Liquid Cooled Diesel Engine Generator Sets

Standby Power Rating 150KW 60 Hz / 150KVA 50 Hz

Prime Power Rating 120KW 60 Hz / 120KVA 50 Hz

Generac Power Systems SD150 — Liquid Cooled Diesel Engine Generator Sets diagram (page 1)
Fig. 1 · Liquid Cooled Diesel Engine Generator Sets

FEATURES

n INNOVATIVE DESIGN & PROTOTYPE TESTING are key components of GENERAC'S success in "IMPROVING POWER BY DESIGN." But it doesn't stop there. Total commitment to component testing, reliability testing, environmental testing, destruction and life testing, plus testing to applicable CSA, NEMA, EGSA, and other standards, allows you to choose GENERAC POWER SYSTEMS with the confidence that these systems will provide superior performance.

FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-matching the surge loads to the engine.

n SINGLE SOURCE SERVICE RESPONSE from Generac's dealer network provides parts and service know-how for the entire unit, from the engine to the smallest electronic component. You are never on your own when you own a GENERAC POWER SYSTEM.

n TEST CRITERIA: PROTOTYPE TESTED SYSTEM TORSIONAL TESTED ELECTRO-MAGNETIC INTERFERENCE NEMA MG1 EVALUATION MOTOR STARTING ABILITY SHORT CIRCUIT TESTING UL COMPLIANCE AVAILABLE

n ECONOMICAL DIESEL POWER. Low cost operation due to modern diesel engine technology. Better fuel utilization plus lower cost per gallon provide real savings.

n LONGER ENGINE LIFE. Generac heavy-duty diesels provide long and reliable operating life.

n GENERAC TRANSFER SWITCHES, SWITCHGEAR AND ACCESSORIES. Long life and reliability is synonymous with GENERAC POWER SYSTEMS. One reason for this confidence is that the GENERAC product line includes its own transfer systems, accessories, switchgear and controls for total system compatibility.

n SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION. This state-of-the-art power maximizing regulation system is standard on all Generac models. It provides optimized

Generac Power Systems SD150 — FEATURES diagram (page 1)
Fig. 2
Page 2 of the Generac Power Systems SD150 user manual — GENERATOR FEATURES
Page 2 · click to enlarge
Page 2

APPLICATION & ENGINEERING DATA

GENERATOR SPECIFICATIONS

ENGINE SPECIFICATIONS

TYPE Four-pole, revolving field ROTOR INSULATION Class H STATOR INSULATION Class H TOTAL HARMONIC DISTORTION

MAKE GENERAC/DEUTZ MODEL BF6M1013FC Deutz CYLINDERS 6 DISPLACEMENT 7.1 Liter (433 cu.in.) BORE 108 mm (4.25 in.) STROKE 130 mm (5.12 in.) COMPRESSION RATIO 17.6:1 INTAKE AIR Turbocharged/Aftercooled NUMBER OF MAIN BEARINGS 7 CONNECTING RODS Drop Forged Steel CYLINDER HEAD Cast Iron PISTONS Aluminum Alloy CRANKSHAFT Die Forged, Induction Hardened Steel

VALVE TRAIN LIFTER TYPE Solid INTAKE VALVE MATERIAL Heat Resistant Steel EXHAUST VALVE MATERIAL Heat Resistant Steel HARDENED VALVE SEATS Replaceable

EXCITATION SYSTEM ❐PERMANENT MAGNET EXCITER Eighteen pole exciter

Magnetically coupled DC current Mounted outboard of main bearing REGULATION Solid-state

ENGINE GOVERNOR ❐ELECTRONIC Standard

FREQUENCY REGULATION, NO-LOAD TO FULL LOAD ... 0.5% STEADY STATE REGULATION 0.25%

GENERATOR FEATURES

LUBRICATION SYSTEM TYPE OF OIL PUMP Gear OIL FILTER Full flow, Cartridge CRANKCASE CAPACITY 21 Liters (22.2 qts.)

I Four pole, revolving field generator, directly connected to the

engine shaft through a heavy-duty, flexible disc for permanent alignment.

I Generator meets the temperature rise standards for class "F"

COOLING SYSTEM TYPE OF SYSTEM Pressurized, Closed Recovery WATER PUMP Pre-Lubed, Self-Sealing TYPE OF FAN Pusher NUMBER OF FAN BLADES 6 DIAMETER OF FAN 660 mm (26 in.) COOLANT HEATER 120V, 1800 W

insulation as defined by NEMA MG1-32.6, while the insulation system meets the requirements for the higher class "H" rating.

I All prototype models have passed a three-phase symmetrical

short circuit test to assure system protection and reliability.

I All prototype models are tested for motor starting ability by

measuring the instantaneous voltage dip with a waveform data acquisition system.

