With Built-in Wireless Receiver
Digital Keyless Entry System
USA & Canada (800) 421-1587 & (800) 392-0123
Toll Free FAX (800) 468-1340



To avoid damage to the unit from static discharges, connect the
EARTH GROUND terminal to a good earth grounding point. Suggested
wiring size is 18 AWG for earth ground and power (up to 500 feet
of 18 AWG wire can be run for power, use larger wire for longer
runs). Use 22 AWG or larger (depending on the load) for all other
Select a location for the keypad. For door access control installations,
mount the keypad near the controlled door. For gate control
installations, mount the keypad in clear view of the gate, but far
enough from the gate so the user cannot touch the gate from the
the power transformer secondary is connected to earth
MAKE SURE THAT THE UNIT IS FAR ENOUGH FROM
THE GATE SO THAT THE USER CANNOT TOUCH THE
ground, connect the grounded side to the “-” power
THE GATE MUST BE FULLY VISIBLE FROM THE
terminal of the unit.
KEYPAD.
connections.
keypad.
✓ EACH ENTRY CODE CAN BE PROGRAMMED TO ACTIVATE EITHER OR BOTH RELAYS
✓ SUPPORTS 4 BLOCKS OF TRANSMITTERS WITH 4 FACILITY CODES
✓ SUPPORTS 1 MODEL MGT SAFETY EDGE TRANSMITTER
✓ TIMED ANTI-PASSBACK (LAST 3 VALID ENTRIES)
✓ 4 INDEPENDENT OUTPUTS (TIMED/TOGGLED)
✓ RELAY CONTACTS ARE FORM “C” (N.O. & N.C)
✓ 480 ENTRY CODE CAPACITY
✓ 480 TRANSMITTER CAPACITY
✓ KEYPAD PROGRAMMABLE
✓ 4 INDEPENDENT TIMERS
✓ TWO STATUS INDICATORS
✓ REQUEST-TO-ENTER INPUT
✓ DOOR SENSE INPUT
✓ COURTESY LAMP
✓ PIEZO SOUNDER
✓ KEYPAD LOCKOUT
✓ TACTILE KEY FEEL
✓ INHIBIT INPUT
FEATURES

ANTENNA
(HIDDEN)
BLOCK

Figure 1. Component Locations
MASTER CODE
JUMPER JP2
JUMPER JP1
REMOVE TO
TO RESET
"LOCKOUT"
INDICATOR
REMOVE
REDUCE
YELLOW
KEYLOCK
COMPONENT LOCATIONS
POWER/ACCESS
TACTILE
KEYPAD
RED/GREEN
INDICATOR
NIGHT
LIGHT

OPTIONAL WIRING
OTHER WIRING

AND ONE SIDE OF THE POWER TRANSFORMER SECONDARY
AKR-1 TERMINALS
SIDE TO THE "-" POWER TERMINAL OF THE UNIT.
N.O.
N.C.
OUTPUT #4
COMMON
N.O.
N.C.
DOOR SENSE

AKR-1 TERMINALS
TERMINAL 14 SET FOR INHIBIT
WIRING DIAGRAM
N.O.
N.C.
OUTPUT #4
DC OR AC POWER
COMMON
N.O.
N.C.
COMMON
INHIBIT
EARTH GROUND
REQUIRED WIRING
OPTIONAL WIRING
AUXILIARY
MAIN
RELAY
RELAY
NOTE:

The AKR-1 keypad can be mounted directly to a wall or fl at
❑ When mounting the keypad to a concrete wall, use concrete

❑ Use the appropriate fasteners to secure the keypad’s
wedge anchors or molly anchors (see Figure 4).
Figure 4. Wall Mounting Keypad Backplate Figure 3. Pedestal Mounting Keypad Backplate
backplate to the mounting surface.
surface.
❑ Use four security bolts and locking nuts to secure the
The AKR-1 keypad can be mounted on a standard pedestal.
keypad’s backplate to the pedestal (see Figure 3).
PEDESTAL
Pedestal Mounting

