SAFETY INFORMATION
Brookhaven Direct Vent Model: 20DVT

FOR YOUR SAFETY Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Homeowner’s Manual
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
Ê
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
10009459 2/07 Rev. 5



This gas appliance should be installed by a qualified installer in accordance with local building codes and with current CSA-B149.1 Installation codes for Gas Burning Appliances and Equipment. For USA Installations follow local codes and/or the current National Fuel Gas Code. ANSI Z223.1/NFPA 54. In the Commonwealth of Massachusetts, all gas fitting and installation of this heater shall only be done by a licensed gas fitter or licensed plumber. FOR SAFE INSTALLATION AND OPERATION PLEASE NOTE THE FOLLOWING: 1. This fireplace gives off high temperatures and should be located out of high traffic areas and away from furniture and draperies. 2. Children and adults should be alerted to the hazards of high surface temperatures of this fireplace and should stay away to avoid burns or ignition of clothing. 3. CAUTION: Due to high glass surface temperature chil- dren should be carefully supervised when in the same room as fireplace. 4. Under no circumstances should this fireplace be modified. Parts removed for servicing should be replaced prior to operating this fireplace again. 5. Installation and any repairs to this fireplace must be per- formed by a qualified installer, service agency or gas sup- plier. A professional service person should be contacted to inspect this fireplace annually. Make it a practice to have all of your gas fireplaces checked annually. More frequent cleaning may be required due to excess lint and dust from carpeting, bedding material, etc. 6. Control compartments, burners and air passages in this fire- place should be kept clean and free of dust and lint. Make sure the gas valve and pilot light are turned off before you attempt to clean this fireplace. 7. The venting system (chimney) of this fireplace should be checked at least once a year and if needed your venting system should be cleaned. 8. Keep the area around your fireplace clear of combustible materials, gasoline and other flammable vapor and liquids. This fireplace should not be used as a drying rack for cloth- ing, nor should Christmas stockings or decorations be hung on or around the fireplace. 9. Under no circumstances should any solid fuels (wood, coal, paper or cardboard etc.) be used in this fireplace. 10. The flow of combustion and ventilation air must not be ob- structed in any way. 11. When fireplace is installed directly on carpeting, vinyl tile or any combustible material other than wood, the fireplace must be installed on a metal or wood panel extending the full width and depth of the fireplace. 12. This fireplace requires adequate ventilation and combustion air to operate properly. 13. This fireplace must not be connected to a chimney flue serving a separate solid fuel burning fireplace. 14. When the fireplace is not in use it is recommended that the gas valve be left in the OFF position.
This appliance may be installed in an aftermarket per- manently located, manufactured home or mobile home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicat- ed on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
IMPORTANT: PLEASE REVIEW THE FOLLOWING CAREFULLY Remove any plastic from trim parts before turning the fireplace ON. It is normal for fireplaces fabricated of steel to give off some expansion and/or contraction noises during the start up or cool down cycle. Similar noises are found with your furnace heat exchanger or car engine. It is not unusual for your gas fireplace to give off some odor the first time it is burned. This is due to the curing of the paint and any undetected oil from the manufacturing process. Please ensure that your room is well ventilated - open all windows. It is recommended that you burn your fireplace for at least ten (10) hours the first time you use it. If the optional fan kit has been installed, place the fan switch in the “OFF” position during this time.
E A B
Y
D
Y
F
LU584-R
Fig. 1 Locate gas fireplace.
A) Flat on wall B) Cross corner C) **Island D) *Room divider E) *Flat on wall corner F) Chase installation Y) 6” minimum
NOTE: (fig. 1) ** Island (C) and Room Divider (D) installation is possible as long as the horizontal portion of the vent system (X) does not exceed 20’ (610 cm). See details in Venting Section. * When you install your fireplace in(D) Room divider or (E) Flat on wall corner positions (Y), a minimum of 6” (153 mm) clear- ance must be maintained from the perpendicular wall and the front side edge of the fireplace. Refer to (Y) in Figure 1.
10009459 3


No drywall in this area. Must use noncombustible wall board such as DuraRock.
Fig. 2 Fireplace specifications and framing dimensions.

4 10009459


Top of Unit to Ceiling 32” (813 mm) Front of Unit to Combustibles 36” (914 mm) Appliance Top of Standoff 0” (0 mm) Bottom 0” (0 mm) Side 3/4” (19 mm) Back 0” (0 mm) Venting Concentric sections of DV Vent 1” (25 mm) Nonconcentric sections of DV Vent Sides and Bottom 1” (25 mm) Top 2” (51 mm)
The height that a combustible mantel is fitted above the fireplace is dependent on the depth of the mantel. This also applies to the distance between the mantel leg (if fitted) and the fireplace.
For the correct mounting height and widths refer to Figs. 3a and 3b, and the following Mantel Charts.
The fitting of a bay window trim kit does not effect the distances and reference points referred to in the diagram and chart.
Noncombustible mantels and legs may be installed at any height and width around the appliance. When using paint or lacquer to finish the mantel, such paint or lacquer must be heat resistant to prevent discoloration.