I All models utilize an advanced wire harness design for reliable

FUEL SYSTEM FUEL #2D Fuel (Min Cetane #40)

interconnection within the circuitry.

(Fuel should conform to ASTM Spec.) FUEL FILTER 5 Micron FUEL INJECTION PUMP Bosch, Unit type cam driven FUEL PUMP Mechanical INJECTORS Multi-Hole, Nozzle Type ENGINE TYPE Direct Injection FUEL LINE (Supply) 6.35 mm (0.25 in.) FUEL RETURN LINE 6.35 mm (0.25 in.)

I Magnetic circuit, including amortisseur windings, tooth and skewed

stator design, provides a minimal level of waveform distortion and an electromagnetic interference level which meets accepted requirements for standard AM radio, TV, and marine radio telephone applications.

I Voltage waveform deviation, total harmonic content of the AC

waveform, and T.I.F. (Telephone Influence Factor) have been evaluated to acceptable standards in accordance with NEMA MG1-32.

I Alternator is self-ventilated and drip-proof constructed.

ELECTRICAL SYSTEM BATTERY CHARGE ALTERNATOR 20 Amps at 12 V STARTER MOTOR 12 V RECOMMENDED BATTERY 12 Volt, 90 A.H., 27F GROUND POLARITY Negative

I Fully life-tested protective systems, including "field circuit and

thermal overload protection" and optional main-line circuit breakers capable of handling full output capacity.

I System Torsional acceptability confirmed during Prototype Testing.

Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). Prime (Unlimited Running Time): Applicable for supplying electric power in lieu of commercially purchased power. Prime power is the maximum power available at variable load. A 10% overload capacity is available for 1 hour in 12 hours. (All ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271).

+1% regulation

Page 3 of the Generac Power Systems SD150 user manual — OPERATING DATA
Page 3 · click to enlarge
Page 3

OPERATING DATA

STANDBYPRIME SD150SD150 GENERATOR OUTPUT VOLTAGE/KW-60Hz 120/240V, 1-phase, 1.0 pf 120/208V, 3-phase, 0.8 pf NOTE: Consult your 120/240V, 3-phase, 0.8 pf Generac dealer for additional voltages. 277/480V, 3-phase, 0.8 pf 600V, 3-phase, 0.8 pfRated AMP 150 625 150 520 150 451 150 226 150 180Rated AMP 120 500 120 416 120 361 120 180 120 144 GENERATOR OUTPUT VOLTAGE/KVA-50Hz 110/220V, 1-phase, 1.0 pf 115/200V, 3-phase, 0.8 pf NOTE: Consult your 100/200V, 3-phase, 0.8 pf Generac dealer for 231/400V, 3-phase, 0.8 pf additional voltage 480V, 3-phase, 0.8 pfRated AMP 120 545 150 433 150 433 150 217 150 180Rated AMP 96 436 120 346 120 346 120 173 120 144 MOTOR STARTING KVA Maximum at 35% instantaneous voltage dip with standard alternator; 50/60 Hz with optional alternator; 50/60 Hz231/240V 400/480V 390 405 325 338231/240V 400/480V 390 405 325 338 FUEL Fuel consumption—60 Hz Load liters/hr. gal./hr. Fuel consumption—50 Hz liters/hr. gal./hr.25% 50% 75% 100% 9.3 17.3 25.1 32.6 2.5 4.6 6.6 8.6 7.4 13.8 20.1 26.0 2.0 3.6 5.3 6.925% 50% 75% 100% 7.4 13.8 20.1 26.0 2.0 3.6 5.3 6.9 5.9 11.0 16.0 20.8 1.6 2.9 4.2 5.5 COOLING Coolant capacity System - lit. (gal) Engine - lit. (gal) Radiator - lit. (gal) Coolant flow/min. 60 Hz - lit. (gal) 50 Hz - lit. (gal) Heat rejection to coolant @ full load BTU/hr. Air to radiator in 60 Hz - m3/min. (cfm) enclosed unit 50 Hz - m3/min. (cfm) Max. external pressure drop on radiator in. HO 2 Max. air temperature to radiator °C (°F) Max. ambient temperature °C (°F)19.0 (5.0) 9.8 (2.6) 9.2 (2.4) 159.0 (42.0) 132.5 (35.0) 344,700 159 (5,600) 132 (4,667) 0.5 48.9 (120) 43.3 (110)19.0 (5.0) 9.8 (2.6) 9.2 (2.4) 159.0 (42.0) 132.5 (35.0) 275,760 159 (5,600) 132 (4,667) 0.5 48.9 (120) 43.3 (110) COMBUSTION AIR REQUIREMENTS Flow at rated power 60 Hz - m3/min. (cfm) 50 Hz - m3/min. (cfm)14.2 (501.0) 11.3 (398.9)11.3 (400.8) 9.0 (319.2) EXHAUST Exhaust flow at rated output 60 Hz - m3/min. (cfm) 50 Hz - m3/min. (cfm) Max recommended back pressure in. Hg (kPa) Exhaust temperature at rated output °C (°F) Exhaust outlet size mm. (in.)38.6 (1362) 30.7 (1085) 5.1 (1.5) 538 (1000) 127 (5.0)30.9 (1090) 24.6 (868) 5.1 (1.5) 538 (1000) 127 (5.0) ENGINE Rated RPM 60 Hz / 50 Hz HP at rated KW 60 Hz / 50 Hz Piston speed 60 Hz - m./sec. (ft./min.) 50 Hz - m./sec. (ft./min.) BMEP 60 Hz / 50 Hz - psi1800 / 1500 221 / 176 7.8 (1535) 6.5 (1280) 223 / 2131800 / 1500 178 / 141 7.8 (1535) 6.5 (1280) 180 / 171 DERATION FACTORS Temperature -3.5% for every 10oC above - °C -2.77% for every 10oF above - °F Altitude -1.1% for every 100 m above - m -3.5% for every 1000 ft. above - ft.40 104 1066 350040 104 1066 3500
Page 4 of the Generac Power Systems SD150 user manual — 262/544-4811 • FAX 262/544-4851
Page 4 · click to enlarge
Page 4

