

2408f & 2404f PROFIBUS Communications Handbook Introduction
This handbook is written for people who need to use a digital communications link and PROFIBUS-DP communication protocols to supervise Eurotherm Controls Series 2000 instruments. The PROFIBUS-DP protocol is supported by Eurotherm instruments carrying the suffix f in their order codes. Specifically 2408f and 2404f controllers.
It has been assumed that the reader has some experience of communication protocols and is familiar with Series 2000 instruments.
Related handbook: • Installation and Operation Handbook for 2408 and 2404 Controller, Eurotherm part number HA025132. This gives a full description of how to use the instruments, configuration options and definition of parameters.
Eurotherm Controls accepts no responsibility for any loss or damage caused by mis-application of the information contained in this document.
PROFIBUS-FMS
PLC PC DCS
PROFIBUS-DP PROFIBUS-PA
Temp Controller I/O Field Device Motor Drives
PROFIBUS is a vendor independent, open fieldbus standard for a wide range of applications in manufacturing, process and building automation. Vendor independence and openness are guaranteed by the PROFIBUS standard EN50170. With PROFIBUS, devices from different manufacturers can inter-communicate. Suitable interfaces exist for PLCs, which include the Siemens, Mitsubishi and Allen Bradley range.
The 2400f controllers support the PROFIBUS-DP variant of the PROFIBUS protocol which is designed especially for communication between automatic control systems and distributed I/O at the device level. It is most often used to allow a central Programmable Logic Controller or PC based control system to use external ‘slave’ devices for I/O or specialised functions. The principal advantage is that these devices may be distributed around a machine, thereby saving on the cost of point to point wiring. The ‘open’ nature of the network also permits equipment from different manufacturers to be mixed on the same bus. Additionally, the off-loading of complex and specialised tasks such as PID temperature control lessens the processing load on the central PLC so that its other functions may be carried out more efficiently and require less CPU memory.
PROFIBUS-DP is described in DIN 19245 Part 3, and forms part of EN 50170 with P-Net and WorldFIP. However it is important to note that P-Net and WorldFIP are wholly incompatible with PROFIBUS, using different wiring and transmission technologies.
The PROFIBUS-DP network uses a high speed version of the RS485 standard, permitting baud rates of up to 12Mbaud. Note however, that in order to guarantee electrical isolation standards, the 2400f Series supports rates of up to 1.5 MBaud only. A table of network speed against segment length is given in Chapter 3.
A maximum of 32 PROFIBUS-DP stations (nodes) may be contained within a single network segment. Use of RS485 repeaters allows a total of up to 127 stations.

Introduction 2408f & 2404f PROFIBUS Communications Handbook
PROFIBUS-DP is a multimaster, master-slave, token passing network. More detailed information, including a detailed guide to products available, may be obtained from the various world wide PROFIBUS user organisations. You will find contact information in trade magazines or by reference to http://www.profibus.com on the World Wide Web.
PROFIBUS is available in two other types, aimed at different application areas, as follows:
PROFIBUS-PA is designed especially for process automation. It permits sensors and actuators to be connected on one common bus line even in intrinsically safe areas. PROFIBUS PA permits data communication and power over the bus, using intrinsically safe, 2-wire technology according to the international standard IEC 1158-2, but may also be used on the standard RS485 cabling for non-intrinsically safe applications.
PROFIBUS-FMS is the general purpose solution for communication tasks at the cell level.
2400f series controllers may be used on ‘combi’ networks which combine DP and FMS, but may only be used for PA when the intrinsically safe physical medium is not used.

2408f & 2404f PROFIBUS Communications Handbook Principles of Operation
PROFIBUS-DP distinguishes between master devices and slave devices. It allows slave devices to be connected on a single bus thus eliminating considerable plant wiring typical with conventional communications systems. Figure 2-1 compares the two systems.
Master devices determine the data communication on the bus. A master can send messages without an external request when it holds the bus access rights (the token). Masters are also called active stations in the PROFIBUS protocol.
Slave devices are peripheral devices. Typical slave devices include input/output devices, valves, motor drives and measuring transmitters. The 2408f and 2404f series Temperature Controllers are intelligent slaves. This means they will only respond to a master when requested to do so.
PROFIBUS-DP is based around the idea of a ‘cyclical scan’ of devices on the network, during which ‘input’ and ‘output’ data for each device is exchanged.
PLC
Input Input Output Output
Slave 1 Slave 2 Slave 3 Slave 4
The process of reading the inputs and writing to the outputs is known as an I/O data exchange. Typically, the parameters from each slave device will be mapped to an area of PLC input and output registers, or a single function block, so that the controlling ladder logic or program interfaces with the device as if it were an internally fitted module. It is NOT necessary, therefore, for the programmer to know anything about the physical network. The process of network configuration is usually performed using a PC based program which allows the devices on the network to be defined and device parameters to be mapped into the PLC registers or function blocks.
The cyclical scan occurs in the following order:
1. Values from each slave device, ‘Input Data’, are first scanned over the network into a pre-defined set of input registers in the master controller. Such values might be a set of digital input readings for a digital input unit, or the measured temperature and alarm status from a PID controller. 2. The master then runs its control program, (such as a ladder logic program) using the input data read from the slave devices. 3. The master writes output values (output data) into a pre-defined set of output registers. For example, one of the digital inputs read in the input data might be used to select one of a set of setpoints to be sent to the PID controller. 4. These outputs are then written to each slave device, and the scan-process-write cycle repeats.

Principles of Operation 2408f & 2404f PROFIBUS Communications Handbook
Typically no more than 32 bytes of input data and 32 bytes of output data are exchanged for each device during the data exchange. Some PLC masters allow no more than this, although the PROFIBUS-DP standard provides the possibility of transferring 236 bytes in each direction. The input and output data lengths for a given device are variable and it is possible to have devices with only input data, only output data, or both.
The input and output data mixture used by a given slave device is defined by what is known as a GSD file. See Chapter 5 for more details. For simple devices such as digital or analogue I/O blocks, this is fixed. However, since more complex devices often have a much wider choice of possible values to send, it is usually possible to edit the GSD file to change the mapping of device parameters onto Profibus inputs or outputs. This is the case with most Eurotherm implementations, which also allow access to parameter data not in the GSD Input/Output data file. This is called Demand Data and is described further in Chapter 7.
The GSD file is imported into the PROFIBUS Master Network Configuration software before the network is created.
NB: PROFIBUS Input Data = Values sent from a device to a master controller or PLC, PROFIBUS Output Data = Values sent from a master controller or PLC to a device