Fig. 3b Combustible mantel leg minimum installation.
A hearth is not mandatory but is recommended for aesthetic purposes. We recommend a noncombustible hearth which projects out 12” (305 mm) or more from the front of the fireplace.
Cold climate installation recommendation:
When installing this unit against a non-insulated exterior wall or chase, it is mandatory that the outer walls be insulated to conform to applicable insulation codes.

Proposition 65 Warning: Fuels used in gas, wood- burning or oil fired appliances, and the products of combustion of such fuels, contain chemicals known to the State of California to cause cancer, birth defects and other reproductive harm. California Health & Safety Code Sec. 25249.6
Fig. 3a Combustible mantel minimum installation.
10009459 5


Check fireplace to make sure it is levelled and properly positioned.
To mount the appliance: 1. Choose the location. 2. This unit comes with four (4) flanges pre-mounted on both sides of the fireplace to allow two different drywall thicknesses to be used. Flange “A” is for 1/2” drywall while flange “B” is for 5/8” drywall. 3. Bend the desired flanges out 90° on both sides of the fireplace. Slide the fireplace into the framed opening until the flanges contact the front surfaces of the framing. Level the unit and secure it firmly in place.

Flange Drywall Position Depth A 1/2” / 13 mm B 5/8” / 16 mm
Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA, installations must be in accordance with the cur- rent ANSI Z223.1/NFPA 54 and/or local codes hav- ing jurisdiction.
In Canada, please consult provincial and/or local authorities having jurisdiction for installations at elevations above 4,500 feet (1,370m).
When purging the gas lines, the front win- dow frame assembly must be removed.
Fig. 4 Nailing flanges.
The gas pipeline can be brought in through the rear of the appliance as well as the bottom. Knockouts are provided on the bottom behind the valve to allow for the gas pipe installation and testing of any gas connection. It is most convenient to bring the gas line in from the rear right side of the valve as this allows fan installation or removal without disconnecting the gas line.
Noncombustible materials such as brick or tile may be extended over the edges of the face of the fireplace. DO NOT cover any vent or grille panels.
If a Trim Kit is going to be installed on the fireplace, the brick or tile will have to be installed flush with the edges of the fireplace.
The gas line connection can be made with properly tinned 3/8” copper tubing, 3/8” rigid pipe or an ap- proved flex connector. Since some municipalities have additional local codes, it is always best to consult your local authority and the National Fuel Gas Code, ANSI Z223.1/NFPA 54 in the USA or the CSA-B149.1 installa- tion code.

Always check for gas leaks with a mild soap and water solution applied with a brush no larger than 1” (25 mm). Never apply soap and water solution with a spray bottle. Do not use an open flame for leak testing.
6 10009459


Do not wire the remote ON/OFF wall switch for this gas appliance into a 120v power supply.
1. Thread wire through the electrical knockout located on either side of the unit. Take care not to cut the wire or insulation on metal edges. Ensure the wire is secured and protected form possible damage. Run one end of the gas control valve and the other end to the conveniently located wall switch. 2. Attach the wire to the ON/OFF switch and install switch into receptacle box. Attach cover plate to switch. 3. Connect wiring to gas valve. (Fig. 6)
Fig. 5 Typical gas supply installation.
The fireplace valve must not be subjected to any test pressures exceeding 1/2 psi. Isolate or disconnect this or any other gas appliance control form the gas line when pressure testing.

The gas control is equipped with a captured screw type pressure test point, therefore it is not necessary to pro- vide a 1/8” test point up stream of the control.
When using copper or flex connector use only approved fittings. Always provide a union when using black iron pipe so the gas line can be easily disconnected for burner or fan servicing. See gas specification for pres- sure details and ratings.
Fig. 6 Remote switch wiring diagram for R models.
The fireplace valve must not be subjected to any test pressures exceeding 1/2 psi. Isolate or disconnect this and any other gas appliance control from the gas line when pressure testing.
There must not be any obstruction such as bushes, garden sheds, fences, decks or utility buildings within 24” (610 mm) from the front of the termination hood.
Do not locate termination hood where excessive snow or ice build up may occur. Be sure to check vent termi- nation area after snow falls, and clear to prevent ac- cidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.
Location of Vent Termination
It is imperative the vent termination be located observ- ing the minimum clearances as shown on the next page.
*Check with local codes or in absence of same with CSA B149.1 Installation Codes (1991) for Canada or follow the current National Fuel Gas Code, ANSI Z223.1/NFPA 54 for installations in the USA.
10009459 7

Fig. 7 Termination location requirements.
8 10009459

Termination Clearances Termination clearances for buildings with combustible and noncombustible exteriors.
Outside Corner Inside Corner
F = Combustible 6" (152 mm) Noncombustible 2" (51 mm)
G = Combustible 6" (152 mm)
Noncombustible 2" (51 mm)
Balcony - with no side wall
Balcony - with perpendicular side wall
M
P
M = Combustible & Noncombustible 12" (305 mm)
M = 24" (610 mm) P = 20” (508 mm)
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.
Fig. 7a Termination clearances.
Canadian Installations:
* Be sure the flex vent is flat and flush with the flue or outer collar before proceeding. Apply a tug to be sure the vent will not slip off the collars.
Venting system must be installed in accordance with the current CSA-B149.1 installation code.
USA Installations:
Repeat process with 7” flex vent pipe. The same proce- dure must be performed on the vent side.
The venting system must conform with local codes and/ or the current National Fuel Gas code ANSI Z223.1/ NFPA 54.

