keys 0 to F is shifted into [ +1, ] from the least significant byte.

D 2 D 2

1. Input of a numeric value using keys 0 to F: - When the input value is larger than "FFFFFFFF", it overflows from the most significant digit. - Example:

When "9 → 2 → 3 → B → F → A → F" is input, numerical value "923BFAF" is stored in [ +1, ] in binary.

D 2 D 2

M8167

D1 ‚ S ‚ D2 ‚ D3 ‚

DHKY

Related devices

→ For the instruction execution complete flag use method, refer to Subsection 6.5.2.

Turns ON/OFF the hexadecimal data handling function of HKY (FNC 71) instruction. OFF: Ten-keys and function keys ON: Hexadecimal keys

M8167 Extension function flag

D 1 D 1

M8029 Instruction execution com-

OFF: Data is being output to to +3 or the instruction is not executed yet.

ON: A cycle operation of outputting data to to +3 (scan of the keys 0 to F) is completed.

D 1 D 1

FNC70-FNC79 External FX I/O Device

Cautions

1. Limitation in the number of instructions The HKY or DHKY instruction can only be used once in a program. When the TKY and/or DTKY instruction should be used two or more times, use the indexing (V, Z) function.
2. When two or more keys are pressed at the same time In such a case, the first key pressed is valid.

FNC80-FNC89 External FX Device

3. When the command contact turns OFF

Though the contents of do not change, to +7 turn OFF.

D 2 D 3 D 3

4. Number of devices occupied

1. Four devices are occupied from the head X device for connecting 16 keys.

FNC100-FNC109 Data Transfer 2

2. Four devices are occupied from the head Y device for connecting 16 keys.
3. Eight devices are occupied from the head device for outputting the key pressing information. Make sure that these devices are not used by other machine controls.
- to +5Key pressing information for the keys A to F

D 3 D 3

- +6Key sensing output for the keys A to F
- +7Key sensing output for the keys 0 to 9
5. Key input receiving timing HKY and DHKY instructions are executed in synchronization with the operation cycle of the PLC. 8 scan cycles are required to finish reading the keys. To prevent key input receiving errors caused by the filter delay, utilize the "constant scan mode" and "timer interrupt" function.

FNC140-FNC149 Data Operation 2

6. Caution on use in timer interrupt programs When the HKY instruction is used in a timer interrupt program, it turns ON M8029 in the interrupt program.

→ For details, refer to Subsection 36.5.2.

7. Output format Use a transistor output type PLC.
Show 9 more labels / short text on this page
FNC40-FNC49 Data Operation · Command · input · FNC50-FNC59 High-Speed Processing · Device Name Description · FMC60-FNC69 Handy Instruction · plete flag · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 430 of the Mitsubishi Electronics MELSEC FX3S user manual — → FX 3U Hardware Edition → FX 3UC Hardware Edition
Page 430 · click to enlarge
Page 430

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.2 FNC 71 – HKY / Hexadecimal Input

Program example

D1 ‚ S ‚ D2 ‚ D3 ‚

X004 FNC 71

HKY X000 Y000 D 0 M 0

The figure below shows an example of the FX3U series main unit (sink input/sink output). For wiring details, refer to the following manual.

→ FX 3U Hardware Edition → FX 3UC Hardware Edition

Mitsubishi Electronics MELSEC FX3S — → FX 3U Hardware Edition → FX 3UC Hardware Edition diagram (page 430)
Fig. 358 · → FX 3U Hardware Edition → FX 3UC Hardware Edition
Page 431 of the Mitsubishi Electronics MELSEC FX3S user manual — D 2 D 2
Page 431 · click to enlarge
Page 431

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.3 FNC 72 – DSW / Digital Switch (Thumbwheel Input) 11

15.3 FNC 72 – DSW / Digital Switch (Thumbwheel Input)

FNC30-FNC39 Rotation and Shift

Outline

This instruction reads the set value of digital switches. This instruction can read a set of 4 digits (n = K1) or two sets of 4 digits (n = K2).

1. Instruction format

32-bit Instruction Mnemonic Operation Condition

DSW DSW

Continuous Operation −

2. Set data

Operand Type Description Data Type

Head device (X) number connected to a digital switch (Four devices are occupied.) Bit

Head device (Y) number to which the strobe signal is output (Four devices are occupied.) Bit

Device number storing the numeric value of a digital switch ("n" devices are occupied.) 16-bit binary

n Total number of 4-digit switch sets (4 digits/set) (n = 1 or 2) 16-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC70-FNC79 External FX I/O Device

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 3 3 S1 S2 3 3 3

FNC80-FNC89 External FX Device

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

FNC100-FNC109 Data Transfer 2

1. 16-bit operation (DSW)

The value of each digital switch connected to is input by the time division method (in which the value is input in

turn from the 1st digit by the output signal at the interval of 100 ms), and stored to .

D 1 ‚ S ‚ D 2 ‚

1. Data - A numeric value from 0 to 9999 (up to 4 digits) can be read. - A numeric value is stored in binary format.

- The first set is stored to , and the second set is stored to +1.

D 2 D 2

FNC140-FNC149 Data Operation 2

Show 19 more labels / short text on this page
FNC40-FNC49 Data Operation · 16-bit Instruction · Mnemonic Operation Condition · 9 steps · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · n 3 3 · Strobe · Command · signal · input · DSW n · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 432 of the Mitsubishi Electronics MELSEC FX3S user manual — X000 FNC 72
Page 432 · click to enlarge
Page 432

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.3 FNC 72 – DSW / Digital Switch (Thumbwheel Input)

2. Specification of the number of sets ("n") - When using one set of 4 digits [n = k1]

A 4-digit BCD digital switch connected to to +3 is read in turn by the strobe signal to

S S D 1

+3, and stored in binary format to . - When using two sets of 4 digits [n = k2]

D 1 D 2

A 4-digit BCD digital switch connected to to +3 is read in turn by the strobe signal to

S S D 1

D 1 D 2

+3, and stored in binary format to .

A 4-digit BCD digital switch connected to +4 to +7 is read in turn by the strobe signal to

S S D 1

D 1 D 2

+3, and stored in binary format to +1.

Related devices

→ For the instruction execution complete flag use method, refer to Subsection 6.5.2.

Mitsubishi Electronics MELSEC FX3S — Related devices diagram (page 432)
Fig. 359 · Related devices

OFF: Data is being output to to +3 or the instruction is not executed yet.

ON: A cycle operation of outputting data to to +3 (scan of the 1st to 4th digits) is completed.

Cautions

1. When the command contact turns OFF

Though the contents of do not change, all of to +3 turn OFF.

D 2 D 1 D 1

2. Number of occupied devices

1. When two sets of 4 digits (n = K2) are used, two devices are occupied starting from .
2. When one set of 4 digits is used, four devices are occupied starting from . When two sets of 4 digits are

used, eight devices are occupied starting from .

3. When connecting a digital switch of up to 3 digits

It is not necessary to wire the strobe signal (output for digit specification) to unused digits. Because unused digits are occupied also by this instruction, however, they cannot be used for any other purpose. Make sure to leave unused outputs are left vacant.

4. Transistor output type is recommended For continuously receiving digital switch values, make sure to use a transistor output type PLC.

→ For a relay type PLC, refer to "4. How to use this instruction in a relay output type PLC" later.

5. Digital switches Use BCD output type digital switches.

Program example

In the program example shown below, digital switches are connected to inputs starting from X010 and outputs from Y010.

1. Program

n D1 ‚ S ‚ D2 ‚

X000 FNC 72

DSW X010 Y010 D 0 K 1

Page 433 of the Mitsubishi Electronics MELSEC FX3S user manual — SET M 0
Page 433 · click to enlarge
Page 433

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.3 FNC 72 – DSW / Digital Switch (Thumbwheel Input) 11

2. Connection diagram The figure below shows an example of the FX 3U series main unit (sink input/sink output). For wiring details, refer to the Hardware Edition of each PLC.

FNC30-FNC39 Rotation and Shift

103 102 101 100 To second set

103 102 101 100 BCD type digital switch

BCD type digital switch

Diode of 0.1 A, 50 V is required.

4 3 2 1 To second set 8 4 2 1

1 2 4 8

Inputs of second set 0V 24V

S/S X010 X011 X012 X013 X015 X014 X016 X017

Inputs of first set

PLC

COM3 Y010 Y011 Y012 Y013

103 102 101 100

3. Timing chart

FNC70-FNC79 External FX I/O Device

Y010

operation 0.1 sec 0.1 sec 0.1 sec

Y011

0.1 sec

Y012

0.1 sec

FNC80-FNC89 External FX Device

Y013

0.1 sec

While X000 is ON, Y010 to Y013 turn ON in turn at every 100 ms. After one cycle is finished, the execution complete flag M8029 turns ON.

4. How to use this instruction in a relay output type PLC By providing a "digital switch read input", this instruction can be used in a relay output type PLC. When the push button switch (X000) is pressed, DSW (FNC 72) instruction executes a series of operations. Accordingly, with regard to this program, it is not necessary to consider the relay contact life even if Y010 to Y013 are relay outputs.

FNC100-FNC109 Data Transfer 2

SET M 0

M 0

DSW X010 Y010 D 0 K 1

M8029

RST M 0

FNC140-FNC149 Data Operation 2

1. While M0 (digital switch read input) is ON, DSW (FNC 72) is driven.
2. DSW (FNC 72) completes one cycle of operation, and remains driven until the execution complete flag (M8029) turns ON.
Show 8 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Repeated · Pause · M8029 Complete flag · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 434 of the Mitsubishi Electronics MELSEC FX3S user manual — SEGD S ‚ D ‚
Page 434 · click to enlarge
Page 434

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.4 FNC 73 – SEGD / Seven Segment Decoder

15.4 FNC 73 – SEGD / Seven Segment Decoder

Outline

This instruction decodes data, and turns the seven-segment display unit (1 digit) ON.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 434)
Fig. 360 · 1. Instruction format

2. Set data

Operand Type Description Data Type

Head word device to be decoded 16-bit binary

Word device number storing the data to be displayed in the seven-segment display unit 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 434)
Fig. 361 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

Explanation of function and operation

1. 16-bit operation (SEGD and SEGDP)

"0" to "F" (hexadecimal numbers) in low-order 4 bits (1 digit) of are decoded to data for the seven-segment

display unit, and stored in the low-order 8 bits of .

SEGD S ‚ D ‚

Command · input FNC 73

Page 435 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 435 · click to enlarge
Page 435

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.4 FNC 73 – SEGD / Seven Segment Decoder 11

2. Seven-segment decoding table

FNC30-FNC39 Rotation and Shift

S D

b3 b2 b1 b0 B15 ... B8 B7 B6 B5 B4 B3 B2 B1 B0

0 − − 0 0 1

1 0 0 0 1 − − 0 1 1 0

2 0 0 1 0 − − 0 1 0 1 1 0 1 1

3 0 0 1 1 − − 0 1 0 0 1

4 0 1 0 0 − − 0 1 1 0 0 1 1 0

5 0 1 0 1 − − 0 1 1 0 1 1 0 1

6 0 1 1 0 − − 0 1 0 1

7 0 1 1 1 − − 0 0 1 0 0 1 1 1

8 1 0 0 0 − − 0 1

9 1 0 0 1 − − 0 1 1 0 1

A 1 0 1 0 − − 0 1 1 1 0 1 1 1

FNC70-FNC79 External FX I/O Device

B 1 0 1 1 − − 0 1 0 0

C 1 1 0 0 − − 0 0 1 1 1 0 0 1

FNC80-FNC89 External FX Device

E 1 1 1 0 − − 0 1 0 0 1

F 1 − − 0 1 1 1 0 0 0 1

The head bit device or the least significant bit of a word device is handled as B0.

FNC100-FNC109 Data Transfer 2

Caution

1. Number of occupied devices

Low-order 8 bits of are occupied, and high-order 8 bits do not change.

FNC140-FNC149 Data Operation 2

Show 11 more labels / short text on this page
Seven-segment · Display · data Hexadeci- · configuration · mal num- · ber · FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 436 of the Mitsubishi Electronics MELSEC FX3S user manual — D D
Page 436 · click to enlarge
Page 436

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.5 FNC 74 – SEGL / Seven Segment With Latch

15.5 FNC 74 – SEGL / Seven Segment With Latch

Outline

This instruction controls one or two sets of 4-digit seven-segment display units having the latch function.

1. Instruction format

32-bit Instruction Mnemonic Operation Condition FNC 74

SEGL SEGL

−

2. Set data

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 436)
Fig. 362 · 1. Instruction format

Head word device converted into the BCD format 16-bit binary

n Parameter number [setting rangeK0 (H0) to K7 (H7)] 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 436)
Fig. 363 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (SEGL)

The 4-digit numeric value stored in is converted into BCD data, and each digit is output to the seven-segment display unit with the BCD decoder by the time division method.

SEGL n S ‚ D ‚

When using one set of 4 digits (n = K0 to K3)

→ For selection of "n", refer to Subsection 15.5.2.

1. Data and strobe signal

A 4-digit numeric value stored in is converted from binary into BCD, and each digit is output in turn from

D D

to +3 by the time division method.

The strobe signal is output in turn from +4 to +7 by the time division method also to latch one set of 4-digit seven-segment display unit.

D D

2. For , binary data ranging from 0 to 9999 is valid.
Show 6 more labels / short text on this page
16-bit Instruction · Mnemonic Operation Condition · 7 steps · Continuous Operation · Command · input FNC 74
Page 437 of the Mitsubishi Electronics MELSEC FX3S user manual — Related devices
Page 437 · click to enlarge
Page 437

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.5 FNC 74 – SEGL / Seven Segment With Latch 11

3. Example of connecting one seven-segment display unit The figure below shows an example of the FX 3U series main unit (sink output). For wiring details, refer to the Hardware Edition of each PLC.

FNC30-FNC39 Rotation and Shift

PLC (transistor output type)

COM +1 +2 +3 +4 +6 +7 +5

D ‚ D ‚ D ‚ D ‚ D ‚ D ‚ D ‚ D ‚

100 4 2 8 1

101 102 103

103 102 101 100

V+

1 2 4 8

When using two sets of 4 digits (n = K4 to K7)

→ For selection of "n", refer to Subsection 15.5.2.

1. Data and strobe signal a) 1st set of 4 digits

A 4-digit numeric value stored in is converted from binary into BCD, and its each digit is output in turn

from to +3 by the time division method.

D D

The strobe signal is output in turn from +4 to +7 by the time division method also to latch the first set of 4-digit seven-segment display unit. b) 2nd set of 4 digits

D D

FNC70-FNC79 External FX I/O Device

A 4-digit numeric value stored in +1 is converted from binary into BCD, and its each digit is output in

turn from +10 to +13 by the time division method.

D D

The strobe signal is output in turn from +4 to +7 by the time division method also to latch the

D D

second set of 4-digit seven-segment display unit. (The strobe signal outputs +4 to +7 are shared by the 1st and 2nd sets.)

D D

FNC80-FNC89 External FX Device

2. For and +1, binary data ranging from 0 to 9999 is valid.

S S

3. Example of connecting two seven-segment display units The figure below shows an example of the FX 3U series main unit (sink output). For wiring details, refer to the Hardware Edition of each PLC.

FNC100-FNC109 Data Transfer 2

PLC (transistor output type)

COM +1

+2 +3 +4 +6 +7 +5 D ‚ D ‚ D ‚ D ‚ D ‚ D ‚ D ‚ D ‚

+10 +11 +12 +13 D ‚ D ‚ D ‚ D ‚ COM

100 4 2 8 1

101 102 103

4 2 8 1

103 102 101 100

103 102 101 100

V+

V+ 1 2 4 8

1 2 4 8

FNC140-FNC149 Data Operation 2

Related devices

→ For the instruction execution complete flag use method, refer to Subsection 6.5.2.

M8029 Instruction execution com-

plete flag Turns ON when output of 4 digits is finished.

Show 9 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · 1st set · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · 2nd set · 1st set · Device Name Description · FNC150-FNC159 Positioning Control
Page 438 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Number of occupied devices
Page 438 · click to enlarge
Page 438

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.5 FNC 74 – SEGL / Seven Segment With Latch

Cautions

1. Time to update the 4-digit seven-segment display The scan time (operation cycle) multiplied by 12 is required to update (one or two sets of) the 4-digit display.
2. Operation when the command input turns OFF While the command input is ON, the operation is repeated. When the command contact is set to OFF in the middle of an operation, the operation is paused. When the command contact is set to ON again, the operation is started from the beginning.

3. Number of occupied devices

When one set of 4 digits is used: 1 device is occupied from the head device specified in .

8 devices are occupied from the head device specified in . Even if the number of digits is smaller than 4, unused devices cannot be used for any other purpose.

When two sets of 4 digits are used: 2 devices are occupied from the head device specified in .

Twelve devices are occupied from the head device specified in . Even if the number of digits is smaller than 4, unused devices cannot be used for any other purpose.

4. Scan time (operation cycle) and the display timing SEGL instruction is executed in synchronization with the scan time (operation cycle) of the PLC. For achieving a series of display, the scan time of the PLC should be 10 ms or more. If the scan time is less than 10 ms, use the constant scan mode so that the scan time exceeds 10 ms.
5. Caution on use in timer interrupt programs When the SEGL instruction is used in a timer interrupt program, it turns ON M8029 in the interrupt program.

→ For details, refer to Subsection 36.5.2.

6. Output type of the PLC Use a transistor output type PLC.
Page 439 of the Mitsubishi Electronics MELSEC FX3S user manual — Y000
Page 439 · click to enlarge
Page 439

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.5 FNC 74 – SEGL / Seven Segment With Latch 11

15.5.1 How to select a seven-segment display unit

FNC30-FNC39 Rotation and Shift

When selecting a seven-segment display unit based on its electrical characteristics, refer to the manual below:

→ For the wiring, refer to the Hardware Edition of the PLC used.

1. Points to be checked for the seven-segment specifications

1. The input voltage and current characteristics of the data input and strobe signal satisfy the output specifications of the PLC. - The input signal voltage (Lo) is approximately 1.5 V or less - The input voltage is from 5V DC to 30V DC
2. The seven-segment display unit has the BCD decoding and latch functions

15.5.2 How to select parameter "n" based on seven-segment display specifications

The value set to the parameter "n" varies depending on the signal logic of the seven-segment display. Select "n" as described below. The check column is provided at the bottom of the table. Check a corresponding type of logic (positive or negative), and utilize it for parameter setting.

1. Role of the parameter "n" The parameter "n" should be determined according to the data input logic (positive or negative) of the seven-segment display unit, the logic (positive or negative) of the strobe signal and the number of sets of 4 digits to be controlled (1 or 2).
2. Checking the output logic of the PLC Transistor outputs in PLCs are classified into the sink output type and source output type. The table below shows the specifications for each type.

Logic Negative logic Positive logic

FNC70-FNC79 External FX I/O Device

Output type Sink output (− common) Source output (+ common)

V+

+V0

ON

HIGH

FNC80-FNC89 External FX Device

Y000

Y000

ON

LOW

COM1

PLC

PLC

Because transistor output (sink) is provided, the output becomes low level (0 V) when the internal logic is "1 (ON output)". This is called "negative logic".

Because transistor output (source) is provided, the output becomes high level (V+) when the internal logic is "1 (ON output)". This is called "positive logic".

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 12 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Pull-up resistor · Logic 1 · Output circuit · Logic 1 · Pull- down resistor · Description · Check · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 440 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Confirming the logic of the seven-segment display unit
Page 440 · click to enlarge
Page 440

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.5 FNC 74 – SEGL / Seven Segment With Latch

3. Confirming the logic of the seven-segment display unit

1. Data input
Mitsubishi Electronics MELSEC FX3S — 3. Confirming the logic of the seven-segment display unit diagram (page 440)
Fig. 364 · 3. Confirming the logic of the seven-segment display…

Description BCD data at low level BCD data at high level

2. Strobe signal
Mitsubishi Electronics MELSEC FX3S — 3. Confirming the logic of the seven-segment display unit diagram (page 440)
Fig. 365 · 3. Confirming the logic of the seven-segment display…

Description Data latched at low level is held. Data latched at high level is held.

4. Setting the parameter "n" Set a proper value according to the logic (positive or negative) of the PLC and the logic (positive or negative) of the seven-segment display unit as shown in the table below:
Mitsubishi Electronics MELSEC FX3S — 3. Confirming the logic of the seven-segment display unit diagram (page 440)
Fig. 366 · 3. Confirming the logic of the seven-segment display…

4 digits × 1 set 4 digits × 2 sets

5. Explanation of the parameter "n" setting method according to an actual example When the following seven-segment display unit is selected, "n" should be "1" when one display unit is connected (4 digits × 1 set) or "5" when two display units are connected (4 digits × 2 sets).
1. Transistor output of PLC - Sink output = Negative logic - Source output = Positive logic
2. Seven-segment display unit - Data input = Negative logic - Strobe signal = Positive logic
Mitsubishi Electronics MELSEC FX3S — 3. Confirming the logic of the seven-segment display unit diagram (page 440)
Fig. 367 · 3. Confirming the logic of the seven-segment display…

4 digits × 1 set 4 digits × 2 sets

Page 441 of the Mitsubishi Electronics MELSEC FX3S user manual — 1. 16-bit operation (ARWS)
Page 441 · click to enlarge
Page 441

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.6 FNC 75 – ARWS / Arrow Switch 11

15.6 FNC 75 – ARWS / Arrow Switch

FNC30-FNC39 Rotation and Shift

Outline

This instruction inputs data through arrow switches used for shifting the digit and incrementing/decrementing the numeric value in each digit.

1. Instruction format

32-bit Instruction Mnemonic Operation Condition

ARWS ARWS

Continuous Operation −

2. Set data

Operand Type Description Data Type

Head bit device number to be input Bit

Word device number storing data converted into BCD 16-bit binary

Head bit device (Y) number connected to seven-segment display unit Bit

n Number of digits of seven-segment display unit [setting range: K0 to K3] 16-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC70-FNC79 External FX I/O Device

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

FNC80-FNC89 External FX Device

S: "D .b" cannot be indexed with index registers (V and Z).

Explanation of function and operation

Four arrow switches are connected to the inputs to +3, a seven-segment display unit having the BCD

S S

decoder is connected to the outputs to +7, and a numeric value is input to .

D 2 D 2 D 1

FNC100-FNC109 Data Transfer 2

1. 16-bit operation (ARWS)

actually stores a 16-bit binary value ranging from 0 to 9999, but the value is expressed in the BCD format in the explanation below for convenience. When the command input is set to ON, the ARWS instruction executes the following operation.

ARWS n D1 ‚ S ‚ D2 ‚

FNC140-FNC149 Data Operation 2

Show 16 more labels / short text on this page
FNC40-FNC49 Data Operation · 16-bit Instruction · Mnemonic Operation Condition · 9 steps · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · n 3 3 · Command · input FNC 75 · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 442 of the Mitsubishi Electronics MELSEC FX3S user manual — S S
Page 442 · click to enlarge
Page 442

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.6 FNC 75 – ARWS / Arrow Switch

Contents of the display and operation part

Mitsubishi Electronics MELSEC FX3S — Contents of the display and operation part diagram (page 442)
Fig. 368 · Contents of the display and operation part

Seven-segment display unit Equipped with the latch function so that a numeric value being set can be seen.

Arrow switches Provided to select a digit and increment or decrement the numeric value in the selected digit.

1. Specifying the number of digits of the seven-segment display unit having the BCD decoder n In the explanation below, "n" is set to "4" (up to the 10 3 digit).

2) Operation of the digit selection switches ( +2 and +3) - Operation when the lower digit input +2 turns ON Every time the lower digit switch is pressed, the digit specification changes in the way "103 → 102 → 101 → 100 → 103". - Operation when the higher digit input +3 turns ON Every time the higher digit switch is pressed, the digit specification changes in the way "103 → 100 → 101 → 102 → 103".

S S

3. Operation of the LED for displaying a selected digit ( +4 to +7)

D 2 D 2

A specified digit can be displayed by the LED offered by the strobe signals +4 to +7.

D 2 D 2

4. Operation of the switches for changing data in each digit ( and +1) In a digit specified by a digit selection switch described above, data is changed as follows: - When the increment input turns ON

S S

Every time the increment switch is pressed, the contents of change in the way "0 → 1 → 2 → ... → 8 → 9 → 0 → 1". - When the decrement input turns ON

Every time the decrement switch is pressed, the contents of change in the way "0 → 9 → 8 → 7 ... 1 → 0 → 9". The contents can be displayed in the seven-segment display unit.

As described above, a target numeric value can be written to using a series of operation while looking at the seven-segment display unit.

Page 443 of the Mitsubishi Electronics MELSEC FX3S user manual — Y000 Y001
Page 443 · click to enlarge
Page 443

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.6 FNC 75 – ARWS / Arrow Switch 11

Cautions

FNC30-FNC39 Rotation and Shift

1. Setting of the parameter "n" Refer to the explanation of parameter setting in the SEGL (FNC 74) instruction. The setting range is from 0 to 3 for the ARWS instruction.

→ For the parameter setting, refer to Subsection 15.5.2.

2. Output type of the PLC Use a transistor output type PLC.
3. Scan time (operation cycle) and the display timing ARWS instruction is executed in synchronization with the scan time (operation cycle) of the PLC. For achieving a series of display, the scan time of the PLC should be 10 ms or more. If the scan time is less than 10 ms, use the constant scan mode so that the scan time exceeds 10 ms.

4. Number of occupied devices

1. Four input devices are occupied starting from .
2. Eight output devices are occupied starting from .
5. Limitation in the number of the instruction ARWS instruction can only be used once in a program. When ARWS instruction should be used two or more times, use the indexing (V, Z) function.

Program example

1. When changing the timer number and displaying the current value

1. Specifying the timer number using a 3-digit digital switch

FNC70-FNC79 External FX I/O Device

X010 X011 X012

FNC80-FNC89 External FX Device

Y012

Y011

Y010

2. Setting the constant of the timer using the arrow switches

Y007 Y006 Y005

Y004

FNC100-FNC109 Data Transfer 2

Y000 Y001

Y014

Y002

Y015

Set Write X004 X003 X002 X000

Explanation of operation Every time the read/write key is pressed, the read/write LED lights alternately.

FNC140-FNC149 Data Operation 2

  • In reading Set the timer number using the digital switch, and then press the set switch (X003).
  • In writing Set a numeric value using the arrow switches while looking at the seven-segment display unit, and then press the switch X003.
Show 8 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Read · Write Y003 · FNC110-FNC139 Floating Point · Read · FNC150-FNC159 Positioning Control
Page 444 of the Mitsubishi Electronics MELSEC FX3S user manual — Program
Page 444 · click to enlarge
Page 444

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.6 FNC 75 – ARWS / Arrow Switch

Program

Mitsubishi Electronics MELSEC FX3S — Program diagram (page 444)
Fig. 369 · Program

Digital switch → Z 4 digits × 1 set

(M 0 to M 3) → (D511) → (Y000 to Y007) → Seven-segment display unit

Page 445 of the Mitsubishi Electronics MELSEC FX3S user manual — 44 (D) 43 (C) +1
Page 445 · click to enlarge
Page 445

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.7 FNC 76 – ASC / ASCII Code Data Input 11

15.7 FNC 76 – ASC / ASCII Code Data Input

FNC30-FNC39 Rotation and Shift

Outline

This instruction converts a half-width alphanumeric character string into ASCII codes. Use this instruction for selecting one among two or more messages and displaying it on an external display unit.

1. Instruction format

32-bit Instruction Mnemonic Operation Condition

ASC −

ASC

2. Set data

Operand Type Description Data Type

Eight half-width alphanumeric characters input from a personal computer*1 Character string (only ASCII codes)

Head word device number storing ASCII data 16-bit binary

*1. The number of characters is fixed to 8. When ASCII code less than 8 characters is input, the space character (H20) is stored in remaining .

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC70-FNC79 External FX I/O Device

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

*2. It is not necessary to attach quotes (" ") to the character string specified in .

FNC80-FNC89 External FX Device

Explanation of function and operation

1. 16-bit operation (ASC)

The half-width alphanumeric characters specified in are converted into ASCII codes, and each ASCII code is

transferred in turn to .

FNC100-FNC109 Data Transfer 2

  • can handle half-width characters A to Z, 0 to 9 and symbols (, but cannot handle regular-width characters). A character string is entered when a program is created with a programming tool.
  • stores converted ASCII codes in the order of low-order 8 bits and high-order 8 bits by 2 characters/byte at one time.

ASC S

D ‚ 42 (B) 41 (A)

ExampleABCDEFGH

44 (D) 43 (C) +1

46 (F) 45 (E)

48 (H) 47 (G)

FNC140-FNC149 Data Operation 2

Show 23 more labels / short text on this page
FNC40-FNC49 Data Operation · 16-bit Instruction · Mnemonic Operation Condition · 11 steps · Continuous Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · 3*2 · Command · High-order 8 · Low-order 8 · input FNC 76 · bits · bits · FNC110-FNC139 Floating Point · +2 · +3 · FNC150-FNC159 Positioning Control
Page 446 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 446 · click to enlarge
Page 446

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.7 FNC 76 – ASC / ASCII Code Data Input

Extension function

When M8161 is set to ON for making the extension function valid, a half-width alphanumeric character string specified

in is converted into ASCII codes, and transferred in turn only to low-order 8 bits (1 byte) of .

Mitsubishi Electronics MELSEC FX3S — Extension function diagram (page 446)
Fig. 370 · Extension function

"H00" is stored in high-order 8 bits.

Mitsubishi Electronics MELSEC FX3S — Extension function diagram (page 446)
Fig. 371 · Extension function

Related devices

Mitsubishi Electronics MELSEC FX3S — Related devices diagram (page 446)
Fig. 372 · Related devices

8-bit processing mode for ASC (FNC 76), RS (FNC 80), ASCI (FNC 82), HEX (FNC 83) and CCD (FNC 84) instructions OFF: Two characters are stored to low-order 8 bits and high-order 8 bits in this order at one time (2 characters/word). ON: One character is stored to low-order 8 bits at one time (1 character/word).

Caution

1. Number of occupied devices

1. While the extension function is OFF

- Four devices are occupied from .

2. While the extension function is ON

- Eight devices are occupied from .

2. When using RS (FNC 80), ASCI (FNC 82), HEX (FNC 83) and/or CCD (FNC 84) instructions The extension function flag M8161 is also used for other instructions. When using an instruction described above and the ASC instruction in the same program, make sure to set M8161 to ON or OFF just before the ASC instruction so that M8161 does not apply to another instruction.
Page 447 of the Mitsubishi Electronics MELSEC FX3S user manual — D D D D
Page 447 · click to enlarge
Page 447

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.8 FNC 77 – PR / Print (ASCII Code) 11

15.8 FNC 77 – PR / Print (ASCII Code)

FNC30-FNC39 Rotation and Shift

Outline

This instruction outputs ASCII code data to outputs (Y) in parallel.

1. Instruction format

32-bit Instruction Mnemonic Operation Condition

PR −

PR

2. Set data

Operand Type Description Data Type

Head device number storing ASCII code data Character string (only ASCII codes)

Head output (Y) number to which ASCII code data is output Bit

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

FNC70-FNC79 External FX I/O Device

Explanation of function and operation

1. 16-bit operation (PR)

ASCII codes stored of to +3 are output to to +7 in turn by one character at a time in the time division method.

S S D D

FNC80-FNC89 External FX Device

PR S ‚ D ‚

Eight bytes are sent from the low-order 8 bits (1 byte) of first to the high-order 8 bits (1 byte) of +3 at the end.

S S

When data is stored from to +3 as shown in the table below, data is sent in the order of A to H of "2. Timing chart".

S S

FNC100-FNC109 Data Transfer 2

+1 +2 +3 high-order 8 bits low-order 8 bits high-order 8 bits low-order 8 bits high-order 8 bits low-order 8 bits high-order 8 bits low-order 8 bits B (H42) A (H41) D (H44) C (H43) F (H46) E (H45) H (H48) G (H47)

S

2. Timing chart

A B C D H

D D

T0: Scan time (ms)

FNC140-FNC149 Data Operation 2

Types of output signals

  • to +7: Sending output ( handles low-order bits, and +7 handles high-order bits.)

D

  • +8: Strobe signal
  • +9: Execution flag which operates as shown in the above timing chart
Show 20 more labels / short text on this page
FNC40-FNC49 Data Operation · 16-bit Instruction · Mnemonic Operation Condition · 5 steps · Continuous Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input FNC 77 · FNC110-FNC139 Floating Point · Command input · to +7 Data · +8 Strobe · +9 Execution flag · FNC150-FNC159 Positioning Control
Page 448 of the Mitsubishi Electronics MELSEC FX3S user manual — Related devices
Page 448 · click to enlarge
Page 448

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.8 FNC 77 – PR / Print (ASCII Code)

Extension function

1. 16-byte serial output The number of output characters varies depending on the ON/OFF status of the special auxiliary relay M8027. While M8027 is OFF, 8-byte serial output (fixed to 8 characters) is executed. While M8027 is ON, 16-byte serial output (1 to 16 characters) is executed. In the example shown below, up to 16 characters (1 character/byte) are output to the display unit (external display unit

A6FD*1, for example). It is supposed that data to be displayed is stored in hexadecimal codes in D300 to D307.

1. Program

M8027

D300 Y020

PR

2. Connection example of the external display unit A6FD *1

The PLC shown in the example below is the FX2N-16EYT (sink output) connected to the FX3U-32M .

Mitsubishi Electronics MELSEC FX3S — M8027 diagram (page 448)
Fig. 373

Y033 COM1 Y020 Y021 Y022 Y023 Y024 Y025 Y026 Y027 COM2 Y030

D 0 D 1 D 2 D 3 D 4 D 5 D 6 D 7

*1. A6FD was distributed only inside Japan, however, production of the external display unit A6FD was terminated in November 2002.

3. Timing chart (while M8027 is ON)
Mitsubishi Electronics MELSEC FX3S — M8027 diagram (page 448)
Fig. 374

Operation is started when X000 turns ON from OFF.

*2. If "H00 (NULL code)" is contained in the data (16 characters), the character just before "H00 (NULL code)" is handled as the last character.

Related devices

M8027*3 PR mode OFF: 8-byte serial output (fixed to 8 characters) ON: 16-byte serial output (1 to 16 characters)

*3. Cleared when the PR mode is changed from RUN to STOP.

Device Name Description

Page 449 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 449 · click to enlarge
Page 449

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.8 FNC 77 – PR / Print (ASCII Code) 11

Cautions

FNC30-FNC39 Rotation and Shift

1. Command input and instruction operation While the command input is ON: Even if the command input is continuously ON, execution is completed after a series of outputs. M8029 turns ON when the command input turns OFF after M8027 turns ON and execution is completed. While the command input is OFF: All outputs are OFF.
2. Relationship with the scan time (operation cycle) This instruction is executed in synchronization with the scan time. If the scan time is short, the constant scan mode can be used. If the scan mode is too long, the timer interrupt function can be used.
3. Output type of the PLC Use a transistor output type PLC.
4. When "00H (NULL code)" is contained in the data (while M8027 is ON) The instruction is executed completely, and the data after "00H" is not output. M8029 remains ON during one operation cycle.
5. Limitation in number of instructions The PR instruction can only be executed twice in a program. If it is necessary to use the PR instruction 3 times or more, use the indexing (V, Z) function in programming.
6. Caution on use in timer interrupt programs When the PR instruction is used in a timer interrupt program, it turns ON M8029 in the interrupt program.

→ For details, refer to Subsection 36.5.2.

FNC70-FNC79 External FX I/O Device

FNC80-FNC89 External FX Device

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 5 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 450 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 450 · click to enlarge
Page 450

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.9 FNC 78 – FROM / Read From A Special Function Block

15.9 FNC 78 – FROM / Read From A Special Function Block

Outline

This instruction reads the contents of buffer memories (BMF) in a special function unit/block attached to a PLC. When a large capacity of buffer memory (BFM) data is read by this instruction, a watchdog timer error may occur. When bad effect is not given to the control even if data to be read is divided, use RBFM (FNC278) instruction.

→ For RBFM (FNC278) instruction, refer to Section 31.1.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 450)
Fig. 375 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 450)
Fig. 376 · 2. Set data

m1 Unit number of a special extension unit/block (K0 to K7 from the right side of the main unit) 16- or 32-bit binary

m2 Transfer source buffer memory (BFM) number 16- or 32-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 450)
Fig. 377 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

Explanation of function and operation

1. 16-bit operation (FROM and FROMP) → For the common items between FROM instruction and TO instruction,

refer to Subsection 15.9.1.

Special extension unit/block (BFM) → PLC (word device) "n"-point 16-bit data starting from the buffer memory (BFM) # m2 inside a special function unit/block No. m1 are

transferred (read) to "n"-point 16-bit data starting from inside a PLC.

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 450)
Fig. 378 · Explanation of function and operation

Number of transfer points n = 1 to 32767

Transfer source BFM# (Special extension unit/block) m2 = 0 to 32766

Page 451 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 451 · click to enlarge
Page 451

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.9 FNC 78 – FROM / Read From A Special Function Block 11

2. 32-bit operation (DFROM and DFROMP)

FNC30-FNC39 Rotation and Shift

Special extension unit/block (BFM) → PLC (word device) "n" 32-bit data starting from the buffer memory (BFM) # [m2+1, m2] inside a special extension unit/block No. m1 are

transferred (read) to "n" devices starting from [ +1, ] inside a PLC.

D D

input FNC 78 DFROM m1 m2 n D ‚

Number of transfer points n = 1 to 16383

Transfer source BFM# (Special extension unit/block) m2 = 0 to 32765

Unit No. m1 = 0 to 7

Related devices

Disables or enables interrupts while FROM/TO instruction is executed. → For details, refer to "Acceptance of interrupts while FROM/TO instruction is executed

(M8028)" on the next page. OFF: Disables interrupts. (Interrupts are executed after FROM/TO instruction is executed.) ON: Enables interrupts.

M8028 Enable interrupt flag

Cautions

FNC70-FNC79 External FX I/O Device

  • Digit specification in bit device For the 16-bit operation instruction, specify K1 to K4. For the 32-bit operation instruction, specify K1 to K8.
  • Note that the 32-bit values [m1+1, 1], [m2+1, m2] and [n+1, n] are valid when D or R is specified as "m1", "m2" or "n" in a 32-bit instruction. In the case of "DFROM D0 D2 D100 R0", "m1" is [D1, D0], "m2" is [D3, D2], and "n" is [R1, R0].

FNC80-FNC89 External FX Device

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 8 more labels / short text on this page
Command · FNC40-FNC49 Data Operation · Transfer destination (PLC) · FNC50-FNC59 High-Speed Processing · Device Name Description · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 452 of the Mitsubishi Electronics MELSEC FX3S user manual — BFM#0
Page 452 · click to enlarge
Page 452

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.9 FNC 78 – FROM / Read From A Special Function Block

Program examples

In programs, the contents of buffer memories (BFMs) in special extension units/blocks are read (transferred) to data registers (D), extension registers (R) and auxiliary relays (M) with digit specification using the FROM instruction and

direct specification of buffer memories*1.

*1. This function is supported only in FX3U/FX3UC PLCs.

Example: When the BFM#4 (abnormal station information) in the CC-Link/LT master unit (whose unit number is fixed

to "0") built in the FX3UC-32MT-LT(-2) is read to D0 -In case of FROM instruction

M8000

FROM K0 K4 D0 K1

Unit No. 0

-In case of MOV instruction

M8000

MOV U0\G4 D0

Unit No. 0

BFM#4

Example: When the BFMs#0 to 3 (remote station connection information) in the CC-Link/LT master unit (whose unit

number is fixed to "0") built in the FX3UC-32MT-LT(-2) are read to D10 to D13 -In case of FROM instruction

M0

FNC 78 FROMP K0 K0 D10 K4

Unit No. 0

-In case of BMOV instruction

M0

FNC 15 BMOVP U0\G0 D10

K4

Unit No. 0

BFM#0

Show 13 more labels / short text on this page
BFM#4 Transfer destination · Number of · transfer · points · Transfer destination · BFM#0 Transfer destination · Number of · transfer · points · Transfer destination · Number of · transfer · points
Page 453 of the Mitsubishi Electronics MELSEC FX3S user manual — D100 D101 D102 D103 D104
Page 453 · click to enlarge
Page 453

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.9 FNC 78 – FROM / Read From A Special Function Block 11

15.9.1 Common items between FROM instruction and TO instruction (details)

FNC30-FNC39 Rotation and Shift

Contents specified by operands

1. Unit number "m1" of a special extension unit/block Use the unit number to specify which equipment FROM/TO instruction works for. Setting range: K0 to K7

Unit No. 0 Built-in CC-Link/LT

Unit No.1

Unit No.2

Unit No.3

FX3UC- 32MT- LT(-2) main unit

A unit number is automatically assigned to each special extension unit/block connected to a PLC. The unit number is assigned in the way "No. 0 → No. 1 → No. 2 ..." starting from the equipment nearest to the main unit. When the main unit is the FX3UC-32MT-LT(-2), the unit number is assigned in the way "No. 1 → No. 2 → No. 3 ..." starting from the equipment nearest to the main unit because the CC-Link/LT master is built into the FX3UC-32MT-LT (-2).

2. Buffer memory (BFM) number "m2" Up to 32767 16-bit RAM memories are built into a special extension unit/block, and they are called buffer memories. Buffer memory numbers range from "0" to "32766" and their contents vary depending on the function of the extension equipment. Setting range: K0 to K32766

FNC70-FNC79 External FX I/O Device

  • When BFMs are handled in a 32-bit instruction, a specified BFM stores low-order 16 bits, and a consecutive BFM stores high-order 16-bits.

16 bits ← Specified BFM number

BFM#10 BFM#9

FNC80-FNC89 External FX Device

3. Number of transfer points "n" Setting range: K1 to K32767

Specify the number of transferred word devices in "n". "n =2" in a 16-bit instruction indicates the same meaning with "n = 1" in a 32-bit instruction.

Specified devices Specified BFMs

Specified devices Specified BFMs

FNC100-FNC109 Data Transfer 2

D100 D101 D102 D103 D104

BFM#5

D100 D101 D102 D103

BFM#5

#6 #7 #8 #9

In the case of "n = 5" in a 16-bit

In the case of "n = 2" in a 32-bit

FNC140-FNC149 Data Operation 2

Show 20 more labels / short text on this page
FNC40-FNC49 Data Operation · I/O extension · Special extension · Special extension · I/O extension · Special extension · FNC50-FNC59 High-Speed Processing · block · block · block · block · block · FMC60-FNC69 Handy Instruction · 16 bits High-order · Low-order · #6 #7 #8 · FNC110-FNC139 Floating Point · instruction · instruction · FNC150-FNC159 Positioning Control
Page 454 of the Mitsubishi Electronics MELSEC FX3S user manual — Handling of special extension units/blocks
Page 454 · click to enlarge
Page 454

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.9 FNC 78 – FROM / Read From A Special Function Block

Acceptance of interrupts while FROM/TO instruction is executed (M8028)

1. While M8028 is OFF While a FROM/TO instruction is being executed, interrupts are automatically disabled. Input interrupts and timer interrupts are not executed. Interrupts generated during the execution of FROM/TO instructions are immediately executed after the FROM/TO instruction completes. FROM/TO instructions can be used in interrupt programs.
2. While M8028 is ON When an interrupt is generated during the execution of a FROM/TO instruction, the FROM/TO operation is momentarily paused while the interrupt program executes. FROM/TO instructions cannot be used in interrupt programs.

Action against watchdog timer error

1. Cause of watchdog timer error A watchdog timer error may occur in the following cases:
1. When a large number of special extension equipment is connected When a large number of special extension equipment (such as positioning units, cam switches, link units and analog units) are connected, considerable time may be required to initialize buffer memories when the PLC mode is set to RUN, the operation time may be long, and a watchdog timer error may occur.
2. When many FROM/TO instructions are driven at the same time When many FROM/TO instructions are driven at the same time or when many buffer memories are transferred, the operation time may be long, and a watchdog timer error may occur.

2. Countermeasures

1. Using RBFM (FNC278) or WBFM (FNC279) instruction [Ver. 2.20 or later]

→ For divided BFM read [RBFM (FNC278) instruction], refer to Section 31.1. → For divided BFM write [WBFM (FNC279) instruction], refer to Section 31.2.

2. Changing the watchdog timer time By overwriting the contents of D8000 (watchdog timer time), the watchdog timer detection time can be changed. When the program shown below is input, the sequence program after the input will be monitored with the new watchdog timer time.

M8002

Watchdog timer time300 ms 0

MOV K300 D8000

Watchdog timer refresh If WDT (FNC 07) instruction is not programmed, the value of D8000 is valid during END processing.

WDT

3. Changing FROM/TO instruction execution timing Shift FROM/TO instruction execution timing to make the operation time shorter.

Handling of special extension units/blocks

For the special extension unit/block connection method, number of connectable special extension units/blocks and handling of I/O numbers, refer to the manuals of the PLC and each special extension unit/block.

Initial pulse

Page 455 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 455 · click to enlarge
Page 455

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.10 FNC 79 – TO / Write To A Special Function Block 11

15.10 FNC 79 – TO / Write To A Special Function Block

FNC30-FNC39 Rotation and Shift

Outline

This instruction writes data from a PLC to buffer memories (BFM) in a special function unit/block. When a large capacity of data is written to buffer memories (BFM) by this instruction, a watchdog timer error may occur. When splitting the data to be written does not affect the control, use WBFM (FNC279) instruction.

→ For WBFM (FNC279) instruction, refer to Section 31.2.

1. Instruction format

P FNC 79

Mnemonic Operation Condition 32-bit Instruction

TO D DTO

TO

Continuous Operation Pulse (Single) Operation

17 steps Continuous Operation Pulse (Single) Operation

TOP

DTOP

2. Set data

Operand Type Description Data Type

m1 Unit number of a special extension unit/block (K0 to K7 from the right side of the main unit) 16- or 32-bit binary

m2 Transfer destination buffer memory (BFM) number 16- or 32-bit binary

Device number storing the transfer source data 16- or 32-bit binary

n Number of transfer points 16- or 32-bit binary

3. Applicable devices

Bit Devices Word Devices Others

FNC70-FNC79 External FX I/O Device

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

m1 3

m2 3

3

FNC80-FNC89 External FX Device

n 3

Explanation of function and operation

1. 16-bit operation (TO and TOP) → For the common items between FROM instruction and TO instruction, refer to Subsection 15.9.1.

FNC100-FNC109 Data Transfer 2

PLC (word device) → Special extension unit/block (BFM)

"n"-point 16-bit data starting from inside a PLC are transferred (written) to "n"-point buffer memories starting from the buffer memory (BFM) # m2 inside a special function unit/block No. m1.

TO m1 m2 n S ‚

Number of transfer points n = 1 to 32767

Transfer destination (Special extension unit/block) BFM# m2 = 0 to 32766

Unit No. m1 = 0 to 7

FNC140-FNC149 Data Operation 2

Show 16 more labels / short text on this page
FNC40-FNC49 Data Operation · 16-bit Instruction · Mnemonic Operation Condition · 9 steps · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input FNC 79 · FNC110-FNC139 Floating Point · Transfer source (PLC) · FNC150-FNC159 Positioning Control
Page 456 of the Mitsubishi Electronics MELSEC FX3S user manual — BFM#27
Page 456 · click to enlarge
Page 456

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

15 External FX I/O Device – FNC 70 to FNC 79

15.10 FNC 79 – TO / Write To A Special Function Block

2. 32-bit operation (DTO and DTOP)

PLC (word device) → Special extension unit/block (BFM)

"n"-point 32-bit data starting from [ , +1] inside a PLC are transferred (written) to "n"-point buffer memories starting from the buffer memory (BFM) # [m2+1, m2] inside a special extension unit/block No. m1.

S S

Mitsubishi Electronics MELSEC FX3S — S S diagram (page 456)
Fig. 379

Number of transfer points n = 1 to 16383

Transfer destination (Special extension unit/block) BFM# m2 = 0 to 32765

Related devices

Mitsubishi Electronics MELSEC FX3S — Related devices diagram (page 456)
Fig. 380 · Related devices

Disables or enables interrupts while FROM/TO instruction is executed.

→ For details, refer to "Acceptance of interrupt while FROM/TO instruction is executed

(M8028)" in Subsection 15.9.1. OFF: Disables interrupts. (Interrupts are executed after FROM/TO instruction is executed.) ON: Enables interrupts.

Cautions

  • Digit specification in bit device For the 16-bit operation instruction, specify K1 to K4. For the 32-bit operation instruction, specify K1 to K8.
  • Note that the 32-bit values [m1+1, 1], [m2+1, m2] and [n+1, n] are valid when D or R is specified as "m1", "m2" or "n" in a 32-bit instruction. In the case of "DTO D0 D2 D100 R0", "m1" is [D1, D0], "m2" is [D3, D2], and "n" is [R1, R0].

Program examples

In programs, the contents of data registers (D), extension registers (R), auxiliary relays (M) with digit specification and constants (K and H) are written (transferred) to buffer memories (BFMs) in special extension units/blocks using the TO

instruction and direct specification of buffer memories*1.

*1. This function is supported only in FX3U/FX3UC PLCs.

Example: When writing "H0" to the BFM#27 (command) in the CC-Link/LT master unit (whose unit number is fixed to

"0") built in the FX3UC-32MT-LT(-2) -In case of TO instruction

M1

TOP K0 K27 H0 K1

Unit No. 0

-In case of MOV instruction

M1

MOVP H0 U0\G27

Unit No. 0

BFM#27

Show 9 more labels / short text on this page
BFM#27 Transfer · Number of · source · Transfer · data · points · Transfer · source · data
Page 457 of the Mitsubishi Electronics MELSEC FX3S user manual — 16. External FX Device – FNC 80 to FNC 89
Page 457 · click to enlarge
Page 457

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

Mitsubishi Electronics MELSEC FX3S — 16. External FX Device – FNC 80 to FNC 89 diagram (page 457)
Fig. 381 · 16. External FX Device – FNC 80 to FNC 89

16. External FX Device – FNC 80 to FNC 89

FNC 80 to FNC 89 provide control instructions for special adapters mainly connected to serial ports. PID control loop instruction is included in this group.

Page 458 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 458 · click to enlarge
Page 458

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.1 FNC 80 – RS / Serial Communication

16.1 FNC 80 – RS / Serial Communication

Outline

This instruction sends and receives data using non-protocol communication by way of a serial port (only ch1) in accordance with RS-232C or RS-485 provided in the main unit.

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

RS −

2. Set data

Mitsubishi Electronics MELSEC FX3S — RS − diagram (page 458)
Fig. 382

Head device of data registers storing data to be sent 16-bit binary or character string

m Number of bytes of data to be sent [setting range: 0 to 4096] 16-bit binary

Head device of data registers storing received data when receiving is completed 16-bit binary or character string

n Number of bytes to be received [setting range: 0 to 4096] 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 458)
Fig. 383 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (RS) This instruction sends and receives data in non-protocol communication by way of serial ports in accordance with RS-232C or RS-485 provided in the main unit.

→ For detailed explanation, refer to the Data Communication Edition manual.

input D ‚ n

RS m S ‚

Show 5 more labels / short text on this page
Mnemonic Operation Condition · 32-bit Instruction · Continuous Operation · 9 steps RS · Command
Page 459 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 459 · click to enlarge
Page 459

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.1 FNC 80 – RS / Serial Communication 11

Related devices

FNC30-FNC39 Rotation and Shift

→ For detailed explanation, refer to the Data Communication Edition manual.

Device Name Device Name

M8063*1 Serial communication error 1 D8063*1 Error code number of serial communication error

M8121*2 Sending wait flag D8120*3 Communication format setting

M8122*2 Sending request D8122*4 Remaining amount of data to be sent

M8123*2 Receiving complete flag D8123*4 Amount of data already received

M8124 Carrier detection flag D8124 Header

M8129 Time-out check flag D8125 Terminator

M8161*4 8-bit processing mode D8129*3 Time-out time setting

D8405 Communication parameter display

D8419 Operation mode display

*1. Cleared when PLC power supply is turned from OFF to ON (in FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs). Cleared when the PLC mode is changed from STOP to RUN (in other PLCs).

  • *2. Cleared in the following cases:
  • When the PLC mode is changed from RUN to STOP
  • When the RS instruction is not driven

*3. Latched (battery or EEPROM backed).

*4. Cleared when the PLC mode is changed from RUN to STOP.

System configuration

To use this instruction, it is necessary to attach one of the products shown in the table below to the main unit.

→ For the system configuration, refer to the respective PLC Hardware Edition manual.

→ For detailed explanation, refer to the Data Communication Edition manual.

FNC70-FNC79 External FX I/O Device

PLC Communication type Option

RS-232C communication FX3G-232-BD or FX3U-232ADP(-MB) (with FX3S-CNV-ADP)

FX 3S

RS-485 communication FX3G-485-BD(-RJ) or FX3U-485ADP(-MB) (with FX3S-CNV-ADP)

RS-232C communication FX3G-232-BD or FX3U-232ADP(-MB) (with FX3G-CNV-ADP)

FX 3G

RS-485 communication FX3G-485-BD(-RJ) or FX3U-485ADP(-MB) (with FX3G-CNV-ADP)

FNC80-FNC89 External FX Device

RS-232C communication FX3U-232ADP(-MB)

FX 3GC , FX 3UC (D,DS,DSS)

RS-485 communication FX3U-485ADP(-MB)

FX 3U , FX 3UC -32MT-LT(-2)

RS-232C communication FX3U-232-BD or FX3U-232ADP(-MB) (with FX3U-CNV-BD)

RS-485 communication FX3U-485-BD or FX3U-485ADP(-MB) (with FX3U-CNV-BD)

Differences between the RS (FNC 80) instruction and RS2 (FNC 87) instruction

FNC100-FNC109 Data Transfer 2

Item RS2 instruction RS instruction Remarks

Header size 1 to 4 characters (bytes) Up to 1 character (byte) For the RS2 instruction, up to 4 characters (bytes) can be specified as a header or terminator. Terminator size 1 to 4 characters (bytes) Up to 1 character (byte)

For the RS2 instruction, the check sum can be automatically attached to the sent and received data. In this case, however, make sure to use a terminator with the communication frame to be sent and received.

The check sum should be attached by a user program.

Attachment of check sum

The check sum can be automatically attached.

For the RS2 instruction: Ch0 is available only in FX3G/FX3GC PLCs. Ch2 is not available in FX3G PLC (14-point and 24-point type) and FX3S PLC.

Used channel number ch0, ch1, ch2 ch1

FNC140-FNC149 Data Operation 2

Cautions

→ For other cautions, refer to the Data Communication Edition manual.

  • The RS (FNC 80) instruction can be used for ch1 only (cannot be used for ch0/ch2).
  • Do not drive two or more RS (FNC 80) and/or RS2 (FNC 87) instructions for the same port at the same time.
  • It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)" instruction and an "IVCK (FNC270) to IVMC (FNC275)", "ADPRW (FNC276)", "FLCRT (FNC300) to FLSTRD (FNC305)" instruction for the same port.
Show 5 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 460 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 460 · click to enlarge
Page 460

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.2 FNC 81 – PRUN / Parallel Run (Octal Mode)

16.2 FNC 81 – PRUN / Parallel Run (Octal Mode)

Mitsubishi Electronics MELSEC FX3S — 16.2 FNC 81 – PRUN / Parallel Run (Octal Mode) diagram (page 460)
Fig. 384 · 16.2 FNC 81 – PRUN / Parallel Run (Octal Mode)

This instruction handles the device number of with digit specification and the device number of as octal numbers, and transfers data.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 460)
Fig. 385 · 1. Instruction format

2. Set data

Operand type Description Data type

S 1 ‚ S

Digit specification*1 16- or 32-bit binary

Device number of transfer destination*1 16- or 32-bit binary

*1. Make sure that the least significant digit of a specified device number is "0".

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 460)
Fig. 386 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 16-bit operation (PRUN and PRUNP)

Octal bit device → Decimal bit device

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 460)
Fig. 387 · Explanation of function and operation

X000 to X017 → M0 to M7, M10 to M17

X17 X16 X15 X14 X13 X12 X11 X10 X7 X6 X5 X4 X3 X2 X1 X0

M15 M14 M13 M12 M11 M9 M8 M7 M6 M5 M4 M3 M2 M1 M0 M17 M16 M10

M8 and M9 do not change Decimal bit device (M)

Page 461 of the Mitsubishi Electronics MELSEC FX3S user manual — 16.2 FNC 81 – PRUN / Parallel Run (Octal Mode) 11
Page 461 · click to enlarge
Page 461

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.2 FNC 81 – PRUN / Parallel Run (Octal Mode) 11

Mitsubishi Electronics MELSEC FX3S — 16.2 FNC 81 – PRUN / Parallel Run (Octal Mode) 11 diagram (page 461)
Fig. 388 · 16.2 FNC 81 – PRUN / Parallel Run (Octal Mode) 11

M0 to M7, M10 to M17 → Y0 to Y17

M15 M14 M13 M12 M11 M9 M8 M7 M6 M5 M4 M3 M2 M1 M0 M17 M16 M10

Y17 Y16 Y15 Y14 Y13 Y12 Y11 Y10 Y7 Y6 Y5 Y4 Y3 Y2 Y1 Y0

X000 to X027 → M0 to M7, M10 to M17, M20 to M27

X27 … X20 X17 … X10 X7 X6 X5 X4 X3 X2 X1 X0

M19 M18 M17 … M9 M8 M7 M6 M5 M4 M3 M2 M1 M0 M27 …

M18 and M19 do not change Decimal bit device (M)

M0 to M7, M10 to M17, M20 to M27 → Y000 to Y027

M19 M18 M17 … M9 M8 M7 M6 M5 M4 M3 M2 M1 M0 M27 …

Y27 … Y20 Y17 … Y10 Y7 Y6 Y5 Y4 Y3 Y2 Y1 Y0

Page 462 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 462 · click to enlarge
Page 462

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.3 FNC 82 – ASCI / Hexadecimal to ASCII Conversion

16.3 FNC 82 – ASCI / Hexadecimal to ASCII Conversion

Outline

This instruction converts hexadecimal code into ASCII code. On the other hand, BINDA (FNC261) instruction converts binary data into ASCII code, and ESTR (FNC116) instruction converts binary floating point data into ASCII code.

→ For BINDA (FNC261) instruction, refer to Section 29.6.

→ For ESTR (FNC116) instruction, refer to Section 18.4.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 462)
Fig. 389 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 462)
Fig. 390 · 2. Set data

Head device number storing hexadecimal code to be converted 16-bit binary

Head device number storing converted ASCII code Character string (only ASCII code)

n Number of characters (digits) of hexadecimal code to be converted [setting range: 1 to 256] 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 462)
Fig. 391 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (ASCI and ASCIP)

"n" hexadecimal code characters (digits) stored in and later are converted into ASCII code, and then stored to

the devices and later. The 16-bit mode and 8-bit mode options are available for this instruction. For operation in each mode, refer to the proceeding pages.

ASCI n S ‚

Command · input D ‚

Page 463 of the Mitsubishi Electronics MELSEC FX3S user manual — [C] → 43H [B] → 42H
Page 463 · click to enlarge
Page 463

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.3 FNC 82 – ASCI / Hexadecimal to ASCII Conversion 11

2. 16-bit conversion mode (while M8161 is OFF) (M8161 is also used for the RS, HEX, CCD and CRC instructions.)

FNC30-FNC39 Rotation and Shift

Each digit of hexadecimal data stored in and later is converted into ASCII code, and transferred to the high-

order 8 bits and low-order 8 bits of each device and later. The number of digits (characters) to be converted is specified by "n".

Each ASCII code is stored in either the high-order 8 bits or low-order 8 bits of each device and later. M8161 is used also for RS, HEX, CCD and CRC instructions. When using the 16-bit mode, set M8161 to normally OFF. M8161 is cleared when the PLC mode is changed from RUN to STOP.

M8161 M8000

ASCI n S ‚

Operation In the following program, conversion is executed as follows:

M8161 M8000

ASCI D100 D200 K4 X010

Devices after D100 = 0ABCH D101 = 1234H D102 = 5678H

FNC70-FNC79 External FX I/O Device

Number of specified digits (characters) and conversion result

K1 K2 K3 K4 K5 K6 K7 K8 K9

Low-order 8 bits of D200 [C] [B] [A] [0] [4] [3] [2] [1] [8]

FNC80-FNC89 External FX Device

High-order 8 bits of D200 [C] [B] [A] [0] [4] [3] [2] [1]

Low-order 8 bits of D201 [C] [B] [A] [0] [4] [3] [2]

High-order 8 bits of D201 [C] [B] [A] [0] [4] [3]

Low-order 8 bits of D202 [C] [B] [A] [0] [4]

High-order 8 bits of D202 [C] [B] [A] [0]

Low-order 8 bits of D203 Does not change [C] [B] [A]

FNC100-FNC109 Data Transfer 2

High-order 8 bits of D203 [C] [B]

Low-order 8 bits of D204 [C]

Bit configuration in the case of "n = K4"

0 0 1 0 1 0 1 0 1 0 D 100 = 0ABCH

ASCII code [0] = 30H [1] = 31H [5] = 35H [A] = 41H [2] = 32H [6] = 36H [B] = 42H [3] = 33H [7] = 37H [C] = 43H [4] = 34H [8] = 38H

0 A B C

0 1 1 0 0 1 0 1 0

[A] → 41H [0] → 30H D 201

0 1 0 1 0 1 1 0 1 0

[C] → 43H [B] → 42H

FNC140-FNC149 Data Operation 2

  • When outputting data in the BCD format for a printer, for example, it is necessary to convert binary data into BCD data before executing this instruction.
Show 10 more labels / short text on this page
FNC40-FNC49 Data Operation · 16-bit mode · Command · input D ‚ · FNC50-FNC59 High-Speed Processing · 16-bit mode · FMC60-FNC69 Handy Instruction · n · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 464 of the Mitsubishi Electronics MELSEC FX3S user manual — Bit configuration in the case of "n = K2"
Page 464 · click to enlarge
Page 464

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.3 FNC 82 – ASCI / Hexadecimal to ASCII Conversion

3. 8-bit conversion mode (while M8161 is ON) (M8161 is used also for the RS, HEX, CCD and CRC instructions.)

Each digit of hexadecimal data stored in and later is converted into an ASCII code, and transferred to low-order

8 bits of each device and later. The number of digits (characters) to be converted is specified by "n". "0" is

stored in high-order 8 bits of each device and later. M8161 is used also for the RS, HEX, CCD and CRC instructions. When using the 8-bit mode, set M8161 to normally ON. M8161 is cleared when the PLC mode is changed from RUN to STOP.

Mitsubishi Electronics MELSEC FX3S — 16.3 FNC 82 – ASCI / Hexadecimal to ASCII Conversion diagram (page 464)
Fig. 392 · 16.3 FNC 82 – ASCI / Hexadecimal to ASCII Conversion

When M8161 is set to ON, the 8-bit mode is selected. The conversion processing is executed as follows

Operation In the following program, conversion is executed as follows:

Mitsubishi Electronics MELSEC FX3S — 16.3 FNC 82 – ASCI / Hexadecimal to ASCII Conversion diagram (page 464)
Fig. 393 · 16.3 FNC 82 – ASCI / Hexadecimal to ASCII Conversion

Devices after D100 = 0ABCH D101 = 1234H D102 = 5678H

Number of specified digits (characters) and conversion result

Mitsubishi Electronics MELSEC FX3S — Number of specified digits (characters) and conversion result diagram (page 464)
Fig. 394 · Number of specified digits (characters) and conversi…

K1 K2 K3 K4 K5 K6 K7 K8 K9

D 200 [C] [B] [A] [0] [4] [3] [2] [1] [8]

D 201 [C] [B] [A] [0] [4] [3] [2] [1]

D 202 [C] [B] [A] [0] [4] [3] [2]

Bit configuration in the case of "n = K2"

Mitsubishi Electronics MELSEC FX3S — Bit configuration in the case of "n = K2" diagram (page 464)
Fig. 395 · Bit configuration in the case of "n = K2"

0 0 1 0 1 0 1 0 1 0

ASCII codes [0] = 30H [1] = 31H [5] = 35H [A] = 41H [2] = 32H [6] = 36H [B] = 42H [3] = 33H [7] = 37H [C] = 43H [4] = 34H [8] = 38H

0 1 0 1 0

1 1 0 1 0

  • When outputting data in the BCD format for a printer, for example, it is necessary to convert binary data into BCD data before executing this instruction.
Page 465 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 465 · click to enlarge
Page 465

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.4 FNC 83 – HEX / ASCII to Hexadecimal Conversion 11

16.4 FNC 83 – HEX / ASCII to Hexadecimal Conversion

FNC30-FNC39 Rotation and Shift

Outline

This instruction converts ASCII codes into hexadecimal codes. On the other hand, DABIN (FNC260) instruction converts ASCII codes into binary data, and EVAL (FNC117) instruction converts ASCII codes into binary floating point data.

→ For DABIN (FNC260) instruction, refer to Section 29.5.

→ For EVAL (FNC117) instruction, refer to Section 18.5.

1. Instruction format

P FNC 83

Mnemonic Operation Condition 16-bit Instruction

HEX − −

Continuous Operation Pulse (Single) Operation

HEXP

2. Set data

Operand type Description Data type

Head device number storing ASCII code to be converted Character string

S 1 ‚ S

(only ASCII code)*1

Head device number storing converted hexadecimal code 16-bit binary

n Number of ASCII codes (bytes) to be converted [setting range: 1 to 256] 16-bit binary

*1. Make sure to use only ASCII codes "0" to "9" and "A" to "F".

FNC70-FNC79 External FX I/O Device

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FNC80-FNC89 External FX Device

S 1 ‚ S

3 S1 S2 3 3 3

S 2 ‚ D

3 S1 S2 3 3 3

n 3 S1 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

FNC100-FNC109 Data Transfer 2

Explanation of function and operation

1. 16-bit operation (HEX and HEXP)

Among the ASCII codes stored in and later, "n" characters are converted into hexadecimal codes, and then

stored to the devices and later. The 16-bit mode and 8-bit mode are available for this instruction. For operation in each mode, refer to the proceeding pages.

HEX n S ‚

FNC140-FNC149 Data Operation 2

Show 15 more labels / short text on this page
FNC40-FNC49 Data Operation · Mnemonic Operation Condition · 32-bit Instruction · FNC50-FNC59 High-Speed Processing · 7 steps HEX · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · FNC110-FNC139 Floating Point · Command · input · FNC150-FNC159 Positioning Control
Page 466 of the Mitsubishi Electronics MELSEC FX3S user manual — Conversion source data
Page 466 · click to enlarge
Page 466

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.4 FNC 83 – HEX / ASCII to Hexadecimal Conversion

2. 16-bit conversion mode (while M8161 is OFF) (M8161 is used also for the RS, ASCI, CCD, and CRC instructions.)

Each ASCII code stored in high-order 8 bits and low-order 8 bits of devices and later is converted into a

hexadecimal code, and transferred to devices and later in units of 4 digits. The number of characters to be converted is specified by "n". M8161 is used also for the RS, ASCI, CCD and CRC instructions. When using the 16-bit mode, set M8161 to normally OFF. M8161 is cleared when the PLC mode is changed from RUN to STOP.

Mitsubishi Electronics MELSEC FX3S — 16.4 FNC 83 – HEX / ASCII to Hexadecimal Conversion diagram (page 466)
Fig. 396 · 16.4 FNC 83 – HEX / ASCII to Hexadecimal Conversion

Operation In the following program, conversion is executed as follows:

Mitsubishi Electronics MELSEC FX3S — 16.4 FNC 83 – HEX / ASCII to Hexadecimal Conversion diagram (page 466)
Fig. 397 · 16.4 FNC 83 – HEX / ASCII to Hexadecimal Conversion

Conversion source data

Mitsubishi Electronics MELSEC FX3S — Conversion source data diagram (page 466)
Fig. 398 · Conversion source data

Number of specified characters and conversion result " • " indicates "0".

Mitsubishi Electronics MELSEC FX3S — Conversion source data diagram (page 466)
Fig. 399 · Conversion source data
  • When the input data is in BCD format, it is necessary to convert BCD data into binary data after executing this instruction.
  • If ASCII code is not stored in in the HEX instruction, an operation error occurs and conversion into

hexadecimal code is disabled. Especially, note that ASCII code should be stored in high-order 8 bits of also when M8161 is OFF.

Page 467 of the Mitsubishi Electronics MELSEC FX3S user manual — 0 A
Page 467 · click to enlarge
Page 467

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.4 FNC 83 – HEX / ASCII to Hexadecimal Conversion 11

3. 8-bit conversion mode (while M8161 is ON) (M8161 is used also for the RS, ASCI, CCD and CRC instructions.)

FNC30-FNC39 Rotation and Shift

Each ASCII code stored in the low-order 8 bits of each device and later is converted into a hexadecimal code,

and transferred to device and later in 4-digits units. The number of characters to be converted is specified by "n". M8161 is also used for the RS, ASCI, CCD and CRC instructions. When using the 8-bit mode, set M8161 to normally ON. M8161 is cleared when the PLC mode is changed from RUN to STOP.

M8161 M8000

Ignored Low-order 8 bits

HEX n S ‚

Operation In the following program, conversion is executed as follows:

M8161 M8000

HEX D200 D100 K4 X010

Conversion source data

ASCII code Hexadecimal code

D 200 30H 0

D 201 41H A

FNC70-FNC79 External FX I/O Device

D 202 42H B

D 203 43H C

D 204 31H 1

D 205 32H 2

D 206 33H 3

D 207 34H 4

FNC80-FNC89 External FX Device

D 208 35H 5

Number of specified characters and conversion result " • " indicates "0".

In the case of "n = K2"

D 102 D 101 D 100 n

FNC100-FNC109 Data Transfer 2

  • 0H

30H → [0]

  • 0AH

3 • 0ABH

4 0ABCH

41H → [A]

  • 0H ABC1H
  • 0AH BC12H

0 A

7 • 0ABH C123H

8 0ABCH 1234H

  • 0H ABC1H 2345H
  • When the input data is in BCD format, it is necessary to convert BCD data into binary data after executing this instruction.

FNC140-FNC149 Data Operation 2

Show 12 more labels / short text on this page
FNC40-FNC49 Data Operation · 8-bit mode · 16 bits · Command · input D ‚ · Source data · FNC50-FNC59 High-Speed Processing · 8-bit mode · FMC60-FNC69 Handy Instruction · Does not change · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 468 of the Mitsubishi Electronics MELSEC FX3S user manual — D D
Page 468 · click to enlarge
Page 468

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.5 FNC 84 – CCD / Check Code

16.5 FNC 84 – CCD / Check Code

Outline

This instruction calculates the horizontal parity value and sum check value in the error check methods used in communication. There is another check method, CRC (cyclic redundancy check) also. For obtaining CRC value, use CRC instruction.

→ For CRC instruction, refer to Section 24.4. → For complement [NEG (FNC 29) instruction], refer to Section 10.10.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 468)
Fig. 400 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 468)
Fig. 401 · 2. Set data

Head device number of applicable device 16-bit binary or character string

Head device number storing the calculated data 16-bit binary or character string

n Number of data [setting range: 1 to 256] 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 468)
Fig. 402 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (CCD and CCDP)

The addition data and horizontal parity value of data stored in to +n-1 are calculated. The addition data is

S S

stored to , and the horizontal parity value is stored to +1. The 16-bit mode and 8-bit mode are available in this instruction. For the operation in each mode, refer to the proceeding pages.

D D

CCD n S ‚

Command · input

Page 469 of the Mitsubishi Electronics MELSEC FX3S user manual — M8161 M8000
Page 469 · click to enlarge
Page 469

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.5 FNC 84 – CCD / Check Code 11

2. 16-bit conversion mode (while M8161 is OFF) (M8161 is also used for the RS, ASCI, HEX and CRC instructions.)

FNC30-FNC39 Rotation and Shift

With regard to "n" data starting from , the addition data and horizontal parity data of high-order 8 bits and low-

order 8 bits are stored to and +1 respectively. M8161 is used also for the RS, ASCI, HEX and CRC instructions. When using the 16-bit mode, set M8161 to normally OFF. M8161 is cleared when the PLC mode is changed from RUN to STOP.

D D

M8161 M8000

CCD n S ‚

Example of 16-bit conversion In the following program, conversion is executed as follows:

M8161 M8000

CCD D100 D0 K10 X010

Example of data contents

Low-order 8 bits of D100 K100 = 01100100

High-order 8 bits of D100 K111 = 0110111 (1) ←

Low-order 8 bits of D101 K100 = 01100100

High-order 8 bits of D101 K 98 = 01100010

FNC70-FNC79 External FX I/O Device

Low-order 8 bits of D102 K123 = 0111101 (1) ←

High-order 8 bits of D102 K 66 = 01000010

Low-order 8 bits of D103 K100 = 01100100

High-order 8 bits of D103 K 95 = 0101111 (1) ←

Low-order 8 bits of D104 K210 = 11010010

FNC80-FNC89 External FX Device

High-order 8 bits of D104 K 88 = 01011000

Horizontal parity 1000010 (1) ← When the number of "1" is odd, the horizontal parity is "1". When the number of "1" is even, the horizontal parity is "0".

FNC100-FNC109 Data Transfer 2

1 1 0 1 0 0 0 1 0 D 0 "1091" in BCD

1 0 1 0 1 0 D 1 Horizontal parity

FNC140-FNC149 Data Operation 2

Show 10 more labels / short text on this page
FNC40-FNC49 Data Operation · 16-bit mode · Command · input · FNC50-FNC59 High-Speed Processing · 16-bit mode · FMC60-FNC69 Handy Instruction · Total K1091 · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 470 of the Mitsubishi Electronics MELSEC FX3S user manual — D D
Page 470 · click to enlarge
Page 470

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.5 FNC 84 – CCD / Check Code

3. 8-bit conversion mode (while M8161 is ON) (M8161 is used also for the RS, ASCI, HEX and CRC instructions.)

With regard to "n" data starting from , the addition data and horizontal parity data of only low-order 8 bits are

stored to and +1 respectively. M8161 is also used for the RS, ASCI, HEX and CRC instructions. When using the 8-bit mode, set M8161 to normally ON. M8161 is cleared when the PLC mode is changed from RUN to STOP.

D D

Mitsubishi Electronics MELSEC FX3S — D D diagram (page 470)
Fig. 403

Example of 8-bit conversion In the following program, conversion is executed as follows:

Mitsubishi Electronics MELSEC FX3S — D D diagram (page 470)
Fig. 404

Horizontal parity 1000010 (1) ← When the number of "1" is odd, the horizontal parity is "1". When the number of "1" is even, the horizontal parity is "0".

1 1 0 1 0 0 0 1 0 D 0 "1091" in BCD

1 0 1 0 1 0 D 1 Horizontal parity

Page 471 of the Mitsubishi Electronics MELSEC FX3S user manual — T0 D0
Page 471 · click to enlarge
Page 471

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.6 FNC 85 - VRRD / Volume Read 11

16.6 FNC 85 - VRRD / Volume Read

FNC30-FNC39 Rotation and Shift

Outline

This instruction reads the analog value of a variable analog potentiometer board attached to the PLC main unit.

1. Instruction format

32-bit Instruction P FNC 85

Mnemonic Operation Condition 16-bit Instruction

VRRD

Continuous Operation Pulse (Single) Operation

− −

VOLUME READ

VRRDP

2. Set data

Operand type Description Data type

Volume number [setting range0 to 7] 16-bit binary

S 1 ‚ S

Device to which the read analog value is transferred 16-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S 1 ‚ S

FNC70-FNC79 External FX I/O Device

S 2 ‚ D

S: This function is supported only in FX3G/FX3U/FX3UC PLCs.

Explanation of function and operation

This instruction reads the analog value of a variable analog potentiometer board attached the PLC main unit.

FNC80-FNC89 External FX Device

This instruction converts the analog value of the variable analog potentiometer specified in into binary 8-bit

S 1 ‚ S

data, and transfers the numeric value ranging from 0 to 255 to .

S ‚ D ‚

VRRD

FNC100-FNC109 Data Transfer 2

Program example

1. Example in which the read analog value is used as the set value of an analog timer The analog value of the variable analog potentiometer No.0 is converted into binary 8-bit data, and the value ranging from 0 to 255 is transferred to D0. The value of D0 is used as the set value of a timer.

VRRD K0 D0

FNC140-FNC149 Data Operation 2

T0 D0

When a value larger than 255 is required as the set value of a timer, the read value multiplied by a constant using the MUL (FNC 22) instruction can be set indirectly as the timer constant.

Show 16 more labels / short text on this page
FNC40-FNC49 Data Operation · Mnemonic Operation Condition · 5 steps VRRD · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · and Type · Unit Index Con- stant · Real Number · Charac- ter String Pointer · Command · input · FNC110-FNC139 Floating Point · Read destination X000 · Volume number · FNC150-FNC159 Positioning Control
Page 472 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 472 · click to enlarge
Page 472

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.6 FNC 85 - VRRD / Volume Read

2. Example in which the analog values of the variable analog potentiometers Nos. 0 to 7 are read in turn, and used as analog timers

K0 to K7 are specified in of the VRRD instruction in accordance with the values of the variable potentiometers VR0 to VR7. Index (Z = 0 to 7) is used for indexing in the sequence below, and K0Z indicates K0 to K7.

S 1 ‚ S

Mitsubishi Electronics MELSEC FX3S — S 1 ‚ S diagram (page 472)
Fig. 405

The routine "FOR ~ NEXT" is repeated 8 times.

Analog values of variable potentiometers are stored in data registers D200 to D207.

Because T0 to T7 are 100 ms timers, 0 to 25.5 sec are obtained from the set values 0 to 255.

Cautions

  • In FX 3S PLC, the variable analog potentiometer board can be connected to the option connector. In this case, the communication function is not available when the VRRD or VRSC instruction is used.
  • In 14-point and 24-point type FX 3G PLCs, the variable analog potentiometer board can be connected to the option connector 1, and occupies communication channel ch1. In this case, the communication function using communication channel ch1 is not available when the VRRD or VRSC instruction is used.
  • In 40-point and 60-point type FX 3G PLCs, the variable analog potentiometer board can be connected only to the option connector 2, and occupies communication channel ch2. In this case, the communication function using communication channel ch2 is not available when the VRRD or VRSC instruction is used.
  • The communication function is not available for ch1 when the VRRD or VRSC instruction is used in the program in FX 3U /FX 3UC PLCs.

→ For details, refer to the Data Communication Edition manual.

  • FX 3S /FX 3G PLCs support the FX 3G -8AV-BD.
  • FX 3U /FX 3UC -32MT-LT(-2) PLCs support the FX 3U -8AV-BD.
Page 473 of the Mitsubishi Electronics MELSEC FX3S user manual — S ‚ D ‚
Page 473 · click to enlarge
Page 473

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.7 FNC 86 - VRSC / Volume Scale 11

16.7 FNC 86 - VRSC / Volume Scale

FNC30-FNC39 Rotation and Shift

Outline

This instruction reads the value of a variable analog potentiometer on the variable analog potentiometer board attached to the PLC main unit as a numeric value ranging from 0 to 10.

1. Instruction format

32-bit Instruction P FNC 86

Mnemonic Operation Condition 16-bit Instruction

VRSC

Continuous Operation Pulse (Single) Operation

− −

VOLUME SCALE

VRSCP

2. Set data

Operand type Description Data type

S 1 ‚ S

Volume number [setting range0 to 7] 16-bit binary

Device to which the read analog value is transferred 16-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FNC70-FNC79 External FX I/O Device

S 1 ‚ S

S 2 ‚ D

S: This function is supported only in FX3G/FX3U/FX3UC PLCs.

Explanation of function and operation

FNC80-FNC89 External FX Device

This instruction reads the value of a variable analog potentiometer on the variable analog potentiometer board attached to the main unit as a numeric value ranging from 0 to 10. However, the actual scale value does not always correspond to the switching position of the variable analog potentiometer scale (0 to 10).

This instruction converts into a binary value the scale value of a variable analog potentiometer specified in , and

S 1 ‚ S

transfers the converted binary value to .

FNC100-FNC109 Data Transfer 2

S ‚ D ‚

VRSC

FNC140-FNC149 Data Operation 2

Show 14 more labels / short text on this page
FNC40-FNC49 Data Operation · Mnemonic Operation Condition · 5 steps VRSC · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 474 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 474 · click to enlarge
Page 474

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.7 FNC 86 - VRSC / Volume Scale

Program example

1. Example in which the scale value is used as a rotary switch One of the auxiliary relays from M0 to M10 turns ON in accordance with the scale value ranging from 0 to 10 of the specified variable analog potentiometer.

K1 X000 FNC 86

VRSC

DECO D1 M0 K4 X001

The FNC 41 (DECO) instruction occupies auxiliary relays M0 to M15.

M0

M0 turns ON when the scale value is "0".

M1

M0 turns ON when the scale value is "1".

M10

M0 turns ON when the scale value is "10".

Cautions

  • In FX 3S PLC, the variable analog potentiometer board can be connected to the option connector. In this case, the communication function is not available when the VRRD or VRSC instruction is used.
  • In 14-point and 24-point type FX 3G PLCs, the variable analog potentiometer board can be connected to the option connector 1, and occupies communication channel ch1. In this case, the communication function using communication channel ch1 is not available when the VRRD or VRSC instruction is used.
  • In 40-point and 60-point type FX 3G PLCs, the variable analog potentiometer board can be connected only to the option connector 2, and occupies communication channel ch2. In this case, the communication function using communication channel ch2 is not available when the VRRD or VRSC instruction is used.
  • The communication function is not available for ch1 when the VRRD or VRSC instruction is used in the program in FX 3U /FX 3UC PLCs.

→ For details, refer to the Data Communication Edition manual.

  • FX 3S /FX 3G PLCs support the FX 3G -8AV-BD.
  • FX 3U /FX 3UC -32MT-LT(-2) PLCs support the FX 3U -8AV-BD.
Page 475 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 475 · click to enlarge
Page 475

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.8 FNC 87 – RS2 / Serial Communication 2 11

16.8 FNC 87 – RS2 / Serial Communication 2

FNC30-FNC39 Rotation and Shift

Outline

This instruction sends and receives data using non-protocol communication by way of serial ports in accordance with RS-232C or RS-485 provided in the main unit. In FX3G/FX3GC PLCs, data can be sent and received using non-protocol communication by way of the standard built- in port (RS-422).

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

RS2 −

2. Set data

Operand type Description Data type

Head device of data registers storing data to be sent 16-bit binary or character string

S 1 ‚ S

m Number of bytes of data to be sent [setting range: 0 to 4,096] 16-bit binary

Head device of data registers storing received data when receiving is completed 16-bit binary or character string

n Number of bytes to be received [setting range: 0 to 4,096] 16-bit binary

n1 Used channel number [contents of setting: K0 = ch0, K1 = ch1, K2 = ch2]*1 16-bit binary

FNC70-FNC79 External FX I/O Device

*1. Ch0 is available only in FX3G/FX3GC PLCs. Ch2 is not available in FX3G PLC (14-point and 24-point type) and FX3S PLC.

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC80-FNC89 External FX Device

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S 1 ‚ S

m 3 S 3 3

S 2 ‚ D

FNC100-FNC109 Data Transfer 2

n 3 S 3 3

S: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (RS2) This instruction sends and receives data using non-protocol communication by way of serial ports in accordance with RS-232C or RS-485 provided in the main unit.

→ For detailed explanation, refer to the Data Communication Edition.

input D ‚ n n1

RS2 m S ‚

FNC140-FNC149 Data Operation 2

Show 16 more labels / short text on this page
FNC40-FNC49 Data Operation · Mnemonic Operation Condition · 32-bit Instruction · 11 steps RS2 · Continuous Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · n1 3 3 · FNC110-FNC139 Floating Point · Command · FNC150-FNC159 Positioning Control
Page 476 of the Mitsubishi Electronics MELSEC FX3S user manual — FX 3U , FX 3UC -32MT-LT(-2)
Page 476 · click to enlarge
Page 476

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.8 FNC 87 – RS2 / Serial Communication 2

Related devices

→ For detailed explanation, refer to the Data Communication Edition.

Name ch0*1 ch1 ch2*1 ch0*1 ch1 ch2*1

M8371 M8401 M8421 Sending wait flag*2 D8370 D8400 D8420 Communication format setting

M8372 M8402 M8422 Sending request*2 – − − −

M8373 M8403 M8423 Receiving complete flag*2 D8372 D8402 D8422 Remaining number of data to be sent*2

– M8404 M8424 Carrier detection flag D8373 D8403 D8423 Monitor for number of received data*2

– M8405 M8425 Data Set Ready (DSR) Flag*3 – D8405 D8425 Communication parameter display

– D8379 D8409 D8429 Time-out time setting

M8379 M8409 M8429 Time-out check flag D8380 D8410 D8430 Header 1, 2

D8381 D8411 D8431 Header 3, 4

D8382 D8412 D8432 Terminator 1, 2

D8383 D8413 D8433 Terminator 3, 4

– − − −

D8384 D8414 D8434 Receiving sum (received data)

D8385 D8415 D8435 Receiving sum (calculation result)

D8386 D8416 D8436 Sending sum

D8389 D8419 D8439 Operation mode display

M8062 M8063 M8438 Serial communication error*4 D8062 D8063 D8438 Serial communication error code*4

*1. Ch0 is available only in FX3G/FX3GC PLCs. Ch2 is not available in FX3G PLC (14-point and 24-point type) and FX3S PLC.

*2. Cleared when the PLC mode is changed from RUN to STOP.

*3. Available in all FX3G/FX3GC PLCs and FX3U/FX3UC PLCs Ver. 2.30 or later.

*4. Cleared when PLC power supply is turned from OFF to ON.

System configuration

For using this instruction, it is necessary to attach one of the products shown in the table below to the main unit.

→ For the system configuration, refer to the respective PLC Hardware Edition manual.

→ For detailed explanation, refer to the Data Communication Edition manual.

PLC Communication type Option

FX3S RS-232C communication FX3G-232-BD or FX3U-232ADP(-MB) (with FX3S-CNV-ADP)

RS-485 communication FX3G-485-BD(-RJ) or FX3U-485ADP(-MB) (with FX3S-CNV-ADP)

FX3G-232BD or FX3U-232ADP(-MB) (which requires FX3G-CNV-ADP)

FX3G RS-232C communication

RS-232C/RS-422 converter*5 (FX-232AW, FX232AWC and FX-232AWC-H)

RS-485 communication FX3G-485-BD(-RJ) or FX3U-485ADP(-MB) (which requires FX3G-CNV-ADP)

FX 3U -232ADP(-MB)

FX3GC RS-232C communication

RS-232C/RS-422 converter*5 (FX-232AW, FX232AWC and FX-232AWC-H)

RS-485 communication FX3U-485ADP(-MB)

RS-232C communication FX3U-232-BD or FX3U-232ADP(-MB)

FX 3U , FX 3UC -32MT-LT(-2)

RS-485 communication FX3U-485-BD or FX3U-485ADP(-MB)

FX3UC(D,DS,DSS) RS-232C communication FX3U-232ADP(-MB)

RS-485 communication FX3U-485ADP(-MB)

*5. Required to use ch0 (standard built-in RS-422 port) in FX3G/FX3GC PLCs.

Device · Device · Name

Page 477 of the Mitsubishi Electronics MELSEC FX3S user manual — Function Changes According to Versions
Page 477 · click to enlarge
Page 477

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.8 FNC 87 – RS2 / Serial Communication 2 11

Differences between the RS (FNC 80) instruction and RS2 (FNC 87) instruction

FNC30-FNC39 Rotation and Shift

Item RS2 instruction RS instruction Remarks

Header size 1 to 4 characters (bytes) Up to 1 character (byte) For the RS2 instruction, up to 4 characters (bytes) can be specified as a header or terminator. Terminator size 1 to 4 characters (bytes) Up to 1 character (byte)

For the RS2 instruction, the check sum can be automatically attached to the sent and received data. In this case, however, make sure to use a terminator in the communication frame to be sent and received.

The check sum should be attached by a user program.

Attachment of check sum

The check sum can be automatically attached.

For the RS2 instruction: Ch0 is available only in FX3G/FX3GC PLCs. Ch2 is not available in FX3G PLC (14-point and 24-point type) and FX3S PLC.

Used channel number ch0, ch1, ch2 ch1

Cautions

  • → For other cautions, refer to the Data Communication Edition.
  • Do not drive two or more RS (FNC 80) and/or RS2 (FNC 87) instructions for the same port at the same time.
  • It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)" instruction and an "IVCK (FNC270) to IVMC (FNC275)", "ADPRW (FNC276)", "FLCRT (FNC300) to FLSTRD (FNC305)" instruction for the same port.
  • When using a header and terminator, set the data in the header and terminator to corresponding special data register (D) before executing the RS2 instruction. Do not change the values of the header and terminator while the RS2 instruction is being executed.

Function Changes According to Versions

The function of the FNC 87 instruction varies depending on the PLC version shown in the table below.

Item Function Summary FX3S FX3G FX3GC FX3U FX3UC

ch1 Data Set Ready (DSR) Flag

Turns M8405 ON when the DR (DSR) signal of ch1 is ON.

Ver. 1.00

Ver. 1.00

Ver. 1.40

Ver. 2.30

Ver. 2.30

FNC70-FNC79 External FX I/O Device

ch2 Data Set Ready (DSR) Flag

Turns M8425 ON when the DR (DSR) signal of ch2 is ON.

FNC80-FNC89 External FX Device

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 11 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Compatible Versions · or later · or later · or later · or later · or later · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 478 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 478 · click to enlarge
Page 478

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.9 FNC 88 – PID / PID Control Loop

16.9 FNC 88 – PID / PID Control Loop

Outline

This instruction executes PID control which changes the output value according to the input variation.

→ For details, refer to the Analog Control Edition.

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

PID −

2. Set data

Mitsubishi Electronics MELSEC FX3S — PID − diagram (page 478)
Fig. 406

Data register number storing the target value (SV) 16-bit binary

Data register number storing the measured value (PV) 16-bit binary

Data register number storing the output value (MV) 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 478)
Fig. 407 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (PID)

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 478)
Fig. 408 · Explanation of function and operation

When the target value , measured value , and parameters to +6 are set and a program is

executed, the operation result (MV) is stored to the output value at every sampling time .

Target value (SV) Measured value (PV) Parameter Output value (MV)

Show 4 more labels / short text on this page
Mnemonic Operation Condition · 32-bit Instruction · Continuous Operation · 9 steps PID
Page 479 of the Mitsubishi Electronics MELSEC FX3S user manual — S 3 S 3
Page 479 · click to enlarge
Page 479

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.9 FNC 88 – PID / PID Control Loop 11

2. Set items

FNC30-FNC39 Rotation and Shift

  • Set the target value (SV).
  • PID instruction does not change the contents of setting.
  • Caution on using the auto tuning (limit cycle method) If the target value for auto tuning is different from the target value for PID control, it is necessary to set a value including the bias value first, and then store the actual target value when the auto tuning flag turns OFF.

Measured value (PV) This is the input value in PID control loop. 1

1. Auto tuning: In the case of limit cycle method

Twenty-nine devices are occupied from the head device specified in . 2) Auto tuning: In the case of step response method a) Operation setting (ACT): When bits 1, 2 and 5 are not all "0"

Twenty-five devices are occupied from the head device specified in . b) Operation setting (ACT): When bits 1, 2 and 5 are all "0"

Twenty devices are occupied from the head device specified in .

1) In case of PID control (normal processing) Before driving PID instruction, the user should set the initial output value. After that, the operation result is stored. 2) Auto tuning: In the case of limit cycle method During auto tuning, the ULV or LLV value is output automatically. When auto tuning is finished, the specified MV value is set. 3) Auto tuning: In the case of step response method Before driving PID instruction, the user should set the initial output value. During auto tuning, PID instruction does not change the MV output.

*1. When auto tuning is not used, the number of points is the same as the number in the step response method are occupied.

FNC70-FNC79 External FX I/O Device

3. List of parameters to +28

S 3 S 3

Set item Setting Value Remarks

Sampling time (Ts) 1 to 32767 (ms) It cannot be shorter than the operation cycle.

FNC80-FNC89 External FX Device

bit0 0Forward operation, 1: Backward operation Operation direction

bit1 0: Input variation alarm is invalid. 1: Input variation alarm is valid.

bit2 0: Output variation alarm is invalid. 1: Output variation alarm is valid. Do not set to ON bit 2 and bit 5 at the same time.

FNC100-FNC109 Data Transfer 2

bit4 0: Auto tuning is not executed. 1: Auto tuning is executed.

0. Upper and lower limits of output value are not valid. 1: Upper and lower limits of output value are valid.

Do not set to ON bit 2 and bit 5 at the same time.

bit6 0: Step response method 1: Limit cycle method Select the auto tuning mode.

bit7 to bit15 Not available

+2 Input filter constant (α) 0 to 99 (%) When "0" is set, the input filter is not provided.

+3 Proportional gain (KP) 1 to 32767 (%)

+4 Integral time (TI) 0 to 32767 (× 100 ms) When "0" is set, it is handled as "\" (no integration).

FNC140-FNC149 Data Operation 2

+5 Derivative gain (KD) 0 to 100 (%) When "0" is set, the derivative gain is not provided.

+6 Derivative time (TD) 0 to 32767 (× 10 ms) When "0" is set, the derivative operation is not executed.

+7 :

These devices are occupied for internal processing in PID control loop. Do not change the data.

Show 17 more labels / short text on this page
Number of · Set item Description · occupied · points · Target value (SV) · FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · Parameter*1 · FMC60-FNC69 Handy Instruction · Output value (MV) · bit3 Not available · Operation setting (ACT) · +1 · bit5 · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control · +19
Page 480 of the Mitsubishi Electronics MELSEC FX3S user manual — S 3 S 3 S 3
Page 480 · click to enlarge
Page 480

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.9 FNC 88 – PID / PID Control Loop

Set item Setting Value Remarks

+20*1 Input variation (incremental) alarm set value 0 to 32767 It is valid when bit 1 is set to "1" in +1 for the operation setting (ACT).

S 3 S 3

S 3 S 3

+21*1 Input variation (decremental) alarm set value 0 to 32767 It is valid when bit 1 is set to "1" in +1 for the operation setting (ACT).

Output variation (incremental) alarm set value 0 to 32767 It is valid when bit 2 is set to "1" and bit 5 is set to

"0" in +1 for the operation setting (ACT).

It is valid when bit 2 is set to "0" and bit 5 is set to

Output upper limit set value −32768 to 32767

"1" in +1 for the operation setting (ACT).

Output variation (decremental) alarm set value 0 to 32767 It is valid when bit 2 is set to "1" and bit 5 is set to

"0" in +1 for the operation setting (ACT).

It is valid when bit 2 is set to "0" and bit 5 is set to

Output lower limit set value −32768 to 32767

"1" in +1 for the operation setting (ACT).

0. Input variation (incremental) is not exceeded. 1: Input variation (incremental) is exceeded.
0. Input variation (decremental) is not exceeded. 1: Input variation (decremental) is exceeded.

It is valid when bit 1 is set to "1" or bit 2 is set to

+24*1 Alarm output

S 3 S 3

0. Output variation (incremental) is not exceeded. 1: Output variation (incremental) is exceeded.

"1" in +1 for the operation setting (ACT).

0. Output variation (decremental) is not exceeded. 1: Output variation (decremental) is exceeded.

The setting below is required when the limit cycle method is used (when bit 6 is set to "ON" in the operation setting (ACT)).

PV value threshold (hysteresis) width (SHPV)

Set it according to the fluctuation of the measured value (PV).

+26 Output value upper limit (ULV) Set the maximum value (ULV) of the

output value (MV).

They are occupied when bit 6 is set to "ON (limit cycle method)" in the operation setting (ACT).

+27 Output value lower limit (LLV) Set the minimum value (LLV) of the output value (MV).

Wait setting from end of tuning cycle to start of PID control (Kw)

−50 to 32717%

*1. +20 to +24 are occupied when any bit 1, 2 or 5 is set to "1" in +1 for operation setting (ACT).

S 3 S 3 S 3

Show 8 more labels / short text on this page
+22*1 · +23*1 · bit0 · bit1 · bit2 · bit3 · +25 · +28
Page 481 of the Mitsubishi Electronics MELSEC FX3S user manual — Error
Page 481 · click to enlarge
Page 481

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

16 External FX Device – FNC 80 to FNC 89

16.9 FNC 88 – PID / PID Control Loop 11

Cautions

FNC30-FNC39 Rotation and Shift

1. When using two or more PID instructions Two or more PID instructions can be executed at the same time. (There is no limitation in the number of loops.)

However, make sure that , and other operands specified in each instruction are different to each other.

S 3 D

2. Number of devices occupied for parameters starting from

1. In the limit cycle method

- Twenty-nine devices are occupied from the head device specified in .

2. In the step response method - Operation setting (ACT): When bits 1, 2 and 5 are not all "0"

Twenty-five devices are occupied from the head device specified in . - Operation setting (ACT): When bits 1, 2 and 5 are all "0"

Twenty devices are occupied from the head device specified in .

3. When specifying a device in the latched area backed up against power failure For the output value (MV) in the PID instruction, specify a data register outside the latched area. When specifying a data register in the latched area, make sure to clear the latched (backed up) contents when the PLC mode is set to RUN using the following program. Program example

M8002

RST D***

Data register number in the latched area specified in D

FNC70-FNC79 External FX I/O Device

Error

When an operation error occurs, the special auxiliary relay M8067 turns ON, and the error code is stored in the special data register D8067.

→ For the error code, refer to Section 38.4.

FNC80-FNC89 External FX Device

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 6 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Initial pulse · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 482 of the Mitsubishi Electronics MELSEC FX3S user manual — ZPOP D
Page 482 · click to enlarge
Page 482

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

17 Data Transfer 2 – FNC100 to FNC109

17. Data Transfer 2 – FNC100 to FNC109

FNC100 to FNC109 provide instructions for executing complicated processing for fundamental applied instructions and for executing special processing.

FNC No. Mnemonic Symbol Function Reference

102 ZPUSH Batch Store of Index Register Section 17.1

ZPUSH D

103 ZPOP Batch POP of Index Register Section 17.2

ZPOP D

Page 483 of the Mitsubishi Electronics MELSEC FX3S user manual — ZPUSH D
Page 483 · click to enlarge
Page 483

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

17 Data Transfer 2 – FNC100 to FNC109

17.1 FNC102 – ZPUSH/Batch Store of Index Register 11

17.1 FNC102 – ZPUSH/Batch Store of Index Register

FNC30-FNC39 Rotation and Shift

Outline

This instruction temporarily batch-stores the present value of the index registers V0 to V7 and Z0 to Z7. For restoring the present value of temporarily batch-stored index registers, use the ZPOP (FNC103) instruction.

→ For the ZPOP (FNC103) instruction, refer to Section 17.2.

1. Instruction format

P FNC 102

Mnemonic Operation Condition Mnemonic Operation Condition 32-bit Instruction

ZPUSH

Continuous Operation Pulse (Single) Operation

−

ZPUSHP

−

2. Set data

Operand Type Description Data Type

Head device number batch-storing the present value of the index registers V0 to V7 and Z0 to Z7

D D

: Number of times of batch-storage

+1 to +16 × Number of times of batch-storage: Batch-stored data storage destination

D D

3. Applicable devices

Bit Devices Word Devices Others

FNC70-FNC79 External FX I/O Device

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

SExcept special data register (D)

FNC80-FNC89 External FX Device

Explanation of function and operation

1. 16-bit operation (ZPUSH/ZPUSHP)

ZPUSH D

FNC100-FNC109 Data Transfer 2

1. The contents of the index registers V0 to V7 and Z0 to Z7 are batch-stored temporarily to and later. When

the contents of index registers are batch-stored, the number of times of batch-storage is incremented by "1".

2. For restoring the batch-stored data, use the ZPOP (FNC103) instruction. Use the ZPUSH (FNC102) and ZPOP (FNC103) instruction as a pair.
3. By specifying the same device to , ZPUSH (FNC102) and ZPOP (FNC103) instructions can be used in the nest structure.

In this case, the occupied points are incremented by "16" after every time the ZPUSH (FNC102) instruction is executed. Secure sufficient area for the number of the next structure in advance.

FNC140-FNC149 Data Operation 2

Show 15 more labels / short text on this page
FNC40-FNC49 Data Operation · 16-bit Instruction · 3 steps ZPUSH · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · 16-bit binary · Oper- · and Type · Unit Index Con- stant · Real Number · Charac- ter String Pointer · Command · input FNC102 · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 484 of the Mitsubishi Electronics MELSEC FX3S user manual — Errors
Page 484 · click to enlarge
Page 484

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

17 Data Transfer 2 – FNC100 to FNC109

17.1 FNC102 – ZPUSH/Batch Store of Index Register

4. The figure below shows the data structure batch-stored in and later.

· When the nest structure is not used Index register Batch- stored data

· When the nest structure is used Index register

[1] ZPUSH instruction Number of times of batch-storage is incremented by "1". 16 points for 1 nesting

Z0 V0 Z1 V1 Z2 V2

D D

Z0 V0 Z1 V1 Z2

[1] ZPUSH instruction Number of times of batch-storage : 0 → 1

Z0 V0 Z1 V1 Z2 V2

Z0 V0 Z1 V1 Z2

1st nesting Number of

[4] ZPOP instruction Number of times of batch-storage : → 0

[2] ZPOP instruction Number of times of batch-storage is decremented by "1".

Z7 V7

Z7 V7

Z7 V7

Z7 V7

[2] ZPUSH instruction Number of times of batch-storage : 1 → 2

Z0 V0 Z1 V1

2nd nesting Number of

[3] ZPOP instruction Number of times of batch-storage : 2 → 1

*1 Number of times of batch-storage

Related instruction

ZPOP (FNC103) Restores the index registers V0 to V7 and Z0 to Z7 which were batch-stored temporarily by the ZPUSH (FNC102) instruction.

Cautions

  • When not using the nest structure, clear the number of batch-storage times before executing ZPUSH (FNC102) instruction.
  • When using the nest structure, clear the number of batch-storage times before executing ZPUSH (FNC102) instruction the first time.

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When the range of points used after in ZPUSH (FNC102) instruction exceeds the corresponding device range (error code: K6706)
  • When the number of batch-storage times stores a negative value while the ZPUSH (FNC102) instruction is executed (error code: K6706)
Show 20 more labels / short text on this page
Batch- stored data · *1 +1 +0 · *1 +1 +0 · +3 +2 · +3 +2 · +5 +4 · times of · +5 +4 · batch- storage · = 1 · +6 · +16 +15 · +16 +15 · +17 · +19 +18 · times of · batch- storage · +20 · = 2 · Instruction Description
Page 485 of the Mitsubishi Electronics MELSEC FX3S user manual — 17.1 FNC102 – ZPUSH/Batch Store of Index Register 11
Page 485 · click to enlarge
Page 485

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

17 Data Transfer 2 – FNC100 to FNC109

17.1 FNC102 – ZPUSH/Batch Store of Index Register 11

Mitsubishi Electronics MELSEC FX3S — 17.1 FNC102 – ZPUSH/Batch Store of Index Register 11 diagram (page 485)
Fig. 409 · 17.1 FNC102 – ZPUSH/Batch Store of Index Register 11

In the program shown below, the contents of the index registers Z0 to Z7 and V0 to V7 before execution of subroutine program are batch-stored in D0 and later when index registers are used in the subroutine after the pointer P0.

Page 486 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 486 · click to enlarge
Page 486

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

17 Data Transfer 2 – FNC100 to FNC109

17.2 FNC103 – ZPOP/Batch POP of Index Register

17.2 FNC103 – ZPOP/Batch POP of Index Register

Outline

This instruction restores the contents of the index registers V0 to V7 and Z0 to Z8 which were batch-stored temporarily by ZPUSH (FNC102) instruction.

→ For ZPUSH (FNC102) instruction, refer to Section 17.1.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 486)
Fig. 410 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 486)
Fig. 411 · 2. Set data

Head device number temporarily batch-storing the contents of the index registers V0 to V7 and Z0 to Z7

+1 to +16 × Number of times of batch-storage: Batch-stored data storage destination

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 486)
Fig. 412 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

SExcept special data register (D)

Explanation of function and operation

1. 16-bit operation (ZPOP/ZPOPP) → For the function and operation, refer also to Section 17.1.

ZPOP D

1. The contents of the index registers V0 to V7 and Z0 to Z7 which were batch-stored temporarily to and later are restored to the original index registers. When the contents of the index registers are restored, the number of

times of batch-storage is decremented by "1".

2. For temporarily batch-storing the data, use ZPUSH (FNC102) instruction. Use ZPUSH (FNC102) and ZPOP (FNC103) instruction as a pair.

Related instruction

ZPUSH (FNC102) Temporarily batch-stores the present value of the index registers V0 to V7 and Z0 to Z7.

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When the number of times of batch-storage (D) stores "0" or a negative value while ZPOP (FNC103) instruction is executed (error code: K6706)

Program example

→ For a program example, refer to Section 17.1.

Command · input FNC103 · Instruction Description

Page 487 of the Mitsubishi Electronics MELSEC FX3S user manual — 18. Floating Point – FNC110 to FNC139
Page 487 · click to enlarge
Page 487

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

Mitsubishi Electronics MELSEC FX3S — 18. Floating Point – FNC110 to FNC139 diagram (page 487)
Fig. 413 · 18. Floating Point – FNC110 to FNC139

FNC110 to FNC119, FNC120 to FNC129 and FNC130 to FNC139 provide instructions for conversion, comparison, arithmetic operations, square root operation, trigonometry, etc. for floating point operations.

116 ESTR Floating Point to Character String Conversion Section 18.4

117 EVAL Character String to Floating Point Conversion Section 18.5

118 EBCD Floating Point to Scientific Notation Conversion Section 18.6

119 EBIN Scientific Notation to Floating Point Conversion Section 18.7

Page 488 of the Mitsubishi Electronics MELSEC FX3S user manual — 18. Floating Point – FNC110 to FNC139
Page 488 · click to enlarge
Page 488

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

Mitsubishi Electronics MELSEC FX3S — 18. Floating Point – FNC110 to FNC139 diagram (page 488)
Fig. 414 · 18. Floating Point – FNC110 to FNC139
Page 489 of the Mitsubishi Electronics MELSEC FX3S user manual — D D D D
Page 489 · click to enlarge
Page 489

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.1 FNC110 – ECMP / Floating Point Compare 11

18.1 FNC110 – ECMP / Floating Point Compare

FNC30-FNC39 Rotation and Shift

Outline

This instruction compares two data values (binary floating point), and outputs the result (larger, same or smaller) to three consecutive bit devices.

→ For handling of floating point, refer to Subsection 5.1.3. 1. Instruction format

P FNC 110

Mnemonic Operation Condition 16-bit Instruction

Mnemonic Operation Condition 32-bit Instruction

ECMP D −

13 steps Continuous Operation Pulse (Single) Operation

DECMP

DECMPP

2. Set data

Operand Type Description Data Type

Device number storing binary floating point data to be compared

Real number (binary)*1 Device number storing binary floating point data to be compared

Head bit device number to which the comparison result is output (Three devices are occupied.) Bit

*1. When a constant (K or H) is specified, it is automatically converted from binary into binary floating point (real number) when the instruction is executed. 3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC70-FNC79 External FX I/O Device

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S2 S3

3 S2 S3

FNC80-FNC89 External FX Device

S1: "D .b" is available only in FX3U/FX3UC PLCs, and cannot be indexed with index registers (V and Z). S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S3: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 32-bit operation (DECMP and DECMPP) The comparison value [ +1, ] is compared with the comparison source [ +1, ] as floating point data, and one of the bits among , +1 and +2 turns ON according to the result (smaller, same or larger).

S 1 S 1 S 2 S 2

FNC100-FNC109 Data Transfer 2

D D D

  • When a constant (K or H) is specified as [ +1, ] or [ +1, ], it is automatically converted from binary into binary floating point (real number) when the instruction is executed.

S 1 S 1 S 2 S 2

S 1 S 2 D

Turns ON in the case of

] ". +1, " [ ] S1 S1 +1, [ S2 S2 >

Turns ON in the case of

= +1, ] S1 S1 +1, [ S2 S2 " [ ] ".

Turns ON in the case of

FNC140-FNC149 Data Operation 2

+1, ] S1 S1 +1, [ S2 S2 " [ ] ".

Even if the command input turns OFF before the DECMP instruction is fully executed, to +2 hold the status.

D D

Caution

1. Number of occupied devices Three devices are occupied from ( , +1 and +2). Make sure that these devices are not used for any other purpose.

D

Show 15 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input FNC110 DECMP · FNC110-FNC139 Floating Point · +1 · +2 · < · FNC150-FNC159 Positioning Control
Page 490 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Applicable devices
Page 490 · click to enlarge
Page 490

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.2 FNC111 – EZCP / Floating Point Zone Compare

18.2 FNC111 – EZCP / Floating Point Zone Compare

Outline

This instruction compares data (binary floating point) with two values (one zone), and outputs the comparison result to three consecutive bit devices.

→ For handling of floating point, refer to Subsection 5.1.3.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 490)
Fig. 415 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 490)
Fig. 416 · 2. Set data

Data register number storing binary floating point data to be compared

Real number (binary)*1 Data register number storing binary floating point data to be compared

Data register number storing binary floating point data to be compared

Head bit device number to which the comparison result is output (Three devices are occupied.) Bit

*1. When a constant (K or H) is specified, it is automatically converted from binary into binary floating point (real number) when the instruction is executed.

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 490)
Fig. 417 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S: "D .b" cannot be indexed with index registers (V and Z).

Page 491 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 1 S 2 S 2
Page 491 · click to enlarge
Page 491

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.2 FNC111 – EZCP / Floating Point Zone Compare 11

Explanation of function and operation

FNC30-FNC39 Rotation and Shift

1. 32-bit operation (DEZCP and DEZCPP)

The comparison values [ +1, ], [ +1, ] are compared with the comparison source [ +1,

S1 S1 S2 S2 S

] as floating point data, and one of the bits among , +1, and +2 turns ON according to the result (smaller, same or larger).

S D D D

  • When a constant (K or H) is specified as [ +1, ], [ +1, ], or [ +1, ], it is automatically converted into binary floating point when the instruction is executed.

S1 S1 S2 S2 S S

S1 S2 S D

EDZCP

Turns ON in the case of

+1, [ S S +1, ] S1 S1 ] ". " [ >

Turns ON in the case of

+1, [ S S ] +1, ] S1 S1 +1, [ S2 S2 ] ". " [

Turns ON in the case of

+1, S S ] +1, [ S2 S2 ] ". " [

Even if the command input turns OFF before the DEZCP instruction is fully executed, to +2 will hold their previous status.

D D

Cautions

FNC70-FNC79 External FX I/O Device

1. Number of occupied devices

Three devices are occupied from ( , +1 and +2). Make sure that these devices are not used for any other purpose.

D

2. Comparison values [ +1, ] and [ +1, ] Make sure that two comparison values have the following relationship:

S 1 S 1 S 2 S 2

FNC80-FNC89 External FX Device

[ +1, ] ≤ [ +1, ]

S 1 S 1 S 2 S 2

In the case of "[ +1, ] > [ +1, ]", the value [ +1, ] is regarded as [ +1, ] value during comparison.

S1 S1 S2 S1 S1

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 10 more labels / short text on this page
FNC40-FNC49 Data Operation · Command · input FNC 111 · FNC50-FNC59 High-Speed Processing · +1 · +2 · > · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 492 of the Mitsubishi Electronics MELSEC FX3S user manual — Program examples
Page 492 · click to enlarge
Page 492

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.3 FNC112 – EMOV / Floating Point Move

18.3 FNC112 – EMOV / Floating Point Move

Outline

This instruction transfers binary floating point data.

→ For handling of floating point, refer to Subsection 5.1.3.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 492)
Fig. 418 · 1. Instruction format

2. Set data

Operand Type Description Data Type

Binary floating point data (transfer source) or device number storing data

Real number (binary) Device number receiving floating point data

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 492)
Fig. 419 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 32 bit operation (DEMOV and DEMOPV)

The contents (binary floating point data) of the transfer source [ +1, ] are transferred to [ +1, ].

S S D D

A real number (E) can be directly specified as .

Mitsubishi Electronics MELSEC FX3S — S S D D diagram (page 492)
Fig. 420

+1 +1 S ‚ D ‚ S ‚ D ‚ Command

Program examples

1. In the program example shown below, a real number stored in D11 and D10 is transferred to D1 and D0 when X007 turns ON
Mitsubishi Electronics MELSEC FX3S — Program examples diagram (page 492)
Fig. 421 · Program examples
2. In the program shown below, a real number "-1.23" is transferred to D11 and D10 when X007 turns ON
Mitsubishi Electronics MELSEC FX3S — Program examples diagram (page 492)
Fig. 422 · Program examples
Page 493 of the Mitsubishi Electronics MELSEC FX3S user manual — S 2 S 2 S 2 D
Page 493 · click to enlarge
Page 493

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.4 FNC116 – ESTR / Floating Point to Character String Conversion 11

18.4 FNC116 – ESTR / Floating Point to Character String Conversion

FNC30-FNC39 Rotation and Shift

Outline

This instruction converts binary floating point data into a character string (ASCII codes) having a specified number of digits. On the other hand, STR (FNC200) instruction converts binary data into a character string (ASCII codes).

→ For a character string, refer to Section 5.3. → For handling of floating point, refer to Subsection 5.1.3.

→ For STR (FNC200) instruction, refer to Section 26.1.

1. Instruction format

P FNC 116

Mnemonic Operation Condition 16-bit Instruction

Mnemonic Operation Condition 32-bit Instruction

ESTR D

− −

13 steps Continuous Operation Pulse (Single) Operation

DESTR

DESTRP

2. Set data

Operand Type Description Data Type

Binary floating point data to be converted or device storing data Real number (binary)

Head device number storing the display specification of a numeric value to be converted 16-bit binary

Head device number storing converted character string Character string

3. Applicable devices

FNC70-FNC79 External FX I/O Device

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

FNC80-FNC89 External FX Device

3

3

Explanation of function and operation

1. 32-bit operation (DESTR and DESTRP)

FNC100-FNC109 Data Transfer 2

The contents (binary floating point data) of [ +1, ] are converted into a character string according to the

S 1 S 1

contents specified by , +1 and +2, and then stored to devices and later. A real number can

S 2 S 2 S 2 D

be directly specified as .

DESTR S1 ‚ S2 ‚ D ‚

  • The data after conversion varies depending on the display specification stored in .
0. Decimal point format 1: Exponent format Total number of

The data after conversion varies depending on the display specification stored in .

digits Number of digits

2 to 24 can be set.

FNC140-FNC149 Data Operation 2

Show 15 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input FNC116 · FNC110-FNC139 Floating Point · +1 · +2 · of decimal part · FNC150-FNC159 Positioning Control
Page 494 of the Mitsubishi Electronics MELSEC FX3S user manual — 2. In the case of decimal point format
Page 494 · click to enlarge
Page 494

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.4 FNC116 – ESTR / Floating Point to Character String Conversion

2. In the case of decimal point format

Mitsubishi Electronics MELSEC FX3S — 2. In the case of decimal point format diagram (page 494)
Fig. 423 · 2. In the case of decimal point format

ASCII code in "(specified total number of digits - 1)"th

ASCII code in "(specified total number of digits - 3)"th

ASCII code in "(specified total number of digits - 2)"th

ASCII code in "(specified total number of digits - 5)"th

ASCII code in "(specified total number of digits - 7)"th

ASCII code in "(specified total number of digits - 6)"th

0000H is automatically stored at the end of the character string.

  • The total number of digits which can be specified by +1 is as follows (24 digits maximum): When the number of digits of the decimal part is "0", Total number of digits ≥ 2 When the number of digits of the decimal part is any value other than "0", Total number of digits ≥ (Number of digits of decimal part + 3)
  • The number of digits of the decimal part which can be specified by +2 is from 0 to 7. However, the following must be satisfied, "Number of digits of decimal part ≤ (Total number of digits - 3)"

For example, when the total number of digits is "8", the number of digits of the decimal part is "3", and

"-1.23456" is specified, data is stored in and later as shown below:

Mitsubishi Electronics MELSEC FX3S — 2. In the case of decimal point format diagram (page 494)
Fig. 424 · 2. In the case of decimal point format

0000H is automatically stored at the end of the character string.

  • The character string data after conversion is stored in the devices and later as shown below: - For the sign, "20H (space)" is stored when the binary floating point data is positive, and "2DH (-)" is stored when the data is negative. - If the decimal part of the binary floating point data cannot be accommodated in the number of digits of the decimal part, low-order digits of the decimal part are rounded.
Mitsubishi Electronics MELSEC FX3S — 2. In the case of decimal point format diagram (page 494)
Fig. 425 · 2. In the case of decimal point format
Page 495 of the Mitsubishi Electronics MELSEC FX3S user manual — 0000H
Page 495 · click to enlarge
Page 495

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.4 FNC116 – ESTR / Floating Point to Character String Conversion 11

- When the number of digits of the decimal part is set to any value other than "0", "2EH (.)" is automatically stored in "specified number of digits of decimal part + 1"th digit. When the number of digits of the decimal part is "0", "2EH (.)" is not stored.

FNC30-FNC39 Rotation and Shift

0. Decimal point format

8 (Total number of digits)

2 (Number of digits of decimal part)

Low-order digits of decimal part

S 1 ‚ S 1 ‚

Automatically added. +1

−1.23456

- When the total number of digits subtracted by the digits for sign, decimal point and decimal part is larger than the integer part of the binary floating point data, "20H (space)" is stored between the sign and the integer part.

Low-order digits of decimal part

S 1 ‚ S 1 ‚

"20H (space)" is stored. +1

−1.23456

- "00H" or "0000H" is automatically stored at the end of the converted character string.

3. In the case of exponent format

FNC70-FNC79 External FX I/O Device

ASCII code in "(specified total number of digits - 1)"th

S 2 ‚ D ‚

ASCII code for sign

digits Number of digits

ASCII code for decimal point

ASCII code in "(specified total number of digits - 2)"th

(.) (2EH)

ASCII code in "(specified total number of digits - 5)"th

ASCII code in "(specified total number of digits - 4)"th

FNC80-FNC89 External FX Device

E

ASCII code in "(specified total number of digits - 7)"th

ASCII code in "(specified total number of digits - 6)"th

ASCII code of sign

45H(E)

Automatically added.

ASCII code in "(specified

ASCII code in "(specified

FNC100-FNC109 Data Transfer 2

total number of digits - 10)"th digit (exponent part) +5

total number of digits - 11)"th digit (exponent part)

0000H

0000H is automatically stored at the end of the character string.

  • The total number of digits which can be specified by +1 is as follows (24 digits maximum): When the number of digits of the decimal part is "0" Total number of digits ≥ 6 When the number of digits of the decimal part is any value other than "0" Total number of digits ≥ (Number of digits of decimal part + 7)

FNC140-FNC149 Data Operation 2

Show 37 more labels / short text on this page
Total number of · +1 · digits · +2 · FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · Total number of · +1 · digits · +2 · FMC60-FNC69 Handy Instruction · b15 · b8 b7 b0 · Exponent format · digit · +1 · Total number of · +1 · +2 · digit · of decimal part · +2 · digit (decimal part) · digit (decimal part) · +3 · digit (decimal part) · digit (decimal part) · Sign (integer part) · Sign (exponent part) · +4 · (exponent part) · +1 · Binary floating point · (real number) · +6 · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 496 of the Mitsubishi Electronics MELSEC FX3S user manual — 18.4 FNC116 – ESTR / Floating Point to Character String Conversion
Page 496 · click to enlarge
Page 496

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.4 FNC116 – ESTR / Floating Point to Character String Conversion

  • The number of digits of the decimal part which can be specified by +2 is from 0 to 7. However, the following must be satisfied, "Number of digits of decimal part ≤ (Total number of digits - 7)"

For example, when the total number of digits is "12", the number of digits of the decimal part is "4", and

"-12.34567" is specified, data is stored in and later as shown below:

Mitsubishi Electronics MELSEC FX3S — 18.4 FNC116 – ESTR / Floating Point to Character String Conversion diagram (page 496)
Fig. 426 · 18.4 FNC116 – ESTR / Floating Point to Character Str…

0000H is automatically stored at the end of the character string.

  • The character string data after conversion is stored in the devices and later as shown below: - For the sign of the integer part, "20H (space)" is stored when the binary floating point data is positive, and "2DH (-)" is stored when the data is negative. - The integer part is fixed to 1 digit. "20H (space)" is stored between the integer part and the sign.
Mitsubishi Electronics MELSEC FX3S — 18.4 FNC116 – ESTR / Floating Point to Character String Conversion diagram (page 496)
Fig. 427 · 18.4 FNC116 – ESTR / Floating Point to Character Str…

- If the decimal part of the binary floating point data cannot be accommodated in the number of digits of the decimal part, low-order digits of the decimal part are rounded.

Mitsubishi Electronics MELSEC FX3S — 18.4 FNC116 – ESTR / Floating Point to Character String Conversion diagram (page 496)
Fig. 428 · 18.4 FNC116 – ESTR / Floating Point to Character Str…

0 2 3 4 6 E + 1 1 6 7

- When the number of digits of the decimal part is set to any value other than "0", "2EH (.)" is automatically stored in "specified number of digits of decimal part + 1"th digit. When the number of digits of the decimal part is "0", "2EH (.)" is not stored.

Mitsubishi Electronics MELSEC FX3S — 18.4 FNC116 – ESTR / Floating Point to Character String Conversion diagram (page 496)
Fig. 429 · 18.4 FNC116 – ESTR / Floating Point to Character Str…

0 2 3 4 6 E + 1 1

Number of digits of decimal part (4) Automatically added. +1

- For the sign of the exponent part, "2BH (+)" is stored when the exponent is positive, and "2DH (-)" is stored when the exponent is negative.

Page 497 of the Mitsubishi Electronics MELSEC FX3S user manual — Errors
Page 497 · click to enlarge
Page 497

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.4 FNC116 – ESTR / Floating Point to Character String Conversion 11

- The exponent part is fixed to 2 digits. When the exponent part is 1 digit, "30H (0)" is stored after the sign of the exponent part.

FNC30-FNC39 Rotation and Shift

Total number of digits (12)

Fixed to 2 digits.

2 3 4 6 E + 1 1

S 1 ‚ S 1 ‚

"30H (0)" is stored.

−12.34567

- "00H" or "0000H" is automatically stored at the end of the converted character string.

Related instructions

EVAL (FNC117) Converts a character string (ASCII codes) into binary floating point data.

STR (FNC200) Converts binary data into a character string (ASCII codes).

VAL (FNC201) Converts a character string (ASCII codes) into binary data.

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When is not located within the following range (error code: K6706)

0, ±2−126 ≤ < ±2128

  • When the format specified by is any value other than "0" or "1" (error code: K6706)

FNC70-FNC79 External FX I/O Device

  • When the total number of digits specified by +1 is not located within the following range (error code: K6706) In the case of decimal point format:

When the number of digits of the decimal part is "0", Total number of digits ≥ 2 When the number of digits of the decimal part is any value other than "0", Total number of digits ≥ (Number of digits of decimal part + 3) In the case of exponent format:

FNC80-FNC89 External FX Device

When the number of digits of the decimal part is "0", Total number of digits ≥ 6 When the number of digits of the decimal part is any value other than "0", Total number of digits ≥ (Number of digits of decimal part + 7)

  • When the number of digits of the decimal part specified by +2 is not located within the following range (error code: K6706) In the case of decimal point format: Number of digits of decimal part ≤ (Total number of digits - 3) In the case of exponent format: Number of digits of decimal part ≤ (Total number of digits - 7)

FNC100-FNC109 Data Transfer 2

  • When the devices storing a character string specified by exceeds the allowable device range (error code: K6706)
  • When the conversion result exceeds the specified total number of digits (error code: K6706)

FNC140-FNC149 Data Operation 2

Show 9 more labels / short text on this page
+1 · +2 · FNC40-FNC49 Data Operation · +1 · FNC50-FNC59 High-Speed Processing · Instruction Description · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 498 of the Mitsubishi Electronics MELSEC FX3S user manual — Program examples
Page 498 · click to enlarge
Page 498

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.4 FNC116 – ESTR / Floating Point to Character String Conversion

Program examples

1. In the program example shown below, the contents (binary floating point data) of R0 and R1 are converted according to the contents specified by R10 to R12, and then stored to D0 and later when X000 turns ON
Mitsubishi Electronics MELSEC FX3S — Program examples diagram (page 498)
Fig. 430 · Program examples

Conversion format Total number of digits Number of digits of decimal part

00H is automatically stored at the end of the character string.

2. In the program shown below, the contents (binary floating point data) of R0 and R1 are converted according to the contents specified by R10 to R12, and then stored to D10 and later when X000 turns ON
Mitsubishi Electronics MELSEC FX3S — Program examples diagram (page 498)
Fig. 431 · Program examples

Conversion format Total number of digits Number of digits of decimal part

Number of digits of decimal part Space R1 R0 0.0327457 20H(space)

0000H is automatically stored at the end of the character string.

Page 499 of the Mitsubishi Electronics MELSEC FX3S user manual — 00H
Page 499 · click to enlarge
Page 499

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.5 FNC117 – EVAL / Character String to Floating Point Conversion 11

18.5 FNC117 – EVAL / Character String to Floating Point Conversion

FNC30-FNC39 Rotation and Shift

Outline

This instruction converts a character string (ASCII codes) into binary floating point data. On the other hand, the VAL (FNC201) instruction converts a character string (ASCII codes) into binary data.

→ For a character string, refer to Section 5.3. → For handling of floating point, refer to Subsection 5.1.3.

→ For VAL (FNC201) instruction, refer to Section 26.2.

1. Instruction format

P FNC 117

Mnemonic Operation Condition 16-bit Instruction

Mnemonic Operation Condition 32-bit Instruction

EVAL D

− −

9 steps Continuous Operation Pulse (Single) Operation

DEVAL

DEVALP

2. Set data

Operand Type Description Data Type

Head device number storing character string data to be converted into binary floating point data Character string

Head device number storing converted binary floating point data Real number (binary)

3. Applicable devices

Bit Devices Word Devices Others

FNC70-FNC79 External FX I/O Device

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

FNC80-FNC89 External FX Device

Explanation of function and operation

1. 32-bit operation (DEVAL and DEVALP)

A character string stored in and later is converted into binary floating point, and stored to [ +1, ].

S D D

FNC100-FNC109 Data Transfer 2

DEVAL S ‚ D ‚

A specified character string may be in the decimal point format or exponent format. A character string in either format can be converted into binary floating point data.

b15 b8 b7 b0

ASCII code for 1st character

ASCII code for sign

D ‚ S ‚

ASCII code for 3rd character

ASCII code for 2nd character

ASCII code for 5th character

ASCII code for 4th character

ASCII code for 7th character

ASCII code for 6th character

00H

FNC140-FNC149 Data Operation 2

Indicates the end of the character string.

Show 19 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input FNC117 · FNC110-FNC139 Floating Point · +1 · +1 · +2 · Binary floating point · +3 · (real number) · +4 · FNC150-FNC159 Positioning Control
Page 500 of the Mitsubishi Electronics MELSEC FX3S user manual — 18.5 FNC117 – EVAL / Character String to Floating Point Conversion
Page 500 · click to enlarge
Page 500

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.5 FNC117 – EVAL / Character String to Floating Point Conversion

a) In the case of decimal point format

Mitsubishi Electronics MELSEC FX3S — 18.5 FNC117 – EVAL / Character String to Floating Point Conversion diagram (page 500)
Fig. 432 · 18.5 FNC117 – EVAL / Character String to Floating Po…

b) In the case of exponent format

Mitsubishi Electronics MELSEC FX3S — 18.5 FNC117 – EVAL / Character String to Floating Point Conversion diagram (page 500)
Fig. 433 · 18.5 FNC117 – EVAL / Character String to Floating Po…

3 2 0 1 1 + 1 0 E

  • When a character string to be converted into binary floating point specified by has 7 digits or more excluding the sign, decimal point and exponent part, the conversion result may contain rounding error.

a) In the case of decimal point format

Mitsubishi Electronics MELSEC FX3S — 18.5 FNC117 – EVAL / Character String to Floating Point Conversion diagram (page 500)
Fig. 434 · 18.5 FNC117 – EVAL / Character String to Floating Po…

3 0 1 1 5 8 1 2 6

Page 501 of the Mitsubishi Electronics MELSEC FX3S user manual — 00H
Page 501 · click to enlarge
Page 501

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.5 FNC117 – EVAL / Character String to Floating Point Conversion 11

b) In the case of exponent format

FNC30-FNC39 Rotation and Shift

b15 b8 b7 b0

20H(.)

2DH(-)

2EH(.)

31H(1)

35H(5)

33H(3)

D ‚ D ‚

33H(3)

30H(0)

− 1.35034E − 2

Up to 6 digits are securely equivalent.

31H(1)

34H(4)

45H(E) 32H(2)

30H(0) 2DH(-)

00H

32H(2)

5 0 3 3 4 2 E 1 1 0 2

Rounded.

  • When "2BH (+)" is specified as the sign in the floating point format or when the sign is omitted, a character string is converted into a positive value. When "2DH (-)" is specified as the sign, a character string is converted into a negative value.
  • When "2BH (+)" is specified as the sign in the exponent format or when the sign is omitted, a character string is converted into a positive exponent. When "2DH (-)" is specified as the sign, a character string is converted into a negative exponent.
  • When "20H (space)" or "30H (0)" exists between numbers except the first "0" in a character string specified by

, "20H" or "30H" is ignored during conversion.

FNC70-FNC79 External FX I/O Device

b15 b8 b7 b0

2DH(-)

31H(1)

30H(0)

D ‚ D ‚

32H(2)

2EH(.)

−1.231

FNC80-FNC89 External FX Device

31H(1)

33H(3)

00H

2 3 1 1 0

Ignored.

FNC100-FNC109 Data Transfer 2

  • When "30H (0)" exists between a number and "E" in a character string in the exponent format, "30H" is ignored during conversion.

b15 b8 b7 b0

2DH(-)

2EH(.)

31H(1)

34H(4)

30H(0)

D ‚ D ‚

33H(3)

35H(5)

− 1.0453E+3

2BH(+)

45H(E)

33H(3) 30H(0)

FNC140-FNC149 Data Operation 2

00H

4 5 3 0 E 0 3 + 1

Ignored.