2408f & 2404f PROFIBUS Communications Handbook Wiring
RS485 is the transmission technology used in 2404f and 2408f PROFIBUS-DP controllers. Connections are made to the rear terminal block as follows:
The PROFIBUS standard suggests that both ends of the transmission line be connected to safety earth. If such a course is followed, care must be taken to ensure that differences in local earth potential do not allow circulating currents to flow, as these can not only induce large common mode signals in the data lines, but can also produce potentially dangerous heating in the cable. Where doubt exists, it is recommended that the shield be earthed at only one section of the network.
Do not connect the shield to DGND.
SHIELD
HB
HC
VP (+5Vdc Voltage Potential)
HE
HF
B A
2408 f or 2404 f controller
Intermediate stations
B A
HB
HC
VP (+5Vdc Voltage Potential)
HD
220 Ω
HE
Last station only requires terminating resistors
390 Ω
HF
2408 f or 2404 f controller

Wiring 2408f & 2404f PROFIBUS Communications Handbook
Either of the two cable types detailed below can be used. Please note that the cable types A and B, specified below, are NOT related to the wire numbers A and B in the above wiring diagram. Type A is recommended as it allows higher speed and longer cable length.
Belden B3079A meets cable A specifications, but there are other choices. For more information refer to the ‘PROFIBUS Product Guide’ produced by the PROFIBUS User Group.

2408f & 2404f PROFIBUS Communications Handbook Controller Set Up & Network Configuration
PROFIBUS-DP communications is available in Eurotherm 2408f and 2404f controllers. Other 2000 series controllers (i.e. controllers without the f suffix) cannot be converted to PROFIBUS-DP comms, since a different microprocessor board is required.
Main Differences between 2400f Controllers and Other Series 2000 Instruments.
2400f The 20 program variant is not available EI Bisynch is not available. The Instrument Programming System software, IPSG, therefore, cannot be used for cloning or configuration. Module slot H can only be used for PROFIBUS-DP or Modbus communications. A PROFIBUS-DP module fitted to 2400f may be configured to Modbus communications if required. A Modbus module fitted to any other 2000 series instrument cannot be configured to PROFIBUS-DP. A PDSIO master or slave module can only be fitted in module slot J.
PROFIBUS-DP may be used with either mains powered and 24V AC/DC controllers, and in all respects, other than those described above, they are standard units and may be used in exactly the same way as other 2400 series controllers.
Assigning a Node Address
Connect the controller to the PROFIBUS network as described in Chapter 3.
Every controller on the network must have its own unique address to distinguish it from any other.
From the HOME display,
press until you reach the , list
, )O6 From the Comms List
Press to display the node address. Press or to set the desired address. B
From the Address List
Press to display the Comms Status This is a read-only diagnostic display 5A Ready to run 59. Comms running
Press to return to the HOME display
5 · 66


Controller Set Up & Network Configuration 2408f & 2408f PROFIBUS Communications Handbook
If the password has been set to ‘0’ - access is permanently unlocked & the lower readout always shows PASS
At this point the controller is in configuration level
Press or to set 9. = 05/ D This selects PROFIBUS-DP protocol
Press or to select 9)) = Full, or N.6 = Integer 9)) is the recommended setting

2408f & 2404f PROFIBUS Communications Handbook Controller Set Up & Network Configuration
Having wired and configured the controller, the master PLC or PC based supervisory package must be configured to set-up the parameters that it will be able to read and write to. This is known as ‘network configuration’.
The network is configured by importing ‘GSD’ files into your Master PROFIBUS network configuration software: This should be explained in your network configuration software documentation. ‘GSD’ is an acronym of a German phrase meaning ‘Device Database’.
The GSD files supplied with your 2408f and 2404f controllers are created using a Windows-based configuration tool. This software is also separately available under ordering code PROF-ENG. Two standard GSD files, are supplied on the disc: EURO2400.GSD - standard parameter mapping. This is the default file, which is pre-configured for commonly used
parameters, as shown in Table 4-1 below. EURD2400.GSD - standard parameter mapping with ‘demand data’, which allows random read/write to any parameter
within the controller. This is configured with the same default parameters.
Table 4-1: Default Parameters.
The Summary Output Status Word is shown in Table 4-2., see ‘PROFIBUS DIAGNOSTICS’
It is possible to edit the above files or create new files using the Windows configurator.
The Master network configuration software uses the GSD files to produce a further file which is downloaded into your master PLC or PC supervisory package. Once the configuration file has been downloaded, you can set the network running. If all is well, the ‘REM’ beacon on the controller will start to flash, indicating that the data exchange is proceeding. The 66 parameter in the + list will show 59.. Input data will then be transferred from the controller to the master, and output data will be transferred from the master to the controller.
If all 2400f controllers are of the same type only one GSD file needs to be configured.
Data is returned or sent in the form of a single 16 bit integer value (register). Since the controllers use and display floating point values, these are translated into integers in one of two ways, selected in controller configuration.
Full Resolution: The value is returned as a ‘scaled integer’, such that 999.9 is returned or sent as 9999; 12.34 is encoded as 1234. The control program in the PROFIBUS master must convert the numbers into floating point values if required. This is the recommended format and is the factory default.
Integer Resolution. The floating point value is returned as a rounded integer, with the fractional part discarded. For example 999.9 would be returned as 1000; 12.34 would be returned as 12. Similar rules apply to output operations, although note that it is only possible to send integer values so that setpoint values such as 11.5 cannot be used and so either 11 or 12 would have to be chosen instead.

Controller Set Up & Network Configuration 2408f & 2408f PROFIBUS Communications Handbook
One of the features of PROFIBUS-DP is that high priority diagnostic information is provided for each slave. The 2400f Series uses the ‘Ext_Diag_Data’ area of this message (bytes 7 and 8) to send a word containing 16 bits of information pertaining to the process and alarm status of the controller: The documentation supplied with your master should provide further details on how to access diagnostic information.
A ‘new diagnostics’ event will occur whenever any of the monitored events changes state...
The example below may be returned which gives a summary of the Output Status Word information shown in the table above.
Byte 6 signifies 3 bytes of information are included Bytes 7 & 8 are 4030Hex or 01 00 11 00 00 Binary
From table 4-1:
Bit 4 is set Meaning the controller is in Manual Mode Bit 5 is set Meaning the controller is in Sensor Break Bit 14 is set Meaning the controller is in IP1 Fault
This is a further PROFIBUS-DP feature, which is not supported by the 2400f series of temperature controllers.

2408f & 2404f PROFIBUS Communications Handbook The Windows Configurator
The Windows Configurator creates a ‘GSD’ file which provides a simple way of mapping device parameters into the PLC or supervisory package input/output registers. The GSD file is imported into a PROFIBUS Master which in turn produces a file that is downloaded into the PLC or supervisory package. It works on the ‘drag and drop’ principle by clicking on parameters within lists (which correspond to the parameter lists in the controller) and dragging the chosen parameter to input or output windows.
The program will run on Windows 3.1, Windows 95 or Windows NT.