(BEHIND GATE)
OPERATOR
GATE
Figure 5. Gate Installation
2 WIRES FROM AKR-1 TO TRIGGER GATE OPEN
KEYSWITCH
ACCESS
FIRE
KEYPAD
AKR-1
❑ Route four wires between the gate and the keypad (two for
❑ Connect the gate operator’s auxiliary or radio power output
❑ Connect the gate operator’s OPEN terminals to the keypad’s
☞ NOTE: If the INHIBIT input is going to be used, it must be programmed to select that input type. See the Programming
terminals to the keypads POWER input terminals (observe
❑ If a request-to-enter pushbutton or fi re access keyswitch is
Connect the inhibit switch/timer terminals to the keypad’s
going to be used, route two wires from the keypad to the
normally open switch. Connect the wires to the normally
open switch and to the keypad’s REQUEST-TO-ENTER and
❑ If an inhibit switch or timer is going to be used, route two
wires from the keypad to the inhibit switch or timer relay.
☞ NOTE: For operator wiring specifi cs, refer to the gate operator’s wiring diagram.
Refer to Figure 5 for an outline of a typical gate installation.
Relay #1 COMMON & N.O. terminals.
INHIBIT and COMMON terminals.
Options section of this manual
power, two for control).
COMMON terminals.
wiring polarity).

2 WIRES FOR
POWER
SENSE
KEYPAD
AKR-1
POWER
SUPPLY
FROM
Figure 6. Door Installation
STRIKE
SWITCH
ELECTRIC
DOOR
SENSE
DOOR
STRIKE
❑ Route two wires between the power supply and the keypad.
Connect the power supply’s output terminals to the keypad’s
❑ To use the door sense feature to detect forced entry or door
ajar conditions, install a normally closed door switch on the
❑ Route two wires between the door strike and the keypad.
to the keypad’s POWER + terminal. Connect a wire between
❑ If a request-to-enter pushbutton or fi re access keyswitch is
Connect the door switch to the keypad’s DOOR SENSE and
wires from the switch or timer to the keypad. Connect the
❑ Install a low voltage electric door strike for unlocking the
Relay #1 N.O. terminal. Connect the other door strike wire
the keypad’s POWER - terminal and the Relay #1 COMMON
going to be used, route two wires from the keypad to the
normally open switch. Connect the wires to the normally
open switch and to the keypad’s REQUEST-TO-ENTER and
door and route two wires from the switch to the keypad.
❑ If an inhibit switch or timer is going to be used, route two
inhibit switch/timer terminals to the keypad’s INHIBIT and
❑ Choose a location for the power supply or transformer.
☞ NOTE: Either door sense or inhibit can be used. Both features cannot be used at the same time.
Connect one of the door strike wires to the keypad’s
POWER input terminals (observe wiring polarity).
COMMON terminals.
COMMON terminals.
COMMON terminals.
terminal.
door.

