Page 1 of the Mitsubishi Electronics FX0N-232ADP user manual — JY992D51301C
Page 1 · click to enlarge
Page 1
Mitsubishi Electronics FX0N-232ADP — Front cover diagram (page 1)
Fig. 1 · Front cover
Mitsubishi Electronics FX0N-232ADP — Front cover diagram (page 1)
Fig. 2 · Front cover

FX 0N -232ADP COMMUNICATION ADAPTER

USER'S GUIDE

JY992D51301C

This manual contains text,diagrams and explanations which will guide the reader in the correct installation and operation of the FX0N-232ADP and should be read and understood before attempting to install or use the unit. Further information can be found in the FX SERIES PROGRAMMING MANUAL and FX0/FX0N HARDWARE MANUAL.

Page 2 of the Mitsubishi Electronics FX0N-232ADP user manual — TERMINAL LAYOUTS
Page 2 · click to enlarge
Page 2
Mitsubishi Electronics FX0N-232ADP — 1 INTRODUCTION diagram (page 2)
Fig. 3

G The FX0N-232ADP type RS232C adapter (hereinafter called 232ADP)

is connected to the FX0N series PC to exchange serial data with a personal computer, barcode reader, printer, and other various RS232C devices.

G Only one 232ADP unit can be connected to one base unit to the serial

G The buffer size and location are specified by an RS instruction in the PC.

EXTERNAL DIMENSIONS

MOUNTING HOLE POWER LED Lit up by the DC 5 V power supplied from the base unit. RD-LED Lit when receiving data from the RS232C device connected to the product. SD-LED Lit when transmitting data to the RS232C device connected to the product. Connection cable Used for connection with FX0N PC. RS232C connector Used for connection between the product and RS232C device.

Mitsubishi Electronics FX0N-232ADP — EXTERNAL DIMENSIONS diagram (page 2)
Fig. 4

(1.69)

  • DIN rail width : 35 Weight : approx.0.1 kg (0.11 lbs) All dimensions are in mm (inch)

TERMINAL LAYOUTS

The connector is a 25-pin D-SUB type, and the pin configuration is as shown below.

Pin No.Function 1No connection 2Send data (232ADP to RS232C device) 3Receive data (RS232C device to 232ADP) 4 • 5Not used ; Connected internally 6Shows RS232C device is ready to receive 7 8Signal ground No connection 20Signal requesting preparation for data sending to RS232C device.
Mitsubishi Electronics FX0N-232ADP — TERMINAL LAYOUTS diagram (page 2)
Fig. 5

Pins 4, 5 are not used.Short-circuited inside.

ER(DTR)Send request (Data Terminal Ready)

NC SG(Signal Ground) DR(DSR)Send enable (Data Set Ready) CS (CTS) Send enable RS (RTS) Send request RD (RXD) Receive data SD (TXD) Send data NC

Show 5 more labels / short text on this page
y · z · { · | · }
Page 3 of the Mitsubishi Electronics FX0N-232ADP user manual — INSTALLATION NOTES AND USAGE
Page 3 · click to enlarge
Page 3

INSTALLATION NOTES AND USAGE

Transmission standardConforming to RS232C, 25pin D-SUB, connector used Isolation methodPhoto coupler isolation Transmission distance15m or less (shielded cable recommended) Current consumptionDC 5V less than 200mA from base unit Control flags and data registersM8121:Send wait flag M8122:Send flag M8123:Receive completion M8161:8 bits/16 bits changeoverD8120:System configuration D8122:Remainder of send data D8123:Amount of received data D8124:Header byte D8125:Terminator byte
Ambient Temperature0 to 55°C in operation -20 to 70 °C in storage Ambient Humidity35 to 85% RH (no condensation) in operation Vibration ResistanceConforming to JIS C 0911, 10 to 55Hz 0.5mm (max.2G),2 hours each in 3 axial Impact ResistanceConforming to JIS C 0912, 10 G three times each in 3 axial directions Operating AmbienceFree from corrosive gas or excessive dust

Performance specification · General specification

Page 4 of the Mitsubishi Electronics FX0N-232ADP user manual — RD(RXD)
Page 4 · click to enlarge
Page 4

G For data transmission to be effective it is necessary to match the communication format between the product and the

RS232C device, such as Baud rate and parity.

Communication format D8120 (bit mapping)

Mitsubishi Electronics FX0N-232ADP — 3 INSTALLATION NOTES AND USAGE diagram (page 4)
Fig. 6
BitDescription0(OFF)1(ON) b 0Data length7bit8bit b 1 b 2Parity(00) : None (01) : Odd (11) : Even b 3Stop1bit2bit b 4 b 5 b 6 b 7Baud rate (bps)(0011) : 300 (0100) : 600 (0101) : 1,200 (0110) : 2,400 (0111) : 4,800 (1000) : 9,600 (1001) : 19,200
Mitsubishi Electronics FX0N-232ADP — 3 INSTALLATION NOTES AND USAGE diagram (page 4)
Fig. 7
BitDescription0(OFF)1(ON) b 8HeaderNoneD8124 *1 b 9TerminatorNoneD8125 *2 b10Control lineNoneH/W b11Mode (Control line)Ordinary modeSingle line mode b12 b13 b14 b15Not used- - -- - -

*1 The default value is STX (02H: changeable). *2 The default value is ETX (03H: changeable).