Figure 5-1: The Default Configurator Screen Layout.
Leave the mouse cursor over a portion of the screen to see a hint explaining how it works. Hints can be turned off via the Help menu once you have learned how to operate the program.
Open a GSD file for modification or editing, or create a new file for the currently selected controller type, using the ‘file’ menu. Note, however, that only files for the Eurotherm products, which include 2400f and T630, may be edited using this program. Selected input or output parameters may be printed using the ‘print’ command in the ‘file’ menu. Standard Windows facilities for Save and Save As are provided, allowing GSD files to be written to disk. The buttons on the task bar provide quick access to most of these functions.
The controller parameter set is represented by a box to the left of the screen. A set of tabs allows a group of parameters to be displayed, corresponding to lists in the controller user interface. A separate list for 2400f series status words is also provided for the controller type.

The Windows Configurator 2408f & 2404f PROFIBUS Communications Handbook
To add a parameter to the PROFIBUS-DP Input Data, simply drag it from the Device Parameter list using the mouse, and drop it into the Inputs list. Similarly, drop a parameter into the Outputs list to set PROFIBUS-DP Output Data. Alternatively, double click on a parameter name to add it to the currently selected window - select the list by clicking on it - or use the arrow button to the left of the input and output lists. You may change the order of the Input and Output List by dragging and dropping between them. Parameters may be deleted or the list cleared using the buttons on the right hand side of the I/O lists, or by pressing the right mouse button when the cursor is over a parameter name, whereupon a pop up menu will be displayed.
Select or remove support for ‘Demand Data’ (see Chapter 7) using the check box in the lower part of the screen. Add a short description of the function of the GSD file in the lower window: this will usually be displayed by your network configuration tool when selecting a device from the list.
Once the I/O data has been specified to your wishes, save the GSD file to disk: you may use any filename you wish. You may then import it into your PROFIBUS-DP network configuration tool and use it in an application program. It is possible to save several different GSD files for the same basic instrument, thereby setting up a library for different applications.
Input Data • Process Variable
In this application, the PLC monitors ‘Process Variable’ (actual temperature), and when it passes into a particular pre-set band, sets the output data parameters from settings stored in the PLC.
Use the right mouse button when the cursor is over a parameter in the left hand window to determine its tag for demand data operations.
A limit of 117 total input and output words, including the requirements for demand data, is imposed by the configurator. When this limit is reached, it will no longer be possible to add parameters into either the input or output lists until other parameters have been deleted. In any case it is advisable not to exceed 32 input and 32 output words in total, since some masters are unable to deal with more.
To obtain a summary of the I/O memory map for the current GSD file, select ‘View I/O map’ from the file menu. This may be pasted into the clipboard and placed into a document if required for project documentation. It may also be printed directly from the File menu.

2408f & 2404f PROFIBUS Communications Handbook Troubleshooting
Iss No. DATE
Intermittent Failure to Communicate. Intermittent Flickering of Status From ‘5A 5A’ to ‘59. 59.’. Diagnostic Status Changing but no Alarms Present in the Controller.
Setpoint, Output Power, Auto/Manual etc ‘jammed’ to one setting and cannot be altered using controller front panel.

2408f & 2404f PROFIBUS Communications Handbook Demand Data
The GSD file is used to define those parameters which need to be updated continuously. It is, therefore, a convenient way to transfer input and output data between the controller and the master PLC or Supervisory Computer. It is, however, wasteful in comms bandwidth if, for example:
For these parameters use the ‘Demand Data’ sub-protocol. This allows read/write access to any parameter within the controller using, what are known as ‘Tags’ which identify the parameters. Each parameter has a unique 16 bit tag, a full list of which is given in the next chapter.
When Demand Data is used, the first four (16 bit) registers of the PROFIBUS-DP Output data are reserved to encode a ‘request message’ using the protocol. The control program is responsible for writing values into the first four registers to make requests. The instrument uses the first four registers of PROFIBUS-DP input data as a ‘response message’ to return values and indicate success or failure of the operation that was requested.
Demand Data is supported by standard software in many PLCs. It can be implemented easily as part of the PLC program.

Demand Data 2408f & 2404f PROFIBUS Communications Handbook
Demand Data uses the first 8 bytes in both the request and response message of the cyclic Data Exchange.
Read Request (from PLC)
Response to Read Request (from Controller)
PLC Input Register Number Input Data The first four registers are reserved for responses to demand data.
The first four registers are reserved for demand data. The control program is responsible for writing values into these first four registers to make requests.
1 Command Code and Parameter Tag 2 Extended Parameter Tag 3 Reserved 4 Returned value The registers that follow are used for the fixed input data defined by the GSD file
1 Command Code and Parameter Tag 2 Extended Parameter Tag 3 Reserved 4 Anything The registers that follow are used for the fixed output data defined by the GSD file
5 Value or State 6 Value or State 7 Value or State etc. Value or State
5 Value or State 6 Value or State 7 Value or State etc. Value or State
Response to Write Request (from Controller)
The first four registers are reserved for demand data. The control program is responsible for writing values into these first four registers to make requests.
The first four registers are reserved for responses to demand data.
1 Command Code and Parameter Tag 2 Extended Parameter Tag 3 Reserved 4 Value or State to be written The registers that follow are used for the fixed output data defined by the GSD file
1 Command Code and Parameter Tag 2 Extended Parameter Tag 3 Reserved 4 Write error code The registers that follow are used for the fixed output data defined by the GSD file
5 Value or State 6 Value or State 7 Value or State etc. Value or State
5 Value or State 6 Value or State 7 Value or State etc. Value or State
7-2 2408f & 2404f PROFIBUS Communications Handbook

