EN
Apollo logo
Official user manual

Apollo Ball Valve (IMY)

48 pages·584 KB·Marine Instruments·PDF·ENDEFRITNLJA
Apollo Ball Valve (IMY)
Table of Contents 53 sections Table of Contents · SAFETY IN FOR MA TION 3 · Safety Summary 3 · GENERAL DESCRIPTION 4 · … ShowHide
Table of Contentsp.3SAFETY IN FOR MA TION 3p.5Safety Summary 3p.5GENERAL DESCRIPTION 4p.6Theory Of Operation 4p.6Block Diagram 5p.7PROGRAMMING AND OPERATING THE IMY 6p.8Programming the IMY 6p.8Module #1 - Program Thermistor Type, Temperature Scale (F or C) and Decimal Point Position 8p.10Module #2 - Program Temperature Display Offset and Slope 8p.10Module #3 - Program Functions Accessible W/ Front Panel Lockout 9p.11Module #4 - Program Digital Filter and Remote Input 11p.13Module #5 - Program Integrator/Totalizer 13p.15Module #6 - Program Alarm/Setpoint 14p.16Module #7 - Program Serial Communications 16p.18Module #8 - Program Re-Transmitted Analog Output 17p.19Module #9 - Service Operations 18p.20Operating The IMY 19p.21Quick Programming 19p.21Factory Configuration 20p.22Temperature Monitoring Example 22p.24INTEGRATOR / TOTALIZER / PEAK / VALLEY / TEMPERATURE OFFSET (Optional) 23p.25Integrator/Totalizer 23p.25Peak/Valley 23p.25Offset And Slope Display Temperature 23p.25Integrator/Totalizer Example 24p.26Integrator/Totalizer Set-Up 24p.26ALARMS (Optional) 26p.2820 mA CURRENT LOOP SERIAL COMMUNICATIONS (Optional) 27p.29General Description 27p.29Communication Format 27p.29Sending Commands to the IMY 28p.30Command String Examples 28p.30Receiving Data from the IMY 30p.32Current Loop Installation 30p.32Serial Terminal Descriptions 30p.32Serial Communications Examples 31p.33RE-TRANSMITTED ANALOG OUTPUT (Optional) 33p.35Analog Output Calibration 34p.36APPENDIX fiAfl - INSTALLATION & CONNECTIONS 35p.37Installation Environment 35p.37Panel In stal la tion 35p.37Select AC Power (115/230 VAC) 35p.37EMC Installation Guidelines 36p.38Wiring Connections 37p.39Power Wiring 37p.39Signal Wiring (Thermistor) 37p.39User In put Wiring 37p.39Out put Wiring 37p.39APPENDIX fiBfl - SPECIFICATIONS AND DIMENSIONS 38p.40APPENDIX fiCfl - TROUBLESHOOTING GUIDE 41p.43APPENDIX fiDfl - PROGRAMMABLE FUNCTIONS 42p.44APPENDIX fiEfl - ORDERING INFORMATION 44p.46
Page 1 of the Apollo Ball Valve (IMY) user manual — MODEL IMY INSTRUCTION MANUAL
Page 1 · click to enlarge
Page 1

THE APOLLO INTELLIGENT METER SERIES

Apollo Ball Valve (IMY) — THE APOLLO INTELLIGENT METER SERIES diagram (page 1)
Fig. 1

MODEL IMY INSTRUCTION MANUAL

Page 2 of the Apollo Ball Valve (IMY) user manual — INTRODUCTION
Page 2 · click to enlarge
Page 2

INTRODUCTION

The Intelligent Meter for Thermistor Inputs (IMY) is another unit in our multi- purpose series of industrial control products that are field-programmable to solve multiple applications. This series of products is built around the concept that the end user has the capability to program different personalities and functions into the unit in order to adapt to different indication and control requirements.

The Intelligent Thermistor Meter which you have purchased has the same high quality workmanship and advanced technological capabilities that have made Red Lion Controls the leader in today’s industrial market.

Red Lion Controls has a complete line of industrial indication and control equipment, and we look forward to being of service to you now and in the future.

tions prior to installation and operation of the unit.

Page 3 of the Apollo Ball Valve (IMY) user manual — Table of Contents
Page 3 · Contents
Contents

Contents

Table of Contentsp.3SAFETY IN FOR MA TION 3p.5Safety Summary 3p.5GENERAL DESCRIPTION 4p.6Theory Of Operation 4p.6Block Diagram 5p.7PROGRAMMING AND OPERATING THE IMY 6p.8Programming the IMY 6p.8Module #1 - Program Thermistor Type, Temperature Scale (F or C) and Decimal Point Position 8p.10Module #2 - Program Temperature Display Offset and Slope 8p.10Module #3 - Program Functions Accessible W/ Front Panel Lockout 9p.11Module #4 - Program Digital Filter and Remote Input 11p.13Module #5 - Program Integrator/Totalizer 13p.15Module #6 - Program Alarm/Setpoint 14p.16Module #7 - Program Serial Communications 16p.18Module #8 - Program Re-Transmitted Analog Output 17p.19Module #9 - Service Operations 18p.20Operating The IMY 19p.21Quick Programming 19p.21Factory Configuration 20p.22Temperature Monitoring Example 22p.24INTEGRATOR / TOTALIZER / PEAK / VALLEY / TEMPERATURE OFFSET (Optional) 23p.25Integrator/Totalizer 23p.25Peak/Valley 23p.25Offset And Slope Display Temperature 23p.25Integrator/Totalizer Example 24p.26Integrator/Totalizer Set-Up 24p.26ALARMS (Optional) 26p.2820 mA CURRENT LOOP SERIAL COMMUNICATIONS (Optional) 27p.29General Description 27p.29Communication Format 27p.29Sending Commands to the IMY 28p.30Command String Examples 28p.30Receiving Data from the IMY 30p.32Current Loop Installation 30p.32Serial Terminal Descriptions 30p.32Serial Communications Examples 31p.33RE-TRANSMITTED ANALOG OUTPUT (Optional) 33p.35Analog Output Calibration 34p.36APPENDIX fiAfl - INSTALLATION & CONNECTIONS 35p.37Installation Environment 35p.37Panel In stal la tion 35p.37Select AC Power (115/230 VAC) 35p.37EMC Installation Guidelines 36p.38Wiring Connections 37p.39Power Wiring 37p.39Signal Wiring (Thermistor) 37p.39User In put Wiring 37p.39Out put Wiring 37p.39APPENDIX fiBfl - SPECIFICATIONS AND DIMENSIONS 38p.40APPENDIX fiCfl - TROUBLESHOOTING GUIDE 41p.43APPENDIX fiDfl - PROGRAMMABLE FUNCTIONS 42p.44APPENDIX fiEfl - ORDERING INFORMATION 44p.46
Page 5 of the Apollo Ball Valve (IMY) user manual — DEFINITION OF TERMS
Page 5 · click to enlarge
Page 5

All safety related regulations, local codes and instructions that appear in

the manual or on equipment must be observed to ensure personal safety and to

prevent damage to either the instrument or equipment connected to it. If

equipment is used in a manner not specified by the manufacturer, the

Do not use this unit to directly command motors, valves, or other actuators

not equipped with safeguards. To do so, can be potentially harmful to persons

Signal level, special equipment or parts of equipment, telecommunication,

electronic, etc. with smaller transient overvoltages than Installation

Local level, appliances, portable equipment, etc. with smaller transient

overvoltages than Installation Category (overvoltage category) III.

INSTALLATION CATEGORY (overvoltage category) I:

INSTALLATION CATEGORY (overvoltage category) II:

protection provided by the equipment may be impaired.

or equipment in the event of a fault to the unit.

Category (overvoltage category) II.

SAFETY INFORMATION

DEFINITION OF TERMS

SAFETY SUMMARY

Page 6 of the Apollo Ball Valve (IMY) user manual — GENERAL DESCRIPTION
Page 6 · click to enlarge
Page 6

More than one unit can be connected in the loop with other RLC products

An optional 4 to 20 mA or 0 to 10 VDC re-transmitted analog output can be

scaled by the user to interface with a host of recorders, indicators and

controllers. The type of analog output is determined by the model ordered.

The indicator has several built-in diagnostic functions to alert operators of

most malfunctions. Extensive testing of noise interference mechanisms and

full burn-in make the indicator extremely reliable in industrial environments.

The die-cast front bezel meets NEMA 4/IP65 requirements for washdown

applications. Plug-in style terminal blocks simplify installation wiring and

The IMY employs a microprocessor to perform the A/D conversion on the

input signal via a voltage-to-frequency converter. It digitally scales the

result, corrects for meter drift which may be present and then displays the

result in a 6-digit display (4 digits for temperature, 6 digits for totalizer). The

inputs are filtered to enhance the stability of the display. A non-volatile

E 2PROM provides permanent data retention for operating variables. The display consists of drivers and 6-digit solid-state LEDs. The alarm option

employs opto-isolators to isolate the open collector devices from meter

common. Operating in parallel, the relays are type Form-C and are rated at

5-amps. The serial communication option features a built-in 20 mA current source and complete opto-isolation. The analog option features a 12-bit DAC

and provides a 4 to 20 mA or 0 to 10 VDC output that is digitally scaled. The

(See Ordering Information for available models.)

which have serial communications capabilities.

analog output is isolated from meter common.

THEORY OF OPERATION

change-outs.

The Apollo Intelligent Thermistor Meter (IMY) accepts standard Thermistor

inputs and precisely linearizes them into temperature readings. Like an RTD, a

thermistor is a temperature sensitive resistor, but the thermistor provides a much

larger resistance change per degree. Since thermistors provide a large resistance

change, significant errors from long lead lengths or switches are eliminated.

Other advantages of using a thermistor are accuracy, repeatability, long term

stability, and sensor cost. A full 6-digit display accommodates a wide range of

temperature inputs and holds large totalization values. State-of-the-art digital

circuitry virtually eliminates errors due to drift. A full complement of option

The IMY supports two popular thermistor series - the 400 Series 2,252

Ohm thermistor, and the 700 Series Thermolinear thermistor. Selection

The indicator features a readout choice of either Fahrenheit or Celsius with

0.1 or 1 degree of resolution. English Style display prompts aid the operator through set-up and operation. A front panel lock-out menu protects set-up

data and operation modes from unauthorized personnel. Programmable

digital filtering enhances the stability of the reading. Programmable remote

input “E1-CON” pin can be utilized to control a variety of functions, such as

totalizing, alarm control, peak/valley reading, display hold or offset

operations. All set-up data is stored in the E 2PROM, which will hold data for a minimum of 10 years without power.

An optional integrator/totalizer can be used to totalize or integrate

temperatures up to a maximum display value of 999,999. It features

independent scaling and a low temperature cut-out to suit a wide variety of

temperature integration applications. A programmable remote input,

“E2-CON”, is included with the option and can be utilized to control a variety

of functions, such as totalizing, alarm control, peak/valley readings, display

hold or offset operations, simultaneously with the “E1-CON”. Peak/valley

(max/min) reading memory functions are included with this option and they

are easily recalled and controlled by either the front panel or a remote input.

Optional dual relays with parallel solid state outputs are fully programmable

to operate in a wide variety of modes to suit many control or alarm applications.

Optional 20 mA loop, bi-directional serial communications provides

computer and printer interfacing to extend the capabilities of the indicator.

between the two types is done in Programming Module 1.

packages is available to fulfill many process applications.

All readings are retained at power-down.

GENERAL DESCRIPTION

Page 7 of the Apollo Ball Valve (IMY) user manual — BLOCK DIAGRAM
Page 7 · click to enlarge
Page 7

BLOCK DIAGRAM

*Reference Installation and Connections section for power connection.

Page 8 of the Apollo Ball Valve (IMY) user manual — PROGRAMMING THE IMY
Page 8 · click to enlarge
Page 8

Although the unit has been programmed at the factory, the set-ups will

generally have to be changed to suit the application. Basic set-up is complete

after selection of the temperature units, decimal point placement, and

Before actually trying to program the indicator, it is advised to organize all

the data for the programming steps to avoid any possible confusion and to

To set-up the indicator, connect primary power and signal wires as

outlined in the connections section (Appendix “A”). Remove the jumper

wire (if installed) from TBA #3 (PGM. DIS.). This will allow the operator to

enter and modify all of the indicator’s parameters. Press the front panel

button labeled “P”, momentarily. Briefly, the display will show “Pro”

alternately flashing with “0”. This is the indicator’s programming mode.

