This manual covers the items required for installing and connecting the MITSUBISHI CNC E70 Series. Read this manual thoroughly and understand the product's functions and performance before starting to use. This manual is written on the assumption that all optional functions are added, but the actually delivered device may not have all functions. The unit names, cable names and various specifications are subject to change without notice. Please confirm these before placing an order.
This manual notes a reference chapter as "Chapter: Section: Paragraph". (Example) For "1.3.1 List of Units": "System Configuration: List of Configuration: List of Units" ("1.3.1 List of Units" included in "1.3 List of Configuration" of "1 System Configuration")
For items described as "Restrictions" or "Usable State" in this manual, the instruction manual issued by the machine
tool builder takes precedence over this manual.
Items that are not described in this manual must be interpreted as "not possible".
This manual is written on the assumption that all optional functions are added. Confirm the specifications issued by
the machine tool builder before starting to use.
Refer to the Instruction Manual issued by each machine tool builder for details on each machine tool.
Some screens and functions may differ depending on each NC system (or version), and some functions may not be
possible. Please confirm the specifications before starting to use.
The numerical control unit is configured of the control unit, display unit, operation board (keyboard unit, operation panel I/O unit), servo drive unit, spindle drive unit, power supply unit + driver, servomotor, spindle motor, etc.
In this manual, the following items are generically called "controller". - Control unit - Display unit - operation board (keyboard unit, operation panel I/O unit) - Numerical control unit peripheral devices (input/output unit, safety unit)
In this manual, the following items are generically called "drive unit". - Servo drive unit - Spindle drive unit - Power supply unit + driver
In this manual, the following items are generically called "motor". - Servo motor - Spindle motor

Refer to the following documents. M700V/M70V/E70 Series PLC Interface Manual IB-1500920 MDS-DM2 Series Specifications Manual IB-1501136 MDS-DM2 Series Instruction Manual IB-1501139 MDS-DJ Series Specifications Manual IB-1501130 MDS-DJ Series Instruction Manual IB-1501133 Safety Handbook (Original Instructions) IB-1501025

Always read this manual and enclosed documents before installation, operation, maintenance and inspection to ensure correct usage. Thoroughly understand the basics, safety information and precautions of the devices before using. This manual classifies the safety precautions into "DANGER", "WARNING" and "CAUTION".

When the user could be subject to imminent fatalities or serious injuries if handling is mistaken.
When the user could be subject to fatalities or serious injuries if handling is mistaken.
When the user could be subject to injuries or the property could be damaged if handling is mistaken.
All the items are important and must always be observed.
The following signs indicate prohibition and compulsory.

This sign indicated a thing that is pompously (must do).
The meaning of each pictorial sing is as follows.


Mitsubishi CNC is designed and manufactured solely for applications to machine tools. Do not use this product in any applications other than those specified as above, especially those which are substantially influential on the public interest or which are expected to have significant influence on human lives or properties. We will review the acceptability of the abovementioned applications, if the customer agrees not to require a specific quality for a specific application. Please contact us for consultation.
Do not open or remove the front cover while the power is ON or during operation. The high voltage terminals and charged sections will be exposed, and this could result in electric shocks. Do not remove the front cover even when the power is OFF, except for the wiring works or periodic inspections. The inside of the controller and drive unit are charged, and this could result in electric shocks. Always wait at least 15 minutes after turning the power OFF. Then, check the voltage with a tester, etc., before wiring works, inspections or connecting with peripheral devices. Failure to observe this could result in electric shocks. Earth ground the controller, drive unit and motor according to the local laws. (In Japan, ground the 200V Series input products with Class C or higher protective grounding and the 400V Series input with Class D or higher protective grounding.) All wiring works, maintenance and inspections must be carried out by a qualified technician. Failure to observe this could result in electric shocks. Contact your nearby Service Center or Service Station for replacing parts and servicing.
Wire the controller, drive unit and motor after installation. Failure to observe this could result in electric shocks.
Do not operate the switches with wet hands. Failure to observe this could result in electric shocks.
Do not damage, apply excessive stress, place heavy things on or sandwich the cables. Failure to observe this could result in electric shocks.
Insulate the power lead using a fixed terminal block. Failure to observe this could result in electric shocks.
Install the controller, drive unit, motor and regenerative resistor on non-combustible material. Installation directly on or near combustible materials could result in fires.
If any malfunction in the unit is observed, shut off the power at the unit’s power supply side. Continuous flow of large current could result in fires. Install an appropriate no fuse breaker (NFB) and contactor (MC) on the power input section of the drive unit and configure the sequence that shuts the power off upon drive unit’s emergency stop or alarm. When a breaker is shared for multiple power supply units, the breaker may not function upon short-circuit failure in a small capacity unit. Do not share a breaker for multiple units as this is dangerous.
Incorrect wiring and connections could cause the devices to damage or burn.
For Safe Use

When transporting or installing a built-in IPM spindle or linear servomotor, be careful so that your hand or property will not be trapped in the motors or other metal objects. Also keep the devices with low magnetic tolerance away from the product.
Do not apply voltages to the connectors or terminals other than voltages indicated in the connection manual for the controller or specifications manual for the drive unit. Failure to observe this could cause bursting, damage, etc. Incorrect connections could cause the devices to rupture or damage, etc. Always connect the cables to the indicated connectors or terminals.
Incorrect polarity (+ -) could cause the devices to rupture or damage, etc.
Persons wearing medical devices, such as pacemakers, must stay away from this unit. The electromagnetic waves could adversely affect the medical devices. Fins on the rear of the unit, regenerative resistor and motor, etc., will be hot during operation and for a while after the power has been turned OFF. Do not touch or place the parts and cables, etc. close to these sections. Failure to observe this could result in burns.
Do not enter the machine’s movable range during automatic operation. Keep your hands, feet or face away from the spindle during rotation.

(1) Transportation and installation
Correctly transport the products according to the mass.
Use motor’s suspension bolts to transport the motor itself. Do not use it to transport the motor after installation onto the machine.
Do not stack the products exceeding the indicated limit.
Do not hold the cables, shaft or detector when transporting the motor.
Do not transport the controller or drive unit by suspending or holding the connected wires or cables.
Do not hold the front cover when transporting the unit, or the front cover could come off, causing the unit to drop.
Install on a non-combustible place where the unit’s or motor’s mass can be withstood according to the instruction manual. The motor does not have a complete water-proof (oil-proof) structure. Do not allow oil or water to contact or enter the motor. Prevent the cutting chips from being accumulated on the motor as they easily soak up oil. When installing the motor facing upwards, take measures on the machine side so that gear oil, etc., will not enter the motor shaft.
Do not remove the detector from the motor. (The detector installation screw is treated with sealing.)
Do not allow foreign matters, especially, conductive foreign matters such as screws or metal chips, or combustible foreign matters such as oil, to enter the controller, drive unit or motor. Failure to observe this could result in rupture or damage.
Do not get on the product or place heavy objects on it.
Provide prescribed distance between the controller/drive unit and inner surface of the control panel/other devices.
Do not install or operate the controller, drive unit or motor that is damaged or has missing parts.
Take care not to cut hands, etc. with the heat radiating fins or metal edges.
Do not block the intake/outtake ports of the motor with the cooling fan.
Install the controller’s display section and operation board section on the spot where cutting oil will not reach.
The controller, drive unit and motor are precision devices, so do not drop or apply thumping vibration and strong impacts on them.
Hard disk unit is a precision device, so do not drop or apply strong impacts on it.
Store and use the units according to the environment conditions indicated in each specifications manual.
Securely fix the motor to the machine. The motor could come off during operation if insecurely fixed.

Always install the motor with reduction gear in the designated direction. Failure to observe this could result in oil leaks. Always install a cover, etc., over the shaft so that the rotary section of the motor cannot be touched during motor rotation. When installing a coupling to the servomotor shaft end, do not apply impacts by hammering, etc. The detector could be damaged. Use a flexible coupling when connecting with a ball screw, etc., and keep the shaft core deviation smaller than the tolerable radial load of the shaft. Do not use a rigid coupling as an excessive bending load will be applied on the shaft and could cause the shaft to break.
Do not apply a load exceeding the tolerable level onto the motor shaft. The shaft or bearing could be damaged.
Before using this product after a long period of storage, please contact the Mitsubishi Service Station or Service Center. Following the UN recommendations, battery units and batteries should be transported based on the international regulations such as those determined by International Civil Aviation Organization (ICAO), International Air Transport Association (IATA), International Maritime Organization (IMO) and U.S. Department of Transportation (DOT).

(2) Items related to wiring
Correctly wire this product. Failure to observe this could result in motor runaway, etc.
Do not install a phase advancing capacitor, surge absorber or radio noise filter on the output side of the drive unit.
Correctly connect the output side (terminal U, V, W). The motor will not run properly if incorrectly connected.
Always install an AC reactor per each power supply unit.
Always install an appropriate breaker per each power supply unit. A breaker cannot be shared for multiple power supply units.
Do not directly connect a commercial power supply to the motor. Failure to observe this could result in faults.
When using an inductive load such as relays, always connect a diode in parallel to the load as a noise countermeasure. When using a capacitive load such as a lamp, always connect a protective resistor serially to the load to suppress rush currents. Do not mistake the direction of the surge absorption diode to be installed on the DC relay for the control output signal. If mistaken, the signal will not be output due to fault in the drive unit, and consequently the protective circuit, such as emergency stop, could be disabled.
(24VDC) (24VDC)
RA RA
Do not connect or disconnect the cables between units while the power is ON.
Do not connect or disconnect the PCBs while the power is ON.
Do not pull the cables when connecting/disconnecting them.
Securely tighten the cable connector fixing screw or fixing mechanism. The motor could come off during operation if insecurely fixed.
Always treat the shield cables indicated in the Connection Manual with grounding measures such as cable clamps.
Separate the signal wire from the drive line or power line when wiring.
Use wires and cables whose wire diameter, heat resistance level and bending capacity are compatible with the system.
Ground the device according to the requirements of the country where the device is to be used.
Wire the heat radiating fins and wires so that they do not contact.
When using the RS-232C device as a peripheral device, caution must be paid for connector connection/ disconnection. Always use a double-OFF type AC power supply switch on the device side, and connect/disconnect the connector with the AC power supply on the device side OFF.


Check and adjust programs and each parameter before starting operation. Failure to observe this could result in unpredictable operations depending on the machine.
Do not make drastic adjustments or changes as the operation could become unstable.
Install an external emergency stop circuit so that the operation can be stopped and the power turns OFF immediately when unforeseen situation occurs. A contactor, etc., is required in addition to the shutoff function mounted in the controller. Turn OFF the power immediately if any smoke, abnormal noise or odor is generated from the controller, drive unit or motor.
Only a qualified technician may disassemble or repair this product.
Do not alter.
Use a noise filter, etc. to reduce the effect of electromagnetic disturbances in the case where electromagnetic disturbances could adversely affect the electronic devices used near the drive unit. Use the drive unit, motor and each regenerative resistor with the designated combination. Failure to observe this could result in fires or faults. The combination of the motor and drive unit that can be used is determined. Be sure to check the models of motor and drive unit before test operation. The brakes (electromagnetic brakes) mounted in the servomotor are used for the purpose of holding, and must not be used for normal braking. Also, do not run the motor with the motor brake applied. Motor brake is used for the purpose of holding.
For the system running via a timing belt, install a brake on the machine side so that safety can be ensured.
Be sure to confirm SERVO OFF (or READY OFF) when applying the electromagnetic brake. Also, be sure to confirm SERVO ON prior to releasing the brake.
When using the DC OFF type electromagnetic brake, be sure to install a surge absorber on the brake terminal.
Do not connect or disconnect the cannon plug while the electromagnetic brake’s power is ON. The cannon plug pins could be damaged by sparks. After changing programs/parameters, or after maintenance/inspection, always carry out a test operation before starting actual operation. Use the power that are complied with the power specification conditions (input voltage, input frequency, tolerable instantaneous power failure time) indicated in each specifications manual. When making detector cables, do not mistake connection. Failure to observe this could result in malfunction, runaway or fire.
(3) Adjustments · (4) Usage

Use a motor with electromagnetic brakes or establish an external brake mechanism for the purpose of holding; this serves as countermeasures for possible hazardous situation caused by power failure or product fault.
Shut off with motor brake control output
Shut off with CNC brake control PLC output
Use a double circuit structure for the electromagnetic brake’s operation circuit so that the brakes will activate even when the external emergency stop signal is issued.
The machine could suddenly restart when the power is restored after an instantaneous power failure, so stay away from the machine. (Design the machine so that the operator safety can be ensured even if the machine restarts.)
To secure the absolute position, do not shut off the servo drive unit’s control power supply when its battery voltage drops (warning 9F) in the servo drive unit side. If the battery voltage drop warning alarm occurs in the controller side, make sure to back up the machining programs, tool data and parameters, etc. with the input/output device before replacing the battery. Depending on the level of voltage drop, memory loss could have happened. In that case, reload all the data backed up before the alarm occurrence.
(5) Troubleshooting · Motor · Electro- magnetic brake

(6) Maintenance, inspection and part replacement
Periodically back up the programs, tool data and parameters to avoid potential data loss. Also, back up those data before maintenance and inspections. When replacing the battery on the controller side, the machining programs, tool data and parameters should be backed up with the input/output device beforehand. In case the memory is damaged in replacing the batteries, reload all the data backed up before replacing the battery.
The electrolytic capacitor’s capacity will drop due to deterioration. To prevent secondary damage due to capacitor’s faults, Mitsubishi recommends the electrolytic capacitor to be replaced approx. every five years even when used in a normal environment. Contact the Service Center or Service Station for replacements.
Do not perform a megger test (insulation resistance measurement) during inspection.
Do not replace parts or devices while the power is ON.
Do not short-circuit, charge, overheat, incinerate or disassemble the battery.
There may be a unit filled with substitute Freon in the heat radiating fins of the 37kW or smaller unit. Be careful not to break the heat radiating fins during maintenance or replacement.
Take the batteries and backlights for LCD, etc., off from the controller, drive unit and motor, and dispose of them as general industrial wastes.
Do not alter or disassemble controller, drive unit, or motor.
Collect and dispose of the spent batteries and the backlights for LCD according to the local laws.
To explain the details, drawings given in the instruction manual, etc., may show the unit with the cover or safety partition removed. When operating the product, always place the cover or partitions back to their original position, and operate as indicated in the instruction manual, etc.
(7) Disposal · (8) General precautions



The following two laws will apply when disposing of this product. Considerations must be made to each law. The following laws are in effect in Japan. Thus, when using this product overseas, the local laws will have a priority. If necessary, indicate or notify these laws to the final user of the product.
(1) Requirements for "Law for Promotion of Effective Utilization of Resources"
(a) Recycle as much of this product as possible when finished with use. (b) When recycling, often parts are sorted into steel scraps and electric parts, etc., and sold to scrap
contractors. Mitsubishi recommends sorting the product and selling the members to appropriate contractors.
(2) Requirements for "Law for Treatment of Waste and Cleaning"
(a) Mitsubishi recommends recycling and selling the product when no longer needed according to item
(1) above. The user should make an effort to reduce waste in this manner. (b) When disposing a product that cannot be resold, it shall be treated as a waste product. (c) The treatment of industrial waste must be commissioned to a licensed industrial waste treatment contractor, and appropriate measures, including a manifest control, must be taken. (d) Batteries correspond to "primary batteries", and must be disposed of according to local disposal
laws.



(Note) This symbol mark is for EU countries only. This symbol mark is according to the directive 2006/66/EC Article 20 Information for end- users and Annex II.
Your MITSUBISHI ELECTRIC product is designed and manufactured with high quality materials and components which can be recycled and/or reused. This symbol means that batteries and accumulators, at their end-of-life, should be disposed of separately from your household waste. If a chemical symbol is printed beneath the symbol shown above, this chemical symbol means that the battery or accumulator contains a heavy metal at a certain concentration. This will be indicated as follows: Hg: mercury (0,0005%), Cd: cadmium (0,002%), Pb: lead (0,004%) In the European Union there are separate collection systems for used batteries and accumulators. Please, dispose of batteries and accumulators correctly at your local community waste collection/ recycling centre.
Please, help us to conserve the environment we live in!



Trademarks MELDAS, MELSEC, EZSocket, EZMotion, iQ Platform, MELSOFT, GOT, CC-Link, CC-Link/LT and CC-Link
IE are either trademarks or registered trademarks of Mitsubishi Electric Corporation in Japan and/or other
countries.
Ethernet is a registered trademark of Xerox Corporation in the United States and/or other countries.
Microsoft® and Windows® are either trademarks or registered trademarks of Microsoft Corporation in the
United States and/or other countries.
CompactFlash and CF are either trademarks or registered trademarks of SanDisk Corporation in the United
States and/or other countries.
UNIX is a registered trademark of The Open Group in the United States and/or other countries.
Intel® and Pentium® are either trademarks or registered trademarks of Intel Corporation in the United States
and/or other countries.
Other company and product names that appear in this manual are trademarks or registered trademarks of the
respective companies.



の使用をお願いいたします。
Handling of our product
(English) This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
( 한국어/Korean) 이 기기는 업무용(A 급) 전자파적합기기로서 판매자 또는 사용자는 이 점을 주의하시기 바라며 가정외의 지역에 서 사용하는 것을 목적으로 합니다.
( 日本語/Japanese)





1.1 System Basic Configuration Drawing

(Note 1) Control unit is mounted on the back side of the display unit. (Note 2) Operation panel I/O unit is mounted on the back side of the keyboard unit. (Note 3) For the drive unit configuration, refer to the Instruction Manual of the drive unit you use.

1.2 General Connection Diagram

Dotted lines indicate the sections prepared by the machine tool builder.
The name with brackets < > indicates the cable for the unit.
(Note 1) For information on how to connect the drive unit, refer to the drive unit's manual. (Note 2) For a connection of the MITSUBISHI CNC Machine Operation Panel, refer to "Connection: Connection of MITSUBISHI CNC Machine Operation Panel" to be described.

[Analog Spindle Configuration]

Dotted lines indicate the sections prepared by the machine tool builder.
The name with brackets < > indicates the cable for the unit.
(Note 1) For information on how to connect the drive unit, refer to the drive unit's manual. (Note 2) For a connection of the MITSUBISHI CNC Machine Operation Panel, refer to "Connection: Connection of MITSUBISHI CNC Machine Operation Panel" to be described.