2408f & 2404f PROFIBUS Communications Handbook Demand Data
THE COMMAND CODE AND TAG ARE ENCODED INTO REGISTER 1 AS FOLLOWS:
Bits 15-12 Bit 11 Bit 10 - 0 Command Code Reserved Parameter Tag
Because only 11 bits are available for the Parameter Tag, the maximum tag allowable for standard demand data operations is 2048. The 2400f series controller allows tag values of up to 16383, therefore, extended tags have been provided using register 2. This is particularly important if ramp/dwell programs or configuration information is to be transferred over PROFIBUS-DP.
Fields in a request (output registers) should be set as follows: NB: Eurotherm Extensions are printed in bold italic text
Command (Hex) Request (Master to Slave) Parameter Tag Extended Parameter Tag
0000 No Command - - - 1000 Read Request Tag to Read - - 2000 Write Request Tag to Write - Value to write 3000 Extended Read Request Must be Zero Tag to Read - 4000 Extended Write Request Must be Zero Tag to Write Value to Write
Valid responses to a given command are as follows:
Command Field in request (output register)
Command Field in response
Meaning Returned Value (input register 4)
0000 0000 Acknowledge No Command - 1000 1000 Tag Read Successfully Value Read 1000 7000 Tag Read Not Successful Error Code (see below) 2000 1000 Tag Written Successfully - 2000 7000 Tag Write Not Successful Write Request 3000 1000 Extended Tag Read Successfully Value Read 3000 7000 Extended Tag Read Not Successful Error Code (see below) 4000 1000 Extended Tag Written Successfully - 4000 7000 Extended Tag Write Not Successful Error Code (see below)
Error Codes in input register 4 are as follows.
Error Code Meaning 0 Invalid Tag Number 1 Read Only Parameter 2 Value out of range
Value · (input register)

Demand Data 2408f & 2404f PROFIBUS Communications Handbook
An autotune is a good example of an operation that might be performed using the demand data sub-protocol, since it is a relatively infrequent operation and it would be wasteful to dedicate PROFIBUS-DP I/O data to such a task.
Request 1: Clear any previous demand data requests. You should do this at the start of any sequence of operations using demand data in order to ensure that the system is properly initialised.
PLC Output Register Number Output Data Comment 1 0 2 Anything 3 Anything 4 Anything
PLC Input Register Number Input Data Comment 1 0 2 Anything 3 Anything 4 Anything
Request 2: Write 1 to Autotune enable. Note Tag address is 270 (decimal) see ‘TAG ADDRESSES’ Chapter 8
PLC Output Register Number Output Data Comment 1 8462 Write request 2000 (hex) (8192 dec) + tag address 270 (dec.) = 8462 (dec) 2 Anything 3 Anything 4 1 Write state 1 to enable Autotune see enumerators for each tag address in Chapter 8
Response 2: Wait for one of the following responses to be received. a. An error has occurred (Code 7)
PLC Input Register Number Input Data Comment 1 28942 Error 7000 (Hex) (28672 dec) + tag address (270 dec) = 28942 2 Anything 3 Anything 4 1 or 2 or 3
Invalid tag number Read only parameter Value out of range
PLC Input Register Number Input Data Comment 1 4366 Successful write code 1000 (Hex) (4096dec) + tag address 270 (decimal) = 4366 2 Anything 3 Anything 4 Anything
Request 3: If there was no error, poll Control Status Word (tag 76) until autotune complete.
PLC Output Register Number Output Data Comment 1 4172 Successful write code 1000 (Hex) (4096dec) + tag address 76 (decimal) = 4172 2 Anything 3 Anything 4 Anything
To determine when Autotune is complete: Look at the PROFIBUS-DP Input data until either bit 3 (Self Tune Fail) of the value field is set, or bit 12 (Autotune enabled) is cleared. There is no need to set up more requests, since the value field will be automatically updated by the slave, but you should not try to access other demand data until this operation has completed. Any value for register 1 other than 4172 signifies an error has occurred, in which case register 4 will contain an error code of 0 or 1 or 2.
PLC Input Register Number Input Data Comment 1 4172 Anything 3 Anything 4 XXXX The value of the Control Status Word
7-4 2408f & 2404f PROFIBUS Communications Handbook

2408f & 2404f PROFIBUS Communications Handbook Demand Data
The 2400f series with PROFIBUS-DP may be configured with a ramp/dwell programmer option. It is often the case that specific ramp dwell sequences need to be downloaded to an instrument. Because of the amount of data involved, it would be impossible if only standard PROFIBUS-DP input and output frames were to be used. Use of the demand data protocol is the only way the operation may be performed.
Note that if the programmer option is configured, the instrument defines two types of program data store. Program 0 holds a copy of the currently running program (if any) which may be accessed or changed in ‘hold’ mode only. Programs 1, and 2, 3, and 4 for a 4 programmer instrument, hold the actual program data and may be accessed at any time.
From the tag list, we find that the Program 1 has tags running from 8328 to 8463. This is above the maximum of 2047 for a standard tag read, so we will need to use the Eurotherm extensions.
Request 1: Clear any previous demand data requests. You should do this at the start of any sequence of operations using demand data in order to ensure that the system is properly initialised.
PLC Output Register Number Output Data Comment 1 0 2 Anything 3 Anything 4 Anything
Response 1 Wait until the following response message is received in the input data:
PLC Input Register Number Input Data Comment 1 0 2 Anything 3 Anything 4 Anything
Request 2: Read from the first program address.
PLC Output Register Number Output Data Comment 1 12288 Extended read tag 3000 (Hex) 2 8328 Program 1 tag address,. see Chapter 8 3 Anything 4 Anything
Response 2: Wait for one of the following responses to be received. a. An error has occurred
PLC Input Register Number Input Data Comment 1 37000 Error 7000 (Hex) (28672 dec) + tag address 8328 (dec) = 37000 2 Anything 3 Anything 4 0 1 2
Invalid tag number Read only parameter Value out of range
b. No error.
PLC Input Register Number Input Data Comment 1 12288 Extended read tag 3000 (Hex) 2 8328 Program 1 tag address,. see Chapter 8 3 Anything 4 Anything If there was no error, store the Program Value in the required memory location, increment register 2 in the request message, and repeat until tag 8463 (end of program 1 segments) has been reached.
Parameter Tags may be obtained by reference to the following chapter. Note also that the GSD Configuration Program allows the display of the tag for a given parameter, by clicking the right mouse button when pointing to the parameter.