The programming mode is divided into sections, numbered 0-9, each of

which can be individually accessed. The front panel “UP” and “DOWN”

arrow buttons can be used to select one of these numbers and the “P” button

can be used to enter the selected programming module. In all of the

programming modules, “UP” and “DOWN” are used to either select from a

list of choices or enter a value. The “P” button is used to save the new value

and progress to the next step within a module (Note: the new value takes

effect when “P” is pressed). Upon completion of a module, the indicator

returns to the “Pro” < > “0” stage. Pressing the “P” button at this time

causes the unit to display “End” after which the unit returns to the normal

display mode. The following table explains the basic function of each step.

PROGRAMMING AND OPERATING THE IMY

read the programming procedure entirely before proceeding.

selection of the digital filtering level.

PROGRAMMING THE IMY

prompt and the actual data.

Page 9 of the Apollo Ball Valve (IMY) user manual — DISPLAY RESULT OF “P” BUTTON
Page 9 · click to enlarge
Page 9

“Pro” < > “5” - This module sets the time base, scale factor and low

temperature disable function for the optional integrator/

“Pro” < > “6” - This module allows programming for the basic

configuration of the alarm option. The programming

includes HI/LO acting, tracking, alarm display, latched

or auto-reset, assignment to either the input or the

“Pro” < >“7” - Module #7 is the serial communication parameter

programming. Baud rate, unit address, print request

“Pro” < > “8” - This module allows digital scaling of the retransmitted

analog output. Display values that correspond to 4 mA or

0 VDC and 20 mA or 10 VDC are keyed-in to scale the output and it may be assigned to either the input or the

“Pro” < > “9” - This module is the service operation sequence and is not

normally accessed by the user. This step re-calibrates the

basic input and is used to compensate for long-term drift.

Execution of this module should be done by technicians

with the proper equipment in accordance with a

maintenance plan of yearly recalibrations. A code number

entry step is used to protect from inadvertent entries. Also,

there is a number of other access codes which provide test

integrator/totalizer, and alarm and hysteresis values.

function and condensed prints are all programmable.

and set-up changes as an aid in troubleshooting.

DISPLAY RESULT OF “P” BUTTON

integrator / totalizer.

totalizer.

“Pro” < > “0” - Causes the indicator to return to normal display mode.

Any changes to set-up data are permanently stored in the

E 2PROM. “Pro” < > “1” - Entry into this module allows the user to select the

Thermistor type, whether the display will read in degrees

Fahrenheit (F) or Celsius (C), and display decimal point

non-standard display slope and display offset values.

This enables the meter to be “scaled” to a calibrated

temperature probe. (This scaling is NOT required for

“Pro” < > “3” - Module #3 allows the user to program what can be

accessed from the front panel when the PGM. DIS.

(Program Disable, TBA #3) pin is connected to common.

This feature protects critical set-up data from accidental

modification while allowing access to setpoints and other

functions. The front panel lock-out menu (quick

programming) includes setpoint modification,

ability to change the information that can be accessed from

the front panel when the “PGM. DIS.” terminal is connected

“Pro” <> “4” - Module #4 programs the digital filtering level and the

function of the remote input “E1-CON” pin (TBA #4), and

if the totalizer option is installed, the remote input

“E2-CON” pin (TBA #8). The functions of the remote E1

and E2 pins are the same and include display hold,

peak/valley modes, totalizer reset, alarm reset, temperature

“Pro” < >“2” - Entry into this module allows the user to select

integrator/totalizer resetting, and peak/valley resetting.

offset, reading synchronization or print request.

DISPLAY RESULT OF “P” BUTTON

most applications.)

to “COMM.”.

position.

Page 10 of the Apollo Ball Valve (IMY) user manual — “SCALE” < > “F”
Page 10 · click to enlarge
Page 10

MODULE #1 - PROGRAM THERMISTOR TYPE, TEMPERATURE SCALE (F OR C)

MODULE #2 - PROGRAM TEMPERATURE DISPLAY OFFSET AND SLOPE

AND DECIMAL POINT POSITION

Select the desired Thermistor type by pressing the “UP” or “DOWN”

Select the desired temperature scale by pressing the “UP” or “DOWN”

Select the desired decimal point location by pressing the “UP” or

If the totalizer option is installed, the offset and slope can be programmed

for various temperature probe differences. See the Offset and Slope Display

Select the desired temperature display slope value by pressing the “UP” or

Select the desired temperature display offset value by pressing the “UP” or

“SLOPE” < > “0.0001” to “10.0000” (ex. 1.0309)

“OFFSEt” < > “-999” to “9999” (ex. -17.5)

“tYPE” < > “400” 400 = 400 Series, 2,252 ohm “700” 700 = Thermolinear Series

“0.0”

“C”

“ dECPNt” < > “0”

“SCALE” < > “F”

Temperature section for more details.

the “DOWN” button.

the “DOWN” button.

“DOWN” button.

button.

button.

Page 11 of the Apollo Ball Valve (IMY) user manual — DISPLAY ALARM VALUES
Page 11 · click to enlarge
Page 11

If the alarm option is installed and if either alarm is programmed to latch,

If the integrator/totalizer option is installed, this selects whether peak and

If “YES” was selected for the previous step, this selects whether the peak

and valley buffers may be reset from the front panel. (If “NO” was selected,

If the integrator/totalizer option is installed, this selects whether the

display can be switched from input display to total display and from total

If the integrator/totalizer option is installed, this selects whether the total

then this step defaults to “NO” and will not be displayed for selection.)

this will select if a latched alarm(s) can be reset from the front panel.

DISPLAY PEAK/VALLEY MEMORY BUFFER

“dSPbUF” < > “yES” or “NO”

RESET PEAK/VALLEY MEMORY BUFFER

“rStbUF” < > “yES” or “NO”

“SELdSP” < > “yES” or “NO”

“rSt AL” < > “yES” or “NO”

“rSttOt” < > “yES” or “NO”

MODULE #3 - PROGRAM FUNCTIONS ACCESSIBLE W/ FRONT PANEL LOCKOUT

RESET LATCHED ALARMS

valley buffers will be displayed.

can be reset from the front panel.

the only display accessible.

SELECT DISPLAY *

display to input display.

RESET TOTAL *

This programming module programs what is accessible through the front

information that can be accessed from the front panel when the “PGM. DIS.”

If the alarm option is installed, this selects whether the alarm values will or

If “YES” was selected for display alarm values, this will select if alarm

values may be modified from the front panel. (If “NO” was selected for

display alarm values, then this step will default to “NO” and will not be

If the alarm option is installed, this selects whether the hysteresis values

If “YES” was selected for display hysteresis values, this selects whether

hysteresis values may be modified from the front panel. (If “NO” was

selected for display hysteresis value, then this step will default to “NO” and

* Note: This function operates independent of the state of the “PGM. DIS.” pin.

Note: This sequence may be locked-out due to other programmed sequences.

panel when the PGM. DIS. pin is connected to common (COMM.).

“dSPHYS” < > “yES” or “NO”

“ENtHYS” < > “yES” or “NO”

“dSP AL” < > “yES” or “NO”

“ENt AL” < > “yES” or “NO”

DISPLAY HYSTERESIS VALUES

ENTER HYSTERESIS VALUES

terminal is connected to “COMM.”.

will not be displayed for selection.)

DISPLAY ALARM VALUES

ENTER ALARM VALUES

will or will not be displayed.

displayed for selection.)

will not be displayed.

Page 12 of the Apollo Ball Valve (IMY) user manual — TEMPERATURE OFFSET VALUE
Page 12 · click to enlarge
Page 12

If the Integrator/Totalizer/Peak/Valley/Temperature Offset option is

If “YES” was selected for the previous step, this selects whether the offset

value can be entered from the panel. (If “NO” was selected, then this step

Depending on functions selected under Pro 3 and Pro 6, alarms, hysteresis,

peak, valley and offset values can be monitored and/or changed with PGM.

DIS. is tied to COMM. This provides a “QUICK PROGRAMMING” method

for “day to day” process changes. (See QUICK PROGRAMMING SECTION

Note: This sequence may be locked-out due to other programmed sequences.

installed, this selects whether the programmed offset value will be displayed.

* Note: This function operates independent of the state of the “PGM. DIS.” pin.

defaults to “NO” and will not be displayed for selection.)

“dSPOFF” < > “yES” or “NO”

“ENtOFF” < > “yES” or “NO”

TEMPERATURE OFFSET VALUE

ENTER OFFSET VALUE

for more details.)

Page 13 of the Apollo Ball Valve (IMY) user manual — PROGRAM DIGITAL FILTERING
Page 13 · click to enlarge
Page 13

“3” - A low level allows totalization as long as the input is

low. If the input goes high, totalization is stopped and

the contents are saved. This acts as a totalization

“4” - A low level holds the display (display hold). While this

input is low, the indicator continues to process the

input signal and drive the alarms, totalizer, etc., with

the actual signal. The contents of the totalizer are held

requested via serial, the value on the display will be

“5” - A negative going edge resets both peak and valley buffers.

“6” - A negative going edge resets only the peak buffer and

the indicator enters a peak reading display mode as

long as the input is low. If the input goes high, peak

detection and indication are stopped and the last peak

“7” - A negative going edge resets only the valley buffer and

the indicator enters a valley reading display mode as

long as the input is low. If the input goes high, valley

detection and indication are stopped and the last valley

“8” - If the alarm option is installed, a negative going edge

totalization enable control from Time 1 to Time 2.

sent instead of the actual input value at that time.

display until the next time the P/V is called up.

at the same time the input display is held.

enable control from Time 1 to Time 2.

resets the latched alarm(s).

reading is retained.

reading is retained.

MODULE #4 - PROGRAM DIGITAL FILTER AND REMOTE INPUT

If the displayed process signal is difficult to read due to small process

variations or noise, increased levels of filtering will help to stabilize the

display. This programming step may be used in conjunction with display

rounding programming (Pro 1 & 2) to help minimize this effect. Although the

digital filter features a “moving window” to help minimize response time,

The function of the remote input “E1-CON” (TBA #4) and, if the totalizer

option is installed, the remote input “E2-CON” (TBA #8) are the same.

Functions are activated, as described in the appropriate function, when

connected to signal common (TBA #7). Whether a function is edge or level

activated, it must be held low for a minimum of 20 msec in order for the

function to occur. The remote input pins can be used simultaneously and with

any combination of functions. When pins are tied together and activated,

“E1-CON”< > “0” - If the Totalizer/Peak/Valley/Display Offset option is

installed, a negative going edge offsets the displayed

temperature to zero. (At the time the E-Pin is activated,

the value of the actual temperature being displayed is

placed in the location of the display offset value. To

bring the unit into the normal temperature display

“1” - A negative going edge resets the contents of the

totalizer to zero. Totalization commences regardless

“2” - A negative going edge resets the contents of the

totalizer to zero and allows totalization as long as the

input is low. If the input goes high, totalization is

stopped and the contents are saved. This acts as a

higher degrees of filtering levels will have slightly longer response times.

PROGRAM FUNCTION OF E1-CON AND OPTIONAL E2-CON

mode, reset the offset value to zero via the front panel.)

of the state of the remote input.

“FILter” < > “0” - no digital filtering

“2” - increased filtering

“3” - maximum filtering

E1-CON function is generally performed first.