1.3 List of Configuration
1.3.1 List of Units
Classification Type Components Remarks [Control unit]
Main control card Memory card Front side memory I/F card
NC functions and display controller FCU7-MU558
Export Tarde Control Order and Foreign Exchange Order noncompliant unit
LCD panel Backlight driver Menu keys Driver cable LED backlight cable LCD cable
8.4-type color TFT (VGA:640*480) FCU7-DU120-13
Front side memory I/F is normally equipped with the control unit
[Keyboard unit] Keyboard for 8.4-type display unit Sheet keys FCU7-KB024 Escutcheon, key switch G402 cable ONG layout (for M system/L system, XYZ)
Keyboard for 8.4-type display unit Lathe system sheet keys FCU7-KB025 Escutcheon, key switch G402 cable ONG layout (for L system, XZF)
[Operation panel I/O unit]
DI: 64-points 24V/0V common type DO: 48-points source type MPG:2ch AO: 1 point Occupied stations (fixed): 1, 2, 3, 7, 8 RIO3 extensible stations: 4, 5, 6
DI 24V/0V common input DO Source output AO Analog output
Base card Terminator (R-TM) Add-on card
DI: 64-points 24V/0V common type DO: 64-points source type MPG:2ch Occupied stations (fixed): 1, 2, 7, 8 RIO3 extensible stations: 3, 4, 5, 6
DI 24V/0V common input DO Source output FCU7-DX711 Base card Terminator (R-TM)
DI: 96-points 24V/0V common type DO: 80-points source type MPG:2ch AO: 1 point Occupied stations (fixed): 1, 2, 3, 7, 8 RIO3 extensible stations: 4, 5, 6
DI 24V/0V common input DO Source output AO Analog output
Base card Terminator (R-TM) Add-on card
DI: 96-points 24V/0V common type DO: 96-points source type MPG:2ch Occupied stations (fixed): 1, 2, 3, 7, 8 RIO3 extensible stations: 4, 5, 6 [Remote I/O unit]
Base card Terminator (R-TM) Add-on card
DI 24V/0V common input DO Source output FCU7-DX731
DI: 32-points 24V/0V common type (photo coupler insulation) DO: 32-points source type (non-insulation) Number of occupied stations: 1
DI 24V/0V common input DO Source output FCUA-DX101 RX312
DI: 64-points 24V/0V common type (photo coupler insulation) DO: 48-points source type (non-insulation) Number of occupied stations: 2
DI 24V/0V common input DO Source output FCUA-DX111 RX312+RX322-1
DI: 64-points 24V/0V common type (photo coupler insulation) DO: 48-points source type (non-insulation) AO: 1 point Number of occupied stations: 2
DI 24V/0V common input DO Source output AO Analog output
DI: 32-points 24V/0V common type (photo coupler insulation) DO: 32-points source type (non-insulation) AI: 4 points AO: 1 point Number of occupied stations: 2
DI 24V/0V common input DO Source output AI Analog input AO Analog output
[Display unit]

Classification Type Components Remarks [External power supply unit] External power supply with power supply ON/OFF function PD25 Power supply card Case set
Input 200VAC Output 24VDC (3A) [Manual pulse generator]
5V Manual pulse generator UFO-01-2Z9 UFO-01-2Z9 (Produced by NIDEC NEMICON)
12V Manual pulse generator HD60C HD60C Input 12VDC 25pulse/rev [Encoder]
Synchronous feed encoder OSE1024-3-15-68 OSE1024-3-15-68 Input 5VDC 1024pulse/rev [MITSUBISHI CNC machine operation panel] MITSUBISHI CNC machine operation panel A FCU7-KB921 Escutcheon, key switch control card Mitsubishi standard 55 key
MITSUBISHI CNC machine operation panel B FCU7-KB926 Escutcheon, Switch
For ENC,SKIP,SIO,MPG,AO FCUA-CS000 Connector (10120-3000VE,2pcs), Shell kit (10320-52F0-008,2pcs)
For RIO FCUA-CS301 Connector (7940-6500SC,4pcs.), Strain relief (3448-7940,2pcs.)
For PD25/PD27 ACIN FCUA-CN200 Connector (2-178128-3), Contact (1-175218-5,3pcs.)
For PD25/PD27 DCOUT 3-178127-6 1-175218-5 Connector (3-178127-6), Contact (1-175218-5,6pcs.)
For PD25/PD27 ON/OFF 1-178288-5 1-175218-5 Connector (1-178288-5), Contact (1-175218-5,6pcs.)
For EMG F120 005057-9403 0016020103 Connector (005057-9403), Contact (0016020103,3pcs.)
For RIO FCUA-CN211 Connector (1-178288-3), Contact (1-175218-2,3pcs.)
For DCIN,F070 FCUA-CN220 Connector (2-178288-3), Contact (1-175218-5,3pcs) For DIO FCUA-CN300 Connector (7940-6500SC,2pcs.) [Original manufactured memory card] Exclusive CF cards for MITSUBISHI CNC 256MB FCU7-CF256M FCU7-CF256M 256MB capacity
Exclusive CF cards for MITSUBISHI CNC 2GB FCU7-CF002G FCU7-CF002G 2GB capacity
(Note 1) Operation panel I/O unit can be mounted on the back side of the keyboard unit. (Note 2) Operation panel I/O units for 700 Series (FCU7-DX67x/ FCU7-DX77x) are not available. (Note 3) DI: Digital input signals, DO: Digital output signals, AI: Analog input signals, AO: Analog output signals
Durable parts Part type Control unit battery Q6BAT Backlight for FCU7-DU120-13(*) 84LHS16 Key sheet for FCU7-KB024 N330B532G51 Key sheet for FCU7-KB025 N330B532G52
(*) Contact the Service Center, Service Station, Sales Office or delayer for repairs or part replacement.
Replacements Part type Protection fuse LM40
Input 5VDC 100pulse/rev · [Cable connector sets]

1.3.4 List of Cables
Type Application Length (m) of cables provided
Max. cable
length CNP2E-1-xM Motor side PLG cable 2, 3, 4, 5, 7, 10, 15, 20, 25, 30 30m CNP3EZ-2P-xM Spindle side detector cable 2, 3, 4, 5, 7, 10, 15, 20, 25, 30 30m CNP3EZ-3P-xM Spindle side detector cable 2, 3, 4, 5, 7, 10, 15, 20, 25, 30 30m CNV22J-K1P-0.3M Detector extension cable for HF-KP motor 0.3 0.3m CNV22J-K2P-0.3M Detector extension cable for HF-KP motor 0.3 0.3m
CNV2E-8P-xM Motor side detector cable (for A74(N)/A51/A48)/ Ball screw side detector cable 2, 3, 4, 5, 7, 10, 15, 20, 25, 30 30m
CNV2E-9P-xM Motor side detector cable (for A74(N)/A51/A48)/ Ball screw side detector cable 2, 3, 4, 5, 7, 10, 15, 20, 25, 30 30m
CNV2E-HP-xM MDS-B-HR unit cable 2, 3, 4, 5, 7, 10, 15, 20, 25, 30 30m CNV2E-K1P-xM Detector cable for HF-KP motor (load side angle) 2, 3, 5, 7, 10 10m CNV2E-K2P-xM Detector cable for HF-KP motor (reverse load side angle) 2, 3, 5, 7, 10 10m
DG21-xM Battery cable (For drive unit - battery unit) 0.3, 0.5, 1, 5 5m
Battery cable (For servo drive unit - servo drive unit) * This cable is required to supply the power from the battery unit to multiple drive units.
0.3, 0.5, 1, 2, 3, 5, 7, 10 10m
DG23-xM Battery cable (For servo drive unit -battery box) 0.3, 0.5, 1, 2, 3, 5, 7, 10 10m
DG24-xM 5V spply/DO output cable (For servo drive unit -battery box) 0.3, 0.5, 1, 2, 3, 5, 7, 10 10m
DG25-xM Battery cable (For servo drive unit -battery box) 0.3, 0.5, 1, 2, 3, 5, 7, 10 10m
F023 LxM Manual pulse generator cable (5V): 1ch (for connection to operation panel I/O unit) 1, 2, 3, 5, 8, 10, 15, 20 20m
F024 LxM Manual pulse generator cable (5V): 2ch (for connection to operation panel I/O unit) 1, 2, 3, 5, 8, 10, 15, 20 20m
F034 LxM RS-232C I/F cable: 1ch 0.5, 1, 2, 3, 5, 8, 10 15m (*) F035 LxM RS-232C I/F cable: 2ch 0.5, 1, 2, 3, 5, 8, 10 15m (*) F070 LxM 24VDC power cable 0.5, 1.5, 3, 5, 8, 10, 15, 20 30m F110 LxM 24VDC power cable for PD25 0.5, 1.5, 3, 5, 8, 10, 15 15m F120 LxM Emergency stop cable 0.5, 1.5, 3, 5, 8, 10, 15, 20 30m F170 LxM ON/OFF switch cable for PD25 0.5, 1.5, 3, 5, 8, 10, 15 15m F221 LxM Analog output cable 1, 2, 3, 5, 8, 10, 15, 20 30m
F320 LxM Manual pulse generator cable (12V): 1ch (for connection to operation panel I/O unit) 1, 2, 3, 5, 8, 10, 15, 20 50m
F321 LxM Manual pulse generator cable (12V): 2ch (for connection to operation panel I/O unit) 1, 2, 3, 5, 8, 10, 15, 20 50m
F351 DI/DO cable (one side connector) (for operation panel I/O unit) 3 50m
FCUA-R030-xM SKIP input 3, 7 20m FCUA-R031-xM Analog input/output 2, 3, 7 30m FCUA-R050-xM Encoder input (straight, with connector) 5 30m FCUA-R054-xM Encoder input (right angle, with connector) 3, 5, 10, 15, 20 30m FCUA-R211-xM Remote I/O (with terminal block) 0.3, 1, 2, 3, 5, 8, 10, 15, 20 30m (*)
FCUA-R300 DI/DO cable (one side connector) (for remote I/O unit) 3 50m
FCUA-R301-xM DI/DO cable (both side connectors) (for remote I/O unit) 1, 2, 3, 5 50m
G011 LxM Operation panel I/O interface cable 0.5 0.5m
G023 LxM Manual pulse generator cable (5V): 1ch (for connection to control unit) 1, 2, 3, 5, 8, 10, 15, 20 20m (*)
G024 LxM Manual pulse generator cable (5V): 2ch (for connection to control unit) 1, 2, 3, 5, 8, 10, 15, 20 20m (*)
G071 xM DC24V relay cable for MITSUBISHI CNC machine operation panel 0.5 0.5m
G300 LxM LAN cross cable (Shielded cable is recommended when the length will be 1m or more) 1, 3, 5, 10 10m
G301 LxM LAN straight cable (Shielded cable is recommended when the length will be 1m or more) 1 1m
G380 LxM Optical communication cable (PCF type with reinforced sheath) (for wiring outside of the panel) 5, 10, 12, 15, 20, 25, 30 30m
G395 LxM Optical communication cable (POF type with reinforced sheath) (for wiring outside of the panel) 3, 5, 7, 10 10m
G396 LxM Optical communication cable (POF type without reinforced sheath) (for wiring inside of the panel) 0.3, 0.5, 1, 2, 3, 5 10m
G460 xM Cable between MITSUBISHI CNC machine operation panel A and MITSUBISHI CNC machine operation panel B 0.5 0.5m
by Mitsubishi · DG22-xM

Type Application Length (m) of cables provided
Max. cable
MR-BKS1CBLxM- A1-H Brake cable for HF-KP motor (load side angle) 2, 3, 5, 7, 10 10m
MR-BKS1CBLxM- A2-H Brake cable for HF-KP motor (reverse load side angle) 2, 3, 5, 7, 10 10m
MR-PWS1CBLxM- A1-H Power cable for HF-KP motor (load side angle) 2, 3, 5, 7, 10 10m
MR-PWS1CBLxM- A2-H Power cable for HF-KP motor (reverse load side angle) 2, 3, 5, 7, 10 10m
R-TM Remote I/O Interface terminator - -
SH21 xM Power supply communication cable 0.35, 0.5, 1, 2, 3, 5, 10, 15, 20, 30 30m
SH41 xM Remote I/O (between units in a panel) 0.3, 0.5, 0.7 1m (*)
(Note 1) Asterisks "x" in type columns indicate cable length (unit: m). (Note 2) Lengths indicated with an asterisk (*) in the max. cable length column indicate the maximum cable length when connecting via other unit.
by Mitsubishi · length


2.1 Environment Conditions
Unit name Control unit Display unit Keyboard unit Operation panel
Type FCU7-MU558 FCU7-DU120-13 FCU7-KB024/025 FCU7-DX621/711/
During operation 0 to 55C°
During storage -20 to 60C°
Long term 10 to 75% RH (with no dew condensation)
Short term 10 to 95% RH (with no dew condensation) (Note 1)
Vibration resistance 4.9m/s2 or less (during operation)
Shock resistance 29.4m/s2 or less (during operation)
Working atmosphere No corrosive gases, dust or oil mist
24VDC ±5% Ripple noise 200mV
3.3V/12VDC 5VDC 3.3V/5VDC 24VDC ±5%(Note 7) (Provided by the control unit)
Power capacity 24V 2.5A - - - (Note 2) 0.25A(Note 7)
Instantaneous stop tolerance time 20ms - 20ms(min)(Note 7)
Heating value (max.) 12.0W 3.3W 1.0W Control section: 5.0W
Mass (kg) 1.0 1.5 0.8 0.4 FCU7-KB921:1.2 FCU7-KB926:0.5
235(width) x 173(height) x 73(depth) (Depth from the plate mounting surface: 60)
260(width) x 200(height) 140(width) x 200(height) 120(width) x 180(height)
Unit name Remote I/O unit
Type FCUA-DX101 FCUA-DX111 FCUA-DX121 FCUA-DX141
During operation 0 to 55C°
During storage -20 to 60C°
Ambient humidity Long term 10 to 75% RH (with no dew condensation)
Short term 10 to 95% RH (with no dew condensation) (Note 1)
Vibration resistance 4.9m/s2 or less (during operation)
Shock resistance 29.4m/s2 or less (during operation)
Working atmosphere No corrosive gases or dust
Input power voltage 24VDC±5% Ripple noise 200mV (P-P)
Power capacity 24V 0.7A (Note 4) 24V 1.5A (Note 4) 24V 0.7A (Note 4)
Instantaneous stop tolerance time -
Others Heating value (max.) 25W (Note 5) 30W (Note 5) 30W (Note 5)
Mass (kg) 0.5 0.6 0.6 0.6
(Note 1) "Short term" means within one month. (Note 2) For the current value of the I/O circuit, calculate with the number of points used and load. (Note 3) For the heating value of the I/O circuit, calculate with the number of points used. (Note 4) Allows only the amount to be consumed by control circuit. (Note 5) Differs according to the number of machine input operation points and the load and number of points connected to the machine output. The maximum value applies when all points are ON. (Note 6) These units, which are open equipments, must be installed within a sealed metal control panel. (Note 7) FCU7-KB926 does not need 24VDC power supply input.

2.2 Control Unit
Dimension and names of parts
[FCU7-MU558]

(8) (9) (10) (12) (13) (14) (15) (16) (17)

(1) USB Front USB memory I/F (11) RIO1 Remote I/O unit I/F
(2) CF Front CF card I/F (12) MENUKEY Menu key I/F
Encoder input 1ch (5V manual pulse generator input 2ch)
(3) INV Display unit backlight driver I/F (13) ENC
(4) DCIN 24VDC input (14) SKIP Skip input 8ch
(5) EMG External emergency stop input (15) SIO Serial communication (RS- 232C) I/F 2ch
(6) ADONCCB Expansion card slot (16) BAT Battery (Q6BAT) I/F
(7) LCD Display unit signal I/F (17) FG FG terminal
Do not connect devices other than USB memories. When using a commercially available USB memory, performance check must be made by machine tool builder.

(2) Front CF card I/F (CF)
It is recommended to use CF cards of the original equipment manufactured parts. Mitsubishi is unable to guarantee the machine operation when a commercially available CF card or SD memory card (SD-CF adapter is required) is used. In that case, performance check must be made carefully by machine tool builder. (Refer to "General Specifications: Exclusive CF cards for MITSUBISHI CNC: Precautions for Use of Commercially Available CF Cards".)
(4) 24VDC input (DCIN)
1 I +24V
3 FG
<Cable side connector type>
Consider the following characteristics when selecting the stabilized power supply (prepared by machine tool builder). Use a power supply that complies with CE Marking or that follows the safety standards given below.
Output Voltage fluctuation ±5% or less of 24VDC
Ripple noise 200mV (P-P)
Power capacity 2.5A or more
Output holding time 20ms
Safety Standards: UL1950, CSA C22.2 No.234 approved, IEC950 compliant Noise Terminal Voltage: FCC Class A, VCCI-Class A High Harmonics Current Restrictions: IEC61000-3-2
(Note) 24VDC voltage may drop instantaneously due to rush current at the beginning of 24V power supply to the control unit. The level of voltage drop depends on the capacity of the power supply. Do not share the power supply with the devices that have alarms to warn the voltage drop.
Item Standard setting · Overcurrent protection Required

(5) External emergency stop input (EMG)
1 FG
2 I EMG IN
3 O +24V
* Be sure to connect EMG terminal cable (G123) to the connector when not used.
(7) Display unit signal I/F (LCD)
(8) Optical communication I/F (OPT)
<Cable side connector type>
(PCF type)

(9) Ethernet I/F (LAN)
1 O TD+
2 O TD-
3 I RD+
6 I RD-
* Connect connector case with FG pattern. * Use cross cable (G300) when directly connecting a device such as a personal computer to the unit.

* Connect connector case with FG pattern.

(11) Remote I/O unit I/F (RIO1)
Up to eight remote I/O stations can be connected.
2 I/O TXRX1*
<Cable side connector type>
(13) Encoder input 1ch/ 5V manual pulse generator input 2ch (ENC)
Synchronous feed encoder or 5V manual pulse generator can be connected to this connector.

* Connect connector case with FG pattern.

(a) Input for synchronous feed encoder
<Specification of input part>

Number of pulse phases Three phases (A phase, B phase, a phase difference 90 degrees, Z phase) (Refer to the waveform below.)
Input frequency (rotation speed) 136kHz or less (8000r/min or less)
a.b.c.d.e: A phase or B phase rising edge (falling edge) phase difference = T/4 ± T/10
<Specification of input part>

Number of pulse phases Two phases (A phase, B phase, a phase difference 90 degrees) (Refer to the waveform below.)
Signal output of manual pulse generator Voltage output, open collector output
Signal voltage H level 3.5V to 5.25V L level 0V to 0.5V
Number of pulses per rotation 25 pulse/rev, 100 pulse/rev
Input frequency (rotation speed) 1kHz or less (40r/s or less for 25pluse/rev, 10r/s or less for 100pluse/rev)
a.b.c.d.e: A phase or B phase rising edge (falling edge) phase difference = T/4 ± T/10 T: A or B phase cycle

(c) 5V manual pulse generator input/output circuit

When using the synchronous feed encoder and the manual pulse generator at the same time, connect the manual pulse generator to the operation panel I/O unit or use a distribution cable made by the machine tool builder.

* Connect connector case with FG pattern.

(a) Skip signal input conditions
Use the input signal within the following condition ranges.

