INSTALLATION INSTRUCTIONS FOR *M(H,S)8 / *D(H,S)8 / *HS8 / GME8 GAS FURNACE
Installer: Affix all manuals adjacent to the unit.
These furnaces comply with requirements em- bodied in the American National Standard / Na- tional Standard of Canada ANSI Z21.47·CSA- 2.3 Gas Fired Central Furnaces.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
As a professional installer, you have an obligation to know the product better than the customer.
This includes all safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual. Pay special attention to all safety warnings. Often during installation or repair, it is possible to place yourself
in a position which is more hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product safely and to know it well enough
to be able to instruct a customer in its safe use.
Safety is a matter of common sense...a matter of thinking before acting.
Most dealers have a list of specific, good safety practices...follow them.
The precautions listed in this Installation Manual are intended as supplemental to existing practices.
However, if there is a direct conflict between existing practices and the content of this manual,
the precautions listed here take precedence.
for the applicable Specification Sheet referred to in this manual.
DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES. IF YOU INSTALL OR PERFORM SERVICE ON THIS UNIT, YOU ASSUME
WHICH MAY RESULT . M ANY JURISDICTIONS REQUIRE A LICENSE TO
INSTALL OR SERVICE HEATING AND AIR CONDITIONING EQUIPMENT.
®







SAFETY PRECAUTIONS Adhere to the following warnings and cautions when installing, adjusting, altering, servicing, or operating the furnace. To ensure proper installation and operation, thoroughly read this manual for specifics pertaining to the installation and application of this product.

INSTALLATION , ADJUSTMENT , ALTERATION , SERVICE OR MAINTENANCE ,
REFER TO THIS MANUAL . F OR ADDITIONAL ASSISTANCE OR
INFORMATION , CONSULT A QUALIFIED INSTALLER , SERVICER AGENCY OR
THE GAS SUPPLIER.
IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
Special Warning for Installation of Furnace or Air Handling Units in Enclosed Areas such as Garages, Utility Rooms or Parking Areas
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
Carbon monoxide producing devices (such as an automobile, space heater, gas water heater, etc.) should not be operated in enclosed areas such as unventilated garages, utility rooms or parking areas because of the danger of carbon monoxide (CO) poisoning resulting from the exhaust emissions. If a furnace or air handler is installed in an enclosed area such as a garage, utility room or parking area and a carbon monoxide producing device is operated therein, there must be adequate, direct outside ventilation.
DO NOT TRY TO LIGHT ANY APPLIANCE. DO NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT USE ANY PHONE IN YOUR BUILDING. IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR’S PHONE. FOLLOW THE GAS SUPPLIER’S INSTRUCTIONS. IF YOU CANNOT REACH YOUR GAS SUPPLIER, CALL THE FIRE DEPARTMENT. INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
This ventilation is necessary to avoid the danger of CO poisoning which can occur if a carbon monoxide producing device continues to operate in the enclosed area. Carbon monoxide emissions can be (re)circulated throughout the structure if the furnace or air handler is operating in any mode.
CO can cause serious illness including permanent brain damage or death.
THIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM.
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE FURNACE BEFORE TURNING OFF THE ELECTRICAL SUPPLY.
ROUTINE , INSPECTION , MAINTENANCE AND SUPERVISION . I F THE
BUILDING IN WHICH ANY SUCH DEVICE IS LOCATED WILL BE VACANT ,
CARE SHOULD BE TAKEN THAT SUCH DEVICE IS ROUTINELY INSPECTED ,
P OSSIBLE PROPERTY DAMAGE , PERSONAL INJURY OR DEATH DUE TO
MAINTAINED AND MONITORED . IN THE EVENT THAT THE BUILDING
FIRE , EXPLOSION , SMOKE , SOOT , CONDENSATION , ELECTRICAL SHOCK
MAYBE EXPOSED TO FREEZING TEMPERATURES AND WILL BE VACANT ,
OR CARBON MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION ,
ALL WATER ‐ BEARING PIPES SHOULD BE DRAINED , THE BUILDING SHOULD
REPAIR OPERATION, OR MAINTENANCE OF THIS PRODUCT.
EVENT THAT THE BUILDING MAY BE EXPOSED TO FREEZING
TEMPERATURES AND WILL BE VACANT , ANY HYDRONIC COIL UNITS
T O PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER
SHOULD BE DRAINED AS WELL AND, IN SUCH CASE, ALTERNATIVE HEAT
SOURCES SHOULD BE UTILIZED.
INFORMATION , CONSULT A QUALIFIED INSTALLER , SERVICER AGENCY OR
THE GAS SUPPLIER.
TO PREVENT POSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, THE FURNACE MUST BE LOCATED TO PROTECT THE ELECTRICAL COMPONENTS FROM WATER.

ing the integrated control module to electrostatic discharge. This procedure is applicable to both installed and non-installed (ungrounded) furnaces.
FURNACE MUST BE CATEGORY I VENTED. DO NOT VENT USING CATEGORY III VENTING. PROVISIONS MUST BE MADE FOR VENTING COMBUSTION PRODUCTS
1. Disconnect all power to the furnace. Do not touch the integrated control module or any wire connected to the control prior to discharging your body’s electrostatic charge to ground. 2. Firmly touch a clean, unpainted, metal surface of the furnaces near the control. Any tools held in a person’s hand during grounding will be discharged. 3. Service integrated control module or connecting wiring following the discharge process in step 2. Use caution not to recharge your body with static electricity; (i.e., do not move or shuffle your feet, do not touch ungrounded objects, etc.). If you come in contact with an ungrounded object, repeat step 2 before touching control or wires. 4. Discharge your body to ground before removing a new control from its container. Follow steps 1 through 3 if installing the control on a furnace. Return any old or new controls to their containers before touching any ungrounded object.
FLUE PIPE COULD BE A LIMITING FACTOR IN LOCATING THE FURNACE.
All units are securely packed in shipping containers tested according to International Safe Transit Association specifica- tions. The carton must be checked upon arrival for external damage. If damage is found, a request for inspection by carrier’s agent must be made in writing immediately.
The furnace must be carefully inspected on arrival for damage and bolts or screws which may have come loose in transit. In the event of damage the consignee should:
Before installing this unit, please read this manual thoroughly to familiarize yourself with specific items which must be ad- hered to, including but not limited to: unit maximum external static pressure, gas pressures, BTU input rating, proper elec- trical connections, circulating air temperature rise, minimum or maximum CFM, and motor speed connections, and venting. These furnaces are designed for Category I venting only.
TO PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE, DO NOT INSTALL THIS FURNACE IN A MOBILE HOME, TRAILER, OR RECREATIONAL VEHICLE.
IMPORTANT NOTE TO THE OWNER REGARDING PRODUCT WARRANTY
Your warranty certificate is supplied as a separate document with the unit installed by your contractor. Read the limited war- ranty certificate carefully to determine what is and is not cov- ered and keep the warranty certificate in a safe place. If you are unable to locate the warranty certificate please contact your installing contractor or contact customer service (877-254-4729) to obtain a copy.
The carrier is responsible for making prompt inspection of dam- age and for a thorough investigation of each claim. The distribu- tor or manufacturer will not accept claims from dealers for trans- portation damage.
Keep this literature in a safe place for future reference.
IMPORTANT: To receive the Lifetime Heat Exchanger Limited Warranty (good for as long as you own your home) and the 10- year Parts Limited Warranty, online registration must be com- pleted within 60 days of installation. Online registration is not required in California or Quebec. Complete warranty details available from your local dealer or, for Goodman® brand prod- ucts, visit www.goodmanmfg.com and for Amana® brand prod- ucts, visit www.amana-hac.com
Use the following precautions during furnace installation and servicing to protect the integrated control module from dam- age. By putting the furnace, the control, and the person at the same electrostatic potential, these steps will help avoid expos-