Only venting components manufactured by CFM Corpo- ration can be used in Direct Vent systems.
Before joining the flex vent pipe to the unit, apply a bead of high temperature sealant* (provided) to the 4” pipe exiting the fireplace. Secure flex vent piep in place with a hose clamp (provided). *Be sure the flex pipe overlaps at least 1” (25 mm) onto the collars of the fireplace and termination. If the ter- mination has an internal bead, be sure to overlap and secure 1” (25 mm) past the bead.
Fig. 8 Apply high temperature sealant to 4” and 7” pipes.
Alcove Applications* · Combustible & Noncombustible · 10009459 9

When using CFM Corporation twist-lock pipe it is not necessary to use sealant on the joints. The only areas of the venting system that need to be sealed with high temperature silicone sealant are the sliding joints of any telescopic vent section used in the system.
Vertical dimension from the floor of the unit to the center of the horizontal vent pipe
To join the twist lock pipes together, simply align the beads of the male end with the grooves of the female end, then while bringing the pipe together, twist the pipe until the flange on the female end contacts the external flange on the male end. It is recommended that you secure the joints with three (3) sheet metal screws, however this is not mandatory with twist lock pipe.
To make it easier to assemble the joints we suggest putting a lubricant (Vaseline or similar) on the male end of the twist lock pipe prior to assembly.
Male End Female End
Horizontal dimension from the outside face of the
Fig. 9 Twist-lock pipe joints.
wall to the center of the fireplace vent flange
Sidewall vent graph showing the relationship between vertical
and horizontal dimensions for a Direct Vent flue system.
The vent chart should be read in conjunction with the following vent installation instructions to determine the relationship of the vertical and horizontal dimensions of the vent system.
Fig. 10 Sidewall venting graph. (Dimensions in feet)
Since it is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.
The Vent Graph shows the relationship between vertical and horizontal side wall venting and will help to deter- mine the various dimensions allowable.
Example A: If the vertical dimension from the floor of the fireplace is 11’ (3.4 m) the horizontal run to the face of the outer wall must not exceed 14’ (4.3 m).
Minimum clearance between vent pipes and com- bustible materials is 1”(25 mm) on top, bottom and sides unless otherwise noted.
When vent termination exits through foundations less than 20” below siding outcrop, the vent pipe must flush up with the siding. It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.
Example B: If the vertical dimension from the floor of the unit is 7’ (2.14 m), the horizontal run to the face of the outer wall must not exceed 8¹⁄₂’ (2.6 m).
The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace to the face of the outer wall.
Screw Holes TWL100 · ÎÊÊÊÊÊ{ÊÊÊÊxÊ ÊÈÊÊÊÊÇÊÊÊÊÊnÊÊÊÊÊÊÊ£äÊÊ££ÊÊ£ÓÊÊ£ÎÊÊ£{ÊÊ£xÊÊÊ£ÈÊÊ£ÇÊÊ£nÊÊ£ÊÊÓä · 10 10009459

3 x 90° Elbows
1 + 2 + 3 + 4 = 270°
FP1176 Fig. 11 Maximum three (3) 90° elbows per installation.
Max.
Max.
FP1177
Fig. 14 Maximum elbow usage.
Fig. 12 Maximum horizontal run with no rise.
Twist Lock Pipe
A B
STEP 1
Locate vent opening on the wall. It may be necessary to first position the fireplace and measure to obtain hole location. Depending on whether the wall is combustible or noncombustible, cut opening to size. (Fig. 15) (For combustible walls first frame in opening.)
A + B = 17' (Max.)
(5.2m)
7'6" (2.3m)
Fig. 13 Horizontal run reduction.
Combustible Walls (Fig. 15): Cut a 9³⁄₈”H x 9³⁄₈” W (240 x 240 mm) hole through the exterior wall and frame.
Noncombustible Walls (Fig. 15): Hole opening must be 7.5” (190 mm) in diameter.
36" (914 mm) · 36" (914 mm) · 10009459 11


Measure the horizontal length requirement including a 2” (51 mm) overlap, i.e. from the elbow to the outside wall finish plus 2”, or the distance required if installing a second 90° elbow. (Fig. 18)
Measure wall thickness and cut adjustable zero clearance sleeve parts to proper length (MAXIMUM 12”/305 mm). Assemble sleeve and attach to firestop with #8 sheet metal screws (supplied). Install firestop assembly. (Fig. 16)