2408f & 2404f PROFIBUS Communications Handbook Tag Addresses
Tag addresses are used to identify parameters in the controller and are identical to the Modbus addresses which are also listed in the Series 2000 Communications Manual, Eurotherm Part No. HA 026230. Tag addresses are used with the demand data protcol to set up input/output data in the PLC or supervisory PC.. They are repeated here in the order in which they appear in the GSD file. They can also be read from the Windows Configurator by pointing to the parameter and clicking the right mouse button.
Display Parameter Description Address
12 Programmer Segment Synchronise (0 = Waiting, 1 = Running) 13 Remote input sensor break ( 0 = Good, 1 = Bad) 14 IP1 Fault 15 Reserved
0 0 Target setpoint 2
0 0 % Output power For ON/OFF controllers the following power levels must be written: Cool -100% OFF 0% Heat 100%
Fast Status Byte 74
BIT DESCRIPTION Bit 0 Alarm 1 State ( 0 = Safe 1 = Alarm ) Bit 1 Alarm 2 State ( 0 = Safe 1 = Alarm ) Bit 2 Alarm 3 State ( 0 = Safe 1 = Alarm ) Bit 3 Alarm 4 State ( 0 = Safe 1 = Alarm ) Bit 4 Manual Mode ( 0 = Auto 1 = Manual ) Bit 5 Sensor Break ( 0 = Good PV 1 = Sensor Broken ) Bit 6 Loop Break ( 0 = Good closed loop 1 = Open Loop ) Bit 7 Heater Fail ( 0 = No Fault 1 = Load fault detected )
=D0 =D0 Working set point. Read only: use Target set point or currently selected set point (1 to 16) to change the value
,B ,B Auto-man select 0: Auto 1: Manual
B Valve Posn (computed by VP algorithm)
B VP Manual Output (alterable in Man only)
Control Status Word 76
,0 ,0 Heater current (With PDSIO mode 2)
BIT DESCRIPTION 0 Control algorithm Freeze 1 PV input sensor broken 2 PV out of sensor range 3 Self Tune failed 4 PID servo signal 5 PID debump signal 6 Fault detected in closed loop behaviour (loop break) 7 Freezes the integral accumulator 8 Indicates that a tune has completed successfully 9 Direct/reverse acting control 10 Algorithm Initialisation flag 11 PID demand has been limited. 12 Autotune enabled 13 Adaptive tune enabled 14 Automatic Droop compensation enabled 15 Manual / Auto mode switch Instrument Status Word 77
DO DO Customer defined identification number
Setpoint Span 552 Error (PV-SP) 39 Remote Input Value 26
Summary Output Status Word 75
BIT DESCRIPTION 0 Alarm 1 State ( 0 = Safe 1 = Alarm ) 1 Alarm 2 State ( 0 = Safe 1 = Alarm ) 2 Alarm 3 State ( 0 = Safe 1 = Alarm ) 3 Alarm 4 State ( 0 = Safe 1 = Alarm ) 4 Manual Mode ( 0 = Auto 1 = Manual ) 5 Sensor Break ( 0 = Good PV 1 = Sensor Broken ) 6 Loop Break ( 0 = Good closed loop 1 = Open Loop ) 7 Heater Fail ( 0 = No Fault 1 = Load fault detected ) 8 Tune Active ( 0 = Auto Tune disabled 1 = Auto Tune active) 9 Ramp/Program Complete ( 0 = Running/Reset 1 = Complete ) 10 PV out of range ( 0 = PV within table range 1 = PV out of table range ) 11 DC control module fault (0= Good. 1= BAD)
BIT DESCRIPTION 0 Config/Oper mode switch 1 Disables limit checking 2 SRL ramp running (Read Only) 3 Remote setpoint active 4 Alarm acknowledge switch. 5 Reserved 6 Reserved 7 Reserved 8 Reserved
Process Variable 1 · Pot Position 317

Tag Addresses 2408f & 2404f PROFIBUS Communications Handbook
9 Reserved 10 Reserved 11 Reserved 12 Reserved 13 Reserved 14 Reserved 15 Reserved Program Logic Status 162
14 Reserved 15 Reserved
Parameter Description Tag Address SP Rate Limit Holdback Status 0: Inactive 1: Active
BIT DESCRIPTION 0 Program Output 1 ( 0 = OFF 1 = ON ) 1 Program Output 2 ( 0 = OFF 1 = ON ) 2 Program Output 3 ( 0 = OFF 1 = ON ) 3 Program Output 4 ( 0 = OFF 1 = ON ) 4 Program Output 5 ( 0 = OFF 1 = ON ) 5 Program Output 6 ( 0 = OFF 1 = ON ) 6 Program Output 7 ( 0 = OFF 1 = ON ) 7 Program Output 8 ( 0 = OFF 1 = ON ) 8 Reserved 9 Reserved 10 Reserved 11 Reserved 12 Reserved 13 Reserved 14 Reserved 15 Reserved Digital Output Status Word 551
Pot Break 350 Freeze Control Flag 0: Controlling 1: Hold
SP Rate Limit Active Status 0: No setpoint rate limit 1: Setpoint rate limit active
New Alarm Flag 260 Loop Break Status Flag 0: Good 1: Loop break
BIT DESCRIPTION 0 H Interface module telemetry (0 = Off, 1 = On) 1 J Interface module telemetry (0 = Off, 1 = On) 2 1A module telemetry (0 = Off, 1 = On) 3 LB logic telemetry (0 = Off, 1 = On) 4 LA logic telemetry (0 = Off, 1 = On) 5 1B module telemetry (0 = Off, 1 = On) 6 1C module telemetry (0 = Off, 1 = On) 7 2A module telemetry (0 = Off, 1 = On) 8 2B module telemetry (0 = Off, 1 = On) 9 2C module telemetry (0 = Off, 1 = On) 10 3A module telemetry (0 = Off, 1 = On) 11 3B module telemetry (0 = Off, 1 = On) 12 3C module telemetry (0 = Off, 1 = On) 13 AA relay telemetry (0 = Off, 1 = On) 14 Reserved 15 Reserved Digital Input Status Word 87
BIT DESCRIPTION 0 H Interface module (0 = Off, 1 = On) 1 J Interface module (0 = Off, 1 = On) 2 1A module (0 = Off, 1 = On) 3 LB logic input (0 = Off, 1 = On) 4 LA logic input (0 = Off, 1 = On) 5 1B module telemetry (0 = Off, 1 = On) 6 1C module (0 = Off, 1 = On) 7 2A module (0 = Off, 1 = On) 8 2B module (0 = Off, 1 = On) 9 2C module (0 = Off, 1 = On) 10 3A module (0 = Off, 1 = On) 11 3B module (0 = Off, 1 = On) 12 3C module (0 = Off, 1 = On) 13 Reserved
8-2 2408f & 2404f PROFIBUS Communications Handbook


)6 )6 Loop break time 0: Off 83
6@0 6@0 Current segment type 0: End 1: Ramp (Rate) 2: Ramp (Time to target) 3: Dwell 4: Step 5: Call
O! O! Enable diagnostic messages 0: No Diagnostics 1: Diagnostics
!6 !6 Segment time remaining in secs 36
5 5 Adaptive tune enable 0: No Adaotive Tune 1: Tune
/96D /96D Logic 1 output (current program) 0: Off (applies to all 8 logic outputs) 1: On (applies to all 8 logic o/ps)
Automatic droop compensation (manual reset) 0: Manual reset 1: Calculated
!D !D Flash active segment in lower display