When the AKR-1 is in Programming Mode, both indicators will turn
off until programming begins. After a programming option number is
entered the yellow indicator will blink. This shows that the AKR-1 is
ready to accept the new programming data. After the new data entry
is complete, the green indicator will light while the data is being
stored.The red indicator will light if any programming data is entered
The 6-digit Master Programming Code (default = 123456) is used to enter
If the red indicator lights, signaling an incorrect entry, or an incorrect key is pressed
☞ NOTE: The AKR-1 will automatically exit Programming Mode after two minutes of inactivity.
☞ NOTE: If the Entry Code Length is going to be changed from the factory default of four digits, make this change fi rst, before programming any entry codes.
incorrectly, and the command will have to be fully re-entered.
Master Code = the current 6-digit Master Programming Code
during programming, to clear the keypad and re-enter the command:
The red indicator will light when Programming Mode is exited.
Length = 1 - 6 for entry code length
Re-entering a Command After a Mistake
Press: * 9 #
Programming Mode.
MASTER PROGRAMMING CODE 123456
ENTRY CODE LENGTH 4 DIGITS
REQUEST-TO-ENTER OUTPUT RELAY #1
ALARM SHUNT OUTPUT DISABLED
FORCED ENTRY OUTPUT OUTPUT #3
DOOR AJAR OUTPUT OUTPUT #4
RELAY #1 ON TIME 2 SECONDS
RELAY #2 ON TIME 2 SECONDS
SOLID STATE OUTPUT #3 ON TIME 2 SECONDS
SOLID STATE OUTPUT #4 ON TIME 2 SECONDS
DOOR SENSE/INHIBIT INPUT DOOR SENSE
KEYPAD LOCKOUT OUTPUT DISABLED
KEYPAD ACTIVE OUTPUT DISABLED
BEEPER SOUNDS WHEN KEY PRESSED YES
BEEPER SOUNDS DURING RELAY #1 NO
BEEPER SOUNDS DURING RELAY #2 NO
BEEPER SOUNDS DURING OUTPUT #3 NO
BEEPER SOUNDS DURING OUTPUT #4 NO
KEYPAD LOCKOUT COUNT 3 TRIES BEFORE LOCKOUT
ANTI-PASSBACK TIME NO ANTI-PASSBACK
TRANSMITTER LEFT BUTTON ACTIVATES RELAY #1
TRANSMITTER RIGHT BUTTON ACTIVATES RELAY #2
TRANSMITTER TOP BUTTON ACTIVATES NONE
TRANSMITTER LOWER LEFT BUTTON ACTIVATES NONE
TRANSMITTER LOWER RIGHT BUTTON ACTIVATES NONE
Entering Programming Mode · Exiting Programming Mode

There are several AKR-1 programming options. For most installations, the factory
set default options are suffi cient. The keypad must be in Programming Mode to
Linear’s AccessKey products have a programmable “Toggle Mode” available for
each relay and solid-state output. When an output is programmed for Toggle Mode,
the output alternates from OFF to ON or from ON to OFF each time it is activated.
With the unit in Program Mode, set the Auxiliary Relay (Relay #2) output to Toggle
22 = Programming Step; 99 = Toggle Mode Program all normal entry codes to use the Main Relay (Relay #1), and only
Relay #1 as the output relay. Program the code(s) that you want to use to hold the
output for an indefi nite period to the Auxiliary Relay (Relay #2). See the following
example that sets entry codes 1234 for normal and 5678 for toggle operation.
Press: 0 1 # 1 2 3 4 # 1 2 3 4 # 1 #
Press: 0 1 # 5 6 7 8 # 5 6 7 8 # 2 #
01 = Programming Step; 1234 = Entry Code; 1 = Main Relay
01 = Programming Step; 5678 = Entry Code; 2 = Auxiliary Relay
Programming AKR-1 to Hold the Output
Mode using the following keystrokes:
The rules for a toggle output are:
make these changes.
ENTRY CODE
5678 TOGGLE
ENTRY CODE
1 = Relay #1 2 = Relay #2 3 = Both Relays The yellow indicator will fl ash quickly while the AKR-1 searches its memory for
available space and duplicate entries. The green indicator will light when the new
If the new entry code chosen is already being used for another entry code, the red
☞ NOTE: Leading zeros (zeros before the code number, i.e. 0001) do not need to be entered when programming a new entry code. The AKR-1 will internally add any zeros to fi ll all
digits determined by the entry code length setting. Leading zeros will have to be entered by
The yellow indicator will fl ash quickly while the AKR-1 searches its memory for the
☞ NOTE: The green indicator will light while the memory is being erased. This may take up to 15 seconds.
Code = The new entry code: 1-999999, depending on code length
Master Code = The new 6-digit Master Programming Code
code to erase. The green indicator will light when the code is erased.
Press: 9 7 # 0 # 0 #
Changing the 6-Digit Master Programming Code
Relay = Relay output entry code will activate:
indicator will light. A new unique code needs to be entered.
Code = The entry code to delete.
entry codes from the memory.
the user when entering their code to gain access.
Erasing a Single Entry Code
Adding a New Entry Code
Erasing All Entry Codes
code is stored.