To register your Goodman® brand unit, go to www.goodmanmfg.com and click “Warranty Registration”. Complete the registration as prompted.
To register your Amana® brand unit, go to www.amana-hac.com and click “Warranty Registration”. Complete the registration as prompted.
Product limited warranty certificates for models currently in pro- duction can be viewed at www.goodmanmfg.com or www.amana- hac.com. If your model is not currently in production or does not appear on the website, please contact your installing con- tractor or contact customer service (877-254-4729) to obtain a copy of your warranty certificate.
Each product overview page contains a Product Warranty link; by clicking on it you will be able to view the limited warranty coverage for that specific product. To view warranty registration information, click on the Product Warranty text on the left navi- gation panel on the home page of each website. The Online Product Registration pages are located in this same section.
This furnace is primarily designed for residential home-heating applications. It is NOT designed or certified for use in mobile homes, trailers or recreational vehicles. Neither is it designed or certified for outdoor applications. The furnace must be in- stalled indoors (i.e., attic space, crawl space, or garage area provided the garage area is enclosed with an operating door).
This furnace can be used in the following non-industrial com- mercial applications:
Schools, Office buildings, Churches, Retail stores, Nursing homes, Hotels/motels, Common or office areas
TO PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE, DO NOT INSTALL THIS FURNACE IN A MOBILE HOME, TRAILER, OR RECREATIONAL VEHICLE.
In such applications , the furnace must be installed with the following stipulations:
To ensure proper furnace operation, install, operate and maintain the furnace in accordance with these installa- tion and operation instructions, all local building codes and ordinances. In their absence, follow the latest edition of the National Fuel Gas Code (NFPA 54/ANSI Z223.1), and/or CAN/CSA B149 Installation Codes, local plumbing or waste water codes, and other applicable codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI Z223.1) can be obtained from any of the following:
This furnace may be used as a construction site heater ONLY if the following conditions are met:
1430 Broadway New York, NY 10018
1 Batterymarch Park Quincy, MA 02269
CSA International 8501 East Pleasant Valley Cleveland, OH 44131

A copy of the CAN/CSA B149 Installation Codes can also be obtained from:
CSA International 178 Rexdale Boulevard Etobicoke, Ontario, Canada M9W 1R3
The rated heating capacity of the furnace should be greater than or equal to the total heat loss of the area to be heated. The total heat loss should be calculated by an approved method or in accordance with “ASHRAE Guide” or “Manual J-Load Cal- culations” published by the Air Conditioning Contractors of America.
In the USA, this furnace MUST be installed in accordance with the latest edition of the ANSI Z223.1 booklet entitled “National Fuel Gas Code” (NFPA 54), and the requirements or codes of the local utility or other authority having jurisdiction. In Canada, this furnace must be installed in accordance with the current CAN/CGA-B149.1 & 2 Gas Installation Codes, local plumbing or waste water codes and other applicable codes. Additional helpful publications available from the NFPA are, NFPA 90A - Installation of Air Conditioning and Ventilating System and NFPA 90B - Warm Air Heating and Air Conditioning System.
All venting shall be in accordance with PART 7, Venting of Equip- ment, of the National Fuel Gas Code, ANSI Z223.1, or appli- cable local building and/or air conditioning codes. These pub- lications are available from:
National Fire Protection Association, Inc.
1 Batterymarch Park, Quincy, MA 02269
chlorinated waxes or cleaners chlorine-based swimming pool chemicals
water softening chemicals deicing salts or chemicals
carbon tetrachloride halogen type refrigerants cleaning solutions (such as perchloroethylene)
Your unit model type determines which installation procedures must be used. For *MH8, *MS8, and GHS8 models, you must follow instructions for Horizontal Left, Horizontal Right or Up- flow installations only. These furnaces are not approved for Downflow installations. Downflow models GD(H,S) ARE NOT APPROVED FOR HORI- ZONTAL OR UPFLOW INSTALLATIONS. For these models, use only the instructions for downflow installation only.
printing inks paint removers
varnishes hydrochloric acid cements and glues antistatic fabric softeners for clothes dryers
PERSONAL INJURY OR DEATH , THE FOLLOWING BULLET POINTS MUST BE
OBSERVED WHEN INSTALLING THIS UNIT.
Follow the instructions listed below when selecting a furnace location. Refer also to the guidelines provided in Section V, Combustion and Ventilation Air Requirements.

VENT SIDES FRONT BACK
1" 6" 1" 3" 0" 1"
An upflow furnace may be installed in an upright position or horizontal on either the left or right side panel. Do not install this furnace on its back. For vertically installed upflow furnaces, return air ductwork may be attached to the side panel(s) and/ or basepan. For horizontally installed upflow furnaces, return air ductwork must be attached to the basepan. For counterflow furnaces, return ductwork must be attached to the top end of the blower compartment.
Line contact to framing is permitted when installed in the hori- zontal configuration. Line contact is defined as the portion of the cabinet that is formed by the intersection of the top and side. ACCESSIBILITY CLEARANCE, WHERE GREATER, SHOULD TAKE PRECEDENCE OVER MINIMUM FIRE PRO- TECTION CLEARANCE. A gas-fired furnace for installation in a residential garage must be installed so that the ignition source and burners are located not less than eighteen inches (18") above the floor and is protected or located to prevent physical damage by vehicles. A gas furnace must not be installed di- rectly on carpeting, tile, or other combustible materials other than wood flooring.
Vent Pipe Clearance to Combustibles- 6" using Single Wall Connector or 1" using B-1 vent.

FURNACE SUSPENSION If suspending the furnace from rafters or joist, use 3/8" threaded rod and 2”x2”x3/8” angle iron as shown below. The length of rod will depend on the application and the clearances neces- sary.

Unobstructed front clearance of 24" for servicing is recom- mended.
Suspended Furnace

COMBUSTION & VENTILATION CATEGORY I VENTING AIR REQUIREMENTS
The following vent testing procedure is reproduced from the American National Standard/National Standard of Canada for Gas-Fired Central Furnaces ANSI Z21.47-Latest Edi- tion, CSA-2.3-Latest Edition Section 1.23.1. The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation:

a. Seal any unused openings in the venting system; b. Inspect the venting system for proper size and horizontal pitch, as required by the National Fuel Gas Code, ANSI Z223.1 or the CAN/CSA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition; c. In so far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers; d. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so appliance shall operate continuously; e. Test for draft hood equipped appliance spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle; f. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use; g. If improper venting is observed during any of the above tests, the common venting system must be corrected.
Consult the instructions packaged with the thermostat for mount- ing instructions and further precautions.