STANDARD ENGINE & SAFETY FEATURES

I High Coolant Temperature Automatic Shutdown I Low Coolant Level Automatic Shutdown I Low Oil Pressure Automatic Shutdown I Overspeed Automatic Shutdown (Solid-state) I Crank Limiter (Solid-state) I Oil Drain Extension I Radiator Drain Extension I Factory-Installed Cool Flow Radiator I Closed Coolant Recovery System I UV/Ozone Resistant Hoses I Rubber-Booted Engine Electrical Connections I Coolant Heater

I Secondary Fuel Filter I Fuel Lockoff Solenoid I Stainless Steel Flexible Exhaust Connection I Battery Charge Alternator I Battery Cables I Battery Tray I Vibration Isolation of Unit to Mounting Base I 12 Volt, Solenoid-activated Starter Motor I Air Cleaner I Fan Guard I Control Console I Radiator Duct Adaptor

OPTIONS

n OPTIONAL COOLING SYSTEM ACCESSORIES ❍208/240V Coolant Heater

n ADDITIONAL OPTIONAL EQUIPMENT ❍Automatic Transfer Switch ❍Isochronous Governor ❍3 Light Remote Annunciator ❍5 Light Remote Annunciator ❍20 Light Remote Annunciator ❍Remote Relay Panels ❍Unit Vibration Isolators ❍Oil Make-Up System ❍Oil Heater ❍5 Year Warranties ❍Export Boxing ❍GenLink® Communications Software

n OPTIONAL FUEL ACCESSORIES ❍Flexible Fuel Lines ❍UL Listed Fuel Tanks ❍Base Tank Low Fuel Alarm ❍Primary Fuel Filters

n OPTIONAL EXHAUST ACCESSORIES ❍Critical Exhaust Silencer

n OPTIONAL ELECTRICAL ACCESSORIES ❍2A Battery Charger ❍10A Dual Rate Battery Charger ❍Battery, 12 Volt, 135 A.H.

n OPTIONAL ENCLOSURE ❍Weather Protective ❍Sound Attenuated ❍Aluminum and Stainless Steel ❍Enclosed Muffler

n OPTIONAL ALTERNATOR ACCESSORIES ❍Alternator Upsizing ❍Alternator Strip Heater ❍Alternator Tropicalization ❍Voltage Changeover Switch ❍Main Line Circuit Breaker

Generac Power Systems SD150 — OPTIONS diagram (page 4)
Fig. 3

n CONTROL CONSOLE OPTIONS ❍Analog Control "C" Panel (Bulletin 0151160SBY) ❍Analog/Digital Control "E" Panel (Bulletin 0161310SBY)

Design and specifications subject to change without notice. Dimensions shown are approximate. Contact your Generac dealer for certified drawings. DO NOT USE THESE DIMENSIONS FOR INSTALLATION PURPOSES.

GENERAC

  • ® POWER SYSTEMS, INC.
  • P.O. BOX 8
  • WAUKESHA, WI 53187

262/544-4811 • FAX 262/544-4851

Bulletin 0167290SBY / Printed in USA 01.03

All specifications subject to change without notice.

Ask about the Generac Power Systems SD150

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Generac Power Systems SD150

Be the first to ask — other owners or our team will answer.

Original document

Generac Power Systems SD150 manual PDF

4 pages·127 KB·Automobile Parts·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…