Sets which output activates if the DOOR SENSE input opens before access is
Sets which output activates if the DOOR SENSE input stays open 60 seconds after
Sets which output activates when the keypad is “locked out” after too many
Sets which output activates when any keys are pressed. This output is timed. If
1 = Relay #1 2 = Relay #2 3 = Output #3 4 = Output #4 0 = No Output
1 = Relay #1 2 = Relay #2 3 = Output #3 4 = Output #4 0 = No Output
1 = Relay #1 2 = Relay #2 3 = Output #3 4 = Output #4 0 = No Output
1 = Relay #1 2 = Relay #2 3 = Output #3 4 = Output #4 0 = No Output
toggle mode is selected for the output, the timer value defaults to 2 seconds.
incorrect entry code attempts. The lockout time is 60 seconds.
Output = Output to Activate (0-4)
Output = Output to Activate (0-4)
Output = Output to Activate (0-4)
Output = Output to Activate (0-4)
access is granted. This output is not timed.
granted. This output is not timed.
For devices triggered by a normally open circuit, wire the contacts of the Main
and Auxiliary Relays in parallel (see the Figure below). Either relay will be able to
trigger the access device. Entry codes programmed for the Auxiliary Relay will be
Select Door Sense or Inhibit Input Default: Door Sense
When programmed for DOOR SENSE, if an open condition on the input occurs
before access is granted (with an entry code, transmitter or with the request-to-
enter input) a FORCED ENTRY output will occur. If an open condition remains 60
When programmed for INHIBIT, a closed condition on the input will prevent
Relay #1 from activating when access is requested (with an entry code or
transmitter). This mode is typically used with an external timer to disable the
The input on Terminal #14 can be programmed for DOOR SENSE or INHIBIT.
seconds after a relay activation for access, a DOOR AJAR output will occur.
DEVICE
THE ACCESS DEVICE
Input = 0 for Door Sense, = 1 for Inhibit
N.O.
N.C.
N.O.
N.C.
access device at certain times.
able to hold the output on.
RELAY
RELAY
AKR-1
OUTPUTS

Sets the number of incorrect entry code attempts allowed before the keypad “locks
Beep Sounds During Relay #1 Default: No
Beep Sounds During Relay #2 Default: No
Beep Sounds During Output #3 Default: No
Beep Sounds During Output #4 Default: No
Seconds = Output time in seconds (0-60), 99 = Toggle mode
Selects whether or not the keypad beeps during Relay #1 activation.
Selects whether or not the keypad beeps during Relay #2 activation.
Selects whether or not the keypad beeps during Output #3 activation.
Selects whether or not the keypad beeps during Output #4 activation.
Selects whether or not the keypad beeps as each key is pressed.
Attempts = Number of attempts before lockout (2-7)
Press: 2 4 # Seconds #
Press: 4 0 # Sound #
Press: 4 1 # Sound #
Press: 4 2 # Sound #
Press: 4 3 # Sound #
Press: 4 4 # Sound #
Sound = 1 for Yes, = 0 for No
Sound = 1 for Yes, = 0 for No
Sound = 1 for Yes, = 0 for No
Sound = 1 for Yes, = 0 for No
Sound = 1 for Yes, = 0 for No
out”.
Sets which output activates during the time access is granted. (Use this output
to shunt alarm contacts attached to the access door.) This output may be timed
Sets which output activates when the Request-to-Enter input is grounded. This
1 = Relay #1 2 = Relay #2 3 = Output #3, 4 = Output #4 0 = No Output
1 = Relay #1 2 = Relay #2 3 = Output #3 4 = Output #4 0 = No Output
Seconds = Output time in seconds (0-60), 99 = Toggle mode
Seconds = Output time in seconds (0-60), 99 = Toggle mode
Seconds = Output time in seconds (0-60), 99 = Toggle mode
Output = Output to Activate (0-4)
Output = Output to Activate (0-4)
Sets the length of time Relay #1 activates when triggered.
Sets the length of time Relay #2 activates when triggered.
Sets the length of time Output #3 activates when triggered.
Sets the length of time Output #4 activates when triggered.
Press: 1 6 # Output #
output may be timed or toggled.
or toggled.