“1” - normal filtering

PROGRAM DIGITAL FILTERING

Page 14 of the Apollo Ball Valve (IMY) user manual — PROGRAM FUNCTION OF E1-CON AND OPTIONAL E2-CON
Page 14 · click to enlarge
Page 14

“9” - If the alarm option is installed, a low level resets a latched or

unlatched alarm into its inactive state. This provides manual

override of alarms for system start-up and other unusual

“10” - A negative going edge toggles the display between “input”

and “total” (from input to total, or vice versa). No action is

“11” - A negative going edge zeros (tares) the input signal and adds

the value that was in the input display to the totalizer value,

every time this operation is performed. The time-base, scale

factor and low cut-out in “Module #5” are in affect disabled,

“12” - Display hold with offset. A negative going edge tares (zeros)

the input signal. Prior to the offset operation, the input

signal is saved and held (display hold) as long as the remote

input pin is low. On the positive edge, the input display will

show zero. If there is an increase to the input signal while the

remote input is low, the display will reflect (show) the

“13”- Instrument reading synchronization. A low level disables all

meter operations (alarms, total, analog out, etc.). A positive

edge resets the start of the A/D conversion, to allow

synchronization with external processes and controls.

While in this function, the other E-CON pin will be

“14”- Print request. Transmits data according to the print options

that have been selected in Program Module #7. If the low

“E2-CON” < > If the totalizer option is installed, E2-CON has the

PROGRAM FUNCTION OF E1-CON AND OPTIONAL E2-CON

time exceeds 800 msec, a second print-out may occur.

same programmable functions as E1-CON.

taken on the positive going edge.

when this function is selected.

events such as system testing.

increase at the positive edge.

operational.

(Cont’d)

Page 15 of the Apollo Ball Valve (IMY) user manual — INTEGRATOR/TOTALIZER
Page 15 · click to enlarge
Page 15

PROGRAM THE INTEGRATOR/TOTALIZER SCALE FACTOR

As explained in the previous programming step, a multiplying scale factor

can be used to scale the update rate as required. This may be used to span the

standard ranges. A scale factor of “1.000” has no effect on the standard ranges.

In order to prevent false integration/totalization in situations where

integration/totalization is undesirable, a programmable setpoint can be used

to disable integration/totalization when the input temperature falls below this

TB = If Program Select Number Chosen Is: Enter in Formula

D.T.D.P. = Desired Totalizer Value Decimal Point Enter in Formula

I.D.D.P. = Input Display Value Decimal Point Enter in Formula

PROGRAM THE LOW-END CUTOUT (low temperature level

0 1 0.0 10 0.00 100 0.000 1000 0.0000 10000

“0” for sec. 1 “1” for min. 60 “2” for hr. 3600

0 1 0.0 10

TIME = Actual Time period in seconds

“SCLFAC” < > “0.001” to “100.000”

I.D. = Input Display Value

“Lo-cut” < > “-999” to “9999”

“tbASE” < > “0” - per second

“1” - per minute

“2” - per hour

low-end cutout level.

MODULE #5 - PROGRAM INTEGRATOR/TOTALIZER

Programming for the integrator/totalizer consists of four programming

stepstotalizer decimal point position, time base, scale factor and low

temperature disable. Note that the decimal point position of the

integrator/totalizer can be set independent of the decimal point position of the

input. The totalizer value will roll over and flash when the total exceeds,

999999 or -99999, indicating an overflow condition. Reverse signal input will cause the totalizer value to count in the opposite direction and eventually

The time base determines the rate at which readings increase. The

integrator/totalizer display is updated 2 12 times per second regardless of time

base selected, but longer time bases decrease the magnitude of each increase.

The three time bases are per second, per minute and per hour. A constant input

temperature of 100 for example, would integrate/totalize to in one

second (with a TB of 1 sec.), 100 in one minute (with a TB of 1 min.), and 100

in one hour (with a TB of 1 hr.). (Note: Input changes can be made

synchronous to the display by programming E1 or optional E2-CON pin for

function 13, Instrument reading synchronization.) A multiplying scale factor

may be used to span the standard time ranges (or divide if scale factor < 1).

The following equation expresses the integration/totalization process.

PROGRAM DECIMAL POINT POSITION FOR THE

PROGRAM INTEGRATOR/TOTALIZER TIME BASE

The decimal point position for the totalizer are as follows:

“0.0000”

“0.00”

“0.000”

S.F. = D.T. x T.B. x D.T.D.P.

I.D. TIME I.D.D.P.

“0.0”

S.F. = Programmable Scale Factor

D.T. = Desired Totalizer value for a

“dECPNt” < > “0”

no longer be in an overflow condition.

T.B. = Programmable Time Base

INTEGRATOR/TOTALIZER

disable) · fixed time duration

Page 16 of the Apollo Ball Valve (IMY) user manual — ALARM TRACKING
Page 16 · click to enlarge
Page 16

Alarm #1 may be programmed to activate on either the input or the

integrator/totalizer value. If the integrator/totalizer option is not installed,

The range of the alarm value is -999 to 9,999 for the input display and

The hysteresis (deadband) value for alarm #1 may be programmed from 1

to 9,999 for the input and 1 to 999999 for the totalizer option. The value is

either added to or subtracted from the alarm value depending on whether the

The action of alarm #1 may be programmed to activate either when the display

The reset action of alarm #2 may be programmed to reset automatically

(unlatched) or be programmed to require a manual reset (latched), through

either a remote input (E1-CON or optional E2-CON) or through the front

panel. Latched alarms are usually used when an operator is required to take

value goes above the alarm value (high acting) or goes below it (low acting).

(Cannot be programmed if alarm latch is programmed)

alarm is high or low acting. (See “alarm” section for operation.)

PROGRAM HYSTERESIS VALUE FOR ALARM #1

“ASN-1” < > “INPUt” or “totAL”

AUTO OR MANUAL RESET FOR ALARM #2

“AL-1” < > “-999” to “9999”

“HyS-1” < > “1” to “9999”

“LAtC-2” < > “yES” or “NO”

“Act-1” < > “HI” or “LO”

ALARM #1 ASSIGNMENT TO INPUT OR

-99999 to 999999 for the totalizer option display.

PROGRAM VALUE FOR ALARM #1

ALARM #1 HIGH OR LOW ACTING

some action for the alarm condition.

INTEGRATOR/TOTALIZER

this step defaults to the input.

If the alarm option is installed, this module is used to configure the

operation of the alarms to a variety of combinations. The programmable

options are HI/LO acting, auto/manual reset (latching), tracking, assignment

to input or integrator/totalizer, display alarms, alarm values and hysteresis

With alarm tracking, whenever alarm #2 is changed, alarm #1 will also

change so that the offset between alarm #2 and alarm #1 remains the same.

This is useful for hierarchical setpoints (pre-alarm and alarm) when one

change applies to both alarm values. When programming from the front

panel, tracking only occurs when PGM. DIS. is low (front panel lock-out

mode, alarm #1 will not appear). Tracking will always occur if alarm #2 is

If display alarms are desired, a message will flash on the display every 5-10

secs when an alarm activates. For alarm 1, the message will flash “AL1 ON”

and alarm 2 will flash “AL2 ON”. This warns an operator of an alarm condition.

The reset action of alarm #1 may be programmed to reset automatically

(unlatched) or be programmed to require a manual reset (latched), through

either a remote input (E1-CON or optional E2-CON) or through the front

panel. Latched alarms are usually used when an operator is required to take

The message will stop when the unit is no longer in an alarm condition.

MODULE #6 - PROGRAM ALARM/SETPOINT

modified via serial communications independent of PGM. DIS.

AUTO OR MANUAL RESET FOR ALARM #1

“LAtC-1” < > “yES” or “NO”

“trAc” < > “yES” or “NO”

“dISP” < > “yES” or “NO”

some action for the alarm condition.

ALARM TRACKING

DISPLAY ALARMS

(deadband) values.

Page 17 of the Apollo Ball Valve (IMY) user manual — TOTALIZER
Page 17 · click to enlarge
Page 17

Alarm #2 may be programmed to activate on either the input or the

integrator/totalizer value. If the integrator/totalizer option is not installed,

The range of the alarm value is -999 to 9,999 for the input display and

The hysteresis (deadband) value for alarm #2 may be programmed from 1

to 9,999 for the input and 1 to 999999 for the totalizer option. The value is

either added to or subtracted from the alarm value depending on whether the

The action of alarm #2 may be programmed to activate either when the display

peak, and valley values can be monitored and/or changed when PGM. DIS. is

tied to COMM. This provides a “QUICK PROGRAMMING” method for “day

to day” process changes. (See QUICK PROGRAMMING SECTION for more

value goes above the alarm value (high acting) or goes below it (low acting).

ALARM #2 ASSIGNMENT TO INPUT OR INTEGRATOR/

alarm is high or low acting. (See “alarms” section for operation.)

(Cannot be programmed if alarm latch is programmed)

PROGRAM HYSTERESIS VALUE FOR ALARM #2

“ASN-2” < > “INPUt”or “totAL”

“AL-2” < > “-999” to “9999”

“HyS-2” < > “1” to “9999”

“Act-2” < > “HI” or “LO”

-99999 to 999999 for the totalizer option display.

PROGRAM VALUE FOR ALARM #2

ALARM #2 HIGH OR LOW ACTING

this step defaults to the input.

TOTALIZER

details.)

Page 18 of the Apollo Ball Valve (IMY) user manual — BAUD RATE
Page 18 · click to enlarge
Page 18

When transmitting data, the IMY can be programmed to suppress the

address number, mnemonics and some spaces, if desired, by selecting “NO”.

A selection of “NO” results in faster transmission. This feature may be

helpful when interfacing with a computer. When interfacing to a printer, a

“6” - input signal, totalizer, peak, valley, and offset

“3” - input signal, alarm 1, alarm 2, hysteresis 1,

“8” - input signal, totalizer, alarm 1, and alarm 2

hysteresis 1, hysteresis 2, peak, valley, and

An example of full and abbreviated transmission is shown below:

“9” - input signal, totalizer, alarm 1, alarm 2,

hysteresis 2, peak, valley, and offset

“1” - input signal, peak, valley and offset

2 INP -125.7F < CR > < LF > Full transmission

-125.7 < CR > < LF > Abbreviated transmission

“2” - input signal, alarm 1 and alarm 2

“7” - totalizer, alarm 1, and alarm 2

“5” - input signal and totalizer

FULL OR ABBREVIATED TRANSMISSION

“FULL” < > “yES” or “NO”

“Print” < > “0” - input signal

“yES” response is usually desirable.

MODULE #7 - PROGRAM SERIAL COMMUNICATIONS

Several programmable parameters must be programmed before serial

Select one of the baud rates from the list to match the baud rate of the

To allow multiple units to communicate on the 20 mA loop, different address

numbers must be assigned to each unit. If only one unit is on the loop, an

address of “0” may be given, eliminating the need for the address command. “

A selection of print operations can be programmed. A print operation

occurs when a print request is activated via E1-CON (TBA #4) or optional

E2-CON (TBA #8), or a “P” command is sent from a terminal via the serial

communications option. If the option to which a particular print code applies

If the totalizer is overflowed, an asterisk (*) will precede the digits that are

printed (ex. *000127 positive overflow, -*00127 negative overflow). If the

temperature exceeds the range of the unit, the print-out will show

“OLOLOL”. If the sensor opens, the print-out will show “ULULUL”. For the

negative direction or shorted, the print-out will show “SHOrt”.

is not installed, then that parameter will not be printed.

“bAud” < > “300” - 300 baud “600” - 600 baud “1200” - 1200 baud “2400” - 2400 baud

“AddrES” < > “0” to “99”

PRINT REQUEST FUNCTION

printer, computer, controller, etc.

UNIT ADDRESS NUMBER

communication can occur.

BAUD RATE

“4” - totalizer · offset

Page 19 of the Apollo Ball Valve (IMY) user manual — ANALOG OUTPUT LO DISPLAY VALUE
Page 19 · click to enlarge
Page 19

MODULE #8 - PROGRAM RE-TRANSMITTED ANALOG OUTPUT

This programming module allows digital scaling of the 4 to 20 mA or 0 to

10 VDC analog output. The type of analog output is determined by the model ordered. (See Ordering Information for available models.) The display value

at which 4 mA or 0 VDC and the display value at which 20 mA or 10 VDC are

transmitted are keyed-in. The indicator automatically calculates slope and

intercept values to complete the scaling. The analog output then follows the

calculated display value and as such will update every measurement cycle.