  • A character string can consist of up to 24 characters. "20H (space)" and "30H (0)" in a character string are counted as one character respectively.
Show 24 more labels / short text on this page
+1 · +2 · +1 · FNC40-FNC49 Data Operation · +3 · +4 · +5 · Binary floating point · +6 · (real number) · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · 20H(space) · +1 · +1 · +2 · +3 · Binary floating point · (real number) · +4 · 20H(space) · FNC110-FNC139 Floating Point · +1 · FNC150-FNC159 Positioning Control
Page 502 of the Mitsubishi Electronics MELSEC FX3S user manual — Program examples
Page 502 · click to enlarge
Page 502

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.5 FNC117 – EVAL / Character String to Floating Point Conversion

Related devices

→ For the use methods of the zero, borrow and carry flags, refer to Subsection 6.5.2.

Mitsubishi Electronics MELSEC FX3S — Related devices diagram (page 502)
Fig. 435 · Related devices

M8020 Zero flag The conversion result is true "0". (The mantissa part is "0".) The zero flag M8020 turns ON.

M8021 Borrow flag The absolute value of the conversion result

The value of is the minimum value (2−126) of 32-bit real numbers and the borrow flag M8021 turns ON.

M8022 Carry flag The absolute value of the conversion result

The value of is the maximum value (2128) of 32-bit real numbers and the carry flag M8022 turns ON.

Related instructions

Mitsubishi Electronics MELSEC FX3S — Related instructions diagram (page 502)
Fig. 436 · Related instructions

ESTR (FNC116) Converts binary floating point data into a character string (ASCII codes).

STR (FNC200) Converts binary data into a character string (ASCII codes).

VAL (FNC201) Converts a character string (ASCII codes) into binary data.

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When any character other than "30H (0)" to "39H (9)" exists in the integer part or decimal part (error code: K6706)
  • When "2EH (.)" exists in two or more positions in a character string specified by (error code: K6706)
  • When any character other than "45H (E)", "2BH (+)" or "2DH (-)" exists in the exponent part, or when two or more exponent parts exist (error code: K6706)
  • When "00H" does not exist in the corresponding device range starting from (error code: K6706)
  • When the number of characters after is "0" or more than "24" (error code: K6706)

Program examples

1. In the program example shown below, a character string stored in R0 and later is converted into binary floating point, and stored to D0 and D1 when X000 turns ON
Mitsubishi Electronics MELSEC FX3S — Program examples diagram (page 502)
Fig. 437 · Program examples
Page 503 of the Mitsubishi Electronics MELSEC FX3S user manual — 18.5 FNC117 – EVAL / Character String to Floating Point Conversion 11
Page 503 · click to enlarge
Page 503

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.5 FNC117 – EVAL / Character String to Floating Point Conversion 11

Mitsubishi Electronics MELSEC FX3S — 18.5 FNC117 – EVAL / Character String to Floating Point Conversion 11 diagram (page 503)
Fig. 438 · 18.5 FNC117 – EVAL / Character String to Floating Po…
2. In the program shown below, a character string stored in D10 and later is converted into binary floating point, and stored to D100 and D101 when X000 turns ON

The value of is the minimum value (2−126) of 32-bit real numbers and the borrow flag M8021 turns ON.

The value of is the maximum value (2128) of 32-bit real numbers and the carry flag M8022 turns ON.

The conversion result is true "0". (The mantissa part is "0".) The zero flag M8020 turns ON.

Page 504 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 504 · click to enlarge
Page 504

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.6 FNC118 – EBCD / Floating Point to Scientific Notation Conversion

18.6 FNC118 – EBCD / Floating Point to Scientific Notation Conversion

Outline

This instruction converts binary floating point into scientific notation.

→ For handling of floating point, refer to Subsection 5.1.3.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 504)
Fig. 439 · 1. Instruction format

2. Set data

Operand Type Description Data Type

Data register number storing binary floating point Real number (binary)

Data register number storing converted scientific notation Real number (decimal)

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 504)
Fig. 440 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 32-bit operation (DEBCD and DEBCDP)

Binary floating point stored in [ +1, ] is converted into scientific notation, and transferred to [ +1, ].

S S D

Mitsubishi Electronics MELSEC FX3S — S S D diagram (page 504)
Fig. 441

S ‚ D ‚ [ +1, ] → [ +1, ] S ‚ S ‚ D ‚ D ‚

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 b31 b30 b29 b28 b27 b26 b25 b24 b23 b22 b21 b20 b19 b18 b17 b16 Before execution Mantissa part (23 bits)

Low order b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 High order

b31 b30 b29 b28 b27 b26 b25 b24 b23 b22 b21 b20 b19 b18 b17 b16 After execution Mantissa part Exponent part

Caution

1. Handling of floating point In floating point operations, all data is handled in binary floating point. Because binary floating point is difficult to understand (requiring a dedicated monitoring method), it is converted into scientific notation so that monitoring can be easily executed by peripheral equipment. GX Works2, GX Developer and GOT have the function to directly monitor and display binary floating point.
Page 505 of the Mitsubishi Electronics MELSEC FX3S user manual — D ‚ D ‚
Page 505 · click to enlarge
Page 505

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.7 FNC119 – EBIN / Scientific Notation to Floating Point Conversion 11

18.7 FNC119 – EBIN / Scientific Notation to Floating Point Conversion

FNC30-FNC39 Rotation and Shift

Outline

This instruction converts scientific notation stored in devices into binary floating point.

→ For handling of floating point, refer to Subsection 5.1.3.

1. Instruction format

P FNC 119

Mnemonic Operation Condition 16-bit Instruction

Mnemonic Operation Condition 32-bit Instruction

EBIN D −

9 steps Continuous Operation Pulse (Single) Operation

DEBIN

DEBINP

2. Set data

Operand Type Description Data Type

Data register number storing scientific notation data Real number

Data register number storing converted binary floating point. Real number (binary)

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FNC70-FNC79 External FX I/O Device

3

3

Explanation of function and operation

FNC80-FNC89 External FX Device

1. 32-bit operation (DEBIN and DEBINP)

Scientific notation stored in [ +1, ] is converted into binary floating point, and transferred to [ +1,

S S D

].

S ‚ D ‚ [ +1, ] → [ +1, ] S ‚ S ‚ D ‚ D ‚

DEBIN

FNC100-FNC109 Data Transfer 2

Scientific notation Binary floating point

Low order b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 High order

b31 b30 b29 b28 b27 b26 b25 b24 b23 b22 b21 b20 b19 b18 b17 b16 Before execution Mantissa part Exponent part

× 10

FNC140-FNC149 Data Operation 2

High order Low order

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 b31 b30 b29 b28 b27 b26 b25 b24 b23 b22 b21 b20 b19 b18 b17 b16 After execution

Mantissa part (23 bits) Exponent part (8 bits)

D ‚ D ‚

Show 18 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · (decimal) · FMC60-FNC69 Handy Instruction · Oper- · and Type · Unit Index Con- stant · Real Number · Charac- ter String Pointer · Command · input FNC119 · +1 · FNC110-FNC139 Floating Point · +1 · After execution · Sign (1 bit) · +1 · FNC150-FNC159 Positioning Control
Page 506 of the Mitsubishi Electronics MELSEC FX3S user manual — DEBIN D 0 D 10
Page 506 · click to enlarge
Page 506

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.7 FNC119 – EBIN / Scientific Notation to Floating Point Conversion

Program example

By DEBIN instruction, a numeric value containing the decimal point can be directly converted into binary floating point.

ExampleConverting "3.14" into binary floating point

3.14 = 314 × 10−2 (scientific notation)

X002 FNC 12

MOVP K314 D 0 K314 → D0

314 × 10−2

MOVP K -2 D 1

K -2 → D1

(D1,D0) → (D11,D10) 314 × 10−2 Binary floating point

DEBIN D 0 D 10

→ For program examples of floating point operations, refer to Section 12.10.

Page 507 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 507 · click to enlarge
Page 507

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.8 FNC120 – EADD / Floating Point Addition 11

18.8 FNC120 – EADD / Floating Point Addition

FNC30-FNC39 Rotation and Shift

Outline

This instruction executes addition of two binary floating point data.

→ For program examples of floating point operations, refer to Section 12.10.

→ For handling of floating point, refer to Subsection 5.1.3.

→ For flag operations, refer to Subsection 6.5.2.

1. Instruction format

P FNC 120

Mnemonic Operation Condition 16-bit Instruction

Mnemonic Operation Condition 32-bit Instruction

EADD D −

13 steps Continuous Operation Pulse (Single) Operation

DEADD

DEADDP

2. Set data

Operand Type Description Data Type

Word device number storing binary floating point data used in addition

(binary)*1 Word device number storing binary floating point data used in addition

Data register number storing the addition result

*1. When a constant (K or H) is specified, it is automatically converted into binary floating point (real number) when the instruction is executed.

FNC70-FNC79 External FX I/O Device

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

FNC80-FNC89 External FX Device

3 S1 S2 3

3 S 1 S 2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

FNC100-FNC109 Data Transfer 2

Explanation of function and operation

1. 32-bit operation (DEADD and DEADDP)

Binary floating point data [ +1, ] is added to binary floating point data [ +1, ], and the addition

S 2 S 2 S 1 S 1

result in the binary floating point format is transferred to [ +1, ].

D D

S1 ‚ S2 ‚ D ‚ [ +1, ] + [ +1, ] → [ +1, ]

Binary floating point Binary floating point Binary floating point S1 ‚ S1 ‚ S2 ‚ S2 ‚ D ‚ D ‚

DEADD

When a constant (K or H) is specified as [ +1, ] or [ +1, ], it is automatically converted into binary floating point.

S 1 S 1 S 2 S 2

S1 ‚ S2 ‚ D ‚ [ +1, ] + [ K2346 ] → [ +1, ]

Binary floating point S1 ‚ S1 ‚ D ‚ D ‚

FNC140-FNC149 Data Operation 2

DEADD

Binary floating point Automatically converted into binary

Caution

1. When the same device is specified

The same device number can be specified in [ +1, ],[ +1, ] and [ +1, ]. In this case, note that the addition result changes in every operation cycle when the continuous operation type instruction (DEADD) is used.

S1 S1 S2 S2 D D

Show 16 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Real number · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input · FNC110-FNC139 Floating Point · Command · input · floating point · FNC150-FNC159 Positioning Control
Page 508 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 508 · click to enlarge
Page 508

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.9 FNC121 – ESUB / Floating Point Subtraction

18.9 FNC121 – ESUB / Floating Point Subtraction

Outline

This instruction executes subtraction of two binary floating point data.

→ For program examples of floating point operations, refer to Section 12.10.

→ For handling of floating point, refer to Subsection 5.1.3.

→ For flag operations, refer to Subsection 6.5.2.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 508)
Fig. 442 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 508)
Fig. 443 · 2. Set data

Word device number storing binary floating point data used in subtraction

Real number (binary)*1 Word device number storing binary floating point data used in subtraction

*1. When a constant (K or H) is specified, it is automatically converted into binary floating point (real number) when the instruction is executed.

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 508)
Fig. 444 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 32-bit operation (DESUB and DESUBP)

Binary floating point data [ +1, ] is subtracted from binary floating point data [ +1, ], and the

S 2 S 2 S 1 S 1

subtraction result in the binary floating point format is transferred to [ +1, ].

Mitsubishi Electronics MELSEC FX3S — S 2 S 2 S 1 S 1 diagram (page 508)
Fig. 445

S1 ‚ S2 ‚ D ‚ [ +1, ] − [ +1, ] → [ +1, ]

Binary floating point Binary floating point Binary floating point S1 ‚ S1 ‚ S2 ‚ S2 ‚ D ‚ D ‚

When a constant (K or H) is specified as [ +1, ] or [ +1, ], it is automatically converted into binary floating point.

S1 ‚ S2 ‚ D ‚ [ +1, ] − [ K2346 ] → [ +1, ]

Binary floating point S1 ‚ S1 ‚ D ‚ D ‚

Caution

1. When the same device is specified

The same device number can be specified in [ +1, ],[ +1, ] and [ +1, ]. In this case, note that the subtraction result changes in every operation cycle when the continuous operation type instruction (DESUB) is used.

S1 S1 S2 S2 D D

Page 509 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 1 S 2 S 2
Page 509 · click to enlarge
Page 509

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.10 FNC122 – EMUL / Floating Point Multiplication 11

18.10 FNC122 – EMUL / Floating Point Multiplication

FNC30-FNC39 Rotation and Shift

Outline

This instruction executes multiplication of two binary floating point data.

→ For program examples of floating point operations, refer to Section 12.10.

→ For handling of floating point, refer to Subsection 5.1.3.

1. Instruction format

P FNC 122

Mnemonic Operation Condition 16-bit Instruction

Mnemonic Operation Condition 32-bit Instruction

EMUL D −

13 steps Continuous Operation Pulse (Single) Operation

DEMUL

DEMULP

2. Set data

Operand Type Description Data Type

Word device number storing binary floating point data used in multiplication

Real number (binary)*1 Word device number storing binary floating point data used in multiplication

Data register number storing the multiplication result

*1. When a constant (K or H) is specified, it is automatically converted into binary floating point (real number) when the instruction is executed.

3. Applicable devices

FNC70-FNC79 External FX I/O Device

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

FNC80-FNC89 External FX Device

3 S1 S2 3

3 S 1 S 2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

FNC100-FNC109 Data Transfer 2

1. 32-bit operation (DEMUL and DEMULP)

Binary floating point data [ +1, ] is multiplied by binary floating point data [ +1, ], and the

S 1 S 1 S 2 S 2

multiplication result in the binary floating point format is transferred to [ +1, ].

D D

DEMUL S1 ‚ S2 ‚ D ‚ [ +1, ] × [ +1, ] → [ +1, ]

Binary floating point Binary floating point Binary floating point S1 ‚ S1 ‚ S2 ‚ S2 ‚ D ‚ D ‚

When a constant (K or H) is specified as [ +1, ] or [ +1, ], it is automatically converted into binary floating point.

S 1 S 1 S 2 S 2

DEMUL S1 ‚ S2 ‚ D ‚ [ +1, ] × [ K100 ] → [ +1, ]

Binary floating point S1 ‚ S1 ‚ D ‚ D ‚

FNC140-FNC149 Data Operation 2

Binary floating point Automatically converted into binary

Show 15 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · and Type · Unit Index Con- stant · Real Number · Charac- ter String Pointer · Command · input FNC122 · FNC110-FNC139 Floating Point · Command · input · floating point · FNC150-FNC159 Positioning Control
Page 510 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 1 S 2 S 2
Page 510 · click to enlarge
Page 510

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.11 FNC123 – EDIV / Floating Point Division

18.11 FNC123 – EDIV / Floating Point Division

Outline

This instruction executes division of two binary floating point.

→ For program examples of floating point operations, refer to Section 12.10.

→ For handling of floating point, refer to Subsection 5.1.3.

→ For flag operations, refer to Subsection 6.5.2.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 510)
Fig. 446 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 510)
Fig. 447 · 2. Set data

Word device number storing binary floating point data used in division

Real number (binary)*1 Word device number storing binary floating point data used in division

Data register number storing binary floating point data obtained by division

*1. When a constant (K or H) is specified, it is automatically converted into binary floating point (real number) when the instruction is executed.

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 510)
Fig. 448 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 32-bit operation (DEDIV and DESDIVP)

Binary floating point data [ +1, ] is divided by binary floating point data [ +1, ], and the division

S 1 S 1 S 2 S 2

Mitsubishi Electronics MELSEC FX3S — S 1 S 1 S 2 S 2 diagram (page 510)
Fig. 449

result in the binary floating point format is transferred to [ +1, ].

DEDIV S1 ‚ S2 ‚ D ‚ [ +1, ] ÷ [ +1, ] → [ +1, ]

Binary floating point Binary floating point Binary floating point S1 ‚ S1 ‚ S2 ‚ S2 ‚ D ‚ D ‚

When a constant (K or H) is specified as [ +1, ] or [ +1, ], it is automatically converted into binary floating point.

DEDIV K100 S1 ‚ D ‚ [ +1, ] ÷ [ K100 ] → [ +1, ]

Binary floating point S1 ‚ S1 ‚ D ‚ D ‚

Binary floating point Automatically converted into binary

Show 4 more labels / short text on this page
Command · Dividend Divisor · input FNC123 · floating point
Page 511 of the Mitsubishi Electronics MELSEC FX3S user manual — 18.12 FNC124 – EXP / Floating Point Exponent 11
Page 511 · click to enlarge
Page 511

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.12 FNC124 – EXP / Floating Point Exponent 11

Mitsubishi Electronics MELSEC FX3S — 18.12 FNC124 – EXP / Floating Point Exponent 11 diagram (page 511)
Fig. 450 · 18.12 FNC124 – EXP / Floating Point Exponent 11

This instruction executes exponential operation whose base is "e (2.71828)".

→ For handling of floating point, refer to Subsection 5.1.3.

Head device number storing binary floating point data used in exponential operation.

Real number (binary) Head device number storing the operation result.

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

The exponent of [ +1, ] is calculated, and the operation result is stored to [ +1, ].

A real number can be directly specified as .

  • In the exponential operation, the base (e) is set to "2.71828".

An operation error occurs in the following case; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When the operation result is outside the following range (error code: K6706) 2 − 126 ≤ | Operation result | < 2 128
Page 512 of the Mitsubishi Electronics MELSEC FX3S user manual — S S
Page 512 · click to enlarge
Page 512

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.12 FNC124 – EXP / Floating Point Exponent

Program example

In the program example shown below, the exponential operation is executed for a value set in the 2-digit BCD format in X020 to X027, and the operation result is stored in the binary floating point format to D0 and D1 when X000 turns ON.

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 512)
Fig. 451 · Program example

Data used in the exponential operation is input ([1]).

The range of the value to be operated is checked. (Refer to 1) in "Points" below.)

The input data is converted into binary floating point (real number) ([2]).

Operation when "13" is specified in X020 to X027

Mitsubishi Electronics MELSEC FX3S — Operation when "13" is specified in X020 to X027 diagram (page 512)
Fig. 452 · Operation when "13" is specified in X020 to X027

Points

1. The operation result becomes less than "2 128 " when the BCD value set in X020 to X027 is "88" or less because of

"loge2128 = 88.7". If a value "89" or more is set, an operation error occurs. To prevent this operation error, when a value more than "89" is set, M0 is set to ON so that the exponential operation is not executed.

2. Conversion from natural logarithm into common logarithm In the CPU, operations are executed in natural logarithm. For obtaining a value in common logarithm, specify a common logarithm value divided by "0.4342945" in

[ +1, ].

S S

10 X = e 0.4342945 X

Page 513 of the Mitsubishi Electronics MELSEC FX3S user manual — S S
Page 513 · click to enlarge
Page 513

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.13 FNC125 – LOGE / Floating Point Natural Logarithm 11

18.13 FNC125 – LOGE / Floating Point Natural Logarithm

FNC30-FNC39 Rotation and Shift

Outline

This instruction executes the natural logarithm operation.

→ For handling of floating point, refer to Subsection 5.1.3.

1. Instruction format

P FNC 125

Mnemonic Operation Condition 16-bit Instruction

Mnemonic Operation Condition 32-bit Instruction

LOGE D − −

9 steps Continuous Operation Pulse (Single) Operation

DLOGE

DLOGEP

2. Set data

Operand Type Description Data Type

Head device number storing binary floating point data used in the natural logarithm operation Real number (binary) Head device number storing the operation result

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FNC70-FNC79 External FX I/O Device

3

3

Explanation of function and operation

FNC80-FNC89 External FX Device

1. 32-bit operation (DLOGE and DLOGEP)

Natural logarithm [logarithm whose base is "e (2.71828)"] of [ +1, ] is calculated, and the operation result

S S

is stored to [ +1, ]. A real number can be directly specified as .

D D S

S ‚ S ‚ D ‚ D ‚

DLOGE S ‚ D ‚

FNC100-FNC109 Data Transfer 2

  • Only a positive value can be set in [ +1, ]. (The natural logarithm operation cannot be executed for a negative value.)

S S

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When a negative value is specified in (error code: K6706)
  • When "0" is specified in (error code: K6706)

FNC140-FNC149 Data Operation 2

Show 19 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · and Type · Unit Index Con- stant · Real Number · Charac- ter String Pointer · Command · +1 · +1 · input FNC125 · loge · Binary floating point · Binary floating point · (real number) · (real number) · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 514 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 514 · click to enlarge
Page 514

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.13 FNC125 – LOGE / Floating Point Natural Logarithm

Program example

In the program example shown below, natural logarithm of "10" set in D50 is calculated, and stored to D30 and D31 when X000 turns ON.

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 514)
Fig. 453 · Program example

Data used in the natural logarithm operation is set ([1]).

The data to be used is converted into binary floating point (real number) ([2]).

Page 515 of the Mitsubishi Electronics MELSEC FX3S user manual — S S
Page 515 · click to enlarge
Page 515

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.14 FNC126 – LOG10 / Floating Point Common Logarithm 11

18.14 FNC126 – LOG10 / Floating Point Common Logarithm

FNC30-FNC39 Rotation and Shift

Outline

This instruction executes the common logarithm operation.

→ For handling of floating point, refer to Subsection 5.1.3.

1. Instruction format

P FNC 126

Mnemonic Operation Condition 16-bit Instruction

Mnemonic Operation Condition 32-bit Instruction

LOG10 D − −

9 steps Continuous Operation Pulse (Single) Operation

DLOG10

DLOG10P

2. Set data

Operand Type Description Data Type

Head device number storing binary floating point data used in the common logarithm operation Real number (binary) Head device number storing the operation result

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FNC70-FNC79 External FX I/O Device

3

3

Explanation of function and operation

FNC80-FNC89 External FX Device

1. 32-bit operation (DLOG10 and DLOG10P)

Common logarithm [logarithm whose base is "10"] of [ +1, ] is calculated, and the operation result is

S S

stored to [ +1, ]. A real number can be directly specified as .

D D S

S ‚ D ‚ S ‚ D ‚

input FNC126 DLOG10 S ‚ D ‚

FNC100-FNC109 Data Transfer 2

  • Only a positive value can be set in [ +1, ]. (The common logarithm operation cannot be executed for a negative value.)

S S

Errors

An operation error occurs in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When a negative value is specified in (error code: K6706)
  • When "0" is specified in (error code: K6706)

FNC140-FNC149 Data Operation 2

Show 18 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · and Type · Unit Index Con- stant · Real Number · Charac- ter String Pointer · Command · +1 · +1 · log10 · Binary floating point · Binary floating point · (real number) · (real number) · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 516 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 516 · click to enlarge
Page 516

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.14 FNC126 – LOG10 / Floating Point Common Logarithm

Program example

In the program example shown below, common logarithm of "15" set in D50 is calculated, and stored to D30 and D31 when X000 turns ON.

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 516)
Fig. 454 · Program example

Data used in the common logarithm operation is set ([1]).

The data to be used is converted into binary floating point (real number) ([2]).

Page 517 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 1
Page 517 · click to enlarge
Page 517

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.15 FNC127 – ESQR / Floating Point Square Root 11

18.15 FNC127 – ESQR / Floating Point Square Root

FNC30-FNC39 Rotation and Shift

Outline

This instruction obtains the square root of binary floating point.

→ For handling of floating point, refer to Subsection 5.1.3.

1. Instruction format

P FNC 127

Mnemonic Operation Condition 16-bit Instruction

Mnemonic Operation Condition 32-bit Instruction

ESQR D

9 steps Continuous Operation Pulse (Single) Operation

DESQR

−

DESQRP

2. Set data

Operand Type Description Data Type

Word device number storing binary floating point data whose square root is calculated

Real number (binary)*1 Data register number storing the square root of binary floating point data

*1. When a constant (K or H) is specified, it is automatically converted into binary floating point (real number) when the instruction is executed.

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC70-FNC79 External FX I/O Device

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S 1 S 2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

FNC80-FNC89 External FX Device

Explanation of function and operation

1. 32-bit operation (DESQR and DESQRP)

The square root of [ +1, ] is calculated (in the binary floating point operation), and the result is transferred

S 1 S 1

FNC100-FNC109 Data Transfer 2

to [ +1, ].

D D

→ [ +1, ] Binary floating point [ +1, ] Binary floating point S ‚ D ‚ S ‚ D ‚ S ‚ D ‚

DESQR

Related device

→ For the zero flag use method, refer to Subsection 6.5.2.

M8020 Zero flag Turns ON when the operation result is true "0".

Error

FNC140-FNC149 Data Operation 2

The contents of [ +1, ] are valid only when a positive value is set. When a negative value is set, the operation error flag M8067 turns ON, and the instruction is not executed.

S 1 S 1

Show 13 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input FNC127 · FNC110-FNC139 Floating Point · Device Name Description · FNC150-FNC159 Positioning Control
Page 518 of the Mitsubishi Electronics MELSEC FX3S user manual — DENEG D ‚
Page 518 · click to enlarge
Page 518

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.16 FNC128 – ENEG / Floating Point Negation

18.16 FNC128 – ENEG / Floating Point Negation

Outline

This instruction inverts the sign of binary floating point (real number) data.

→ For handling of floating point, refer to Subsection 5.1.3.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 518)
Fig. 455 · 1. Instruction format

2. Set data

Operand Type Description Data Type

Head device number storing binary floating data whose sign is to be inverted Real number (binary)

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 518)
Fig. 456 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 32-bit operation (DENEG and DENEGP)

The sign of binary floating point stored in [ +1, ] is inverted, and the negation result is stored to [ +1,

D D D

].

DENEG D ‚

Program example

In the program example shown below, the sign of floating point data stored in D100 and D101 is inverted, and the negation result is stored to D100 and D101 when X000 turns ON.

Mitsubishi Electronics MELSEC FX3S — DENEG D ‚ diagram (page 518)
Fig. 457

Command · input FNC128

Page 519 of the Mitsubishi Electronics MELSEC FX3S user manual — S ‚ D ‚ S ‚ D ‚
Page 519 · click to enlarge
Page 519

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.17 FNC129 – INT / Floating Point to Integer Conversion 11

18.17 FNC129 – INT / Floating Point to Integer Conversion

FNC30-FNC39 Rotation and Shift

Outline

This instruction converts binary floating point data into a binary integer which is a normal data format inside PLCs (binary floating point → binary integer).

→ For program examples of floating point operations, refer to Section 12.10.

→ For handling of floating point, refer to Subsection 5.1.3.

1. Instruction format

P FNC 129

Mnemonic Operation Condition 32-bit Instruction

INT D

Continuous Operation Pulse (Single) Operation

9 steps Continuous Operation Pulse (Single) Operation

INT

DINT

INTP

DINTP

2. Set data

Operand Type Description Data Type

Data register number storing binary floating point data to be converted into a binary integer Real number (binary)

Data register number storing a converted binary integer 16- or 32-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC70-FNC79 External FX I/O Device

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S 1 S 2 3

3 S 1 S 2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

FNC80-FNC89 External FX Device

Explanation of function and operation

1. 16-bit operation (INT and INTP)

Binary floating point stored in [ +1, ] is converted into a binary integer, and transferred to .

S S D

FNC100-FNC109 Data Transfer 2

INT S ‚ D ‚ → 16-bit binary integer The decimal part is cut.

+1, Binary floating point

S ‚ D ‚ S ‚

Instruction for inverse conversion The inverse conversion is executed by FLT (FNC 49) instruction.

→ For FLT (FNC 49) instruction, refer to Section 12.10.

2. 32-bit operation (DINT and DINTP)

Binary floating point stored in [ +1, ] is converted into a binary integer, and transferred to [ +1,

S S D

].

FNC140-FNC149 Data Operation 2

DINT S ‚ D ‚ → +1, 32-bit binary integer The decimal part is cut.

+1, Binary floating point

S ‚ D ‚ S ‚ D ‚

Instruction for inverse conversion The inverse conversion is executed by DFLT (FNC 49) instruction.

→ For FLT (FNC 49) instruction, refer to Section 12.10.

Show 17 more labels / short text on this page
FNC40-FNC49 Data Operation · Mnemonic Operation Condition · 16-bit Instruction · 5 steps · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input FNC129 · FNC110-FNC139 Floating Point · Command · input FNC129 · FNC150-FNC159 Positioning Control
Page 520 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 520 · click to enlarge
Page 520

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.17 FNC129 – INT / Floating Point to Integer Conversion

Related devices

→ For the methods of zero, borrow and carry flags, refer to Subsection 6.5.2.

M8020 Zero flag Turns ON when the operation result is 0

M8021 Borrow flag Turns ON when the conversion result is cut in the decimal part.

Turns ON when the operation result is outside the range from −32768 to 32767 (in 16-bit operation) or from −2,147,483,583 to 2,147,483,583 (in 32-bit operation) and overflow occurs. (The operation result is not reflected.)

Caution

1. Caution in the operation

  • Values after the decimal point are rounded.

Device Name Description · M8022 Carry flag

Page 521 of the Mitsubishi Electronics MELSEC FX3S user manual — DEMUL D 4 D 20 D 30
Page 521 · click to enlarge
Page 521

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.18 FNC130 – SIN / Floating Point Sine 11

18.18 FNC130 – SIN / Floating Point Sine

FNC30-FNC39 Rotation and Shift

Outline

This instruction obtains the sine value of an angle (in radians).

→ For handling of floating point, refer to Subsection 5.1.3.

1. Instruction format

P FNC 130

Mnemonic Operation Condition 16-bit Instruction

Mnemonic Operation Condition 32-bit Instruction

SIN D

−

9 steps Continuous Operation Pulse (Single) Operation

DSIN

DSINP

2. Set data

Operand Type Description Data Type

Device number storing an angle (in radians) in binary floating point

Real number (binary) Device number storing the sine value in binary floating point

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

FNC70-FNC79 External FX I/O Device

Explanation of function and operation

1. 32-bit operation (DSIN and DSINP)

A value of angle (binary floating point) specified in [ +1, ] is converted into the sine value, and transferred

S S

to [ +1, ].

D D

FNC80-FNC89 External FX Device

[ +1, ] RAD → [ +1, ] SIN Binary floating point Binary floating point

S ‚ S ‚ D ‚ D ‚

DSIN S ‚ D ‚

Value in radians (Value in degrees × π /180) Binary floating point

S ‚ S ‚

FNC100-FNC109 Data Transfer 2

D ‚ D ‚

Sine value Binary floating point

Program example

X001 FNC 12

MOVP K 45 D 0 (K45) → (D 0)

An angle is selected by the inputs X001 and X002.

X002 FNC 12

MOVP K 90 D 0 (K90) → (D 0)

M8000 FNC 49

FLTP D 0 D 4 (D 0) → (D5, D4) Binary floating point

value RUN monitor FNC123

FNC140-FNC149 Data Operation 2

DEDIV K31415926 K1800000000 D 20 (π/180) → (D21, D20) Binary floating point

(D5, D4) Degrees × (π/180) → (D31, D30) Radians Binary floating point

DEMUL D 4 D 20 D 30

S ‚ D ‚

DSIN D 30 D100 (D31, D30) RAD → (D101, D100) SIN Binary floating point

Show 14 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · and Type · Unit Index Con- stant · Real Number · Charac- ter String Pointer · Command · input FNC130 · +1 · +1 · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 522 of the Mitsubishi Electronics MELSEC FX3S user manual — S S
Page 522 · click to enlarge
Page 522

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.19 FNC131 – COS / Floating Point Cosine

18.19 FNC131 – COS / Floating Point Cosine

Outline

This instruction obtains the cosine value of an angle (in radians).

→ For handling of floating point, refer to Subsection 5.1.3.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 522)
Fig. 458 · 1. Instruction format

2. Set data

Operand Type Description Data Type

Device number storing an angle (in radians) in binary floating point

Real number (binary) Device number storing the cosine value in binary floating point

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 522)
Fig. 459 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 32-bit operation (DCOS and DCOSP)

A value of angle (binary floating point) specified in [ +1, ] is converted into the cosine value, and

S S

Mitsubishi Electronics MELSEC FX3S — S S diagram (page 522)
Fig. 460

DCOS S ‚ D ‚ [ +1, ] RAD → [ +1, ] COS Binary floating point Binary floating point

Value in radians (Value in degrees × π /180) Binary floating point

Page 523 of the Mitsubishi Electronics MELSEC FX3S user manual — 18.20 FNC132 – TAN / Floating Point Tangent 11
Page 523 · click to enlarge
Page 523

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.20 FNC132 – TAN / Floating Point Tangent 11

Mitsubishi Electronics MELSEC FX3S — 18.20 FNC132 – TAN / Floating Point Tangent 11 diagram (page 523)
Fig. 461 · 18.20 FNC132 – TAN / Floating Point Tangent 11

This instruction obtains the tangent value of an angle (in radians).

→ For handling of floating point, refer to Subsection 5.1.3.

Device number storing an angle (in radians) in binary floating point

Real number (binary) Device number storing the tangent value in binary floating point

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

A value of angle (binary floating point) specified in [ +1, ] is converted into the tangent value, and

DTAN S ‚ D ‚ [ +1, ] RAD → [ +1, ] TAN Binary floating point Binary floating point

Value in radians (Value in degrees × π /180) Binary floating point

Page 524 of the Mitsubishi Electronics MELSEC FX3S user manual — Error
Page 524 · click to enlarge
Page 524

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.21 FNC133 – ASIN / Floating Point Arc Sine

18.21 FNC133 – ASIN / Floating Point Arc Sine

Outline

This instruction executes SIN−1 (arc sine) operation.

→ For handling of floating point, refer to Subsection 5.1.3.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 524)
Fig. 462 · 1. Instruction format

2. Set data

Operand Type Description Data Type

Head device number storing a sine value used in SIN−1 (arc sine) operation.

Real number (binary) Head device number storing the operation result

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 524)
Fig. 463 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 32-bit operation (DASIN and DASINP)

An angle is obtained from the sine value stored in [ +1, ], and stored to [ +1, ].

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 524)
Fig. 464 · Explanation of function and operation

S S D D

A real number can be directly specified as .

  • The sine value stored in [ +1, ] can be set ranging from − 1.0 to +1.0.
  • The angle (operation result) stored in [ +1, ] is expressed in radians (from −π /2 to π /2). For conversion between radians and degrees, refer to the RAD (FNC136) and DEG (FNC137) instructions.

→ For the RAD (FNC136) instruction, refer to Section 18.24. → For the DEG (FNC137) instruction, refer to Section 18.25.

Error

An operation error is caused in the following case; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When a value specified in is outside the range from − 1.0 to +1.0 (error code: K6706)
Page 525 of the Mitsubishi Electronics MELSEC FX3S user manual — Operation when "0.5" is stored in D0 and D1
Page 525 · click to enlarge
Page 525

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.21 FNC133 – ASIN / Floating Point Arc Sine 11

Mitsubishi Electronics MELSEC FX3S — 18.21 FNC133 – ASIN / Floating Point Arc Sine 11 diagram (page 525)
Fig. 465 · 18.21 FNC133 – ASIN / Floating Point Arc Sine 11

In the program example shown below, the SIN−1 value of data (binary floating point) stored in D0 and D1 is calculated, and the angle is output in 4-digit BCD to Y040 to Y057 when X000 turns ON.

The angle (in radians) is calculated by the SIN−1

The value in radians is converted into the value in degrees ([2]).

The angle expressed in binary floating point (real number) is converted into an integer (binary) ([3]).

The angle expressed in integer (binary) is output to the display unit ([4]). FNC 18

Operation when "0.5" is stored in D0 and D1

Page 526 of the Mitsubishi Electronics MELSEC FX3S user manual — Error
Page 526 · click to enlarge
Page 526

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.22 FNC134 – ACOS / Floating Point Arc Cosine

18.22 FNC134 – ACOS / Floating Point Arc Cosine

Outline

This instruction executes COS−1 (arc cosine) operation.

→ For handling of floating point, refer to Subsection 5.1.3.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 526)
Fig. 466 · 1. Instruction format

2. Set data

Operand Type Description Data Type

Head device number storing a cosine value used in COS−1 (arc cosine) operation

Real number (binary) Head device number storing the operation result

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 526)
Fig. 467 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 32-bit operation (DACOS and DACOSP)

An angle is obtained from the cosine value stored in [ +1, ], and stored to [ +1, ].

S S D D

A real number can be directly specified as .

Mitsubishi Electronics MELSEC FX3S — S S D D diagram (page 526)
Fig. 468
  • The cosine value stored in [ +1, ] can be set ranging from − 1.0 to +1.0.
  • The angle (operation result) stored in [ +1, ] is expressed in radians (from 0 to π ). For conversion between radians and degrees, refer to the RAD (FNC136) and DEG (FNC137) instructions.

→ For the RAD (FNC136) instruction, refer to Section 18.24. → For the DEG (FNC137) instruction, refer to Section 18.25.

Error

An operation error is caused in the following case; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When a value specified in is outside the range from − 1.0 to +1.0 (error code: K6706)
Page 527 of the Mitsubishi Electronics MELSEC FX3S user manual — Operation when "0.5" is stored in D0 and D1
Page 527 · click to enlarge
Page 527

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.22 FNC134 – ACOS / Floating Point Arc Cosine 11

Mitsubishi Electronics MELSEC FX3S — 18.22 FNC134 – ACOS / Floating Point Arc Cosine 11 diagram (page 527)
Fig. 469 · 18.22 FNC134 – ACOS / Floating Point Arc Cosine 11

In the program example shown below, the COS−1 value of data (binary floating point) stored in D0 and D1 is calculated, and the angle is output in 4-digit BCD to Y040 to Y057 when X000 turns ON.

The angle (in radians) is calculated by the COS−1

The value in radians is converted into the value in degrees ([2]). D20

The angle expressed in the binary floating point (real number) is converted into an integer (binary) ([3]).

The angle expressed in integer (binary) is output to the display unit ([4]). FNC 18

Operation when "0.5" is stored in D0 and D1

Page 528 of the Mitsubishi Electronics MELSEC FX3S user manual — S S D D
Page 528 · click to enlarge
Page 528

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.23 FNC135 – ATAN / Floating Point Arc Tangent

18.23 FNC135 – ATAN / Floating Point Arc Tangent

Outline

This instruction executes the TAN−1 (arc tangent) operation.

→ For handling of floating point, refer to Subsection 5.1.3.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 528)
Fig. 470 · 1. Instruction format

2. Set data

Operand Type Description Data Type

Head device number storing a tangent value used in the TAN−1 (arc tangent) operation

Real number (binary) Head device number storing the operation result

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 528)
Fig. 471 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 32-bit operation (DATAN and DATANP)

An angle is obtained from the tangent value stored in [ +1, ], and stored to [ +1, ].

S S D D

A real number can be directly specified as .

Mitsubishi Electronics MELSEC FX3S — S S D D diagram (page 528)
Fig. 472
  • The angle (operation result) stored in [ +1, ] is expressed in radians (from −π /2 to + π /2). For conversion between radians and degrees, refer to RAD (FNC136) and DEG (FNC137) instructions.

→ For RAD (FNC136) instruction, refer to Section 18.24. → For DEG (FNC137) instruction, refer to Section 18.25.

Page 529 of the Mitsubishi Electronics MELSEC FX3S user manual — Operation when "1" is stored in D0 and D1
Page 529 · click to enlarge
Page 529

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.23 FNC135 – ATAN / Floating Point Arc Tangent 11

Mitsubishi Electronics MELSEC FX3S — 18.23 FNC135 – ATAN / Floating Point Arc Tangent 11 diagram (page 529)
Fig. 473 · 18.23 FNC135 – ATAN / Floating Point Arc Tangent 11

In the program example shown below, the TAN−1 value of data (binary floating point) stored in D0 and D1 is calculated, and the angle is output in 4-digit BCD to Y040 to Y057 when X000 turns ON.

The angle (in radians) is calculated by the TAN−1

The value in radians is converted into the value in degrees ([2]). D20

The angle expressed in binary floating point (real number) is converted into an integer (binary) ([3]).

The angle expressed in integer (binary) is output to the display unit ([4]). FNC 18

Operation when "1" is stored in D0 and D1

Page 530 of the Mitsubishi Electronics MELSEC FX3S user manual — S S D
Page 530 · click to enlarge
Page 530

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.24 FNC136 – RAD / Floating Point Degrees to Radians Conversion

18.24 FNC136 – RAD / Floating Point Degrees to Radians Conversion

Outline

This instruction converts a value in degrees into a value in radians.

→ For handling of floating point, refer to Subsection 5.1.3.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 530)
Fig. 474 · 1. Instruction format

2. Set data

Operand Type Description Data Type

Head device number storing a value in degrees to be converted into a value in radians

Real number (binary) Head device number storing a value in radians acquired by conversion

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 530)
Fig. 475 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 32-bit operation (DRAD and DRADP)

The unit of [ +1, ] is converted from degrees into radians, and the operation result is stored to [ +1,

S S D

].

A real number can be directly specified as .

Mitsubishi Electronics MELSEC FX3S — S S D diagram (page 530)
Fig. 476
  • The conversion from degrees into radians is executed as follows:

Radians = Degrees ×

180 π

Page 531 of the Mitsubishi Electronics MELSEC FX3S user manual — Operation when "120" is specified in X020 to X037
Page 531 · click to enlarge
Page 531

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.24 FNC136 – RAD / Floating Point Degrees to Radians Conversion 11

Mitsubishi Electronics MELSEC FX3S — 18.24 FNC136 – RAD / Floating Point Degrees to Radians Conversion 11 diagram (page 531)
Fig. 477 · 18.24 FNC136 – RAD / Floating Point Degrees to Radia…

In the program example shown below, a 4-digit BCD value set in degrees in X020 to X037 is converted into a binary floating point value in radians, and stored to D20 and D21 when X000 turns ON.

Angle to be converted into radians is input ([1]).

The input angle is converted into binary floating point (real number) ([2]).

The angle is converted from degrees into radians ([3]).

Operation when "120" is specified in X020 to X037

Page 532 of the Mitsubishi Electronics MELSEC FX3S user manual — Operation when "1.435792" is specified in D20 and D21
Page 532 · click to enlarge
Page 532

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

18 Floating Point – FNC110 to FNC139

18.25 FNC137 – DEG / Floating Point Radians to Degrees Conversion

18.25 FNC137 – DEG / Floating Point Radians to Degrees Conversion

Outline

This instruction converts a value in radians into a value in degrees.

→ For handling of floating point, refer to Subsection 5.1.3.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 532)
Fig. 478 · 1. Instruction format

2. Set data

Operand Type Description Data Type

Head device number storing a value in radians to be converted into a value in degrees

Real number (binary) Head device number storing a value in degrees acquired by conversion

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 532)
Fig. 479 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 32-bit operation (DDEG and DDEGP) The unit of [ +1, ] is converted from radians into degrees, and the operation result is stored to [ +1, ].

S S D

S ‚ S ‚ D ‚ D ‚

DDEG S ‚ D ‚

  • The conversion from radians into degrees is executed as follows:

Degrees = Radians ×

Program example

In the program example shown below, a binary floating point value set in radians in D20 and D21 is converted into a BCD value in degrees, and stored to Y040 and Y057 when X000 turns ON.

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 532)
Fig. 480 · Program example

A value in radians is converted into a value in degrees ([1]).

The angle in binary floating point (real number) is converted into an integer ([2]).

The converted integer is output to the display unit ([3]).

Operation when "1.435792" is specified in D20 and D21

Mitsubishi Electronics MELSEC FX3S — Operation when "1.435792" is specified in D20 and D21 diagram (page 532)
Fig. 481 · Operation when "1.435792" is specified in D20 and D2…
Show 10 more labels / short text on this page
Command · +1 · +1 · input FNC137 · ° rad · Binary floating point · Binary floating point · (real number) · (real number) · π
Page 533 of the Mitsubishi Electronics MELSEC FX3S user manual — 19. Data Operation 2 – FNC140 to FNC149
Page 533 · click to enlarge
Page 533

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

19 Data Operation 2 – FNC140 to FNC149

Mitsubishi Electronics MELSEC FX3S — 19. Data Operation 2 – FNC140 to FNC149 diagram (page 533)
Fig. 482 · 19. Data Operation 2 – FNC140 to FNC149

FNC140 to FNC149 provide instructions for executing complicated processing for fundamental applied instructions and for executing special processing.

143 UNI 4-bit Linking of Word Data Section 19.4

144 DIS 4-bit Grouping of Word Data Section 19.5

Page 534 of the Mitsubishi Electronics MELSEC FX3S user manual — S S D D D
Page 534 · click to enlarge
Page 534

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

19 Data Operation 2 – FNC140 to FNC149

19.1 FNC140 – WSUM / Sum of Word Data

19.1 FNC140 – WSUM / Sum of Word Data

Outline

This instruction calculates the sum of consecutive 16-bit or 32-bit data. When calculating the addition data (sum value) in units of byte (8 bits), use the CCD (FNC 84) instruction.

→ For CCD (FNC 84) instruction, refer to Section 16.5.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 534)
Fig. 483 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 534)
Fig. 484 · 2. Set data

Head device number storing data whose sum is calculated 16- or 32-bit binary

n Number of data (0 < n) 16- or 32-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 534)
Fig. 485 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 16-bit operation (WSUM and WSUMP)

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 534)
Fig. 486 · Explanation of function and operation

The sum of "n" 16-bit data starting from is stored as 32-bit data in [ +1, ].

D ‚ D ‚ Sum of "n" data "n" points (n = 6)

2. 32-bit operation (DWSUM and DWSUMP)

The sum of "n" 32-bit data starting from [ +1, ] is stored as 64-bit data in [ +3, +2, +1,

S S D D D

Mitsubishi Electronics MELSEC FX3S — S S D D D diagram (page 534)
Fig. 487

[ +1, ] [ +3, +2] [ +5, +4] [ +7, +6] [ +9, +8]

Sum of "n" data "n" points (n = 5)

Page 535 of the Mitsubishi Electronics MELSEC FX3S user manual — K14948 END
Page 535 · click to enlarge
Page 535

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

19 Data Operation 2 – FNC140 to FNC149

19.1 FNC140 – WSUM / Sum of Word Data 11

Related instruction

FNC30-FNC39 Rotation and Shift

CCD (FNC 84) Check code Calculates the sum of 16-bit data in units of byte (8 bits) and the horizontal parity.

Caution

  • In the 32-bit operation, the acquired sum is 64-bit data. FX 3U and FX 3UC PLCs cannot handle 64-bit data. When the sum is within the numeric range of 32-bit data (K-2,147,483,648 to K2,147,483,647), however, FX 3U and FX 3UC PLCs can handle the low-order 32 bits of 32-bit data as the sum while ignoring the high-order 32 bits.
  • Note that the 32-bit value [n+1, n] is valid when D or R is specified as "n" in a 32-bit instruction. In the case of "DWSUM D0 D100 R0", "n" is [R1, R0].

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When "n" points starting from are outside the specified device range (error code: K6706)
  • When "n" is smaller than or equivalent to "0" (error code: K6706)
  • When are outside the specified device range. (error code: K6706)

Program example

In the program shown below, the sum of 16-bit data stored in D10 to D14 is stored in [D101, D100].

X010 FNC140 WSUMP D10 D100

K4500 K2500 K-3276

[D101,D100] K5 WSUMP instruction

D11 D12 D13 D14

FNC70-FNC79 External FX I/O Device

K14948 END

K6780 K4444

FNC80-FNC89 External FX Device

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 6 more labels / short text on this page
Instruction Description · FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 536 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 536 · click to enlarge
Page 536

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

19 Data Operation 2 – FNC140 to FNC149

19.2 FNC141 – WTOB / WORD to BYTE

19.2 FNC141 – WTOB / WORD to BYTE

Outline

This instruction separates consecutive 16-bit data in byte units (8 bits).

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 536)
Fig. 488 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 536)
Fig. 489 · 2. Set data

Head device number storing data to be separated in byte units

16-bit binary Head device number storing result of separation in byte units

n Number of byte data to be separated (0 ≤ n)

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 536)
Fig. 490 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 16-bit operation (WTOB and WTOBP)

1. "n/2" 16-bit data stored in and later is separated into "n" bytes, and stored in "n" devices starting from
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 536)
Fig. 491 · Explanation of function and operation

00H 00H Low-order byte High-order byte 00H 00H Low-order byte High-order byte

*1 When "n" is an odd number, "n/2" is rounded up. When "n" is "5", for example, " +3" is used.

2. "00H" is stored in the high-order byte (8 bits) of each device ( and later) storing the separated byte data.
Page 537 of the Mitsubishi Electronics MELSEC FX3S user manual — 00H 34H D25
Page 537 · click to enlarge
Page 537

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

19 Data Operation 2 – FNC140 to FNC149

19.2 FNC141 – WTOB / WORD to BYTE 11

3. When "n" is an odd number, only the low-order byte (8 bits) of the final separation source device is regarded as the target data as shown in the figure below.

FNC30-FNC39 Rotation and Shift

For example, when "n" is "5", the data from to the low-order byte (8 bits) of +2 is stored in to

S S D

+4.

b15 b8 b7 b0

b15 b8 b7 b0

12H 56H FEH

39H 78H DCH

00H 00H 39H 12H 00H 00H 78H 56H 00H DCH

When "n" is "5"

It is ignored when "n" is "5".

"00H" is stored.

4. When "n" is "0", WTOB instruction is not executed.

Related instruction

BTOW (FNC142) Combines the low-order 8 bits (low-order byte) of consecutive 16-bit data.

Caution

Devices storing the separation source data can overlap devices storing the separated data. When "n" is an odd number, however, the high-order byte (8 bits) of the final separation source device is overwritten and erased.

b15 b8 b7 b0 b15 b8 b7 b0

S ‚ =D12

32H 34H 36H

31H 33H 35H

D ‚ =D12

00H 00H 31H 32H 00H 00H 33H 34H 00H 35H

D13 D14 D14 D15 D16

When "n" is "5"

FNC70-FNC79 External FX I/O Device

"36H" is ignored when "n" is "5". Because D14 is also used in the separation result destination devices D and later, "36H" is erased and overwritten.

"00H" is stored.

Errors

FNC80-FNC89 External FX Device

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When the separation source devices to +n/2 are outside the specified device range (error code: K6706) When "n" is an odd number, the number of a rounded up value decides the number of devices. (error code: K6706)

S S

  • When the separated data destination devices to +n-1 are outside the specified device range (error code: K6706)

D D

FNC100-FNC109 Data Transfer 2

Program example

In the program shown below, the data stored in D10 to D12 is separated in byte units, and stored in D20 to D25.

X000 FNC141 WTOBP D10 D20 K6

END

b15 b8 b7 b0 b15 b8 b7 b0

D10 D20 D21

FDH

58H E2H 44H

00H 00H 58H FDH 00H 00H E2H 57H 00H 44H

D11 D12 D22 D23 D24

57H 34H

FNC140-FNC149 Data Operation 2

00H 34H D25

"00H" is stored.

Show 10 more labels / short text on this page
+1 +2 · +1 · FNC40-FNC49 Data Operation · +2 +3 +4 · FNC50-FNC59 High-Speed Processing · Instruction Description · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · 6 bytes · FNC150-FNC159 Positioning Control
Page 538 of the Mitsubishi Electronics MELSEC FX3S user manual — S S D D
Page 538 · click to enlarge
Page 538

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

19 Data Operation 2 – FNC140 to FNC149

19.3 FNC142 – BTOW / BYTE to WORD

19.3 FNC142 – BTOW / BYTE to WORD

Outline

This instruction combines the low-order 8 bits (low-order byte) of consecutive 16-bit data.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 538)
Fig. 492 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 538)
Fig. 493 · 2. Set data

Head device number storing data to be combined in byte units

16-bit binary Head device number storing data acquired by combination in byte units

n Number of byte data to be combined (0 ≤ n)

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 538)
Fig. 494 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 16-bit operation (BTOW and BTOWP)

1. The low-order byte (8 bits) of "n" 16-bit data starting from is combined, and stored in "n/2" devices starting
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 538)
Fig. 495 · Explanation of function and operation

1st byte data 2nd byte data 3rd byte data

*1 When "n" is an odd number, refer to "3)" below

2. The high-order byte (8 bits) of each combination source 16-bit data ( and later) is ignored.
3. When "n" is an odd number, "00H" is stored in the high-order byte (8 bits) of the final one among the combination result destination devices as shown below. For example, when "n" is "5", the low-order byte (8 bits) of to +4 is stored in to +2, and

S S D D

Mitsubishi Electronics MELSEC FX3S — S S D D diagram (page 538)
Fig. 496

"00H" is stored in the high-order byte (8 bits) of +2.

CDH 9AH +3 +4 When "n" is "5", "00H" is stored.

4. When "n" is "0", the BTOW instruction is not executed.
Page 539 of the Mitsubishi Electronics MELSEC FX3S user manual — D20 D21
Page 539 · click to enlarge
Page 539

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

19 Data Operation 2 – FNC140 to FNC149

19.3 FNC142 – BTOW / BYTE to WORD 11

Related instruction

FNC30-FNC39 Rotation and Shift

WTOB (FNC141) Separates consecutive 16-bit data in byte units (8 bits).

Caution

Devices storing the combination source data may be equivalent to devices storing the combined data. After combination, however, the high-order byte (8 bits) of the combination source data stored in the devices used for the combination destination data is erased and overwritten with the data acquired by combining the high-order byte (8 bits).

b15 b8 b7 b0 b15 b8 b7 b0

S ‚ =D11

ABH CDH

12H 34H

D ‚ =D10 34H 78H 12H 56H 9AH

D11 D12 D13 D14 D15

When "n" is "6"

D13 D14 D15

78H EFH 56H

BCH

ABH

EFH ABH

56H 78H 9AH

CDH 9AH

EFH BCH

CDH

EFH BCH D16

The high-order bytes is ignored.

It is not changed.

Because these combination source devices are also used for the combination destination, "ABH" and "CDH" are erased and overwritten.

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

FNC70-FNC79 External FX I/O Device

  • When the combination source devices to +n-1 are outside the specified device range (error code: K6706)

S S

  • When the combined data destination devices to +n/2 are outside the specified device range (error code: K6706) When "n" is an odd number, the number of a rounded up value decides the number of devices. (error code: K6706)

D D

FNC80-FNC89 External FX Device

Program example

In the program shown below, the low-order byte (8 bits) data stored in D20 to D25 is combined, and stored in D10 to D12.

X000 FNC142 BTOWP D20 D10 K6

FNC100-FNC109 Data Transfer 2

END

b15 b8 b7 b0 b15 b8 b7 b0

D20 D21

00H 31H

78H 12H

D10 D11 D12

12H 55H 78H 49H 67H

55H 36H 49H

31H

48H 67H D23 D24

44H

49H 31H D25

The high-order bytes is ignored.

FNC140-FNC149 Data Operation 2

Show 7 more labels / short text on this page
Instruction Description · FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · D22 6 bytes · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 540 of the Mitsubishi Electronics MELSEC FX3S user manual — S S D
Page 540 · click to enlarge
Page 540

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

19 Data Operation 2 – FNC140 to FNC149

19.4 FNC143 – UNI / 4-bit Linking of Word Data

19.4 FNC143 – UNI / 4-bit Linking of Word Data

Outline

This instruction combines the low-order 4 bits of consecutive 16-bit data.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 540)
Fig. 497 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 540)
Fig. 498 · 2. Set data

n Number of data to be combined (0 to 4, When "n" is "0", UNI instruction is not executed.)

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 540)
Fig. 499 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 16-bit operation (UNI/UNIP)

1. The low-order 4 bits of "n" 16-bit data starting from are combined, and stored in as shown below.
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 540)
Fig. 500 · Explanation of function and operation

Low-order 4 bits Low-order 4 bits Low-order 4 bits Low-order 4 bits

2. Specify a number 1 to 4 in "n". In the case of "n = 0", UNI instruction is not executed.
3. In the case of "1 ≤ n ≤ 3", the high-order {4 × (4-n)} bits of are set to "0".

For example, when "n" is "3", the low-order 4 bits of to +2 are stored in b0 to b11 of , and the

S S D

Mitsubishi Electronics MELSEC FX3S — S S D diagram (page 540)
Fig. 501

Low-order 4 bits Low-order 4 bits Low-order 4 bits

When "n" is "3", b12 to b15 are set to "0".

Page 541 of the Mitsubishi Electronics MELSEC FX3S user manual — 19.4 FNC143 – UNI / 4-bit Linking of Word Data 11
Page 541 · click to enlarge
Page 541

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

19 Data Operation 2 – FNC140 to FNC149

19.4 FNC143 – UNI / 4-bit Linking of Word Data 11

Mitsubishi Electronics MELSEC FX3S — 19.4 FNC143 – UNI / 4-bit Linking of Word Data 11 diagram (page 541)
Fig. 502 · 19.4 FNC143 – UNI / 4-bit Linking of Word Data 11

An operation error occurs in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When to +n are outside the specified device range (error code: K6706)
  • When "n" is outside the range from "0 to 4" (error code: K6706)

In the program below, the low-order 4 bits of D0 to D2 are combined and stored in D10 when X000 turns ON.

1 0 0 0 1 0 1 0 1 0 0 1 0 1 0

1 0 1 0

1 0 0 1 0

Because "n" is "K3", they are set to "0".

Page 542 of the Mitsubishi Electronics MELSEC FX3S user manual — Related instruction
Page 542 · click to enlarge
Page 542

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

19 Data Operation 2 – FNC140 to FNC149

19.5 FNC144 – DIS / 4-bit Grouping of Word Data

19.5 FNC144 – DIS / 4-bit Grouping of Word Data

Outline

This instruction separates 16-bit data into 4 bit units.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 542)
Fig. 503 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 542)
Fig. 504 · 2. Set data

n Number of data to be separated (0 to 4) (When "n" is "0", DIS instruction is not executed.)

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 542)
Fig. 505 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 16-bit operation (DIS and DISP)

1. 16-bit data stored in is separated in 4-bit units, and stored in as shown below.
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 542)
Fig. 506 · Explanation of function and operation

Low-order 4 bits Low-order 4 bits Low-order 4 bits Low-order 4 bits

2. Specify a number 1 to 4 in "n". In the case of "n = 0", DIS instruction is not executed.
3. High-order 12 bits of "n" devices starting from are set to "0".

Related instruction

UNI (FNC143) Combines low-order 4 bits of 16-bit data.

Instruction Description

Page 543 of the Mitsubishi Electronics MELSEC FX3S user manual — X000 FNC144
Page 543 · click to enlarge
Page 543

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

19 Data Operation 2 – FNC140 to FNC149

19.5 FNC144 – DIS / 4-bit Grouping of Word Data 11

Errors

FNC30-FNC39 Rotation and Shift

An operation error occurs in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When to +n are outside the specified device range (error code: K6706)

D D

  • When "n" is outside the range from "0 to 4" (error code: K6706)

Program example

In the program below, D0 is separated into 4 bit units and stored in D10 to D13 when X000 turns ON.

X000 FNC144

DISP D0 D10 K4

END

b15 b4 b3 b0 b2 b1 D10

b15 b12b11 b4 b3 b0

1 0 0 0 1 0 1 0 1 0 0 1 0 0 1 1 1 0

1 0 1 0

1 0 0 1 0

0 0 1 1 0

They are set to "0".

FNC70-FNC79 External FX I/O Device

FNC80-FNC89 External FX Device

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 8 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · b8 b7 · FMC60-FNC69 Handy Instruction · Data storage · area · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 544 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 544 · click to enlarge
Page 544

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

19 Data Operation 2 – FNC140 to FNC149

19.6 FNC147 – SWAP / Byte Swap

19.6 FNC147 – SWAP / Byte Swap

Outline

This instruction swaps the high-order 8 bits and low-order 8 bits of a word device.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 544)
Fig. 507 · 1. Instruction format

2. Set data

Operand type Description Data type

Word device whose high-order 8 bits and low-order 8 bits are swapped for each other 16- or 32-bit binary

S 1 ‚ S

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — S 1 ‚ S diagram (page 544)
Fig. 508

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

Explanation of function and operation

1. 16-bit operation (SWAP and SWAPP) High-order 8 bits and low-order 8 bits are swapped for each other.

input FNC147 SWAPP S ‚

High-order 8 bits Low-order 8 bits

2. 32-bit operation (DSWAP and DSWAPP) High-order 8 bits and low-order 8 bits are swapped for each other in each word device.

+1 S ‚ S ‚ Command

input FNC147 DSWAPP S ‚

High-order 8 bits Low-order 8 bits , High-order 8 bits Low-order 8 bits

Caution

When the continuous operation type instruction is used, swapping is executed in each operation cycle. This instruction works in the same way as the extension function of the XCH (FNC 17) instruction.

S ‚ Command

Page 545 of the Mitsubishi Electronics MELSEC FX3S user manual — M8029
Page 545 · click to enlarge
Page 545

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

19 Data Operation 2 – FNC140 to FNC149

19.7 FNC149 – SORT2 / Sort Tabulated Data 2 11

19.7 FNC149 – SORT2 / Sort Tabulated Data 2

FNC30-FNC39 Rotation and Shift

Outline

This instruction sorts a data table consisting of data (lines) and group data (columns) based on a specified group data (column) sorted by line in either ascending or descending order. This instruction stores the data (lines) in serial devices facilitating the addition of data (lines). On the other hand, the SORT (FNC 69) instruction stores the group data (columns) in serial devices, and sorts a table in ascending order only.

→ For SORT (FNC 69) instruction, refer to Section 14.10.

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

SORT2 D

21 steps DSORT2 Continuous Operation

2. Set data

Operand type Description Data type

Head device number storing the data table [which occupies m1 × m2 points]

m1 Number of data (lines) [1 to 32]

m2 Number of group data (columns) [1 to 6]

Head device number storing the operation result [which occupies m1 × m2 points]

FNC70-FNC79 External FX I/O Device

n Column number of group data (column) used as the basis of sorting [1 to m2]

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC80-FNC89 External FX Device

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

m1 3

n 3

FNC100-FNC109 Data Transfer 2

Explanation of function and operation

1. 16-bit operation (SORT2)

In the data table (sorting source) having (m1 x m2) points from , data lines are sorted in the ascending or descending order based on the group data in column No. "n", and the result is stored in the data table (occupying m1

x m2 points) from .

→ For operation examples, refer to Page 545.

SORT2 m1 m2 S n D

Instruction execution complete flag

FNC140-FNC149 Data Operation 2

M8029

M{{ Instruction execution complete flag for SORT2 instruction

Show 18 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · Mnemonic Operation Condition · 32-bit Instruction · 11 steps SORT · Continuous Operation · FMC60-FNC69 Handy Instruction · 16- or 32-bit binary · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · m2 3 3 · FNC110-FNC139 Floating Point · Command · input FNC149 · FNC150-FNC159 Positioning Control
Page 546 of the Mitsubishi Electronics MELSEC FX3S user manual — D D
Page 546 · click to enlarge
Page 546

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

19 Data Operation 2 – FNC140 to FNC149

19.7 FNC149 – SORT2 / Sort Tabulated Data 2

The data table configuration is explained in an example in which the sorting source data table has 3 lines and 4

columns (m1 = K3, m2 = K4). For the sorting result data table, understand as .

Mitsubishi Electronics MELSEC FX3S — 19.7 FNC149 – SORT2 / Sort Tabulated Data 2 diagram (page 546)
Fig. 509 · 19.7 FNC149 – SORT2 / Sort Tabulated Data 2
  • Set the sorting order by setting M8165 to ON or OFF.
  • When the command input turns ON, data sorting is started. Data sorting is completed after "m1" scans, and the instruction execution complete flag M8029 is set to ON.

→ For the instruction execution complete flag use method, refer to Subsection 6.5.2.

2. 32-bit operation (DSORT2)

In the data table (sorting source) having (m1 × m2) points from [ +1, ], data lines are sorted in the ascending or descending order based on the group data in the column No. "n", and the result is stored in the data table

S S

(sorting result) having (m1 × m2) points from [ +1, ].

D D

→ For operation examples, refer to next page.

Mitsubishi Electronics MELSEC FX3S — D D diagram (page 546)
Fig. 510

M{{ Instruction execution complete flag for SORT2 instruction

The data table configuration is explained in an example in which the sorting source data table has 3 lines and 4

columns (m1 = K3, m2 = K4). For the sorting result data table, understand as .

Mitsubishi Electronics MELSEC FX3S — D D diagram (page 546)
Fig. 511

1 [ +1, ] [ +3, +2] [ +5, +4] [ +7, +6]

2 [ +9, +8] [ +11, +10] [ +13, +12] [ +15, +14]

3 [ +17, +16] [ +19, +18] [ +21, +20] [ +23, +22]

  • Set the sorting order by setting M8165 to ON or OFF.
  • When a data register D or extension register (R) is used for "m1", the data length is 32 bits. For example, when "m1" is specified in D0, "m1" is 32-bit data stored in [D1, D0].
  • When the command input turns ON, data sorting is started. Data sorting is completed after "m1" scans, and the instruction execution complete flag M8029 is set to ON.

→ For the instruction execution complete flag use method, refer to Subsection 6.5.2.

Show 6 more labels / short text on this page
Sorting order · M8165=ON Descending order · M8165=OFF Ascending order · Sorting order · M8165=ON Descending order · M8165=OFF Ascending order
Page 547 of the Mitsubishi Electronics MELSEC FX3S user manual — D D D D
Page 547 · click to enlarge
Page 547

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

19 Data Operation 2 – FNC140 to FNC149

19.7 FNC149 – SORT2 / Sort Tabulated Data 2 11

3. Operation examples When the instruction is executed with "n = K2 (column No. 2)" and "n = K3 (column No. 3)" for the following sorting source data, the operations shown below result. The operation examples below indicate 16-bit operations. In the case of 32-bit operation, construct the data table with 32-bit binary data. It is recommended to put a serial number such as a control number in the first column so that the original line number can be estimated based on the contents.

FNC30-FNC39 Rotation and Shift

Sorting source data

Column No. Number of groups (m2 = K4)

1 2 3 4

Line No. Control number Height Weight Age

1 +1 +2 +3

S

1 150 45 20

2 +4 +5 +6 +7

S

2 180 50 40

3 +8 +9 +10 +11

S

3 160 70 30

4 +12 +13 +14 +15

S

4 100 20 8

5 +16 +17 +18 +19

S

5 150 50 45

1. Sorting result when the instruction is executed with "n = K2 (column No. 2)" (in the case of ascending order)

FNC70-FNC79 External FX I/O Device

Column No. 1 2 3 4

Line No. Control number Height Weight Age

1 +1 +2 +3

D

4 100 20 8

2 +4 +5 +6 +7

D

FNC80-FNC89 External FX Device

1 150 45 20

3 +8 +9 +10 +11

D

5 150 50 45

4 +12 +13 +14 +15

D

3 160 70 30

5 +16 +17 +18 +19

D

FNC100-FNC109 Data Transfer 2

2 180 50 40

2. Sorting result when the instruction is executed with "n = K3 (column No. 3)" (in the case of descending order)

Column No. 1 2 3 4

Line No. Control number Height Weight Age

1 +1 +2 +3

D

3 160 70 30

2 +4 +5 +6 +7

D

2 180 50 40

3 +8 +9 +10 +11

D

FNC140-FNC149 Data Operation 2

5 150 50 45

4 +12 +13 +14 +15

D

1 150 45 20

5 +16 +17 +18 +19

D

4 100 20 8

Show 7 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · Number of · data m1 =K5 · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 548 of the Mitsubishi Electronics MELSEC FX3S user manual — S D
Page 548 · click to enlarge
Page 548

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

19 Data Operation 2 – FNC140 to FNC149

19.7 FNC149 – SORT2 / Sort Tabulated Data 2

Related devices

→ For the instruction execution complete flag use method, refer to Subsection 6.5.2.

Mitsubishi Electronics MELSEC FX3S — Related devices diagram (page 548)
Fig. 512 · Related devices

M8029 Instruction execution complete Turns ON when data sorting is completed.

M8165 Descending order Sorts data in the descending order when set to ON. Sorts data in the ascending order when set to OFF.

Related instruction

Mitsubishi Electronics MELSEC FX3S — Related instruction diagram (page 548)
Fig. 513 · Related instruction

Sort tabulated data This instruction sorts a data table consisting of data (lines) and group data (columns) based on a specified group data (column) sorted by line in ascending order. This instruction stores the group data (columns) in serial devices.

Cautions

  • Do not change the contents of operands and data during operation.
  • To execute SORT2 instruction again, set the command input to OFF once, then ON again.
  • Limitation in number of SORT2 instructions Up to two SORT2 instructions can be simultaneously driven in a program.
  • Writing during RUN is disabled for a circuit block including SORT2 instruction.
  • When the same device is specified in and The source data is overwritten with the data acquired by sorting.

S D

Pay close attention not to change the contents of until execution of SORT2 instruction is completed.

  • Ensure that the sorted data does not overlap with the source data.
Mitsubishi Electronics MELSEC FX3S — S D diagram (page 548)
Fig. 514
  • Note that the 32-bit values [m1+1, m1] and [n+1, n] are valid when D or R is specified as "m1" or "n" in a 32-bit instruction. In the case of "DSORT2 D0 D50 K4 D100 R0", "m1" is [D51, D50], and "n" is [R1, R0].
Page 549 of the Mitsubishi Electronics MELSEC FX3S user manual — 20. Positioning Control – FNC150 to FNC159
Page 549 · click to enlarge
Page 549

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

20 Positioning Control – FNC150 to FNC159

Mitsubishi Electronics MELSEC FX3S — 20. Positioning Control – FNC150 to FNC159 diagram (page 549)
Fig. 515 · 20. Positioning Control – FNC150 to FNC159

FNC150 to FNC159 provide positioning instructions using the built-in pulse output function of the PLC.

→ For details, refer to the Positioning Control Edition manual.

During RUN, avoid writing while any positioning control instruction (FNC150, FNC151, or FNC156 to FNC159) is executed (that is, while pulses are output). If program write is executed during RUN to a circuit block including a target instruction below while pulses are being output, the PLC executes the operation shown below.

Target instruction PLC operation when writing executed during RUN while instruction is

During operation with acceleration/deceleration Decelerates and stops pulse output.

Page 550 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Applicable devices
Page 550 · click to enlarge
Page 550

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

20 Positioning Control – FNC150 to FNC159

20.1 FNC150 – DSZR / Dog Search Zero Return

20.1 FNC150 – DSZR / Dog Search Zero Return

Outline

This instruction executes a zero return, and aligns the mechanical position with a present value register inside the PLC. In addition, this instruction enables the following functions not supported by the ZRN (FNC156) instruction:

  • DOG search function
  • Zero return by the near-point (dog) signal and zero-phase signal It is not possible, however, to count the zero-phase signal and then determine the zero point.

→ For explanation of the instruction, refer to the Positioning Control Edition manual.

→ For cautions on using special high-speed output adapters,

refer to the Positioning Control Edition manual.

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

DSZR −

2. Set data

Mitsubishi Electronics MELSEC FX3S — DSZR − diagram (page 550)
Fig. 516

Device number (Y) from which pulses are to be output

Device number to which rotation direction signal is output

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 550)
Fig. 517 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S1 : "D .b" is available only in FX3U/FX3UC PLCs. However, index modifiers (V and Z) are not available. S2 : In the case of FX3G/FX3GC/FX3U/FX3UC PLCs, specify X000 to X007.

In the case of FX3S PLC, specify X000 to X005. S3 : Specify Y000, Y001 or Y002*1 transistor output from the main unit, or specify Y000, Y001, Y002*3 or Y003*3

from a high-speed output special adapter*2.

*1. Y002 is not available in FX3G PLC (14-point and 24-point type) and FX3S/FX3GC PLCs.

*2. High-speed output special adapters can be connected only to FX3U PLC.

*3. To use Y002 and Y003 with a high-speed output special adapter, connected a second high-speed output special adapter. Points

  • When using a relay output type or triac output type FX 3U PLC, a special high-speed output adapter is required.
  • Outputs of special high-speed output adapters work as differential line drivers.
Show 4 more labels / short text on this page
Mnemonic Operation Condition · 32-bit Instruction · 9 steps DSZR · Continuous Operation
Page 551 of the Mitsubishi Electronics MELSEC FX3S user manual — Function change depending on the version
Page 551 · click to enlarge
Page 551

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

20 Positioning Control – FNC150 to FNC159

20.1 FNC150 – DSZR / Dog Search Zero Return 11

S4 : When using a special high-speed output adapter for the pulse output destination in an FX3U PLC, the rotation

FNC30-FNC39 Rotation and Shift

direction signal must be used by the following table output. When using a built-in transistor output for the pulse output destination in an FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs, the rotation direction signal must use transistor output.

Special high-speed output adapter No. Pulse output Rotation direction output

D 1 D 2

=Y000 =Y004

No. 1 (1st unit)

D 1 D 2

=Y001 =Y005

D 1 D 2

=Y002 =Y006

No. 2 (2nd unit)

D 1 D 2

=Y003 =Y007

Explanation of function and operation

DSZR S2 ‚ S1 ‚ D1 ‚ D2 ‚

Caution on writing during RUN

During RUN, avoid writing while the DSZR (FNC150) instruction is executed (that is, while a pulse is output). Note that if writing is executed during RUN to a circuit block including the FNC150 instruction while pulses are output, the PLC decelerates and stops pulse output.

Function change depending on the version

The function of FNC150 instruction is changed depending on the version as shown in the table below.

→ For explanation of the instruction and the contents of function change,

refer to the Positioning Control Edition.

FNC70-FNC79 External FX I/O Device

Item Outline of function FX3S FX3G FX3GC FX3U FX3UC

When a special auxiliary relay corresponding to is set to ON, the clear signal output destination is changed to an output number specified by a special data register

Ver. 1.00

Ver. 1.00

Ver. 1.40

Ver. 2.20

Ver. 2.20

Clear signal output destination specification function

FNC80-FNC89 External FX Device

corresponding to .

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 13 more labels / short text on this page
FNC40-FNC49 Data Operation · Command · FNC50-FNC59 High-Speed Processing · input FNC150 · FMC60-FNC69 Handy Instruction · Applicable version · or later · or later · or later · or later · or later · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 552 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Applicable devices
Page 552 · click to enlarge
Page 552

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

20 Positioning Control – FNC150 to FNC159

20.2 FNC151 – DVIT / Interrupt Positioning

20.2 FNC151 – DVIT / Interrupt Positioning

Outline

This instruction executes one-speed interrupt constant quantity feed.

→ For explanation of the instruction, refer to the Positioning Control Edition manual.

→ For cautions on using special high-speed output adapters,

refer to the Positioning Control Edition manual.

1. Instruction format

DVIT D DVIT

2. Set data

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 552)
Fig. 518 · 1. Instruction format

Number of output pulses (incremental address) after interrupt*1

Device number (Y) from which pulses are to be output

Bit Device number to which rotation direction signal is output

*1. Setting range: −32768 to +32767 (except 0) in 16-bit operation −999,999 to +999,999 (except 0) in 32-bit operation

*2. Setting range10 to 32767 Hz in 16-bit operation Following range in 32-bit operation

Pulse output destination Setting range

FX3U PLC Special high-speed output adapter 10 to 200,000 (Hz)

FX3U/FX3UC PLC Main unit (transistor output) 10 to 100,000 (Hz)

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 552)
Fig. 519 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

S1 : Specify Y000, Y001 or Y002 transistor output from the main unit, or specify Y000, Y001, Y002*4 or Y003*4 from

a high-speed output special adapter*3.

*3. High-speed output special adapters can be connected only to FX3U PLC.

*4. To use Y002 and Y003 with a high-speed output special adapter, connected a second high-speed output special adapter. Points

  • When using a relay output type or triac output type FX 3U PLC, a special high-speed output adapter is required.
  • Outputs of special high-speed output adapters work as differential line drivers.
Show 8 more labels / short text on this page
16-bit Instruction · Mnemonic Operation Condition · 32-bit Instruction · Mnemonic Operation Condition · Continuous Operation DDVIT · Continuous Operation · 9 steps · 17 steps
Page 553 of the Mitsubishi Electronics MELSEC FX3S user manual — Function change depending on the version
Page 553 · click to enlarge
Page 553

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

20 Positioning Control – FNC150 to FNC159

20.2 FNC151 – DVIT / Interrupt Positioning 11

S2 : When using a special high-speed output adapter for the pulse output destination in an FX3U PLC, the rotation

FNC30-FNC39 Rotation and Shift

direction signal must be used by the following table output. When using a built-in transistor output for the pulse output destination in an FX3U/FX3UC PLC, the rotation direction signal must use transistor output.

Special high-speed output adapter No. Pulse output Rotation direction output

D 1 D 2

=Y000 =Y004

No. 1 (1st unit)

D 1 D 2

=Y001 =Y005

D 1 D 2

=Y002 =Y006

No. 2 (2nd unit)

D 1 D 2

=Y003 =Y007

S3 : "D .b" cannot be indexed with index registers (V and Z).

Explanation of function and operation

DVIT S2 ‚ S1 ‚ D1 ‚ D2 ‚

Caution on writing during RUN

During RUN, avoid writing while the DVIT (FNC151) instruction is executed (that is, while a pulse is output). Note that if writing is executed during RUN to a circuit block including the FNC151 instruction while pulses are output, the PLC decelerates and stops pulse output.

Function change depending on the version

The functions of FNC151 instruction are changed depending on the version as shown in the table below.

FNC70-FNC79 External FX I/O Device

→ For explanation of the instruction and the contents of function change,

refer to the Positioning Control Edition.

Item Outline of function FX3U FX3UC

When M8336 is set to ON, the interrupt input signal corresponding to Y000 to Y003 is changed to an input number (X000 to X007) specified by D8336. When using a transistor output in the main unit, Y003 cannot be specified.

Ver. 2.20 or later Ver. 1.30 or later Interrupt input signal

FNC80-FNC89 External FX Device

When "8" is specified by D8336 to the interrupt input signal corresponding to Y000 to Y003 and M8336 is set to ON, the interrupt input signal is changed to a special auxiliary relay. When this changed special auxiliary relay is set to from OFF to ON in an input interrupt program, the PLC starts the interrupt operation. When this function is used, however, the logic of the interrupt input cannot be inverted. In addition, when using a transistor output in the main unit, Y003 cannot be specified.

Ver. 2.20 or later Ver. 2.20 or later User interrupt mode

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 9 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · Command · input FNC151 · FMC60-FNC69 Handy Instruction · Applicable version · specification function · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 554 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 554 · click to enlarge
Page 554

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

20 Positioning Control – FNC150 to FNC159

20.3 FNC152 – TBL / Batch Data Positioning Mode

20.3 FNC152 – TBL / Batch Data Positioning Mode

Outline

This instruction executes one specified table operation from the data table set in GX Works2 etc.

→ For explanation of the instruction, refer to the Positioning Control Edition manual.

→ For cautions on using special high-speed output adapters,

refer to the Positioning Control Edition manual.

DVIT (FNC151)*1 Interrupt positioning

PLSV (FNC157) Variable speed pulse output

DRVI (FNC158) Drive to increment

DRVA (FNC159) Drive to absolute

*1. This function is supported only in FX3U/FX3UC PLCs.

1. Instruction format

16-bit Instruction Mnemonic Operation Condition FNC 152

TBL D

DTBL

2. Set data

Operand type Description Data type

Device number (Y) from which pulses are to be output Bit

n Table entry number [1 to 100] to be executed 32-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 554)
Fig. 520 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S1 : Specify Y000, Y001 or Y002*2 transistor output from the main unit, or specify Y000, Y001, Y002*4 or Y003*4

from a high-speed output special adapter*3.

*2. Y002 is not available in FX3G PLC (14-point and 24-point type) and FX3GC PLC.

*3. High-speed output special adapters can be connected only to FX3U PLC.

*4. To use Y002 and Y003 with a high-speed output special adapter, connected a second high-speed output special adapter. Points

  • When using a relay output type or triac output type FX 3U PLC, a special high-speed output adapter is required.
  • Outputs of special high-speed output adapters work as differential line drivers.

Explanation of function and operation

Caution on writing during RUN

Writing is disabled to a circuit block including the TBL (FNC152) instruction during RUN.

Show 8 more labels / short text on this page
Instruction Description · 32-bit Instruction · Mnemonic Operation Condition · Continuous Operation − · 17 steps · Command · input FNC152 · DTBL D n
Page 555 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 555 · click to enlarge
Page 555

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

20 Positioning Control – FNC150 to FNC159

20.4 FNC155 – ABS / Absolute Current Value Read 11

20.4 FNC155 – ABS / Absolute Current Value Read

FNC30-FNC39 Rotation and Shift

Outline

This instruction reads the absolute position (ABS) data when the servo amplifier (equipped with the absolute position detection function) MR-J4 A, MR-J3 A, MR-J2(S) A, or MR-H A is connected. The data is converted into a pulse when being read.

→ For explanation of the instruction, refer to the Positioning Control Edition.

1. Instruction format

16-bit Instruction Mnemonic Operation Condition

ABS D DABS

2. Set data

Operand type Description Data type

Head device number inputting absolute (ABS) data output signal sent from servo amplifier

S S

Three points are occupied from .

Bit Head device number outputting absolute (ABS) data control signal to servo amplifier

D 1 D 1

Three points are occupied from .

Device number storing absolute (ABS) data (32-bit value) 32-bit binary

3. Applicable devices

FNC70-FNC79 External FX I/O Device

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FNC80-FNC89 External FX Device

3 S3 S4 3 3

S1: Specify a transistor output. S2: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S3: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S4: This function is supported only in FX3U/FX3UC PLCs.

FNC100-FNC109 Data Transfer 2

Explanation of function and operation

DABS S ‚ D1 ‚ D2 ‚

FNC140-FNC149 Data Operation 2

Show 16 more labels / short text on this page
FNC40-FNC49 Data Operation · 32-bit Instruction · Mnemonic Operation Condition · Continuous Operation − · 13 steps · FNC50-FNC59 High-Speed Processing · FMC60-FNC69 Handy Instruction · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input FNC155 · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 556 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Applicable devices
Page 556 · click to enlarge
Page 556

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

20 Positioning Control – FNC150 to FNC159

20.5 FNC156 – ZRN / Zero Return

20.5 FNC156 – ZRN / Zero Return

Outline

This instruction executes a zero return, and aligns the mechanical position with a present value register inside the PLC. When the dog search function is required, use DSZR (FNC150) instruction.

→ For explanation of the instruction, refer to the Positioning Control Edition manual.

→ For cautions on using special high-speed output adapters,

refer to the Positioning Control Edition manual.

1. Instruction format

ZRN D ZRN

2. Set data

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 556)
Fig. 521 · 1. Instruction format

16- or 32-bit binary Creep speed [10 to 32767 Hz]

Bit Device number (Y) from which pulses are to be output

*1. Setting range10 to 32767 Hz for 16-bit operation

Following range for 32-bit operation

Pulse output destination Setting range

FX3U PLC Special high-speed output adapter 10 to 200,000 (Hz)

FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs Main unit (transistor output) 10 to 100,000 (Hz)

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 556)
Fig. 522 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S3 S4 3

3 S3 S4 3

S1 : "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available.

S2 : Specify Y000, Y001 or Y002*2 transistor output from the main unit, or specify Y000, Y001, Y002*4 or Y003*4

from a high-speed output special adapter*3.

*2. Y002 is not available in FX3G PLC (14-point and 24-point type) and FX3S/FX3GC PLCs.

*3. High-speed output special adapters can be connected only to FX3U PLC.

*4. To use Y002 and Y003 with a high-speed output special adapter, connected a second high-speed output special adapter. Points

  • When using a relay output type or triac output type FX 3U PLC, a special high-speed output adapter is required.
  • Outputs of special high-speed output adapters work as differential line drivers. S 3 : This function is supported only in FX 3G /FX 3GC /FX 3U /FX 3UC PLCs. S 4 : This function is supported only in FX 3U /FX 3UC PLCs.
Show 8 more labels / short text on this page
16-bit Instruction · Mnemonic Operation Condition · 32-bit Instruction · Mnemonic Operation Condition · 9 steps · Continuous Operation DZRN · 17 steps · Continuous Operation
Page 557 of the Mitsubishi Electronics MELSEC FX3S user manual — Function change depending on the version
Page 557 · click to enlarge
Page 557

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

20 Positioning Control – FNC150 to FNC159

20.5 FNC156 – ZRN / Zero Return 11

Explanation of function and operation

FNC30-FNC39 Rotation and Shift

ZRN S1 ‚ S2 ‚ S3 ‚ D ‚

Caution on writing during RUN

During RUN, avoid writing while the ZRN (FNC156) instruction is executed (that is, while pulses are output). Note that if writing is executed during RUN to a circuit block including the FNC156 instruction while pulses are output, the PLC decelerates and stops pulse output.

Function change depending on the version

The function of FNC156 instruction is changed depending on the version as shown in the table below.

→ For explanation of the instruction and the contents of function change,

refer to the Positioning Control Edition.

Item Outline of function FX3S FX3G FX3GC FX3U FX3UC

When a special auxiliary relay corresponding to is set to ON, the clear signal output destination is changed to an output number specified by a special data register

Ver. 1.00

Ver. 1.00

Ver. 1.40

Ver. 2.20

Ver. 2.20

Clear signal output destination specification function

corresponding to .

FNC70-FNC79 External FX I/O Device

FNC80-FNC89 External FX Device

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 13 more labels / short text on this page
Command · input FNC156 · FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · Applicable version · FMC60-FNC69 Handy Instruction · or later · or later · or later · or later · or later · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 558 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Applicable devices
Page 558 · click to enlarge
Page 558

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

20 Positioning Control – FNC150 to FNC159

20.6 FNC157 – PLSV / Variable Speed Pulse Output

20.6 FNC157 – PLSV / Variable Speed Pulse Output

Outline

This instruction outputs variable speed pulses with an assigned rotation direction.

→ For explanation of the instruction, refer to the Positioning Control Edition manual.

→ For cautions on using special high-speed output adapters,

refer to the Positioning Control Edition manual.

1. Instruction format

PLSV D PLSV

2. Set data

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 558)
Fig. 523 · 1. Instruction format

Device number for output pulse frequency*1 16- or 32-bit binary

Device number (Y) from which pulses are to be output

Bit Device number to which rotation direction signal is output

*1. Setting range: −32768 to −1, +1 to +32767 (except 0) Hz*2 for 16-bit operation

Following range for 32-bit operation

Pulse output destination Setting range

FX3U PLC Special high-speed output adapter −200,000 to −1, +1 to 200,000 (Hz)

FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs Main unit (transistor output) −100,000 to −1, +1 to 100,000 (Hz)*3

*2. When operation without acceleration/deceleration (M8338 = OFF), setting range of FX3S/FX3G/FX3GC PLC is -32,768 to -10 Hz, +10 to 32,767 Hz.

*3. When operation without acceleration/deceleration (M8338 = OFF), setting range of FX3S/FX3G/FX3GC PLC is -100,000 to -10 Hz, +10 to 100,000 Hz.

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 558)
Fig. 524 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S4 S5 3

S1 : Specify Y000, Y001 or Y002*4 transistor output from the main unit, or specify Y000, Y001, Y002*6 or Y003*6

from a high-speed output special adapter*5.

*4. 002 is not available in FX3G PLC (14-point and 24-point type) and FX3S/FX3GC PLC. *5. High-speed output special adapters can be connected only to FX3U PLC. *6. To use Y002 or Y003 with a high-speed output special adapter, connected a second high-speed output special adapter. Points

  • When using a relay output type or triac output type FX 3U PLC, a special high-speed output adapter is required.
  • Outputs of special high-speed output adapters work as differential line drivers. S 2 : When using a special high-speed output adapter for the pulse output destination in an FX 3U PLC, the rotation

direction signal must be used by the following table output. When using a built-in transistor output for the pulse output destination in an FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs, the rotation direction signal must use transistor output.

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 558)
Fig. 525 · 3. Applicable devices

Special high-speed output adapter No. Pulse output Rotation direction output

Show 8 more labels / short text on this page
16-bit Instruction · Mnemonic Operation Condition · 32-bit Instruction · Mnemonic Operation Condition · 7 steps · Continuous Operation DPLSV · 13 steps · Continuous Operation
Page 559 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 S 1
Page 559 · click to enlarge
Page 559

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

20 Positioning Control – FNC150 to FNC159

20.6 FNC157 – PLSV / Variable Speed Pulse Output 11

S3 : "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S4 : This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S5 : This function is supported only in FX3U/FX3UC PLCs.

FNC30-FNC39 Rotation and Shift

Explanation of function and operation

PLSV S1 ‚ D1 ‚ D2 ‚

Caution on writing during RUN

During RUN, avoid writing while PLSV (FNC157) instruction is executed (that is, while pulses are output). Note that if writing is executed during RUN to a circuit block including FNC157 instruction while pulses are output, the PLC executes the operation shown below.

PLC operation when writing is executed during RUN while instruction is

During operation with acceleration/deceleration*1 Decelerates and stops pulse output.

During operation without acceleration/deceleration Immediately stops pulse output.

*1. Only available for FX3UC PLC Ver. 2.20 or later and FX3S/FX3G/FX3GC/FX3U PLCs.

Function change depending on the version

The function of the FNC157 instruction is changed depending on the version as shown in the table below.

→ For explanation of the instruction and the contents of function change,

refer to the Positioning Control Edition.

Item Outline of function FX3S FX3G FX3GC FX3U FX3UC

FNC70-FNC79 External FX I/O Device

When M8338 is set to ON, the PLC accelerates or

Acceleration/ deceleration operation function

Ver. 1.00

Ver. 1.00

Ver. 1.40

Ver. 2.20

Ver. 2.20

decelerates up to in the acceleration or deceleration

time corresponding to if changes.

D 1 S 1

FNC80-FNC89 External FX Device

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 14 more labels / short text on this page
Command · input FNC157 · FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · executed · FMC60-FNC69 Handy Instruction · Applicable version · or later · or later · or later · or later · or later · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 560 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Applicable devices
Page 560 · click to enlarge
Page 560

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

20 Positioning Control – FNC150 to FNC159

20.7 FNC158 – DRVI / Drive to Increment

20.7 FNC158 – DRVI / Drive to Increment

Outline

This instruction executes one-speed positioning by incremental drive. The movement distance from the present position can be specified, positive or negative.

→ For explanation of the instruction, refer to the Positioning Control Edition manual.

→ For cautions on using special high-speed output adapters,

refer to the Positioning Control Edition manual.

1. Instruction format

DRVI D DRVI

2. Set data

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 560)
Fig. 526 · 1. Instruction format

Device number (Y) from which pulses are to be output

Bit Device number to which rotation direction signal is output

*1. Setting range: −32768 to +32767 (except 0) for 16-bit operation −999,999 to +999,999 (except 0) for 32-bit operation

*2. Setting range10 to 32767 Hz for 16-bit operation

Following range for 32-bit operation

Pulse output destination Setting range

FX3U PLC Special high-speed output adapter 10 to 200,000 (Hz)

FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs Main unit (transistor output) 10 to 100,000 (Hz)

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 560)
Fig. 527 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S4 S5 3

3 S4 S5 3

S1 : Specify Y000, Y001 or Y002*3 transistor output from the main unit, or specify Y000, Y001, Y002*5, or Y003*5

from a high-speed output special adapter*4.

*3. Y002 is not available in FX3G PLC (14-point and 24-point type) and FX3S/FX3GC PLC.

*4. High-speed output special adapters can be connected only to FX3U PLC.

*5. To use Y002 or Y003 with a high-speed output special adapter, connected a second high-speed output special adapter. Points

  • When using a relay output type or triac output type FX 3U PLC, a special high-speed output adapter is required.
  • Outputs of special high-speed output adapters work as differential line drivers.
Show 8 more labels / short text on this page
Mnemonic Operation Condition · Mnemonic Operation Condition · 16-bit Instruction · 32-bit Instruction · 9 steps · Continuous Operation DDRVI · 17 steps · Continuous Operation
Page 561 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution on writing during RUN
Page 561 · click to enlarge
Page 561

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

20 Positioning Control – FNC150 to FNC159

20.7 FNC158 – DRVI / Drive to Increment 11

S2 :When using a special high-speed output adapter for the pulse output destination in an FX3U PLC, the rotation

FNC30-FNC39 Rotation and Shift

direction signal must be used by the following table output. When using a built-in transistor output for the pulse output destination in an FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs, the rotation direction signal must use transistor output.

Special high-speed output adapter No. Pulse output Rotation direction output

D 1 D 2

=Y000 =Y004

No. 1 (1st unit)

D 1 D 2

=Y001 =Y005

D 1 D 2

=Y002 =Y006

No. 2 (2nd unit)

D 1 D 2

=Y003 =Y007

S3 : "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S4 : This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S5 : This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

DRVI S1 ‚ S2 ‚ D1 ‚ D2 ‚

Caution on writing during RUN

During RUN, avoid writing while DRVI (FNC158) instruction is executed (that is, while pulses are output). Note that if writing is executed during RUN to a circuit block including FNC158 instruction while pulses are output, the PLC decelerates and stops pulse output.

FNC70-FNC79 External FX I/O Device

FNC80-FNC89 External FX Device

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 7 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · Command · input FNC158 · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 562 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Applicable devices
Page 562 · click to enlarge
Page 562

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

20 Positioning Control – FNC150 to FNC159

20.8 FNC159 – DRVA / Drive to Absolute

20.8 FNC159 – DRVA / Drive to Absolute

Outline

This instruction executes one-speed positioning by absolute drive. The movement distance from the zero point can be specified.

→ For explanation of the instruction, refer to the Positioning Control Edition manual.

→ For cautions on using special high-speed output adapters,

refer to the Positioning Control Edition manual.

1. Instruction format

DRVA D DRVA

2. Set data

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 562)
Fig. 528 · 1. Instruction format

Device number (Y) from which pulses are to be output

Bit Device number to which rotation direction signal is output

*1. Setting range− 32768 to +32767 for 16-bit operation − 999,999 to +999,999 for 32-bit operation
*2. Setting range10 to 32767 Hz for 16-bit operation

Following range for 32-bit operation

Pulse output destination Setting range

FX3U PLC Special high-speed output adapter 10 to 200,000 (Hz)

FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs Main unit (transistor output) 10 to 100,000 (Hz)

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 562)
Fig. 529 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S4 S5 3

3 S4 S5 3

S1 : Specify Y000, Y001 or Y002*3 transistor output from main unit, or specify Y000, Y001, Y002*5 or Y003*5 from a

high-speed output special adapter*4.

*3. Y002 is not available in FX3G PLC (14-point and 24-point type) and FX3S/FX3GC PLC.

*4. High-speed output special adapters can be connected only to FX3U PLC.

*5. To use Y002 or Y003 with a high-speed output special adapter, connected a second high-speed output special adapter. Points

  • When using a relay output type or triac output type FX 3U PLC, a special high-speed output adapter is required.
  • Outputs of special high-speed output adapters work as differential line drivers.
Show 8 more labels / short text on this page
Mnemonic Operation Condition · Mnemonic Operation Condition · 16-bit Instruction · 32-bit Instruction · 9 steps · Continuous Operation DDRVA · 17 steps · Continuous Operation
Page 563 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution on writing during RUN
Page 563 · click to enlarge
Page 563

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

20 Positioning Control – FNC150 to FNC159

20.8 FNC159 – DRVA / Drive to Absolute 11

S2 : When using a special high-speed output adapter for the pulse output destination in an FX3U PLC, the rotation

FNC30-FNC39 Rotation and Shift

direction signal must be used by the following table output. When using a built-in transistor output for the pulse output destination in an FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs, the rotation direction signal must use transistor output.

Special high-speed output adapter No. Pulse output Rotation direction output

D 1 D 2

=Y000 =Y004

No. 1 (1st unit)

D 1 D 2

=Y001 =Y005

D 1 D 2

=Y002 =Y006

No. 2 (2nd unit)

D 1 D 2

=Y003 =Y007

S3 : "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S4 : This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S5 : This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

DRVA S1 ‚ S2 ‚ D1 ‚ D2 ‚

Caution on writing during RUN

During RUN, avoid writing while DRVA (FNC159) instruction is executed (that is, while pulses are output). Note that if writing is executed during RUN to a circuit block including FNC159 instruction while pulses are output, the PLC decelerates and stops pulse output.

FNC70-FNC79 External FX I/O Device

FNC80-FNC89 External FX Device

FNC100-FNC109 Data Transfer 2

FNC140-FNC149 Data Operation 2

Show 7 more labels / short text on this page
FNC40-FNC49 Data Operation · FNC50-FNC59 High-Speed Processing · Command · input FNC159 · FMC60-FNC69 Handy Instruction · FNC110-FNC139 Floating Point · FNC150-FNC159 Positioning Control
Page 564 of the Mitsubishi Electronics MELSEC FX3S user manual — 21. Real Time Clock Control – FNC160 to FNC169
Page 564 · click to enlarge
Page 564

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

21 Real Time Clock Control – FNC160 to FNC169

21. Real Time Clock Control – FNC160 to FNC169

FNC160 to FNC169 provide operation and comparison instructions for the time data. These instructions can set the time of the built-in PLC real time clock, and converts the format of the time data.

Mitsubishi Electronics MELSEC FX3S — 21. Real Time Clock Control – FNC160 to FNC169 diagram (page 564)
Fig. 530 · 21. Real Time Clock Control – FNC160 to FNC169
Page 565 of the Mitsubishi Electronics MELSEC FX3S user manual — 3 3 3 S 2 S 3 3
Page 565 · click to enlarge
Page 565

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

21 Real Time Clock Control – FNC160 to FNC169

21.1 FNC160 – TCMP / RTC Data Compare 21

21.1 FNC160 – TCMP / RTC Data Compare

FNC160-FNC169 Real Time Clock Control

Outline

This instruction compares the comparison time with the time data, and turns ON or OFF bit devices according to the comparison result.

1. Instruction format

P FNC 160

Mnemonic Operation Condition 16-bit Instruction

TCMP − −

Continuous Operation Pulse (Single) Operation

TCMPP

2. Set data

Operand type Description Data type

S 1 ‚ S 1

Specifies "hour" of the comparison time [setting range: 0 to 23]. 16-bit binary

Specifies "minute" of the comparison time [setting range: 0 to 59]. 16-bit binary

Specifies "second" of the comparison time [setting range: 0 to 59]. 16-bit binary

Specifies "hour" of the time data (hour, minute, and second). (Three devices are occupied.) 16-bit binary

Turns ON or OFF according to the comparison result. (Three devices are occupied.) Bit

3. Applicable devices

FNC190-FNC199 Block Data Operation

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S 1 ‚ S 1

3 S2 S3

3 S2 S3

FNC200-FNC209 Character String Control

3 S2 S3

3 3 3 S 2 S 3 3

S 2 ‚ D

S1: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S3: This function is supported only in FX3U/FX3UC PLCs.

FNC210-FNC219 Data Operation 3

FNC250-FNC269 Data Table Operation

Show 13 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 11 steps TCMP · FNC180 Alternate Instructions · FNC181-FNC189 Others · Oper- · and Type · Unit Index Con- stant · Real Number · Charac- ter String Pointer · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 566 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 566 · click to enlarge
Page 566

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

21 Real Time Clock Control – FNC160 to FNC169

21.1 FNC160 – TCMP / RTC Data Compare

Explanation of function and operation

1. 16-bit operation (TCMP)

The comparison time (hour, minute, and second) stored in , , and is compared with the time data

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 566)
Fig. 531 · Explanation of function and operation

(hour, minute, and second) stored in , +1, and +2. Three devices starting from turn ON or OFF according to the comparison result.

TCMP S1 ‚ S2 ‚ S3 ‚ S ‚ D ‚

↑ Even if the command contact turns OFF from ON and TCMP instruction is not executed, , +1 and +2 hold the status before the command contact turned OFF.

Cautions

1. Number of occupied devices

Three devices are occupied respectively by and . Make sure that these devices are not used in other controls for the machine.

S D

2. When utilizing the time (hour, minute, and second) of the built-in PLC real time clock Read the values of special data registers by TRD (FNC166) instruction, and then specify those word devices as the operands.

Program example

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 566)
Fig. 532 · Program example

S1 ‚ S2 ‚ S3 ‚ S ‚ D ‚

Turns ON in the case of "10:30:50 > "

: Specifies "hour" of the comparison time. : Specifies "minute" of the comparison time.

Turns ON in the case of "10:30:50 = "

Turns ON in the case of "10:30:50 < "

↑ Even if X000 is OFF and TCMP instruction is not executed, M0 to M2 hold the status before X000 turned OFF.

D ‚ +1, D ‚ +2 D ‚ ,

: Three bit devices turn ON or OFF according to the comparison result.

Page 567 of the Mitsubishi Electronics MELSEC FX3S user manual — D ‚ D ‚ D ‚
Page 567 · click to enlarge
Page 567

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

21 Real Time Clock Control – FNC160 to FNC169

21.2 FNC161 – TZCP / RTC Data Zone Compare 21

21.2 FNC161 – TZCP / RTC Data Zone Compare

FNC160-FNC169 Real Time Clock Control

Outline

This instruction compares two comparison time (comparison time zone) with the time data, and turns ON or OFF the specified bit devices according to the comparison results. 1. Instruction format

P FNC 161

Mnemonic Operation Condition 16-bit Instruction

TZCP − −

Continuous Operation Pulse (Single) Operation

TZCPP

2. Set data

Operand type Description Data type

Specifies "hour" of the lower limit comparison time (hour, minute, and second). (Three devices are occupied.) 16-bit binary

S 1 ‚ S 1

Specifies "hour" of the upper limit comparison time (hour, minute, and second). (Three devices are occupied.) 16-bit binary

Specifies "hour" of the time data (hour, minute, and second). (Three devices are occupied.) 16-bit binary

Turns ON or OFF according to the comparison result. (Three devices are occupied.) Bit

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC190-FNC199 Block Data Operation

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S 1 ‚ S 1

3 3 3 S 2 S 3 3

3 3 3 S 2 S 3 3

3 3 3 S 2 S 3 3

S 2 ‚ D

FNC200-FNC209 Character String Control

S1: "D .b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S3: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (TZCP) The lower limit and upper limit comparison time (hour, minute, and second) are compared with the time data (hour, minute, and second) stored in three devices , +1, and +2. Three devices starting from turn ON or OFF according to the comparison result.

FNC210-FNC219 Data Operation 3

S S S D

This instruction compares the comparison time zone specified by two points with the time data.

TZCP S1 ‚ S2 ‚ S ‚ D ‚

Turns ON in the case of " ".

>

Turns ON in the case of " ".

≤ ≤

FNC250-FNC269 Data Table Operation

>

Turns ON in the case of " ".

↑

Even if the command contact turns OFF from ON and TZCP instruction is not executed, , +1 and +2 hold the status before the command contact turned OFF.

D ‚ D ‚ D ‚

Show 36 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 9 steps TZCP · FNC180 Alternate Instructions · FNC181-FNC189 Others · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input FNC161 · FNC220-FNC249 Data Comparison · (hour) · (hour) · +1 (minute) · +1 (minute) · +2 (second) · +2 (second) · (hour) · (hour) · (hour) · +1 (minute) · +1 (minute) · +1 (minute) · +2 (second) · +2 (second) · +2 (second) · (hour) · (hour) · +1 (minute) · +1 (minute) · +2 (second) · +2 (second) · FNC270-FNC276 Ex-Device
Page 568 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 568 · click to enlarge
Page 568

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

21 Real Time Clock Control – FNC160 to FNC169

21.2 FNC161 – TZCP / RTC Data Zone Compare

Cautions

1. Number of occupied devices

Three devices are occupied respectively by , , , and . Make sure that these devices are not used in other controls for the machine.

S 1 S 2 S 3 D

2. When utilizing the time (hour, minute, and second) of the built-in PLC real time clock Read the values of special data registers by TRD (FNC166) instruction, and then specify those word devices as the operands.

Program example

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 568)
Fig. 533 · Program example

S1 ‚ S2 ‚ S ‚ D ‚

TZCP D 20 D 30 D 0 M 3

↑ Even if X000 is OFF and TZCP instruction is not executed, M0 to M2 hold the status before X000 turned OFF.

S1 ‚ : Specify the lower limit of the comparison time zone in "hour", "minute" and "second. S1 ‚ +1 and +2 S1 ‚ ,

S2 ‚ S2 ‚ +1 and S2 ‚ +2 , : Specify the upper limit of the comparison time zone in "hour", "minute" and "second.

S ‚ S ‚ +1 and +2 S ‚ , : Specify the time data in "hour", "minute" and "second.

+1 and +2 D ‚ D ‚ D ‚ , : Turn ON or OFF according to the comparison result.

The setting range of "hour" is from 0 to 23.

The setting range of "minute" is from 0 to 59.

The setting range of "second" is from 0 to 59.

Page 569 of the Mitsubishi Electronics MELSEC FX3S user manual — +
Page 569 · click to enlarge
Page 569

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

21 Real Time Clock Control – FNC160 to FNC169

21.3 FNC162 – TADD / RTC Data Addition 21

21.3 FNC162 – TADD / RTC Data Addition

FNC160-FNC169 Real Time Clock Control

Outline

This instruction executes addition of two time data, and stores the addition result to word devices.

1. Instruction format

P FNC 162

Mnemonic Operation Condition 16-bit Instruction

TADD − −

Continuous Operation Pulse (Single) Operation

TADDP

2. Set data

Operand type Description Data type

Specifies "hour" of the first time data (hour, minute, and second) used in addition. (Three devices are occupied.) 16-bit binary

S 1 ‚ S 1

Specifies "hour" of the second time data (hour, minute, and second) used in addition. (Three devices are occupied.) 16-bit binary

Stores the addition result (hour, minute, and second) of two time data. (Three devices are occupied.) 16-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC190-FNC199 Block Data Operation

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S 1 ‚ S 1

3 3 3 S 1 S 2 3

3 3 3 S 1 S 2 3

S 2 ‚ D

3 3 3 S 1 S 2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

FNC200-FNC209 Character String Control

Explanation of function and operation

1. 16-bit operation (TADD)

The time data (hour, minute, and second) stored in , +1, and +2 is added to the time data (hour,

S 2 S 2 S 2

FNC210-FNC219 Data Operation 3

minute, and second) stored in , +1, and +2, and the addition result (hour, minute, and second) is

S 1 S 1 S 1

stored in , +1, and +2.

D D D

( , +1, +2)+( , +1, +2)

S1 ‚ S1 ‚ S1 ‚ S2 ‚ S2 ‚ S2 ‚

TADD S1 ‚ S2 ‚ D ‚

→( , +1, +2)

D ‚ D ‚ D ‚

The setting range of "hour" is from 0 to 23.

+

The setting range of "minute" is from 0 to 59.

The setting range of "second" is from 0 to 59.

  • When the operation result exceeds 24 hours, the carry flag turns ON, and the value simply acquired by addition subtracted by 24 hours is stored as the operation result.

FNC250-FNC269 Data Table Operation

  • When the operation result becomes "0" (0:0:0), the zero flag turns ON.
Show 24 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 7 steps TADD · FNC180 Alternate Instructions · FNC181-FNC189 Others · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input FNC162 · FNC220-FNC249 Data Comparison · (hour) · (hour) · (hour) · +1 (minute) · +1 (minute) · +1 (minute) · +2 (second) · +2 (second) · +2 (second) · FNC270-FNC276 Ex-Device
Page 570 of the Mitsubishi Electronics MELSEC FX3S user manual — When the operation result exceeds 24 hours
Page 570 · click to enlarge
Page 570

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

21 Real Time Clock Control – FNC160 to FNC169

21.3 FNC162 – TADD / RTC Data Addition

Cautions

1. Number of occupied devices

Three devices are occupied by , and respectively. Make sure that these devices are not used in other controls for the machine.

S 1 S 2 D

2. When utilizing the time (hour, minute, and second) of the built-in PLC real time clock Read the values of special data registers using the TRD (FNC166) instruction, and then specify those word devices as the operands.

Program example

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 570)
Fig. 534 · Program example

When the operation result exceeds 24 hours

Mitsubishi Electronics MELSEC FX3S — When the operation result exceeds 24 hours diagram (page 570)
Fig. 535 · When the operation result exceeds 24 hours
Page 571 of the Mitsubishi Electronics MELSEC FX3S user manual — −
Page 571 · click to enlarge
Page 571

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

21 Real Time Clock Control – FNC160 to FNC169

21.4 FNC163 – TSUB / RTC Data Subtraction 21

21.4 FNC163 – TSUB / RTC Data Subtraction

FNC160-FNC169 Real Time Clock Control

Outline

This instruction executes subtraction of two time data, and stores the subtraction result to word devices.

1. Instruction format

P FNC 163

Mnemonic Operation Condition 16-bit Instruction

TSUB − −

Continuous Operation Pulse (Single) Operation

TSUBP

2. Set data

Operand type Description Data type

Specifies "hour" of the time data (hour, minute, and second) used in subtraction. (Three devices are occupied.) 16-bit binary

S 1 ‚ S 1

Specifies "hour" of the time data (hour, minute, and second) used in subtraction. (Three devices are occupied.) 16-bit binary

Stores the subtraction result (hour, minute, and second) of two time data. (Three devices are occupied.) 16-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC190-FNC199 Block Data Operation

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S 1 ‚ S 1

3 3 3 S 1 S 2 3

3 3 3 S 1 S 2 3

S 2 ‚ D

3 3 3 S 1 S 2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

FNC200-FNC209 Character String Control

Explanation of function and operation

1. 16-bit operation (TSUB)

The time data (hour, minute, and second) stored in , +1, and +2 is subtracted from the time data

S 2 S 2 S 2

FNC210-FNC219 Data Operation 3

(hour, minute, and second) stored in , +1, and +2, and the subtraction result (hour, minute, and

S 1 S 1 S 1

second) is stored in , +1, and +2.

D D D

( , +1, +2)−( , +1, +2)

S1 ‚ S1 ‚ S1 ‚ S2 ‚ S2 ‚ S2 ‚

TSUB S1 ‚ S2 ‚ D ‚

→ ( , +1, +2)

D ‚ D ‚ D ‚

The setting range of "hour" is from 0 to 23.

−

The setting range of "minute" is from 0 to 59.

The setting range of "second" is from 0 to 59.

When the operation result is smaller than 0 hour, the borrow flag turns ON, and the value simply acquired by subtraction added by 24 hours is stored as the operation result. When the operation result becomes "0" (0:0:0), the zero flag turns ON.

FNC250-FNC269 Data Table Operation

Show 24 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 7 steps TSUB · FNC180 Alternate Instructions · FNC181-FNC189 Others · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input FNC163 · FNC220-FNC249 Data Comparison · (hour) · (hour) · (hour) · +1 (minute) · +1 (minute) · +1 (minute) · +2 (second) · +2 (second) · +2 (second) · FNC270-FNC276 Ex-Device
Page 572 of the Mitsubishi Electronics MELSEC FX3S user manual — When the operation result is smaller than "00:00:00"
Page 572 · click to enlarge
Page 572

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

21 Real Time Clock Control – FNC160 to FNC169

21.4 FNC163 – TSUB / RTC Data Subtraction

Cautions

1. Number of occupied devices

Three devices are occupied by , and respectively. Make sure that these devices are not used in other controls for the machine.

S 1 S 2 D

2. When utilizing the time (hour, minute, and second) of the built-in PLC real time clock Read the values of special data registers using the TRD (FNC166) instruction, and then specify those word devices as the operands.

Program example

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 572)
Fig. 536 · Program example

When the operation result is smaller than "00:00:00"

Mitsubishi Electronics MELSEC FX3S — When the operation result is smaller than "00:00:00" diagram (page 572)
Fig. 537 · When the operation result is smaller than "00:00:00"
Page 573 of the Mitsubishi Electronics MELSEC FX3S user manual — 21.5 FNC164 – HTOS / Hour to Second Conversion
Page 573 · click to enlarge
Page 573

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

21 Real Time Clock Control – FNC160 to FNC169

21.5 FNC164 – HTOS / Hour to Second Conversion 21

Mitsubishi Electronics MELSEC FX3S — 21.5 FNC164 – HTOS / Hour to Second Conversion 21 diagram (page 573)
Fig. 538 · 21.5 FNC164 – HTOS / Hour to Second Conversion 21

21.5 FNC164 – HTOS / Hour to Second Conversion

This instruction converts the time data in units of "hour, minute, and second" into data in units of "second".

Head device number storing the time data (hour, minute and second) before conversion 16-bit binary

Device number storing the time data (second) after conversion 16- or 32-bit binary

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

The time data (hour, minute, and second) stored in , +1, and +2 is converted into data in units of

For example, when "4 hours 29 minutes 31 seconds" is specified, the operation is as follows:

Page 574 of the Mitsubishi Electronics MELSEC FX3S user manual — D101,D100 D13
Page 574 · click to enlarge
Page 574

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

21 Real Time Clock Control – FNC160 to FNC169

21.5 FNC164 – HTOS / Hour to Second Conversion

2. 32-bit operation (DHTOS and DHTOSP)

The time data (hour, minute, and second) stored in , +1, and +2 is converted into data in units of

S S S

"second", and stored to +1, .

D D

DHTOS S ‚ D ‚

Mitsubishi Electronics MELSEC FX3S — D D diagram (page 574)
Fig. 539

For example, when "35 hours 10 minutes 58 seconds" is specified, the operation is as follows:

Mitsubishi Electronics MELSEC FX3S — D D diagram (page 574)
Fig. 540

Error

An operation error is caused in the following case; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When the data of , + 1 or + 2 is outside the allowable range (error code: K6706)

S S S

Program example

In the program shown below, the time data read from the built-in PLC real time clock is converted into data in units of "second", and stored to D100 and D101 when X020 turns ON.

Mitsubishi Electronics MELSEC FX3S — S S S diagram (page 574)
Fig. 541

Operation

  • Clock data reading operation by TRD (FNC166) instruction
Mitsubishi Electronics MELSEC FX3S — Operation diagram (page 574)
Fig. 542 · Operation
  • Conversion operation into "second" by DHTOS (FNC164) instruction

D101,D100 D13

Command · input FNC164

Page 575 of the Mitsubishi Electronics MELSEC FX3S user manual — 21.6 FNC165 – STOH / Second to Hour Conversion
Page 575 · click to enlarge
Page 575

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

21 Real Time Clock Control – FNC160 to FNC169

21.6 FNC165 – STOH / Second to Hour Conversion 21

Mitsubishi Electronics MELSEC FX3S — 21.6 FNC165 – STOH / Second to Hour Conversion 21 diagram (page 575)
Fig. 543 · 21.6 FNC165 – STOH / Second to Hour Conversion 21

21.6 FNC165 – STOH / Second to Hour Conversion

This instruction converts the time data in units of "second" into data in units of "hour, minute, and second".

Device number storing the time data (second) before conversion 16- or 32-bit binary

Head device number storing the time data (hour, minute and second) after conversion 16-bit binary

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

The time data in units of "second" stored in is converted into data in units of "hour, minute, and second", and

stored to , +1, and +2 (hour, minute, and second).

For example, when "29,011 seconds" is specified, the operation is as follows:

Page 576 of the Mitsubishi Electronics MELSEC FX3S user manual — 40000 D1,D0
Page 576 · click to enlarge
Page 576

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

21 Real Time Clock Control – FNC160 to FNC169

21.6 FNC165 – STOH / Second to Hour Conversion

2. 32-bit operation (DSTOH and DSTOHP)

Mitsubishi Electronics MELSEC FX3S — 2. 32-bit operation (DSTOH and DSTOHP) diagram (page 576)
Fig. 544 · 2. 32-bit operation (DSTOH and DSTOHP)

The time data in units of "second" stored in +1 and is converted into data in units of "hour, minute, and

second", and stored to three devices , +1, and +2 (hour, minute, and second).

For example, when "45,325 seconds" is specified, the operation is as follows:

Error

An operation error is caused in the following case; The error flag M8067 turns ON, and the error code is store in D8067.

  • When the data of is outside the allowable range (error code: K6706)

Program example

In the program shown below, the time data in units of "second" stored in D0 and D1 is converted into data in units of "hour, minute, and second", and stored to D100, D101, and D102 when X020 turns ON.

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 576)
Fig. 545 · Program example

Operation

  • Converting the data in second into the data in hour, minute and second using STOHP instruction (when "40,000 seconds" is specified by D1 and D0)

40000 D1,D0

+1 · +2

Page 577 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 577 · click to enlarge
Page 577

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

21 Real Time Clock Control – FNC160 to FNC169

21.7 FNC166 – TRD / Read RTC data 21

21.7 FNC166 – TRD / Read RTC data

FNC160-FNC169 Real Time Clock Control

Outline

This instruction reads the clock data of the built-in PLC real time clock.

1. Instruction format

P FNC 166

Mnemonic Operation Condition 16-bit Instruction

TRD

Continuous Operation Pulse (Single) Operation

−

TRDP

2. Set data

Operand type Description Data type

Specifies the head device number storing the clock data. (Seven devices are occupied.) 16-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S 2 ‚ D

3 3 3 S 1 S 2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

FNC190-FNC199 Block Data Operation

Explanation of function and operation

1. 16-bit operation (TRD) The clock data stored in D8013 to D8019 of the built-in PLC real time clock is read in the following format, and stored

to to +6.

D D

FNC200-FNC209 Character String Control

This instruction reads the real time clock data in a PLC, and transfers it to seven data registers.

TRD D ‚

Device Item Clock data Device Item

D8018 Year 0 to 99 (lower two digits) → D 0 Year

FNC210-FNC219 Data Operation 3

D8017 Month 1 to 12 → D 1 Month

D8016 Day 1 to 31 → D 2 Day

D8015 Hour 0 to 23 → D 3 Hour

D8014 Minute 0 to 59 → D 4 Minute

D8013 Second 0 to 59 → D 5 Second

FNC250-FNC269 Data Table Operation

D8019 Day of week 0 (Sunday) to 6 (Saturday) → D 6 Day of week

Caution

1. Number of occupied devices

Seven devices are occupied by . Make sure that these devices are not used in other controls for the machine.

Show 16 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 3 steps TRD · FNC180 Alternate Instructions · Oper- · FNC181-FNC189 Others · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input FNC166 · Special data register · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 578 of the Mitsubishi Electronics MELSEC FX3S user manual — S S
Page 578 · click to enlarge
Page 578

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

21 Real Time Clock Control – FNC160 to FNC169

21.8 FNC167 – TWR / Set RTC data

21.8 FNC167 – TWR / Set RTC data

Outline

This instruction writes the clock data to the built-in PLC real time clock.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 578)
Fig. 546 · 1. Instruction format

2. Set data

Operand type Description Data type

Specifies the head device number to which the clock data is written. (Seven devices are occupied.) 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 578)
Fig. 547 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

The clock data stored in to +6 is written to D8013 to D8019 for the built-in PLC real time clock.

S S

TWRP S ‚

- D8018 (year data) can be converted into the 4-digit mode. (Refer to the program example shown later.)

Mitsubishi Electronics MELSEC FX3S — S S diagram (page 578)
Fig. 548
Mitsubishi Electronics MELSEC FX3S — S S diagram (page 578)
Fig. 549

D 10 Year 0 to 99 (lower two digits) → D8018 Year

D 11 Month 1 to 12 → D8017 Month

D 12 Day 1 to 31 → D8016 Day

D 13 Hour 0 to 23 → D8015 Hour

D 14 Minute 0 to 59 → D8014 Minute

D 15 Second o to 59 → D8013 Second

D 16 Day of week 0 (Sunday) to 6 (Saturday) → D8019 Day of week

- When TWR (FNC167) instruction is executed, the clock data of the real time clock is immediately changed.

Accordingly, transfer the clock data several minutes ahead to to +6 in advance, and then execute FNC167 instruction when the accurate time has come. - When setting the clock data (time) using this instruction, it is not necessary to control the special auxiliary relay M8015 (time stop and time setting). - If a numeric value indicating impossible date/time is set, the clock data is not changed. Set the correct clock data, and then write it. - The day of the week (D8019) is automatically corrected in accordance with the date without regard to the written numeric value.

S S

Command · input FNC167

Page 579 of the Mitsubishi Electronics MELSEC FX3S user manual — M8002 FNC 12
Page 579 · click to enlarge
Page 579

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

21 Real Time Clock Control – FNC160 to FNC169

21.8 FNC167 – TWR / Set RTC data 21

Caution

FNC160-FNC169 Real Time Clock Control

1. Number of occupied devices

Seven devices are occupied by . Make sure that these devices are not used in other controls for the machine.

Program example

1. Example of setting the clock data (time) In the program example shown below, the real time clock is set (to 15:20:30 on Tuesday, April 25, 2001).

K1 D0 FNC 12

Year (lower two digits)

MOV

D1 K4 FNC 12

MOV

D2 K25 FNC 12

MOV

D3 K15 FNC 12

MOV

D4 K20 FNC 12

MOV

D5 K30 FNC 12

MOV

D6 K2 FNC 12

FNC190-FNC199 Block Data Operation

MOV

The current value of the built-in real time clock is updated.

TWR D0

M8017 X001 The current value is corrected by ±30 seconds.

FNC200-FNC209 Character String Control

  • The shaded area indicates the set value of each item.
  • When setting the time, it is recommended to set the time to several minutes ahead in advance, and then set X000 to ON when the accurate time is reached. The set time is then immediately written to the real time clock, and the clock data is updated.
  • Every time X001 is set to ON, the current time can be corrected by ±30 seconds.

FNC210-FNC219 Data Operation 3

  • When handling the year in the 4-digit mode, add the following program. D8018 will specify the 4-digit year mode in the second scan and later after the PLC mode is changed to RUN.

M8002 FNC 12

MOV K2000 D8018 Initial pulse

- A PLC is normally operating in the 2-digit year mode. When the above instruction is executed and "K2000 (fixed value)" is transferred to D8018 (year) in only one operation cycle after the PLC mode was changed to RUN, the year mode is switched to the 4-digit mode. - Execute this program every time the PLC mode is changed to RUN. Even if "K2000" is transferred, only the display format is changed to the 4-digit year mode. The current date and time are not affected. - In the 4-digit year mode, the set values "80 to 99" correspond to "1980 to 1999", and "00 to 79" correspond to "2000 to 2079". Examples: "80" indicates 1980. "99" indicates 1999. "00" indicates 2000. "79" indicates 2079.

FNC250-FNC269 Data Table Operation

  • When the data access unit FX-10DU-E/20DU-E/25DU-E is connected, select the 2-digit year mode. If the 4-digit year mode is selected, the year is not correctly displayed in the current version of the FX-10DU-E/20DU-E/25DU-E. Note that the clock is changed to the 2-digit year mode when the clock is set from the FX-10DU-E/20DU-E/25DU-E while the PLC is operating in the 4-digit year mode.
Show 11 more labels / short text on this page
FNC170-FNC179 External Device · FNC180 Alternate Instructions · Month · Day · Hour · FNC181-FNC189 Others · Minute · Second · Day of week · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 580 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 D 1
Page 580 · click to enlarge
Page 580

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

21 Real Time Clock Control – FNC160 to FNC169

21.9 FNC169 – HOUR / Hour Meter

21.9 FNC169 – HOUR / Hour Meter

Outline

This instruction measures the ON time of the input contact in units of hour.

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

32-bit Instruction D 13 steps DHOUR Continuous Operation

HOUR

2. Set data

Mitsubishi Electronics MELSEC FX3S — 32-bit Instruction D 13 steps DHOUR Continuous Operation diagram (page 580)
Fig. 550 · 32-bit Instruction D 13 steps DHOUR Continuous Opera…

Time after which is set to ON (unit: hour) 16- or 32-bit binary

Current value (unithour) (latched (battery backed) type data register latched (battery backed)) 16or 32-bit binary

Head device number to which alarm is output Bit

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 580)
Fig. 551 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S2 S3

S1: D .b is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available. S2: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S3: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation When the accumulated ON time of the command input reaches
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 580)
Fig. 552 · Explanation of function and operation

or exceeds the time stored in , is set to ON.

D 1 S

HOUR S ‚ D1 ‚ D2 ‚

The current value less than one hour is stored in +1 (unit: second).

: Time after which is set to ON Specify a value in units of hour.

+ 1Current value less than one hour (unit: second)

It turns ON when the current value reaches or exceeds the time specified in .

D 1 S

  • Specify a latched (battery backed) type data register as so that the current value data can be continuously used even after the PLC turns OFF. If a general type data register is used, the current value data is cleared when the power to the PLC is turned OFF or when the PLC mode switches from STOP to RUN.
  • Even after the alarm output turns ON, the measurement is continued.

To begin measuring the ON time again, clear the current value stored in and +1. When the current value is cleared, alarm output is turned OFF.

D 1 D 1

  • When the current value reaches the maximum value of 16-bit data, the measurement is stopped.

For continuing the measurement, clear the current value stored in and +1.

D 1 D 1

Mnemonic Operation Condition · 7 steps HOUR · Continuous Operation

Page 581 of the Mitsubishi Electronics MELSEC FX3S user manual — D 1 S
Page 581 · click to enlarge
Page 581

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

21 Real Time Clock Control – FNC160 to FNC169

21.9 FNC169 – HOUR / Hour Meter 21

2. 32-bit operation

FNC160-FNC169 Real Time Clock Control

input FNC169 DHOUR S ‚ D1 ‚ D2 ‚

[ +1, ]Time after which is set to ON

S S D 2

Specify the high-order side in +1, and the low-order side in .

S 1 S 1

[ +1, ]Current value in units of hour

D 1 D 1

The high-order side is stored in +1, and the low-order side is stored in .

D 1 D 1

+2Current value less than one hour (unit: second)

: Alarm output destination

It turns ON when the current value and +1 reaches or exceeds the time specified in

D 1 D 1

  • Specify a latched (battery backed) type data register as so that the current value data can be continuously used even after the PLC turns OFF. If a general data type register is used, the current value data is cleared when the power to the PLC is turned OFF or when the PLC mode switches from STOP to RUN.
  • Even after the alarm output turns ON, the measurement is continued.

When measures the ON time beginning again, clear the current value stored in to +2. When the current value is clear, alarm output is turned OFF.

D 1 D 1

  • When the current value [ +1, ] reaches the maximum value of 32-bit data, the measurement is stopped.

D 1 D 1

For continuing the measurement, clear the current value stored in to +2.

D 1 D 1

Caution

FNC190-FNC199 Block Data Operation

1. Number of occupied devices

Two (16-bit operation) or three (32-bit operation) devices are occupied by . Make sure that these devices are not used in other controls for the machine.

Program example

In the program example shown below, when the accumulated X000 ON time exceeds 300 hours, Y005 turns ON. The current value less than one hour is stored in D201 in units of second.

FNC200-FNC209 Character String Control

X000 FNC169

HOUR K300

Y005

FNC210-FNC219 Data Operation 3

S D 2

: Time after which is set to ON Specify a value in units of hour.

: Current value in units of hour

+1Current value less than one hour (unit: second)

: Alarm output destination

It turns ON when the current value reaches or exceeds the time specified in . (In this example, it turns ON when the current value becomes 300 hours.)

D 1 S

FNC250-FNC269 Data Table Operation

Show 6 more labels / short text on this page
Command · FNC170-FNC179 External Device · FNC180 Alternate Instructions · FNC181-FNC189 Others · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 582 of the Mitsubishi Electronics MELSEC FX3S user manual — 22. External Device – FNC170 to FNC179
Page 582 · click to enlarge
Page 582

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

22 External Device – FNC170 to FNC179

22. External Device – FNC170 to FNC179

FNC170 to FNC179 provide conversion instructions for gray codes used in absolute type rotary encoders and instructions dedicated to analog blocks.

Mitsubishi Electronics MELSEC FX3S — 22. External Device – FNC170 to FNC179 diagram (page 582)
Fig. 553 · 22. External Device – FNC170 to FNC179

170 GRY Decimal to Gray Code Conversion Section 22.1

171 GBIN Gray Code to Decimal Conversion Section 22.2

176 RD3A Read form Dedicated Analog Block Section 22.3

177 WR3A Write to Dedicated Analog Block Section 22.4

Page 583 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 583 · click to enlarge
Page 583

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

22 External Device – FNC170 to FNC179

22.1 FNC170 – GRY / Decimal to Gray Code Conversion 21

22.1 FNC170 – GRY / Decimal to Gray Code Conversion

FNC160-FNC169 Real Time Clock Control

Outline

This instruction converts a binary value into a gray code, and transfers it.

1. Instruction format

Mnemonic Operation Condition P FNC 170

GRY D

Continuous Operation Pulse (Single) Operation

DGRY

Continuous Operation Pulse (Single) Operation

GRYP

DGRYP

2. Set data

Operand Type Description Data Type

Conversion source data or word device storing conversion source data 16- or 32-bit binary

Word device storing data after conversion 16- or 32-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

FNC190-FNC199 Block Data Operation

3 S1 S2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

FNC200-FNC209 Character String Control

1. 16-bit operation (GRY and GRYP)

This instruction converts and transfers data from the source (binary) to the destination (gray code). FNC170

D ‚ S ‚

GRY

When is K1234 and is K3Y10

S ‚ D ‚

FNC210-FNC219 Data Operation 3

BIN 1234

0 1 0 0 1 0 1 1 0 0 1 0

Y23 Y20 Y17 Y10 GRY 1234

1 1 0 1 1 1 0 1 0 1 1 0

- can store a value from 0 to 32767.

2. 32-bit operation (DGRY and DGRYP) - A binary value can be converted into a gray code of up to 32 bits.

- can store a value from 0 to 2,147,483,647.

FNC250-FNC269 Data Table Operation

Caution

The data conversion speed depends on the scan time of the PLC.

Show 18 more labels / short text on this page
FNC170-FNC179 External Device · 16-bit Instruction · Mnemonic Operation Condition · 32-bit Instruction · 5 steps GRY · 9 steps · FNC180 Alternate Instructions · FNC181-FNC189 Others · Oper- · and Type · Unit Index Con- stant · Real Number · Charac- ter String Pointer · Command · input · b0 b15 · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 584 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 584 · click to enlarge
Page 584

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

22 External Device – FNC170 to FNC179

22.2 FNC171 – GBIN / Gray Code to Decimal Conversion

22.2 FNC171 – GBIN / Gray Code to Decimal Conversion

Outline

This instruction converts a gray code into a binary value, and transfers it.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 584)
Fig. 554 · 1. Instruction format

2. Set data

Operand Type Description Data Type

Conversion source data or word device storing conversion source data 16- or 32-bit binary

Word device storing data after conversion 16- or 32-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 584)
Fig. 555 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

1. 16-bit operation (GBIN and GBINP)

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 584)
Fig. 556 · Explanation of function and operation

input This instruction converts and transfers data from the source (gray code) to the destination (binary).

1 1 0 1 1 1 0 1 0 1 1 0

0 1 0 0 1 0 1 1 0 0 1 0

- This instruction can be used for detecting an absolute position by a gray code type encoder.

- can store a value from 0 to 32,767.

2. 32-bit operation (DGBIN and DGBINP) - A gray code can be converted into a binary value of up to 32 bits.