SUFFICIENT FRESH AIR FOR PROPER COMBUSTION AND VENTILATION OF
FLUE GASES MUST BE SUPPLIED. MOST HOMES REQUIRE OUTSIDE AIR BE
Improved construction and additional insulation in buildings have reduced heat loss by reducing air infiltration and escape around doors and windows. These changes have helped in reducing heating/cooling costs but have created a problem supplying combustion and ventilation air for gas fired and other fuel burn- ing appliances. Appliances that pull air out of the house (clothes dryers, exhaust fans, fireplaces, etc.) increase the problem by starving appliances for air.
Corrections must be in accordance with the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1 and/or CAN/ CSA B149 Installation Codes.
If resizing is required on any portion of the venting system, use the appropriate table in Appendix G in the latest edition of the National Fuel Gas Code ANSI Z223.1 and/or CAN/CSA B149 Installation Codes.
House depressurization can cause back drafting or improper combustion of gas-fired appliances, thereby exposing building occupants to gas combustion products that could include car- bon monoxide.
If this furnace is to be installed in the same space with other gas appliances, such as a water heater, ensure there is an adequate supply of combustion and ventilation air for the other appliances. Refer to the latest edition of the National Fuel Gas
In an area having good air circulation, locate the thermostat about five feet high on a vibration-free inside wall. Do not install the thermostat where it may be influenced by any of the follow- ing:
Thermostat Influences

EXTERIOR MASONRY CHIMNEYS - CATEGORY I FURNACES ONLY
Code NFPA 54/ANSI Z223.1 or CAN/CSA B149 Installation Codes or applicable provisions of the local building codes for determining the combustion air requirements for the appliances.
Under some conditions, larger vents than those shown above may be required or allowed. When an existing furnace is re- moved from a venting system serving other appliances, the venting system may be too large to properly vent the remaining attached appliances.
This furnace must use indoor air for combustion. It cannot be installed as a direct vent (i.e., sealed combustion) furnace.
Upflow or Horizontal units are shipped with the induced draft blower discharging from the top of the furnace. (“Top” is as viewed for an upflow installation.) The induced draft blower can be rotated 90 degrees with the (0270F01119) chimney transi- tion bottom kit for Category I venting. For horizontal installa- tions, a four inch single wall pipe can be used to extend the induced draft blower outlet 1/2” beyond the furnace cabinet. THIS PRODUCT IS NOT DESIGNED FOR COUNTERCLOCK- WISE INDUCED DRAFT BLOWER ROTATION.
Most homes will require outside air be supplied to the furnace area by means of ventilation grilles or ducts connecting directly to the outdoors or spaces open to the outdoors such as attics or crawl spaces.
Vent the furnace in accordance with the National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition. In Canada, vent the furnace in accordance with the National Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 - latest editions and amendments.
ASPHYXIATION, THIS FURNACE MUST BE CATEGORY I VENTED. DO NOT
VENT USING CATEGORY III VENTING.
Category I Venting is venting at a non-positive pressure. A furnace vented as Category I is considered a fan-assisted ap- pliance and the vent system does not have to be “gas tight.” NOTE: Single stage gas furnaces with induced draft blowers draw products of combustion through a heat exchanger allow- ing, in some instances, common venting with natural draft ap- pliances (i.e. water heaters). All installations must be vented in accordance with National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition. In Canada, the furnaces must be vented in ac- cordance with the National Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 - latest editions and amendments.
THIS FURNACE IS NOT DESIGN CERTIFIED TO BE HORI- ZONTALLY VENTED THROUGH AN EXTERIOR SIDE WALL.
The following describes an optional venting procedure when the furnace is installed in the horizontal left discharge position.
To rotate the induced draft blower clockwise, you will need to purchase one (0270F01119) chimney transition bottom kit.
1. Disconnect electrical power from the furnace. 2. Disconnect the induced draft blower power leads, flue pipe, and pressure switch tubing. 3. Remove the round cutout from the right side of the wrapper. 4. Remove and save the four screws that fasten the induced draft blower to the flue collector box. 5. Remove and save the three screws that hold the chimney assembly to the induced draft blower. 6. Remove and save the four screws that fasten the chimney top to the chimney bottom. 7. Remove the chimney transition bottom from the transition bottom kit. 8. Install the chimney top with the four screws retained from step 6 onto the new chimney transition bottom from the transition bottom kit. 9. Remove the induced draft blower and install the new chimney assembly to it using the three screws retained from step 5. 10. Rotate the induced draft blower 90 degrees to the right, feed the flue pipe through the round cutout from the outside of the wrapper, and fit onto the chimney top assembly. Secure the pipe to the chimney top from the front, top, and bottom using (3) screws and rotating the induced
ASPHYXIATION , COMMON VENTING WITH OTHER MANUFACTURER ’ S
INDUCED DRAFT APPLIANCES IS NOT ALLOWED.
The minimum vent diameter for the Category I venting system is as shown:

EXTERIOR MASONRY CHIMNEYS - CATEGORY I FURNACES ONLY
draft blower to properly orient the assembly. NOTE: If the pipe section is less than 18”, then attach it directly to the chimney top on 3 sides and feed it through the round cutout from the inside of the wrapper. 11. Reattach the induced draft blower using the (4) screws retained from step 3. Ensure the gasket located between the induced draft blower and collector box is rotated accordingly. 12. Reconnect the induced draft blower power leads. NOTE: If the wires are not long enough, pull extra wire from the wire bundle in the blower compartment. 13. Reconnect the remaining flue pipe, and the pressure switch tubing. Ensure that all wires and the pressure switch tubing is at least one inch from the flue pipe, or any other hot surface. 14. Restore power to furnace. NOTE: In a horizontal installation the air conditioning coil must be adequately supported by proper brackets and supports. Inadequate coil support can result in furnace cabinet distortion and air leakage.
DAMAGING CONDENSATION CAN OCCUR INSIDE MASONRY CHIMNEYS
WHEN A SINGLE FAN ‐ ASSISTED C ATEGORY I APPLIANCE (80% AFUE
FURNACE ) IS VENTED WITHOUT ADEQUATE DILUTION AIR . D O NOT
CONNECT AN 80% FURNACE TO A MASONRY CHIMNEY UNLESS THE
FURNACE IS COMMON VENTED WITH A DRAFT HOOD EQUIPPED
APPLIANCE OR THE CHIMNEY IS LINED WITH A METAL LINER OR TYPE B
SIZED IN ACCORDANCE WITH THE APPROPRIATE VENTING TABLES. IF AN 80% FURNACE IS COMMON VENTED WITH A DRAFT HOOD EQUIPPED
EXIST WITH EXTREMELY COLD CONDITIONS , LONG VENT CONNECTORS ,
EXTERIOR CHIMNEYS, OR ANY COMBINATION OF THESE CONDITIONS. THE RISK OF CONDENSATION DAMAGE IS BEST AVOIDED BY USING
OR TYPE B METAL VENT.
Counterflow units are shipped with the induced draft blower discharging from the top of the furnace. (“Top” as viewed for a counterflow installation.)
(Each x 24" Length)
Vent the furnace in accordance with the National Fuel Gas Code NFPA54/ANSI Z223.1-latest edition. In Canada, vent the furnace in accordance with the national standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2- latest editions and amendments.
1/2" to 1" Air Space
Water Heater Vent Connector
F.A.F. Vent Connector
SUPPLY.
Natural Draft Water Heater
Fan Assisted Forced Air Furnace
EXTERIOR MASONRY CHIMNEYS (CATEGORY I FURNACES ONLY)
Typical Multiple Flue Clay Tile Chimney
An exterior masonry chimney is defined as a “Masonry” chim- ney exposed to the outdoors on one or more sides below the roof line.” The ability to use a clay lined masonry chimney depends on a parameter not associated with interior chimneys. This variable is the geographic location of the installation. Re- searchers have discovered that the winter design temperatures have a direct impact on the suitability of this type of venting. In most situations, the existing masonry chimneys will require a properly sized metallic liner.
This checklist serves as a summary of the items to be checked before venting an 80+ furnace into a masonry chimney. In addi- tion, we recommend that a qualified serviceman use this check- list to perform a yearly inspection of the furnace venting sys- tem.
This checklist is only a summary. For detailed information on each of the procedures mentioned, see the paragraph refer- enced with each item.
This inspection is based upon a draft topical report, “Masonry Chimney Inspection and Relining”, issued by the Gas Research Institute. While not yet finalized, we believe this report repre- sents the best information on this subject which is currently available.