The output may also be programmed to proportionally re-transmit the

contents of the totalizer instead of the input. Reverse acting output can be

achieved by programming the “high” display value for the “AN-LO”

THE UNIT. Fine offset and span adjustment pots are externally accessible to

compensate for small drifts in the output. These pots have been set at the

Program whether the input or the totalizer will serve as the basis for the

analog output signal. If the integrator/totalizer option is not installed, then

Program the display value at which the analog output transmits 4 mA or 0

Program the display value at which the analog output transmits 20 mA or

programming step and the “low” display value for the “AN-HI” step.

“-99999” to “999999” for “totAL”

“-99999” to “999999” for “totAL”

“AN-Lo” < > “-999” to “9999” for “INPUt”

“AN-HI” < > “-999” to “9999” for “INPUt”

“ASIN” < > “INPUt” or “totAL”

factory and do not normally require adjustment.

ANALOG OUTPUT LO DISPLAY VALUE

ANALOG OUTPUT HI DISPLAY VALUE

ANALOG OUTPUT SOURCE

this step defaults to “Input”.

10 VDC.

VDC.

Page 20 of the Apollo Ball Valve (IMY) user manual — ENTER ZERO REFERENCE
Page 20 · click to enlarge
Page 20

Indicator calibration is complete. It is recommended that calibration be

The internal serial communications hardware in the IMY can be tested to

verify proper operation. The procedure consists of connecting the Serial

All of the programming in Modules #1 through #8 can be restored back to

the factory configuration by entering a specific access code (refer to the

“Factory Configuration” section for the data that will be entered). The

procedure consists of entering “Pro 9”, keying-in “Code 66”, then pressing

“P”. The IMY responds by displaying “INItAL” for several seconds, and

checked by comparing the displayed temperature with a precision thermometer.

RESTORING ALL PROGRAMMING PARAMETERS BACK TO

SERIAL HARDWARE (loop-back) DIAGNOSTICS

were programmed into the IMY will be overwritten.

“CodE” < > “66”

Input (SI), Serial Output (SO), and

20 mA Source into a simple loop, and then entering an access code.

Connect the IMY as shown at

right. Enter “Pro 9”, key-in “Code

39”, and then press “P”. If the serial communication hardware is OK,

Conversely, if there is an internal

problem, “FAIL” will be displayed.

After the diagnostic test is complete,

FACTORY CONFIGURATION

press “P” to return to “Pro 0”.

“PASS” will be displayed.

“CodE” < > “39”

then returns to “Pro 0”.

The indicator has been fully calibrated at the factory. If the unit appears to

be indicating incorrectly or inaccurately, refer to the troubleshooting section

When re-calibration is required (generally every 2 years), this procedure

should only be performed by qualified technicians using appropriate

The procedure consists of applying accurate signal levels to the indicator in

a series of two steps. Allow a 30 minute warm-up period before starting this

“Code 48” must be keyed-in prior to the calibration sequence to guard

against inadvertent entries. Access code numbers other than those listed in

this section should not be entered at this step. If any are entered, undefined or

If the code number for the previous step was not recognized, the indicator

returns to “Pro 0”, with no action taken. Otherwise, the calibration procedure

equipment. Resistance source accuracies of 0.01% or better are required.

Apply 0 ohms to input by shorting Terminals 6 and 7 as

shown in the drawing to the right. Allow to stabilize for 20

Connect a precision (0.01%) 5.11 K resistor across

MODULE #9 - SERVICE OPERATIONS

Allow to stabilize for 20 seconds before pressing “P”.

module without completing the calibration procedure.

“CodE” < > “0” to “99”

“StEP 1” (Press “P”)

APPLY PRECISION RESISTANCE

“StEP 2” (Press “P”)

unpredictable operation could result.

before attempting this procedure.

ENTER ZERO REFERENCE

ENTER ACCESS CODE

seconds before pressing “P”.

Terminals 6 and 7.

procedure.

is started.

Page 21 of the Apollo Ball Valve (IMY) user manual — QUICK PROGRAMMING
Page 21 · click to enlarge
Page 21

The other operations in the “quick programming” mode require special

The front panel buttons are not only used to input data during the

programming and “quick programming” mode, but control a number of other

functions (if enabled in Pro “3”) as well. In the normal meter mode, these

After each operation, a message will appear briefly to acknowledge the action.

To reset latched alarm, scroll through steps in “quick

programming” mode using the “P” button until “LAtCH1” or

“LAtCH2” appears in the display. If they do not appear, they are

To reset peak and valley buffers, scroll through steps in “quick

programming” mode using the “P” button until “PEA” or

To reset totalizer to zero: Press and hold “UP” and press “P”.

To enter programming or “quick programming”: Press “P”.

To resetWhile “LAtCH1” or “LAtCH2” is being

displayed, press and hold “DOWN” and press “P”.

Pressing “P” alone causes a step to the next item

To resetWhile “PEA” or “VAL” is being

displayed, press and hold “DOWN” and press “P”.

Pressing “P” alone causes a step to the next item

To switch to display of input: Press “DOWN” button.

To switch to display of totalizer: Press “UP” button.

with no action taken on the buffer.

with no action on the alarm.

“VAL” appears in the display.

key sequences as shown:

functions are available:

not latched.

After completing all set-up operations, the unit is ready to install and

operate. After power is applied, a display test consisting of illuminating all

segments for 2 seconds is performed. Afterward, the input or total will

appear, depending upon the display mode prior to the last power-down. To

switch the display to input, press “DOWN” (indicated by “arrows” on the

front panel) and to switch it to total, press “UP”. If the integrator/totalizer

option is not installed, then display switching to total is inoperative. A minus

To limit access to the set-up parameters, connect a key-switch or wire from

PGM. DIS. (TBA #3) to COMM. (TBA #7). With this pin connected to

common, only a predetermined amount of data can be viewed or altered, as

programmed by programming module #3. If “NO” was programmed for all of

the available steps in module #3, then pressing “P” will cause the unit to

display “Loc”. However, if “YES” was programmed in one or more of the

steps, then “P” will invoke entry into a series of commonly modified

parameters while protecting the crucial set-up information. This is referred to

as the “quick programming” mode. When “quick programming” mode is

entered, the alarms and hysteresis values can be modified in the same manner

as in the regular programming mode. The new alarm and hysteresis values

sign “-” will precede numbers that are negative.

will take effect when “P” is pressed.

OPERATING THE IMY

QUICK PROGRAMMING

Page 22 of the Apollo Ball Valve (IMY) user manual — “SCALE” - “F”
Page 22 · click to enlarge
Page 22

“AN-HI” - “100.0 F”

“AL-1” - “0.0 F”

“HYS-1” - “0.1 F”

“ASN -2” - “INPUt”

“AL-2” - “0.0 F”

“HYS-2” - “0.1 F”

“Pro 7” “bAud” - “1200”

“Pro 8” “ASIN” - “INPUt”

“AN-Lo” - “0.0 F”

“Pro 6” “trAc” - “NO”

The following chart lists the programming of the unit when shipped from the

factory. (In Program Module #9, Code 66 will restore the unit to these values.)

“E1-CON” - “4” (Display Hold)

“E2-CON” - “4” (Display Hold)

“Pro 2” “SLOPE” - “1.0000”

“OFFSEt” - “0.0 F”

“SCLFAC” - “1.000”

“Lo-cut” - “0.0 F”

“Pro 1” “tYPE” - “700”

“dECPNt” - “0.0”

“Pro 3” “dSP AL” - “yES”

“ENt AL” - “yES”

“rSt AL” - “yES”

“SCALE” - “F”

FACTORY CONFIGURATION

“Pro 4” “FILter” - “1”

“Pro 5” “dECPNt” - “0”

Show 18 more labels / short text on this page
“ASN-1” - “INPUt” · “dISP” - “NO” · “LAtC-1” - “NO” · “LAtC-2” - “NO” · “FULL” - “yES” · “Act-1” - “HI” · “Act-2” - “HI” · “AddrES” - “0” · “Print” - “0” · “dSPHYS” - “yES” · “ENtHYS” - “yES” · “dSPbUF” - “yES” · “rStbUF” - “yES” · “SELdSP” - “yES” · “rSttOt” - “yES” · “dSPOFF” - “yES” · “ENtOFF” - “yES” · “tbASE” - “0”
Page 23 of the Apollo Ball Valve (IMY) user manual — PROGRAMMING EXAMPLE
Page 23 · click to enlarge
Page 23

“E1-CON” - Enter 7 (reset alarm #2)

“E2-CON” - Enter 14 (print request)

“Pro 4” “FILter” - Enter 1 (Normal)

“SCLFAC” - Enter 1.000

“AL-2” - Enter 30000

“Lo-cut” - Enter 200

“dISP” - Enter yes

“ASN-1” - Enter input

“LAtC-2” - Enter yes

“ASN -2” - Enter total

“Pro 7” “bAud” - Enter 300

“FULL” - Enter yes

“Pro 8” “ASIN” - Enter input

“AN-HI” - Enter 200

“Pro 6” “trAc” - Enter no

“LAtC-1” - Enter no

“AL-1” - Enter 25

“Act-1” - Enter LO

“Act-2” - Enter HI

“AN-Lo” - Enter 50

“Pro 5” “tbASE” - Enter 1

“HYS-1” - Enter 1

“AddrES” - Enter 0

“Print” - Enter 6

“HYS-2” - N/A

As an example of a programming sequence, the following values, gained from

a temperature-time monitoring application, are programmed into the indicator.

Activate alarm #1 output when temperature falls below 25F, activate

display alarm. Peak and valley (max/min) readings for each cycle to be

TOTALIZERWhen total exceeds 30,000 degree-minutes then latch alarm

#2 which stops the heating process and sounds a process complete bell.

Reset alarm #2 by remote input. Disable totalization when temperature

falls below 200F. Reset the total from the front panel. Allow switching of

SERIALProvide hardcopy printout of total, input and peak/valley when
ANALOG RE-TRANSMISSIONRecord temperature profile. 4 mA at

DISPLAY: Display the actual temperature of a liquid solution in F.

operator actuates print request. Baud rate 300.

“Pro 2” “SLOPE” - Enter 1.0000

the display from/to temperature and total.

“Pro 1” “tYPE” - Enter 400

“Pro 3” “dSP AL” - Enter yes

“ENt AL” - Enter yes

“dSPHYS” - Enter no

“rSt AL” - Enter no

“dSPbUF” - Enter yes

“rStbUF” - Enter yes

“SELdSP” - Enter yes

“rSttOt” - Enter yes

“dSPOFF” - Enter no

“SCALE” - Enter F

“dECPNt” - Enter 0

“OFFSEt” - Enter 0

PROGRAMMING EXAMPLE

50F and 20 mA at 200F.

recorded.

Page 24 of the Apollo Ball Valve (IMY) user manual — TEMPERATURE MONITORING EXAMPLE
Page 24 · click to enlarge
Page 24

An IMY is installed as a monitoring device and back-up

controller for a freezer storage facility. Normally, the

freezer temperature is maintained at about -29C 2. The

absolute maximum allowable temperature of the freezer is

0C. In the event of a system failure, alarm output #1 of the IMY is programmed to start a secondary cooling system

should the temperature reach 0C. The additional alarm of

the IMY is used to signal personnel with a warning bell

when the temperature rises above -17C (indicating a

possible failure of the main cooling system). This alarm is

programmed to latch in order to assure that personnel

inform maintenance of a possible problem. Key switches

are installed to lock out the front panel from unauthorized

personnel and to provide a means of resetting the latched

alarm. The Integrator/totalizer option is specified to store

peak and valley temperatures overnight, weekly, etc.

Programming module #5 (Pro 5) is used to set up the

integrator. The re-transmitted analog output is specified to

drive a chart recorder with 4-20 mA for a hard copy of

TEMPERATURE MONITORING EXAMPLE

temperature profiles for later evaluation.

Page 25 of the Apollo Ball Valve (IMY) user manual — INTEGRATOR/TOTALIZER
Page 25 · click to enlarge
Page 25

valuable in monitoring the limits of the process over any length of time since

these values are stored at power-down to span over shifts, days, etc. An

external input can be programmed to reset or engage the unit into a

peak/valley reading indicator. Additionally, the peak and valley can be

viewed and reset from the front panel, if so programmed, and viewed and reset

If a difference exists between the displayed temperature and a reference

temperature point, the display may be offset for this effect. Similarly, a

correcting “slope” may be programmed, with the offset, to allow for two

For most applications, the slope and offset values are not changed. But if it is

required to scale the display to match a calibrated probe, the following formula

The meter is displaying 52 degrees and 146 degrees (actual temperature)

when the calibrated temperature reference shows that 50 degrees and 150

First determine the new slope value using the sets of temperature points.

slope = 150 - 50 = 100 = 1.0638 146 - 52 94 Next, determine the new offset value by using either one of the temperature

and example show the calculation of appropriate slope and offset values.