G The communication format is set by special data register D8120.

Setting the communication format using D8120 is effective only at the time the RS instruction is driven, and therefore any change after driving is not actually accepted.

G An example of setting D8120 is shown below.

Data length8 bit ParityEven Stop2 bit Baud rate9,600 HeaderUsed TerminatorUsed Control lineH/W ModeOrdinary mode
Mitsubishi Electronics FX0N-232ADP — 3 INSTALLATION NOTES AND USAGE diagram (page 4)
Fig. 8

[MOV H138F M8002

D8120]

H138F= 0001 0011 1000 1111(binary) The settings for the above program are as right.

G The control line is set by b10.

b10 = 0 :No hardware handshaking.Send and receive are controlled by software protocol. b10 = 1 :Hardware handshaking.Signal lines ER(DTR)and DR(DSR)are used to control send and receive of data.

Mitsubishi Electronics FX0N-232ADP — [MOV H138F M8002 diagram (page 4)
Fig. 9
b 101 b 110

SD(TXD)

H/W. Ordinary mode

ER(DTR)

DR(DSR)

b 101 b 111

Pin No.

SD(TXD)

Mitsubishi Electronics FX0N-232ADP — SD(TXD) diagram (page 4)
Fig. 10

H/W. Single line mode

RD(RXD)

ER(DTR)

Setting input · b15 b0 · When sending

Page 5 of the Mitsubishi Electronics FX0N-232ADP user manual — N/A
Page 5 · click to enlarge
Page 5

WIRING

G The connections of RS232C devices varies with each device being used.

Check the specification of the device, and connect. Connection examples

G Terminal specification device G Modem specification device

When RS232C device uses pins 4,5 RS232C

When RS232C device uses pins 6,20

When RS232C device uses pins 4,5 RS232C

When RS232C device uses pins 6,20

232ADP RS232C

232ADP

232ADP RS232C

232ADP

Mitsubishi Electronics FX0N-232ADP — 232ADP RS232C diagram (page 5)
Fig. 11
Mitsubishi Electronics FX0N-232ADP — 232ADP RS232C diagram (page 5)
Fig. 12
Mitsubishi Electronics FX0N-232ADP — 232ADP RS232C diagram (page 5)
Fig. 13

N/A

Show 4 more labels / short text on this page
device · device · device · device
Page 6 of the Mitsubishi Electronics FX0N-232ADP user manual — X001,ON
Page 6 · click to enlarge
Page 6

PROGRAM EXAMPLES

G Connecting 232ADP and a printer,and printing out the data sent from the PC.

FX0N series sequencer

Common pin out for printer communication

  • Receive data
  • Send data

G The communication format of the serial printer is as follows.

Data length 8 bit ParityEven Stop bit2 bit Baud rate 2400bps

G In this example, CR (H000D) and LF (H000A) are written at the end of the message.The printer moves down one line for each message. CR: Carriage Return LF: Line Feed

Turn on the power of the PC and printer, check the printer is on line and switch the PC to RUN.

X000,ON

Turn on X000, and drive RS instruction.

X001,ON

Every time X001 is turned on, the contents of D200 to D210 are sent to the printer, and "test line" is printed.

Show 7 more labels / short text on this page
Printer · Send · Sequence program · Operation · Power on · RS instruction drive · Data send
Page 7 of the Mitsubishi Electronics FX0N-232ADP user manual — 5 PROGRAM EXAMPLES
Page 7 · click to enlarge
Page 7

G Connect 232ADP and a personal computer,and exchange data with the PC.

G Use ordinary communication software (terminal emulator) or dedicated program in the personal computer.

Mitsubishi Electronics FX0N-232ADP — 5 PROGRAM EXAMPLES diagram (page 7)
Fig. 14

The communication format of the PC for this example is as follows.

  • Send data
  • Receive data
  • Receive data
  • Send data
Mitsubishi Electronics FX0N-232ADP — 5 PROGRAM EXAMPLES diagram (page 7)
Fig. 15
Data length8 bit ParityEven Stop bit1 bit Baud rate2400

G Use the communication cable suited to the connector pin configuration of the personal computer. (For representative wiring see section 4.)

If the communication format of the software cannot be adjusted to this setting, adjust the PC and the software to be the same.

Preparation of software · Personal computer

Page 8 of the Mitsubishi Electronics FX0N-232ADP user manual — 5 PROGRAM EXAMPLES
Page 8 · click to enlarge
Page 8
Mitsubishi Electronics FX0N-232ADP — 5 PROGRAM EXAMPLES diagram (page 8)
Fig. 16
Mitsubishi Electronics FX0N-232ADP — 5 PROGRAM EXAMPLES diagram (page 8)
Fig. 17

Turn on the power of the PC and printer, check the printer is on line and switch the PC to RUN.