Zero clearance sleeve is only required for combustible walls.
Use appropriate length of pipe section - telescopic or fixed - and install. The sections which go through the wall are packaged with the starter kit, and can be cut to suit if necessary.
Fig. 16 Adjustable zero clearance sleeve.
Place fireplace into position. Measure the vertical height (X) required from the base of the flue collars to the center of the wall opening. (Fig. 17)
Sealing vent pipe and firestop gaps with high tem- perature sealant will restrict cold air being drawn in around fireplace.
Apply a band of silicone to the inner and outer flue collars of the fireplace and using appropriate length of pipe section(s) attach to fireplace with three (3) screws. Follow with the installation of the inner and outer elbow, again secure joints with three (3) sheet metal screws. Wipe off any excess silicone.
12 10009459

STEP 4 Install the 4” (102 mm) flex vent pipe to the appliance collar as described on Page 13. Secure the end with the first spring 6³⁄₄” (172 mm) from the flex pipe end to the unit. STEP 5 Slide the 7” (178 mm) flex vent pipe over the 4” flex vent pipe and secure 7” collar as described on Page 14. STEP 6 Bend the flex pipe horizontal so the bottom of the hori- zontal pipe measures 6¹⁄₂” (165 mm) from the top of the unit immediately after the 90° formation. (Fig. 20) Be sure to follow the 1/2” (13 mm) rise in a 12” (305 mm) horizontal run rule. STEP 7 Install the 4” flex then 7” flex to the termination.
Apply high temperature sealant to 4” (102 mm) and 7” (178 mm) collars or the termination one inch away from the end. Guide the vent termination’s 4” and 7” collars into their respective vent pipes. Double check that the vent pipes overlap the collars by 2” (51 mm). Secure the termination to the wall with screws provided and caulk around the wall plate to weatherproof. As an alterna- tive to screwing the termination directly to the wall, you may also use expanding plugs or an approved exterior construction adhesive. You may also attach the termina- tion with screws through the inner body into the 4” vent pipe, however for this method, you must extend the 4” pipe approximately 6” (152 mm) beyond the outer face of the wall.

Support horizontal pipes every 36” (914 mm) with metal pipe straps.

NOTE: The 40” (1016 mm) flex vent is used for 90° off the top of the unit then out the back wall. Follow Steps 1 and 2 on Page 11. STEP 3 Install the four (4) spacer springs on the 4” flex vent pipe. When installing the spacer springs around the 4” pipe, stretch the spring to approximately 15” (381 mm), wrap the spring around the pipe and interlock the ends of the spacer spring approximately 2” (51 mm). Mea- sure 6³⁄₄” (172 mm) from the end of the pipe. Place the next spring 5” (127 mm) from the previously installed spring. Place the next spring 6” (152 mm) from the last spring. Finally, place the last spring 12” (305 mm) from the last spring installed. (Fig. 19)
Fig. 20 Bend flex vent at 90° so horizontal portion is 6¹⁄₂” (165 mm) off top of unit.
When it is not possible to meet the required vent ter- minal clearances of 12” (305 mm) above grade level a snorkel kit is recommended. This allows installation depth of down to 7” (178 mm) below grade level. The 7” is measured from the center of the horizontal vent pipe as it penetrates through the wall.

Ensure the sidewall venting clearances are observed. If venting system is installed below ground, we recom- mend a window well with adequate and proper drainage to be installed around the termination.
If installing a snorkel, a minimum 24” (610 mm) vertical rise is necessary. The maximum horizontal run with the 24” vertical pipe is 36” (914 mm). This measurement is taken from the collar of the fireplace (or transition elbow) to the face of the exterior wall. See the Sidewall Venting Graph for extended horizontal run if the vertical exceeds 24” (610 mm).
Fig. 19 Install spacer springs.
10009459 13


*A minimum of 24” (610 mm) vertical pipe must be installed when using the 7TDVSNORK.
Fig. 21 Below grade installation.
Do not backfill around snorkel.

A clearance of at lest 4” must be main- tained between the snorkel and the soil.
If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fas- ten brackets to wall first, then secure to snorkel with self drilling #8 x 1/2 sheet metal screws. It will be necessary to extend vent pipes out as far as the protruding wall face. (Fig. 22)

Fig. 22 Snorkel installation, recessed foundation.
14 10009459


1 + 2 + 3 + 4 = 270°
4. Proceed to plumb for additional openings through the roof. In all cases, the opening must provide a mini- mum of 1” (25 mm) clearance to the vent pipe, i.e., the hole must be at least 9³⁄₈” x 9³⁄₈” (240 x 240 mm). 5. Place fireplace into position. 6. Place firestop(s) #7DVFS or Attic Insulation Shield #7DVAIS into position and secure. (Fig. 26) 7. Install roof support (Fig. 25) and roof flashing making sure upper flange is below the shingles. (Fig. 28) 8. Install appropriate pipe sections until the venting is above the flashing. (Fig. 28) 9. Install storm collar and seal around the pipe. 10. Add additional vent lengths for proper height. (Fig. 28) 11. Apply high temperature sealant to 4” and 7” collars of vertical vent termination and install. If there is a room above ceiling level, fire stop spacer must be installed on both the bottom ad the top side of the ceiling joists. If an attic is above ceiling level a 7DVAIS (Attic Insulation Shield) must be installed. The enlarged ends of the vent section always face downward.
Fig. 26 Place firestop spacer(s) and secure.


