Instruction/ maintenance manual of the product P520 Honeywell
Go to page of 16
USER MANU AL Put Bar Code Here 66-2066-01 P520 Signal Pr ocessor APPLICATION The Hone ywell P520 is a rac k mounting signal proc essor that is compatible with viewing heads in the S5XX and S55XB/BE series. These include models S506, S509 , S511 and S512 , and the advanced viewing head seri es models S550B/BE, S552B/BE and S556B/BE.
P520 SIGNAL PROCESSOR 66-2066—0 1 2 Fig. 1. P520 front faceplate dim ensions. Fig. 2. P520 side view dimensions. INSTALLATION When Installing this Product… 1. Read these instr uctions carefully . F ailure to follo w them could damage the pro duct or cause a hazardo us condition.
P520 SIGNAL PROCESSOR 3 66-2066—01 3. Install a ground wire from the igni tion transformer case to the igniter assembly . 4. Ensure all igniter wires and cables show no signs of wear . Replace any igniter cab les or wires that are fra yed or crac ked.
P520 SIGNAL PROCESSOR 66-2066—0 1 4 Fig. 3. Rear PCB terminal wiring. P olar ity must be observed when wiri ng this connection (the positive terminal is o n the top). This is an is olated input, so two wires are required. Any DC voltage from 7.5 to 30 may be used.
P520 SIGNAL PROCESSOR 5 66-2066—01 Wiring the Vie wing Head Wiring of the viewing head is made to the ter minals on the rear backplane PCB. These termina ls are described as follows: Fig.
P520 SIGNAL PROCESSOR 66-2066—0 1 6 IMPORTANT Source impedance resistor required at the si gnal processor between SC and SIG GND ter minals for proper signal trans- mission. F or resistor value, ref er to the Wir ing of the Viewing Head section. Fig.
P520 SIGNAL PROCESSOR 7 66-2066—01 V erifyin g the v alidity of the ga in code rece iv ed is one o f the tasks performed by the processor in the viewing heads. The self-check pulse from the signal p rocessors is a 100ms-wide, 20V to 24V pulse with two notche s or breaks in it.
P520 SIGNAL PROCESSOR 66-2066—0 1 8 change the display ed value. Once the desired value is display ed, press the ST ORE button. When the set point is stored, four dashes are display ed momen tarily , indicating that the new v alue was stored into the EEPROM.
P520 SIGNAL PROCESSOR 9 66-2066—01 SETUP AND ADJUSTMENT PR OCEDURES Sighting Adjustment Bef ore making definitiv e settings (i.e., estab lishing the set points) for FLAME ON/OFF , the us er must f irst opti mize the sighting of the viewing head.
P520 SIGNAL PROCESSOR 66-2066—0 1 10 TR OUBLESHOO TING Module Comm unications The P520 communicates with any host computer that has a USB por t and suppor ts ASCII character code transmission at 4800 baud (or , in current revisions of the processor chip, at 4800 or 9600 ba ud).
P520 SIGNAL PROCESSOR 11 66-2066—01 T o change or check the station number of the P520, proceed as f ollows: 1. Press and hold th e Reset button for 4 seconds. 2. The 4 LED digits will show the baud rate and the station number . The 2 leftmost digits are the baud rate (96 or 48); the 2 righ tmost digits are station number fro m (0 to 63).
P520 SIGNAL PROCESSOR 66-2066—0 1 12 address 2). T o change to 9600 baud, in crease the display past 4863. The ne xt display will be 9600, which is 9600 baud, address 0. Then increase the display fur ther to the desired address. T o retur n to 4800 ba ud, reduce the display below 9600, and set the desired address.
P520 SIGNAL PROCESSOR 13 66-2066—01 Fig. 8. P520 with S550B/BE programming flowchart. PRESS BOT H A & B BU TTO N S “CAL ? ” CALI BR ATE VI EW ING HEAD? N N “CAL U” AUTO ADJ UST UV GAIN? .
P520 SIGNAL PROCESSOR 66-2066—0 1 14 Fig. 9. P520 with S552B/BE programming flowchar t. PRESS BOT H A & B BU TTO N S “CAL ?” CALI BR ATE VI EW ING HEAD? N N NO RMAL O PERA TIO N Y CA LI B R .
P520 SIGNAL PROCESSOR 15 66-2066—01 Fig. 10. P520 with S556B/ BE programming flo wchar t. PRESS BOT H A & B BU TTO N S “CAL ?” CALI BR ATE VI EW ING HEAD? N N “CAL U” AUT O A DJUST UV GA.
P520 SIGNAL PROCESSOR Automation and Co ntrol Solutions Honeywell Internationa l Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.
An important point after buying a device Honeywell P520 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Honeywell P520 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Honeywell P520 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Honeywell P520 you will learn all the available features of the product, as well as information on its operation. The information that you get Honeywell P520 will certainly help you make a decision on the purchase.
If you already are a holder of Honeywell P520, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Honeywell P520.
However, one of the most important roles played by the user manual is to help in solving problems with Honeywell P520. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Honeywell P520 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center