Desired Display = (slope x actual temp. display) + offset

slope = difference of two desired temperature points

difference of two actual temperature points

offset = one desired temperature point - (slope x one

corresponding actual temperature point)

degrees respectively should be displayed (desired temperature).

OFFSET AND SLOPE DISPLAY TEMPERATURE

INTEGRATOR / TOTALIZER / PEAK / VALLEY / TEMPERATURE OFFSET (Optional)

from the serial communication option.

pairs. offset = 150 - (146 x 1.0638)

nominal 2 sec. response time.

point temperature correction.

offset = 5.3

Example:

The integrator/totalizer option simply adds input readings together using a

programmable time base and scaling coefficient. The decimal point position

of the integrator/totalizer can be programmed independent of the scaled input

signal. The integrator/totalizer may be reset through a remote input, by the

front panel or through the serial communications option. Alarms may be

programmed to trigger from integrator/totalizer values; for example to total

“degree minutes” for batching operations. The programmable time bases are

“per second”, “per minute” and “per hour”, meaning the integrator/totalizer

will accumulate at a fixed rate of 2 12 times per second and be equal to a fixed

input level over the selected time period. For example, if the input is a

constant 100 and the “per minute” time base is selected, the

integrator/totalizer will accumulate at the rate of 100 per minute. The

totalizer is updated at this rate every 400 msec. As a result, the input is

accumulated in “batches” of 6.6 counts every 400 msec. Therefore, the

totalizer start and stop sequencing, as well as alarm values set for triggering at

specific totalizer values, are only accurate to the 400 msec totalizer update

rate. The preceding example requires a scale factor of 1.000 to yield exact

time bases, but any scale factor can be used to span between the ranges. (See

section on integrator/totalizer programming for detailed information.) A

programmable low temperature level disable feature completes the

integrator/totalizer features (this will stop totalization when the input drops

below this programmed value, “low cut”). At loss of power to the indicator,

the contents of the integrator/totalizer is saved. This will allow

integrating/totalizing of interrupted processes. The total can accumulate to

999,999. If the low-end cut-out value is programmed negative (ex. -100, reference Program Module #5), and the input display value is between zero and

the low-end cut-out value, the totalizer value will decrement. If the input

display value goes above zero the total will increment. If the display value goes

The other features of the integrator/totalizer option are peak and valley

detection. The indicator will record the lowest reading (valley) and the

highest reading (peak), automatically, for later recall. This information is

below (more negative than), the low-end cut-out value, totalization will stop.

INTEGRATOR/TOTALIZER

PEAK/VALLEY

Page 26 of the Apollo Ball Valve (IMY) user manual — BASIC SET-UP
Page 26 · click to enlarge
Page 26

With an average temperature input which gives a display of 110.0 at the

T.B. = If Program Select Number Chosen Is: Enter in Formula

D.T.D.P. = Desired Totalizer Value Decimal Point Enter in Formula

I.D.D.P. = Input Display Value Decimal Point Enter in Formula

This value is normally 1, but can be used as a course scale factor of 60 or

end of an 8 hour time period (one shift), the following formula applies:

0 1 0.0 10 0.00 100 0.000 1000 0.0000 10000

“0” for sec. 1 “1” for min. 60 “2” for hr. 3600

0 1 0.0 10

TIME = Actual Time period in seconds

S.F. = D.T. x ( T.B. ) x D.T.D.P.

I.D. TIME I.D.D.P.

D.T. = Desired Totalizer value for a

S.F. = Programmable Scale Factor

T.B. = Programmable Time Base

I.D. = Input Display Value

INTEGRATOR/TOTALIZER SET-UP

This feature allows the operator to manipulate the displayed temperature

reading. The operator may utilize this feature for example, when switching

thermistor probes, to compensate for differences in thermistor probe

accuracy from one manufacturer to another or to offset the input reading to

The displayed temperature can be offset either positive or negative to the

actual measured temperature. Programming a positive number for the offset

value increases the display value. Programming a negative number for the

offset value decreases the display value. For example, if the displayed

temperature is 10 less than the measured temperature, programming a +10

for the offset value will increase the displayed value by 10 throughout the

entire range. If the displayed temperature is 10 higher than the measured

temperature, programming a -10 for the offset value will decrease the display

The indicator is employed to indicate average daily (8 hour) temperature of

a “Hot Room” used for storing various ingredients at a large food processing

plant. Ingredients which must be kept at temperatures above 100.0F are

stored in this room. The desired constant temperature is 110.0°F. However,

frequent opening and closing of the door causes temperature variations. The

OFFSET AND SLOPE DISPLAY TEMPERATURE (Cont’d)

“Pro 2” “SLOPE” - 1.0638 “OFFSEt” - -5.3

INTEGRATOR/TOTALIZER EXAMPLE

following programming steps are performed:

“Pro 1” “tYPE” - 400

“dECPNt” - 0.0

value by 10 throughout the entire range.

“SCALE” - F

match a “Reference” temperature.

BASIC SET-UP

SET-UP:

fixed time duration

Page 27 of the Apollo Ball Valve (IMY) user manual — S.F. = .125
Page 27 · click to enlarge
Page 27

The integrator/totalizer will accumulate up to 99999.9. At the end of the shift,

the average temperature over the previous 8 hours can be read directly. The

integrator/totalizer can then be reset for the next 8 hour shift. Anytime during the

For example, 6 hours and 37 minutes into the shift the integrator/ totalizer

This value is normally 1, but can be used as a course scale factor of 60 or

Since the time period is in Hrs., the selected T.B. is 3600 (Program select

T.T. = Total Time (From the beginning of the shift)

The average temperature over the last 6 hours and 37 minutes was 109.9°F.

Time is in hours. The number of minutes must be divided by 60 and then

shift, the average temperature can be calculated by the following formula:

Av = 90.9 = 90.9 Av = 109.9 .125 x 6.6166 .827

reads “90.9”. To find the average temperature up to this point:

S.F . = 110 x ( 3600) x 10 110 28800 10 (8 Hours x 3600)

S.F. = Programmable Scale Factor

I.V. = Integrator/Totalizer Value

value = 2) which equals per hour (3600 sec.).

S.F. x T.T.

“SCLFAC” - .125

S.F. = 1x.125

“Pro 5” “dECPNt” - 0.0

“Lo-cut ” - 0.0

S.F. = .125

“tbASE ” - 2

Av = I.V.

added to the hours.

Page 28 of the Apollo Ball Valve (IMY) user manual — ALARMS (Optional)
Page 28 · click to enlarge
Page 28

alarm shuts off the process. When tracking is programmed, changing the

shut-off trip value (Alarm #2) automatically changes Alarm #1 so that the

offset between Alarm #2 and Alarm #1 remains the same. Alarm and

hysteresis values can be modified through the optional serial

communications to provide automatic control. The following diagrams

Programming of the alarms can be accomplished in the normal

programming mode “Pro 6”or the unit can be programmed so that the values

If the display should indicate an “OLOLOL”, “ULULUL”, or “SHort” the

depict how the alarms work with both “HI” and “LO” acting set-ups.

alarms will de-energize, whether they are latched or unlatched.

can only be changed in the “quick programming” mode.

ALARM TIMING DIAGRAMS

The alarm option consists of an additional printed circuit board with nine

terminals. Six of these terminals are the two Form-C relays and the other three

are the two open collector transistors, which act in parallel with the relays.

The two alarms are completely independent with programmable values,

hysteresis (deadband), high or low acting, auto or manual reset, triggering

from input or total, and tracking one another, if desired. If the alarms are

programmed to latch (manual reset), then they will have to be reset either by

the front panel or remote input. The alarms can be made to trigger from the

integrator/totalizer instead of the input, to activate external alarms, control

valves, etc. Additionally, the alarms may be programmed to activate an alarm

Alarm #1 can be made to track Alarm #2 by enabling alarm tracking. This is

useful in alarm set-ups where a pre-warning control activates before a second

display to alert operators of the condition.

ALARMS (Optional)

Page 29 of the Apollo Ball Valve (IMY) user manual — COMMUNICATION FORMAT
Page 29 · click to enlarge
Page 29

Before serial communication can take place, the indicator must be

programmed to the same baud rate as the connected equipment. In addition, the

loop address number, print options and full or abbreviated transmission must

be programmed. If only one indicator is to be used, then a loop address number

of “0” may by used, to eliminate the requirement for the address specifier when

sending a command. If more than one indicator is on the loop, assignment of

unique addresses, other than zero, for each indicator is recommended. Valid

addresses of 0 to 99 may be assigned, but the built-in current source, if used, is

capable of driving up to 7 units. Additional drive capability may be afforded by

an external current source with a higher compliance voltage. Refer to

DATA FORMAT-10 BIT FRAME [300, 600, 1200, 2400 Baud]

programming section “Pro 7” to program the serial option.

20 mA CURRENT LOOP SERIAL COMMUNICATIONS (Optional)

The serial communication option is a half-duplex, two-way, 20 mA loop

that can connect to a variety of printers, computers, terminals and controllers

to suit many data-polling or automatic operation applications. The indicator

responds to a host of commands, including change alarm value, reset totalizer

and transmit input value. Two loops are required for all hook-ups; a transmit

(out-going data) loop and a receive (in-coming data) loop. Since the indicator

monitors the receive loop for a busy signal (current interrupted) while

transmitting, the receive loop must be connected even if the indicator is

transmitting only, such as to a printer. A built-in 20 mA source can be used in

the transmit loop (only) by connecting the current return wire to -20 mA

SRC., instead of SO+. To bypass the built-in current source, make transmit

loop connections to SO+ and SO-. Additionally, multiple units and other Red

Lion Controls instruments can be serially addressed, up to a maximum of 99

units. (The actual number in a single loop is limited by the serial hardware

specifications.) To eliminate problems with ground loops, the serial circuitry

is isolated from both signal common and output common. Optional 20 mA to

RS232C and 20 mA to RS422 converter modules expand the unit’s flexibility.

Data is sent by switching current on and off in the loop and is received by

monitoring the switching action and interpreting the codes that are

transmitted. In order for data to be correctly interpreted, there must be

identical formats and baud rates among the communicating equipment. The

only format available with this indicator is 1 start bit, 7 data bits, 1 odd parity

bit and 1 stop bit. The baud rates are programmable and the choices are: 300,

must have current flowing into it before transmission can take place.

COMMUNICATION FORMAT

GENERAL DESCRIPTION

600, 1200 and 2400.

Page 30 of the Apollo Ball Valve (IMY) user manual — COMMAND FUNCTIONS
Page 30 · click to enlarge
Page 30

The command string is constructed in a specific logical sequence. The

indicator will reject command strings that do not conform. Only one

operation can be performed per command string. Below is a description of

1. If the indicator has an address other than zero, the first two characters of the string must consist of the address command (N) followed by the unit

address number (0-99). If the indicator has an address of 0, the address

2. The next two characters in the string are the actual command the indicator must perform and the identifier on which it operates. Command P-print,

Value I-zero offset and J-offset input, have implied operators and need no

3. If the change value command is being used (V) , the next characters in the string after the value identifier, are the numerical data. When sending

numerical data, such as change an alarm value, the correct number of digits

to the right, must be included. As an example, to change an alarm value

from 150.2 to 50.0. Sending 50 would cause the indicator to see 5.0 and

4. All commands must be terminated by an asterisk (*) . The indicator will not respond to any other code. Carriage return and line feed are not valid

terminators and should be suppressed with the character “;”, if using a

Indicator with address 3, transmit temperature reading.

Indicator with address 0, change alarm #1 to 150.

Indicator with address 99, print the print options.

BASIC print statement (ex. Print “N9TA*”;).

Indicator with address 0, zero the offset value.