EXTERIOR MASONRY CHIMNEYS - CATEGORY I FURNACES ONLY

If the chimney does not meet these termination requirements, but all other requirements in the checklist can be met, it may be possible for a mason to extend the chimney. If this will not be practical, see Fix 1.
Termination 10 Feet Or Less From Ridge, Wall or Parapet
Height above any roof surface within 10 feet horizontally. Ridge
CHECK 1 - PROPER CHIMNEY TERMINATION.
A masonry chimney used as a vent for gas fired equipment must extend at least three feet above the highest point where it passes through the roof. It must extend at least two feet higher than any portion of a building within a horizontal distance of 10 feet. In addition, the chimney must terminate at least 3 feet above any forced air inlet located within 10 feet. The chimney must extend at least five feet above the highest connected equip- ment draft hood outlet or flue collar.
Termination More Than 10 Feet From Ridge, Wall or Parapet CHECK 2 - ANY SOLID OR LIQUID FUEL APPLIANCES VENTED
Solid fuel appliances include fireplaces, wood stoves, coal fur- naces, and incinerators.

EXTERIOR MASONRY CHIMNEYS - CATEGORY I FURNACES ONLY
Liquid fuel appliances include oil furnaces, oil-fired boilers and oil-fired water heaters.
Next, use a flashlight and small mirror to sight up the liner. B vent must be supported so as to not come into direct contact with the chimney walls or tile liner. If it is not, it can probably be rehung so as to be acceptable. A thimble or fire stop may be helpful here.
Appliances which burn propane (sometimes referred to as LP (liquefied petroleum)) gas are considered gas-fired appliances.
CHECK 3 - CHIMNEY CROWN CONDITION.
Flexible liners should be hung straight or nearly straight. If it is spiraled in the chimney and in good condition, it should be rehung. To do this, break the top seal; pull up and cut off the excess liner length, and refit the top seal. Use caution when doing this, as the cut edges of flexible liners may be sharp.
Damage from condensate usually shows up first in the crown. If any of the following trouble signs are present, the condition of the crown is not satisfactory:
a) Crown leaning b) Bricks missing c) Mortar missing d) Tile liner cracked e) No tile liner f) Salt staining at mortar joints. (White stains, and mortar becomes sandy and/or erodes.)
The surfaces of the liner must be physically sound. If gaps or holes are present, the metal liner must be removed and re- placed (Fix 4). Finally, confirm that the metal liner is the cor- rect size for the appliances to be installed. Use the GAMA tables and rules.
If a metal liner is not present, a clay tile liner must be present, or the chimney must be lined (Fix 4).
For problems a, b, or c, see Fix 3. If problems d, e, or f are present, see Fix 4. IMPORTANT: It may be necessary to follow both Fix 3 and Fix 4.
Use a flashlight and small mirror at the cleanout or vent con- nector to inspect the clay tile liner. If any of the following prob- lems are present:
A cleanout (dropleg) must be present such that the upper edge of the cleanout cover is at least 12 inches below the lower edge of the lowest chimney inlet opening.
A chimney without a cleanout could become partially blocked by debris. If no cleanout is present, the chimney must be re- lined (Fix 4). Remove the cleanout cover, and examine the cleanout for debris. If significant amounts of any of the following are found:
Next, measure the size of the liner. It may be possible to do this from the cleanout. The liner must be at least as large as the minimum size established by the tables in National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition and in the National Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 - latest editions and amendments. If the liner is too small or too large, then the chimney must be relined (Fix 4).
CHECK 5 - LINER CONDITION. If a metal liner is present, it must be checked. It cannot be assumed that all existing metal liners are correctly installed and in good condition.
CHECK 6 - DILUTION AIR.
If gas-fired appliances are to be vented into a clay tile liner, a source of dilution air is required.
Remove the lowest existing vent connector, and examine the inside of the elbow or tee at the base of the liner. A small amount of soot may be considered acceptable, provided the installer vacuums it away. If rusted pieces of the liner have collected here, the metal liner must be removed and replaced (Fix 4).
Dilution air cannot be obtained through:
Sufficient dilution air can ordinarily be obtained through the draft hood of a natural draft appliance only if the appliance’s vent connector does not include a vent damper. If dilution air will not be available, the chimney must be relined (Fix 4).
Next, gently tap the inside of the liner with a Phillips screw- driver. If the screwdriver perforates the liner, or if the tapping does not sound like metal hitting metal, the liner must be re- moved and replaced (Fix 4).
Remember that all appliances must be vented inside the liner. Venting one appliance inside the liner and another appliance outside the liner is not acceptable.

EXTERIOR MASONRY CHIMNEYS - CATEGORY I FURNACES ONLY
CHECK 7 - COMPLETE THE INSTALLATION.
If Checks 1 through 6 have been satisfactory, and the liner is an acceptable size as determined by the tables in National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition and in the National Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 - latest editions and amendments, then the clay tile liner can probably be used as a vent for the gas appliances. However, the installer must keep in mind the following factors which may render the tile liner unsuitable for use as a vent:
If the chimney crown is damaged, a qualified mason must re- pair it in accordance with nationally recognized building codes or standards. One such standard which may be referenced is the Standard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances, ANSI/NFPA 211.
Relining options include B vent and flexible liners.
If the chimney has diagonal offsets, B vent probably cannot be used.
If B vent is to be used, it must be supported adequately. Sup- ports (such as fire stops or thimbles) must be used to prevent the B vent from coming into direct contact with the tile liner or chimney walls. Direct contact would result in higher heat loss, with an increased possibility of poor venting system perfor- mance.
It is not acceptable to vent one appliance inside the B vent and other appliances outside. The excess space between the B vent and the chimney walls must be covered at the top of the chimney by a weatherproof, corrosion resistant flashing.
If, in the judgment of the local gas utility, installer, and/or local codes; one or more of the above factors is likely to present a problem, the chimney must be relined (Fix 4).
The B vent should then be topped with a listed vent cap. The listed vent cap will, when installed per the manufacturer’s in- structions, prevent problems due to rain, birds, or wind effects.
Any cap or roof assembly used with a liner must be approved by the liner manufacturer for such use. The liner and cap/roof assembly must then terminate above the roof in accordance with the manufacturer’s instructions.
A B-vent installed as described in this section is considered to be an enclosed vent system, and the sizing tables in National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition and in the National Standard of Canada, CAN/CSA B149.1 and CAN/ CSA B149.2 - latest editions and amendments may be used.
In some cases, a shorter extension above the roof may be possible with a liner than would be required with a masonry chimney.
If a flexible liner is to be used, it must be made of the proper materials:
For further information on relining, see Fix 4.
If the masonry chimney has more than one channel, it may be possible to vent the gas appliances into one channel and vent the solid or liquid fuel appliance(s) into another channel(s). Do not vent an 80+ Furnace inside of a metal liner with other appli- ances vented outside the liner.
Alternatively, the homeowner may agree to discontinue use of the fireplace (solid fuel appliance). If so, the tile liner must be cleaned to remove creosote buildup. The fireplace opening must then be permanently sealed.
If oil-fired appliance(s) are being replaced by gas-fired appliance(s), the tile liner must first be cleaned to remove the fuel oil residue.
If none of the above options is practical, the furnace may need to be vented vertically with a B Vent.
Under some conditions, a 90%+ furnace could be installed rather than an 80% furnace. The 90%+ furnace can be vented hori- zontally or vertically through PVC pipe.

