HP Uninterruptible Power System R1500 XR Models User Guide August 2002 (Second Edition) Part Number 217823-002.
Hewlett-P ackard Co mpany s hall not be l iable f or techni cal or edit or ial errors or omissio ns contain ed herein. The informati on in t his doc ument is provid ed “as is ” without war ranty o f any ki nd and is su bject to c hange without notice.
HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide iii Contents About This Guide Audience Assump tions ........................................................................................................... .................... vii Important Safety Inf ormation .
Contents iv H P Uninterrupti ble Power Sy stem R1500 XR M odels U ser Guide Audible Alarms ................................................................................................................. ........................ 2-6 Silencing an Aud ible Alarm .
Contents HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide v Appendix B Electrostati c Dischar ge Grounding Meth ods .............................................................................................................. ...........
.
HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide vii About This Guide This guide provide s step-by-st ep instructi ons for configurat ion, and refere nce informat ion for operation, ba ttery maintena nce, and t roublesh ooting fo r the Unin terrup tible P ower System (U PS).
About This G uide viii HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide Rack Stability WARNING: To reduce the risk of personal injury or damage to the equipment, be sure that: • The leveling feet are extend ed to the floor. • The full weight of t he rack rests on th e levelin g jacks.
About This G uide HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide ix Getting Hel p If you hav e a problem and have exhaus ted the infor mation in this guide, y ou can g et fur ther informat ion and o ther help in the fo llowing locations.
HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide 1-1 1 Overview This chap ter contain s a gen eral overvi ew of the HP UP S, includ ing an introd uctio n to the model conf igurations, power managem ent softwa re, availabl e hardware op tions, and warr antie s.
Overv iew 1-2 HP Uninterrupti ble Power Sy stem R1500 XR Models U ser Guide Network Transient Protector The UPS inc ludes a N etwo rk Transi ent Pro tector (N TP) th at prov ides su rge prote ction fo r connected commu nicat ion devices.
Overv iew HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide 1-3 Front Panel The front pane l of th e UPS is shown in F igure 1 -1. 2 3 1 Figure 1-1: Front panel configuration 1 Battery com.
Overv iew 1-4 HP Uninterrupti ble Power Sy stem R1500 XR Models U ser Guide Rear Panels The rear pane l config uratio ns of the UPS are shown in Figures 1 -2, 1-3, and 1-4 .
Overv iew HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide 1-5 1 3 4 6 7 9 10 5 2 8 Figure 1-3: Rear panel of R1500 XR JPN 1 Com munications port/opt ion slot 2 Load segm ent circ uit pro.
Overv iew 1-6 HP Uninterrupti ble Power Sy stem R1500 XR Models U ser Guide 1 4 2 3 7 8 9 10 6 5 Figure 1-4: Rear panel of R1500 XR H INT’L 1 Com munications port/opt ion slot 2 Circuit protector 3 .
Overv iew HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide 1-7 Power Mana gement Soft ware Power manag ement sof tware ensu res maxi mum powe r reliab ility of HP compute r system s through co mprehensi ve con trol of HP UPS s.
Overv iew 1-8 HP Uninterrupti ble Power Sy stem R1500 XR Models U ser Guide Remote E mergency Power Off P ort The UPS includes an isolat ed REPO port. The REPO f eature allows t he UPS to be powered down from a remo te locati on. To use this feature, th e RE PO port must b e connec ted to a remote, nor mally open switch (no t supplied ).
Overv iew HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide 1-9 Pre-Failure Battery Warranty For specifi c info rmation on the bat tery warran ty, refer to the se ction, “Pre-Fa ilure Batte ry Warranty,” in Chapte r 4.
HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide 2-1 2 Operation This chap ter con tains info rmation on opera ting th e UPS. Topic s inclu de the f ront panel controls, LED in dicato rs, and mod es of ope ratio n. Knowledge of these f eatures i s help ful when configuri ng and troub leshooting the uni t.
Operation 2-2 HP Uninterrupti ble Power Sy stem R1500 XR Models U ser Guide continued Item Description Meaning/Function 5 Utility LED ( ) Flashing Red—U tility i nput v oltage is o utside the + 20% to -3 0% configured n ominal range.
Operation HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide 2-3 Charging the B atteries When the UPS is in S tandby mod e, allow the b atterie s to charge before putting th e U PS into service.