) ) Select setpoint 0: SP1 1: SP2
7 7 Current PID set (read only if gain scheduling is selected) 0: Set 1 1: Set 2
6 6 Derivative time PID1 0: Off 9
# # Cutback high PID1 0: Auto 18
) ) Cutback low PID1 0: Auto 17
)B5 )B5 Local or remote setpoint select 0: Local 1: Remote
5 )D 5 )D Relative cool gain PID1 19
6 6 Derivative time PID2 0: Off 51
# # Cutback high PID2 0: Auto 118
) ) Cutback low PID2 0: Auto 117
0 ) 0 ) Setpoint 1 low limit 112
0 # 0 # Setpoint 1 high limit 111
0 D) 0 D) Setpoint 2 low limit 114
0 D# 0 D# Setpoint 2 high limit 113
)/D) )/D) Local setpoint trim low limit 67
)/D# )/D# Local setpoint trim high limit 66
#D6@ #D6@ Holdback type for sp rate limit 0: Off 1: Low 2: High 3: Band
# # Holdback value for srtpoint rate limit


O)6 O)6 Input 1 filter time constant 0: Off 101
)6D )6D Input 2 filter time constant 0: Off 103
0;DO0 0;DO0 Select input 1 or input 2 288
)/D 0 )/D 0 Switchover transition region low 287
/.6D# /.6D# Heat output minimum on time 0: Auto 45
/.6D /.6D Cool output minimum on time 0: Auto 89
) ) User calibration enable 0: Factory 1: User
)D )D Selected calibration point 0: None 1: Input 1 low 2: Input 1 high 3: Input 2 low 4: Input 2 high
D0 D0 On/Off Sensor Break Output Power 0: -100% 1: 0% 2: 100%
D D Input 1 calibration offset 141
D D Input 2 calibration offset 142

Tag Addresses 2408f & 2404f PROFIBUS Communications Handbook
Controller I/O Tab Tag
Display Parameter Description Address
Display Parameter Description Addres
DC Output 1A Telemetry 12694 DC Output 2A Telemetry 12758
O0 O0 Configuration of lower readout display 0: Standard 1: Load current 2: Output power 3: Status 4: Program time 5: None 6: Valve position 7: Process value 2 8: Ratio setpoint 9: Selected program number 10: Remote setpoint
DC Output 3A Telemetry 12822
BCD Input Value 96
Display Parameter Description Address
Instrument Mode 199 Instrument Version Number 107
Slave Instrument Target Setpoint
)/!D) )/!D) PV minimum 134
Slave Instrument Ramp Rate 93 Slave Instrument Sync 94 Remote SRL Hold 95 CNOMO Manufacturers ID 121 Remote Parameter 151 Error Logged Flag 73 Ramp Rate Disable 78 Maximum Input Value 548 Minimum Input Value 549 Holdback Disable 278 All User Interface Keys Disable 279
)/!D# )/!D# PV maximum 133
)/!D )/!D PV mean value 135
)/!D6 )/!D6 Time PV above threshold level 139
5 D) 5 D) Logging reset 0: Not reset 1: Reset
,6 ,6 Maximum Control Task Time (Processor utilisation factor)
=D0 =D0 Working output 4
5 5 PDSIO SSR status 0: Good 1: Load fail 2: Open 3: Heater fail 4: SSR fail 5: Sn fail
D0 D0 Feedforward component of output
0 Proportional component of output
N 0 N 0 Integral component of output 55
0 0 Derivative component of output 116
:0 :0 VP motor calibration state 0: Start 1: Waiting 2: Open valve 3: BLUp/InDn 4: Ttup 5: Overshoot 6: InUp/BLDn 7: TT down 8: Open 9: Low lim 10: Stopping 11: Raise 12: Inert up 13: Lower 14: Low lim 15: Stopping 16: Lower 17: InDn/BL 99: Abort
8-6 2408f & 2404f PROFIBUS Communications Handbook
s · Instrument Ident 122

2408f & 2404f PROFIBUS Communications Handbook Tag Addresses
Display Custom Linearisation Tab
Display Parameter Description Address
O. O. Custom linearisation input 1 601
;)D ;)D Display value corresponding to input 1
O. O. Custom linearisation input 2 602
;)D ;)D Display value corresponding to input 2
O. O. Custom linearisation input 3 603
;)D ;)D Display value corresponding to input 3
//) //) Type of cooling 0: Linear 1: Oil 2: Water 3: Fan
O. O. Custom linearisation input 4 604
;)D ;)D Display value corresponding to input 4
O. O. Custom linearisation input 5 605
;)D ;)D Display value corresponding to input 5
6OD6 6OD6 Integral and Derivative time units 0: Seconds 1: Minutes 2: Hours
O. O. Custom linearisation input 6 606
;)D ;)D Display value corresponding to input 6
O. O. Custom linearisation input 7 607
;)D ;)D Display value corresponding to input 7
,B ,B Front panel Auto/Manual button 0: Enabled 1: Disabled
O. O. Custom linearisation input 8 608
;)D ;)D Display value corresponding to input 8
5B$ 5B$ Front panel Run/Hold button 0: Enabled 1: Disabled
0=5 0=5 Power feedback enable 0: Off 1: On
=D6 =D6 Feed forward type 0: None 1: Power feedforward 2: Setpoint feedforward 3: PV feedforward
0D65 0D65 Manual/Auto transfer PD control 0: No 1: Yes
D0 D0 Decimal places in displayed value 0: nnnn 1: nnn.n 2: nn.nn
5D6 5D6 Sensor break output 0: Sensor break (go to set value) 1: Hold (output)
0 0 Forced manual output 0: No 1: Trac (returns to last value) 2: Step (steps to forced output level)
5."D) 5."D) Setpoint Min. (Low range limit) 11
5."D# 5."D# Setpoint Max. (High range limit) 12
BCD input function 0: None 1: Select program number 2: Select SP number
!$ !$ Gain schedule enable 0: No (disabled) 1: Yes (enabled)