For sizing of flexible liners, see Note 22 and the tables in the National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition and in the National Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 - latest editions and amendments.
L ABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING
CONTROLS . W IRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS
OPERATION. VERIFY PROPER OPERATION AFTER SERVICING.
To install the liner, read and follow the liner manufacturer’s in- structions and your local codes. Excess liner length should be pulled out of the chimney and cut off. Use caution when doing this, as the cut edges of flexible liners may be sharp. Do not spiral excess liner inside of the chimney. Support the liner as recommended by the liner manufacturer.
HIGH VOLTAGE ! TO AVOID THE RISK OF INJURY, ELECTRICAL SHOCK OR
Some manufacturers of flexible liners offer an insulation sleeve designed to be added to the liner before it is installed in the chimney. (Poured insulation, either vermiculite or other materi- als, is no longer recommended.) Insulation will need to be added to the flexible liner if:
THEIR ABSENCE, WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC CODE.
The wiring harness is an integral part of this furnace. Field alteration to comply with electrical codes should not be re- quired. Wires are color coded for identification purposes. Re- fer to the wiring diagram for wire routings. If any of the original wire as supplied with the furnace must be replaced, it must be replaced with wiring material having a temperature rating of at least 105° C. Any replacement wiring must be a copper con- ductor.
Even if none of those three conditions exist which require addi- tional liner insulation, the installer may wish to consider it if:
Before proceeding with electrical connections, ensure that the supply voltage, frequency, and phase correspond to that speci- fied on the unit rating plate. Power supply to the furnace must be NEC Class 1, and must comply with all applicable codes. The furnace must be electrically grounded in accordance with local codes or, in their absence, with the latest edition of The National Electric Code, ANSI NFPA 70 and/or The Canadian Electric Code CSA C22.1.
Insulation must be selected and installed in accordance with the liner manufacturer’s instructions.
Finally, cap the chimney and terminate the liner in accordance with the liner manufacturer’s instructions.
Use a separate fused branch electrical circuit containing prop- erly sized wire, and fuse or circuit breaker. The fuse or circuit breaker must be sized in accordance with the maximum over- current protection specified on the unit rating plate. An electri- cal disconnect must be provided at the furnace location.

HIGH VOLTAGE ! TO AVOID THE RISK OF ELECTRICAL SHOCK, WIRING TO
Line voltage wiring must enter into the junction box provided with the furnace.
This furnace can be used in conjunction with a heat pump in a fossil fuel application. A fossil fuel application refers to a com- bined gas furnace and heat pump installation which uses an outdoor temperature sensor to determine the most cost effi- cient means of heating (heat pump, gas furnace, or both).

A heat pump thermostat with two stages of heat is required to properly use a furnace in conjunction with a heat pump. Refer to the fossil fuel kit installation instructions for additional ther- mostat requirements.
HIGH VOLTAGE ! TO AVOID THE RISK OF INJURY, ELECTRICAL SHOCK OR
Strictly follow the wiring guidelines in the fossil fuel kit installa- tion instructions. All furnace connections must be made to the furnace integrated control module and the FURNACE terminal strip on the fossil fuel control board.
THEIR ABSENCE, WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC CODE.
To ensure proper unit grounding, the ground wire should run from the furnace ground screw located inside the furnace junc- tion box all the way back to the electrical panel. NOTE: Do not use gas piping as an electrical ground. To confirm proper unit grounding, turn off the electrical power and perform the following check.
EDGES OF SHEET METAL HOLES MAY BE SHARP. USE GLOVES AS A
PRECAUTION WHEN REMOVING HOLE PLUGS.
Line voltage connections can be made through either the right or left side panel. The furnace is shipped configured for a right side electrical connection. To make electrical connections through the opposite side of the furnace, the junction box must be relocated to the left side prior to making electrical connec- tions. To relocate the junction box, perform the following steps.
This furnace is equipped with a blower door interlock switch which interrupts unit voltage when the blower door is opened for servicing. Do not defeat this switch.

Low voltage connections can be made through either the right or left side panel. Thermostat wiring entrance holes are located in the blower compartment. The following figure shows con- nections for a “heat only” system and “heat/cool system”.
1. Remove both doors from the furnace. 2. Remove and save the screws holding the junction box to the right side of the furnace. 3. Models that have the junction box located in the burner compartment will need to move the junction box directly over. 4. Attach the junction box to the left side of the furnace, using the screws removed in step 2. 5. Check the location of the wiring. Confirm that it will not be damaged by heat from the burners or by the rotation of the fan. Also confirm that wiring location will not interfere with filter removal or other maintenance.
Typical Field Wiring (24 VAC Control Circuit)
After the junction box is in the desired location, use washers to connect field-supplied conduit to the junction box in accordance with NEC and local codes. Connect hot, neutral, and ground wires as shown in the furnace wiring diagram. The wires and ground screw are located in the furnace junction box.
This furnace is equipped with a 40 VA transformer to facilitate use with most cooling equipment. Consult the wiring diagram, located on the blower compartment door, for further details of 115 Volt and 24 Volt wiring.
A single-stage thermostat with only one heating stage can be used to control this furnace.
Low voltage wires may be connected to the terminal strip.
The GME8 model furnaces may be used with a 2-stage outdoor air conditioner. A two stage cooling/single stage gas heat thermostat is required, in addition to a field supplied relay. The relay must have a 24VAC coil and contacts rated for up to 1 horse power at 125VAC.

1. Install the field supplied relay on the control mount- ing panel near the furnace ignition control. The relay should be installed such that the motor leads will reach the relay contact terminals. 2. Connect the “Y2” (high stage cool) thermostat terminal to one coil terminal of the field supplied relay. Connect the other field supplied relay coil terminal to the “C” terminal on the furnace ignition control. Typical 18AWG thermostat wire may be used. 3. Connect the common terminal of the field supplied relay to the “LINE-H” terminal on the furnace ignition control. Use wiring having copper conductors only and a temperature rating of at least 105°C. 4. Using the GME8 airflow tables in this manual, determine the motor speed tap needed to deliver the required high stage cooling airflow. Connect the selected motor speed tap to the normally open terminal on the field supplied relay. Use wiring having copper conductors only and a temperature rating of at least 105°C. 5. See the wiring schematic below.
Example: If the reading on the ammeter is “4”, divide this by 10. The anticipator setting will be .4 amps.
(E LECTRONIC A IR C LEANER )

The furnace integrated control module is equipped with line voltage accessory terminals for controlling power to an optional field-supplied electronic air cleaner.