Fig. 28 Roof flashing.
10009459 15

Starter Kit - Model 7TDVSK - Sidewall Venting (Twist Lock Pipe) Model 7FDVSK - Sidewall Venting (Flex Vent Pipe) Models 7TDVTK/TV - Hot Touch Termination Kits Model 7TDVTVTK/TV - Cool Touch Termination Kit Starter Kit - Model 7TDVSKV - Vertical Venting for 7TDVSKV-A order 1/12 to 6/12 roof pitch for 7TDVSKV-B order 7/12 to 12/12 roof pitch for 7TDVSKV-F order flat roof Starter Kit for Below Grade Installation Model 7TDVSKS -Snorkel Kit (Twist Lock Pipe) Model 7FDVSKS -Snorkel Kit (Flex Vent Pipe)
Starter Pipe Model 7TDVP 20/8 - 24” Starter Pipe Bulk Model 7FDVP 30/8 - 30” Flex Pipe Bulk
45o Elbow 7TDV45 for Rear Vent to Vertical Vent or Vertical/Horizontal Offsets
90o Transition Elbow 7TDVRT90 for Rear Vent to Vertical Vent 90° Elbow 7TDV90 Vertical/Horizontal Offset
Telescopic vent sections 7TDVP1117 -11” to 17” adjustable length 7TDVP3567 -35” to 67” adjustable length
Pipe sections for vertical or horizontal venting Model 7TDVP8” - 4 per box Model 7TDVP12” - 4 per box Model 7TDVP24” - 4 per box Model 7TDVP36” Model 7TDVP48”
Firestop Spacer Model 7DVFS
Attic Insulation Shield Model 7DVAIS
Vertical/Horizontal Combination Offset Support Model 7DVCS
16 10009459

Only glass approved by CFM Corporation should be used on this fireplace.
Pull Left Side Latch Counter- clockwise Pull Right Side Latch Clockwise
Attach the cast panel by hook- ing onto top of fireplace.
FP1629 Fig. 30 Window frame assembly removal.
It is necessary to clean the glass periodically. During start-up condensation, which is normal, forms on the inside of the glass and causes lint, dust and other airborne particles to cling to the glass surface. Also initial paint curing may deposit a slight film on the glass. It is therefore recommended the glass be cleaned two or three times with a non-ammonia household cleaner and warm water (gas fireplace glass cleaner is recommended). After the initial cleaning process the glass should be cleaned two or three times during each operating season depending on the environment in the house.
To remove the cast front assem- bly, pull cast front up then lift out.
Fig. 29 Remove cast front by lifting up then out.
Window Frame Assembly Removal
Clean the glass after the first two weeks of operation. Do not clean glass when hot. Do not use abrasive cleaners. Do not strike or slam the glass.
1. Turn the fireplace OFF (including the pilot). 2. If the unit has been operating, allow time for the components to cool. 3. Remove cast front assembly. 4. Unlock the frame window by removing the two (2) machine screws at the top corners of the window frame. 5. Unlock the frame window by pulling the handle of the two latches at the bottom part of the window frame. Pull the left latch counterclockwise and the right latch clockwise. 6. Pull the bottom of the glass frame assembly out and slide the top of the frame assembly out the slot at the top. 7. To replace the window frame assembly, reverse this procedure.

6. Place the log front (J12). Place the two underside holes of the log over the two pin studs of the bracket on the left and right sides of the front burner hous- ing. (Fig. 32) 7. Place ember material on top of burner. Scatter the ember material over the tiles on the front area of the burner housing. (Fig. 31) Do not pack the ember material. Separate it when unpacking and keep it in a fluffy and loose condition for more realistic ember effect. 8. Place large lava rock onto the two sides of the burner tray. (Fig. 31)
The logs are fragile and should be handled with care. Keep the packaging material out of the reach of children and dispose of the mterial in a safe manner.
The individual logs can be easily identified by the numbers cast on the underside of each log.
LOGS 20DVT Log Rear J11 Log Front J12
Do not place any of the lava rock material on the burner housing assembly.
Log Rear (J11) Figure 31

As with all plastic bags - these are not toys and should be kept away from children and infants. 5. Place the log rear (J11). Place the two under- side holes of the log over the two pin studs of the bracket on the left and right sides of the burner housing. (Fig. 31)

Log Front (J12) Figure 32


Ember Material · Lava Rock · 18 10009459

Flame Characteristics
The large bag of lava rock provided with this fireplace must be placed on the firebox base around the sides of the burner assembly and on the tray beneath the grate.
It is important to periodically perform a visual check of the pilot and the burner flames. Compare them to Fig- ures 35 & 36. If any of the flames appear abnormal call a service person.
Under no circumstances should this large lava rock be placed on any part of the burner assembly.