Indicator with address 1, reset totalizer.

COMMAND STRING EXAMPLES

change the alarm value accordingly.

how to construct a command string.

N3TA*

VC150*

N1RB*

N99P*

RI*

command is optional.

additional characters.

When sending commands to the unit a command string must be

constructed. The command string may consist of command codes, value

identifiers, and numerical data. Below is a table outlining the codes the

“RJ”) the amount is stored in the offset reading (I). Ex. When an offset is

performed, the display reads “5.0”, the offset value will be “-00005.0” (and

A command string is constructed by using the above commands and

identifiers along with any data values that are required. The indicator will

accept “+” or “-” in front of the data value. Numbers without “+” are

understood to be positive. Leading zeros can be eliminated and both lower

and upper case characters are accepted. The address command is used to

allow a command to be directed to a specific unit on the loop. If the indicator

is assigned an address of “0”, transmission of the address command is not

R reset a value specified by the identifier (B-D, G, H, I, and J)

V change a value specified by the identifier (C-F, K, and L)

N address a particular indicator in a multiple unit loop (0-99)

T transmits the requested information specified by the

VALUE IDENTIFIERS SERIAL MNEMONICS

required. This is done where only one indicator is in the loop.

C alarm #1 AL1

D alarm #2 AL2

E hysteresis #1 HS1

F hysteresis #2 HS2

G peak reading PEK

H valley reading VAL

I zero offset OFS

K analog low ANL

L analog high ANH

P print per programmable print options (A-I)

COMMAND FUNCTIONS

SENDING COMMANDS TO THE IMY

identifier (A-I, K, and L)

the display will show 0.0).

indicator will recognize.

A temperature INP · B integrator/totalizer TOT · J offset input

Page 31 of the Apollo Ball Valve (IMY) user manual — Sending Commands to the IMY 28
Page 31 · click to enlarge
Page 31

the time of transmission, the IM may take as long as 2 seconds to respond.

If illegal commands or characters are sent to the IM, an asterisk (*) must be

sent to clear the input buffer. The IM will not respond to an illegal or

incomplete transmission. The diagrams show the difference in the timing

considerations for either Abbreviated or Full Character Transmission, or if a

Reset Command is issued.

Show 7 more labels / short text on this page
(Full Transmission Selected) · of Transmission Selected · Independent of Type · Timing Diagrams · Reset Command · (Abbreviated Transmission Selected) · Timing Diagrams
Page 32 of the Apollo Ball Valve (IMY) user manual — RECEIVING DATA FROM THE IMY
Page 32 · click to enlarge
Page 32

When wiring the 20 mA current loop, remove the bottom terminal block

(TBA), located on the rear of the unit. Refer to the numbers listed with the

terminal descriptions below or those located on the label. It is recommended

that shielded (screened) cable be used for serial communications. This unit

meets the EMC specifications using Alpha #2404 cable or equivalent. There

are higher grades of shielded cable, such as four conductor twisted pair, that

offer an even higher degree of noise immunity. Install each wire in its proper

location on the terminal block. When all connections are made, replace the

8. PRINT REQ. - The Print Request terminal is pulled low to activate the unit to transmit data according to the print function selected in Program Module

#7 (Reference Programming Module #7 for more details). In order for a

print request function to occur, E1-CON (TBA #4) or E2-CON (TBA #8)

must be programmed for print request. Note: In order to guarantee a

print-out, the programmed E-CON pin must be held low for at least 20

9. -20 mA SRC. - 20 mA current source return path for the transmit loop. Current flows into this pin.
10. SI+ (Serial In+) - 11. SI- (Serial In-) - The unit receives commands on the SI terminals. They are connected in
12. SO+/+20 mA SRC. (Serial Out+) - 20 mA current source for the transmit loop (internally connected).
13. SO- (Serial Out-) - The unit transmits the requested data on the SO terminals. They are

flowing) in order for the unit to respond to a Print Request terminal activation.

series with the transmit or output terminals of the device to be connected.

-125.7 < CR> < LF > abbreviated transmission

connected in series to the receive input of the device to be connected.

msec. If this time exceeds 800 msec, a second print-out may occur.

2 INP -125.7F < CR> < LF > full transmission

Examples of transmissions are as follows:

SERIAL TERMINAL DESCRIPTIONS

CURRENT LOOP INSTALLATION

terminal block into its proper location.

WIRING CONNECTIONS

Data is transmitted from the indicator whenever a “T” or “P” command is

received via serial communications or a remote input, E1-CON or optional

E2-CON pin is programmed for print request, is activated. If the abbreviated

transmission was programmed, just data will be transmitted with no built-in

delay. (If full transmission is programmed, then there is a 400 msec min to

The first two characters transmitted are the unit address number, unless it is

zero, in which case it is left blank. Then two blank spaces are sent. The next

three characters are the abbreviation for the value (mnemonics), which is then

followed by a blank. The actual data is transmitted next. The field is right

justified with leading zeros. Negative numbers are indicated by a minus sign

fixed next to the identifier. A carriage return and a line feed are transmitted

next. For various reasons, “extra” characters are added onto the end of the

above character string. (These characters could be and are used for control or

For a “T” command or after each “line of a block” transmission, no

additional characters are sent. If the abbreviated transmission is selected, the

address, mnemonics, and any blank spaces (first eight characters) are not

If the transmitted data is overrunning the peripheral’s buffer, the receive

channel to the indicator may be used for handshaking purposes. As a

consequence of this, even if the indicator is to transmit only (ex. to a printer),

< SP>< CR>< LF> sent after “last line of a block” transmission from IM.

current must be flowing in the receive channel to allow transmission.

transmitted (the data strings are left justified in this case).

< CR> sent after single line transmissions from IM unit.

800 msec max delay built-in to the string.) A data string transmission is shown below.

RECEIVING DATA FROM THE IMY

signaling purposes.) These characters are:

Page 33 of the Apollo Ball Valve (IMY) user manual — SERIAL COMMUNICATIONS EXAMPLES
Page 33 · click to enlarge
Page 33

The drawing shows the indicator with the 20 mA Serial Communication

Option set-up with an RLC Model DMPC printer. An external current source

is required to implement the printer’s busy signal to the indicator’s receive

loop, which prevents overruns. The “Print switch” is a momentary contact,

push button type connected between the E2-CON (TBA #8) and the signal

common (TBA #7). The print function and E2-CON must be pro- grammed

and the baud rate must match those of the printer. If a printer is used which

does not have a ‘busy’ line, current must still be flowing into the indicator’s

SERIAL COMMUNICATIONS EXAMPLES

CONNECTING TO AN RLC PRINTER

receive loop before transmission can occur.

Page 34 of the Apollo Ball Valve (IMY) user manual — PROCESS CONTROLLING SYSTEM
Page 34 · click to enlarge
Page 34

An application program is written, which sends and

are connected internally. Therefore it is not necessary

to have this terminal tied to any other terminal on the

unit if that unit is serving as the loop supply source.

retrieves data from the IMYs.

Six Model IMYs with Serial Communication Option

are used to monitor and control the temperature of 6

ovens at a large bakery. The IMYs are located at each of

the ovens in the production area of the building. The

communications lines are run to an industrial computer

The drawing below shows the Current Loop set-up.

Each IMY is given an address and programmed

accordingly (Program Module #7). A baud rate of 1200

PROCESS CONTROLLING SYSTEM

located in the production offices.

is selected.

Page 35 of the Apollo Ball Valve (IMY) user manual — RE-TRANSMITTED ANALOG OUTPUT (Optional)
Page 35 · click to enlarge
Page 35

by calculating the slope and intercept of the display/output and calculating

the required display values at 4 mA or 0 VDC and 20 mA or 10 VDC. Reverse

action can be achieved by programming a “high” display value for “AN-Lo”

If the display should indicate an “OLOLOL”, “ULULUL”, or “SHort” the

analog output will go to 20 mA or 10 VDC for an “OLOLOL” or “SHort”, and

and a “low” display value for “AN-HI”.

4 mA or 0 VDC for a “ULULUL”.

ANALOG OUTPUT DIAGRAMS

The re-transmitted analog output option transmits a digitally

programmable 4 to 20 mA or 0 to 10 VDC signal to drive chart recorders,

remote indicators and controllers. The option is contained on the upper PCB

and has two outputs, “ANALOG-” (TBB #10) and “ANALOG+” (TBB #11)

and is self-powered (active) with a compliance of 10 VDC. The analog “-”

output is isolated from the input common, eliminating problems from ground

loops. Programming of the option is performed in “Pro 8” of the normal

programming mode. Display values are simply keyed in to provide a 4 mA or

0 VDC output, “AN-Lo”, and a 20 mA or 10 VDC output, “AN-HI”. The analog output then follows the assigned value and as such will update every

measurement cycle. Nonstandard current or voltage ranges can be supported

RE-TRANSMITTED ANALOG OUTPUT (Optional)

Page 36 of the Apollo Ball Valve (IMY) user manual — ANALOG OUTPUT CALIBRATION
Page 36 · click to enlarge
Page 36

Although the analog output has been calibrated at the factory, zero and

span adjustments are provided to compensate for small offsets and drifts. If

excessive drift is noticed, the following calibration procedure may be

Scale the analog output by entering an arbitrarily larger display value for

4 to 20 mA Calibration Exit the programming mode and apply a (temperature)/(resistance) to the

input of the indicator so that the display reading is below that of the value

entered for “AN-LO”. Adjust the zero potentiometer (right side) so that

exactly 4.00 mA flows, as verified by an accurate ammeter. Next, apply a

(temperature)/ (resistance) to the indicator so that the display reading is

above that of the value entered for “AN-HI”. (See Appendix “B” for max.

input voltage.) Adjust the span potentiometer (left side) so that 20.00 mA is

flowing. Repeat the zero and span adjustments until both are accurate. Analog

0 to 10 VDC Calibration Exit the programming mode and apply a (temperature)/(resistance) to the

input of the indicator so that the display reading is below that of the value

entered for “AN-LO”. Adjust the zero potentiometer (right side) so that exactly

0.00 VDC flows, as verified by an accurate voltmeter. Next, apply a (temperature)/ (resistance) to the input of the indicator so that the display

reading is above that of the value entered for “AN-HI”. (See Appendix “B” for

max. input voltage.) Adjust the span potentiometer (left side) so that 10.00

VDC is flowing. Repeat the zero and span adjustments until both are accurate.

ANALOG OUTPUT CALIBRATION

“AN-HI” then for “AN-LO”, in “PRO 8”.

Analog output calibration is complete.

output calibration is complete.

performed.

Page 37 of the Apollo Ball Valve (IMY) user manual — SELECT AC POWER (115/230 VAC)
Page 37 · click to enlarge
Page 37

Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate

Before installing the IM into the panel, the user should first become familiar

with the unit. It may also be desirable to program the unit for the application.

When programming is complete, all parameters will be saved in non-volatile

memory. The Program Disable (PGM.DIS.) terminal should be connected to

PANEL INSTALLATION The unit meets NEMA 4/IP65 requirements for indoor use, when properly

installed. The units are intended to be mounted into an enclosed panel with a

gasket to provide a water-tight seal. Two mounting clips and screws are

provided for easy installation. Consideration should be given to the thickness

of the panel. A panel which is too thin may distort and not provide a

After the panel cut-out has been completed and deburred, carefully slide

the gasket over the rear of the unit to the back of the bezel. Insert the unit into

appropriate position before applying power to the unit.

Damage to the unit may occur if the AC selector switch is set

COMM. to prevent accidental or unauthorized programming changes.

water-tight seal. Recommended minimum panel thickness is 1/8".)

the panel. As depicted in the drawing,

install the screws into the narrow end of

the mounting clips. Thread the screws

into the clips until the pointed end just

protrudes through the other side. Install

each of the mounting clips by inserting

the wide lip of the clips into the wide end

of the hole, located on either side of the

case. Then snap the clip onto the case.

Tighten the screws evenly to apply

uniform compression, thus providing a

incorrectly.

the keypad of the unit.

overtighten screws.

water-tight seal.

APPENDIX “A” - INSTALLATION & CONNECTIONS

The unit should be installed in a location that does not exceed the maximum

operating temperature and provides good air circulation. Placing the unit near

The bezel should be cleaned only with a soft cloth and neutral soap product.