- can store a value from 0 to 2,147,483,647.

Caution

When an input relay (X) is specified as , the response relay will be “Scan time of PLC + Input filter constant”.

The input filter value in X000 to X017*1 can be converted using the REFF (FNC51) instruction or D8020 (filter adjustment) so that the delay caused by the filter constant is eliminated.

*1. X000 to X007 in FX3G/FX3GC PLCs

Page 585 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 585 · click to enlarge
Page 585

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

22 External Device – FNC170 to FNC179

22.3 FNC176 – RD3A / Read form Dedicated Analog Block 21

22.3 FNC176 – RD3A / Read form Dedicated Analog Block

FNC160-FNC169 Real Time Clock Control

Outline

This instruction reads an analog input value from the analog block FX0N-3A*1 or FX2N-2AD.

1. Instruction format

P FNC 176

Mnemonic Operation Condition 16-bit Instruction

RD3A

Continuous Operation Pulse (Single) Operation

RD3AP

2. Set data

Operand Type Description Data Type

- FX3G/FX3GC/FX3U/FX3UC (D, DS, DSS) PLCs: K0 to K7 - FX3UC-32MT-LT(-2) : K1 to K7

m2 ‚ Analog input channel number 16-bit binary

Word device storing the read data 16-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC190-FNC199 Block Data Operation

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

m1 ‚ 3

m2 ‚ 3

3

FNC200-FNC209 Character String Control

Explanation of function and operation

1. 16-bit operation (RD3A)

RD3A m1‚ m2‚

FNC210-FNC219 Data Operation 3

m1 ‚ : Special block number FX3G/FX3GC/FX3U/FX3UC (D, DS, DSS) PLCs : K0 to K7 FX3UC-32MT-LT(-2) : K1 to K7 (K0 indicates the built-in CC-Link/LT master.) m2 ‚ : Analog input channel number

FX0N-3A*1 : K1 (ch 1) or K2 (ch 2) FX2N-2AD : K21 (ch 1) or K22 (ch 2)

: Read data A value read from the analog block is stored.

FX 0N -3A *10 to 255 (8 bits) FX 2N -2AD : 0 to 4095 (12 bits)

*1. The FX0N-3A is available only for the FX3U and FX3UC PLCs.

FNC250-FNC269 Data Table Operation

Show 19 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 7 steps RD3A · − · FNC180 Alternate Instructions · Special block number · m1 ‚ · 16-bit binary · FNC181-FNC189 Others · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 586 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 586 · click to enlarge
Page 586

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

22 External Device – FNC170 to FNC179

22.4 FNC177 – WR3A / Write to Dedicated Analog Block

22.4 FNC177 – WR3A / Write to Dedicated Analog Block

Outline

This instruction writes a digital value to the analog block FX0N-3A*1 or FX2N-2DA.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 586)
Fig. 557 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 586)
Fig. 558 · 2. Set data

- FX3G/FX3GC/FX3U/FX3UC (D, DS, DSS) PLCs: K0 to K7 - FX3UC-32MT-LT(-2) : K1 to K7

Data to be written or word device storing data to be written 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 586)
Fig. 559 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

m1 ‚ 3

m2 ‚ 3

3

Explanation of function and operation

1. 16-bit operation (WR3A)

WR3A m1‚ m2‚

m1 ‚ : Special block number FX3G/FX3GC/FX3U/FX3UC (D, DS, DSS) PLCs : K0 to K7 FX3UC-32MT-LT(-2) : K1 to K7 (K0 indicates the built-in CC-Link/LT master.) m2 ‚ : Analog output channel number

FX 0N3A *1K1 (ch 1) FX 2N -2DA : K21 (ch 1) or K22 (ch 2)

: Data to be written Specify a value output to the analog block.

FX 0N -3A *10 to 255 (8 bits) FX 2N -2DA : 0 to 4095 (12 bits)

*1. The FX0N-3A is available only for the FX3U and FX3UC PLCs.

Command · input

Page 587 of the Mitsubishi Electronics MELSEC FX3S user manual — Instruction correspondence table
Page 587 · click to enlarge
Page 587

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

23 Introduction of Alternate Instructions – FNC180

23.1 Instruction correspondence table 21

FNC160-FNC169 Real Time Clock Control

23. Introduction of Alternate Instructions – FNC180

23.1 Instruction correspondence table

Outline

EXTR instruction is provided for FX2N/FX2NC PLCs. For FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs equipped with the built-in inverter communication function, dedicated instructions shown below are provided. (EXTR instruction is not provided.)

Instruction correspondence table

FX2N/FX2NC FX3S/FX3G/FX3GC/FX3U/FX3UC Description

EXTR K10 → FNC270 IVCK Inverter status check

EXTR K11 → FNC271 IVDR Inverter drive

EXTR K12 → FNC272 IVRD Inverter parameter read

EXTR K13 → FNC273 IVWR Inverter parameter write

– – FNC274 IVBWR*1 Inverter parameter block write

– – FNC275 IVMC Inverter multi command

*1. This function is supported only in FX3U/FX3UC PLCs.

→ For details, refer to the Data Communication Edition manual.

FNC190-FNC199 Block Data Operation

FNC200-FNC209 Character String Control

FNC210-FNC219 Data Operation 3

FNC250-FNC269 Data Table Operation

Show 5 more labels / short text on this page
FNC170-FNC179 External Device · FNC180 Alternate Instructions · FNC181-FNC189 Others · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 588 of the Mitsubishi Electronics MELSEC FX3S user manual — 24. Others – FNC181 to FNC189
Page 588 · click to enlarge
Page 588

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

24 Others – FNC181 to FNC189

24. Others – FNC181 to FNC189

FNC181 to FNC189 provide instructions for generating random numbers, executing CRC data operations, and processing data in high-speed counter operations.

Mitsubishi Electronics MELSEC FX3S — 24. Others – FNC181 to FNC189 diagram (page 588)
Fig. 560 · 24. Others – FNC181 to FNC189
Page 589 of the Mitsubishi Electronics MELSEC FX3S user manual — S D
Page 589 · click to enlarge
Page 589

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

24 Others – FNC181 to FNC189

24.1 FNC182 – COMRD / Read Device Comment Data 21

24.1 FNC182 – COMRD / Read Device Comment Data

FNC160-FNC169 Real Time Clock Control

Outline

This instruction reads the comment data for registered devices written to the PLC by programming software such as GX Works2.

1. Instruction format

P FNC 182

Mnemonic Operation Condition 16-bit Instruction

COMRD − −

Continuous Operation Pulse (Single) Operation

COMRDP

2. Set data

Operand Type Description Data Type

Device number for which comment to be read is registered Device name

Head device number storing read comment Character string

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

FNC190-FNC199 Block Data Operation

Explanation of function and operation

1. 16-bit operation (COMRD and COMRDP)

1. The comment registered for device is read, and stored in ASCII code in and later.

S D

FNC200-FNC209 Character String Control

input FNC182 COMRDP S ‚ D ‚

b15 b8 b7 b0

ASCII code of 2nd character

ASCII code of 1st character

ASCII code of 4th character

ASCII code of 3rd character ASCII code of 5th character

Comment of device specified in 16 characters can be stored.

ASCII code of 6th character

FNC210-FNC219 Data Operation 3

ASCII code of 8th character ASCII code of 7th character

ASCII code of 16th character ASCII code of 14th character ASCII code of 13th character

ASCII code of 15th character 0000H

- When M8091 is OFF, "0000H" is written to the device following the final character. - When M8091 is ON, the device following the final character does not change.

For example, when the comment of is "LineNo.1Start", it is stored in and later as shown below.

S D

b15 b8 b7 b0

69H(i) 65H(e) 4CH(L) 6EH(n) 4EH(N) 31H(1) 2EH(.)

FNC250-FNC269 Data Table Operation

LineNo.1Start

74H(t) 72H(r) 53H(S) 61H(a) 74H(t) 20H(space) 20H(space) +7 +8 0000H

- When M8091 is OFF, "0000H" is written to the next device following the final character. - When M8091 is ON, the device following the final character does not change.

Show 23 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 5 steps COMRD · FNC180 Alternate Instructions · FNC181-FNC189 Others · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · +1 +2 · +3 · +7 +8 · FNC220-FNC249 Data Comparison · +1 +2 · Comment of · 6FH(o) · +3 · +4 +5 +6 · 20H(space) · FNC270-FNC276 Ex-Device
Page 590 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 590 · click to enlarge
Page 590

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

24 Others – FNC181 to FNC189

24.1 FNC182 – COMRD / Read Device Comment Data

2. The final device of is as follows depending on the ON/OFF status of M8091.
Mitsubishi Electronics MELSEC FX3S — 24.1 FNC182 – COMRD / Read Device Comment Data diagram (page 590)
Fig. 561 · 24.1 FNC182 – COMRD / Read Device Comment Data

M8091 = OFF When M8091 is OFF, "0000H" is written to in the device following the final character.

M8091 = ON When M8091 is ON, the device following the final character does not change.

Related device

M8091 Output character number selector signal Refer to the above explanation.

Caution

  • Specify a device number in device for which a comment is registered in the PLC.

If a comment is not registered for the device , "20H" (space) is stored in and later for the number of characters in the comment (16 half-width characters).

S D

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When a comment is not registered for the device (error code: K6706)
  • When the range of points used from for the comment exceeds the corresponding device range (error code: K6706)

Program example

In the program shown below, the comment "Target Line A" registered to D100 is stored in ASCII code in D0 and later when X010 is set to ON. And since M8091 is OFF "0000H" is written to the device following the last character.

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 590)
Fig. 562 · Program example

Device Name Description

Page 591 of the Mitsubishi Electronics MELSEC FX3S user manual — MUL D12 D2 D10
Page 591 · click to enlarge
Page 591

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

24 Others – FNC181 to FNC189

24.2 FNC184 – RND / Random Number Generation 21

24.2 FNC184 – RND / Random Number Generation

FNC160-FNC169 Real Time Clock Control

Outline

This instruction generates random numbers.

1. Instruction format

P FNC 184

Mnemonic Operation Condition 16-bit Instruction

RND

Continuous Operation Pulse (Single) Operation

RNDP

2. Set data

Operand Type Description Data Type

Head device number storing a random number 16-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

Explanation of function and operation

1. 16-bit operation (RND and RNDP) This instruction generates a pseudo-random number ranging from 0 to 32767, and stores it as a random number to

FNC190-FNC199 Block Data Operation

. In the pseudo-random number sequence, the source value of a random number is calculated at every time, and this instruction calculates a pseudo-random number using the source value.

FNC200-FNC209 Character String Control

RND

Pseudo-random number calculation equation:

(D8311, D8310) = (D8311, D8310) *1 × 1103515245 + 12345 (1)

= “([D8311, D8310]>>16)&00007FFFh”

*1. To (D8311, D8310), write a non-negative value (0 to 2,147,483,647) only once when the PLC mode switches from STOP to RUN. [K1 is written to (D8311, D8310) as the initial value when the power is restored.]

FNC210-FNC219 Data Operation 3

Program example

In the program example shown below, a random number is stored to D100 every time X010 turns ON. When the PLC mode switches from STOP to RUN, the time data converted into seconds and added by the value “(Year + Month) × Day” is written to D8311 and D8310.

M8002 FNC166

TRD D0

The clock data is read.

DHTOS D14 D3

Data in hour, minute and second → Data in second

ADD D10 D1 D0

FNC250-FNC269 Data Table Operation

The data in second is added by the value “(Year + Month) × Day”, and written to D8311 and D8310. FNC 23

MUL D12 D2 D10

DADD D8310 D12 D14

X010 FNC184

RNDP D100

END

Show 16 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 3 steps RND · ⎯ ⎯ · FNC180 Alternate Instructions · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · FNC181-FNC189 Others · Command · input · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 592 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 592 · click to enlarge
Page 592

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

24 Others – FNC181 to FNC189

24.3 FNC186 – DUTY / Timing Pulse Generation

24.3 FNC186 – DUTY / Timing Pulse Generation

Outline

This instruction generates the timing signal whose one cycle corresponds to the specified number of operation cycles.

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

DUTY −

2. Set data

Mitsubishi Electronics MELSEC FX3S — DUTY − diagram (page 592)
Fig. 563

n1 Number of scans (operation cycles) to remain ON [n1 > 0]

16-bit binary n2 Number of scans (operation cycles) to remain OFF [n2 > 0]

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 592)
Fig. 564 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S: Specify either one among M8330 to M8334.

Explanation of function and operation

1. 16-bit operation (DUTY)

1. The timing clock output destination is set to ON and OFF with the ON duration for "n1" scans and OFF duration for "n2" scans.
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 592)
Fig. 565 · Explanation of function and operation
2. Specify either one among M8330 to M8334 as the timing clock output destination device .
3. The counted number of scans is stored among D8330 to D8334 in accordance with the timing clock output

destination device . The counted number of scans stored among D8330 to D8334 is reset when the counted value reaches "n1+n2" or when the command input (instruction) is set to ON.

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 592)
Fig. 566 · Explanation of function and operation
Show 4 more labels / short text on this page
Mnemonic Operation Condition · 32-bit Instruction · 7 steps DUTY · Continuous Operation
Page 593 of the Mitsubishi Electronics MELSEC FX3S user manual — ON X000
Page 593 · click to enlarge
Page 593

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

24 Others – FNC181 to FNC189

24.3 FNC186 – DUTY / Timing Pulse Generation 21

4. When the command input is set to ON, the operation is started. The timing clock output destination device is set to ON or OFF by the END instruction. Even if the command input is set to OFF, the operation is not stopped. In the STOP mode, the operation is suspended. When the power to the PLC is turned OFF, the operation is stopped.

FNC160-FNC169 Real Time Clock Control

5. When "n1" and "n2" are set to "0", the device is set to the following status:

n1/n2 status ON/OFF status

n1 = 0, n2 ≥ 0 Fixed to OFF

n1 > 0, n2 = 0 Fixed to ON

Related devices

M8330 Timing clock output 1

M8331 Timing clock output 2

M8332 Timing clock output 3

Timing clock output in the DUTY (FNC186) instruction

M8333 Timing clock output 4

M8334 Timing clock output 5

D8330 Counted number of scans for timing clock output 1 Counted number of scans for timing clock output 1 in the DUTY (FNC186) instruction

D8331 Counted number of scans for timing clock output 2 Counted number of scans for timing clock output 2 in the DUTY (FNC186) instruction

D8332 Counted number of scans for timing clock output 3 Counted number of scans for timing clock output 3 in the DUTY (FNC186) instruction

D8333 Counted number of scans for timing clock output 4 Counted number of scans for timing clock output 4 in the DUTY (FNC186) instruction

FNC190-FNC199 Block Data Operation

D8334 Counted number of scans for timing clock output 5 Counted number of scans for timing clock output 5 in the DUTY (FNC186) instruction

Caution

  • The DUTY (FNC186) instruction can be used up to 5 times (points).

FNC200-FNC209 Character String Control

It is not permitted, however, to use the same timing clock output destination device for two or more DUTY (FNC186) instructions.

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

FNC210-FNC219 Data Operation 3

  • When "n1" and/or "n2" is less than "0" (error code: K6706)
  • When any device other than M8330 to M8334 is set to (error code: K6705)

Program example

In the program shown below, when X000 is set to ON, M8330 is set to ON for 1 scan and OFF for 3 scans.

X000 FNC186

DUTY K3 M8330

K1

END

FNC250-FNC269 Data Table Operation

ON X000

OFF

M8330

OFF ON

1 scan 3 scans

0 1 2 3

0 1 D8330 current value

Show 6 more labels / short text on this page
FNC170-FNC179 External Device · FNC180 Alternate Instructions · Device Name Description · FNC181-FNC189 Others · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 594 of the Mitsubishi Electronics MELSEC FX3S user manual — S D
Page 594 · click to enlarge
Page 594

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

24 Others – FNC181 to FNC189

24.4 FNC188 – CRC / Cyclic Redundancy Check

24.4 FNC188 – CRC / Cyclic Redundancy Check

Outline

This CRC instruction calculates the CRC (cyclic redundancy check) value which is an error check method used in communication. In addition to CRC value, there are other error check methods such as parity check and sum check. For obtaining the horizontal parity value and sum check value, CCD (FNC 84) instruction is available.

For the generation of CRC value (CRC-16), the CRC instruction uses “X16 + X15 + X2 + 1” as a polynomial and uses "FFFFH" as a default value.

→ For CCD instruction (check code), refer to Section 16.5.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 594)
Fig. 567 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 594)
Fig. 568 · 2. Set data

Head device number storing data for which the CRC value is generated

16-bit binary Device number storing the generated CRC value

n Number of 8-bit (1-byte) data for which the CRC value is generated or the device number storing the number of data

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 594)
Fig. 569 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S 3

S S S 3

S: Make sure to specify four digits (K4 {{{) when specifying the digits of a bit device.

Explanation of function and operation

1. 16-bit operation

CRC value is generated for “n” 8-bit data (unit: byte) starting from a device specified in , and stored to . The 8-bit conversion mode and 16-bit conversion mode are available in this instruction, and the mode can be switched by turning ON or OFF M8161. For the operation in each mode, refer to the following pages.

S D

D ‚ S ‚

Command · input · CRC n

Page 595 of the Mitsubishi Electronics MELSEC FX3S user manual — D ‚ S ‚
Page 595 · click to enlarge
Page 595

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

24 Others – FNC181 to FNC189

24.4 FNC188 – CRC / Cyclic Redundancy Check 21

16-bit conversion mode (while M8161 is OFF) In this mode, the operation is executed for high-order 8 bits (1 byte) and low-order 8 bits (1 byte) of a device specified

FNC160-FNC169 Real Time Clock Control

in .

The operation result is stored to one 16-bit device specified in .

M8161 M8000

D ‚ S ‚

Example= D100

= D0 n = 6

Contents of target data

8 bits 16 bits

Low-order byte Low-order bits of D100 01H 0301H High-order byte High-order bits of D100 03H

Low-order byte Low-order bits of D101 03H 0203H High-order byte High-order bits of D101 02H

Device storing data for which the CRC value is generated

Low-order byte Low-order bits of D102 00H 1400H High-order byte High-order bits of D102 14H

Low-order byte Low-order bits of D0 E4H

FNC190-FNC199 Block Data Operation

Device storing the generated CRC value

41E4H High-order byte High-order bits of D0 41H

8-bit conversion mode (while M8161 is ON)

In this mode, the operation is executed only for low-order 8 bits (low-order 1 byte) of a device specified by .

With regard to the operation result, low-order 8 bits (1 byte) are stored to a device specified by , and high-order

8 bits (1 byte) are stored to a device specified by +1.

FNC200-FNC209 Character String Control

M8161 M8000

8-bit conversion mode Command

D ‚ S ‚

FNC210-FNC219 Data Operation 3

Example= D100

= D0 n = 6

Device Contents of target data

Low-order byte Low-order bits of D100 01H

+1 Low-order byte Low-order bits of D101 03H

+2 Low-order byte Low-order bits of D102 03H

Device storing data for which the CRC value is generated

+3 Low-order byte Low-order bits of D103 02H

+4 Low-order byte Low-order bits of D104 00H

+5 Low-order byte Low-order bits of D105 14H

FNC250-FNC269 Data Table Operation

+n-1 Low-order byte –

Low-order byte Low-order bits of D0 E4H

Device storing the generated CRC value

+1 Low-order byte Low-order bits of D1 41H

Show 17 more labels / short text on this page
16-bit conversion mode · Command · FNC170-FNC179 External Device · input · CRC n · FNC180 Alternate Instructions · Device · +1 · FNC181-FNC189 Others · +2 · Low-order byte · +n/2-1 · – High-order byte · input · CRC n · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 596 of the Mitsubishi Electronics MELSEC FX3S user manual — S D
Page 596 · click to enlarge
Page 596

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

24 Others – FNC181 to FNC189

24.4 FNC188 – CRC / Cyclic Redundancy Check

2. Related device

M8161*1 ON CRC instruction operates in the 8-bit mode.

OFF CRC instruction operates in the 16-bit mode.

*1. Cleared when the PLC mode is changed from RUN to STOP.

Caution

In this instruction, “X16 + X15 + X2 + 1” is used as a polynomial for generating the CRC value (CRC-16). There are many other standard polynomials for generating the CRC value. Note that the CRC value completely differs if an adopted polynomial is different.

Reference: Major polynomials for generating the CRC value

Mitsubishi Electronics MELSEC FX3S — Reference: Major polynomials for generating the CRC value diagram (page 596)
Fig. 570 · Reference: Major polynomials for generating the CRC…

CRC-12 X12 + x11 + X3 + X2 + X + 1

CRC-16 X16 + X15 + X2 + 1

CRC-32 X32 + X26 + X23 + X22 + X16 + X12 + X11 + X10 + X8 + X7 + X5 + X4 + X2 + X + 1

CRC-CCITT X16 + X12 + X5 + 1

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When any digits other than 4 digits are specified as or in digit specification of bit device (error code: K6706)

S D

  • When n is outside the allowable range (1 to 256) (error code: K6706)
  • When a device specified by +n-1 or +1 is outside the allowable range (error code: K6706)

S D

Related device Description

Page 597 of the Mitsubishi Electronics MELSEC FX3S user manual — 24.4 FNC188 – CRC / Cyclic Redundancy Check 21
Page 597 · click to enlarge
Page 597

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

24 Others – FNC181 to FNC189

24.4 FNC188 – CRC / Cyclic Redundancy Check 21

Mitsubishi Electronics MELSEC FX3S — 24.4 FNC188 – CRC / Cyclic Redundancy Check 21 diagram (page 597)
Fig. 571 · 24.4 FNC188 – CRC / Cyclic Redundancy Check 21

In the program example shown below, the CRC value of the ASCII code “0123456” stored in D100 to D106 is generated and stored to D0 when M0 turns ON.

Device storing data for which CRC value is generated

Device storing generated CRC value D0 2ACFH Low-order byte CFH

Device storing data for which the CRC value is generated

Page 598 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 598 · click to enlarge
Page 598

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

24 Others – FNC181 to FNC189

24.5 FNC189 – HCMOV / High-Speed Counter Move

24.5 FNC189 – HCMOV / High-Speed Counter Move

Outline

This instruction updates the current value of a specified high-speed counter or ring counter. The function of this instruction varies depending on the PLC version.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 598)
Fig. 572 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 598)
Fig. 573 · 2. Set data

Device number of high-speed counter or ring counter*1 handled as transfer source

n Specification to clear the current value of high-speed counter or ring counter*1 (transfer source) after transfer [clear (K1), no clear (K0)] 16-bit binary

*1. Ring counters (D8099 and D8398) cannot be specified in FX3UC PLCs before Ver. 2.20.

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 598)
Fig. 574 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S: Only high-speed counters (C235 to C255) and ring counters (D8099 and D8398) can be specified.

Explanation of function and operation

1. 32-bit operation (DHCMOV)

FNC189 DHCMOV n S D

  • The current value of a high-speed counter or ring counter specified in is transferred to [ +1, ].
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 598)
Fig. 575 · Explanation of function and operation

High-speed counter C235 to C255 Current value of high-speed counter → [ +1, ]

D8398 Current value of [D8399, D8398] → [ +1, ]

  • After transfer, the current value of the high-speed counter or ring counter is processed as shown in the table below depending on the set value of "n":

"n" set value Operation

K0 (H0) Does not clear the current value (no processing).

K1 (H1) Clears the current value to "0".

Command · input

Page 599 of the Mitsubishi Electronics MELSEC FX3S user manual — IRET
Page 599 · click to enlarge
Page 599

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

24 Others – FNC181 to FNC189

24.5 FNC189 – HCMOV / High-Speed Counter Move 21

2. High-speed counter current value update timing and the effect of DHCMOV instruction

FNC160-FNC169 Real Time Clock Control

1. High-speed counter current value update timing When a pulse is input to an input terminal for a high-speed counter (C235 to C255), the high-speed counter executes up-counting or down-counting. If the current value of a high-speed counter is handled in an applied instruction such as the normal MOV instruction, the current value is updated at the timing shown in the table below. As a result, it is affected by the program scan time.

Current value update timing

Hardware counter When OUT instruction for the counter is executed

Software counter Every time a pulse is input

By using DHCMOV instruction, the current value can be updated and transferred when it is executed.

2. Effect of DHCMOV instruction
  • By using both input interrupt and DHCMOV instruction, the current value of a high-speed counter can be received at the rising edge or falling edge of an external input (at reception of input interrupt).

→ Refer to the Program example 2.

  • When DHCMOV instruction is used just before a comparison instruction (CMP, ZCP or comparison contact instruction), the latest value of a high-speed counter is used in comparison. The following points must be kept in mind when using the DHCMOV command. - When the current value of a high-speed counter is compared using CMP, ZCP or comparison contact instruction (not using a designated high-speed counter comparison instruction), a hardware counter does not change into a software counter. → For the condition in which a hardware counter is handled as a software counter, refer to Subsection 4.8.9.

- When the number of high-speed software counter comparison instructions is reduced, the total frequency limitation is decreased.

→ For the limitation in software counters by the total frequency, refer to Subsection 4.8.10. - When it is necessary to execute comparison and change an output contact (Y) as soon as the current value of a high-speed counter changes, use a designated high-speed counter comparison instruction (HSCS, HSCR or HSZ). - DHCMOV instruction can be used as many times as necessary.

FNC190-FNC199 Block Data Operation

Cautions

When programming DHCMOV instruction in an input interrupt program, the following points should be observed. For assignment of pointers for input interrupt and inputs, refer to the table shown in 5) below.

FNC200-FNC209 Character String Control

1. Program EI (FNC 04) and FEND (FNC 06) instructions in the main program. They are necessary to execute an input interrupt program.

→ For EI (FNC 04) and FEND (FNC 06) instructions, refer to Section 8.5 and Section 8.7.

2. When programming DHCMOV instruction in the 1st line in an input interrupt program, make sure to use the pattern program shown below. Make sure to use the command contact M8394. Do not add, change, or delete this pattern program when writing during RUN. Interrupt programs may not operate normally.

FNC210-FNC219 Data Operation 3

I Pattern program for using the DHCMOV instruction in an interrupt program

M8394

S D

Program to be processed as input interrupt

IRET

FNC250-FNC269 Data Table Operation

Show 6 more labels / short text on this page
FNC170-FNC179 External Device · FNC180 Alternate Instructions · FNC181-FNC189 Others · n FNC189 DHCMOV · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 600 of the Mitsubishi Electronics MELSEC FX3S user manual — S D D
Page 600 · click to enlarge
Page 600

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

24 Others – FNC181 to FNC189

24.5 FNC189 – HCMOV / High-Speed Counter Move

3. If two or more DHCMOV instructions are used in one input interrupt program, only the first instruction (just after the interrupt pointer) is executed when the interrupt is generated. The rest of the interrupt, including additional DHCMOV instructions, is executed according to normal interrupt processing. Do not use M8394 as the command contact for the DHCMOV instructions following the first.
Mitsubishi Electronics MELSEC FX3S — 24.5 FNC189 – HCMOV / High-Speed Counter Move diagram (page 600)
Fig. 576 · 24.5 FNC189 – HCMOV / High-Speed Counter Move

When the input X003 turns from OFF to ON (that is, when input interrupt is accepted): → [ +1, ]

When this instruction is executed in interrupt program: ' → [ ' +1, ' ]

4. It is not permitted to use DHCMOV instruction for the same counter in two or more input interrupt programs.
Mitsubishi Electronics MELSEC FX3S — 24.5 FNC189 – HCMOV / High-Speed Counter Move diagram (page 600)
Fig. 577 · 24.5 FNC189 – HCMOV / High-Speed Counter Move
5. While input interrupts are disabled by the interrupt disable flags (shown in the table below), DHCMOV instructions are not executed when they are placed inside a corresponding interrupt.
Mitsubishi Electronics MELSEC FX3S — 24.5 FNC189 – HCMOV / High-Speed Counter Move diagram (page 600)
Fig. 578 · 24.5 FNC189 – HCMOV / High-Speed Counter Move

Interrupt disable flag Corresponding interrupt pointer Input number corresponding to interrupt pointer

*1.Cleared when the PLC mode is changed from RUN to STOP.

6. If an input interrupt is generated while input interrupts are disabled by something other than the interrupt disable flags M8050 to M8055 (after execution of DI instruction and before execution of EI instruction), DHCMOV instruction is immediately executed, but execution of the interrupt program is held. The interrupt program will be executed after EI instruction is executed and interrupts are enabled.

Function change depending on the version

The function of FNC189 instruction changes depending on the version as shown in the table below.

Mitsubishi Electronics MELSEC FX3S — Function change depending on the version diagram (page 600)
Fig. 579 · Function change depending on the version

later Target device Ring counter (D8099 and D8398) can be specified in .

Error

An operation error occurs in the following case; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When a device specified in or [ +1, ] is outside the allowable range (error code: K6705)

S D D

Page 601 of the Mitsubishi Electronics MELSEC FX3S user manual — IRET
Page 601 · click to enlarge
Page 601

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

24 Others – FNC181 to FNC189

24.5 FNC189 – HCMOV / High-Speed Counter Move 21

Program examples

FNC160-FNC169 Real Time Clock Control

1. Program example 1 In the program example below, the current value of the high-speed counter C235 is compared in each operation cycle, and then the output Y000 is set to ON if the current value is "K500" or more (when the current value of C235 is not cleared).

The current value of C235 is transferred to D1 and D0. (The current value of C235 is not cleared.)

M8000

D0 K0* 1 FNC189 DHCMOV C235

Y000 K500 FNC238 DAND>= D0

In the case of "(D1, D0) ≥ K500", Y000 is set to ON.

END

*1. K0: The current value of the high-speed counter is not cleared when DHCMOV instruction is executed. K1: The current value of the high-speed counter is cleared when DHCMOV instruction is executed.

2. Program example 2 In the program example shown below, the current value of C235 is transferred to D201 and D200, and the current value of C235 is cleared when X001 turns from OFF to ON.

EI

FEND

FNC190-FNC199 Block Data Operation

M8394

D200 K1 *2 FNC189 DHCMOV C235

‚ When X001 turns from OFF to ON, the

interrupt program from I101 to IRET is executed. ‚ The current value of C235 is

transferred to D201 and D200. (The current value of C235 is cleared to “0”.)

IRET

FNC200-FNC209 Character String Control

*2. K0: The current value of the high-speed counter is not cleared when DHCMOV instruction is executed. K1: The current value of the high-speed counter is cleared when DHCMOV instruction is executed.

FNC210-FNC219 Data Operation 3

FNC250-FNC269 Data Table Operation

Show 5 more labels / short text on this page
FNC170-FNC179 External Device · FNC180 Alternate Instructions · FNC181-FNC189 Others · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 602 of the Mitsubishi Electronics MELSEC FX3S user manual — 25. Block Data Operation – FNC190 to FNC199
Page 602 · click to enlarge
Page 602

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

25 Block Data Operation – FNC190 to FNC199

25. Block Data Operation – FNC190 to FNC199

FNC190 to FNC199 provide instructions for adding, subtracting and comparing block data.

Mitsubishi Electronics MELSEC FX3S — 25. Block Data Operation – FNC190 to FNC199 diagram (page 602)
Fig. 580 · 25. Block Data Operation – FNC190 to FNC199

n D S2 S1 BKCMP= S1 S2

n D S2 S1 BKCMP> S1 S2

n D S2 S1 BKCMP< S1 S2

n D S2 S1 BKCMP S1 S2

n D S2 S1 BKCMP

n D S2 S1 BKCMP>= S1 S2

Page 603 of the Mitsubishi Electronics MELSEC FX3S user manual — 25.1 FNC192 – BK+ / Block Data Addition 21
Page 603 · click to enlarge
Page 603

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

25 Block Data Operation – FNC190 to FNC199

25.1 FNC192 – BK+ / Block Data Addition 21

Mitsubishi Electronics MELSEC FX3S — 25.1 FNC192 – BK+ / Block Data Addition 21 diagram (page 603)
Fig. 581 · 25.1 FNC192 – BK+ / Block Data Addition 21

16- or 32-bit binary Added constant or head device number storing addition data

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

BK+ S1 ‚ S2 ‚ n D ‚

1. "n" 16-bit binary data starting from are added to "n" 16-bit binary data starting from , and the

operation result is stored in "n" points starting from .

2. A (16-bit) constant from -32768 to +32767 can be directly specified in .
Page 604 of the Mitsubishi Electronics MELSEC FX3S user manual — K2,147,483,647(H7FFFFFFF) + K2(H00000002) → K-2,147,483,647(H80000001)
Page 604 · click to enlarge
Page 604

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

25 Block Data Operation – FNC190 to FNC199

25.1 FNC192 – BK+ / Block Data Addition

2. 32-bit operation (DBK+ and DBK+P)

Mitsubishi Electronics MELSEC FX3S — 2. 32-bit operation (DBK+ and DBK+P) diagram (page 604)
Fig. 582 · 2. 32-bit operation (DBK+ and DBK+P)

DBK+P S1 ‚ S2 ‚ n D ‚

1. "2n" 32-bit binary data starting from [ +1, ] are added to "2n" 32-bit binary data starting from

[ +1, ], and the operation result is stored in "2n" points starting from [ +1, ].

2. A (32-bit) constant from -2,147,483,648 to +2,147,483,647 can be directly specified in [ +1, ].

Related instruction

BK- (FNC193) Subtracts binary block data.

Caution

  • When underflow or overflow occurs in the operation result, the following processing is executed. At this time, the carry flag does not turn ON. - In the case of 16-bit operation

K32767(H7FFF) + K2(H0002) → K-32767(H8001)

K-32768(H8000) + K-2(HFFFE) → K32766(H7FFE)

- In the case of 32-bit operation

K2,147,483,647(H7FFFFFFF) + K2(H00000002) → K-2,147,483,647(H80000001)

K-2,147,483,648(H80000000) + K-2(HFFFFFFFE) → K2,147,483,646(H7FFFFFFE)

  • Note that the 32-bit value [n+1, n] is valid when D or R is specified as "n" in a 32-bit instruction. In the case of "DBK+ D0 D100 D200 R0", "n" is [R1, R0].

Instruction Description

Page 605 of the Mitsubishi Electronics MELSEC FX3S user manual — 3520 5432 D101 D102 D103
Page 605 · click to enlarge
Page 605

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

25 Block Data Operation – FNC190 to FNC199

25.1 FNC192 – BK+ / Block Data Addition 21

Errors

FNC160-FNC169 Real Time Clock Control

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When "n" ("2n" in 32-bit operation) devices starting from , , and/or exceed the corresponding device range (error code: K6706)

S 1 S 2 D

  • When "n" ("2n" in 32-bit operation) devices starting from overlap "n" ("2n" in 32-bit operation) devices
starting from (error codeK6706)
  • When "n" ("2n" in 32-bit operation) devices starting from overlap "n" ("2n" in 32-bit operation) devices
starting from (error codeK6706)

Program example

In the program shown below, the specified number of data stored in D150 to D0 are added to the specified number of data stored in D100 to D0 when X020 is set to ON, and the operation result is stored in D200 and later.

X020 FNC192

BK+ D100 D150 D200

D0 When D0 is "4"

END

b15 b0 1234 2032

b15 b0 8023 9853

3520 5432 D101 D102 D103

+

-1000 -3252 D151 D152 D153

2520 2180 D201 D202 D203

FNC190-FNC199 Block Data Operation

FNC200-FNC209 Character String Control

FNC210-FNC219 Data Operation 3

FNC250-FNC269 Data Table Operation

Show 7 more labels / short text on this page
FNC170-FNC179 External Device · FNC180 Alternate Instructions · FNC181-FNC189 Others · b15 b0 · 6789 7821 · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 606 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 606 · click to enlarge
Page 606

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

25 Block Data Operation – FNC190 to FNC199

25.2 NFC193 – BK– / Block Data Subtraction

25.2 NFC193 – BK– / Block Data Subtraction

Outline

This instruction subtracts binary block data.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 606)
Fig. 583 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 606)
Fig. 584 · 2. Set data

16- or 32-bit binary Subtracted constant or head device number storing subtraction data

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 606)
Fig. 585 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 16-bit operation (BKand BK-P)

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 606)
Fig. 586 · Explanation of function and operation

BK-P S1 ‚ S2 ‚ n D ‚

1. "n" 16-bit binary data starting from are subtracted from "n" 16-bit binary data starting from , and the

operation result is stored in "n" points starting from .

2. A (16-bit) constant from -32768 to +32767 can be directly specified in .
Page 607 of the Mitsubishi Electronics MELSEC FX3S user manual — K-2,147,483,648(H80000000) – K2(H00000002) → K2,147,483,646(H7FFFFFFE)
Page 607 · click to enlarge
Page 607

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

25 Block Data Operation – FNC190 to FNC199

25.2 NFC193 – BK– / Block Data Subtraction 21

2. 32-bit operation (DBKand DBK-P)

FNC160-FNC169 Real Time Clock Control

DBK-P S1 ‚ S2 ‚ n D ‚

1. "2n" 32-bit binary data starting from [ +1, ] are subtracted from "2n" 32-bit binary data starting from

S 2 S 2

[ +1, ], and the operation result is stored in "2n" points starting from [ +1, ].

S 1 S 1 D D

K8765 K8888

K1234 K5678

S1‚ S1‚ S1‚

[ +3, +2] [ +5, +4]

[ +3, +2] [ +5, +4]

S 1 ‚ S 1 ‚

K9325

"n" points −

K9876

[ +2n-3, +2n-4] [ +2n-1, +2n-2]

K50000

[ +2n-3, +2n-4] [ +2n-1, +2n-2]

K4321

S 1 ‚ S 1 ‚

K4352

S 2 ‚ S 2 ‚

K4000

K7531 K3210

[ +3, +2] [ +5, +4]

D ‚ D ‚

D ‚ D ‚

K-551

[ +2n-3, +2n-4] [ +2n-1, +2n-2]

K45679

K352

2. A (32-bit) constant from -2,147,483,648 to +2,147,483,647 can be directly specified in [ +1, ].

S 2 S 2

FNC190-FNC199 Block Data Operation

S 1 ‚ S 1 ‚

K8765 K8888

[ +3, +2] [ +5, +4]

K9325

"n" points −

K8880

[ +2n-3, +2n-4] [ +2n-1, +2n-2]

K50000

K4352

K-115

FNC200-FNC209 Character String Control

[ +3, +2] [ +5, +4]

K8

D ‚ D ‚

D ‚ D ‚

K445

[ +2n-3, +2n-4] [ +2n-1, +2n-2]

K41120

K-4528

FNC210-FNC219 Data Operation 3

Related instruction

BK+ (FNC192) Adds binary block data.

Caution

  • When underflow or overflow occurs in the operation result, the following processing is executed. At this time, the carry flag does not turn ON. - In the case of 16-bit operation

K-32768(H8000) – K2(H0002) → K32766(H7FFE)

K32767(H7FFF) – K-2(HFFFE) → K-32767(H8001)

FNC250-FNC269 Data Table Operation

- In the case of 32-bit operation

K-2,147,483,648(H80000000) – K2(H00000002) → K2,147,483,646(H7FFFFFFE)

K2,147,483,647(H7FFFFFFF) – K-2(HFFFFFFFE) → K-2,147,483,647(H80000001)

  • Note that the 32-bit value [n+1, n] is valid when D or R is specified as "n" in a 32-bit instruction. In the case of "DBK - D0 D100 D200 R0", "n" is [R1, R0].
Show 21 more labels / short text on this page
Command · input FNC193 · FNC170-FNC179 External Device · b31 b0 · b31 b0 · [ +1, ] · [ +1, ] · "n" points · FNC180 Alternate Instructions · b31 b0 · [ +1, ] · "n" points · FNC181-FNC189 Others · b31 b0 · [ +1, ] · b31 b0 · [ +1, ] · "n" points · Instruction Description · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 608 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 608 · click to enlarge
Page 608

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

25 Block Data Operation – FNC190 to FNC199

25.2 NFC193 – BK– / Block Data Subtraction

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When "n" ("2n" in 32-bit operation) devices starting from , , and/or exceed the corresponding device range (error code: K6706)

S 1 S 2 D

  • When "n" ("2n" in 32-bit operation) devices starting from overlap "n" ("2n" in 32-bit operation) devices
starting from (error codeK6706)
  • When "n" ("2n" in 32-bit operation) devices starting from overlap "n" ("2n" in 32-bit operation) devices
starting from (error codeK6706)

Program example

In the program shown below, the constant "8765" is subtracted from the data stored in D100 to D102 when X010 is set to ON, and the operation result is stored in D200 and later.

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 608)
Fig. 587 · Program example
Page 609 of the Mitsubishi Electronics MELSEC FX3S user manual — 25.3 FNC194~199 – BKCMP=, >, <, < >, <=, >= / Block Data Compare
Page 609 · click to enlarge
Page 609

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

25 Block Data Operation – FNC190 to FNC199

25.3 FNC194~199 – BKCMP=, >, <, < >, <=, >= / Block Data Compare 21

Mitsubishi Electronics MELSEC FX3S — 25.3 FNC194~199 – BKCMP=, >, <, < >, <=, >= / Block Data Compare diagram (page 609)
Fig. 588 · 25.3 FNC194~199 – BKCMP=, >, <, < >, <=, >= / Block…

25.3 FNC194~199 – BKCMP=, >, <, < >, <=, >= / Block Data Compare

These instructions compare block data in the comparison condition set in each instruction.

16- or 32-bit binary Head device number storing comparison source data

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S: "D .b" cannot be indexed with index registers (V and Z).

Page 610 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 2
Page 610 · click to enlarge
Page 610

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

25 Block Data Operation – FNC190 to FNC199

25.3 FNC194~199 – BKCMP=, >, <, < >, <=, >= / Block Data Compare

Explanation of function and operation

1. 16-bit operation (BKCMP=, >, P,
1. "n" 16-bit binary data starting from are compared with "n" 16-bit binary data starting from , and the

S 1 S 2

Mitsubishi Electronics MELSEC FX3S — S 1 S 2 diagram (page 610)
Fig. 589

comparison result is stored in "n" points starting from .

*1 The number out of 194 to 199 is put in "OOO". *2 The symbol out of "=", ">", "

S1 ‚ S2 ‚ n D ‚

*3 An operation example of BKCMP> (FNC195) instruction is shown here.

2. A constant can be directly specified in .

*4 An operation example of BKCMP= (FNC194) instruction is shown here.

3. The table below shows the comparison result in each instruction:
Mitsubishi Electronics MELSEC FX3S — S 1 S 2 diagram (page 610)
Fig. 590

Instruction Comparison result ON (1) condition Comparison result OFF (0) condition

4. When the comparison result is ON (1) in all of "n" points starting from , M8090 (block comparison signal) turns ON.
Page 611 of the Mitsubishi Electronics MELSEC FX3S user manual — Related device
Page 611 · click to enlarge
Page 611

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

25 Block Data Operation – FNC190 to FNC199

25.3 FNC194~199 – BKCMP=, >, <, < >, <=, >= / Block Data Compare 21

2. 32-bit operation (DBKCMP=, >, P,

FNC160-FNC169 Real Time Clock Control

1. "n" 32-bit binary data starting from [ +1, ] are compared with "n" 32-bit binary data starting from

S 1 S 1

[ +1, ], and the comparison result is stored in "n" points starting from [ +1, ].

S 2 S 2 D D

*1 The number out of 194 to 199 is put in "OOO". *2 The symbol out of "=", ">", "

input FNCOOO*1 DBKCMP *2 S1 ‚ S2 ‚ n D ‚

K1234 K5678

K5321 K3399

[ +3, +2] [ +5, +4]

S 1 ‚ S 1 ‚

S 1 ‚ S 1 ‚

[ +3, +2] [ +5, +4]

S 2 ‚ S 2 ‚

S 2 ‚ S 2 ‚

K5000

K5678

>

[ +2n-3, +2n-4] [ +2n-1, +2n-2]

K40000

[ +2n-3, +2n-4] [ +2n-1, +2n-2]

K6543

K4321

K1200

*3 An operation example of DBKCMP> (FNC195) instruction is shown here.

OFF(0)

ON(1)

OFF(0)

ON(1)

ON(1)

2. A constant can be directly specified in [ +1, ].

S 1 S 1

K32000

[ +3, +2] [ +5, +4]

S2‚

K4321

FNC190-FNC199 Block Data Operation

[ +1, ] K32000

=

K32000

[ +2n-3, +2n-4] [ +2n-1, +2n-2]

K1234

*4 An operation example of DBKCMP= (FNC194) instruction is shown here.

K5678

ON(1) OFF(0)

FNC200-FNC209 Character String Control

ON(1)

OFF(0)

OFF(0)

3. The table below shows the comparison result for each instruction:

FNC210-FNC219 Data Operation 3

Instruction Comparison result ON (1) condition Comparison result OFF (0) condition

DBKCMP= (FNC194) [ +1, ] = [ +1, ] [ +1, ] ≠ [ +1, ]

S1 S1 S2 S2 S1 S1 S2 S2

DBKCMP> (FNC195) [ +1, ] > [ +1, ] [ +1, ]

S1 S1 S2 S2 S1 S1 S2 S2

DBKCMP< (FNC196) [ +1, ]< [ +1, ] [ +1, ] >= [ +1, ]

S1 S1 S2 S2 S1 S1 S2 S2

DBKCMP (FNC197) [ +1, ] ≠ [ +1, ] [ +1, ] = [ +1, ]

S1 S1 S2 S2 S1 S1 S2 S2

DBKCMP

S1 S1 S2 S2 S1 S1 S2 S2

DBKCMP>= (FNC199) [ +1, ] >= [ +1, ] [ +1, ] < [ +1, ]

S1 S1 S2 S2 S1 S1 S2 S2

4. When the comparison result is ON (1) in all of "n" points starting from [ +1, ], the M8090 (block comparison signal) turns ON.

D D

FNC250-FNC269 Data Table Operation

Related device

→ For the block comparison signal use method, refer to Subsection 6.5.2.

Turns ON when all comparison results are "ON (1)" in a block data instruction. DBKCMP= (FNC194), DBKCMP> (FNC195), DBKCMP< (FNC196), DBKCMP (FNC197), DBKCMP= (FNC199)

M8090 Block comparison signal

Show 25 more labels / short text on this page
Command · FNC170-FNC179 External Device · [ +1, ] · [ +1, ] · "n" points · *3 · "n" points · FNC180 Alternate Instructions · Comparison result · +0 · +1 +2 · "n" points · +n-2 +n-1 · FNC181-FNC189 Others · [ +1, ] · *4 · "n" points · Comparison result · +0 · +1 +2 · "n" points · +n-2 +n-1 · FNC220-FNC249 Data Comparison · Device Name Description · FNC270-FNC276 Ex-Device
Page 612 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 2
Page 612 · click to enlarge
Page 612

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

25 Block Data Operation – FNC190 to FNC199

25.3 FNC194~199 – BKCMP=, >, <, < >, <=, >= / Block Data Compare

Caution

  • When using 32-bit counters (including 32-bit high-speed counters) For comparing 32-bit counters and 32-bit high-speed counters (C200 to C255), make sure to use an instruction for 32-bit operation (DBKCMP=, DBKCMP>, DBKCMP<, DBKCMP<>, DBKCMP<=, or DBKCMP>=). If an instruction for 16-bit operation (BKCMP=, BKCMP>, BKCMP<, BKCMP<>, BKCMP<=, or BKCMP>=) is used, an operation error is caused (error code: K6705).
  • Note that the 32-bit value [n+1, n] is valid when D or R is specified as "n" in a 32-bit instruction. In the case of "DBKCMP = D0 D100 M0 R0", "n" is [R1, R0].

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When the range of "n" ("2n" in 32-bit operation) points starting from and/or exceeds the corresponding device range (error code: K6706)

S 1 S 2

  • When the range of "n" points starting from exceeds the corresponding device range (error code: K6706)
  • When data registers starting from specified as "D .b" overlap "n" ("2n" in 32-bit operation) points starting
from (error codeK6706)
  • When data registers starting from specified as "D .b" overlap "n" ("2n" in 32-bit operation) points starting
from (error codeK6706)
  • When a 32-bit counter (C200 to C255) is specified in and/or in 16-bit operation (error code: K6705) For comparing 32-bit counters, make sure to use an instruction for 32-bit operation (DBKCMP=, DBKCMP>, DBKCMP<, DBKCMP<>, DBKCMP<=, or DBKCMP>=).

S 1 S 2

Program example

1. In the program shown below, four 16-bit binary data starting from D100 are compared with four 16-bit binary data starting from D200 by BKCMP= (FNC194) instruction when X020 is set to ON, and the comparison result is stored in four points starting from M10. When the comparison result is "ON (1)" in all of the four points starting from M10, Y000 is set to ON.
Mitsubishi Electronics MELSEC FX3S — S 1 S 2 diagram (page 612)
Fig. 591

(When all of M10 to M13 are ON, Y000 is set to ON.)

2. In the program shown below, the constant K1000 is compared with four data starting from D10 when X010 is set to ON, and the comparison result is stored in b4 to b7 of D0.
Mitsubishi Electronics MELSEC FX3S — S 1 S 2 diagram (page 612)
Fig. 592

b15 b7 b4 b0 D0 before operation 0 1 0 0 0 1 0 1 0

b15 b7 b4 b0 D0 after operation 0 1 0 0 1 0 1 0 1 0

Page 613 of the Mitsubishi Electronics MELSEC FX3S user manual — 26. Character String Control – FNC200 to FNC209
Page 613 · click to enlarge
Page 613

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

Mitsubishi Electronics MELSEC FX3S — 26. Character String Control – FNC200 to FNC209 diagram (page 613)
Fig. 593 · 26. Character String Control – FNC200 to FNC209

FNC200 to FNC209 provide instructions for controlling character strings such as linking character string data, replacing some characters and extracting character string data.

200 STR BIN to Character String Conversion Section 26.1

201 VAL Character String to BIN Conversion Section 26.2

204 RIGHT Extracting Character String Data from the Right Section 26.5

205 LEFT Extracting Character String Data from the Left Section 26.6

206 MIDR Random Selection of Character Strings Section 26.7

207 MIDW Random Replacement of Character Strings Section 26.8

Page 614 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Applicable devices
Page 614 · click to enlarge
Page 614

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.1 FNC200 – STR / BIN to Character String Conversion

26.1 FNC200 – STR / BIN to Character String Conversion

Outline

This instruction converts binary data into character strings (ASCII codes). On the other hand, the ESTR (FNC116) instruction converts floating point data into character strings.

→ For character strings, refer to Section 5.3. → For ESTR (FNC116) instruction, refer to Section 18.4.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 614)
Fig. 594 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 614)
Fig. 595 · 2. Set data

Head device number storing the number of digits of a numeric value to be converted 16-bit binary

Device number storing binary data to be converted 16- or 32-bit binary

Head device number storing converted character string Character string

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 614)
Fig. 596 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

Page 615 of the Mitsubishi Electronics MELSEC FX3S user manual — 00H
Page 615 · click to enlarge
Page 615

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.1 FNC200 – STR / BIN to Character String Conversion 21

Explanation of function and operation

FNC160-FNC169 Real Time Clock Control

1. 16-bit operation (STR and STRP)

1. All digits (specified by ) of 16-bit binary data stored in are converted into ASCII codes while the decimal point is added to the position specified by the device storing the number of digits of the decimal part

S 1 S 2

( +1), and stored in and later.

S 1 D

STR S2 ‚ S1 ‚ D ‚

+0 Number of all

ASCII code in "(Value specifying number of all

ASCII code indicating sign

digits Number of digits

digits - 1)"th digit ASCII code in "(Value specifying number of all

ASCII code in "(Value specifying number of all

+1 For number of all digits For value stored in S1‚

digits - 3)"th digit ASCII code in "(Value specifying number of all

digits - 2)"th digit ASCII code in "(Value specifying number of all

digits - 5)"th digit ASCII code in "(Value specifying number of all

digits - 4)"th digit ASCII code in "(Value specifying number of all

digits - 7)"th digit

digits - 6)"th digit 0000H

S2‚ 16-bit binary data

0000H is automatically stored at the end of a character string.

31H(1)

2DH(-)

For number of all digits

2EH(.)

32H(2)

FNC190-FNC199 Block Data Operation

- 1 2 3

00H

33H(3)

00H is automatically stored at the end of a character string.

2. Set the number of all digits ranging from 2 to 8.

FNC200-FNC209 Character String Control

3. Set the number of digits of the decimal part +1 ranging from 0 to 5. Make sure to satisfy "Number of digits of decimal part
4. 16-bit binary data to be converted stored in should be ranging from -32768 to +32767.
5. Converted character string data is stored in and later as shown below.

- As the sign, "space" (20H) is stored when the 16-bit binary data stored in is positive, and "-" (2DH) is

stored when the 16-bit binary data stored in is negative. - When the number of digits of the decimal

FNC210-FNC219 Data Operation 3

Number of all digits

part +1 is set to any value other than "0", the decimal point "." (2EH) is automatically added in "number of digits of decimal part + 1"th digit. When the number of digits of the decimal

Number of digits of decimal part 16-bit binary data

1 2 3 Number of digits of decimal part

It is automatically added.

part +1 is set to "0", the decimal point is not added. - When the number of digits of the decimal

Number of all digits Number of digits of decimal part 16-bit binary data It is automatically added.

part +1 is larger than the number of digits of 16-bit binary data stored in

0 0 1 2

, "0" (30H) is automatically added, and the data is shifted to the right end during conversion.

FNC250-FNC269 Data Table Operation

Show 21 more labels / short text on this page
FNC170-FNC179 External Device · Command · input FNC200 · b15 · b8 b7 b0 · +1 · of decimal part · FNC180 Alternate Instructions · +2 · +3 · Sign · +4 · FNC181-FNC189 Others · +1 b15 · b8 b7 b0 · +0 · +1 · 16-bit binary data · +2 · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 616 of the Mitsubishi Electronics MELSEC FX3S user manual — S 2 S 2
Page 616 · click to enlarge
Page 616

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.1 FNC200 – STR / BIN to Character String Conversion

- When the number of all digits stored in

Mitsubishi Electronics MELSEC FX3S — 26.1 FNC200 – STR / BIN to Character String Conversion diagram (page 616)
Fig. 597 · 26.1 FNC200 – STR / BIN to Character String Conversi…

Number of all digits Number of digits of decimal part 16-bit binary data

excluding the sign and decimal point is larger than the number of digits of

16-bit binary data stored in , "space" (20H) is stored in each digit between the sign and the numeric value. When the number of all digits stored in

excluding the sign and decimal point is smaller than the number of digits of 16-bit binary data stored in

, an error is caused. - "00H" indicating the end of a character string is automatically stored at the end of a converted character string. When the number of all digits is even, "0000H" is stored in the device after the last character. When the number of all digits is odd, "00H" is stored in the high-order byte (8 bits) of the device storing the final character.

2. 32-bit operation (DSTR and DSTRP)

1. All digits (specified by ) of 32-bit binary data stored in [ +1, ] are converted into ASCII codes while the decimal point is added to the position specified by the device storing the number of digits of the decimal

S 1 S 2 S 2

part ( +1), and stored in and later.

S 1 D

DSTR S2 ‚ S1 ‚ D ‚

ASCII code in "(Value specifying number of all

digits Number of digits

ASCII code indicating sign

digits - 1)"th digit ASCII code in "(Value specifying number of all

ASCII code in "(Value specifying number of all

digits - 3)"th digit ASCII code in "(Value specifying number of all

digits - 2)"th digit ASCII code in "(Value specifying number of all

For number of all digits For value stored in S1‚

digits - 5)"th digit ASCII code in "(Value specifying number of all

digits - 4)"th digit ASCII code in "(Value specifying number of all

digits - 7)"th digit

digits - 6)"th digit

ASCII code in "(Value specifying number of all

ASCII code in "(Value specifying number of all

digits - 8)"th digit +4 b31 b16 b15 b0 S2‚ +1 S2‚

digits - 9)"th digit

00H Low-order 16 bits ASCII code in "(Value specifying number of all

S2‚ High-order 16 bits

digits - 10)"th digit

00H is automatically stored at the end of a character string.

36H(6)

2DH(-)

34H(4)

35H(5)

For number of all digits

2EH(.) 5 6 -

4 3 2 1

33H(3)

S2‚ S2‚ 32-bit binary data +4

+3 31H(1)

32H(2)

0000H

0000H is automatically stored at the end of a character string.

2. Set the number of all digits ranging from 2 to 13.
3. Set the number of digits of the decimal part +1 ranging from 0 to 10. Make sure to satisfy "Number of digits of decimal part
4. 32-bit binary data to be converted stored in [ +1, ] should be ranging from -2,147,483,648 to +2,147,483,647.

S 2 S 2

Show 21 more labels / short text on this page
Command · input FNC200 · b15 · b8 b7 b0 · Number of all · +0 · +1 · of decimal part · +1 · +2 · Sign · +3 · +5 · 32-bit binary data · +1 b15 · b8 b7 b0 · +0 · +1 · +2 · +1 · -654321
Page 617 of the Mitsubishi Electronics MELSEC FX3S user manual — S 2 S 2
Page 617 · click to enlarge
Page 617

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.1 FNC200 – STR / BIN to Character String Conversion 21

5. Converted character string data is stored in and later as shown below.

FNC160-FNC169 Real Time Clock Control

- For the sign, "space" (20H) is stored when the 32-bit binary data stored in is positive, and "- (2DH)" is

stored when the 32-bit binary data stored in is negative. - When the number of digits of the

Number of all digits Number of digits of decimal part 32-bit binary data

decimal part +1 is set to any value other than "0", the decimal point "." (2EH) is automatically added in "number of digits of decimal part + 1"th digit. When the number of digits of the

1 2 6 7

3 4 5 8

Number of digits of decimal part It is automatically added.

decimal part +1 is set to "0", the decimal point is not added. - When the number of digits of the decimal

Number of all digits Number of digits of decimal part 16-bit binary data

part +1 is larger than the number of digits of 32-bit binary data stored in

0 1 0 5

0 0 0 4 0 3 2

[ +1, ], "0" (30H) is automatically added, and the data is shifted to the right end during conversion.

S 2 S 2

It is automatically added.

- When the number of all digits stored in

Number of all digits Number of digits of decimal part 32-bit binary data

excluding the sign and decimal point is larger than the number of digits of 32-bit

0 4 3 2 1 -

binary data stored in [ +1, ], "space" (20H) is stored in each digit between the sign and the numeric value. When the number of all digits stored in

S 2 S 2

"20H" (space) is stored in each digit.

excluding the sign and decimal point is smaller than the number of digits of 32-bit binary data stored in

FNC190-FNC199 Block Data Operation

[ +1, ], an error is caused. - "00H" indicating the end of a character string is automatically stored at the end of a converted character string. When the number of all digits is even, "0000H" is stored in the device after the last character. When the number of all digits is odd, "00H" is stored in the high-order byte (8 bits) of the device storing the final character.

S 2 S 2

FNC200-FNC209 Character String Control

Related instructions

ESTR (FNC116) Converts binary floating point data into a character string (ASCII codes) with a specified number of digits.

EVAL (FNC117) Converts a character string (ASCII codes) into binary floating point data.

VAL (FNC201) Converts a character string (ASCII codes) into binary data.

FNC210-FNC219 Data Operation 3

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When the number of all digits stored in is outside the following range (error code: K6706)

16-bit operation 2 to 8

32-bit operation 2 to 13

  • When the number of digits of the decimal part stored in +1 is outside the following range (error code: K6706)

16-bit operation 0 to 5

32-bit operation 0 to 10

FNC250-FNC269 Data Table Operation

  • When the relationship between the number of all digits stored in and the number of digits of the decimal part

stored in +1 does not satisfy the following (error code: K6706) (Number of all digits -3) ≥ Number of digits of decimal part

  • When the number of all digits stored in including the digit for sign and the digit for decimal point is smaller

than the number of digits of the binary data stored in [ +1, ] (error code: K6706)

S 2 S 2

  • When the devices and later storing a character string exceeds the corresponding device range (error code: K6706)
Show 10 more labels / short text on this page
FNC170-FNC179 External Device · 12345678 · FNC180 Alternate Instructions · FNC181-FNC189 Others · -543210 · Instruction Description · Setting range · FNC220-FNC249 Data Comparison · Setting range · FNC270-FNC276 Ex-Device
Page 618 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 618 · click to enlarge
Page 618

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.1 FNC200 – STR / BIN to Character String Conversion

Program example

In the program below, the 16-bit binary data stored in D10 is converted into a character string in accordance with the digit specification by D0 and D1 when X000 is set to ON, and then stored in D20 to D23.

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 618)
Fig. 598 · Program example

The number of digits of the decimal part is set.

Number of all digits Number of digits of decimal part

Page 619 of the Mitsubishi Electronics MELSEC FX3S user manual — 00H
Page 619 · click to enlarge
Page 619

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.2 FNC201 – VAL / Character String to BIN Conversion 21

26.2 FNC201 – VAL / Character String to BIN Conversion

FNC160-FNC169 Real Time Clock Control

Outline

This instruction converts a character string (ASCII codes) into binary data. On the other hand, EVAL (FNC117) instruction converts a character string (ASCII codes) into floating point data.

→ For character strings, refer to Section 5.3. → For EVAL (FNC117) instruction, refer to Section 18.5.

1. Instruction format

Mnemonic Operation Condition P FNC 201

VAL D

Continuous Operation Pulse (Single) Operation

13 steps Continuous Operation Pulse (Single) Operation

DVAL

VALP

DVALP

2. Set data

Operand Type Description Data Type

Head device number storing a character string to be converted into binary data Character string

Head device number storing the number of all digits of the binary data acquired by conversion 16-bit binary

Head device number storing the binary data acquired by conversion 16- or 32-bit binary

3. Applicable devices

Bit Devices Word Devices Others

FNC190-FNC199 Block Data Operation

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

FNC200-FNC209 Character String Control

3

Explanation of function and operation

1. 16-bit operation (VAL and VALP)

1. A character string stored in and later is converted into 16-bit binary data. The number of all digits of the

FNC210-FNC219 Data Operation 3

binary data acquired for conversion is stored in , the number of digits of the decimal part is stored in

D 1 D 2

+1, and the converted binary data is stored in .

In converting a character string into binary data, the data from to a device number storing "00H" is handled as a character string in byte units.

VAL D1 ‚ S ‚ D2 ‚

digits Number of digits

ASCII code of 1st character

ASCII code indicating sign

ASCII code of 3rd character

ASCII code of 2nd character

ASCII code of 5th character

ASCII code of 4th character

which decimal point is ignored

FNC250-FNC269 Data Table Operation

ASCII code of 7th character

ASCII code of 6th character

00H

1st character 2nd character

It indicates the end of character string.

Show 29 more labels / short text on this page
FNC170-FNC179 External Device · 16-bit Instruction · Mnemonic Operation Condition · 32-bit Instruction · 7 steps VAL · FNC180 Alternate Instructions · FNC181-FNC189 Others · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input FNC201 · FNC220-FNC249 Data Comparison · Number of all · +1 b15 · b8 b7 b0 · +0 · of decimal part · +1 · Integer value in · +2 · +3 · Sign · 7th character · +4 · 16-bit binary data · FNC270-FNC276 Ex-Device
Page 620 of the Mitsubishi Electronics MELSEC FX3S user manual — 26.2 FNC201 – VAL / Character String to BIN Conversion
Page 620 · click to enlarge
Page 620

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.2 FNC201 – VAL / Character String to BIN Conversion

For example, when a character string "-123.45" is specified in and later, the conversion result is stored in

Mitsubishi Electronics MELSEC FX3S — 26.2 FNC201 – VAL / Character String to BIN Conversion diagram (page 620)
Fig. 599 · 26.2 FNC201 – VAL / Character String to BIN Conversi…
2. Character string to be converted a) Number of characters of character string and the numeric range when the decimal point is ignored
Mitsubishi Electronics MELSEC FX3S — 26.2 FNC201 – VAL / Character String to BIN Conversion diagram (page 620)
Fig. 600 · 26.2 FNC201 – VAL / Character String to BIN Conversi…

Number of characters (digits) of decimal part 0 to 5 and smaller than "number of all digits -3"

Numeric range when decimal point is ignored −32768 to +32767 Example: 123.45 → 12345

b) Character types used in characters to be converted

Mitsubishi Electronics MELSEC FX3S — 26.2 FNC201 – VAL / Character String to BIN Conversion diagram (page 620)
Fig. 601 · 26.2 FNC201 – VAL / Character String to BIN Conversi…

Number "0" (30H) to "9" (39H)

3. stores the number of all digits. The number of all digits indicates the number of all characters (including the number, sign and decimal point).
4. +1 stores the number of digits of the decimal part. The number of digits of the decimal part indicates the number of all characters after the decimal point "." (2EH).
5. stores 16-bit data (bin) converted from a character string with the decimal point ignored.

In the character string located in and later, "space" (20H) and "0" (30H) characters between the sign and the first number other than "0" are ignored in the conversion to 16-bit binary data.

Mitsubishi Electronics MELSEC FX3S — 26.2 FNC201 – VAL / Character String to BIN Conversion diagram (page 620)
Fig. 602 · 26.2 FNC201 – VAL / Character String to BIN Conversi…

Number of all digits Number of digits of decimal part 16-bit binary data

Number of digits of decimal part 16-bit binary data

Page 621 of the Mitsubishi Electronics MELSEC FX3S user manual — 00H
Page 621 · click to enlarge
Page 621

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.2 FNC201 – VAL / Character String to BIN Conversion 21

2. 32-bit operation (DVAL and DVALP)

FNC160-FNC169 Real Time Clock Control

1. A character string stored in and later is converted into 32-bit binary data. The number of all digits of the

binary data acquired for conversion is stored in , the number of digits of the decimal part is stored in

D 1 D 2 D 2

+1, and the binary data is stored in [ +1, ].

In conversion from a character string into binary data, the data from to a device number storing "00H" is handled as a character string in byte units.

DVAL D1 ‚ S ‚ D2 ‚

digits Number of digits

ASCII code of 1st character

ASCII code indicating sign

ASCII code of 3rd character

ASCII code of 2nd character

ASCII code of 5th character

ASCII code of 4th character

which decimal point is ignored

ASCII code of 7th character

ASCII code of 6th character

1st character 2nd character

ASCII code of 9th character

ASCII code of 8th character

ASCII code of 11th character

ASCII code of 10th character

00H

ASCII code of 12th character

It indicates the end of character string.

For example, when a character string "-12345.678" is specified in and later, the conversion result is stored

in and as shown below.

D 1 D 2

FNC190-FNC199 Block Data Operation

31H(1)

2DH(-)

33H(3)

32H(2)

35H(5)

34H(4)

- 2 3 5 6

7 4 8 1 -12345678 D2‚ +1 D2‚

36H(6)

2EH(.)

38H(8) 37H(7)

FNC200-FNC209 Character String Control

00H

2. Character string to be converted a) Number of characters of character string and the numeric range when the decimal point is ignored

Number of all characters (digits) 2 to 13

FNC210-FNC219 Data Operation 3

Number of characters (digits) of decimal part 0 to 10 and smaller than "number of all digits −3"

Numeric range when decimal point is ignored −2,147,483,648 to +2,147,483,647 Example: 12345.678 → "12345678"

b) Character types used in characters to be converted

Positive numeric value "Space" (20H)

Negative numeric value "–" (2DH)

Decimal point "." (2EH)

Number "0" (30H) to "9" (39H)

3. stores the number of all digits. The number of all digits indicates the number of all characters (including the number, sign and decimal point).

FNC250-FNC269 Data Table Operation

4. +1 stores the number of digits of the decimal part. The number of digits of the decimal part indicates the number of all characters after the decimal point "." (2EH).
Show 33 more labels / short text on this page
FNC170-FNC179 External Device · Command · input FNC201 · Number of all · +1 b15 · b8 b7 b0 · +0 · of decimal part · FNC180 Alternate Instructions · +2 · Integer value in · +3 · Sign · 12th character · +4 · 32-bit binary data · +5 · +6 · FNC181-FNC189 Others · b15 · b8 b7 b0 · +0 10 3 · +1 · +1 · +2 · +3 · +4 · +5 · Description · Character type · FNC220-FNC249 Data Comparison · Sign · FNC270-FNC276 Ex-Device
Page 622 of the Mitsubishi Electronics MELSEC FX3S user manual — Errors
Page 622 · click to enlarge
Page 622

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.2 FNC201 – VAL / Character String to BIN Conversion

5. [ +1, ] stores 16-bit data (bin) converted from a character string with the decimal point ignored. For the character string located in and later, the "space" (20H) and "0" (30H) characters between the sign and the first number other than "0" are ignored in the conversion to 32-bit binary data.

D 2 D 2

Mitsubishi Electronics MELSEC FX3S — D 2 D 2 diagram (page 622)
Fig. 603

Total number of digits Number of digits after the decimal point

Total number of digits Number of digits after the decimal point

Related instructions

Mitsubishi Electronics MELSEC FX3S — Related instructions diagram (page 622)
Fig. 604 · Related instructions

ESTR (FNC116) Converts binary floating point data into a character string (ASCII code) with a specified number of digits.

EVAL (FNC117) Converts a character string (ASCII code) into binary floating point data.

STR (FNC200) Converts binary data into a character string (ASCII code).

Caution

Store sign data, "space (20H)" or "- (2DH)", must be stored in the 1st byte (lower order 8 bits of the head device set in ). Only the ASCII code data "0 (30H)" to "9 (39H)", "space (20H)" and "decimal point (2EH)" can be stored from the 2nd byte to the "00H" at the end of the character string in . If "- (2DH)" is stored in the 2nd byte or later, an operation error (error code: K6706) occurs.

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When the number of characters of the character string to be converted ( and later) is outside the following ranges (error code: K6706)

16-bit operation 2 to 8

32-bit operation 2 to 13

  • When the number of characters after the decimal point of the character string to be converted ( and later) is outside the following ranges (error code: K6706)

16-bit operation 0 to 5

32-bit operation 0 to 10

  • When the relationship between the number of all characters in the character string to be converted ( and later) and the number of characters after the decimal point does not satisfy the following (error code: K6706) (Number of all characters -3) ≥ Number of characters after the decimal point
  • When the sign is set to any ASCII code other than "space" (20H) and "-" (2DH) (error code: K6706)
  • When a digit of a number is set to any ASCII code other than "0" (30H) to "9" (39H) or a decimal point "." (2EH) (error code: K6706)
  • When the decimal point "." (2EH) is set two or more times in the character string to be converted ( and later) (error code: K6706)
  • When the binary data acquired by conversion is outside the following range (error code: K6706)

16-bit operation −32768 to 32767

32-bit operation −2,147,483,648 to 2,147,483,647

  • When "00H" is not present in the location from to the final device number (error code: K6706)

Setting range · Setting range · Setting range

Page 623 of the Mitsubishi Electronics MELSEC FX3S user manual — 26.2 FNC201 – VAL / Character String to BIN Conversion 21
Page 623 · click to enlarge
Page 623

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.2 FNC201 – VAL / Character String to BIN Conversion 21

Mitsubishi Electronics MELSEC FX3S — 26.2 FNC201 – VAL / Character String to BIN Conversion 21 diagram (page 623)
Fig. 605 · 26.2 FNC201 – VAL / Character String to BIN Conversi…
1. In the program below, the character string data stored in D20 to D22 is regarded as an integer value, converted into a binary value, and stored in D0 when X000 is set to ON.

Number of all digits Number of digits of decimal part

2. In the program below, the character string data stored in D20 to D24 is regarded as an integer value, converted into a binary value, and stored in D0 when X000 is set to ON.

Number of all digits Number of digits of decimal part 36H(6) 2EH(.) 31H(1) 31H(1) D24 D25

Page 624 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 2
Page 624 · click to enlarge
Page 624

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.3 FNC202 – $+ / Link Character Strings

26.3 FNC202 – $+ / Link Character Strings

Outline

This instruction links a character string to another character string.

→ For handling of character strings, refer to Section 5.3.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 624)
Fig. 606 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 624)
Fig. 607 · 2. Set data

Head device number storing the link source data (character string) or directly specified character string

Character string Head device number storing the link data (character string) or directly specified character string

Head device number storing the linked data (character string)

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 624)
Fig. 608 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

3

Explanation of function and operation

1. 16-bit operation ($+ and $+P)

The character string data stored in and later is linked to the end of the character string data stored in and

S 2 S 1

later, and the linked data is stored to devices starting from .

A character string stored in or or later indicates the data from the specified device to the first "00H" in units of byte.

S 1 S 2

Mitsubishi Electronics MELSEC FX3S — S 1 S 2 diagram (page 624)
Fig. 609
  • In linking, “00H” indicating the end of a character string specified in is ignored, and a character string

specified in is linked to the last character specified in . When a character string is linked, “00H” is automatically added at the end. - When the number of characters after linking is odd, “00H” is stored in the high-order byte of the device storing the last character. - When the number of characters after linking is even, “0000H” is stored in the device after the last character.

Page 625 of the Mitsubishi Electronics MELSEC FX3S user manual — D102 41H(A)
Page 625 · click to enlarge
Page 625

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.3 FNC202 – $+ / Link Character Strings 21

Cautions

FNC160-FNC169 Real Time Clock Control

  • When directly specifying a character string, up to 32 characters can be specified (input).

However, this limitation in the number of characters is not applied when a word device is specified in or

  • When the values in both and start from "00H" (that is, when the number of characters is “0”), "0000H"

S 1 S 2

is stored in .

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When the number of devices after a device number specified by is smaller than the number of devices required to store all linked character strings (that is, when “00H” cannot be stored after all character strings and the last character) (error code: K6706)
  • When the same device is specified in , and as a device for storing a character string (error code: K6706)

S 1 S 2 D

  • When “00H” is not set within the corresponding device range after the device specified by or (error code: K6706)

S 1 S 2

Program example

In the program example shown below, a character string stored in D10 to D12 (abcde) is linked to the character string “ABCD”, and the result is stored to D100 and later when X000 turns ON.

“ABCD” D100 FNC202

FNC190-FNC199 Block Data Operation

END

00H +

65H(e) “ABCD”

FNC200-FNC209 Character String Control

D102 41H(A)

43H(C) 42H(B)

00H 44H(D)

“00H” is automatically stored.

FNC210-FNC219 Data Operation 3

FNC250-FNC269 Data Table Operation

Show 14 more labels / short text on this page
FNC170-FNC179 External Device · FNC180 Alternate Instructions · FNC181-FNC189 Others · $+ · b15---b8 · b7----b0 b7----b0 · b15---b8 · 62H(b) 61H(a) · 62H(b) 61H(a) · 64H(d) 63H(c) · 64H(d) 63H(c) · 65H(e) · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 626 of the Mitsubishi Electronics MELSEC FX3S user manual — S D S
Page 626 · click to enlarge
Page 626

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.4 FNC203 – LEN / Character String Length Detection

26.4 FNC203 – LEN / Character String Length Detection

Outline

This instruction detects the number of characters (bytes) of a specified character string.

→ For handling of character strings, refer to Section 5.3.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 626)
Fig. 610 · 1. Instruction format

2. Set data

Operand Type Description Data Type

Head device number storing a character string whose length is to be detected Character string

Device number storing the detected character string length (number of bytes) 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 626)
Fig. 611 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

Explanation of function and operation

1. 16-bit operation (LEN and LENP)

The length of a character string stored in and later is detected, and stored to . Data starting from until the first device storing "00H" is handled as a character string in units of byte.

S D S

Mitsubishi Electronics MELSEC FX3S — S D S diagram (page 626)
Fig. 612

For example, when “ABCDEFGHI” is stored in and later as shown below, K9 is stored to .

Page 627 of the Mitsubishi Electronics MELSEC FX3S user manual — 43H(C)
Page 627 · click to enlarge
Page 627

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.4 FNC203 – LEN / Character String Length Detection 21

Caution

FNC160-FNC169 Real Time Clock Control

  • This instruction can handle character codes other than ASCII codes, but the character string length is handled in byte units (8 bits). Accordingly, in the case of character codes in which 2 bytes express 1 character such as shift JIS codes, the length of 1 character is detected as “2”.

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When “00H” is not set within the corresponding device range after a device specified by (error code: K6706)
  • When the detected number of characters is “32768” or more (error code: K6706)

Program example

In the program example shown below, the length of a character string stored in D0 and later is output in 4-digit BCD to Y040 to Y057 when X000 turns ON.

D10 FNC203

LEN D0

The length of the character string is output to the display unit.

K4Y40 FNC 18

BCD D10

END

49H(I) 4DH(M)

FNC190-FNC199 Block Data Operation

53H(S) 54H(T)

42H(B) 55H(U)

0 0 0 1

53H(S)

BCD

49H(I) 48H(H)

“ ABC.......”

41H(A) 00H

after “00H” are ignored.)

FNC200-FNC209 Character String Control

43H(C)

42H(B)

FNC210-FNC219 Data Operation 3

FNC250-FNC269 Data Table Operation

Show 12 more labels / short text on this page
FNC170-FNC179 External Device · FNC180 Alternate Instructions · FNC181-FNC189 Others · b15---b8 · b7----b0 · Conversion · into BCD · Y057 to Y040 · 49H(I) “MITSUBISHI” (Characters · BCD value · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 628 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 628 · click to enlarge
Page 628

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.5 FNC204 – RIGHT / Extracting Character String Data from the Right

26.5 FNC204 – RIGHT / Extracting Character String Data from the Right

Outline

This instruction extracts a specified number of characters from the right end of a specified character string.

→ For handling of character strings, refer to Section 5.3.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 628)
Fig. 613 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 628)
Fig. 614 · 2. Set data

Character string Head device number storing extracted character string

n Number of characters to be extracted 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 628)
Fig. 615 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

Explanation of function and operation

1. 16-bit operation (RIGHT and RIGHTP)

“n” characters are extracted from the right end (that is, from the end) of the character string data stored in and

later, and stored to and later.

If the number of characters specified by “n” is “0”, the NULL code (0000H) is stored to . When characters are extracted from a character string, “00H" is automatically added at the end of the extracted characters.

- When the number of extracted characters is odd, “00H” is stored in the high-order byte of a device storing the last character. - When the number of extracted characters is even, “0000H” is stored in the device after the last character.

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 628)
Fig. 616 · Explanation of function and operation
Page 629 of the Mitsubishi Electronics MELSEC FX3S user manual — “BA210EFA”
Page 629 · click to enlarge
Page 629

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.5 FNC204 – RIGHT / Extracting Character String Data from the Right 21

FNC160-FNC169 Real Time Clock Control

In the case of “n = 5”

42H(B) 41H(A)

32H(2) 31H(1)

44H(D) 43H(C)

34H(4)

33H(3)

46H(F) 45H(E)

+2 00H “12345”

35H(5)

31H(1) 32H(2)

34H(4) 33H(3)

35H(5) ASCII code for 5th character

00H “ABCDEF12345”

ASCII code for 1st character

  • A character string stored in and later indicates data stored in devices from the specified device until "00H" is first detected in byte units.

Cautions

When handling character codes other than ASCII codes, note the following contents:

  • The number of characters is handled in byte units (8 bits). Accordingly, in the case of character codes in which 2 bytes express 1 character such as shift JIS codes, the length of 1 character is detected as “2”.
  • When extracting characters from a character string including character codes in which 2 bytes express 1 character such as shift JIS codes, consider the number of characters to be extracted in units of character codes for 1 character. Note that the expected character code is not given if only 1 byte is executed out of a 2-byte character code.

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

FNC190-FNC199 Block Data Operation

  • When “00H” is not set within the corresponding device range after a device specified by (error code: K6706)
  • When “n” exceeds the number of characters specified by (error code: K6706)
  • When the number of devices after a device number specified by is smaller than the number of devices required to store extracted “n” characters (that is, when “00H” cannot be stored after all character strings and the last character) (error code: K6706)

FNC200-FNC209 Character String Control

  • When “n” is a negative value (error code: K6706)

Program example

In the program example shown below, 4 characters are extracted from the right end of the character string data stored in R0 and later, and stored to D0 and later when X000 turns ON.

FNC210-FNC219 Data Operation 3

D0 FNC204 RIGHTP R0

K4

END

R0 D0

41H(A) 42H(B)

45H(E) 30H(0)

R1

31H(1) 32H(2)

41H(A) 46H(F)

R2

45H(E) 30H(0)

D2 0000H “0EFA”

R3

41H(A)

46H(F)

00H

R4

ASCII code for 4th character

FNC250-FNC269 Data Table Operation

“BA210EFA”

ASCII code for 1st character

Show 12 more labels / short text on this page
b15----------------------b8b7-----------------------b0 · b15----------------------b8b7-----------------------b0 · +1 · +1 · +2 · FNC170-FNC179 External Device · FNC180 Alternate Instructions · FNC181-FNC189 Others · FNC220-FNC249 Data Comparison · b15----------------------b8b7-----------------------b0 · b15----------------------b8b7-----------------------b0 · FNC270-FNC276 Ex-Device
Page 630 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 630 · click to enlarge
Page 630

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.6 FNC205 – LEFT / Extracting Character String Data from the Left

26.6 FNC205 – LEFT / Extracting Character String Data from the Left

Outline

This instruction extracts a specified number of characters from the left end of a specified character string.

→ For handling of character strings, refer to Section 5.3.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 630)
Fig. 617 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 630)
Fig. 618 · 2. Set data

Character string Head device number storing extracted character string

n Number of characters to be extracted 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 630)
Fig. 619 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

Explanation of function and operation

1. 16-bit operation (LEFT and LEFTP)

“n” characters are extracted from the left end (that is, from the head) of the character string data stored in and

later and stored to and later.

If the number of characters specified by “n” is “0”, the NULL code (0000H) is stored to . When characters are extracted from a character string, "00H” is automatically added at the end of the extracted characters.

- When the number of extracted characters is odd, “00H” is stored in the high-order byte of a device storing the last character. - When the number of extracted characters is even, “0000H” is stored in the device after the last character.

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 630)
Fig. 620 · Explanation of function and operation
Page 631 of the Mitsubishi Electronics MELSEC FX3S user manual — 00H
Page 631 · click to enlarge
Page 631

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.6 FNC205 – LEFT / Extracting Character String Data from the Left 21

FNC160-FNC169 Real Time Clock Control

ASCII code for 1st character

In the case of "n = 7"

42H(B) 41H(A)

42H(B) 41H(A)

44H(D) 43H(C)

44H(D) 43H(C)

46H(F) 45H(E)

46H(F) 45H(E)

32H(2)

31H(1)

00H +3 D ‚

31H(1)

34H(4) 33H(3)

"ABCDEF1"

ASCII code for 7th character

00H 35H(5) "ABCDEF12345"

  • A character string stored in and later indicates data stored in devices from the specified device until "00H" is first detected in byte units.

Cautions

When handling character codes other than ASCII codes, note the following contents:

  • The number of characters is handled in byte units (8 bits). Accordingly, in the case of character codes in which 2 bytes express 1 character such as shift JIS codes, the length of 1 character is detected as “2”.
  • When extracting characters from a character string including character codes in which 2 bytes express 1 character such as shift JIS codes, consider the number of characters to be extracted in units of character codes for 1 character. Note that the expected character code is not given if only 1 byte is executed out of a 2-byte character code.

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

FNC190-FNC199 Block Data Operation

  • When “00H” is not set within the corresponding device range after a device specified by (error code: K6706)
  • When “n” exceeds the number of characters specified by (error code: K6706)
  • When the number of devices after a device number specified by is smaller than the number of devices required to store extracted “n” characters (that is, when “00H” cannot be stored after all character strings and the last character) (error code: K6706)

FNC200-FNC209 Character String Control

  • When “n” is a negative value (error code: K6706)

Program example

In the program example shown below, the number of characters which is equivalent to the number stored in D0 are extracted from the left end of the character string data stored in D100 and later, and stored to R10 and later when X010 turns ON.

FNC210-FNC219 Data Operation 3

R10 FNC205

LEFTP D100

END

ASCII code for 1st character

D100 R10

51H(Q) 53H(S)

51H(Q) 53H(S)

4EH(N) 4FH(O)

R11

4EH(N) 4FH(O)

48H(H) 44H(D)

R12

44H(D) 48H(H)

42H(B) 41H(A)

R13

0000H “SQONHD”

FNC250-FNC269 Data Table Operation

00H

“SQONHDAB”

ASCII code for 6th character

Show 13 more labels / short text on this page
b15----------------------b8b7----------------------b0 · b15----------------------b8b7-----------------------b0 · +1 · +1 · +2 · +2 · FNC170-FNC179 External Device · FNC180 Alternate Instructions · FNC181-FNC189 Others · FNC220-FNC249 Data Comparison · b15----------------------b8b7-----------------------b0 · b15----------------------b8b7-----------------------b0 · FNC270-FNC276 Ex-Device
Page 632 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Applicable devices
Page 632 · click to enlarge
Page 632

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.7 FNC206 – MIDR / Random Selection of Character Strings

26.7 FNC206 – MIDR / Random Selection of Character Strings

Outline

This instruction extracts a specified number of characters from arbitrary positions of a specified character string.

→ For handling of character strings, refer to Section 5.3.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 632)
Fig. 621 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 632)
Fig. 622 · 2. Set data

Character string Head device number storing extracted character string

Head device number specifying the head position and number of characters to be extracted

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 632)
Fig. 623 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

3

Page 633 of the Mitsubishi Electronics MELSEC FX3S user manual — 44H(D) 43H(C)
Page 633 · click to enlarge
Page 633

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.7 FNC206 – MIDR / Random Selection of Character Strings 21

Explanation of function and operation

FNC160-FNC169 Real Time Clock Control

1. 16-bit operation (MIDR and MIDRP)

" +1" characters are extracted leftward from the position specified by of the character string data stored

S 2 S 2

in and later, and stored to and later. When characters are extracted from a character string, "00H" is automatically added at the end of the extracted characters.

S 1 D

- When the number of extracted characters specified by +1 is odd, "00H" is stored in the high-order byte of a device storing the last character.

- When the number of extracted characters specified by +1 is even, "0000H" is stored in the device after the last character.

MIDR S1 ‚ D ‚ S2 ‚

1st character Target character string (extraction source) Extracted character string

42H(B) 41H(A)

46H(F) 45H(E)

44H(D) 43H(C)

48H(H) 47H(G)

46H(F) 45H(E)

00H "EFGHI"

49H(I)

48H(H)

47H(G)

4AH(J)

49H(I)

S1 ‚ 5 characters starting from 5th character +1

00H 4BH(K)

"ABCDEFGHIJK"

FNC190-FNC199 Block Data Operation

  • A character string stored in and later indicates data stored in devices from the specified device until “00H” is first detected in units of byte.

FNC200-FNC209 Character String Control

  • When the number of characters to be extracted specified by +1 is “0”, the extraction processing is not executed.
  • When the number of characters to be extracted specified by +1 is “-1”, the entire character string stored in

S 1 D

and later is stored to and later.

42H(B) 41H(A)

46H(F) 45H(E)

FNC210-FNC219 Data Operation 3

44H(D) 43H(C)

48H(H) 47H(G)

46H(F) 45H(E)

4AH(J) 49H(I)

48H(H)

47H(G)

00H +3 D ‚

4BH(K)

4AH(J) 49H(I)

“FEGHIJK”

S 1 ‚ S 2 ‚

00H

4BH(K)

“ABCDEFGHIJK”

Cautions

FNC250-FNC269 Data Table Operation

When handling character codes other than ASCII codes, note the following contents:

  • The number of characters is handled in byte units (8 bits). Accordingly, in the case of character codes in which 2 bytes express 1 character such as shift JIS code, the length of 1 character is regarded as 2 characters.
  • When extracting characters from a character string including character codes in which 2 bytes express 1 character such as shift JIS codes, consider the number of characters to be extracted in units of character codes for 1 character. Note that the expected character code is not given if only 1 byte is executed out of a 2-byte character code.
Show 30 more labels / short text on this page
FNC170-FNC179 External Device · Command · input · FNC180 Alternate Instructions · b15-----------------b8b7-------------------b0 · b15------------------b8b7-------------------b0 · FNC181-FNC189 Others · +1 · +1 · +2 · +2 · +3 · 5th character · +4 · +5 · +1 · b15-----------------b8 · b7-------------------b0 · b15-----------------b8b7-------------------b0 · +1 · +1 · +2 · +2 · +3 · +4 · +5 · 5th character · FNC220-FNC249 Data Comparison · +1 · FNC270-FNC276 Ex-Device
Page 634 of the Mitsubishi Electronics MELSEC FX3S user manual — S 2 S 1
Page 634 · click to enlarge
Page 634

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.7 FNC206 – MIDR / Random Selection of Character Strings

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When “00H” is not set within the corresponding device range after a device specified by (error code: K6706)
  • When the value specified by +1 exceeds the number of characters specified by (error code: K6706)

S 2 S 1

  • When the number of characters specified by +1 from the position specified by exceeds the device

S 2 D

range specified by (error codeK6706)
  • When the number of devices after a device number specified by is smaller than the number of devices

required to store extracted characters as many as the number specified by +1 (that is, when “00H” cannot be stored after all character strings and the last character) (error code: K6706)

  • When specifies a negative value (error code: K6706)
  • When +1 specifies “-2” or less (error code: K6706)
  • When +1 specifies a number larger than the number of characters specified by (error code: K6706)

S 2 S 1

Program example

In the program example shown below, four characters are extracted from the 3rd character from the left end of the character string data stored in D10 and later, and then stored to D0 and later when X000 turns ON.

Mitsubishi Electronics MELSEC FX3S — S 2 S 1 diagram (page 634)
Fig. 624
Page 635 of the Mitsubishi Electronics MELSEC FX3S user manual — 42H(B) 41H(A)
Page 635 · click to enlarge
Page 635

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.8 FNC207 – MIDW / Random Replacement of Character Strings 21

26.8 FNC207 – MIDW / Random Replacement of Character Strings

FNC160-FNC169 Real Time Clock Control

Outline

This instruction replaces the characters in arbitrary positions inside designated character string with a specified character string.

→ For handling of character strings, refer to Section 5.3.

1. Instruction format

P FNC 207

Mnemonic Operation Condition 16-bit Instruction

MIDW

Continuous Operation Pulse (Single) Operation

MIDWP

2. Set data

Operand Type Description Data Type

Head device number storing a character string used in overwriting

Character string Head device number storing character string to be overwritten

Head device number specifying the head position and number of characters to be overwritten

S 2 S 2

: Head character position to be overwritten

+1Number of characters to be overwritten

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC190-FNC199 Block Data Operation

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

3

FNC200-FNC209 Character String Control

Explanation of function and operation

1. 16-bit operation (MIDW and MIDWP)

“ +1” characters are extracted from the left end (that is, the head) of the character string data stored in and later, and stored to the position specified by and later of the character string data stored in and later.

S 2 S 1

S 2 D

FNC210-FNC219 Data Operation 3

MIDW S1 ‚ D ‚ S2 ‚

31H(1) 30H(0)

42H(B) 41H(A)

33H(3) 32H(2)

44H(D) 43H(C)

35H(5) 34H(4)

46H(F) 45H(E)

37H(7) 36H(6)

48H(H) 47H(G)

00H 38H(8)

+4 D ‚ 00H 49H(I)

“ABCDEFGHI”

After execution 6th character

3 Position from the left end in the character string stored in and later Number of characters from the left end in the character string stored in and later

FNC250-FNC269 Data Table Operation

42H(B) 41H(A)

31H(1) 30H(0)

33H(3)

32H(2)

35H(5) 34H(4)

+4 D ‚ 00H 49H(I)

“AB012345I”

Six characters starting from 3rd character (overwritten character string)

Show 35 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 7 steps MIDW · ⎯ ⎯ · FNC180 Alternate Instructions · FNC181-FNC189 Others · 16-bit binary · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input · Before execution · b15---------------b8b7-----------------b0 · b15---------------b8b7-----------------b0 · 1st character · 1st character · 3rd character · +1 · +1 · FNC220-FNC249 Data Comparison · +2 · +2 · +3 · +4 · “012345678” · b15---------------b8b7-----------------b0 · +1 · 3rd character · +1 · +2 · FNC270-FNC276 Ex-Device
Page 636 of the Mitsubishi Electronics MELSEC FX3S user manual — “ABCDEFGHIJK”
Page 636 · click to enlarge
Page 636

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.8 FNC207 – MIDW / Random Replacement of Character Strings

  • The character string stored in and later or and later indicates data stored in devices from the specified device until “00H” is first detected in byte units.

S 1 D

  • When the number of characters to be overwritten specified by +1 is “0”, the overwriting processing is not executed.
  • When the number of characters to be overwritten specified by +1 exceeds the last character of the character

string stored in and later, data is stored up to the last character.

31H(1) 30H(0)

42H(B) 41H(A)

33H(3) 32H(2)

44H(D) 43H(C)

35H(5) 34H(4)

46H(F) 45H(E)

37H(7)

36H(6)

48H(H) 47H(G)

00H 38H(8)

+4 00H

49H(I)

“ABCDEFGHI”

Position from the left end in the character string stored in and later Number of characters from the left end in the character string stored in and later

42H(B) 41H(A)

44H(D) 43H(C)

31H(1) 30H(0)

33H(3)

32H(2)

+4 00H

34H(4)

“ABCD01234”

Characters from the 5th character to the last character are overwritten. Excessive characters, “35H (5)” to “37H (7)” , are not stored.

  • When +1 (the number of characters to be extracted) is “-1”, the entire character string stored in and

S 2 S 1

later is stored to and later.

41H(A)

31H(1) 30H(0)

44H(D) 43H(C)

33H(3) 32H(2) +1

46H(F) 45H(E)

35H(5) 34H(4)

48H(H)

47H(G)

00H

4AH(J) 49H(I)

+5 00H 4BH(K)

D ‚ Position from the left end in the character string stored in and later Number of characters from the left end in the character string stored in and later

“ABCDEFGHIJK”

30H(0)

41H(A)

32H(2) 31H(1)

34H(4) 33H(3)

48H(H)

35H(5)

+4 4AH(J) 49H(I)

+5 00H 4BH(K)

“A012345HIJK”

Six characters from the 2nd character are overwritten.

Show 42 more labels / short text on this page
Before execution · b15---------------b8b7-----------------b0 · b15---------------b8b7-----------------b0 · 1st character · +1 · +1 · 5th character · +2 · +2 · +3 · +3 · +4 · “012345678” · 8th character · After execution · b15---------------b8b7-----------------b0 · +1 8 · +1 · 5th character · +2 · +3 · 2nd character · Before execution · b15---------------b8b7-----------------b0 · 1st character 42H(B) · b15---------------b8b7-----------------b0 · 1st character · +1 · +2 · +2 · +3 · +3 · +4 · “012345” · Last character · 2nd character · After execution · +1 -1 · b15---------------b8b7-----------------b0 · +1 · +2 · +3
Page 637 of the Mitsubishi Electronics MELSEC FX3S user manual — “21FE03”
Page 637 · click to enlarge
Page 637

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.8 FNC207 – MIDW / Random Replacement of Character Strings 21

Cautions

FNC160-FNC169 Real Time Clock Control

This instruction can handle character codes other than ASCII codes, but please note the following:

  • The number of characters is handled in byte units (8 bits). Accordingly, in the case of character codes in which 2 bytes express 1 character such as shift JIS code, the length of 1 character is regarded as 2 characters.
  • When overwriting a character string including character codes in which 2 bytes express 1 character such as shift JIS codes, consider the number of characters to be extracted in units of character codes for 1 character. Note that the expected character code is not given if only 1 byte is overwritten out of a 2-byte character code.

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When “00H” is not set within the corresponding device range after a device specified by or (error code: K6706)

S 1 D

  • When the value specified by exceeds the number of characters of the character string stored in and later (error code: K6706)

S 2 D

  • When the number of characters specified by +1 exceeds the number of characters specified by (error code: K6706)

S 2 S 1

  • When specifies a negative value (error code: K6706)
  • When +1 specifies “-2” or less (error code: K6706)

Program example

In the program example shown below, 4 characters are extracted from the character string data stored in D0 and later, and stored to the 3rd character (from the left end) and later for the character string data stored in D100 and later when X010 turns ON.

FNC190-FNC199 Block Data Operation

D100 FNC207

MIDWP D0

R0

END

Before execution 4th character

FNC200-FNC209 Character String Control

1st character 3rd character

31H(1) 32H(2)

53H(S) 55H(U)

45H(E) 46H(F)

59H(Y) 43H(C)

33H(3) 30H(0)

31H(1) 5AH(Z)

00H

D103 42H(B) 30H(0)

FNC210-FNC219 Data Operation 3

“21FE03”

0000H

R0

“USCYZ10B”

R1 4

53H(S) 55H(U)

31H(1) 32H(2)

45H(E) 46H(F)

42H(B) 30H(0)

0000H

“US21FE0B”

FNC250-FNC269 Data Table Operation

The 1st to 4th characters are stored.

Show 11 more labels / short text on this page
FNC170-FNC179 External Device · FNC180 Alternate Instructions · FNC181-FNC189 Others · b15---------------b8b7-----------------b0 · b15---------------b8b7-----------------b0 · 1st character · After execution · b15---------------b8b7-----------------b0 · FNC220-FNC249 Data Comparison · 3rd character · FNC270-FNC276 Ex-Device
Page 638 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 2
Page 638 · click to enlarge
Page 638

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.9 FNC208 – INSTR / Character string search

26.9 FNC208 – INSTR / Character string search

Outline

This instruction searches a specified character string within another character string.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 638)
Fig. 625 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 638)
Fig. 626 · 2. Set data

Head device number storing a character string Character string

Head device number storing a character string to be searched Character string

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 638)
Fig. 627 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 16-bit operation (INSTR and INSTRP)

1. The character string stored in and higher is searched for within the character string and higher. The

S 1 S 2

search begins at the "n"th character from the left end (head character) of and the search result is stored in

Mitsubishi Electronics MELSEC FX3S — S 1 S 2 diagram (page 638)
Fig. 628

. The search result provides the first matching character (located from the left end (head character)) in

INSTR S2 ‚ S1 ‚ D ‚ n

Search is started from the 3rd character (n = 3). Fifth character from the head character 46H(F) 48H(H) 45H(E) 47H(G)

The position where the first detected character is located from the head character in the character string data stored in .

2. When the searched character string is not detected, "0" is stored in .
3. When the search start position "n" is a negative number or "0", search processing is not executed.
Page 639 of the Mitsubishi Electronics MELSEC FX3S user manual — R0
Page 639 · click to enlarge
Page 639

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.9 FNC208 – INSTR / Character string search 21

4. A character string can be directly specified in the character string .

FNC160-FNC169 Real Time Clock Control

Character string Character string to be searched S1‚ S2‚

"AB"

32H(2) 34H(4)

31H(1) 33H(3)

Search is started from the 3rd character (n = 3). Fifth character from the head character

42H(B) 41H(A)

36H(6)

35H(5) 42H(B) 41H(A)

00H

"1234AB56AB"

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When the search start position "n" exceeds the number of characters stored in (error code: K6706)
  • When "00H (NULL)" is not located within the corresponding device range starting from (error code: K6706)
  • When "00H (NULL)" is not located within the corresponding device range starting from (error code: K6706)

Program example

1. In the program example below, the character string "CI23" (D0 and later) is searched from the 5th character from the left end (head character) of the character string "CI2312CIM" (R0 and later) when X000 is set to ON. The search result is stored in D100

X000 FNC208

FNC190-FNC199 Block Data Operation

INSTR D0 R0 D100 K5

END

Character string to be searched R0 Character string D0

b15 b8 b7 b0

FNC200-FNC209 Character String Control

These characters are not searched because the search start position is "5". The search source character string is searched from the 5th character.

R0

49H(I) 33H(3) 43H(C) 32H(2)

49H(I) 33H(3) 43H(C) 32H(2) 00H

R1

D1 D2

R2 R3 R4

32H(2) 49H(I) 31H(1) 43H(C)

"CI23"

00H 4DH(M)

"CI2312CIM"

FNC210-FNC219 Data Operation 3

0 Because the searched character string is not detected, "0" is stored.

FNC250-FNC269 Data Table Operation

Show 13 more labels / short text on this page
b15 · b8 b7 b0 · +0 · +1 · +2 +3 +4 · FNC170-FNC179 External Device · +5 · FNC180 Alternate Instructions · FNC181-FNC189 Others · b15 · b8 b7 b0 · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 640 of the Mitsubishi Electronics MELSEC FX3S user manual — $MOV D10 D11
Page 640 · click to enlarge
Page 640

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.10 FNC209 – $MOV / Character String Transfer

26.10 FNC209 – $MOV / Character String Transfer

Outline

This instruction transfers character string data.

→ For handling of character strings, refer to Section 5.3.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 640)
Fig. 629 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 640)
Fig. 630 · 2. Set data

Directly specified character string (up to 32 characters) or head device number storing character string which is handled as the transfer source Character string Head device number storing transferred character string

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 640)
Fig. 631 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

Explanation of function and operation

1. 16-bit operation ($MOV and $MOVP)

The character string data stored in the device specified by and later is transferred to the device specified by

and later.

From the device number specified by to a device after that which stores “00H” in its high-order or low-order byte are transferred at one time.

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 640)
Fig. 632 · Explanation of function and operation

Even if the device range “ to +n” storing the transfer source character string data overlaps the device

range “ to +n/2” storing the transferred character string data, transfer is executed. For example, when a character string stored in D10 to D13 is transferred to D11 to D14, the transfer is executed as shown below:

$MOV D10 D11

Command · input

Page 641 of the Mitsubishi Electronics MELSEC FX3S user manual — D10 4DH(M)
Page 641 · click to enlarge
Page 641

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

26 Character String Control – FNC200 to FNC209

26.10 FNC209 – $MOV / Character String Transfer 21

FNC160-FNC169 Real Time Clock Control

b15 b8 b7 b0

b15 b8 b7 b0

D10 32H(2)

31H(1)

D10 32H(2)

31H(1)

It is the same as the character string before transfer.

34H(4)

33H(3)

32H(2) 31H(1)

36H(6)

35H(5)

34H(4)

33H(3)

00H

36H(6)

35H(5)

0000H

Caution

When “00H” is stored in the low-order byte of +n, “00H” is stored to both the high-order byte and low-order byte

of +n.

$MOV S ‚ D ‚

b15 b8 b7 b0

b15 b8 b7 b0

42H(B)

41H(A)

42H(B)

41H(A)

44H(D)

43H(C)

44H(D)

43H(C)

45H(E)

00H

00H

00H

The high-order byte is not transferred.

“00H” is automatically stored in the high-order byte.

FNC190-FNC199 Block Data Operation

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

FNC200-FNC209 Character String Control

  • When “00H” does not exist in the range specified from device (error code: K6706)
  • When the specified character string cannot be stored in devices from the device specified by to the last device (error code: K6706)

Program example

In the program example shown below, character string data stored in D10 to D12 is transferred to D20 through D22.

FNC210-FNC219 Data Operation 3

X000 FNC209

$MOV D10 D20

END

b15 b8 b7 b0

b15 b8 b7 b0

D10 4DH(M)

2AH(*)

4DH(M)

2AH(*)

45H(E)

45H(E)

45H(E)

45H(E)

00H

0000H

FNC250-FNC269 Data Table Operation

Show 7 more labels / short text on this page
FNC170-FNC179 External Device · FNC180 Alternate Instructions · Command · input · FNC181-FNC189 Others · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 642 of the Mitsubishi Electronics MELSEC FX3S user manual — 27. Data Operation 3 – FNC210 to FNC219
Page 642 · click to enlarge
Page 642

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

27 Data Operation 3 – FNC210 to FNC219

27. Data Operation 3 – FNC210 to FNC219

FNC210 to FNC219 provide instructions for reading last-in data and controlling leftward/rightward shift instructions with carry.

Mitsubishi Electronics MELSEC FX3S — 27. Data Operation 3 – FNC210 to FNC219 diagram (page 642)
Fig. 633 · 27. Data Operation 3 – FNC210 to FNC219

212 POP Shift Last Data Read [FILO Control] Section 27.3

213 SFR 16-bit data n Bit Shift Right with Carry Section 27.4

214 SFL 16-bit data n Bit Shift Left with Carry Section 27.5

Page 643 of the Mitsubishi Electronics MELSEC FX3S user manual — Related instruction
Page 643 · click to enlarge
Page 643

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

27 Data Operation 3 – FNC210 to FNC219

27.1 FNC210 – FDEL / Deleting Data from Tables 21

27.1 FNC210 – FDEL / Deleting Data from Tables

FNC160-FNC169 Real Time Clock Control

Outline

This instruction deletes an arbitrary data value from a data table.

1. Instruction format

⎯ ⎯ P FNC 210

Mnemonic Operation Condition 16-bit Instruction

FDEL

Continuous Operation Pulse (Single) Operation

FDELP

2. Set data

Operand Type Description Data Type

Device number storing deleted data value

16-bit binary Head device number in data table

n Position of deleted data in table

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FNC190-FNC199 Block Data Operation

3

3

n 3

Explanation of function and operation

FNC200-FNC209 Character String Control

1. 16-bit operation (FDEL and FDELP)

The "n"th data value is deleted from a data table (stored in and later), and the deleted value is stored in . "n+1"th data value and later in the data table are shifted forward one by one, and the number of stored data is subtracted by "−1".

D S

FDELP S ‚ D ‚ n

FNC210-FNC219 Data Operation 3

Number of stored data Number of stored data

When "n" is "2"

Device range used in data table

Data table (having data starting from +1)

"0" is stored.

Deleted data S‚

FNC250-FNC269 Data Table Operation

Caution

The device range used in a data table should be controlled by the user. The data table has number of stored data starting from ( +1).

D D

→ Refer to the program example.

Related instruction

FINS (FNC211) Inserts data into an arbitrary position in a data table.

Show 30 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 7 steps FDEL · FNC180 Alternate Instructions · FNC181-FNC189 Others · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input FNC210 · Data table · Data table · +0 · +0 · +1 · +1 · +2 +3 +4 · 3333 4444 · +2 +3 +4 · 4444 1234 · Data table range · FNC220-FNC249 Data Comparison · 1234 5678 · +5 · +5 · FNC270-FNC276 Ex-Device · Instruction Description
Page 644 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 644 · click to enlarge
Page 644

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

27 Data Operation 3 – FNC210 to FNC219

27.1 FNC210 – FDEL / Deleting Data from Tables

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When the table position "n" of the data to be deleted exceeds the amount of data stored (error code: K6706)
  • When the value "n" exceeds the device range of the data table (error code: K6706)
  • When the FDEL (FNC210) instruction is executed under the condition "n ≤ 0" (error code: K6706)
  • When the amount of data stored specified in is "0" (error code: K6706)
  • When the data table range exceeds the corresponding device range (error code: K6706)

Program example

In the program shown below, the 2nd data value entry is deleted from the data table stored in D100 to D105, and the deleted data is stored in D0. When the amount of data stored is "0", however, the FDEL (FNC210) instruction is not executed. (The device range used in the data table is D100 to D107).

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 644)
Fig. 634 · Program example

Amount of data stored D101 D102 D103 D104 D105 D106 D107

Data table range Device range used in data table

Page 645 of the Mitsubishi Electronics MELSEC FX3S user manual — 27.2 FNC211 – FINS / Inserting Data to Tables
Page 645 · click to enlarge
Page 645

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

27 Data Operation 3 – FNC210 to FNC219

27.2 FNC211 – FINS / Inserting Data to Tables 21

Mitsubishi Electronics MELSEC FX3S — 27.2 FNC211 – FINS / Inserting Data to Tables 21 diagram (page 645)
Fig. 635 · 27.2 FNC211 – FINS / Inserting Data to Tables 21

27.2 FNC211 – FINS / Inserting Data to Tables

This instruction inserts a data value into an arbitrary position in a data table.

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

16-bit data is inserted in the "n"th position in a data table (stored in and later). "n"th data and later in the data table are shifted backward one by one, and the number of stored data is added by "1".

Data table range Device range used in data table

The device range used in a data table should be controlled by the user. The data table has number of stored data starting from ( +1).

FDEL (FNC210) Deletes an arbitrary data entry from a data table.

Page 646 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 646 · click to enlarge
Page 646

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

27 Data Operation 3 – FNC210 to FNC219

27.2 FNC211 – FINS / Inserting Data to Tables

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When the table position "n" for data insertion exceeds the amount of stored data plus 1 (error code: K6706)
  • When the value "n" exceeds the device range of the data table (error code: K6706)
  • When FNC211 instruction is executed under the condition "n ≤ 0" (error code: K6706)
  • When the data table range exceeds the corresponding device range (error code: K6706)

Program example

In the program shown below, data stored in D100 is inserted into the 3rd position of the data table stored in D0 to D4. When the amount of data stored exceeds "7", however, the FINS (FNC211) instruction is not executed. (The device range used in the data table is D0 to D7).

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 646)
Fig. 636 · Program example

Amount of data stored D0 D1 D2 D3 D4 D5 D6 D7

Data table range Device range used in data table

Page 647 of the Mitsubishi Electronics MELSEC FX3S user manual — S S S
Page 647 · click to enlarge
Page 647

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

27 Data Operation 3 – FNC210 to FNC219

27.3 FNC212 – POP / Shift Last Data Read [FILO Control] 21

27.3 FNC212 – POP / Shift Last Data Read [FILO Control]

FNC160-FNC169 Real Time Clock Control

Outline

This instruction reads the last data written by a shift write (SFWR) instruction for FILO control.

→ For SFWR (FNC 38) instruction, refer to Section 11.9.

1. Instruction format

⎯ ⎯ P FNC 212

Mnemonic Operation Condition 16-bit Instruction

POP

Continuous Operation Pulse (Single) Operation

POPP

2. Set data

Operand Type Description Data Type

Head device number storing first-in data (including pointer data)

16-bit binary Device number storing last-out data

Length of data array (Add "1" because pointer data is also included.) 2 ≤ n ≤ 512

3. Applicable devices

Bit Devices Word Devices Others

FNC190-FNC199 Block Data Operation

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

FNC200-FNC209 Character String Control

Explanation of function and operation

1. 16-bit operation (POP and POPP)

FNC210-FNC219 Data Operation 3

POPP S ‚ D ‚ n

Data for FILO control

Pointer data (amount of data stored)

Data area (First-in data written by shift write (SFWR) instruction)

FNC250-FNC269 Data Table Operation

  • Every time the instruction is executed for the word devices to +n-1, a device “ + Pointer data

S S S

S D

” is read to . (The last data entry written by the shift write (SFWR) instruction for first-in first-out control

is read to .) Specify “n” ranging from “2” to “512”.

Show 24 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 7 steps POP · FNC180 Alternate Instructions · FNC181-FNC189 Others · n · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · n 3 3 · Command · input · Description · FNC220-FNC249 Data Comparison · +1 · +2 · +3 · +n-3 · +n-2 · +n-1 · FNC270-FNC276 Ex-Device
Page 648 of the Mitsubishi Electronics MELSEC FX3S user manual — S S
Page 648 · click to enlarge
Page 648

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

27 Data Operation 3 – FNC210 to FNC219

27.3 FNC212 – POP / Shift Last Data Read [FILO Control]

  • Subtract “1” from the value of the pointer data .
Mitsubishi Electronics MELSEC FX3S — 27.3 FNC212 – POP / Shift Last Data Read [FILO Control] diagram (page 648)
Fig. 637 · 27.3 FNC212 – POP / Shift Last Data Read [FILO Contr…

S ‚ +n-2 S ‚ +n-1 S ‚ +6 S ‚ +5 S ‚ +3 S ‚ +2 S ‚ +1 S ‚

S ‚ +n-2 S ‚ +n-1 S ‚ +6 S ‚ +5 S ‚ +3 S ‚ +2 S ‚ +1 S ‚ D ‚

Related device

→ For the zero flag use method, refer to Subsection 6.5.2.

M8020 Zero flag Turns ON when the instruction is executed while the pointer is “0”.

Related instructions

SFWR (FNC 38) Shift write [for FIFO/FILO control]

SFRD (FNC 39) Shift read [for FIFO control]

Cautions

  • When this instruction is programmed in the continuous operation type, the instruction is executed in every operation cycle. As a result, an expected operation may not be achieved. Usually, program this instruction in the “pulse operation type”, or let this instruction be executed by a “pulsed command contact”.
  • When the current value of the pointer is “0”, the zero flag M8020 turns ON and the instruction is not executed.

Check in advance using a comparison instruction whether the current value of satisfies “1 ≤ ≤ n-1”, and then execute this instruction.

S S

  • When the current value of the pointer is “1”, “0” is written to and the zero flag M8020 turns ON.

S S

Error

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When is larger than “n-1” (error code: K6706)
  • When is smaller than “0” (error code: K6706)

Device Name Description · Instruction Description

Page 649 of the Mitsubishi Electronics MELSEC FX3S user manual — 27.3 FNC212 – POP / Shift Last Data Read [FILO Control] 21
Page 649 · click to enlarge
Page 649

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

27 Data Operation 3 – FNC210 to FNC219

27.3 FNC212 – POP / Shift Last Data Read [FILO Control] 21

Mitsubishi Electronics MELSEC FX3S — 27.3 FNC212 – POP / Shift Last Data Read [FILO Control] 21 diagram (page 649)
Fig. 638 · 27.3 FNC212 – POP / Shift Last Data Read [FILO Contr…

Among values stored in D20 input first to D101 to D106, the last value input is stored to D10, and “1” is subtracted from the number of stored data (pointer D100) every time X000 turns ON.

When the first-in data is as shown in the table below

H0000 H0000 H0000 HABCD H5678 H1234 K3→K2

Page 650 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 650 · click to enlarge
Page 650

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

27 Data Operation 3 – FNC210 to FNC219

27.4 FNC213 – SFR / Bit Shift Right with Carry

27.4 FNC213 – SFR / Bit Shift Right with Carry

Outline

This instruction shifts 16 bits stored in a word device rightward by “n” bits.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 650)
Fig. 639 · 1. Instruction format

2. Set data

Operand Type Description Data Type

Device number storing data to be shifted

16-bit binary n Number of times of shift (0 ≤ n ≤ 15)

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 650)
Fig. 640 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

n 3

Explanation of function and operation

1. 16-bit operation (SFR and SFRP)

SFRP D ‚ n

1. 16 bits stored in a word device are shifted rightward by “n” bits. Specify a value ranging from “0” to “15” as “n”. If “16” or larger value is specified as “n”, 16 bits are shifted rightward by the remainder of “n/16”. For example, when “n” is set to “18”, 16 bits are shifted rightward by 2 bits (18/16 = 1 ... 2).
2. The ON (1)/OFF (0) status of the “n”th bit (bit “n-1”) in the word device is transferred to the carry flag M8022.
3. “0” is set to “n” bits from the most significant bit.
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 650)
Fig. 641 · Explanation of function and operation

Command · input

Page 651 of the Mitsubishi Electronics MELSEC FX3S user manual — M8022
Page 651 · click to enlarge
Page 651

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

27 Data Operation 3 – FNC210 to FNC219

27.4 FNC213 – SFR / Bit Shift Right with Carry 21

When a bit device is specified by digit specification 4°K bits are shifted according to the data bit specification.

FNC160-FNC169 Real Time Clock Control

SFRP K3M0 K4

1 M11

0 1 0 M8

M7 M4 M3 M0

1 0 1 0 1 0 1 0

0 1 0 1 0 1 0 1 0 M11 M8 M7 M4 M3 M0

M8022

Become “0”.

Related device

→ For the carry flag use method, refer to Subsection 6.5.2.

M8022 Carry flag Shifts the ON/OFF status of bit “n-1”.

Error

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

FNC190-FNC199 Block Data Operation

  • When a negative value is set to “n” (error code: K6706)

Program example

In the program example shown below, the contents of Y010 to Y023 are shifted rightward by the number of bits specified by D0 when X020 turns ON.

FNC200-FNC209 Character String Control

X020 FNC213

SFRP K3Y010 D0

END

FNC210-FNC219 Data Operation 3

1 Y23

0 1 0 Y20

Y17 Y14 Y13 Y10

1 0 1 0 1 0 1 0

0 1 0 1 0 1 0 1 0 Y23 Y20 Y17 Y14 Y13 Y10

M8022

Become “0”.

FNC250-FNC269 Data Table Operation

Show 10 more labels / short text on this page
Command · input · FNC170-FNC179 External Device · Carry flag · FNC180 Alternate Instructions · FNC181-FNC189 Others · Device Name Description · Carry flag · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 652 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 652 · click to enlarge
Page 652

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

27 Data Operation 3 – FNC210 to FNC219

27.5 FNC214 – SFL / Bit Shift Left with Carry

27.5 FNC214 – SFL / Bit Shift Left with Carry

Outline

This instruction shifts 16 bits stored in a word device leftward by “n” bits.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 652)
Fig. 642 · 1. Instruction format

2. Set data

Operand Type Description Data Type

Device number storing data to be shifted

16-bit binary n Number of times of shift (0 ≤ n ≤ 15)

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 652)
Fig. 643 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

n 3

Explanation of function and operation

1. 16-bit operation (SFL and SFLP)

SFLP D ‚ n

1. 16 bits stored in a word device are shifted leftward by “n” bits. Specify a value ranging from “0” to “15” as “n”. If “16” or larger value is specified as “n”, 16 bits are shifted leftward by the remainder of “n/16”. For example, when “n” is set to “18”, 16 bits are shifted leftward by 2 bits (18/16 = 1 ... 2).
2. The ON (1)/OFF (0) status of the “n+1”th bit (bit “n”) in the word device is transferred to the carry flag M8022.
3. “0” is set to “n” bits from the least significant bit.
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 652)
Fig. 644 · Explanation of function and operation

Command · input

Page 653 of the Mitsubishi Electronics MELSEC FX3S user manual — 27.5 FNC214 – SFL / Bit Shift Left with Carry 21
Page 653 · click to enlarge
Page 653

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

27 Data Operation 3 – FNC210 to FNC219

27.5 FNC214 – SFL / Bit Shift Left with Carry 21

Mitsubishi Electronics MELSEC FX3S — 27.5 FNC214 – SFL / Bit Shift Left with Carry 21 diagram (page 653)
Fig. 645 · 27.5 FNC214 – SFL / Bit Shift Left with Carry 21

When a bit device is specified by digit specification 4°K bits are shifted according to the data of bit specification.

1 0 0 1 1 0 0 0 1

→ For the carry flag use method, refer to Subsection 6.5.2.

M8022 Carry flag Shifts the ON/OFF status of bit “n”.

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When a negative value is set to “n” (error code: K6706)

In the program example shown below, the contents of Y010 to Y017 are shifted leftward by the number of bits specified by D0 when X020 turns ON.

1 0 0 1 1 0 0 0 1

Page 654 of the Mitsubishi Electronics MELSEC FX3S user manual — 28. Data Comparison – FNC220 to FNC249
Page 654 · click to enlarge
Page 654

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

28 Data Comparison – FNC220 to FNC249

28. Data Comparison – FNC220 to FNC249

FNC220 to FNC249 provide data comparison instructions which can be handled as contact symbols in programming such as LD, AND and OR.

Mitsubishi Electronics MELSEC FX3S — 28. Data Comparison – FNC220 to FNC249 diagram (page 654)
Fig. 646 · 28. Data Comparison – FNC220 to FNC249
Page 655 of the Mitsubishi Electronics MELSEC FX3S user manual — 28. Data Comparison – FNC220 to FNC249
Page 655 · click to enlarge
Page 655

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

28 Data Comparison – FNC220 to FNC249

Mitsubishi Electronics MELSEC FX3S — 28. Data Comparison – FNC220 to FNC249 diagram (page 655)
Fig. 647 · 28. Data Comparison – FNC220 to FNC249
Page 656 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Applicable devices (common among FNC224 to FNC230)
Page 656 · click to enlarge
Page 656

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

28 Data Comparison – FNC220 to FNC249

28.1 FNC224~230 – LD =, >, <, <>, <=, >= / Data Comparison

28.1 FNC224~230 – LD =, >, <, <>, <=, >= / Data Comparison

Outline

These instructions compare numeric values, and set a contact to ON when the condition agrees so that an operation is started.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 656)
Fig. 648 · 1. Instruction format

2. Set data (common among FNC224 to FNC230)

Operand Type Description Data Type

Device number storing comparison data 16- or 32-bit binary

Device number storing comparison data 16- or 32-bit binary

3. Applicable devices (common among FNC224 to FNC230)

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices (common among FNC224 to FNC230) diagram (page 656)
Fig. 649 · 3. Applicable devices (common among FNC224 to FNC230…

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Page 657 of the Mitsubishi Electronics MELSEC FX3S user manual — LDD> K678493 M50
Page 657 · click to enlarge
Page 657

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

28 Data Comparison – FNC220 to FNC249

28.1 FNC224~230 – LD =, >, <, <>, <=, >= / Data Comparison 21

Explanation of function and operation

FNC160-FNC169 Real Time Clock Control

FNC224 to FNC230 are data comparison instructions connected to bus lines. The contents of are compared with the contents of in binary format, and a contact becomes conductive (ON) or non-conductive (OFF) depending on the comparison result.

S 1 S 2

FNC No. 16-bit instruction 32-bit instruction ON condition OFF condition

224 LD= LDD= = ≠

S 1 S 2 S 1 S 2

225 LD> LDD> > <=

S 1 S 2 S 1 S 2

226 LD< LDD< < >=

S 1 S 2 S 1 S 2

228 LD<> LDD<> ≠ =

S 1 S 2 S 1 S 2

229 LD<= LDD<= <= >

S 1 S 2 S 1 S 2

230 LD>= LDD>= >= <

S 1 S 2 S 1 S 2

Cautions

1. Negative value

  • When the most significant bit is "1" in the data stored in or , it is regarded as a negative value in comparison.
  • In the 16-bit operation: bit 15
  • In the 32-bit operation: bit 31

S 1 S 2

2. When using 32-bit counters (including 32-bit high-speed counters) Make sure to execute the 32-bit operation (such as "LDD=", "LDD>" and "LDD" and "LD
3. Programming of data comparison instructions When programming in GX Works2 and GX Developer, symbols " ≤ " and " ≥ " cannot be input. Separate " ≤ " into "" and "=".

FNC190-FNC199 Block Data Operation

<Input example for 16-bit operation>

Mitsubishi Electronics MELSEC FX3S — <Input example for 16-bit operation> diagram (page 657)
Fig. 650 · <Input example for 16-bit operation>

FNC200-FNC209 Character String Control

<Input example for 32-bit operation>

Mitsubishi Electronics MELSEC FX3S — <Input example for 32-bit operation> diagram (page 657)
Fig. 651 · <Input example for 32-bit operation>

FNC210-FNC219 Data Operation 3

Program example

S 1 S 2

C10 FNC224

When the current value of the counter C10 is "200", Y010 is driven.

LD= K200

Y10

K-30 FNC225

When the contents of D200 are "-29" or higher and X001 is ON, Y011 is set.

LD> D200

SET Y11

FNC250-FNC269 Data Table Operation

C200 FNC225

When the contents of the counter C200 are less than "K678,493" or when M3 turns ON, M50 is driven.

LDD> K678493 M50

M3

Show 5 more labels / short text on this page
FNC170-FNC179 External Device · FNC180 Alternate Instructions · FNC181-FNC189 Others · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 658 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Applicable devices (common among FNC232 to FNC238)
Page 658 · click to enlarge
Page 658

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

28 Data Comparison – FNC220 to FNC249

28.2 FNC232~238 – AND=, >, <, < >, <=, >= / Data Comparison

28.2 FNC232~238 – AND=, >, <, < >, <=, >= / Data Comparison

Outline

These instructions compare numeric values, and set a contact to ON when the condition agrees.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 658)
Fig. 652 · 1. Instruction format

2. Set data (common among FNC232 to FNC238)

Operand Type Description Data Type

Device number storing comparison data 16- or 32-bit binary

Device number storing comparison data 16- or 32-bit binary

3. Applicable devices (common among FNC232 to FNC238)

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices (common among FNC232 to FNC238) diagram (page 658)
Fig. 653 · 3. Applicable devices (common among FNC232 to FNC238…

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Page 659 of the Mitsubishi Electronics MELSEC FX3S user manual — D10 FNC233
Page 659 · click to enlarge
Page 659

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

28 Data Comparison – FNC220 to FNC249

28.2 FNC232~238 – AND=, >, <, < >, <=, >= / Data Comparison 21

Explanation of function and operation

FNC160-FNC169 Real Time Clock Control

FNC232 to FNC237 are data comparison instructions connected to other contacts in series. The contents of are compared with the contents of in binary format, and a contact becomes conductive (ON) or non-conductive (OFF) depending on the comparison result.

S 1 S 2

FNC No. 16-bit instruction 32-bit instruction ON condition OFF condition

232 AND= ANDD= = ≠

S 1 S 2 S 1 S 2

233 AND> ANDD> > <=

S 1 S 2 S 1 S 2

234 AND< ANDD< < >=

S 1 S 2 S 1 S 2

236 AND<> ANDD<> ≠ =

S 1 S 2 S 1 S 2

237 AND<= ANDD<= <= <

S 1 S 2 S 1 S 2

238 AND>= ANDD>= >= >

S 1 S 2 S 1 S 2

Cautions

  • 1. Negative value When the most significant bit is "1" in the data stored in or , it is regarded as a negative value in comparison.
  • In the 16-bit operation: bit 15
  • In the 32-bit operation: bit 31

S 1 S 2

2. When using 32-bit counters (including 32-bit high-speed counters) Make sure to execute the 32-bit operation (such as "ANDD=", "ANDD>" and "ANDD" and "AND
3. Programming of data comparison instructions When programming in GX Works2 and GX Developer, symbols " ≤ " and " ≥ " cannot be input. Separate " ≤ " into "" and "=".

FNC190-FNC199 Block Data Operation

<Input example for 16-bit operation>

Mitsubishi Electronics MELSEC FX3S — <Input example for 16-bit operation> diagram (page 659)
Fig. 654 · <Input example for 16-bit operation>

FNC200-FNC209 Character String Control

<Input example for 32-bit operation>

Mitsubishi Electronics MELSEC FX3S — <Input example for 32-bit operation> diagram (page 659)
Fig. 655 · <Input example for 32-bit operation>

FNC210-FNC219 Data Operation 3

Program example

S 1 S 2

C10 FNC232

AND= K200 Y10

When X000 is ON and the current value of the counter C10 is "200" Y010 is driven.

When X001 is OFF and the contents of the data register D0 are not "-10", Y011 is set.

D0 FNC236

AND<> K-10

SET Y11

FNC250-FNC269 Data Table Operation

When X002 is ON, and the contents of the data registers D11 and D10 are less than "K678,493", or when M3 turns ON, M50 is driven.

D10 FNC233

ANDD> K678493 M50

M3

Show 5 more labels / short text on this page
FNC170-FNC179 External Device · FNC180 Alternate Instructions · FNC181-FNC189 Others · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 660 of the Mitsubishi Electronics MELSEC FX3S user manual — 3. Applicable devices (common among FNC240 to FNC246)
Page 660 · click to enlarge
Page 660

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

28 Data Comparison – FNC220 to FNC249

28.3 FNC240~246 – OR=, >, <, < >, <=, >= / Data Comparison

28.3 FNC240~246 – OR=, >, <, < >, <=, >= / Data Comparison

Outline

These instructions compare numeric values, and set a contact to ON when the condition agrees.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 660)
Fig. 656 · 1. Instruction format

2. Set data (common among FNC240 to FNC246)

Operand Type Description Data Type

Device number storing comparison data 16- or 32-bit binary

Device number storing comparison data 16- or 32-bit binary

3. Applicable devices (common among FNC240 to FNC246)

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices (common among FNC240 to FNC246) diagram (page 660)
Fig. 657 · 3. Applicable devices (common among FNC240 to FNC246…

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S1 S2 3

3 S1 S2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Page 661 of the Mitsubishi Electronics MELSEC FX3S user manual — K100000 FNC246
Page 661 · click to enlarge
Page 661

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

28 Data Comparison – FNC220 to FNC249

28.3 FNC240~246 – OR=, >, <, < >, <=, >= / Data Comparison 21

Explanation of function and operation

FNC160-FNC169 Real Time Clock Control

FNC240 to 246 are data comparison instructions connected to other contacts in parallel. The contents of are compared with the contents of in binary format, and a contact becomes conductive (ON) or non-conductive (OFF) depending on the comparison result.

S 1 S 2

FNC No. 16-bit instruction 32-bit instruction ON condition OFF condition

240 OR= ORD= = ≠

S 1 S 2 S 1 S 2

241 OR> ORD> > <=

S 1 S 2 S 1 S 2

242 OR< ORD< < >=

S 1 S 2 S 1 S 2

244 OR<> ORD<> ≠ =

S 1 S 2 S 1 S 2

245 OR<= ORD<= <= >

S 1 S 2 S 1 S 2

246 OR>= ORD>= >= <

S 1 S 2 S 1 S 2

Cautions

  • 1. Negative value When the most significant bit is "1" in the data stored in or , it is regarded as a negative value in comparison.
  • In the 16-bit operation: bit 15
  • In the 32-bit operation: bit 31

S 1 S 2

2. When using 32-bit counters (including 32-bit high-speed counters) Make sure to execute the 32-bit operation (such as "ORD=", "ORD>" and "ORD" and "OR
3. Programming of data comparison instructions When programming in GX Works2 and GX Developer, symbols " ≤ " and " ≥ " cannot be input. Separate " ≤ " into "" and "=".

FNC190-FNC199 Block Data Operation

<Input example for 16-bit operation>

Mitsubishi Electronics MELSEC FX3S — <Input example for 16-bit operation> diagram (page 661)
Fig. 658 · <Input example for 16-bit operation>

FNC200-FNC209 Character String Control

<Input example for 32-bit operation>

Mitsubishi Electronics MELSEC FX3S — <Input example for 32-bit operation> diagram (page 661)
Fig. 659 · <Input example for 32-bit operation>

FNC210-FNC219 Data Operation 3

Program example

Y000 X001

When X001 turns ON or when the current value of the counter C10 is "200", Y000 is driven.

S 1 ‚ S 2 ‚

C10 FNC240

OR= K200

FNC250-FNC269 Data Table Operation

M60 M30 X002

When X002 and M30 turn ON or when the contents of the data registers D101 and D100 are more than "K100,000" M60 is driven.