For fireplaces equipped with Hi/Lo valves, flame adjust- ment is accomplished by rotating the Hi/Lo adjustment knob located near the centre of the gas control. (Fig. 33 or 34)

This appliance venting system is designed and con- structed to develop a positive flow adequate to remove flue gases to the outside atmosphere.
Fig. 33 Flame adjustment knob for Honeywell valve.

Any foreign objects in the venting system, except those designed specifically for the venting system, may cause spillage of flue gases.
To inspect the venting system, make sure the main gas valve is off. Remove window frame assembly (Refer to Window Frame Assembly Removal Section). Using a flashlight, check the area above the baffle in the com- bustion dome. Clean if necessary.
Fig. 34 Flame adjustment knob for SIT valve.

Fig. 36 Correct burner flame appearance for the 20DVT.
10009459 19

may result causing property damage, personal injury or loss of life.
A. This heater has a pilot which must be lit manu-
er’s instructions. • If you cannot reach your gas supplier, call the Fire Department C. Use only your hand to push in or turn the gas
ally. When lighting the pilot follow these instruc- tions exactly. B. BEFORE LIGHTING smell all around the
control knob. Never use tools. If the knob will not push in or turn by hand, do not try to repair it, call a qualified service technician. Applying force or any attempted repair may result in a fire or explosion.
D. Do not use this fireplace if any part has been under
water. Immediately call a qualified service techni- cian to inspect the heater and to replace any part of the control system and any gas control which has been under water.
OFF
P
O
T
F P
F
ON
ON
F
O
F
O
F
F
O
Euro SIT SIT NOVA Honeywell

1. Spark ignitor will not light A. Defective or misaligned Using a match, light pilot. If pilot lights, turn off electrode at pilot. pilot and push the red button again. If pilot will not light, check the gap at electrode and pilot; it should be 1/8” to have a strong spark. B. Defective ignitor (Push Button) Push piezo Ignitor Button. Check for spark at electrode and pilot. If no spark to pilot, and electode wire is properly connected, replace ignitor. 2. Pilot will not stay lit after A. Defective pilot generator Check pilot flame. Must impinge on thermocouple/ carefully following lighting (thermocouple), remote wall thermopile. NOTE: This pilot burner assembly instructions. switch. utilizes both a thermocouple and a thermopile. The thermocouple operates the main valve opera- tion (ON/OFF). Clean and/or adjust pilot for maxi- mum flame impingement on thermopile and thermo- couple. B. Defective automatic valve Turn valve knob to “Pilot.” Maintain flow to pilot; millivolt meter should read greater than 10 mV. If the reading is okay and the pilot does not stay on, replace the gas valve. NOTE: An interrupter block (not supplied) must be used to conduct this test. 3. Pilot burning, no gas to A. Wall switch or wires defective Check wall switch and wires for proper connections main burner Jumper wires across terminals at wall switch; if burner comes on, repalce defective wall switch. If okay, jumper wires across wall switch wires at valve; if burner comes on, wires are faulty or connections are bad. B. Thermopile may not be 1. Be sure wire connections from thermopile at generating sufficient gas valve terminals are tight and thermopile is millivoltage. fully inserted into pilot bracket. 2. One of the wall switch wires may be grounded. Remove wall switch wires from valve terminals if pilot now stays lit, trace wall switch wiring for ground. May be grounded to fireplace or gas supply. 3. Check thermopile with millivolt meter. Take reading at thermopile terminals of gas valve— should read 250-300 millivolts (minimum 150) while holding valve knob depressed in pilot position and wall switch “OFF.” Replace faulty thermopile if reading is below specified minimum. C. Plugged burner orifice. Check burner orifices for debris and remove. D. Defective automatic valve Turn valve knob to “ON,” place wall switch to “ON” — operator. millivolt meter should read greater than 100 mV. If the reading is okay and the burner does not come on, replace the gas valve. 4. Frequent pilot outage A. Pilot flame may be too low Clean and/or adjust pilot flame for maximum flame problem. or blowing (high) causing the impingement on thermopile and thermocouple. pilot safety to drop out. B. Possible blockage of the vent Check the vent terminal for blockage (recycling the terminal. flue gases) C. Low gas supply pressure Check gas supply pressure to be between minimum and maximum with the burner in the “ON” position.
10009459 21

Fuel Conversion Instructions

To convert the 20DVT unit for use with a different gas follow these instructions. Before proceeding, turn control knob on valve to “OFF” and turn gas supply OFF. Turn OFF any electricity that may be going to the appliance. CAUTION: Logs may be HOT! Allow to cool before proceeding.
NOVA SIT820 Valve Conversion 1. Using the TORX T20 bit, remove and discard the three (3) pressure regulator mounting screws (A), pressure regulator tower (B) and the spring and diaphragm assembly (C). (Fig. 37)
Fig. 38 Replace regulator.
Burner Orifice Conversion 1. Remove two (2) burner housing assembly mounting screws. (Fig. 39) 2. Lift burner housing up and remove burner orifice from manifold assembly using 7/16” wrench. (Fig. 39)


Pilot Location Burner Orifice (Refer to Conversion Kit Orifice chart)
Fig. 37 Remove mounting screws, pressure regulator tower and spring and diaphragm assembly.
Fig. 39 Burner housing assembly.
22 10009459