The accessory load specifications are as follows:
Electronic Air Cleaner 1.0 Amp maximum at 120 VAC
Turn OFF power to the furnace before installing any accesso- ries. Follow the air cleaner manufacturers’ instructions for lo- cating, mounting, grounding, and controlling these accesso- ries. Accessory wiring connections are to be made through the 1/4" quick connect terminals provided on the furnace inte- grated control module. The electronic air cleaner hot terminal is identified as EAC-H and the neutral terminal is identified as NEUTRAL. All field wiring must conform to applicable codes. Connections should be made as shown in the following illustra- tion.

S ETTING THE H EAT A NTICIPATOR
The following method should be used in measuring the amp draw of the control circuit to assure proper adjustment of the thermostat heat anticipator
If it is necessary for the installer to supply additional line volt- age wiring to the inside of the furnace, the wiring must conform to all local codes, and have a minimum temperature rating of 105°C. All line voltage wire splices must be made inside the furnace junction box.
The integrated control module electronic air cleaner terminals (EAC) are energized with 115 volts whenever the circulator blower is energized.

24 VAC HUMIDIFIER The yellow wire connected to the I.D. Blower pressure switch is powered anytime the pressure switch is closed and provides 24 VAC humidifier control. Remove the yellow wire and connect the supplied brown jumper wire to the pressure switch terminal. Reconnect the yellow wire to the “piggyback” terminal on the brown jumper and then connect the 24 VAC line of the humidifier to the stripped end of the brown wire. Using a wire nut or a field-supplied quick connect terminal can make this connection. The wiring must conform to all local and national codes. Connect the COM side of the humidifier to the B/C terminal on the furnace control board (or to the COM side of the 24 VAC transformer). DO NOT CONNECT 115V HUMIDIFIER TO THESE TERMINALS.
High altitude installations may require both a pressure switch and an orifice change. These changes are necessary to com- pensate for the natural reduction in the density of both the gas fuel and the combustion air at higher altitude.
For installations above 7000 feet, please refer to your distribu- tor for required kit(s).
Contact the distributor for a tabular listing of appropriate manufacturer’s kits for propane gas and/or high altitude instal- lations. The indicated kits must be used to insure safe and proper furnace operation. All conversions must be performed by a qualified installer, or service agency.
G AS S UPPLY AND P IPING
The furnace rating plate includes the approved furnace gas in- put rating and gas types. The furnace must be equipped to operate on the type of gas applied. This includes any conver- sion kits required for alternate fuels and/or high altitude.
OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED . T HE
APPROPRIATE KITS MUST BE APPLIED TO ENSURE SAFE AND PROPER
FURNACE OPERATION . A LL CONVERSIONS MUST BE PERFORMED BY A
CAUTION
QUALIFIED INSTALLER OR SERVICE AGENCY.
This unit is configured for natural gas. The appropriate manufacturer’s propane gas conversion kit, must be applied for propane gas installations. Refer to the “Propane Gas and/or High Altitude Installations” section for details.
INLET GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT
RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES
OPERATING.
Inlet gas supply pressures must be maintained within the ranges specified in the following table. The supply pressure must be constant and available with all other household gas fired appli- ances operating. The minimum gas supply pressure must be maintained to prevent unreliable ignition. The maximum must not be exceeded to prevent unit overfiring.
Altitude Gas Kit Orifice Manifold Pressure
Inlet Gas Supply Pressure
Natural None #45 3.5" w.c.
Natural Gas Minimum: 5.0" w.c. Maximum:10.0" w.c. Propane Gas Minimum: 11.0" w.c. Maximum:13.0" w.c.
#55 10.0" w.c.
NOTE: Adjusting the minimum supply pressure below the limits in the above table could lead to unreliable ignition. Gas input to the burners must not exceed the rated input shown on the rating plate. Overfiring of the furnace can result in premature heat exchanger failure. Gas pressures in excess of 13 inches water column can also cause permanent damage to the gas valve.
At all altitudes, the manifold pressure must be within 0.3 inches w.c. of that listed in the Specification Sheet applicable to your model for the fuel used. At all altitudes and with either fuel, the air temperature rise must be within the range listed on the fur- nace nameplate. Should this appliance be converted to LP, refer to the instructions included in the factory authorized LP conversion kit.
Gas Altitude Kit Orifice
Natural None #45 3.5" w.c. 1.9" w.c. None
Propane LPM-06 #55 10.0" w.c. 6.0" w.c. None 0-7000

Contact your distributor for a tabular listing of appropriate manufacturer’s kits for propane gas and/or high altitude instal- lations. The indicated kits must be used to insure safe and proper furnace operation. All conversions must be performed by a qualified installer, or service agency.

When sizing a trunk line, be sure to include all appliances which will operate simultaneously.
The gas piping supplying the furnace must be properly sized based on the gas flow required, specific gravity of the gas, and length of the run. The gas line installation must comply with local codes, or in their absence, with the latest edition of the National Fuel Gas Code, NFPA 54/ANSI Z223.1.
Aluminum alloy tubing must not be used in exterior locations. – Use listed gas appliance connectors in accordance
with their instructions. Connectors must be fully in the same room as the furnace. – Protect connectors and semi-rigid tubing against
Natural Gas Capacity of Pipe In Cubic Feet of Gas Per Hour (CFH) Length of Nominal Black Pipe Size Pipe in Feet 1/2" 3/4" 1" 1 1/4" 1 1/2" 10 132 278 520 1050 1600 20 92 190 350 730 1100 30 73 152 285 590 980 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490 100 38 79 150 305 460 (Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based on 0.60 Specific Gravity Gas)

physical and thermal damage when installed. Ensure aluminum-alloy tubing and connectors are coated to protect against external corrosion when in contact with masonry, plaster, or insulation, or subjected to repeated wetting by liquids such as water (except rain water), detergents, or sewage.
Location of Manual Valve

(Installed Ahead of Ground Joint Pipe Union)
CFH = BTUH Furnace Input Heating Value of Gas (BTU/Cubic Foot)
Ground Joint Pipe Union
To Be Installed Ahead of
To connect the furnace to the building’s gas piping, the installer must supply a ground joint union, drip leg, manual shutoff valve, and line and fittings to connect to gas valve. In some cases, the installer may also need to supply a transition piece from 1/ 2" pipe to a larger pipe size.
Reducing Coupling 1/2” x 1/8” with 1/8” Pipe Plug to Measure
The following stipulations apply when connecting gas piping.
U PFLOW I NSTALLATIONS
When the gas piping enters through the right side of the fur- nace, the installer must supply the following fittings (starting from the gas valve):

A ground joint union, drip leg, and manual shutoff valve must also be supplied by the installer. In some cases, the installer may also need to supply a transition piece from 1/2" to another pipe size.
This unit must be isolated from the gas supply system by clos- ing its manual shutoff valve before pressure testing of gas sup- ply piping system with test pressures equal to or less than 1/2 psig (3.48 kPa).
When the gas piping enters through the left side of the furnace, the installer must supply the following fittings (starting from the gas valve):