1 Input voltage at external contact ON 6V or less 18V or more, 25.2V or less
2 Input current at external contact ON 6mA or more
3 Input voltage at external contact OFF 20V or more, 25.2V or less 4V or less
4 Input current at external contact OFF 2mA or less
6 Input signal holding time (Ton) 2ms or more
8 Machine side contact capacity +30V or more, 16mA or more


(15) Serial communication (RS-232C) I/F 2ch (SIO)
1 0V 11 0V
2 I RD1(RXD1) 12 O SD1(TXD1)
3 I CS1(CTS1) 13 O RS1(RTS1)
4 O DR1(DSR1) 14 I ER1(DTR1)
5 0V 15 0V
6 NC 16 NC
7 I RD2(RXD2) 17 O SD2(TXD2)
8 I CS2(CTS2) 18 O RS2(RTS2)
9 O DR2(DSR2) 19 I ER2(DTR2)
10 NC 20 NC
* Connect connector case with FG pattern.
(17) FG terminal (FG)

(18) LED

Name Function At fault Conditions
24VDCIN 24VDC input check Not lit (1) Failure of 24VDC input (2) Fuse is disconnected near DCIN connector
DCOUT Internal output voltage check Not lit (1) Failure of internal voltage output in control unit (2) Short circuit of 5VDC output on CG71 or ENC
LCDON 12VDC output voltage check for backlight driver Not lit (1) Failure of 12VDC output in control unit (2) 24VDC input voltage is +20V or less
PSEMG External emergency stop status display Lit (Red) External emergency stop signal has inputted
WDER System error display Lit (Red) (1) Failure of control unit (2) SRAM data is broken
BATALM Battery voltage drop Lit (Red) Battery voltage has dropped to 2.7V or less

2.3 Display Unit
Outline dimension
[FCU7-DU120-13 (8.4-type)]

(Note 1) The above side view shows the state with the control unit mounted. (Note 2) Consider the minimum radius value of optical communication cable for the bottom space. (Refer to "Connection : Precautions for Using Optical Communication Cable".)


2.4 Keyboard Unit
Outline dimension
[FCU7-KB024 (8.4-type)]

(Note) The above side view shows the state with the operation panel I/O unit FCU7-DX721 mounted.


[FCU7-KB025 (8.4-type)]

(Note) The above side view shows the state with the operation panel I/O unit FCU7-DX721 mounted.


2.5 Operation Panel I/O Unit
Characteristics of operation panel I/O unit are as follows.
(1) Number of DI/DO points that can be mounted on the machine operation panel is 64/64 at the minimum and 96/96 at the maximum. Operation panel I/O unit DI/DO uses equivalent serial link connections as those used for remote I/O. (2) Remote I/O interface --- 1ch Extension with remote I/O unit is possible up to 4 stations. (a) When FCU7-DX711 is used: Up to 4 stations, 128 points/128 points in total, are available. (b) When any one of FCU7-DX621/721/731 is used: Up to 3 stations, 96 points/96 points in total, are available. (Note) The maximum number of stations that can be extended is described above whether DI/DO of the operation panel I/O unit is used or not. (3) Manual pulse generator --- 2ch 5V and 12V manual pulse generators can be connected. (4) Installation on the back side of the keyboard unit is possible. Allows space saving inside the operation panel.
Classification Type Components Remarks
DI: 64-points 24V/0V common type DO: 48-points source type MPG:2ch AO: 1 point Occupied stations (fixed): 1, 2, 3, 7, 8 RIO3 extensible stations: 4, 5, 6
DI 24V/0V common input DO Source output AO Analog output
Base card Terminator (R-TM) Add-on card
DI: 64-points 24V/0V common type DO: 64-points source type MPG:2ch Occupied stations (fixed): 1, 2, 7, 8 RIO3 extensible stations: 3, 4, 5, 6
DI 24V/0V common input DO Source output FCU7-DX711 Base card Terminator (R-TM)
DI: 96-points 24V/0V common type DO: 80-points source type MPG:2ch AO: 1 point Occupied stations (fixed): 1, 2, 3, 7, 8 RIO3 extensible stations: 4, 5, 6
DI 24V/0V common input DO Source output AO Analog output
Base card Terminator (R-TM) Add-on card
DI: 96-points 24V/0V common type DO: 96-points source type MPG:2ch Occupied stations (fixed): 1, 2, 3, 7, 8 RIO3 extensible stations: 4, 5, 6
Base card Terminator (R-TM) Add-on card
DI 24V/0V common input DO Source output FCU7-DX731
(Note 1) The station Nos. occupied by the operation panel I/O unit cannot be changed. (Note 2) Set the number of DI points that are simultaneously turned ON to be less than half of the total points. If many points are set to be simultaneously turned ON in high temperature, operation panel I/O unit may be deteriorated due to the heat.

Dimension and names of parts
[FCU7-DX621]

<Dimension drawing for installing on the panel> <Installation on the back side of the keyboard>

Operation panel I/O unit can be installed on the back side of the keyboard.

Fixing screw (4 pcs.) M3x25 (with plain washer and spring washer)
(Note) Use M3x25 screws (with spring washer and plain washer) when mounting the operation panel I/O unit.

[FCU7-DX711]

<Dimension drawing for installing on the panel> <Installation on the back side of the keyboard>

Operation panel I/O unit can be installed on the back side of the keyboard.

Fixing screw (4 pcs.) M3x25 (with plain washer and spring washer)
(Note) Use M3x25 screws (with spring washer and plain washer) when mounting the operation panel I/O unit.

[FCU7-DX721/ FCU7-DX731]

(Note) (9) is not available for FCU7-DX731.
<Dimension drawing for installing on the panel> <Installation on the back side of the keyboard>

Operation panel I/O unit can be installed on the back side of the keyboard.

Fixing screw (4 pcs.) M3x25 (with plain washer and spring washer)
(Note) Use M3x25 screws (with spring washer and plain washer) when mounting the operation panel I/O unit.


Digital input 32 points (1st station) (2) Machine input (CG33)
Digital input 32 points (2nd station) (Note) This is not available for FCU7-DX621. (3) Machine input (CG35)
Digital input 32 points (3rd station) (Note) This is not available for FCU7-DX711.
A1 A20
<Cable side connector type>
B A B A B A
20 I X200 20 I X210 20 I X220 20 I X230 20 I X240 20 I X250
19 I X201 19 I X211 19 I X221 19 I X231 19 I X241 19 I X251
18 I X202 18 I X212 18 I X222 18 I X232 18 I X242 18 I X252
17 I X203 17 I X213 17 I X223 17 I X233 17 I X243 17 I X253
16 I X204 16 I X214 16 I X224 16 I X234 16 I X244 16 I X254
15 I X205 15 I X215 15 I X225 15 I X235 15 I X245 15 I X255
14 I X206 14 I X216 14 I X226 14 I X236 14 I X246 14 I X256
13 I X207 13 I X217 13 I X227 13 I X237 13 I X247 13 I X257
12 I X208 12 I X218 12 I X228 12 I X238 12 I X248 12 I X258
11 I X209 11 I X219 11 I X229 11 I X239 11 I X249 11 I X259
10 I X20A 10 I X21A 10 I X22A 10 I X23A 10 I X24A 10 I X25A
9 I X20B 9 I X21B 9 I X22B 9 I X23B 9 I X24B 9 I X25B
8 I X20C 8 I X21C 8 I X22C 8 I X23C 8 I X24C 8 I X25C
7 I X20D 7 I X21D 7 I X22D 7 I X23D 7 I X24D 7 I X25D
6 I X20E 6 I X21E 6 I X22E 6 I X23E 6 I X24E 6 I X25E
5 I X20F 5 I X21F 5 I X22F 5 I X23F 5 I X24F 5 I X25F
4 NC 4 NC 4 NC 4 NC 4 NC 4 NC
3 COM 3 COM 3 COM 3 COM 3 COM 3 COM
2 I +24V 2 0V 2 I +24V 2 0V 2 I +24V 2 0V
1 I +24V 1 0V 1 I +24V 1 0V 1 I +24V 1 0V
Each station has fixed input/output assignments. Refer to "PLC Interface Manual" for details.


Both 24V common and 0V common connections are allowed in the digital signal input circuit. Follow the wiring diagram below for each type. Input circuit

The input signals must be used within the following condition ranges.

1 Input voltage at external contact ON 6V or less 18V or more, 25.2V or less
2 Input current at external contact ON 9mA or more
3 Input voltage at external contact OFF 20V or more, 25.2V or less 4V or less
4 Input current at external contact OFF 2mA or less
7 Input signal holding time (T2) 40ms or more (Note)
8 input circuit operation delay time (T3 and T4) 3 to 16ms
9 Machine side contact capacity 30V or more, 16mA or more
(Note) Input signal holding time: The guide is 40ms or more. The input signal will not be recognized unless it is held for the ladder processing cycle time or longer.

Connection to 24V common input Connection to 0V common input


Digital output 32 points (1st station) (5) Machine output (CG34)
Digital output 32 points (2nd station) (Note) This is not available for FCU7-DX621. (6) Machine output (CG36)
FCU7-DX731: Digital output 32 points (3rd station) FCU7-DX621/DX721: Digital output 16 points (3rd station) (with analog output) (Note) This is not available for FCU7-DX711.
A1 A20
<Cable side connector type>
CG32 CG34 CG36 (Note 1)
20 O Y200 20 O Y210 20 O Y220 20 O Y230 20 O Y240 20 O Y250
19 O Y201 19 O Y211 19 O Y221 19 O Y231 19 O Y241 19 O Y251
18 O Y202 18 O Y212 18 O Y222 18 O Y232 18 O Y242 18 O Y252
17 O Y203 17 O Y213 17 O Y223 17 O Y233 17 O Y243 17 O Y253
16 O Y204 16 O Y214 16 O Y224 16 O Y234 16 O Y244 16 O Y254
15 O Y205 15 O Y215 15 O Y225 15 O Y235 15 O Y245 15 O Y255
14 O Y206 14 O Y216 14 O Y226 14 O Y236 14 O Y246 14 O Y256
13 O Y207 13 O Y217 13 O Y227 13 O Y237 13 O Y247 13 O Y257
12 O Y208 12 O Y218 12 O Y228 12 O Y238 12 O Y248 12 O Y258
11 O Y209 11 O Y219 11 O Y229 11 O Y239 11 O Y249 11 O Y259
10 O Y20A 10 O Y21A 10 O Y22A 10 O Y23A 10 O Y24A 10 O Y25A
9 O Y20B 9 O Y21B 9 O Y22B 9 O Y23B 9 O Y24B 9 O Y25B
8 O Y20C 8 O Y21C 8 O Y22C 8 O Y23C 8 O Y24C 8 O Y25C
7 O Y20D 7 O Y21D 7 O Y22D 7 O Y23D 7 O Y24D 7 O Y25D
6 O Y20E 6 O Y21E 6 O Y22E 6 O Y23E 6 O Y24E 6 O Y25E
5 O Y20F 5 O Y21F 5 O Y22F 5 O Y23F 5 O Y24F 5 O Y25F
4 COM (Note 2) 4 COM (Note 2) 4 COM (Note 2) 4 COM (Note 2) 4 COM (Note 2) 4 COM (Note 2)
3 COM (Note 2) 3 COM (Note 2) 3 COM (Note 2) 3 COM (Note 2) 3 COM (Note 2) 3 COM (Note 2)
2 I 24VDC 2 GND (0V) 2 I 24VDC 2 GND (0V) 2 I 24VDC 2 GND (0V)
1 I 24VDC 1 GND (0V) 1 I 24VDC 1 GND (0V) 1 I 24VDC 1 GND (0V)
(Note 1) FCU7-DX621/DX721 uses 16 points of digital outputs, Y240 to Y24F. (Note 2) COM (3A, 3B, 4A, and 4B) is connected to 24VDC inside the unit.
Each station has fixed input/output assignments. Refer to "PLC Interface Manual" for details.

(a) Outline of digital signal output circuit
Use within the specification ranges shown below.

Rated load voltage 24VDC
Max. output current 60mA/point
Output delay time 40μs
(Note 1) When using an inductive load such as a relay, always connect a diode (voltage resistance 100V or more, 100mA or more) in parallel to the load.
(Note 2) When using a capacitive load such as a lamp, always connect a protective resistor (R=150Ω) serially to the load to suppress rush currents. (Make sure that the current is less than the above tolerable current including the momentary current.)

Insulation method Insulation

(7) Keyboard I/F (NCKB)
(8) FG terminal (FG)
(9) Analog output 1ch (AO)
(Note) This is not available for FCU7-DX731.

* Connect connector case with FG pattern.


(Note) n=(20 to 211)
1 AO* GND
7 AO Analog voltage output

(10) Manual pulse generator input 2ch (5V and 12V) (MPG)
5V manual pulse generator and 12V manual pulse generator can be connected to this connector. Connect the synchronous feed encoder to the ENC connector of the control unit.

* Connect connector case with FG pattern.

Number of pulse phases Two phases (A phase, B phase, a phase difference 90 degrees)
Signal output of manual pulse generator Voltage output, open collector output Open collector output
Input frequency (rotation speed) 1kHz or less (40r/s or less for 25pluse/rev, 10r/s or less for 100pluse/rev)
b d a c e
a.b.c.d.e: A phase or B phase rising edge (falling edge) phase difference = T/4 ± T/10 T: A or B phase cycle
A(B) phase · B(A) phase

<Input/output circuit>

1 I/O TXRX3
2 I/O TXRX3*
3 0V(GND)
<Cable side connector type>
Refer to the following chart for the maximum number of connecting stations and I/O points.

Operation panel I/O unit type Max. number of stations
FCU7-DX711 4 stations (stations 3rd to 6th can be used) 128 points/128 points
FCU7-DX621/DX721/DX731 3 stations (stations 4th to 6th can be used) 96 points/96 points
(Note) Refer to the section "General Specifications: Remote I/O Unit" for the number of occupying stations and I/ O points of remote I/O units.

(13) LED

Name Function At fault Conditions
3VON 3VDC input check Not lit (1) Disconnection between control unit and operation panel I/O unit
5VON 5VDC input check Not lit (1) Disconnection between control unit and operation panel I/O unit (2) Short circuit of manual pulse generator cable
PACKETNG RIO communication status check Lit (Red)
(1) Partial disconnection between control unit and operation panel I/O unit (2) Miswiring of extended I/O unit to RIO3 RIO1 RIO communication status check Not lit
12VON For manual pulse generator Not lit Short circuit of manual pulse generator cable
DOCOM 24VDC input check Not lit (1) Disconnection of 24V input (2) Disconnection of protection fuse on the operation panel I/O unit

2.6 Remote I/O Unit
The following four types of signals can be input/output from the remote I/O unit (FCUA-DX1x1) according to the type and No. of contacts. Use serial link connections to connect the unit with the control unit or the operation panel I/O unit. Multiple remote I/O units can be used as long as the total number of occupied stations is eight or less.
Classification Type Components Remarks
DI: 32-points 24V/0V common type (photo coupler insulation) DO: 32-points source type (non-insulation) Number of occupied stations: 1
DI 24V/0V common input DO Source output FCUA-DX101 RX312
DI: 64-points 24V/0V common type (photo coupler insulation) DO: 48-points source type (non-insulation) Number of occupied stations: 2
DI 24V/0V common input DO Source output FCUA-DX111 RX312+RX322-1
DI: 64-points 24V/0V common type (photo coupler insulation) DO: 48-points source type (non-insulation) AO: 1 point Number of occupied stations: 2
DI 24V/0V common input DO Source output AO Analog output
DI: 32-points 24V/0V common type (photo coupler insulation) DO: 32-points source type (non-insulation) AI: 4 points AO: 1 point Number of occupied stations: 2
DI 24V/0V common input DO Source output AI Analog input AO Analog output

Dimension and names of parts



(1) Machine input (DI-L) (2) Machine input (DI-R)
Both 24V common and 0V common connections are allowed in the digital signal input circuit. Follow the wiring diagram below for each type. Input circuit

The input signals must be used within the following condition ranges.

1 Input voltage at external contact ON 6V or less 18V or more, 25.2V or less
2 Input current at external contact ON 9mA or more
3 Input voltage at external contact OFF 20V or more, 25.2V or less 4V or less
4 Input current at external contact OFF 2mA or less
7 Input signal holding time (T2) 40ms or more (Note)
8 input circuit operation delay time (T3 and T4) 3 to 16ms
9 Machine side contact capacity 30V or more, 16mA or more
(Note) Input signal holding time: The guide is 40ms or more. The input signal will not be recognized unless it is held for the ladder processing cycle time or longer.

Connection to 24V common input Connection to 0V common input

(3) Machine output (DO-L) (4) Machine output (DO-R)
Use within the specification ranges shown below. Output circuit

Rated load voltage 24VDC
Max. output current 60mA/point
Output delay time 40μs
(Note 1) When using an inductive load such as a relay, always connect a diode (voltage resistance 100V or more, 100mA or more) in parallel to the load.
(Note 2) When using a capacitive load such as a lamp, always connect a protective resistor (R=150Ω) serially to the load to suppress rush currents. (Make sure that the current is less than the above tolerable current including the momentary current.)
Insulation method Non-insulation

[Outline of analog signal output circuit]
The analog signal output circuit can be used only for FCUA-DX121.


(Note) n=(20 to 211)


(5) Analog signal input/output (AIO)
(a) Outline of analog signal output circuit
The analog signal output circuit can be used only for FCUA-DX141.


(Note) n=(20 to 211)
The analog signal input circuit can be used only for FCUA-DX141.



(6) Transfer speed changeover switch (DS)
(7) Station No. changeover switch (CS)
4 2 5 6 7
F
Selection of station No.
A D
B
(8) Remote I/O unit I/F #1 (RIO1) (9) Remote I/O unit I/F #2 (RIO2)
2 I/O TXRX*
<Cable side connector type>
1 I +24V
3 FG
<Cable side connector type>
Name Function At fault Conditions
(1) Failure of 24VDC input (2) Fuse is disconnected (3) Failure of internal voltage output in I/O unit
Internal output voltage(5VDC) check Not lit
RIO communication status check Lit (1) Partial disconnection between control unit and remote I/O unit (2) Miswiring of connected remote I/O unit

2.7 External Power Supply Unit

(Note 1) PD25 will not be turned ON by the ON/OFF switch immediately after the power OFF. Wait at least 2 seconds, and then turn the power ON. (Note 2) The power supply configuration for NC devices depends on the machine. Appropriate circuit protector must be selected by machine builder according to the load of the machine. (Note 3) PD25 does not comply with 100VAC.
[PD25]

Mount the external power supply unit vertically and so that it is visible from the front. Provide space for heat dissipation and ventilation.
100mm · 20mm 20mm · 100mm

(1) AC power input (ACIN)
1 I ACIN N
2 I ACIN H
3 FG
<Cable side connector type>
1 NC
2 I P-OFF
5 I P-ON
<Cable side connector type>
Green light at +24V output

Connector: 3-178127-6 Contact: 1-175218-5 (for AWG16) × 3, 1-175217-5 (for AWG22) × 2 Recommended manufacturer: Tyco Electronics

2.8 Manual Pulse Generator
[UFO-01-2Z9]
5V Manual Pulse Generator (100 pulse/rev)
72 at equal pitch Panel cut diameter stud Index

Produced by NIDEC NEMICON CORPORATION

[HD60C]
12V Manual Pulse Generator (25 pulse/rev)



2.9 Synchronous Feed Encoder
Dimension and names of parts
[OSE-1024-3-15-68]



Connector pin assignment

2.10 MITSUBISHI CNC Machine Operation Panel
2.10.1 MITSUBISHI CNC Machine Operation Panel A
Outline dimension
[FCU7-KB921 (MITSUBISHI CNC machine operation panel A)]



Connector


(3) RIOIN Remote I/O (6) SUBP Mahine operation panel B switch
1 I/O +24V
3 - FG

(3) Remote I/O connected connector (RIOIN)
1 I/O TXRX
2 I/O TXRX*
(5) Relay wiring (EXT)
A1 A5
B5
B1
B05 - A05 -
B04 O Relay EMGCOM A04 O Relay EMG
B03 O Relay 6 A03 O Relay 5
B02 O Relay 4 A02 O Relay 3
B01 O Relay 2 A03 O Relay 1

(6) Machine operation panel B switch (SUBP)
A20
A1
B20
B1


(a) Wiring of machine operation panel B

(Note1) Use the special lead wire with a connector for wiring of rotary switch. Lead wire with a connector: ACX011-705 (7 terminals, 0.5m) Fuji Electric (Note2) A09 to 12 and B09 to 11 of SUBP are spares, so they do not need wiring. (Note3) Select a rotary switch which guarantees 5V/1mA. (Note4) Length of cables must be 0.5m or shorter. (Note5) The numbers in the above diagram do not indicate the actual device numbers.