K100000 FNC246

ORD>= D100

Show 5 more labels / short text on this page
FNC170-FNC179 External Device · FNC180 Alternate Instructions · FNC181-FNC189 Others · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 662 of the Mitsubishi Electronics MELSEC FX3S user manual — 29. Data Table Operation – FNC250 to FNC269
Page 662 · click to enlarge
Page 662

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29. Data Table Operation – FNC250 to FNC269

Mitsubishi Electronics MELSEC FX3S — 29. Data Table Operation – FNC250 to FNC269 diagram (page 662)
Fig. 660 · 29. Data Table Operation – FNC250 to FNC269

259 SCL Scaling (Coordinate by Point Data) Section 29.4

260 DABIN Decimal ASCII to BIN Conversion Section 29.5

261 BINDA BIN to Decimal ASCII Conversion Section 29.6

269 SCL2 Scaling 2 (Coordinate by X/Y Data) Section 29.7

Page 663 of the Mitsubishi Electronics MELSEC FX3S user manual — S 3 ‚ S 2 ‚
Page 663 · click to enlarge
Page 663

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.1 FNC256 – LIMIT / Limit Control 21

29.1 FNC256 – LIMIT / Limit Control

FNC160-FNC169 Real Time Clock Control

Outline

This instruction provides the upper limit value and lower limit value for an input numeric value, and controls the output value using these limit values.

1. Instruction format

P FNC 256

Mnemonic Operation Condition 16-bit Instruction

LIMIT D

Continuous Operation Pulse (Single) Operation

Continuous Operation Pulse (Single) Operation

LIMITP

DLIMITP

2. Set data

Operand Type Description Data Type

Lower limit value (minimum output value)

16- or 32-bit binary Upper limit value (maximum output value)

Input value controlled by the upper and lower limit values

Head device number storing the output value controlled by the upper and lower limit values

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC190-FNC199 Block Data Operation

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

3

FNC200-FNC209 Character String Control

3

Explanation of function and operation

1. 16-bit operation (LIMIT and LIMITP)

Depending on how the input value (16-bit binary value) specified by compares to the range between

S 3 S 1

FNC210-FNC219 Data Operation 3

and , the output value is controlled. The output value is controlled as shown below:

S 2 D

LIMIT S1 ‚ S2 ‚ D ‚ S3 ‚

‚In the case of “ Lower limit value > Input value” Lower limit value → Output value

S 3 ‚ S 1 ‚ D ‚

‚In the case of “ Upper limit value < Input value” Upper limit value → Output value

S2 ‚ S3 ‚ S2 ‚ D ‚

‚In the case of “ Lower limit value ≤ Input value ≤ Upper limit value” S1 ‚

S 3 ‚ S 2 ‚

Input value → Output value S3 ‚ D ‚

FNC250-FNC269 Data Table Operation

  • When controlling the output value using only the upper limit value, set “-32768” to the lower limit value specified in
Show 25 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 9 steps LIMIT · 17 steps DLIMIT · FNC180 Alternate Instructions · FNC181-FNC189 Others · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input · FNC220-FNC249 Data Comparison · Output · Output value · ( ) · value · Specified · Input value · Input value · ( ) · Specified · FNC270-FNC276 Ex-Device
Page 664 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 1 S 2 S 2
Page 664 · click to enlarge
Page 664

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.1 FNC256 – LIMIT / Limit Control

  • When controlling the output value using only the lower limit value, set “32767” to the upper limit value specified

in .

2. 32-bit operation (DLIMIT and DLIMITP)

Depending on how the input value (32-bit binary value) specified by [ +1, ] compares to the range

S 3 S 3

between [ +1, ] and [ +1, ], the output value [ +1, ] is controlled.

S1 S1 S2 S2 D D

S1 ‚ S2 ‚ S3 ‚ D ‚

DLIMIT

S1 ‚ S1 ‚ S3 ‚ S3 ‚

+1, S 1 ‚ S 1 ‚

D ‚ D ‚

‚In the case of “Lower limit value > Input value” Lower limit value → Output value

S2 ‚ S2 ‚ S3 ‚ S3 ‚

+1, S 2 ‚ S 2 ‚

+1, D ‚ D ‚

‚In the case of “Upper limit value < Input value” Upper limit value → Output value

+1, S1 ‚ S1 ‚ +1, S3 ‚ S3 ‚ S2 ‚ S2 ‚

+1, S 3 ‚ S 3 ‚

+1, D ‚ D ‚

‚In the case of “Lower limit value ≤ Input value ≤ Upper limit value” Input value → Output value

+1, D ‚ D ‚

+1, S 2 ‚ S 2 ‚

+1, S 3 ‚ S 3 ‚

+1, S 1 ‚ S 1 ‚

  • When controlling the output value using only the upper limit value, set “-2,147,483,648” to the lower limit value

specified in [ +1, ].

S 1 S 1

  • When controlling the output value using only the lower limit value, set “2,147,483,647” to the upper limit value

specified in [ +1, ].

S 2 S 2

Error

An operation error is caused when the instruction is executed in the setting status shown below; The error flag M8067 turns ON, and the error code (K6706) is stored in D8067.

S 1 S 2

32-bit operation [ +1, ] ≤ [ +1, ]

S 1 S 1 S 2 S 2

Show 17 more labels / short text on this page
Command · input · +1, +1, +1, · +1, +1, · +1, · Output · Output · value · ( ) · value · Specified · Input value · Input value · ( ) · Specified · Relationship · 16-bit operation ≤
Page 665 of the Mitsubishi Electronics MELSEC FX3S user manual — END
Page 665 · click to enlarge
Page 665

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.1 FNC256 – LIMIT / Limit Control 21

Program examples

FNC160-FNC169 Real Time Clock Control

1. Program example 1 In the program example shown below, the BCD data set in X020 to X037 is controlled by the limit values “500” to “5000”, and the controlled value is output to D1 when X000 turns ON.

K4X020 D0 FNC 19

BIN

K500 K5000 D0 D1 FNC256

LIMIT

END

Operation

  • In the case of “D0 < 500”, “500” is output to D1.
  • In the case of “500 ≤ D0 ≤ 5000”, the value of D0 is output to D1.
  • In the case of “D0 > 5000”, “5000” is output to D1.
2. Program example 2 In the program example shown below, the BCD data set in X020 to X057 is controlled by the limit values “10000” and “1,000,000”, and the controlled value is output to D11 and D10 when X000 turns ON.

FNC190-FNC199 Block Data Operation

K8X020 D0 FNC 19

DBIN

K10000 K1000000 D0 D10 FNC256

DLIMIT

FNC200-FNC209 Character String Control

END

Operation

  • In the case of “(D1, D0) < 10000”, “10000” is output to (D11, D10).
  • In the case of “10000 ≤ (D1, D0) ≤ 1,000,000”, the value of (D1, D0) is output to (D11, D10).

FNC210-FNC219 Data Operation 3

  • In the case of “(D1, D0) > 1,000,000”, “1,000,000” is output to (D11, D10).

FNC250-FNC269 Data Table Operation

Show 12 more labels / short text on this page
FNC170-FNC179 External Device · FNC180 Alternate Instructions · Output (D1) · FNC181-FNC189 Others · Input (D0) · 500 5000 · Output (D11,D10) · 1,000,000 · Input (D1,D0) · 10000 1,000,000 · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 666 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 666 · click to enlarge
Page 666

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.2 FNC257 – BAND / Dead Band Control

29.2 FNC257 – BAND / Dead Band Control

Outline

This instruction provides the upper limit value and lower limit value of the dead band for an input numeric value, and controls the output value using these limit values.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 666)
Fig. 661 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 666)
Fig. 662 · 2. Set data

Lower limit value of the dead band (no-output band)

16- or 32-bit binary Upper limit value of the dead band (no-output band)

Device number storing the output value controlled by the dead band

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 666)
Fig. 663 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

3

3

Explanation of function and operation

1. 16-bit operation (BAND and BANDP)

Depending on how the input value (16-bit binary value) specified by compares to the dead band range between

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 666)
Fig. 664 · Explanation of function and operation

S1 ‚ S2 ‚ D ‚ S3 ‚

S3 ‚ S1 ‚ S3 ‚ S1 ‚

D‚ S3 ‚ S2 ‚ S3 ‚ S2 ‚

D‚ S3 ‚ S1 ‚ S2 ‚

Upper limit value of dead band ( ) S2 ‚ Output value = 0

Page 667 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 1 S 2 S 2
Page 667 · click to enlarge
Page 667

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.2 FNC257 – BAND / Dead Band Control 21

2. 32-bit operation (DBAND and DBANDP)

FNC160-FNC169 Real Time Clock Control

Depending on how the input value (32-bit binary value) specified by [ +1, ] compares to the dead band

S 3 S 3

range between [ +1, ] and [ +1, ], the output value [ +1, ] is controlled. The output value is controlled as shown below:

S1 S1 S2 S2 D D

S1 ‚ S2 ‚ S3 ‚ D ‚

DBAND

S1 ‚ S1 ‚ S3 ‚ S3 ‚

+1,

S 3 ‚ S 3 ‚

S 1 ‚ S 1 ‚

D ‚ D ‚

‚In the case of “Lower limit value > Input value” Input value − Lower limit value → Output value

S2 ‚ S2 ‚ S3 ‚ S3 ‚

S 3 ‚ S 3 ‚

S 2 ‚ S 2 ‚

+1,

D ‚ D ‚

‚In the case of “Upper limit value < Input value” Input value − Upper limit value → Output value

S3 ‚ S3 ‚ S1 ‚ S1 ‚ S2 ‚ S2 ‚

+1,

D ‚ D ‚

‚In the case of “Lower limit value ≤ Input value ≤ Upper limit value” 0 → Output value

+1, D ‚ D ‚

Lower limit value of dead band

[ ] +1, S1 ‚ S1 ‚

+1, S 3 ‚ S 3 ‚

Upper limit value of dead band [ ] +1, S2 ‚ S2 ‚

Output value = 0

FNC190-FNC199 Block Data Operation

Caution

  • When the output value overflows, it is handled as follows: - In the 16-bit operation The output value is a 16-bit binary value with sign. Accordingly, if the operation result is outside the range from - 32768 to +32767, it is handled as follows:

FNC200-FNC209 Character String Control

Lower limit value of dead band = 10

Output value = -32768-10 = 8000H-AH = 7FF6H = 32758

Input value = -32768

FNC210-FNC219 Data Operation 3

- In the 32-bit operation The output value is a 32-bit binary value with sign. Accordingly, if the operation result is outside the range from - 2,147,483,648 to +2,147,483,647, it is handled as follows:

Lower limit value of dead band [ +1, ] = 1000

Output value = -2,147,483,648-1000 = 80000000H-000003E8H = 7FFFFC18H = 2,147,482,648

Input value [ +1, ] = -2,147,483,648

Error

An operation error is caused when the instruction is executed in the setting status shown below; The error flag M8067 turns ON, and the error code (K6706) is stored in D8067.

FNC250-FNC269 Data Table Operation

S 1 S 2

32-bit operation [ +1, ] > [ +1, ]

S 1 S 1 S 2 S 2

Show 20 more labels / short text on this page
Command · input · FNC170-FNC179 External Device · +1, · +1, · FNC180 Alternate Instructions · Output · Output value · [ ] · value · FNC181-FNC189 Others · Output · Input value · Input value · [ ] · Output · FNC220-FNC249 Data Comparison · Relationship · 16-bit operation > · FNC270-FNC276 Ex-Device
Page 668 of the Mitsubishi Electronics MELSEC FX3S user manual — Operation
Page 668 · click to enlarge
Page 668

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.2 FNC257 – BAND / Dead Band Control

Program examples

1. Program example 1 In the program example shown below, the BCD data set in X020 to X037 is controlled by the dead band from “-1000” to “+1000”, and a controlled value is output to D1 when X000 turns ON.
Mitsubishi Electronics MELSEC FX3S — Program examples diagram (page 668)
Fig. 665 · Program examples
Mitsubishi Electronics MELSEC FX3S — Program examples diagram (page 668)
Fig. 666 · Program examples

Operation

  • In the case of “D0 < -1000”, “D0 - (-1000)” is output to D1.
  • In the case of “-1000 ≤ D0 ≤ +1000”, “0” is output to D1.
  • In the case of “D0 > +1000”, “D0 - 1000” is output to D1.
2. Program example 2 In the program example shown below, the BCD data set in X020 to X057 is controlled by the dead band from “-10000” to “+10000”, and a controlled value is output to D11 and D10 when X000 turns ON.
Mitsubishi Electronics MELSEC FX3S — Operation diagram (page 668)
Fig. 667 · Operation
Mitsubishi Electronics MELSEC FX3S — Operation diagram (page 668)
Fig. 668 · Operation

Operation

  • In the case of “(D1, D0) < -10000”, “(D1, D0) - (-10000)” is output to (D11, D10).
  • In the case of “-10000 ≤ (D1, D0) ≤ +10000”, “0” is output to (D11, D10).
  • In the case of “(D1, D0) > +10000”, “(D1, D0) - 10000” is output to (D11, D10).
Page 669 of the Mitsubishi Electronics MELSEC FX3S user manual — ZONE
Page 669 · click to enlarge
Page 669

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.3 FNC258 – ZONE / Zone Control 21

29.3 FNC258 – ZONE / Zone Control

FNC160-FNC169 Real Time Clock Control

Outline

Depending on how the input value compares to positive or negative, the output value is controlled by the bias value specified.

1. Instruction format

P FNC 258

Mnemonic Operation Condition 16-bit Instruction

ZONE D

Continuous Operation Pulse (Single) Operation

Continuous Operation Pulse (Single) Operation

ZONEP

DZONEP

2. Set data

Operand Type Description Data Type

Negative bias value to be added to the input value

16- or 32-bit binary Positive bias value to be added to the input value

Input value controlled by the zone

Head device number storing the output value controlled by the zone

3. Applicable devices

Bit Devices Word Devices Others

FNC190-FNC199 Block Data Operation

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

FNC200-FNC209 Character String Control

3

3

Explanation of function and operation

1. 16-bit operation (ZONE and ZONEP)

FNC210-FNC219 Data Operation 3

The bias value specified by or is added to the input value specified by , and output to the device

S 1 S 2 S 3

specified by . The bias value is added as shown below:

S1 ‚ S2 ‚ D ‚ S3 ‚

ZONE

‚In the case of “ Input value < 0” Input value + Negative bias value → Output value

‚In the case of “ Input value = 0” 0 → Output value

‚In the case of “ Input value > 0” Input value + Positive bias value → Output value

Output value ( ) D ‚

FNC250-FNC269 Data Table Operation

Input value ( ) S3 ‚

Negative bias value ( ) S1 ‚

Show 20 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 9 steps ZONE · 17 steps DZONE · FNC180 Alternate Instructions · FNC181-FNC189 Others · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · input · FNC220-FNC249 Data Comparison · Output · value · Positive bias value · Input value · FNC270-FNC276 Ex-Device
Page 670 of the Mitsubishi Electronics MELSEC FX3S user manual — Caution
Page 670 · click to enlarge
Page 670

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.3 FNC258 – ZONE / Zone Control

2. 32-bit operation (DZONE and DZONEP)

The bias value specified by [ +1, ] or [ +1, ] is added to the input value specified by [ +1,

S1 S1 S2 S2 S3

], and output to the device specified by [ +1, ]. The bias value is added as shown below:

S 3 D D

Mitsubishi Electronics MELSEC FX3S — S 3 D D diagram (page 670)
Fig. 669

‚In the case of “Input value < 0” Input value + Negative bias value → Output value

‚In the case of “Input value = 0” 0 → Output value

‚In the case of “Input value > 0” Input value + Positive bias value → Output value

+1, [ ] S2 ‚ S2 ‚

+1, [ ] S1 ‚ S1 ‚

Caution

  • When the output value overflows, it is handled as follows: - In the 16-bit operation The operation result is a 16-bit binary value with sign. Accordingly, if the output value is outside the range from -32768 to +32767, it is handled as follows:

Negative bias value = -100

Output value = -32768+(-100) = 8000H+FF9CH = 7F9CH = 32668

Input value = -32768

- In the 32-bit operation The output value is a 32-bit binary value with sign. Accordingly, if the operation result is outside the range from -2,147,483,648 to +2,147,483,647, it is handled as follows:

Negative bias value [ +1, ] = -1000

Output value = -2,147,483,648+(-1000) = 80000000H+FFFFFC18H = 7FFFFC18H = 2,147,482,648

Input value [ +1, ] = -2,147,483,648

Page 671 of the Mitsubishi Electronics MELSEC FX3S user manual — K-10000 K10000 D0 D10 FNC258 DZONEP
Page 671 · click to enlarge
Page 671

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.3 FNC258 – ZONE / Zone Control 21

Program examples

FNC160-FNC169 Real Time Clock Control

1. Program example 1 In the program example shown below, the BCD data set in X020 to X037 is controlled by the zone from “-1000” to “+1000”, and the controlled value is output to D1 when X000 turns ON.

K4X020 D0 FNC 19

BIN

K-1000 K1000 D0 D1 FNC258

ZONEP

END

Operation

  • In the case of “D0 < 0”, “D0 + (-1000)” is output to D1.
  • In the case of “D = 0”, “0” is output to D1.
  • In the case of “D0 > 0”, “D0 + 1000” is output to D1.

FNC190-FNC199 Block Data Operation

2. Program example 2 In the program example shown below, the BCD data set in X020 to X057 is controlled by the zone from “-10000” to “+10000”, and the controlled value is output to D11 and D10 when X000 turns ON.

K8X020 D0 FNC 19

DBIN

FNC200-FNC209 Character String Control

K-10000 K10000 D0 D10 FNC258 DZONEP

END

Operation

FNC210-FNC219 Data Operation 3

  • In the case of “(D1, D0) < 0”, “(D1, D0) + (-10000)” is output to (D11, D10).
  • In the case of “(D1, D0) = 0”, the “0” is output to (D11, D10).
  • In the case of “(D1, D0) > 0”, “(D1, D0) + 10000” is output to (D11, D10).

FNC250-FNC269 Data Table Operation

Show 9 more labels / short text on this page
FNC170-FNC179 External Device · FNC180 Alternate Instructions · Output · FNC181-FNC189 Others · Input · Output · Input 0 · FNC220-FNC249 Data Comparison · FNC270-FNC276 Ex-Device
Page 672 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 672 · click to enlarge
Page 672

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.4 FNC259 – SCL / Scaling (Coordinate by Point Data)

29.4 FNC259 – SCL / Scaling (Coordinate by Point Data)

Outline

This instruction executes scaling of the input value using a specified data table, and outputs the result. SCL2 (FNC269) is also available with a different data table configuration for scaling.

→ For SCL2 (FNC269) instruction, refer to Section 29.7.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 672)
Fig. 670 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 672)
Fig. 671 · 2. Set data

Input value used in scaling or device number storing the input value

16- or 32-bit binary Head device number storing the conversion table used in scaling

Device number storing the output value controlled by scaling

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 672)
Fig. 672 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

Explanation of function and operation

1. 16-bit operation (SCL and SCLP)

The input value specified in is processed by scaling for the specified conversion characteristics, and stored to a

device number specified in . Conversion for scaling is executed based on the data table stored in a device

specified in and later. If the output data is not an integer, however, the number in the first decimal place is rounded.

→ For the method to set the conversion table for scaling, refer to the next page.

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 672)
Fig. 673 · Explanation of function and operation

Number of coordinate points (“5” in the case shown in the left figure)

Page 673 of the Mitsubishi Electronics MELSEC FX3S user manual — Y
Page 673 · click to enlarge
Page 673

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.4 FNC259 – SCL / Scaling (Coordinate by Point Data) 21

2. 32-bit operation (DSCL and DSCLP)

FNC160-FNC169 Real Time Clock Control

The input value specified in [ +1, ] is processed by scaling for the specified conversion characteristics,

S 1 S 1

and stored to a device number specified in [ +1, ]. Conversion for scaling is executed based on the data

D D

table stored in a device specified in [ +1, ] and later. If the output data is not an integer, however, the number in the first decimal place is rounded.

S 2 S 2

Conversion setting data table for scaling

Set item Device assignment in

S 1 ‚ S 2 ‚ D ‚

DSCL

Number of coordinate points (“5” in the case shown in the left figure)

S 2 S 2

Y

X coordinate [ +3, +2]

S 2 S 2

Y coordinate [ +5, +4]

S 2 S 2

value ( ) D ‚

X coordinate [ +7, +6]

S 2 S 2

Point 4 Point 1

Y coordinate [ +9, +8]

S 2 S 2

X coordinate [ +11, +10]

S 2 S 2

Input value ( ) S1 ‚

Y coordinate [ +13, +12]

S 2 S 2

Operation error Operation is enabled.

X coordinate [ +15, +14]

S 2 S 2

Y coordinate [ +17, +16]

S 2 S 2

X coordinate [ +19, +18]

S 2 S 2

Y coordinate [ +21, +20]

S 2 S 2

3. Setting the conversion table for scaling

FNC190-FNC199 Block Data Operation

The conversion table for scaling is set based on the data table stored in a device specified in [ +1, ] and later. The data table has the following configuration:

S 2 S 2

→ For a setting example, refer to the following.

Device assignment in setting data table

16-bit operation 32-bit operation

FNC200-FNC209 Character String Control

Number of coordinate points [ +1, ]

S 2 S 2 S 2

X coordinate +1 [ +3, +2]

S 2 S 2 S 2

Y coordinate +2 [ +5, +4]

S 2 S 2 S 2

X coordinate +3 [ +7, +6]

S 2 S 2 S 2

FNC210-FNC219 Data Operation 3

Y coordinate +4 [ +9, +8]

S 2 S 2 S 2

X coordinate +2n-1 [ +4n-1, +4n-2]

S 2 S 2 S 2

Y coordinate +2n [ +4n+1, +4n]

S 2 S 2 S 2

Setting example of the conversion table for scaling A setting example for the 16-bit operation is shown below. For the 32-bit operation, set each item using a 32-bit binary value. In the case of the conversion characteristics for scaling shown in the figure below, set the following data table.

Y

FNC250-FNC269 Data Table Operation

Point 7 (250,90) Point 8(350,90)

Point 9 (350,30) Point 10(400,7)

Show 29 more labels / short text on this page
Command · FNC170-FNC179 External Device · input · setting data table · [ +1, ] · Point 2 · Output · Point 5 · Point 1 · FNC180 Alternate Instructions · Point 3 · Point 2 · Point 3 · Operation error · FNC181-FNC189 Others · Point 4 · Point 5 · Set item · Point 1 · Point 2 · Point n (last) · FNC220-FNC249 Data Comparison · Point 6(200,250) · Point 3 (50,100) · Point 5 (200,70) · Point 2 (20,30) · Point 1(5,7) · Point 4(200,25) · FNC270-FNC276 Ex-Device
Page 674 of the Mitsubishi Electronics MELSEC FX3S user manual — Errors
Page 674 · click to enlarge
Page 674

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.4 FNC259 – SCL / Scaling (Coordinate by Point Data)

Setting the conversion setting data table for scaling

Mitsubishi Electronics MELSEC FX3S — Setting the conversion setting data table for scaling diagram (page 674)
Fig. 674 · Setting the conversion setting data table for scalin…

When coordinates are specified using three points in this way, the output value can be set to an intermediate value. In this example, the output value (intermediate value) is specified by the Y coordinate of the point 5. If the X coordinate is the same at three points or more, the value at the second point is also output.

When coordinates are specified using two points in this way, the output value is the Y coordinate at the next point. In this example, the output value is specified by the Y coordinate of the point 9.

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When the Xn data is not set in the ascending order in the data table (error code: K6706) The data table is searched from the low-order side of device numbers in the data table in the operation. Accordingly, even if only some Xn data is set in the ascending order in the data table, the instruction is executed without operation error up to the area of the data table in which the Xn data is set in the ascending order.
  • When is outside the data table (error code: K6706)
  • When the value exceeds the 32-bit data range in the middle of operation (error code: K6706) In this case, verify that the distance between points is not “65535” or more. If the distance is “65535” or more, reduce the distance between points.
Page 675 of the Mitsubishi Electronics MELSEC FX3S user manual — 29.4 FNC259 – SCL / Scaling (Coordinate by Point Data) 21
Page 675 · click to enlarge
Page 675

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.4 FNC259 – SCL / Scaling (Coordinate by Point Data) 21

Mitsubishi Electronics MELSEC FX3S — 29.4 FNC259 – SCL / Scaling (Coordinate by Point Data) 21 diagram (page 675)
Fig. 675 · 29.4 FNC259 – SCL / Scaling (Coordinate by Point Dat…

In the program example shown below, the value input to D0 is processed by scaling based on the conversion table for scaling set in R0 and later, and output to D10.

Page 676 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 676 · click to enlarge
Page 676

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.5 FNC260 – DABIN / Decimal ASCII to BIN Conversion

29.5 FNC260 – DABIN / Decimal ASCII to BIN Conversion

Outline

This instruction converts numeric data expressed in decimal ASCII codes (30H to 39H) into binary data.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 676)
Fig. 676 · 1. Instruction format

2. Set data

Operand Type Description Data Type

Head device number storing data (ASCII codes) to be converted into binary data Character string

Device number storing conversion result 16- or 32-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 676)
Fig. 677 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

Explanation of function and operation

1. 16-bit operation (DABIN and DABINP)

1. Data stored in to +2 expressed in decimal ASCII codes (30H to 39H) is converted into 16-bit binary
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 676)
Fig. 678 · Explanation of function and operation

D ‚ ASCII code for 1's digit ASCII code for 10's digit

For example, when to +2 store ASCII codes expressing "-25108", 16-bit binary data is stored in

2. The numeric range of data stored in to +2 is from -32768 to +32767.
3. As "sign data" (low-order byte of ), "20H (space)" is set when the data to be converted is positive, and "2DH (-)" is set when the data to be converted is negative.
4. An ASCII code for each digit is ranging from "30H" to "39H".
5. When an ASCII code for each digit is "20H (space)" or "00H (NULL)", it is handled as "30H".
Page 677 of the Mitsubishi Electronics MELSEC FX3S user manual — S S
Page 677 · click to enlarge
Page 677

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.5 FNC260 – DABIN / Decimal ASCII to BIN Conversion 21

2. 32-bit operation (DDABIN and DDABINP)

FNC160-FNC169 Real Time Clock Control

1. Data stored in to +5 expressed in decimal ASCII codes (30H to 39H) is converted into 32-bit binary

S S

data, and stored in [ +1, ].

D D

input FNC260 DDABINP S ‚ D ‚

ASCII code for 1,000,000,000's digit

b0 b15 D ‚ +1 D ‚

ASCII code for 10,000,000's digit

ASCII code for 100,000,000's digit

ASCII code for 100,000's digit ASCII code for 1,000,000's digit

ASCII code for 1000's digit

ASCII code for 10000's digit

ASCII code for 10's digit

ASCII code for 100's digit

(Ignored) ASCII code for 1's digit

For example, when to +5 store ASCII codes expressing "-1,234,543,210", 32-bit binary data is

S S

stored in [ +1, ] as follows:

D D

31H(1) 33H(3) 2DH(-) 32H(2)

D ‚ +1 D ‚

35H(5) 34H(4)

33H(3) 31H(1) 34H(4) 32H(2)

2. The numeric range of data stored in to +5 is from -2,147,483,648 to +2,147,483,647.

S S

FNC190-FNC199 Block Data Operation

The high-order byte of +5 is ignored.

3. As "sign data" (low-order byte of ), "20H (space)" is set when the data to be converted is positive, and "2DH (-)" is set when the data to be converted is negative.
4. An ASCII code for each digit is ranging from "30H" to "39H".
5. When an ASCII code for each digit is "20H (space)" or "00H (NULL)", it is handled as "30H".

FNC200-FNC209 Character String Control

Related instructions

ASCI (FNC 82) Converts hexadecimal codes into ASCII codes.

HEX (FNC 83) Converts ASCII codes into hexadecimal codes.

STR (FNC200) Converts binary data into a character string (ASCII codes).

FNC210-FNC219 Data Operation 3

VAL (FNC201) Converts a character string (ASCII codes) into binary data.

BINDA (FNC261) Converts binary data into decimal ASCII codes (30H to 39H).

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When the sign data stored in is any value other than "20H (space)" or "2DH (-)" (error code: K6706)
  • When an ASCII code for each digit stored in to +2(5) is any value other than "30H" to "39H", "20H (space)", or "00H (NULL)" (error code: K6706)

S S

  • When the numeric range of to +2(5) is outside the following range (error code: K6706)

S S

FNC250-FNC269 Data Table Operation

16-bit operation −32768 to 32767

32-bit operation −2,147,483,648 to 2,147,483,647

  • When to +2(5) exceeds the device range (error code: K6706)

S S

Show 29 more labels / short text on this page
Command · FNC170-FNC179 External Device · b15 · b8 b7 b0 · +0 · Sign data · +1 · b16 b31 · +2 · High-order 16 bits · Low-order 16 bits · +3 · +5 +4 · 32-bit data · FNC180 Alternate Instructions · b15 · b8 b7 b0 · +0 · FNC181-FNC189 Others · +1 · +2 · -1234543210 · +3 · +5 +4 · (Ignored) 30H(0) · Instruction Description · FNC220-FNC249 Data Comparison · Setting range · FNC270-FNC276 Ex-Device
Page 678 of the Mitsubishi Electronics MELSEC FX3S user manual — X000 FNC260 DABINP D20 D0
Page 678 · click to enlarge
Page 678

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.5 FNC260 – DABIN / Decimal ASCII to BIN Conversion

Program example

In the program below, the sign and decimal ASCII codes in five digits stored in D20 to D22 are converted into a binary value and stored in D0 when X000 is set to ON.

X000 FNC260 DABINP D20 D0

END

b15 b8 b7 b0

20H(space) 32H(2) 2DH(-) 20H(space)

D21 D22 (It is regarded as

"-00276".) "- 276"

value 36H(6) 37H(7) · Binary

Page 679 of the Mitsubishi Electronics MELSEC FX3S user manual — D S
Page 679 · click to enlarge
Page 679

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.6 FNC261 – BINDA / BIN to Decimal ASCII Conversion 21

29.6 FNC261 – BINDA / BIN to Decimal ASCII Conversion

FNC160-FNC169 Real Time Clock Control

Outline

This instruction converts binary data into decimal ASCII codes (30H to 39H).

1. Instruction format

P FNC 261

Mnemonic Operation Condition 16-bit Instruction

BINDA D

Continuous Operation Pulse (Single) Operation

Continuous Operation Pulse (Single) Operation

BINDAP

DBINDAP

2. Set data

Operand Type Description Data Type

Device number storing binary data to be converted into ASCII codes 16- or 32-bit binary

Head device number storing conversion result Character string

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

FNC190-FNC199 Block Data Operation

3

Explanation of function and operation

1. 16-bit operation (BINDA and BINDAP)

FNC200-FNC209 Character String Control

1. Each digit of 16-bit binary data stored in is converted into an ASCII code (30H to 39H), and stored in

and later.

input FNC261 BINDAP S ‚ D ‚

b8 b7 b0 D‚

FNC210-FNC219 Data Operation 3

ASCII code for 10000's digit

Sign data ASCII code for 1000's digit

ASCII code for 100's digit

ASCII code for 1's digit ASCII code for 10's digit

+3 M8091=OFF: 0000H M8091=ON: Does not change.

0000H or source data

For example, when stores "-12345", the conversion result is stored in and later as follows:

S D

b8 b7 b0 D‚

31H(1) 33H(3) 2DH(-) 32H(2)

b0 b15 S‚ 35H(5) 34H(4)

FNC250-FNC269 Data Table Operation

0000H or source data +3 M8091=OFF: 0000H M8091=ON: Does not change.

2. The numeric range of 16-bit binary data stored in is from -32768 to +32767.
3. The conversion result stored in is as follows:

a) As "sign data" (low-order byte of ), "20H (space)" is set when the 16-bit binary data stored in is

D S

positive, and "2DH (-)" is set when 16-bit binary data stored in is negative.

Show 24 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 5 steps BINDA · 9 steps DBINDA · FNC180 Alternate Instructions · FNC181-FNC189 Others · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Command · b15 · +0 · +1 b0 b15 · +2 · 16-bit binary data · FNC220-FNC249 Data Comparison · b15 · +0 · +1 -12345 · +2 · FNC270-FNC276 Ex-Device
Page 680 of the Mitsubishi Electronics MELSEC FX3S user manual — S S
Page 680 · click to enlarge
Page 680

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.6 FNC261 – BINDA / BIN to Decimal ASCII Conversion

b) "20H (space)" is stored for "0" on the left side of the effective digits (zero suppression).

Mitsubishi Electronics MELSEC FX3S — 29.6 FNC261 – BINDA / BIN to Decimal ASCII Conversion diagram (page 680)
Fig. 679 · 29.6 FNC261 – BINDA / BIN to Decimal ASCII Conversio…

c) +3 is set as follows depending on the ON/OFF status of M8091.

2. 32-bit operation (DBINDA and DBINDAP)

1. Each digit of 32-bit binary data stored in [ +1, ] is converted into an ASCII code (30H to 39H), and

S S

Mitsubishi Electronics MELSEC FX3S — S S diagram (page 680)
Fig. 680

ASCII code for 100,000's digit ASCII code for 1,000,000's digit

For example, when [ +1, ] stores "-12,345,678", the conversion result is stored in and later as follows:

Mitsubishi Electronics MELSEC FX3S — S S diagram (page 680)
Fig. 681
2. The numeric range of 32-bit binary data stored in [ +1, ] is from -2,147,483,648 to +2,147,483,647.
3. The conversion result stored in is as follows:

a) "sign data" (low-order byte of ) "20H (space)" is set when the 32-bit binary data stored in [ +1,

] is positive, and "2DH (-)" is set when 32-bit binary data stored in [ +1, ] is negative. b) "20H (space)" is stored for "0" on the left side of the effective digits (zero suppression).

Mitsubishi Electronics MELSEC FX3S — S S diagram (page 680)
Fig. 682

0 0 1 2 0 3 4 5 6 0

c) The high-order byte of +5 is set as follows depending on the ON/OFF status of M8091.

M8091=OFF The high-order byte of +5 is set to "00H (NULL)".

M8091=ON The high-order byte of +5 is set to "20H (space)".

Page 681 of the Mitsubishi Electronics MELSEC FX3S user manual — M8091=OFF
Page 681 · click to enlarge
Page 681

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.6 FNC261 – BINDA / BIN to Decimal ASCII Conversion 21

Related devices

FNC160-FNC169 Real Time Clock Control

  • For 16-bit operation

- When M8091 is OFF, +3 is set to "0000H (NULL)".

M8091 Output character quantity selector signal

- When M8091 is ON, +3 does not change. • For 32-bit operation

- When M8091 is OFF, the high-order byte of +5 is set to "00H (NULL)".

- When M8091 is ON, the high-order byte of +5 is set to "20H (space)".

Related instructions

ASCI (FNC 82) Converts hexadecimal values into ASCII code.

HEX (FNC 83) Converts ASCII code into hexadecimal values.

STR (FNC200) Converts binary data into a character string (ASCII code).

VAL (FNC201) Converts a character string (ASCII code) into binary data.

DABIN (FNC260) Converts numeric data expressed in decimal ASCII code (30H to 39H) into binary data.

Cautions

1. Occupied device points

The table below shows the occupied device points of for 16-bit operation(BINDA/BINDAP) when M8091 is ON/ OFF and 32-bit operation (DBINDA/DBINDAP).

16-bit operation M8091=ON 3

M8091=OFF 4

FNC190-FNC199 Block Data Operation

Errors

An operation error is caused in the following case; The error flag M8067 turns ON, and the error code is stored in D8067.

FNC200-FNC209 Character String Control

  • When the occupied device point of storing the ASCII code character string exceeds the corresponding device rang (error code: K6706).

Program example

In the program below, 16-bit binary data stored in D1000 is converted into decimal ASCII codes when X000 is set to ON, and the ASCII codes converted by the PR (FNC 77) instruction are output one by one by the time division method to Y040 to Y051. By turning to OFF the output character selector signal M8091 and setting to ON PR mode flag M8027, ASCII codes up to "00H" are output.

FNC210-FNC219 Data Operation 3

→ For PR mode flag and the PR (FNC 77) instruction, refer to Section 15.8.

RST M8091

M8027 SET

FNC261 BINDAP D1000 D0

PR D0 Y040

FNC250-FNC269 Data Table Operation

END

b15 b8 b7 b0

20H(space) 31H(1) 20H(space) 35H(5)

PR (FNC 77)

D1 D2

36H(6) 32H(2)

0000H D3

output.

M8091=OFF

Show 13 more labels / short text on this page
Device Name Description · FNC170-FNC179 External Device · Instruction Description · FNC180 Alternate Instructions · FNC181-FNC189 Others · Occupied Points of · 32-bit operation 6 · FNC220-FNC249 Data Comparison · instruction · Y040 to Y051 · FNC270-FNC276 Ex-Device · 16-bit binary data · " 5126" is
Page 682 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 682 · click to enlarge
Page 682

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.7 FNC269 – SCL2 / Scaling 2 (Coordinate by X/Y Data)

29.7 FNC269 – SCL2 / Scaling 2 (Coordinate by X/Y Data)

Outline

This instruction executes scaling of the input value using a specified data table, and outputs the result. SCL (FNC259) is also available with a different data table configuration for scaling. SCL2 instruction is supported in the FX3UC Series Ver. 1.30 or later.

→ For SCL (FNC259) instruction, refer to Section 29.4.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 682)
Fig. 683 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 682)
Fig. 684 · 2. Set data

Input value used in scaling or device number storing the input value

16- or 32-bit binary Head device number storing the conversion table used in scaling

Device number storing the output value controlled by scaling

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 682)
Fig. 685 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

Explanation of function and operation

1. 16-bit operation (SCL2 and SCL2P)

The input value specified in is processed by scaling for the specified conversion characteristics, and stored to a

device number specified in . Conversion for scaling is executed based on the data table stored in a device

specified in and later. If the output data is not an integer, however, the number in the first decimal place is rounded.

→ For the method to set the conversion table for scaling, refer to the next page.

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 682)
Fig. 686 · Explanation of function and operation

Number of coordinate points (“5” in the case shown in the left figure)

Page 683 of the Mitsubishi Electronics MELSEC FX3S user manual — Y
Page 683 · click to enlarge
Page 683

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.7 FNC269 – SCL2 / Scaling 2 (Coordinate by X/Y Data) 21

2. 32-bit operation (DSCL2 and DSCL2P)

FNC160-FNC169 Real Time Clock Control

The input value specified in [ +1, ] is processed by scaling for the specified conversion characteristics,

S 1 S 1

and stored to a device number specified in [ +1, ]. Conversion for scaling is executed based on the data

D D

table stored in a device specified in [ +1, ] and later. If the output data is not an integer, however, the number in the first decimal place is rounded.

S 2 S 2

Conversion setting data table for scaling

Set item Device assignment in

S 1 ‚ S 2 ‚ D ‚

DSCL2

Number of coordinate points (“5” in the case shown in the left figure)

S 2 S 2

Y

Point 1 [ +3, +2]

S 2 S 2

Point 2 [ +5, +4]

S 2 S 2

value ( ) D ‚

Point 3 [ +7, +6]

S 2 S 2

Point 4 Point 1

Point 4 [ +9, +8]

S 2 S 2

Point 5 [ +11, +10]

S 2 S 2

Input value ( ) S1 ‚

Point 1 [ +13, +12]

S 2 S 2

Operation error Operation is enabled.

Point 2 [ +15, +14]

S 2 S 2

Point 3 [ +17, +16]

S 2 S 2

Point 4 [ +19, +18]

S 2 S 2

Point 5 [ +21, +20]

S 2 S 2

3. Setting the conversion table for scaling

FNC190-FNC199 Block Data Operation

The conversion table for scaling is set based on the data table stored in a device specified in [ +1, ] and later. The data table has the following configuration:

S 2 S 2

→ For a setting example, refer to the next page.

Device assignment in setting data table

16-bit operation 32-bit operation

FNC200-FNC209 Character String Control

Number of coordinate points [ +1, ]

S 2 S 2 S 2

Point 1 +1 [ +3, +2]

S 2 S 2 S 2

Point 2 +2 [ +5, +4]

S 2 S 2 S 2

Point n (last) +n [ +2n+1, +2n]

S 2 S 2 S 2

FNC210-FNC219 Data Operation 3

Point 1 +n+1 [ +2n+3, +2n+2]

S 2 S 2 S 2

Point 2 +n+2 [ +2n+5, +2n+4]

S 2 S 2 S 2

Point n (last) +2n [ +4n+1, +4n]

S 2 S 2 S 2

Setting example of the conversion table for scaling A setting example for the 16-bit operation is shown below. For the 32-bit operation, set each item using 32-bit binary value. In the case of the conversion characteristics for scaling shown in the figure below, set the following data table.

Y

FNC250-FNC269 Data Table Operation

Point 7 (250,90) Point 8(350,90)

Point 9 (350,30) Point 10(400,7)

Show 25 more labels / short text on this page
Command · FNC170-FNC179 External Device · input · setting data table · [ +1, ] · Point 2 · Output · Point 5 · FNC180 Alternate Instructions · Point 3 · X coordinate · Operation error · FNC181-FNC189 Others · Y coordinate · Set item · X coordinate · Y coordinate · FNC220-FNC249 Data Comparison · Point 6(200,250) · Point 3 (50,100) · Point 5 (200,70) · Point 2 (20,30) · Point 1(5,7) · Point 4(200,25) · FNC270-FNC276 Ex-Device
Page 684 of the Mitsubishi Electronics MELSEC FX3S user manual — Errors
Page 684 · click to enlarge
Page 684

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.7 FNC269 – SCL2 / Scaling 2 (Coordinate by X/Y Data)

Setting the conversion setting data table for scaling

Mitsubishi Electronics MELSEC FX3S — Setting the conversion setting data table for scaling diagram (page 684)
Fig. 687 · Setting the conversion setting data table for scalin…

*1. When coordinates are specified using three points as shown in the points 4, 5 and 6, the output value can be set to an intermediate value. In this example, the output value (intermediate value) is specified by the Y coordinate of the point 5. If the X coordinate is same at three points or more, the value at the second point is output also.

*2. When coordinates are specified using two points as shown in the points 8 and 9, the output value is the Y coordinate at the next point. In this example, the output value is specified by the Y coordinate of the point 9.

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When the Xn data is not set in the ascending order in the data table (error code: K6706) The data table is searched from the low-order side of the device numbers in the data table in the operation. Accordingly, even if only some Xn data is set in the ascending order in the data table, the instruction is executed without operation error up to the area of the data table in which the Xn data is set in the ascending order.
  • When is outside the data table (error code: K6706)
  • When the value exceeds the 32-bit data range in the middle of operation (error code: K6706) In this case, verify that the distance between points is not “65535” or more. If the distance is “65535” or more, reduce the distance between points.
Page 685 of the Mitsubishi Electronics MELSEC FX3S user manual — 29.7 FNC269 – SCL2 / Scaling 2 (Coordinate by X/Y Data) 21
Page 685 · click to enlarge
Page 685

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

29 Data Table Operation – FNC250 to FNC269

29.7 FNC269 – SCL2 / Scaling 2 (Coordinate by X/Y Data) 21

Mitsubishi Electronics MELSEC FX3S — 29.7 FNC269 – SCL2 / Scaling 2 (Coordinate by X/Y Data) 21 diagram (page 685)
Fig. 688 · 29.7 FNC269 – SCL2 / Scaling 2 (Coordinate by X/Y Da…

In the program example shown below, the value input to D0 is processed by scaling based on the conversion table for scaling set in R0 and later, and output to D10.

Page 686 of the Mitsubishi Electronics MELSEC FX3S user manual — 30. External Device Communication – FNC270 to FNC276
Page 686 · click to enlarge
Page 686

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

30 External Device Communication – FNC270 to FNC276

30. External Device Communication – FNC270 to FNC276

FNC270 to FNC276 provide instructions for executing inverter communication and MODBUS communication.

Mitsubishi Electronics MELSEC FX3S — 30. External Device Communication – FNC270 to FNC276 diagram (page 686)
Fig. 689 · 30. External Device Communication – FNC270 to FNC276
Page 687 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 D
Page 687 · click to enlarge
Page 687

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

30 External Device Communication – FNC270 to FNC276

30.1 FNC270 – IVCK / Inverter Status Check 21

30.1 FNC270 – IVCK / Inverter Status Check

FNC160-FNC169 Real Time Clock Control

Outline

This instruction reads the operation status of an inverter to a PLC using the computer link operation function of the inverter. Applicable inverters vary depending on the version. This instruction corresponds to the EXTR (K10) instruction in the FX2N/FX2NC Series.

→ For detailed explanation of the instruction, refer to the Data Communication Edition manual.

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

IVCK

2. Set data

Operand Type Description Data Type

Inverter station number (K0 to K31)

16-bit binary Inverter instruction code (shown on the next page)

Device number storing the read value

n Channel to be used (K1: ch 1, K2: ch 2)*1

*1. Ch2 is not available in FX3G PLC (14-point and 24-point type) and FX3S PLC.

FNC190-FNC199 Block Data Operation

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FNC200-FNC209 Character String Control

3 S 1 S 2 3 3 3

3 S 1 S 2 3 3 3

3 S1 S2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

FNC210-FNC219 Data Operation 3

Explanation of function and operation

→ For detailed explanation of the instruction, refer to the Data Communication Edition manual.

1. 16-bit operation (IVCK)

The operation status corresponding to the instruction code*2 specified in of an inverter connected to

communication port n whose station number is specified in is read and transferred to .

S 1 D

S 1 ‚ S 2 ‚ D ‚

FNC250-FNC269 Data Table Operation

*2. Refer to the instruction code list shown on the next page. Refer to the pages in the inverter manual on which the computer link function is explained in detail.

Show 19 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 9 steps IVCK · Continuous Operation · ⎯ ⎯ ⎯ · FNC180 Alternate Instructions · FNC181-FNC189 Others · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · n 3 3 · FNC220-FNC249 Data Comparison · Command · input · IVCK n · FNC270-FNC276 Ex-Device
Page 688 of the Mitsubishi Electronics MELSEC FX3S user manual — PLC applicable version
Page 688 · click to enlarge
Page 688

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

30 External Device Communication – FNC270 to FNC276

30.1 FNC270 – IVCK / Inverter Status Check

2. Inverter instruction codes The table below shows inverter instruction codes which can be specified in . Only use the instruction codes shown below. Use of instruction codes not shown below may cause communication errors. Do not use instruction codes not shown in the table below. They may cause communication errors. For the instruction codes, refer to the pages explaining computer link in detail in each inverter manual.

Inverter Instruction code (hexadecimal)

F700 A700 E700 D700 V500 F500 A500 E500 S500

H7B Operation mode 3

H6F Output frequency (speed) 3*1 3

H70 Output current 3

H71 Output voltage 3 –

H72 Special monitor 3 – –

H73 Special monitor selection No. 3 – –

H74 Alarm definition 3

H75 Alarm definition 3

H76 Alarm definition 3 –

H77 Alarm definition 3 –

H79 Inverter status monitor (expansion) 3 –

H7A Inverter status monitor 3

H6E Set frequency (EEPROM) 3*1 3

H6D Set frequency (RAM) 3*1 3

H7F Link parameter extended setting These codes cannot be specified in of the IVCK instruction. They are automatically processed when a "second parameter specification code" is specified the IVRD instruction. H6C Second parameter changing

*1. Please write "0" to instruction code HFF (Link parameter expansion setting) just before the IVCK instruction when reading frequency. When "0" is not written, reading of the frequency may not be executed normally.

3. Related devices → For the instruction execution complete flag use method, refer to Subsection 6.5.2.

Number Description Number Description ch1 ch2 ch1 ch2

M8029 Instruction execution complete D8063 D8438 Error code of serial communication error*2

M8063 M8438 Serial communication error*2 D8150 D8155 Response wait time in inverter communication*2

M8151 M8156 Inverter communicating D8151 D8156 Step number in inverter communication*4

M8152 M8157 Inverter communication error*3 D8152 D8157 Error code of inverter communication error*3

M8153 M8158 Inverter communication error latch*3 D8153 D8158 Latch of inverter communication error occurrence

M8154 M8159 IVBWR instruction error*3 D8154 D8159 IVBWR instruction error parameter number*3*4

*2. Cleared when PLC power supply is turned from OFF to ON. *3. Cleared when the PLC mode switches from STOP to RUN. *4. Initial value: -1

Cautions

  • → For other cautions, refer to the Data Communication Edition manual.
  • It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"ADPRW (FNC276)"/"FLCRT (FNC300) to FLSTRD (FNC305)" instruction and an "IVCK (FNC270) to IVMC (FNC275)" instruction for the same port.
  • Two or more inverter communication instructions (FNC270 to FNC275) can be driven for the same port at the same time.

PLC applicable version

The table below shows PLC versions applicable to each inverter.

Mitsubishi Electronics MELSEC FX3S — PLC applicable version diagram (page 688)
Fig. 690 · PLC applicable version

FX3U Ver. 2.20 or later Ver. 2.32 or later

FX3UC Ver. 1.00 or later Ver. 2.20 or later Ver. 2.32 or later

Applicable inverter · Read contents · step*3*4

Page 689 of the Mitsubishi Electronics MELSEC FX3S user manual — S 3 S 2
Page 689 · click to enlarge
Page 689

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

30 External Device Communication – FNC270 to FNC276

30.2 FNC271 – IVDR / Inverter Drive 21

30.2 FNC271 – IVDR / Inverter Drive

FNC160-FNC169 Real Time Clock Control

Outline

This instruction writes a inverter operation required control value to an inverter using the computer link operation function of the inverter. This instruction corresponds to the EXTR (K11) instruction in the FX2N/FX2NC Series.

→ For detailed explanation of the instruction, refer to the Data Communication Edition manual.

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

IVDR

2. Set data

Operand Type Description Data Type

Inverter station number (K0 to K31)

16-bit binary Inverter instruction code (shown on the next page)

Set value to be written to the inverter parameter or device number storing the data to be set

n Channel to be used (K1: ch 1, K2: ch 2)*1

*1. Ch2 is not available in FX3G PLC (14-point and 24-point type) and FX3S PLC.

FNC190-FNC199 Block Data Operation

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

FNC200-FNC209 Character String Control

3 S 1 S 2 3 3 3

3 S 1 S 2 3 3 3

3 S1 S2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

FNC210-FNC219 Data Operation 3

Explanation of function and operation

→ For detailed explanation of the instruction, refer to the Data Communication Edition manual.

1. 16-bit operation (IVDR)

The control value specified in is written to the instruction code*2 specified in of an inverter connected to

S 3 S 2

a communication port n whose station number is specified in .

IVDR S1 ‚ S2 ‚ S3 ‚ n

FNC250-FNC269 Data Table Operation

*2. Refer to the instruction code list shown on the next page. Refer to the pages in the inverter manual on which the computer link function is explained in detail.

Show 18 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 9 steps IVDR · Continuous Operation · ⎯ ⎯ ⎯ · FNC180 Alternate Instructions · FNC181-FNC189 Others · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · n 3 3 · FNC220-FNC249 Data Comparison · Command · input · FNC270-FNC276 Ex-Device
Page 690 of the Mitsubishi Electronics MELSEC FX3S user manual — PLC applicable version
Page 690 · click to enlarge
Page 690

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

30 External Device Communication – FNC270 to FNC276

30.2 FNC271 – IVDR / Inverter Drive

2. Inverter instruction codes

The table below shows inverter instruction codes which can be specified in . For instruction codes, refer to the pages explaining computer link in detail in each inverter manual.

Mitsubishi Electronics MELSEC FX3S — 2. Inverter instruction codes diagram (page 690)
Fig. 691 · 2. Inverter instruction codes

F700 A700 E700 D700 V500 F500 A500 E500 S500

HFB Operation mode 3

HF3 Special monitor selection number 3 – –

HF9 Run command (expansion) 3 –

HFA Run command 3

HEE Set frequency (EEPROM) 3*3

HED Set frequency (RAM) 3*3

HFD*1 Inverter reset*2 3

HF4 Alarm definition batch clear 3 – 3

HFC Parameter all clear 3

HFC User clear – 3 3 – –

HFF Link parameter extended setting 3

*1. The instruction code "HFD (inverter reset)" does not request a response from the inverter. Accordingly, even if inverter reset is executed to a station number at which an inverter is not connected, error does not occur. It takes about 2.2 seconds to complete execution of inverter reset.

*2. When resetting the inverter, please specify H9696 as the operand of the IVDR instruction. Do not use H9966. *3. Please write "0" to instruction code HFF (Link parameter expansion setting) just before the IVDR instruction when writing frequency. When "0" is not written, writing of the frequency may not be executed normally.

3. Related devices → For the instruction execution complete flag use method, refer to Subsection 6.5.2.

Number Description Number Description ch1 ch2 ch1 ch2

M8029 Instruction execution complete D8063 D8438 Error code of serial communication error*4

M8063 M8438 Serial communication error*4 D8150 D8155 Response wait time in inverter communication*4

M8151 M8156 Inverter communicating D8151 D8156 Step number in inverter communication*6

M8152 M8157 Inverter communication error*5 D8152 D8157 Error code of inverter communication error*5

M8153 M8158 Inverter communication error latch*5 D8153 D8158 Latch of inverter communication error occurrence

M8154 M8159 IVBWR instruction error*5 D8154 D8159 IVBWR instruction error parameter number*5*6

*4. Cleared when PLC power supply is turned from OFF to ON. *5. Cleared when the PLC mode switches from STOP to RUN. *6. Initial value: -1

Cautions

  • → For other cautions, refer to the Data Communication Edition manual.
  • It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"ADPRW (FNC276)"/"FLCRT (FNC300) to FLSTRD (FNC305)" instruction and an "IVCK (FNC270) to IVMC (FNC275)" instruction for the same port.
  • Two or more inverter communication instructions (FNC270 to FNC275) can be driven for the same port at the same time.

PLC applicable version

The table below shows PLC versions applicable to each inverter.

Mitsubishi Electronics MELSEC FX3S — PLC applicable version diagram (page 690)
Fig. 692 · PLC applicable version

FX3U Ver. 2.20 or later Ver. 2.32 or later

FX3UC Ver. 1.00 or later Ver. 2.20 or later Ver. 2.32 or later

step*5*6

Page 691 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 D
Page 691 · click to enlarge
Page 691

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

30 External Device Communication – FNC270 to FNC276

30.3 FNC272 – IVRD / Inverter Parameter Read 21

30.3 FNC272 – IVRD / Inverter Parameter Read

FNC160-FNC169 Real Time Clock Control

Outline

This instruction reads an inverter parameter to the PLC using the computer link operation function of the inverter. This instruction corresponds to the EXTR (K12) instruction in the FX2N/FX2NC Series.

→ For detailed explanation of the instruction, refer to the Data Communication Edition manual.

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

IVRD

2. Set data

Operand Type Description Data Type

Inverter station number (K0 to K31)

16-bit binary Inverter parameter number

Device number storing the read value

n Channel to be used (K1: ch 1, K2: ch 2)*1

*1. Ch2 is not available in FX3G PLC (14-point and 24-point type) and FX3S PLC.

3. Applicable devices

FNC190-FNC199 Block Data Operation

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S 1 S 2 3 3 3

FNC200-FNC209 Character String Control

3 S 1 S 2 3 3 3

3 S 1 S 2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

FNC210-FNC219 Data Operation 3

Explanation of function and operation

→ For detailed explanation of the instruction, refer to the Data Communication Edition manual.

1. 16-bit operation (IVRD)

The value of the parameter is read from an inverter connected to a communication port n whose station

number is , and output to .

S 1 D

IVRD S1 ‚ S2 ‚ D ‚ n

FNC250-FNC269 Data Table Operation

Show 18 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 9 steps IVRD · ⎯ ⎯ ⎯ · Continuous Operation · FNC180 Alternate Instructions · FNC181-FNC189 Others · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · n 3 3 · FNC220-FNC249 Data Comparison · Command · input · FNC270-FNC276 Ex-Device
Page 692 of the Mitsubishi Electronics MELSEC FX3S user manual — PLC FREQROL-V500/F500/A500/E500/S500 FREQROL-F700/A700 FREQROL-E700/D700
Page 692 · click to enlarge
Page 692

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

30 External Device Communication – FNC270 to FNC276

30.3 FNC272 – IVRD / Inverter Parameter Read

2. Related devices → For the instruction execution complete flag use method, refer to Subsection 6.5.2.

Description ch1 ch2 ch1 ch2

M8029 Instruction execution complete D8063 D8438 Error code of serial communication error*1

M8063 M8438 Serial communication error *1 D8150 D8155 Response wait time in inverter communication*1

M8151 M8156 Inverter communicating D8151 D8156 Step number in inverter communication*3

M8152 M8157 Inverter communication error*2 D8152 D8157 Error code of inverter communication error*2

M8153 M8158 Inverter communication error latch*2 D8153 D8158 Latch of inverter communication error occurrence

M8154 M8159 IVBWR instruction error*2 D8154 D8159 IVBWR instruction error parameter number*2*3

*1. Cleared when PLC power supply is turned from OFF to ON.

*2. Cleared when the PLC mode switches from STOP to RUN.

*3. Initial value-1

Cautions

→ For other cautions, refer to the Data Communication Edition manual.

  • It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"ADPRW (FNC276)"/"FLCRT (FNC300) to FLSTRD (FNC305)" instruction and an "IVCK (FNC270) to IVMC (FNC275)" instruction for the same port.
  • Two or more inverter communication instructions (FNC270 to FNC275) can be driven for the same port at the same time.

PLC applicable version

The table below shows PLC versions applicable to each inverter.

PLC FREQROL-V500/F500/A500/E500/S500 FREQROL-F700/A700 FREQROL-E700/D700

FX3S Ver. 1.00 or later

FX3G Ver. 1.10 or later

FX3GC Ver. 1.40 or later

FX3U Ver. 2.20 or later Ver. 2.32 or later

FX3UC Ver. 1.00 or later Ver. 2.20 or later Ver. 2.32 or later

Show 4 more labels / short text on this page
Number · Number · Description · step*2*3
Page 693 of the Mitsubishi Electronics MELSEC FX3S user manual — S 3 S 2
Page 693 · click to enlarge
Page 693

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

30 External Device Communication – FNC270 to FNC276

30.4 FNC273 – IVWR / Inverter Parameter Write 21

30.4 FNC273 – IVWR / Inverter Parameter Write

FNC160-FNC169 Real Time Clock Control

Outline

This instruction writes an inverter parameter of an inverter using the computer link operation function of the inverter. This instruction corresponds to the EXTR (K13) instruction in the FX2N/FX2NC Series.

→ For detailed explanation of the instruction, refer to the Data Communication Edition manual.

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

IVWR

2. Set data

Operand Type Description Data Type

Inverter station number (K0 to K31)

16-bit binary Inverter parameter number

Set value to be written to the inverter parameter or device number storing the data to be set

n Channel to be used (K1: ch 1, K2: ch 2)*1

*1. Ch2 is not available in FX3G PLC (14-point and 24-point type) and FX3S PLC.

FNC190-FNC199 Block Data Operation

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S 1 S 2 3 3 3

FNC200-FNC209 Character String Control

3 S 1 S 2 3 3 3

3 S 1 S 2 3 3 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

FNC210-FNC219 Data Operation 3

Explanation of function and operation

→ For detailed explanation of the instruction, refer to the Data Communication Edition manual.

1. 16-bit operation (IVWR)

A value specified in is written to a parameter in an inverter connected to a communication port n whose

S 3 S 2

station number is .

IVWR S1 ‚ S2 ‚ S3 ‚ n

FNC250-FNC269 Data Table Operation

Show 18 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 9 steps IVWR · ⎯ ⎯ ⎯ · Continuous Operation · FNC180 Alternate Instructions · FNC181-FNC189 Others · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · n 3 3 · FNC220-FNC249 Data Comparison · Command · input · FNC270-FNC276 Ex-Device
Page 694 of the Mitsubishi Electronics MELSEC FX3S user manual — PLC FREQROL-V500/F500/A500/E500/S500 FREQROL-F700/A700 FREQROL-E700/D700
Page 694 · click to enlarge
Page 694

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

30 External Device Communication – FNC270 to FNC276

30.4 FNC273 – IVWR / Inverter Parameter Write

2. Related devices → For the instruction execution complete flag use method, refer to Subsection 6.5.2.

Number Description Number Description ch1 ch2 ch1 ch2

M8029 Instruction execution complete D8063 D8438 Error code of serial communication error*1

M8063 M8438 Serial communication error*1 D8150 D8155 Response wait time in inverter communication*1

M8151 M8156 Inverter communicating D8151 D8156 Step number in inverter communication*3

M8152 M8157 Inverter communication error*2 D8152 D8157 Error code of inverter communication error*2

M8153 M8158 Inverter communication error latch*2 D8153 D8158 Latch of inverter communication error occurrence

M8154 M8159 IVBWR instruction error*2 D8154 D8159 IVBWR instruction error parameter number*2*3

*1. Cleared when PLC power supply is turned from OFF to ON. *2. Cleared when the PLC mode switches from STOP to RUN. *3. Initial value: -1

Cautions

  • → For other cautions, refer to the Data Communication Edition manual.
  • It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"ADPRW (FNC276)"/"FLCRT (FNC300) to FLSTRD (FNC305)" instruction and an "IVCK (FNC270) to IVMC (FNC275)" instruction for the same port.
  • Two or more inverter communication instructions (FNC270 to FNC275) can be driven for the same port at the same time.
  • Cautions on using the password function in the D700 Series.
1. When a communication error occurs When a communication error occurs in an inverter communication instruction, the FX PLC automatically retries

communication up to 3 times*4. Accordingly, note that the number of times of password reset error displayed in accordance with the setting of Pr297 may not agree with the actual number of times of password input error as described below when a

password reset error occurs in the D700 Series in which "display of the number of times of password reset error"*5

is made valid using Pr297. Do not execute automatic retry (re-driving of an inverter instruction) using a sequence program when writing data to Pr297.

Cases in which a password reset error occurs in an inverter communication instruction, and the actual number of times of reset error in such cases.

- When a wrong password is written to Pr297 due to a password input error When the writing instruction is executed once, a password reset error occurs 3 times. - When the password cannot be written correctly to Pr297 due to noise, etc. A password reset error occurs up to 3 times.

2. When registering the password When registering the password in the D700 Series inverter using an inverter communication instruction, write the

password to Pr297, read Pr297, and then confirm that registration of the password is completed normally*6. If writing of the password to Pr297 is not completed normally due to noise, etc., the FX PLC automatically retries writing, and the registered password may be reset by the retry.

*4. The FX PLC executes the first communication, and then retries communication twice (3 time in total).

*5. When "display of the number of times of password reset error" is made valid in the D700 Series using Pr297 and when a password reset error occurs 5 times, the "reading/writing restriction" cannot be reset even if the right password is input. For recovery from this status, it is necessary to all-clear all parameters in the D700 Series.

*6. When the value given as a result of reading Pr297 is "0" to "4", registration of the password is completed normally.

PLC applicable version

The table below shows PLC versions applicable to each inverter.

PLC FREQROL-V500/F500/A500/E500/S500 FREQROL-F700/A700 FREQROL-E700/D700

FX3S Ver. 1.00 or later

FX3G Ver. 1.10 or later

FX3GC Ver. 1.40 or later

FX3U Ver. 2.20 or later Ver. 2.32 or later

FX3UC Ver. 1.00 or later Ver. 2.20 or later Ver. 2.32 or later

step*2*3

Page 695 of the Mitsubishi Electronics MELSEC FX3S user manual — S 3 S 2
Page 695 · click to enlarge
Page 695

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

30 External Device Communication – FNC270 to FNC276

30.5 FNC274 – IVBWR / Inverter Parameter Block Write 21

30.5 FNC274 – IVBWR / Inverter Parameter Block Write

FNC160-FNC169 Real Time Clock Control

Outline

This instruction writes parameters of an inverter at one time using the computer link operation function of the inverter.

→ For detailed explanation of the instruction, refer to the Data Communication Edition manual.

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

IVBWR

2. Set data

Operand Type Description Data Type

Station number of an inverter (K0 to K31)

16-bit binary Number of parameters in an inverter to be written at one time

Head device number of a parameter table to be written to an inverter

n Used channel (K1ch 1, K2: ch 2)

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

FNC190-FNC199 Block Data Operation

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

3

3

FNC200-FNC209 Character String Control

Explanation of function and operation

→ For detailed explanation of the instruction, refer to the Data Communication Edition manual.

1. 16-bit operation (IVBWR)

A data table*1 (parameter numbers and set values) specified in and is written to an inverter connected to

S 2 S 3

FNC210-FNC219 Data Operation 3

a communication port n whose station number is all at once.

IVBWR S1 ‚ S2 ‚ S3 ‚ n

*1. The table below shows the data table format.

: Number of parameters to be written

: Head device number of data table

Device Parameter numbers to be written and set values

1st parameter Parameter number

2nd parameter Parameter number

FNC250-FNC269 Data Table Operation

S 3 S 2

S 2 S 3 S 2

+2 -3 Set value

S 3 S 2

S 2 S 3 S 2

+2 -1 Set value

Show 27 more labels / short text on this page
FNC170-FNC179 External Device · Mnemonic Operation Condition · 32-bit Instruction · 9 steps IVBWR · ⎯ ⎯ ⎯ · Continuous Operation · FNC180 Alternate Instructions · FNC181-FNC189 Others · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · n 3 3 · Command · input · FNC220-FNC249 Data Comparison · +1 Set value · +2 · +3 Set value · +2 -4 · Parameter number · “ -1”th parameter · FNC270-FNC276 Ex-Device · +2 -2 · Parameter number · “ ”th parameter
Page 696 of the Mitsubishi Electronics MELSEC FX3S user manual — PLC FREQROL-V500/F500/A500/E500/S500 FREQROL-F700/A700 FREQROL-E700/D700
Page 696 · click to enlarge
Page 696

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

30 External Device Communication – FNC270 to FNC276

30.5 FNC274 – IVBWR / Inverter Parameter Block Write

2. Related devices → For the instruction execution complete flag use method, refer to Subsection 6.5.2.

Description ch1 ch2 ch1 ch2

M8029 Instruction execution complete D8063 D8438 Error code of serial communication error*1

M8063 M8438 Serial communication error*1 D8150 D8155 Response wait time in inverter communication*1

M8151 M8156 Inverter communicating D8151 D8156 Step number in inverter communication*3

M8152 M8157 Inverter communication error*2 D8152 D8157 Error code of inverter communication error*2

M8153 M8158 Inverter communication error latch*2 D8153 D8158 Latch of inverter communication error occurrence

M8154 M8159 IVBWR instruction error*2 D8154 D8159 IVBWR instruction error parameter number*2*3

*1. Cleared when PLC power supply is turned from OFF to ON.

*2. Cleared when the PLC mode switches from STOP to RUN.

*3. Initial value-1

Cautions

→ For other cautions, refer to the Data Communication Edition manual.

  • It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"ADPRW (FNC276)"/"FLCRT (FNC300) to FLSTRD (FNC305)" instruction and an "IVCK (FNC270) to IVMC (FNC275)" instruction for the same port.
  • Two or more inverter communication instructions (FNC270 to FNC275) can be driven for the same port at the same time.

Applicable models depending on the PLC version

The table below shows PLC versions applicable to each inverter.

PLC FREQROL-V500/F500/A500/E500/S500 FREQROL-F700/A700 FREQROL-E700/D700

FX3U Ver. 2.20 or later Ver. 2.32 or later

FX3UC Ver. 1.00 or later Ver. 2.20 or later Ver. 2.32 or later

Show 4 more labels / short text on this page
Number · Number · Description · step*2*3
Page 697 of the Mitsubishi Electronics MELSEC FX3S user manual — S 3 S 3 D D
Page 697 · click to enlarge
Page 697

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

30 External Device Communication – FNC270 to FNC276

30.6 FNC275 – IVMC / Inverter Multi Command 21

30.6 FNC275 – IVMC / Inverter Multi Command

FNC160-FNC169 Real Time Clock Control

Outline

This instruction writes 2 types of settings (operation command and set frequency) to the inverter, and reads 2 types of data (inverter status monitor, output frequency, etc.) from the inverter at the same time.

→ For detailed explanation of the instruction, refer to the Data Communication Edition manual.

1. Instruction format

Mnemonic Operation Condition 32-bit Instruction Mnemonic Operation Condition

IVMC

11 steps IVMC Continuous Operation

2. Set data

Operand Type Description Data Type

Inverter station number (K0 to K31)

Multiple instructions for inverterSend/receive data type specification

Head device which stores data to be written to the inverter (Occupies 2 points.)

Head device which stores values to be read from the inverter (Occupies 2 points.)

n Channel to be used (K1: ch1, K2: ch2)*1

*1. Ch2 is not available in FX3G PLC (14-point and 24-point type) and FX3S PLC.

3. Applicable devices

Bit Devices Word Devices Others

FNC190-FNC199 Block Data Operation

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3 S 1 S 2 3 3 3

3 S 1 S 2 3 3 3

FNC200-FNC209 Character String Control

3 S 1 S 2 3

3 S 1 S 2 3

S1: This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. S2: This function is supported only in FX3U/FX3UC PLCs.

Explanation of function and operation

FNC210-FNC219 Data Operation 3

→ For detailed explanation of the instruction, refer to the Data Communication Edition manual.

1. 16-bit operation (IVMC) This instruction executes multiple commands of an inverter connected to a communication port n whose station

number is specified in . Specify the send/receive data type using , the head device which stores data to

S 1 S 2

be written to the inverter using , and the head device which stores values to be read from the inverter using .

IVMC S1 S2 S3 n D

2. Send/receive data type The table below shows valid send data 1 and 2 and receive data 1 and 2 specified by the send/receive data type

FNC250-FNC269 Data Table Operation

Send data (Write contents to Inverter)

Receive data (Read contents from Inverter)

Data 1 ( ) Data 2 ( +1) Data 1 ( ) Data 2 ( +1)

S 3 S 3 D D

H0000

H0010 Set frequency (RAM, EEPROM)

Show 25 more labels / short text on this page
FNC170-FNC179 External Device · 16-bit Instruction · FNC180 Alternate Instructions · 16-bit binary · FNC181-FNC189 Others · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · n 3 3 · FNC220-FNC249 Data Comparison · Command · input FNC275 · Send/receive · data type · Output frequency (speed) · Set frequency (RAM) · FNC270-FNC276 Ex-Device · H0001 Special monitor · Inverter status monitor · Run command (expansion) · (expansion) · Output frequency (speed) · H0011 Special monitor
Page 698 of the Mitsubishi Electronics MELSEC FX3S user manual — Applicable programming tool
Page 698 · click to enlarge
Page 698

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

30 External Device Communication – FNC270 to FNC276

30.6 FNC275 – IVMC / Inverter Multi Command

3. Related devices → For the instruction execution complete flag use method, refer to Subsection 6.5.2.

Description ch1 ch2 ch1 ch2

M8029 Instruction execution complete D8063 D8438 Error code of serial communication error*1

M8063 M8438 Serial communication error*1 D8150 D8155 Response wait time in inverter communication*1

M8151 M8156 Inverter communicating D8151 D8156 Step number in inverter communication*3

M8152 M8157 Inverter communication error*2 D8152 D8157 Error code of inverter communication error*2

M8153 M8158 Inverter communication error latch*2 D8153 D8158 Latch of inverter communication error occurrence step*2*3

M8154 M8159 Inverter instruction error*2 D8154 D8159 IVBWR instruction error parameter number*2*3

*1. Cleared when PLC power supply is turned from OFF to ON.

*2. Cleared when the PLC mode switches from STOP to RUN.

*3. Initial value-1

Cautions

→ For other cautions, refer to the Data Communication Edition manual.

  • It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"ADPRW (FNC276)"/"FLCRT (FNC300) to FLSTRD (FNC305)" instruction and an "IVCK (FNC270) to IVMC (FNC275)" instruction for the same port.
  • Two or more inverter communication instructions (FNC270 to FNC275) can be driven for the same port at the same time.
  • Number of occupied devices Two devices are occupied respectively by and . Make sure not to use those devices in another control.

S 3 D

  • If a device number outside the range due to indexing, etc. is specified in , the receive data from the inverter

is not stored in . However, values set in and +1 may be written to the inverter.

D S 3 S 3

  • If any unspecified value is set in , unexpected data may be written to and read from the inverter, and values

of and +1 may be updated.

D D

  • IVMC instruction reads the inverter status at the time of communication with the inverter, and stores the read status to . Accordingly, the status written by the IVMC instruction can be read by a next or later read instruction (IVCK or IVMC).

Applicable inverters

This instruction is applicable to the following inverters:

- FREQROL-E700 (February 2009 and later) - FREQROL-D700 (Applicable in all)

→ For details, refer to the respective inverter manual

Applicable programming tool

This instruction is applicable to the following programming tools:

  • FX 3S Series PLC

Product name Model name Compatible Versions Remarks

GX Works2 SW†DNC-GXW2-E Ver. 1.492N or later - FX-30P Ver. 1.50 or later

  • FX 3G Series PLC

Product name Model name Compatible Versions Remarks

GX Works2 SW†DNC-GXW2-E Ver. 1.62Q or later - FX-30P Ver. 1.50 or later

  • FX 3GC Series PLC

Product name Model name Compatible Versions Remarks

GX Works2 SW†DNC-GXW2-E Ver. 1.77F or later - FX-30P Ver. 1.50 or later

  • FX 3U /FX 3UC Series PLCs
Mitsubishi Electronics MELSEC FX3S — Applicable programming tool diagram (page 698)
Fig. 693 · Applicable programming tool

GX Works2 SW†DNC-GXW2-E Ver. 1.48A or later - FX-30P Ver. 1.20 or later

Number · Number · Description

Page 699 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 699 · click to enlarge
Page 699

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

30 External Device Communication – FNC270 to FNC276

30.7 FNC276 - MODBUS Read/Write Instruction 21

30.7 FNC276 - MODBUS Read/Write Instruction

FNC160-FNC169 Real Time Clock Control

Outline

This instruction allows the MODBUS Master to communicate (read/write data) with its associated Slaves.

→ For explanation of the instruction, refer to the MODBUS Communication Edition.

1. Instruction Format

Mnemonic Operation Condition 32-bit Instruction Mnemonic Operation Condition

ADPRW

11 steps ADPRW Continuous Operation

2. Set Data

Operand Type Description Data Type

Slave Node Address (K0 to K32) 16-bit binary

Command Code 16-bit binary

Command Parameter depending on the Command Code (See Subsection 30.7.1) 16-bit binary

Command Parameter depending on the Command Code (See Subsection 30.7.1) 16-bit binary

/ Command Parameter depending on the Command Code (See Subsection 30.7.1) Bit or 16-bit binary

S 4 D

3. Applicable Devices

FNC190-FNC199 Block Data Operation

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

S 1 S 2 3 3 3

S 1 S 2 3 3 3

FNC200-FNC209 Character String Control

S 1 S 2 3 3 3

S 1 S 2 3 3 3

/ 3 3 S1 3 S1 S2 3 3 3

S 4 D

S1: Except special auxiliary relay (M) and special data register (D). S2: Only available for FX3G/FX3GC/FX3U/FX3UC PLCs.

FNC210-FNC219 Data Operation 3

Explanation of function and operation

1. 16-bit operation (ADPRW)

Command Code is operated on Slave Node according to Parameters , , and / . Use 0 as the Slave Node Address for Broadcast commands.

S1 S S2 S3 S4 D

input FNC276 ADPRW S ‚

S1‚ S2‚ S3‚ S4‚ D ‚

FNC250-FNC269 Data Table Operation

Command Parameters depending on the Command Code

Slave Node Address K0 to K32 (00H to 20H)

Show 17 more labels / short text on this page
FNC170-FNC179 External Device · 16-bit Instruction · FNC180 Alternate Instructions · FNC181-FNC189 Others · Unit Index Con- stant · Real Number · Charac- ter String Pointer · Operand Type · FNC220-FNC249 Data Comparison · Slave Node Address · Command Code Parameters · Command · Command · code · / · Command Code · FNC270-FNC276 Ex-Device
Page 700 of the Mitsubishi Electronics MELSEC FX3S user manual — 30.7.1 Command Code and Command Parameters
Page 700 · click to enlarge
Page 700

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

30 External Device Communication – FNC270 to FNC276

30.7 FNC276 - MODBUS Read/Write Instruction

30.7.1 Command Code and Command Parameters

The following table shows the required command parameters for each command code.

Mitsubishi Electronics MELSEC FX3S — 30.7.1 Command Code and Command Parameters diagram (page 700)
Fig. 694 · 30.7.1 Command Code and Command Parameters

S1 S2 S3 S4 D

7H Read Exception State (Available only in FX3U and FX3UC PLCs.)

Sub-function Data0x0000: Do Not Reset Event Log 0xFF00: Reset Event Log

8H Diagnosis (Available only in FX3U and FX3UC PLCs.)

Sub-function Data (ASCII Mode End of Message Character): 00H~FFH

Page 701 of the Mitsubishi Electronics MELSEC FX3S user manual — 30.7.1 Command Code and Command Parameters
Page 701 · click to enlarge
Page 701

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

30 External Device Communication – FNC270 to FNC276

Mitsubishi Electronics MELSEC FX3S — 30.7.1 Command Code and Command Parameters diagram (page 701)
Fig. 695 · 30.7.1 Command Code and Command Parameters

/ S1 S2 S3 S4 D

(Available only in FX3U and FX3UC PLCs.)

(Available only in FX3U and FX3UC PLCs.)

CH Get Comm. Event Log (Available only in FX3U and FX3UC PLCs.)

Page 702 of the Mitsubishi Electronics MELSEC FX3S user manual — 30.7.1 Command Code and Command Parameters
Page 702 · click to enlarge
Page 702

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

30 External Device Communication – FNC270 to FNC276

30.7 FNC276 - MODBUS Read/Write Instruction

Mitsubishi Electronics MELSEC FX3S — 30.7.1 Command Code and Command Parameters diagram (page 702)
Fig. 696 · 30.7.1 Command Code and Command Parameters

/ S1 S2 S3 S4 D

11H Report Slave ID (Available only in FX3U and FX3UC PLCs.)

16H Mask Write Register (Available only in FX3U and FX3UC PLCs.)

17H Read/Write Multiple Registers (Available only in FX3U and FX3UC PLCs.)

*1. This calculation formula is applicable when the applicable device is D or R.

Page 703 of the Mitsubishi Electronics MELSEC FX3S user manual — 31. Data Transfer 3 – FNC277 to FNC279
Page 703 · click to enlarge
Page 703

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

31 Data Transfer 3 – FNC277 to FNC279

Mitsubishi Electronics MELSEC FX3S — 31. Data Transfer 3 – FNC277 to FNC279 diagram (page 703)
Fig. 697 · 31. Data Transfer 3 – FNC277 to FNC279

FNC277 to FNC279 provide instructions for executing more complicated processing for fundamental applied instructions and for special processing.

Page 704 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 704 · click to enlarge
Page 704

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

31 Data Transfer 3 – FNC277 to FNC279

31.1 FNC278 – RBFM / Divided BFM Read

31.1 FNC278 – RBFM / Divided BFM Read

Outline

This instruction reads data from continuous buffer memories (BFM) in a special function unit/block over several operation cycles by the time division method. This instruction is convenient for reading receive data, etc. stored in buffer memories in a special function unit/block for communication by the time division method. FROM (FNC 78) instruction is also available to read the buffer memory (BFM) data.

→ For FROM (FNC 78) instruction, refer to Section 15.9.

1. Instruction format

Mnemonic Operation Condition 32-bit Instruction

RBFM

Continuous Operation −

2. Set data

Mitsubishi Electronics MELSEC FX3S — RBFM diagram (page 704)
Fig. 698

m2 Head buffer memory (BFM) number [0 to 32766]

Head device number storing data to be read from buffer memory (BFM)

n1 Number of all buffer memories (BFM) to be read [1 to 32767]

n2 Number of points transferred in one operation cycle [1 to 32767]

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 704)
Fig. 699 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

SExcept special data register (D)

Explanation of function and operation

1. 16-bit operation (RBFM)

"n1" buffer memory (BFM) units at location # "m2" in special function unit/block No. "m1" are read to in the PLC. While transferring, "n1" is divided by "n2" so n1/n2 buffer memories (rounded up when there is a remainder) are transferred per scan time.

→ For the unit No., buffer memory (BFM) #, cautions, and program example,

refer to Subsection 31.1.1.

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 704)
Fig. 700 · Explanation of function and operation

*1 "n2" buffer memories are read in each operation cycle. Reading is executed in "n1/n2" times. ("n1/n2" is rounded up if it is not an integer.)

  • When the instruction is finished normally, the instruction execution complete flag M8029 turns ON. When the instruction is finished abnormally, the instruction execution abnormally complete flag M8329 turns ON.
  • When RBFM (FNC278) or WBFM (FNC279) instruction is executed in another step for the same unit number, the instruction non-execution flag M8328 is set to ON, and execution of such an instruction is paused. When execution of the other target instruction is complete, the paused instruction resumes.

16-bit Instruction · Mnemonic Operation Condition · 11 steps RBFM

Page 705 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 705 · click to enlarge
Page 705

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

31 Data Transfer 3 – FNC277 to FNC279

31.1 FNC278 – RBFM / Divided BFM Read 31

Related devices

FNC277-FNC279 Data Transfer 3

→ For the flag use methods for instruction execution complete and instruction execution

abnormally complete, refer to Subsection 6.5.2.

M8029 Instruction execution complete Turns ON when an instruction is finished normally.

M8328 Instruction non-execution Turns ON when RBFM (FNC278) or WBFM (FNC279) instruction in another step is executed for the same unit number.

FNC280-FNC289 High-Speed Processing 2

M8329 Instruction execution abnormally complete Turns ON when an instruction is finished abnormally.

Related instructions

FROM (FNC 78) Read from a special function block

FNC290-FNC299 Extension File Register Control

TO (FNC 79) Write to a special function block

WBFM (FNC279) Divided BFM write

Errors

An operation error is caused in the following case; The error flag M8067 turns ON, and the error code is stored in D8067.

FNC300-FNC305 FX 3U -CF-ADP

  • When the unit number "m1" does not exist (error code: K6708)

31.1.1 Common items between RBFM (FNC278) instruction and WBFM (FNC279) instruction

Specification of unit number of special function unit/block and buffer memory

→ For the connection method of special function units/blocks, number of connectable units/blocks,

and handling of I/O numbers, refer to the manual of the PLC used and special function unit/block.

1. Unit number "m1" of a special function unit/block Use the unit number to specify to which equipment the RBFM/WBFM instruction works. Setting range: K0 to K7

Unit No. 0

Unit No. 1

Unit No. 2

Unit No. 3

FX3UC- 32MT-LT (-2) main unit

A unit number is automatically assigned to each special function unit/block connected to the PLC. The unit number is assigned in the way "No. 0 → No. 1 → No. 2 ..." starting from the equipment nearest the main unit. When the main unit is the FX3UC-32MT-LT(-2), the unit number is assigned in the way "No. 1 → No. 2 → No. 3 ..." starting from the equipment nearest to the main unit because the CC-Link/LT master is built into the FX3UC-32MT-LT (-2).

2. Buffer memory (BFM) number "m2" Up to 32767 16-bit RAM memories are built in a special function unit/block, and they are called buffer memories. The buffer memory number is from "0" to "32766", and the contents are determined according to each special function unit/block. Setting range: K0 to K32766

→ For the contents of buffer memories, refer to the manual of the special function unit/block used.

A

B

Show 19 more labels / short text on this page
Device Name Description · Instruction Description · SFC•STL Programming · Interrupt Function · Built-in CC-Link/LT · I/O extension · Special function · Special function · I/O extension · Special function · block · block · block · block · block · Special Device · Error Code · Version Up Information · Execution Times
Page 706 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 706 · click to enlarge
Page 706

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

31 Data Transfer 3 – FNC277 to FNC279

31.1 FNC278 – RBFM / Divided BFM Read

Cautions

  • A watchdog timer error may occur when many numbers of points are transferred in one operation cycle. In such a case, take one of the following countermeasures: - Change the watchdog timer time By overwriting the contents of D8000 (watchdog timer time), the watchdog timer detection time is changed (initial value: K200). When the program shown below is input, the sequence program will be monitored with the new watchdog timer time.
Mitsubishi Electronics MELSEC FX3S — Cautions diagram (page 706)
Fig. 701 · Cautions

Watchdog timer refresh When WDT (FNC 07) instruction is not programmed, the value of D8000 becomes valid during END processing.

- Change the number of transferred points "n2" in each operation cycle Change the number of transferred points "n2" in each operation cycle to a smaller value.

  • Do not stop the driving of the instruction while it is being executed. If driving is stopped, the buffer memory (BFM) reading/writing processing is suspended, but the data acquired in the middle of reading/writing processing is stored
Mitsubishi Electronics MELSEC FX3S — Cautions diagram (page 706)
Fig. 702 · Cautions
  • When indexing is executed, the contents of index registers at the beginning of execution are used. Even if the contents of index registers are changed after the instruction, such changes do not affect the process of the instruction.
  • The contents of "n1" devices starting from change while the RBFM (FNC278) instruction is executed. After

execution of the instruction is completed, execute another instruction for "n1" devices starting from .

  • Do not update (change) the contents of "n1" devices starting from while the WBFM (FNC279) instruction is executed. If the contents are updated, the intended data may not be written to the buffer memories (BFM).
  • Do not update (change) the contents of "n1" buffer memories (BFM) starting from the buffer memory No. "m2" while the RBFM (FNC278) instruction is executed. If the contents are updated, the intended data may not be read.
Page 707 of the Mitsubishi Electronics MELSEC FX3S user manual — END
Page 707 · click to enlarge
Page 707

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

31 Data Transfer 3 – FNC277 to FNC279

31.1 FNC278 – RBFM / Divided BFM Read 31

Program example

FNC277-FNC279 Data Transfer 3

In the example shown below, data is read from and written to the buffer memories (BFM) in the unit No. 2 as follows:

  • When X000 is set to ON, data stored in D100 to D179 (80 points) are written to the buffer memories (BFM) #1001 to 1080 in the special function unit/block whose unit number is No. 2 by 16 points in each operation cycle.
  • When X001 is set to ON, the buffer memories (BFM) #2001 to 2080 (80 points) in the special function unit/block whose unit number is No. 2 are written to D200 to D279 by 16 points in each operation cycle.

FNC280-FNC289 High-Speed Processing 2

SET M0 The BFM write start flag is set to ON.

D100 to D179 (80 points) are written to the buffer memories #1001 to 1080 in the unit No. 2 (in 5 operation cycles).

M0

WBFM K2 K1001 D100 K80 K16

BFM write start M8029

FNC290-FNC299 Extension File Register Control

RST M0

The BFM write start flag is set to OFF.

M8328

Execution of the WBFM instruction is waited.

M8329

FNC300-FNC305 FX 3U -CF-ADP

RST M0

The BFM write start flag is set to OFF.

Instruction execution abnormally complete

SET M5 BFM read start

The BFM read start flag is set to ON.

The buffer memories #2001 to 2080 (80 points) in the unit No. 2 are read to D200 to D279 (in 5 operation cycles).

RBFM K2 K2001 D200 K80 K16 M5

BFM read start M8029

RST M5

The BFM read start flag is set to OFF.

M8328

Execution of the RBFM instruction is waited.

M8329

RST M5

The BFM read start flag is set to OFF.

Instruction execution abnormally complete

END

A

B

Show 11 more labels / short text on this page
BFM write start · Instruction execution complete · Y000 Instruction non-execution · SFC•STL Programming · Instruction execution complete · Y001 Instruction non-execution · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 708 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 708 · click to enlarge
Page 708

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

31 Data Transfer 3 – FNC277 to FNC279

31.2 FNC279 – WBFM / Divided BFM Write

31.2 FNC279 – WBFM / Divided BFM Write

Outline

This instruction writes data to continuous buffer memories (BFM) in a special function unit/block over several operation cycles by the time division method. This instruction is convenient for writing send data, etc. to buffer memories in a special function unit/block for communication by the time division method. TO (FNC 79) instruction is also available for writing data to the buffer memory (BFM).

→ For TO (FNC 79) instruction, refer to Section 15.10.

1. Instruction format

Mnemonic Operation Condition 32-bit Instruction

WBFM

Continuous Operation −

2. Set data

Mitsubishi Electronics MELSEC FX3S — WBFM diagram (page 708)
Fig. 703

m2 Head buffer memory (BFM) number [0 to 32766]

Head device number storing data to be written to buffer memory (BFM)

n1 Number of all buffer memories (BFM) to be written [1 to 32767]

n2 Number of points transferred in one operation cycle [1 to 32767]

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 708)
Fig. 704 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

SExcept special data register (D)

Explanation of function and operation

1. 16-bit operation (WBFM)

"n1" word units from in the PLC are written to buffer memory (BFM) location # "m2" in special function unit/ block No. "m1". While transferring, "n1" is divided by "n2" so n1/n2 words (rounded up when there is a remainder) are transferred per scan time.

→ For the unit No., buffer memory (BFM) No., cautions, and program example,

refer to Subsection 31.1.1.

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 708)
Fig. 705 · Explanation of function and operation

*1 "n2" points are written in each operation cycle. Writing is executed in "n1/n2" transfers. ("n1/n2" is rounded up if it is not an integer.)

  • When the instruction is finished normally, the instruction execution complete flag M8029 turns ON. When the instruction is finished abnormally, the instruction execution abnormally complete flag M8329 turns ON.
  • When the RBFM (FNC278) or WBFM (FNC279) instruction is executed in another step for the same unit number, the instruction non-execution flag M8328 is set to ON, and execution of such an instruction is paused. When execution of the first target instruction is complete, the paused instruction resumes.

16-bit Instruction · Mnemonic Operation Condition · 11 steps WBFM

Page 709 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 709 · click to enlarge
Page 709

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

31 Data Transfer 3 – FNC277 to FNC279

31.2 FNC279 – WBFM / Divided BFM Write 31

Related devices

FNC277-FNC279 Data Transfer 3

→ For the flag use methods for instruction execution complete and instruction execution

abnormally complete, refer to Subsection 6.5.2.

M8029 Instruction execution complete Turns ON when an instruction is finished normally.

M8328 Instruction non-execution Turns ON when the RBFM (FNC278) or WBFM (FNC279) instruction in another step is executed for the same unit number.

FNC280-FNC289 High-Speed Processing 2

M8329 Instruction execution abnormally complete Turns ON when an instruction is finished abnormally.

Related instructions

FROM (FNC 78) Read from a special function block

FNC290-FNC299 Extension File Register Control

TO (FNC 79) Write to a special function block

RBFM (FNC278) Divided BFM read

Errors

An operation error is caused in the following case; The error flag M8067 turns ON, and the error code is stored in D8067.

FNC300-FNC305 FX 3U -CF-ADP

  • When the unit number "m1" does not exist (error code: K6708)

A

B

Show 8 more labels / short text on this page
Device Name Description · Instruction Description · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 710 of the Mitsubishi Electronics MELSEC FX3S user manual — 32. High-Speed Processing 2 – FNC280 to FNC289
Page 710 · click to enlarge
Page 710

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

32 High-Speed Processing 2 – FNC280 to FNC289

32. High-Speed Processing 2 – FNC280 to FNC289

FNC No. Mnemonic Symbol Function Reference

280 HSCT High-Speed Counter Compare With Data Table Section 32.1

n HSCT D S2 m S1

Show 9 more labels / short text on this page
281 − − · 282 − − · 283 − − · 284 − − · 285 − − · 286 − − · 287 − − · 288 − − · 289 − −
Page 711 of the Mitsubishi Electronics MELSEC FX3S user manual — S 1 S 1 S 1
Page 711 · click to enlarge
Page 711

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

32 High-Speed Processing 2 – FNC280 to FNC289

32.1 FNC280 – HSCT / High-Speed Counter Compare With Data Table 31

32.1 FNC280 – HSCT / High-Speed Counter Compare With Data Table

FNC277-FNC279 Data Transfer 3

Outline

This instruction compares the current value of a high-speed counter with a data table of comparison points, and then sets or resets up to 16 output devices.

FNC280-FNC289 High-Speed Processing 2

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

HSCT D

FNC290-FNC299 Extension File Register Control

2. Set data

Operand Type Description Data Type

Head device number storing the data table 16- or 32-bit binary

m Number of comparison points in data table [1≤m≤128] 16-bit binary

FNC300-FNC305 FX 3U -CF-ADP

High-speed counter number (C235 to C255) 32-bit binary

Head device number to which the operation status is output Bit

n Number of devices to which the operation status is output [1≤n≤16] 16-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

Only a high-speed counter C235 to C255 can be specified in "S".

Explanation of function and operation

1. 32-bit operation (DHSCT)

The current value of a high-speed counter specified in is compared with the data table shown below which has

(3±m) points stored in and later, and the operation output set value (ON or OFF) specified in the data table is

output to to +n-1.

D D

DHSCT S1 ‚ m D ‚ n S2 ‚

Data table used for comparison

A

Comparison point number Comparison value Operation output set value

(SET [1] or RESET [0]) Operation output destination

S 1 S 1 S 1

1 +4, +3 +5

S 1 S 1 S 1

2 +7 +6 +8

S 1 S 1 S 1

D D

B

m-2 +3m-5, +3m-6 +3m-4

S 1 S 1 S 1

m-1 +3m-2, +3m-3 +3m-1

S 1 S 1 S 1

Show 22 more labels / short text on this page
Mnemonic Operation Condition · 32-bit Instruction · 21 steps DHSCT · Continuous Operation · ⎯ ⎯ ⎯ · SFC•STL Programming · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · m 3 3 · Interrupt Function · n 3 3 · Special Device · Command · Error Code · input · Version Up Information · 0 +1, +2 · to +n-1 · Execution Times
Page 712 of the Mitsubishi Electronics MELSEC FX3S user manual — D D
Page 712 · click to enlarge
Page 712

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

32 High-Speed Processing 2 – FNC280 to FNC289

32.1 FNC280 – HSCT / High-Speed Counter Compare With Data Table

Operation output setting (SET [1] or RESET [0]) [Up to 16 points]

Mitsubishi Electronics MELSEC FX3S — Operation output setting (SET [1] or RESET [0]) [Up to 16 points] diagram (page 712)
Fig. 706 · Operation output setting (SET [1] or RESET [0]) [Up…

Operation output setting 1 0 1 0 0 1 1 1 0 0 0 1 0 1 1 0

Operation output setting = HA716 When the current value of the high-speed counter becomes equivalent to the comparison value, the operation output setting pattern is output. In the case of " = Y000, n = K10"

1. When this instruction is executed, the data table is set as the comparison target.
2. When the current value of the high-speed counter, specified in , becomes equivalent to the comparison value in the data table, the corresponding operation output specified in the data table is output to

D D

to +n-1.

If an output (Y) is specified in , the output processing is executed immediately without waiting for the output refresh executed by the END instruction. When specifying an output (Y), make sure that the least significant digit of the device number is “0”. Examples: Y000, Y010 and Y020

3. Immediately after step 2), “1” is added to the current table counter value D8138.
4. The next comparison point is set as the comparison target data.
5. Steps 2) and 3) are repeated until the current value of the table counter D8138 becomes "m". When the current value becomes "m", the instruction execution complete flag M8138 turns ON, and the execution returns to step 1). At this time, the table counter D8138 is reset to "0".
6. When the command contact is set to OFF, execution of the instruction is stopped and the table counter D8138 is reset to “0”.
Page 713 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 713 · click to enlarge
Page 713

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

32 High-Speed Processing 2 – FNC280 to FNC289

32.1 FNC280 – HSCT / High-Speed Counter Compare With Data Table 31

Operation example

FNC277-FNC279 Data Transfer 3

X010 FNC280

DHSCT D200 K5 C235 Y010 K3

FNC 54 DHSCR C235 C235 M8000

K900

FNC280-FNC289 High-Speed Processing 2

Comparison data SET/RESET pattern

Table counter D8138 Device Comparison

value Device Operation output

0 D201,D200 K321 D202 H0001 0 ↓

1 D204,D203 K432 D205 H0007 1 ↓

2 D207,D206 K543 D208 H0002 2 ↓

FNC290-FNC299 Extension File Register Control

3 D210,D209 K764 D211 H0000 3 ↓

4 D213,D212 K800 D214 H0003 4↓ (Repeated from “0↓”)

FNC300-FNC305 FX 3U -CF-ADP

OFF ON

Y010

OFF *1

ON

Because DHSCT instruction is not executed, the operation outputs are not changed by this instruction.

Y011

OFF *1

ON

Y012

OFF *1

ON

1 2 3 4

0 1 2 3

M8138

ON OFF

*1. If this instruction is not executed, no processing is executed for outputs. In the operation example shown above, the command contact is “OFF”.

2. Related device

A

M8138 HSCT (FNC280) instruction execution complete flag Turns ON when the operation for the final table No. "m-1" is completed.

D8138 HSCT (FNC280) table counter Stores the comparison point number handled as the comparison target.

B

Show 20 more labels / short text on this page
Comparison point number · set value · Current value · of C235 · 900 900 · 800 764 · 764 543 · SFC•STL Programming · Command contact · Time · Interrupt Function · HSCT table · Special Device · counter · HSCT instruction · execution complete flag · Error Code · Device Name Description · Version Up Information · Execution Times
Page 714 of the Mitsubishi Electronics MELSEC FX3S user manual — Errors
Page 714 · click to enlarge
Page 714

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

32 High-Speed Processing 2 – FNC280 to FNC289

32.1 FNC280 – HSCT / High-Speed Counter Compare With Data Table

Cautions

  • This instruction can be executed only once in a program. If this instruction is programmed two or more times, an operation error is caused by the second instruction and later, and the instruction will not be executed. (error code: K6765)
  • This instruction constructs the data table at the END instruction of the first execution of the instruction. Accordingly, the operation output works after the second scan and later.
  • With regard to DHSCT (FNC280), DHSCS (FNC 53), DHSCR (FNC 54) and DHSZ (FNC 55) instructions, up to 32 instructions can be executed in one operation cycle. An operation error is caused by the 33rd instruction and later, and the instruction will not be executed. (error code: K6705)
  • If an output (Y) is specified in , the output processing is executed immediately without waiting for the output refresh executed by END instruction. When specifying an output (Y), make sure that the least significant digit of the device number is “0”. Examples: Y000, Y010 and Y020
  • When a high-speed counter specified in is indexed with index, all high-speed counters are handled as software counters.
  • For this instruction, only one comparison point (one line) is handled as the comparison target at one time. Processing will not move to the next comparison point until the current counter value becomes equivalent to the comparison point currently selected as the comparison target. If the current value of a high-speed counter executes up counting using the comparison data table shown in the operation example on the previous page, make sure to execute the instruction while the current value of the highspeed counter is smaller than the comparison value in comparison point No. 1.
  • When the DHSCT instruction is used with a hardware counter (C235, C236, C237, C238, C239, C240, C244 (OP), C245 (OP), C246, C248 (OP), C251, C253), the hardware counter is automatically switched to a software counter, and the maximum frequency and total frequency are affected.

Errors

An operation error occurs in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When any devices other than high-speed counters C235 to C255 are specified in (error code: K6706)
  • When the “3m-1”th device from a device specified in exceeds the last number of the device (error code: K6706)
  • When the “n”th device from a device specified in exceeds the last number of the device (error code: K6706)
  • When this instruction is used two or more times in a program (error code: K6765)
  • With regard to DHSCT (FNC280), DHSCS (FNC 53), DHSCR (FNC 54) and DHSZ (FNC 55) instructions, up to 32 instructions can be executed in one operation cycle. An operation error is caused by the 33rd instruction and later, and the instruction will not be executed. (error code: K6705)
Page 715 of the Mitsubishi Electronics MELSEC FX3S user manual — 32.1 FNC280 – HSCT / High-Speed Counter Compare With Data Table 31
Page 715 · click to enlarge
Page 715

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

32 High-Speed Processing 2 – FNC280 to FNC289

32.1 FNC280 – HSCT / High-Speed Counter Compare With Data Table 31

Mitsubishi Electronics MELSEC FX3S — 32.1 FNC280 – HSCT / High-Speed Counter Compare With Data Table 31 diagram (page 715)
Fig. 707 · 32.1 FNC280 – HSCT / High-Speed Counter Compare With…

In the program shown below, the current value of C235 (counting X000) is compared with the comparison data table set in R0 and later, and a specified pattern is output to Y010 to Y013.

4 R13,R12 K300 R14 H0008 4↓ (Repeated from “0↓”)

Page 716 of the Mitsubishi Electronics MELSEC FX3S user manual — 33. Extension File Register Control – FNC290 to FNC299
Page 716 · click to enlarge
Page 716

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33. Extension File Register Control – FNC290 to FNC299

Mitsubishi Electronics MELSEC FX3S — 33. Extension File Register Control – FNC290 to FNC299 diagram (page 716)
Fig. 708 · 33. Extension File Register Control – FNC290 to FNC2…
Page 717 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 717 · click to enlarge
Page 717

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.1 FNC290 – LOADR / Load From ER 31

33.1 FNC290 – LOADR / Load From ER

FNC277-FNC279 Data Transfer 3

Outline

This instruction reads the current values of extension file registers (ER) stored in the attached memory cassette (flash memory or EEPROM) or EEPROM built into the PLC, and transfers them to extension registers (R) stored in the RAM in the PLC.

FNC280-FNC289 High-Speed Processing 2

1. Instruction format

32-bit Instruction P

Mnemonic Operation Condition 16-bit Instruction

LOADR

5 steps LOADR LOADRP

Continuous Operation Pulse (Single) Operation

FNC290-FNC299 Extension File Register Control

2. Set data

Operand Type Description Data Type

Device number of extension register to which data is to be transferred (The extension file register with the same number is handled as the data transfer source.)

16-bit binary n Number of points to be read (transferred) [FX3G/FX3GC: 1 ≤ n ≤ 24000, FX3U/FX3UC: 0 ≤ n ≤ 32767]

FNC300-FNC305 FX 3U -CF-ADP

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

n 3 3 3

Explanation of function and operation

1. 16-bit operation (LOADR and LOADRP)

1. In FX 3U /FX 3UC PLCs The contents (current values) of extension file registers (ER) stored in a memory cassette (flash memory) with the

same numbers as the extension registers specified by to +n-1 are read, and transferred to the

S S

extension registers specified by to +n-1 stored in the PLC's built-in RAM.

S S

FNC290 LOADRP S ‚ n

Extension file registers (ER) inside memory cassette

Extension registers (R) inside built-in RAM

E

E +1

E +2

E +3

A

S ‚ S ‚

  • Reading (transferring) is executed in device units. Up to 32,768 devices can be read (transferred).

B

  • As apposed to the SAVER (FNC291), INITR (FNC292) and LOGR (FNC293) instructions, it is not necessary to execute this instruction in sector units.
  • If “n” is set to “0”, it is handled as “32768” when the instruction is executed.
Show 22 more labels / short text on this page
Mnemonic Operation Condition · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · SFC•STL Programming · Interrupt Function · Command · input · Special Device · Read (transfer) · Error Code · +1 · +2 · +3 · E +n-2 · +n-2 · Version Up Information · E +n-1 · +n-1 · Execution Times
Page 718 of the Mitsubishi Electronics MELSEC FX3S user manual — S S
Page 718 · click to enlarge
Page 718

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.1 FNC290 – LOADR / Load From ER

2. In FX 3G /FX 3GC PLCs a) When a memory cassette is connected (A memory cassette can be connected only to FX 3G PLC.)

The contents (current values) of extension file registers (ER) stored in a memory cassette (EEPROM) with the

same numbers as the extension registers specified by to +n-1 are read, and

S S

transferred to the extension registers specified by to +n-1 stored in the PLC's built-in RAM.

S S

Mitsubishi Electronics MELSEC FX3S — S S diagram (page 718)
Fig. 709
  • Reading (transferring) is executed in device units. Up to 24,000 devices can be read (transferred).

b) When a memory cassette is not connected

In the program example below, the contents (current value) of extension file registers (ER) which are stored in

the EEPROM built in the PLC and have the same device numbers as extension registers to +n- 1 are read, and transferred to extension registers (R) which are stored in the RAM built in the PLC and have

S S

Mitsubishi Electronics MELSEC FX3S — S S diagram (page 718)
Fig. 710
  • Reading (transferring) is executed in device units. Up to 24,000 devices can be read (transferred).
Page 719 of the Mitsubishi Electronics MELSEC FX3S user manual — ER1 K100
Page 719 · click to enlarge
Page 719

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.1 FNC290 – LOADR / Load From ER 31

Caution

FNC277-FNC279 Data Transfer 3

1. Allowable number of writes to the memory Note the following cautions on access to extension file registers.
  • In FX 3U /FX 3UC PLCs Data can be written to the memory cassette (flash memory) up to 10,000 times. Every time the INITR (FNC292), RWER (FNC294) or INITER (FNC295) instruction is executed, it is counted as a write to the memory. Make sure not to exceed the allowable writes. When a continuous operation type instruction is used, data is written to the memory in every operation cycle of the PLC. To prevent this, make sure to use a pulse operation type instruction.

FNC280-FNC289 High-Speed Processing 2

Execution of the LOADR (FNC290), SAVER (FNC291) or LOGR (FNC293) instruction is not counted as a write to the memory. However, it is necessary to initialize the writing target sector before executing the SAVER (FNC291) or LOGR (FNC293) instruction. Every time the INITR (FNC292) or INITER (FNC295) instruction is executed, it is counted as a number of times of writing to the memory. Make sure not to exceed the allowable number of writes.

FNC290-FNC299 Extension File Register Control

  • In FX 3G /FX 3GC PLCs Data can be written to the memory cassette (EEPROM) up to 10,000 times, and to the built-in memory (EEPROM) up to 20,000 times. Every time the RWER (FNC294) instruction is executed, it is counted as a write to the memory. Make sure not to exceed the allowable number of writes. When a continuous operation type instruction is used, data is written to the memory in every operation cycle of the PLC. To prevent this, make sure to use a pulse operation type instruction. Execution of the LOADR (FNC290)instruction is not counted as a write to the memory.

FNC300-FNC305 FX 3U -CF-ADP

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When the last device number to be transferred exceeds “32767” (error code: K6706) At this time, devices up to R32767 are read and transferred.
  • When a memory cassette is not connected (error code: K6771) *1

*1. An operation error is not caused in FX3G PLC because the contents of extension file registers stored in the EEPROM built in the PLC are read if a memory cassette is not connected.

Program example

In the program example shown below, the contents (current value) of 4,000 extension file registers ER1 to ER4000 inside the memory cassette are read, and transferred to 4,000 extension registers R1 to R4000 inside the built-in RAM.

M0 FNC290

LOADR R1 K4000

Extension file registers (ER) inside memory cassette

Extension registers (R) inside built-in RAM

ER1 K100

R1 K100

ER2 K50

R2 K50

ER3 H0003

R3 H0003

ER4 H0101

R4 H0101

A

ER3999 K55

R3999 K55

ER4000 K59

R4000 K59

B

Show 12 more labels / short text on this page
SFC•STL Programming · Interrupt Function · Special Device · Device number · Current · Device number · Current · value Read (transfer) · value · Error Code · Version Up Information · Execution Times
Page 720 of the Mitsubishi Electronics MELSEC FX3S user manual — S S
Page 720 · click to enlarge
Page 720

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.2 FNC291 – SAVER / Save to ER

33.2 FNC291 – SAVER / Save to ER

Outline

This instruction writes the current values of the extension registers (R) stored in the PLC's built-in RAM to extension file registers (ER) stored in a memory cassette (flash memory) in sector units (2048 points). The RWER (FNC294) instruction provided in FX3UC PLC Ver. 1.30 or later and FX3U PLC only writes (transfers) a arbitrary number of points. It is not necessary to execute the INITR (FNC292) or the INITER (FNC295) instruction when RWER instruction is used.

→ For RWER instruction, refer to Section 33.5.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 720)
Fig. 711 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 720)
Fig. 712 · 2. Set data

Head device number of extension register sector to which data is to be written (Only the head device number of a sector of extension registers can be specified.)

16-bit binary n Number of points written (transferred) in one operation cycle [0 ≤ n ≤ 2048]

Device number storing the number of already written points

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 720)
Fig. 713 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 16-bit operation (SAVER)

The contents (current values) of extension registers (R) specified by to +2047 are written (transferred) to extension file registers (ER) inside a memory cassette (flash memory) with the same device numbers in “2048/n” operation cycles (“2048/n+1” cycles if there is a remainder).

S S

Mitsubishi Electronics MELSEC FX3S — S S diagram (page 720)
Fig. 714

While the instruction is being executed, the number of points already written is stored in .

Extension file registers (ER) inside memory cassette Extension registers (R) inside built-in RAM *1

*1 “n” points are written (transferred) in each operation cycle.

Page 721 of the Mitsubishi Electronics MELSEC FX3S user manual — M8029
Page 721 · click to enlarge
Page 721

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.2 FNC291 – SAVER / Save to ER 31

  • Extension file registers are written in sector units (2048 points). The table below shows the head device number in each sector:

FNC277-FNC279 Data Transfer 3

Sector number Head device number Written device range Sector number Head device number Written device range

Sector 0 R0 ER0 to ER2047 Sector 8 R16384 ER16384 to ER18431

Sector 1 R2048 ER2048 to ER4095 Sector 9 R18432 ER18432 to ER20479

Sector 2 R4096 ER4096 to ER6143 Sector 10 R20480 ER20480 to ER22527

FNC280-FNC289 High-Speed Processing 2

Sector 3 R6144 ER6144 to ER8191 Sector 11 R22528 ER22528 to ER24575

Sector 4 R8192 ER8192 to ER10239 Sector 12 R24576 ER24576 to ER26623

Sector 5 R10240 ER10240 to ER12287 Sector 13 R26624 ER26624 to ER28671

Sector 6 R12288 ER12288 to ER14335 Sector 14 R28672 ER28672 to ER30719

Sector 7 R14336 ER14336 to ER16383 Sector 15 R30720 ER30720 to ER32767

  • If "n" is set to "0", it is handled as "2048" when the instruction is executed.

FNC290-FNC299 Extension File Register Control

  • When writing (transferring) of 2,048 points is finished, execution of the instruction is completed and the instruction execution complete flag M8029 turns ON.
  • The number of already written points is stored in .
2. Related device → For the instruction execution complete flag use method, refer to Subsection 6.5.2.

FNC300-FNC305 FX 3U -CF-ADP

Device number Name Description

When execution of the target instruction is completed, the instruction execution complete flag M8029 turns ON. In a program, however, there may be two or more instructions which use the flag M8029. To avoid confusion, make sure to use the NO contact of this flag immediately under the SAVER instruction so that this flag works only for the SAVER instruction.

M8029 Instruction execution complete flag

Cautions

1. Cautions on writing data to a memory cassette Memory cassettes use flash memory. Note the following when writing data to extension file registers in a memory cassette with the FNC291 instruction.
  • It takes about 340ms to write 2,048 points. If “n” is set to K0 or K2048, the operation cycle for executing this instruction becomes longer than about 340ms. If the operation cycle is severely affected, write data in two or more operation cycles. When writing data in two or more operation cycles, set “n” ranging from K1 to K1024.
  • Do not abort execution of this instruction in the middle of operation. If execution is aborted, unexpected data may be written to extension file registers. If execution of this instruction is aborted by turning OFF the power, execute the instruction again using step 2 described below after turning the power ON again.

SET M

M FNC295 INITERP S n

SAVER S n D

Instruction execution complete flag

M8029

A

RST M

B

Show 7 more labels / short text on this page
SFC•STL Programming · Interrupt Function · Special Device · Write command · Error Code · Version Up Information · Execution Times
Page 722 of the Mitsubishi Electronics MELSEC FX3S user manual — [1] When storing sectors of 2,048 extension registers (R) to extension file
Page 722 · click to enlarge
Page 722

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.2 FNC291 – SAVER / Save to ER

2. Initialization of extension file registers Execute the INITER (FNC295) or INITR (FNC292) instruction to target extension file registers (ER) before executing the SAVER instruction. If the SAVER instruction is driven before the INITER (FNC295) or INITR (FNC292) instruction is executed, an operation error (error code: K6770) may occur. To avoid this an operation error, make a program executing the SAVER instruction as shown in the following sequence:
  • If the FX 3U /FX 3UC PLC is Ver. 1.30 or later

[1] When storing sectors of 2,048 extension registers (R) to extension file

registers (ER) 1) Execute the INITER (FNC295) instruction to the target extension file registers (ER) specified as targets in the SAVER instruction. 2) Execute the SAVER instruction.

[2] When storing an arbitrary number of extension registers (R) to extension file registers (ER)

Use the RWER instruction.

→ For RWER (FNC294) instruction, refer to Section 33.5.

  • When the FX 3UC PLC is before Ver. 1.30

[1] When storing sectors of 2,048 extension registers (R) in one sector to

extension file registers (ER) If the extension registers (R) have data to be stored in extension file registers (ER), use the procedure [2]. 1) Execute the INITR (FNC292) instruction to extension registers (R) and extension file registers (ER) specified as targets of the SAVER instruction. 2) Store data to extension registers (R) specified as targets. 3) Execute the SAVER instruction.

[2] When storing sector of 2,048 extension registers (R) in one sector to extension file registers (ER)

1) Temporarily withdraw the data of the extension registers (R) specified as targets of the SAVER instruction to data registers or 2048 unused extension registers (R) by using the BMOV (FNC 15) instruction. 2) Execute the INITR (FNC292) instruction to extension registers (R) and extension file registers (ER) specified as targets of the SAVER instruction. 3) Return the data of 2048 points temporarily withdrawn in step 1) to extension registers (R) specified as targets by using the BMOV (FNC 15) instruction. 4) Execute the SAVER instruction.

3. Allowable number of writes to the memory Note the following cautions on access to extension file registers.
  • Data can be written to the memory cassette (flash memory) up to 10,000 times. Every time the INITR (FNC292), RWER (FNC294) or INITER (FNC295) instruction is executed, it is counted as a write to the memory. Make sure not to exceed the allowable number of writes. When a continuous operation type instruction is used, data is written to the memory in every operation cycle of the PLC. To prevent this, make sure to use a pulse operation type instruction.
  • Execution of the LOADR (FNC290), SAVER (FNC291) or LOGR (FNC293) instruction is not counted as a write to the memory. However, it is necessary to initialize the writing target sector before executing the SAVER (FNC291) or LOGR (FNC293) instruction. Every time the INITR (FNC292) or INITER (FNC295) instruction is executed, it is counted as a write to the memory. Make sure not to exceed the allowable number of writes.
Page 723 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 723 · click to enlarge
Page 723

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.2 FNC291 – SAVER / Save to ER 31

Errors

FNC277-FNC279 Data Transfer 3

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When any device number other than the head device number of a sector of extension file registers is set to (error code: K6706)
  • When a memory cassette is not connected (error code: K6771)

FNC280-FNC289 High-Speed Processing 2

  • When the protect switch of the memory cassette is set to ON (error code: K6770)
  • When the collation result after data writing is a "mismatch" due to omission of initialization or for another reason (error code: K6770) When this error occurs, the current values (data) of extension registers (R) may be lost. To avoid the data loss, back up the data of extension registers (R) in advance using the following procedure:
1. Set the PLC mode to STOP.
2. Create a new project in GX Works2. This step is not necessary if it is alright to overwrite the current project.

FNC290-FNC299 Extension File Register Control

3. Read the contents of extension registers (R) to GX Works2. [1] Select “Online” → “Read from PLC..." to
Mitsubishi Electronics MELSEC FX3S — Errors diagram (page 723)
Fig. 715 · Errors

display the Online Data Operation dialog box. [2] Click "PLC Parameter/Network Parameter"

and "Device Data/File Register" to check mark each of them. [3] Click [Execute] button. [4] When reading is completed, save the project.

FNC300-FNC305 FX 3U -CF-ADP

4. Change the current program inside the PLC to the program shown in “Cautions on writing data to a memory cassette” in “Cautions” on the previous page.
5. Write the data which was temporarily withdrawn to GX Works2 to the PLC. [1] Select “Online” → “Write to PLC...” to display
Mitsubishi Electronics MELSEC FX3S — FNC300-FNC305 FX 3U -CF-ADP diagram (page 723)
Fig. 716

the Online Data Operation dialog box. [2] Click "PLC Parameter/Network Parameter"

and “MAIN” to check mark each of them. [3] Click [Execute] button.

6. Change the PLC mode from STOP to RUN, execute the program, and store the data to the extension file registers inside the memory cassette.

A

B

Show 6 more labels / short text on this page
SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 724 of the Mitsubishi Electronics MELSEC FX3S user manual — Operation
Page 724 · click to enlarge
Page 724

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.2 FNC291 – SAVER / Save to ER

Program examples

1. In the case of FX 3U PLC Ver. 2.20 or later and FX 3UC PLC Ver. 1.30 or later

In the example shown below, only extension registers R10 to R19 (in sector 0) need to be updated in the extension file registers (ER). When X000 is set to ON, sector 0 (head device R0) is written to the extension file registers 128 points at a time. (128 points are written in one operation cycle)

Program

Mitsubishi Electronics MELSEC FX3S — Program diagram (page 724)
Fig. 717 · Program

Operation

Mitsubishi Electronics MELSEC FX3S — Operation diagram (page 724)
Fig. 718 · Operation
Page 725 of the Mitsubishi Electronics MELSEC FX3S user manual — 33.2 FNC291 – SAVER / Save to ER 31
Page 725 · click to enlarge
Page 725

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.2 FNC291 – SAVER / Save to ER 31

Mitsubishi Electronics MELSEC FX3S — 33.2 FNC291 – SAVER / Save to ER 31 diagram (page 725)
Fig. 719 · 33.2 FNC291 – SAVER / Save to ER 31
Page 726 of the Mitsubishi Electronics MELSEC FX3S user manual — Operation
Page 726 · click to enlarge
Page 726

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.2 FNC291 – SAVER / Save to ER

2. In the case of FX 3UC PLC before Ver. 1.30

In the example shown below, only extension registers R10 to R19 (in sector 0) need to be updated in the extension file registers (ER). When X000 is set to ON, sector 0 (head device R0) is written to the extension file registers 128 points at a time. (128 points are written in one operation cycle)

Program

Mitsubishi Electronics MELSEC FX3S — Program diagram (page 726)
Fig. 720 · Program

Operation

Mitsubishi Electronics MELSEC FX3S — Operation diagram (page 726)
Fig. 721 · Operation
Page 727 of the Mitsubishi Electronics MELSEC FX3S user manual — 33.2 FNC291 – SAVER / Save to ER 31
Page 727 · click to enlarge
Page 727

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.2 FNC291 – SAVER / Save to ER 31

Mitsubishi Electronics MELSEC FX3S — 33.2 FNC291 – SAVER / Save to ER 31 diagram (page 727)
Fig. 722 · 33.2 FNC291 – SAVER / Save to ER 31
Page 728 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 728 · click to enlarge
Page 728

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.3 FNC292 – INITR / Initialize R and ER

33.3 FNC292 – INITR / Initialize R and ER

Outline

This instruction initializes extension registers (R) to “HFFFF” () in the RAM built into the PLC and extension file registers in a memory cassette (flash memory) before data logging using the LOGR (FNC293) instruction. In FX3UC PLC before Ver. 1.30, use this instruction to initialize extension file registers (ER) before writing data to them using SAVER (FNC291) instruction. In FX3UC PLC Ver. 1.30 or later and FX3U PLC, the INITER (FNC295) instruction is also provided to initialize only extension file registers (ER) to "HFFFF" () in a memory cassette (flash memory) in units of sector.

→ For the SAVER (FNC291) instruction, refer to Section 33.2.

→ For the LOGR (FNC293) instruction, refer to Section 33.4. → For the INITER (FNC295) instruction, refer to Section 33.6.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 728)
Fig. 723 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 728)
Fig. 724 · 2. Set data

Head device number of extension register and extension file register*1 sector to be initialized It is possible to specify only the head device number in a sector of extension registers. 16-bit binary

n Number of sectors of extension registers and extension file registers to be initialized

*1. When a memory cassette is not used, extension file registers (ER) are not initialized.

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 728)
Fig. 725 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 16-bit operation (INITR and INITRP)

“n” sectors of extension registers in the PLC’s built-in RAM starting from the one specified by and “n” sectors of extension file registers in a memory cassette (flash memory) having the same device numbers are initialized to “HFFFF” (). Initialization is executed in sector units.

INITRP S ‚ n

Command · input

Page 729 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 729 · click to enlarge
Page 729

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.3 FNC292 – INITR / Initialize R and ER 31

The table below shows the head device number in each sector:

FNC277-FNC279 Data Transfer 3

number Initialized device range Sector number

number Initialized device range

Sector 0 R0 R0 to R2047, ER0 to ER2047 Sector 8 R16384 R16384 to R18431, ER16384 to ER18431

Sector 1 R2048 R2048 to R4095, ER2048 to ER4095 Sector 9 R18432 R18432 to R20479, ER18432 to ER20479

FNC280-FNC289 High-Speed Processing 2

Sector 2 R4096 R4096 to R6143, ER4096 to ER6143 Sector 10 R20480 R20480 to R22527, ER20480 to ER22527

Sector 3 R6144 R6144 to R8191, ER6144 to ER8191 Sector 11 R22528 R22528 to R24575, ER22528 to ER24575

Sector 4 R8192 R8192 to R10239, ER8192 to ER10239 Sector 12 R24576 R24576 to R26623, ER24576 to ER26623

Sector 5 R10240 R10240 to R12287, ER10240 to ER12287 Sector 13 R26624 R26624 to R28671, ER26624 to ER28671

FNC290-FNC299 Extension File Register Control

Sector 6 R12288 R12288 to R14335, ER12288 to ER14335 Sector 14 R28672 R28672 to R30719, ER28672 to ER30719

Sector 7 R14336 R14336 to R16383, ER14336 to ER16383 Sector 15 R30720 R30720 to R32767, ER30720 to ER32767

Operation (when a memory cassette is used)

FNC300-FNC305 FX 3U -CF-ADP

  • Extension registers (R) [inside the built-in RAM]
  • Extension file registers (ER) [inside the memory cassette]

Before execution After execution Before execution After execution

S S

H0010 HFFFF H1234 HFFFF

S S

+1 H0020 HFFFF +1 H5678 HFFFF

S S

+2 H0011 HFFFF +2 H90AB HFFFF

+(2048×n)-1 HABCD HFFFF +(2048×n)-1 HCDEF HFFFF

S S

Caution

1. Initialization of two or more sectors When a memory cassette is attached, 18 ms is required to initialize one sector. (When a memory cassette is not attached, only 1 ms or less is required to initialize one sector.) When initializing two or more sectors, take either measure shown below.
  • Set a large value to the watchdog timer D8000 using the following program

M8002 FNC 12

MOV K {{{ D8000

Guideline of the watchdog timer set value

A value acquired by the following procedure can be regarded as the guideline of the watchdog timer set value. If an acquired value is 200 ms or less, however, it is not necessary to change the watchdog timer set value.

1. Write a program to be executed from GX Works2 to the PLC. [Online] → [Write to PLC...]

A

2. Set the current value of D8000 (unit: ms) to "1000" using the modify value function in GX Works2. [Debug] → [Modify Value]
3. Set the PLC mode to RUN, and execute the program. (Execute this instruction also.)
4. Monitor the maximum scan time D8012 (unit: 0.1 ms) using the device/buffer memory batch monitor function in GX Works2.
5. Set the watchdog timer to the maximum scan time (D8012) or more. D8012 stores the maximum scan time in increments of 0.1 ms. Rough guide to the watchdog timer set value D8000 (unit: ms) is the "value stored in D8012 divided by 10" added by 50 to 100.

B

Show 14 more labels / short text on this page
Sector number · Head device · Head device · Current value · Current value · Device number · Device number · SFC•STL Programming · Interrupt Function · Special Device · Initial pulse · Error Code · Version Up Information · Execution Times
Page 730 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 730 · click to enlarge
Page 730

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.3 FNC292 – INITR / Initialize R and ER

  • Setting the WDT (FNC 07) instruction just before and after the INITR instruction as shown below:
Mitsubishi Electronics MELSEC FX3S — 33.3 FNC292 – INITR / Initialize R and ER diagram (page 730)
Fig. 726 · 33.3 FNC292 – INITR / Initialize R and ER

If the processing time of the INITR command exceeds 200ms, set the watchdog timer value D8000 (unit: ms) to the processing time or more.

2. Allowable number of writes to the memory Note the following cautions on access to extension file registers.
  • Data can be written to the memory cassette (flash memory) up to 10,000 times. Every time the INITR (FNC292), RWER (FNC294) or INITER (FNC295) instruction is executed, it is counted as a write to the memory. Make sure not to exceed the allowable number of writes. When a continuous operation type instruction is used, data is written to the memory in every operation cycle of the PLC. To prevent this, make sure to use a pulse operation type instruction.
  • Execution of the LOADR (FNC290), SAVER (FNC291) or LOGR (FNC293) instruction is not counted as a write to the memory. However, it is necessary to initialize the writing target sector before executing the SAVER (FNC291) or LOGR (FNC293) instruction. Every time the INITR (FNC292) or INITER (FNC295) instruction is executed, it is counted as a write to the memory. Make sure not to exceed the allowable number of writes.

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When any device number other than the head device number of a sector of extension file registers is set to (error code: K6706)
  • When a device number to be initialized exceeds "32767" (error code: K6706) In this case, devices up to R32767 (ER32767) are initialized.
  • When the protect switch of the memory cassette is set to ON (error code: K6770)

Program example

In the program example shown below, the extension registers R0 to R2047 in the sector 0 are initialized. Note that the extension file registers ER0 to ER2047 are also initialized if a memory cassette is attached.

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 730)
Fig. 727 · Program example
  • Extension registers (R) [inside the built-in RAM]
Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 730)
Fig. 728 · Program example
Page 731 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 731 · click to enlarge
Page 731

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.4 FNC293 – LOGR / Logging R and ER 31

33.4 FNC293 – LOGR / Logging R and ER

FNC277-FNC279 Data Transfer 3

Outline

This instruction logs specified devices, and stores the logged data to extension registers (R) in the RAM and extension file registers (ER) in a memory cassette.

FNC280-FNC289 High-Speed Processing 2

1. Instruction format

P FNC 293

Mnemonic Operation Condition 16-bit Instruction

LOGR

⎯ ⎯ LOGRP Pulse (Single) Operation

FNC290-FNC299 Extension File Register Control

2. Set data

Operand Type Description Data Type

Head device number to be logged*1

m Number of devices to be logged [1 ≤ m ≤ 8000]

Head device number used in logging

FNC300-FNC305 FX 3U -CF-ADP

n Number of destination sectors of used for logging [1 ≤ n ≤ 16]

Number of logged data

*1. C200 to C255 cannot be set.

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

m 3 3 3

Explanation of function and operation

1. 16-bit operation (LOGR and LOGRP)

While the instruction is driven, “m” devices starting from are logged until “n” sectors of extension registers (R)

starting from and extension file registers (ER) in a memory cassette are filled.

The number of logged data is stored to . If a memory cassette is not used, data is not written to extension file registers (ER).

LOGRP m D1 n D2 ‚ S ‚

A

B

Show 19 more labels / short text on this page
Mnemonic Operation Condition · 32-bit Instruction · 11 steps LOGR · Continuous Operation · 16-bit binary · SFC•STL Programming · Oper- · and Type · Unit Index Con- stant · Real Number · Charac- ter String Pointer · Interrupt Function · n 3 3 · Special Device · Error Code · Command · input · Version Up Information · Execution Times
Page 732 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 732 · click to enlarge
Page 732

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.4 FNC293 – LOGR / Logging R and ER

Logging data format

Mitsubishi Electronics MELSEC FX3S — Logging data format diagram (page 732)
Fig. 729 · Logging data format

Writing position control area (Every time one word is used in the data writing area, bits are set to OFF (0) from ON (1) in turn from bit 0 of [ + (1926 × n) -1]. After bit 15 of [ + (1926 × n) -1] is set to OFF (0), bit 0 of the next device [ + (1926 × n)] is set to OFF (0) in the next logging.

The table below shows the head device number in each sector:

number Written device range Sector number

Mitsubishi Electronics MELSEC FX3S — Logging data format diagram (page 732)
Fig. 730 · Logging data format

Sector 0 R0 R0 to R2047, ER0 to ER2047 Sector 8 R16384 R16384 to R18431, ER16384 to ER18431

Sector 1 R2048 R2048 to R4095, ER2048 to ER4095 Sector 9 R18432 R18432 to R20479, ER18432 to ER20479

Sector 2 R4096 R4096 to R6143, ER4096 to ER6143 Sector 10 R20480 R20480 to R22527, ER20480 to ER22527

Sector 3 R6144 R6144 to R8191, ER6144 to ER8191 Sector 11 R22528 R22528 to R24575, ER22528 to ER24575

Sector 4 R8192 R8192 to R10239, ER8192 to ER10239 Sector 12 R24576 R24576 to R26623, ER24576 to ER26623

Sector 5 R10240 R10240 to R12287, ER10240 to ER12287 Sector 13 R26624 R26624 to R28671, ER26624 to ER28671

Sector 6 R12288 R12288 to R14335, ER12288 to ER14335 Sector 14 R28672 R28672 to R30719, ER28672 to ER30719

Sector 7 R14336 R14336 to R16383, ER14336 to ER16383 Sector 15 R30720 R30720 to R32767, ER30720 to ER32767

Cautions

1. LOGR instruction The LOGR instruction executes logging in each operation cycle in the continuous operation type. When logging should be executed only once by one input, use the pulse operation type.

Sector number · Head device

Page 733 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 733 · click to enlarge
Page 733

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.4 FNC293 – LOGR / Logging R and ER 31

2. Caution on using a memory cassette Flash memory is adopted in a memory cassette. Make sure to initialize the data storage area in sector units before starting logging. If the LOGR instruction is executed without initializing the data storage area, an operation error (error code: K6770) may be caused.

FNC277-FNC279 Data Transfer 3

Logging data storage area initialization command input *1 *2

INITR D 1 ‚

FNC280-FNC289 High-Speed Processing 2

*1 Specify the same device as in LOGR instruction. *2 Specify the same number as (n) in LOGR instruction. D1 ‚

3. Allowable number of writes to the memory Note the following cautions on access to extension file registers.

FNC290-FNC299 Extension File Register Control

  • Data can be written to the memory cassette (flash memory) up to 10,000 times. Every time the INITR (FNC292), RWER (FNC294) or INITER (FNC295) instruction is executed, it is counted as a write to the memory. Make sure not to exceed the allowable number of writes. When a continuous operation type instruction is used, data is written to the memory in every operation cycle of the PLC. To prevent this, make sure to use a pulse operation type instruction.
  • Execution of the LOADR (FNC290), SAVER (FNC291) or LOGR (FNC293) instruction is not counted as a write to the memory. However, it is necessary to initialize the writing target sector before executing the SAVER (FNC291) or LOGR (FNC293) instruction. Every time the INITR (FNC292) or INITER (FNC295) instruction is executed, it is counted as a write to the memory. Make sure not to exceed the allowable number of writes.