Tag Addresses 2408f & 2404f PROFIBUS Communications Handbook
Display Setpoint Configuration
O.16 O.16 Input type 0: J Type 1: K Type 2: L Type 3: R Type 4: B Type 5: N Type 6: T Type 7: S Type 8: PL 2 9: Custom (factory) * 10: RTD * 11: Linear mV (+/- 100mV) 12: Linear V (0-10V) 13: Linear mA 14: Square root V 15: Square root mA 16: Custom mV 17: Custom V 18: Custom mA
.0 .0 Number of setpoints 521
5,0D; 5,0D; Setpoint rate limit units 0: /Sec 1: /Min 2: /Hour
5,6 5,6 Remote setpoint configuration 0: None 1: Remote setpoint 2: Remote setpoint + local trim 4: Remote trim + local setpoint
% % Cold junction compensation 0: Auto 1: 0oC 2: 45oC 3: 50oC 4: Off
) ) Alarm 1 type 0: Off 1: Full scale low 2: Full scale high 16: Deviation band 17: Deviation high 18: Deviation low 34: Load current low 35: Load current high 36: Input 2 full scale low 37: Input 2 full scale high 38: Working output low 39: Working output high 40: Working setpoint low 41: Working setpoint high
N,1 N,1 Sensor break impedance 0: Off (disabled linear. inputs only) 1: Auto 2: Hi (> 5K) 3: Hi Hi (>15K)
O.1D) O.1D) Input value low 12307
O.1D$ O.1D$ Input value high 12306
;)D) ;)D) Displayed reading low 12303
;)D# ;)D# Displayed reading high 12302
) ) Alarm 2 type (types as alarm 1) 537
)6$ )6$ Latching (types as alarm 1) 541
)/ )/ Blocking (types as alarm 1) 545
) ) Alarm 3 type (types as alarm 1) 538
)6$ )6$ Latching (types as alarm 1) 542
)/ )/ Blocking (types as alarm 1) 546
) ) Alarm 4 type (types as alarm 1) plus 64: Rate of change
)6$ )6$ Latching (types as alarm 1) 543
)/ )/ Blocking (types as alarm 1) 547
8-8 2408f & 2404f PROFIBUS Communications Handbook

2408f & 2404f PROFIBUS Communications Handbook Tag Addresses
Display Programmer Configuration
9. 9. Input functions 192: None 193: Manual mode select 194: Remote setpoint select 195: Setpoint 2 select 196: PID set 2 select 197: Integral hold 198: One-shot self tune enable 199: Adaptive tune enable 200: Acknowledge alarms 201: Select full access level 202: Keylock 203: Up button 204: Down button 205: Scroll button 206: Page button 207: Run 208: Hold 209: Run/Hold 210: Reset 211: Skip 212: Holdback enabled 213: Least significant BCD digit 214: 2nd digit 215: 3rd digit 216: 4th digit 217: 5th digit 218: Most significant digit 219: Setpoint rate limit enable 220: Prog. waits at end of segment 223: Run/Hold 224: Reset/Run 225: Standby 226: PV select 227: Advance to end of segment 240: Amps
0=5D 0=5D Power fail recovery 0: Ramp back 1: Reset 2: Continue
5:/ 5:/ Servo 0: Servo to PV 1: Servo to SP
/96 /96 Programmable event outputs Version 1 controllers: 0: None 3: Three 6: Six 8: Eight Versions 2 and 3 controllers: 0: None 1: Eight
@- @- Synchronisation of programs 0: No 1: Yes
Maximum Number Of Segments 211
9. 9. Input functions, as ) above 12419
;)D) ;)D) Low scalar 12431
;)D# ;)D# High scalar 12430

Tag Addresses 2408f & 2404f PROFIBUS Communications Handbook
O O Module identity 12480
. . Sense of output 0: Normal 1: Inverted
Summary of AA configuration 12486 Program summary OP AA configuration
;)D) ;)D) % PID or Retran value giving min. o/p
;)D# ;)D# % PID or Retran value giving max. o/p
5 5 Comms Resolution 0: Full 1: Integer
96D) 96D) Minimum electrical output 12689
96D# 96D# Maximum electrical output 12688
. . Sense of output 0: Normal 1: Inverted
O O Module Identity 0: None 8: PDSIO output 9: PDSIO input
Summary output 1A configuration 12678
DC output 1A telemetry parameter 12694
;)D) ;)D) Retransmitted Low Scalar 12623
Program summary output 1A config
;)D# ;)D# Retransmitted High Scalar 12622
9. 9. Module Function For O = 1 128: None 129: PDSIO SP retransmission 130: PDSIO PV retransmission 131: PDSIO OP retransmission 133: PDSIO SP retrans. no holdback For O = 0O 96: None 97: PDSIO setpoint input
O O Module 1B identity 12673
9. 9. Module 1B function 12676
. . Sense of output (nor/inv as1A) 12682
Summary of 1B configuration 12679
Summary program O/P 1B config. 12696
1C Display Output 1C Configuration Tab
O O Module identity 0: None 1: Relay output 2: DC output non-isolated 3: Logic/PDSIO output 4: Logic input 5: Triac output 10: Error/Bad module 11: DC retransmission 12: DC output isolated
O O Module 1C identity 12674
9. 9. Module 1C function 12677
;)D) ;)D) Module 1C value giving min output 12699
;)D# ;)D# Module 1C value giving max output 12698
96D) 96D) Module 1C Minimum electrical output
96D# 96D# Module 1C Maximum electrical output
. . Sense of output (nor/inv as 1A) 12683
Summary of 1C configuration 12680
9. 9. Module function For O = 5 )@ )/! or 5
Summary program O/P 1C config. 12697
8-10 2408f & 2404f PROFIBUS Communications Handbook

2408f & 2404f PROFIBUS Communications Handbook Tag Addresses
2B Display Output 2B Configuration Tab
O O Module identity 0: None 1: Relay output 2: DC output non-isolated 3: Logic/PDSIO output 4: Logic input 5: Triac output 10: Error/Bad module 11: DC retransmission 12: DC output isolated 13: Transmitter power supply 14: Pot input (valve position)
O O Module 2B identity 12737
9. 9. Module 2B function 12740
. . Sense of output (nor/inv as 2A) 12746
Summary of 2B configuration 12743
Summary program O/P 2B config. 12760
9. 9. Module function For O = 5 )@ )/! or 5 0: None 1: Digital output 2: Heating output 3: Cooling output 5: Close motorised valve For O = D5 or D0 16: None 17: Heating output 18: Cooling output 19: Retransmission of PV 20: Retransmission of SP 21: Retransmission of error 22: Retransmission of OP power For O = 0/6 160: None 161: Remote setpoint 162: Feedforward input 163: Remote OP power high 164: Remote OP power low 165: Valve position
O O Module 2C identity 12738
9. 9. Module 2C function 12741
. . Sense of output (nor/inv as 2A) 12747
Summary of 2C configuration 12744
Summary program O/P 2C config. 12761
;)D) ;)D) % PID or Retran low value 12751
;)D) ;)D) Potentiometer input low scalar 12763
;)D# ;)D# % PID or Retran high value 12750
;)D# ;)D# Potentiometer input high scalar 12762
96D) 96D) Minimum electrical output 12753
96D# 96D# Maximum electrical output 12752
. . Sense of output 0: Normal 1: Inverted
Summary output 2A configuration 12742
Program summary output 2A conf. 12759