<Wiring of other switches (SUBP)>

(Note1) Wirings for selector switches must be directly soldered to terminals or use tab terminals (110 series). (Note2) When wiring the emergency stop switch, the crimp terminal must be fastened with thread. (Note3) For NCs whose control unit and display unit are integrated, wire the emergency stop switch directly to the EMG connector of the control unit. (Use F120 cable) And for NCs whose control unit and display are separated, relay it by the machine operation panel I/F PCB HN232. (Note4) Select a rotary switch which guarantees 5V/1mA. (Note5) Length of cables must be 0.5m or shorter. (Note6) The numbers in the above diagram do not indicate the actual device numbers.

<Connection when the selector SW has 3 notches>

<Connection when relaying wiring to control panel>

Push button SW (For emergency stop) Push Lock - Turn Reset 2a2b contact

2.10.2 MITSUBISHI CNC Machine Operation Panel B
Outline dimension
[FCU7-KB926 (MITSUBISHI CNC machine operation panel B)]



Connector

No. Switch No. Switch
(1) Memory protection switch (3) Spindle override (RSW2)
(2) Emergency stop button (4) Cutting override (RSW1)

Contact 2 Contact 1
C - Contact 1(Common)
NO O Contact 1(A contact)
NC O Contact 1(B contact)
C - Contact 2(Common)
NO O Contact 2(A contact)
NC O Contact 2(B contact)

(2) Emergency stop button

13 O Contact 1(A contact)
14 O Contact 1(A contact)
21 O Contact 2(B contact)
22 O Contact 2(B contact)
33 O Contact 3(A contact)
34 O Contact 3(A contact)
41 O Contact 4(B contact)
42 O Contact 4(B contact)
A G

A O Output signal 1
B O Output signal 3
C O Output signal 5
D - Common terminal
E O Output signal 4
F O Output signal 2

(4) Cutting override (RSW1)
A G
A O Output signal 1
B O Output signal 3
C O Output signal 5
D - Common terminal
E O Output signal 4
F O Output signal 2
G O Output signal 6

2.11 Exclusive CF Cards for MITSUBISHI CNC
Operation-guaranteed temperature -40 ℃to +85 ℃
NAND Flash SLC (Note)
(Note) SLC stands for Single Level Cell, and it stores one bit data in each memory cell. This provides longer life span and high product reliability in comparison with MLC (Multi Level Cell), which is commonly applied to CF cards.
Mitsubishi is unable to guarantee the machine operation when a commercially available CF card or SD memory card (SD-CF adapter is required) is used. In that case, performance check must be made carefully by machine tool builder.
(1) Commercially available CF cards may not be compatible with MITSUBISHI units or suitable FA environment for temperature- or noise-wise. In case of using it, careful performance check must be required by the machine tool builder. (2) When inserting/removing a commercially available CF card, turn the MITSUBISHI device’s power OFF to avoid any troubles. If a card must be inserted and removed while the power is ON, make sure to take sufficient time (approx. ten seconds or more) between the insertion and removal. (3) Do not pull out the card or turn OFF the power during access to the CF card. Failure to observe this could cause the memory contents to be erased. In case of emergency, always perform backups by having your important data duplicated, etc. as MITSUBISHI will not guarantee the broken or lost data.
Item FCU7-CF256M FCU7-CF002G · Capacity 256MB 2GB



3.1 Heat Radiation Countermeasures
Please refer to the following method for heat radiation countermeasures.
<Hypothetical conditions>
(1) Average internal temperature of operation panel: T ≤ 55°C (2) Peripheral temperature of operation panel : Ta ≤ 0°C to 45°C
(3) Internal temperature rise value : ΔT = T - Ta (max) = 10°C Procedures for heat design and verification
Calculate total heat radiation of each mounted unit (W)
Calculate cooling capacity of operation panel (W1)
Comparison of W and W1
Selection of heat exchanger
Collection of internal temperature rise distribution data
Δ T>10°C
<Supplement>
(1) Refer to "General Specification" for the heat generated by each unit. (2) Enclosed cabinet (thin steel plate) cooling capacity calculation equation
U: 6 W/m2°C
A: Effective heat radiation area (m2) (Area where heat can be radiated from operation panel)
(Caution) 8 W/m2°C can be applied only when the operation panel is so small that the internal
temperature stays uniform. (3) Points of caution for heat radiation countermeasures when designing mounting state
- Consider convection in operation panel (eliminate heat spots) - Collect hot air at suction port of heat exchanger in operation panel. (4) Criterion for internal temperature rise distribution data
ΔT (average value) ≤ 10°C
ΔTmax (maximum value) ≤ 15°C
R (inconsistency ΔTmax - ΔTmin) ≤ 6°C (Evaluate existence of heat spots)

The following shows an example of calculation applied to heat radiation countermeasures for the operation panel when 8.4-type display unit is used. Because heat will accumulate in the upper portions of the unit, install an agitating fan as required.


Calculation example of panel internal heating value
(1) Calculation of unit heating value
Heating value (W)
Total heating value of units (W):
28W (= control unit + display unit + keyboard unit + operation panel I/O unit) Total heating value (W) by machine input (D1):
5.6W (=24V (total heating value when the 32 points are simultaneously turned ON) × 7.3mA × 32)
... 24V (current consumption per point of the operation panel I/O unit DI) divided by 3.3kΩ ≈ 7.3mA
Total heating value W = 33.6W (28 + 5.6)
Tolerance value for temperature rise ( ⊿t)
Panel internal temperature (according to each unit's specification) T ≤ 55C° Panel peripheral temperature (according to machine's specification) Ta ≤ 45C°
Tolerance value for internal temperature rise ⊿T = 10C° (T - Ta)
The surface of the molded unit, which has lower radiation capacity than the base plate surface, should be excluded for the heat radiation area in principle. The bottom of the operation panel, which has difficulty in radiating due to the temperature distribution, should also be excluded for the heat radiation area in principle.
Heat radiation area A = 0.71mm2
(≈ 0.6 × 0.12 + 0.6 × 0.5 × 2 - (0.26 + 0.14) × 0.2 + 0.12 × 0.5 × 2) (Top surface) (Front, rear surface) (Unit surface) (Both sides surface)
Calculate the cooling capacity to keep the temperature rise in the operation panel less than 10°C.
Cooling capacity W1 = 42.6W (6 × A × ⊿T)
The operation panel cooling capacity is over the heating value, which presumed no need to install the heat exchanger.
The result of the calculation above is only a rough indication. The actual temperature rise may differ according to the structure of the operation panel. Be sure to confirm the temperature rise value in the operation panel when the machine is running.

3.2 Noise Countermeasures
3.2.1 Connection of FG (Frame Ground)
The frame should basically be grounded at one ground point. Connect the control unit and operation panel I/O unit's 0V (RG) to the FG on the +24V stabilized power supply.

Stabilized power supply Main grounding plate for electric cabinet
(Note) "24VDC" represents (+) side of 24V stabilized power supply, while "0V(RG)" represents (-) side. "FG" (Frame Ground) corresponds to the general expression "PE" (Protective Earth).

3.2.2 Shield Clamping of Cables
The shield cables connected to the units must be properly connected to the ground with clamp fittings and the like in order to stabilize the system's operation while preventing malfunctioning due to exogenous noise. (Refer to "EMC Installation Guidelines: EMC Countermeasure Parts: Shield Clamp Fitting".)
Connect a spark killer on the coil or the contact in parallel for noise countermeasures.
Use spark killers which are 0.33 to 0.1μF, 10 to 120Ω.

3.3 Unit Installation
3.3.1 Display Unit
Mount the display unit with four fixing screws.
(Note) Refer to "General Specifications: Display Unit" for the panel cut dimension drawing and the screw hole position.


3.3.2 Keyboard Unit
Mount the keyboard unit with four fixing screws.
(Note 1) Refer to "General Specifications: Keyboard Unit" for the panel cut dimension drawing and the screw hole position. (Note 2) A clear protective film covers the sheet keys of the keyboard at the time of shipment. Make sure to remove the sheet before use.

Mount the operation panel I/O unit on the back of the keyboard unit with four fixing screws.
(Note) The operation panel I/O unit is usually mounted on the keyboard unit when shipped.

Fixing screw (4 pcs.) M3x25 (with plain washer and spring washer)

3.3.4 Control Unit Battery
A lithium battery in the control unit battery holder retains parameter settings, machining programs and the like, which requires to be backed up at the power OFF.
Battery cumulative data holding time 45,000 hours (At 0 to 45°C. The life will be shorter if the temperature is high.)
Battery life Approx. 5 years (from date of battery manufacture)
(1) Check that the machine power is turned OFF. (If the power is not OFF, turn it OFF.) (2) Confirm that the control unit LED, 7-segment display, etc., are all OFF. (3) Open the battery cover of the control unit. Pull the right side of the battery cover toward front. (4) Fit the new battery into the battery holder. (5) Insert the connector connected to the new battery into the BAT connector. Pay attention to the connector orientation: do not insert backwards. (6) Close the front cover of the control unit. At this time, confirm that the cover is closed by listening for the "click" sound when the latch catches.
![Mitsubishi Electronics Freqrol E70 — [Installation method] diagram (page 94)](/cdn/reader/be/be4646ece03a49592ccc934c31a00ecac7aa46ef3481bcfce32ff74c6884f73b/images/fig-94-1.webp)
(1) Do not disassemble the battery. (2) Do not place the battery in flames or water. (3) Do not pressurize and deform the battery. (4) This is a primary battery so do not charge it.
Do not short circuit, charge, overheat, incinerate or disassemble the battery.
Battery Q6BAT



4.1 Precautions for Wiring
4.1.1 Precautions when Connecting/Disconnecting Cables
If the cable is connected/disconnected without turning the power OFF, the normal unit or peripheral devices could be damaged, and risks could be imposed. Disconnect each cable with the following procedures.
(a) For the following type of connector, press the tabs with a thumb and forefinger in the direction of the arrow, and pull the connector off.
CAUTION

(b) For a flat cable type connector with latches, open the latches in the directions of the arrows, and pull the connector off.
(c) For a flat cable type connector without latches, hold the connector with a thumb and forefinger, and pull the connector off.
Hold with thumb and forefinger.
(d) For the screw fixed type connector, loosen the two fixing screws, and pull the connector off.

(e) For the optical cable connector, pull off while holding down the lock button.
(f) For the Ethernet connector, pull off while holding down the locked latch.

4.1.2 Precautions for Using Optical Communication Cable
An optical communication cable is used for communication between the control unit and the drive unit. Special precautions, differing from the conventional cable, are required when laying and handling the optical communication cable.
(Note) If the cable you use is not Mitsubishi's, malfunctions resulted from connection problems or aged deterioration are not covered under the warranty.
Fiber code/connector connection section
22.7 150 35
To ensure the system performance and reliability, purchase the optical communication cable from Mitsubishi. A machining drawing is given in "Cable" as reference, but the purchased optical communication cable cannot be cut or connected by the machine tool builder.
(1) A protective cap is attached to the optical module and optical communication cable mounted on the PCB when the system is delivered. Leaving this protective cap unattached could result in connection faults from the adherence of dirt and dust. Do not remove the protective cap when not connecting the cable. If dirty, wipe off lightly with a piece of dry gauze, etc. (Do not use solvents such as alcohol as the optical fiber material could melt.) (2) Hold the connector section when connecting or disconnecting the optical connector. Holding the fiber cord will result in force exceeding the tolerable tension on the fiber cord and connector connection section, and could cause the fiber cord to dislocate from the optical connector thereby inhibiting use. (3) The optical connector cannot be connected in reversed. Check the connector orientation when connecting the optical communication cable to the optical module. Align the connector lock lever with the lock holes on the PCB's optical module, and press the connector straight in. Confirm that the lock lever connects with the optical module and that a "click" is heard. (4) When disconnecting the optical communication cable from the PCB, press the lock release buttons on the lock lever, and pull out the cable while holding the connector section. The connector could be damaged if the cable is pulled without pressing down on the lock release buttons. (5) Do not apply excessive force onto the optical communication cable by stepping on it or dropping tools, etc., on it.
Bushing Reinforced sheath · Optical connector · Fiber cord

4.1.2.3 Precautions for Laying Optical Communication Cable
(1) Do not apply a force exceeding the cable's tolerable tension. Binding the cables too tight with tie-wraps could result in an increased loss or a disconnection. Use a cushioning material such as a sponge or rubber when bundling the cables and fix so that the cables do not move. (2) Do not connect the cables with a radius less than the tolerable bending radius. Excessive stress could be applied near the connector connection section and cause the optical characteristics to drop. The cable bending radius should be 10 times or more than the outer diameter at the reinforced sheath, and 20 times or more than the outer diameter at the fiber cord section. (3) Do not apply torsion to the optical communication cable. Laying a twisted cable could cause the optical characteristics to drop. (4) When laying the cables in a conduit, avoid applying stress on the fiber cord and connector connection section. Use the tensile end such as a pulling eye or cable grip, etc. (5) Fix the reinforced sheath with a cable clamp so that the mass of the optical communication cable is not directly applied on the fiber cord and connector connection section. (6) Never bundle the cables with vinyl tape. The plasticizing material in the vinyl tape could cause the POF cable to break. (7) Loop the excessive cable with twice or more than the minimum bending radius.
KITAGAWA INDUSTRIES
Optical communication cable (section with reinforced sheath):
Bending radius: Refer to the specification of your optical communication cable.
(1) When 24V power is supplied to the unit (control unit, display unit) under the following conditions, welding may occur on the contacts due to rush current; so be careful.
When 24VDC's ON/OFF are directly controlled by a magnetic switch such as relay AND When heat capacity of the contacts for relay, etc. used to control 24VDC's ON/OFF is small.
Control unit · Recommended clamp material

4.2 Connection of Control Unit
The method for connecting to each unit and device from the control unit is explained in this section.
Operation panel I/O unit Control unit
CG71
F034,F035
SIO
R050,R054
Synchronous feed encoder, or
G023,G024
5V manual pulse generator
Accessory cable for unit
Accessory cable for unit
Accessory cable for unit
Accessory cable for unit
R030
Skip input (Sensor input)
G395/G396/G380
OPT
Optical communication repeater unit
RIO1
MITSUBISHI CNC Machine operation panel
LAN
F120
EMG
24VDC
F070
DCIN

4.2.2 Connecting with Power Supply
Connect a general-purpose 24VDC stabilized power supply or PD25 power supply unit to the control unit.

(Note 1) Rush current may occur to lead welding on the contacts, when a magnetic switch such as relay directly controls 24VDC's ON/OFF during 24V power supply to the control unit. Use relay with large heat capacity of contacts to control 24VDC's ON/OFF. (Note 2) Make a short-circuit between 0V and FG on the terminal to cut noise.

(Note) ACFAIL function is not available with this NC system. (CF01 is not connected.)
Cable drawing: "Cable: F110 Cable", "Cable: F170 Cable" Connector pin assignment: "General Specifications: Control Unit" (DCIN connector)

4.2.3 Connecting with Emergency Stop Signal
Connect the emergency stop switch to EMG connector by F120 cable.

Besides the emergency stop input from the NC controller, double-protection when an emergency stop occurs can be provided by directly inputting an external emergency stop to the drive unit. Even if the emergency stop is not input from NC for some reason, the contactors can be shut off by the external emergency stop input. Outlines are shown below. For more details, refer to the Instruction Manual of each drive unit.


<Drive unit (MDS-DJ-V1) external emergency stop: Example 2>

(1) External emergency stop cannot substitute the emergency stop signal which is input to NC. It is a function which helps the NC emergency stop. (2) When duplicating emergency stop input, wire the NC emergency stop input and the drive unit external emergency stop input from the same emergency stop switch.

4.2.4 Connecting with Operation Panel I/O Unit
Connect the operation panel I/O unit to the connector CG71.


4.2.5 Connecting with Drive Unit
Connect the optical communication cables from the NC to the each drive unit so that they run in a straight line from the NC to the drive unit that is a final axis. Up to 6 axes can be connected. Note that the number of connected axes is limited by the NC.
(Note) Refer to "Precautions for Using Optical Communication Cable" when handling and wiring optical communication cable.
Cable Panel internal wiring Panel external wiring
Under 10m 10 to 30m 10m or less 10 to 30m
G396 ○ × × × G395 ○ × ○ × G380 ○

4.2.5.1 Connecting with MDS-DM2 Series

Connect the NC and the drive units by the optical communication cables. The distance between the NC and the
final drive unit must be within 30m and the bending radius within 80mm.

As for MDS-DJ series, axis Nos. are determined by the rotary switch for setting the axis No. (Refer to the MDS-DJ
Series Instruction Manual.) The axis No. has no relation to the order for connecting to the NC.


(2) When using the MDS-DJ unit together

The optical communication cables from the NC to the final drive unit must be within 30m.

Connect the NC and the drive units by the optical communication cables. The distance between the NC and the
final drive unit must be within 30m and the bending radius within 80mm.

Axis Nos. are determined by the rotary switch for setting the axis No. (Refer to the MDS-DJ Series Instruction
Manual.) The axis No. has no relation to the order for connecting to the NC.
<Connection> CN1A: CN1B connector on NC or previous stage's drive unit CN1B: CN1A connector on next stage's drive unit

The optical communication cable up to 5m can be used in G396 series, up to 10m in G395 series, and up to 30m in G380 series.

4.2.6 Connecting with RS-232C Device
(1) Connect the RS-232C device to the connector SIO.



(2) Example of wiring connections to the RS-232C device When connecting to the RS-232C device, refer to the following diagrams and cross the wiring for the transmission signals.
No hand shaking upon RS/CS, ER/DR signals Hand shaking upon RS/CS, ER/DR signals
SD(TXD)
SD(TXD)
SD(TXD)
RD(RXD)
RD(RXD)
RD(RXD)
RD(RXD)
RS(RTS)
RS(RTS)
RS(RTS)
RS(RTS)
CS(CTS)
CS(CTS)
CS(CTS)
CS(CTS)
ER(DTR)
ER(DTR)
ER(DTR)
ER(DTR)
DR(DSR)
DR(DSR)
DR(DSR)
DR(DSR)
CD(DCD)
CD(DCD)
CD(DCD)
CD(DCD)
FG
FG
FG
FG

4.2.7 Connecting with Skip Signal (Sensor)
Connect skip signals to the connector SKIP. Skip signals are used for processing high-speed signals. Always shield the cable.

(Note) Connecting the skip signal cable to a wrong connector causes a damage on the control unit when turning ON the skip signal power supply. Confirm the wiring before turning the power ON.
<0V connection at COM terminal>


<24V connection at COM terminal>

(Note 1) NC recognizes input signals of 2ms or more as the valid skip signals. If machine contacts (relay, etc.) are used, malfunctions will occur due to chattering. Use semiconductor contacts (transistor, etc.). (Note 2) Fold the cable shield over the sheath, and wrap copper foil tape over it. Connect the wound copper foil tape to GND plate of the connector.