Facility Codes increase security by requiring the Facility Code as well the TX ID
code to match before access is granted. Up to four Facility Codes can be entered.
The Facility Code number is labeled on the box of block coded transmitters. Enter
Programs a Model MGT obstacle transmitter into the AKR-1. Locate the MGT
ID and facility codes on a label inside the MGT enclosure. See previous section
(Selecting the facility codes) to enter the MGT facility code. Refer to the MGT
Obstacle Transmitter Operation section of this manual and the MGT Installation
Sets which relay output activates when a transmitter’s left button is pressed. This
setting effects all transmitters used with the AKR-1. See Figure 7 for transmitter
the Facility Code number (1-15) for each transmitter block added to the AKR-1.
Code = Facility Code number (1-15), 0 = Ignore transmitter Facility Codes
1 = Relay #1 2 = Relay #2 3 = Both Relays 0 = No Output
Instructions for details on MGT transmitter operation. To enter MGT ID:
Removes a Model MGT obstacle transmitter from the AKR-1 memory.
Press: 9 5 # 0 # 0 #
Location = Facility Code Memory Location (1-4)
Status = 0 for Suspend, = 1 for Reactivate
Press: 7 1 # Output #
Output = Output to Activate (0-3)
ID = 1 - 65535
Erase MGT Obstacle Transmitter
Add MGT Obstacle Transmitter
button designations for various models.
Sets the length of time an entry code or transmitter will not function after it is
The following programming steps are used to add, remove, suspend,
and confi gure block coded transmitters used with the AKR-1.
Programming of individual (non-block coded) transmitters is
Sets the starting and ending TX ID numbers for up to four blocks of pre-programmed
transmitters. Enter this command up to four times to select TX IDs for transmitter
blocks one, two, three, and four. Up to 480 transmitters total, distributed in any
This command will erase all transmitters from memory. Transmitter blocks cannot
be erased individually. Single transmitters can be suspended from operation using
This command suspends (prevents transmitter from being used), or reactivates
(un-suspends) the designated transmitter. NOTE: This command will effect the fi rst
occurrence of the TX ID in memory. If, by rare chance, duplicate TX ID numbers
occur in different transmitter blocks, contact Linear Technical Services for details
Minutes = Time in Minutes (1-4), 0 = No Anti-passback
quantity between the blocks, can be added to the AKR-1’s memory.
Press: 9 1 # 0 # 0 #
Suspend/Reactivate an Individual Transmitter
on how to suspend/reactivate individual transmitters.
Start ID = 1-65535
End ID = 1-65535
not supported by the AKR-1.
the Suspend/Reactivate command.
used.
Erase Transmitter Block(s) · Add Transmitter Block(s)

Sets which relay output activates when a transmitter’s right button is pressed. This
setting effects all transmitters used with the AKR-1. See Figure 7 for transmitter
Sets which relay output activates when a transmitter’s top button is pressed. This
setting effects all transmitters used with the AKR-1. See Figure 7 for transmitter
Sets which relay output activates when a transmitter’s bottom-left button is
pressed. This setting effects all transmitters used with the AKR-1. See Figure 7 for
Sets which relay output activates when a transmitter’s bottom-right button is
pressed. This setting effects all transmitters used with the AKR-1. See Figure 7 for
Select Bottom-right Button Output Default: No Output
1 = Relay #1 2 = Relay #2 3 = Both Relays 0 = No Output
1 = Relay #1 2 = Relay #2 3 = Both Relays 0 = No Output
1 = Relay #1 2 = Relay #2 3 = Both Relays 0 = No Output
1 = Relay #1 2 = Relay #2 3 = Both Relays 0 = No Output
Output = Output to Activate (0-3)
Output = Output to Activate (0-3)
Output = Output to Activate (0-3)
Output = Output to Activate (0-3)
transmitter button designations for various models.
transmitter button designations for various models.
button designations for various models.
button designations for various models.
ACT-22
BOTTOM-RIGHT
TRANSMITTER FOUR-CHANNEL
BUTTON BOTTOM-LEFT
ACT-21
RIGHT
BUTTON
RIGHT
BUTTON
LEFT
BUTTON
Figure 7. Transmitter Button Designations
TRANSMITTERS
BOTH EQUALS
TOP BUTTON
BUTTON
BUTTON
TOP
LEFT
LEFT
BUTTON
THREE-CHANNEL
TRANSMITTERS
LEFT
BUTTON
ACT-31
BUTTON
RIGHT
BUTTON
BUTTON BOTTOM-LEFT
BOTTOM-RIGHT
LEFT
BUTTON
TRANSMITTER
FUNCTION
AS LEFT
BUTTON
TOP
BUTTON
BOTH
ACT-34
RIGHT
BUTTON
BUTTON
MDT-2
LEFT
MDT
BUTTON

