Instruction/ maintenance manual of the product RCOR-HVB-IPI Hearth and Home Technologies
Go to page of 41
1 Models: Pier-HVB-IPI ST -HVB-IPI LCOR-HVB-IPI RCOR-HVB-IPI Underwriters Laboratories Listed This product is covered by one or more of the following patents: (United S tates) 4,1 12,913; 4,408,594; 4.
2 These units MUST use one of the vent systems described in the Installing the Fireplace section of the Installers Guide . NO OTHER vent systems or component s MA Y BE USED . This gas fireplace and vent assembly MUST be vented directly to the outside and MUST NEVER be attached to a chimney serving a separate solid fuel burning appliance.
3 Safety and W arning Information .................................................. 2 Service Parts List ......................................................................... 4 Approvals and Codes .................................................
4 * Part number list on following page. * La liste des numéros de pièce se trouve à la page suivante. 5 Log Assembly (NG , LP) Exploded Part s Diagram (GN, PL) Vue éclatée des pièces Service Par.
5 (NG , LP) Exploded Part s Diagram / V ue éclatée des pièces IMPORT ANT : THIS IS DA TED INFORMA TION. The most current information is located on your dealers VIP site. When ordering, supply serial and model numbers to ensure correct service part s.
6 (NG , LP) Exploded Parts Diagram (GN, PL) Vue éclatée des pièces Service Parts ST -HVB-IPI Beginning Manufacturing Date: 6-03 Ending Manufacturing Date: ______ * Part number list on following page. * La liste des numéros de pièce se trouve à la page suivante.
7 (NG , LP) Exploded Part s Diagram / V ue éclatée des pièces IMPORT ANT : THIS IS DA TED INFORMA TION. The most current information is located on your dealers VIP site. When ordering, supply serial and model numbers to ensure correct service part s.
8 * Part number list on following page. * La liste des numéros de pièce se trouve à la page suivante. 5 Log Assembly (NG , LP) Exploded Parts Diagram (GN, PL) Vue éclatée des pièces Service Part.
9 (NG , LP) Exploded Parts Diagram / V ue éclatée des pièces IMPORT ANT : THIS IS DA TED INFORMA TION. The most current information is located on your dealers VIP site. When ordering, supply serial and model numbers to ensure correct service p arts.
10 * Part number list on following page. * La liste des numéros de pièce se trouve à la page suivante. 5 Log Assembly (NG , LP) Exploded Parts Diagram (GN, PL) Vue éclatée des pièces Service Par.
11 (NG , LP) Exploded Part s Diagram / V ue éclatée des pièces IMPORT ANT : THIS IS DA TED INFORMA TION. The most current information is located on your dealers VIP site. When ordering, supply serial and model numbers to ensure correct service part s.
12 (NG , LP) Exploded Parts Diagram (GN, PL) Vue éclatée des pièces Service Parts L&RCOR-HVB-IPI Beginning Manufacturing Date: 6-03 Ending Manufacturing Date: ______ IT E M DESCRI PTI O N SERI .
13 Appliance Certification The Heat & Glo fireplace models discussed in this Installers Guide have been tested to certification standards and listed by the applicable laboratories.
14 2 Getting St arted Introducing the Heat & Glo Gas Fireplaces Heat & Glo direct vent gas fireplaces are designed to oper- ate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the outside.
15 Figure 1. Diagram of the PIER-HVB-IPI 42-5/8 (1082mm) Ø 8 (204mm) 12 (305mm) ELECTRICAL ACCE SS GA S LI NE ACCE SS 34-3/4 (882m m ) 4-1/16 (102m m ) 4-1/2 (1 14mm) 4-3/4 (121mm) 2-5/16 (58mm) 37-7.
16 Figure 2. Diagram of the ST -HVB-IPI 5-14 (133 mm) 12 (306m m) 1/2 (13mm) (4) 46-5/ 8 (1183mm) 42 (1067 mm) 32-5/16 (820 mm) 21 (533m m) 36-3/ 16 (919 mm) 2-5/ 16 (58mm) 4-3/ 4 (121 mm) 4-1/1 6 (10.