4.2.8 Connecting with Synchronous Feed Encoder/ Manual Pulse Generator
Synchronous feed encoder (1ch) or 5V power supply type manual pulse generator (2ch) can be connected.

Cable drawing: "Cable: FCUA-R050/R054 Cable" and "Cable: G023/G024 Cable" Connector pin assignment: "General Specifications: Control Unit" (ENC connector)
When using the synchronous feed encoder and the manual pulse generator at the same time, the cables must be prepared by the machine tool builder.
Unit configuration decides handle Nos. "ENC": Connector on control unit "MPG": Connector on operation panel I/O unit
Operation panel I/O unit (FCU7-DX71x/ DX72x/ DX73x/DX621) 1st handle 2nd handle 3rd handle
Used "MPG" 1ch "MPG" 2ch "ENC" 1ch (Note)
Not used "ENC" 1ch "ENC" 2ch -
(Note) If one handle is only connected to "MPG", the handle connected to "ENC" 1ch will still be treated as the 3rd handle. "ENC" 2ch is not employed when an operation panel I/O unit is used.

4.2.9 Connecting with Safety Observing I/O Device
Connect safety observing I/O device as the example below. (Below is an example where an MDS-DJ series drive unit is used.)

Safety observing functions follow "IEC61800-5-2/EN61800-5-2", and safety of the functions complies with "EN ISO13849-1:2008 (PL d, Category 3)". However, make sure to check the safety of the machine by using "risk assessment". With this function, the following executions can be realized.
(1) Open the door without shutting the motor drive power OFF. (2) Operate under the safety speed or lower while the door is opened.
Refer to the "Safety Handbook (Original Instructions)" (IB-1501025) for the details of the connection with the safety observing I/O devices. Refer to the instruction manual of the drive unit for the details of the connection with the drive unit.

4.3 Connection of Operation Panel I/O Unit
4.3.1 Operation Panel I/O Unit Connection System Drawing
Control unit Operation panel I/O unit
CG71
R211
Remote I/O unit, scan I/O unit card
MITSUBISHI CNC Machine operation panel
CG31
Machine control panel, switchboard, etc.
CG32
Machine control panel, switchboard, etc.
Machine control panel, switchboard, etc.
F351
Machine control panel, switchboard, etc.
F351
CG35
Machine control panel, switchboard, etc.
CG36
Machine control panel, switchboard, etc.
AO
Machine control panel, switchboard, etc.
MPG
F023/F024
Keyboard unit Accessory cable for unit

4.3.2 Connecting with Keyboard Unit
Connect the keyboard unit to the connector NCKB. The cable comes with the keyboard unit.

(Note) Firmly insert the connection cable until it is locked.

4.3.3 Connecting with Manual Pulse Generator (MPG)
Both 5V power supply type (UFO-01-2Z9) and 12V power supply type (HD60C) manual pulse generator can be used. Take the maximum cable length, etc. into consideration when selecting. (Note) Set one of the following parameters which is suitable for your manual pulse generator. - 5V manual pulse generator (UFO-01-2Z9) : #1240 set12/bit0 = 1 (100 pulse/rev) -12V manual pulse generator (HD60C) : #1240 set12/bit0 = 0 ( 25 pulse/rev)
Connect the 5V manual pulse generator to the connector MPG.

Connect the 12V manual pulse generator to the connector MPG.

(Note 1) When selecting a manual pulse generator, make sure that its case and 0V terminal are insulated. (Note 2) Select 25pulse/rev or 100pulse/rev on the parameter screen.

4.3.3.1 Handle Numbers
Unit configuration decides handle Nos. "ENC": Connector on control unit "MPG": Connector on operation panel I/O unit
Operation panel I/O unit (FCU7-DX71x/ DX72x/ DX73x/DX621) 1st handle 2nd handle 3rd handle
Used "MPG" 1ch "MPG" 2ch "ENC" 1ch (Note)
Not used "ENC" 1ch "ENC" 2ch -
(Note) If one handle is only connected to "MPG", the handle connected to "ENC" 1ch will still be treated as the 3rd handle. "ENC" 2ch is not employed when an operation panel I/O unit is used.
Connect the machine operation panel to the connector CG31, CG32, CG33, CG34, CG35 or CG36.

Cable drawing: "Cable: F351 Cable" Connector pin assignment: "General Specifications: Operation Panel I/O Unit" (CG31/CG32/CG33/CG34/CG35/ CG36 connector)

4.3.4.1 Wiring for 24V Common Input
For connection details, refer to the descriptions on machine input connector pin assignment in "(1) Machine input (CG31)", "(2) Machine input (CG33)", and "(3) Machine input (CG35)" under Section "General Specifications: Operation Panel I/O Unit".

For connection details, refer to the descriptions on machine input connector pin assignment in "(1) Machine input (CG31)", "(2) Machine input (CG33)", and "(3) Machine input (CG35)" under Section "General Specifications: Operation Panel I/O Unit".


4.3.4.3 Wiring for Source Type Output (FCU7-DX621/DX711/DX721/DX731)

20B 19B 18B 17B 16B 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B
Y200 Y201 Y202 Y203 Y204 Y205 Y206 Y207 Y208 Y209 Y20A Y20B Y20C Y20D Y20E Y20F Y210 Y211 Y212 Y213 Y214 Y215 Y216 Y217 Y218 Y219 Y21A Y21B Y21C Y21D Y21E Y21F
20A 19A 18A 17A 16A 15A 14A 13A 12A 11A 10A 9A 8A 7A 6A 5A
(Note 1) Connect +24V to either or both of the flat connector 1B, 2B (24VDC). (*1) (Note 2) Connect +24V (GND) to the flat connector 3A, 3B, 4A, 4B (24VDC). (*1) Decide the number of 24VDCs to wire with regard to the total amount of each connector's maximum output current and the voltage drop by the cables. The rated current is 1A per connector pin. (Note 3) Connect 0V (GND) to the flat connector 1A, 2A (GND). (*2) (Note 4) When large current flows due to small amount of connected load, fuse may be blown out or 24V power supply voltage may drop. In order to secure the appropriate current value, watch the connected load.

4.3.4.4 Outline of Analog Signal Output Circuit

The analog signal output circuit can be used only for the FCU7-DX621/DX721.

4.4 Connection of Remote I/O Unit
This chapter describes the connection of the remote I/O unit and machine control signals.

(Note) A remote I/O unit has one or two rotary switch(es) for unit No. setting, which links the device Nos. (with X/ Y). The rotary switch setting is as follows, from "0" to "7".
No. Rotary switch
Station

When connecting to the operation panel I/O unit

Occupies the station No. 1, 2, 3, 7, 8
(Note) Operation panel I/O unit occupies the specified Nos. of stations. (Station No. 7 and 8 are reserved for manual pulse generator.) RIO3 can use either four stations (3rd to 6th) or three stations (4th to 6th) which depends on the operation panel I/O unit type.

4.4.2 Station No. Setting when Using Multiple Remote I/O Units
Multiple remote I/O units can be used, as long as the total No. of occupied stations connected with serial links is eight or less. (three/four or less when connected to the operation panel I/O unit).

When using multiple remote I/O units, a characteristic station No. must be set for each unit. The FCUA-DX101 unit has one rotary switch, FCUA-DX111, DX121 and DX141 unit have two. Each of these switches must be set to a characteristic station No. within a range of 0 to 7 (2 or 3 to 5 when connected to the operation panel I/O unit).
Setting example 1

Setting example 2


Setting example 3


When connecting to the operation panel I/O unit
Station No. 1, 2, 7, 8 (or 1, 2, 3, 7, 8) are occupied by the operation panel I/O unit. (Station No. 7 and 8 are reserved for manual pulse generator.) The maximum numbers of stations and I/O points assigned to remote I/O unit(s) via RIO3 are as follows.

Operation panel I/O unit type Max. number of stations (RIO3
FCU7-DX711 4 stations (No. 3 to 6) 128 points/128 points 2 to 5
FCU7-DX621/721/731 3 stations (No. 4 to 6) 96 points/96 points 3 to 5

Setting example 2


Setting example 3


4.4.3 Connecting FCUA-DX101/141 Unit with Machine Control Signal
Type of machine input/output signal and
32 points 32 points


Input Output · number of points

<Signal assignment>
<CAUTION>
FCUA-DX101/141
Machine side control panel, etc.
When using two or more remote I/O units or when connecting to the operation panel I/O unit, the signal assignment will differ. Refer to the "PLC Interface Manual" for details. The I/O assignment shows an example when the units are connected to the control unit and the station No. is set to “2”.
B X40 X41 X42 X43 X44 X45 X46 X47 X48 X49 X4A X4B X4C X4D X4E X4F
A X50 X51 X52 X53 X54 X55 X56 X57 X58 X59 X5A X5B X5C X5D X5E X5F
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
DI-L
0V(RG)
COM
COM 0V(RG) 0V(RG) A
24VDC 24VDC
B
DO-L
B Y40 Y41 Y42 Y43 Y44 Y45 Y46 Y47 Y48 Y49 Y4A Y4B Y4C Y4D Y4E Y4F
A Y50 Y51 Y52 Y53 Y54 Y55 Y56 Y57 Y58 Y59 Y5A Y5B Y5C Y5D Y5E Y5F
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
RA
DO-L
R
PL
0V(RG)
24VDC 24VDC
0V(RG) 0V(RG) A
B
RIO1 1 2 3 TxRx TxRx* LG
RIO2 1 2 3 TxRx TxRx* LG
24VDC(+)
Y
0V(RG)
R-TM
<Adaptive connector>

(Note 1) ( ) is the MITSUBISHI original type name. (Note 2) Refer to "Cable: R-TM Terminator Connector" for the details of R-TM.

4.4.4 Connecting FCUA-DX141 Unit with Analog Input/Output Signal
For the analog input/output signal, connect the FCUA-R031 cable to "AIO". Up to four input points and one output point can be connected for the analog input/output signal. When manufacturing the FCUA-R031 cable, use the FCUA-CS000 connector set (optional, with both ends).




4.4.5 Connecting FCUA-DX111 Unit with Machine Control Signal
Type of machine input/output signal and
64 points 48 points



Input Output · number of points

<Signal assignment>
When using two or more remote I/O units or when connecting to the operation panel I/O unit, the signal assignment will differ. Refer to the "PLC Interface Manual" for details. The I/O assignment shows an example when the station No. is set to "2".
DI-L
DI-R
B X40 X41 X42 X43 X44 X45 X46 X47 X48 X49 X4A X4B X4C X4D X4E X4F
A X50 X51 X52 X53 X54 X55 X56 X57 X58 X59 X5A X5B X5C X5D X5E X5F
B X60 X61 X62 X63 X64 X65 X66 X67 X68 X69 X6A X6B X6C X6D X6E X6F
A X70 X71 X72 X73 X74 X75 X76 X77 X78 X79 X7A X7B X7C X7D X7E X7F
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
control panel, etc.
0V(RG)
DI-R
24VDC(+)
COM
COM
COM
COM
24VDC 24VDC 24VDC 24VDC
0V(RG) 0V(RG)
0V(RG) 0V(RG)
B
A
B
A
0V(RG)
DO-L DO-R
B Y40 Y41 Y42 Y43 Y44 Y45 Y46 Y47 Y48 Y49 Y4A Y4B Y4C Y4D Y4E Y4F
A Y50 Y51 Y52 Y53 Y54 Y55 Y56 Y57 Y58 Y59 Y5A Y5B Y5C Y5D Y5E Y5F
B Y60 Y61 Y62 Y63 Y64 Y65 Y66 Y67 Y68 Y69 Y6A Y6B Y6C Y6D Y6E Y6F
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
DO-L
RA
R
PL
0V(RG)
24VDC(+)
DO-R
RA
24VDC 24VDC 24VDC 24VDC
0V(RG) 0V(RG)
0V(RG) 0V(RG)
B
A
B
R
PL
RIO1
RIO2
D CIN
0V(RG)
1 2 3 1 2 3 1 2 3
24VDC(+)
Y
R-TM
0V(RG)
<Adaptive connector>

(Note 1) ( ) is the MITSUBISHI original type name. (Note 2) Refer to "Cable: R-TM Terminator Connector" for the details of R-TM.

4.4.6 Connecting FCUA-DX121 Unit with Machine Control Signal
Type of machine input/output signal and
64 points 48 points 1 point



Input Output Analog · output · number of points

<Signal assignment>
<CAUTION>
When using two or more remote I/O units or when connecting to the operation panel I/O unit, the signal assignment will differ. Refer to the "PLC Interface Manual" for details. The I/O assignment shows an example when the station No. is set to "2".
DI-L DI-R
B X40 X41 X42 X43 X44 X45 X46 X47 X48 X49 X4A X4B X4C X4D X4E X4F
A X50 X51 X52 X53 X54 X55 X56 X57 X58 X59 X5A X5B X5C X5D X5E X5F
B X60 X61 X62 X63 X64 X65 X66 X67 X68 X69 X6A X6B X6C X6D X6E X6F
A X70 X71 X72 X73 X74 X75 X76 X77 X78 X79 X7A X7B X7C X7D X7E X7F
Machine side control panel, etc.
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
24VDC(+)
DI-R
24VDC(+)
COM
COM 0V 0V A
COM
COM 0V 0V A
24VDC 24VDC 24VDC 24VDC
B
B
DO-L DO-R
B Y40 Y41 Y42 Y43 Y44 Y45 Y46 Y47 Y48 Y49 Y4A Y4B Y4C Y4D Y4E Y4F
A Y50 Y51 Y52 Y53 Y54 Y55 Y56 Y57 Y58 Y59 Y5A Y5B Y5C Y5D Y5E Y5F
B Y60 Y61 Y62 Y63 Y64 Y65 Y66 Y67 Y68 Y69 Y6A Y6B Y6C Y6D Y6E Y6F AO
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
DO-L
RA
PL R
DO-R
24VDC(+)
AO*
RA
24VDC 24VDC 24VDC 24VDC
0V 0V A
0V 0V A
B
B
R
PL
RIO1 1 2 3 TxRx TxRx*
D CIN 1 2 3 +24V 0V FG
TxRx LG 1 2 3
Y
R-TM
<Adaptive connector>

(Note 1) ( ) is the MITSUBISHI original type name. (Note 2) Refer to "Cable: R-TM Terminator Connector" for the details of R-TM.

4.5 Connection of MITSUBISHI CNC Machine Operation Panel
(Note) In this chapter "MITSUBISHI CNC Machine operation panel" is shorten to Machine operation panel. Connect Machine operation panel A to the remote I/O unit I/F of control unit or operation panel I/O unit. - Machine operation panel A (RIOIN) - cable (FCUA-R211 or SH41) - control unit (RIO1) - Machine operation panel A (RIOIN) - cable (FCUA-R211 or SH41) - operation panel I/O unit (RIO3)
When supplying power to control unit from Machine operation panel A, the following connection is necessary. - Machine operation panel A (DCOUT) - cable (G071) - control unit (DCIN)
Connect Machine operation panel B to Machine operation panel A and control unit as follows. - Machine operation panel B - cable (G460) - Machine operation panel A (SUBP) - Machine operation panel B - cable (F120) - control unit (EMG)
[When connecting to operation panel I/O unit (RIO3)]

HN232 Card (Placed on the back of the panel A)
Cable drawing: "Cable: F120 Cable" "Cable: FCUA-R211 Cable" "Cable: G460 Cable" "Cable: SH41 Cable" "Cable: G011 Cable" Connector pin assignment: "General Specifications: Operation panel I/O unit" (RIO3 connector/DCIN connector/ DCOUT connector/ RIOIN connector/SUBP connector/EMG connector/CG71 connector)

<Software Interface>
Machine operation panel occupies RIO station No. 4 to 6. The device numbers for switch and LED on operation panel are fixed as listed below. The following lists the devices for using the RIO 1st channel.
Station Device No. Detail RIO1 RIO3
1 X00 ~X1F/Y00 ~Y1F X200 ~X21F/Y200 ~Y21F
2 X20 ~X3F/Y20 ~Y3F X220 ~X23F/Y220 ~Y23F
3 X40 ~X5F/Y40 ~Y5F X240 ~X25F/Y240 ~Y25F
4 X60 ~X7F/Y60 ~Y7F X260 ~X27F/Y260 ~Y27F Machine operation panel B
(Switch)...16 points vacant
5 X80 ~X9F/Y80 ~Y9F X280 ~X29F/Y280 ~Y29F Machine operation panel A
Machine operation panel A (Key switch/LED)
6 XA0 ~XBF/YA0 ~YBF X2A0 ~X2BF/Y2A0 ~
7 XC0 ~ XDF/YC0 ~ YDF -
8 XE0 ~ XFF/YE0 ~ YFF -
(1) Machine operation panel B (Switch) Machine operation panel B is equipped with rotary switches (cutting override, spindle override) and a selector switch (memory protection key), and an emergency stop button. Direct wiring connection will be applied to the emergency stop button, and device numbers for other switches are defined as listed below.
21 position code list
Device No.
Setting value X60 X61 X62 X63 X64 X65
0
1 1 0 1
2 1 1 0
3 0 1 0 0 0 1
4 0 1 1 0 0 0
5 1 1 1 0 0 1
6 1 0 1 0 0 0
7 0 0 1 0 0 1
8 0 0 1 1 0 0
9 1 0 1 1 0 1
10 1 0 0
11 0 1 1 1 0 1
12 0 1 0 1 0 0
13 1 1 0 1 0 1
14 1 0 0 1 0 0
15 0 0 0 1 0 1
16 0 0 0 1 1 0
17 1 0 0 1 1 1
18 1 1 0 1 1 0
19 0 1 0 1 1 1
20 0 1 0
(Key switch/LED)

(b) Spindle override (6bit)
8 position code list

Memory protection switch X6C Spare X6D - X6F
(2) Machine operation panel A (Key switch/LED) Machine operation panel A is equipped with 55 switches and 55 LEDs. They are allocated X device and Y device as in the figure below.

X/Y
X/Y
X/Y
(Note1) If the stations of Machine operation panel and other RIO unit overlap, all the connections of the overlapping RIOs will be invalidated and cannot be used. Stations which do not overlap can be used. (Note2) Refer to the last page "Table: Device No. for Machine operation panel" for the device No. when connecting to RIO3.


付録 Ap 1 章
Cable

(Note) Symbols for writing cable drawings
(1) indicates twisted pair.
(2) indicates the shield sheath.
(3) indicates shield clamping to the grounding plate. (4) In the cable drawings, the partner of the twisted pair cable is given a priority, so the pin No. of the connectors at both ends are not necessary in number of order. (5) Equivalent parts can be used for the connector, contact and wire material.