FP1631 Fig. 40 Back burner housing.
Pilot Orifice Conversion 1. Remove pilot hood by lifting up. (Fig. 41) 2. Remove pilot orifice with 5/32” Allen wrench. (Fig. 42) 3. Install conversion pilot orifice. 4. Reinstall pilot hood and be sure to align with index tab. 5. Turn the gas supply valve and gas valve on and test for leaks. Use a 50/50 solution of liquid soap and water to test for leaks at gas fittings and joints. Apply water/soap solution with brush only - do not over ap- ply. NEVER test with an open flame. 6. Follow procedure on rating plate to light the pilot. Check for leaks. 7. Turn main burner on and check for leaks. 8. Reinstall logs and window frame assembly. Refer to Page 18 for proper log placement. Installation complete.
10009459 23

To obtain proper operation, it is imperative that the pilot and burner’s flame characteristics are steady, not lifting or floating.
Burner and Burner Compartment
It is important to keep the burner and the burner compartment clean. At least once per year the logs and lava rock/ember material should be removed and the burner compartment vacuumed and wiped out. Remove and replace the logs as per the instructions in this manual.
Typically, the top 3/8” or 1/2” of the thermopile should be engulfed in the pilot flame. (Fig. 43)
To adjust pilot burner; (by qualified service technician)
Always handle the logs with care as they are fragile and may also be hot if the fireplace has been in use. Contact your local representative to arrange an annual service program.
The primary air shutter is set at factory and should only be adjusted, if necessary, by a qualified service techni- cian.

24 10009459


CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time, without notice. 20DVT

Ref. Description 20DVT 1. Log Set (Complete) 10009451 1a. Log Rear J11 1b. Log Front J12 2. Lava Rock (Pkg) 10001454 3. Ember (Pkg) 10000550 4. Burner Housing Assy 10009061 5. Ceramic Tile (single) 57803 6a. Orifice Burner - Nat. (not shown) Refer to Rating Plate for Orifice Size 6b. Orifice Burner - Prop. (not shown) Refer to Rating Plate for Orifice Size
10009459 25

Ref. Description 20DVT
7a. Orifice Pilot - Natural 10002268 7b. Orifice Pilot - Propane 10002269 8a. Pilot Assy. SIT - RN 10002264 8b. Pilot Assy. SIT - RP 10002265 9. Pilot Tubing w/Fittings SIT 10001296 10. Remote Switch Wire Assy. 20010345 11. Manifold Tubing w/Fittings (not shown) 57318 12. Thermocouple (RN/RP) 53373 13. Thermopile (RN/RP) 51827 14. Electrode Ignitor w/Cable (RN/RP) 10001297 15. Ignitor Piezo w/Nut 50932 16. Valve SIT 820.662 (RN) 20010563 17. Flexible Gas Line w/ON/OFF Shut-Off Valve 10009064 18. Frame Window w/Glass Assy. 10009485 19. Console Assy. 10009081 20. Support Housing & Log Left Assy. 10009060 21. Support Housing & Log Right Assy. 10009463 22. ON/OFF Switch 51842 23. Ceramic Refractory Lining Kit (not shown) 10009457 24. Relief Plate Assy. 10009064 25. Remote Switch Kit (not shown) 53875
Fuel Conversion Kits Conversion Kit, NG to LP 20DVT Kit #10009486 Conversion Kit, LP to NG 20DVT Kit #10009488
26 10009459

Optional remote control units are available to control different functions of the appliance. Model Functions Controlled RC1 ON/OFF RC2 ON/OFF and Temperature IMTFK Wall mounted thermostat control
Take care when handling the refractory panels as they are fragile until held in place and supported.
Fig. 44 Rear ceramic panel placement.
A cherry finish corner cabinet is available for the 20DVT. Item #BACG6B0, Model #BCCGF20CC.