Every time X001 is turned on, the contents of D200 to D210 are sent to the personal computer, and "test data" is displayed.

After receiving and storing data from personal computer in D211, it is output to Y000 to Y017. When input X002 is turned on, the receive completion flag is reset.

Sequence program

Page 9 of the Mitsubishi Electronics FX0N-232ADP user manual — 6 DIAGNOSTICS
Page 9 · click to enlarge
Page 9
Mitsubishi Electronics FX0N-232ADP — 6 DIAGNOSTICS diagram (page 9)
Fig. 18

G If data transfer does not perform correctly when using

G If sending and receiving using these programs is

the 232ADP, check the operation using the following programs.

successful, it is considered that the operation failure was due to sequence program or communication protocol error.

to the external device to be used. G Header and terminator are not attached.

G If not operating normally when using these programs,

eliminate the cause using the flow diagrams shown following.

* Write the data to be sent to D 0 to D 19 before operating.

Page 10 of the Mitsubishi Electronics FX0N-232ADP user manual — YES
Page 10 · click to enlarge
Page 10

NO

  • Check connection with the PC.
  • Check power source of PC.

YES

  • Match the communication format.
  • Check the wiring of control line.
  • Check the start timing of send, receive.

YES NO

Is M8063 turned on?

once.

No send or receive error

NO

No send or receive error

  • There is a possibility of send crosstalk. Check the send and receive timing with the external RS232C device.
  • The receive data length may exceed the receive data area. Check the receive data length and timing of receive start.
  • Check that the program is not set so that M8122 may be always on .

YES

Only receiving fails to operate

1 YES

NO

  • Check wiring of control line.
  • Check timing of send, receive.
  • Change RS instruction from OFF to ON.
  • Make sure the received data length matches with the receive data area length.

Is send wait flag M8121

YES

NO

Is SD LED (send) lit up momentarily?

NO

  • Check wiring of RS232C cable.
  • Check wiring of control line.
  • Make sure the receiving external device is normal.
  • Check the voltage level of RS232C signal (±9 V).
  • Make sure content of send data and communication format are established before driving RS instruction.

YES

Is the send data remainder

NO

  • Check the timing of control line.

YES

  • Check the wiring of RS232C cable.
  • Check the wiring of control line.
  • Match the communication format.
  • Make sure the receiving external device is normal. (CR, LF may be needed in some printers.)
  • Check the data format of sending device.
Show 9 more labels / short text on this page
Start · Is power · LED lit? · The data · transfer complates · Send, receive error · normally · turned on? · zero?
Page 11 of the Mitsubishi Electronics FX0N-232ADP user manual — YES
Page 11 · click to enlarge
Page 11
  • Check wiring of RS232C cable.
  • Make sure wiring of control line is suited to the external device.
  • Make sure the external sending device is normal.
  • Check the voltage level of RS232C signal.

NO

Is RD LED (receive) lit?

YES

  • Check if receive data length is exceeding the data area length. When using terminator
  • Make sure the external sending device is sending the terminator.
  • Make sure the terminator value matches.

Is M8123 turned on? No receive completion

YES NO

All data is received?

YES

NO

  • Match the communication format.
  • Check the timing of control line.
  • Check if the send data length is not zero when driving RS instruction. When using header
  • Make sure the external sending device is sending the header. When using terminator
  • Check the timing of send, receive.

Are the contents of receive data unintelligible?

  • Monitor data in hexadecimal notation (HEX).
  • Check on/off of M8161.
  • Confirm send data format of the sending device.

YES

NO

[ When M8123 is reset, the PC returns to the wait state. ]

Receive completion · (Monitoring D8123) · Normal

Page 12 of the Mitsubishi Electronics FX0N-232ADP user manual — JY992D51301C
Page 12 · click to enlarge
Page 12
  • Guidelines for the safety of the user and protection of the FX 0N -232ADP
  • This manual has been written to be used by trained and competent personnel. This is defined by the European directives for machinery, low voltage and EMC.
  • If in doubt at any stage during the installation of the FX 0N -232ADP always consult a professional electrical engineer who is qualified and trained to the local and national standards.If in doubt about the operation or use of the FX 0N -232ADP please consult the nearest Mitsubishi Electric distributor.
  • Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of the installation or use of this equipment.
  • All example and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples.
  • Owing to the very great variety in possible application of this equipment, you must satisfy yourself as to its suitability for to your specific application.
Manual numberJY992D51301 Manual revision : C Date : JUNE 1996

HEAD OFFICE:MITSUBISHI DENKI BLDG MARUNOUCHI TOKYO 100 TELEX:J24532 CABLE MELCO TOKYO HIMEJI WORKS:840, CHIYODA CHO, HIMEJI, JAPAN

Effective JUN.1996 Specifications are subject to change without notice.

JY992D51301C

Ask about the Mitsubishi Electronics FX0N-232ADP

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Mitsubishi Electronics FX0N-232ADP

Be the first to ask — other owners or our team will answer.

Original document

Mitsubishi Electronics FX0N-232ADP manual PDF

12 pages·485 KB·Network Card·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…