Do NOT use solvents. Continuous exposure to direct sunlight may accelerate

The AC power to the unit must be selected for either 115 VAC or 230 VAC.

The selector switch is located through an access slot on the side of the case

(See figure above or label on case). The unit is shipped from the factory with

devices that generate excessive heat should be avoided.

SELECT AC POWER (115/230 VAC)

INSTALLATION ENVIRONMENT

the switch in the 230 VAC position.

the aging process of the bezel.

Page 38 of the Apollo Ball Valve (IMY) user manual — EMC INSTALLATION GUIDELINES
Page 38 · click to enlarge
Page 38
5. In extremely high EMI environments, the use of external EMI suppression devices, such as ferrite suppression cores, is effective. Install them on

Signal and Control cables as close to the unit as possible. Loop the cable

through the core several times or use multiple cores on each cable for

additional protection. Install line filters on the power input cable to the unit

to suppress power line interference. Install them near the power entry point

of the enclosure. The following EMI suppression devices (or equivalent)

6. Long cable runs are more susceptible to EMI pickup than short cable runs. Therefore, keep cable runs as short as possible.
7. Switching of inductive loads produces high EMI. Use of snubbers across inductive loads suppresses EMI.

Ferrite Suppression Cores for signal and control cables:

Fair-Rite # 0443167251 (RLC #FCOR0000)

Schaffner # FN610-1/07 (RLC #LFIL0000)

Line Filters for input power cables:

TDK # ZCAT3035-1330A

Schaffner # FN670-1.8/07

RLC #SNUB0000

are recommended:

Snubbers:

Although this unit is designed with a high degree of immunity to

ElectroMagnetic Interference (EMI), proper installation and wiring methods

must be followed to ensure compatibility in each application. The type of

electrical noise, source or coupling method into the unit may be different for

various installations. In extremely high EMI environments, additional

measures may be needed. The unit becomes more immune to EMI with fewer

I/O connections. Cable length, routing and shield termination are very

installation. Listed below are some EMC guidelines for successful

1. The unit should be mounted in a metal enclosure, which is properly connected to protective earth.

a. If the bezel is exposed to high Electro-Static Discharge (ESD) levels,

above 4 Kv, it should be connected to protective earth. This can be done

by making sure the metal bezel makes proper contact to the panel cut-out

or connecting the bezel screw with a spade terminal and wire to

2. Use shielded (screened) cables for all Signal and Control inputs. The shield (screen) pigtail connection should be made as short as possible. The

connection point for the shield depends somewhat upon the application.

Listed below are the recommended methods of connecting the shield, in

a. Connect the shield only at the panel where the unit is mounted to earth

b. Connect the shield to earth ground at both ends of the cable, usually

c. Connect the shield to common of the unit and leave the other end of the

3. Never run Signal or Control cables in the same conduit or raceway with AC power lines, conductors feeding motors, solenoids, SCR controls, and

heaters, etc. The cables should be run in metal conduit that is properly

grounded. This is especially useful in applications where cable runs are

long and portable two-way radios are used in close proximity or if the

4. Signal or Control cables within an enclosure should be routed as far away as possible from contactors, control relays, transformers, and other noisy

shield unconnected and insulated from earth ground.

when the noise source frequency is above 1 MHz.

installation is near a commercial radio transmitter.

EMC INSTALLATION GUIDELINES

installation in an industrial environment.

order of their effectiveness.

ground (protective earth).

protective earth.

components.

Steward #28B2029-0A0 · Corcom #1VR3

Page 39 of the Apollo Ball Valve (IMY) user manual — WIRING CONNECTIONS
Page 39 · click to enlarge
Page 39

The 700 Series Thermolinear thermistor is a 3-wire sensor. One lead

connects to TBA #6 (T1) and the common lead connects to TBA #7 (comm).

Always refer to the sensor manufacturer’s instructions for probe wiring

User inputs (PGM.DIS., E1-CON, and optional E2-CON) are digital inputs

that are active when connected to TBA #5 Common. Any form of mechanical

switch, sinking collector logic with less than 0.7 V saturation may be used.

The use of shielded cable is recommended. Follow the EMC Installation

To prolong contact life and suppress electrical noise interference due to the

switching of inductive loads, it is good installation practice to install a

snubber across the contactor. Follow the manufacturer’s instructions for

The third wire is an additional thermistor lead and connects to TBA #5 (T2).

A.C. Powered Basic Connection

Guidelines for shield connection.

connections, if available.

USER INPUT WIRING

devices to be held ON.

OUTPUT WIRING

installation.

After the unit has been mechanically mounted, it is ready to be wired. All

conductors should meet voltage and current ratings for each terminal. Also

cabling should conform to approriate standards of good installation, local

codes, and regulations. It is recommended that power supplied to the unit be

protected by a fuse or circuit breaker. All wiring connections are made on

removable plug-in terminal blocks. There is a separate terminal block for the

bottom board (TBA) and optional top board (TBB). When wiring the unit,

remove the terminal block and use the numbers on the label to identify the

position number with the proper function. Strip the wire, leaving approx. 1/4"

bare wire exposed (stranded wires should be tinned with solder). Insert the

wire into the terminal and tighten down the screw until the wire is clamped

tightly. Each terminal can accept up to one 14-gauge, two 18-gauge or four

20-gauge wire(s). After the terminal block is wired, install it into proper location on the PC board. Wire each terminal block in this manner.

Primary AC power is connected to terminal 1 and 2 (marked VAC 50/60 Hz,

located on the left hand side of the bottom terminal block). To reduce the

chance of noise spikes entering the AC line and affecting the indicator, the

AC power should be relatively “clean” and within the specified 10%

variation limit. Drawing power from heavily loaded circuits or circuits which

also power loads that cycle on and off, (contactors, relays, motors,

Meter signal input common is not isolated from PGM. DIS.,

E1-CON, E2-CON; maximum allowable 50 V can be present in

Thermistors provide a higher degree of accuracy, stability, and resolution

over other temperature sensing elements, such as platinum RTDs or

The IMY supports two popular types of thermistors; the 400 Series (YSI

44000) 2,252 thermistor, and the 700 Series “Thermolinear” thermistor. Selection of the two types is done in Programming Module #1.

The 400 Series thermistor is a 2-wire sensor. One lead connects to TBA #6

(T1) and the other lead connects to TBA #7 (comm).

the circuit that is being measured.

SIGNAL WIRING (THERMISTOR)

machinery, etc.) should be avoided.

WIRING CONNECTIONS

POWER WIRING

thermocouples.

Relay Connections

Page 40 of the Apollo Ball Valve (IMY) user manual — APPENDIX “B” - SPECIFICATIONS AND DIMENSIONS
Page 40 · click to enlarge
Page 40
6. RANGE: 400 Series -40.0 to C (-40.0 to 257 F 700 Series -30.0 to 100.0 C (-22.0 to 212 F). 7. RESOLUTION: 0.1 or 1 degree. 8. ACCURACY: 0.2 C (0.36 F) 12 LSD, @ 23 C and 10 min. warm-up. 9. READING RATE: 2.5 readings/second 10. RESPONSE TIME: 2 seconds to settle for step input (increases with programmable digital filtering)
11. NORMAL MODE REJECTION: 40 dB at 50/60 Hz (may be improved by programmable digital filtering)
12. COMMON MODE REJECTION: 120 dB, DC to 50/60 Hz 13. INTEGRATOR/TOTALIZER: Front panel button for input/total display select. External integrator/totalizer reset/enable. Programmable

time-base, scale factor (0.001-999.999) and low-temp cut-out. Maximum

14. E1-CON & E2-CON: External remote inputs which allow activation of various functions. (Reset total, peak indicator mode, trigger mode, etc.)

VIL = 0.8 VMAX; VIH = 2.0 VMIN; Response Time = 0.2 sec. Maximum.

PANEL CUT-OUT

response time 0.2 sec.

APPENDIX “B” - SPECIFICATIONS AND DIMENSIONS

1. DISPLAY: 4-digit with F/C indication, 0.56" (14.2 mm) high LED, minus sign displayed for negative temperatures. 6-digits for integrator/ totalizer.

“Flashing” display for totalizer overflow. “ULULUL” displayed for input

2. POWER REQUIREMENTS: Switch selectable 115/230 VAC, 10%, 50/60 Hz, 14 VA. Isolation: 2300 Vrms for 1 min. To all inputs and outputs.
3. CONTROLS: Three front panel push buttons for modifying alarm values and indicator set-up. Two external inputs for disabling the front panel and
4. SIGNAL INPUT: 2-Wire, 400 Series 2,252 ohm Thermistor; or 3-wire, 700 Series Thermolinear thermistor. Max. Input Signal Voltage : 15 VDC.

overload and “OLOLOL” displayed for underload (negative overload).

Input Common potential with respect to earth Common: 50 V max., CAT I

Working Voltage300 V max., CAT II

Setpoint Outputs - Disabled (Deactivated)

Serial Output - “ULULUL” in data field

5. OPEN THERMISTOR DETECTION: Display - “ULULUL”

controlling programmable functions.

DIMENSIONS In inches (mm)

Analog Output - 4 mA

Integration/Totalization - Disabled

Page 41 of the Apollo Ball Valve (IMY) user manual — APPENDIX fiBfl - SPECIFICATIONS AND DIMENSIONS 38
Page 41 · click to enlarge
Page 41
Max. Rating5 Amps @ 120/240 VAC or 28 VDC (resistive load) , 1/8
Relay Life Expectancy100,000 cycles at max. rating. (As load level
19. PEAK/VALLEY/SLOPE/OFFSET (Optional): Peak and Valley recording. Programmable temperature offset and slope.
18. ANALOG OUTPUT (Optional): Digital scaling and offsetting Isolation To Signal Input Common: 500 Vrms for 1 min.
Compliance Voltage10 VDC (500 max. loop resistance)

Isolation To Signal Input Common: 2300 Vrms for 1 min.

Working Voltage300 V max., CAT II
Working Voltage50 V max., CAT I
Min. Load Resistance10 K (1 mA max.)

decreases, life expectancy increases.)

0 to 10 VDCAccuracy: ±(0.1% of reading + 35 mV)

hp @ 120 VAC (inductive load).

Not isolated from all other commons.

4 to 20 mAAccuracy: 0.1% of full scale
Resolution12 bits
Resolution12 bits
TypeForm C (2)

Relays:

TypeBi-directional 20 mA current loop, 20 mA source provided on

transmit loop. (Powers up to 7 units in a loop with internal current

Maximum address99 (Actual number in a single loop is limited by serial
Data Format10 bit frame, Odd parity (one start bit, 7 data bits, one odd

than the sum of the voltage drops around the loop. (Typically a 30

VDC powered source would be capable of operating between 18

17. ALARMS (Optional): Solid State: Two, isolated, sinking open collector NPN transistors acting in

SO - Output Transistor Rating: Vmax = 30 VDC, VSAT = 1Vmax at 20 mA.

parallel with relays. Imax: 100 mA. VSAT = 1.0 V @ 100 mA. Vmax: 30 VDC.

Operating and Storage Humidity85% max. relative humidity
16. SERIAL COMMUNICATIONS (Optional): Isolation To Signal Input Common : 500 Vrms for 1 min.

Isolation To Signal Input Common: 500 Vrms for 1 min.

Working Voltage50 V max., CAT I
Working Voltage50 V max., CAT I
SI - Input Diode RatingV F = 1.25 V TYP ; 1.5 V MAX
15. ENVIRONMENTAL CONDITIONS : Operating Temperature Range: 0 to 50°C
Storage Temperature Range-40 to 80°C

Not isolated from all other commons.

Baud Rateprogrammable 300 to 2400

Not isolated from all other commons.

(non-condensing) from 0°C to 50°C.

Serial Hardware Specifications:

parity bit, and one stop bit.)

and 22 units in a loop.)

AltitudeUp to 2000 meters

hardware specifications.)

source).

Page 42 of the Apollo Ball Valve (IMY) user manual — ELECTROMAGNETIC COMPATIBILITY
Page 42 · click to enlarge
Page 42
IEC 1010-1, EN 61010-1Safety requirements for electrical equipment for
1. Metal bezel of unit connected with ground lead from rear bezel screw to metal mounting panel.