FNC300-FNC305 FX 3U -CF-ADP

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When any device number other than the head device number of a sector of extension file registers is set to (error code: K6706)
  • While data is written, the remaining area and the data quantity to be written are compared with each other. If the remaining storage area is insufficient, only a limited amount of data is written. (error code: K6706)
  • When the protect switch of the memory cassette is set to ON (error code: K6770)
  • When the collation result after data writing is "mismatch" due to omission of initialization or for another reason (error code: K6770) When this error occurs, the current values (data) of extension registers (R) may be lost. To avoid the data loss, back up the data of extension registers (R) in advance using the following procedure: 1) Set the PLC mode to STOP. 2) Create a new project in GX Works2. This step is not necessary if it is alright to overwrite the current project. 3) Read the contents of extension registers (R) to GX Works2. [1] Select "Online" → "Read from PLC..." to

display Online Data Operation dialog box. [2] Click "PLC Parameter/Network Parameter"

and "Device Data/File Register" to check mark each of them. [3] Click [Execute] button. [4] When reading is completed, save the project.

A

B

4. Change the current program inside the PLC to the program shown in “Cautions on using a memory cassette” in “Cautions” on the previous page.
Show 7 more labels / short text on this page
n FNC292 · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 734 of the Mitsubishi Electronics MELSEC FX3S user manual — Program example
Page 734 · click to enlarge
Page 734

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.4 FNC293 – LOGR / Logging R and ER

5. To the PLC, write the data which was temporarily withdrawn to GX Works2. [1] Select “Online” → “Write to PLC...” to display
Mitsubishi Electronics MELSEC FX3S — 33.4 FNC293 – LOGR / Logging R and ER diagram (page 734)
Fig. 731 · 33.4 FNC293 – LOGR / Logging R and ER

the Online Data Operation dialog box. [2] Click "PLC Parameter/Network Parameter"

and "MAIN" to check mark each of them. [3] Click [Execute] button to execute writing.

6. Change the PLC mode from STOP to RUN, execute the program, and store the data to the extension file registers inside the memory cassette.

Program example

In the program example shown below, D1 and D2 are logged to the area from R2048 to R6143 every time X001 turns ON.

Mitsubishi Electronics MELSEC FX3S — Program example diagram (page 734)
Fig. 732 · Program example

Because two words are used, low-order two bits are set to OFF (0).

Because two words are used, low-order two bits are set to OFF (0).

Page 735 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 735 · click to enlarge
Page 735

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.5 FNC294 – RWER / Rewrite to ER 31

33.5 FNC294 – RWER / Rewrite to ER

FNC277-FNC279 Data Transfer 3

Outline

This instruction writes the current values of an arbitrary number of extension registers (R) stored in the RAM in the PLC to extension file registers (ER) stored in a memory cassette (flash memory or EEPROM) or the EEPROM built into the PLC. Because RWER (FNC294) instruction is not supported in FX3UC PLC before Ver. 1.30, use the SAVER (FNC291) instruction instead.

FNC280-FNC289 High-Speed Processing 2

→ For the SAVER (FNC291) instruction, refer to Section 33.2.

1. Instruction format

P FNC 294

Mnemonic Operation Condition 16-bit Instruction

FNC290-FNC299 Extension File Register Control

RWER

⎯ ⎯ RWERP Pulse (Single) Operation

2. Set data

Operand Type Description Data Type

FNC300-FNC305 FX 3U -CF-ADP

Device number of extension register storing data

16-bit binary n Number of devices [FX3G/FX3GC: 1 ≤ n ≤ 24000, FX3U/FX3UC: 0 ≤ n ≤ 32767] to be written (transferred)

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

n 3 3 3

Explanation of function and operation

1. 16-bit operation (RWER)

1. In FX 3U /FX 3UC PLCs

The contents (current values) of “n” extension registers (R) starting from are written (transferred) to extension file registers with the same device numbers in a memory cassette (flash memory).

FNC294 RWERP n S ‚

Extension file registers (ER) inside memory cassette Extension registers (R) inside built-in RAM

E

E +1

E +2

A

*1. All points specified by the instruction are written (transferred).

  • When “n” is set to “0”, it is handled as “32768” when the instruction is executed.

B

Show 22 more labels / short text on this page
Mnemonic Operation Condition · 32-bit Instruction · 5 steps RWER · Continuous Operation · SFC•STL Programming · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · Interrupt Function · Special Device · Command · input · Error Code · *1 Write (transfer) · +1 · +2 · Version Up Information · +n-1 · E +n-1 · Execution Times
Page 736 of the Mitsubishi Electronics MELSEC FX3S user manual — 33.5 FNC294 – RWER / Rewrite to ER
Page 736 · click to enlarge
Page 736

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.5 FNC294 – RWER / Rewrite to ER

2. In FX 3G /FX 3GC PLCs a) When a memory cassette is connected (A memory cassette can be connected only to FX 3G PLC.)

The contents (current values) of “n” extension registers (R) starting from are written (transferred) to extension file registers having with same device numbers in a memory cassette (flash memory).

FNC290 RWERP S n

Extension file registers (ER) inside memory cassette Extension registers (R) inside built-in RAM

Mitsubishi Electronics MELSEC FX3S — 33.5 FNC294 – RWER / Rewrite to ER diagram (page 736)
Fig. 733 · 33.5 FNC294 – RWER / Rewrite to ER

*1. All points specified by the instruction are written (transferred). b) When a memory cassette is not connected

The contents (current values) of "n" extension registers (R) starting from are written (transferred) to extension file registers which are stored in the EEPROM built into the PLC and have the same device numbers.

FNC290 RWERP S n

Mitsubishi Electronics MELSEC FX3S — 33.5 FNC294 – RWER / Rewrite to ER diagram (page 736)
Fig. 734 · 33.5 FNC294 – RWER / Rewrite to ER

*2. All points specified by the instruction are written (transferred).

Show 4 more labels / short text on this page
Command · input · Command · input
Page 737 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 737 · click to enlarge
Page 737

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.5 FNC294 – RWER / Rewrite to ER 31

Cautions

FNC277-FNC279 Data Transfer 3

1. Cautions on writing data to a memory cassette (flash memory) for FX 3U /FX 3UC PLCs Memory cassettes use flash memory. Note the following contents when writing data to extension file registers in a memory cassette with the RWER (FNC294) instruction.
  • Though extension file registers to be written can be specified arbitrarily, writing is executed in sector units. It takes about 47 ms to write one sector. If the extension file registers to be written are located in two sectors, the instruction execution time will be about 94 ms. Make sure to change the set value of the watchdog timer D8000 before executing this instruction.

FNC280-FNC289 High-Speed Processing 2

PLS M100

M100 FNC 12

MOV D8000 D200

FNC290-FNC299 Extension File Register Control

ADD D8000 K47 *1 D8000

*1 Number of sectors to be written × 47 ms

WDT

FNC300-FNC305 FX 3U -CF-ADP

RWER R1000 K100

The contents of R1000 to R1099 in the sector 0 are written to ER1000 to ER1099.

MOV D200 D8000

WDT

The table below shows the head device number in each sector:

Sector number Device range Sector number Device range

Sector 0 ER0 to ER2047 Sector 8 ER16384 to ER18431

Sector 1 ER2048 to ER4095 Sector 9 ER18432 to ER20479

Sector 2 ER4096 to ER6143 Sector 10 ER20480 to ER22527

Sector 3 ER6144 to ER8191 Sector 11 ER22528 to ER24575

Sector 4 ER8192 to ER10239 Sector 12 ER24576 to ER26623

Sector 5 ER10240 to ER12287 Sector 13 ER26624 to ER28671

Sector 6 ER12288 to ER14335 Sector 14 ER28672 to ER30719

Sector 7 ER14336 to ER16383 Sector 15 ER30720 to ER32767

  • Do not turn OFF the power while this instruction is being executed. If the power is turned OFF, execution of this instruction may be aborted. If execution is aborted, the data may be lost. Make sure to back up the data before executing this instruction.

→ For the backup method, refer to the next page.

2. Cautions on writing data to a memory cassette (EEPROM) for FX 3G PLC Memory cassettes adopt the EEPROM. Note the following contents when writing data to extension file registers in a memory cassette using the RWER (FNC294) instruction.
  • Do not turn OFF the power while this instruction is being executed. If the power is turned OFF, execution of this instruction may be aborted. If execution is aborted, the data may be lost. Make sure to back up the data before executing this instruction.

→ For the backup method, refer to the next page.

A

B

Show 7 more labels / short text on this page
Writing command input · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 738 of the Mitsubishi Electronics MELSEC FX3S user manual — Data backup method
Page 738 · click to enlarge
Page 738

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.5 FNC294 – RWER / Rewrite to ER

3. Allowable number of writes to the memory Note the following cautions on access to extension file registers.
  • In FX 3U /FX 3UC PLCs Data can be written to the memory cassette (flash memory) up to 10,000 times. Every time the INITR (FNC292), RWER (FNC294) or INITER (FNC295) instruction is executed, it is counted as a write to the memory. Make sure not to exceed the allowable number of writes. When a continuous operation type instruction is used, data is written to the memory in every operation cycle of the PLC. To prevent this, make sure to use a pulse operation type instruction.

Execution of the LOADR (FNC290), SAVER (FNC291) or LOGR (FNC293) instruction is not counted as a write to the memory. However, it is necessary to initialize the writing target sector before executing the SAVER (FNC291) or LOGR (FNC293) instruction. Every time the INITR (FNC292) or INITER (FNC295) instruction is executed, it is counted as a write to the memory. Make sure not to exceed the allowable number of writes.

  • In FX 3G /FX 3GC PLCs Data can be written to the memory cassette (EEPROM) up to 10,000 times, and to the built-in memory (EEPROM) up to 20,000 times. Every time the RWER (FNC294) instruction is executed, it is counted as a write to the memory. Make sure not to exceed the allowable number of writes. When a continuous operation type instruction is used, data is written to the memory in every operation cycle of the PLC. To prevent this, make sure to use a pulse operation type instruction. Execution of the LOADR (FNC290)instruction is not counted as a write to the memory.

Data backup method

When the contents of extension file registers (ER) and extension registers (R) should not be lost, back up the current values (data) of extension file registers (ER) and extension registers (R) in advance using the following procedure:

1. Set the PLC mode to STOP.
2. Create a new project in GX Works2. This step is not necessary if it is alright to overwrite the current project.
3. Read the contents of extension file registers (ER) and extension registers (R) to GX Works2. [1] Select “Online” → “Read from PLC...” to display the Online Data Operation dialog box. [2] Click "PLC Parameter/Network Parameter" and "Device Data/File Register" to check mark each of them.

[3] Click the [Detail] button of the device memory to display the "Device Data Detail Setting" dialog box. [4] Enter the file name to be saved to "Device Data Name". [5] Check "Ext. register" and "Ext. file register"*1

Mitsubishi Electronics MELSEC FX3S — Data backup method diagram (page 738)
Fig. 735 · Data backup method

of "Device Data Name", and click the [OK] button. [6] Click [Execute] button to execute reading. [7] When reading is completed, save the project.

*1. The extension file register range cannot be set in GX Developer whose version is earlier than Ver. 8.18U or in GX Works2.

Page 739 of the Mitsubishi Electronics MELSEC FX3S user manual — HFFFF R2047
Page 739 · click to enlarge
Page 739

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.5 FNC294 – RWER / Rewrite to ER 31

Errors

FNC277-FNC279 Data Transfer 3

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When the last device number to be transferred exceeds “32767 *1 ” (error code: K6706) At this time, data is read (and transferred) until the last device number R32767 *1 .
  • When a memory cassette is not connected (error code: K6771) *2

FNC280-FNC289 High-Speed Processing 2

  • When the protect switch of the memory cassette is set to ON (error code: K6770)

*1. The last device number is 23,999 in FX3G/FX3GC PLCs. *2. An operation error is not caused in FX3G PLC because the contents of extension file registers stored in the EEPROM built into the PLC are read if a memory cassette is not connected.

Program example

In the program example shown below, the contents of extension registers R10 to R19 (sector 0) are transferred to extension file registers (ER) when X000 turns ON.

FNC290-FNC299 Extension File Register Control

Program

PLS M0

M0

MOV D8000 D200

FNC300-FNC305 FX 3U -CF-ADP

ADD D8000

K47 D8000

WDT

RWER R10 K10

MOV D200 D8000

WDT

END

Operation

Setting backup data Extension file registers

(ER)

R0 K100

ER0 K100

R1 K105

ER1 K105

R10 K200

ER10 K200

R11 K215

ER11 K215

R12 K400

ER12 K400

A

R19 K350

ER19 K350

R99 K1000

ER99 K1000

B

R100 HFFFF

ER100 HFFFF

HFFFF R2047

HFFFF ER2047

Show 16 more labels / short text on this page
SFC•STL Programming · Interrupt Function · Setting data · Special Device · Extension registers (R) · Device number Current · Device number Current · value · value · Error Code · Setting data (A) · Changed data Unused · Write (when X000 · Version Up Information · turns ON) · Execution Times
Page 740 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 740 · click to enlarge
Page 740

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.6 FNC295 – INITER / Initialize ER

33.6 FNC295 – INITER / Initialize ER

Outline

This instruction initializes extension file registers (ER) to “HFFFF” () in a memory cassette (flash memory) before executing the SAVER (FNC291) instruction. Because the INITER (FNC295) instruction is not supported in FX3UC PLC earlier than Ver. 1.30, use INITR (FNC292) instruction instead.

→ For SAVER (FNC291) instruction, refer to Section 33.2.

→ For INITR (FNC292) instruction, refer to Section 33.3.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 740)
Fig. 736 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 740)
Fig. 737 · 2. Set data

Head device number of extension register sector with the same device number as the extension file register to be initialized 16-bit binary n Number of sectors of extension file registers to be initialized

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 740)
Fig. 738 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

Explanation of function and operation

1. 16-bit operation (INITER and INITERP) “n” sectors of extension file registers (ER) in a memory cassette (flash memory) with the same device number as

are initialized to “HFFFF” (). Initialization is executed in sectors.

FNC295 INITERP n S ‚

The table below shows the head device number in each sector:

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 740)
Fig. 739 · Explanation of function and operation
Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 740)
Fig. 740 · Explanation of function and operation

Sector 0 R0 ER0 to ER2047 Sector 8 R16384 ER16384 to ER18431

Sector 1 R2048 ER2048 to ER4095 Sector 9 R18432 ER18432 to ER20479

Sector 2 R4096 ER4096 to ER6143 Sector 10 R20480 ER20480 to ER22527

Sector 3 R6144 ER6144 to ER8191 Sector 11 R22528 ER22528 to ER24575

Sector 4 R8192 ER8192 to ER10239 Sector 12 R24576 ER24576 to ER26623

Sector 5 R10240 ER10240 to ER12287 Sector 13 R26624 ER26624 to ER28671

Sector 6 R12288 ER12288 to ER14335 Sector 14 R28672 ER28672 to ER30719

Sector 7 R14336 ER14336 to ER16383 Sector 15 R30720 ER30720 to ER32767

Command · input

Page 741 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 741 · click to enlarge
Page 741

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.6 FNC295 – INITER / Initialize ER 31

Operation

FNC277-FNC279 Data Transfer 3

  • Extension file registers (ER) [inside the memory cassette]

Before execution After execution

H1234 HFFFF

+1 H5678 HFFFF

FNC280-FNC289 High-Speed Processing 2

+2 H90AB HFFFF

+(2048×n)-1 HCDEF HFFFF

Caution

FNC290-FNC299 Extension File Register Control

About 25 ms is required to initialize one sector. When initializing two or more sectors, take either measure shown below.

  • Set a large value to the watchdog timer D8000 using the following program

M8002 FNC 12

MOV K {{{ D8000

FNC300-FNC305 FX 3U -CF-ADP

Guideline of the watchdog timer set value

A value acquired by the following procedure can be regarded as the guideline of the watchdog timer set value. If an acquired value is 200 ms or less, however, it is not necessary to change the watchdog timer set value.

1. Write a program to be executed from GX Works2 to the PLC. [Online] → [Write to PLC...]
2. Set the current value of D8000 (unit: ms) to "1000" using the [Modify Value] function in GX Works2. [Debug] → [Modify Value]
3. Set the PLC mode to RUN, and execute the program. (Execute this instruction also.)
4. Monitor the maximum scan time D8012 (unit: 0.1 ms) using the device/buffer memory batch monitor function in GX Works2.
5. Set the watchdog timer to the maximum scan time (D8012) or more. D8012 stores the maximum scan time in increments of 0.1 ms. Rough guide to the watchdog timer set value D8000 (unit: ms) is the "value stored in D8012 divided by 10" added by 50 to 100.
  • Setting the WDT (FNC 07) instruction just before and after the INITER instruction as shown below:

WDT The watchdog timer is reset.

The watchdog timer is reset.

WDT

If the processing time of the INITER command exceeds 200 ms, set the watchdog timer value D8000 (unit: ms) to the processing time or more.

2. Allowable number of writes to the memory Note the following cautions on access to extension file registers.

A

  • Data can be written to the memory cassette (flash memory) up to 10,000 times. Every time the INITR (FNC292), RWER (FNC294) or INITER (FNC295) instruction is executed, it is counted as a write to the memory. Make sure not to exceed the allowable number of writes. When a continuous operation type instruction is used, data is written to the memory in every operation cycle of the PLC. To prevent this, make sure to use a pulse operation type instruction.
  • Execution of the LOADR (FNC290), SAVER (FNC291) or LOGR (FNC293) instruction is not counted as a write to the memory. However, it is necessary to initialize the writing target sector before executing the SAVER (FNC291) or LOGR (FNC293) instruction. Every time the INITR (FNC292) or INITER (FNC295) instruction is executed, it is counted as a write to the memory. Make sure not to exceed the allowable number of writes.

B

Show 12 more labels / short text on this page
Current value · Device number · Initial pulse · SFC•STL Programming · Interrupt Function · Command · input · Special Device · INITER n · Error Code · Version Up Information · Execution Times
Page 742 of the Mitsubishi Electronics MELSEC FX3S user manual — ER0 H1234 HFFFF
Page 742 · click to enlarge
Page 742

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

33 Extension File Register Control – FNC290 to FNC299

33.6 FNC295 – INITER / Initialize ER

Errors

An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in D8067.

  • When any device number other than the head device number of a sector of extension file registers (ER) is set to
(error codeK6706)
  • When a device number to be initialized exceeds “32767” (error code: K6706) In this case, devices up to R32767 (ER32767) are initialized.
  • When the protect switch of the memory cassette is set to ON (error code: K6770)
  • When a memory cassette is not connected (error code: K6771)

Program example

In the program example shown below, the extension file registers ER0 to ER2047 in sector 0 are initialized.

WDT

R0 K1

INITER

WDT

END

  • Extension file registers (ER) [inside the memory cassette]

Before execution After execution

ER0 H1234 HFFFF

ER1 H5678 HFFFF

ER2 H90AB HFFFF

ER2047 HCDEF HFFFF

Current value · Device number

Page 743 of the Mitsubishi Electronics MELSEC FX3S user manual — 34. FX 3U -CF-ADP Applied Instructions – FNC300 to FNC305
Page 743 · click to enlarge
Page 743

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305

Mitsubishi Electronics MELSEC FX3S — 34. FX3U-CF-ADP Applied Instructions – FNC300 to FNC305 diagram (page 743)
Fig. 741 · 34. FX3U-CF-ADP Applied Instructions – FNC300 to FNC…

34. FX 3U -CF-ADP Applied Instructions – FNC300 to FNC305

301 FLDEL File delete / CF card format Section 34.2

305 FLSTRD FX3U-CF-ADP status read Section 34.6

Page 744 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 744 · click to enlarge
Page 744

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305

34.1 FNC300 – FLCRT / File create•check

34.1 FNC300 – FLCRT / File create • check

Outline

The FLCRT instruction creates a file inside the CompactFlashTM card mounted in the FX3U-CF-ADP. When executed after creation of a new file, the FLCRT instruction checks the association with the file ID, and evaluates it.

→ For explanation of the instruction, refer to the CF-ADP Manual.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 744)
Fig. 742 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 744)
Fig. 743 · 2. Set data

File creation parameter (Refer to Subsection 34.1.1) 16-bit binary

n Used channel number [contents of setting : K1 = ch1, K2 = ch2] 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 744)
Fig. 744 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

SExcept special data register (D)

Explanation of function and operation

1. 16-bit operation (FLCRT)

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 744)
Fig. 745 · Explanation of function and operation
  • When the file ID is "K0"

When is "K0", the FLCRT instruction creates a FIFO file. When the PLC creates two or more files for FIFO file, and executes FIFO (first in, first out) in units of files. The PLC keeps the latest file, and deletes older files so that the total capacity of FIFO files and other files does not exceed the specified capacity.

  • When the file ID is "K1" to "K63"

When is "K1" to "K63", the FLCRT instruction creates a file having the specified file name.

Sequence programs use the file ID for specifying a file. Accordingly, each file name saved in the CompactFlashTM card is associated with the file ID, and controlled by the file ID table. If a file having the specified file name already exists and is registered in the file ID table, the PLC finishes the FLCRT instruction without executing any processing. If a file having the specified name already exists but is not registered in the file ID table, the PLC only registers the existing file to the file ID table.

Page 745 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 745 · click to enlarge
Page 745

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305

34.1 FNC300 – FLCRT / File create • check 31

34.1.1 Detailed explanation of setting data

FNC277-FNC279 Data Transfer 3

Details on the setting data in the FLCRT instruction are as shown below.

Setting items Description Data Type

File ID This ID number is associated with the file name. The FLCRT instruction creates a file, and associates the file name with the file ID at the same time. The user should use the file ID for specifying a file after that. Allowable setting range : K0 to K63 ("K0" indicates "FIFO file".)

FNC280-FNC289 High-Speed Processing 2

When is "K0 (FIFO file)" Not used (ignored) Use an unused device. (D or R)

When is "K1" to "K63" Specify the file name in up to 8 characters until "null" or "null + null". Half-width alphanumeric characters and half-width symbols permitted in the MS-DOS are available. Half-width symbols : !, #, $, %, &, ', (, ), +, -, @, ^, _, ', ~ The extension is fixed to "CSV"

FNC290-FNC299 Extension File Register Control

Time stamp setting Set whether or not the time stamp is added to the file. Specify the format when adding the time stamp. K0 : None (NULL) K1 : yyyy/mm/dd hh:mm:ss K2 : yy/mm/dd hh:mm:ss K3 : dd/mm/yyyy hh:mm:ss K4 : dd/mm/yy hh:mm:ss K5 : mm/dd/yyyy hh:mm:ss K6 : mm/dd/yy hh:mm:ss K7 : hh:mm:ss

FNC300-FNC305 FX 3U -CF-ADP

Data type Set the data type to be saved. K0 : No data type specification (mixed type) K1 : Bit type K2 : Decimal type (16-bit) K3 : Decimal type (32-bit) K4 : Hexadecimal type (16-bit) K5 : Hexadecimal type (32-bit) K6 : Real numbers (Floating point data) Exponent expression type K7 : Character string

Maximum number of lines Set the maximum number of lines. Allowable setting range : K1 to K32767*1

When is "K0" Set the CompactFlashTM card use ratio. Specify the ratio (%) out of the whole CompactFlashTM card capacity to be used. Allowable setting range : 10 to 90 (%)

When is "K1" to "K63" File processing to be executed when the specified maximum number of lines is reached. Set the file processing method to be executed when the number of lines reaches the specified maximum value. K0 : Stops execution. (The line position remains the specified maximum line position.) K1 : Returns to the head (ring buffer file).

Channel number used by the CF-ADP K1 : ch1 K2 : ch2

*1. Adjust the maximum number of lines to specify the file size available in the used application software used.

A

Cautions

  • When the file ID is "K0"
1. The CF-ADP can create up to 1000 files (within the CompactFlash TM card capacity). 2) The file name is set to "FILE0000.CSV" to "FILE0999.CSV". • When the file ID is "K1" to "K63"
1. The user can create up to 63 files (within the CompactFlash TM card capacity). 2) The FLCRT instruction is completed abnormally if different file names are specified for the same file ID or if the same file name is specified for different file IDs. • It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"ADPRW (FNC276)"/"IVCK (FNC270) to IVMC (FNC275)" instruction and an "FLCRT (FNC300) to FLSTRD (FNC305)" instruction for the same port.

B

Show 20 more labels / short text on this page
16-bit binary · File name · Character string · 16-bit binary · SFC•STL Programming · File creation parameter · +1 · 16-bit binary · Interrupt Function · 16-bit binary · +2 · 16-bit binary · Special Device · +3 · 16-bit binary · Error Code · n · 16-bit binary · Version Up Information · Execution Times
Page 746 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 746 · click to enlarge
Page 746

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305

34.2 FNC301 – FLDEL / File delete•CF card format

34.2 FNC301 – FLDEL / File delete • CF card format

Outline

The FLDEL instruction deletes files stored in the CompactFlashTM card, or formats the CompactFlashTM card.

→ For explanation of the instruction, refer to the CF-ADP Manual.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 746)
Fig. 746 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 746)
Fig. 747 · 2. Set data

File delete method (Refer to Subsection 34.2.1) 16-bit binary

n Used channel number [contents of setting : K1 = ch1, K2 = ch2] 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 746)
Fig. 748 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

SExcept special data register (D)

Explanation of function and operation

1. 16-bit operation (FLDEL)

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 746)
Fig. 749 · Explanation of function and operation

S1 ‚ S2 ‚ D ‚ S1 S2

The FLDEL instruction deletes files stored in the CompactFlashTM card, or formats the CompactFlashTM card in the following method.

  • Specify file deletion or file formatting using .

- When is "K-1 (H0FFFF)", the FLDEL instruction deletes all files whose ID is 0 to 63.

- When is "K0" to "K63", the FLDEL instruction deletes the file associated with the specified file ID.

- When is "K512 (H200)", the FLDEL instruction formats the CompactFlashTM card.

  • Specify the file deletion method or format type using .

- When is "K-1 (H0FFFF)" or "K0" to "K63", specify the deletion method K0 : The FLDEL instruction deletes the specified file. K1 : The FLDEL instruction deletes the association between the file name and the file ID (but does not

delete the file itself).

However, when the file ID specified in is "0", the FLDEL instruction deletes the file regardless of the

setting of .

- When is "K512 (H200)", specify the format type.

K256(H100) : The FLDEL instruction formats the CompactFlashTM card in FAT16 format.

For details, refer to Subsection 34.2.1.

Page 747 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 747 · click to enlarge
Page 747

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305

34.2 FNC301 – FLDEL / File delete • CF card format 31

34.2.1 Detailed explanation of setting data

FNC277-FNC279 Data Transfer 3

Details on the setting data in the FLDEL instruction are as shown below.

Setting items Description Data Type

File ID K-1(H0FFFF) : The FLDEL instruction deletes all files. K0 to K63 : The FLDEL instruction deletes a file associated with the specified file ID.

FNC280-FNC289 High-Speed Processing 2

K512(H200) : The FLDEL instruction formats the CompactFlashTM card.

When is "K-1 (H0FFFF)" or "K0" to "K63" Specify the deletion method. K0 : The FLDEL instruction deletes the specified file. K1 : The FLDEL instruction deletes the association between the file name and the file ID

(but does not delete the file itself).

However, when the file ID specified in is "0", the FLDEL instruction deletes the file itself

FNC290-FNC299 Extension File Register Control

regardless of the setting of

When is "K512 (H200)" Specify the format type.

K256(H100) : The FLDEL instruction formats the CompactFlashTM card in the FAT16 format.

Channel number used by the CF-ADP K1 : ch1 K2 : ch2

FNC300-FNC305 FX 3U -CF-ADP

Cautions

  • When the file ID "K0 (FIFO file)" or "K-1 (all files)" is specified, it may take approximately 1 minute to delete the files depending on the number of stored files.
  • It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"ADPRW (FNC276)"/"IVCK (FNC270) to IVMC (FNC275)" instruction and an "FLCRT (FNC300) to FLSTRD (FNC305)" instruction for the same port.

A

B

Show 10 more labels / short text on this page
16-bit binary · 16-bit binary · n · 16-bit binary · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 748 of the Mitsubishi Electronics MELSEC FX3S user manual — Explanation of function and operation
Page 748 · click to enlarge
Page 748

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305

34.3 FNC302 – FLWR / Data write

34.3 FNC302 – FLWR / Data write

Outline

The FLWR instruction writes data to the CompactFlashTM card or to the buffer inside the FX3U-CF-ADP.

→ For explanation of the instruction, refer to the CF-ADP Manual.

1. Instruction format

Mitsubishi Electronics MELSEC FX3S — 1. Instruction format diagram (page 748)
Fig. 750 · 1. Instruction format

2. Set data

Mitsubishi Electronics MELSEC FX3S — 2. Set data diagram (page 748)
Fig. 751 · 2. Set data

Head of devices which store data to be written (Refer to Subsection 34.3.1) -

Data write parameter (Refer to Subsection 34.3.1) 16-bit binary

Position after data writing (Refer to Subsection 34.3.1) 16-bit binary

n Used channel number [contents of setting : K1 = ch1, K2 = ch2] 16-bit binary

3. Applicable devices

Mitsubishi Electronics MELSEC FX3S — 3. Applicable devices diagram (page 748)
Fig. 752 · 3. Applicable devices

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

SExcept special data register (D)

Explanation of function and operation

1. 16-bit operation (FLWR)

Mitsubishi Electronics MELSEC FX3S — Explanation of function and operation diagram (page 748)
Fig. 753 · Explanation of function and operation

Head of devices which store data to be written

Page 749 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 749 · click to enlarge
Page 749

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305

34.3 FNC302 – FLWR / Data write 31

The FLWR instruction writes data specified by the device to a file stored in the CompactFlashTM card specified by the file ID or to the buffer inside the CF-ADP. The FLWR instruction can overwrite data in the line position specified

FNC277-FNC279 Data Transfer 3

by the device +1, and can write additional data (K-1). When the writing destination is the buffer inside the CF- ADP, the FLWR instruction can only execute additional writing. When writing is completed, the line position and column position after writing are as follows.

  • When data in 1 line is written additionally - Line position after writing : Written line position + K1 - Column position after writing : K1

FNC280-FNC289 High-Speed Processing 2

  • When a line having existing data is overwritten - Line position after writing : Written line position if data is not written to the final column position of specified the line position Line position next to the written line position if data is written to the final column position of the line - Column position after writing: Column position next to the final written data point K1 if data is written to the final data point in the line "K1" if data is written to the final data point in the line

FNC290-FNC299 Extension File Register Control

Both additional writing and overwriting are executed to the maximum number of lines specified during file creation. If data is written up to the final column position, the line position after writing varies depending on the file type and setting.

  • When the processing is stopped by the maximum line position in a normal file Line position after writing = Maximum line position + K1 K-32768 when the maximum line position is "K32767"

FNC300-FNC305 FX 3U -CF-ADP

  • In the case of a normal file in which processing returns to the head of the file from the end of the file (ring buffer file) Line position after writing = K1

In either case, the column position after writing is "K1".

A

B

Show 6 more labels / short text on this page
SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 750 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 750 · click to enlarge
Page 750

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305

34.3 FNC302 – FLWR / Data write

34.3.1 Detailed explanation of setting data

Details on the setting data in the FLWR instruction are as shown below.

Setting items Description Data Type

File IDK0 to K63 16-bit binary

Head of devices which store data to be written.

Specify the head of devices which store the data to be written to the CompactFlashTM

card.

Specify the data writing type K0 : Mixed type K1 : Bit type K2 : Decimal type (16-bit) K3 : Decimal type (32-bit) K4 : Hexadecimal type (16-bit) K5 : Hexadecimal type (32-bit) K6 : Real numbers (Floating point data) Exponent expression type (32-bit) K7 : Character string (512 half-width/full-width characters maximum) K8 : Data name : Character string consisting of up to 32 half-width/full-width characters. Index, DATE TIME are added automatically.

Specify the line position of the writing destination, or specify additional writing. Line position of the writing destination : K1 to specified maximum number of lines Additional writing : K-1

Specify the data column position in the writing destination. Column position : K1 to K254 Additional writing : K-1

+3 Number of written data points : K1 to K254 16-bit binary

K0CompactFlash TM card K1 : Buffer inside the CF-ADP
Line position after writingK1 to specified maximum number of lines 16-bit binary
+1 Column position after writingK1 to K254 16-bit binary

Channel number used by the CF-ADP K1 : ch1 K2 : ch2

Cautions

  • The FLWR instruction is completed abnormally if a CompactFlash TM card is not mounted.
  • The user should pay close attention to the number of times data is written when the writing destination is set to the CompactFlash TM card because data is written every time the FLWR instruction is executed. For example, if data is written to the CompactFlash TM card every one minute, data is written 100,000 times in approximately 2 months.
  • Even if the writing destination is set to the buffer inside the CF-ADP, data is written to the CompactFlash TM card in the case of overwriting.
  • The FLWR instruction writes data to the CompactFlash TM card after the internal buffer inside the CF-ADP becomes full when the writing destination is set to the buffer. Data stored in the internal buffer inside the CF-ADP is erased when a (instantaneous or long) power interruption occurs.
  • When the data type is a data name (K8), the user can specify only the head line position before writing other data. Index and DATE TIME are added automatically.
  • The FLWR instruction may require several scans to acquire data. Take proper measures such as saving acquired data in another device if data consistency is required.
  • It is necessary to set the device number in multiples of 16 when a bit device is specified in and the data type is set to anything other than bit type. When a word device is specified in and the data type is set to bit, the FLWR instruction acquires data to be written from the least significant bit of the specified device.
  • When is "K7" or "K8", 00H, which indicates the end of the string, must be added to the end of the character string.
  • It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"ADPRW (FNC276)"/"IVCK (FNC270) to IVMC (FNC275)" instruction and an "FLCRT (FNC300) to FLSTRD (FNC305)" instruction for the same port.
Show 11 more labels / short text on this page
16-bit binary · Data write parameter · 16-bit binary · +1 · +2 · 16-bit binary · Writing destination · +4 · 16-bit binary · n · 16-bit binary
Page 751 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 751 · click to enlarge
Page 751

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305

34.4 FNC303 – FLRD / Data read 31

34.4 FNC303 – FLRD / Data read

FNC277-FNC279 Data Transfer 3

Outline

The FLRD instruction reads data from the CompactFlashTM card.

→ For explanation of the instruction, refer to the CF-ADP Manual.

FNC280-FNC289 High-Speed Processing 2

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

FLRD

FNC290-FNC299 Extension File Register Control

2. Set data

Operand Type Description Data Type

File ID (Refer to Subsection 34.4.1) 16-bit binary

FNC300-FNC305 FX 3U -CF-ADP

Data read parameter (Refer to Subsection 34.4.1) 16-bit binary

Device which stores the read data (Refer to Subsection 34.4.1) -

Number of data points existing in the specified line (Refer to Subsection 34.4.1) 16-bit binary

n Used channel number [contents of setting : K1 = ch1, K2 = ch2] 16-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

3

SExcept special data register (D)

Explanation of function and operation

1. 16-bit operation (FLRD)

D 2 D 1 S 1 S 2

Used channel number Number of data points existing in the specified line Device which stores the read data

A

The FLRD instruction reads corresponding number of data from the position determined by the line position and

column position in the file specified by the file ID, and stores the read data to a device specified in .

B

Show 21 more labels / short text on this page
Mnemonic Operation Condition · 32-bit Instruction · 11 steps FLRD · Continuous Operation · SFC•STL Programming · Oper- · and Type · Unit Index Con- stant · Real Number · Charac- ter String Pointer · Interrupt Function · n 3 3 · Special Device · Command · input FNC303 · FLRD n · Error Code · Data read parameter · Version Up Information · File ID · Execution Times
Page 752 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 752 · click to enlarge
Page 752

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305

34.4 FNC303 – FLRD / Data read

34.4.1 Detailed explanation of setting data

Details on the setting data in the FLRD instruction are as shown below.

Setting items Description Data Type

File IDK0 to K63 16-bit binary

Specify the data reading type K0 : Mixed type K1 : Bit type K2 : Decimal type (16-bit) K3 : Decimal type (32-bit) K4 : Hexadecimal type (16-bit) K5 : Hexadecimal type (32-bit) K6 : Real numbers (Floating point data) Exponent expression type (32-bit) K7 : Character string (512 half-width/full-width characters maximum)

Specify the line position from which data is read. Line position : K1 to specified maximum number of lines 16-bit binary

Specify the column position from which data is read. Column position : K1 to K254 16-bit binary

+3 Read pointsK1 to K254 16-bit binary

Device which stores the read data

Specify the head of devices which store the data read from the CompactFlashTM card. 16-bit binary

Number of data points existing in the specified line K1 to K254 K0 : No data

Channel number used by the CF-ADP K1 : ch1 K2 : ch2

Cautions

  • The FLRD instruction is completed abnormally if a CompactFlash TM card is not mounted.
  • The FLRD instruction may require several scans to acquire data. Use the acquired data only after confirming completion of the FLRD instruction if data consistency is required.
  • It is necessary to set the device number in a multiple of 16 when a bit device is specified in and the read data

type is anything other than bit. When a word device is specified in and the read data type is bit, the FLRD instruction stores data read from the least significant bit of the specified word device.

  • When the data type is anything other than character string and the number of devices which store the read data is insufficient, the FLRD instruction does not read data from the CF-ADP. An error occurs. When the data type is a character string, the character string length is unknown. The PLC stores as much read data as possible. When reading is not completed even after the final device is reached, an error occurs.
  • It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"ADPRW (FNC276)"/"IVCK (FNC270) to IVMC (FNC275)" instruction and an "FLCRT (FNC300) to FLSTRD (FNC305)" instruction for the same port.
Show 7 more labels / short text on this page
Data read parameter · 16-bit binary · +1 · +2 · 16-bit binary · n · 16-bit binary
Page 753 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 753 · click to enlarge
Page 753

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305

34.5 FNC304 – FLCMD / FX3U-CF-ADP command 31

34.5 FNC304 – FLCMD / FX 3U -CF-ADP command

FNC277-FNC279 Data Transfer 3

Outline

The FLCMD instruction gives instruction for operation to the FX3U-CF-ADP.

→ For explanation of the instruction, refer to the CF-ADP Manual.

FNC280-FNC289 High-Speed Processing 2

1. Instruction format

Mnemonic Operation Condition 16-bit Instruction

FLCMD

FNC290-FNC299 Extension File Register Control

2. Set data

Operand Type Description Data Type

Instruction for operation (Refer to Subsection 34.5.1) 16-bit binary

n Used channel number [contents of setting : K1 = ch1, K2 = ch2] 16-bit binary

FNC300-FNC305 FX 3U -CF-ADP

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

SExcept special data register (D)

Explanation of function and operation

1. 16-bit operation (FLCMD)

The FLCMD instruction gives instruction for operation to the CF-ADP. The contents of instruction are as follows.

  • When is "K-1", the FLCMD instruction forcibly writes all buffered data (stored in the buffer inside the CF-ADP) to the CompactFlash TM card.
  • When is "K0" to "K63", the FLCMD instruction forcibly writes the buffered data of the specified file ID (stored

in the buffer inside the CF-ADP) to the CompactFlashTM card.

  • When is "K256 (H100)", the FLCMD instruction sets the CompactFlash TM card to the mounted status if it is in the unmounted status.

A

  • When is "K512 (H200)", the FLCMD instruction sets the CompactFlash TM card to the unmounted status if it is in the mounted status.
  • When is "K1280 (H500)", the FLCMD instruction clears error codes stored in the CF-ADP.

For details, refer to Subsection 34.5.1.

B

Show 21 more labels / short text on this page
Mnemonic Operation Condition · 32-bit Instruction · 5 steps FLCMD · Continuous Operation · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · SFC•STL Programming · n 3 3 · Interrupt Function · Command · input FNC304 · FLCMD n · Used channel number · Special Device · Instruction for operation · Error Code · Version Up Information · Execution Times
Page 754 of the Mitsubishi Electronics MELSEC FX3S user manual — Cautions
Page 754 · click to enlarge
Page 754

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305

34.5 FNC304 – FLCMD / FX3U-CF-ADP command

34.5.1 Detailed explanation of setting data

Details on the setting data in the FLCMD instruction are as shown below.

Setting items Description Data Type

Contents of instruction for operation

K0 to K63 : Forcibly writes the buffered data of the specified file ID to the CompactFlashTM card.

K-1 : Forcibly writes all buffered data to the CompactFlashTM card.

K256(H100) : Sets the CompactFlashTM card to the mounted status*1.

K512(H200) : Sets the CompactFlashTM card to the unmounted status*2. K1280(H500) : Clears error codes stored in the CF-ADP.

Channel number used by the CF-ADP K1 : ch1 K2 : ch2

*1. The CompactFlashTM card is available in the "mounted" status.

*2. The CompactFlashTM card is unavailable in the "unmounted" status.

Cautions

It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"ADPRW (FNC276)"/"IVCK (FNC270) to IVMC (FNC275)" instruction and an "FLCRT (FNC300) to FLSTRD (FNC305)" instruction for the same port.

16-bit binary · n · 16-bit binary

Page 755 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 755 · click to enlarge
Page 755

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305

34.6 FNC305 – FLSTRD / FX3U-CF-ADP status read 31

34.6 FNC305 – FLSTRD / FX 3U -CF-ADP status read

FNC277-FNC279 Data Transfer 3

Outline

The FLSTRD instruction reads the status (including the error information and file information) of the FX3U-CF-ADP.

FNC280-FNC289 High-Speed Processing 2

1. Instruction format

FNC 305 FLSTRD

Mnemonic Operation Condition 16-bit Instruction

FNC290-FNC299 Extension File Register Control

2. Set data

Operand Type Description Data Type

Contents of status to be read (Refer to Subsection 34.6.1) 16-bit binary

Head device to which the read status is written (Refer to Subsection 34.6.1) 16-bit binary

FNC300-FNC305 FX 3U -CF-ADP

n Used channel number [contents of setting : K1 = ch1, K2 = ch2] 16-bit binary

3. Applicable devices

Bit Devices Word Devices Others

System User Digit Specification System User Special

X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z Modify K H E " " P

SExcept special data register (D)

Explanation of function and operation

1. 16-bit operation (FLSTRD)

input FNC305 FLSTRD n

S D

Head device to which the read status is written

Contents of status to be read

The FLSTRD instruction reads the status information of the CF-ADP. The following contents can be read.

The number of data stored in varies depending on the contents of the read status.

  • When is "K0" to "K63" the FLSTRD instruction reads the final line position and final column position of each file.
  • When is "K256 (H100)" the FLSTRD instruction reads file IDs stored in the CompactFlash TM card.

A

  • When is "K512 (H200)" the FLSTRD instruction reads the data capacity.
  • When is "K768 (H300)" the FLSTRD instruction reads the version information of the CF-ADP.
  • When is "K1024 (H400)" the FLSTRD instruction reads the error information (error flag) for errors having occurred in the CF-ADP.
  • When is "K1280 (H500)" the FLSTRD instruction reads error codes and error code details. Up to 5 of the latest error codes and error code details can be stored.

B

For details, refer to Subsection 34.6.1.

Show 18 more labels / short text on this page
Mnemonic Operation Condition · 32-bit Instruction · 7 steps FLSTRD · Continuous Operation · Oper- · Unit Index Con- stant · Real Number · Charac- ter String Pointer · and Type · SFC•STL Programming · n 3 3 · Interrupt Function · Command · Special Device · Used channel number · Error Code · Version Up Information · Execution Times
Page 756 of the Mitsubishi Electronics MELSEC FX3S user manual — 34.6.1 Detailed explanation of setting data
Page 756 · click to enlarge
Page 756

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305

34.6 FNC305 – FLSTRD / FX3U-CF-ADP status read

34.6.1 Detailed explanation of setting data

Details on the setting data in the FLSTRD instruction are as shown below.

Mitsubishi Electronics MELSEC FX3S — 34.6.1 Detailed explanation of setting data diagram (page 756)
Fig. 754 · 34.6.1 Detailed explanation of setting data

Contents of status to be read K0 to K63 : Final line position of each file

K256(H100)File IDs stored in the CompactFlash TM card

K512(H200) : Capacity of the CompactFlashTM card K768(H300) : Version of the CF-ADP K1024(H400) : Error information (error flag) K1280(H500) : Error codes

Head device to which the read status is written

The number of data points stored in varies depending on the contents of the read status.

Channel number used by the CF-ADP K1 : ch1 K2 : ch2

  • When is "K0" to "K63" The FLSTRD instruction reads the final line position and final column position of each file.
Mitsubishi Electronics MELSEC FX3S — 34.6.1 Detailed explanation of setting data diagram (page 756)
Fig. 755 · 34.6.1 Detailed explanation of setting data

Final line position K1 to the specified maximum line position

The FLSTRD instruction reads file IDs stored in the CompactFlashTM card. For a file ID corresponding to the read data, refer to the file ID correspondence table shown below. When a file exists, a bit corresponding to the file ID turns ON.

Mitsubishi Electronics MELSEC FX3S — 34.6.1 Detailed explanation of setting data diagram (page 756)
Fig. 756 · 34.6.1 Detailed explanation of setting data

File ID correspondence table

Mitsubishi Electronics MELSEC FX3S — 34.6.1 Detailed explanation of setting data diagram (page 756)
Fig. 757 · 34.6.1 Detailed explanation of setting data

Setting items b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

+1 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16

+2 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32

+3 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48

The FLSTRD instruction reads the data capacity, used space and free space of the CompactFlashTM card to the following devices respectively.

Mitsubishi Electronics MELSEC FX3S — 34.6.1 Detailed explanation of setting data diagram (page 756)
Fig. 758 · 34.6.1 Detailed explanation of setting data

+1, Data capacity of the CompactFlashTM card (kB) Units, If the data capacity is less than 1 kB, "1" is stored.

+3, +2 Used space of the CompactFlashTM card (kB) Units, If the data size is less than 1 kB, "1" is stored.

+5, +4 Free space of the CompactFlashTM card (kB) Units, If the data size is less than 1 kB, "1" is stored.

Page 757 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 757 · click to enlarge
Page 757

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

34 FX3U-CF-ADP Applied Instructions – FNC300 to FNC305

34.6 FNC305 – FLSTRD / FX3U-CF-ADP status read 31

  • When is "K768 (H300)" The FLSTRD instruction reads the version information of the CF-ADP.

FNC277-FNC279 Data Transfer 3

Stores the version of CF-ADP. (Example) K100 = Ver. 1.00

  • When is "K1024 (H400)" The FLSTRD instruction reads the error information (error flag).

FNC280-FNC289 High-Speed Processing 2

b0 : The CompactFlashTM card is not mounted.

b1 : The CompactFlashTM card is full. b2 : An error has occurred in the CF-ADP. b3 : CF-ADP H/W error

FNC290-FNC299 Extension File Register Control

b4CompactFlash TM card error b5 to b15 : Not used
  • When is "K1280 (H500)" The FLSTRD instruction reads the error code and error code details for errors having occurred in the CF-ADP. Up to 5 of the latest error codes and error code details can be stored.

FNC300-FNC305 FX 3U -CF-ADP

+1 Error code details 1

+2 Error code 2

+3 Error code details 2

+4 Error code 3

+5 Error code details 3

+6 Error code 4

+7 Error code details 4

+8 Error code 5

+9 Error code details 5

Cautions

It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"ADPRW (FNC276)"/"IVCK (FNC270) to IVMC (FNC275)" instruction and an "FLCRT (FNC300) to FLSTRD (FNC305)" instruction for the same port.

A

B

Show 11 more labels / short text on this page
Setting items Description · Setting items Description · Error detection signal · Setting items Description · Error code 1 · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 758 of the Mitsubishi Electronics MELSEC FX3S user manual — Operation of state relay State S and driven instruction
Page 758 · click to enlarge
Page 758

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program

35. SFC Program and Step Ladder

This chapter explains the programming procedures and sequence operations for the “SFC” and “step ladder” programming methods in GX Works2 and GX Developer.

35.1 SFC Program

35.1.1 Outline

Sequence control using the SFC (sequential function chart) is available in FX PLCs. In SFC programs, the role of each process and the overall control flow can be expressed easily based on machine operations, so sequence design is easy. Accordingly, machine operations can be easily transmitted to any person, and created programs are efficient in maintenance, specifications changes and actions against problems. When SFC programs and step ladder instructions are programmed conforming to the same rules, they are compatible with each other. As a result, the same contents can be handled in relay ladder charts which are familiar and easy to understand.

35.1.2 Explanation of function and operation

In SFC programs, a state relay State S is regarded as one control process, and the input conditions and output control sequence are programmed in each process. Because the preceding process is stopped when the program execution proceeds to the next process, a machine can be controlled using simple sequences for each process.

Operation of state relay State S and driven instruction

In SFC programs, each process performed by the machine is expressed by a state relay. Operations of internal circuits connected to state relays are classified into three types, execution in the contact ON status, execution in the contact OFF status (for one operation cycle) and non-execution.

  • Execution in the contact ON status: When a state relay turns ON, a connected circuit (internal circuit) is activated with a STL contact.
  • Execution in the contact OFF status (for one operation cycle): When a condition (transfer condition) provided between state relays is satisfied, the next state relay turns ON, and the state relay which has been ON before hand turns OFF (transfer operation). In the state relay ON status transfer process, both state relays are ON only momentarily (for one operation cycle). In the next operation cycle after the ON status is transferred to the next state relay, the former state relay is reset to OFF. A drive instruction connected to the bus line of the reset state relay is executed in the contact OFF status in one operation cycle regardless of the actual contact status before the drive instruction. When the transfer state relay S is used in a contact instruction, however, the contact image is executed in the OFF status immediately after the transfer condition is satisfied.
  • Non-execution: An instruction is not executed in the contact OFF status after the operation cycle where the instruction was executed in the contact OFF status (jump status).
  • The figure below shows the timing chart of the state relay (internal circuit) activation status.

Execution in the contact ON status

Execution in the contact OFF status in one operation cycle

Non-execution (jump status) Execution

  • A state relay number can only be used once.
Page 759 of the Mitsubishi Electronics MELSEC FX3S user manual — 35. SFC Program and Step Ladder
Page 759 · click to enlarge
Page 759

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

Mitsubishi Electronics MELSEC FX3S — 35. SFC Program and Step Ladder diagram (page 759)
Fig. 759 · 35. SFC Program and Step Ladder

Y31 programmed in the SET instruction remains ON even if S31 turns OFF.

*1. Output coils can be used again in different state relays.

Page 760 of the Mitsubishi Electronics MELSEC FX3S user manual — 1. Operation example
Page 760 · click to enlarge
Page 760

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program

35.1.3 SFC program creating procedure

Create an SFC program using the following procedure:

1. Operation example

Mitsubishi Electronics MELSEC FX3S — 1. Operation example diagram (page 760)
Fig. 760 · 1. Operation example
1. When the start pushbutton switch is pressed, the truck moves forward. When the limit switch LS1 turns ON, the truck immediately starts to move backward. (The limit switch LS1 is normally OFF, and turns ON when the truck reaches the forward limit. Other limit switches function in the same way.)
2. When the truck moves backward and the limit switch LS2 turns ON, the truck stops for 5 seconds, and then starts to move forward again. When the limit switch LS3 turns ON, the truck immediately starts to move backward.
3. When LS2 turns ON after that, the truck driving motor stops.
4. When the start pushbutton switch is pressed again after a series of operations finish, the above operation is repeated.
2. Creating a process drawing Create the process drawing shown on the right using the following procedure:
Mitsubishi Electronics MELSEC FX3S — 1. Operation example diagram (page 760)
Fig. 761 · 1. Operation example
1. Divide the operation described in the above example into individual processes, and express each process in a rectangle in the order of operation from top to bottom.
2. Connect each process with vertical lines, and write the condition for each proceeding process. When performing repeated operations, indicate with an arrow the process the truck will return to after a series of operations finish.
3. Write the operation performed in each process on the right side of each rectangle indicating a process.
Page 761 of the Mitsubishi Electronics MELSEC FX3S user manual — M8002
Page 761 · click to enlarge
Page 761

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program 31

3. Assigning devices Assign devices of a PLC in the created process drawing.

FNC277-FNC279 Data Transfer 3

1) Assign a state relay to a rectangle indicating a process. At this time, assign a state relay (S0 to S9) to the initial process. After the first process, arbitrarily assign state relay numbers (S20 to S899) except the initial state relays. (There is no relationship between state relay numbers and order of processes.) There are latched (battery backed) type state relays whose ON/ OFF status is stored against power failure. The state relays S10 to S19 are used for special purposes when the IST (FNC 60) instruction is used.

FNC280-FNC289 High-Speed Processing 2

Y023

Y021

Limit switch for minor forward movement

2. Assign a device (input terminal number connected to a pushbutton switch or limit switch, timer number, etc.) to each transfer condition. NO contact and NC contact are available for a transfer condition. If there are two or more transfer conditions, AND circuit or OR circuit is available.

Y023 Y021

FNC290-FNC299 Extension File Register Control

Limit switch for backward movement

T0 K50

FNC300-FNC305 FX 3U -CF-ADP

3) Assign a device (output terminal number connected to external equipment, timer number, etc.) used for an operation performed in each process. Many devices such as timers, counters and auxiliary relays are provided in a PLC, and can be used arbitrarily. The timer T0 is used here. Because T0 works by the 0.1 sec clock, the output contact turns ON five seconds after a coil is driven when the set value is K50. If there are two or more loads such as timers and counters which are driven at the same time, two or more circuits can be assigned to one state relay.

T0

Y021 Y023

Limit switch for major forward movement

Y023 Y021

Limit switch for backward movement

4. When performing repeated operations or skipping some processes (jump operation), use “ ” and specify the jump destination state relay number.

In this example, only the SFC program creating procedure is explained. In practical cases, a circuit for setting the initial state relay to ON is required to execute the SFC program. Create a circuit for setting the initial state relay to ON using the relay ladder. At this time, use SET instruction to set the initial state relay to ON.

M8002

SET S0

A

B

Show 14 more labels / short text on this page
Start switch · Forward · Backward · Stop timer · Timer · Forward · SFC•STL Programming · Backward · Interrupt Function · Initial pulse · Special Device · Error Code · Version Up Information · Execution Times
Page 762 of the Mitsubishi Electronics MELSEC FX3S user manual — 4. Inputting and indicating a program using GX Works2 and GX Developer
Page 762 · click to enlarge
Page 762

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program

4. Inputting and indicating a program using GX Works2 and GX Developer

  • Input a circuit for setting the initial state relay to ON using the relay ladder. In this example, the initial state relay S0 is set to ON in a ladder block using the special auxiliary relay M8002 which turns ON momentarily when the PLC mode is changed from STOP to RUN.
  • When inputting a program using GX Works2 and GX Developer, write a relay ladder program to a ladder block, and write an SFC program to an SFC block.
  • Programs expressing operations in state relays and transfer conditions are handled as internal circuits of the state relays and transfer conditions. Create each one using a relay ladder.

For details on the programming procedure, refer to the following manual.

→ GX Developer Version 8 Operating Manual → GX Works2 Version 1 Operating Manual (Simple Project)

Write a circuit not belonging to SFC to a ladder block using a relay ladder.

Mitsubishi Electronics MELSEC FX3S — 4. Inputting and indicating a program using GX Works2 and GX Developer diagram (page 762)
Fig. 762 · 4. Inputting and indicating a program using GX Works…

SET S0 Program for setting the initial state relay to ON

Indicate the state relay number and transfer condition number. 0

When a program is input using GX Works2 and GX Developer, “RET” and “END” are automatically written.

Page 763 of the Mitsubishi Electronics MELSEC FX3S user manual — 35.1.5 Latched (battery backed) type state relays
Page 763 · click to enlarge
Page 763

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program 31

35.1.4 Handling and role of initial state relay

FNC277-FNC279 Data Transfer 3

Handling of the initial state relay

  • A state relay located at the head of an SFC program is the initial state relay. Only state relays S0 to S9 are available.
  • The initial state relay is driven by way of another state relay (S24 in the example shown below). But it is necessary to drive the initial state relay in advance by another measure at the start of operation.

FNC280-FNC289 High-Speed Processing 2

  • In the example shown below, the initial state relay is driven by the special auxiliary relay M8002 which turns ON and remains ON only momentarily when the PLC mode is changed from STOP to RUN.
  • General state relays other than initial state relays should be driven by another state relay. They cannot be driven by any other device.
  • The state relay which may be driven by a contact other than the STL instruction is there by defined as the initial state relay, and should be described at the top of the flow.

FNC290-FNC299 Extension File Register Control

The initial state relay is driven.

M8002

SET S0

FNC300-FNC305 FX 3U -CF-ADP

TRAN

Y023

Y021

TRAN

TRAN

Y021

Y023

TRAN

RET END

Role of the initial state relay

1. Used as an identification device for inverse conversion

  • In inverse conversion from an instruction list into an SFC program, it is necessary to identify the top of the flow. For this purpose, use the initial state relay S0 to S9. If any other state relay number is used, inverse conversion is disabled.
  • Program the STL instruction for the initial state relay before the STL instructions for subsequent state relays. Program the RET instruction at the end. By this programming method, if there are two or more independent flows, they the separated from each other.

A

2. Used to prevent double start

  • In the above example, even if the start button is pressed while the state relay S24 is ON, the command is invalid (S0 does not turn ON). As a result, double start is prevented.

B

35.1.5 Latched (battery backed) type state relays

In the latched (battery backed) type state relays, the ON/OFF status is backed up by the battery or EEPROM memory against power failure. Use this type of state relay if the operation should be restarted from the last point before power failure.

Show 10 more labels / short text on this page
Initial pulse · Ladder block · Initial state relay · SFC block · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 764 of the Mitsubishi Electronics MELSEC FX3S user manual — Special auxiliary relays
Page 764 · click to enlarge
Page 764

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program

35.1.6 Role of the RET instruction

  • Use the RET instruction at the end of an SFC program. When inputting an SFC program using GX Works2 and GX Developer, however, it is not necessary to input the RET instruction (because RET instruction is automatically written).
  • In a PLC, two or more SFC blocks can be put between step 0 and the END instruction. When there are ladder blocks and SFC blocks, put a RET instruction at the end of each SFC program.

35.1.7 Preliminary knowledge for creating SFC program

List of sequence instructions available in states

LD/LDI/LDP/LDF, AND/ANI/ANDP/ANDF,

OR/ORI/ORP/ORF, INV,MEP/MEF,OUT,

ANB/ORB/MPS/MRD/

MPP MC/MCR

SET/RST,PLS/PLF

Initial/general state relay Available Available*1 Not available

Drive processing Available Available*1 Not available

Transfer processing Available Not available Not available

  • STL instruction cannot be used in interrupt programs and subroutine programs.
  • When using SFC programs (STL instruction), do not drive state relays S using SET or OUT instructions in an interrupt program.
  • It is not prohibited to use jump instructions in state relays. However, it is not recommended to use jump instructions because complicated movements will result.

*1. The MPS instruction cannot be used immediately after a state relay (STL instruction), even in a drive processing circuit.

Special auxiliary relays

For efficiently creating SFC programs, it is necessary to use some special auxiliary relays. The table below shows major ones.

Device number Name Function and application

This relay is normally ON while the PLC is in the RUN mode. Use this relay as the program input condition requiring the normally driven status or for indicating the PLC operation status.

This relay turns ON and remains ON only momentarily when the PLC mode is changed from STOP to RUN. Use this relay for the initial setting of a program or for setting the initial state relay.

When this relay is set to ON, transfer to the ON status is disabled among all state relays. Because programs in state relays are operating even in the transfer disabled status, output coils do not turn OFF automatically.

M8040 STL transfer disable

Use this relay to prevent simultaneous startup of another flow or as a process ON/OFF flag. When M8047 is OFF, M8046 is normally OFF. When M8047 is ON, M8046 operates as follows: FX3S PLC When at least one among the state relays S0 to S255 is ON: ON When all of the state relays S0 to S255 are OFF: OFF FX3G/FX3GC/FX3U/FX3UC PLCs When at least one among the state relays S0 to S899 and S1000 to S4095 is ON: ON When all of the state relays S0 to S899 and S1000 to S4095 are OFF: OFF

M8046*2 STL state ON

  • When this relay is driven, the device number of a state relay in the ON status having the smallest device number among S0 to S255(FX 3S PLC), S0 to S899 and S1000 to S4095(FX 3G /FX 3GC /FX 3U /FX 3UC PLCs) is stored to D8040, and the state relay number in the ON status having the next smallest device number is stored to D8041. In this way, up to eight state relays in the ON status are stored in registers up to D8047.
  • In the FX-PCS/WIN(-E), FX-30P, FX-20P(-E), and FX-10P(-E), when this relay is driven, the state relays in the ON status are automatically read and displayed. For details, refer to the appropriate peripheral equipment manual.
  • In the SFC monitor in GX Works2 and GX Developer, the automatic scroll monitoring function is valid even if this relay is not driven.

M8047*2 Enable STL monitoring

*2. Processed when the END instruction is executed.

Show 5 more labels / short text on this page
Instruction · State relay · Branch/recombination state relay · M8000 RUN monitor · M8002 Initial pulse
Page 765 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 765 · click to enlarge
Page 765

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program 31

Operation of state relays and use of an output two or more times

FNC277-FNC279 Data Transfer 3

20 Y001

  • In different state relays, the same output device (Y002 in this example) can be programmed as shown in the right figure. In this case, when S21 or S22 is ON, Y002 is output. However, if the same output coil (Y002) in a state relay is programmed in a ladder block program or if the same output coil is programmed twice in one state relay, it is handled in the same way as general double coil.

Y002

FNC280-FNC289 High-Speed Processing 2

When S21 or S22 is ON, Y002 is output.

Y002

Interlock of outputs

FNC290-FNC299 Extension File Register Control

  • In the state relay ON status transfer process, both states turn ON at the same time only momentarily (during one operation cycle). Accordingly, between a pair of outputs which should not be set to ON at the same time, provide an interlock outside the PLC in conformance to the handy manual of the PLC so that simultaneous driving can be prevented. In addition, provide on interlock in the program as shown in the right figure.

Y002

20 Y001

Y002 Y001

FNC300-FNC305 FX 3U -CF-ADP

Use of a timer two or more times

  • In the same way as an output coil, a timer coil can be programmed in different state relays. However, it is not permitted to program the same timer coil in adjacent state relays. If the same timer coil is programmed in adjacent state relays, the timer coil is not set to OFF at process transfer, so the current value is not reset.

40 T1

K10

T1

T1

K20

Output driving method

  • It is not permitted to program an instruction without a contact after an LD or LDI instruction from a bus line in a state relay. Change such a circuit as shown below.

10 Y001

Y002

Y003

A

10 Y001

10 Y001

Y003

Y002

M8000

Y002

Y003

Move the position.

Insert "Always ON" contact.

B

Show 13 more labels / short text on this page
Forward · rotation · Backward rotation · SFC•STL Programming · Not allowed · Interrupt Function · Special Device · Error Code · Change Change · Version Up Information · or · RUN monitor · Execution Times
Page 766 of the Mitsubishi Electronics MELSEC FX3S user manual — Operation of “ ” and “ V ”
Page 766 · click to enlarge
Page 766

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program

Operation of “ ” and “ V ”

Use “ ” to express transfer to a state relay in an upper position (repeat), transfer to a state relay in a lower position (jump), or transfer to a state relay in a separate flow. Use “V” to express reset of a state relay.

1. Transfer source program
Mitsubishi Electronics MELSEC FX3S — Operation of “ ” and “ V ” diagram (page 766)
Fig. 763 · Operation of “ ” and “ V ”
2. Transfer destination program In GX Works2 and GX Developer, “ z ” is automatically displayed in the transfer destination state relay.
Mitsubishi Electronics MELSEC FX3S — Operation of “ ” and “ V ” diagram (page 766)
Fig. 764 · Operation of “ ” and “ V ”
3. Reset circuit program In the program example shown below, S65 is reset from S65 by way of X007. Reset of another state relay (S70, for example) from S65 is executed in the same way. In GX Works2 and GX Developer, “ z ” is automatically displayed in a state relay to be reset.
Mitsubishi Electronics MELSEC FX3S — Operation of “ ” and “ V ” diagram (page 766)
Fig. 765 · Operation of “ ” and “ V ”
Page 767 of the Mitsubishi Electronics MELSEC FX3S user manual — X001 LD
Page 767 · click to enlarge
Page 767

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program 31

Resetting multiple state relays at one time and output disable

FNC277-FNC279 Data Transfer 3

For output disability corresponding to emergency stop, follow “Cautions on safety” described in the PLC manual.

1. Resetting multiple state relays at one time by specifying a range Resetting fifty-one state relays from S0 to S50 are reset time.

ZRST S0 S50

FNC280-FNC289 High-Speed Processing 2

State relays from S0 to S50 are reset. 50

FNC290-FNC299 Extension File Register Control

2. Disabling arbitrary outputs of state relays in the ON status

FNC300-FNC305 FX 3U -CF-ADP

SET M10

Even when the output disable contact turns ON, this output remains ON.

Y001

M10

Y005

When the output disable contact turns ON, these outputs turn OFF.

M30

T4

3. Turning OFF all output relays (Y) in a PLC While the special auxiliary relay M8034 is ON, the sequence program is executed continuously, but all output relays (Y) turn OFF. (These output relays are in the ON status in the monitor.)

M8034

While the special auxiliary relay M8034 is ON, the sequence program is executed continuously, but all output relays (Y) turn OFF.

Position of the MPS, MRD and MPP instructions

The MPS, MRD or MPP instructions cannot be used directly from a bus line in a state relay inside the STL. Program MPS, MRD or MPP instructions after LD or LDI instructions as shown below.

X001 LD

Y001

MPS

Y002

MRD

A

Y003

MPP

B

Show 15 more labels / short text on this page
Reset FNC 40 · Ladder block · SFC block · Output disable · Ladder block · SFC block · SFC•STL Programming · Interrupt Function · Output disable · Ladder block · Special Device · Error Code · Version Up Information · STL bus line · Execution Times
Page 768 of the Mitsubishi Electronics MELSEC FX3S user manual — Transfer of state relay ON status by the same signal
Page 768 · click to enlarge
Page 768

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program

Programming complicated transfer conditions

In a transfer condition circuit, the ANB, ORB, MPS, MRD and MPP instructions are not available. Program the circuit as shown below:

Mitsubishi Electronics MELSEC FX3S — Programming complicated transfer conditions diagram (page 768)
Fig. 766 · Programming complicated transfer conditions

Processing of state relay whose transfer condition is already satisfied

In some cases, it is necessary to execute the next transfer after the limit switch X030 (working as the transfer condition) in the ON status is set to OFF once, and then set to ON again. In such a case, make the transfer condition into pulses as shown below so that transfer is not executed by M100 when S30 turns ON for the first time.

Mitsubishi Electronics MELSEC FX3S — Processing of state relay whose transfer condition is already satisfied diagram (page 768)
Fig. 767 · Processing of state relay whose transfer condition i…

Transfer of state relay ON status by the same signal

In some cases, it is necessary to transfer the state relay ON status by the ON/OFF operation of one pushbutton switch. To achieve such a transfer, it is necessary to convert the transfer signal into pulses in programming. The following two methods are available to convert the transfer condition into pulses:

1. Procedure using PLS instruction Immediately after pulse signal M0 turns ON and S50 turns ON, the transfer condition M1 (NC contact) is open. As a result, it is not possible to transfer the ON status to S51 at the same time when S50 turns ON. When M0 pulse turns ON again, the ON status is transferred to S51.
Mitsubishi Electronics MELSEC FX3S — Transfer of state relay ON status by the same signal diagram (page 768)
Fig. 768 · Transfer of state relay ON status by the same signal
Page 769 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 769 · click to enlarge
Page 769

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program 31

2. Procedure using a pulse contact instruction (M2800 to M3071) By using an auxiliary relay M2800 to M3071 in a rising/falling edge detection instruction (LDP, LDF, ANDP, ANDF, ORP or ORF), the ON status can be efficiently transferred by the same signal. When M2800 or later is specified as a device in a rising/falling edge detection instruction, only the first rising/falling edge detection instruction after a coil instruction is executed. Accordingly, when X001 is set to ON, only the transfer condition in a state relay currently in the ON status is ON during one operation cycle, and then the ON status is transferred to the next state relay.

FNC277-FNC279 Data Transfer 3

M2800 M2800

M2800

FNC280-FNC289 High-Speed Processing 2

1 M2800

TRAN

TRAN M2800

TRAN M2800

FNC290-FNC299 Extension File Register Control

*1. It is allowable to program a device number used in LD, LDI, OR or ORI instructions after a corresponding coil in the ladder block. However, if the same device number is programmed in a LDP, LDF, ANDP, ANDF, ORP or ORF instruction, the priority is given to such an instruction and the transfer condition is not effective.

FNC300-FNC305 FX 3U -CF-ADP

Caution on using a rising/falling edge detection contact When a rising/falling detection contact in a LDP, LDF, ANDP, ANDF, ORP or ORF instruction is used in a state relay, the contact whose status was changed while the state relay was OFF is detected when the state relay turns ON the next time. When it is necessary to immediately detect the rising edge or falling edge for a condition which may change while a state relay is OFF, change the program as shown below:

M6

M7 X014

SET S70

M6

SET S70

M7

When the ON status is transferred to S70 at the falling edge of X013 and then X014 turns OFF after that, the falling edge of X014 is not detected at this point because S3 is OFF. When S3 turns ON the next time, the falling edge of X014 is detected. Accordingly, when S3 turns ON the next time, the ON status is immediately transferred to S70.

A

B

Show 11 more labels / short text on this page
(Transfer input) · Ladder block · *1 · SFC block · SFC•STL Programming · Interrupt Function · Change · Special Device · Error Code · Version Up Information · Execution Times
Page 770 of the Mitsubishi Electronics MELSEC FX3S user manual — 1. Jump and repeat flows
Page 770 · click to enlarge
Page 770

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program

35.1.8 SFC flow formats

This section shows operation patterns of single flows and operation patterns when selective branches and parallel branches are combined in SFC programs.

1. Jump and repeat flows

1. Jump Direct transfer to a state relay in a lower position or transfer to a state relay in a different flow is called jump, and the transfer destination state relay is indicated by " ".
Mitsubishi Electronics MELSEC FX3S — 1. Jump and repeat flows diagram (page 770)
Fig. 769 · 1. Jump and repeat flows
2. Repeat Transfer to a state relay in an upper position is called repeat, and the transfer destination state relay is indicated by " " in the same way as "jump".
Mitsubishi Electronics MELSEC FX3S — 1. Jump and repeat flows diagram (page 770)
Fig. 770 · 1. Jump and repeat flows
Page 771 of the Mitsubishi Electronics MELSEC FX3S user manual — 35.1.8 SFC flow formats
Page 771 · click to enlarge
Page 771

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

Mitsubishi Electronics MELSEC FX3S — 35.1.8 SFC flow formats diagram (page 771)
Fig. 771 · 35.1.8 SFC flow formats

When creating an SFC program having two or more initial state relays, separate the blocks for each initial state relay. The ON status can be transferred among SFC programs created by block separation (jump to a different flow). A state relay in a program created in a different block can be used as a contact for the internal circuit or transfer condition of another state relay.

3. Using a state relay in a program created in a different block
Page 772 of the Mitsubishi Electronics MELSEC FX3S user manual — Composite flows with branches and recombination
Page 772 · click to enlarge
Page 772

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program

Composite flows with branches and recombination

The single flow format is the fundamental style in process transfer control. Only single flow is sufficient in sequence control for simple operations. When various input conditions and operator manipulations intervene, however, complicated conditions can be easily handled by using selective branches and parallel branches. A branch for selectively processing many processes depending on a condition is called selective branch. A branch for processing many processes at the same time is called parallel branch.

1. Selective branch Either one among many flows is selected and executed.
Mitsubishi Electronics MELSEC FX3S — Composite flows with branches and recombination diagram (page 772)
Fig. 772 · Composite flows with branches and recombination
2. Parallel branch All of many flows are executed at the same time.
Mitsubishi Electronics MELSEC FX3S — Composite flows with branches and recombination diagram (page 772)
Fig. 773 · Composite flows with branches and recombination
Page 773 of the Mitsubishi Electronics MELSEC FX3S user manual — 35.1.9 Program of branch/recombination state relays
Page 773 · click to enlarge
Page 773

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

Mitsubishi Electronics MELSEC FX3S — 35.1.9 Program of branch/recombination state relays diagram (page 773)
Fig. 774 · 35.1.9 Program of branch/recombination state relays
Page 774 of the Mitsubishi Electronics MELSEC FX3S user manual — 35.1.10 Rule for creating branch circuit
Page 774 · click to enlarge
Page 774

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program

35.1.10 Rule for creating branch circuit

Limitation in the number of branch circuits

In one parallel branch or selective branch, up to eight circuits can be provided. When there are many parallel branches and selective branches, however, the total number of circuits per initial state is limited to 16 or less.

Mitsubishi Electronics MELSEC FX3S — 35.1.10 Rule for creating branch circuit diagram (page 774)
Fig. 775 · 35.1.10 Rule for creating branch circuit

8 circuits or less in 1 (parallel or selective) branch

It is not permitted to execute transfer or reset from a recombination line or state relay before recombination to a branch state relay. Make sure to provide a dummy state, then execute transfer or reset from a branch line to a separate state relay.

Page 775 of the Mitsubishi Electronics MELSEC FX3S user manual — 35.1.10 Rule for creating branch circuit
Page 775 · click to enlarge
Page 775

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

Mitsubishi Electronics MELSEC FX3S — 35.1.10 Rule for creating branch circuit diagram (page 775)
Fig. 776 · 35.1.10 Rule for creating branch circuit
1. When a recombination line is directly connected to a branch line without a state relay When a recombination line is directly connected to a branch line without a state relay as shown below, it is necessary to provide a dummy state relay between the lines. There are no dedicated numbers for dummy state relays. Use a state relay number not used in a program as a dummy state relay.

100 Dummy state relay 101 102 103 Dummy state relay

Page 776 of the Mitsubishi Electronics MELSEC FX3S user manual — 35.1.10 Rule for creating branch circuit
Page 776 · click to enlarge
Page 776

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program

2. When there are selective branches continuously, reduce the number of branches.
Mitsubishi Electronics MELSEC FX3S — 35.1.10 Rule for creating branch circuit diagram (page 776)
Fig. 777 · 35.1.10 Rule for creating branch circuit
Page 777 of the Mitsubishi Electronics MELSEC FX3S user manual — 35.1.10 Rule for creating branch circuit
Page 777 · click to enlarge
Page 777

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

Mitsubishi Electronics MELSEC FX3S — 35.1.10 Rule for creating branch circuit diagram (page 777)
Fig. 778 · 35.1.10 Rule for creating branch circuit
3. It is not permitted to provide a selective transfer condition * after parallel branches or to recombine parallel branches after a transfer condition < * >.
4. In the flow shown below, it is not determined whether a selective or parallel branch is provided. Change it as shown below.
5. The following flows are allowed. Flow B is alright. In flow A, however, note that an operation is paused at a point where parallel branches are recombined.
Page 778 of the Mitsubishi Electronics MELSEC FX3S user manual — 35.1.11 Program examples
Page 778 · click to enlarge
Page 778

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program

6. It is not permitted to cross flows in SFC programs. Change a flow on the left to a flow on the right. This change enables inverse conversion from a program on the instruction word basis into an SFC program. (The flow on the left cannot be converted into an SFC program.)
Mitsubishi Electronics MELSEC FX3S — 35.1.11 Program examples diagram (page 778)
Fig. 779 · 35.1.11 Program examples

35.1.11 Program examples

Examples of single flows

1. Example of flicker circuit

1. When the PLC mode is changed from STOP to RUN, the state relay S3 is driven by the initial pulse (M8002).
2. The state relay S3 outputs Y000. One second later, the ON status transfers to the state relay S20.
3. The state relay S20 outputs Y001. 1.5 seconds later, the ON status returns to the state relay S3.
Mitsubishi Electronics MELSEC FX3S — 35.1.11 Program examples diagram (page 778)
Fig. 780 · 35.1.11 Program examples
Page 779 of the Mitsubishi Electronics MELSEC FX3S user manual — 0 TRAN X000
Page 779 · click to enlarge
Page 779

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program 31

2. Example of fountain control

FNC277-FNC279 Data Transfer 3

1. Cyclic operation (X001 = OFF, X002 = OFF) When the start button X000 is pressed, the outputs turn ON in the order “Y000 (wait indication) → Y001 (center lamp) → Y002 (center fountain) → Y003 (loop line lamp) → Y007 (loop line fountain) → Y000 (wait indication)”, and then the outputs return to the wait status. Each output is switched in turn every 2 seconds by a timer.
2. Continuous operation (X001 = ON) Y001 to Y007 turn ON in turn repeatedly.

FNC280-FNC289 High-Speed Processing 2

3. Stepping operation (X002 = ON) Every time the start button is pressed, each output turns ON in turn.

Y000

FNC290-FNC299 Extension File Register Control

0 TRAN X000

Y001

M8002

S3 SET

T1

TRAN T1 K20

FNC300-FNC305 FX 3U -CF-ADP

Y002

T2

TRAN T2 K20

Y003

T3

TRAN T3 K20

Y007

T7

K2 0

TRAN T7

TRAN T7 X001 5

A

B

Show 23 more labels / short text on this page
M8000 Ladder block · Enable STL monitoring · Wait indication · M8047 RUN monitor · SFC block · Start button · STL transfer disable · M8040 Stepping · Start · Center lamp · Initial state relay · Initial pulse · Center fountain · Loop line lamp · SFC•STL Programming · Loop line fountain · Interrupt Function · RET END Continuous · Cyclic/stepping · Special Device · Error Code · Version Up Information · Execution Times
Page 780 of the Mitsubishi Electronics MELSEC FX3S user manual — 35.1.11 Program examples
Page 780 · click to enlarge
Page 780

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program

3. Example of cam shaft turning control The limit switches X013 and X011 are provided in two positions, large forward rotation angle and small forward rotation angle. The limit switches X012 and X010 are provided in two positions, large backward rotation angle and small backward rotation angle. When the start button is pressed, the cam shaft performs the operation “small forward rotation → small backward rotation → large forward rotation → large backward rotation”, and then stops.
Mitsubishi Electronics MELSEC FX3S — 35.1.11 Program examples diagram (page 780)
Fig. 781 · 35.1.11 Program examples

The limit switches X010 to X013 are normally OFF. When the cam shaft reaches a specified angle, a corresponding limit switch turns ON.

  • When M8047 turns ON, the operation state monitoring becomes valid. If either one among S0 to S899 and S1000 to S4095 is ON, M8046 turns ON after the END instruction is executed.
  • This SFC program adopts latched (battery backed) type state relays so that the operation is restarted from this process when the start button is pressed even after the power is interrupted in the middle of operation. However, all outputs except Y020 are disabled until the start button is pressed.
Mitsubishi Electronics MELSEC FX3S — 35.1.11 Program examples diagram (page 780)
Fig. 782 · 35.1.11 Program examples

<M8034: All outputs disable> When M8034 is set to ON, all outputs to the outside turn OFF even though the PLC is executing each program in RUN mode.

Page 781 of the Mitsubishi Electronics MELSEC FX3S user manual — 35.1.11 Program examples
Page 781 · click to enlarge
Page 781

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

Mitsubishi Electronics MELSEC FX3S — 35.1.11 Program examples diagram (page 781)
Fig. 783 · 35.1.11 Program examples
4. Example of sequential start and stop The motors M1 to M4 are started in turn by a timer, and stopped in turn in the reverse order. This SFC flow is based on a single flow, and has jumps of state relays.

In the case of stop in the middle of operation, the motors are stopped also in turn in the reverse order.

This SFC program shows an example in which a part of the flow is skipped according to a condition, and the execution is transferred to a state in a lower position. The execution can be transferred to a state in an upper position.

Page 782 of the Mitsubishi Electronics MELSEC FX3S user manual — 35.1.11 Program examples
Page 782 · click to enlarge
Page 782

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program

The partial skip flow shown on the previous page can be expressed in a flow of selective branches and recombination as shown below. Make sure that a flow proceeds from top to bottom, and that a flow does not cross except branch lines and recombination lines.

Mitsubishi Electronics MELSEC FX3S — 35.1.11 Program examples diagram (page 782)
Fig. 784 · 35.1.11 Program examples

For example, if X001 turns ON while the state relay S20 is ON, the state relay S32 turns ON; The contact of S32 turns ON, and the ON status is immediately transferred to the state relay S27. Because one or more state relays are required in a branch line, dummy states are provided for this purpose.

Page 783 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 783 · click to enlarge
Page 783

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program 31

Examples of flows having selective branches and recombination

FNC277-FNC279 Data Transfer 3

1. Operation of selective branch

  • When two or more flows are provided and either one is selected and executed, it is called a selective branch.

TRAN X000

TRAN X010

TRAN X020

  • In the example shown on the right, X000, X010 and X020 should not turn ON at the same time.

FNC280-FNC289 High-Speed Processing 2

  • For example, when X000 turns ON while S20 is ON, the ON status is transferred to S21; S20 turns OFF, and S21 turns ON. Accordingly, even if X010 or X020 turns ON after that, S31 and S41 do not turn ON.

TRAN X002

TRAN X012

TRAN X022

FNC290-FNC299 Extension File Register Control

  • The recombination state relay S50 is driven by either S22, S32 or S42.

2. Example of selecting and carrying large and small balls The figure below shows a mechanism which selects and carries large and small balls using conveyors. The upper left position is regarded as the origin, and the mechanism performs in the order “moving down → suction → moving up → moving rightward → moving down → release → moving up → moving leftward”. When the arm moves down and the electromagnet pushes a large ball, the lower limit switch LS2 turns OFF. When the electromagnet pushes a small ball, LS2 turns ON.

FNC300-FNC305 FX 3U -CF-ADP

X005 LS5 X001 LS1 Left limit switch

X004 LS4

Moving rightwardY003 Moving leftward: Y004

X003 LS3 Upper limit switch

M

Moving upY002 Moving down: Y000

CY1

When a large ball is pushed, the piston does not reach the lower limit and X002 does not turn ON.

X002 LS2 Lower limit switch

Proximity switch PS0 X000

A

B

Show 12 more labels / short text on this page
X026 Start · SFC•STL Programming · Origin indication Y007 · Interrupt Function · + · + · Special Device · Electromagnet Y001 · Error Code · Small Large · Version Up Information · Execution Times
Page 784 of the Mitsubishi Electronics MELSEC FX3S user manual — RET END
Page 784 · click to enlarge
Page 784

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program

In an SFC program for selecting large or small products and judging products as either accepted or rejected, selective branches and recombination are adopted as shown in the figure below.

M8002

S0 SET Initial pulse

Y007 X003 Y001 Origin indication

When a product is small (when X002 turns ON), the left flow is valid. When a product is large, the right flow is valid.

0 TRAN X026

Y007

Y000

K20

TRAN T0 X002

T0

TRAN

Lower limit switchON (small ball)
Lower limit switchOFF (large ball)

Y001 SET

T1 K10

T1 K10

T1

2 T1

TRAN

TRAN

TRAN

TRAN

Upper limit switch Upper limit switch

Y004 Y004

TRAN X005

Right limit switch (small bucket)

Right limit switch (large bucket)

The ON status is transferred to the recombination state relay S30 when X004 turns ON in the case of a small product, or when X005 turns ON in the case of a large product.

TRAN X002

T2

K10

6 TRAN T2

When the special auxiliary relay M8040 described later is driven, all transfers to any state relay are disabled. In each of the state relays S24, S27 and S33, an interlock contact is connected in series respectively to the rightward movement output Y003 and leftward movement output Y004.

TRAN X003

Y003

TRAN X001

Left limit switch 0

RET END

Show 31 more labels / short text on this page
Ladder block · Left limit · Upper · Release · limit · SFC block · · Start · Origin · Moving down T0 · Y001 SET Suction · Suction · Y002 Moving · Y002 Moving · up X003 · up X003 · Y003 Moving · Y003 Moving · rightward · rightward TRAN X004 · Y000 Moving · · down · Lower limit switch · Y001 RST Release · Y002 Moving · up · · Upper limit switch · Y004 Moving · leftward
Page 785 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 785 · click to enlarge
Page 785

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program 31

Example of flows having parallel branches and recombination

FNC277-FNC279 Data Transfer 3

1. Operation of parallel branch

  • Branches in which all flows proceed at the same time are called parallel branches.

TRAN X000

  • In the example shown on the left, when X000 turns ON while S20 is ON, S21, S24 and S27 turn ON at the same time and the operation is started in each flow.

FNC280-FNC289 High-Speed Processing 2

  • When the operation is finished in each flow and X007 turns ON, the recombination state relay S30 turns ON. S23, S26 and S29 turn OFF.
  • Such recombination is sometimes called wait recombination. (The original flow continues its operation until all flows finish their operations and join the original flow.)

FNC290-FNC299 Extension File Register Control

When the parts A, B and C are processed in parallel and then assembled afterward, flows having parallel branches and recombination are used.

TRAN X007

FNC300-FNC305 FX 3U -CF-ADP

2. Example of pushbutton type crosswalk A pushbutton type crosswalk shown in the figure below can be expressed in flows having parallel branches and recombination. Y003: Green Y002: Yellow Y001: Red
Mitsubishi Electronics MELSEC FX3S — TRAN X007 diagram (page 785)
Fig. 785
  • The SFC program for a pushbutton type crosswalk is as shown below. In this example, a partial flow (jump to a state relay located in an upper position) is repeated for blinking the green lamp on the crosswalk.
  • When the PLC mode is changed from STOP to RUN, the initial state relay S0 turns ON. Normally, the green lamp is ON for the road and the red lamp is ON for the sidewalk.
  • When the crossing button X000 or X001 is pressed, the state relay S21 specifies “road: green” and the state relay S30 specifies “sidewalk: red”. The signal lamp status is not changed.
  • 30 seconds later, the yellow lamp turns ON for the road. 10 seconds later after that, the red lamp turns ON for the road.
  • When the timer T2 (5 seconds) reaches timeout after that, the green lamp turns ON for the sidewalk.
  • 15 seconds later, the green lamp starts to blink for the sidewalk. (S32 turns OFF the green lamp, and S33 turns ON the green lamp.)
  • While the green lamp is blinking, S32 and S33 turn ON and OFF repeatedly. When the counter C0 (set value: 5) turns ON, S34 turns ON. 5 seconds after the red lamp turns ON for the sidewalk, the signal lamps return to the initial state.
  • Even if the crossing button X000 or X001 is pressed in the middle of operation, the pressing is ignored.

A

B

Show 6 more labels / short text on this page
SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 786 of the Mitsubishi Electronics MELSEC FX3S user manual — 35.1.11 Program examples
Page 786 · click to enlarge
Page 786

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.1 SFC Program

Mitsubishi Electronics MELSEC FX3S — 35.1.11 Program examples diagram (page 786)
Fig. 786 · 35.1.11 Program examples

This counter counts how many times the state relay S33 turns ON. When S33 turns ON five times, the contact C0 turns ON.

Page 787 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 787 · click to enlarge
Page 787

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.2 Step Ladder 31

35.2 Step Ladder

FNC277-FNC279 Data Transfer 3

35.2.1 Outline

In programs using step ladder instructions, a state relay State S is assigned to each process based on machine operations, and sequences of input condition and output control are programmed as circuits connected to contacts (STL contacts) of state relays in the same way as SFC programs. The concept of program creation and the types and operations of state relays are the same as for SFC programs. However, because the contents can be expressed in the ladder format, step ladder programs can be handled as familiar relay ladder charts even though the actual contents are the same as those of SFC programs. In step ladder programs, the list format is also available. SFC programs and step ladder programs can be converted inter changeably if they are programmed according to the same rules.

FNC280-FNC289 High-Speed Processing 2

This section explains the expressions and cautions of step ladder programs in comparison with SFC programs, and the input order in the list format.

FNC290-FNC299 Extension File Register Control

35.2.2 Explanation of function and operation

In a step ladder program, a state relay State S is regarded as one control process, and a sequence of input conditions and output controls are programmed in a state relay. Because the preceding process is stopped when the program execution proceeds to the next process, a machine can be controlled using simple sequences for each process.

FNC300-FNC305 FX 3U -CF-ADP

Operation of step ladder instructions

In a step ladder program, each process performed by the machine is expressed by a state relay. A state relay consists of a drive coil and contact (STL contact) in the same way as other relays. Use SET or OUT instructions to drive a coil, and use STL instructions for a contact. Operations of internal circuits connected to state relays are classified into three types, execution in the contact ON status, execution in the contact OFF status (for one operation cycle) and non-execution.

  • Execution in the contact ON status: When a state relay turns ON, a connected circuit (internal circuit) is activated with a STL contact.
  • Execution in the contact OFF status (for one operation cycle): When a condition (transfer condition) provided between state relays is satisfied, the next state relay turns ON, and the state relay which has been ON before hand turns OFF (transfer operation). In the state relay ON status transfer process, both state relays are ON only momentarily (for one operation cycle). In the next operation cycle after the ON status is transferred to the next state relay, the former state relay is reset to OFF. A drive instruction connected to the bus line of the reset state relay is executed in the contact OFF status in one operation cycle regardless of the actual contact status before the drive instruction. When the transfer state relay S is used in a contact instruction, however, the contact image is executed in the OFF status immediately after the transfer condition is satisfied.
  • Non-execution: An instruction is not executed in the contact OFF status after the operation cycle where the instruction was executed in the contact OFF status (jump status).
  • The figure below shows the timing chart of the state relay (internal circuit) activation status.

Execution in the contact ON status

Execution in the contact OFF status in one operation cycle

Non-execution (jump status) Execution

A

  • One state relay number can only be used once.

B

Show 6 more labels / short text on this page
SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 788 of the Mitsubishi Electronics MELSEC FX3S user manual — 35.2 Step Ladder
Page 788 · click to enlarge
Page 788

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.2 Step Ladder

Mitsubishi Electronics MELSEC FX3S — 35.2 Step Ladder diagram (page 788)
Fig. 787 · 35.2 Step Ladder

Y31 programmed in the SET instruction remains ON even if S31 is reset.

When X001 turns ON, S32 turns ON and S31 is automatically reset.

*1. Output coils can be used again in different state relays.

*2. It is not possible to place a pointer immediately after the STL instruction. If a pointer is placed, a circuit error (Error code: 6617) occurs.

*3. The contact instruction can be omitted only immediately after the STL instruction. If the contact instruction is omitted, the contact status follows the status of the corresponding state relay.

Page 789 of the Mitsubishi Electronics MELSEC FX3S user manual — 35.2.3 Expression of step ladder
Page 789 · click to enlarge
Page 789

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

Mitsubishi Electronics MELSEC FX3S — 35.2.3 Expression of step ladder diagram (page 789)
Fig. 788 · 35.2.3 Expression of step ladder

Step ladder programs and SFC programs are substantially the same as described above, but actual programs are expressed as shown below. A step ladder program is expressed as a relay ladder, but it can be created according to the machine control flow using state relays.

SET S0 Program for setting to ON an initial state relay

State number and transfer condition number are indicated. 0

It is necessary to input the RET instruction in a program.

When a program is input using GX Works2 and GX Developer, “RET” and “END” are automatically written.

Page 790 of the Mitsubishi Electronics MELSEC FX3S user manual — Program with jump/repeated flows
Page 790 · click to enlarge
Page 790

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.2 Step Ladder

35.2.4 Creation of step ladder program (SFC program → STL program)

The figure on the left shows one state relay extracted as an example from an SFC program. Each state relay has three functions, driving a load, specifying a transfer destination and specifying a transfer condition. The step ladder shown on the right expresses this SFC program as a relay sequence. In this program, a load is driven, and then the ON status is transferred. In a state relay without any load, the drive processing is not required. For the program creation procedure, refer to the description on SFC programs.

→ For the program creation procedure, refer to Subsection 35.1.3. → For the handling and role of initial state relays, refer to Subsection 35.1.4.

→ For latched (battery backed) type state relays, refer to Subsection 35.1.5.

→ For RET instruction, refer to Subsection 35.1.6.

Mitsubishi Electronics MELSEC FX3S — 35.2.4 Creation of step ladder program (SFC program → STL program) diagram (page 790)
Fig. 789 · 35.2.4 Creation of step ladder program (SFC program…

S20 Y010 X010 X011 Y011 X000 X001 S21 *1

The above program can be expressed in the list format (list program) shown on the left. The segment from the STL instruction to the RET instruction is handled as a step ladder program.

*1. SET and RST instructions for a state relay are two-step instructions.

  • When every state relay used in an SFC program is defined, programming is complete.
  • Program a step ladder program starting from the initial state relay in the order of state relay ON status transfer. Make sure to put the RET instruction at the end of a step ladder program.

Program with jump/repeated flows

1. Program for the transfer source Use OUT instruction in the jump/repeated part.
Mitsubishi Electronics MELSEC FX3S — Program with jump/repeated flows diagram (page 790)
Fig. 790 · Program with jump/repeated flows
Page 791 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 791 · click to enlarge
Page 791

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.2 Step Ladder 31

2. Program for the transfer destination There is no change in programming especially for the transfer destination.

FNC277-FNC279 Data Transfer 3

<Step ladder> <SFC program> <List program>

STL LD OUT LD SET 53

S52 X004 Y002 X005 S53

52 Y002

STL S52

X004 X005

Y002

FNC280-FNC289 High-Speed Processing 2

TRAN

SET S53

FNC290-FNC299 Extension File Register Control

35.2.5 Preliminary knowledge for creating step ladder programs

→ For the preliminary knowledge for creating SFC programs, refer to Subsection 35.1.7.

List of sequence instructions available between the STL instruction and RET instruction

FNC300-FNC305 FX 3U -CF-ADP

LD/LDI/LDP/LDF, AND/ANI/ANDP/ANDF,

ANB/ORB/MPS/MRD/

OR/ORI/ORP/ORF, INV,MEP/MEF,OUT,

MPP MC/MCR

SET/RST,PLS/PLF

Initial/general state relay Available Available*1 Not available

Drive processing Available Available*1 Not available

Transfer processing Available Not available Not available

  • The STL instruction cannot be used in interrupt programs and subroutine programs.
  • When using SFC programs (STL instruction), do not drive state relays S using SET or OUT instructions in an interrupt program.
  • It is not prohibited to use jump instructions in state relays, but it is not recommended because complicated movements will result.

*1. MPS instruction cannot be used immediately after an STL instruction, even in a drive processing circuit.

A

B

Show 9 more labels / short text on this page
Instruction · State relay · SFC•STL Programming · Branch/recombination state relay · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 792 of the Mitsubishi Electronics MELSEC FX3S user manual — Block
Page 792 · click to enlarge
Page 792

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.2 Step Ladder

Special auxiliary relays

For efficiently creating step ladder programs, it is necessary to use some special auxiliary relays. The table below shows major ones. The special auxiliary relays shown below are the same as those available in SFC programs.

Device number Name Function and application

This relay is normally ON while the PLC is in the RUN mode. Use this relay as the program input condition requiring the normally driven status or for indicating the PLC operation status.

This relay turns ON and remains ON only momentarily when the PLC mode is changed from STOP to RUN. Use this relay for the initial setting of a program or for setting the initial state relay.

M8040 STL transfer disable

When this relay is set to ON, transfer of the ON status is disabled among all state relays. Because programs in state relays are operating even in the transfer disabled status, output coils do not turn OFF automatically.

Use this relay to prevent simultaneous startup of another flow or as a process ON/OFF flag. When M8047 is OFF, M8046 is normally OFF. When M8047 is ON, M8046 operates as follows: FX3S PLC When at least one among the state relays S0 to S255 is ON: ON When all of the state relays S0 to S255 are OFF: OFF FX3G/FX3GC/FX3U/FX3UC PLCs When at least one among the state relays S0 to S899 and S1000 to S4095 is ON: ON When all of the state relays S0 to S899 and S1000 to S4095 are OFF: OFF

M8046*1 STL state ON

  • When this relay is driven, the device number of a state relay in the ON status having the smallest device number among S0 to S255(FX 3S PLC), S0 to S899 and S1000 to S4095(FX 3G /FX 3GC /FX 3U /FX 3UC PLCs) is stored to D8040, and the state relay number in the ON status having the next smallest device number is stored to D8041. In this way, up to eight state relays in the ON status are stored in registers up to D8047.
  • In the FX-PCS/WIN(-E), FX-30P, FX-20P(-E), and FX-10P(-E), when this relay is driven, the state relays in the ON status are automatically read and displayed. For details, refer to the appropriate peripheral equipment manual.
  • In the SFC monitor in GX Works2 and GX Developer, the automatic scroll monitoring function is valid even if this relay is not driven.

M8047*1 Enable STL monitoring

*1. Processed when END instruction is executed.

Block

Mitsubishi Electronics MELSEC FX3S — Block diagram (page 792)
Fig. 791 · Block

A step ladder program is created as ladder circuits in the same way as relay ladder. Accordingly, different from SFC programs, it is not necessary to divide blocks for relay ladder parts and SFC parts. When there are ladder blocks and SFC blocks, put a RET instruction at the end of each step ladder program. A PLC starts the step ladder processing by a STL instruction, and returns to the relay ladder processing from the step ladder processing by a RET instruction. However, when consecutively programming a step ladder in a different flow (when there is no relay ladder before the step ladder in the different flow), a RET instruction between flows can be omitted, and a RET instruction can be programmed only at the end of the last flow.

M8000 RUN monitor · M8002 Initial pulse

Page 793 of the Mitsubishi Electronics MELSEC FX3S user manual — RST S41
Page 793 · click to enlarge
Page 793

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.2 Step Ladder 31

Output driving method

FNC277-FNC279 Data Transfer 3

It is required to include a LD or LDI instruction before the last OUT instruction in a state relay. Change such a circuit as shown below.

STL S20

Y001

FNC280-FNC289 High-Speed Processing 2

Y002

Y003

FNC290-FNC299 Extension File Register Control

STL S20 STL S20

Y001

Y001

Y003

Y002

M8000

FNC300-FNC305 FX 3U -CF-ADP

Y002

Y003

Move the position.

Insert "Always ON" contact.

State relay transfer method

Each OUT and SET instruction in state relays automatically resets the transfer source, and has the self-holding function. OUT instructions can only be used for transfer to a separate state relay in an SFC program.

STL S41

Transfer to the next state relay (SET instruction)

SET S42 Transfer condition

Transfer to a separate state relay (OUT instruction)

Replacing “ ” and “ V ”

Replace the symbol “ ” used in SFC programs to express repeat, jump or transfer to a state relay in another separate flow with the OUT instruction. Replace the symbol “V” (used to express reset of a state relay) with the RST instruction.

<Step ladder> <SFC program>

40 Y001

STL S40

Y001

TRAN

TRAN

SET S41

Replacement of “ ” in the part 52

A

STL S41

TRAN

Replacement of “ ” in the part 41

RST S41

B

Show 10 more labels / short text on this page
Change · Change · or · RUN monitor · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 794 of the Mitsubishi Electronics MELSEC FX3S user manual — 35.2.6 Program with state relays in branches and recombination
Page 794 · click to enlarge
Page 794

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.2 Step Ladder

35.2.6 Program with state relays in branches and recombination

1. Example of selective branch Do not use MPS, MRD, MPP, ANB and ORB instructions in a transfer processing program with branches and recombination. Even in a load driving circuit, MPS instructions cannot be used immediately after STL instructions. In the same way as programs for general state relays, program the drive processing first, and then program the transfer processing. Continuously program all transfer processing.
Mitsubishi Electronics MELSEC FX3S — 35.2.6 Program with state relays in branches and recombination diagram (page 794)
Fig. 792 · 35.2.6 Program with state relays in branches and rec…
Page 795 of the Mitsubishi Electronics MELSEC FX3S user manual — <Step ladder> <SFC program>
Page 795 · click to enlarge
Page 795

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.2 Step Ladder 31

2. Example of selective recombination Do not use MPS, MRD, MPP, ANB and ORB instructions in a transfer processing program with branches and recombination. Even in a load driving circuit, MPS instructions cannot be used immediately after STL instructions. Pay attention to the programming order so that a branch line does not cross a recombination line.

FNC277-FNC279 Data Transfer 3

<SFC program>

FNC280-FNC289 High-Speed Processing 2

Y010

39 Y011

49 Y012

TRAN 2 TRAN 3 TRAN

FNC290-FNC299 Extension File Register Control

<Step ladder> <List program>

STL OUT STL OUT STL OUT STL LD SET STL LD SET STL LD SET

S29 Y010 S39 Y011 S49 Y012 S29 X010 S50 S39 X011 S50 S49 X012 S50

STL S29

Y010

FNC300-FNC305 FX 3U -CF-ADP

STL S39

Y011

STL S49

Y012

STL S29

SET S50

STL S39

SET S50

STL S49

SET S50

Before recombination, first program the drive processing of state relays. After that, program only the transfer processing to recombination state relays. This rule should be observed to enable inverse conversion into an SFC program.

3. Example of parallel branch Do not use MPS, MRD, MPP, ANB and ORB instructions in a program with branches and recombination. Even in a load driving circuit, MPS instructions cannot be used immediately after STL instructions. In the same way as programs for general state relays, program the drive processing first, and then program the transfer processing. Continuously program all transfer processing.

<Step ladder> <SFC program>

<List program>

STL OUT LD SET SET SET 21

S20 Y000 X000 S21 S31 S41 31 41 SET S31

20 Y000

STL S20

A

TRAN

Y001

SET S21

B

SET S41

Show 10 more labels / short text on this page
Drive processing · SFC•STL Programming · Transfer processing · Interrupt Function · Special Device · Error Code · Drive processing · Version Up Information · Transfer processing · Execution Times
Page 796 of the Mitsubishi Electronics MELSEC FX3S user manual — STL LD SET STL LD SET STL LD SET LD SET
Page 796 · click to enlarge
Page 796

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.2 Step Ladder

4. Example of parallel recombination Do not use MPS, MRD, MPP, ANB and ORB instructions in a program with branches and recombination. Even in a load driving circuit, MPS instructions cannot be used immediately after STL instructions. Pay attention to the programming order so that a branch line does not cross a recombination line.
Mitsubishi Electronics MELSEC FX3S — 35.2.6 Program with state relays in branches and recombination diagram (page 796)
Fig. 793 · 35.2.6 Program with state relays in branches and rec…

STL OUT STL OUT STL OUT STL STL STL LD AND AND SET

S29 Y010 S39 Y011 S49 Y012 S29 S39 S49 X010 X011 X012 S50

Before recombination, first program the drive processing of the state relays. After that, program only the transfer processing to the recombination state relay.

5. Composition of branches and recombination When a recombination line is directly connected to a branch line without a state relay as shown below, it is necessary to provide a dummy state relay between the lines. Create step ladder programs as shown below.
1. Selective recombination and selective branch
Mitsubishi Electronics MELSEC FX3S — 35.2.6 Program with state relays in branches and recombination diagram (page 796)
Fig. 794 · 35.2.6 Program with state relays in branches and rec…

STL LD SET STL LD SET STL LD SET LD SET

S20 X000 S100 S30 X001 S100 S100 X003 S50 X004 S60

Page 797 of the Mitsubishi Electronics MELSEC FX3S user manual — STL LD SET STL LD SET STL LD SET SET
Page 797 · click to enlarge
Page 797

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

Mitsubishi Electronics MELSEC FX3S — 35.2.6 Program with state relays in branches and recombination diagram (page 797)
Fig. 795 · 35.2.6 Program with state relays in branches and rec…

STL LD SET STL LD SET STL LD SET SET

S20 X000 S102 S30 X001 S102 S102 S102 S40 S50

STL STL LD SET STL LD SET LD SET

S20 S30 X000 S103 S103 X001 S40 X002 S50

Page 798 of the Mitsubishi Electronics MELSEC FX3S user manual — SET S20
Page 798 · click to enlarge
Page 798

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.2 Step Ladder

35.2.7 Program examples

Examples of single flows

1. Example of flicker circuit

  • When the PLC mode is changed from STOP to RUN, the state relay S3 is driven by the initial pulse (M8002).
  • The state relay S3 outputs Y000. 1 second later, the ON status transfers to the state relay S20.
  • The state relay S20 outputs Y001. 1.5 seconds later, the ON status returns to the state relay S3.

<List program> <Step ladder>

M8002

SET S3 M8002 S3 S3 Y000 T0 K10 T0 S20 S20 Y001 T1 K15 T1 S3

0 1 3 4 5 8 9 11 12 13 16 17 19 20

LD SET STL OUT OUT LD SET STL OUT OUT LD OUT RET END

STL S3

Y000

Y000

Y001

K10 T0

T0

1.5 seconds

SET S20

STL S20

Y001

K15 T1

T1

RET

END

Show 4 more labels / short text on this page
Step number · Step number 0 · Initial pulse · 1 second
Page 799 of the Mitsubishi Electronics MELSEC FX3S user manual — X002 X000
Page 799 · click to enlarge
Page 799

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.2 Step Ladder 31

2. Example of fountain control

FNC277-FNC279 Data Transfer 3

1. Cyclic operation (X001 = OFF, X002 = OFF) When the start button X000 is pressed, the outputs turn ON in the order “Y000 (wait indication) → Y001 (center lamp) → Y002 (center fountain) → Y003 (loop line lamp) → Y007 (loop line fountain) → Y000 (wait indication)”, and then the outputs return to the wait status. Each output is switched in turn every 2 seconds by a timer.
2. Continuous operation (X001 = ON) Y001 to Y007 turn ON in turn repeatedly.

FNC280-FNC289 High-Speed Processing 2

3. Stepping operation (X002 = ON) Every time the start button is pressed, each output turns ON in turn.

<List program> <Step ladder>

Enable STL monitoring STL transfer disable

M8000 0 1 3 4 5 7 8 10 11 12 13 15 16 17 20 21 23 24 25 28 29 31 32 33 36 37 39 40 41 44 45 46 48 49 50 52 53

LD OUT LD ANI OUT LD SET STL OUT LD SET STL OUT OUT LD SET STL OUT OUT LD SET STL OUT OUT LD SET STL OUT OUT LD AND OUT LD ANI OUT RET END

M8000 M8047 X002 X000 M8040 M8002 S3 S3 Y000 X000 S20 S20 Y001 T1 K20 T1 S21 S21 Y002 T2 K20 T2 S22 S22 Y003 T3 K20 T3 S27 S27 Y007 T7 K20 T7 X001 S20 T7 X001 S3

M8047

FNC290-FNC299 Extension File Register Control

X002 X000

M8040

M8002 7 SET

STL

FNC300-FNC305 FX 3U -CF-ADP

Y000

X000 12 SET

15 STL

Y001

K20 T1

T1 20 SET

23 STL

Y002

T2

T2 28 SET

K20

31 STL

Y003

T3

K20

T3 36 SET

39 STL

Y007

T7

K20

44 T7 X001

A

48 T7 X001

RET

END

B

Show 19 more labels / short text on this page
RUN monitor · Stepping · Start · Initial state relay · Initial pulse · Wait indication · Start button · Center lamp · SFC•STL Programming · Center fountain · Interrupt Function · Special Device · Loop line lamp · Error Code · Loop line fountain · Continuous · Cyclic/stepping · Version Up Information · Execution Times
Page 800 of the Mitsubishi Electronics MELSEC FX3S user manual — Examples of flows with selective branches and recombination
Page 800 · click to enlarge
Page 800

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.2 Step Ladder

Examples of flows with selective branches and recombination

1. Example of selecting and carrying large and small balls The figure below shows a mechanism which selects and carries large and small balls using conveyors. The upper left position is regarded as the origin, and the mechanism performs in the order "moving down → suction → moving up → moving rightward → moving down → release → moving up → moving leftward". When the arm moves down and the electromagnet pushes a large ball, the lower limit switch LS2 turns OFF. When the electromagnet pushes a small ball, LS2 turns ON.

Mitsubishi Electronics MELSEC FX3S — Examples of flows with selective branches and recombination diagram (page 800)
Fig. 796 · Examples of flows with selective branches and recomb…

When a large ball is pushed, the piston does not reach the lower limit and X002 does not turn ON.

Page 801 of the Mitsubishi Electronics MELSEC FX3S user manual — SET
Page 801 · click to enlarge
Page 801

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.2 Step Ladder 31

The figure below shows a step ladder program for selecting the product size and judging products as either accepted or rejected.

FNC277-FNC279 Data Transfer 3

<Step ladder>

S0 M8002

SET

S30 STL

X001 X003

Y001

Y000

Y007

FNC280-FNC289 High-Speed Processing 2

S31 SET

S0 7 STL

X026 X007

S31 STL

S21 SET

73 RST

Y001

S21 STL

T2

FNC290-FNC299 Extension File Register Control

Y000

K10 T2

S32 SET 77

T0

K20

S32 STL

T0 X002

17 S22 SET

Lower limit (small ball)

Y002 81 X003

T0 X002

FNC300-FNC305 FX 3U -CF-ADP

S25 SET

S33 SET 82

S22 STL

S33 STL

85 X001 86 X001 89

Y001 SET

Y003

Y004

T1

K10

30 T1

SET

RET

33 STL

END

34 SET

Y001

The ON status is transferred to the recombination state relay S30 when X004 turns ON in the case of a small product, or when X005 turns ON in the case of a large product.

T1

K10

When the special auxiliary relay M8040 is driven, all transfers to any state relay are disabled. In each of the state relays S24, S27 and S33, an interlock contact is connected in series respectively to the rightward movement output Y003 and leftward movement output Y004.

38 T1

SET

41 STL

Y002

<List program>

T3

0 1 3 4 5 6 7 8 9 10 12 13 14 17 18 19 21 22 23 25 26 27 30 31 33

LD SET LD AND ANI OUT STL LD AND SET STL OUT OUT LD AND SET LD ANI SET STL SET OUT LD SET STL

M8002 S0 X001 X003 Y001 Y007 S0 X026 Y007 S21 S21 Y000 T0 K20 T0 X002 S22 T0 X002 S25 S22 Y001 T1 K10 T1 S23 S25

34 35 38 39 41 42 43 44 46 47 48 49 51 52 53 54 55 56 57 58 59 60 61 63 64

SET OUT LD SET STL OUT LD SET STL OUT LD SET STL LDI ANI OUT STL LDI ANI OUT STL LD SET STL LD

Y001 T1 K10 T1 S26 S233 Y002 T3 S24 S26 Y002 X003 S27 S24 X004 Y004 Y003 S27 X005 Y004 Y003 S24 X004 S30 S27 X005

65 67 68 69 70 72 73 74 77 78 80 81 82 83 85 86 87 88 89 90 92 93

SET STL OUT LD SET STL RST OUT LD SET STL OUT LD SET STL LDI ANI OUT LD OUT RET END

S30 S30 Y000 X002 S31 S31 Y001 T2 K10 T2 S32 S32 Y002 X003 S33 S33 X001 Y003 Y004 X001 S0

SET

STL

Y002

SET

STL

Y004

Y003

STL

A

Y004

Y003

S24 STL

S30 SET

S27 STL

B

S30 SET

Show 27 more labels / short text on this page
Initial pulse · Moving down · Origin indication · Left limit · Upper · Release · limit · Start · Origin · Release · Moving down · Moving up · Suction · Moving leftward · SFC•STL Programming · Suction · · Interrupt Function · · Moving up · Special Device · Moving up · Error Code · Moving rightward · Moving rightward · Version Up Information · Execution Times
Page 802 of the Mitsubishi Electronics MELSEC FX3S user manual — Example of flows with parallel branches and recombination
Page 802 · click to enlarge
Page 802

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.2 Step Ladder

Example of flows with parallel branches and recombination

When the parts A, B and C are processed in parallel and then assembled, flows having parallel branches and recombination are used.

1. Example of pushbutton type crosswalk A pushbutton type crosswalk shown in the figure below can be expressed in flows having parallel branches and recombination. Y003: Green Y002: Yellow Y001: Red
  • The SFC program for a pushbutton type crosswalk is as shown below. In this example, a partial flow (jump to a state relay located in an upper position) is repeated for blinking the green lamp on the crosswalk.
  • When the PLC mode is changed from STOP to RUN, the initial state relay S0 turns ON. Normally, the green lamp is ON for the road and the red lamp is ON for the sidewalk.
  • When the crossing button X000 or X001 is pressed, the state relay S21 specifies “road: green” and the state relay S30 specifies “sidewalk: red”. The signal lamp status is not changed.
  • Thirty seconds later, the yellow lamp turns ON for the road. Ten seconds later after that, the red lamp turns ON for the road.
  • When the timer T2 (5 seconds) reaches timeout after that, the green lamp turns ON for the sidewalk.
  • Fifteen seconds later, the green lamp starts to blink for the sidewalk. (S32 turns OFF the green lamp, and S33 turns ON the green lamp.)
  • While the green lamp is blinking, S32 and S33 turn ON and OFF repeatedly. When the counter C0 (set value: 5) turns ON, S34 turns ON. Five seconds after the red lamp turns ON for the sidewalk, the signal lamps return to the initial state.
  • Even if the crossing button X000 or X001 is pressed in the middle of operation, the pressing is ignored.
Page 803 of the Mitsubishi Electronics MELSEC FX3S user manual — K5
Page 803 · click to enlarge
Page 803

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

35 SFC Program and Step Ladder

35.2 Step Ladder 31

FNC277-FNC279 Data Transfer 3

<Step ladder>

M8002

61 C0 T5

SET

S34 SET

C0 T5

S0 STL

Y003

RoadGreen

S34 STL

FNC280-FNC289 High-Speed Processing 2

SidewalkRed
SidewalkRed

Y005

Y005

S21 SET

C0 RST

S30 SET

T6

K50

FNC290-FNC299 Extension File Register Control

S21 STL

S23 STL

RoadGreen

Y003

S34 STL

T0

78 T6

K300

17 T0

S22 SET

RET

FNC300-FNC305 FX 3U -CF-ADP

S30 STL

END

SidewalkRed

21 T2

Y005

S31 SET

S22 STL

RoadYellow

<List program>

Y002

0 1 3 4 5 6 7 8 10 12 13 14 17 18 20 21 22 23 25

LD SET STL OUT OUT LD OR SET SET STL OUT OUT LD SET STL OUT LD SET STL

M8002 S0 S0 Y003 Y005 X000 X001 S21 S30 S21 Y003 T0 K300 T0 S22 S30 Y005 T2 S31 S22

26 27 30 31 33 34 35 38 39 41 42 43 46 47 50 51 53 54 55

OUT OUT LD SET STL OUT OUT LD SET STL OUT OUT STL OUT LD SET STL OUT OUT

Y002 T1 K100 T1 S23 S31 Y006 T3 K150 T3 S32 S23 Y001 T2 K50 S32 T4 K5 T4 S33 S33 Y006 C0 K5

58 61 62 63 65 66 67 69 70 71 73 76 77 78 79 81 82

OUT LD AND SET LDI AND OUT STL OUT RST OUT STL STL LD OUT RET END

T5 K5 C0 T5 S34 C0 T5 S32 S34 Y005 C0 T6 K50 S23 S34 T6 S0

T1

K100

30 T1

S23 SET

S31 STL

Y006

SidewalkGreen

T3

K150

38 T3

S32 SET

S23 STL

RoadRed

Y001

K50 T2

S32 STL

K5 T4

T4 50

S33 SET

A

S33 STL

Y006

This counter counts how many times the state relay S33 turns ON. When S33 turns ON five times, the contact C0 turns ON.

K5

T5

B

K5

Show 8 more labels / short text on this page
Initial pulse · Crossing button · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 804 of the Mitsubishi Electronics MELSEC FX3S user manual — 5. Pulse catch function *1
Page 804 · click to enlarge
Page 804

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.1 Outline

36. Interrupt Function and Pulse Catch Function

This chapter explains the built-in interrupt function and pulse catch function in FX PLC.

36.1 Outline

This section explains the function to immediately execute an interrupt program (interrupt routine) without affecting the operation cycle of the sequence program (main) while using a interrupt function as a trigger. The delay by operation cycle and machine operation affected by uneven time intervals in normal sequence program process can be improved.

1. Input interrupt function (interrupt of external signal input (X)) *1

By the input signal from an input (X000 to X005), the main sequence program is paused, and an interrupt routine program is executed with priority. The input interrupt execution timing can be specified on the rising edge or falling edge of the signal by the pointer number.

→ For details, refer to Section 36.3.

2. Input interrupt delay function (interrupt of external signal input (X)) *1

By the input signal from an input (X000 to X005), the main sequence program is paused, and an interrupt routine program is executed with priority after the delay time (set in units of 1 ms). The input interrupt execution timing can be specified on the rising edge or falling edge of the signal by the pointer number.

→ For details, refer to Section 36.4.

3. Timer interrupt function (timer interrupt activated in a constant cycle) The main sequence program is paused in a constant cycle of 10 to 99 ms, and an interrupt routine program is executed with priority.

→ For details, refer to Section 36.5.

4. High-speed counter interrupt function (interrupt function given at counting up) *1

When the current value of a high-speed counter reaches a specified value, the main sequence program is paused and an interrupt routine program is executed with priority.

→ For details, refer to Section 36.6.

5. Pulse catch function *1

When the input signal from an input (X000 to X007) turns from OFF to ON, a special auxiliary relay M8170 to M8177 is immediately set to ON by interrupt processing. Relays M8170 to M8177 are used in a normal sequence program. A relay remains ON after its input signal turns OFF, so a short pulse can be easily received. When processing such a signal that turns ON and OFF several times in one operation cycle, however, use the input interrupt function.

→ For details, refer to Section 36.7.

6. Pulse width/Pulse period measurement function When the input signal from an input (X000, X001, X003 or X004) turns from OFF to ON, the value of the 1/6 µs ring counter at the input signal rising edge is stored in special data registers. When the input signal turns OFF from ON, the value of the 1/6 µs ring counter at the input signal falling edge is stored in special data registers. At the same time, the difference in the counter value between the rising edge and the falling edge is divided by "60", and the pulse width in units of 10 µs is stored in special data registers. In the pulse period measurement mode, when the input signal turns from OFF to ON, the difference between the previous rising of the input signal and the current rising of the input signal is divided by "60", and then the pulse period in units of 10 µs is stored in special data registers.

→ For details, refer to Section 36.8.

*1. This function is supported only in DC input type.

Page 805 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 805 · click to enlarge
Page 805

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.2 Common Items 31

36.2 Common Items

FNC277-FNC279 Data Transfer 3

36.2.1 How to disable interrupt function

This section describes how to disable the interrupt function.

FNC280-FNC289 High-Speed Processing 2

1. Limiting the program interrupt range [interrupt function]

1. Programming method Program the FNC 05 (DI) instruction to set the interrupt disabled zone. Even if an interrupt is generated between the DI instruction and EI instruction (interrupt disabled zone), the interrupt is executed after the EI instruction.
2. Program example

FNC290-FNC299 Extension File Register Control

EI

FNC300-FNC305 FX 3U -CF-ADP

DI

FEND

3. Cautions a) The interrupt inputs with special auxiliary relay for interrupt disable (M8050 to M8059) turned ON are

excluded. b) When the disabled zone is long, interrupts are accepted, but the interrupt processing is started after

considerable time. When the interrupt disabling setting is not required, program only EI instruction. It is not always necessary to program DI instruction.

2. Disabling interrupt pointers (for each interrupt routine) [interrupt function]

1. Programming method The special auxiliary relays M8050 to M8059 for disabling interrupt are provided. While an interrupt disable flag (M8050 to M8059) is ON, a corresponding interrupt program is not executed even if the interrupt disable flag is set to OFF after a corresponding interrupt is generated.

Input interrupt The input interrupts X000 to X005 correspond to M8050 to M8055*1 respectively. When a relay M8050 to M8055 turns ON, a corresponding input interrupt is disabled.

Timer interrupt The timer interrupts I6 to I8 correspond to M8056 to M8058*1 respectively. When a relay M8056 to M8058 turns ON, a corresponding timer interrupt is disabled.

A

High-speed counter interrupt When M8059*1 turns ON, all of the high-speed counter interrupts I010 to I060 are disabled.

*1. Cleared when the PLC mode is changed from RUN to STOP.

B

Show 8 more labels / short text on this page
Interrupts are enabled · Interrupts are disabled · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 806 of the Mitsubishi Electronics MELSEC FX3S user manual — 36.2.3 Cautions on use (common)
Page 806 · click to enlarge
Page 806

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.2 Common Items

2. Program example In the program example shown below, when M8053 is set to ON by M20, the interrupt input I301 triggered by X003 is disabled.

EI

M20

M8053

Command to disable an interrupt triggered by X003

FEND

When the rising edge of X003 is detected

IRET

END

36.2.2 Related items

1. Using the I/O refresh function (REF instruction) When controlling an input relay or output relay in an interrupt program, the I/O refresh instruction REF (FNC 50) can be used to acquire the latest input information and immediately output the operation result. As a result, high-speed control is achieved without being affected by the operation cycle of the PLC.
2. Interrupt operation while FROM/TO instruction is executed The interrupt operation is executed as follows depending on the ON/OFF status of the special auxiliary relay M8028.
1. While M8028 is OFF While FROM/TO instructions are being executed, interrupts are automatically disabled. Input interrupts and timer interrupts are not executed. Interrupts generated during this period are immediately executed when the execution of FROM/TO instructions are completed. FROM/TO instruction can be used in an interrupt program when M8028 is OFF.
2. While M8028 is ON When an interrupt is generated while a FROM/TO instruction is being executed, execution of the FROM/TO instruction is paused and the interrupt is immediately executed. FROM/TO instructions cannot be used in an interrupt routine program when M8028 is ON.

36.2.3 Cautions on use (common)

This section explains common cautions on using the interrupt function or pulse catch function. Specific cautions on each interrupt function are explained in the description of each interrupt function.

1. Processing when many interrupts are generated When many interrupts are generated in turn, priority is given to the first one. When many interrupts are generated at the same time, priority is given to the one having the smallest pointer number. While an interrupt routine is being executed, other interrupts are disabled.
2. When double interrupt (interrupt during another interrupt) is required [interrupt function] Usually, interrupts are disabled in an interrupt routine (program). When the EI (FNC 04) and DI (FNC 05) instructions are programmed in an interrupt routine in FX 3U /FX 3UC PLCs, up to two interrupts can be accepted. Double interrupts are not available in FX 3S /FX 3G /FX 3GC PLCs.
Show 4 more labels / short text on this page
Interrupts are enabled · Interrupt · pointer · Interrupt routine
Page 807 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 807 · click to enlarge
Page 807

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.2 Common Items 31

3. Operation when a timer is used [interrupt function] Make sure that counting using a general timer is disabled, even a 1ms retentive type timer. In an interrupt routine, use timers for subroutine program T192 to T199. FX 3S PLCs are not equipped with timers for subroutine program.

FNC277-FNC279 Data Transfer 3

4. Non-overlap of input [input interrupt (with/without delay function) and pulse catch function] The inputs X000 to X007 can be used for high-speed counters, input interrupts, pulse catch, SPD, ZRN, DSZR and DVIT instructions and for general-purpose inputs. Make sure inputs do not overlap with each other. When using SFC program (STL instruction), do not drive state relays S in a SET or OUT instruction in an interrupt program.

FNC280-FNC289 High-Speed Processing 2

5. When using SFC program (STL instruction) When using SFC programs (STL instruction), do not drive state relays S using SET or OUT instructions in an interrupt program.

FNC290-FNC299 Extension File Register Control

6. Operation of devices latched in the ON status [interrupt function] Devices which were set to ON in an interrupt routine are held in the ON status even after the interrupt routine is finished. When the RST instruction for a timer or counter is executed, the reset status of the timer or counter is also held. To turn OFF a device held in the ON status or for canceling such a timer or counter held in the reset status, reset such a device or deactivate the RST instruction respectively inside or outside the routine.

FNC300-FNC305 FX 3U -CF-ADP

Example in which outputs are latched

In the program example shown below, the counter C0 is provided to count X001. When X001 turns from OFF to ON, the interrupt program I001 is executed only in one scan, and then the counter C0 is reset and Y007 is output.

1. Program example

EI

K10

FEND

M8000

RST C0

Y007

IRET

2. Timing chart

Execution of interrupt program I001 triggered by X000

Because the C0 reset instruction is valid, the current value of C0 remains unchanged even if a pulses are input.

Current value of C0 1 2 3 Counter is reset

A

RST C0

Y007

Y007 is being output

B

Outputs are latched.

Show 9 more labels / short text on this page
Step 0 · SFC•STL Programming · Interrupt Function · Special Device · Interrupt program · Error Code · Version Up Information · C0 remains reset · Execution Times
Page 808 of the Mitsubishi Electronics MELSEC FX3S user manual — Example in which latched outputs are reset (countermeasures)
Page 808 · click to enlarge
Page 808

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.2 Common Items

Example in which latched outputs are reset (countermeasures)

1. Program example
Mitsubishi Electronics MELSEC FX3S — Example in which latched outputs are reset (countermeasures) diagram (page 808)
Fig. 797 · Example in which latched outputs are reset (counterm…

RST Y007 Program to reset Y007 at an arbitrary time.

Program to deactivate the preceding C0 reset instruction inside the subroutine.

2. Timing chart
Mitsubishi Electronics MELSEC FX3S — Example in which latched outputs are reset (countermeasures) diagram (page 808)
Fig. 798 · Example in which latched outputs are reset (counterm…

Counter reset instruction is deactivated (part B in above program).

Page 809 of the Mitsubishi Electronics MELSEC FX3S user manual — X000 I001 I000 M8050 *1
Page 809 · click to enlarge
Page 809

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.3 Input Interrupt (Interrupt Triggered by External Signal) [Without Delay Function] 31

36.3 Input Interrupt (Interrupt Triggered by External Signal) [Without Delay Function]

FNC277-FNC279 Data Transfer 3

36.3.1 Input interrupt (interrupt triggered by external signal) [without delay function]

FNC280-FNC289 High-Speed Processing 2

1. Outline An interrupt routine is executed by the input signal from an input X000 to X005.
2. Application Because the external input signal can be processed without being affected by the operation cycle of the PLC, this interrupt is suitable to high-speed control and receiving of short pulses.

3. Basic program (programming procedure)

FNC290-FNC299 Extension File Register Control

Main program Interrupt inputs are accepted after EI instruction. It is not necessary to program DI (disable interrupt) instruction if there is no zone where input interrupts should be disabled.

Interrupts are enabled FNC 04

EI

FNC300-FNC305 FX 3U -CF-ADP

End of main program

FEND instruction finishes the main program. Make sure to describe an interrupt routine after FEND instruction.

FEND

pointer When the rising edge of X000 is detected

When X000 turns ON, its rising edge is detected, and the interrupt routine [1] is executed. IRET instruction returns the program execution to the main program.

Interrupt routine [1] (interrupt program)

IRET

pointer When the falling edge of X001 is detected

When X001 turns OFF, its falling edge is detected, and the interrupt routine [2] is executed. IRET instruction returns the program execution to the main program.

Interrupt routine [2] (interrupt program)

IRET

"END" indicates the end of program.

END

4. Number and operation of (six) interrupt pointers

0. Interrupt at falling edge, 1: Interrupt at rising edge

0 to 5 according to the inputs X000 to X005

A

Interrupt disable command Interrupt at rising edge Interrupt at falling edge

X000 I001 I000 M8050 *1

X001 I101 I100 M8051 *1

X002 I201 I200 M8052 *1

X003 I301 I300 M8053 *1

B

X004 I401 I400 M8054 *1

X005 I501 I500 M8055 *1

*1. Cleared when the PLC mode is changed from RUN to STOP.

Show 14 more labels / short text on this page
Step · Main program · Interrupt · SFC•STL Programming · Interrupt return · Interrupt Function · Interrupt · Special Device · Interrupt return · Error Code · Pointer number · Input number · Version Up Information · Execution Times
Page 810 of the Mitsubishi Electronics MELSEC FX3S user manual — END
Page 810 · click to enlarge
Page 810

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.3 Input Interrupt (Interrupt Triggered by External Signal) [Without Delay Function]

5. How to disable each interrupt input When any among M8050 to M8055 is set to ON in a program, interrupts from the corresponding input number are disabled. (Refer to the previous page table for the correspondence.)

6. Cautions

1. Do not use an input two or more times Make sure that an input relay number used as an interrupt pointer is not used in high-speed counters, pulse catch functions and applied instructions such as the SPD (FNC 56) speed detection instruction which use the same input range.
2. Automatic adjustment of the input filter When an input interrupt pointer I 0 is specified, the input filter of the input relay is automatically changed to the input filter for high-speed receiving. Accordingly, it is not necessary to change the filter value using the REFF (FNC 51) instruction or special data register D8020 (input filter adjustment). The input filter of an input relay not being used as an input interrupt pointer operates at 10 ms (initial value).
3. Pulse width of input interrupt For executing input interrupt by an external signal, it is necessary to input the ON or OFF signal having the duration shown in the table below or more.

PLC Input number Input filter value when "0" is set

X000,X001 10 µs

FX 3S

X002,X003,X004,X005 50 µs

X000,X001,X003,X004 10 µs

FX 3G , FX 3GC

X002,X005 50 µs

FX3U, FX3UC X000 to X005 5 µs*1

*1. When using the input filter at the filter value of 5 µs or when receiving a pulse whose response frequency is 50 k to 100 kHz using a high-speed counter, perform the following: - Make sure that the wiring length is 5 m or less. - Connect a bleeder resistor of 1.5 kΩ (1 W or more) to an input terminal, and make sure that the load

current of the open collector transistor output in the counterpart equipment is 20 mA or more including the input current in the main unit.

4. Using a pointer number two or more times It is not possible to program an interrupt at the rising edge and an interrupt at the falling edge for an input such as I001 or I000.

7. Program examples

1. When using both an external input interrupt at the rising edge and the output refresh (REF instruction) In the program example shown below, the output Y000 immediately turns ON when the rising edge of the external input X000 is detected.

Interrupts are enabled by the EI instruction. The main program is described.

EI

The main program is finished by the FEND instruction.

FEND

When the rising edge of X000 is detected M8000

When an interrupt routine is executed by turning ON of X000, Y000 is set to ON unconditionally.

SET Y000

Y000 K8 *2 FNC 50

The outputs Y000 to Y007 are overwritten with the latest information by the output refresh instruction. If the output refresh instruction is not provided, Y000 turns ON after the END instruction after the program execution returned to the main routine.

REF

IRET

If "SET Y000" is changed to "RST Y000", Y000 is immediately set to OFF by turning ON of X000.

END

*2. Make sure to specify a multiple of "8" for the number of inputs/outputs to be refreshed by the REF (FNC 50) instruction. If any value other than a multiple of "8" is specified, an operation error occurs and the REF (FNC 50) instruction is not executed.