17 Figure 3. Diagram of the LCOR-HVB-IPI and RCOR-HVB-IPI 12 (305mm) Ø 8 (204 mm) 34-3/4 (882mm) 4-3/4 (121 mm) 37-7 /16 (950 mm) ELECTR ICAL ACCES S GAS L IN E ACCE SS 42-5/ 8 (10 82mm 2-5/ 16 (58mm.
18 3 Inst alling the Fireplace Step 1. Locating the Fireplace The diagram below shows space and clearance require- ments for locating a fireplace within a room. Minimum Clearances from the Fireplace to Combustible Materials Inches mm Glass Sides or Ends .
19 Framing should be constructed of 2 X 4 lumber or heavier . Model A B C D E PIER-HVB-IPI 42-1/8 42-1/2 23 35-3/4 48 ST -HVB-IPI 47-5/8 42-1/2 23 35-3/4 48 L&RCOR-HVB-IPI 42-1/8 42-1/2 28-3/4 35-3/4 48 Figure 5. Framing Dimensions NOTE: DIMENSIONS SHOWN IN INCHES Shows center of 10” x 12” vent framing holes for top and rear venting.
20 NOTE: PIPES OVERLAP 1-1/4 INCHES A T EACH JOINT . Figure 6. DVP-Series Direct V ent Component Specifications (5-inch inner pipe / 8-inch outer pipe) D V P 9 0 S T 12- 9/1 6 11 - 1 / 4 7-1 /4 1-1/4 T YP 1/2 TYP 8-9 /16 DVP36 DVP48 48 24 36 4 6 DVP4 DVP6 12 DVP12 2 MIN.
21 Figure 7. V ent System Component s and T ermination Kit s Step 3. Inst alling the V ent System A. V ent System Approvals These models are approved to use DVP series direct vent pipe components and terminations (see Figures 6 and 7). Approved vent system components are labeled for identifi- cation.
22 Figure 8 NOTE: On vertical venting configurations you may want to install the flue re- strictor (385-128). See flue restrictor installation in- structions. Flue Restrictor Instructions 1. Locate the Flue Restrictor which is in the manual bag. Figure 10.
23 Figure 14. V enting with One 90° Elbow Figure 13. V enting with One 90° Elbow V H H V NA TURAL GAS - VENTING WITH ONE 90° ELBOW V (FT .) H (FT .) 1' MIN. (305mm) 3' MAX. (914mm) 2' MIN. (610mm) 6' MAX. (1.83m) 3' MIN. (914mm) 9' MAX.
24 Figure 15. V enting with T wo 90° Elbows H 1 H V V V 1 H NA TURAL GAS VENTING WITH TWO 90° ELBOWS V (FT .) H + H 1 (FT .) 90 0 Elbow on top 2.5’ MAX. (64mm) 1' MIN. (305mm) 3' MAX. (914mm) 2' MIN. (610mm) 6' MAX. (1.83m) 3' MIN.
25 Figure 16. V enting with T wo 90° Elbows Figure 17. V enting with T wo 90° Elbows H 1 V H V H H 1 NA TURAL GAS VENTING WITH TWO 90° ELBOWS V (FT .) H + H 1 (FT .) 1' MIN. (305mm) 3' MAX. (914mm) 2' MIN. (610mm) 6' MAX. (1.83m) 3' MIN.
26 Figure 18. V enting with three 90° elbows H H 1 H 2 V H V H 1 V 1 NA TURAL GAS VENTING WITH THREE 90° ELBOWS V + V 1 (FT .) H + H 1 + H 2 (FT .) 1' MIN. (305mm) 3' MAX. (914mm) 2' MIN. (610mm) 6' MAX. (1.83m) 3' MIN. (914mm) 9' MAX.
27 Figure 19. V enting with three 90° elbows V H H 1 V 1 V H H 1 V 1 NA TURAL GAS VENTING WITH THREE 90° ELBOWS V + V 1 (FT .) H + H 1 (FT .) 90 0 Elbow on top 2.5’ MAX. (64mm) 1' MIN. (305mm) 3' MAX. (914mm) 2' MIN. (610mm) 6' MAX.