Tag Addresses 2408f & 2404f PROFIBUS Communications Handbook
. . Sense of output 0: Normal 1: Inverted
Summary output 3A configuration 12806
O O Module identity 0: None 1: Relay output 2: DC output non-isolated 3: Logic/PDSIO output 4: Logic input 5: Triac output 6: DC input 10: Error/Bad module 11: DC retransmission 12: DC output isolated 13: Transmitter power supply 14: Pot input (valve position)
Program summary output 3A config
O O Module 3B identity 12801
9. 9. Module 3B function 12804
. . Sense of output (nor/inv as 3A) 12810
9. 9. Module function For O = 5 )@ )/! or 5 0: None 1: Digital output 2: Heating output 3: Cooling output For O = D5 or D0 16: None 17: Heating output 18: Cooling output 19: Retransmission of PV 20: Retransmission of SP 21: Retransmission of error 22: Retransmission of OP power For O = 0/6 160: None 161: Remote setpoint 162: Feedforward input 163: Remote OP power high 164: Remote OP power low 165: Valve position For O = DO0 32: None 33: Remote setpoint 34: Feedforward input 35: Remote output power max. 36: Remote output power min. 37: PV = highest of ip1 or ip2 38: PV = lowest of ip1 or ip2 39: Derived function 40: Select ip1 or ip2 41: Transition of control - ip1-ip2
Summary of 3B configuration 12807
Summary program O/P 3B config. 12824
O O Module 3C identity 12802
9. 9. Module 3C function 12805
. . Sense of output (nor/inv as 3A) 12811
Summary of 3C configuration 12808
Summary program O/P 3C config. 12825
O O Module identity 0: None 1: Relay output
O.06 O.06 input type (input 2) Refer to input configuration for all types + #ON.
;)D) ;)D) Input module 4A low value 12879
;)D# ;)D# Input module 4A high value 12878
% % Cold junction compensation (ip 2) Refer to input config. for types
96D) 96D) Minimum electrical output 12881
96D# 96D# Maximum electrical output 12880
O,1 O,1 Sensor break impedance (input 2) Refer to input config. for types
. . Sense of output (nor/inv as 3A) 12873
Summary output 4A configuration 12870
O.1D) O.1D) Input value low 12819
Program summary output 4A config
O.1D# O.1D# Input value high 12818
;)D) ;)D) Input module 3A low value 12829
;)D# ;)D# Input module 3A high value 12828
;)D) ;)D) Module 3A low value 12815
;)D) ;)D) Potentiometer input 3A low scalar 12827
;)D# ;)D# Module 3A high value 12814
;)D# ;)D# Potentiometer input 3A high scalar 12826
D0 D0 Access Mode Password 514
. D0 . D0 Configuration Level Password 515
96D) 96D) Minimum electrical output 12817
96D# 96D# Maximum electrical output 12816
8-12 2408f & 2404f PROFIBUS Communications Handbook

2408f & 2404f PROFIBUS Communications Handbook Tag Addresses
Program Data Organisation
A 2400f series controller can contain multiple “programs”, each consisting of up to 16 segments. The data for each program starts at the base tag address given by the following table:
Program Base Address (Decimal)
Base Address (Hex) Program 0 (Currently Running Program - changes permitted only in hold, and are not permanently stored)
Program 1 8328 2088 Program 2 8464 2110 Program 3 8600 2198 Program 4 8736 2220
The parameters used to describe a program are organised into 17 blocks, each of 8 words in length, starting at the base address for the program. There is one block for general program data, such as the units to be used for ramp and dwell times, and 16 further blocks for the segment data itself. To obtain the tag address of the data block for a given program, add the block offset given in the next table to the program
Program General Data 0 0 Segment 1 8 8 Segment 2 16 10 Segment 3 24 18 Segment 4 32 20 Segment 5 40 28 Segment 6 48 30 Segment 7 56 38 Segment 8 64 40 Segment 9 72 48 Segment 10 80 50 Segment 11 88 58 Segment 12 96 60 Segment 13 104 68 Segment 14 112 70 Segment 15 120 78 Segment 16 128 80
8192 2000 · Contents Offset (Decimal) · Offset (Hex)

Tag Addresses 2408f & 2404f PROFIBUS Communications Handbook
The offsets of each parameter within the program general data block is given by the next table:
Address Offset Parameter 0 HoldbackType
Program segment data is specified using 8 tag addresses, with the contents varying depending on the type of the segment. The format per segment is detailed in the following table, which gives the offset from the start of a segment data block for each item.
Address Offset Segment Types STEP DWELL RAMP RATE
CALL END
0 Segment Type Segment Type Segment Type Segment Type Segment Type Segment Type 1 Target Setpoint
Target Setpoint 2 Duration Rate Duration 3 Program Number
4 Logic O/P’s Logic O/P’s Logic O/P’s Logic O/P’s Call Cycles Logic O/P’s 5 6 7
Program 1, Segment 4, Segment Type = 8328 + 32 + 0 = 8360 (20A8 Hex) Program 2, Holdback Value = 8464 + 0 + 1 = 8465 (2111 Hex) Program 4 Segment 16, End Type = 8872 + 128 + 3 = 9003 (232B Hex)
This has the tag address 64 in 2400f controllers.
Controller Display Parameter Description 6@0 Current Segment Type 0: End 1: Ramp (Rate) 2: Ramp (Time to target) 3: Dwell 4: Step 5: Call .D6 End Segment Type 0: Reset 1: Indefinate Dwell 2: Set Output
Controller Display Parameter Description # Holdback Type 0: None 1: Low 2: High 3: Band =)D8 Dwell Units 0: Seconds 1: Minutes 2: Hours 5,0D8 Ramp Units 0: Seconds 1: Minutes 2: Hours
8-14 2408f & 2404f PROFIBUS Communications Handbook
Target Setpoint · End Type

2408f & 2404f PROFIBUS Communications Handbook Office Addresses
UK SALES OFFICE Eurotherm Controls Limited Faraday Close, Durrington Worthing West Sussex BN13 3PL Telephone Sales: (01903) 695888 Technical: (01903) 695777 Service: (01903) 695444 Fax (01903) 695666
email http://www.eurotherm.co.uk
Eurotherm Controls Inc 11485 Sunset Hills Rd. Reston, Virginia 20190-5286 USA website; http://www.eurotherm.com/controls.htm Telephone 703-471-4870 Fax 703-787-3436 email info@controls.eurotherm.com
2408f and 2404f PROFIBUS Communications Handbook B1
Pages referenced in this manual — manufacturer, support and downloads.
What the fault codes shown on the display mean and how to clear them.
| Code | Meaning | Fix | |
|---|---|---|---|
| 0 1 2 | Invalid Tag Number Read Only Parameter Value out of range | p.17 |
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.