The two solid state outputs (Output #3 & Output #4) can be
programmed to activate during various conditions. These outputs
can be used to activate indicators or sounders. See Figure 8 for
ALARM PANEL
SOURCE, OUTPUT #4 TRIGGERS A NORMALLY OPEN ALARM PANEL ZONE
OUTPUT
N.O. ZONE
COMMON
EACH
EACH
OUTPUT #4 LIGHTS AN LED AND SOUNDS A BEEPER
Figure 8. Using Solid State Outputs
wiring examples using the solid state outputs.
SOURCE LOW VOLTAGE
1K
LED
END-OF-LINE
RESISTOR
LAMP
1K
LED
Solid State Outputs
COMMON
GROUND
OUTPUT #3
OUTPUT #4
OUTPUT #3
OUTPUT #4
AKR-1
POWER
remain lit until the process is complete, then the yellow
STEP 3 With power applied to the keypad, remove jumper JP2.
STEP 4 Replace jumper JP2. THE MASTER PROGRAMMING
STEP 3 Apply power to the keypad, continue holding the keys
The keypad will begin to beep, signaling that the code
programmable options to the factory default values.
STEP 4 Release the keys. The red and yellow indicators will
STEP 2 Locate jumper JP2. This jumper is used to reset the
the entire memory of the AKR-1 and return all
down until the red indicator starts fl ashing.
STEP 2 Press and hold down the * and # keys.
STEP 1 Disconnect power from the keypad.
CODE IS NOW 123456.
STEP 1 Open the AKR-1 case.
indicator will go out.
has been reset.
master code.
ERASED.
100 mA MAXIMUM · 100 mA MAXIMUM

After the installation is complete. Lock the keypad using the keylock
Figure 10. Locking the Keypad Case
USE KEY TO
ONTO BACKPLATE
HOOK KEYPAD
Locking Keypad
(see Figure 10).
❑ If the keypad’s beeper is too loud for the keypad’s location,
REDUCE THE BEEPER
Figure 9. Removing the Beeper Jumper
The keypad’s beeper can be set to low or high level.
remove jumper JP1 (see Figure 9).

DURING KEYPAD LOCKOUT IF
YELLOW LED WILL LIGHT
WRONG KEY IS PRESSED
RESET KEYPAD IF THE
PRESS STAR KEY TO
ARE ENTERED
Figure 11. Operating the AKR-1
ACCESS IS GRANTED
USERS HAVE UP TO
RED LED TURNS
GREEN WHEN
❑ All digits of the entry code must be entered. Example: If the
❑ If the wrong key is pressed, pressing the * key will reset the
❑ After a valid code has been entered, it will be unusable until
❑ Activate a wireless transmitter within radio range (up to 300
the red indicator will turn green, and the programmed relay
❑ Users of the AKR-1 have up to 40 seconds to key in their
❑ Up to eight seconds are allowed between each keystroke.
turn green and the programmed relay will activate for the
❑ After a valid transmitter is decoded, the keypad will beep,
❑ After a transmitter has been used to gain access, it will be
indicating that the keypad is locked out. The lockout will
❑ If the number of incorrect codes entered exceeds the
❑ After a correct code is entered, the red indicator will
keypad lockout count, the yellow indicator will light,
keypad. The correct code can then be re-entered.
unusable until the anti-passback time expires.
code is 0042, the user must enter “0 0 4 2”.
will activate for the programmed time.
the anti-passback time expires.
remain for one minute.
programmed time.
feet) of the AKR-1.
entry code.