28 10009459

10009459 29

30 10009459

PRODUCT COVERED BY THIS WARRANTY All Vermont Castings gas stoves, gas inserts, and gas fireplaces, and all Majestic brand gas fireplaces equipped with an Insta-Flame Ceramic Burner, or standard steel tube burner.
CFM Corporation (hereinafter referred to collectively as the Company) warrants that your new Vermont Castings or Majestic Gas Fireplace/ Stove is free from manufacturing and material defects for a period of one year from the date of purchase, subject to the following conditions and limitations.
The heat exchanger, where applicable, and combustion chamber of every Vermont Castings or Majestic gas product is warranted for life against through wall perforation. All appliances equipped with an Insta-Flame Ceramic Burner have limited lifetime coverage on the ceramic burner plaque. Warrantees are made to the original owner subject to proof of purchase and the conditions and limitations listed on this Warranty Document
CAST IRON: All external and internal cast iron parts are warranted for a period of three years. Note: On porcelain enamel finished external parts and accessories The Company offers no Warranty on chipping of enamel surfaces. Inspect all product prior to accepting it for any damage to the enamel. The salt air environment of coastal areas or a high humidity environment can be corrosive to the porcelain enamel finish. These conditions can cause rusting of the cast iron beneath the porcelain enamel finish, which will cause the finish to flake off. Dye lot variations with replacement parts and/or accessories can occur and are not covered by warranty.
GLASS DOORS: Glass doors are covered for a period of one year. Glass doors are not warranted for breakage due to misuse or accident. Glass doors are not covered for discoloration or burned in stains due to environmental issues, or improper cleaning and maintenance.
BRASS PLATED PARTS AND ACCESSORIES: Brass parts should be cleaned with Lemon oil only. Brass cleaners cannot be used. Mortar mix and masonry cleaners may corrode the brass finish. The Company will not be responsible for, nor will it warrant any brass parts which are damaged by external chemicals or down draft conditions.
ELECTRONIC AND MECHANICAL COMPONENTS: Electronic and mechanical components of the burner assembly are covered for one year. All steel tube burners are warranted for one year.
as near-by trees, buildings, roof tops, hills, or mountains. b) Inadequate ventilation or negative air pressure caused by
ACCESSORIES: Unless otherwise noted all components and CFM Corporation company supplied accessories are covered for a period of one year.
mechanical systems such as furnaces, fans, clothes dryers, etc. • This warranty is void if: a) The fireplace has been operated in atmospheres contaminated by
chlorine, fluorine, or other damaging chemicals. b) The fireplace has been subjected to prolonged periods of dampness
or condensation c) Any damages to the fireplace, combustion chamber, heat exchanger
or other components due to water, or weather damage, which is the result of but not limited to, improper chimney/venting installation. d) Any alteration, willful abuse, accident, or misuse of the product
has occurred.
10009459 31


EnerGuide Ratings D.O.E. Model Fireplace Efficiency (%) Steady State (%) (AFUE%) 20DVTRN 60.1 80 64 20DVTRP 60.1 81 64

Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| 1. Spark ignitor will not light | A. Defective or misaligned electrode at pilot. | Using a match, light pilot. If pilot lights, turn off pilot and push the red button again. If pilot will not light, check the gap at electrode and pilot; it should be 1/8” to have a strong spark. | p.21 |
| 1. Spark ignitor will not light | B. Defective ignitor (Push Button) | Push piezo Ignitor Button. Check for spark at electrode and pilot. If no spark to pilot, and electode wire is properly connected, replace ignitor. | p.21 |
| 2. Pilot will not stay lit after carefully following lighting instructions. | A. Defective pilot generator (thermocouple), remote wall switch. | Check pilot flame. Must impinge on thermocouple/ thermopile. NOTE: This pilot burner assembly utilizes both a thermocouple and a thermopile. The thermocouple operates the main valve opera- tion (ON/OFF). Clean and/or adjust pilot for maxi- mum flame impingement on thermopile and thermo- couple. | p.21 |
| 2. Pilot will not stay lit after carefully following lighting instructions. | B. Defective automatic valve | Turn valve knob to “Pilot.” Maintain flow to pilot; millivolt meter should read greater than 10 mV. If the reading is okay and the pilot does not stay on, replace the gas valve. NOTE: An interrupter block (not supplied) must be used to conduct this test. | p.21 |
| 3. Pilot burning, no gas to main burner | A. Wall switch or wires defective | Check wall switch and wires for proper connections Jumper wires across terminals at wall switch; if burner comes on, repalce defective wall switch. If okay, jumper wires across wall switch wires at valve; if burner comes on, wires are faulty or connections are bad. | p.21 |
| 3. Pilot burning, no gas to main burner | B. Thermopile may not be generating sufficient millivoltage. | 1. Be sure wire connections from thermopile at gas valve terminals are tight and thermopile is fully inserted into pilot bracket. 2. One of the wall switch wires may be grounded. Remove wall switch wires from valve terminals if pilot now stays lit, trace wall switch wiring for ground. May be grounded to fireplace or gas supply. 3. Check thermopile with millivolt meter. Take reading at thermopile terminals of gas valve— should read 250-300 millivolts (minimum 150) while holding valve knob depressed in pilot position and wall switch “OFF.” Replace faulty thermopile if reading is below specified minimum. | p.21 |
| 3. Pilot burning, no gas to main burner | C. Plugged burner orifice. | Check burner orifices for debris and remove. | p.21 |
| 3. Pilot burning, no gas to main burner | D. Defective automatic valve operator. | Turn valve knob to “ON,” place wall switch to “ON” — millivolt meter should read greater than 100 mV. If the reading is okay and the burner does not come on, replace the gas valve. | p.21 |
| 4. Frequent pilot outage problem. | A. Pilot flame may be too low or blowing (high) causing the pilot safety to drop out. | Clean and/or adjust pilot flame for maximum flame impingement on thermopile and thermocouple. | p.21 |
| 4. Frequent pilot outage problem. | B. Possible blockage of the vent terminal. | Check the vent terminal for blockage (recycling the flue gases) | p.21 |
| 4. Frequent pilot outage problem. | C. Low gas supply pressure | Check gas supply pressure to be between minimum and maximum with the burner in the “ON” position. | p.21 |