Fire is a permanent threat to life and property. There- fore, immediate response to a fi re is imperative. The main objective of the Fire Detection Control Panel Series BC06 is to alarm and to react in time and, con- sequently, save lives and protect property. For decades LST have focused their aims to undertaking unrivaled efforts in order to realise new innovations in the security area. Research, development and production are loca-
ted within LST premises, thus guaranteeing fl exible and reliable individual solutions.
Using a powerful processor system and a large number of integrated functions, the Fire/Extinguishing Control Panels Series BC06 ensure topmost effi ciency and speed – prerequisites for saving lives and minimising damage to property.

Already in the basic version the combined Fire/Extingu- ishing Control Panels BC06-1EXT and BC06-2EXT are equipped with four detector lines and the Extinguishing Board EXB1-1 and, owing to its sophisticated factory settings, are immediately ready for operation. This al- lows for quick and effi cient application of the product.
The optional evacuation function serves for the actu- ation of alarming devices independent from activated alarms.
Thanks to the integrated extinguishing module, the BC06 can be used as an extinguishing control panel according to EN 12094-1 with one fl ooding zone. The module provides appropriate inputs and outputs for con- trolling and monitoring a fl ooding zone. The display and operating elements that are necessary for the status indication and the operation of the extinguishing module are integrated into the keypad. A printer for the event log can be connected via the optional Serial Interface Modul SIM06-1.
The conventional technology allows for the connection of automatic and non-automatic fi re detectors as well as a wide range of special detectors with contact out- put. Alarms from manual call points and from automatic detectors that are connected together to one detector line can be differentiated and thus evaluated differently by the fi re/extinguishing control panel, by means of an optional coding module.
The Fire/Extinguishing Control Panel BC06-2EXT dif- fers from the BC06-1EXT by the additionally integrated 4-digit electronic alarm counter.
Thanks to the two auxiliary inputs whose parameters can be freely set as well as the eight open-collector out- puts, manifold tasks in the fi eld of fi re alarm technology can be realised.
BC06EXT_DBL_LST_EN_0826.PDF • PAGE 1 A Building Safety. Building Security.


The combined Fire/Extinguishing Control Panels BC06-1EXT and BC06-2EXT have been designed for use in small fi re detection and extinguishing control sys- tems with one fl ooding zone, and already in the basic version they provide the following features:
The extremely fl at wall-mount cabinet allows for an easy mounting in virtually any place of the building. Thanks to its modern, ageless design, architectural requirements and demands of the respective regulations are ideally combined. Thanks to the compact design, the standard case can accommodate batteries with up to 7Ah also in the event of full extension (central processing board, extinguishing board and an auxiliary module) of the con- trol panel. Series BC06 thus stands for modularity and easy expansion.
ector outputs with fi xed preset functions. • Logical combinations of detector zones for the ac- tivation of external alarming devices and for the ac- tuation of the extinguishing system allow for a high degree of fl exibility. Thus, no additional expenses arise for external relays or logic gates. Thanks to the wide range of parameterisation possibilities, individu- al requirements even under the most diffi cult ambient conditions can be combined into a reasonable fi re protection strategy.
This product complies with all relevant standards of EN 54 and EN 12094-1 and is tested by the VdS. LST‘s high quality level is secured by a permanently monitored quality management system certifi ed to ISO 9001.
BC06EXT_DBL_LST_EN_0826.PDF • PAGE 2 A Building Safety. Building Security.

By means of the Extinguishing Board EXB1-1, the Fire/Extinguishing Control Panels BC06-1EXT and BC06-2EXT provide numerous inputs and outputs with fi xed or parameterisable function. With that, the follo- wing components of an extinguishing system can be ac- tuated and monitored in accordance with EN 12094-1:


The operating fi eld of the Fire/Extinguishing Control Pa- nels BC06-1EXT and BC06-2EXT provides 13 LEDs for displaying the operating conditions and 4 buttons for the operation of the extinguishing system.

BC06EXT_DBL_LST_EN_0826.PDF • PAGE 3 A Building Safety. Building Security.



Mains voltage 230VAC +10/-20%, 47...63Hz
Output/nominal voltage typ. 27.6VDC
Output current max. 2.2A
Output current siren outputs output 1 max. 1A output 2 max. 0.5A (the sum of the currents of the signalling devices that are connected to the two outputs must not exceed 1A!)
Output current, extinguishing output max. 1A
Output current, activated condition output/signal output max. 500mA per output
Own current consumption (incl. extinguishing board) at 24V typ. 80mA (without optional componentries, line termination 5.6kΩ) typ. 65mA (without optional componentries, line termination 47µF)
Line voltage typ. 20V (line termination 5.6kΩ) typ. 23V (line termination 47µF)
Line current without fi re detectors typ. 3.7mA (line termination 5.6kΩ) typ. 0mA (line termination 47µF)
Line termination 5.6kΩ or 47µF
Line resistance max. 50Ω per core
Ambient temperature -5°C to +50°C
Relative humidity max. 95% (no condensation)
Dimensions W × H × D 330 × 330 × 90 (mm)
Colour grey-white, RAL 9002
Weight without batteries approx. 3kg
Approvals 0786-CPD-20300 VdS pending
Fire Detection Control Panel BC06-1EXT
Order name Fire Detection Control Panel BC06-1EXT/INT1
Fire Detection Control Panel BC06-2EXT
Order name Fire Detection Control Panel BC06-2EXT/INT1
BC06EXT_DBL_LST_EN_0826.PDF • PAGE 4 A Building Safety. Building Security.
Order number 210223 · Order number 210224
Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.