The fi re detection control panels Series BC216 and BC016, respectively, provide 16 freely programmable open-collector control outputs. Eight of these outputs are connected to a fl at cable connector. The Relay Mo- dules RL58-1 and RL58-2 allow for the easy conversion of these control outputs to dry changeover contacts. The componentry is connected to the fi re detection con- trol panel via a fl at cable.
The RL58-1 provides eight relay outputs with a maxi- mum contact rating of 30W. The current is limited to 1A and the voltage is limited to 60VDC. The RL58-2 offers four relay outputs with a maximum of 5A/230VAC. The terminal of the RL58-2 are designed for mains voltage. Two relay modules RL58-2 are each cascadable via pin connectors. The relay module is delivered with fl at ca- ble and mounting accessories for easy installation.

Operating voltage 20 – 31VDC
Current consumption at 24V typ. 22mA per activated circuit
Control current typ. 1.2mA per input
Ambient temperature -5°C to +50°C
Switching power per contact 1A/60V/30W
Contact life approx. 5 mill. switching cycles (unloaded) approx. 300,000 switching cycles (at 24VDC/1A)
Dimensions L × W × H 85 × 65 × 37 (mm)
Part No. 222004
Order name Relay Module 8-Fold/60VDC RL58-1
RL58_DBL_LST_EN_0804.PDF • PAGE 1 A Building Safety. Building Security.
Weight 330g

Maximum switching power per contact 3A/30VDC or 5A/230VAC
Contact life approx. 20 mill. switching cycles (unloaded) approx. 400,000 switching cycles (at 230VAC/3A)
Dimensions L × W × H 98 × 74 × 28 (mm)
Part No. 222010
Order name Relay Module 4-Fold/230VAC RL58-2
RL58_DBL_LST_EN_0804.PDF • PAGE 2 A Building Safety. Building Security.
Weight 120g