Show 4 more labels / short text on this page
Step · Interrupt · pointer · RUN monitor
Page 811 of the Mitsubishi Electronics MELSEC FX3S user manual — INC
Page 811 · click to enlarge
Page 811

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.3 Input Interrupt (Interrupt Triggered by External Signal) [Without Delay Function] 31

2. When using both an input interrupt and the input refresh (REF instruction) In the program example shown below, an interrupt is processed using the latest input information.

FNC277-FNC279 Data Transfer 3

Interrupts are enabled by EI instruction. The main program is described.

EI

FNC280-FNC289 High-Speed Processing 2

The main program is finished by FEND instruction.

FEND

When the rising edge of X001 is detected M8000

K8 *1 X010 FNC 50

When an interrupt routine is executed by turning X001 to ON, the input refresh is executed unconditionally, and the ON/OFF information of X010 to X017 at the current time is received.

REF

Y001 SET

FNC290-FNC299 Extension File Register Control

Y001 is set to ON or OFF according to the ON/ OFF status of X010.

Y001 RST

IRET

FNC300-FNC305 FX 3U -CF-ADP

END

*1. Make sure to specify a multiple of "8" as the number of inputs/outputs to be refreshed by REF (FNC 50) instruction. If any value other than a multiple of "8" is specified, an operation error occurs and REF (FNC 50) instruction is not executed.

3. When counting the number of times of input generation (in the same way as 1-phase high-speed counter) In the program example shown below, external inputs are counted.

Interrupts are enabled by EI instruction. The main program is described.

EI

The main program is finished by FEND instruction.

FEND

pointer When the rising edge of X002 is detected

M8000

D0 FNC 24

When X002 turns ON, "1" is added to the value of D0. INC instruction executes increment in every operation cycle, but the interrupt routine is executed only once by an input signal. Accordingly, it is not necessary to use INCP (pulse operation type) instruction.

INC

IRET

END

A

B

Show 13 more labels / short text on this page
Step · Interrupt · pointer · RUN monitor · SFC•STL Programming · Step · Interrupt Function · Interrupt · RUN monitor · Special Device · Error Code · Version Up Information · Execution Times
Page 812 of the Mitsubishi Electronics MELSEC FX3S user manual — IRET
Page 812 · click to enlarge
Page 812

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.3 Input Interrupt (Interrupt Triggered by External Signal) [Without Delay Function]

4. When catching a short pulse In the program example shown below, the ON status is held for a certain period of time after a short pulse turns ON.

M0 ON ON

T0 T0

Interrupts are enabled by EI instruction.

EI

M0

The ON/OFF signal in M0 is utilized in this program.

M0

T0

K10

The period of time to hold M0 is specified.

T0

RST M0

After the timer time, M0 is reset.

The main program is finished by FEND instruction.

FEND

pointer When the rising edge of X003 is detected

M8000

SET M0

When X003 turns ON and the interrupt routine is executed, M0 is set to ON unconditionally.

IRET

END

Show 4 more labels / short text on this page
Pulse input X003 · Step · Interrupt · RUN monitor
Page 813 of the Mitsubishi Electronics MELSEC FX3S user manual — M8000
Page 813 · click to enlarge
Page 813

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.3 Input Interrupt (Interrupt Triggered by External Signal) [Without Delay Function] 31

36.3.2 Examples of practical programs (programs to measure short pulse width)

FNC277-FNC279 Data Transfer 3

By using a 1 ms retentive type timer or the special data register D8099 (high-speed ring counter), the short pulse width can be measured in 1 ms or 0.1 ms units.

1. Example of program to measure the short pulse width using a retentive type 1ms timer

X010:Preparation for measurement

FNC280-FNC289 High-Speed Processing 2

SW

SW(X000,X001)

0V S/S X000 X001

ex:FX3U PLC(sink input)

This period of time is measured.

Interrupts are enabled by the EI instruction. The main program is described.

FNC290-FNC299 Extension File Register Control

EI

The main program is finished by the FEND instruction.

When the rising edge of X000 is detected

FEND

FNC300-FNC305 FX 3U -CF-ADP

M8000

The reset status is cleared

When X000 turns ON, the 1 ms timer T246 is started up by the interrupt I001.

RST T246

A

RST M0

RST D0

T246

K32767

IRET

When the falling edge of X001 is detected

When X001 turns OFF, the current value of T246 is transferred to the data register D0 for storing the measured value by the interrupt I100, and M0 for the complete signal is set to ON.

T246 D0

M0V

SET M0

M0

T246

K1

"T246" is set to OFF, and the timer is stopped.

M8000

RST T246

B

IRET

END

A

B

Show 16 more labels / short text on this page
Step · Interrupt · pointer · SFC•STL Programming · Timer is driven · Measurement data · Interrupt Function · Interrupt · pointer · Measurement is completed · Special Device · Timer is stopped · Timer is reset · Error Code · Version Up Information · Execution Times
Page 814 of the Mitsubishi Electronics MELSEC FX3S user manual — 36.3.2 Examples of practical programs (programs to measure short pulse width)
Page 814 · click to enlarge
Page 814

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.3 Input Interrupt (Interrupt Triggered by External Signal) [Without Delay Function]

Mitsubishi Electronics MELSEC FX3S — 36.3.2 Examples of practical programs (programs to measure short pulse width) diagram (page 814)
Fig. 799 · 36.3.2 Examples of practical programs (programs to m…
2. Example of program to measure the short pulse width using a high-speed ring counter (only in FX 3U /FX 3UC PLCs)
Mitsubishi Electronics MELSEC FX3S — 36.3.2 Examples of practical programs (programs to measure short pulse width) diagram (page 814)
Fig. 800 · 36.3.2 Examples of practical programs (programs to m…

Interrupts are enabled by the EI instruction. The main program is described.

When X000 turns ONThe ring counter is reset

The special data register M8099 up-counts the 0.1 ms clock from the next operation cycle after being driven. When the count value exceeds "32767", it is returned to "0".

Page 815 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 815 · click to enlarge
Page 815

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.4 Input interrupt (Interrupt by External Signal) [With Delay Function] 31

36.4 Input interrupt (Interrupt by External Signal) [With Delay Function]

FNC277-FNC279 Data Transfer 3

1. Outline An input interrupt has the function to delay execution of an interrupt routine in units of 1 ms. The delay time can be specified using the pattern program shown below. By using the delay function, the mounting position of a sensor used for input interrupts can be adjusted electrically without changing the actual position.

FNC280-FNC289 High-Speed Processing 2

2. Programming procedure

Contact for setting delay time

M8393 FNC 12

FNC290-FNC299 Extension File Register Control

MOV K* Delay time specification program Make sure to describe the delay time specification program shown on the left at the head of an interrupt routine program. Do not add, change, or delete this routine program when writing during RUN. Interrupt programs may not operate normally. Because this program is a pattern program, change only the delay time ([1]). Only a constant (K) or data register (D) is available for specifying the time here*. If any other device or constant is used, the delay time setting becomes invalid and the interrupt functions as a normal input interrupt. If the contents of the set data register (D) are "0", the delay time is regarded as "0".

[1] Delay time (unitms)

FNC300-FNC305 FX 3U -CF-ADP

Program to be executed as input interrupt

End of interrupt program. •

IRET

3. Timing chart

Because the previous interrupt processing is not completed, the interrupt processing is not executed here.

Interrupt input (X000 to X005)

Interrupt program is executed

36.5 Timer Interrupt (Interrupt in Constant Cycle)

36.5.1 Timer interrupt (interrupt in constant cycle)

1. Outline An interrupt routine is executed at every 10 to 99 ms without being affected by the operation cycle of a PLC.

A

2. Application This type of interrupt is suitable when a certain program should be executed at high-speed while the main program operation time is long or when a program should be executed at a constant time interval in sequence operations.

B

Show 11 more labels / short text on this page
• · SFC•STL Programming · Interrupt Function · Valid · Delay time · IRET instruction · (msec) · Special Device · Error Code · Version Up Information · Execution Times
Page 816 of the Mitsubishi Electronics MELSEC FX3S user manual — 5. Cautions
Page 816 · click to enlarge
Page 816

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.5 Timer Interrupt (Interrupt in Constant Cycle)

3. Basic program (programming procedure)

Timer interrupts are enabled after the EI instruction. It is not necessary to program DI (disable interrupt) if there is no zone where input interrupts should be disabled.

EI

End of main program

The FEND instruction indicates the end of the main program. Make sure to describe an interrupt routine after the FEND instruction.

FEND

When interrupt is given at every 20 ms

The interrupt routine is executed at every 20 ms. Create a program to be executed as interrupt. The IRET instruction returns the program execution to the main program.

IRET

END

4. Number and operation of (three) timer interrupt pointers

I

Timer time10 to 99 (ms)

Timer interrupt pointer (6, 7 or 8)

An interrupt routine program is executed at every specified interrupt cycle time (10 to 99 ms). Use the type of interrupt in control requiring cyclic interrupt processing regardless of the operating cycle of a PLC.

Input number Interrupt cycle (ms) Interrupt disable Flag

M8056 *1

An integer ranging from 10 to 99 is put in " " in the pointer name. Example: "I610" indicates a timer interrupt at every 10 ms.

I7 M8057 *1

I8 M8058 *1

*1. Cleared when the PLC mode is changed from RUN to STOP.

Caution

If the timer interrupt time is set to 9ms or less, the timer interrupt processing may not be executed in an accurate cycle in the following cases. Therefore, using a time that is over 10 ms is recommended.

  • When the interrupt program processing time is long
  • When the main program contains an applied instruction which processing time is long

5. Cautions

  • Each pointer number (I6, I7 or I8) can only be used once.
  • When M8056 to M8058 is set to ON in a program, a corresponding timer interrupt is disabled.
Show 9 more labels / short text on this page
Main program · Step · Interrupts are enabled · Main program · Interrupt · Interrupt subroutine · pointer · Interrupt routine · Interrupt return
Page 817 of the Mitsubishi Electronics MELSEC FX3S user manual — Y000 K8
Page 817 · click to enlarge
Page 817

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.5 Timer Interrupt (Interrupt in Constant Cycle) 31

6. Program example → For program examples in which RAMP (FNC 67) or HKY (FNC 71) instructions are combined,

FNC277-FNC279 Data Transfer 3

refer to Subsection 36.5.2. In the program example shown below, data is added and the addition result is compared with the set value every 10 ms.

1. Program example

Interrupts are enabled by EI instruction. The main program is described.

FNC280-FNC289 High-Speed Processing 2

EI

SET M3

When M3 is set to ON, INC (FNC 24) instruction becomes valid.

The main program is finished by FEND instruction.

FEND

When interrupt is given at every 10 ms M3

FNC290-FNC299 Extension File Register Control

"1" is added to the current value of D0 at every 10 ms.

INC

When the current value of D0 reaches "1000", M3 is reset.

K1000 D0 RST M3

LD=

The current value of D0 is ramp data which changes from "0" to "1000" in 10 seconds. In the program example using RAMP (FNC 67) instruction shown later, the ramp data is made using a dedicated applied instruction.

FNC300-FNC305 FX 3U -CF-ADP

IRET

END

36.5.2 Examples of practical program (timer interrupt programs using applied instruction)

RAMP (FNC 67), HKY (FNC 71), SEGL (FNC 74), ARWS (FNC 75) and PR (FNC 77) instructions execute a series of operations in synchronization with the scan time. Because the total time may be too long or time fluctuation may cause a problem in these instructions, it is recommended to execute these instructions at a constant time interval using the timer interrupt function. When not using the timer interrupt function, use the constant scan mode.

1. Timer interrupt processing of HKY (FNC 71) instruction → For HKY (FNC 71) instruction, refer to Section 15.2.

Interrupts are enabled by EI instruction. The main program is described.

EI

The main program is finished by FEND instruction.

FEND

pointer When interrupt is given every 20 ms M8000

The latest input information is received from X000 to X007.

K8 X000

REF

X000 Y000 D0 M0

HKY (FNC 71) is executed in one scan.

HKY

A

Y000 to Y007 are refreshed to the latest output information.

Y000 K8

REF

IRET

B

END

Show 12 more labels / short text on this page
Step · Interrupt · pointer · SFC•STL Programming · Interrupt Function · Step · Special Device · Interrupt · Error Code · RUN monitor · Version Up Information · Execution Times
Page 818 of the Mitsubishi Electronics MELSEC FX3S user manual — RST
Page 818 · click to enlarge
Page 818

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.5 Timer Interrupt (Interrupt in Constant Cycle)

2. Timer interrupt processing of RAMP (FNC 67) instruction The ramp signal output circuit shown below is programmed using the timer interrupt function executed every 10 ms.

→ For the use method of the instruction execution complete flag M8029, refer to Subsection 6.5.2.

→ For RAMP (FNC 67) instruction, refer to Section 14.8.

1. Ramp output pattern D4 is occupied as a register for counting the number of times of execution.
Mitsubishi Electronics MELSEC FX3S — 36.5.2 Examples of practical program (timer interrupt programs using applied instruction) diagram (page 818)
Fig. 801 · 36.5.2 Examples of practical program (timer interrup…
2. Program

Interrupts are enabled by EI instruction. The main program is described.

FNC 04 EI

With M8026 turned ON, when the value of (D3) reaches the final value (D2), the final value is latched.

M8026

As soon as the start command is given, the initial value (D1) and target value (D2) are transferred.

MOV K 1 D 1

MOV K255 D 2

PLS M 0

M 0

SET M 1

The main program is finished by FEND instruction.

FEND

When interrupt is given every 10 ms

M 1 FNC 67

While the instruction is executed 1000 times (in 10 seconds), the contents of D3 are changed from the value of D1 to the value of D2.

RAMP D 1 D 2 D 3 K1000

M 1 M8029

When the instruction execution complete flag M8029 turns ON, RAMP instruction drive input is set to OFF. If RAMP (FNC 67) instruction is continuously executed while M8026 is OFF, the value of D3 returns to the initial value (D1) immediately after it reaches the final value (D2), and then the same operation is repeated. This program is not necessary when M8026 is ON.

RST

IRET

END

Show 11 more labels / short text on this page
Step · Start · Interrupt · pointer · Initial value · Target · Current · Number of · value · value · times of transfer
Page 819 of the Mitsubishi Electronics MELSEC FX3S user manual — FEND
Page 819 · click to enlarge
Page 819

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.5 Timer Interrupt (Interrupt in Constant Cycle) 31

3. Cautions

FNC277-FNC279 Data Transfer 3

1. When the HKY (FNC 71), SEGL (FNC 74) or PR (FNC 77) instruction is used in an interrupt program, the instruction turns ON M8029 in the interrupt program. When M8029 is referred to in the main program as shown below, M8029 may be changed by an interrupt program depending on the interrupt timing, even if M8029 is referred to immediately after an instruction. As a result, whether the instruction is executed completely cannot be determined properly.

program example

FNC280-FNC289 High-Speed Processing 2

EI

M100 FNC270

IVCK K6 H6F D100 K1

Instruction to use M8029 in the main program

When an interrupt occurs at this timing, whether the instruction is executed completely cannot be determined properly.

M100 M8029

FNC290-FNC299 Extension File Register Control

RST

FEND

Interrupt at every 20 ms

M8000

REF X000 K8

FNC300-FNC305 FX 3U -CF-ADP

X000 Y000

D0 M0

HKY

K8 FNC 50

REF

Y000

IRET

END

2. Countermeasures Disable interrupts using the DI instruction in the section from the instruction which uses M8029 in the main program to the point after M8029 is referred to.

Countermeasures program example

EI

DI

M100 FNC270

Instruction to use M8029 in the main program

IVCK K6 H6F D100 K1

M100 M8029

RST

EI

Interrupt at every 20 ms

FEND

M8000

REF X000 K8

A

HKY

X000 Y000

D0 M0

K8 FNC 50

Y000

REF

IRET

B

END

Show 12 more labels / short text on this page
Interrupt · pointer · RUN monitor · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Interrupt · pointer · RUN monitor · Version Up Information · Execution Times
Page 820 of the Mitsubishi Electronics MELSEC FX3S user manual — 6. Cautions
Page 820 · click to enlarge
Page 820

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.6 Counter Interrupt - Interrupt Triggered by Counting Up of High-Speed Counter

36.6 Counter Interrupt - Interrupt Triggered by Counting Up of High-Speed Counter

1. Outline This type of interrupt utilizes the current value of a high-speed counter.
2. Application This type of interrupt is used together with the comparison set instruction DHSCS (FNC 53). When the current value of a high-speed counter reaches the specified value, an interrupt routine is executed.

3. Basic program (programming procedure)

Mitsubishi Electronics MELSEC FX3S — 3. Basic program (programming procedure) diagram (page 820)
Fig. 802 · 3. Basic program (programming procedure)

Main program Interrupts are enabled after EI (FNC 04) instruction. The main program is described.

The coil of a high-speed counter is driven, and an interrupt pointer is specified in DHSCS (FNC 53) instruction.

When the current value of C255 changes from "999" to "1000", the interrupt routine is executed. For an interrupt routine use example, refer to the input interrupt function described in the preceding section.

*1. When the comparison value specified by a data register, etc. is changed, the current value is actually changed to the specified value when END instruction is executed.

4. Number and operation of (six) counter interrupt pointers

Counter interrupt pointer (1 to 6)

Pointer No. Interrupt disable flag

I010,I020,I030,I040,I050,I060 M8059 *2

*2. Cleared when the PLC mode is changed from RUN to STOP.

5. When setting an interrupt output (Y or M) to ON or OFF using a high-speed counter When only controlling the ON/OFF status of an output relay (Y) or auxiliary relay (M) according to the current value of a high-speed counter, a required program can be easily created using DHSCS (FNC 53), DHSCR (FNC 54) or DHSZ (FNC 55) instruction.

6. Cautions

1. Pointer number Pointer numbers cannot overlap with each other.
2. Disabling interrupts When the special auxiliary relay M8059 is set to ON in a program, all counter interrupts are disabled.
Page 821 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 821 · click to enlarge
Page 821

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.7 Pulse Catch Function [M8170 to M8177] 31

36.7 Pulse Catch Function [M8170 to M8177]

FNC277-FNC279 Data Transfer 3

If the EI instruction is anywhere in the sequence program, the pulse catch function is always enabled. When an input relay X000 to X007 turns from OFF to ON, a special auxiliary relay M8170 to M8177 is immediately set to ON by interrupt processing. The EI (FNC 04) instruction is not required in FX3S/FX3G/FX3GC PLCs.

1. Assignment of input numbers and special auxiliary relays

FNC280-FNC289 High-Speed Processing 2

Pulse catch input Pulse catch relay

X000 M8170 *1

X001 M8171 *1

X002 M8172 *1

FNC290-FNC299 Extension File Register Control

X003 M8173 *1

X004 M8174 *1

X005 M8175 *1

X006 M8176 *1*2

X007 M8177 *1*2

FNC300-FNC305 FX 3U -CF-ADP

*1. Cleared when the PLC mode is changed from STOP to RUN.

*2. This function is supported only in FX3U/FX3UC PLCs.

2. Program example

FNC 04 EI Step

0 The EI (FNC 04) instruction is not required in FX3S/FX3G/FX3GC PLCs.

M8170

Y000 When the rising edge of X000 is detected, M8170 is set as interrupt.

The pulse catch result is reset.

RST M8170

PLC Input number Input pulse width

EI

X000, X001 10 µs or more

FX 3S

X002 to X005 50 µs or more

M8170

X000, X001,

X003, X004 10 µs or more

FX 3G /FX 3GC

X002, X005 50 µs or more

X000 to X005 5 µs*3 or more

FX 3U /FX 3UC

X006, X007 50 µs or more

*3. When using the pulse catch function at 5 µs or when receiving a pulse whose response frequency is 50 k to 100 kHz using a high-speed counter, perform the following: - Make sure that the wiring length is 5 m or less. - Connect a bleeder resistor of 1.5 kΩ (1 W or more) to the input terminal, and make sure that the load current

A

of the open collector transistor output in the counterpart equipment is 20 mA or more including the input current in the main unit.

3. Cautions on use

1. When receiving an input again, it is necessary to reset the device which was once set using a program. Accordingly, until a device is reset, a new input cannot be received.
2. When it is necessary to receive continuous short pulses (input signals), use the external input interrupt function or high-speed counter function.

B

3. A filter adjustment program is not required.
4. The pulse catch function is executed regardless of the operations of the special auxiliary relays M8050 to M8055 for disabling interrupts.
Show 10 more labels / short text on this page
SFC•STL Programming · Interrupt Function · Reset input · Input pulse width · X000(Input) · Special Device · X002(Reset) · Error Code · Version Up Information · Execution Times
Page 822 of the Mitsubishi Electronics MELSEC FX3S user manual — 1. Program example
Page 822 · click to enlarge
Page 822

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.8 Pulse width/Pulse period measurement function [M8075 to M8079, D8074 to D8097]

36.8 Pulse width/Pulse period measurement function [M8075 to M8079, D8074 to D8097]

The pulse width/pulse period measurement function stores the values of 1/6 µs ring counters at the input signal rising edge and falling edge to special data registers. This function also divides by "60" the difference in the counter value (pulse width) between the rising edge and the falling edge or the difference in the counter value (pulse period) between the previous rising edge and the current rising edge, and stores the obtained pulse width or pulse period in units of 10 µs to special data registers.

The pulse width/pulse period measurement function becomes valid when a program is described using M8075 as a contact. Specify the pulse width measurement flag in the subsequent OUT instruction, and set an input terminal to be used. When the pulse width/pulse period measurement function is valid, it always operates while the PLC mode is RUN.

Assignment of special auxiliary relays and special data registers

Mitsubishi Electronics MELSEC FX3S — 36.8 Pulse width/Pulse period measurement function [M8075 to M8079, D8074 to D8097] diagram (page 822)
Fig. 803 · 36.8 Pulse width/Pulse period measurement function […

*1. Cleared when the PLC mode switches from STOP to RUN.

*2. The measurable pulse width is 10 µs minimum and 100 s maximum. The measurable pulse period is 20 µs minimum and 100 s maximum.

1. Program example

1. Pulse width measurement The pulse width of the input signal from X000 is measured.
Mitsubishi Electronics MELSEC FX3S — 1. Program example diagram (page 822)
Fig. 804 · 1. Program example

Interrupts are enabled after EI (FNC 04) instruction. The main program is described.

X000 is used for the pulse width/pulse period measurement function.

When the interrupt routine is executed at the falling edge of the input signal from X000, the pulse width of input signal from X000 stored in D8078 and D8079 is transferred to D1 and D0.

Page 823 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 823 · click to enlarge
Page 823

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.8 Pulse width/Pulse period measurement function [M8075 to M8079, D8074 to D8097] 31

2. Pulse period measurement The pulse period of the input signal from X000 is measured.

FNC277-FNC279 Data Transfer 3

ON

OFF

This duration is measured.

FNC280-FNC289 High-Speed Processing 2

Interrupts are enabled after the EI (FNC 04) instruction. The main program is described.

EI

M8075

M8076

X000 is used for the pulse width/pulse period measurement function.

FNC290-FNC299 Extension File Register Control

When X002 turns ON, the pulse period measurement mode is actuated.

M8080

FNC300-FNC305 FX 3U -CF-ADP

FEND

X000 Rising edge interrupt

When the interrupt routine is executed at the rising edge of the input signal from X000, the pulse period of input signal from X000 stored in D8078 and D8079 is transferred to D1 and D0.

M8000

DMOV D8078 D0

User program (Interrupt at the rising edge(X000))

IRET

END

- Timing chart The pulse period is not measured when the input signal rises for the first time after the PLC mode is changed from STOP to RUN, or when the input signal rises for the first time after the pulse period measurement mode (M8080) is set to from OFF to ON. (Accordingly, D8078 and D8079 are not updated.) The pulse period is measured when the input signal rises at the next time. (As a result, D8078 and D8079 are updated.)

Make the pulse width/pulse period measurement setting flag (M8080) remain OFF for 1 operation cycle or more when discontinuing the pulse input. If M8080 does not remain OFF for 1 operation cycle or more, the "a" period shown below is stored as the pulse period.

RUN/STOP RUN

M8080

ON ON

A

The pulse period is not measured.

The pulse period is not measured.

B

The pulse period is measured. (D8078 and D8079 are updated.) The pulse period is measured. (D8078 and D8079 are updated.)

Show 18 more labels / short text on this page
Step · Pulse width · /Pulse period · measurement setting flag · User program · interrupt · pointer · RUN monitor · SFC•STL Programming · Interrupt return · Interrupt Function · Special Device · Error Code · one operation cycle · a · pulse period · Version Up Information · Execution Times
Page 824 of the Mitsubishi Electronics MELSEC FX3S user manual — IRET
Page 824 · click to enlarge
Page 824

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.8 Pulse width/Pulse period measurement function [M8075 to M8079, D8074 to D8097]

3. Signal delay time measurement The delay time from the rising edge of the input signal from X000 to the rising edge of the input signal from X001 is measured.

ON

OFF

ON

OFF

This duration is measured.

Interrupts are enabled after the EI (FNC 04) instruction. The main program is described.

EI

M8075

X000 is used for the pulse width/pulse period measurement function.

M8076

Pulse width /Pulse period measurement setting flag

X001 is used for the pulse width/pulse period measurement function.

M8077

FEND

The interrupt routine is executed at the rising edge of the input signal from X001.

X001 Rising edge interrupt

M8000

The ring counter value at the rising edge of the input signal from X000 stored in D8074 and D8075 is transferred to D1 and D0.

DMOV D8074 D0

The ring counter value at the rising edge of the input signal from X001 stored in D8080 and D8081 is transferred to D3 and D2.

DMOV D8080 D2

The value "Ring counter value at the rising edge of the input signal from X001 - Ring counter value at the rising edge of the input signal from X000" is stored in D9 and D8.

D2 D0 D8 FNC 21

DSUB

When either one between the ring counter value at the rising edge of the input signal from X000 and the ring counter value at the rising edge of the input signal from X001 is located ranging from H80000000 to HFFFFFFFF, the following process is executed, and the value "Ring counter value at the rising edge of the input signal from X001 - Ring counter value at the rising edge of the input signal from X000" is stored in D9 and D8*1.

LDD>= D0 FNC234

K0

ANDD< D2 K0 FNC 21

DSUB H7FFFFFFF

D0 D4

X000 Rising edge ring counter value: H0 to H7FFFFFFF X001 Rising edge ring counter value: H80000000 to HFFFFFFFF

DSUB D2 H80000000 D6

DADD D4 D6 D8

DINC D8

LDD< D0 FNC238 ANDD>= D2 K0 FNC 21

K0

DSUB HFFFFFFFF

D0 D4

X000 Rising edge ring counter value: H80000000 to HFFFFFFFF X001 Rising edge ring counter value: H0 to H7FFFFFFF

DADD D2 D4 D8

DINC D8

M8000 FNC 23

The obtained value is converted into a value in units of 10 µs.

DDIV D8 K60 D10

User program (Interrupt at the rising edge(X001))

IRET

END

Show 6 more labels / short text on this page
Step · User program · interrupt · pointer · RUN monitor · Interrupt return
Page 825 of the Mitsubishi Electronics MELSEC FX3S user manual — FNC300-FNC305 FX 3U -CF-ADP
Page 825 · click to enlarge
Page 825

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

36 Interrupt Function and Pulse Catch Function

36.8 Pulse width/Pulse period measurement function [M8075 to M8079, D8074 to D8097] 31

*1. The ring counter offers 32-bit data including the most significant bit. The DSUB (FNC21) instruction does not give a correct value because it handles the most significant bit as the sign bit. To obtain a correct value, add the processing inside the dotted frame.

FNC277-FNC279 Data Transfer 3

2. Cautions on use

  • The pulse width/pulse period measurement function and input interrupts can be used at the same time in the same input terminal.

FNC280-FNC289 High-Speed Processing 2

  • When the same input terminal is used by the pulse width/pulse period measurement function and the SPD (FNC56), DSZR (FNC150) or ZRN (FNC156) instruction, an operation error occurs when the instruction is executed.
  • The input terminal used for the pulse width/pulse period measurement function cannot be used for the pulse catch function.
  • When the same input terminal is used by the pulse width/pulse period measurement function and a high-speed counter, a grammatical error occurs.

FNC290-FNC299 Extension File Register Control

  • Make sure that the total frequency of four input channels is 50 kHz or less when using the pulse width/pulse period measurement function.
  • When the pulse width/pulse period measurement function and a high-speed counter are used together, the overall frequency of the high-speed counter is affected.

→ For details on high-speed counters, refer to Subsection 4.7.7.

FNC300-FNC305 FX 3U -CF-ADP

A

B

Show 6 more labels / short text on this page
SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 826 of the Mitsubishi Electronics MELSEC FX3S user manual — M8003
Page 826 · click to enlarge
Page 826

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

37. Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

The device numbers and functions of the special auxiliary relays (indicated as "special M" in tables) and special data registers (indicated as "special D" in tables) are shown below. Note that functions of certain devices vary depending on the series of the PLC. Do not use the undefined / blank special auxiliary relays and special data registers in the sequence program since they are occupied by the CPU. In addition, do not activate or write to the devices with brackets on the first letter such as [M]8000 or [D]8001 in the program.

→ Refer to Section 37.2 for supplementary information on analog special adapter devices.

37.1.1 Special Auxiliary Relay (M8000 to M8511)

name Operation and function

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

[M]8000 RUN monitor NO contact

3 – 3

[M]8001 RUN monitor NC contact

3 – 3

M8000

M8001

[M]8002 Initial pulse NO contact

3 – 3

M8002

[M]8003 Initial pulse NC contact

M8003

3 – 3

→Refer to Subsection 37.2.1.

  • FX 3S /FX 3G /FX 3GC /FX 3U /FX 3UC ON when either M8060, M8061, M8064, M8065, M8066, or M8067 is ON.
  • FX 1S /FX 1N /FX 1NC /FX 2N /FX 2NC ON when either M8060, M8061, M8063, M8064, M8065, M8066, or M8067 is ON.

ON when battery voltage is below the value set in D8006.

[M]8005 Battery voltage low

→Refer to Subsection 37.2.3.

[M]8006 Battery error latch

It is set when battery voltage low is detected.

→Refer to Subsection 37.2.3. – 3 D8006 – – – 3 3

ON for 1 scan, when momentary power failure is detected Even if M8007 turns ON, PLC continues to RUN as long as the duration of power loss is within the time period specified in D8008.

[M]8007 Momentary power failure

– – – 3 3 D8007 D8008 – – – 3 3

→Refer to Subsection 37.2.4.

It is set when momentary power failure is detected. If power loss time is longer than the time period specified in D8008, M8008 is reset and PLC is switched to STOP mode. (M8000=OFF).

[M]8008 Power failure detected

→Refer to Subsection 37.2.4.

[M]8009 24V DC down ON when 24 V DC power fails in an I/O extension unit or special function block. – 3 D8009 – – – 3 3

Show 10 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · PLC Status · RUN input · M8061 Error occurrence · 1 scan time · [M]8004 Error occurrence
Page 827 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 827 · click to enlarge
Page 827

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Operation and function

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Clock [M]8010 Not used –

ON and OFF in 10 ms cycles (ON: 5 ms, OFF: 5 ms)

[M]8011 10 ms clock pulse

3 – 3

FNC280-FNC289 High-Speed Processing 2

→Refer to Subsection 37.2.6.

ON and OFF in 100 ms cycles (ON: 50 ms, OFF: 50 ms)

[M]8012 100 ms clock pulse

3 – 3

→Refer to Subsection 37.2.6.

ON and OFF in 1 sec cycles (ON: 500 ms, OFF: 500 ms)

[M]8013 1 sec clock pulse

3 – 3

→Refer to Subsection 37.2.6.

ON and OFF in 1 min cycles (ON: 30 sec, OFF: 30 sec)

FNC290-FNC299 Extension File Register Control

[M]8014 1 min clock pulse

3 – 3

→Refer to Subsection 37.2.6.

Clock stop and preset For real time clock

M 8015

3 – 3*3

→Refer to Subsection 37.2.7.

Time read display is stopped For real time clock

M 8016

3 – 3*3

FNC300-FNC305 FX 3U -CF-ADP

→Refer to Subsection 37.2.7.

±30 seconds correction For real time clock

M 8017

3 – 3*3

→Refer to Subsection 37.2.7.

Installation detection (Always ON) For real time clock

[M]8018

3 – 3 (Always ON)*3

→Refer to Subsection 37.2.7.

Real time clock (RTC) error For real time clock

M 8019

3 – 3*3

→Refer to Subsection 37.2.7.

ON when the result of addition/subtraction is 0.

→Refer to Subsection 6.5.2 for usage. 3 – 3

ON when the result of subtraction is less than the min. negative number.

3 – 3

→Refer to Subsection 6.5.2 for usage.

ON when 'carry' occurs in result of addition or when an overflow occurs in result of shift operation.

3 – 3

→Refer to Subsection 6.5.2 for usage.

[M]8023 Not used –

M 8024*1 BMOV direction specification (FNC 15) 3 – – 3

M 8025*2 HSC mode (FNC 53 to 55) – – – 3 3 – 3 3

M 8026*2 RAMP mode (FNC 67) – – – 3 3 – 3 3

M 8027*2 PR mode (FNC 77) – – – 3 3 – 3 3

100 ms/10 ms timer changeover 3 – 3 – Interrupt permission during FROM/TO (FNC 78 and 79) instruction execution – 3 – 3 3

M 8028

[M]8029 Instruction execution complete

ON when operation such as DSW (FNC 72) is completed.

3 – 3

A

→Refer to Subsection 6.5.2 for usage.

*1. The operation varies according to PLC: - Not cleared in an FX1N/FX1NC/FX2N/FX2NC PLCs. - Cleared in an FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs when PLC switches from RUN to STOP.

*2. The operation varies according to PLC: - Not cleared in an FX2N/FX2NC PLCs. - Cleared in an FX3U/FX3UC PLCs when PLC switches from RUN to STOP.

B

*3. The FX2NC PLC requires the optional memory board (with the real time clock).

Show 14 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · SFC•STL Programming · Flag [M]8020 Zero · [M]8021 Borrow · Interrupt Function · M 8022 Carry · Special Device · Error Code · Version Up Information · Execution Times
Page 828 of the Mitsubishi Electronics MELSEC FX3S user manual — M 8034 *1
Page 828 · click to enlarge
Page 828

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

name Operation and function

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

M 8030 *1

When M8030 set to ON, LED on PLC is not lit even if battery voltage low is detected.

– 3 – 3 3

→Refer to Subsection 37.2.10.

M 8031 *1

If this special auxiliary relay is activated, the ON/OFF image memory of Y, M, S, T, and C, and present values of T, C, D, special data

Non-latch memory all clear

3 – 3

registers*3, and R*2 are cleared to zero. However, file registers (D) in program memory

M 8032 *1

and extension file registers (ER)*2 in the memory cassette are not cleared.

3 – 3

Latch memory all clear

→Refer to Subsection 37.2.12.

M 8033 Memory hold STOP

When PLC is switched from RUN to STOP, image memory and data memory are retained.

3 – 3

→Refer to Subsection 37.2.13.

All external output contacts of PLC are turned OFF.

M 8034 *1

3 – 3

→Refer to Subsection 37.2.14.

M 8035 Forced RUN mode

3 – 3

M 8036 Forced RUN signal 3 – 3

→Refer to Subsection 37.2.15 for details.

M 8037 Forced STOP signal

3 – 3

Communication parameter setting flag (for N:N network setting)

3 D8176 to

→Refer to Data Communication Edition.

When M8039 is ON, PLC waits until scan time specified in D8039 and then executes cyclic operation.

M 8039 Constant scan mode

→Refer to Subsection 37.2.16.

*1. It is executed when END instruction is executed.

*2. R and ER are available only in FX3G/FX3GC/FX3U/FX3UC PLCs.

*3. Special data registers are not cleared in FX1S/FX1N/FX1NC/FX2N/FX2NC PLCs.

*4. It is available in Ver. 2.00 or later.

Show 9 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · PLC Mode · Battery LED OFF · All outputs disable · [M]8038 Parameter setting
Page 829 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 829 · click to enlarge
Page 829

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Operation and function

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Step Ladder and Annunciator (Refer to ANS (FNC 46), ANR (FNC 47), IST (FNC 60), and Chapter 35 for details.) M 8040 Transfer disable

While M8040 is turned ON, transfer between states is disabled. 3 – 3

[M]8041 *1

Transfer from initial state is enabled in automatic operation mode. 3 – 3

FNC280-FNC289 High-Speed Processing 2

Pulse output is given in response to a start input. 3 – 3

M 8043 *1

Zero return complete Set this in the last state of zero return mode. 3 – 3

M 8044 *1

Zero point condition Set this when machine zero return is detected. 3 – 3

FNC290-FNC299 Extension File Register Control

M 8045 All output reset disable

Disables the ’all output reset’ function when the operation mode is changed. 3 – 3

[M]8046 *2

ON when M8047 is ON and any state S0 to

S899 or S1000 to S4095*3 is active. 3 M8047 3

M 8047 *2

D8040 to D8047 are enabled when M8047 is ON. 3 D8040 to

FNC300-FNC305 FX 3U -CF-ADP

[M]8048 *2

ON when M8049 is ON and any annunciator S900 to S999 is ON. – 3 – 3 3

M 8049 *1

Annunciator enable D8049 is enabled when M8049 is ON. – 3 D8049 M8048 – – – 3 3

*1. Cleared when the PLC switches from RUN to STOP.

*2. Executed at END instruction.

*3. S1000 to S4095 are available only in the FX3G/FX3GC/FX3U/FX3UC Series PLCs.

Interrupt Disable (Refer to Subsection 36.2.1.) for details.

3 – 3

3 – 3

  • If an input interrupt or timer interrupt occurs while a special auxiliary relay for that interrupt (M8050 - M8058) is ON, the interrupt will not operate. For example, turning M8050 ON disables the I00 interrupt; hence, the interrupt routine is not processed even in an allowable program area.

3 – 3

3 – 3

  • If an input interrupt or timer interrupt occurs while a special auxiliary relay for that interrupt (M8050 - M8058) is OFF,

3 – 3

a) The interrupt will be accepted. b) The interrupt routine will be processed promptly if it is permitted by the EI (FNC 04) instruction. However, if the DI (FNC 05) instruction disables interrupts, the interrupt program will not be processed until EI (FNC 04) permits the interrupts.

3 – 3

3 – 3 3

A

3 – 3 3

3 – 3 3

B

Interrupt of I010 to I060 disabled – – – 3 3 – 3 3

*4. Cleared when the PLC switches from RUN to STOP.

Show 36 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · Transfer start · [M]8042 Start pulse · STL state ON · STL monitoring enable · Annunciator operate · SFC•STL Programming · M8050 (input interrupt) · Interrupt Function · I00 disable*4 · M8051 (input interrupt) · I10 disable*4 · M8052 (input interrupt) · I20 disable*4 · Special Device · M8053 (input interrupt) · I30 disable*4 · M8054 (input interrupt) · I40 disable*4 · M8055 (input interrupt) · Error Code · I50 disable*4 · M8056 (Timer interrupt) · I6 disable*4 · M8057 (Timer interrupt) · I7 disable*4 · Version Up Information · M8058 (Timer interrupt) · I8 disable*4 · M8059 Counter interrupt · disable*4 · Execution Times
Page 830 of the Mitsubishi Electronics MELSEC FX3S user manual — 37. Operation of Special Devices (M8000 -, D8000 -)
Page 830 · click to enlarge
Page 830

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

Mitsubishi Electronics MELSEC FX3S — 37. Operation of Special Devices (M8000 -, D8000 -) diagram (page 830)
Fig. 805 · 37. Operation of Special Devices (M8000 -, D8000 -)

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Error Detection (Refer to Chapter 38 for details.) [M]8060 I/O configuration error – 3 D8060 – – – 3 3 [M]8061 PLC hardware error 3 D8061 – – – 3 3

PLC/PP communication error 3*1 – – 3*1 3*1 D8062 3

Serial communication error 0 [ch0]*2 – 3 3 – – D8062 –

[M]8063*3*4 Serial communication error 1 [ch1] 3 D8063

[M]8064 Parameter error 3 D8064 3

[M]8067*5 Operation error 3

M 8068 Operation error latch 3 D8068 D8312 D8313

M 8069*6 I/O bus check – 3 – 3 3

*1. It truns on, only when a memory access error (6230) occurs in FX3S/FX3U/FX3UC PLCs.

*2. Cleared when PLC power supply is turned from OFF to ON.

*3. The operation varies according to PLC: - Cleared in an FX1S/FX1N/FX1NC/FX2N/FX2NC PLCs when PLC switches from STOP to RUN. - Cleared in an FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs when PLC power supply from OFF to ON.

*4. Serial communication error 2 [ch2] is detected by M8438 in FX3G/FX3GC/FX3U/FX3UC PLCs.

*5. Cleared when PLC switches from STOP to RUN.

*6. When M8069 is ON, I/O bus check is executed.

Mitsubishi Electronics MELSEC FX3S — 37. Operation of Special Devices (M8000 -, D8000 -) diagram (page 830)
Fig. 806 · 37. Operation of Special Devices (M8000 -, D8000 -)

M 8070*7 Parallel link Set M8070 when using master station. 3 – 3

M 8071*7 Parallel link Set M8071 when using slave station. 3 – 3

[M]8072 Parallel link ON when operating 3 – 3

[M]8073 Parallel link ON when M8070 or M8071 setting is incorrect 3 – 3

*7. Cleared when PLC switches from STOP to RUN.

Mitsubishi Electronics MELSEC FX3S — 37. Operation of Special Devices (M8000 -, D8000 -) diagram (page 830)
Fig. 807 · 37. Operation of Special Devices (M8000 -, D8000 -)

Sampling Trace [FX3U/FX3UC/FX2N/FX2NC] [M]8074 Not used – [M]8075 Ready request for sampling trace – – – 3 3

– – – 3 3 [M]8076 Start request for sampling trace – – – 3 3 – – – 3 3 [M]8077 ON during sampling trace – – – 3 3 – – – 3 3 [M]8078 ON when sampling trace is completed – – – 3 3 – – – 3 3 [M]8079 Sampling trace system area – – – 3 3 – – – 3 3

Page 831 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 831 · click to enlarge
Page 831

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Operation and function

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Pulse width/Pulse period measurement [FX3G/FX3GC PLCs ] [M]8074 Not used –

[M]8075 Pulse width/Pulse period measurement setting flag – 3*1 3 –

FNC280-FNC289 High-Speed Processing 2

[M]8076 [X000] Pulse width/Pulse period measurement flag – 3*1 3 – – D8074 to

[M]8077 [X001] Pulse width/Pulse period measurement flag – 3*1 3 – – D8080 to

[M]8078 [X003] Pulse width/Pulse period measurement flag – 3*1 3 – – D8086 to

[M]8079 [X004] Pulse width/Pulse period measurement flag – 3*1 3 – – D8092 to

FNC290-FNC299 Extension File Register Control

M 8080 [X000] Pulse period measurement mode – 3*1 3 – – D8074 to

M 8081 [X001] Pulse period measurement mode – 3*1 3 – – D8080 to

M 8082 [X003] Pulse period measurement mode – 3*1 3 – – D8086 to

FNC300-FNC305 FX 3U -CF-ADP

M 8083 [X004] Pulse period measurement mode – 3*1 3 – – D8092 to

[M]8084 to [M]8089 Not used –

*1. Available in Ver. 1.10 or later.

[M]8090 BKCMP (FNC194 to FNC199) instructions - Block comparison signal – – – 3 3*2 –

COMRD (FNC182) and BINDA (FNC261) instructions - Output character quantity selector signal

– – – 3 3*2 –

M 8091

[M]8092

– [M]8093 – [M]8094 – [M]8095 – [M]8096 – [M]8097 – [M]8098 – High-Speed Ring Counter

M 8099*3 High-speed ring counter operation (in units of 0.1ms, 16 bits) – – – 3 3 D8099 – – – 3 3

[M]8100 Not used –

*2. Available in Ver. 2.20 or later.

*3. For FX2N/FX2NC PLCs, 0.1ms high-speed ring counter D8099 will operate after END instruction is executed with after M8099 is driven. For FX3U/FX3UC PLCs, 0.1ms high-speed ring counter D8099 will operate after M8099 is driven.

A

B

Show 13 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · Flag · SFC•STL Programming · Interrupt Function · Not used · Special Device · Error Code · Version Up Information · Execution Times
Page 832 of the Mitsubishi Electronics MELSEC FX3S user manual — M 8129
Page 832 · click to enlarge
Page 832

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

Mitsubishi Electronics MELSEC FX3S — 37. Operation of Special Devices (M8000 -, D8000 -) diagram (page 832)
Fig. 808 · 37. Operation of Special Devices (M8000 -, D8000 -)

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

– [M]8102 – [M]8103 –

[M]8104 ON when function extension memory is installed. – D8104 D8105 – – – 3*2 3*2

[M]8105 ON during writing in RUN mode*1 3 –

[M]8106 Not used – [M]8107 Device comment registration check – – – 3 3 D8107 – [M]8108 Not used –

*1. For FX3U/FX3UC PLCs, available only when a memory cassette is connected.

*2. Available in Ver. 3.00 or later.

Output Refresh Error (Refer to Chapter 38 for details.) [M]8109 Output refresh error – 3 D8109 – – – 3 3 [M]8110 Not used – [M]8111 – Expansion Board [For FX3S/FX3G]

[M]8112 FX3G-4EX-BD: BX0 input 3*3 3*4 –

[M]8113 FX3G-4EX-BD: BX1 input 3*3 3*4 –

[M]8114 FX3G-4EX-BD: BX2 input 3*3 3*4 –

[M]8115 FX3G-4EX-BD: BX3 input 3*3 3*4 –

M 8116 FX3G-2EYT-BD: BY0 output 3*3 3*4 –

M 8117 FX3G-2EYT-BD: BY1 output 3*3 3*4 –

[M]8118 Not used – [M]8119 –

*3. Available in Ver. 1.10 or later.

*4. Available in Ver. 2.20 or later.

Expansion Board [For FX1S/FX1N]

M 8112 FX1N-4EX-BD: BX0 input – 3 3 – – – FX1N-2AD-BD: ch1 input mode change – D8112 3 3 – – –

M 8113 FX1N-4EX-BD: BX1 input – 3 3 – – – FX1N-2AD-BD: ch2 input mode change – D8113 3 3 – – –

M 8114 FX1N-4EX-BD: BX2 input – 3 3 – – – FX1N-1DA-BD: output mode change – D8114 3 3 – – – M 8115 FX1N-4EX-BD: BX3 input – 3 3 – – – M 8116 FX1N-2EYT-BD: BY0 output – 3 3 – – – M 8117 FX1N-2EYT-BD: BY1 output – 3 3 – – – [M]8118 Not used – [M]8119 – RS (FNC 80) and Computer Link [ch1] (Refer to Data Communication Edition for details.) [M]8120 Not used –

[M]8121*5 RS (FNC 80) instruction: Send wait flag 3 – 3

M 8122*5 RS (FNC 80) instruction: Send request 3 D8122 3

M 8123*5 RS (FNC 80) instruction: Receive complete flag 3 D8123

[M]8124 RS (FNC 80) instruction: Carrier detection flag 3 – 3 [M]8125 Not used – [M]8126 Computer link [ch1] Global ON 3

3

[M]8127 Computer link [ch1] On-demand send processing 3 – – – 3 3

D8127 D8128 D8129

M 8128 Computer link [ch1] On-demand error flag 3

Computer link [ch1] On-demand Word / Byte changeover RS (FNC 80) instruction: Time-out check flag

M 8129

3

*5. Cleared when PLC switches from RUN to STOP or RS instruction is OFF.

Page 833 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 833 · click to enlarge
Page 833

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Operation and function

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

High-Speed Counter Comparison, High-Speed Table, and Positioning [Positioning is supported in FX3S/FX3G/FX3GC/FX1S/FX1N/FX1NC]

M 8130 HSZ (FNC 55) instruction: Table comparison mode – – – 3 3 D8130

– – – 3 3

[M]8131 HSZ (FNC 55) instruction: Table comparison mode completion flag – – – 3 3 – – – 3 3

FNC280-FNC289 High-Speed Processing 2

M 8132 HSZ (FNC 55) and PLSY (FNC 57) instructions: Speed pattern mode – – – 3 3 D8131 to

– – – 3 3

[M]8133 HSZ (FNC 55) and PLSY (FNC 57) instructions: Speed pattern mode completion flag – – – 3 3 – – – 3 3

[M]8134

– [M]8135 – [M]8136 – [M]8137 –

FNC290-FNC299 Extension File Register Control

[M]8138 HSCT (FNC280) instruction: Instruction execution complete flag – – – 3 3 D8138 –

HSCS (FNC 53), HSCR (FNC 54), HSZ (FNC 55), HSCT (FNC280) instructions: High-speed counter comparison instruction executing

[M]8139

FNC300-FNC305 FX 3U -CF-ADP

M 8140 ZRN (FNC156) instruction: CLR signal output function enable – 3 3 3 – –

[M]8141

– [M]8142 – [M]8143 – [M]8144 – M 8145 [Y000] Pulse output stop command 3 3 3 – – – 3 3 3 – – M 8146 [Y001] Pulse output stop command 3 3 3 – – – 3 3 3 – – [M]8147 [Y000] Pulse output monitor (BUSY/READY) 3 3 3 – – – 3 3 3 – – [M]8148 [Y001] Pulse output monitor (BUSY/READY) 3 3 3 – – – 3 3 3 – – [M]8149 Not used – Inverter Communication Function (Refer to Data Communication Edition for details.) [M]8150 Not used –

[M]8151 Inverter communication in execution [ch1] 3 3*3 D8151 –

[M]8152*1 Inverter communication error [ch1] 3 3*3 D8152 –

[M]8153*1 Inverter communication error latch [ch1] 3 3*3 D8153 –

[M]8154*1 IVBWR (FNC274) instruction error [ch1] – – – 3 3 D8154 –

[M]8154 Defined per use of EXTR (FNC180) – 3*2 3*2

[M]8155 EXTR (FNC180) is using communicating port – D8155 – – – 3*2 3*2

[M]8156 Inverter communication in execution [ch2] – 3*3 D8156 –

[M]8156 Communication error or parameter error in EXTR (FNC180) instruction – D8156 – – – 3*2 3*2

Inverter communication error [ch2] – 3*3 D8157 –

[M]8157 *1

Communication error in EXTR (FNC180) instruction is latched. – D8157 – – – 3*2 3*2

[M]8158*1 Inverter communication error latch [ch2] – 3*3 D8158 –

[M]8159*1 IVBWR (FNC274) instruction error [ch2] – – – 3 3 D8159 –

*1. Cleared when PLC switches from STOP to RUN.

*2. Available in Ver. 3.00 or later.

A

*3. Available in Ver. 1.10 or later.

B

Show 13 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · Not used · Not used · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 834 of the Mitsubishi Electronics MELSEC FX3S user manual — 37. Operation of Special Devices (M8000 -, D8000 -)
Page 834 · click to enlarge
Page 834

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

name Operation and function

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

M 8160*1 SWAP function of XCH (FNC 17) – – – 3 3 – 3 3

M 8161*1*2 8-bit process mode 3 – 3

M 8162 High-speed parallel link mode 3 – 3 [M]8163 Not used –

M 8164*1 FROM (FNC 78), TO (FNC 79) instructions: Transfer points variable mode – D8164 – – – 3*3 3

M 8165*1 SORT2 (FNC149) instruction: Sorting in descending order – – – 3 3*4 –

[M]8166 Not used –

M 8167*1 HKY (FNC 71) instruction: HEX data handling function – – – 3 3 – 3 3

M 8168*1 SMOV (FNC 13) instruction: HEX data handling function 3 – 3 3

[M]8169 Not used –

*1. Cleared when the PLC switches from RUN to STOP.

*2. Applicable to ASC (FNC 76), RS (FNC 80), ASCI (FNC 82), HEX (FNC 83), CCD (FNC 84), and CRC

(FNC188) instructions*5.

*3. Available in Ver. 2.00 or later.

*4. Available in Ver. 2.20 or later.

*5. CRC (FNC188) instruction is available only in FX3U/FX3UC PLCs.

Mitsubishi Electronics MELSEC FX3S — 37. Operation of Special Devices (M8000 -, D8000 -) diagram (page 834)
Fig. 809 · 37. Operation of Special Devices (M8000 -, D8000 -)

M 8170*6 Input X000 pulse catch 3 – 3

M 8171*6 Input X001 pulse catch 3 – 3

M 8172*6 Input X002 pulse catch 3 – 3

M 8173*6 Input X003 pulse catch 3 – 3

M 8174*6 Input X004 pulse catch 3 – 3

M 8175*6 Input X005 pulse catch 3 – 3

M 8176*6 Input X006 pulse catch – – – 3 3 –

M 8177*6 Input X007 pulse catch – – – 3 3 –

*6. Cleared when PLC switches from STOP to RUN. FX3U/FX3UC/FX2N/FX2NC PLCs: EI (FNC 04) instruction is necessary. FX3S/FX3G/FX3GC/FX1S/FX1N/FX1NC PLCs: EI (FNC 04) instruction is unnecessary.

Communication Port Channel Setting (Refer to Data Communication Edition for details.) M 8178 Parallel link channel switch (OFF: ch1/ON: ch2) – 3 –

M 8179 N:N network channel switch*7 – 3 –

*7. The channel is specified by either setting or not setting M8179 in the setting program.

  • → For setting program, Refer to Data Communication Edition
  • ch1: M8179 is not set in program
  • ch2: M8179 is set in program
Show 6 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · Advanced Function
Page 835 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 835 · click to enlarge
Page 835

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Operation and function

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

N:N Network (Refer to FX Series User’s Manual - Data Communication Edition for details.) [M]8180

– [M]8181 – [M]8182 –

FNC280-FNC289 High-Speed Processing 2

[M]8183*1 Data communication error (Master station) 3

(M504) 3 3 3 *2 3

[M]8184*1 Data communication error (Slave station No.1) 3 (M505) 3 3 3*2 3

[M]8185*1 Data communication error (Slave station No.2) 3 (M506) 3 3 3*2 3

[M]8186*1 Data communication error (Slave station No.3) 3 (M507) 3 3 3*2 3

[M]8187*1 Data communication error (Slave station No.4) 3 (M508) 3 3 3*2 3

[M]8188*1 Data communication error (Slave station No.5) 3 (M509) 3 3 3*2 3

FNC290-FNC299 Extension File Register Control

[M]8189*1 Data communication error (Slave station No.6) 3 (M510) 3 3 3*2 3

[M]8190*1 Data communication error (Slave station No.7) 3 (M511) 3 3 3*2 3

[M]8191*1 Data communication in execution 3 (M503) 3 3 3*2 3

[M]8192

– [M]8193 – [M]8194 – [M]8195 – [M]8196 – [M]8197 –

FNC300-FNC305 FX 3U -CF-ADP

*1. In FX1S PLC, use numbers shown inside parentheses.

*2. Available in Ver. 2.00 or later.

High-Speed Counter Edge Count Specification (Refer to Subsection 4.8.8 for details.)

M 8198*3*4 C251, C252, C254: 1/4 edge count selector – – – 3 3 –

M 8199*3*4 C253, C255, or C253 (OP): 1/4 edge count selector – – – 3 3 –

*3. OFF1 edge count ON: 4 edge count

*4. Cleared when the PLC switches from RUN to STOP.

A

B

Show 14 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · Not used · D8201 to · Not used · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 836 of the Mitsubishi Electronics MELSEC FX3S user manual — 37. Operation of Special Devices (M8000 -, D8000 -)
Page 836 · click to enlarge
Page 836

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

name Operation and function

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Counter Up/down Counter Counting Direction (Refer to Section 4.6 for details.) M 8200 C200

3 – – 3 M 8201 C201 3 – – 3 M 8202 C202 3 – – 3 M 8203 C203 – – 3 M 8204 C204 3 – – 3 M 8205 C205 3 – – 3 M 8206 C206 3 – – 3 M 8207 C207 3 – – 3 M 8208 C208 3 – – 3 M 8209 C209 3 – – 3 M 8210 C210 3 – – 3 M 8211 C211 3 – – 3 M 8212 C212 3 – – 3 M 8213 C213 – – 3 M 8214 C214 3 – – 3 M 8215 C215 3 – – 3 M 8216 C216 3 – – 3 M 8217 C217 3 – – 3 M 8218 C218 3 – – 3 M 8219 C219 3 – – 3 M 8220 C220 3 – – 3 M 8221 C221 3 – – 3 M 8222 C222 3 – – 3 M 8223 C223 – – 3 M 8224 C224 3 – – 3 M 8225 C225 3 – – 3 M 8226 C226 3 – – 3 M 8227 C227 3 – – 3 M 8228 C228 3 – – 3 M 8229 C229 3 – – 3 M 8230 C230 3 – – 3 M 8231 C231 3 – – 3 M 8232 C232 3 – – 3 M 8233 C233 – – 3 M 8234 C234 3 – – 3

  • When M8 is ON, the corresponding C is changed to down mode.
  • ON: Down count operation
  • OFF: Up count operation
Show 5 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device
Page 837 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 837 · click to enlarge
Page 837

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Operation and function

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

High-Speed Counter Up/down Counter Counting Direction (Refer to Section 4.7 or 4.8 for details.) M 8235 C235

3 – 3 M 8236 C236 3 – 3 M 8237 C237 3 – 3 M 8238 C238 3 – 3 M 8239 C239 3 – 3 M 8240 C240 3 – 3 M 8241 C241 3 – 3 M 8242 C242 3 – 3 M 8243 C243 – 3 M 8244 C244 3 – 3 M 8245 C245 3 – 3 High-Speed Counter Up/down Counter Monitoring (Refer to Section 4.7 or 4.8 for details.) [M]8246 C246

FNC280-FNC289 High-Speed Processing 2

  • When M8 is ON, the corresponding C is changed to down mode.
  • ON: Down count operation
  • OFF: Up count operation

FNC290-FNC299 Extension File Register Control

3 – 3 [M]8247 C247 3 – 3 [M]8248 C248 3 – 3 [M]8249 C249 3 – 3 [M]8250 C250 3 – 3 [M]8251 C251 3 – 3 [M]8252 C252 3 – 3 [M]8253 C253 – 3 [M]8254 C254 3 – 3 [M]8255 C255 3 – 3 [M]8256 to [M]8259 Not used – Analog Special Adapter [FX3U/FX3UC] (Refer to Subsection 37.2.19 for applicability of each analog special adapter.)

  • When C of 1-phase 2-input or 2phase 2-input counter is in down mode, the corresponding M8 turns ON.
  • ON: Down count operation
  • OFF: Up count operation

FNC300-FNC305 FX 3U -CF-ADP

M 8260 to M 8269 1st special adapter*1 – – – 3 3*2 –

M 8270 to M 8279 2nd special adapter*1 – – – 3 3*2 –

M 8280 to M 8289 3rd special adapter*1 – – – 3 3*2 –

M 8290 to M 8299 4th special adapter*1 – – – 3 3*2 –

Analog Special Adapter [FX3S/FX3G/FX3GC], Analog Expansion Board [FX3S/FX3G] (Refer to Subsection 37.2.18 for applicability of each analog special adapter, and analog expansion board)

M 8260 to M 8269 1st expansion board*3 3 3*6 –

M 8270 to M 8279 2nd expansion board*4*5 – 3*6 –

M 8280 to M 8289 1st special adapter*1 3 3 3 –

M 8290 to M 8299 2nd special adapter*1*5 – 3 3 –

*1. Count the number of connected analog special adapter from the main unit.

*2. Available in Ver. 1.20 or later.

*3. Expansion board connected to the BD1 connector of a FX3G PLC (40-point and 60-point type) or the BD connector of a FX3G PLC (14-point and 24-point type) and FX3S PLC.

*4. Expansion board connected to the BD2 connector of a FX3G PLC (40-point and 60-point type).

*5. Only a FX3G PLC (40-point and 60-point type) can be connected.

*6. Available in Ver. 1.10 or later.

A

B

Show 11 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 838 of the Mitsubishi Electronics MELSEC FX3S user manual — [M]8322
Page 838 · click to enlarge
Page 838

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

name Operation and function

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Flags [M]8300 to [M]8303 Not used –

[M]8304 Zero ON when the multiplication and division calculated result is 0 3*1 3*1 –

[M]8305 Not used –

[M]8306 Carry ON when the division calculated result overflows 3*1 3*1 –

[M]8307 to [M]8311 Not used – Unconnected I/O Designation Error (Refer to Chapter 38 for details.) and flag

[M]8312*2 Real time clock data lost error 3 3 3 –

[M]8313 to [M]8315 Not used –

[M]8316*3 Unconnected I/O designation error – – – 3 3 D8316 D8317 –

[M]8317 Not used –

BFM initialization failure ON when a FROM/TO error has occurred in a special function unit/block as specified in the BFM initialization function at changing PLC from STOP to RUN. When M8318 turns ON, the unit number in which the error has occurred is stored in D8318, and the BFM number is stored in D8319.

– – – 3 3*4 D8318 D8319 –

[M]8318

[M]8319 to [M]8321 Not used –

FX3UC-32MT-LT/FX3UC-32MT-LT-2 model indicator 1:FX3UC-32MT-LT-2 0:FX3UC-32MT-LT

[M]8322

– 3*5 –

[M]8323 CC-Link/LT configuration required – 3*5 –

[M]8324 CC-Link/LT configuration completed – 3*5 –

[M]8325 to [M]8327 Not used –

[M]8328 Instruction non-execution – – – 3 3*4 –

[M]8329 Instruction execution abnormal end 3 –

*1. Available in Ver. 2.30 or later.

*2. M8312 is EEPROM backed up against power failure, and is automatically cleared when it is cleared or when the clock data is set again. For details on backup against power failure, refer to Section 2.6.

*3. If the I/O device numbers are unavailable, M8316 turns ON when its directly designated to device numbers including LD, AND, OR, and OUT instructions or indirectly designated by index.

*4. Available in Ver. 2.20 or later.

*5. Only the FX3UC-32MT-LT-2 is applicable.

Show 5 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device
Page 839 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 839 · click to enlarge
Page 839

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Operation and function

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Timing Clock (Refer to Section 24.3 for details.) and Positioning [FX3S/FX3G/FX3GC/FX3U/FX3UC] (Refer to Positioning Control Edition for details.)

[M]8330 DUTY (FNC186) instruction: Timing clock output 1 – – – 3 3*1 D8330 –

FNC280-FNC289 High-Speed Processing 2

[M]8331 DUTY (FNC186) instruction: Timing clock output 2 – – – 3 3*1 D8331 –

[M]8332 DUTY (FNC186) instruction: Timing clock output 3 – – – 3 3*1 D8332 –

[M]8333 DUTY (FNC186) instruction: Timing clock output 4 – – – 3 3*1 D8333 –

[M]8334 DUTY (FNC186) instruction: Timing clock output 5 – – – 3 3*1 D8334 –

FNC290-FNC299 Extension File Register Control

[M]8335 Not used –

M 8336*2 DVIT (FNC151) instruction: Interrupt input specification function enabled – – – 3 3*3 D8336 –

[M]8337 Not used –

M 8338*2 PLSV (FNC157) instruction: Acceleration/deceleration operation 3*1 –

FNC300-FNC305 FX 3U -CF-ADP

[M]8339 Not used –

[M]8340 [Y000] Pulse output monitor (ON: BUSY/ OFF: READY) 3 –

M 8341*2 [Y000] Clear signal output function enable 3 –

M 8342*2 [Y000] Zero return direction specification 3 –

M 8343 [Y000] Forward limit 3 – M 8344 [Y000] Reverse limit 3 –

M 8345*2 [Y000] DOG signal logic reverse 3 –

M 8346*2 [Y000] Zero point signal logic reverse 3 –

M 8347*2 [Y000] Interrupt signal logic reverse – – – 3 3 –

[M]8348 [Y000] Positioning instruction activation 3 –

M 8349*2 [Y000] Pulse output stop command 3 –

[M]8350 [Y001] Pulse output monitor (ON: BUSY/ OFF: READY) 3 –

M 8351*2 [Y001] Clear signal output function enable 3 –

M 8352*2 [Y001] Zero return direction specification 3 –

M 8353 [Y001] Forward limit 3 – M 8354 [Y001] Reverse limit 3 –

M 8355*2 [Y001] DOG signal logic reverse 3 –

M 8356*2 [Y001] Zero point signal logic reverse 3 –

M 8357*2 [Y001] Interrupt signal logic reverse – – – 3 3 –

[M]8358 [Y001] Positioning instruction activation 3 –

M 8359*2 [Y001] Pulse output stop command 3 –

[M]8360 [Y002] Pulse output monitor (ON: BUSY/ OFF: READY) – 3 – 3 3 –

M 8361*2 [Y002] Clear signal output function enable – 3 – 3 3 –

M 8362*2 [Y002] Zero return direction specification – 3 – 3 3 –

M 8363 [Y002] Forward limit – 3 – 3 3 – M 8364 [Y002] Reverse limit – 3 – 3 3 –

M 8365*2 [Y002] DOG signal logic reverse – 3 – 3 3 –

A

M 8366*2 [Y002] Zero point signal logic reverse – 3 – 3 3 –

M 8367*2 [Y002] Interrupt signal logic reverse – – – 3 3 –

[M]8368 [Y002] Positioning instruction activation – 3 – 3 3 –

M 8369*2 [Y002] Pulse output stop command – 3 – 3 3 –

*1. Available in Ver. 2.20 or later.

B

*2. Cleared when the PLC switches from RUN to STOP.

*3. Available in the Ver. 1.30 or later.

Show 11 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 840 of the Mitsubishi Electronics MELSEC FX3S user manual — 37. Operation of Special Devices (M8000 -, D8000 -)
Page 840 · click to enlarge
Page 840

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

name Operation and function

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Positioning [FX3U] (Refer to Positioning Control Manual for details.)

[M]8370 [Y003] Pulse output monitor (ON: BUSY/ OFF: READY) – – – 3*2 –

M 8371*1 [Y003] Clear signal output function enable – – – 3*2 –

M 8372*1 [Y003] Zero return direction specification – – – 3*2 –

M 8373 [Y003] Forward limit – – – 3*2 –

M 8374 [Y003] Reverse limit – – – 3*2 –

M 8375*1 [Y003] DOG signal logic reverse – – – 3*2 –

M 8376*1 [Y003] Zero point signal logic reverse – – – 3*2 –

M 8377*1 [Y003] Interrupt signal logic reverse – – – 3*2 –

[M]8378 [Y003] Positioning instruction activation – – – 3*2 –

M 8379*1 [Y003] Pulse output stop command – – – 3*2 –

RS2 (FNC 87) [ch0] [FX3G/FX3GC] (Refer to Data Communication Edition for details.) [M]8370 Not used –

[M]8371*1 RS2 (FNC 87) [ch0] instruction: Send wait flag – 3 3 –

M 8372*1 RS2 (FNC 87) [ch0] instruction: Send request – 3 3 – – D8372 –

M 8373*1 RS2 (FNC 87) [ch0] instruction: Receive complete flag – 3 3 – – D8373 –

[M]8374 to [M]8378 Not used –

M 8379 RS2 (FNC 87) [ch0] instruction: Time-out check flag – 3 3 –

*1. These devices are cleared when the PLC mode switches from RUN to STOP or when the RS2 instruction [ch0] turns OFF.

*2. Available only when two FX3U-2HSY-ADP units are connected to an FX3U PLC.

High-Speed Counter Function (Refer to Subsection 4.7.5 and 4.8.5 for details.)

[M]8380*3 Operation status of C235, C241, C244, C246, C247, C249, C251, C252, and C254 – – – 3 3 –

[M]8381*3 Operation status of C236 – – – 3 3 –

[M]8382*3 Operation status of C237, C242, and C245 – – – 3 3 –

[M]8383*3 Operation status of C238, C248, C248 (OP), C250, C253, and C255 – – – 3 3 –

[M]8384*3 Operation status of C239 and C243 – – – 3 3 –

[M]8385*3 Operation status of C240 – – – 3 3 –

[M]8386*3 Operation status of C244 (OP) – – – 3 3 –

[M]8387*3 Operation status of C245 (OP) – – – 3 3 –

[M]8388 Contact for high-speed counter function change 3 – M 8389 External reset input logic reverse – – – 3 3 – M 8390 Function changeover device for C244 – – – 3 3 – M 8391 Function changeover device for C245 – – – 3 3 –

M 8392 Function changeover device for C248 and C253 –

*3. Cleared when PLC switches from STOP to RUN.

Mitsubishi Electronics MELSEC FX3S — 37. Operation of Special Devices (M8000 -, D8000 -) diagram (page 840)
Fig. 810 · 37. Operation of Special Devices (M8000 -, D8000 -)

Interrupt Program [M]8393 Contact for delay time setting – – – 3 3 D8393 –

[M]8394 HCMOV (FNC189): Drive contact for interrupt program – – – 3 3 –

[M]8395 Function changeover device for C254 – 3 3 – [M]8396 Not used – [M]8397 – Ring Counter

(in units of 1ms, 32 bits)*4 3 D8398,

[M]8399 Not used –

*4. 1ms ring counter (D8399, D8398) will operate after M8398 turns ON.

Show 5 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device
Page 841 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 841 · click to enlarge
Page 841

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Operation and function

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

RS2 (FNC 87) [ch1] (Refer to Data Communication Edition for details.) [M]8400 Not used –

[M]8401*1 RS2 (FNC 87) [ch1] Send wait flag 3 –

FNC280-FNC289 High-Speed Processing 2

M 8402*1 RS2 (FNC 87) [ch1] Send request 3 D8402 –

M 8403*1 RS2 (FNC 87) [ch1] Receive complete flag 3 D8403 –

[M]8404 RS2 (FNC 87) [ch1] Carrier detection flag 3 –

[M]8405 RS2 (FNC 87) [ch1] Data set ready (DSR) flag 3*3 3*3 –

[M]8406 to [M]8408 Not used – M 8409 RS2 (FNC 87) [ch1] Time-out check flag 3 – RS2 (FNC 87) [ch2] and Computer Link [ch2] (Refer to the Data Communication Edition for details.) [M]8410 to [M]8420 Not used –

FNC290-FNC299 Extension File Register Control

[M]8421*2 RS2 (FNC 87) [ch2] Send wait flag – 3 –

M 8422*2 RS2 (FNC 87) [ch2] Send request – 3 D8422 –

M 8423*2 RS2 (FNC 87) [ch2] Receive complete flag – 3 D8423 –

[M]8424 RS2 (FNC 87) [ch2] Carrier detection flag – 3 –

[M]8425 RS2 (FNC 87) [ch2] Data set ready (DSR) flag – 3 3 3*3 3*3 –

FNC300-FNC305 FX 3U -CF-ADP

[M]8426 Computer link [ch2] Global ON – 3

–

[M]8427 Computer link [ch2] On-demand send processing – 3 –

D8427 D8428 D8429

M 8428 Computer link [ch2] On-demand error flag – 3 –

Computer link [ch2] On-demand Word / Byte changeover RS2 (FNC 87) [ch2] Time-out check flag

M 8429

– 3 –

*1. These devices are cleared when the PLC mode switches from RUN to STOP or when the RS2 instruction [ch1] turns OFF.

*2. These devices are cleared when the PLC mode switches from RUN to STOP or when the RS2 instruction [ch2] turns OFF.

*3. Available in Ver. 2.30 or later.

MODBUS communication [ch1] (Refer to MODBUS Communication Edition for details.)

[M]8401 MODBUS request in process 3 3*4 3 3*5 3*5 –

[M]8402 MODBUS communication error 3 3*4 3 3*5 3*5 D8402 –

[M]8403 MODBUS communication error (latched) 3 3*4 3 3*5 3*5 D8403 –

[M]8404 Listen only mode – – – 3*5 3*5 –

[M]8405 to [M]8407 Not used –

[M]8408 Retry 3 3*4 3 3*5 3*5 –

[M]8409 Timeout 3 3*4 3 3*5 3*5 –

[M]8410 Not used – MODBUS communication [ch2] (Refer to MODBUS Communication Edition for details.)

[M]8421 MODBUS request in process – 3*4 3 3*5 3*5 –

[M]8422 MODBUS communication error – 3*4 3 3*5 3*5 D8422 –

[M]8423 MODBUS communication error (latched) – 3*4 3 3*5 3*5 D8423 –

[M]8424 Listen only mode – – – 3*5 3*5 –

[M]8425 to [M]8427 Not used –

[M]8428 Retry – 3*4 3 3*5 3*5 –

A

[M]8429 Timeout – 3*4 3 3*5 3*5 –

[M]8430 Not used – MODBUS communication [ch1, ch2] (Refer to MODBUS Communication Edition for details.)

M 8411 MODBUS configuration request flag 3 3*4 3 3*5 3*5 –

*4. Available in Ver. 1.30 or later.

*5. Available in Ver. 2.40 or later.

B

Show 11 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 842 of the Mitsubishi Electronics MELSEC FX3S user manual — 37. Operation of Special Devices (M8000 -, D8000 -)
Page 842 · click to enlarge
Page 842

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

name Operation and function

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

FX3U-CF-ADP [ch1] (Refer to CF-ADP Manual for details.) [M]8400 to [M]8401 Not used –

[M]8402 CF-ADP instruction executing – – – 3*1 3*1 –

[M]8403 Not used –

[M]8404 CF-ADP unit ready – – – 3*1 3*1 –

[M]8405 CF card mount status – – – 3*1 3*1 –

[M]8406 to [M]8409 Not used –

M 8410 CF-ADP status renewal stop – – – 3*1 3*1 –

[M]8411 to [M]8417 Not used –

M 8418 CF-ADP instruction error*2 – – – 3*1 3*1 –

[M]8419 Not used – FX3U-CF-ADP [ch2] (Refer to CF-ADP Manual for details.) [M]8420 to [M]8421 Not used –

[M]8422 CF-ADP instruction executing – – – 3*1 3*1 –

[M]8423 Not used –

[M]8424 CF-ADP unit ready – – – 3*1 3*1 –

[M]8425 CF card mount status – – – 3*1 3*1 –

[M]8426 to [M]8429 Not used –

M 8430 CF-ADP status renewal stop – – – 3*1 3*1 –

[M]8431 to [M]8437 Not used –

M 8438 CF-ADP instruction error*2 – – – 3*1 3*1 –

[M]8439 Not used –

*1. Available in Ver. 2.61 or later. *2. Cleared when PLC switches from STOP to RUN.

FX3U-ENET-ADP [ch1] (Refer to ENET-ADP Manual for details.) [M]8400 to [M]8403 Not used –

[M]8404 FX3U-ENET-ADP unit ready 3 3*4 3*4 3*5 3*5 –

[M]8405 Not used –

[M]8406*3 Time setting execution 3 3*4 3*4 3*5 3*5 –

[M]8407 to [M]8410 Not used –

M 8411*3 Execute time setting 3 3*4 3*4 3*5 3*5 –

[M]8412 to [M]8415 Not used – FX3U-ENET-ADP [ch2] (Refer to ENET-ADP Manual for details.) [M]8420 to [M]8423 Not used –

[M]8424 FX3U-ENET-ADP unit ready – 3*4 3*4 3*5 3*5 –

[M]8425 Not used –

[M]8426*3 Time setting execution – 3*4 3*4 3*5 3*5 –

[M]8427 to [M]8430 Not used –

M 8431*3 Execute time setting – 3*4 3*4 3*5 3*5 –

[M]8432 to [M]8435 Not used – FX3U-ENET-ADP [ch1, ch2] (Refer to ENET-ADP Manual for details.) [M]8490 to [M]8491 Not used –

M 8492 IP address storage area write request 3 3*6 3*6 –

[M]8493 IP address storage area write completion 3 3*6 3*6 –

[M]8494 IP address storage area write error 3 3*6 3*6 –

M 8495 IP address storage area clear request 3 3*6 3*6 –

[M]8496 IP address storage area clear completion 3 3*6 3*6 –

[M]8497 IP address storage area clear error 3 3*6 3*6 –

[M]8498 IP address change function enable flag 3 3*6 3*6 –

*3. Used when the SNTP function setting is set to "Use" in the time setting parameters. *4. Available in Ver. 2.00 or later. *5. Available in Ver. 3.10 or later. *6. Available in Ver. 2.10 or later.

Show 5 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device
Page 843 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 843 · click to enlarge
Page 843

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Operation and function

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Error Detection (Refer to Chapter 38 for details.) [M]8430 to [M]8437 Not used –

M 8438 Serial communication error 2 [ch2]*1 – 3 D8438 –

[M]8439 to [M]8448 Not used –

FNC280-FNC289 High-Speed Processing 2

[M]8449 Special block error flag – 3*2 D8449

[M]8450 to [M]8459 Not used –

*1. Cleared when PLC power supply is turned from OFF to ON. *2. Available in Ver. 2.20 or later.

Positioning [FX3S/FX3G/FX3GC/FX3U/FX3UC] (Refer to Positioning Control Edition for details.)

M 8460 DVIT (FNC151) instruction [Y000] User interrupt input command – – – 3 3*3 D8336 –

FNC290-FNC299 Extension File Register Control

M 8461 DVIT (FNC151) instruction [Y001] User interrupt input command – – – 3 3*3 D8336 –

M 8462 DVIT (FNC151) instruction [Y002] User interrupt input command – – – 3 3*3 D8336 –

M 8463 DVIT (FNC151) instruction [Y003] User interrupt input command – – – 3*4 3*3 D8336 –

DSZR (FNC150), ZRN (FNC156) instructions [Y000] Clear signal device specification function enabled

FNC300-FNC305 FX 3U -CF-ADP

M 8464

DSZR (FNC150), ZRN (FNC156) instructions [Y001] Clear signal device specification function enabled

M 8465

DSZR (FNC150), ZRN (FNC156) instructions [Y002] Clear signal device specification function enabled

M 8466

DSZR (FNC150), ZRN (FNC156) instructions [Y003] Clear signal device specification function enabled

M 8467

*3. Available in Ver. 2.20 or later. *4. Available only when two FX3U-2HSY-ADP adapters are connected to an FX3U PLC.

Error Detection [M]8468 to [M]8488 Not used –

[M]8487 USB communication error 3 – D8487 –

[M]8488 Not used –

[M]8489 Special parameter error 3 3*6 3*6 3*5 3*5 D8489 –

[M]8490 to [M]8511 Not used –

*5. Available in Ver. 3.10 or later. *6. Available in Ver. 2.00 or later.

A

B

Show 11 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 844 of the Mitsubishi Electronics MELSEC FX3S user manual — ON
Page 844 · click to enlarge
Page 844

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

37.1.2 Special Data Register (D8000 to D8511)

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Default value is shown on the right (in 1ms steps) (Writes from system ROM at power ON) Value overwritten by program is valid after END or WDT instruction execution.

D 8000 Watchdog timer

200 – 200

→Refer to Subsection 37.2.2.

[D]8001 PLC type and system version

2 4 1 0 0

Version 1.00

Indicated on the right

  • 2...2K steps
  • 4...4K steps
  • 8...8K steps
  • If 16K steps or more "8" is written to D8002, and "16", "32" or "64" is written to D8102.

Type of internal memory/RAM/EEPROM/ EPROM cassette or ON/OFF status of protect switch is stored

value Type of memory Protect

00H RAM memory cassette –

01H EPROM memory cassette –

3 – 3

02H EEPROM memory cassette or flash memory cassette

OFF

0AH EEPROM memory cassette or flash memory cassette

ON

10H Built-in memory in PLC –

8 0 6 0

[D]8004 Error number M 3 M8004 3

8060 to 8068 (when M8004 is ON)

(in 0.1-V units)

[D]8005 Battery voltage – 3 M8005 – – – 3 3

Battery voltage present value (Example3.0V)
  • Default:
  • FX 2N /FX 2NC PLCs: 3.0V (in 0.1-V units)
  • FX 3G /FX 3GC /FX 3U /FX 3UC PLCs: 2.7V (in 0.1-V units) (Writes from system ROM at power ON)

[D]8006 Low battery voltage detection level

– 3 M8006 – – – 3 3

*1. The corresponding special data register D8101 is available only in FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs. No corresponding device is available in FX1S/FX1N/FX1NC/FX2N/FX2NC PLCs.

*2. "4" is displayed even when the memory capacity is set to 16K steps in the parameter setting.

Show 10 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · PLC Status · [D]8002 Memory capacity · Present · switch · [D]8003 Memory type
Page 845 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 845 · click to enlarge
Page 845

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

[D]8007 Momentary power failure count

Operation frequency of M8007 is stored. Cleared at power-off. – – – 3 3 M8007 – – – 3 3

FNC280-FNC289 High-Speed Processing 2

Default*1

D8008 Power failure detection

  • FX 3U /FX 2N PLCs: 10 ms (AC power supply type)
  • FX 3UC /FX 2NC PLCs: 5 ms (DC power supply type)

– – – 3 3 M8008 – – – 3 3

[D]8009 24V DC failed device

Lowest input device number of the I/O extension units in which 24 V DC power has failed

– 3 – 3 – M8009 – – – 3 3

FNC290-FNC299 Extension File Register Control

*1. The power failure detection time in FX2N/FX2NC PLCs is as follows. For FX3U/FX3UC PLCs, refer to Subsection 37.2.4. - 10ms for FX2N PLC used with a 100V AC power supply system. D8008 is set to 10ms by default. - 100ms maximum for FX2N PLC used with a 200V AC power supply system. D8008 can be set ranging from 10 to 100 ms. - 5ms for FX2N PLC used with a DC power supply type. Write "K-1" to D8008 for correction. - 5ms for FX2NC PLC used with a DC power supply type. System writes "K-1" to D8008 for correction. Do not make any change in a sequence program.

FNC300-FNC305 FX 3U -CF-ADP

Accumulated instruction-execution time from step 0 (in 0.1-ms units)

[D]8010 Present scan time

→Refer to Subsection 37.2.5. 3 Same as on

3 Indicated value includes waiting

Minimum value of scan time (in 0.1-ms units)

[D]8011 Minimum scan time

time of constant scan operation

→Refer to Subsection 37.2.5.

(when M8039 is activated).

[D]8012 Maximum scan time

Maximum value of scan time (in 0.1-ms units)

→Refer to Subsection 37.2.5.

0 to 59 seconds (for real time clock)

3 – 3*2

→Refer to Subsection 37.2.7.

0 to 59 minutes (for real time clock)

3 – 3*2

→Refer to Subsection 37.2.7.

0 to 23 hours (for real time clock)

3 – 3*2

→Refer to Subsection 37.2.7.

1 to 31 days (for real time clock)

3 – 3*2

→Refer to Subsection 37.2.7.

1 to 12 months (for real time clock)

3 – 3*2

→Refer to Subsection 37.2.7.

2 digits of year data (0 to 99) (for real time clock)

3 – 3*2

→Refer to Subsection 37.2.7.

A

0 (Sunday) to 6 (Saturday) (for real time clock)

3 – 3*2

→Refer to Subsection 37.2.7.

*2. A memory board having the real time clock function is required in FX2NC PLC.

B

Show 33 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · PLC Status · Clock · SFC•STL Programming · 3 Same · 3 Same · 3 Same · 3 Same · as on · as on · as on · as on · the right · the right · the right · the right · the right · Interrupt Function · D8013 Second data · D8014 Minute data · Special Device · D8015 Hour data · D8016 Day data · Error Code · D8017 Month data · D8018 Year data · D8019 Day-of-the-week data · Version Up Information · Execution Times
Page 846 of the Mitsubishi Electronics MELSEC FX3S user manual — 37.1.2 Special Data Register (D8000 to D8511)
Page 846 · click to enlarge
Page 846

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

Mitsubishi Electronics MELSEC FX3S — 37.1.2 Special Data Register (D8000 to D8511) diagram (page 846)
Fig. 811 · 37.1.2 Special Data Register (D8000 to D8511)

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

3 – 3

–

[D]8028 Value of Z0 (Z) register*2 3 – 3

[D]8029 Value of V0 (V) register*2 3 – 3

*1. In FX3G/FX3GC/FX1N/FX1NC PLCs the input filter can be adjusted in X000 to X007.

*2. The values of Z1 to Z7 and V1 to V7 are stored in D8182 to D8195.

Mitsubishi Electronics MELSEC FX3S — 37.1.2 Special Data Register (D8000 to D8511) diagram (page 846)
Fig. 812 · 37.1.2 Special Data Register (D8000 to D8511)

Analog Volume [FX3S/FX3G/FX1S/FX1N]

[D]8030 Value of analog volume VR1 (Integer from 0 to 255) 3*3 3 – 3 3 – – –

[D]8031 Value of analog volume VR2 (Integer from 0 to 255) 3*3 3 – 3 3 – – –

–

Default: 0 ms (in 1 ms steps) (Writes from system ROM at power ON) Can be overwritten by program

3 M8039 3

*3. This function is not supported in the FX3S-30M /E -2AD PLC.

Page 847 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 847 · click to enlarge
Page 847

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

3

3

ON state number 1

FNC280-FNC289 High-Speed Processing 2

ON state number 2 3

ON state number 3

The smallest number out of active state ranging from S0 to S899 and S1000 to

ON state number 4 3

S4095*2 is stored in D8040 and the second- smallest state number is stored in D8041. Active state numbers are then sequentially stored in registers up to D8047 (Max. 8 points).

M8047

FNC290-FNC299 Extension File Register Control

ON state number 5 3

ON state number 6 3

ON state number 7 3

FNC300-FNC305 FX 3U -CF-ADP

ON state number 8 3

[D]8048 Not used –

When M8049 is ON, the smallest number out of active annunciator relay ranging from S900 to S999 is stored in D8049.

On state minimum number

– 3 M8049 – – – 3 3

[D]8050 to [D]8059 Not used –

*1. Executed at END instruction.

*2. S1000 to S4095 are available only in FX3G/FX3GC/FX3U/FX3UC PLCs.

Error Detection (Refer to Chapter 38 for details.)

If the unit or block corresponding to a programmed I/O number is not actually loaded, M8060 is set to ON and the first device number of the erroneous block is written to D8060.

ample: If X020 is unconnected.

Example: If X020 is unconnected.

– 3 M8060 – – – 3 3

1 0 2 0

1 0 2 0

1. Input X 0: Output Y
1. Input X 0: Output Y

[D]8061 Error code for PLC hardware error 3 M8061 – – – 3 3

Error code for PLC/PP communication error 3 M8062 3

Error code for serial communication error 0 [ch0]*4 – 3 3 – – M8062 –

[D]8063*5 Error code for serial communication error 1 [ch1] 3 M8063

[D]8064 Error code for parameter error 3 M8064 3

[D]8065 Error code for syntax error 3 M8065 3

[D]8066 Error code for ladder error 3 M8066 3

[D]8067*6 Error code for operation error 3 M8067 3

D 8068 Operation error step number latched 3*7 3*7 M8068 3

A

[D]8069*6 Error step number of M8065 to M8067 3*8 3*8 M8065 to

M8067 3

*3. 10 to 337 in FX3U/FX3UC/FX2N/FX2NC PLCs, and 10 to 177 in FX3G/FX3GC PLCs. *4. Cleared when PLC power supply is turned from OFF to ON. *5. The operation varies according to PLC: - Cleared in an FX1S/FX1N/FX1NC/FX2N/FX2NC when PLC switches from STOP to RUN. - Cleared in an FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs when PLC power supply from OFF to ON. *6. Cleared when PLC switches from STOP to RUN. *7. In case of 32K steps or more, step number is stored in [D8313, D8312]. *8. In case of 32K steps or more, step number is stored in [D8315, D8314].

B

Show 18 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · Stepladder and Annunciator · SFC•STL Programming · Interrupt Function · BCD converted value · BCD converted value · Device number · Device number · *3 · *3 · Special Device · Error Code · Version Up Information · Execution Times
Page 848 of the Mitsubishi Electronics MELSEC FX3S user manual — M8079
Page 848 · click to enlarge
Page 848

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Parallel Link (Refer to Data Communication Edition for details.)

[D]8070 Parallel link error time-out check time: 500 ms 3 – 3

–

Sampling Trace*1 [FX3U/FX3UC/FX2N/FX2NC]

– – – 3 3

– – – 3 3

These devices are occupied by the PLC system when the sampling trace function is used in a connected personal computer*1.

M8079

*1. The sampling trace devices are used by peripheral equipment.

Show 7 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · Not used · M8075 to
Page 849 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 849 · click to enlarge
Page 849

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Pulse width/Pulse period measurement [FX3G/FX3GC] (Refer to Section 36.8 for details.)

D 8074*1 Lower [X000]

– 3*2 3 – –

–

Ring counter value for rising edge (1/6 µs unit)

D 8075*1 Upper –

FNC280-FNC289 High-Speed Processing 2

D 8076*1 Lower [X000]

– 3*2 3 –

Ring counter value for falling edge (1/6 µs unit)

M8076 M8080

D 8077*1 Upper –

D 8078*1 Lower [X000]

– 3*2 3 –

Pulse width/Pulse period (10 µs unit)

D 8079*1 Upper –

D 8080*1 Lower [X001]

FNC290-FNC299 Extension File Register Control

– 3*2 3 – –

–

Ring counter value for rising edge (1/6 µs unit)

D 8081*1 Upper –

D 8082*1 Lower [X001]

– 3*2 3 –

M8077 M8081

Ring counter value for falling edge (1/6 µs unit)

D 8083*1 Upper –

D 8084*1 Lower [X001]

– 3*2 3 –

FNC300-FNC305 FX 3U -CF-ADP

Pulse width/Pulse period (10 µs unit)

D 8085*1 Upper –

D 8086*1 Lower [X003]

– 3*2 3 – –

–

Ring counter value for rising edge (1/6 µs unit)

D 8087*1 Upper –

D 8088*1 Lower [X003]

– 3*2 3 –

M8078 M8082

Ring counter value for falling edge (1/6 µs unit)

D 8089*1 Upper –

D 8090*1 Lower [X003]

– 3*2 3 –

Pulse width/Pulse period (10 µs unit)

D 8091*1 Upper –

D 8092*1 Lower [X004]

– 3*2 3 – –

–

Ring counter value for rising edge (1/6 µs unit)

D 8093*1 Upper –

D 8094*1 Lower [X004]

– 3*2 3 –

M8079 M8083

Ring counter value for falling edge (1/6 µs unit)

D 8095*1 Upper –

D 8096*1 Lower [X004]

– 3*2 3 –

Pulse width/Pulse period (10 µs unit)

D 8097*1 Upper –

[D]8098 Not used –

*1. Cleared when PLC switches from STOP to RUN.

*2. Available in Ver. 1.10 or later.

D 8099 Up-operation high-speed ring counter of 0 to

32,767 (in units of 0.1ms, 16-bit)*3 – – – 3 3 M8099 – – – 3 3

[D]8100 Not used –

*3. The 0.1ms high-speed ring counter D8099 will operate after END instruction is executed while M8099 is ON.

A

B

Show 12 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · SFC•STL Programming · Interrupt Function · Special Device · High-Speed Ring Counter · Error Code · Version Up Information · Execution Times
Page 850 of the Mitsubishi Electronics MELSEC FX3S user manual — M8129
Page 850 · click to enlarge
Page 850

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

Mitsubishi Electronics MELSEC FX3S — 37.1.2 Special Data Register (D8000 to D8511) diagram (page 850)
Fig. 813 · 37.1.2 Special Data Register (D8000 to D8511)

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

28 26 26 16 16 –

2 2K steps 4 4K steps 8 8K steps 16 16K steps 32 32K steps 64 64K steps

[D]8103 Not used –

[D]8104 Identity code for function extension memory –

[D]8105 Version of function extension memory (Version 1.00 = 100) – 3*3 3*3

[D]8106 Not used –

[D]8107 Number of registered device comments – – – 3 3 M8107 –

[D]8108 Number of special function units/blocks connected – 3 –

*1. "4" is displayed even when the memory capacity is set to 16K steps in the parameter setting.

*2. When loading FX3U-FLROM-16.

*3. Available in Ver. 3.00 or later.

Output Refresh Error (Refer to Chapter 38 for details.)

[D]8109 Y number where output refresh error occurs – 3 M8109 – – – 3 3

–

Expansion Board Dedicated to FX1S/FX1N

[D]8112 FX1N-2AD-BD: Digital value of ch1 – M8112 3 3 – – –

[D]8113 FX1N-2AD-BD: Digital value of ch2 – M8113 3 3 – – –

D 8114 FX1N-1DA-BD: Digital value to be output – M8114 3 3 – – –

[D]8115 to [D]8119 Not used –

RS (FNC 80) and Computer Link [ch1] (Refer to Data Communication Edition for details.)

RS (FNC 80) instruction and computer link [ch1] Communication format setting

3 – 3

D 8121*4 Computer link [ch1] Station number setting 3 – 3

[D]8122*5 RS (FNC 80) instruction: Remaining points of transmit data 3 M8122 3

[D]8123*5 RS (FNC 80) instruction: Monitoring receive data points 3 M8123

D 8124 RS (FNC 80) instruction: Header

<DefaultSTX> 3 3 3 3 3 – 3 3 3 3 3

D 8125 RS (FNC 80) instruction: Terminator

<DefaultETX> 3 3 3 3 3 – 3 3 3 3 3

[D]8126 Not used –

Computer link [ch1] Specification of on-demand head device register

3

3

Computer link [ch1] Specification of on-demand data length register

3

M8129

D 8129*4 RS (FNC 80) instruction, computer link [ch1] Time-out time setting 3

*4. Latch (battery or EEPROM backed) device. For details on backup against power failure, refer to Section 2.6.

*5. Cleared when the PLC switches from RUN to STOP.

Not used · M8126 to

Page 851 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 851 · click to enlarge
Page 851

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

High-Speed Counter Comparison, High-Speed Table, and Positioning [Positioning is supported in FX3S/FX3G/FX3GC/FX1S/FX1N/FX1NC]

[D]8130 HSZ (FNC 55) instruction: High-speed comparison table counter – – – 3 3 M8130 – – – 3 3

FNC280-FNC289 High-Speed Processing 2

[D]8131 HSZ (FNC 55) and PLSY (FNC 57) instructions: Speed pattern table counter – – – 3 3 M8132 – – – 3 3

[D]8132 Lower HSZ (FNC 55) and PLSY (FNC 57)

instructions: Speed pattern frequency – – – 3 3 M8132 – – – 3 3 [D]8133 Upper

[D]8134 Lower HSZ (FNC 55) and PLSY (FNC 57)

instructionsNumber of target pulses for speed pattern

– – – 3 3 M8132 – – – 3 3 [D]8135 Upper

FNC290-FNC299 Extension File Register Control

D 8136 Lower PLSY (FNC 57), PLSR (FNC 59)

3 – 3 D 8137 Upper

instructionsAccumulated total number of pulses output to Y000 and Y001
[D]8138 HSCT (FNC280) instructionTable counter – – – 3 3 M8138 – – – – –

HSCS (FNC 53), HSCR (FNC 54), HSZ (FNC 55), and HSCT (FNC280) instructions: Number of instructions being executed

FNC300-FNC305 FX 3U -CF-ADP

– – – 3 3 M8139 –

D 8140 Lower Accumulated number of pulses output

3 – 3 D 8141 Upper

from Y000 for PLSY (FNC 57) and PLSR (FNC 59) instructions.

D 8142 Lower Accumulated number of pulses output

3 – 3 D 8143 Upper

from Y001 for PLSY (FNC 57) and PLSR (FNC 59) instructions.

[D]8144 Not used –

ZRN (FNC156), DRVI (FNC158), and DRVA (FNC159) instructions: Bias speed Default: 0

– 3 3 3 – –

D 8146 Lower ZRN (FNC156), DRVI (FNC158),

and DRVA (FNC159) instructionsMaximum speed • Default in FX 1S /FX 1N : 100000

– 3 3 3*1 – –

  • Default in FX 1NC : 100000 *1

ZRN (FNC156), DRVI (FNC158), and DRVA (FNC159) instructions: Acceleration/deceleration time Default: 100

– 3 3 3 – –

[D]8149 Not used –

*1. Must be changed to 10000 or less by PLC program.

A

B

Show 12 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · SFC•STL Programming · Interrupt Function · D 8147 Upper · Special Device · Error Code · Version Up Information · Execution Times
Page 852 of the Mitsubishi Electronics MELSEC FX3S user manual — 37.1.2 Special Data Register (D8000 to D8511)
Page 852 · click to enlarge
Page 852

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Inverter Communication Function (Refer to Data Communication Edition for details.)

D 8150*1 Response wait time of inverter communication [ch1] 3 3*4 3 3 3 –

Step number of instruction during inverter communication [ch1] Default: -1

3 3*4 3 3 3 M8151 –

[D]8152*2 Error code for inverter communication [ch1] 3 3*4 3 3 3 M8152 –

Inverter communication error step number latched [ch1] Default: -1

3 3*4 3 3 3 M8153 –

Parameter number when error occurs during IVBWR (FNC274) instruction [ch1] Default: -1

– – – 3 3 M8154 –

Response waiting time of EXTR (FNC180) instruction – 3*3 3*3

D 8155*1 Response wait time of inverter communication [ch2] – 3*4 3 3 3 –

[D]8155 Step number during communication of EXTR (FNC180) instruction – M8155 – – – 3*3 3*3

Step number of instruction during inverter communication [ch2] Default: -1

– 3*4 3 3 3 M8156 –

Error code for EXTR (FNC180) instruction – M8156 – – – 3*3 3*3

[D]8157*2 Error code for inverter communication [ch2] – 3*4 3 3 3 M8157 –

Error step (latched) for EXTR (FNC180) instruction Default: -1

– M8157 – – – 3*3 3*3

Inverter communication error step number latched [ch2] Default: -1

– 3*4 3 3 3 M8158 –

Parameter number when error occurs during IVBWR (FNC274) instruction [ch2] Default: -1

– – – 3 3 M8159 –

*1. Cleared when PLC power supply is turned from OFF to ON.

*2. Cleared when PLC switches from STOP to RUN.

*3. Available in Ver. 3.00 or later.

*4. Available in Ver. 1.10 or later.

Mitsubishi Electronics MELSEC FX3S — 37.1.2 Special Data Register (D8000 to D8511) diagram (page 852)
Fig. 814 · 37.1.2 Special Data Register (D8000 to D8511)

D 8158 FX1N-5DM: Control device (D) Default: -1 – 3 3 – – –

D 8159 FX1N-5DM: Control device (M) Default: -1 – 3 3 – – –

FX1N-BAT [FX1N] (Refer to FX1N-BAT Manual for details.)

Specification of low battery voltage detection flag for the FX1N-BAT Default: -1

– 3 – – –

Show 5 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device
Page 853 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 853 · click to enlarge
Page 853

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

–

FNC280-FNC289 High-Speed Processing 2

D 8164 FROM (FNC 78), TO (FNC 79) instructions: Specification of transfer points – M8164 – – – 3*1 3

[D]8165 Not used –

[D]8166 Special block error condition – – – 3*5 3*5 –

FNC290-FNC299 Extension File Register Control

–

value change Read Write

FNC300-FNC305 FX 3U -CF-ADP

2nd keyword is not set.

H**00

3*3

H**10

*2 Write protection 3 – 3 3

3*4 –

H**11

*2 Read/write protection – – 3 3

All online operation protection

H**12

–

H**20

*2 Keyword cancel 3

*1. Available in Ver. 2.00 or later.

*2. "**" indicates areas used by the system.

*3. The accessibility is restricted depending on the keyword setting status.

*4. Available in Ver. 2.20 or later.

*5. Available in Ver. 3.00 or later. For details, refer to Section 38.4 Error Code List and Action.

N:N Network (setting) (Refer to Data Communication Edition for details.)

–

[D]8173 Station number 3 – 3*6 3

[D]8174 Total number of slave stations 3 – 3*6 3

[D]8175 Refresh range 3 – 3*6 3

D 8176 Station number setting 3

3*6 3

D 8177 Total slave station number setting 3*6 3

D 8178 Refresh range setting 3*6 3

M8038

A

D 8179 Retry count setting 3*6 3

D 8180 Comms time-out setting 3*6 3

[D]8181 Not used –

*6. Available in Ver. 2.00 or later.

B

Show 25 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · Advanced Function · Not used · Not used · Access restriction status · Pres- · Access restriction · Program Monito- · Present · ent value · ring · status · *2 · SFC•STL Programming · *2 · Interrupt Function · Special Device · Not used · Error Code · Version Up Information · Execution Times
Page 854 of the Mitsubishi Electronics MELSEC FX3S user manual — M8191
Page 854 · click to enlarge
Page 854

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Index Register Z1 to Z7 and V1 to V7

[D]8182 Value of Z1 register 3 – 3

[D]8183 Value of V1 register 3 – 3

[D]8184 Value of Z2 register 3 – 3

[D]8185 Value of V2 register 3 – 3

[D]8186 Value of Z3 register 3 – 3

[D]8187 Value of V3 register 3 – 3

[D]8188 Value of Z4 register 3 – 3

[D]8189 Value of V4 register 3 – 3

[D]8190 Value of Z5 register 3 – 3

[D]8191 Value of V5 register 3 – 3

[D]8192 Value of Z6 register 3 – 3

[D]8193 Value of V6 register 3 – 3

[D]8194 Value of Z7 register 3 – 3

[D]8195 Value of V7 register 3 – 3

[D]8196 to [D]8199 Not used –

N:N Network (monitoring) (Refer to Data Communication Edition for details.)

[D]8200 Not used –

[D]8201*1 Current link scan time 3 – (D201) 3 3 3*2 3

[D]8202*1 Maximum link scan time 3 – (D202) 3 3 3*2 3

[D]8203*1 Number of communication error at master station 3

[D]8204*1 Number of communication error at slave station No.1 3 (D204) 3 3 3*2 3

[D]8205*1 Number of communication error at slave station No.2 3 (D205) 3 3 3*2 3

[D]8206*1 Number of communication error at slave station No.3 (D206) 3 3 3*2 3

[D]8207*1 Number of communication error at slave station No.4 3 (D207) 3 3 3*2 3

[D]8208*1 Number of communication error at slave station No.5 3 (D208) 3 3 3*2 3

[D]8209*1 Number of communication error at slave station No.6 3 (D209) 3 3 3*2 3

[D]8210*1 Number of communication error at slave station No.7 3 (D210) 3 3 3*2 3

M8191

[D]8211*1 Code of communication error at master station 3 (D211) 3 3 3*2 3

[D]8212*1 Code of communication error at slave station No.1 3 (D212) 3 3 3*2 3

[D]8213*1 Code of communication error at slave station No.2 3 (D213) 3 3 3*2 3

[D]8214*1 Code of communication error at slave station No.3 (D214) 3 3 3*2 3

[D]8215*1 Code of communication error at slave station No.4 3 (D215) 3 3 3*2 3

[D]8216*1 Code of communication error at slave station No.5 3 (D216) 3 3 3*2 3

[D]8217*1 Code of communication error at slave station No.6 3 (D217) 3 3 3*2 3

[D]8218*1 Code of communication error at slave station No.7 3 (D218) 3 3 3*2 3

[D]8219 to [D]8259 Not used –

*1. In FX1S PLC, use numbers shown inside parentheses.

*2. Available in Ver. 2.00 or later.

Show 6 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · M8183 to
Page 855 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 855 · click to enlarge
Page 855

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Analog Special Adapter [FX3U/FX3UC] (Refer to Subsection 37.2.19 for applicability of each analog special adapter.)

D 8260 to D 8269 1st special adapter*1 – – – 3 3*2 –

D 8270 to D 8279 2nd special adapter*1 – – – 3 3*2 –

FNC280-FNC289 High-Speed Processing 2

D 8280 to D 8289 3rd special adapter*1 – – – 3 3*2 –

D 8290 to D 8299 4th special adapter*1 – – – 3 3*2 –

Analog Special Adapter [FX3S/FX3G/FX3GC], Analog Expansion Board [FX3S/FX3G] (Refer to Subsection 37.2.18 for applicability of each analog special adapter and analog expansion board)

D 8260 to D 8269 1st expansion board*3 3 3*6 –

FNC290-FNC299 Extension File Register Control

D 8270 to D 8279 2nd expansion board*4*5 – 3*6 –

D 8280 to D 8289 1st special adapter*1 3 3 3 –

D 8290 to D 8299 2nd special adapter*1*5 – 3 3 –

Built-in analog function [FX3S-30M /E -2AD] (Refer to FX3S Hardware Edition for details.)

[D]8270 Ch1 analog input data (0 to 1020) 3*7 –

[D]8271 Ch2 analog input data (0 to 1020) 3*7 –

FNC300-FNC305 FX 3U -CF-ADP

–

D 8274 Averaging time for ch1 (1 to 4095) 3*7 –

D 8275 Averaging time for ch2 (1 to 4095) 3*7 –

–

Error status b0: Ch1 upper over-scale detection b1: Ch2 upper over-scale detection b2: Not used b3: Not used b4: EEPROM error b5: Averaging time setting error

3*7 –

(common ch1 and ch2) b6 to b15: Not used

[D]8279 Model codeK5 3 *7 – – – – – – – – – –

*1. Count the number of connected analog special adapter from the main unit.

*2. Available in Ver. 1.20 or later.

*3. BD1 connector of a FX3G PLC (40-point and 60-point type) or the BD connector of a FX3G PLC (14-point and 24-point type) and FX3S PLC.

*4. Expansion board connected to the BD2 connector of a FX3G PLC (40-point and 60-point type).

*5. Only to FX3G PLC (40-point and 60-point type) can be connected.

*6. Available in Ver. 1.10 or later.

*7. This function is supported only in the FX3S-30M /E -2AD PLC.

A

B

Show 13 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · Not used · Not used · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 856 of the Mitsubishi Electronics MELSEC FX3S user manual — 37.1.2 Special Data Register (D8000 to D8511)
Page 856 · click to enlarge
Page 856

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

Mitsubishi Electronics MELSEC FX3S — 37.1.2 Special Data Register (D8000 to D8511) diagram (page 856)
Fig. 815 · 37.1.2 Special Data Register (D8000 to D8511)

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Display Module Function (FX3G-5DM, FX3U-7DM) (Refer to Hardware Edition Manual of PLC main unit used for details.)

D 8300 Control device (D) for display module Default: K-1 – 3*1 – 3 3 –

D 8301 Control device (M) for display module Default: K-1 – 3*1 – 3 3 –

Language display setting JapaneseK0 English: Other than K0

– 3*1 – 3 3 –

D 8303 LCD contrast setting value Default: K0 – 3*1 – 3 3 –

–

*1. Available in Ver. 1.10 or later.

*2. Latch (battery or EEPROM backed) device. For details on backup against power failure, refer to Section 2.6.

Mitsubishi Electronics MELSEC FX3S — 37.1.2 Special Data Register (D8000 to D8511) diagram (page 856)
Fig. 816 · 37.1.2 Special Data Register (D8000 to D8511)

– – – 3 3 – [D]8311 Upper

Syntax, Circuit, Operation, or Unconnected I/O Designation Error Step Number (Refer to Chapter 38 for details.)

(32-bit) – – – 3 3 M8068 – D 8313 Upper

[D]8314*3 Lower Error step number of M8065 to M8067

M8067 – [D]8315*3 Upper

– – – 3 3 M8316 – [D]8317 Upper

an unconnected I/O number (directly or indirectly using index register)

[D]8318 BFM initialization function: Error unit number – – – 3 3*4 M8318 –

[D]8319 BFM initialization function: Error BFM number – – – 3 3*4 M8318 –

[D]8320 to [D]8328 Not used –

*3. Cleared when PLC switches from STOP to RUN.

*4. Available in Ver. 2.20 or later.

Page 857 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 857 · click to enlarge
Page 857

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Timing Clock (Refer to Section 24.3 for details.) and Positioning [FX3S/FX3G/FX3GC/FX3U/FX3UC] (Refer to Positioning Control Edition for details.)

[D]8329 Not used –

FNC280-FNC289 High-Speed Processing 2

[D]8330 DUTY (FNC186) instruction: Scan counting for timing clock output 1 – – – 3 3*1 –

[D]8331 DUTY (FNC186) instruction: Scan counting for timing clock output 2 – – – 3 3*1 –

[D]8332 DUTY (FNC186) instruction: Scan counting for timing clock output 3 – – – 3 3*1 –

[D]8333 DUTY (FNC186) instruction: Scan counting for timing clock output 4 – – – 3 3*1 –

FNC290-FNC299 Extension File Register Control

[D]8334 DUTY (FNC186) instruction: Scan counting for timing clock output 5 – – – 3 3*1 –

D 8336 DVIT (FNC151) instruction: Specification of interrupt input – – – 3 3*2 M8336 –

[D]8337 to [D]8339 Not used –

FNC300-FNC305 FX 3U -CF-ADP

D 8340 Lower [Y000] Current value register

3 – D 8341 Upper 3

Default0

D 8342 [Y000] Bias speed Default: 0 3 –

D 8343 Lower [Y000] Maximum speed

3 – D 8344 Upper 3

Default100000

D 8345 [Y000] Creep speed Default: 1000 3 –

D 8346 Lower [Y000] Zero return speed

3 – D 8347 Upper 3

Default50000

D 8348 [Y000] Acceleration time Default: 100 3 –

D 8349 [Y000] Deceleration time Default: 100 3 –

D 8350 Lower [Y001] Current value register

3 – D 8351 Upper 3

Default0

D 8352 [Y001] Bias speed Default: 0 3 –

D 8353 Lower [Y001] Maximum speed

3 – D 8354 Upper 3

Default100000

D 8355 [Y001] Creep speed Default: 1000 3 –

D 8356 Lower [Y001] Zero return speed

3 – D 8357 Upper 3

Default50000

D 8358 [Y001] Acceleration time Default: 100 3 –

D 8359 [Y001] Deceleration time Default: 100 3 –

*1. Available in Ver. 2.20 or later.

*2. Available in Ver. 1.30 or later.

A

B

Show 11 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 858 of the Mitsubishi Electronics MELSEC FX3S user manual — 37.1.2 Special Data Register (D8000 to D8511)
Page 858 · click to enlarge
Page 858

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Positioning [FX3G/FX3U/FX3UC] (Refer to Positioning Control Edition for details.)

D 8360 Lower [Y002] Current value register

– 3 – 3 3 – D 8361 Upper – 3 – 3 3

Default0

D 8362 [Y002] Bias speed Default: 0 – 3 – 3 3 –

D 8363 Lower [Y002] Maximum speed

– 3 – 3 3 – D 8364 Upper – 3 – 3 3

Default100000

D 8365 [Y002] Creep speed Default: 1000 – 3 – 3 3 –

D 8366 Lower [Y002] Zero return speed

– 3 – 3 3 – D 8367 Upper – 3 – 3 3

Default50000

D 8368 [Y002] Acceleration time Default: 100 – 3 – 3 3 –

D 8369 [Y002] Deceleration time Default: 100 – 3 – 3 3 –

D 8370 Lower [Y003] Current value register

Default0 – – – 3 *2 – – – – – – –

D 8371 Upper –

D 8372 [Y003] Bias speed Default: 0 – – – 3*2 –

D 8373 Lower [Y003] Maximum speed

Default100000 – – – 3 *2 – – – – – – –

D 8374 Upper –

D 8375 [Y003] Creep speed Default: 1000 – – – 3*2 –

D 8376 Lower [Y003] Zero return speed

Default50000 – – – 3 *2 – – – – – – –

D 8377 Upper –

D 8378 [Y003] Acceleration time Default: 100 – – – 3*2 –

D 8379 [Y003] Deceleration time Default: 100 – – – 3*2 –

[D]8380 to [D]8392 Not used –

RS2 (FNC 87) [ch0] [FX3G/FX3GC PLCs] (Refer to Data Communication Edition for details.)

D 8370 RS2 (FNC 87) [ch0] Communication format setting – 3 3 –

[D]8371 Not used –

[D]8372*1 RS2 (FNC 87) [ch0] Remaining points of transmit data – 3 3 –

[D]8373*1 RS2 (FNC 87) [ch0] Monitoring receive data points – 3 3 –

[D]8374 to [D]8378 Not used –

D 8379 RS2 (FNC 87) [ch0] Time-out time setting – 3 3 –

D 8380 RS2 (FNC 87) [ch0] Header 1 and 2

<DefaultSTX> – 3 3 – – – – – – – –

D 8381 RS2 (FNC 87) [ch1] Header 3 and 4 – 3 3 –

D 8382 RS2 (FNC 87) [ch0] Terminator 1 and 2

<DefaultETX> – 3 3 – – – – – – – –

D 8383 RS2 (FNC 87) [ch0] Terminator 3 and 4 – 3 3 –

[D]8384 RS2 (FNC 87) [ch0] Receive sum (received data) – 3 3 –

[D]8385 RS2 (FNC 87) [ch0] Receive sum (calculated result) – 3 3 –

[D]8386 RS2 (FNC 87) [ch0] Send sum – 3 3 –

[D]8387 to [D]8388 Not used –

[D]8389 Operation mode display [ch0] – 3 3 –

[D]8390 to [D]8392 Not used –

*1. Cleared when the PLC switches from RUN to STOP.

*2. Available only when two FX3U-2HSY-ADP adapters are connected to an FX3U PLC.

Show 5 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device
Page 859 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 859 · click to enlarge
Page 859

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Interrupt Program (Refer to Chapter 36 for details.)

D 8393 Delay time

→Refer to Section 36.4. – – – 3 3 M8393 –

FNC280-FNC289 High-Speed Processing 2

[D]8394 Not used –

Symbolic information storage status and execution program protection status using the block password.

[D]8395 Symbolic Information, Block password status

– – – 3*2 3*2 –

FNC290-FNC299 Extension File Register Control

H**00*1 None None

H**01*1 None Provided

H**10*1 Provided None

H**11*1 Provided Provided

[D]8396 Built-in CC-Link/LT setup information – 3*3 –

FNC300-FNC305 FX 3U -CF-ADP

[D]8397 Not used –

D 8398 Lower Up-operation ring counter of 0 to

2,147,483,647 (in 1-ms units, 32-bit)*4 3 M8398 – D 8399 Upper

*1. "**" indicates areas used by the system.

*2. Available in Ver. 3.00 or later.

*3. Only the FX3UC-32MT-LT-2 is applicable.

*4. 1ms ring counter (D8399, D8398) will operate after M8398 turns ON.

RS2 (FNC 87) [ch1] (Refer to Data Communication Edition for details.)

D 8400 RS2 (FNC 87) [ch1] Communication format setting 3 –

[D]8401 Not used –

RS2 (FNC 87) [ch1] Remaining points of transmit data

3 M8402 –

[D]8403*5 RS2 (FNC 87) [ch1] Monitoring receive data points 3 M8403 –

[D]8404 Not used –

[D]8405 Communication parameter display [ch1] 3 –

[D]8406 to [D]8408 Not used –

D 8409 RS2 (FNC 87) [ch1] Time-out time setting 3 –

D 8410 RS2 (FNC 87) [ch1] Header 1 and 2 3 –

D 8411 RS2 (FNC 87) [ch1] Header 3 and 4 3 –

D 8412 RS2 (FNC 87) [ch1] Terminator 1 and 2 3 –

D 8413 RS2 (FNC 87) [ch1] Terminator 3 and 4 3 –

[D]8414 RS2 (FNC 87) [ch1] Receive sum (received data) 3 –

A

[D]8415 RS2 (FNC 87) [ch1] Receive sum (calculated result) 3 –

[D]8416 RS2 (FNC 87) [ch1] Send sum 3 –

[D]8417 to [D]8418 Not used –

[D]8419 Operation mode display [ch1] 3 –

B

*5. Cleared when the PLC switches from RUN to STOP.

Show 19 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · Symbolic information · Protection of · Present · execution · value · storage · program · Ring Counter · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 860 of the Mitsubishi Electronics MELSEC FX3S user manual — M8429
Page 860 · click to enlarge
Page 860

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

RS2 (FNC 87) [ch2] and Computer Link [ch2] (Refer to Data Communication Edition for details.)

D 8420 RS2 (FNC 87) [ch2] Communication format setting – 3 –

D 8421 Computer link [ch2] Station number setting – 3 –

[D]8422*1 RS2 (FNC 87) [ch2] Remaining points of transmit data – 3 M8422 –

[D]8423*1 RS2 (FNC 87) [ch2] Monitoring receive data points – 3 M8423 –

[D]8424 Not used –

[D]8425 Communication parameter display [ch2] – 3 –

[D]8426 Not used –

Computer link [ch2] Specification of on-demand head device register

– 3

–

Computer link [ch2] Specification of on-demand data length register

– 3 –

M8429

D 8429 RS2 (FNC 87) [ch2], computer link [ch2] Time-out time setting – 3 –

D 8430 RS2 (FNC 87) [ch2] Header 1 and 2 – 3 –

D 8431 RS2 (FNC 87) [ch2] Header 3 and 4 – 3 –

D 8432 RS2 (FNC 87) [ch2] Terminator 1 and 2 – 3 –

D 8433 RS2 (FNC 87) [ch2] Terminator 3 and 4 – 3 –

[D]8434 RS2 (FNC 87) [ch2] Receive sum (received data) – 3 –

[D]8435 RS2 (FNC 87) [ch2] Receive sum (calculated result) – 3 –

[D]8436 RS2 (FNC 87) [ch2] Send sum – 3 –

[D]8437 Not used –

*1. Cleared when the PLC switches from RUN to STOP.

MODBUS communication [ch1] (Refer to MODBUS Communication Edition for details.)

D 8400 Communication format 3 3*2 3 3*3 3*3 –

D 8401 Protocol 3 3*2 3 3*3 3*3 –

D 8402 Communication error code 3 3*2 3 3*3 3*3 M8402 –

D 8403 Error details 3 3*2 3 3*3 3*3 M8403 –

D 8404 Error step number 3 3*2 3 3*3 3*3 –

[D]8405 Communication format display 3 3*2 3 3*3 3*3 –

D 8406 ASCII input delimiter – – – 3*3 3*3 –

[D]8407 Step number being executed 3 3*2 3 3*3 3*3 –

[D]8408 Current retry value 3 3*2 3 3*3 3*3 –

D 8409 Slave response timeout 3 3*2 3 3*3 3*3 –

D 8410 Turn around delay 3 3*2 3 3*3 3*3 –

D 8411 Message to message delay 3 3*2 3 3*3 3*3 –

D 8412 Number of retries 3 3*2 3 3*3 3*3 –

D 8414 Slave node address 3 3*2 3 3*3 3*3 –

D 8415 Communication status information setup – – – 3*3 3*3 –

D 8416 Communication status device range setup – – – 3*3 3*3 –

[D]8419 Communication mode 3 3*2 3 3*3 3*3 –

*2. Available in Ver. 1.30 or later. *3. Available in Ver. 2.40 or later.

Show 6 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · M8426 to
Page 861 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 861 · click to enlarge
Page 861

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

MODBUS communication [ch2] (Refer to MODBUS Communication Edition for details.)

D 8420 Communication format – 3*1 3 3*2 3*2 –

D 8421 Protocol – 3*1 3 3*2 3*2 –

FNC280-FNC289 High-Speed Processing 2

D 8422 Communication error code – 3*1 3 3*2 3*2 M8422 –

D 8423 Error details – 3*1 3 3*2 3*2 M8423 –

D 8424 Error step number – 3*1 3 3*2 3*2 –

[D]8425 Communication format display – 3*1 3 3*2 3*2 –

D 8426 ASCII input delimiter – – – 3*2 3*2 –

FNC290-FNC299 Extension File Register Control

[D]8427 Step number being executed – 3*1 3 3*2 3*2 –

[D]8428 Current retry value – 3*1 3 3*2 3*2 –

D 8429 Slave response timeout – 3*1 3 3*2 3*2 –

D 8430 Turn around delay – 3*1 3 3*2 3*2 –

D 8431 Message to message delay – 3*1 3 3*2 3*2 –

FNC300-FNC305 FX 3U -CF-ADP

D 8432 Number of retries – 3*1 3 3*2 3*2 –

D 8434 Slave node address – 3*1 3 3*2 3*2 –

D 8435 Communication status information setup – – – 3*2 3*2 –

D 8436 Communication status device range setup – – – 3*2 3*2 –

[D]8439 Communication mode – 3*1 3 3*2 3*2 –

*1. Available in Ver. 1.30 or later. *2. Available in Ver. 2.40 or later.

MODBUS communication [ch1, ch2] (Refer to MODBUS Communication Edition for details.)

MODBUS device mapping 1 – – – 3*3 3*3 –

D 8471 Upper –

MODBUS device mapping 2 – – – 3*3 3*3 –

D 8473 Upper –

MODBUS device mapping 3 – – – 3*3 3*3 –

D 8475 Upper –

MODBUS device mapping 4 – – – 3*3 3*3 –

D 8477 Upper –

MODBUS device mapping 5 – – – 3*3 3*3 –

D 8479 Upper –

MODBUS device mapping 6 – – – 3*3 3*3 –

D 8481 Upper –

MODBUS device mapping 7 – – – 3*3 3*3 –

D 8483 Upper –

MODBUS device mapping 8 – – – 3*3 3*3 –

D 8485 Upper –

*3. Available in Ver. 2.40 or later.

A

B

Show 19 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · SFC•STL Programming · D 8470 Lower · Interrupt Function · D 8472 Lower · D 8474 Lower · D 8476 Lower · Special Device · D 8478 Lower · D 8480 Lower · D 8482 Lower · Error Code · D 8484 Lower · Version Up Information · Execution Times
Page 862 of the Mitsubishi Electronics MELSEC FX3S user manual — 37.1.2 Special Data Register (D8000 to D8511)
Page 862 · click to enlarge
Page 862

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

FX3U-CF-ADP [ch1] (Refer to CF-ADP Manual for details.)

[D]8400 to [D]8401 Not used –

[D]8402 Step number of executing CF-ADP

– – – 3*1 3*1 –

[D]8404 to [D]8405 Not used –

[D]8406 CF-ADP status – – – 3*1 3*1 –

[D]8407 Not used –

[D]8408 CF-ADP version – – – 3*1 3*1 –

[D]8409 to [D]8413 Not used –

Error step number of M8418*1 – – – 3*1 3*1 –

[D]8416 Not used –

[D]8417 Error code in detail for CF-ADP instructions*2*3 – – – 3*1 3*1 –

[D]8418 Error code for CF-ADP instructions*2*3 – – – 3*1 3*1 –

[D]8419 Operation mode display – – – 3*1 3*1 –

*1. Available in Ver. 2.61 or later.

*2. Cleared when the PLC switches from STOP to RUN.

*3. For details on the error code is stored in special data register, refer to the CF-ADP Manual.

FX3U-CF-ADP [ch2] (Refer to CF-ADP Manual for details.)

[D]8420 to [D]8421 Not used –

[D]8422 Step number of executing CF-ADP

– – – 3*4 3*4 –

[D]8424 to [D]8425 Not used –

[D]8426 CF-ADP status – – – 3*4 3*4 –

[D]8427 Not used –

[D]8428 CF-ADP version – – – 3*4 3*4 –

[D]8429 to [D]8433 Not used –

Error step number of M8438*5 – – – 3*4 3*4 –

[D]8436 Not used –

[D]8437 Error code in detail for CF-ADP instructions*5*6 – – – 3*4 3*4 –

[D]8438 Error code for CF-ADP instructions*5*6 – – – 3*4 3*4 –

[D]8439 Operation mode display –

*4. Available in Ver. 2.61 or later.

*5. Cleared when PLC switches from STOP to RUN.

*6. For details on the error code is stored in special data register, refer to the CF-ADP Manual.

Show 7 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · instruction*2 · instruction*5
Page 863 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 863 · click to enlarge
Page 863

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

FX3U-ENET-ADP [ch1] (Refer to ENET-ADP Manual for details.)

[D]8400 IP Address (Low-order) 3 3*1 3*1 3*2 3*2 –

[D]8401 IP Address (High-order) 3 3*1 3*1 3*2 3*2 –

FNC280-FNC289 High-Speed Processing 2

[D]8402 Subnet mask (Low-order) 3 3*1 3*1 3*2 3*2 –

[D]8403 Subnet mask (High-order) 3 3*1 3*1 3*2 3*2 –

[D]8404 Default router IP Address (Low-order) 3 3*1 3*1 3*2 3*2 –

[D]8405 Default router IP Address (High-order) 3 3*1 3*1 3*2 3*2 –

[D]8406 Status information 3 3*1 3*1 3*2 3*2 –

FNC290-FNC299 Extension File Register Control

[D]8407 Connection condition of the Ethernet port 3 3*1 3*1 3*2 3*2 –

[D]8408 FX3U-ENET-ADP version 3 3*1 3*1 3*2 3*2 –

D 8409 Communication timeout time 3 3*1 3*1 3*2 3*2 –

D 8410 Connection forcible nullification 3 3*1 3*1 3*2 3*2 –

[D]8411 Time setting functional operation result 3 3*1 3*1 3*2 3*2 –

FNC300-FNC305 FX 3U -CF-ADP

[D]8412 to [D]8414 Host MAC address 3 3*1 3*1 3*2 3*2 –

[D]8415 Not used –

[D]8416 Model code 3 3*1 3*1 3*2 3*2 –

[D]8417 Error code of the Ethernet adapter 3 3*1 3*1 3*2 3*2 –

[D]8418 Not used –

[D]8419 Operation mode display 3 3*1 3*1 3*2 3*2 –

*1. Available in Ver. 2.00 or later.

*2. Available in Ver. 3.10 or later.

A

B

Show 11 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 864 of the Mitsubishi Electronics MELSEC FX3S user manual — 37.1.2 Special Data Register (D8000 to D8511)
Page 864 · click to enlarge
Page 864

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -)

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

FX3U-ENET-ADP [ch2] (Refer to ENET-ADP Manual for details.)

[D]8420 IP Address (Low-order) – 3*1 3*1 3*2 3*2 –

[D]8421 IP Address (High-order) – 3*1 3*1 3*2 3*2 –

[D]8422 Subnet mask (Low-order) – 3*1 3*1 3*2 3*2 –

[D]8423 Subnet mask (High-order) – 3*1 3*1 3*2 3*2 –

[D]8424 Default router IP Address (Low-order) – 3*1 3*1 3*2 3*2 –

[D]8425 Default router IP Address (High-order) – 3*1 3*1 3*2 3*2 –

[D]8426 Status information – 3*1 3*1 3*2 3*2 –

[D]8427 Connection condition of the Ethernet port – 3*1 3*1 3*2 3*2 –

[D]8428 FX3U-ENET-ADP version – 3*1 3*1 3*2 3*2 –

D 8429 Communication timeout time – 3*1 3*1 3*2 3*2 –

D 8430 Connection forcible nullification – 3*1 3*1 3*2 3*2 –

[D]8431 Time setting functional operation result – 3*1 3*1 3*2 3*2 –

[D]8432 to [D]8434 Host MAC address – 3*1 3*1 3*2 3*2 –

[D]8435 Not used –

[D]8436 Model code – 3*1 3*1 3*2 3*2 –

[D]8437 Error code of the Ethernet adapter – 3*1 3*1 3*2 3*2 –

[D]8438 Not used –

[D]8439 Operation mode display – 3*1 3*1 3*2 3*2 –

FX3U-ENET-ADP [ch1, ch2] (Refer to ENET-ADP Manual for details.)

[D]8490 to [D]8491 Not used –

D 8492 IP address setting (Low-order) 3 3*3 3*3 –

D 8493 IP address setting (High-order) 3 3*3 3*3 –

D 8494 Subnet mask setting (Low-order) 3 3*3 3*3 –

D 8495 Subnet mask setting (High-order) 3 3*3 3*3 –

D 8496 Default router IP address setting (Low-order) 3 3*3 3*3 –

D 8497 Default router IP address setting (High-order) 3 3*3 3*3 –

[D]8498 Error code for IP address storage area write 3 3*3 3*3 –

[D]8499 Error code for IP address storage area clear 3 3*3 3*3 –

*1. Available in Ver. 2.00 or later.

*2. Available in Ver. 3.10 or later.

*3. Available in Ver. 2.10 or later.

Mitsubishi Electronics MELSEC FX3S — 37.1.2 Special Data Register (D8000 to D8511) diagram (page 864)
Fig. 817 · 37.1.2 Special Data Register (D8000 to D8511)

[D]8438*4 Error code for serial communication error 2 [ch2] – 3 M8438 –

RS2 (FNC 87) [ch2] and Computer Link [ch2] (Refer to Data Communication Edition for details.)

[D]8439 Operation mode display [ch2] – 3 –

[D]8440 to [D]8448 Not used –

[D]8449 Special block error code – 3*5 M8449 –

[D]8450 to [D]8459 Not used –

*4. Cleared when PLC power supply is turned from OFF to ON.

*5. Available in Ver. 2.20 or later.

Show 5 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device
Page 865 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 865 · click to enlarge
Page 865

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.1 Special Device List (M8000 -, D8000 -) 31

FNC277-FNC279 Data Transfer 3

name Content of register

FX3S FX3G FX3GC FX3U FX3UC

FX1S FX1N FX1NC FX2N FX2NC

Positioning [FX3S/FX3G/FX3GC/FX3U/FX3UC] (Refer to Positioning Control Edition for details.)

[D]8460 to [D]8463 Not used – – – 3 3 –

DSZR (FNC150) and ZRN (FNC156) instructions: [Y000] Clear signal device specification

FNC280-FNC289 High-Speed Processing 2

3*1 M8464 –

DSZR (FNC150) and ZRN (FNC156) instructions: [Y001] Clear signal device specification

3*1 M8465 –

DSZR (FNC150) and ZRN (FNC156) instructions: [Y002] Clear signal device specification

– 3 – 3 3*1 M8466 –

FNC290-FNC299 Extension File Register Control

DSZR (FNC150) and ZRN (FNC156) instructions: [Y003] Clear signal device specification

– – – 3*2 – M8467 –

*1. Available in Ver. 2.20 or later.

*2. Available only when two FX3U-2HSY-ADP adapters are connected to an FX3U PLC.

FNC300-FNC305 FX 3U -CF-ADP

[D]8468 to [D]8486 Not used –

[D]8487 USB communication error 3 – M8487 –

[D]8488 Not used –

[D]8489 Error code for special parameter error 3 3*4 3*4 3*3 3*3 M8489 –

[D]8490 to [D]8511 Not used –

*3. Available in Ver. 3.10 or later.

*4. Available in Ver. 2.00 or later.

A

B

Show 12 more labels / short text on this page
Applicable model · Number and · Correspond- · ing special · device · Error Detection · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 866 of the Mitsubishi Electronics MELSEC FX3S user manual — M8002
Page 866 · click to enlarge
Page 866

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -)

This section explains how to use the provided special devices to activate built-in PLC functions for additional program control.