IF THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED
CONTACT A PROPANE SUPPLIER TO INSTALL A GAS DETECTING WARNING
SINCE PROPANE GAS IS HEAVIER THAN AIR, ANY LEAKING GAS CAN SETTLE IN ANY LOW AREAS OR CONFINED SPACES.
PROPANE GAS ODORANT MAY FADE, MAKING THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE.
When the gas piping enters through the left side of the furnace, the installer must supply a straight pipe to reach the exterior of the furnace.
A gas detecting warning system is the only reliable way to detect a propane gas leak. Rust can reduce the level of odorant in propane gas. Do not rely on your sense of smell. Contact a local propane gas supplier about installing a gas detecting warning system. If the presence of gas is suspected, follow the instructions on Page 3 of this manual.
A ground joint union, drip leg and manual shutoff valve must also be supplied by the installer. In most cases, the installer may also need to supply a transition piece from ½” to another pipe size. When the gas piping enters through the right side of the furnace, the installer must supply the following fittings (start- ing at the gas valve):
All propane gas equipment must conform to the safety stan- dards of the National Board of Fire Underwriters, NBFU Manual 58.
For satisfactory operation, propane gas pressure must be 10 inch WC at the furnace manifold with all gas appliances in operation. Maintaining proper gas pressure depends on three main factors:
Before placing unit in operation, leak test the unit and gas con- nections.
TO AVOID THE POSSIBILITY OF EXPLOSION OR FIRE, NEVER USE A MATCH
OR OPEN FLAME TO TEST FOR LEAKS.
Check for leaks using an approved chloride-free soap and wa- ter solution, an electronic combustible gas detector, or other approved testing methods.
Complete information regarding tank sizing for vaporization, rec- ommended regulator settings, and pipe sizing is available from most regulator manufacturers and propane gas suppliers.

Since propane gas will quickly dissolve white lead and most standard commercial compounds, special pipe dope must be used. Shellac-based compounds resistant to the actions of liquefied petroleum gases such as Gasolac®, Stalactic®, Clyde’s® or John Crane® are satisfactory.
Refer to the following illustration for typical propane gas instal- lations and piping.
Disconnect this unit and shutoff valve from the gas supply pip- ing system before pressure testing the supply piping system with pressures in excess of 1/2 psig (3.48 kPa).


A duct system must be installed in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air Conditioning, Warm Air Heating and Ventilating Systems. Pamphlets No. 90A and 90B.
A closed return duct system must be used, with the return duct connected to the furnace. NOTE: Ductwork must never be attached to the back of the furnace. For installations requiring more than 1800 CFM, use a bottom return or two sided return. Supply and return connections to the furnace may be made with flexible joints to reduce noise transmission. To prevent the blower from interfering with combustion air or draft when a cen- tral return is used, a connecting duct must be installed be- tween the unit and the utility room wall. Furnace is shipped with the top flanges in the flat position. Before installing a coil or ducts, the flanges must be bent 90°. A room, closet, or alcove must not be used as a return air chamber.
P ROPANE G AS P IPING C HARTS
Sizing Between First and Second Stage Regulator* Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting. Capacities in 1,000 BTU/hour.

Schedule 40 Tubing Size, O.D. Type L Pipe or Tubing Length,
When the furnace is used in connection with a cooling unit, the furnace should be installed in parallel with or on the upstream side of the cooling unit to avoid condensation in the heating element. With a parallel flow arrangement, the dampers or other means used to control the flow of air must be adequate to prevent chilled air from entering the furnace and, if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in the full heat or cool position.
10 730 1,700 3,200 5,300 8,300 3,200 7,500 20 500 1,100 2,200 3,700 5,800 2,200 4,200 30 400 920 2,000 2,900 4,700 1,800 4,000 40 370 850 1,700 2,700 4,100 1,600 3,700 50 330 770 1,500 2,400 3,700 1,500 3,400 60 300 700 1,300 2,200 3,300 1,300 310 80 260 610 1,200 1,900 2,900 1,200 2,600 100 220 540 1,000 1,700 2,600 1,000 2,300 125 200 490 900 1,400 2,300 900 2,100 150 190 430 830 1,300 2,100 830 1,900 175 170 400 780 1,200 1,900 770 1,700 200 160 380 730 1,100 1,800 720 1,500
When the furnace is installed without a cooling coil, it is rec- ommended that a removable access panel be provided in the outlet air duct. This opening shall be accessible when the fur- nace is installed and shall be of such a size that the heat exchanger can be viewed for visual light inspection or such that a sampling probe can be inserted into the airstream. The ac- cess panel must be made to prevent air leaks when the furnace is in operation.
Sizing Between Second Stage and Appliance Regulator* Maxim um Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting. Capacities in 1,000 BTU/hour.
Schedule 40 Tubing Size, O.D. Type L
3/8" 1/2" 5/8" 3/4" 7/8" 1-1/8" 1/2" 3/4" 1" 1-1/4" 1-1/2"
10 39 92 199 329 501 935 275 567 1,071 2,205 3,307 20 26 62 131 216 346 630 189 393 732 1,496 2,299 30 21 50 107 181 277 500 152 315 590 1,212 1,858 40 19 41 90 145 233 427 129 267 504 1,039 1,559 50 18 37 79 131 198 376 114 237 448 913 1,417 60 16 35 72 121 187 340 103 217 409 834 1,275 80 13 29 62 104 155 289 89 185 346 724 1,066 100 11 26 55 90 138 255 78 162 307 630 976 125 10 24 48 81 122 224 69 146 275 567 866 150 9 21 43 72 109 202 63 132 252 511 787 200 8 19 39 66 100 187 54 112 209 439 665 250 8 17 36 60 93 172 48 100 185 390 590
When the furnace is heating, the temperature of the return air entering the furnace must be between 55°F and 100°F.
When a furnace is installed so that supply ducts carry air cir- culated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct sealed to the furnace casing and terminating outside the space con- taining the furnace.

MONOXIDE , TO ENTER THE RETURN DUCT WORK OR CIRCULATION AIR
C HECKING D UCT S TATIC
Refer to your furnace rating plate for the maximum ESP (exter- nal duct static) rating.
Duct systems and register sizes must be properly designed for the CFM and external static pressure rating of the furnace. Ductwork should be designed in accordance with the recom- mended methods of “Air Conditioning Contractors of America” Manual D.
Total external static refers to everything external to the furnace cabinet. Cooling coils, filters, ducts, grilles, registers must all be considered when reading your total external static pres- sure. The supply duct pressure must be read between the fur-

nace and the cooling coil. This reading is usually taken by removing the “A” shaped block off plate from the end on the coil; drilling a test hole in it and reinstalling the block off plate. Take a duct static reading at the test hole. Tape up the test hole after your test is complete. The negative pressure must be read between the filter and the furnace blower.
FILTERS - READ THIS SECTION BEFORE INSTALLING THE RETURN AIR DUCTWORK
Filters must be used with this furnace. Discuss filter mainte- nance with the building owner. Filters do not ship with this furnace, but must be provided by the installer. Filters must com- ply with UL900 or CAN/ULCS111 standards. If the furnace is installed without filters, the warranty will be voided.
Too much external static pressure will result in insufficient air that can cause excessive temperature rise. This can cause limit switch tripping and heat exchanger failure.
To determine total external duct static pressure, proceed as follows;
Depending on the installation and/or customer preference, dif- fering filter arrangements can be applied. Filters can be in- stalled in the central return register or a side panel external filter rack kit (upflows), or the ductwork above a downflow fur- nace. As an alternative, a media air filter or electronic air cleaner can be used as the primary filter.
One of the most common causes of a problem in a forced air heating system is a blocked or dirty filter. Circulating air filters must be inspected monthly for dirt accumulation and replaced if necessary. Failure to maintain clean filters can cause prema- ture heat exchanger failure.
A new home may require more frequent replacement until all construction dust and dirt is removed. Circulating air filters are to be installed in the return air duct external to the furnace cabinet.
If the total external static pressure exceeds the maximum listed on the furnace rating plate, check for closed dampers, regis- ters, undersized and/or oversized poorly laid out duct work.