Appendix 1.1 Cable Wire and Assembly
(1) Cable wire The specifications of the wire used for each cable, and the machining methods are shown in this section. When manufacturing the detector cable and battery connection cable, use the recommended wires shown below or equivalent products.
Wire type (special order part)
No. of
BD20288 Compound 6-pair shielded cable Specification No. Bangishi-17145 (Note 1)
2 (0.5mm2) 100 strands/ 0.08mm
40.7Ω/km or less 500VAC/ 1min 1000MΩ/km or more 105C° 70 × 104 times or more at R200 4 (0.2mm2) 40 strands/ 0.08mm
8.7mm Heat resistant
(b) General-purpose heat resistant specifications cable
Wire type (special order part)
Sheath material No. of pairs
BD20032 Compound 6-pair shielded cable Specification No. Bangishi-16903 Revision No. 3 (Note 1)
2 (0.5mm2) 100 strands/ 0.08mm
40.7Ω/km or less
500VAC/ 1min 1000MΩ/ km or more 60C° 100 × 104 times or more at R200 4 (0.2mm2) 40 strands/ 0.08mm
8.7mm PVC
(Note 1) Bando Electric Wire (Contact: +81-48-461-0561 http://www.bew.co.jp) (Note 2) The Mitsubishi standard cable is the (a) Heat resistant specifications cable. For MDS-C1/CH series, (b) or equivalent is used as the standard cable.

Compound 6-pair cable structure drawing
B1 B4
B3
B2
A2
Pair No. Insulator color L1 L2 A1 (0.5mm2) Red White A2 (0.5mm2) Black White B1 (0.2mm2) Brown Orange B2 (0.2mm2) Blue Green B3 (0.2mm2) Purple White B4 (0.2mm2) Yellow White

(2) Cable assembly Assemble the cable with the cable shield wire securely connected to the ground plate of the connector.
Connect with a ground plate of connector.
Core wire · Shield (external conductor) · Sheath

Appendix 1.2 CNP2E-1 Cable
Max. cable length: 30m Application: Motor side PLG cable
Spindle side accuracy detector TS5690 cable
Spindle drive unit side connector
Spindle motor side connector
7 8 2 1 5 6 3 4 9
P5(+5V) LG MT1 MT2 SD SD* RQ RQ* SHD
0.5mm2
MT1 MT2
0.2mm2
7 8 3 4
0.2mm2
0.2mm2
(Note) For the pin "7" or "8", use the contact "170364-1". For the other pins, use the contact "170363-1".
Spindle drive unit side connector
Spindle motor side connector
7 8 2 1 5 6 3 4 9
P5(+5V) LG MT1 MT2 SD SD* RQ RQ* SHD
0.5mm2
LG
0.5mm2
0.2mm2
7 8 3 4
0.2mm2
0.2mm2
(Note) For the pin "7" or "8", use the contact "170364-1". For the other pins, use the contact "170363-1".

Appendix 1.3 CNP3EZ-2P/CNP3EZ-3P Cable
Max. cable length: 30m Application: Spindle side detector cable
OSE-1024 cable CNP3EZ-2P (Straight)
CNP3EZ-3P (Angle)



Appendix 1.4 CNV22J-K1P / CNV22J-K2P Cable
Compatible with only IP65 CNV22J-K1P (load side angle) CNV22J-K2P (reverse load side angle)
Servo drive unit side connector
Servo motor detector/ Ball screw side detector side connector Plug: 1747464-1 Contact: 1674335-4 Plug: CM10-CR10P-M
8 5 4 6 7 1 2
P5(+5V) LG P5(+5V)
0.08mm2
CNT BT SD SD* RQ RQ* SHD
1 2 8 7 5 4 9 10
0.08mm2
0.08mm2
0.08mm2
Case grounding ·

Appendix 1.5 CNV2E-8P/CNV2E-9P Cable
For HF-KP (Servo) Motor side detector relay cable (Drive unit side) (CNV2E-8P) CNV2E-8P (Straight)

8 5 3 4 6 7 1 2 10
P5(+5V) LG CNT BT SD SD* RQ RQ* SHD

8 5 3 4 6 7 1 2 10
P5(+5V) LG CNT BT SD SD* RQ RQ* SHD

Appendix 1.6 CNV2E-HP Cable
Max. cable length: 30m Application: MDS-B-HR unit cable
Drive unit side connector
MDS-B-HR unit side connector
5 7 6 8 1 2 3 4 PE
0.5mm2
0.5mm2
LG
0.2mm2
0.2mm2
7 8 PE

Appendix 1.7 CNV2E-K1P / CNV2E-K2P Cable
Max. cable length: 10m Application: For HF-KP (Servo) Motor side detector cable
Compatible with only IP65 CNV2E-K1P (load side angle) CNV2E-K2P (reverse load side angle)

Servo motor detector connector (Tyco Electronics AMP) Connector : 1674320-1
3 6 5 4 8 7 2 1 9
P5 P5G MR MRR MD MDR BAT CONT SD

Appendix 1.8 DG21 Cable
Drive unit side connector
Battery unit side connector
BT LG
0.2mm2
(Hirose Electric) (3M) · Case grounding

Appendix 1.9 DG22 Cable
(Note) This cable is required to supply the power from the battery unit to multiple drive units.
Drive unit side connector
Drive unit side connector
(Hirose Electric) (Hirose Electric)
0.2mm2

Appendix 1.10 DG23 Cable
(Note) The battery box side is connected using a bare conductor or a terminal bar.


Appendix 1.11 DG24 Cable
(Note) The battery box side is connected using a bare conductor or a terminal bar.


(For MDS-D2/DH2) · (For MDS-DM2)

Appendix 1.12 DG25 Cable


Appendix 1.13 F023/F024 Cable
Max. cable length: 20m Application: Manual Pulse Generator (5V spec)


Cable name 1ch 2ch
F023 cable ○ F024 cable ○ ○
(Note) Fold the cable shield over the sheath, and wrap copper foil tape over it. Connect the wound copper foil tape to GND plate of the connector.

Appendix 1.14 F034/F035 Cable
Max. cable length: 15m (the maximum length of the cable when connected to the control unit via other


Cable name 1ch 2ch
F034 cable ○ F035 cable ○ ○
(Note 1) Fold the cable shield over the sheath, and wrap copper foil tape over it. Connect the wound copper foil tape to GND plate of the connector. (Note 2) Signal names in parentheses "( )" are generally used. (Note 3) Connect to the serial communication connector of the control unit. Use G031/G032 cable when connecting to the serial communication connector of the display unit.

Appendix 1.15 F070 Cable
Max. cable length: 30m Application: 24VDC power cable
DCIN
Y
DCIN
+24V 0V FG
+24V 0V

Appendix 1.16 F110 Cable
Max. cable length: 15m Application: 24VDC power cable for PD25/PD27
DCIN
DCOUT
Y
CF01

[DCIN] Connector: 2-178288-3 Contact: 1-175218-5 ×3 Recommended manufacturer: Tyco Electronics [CF01] Connector: 005057-9402 Contact: 0016020103 ×2 Recommended manufacturer: MOLEX

Appendix 1.17 F120 Cable
Max. cable length: 30m Application: Emergency stop cable
EMG
EMG
B22-9
FG EMG IN
EMG IN COM
COM

Appendix 1.18 F170 Cable
Max. cable length: 15m Application: ON/OFF switch cable for PD25/PD27
ON/OFF
:
ON/OFF
1 2 3 4 5
OFF-1 OFF-2 ON-1 ON-2
(Note) Select the crimp terminal suitable for the terminal block and switch you use.

Appendix 1.19 F221 Cable
Max. cable length: 30m Application: Analog output
AO
AO
AO
AO
GND
GND
(Note 1) Follow the instruction of the machine side in connecting the shield. Do not connect on the base I/O unit side. (Note 2) Select the crimp terminal suitable for the terminal block you use.

Appendix 1.20 F320/F321 Cable
Max. cable length: 50m Application: Manual Pulse Generator (12V spec)
HANDLE

Cable name 1ch 2ch
F320 Cable ○ F321 Cable ○ ○
(Note) Fold the cable shield over the sheath, and wrap copper foil tape over it. Connect the wound copper foil tape to GND plate of the connector.

Appendix 1.21 F351 Cable
Max. cable length: 50m Application: DI/DO
CG31,CG32,CG33,CG34,CG35,CG36
[CG31, CG32, CG33, CG34, CG35, CG36] Connector: 7940-6500SC Strain relief: 3448-7940 Recommended manufacturer: 3M
(Note) This cable is used to connect the operation panel I/O unit. Select FCUA-R300, which doesn’t have strain relief, when connecting to remote I/O unit.

Appendix 1.22 FCUA-R030 Cable
Max. cable length: 20m Application: SKIP input cable
SKIP

(Note) Fold the cable shield over the sheath, and wrap copper foil tape over it. Connect the wound copper foil tape to GND plate of the connector.

Appendix 1.23 FCUA-R031 Cable
Max. cable length: 30m Application: Analog input/output (for remote I/O unit)
AIO

(Note) Fold the cable shield over the sheath, and wrap copper foil tape over it. Connect the wound copper foil tape to GND plate of the connector.

Appendix 1.24 FCUA-R050/R054 Cable
Max. cable length: 30m Application: Synchronous encoder - control unit


ENC1A (ENC2A) ENC1A*(ENC2A*) ENC1B (ENC2B) ENC1B*(ENC2B*) ENC1Z (ENC2Z) ENC1Z*(ENC2Z*)
[FCUA-R050 cable] Connector: MS3106B20-29S Cable clamp: MS3057-12A Recommended manufacturer: ITT Cannon [FCUA-R054 cable] Connector: MS3108B20-29S Cable clamp: MS3057-12A Recommended manufacturer: ITT Cannon
(Note) Fold the cable shield over the sheath, and wrap copper foil tape over it. Connect the wound copper foil tape to GND plate of the connector.

Appendix 1.25 FCUA-R211 Cable
Max. cable length: 30m (the maximum length of the cable when connected to the control unit via other
between remote I/O, remote I/O-CNC control unit, remote I/O-Operation panel I/O unit, remote I/O-MITSUBISHI CNC machine operation panel A

(FCUA-R211)
TXRX TXRX*
TXRX TXRX* 0V
FG FG
Wire material:
MVVS 3C×0.5mm2 (MIC 3C×0.5mm2) Recommended manufacturer: Takeuchi Densen
(Note) Fold the cable shield over the sheath, and wrap copper foil tape over it. Connect the wound copper foil tape to GND plate of the connector.

Appendix 1.26 FCUA-R300/FCUA-R301 Cable
Type: FCUA-R300 Max. cable length: 50m Application: DI/DO cable (one side connector)
(for remote I/O unit)

(for remote I/O unit)

There are two types of cable for the remote I/O unit: FCUA-R300 and FCUA-R301. The FCUA-R300 cable has one end cut off, and the FCUA-R301 cable is used for connection to the IDEC terminal block BX1F-T40A (Note 1). If a cable longer than 3m is required, use the connector set FCUA-CN300 or FCUA- CS301. The one-end FCUA-CN300 connector (optional, with one end) includes the DI-L (DI-R) and DO-L (DO-R) connectors. The FCUA-CS301 connector (optional, with both ends) includes the DI-L (DI-R) and DO-L (DO-R) connectors, and two connectors for connection with the terminal block (IDEC). (Note 1) IDEC I/O terminal BX1F-T40A


16 14 10 12 8 6 4 2 32 30 26 28 24 22 20 18 34 36 38 40
15 13 9 11 7 5 3 1 31 29 25 27 23 21 19 17 33 35 37 39


Appendix 1.27 G011 Cable

(Note) Fold the cable shield over the sheath, and wrap copper foil tape over it. Connect the wound copper foil tape to GND plate of the connector.

Appendix 1.28 G023/G024 Cable
Max. cable length: 20m (the maximum length of the cable when connected to the control unit via other
(for connection to control unit)
ENC

Cable name 1ch 2ch
G023 cable ○ G024 cable ○ ○
(Note) Fold the cable shield over the sheath, and wrap copper foil tape over it. Connect the wound copper foil tape to GND plate of the connector.

Appendix 1.29 G071 Cable
Y
Y
R R
GND
GND
FG
G G
FG
(Note) These cables are available only when wired to a same control panel.

Appendix 1.30 G300 Cable
Max. cable length: 10m Application: LAN cross cable (Shielded cable is recommended when the length will be 1m or more)



Appendix 1.31 G301 Cable
Max. cable length: 1m Application: LAN straight cable (Shielded cable is recommended when the length will be 1m or more)


Appendix 1.32 G380 Cable
Max. cable length: 30m Application: Optical communication cable
for wiring between drive units (outside panel) for optical communication repeater unit Use when the cable length is 10m or more to 30m or less.
Section with reinforced sheath
Section without reinforced sheath
OPT
2-core cable (section with reinforced sheath) 50mm
2-core cable (section without reinforced sheath) 25mm
(Note 1) Binding the cables too tight with tie-wraps could result in an increased loss or a disconnection. Use a
cushioning material such as a sponge or rubber when bundling the cables and fix so that the cables do not move. Recommended clamp material: CKN-13SP KITAGAWA INDUSTRIES. (Note 2) Never bundle the cables with vinyl tape. The plasticizing material in the vinyl tape could cause the PCF cable
reinforced sheath to damage. (Note 3) Loop the excessive cable with twice or more than the minimum bending radius.

Appendix 1.33 G395 Cable
Max. cable length: 10m Application: Optical communication cable
for wiring between drive units (outside panel) for wiring between NC-drive units Use when wiring outside of the panel with a cable of 10m or less.
OPT OPT Section with reinforced sheath
Section without reinforced sheath
OPT
2-core cable (section with reinforced sheath) 50mm
2-core cable (section without reinforced sheath) 30mm
(Note 1) Binding the cables too tight with tie-wraps could result in an increased loss or a disconnection. Use a
cushioning material such as a sponge or rubber when bundling the cables and fix so that the cables do not move. Recommended clamp material: CKN-13SP KITAGAWA INDUSTRIES. (Note 2) Never bundle the cables with vinyl tape. The plasticizing material in the vinyl tape could cause the POF cable
to break. (Note 3) Loop the excessive cable with twice or more than the minimum bending radius.

Appendix 1.34 G396 Cable
Max. cable length: 10m Application: Optical communication cable
for wiring between drive units (inside panel) Use when wiring in the panel with a cable of 10m or less.
OPT
OPT
2-core parallel cord 30mm
(Note 1) Binding the cables too tight with tie-wraps could result in an increased loss or a disconnection. Use a
cushioning material such as a sponge or rubber when bundling the cables and fix so that the cables do not move. Recommended clamp material: CKN-13SP KITAGAWA INDUSTRIES. (Note 2) Never bundle the cables with vinyl tape. The plasticizing material in the vinyl tape could cause the POF cable
to break. (Note 3) Loop the excessive cable with twice or more than the minimum bending radius.

Appendix 1.35 G460 Cable


[RSW1][RSW2] 1 : Purple 2 : Blue 3 : Green 4 : Yellow 5 : Orange 6 : Red 7 : Brown
Connector with cable : ACX011-705 x 2 Contact: 1-175218-5 x 3 Recommended manufacturer: Fuji Electric [SW-NO][SW-C] Connector: STO-01T-110N Recommended manufacturer: JST
(Note) Coat the connector [SW-NO][SW-C] with an insulation.

Appendix 1.36 MR-BKS1CBL-A1-H / MR-BKS1CBL-A2-H Cable
Max. cable length: 10m Application: <200V Series> Brake cable for HF-KP
MR-BKS1CBL-A1-H (load side angle) MR-BKS1CBL-A2-H (reverse load side angle)
Servo motor brake connector (Japan Aviation Electronics)
B1
AWG 20
B2
Hood, Socket insulator, ·

Appendix 1.37 MR-PWS1CBL-A1-H / MR-PWS1CBL-A2-H Cable
Max. cable length: 10m Application: <200V Series> Power cable for HF-KP
MR-PWS1CBL-A1-H (load side angle) MR-PWS1CBL-A2-H (reverse load side angle)
Servo motor power supply connector (Japan Aviation Electronics) Connector: JN4FT04SJ1 Hood, Socket insulator, Bushing and Grand nut Contact: ST-TMH-S-C1B-100(A534G) Crimp tool: CT160-3TM5B
AWG 19 (Red) AWG 19 (White) AWG 19 (Black) AWG 19 (Green/ Yellow)

Appendix 1.38 R-TM Terminator Connector
Application: Terminator for OPI interface
R-TM
R-TM
TXRX*
TXRX
(Note 1) The parts used shall be Mitsubishi recommended parts. Equivalent parts may be used providing they are
compatible with the specifications.
(Note 2) Cover the 100Ω terminator with a black insulation tube. (Note 3) Stamp the connector name "R-TM" in white on the rear of the connector.

Appendix 1.39 SH21 Cable
Max. cable length: 30m Application: Power supply communication cable
Power backup unit communication cable Cable for Auxiliary axis/Servo drive units
SV1, SV2
SVTXD SVTXD*
SVTXD SVTXD*
SVALM SVALM*
SVALM SVALM*
SVRXD SVRXD4
SVRXD SVRXD4
SVEMG SVEMG*
SVEMG SVEMG*
+5V
+5V
FG FG
(Note) Fold the cable shield over the sheath, and wrap copper foil tape over it. Connect the wound copper foil tape to GND plate of the connector.

Appendix 1.40 SH41 Cable
Max. cable length: 1m (the maximum length of the cable when connected to the control unit via other units) Application: Remote I/O cable
between remote I/O, remote I/O-CNC control unit, remote I/O-Operation panel I/O unit, remote I/O-MITSUBISHI CNC machine operation panel A (between remote I/O units in a panel)
RIO1,RIO3(CSH41)
(CSH41)
TXRX TXRX*
TXRX TXRX* 0V
Wire material:
MVVS 3C×0.5mm2 (MIC 3C×0.5mm2) Recommended manufacturer: Takeuchi Densen
(Note 1) Protect both ends of the cable with insulated bushing. (Note 2) RIO1 and RIO3 can be used commonly. (Note 3) Use this cable for short applications, such as bridging the remote I/O units in the same panel. Normally use the FCUA-R211 cable with high noise withstand level.