37.2.1 RUN monitor and initial pulse [M8000 to M8003]

1. RUN monitor (M8000 and M8001) The RUN monitor (M8000 and M8001) may be used to continually drive an output during PLC "normal operation".
1. Example program

M8000

RUN monitor (NO contact) Always ON while the PLC is in RUN mode.

Output to be always driven

M8001 is always OFF while the PLC is in the RUN mode.

2. Flag operation timing
Mitsubishi Electronics MELSEC FX3S — M8000 diagram (page 866)
Fig. 818

M8002 Initial pulse (NO contact) ON ON 1 scan time

2. Initial pulse (M8002 and M8003) The initial pulse M8002 & M8003 is turned to ON or OFF respectively during the 1st scan of the PLC program. It can be utilized as an initial setting signal in a program for initializing the program, for writing a specified value, or for another purpose.
1. Example program

M8002

ZRST D200 D299 The latched (battery backed) type data registers D200 to D299 are cleared.

Initial pulse (NO contact)

M8003 turns OFF momentarily (for only 1 scan time) when the PLC enters the RUN mode.

2. Flag operation timing
Mitsubishi Electronics MELSEC FX3S — M8002 diagram (page 866)
Fig. 819

M8002 Initial pulse (NO contact) ON ON 1 scan time

"Normal operation" Y000

Page 867 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 867 · click to enlarge
Page 867

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -) 31

37.2.2 Watchdog timer [D8000]

FNC277-FNC279 Data Transfer 3

The watchdog timer monitors the operation (scan) time of the PLC. When the operation is not completed within the specified time, ERROR (ERR) LED light turns on and all outputs are turned OFF. When the power is initially turned ON, "200 ms" is transferred from the system to D8000 as the default value. For executing a program beyond 200 ms, the contents of D8000 must be changed by the user program.

1. Example program

FNC280-FNC289 High-Speed Processing 2

M8002

Setting value of watchdog timer is set to "300 ms". 0

MOV K300 D8000

The watchdog timer When WDT (FNC 07) instruction is not programmed, the value stored in D8000 is not valid until END processing.

WDT

FNC290-FNC299 Extension File Register Control

2. When a watchdog timer error occurs A watchdog timer error may occur in the following cases. Add the above program to somewhere near the first step or adjust the number of execution FROM/TO instructions at the same scan.
1. When using many special function units/blocks When many special function units/blocks (such as positioning, cam switches, link and analog) are used, buffer memory initial setting time becomes long at turning on the PLC, thus extending the operation time and allowing the possibility for a watchdog timer error to occur.

FNC300-FNC305 FX 3U -CF-ADP

2. When executing many FROM/TO instructions at the same time When many FROM/TO instructions are executed or when many buffer memories are transferred, it extends the scan time, and a watchdog timer error may occur.
3. When using many high-speed counters (software counters) When many high-speed counters are programmed and high frequency is counted at the same time, it extends the scan time, and a watchdog timer error may occur.
3. How to reset the watchdog timer The watchdog timer can be reset in the middle of a sequence program using WDT (FNC 07) instruction. It is recommended to reset the watchdog timer by WDT (FNC 07) instruction when the scan time of a particular sequence program is extended or when many special function units/blocks are connected.

→ For WDT (FNC 07) instruction, refer to Section 8.8.

4. Cautions on changing the watchdog timer The watchdog timer time can be set to a maximum of 32767 ms. However, CPU error detection is delayed when the watchdog timer time is extended. It is recommended to use the default value (200 ms) when no problems are to be expected in operation. The watchdog timer time becomes "0" when a value less than "0" is set to D8000.

37.2.3 Battery voltage low detection [M8005 and M8006]

This special device detects low voltage in the lithium battery for memory backup. In FX3U/FX3UC PLCs, the BATT (BAT) LED turns ON when the PLC detects low battery voltage. In FX3G/FX3GC PLCs, the ALM LED indicator turns ON when the PLC detects low battery voltage if the optional battery is installed and the battery mode is selected by the parameter setting. Use the following program to notify low battery voltage to the outside.

M8005

"Battery voltage low" Y001

A

M8006 latches the battery voltage low.

B

Show 8 more labels / short text on this page
Initial pulse · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Battery voltage low · Version Up Information · Execution Times
Page 868 of the Mitsubishi Electronics MELSEC FX3S user manual — 37.2.6 Internal clock [M8011 to M8014]
Page 868 · click to enlarge
Page 868

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -)

37.2.4 Power failure detection time [D8008, M8008 and M8007]

1. FX 3U PLC (AC power supply type) The table below shows the allowable momentary power failure time in FX 3U PLC (AC power supply type).
Mitsubishi Electronics MELSEC FX3S — 37.2.4 Power failure detection time [D8008, M8008 and M8007] diagram (page 868)
Fig. 820 · 37.2.4 Power failure detection time [D8008, M8008 an…

Supply voltage Allowable momentary power

100V AC system 10 ms

200V AC system Setting range10 to 100 ms Set a value to D8008. Default: 10 ms
2. FX 3U /FX 3UC PLCs (DC power supply type) The allowable momentary power failure time in the FX 3U /FX 3UC PLCs (DC power supply type) is 5 ms. Do not overwrite the power failure detection time in device D8008.
Mitsubishi Electronics MELSEC FX3S — 37.2.4 Power failure detection time [D8008, M8008 and M8007] diagram (page 868)
Fig. 821 · 37.2.4 Power failure detection time [D8008, M8008 an…

37.2.5 Scan time (monitor) [D8010 to D8012]

The present value, minimum value and maximum value of the PLC scan time (operation time) are stored in D8010, D8011 and D8012 respectively (in 0.1-ms units). When using the constant scan mode, the values stored in these devices include the waiting time for the constant scan time.

D8010Present value D8011: Minimum value D8012: Maximum value

The values stored in these devices can be monitored from peripheral equipment.

37.2.6 Internal clock [M8011 to M8014]

The PLC has the following four types of internal clocks which are always oscillating while the PLC power is ON.

Mitsubishi Electronics MELSEC FX3S — 37.2.6 Internal clock [M8011 to M8014] diagram (page 868)
Fig. 822 · 37.2.6 Internal clock [M8011 to M8014]

failure time

Page 869 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 869 · click to enlarge
Page 869

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -) 31

37.2.7 Real time clock [M8015 to M8019 and D8013 to D8019]

FNC277-FNC279 Data Transfer 3

1. Assignment of special auxiliary relays (M8015 to M8019) and special data registers (D8013 to D8019)

Number Name Operation and function

When M8015 turns ON, the real time clock is stopped. At the edge from ON to OFF, the time from D8013 to D8019 is written to the PLC and the clock is started again.

FNC280-FNC289 High-Speed Processing 2

M8015 Clock stop and preset

M8016 Time read display is stopped When M8016 turns ON, the time display is stopped (but RTC is continued).

At the edge from OFF to ON, the RTC is set to the nearest minute. (When the second data is from 0 to 29, it is set to 0. When the second data is from 30 to 59, it is set to 0 and the minute data is incriminated by "1".)

M8017 ±30 seconds correction

M8018 Installation detection This device is always ON.

FNC290-FNC299 Extension File Register Control

M8019 Real time clock (RTC) error

When the data stored in special data registers is outside the allowable time, setting range this device turns ON.

Number Name Set value range Operation and function

D8013 Second data 0 to 59

D8014 Minute data 0 to 59

Use these devices for writing the initial value in time setting or read the present time.

D8015 Hour data 0 to 23

FNC300-FNC305 FX 3U -CF-ADP

D8016 Day data 1 to 31

D8017 Month data 1 to 12

  • D8018 (year data) can be changed over to the four-digit year mode. In the four-digit year mode, 1980 to 2079 can be displayed.
  • Clock accuracy: ±45 sec/month (at 25 ° C)
  • Leap year correction: Provided

D8018 Year data 00 to 99 (last two digits of year)

0 to 6 (which corresponds to

→ For the real time clock setting method, refer to Subsection 37.2.8.

2. Changeover of the year display (to the four-digit mode) When changing the year data to the four-digit mode, add the following program. D8018 is set to the four-digit year mode on the second ladder scan in RUN mode.

M8002

MOV K2000 D8018 Initial pulse

1. The PLC is usually operating in the two-digit year mode. When the above instruction is executed during RUN and "K2000 (fixed value)" is transferred to D8018 (year data), D8018 switches to the four-digit year mode.
2. Execute this program every time the PLC enters RUN. Only the year data display switches to four-digit mode when "K2000" is transferred. The actual time date is not affected.
3. In the four-digit year mode, the values "80" to "99" correspond to "1980" to "1999" and "00" to "79" correspond to "2000" to "2079". Examples: 80 = 1980, 99 = 1999, 00 = 2000, 79 = 2079
4. When connecting the data access unit FX-10DU-E/20DU-E/25DU-E, use the two-digit year mode. If the four-digit year mode is selected, the year data will not be displayed correctly. Note that the clock is changed to the 2-digit year mode when the clock is set from the FX-10DU-E/20DU-E/ 25DU-E while the PLC is operating in the 4-digit year mode.

A

B

Show 8 more labels / short text on this page
D8019 Day-of-the-week data · Sunday to Saturday) · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 870 of the Mitsubishi Electronics MELSEC FX3S user manual — → FX 3G Series User’s Manual - Hardware Edition
Page 870 · click to enlarge
Page 870

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -)

37.2.8 How to set real time clock

The real time clock is set by the following method.

1. Method using the display module This subsection explains how to set the real time clock in the display module FX 3U -7DM (built in the FX 3UC -32MT-LT (-2)). Refer to the following manual for the display module FX 3G -5DM.

→ FX 3G Series User’s Manual - Hardware Edition

1. Scroll to "ClockMenu" by pressing the [+] or [-] key on the MENU screen, and press the [OK] key. The selection screen on the right is displayed. Press the [ESC] key to cancel the operation and return to "TOP screen".
Mitsubishi Electronics MELSEC FX3S — → FX 3G Series User’s Manual - Hardware Edition diagram (page 870)
Fig. 823 · → FX 3G Series User’s Manual - Hardware Edition

C u r r e n t m t i e

C l o c k e s t t i n g

2. Scroll to "Clock setting" by pressing the [+] or [-] key. Press the [ESC] key to cancel the operation and return to the "MENU screen".

C u r r e n t m t i e

C l o c k e s t t i n g

3. Press the [OK] key, and the "Clock setting" screen on the right is displayed. Press the [ESC] key to cancel the operation and return to the "selection screen".

t C c o l k s e t g n i

7. 1 1 : 1 9 [ u ] T h
4. Change the flickering value by pressing the [+] or [-] key, and press the [OK] key to set the value. The items are set in the order "year → month → day → hour → minute → second". When the last "second" value is decided by pressing the [OK] key, the message "Current time is set" appears, and setting of the present time is completed.

t C c o l k s e t g n i

* 3 1 . 1 . 2 0 0 4

3. 5 9 : 5 9 [ t ] S a 2
Mitsubishi Electronics MELSEC FX3S — → FX 3G Series User’s Manual - Hardware Edition diagram (page 870)
Fig. 824 · → FX 3G Series User’s Manual - Hardware Edition

The default "Year" display is a 2-digit value indicating the Western calendar year.

Return to the previous set item. When pressed while "year" data is flickering, the "selection screen" is displayed.

Decreases a numeric value. A numeric value decreases at high-speed when pressed and held for 1 second or more.

Increases a numeric value. A numeric value increases at high-speed when pressed and held for 1 second or more.

Shifts to the next set item. When pressed while "second" data is flickering, the message "Current time is set" appears.

5. Press the [OK] or [ESC] key to return to "selection screen".
6. Press the [ESC] key to return to the "MENU screen".

C u r r e n t m t i e

C l o c k e s t t i n g

Page 871 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 871 · click to enlarge
Page 871

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -) 31

2. Method by program

FNC277-FNC279 Data Transfer 3

1. Method using TWR (FNC167) instruction dedicated to time setting.

→ For details, refer to Subsection 21.8.

2. Method using M8015 and D8013 to D8019. When not using TWR (FNC167) instruction dedicated to time setting, the following program can be used for time setting.

FNC280-FNC289 High-Speed Processing 2

M8015

indicates a set item.

PLF M0

Example: 10:20:30 on April 25 Tuesday in 2000 Set the time 2 to 3 minutes ahead of the actual time, write the program on the left to the PLC, and turn RUN X000 ON.

M0 FNC 12

MOV K30 D8013

MOV K20 D8014

FNC290-FNC299 Extension File Register Control

When the actual time reaches the input set time, turn the input switch X000 OFF to set the time and start the clock operation.

MOV K10 D8015

MOV K25 D8016

±30 seconds correction Every time X001 is set from OFF to ON, the second data of the clock is corrected. (When the second data is from 0 to 29, it is set to 0. When the second data is from 30 to 59, it is set to 0 and the minute data is incremented by "1".)

MOV K4 D8017

FNC300-FNC305 FX 3U -CF-ADP

MOV K0 D8018

MOV D8019 X001

K2

M8017

+/- 30 seconds correction

Point

a) While M8015 is OFF, the registers for date and time cannot be changed.

Make sure to set M8015 to ON, and then input date and time. b) When inputting the time, set the time several minutes ahead of the current time.

When the actual time reaches the set time, set M8015 to OFF from ON to make the new time valid and to begin the real time clock again. c) If values indicating infeasible date, time and day of the week are input (Example: February 30, 2006), the time

cannot be set. Input the correct date, time and day of the week. d) The day of the week (D8019) is automatically corrected in accordance with the date without regard to the

written numeric value.

3. Method by programming tool

1. Starting the time change Set M8015 to ON by forced ON/OFF.
2. By using the data register value change function in the device monitor of the programming tool, input the date and time (several minutes ahead) to each data register.
3. Finishing the time change When the actual time reaches the input data, reset M8015 by forced ON/OFF.

Point

a) While M8015 is OFF, the registers for date and time cannot be changed.

Make sure to set M8015 to ON, and then input date and time. b) When inputting the time, set the time several minutes ahead of the current time.

When the actual time reaches the set time, set M8015 to OFF from ON to make the new time valid and to begin the real time clock again. c) If values indicating infeasible date and time are input (Example: February 30, 2006), the time cannot be set.

A

Input the correct date and time.

B

Show 13 more labels / short text on this page
Second data · Minute data · Hour data · Day data · Month data · Year data · Day-of-the-week data · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 872 of the Mitsubishi Electronics MELSEC FX3S user manual — M8000
Page 872 · click to enlarge
Page 872

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -)

37.2.9 Input filter adjustment [D8020]

The inputs X000 to X017*1 have a digital filter circuit with a setting range of 0 to 60 ms. The digital filter setting value is set between 0 to 60*2 ms (in 1 ms steps) in special data register D8020. After the PLC powers ON, D8020 is automatically set to K10 (10 ms).

Determined by the contents of D8020 (initial value: 10)

X017 *1

*1. X000 to X007 in the FX3G/FX3GC PLCs.

*2. 0 to 15 in FX3S/FX3G/FX3GC PLCs

1. Program example for adjusting the input filter When the program shown below is executed, the filter constant is changed to 0 ms. Because the C-R filter is provided in the hardware, however, the filter constant is shown in the table below when "0" is specified.

M8000

MOV K0 D8020

1) FX 3S PLC

Input number Input filter value when "0" is set

X000, X001 10µs

X002 to X007 50µs

X010 to X017 200µs

2. FX 3G /FX 3GC PLCs

Input number Input filter value when "0" is set

X000, X001, X003, X004 10µ

X002, X005, X006, X007 50µs

3. FX 3U /FX 3UC PLCs

Input number Input filter value when "0" is set

X000 to X005 5µs*3

X006, X007 50µs

X010 to X017*4 200µs

*3. When setting the input filter to "5 µs" or when receiving pulses whose response frequency is 50 k to 100 kHz using high-speed counters, perform the following actions: - Input wiring length should be 5 m (16' 4") or less. - Connect a bleeder resistor (1.5 kΩ, 1/2 W) to the input terminal. The load current of the open collector transistor output in the device on the other end should be 20 mA or more including the input current of the PLC.

*4. In the FX3U/FX3UC PLCs (16-point type), only X000 to X007 support the input filter adjustment function.

  • The input filter constant can be changed as many times as need in the user program.
  • This input filter adjustment described here is not required when using high-speed counter, input interrupt, or pulse catch (M8170 to M8177) functions.
Show 9 more labels / short text on this page
Input terminal · Filter · 0ms · 1ms · Input refresh · 10ms · 60 Image memory · 60ms · RUN monitor
Page 873 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 873 · click to enlarge
Page 873

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -) 31

37.2.10 Battery [BATT (BAT)] LED and [ALM] LED OFF command [M8030]

FNC277-FNC279 Data Transfer 3

When M8030 is set to ON, the battery LED does not turn ON even if the voltage in the battery for memory backup becomes low. When the indication of "battery voltage low error" is not required or when the battery is removed, set M8030 to ON. When batteryless operation is required in FX3U/FX3UC PLCs, do not use M8030 and refer to "1. Batteryless operation by parameter setting in peripheral equipment" below.

FNC280-FNC289 High-Speed Processing 2

1. Batteryless operation by parameter setting in peripheral equipment Specify "batteryless operation" mode in the parameter settings.
1. When the batteryless operation option is specified When "batteryless mode" is specified, the control to turn OFF the BATT (BAT) LED and initialization of the latch area for the devices shown below are automatically executed by the PLC system. - Auxiliary relay (M) - Counter (C) - State relay (S) - Data register (D) - Timer (T) - Extension register (R)

FNC290-FNC299 Extension File Register Control

2. Applicable programming tool Some programming tool versions do not support "batteryless mode". In such versions, input a sequence program to enable the batteryless operation as explained below.

2. Conditions for batteryless operation

1. An FLROM (optional memory cassette) for program memory is installed so that programs are not erased. (only in FX 3U /FX 3UC PLCs)

FNC300-FNC305 FX 3U -CF-ADP

2. The latch (battery backed) devices such as auxiliary relays and data registers are not used for control.
3. The sampling trace function is not used.
4. The real time clock function is not used. (only in FX 3U /FX 3UC PLCs)
3. Example program for batteryless mode When a parameter setting for "batteryless mode" is not available, create the sequence program shown below.
  • Example program for clearing the memory backup area {when the latch (battery backed) ranges in the parameter settings are set to their initial values.}

M8000

M8000

M8030 BATT(BAT) LED turns OFF.

M8030 BATT(BAT) LED turns OFF.

ZRST M500 *1 M7679 M8002

M8002

M8032 The latch areas are cleared.

S500*1 S4095 State relay

ZRST

ZRST

C100 *1 C199 *1

ZRST

C220*1 C255*1 32 bit counter

ZRST

D200*1 D7999 Data register

ZRST

R0 R32767 FNC 40

ZRST

*1. The device number is the default number of the latch (battery backed) device range limits in the parameter settings. If the latch (battery backed) device numbers in the parameter settings are changed to other values, change the device numbers here in accordance with the changed latch ranges.

A

4. Cautions for communication setting devices (D8120, D8121 and D8129) Special data registers D8120 (communication format), D8121 (station number setting) and D8129 (timeout check time) are backed up by the battery in FX3U/FX3UC PLCs. When performing the batteryless operation in FX3U/FX3UC PLCs, reset these special data registers using the procedure described above, and then transfer proper set values to them using a program. The communication conditions can be set in the parameter settings. When the communication conditions are set in the parameter settings, the PLC transfers the parameter values to the above special data registers before operation. Thus it is recommended to set the communication conditions via the parameter settings.

B

Show 14 more labels / short text on this page
SFC•STL Programming · or · RUN monitor · RUN monitor · Interrupt Function · Auxiliary relay · Initial pulse · Initial pulse · T246 T255 Timer · Special Device · 16 bit counter · Error Code · Version Up Information · Execution Times
Page 874 of the Mitsubishi Electronics MELSEC FX3S user manual — 1. Example program
Page 874 · click to enlarge
Page 874

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -)

37.2.11 Built-in analog volume [D8030 and D8031]

Values of variable analog potentiometers built in FX3S/FX3G PLCs*1 as standard are stored as numeric data ranging from 0 to 255 in the following special registers in accordance with the scale position. An obtained numeric value can be specified as the indirectly specified value for a timer to make a variable potentiometer type analog timer.

  • VR1 → D8030 (Integer from 0 to 255)
  • VR2 → D8031 (Integer from 0 to 255)
Mitsubishi Electronics MELSEC FX3S — 37.2.11 Built-in analog volume [D8030 and D8031] diagram (page 874)
Fig. 825 · 37.2.11 Built-in analog volume [D8030 and D8031]

0 to 25.5 sec This register stores the value (0 to 255) of variable analog potentiometer.

"D8030 (VR2) value x 2" is transferred to D0 (D1).

The set value range can be changed (up to 32,767) by multiplying the data register value by "n". Do not use D1 in other programs.

*1. This function is not supported in the FX3S-30M /E -2AD PLC.

37.2.12 Clear command [M8031 and M8032]

For all devices (image memory) in the PLC, the latch (battery backed) areas and non-latch areas can be cleared. M8031 (non-latch memory all clear), M8032 (latch memory all clear)

Device number Cleared devices

  • Contact image of output relay (Y), general type auxiliary relay (M), and general type state relay (S)
  • Contact and coil of timer (T)
  • Contact, counting coil, and reset coil of general type counter (C)
  • Present value of general type data register (D) (Except data registers used as file registers)
  • Present value register of timer (T)
  • Present value register of general type counter (C)
  • Extension register for general

M8031*1 (non-latch memory all clear)

  • Contact image of latch (battery backed) type auxiliary relay (M) and latch (battery backed) type state relay (S)
  • Contact and coil of retentive type timer (T)
  • Contact, counting coil, and reset coil of latch (battery backed) type counter and high-speed counter
  • Present value of latch (battery backed) type data register (D)
  • Present value of general type data register (D) (Data registers used as file registers)
  • Present value register of retentive type timer (T) and 1-ms timer (T)
  • Present value register of latch (battery backed) type counter and high-speed counter
  • Latch (battery backed) type extension register (R)

M8032 (latch memory all clear)

*1. When the optional battery is installed in FX3G/FX3GC PLCs, general type devices which were changed to the latch (battery backed) type are handled as devices in latch areas.

37.2.13 Memory hold stop [M8033] (output hold in STOP mode)

When the special auxiliary relay M8033 is turned ON, the output status in the RUN mode is retained even if the PLC status switches from RUN to STOP.

1. Example program

M8033 Outputs are retained even during STOP mode.

For example, when a heater is driven by the PLC, the PLC can be stopped while the heater and other equipment are kept driven, and then the PLC can be started again after program changes.

Command · input

Page 875 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 875 · click to enlarge
Page 875

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -) 31

37.2.14 All outputs disable [M8034]

FNC277-FNC279 Data Transfer 3

When M8034 is turned ON, the output memory is cleared. As a result, all actual output relay contacts are turned OFF and the PLC is operated in the image memory.

1. Program example

FNC280-FNC289 High-Speed Processing 2

M8034 All outputs are disabled (image RUN status).

37.2.15 Individual operation for RUN/STOP input [M8035 to M8037]

When using external push button switches to control the PLC's RUN/STOP mode, operate the switches using the following procedure. The PLC enters RUN mode by one-shot input of the RUN switch, while one-shot input of the STOP switch drives the STOP mode.

FNC290-FNC299 Extension File Register Control

1. Program example The figure on the left shows an example for the FX 3U PLC (sink input).

FNC300-FNC305 FX 3U -CF-ADP

RUN

STOP

S/S X001

X000 PLC

M8000 Forced RUN mode M8035

Forced RUN signal M8036

Forced STOP signal M8037 X001

Write the above program to the PLC.

2. Setting method

1. Turn the built-in RUN/STOP switch to STOP.
2. Set up the RUN input switch, (X) (X000 is specified in the circuit diagram example above.) Make the external RUN/STOP input valid by specifying an input between X000 and X017 *1 for the RUN input signal. a) Display the parameter setting in the programming tool

In GX Works2, double-click [Parameter] - [PLC parameter] in the project view to display the dialog box. Go to the [PLC System(1)] tab, and set "RUN Terminal Input". b) Specify the input (X) number to switch from STOP mode to RUN mode.

3. Set up the STOP switch input (X) Specify an arbitrary input terminal (actual I/O on the PLC) within the sequence program. Refer to the program above.
4. Transfer the program and parameters to the PLC.
5. For the parameter settings to become valid, the PLC power must be turned from OFF to ON.

3. Cautions

A

1. When both RUN and STOP switches are pressed at the same time, priority is given to the STOP switch.
2. When the built-in RUN/STOP switch is turned to RUN, the PLC can be set to RUN mode. However, when the STOP switch assigned to an arbitrary input is activated, the PLC will enter STOP mode. (Even if the built-in switch is turned to RUN, priority is given to the STOP command.)

B

Show 8 more labels / short text on this page
Command · input · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 876 of the Mitsubishi Electronics MELSEC FX3S user manual — 37.2.17 State control in program with STL instruction/SFC chart [M8040]
Page 876 · click to enlarge
Page 876

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -)

4. RUN/STOP command via the programming tool

1. Using the programming software for personal computer There is a remote RUN/STOP function in the programming software. By using the programming software, the PLC can be set to the RUN or STOP mode by giving a command from the personal computer.
2. Using any other programming tool When M8035 (forced RUN mode) and M8036 (forced RUN signal) are set to ON in the forced ON/OFF procedure, the PLC begins RUN mode. When M8037 (forced STOP signal) is set to ON, the PLC changes to STOP mode.
3. Even when the built-in RUN/STOP switch is on the RUN side of the PLC. The remote STOP command via the programming tool or M8037 (forced STOP signal) are valid.

37.2.16 Constant scan mode [M8039 and D8039]

When the special auxiliary relay M8039 is set to ON and a setting value for the constant scan time (in 1-ms units) is stored in special data register D8039, the scan time in the PLC does not become shorter than the value stored in D8039. The PLC pauses for the remaining time when the operation ends earlier, and then returns to step 0.

1. Example program

M8000

M8039 Constant scan mode

RUN monitor FNC 12

MOVP K20 D8039

The constant scan time is set to 20 ms.

2. Cautions

1. When using an instruction executed in synchronization with a scan a) When using an instruction executed in synchronization with a scan such as RAMP (FNC 67), HKY (FNC 71),

SEGL (FNC 74), ARWS (FNC 75) and PR (FNC 77), it is recommended to use the constant scan mode or to use the instruction in a timer interrupt program. b) When using HKY (FNC 71) instruction

It is necessary to use a scan time of 20 ms or more due to the response delays of the key input filter.

2. Scan time display (D8010 to D8012) The scan time specified in the constant scan time is included in the scan time display stored in D8010 to D8012.

37.2.17 State control in program with STL instruction/SFC chart [M8040]

When M8040 is ON, the state relay ON status is not transferred even if the transfer condition is satisfied. The transfer between states is disabled and the output status remains in stopped State.

→ For resetting outputs in a state, refer to Subsection 35.1.7.

Page 877 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 877 · click to enlarge
Page 877

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -) 31

37.2.18 Analog expansion boards [M8260 to M8279 and D8260 to D8279]

FNC277-FNC279 Data Transfer 3

When the analog expansion board is connected, operations and functions are assigned to devices shown in the table below in accordance with the connection position. Operations and functions in the table below are shaded for write-prohibited devices.

→ For details, refer to the Analog Control Edition.

1. Special auxiliary relay (M8260 to M8279)

FNC280-FNC289 High-Speed Processing 2

  • FX 3S /FX 3G PLCs

Number Operation and function

FX 3G -2AD-BD FX 3G -1DA-BD

version Ver. 1.10 or later*1 Ver. 1.10 or later*1

1st analog expansion board

FNC290-FNC299 Extension File Register Control

M 8260 Input mode switching Ch1 Output mode switching

M 8261 Input mode switching Ch2 Not used

M 8262 Not used Not used

M 8263 Not used Not used

M 8264 Not used Output hold mode cancel

M 8265 Not used Not used

FNC300-FNC305 FX 3U -CF-ADP

M 8266 Not used Not used

M 8267 Not used Not used

M 8268 Not used Not used

M 8269 Not used Not used

2nd analog expansion board*2

M 8270 Input mode switching Ch1 Output mode switching

M 8271 Input mode switching Ch2 Not used

M 8272 Not used Not used

M 8273 Not used Not used

M 8274 Not used Output hold mode cancel

M 8275 Not used Not used

M 8276 Not used Not used

M 8277 Not used Not used

M 8278 Not used Not used

M 8279 Not used Not used

*1. In the case of FX3S PLC, all versions are applicable.

*2. Only to FX3G PLC (40-point and 60-point type) can be connected.

A

B

Show 7 more labels / short text on this page
Applicable · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 878 of the Mitsubishi Electronics MELSEC FX3S user manual — FX 3G -2AD-BD FX 3G -1DA-BD
Page 878 · click to enlarge
Page 878

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -)

2. Special data register (D8260 to D8279)

  • FX 3S /FX 3G PLCs

Number Operation and function

FX 3G -2AD-BD FX 3G -1DA-BD

version Ver. 1.10 or later*1 Ver. 1.10 or later*1

1st analog expansion board

D 8260 Input data Ch1 Output data

D 8261 Input data Ch2 Not used

D 8262 Not used Not used

D 8263 Not used Not used

D 8264 Number of averaging times for Ch1 (1 to 4095) Not used

D 8265 Number of averaging times for Ch2 (1 to 4095) Not used

D 8266 Not used Not used

D 8267 Not used Not used

D 8268 Error status Error status

D 8269 Model codeK3 Model code: K4

2nd analog expansion board*2

D 8270 Input data Ch1 Output data

D 8271 Input data Ch2 Not used

D 8272 Not used Not used

D 8273 Not used Not used

D 8274 Number of averaging times for Ch1 (1 to 4095) Not used

D 8275 Number of averaging times for Ch2 (1 to 4095) Not used

D 8276 Not used Not used

D 8277 Not used Not used

D 8278 Error status Error status

D 8279 Model codeK3 Model code: K4

*1. In the case of FX3S PLC, all versions are applicable.

*2. Only to FX3G PLC (40-point and 60-point type) can be connected.

Applicable

Page 879 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 879 · click to enlarge
Page 879

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -) 31

37.2.19 Analog special adapters [M8260 to M8299 and D8260 to D8299]

FNC277-FNC279 Data Transfer 3

When analog special adapters are connected, operations and functions are assigned to the devices shown in the tables below in accordance with the number of connected analog special adapters. Devices which cannot be written to are shaded in the "Operation and function" column.

→ For details, refer to the Analog Control Edition.

1. Special auxiliary relays (M8260 to M8299)

FNC280-FNC289 High-Speed Processing 2

  • FX 3U /FX 3UC PLC

Number Operation and function

FX3U-4AD-ADP FX3U-4DA-ADP FX3U-3A-ADP

version Ver. 1.20 or later*1 Ver. 1.20 or later*1 Ver. 2.61 or later

1st analog special adapter

FNC290-FNC299 Extension File Register Control

M 8260 Input mode switching Ch1 Output mode switching Ch1 Input mode switching Ch1

M 8261 Input mode switching Ch2 Output mode switching Ch2 Input mode switching Ch2

M 8262 Input mode switching Ch3 Output mode switching Ch3 Output mode switching

M 8263 Input mode switching Ch4 Output mode switching Ch4 Not used

M 8264 Not used Output hold mode cancel Ch1 Not used

M 8265 Not used Output hold mode cancel Ch2 Not used

FNC300-FNC305 FX 3U -CF-ADP

M 8266 Not used Output hold mode cancel Ch3 Output hold mode cancel

M 8267 Not used Output hold mode cancel Ch4 Sets whether or not input channel 1 is used.

M 8268 Not used Not used Sets whether or not input channel 2 is used.

M 8269 Not used Not used Sets whether or not output channel is used.

2nd analog special adapter

M 8270 Input mode switching Ch1 Output mode switching Ch1 Input mode switching Ch1

M 8271 Input mode switching Ch2 Output mode switching Ch2 Input mode switching Ch2

M 8272 Input mode switching Ch3 Output mode switching Ch3 Output mode switching

M 8273 Input mode switching Ch4 Output mode switching Ch4 Not used

M 8274 Not used Output hold mode cancel Ch1 Not used

M 8275 Not used Output hold mode cancel Ch2 Not used

M 8276 Not used Output hold mode cancel Ch3 Output hold mode cancel

M 8277 Not used Output hold mode cancel Ch4 Sets whether or not input channel 1 is used.

M 8278 Not used Not used Sets whether or not input channel 2 is used.

M 8279 Not used Not used Sets whether or not output channel is used.

3rd analog special adapter

M 8280 Input mode switching Ch1 Output mode switching Ch1 Input mode switching Ch1

M 8281 Input mode switching Ch2 Output mode switching Ch2 Input mode switching Ch2

M 8282 Input mode switching Ch3 Output mode switching Ch3 Output mode switching

M 8283 Input mode switching Ch4 Output mode switching Ch4 Not used

M 8284 Not used Output hold mode cancel Ch1 Not used

M 8285 Not used Output hold mode cancel Ch2 Not used

M 8286 Not used Output hold mode cancel Ch3 Output hold mode cancel

M 8287 Not used Output hold mode cancel Ch4 Sets whether or not input channel 1 is used.

M 8288 Not used Not used Sets whether or not input channel 2 is used.

M 8289 Not used Not used Sets whether or not output channel is used.

4th analog special adapter

M 8290 Input mode switching Ch1 Output mode switching Ch1 Input mode switching Ch1

M 8291 Input mode switching Ch2 Output mode switching Ch2 Input mode switching Ch2

M 8292 Input mode switching Ch3 Output mode switching Ch3 Output mode switching

A

M 8293 Input mode switching Ch4 Output mode switching Ch4 Not used

M 8294 Not used Output hold mode cancel Ch1 Not used

M 8295 Not used Output hold mode cancel Ch2 Not used

M 8296 Not used Output hold mode cancel Ch3 Output hold mode cancel

M 8297 Not used Output hold mode cancel Ch4 Sets whether or not input channel 1 is used.

M 8298 Not used Not used Sets whether or not input channel 2 is used.

B

M 8299 Not used Not used Sets whether or not output channel is used.

*1. In the case of FX3U PLCs, all versions are applicable.

Show 7 more labels / short text on this page
Applicable · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 880 of the Mitsubishi Electronics MELSEC FX3S user manual — 37.2.19 Analog special adapters [M8260 to M8299 and D8260 to D8299]
Page 880 · click to enlarge
Page 880

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -)

Mitsubishi Electronics MELSEC FX3S — 37.2.19 Analog special adapters [M8260 to M8299 and D8260 to D8299] diagram (page 880)
Fig. 826 · 37.2.19 Analog special adapters [M8260 to M8299 and…

FX3U-4AD-PT(W)-ADP FX3U-4AD-TC-ADP FX3U-4AD-PNK-ADP

version Ver. 1.30 or later*1 Ver. 1.30 or later*1 Ver. 1.30 or later*1

M 8260 Temperature unit selection Temperature unit selection Temperature unit selection

M 8261 Not used Type-K/-J switching Input sensor selection

M 8270 Temperature unit selection Temperature unit selection Temperature unit selection

M 8271 Not used Type-K/-J switching Input sensor selection

M 8280 Temperature unit selection Temperature unit selection Temperature unit selection

M 8281 Not used Type-K/-J switching Input sensor selection

M 8290 Temperature unit selection Temperature unit selection Temperature unit selection

M 8291 Not used Type-K/-J switching Input sensor selection

*1. In the case of FX3U PLCs, all versions are applicable.

Page 881 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 881 · click to enlarge
Page 881

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -) 31

  • FX 3S /FX 3G /FX 3GC PLCs

FNC277-FNC279 Data Transfer 3

FX3U-4AD-ADP FX3U-4DA-ADP FX3U-3A-ADP

version Ver. 1.00 or later Ver. 1.00 or later Ver. 1.20 or later*1

1st analog special adapter

M 8280 Input mode switching Ch1 Output mode switching Ch1 Input mode switching Ch1

FNC280-FNC289 High-Speed Processing 2

M 8281 Input mode switching Ch2 Output mode switching Ch2 Input mode switching Ch2

M 8282 Input mode switching Ch3 Output mode switching Ch3 Output mode switching

M 8283 Input mode switching Ch4 Output mode switching Ch4 Not used

M 8284 Not used Output hold mode cancel Ch1 Not used

M 8285 Not used Output hold mode cancel Ch2 Not used

M 8286 Not used Output hold mode cancel Ch3 Output hold mode cancel

FNC290-FNC299 Extension File Register Control

M 8287 Not used Output hold mode cancel Ch4 Sets whether or not input channel 1 is used.

M 8288 Not used Not used Sets whether or not input channel 2 is used.

M 8289 Not used Not used Sets whether or not output channel is used.

2nd analog special adapter*2

M 8290 Input mode switching Ch1 Output mode switching Ch1 Input mode switching Ch1

M 8291 Input mode switching Ch2 Output mode switching Ch2 Input mode switching Ch2

FNC300-FNC305 FX 3U -CF-ADP

M 8292 Input mode switching Ch3 Output mode switching Ch3 Output mode switching

M 8293 Input mode switching Ch4 Output mode switching Ch4 Not used

M 8294 Not used Output hold mode cancel Ch1 Not used

M 8295 Not used Output hold mode cancel Ch2 Not used

M 8296 Not used Output hold mode cancel Ch3 Output hold mode cancel

M 8297 Not used Output hold mode cancel Ch4 Sets whether or not input channel 1 is used.

M 8298 Not used Not used Sets whether or not input channel 2 is used.

M 8299 Not used Not used Sets whether or not output channel is used.

Number Operation and function

FX 3U -4AD-PT(W)-ADP FX 3U -4AD-TC-ADP FX 3U -4AD-PNK-ADP

version Ver. 1.00 or later Ver. 1.00 or later Ver. 1.00 or later

1st analog special adapter

M 8280 Temperature unit selection Temperature unit selection Temperature unit selection

M 8281 Not used Type-K/-J switching Input sensor selection

M 8282 Not used Not used Not used

M 8283 Not used Not used Not used

M 8284 Not used Not used Not used

M 8285 Not used Not used Not used

M 8286 Not used Not used Not used

M 8287 Not used Not used Not used

M 8288 Not used Not used Not used

M 8289 Not used Not used Not used

2nd analog special adapter *2

M 8290 Temperature unit selection Temperature unit selection Temperature unit selection

M 8291 Not used Type-K/-J switching Input sensor selection

M 8292 Not used Not used Not used

M 8293 Not used Not used Not used

A

M 8294 Not used Not used Not used

M 8295 Not used Not used Not used

M 8296 Not used Not used Not used

M 8297 Not used Not used Not used

M 8298 Not used Not used Not used

M 8299 Not used Not used Not used

B

*1. In the case of FX3S/FX3GC PLCs, all versions are applicable.

*2. Can be connected only to FX3G PLC (40-point and 60-point type) and FX3GC PLC.

Show 10 more labels / short text on this page
Operation and function · Number · Applicable · SFC•STL Programming · Applicable · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 882 of the Mitsubishi Electronics MELSEC FX3S user manual — 2. Special data registers (D8260 to D8299)
Page 882 · click to enlarge
Page 882

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -)

2. Special data registers (D8260 to D8299)

  • FX 3U /FX 3UC PLC

Number Operation and function FX3U-4AD-ADP FX3U-4DA-ADP FX3U-3A-ADP Applicable

version Ver. 1.20 or later*1 Ver. 1.20 or later*1 Ver. 2.61 or later

1st analog special adapter D 8260 Input data Ch1 Output data Ch1 Input data Ch1 D 8261 Input data Ch2 Output data Ch2 Input data Ch2 D 8262 Input data Ch3 Output data Ch3 Output data D 8263 Input data Ch4 Output data Ch4 Not used

D 8264 Number of averaging times for Ch1 (1 to 4095) Not used Number of averaging times for Ch1 (1 to 4095)

D 8265 Number of averaging times for Ch2 (1 to 4095) Not used Number of averaging times for Ch2 (1 to 4095)

D 8266 Number of averaging times for Ch3 (1 to 4095) Not used Not used

D 8267 Number of averaging times for Ch4 (1 to 4095) Not used Not used

D 8268 Error status Error status Error status D 8269 Model code: K1 Model code: K2 Model code: K50 2nd analog special adapter D 8270 Input data Ch1 Output data Ch1 Input data Ch1 D 8271 Input data Ch2 Output data Ch2 Input data Ch2 D 8272 Input data Ch3 Output data Ch3 Output data D 8273 Input data Ch4 Output data Ch4 Not used

D 8274 Number of averaging times for Ch1 (1 to 4095) Not used Number of averaging times for Ch1 (1 to 4095)

D 8275 Number of averaging times for Ch2 (1 to 4095) Not used Number of averaging times for Ch2 (1 to 4095)

D 8276 Number of averaging times for Ch3 (1 to 4095) Not used Not used

D 8277 Number of averaging times for Ch4 (1 to 4095) Not used Not used

D 8278 Error status Error status Error status D 8279 Model code: K1 Model code: K2 Model code: K50 3rd analog special adapter D 8280 Input data Ch1 Output data Ch1 Input data Ch1 D 8281 Input data Ch2 Output data Ch2 Input data Ch2 D 8282 Input data Ch3 Output data Ch3 Output data D 8283 Input data Ch4 Output data Ch4 Not used

D 8284 Number of averaging times for Ch1 (1 to 4095) Not used Number of averaging times for Ch1 (1 to 4095)

D 8285 Number of averaging times for Ch2 (1 to 4095) Not used Number of averaging times for Ch2 (1 to 4095)

D 8286 Number of averaging times for Ch3 (1 to 4095) Not used Not used

D 8287 Number of averaging times for Ch4 (1 to 4095) Not used Not used

D 8288 Error status Error status Error status D 8289 Model code: K1 Model code: K2 Model code: K50 4th analog special adapter D 8290 Input data Ch1 Output data Ch1 Input data Ch1 D 8291 Input data Ch2 Output data Ch2 Input data Ch2 D 8292 Input data Ch3 Output data Ch3 Output data D 8293 Input data Ch4 Output data Ch4 Not used

D 8294 Number of averaging times for Ch1 (1 to 4095) Not used Number of averaging times for Ch1 (1 to 4095)

D 8295 Number of averaging times for Ch2 (1 to 4095) Not used Number of averaging times for Ch2 (1 to 4095)

D 8296 Number of averaging times for Ch3 (1 to 4095) Not used Not used

D 8297 Number of averaging times for Ch4 (1 to 4095) Not used Not used

D 8298 Error status Error status Error status D 8299 Model code: K1 Model code: K2 Model code: K50

*1. In the case of FX3U PLCs, all versions are applicable.

Page 883 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 883 · click to enlarge
Page 883

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -) 31

FNC277-FNC279 Data Transfer 3

Number Operation and function FX3U-4AD-PT(W)-ADP FX3U-4AD-TC-ADP FX3U-4AD-PNK-ADP Applicable

version Ver. 1.30 or later*1 Ver. 1.30 or later*1 Ver. 1.30 or later*1

1st analog special adapter D 8260 Measured temperature Ch1 Measured temperature Ch1 Measured temperature Ch1 D 8261 Measured temperature Ch2 Measured temperature Ch2 Measured temperature Ch2 D 8262 Measured temperature Ch3 Measured temperature Ch3 Measured temperature Ch3 D 8263 Measured temperature Ch4 Measured temperature Ch4 Measured temperature Ch4

FNC280-FNC289 High-Speed Processing 2

D 8264 Number of averaging times for Ch1 (1 to 4095)

Number of averaging times for Ch1 (1 to 4095)

Number of averaging times for Ch1 (1 to 4095)

D 8265 Number of averaging times for Ch2 (1 to 4095)

Number of averaging times for Ch2 (1 to 4095)

Number of averaging times for Ch2 (1 to 4095)

D 8266 Number of averaging times for Ch3 (1 to 4095)

Number of averaging times for Ch3 (1 to 4095)

Number of averaging times for Ch3 (1 to 4095)

FNC290-FNC299 Extension File Register Control

D 8267 Number of averaging times for Ch4 (1 to 4095)

Number of averaging times for Ch4 (1 to 4095) D 8268 Error status Error status Error status

Number of averaging times for Ch4 (1 to 4095)

D 8269 Model codeK20, K21 *2 Model code: K10 Model code: K11

2nd analog special adapter D 8270 Measured temperature Ch1 Measured temperature Ch1 Measured temperature Ch1 D 8271 Measured temperature Ch2 Measured temperature Ch2 Measured temperature Ch2 D 8272 Measured temperature Ch3 Measured temperature Ch3 Measured temperature Ch3 D 8273 Measured temperature Ch4 Measured temperature Ch4 Measured temperature Ch4

FNC300-FNC305 FX 3U -CF-ADP

D 8274 Number of averaging times for Ch1 (1 to 4095)

Number of averaging times for Ch1 (1 to 4095)

Number of averaging times for Ch1 (1 to 4095)

D 8275 Number of averaging times for Ch2 (1 to 4095)

Number of averaging times for Ch2 (1 to 4095)

Number of averaging times for Ch2 (1 to 4095)

D 8276 Number of averaging times for Ch3 (1 to 4095)

Number of averaging times for Ch3 (1 to 4095)

Number of averaging times for Ch3 (1 to 4095)

D 8277 Number of averaging times for Ch4 (1 to 4095)

Number of averaging times for Ch4 (1 to 4095) D 8278 Error status Error status Error status

Number of averaging times for Ch4 (1 to 4095)

D 8279 Model codeK20, K21 *2 Model code: K10 Model code: K11

3rd analog special adapter D 8280 Measured temperature Ch1 Measured temperature Ch1 Measured temperature Ch1 D 8281 Measured temperature Ch2 Measured temperature Ch2 Measured temperature Ch2 D 8282 Measured temperature Ch3 Measured temperature Ch3 Measured temperature Ch3 D 8283 Measured temperature Ch4 Measured temperature Ch4 Measured temperature Ch4

D 8284 Number of averaging times for Ch1 (1 to 4095)

Number of averaging times for Ch1 (1 to 4095)

Number of averaging times for Ch1 (1 to 4095)

D 8285 Number of averaging times for Ch2 (1 to 4095)

Number of averaging times for Ch2 (1 to 4095)

Number of averaging times for Ch2 (1 to 4095)

D 8286 Number of averaging times for Ch3 (1 to 4095)

Number of averaging times for Ch3 (1 to 4095)

Number of averaging times for Ch3 (1 to 4095)

D 8287 Number of averaging times for Ch4 (1 to 4095)

Number of averaging times for Ch4 (1 to 4095) D 8288 Error status Error status Error status

Number of averaging times for Ch4 (1 to 4095)

D 8289 Model codeK20, K21 *2 Model code: K10 Model code: K11

4th analog special adapter D 8290 Measured temperature Ch1 Measured temperature Ch1 Measured temperature Ch1 D 8291 Measured temperature Ch2 Measured temperature Ch2 Measured temperature Ch2 D 8292 Measured temperature Ch3 Measured temperature Ch3 Measured temperature Ch3 D 8293 Measured temperature Ch4 Measured temperature Ch4 Measured temperature Ch4

D 8294 Number of averaging times for Ch1 (1 to 4095)

Number of averaging times for Ch1 (1 to 4095)

Number of averaging times for Ch1 (1 to 4095)

A

D 8295 Number of averaging times for Ch2 (1 to 4095)

Number of averaging times for Ch2 (1 to 4095)

Number of averaging times for Ch2 (1 to 4095)

D 8296 Number of averaging times for Ch3 (1 to 4095)

Number of averaging times for Ch3 (1 to 4095)

Number of averaging times for Ch3 (1 to 4095)

D 8297 Number of averaging times for Ch4 (1 to 4095)

Number of averaging times for Ch4 (1 to 4095) D 8298 Error status Error status Error status

Number of averaging times for Ch4 (1 to 4095)

B

D 8299 Model codeK20, K21 *2 Model code: K10 Model code: K11

*1. In the case of FX3U PLCs, all versions are applicable.

*2. The model code is "20" for the PT-ADP, and "21" for the PTW-ADP.

Show 6 more labels / short text on this page
SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 884 of the Mitsubishi Electronics MELSEC FX3S user manual — 37.2.19 Analog special adapters [M8260 to M8299 and D8260 to D8299]
Page 884 · click to enlarge
Page 884

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -)

  • FX 3S /FX 3G /FX 3GC PLCs

Number Operation and function

FX3U-4AD-ADP FX3U-4DA-ADP FX3U-3A-ADP

version Ver. 1.00 or later Ver. 1.00 or later Ver. 1.20 or later*1

1st analog special adapter

D 8280 Input data Ch1 Output data Ch1 Input data Ch1

D 8281 Input data Ch2 Output data Ch2 Input data Ch2

D 8282 Input data Ch3 Output data Ch3 Output data

D 8283 Input data Ch4 Output data Ch4 Not used

D 8284 Number of averaging times for Ch1 (1 to 4095) Not used Number of averaging times for Ch1 (1 to 4095)

D 8285 Number of averaging times for Ch2 (1 to 4095) Not used Number of averaging times for Ch2 (1 to 4095)

D 8286 Number of averaging times for Ch3 (1 to 4095) Not used Not used

D 8287 Number of averaging times for Ch4 (1 to 4095) Not used Not used

D 8288 Error status Error status Error status

D 8289 Model codeK1 Model code: K2 Model code: K50

2nd analog special adapter*2

D 8290 Input data Ch1 Output data Ch1 Input data Ch1

D 8291 Input data Ch2 Output data Ch2 Input data Ch2

D 8292 Input data Ch3 Output data Ch3 Output data

D 8293 Input data Ch4 Output data Ch4 Not used

D 8294 Number of averaging times for Ch1 (1 to 4095) Not used Number of averaging times for Ch1 (1 to 4095)

D 8295 Number of averaging times for Ch2 (1 to 4095) Not used Number of averaging times for Ch2 (1 to 4095)

D 8296 Number of averaging times for Ch3 (1 to 4095) Not used Not used

D 8297 Number of averaging times for Ch4 (1 to 4095) Not used Not used

D 8298 Error status Error status Error status

D 8299 Model codeK1 Model code: K2 Model code: K50

*1. In the case of FX3S/FX3G PLCs, all versions are applicable.

*2. Can be connected only to FX3G PLC (40-point and 60-point type) and FX3GC PLC.

Applicable

Page 885 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 885 · click to enlarge
Page 885

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

37 Operation of Special Devices (M8000 -, D8000 -)

37.2 Supplement of Special Devices (M8000 - and D8000 -) 31

FNC277-FNC279 Data Transfer 3

Number Operation and function

FX3U-4AD-PT(W)-ADP FX3U-4AD-TC-ADP FX3U-4AD-PNK-ADP

version Ver. 1.00 or later Ver. 1.00 or later Ver. 1.00 or later

1st analog special adapter

D 8280 Measured temperature Ch1 Measured temperature Ch1 Measured temperature Ch1

D 8281 Measured temperature Ch2 Measured temperature Ch2 Measured temperature Ch2

FNC280-FNC289 High-Speed Processing 2

D 8282 Measured temperature Ch3 Measured temperature Ch3 Measured temperature Ch3

D 8283 Measured temperature Ch4 Measured temperature Ch4 Measured temperature Ch4

D 8284 Number of averaging times for Ch1 (1 to 4095)

Number of averaging times for Ch1 (1 to 4095)

Number of averaging times for Ch1 (1 to 4095)

D 8285 Number of averaging times for Ch2 (1 to 4095)

Number of averaging times for Ch2 (1 to 4095)

Number of averaging times for Ch2 (1 to 4095)

D 8286 Number of averaging times for Ch3 (1 to 4095)

Number of averaging times for Ch3 (1 to 4095)

Number of averaging times for Ch3 (1 to 4095)

FNC290-FNC299 Extension File Register Control

D 8287 Number of averaging times for Ch4 (1 to 4095)

Number of averaging times for Ch4 (1 to 4095)

Number of averaging times for Ch4 (1 to 4095)

D 8288 Error status Error status Error status

D 8289 Model codeK20, K21 *2 Model code: K10 Model code: K11

2nd analog special adapter*1

FNC300-FNC305 FX 3U -CF-ADP

D 8290 Measured temperature Ch1 Measured temperature Ch1 Measured temperature Ch1

D 8291 Measured temperature Ch2 Measured temperature Ch2 Measured temperature Ch2

D 8292 Measured temperature Ch3 Measured temperature Ch3 Measured temperature Ch3

D 8293 Measured temperature Ch4 Measured temperature Ch4 Measured temperature Ch4

D 8294 Number of averaging times for Ch1 (1 to 4095)

Number of averaging times for Ch1 (1 to 4095)

Number of averaging times for Ch1 (1 to 4095)

D 8295 Number of averaging times for Ch2 (1 to 4095)

Number of averaging times for Ch2 (1 to 4095)

Number of averaging times for Ch2 (1 to 4095)

D 8296 Number of averaging times for Ch3 (1 to 4095)

Number of averaging times for Ch3 (1 to 4095)

Number of averaging times for Ch3 (1 to 4095)

D 8297 Number of averaging times for Ch4 (1 to 4095)

Number of averaging times for Ch4 (1 to 4095)

Number of averaging times for Ch4 (1 to 4095)

D 8298 Error status Error status Error status

D 8299 Model codeK20, K21 *2 Model code: K10 Model code: K11

*1. Can be connected only to FX3G PLC (40-point and 60-point type) and FX3GC PLC.

*2. The model code is "20" for the PT-ADP, and "21" for the PTW-ADP.

A

B

Show 7 more labels / short text on this page
Applicable · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 886 of the Mitsubishi Electronics MELSEC FX3S user manual — FX 3U PLC
Page 886 · click to enlarge
Page 886

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

38 Error Check Method and Error Code List

38.1 States and Colors of LEDs PLC Operation Status

38. Error Check Method and Error Code List

When an error occurs while the program is being executed, troubleshoot the cause of the error in accordance with this chapter. For error details, refer to the Data Communication Edition and the Hardware Edition of the PLC main unit.

38.1 States and Colors of LEDs PLC Operation Status

When an error has occurred, the PLC state can be checked using the LED status lights on the PLC.

FX 3S PLC

FX 3GC PLC

Mitsubishi Electronics MELSEC FX3S — FX 3S PLC diagram (page 886)
Fig. 827
Mitsubishi Electronics MELSEC FX3S — FX 3S PLC diagram (page 886)
Fig. 828

FX 3G PLC

FX 3UC (D, DS, DSS) PLC

Mitsubishi Electronics MELSEC FX3S — FX 3G PLC diagram (page 886)
Fig. 829
Mitsubishi Electronics MELSEC FX3S — FX 3G PLC diagram (page 886)
Fig. 830

FX 3U PLC

FX 3UC -32MT-LT(-2) PLC

Mitsubishi Electronics MELSEC FX3S — FX 3U PLC diagram (page 886)
Fig. 831

POWER (Green) RUN (Green) BATT (Red) ERROR (Red) L. RUN (Green) L. ERR (Red)

Page 887 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 887 · click to enlarge
Page 887

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

38 Error Check Method and Error Code List

38.1 States and Colors of LEDs PLC Operation Status 31

38.1.1 POWER (POW) LED [lit, flickering or unlit]

FNC277-FNC279 Data Transfer 3

LED status PLC status Action

Lit The voltage is correctly supplied to the power terminal. The power supply is normal.

  • One of the following has occurred:
  • The voltage or current is incorrectly supplied to the power terminal.
  • The wiring is incorrect.
  • There is fault inside the PLC.
  • Check the power supply voltage.
  • Disconnect cables except the power cable, turn the PLC power ON again, and verify that the status is changed. If the status is not improved, consult a Mitsubishi Electric representative.

FNC280-FNC289 High-Speed Processing 2

  • One of the following has occurred:
  • The power is OFF.
  • The voltage is incorrectly supplied to the power terminal.
  • There is a break in the power cable.

When the power is not OFF, check the power supply and power line route. When the power is correctly supplied, consult a Mitsubishi Electric representative.

FNC290-FNC299 Extension File Register Control

38.1.2 RUN LED [lit or unlit]

LED status PLC status Action

Lit Sequence program is executing. The PLC operation status is indicated. This LED is not lit depending on the ERROR (ERR) LED status. (Refer to Subsection 38.1.4.) Unlit Sequence program is stopped.

FNC300-FNC305 FX 3U -CF-ADP

38.1.3 BATT (BAT) LED [lit or unlit] [FX 3U /FX 3UC ]

LED status PLC status Action

Lit The battery voltage is low. Replace the battery as soon as possible. (Refer to FX3U/FX3UC Hardware edition.)

Unlit The battery voltage exceeds the value set in D8006. The battery is normal.

38.1.4 ALM LED [lit or unlit] [FX 3G /FX 3GC ]

This LED is valid when the optional battery is installed and the battery mode is selected using a parameter.

LED status PLC status Action

Lit The battery voltage is low. Replace the battery as soon as possible. (Refer to FX3G/FX3GC Hardware edition.)

Unlit The battery voltage exceeds the value set in D8006. The battery is normal.

A

B

Show 8 more labels / short text on this page
Flickering · Unlit · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 888 of the Mitsubishi Electronics MELSEC FX3S user manual — TEST
Page 888 · click to enlarge
Page 888

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

38 Error Check Method and Error Code List

38.1 States and Colors of LEDs PLC Operation Status

38.1.5 ERROR (ERR) LED [lit, flickering or unlit]

LED status PLC status Action

1) Change the PLC mode to STOP, and turn ON the PLC power again. When the ERROR (ERR) LED is off, a watchdog timer error occurred. Take one of the following actions: - Review the program, and make sure that the maximum value (D8012) of the scan time is not larger than the set value (D8000) of the watchdog timer. - Make sure that an input used for input interrupt or pulse catch does not abnormally turn ON and OFF several times in one scan time. - Make sure that the frequency of the pulse (duty: 50%) input to a high-speed counter is within the specifications range. - Adding a WDT instruction Use two or more WDT instructions in a program so that the watchdog timer is reset several times in one scan time. - Change the set value of the watchdog timer Change the set value (D8000) of the watchdog timer in a program so that it is larger than the maximum value (D8012) of the scan time. 2) Remove the PLC, and connect another power supply to the PLC. If the ERROR (ERR) LED is off, the cause of the error may be noise. Examine the following action: - Check the wiring for grounding, and then review the wiring route and installation location. - Add a noise filter in the power line. 3) If the ERROR (ERR) LED is not off even after the step 1) or 2), consult a Mitsubishi Electric representative.

A watchdog timer error has occurred, or the hardware of the PLC may be damaged.

  • One of the following errors occur in PLC:
  • Parameter error
  • Syntax error
  • Circuit error

Execute PLC diagnostics and program check by programming tool. For instructions, refer to Section 38.4.

If PLC operation is a failure, execute the PLC diagnostics or program check by programming tool. An I/O configuration error, serial communication error, or operation error may occur.

Unlit Error which stops PLC has not occurred.

38.1.6 L RUN LED [FX 3UC -32MT-LT(-2)]

Mode LED status PLC status Action

Lit Data link is executing ⎯

ONLINE

Unlit Data link is stopped • Take action according to the L ERR LED status.

CONFIG*1 Lit Data link is executing ⎯

Unlit Data link is stopped • Take action according to the L ERR LED status.

Lit The self-loopback test is normally finished. ⎯

The self-loopback test is abnormally finished. (This LED is off while the self-loopback test is executing.)

TEST

  • Make sure that the power is correctly supplied to the PLC.
  • If the L RUN LED is not off even after the above check, consult a Mitsubishi Electric representative.

*1. FX3UC-32MT-LT only.

Lit · Flickering · Unlit

Page 889 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 889 · click to enlarge
Page 889

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

38 Error Check Method and Error Code List

38.1 States and Colors of LEDs PLC Operation Status 31

38.1.7 L ERR LED [FX 3UC -32MT-LT(-2)]

FNC277-FNC279 Data Transfer 3

Mode LED status PLC status Action

  • Unit disconnected
  • Outside-control-range station error
  • RD station number setting error
  • Securely connect the built-in master to remote I/O units and remote device stations on the network.
  • Make sure that the connected remote I/O units and remote device stations are consistent with the detailed information on remote stations.

FNC280-FNC289 High-Speed Processing 2

ONLINE

  • Securely connect the built-in master to remote I/O units and remote device stations on the network.
  • Make sure that the connected remote I/O units and remote device stations are consistent with the detailed information on remote stations.

Flickering All stations are abnormal

Unlit Data link is being normally executed ⎯

FNC290-FNC299 Extension File Register Control

Used station numbers mismatch. (Remote stations are checked while the remote station information is edited.)

  • Securely connect the built-in master to remote I/O units and remote device stations on the network.
  • Make sure that the connected remote I/O units and remote device stations are consistent with the detailed information on remote stations.
  • Verify that remote device station numbers are within the allowable range. Flickering

CONFIG *1

All stations are abnormal. (Remote stations are checked while the remote station information is edited.)

FNC300-FNC305 FX 3U -CF-ADP

Unlit Data link is being normally executed ⎯

  • Make sure that the power is correctly supplied to the PLC.
  • If the L RUN LED is on even after the above check, consult a Mitsubishi Electric representative.

Lit The self-loopback test is abnormally finished.

TEST

The self-loopback test is normally finished. (This LED is off while the self- loopback test is executing.)

*1. FX3UC-32MT-LT only.

→ For details, refer to the Hardware Edition of the PLC main unit.

A

B

Show 10 more labels / short text on this page
Lit · Lit · SFC•STL Programming · Unlit · ⎯ · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 890 of the Mitsubishi Electronics MELSEC FX3S user manual — M 0 8 3 6
Page 890 · click to enlarge
Page 890

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

38 Error Check Method and Error Code List

38.2 Error Code Check Method and Indication

38.2 Error Code Check Method and Indication

38.2.1 Error code check method by display module

The error code can be checked by programming tool and display module. This subsection explains how to set the real time clock in the display module FX3U-7DM (built in the FX3UC-32MT-LT (-2)). Refer to the following manual for the display module FX3G-5DM.

→ FX 3G Series User’s Manual - Hardware Edition

Error code check method by display module

1. Scroll to "ErrorCheck" by pressing [+] or [-] key on "MENU screen" (shown on the right figure). For the menu system, refer to FX 3U /FX 3UC Hardware Edition. On this menu screen, the operation keys are as shown below:

key Contents of operation

LANGUAGE

ESC Return to "TOP screen".

Moves the cursor up. Moves the cursor at high-speed when pressed for 1 second or more. When the cursor is located at the top, [-] key operation is invalid.

Moves the cursor down. Moves the cursor at high-speed when pressed for 1 second or more. When the cursor is located at the bottom, [+] key operation is invalid.

OK Selects a flickering item with the cursor.

*1. Displayed in the FX3UC-32MT-LT-2.

2. Pressing [OK] key executes the error check and displays the result on "error display screen" (shown in the right figure). Press [ESC] key to cancel the operation and return to "Top screen".

When error does not occur

3. If two or more errors occur, press [+] or [-] key to changeover the page.

key Contents of operation

When one error occurs

ESC Returns to "menu screen".

When one or no error Is invalid.

When two or more errors Displays the previous error display screen.

M 0 8 6 6

When one or no error Is invalid.

When two or more errors Displays the next error display screen.

Error code 6 6 1 2

OK Returns to "menu screen".

2 or more errors occur

M 0 8 0 6

Error code 1 0 2 0

[4] Number of errors at same time (When two or more errors occur, this information displays.)

/ 2 2 [4]

4. Press [ESC] key to cancel the operation and return to "menu screen".

M 0 8 3 6

Error code 6 3 0 1

Show 39 more labels / short text on this page
Monitor/Test · Operation · ErrorCheck · Contrast · ClockMenu · EntryCode · + · ClearAllDev · PLC status · ScanTime · Cassette · CC-Link/LT *1 · ErrorCheck · No errors · Operation · ErrorCheck · [1] · [2] · Ladder error · + · [3] · Displayed contents · ErrorCheck · / 1 2 · [4] · [1] · Displayed contents · [2] · I/O error · [1] Error flag · [2] Error name · [3] · [3] Error code · + - · ErrorCheck · [1] · [2] · Link error1 · [3]
Page 891 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 891 · click to enlarge
Page 891

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

38 Error Check Method and Error Code List

38.2 Error Code Check Method and Indication 31

38.2.2 Error code check method by GX Works2

FNC277-FNC279 Data Transfer 3

1 Connect a personal computer to PLC. 2 Execute PLC diagnostics.

FNC280-FNC289 High-Speed Processing 2

Click [Diagnostics]→[PLC Diagnostics] on the menu bar, and execute the PLC diagnostics.

Mitsubishi Electronics MELSEC FX3S — 38.2.2 Error code check method by GX Works2 diagram (page 891)
Fig. 832 · 38.2.2 Error code check method by GX Works2

FNC290-FNC299 Extension File Register Control

FNC300-FNC305 FX 3U -CF-ADP

3 Check the diagnostics result.

When the following dialog box appears, check the contents of the error.

Exampleone error occurs
Mitsubishi Electronics MELSEC FX3S — FNC300-FNC305 FX 3U -CF-ADP diagram (page 891)
Fig. 833

Open the error help dialog box to check the error details.

The error in PLC is displayed.

The LED status of FX PLC is displayed.

A

B

Show 6 more labels / short text on this page
SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 892 of the Mitsubishi Electronics MELSEC FX3S user manual — 38.2.3 Error indication
Page 892 · click to enlarge
Page 892

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

38 Error Check Method and Error Code List

38.2 Error Code Check Method and Indication

38.2.3 Error indication

The table below shows the error expression in this manual, GX Works2, GX Developer, and display modules (FX3U- 7DM). • Comparison between this manual and GX Works2.

Mitsubishi Electronics MELSEC FX3S — 38.2.3 Error indication diagram (page 892)
Fig. 834 · 38.2.3 Error indication

Serial communication error 2 [ch2] Serial Communication Error 2[ch2]

  • Comparison between this manual and GX Developer
Mitsubishi Electronics MELSEC FX3S — 38.2.3 Error indication diagram (page 892)
Fig. 835 · 38.2.3 Error indication
  • Comparison between this manual and the display module (FX 3U -7DM)
Mitsubishi Electronics MELSEC FX3S — 38.2.3 Error indication diagram (page 892)
Fig. 836 · 38.2.3 Error indication
Page 893 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 893 · click to enlarge
Page 893

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

38 Error Check Method and Error Code List

38.3 Supplementary Explanation of Devices for Error Detection 31

38.3 Supplementary Explanation of Devices for Error Detection

FNC277-FNC279 Data Transfer 3

38.3.1 Error detection (M8060 to/D8060 to)

When the M8060, M8061, M8064 to M8067 turn ON, the smallest ON device number is stored in D8004, and M8004 turns ON.

FNC280-FNC289 High-Speed Processing 2

1. M8060,M8061,M8064 to M8067 are cleared when the PLC mode switches from STOP to RUN. Note that M8068 and D8068 do not clear.

2) When turning M8069 ON in advance, PLC will enter STOP mode (as M8061 PLC hardware error occurs) if a failure occurs in an I/O extension unit, an extension power supply module, or an extension unit/block. When turning M8069 ON, PLC executes I/O bus check. If an error is found, error code 6103 or 6104 is stored to D8061, and M8061 turns ON. When error code 6104 is stored, M8009 turns ON, and the PLC stores the I/O numbers following the extension power supply module or the powered extension unit with DC 24V output failure to D8009.

FNC290-FNC299 Extension File Register Control

3. If the unit or block corresponding to a programmed I/O number is not actually loaded, M8060 is set to ON and the first device number of the erroneous block is written to D8060.
ExampleWhen X020 is unconnected

1 0 2 0

FNC300-FNC305 FX 3U -CF-ADP

1. Input (X), 0: Output (Y)

*1. 10 to 337 in FX3U/FX3UC PLCs, and 10 to 177 in FX3G/FX3GC PLCs

4. When a device number is specified directly or indirectly with an index by the LD, AND, OR or OUT instruction, and if the device numbers specified in those instructions are not actually loaded, M8316 will turn ON and the error step number in the instruction will be written to D8317 (high-order bits) and D8316 (low-order bits).

A

B

Show 9 more labels / short text on this page
BCD conversion value · Device number · *1 · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 894 of the Mitsubishi Electronics MELSEC FX3S user manual — 38.3.3 Error detection timing
Page 894 · click to enlarge
Page 894

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

38 Error Check Method and Error Code List

38.3 Supplementary Explanation of Devices for Error Detection

38.3.2 Operations of special devices for error detection

Special auxiliary relays for error detection and special data registers for error detection operate in the relationship shown below. The state of error occurrence can be checked by monitoring the contents of auxiliary relays and data registers or by using the PLC diagnosis function programming tool.

By using the PLC diagnosis function provided in the programming tool (GX Works2, etc.), Graphic Operation Terminal (GOT1000) or the display module (FX 3U-7DM), the contents of the error code (D8060 to D8067, D8438, D8449) can be checked in message format.

D8009 M8009 24V DC down

D8060 M8060 I/O configuration error

D8061 M8061 PLC hardware error

M8069 I/O bus check

M8004

D8062 M8062 Serial communication error 0

Special M number (smallest device number) of error occurrence

ON when an error occurs

D8063 M8063 Serial communication error 1

D8438 M8438 Serial communication error 2

D8064 M8064 Parameter error

32K Error step number The error step number is also stored in D8069, but only for programs 32K steps and less.

D8065 M8065 Syntax error

D8314 D8315

D8066 M8066 Circuit error

D8067 M8067 Operation error

1st error step latched The error step number is also stored in D8068, but only for programs 32K steps and less.

M8068 Operation error latch

After clearing errors, forcibly clear M8068 using the device monitor function in a programming tool.

D8317 M8316 Unconnected I/O designation error D8316

M8318 BFM initialization failure D8318

D8487 D8449 D8489

M8487 M8449 M8489

USB communication error Special block error Special parameter error

38.3.3 Error detection timing

Error item ERROR (ERR)

The status of the PLC

M8060 I/O configuration error Unlit RUN/STOP is Continued Check Check ⎯

M8061 PLC hardware error Lit Forced STOP Check ⎯ Always

M8062 Serial communication error 0 [ch 0] Unlit RUN/STOP is Continued ⎯ ⎯ When receiving signal from counterpart station

M8063 Serial communication error 1 [ch 1] Unlit RUN/STOP is Continued ⎯ ⎯ When receiving signal from counterpart station

M8438 Serial communication error 2 [ch 2] Unlit RUN/STOP is Continued ⎯ ⎯ When receiving signal from counterpart station

M8064 Parameter error Flickering STOP is Continued

When program is changed (STOP) When program is transferred (STOP)

M8065 Syntax error Flickering STOP is Continued

M8066 Circuit error Flickering STOP is Continued

M8067 Operation error Unlit RUN is Continued ⎯ ⎯ RUN mode M8068 Operation error latch Unlit RUN is Continued

M8109 I/O refresh error Unlit RUN/STOP is Continued ⎯ ⎯ Always

M8316 Unconnected I/O designation error Unlit RUN is Continued ⎯ ⎯ RUN mode

M8318 BFM initialization failure Unlit RUN is Continued ⎯ Check ⎯

M8449 Special block error Unlit RUN/STOP is Continued ⎯ ⎯ Always

M8487 USB communication error [USB] Unlit RUN/STOP is Continued ⎯ ⎯ When receiving signal from counterpart station

M8489 Special parameter error Unlit STOP is Continued Check ⎯ When special parameter is changed (STOP)

D8166 Special block error condition Unlit RUN/STOP is Continued ⎯ ⎯ Always

Show 14 more labels / short text on this page
Error step number · Error unit number · Error BFM number · Error detection timing · When power is · When PLC mode · LED status · after error detection · turned from · switches from · Other timing · OFF to ON · STOP to RUN · Check Check
Page 895 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 895 · click to enlarge
Page 895

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

38 Error Check Method and Error Code List

38.4 Error Code List and Action 31

38.4 Error Code List and Action

FNC277-FNC279 Data Transfer 3

When a program error occurs in the PLC, the error code is stored in the special data registers D8060 to D8067, D8438, D8449, D8487 and D8489, and the error bit turns ON in the special data register D8166 as follows. The following actions should be taken.

PLC operation at error occurrence Contents of error Action

FNC280-FNC289 High-Speed Processing 2

I/O configuration error [M8060(D8060)]

The head number of unconnected I/O device

ExampleWhen X020 is unconnected

1 0 2 0

FNC290-FNC299 Extension File Register Control

Unconnected I/O relay numbers are programmed. The PLC continues its operation. Modify the program, check wiring connection, or add the appropriate unit/ block.

Ex- ample:

1. Input (X), 0: Output (Y)
  • 1st to 3rd digits: Device number FX 3G /FX 3GC :10 to 177 FX 3U /FX 3UC :10 to 337
  • 4th digit: I/O type (1 = input (X), 0 = output (Y)) Example: When 1020 is stored in D8060 Inputs X020 and later are unconnected.

FNC300-FNC305 FX 3U -CF-ADP

Serial communication error 2 [M8438(D8438)]

0000 ⎯ No error

Parity, overrun or framing error

3802 Communication character error

3803 Communication data sum check error

  • Ethernet communication, inverter communication, computer link and programming: Ensure the parameters are correctly set according to their applications.
  • N:N network, parallel link, MODBUS communication, etc.: Check programs according to applications.
  • Remote maintenance: Ensure modem power is ON and check the settings of the AT commands.
  • Wiring: Check the communication cables for correct wiring.

3804 Communication data format error

3806 Communication time-out detected

3807 Modem initialization error

3808 N:N network parameter error

3809 N:N Network setting error

3812 Parallel link character error

3813 Parallel link sum error

3814 Parallel link format error

3820 Inverter communication error

3821 MODBUS communication error

When the memory cassette is used, check whether it is mounted correctly. If the problem persists or if the memory cassette is not used, something may be malfunctioning inside the PLC. Consult your local Mitsubishi Electric representative.

3830 Memory access error

3840 Special adapter connection error Check connection of the special adapter.

PLC hardware error [M8061(D8061)]

0000 ⎯ No error

When the memory cassette is used, check whether it is mounted correctly. If the problem persists or if the memory cassette is not used, something may be malfunctioning inside the PLC. Consult your local Mitsubishi Electric representative.

Isolate the PLC and supply power to it using a different power supply. If the ERROR(ERR) LED turns OFF, noise may be affecting the PLC. Take the following measures.

A

- Check the ground wiring, and reexamine the wiring route and installation location. - Fit a noise filter onto the power supply line. If the ERROR(ERR) LED does not turn OFF even after the above actions are taken, consult your local Mitsubishi Electric representative.

6102 Operation circuit error

B

Show 16 more labels / short text on this page
Error code · BCD conversion value · Device number · Continues · operation · SFC•STL Programming · 3805 Command error · Continues · Interrupt Function · operation · Special Device · Error Code · Memory access error · Stops operation · Version Up Information · Execution Times
Page 896 of the Mitsubishi Electronics MELSEC FX3S user manual — 38.4 Error Code List and Action
Page 896 · click to enlarge
Page 896

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

38 Error Check Method and Error Code List

38.4 Error Code List and Action

PLC operation at error occurrence Contents of error Action

PLC hardware error [M8061(D8061)]

I/O bus error (M8069 = ON) Verify that extension cables are correctly connected. 6104 Powered extension unit 24 V failure (M8069 = ON)

6105 Watchdog timer error Confirm user program. The scan time exceeds the value stored in D8000.

  • When turning the power ON to the main unit, a 24V power failure occurs in a powered extension unit. (The error occurs if the 24V power is not supplied for 10 seconds or more after main power turns ON.)
  • When turning main power ON, I/O assignment to CCLink/LT (built into the FX 3UC -32MT-LT(-2) PLC) is disabled.

6106 I/O table creation error (CPU error)

Check the number of connected special function units/ blocks. Some special function units/blocks have a connection number limit.

6107 System configuration error

6112 Changed settings for the built-in CC-Link/LT special function block cannot be written to the attached flash memory cassette.

Verify that the memory cassette is installed correctly.

6113 Changed settings for the built-in CC-Link/LT special function block cannot be written to the attached write- protected flash memory cassette.

Set the protect switch to OFF.

6114 CC-Link/LT settings cannot be written to the built-in CC- Link/LT special function block. Set the configuration again. If the problem persists, something may be malfunctioning inside the PLC. Consult your local Mitsubishi Electric representative. 6115

A built-in CC-Link/LT special function block EEPROM writing time-out error occurred, or the built-in CC-Link/LT special function block configuration could not be completed normally in self CONFIG mode.

PLC/PP communication error, Serial communication error 0 [M8062(D8062)]

0000 ⎯ No error

Parity, overrun or framing error

6202 Communication character error

Confirm the cable connection between the programming panel (PP)/programming device and the PLC. This error may occur when a cable is disconnected and reconnected during PLC monitoring.

6203 Communication data sum check error

6204 Data format error

When the memory cassette is used, check whether it is mounted correctly. If the problem persists or if the memory cassette is not used, something may be malfunctioning inside the PLC. Consult your local Mitsubishi Electric representative.

6230 Memory access error

Show 5 more labels / short text on this page
Error code · Stops operation · Continues · 6205 Command error · operation
Page 897 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 897 · click to enlarge
Page 897

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

38 Error Check Method and Error Code List

38.4 Error Code List and Action 31

FNC277-FNC279 Data Transfer 3

PLC operation at error occurrence Contents of error Action

Serial communication error 1 [M8063(D8063)]

0000 ⎯ No error

Parity, overrun or framing error

6302 Communication character error

FNC280-FNC289 High-Speed Processing 2

6303 Communication data sum check error

  • Ethernet communication, inverter communication, computer link and programming: Ensure the parameters are correctly set according to their applications.
  • N:N network, parallel link, MODBUS communication, etc.: Check programs according to applications.
  • Remote maintenance: Ensure modem power is ON and check the settings of the AT commands.
  • Wiring: Check the communication cables for correct wiring.

6304 Communication data format error

6306 Communication time-out detected

6307 Modem initialization error

6308 N:N network parameter error

6309 N:N Network setting error

FNC290-FNC299 Extension File Register Control

6312 Parallel link character error

6313 Parallel link sum error

6314 Parallel link format error

6320 Inverter communication error

6321 MODBUS communication error

When the memory cassette is used, check whether it is mounted correctly. If the problem persists or if the memory cassette is not used, something may be malfunctioning inside the PLC. Consult your local Mitsubishi Electric representative.

FNC300-FNC305 FX 3U -CF-ADP

6330 Memory access error

6340 Special adapter connection error Check connection of the special adapter.

0000 ⎯ No error

  • Program sum check error
  • STOP the PLC, and correctly set the parameters.
  • Check that the following functions are not used with an unsupported PLC version when a memory cassette is attached: - Permanent PLC lock (supported in FX 3U /FX 3UC PLCs Ver. 2.61 or later) - Read-protect the execution program for block passwords (supported in FX 3U /FX 3UC PLCs Ver. 3.00 or later) - FX 3U -FLROM-1M (supported in FX 3U /FX 3UC PLCs Ver. 3.00 or later)

6402 Memory capacity setting error

6403 Latched device area setting error

6404 Comment area setting error

6405 File register area setting error

6406 Special unit (BFM) initial value setting, positioning instruction setting sum check error

6407 Special unit (BFM) initial value setting, positioning instruction setting error

6409 Other setting error

6411 Built-in CC-Link/LT special function block invalid parameter settings (LT-2 dedicated area).

  • STOP the PLC, and correctly set the parameters.
  • Set parameters correctly, turn OFF the power, and then turn ON the power. 6412 Built-in CC-Link/LT special function block parameter settings sum check error (special function settings area).

6413 Built-in CC-Link/LT special function block parameter settings sum check error (LT-2 dedicated area).

  • STOP the PLC, and correctly set the parameters.
  • Set special parameters correctly, turn OFF the power, and then turn ON the power.

6420 Special parameter sum check error

  • Check the contents of the special parameter error code (D8489), confirm troubleshooting for special adapters/special blocks, and set special parameters correctly.
  • Set special parameters correctly, turn OFF the power, and then turn ON the power.

6421 Special parameters setting error

A

B

Show 12 more labels / short text on this page
Error code · 6305 Command error · Continues · operation · Parameter error [M8064(D8064)] · SFC•STL Programming · Interrupt Function · Stops operation · Special Device · Error Code · Version Up Information · Execution Times
Page 898 of the Mitsubishi Electronics MELSEC FX3S user manual — 38.4 Error Code List and Action
Page 898 · click to enlarge
Page 898

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

38 Error Check Method and Error Code List

38.4 Error Code List and Action

PLC operation at error occurrence Contents of error Action

0000 ⎯ No error

Incorrect combination of instruction, device symbol and device number

6502 No OUT T or OUT C before setting value

  • 6503
  • No setting value after OUT T or OUT C
  • Insufficient number of operands for an applied instruction
  • 6504
  • Same label number is used more than once.
  • Same interrupt input or high-speed counter input is used more than once.

During programming, each instruction is checked. If a syntax error is detected, modify the instruction correctly.

6505 Device number is out of allowable range.

6507 Invalid label number [P]

6508 Invalid interrupt input [I]

6510 MC nesting number error

0000 ⎯ No error

LD, LDI is continuously used 9 times or more.

6611 More ANB/ORB instructions than LD/LDI instructions

6612 Less ANB/ORB instructions than LD/LDI instructions

6613 MPS is continuously used 12 times or more.

6614 No MPS instruction

6615 No MPP instruction

6616 No coil between MPS, MRD and MPP, or incorrect combination

6617 Instruction below is not connected to bus line: STL, RET, MCR, P, I, DI, EI, FOR, NEXT, SRET, IRET, FEND or END

6618 STL, MC or MCR can only be used in main program, but it is used elsewhere (e.g. in interrupt routine or subroutine).

6619 Invalid instruction is used in FOR-NEXT loop: STL, RET, MC, MCR, I (interrupt pointer) or IRET.

This error occurs when a combination of instructions is incorrect in the entire circuit block or when the relationship between a pair of instructions is incorrect. Modify the instructions in the program mode so that their mutual relationship becomes correct.

6620 FOR-NEXT instruction nesting level exceeded

6621 Numbers of FOR and NEXT instructions do not match.

6622 No NEXT instruction

6623 No MC instruction

6624 No MCR instruction

6625 STL instruction is continuously used 9 times or more.

6626 Invalid instruction is programmed within STL-RET loop: MC, MCR, I (interrupt pointer), SRET or IRET.

6627 No STL instruction

6628 Invalid instruction is used in main program: I (interrupt pointer), SRET or IRET

6629 No P or I (interrupt pointer)

6630 No SRET or IRET instruction STL-RET / MC-MCR instructions programmed in the subroutine.

6631 SRET programmed in invalid location

6632 FEND programmed in invalid location

Show 7 more labels / short text on this page
Error code · Syntax error [M8065(D8065)] · Stops operation · 6506 Invalid instruction · 6509 Other error · Circuit error [M8066(D8066)] · Stops operation
Page 899 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 899 · click to enlarge
Page 899

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

38 Error Check Method and Error Code List

38.4 Error Code List and Action 31

FNC277-FNC279 Data Transfer 3

PLC operation at error occurrence Contents of error Action

0000 ⎯ No error

  • No jump destination (pointer) for CJ or CALL instruction
  • Label is undefined or out of P0 to P4095 due to indexing
  • Label P63 is executed in CALL instruction; cannot be used in CALL instruction as P63 is for jumping to END instruction.

FNC280-FNC289 High-Speed Processing 2

This error occurs in the execution of operation. Review the program and check the contents of the operands used in applied instructions. Even if the syntax or circuit design is correct, an operation error may still occur. For example: "T500Z" itself is not an error. But if Z had a value of 100, the timer T600 would be attempted to be accessed. This would cause an operation error since there is no T600 device available.

6702 CALL instruction nesting level is 6 or more

6703 Interrupt nesting level is 3 or more

6704 FOR-NEXT instruction nesting level is 6 or more.

FNC290-FNC299 Extension File Register Control

6705 Operand of applied instruction is inapplicable device.

6706 Device number range or data value for operand of applied instruction exceeds limit.

6707 File register is accessed without parameter setting of file register.

  • This error occurs in the execution of operation.
  • Review the program and check the contents of the operands used in applied instructions.
  • Verify that the specified buffer memories exist in the counterpart equipment.
  • Verify that extension cables are correctly connected.

FNC300-FNC305 FX 3U -CF-ADP

6708 FROM/TO instruction error

This error occurs in the execution of operation. Review the program and check the contents of the operands used in applied instructions. Even if the syntax or circuit design is correct, an operation error may still occur. For example: "T500Z" itself is not an error. But if Z had a value of 100, the timer T600 would be attempted to be accessed. This would cause an operation error since there is no T600 device available.

6709 Other (e.g. improper branching)

6710 Mismatch among parameters This error occurs when the same device is used within the source and destination in a shift instruction, etc.

6730 Incorrect sampling time (TS) (TS ≤ 0)

6732 Incompatible input filter constant (α) (α < 0 or 100 ≤ α)

This error occurs in the parameter setting value or operation data executing PID instruction. Check the contents of the parameters.

6733 Incompatible proportional gain (KP) (KP < 0)

6734 Incompatible integral time (TI) (TI < 0)

6735 Incompatible derivative gain (KD) (KD < 0 or 201 ≤ KD)

6736 Incompatible derivative time (TD) (TD < 0)

The operation is continued in the condition "sampling time (TS) = cyclic time (scan time)".

6740 Sampling time (TS) ≤ Scan time

6742 Variation of measured value exceeds limit. (UPV < −32768 or +32767 < UPV)

6743 Deviation exceeds limit. (EV < −32768 or +32767 < EV)

6744 Integral result exceeds limit. (Outside range from −32768 to +32767)

The operation is continued with each parameter set to the maximum and minimum value.

6745 Derivative value exceeds limit due to derivative gain (KD).

A

6746 Derivative result exceeds limit. (Outside range from −32768 to +32767)

6747 PID operation result exceeds limit. (Outside range from −32768 to +32767)

B

Show 10 more labels / short text on this page
Error code · Operation error [M8067(D8067)] · SFC•STL Programming · Continues · operation · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 900 of the Mitsubishi Electronics MELSEC FX3S user manual — 38.4 Error Code List and Action
Page 900 · click to enlarge
Page 900

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

38 Error Check Method and Error Code List

38.4 Error Code List and Action

PLC operation at error occurrence Contents of error Action

Verify that the target setting contents are correct.

PID output upper limit set value < PID output lower limit set value.

Verify that the target setting contents are correct.

6749 Abnormal PID input variation alarm set value or output variation alarm set value (Set value < 0)

  • <Auto tuning is finished. → PID operation is started.>
  • The deviation at start of auto tuning is 150 or less.
  • The deviation at end of auto tuning is 1/3 or more of the deviation at start of auto tuning. Check the measured value and target value, and then execute auto tuning again.

6750 Improper auto tuning result

The operation direction estimated from the measured value at the start of auto tuning was different from the actual operation direction of the output during auto tuning. Correct the relationship among the target value, output value for auto tuning, and the measured value, and then execute auto tuning again.

6751 Auto tuning operation direction mismatch

Because the set value was fluctuated during auto tuning, auto tuning was not executed correctly. Set the sampling time to a value larger than the output change cycle, or set a larger value for the input filter constant. After changing the setting, execute auto tuning again.

6752 Improper auto tuning operation

6753 Abnormal output set value for auto tuning [ULV (upper limit) ≤ LLV (lower limit)] Verify that the target setting contents are correct. 6754 Abnormal PV threshold (hysteresis) set value for auto tuning (SHPV < 0)

Abnormal auto tuning transfer status (Data of device controlling transfer status is abnormally overwritten.)

Ensure that devices occupied by PID instruction are not overwritten in the program.

The auto tuning time is longer than necessary. Increase the difference (ULV - LLV) between the upper limit and lower limit of the output value for auto tuning, set a smaller value to the input filter constant (α), or set a smaller value to the PV threshold (SHPV) for auto tuning, and then check the result for improvement.

6756 Abnormal result due to excessive auto tuning measurement time (τon > τ, τon < 0, τ < 0)

The variation of the measured value (PV) is small compared with the output value. Multiply the measured value (PV) by "10" so that the variation of the measured value will increase during auto tuning.

6757 Auto tuning result exceeds proportional gain. (KP= outside range from 0 to 32767)

6758 Auto tuning result exceeds integral time. (TI = outside range from 0 to 32767)

The auto tuning time is longer than necessary. Increase the difference (ULV - LLV) between the upper limit and lower limit of the output value for auto tuning, set a smaller value to the input filter constant (α), or set a smaller value to the PV threshold (SHPV) for auto tuning, and then check the result for improvement.

6759 Auto tuning result exceeds derivative time. (TD = outside range from 0 to 32767)

6760 ABS data read from servo sum check error Check servo wiring and parameter setting. Also check the ABS instruction.

Show 4 more labels / short text on this page
Error code · Operation error [M8067(D8067)] · Continues · operation
Page 901 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 901 · click to enlarge
Page 901

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

38 Error Check Method and Error Code List

38.4 Error Code List and Action 31

FNC277-FNC279 Data Transfer 3

PLC operation at error occurrence Contents of error Action

Port specified by inverter communication instruction is already used in another communication.

Check to make sure the port is not specified by another instruction.

1. Check to make sure the input (X), as specified by a DSZR, DVIT or ZRN instruction, is not being used for the following purposes: - Input interrupt (including the delay function) - High-speed counter C235 to C255 - Pulse catch M8170 to M8177 - SPD instruction 2) Check the contents of D8336 for the correct interrupt signal specification for a DVIT instruction.

FNC280-FNC289 High-Speed Processing 2

1. Input (X) specified by a DSZR, DVIT or ZRN instruction is already used in another instruction. 2) The interrupt signal device for a DVIT instruction is outside the allowable setting range.

6764 Pulse output number is already used in a positioning instruction or pulse output instruction (PLSY, PWM, etc.).

FNC290-FNC299 Extension File Register Control

Check to make sure the pulse output destination is not being driven by another positioning instruction.

Verify that the number of times that applied instructions are used in the program does not exceed the specified limit.

6765 Number of applied instruction exceeds limit.

When the memory cassette is used, check whether it is mounted correctly. If the problem persists or if the memory cassette is not used, something may be malfunctioning inside the PLC. Consult your local Mitsubishi Electric representative.

FNC300-FNC305 FX 3U -CF-ADP

6770 Memory access error

6771 Memory cassette is not connected. Check for the correct attachment of the memory cassette.

The write-protect switch of the memory cassette was set to ON when data was transferred to the flash memory. Set the protect switch to OFF.

6772 Memory cassette is protected against writing.

6773 Access error to memory cassette during writing in RUN mode

While data was written in the RUN mode, data was transferred to (read from or written to) the memory cassette.

USB communication error [M8487(D8487)]

Confirm the cable connection between the programming device and the PLC. This error may occur when a cable is disconnected and reconnected during PLC monitoring.

8703 Communication data sum check error

8704 Data format error

When the memory cassette is used, check whether it is mounted correctly. If the problem persists or if the memory cassette is not used, something may be malfunctioning inside the PLC. Consult your local Mitsubishi Electric representative.

8730 Memory access error

Special block error [M8449(D8449)]

General data sum error

021*1 General data message error

022*1 System access error

Verify that extension cables are correctly connected.

025*1 Access sum error in other station via CC-Link

026*1 Message error in other station via CC-Link

When the memory cassette is used, check whether it is mounted correctly. If the problem persists or if the memory cassette is not used, something may be malfunctioning inside the PLC. Consult your local Mitsubishi Electric representative.

030*1 Memory access error

  • This error occurs in the execution of operation.
  • Review the program and check the contents of the operands used in applied instructions.
  • Verify that specified buffer memories exist in the counterpart equipment.
  • Verify that extension cables are correctly connected.

A

080*1 FROM/TO error

  • Check the cable connection between the programming panel (PP) / programming device and the PLC.
  • Verify that extension cables are correctly connected.

090*1 Peripheral equipment access error

B

*1. The unit number 0 to 7 of the special function unit/block error is put in .

Show 17 more labels / short text on this page
Error code · Operation error [M8067(D8067)] · Continues · operation · SFC•STL Programming · Communication character error · Interrupt Function · 8705 Command error · Continues · operation · 020*1 · Special Device · Error Code · Continues · operation · Version Up Information · Execution Times
Page 902 of the Mitsubishi Electronics MELSEC FX3S user manual — Value of (decimal) Special adapter/special block where an error has occurred
Page 902 · click to enlarge
Page 902

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

38 Error Check Method and Error Code List

38.4 Error Code List and Action

PLC operation at error occurrence Contents of error Action

Special parameter error [M8489(D8489)]

Special parameter setting time-out error Turn OFF the power, and check the power supply and connection of special adapters/special blocks.

  • Special parameters are set improperly.
  • Confirm troubleshooting for special adapters/special blocks, and set special parameters correctly.
  • Set special parameters correctly, turn OFF the power, and then turn ON the power.

02*1 Special parameter setting error

Special parameters are set, but special adapters/special blocks are not connected. Check whether special adapters/special blocks are connected.

03*1 Special parameter transfer target unconnected error

04*1 Special parameter unsupported function Check that special parameters with unsupported settings are not set for connected special adapters/special blocks.

*1. " " indicates the following values for each special adapter/special block where an error has occurred. If an error has occurred in 2 or more special adapters/special blocks, " " indicates the lowest unit number among the special adapters/special blocks in which an error has occurred.

Value of (decimal) Special adapter/special block where an error has occurred

00 Unit number 0 (Special block)

10 Unit number 1 (Special block)

20 Unit number 2 (Special block)

30 Unit number 3 (Special block)

40 Unit number 4 (Special block)

50 Unit number 5 (Special block)

60 Unit number 6 (Special block)

70 Unit number 7 (Special block)

81 Communication channel 1 (Special adapter)

82 Communication channel 2 (Special adapter)

PLC operation at error occurrence Contents of error Action

Special block error condition [D8166]

Unit 0 access error

b1 Unit 1 access error

  • This error occurs when an operation is executed or when the END instruction is executed.
  • Review the program and check the contents of the operands used in applied instructions.
  • Verify that the specified buffer memories exist in the counterpart equipment.
  • Verify that extension cables are correctly connected.

b2 Unit 2 access error

b3 Unit 3 access error

b4 Unit 4 access error

b5 Unit 5 access error

b6 Unit 6 access error

b7 Unit 7 access error

b15 ⎯ Not available

Show 10 more labels / short text on this page
Error code · 01*1 · Continues · operation · Error · bit · b0 · Continues · operation · b8 to
Page 903 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 903 · click to enlarge
Page 903

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

A Programming Tool Applicability and Version Upgrade History

A-1 Programming Tool Applicability

FNC277-FNC279 Data Transfer 3

Appendix A: Programming Tool Applicability and Version

Upgrade History

FNC280-FNC289 High-Speed Processing 2

Appendix A-1 Programming Tool Applicability

Appendix A-1-1 Programming tool applicability

FNC290-FNC299 Extension File Register Control

1. Applicable versions of programming tool

1. GX Works2
  • GX Works2 English version (SW † DNC-GXW2-E) is applicable to FX 3S /FX 3G /FX 3GC /FX 3U /FX 3UC PLCs from the following versions.

Model name PLC version Applicable GX Works2

FNC300-FNC305 FX 3U -CF-ADP

FX3S PLC Ver. 1.00 Ver. 1.492N or later -

Before Ver. 1.40 Ver. 1.08J or later

FX 3G PLC

- Before Ver. 2.00 Ver. 1.62Q or later

Ver. 2.00 Ver. 1.87R or later

Before Ver. 2.00 Ver. 1.77F or later

FX 3GC PLC

- Ver. 2.00 Ver. 1.87R or later

Before Ver. 2.70 Ver. 1.08J or later

- Before Ver. 3.00 Ver. 1.48A or later

FX 3U PLC

Before Ver. 3.10 Ver. 1.62Q or later

Ver. 3.10 Ver. 1.73B or later

Before Ver. 2.70 Ver. 1.08J or later

- Before Ver. 3.00 Ver. 1.48A or later

FX 3UC PLC

Before Ver. 3.10 Ver. 1.62Q or later

Ver. 3.10 Ver. 1.73B or later

  • GX Works2 Japanese version (SW † DNC-GXW2-J) is applicable to FX 3S /FX 3G /FX 3GC /FX 3U /FX 3UC PLCs from the following versions.

Model name PLC version Applicable GX Works2

FX3S PLC Ver. 1.00 Ver. 1.492N or later -

Before Ver. 1.40 Ver. 1.07H or later

FX 3G PLC

- Before Ver. 2.00 Ver. 1.56J or later

Ver. 2.00 Ver. 1.86Q or later

Before Ver. 2.00 Ver. 1.77F or later - Ver. 2.00 Ver. 1.86Q or later

FX 3GC PLC

Before Ver. 2.70 Ver. 1.07H or later

- Before Ver. 3.00 Ver. 1.45X or later

FX 3U PLC

Before Ver. 3.10 Ver. 1.56J or later

Ver. 3.10 Ver. 1.73B or later

A

Before Ver. 2.70 Ver. 1.07H or later

- Before Ver. 3.00 Ver. 1.45X or later

FX 3UC PLC

Before Ver. 3.10 Ver. 1.56J or later

Ver. 3.10 Ver. 1.73B or later

B

Show 8 more labels / short text on this page
version Remarks · SFC•STL Programming · Interrupt Function · version Remarks · Special Device · Error Code · Version Up Information · Execution Times
Page 904 of the Mitsubishi Electronics MELSEC FX3S user manual — FX 3UC PLC
Page 904 · click to enlarge
Page 904

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

A Programming Tool Applicability and Version Upgrade History

A-1 Programming Tool Applicability

2. GX Developer
  • GX Developer English version (SW † D5C-GPPW-E) is applicable to FX 3G /FX 3U /FX 3UC PLCs from the following versions.

Model name PLC version Applicable GX Developer

Before Ver. 1.10 Ver. 8.72A or later - Ver. 1.10 Ver. 8.78G or later

FX 3G PLC

Before Ver. 2.30 Ver. 8.24A or later - Before Ver. 2.41 Ver. 8.29F or later

FX 3U PLC

Before Ver. 2.61 Ver. 8.29F or later Ver. 8.89T and later versions support the baud rate "38400 bps" in the communication setting for RS and RS2 instructions, inverter communication and computer link. Ver. 2.61 Ver. 8.82L or later

Before Ver. 2.20 Ver. 8.18U or later

- Before Ver. 2.30 Ver. 8.24A or later

Before Ver. 2.41 Ver. 8.29F or later

FX 3UC PLC

Before Ver. 2.53 Ver. 8.29F or later Ver. 8.89T and later versions support the baud rate "38400 bps" in the communication setting for RS and RS2 instructions, inverter communication and computer link.

Before Ver. 2.61 Ver. 8.68W or later

Ver. 2.61 Ver. 8.82L or later

  • GX Developer Japanese version (SW † D5C-GPPW-J) is applicable to FX 3G /FX 3U /FX 3UC PLCs from the following versions.

Model name PLC version Applicable GX Developer

Before Ver. 1.10 Ver. 8.72A or later - Ver. 1.10 Ver. 8.76E or later

FX 3G PLC

Before Ver. 2.30 Ver. 8.23Z or later - Before Ver. 2.41 Ver. 8.29F or later

FX 3U PLC

Before Ver. 2.61 Ver. 8.29F or later Ver. 8.88S and later versions support the baud rate "38400 bps" in the communication setting for RS and RS2 instructions, inverter communication and computer link. Ver. 2.61 Ver. 8.82L or later

Before Ver. 1.30 Ver. 8.13P or later

- Before Ver. 2.20 Ver. 8.18U or later

Before Ver. 2.30 Ver. 8.23Z or later

FX 3UC PLC

Before Ver. 2.41 Ver. 8.29F or later

Before Ver. 2.53 Ver. 8.29F or later Ver. 8.88S and later versions support the baud rate "38400 bps" in the communication setting for RS and RS2 instructions, inverter communication and computer link.

Before Ver. 2.61 Ver. 8.68W or later

Ver. 2.61 Ver. 8.82L or later

3. FX-30P FX-30P is applicable to FX 3S /FX 3G /FX 3GC /FX 3U /FX 3UC PLCs starting with the following version:

Model name PLC version Applicable FX-30P version Remarks

FX3S PLC Ver. 1.00 Ver. 1.50 or later -

  • FX-30P (from first version) supports FX 3G PLC (Ver. 1.10 or later).
  • FX-30P (Ver. 1.50 or later) supports IVMC instruction.

FX3G PLC Ver. 1.00 Ver. 1.00 or later

FX3GC PLC Ver. 1.40 Ver. 1.30 or later FX-30P (Ver. 1.50 or later) supports IVMC instruction.

Before Ver. 2.41 Ver. 1.00 or later - Ver. 2.70 Ver. 1.20 or later

FX 3U PLC

Before Ver. 2.41 Ver. 1.00 or later - Ver. 2.70 Ver. 1.20 or later

FX 3UC PLC

version Remarks · version Remarks

Page 905 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 905 · click to enlarge
Page 905

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

A Programming Tool Applicability and Version Upgrade History

A-1 Programming Tool Applicability

2. In the case of programming tool (version) Even using a programming tool not applicable to the FX 3S /FX 3G /FX 3GC /FX 3U /FX 3UC PLCs, programming is enabled when an alternative model is set.

FNC277-FNC279 Data Transfer 3

Using an alternative model

Model to be programmed Model to be set Priority High → Low

FX3S PLC FX3S → FX3G → FX1N*2 → FX2N*2

FNC280-FNC289 High-Speed Processing 2

FX3G PLC FX3G → FX1N*4 → FX2N*2 → FX2

FX3GC PLC FX3GC → FX3G → FX1N*2 → FX2N*2

FX3U PLC FX3U(C)*1 → FX3UC → FX2N → FX2

FX3UC PLC FX3U(C)*1 → FX3UC → FX2N → FX2

*1. For Ver. 8.18U to 8.24A of GX Developer, the PLC type is FX3UC. *2. "FX2N" is selected when the FX-10P(-E) is used.

FNC290-FNC299 Extension File Register Control

Contents of restrictions

  • Programming is enabled only in the function ranges such as instruction/device range and program size available in both the PLC model to be programmed and the alternative PLC model.
  • In the FX 3S PLC, memory capacity setting of the PLC parameter must be set to 4,000 steps or less.

FNC300-FNC305 FX 3U -CF-ADP

  • Use a programming tool which can select FX 3S , FX 3G , FX 3GC , FX 3U or FX 3UC when changing the parameters such as memory capacity and file register capacity.
  • Use a programming tool which can select FX 3G when executing communication using the standard (USB) built-in port of the FX 3S /FX 3G /FX 3GC PLCs.

3. Program transfer speed and programming tools

In FX 3S /FX 3G /FX 3GC PLCs

1. Built-in USB communication The FX 3S /FX 3G /FX 3GC PLCs has a built-in USB communication port, and performs program writing, program reading and monitoring at high speed (12 Mbps) with a personal computer that supports USB.

a) Supported programming tools*3

GX Works2 (Ver. 1.08J or later), GX Developer (Ver. 8.72A or later) b) In programming tools not supporting USB

Communication is performed via RS-422 or RS-232C.

2. RS-422/RS-232C communication The FX 3S /FX 3G /FX 3GC PLCs can write and read programs and perform monitoring at 115.2 kbps through RS-422/ RS-232C communication.

a) 115.2 kbps supported programming tools*3

GX Works2 (Ver. 1.08J or later), GX Developer (Ver. 8.72A or later), FX-30P (Ver. 1.00 or later) b) 115.2 kbps supported interfaces

- Standard built-in port(RS-422) or expansion board FX3G-422-BD for RS-422 When the RS-232C/RS-422 converter FX-232AWC-H is connected. - Expansion board FX3G-232-BD for RS-232C - Special adapter FX3U-232ADP(-MB) for RS-232C c) In programming tools not supporting 115.2 kbps

Communication is executed at 9,600 or 19,200 bps.

*3. Select "FX3G" for a programming tool not supporting FX3S/FX3GC PLCs.

A

B

Show 6 more labels / short text on this page
SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 906 of the Mitsubishi Electronics MELSEC FX3S user manual — FX-PCS/WIN-E *2
Page 906 · click to enlarge
Page 906

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

A Programming Tool Applicability and Version Upgrade History

A-1 Programming Tool Applicability

In FX 3U /FX 3UC PLCs

1. RS-422/RS-232C/USB communication The FX 3U /FX 3UC PLCs can write and read programs and perform monitoring at 115.2 kbps through RS-422/RS232C/USB communication. a) 115.2 kbps supported programming tools

GX Works2 (Ver. 1.08J or later), GX Developer (Ver. 8.18U or later), FX-30P (Ver. 1.00 or later) b) 115.2 kbps supported interfaces

- Standard built-in port or expansion board FX3U-422-BD for RS-422 When the RS-232C/RS-422 converter FX-232AWC-H or USB/RS-422 converter FX-USB-AW is connected. - Expansion board FX3U-232-BD for RS-232C - Special adapter FX3U-232ADP(-MB) for RS-232C - Expansion board FX3U-USB-BD for USB c) In programming tools not supporting 115.2 kbps

Communication is executed at 9,600 or 19,200 bps.

Appendix A-1-2 Cautions on writing during RUN

"In the FX3S, FX3G, FX3GC, FX3U and FX3UC PLCs, writing is enabled during RUN (program changes during RUN mode) using the following programming tools".

→ For the operating procedure of and cautions on writing during RUN,

refer to the respective programming tool manual. Programming tools which support writing during RUN

  • English version

Programming tool PLC Version Remarks

FX3S Ver. 1.492N or later Writing in the instruction and device ranges during RUN is supported in FX3S PLC earlier than Ver. 1.00.

Ver. 1.08J or later Writing in the instruction and device ranges during RUN is supported in FX3G PLC earlier than Ver. 1.40.

FX 3G /FX 3GC

Ver. 1.77F or later Writing in the instruction and device ranges during RUN is supported in FX3G and FX3GC PLCs earlier than Ver. 1.40.

(SW † DNC-GXW2-E)

Ver. 1.08J or later Writing in the instruction and device ranges during RUN is supported in FX3U and FX3UC PLCs earlier than Ver. 2.70.

FX 3U /FX 3UC

Ver. 1.48A or later Writing in the instruction and device ranges during RUN is supported in FX3U and FX3UC PLCs Ver. 2.70.

Ver. 2.00A or later Writing in the instruction and device ranges during RUN is supported in FX2N PLC Ver. 1.00.

Ver. 5.00A or later Writing in the instruction and device ranges during RUN is supported in FX1N PLC Ver. 1.00.

FX 3G

Ver. 8.72A or later Writing in the instruction and device ranges during RUN is supported in FX3G PLC earlier than Ver. 1.10.

Ver. 8.78G or later Writing in the instruction and device ranges during RUN is supported in FX3G PLC Ver. 1.10.

Ver. 7.00A or later Writing in the instruction and device ranges during RUN is supported in FX2N PLC Ver. 3.00.

(SW † D5C-GPPW-E)

Ver. 8.18U or later Writing in the instruction and device ranges during RUN is supported in FX3UC PLC earlier than Ver. 2.20.

Ver. 8.24A or later Writing in the instruction and device ranges during RUN is supported in FX3U and FX3UC PLCs earlier than Ver. 2.30.

FX 3U /FX 3UC

Ver. 8.29F or later Writing in the instruction and device ranges during RUN is supported in FX3U and FX3UC PLCs earlier than Ver. 2.61.

Ver. 8.82L or later Writing in the instruction and device ranges during RUN is supported in FX3U and FX3UC PLCs Ver. 2.61.

FX3G Ver. 3.00 or later Writing in the instruction and device ranges during RUN is supported in FX1N PLC Ver. 1.00.

Ver. 1.00 or later Writing in the instruction and device ranges during RUN is supported in FX2N PLC Ver. 1.00.

FX-PCS/WIN-E *2

FX 3U /FX 3UC

Ver. 3.10 or later Writing in the instruction and device ranges during RUN is supported in FX2N PLC Ver. 3.00.

*1. Write during RUN is not possible with a SFC program.

*2. Write during RUN is not possible with a list program or a SFC program.

GX Works2*1 · GX Developer*2

Page 907 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 907 · click to enlarge
Page 907

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

A Programming Tool Applicability and Version Upgrade History

A-1 Programming Tool Applicability

  • Japanese version

FNC277-FNC279 Data Transfer 3

Programming tool PLC Version Remarks

FX3S Ver. 1.492N or later Writing in the instruction and device ranges during RUN is supported in FX3S PLC earlier than Ver. 1.00.

Ver. 1.07H or later Writing in the instruction and device ranges during RUN is supported in FX3G PLC earlier than Ver. 1.40.

FX 3G /FX 3GC

Ver. 1.77F or later Writing in the instruction and device ranges during RUN is supported in FX3G and FX3GC PLCs earlier than Ver. 1.40.

FNC280-FNC289 High-Speed Processing 2

(SW † DNC-GXW2-J)

Ver. 1.07H or later Writing in the instruction and device ranges during RUN is supported in FX3U and FX3UC PLCs earlier than Ver. 2.70.

FX 3U /FX 3UC

Ver. 1.45X or later Writing in the instruction and device ranges during RUN is supported in FX3U and FX3UC PLCs Ver. 2.70.

Ver. 2.00A or later Writing in the instruction and device ranges during RUN is supported in FX2N PLC Ver. 1.00.

Ver. 5.00A or later Writing in the instruction and device ranges during RUN is supported in FX1N PLC Ver. 1.00.

FNC290-FNC299 Extension File Register Control

FX 3G

Ver. 8.72A or later Writing in the instruction and device ranges during RUN is supported in FX3G PLC earlier than Ver. 1.10.

Ver. 8.76E or later Writing in the instruction and device ranges during RUN is supported in FX3G PLC Ver. 1.10.

Ver. 7.00A or later Writing in the instruction and device ranges during RUN is supported in FX2N PLC Ver. 3.00.

FNC300-FNC305 FX 3U -CF-ADP

(SW † D5C-GPPW-J)

Ver. 8.13P or later Writing in the instruction and device ranges during RUN is supported in FX3UC PLC earlier than Ver. 1.30.

Ver. 8.18U or later Writing in the instruction and device ranges during RUN is supported in FX3UC PLC earlier than Ver. 2.20.

FX 3U /FX 3UC

Ver. 8.23Z or later Writing in the instruction and device ranges during RUN is supported in FX3U and FX3UC PLCs earlier than Ver. 2.30.

Ver. 8.29F or later Writing in the instruction and device ranges during RUN is supported in FX3U and FX3UC PLCs earlier than Ver. 2.61.

Ver. 8.82L or later Writing in the instruction and device ranges during RUN is supported in FX3U and FX3UC PLCs Ver. 2.61.

FX3G Ver. 4.00 or later Writing in the instruction and device ranges during RUN is supported in FX1N PLC Ver. 1.00.

Ver. 1.00 or later Writing in the instruction and device ranges during RUN is supported in FX2 PLC Ver. 3.30.

FX-PCS/WIN *2

Ver. 2.00 or later Writing in the instruction and device ranges during RUN is supported in FX2N PLC Ver. 1.00.

FX 3U /FX 3UC

Ver. 4.20 or later Writing in the instruction and device ranges during RUN is supported in FX2N PLC Ver. 3.00.

*1. Write during RUN is not possible with a SFC program. *2. Write during RUN is not possible with a list program or a SFC program.

A

B

Show 8 more labels / short text on this page
GX Works2*1 · GX Developer*2 · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 908 of the Mitsubishi Electronics MELSEC FX3S user manual — IRET
Page 908 · click to enlarge
Page 908

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

A Programming Tool Applicability and Version Upgrade History

A-1 Programming Tool Applicability

Cautions on writing during RUN

Program memory which can be written in RUN mode Built-in RAM and optional memory cassette (whose write protect switch is set to OFF)

  • GX Works2 Ver. 1.08J or later
  • GX Developer Ver. 8.72A or later
  • For FX 3S /FX 3G /FX 3GC PLCs 256 steps or less after edit (addition/deletion) (including NOP immediately after circuit blocks except final circuit

Number of program steps which can be written for circuit change in RUN mode

  • For FX 3U /FX 3UC PLCs Ver. 2.20 or later 256 steps or less after edit (addition/deletion) (including NOP immediately after circuit blocks except final circuit)
  • For FX 3UC PLC earlier than Ver. 2.20 127 steps or less after edit (addition/deletion) (including NOP immediately after circuit blocks except final circuit)
  • GX Works2 Ver. 1.08J or later
  • GX Developer Ver. 8.24A or later
  • GX Developer Ver. 8.22Y and earlier
  • FX-PCS/WIN(-E)

127 steps or less after edit (addition/deletion) (including NOP immediately after circuit blocks except final circuit)

Circuit blocks*1 in which labels P and I are added, deleted, or changed in edited circuits

Circuit blocks which cannot be written during RUN

Circuit blocks in which 1-ms timers (T246 to T249 and T256 to T511) are added in edited circuits

  • Circuit blocks in which the following instructions are included in edited circuits
  • Instruction to output high-speed counters C235 to C255 (OUT instruction)
  • SORT2 (FNC149), TBL (FNC152), RBFM (FNC278) and/or WBFM (FNC279) instructions

*1. Circuit blocks cannot be edited to insert a label as shown below when written during RUN.

EI

Added, deleted, or changed

interrupt Label I is inserted by editing the circuit block

Added, deleted, or changed

IRET

END

Item Caution · Step · FEND Pointer for

Page 909 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 909 · click to enlarge
Page 909

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

A Programming Tool Applicability and Version Upgrade History

A-1 Programming Tool Applicability

FNC277-FNC279 Data Transfer 3

During RUN, avoid writing to a circuit block including the following instructions under execution. If writing is executed during RUN to such a circuit block, the PLC decelerates and stops pulse output. • DSZR (FNC150), DVIT (FNC151), ZRN (FNC156), PLSV (FNC157) instructions [with acceleration/ deceleration operation], DRVI (FNC158) and/or DRVA (FNC159) instructions

During RUN, avoid writing to a circuit block including the following instruction under execution. If writing is executed during RUN to such a circuit block, the PLC immediately stops pulse output. • PLSV (FNC157) instruction [without acceleration/deceleration operation]

FNC280-FNC289 High-Speed Processing 2

During RUN, avoid writing to a circuit block including the following instruction under execution. • PLSY (FNC 50), PWM (FNC 58), PLSR (FNC 59) instructions

During RUN, avoid writing to a circuit block including the following instructions under execution of communication. If writing is executed during RUN to such a circuit block, the PLC may stop communication after that. If the PLC stops communication, set the PLC to the STOP mode once, and then set it to the RUN mode again. • IVCK (FNC270), IVDR (FNC271), IVRD (FNC272), IVWR (FNC273), IVBWR (FNC274), IVMC (FNC275) and ADPRW (FNC276) instructions

FNC290-FNC299 Extension File Register Control

During RUN, avoid writing to a circuit block including the following instruction under execution. If such writing is executed during RUN, instructions being executed are canceled. • FLCRT (FNC300), FLDEL (FNC301), FLWR (FNC302), FLRD (FNC303), FLCMD (FNC304) and FLSTRD (FNC305) instructions

  • When writing to a circuit block during RUN, which includes the following instructions, the following results.
  • instruction for falling edge pulse When writing is completed during RUN for a circuit including an instruction for falling edge pulse (LDF, ANDF, or ORF instruction), the instruction for falling edge pulse is not executed regardless of the ON/OFF status of the target device of the instruction for falling edge pulse. When writing is completed during RUN for a circuit including an instruction for falling edge pulse (PLF instruction), the instruction for falling edge pulse is not executed regardless of the ON/OFF status of the operation condition device. It is necessary to set to ON the target device or operation condition device once and then set it to OFF to execute the instruction for falling edge pulse.
  • Instruction for rising edge pulse When writing is completed during RUN for a circuit including an instruction for rising edge pulse, the instruction for rising edge pulse is executed if a target device of the instruction for rising edge pulse or the operation condition device is ON. Target instructions for rising edge pulse: LDP, ANDP, ORP, and pulse operation type applied instructions (such as MOVP)

FNC300-FNC305 FX 3U -CF-ADP

Circuit blooks which require attention on operation after writing during RUN

While writing is executed

Instruction for rising edge

Instruction for falling edge

OFF Not executed Not executed

ON Executed*1 Not executed

*2. The PLS instruction is not executed.

  • When writing to a circuit block during RUN, which includes the following instructions, the following results.
  • Pulse instruction during rising edge of operation results (MEP instruction) After writing to the circuit with MEP instructions during RUN, the MEP instruction result turns ON (conductive) while the operation results leading up to the MEP instruction are ON.
  • Pulse instruction during falling edge of operation results (MEF instruction) After writing to the circuit with MEF instructions during RUN, the MEF instruction result turns OFF (nonconductive), regardless of the operation results up to the MEF instruction. The operation results of the MEF instruction turns ON (conductive) when the operation results leading up to the MEF instruction are turned OFF.

Operation results leading up to

MEP/MEF instruction MEP instruction MEF instruction

OFF OFF (non-conductive) OFF (non-conductive)

ON ON (conductive) OFF (non-conductive)

  • When GX Works2 Ver. 1.08J or later or GX Developer Ver. 8.72A or later is used in FX 3S /FX 3G /FX 3GC PLCs to write data during RUN, the following will occur. If the number of program steps is reduced by deleting contact or coil application instructions, etc., the program becomes shorter by the number of reduced steps.
  • When GX Works2 Ver. 1.08J or later or GX Developer Ver. 8.18U or later is used in FX 3U /FX 3UC PLCs to write data during RUN, the following will occur. If the number of program steps is reduced by deleting contact or coil application instructions, etc., the program becomes shorter by the number of reduced steps.
  • FX 3U /FX 3UC PLCs Ver. 3.00 or later and GX Works2 Ver. 1.62Q or later. Writing during RUN is enabled only when the protection status (valid or invalid) by the setting "Read-protect the execution program" for the block password is same as the protection status of the PLC designated as the target of writing during RUN.
  • Errors cannot be detected in write during RUN even in a circuit which causes errors. Errors are detected after the PLC is stopped once, and then run again.

A

B

Show 11 more labels / short text on this page
Item Caution · SFC•STL Programming · during RUN · pulse · pulse · Interrupt Function · Special Device · Error Code · Version Up Information · Other · Execution Times
Page 910 of the Mitsubishi Electronics MELSEC FX3S user manual — 2. Setting in GX Developer
Page 910 · click to enlarge
Page 910

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

A Programming Tool Applicability and Version Upgrade History

A-1 Programming Tool Applicability

Appendix A-1-3 Precautions on Use of (Built-in USB) Programming Port

Make sure to set the contents described in this section when using the (built-in USB) programming port of the FX3G/ FX3GC PLC to execute ladder monitor, device monitor, program read/write, etc by GX Developer. For GX Developer prior to Ver. 8.72A, communication using the (built-in USB) programming port is not available.

1. Installation of USB driver It is necessary to install the USB driver to execute USB communication using the (built-in USB) programming port. For the USB driver installation method and procedure, refer to the following manual.

→ GX Developer Operating Manual (Startup)

2. Setting in GX Developer

1. Select [Online] → [Transfer setup...] to open Transfer setup dialog box.
2. Double-click [Serial] in [PC side I/F] to open PC side I/F Serial setting dialog box.
3. Select "USB (Built-in port)".
Mitsubishi Electronics MELSEC FX3S — 2. Setting in GX Developer diagram (page 910)
Fig. 837 · 2. Setting in GX Developer

A display screen is the example of Ver. 8.72A.

4. Click [OK] button to finish the setting.
Page 911 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 911 · click to enlarge
Page 911

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

A Programming Tool Applicability and Version Upgrade History

A-1 Programming Tool Applicability

Appendix A-1-4 Cautions on using transparent function by way of USB in GOT1000 Series

FNC277-FNC279 Data Transfer 3

Make sure to provide the following setting when executing ladder monitor, device monitor, and reading/writing programs in an FX3G/FX3GC/FX3U/FX3UC PLC using GX Developer or later and the transparent function by way of the USB in the GOT1000 Series. If the following setting is not provided, a communication error occurs.

GX Developer Ver. 8.21X or former GX Developer Ver. 8.22Y or later

FNC280-FNC289 High-Speed Processing 2

When using transparent function by way of USB in GOT1000 Series Not supported (not available) Setting shown below is required.

When using transparent function by way of RS-232 in GOT1000 Series Set "COM port" and "Transmission speed" on "PC side I/F Serial setting" dialog box.

Select "RS-232C" in setting shown below, and set "COM port" and "Transmission speed". When directly connecting GX Developer to PLC When directly connecting GX Developer to PLC (standard built-in RS-422 port)

FNC290-FNC299 Extension File Register Control

Setting in GX Developer

1. Select [Online] → [Transfer setup...] to open Transfer setup dialog box.
2. Double-click [Serial] in [PC side I/F] to open PC side I/F Serial setting dialog box.

FNC300-FNC305 FX 3U -CF-ADP

3. Select "USB (GOT Transparent mode)".

FX3G/FX3GC PLCs

Mitsubishi Electronics MELSEC FX3S — FNC300-FNC305 FX 3U -CF-ADP diagram (page 911)
Fig. 838

Double-click it.

Mitsubishi Electronics MELSEC FX3S — FNC300-FNC305 FX 3U -CF-ADP diagram (page 911)
Fig. 839

Select "USB(GOT transparent mode)"

This example shows a window displayed when GX Developer Ver. 8.72A is used.

FX3U/FX3UC PLCs

Mitsubishi Electronics MELSEC FX3S — FNC300-FNC305 FX 3U -CF-ADP diagram (page 911)
Fig. 840

Double-click it.

Mitsubishi Electronics MELSEC FX3S — FNC300-FNC305 FX 3U -CF-ADP diagram (page 911)
Fig. 841

A

Select "USB(GOT transparent mode)"

This example shows a window displayed when GX Developer Ver. 8.72A is used.

B

4. Click [OK] button to finish the setting.
Show 6 more labels / short text on this page
SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 912 of the Mitsubishi Electronics MELSEC FX3S user manual — Setting in GX Developer
Page 912 · click to enlarge
Page 912

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

A Programming Tool Applicability and Version Upgrade History

A-1 Programming Tool Applicability

Appendix A-1-5 Cautions on using transparent (2-port) function of GOT-F900 Series

Make sure to provide the following setting when executing ladder monitor, device monitor, etc. in an FX3G/FX3GC/ FX3U/FX3UC PLC using GX Developer and the transparent (2-port) function of the GOT-F900 Series. If the following setting is not provided, write to PLC, read from PLC, verify with PLC, etc. operate normally, but monitoring (ladder monitor, entry data monitor, etc.) cannot be normally executed.

Mitsubishi Electronics MELSEC FX3S — Appendix A-1-5 Cautions on using transparent (2-port) function of GOT-F900 Series diagram (page 912)
Fig. 842 · Appendix A-1-5 Cautions on using transparent (2-port…

GX Developer Ver. 8.18U or later GX Developer Ver. 8.22Y or later

When directly connecting GX Developer to PLC (standard built-in RS-422 port)

Select "RS-232C" on "PC side I/F Serial setting" dialog box, and set "COM port" and "Transmission speed".

Set "COM port" and "Transmission speed" on "PC side I/F Serial setting" dialog box.

Select "RS-232C" on "PC side I/F Serial setting" dialog box, and execute settings shown below.

Setting in GX Developer

1. Select [Online] → [Transfer setup...] to open Transfer Setup dialog box.
2. Double-click [PLC module] in [PLC side I/F] to open PLC side I/F Detailed setting of PLC module dialog box.
3. Put a check mark in the check box [via GOT-F900 transparent mode] as shown below.
Mitsubishi Electronics MELSEC FX3S — Setting in GX Developer diagram (page 912)
Fig. 843 · Setting in GX Developer

Put a check mark in the check box "via GOT-F900 transparent mode".

4. Click [OK] button to finish the setting.
Page 913 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 913 · click to enlarge
Page 913

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

A Programming Tool Applicability and Version Upgrade History

A-2 Peripheral product applicability (except programming tools)

Appendix A-2 Peripheral product applicability (except programming tools)

FNC277-FNC279 Data Transfer 3

Appendix A-2-1 Peripheral product applicability

FX 3S PLC

Product Name Applicability Remarks

FNC280-FNC289 High-Speed Processing 2

Standard monitor OS, communication driver and option OS which support the FX3S PLC are required. For details, refer to the GOT manual.

This series is subject to the following restrictions when connected using unsupported standard monitor OS, communication driver or option OS.

  • Contents of restrictions
  • When connected using standard monitor OS, communication driver and option OS which support the FX 3G PLC - Programming is enabled only in the function range such as instructions, device ranges and program sizes available in both the FX 3S PLC and the FX 3G PLC.
  • When connected using standard monitor OS, communication driver and option OS which do not support the FX 3G PLC - Programming is enabled only in the function range such as instructions, device ranges and program sizes available in both the FX 3S PLC and the FX 1N PLC. - The list editor function for MELSEC-FX is not available. When using the list editor function for MELSEC-FX, upgrade the standard monitor OS, communication driver and option OS to the version compatible with the FX 3S PLC.

FNC290-FNC299 Extension File Register Control

FNC300-FNC305 FX 3U -CF-ADP

Check the applicability of other items in the GOT manual.

The following restriction applies when connected.

Contents of restrictions Programming is enabled only in the function range such as instructions, device ranges and program sizes available in both the FX3S PLC and the FX1N PLC. For applicable models, refer to the GOT manual.

GOT-F900 Series Not applicable

For connection using the 2-port interface function*1, refer to Appendix A-1-4.

The following restriction applies when connected.

Contents of restrictions Programming is enabled only in the function range such as instructions, device ranges and program sizes available in both the FX3S PLC and the FX1N PLC. For supported models and device ranges, refer to the FX-10DM USER’ MANUAL (Manual No. JY992D86401).

A

B

Show 8 more labels / short text on this page
GOT1000 Series Applicable · SFC•STL Programming · Interrupt Function · FX-10DM(-SET0) Not applicable · Special Device · Error Code · Version Up Information · Execution Times
Page 914 of the Mitsubishi Electronics MELSEC FX3S user manual — FX 3U /FX 3UC PLC
Page 914 · click to enlarge
Page 914

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

A Programming Tool Applicability and Version Upgrade History

A-2 Peripheral product applicability (except programming tools)

FX3G/FX3GC PLCs

Product Name Applicability Remarks

Standard monitor OS, communication driver and option OS which support the FX3G/FX3GC PLCs are required. For details, refer to the GOT manual.

This series is subject to the following restrictions when connected using unsupported standard monitor OS, communication driver or option OS.

  • Contents of restrictions
  • Programming is enabled only in the function ranges such as instructions, device ranges and program sizes available in the FX 1N and FX 1NC PLCs.
  • The list editor function for MELSEC-FX is not available. When using the list editor function for MELSEC-FX, upgrade the standard monitor OS, communication driver and option OS to the version compatible with the FX 3G PLC.

Check the applicability of other items in the GOT manual.

F940WGOT Not applicable The following restriction applies when connected.

F940GOT, F940 Handy GOT Not applicable

Contents of restrictions Programming is enabled only in the function ranges such as instructions, device ranges and program sizes available in the FX1N and FX1NC PLCs. For applicable models, refer to the GOT manual.

F930GOT (-K) Not applicable

F920GOT (-K) Not applicable

For connection using the 2-port interface function*1, refer to Appendix A-1-4.

The following restriction applies when connected.

Contents of restrictions Programming is enabled only in the function ranges such as instructions, device ranges and program sizes available in the FX1N and FX1NC PLCs. For supported models and device ranges, refer to the FX-10DM USER’ MANUAL (Manual No. JY992D86401).

FX-10DM (-SET0) Not applicable

The following restriction applies when connected.

Contents of restrictions It is limited to the device range and function range supported by the highest class model (FX1N or FX1NC) applicable in the product version. For supported models and device ranges, refer to the FX-10DU Operation Manual (Manual No. JY992D34701).

FX 3U /FX 3UC PLC

Product Name Applicability Remarks

GOT1000 Series Applicable (From first product)

The GOT1000 Series is applicable to the device ranges in the FX3U/FX3UC PLCs. Check the applicability of other items in the GOT manual.

F940WGOT Not applicable The following restriction applies when connected.

F940GOT, F940 Handy GOT Not applicable

Contents of restrictions Programming is enabled only in the function ranges such as instructions, device ranges and program sizes available in the FX2N and FX2NC PLCs. For applicable models, refer to the GOT manual.

F930GOT (-K) Not applicable

F920GOT (-K) Not applicable

For connection using the 2-port interface function*1, refer to Appendix A-1-4.

The following restriction applies when connected.

Contents of restrictions Programming is enabled only in the function ranges such as instructions, device ranges and program sizes available in the FX2N and FX2NC PLCs. For supported models and device ranges, refer to the FX-10DM USER’S MANUAL (Manual No. JY992D86401).

FX-10DM (-SET0) Not applicable

The following restriction applies when connected.

Contents of restrictions It is limited to the device range and function range supported by the highest class model (FX2N or FX2) applicable in the product version. For supported models and device ranges, refer to the FX-10DU Operation Manual (Manual No. JY992D34701).

*1. The F940GOT and ET-940 whose version is earlier than Ver. 1.10 do not support the transparent (2-port) function of the GX Developer.

Show 5 more labels / short text on this page
GOT1000 Series Applicable · ET-940 Not applicable · FX-10DU Not applicable · ET-940 Not applicable · FX-10DU Not applicable
Page 915 of the Mitsubishi Electronics MELSEC FX3S user manual — 9 Z 1 0 1
Page 915 · click to enlarge
Page 915

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

A Programming Tool Applicability and Version Upgrade History

A-3 Version Upgrade History

Appendix A-3 Version Upgrade History

FNC277-FNC279 Data Transfer 3

Appendix A-3-1 Manufacturer's serial number check method

The year and month of production of the PLC main unit can be checked on the nameplate, and "LOT" indicated on the front of the product.

FNC280-FNC289 High-Speed Processing 2

1. Checking the nameplate The year and month of production of the product can be checked from the manufacturer's serial number S/N indicated on the label adhered to the right side of the product.

Example nameplate (manufacture's serial number : 1010001)

FNC290-FNC299 Extension File Register Control

FNC300-FNC305 FX 3U -CF-ADP

Actual product nameplate differs from the example shown above. *

9 Z 0 0 0

0 1 1 0 0 0

Month (Example: Dec.): 1 to 9 = January to September, X = October, Y = November, Z = December

Month (Example: Jan.): 1 to 9 = January to September, X = October, Y = November, Z = December

Year (Example2009): Last digit of year Year (Example: 2010): Last two digit of year
2. Checking the front of the product The year and month of production of the product can be checked from the manufacturer's serial number "LOT" on the front (at the bottom) of the product. The "LOT" indication is adopted in products manufactured at the following time.