Operation 2-4 HP Uninterrupti ble Power Sy stem R1500 XR Models U ser Guide Returning to Stand by Mode When the UPS is in Operate mod e (the U tility LED is sol id green), pr ess and ho ld the Standby button (1) until the audib le ala rm sounds. Th e Util ity LED (2) f lashes, an d power to the loads ceases .
Operation HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide 2-5 Initiating a Self -Test To initiate a s elf-tes t, pres s and hold th e Test /Alarm R eset b utton (1) for th ree seco nds.
Operation 2-6 HP Uninterrupti ble Power Sy stem R1500 XR Models U ser Guide Audible Al arms The UPS may sound an audible alarm t o warn of a prob lem. For in formatio n on what to do if the UPS detects an ala rm condi tion, re fer to Ch apter 5, “Troub leshoo ting.
HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide 3-1 3 Configuration This chap ter contain s info rmation on configur ing the UPS. Prope r config uration of the UPS is important in per forming o ther func tions on the unit, s uch as ma intai ning the battery an d trouble shooting alarms.
Configurati on 3-2 HP Uninterrupti ble Power Sy stem R1500 XR Models U ser Guide 2. Press and h old the Co nfigure bu tton (1 ) for three se conds. Wh en the Con figure butto n is released, t he front pan el co nfigura tion pa rameter s flash in un ison and the Configu re Mode On LED (2) illuminates sol id green.
Configurati on HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide 3-3 Table 3-2: Available Volt age Settin gs UPS Model Available Settin gs Utility Voltage (VAC) Parameter (LED) R1500 XR NA.
Configurati on 3-4 HP Uninterrupti ble Power Sy stem R1500 XR Models U ser Guide 2. To advance to the approp riate v oltage conf iguration (to the right ), press the On button (3). The selec ted voltage configu ration LED fl ashes. Acti vate th e voltage configurat ion by press ing the Sta ndby butt on (2).
HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide 4-1 4 Battery Maintenance This ch apter con tains i nfor mation fo r prop erly ma intai ning bat teries fo r the U PS, including battery cha rging, repl aceme nt, disposal procedu res, and warranties.
Battery Mainte nance 4-2 HP Uninterrupti ble Power Sy stem R1500 XR Models U ser Guide Determining Wh en to Replace Batteries When the Bad Bat tery/Low Battery LED (1) illu minate s red, bat teries may need to be replaced wit hin 30 to 60 days. 100% 25% 1 1 Figure 4-1.
Battery Mainte nance HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide 4-3 Replacing Batte ries There are two options for repla cing UPS batteries: • Powering down the UPS before remov i.
Battery Mainte nance 4-4 HP Uninterrupti ble Power Sy stem R1500 XR Models U ser Guide 2. Remove th e plastic b attery cover plate, as fea tured in selec t mode ls. Figure 4-3: Removing t he batt ery cove r plate 3. Remove th e two screws to obta in access t o the ba ttery pack.
Battery Mainte nance HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide 4-5 4. Disconnec t the ba ttery cabl e from the circu it board located on the r ight side o f the UPS (1). Un fasten the cabl e wires f rom the c lasp and remov e the wi res witho ut disturbing the pede stal or t he user in terface (2).
Battery Mainte nance 4-6 HP Uninterrupti ble Power Sy stem R1500 XR Models U ser Guide Installing a N ew Battery Pack To install a new batt ery pack, rev erse th e steps in “Remov ing the Batte ry Pack,” in thi s chapter. Testing the New Ba ttery Pack After in stalling the new ba ttery pack , press the Tes t/Alarm Rese t butto n.
Battery Mainte nance HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide 4-7 Care and Storage o f Batteries To maxi mize th e life of batteries : • Minimize the amoun t of ti me the UPS uses b attery po wer by ma tching the UPS configurat ion with the u tilit y voltage.
HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide 5-1 5 Troubleshooting This chap ter serves as a tr oubleshoot ing guid e when proble ms occu r with the UPS . Solu tions for UPS proble ms tha t occu r both during and after startup are covered .
Troubleshoot ing 5-2 HP Uninterrupti ble Power Sy stem R1500 XR Models U ser Guide Table 5-1: Troubleshooting continued Symptom Possible Caus e Suggested Action The Utility LED ( ) is red. The utility input v oltage is a bove the normal ran ge and t he UPS is in Buck mode.