Appendix 1.41 List of Cable Connector Sets

FCUA-CN200 200VAC power supply connector (for power supply unit PD25/PD27)
24VDC power supply connector for power supply unit (PD25/PD27) (with power OFF detection)


付録 Ap 2 章
EMC Installation Guidelines

For details of the drive section (servo/spindle drive unit), refer to the "EMC Installation Guidelines" of instruction manuals for each drive unit.
EMC Directives became mandatory as of January 1, 1996. The subject products must have a CE mark attached indicating that the product complies with the Directives. As the NC unit is a component designed to control machine tools, it is believed that it is not a direct EMC Directives subject. However, we would like to introduce the following measure plans to back up EMC Directives compliance of the machine tool as the NC unit is a major component of the machine tools.
(1) Methods of installation in control/operation panel (2) Methods of wiring cables to outside of panel (3) Introduction of members for measures
Mitsubishi is carrying out tests to confirm the compliance to the EMC Directives under the environment described in this manual. However, the level of the noise will differ according to the equipment type and layout, control panel structure and wiring lead-in, etc. Thus, we ask that the final noise level be confirmed by the machine manufacturer.
The EMC Directives largely regulate the following two items.
- Emission Capacity to prevent output of obstructive noise that adversely affects external devices. - Immunity Capacity to not malfunction due to obstructive noise from external source. The details of each level are classified in the table below. It is assumed that the Standards and test details required for a machine tool are the same as these.
Class Name Details EN Standards
Radiated noise Restriction of electromagnetic noise radiated through the air
EN61000-6-4 (General industrial machine) EN61800-3 (Motor control unit)
(Example) Regulation of withstand level of static electricity electrical discharge accumulated in human body
Static electricity electrical discharge
Radiation immunity (Example) Simulation of immunity from digital wireless telephones EN61000-4-3
Burst immunity (Example) Regulation of withstand level of noise from relay or plug and play EN61000-4-4
EN61000-6-2 (General industrial machine) EN61800-3 (Motor control unit)
Conductive immunity (Example) Regulation of withstand level of noise flowed from power supply wires, etc. EN61000-4-6
Power supply frequency magnetic field
(Example) Regulation of electromagnetic noise of 50/ 60Hz power supply frequency EN61000-4-8
Power supply dip (fluctuation)
(Example) Regulation of power voltage drop withstand level EN61000-4-11
Surge (Example) Regulation of withstand level of noise caused by lightning EN61000-4-5
Emission · Immunity

Appendix 2.3 EMC Measures
The main items relating to EMC measures include the following.
(1) Store the device in a sealed metal panel. (2) Ground all conductors that are floating electrically. Decrease the impedance. (3) Increase the distance between the drive line and signal wire. (4) Shield the cables wired outside of the panel. (5) Install a noise filter.
Take care to the following items to suppress the noise radiated outside of the panel.
(1) Accurately ground the devices. (2) Use shielded cables. (3) Increase the electrical seal of the panel. Reduce the gaps and holes.
The design of the panel is a very important factor for the EMC measures, so take the following measures into consideration.
(1) Use metal for all members configuring the panel. (2) When joining the metal plate, treat the welded or contacting sections so that the impedance is reduced, and then fix with screws.
Joining clearance:Approx. 20cm
(3) Note that if the plate warps due to the screw fixing, etc. By creating a clearance, noise could leak from that place. (4) Plate (nickel tin) the metal plate surface at the grounding plate, and connect the connections with a low impedance. (5) If there is a large opening, such as ventilation holes, make sure to close the hole.
Mesh cover (conductive sponge)
(Note 1) Using screws to fix the plates that have been painted is the same as an insulated state. Peel the paint and fix the screws.
Painting mask · Control panel · Opening

Appendix 2.4.2 Measures for Door
(1) Use metal for all members configuring the panel. (2) When joining the door, use a gasket to lower the impedance of the contacting sections, or use a structure with a large contact area as shown below. (3) The EMI gasket or conductive packing must contact the metal surface uniformly and at the correct position.
Use of gasket Large contact area
(Note 1) When not using a gasket, ground the control panel grounding with a grounding wire to lower the door's impedance. (Note 2) Using screws to fix the plates that have been painted (attachment of packing) is the same as an insulated state. Peel the paint and fix the screws.
(1) Shield the power supply section and insert a filter to prevent the noise from flowing in or out. Selection of the noise filter capacity will differ according to the drive unit and devices being used. Refer to the "EMC Installation Guidelines" (BNP-B8582-45).
Conductive noise Conductive noise Noise filter
(Note 1) The conductive noise can be suppressed by inserting a noise filter, but the radiated noise will flow out. (Note 2) The conductive and radiated noise can both be suppressed by adding a partition plate to the noise filter.

Appendix 2.5 Measures for Wiring in Panel
Cables act as antennas to propagate unnecessary noise, and thus must be appropriately shielded and treated. The following measures must be sufficiently considered for the cables (SH21/G018/F012/FCUA-R211) that carry out high-speed communication.
(1) If the cables are led unnecessary in the panel, they will pick up noise. Pay attention to the device layout and wire length so that the wiring length is as short as possible.
Device
(2) Always connect the grounding wire to the FG terminal indicated on the device. (3) Keep the distance between the drive line and detector cable to the drive section motor as far apart as possible when wiring. (4) Do not lead the power supply wire around the panel without using a filter.
![Page 191 of the Mitsubishi Electronics Freqrol E70 user manual — (2) Remote I/O cable [FCUA-R211 cable]](/cdn/reader/be/be4646ece03a49592ccc934c31a00ecac7aa46ef3481bcfce32ff74c6884f73b/images/page-191.webp?w=400)
Appendix 2.5.2 Shield Treatment of Cables
Use shielded cables for the cables wired outside the panel. Use a shield clamp within 10cm of the lead-out port from the panel. (Refer to "EMC Countermeasure Parts: Shield Clamp Fitting".)
![Mitsubishi Electronics Freqrol E70 — (1) DC power supply cable [F110/F070 cable] diagram (page 191)](/cdn/reader/be/be4646ece03a49592ccc934c31a00ecac7aa46ef3481bcfce32ff74c6884f73b/images/fig-191-1.webp)
- Use a shield clamp within 10cm from the panel's inlet/outlet. - When using a ferrite core, install it on both ends of the connected units. - Always install a ferrite core (Refer to "EMC Countermeasure Parts: Ferrite Core".) on the general-purpose stabilized power supply. The ferrite core may not be required depending on the selected power supply.
![Mitsubishi Electronics Freqrol E70 — (2) Remote I/O cable [FCUA-R211 cable] diagram (page 191)](/cdn/reader/be/be4646ece03a49592ccc934c31a00ecac7aa46ef3481bcfce32ff74c6884f73b/images/fig-191-2.webp)
- Use a shield clamp within 10cm from the panel's inlet/outlet. - When using a ferrite core, install it on both ends of the connected units.

(3) Servo communication cable [SH21 cable]
Control unit Drive section unit
- Use a shield clamp within 10cm from the panel's inlet/outlet. - When using a ferrite core, install it on both ends of the connected units.
- Use a shielded cable. Use a shield clamp within 10cm from the panel's inlet/outlet. - When using a ferrite core, install it on both ends of the connected units.

Appendix 2.6 EMC Countermeasure Parts
Appendix 2.6.1 Shield Clamp Fitting
The effect can be improved by directly connecting the cable's shield sheath to the grounding plate as shown below. Install the grounding plate near the outlet (within 10cm) of each panel, and press against the grounding plate with the clamp fitting. If the cables are thin, several can be bundled and clamped together. To provide sufficient frame ground, install the grounding plate directly on the cabinet or connect with a grounding wire.

Ground Plate #D 100 86 30 Clamp fitting A×2
Ground Plate #E 70 56 - Clamp fitting B×1

(Note 1) Screw hole for wiring to earthing plate in cabinet. (Note 2) The earthing plate thickness is 1.6mm.

Appendix 2.6.2 Ferrite Core
The ferrite core is mounted integrally with the plastic case. This can be installed with one touch without cutting the interface cable or power supply cable. This ferrite core is effective against common mode noise, allowing measures against noise without affecting the quality of the signal.

ZCAT-A, ZCAT-AP type Shape and dimensions ZCAT type
Part Name A B φC φD E Applicable cable outer
ZCAT1518-0730-M(-BK)*1 22±1 18±1 7±1 15±1 - 7max. 6
ZCAT1518-0730(BK)*2 22±1 18±1 7±1 15±1 - 7max. 6
ZCAT2017-0930-M(-BK) 21±1 17±1 9±1 20±1 - 9max. 11
ZCAT2032-0930-M(-BK)*1 36±1 32±1 9±1 19.5±1 - 9max. 22
ZCAT2032-0930(-BK)*2 36±1 32±1 9±1 19.5±1 - 9max. 22
ZCAT2132-1130-M(-BK)*1 36±1 32±1 11±1 20.5±1 - 11max. 22
ZCAT2132-1130(-BK)*2 36±1 32±1 11±1 20.5±1 - 11max. 22
ZCAT3035-1330-M(-BK)*1 39±1 34±1 13±1 30±1 - 13max. 63
ZCAT3035-1330(-BK)*2 39±1 34±1 13±1 30±1 - 13max. 63
ZCAT1525-0430AP-M(-BK) 25±1 20±1 4±1 15±1 11.5±1 2.5 to 4(USB) 7
ZCAT1325-0530A-M(-BK)*1 25±1 20±1 5±1 12.8±1 11.2±1 3 to 5(USB) 7
ZCAT1325-0530A(-BK) 25±1 20±1 5±1 12.8±1 11.2±1 3 to 5(USB) 7
ZCAT1730-0730A-M(-BK) 30±1 23±1 7±1 16.5±1 15±1 4 to 7(USB) 12
ZCAT2035-0930A-M(-BK)*1 35±1 28±1 9±1 19.5±1 17.4±1 6 to 9 22
ZCAT2035-0930A(-BK) 35±1 28±1 9±1 19.5±1 17.4±1 6 to 9 22
ZCAT2235-1030A-M(-BK) 35±1 28±1 10±1 21.5±1 20±1 8 to 10 27
ZCAT2436-1330A-M(-BK) 36±1 29±1 13±1 23.5±1 22±1 10 to 13 29
ZCAT2017-0930B-M(-BK) 21±1 17±1 9±1 20±1 28.5±1 9max. 12
ZCAT2749-0430C-M(-BK) 49±1 27±1 4.5±1 19.5±1 - 4.5max. 26
ZCAT4625-3430D(-BK) 45.5±1 24.5±1 34±1 12±1 - 26 For core flat cable 32
ZCAT4625-3430DT(-BK)*3 45.5±1 24.5±1 34±1 13±1 - 26 For core flat cable 32
ZCAT6819-5230D(-BK) 67.5±1 18.5±1 52±1 16±1 - 40 For core flat cable 58
ZCAT6819-5230DT(-BK)*3 67.5±1 18.5±1 52±1 17±1 - 40 For core flat cable 58
*1 The M stamp is attached. *2 A fixing band is attached at shipment. *3 The core is fixed with double-sided tape. (The tape is enclosed with the part.)

Appendix 2.6.3 Surge Absorber
Make sure that the surge does not directly enter the AC line of the general-purpose stabilized power supply (user- prepared) supplying power to the control unit and DIO. Select the following product or equivalent for the surge absorber. Refer to the manufacturer catalog for detailed characteristics, outline and connection methods of the surge absorber.

250V 3φ 300V 783V 2,500A 20kV 75pF -20 to +70°C

250V 3φ 300V 700V 2,500A 2kV 75pF -20 to +70°C
Outline drawing (a) Black (b) Black (c) Black Circuit drawing

(3) Example of surge absorber installation An example of installing the surge absorber in the machine control panel is shown below. A short-circuit fault will occur in the surge absorber if a surge exceeding the tolerance is applied. Thus, install a circuit protection breaker in the stage before the surge absorber. Note that almost no current flows to the surge absorber during normal use, so a breaker installed as the circuit protection for another device can be used for the surge absorber.


or less. If the wires are long, the surge absorber's performance may drop and inhibit protection of the devices
Surge absorber installation

Appendix 2.6.4 Selection of Stabilized Power Supply
Consider the following characteristics when selecting the stabilized power supply (prepared by machine manufacturer). Use a power supply that complies with CE Marking or that follows the safety standards given below.
Item Standard setting Remarks
Voltage fluctuation ±5% ±5% or less of 24VDC output
Ripple noise 120mV (max.)
Spike noise 500mV (max.)
Output current ―― Refer to the maximum current consumption of the unit in use and calculate.
Output holding time 20ms (min) Instantaneous power failure time (AC side)
Safety Standards: UL1950, CSA C22.2 No. 234 approved, IEC950 compliant Noise Terminal Voltage: FCC Class A, VCCI-Class A High Harmonics Current Restrictions: IEC61000-3-2
Output

付録 Ap 3 章
Restrictions for Lithium Batteries

Appendix 3.1 Restriction for Packing
The United Nations Dangerous Goods Regulations "Article 12" became effective from 2003. When transporting lithium batteries with means subject to the UN Regulations, such as by air transport, measures corresponding to the Regulations must be taken. The UN Regulations classify the batteries as dangerous goods (Class 9) or not dangerous goods according to the lithium metal content. To ensure safety during transportation, lithium batteries (battery unit) directly exported from Mitsubishi are packaged in a dedicated container (UN package) for which safety has been confirmed. When the customer is transporting these products with means subject to the UN Regulations, such as air transport, the shipper must follow the details explained in this section "Handling by User". The followings are restrictions for transportation. Each restriction is specified based on the recommendation of the United Nations.
Area Transportation method Restriction Special clause World Air ICAO, IATA - World Marine IMO 188 United States All (air, marine, land) DOT 49 CFR 173.185 Europe land RID, ADR 188

Appendix 3.1.1 Target Products
The following Mitsubishi NC products use lithium batteries. If the lithium metal content exceeds 1g for battery cell and 2g for battery, the battery is classified as dangerous good (Class9). In order to avoid an accidental actuation during the transportation, all lithium battery products incorporated in a machinery or device must be fixed securely and must be shipped with wrapped over the outer package as to prevent damage or short- circuits.
Number of incorporated ER6V batteries
Mitsubishi type (Type for arrangement) Battery type Lithium metal
Refer to "Battery Option" in the specification manual for drive unit you are using for the outline dimension drawing for servo.
CR23500SE-CJ5 CR23500SE-CJ5 1.52g - For NC SRAM
(2) Materials not falling under Class 9
Number of incorporated ER6V batteries
Mitsubishi type (Type for arrangement) Battery type Lithium metal
CR2032 (for built-in battery) CR2032 0.067g - For NC SRAM/
CR2450 (for built-in battery) CR2450 0.173g - For NC SRAM
Refer to "Battery Option" in the specification manual for drive unit you are using for the outline dimension drawing for servo.
ER6, ER6V series (for built-in battery) ER6, ER6V 0.65g - For NC SRAM/
servo detector A6BAT(MR-BAT) ER17330V 0.48g - For servo detector Q6BAT Q6BAT 0.49g - For NC SRAM
(Note) If the number of batteries exceeds 24 batteries for the battery cell or 12 batteries for the battery, the dedicated packing (for materials falling under Class 9) is required.
(Example) Rating nameplate for battery units


Appendix 3.1.2 Handling by User
The following technical opinion is solely Mitsubishi's opinion. The shipper must confirm the latest IATA Dangerous Goods Regulations, IMDG Codes and laws and orders of the corresponding export country. These should be checked by the company commissioned for the actual transportation.
IATA: International Air Transport Association IMDG Code: A uniform international code for the transport of dangerous goods by seas determined by IMO (International Maritime Organization).
Example of completing form

Shipper information Consignee information
[4] A care label with a telephone number for additional information (120×110mm) (A care label is to be attached on the outer package.Shipping less than or equal to 4 isolated batteries incorporated in machinery does not need care label.)
Lithium battery care label (Air transportation sample)

(b) Preparation of shipping documents and declaration of dangerous goods For information required in description, refer to "Product information data sheet".
x-xxxx-xx-xx-xxx

(2) When packaged by user
The user must follow UN Regulations when packing, preparing for shipping and preparing the indications, etc. (a) Packing a lithium battery falling under Class 9 [1] Consult with The Ship Equipment Inspection Society of Japan for details on packaging. [2] Prepare for shipping as explained in "(1) Reshipping in Mitsubishi UN packaging". The Ship Equipment Inspection Society of Japan http://www.hakuyohin.or.jp/english.html (b) Packing a lithium battery not falling under Class 9 [1] Cells and batteries are separated so as to prevent short circuits and are stored in a strong outer packaging (12 batteries or less, 24 battery cells or less). [2] Prepare for the certificates or test results showing compliance to drop test from 1.2m in height. (The safety test results have been obtained from the battery manufacturer. Consult with Mitsubishi when the safety test results are required.) [3] Prepare for shipping as explained in "(1) Reshipping in Mitsubishi UN packaging (Class 9)".
Refer to the following materials for details on the regulations and responses. Guidelines regarding transportation of lithium batteries and lithium ion batteries (Edition 2) Battery Association of Japan

Appendix 3.2 Products information data sheet (ER battery)
MSDS system does not cover the product used in enclosed state. The ER battery described in this section applies to that product. This description is applied to the normal use, and is provided as reference but not as guarantee. This description is based on the lithium battery's (ER battery) hazardous goods data sheet (Products information data sheet) which MITSUBISHI has researched, and will be applied only to the ER batteries described in the previous section "Restriction for Packing".
Principal hazard and effect Not found.
As the chemical substance is stored in a sealed metal container, the battery itself is not hazardous. But when the internal lithium metal attaches to human skin, it causes a chemical skin burn. As a reaction of lithium with water, it may ignite or forms flammable hydrogen gas. Environmental effect Not found. Possible state of emergency Damages or short-circuits may occur due to external mechanical or electrical pressures.
Inhalation If a person inhales the vapor of the substance due to the battery damage, move the person immediately to fresh air. If the person feels sick, consult a doctor immediately.
Skin contact If the content of the battery attaches to human skin, wash off immediately with water and soap. If skin irritation persists, consult a doctor.
Eye contact In case of contact with eyes due to the battery damage, rinse immediately with a plenty of water for at least 15 minutes and then consult a doctor. Ingestion If swallowed, consult a doctor immediately.
Appropriate fire-extinguisher Dry sand, dry chemical, graphite powder or carbon dioxide gas Special fire-fighting measure Keep the battery away from the fireplace to prevent fire spreading. Protectors against fire Fire-protection gloves, eye/face protector (face mask), body/skin protective cloth
Environmental precaution Dispose of them immediately because strong odors are produced when left for a long time. How to remove Get them absorbed into dry sand and then collect the sand in an empty container.
Do not peel the external tube or damage it. Do not dispose of the battery in fire or expose it to heat. Do not immerse the battery in water or get it wet. Do not throw the battery. Do not disassemble, modify or transform the battery. Do not short-circuit the battery.
Avoid direct sunlight, high temperature and high humidity. (Recommended temp. range: +5 to +35C°, humidity: 70%RH or less) Material to avoid Flammable or conductive material (Metal: may cause a short-circuit)
Physical form Solid Shape Cylinder type Smell Odorless pH Not applicable (insoluble) Boiling point/Boiling range, Melting point, Decomposition temperature, Flash point

(7) Stability and reactivity
Stability Stable under normal handling condition.
Condition to avoid Do not mix multiple batteries with their terminals uninsulated. This may cause a short- circuit, resulting in heating, bursting or ignition. Hazardous decomposition products Irritative or toxic gas is emitted in the case of fire.
(8) Toxicological information As the chemical substance is stored in a sealed metal container, the battery has no harmfulness. Just for reference, the table below describes the main substance of the battery. < Lithium metal >
Acute toxicity No information Local effect Corrosive action in case of skin contact
Acute toxicity Lc50: 500ppm (inhaled administration to rat) Local effect The lungs can be damaged by chronic cough, dyspnea and asthma.
Acute toxicity LD50: 3700ppm (oral administration to rat) Local effect Not found.
Acute toxicity LD50: 526ppm (oral administration to rat) Local effect The central nerves and kidney can be influenced.
Mobility, Persistence/ Decomposability, Bio- accumulation potential, Ecological toxicity
Not found.
Dispose of the battery following local laws or regulations. Pack the battery properly to prevent a short-circuit and avoid contact with water.