Main unit "LOT" indication adoption time

FX3S Series PLC March 2013 and later (From first product)

FX3G Series PLC October 2008 and later

FX3GC Series PLC January 2012 and later (From first product)

FX3U Series PLC January 2009 and later

FX3UC Series PLC January 2009 and later

ExampleFX 3U -48MR/ES

A

9 Z 1 0 1

B

Month (Example: Jan.): 1 to 9 = January to September, X = October, Y = November, Z = December Year (Example: 2009): Last digit of year

Month (Example: Dec.): 1 to 9 = January to September, X = October, Y = November, Z = December

Year (Example2010): Last two digit of year
Show 9 more labels / short text on this page
Right side · Control number · Control number · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Up Information · Execution Times
Page 916 of the Mitsubishi Electronics MELSEC FX3S user manual — Appendix A-3-4 Version upgrade history [FX 3G ]
Page 916 · click to enlarge
Page 916

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

A Programming Tool Applicability and Version Upgrade History

A-3 Version Upgrade History

Appendix A-3-2 Version check

The PLC version can be verified by monitoring the special data register D8001 or D8101 and checking the last three digits. Or for the FX3U and FX3UC PLCs, the PLC version can be verified in "PLC Status" within the display module.

→ For the operating procedure of the display module, refer to the Hardware Edition Manual of the PLC to be checked.

D8001/D8101

2 4 1 0 0

Version information (ExampleVer. 1.00)
PLC type (Example24 = FX 3U /FX 3UC PLCs)

Appendix A-3-3 Version upgrade history [FX 3S ]

serial number Contents of version upgrade

Ver. 1.00 133**** (March, 2013) First product

  • FX 3S -30M † /E † -2AD (First product)
  • Supports connection of the following expansion board: - FX 3G -4EX-BD, FX 3G -2EYT-BD

Ver. 1.10 13X**** (October, 2013)

Appendix A-3-4 Version upgrade history [FX 3G ]

serial number Contents of version upgrade

Ver. 1.00 86**** (June, 2008) First product

  • Supports following 15 instructions: FLT (FNC 49), VRRD (FNC 85), VRSC (FNC 86), ECMP (FNC110), EMOV (FNC112), EADD (FNC120), ESUB (FNC121), EMUL (FNC122), EDIV (FNC123), ESQR (FNC127), INT (FNC129), IVCK (FNC270), IVDR (FNC271), IVRD (FNC272), IVWR (FNC273)
  • Supports connection of FX 3G -8AV-BD, FX 3G -2AD-BD, and FX 3G -1DA-BD.
  • Supports connection of display module (FX 3G -5DM).
  • Supports the floating point operation function.
  • Supports the inverter communication function.
  • Supports the pulse width/pulse period measurement function.

Ver. 1.10 8X**** (October, 2008)

  • Supports connection of following analog special adapters: - FX 3U -3A-ADP
  • Supports the hardware error function of FX 3U -4DA-ADP.

Ver. 1.20 96**** (June, 2009)

Ver. 1.30 9Z**** (December, 2009)

  • Supports the following instructions: ADPRW(FNC276)

Ver. 1.40 111**** (January, 2011)

  • Supports the following instructions: IVMC(FNC275)
  • Supports the following functions of the FX 3U -16CCL-M: - Network parameter - Accessing the other station from CC-Link - Remote device station initialization procedure registration - CC-Link diagnostics
  • Special parameter error (M8489 and D8489) is added.

Ver. 2.00 124**** (April, 2012)

Ver. 2.10 134**** (April, 2013) Supports the IP address change function of Ethernet adapter.

Ver. 2.20 13X**** (October, 2013)

  • Supports connection of the following expansion board: - FX 3G -4EX-BD, FX 3G -2EYT-BD

→ For the manufacturer’ serial number check method, refer to Appendix A-3-1.

Show 4 more labels / short text on this page
PLC type and · version · Version Manufacturer’s · Version Manufacturer’s
Page 917 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 917 · click to enlarge
Page 917

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

A Programming Tool Applicability and Version Upgrade History

A-3 Version Upgrade History

Appendix A-3-5 Version upgrade history [FX 3GC ]

FNC277-FNC279 Data Transfer 3

serial number Contents of version upgrade

Ver. 1.40 121**** (January, 2012)

First product Corresponds to FX3G PLC Ver. 1.40.

  • Supports the following functions of the FX 3U -16CCL-M: - Network parameter - Accessing the other station from CC-Link - Remote device station initialization procedure registration - CC-Link diagnostics
  • Special parameter error (M8489 and D8489) is added.

FNC280-FNC289 High-Speed Processing 2

Ver. 2.00 124**** (April, 2012)

Ver. 2.10 134**** (April, 2013) Supports the IP address change function of Ethernet adapter.

→ For the manufacturer’ serial number check method, refer to Appendix A-3-1.

FNC290-FNC299 Extension File Register Control

Appendix A-3-6 Version upgrade history [FX 3U ]

serial number Contents of version upgrade

Ver. 2.20 55**** (May, 2005)

First product (supporting the functions described as "Ver. 2.20 or later" in this manual) Corresponds to FX3UC PLC Ver. 2.20.

  • Adding the following instructions and function up. - Adding MEP and MEF instructions - Function up of MUL (FNC 22), DIV (FNC 23), and RS2 (FNC 87) instructions

FNC300-FNC305 FX 3U -CF-ADP

Ver. 2.30 5Y**** (November, 2005)

Ver. 2.40 74**** (April, 2007)

  • Supports the following instructions: ADPRW (FNC276)

Ver. 2.41 7Y**** (November, 2007)

  • The baud rate "38400 bps" is supported in the RS and RS2 instructions, inverter communication and computer link.
  • Supports following 6 instructions: FLCRT (FNC300), FLDEL (FNC301), FLWR (FNC302), FLRD (FNC303), FLCMD (FNC304), FLSTRD (FNC305)
  • Supports connection of following special adapters: - FX 3U -3A-ADP - FX 3U -CF-ADP
  • Supports the hardware error function of FX 3U -4DA-ADP.
  • Customer keyword / permanent PLC lock is supported.

Ver. 2.61 97**** (July, 2009)

  • Supports the following 3 instructions: VRRD (FNC85), VRSC (FNC86), IVMC (FNC275)
  • Supports connection of following analog volume expansion board: - FX 3U -8AV-BD
  • Supports the lower over-scale detection function of FX 3U -4AD-ADP and FX 3U -3A-ADP.

Ver. 2.70 107**** (July, 2010)

  • Supports storage of symbolic information.
  • Support of the setting "Read-protect the execution program" for block passwords.
  • Special block error condition (D8166) is added.
  • Supports connection of following memory cassette. - FX 3U -FLROM-1M

Ver. 3.00 115**** (May, 2011)

  • Supports the following functions of the FX 3U -16CCL-M: - Network parameter - Accessing the other station from CC-Link - Remote device station initialization procedure registration - CC-Link diagnostics
  • Special parameter error (M8489 and D8489) is added.

Ver. 3.10 11Y**** (November, 2011)

→ For the manufacturer’ serial number check method, refer to Appendix A-3-1.

Appendix A-3-7 Version upgrade history [FX 3UC ]

serial number Contents of version upgrade

A

Ver. 1.00 41**** (January, 2004) First product

Supports connection of the following special analog adapters:

Ver. 1.20 44**** (April, 2004)

- FX 3U -4AD-ADP - FX 3U -4DA-ADP

  • Supports connection of the following special analog adapters: - FX 3U -4AD-PT-ADP - FX 3U -4AD-TC-ADP
  • Supports connection of the following special function block: - FX 3UC -4AD
  • Supports the following 3 instructions: - SCL2 (FNC269), RWER (FNC 294), and INITER (FNC 295)
  • Adds function of the following instruction: - DVIT (FNC151)

B

Ver. 1.30 48**** (August, 2004)

Show 9 more labels / short text on this page
Version Manufacturer’s · Version Manufacturer’s · SFC•STL Programming · Interrupt Function · Special Device · Error Code · Version Manufacturer’s · Version Up Information · Execution Times
Page 918 of the Mitsubishi Electronics MELSEC FX3S user manual — - FX 3U -8AV-BD *3
Page 918 · click to enlarge
Page 918

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

A Programming Tool Applicability and Version Upgrade History

A-3 Version Upgrade History

serial number Contents of version upgrade

  • Supports the functions described as "Ver. 2.20 or later" in this manual.
  • Supports the following 28 instructions: ZPUSH (FNC102), ZPOP (FNC103), WSUM (FNC140), WTOB (FNC141), BTOW (FNC142), UNI (FNC143), DIS (FNC144), SORT2 (FNC149), TBL (FNC152), COMRD (FNC182), DUTY (FNC186), BK+ (FNC192), BK- (FNC193), BKCMP= (FNC194), BKCMP> (FNC195), BKCMP< (FNC196), BKCMP<> (FNC197), BKCMP<= (FNC198), BKCMP>= (FNC199), STR (FNC200), VAL (FNC201), INSTR (FNC208), FDEL (FNC210), FINS (FNC211), DABIN (FNC260), BINDA (FNC261), RBFM (FNC278), WBFM (FNC279)
  • Adds function of the following 5 instructions: SPD (FNC 56), DSZR (FNC150), DVIT (FNC151), ZRN (FNC156), PLSV (FNC157), HCMOV (FNC189)
  • Supports connection of FREQROL-F700/A700 inverters supporting the following 5 instructions: IVCK (FNC270), IVDR (FNC271), IVRD (FNC272), IVWR (FNC273), and IVBWR (FNC274)
  • Adds second entry code (when GX Developer SW8.23Z (Ver. 8.23Z or later) is used).
  • Supports BFM initial value setting function (when GX Developer SW8.23Z (Ver. 8.23Z or later) is used).
  • Mitigates restriction in writing during RUN (when GX Developer SW8.23Z (Ver. 8.23Z or later) is used). - Number of steps which can be changed by one-time write during RUN is changed. 127 steps → 256 steps - Handling of circuit blocks which can be changed by one-time write during RUN is changed. Program of continuous circuit blocks having 127 steps or less → Program of circuit blocks having 256 steps or less in total

Ver. 2.20 55**** (May, 2005)

Adding the following instructions and function upgrade. Adding MEP and MEF instructions Function upgrade of MUL (FNC 22), DIV (FNC 23), and RS2 (FNC 87) instructions.

Ver. 2.30 5Y**** (November, 2005)

Ver. 2.40 74**** (April, 2007)

  • Supports the following instructions: ADPRW(FNC276)

Ver. 2.41 79*****1

  • FX 3UC - MT/D(SS) (First product)
  • The baud rate "38400 bps" is supported in the RS and RS2 instructions, inverter communication and computer link.

Ver. 2.53 84**** (April, 2008) FX3UC-32MT-LT-2 (First product)

  • Supports the following 6 instructions: FLCRT (FNC300), FLDEL (FNC301), FLWR (FNC302), FLRD (FNC303), FLCMD (FNC304), FLSTRD (FNC305)
  • Supports connection of the following special adapters: - FX 3U -3A-ADP - FX 3U -CF-ADP
  • Supports the hardware error function of FX 3U -4DA-ADP.
  • Customer keyword / permanent PLC lock is supported.

Ver. 2.61*2 97**** (July, 2009)

  • FX 3UC -16MR/D-T, FX 3UC -16MR/DS-T (First product)
  • Supports the following 3 instructions: VRRD(FNC85), VRSC(FNC86), IVMC(FNC275)
  • Supports connection of the following analog volume expansion board:

Ver. 2.70 107**** (July, 2010)

- FX 3U -8AV-BD *3

  • Supports the lower over-scale detection function of FX 3U -4AD-ADP and FX 3U -3A-ADP.
  • Supports storage of symbolic information.
  • Support of the setting "Read-protect the execution program" for block passwords.
  • Special block error condition (D8166) is added.
  • Supports connection of following memory cassette. - FX 3U -FLROM-1M

Ver. 3.00 115**** (May, 2011)

  • Supports the following functions of the FX 3U -16CCL-M: - Network parameter - Accessing the other station from CC-Link - Remote device station initialization procedure registration - CC-Link diagnostics
  • Special parameter error (M8489 and D8489) is added.

Ver. 3.10 11Y**** (November, 2011)

*1. The FX3UC-32MT-LT supports Ver. 2.41 from the manufacturer's serial number "7X****" (October 2007).

*2. Available in Ver. 2.70 or later of FX3UC-32MT-LT-2 PLC.

*3. This function is supported only in the FX3UC-32MT-LT(-2).

→ For the manufacturer’ serial number check method, refer to Appendix A-3-1.

Version Manufacturer’s · (September, 2007)

Page 919 of the Mitsubishi Electronics MELSEC FX3S user manual — ORP 2.36 2.36
Page 919 · click to enlarge
Page 919

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-1 Basic Instruction Execution Time

FNC277-FNC279 Data Transfer 3

Appendix B: Instruction Execution Time

The instruction execution time in FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs is as shown below:

FNC280-FNC289 High-Speed Processing 2

Measurement condition

  • High-speed counters and interrupt instructions (I) are not used together.
  • In operands, data registers are used as target devices.
  • Indexing (V or Z) is not provided.

Appendix B-1 Basic Instruction Execution Time

FNC290-FNC299 Extension File Register Control

  • FX 3S PLC

Execution time in ON status (µs) Execution time in OFF status (µs)

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

FNC300-FNC305 FX 3U -CF-ADP

LD 0.21 1.34 µs in 2-step instruction

LDI 0.21 1.34 µs in 2-step instruction

LDP 2.32 2.28

LDF 2.59 2.32

AND 0.2 1.16 µs in 2-step instruction

ANI 0.2 1.16 µs in 2-step instruction

ANP 2.36 2.32

ANF 2.4 2.36

OR 0.21 1.28 µs in 2-step instruction

ORI 0.21 1.28 µs in 2-step instruction

ORP 2.36 2.36

ORF 2.4 2.36

ANB 0.2

ORB 0.2

MPS 0.21

MRD 0.2

MPP 0.17

INV 0.17

MEP 1.52

MEF 1.6

A

B

Show 9 more labels / short text on this page
Instruction · Contact instructions · SFC•STL Programming · Interrupt Function · Connection instructions · Special Device · Error Code · Version Up Information · Execution Times
Page 920 of the Mitsubishi Electronics MELSEC FX3S user manual — END 209 ⎯
Page 920 · click to enlarge
Page 920

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-1 Basic Instruction Execution Time

Execution time in ON status (µs) Execution time in OFF status (µs)

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

OUT Y,M 0.21 1.2 µs in 2-step instruction

OUT S 1.25 1.25

OUT T K 2.41 2.16

OUT T D 2.77 2.54

OUT C K 1.9 2.25 1.57 1.72 C235 to C255 1.6 µs in execution in ON status 1.06 µs in execution in OFF status

OUT C D 2.26 1.49 1.93 2.35 C235 to C255 2.21 µs in execution in ON status 1.06 µs in execution in OFF status

SET Y,M 0.23 1.25 µs in 2-step instruction

SET S 1.23 or 1.33 + 0.51n 0.59 n: Number of recombination 1.23 µs when there is no recombination

RST Y,M 0.23 1.22 µs in 2-step instruction

RST S 1.17 0.59

RST T 1.68 1.21

RST C 1.77 1.82 1.18 1.19

RST D 1.08 0.54

PLS Y,M 1.52

PLF Y,M 1.52

MC 1.63 1.76

MCR 1.3 ⎯

NOP 0.21

Even if FEND and END are used together, execution time of only END is required.

END 209 ⎯

Show 5 more labels / short text on this page
Instruction · Output instructions · Master control instructions · Other instruction · End instruction
Page 921 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 921 · click to enlarge
Page 921

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-1 Basic Instruction Execution Time

  • FX 3G /FX 3GC PLCs (Standard mode)

FNC277-FNC279 Data Transfer 3

Execution time in ON status (µs) Execution time in OFF status (µs)

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

LD 0.21 1.34 µs in 2-step instruction*1

1.34 µs in 3-step instruction*3

FNC280-FNC289 High-Speed Processing 2

LDI 0.21 1.34 µs in 2-step instruction*1

1.34 µs in 3-step instruction*3

2.4 µs in execution in ON status*3

LDP 2.32 2.28

2.36 µs in execution in OFF status*3

2.44 µs in execution in ON status*3

FNC290-FNC299 Extension File Register Control

LDF 2.36 2.32

2.4 µs in execution in OFF status*3

AND 0.2 1.16 µs in 2-step instruction*1

1.2 µs in 3-step instruction*3

ANI 0.2 1.16 µs in 2-step instruction*1

1.2 µs in 3-step instruction*3

FNC300-FNC305 FX 3U -CF-ADP

ANP 2.36 2.32

2.48 µs in execution in ON status*3

2.44 µs in execution in OFF status*3

ANF 2.4 2.36

2.48 µs in execution in ON status*3

2.44 µs in execution in OFF status*3

OR 0.21 1.28 µs in 2-step instruction*1

1.32 µs in 3-step instruction*3

ORI 0.21 1.28 µs in 2-step instruction*1

1.32 µs in 3-step instruction*3

ORP 2.36 2.32

2.48 µs in execution in ON status*3

2.44 µs in execution in OFF status*3

ORF 2.4 2.36

2.48 µs in execution in ON status*3

2.44 µs in execution in OFF status*3

ANB 0.2

ORB 0.2

MPS 0.21

MRD 0.2

MPP 0.17

INV 0.17

MEP 1.52

MEF 1.6

OUT Y,M 0.21 1.2 µs in 2-step instruction*2

1.2 µs in 3-step instruction*3

A

OUT S 1.25 1.25

OUT T K 2.41 2.16 T246 to T319 2.69 µs in execution in ON status 2.04 µs in execution in OFF status

B

Show 16 more labels / short text on this page
Instruction · Contact instructions · 3-step instruction · 3-step instruction · 3-step instruction · 3-step instruction · SFC•STL Programming · 3-step instruction · Interrupt Function · 3-step instruction · Connection instructions · Special Device · Error Code · Output instructions · Version Up Information · Execution Times
Page 922 of the Mitsubishi Electronics MELSEC FX3S user manual — END 292 + 2.5X + 3.75Y ⎯
Page 922 · click to enlarge
Page 922

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-1 Basic Instruction Execution Time

Execution time in ON status (µs) Execution time in OFF status (µs)

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

OUT T D 2.77 2.54 T246 to T319 3.06 µs in execution in ON status 2.41 µs in execution in OFF status

OUT C K 1.9 2.25 1.57 1.72 C235 to C255 1.6 µs in execution in ON status 1.06 µs in execution in OFF status

OUT C D 2.26 2.49 1.93 2.35 C235 to C255 2.21 µs in execution in ON status 1.06 µs in execution in OFF status

SET Y,M 0.23 1.25 µs in 2-step instruction*2

1.25 µs in 3-step instruction*3

SET S 1.23 or 1.33 + 0.51n 0.59 n: Number of recombination 1.23 µs when there is no recombination

RST Y,M 0.23 1.22 µs in 2-step instruction*2

1.22 µs in 3-step instruction*3

RST S 1.17 0.59

RST T 1.68 1.21

RST C 1.68 1.82 1.18 1.19

RST D 1.08 0.54

PLS Y,M 1.52 1.56 µs in M3584 to M7679

PLF Y,M 1.52 1.56 µs in M3584 to M7679

MC 1.63 1.76

MCR 1.3 ⎯

NOP 0.21

Even if FEND and END are used together, execution time of only END is required. X: Number of input points Y: Number of output points

END 292 + 2.5X + 3.75Y ⎯

*1. M1536 to M3583, M8256 to M8511, S1024 to S4095

*2. M1536 to M3583, M8000 to M8511

*3. M3584 to M7679

Show 5 more labels / short text on this page
Instruction · Output instructions · Master control instructions · Other instruction · End instruction
Page 923 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 923 · click to enlarge
Page 923

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-1 Basic Instruction Execution Time

  • FX 3G /FX 3GC PLCs (Extension mode)

FNC277-FNC279 Data Transfer 3

Execution time in ON status (µs) Execution time in OFF status (µs)

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

LD 0.42 1.68 µs in 2-step instruction*1

1.68 µs in 3-step instruction*3

FNC280-FNC289 High-Speed Processing 2

LDI 0.42 1.68 µs in 2-step instruction*1

1.68 µs in 3-step instruction*3

2.8 µs in execution in ON status*3

LDP 2.72 2.68

2.76 µs in execution in OFF status*3

2.84 µs in execution in ON status*3

FNC290-FNC299 Extension File Register Control

LDF 2.76 2.72

2.8 µs in execution in OFF status*3

AND 0.41 1.48 µs in 2-step instruction*1

1.52 µs in 3-step instruction*3

ANI 0.41 1.48 µs in 2-step instruction*1

1.52 µs in 3-step instruction*3

FNC300-FNC305 FX 3U -CF-ADP

ANP 2.72 2.68

2.8 µs in execution in ON status*3

2.76 µs in execution in OFF status*3

ANF 2.76 2.72

2.8 µs in execution in ON status*3

2.76 µs in execution in OFF status*3

OR 0.42 1.6 µs in 2-step instruction*1

1.6 µs in 3-step instruction*3

ORI 0.42 1.6 µs in 2-step instruction*1

1.6 µs in 3-step instruction*3

ORP 2.72 2.68

2.8 µs in execution in ON status*3

2.76 µs in execution in OFF status*3

ORF 2.76 2.72

2.8 µs in execution in ON status*3

2.76 µs in execution in OFF status*3

ANB 0.41

ORB 0.41

MPS 0.42

MRD 0.41

MPP 0.38

INV 0.38

MEP 1.73

MEF 1.81

OUT Y,M 0.42 1.52 µs in 2-step instruction*2

1.56 µs in 3-step instruction*3

A

OUT S 1.65 1.65

OUT T K 3.19 2.95 T246 to T319 3.47 µs in execution in ON status 2.82 µs in execution in OFF status

B

Show 16 more labels / short text on this page
Instruction · Contact instructions · 3-step instruction · 3-step instruction · 3-step instruction · 3-step instruction · SFC•STL Programming · 3-step instruction · Interrupt Function · 3-step instruction · Connection instructions · Special Device · Error Code · Output instructions · Version Up Information · Execution Times
Page 924 of the Mitsubishi Electronics MELSEC FX3S user manual — END 292 + 2.5X + 3.75Y ⎯
Page 924 · click to enlarge
Page 924

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-1 Basic Instruction Execution Time

Execution time in ON status (µs) Execution time in OFF status (µs)

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

OUT T D 3.55 3.32 T246 to T319 3.83 µs in execution in ON status 3.19 µs in execution in OFF status

OUT C K 2.68 3.02 2.35 2.89 C235 to C255 2.66 µs in execution in ON status 1.45 µs in execution in OFF status

OUT C D 3.04 3.25 2.72 3.1 C235 to C255 3.00 µs in execution in ON status 1.45 µs in execution in OFF status

SET Y,M 0.44 1.62 µs in 2-step instruction*2

1.62 µs in 3-step instruction*3

SET S 1.62 or 1.66 + 0.55n 0.78 n: Number of recombination n=1.62 when there is no recombination

RST Y,M 0.44 1.6 µs in 2-step instruction*2

1.6 µs in 3-step instruction*3

RST S 1.55 0.78

RST T 2.08 1.6

RST C 2.08 2.31 1.19 1.58

RST D 1.66 0.74

PLS Y,M 1.88 1.88 µs in M3584 to M7679

PLF Y,M 1.88 1.88 µs in M3584 to M7679

MC 2.01 2.13

MCR 1.51 ⎯

NOP 0.42

Even if FEND and END are used together, execution time of only END is required. X: Number of input points, Y: Number of output points

END 292 + 2.5X + 3.75Y ⎯

*1. M1536 to M3583, M8256 to M8511, S1024 to S4095

*2. M1536 to M3583, M8000 to M8511

*3. M3584 to M7679

Show 5 more labels / short text on this page
Instruction · Output instructions · Master control instructions · Other instruction · End instruction
Page 925 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 925 · click to enlarge
Page 925

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-1 Basic Instruction Execution Time

  • FX 3U /FX 3UC PLCs

FNC277-FNC279 Data Transfer 3

Execution time in ON status (µs) Execution time in OFF status (µs)

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

LD 0.065 0.129 µs in 2-step instruction*1

0.193 µs in 3-step instruction*3

FNC280-FNC289 High-Speed Processing 2

LDI 0.065 0.129 µs in 2-step instruction*1

0.193 µs in 3-step instruction*3

LDP 7.8 ⎯

LDF 7.8 ⎯

AND 0.065 0.129 µs in 2-step instruction*1

0.193 µs in 3-step instruction*3

FNC290-FNC299 Extension File Register Control

ANI 0.065 0.129 µs in 2-step instruction*1

0.193 µs in 3-step instruction*3

ANP 7.5 ⎯

ANF 7.5 ⎯

OR 0.065 0.129 µs in 2-step instruction*1

0.193 µs in 3-step instruction*3

FNC300-FNC305 FX 3U -CF-ADP

ORI 0.065 0.129 µs in 2-step instruction*1

0.193 µs in 3-step instruction*3

ORP 7.4 ⎯

ORF 7.4 ⎯

ANB 0.065

ORB 0.065

MPS 0.065

MRD 0.065

MPP 0.065

INV 0.065

MEP 3.4

MEF 3.4

OUT Y,M 0.065 0.129 µs in 2-step instruction*2

0.193 µs in 3-step instruction*3

OUT S 4.8 4.8

OUT T K 0.71 0.71 T192 to T199, T246 to T511 11.6 µs in execution in ON status 8.2 µs in execution in OFF status

OUT T D 0.71 0.71 T192 to T199, T246 to T511 11.6 µs in execution in ON status 8.2 µs in execution in OFF status

OUT C K 0.71 6.1 0.71 6.1 C235 to C255 9.5 µs in execution in ON status 9.0 µs in execution in OFF status

OUT C D 0.71 6.1 0.71 6.1 C235 to C255 9.5 µs in execution in ON status 9.0 µs in execution in OFF status

A

SET Y,M 0.065 0.129 µs in 2-step instruction*2

0.193 µs in 3-step instruction*3

SET S 4.7 or 6.6 + 0.9n 0.13 n: Number of recombination 4.7 µs when there is no recombination

RST Y,M 0.065 0.129 µs in 2-step instruction*2

0.193 µs in 3-step instruction*3

B

Show 10 more labels / short text on this page
Instruction · Contact instructions · Connection instructions · SFC•STL Programming · Interrupt Function · Output instructions · Special Device · Error Code · Version Up Information · Execution Times
Page 926 of the Mitsubishi Electronics MELSEC FX3S user manual — END 113.9 + 2.13X + 3.25Y ⎯
Page 926 · click to enlarge
Page 926

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-1 Basic Instruction Execution Time

Execution time in ON status (µs) Execution time in OFF status (µs)

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

RST S 4.6 0.13

RST T 0.45 0.45

RST C 0.45 5.8 0.45 4.8

RST D 5.4 ⎯ 0.195 ⎯

PLS Y,M 0.257 0.321 µs in M3584 to M7679

PLF Y,M 0.257 0.321 µs in M3584 to M7679

MC 4.3 4.7

MCR 3.9 ⎯

NOP 0.065

Even if FEND and END are used together, execution time of only END is required. X: Number of input points Y: Number of output points

END 113.9 + 2.13X + 3.25Y ⎯

*1. M1536 to M3583, M8256 to M8511, S1024 to S4095

*2. M1536 to M3583, M8000 to M8511

*3. M3584 to M7679

Show 5 more labels / short text on this page
Instruction · Output instructions · Master control instructions · Other instruction · End instruction
Page 927 of the Mitsubishi Electronics MELSEC FX3S user manual — Appendix B-2 Step Ladder Instruction Execution Time
Page 927 · click to enlarge
Page 927

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-2 Step Ladder Instruction Execution Time

Mitsubishi Electronics MELSEC FX3S — Appendix B-2 Step Ladder Instruction Execution Time diagram (page 927)
Fig. 844 · Appendix B-2 Step Ladder Instruction Execution Time

Execution time in ON status (µs) Execution time in OFF status (µs)

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

n: Number of recombination n = 0: When there is no recombination

n: Number of recombination n = 0: When there is no recombination

STL 3.36 + 1.19n ⎯ 3.35 + 1.46n ⎯

Execution time in ON status (µs) Execution time in OFF status (µs)

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

n: Number of recombination n = 0: When there is no recombination

Execution time in ON status (µs) Execution time in OFF status (µs)

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

Execution time in ON status (µs) Execution time in OFF status (µs)

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

P*** 0.065 0.129 µs in P256 to P4095

Page 928 of the Mitsubishi Electronics MELSEC FX3S user manual — 49 FLT 6.96 7.56 0.61 0.61
Page 928 · click to enlarge
Page 928

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-4 Applied Instruction Execution Time

Appendix B-4 Applied Instruction Execution Time

  • FX 3S PLC

Execution time in ON status (µs) Execution time in OFF status (µs)

No. Instruction

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

00 CJ 2.59 ⎯ 0.61 ⎯

⎯ 0.61 ⎯

01 CALL 6.44 (CALL+SRET)

02 SRET ⎯ ⎯ ⎯

03 IRET 6.34 ⎯ ⎯ ⎯

04 EI 2.52 ⎯ ⎯ ⎯

05 DI 1.94 ⎯ ⎯ ⎯

Even if FEND and END are used together, execution time of only END is required.

06 FEND 209 ⎯ ⎯

07 WDT 1.94 ⎯ 0.61 ⎯

08 FOR 4.98 (FOR+NEXT)

09 NEXT ⎯ ⎯ ⎯

10 CMP 11.18 11.54 0.61 0.61

11 ZCP 12.51 13.15 0.61 0.61

12 MOV 0.52 0.61 0.38 0.41 For details, refer to Appendix B-6-2.

13 SMOV 16.19 ⎯ 0.61 ⎯

14 CML 6.68 7.15 0.61 0.61

15 BMOV 15.95+3.96n ⎯ 0.61 ⎯

16 FMOV 10.20+0.77n 10.87+0.79n 0.61 0.61

18 BCD 2.93 4.6 0.41 0.43

19 BIN 2.93 4.61 0.41 0.43

Arithmetic and logical operation

20 ADD 1.79 2.13 0.41 0.45

21 SUB 1.79 2.13 0.41 0.45

22 MUL 1.29 3.21 0.41 0.45

23 DIV 1.93 3.7 0.41 0.45

24 INC 0.78 1.01 0.41 0.41

25 DEC 0.78 1.01 0.41 0.41

26 WAND 1.24 1.59 0.41 0.45

27 WOR 1.24 1.59 0.41 0.45

28 WXOR 1.24 1.59 0.41 0.45

30 ROR 7.37 8.94 0.61 0.61

31 ROL 7.37 8.94 0.61 0.61

34 SFTR 14.51+0.46n ⎯ 0.61 ⎯

35 SFTL 14.7+0.46n ⎯ 0.61 ⎯

36 WSFR 11.74+1.44n ⎯ 0.61 ⎯

37 WSFL 12.02+1.48n ⎯ 0.61 ⎯

38 SFWR 7.46 ⎯ 0.61 ⎯

39 SFRD 9.27 ⎯ 0.61 ⎯

ZRST(D) 7.96+0.22n ⎯ 0.61 ⎯ n: Number of reset points

ZRST(T) 8.77+0.46n ⎯ 0.61 ⎯ n: Number of reset points

ZRST(M) 14.76+0.37n ⎯ 0.61 ⎯ n: Number of reset points

41 DECO 8.5 ⎯ 0.61 ⎯

42 ENCO 9.29 ⎯ 0.61 ⎯

43 SUM 6.95 7.43 0.61 0.61

44 BON 10.4 10.77 0.61 0.61

45 MEAN 13.83+3.33n 14.69+3.5n 0.61 0.61

49 FLT 6.96 7.56 0.61 0.61

Show 5 more labels / short text on this page
Program flow · ⎯ ⎯ ⎯ · Move and compare · Rotation and shift · Data operation
Page 929 of the Mitsubishi Electronics MELSEC FX3S user manual — Appendix B-4 Applied Instruction Execution Time
Page 929 · click to enlarge
Page 929

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-4 Applied Instruction Execution Time

Mitsubishi Electronics MELSEC FX3S — Appendix B-4 Applied Instruction Execution Time diagram (page 929)
Fig. 845 · Appendix B-4 Applied Instruction Execution Time

Execution time in ON status (µs) Execution time in OFF status (µs)

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

Page 930 of the Mitsubishi Electronics MELSEC FX3S user manual — 270 IVCK 32.6 ⎯ 4.46 ⎯
Page 930 · click to enlarge
Page 930

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-4 Applied Instruction Execution Time

Execution time in ON status (µs) Execution time in OFF status (µs)

No. Instruction

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

170 GRY 11.46 11.81 0.61 0.61

171 GBIN 11.46 11.83 0.61 0.61

224 LD= 1.56 1.8 1.52 1.76 For details, refer to Appendix B-6-2.

225 LD> 1.92 2.36 1.92 2.32 For details, refer to Appendix B-6-2.

226 LD< 1.96 2.4 1.88 2.28 For details, refer to Appendix B-6-2.

228 LD 1.52 1.76 1.56 1.8 For details, refer to Appendix B-6-2.

229 LD

230 LD>= 1.84 2.28 1.92 2.36 For details, refer to Appendix B-6-2.

232 AND= 1.52 1.76 1.46 1.7 For details, refer to Appendix B-6-2.

233 AND> 1.88 2.24 1.84 2.28 For details, refer to Appendix B-6-2.

234 AND< 1.92 2.36 1.84 2.18 For details, refer to Appendix B-6-2.

236 AND 1.48 1.68 1.5 1.7 For details, refer to Appendix B-6-2.

237 AND

238 AND>= 1.8 2.16 1.92 2.32 For details, refer to Appendix B-6-2.

240 OR= 1.54 1.76 1.52 1.72 For details, refer to Appendix B-6-2.

241 OR> 1.92 2.32 1.88 2.32 For details, refer to Appendix B-6-2.

242 OR< 1.96 2.36 1.84 2.28 For details, refer to Appendix B-6-2.

244 OR 1.52 1.72 1.56 1.76 For details, refer to Appendix B-6-2.

245 OR

246 OR>= 1.84 2.2 1.96 2.36 For details, refer to Appendix B-6-2.

270 IVCK 32.6 ⎯ 4.46 ⎯

271 IVDR 31.6 ⎯ 4.46 ⎯

272 IVRD 35.3 ⎯ 4.46 ⎯

273 IVWR 34.6 ⎯ 4.46 ⎯

275 IVMC 44.2 ⎯ 4.46 ⎯

276 ADPRW 67.19 ⎯ 9.83 ⎯

External device · Data comparison · External device communication

Page 931 of the Mitsubishi Electronics MELSEC FX3S user manual — Appendix B-4 Applied Instruction Execution Time
Page 931 · click to enlarge
Page 931

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-4 Applied Instruction Execution Time

Mitsubishi Electronics MELSEC FX3S — Appendix B-4 Applied Instruction Execution Time diagram (page 931)
Fig. 846 · Appendix B-4 Applied Instruction Execution Time

Remarks Execution time in ON status (µs)

00 CJ 2.59 ⎯ 0.61 ⎯ 2.93 ⎯ 0.8 ⎯

03 IRET 6.34 ⎯ ⎯ ⎯ 6.9 ⎯ ⎯ ⎯

04 EI 2.52 ⎯ ⎯ ⎯ 2.71 ⎯ ⎯ ⎯

05 DI 1.94 ⎯ ⎯ ⎯ 2.12 ⎯ ⎯ ⎯

Even if FEND and END are used together, execution time of only END is required. X: Number of input points, Y: Number of output points

07 WDT 1.94 ⎯ 0.61 ⎯ 2.16 ⎯ 0.8 ⎯

10 CMP 11.18 11.54 0.61 0.61 12.91 13.66 0.8 0.8

11 ZCP 12.51 13.15 0.61 0.61 14.62 16.02 0.8 0.8

12 MOV 0.52 0.61 0.38 0.41 1.29 1.56 0.61 0.65 For details, refer to Appendix B-6-2.

13 SMOV 16.19 ⎯ 0.61 ⎯ 18.68 ⎯ 0.8 ⎯

14 CML 6.68 7.15 0.61 0.61 8.03 8.5 0.8 0.8

15 BMOV 15.08+5.58n ⎯ 0.61 ⎯ 17.54+5.58n ⎯ 0.8 ⎯

16 FMOV 10.20+0.77n 10.87+0.79n 0.61 0.61 11.90+0.77n 12.94+0.79n 0.8 0.8

18 BCD 2.93 4.6 0.41 0.43 3.9 5.8 0.61 0.65

19 BIN 2.93 4.61 0.41 0.43 4.01 5.82 0.61 0.65

20 ADD 1.79 2.13 0.41 0.45 3.14 3.87 0.61 0.65

21 SUB 1.79 2.13 0.41 0.45 3.14 3.87 0.61 0.65

22 MUL 1.29 3.21 0.41 0.45 2.78 4.88 0.61 0.65

23 DIV 1.93 3.7 0.41 0.45 3.48 5.3 0.61 0.65

24 INC 0.78 1.01 0.41 0.41 1.53 1.96 0.61 0.65

25 DEC 0.78 1.01 0.41 0.41 1.53 1.96 0.61 0.65

26 WAND 1.24 1.59 0.41 0.45 2.61 3.34 0.61 0.65

27 WOR 1.24 1.59 0.41 0.45 2.61 3.34 0.61 0.65

28 WXOR 1.24 1.59 0.41 0.45 2.61 3.34 0.61 0.65

30 ROR 7.37 8.94 0.61 0.61 8.21 10.21 0.8 0.8

31 ROL 7.37 8.94 0.61 0.61 8.21 10.21 0.8 0.8

34 SFTR 14.51+0.46n ⎯ 0.61 ⎯ 16.61+0.46n ⎯ 0.8 ⎯

35 SFTL 14.7+0.46n ⎯ 0.61 ⎯ 16.82+0.46n ⎯ 0.8 ⎯

36 WSFR 11.74+1.44n ⎯ 0.61 ⎯ 13.91+1.44n ⎯ 0.8 ⎯

37 WSFL 12.02+1.48n ⎯ 0.61 ⎯ 14.11+1.48n ⎯ 0.8 ⎯

38 SFWR 7.46 ⎯ 0.61 ⎯ 9.19 ⎯ 0.8 ⎯

39 SFRD 9.27 ⎯ 0.61 ⎯ 10.99 ⎯ 0.8 ⎯

Page 932 of the Mitsubishi Electronics MELSEC FX3S user manual — Appendix B-4 Applied Instruction Execution Time
Page 932 · click to enlarge
Page 932

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-4 Applied Instruction Execution Time

Standard mode Extension mode

Remarks Execution time in ON status (µs)

Execution time in ON status (µs)

No.

ZRST(D) 7.96+0.22n ⎯ 0.61 ⎯ 10.26+0.22n ⎯ 0.8 ⎯ n: Number of reset points

ZRST(T) 8.77+0.46n ⎯ 0.61 ⎯ 10.68+0.46n ⎯ 0.8 ⎯ n: Number of reset points

ZRST(M) 14.76+0.37n ⎯ 0.61 ⎯ 16.16+0.37n ⎯ 0.8 ⎯ n: Number of reset points

41 DECO 8.5 ⎯ 0.61 ⎯ 10.31 ⎯ 0.8 ⎯

42 ENCO 9.29 ⎯ 0.61 ⎯ 11.02 ⎯ 0.8 ⎯

43 SUM 6.95 7.43 0.61 0.61 8.3 8.76 0.8 0.8

44 BON 10.4 10.77 0.61 0.61 12.13 12.83 0.8 0.8

45 MEAN 13.83+3.33n 14.69+3.5n 0.61 0.61 16.28+3.32n 17.6+3.49n 0.8 0.8

46 ANS 9.55 ⎯ 9.09 ⎯ 11.27 ⎯ 10.81 ⎯

47 ANR 11.08 ⎯ 0.61 ⎯ 11.12 ⎯ 0.8 ⎯

49 FLT 6.96 7.56 0.61 0.61 8.28 8.88 0.8 0.8

50 REF 9+1.43n ⎯ 0.61 ⎯ 10.27+1.42n ⎯ 0.8 ⎯

52 MTR 14.72 ⎯ 1.65 ⎯ 16.11 ⎯ 1.85 ⎯

53 HSCS ⎯ 10.8 ⎯ 0.61 ⎯ 12.8 ⎯ 0.8

54 HSCR ⎯ 10.79 ⎯ 0.61 ⎯ 12.71 ⎯ 0.8

55 HSZ ⎯ 12.2 ⎯ 0.61 ⎯ 14.86 ⎯ 0.8

56 SPD 15.51 15.86 3.08 3.12 17.25 18.01 3.27 3.31

57 PLSY 38.21 38.61 4.63 4.78 40.1 41.33 5.5 5.36

58 PWM 21.79 ⎯ 8.11 ⎯ 22.46 ⎯ 8.5 ⎯

59 PLSR 156.25 157.02 4.61 4.66 158.85 159.63 5.3 5.33

60 IST 23.33 ⎯ 0.61 ⎯ 25.3 ⎯ 0.8 ⎯

61 SER 21.33+3.97n 22.14+4.29n 2.4 2.3 23.99+3.96n 25.7+4.29n 2.6 2.5

62 ABSD 14.72+2.25n 15.22+3.44n 0.61 0.61 17.04+2.25n 17.96+3.44n 0.8 0.8

63 INCD 23.69 ⎯ 3.04 ⎯ 25.02 ⎯ 3.23 ⎯

66 ALT 5.82 ⎯ 0.61 ⎯ 6.62 ⎯ 0.8 ⎯

67 RAMP 12.33 ⎯ 9.89 ⎯ 15.21 ⎯ 12.37 ⎯

External FX I/O device

72 DSW 24.74 ⎯ 18 ⎯ 27.08 ⎯ 20.3 ⎯

74 SEGL 17.76 ⎯ 6.27 ⎯ 19.34 ⎯ 6.41 ⎯

FROM*1 115.6+454.4n 119.14+904.86n 0.61 0.61 117.29+454.74n 121.98+905.03n 0.8 0.8 n: Number of transfer points

FROM*2 114.98+968.02n 119.62+1931.4n 0.61 0.61 117.81+968.19n 123.62+1931.4n 0.8 0.8 n: Number of transfer points

FROM*3 52.58+131.43n 11.67+242.33n 0.61 0.61 55.58+131.43n 14.67+242.34n 0.8 0.8 n: Number of transfer points

TO*1 74.84+515.17n 78.31+1025.7n 0.61 0.61 76.67+515.34n 82.39+1025.7n 0.8 0.8 n: Number of transfer points

TO*2 77.62+1025.4n 78.93+2047.1n 0.61 0.61 81.62+1025.4n 82.93+2047.1n 0.8 0.8 n: Number of transfer points

TO*3 129.9+134.1n 13.67+350.33n 0.61 0.61 132.91+134.1n 18.58+350.43n 0.8 0.8 n: Number of transfer points

*1. When the instruction is executed to BFM #0 to BFM #31 in a special function unit/block for the FX2N Series. *2. When the instruction is executed to BFM #32 or later in a special function unit/block for the FX2N Series. *3. When the instruction is executed to a BFM in a special function unit/block for the FX3U/FX3UC Series

Mitsubishi Electronics MELSEC FX3S — Appendix B-4 Applied Instruction Execution Time diagram (page 932)
Fig. 847 · Appendix B-4 Applied Instruction Execution Time

80 RS 17.21 ⎯ 2.52 ⎯ 19.99 ⎯ 2.91 ⎯

81 PRUN 11.41+1.67n 11.65+1.63n 0.61 0.61 12.92+1.6n 12.87+1.65n 0.8 0.8

82 ASCI 12.34+1.52n ⎯ 0.61 ⎯ 14.07+1.52n ⎯ 0.8 ⎯

83 HEX 11.89+2.66n ⎯ 0.61 ⎯ 13.66+2.66n ⎯ 0.8 ⎯

84 CCD 11.98+1.16n ⎯ 0.61 ⎯ 13.7+1.16n ⎯ 0.8 ⎯

85 VRRD 102.46 ⎯ 0.61 ⎯ 103.88 ⎯ 0.8 ⎯

86 VRSC 102.46 ⎯ 0.61 ⎯ 103.88 ⎯ 0.8 ⎯

87 RS2 23.48 ⎯ 2.68 ⎯ 26.52 ⎯ 2.92 ⎯

88 PID 29.1 ⎯ 15.41 ⎯ 31.5 ⎯ 18.005 ⎯

Show 23 more labels / short text on this page
Execution time · Execution time · in OFF status · in OFF status · Instruc- · tion · (µs) · (µs) · 16-bit instruction · 32-bit instruction · 16-bit instruc · 32-bit instruc · 16-bit instruction · 32-bit instruction · 16-bit instruc · 32-bit instruc · tion · tion · tion · tion · Data operation · High-speed processing · Handy instructions
Page 933 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 933 · click to enlarge
Page 933

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-4 Applied Instruction Execution Time

Standard mode Extension mode

FNC277-FNC279 Data Transfer 3

Remarks Execution time in ON status (µs)

Execution time in ON status (µs)

No.

FNC280-FNC289 High-Speed Processing 2

110 ECMP ⎯ 12.46 ⎯ 0.61 ⎯ 14.68 ⎯ 0.8

112 EMOV ⎯ 6.36 ⎯ 0.61 ⎯ 7.68 ⎯ 0.8

120 EADD ⎯ 11.96 ⎯ 0.61 ⎯ 13.96 ⎯ 0.8

121 ESUB ⎯ 12.06 ⎯ 0.61 ⎯ 13.98 ⎯ 0.8

122 EMUL ⎯ 12.76 ⎯ 0.61 ⎯ 14.68 ⎯ 0.8

123 EDIV ⎯ 20.86 ⎯ 0.61 ⎯ 22.68 ⎯ 0.8

FNC290-FNC299 Extension File Register Control

127 ESQR ⎯ 10.66 ⎯ 0.61 ⎯ 11.88 ⎯ 0.8

129 INT 12.06 12.06 0.61 0.61 13.28 13.28 0.8 0.8

150 DSZR 166.48 ⎯ 4.56 ⎯ 168.92 ⎯ 4.96 ⎯

152 TBL ⎯ *1 ⎯ 0.61 ⎯ *1 ⎯ 0.8

155 ABS ⎯ 16.68 ⎯ 3.68 ⎯ 18.52 ⎯ 3.88

FNC300-FNC305 FX 3U -CF-ADP

156 ZRN 140.48 141.48 4.68 4.68 142.92 143.92 5.08 5.08

157 PLSV 160.48 160.48 4.64 4.64 161.92 162.92 5.04 5

158 DRVI 275.38 275.94 4.78 4.78 278.02 278.58 5.12 5.12

159 DRVA 276.08 276.65 4.74 4.74 278.69 279.25 5.16 5.16

*1. The instruction execution time is as shown below depending on the executed positioning type (instruction)

Instruction execution time in ON status (µs)

Positioning type Operation instruction

Standard mode Extension mode

DPLSV (variable speed pulse output) DPLSV instruction 160.48 µs 162.92 µs

DDRVI (drive to increment) DDRVI instruction 275.94 µs 278.58 µs

DDRVA (drive to absolute) DDRVA instruction 276.65 µs 279.25 µs

Real time clock control

160 TCMP 15.07 ⎯ 0.61 ⎯ 17.57 ⎯ 0.8 ⎯

161 TZCP 17.84 ⎯ 0.61 ⎯ 20.33 ⎯ 0.8 ⎯

162 TADD 11.98 ⎯ 0.61 ⎯ 13.91 ⎯ 0.8 ⎯

163 TSUB 11.98 ⎯ 0.61 ⎯ 13.91 ⎯ 0.8 ⎯

166 TRD 6.76 ⎯ 0.61 ⎯ 7.52 ⎯ 0.8 ⎯

167 TWR 337.1 ⎯ 0.61 ⎯ 339.6 ⎯ 0.8 ⎯

169 HOUR 10.86 11.57 10.44 10.44 12.59 13.69 12.17 13.01

170 GRY 11.46 11.81 0.61 0.61 12.62 13.35 0.8 0.8

171 GBIN 11.46 11.83 0.61 0.61 12.62 13.37 0.8 0.8

176 RD3A (2AD) 1939 ⎯ 0.61 ⎯ 1941 ⎯ 0.8 ⎯ FX2N-2AD

177 WR3A (2DA) 3086 ⎯ 0.61 ⎯ 3089 ⎯ 0.8 ⎯ FX2N-2DA

224 LD= 1.56 1.8 1.52 1.76 2.28 2.72 2.24 2.68 For details, refer to Appendix B-6-2.

225 LD> 1.92 2.36 1.92 2.32 2.68 3.24 2.68 3.24 For details, refer to Appendix B-6-2.

A

226 LD< 1.96 2.4 1.88 2.28 2.72 3.28 2.64 3.2 For details, refer to Appendix B-6-2.

228 LD 1.52 1.76 1.56 1.8 2.24 2.68 2.28 2.72 For details, refer to Appendix B-6-2.

229 LD

B

230 LD>= 1.84 2.28 1.92 2.36 2.6 3.16 2.72 3.28 For details, refer to Appendix B-6-2.

232 AND= 1.52 1.76 1.46 1.7 2.28 2.96 2.24 2.64 For details, refer to Appendix B-6-2.

Show 30 more labels / short text on this page
Execution time · Execution time · in OFF status · in OFF status · Instruc- · tion · (µs) · (µs) · 16-bit instruction · 32-bit instruction · 16-bit instruc · 32-bit instruc · 16-bit instruction · 32-bit instruction · 16-bit instruc · 32-bit instruc · tion · tion · tion · tion · Floating point · Positioning control · SFC•STL Programming · Interrupt Function · Special Device · External device · Error Code · Data comparison · Version Up Information · Execution Times
Page 934 of the Mitsubishi Electronics MELSEC FX3S user manual — Appendix B-4 Applied Instruction Execution Time
Page 934 · click to enlarge
Page 934

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-4 Applied Instruction Execution Time

Standard mode Extension mode

Remarks Execution time in ON status (µs)

Execution time in ON status (µs)

No.

233 AND> 1.88 2.24 1.84 2.28 2.6 3.2 2.6 3.2 For details, refer to Appendix B-6-2.

234 AND< 1.92 2.36 1.84 2.18 2.68 3.28 2.56 3.16 For details, refer to Appendix B-6-2.

236 AND 1.48 1.68 1.5 1.7 2.24 2.64 2.24 2.64 For details, refer to Appendix B-6-2.

237 AND

238 AND>= 1.8 2.16 1.92 2.32 2.52 3.12 2.64 3.24 For details, refer to Appendix B-6-2.

240 OR= 1.54 1.76 1.52 1.72 2.28 2.68 2.24 2.64 For details, refer to Appendix B-6-2.

241 OR> 1.92 2.32 1.88 2.32 2.64 3.24 2.64 3.24 For details, refer to Appendix B-6-2.

242 OR< 1.96 2.36 1.84 2.28 2.68 3.28 2.6 3.2 For details, refer to Appendix B-6-2.

244 OR 1.52 1.72 1.56 1.76 2.24 2.64 2.28 2.68 For details, refer to Appendix B-6-2.

245 OR

246 OR>= 1.84 2.2 1.96 2.36 2.56 3.16 2.68 3.28 For details, refer to Appendix B-6-2.

270 IVCK 32.60 ⎯ 4.46 ⎯ 33.90 ⎯ 4.88 ⎯

271 IVDR 31.60 ⎯ 4.46 ⎯ 32.40 ⎯ 4.88 ⎯

272 IVRD 35.30 ⎯ 4.46 ⎯ 36.60 ⎯ 4.88 ⎯

273 IVWR 34.60 ⎯ 4.46 ⎯ 35.40 ⎯ 4.88 ⎯

275 IVMC 44.2 ⎯ 4.46 ⎯ 45.4 ⎯ 4.88 ⎯

276 ADPRW 68.15 ⎯ 8.83 ⎯ 71.48 ⎯ 9.77 ⎯

Extension file register control

290 LOADR 107.23+30.25n ⎯ 0.61 ⎯ 108.59+30.33n ⎯ 0.8 ⎯

294 RWER 4692.4+128.57n ⎯ 0.61 ⎯ 4700.4+128.57n ⎯ 0.8 ⎯ n:Number of write points (Unit: Word)

Show 22 more labels / short text on this page
Execution time · Execution time · in OFF status · in OFF status · Instruc- · tion · (µs) · (µs) · 16-bit instruction · 32-bit instruction · 16-bit instruc · 32-bit instruc · 16-bit instruction · 32-bit instruction · 16-bit instruc · 32-bit instruc · tion · tion · tion · tion · Data comparison · External device communication
Page 935 of the Mitsubishi Electronics MELSEC FX3S user manual — Appendix B-4 Applied Instruction Execution Time
Page 935 · click to enlarge
Page 935

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-4 Applied Instruction Execution Time

Mitsubishi Electronics MELSEC FX3S — Appendix B-4 Applied Instruction Execution Time diagram (page 935)
Fig. 848 · Appendix B-4 Applied Instruction Execution Time

Execution time in ON status (µs) Execution time in OFF status (µs)

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

Even if FEND and END are used together, execution time of only END is required. X: Number of input points, Y: Number of output points

06 FEND 113.9 + 2.13X + 3.25Y ⎯ ⎯ ⎯

12 MOV 0.64 1.48 0.32 1.48 For details, refer to Appendix B-6-2.

16 FMOV 14.2 + 0.19n 14.0 + 0.38n 0.455 0.845

Page 936 of the Mitsubishi Electronics MELSEC FX3S user manual — 70 TKY 21.5 21.8 5.2 5.2
Page 936 · click to enlarge
Page 936

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-4 Applied Instruction Execution Time

Execution time in ON status (µs) Execution time in OFF status (µs)

No. Instruction

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

ZRST(D) 11.1 + 0.19n ⎯ 0.325 ⎯ n: Number of reset points

ZRST(T) 17.1 + 0.23n ⎯ 0.325 ⎯ n: Number of reset points

ZRST(M) 20.7 + 0.02n ⎯ 0.325 ⎯ n: Number of reset points

41 DECO 13.5 ⎯ 0.455 ⎯

42 ENCO 18.0 ⎯ 0.455 ⎯

43 SUM 12.7 16.9 0.325 0.585

44 BON 14.4 15.1 0.455 0.845

45 MEAN 11.8 + 0.41n 17.8 + 2.13n 0.455 0.845

46 ANS 20.4 ⎯ 19.7 ⎯

47 ANR 7.0 ⎯ 0.065 ⎯

48 SQR 9.7 12.1 0.325 0.585

49 FLT 9.8 9.5 0.325 0.585

50 REF 4.5 + 1.39n ⎯ 0.325 ⎯

51 REFF 14.4 + 0.24n ⎯ 0.195 ⎯

52 MTR 5.9 ⎯ 5.5 ⎯

53 HSCS ⎯ 20.0 ⎯ 0.845

54 HSCR ⎯ 20.0 ⎯ 0.845

55 HSZ ⎯ 22.0 ⎯ 1.105

56 SPD 16.0 16.0 12.6 12.6

57 PLSY 20.0 13.6 6.9 6.9

58 PWM 10.6 ⎯ 6.2 ⎯

59 PLSR 11.2 11.2 7.0 7.0

60 IST 28.5 ⎯ 0.455 ⎯

61 SER 16.4 + 1.4n 18.5 + 2.13n 0.585 1.105

62 ABSD 19 + 0.85n 20.0 + 1.23n 0.585 1.105

63 INCD 23.7 ⎯ 6.5 ⎯

64 TTMR 10.4 ⎯ 9.2 ⎯

65 STMR 19.0 ⎯ 21.0 ⎯

66 ALT 11.6 ⎯ 0.2 ⎯

67 RAMP 15.0 ⎯ 7.5 ⎯

68 ROTC 25.8 ⎯ 24.8 ⎯

69 SORT 18.4 ⎯ 6.6 ⎯

External FX I/O device

70 TKY 21.5 21.8 5.2 5.2

71 HKY 32.0 32.3 5.7 5.7

72 DSW 26.8 ⎯ 22.1 ⎯

73 SEGD 10.8 ⎯ 0.325 ⎯

74 SEGL 22.3 ⎯ 7.5 ⎯

75 ARWS 28.8 ⎯ 5.2 ⎯

76 ASC 19.8 ⎯ 0.715 ⎯

77 PR 24.0 ⎯ 13.6 ⎯

Data operation · High-speed processing · Handy instructions

Page 937 of the Mitsubishi Electronics MELSEC FX3S user manual — 118 EBCD ⎯ 10.0 ⎯ 0.585
Page 937 · click to enlarge
Page 937

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-4 Applied Instruction Execution Time

Execution time in ON status (µs) Execution time in OFF status (µs)

FNC277-FNC279 Data Transfer 3

No. Instruction

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

External FX I/O device

FROM*1 141 + 419n 119 + 841n 0.585 1.105 n: Number of transfer points

FROM*2 107 + 903n 119 + 1791n 0.585 1.105 n: Number of transfer points

FROM*3 27.9 + 108n 17.6 + 187.4n 0.585 1.105 n: Number of transfer points

FNC280-FNC289 High-Speed Processing 2

TO*1 87 + 483n 73 + 967n 0.585 1.105 n: Number of transfer points

TO*2 73 + 967n 67 + 1923n 0.585 1.105 n: Number of transfer points

TO*3 96.7 + 119.2n 17.3 + 297.7n 0.585 1.105 n: Number of transfer points

*1. When the instruction is executed to BFM #0 to BFM #31 in a special function unit/block for the FX0N/FX2N/ FX2NC Series or in the CC-Link/LT built in the FX3UC-32MT-LT(-2)

FNC290-FNC299 Extension File Register Control

*2. When the instruction is executed to BFM #32 or later in a special function unit/block for the FX0N/FX2N/FX2NC Series or in the CC-Link/LT built in the FX3UC-32MT-LT(-2)

*3. When the instruction is executed to a BFM in a special function unit/block for the FX3U/FX3UC Series

80 RS 15.6 ⎯ 5.7 ⎯

81 PRUN 17.1 + 1.67n 18.2 + 2.9n 0.325 0.585

FNC300-FNC305 FX 3U -CF-ADP

82 ASCI 13.5 + 1.45n ⎯ 0.455 ⎯

83 HEX 13.6 + 1.89n ⎯ 0.455 ⎯

84 CCD 13.6 + 1.63n ⎯ 0.455 ⎯

85 VRRD 129.50 ⎯ 0.325 ⎯

86 VRSC 129.94 ⎯ 0.325 ⎯

87 RS2 18.1 ⎯ 5.3 ⎯

88 PID 20.0 ⎯ 8.9 ⎯

89 ⎯

100 ⎯

101 ⎯

102 ZPUSH 16.0 ⎯ 0.195 ⎯

103 ZPOP 16.0 ⎯ 0.195 ⎯

104 ⎯

105 ⎯

106 ⎯

107 ⎯

108 ⎯

109 ⎯

110 ECMP ⎯ 18.2 ⎯ 0.845

111 EZCP ⎯ 21.6 ⎯ 1.105

112 EMOV ⎯ 10.0 ⎯ 0.585

113 ⎯

114 ⎯

115 ⎯

n: Number of character

digits mNumber of digits in

A

116 ESTR ⎯ 27 + 1.7n + 1.26m ⎯ 0.845

117 EVAL ⎯ 26 + 3.8n ⎯ 0.585

118 EBCD ⎯ 10.0 ⎯ 0.585

119 EBIN ⎯ 11.9 ⎯ 0.585

120 EADD ⎯ 14.2 ⎯ 0.845

B

121 ESUB ⎯ 14.2 ⎯ 0.845

122 EMUL ⎯ 14.1 ⎯ 0.845

123 EDIV ⎯ 17.7 ⎯ 0.845

Show 10 more labels / short text on this page
External FX device · SFC•STL Programming · Data move 2 · Interrupt Function · Special Device · Floating point · Error Code · decimal part · Version Up Information · Execution Times
Page 938 of the Mitsubishi Electronics MELSEC FX3S user manual — 155 ABS ⎯ 25.4 ⎯ 22.2
Page 938 · click to enlarge
Page 938

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-4 Applied Instruction Execution Time

Execution time in ON status (µs) Execution time in OFF status (µs)

No. Instruction

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

124 EXP ⎯ 11.9 ⎯ 0.585

125 LOGE ⎯ 24.0 ⎯ 0.585

126 LOG10 ⎯ 24.3 ⎯ 0.585

127 ESQR ⎯ 10.6 ⎯ 0.585

128 ENEG ⎯ 8.9 ⎯ 0.325

129 INT 13.2 13.0 0.325 0.585

130 SIN ⎯ 12.0 ⎯ 0.585

131 COS ⎯ 23.2 ⎯ 0.585

132 TAN ⎯ 12.0 ⎯ 0.585

133 ASIN ⎯ 13.5 ⎯ 0.585

134 ACOS ⎯ 13.5 ⎯ 0.585

135 ATAN ⎯ 12.0 ⎯ 0.585

136 RAD ⎯ 14.9 ⎯ 0.585

137 DEG ⎯ 14.9 ⎯ 0.585

138 ⎯

139 ⎯

140 WSUM 11.7 + 0.38n 14.1 + 1.94n 0.455 0.845

141 WTOB 12.6 + 1.43n ⎯ 0.455 ⎯

142 BTOW 12.6 + 0.92n ⎯ 0.455 ⎯

143 UNI 11.6 + 0.4n ⎯ 0.455 ⎯

144 DIS 10.6 + 0.2n ⎯ 0.455 ⎯

145 ⎯

146 ⎯

147 SWAP 7.7 8.0 0.195 0.325

148 ⎯

149 SORT2 13.2 15.2 6.5 7.7

150 DSZR 170.0 ⎯ 7.0 ⎯

151 DVIT 178.0 178.0 7.1 7.1

152 TBL ⎯ *1 ⎯ 7.1

153 ⎯

154 ⎯

155 ABS ⎯ 25.4 ⎯ 22.2

156 ZRN 58.0 62.0 7.1 7.1

157 PLSV 144.0 144.0 7.1 7.1

158 DRVI 178.0 178.0 7.1 7.1

159 DRVA 178.0 178.0 7.1 7.1

*1. The instruction execution time is as shown below depending on the executed positioning type (instruction)

Positioning type Operation instruction Instruction execution time in ON status (µs)

DDVIT (interrupt positioning) DDVIT instruction 178.0 µs

DPLSV (variable speed pulse output) DPLSV instruction 144.0 µs

DDRVI (drive to increment) DDRVI instruction 178.0 µs

DDRVA (drive to absolute) DDRVA instruction 178.0 µs

Floating point · Data operation 2 · Positioning control

Page 939 of the Mitsubishi Electronics MELSEC FX3S user manual — Appendix B-4 Applied Instruction Execution Time
Page 939 · click to enlarge
Page 939

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-4 Applied Instruction Execution Time

Mitsubishi Electronics MELSEC FX3S — Appendix B-4 Applied Instruction Execution Time diagram (page 939)
Fig. 849 · Appendix B-4 Applied Instruction Execution Time

Execution time in ON status (µs) Execution time in OFF status (µs)

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

176 RD3A(3A) 1404 ⎯ 0.455 ⎯ FX0N-3A

177 WR3A(3A) 1466 ⎯ 0.455 ⎯ FX0N-3A

192 BK+ 13.1 + 0.66n 13.9 + 1.23n 0.585 1.105

193 BK- 13.1 + 0.66n 13.9 + 1.23n 0.585 1.105

194 BKCMP= 19.6 + 1.88n 20.3 + 2.26n 0.585 1.105

195 BKCMP> 19.6 + 1.88n 20.3 + 2.26n 0.585 1.105

196 BKCMP< 19.6 + 1.88n 20.3 + 2.26n 0.585 1.105

197 BKCMP 19.6 + 1.88n 20.3 + 2.26n 0.585 1.105

198 BKCMP

199 BKCMP>= 19.6 + 1.88n 20.3 + 2.26n 0.585 1.105

202 $+ 24.8 + 1.5m ⎯ 0.455 ⎯ m: Number of character

203 LEN 12 + 0.44m ⎯ 0.325 ⎯ m: Number of character

204 RIGHT 18.1 + 1.06n + 0.47m ⎯ 0.455 ⎯

205 LEFT 18.1 + 0.74n + 0.44m ⎯ 0.455 ⎯

Page 940 of the Mitsubishi Electronics MELSEC FX3S user manual — Appendix B-4 Applied Instruction Execution Time
Page 940 · click to enlarge
Page 940

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-4 Applied Instruction Execution Time

Mitsubishi Electronics MELSEC FX3S — Appendix B-4 Applied Instruction Execution Time diagram (page 940)
Fig. 850 · Appendix B-4 Applied Instruction Execution Time

Execution time in ON status (µs) Execution time in OFF status (µs)

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

206 MIDR 25 + 0.59n + 0.68m ⎯ 0.455 ⎯ n: Character position m: Number of characters

207 MIDW 25.8 + 0.3m + 0.44n ⎯ 0.455 ⎯

208 INSTR 20.6 + 2.98m ⎯ 0.585 ⎯ m: Number of searched

*1. Number of characters from the head of the searched character string to detected character

210 FDEL 43 + 0.95m ⎯ ⎯ ⎯ m: Number of data shifted

211 FINS 63 + 0.98m ⎯ ⎯ ⎯ m: Number of data shifted

*2. m = (Number of data tables) - (Table position of deleted data)

Number of data tablesPresent value of , table position of deleted data: n

*3. m = (Number of data tables) - (Table position of data insertion)

Number of data tablesPresent value of , table position data insertion: n

220 ⎯

221 ⎯

222 ⎯

223 ⎯

224 LD= 1.22 1.48 1.22 1.48 For details, refer to Appendix B-6-2.

225 LD> 1.22 1.48 1.22 1.48 For details, refer to Appendix B-6-2.

226 LD< 1.22 1.48 1.22 1.48 For details, refer to Appendix B-6-2.

227 ⎯

228 LD 1.22 1.48 1.22 1.48 For details, refer to Appendix B-6-2.

229 LD

230 LD>= 1.22 1.48 1.22 1.48 For details, refer to Appendix B-6-2.

231 ⎯

232 AND= 1.22 1.48 1.22 1.48 For details, refer to Appendix B-6-2.

233 AND> 1.22 1.48 1.22 1.48 For details, refer to Appendix B-6-2.

234 AND< 1.22 1.48 1.22 1.48 For details, refer to Appendix B-6-2.

235 ⎯

236 AND 1.22 1.48 1.22 1.48 For details, refer to Appendix B-6-2.

Data comparison

Page 941 of the Mitsubishi Electronics MELSEC FX3S user manual — 270 IVCK 24.5 ⎯ 6.5 ⎯
Page 941 · click to enlarge
Page 941

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-4 Applied Instruction Execution Time

Execution time in ON status (µs) Execution time in OFF status (µs)

FNC277-FNC279 Data Transfer 3

No. Instruction

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

237 AND

238 AND>= 1.22 1.48 1.22 1.48 For details, refer to Appendix B-6-2.

FNC280-FNC289 High-Speed Processing 2

239 ⎯

240 OR= 1.22 1.48 1.22 1.48 For details, refer to Appendix B-6-2.

241 OR> 1.22 1.48 1.22 1.48 For details, refer to Appendix B-6-2.

242 OR< 1.22 1.48 1.22 1.48 For details, refer to Appendix B-6-2.

FNC290-FNC299 Extension File Register Control

243 ⎯

244 OR 1.22 1.48 1.22 1.48 For details, refer to Appendix B-6-2.

245 OR

246 OR>= 1.22 1.48 1.22 1.48 For details, refer to Appendix B-6-2.

FNC300-FNC305 FX 3U -CF-ADP

247 ⎯

248 ⎯

249 ⎯

250 ⎯

251 ⎯

252 ⎯

253 ⎯

254 ⎯

255 ⎯

256 LIMIT 8.1 8.6 0.585 1.105

257 BAND 8.1 8.6 0.585 1.105

258 ZONE 7.9 8.5 0.585 1.105

259 SCL 15.9 16.8 0.455 0.845

260 DABIN 13.7 19.5 0.325 0.585

261 BINDA 16.7 23.1 0.325 0.585

262 ⎯

263 ⎯

264 ⎯

265 ⎯

266 ⎯

267 ⎯

268 ⎯

269 SCL2 2.79 + 5.21n 29.06 + 7.94n 0.455 0.845 n: Number of data

270 IVCK 24.5 ⎯ 6.5 ⎯

271 IVDR 22.7 ⎯ 6.5 ⎯

A

272 IVRD 26.8 ⎯ 6.5 ⎯

273 IVWR 24.7 ⎯ 6.5 ⎯

274 IVBWR 31.0 ⎯ 6.5 ⎯

275 IVMC 29.6 ⎯ 6.5 ⎯

276 ADPRW 106.55 ⎯ 30.4 ⎯

B

Show 9 more labels / short text on this page
Data comparison · Data table processing · SFC•STL Programming · Interrupt Function · Special Device · Error Code · External device communication · Version Up Information · Execution Times
Page 942 of the Mitsubishi Electronics MELSEC FX3S user manual — 304 FLCMD 50.9 ⎯ 6.26 ⎯
Page 942 · click to enlarge
Page 942

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-4 Applied Instruction Execution Time

Execution time in ON status (µs) Execution time in OFF status (µs)

No. Instruction

Remarks 16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction

277 ⎯

278 RBFM*1 50+900n ⎯ 0.715 ⎯ n : Number of points transferred in

one operation cycle RBFM*2 244 + 103n ⎯ 0.715 ⎯

279 WBFM*1 24 + 966n ⎯ 0.715 ⎯ n : Number of points transferred in

one operation cycle WBFM*2 292 + 116n ⎯ 0.715 ⎯

*1. When the instruction is executed to a BFM in a special function unit/block for the FX0N/FX2N/FX2NC Series or in the CC-Link/LT built in the FX3UC-32MT-LT(-2)

*2. When the instruction is executed to a BFM in a special function unit/block for the FX3U/FX3UC Series

280 HSCT ⎯ 30.0 ⎯ 1.365

281 ⎯

282 ⎯

283 ⎯

284 ⎯

285 ⎯

286 ⎯

287 ⎯

288 ⎯

289 ⎯

Extension file register control

290 LOADR 13.2 + 0.44n ⎯ 0.325 ⎯

291 SAVER 166n ⎯ 6.4 ⎯

292 INITR 17600n ⎯ 0.325 ⎯

293 LOGR 244 + 17.9n ⎯ 0.715 ⎯

294 RWER 46700n ⎯ 0.325 ⎯ n : Number of write target

295 INITER 17300n ⎯ 0.325 ⎯

296 to 299 ⎯

FX 3U -CF-ADP

300 FLCRT 83.2 ⎯ 6.64 ⎯

301 FLDEL 49.1 ⎯ 6.32 ⎯

302 FLWR 77.9 + 2.9n ⎯ 6.26 ⎯ n : Number of written data

303 FLRD 59.2 + 4.25n ⎯ 6.18 ⎯ n : Number of read data

304 FLCMD 50.9 ⎯ 6.26 ⎯

305 FLSTRD 50.9 ⎯ 6.24 ⎯

*3. When 16-bit data is written or read.

Show 5 more labels / short text on this page
Data move 3 · High-speed processing 2 · sectors · points*3 · points*3
Page 943 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 943 · click to enlarge
Page 943

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-5 Execution Time of Pulse Generation Instruction P in Each Applied Instruction

Appendix B-5 Execution Time of Pulse Generation Instruction P in Each Applied

FNC277-FNC279 Data Transfer 3

Instruction

  • FX 3S PLC

Applied instruction Execution time Remarks

Execution time at rising edge of input: Execution time in ON status = 4.98 µs

FNC280-FNC289 High-Speed Processing 2

MOV instruction (FNC 12)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 7.81 µs

BCD instruction (FNC 18)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 7.77 µs

BIN instruction (FNC 19)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 6.37 µs

FNC290-FNC299 Extension File Register Control

ADD instruction (FNC 20)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 6.47 µs

SUB instruction (FNC 21)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 7.07 µs

MUL instruction (FNC 22)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 7.03 µs

FNC300-FNC305 FX 3U -CF-ADP

DIV instruction (FNC 23)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 3.48 µs

INC instruction (FNC 24)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 3.48 µs

DEC instruction (FNC 25)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 6.42 µs

WAND instruction (FNC 26)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 6.42 µs

WOR instruction (FNC 27)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 6.42 µs

WXOR instruction (FNC 28)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status + 0.68 µs

Non-execution timeExecution time in OFF status + 0.6 µ s

A

B

Show 7 more labels / short text on this page
SFC•STL Programming · Interrupt Function · Other applied instructions · Special Device · Error Code · Version Up Information · Execution Times
Page 944 of the Mitsubishi Electronics MELSEC FX3S user manual — Appendix B-5 Execution Time of Pulse Generation Instruction P in Each Applied Instruction
Page 944 · click to enlarge
Page 944

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-5 Execution Time of Pulse Generation Instruction P in Each Applied Instruction

  • FX 3G /FX 3GC PLCs (Standard mode)

Applied instruction Execution time Remarks

Execution time at rising edge of input: Execution time in ON status = 4.98 µs

MOV instruction (FNC 12)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 7.81 µs

BCD instruction (FNC 18)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 7.77 µs

BIN instruction (FNC 19)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 6.37 µs

ADD instruction (FNC 20)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 6.47 µs

SUB instruction (FNC 21)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 7.07 µs

MUL instruction (FNC 22)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 7.03 µs

DIV instruction (FNC 23)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 3.48 µs

INC instruction (FNC 24)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 3.48 µs

DEC instruction (FNC 25)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 6.42 µs

WAND instruction (FNC 26)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 6.42 µs

WOR instruction (FNC 27)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status = 6.42 µs

WXOR instruction (FNC 28)

Non-execution timeExecution time in OFF status = 1.44 µ s

Execution time at rising edge of input: Execution time in ON status + 0.68 µs

Non-execution timeExecution time in OFF status + 0.6 µ s

Other applied instructions

Page 945 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 945 · click to enlarge
Page 945

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-5 Execution Time of Pulse Generation Instruction P in Each Applied Instruction

  • FX 3G /FX 3GC PLCs (Extension mode)

FNC277-FNC279 Data Transfer 3

Applied instruction Execution time Remarks

Execution time at rising edge of input: Execution time in ON status = 5.43 µs

MOV instruction (FNC 12)

Non-execution timeExecution time in OFF status = 1.81 µ s

Execution time at rising edge of input: Execution time in ON status = 9.13 µs

BCD instruction (FNC 18)

Non-execution timeExecution time in OFF status = 1.81 µ s

FNC280-FNC289 High-Speed Processing 2

Execution time at rising edge of input: Execution time in ON status = 9.08 µs

BIN instruction (FNC 19)

Non-execution timeExecution time in OFF status = 1.81 µ s

Execution time at rising edge of input: Execution time in ON status = 6.68 µs

ADD instruction (FNC 20)

Non-execution timeExecution time in OFF status = 1.81 µ s

Execution time at rising edge of input: Execution time in ON status = 6.78 µs

SUB instruction (FNC 21)

Non-execution timeExecution time in OFF status = 1.81 µ s

FNC290-FNC299 Extension File Register Control

Execution time at rising edge of input: Execution time in ON status = 7.24 µs

MUL instruction (FNC 22)

Non-execution timeExecution time in OFF status = 1.81 µ s

Execution time at rising edge of input: Execution time in ON status = 7.44 µs

DIV instruction (FNC 23)

Non-execution timeExecution time in OFF status = 1.81 µ s

Execution time at rising edge of input: Execution time in ON status = 3.49 µs

INC instruction (FNC 24)

Non-execution timeExecution time in OFF status = 1.81 µ s

FNC300-FNC305 FX 3U -CF-ADP

Execution time at rising edge of input: Execution time in ON status = 3.49 µs

DEC instruction (FNC 25)

Non-execution timeExecution time in OFF status = 1.81 µ s

Execution time at rising edge of input: Execution time in ON status = 6.81 µs

WAND instruction (FNC 26)

Non-execution timeExecution time in OFF status = 1.81 µ s

Execution time at rising edge of input: Execution time in ON status = 6.81 µs

WOR instruction (FNC 27)

Non-execution timeExecution time in OFF status = 1.81 µ s

Execution time at rising edge of input: Execution time in ON status = 6.81 µs

WXOR instruction (FNC 28)

Non-execution timeExecution time in OFF status = 1.81 µ s

Execution time at rising edge of input: Execution time in ON status + 0.7 µs

Non-execution timeExecution time in OFF status + 0.6 µ s
  • FX 3U /FX 3UC PLCs

Applied instruction Execution time Remarks

Execution time at rising edge of input: Execution time in ON status 1.22 µs in MOVP instruction

MOV instruction (FNC 12)

Non-execution timeExecution time in OFF status

Execution time at rising edge of input: Execution time in ON status + 0.45 µs

Non-execution timeExecution time in OFF status + 0.45 µ s

A

B

Show 8 more labels / short text on this page
SFC•STL Programming · Other applied instructions · Interrupt Function · Other applied instructions · Special Device · Error Code · Version Up Information · Execution Times
Page 946 of the Mitsubishi Electronics MELSEC FX3S user manual — OFF
Page 946 · click to enlarge
Page 946

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-6 Execution Time on Combination of Applicable Devices and Indexing

Appendix B-6 Execution Time on Combination of Applicable Devices and

Indexing

In examples shown below for basic instructions, the MOV instruction and data comparison instructions, the instruction execution time varies depending on the combination of target devices and absence/presence of indexing. The combinations of target devices marked with "*1" and "*2" are handled as exceptions because high-speed processing is adopted in the technique.

Appendix B-6-1 Basic instruction (LD/LDI/AND/ANI/OR/ORI) execution time

  • FX 3U /FX 3UC PLCs

Specified device type Condition Instruction execution time (µs)

Bit device Without indexing 0.065

With indexing 11.9

Word device Bit specification 8.8

  • FX 3S /FX 3G /FX 3GC PLCs do not support indexing of bit devices and contact instructions with bit specification of word devices in basic instructions.

Appendix B-6-2 Applied instruction execution time

1. MOV (FNC 12) instruction execution time

  • FX 3S PLC - MOV instruction (16-bit operation)

D (destination) Without indexing (µs) With indexing (µs)

KnY,KnM,KnS*1 T,C,D KnY,KnM,KnS T,C,D

KnX,KnY,KnM,KnS*1 0.64 0.72 14.68 8.28

ON

T,C,D 0.88 0.84 13.08 6.68 K,H 0.48 0.52 12.28 5.78

OFF

0.36 0.58 T,C,D K,H

*1. When K4 is specified, and the head bit device number is a multiple of 8 (K4M0, K4M8 ...)

- DMOV instruction (32-bit instruction)

D (destination) Without indexing (µs) With indexing (µs)

KnY,KnM,KnS*1 T,C,D KnY,KnM,KnS T,C,D

KnX,KnY,KnM,KnS*1 0.68 0.88 19.48 8.68

ON

T,C,D 1.24 1.04 18.18 7.28 K,H 0.56 0.56 17.18 6.28

OFF

0.4 0.58 T,C,D K,H

*1. When K8 is specified, and the head bit device number is a multiple of 8 (K8M0, K8M8 ...)

Show 6 more labels / short text on this page
Command · contact S (source) · KnX,KnY,KnM,KnS*1 · Command · contact S (source) · KnX,KnY,KnM,KnS*1
Page 947 of the Mitsubishi Electronics MELSEC FX3S user manual — A
Page 947 · click to enlarge
Page 947

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-6 Execution Time on Combination of Applicable Devices and Indexing

  • FX 3G /FX 3GC PLCs - MOV instruction (16-bit operation)

FNC277-FNC279 Data Transfer 3

D (destination) Standard mode Extension mode Without indexing (µs) With indexing (µs) Without indexing (µs) With indexing (µs) KnY, KnM,

T,C,D,R

T,C,D,R

T,C,D,R

T,C,D,R

FNC280-FNC289 High-Speed Processing 2

KnX,KnY,KnM,KnS*1 0.64 0.72 14.68 8.28 1.56 1.8 16.42 9.92

ON

T,C,D,R 0.88 0.84 13.08 6.68 1.84 1.96 14.82 8.32 K,H 0.48 0.52 12.28 5.78 1.24 1.4 13.22 7.22

OFF

0.36 0.58 0.52 0.82 T,C,D,R K,H

FNC290-FNC299 Extension File Register Control

*1. When K4 is specified, and the head bit device number is a multiple of 8 (K4M0, K4M8 ...)

- DMOV instruction (32-bit instruction)

D (destination) Standard mode Extension mode Without indexing (µs) With indexing (µs) Without indexing (µs) With indexing (µs) KnY, KnM,

FNC300-FNC305 FX 3U -CF-ADP

T,C,D,R

T,C,D,R

T,C,D,R

T,C,D,R

KnX,KnY,KnM,KnS*1 0.68 0.88 19.48 8.68 1.6 2.12 21.32 10.32

ON

T,C,D,R 1.24 1.04 18.18 7.28 2.2 2.4 19.92 9.02 K,H 0.56 0.56 17.18 6.28 1.48 1.88 19.12 8.22

OFF

0.4 0.58 0.62 0.82 T,C,D,R K,H

*1. When K8 is specified, and the head bit device number is a multiple of 8 (K8M0, K8M8 ...)

  • FX 3U /FX 3UC PLCs - MOV instruction (16-bit operation)

D (destination) Without indexing (µs) With indexing (µs)

KnY,KnM,KnS T,C,D R U \G *3 KnY,KnM,KnS T,C,D R U \G *3

KnX,KnY,KnM,KnS 15.5 12.1 13.8 212.9 18.6 16.6 16.9 214.7

T,C,D 12.1 0.64*1 10.4 209.7 16.6 14.5 14.8 212.8

ON

R 13.8 10.4 12.1 211.3 16.9 14.8 15.1 213.1

U \G *3 131.8 128.5 130.2 377.9 133.1 129.9 131.5 379.4

K,H 12.5 0.64*1 10.8 210.1 15.4 13.3 13.6 211.6

T,C,D 0.32 *2

0.325 (0.325 in combinations other than *2.)

OFF

R

U \G *3

K,H 0.32 *2

*1. *2.These combinations are handled as exceptions because high-speed processing is adopted in the technique.

*3. When the instruction is executed for a BFM in a special function unit/block for FX3U/FX3UC Series.

A

B

Show 29 more labels / short text on this page
Command · contact S (source) · KnY, KnM, · KnY, KnM, · KnY, KnM, · KnS*1 · KnS*1 · KnS · KnS · KnX,KnY,KnM,KnS*1 · Command · contact S (source) · KnY, KnM, · KnY, KnM, · KnY, KnM, · KnS*1 · KnS*1 · KnS · KnS · KnX,KnY,KnM,KnS*1 · SFC•STL Programming · Interrupt Function · Command · contact S (source) · Special Device · KnX,KnY,KnM,KnS · Error Code · Version Up Information · Execution Times
Page 948 of the Mitsubishi Electronics MELSEC FX3S user manual — T,C,D 2.8 3 10.72 8.28
Page 948 · click to enlarge
Page 948

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-6 Execution Time on Combination of Applicable Devices and Indexing

- DMOV instruction (32-bit instruction)

D (destination) Without indexing (µs) With indexing (µs)

KnY,KnM,KnS T,C,D R U \G *3 KnY,KnM,KnS T,C,D R U \G *3

KnX,KnY,KnM,KnS 15.5 12.4 13.8 311.1 18.7 17.0 17.1 313.0

T,C,D 12.4 1.48*1 10.7 307.4 17.0 15.2 15.3 310.5

R 13.8 10.7 12.2 308.9 17.1 15.3 15.4 310.6

ON

U \G *3 199.8 195.9 197.4 542.6 201.2 197.3 198.8 544.0

K,H 13.0 1.48*1 11.4 308.0 16.2 14.4 14.5 309.7

T,C,D 1.48 *2

OFF

R

0.585 (0.585 in combinations other than *2.)

U \G *3

K,H 1.48 *2

*1. *2.These combinations are handled as exceptions because high-speed processing is adopted in the technique.

*3. When the instruction is executed for a BFM in a special function unit/block for FX3U/FX3UC Series.

2. Data comparison instruction execution time

  • FX 3S PLC - Data comparison instruction (16-bit operation)

Without indexing (µs) With indexing (µs)

KnY,KnM,KnS*1 T,C,D KnY,KnM,KnS T,C,D

KnX,KnY,KnM,KnS*1 2.12 2.2 11.28 9.18

T,C,D 2.24 2.36 9.78 7.58

K,H 1.4 1.52 8.88 6.78

*1. When K4 is specified, and the head bit device number is a multiple of 8 (K4M0, K4M8 ...)

- Data comparison instruction (32-bit operation)

Without indexing (µs) With indexing (µs)

KnY,KnM,KnS*1 T,C,D KnY,KnM,KnS T,C,D

KnX,KnY,KnM,KnS*1 2.52 2.76 11.68 9.68

T,C,D 2.8 3 10.72 8.28

K,H 1.4 1.76 9.28 7.28

*1. When K8 is specified, and the head bit device number is a multiple of 8 (K8M0, K8M8 ...)

Show 7 more labels / short text on this page
Command · contact S (source) · KnX,KnY,KnM,KnS · D (destination) · S (source) · D (destination) · S (source)
Page 949 of the Mitsubishi Electronics MELSEC FX3S user manual — B
Page 949 · click to enlarge
Page 949

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

B Instruction Execution Time

B-6 Execution Time on Combination of Applicable Devices and Indexing

  • FX 3G /FX 3GC PLCs - Data comparison instruction (16-bit operation)

FNC277-FNC279 Data Transfer 3

Standard mode Extension mode

Without indexing (µs) With indexing (µs) Without indexing (µs) With indexing (µs)

T,C,D,R

T,C,D,R

T,C,D,R

T,C,D,R

FNC280-FNC289 High-Speed Processing 2

KnX,KnY,KnM,KnS*1 2.12 2.2 11.28 9.18 3 3.12 13.12 10.7

T,C,D,R 2.24 2.36 9.78 7.58 3.16 3.24 11.52 9.32

K,H 1.4 1.52 8.88 6.78 2.12 2.24 10.32 8.12

*1. When K4 is specified, and the head bit device number is a multiple of 8 (K4M0, K4M8 ...)

- Data comparison instruction (32-bit operation)

FNC290-FNC299 Extension File Register Control

Standard mode Extension mode

Without indexing (µs) With indexing (µs) Without indexing (µs) With indexing (µs)

T,C,D,R

T,C,D,R

T,C,D,R

T,C,D,R

FNC300-FNC305 FX 3U -CF-ADP

KnX,KnY,KnM,KnS*1 2.52 2.76 11.68 9.68 3.48 3.68 13.32 11.32

T,C,D,R 2.8 3 10.72 8.28 3.72 3.92 11.92 9.92

K,H 1.4 1.76 9.28 7.28 2.36 2.68 11.12 9.12

*1. When K8 is specified, and the head bit device number is a multiple of 8 (K8M0, K8M8 ...)

  • FX 3U /FX 3UC PLCs - Data comparison instruction (16-bit operation)

Without indexing (µs) With indexing (µs)

KnS T,C,D R U \G *2 KnY,KnM,

KnS T,C,D R U \G *2

KnX,KnY,KnM,KnS 16.2 13.0 14.7 133.1 19.4 17.4 17.6 134.7

T,C,D 13.0 1.22*1 11.3 129.9 17.4 15.4 15.7 132.8

R 14.7 11.3 12.9 131.4 17.6 15.7 16.0 133.1

U \G *2 133.0 129.3 131.4 298.2 134.3 131.0 138.9 299.4

K,H 13.4 1.22*1 11.7 130.2 16.3 14.2 14.5 131.6

*1. These combinations are handled as exceptions because high-speed processing is adopted in the technique.

*2. When the instruction is executed for a BFM in a special extension unit/block for FX3U/FX3UC Series.

- Data comparison instruction (32-bit operation)

Without indexing (µs) With indexing (µs)

KnS T,C,D R U \G *2 KnY,KnM,

KnS T,C,D R U \G *2

KnX,KnY,KnM,KnS 16.4 13.2 14.7 201.1 19.6 17.9 18.0 202.7

T,C,D 13.2 1.48*1 11.6 197.1 17.9 16.1 16.2 200.3

R 14.7 11.6 13.0 198.6 18.0 16.2 16.3 200.4

U \G *2 201.0 197.1 198.6 432.4 202.4 198.5 200.0 433.8

A

K,H 13.9 1.48*1 12.3 197.8 17.1 15.3 15.4 199.4

*1. These combinations are handled as exceptions because high-speed processing is adopted in the technique.

*2. When the instruction is executed for a BFM in a special extension unit/block for FX3U/FX3UC Series.

B

Show 32 more labels / short text on this page
D (destination) · S (source) · KnY, KnM, · KnY, KnM, · KnY, KnM, · KnY, KnM, · KnS*1 · KnS · KnS · KnS · D (destination) · S (source) · KnY, KnM, · KnY, KnM, · KnY, KnM, · KnY, KnM, · KnS*1 · KnS · KnS · KnS · SFC•STL Programming · D (destination) · S (source) · KnY,KnM, · Interrupt Function · Special Device · D (destination) · S (source) · KnY,KnM, · Error Code · Version Up Information · Execution Times
Page 950 of the Mitsubishi Electronics MELSEC FX3S user manual — 1. Data move instructions
Page 950 · click to enlarge
Page 950

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

C Applied Instruction List [by Instruction Type/in Alphabetic Order]

C-1 Applied instructions [by instruction type]

Appendix C: Applied Instruction List

[by Instruction Type/in Alphabetic Order]

Appendix C-1 Applied instructions [by instruction type]

Applied instructions are classified into the following nineteen types:

Mitsubishi Electronics MELSEC FX3S — Appendix C: Applied Instruction List diagram (page 950)
Fig. 851 · Appendix C: Applied Instruction List

1 Data transfer instructions 11 Program flow control instructions

Mitsubishi Electronics MELSEC FX3S — Appendix C: Applied Instruction List diagram (page 950)
Fig. 852 · Appendix C: Applied Instruction List

3 Comparison instructions 13 Real time clock control instructions

4 Arithmetic operation instructions 14 Pulse output/positioning control instructions

6 Special function instructions 16 Special unit/block control instructions

7 Rotation instructions 17 Extension register/extension file register control instructions

1. Data move instructions

3. Comparison instructions

Mitsubishi Electronics MELSEC FX3S — 1. Data move instructions diagram (page 950)
Fig. 853 · 1. Data move instructions

BCD FNC 18 Conversion to Binary Coded Decimal 264

EBCD FNC118 Floating Point to Scientific Notation Conversion 502

EBIN FNC119 Scientific Notation to Floating Point Conversion 503

RAD FNC136 Floating Point Degrees to Radians Conversion 528

DEG FNC137 Floating Point Radians to Degrees Conversion 530

Page 951 of the Mitsubishi Electronics MELSEC FX3S user manual — Appendix C: Applied Instruction List [by Instruction Type/in Alphabetic Order]
Page 951 · click to enlarge
Page 951

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

C Applied Instruction List [by Instruction Type/in Alphabetic Order]

C-1 Applied instructions [by instruction type]

Mitsubishi Electronics MELSEC FX3S — Appendix C: Applied Instruction List [by Instruction Type/in Alphabetic Order] diagram (page 951)
Fig. 854 · Appendix C: Applied Instruction List [by Instruction…

HSCT FNC280 High-Speed Counter Compare With Data Table 709

POP FNC212 Shift Last Data Read [FILO Control] 645

Page 952 of the Mitsubishi Electronics MELSEC FX3S user manual — 11.Program flow control instructions
Page 952 · click to enlarge
Page 952

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

C Applied Instruction List [by Instruction Type/in Alphabetic Order]

C-1 Applied instructions [by instruction type]

9. Data operation instructions

11.Program flow control instructions

Mitsubishi Electronics MELSEC FX3S — 9. Data operation instructions diagram (page 952)
Fig. 855 · 9. Data operation instructions
Mitsubishi Electronics MELSEC FX3S — 9. Data operation instructions diagram (page 952)
Fig. 856 · 9. Data operation instructions

12.I/O refresh instructions

Mnemonic FNC No. Function Ref. Page

SCL2 FNC269 Scaling 2 (Coordinate by X/Y Data) 680

REF FNC 50 Refresh 339

REFF FNC 51 Refresh and Filter Adjust 343

13.Real time clock control instructions

Mitsubishi Electronics MELSEC FX3S — 13.Real time clock control instructions diagram (page 952)
Fig. 857 · 13.Real time clock control instructions

10.Character string operation instructions

Mitsubishi Electronics MELSEC FX3S — 10.Character string operation instructions diagram (page 952)
Fig. 858 · 10.Character string operation instructions

ESTR FNC116 Floating Point to Character String Conversion 491

EVAL FNC117 Character String to Floating Point Conversion 497

14.Pulse output/positioning control instructions

Mitsubishi Electronics MELSEC FX3S — 14.Pulse output/positioning control instructions diagram (page 952)
Fig. 859 · 14.Pulse output/positioning control instructions

RIGHT FNC204 Extracting Character String Data From the Right 626

LEFT FNC205 Extracting Character String Data from the Left 628

15.Serial communication instructions

Mitsubishi Electronics MELSEC FX3S — 15.Serial communication instructions diagram (page 952)
Fig. 860 · 15.Serial communication instructions

11.Program flow control instructions

Mitsubishi Electronics MELSEC FX3S — 11.Program flow control instructions diagram (page 952)
Fig. 861 · 11.Program flow control instructions
Page 953 of the Mitsubishi Electronics MELSEC FX3S user manual — Appendix C: Applied Instruction List [by Instruction Type/in Alphabetic Order]
Page 953 · click to enlarge
Page 953

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

C Applied Instruction List [by Instruction Type/in Alphabetic Order]

C-1 Applied instructions [by instruction type]

Mitsubishi Electronics MELSEC FX3S — Appendix C: Applied Instruction List [by Instruction Type/in Alphabetic Order] diagram (page 953)
Fig. 862 · Appendix C: Applied Instruction List [by Instruction…

FROM FNC 78 Read From a Special Function Block 448

TO FNC 79 Write To a Special Function Block 453

FLDEL FNC301 File delete / CF card format 744

Page 954 of the Mitsubishi Electronics MELSEC FX3S user manual — Appendix C-2 Applied instructions [in alphabetical order]
Page 954 · click to enlarge
Page 954

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

C Applied Instruction List [by Instruction Type/in Alphabetic Order]

C-2 Applied instructions [in alphabetical order]

Appendix C-2 Applied instructions [in alphabetical order]

Mitsubishi Electronics MELSEC FX3S — Appendix C-2 Applied instructions [in alphabetical order] diagram (page 954)
Fig. 863 · Appendix C-2 Applied instructions [in alphabetical o…

DEG FNC137 Floating Point Radians to Degrees Conversion 530

EBCD FNC118 Floating Point to Scientific Notation Conversion 502

BCD FNC 18 Conversion to Binary Coded Decimal 264

EBIN FNC119 Scientific Notation to Floating Point Conversion 503

ESTR FNC116 Floating Point to Character String Conversion 491

EVAL FNC117 Character String to Floating Point Conversion 497

Page 955 of the Mitsubishi Electronics MELSEC FX3S user manual — Appendix C-2 Applied instructions [in alphabetical order]
Page 955 · click to enlarge
Page 955

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

C Applied Instruction List [by Instruction Type/in Alphabetic Order]

C-2 Applied instructions [in alphabetical order]

Mitsubishi Electronics MELSEC FX3S — Appendix C-2 Applied instructions [in alphabetical order] diagram (page 955)
Fig. 864 · Appendix C-2 Applied instructions [in alphabetical o…

FLDEL FNC301 File delete / CF card format 744

LEFT FNC205 Extracting Character String Data from the Left 628

FROM FNC 78 Read From a Special Function Block 448

HSCT FNC280 High-Speed Counter Compare With Data Table 709

Page 956 of the Mitsubishi Electronics MELSEC FX3S user manual — Appendix C-2 Applied instructions [in alphabetical order]
Page 956 · click to enlarge
Page 956

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

C Applied Instruction List [by Instruction Type/in Alphabetic Order]

C-2 Applied instructions [in alphabetical order]

Mitsubishi Electronics MELSEC FX3S — Appendix C-2 Applied instructions [in alphabetical order] diagram (page 956)
Fig. 865 · Appendix C-2 Applied instructions [in alphabetical o…
Mitsubishi Electronics MELSEC FX3S — Appendix C-2 Applied instructions [in alphabetical order] diagram (page 956)
Fig. 866 · Appendix C-2 Applied instructions [in alphabetical o…

POP FNC212 Shift Last Data Read [FILO Control] 645

RAD FNC136 Floating Point Degrees to Radians Conversion 528

TO FNC 79 Write To a Special Function Block 453

RIGHT FNC204 Extracting Character String Data From the Right 626

SCL2 FNC269 Scaling 2 (Coordinate by X/Y Data) 680

Page 957 of the Mitsubishi Electronics MELSEC FX3S user manual — Appendix D: Discontinued models
Page 957 · click to enlarge
Page 957

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

Appendix D: Discontinued models

The table below shows discontinued models of MELSEC-F Series PLCs and programming tools described in this manual.

Discontinued model Production stop date Repair acceptance period

FX3U-232ADP September 30, 2013 Until September 30, 2020

FX3U-485ADP September 30, 2013 Until September 30, 2020

FX-PCS/WIN(-E) March 31, 2013 -

FX-20P(-E) December 31, 2012 Until December 31, 2019

FX-10DU(-E) December 31, 2012 Until December 31, 2019

FX2N September 30, 2012 Until September 30, 2019

FX2NC September 30, 2012 Until September 30, 2019

FX-10P(-E) June 30, 2008 Until June 30, 2015

FX-20DU June 30, 2008 Until June 30, 2015

FX-232AW September 30, 2004 Until September 30, 2011

FX-232AWC June 30, 2004 Until June 30, 2011

FX-25DU-E September 30, 2002 Until September 30, 2009

D Discontinued models · Applicable Instruction List · Discontinued models

Page 958 of the Mitsubishi Electronics MELSEC FX3S user manual — MEMO
Page 958 · click to enlarge
Page 958

FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

MEMO

D Discontinued models

Page 959 of the Mitsubishi Electronics MELSEC FX3S user manual — 6. Product application
Page 959 · click to enlarge
Page 959

Warranty FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

Warranty

Please confirm the following product warranty details before using this product. 1. Gratis Warranty Term and Gratis Warranty Range

2. Onerous repair term after discontinuation of production

If any faults or defects (hereinafter "Failure") found to be the responsibility of Mitsubishi occurs during use of the product within the gratis warranty term, the product shall be repaired at no cost via the sales representative or Mitsubishi Service Company. However, if repairs are required onsite at domestic or overseas location, expenses to send an engineer will be solely at the customer's discretion. Mitsubishi shall not be held responsible for any re-commissioning, maintenance, or testing on-site that involves replacement of the failed module.

Mitsubishi shall accept onerous product repairs for seven (7) years after production of the product is discontinued. Discontinuation of production shall be notified with Mitsubishi Technical Bulletins, etc.

Product supply (including repair parts) is not available after production is discontinued. 2)

3. Overseas service

Overseas, repairs shall be accepted by Mitsubishi's local overseas FA Center. Note that the repair conditions at each FA Center may differ. The gratis warranty term of the product shall be for one year after the date of purchase or delivery to a designated place. Note that after manufacture and shipment from Mitsubishi, the maximum distribution period shall be six (6) months, and the longest gratis warranty term after manufacturing shall be eighteen (18) months. The gratis warranty term of repair parts shall not exceed the gratis warranty term before repairs. [Gratis Warranty Range]

[Gratis Warranty Term]

4. Exclusion of loss in opportunity and secondary loss from warranty liability

Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation of damages caused by any cause found not to be the responsibility of Mitsubishi, loss in opportunity, lost profits incurred to the user or third person by Failures of Mitsubishi products, special damages and secondary damages whether foreseeable or not, compensation for accidents, and compensation for damages to products other than Mitsubishi products, replacement by the user, maintenance of on-site equipment, start-up test run and other tasks.

The range shall be limited to normal use within the usage state, usage methods and usage environment, etc., which follow the conditions and precautions, etc., given in the instruction manual, user's manual and caution labels on the product.

5. Changes in product specifications

Even within the gratis warranty term, repairs shall be charged for in the following cases. 2)

The specifications given in the catalogs, manuals or technical documents are subject to change without prior notice.

Failure occurring from inappropriate storage or handling, carelessness or negligence by the user. Failure caused by the user's hardware or software design.

6. Product application

In using the Mitsubishi MELSEC programmable logic controller, the usage conditions shall be that the application will not lead to a major accident even if any problem or fault should occur in the programmable logic controller device, and that backup and fail-safe functions are systematically provided outside of the device for any problem or fault.

Failure caused by unapproved modifications, etc., to the product by the user. b)

When the Mitsubishi product is assembled into a user's device, Failure that could have been avoided if functions or structures, judged as necessary in the legal safety measures the user's device is subject to or as necessary by industry standards, had been provided.

The Mitsubishi programmable logic controller has been designed and manufactured for applications in general industries, etc. Thus, applications in which the public could be affected such as in nuclear power plants and other power plants operated by respective power companies, and applications in which a special quality assurance system is required, such as for Railway companies or Public service purposes shall be excluded from the programmable logic controller applications. In addition, applications in which human life or property that could be greatly affected, such as in aircraft, medical applications, incineration and fuel devices, manned transportation, equipment for recreation and amusement, and safety devices, shall also be excluded from the programmable logic controller range of applications. However, in certain cases, some applications may be possible, providing the user consults their local Mitsubishi representative outlining the special requirements of the project, and providing that all parties concerned agree to the special circumstances, solely at the users discretion.

Failure that could have been avoided if consumable parts (battery, backlight, fuse, etc.) designated in the instruction manual had been correctly serviced or replaced.

Relay failure or output contact failure caused by usage beyond the specified Life of contact (cycles).

Failure caused by external irresistible forces such as fires or abnormal voltages, and failure caused by force majeure such as earthquakes, lightning, wind and water damage.

Failure caused by reasons unpredictable by scientific technology standards at time of shipment from Mitsubishi.

Any other failure found not to be the responsibility of Mitsubishi or that admitted not to be so by the user.

Show 10 more labels / short text on this page
1) · 1) · a) · 1) · c) · 2) · e) · f) · g) · h)
Page 960 of the Mitsubishi Electronics MELSEC FX3S user manual — 7.15 END
Page 960 · click to enlarge
Page 960

Revised History FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

Revised History

Date Created Revision Description

7/2005 A First Edition

  • 2/2006 B FX 3U and FX 3UC series version 2.30 compatible
  • Two instructions are added. - MEP, MEF [Section 3.1, Chapter 7, Appendix A-1-2, Appendix 8-1]
  • Functions of instructions are added - MUL (FNC 22) [Section 6.5.2, Section 10.3, Section 36.1.1] - DIV (FNC 23) [Section 6.5.2, Section 10.4, Section 36.1.1] - RS2 (FNC 87) [Section 36.1.1]
  • Example of index modification for instructions having limitation on number of executions [Section 5.7.3]
  • Other - Configuration

Revision A Revision B

7.11 PLS, PLF 7.11 MEP, MEF

7.12 SET, RST 7.12 PLS, PLF

7.13 NOP 7.13 SET, RST

7.14 END 7.14 NOP

7.15 Number of Instruction Steps and Specified Devices

7.15 END

- 7.16 Number of Instruction Steps and Specified Devices

Appendix A-2 Version Upgrade History Appendix A-2 Peripheral

Products applicability (except programming tools)

Appendix A-2-1 Version check method Appendix A-2-1 Applicable products

Appendix A-2-2 How to look at

- Appendix A-3 Version Upgrade History

- Appendix A-3-1 Version check method

Appendix A-3-2 How to look at

- Appendix A-3-3 Version Upgrade history [FX3U]

- Appendix A-3-4 Version Upgrade history [FX3UC]

- FX3U transistor output compatibility (change the [illegible] from FX3UC to

FX3U)[Section 13.3, Item 13.3.1, Section 13.8, Section 13.9, Section 13.10, Section 15.2, Section 15.3, Section 15.5]

  • 3/2007 C
  • The FX 3U -4AD, FX 3U -4DA and FX 3U -20SSC-H are added in the related manual introduction section.
  • Note on battery voltage drop is added [Subsection 2.6.2].
  • The expression of battery maintenance is modified [Subsection 2.6.3].
  • The contents of latched type device initialization methods are modified and added [Subsection 2.6.5].
  • Caution on using header and terminator in RS2 instruction is added [Section 16.6].
  • Note on setting the clock data from the FX-10DU-E/20DU-E/25DU-E is added [Section 21.8 and Subsection 36.2.7].
Show 5 more labels / short text on this page
and versions · Appendix A-2-2 Incompatible · manufacturer's serial number · peripheral products · manufacturer's serial number
Page 961 of the Mitsubishi Electronics MELSEC FX3S user manual — Date Created Revision Description
Page 961 · click to enlarge
Page 961

Revised History FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

Date Created Revision Description

  • 3/2007 C
  • Caution on storing sign data of character string is added [Section 26.2].
  • The sentence describing rough guide to the watchdog timer set value is modified [Sections 33.3 and 33.6].
  • Note on using state relays (S) in contact instructions is added [Subsections 34.1.2 and 34.2.2].
  • Note on state relays (S) in interrupt programs is added [Subsections 34.1.7, 34.2.5 and 35.2.3].
  • Errors are corrected.
  • 11/2007 D
  • FX 3UC (D, DSS) Series PLC was added.
  • FX 3U -232ADP-MB, FX 3U -485ADP-MB was added.
  • Timing chart was added [Subsections 4.7.11, 35.3.2].
  • Errors are corrected.
  • 11/2008 E
  • FX 3G Series PLC was added.
  • FX 3UC -32MT-LT-2 PLC was added.
  • Note is added for the allowable number of times of writing to the memory. [Section 4.9, 4.10, 9.6 and Chapter 33]
  • 15 instructions are added: FLT(FNC49), VRRD(FNC85), VRSC(FNC86), ECMP(FNC110), EMOV(FNC112), EADD(FNC120), ESUB(FNC121), EMUL(FNC122), EDIV(FNC123), ESQR(FNC127), INT(FNC129), IVCK(FNC270), IVDR(FNC271), IVRD(FNC272), IVWR(FNC273)
  • Supports connection of FX 3G -8AV-BD, FX 3G -2AD-BD, and FX 3G -1DA-BD. [Section 16.6, 16.7 and Chapter 36]
  • Supports connection of display module (FX 3G -5DM). [Chapter 2, Chapter 36 and Chapter 37]
  • Supports the floating point operation function. [Chapter 12 and Chapter 18]
  • Supports the inverter communication function. [Chapter 30]
  • Supports the pulse width/pulse period measurement function. [Section 35.8]
  • Instruction Execution Time was added (FX 3G )
  • 6/2009 F
  • 6 instructions are added: FLCRT(FNC300), FLDEL(FNC301), FLWR(FNC302), FLRD(FNC303), FLCMD(FNC304), FLSTRD(FNC305) [Chapter 34]
  • Supports connection of FX 3U -CF-ADP. [Chapter 34, Section 37.1 and Appendix B-4,C]
  • Supports connection of FX 3U -3A-ADP. [Section 37.2]
  • FX-30P was added. [Chapter 2 and Appendix A-1-1]
  • Explanation corrections for manufacturer’s serial number.
  • Errors are corrected.
  • 11/2009 G
  • The baud rate "38400 bps" is supported in the RS and RS2 instructions, inverter communication and computer link.
  • Customer keyword / permanent PLC lock is supported.
  • Errors are corrected.
  • 8/2010 H
  • FX 3U and FX 3UC series version 2.70 compatible - 3 instructions are added. VRRD(FNC85) , VRSC(FNC86) , IVMC(FNC275)[Section 16.6, 16.7 and Section 30.6]
  • Supports connection of the FX 3U -8AV-BD. [Section 16.6 and Section 16.7]
  • Note is added for FX 3U Series PLC AC input type and triac output type.
  • GX Works2 is added.
  • Explanation corrections for manufacturer's serial number and lot number. [Appendix A-3-1]
  • Errors are corrected.
Page 962 of the Mitsubishi Electronics MELSEC FX3S user manual — Date Created Revision Description
Page 962 · click to enlarge
Page 962

Revised History FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied Instruction Edition

Date Created Revision Description

  • 7/2011 J
  • Supported in FX 3G series version 1.40 - 1 instruction added. IVMC(FNC275)[Section 30.6]
  • Supported in FX 3U and FX 3UC series version 3.00 - Supports storage of symbolic information. - Support of the setting "Read-protect the execution program" for block passwords. - Special block error condition (D8166) is added. - Supports connection of FX 3U -FLROM-1M.
  • Errors are corrected.
  • 2/2012 K
  • FX 3GC Series PLC was added.
  • Supported in FX 3U and FX 3UC Series version 3.10 - Special parameter error (M8489 and D8489) is added. - The error code for parameter error is added. - The error code for special block error is added.
  • Errors are corrected.
  • 5/2012 L
  • Supported in FX 3G and FX 3GC Series version 2.00
  • Errors are corrected.
  • 5/2013 M
  • FX 3S Series PLC was added.
  • Supported in FX 3G and FX 3GC Series version 2.10 - The IP address change function for the FX 3U -ENET-ADP is added. [Appendix A]
  • 1 instruction added. ADPRW(FNC276)[Section 30.7]
  • Supports connection of FX 3U -ENET-ADP. [Section 37.1]
  • Description of the programming tool is changed accompanied by change of the programming tool from GX Developer to GX Works2.
  • Discontinued models are added. [Appendix D]
  • Errors are corrected.
  • 9/2013 N
  • Supported in FX 3S series version 1.10
  • Supported in FX 3G series version 2.20
  • FX 3S -30M /E -2AD PLC was added.
  • Supports connection of FX 3G -4EX-BD, FX 3G -2EYT-BD and FX 3G -485-BD-RJ.
  • Discontinued models are added. [Appendix D]
  • Errors are corrected.
Page 963 of the Mitsubishi Electronics MELSEC FX3S user manual — Revised History
Page 963 · click to enlarge
Page 963
Page 963 of the Mitsubishi Electronics MELSEC FX3S user manual — Revised History
Page 964 of the Mitsubishi Electronics MELSEC FX3S user manual — JY997D16601N (MEE)
Page 964 · click to enlarge
Page 964

FX3S/FX3G/FX3GC/FX3U/FX3UC SERIES PROGRAMMABLE CONTROLLERS

PROGRAMMING MANUAL

Basic & Applied Instruction Edition

HEAD OFFICE: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN HIMEJI WORKS: 840, CHIYODA CHO, HIMEJI, JAPAN

MODEL FX-P3-E

MODEL CODE 09R517

JY997D16601N (MEE)

Effective Sep. 2013 Specifications are subject to change without notice.

Display codes

Error codes

What the fault codes shown on the display mean and how to clear them.

CodeMeaningFix
X005or 50 µs (X006 and X007). p.130
X007Every time X007 is set to ON, an operation state p.335
S1This function is supported only in FX3G/FX3GC/FX3U/FX3UC PLCs. p.468
S2This function is supported only in FX3U/FX3UC PLCs. p.468
K0None (NULL) p.745
K1yyyy/mm/dd hh:mm:ss p.745
K3dd/mm/yyyy hh:mm:ss p.745
K4dd/mm/yy hh:mm:ss p.745
K5mm/dd/yyyy hh:mm:ss p.745
K6mm/dd/yy hh:mm:ss p.745
K7hh:mm:ss p.745
K-1Forcibly writes all buffered data to the CompactFlashTM card. p.754
B0The CompactFlashTM card is not mounted. p.757
B1The CompactFlashTM card is full. p.757
B2An error has occurred in the CF-ADP. p.757
B3CF-ADP H/W error p.757
Y003Green Y002: Yellow Y001: Red p.785
[D]8060[D]8060 p.847
[D]8061[D]8061 p.847
[D]8062[D]8062 p.847
[D]8063*5[D]8063*5 p.847
[D]8064[D]8064 p.847
[D]8065[D]8065 p.847
[D]8066[D]8066 p.847
[D]8067*6[D]8067*6 p.847
D 8068D 8068 p.847
[D]8069*6[D]8069*6 p.847
[D]8438*4[D]8438*4 p.864
[D]8439[D]8439 p.864
[D]8449[D]8449 p.864
0000No error p.895
3801Parity, overrun or framing error• Ethernet communication, inverter communication, computer link and programming: Ensure the parameters are correctly set according to their applications. • N:N network, parallel link, MODBUS communication, etc.: Check programs according to applications. • Remote maintenance: Ensure modem power is ON and check the settings of the AT commands. • Wiring: Check the communication cables for correct wiring. p.895
3802Communication character error p.895
3803Communication data sum check error p.895
3804Communication data format error p.895
3805Command error p.895
3806Communication time-out detected p.895
3807Modem initialization error p.895
3808N:N network parameter error p.895
3809N:N Network setting error p.895
3812Parallel link character error p.895
3813Parallel link sum error p.895
3814Parallel link format error p.895
3820Inverter communication error p.895
3821MODBUS communication error p.895
3830Memory access errorWhen the memory cassette is used, check whether it is mounted correctly. If the problem persists or if the memory cassette is not used, something may be malfunctioning inside the PLC. Consult your local Mitsubishi Electric representative. p.895
3840Special adapter connection errorCheck connection of the special adapter. p.895
6101Memory access errorWhen the memory cassette is used, check whether it is mounted correctly. If the problem persists or if the memory cassette is not used, something may be malfunctioning inside the PLC. Consult your local Mitsubishi Electric representative. p.895
6102Operation circuit errorIsolate the PLC and supply power to it using a different power supply. If the ERROR(ERR) LED turns OFF, noise may be affecting the PLC. Take the following measures. - Check the ground wiring, and reexamine the wiring route and installation location. - Fit a noise filter onto the power supply line. If the ERROR(ERR) LED does not turn OFF even after the above actions are taken, consult your local Mitsubishi Electric representative. p.895
6103I/O bus error (M8069 = ON)Verify that extension cables are correctly connected. p.896
6104Powered extension unit 24 V failure (M8069 = ON) p.896
6105Watchdog timer errorConfirm user program. The scan time exceeds the value stored in D8000. p.896
6106I/O table creation error (CPU error)• When turning the power ON to the main unit, a 24V power failure occurs in a powered extension unit. (The error occurs if the 24V power is not supplied for 10 seconds or more after main power turns ON.) • When turning main power ON, I/O assignment to CC- Link/LT (built into the FX3UC-32MT-LT(-2) PLC) is disabled. p.896
6107System configuration errorCheck the number of connected special function units/ blocks. Some special function units/blocks have a connection number limit. p.896
6112Changed settings for the built-in CC-Link/LT special function block cannot be written to the attached flash memory cassette.Verify that the memory cassette is installed correctly. p.896
6113Changed settings for the built-in CC-Link/LT special function block cannot be written to the attached write- protected flash memory cassette.Set the protect switch to OFF. p.896
6114CC-Link/LT settings cannot be written to the built-in CC- Link/LT special function block.Set the configuration again. If the problem persists, something may be malfunctioning inside the PLC. Consult your local Mitsubishi Electric representative. p.896
6115A built-in CC-Link/LT special function block EEPROM writing time-out error occurred, or the built-in CC-Link/LT special function block configuration could not be completed normally in self CONFIG mode. p.896
6201Parity, overrun or framing errorConfirm the cable connection between the programming panel (PP)/programming device and the PLC. This error may occur when a cable is disconnected and reconnected during PLC monitoring. p.896
6202Communication character error p.896
6203Communication data sum check error p.896
6204Data format error p.896
6205Command error p.896
6230Memory access errorWhen the memory cassette is used, check whether it is mounted correctly. If the problem persists or if the memory cassette is not used, something may be malfunctioning inside the PLC. Consult your local Mitsubishi Electric representative. p.896
6301Parity, overrun or framing error• Ethernet communication, inverter communication, computer link and programming: Ensure the parameters are correctly set according to their applications. • N:N network, parallel link, MODBUS communication, etc.: Check programs according to applications. • Remote maintenance: Ensure modem power is ON and check the settings of the AT commands. • Wiring: Check the communication cables for correct wiring. p.897
6302Communication character error p.897
6303Communication data sum check error p.897
6304Communication data format error p.897
6305Command error p.897
6306Communication time-out detected p.897
6307Modem initialization error p.897
6308N:N network parameter error p.897
6309N:N Network setting error p.897
6312Parallel link character error p.897
6313Parallel link sum error p.897
6314Parallel link format error p.897
6320Inverter communication error p.897
6321MODBUS communication error p.897
6330Memory access errorWhen the memory cassette is used, check whether it is mounted correctly. If the problem persists or if the memory cassette is not used, something may be malfunctioning inside the PLC. Consult your local Mitsubishi Electric representative. p.897
6340Special adapter connection errorCheck connection of the special adapter. p.897
6401Program sum check error• STOP the PLC, and correctly set the parameters. • Check that the following functions are not used with an unsupported PLC version when a memory cassette is attached: - Permanent PLC lock (supported in FX3U/FX3UC PLCs Ver. 2.61 or later) - Read-protect the execution program for block passwords (supported in FX3U/FX3UC PLCs Ver. 3.00 or later) - FX3U-FLROM-1M (supported in FX3U/FX3UC PLCs Ver. 3.00 or later) p.897
6402Memory capacity setting error p.897
6403Latched device area setting error p.897
6404Comment area setting error p.897
6405File register area setting error p.897
6406Special unit (BFM) initial value setting, positioning instruction setting sum check error p.897
6407Special unit (BFM) initial value setting, positioning instruction setting error p.897
6409Other setting error p.897
6411Built-in CC-Link/LT special function block invalid parameter settings (LT-2 dedicated area).• STOP the PLC, and correctly set the parameters. • Set parameters correctly, turn OFF the power, and then turn ON the power. p.897
6412Built-in CC-Link/LT special function block parameter settings sum check error (special function settings area). p.897
6413Built-in CC-Link/LT special function block parameter settings sum check error (LT-2 dedicated area). p.897
6420Special parameter sum check error• STOP the PLC, and correctly set the parameters. • Set special parameters correctly, turn OFF the power, and then turn ON the power. p.897
6421Special parameters setting error• Check the contents of the special parameter error code (D8489), confirm troubleshooting for special adapters/special blocks, and set special parameters correctly. • Set special parameters correctly, turn OFF the power, and then turn ON the power. p.897
6501Incorrect combination of instruction, device symbol and device numberDuring programming, each instruction is checked. If a syntax error is detected, modify the instruction correctly. p.898
6502No OUT T or OUT C before setting value p.898
6503• No setting value after OUT T or OUT C • Insufficient number of operands for an applied instruction p.898
6504• Same label number is used more than once. • Same interrupt input or high-speed counter input is used more than once. p.898
6505Device number is out of allowable range. p.898
6506Invalid instruction p.898
6507Invalid label number [P] p.898
6508Invalid interrupt input [I] p.898
6509Other error p.898
6510MC nesting number error p.898
6610LD, LDI is continuously used 9 times or more.This error occurs when a combination of instructions is incorrect in the entire circuit block or when the relationship between a pair of instructions is incorrect. Modify the instructions in the program mode so that their mutual relationship becomes correct. p.898
6611More ANB/ORB instructions than LD/LDI instructions p.898
6612Less ANB/ORB instructions than LD/LDI instructions p.898
6613MPS is continuously used 12 times or more. p.898
6614No MPS instruction p.898
6615No MPP instruction p.898
6616No coil between MPS, MRD and MPP, or incorrect combination p.898
6617Instruction below is not connected to bus line: STL, RET, MCR, P, I, DI, EI, FOR, NEXT, SRET, IRET, FEND or END p.898
6618STL, MC or MCR can only be used in main program, but it is used elsewhere (e.g. in interrupt routine or subroutine). p.898
6619Invalid instruction is used in FOR-NEXT loop: STL, RET, MC, MCR, I (interrupt pointer) or IRET. p.898
6620FOR-NEXT instruction nesting level exceeded p.898
6621Numbers of FOR and NEXT instructions do not match. p.898
6622No NEXT instruction p.898
6623No MC instruction p.898
6624No MCR instruction p.898
6625STL instruction is continuously used 9 times or more. p.898
6626Invalid instruction is programmed within STL-RET loop: MC, MCR, I (interrupt pointer), SRET or IRET. p.898
6627No STL instruction p.898
6628Invalid instruction is used in main program: I (interrupt pointer), SRET or IRET p.898
6629No P or I (interrupt pointer) p.898
6630No SRET or IRET instruction STL-RET / MC-MCR instructions programmed in the subroutine. p.898
6631SRET programmed in invalid location p.898
6632FEND programmed in invalid location p.898
6701• No jump destination (pointer) for CJ or CALL instruction • Label is undefined or out of P0 to P4095 due to indexing • Label P63 is executed in CALL instruction; cannot be used in CALL instruction as P63 is for jumping to END instruction.This error occurs in the execution of operation. Review the program and check the contents of the operands used in applied instructions. Even if the syntax or circuit design is correct, an operation error may still occur. For example: "T500Z" itself is not an error. But if Z had a value of 100, the timer T600 would be attempted to be accessed. This would cause an operation error since there is no T600 device available. p.899
6702CALL instruction nesting level is 6 or more p.899
6703Interrupt nesting level is 3 or more p.899
6704FOR-NEXT instruction nesting level is 6 or more. p.899
6705Operand of applied instruction is inapplicable device. p.899
6706Device number range or data value for operand of applied instruction exceeds limit. p.899
6707File register is accessed without parameter setting of file register. p.899
6708FROM/TO instruction errorThis error occurs in the execution of operation. • Review the program and check the contents of the operands used in applied instructions. • Verify that the specified buffer memories exist in the counterpart equipment. • Verify that extension cables are correctly connected. p.899
6709Other (e.g. improper branching)This error occurs in the execution of operation. Review the program and check the contents of the operands used in applied instructions. Even if the syntax or circuit design is correct, an operation error may still occur. For example: "T500Z" itself is not an error. But if Z had a value of 100, the timer T600 would be attempted to be accessed. This would cause an operation error since there is no T600 device available. p.899
6710Mismatch among parametersThis error occurs when the same device is used within the source and destination in a shift instruction, etc. p.899
6730Incorrect sampling time (TS) (TS ≤ 0)<PID instruction is stopped.> This error occurs in the parameter setting value or operation data executing PID instruction. Check the contents of the parameters. p.899
6732Incompatible input filter constant (α) (α < 0 or 100 ≤ α) p.899
6733Incompatible proportional gain (KP) (KP < 0) p.899
6734Incompatible integral time (TI) (TI < 0) p.899
6735Incompatible derivative gain (KD) (KD < 0 or 201 ≤ KD) p.899
6736Incompatible derivative time (TD) (TD < 0) p.899
6740Sampling time (TS) ≤ Scan time<Auto tuning is continued.> The operation is continued in the condition "sampling time (TS) = cyclic time (scan time)". p.899
6742Variation of measured value exceeds limit. (UPV < −32768 or +32767 < UPV)<PID operation is continued.> The operation is continued with each parameter set to the maximum and minimum value. p.899
6743Deviation exceeds limit. (EV < −32768 or +32767 < EV) p.899
6744Integral result exceeds limit. (Outside range from −32768 to +32767) p.899
6745Derivative value exceeds limit due to derivative gain (KD). p.899
6746Derivative result exceeds limit. (Outside range from −32768 to +32767) p.899
6747PID operation result exceeds limit. (Outside range from −32768 to +32767) p.899
6748PID output upper limit set value < PID output lower limit set value.<Transpose of output upper limit value and output lower limit value. → PID operation is continued.> Verify that the target setting contents are correct. p.900
6749Abnormal PID input variation alarm set value or output variation alarm set value (Set value < 0)<Alarm output is not given. → PID operation is continued.> Verify that the target setting contents are correct. p.900
6750<Step response method> Improper auto tuning result<Auto tuning is finished. → PID operation is started.> • The deviation at start of auto tuning is 150 or less. • The deviation at end of auto tuning is 1/3 or more of the deviation at start of auto tuning. Check the measured value and target value, and then execute auto tuning again. p.900
6751<Step response method> Auto tuning operation direction mismatch<Auto tuning is forcibly finished. → PID operation is not started.> The operation direction estimated from the measured value at the start of auto tuning was different from the actual operation direction of the output during auto tuning. Correct the relationship among the target value, output value for auto tuning, and the measured value, and then execute auto tuning again. p.900
6752<Step response method> Improper auto tuning operation<Auto tuning is finished. → PID operation is not started.> Because the set value was fluctuated during auto tuning, auto tuning was not executed correctly. Set the sampling time to a value larger than the output change cycle, or set a larger value for the input filter constant. After changing the setting, execute auto tuning again. p.900
6753<Limit cycle method> Abnormal output set value for auto tuning [ULV (upper limit) ≤ LLV (lower limit)]<Auto tuning is forcibly finished. → PID operation is not started.> Verify that the target setting contents are correct. p.900
6754<Limit cycle method> Abnormal PV threshold (hysteresis) set value for auto tuning (SHPV < 0) p.900
6755<Limit cycle method> Abnormal auto tuning transfer status (Data of device controlling transfer status is abnormally overwritten.)<Auto tuning is forcibly finished. → PID operation is not started.> Ensure that devices occupied by PID instruction are not overwritten in the program. p.900
6756<Limit cycle method> Abnormal result due to excessive auto tuning measurement time (τon > τ, τon < 0, τ < 0)<Auto tuning is forcibly finished. → PID operation is not started.> The auto tuning time is longer than necessary. Increase the difference (ULV - LLV) between the upper limit and lower limit of the output value for auto tuning, set a smaller value to the input filter constant (α), or set a smaller value to the PV threshold (SHPV) for auto tuning, and then check the result for improvement. p.900
6757<Limit cycle method> Auto tuning result exceeds proportional gain. (KP= outside range from 0 to 32767)<Auto tuning is finished (KP = 32767). → PID operation is started.> The variation of the measured value (PV) is small compared with the output value. Multiply the measured value (PV) by "10" so that the variation of the measured value will increase during auto tuning. p.900
6758<Limit cycle method> Auto tuning result exceeds integral time. (TI = outside range from 0 to 32767)<Auto tuning is finished (KP = 32767). → PID operation is started.> The auto tuning time is longer than necessary. Increase the difference (ULV - LLV) between the upper limit and lower limit of the output value for auto tuning, set a smaller value to the input filter constant (α), or set a smaller value to the PV threshold (SHPV) for auto tuning, and then check the result for improvement. p.900
6759<Limit cycle method> Auto tuning result exceeds derivative time. (TD = outside range from 0 to 32767) p.900
6760ABS data read from servo sum check errorCheck servo wiring and parameter setting. Also check the ABS instruction. p.900
6762Port specified by inverter communication instruction is already used in another communication.Check to make sure the port is not specified by another instruction. p.901
67631) Input (X) specified by a DSZR, DVIT or ZRN instruction is already used in another instruction. 2) The interrupt signal device for a DVIT instruction is outside the allowable setting range.1) Check to make sure the input (X), as specified by a DSZR, DVIT or ZRN instruction, is not being used for the following purposes: - Input interrupt (including the delay function) - High-speed counter C235 to C255 - Pulse catch M8170 to M8177 - SPD instruction 2) Check the contents of D8336 for the correct interrupt signal specification for a DVIT instruction. p.901
6764Pulse output number is already used in a positioning instruction or pulse output instruction (PLSY, PWM, etc.).Check to make sure the pulse output destination is not being driven by another positioning instruction. p.901
6765Number of applied instruction exceeds limit.Verify that the number of times that applied instructions are used in the program does not exceed the specified limit. p.901
6770Memory access errorWhen the memory cassette is used, check whether it is mounted correctly. If the problem persists or if the memory cassette is not used, something may be malfunctioning inside the PLC. Consult your local Mitsubishi Electric representative. p.901
6771Memory cassette is not connected.Check for the correct attachment of the memory cassette. p.901
6772Memory cassette is protected against writing.The write-protect switch of the memory cassette was set to ON when data was transferred to the flash memory. Set the protect switch to OFF. p.901
6773Access error to memory cassette during writing in RUN modeWhile data was written in the RUN mode, data was transferred to (read from or written to) the memory cassette. p.901
8702Communication character errorConfirm the cable connection between the programming device and the PLC. This error may occur when a cable is disconnected and reconnected during PLC monitoring. p.901
8703Communication data sum check error p.901
8704Data format error p.901
8705Command error p.901
8730Memory access errorWhen the memory cassette is used, check whether it is mounted correctly. If the problem persists or if the memory cassette is not used, something may be malfunctioning inside the PLC. Consult your local Mitsubishi Electric representative. p.901
020*1General data sum errorVerify that extension cables are correctly connected. p.901
021*1General data message error p.901
022*1System access error p.901
025*1Access sum error in other station via CC-Link p.901
026*1Message error in other station via CC-Link p.901
030*1Memory access errorWhen the memory cassette is used, check whether it is mounted correctly. If the problem persists or if the memory cassette is not used, something may be malfunctioning inside the PLC. Consult your local Mitsubishi Electric representative. p.901
080*1FROM/TO errorThis error occurs in the execution of operation. • Review the program and check the contents of the operands used in applied instructions. • Verify that specified buffer memories exist in the counterpart equipment. • Verify that extension cables are correctly connected. p.901
090*1Peripheral equipment access error• Check the cable connection between the programming panel (PP) / programming device and the PLC. • Verify that extension cables are correctly connected. p.901
01*1Special parameter setting time-out errorTurn OFF the power, and check the power supply and connection of special adapters/special blocks. p.902
02*1Special parameter setting errorSpecial parameters are set improperly. • Confirm troubleshooting for special adapters/special blocks, and set special parameters correctly. • Set special parameters correctly, turn OFF the power, and then turn ON the power. p.902
03*1Special parameter transfer target unconnected errorSpecial parameters are set, but special adapters/special blocks are not connected. Check whether special adapters/special blocks are connected. p.902
04*1Special parameter unsupported functionCheck that special parameters with unsupported settings are not set for connected special adapters/special blocks. p.902
b7Unit 7 access error p.902
b8 to b15Not available p.902
Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
P-SRET p.175
P-SRET p.175
3 p.175
3 p.175

Ask about the Mitsubishi Electronics MELSEC FX3S

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Mitsubishi Electronics MELSEC FX3S

Be the first to ask — other owners or our team will answer.

Original document

Mitsubishi Electronics MELSEC FX3S manual PDF

964 pages·16.5 MB·Garage Door Opener·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…