28 1. Att ach the First V ent Component to the Starting Collars T o attach the first vent component to the starting collars of the fireplace: • Slide the first vent section onto the unit and push in until they snap lock in position. • Rotate this section to the desired position.
29 4. Install Firestops For Horizontal Runs - Firestops are REQUIRED on both sides of a combustible wall through which the vent passes. NOTE: Model DVP-TRAP does not need an exterior firestop on an exterior combustible wall. The firestop is built into the cap.
30 Figure 26. Ceiling Firestop (Ceiling Side) If the area above the ceiling is NOT an attic, position and secure the ceiling firestop on the ceiling side of the previously cut and framed hole. If the area above the ceiling IS an attic, position and secure the firestop on top of the previously framed hole.
31 V = VENT TERMINAL X = AIR SUPPL Y INLET = AREA WHERE TERMINAL IS NOT PERMITTED Figure 29. V ent T ermination Minimum Clearances A = 12" ....................... clearances above grade, veran- da, porch, deck or balcony B = 12" ............
32 For V ertical T erminations - T o locate the vent and install the vent sections: • Locate and mark the vent centerpoint on the underside of the roof, and drive a nail through the centerpoint. • Make the outline of the roof hole around the centerpoint nail.
33 Step 4. Positioning, Leveling, and Securing the Fireplace • Place the fireplace into position. • Level the fireplace from side to side and from front to back. • Shim the fireplace with non-combustible material, such as sheet metal, as necessary .
34 • Insert insulation from the outside of the fireplace and pack the insulation tightly to totally seal between the pipe and the outer casing. • At the gas line access hole the gap between the supply piping and gas access hole can be plugged with non- combustible insulation to prevent cold air infiltration.
35 Step 8. Wiring the Fireplace NOTE: Electrical wiring must be installed by a licensed electrician. CAUTION: DISCONNECT REMOTE CONTROLS IF AB- SENT FOR EXTENDED TIME PERIODS.
36 Wall Switch Position the wall switch in the desired position on a wall. Run a maximum of 25 feet (7.8 m) or less length of 18 A.W .G . minimum wire and connect it to the fireplace ON/OFF switch pigtails. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC- TION WHEN SERVICING CONTROLS.
37 Step 9. Finishing Figures 38 and 39 show the minimum vertical and corresponding maximum horizontal dimensions of fireplace mantels or other combustible projections above the top front edge of the fireplace. See Figures 4 and 5 for other fireplace clearances.
38 Inst alling the T rim Combustible materials may be brought up to the specified clearances on the side and top front edges of the fireplace, but MUST NEVER overlap onto the front face. The joints between the finished wall and the fireplace top and sides can only be sealed with a 300° F .
39 Placing the Ember Material Ember material is shipped with this gas fireplace. The bag labeled Glowing Ember (050-721) is standard glowing em- ber material. T o place the ember material: • Remove the wing nuts and glass clips or tension springs around the glass door .
40 Step 1 1. Before Lighting the Fireplace Before lighting the fireplace, be sure to do the following: ! ! Step 12. Lighting the Fireplace Y ou’ve reviewed all safety warnings, you’ve checked the fireplace for gas leaks, you know the vent system is unobstructed, and you’ve checked for faulty components.
41 4 Maint aining and Servicing Y our Fireplace Fireplace Maintenance Although the frequency of your fireplace servicing and main- tenance will depend on use and the type of installation, you should have a qualified service technician perform an appli- ance check-up at the beginning of each heating season.
An important point after buying a device Hearth and Home Technologies RCOR-HVB-IPI (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Hearth and Home Technologies RCOR-HVB-IPI yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Hearth and Home Technologies RCOR-HVB-IPI - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Hearth and Home Technologies RCOR-HVB-IPI you will learn all the available features of the product, as well as information on its operation. The information that you get Hearth and Home Technologies RCOR-HVB-IPI will certainly help you make a decision on the purchase.
If you already are a holder of Hearth and Home Technologies RCOR-HVB-IPI, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Hearth and Home Technologies RCOR-HVB-IPI.
However, one of the most important roles played by the user manual is to help in solving problems with Hearth and Home Technologies RCOR-HVB-IPI. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Hearth and Home Technologies RCOR-HVB-IPI along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center