A special mode is provided to test transmitters and determine if there is radio
frequency interference present. The keypad will function normally while it is in
The AKR-1 will beep once when the Radio Test Mode is entered. The keypad’s
yellow indicator will blink quickly when radio signals are detected. If a Linear
MegaCode transmitter is detected, the AKR-1 will beep once when the transmission
is decoded. The AKR-1 will automatically exit Radio Test Mode 45 seconds after
UNIT WILL BEEP WHEN A
YELLOW LED WILL FLASH
Radio Test Mode. To enter Radio Test Mode, use the following command:
IS DECODED
Press the * , # , and “0” buttons
DETECTED
together for two seconds
Figure 12. Radio Test Mode
the last MegaCode signal is decoded.
One Model MGT obstacle transmitter can be programmed into the AKR-1. The
MGT is triggered with a safety edge contact and will activate the AKR-1 Relay #2
☞ NOTE: If an MGT transmitter is programmed, all other transmitters or entry code activations programmed for Relay #2 will be blocked.
If an MGT supervisory condition occurs the AKR-1 will beep every 5 seconds. In
addition, all users will have to enter their entry code twice (within one minute), or
The MGT can monitor and produce three supervisory conditions: low battery, case
tamper/loop fault, and status. To determine the supervisory condition place the
If the transmitter detects a low battery, it will send a low battery supervisory report.
If the transmitter case is opened or the safety edge contact becomes defective,
it will send a tamper/loop fault supervisory report. The keypad’s red indicator will
Status reports are sent every hour. If no status reports are received for eight hours,
AKR-1 in MGT supervisory mode, the same command is used to exit this mode:
While in MGT Supervisory Mode, the following conditions can be displayed:
a status exception condition occurs. The keypad’s green indicator will blink.
activate their transmitter twice (within ten seconds) to request access.
The keypad’s yellow indicator will blink.
for the programmed length of time.
blink.
Tamper/Loop Fault · Low Battery · Status

This Linear product is warranted against defects in material and
workmanship for twelve (12) months. The Warranty Expiration
Date is labeled on the product. This warranty extends only to
wholesale customers who buy direct from Linear or through Linear’s
normal distribution channels. Linear does not warrant this product
to consumers. Consumers should inquire from their selling dealer
as to the nature of the dealer’s warranty, if any. There are no
obligations or liabilities on the part of Linear corporation for
consequential damages arising out of or in connection with use
or performance of this product or other indirect damages with
respect to loss of property, revenue, or profi t, or cost of removal,
installation, or reinstallation. All implied warranties, including
implied warranties for merchantability and implied warranties for
fi tness, are valid only until Warranty Expiration Date as labeled on
the product. This Linear Corporation Warranty is in lieu of all
All products returned for warranty service require a Return Product
Authorization Number (RPA#). Contact Linear Technical Services at
1-800-421-1587 for an RPA# and other important details.
other warranties express or implied.
Form “C” 5 Amps @ 24 Volts maximum
Form “C” 1 Amp @ 24 Volts maximum
Solid state outputs (Outputs #3 & #4)
318 MHz ± 1 MHz -30°C to +65°C
@ 24 VDC maximum
MECHANICAL
ELECTRICAL
RADIO
Short-to-common 100 mA · Relay #2

Changes or modifi cations not expressly described in this manual
or approved by the manufacturer could void the user’s authority to
This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment
generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause
harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If
this equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by
Copyright © 2002 Linear Corporation 217350 D
from that to which the receiver is connected.
one or more of the following measures:
operate the equipment.
receiver.
for help.
Linear radio controls provide a reliable communications link and fi ll
an important need in portable wireless signaling. However, there are
signal at a time and may be blocked by radio signals that
occur on or near their operating frequencies, regardless of
gained prior to acting as a wholesale distributor or dealer,
with FCC Rules and Regulations as Part 15 devices. As
such, they have limited transmitter power and therefore
and these facts should be communicated to the ultimate
protect against undetected interference or fault.
some limitations which must be observed.
limited range.
code settings.
compliance.
users.