Troubleshoot ing HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide 5-3 Table 5-1: Troubleshooting continued Symptom Possible Caus e Suggested Action The On Battery LED ( ) is red and a n audible alarm soun ds. The UPS is runnin g on bat tery power.
Troubleshoot ing 5-4 HP Uninterrupti ble Power Sy stem R1500 XR Models U ser Guide Table 5-1: Troubleshooting continued Symptom Possible Caus e Suggested Action The UPS freque ntly switches between utility and battery power. There are varia tions in utility power.
HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide A-1 A Regulatory Compliance Notices Regulatory Compliance I dentification N umbers For the pu rpose of regu lato ry comp liance c ertifi cations and ident ificat ion, your pr oduct has been assigned a unique series nu mber.
Regulatory Complia nce Notice s A-2 HP U ninterrupti ble Power Sys tem R1500 XR M odels U ser Guide Class B Equip ment This equip ment has be en te sted and found to c omply w ith the limits for a Cl ass B digita l device, pu rsuant to Pa rt 15 of the FCC Rule s.
Regulatory Complia nce Notice s HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide A-3 Cables Connection s to th is devi ce must be made w ith shie lded cables w ith me tallic R FI/ EMI connector hood s in ord er to ma intain compliance wi th FCC Rules and Regu lation s.
Regulatory Complia nce Notice s A-4 HP U ninterrupti ble Power Sys tem R1500 XR M odels U ser Guide Japanese Notic e China Taiwan N o t i ce.
Regulatory Complia nce Notice s HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide A-5 Battery Replace ment Notice The UPS is equ ipped with a sealed lead-a cid batte ry pack. There is a danger o f explos ion and risk of p ersonal in jury i f the bat tery is i ncorrect ly replaced o r mis treated.
HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide B-1 B Electrostatic Discharge To prevent damaging t he system, b e aware o f the prec autions you ne ed to fo llow when setting up the syst em or h andling pa rts.
HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide C-1 C Specifications This append ix provides the physical, inp ut, and ou tput spec ifica tions fo r the UPS. Topics also include bat tery descr iptions , battery run time estima tes, and enviro nmental requir ements whe n operating t he UPS.
Specificati ons C-2 HP U ninterrupti ble Power Sys tem R1500 XR M odels U ser Guide Input Specifica tions Table C-2: Input Specifications UPS Model Utility Voltage Frequency (Hz) Default Settings Nomi.
Specificati ons HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide C-3 Output Sp ecifications Table C-3: Output Specifications UPS Model Effective VA Nom inal Power Rating (W) Load Segment .
Specificati ons C-4 HP U ninterrupti ble Power Sys tem R1500 XR M odels U ser Guide Battery Speci fications Table C-5: B attery Specif ications Feature Specification Type Sealed lead-ac id; maint enan.
HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide Index-1 Index A alarms See audible alarms altitude specifications C- 4 audible alarms enabl ing a nd disa blin g for Sit e Wir ing Fa ult .
Index Index-2 H P Uninterrupti ble Power Sys tem R1500 XR M odels Us er Guide Federa l Comm unica tio ns Com missi on notic es See FCC notices front bezel, remo ving 3-1 , 4-3 front panel 1-3 front pa.
Index HP Uninterr uptible Power Sy stem R 1500 XR Models User Guide Index-3 rem oving batte ries 4-3 front bezel 3 -1, 4-3 repla cing batte ries 4-2, 4- 3 REPO Port See Rem ote E me rgenc y Powe r Of .
An important point after buying a device HP (Hewlett-Packard) 217823-002 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought HP (Hewlett-Packard) 217823-002 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data HP (Hewlett-Packard) 217823-002 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, HP (Hewlett-Packard) 217823-002 you will learn all the available features of the product, as well as information on its operation. The information that you get HP (Hewlett-Packard) 217823-002 will certainly help you make a decision on the purchase.
If you already are a holder of HP (Hewlett-Packard) 217823-002, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime HP (Hewlett-Packard) 217823-002.
However, one of the most important roles played by the user manual is to help in solving problems with HP (Hewlett-Packard) 217823-002. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device HP (Hewlett-Packard) 217823-002 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center