Appendix 3.3 Issuing Domestic Law of the United States for Primary
Lithium Battery Transportation
Federal Aviation Administration (FAA) and Research and Special Programs Administration (RSPA) announced an additional regulation (interim final rule) for the primary lithium batteries transportation restrictions item in "Federal Register" on Dec.15 2004. This regulation became effective from Dec.29, 2004. This law is a domestic law of the United States, however if also applies to the domestic flight and international flight departing from or arriving in the United States. Therefore, when transporting lithium batteries to the United State, or within the United State, the shipper must take measures required to transport lithium batteries. Refer to the Federal Register and the code of Federal Regulation ("Reference" from the previous section "Restriction for Packing") for details.
(1) Transporting primary lithium battery by passenger aircraft is forbidden. (a) Excluding primary lithium battery for personal use in a carry-on or checked luggage (Lithium metal content should be not more than 5g for cell and 25g for battery. For details on the lithium metal content, refer to "Transportation Restrictions for Lithium Batteries: Target Products".) (2) When transporting primary lithium battery by cargo aircraft, indicate that transportation by passenger aircraft is forbidden on the exterior box.
All NC products for which the lithium batteries are used are subject to the regulation. (Refer to the table of "Target Products" from the previous section "Restriction for Packing".)
The "Target Products" from the previous section "Outline of Regulation" described above is solely Mitsubishi's opinion. The shipper must confirm orders of "Transportation Restrictions for Lithium Batteries: Reference" described below for transportation method corresponding the regulation. These should be checked by the company commissioned for the actual lithium battery transportation. (1) Indication of exterior box When transporting primary lithium battery by cargo aircraft, indicate that transportation by passenger aircraft is forbidden on the exterior box. Display example
FORBIDDEN FOR TRANSPORT ABOARD PASSENGER AIRCRAFT.
(a) The character color must be displayed with contrast. (black characters against white background, black characters against yellow background, etc.) (b) The height (size) of characters to be displayed is prescribed depending on the packaging mass. (When the total mass is over 30kg: at least 12mm, When the total mass is less than 30kg: at least 6mm)
(1) 49CFR (Code of Federal Regulation, Title49) (173.185 Lithium batteries and cells.) Search from the following URL. http://www.gpoaccess.gov/cfr/index.html (2) DOT regulation body (Department of Transportation) Search "69fr-75207.pdf" from the following URL. http://phmsa.dot.gov/hazmat

Appendix 3.4 Restriction related to EU Battery Directive
EU Battery Directive (2006/66/EC) has been enforced since September 26th in 2008. Hereby, battery and machinery incorporating battery marketed in European Union countries must be in compliance with the EU Battery Directive. Lithium battery provided by MITSUBISHI are subjected to this restriction.
Follow the instruction bellow as shipping products incorporating MITSUBISHI device. (1) When shipping products incorporating MITSUBISHI device any time later than September 26th, 2008, the symbol mark
shown as Figure 1 in section "Information for end-user" is required to be attached on the machinery or on the package. Also, the explanation of the symbol must be added. (2) Machinery with battery and maintenance battery produced before the EU Battery Directive are also subjected to the
restriction. When shipping those products to EU countries later than September 26th, 2008, follow the instruction explained in (1).

This symbol mark is according to the directive 2006/66/EC Article 20 Information for end-users and Annex II.
Your MITSUBISHI ELECTRIC product is designed and manufactured with high quality materials and components which can be recycled and/or reused. This symbol means that batteries and accumulators, at their end-of-life, should be disposed of separately from your household waste.
If a chemical symbol is printed beneath the symbol shown above, this chemical symbol means that the battery or accumulator contains a heavy metal at a certain concentration. This will be indicated as follows:Hg: mercury (0,0005% ), Cd: cadmium (0,002% ), Pb: lead (0,004% )
In the European Union there are separate collection systems for used batteries and accumulators. Please, dispose of batteries and accumulators correctly at your local community waste collection/recycling centre.
Please, help us to conserve the environment we live in!


付録 Ap 4 章
Precautions for Compliance to UL/c-UL Standards

Observe the following matters to comply with UL/c-UL Standards. Refer to "Instruction Manual for Compliance with UL/c-UL Standard"(BNP-B2429-003) for details.
(1) Selection of external 24VDC power supply unit (The unit shall be prepared by the machine tool builder.)
This NC system complies with the UL Standards on the condition that the stabilized power supply unit supplying 24VDC to each unit is a UL-approved part. Use a UL-approved part for the stabilized power supply unit supplying 24VDC to each unit. (2) Unit ambient temperature
This NC system complies with the UL Standards on the condition that the unit is used at a temperature less than the maximum ambient temperature given in "Environment Conditions" section. Make sure that the maximum ambient temperature of each unit does not exceed the temperature given in "Environment Conditions" section.

Dec. 2012 IB(NA)1501151-A First edition created.
The construction of chapters and sections were revised. - "5 EMC Installation Guidelines" to Appendix 2. - "6 Restrictions for Lithium Batteries" to Appendix 3. - "7 Precautions for Compliance to UL/c-UL Standards" to Appendix 4. - "8 Cable" to Appendix 1. Mistakes were corrected.
Dec. 2013 IB(NA)1501151-B
Following chapters were revised. - "4.2.3 Connecting with Emergency Stop Signal" - "Appendix 1.32 G380 Cable" - "Appendix 1.33 G395 Cable" - "Appendix 1.34 G396 Cable" The title of the chapter was revised. - "4.2.5 Connecting with Drive Unit" Mistakes were corrected.
Feb. 2014 IB(NA)1501151-C

MITSUBISHI ELECTRIC AUTOMATION INC. (AMERICA FA CENTER) MITSUBISHI ELECTRIC EUROPE B.V. Central Region Service Center GOTHAER STRASSE 10, 40880 RATINGEN, GERMANY 500 CORPORATE WOODS PARKWAY, VERNON HILLS, ILLINOIS 60061, U.S.A. TEL: +49-2102-486-0 / FAX: +49-2102-486-5910 TEL: +1-847-478-2500 / FAX: +1-847-478-2650
Germany Service Center Michigan Service Satellite KURZE STRASSE. 40, 70794 FILDERSTADT-BONLANDEN, GERMANY ALLEGAN, MICHIGAN 49010, U.S.A. TEL: + 49-711-770598-123 / FAX: +49-711-770598-141 TEL: +1-847-478-2500 / FAX: +1-847-478-2650
France Service Center DEPARTEMENT CONTROLE NUMERIQUE Ohio Service Satellite 25, BOULEVARD DES BOUVETS, 92741 NANTERRE CEDEX FRANCE LIMA, OHIO 45801, U.S.A. TEL: +33-1-41-02-83-13 / FAX: +33-1-49-01-07-25 TEL: +1-847-478-2500 / FAX: +1-847-478-2650 CINCINATTI, OHIO 45201, U.S.A. France (Lyon) Service Satellite DEPARTEMENT CONTROLE NUMERIQUE TEL: +1-847-478-2500 / FAX: +1-847-478-2650 120, ALLEE JACQUES MONOD 69800 SAINT PRIEST FRANCE TEL: +33-1-41-02-83-13 / FAX: +33-1-49-01-07-25 Minnesota Service Satellite ROGERS, MINNESOTA 55374, U.S.A. Italy Service Center TEL: +1-847-478-2500 / FAX: +1-847-478-2650 VIALE COLLEONI, 7 - CENTRO DIREZIONALE COLLEONI PALAZZO SIRIO INGRESSO 1 20864 AGRATE BRIANZA (MB), ITALY West Region Service Center TEL: +39-039-6053-342 / FAX: +39-039-6053-206 16900 VALLEY VIEW AVE., LAMIRADA, CALIFORNIA 90638, U.S.A. TEL: +1-714-699-2625 / FAX: +1-847-478-2650 Italy (Padova) Service Satellite VIA G. SAVELLI, 24 - 35129 PADOVA, ITALY Northern CA Satellite TEL: +39-039-6053-342 / FAX: +39-039-6053-206 SARATOGA, CALIFORNIA 95070, U.S.A. TEL: +1-714-699-2625 / FAX: +1-847-478-2650 U.K. Branch TRAVELLERS LANE, HATFIELD, HERTFORDSHIRE, AL10 8XB, U.K. Pennsylvania Service Satellite TEL: +49-2102-486-0 / FAX: +49-2102-486-5910 PITTSBURG, PENNSYLVANIA 15644, U.S.A. TEL: +1-732-560-4500 / FAX: +1-732-560-4531 Spain Service Center CTRA. DE RUBI, 76-80-APDO. 420 Connecticut Service Satellite 08173 SAINT CUGAT DEL VALLES, BARCELONA SPAIN TORRINGTON, CONNECTICUT 06790, U.S.A. TEL: +34-935-65-2236 / FAX: +34-935-89-1579 TEL: +1-732-560-4500 / FAX: +1-732-560-4531
Poland Service Center South Region Service Center UL.KRAKOWSKA 50, 32-083 BALICE, POLAND 1845 SATTELITE BOULEVARD STE. 450, DULUTH, GEORGIA 30097, U.S.A. TEL: +48-12-630-4700 / FAX: +48-12-630-4701 TEL +1-678-258-4529 / FAX +1-678-258-4519
Mitsubishi Electric Turkey A.Ş Ümraniye Şubesi Texas Service Satellites Turkey Service Center GRAPEVINE, TEXAS 76051, U.S.A. ŞERIFALI MAH. NUTUK SOK. NO.5 34775 TEL: +1-678-258-4529 / FAX: +1-678-258-4519 ÜMRANIYE, ISTANBUL, TURKEY HOUSTON, TEXAS 77001, U.S.A. TEL: +90-216-526-3990 / FAX: +90-216-526-3995 TEL: +1-678-258-4529 / FAX: +1-678-258-4519
Czech Republic Service Center Tennessee Service Satellite KAFKOVA 1853/3, 702 00 OSTRAVA 2, CZECH REPUBLIC Nashville, Tennessee, 37201, U.S.A. TEL: +420-59-5691-185 / FAX: +420-59-5691-199 TEL: +1-678-258-4529 / FAX: +1-678-258-4519
Russia Service Center Florida Service Satellite 213, B.NOVODMITROVSKAYA STR., 14/2, 127015 MOSCOW, RUSSIA WEST MELBOURNE, FLORIDA 32904, U.S.A. TEL: +7-495-748-0191 / FAX: +7-495-748-0192 TEL: +1-678-258-4529 / FAX: +1-678-258-4519
MITSUBISHI ELECTRIC EUROPE B.V. (SCANDINAVIA) Canada Region Service Center Sweden Service Center 4299 14TH AVENUE MARKHAM, ONTARIO L3R OJ2, CANADA HAMMARBACKEN 14 191 49 SOLLENTUNA, SWEDEN TEL: +1-905-475-7728 / FAX: +1-905-475-7935 TEL: +46-8-6251000 / FAX: +46-8-966877
Canada Service Satellite Bulgaria Service Center EDMONTON, ALBERTA T5A 0A1, CANADA 4 A.LYAPCHEV BOUL., POB 21, BG-1756 SOFIA, BULGARIA TEL: +1-905-475-7728 FAX: +1-905-475-7935 TEL: +359-2-8176009 / FAX: +359-2-9744061
Mexico Region Service Center Ukraine (Kharkov) Service Center MARIANO ESCOBEDO 69 TLALNEPANTLA, 54030 EDO. DE MEXICO APTEKARSKIY LANE 9-A, OFFICE 3, 61001 KHARKOV, UKRAINE TEL: +52-55-3067-7500 / FAX: +52-55-9171-7649 TEL: +380-57-732-7774 / FAX: +380-57-731-8721
Monterrey Service Satellite Ukraine (Kiev) Service Center MONTERREY, N.L., 64720, MEXICO 4-B, M. RASKOVOYI STR., 02660 KIEV, UKRAINE TEL: +52-81-8365-4171 TEL: +380-44-494-3355 / FAX: +380-44-494-3366
Belarus Service Center BRAZIL OFFICE 9, NEZAVISIMOSTI PR.177, 220125 MINSK, BELARUS TEL: +375-17-393-1177 / FAX: +375-17-393-0081 MELCO CNC do Brasil Comércio e Serviços S.A Brazil Region Service Center South Africa Service Center ACESSO JOSE SARTORELLI, KM 2.1 CEP 18550-000, BOITUVA-SP, BRAZIL 5 ALBATROSS STREET, RHODESFIELD, KEMPTON PARK 1619, GAUTENG, SOUTH AFRICA TEL: +55-15-3363-9900 / FAX: +55-15-3363-9911 TEL: +27-11-394-8512 / FAX: +27-11-394-8513

MITSUBISHI ELECTRIC ASIA PTE. LTD. (ASEAN FA CENTER) MITSUBISHI ELECTRIC AUTOMATION (CHINA) LTD. (CHINA FA CENTER) Singapore Service Center China (Shanghai) Service Center 307 ALEXANDRA ROAD #05-01/02 MITSUBISHI ELECTRIC BUILDING SINGAPORE 159943 1-3,5-10,18-23/F, NO.1386 HONG QIAO ROAD, CHANG NING QU, TEL: +65-6473-2308 / FAX: +65-6476-7439 SHANGHAI 200336, CHINA TEL: +86-21-2322-3030 / FAX: +86-21-2308-3000 Malaysia (KL) Service Center China (Ningbo) Service Dealer 60, JALAN USJ 10 /1B 47620 UEP SUBANG JAYA SELANGOR DARUL EHSAN, MALAYSIA China (Wuxi) Service Dealer TEL: +60-3-5631-7605 / FAX: +60-3-5631-7636 China (Jinan) Service Dealer China (Hangzhou) Service Dealer Malaysia (Johor Baru) Service Center China (Wuhan) Service Satellite 17 & 17A, JALAN IMPIAN EMAS 5/5, TAMAN IMPIAN EMAS, 81300 SKUDAI, JOHOR MALAYSIA. TEL: +60-7-557-8218 / FAX: +60-7-557-3404 China (Beijing) Service Center 9/F, OFFICE TOWER 1, HENDERSON CENTER, 18 JIANGUOMENNEI DAJIE, Philippines Service Center DONGCHENG DISTRICT, BEIJING 100005, CHINA UNIT NO.411, ALABAMG CORPORATE CENTER KM 25. WEST SERVICE ROAD TEL: +86-10-6518-8830 / FAX: +86-10-6518-8030 SOUTH SUPERHIGHWAY, ALABAMG MUNTINLUPA METRO MANILA, PHILIPPINES 1771 China (Beijing) Service Dealer TEL: +63-2-807-2416 / FAX: +63-2-807-2417
China (Tianjin) Service Center UNIT 2003, TIANJIN CITY TOWER, NO 35 YOUYI ROAD, HEXI DISTRICT, VIETNAM TIANJIN 300061, CHINA TEL: +86-22-2813-1015 / FAX: +86-22-2813-1017 MITSUBISHI ELECTRIC VIETNAM CO.,LTD China (Shenyang) Service Satellite Vietnam (Ho Chi Minh) Service Center China (Changchun) Service Satellite UNIT 01-04, 10TH FLOOR, VINCOM CENTER 72 LE THANH TON STREET, DISTRICT 1, HO CHI MINH CITY, VIETNAM China (Chengdu) Service Center TEL: +84-8-3910 5945 / FAX: +84-8-3910 5946 ROOM 407-408, OFFICE TOWER AT SHANGRI-LA CENTER, NO. 9 BINJIANG DONG ROAD, JINJIANG DISTRICT, CHENGDU, SICHUAN 610021, CHINA Vietnam (Hanoi) Service Satellite TEL: +86-28-8446-8030 / FAX: +86-28-8446-8630 SUITE 9-05, 9TH FLOOR, HANOI CENTRAL OFFICE BUILDING, 44B LY THUONG KIET STREET, HOAN KIEM DISTRICT, HANOI CITY, VIETNAM China (Shenzhen) Service Center TEL: +84-4-3937-8075 / FAX: +84-4-3937-8076 ROOM 2512-2516, 25/F., GREAT CHINA INTERNATIONAL EXCHANGE SQUARE, JINTIAN RD.S., FUTIAN DISTRICT, SHENZHEN 518034, CHINA TEL: +86-755-2399-8272 / FAX: +86-755-8218-4776 INDONESIA China (Xiamen) Service Dealer China (Dongguan) Service Dealer PT. MITSUBISHI ELECTRIC INDONESIA Indonesia Service Center GEDUNG JAYA 11TH FLOOR, JL. MH. THAMRIN NO.12, JAKARTA PUSAT 10340, INDONESIA KOREA TEL: +62-21-3192-6461 / FAX: +62-21-3192-3942
MITSUBISHI ELECTRIC AUTOMATION KOREA CO., LTD. (KOREA FA CENTER) Korea Service Center THAILAND 1480-6, GAYANG-DONG, GANGSEO-GU, SEOUL 157-200, KOREA TEL: +82-2-3660-9602 / FAX: +82-2-3664-8668 MITSUBISHI ELECTRIC FACTORY AUTOMATION (THAILAND) CO.,LTD Thailand Service Center Korea Taegu Service Satellite 12TH FLOOR, SV.CITY BUILDING, OFFICE TOWER 1, NO. 896/19 AND 20 RAMA 3 ROAD, 4F KT BUILDING, 1630 SANGYEOK-DONG, BUK-KU, DAEGU 702-835, KOREA KWAENG BANGPONGPANG, KHET YANNAWA, BANGKOK 10120,THAILAND TEL: +82-53-382-7400 / FAX: +82-53-382-7411 TEL: +66-2-682-6522-31 / FAX: +66-2-682-6020
MITSUBISHI ELECTRIC TAIWAN CO., LTD. (TAIWAN FA CENTER) MITSUBISHI ELECTRIC INDIA PVT. LTD. Taiwan (Taichung) Service Center (Central Area) India Service Center NO.8-1, INDUSTRIAL 16TH RD., TAICHUNG INDUSTRIAL PARK, SITUN DIST., 2nd FLOOR, TOWER A & B, DLF CYBER GREENS, DLF CYBER CITY, TAICHUNG CITY 40768, TAIWAN R.O.C. DLF PHASE-III, GURGAON 122 002, HARYANA, INDIA TEL: +886-4-2359-0688 / FAX: +886-4-2359-0689 TEL: +91-124-4630 300 / FAX: +91-124-4630 399 Ludhiana satellite office Taiwan (Taipei) Service Center (North Area) Jamshedpur satellite office 10F, NO.88, SEC.6, CHUNG-SHAN N. RD., SHI LIN DIST., TAIPEI CITY 11155, TAIWAN R.O.C. TEL: +886-2-2833-5430 / FAX: +886-2-2833-5433 India (Pune) Service Center EMERALD HOUSE, EL-3, J-BLOCK, MIDC BHOSARI. PUNE – 411 026, MAHARASHTRA, INDIA Taiwan (Tainan) Service Center (South Area) TEL: +91-20-2710 2000 / FAX: +91-20-2710 2100 11F-1., NO.30, ZHONGZHENG S. ROAD, YONGKANG DISTRICT, TAINAN CITY 71067, TAIWAN, R.O.C Baroda satellite office TEL: +886-6-252-5030 / FAX: +886-6-252-5031 Mumbai satellite office
India (Bangalore) Service Center PRESTIGE EMERALD, 6TH FLOOR, MUNICIPAL NO. 2, LAVELLE ROAD, BANGALORE - 560 043, KAMATAKA, INDIA TEL: +91-80-4020-1600 / FAX: +91-80-4020-1699 Chennai satellite office Coimbatore satellite office
MITSUBISHI ELECTRIC AUSTRALIA LTD. Australia Service Center 348 VICTORIA ROAD, RYDALMERE, N.S.W. 2116 AUSTRALIA TEL: +61-2-9684-7269 / FAX: +61-2-9684-7245

Every effort has been made to keep up with software and hardware revisions in the contents described in this manual. However, please understand that in some unavoidable cases simultaneous revision is not possible. Please contact your Mitsubishi Electric dealer with any questions or comments regarding the use of this product.
This manual may not be reproduced in any form, in part or in whole, without written permission from Mitsubishi Electric Corporation.