I/O and power cables are routed in metal conduit connected to earth ground.

21. CONSTRUCTION: Die-cast metal front bezel that meets NEMA 4/IP65 requirements for wash-down and/or dusty environments when properly

installed. Pollution Degree 2. Case body is black, high impact plastic

Electrostatic discharge EN 61000-4-2 Level 2; 4 Kv contact 1

2. Self-recoverable loss of performance during EMI disturbance at 10 V/m: Process input and/or analog output signal may vary during EMI disturbance.

Unit is mounted in a metal enclosure (Buckeye SM7013-0 or equivalent)

Power mains class A

Level 3; 2 Kv power

150 KHz - 80 MHz Emissions to EN 50081-2

Electromagnetic RF fields EN 61000-4-3 Level 3; 10 V/m 2

80 MHz - 1 GHz Fast transients (burst) EN 61000-4-4 Level 4; 2 Kv I/O

RF conducted interference EN 61000-4-6 Level 3; 10 V/rms

RF interference EN 55011 Enclosure class A

Refer to the EMC Installation Guidelines for additional information.

Level 3; 8 Kv air

measurement, control and laboratory use, Part 1.

20. CERTIFICATIONS AND COMPLIANCES: SAFETY

22. CONNECTION: Removable terminal blocks 23. WEIGHT: 1.2 lbs. (0.54 kg)

ELECTROMAGNETIC COMPATIBILITY

IP65 Enclosure rating (Face only), IEC 529

Type 4 Enclosure rating (Face only), UL50

(panel gasket and mounting clips included).

For operation without loss of performance:

Immunity to EN 50082-2

Page 43 of the Apollo Ball Valve (IMY) user manual — APPENDIX “C” - TROUBLESHOOTING GUIDE
Page 43 · click to enlarge
Page 43

The majority of all problems with the indicator can be traced to improper

connections or improper programming set-ups. Be sure all connections are clean and

tight and check the programming set-ups for correct data. For further technical

assistance, contact technical support at the appropriate company numbers listed.

2. Dampen process to eliminate oscillations.

1a. Increase digital filtering. b. Increase display rounding increment.

“PPPPPP” IN DISPLAY 1. Program data error. 1. Press “P” and Check data set-ups.

“ ” IN DISPLAY 1. Loss of data set-ups. 1a. Check data set-ups. b. Check for electrical disturbance.

c. Disconnect and reconnect power.

DISPLAY WANDERS 1. Loss of data set-ups. 1a. Check data set-ups. b. Disconnect and reconnect power.

c. Check for electrical disturbance.

1. Connect probe. 2. Repair or obtain new probe. 3. Reduce temperature. 4. Check input levels.

c. Re-route signal wires.

“OLOLOL” IN DISPLAY 1. Input Underload (negative overload). 1. Check input levels.

NO DISPLAY 1. Power off, improperly connected, or brown-out. 1a. Check wiring. b. Verify power.

FLASHING DISPLAY 1. Totalizer overflow. 1. Reset totalizer.

“SHort” IN DISPLAY 1. Shorted probe. 1. Check probe.

PROBLEM POSSIBLE CAUSE REMEDIES

JITTERY DISPLAY 1. Electrical “Noise” in process or signal lines.

“ULULUL” IN DISPLAY 1. Probe unconnected 2. Broken or burnout probe. 3. Excessive probe temperature. 4. Input overload.

2. Process inherently unstable.

APPENDIX “C” - TROUBLESHOOTING GUIDE

Page 44 of the Apollo Ball Valve (IMY) user manual — PANEL LOCKOUT ENGAGED
Page 44 · click to enlarge
Page 44

This sequence may be subject to being locked-out due to other programmed

11. offset input to zero and totalizer the offset values

“Pro 4” - PROGRAM DIGITAL FILTERING AND REMOTE

13. instrument reading with synchronization
10. toggle display between input and total
7. reset valley and start valley indicator
6. reset peak and start peak indicator

“E1-CON” - Enter function of remote input

“FILter” - Enter level of digital filtering

“E2-CON” - same functions as E1-CON

2. reset and gate totalizer
12. display hold with tare
0. offset input to zero
8. reset latched alarms
0. no digital filtering
2. increased filtering
3. maximum filtering
5. reset peak/valley
9. reset all alarms
1. normal filtering

INPUT FUNCTION

3. gate totalizer
4. display hold
14. print request
1. reset total

sequences.

APPENDIX “D” - PROGRAMMABLE FUNCTIONS

Programming of the indicator is divided into modular steps. Each module is a

short sequence of data entries. The front panel buttons “UP” and “DOWN”

(shown as “arrows” on the front panel) are used to change the data and set-ups,

while the “P” button is used to save or enter the data. After pressing “P”,

which gains entry into the programming mode, the programming modules are

identified by the message “Pro” and a number in the display. “UP” and

“DOWN” are used to select the desired programming module and “P” is used

to enter it. All of the subsequent programming steps follow the same procedure.

The rear terminal labeled “PGM. DIS.” must be ungrounded to gain access to

“Pro 1” - PROGRAM THERMISTOR TYPE, TEMPERATURE SCALE

“Pro 3” - PROGRAM FUNCTIONS ACCESSIBLE WITH FRONT

“Pro 2” - PROGRAM TEMPERATURE SLOPE AND OFFSET

“SELdSP” - Enable switching display between input and total

programming. The following table lists the programming steps.

“SLOPE” - Enter display slope (0.0001 to 9.9999)

“dSPbUF” - Enable display of peak/valley readings

“rStbUF” - Enable reset of peak/valley readings

“Pro 0” - RETURN TO MEASUREMENT MODE

“tYPE” - Select thermistor type (400/700)

AND DECIMAL POINT POSITON

“SCALE” - Enter either degree (F or C)

“rSt AL” - Enable reset latched alarms

“dECPNt” - Enter resolution (0 or 0.0)

“OFFSEt” - Enter offset (-999 to 9999)

PANEL LOCKOUT ENGAGED

“dSPHYS” - Enable display hysteresis

“ENtHYS” - Enable enter hysteresis

“dSPOFF” - Enable display offset value

“ENtOFF” - Enable enter offset value

“dSP AL” - Enable display alarms

“ENt AL” - Enable enter alarms

“rSttOt” - Enable reset total

Page 45 of the Apollo Ball Valve (IMY) user manual — APPENDIX “D” - PROGRAMMABLE FUNCTIONS (Cont’d)
Page 45 · click to enlarge
Page 45
9. temp., total, peak/valley, alarms, hysteresis, and offset

“Print” - Enter print function, or “P” command function through

“Pro 8” - PROGRAM RE-TRANSMITTED ANALOG OUTPUT

“Pro 9” - SERVICE OPERATIONS (Protected by access codes)

3. temp, peak/valley, alarms, hysteresis, and offset

“ASIN” - Select source of analog output (input or total)

“Code 66” - Reset programming to factory configuration

“FULL” - Enable complete or abbreviated printing

“Pro 7” - PROGRAM SERIAL COMMUNICATIONS

“AN-HI” - Enter 20 mA or 10 VDC display value

6. temp., total, peak/valley, and offset

“AN-Lo” - Enter 4 mA or 0 VDC display value

“AddrES” - Enter loop address number (0-99)

“Code 39” - Serial hardware (loop-back) test

1. temp., peak/valley, and offset
8. temp., total and alarms

“Code 48” - Basic input calibration

2. temp. and alarms
7. total and alarms

“bAud” - Enter baud rate

5. temp. and total
0. temp.
4. total

APPENDIX “D” - PROGRAMMABLE FUNCTIONS (Cont’d)

“ASN-1” - Enter alarm #1 trigger source ( temp. or integrator/ total)

“ASN-2” - Enter alarm #2 trigger source ( temp. or integrator/ total)

“Pro 5” - PROGRAM INTEGRATOR/TOTALIZER

“dISP” - Enable display alarm annunciators

“HYS-1” - Enter hysteresis value for alarm #1

“Act-1” - Enter alarm #1 action (high or low)

“HYS-2” - Enter hysteresis value for alarm #2

“Act-2” - Enter alarm #2 action (high or low)

“dECPNt” - Enter decimal point for totalizer

“SCLFAC” - Enter multiplying scale factor

“trAc” - Enable alarm value tracking

“LAtC-1” - Enable alarm #1 latching

“LAtC-2” - Enable alarm #2 latching

“Lo-cut” - Enter low-signal cut out

“AL-1” - Enter alarm #1 value

“AL-2” - Enter alarm #2 value

“tbASE” - Enter time base

“Pro 6” - PROGRAM ALARMS

0. second
1. minute
2. hour

Serial Option

Page 46 of the Apollo Ball Valve (IMY) user manual — OUTPUT ANALOG
Page 46 · click to enlarge
Page 46

PART NUMBERS FOR AVAILABLE

SUPPLY VOLTAGES

115/230 VAC

NO NO NO NO IMY00160

NO YES NO NO IMY00162

YES NO NO NO IMY02160

YES NO YES NO IMY02161

YES YES NO NO IMY02162

YES NO NO 4 to 20 mA IMY02163

YES YES YES 4 to 20 mA IMY02167

YES YES YES 0 to 10 VDC IMY02169

For information on Pricing, Enclosures & Panel Mount Kits refer to the RLC Catalog or contact your local RLC distributor.

OUTPUT ANALOG

OUTPUT

OUTPUT SERIAL

ALARM

APPENDIX “E” - ORDERING INFORMATION

PEAK/VALLEY

SLOPE/OFFSET

TOTALIZER/

E2-CON

MODEL NO. DESCRIPTION

for Thermistor Inputs · IMY Intelligent Meter

Page 47 of the Apollo Ball Valve (IMY) user manual — LIMITED WARRANTY
Page 47 · click to enlarge
Page 47

LIMITED WARRANTY

The Company warrants the products it manufactures against defects in materials and work- manship for a period limited to one year from the date of shipment, provided the products have been stored, handled, installed, and used under proper conditions. The Company’s liability under this limited warranty shall extend only to the repair or replacement of a defective product, at The Company’s option. The Company disclaims all liability for any affirmation, promise or repre- sentation with respect to the products.

The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or prod- ucts containing components manufactured by RLC and based upon personal injuries, deaths, property damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be to any extent liable, including without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty Act (P.L. 93-637), as now in effect or as amended hereafter.

No warranties expressed or implied are created with respect to The Company’s products except those expressly contained herein. The Customer acknowledges the disclaimers and limi- tations contained and relies on no other warranties or affirmations.

Page 48 of the Apollo Ball Valve (IMY) user manual — IMY/IM-A 3/02
Page 48 · click to enlarge
Page 48

IMY/IM-A 3/02

DRAWING NO. LP0311

Red Lion Controls France

Red Lion Controls BV

20 Willow Springs Circle

56 Boulevard du Courcerin, Batiment 21,

ZI Pariest F-77183 Croissy Beaubourg

NL - 3821 AL Amersfoort

Tel +1 (717) 767-6511

Tel +33 (64) 80 12 12

Tel +31 (33) 472 32 25

Fax +1 (717) 764-0839

Fax +33 (64) 80 12 13

Fax +31 (33) 489 37 93

Red Lion Controls · Databankweg 6C · York PA 17402

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
NO DISPLAY1. Power off, improperly connected, or brown-out. p.43
“PPPPPP” IN DISPLAY1. Program data error. p.43
FLASHING DISPLAY1. Totalizer overflow. p.43
“......” IN DISPLAY1. Loss of data set-ups. p.43
DISPLAY WANDERS1. Loss of data set-ups. p.43
JITTERY DISPLAY1. Electrical “Noise” in process or signal lines. 2. Process inherently unstable. p.43
“ULULUL” IN DISPLAY1. Probe unconnected 2. Broken or burnout probe. 3. Excessive probe temperature. 4. Input overload. p.43

Ask about the Apollo Ball Valve (IMY)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Apollo Ball Valve (IMY)

Be the first to ask — other owners or our team will answer.

Original document

Apollo Ball Valve (IMY) manual PDF

48 pages·584 KB·Marine Instruments·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…