H ORIZONTAL I NSTALLATIONS
Filters must be installed in either the central return register or in the return air duct work.
Refer to Timing Charts for sequencing.
Checking Static Pressure (80% Furnace Shown, 90% Similar)

(M ODE DIP SWITCH IS SET TO “1 STG” POSITION )
The normal operational sequence in heating mode is as fol- lows:
The normal operational sequence in cooling mode is as fol- lows:
The normal operational sequence in sequence is as follows:

The normal operational sequence in fan only mode is as fol- lows:
Honeywell VR8215 or VR9205: Slide the switch to the OFF position.
White-Rodgers Model 36G22 or 36G54: Push the switch to the ON position.
Honeywell VR8215 or VR9205: Slide the switch to the ON position.
Furnace must have a 115 VAC power supply properly connected and grounded. Proper polarity must be maintained for correct operation. An interlock switch prevents furnace operation if the blower door is not in place. Keep the blower access door in place except for inspection and maintenance.
This furnace is also equipped with a self-diagnosing electronic control module. In the event a furnace component is not operat- ing properly, the control module LED will flash on and off in a factory-programmed sequence, depending on the problem en- countered. This light can be viewed through the observation window in the blower access door. Refer to the Troubleshoot- ing Chart for further explanation of the lighting codes.
Follow the start-up and adjustment items, refer to further infor- mation in Section XIII, Operational Checks (see table of con- tents, pages 2-3 for page number)..
Purge gas lines of air prior to start-up. Do not purge lines into an enclosed burner compartment.
Honeywell VR8215 or VR9205: Slide the switch to the OFF position.
Check for leaks using an approved chloride-free soap and wa- ter solution, an electronic combustible gas detector, or other approved method. Verify that all required kits (propane gas, high altitude, etc.) have been appropriately installed.
T O PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE , THE
INLET GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT
RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES
OPERATING.


4. Attach a hose and manometer to the outlet pressure barb fitting (Honeywell valve) or inlet pressure boss (White- Rodgers valve). 5. Turn ON the gas supply. 6. Turn On power and close thermostat “R” and “W” contacts to provide a call for heat. 7. Using a leak detection solution or soap suds, check for leaks at outlet pressure boss plug (Honeywell valve) or screw (White-Rodgers valve). Bubbles forming indicate a leak. SHUT OFF GAS AND REPAIR ALL LEAKS IMMEDIATELY! 8. Measure the gas supply pressure with burners firing. Adjust supply pressure using the Inlet Gas Supply Pressure table shown below. If supply pressure reading differs from the table, make necessary adjustments to pressure regulator, gas piping size, etc., and/or consult with local gas utility.
BE PRESENT . F AILURE TO DO SO MAY CAUSE PROPERTY
M ODELS USING S INGLE S TAGE G AS V ALVES
The line pressure supplied to the gas valve must be within the range specified below. The supply pressure can be measured at the gas valve inlet pressure tap or at a hose fitting installed in the gas piping drip leg. The supply pressure must be mea- sured with the unit OFF. To measure inlet pressure, use the following procedure.
Inlet Gas Supply Pressure

Minimum:5.0" W.C. Maximum :10.0" W.C. Minimum:11.0" W.C. Maximum :13.0" W.C.
Adjustment (Under Cap Screw)
Remove the 1/8” NPT hose barb fitting from the inlet pressure tap. Replace the inlet pressure boss plug and seal with a high quality thread sealer. b. White-Rodgers 36G22 valve:
Pressure Regulator (under cap screw)
Turn inlet pressure test screw in to seal pressure port (clockwise, 7 in-lb minimum). 12. Retest for leaks. If bubbles form, shut down gas and repair leaks immediately. 13. Turn ON electrical power and gas supply to the system. 14. Turn valve switch ON.


GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING
Honeywell Model VR8215 (Single-Stage)
PLATE . O NLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING
The line pressure supplied to the gas valve must be within the range specified below. The supply pressure can be measured at the gas valve inlet pressure boss or at a hose fitting installed in the gas piping drip leg. The supply pressure must be mea- sured with the burners operating. To measure the gas supply pressure, use the following procedure.
Remove the inlet pressure boss plug. Install an 1/8” NPT hose barb fitting into the outlet pressure tap. b. White-Rodgers 36G22 valve:
Back inlet pressure test screw (inlet pressure boss) out one turn (counterclockwise, not more than one turn).


High Fire Coil Terminal (HI) Coaxial Coil Terminal (M) Common Terminal(C)
NOTE: If measuring gas pressure at the drip leg or Honeywell VR9205 gas valve, a field-supplied hose barb fitting must be installed prior to making the hose connection. If using the inlet pressure boss on the White-Rodgers 36G54 gas valve, then use the 36G Valve Pressure Check Kit, Goodman Part No. 0151K00000S. 3. Turn ON the gas supply and operate the furnace and all other gas consuming appliances on the same gas supply line. 4. Measure furnace gas supply pressure with burners firing. Supply pressure must be within the range specified in the Inlet Gas Supply Pressure table.
High Fire Regulator Adjust

Gas Valve On/Off Selector Switch
Low Fire Regulator Adjust
Inlet Gas Supply Pressure
Natural Gas Minimum: 5.0" w.c. Maximum:10.0" w.c. Propane Gas Minimum: 11.0" w.c. Maximum:13.0" w.c.
If supply pressure differs from table, make the necessary ad- justments to pressure regulator, gas piping size, etc., and/or consult with local gas utility.
On/Off Switch

4. Attach a hose and manometer to the outlet pressure barb fitting (Honeywell valve) or outlet pressure boss (White-Rodgers valve). 5. Turn ON the gas supply. 6. Turn ON power and close thermostat “R” and “W” contacts to provide a call for heat. 7. Using a leak detection solution or soap suds, check for leaks at outlet pressure boss plug (Honeywell valve) or screw (White-Rodgers valve). Bubbles forming indicate a leak. SHUT OFF GAS AND REPAIR ALL LEAKS IMMEDIATELY! 8. Measure the gas manifold pressure with burners firing. Adjust manifold pressure using the Manifold Gas Pressure table shown below.
Gas Line To Furnace
Drip Leg Cap With Fitting
Manifold Gas Pressure Natural Gas 3.5" w.c. Propane Gas 10.0" w.c.

GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING
PLATE . O NLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING
Remove the 1/8” NPT hose barb fitting from the outlet pressure tap. Replace the outlet pressure boss plug and seal with a high quality thread sealer. b. White-Rodgers 36G22 valve: Turn outlet pressure test
screw in to seal pressure port (clockwise, 7 in-lb minimum). 13. Turn ON electrical power and gas supply to the system. 14. Close thermostat contacts to provide a call for heat. 15. Retest for leaks. If bubbles form, SHUT OFF GAS AND REPAIR ALL LEAKS IMMEDIATELY!
M ODELS USING S INGLE S TAGE G AS V ALVES
This valve is shipped from the factory with the regulator preset (see control label).
Consult the appliance rating plate to ensure burner manifold pressure is as specified. If another outlet pressure is required, follow these steps.

PLATE . O NLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING
Only small variations in gas pressure should be made by ad- justing the gas valve pressure regulator. The manifold pressure must be measured with the burners operating. To measure and adjust the manifold pressure, use the following procedure.
Remove the outlet pressure boss plug. Install an 1/8” NPT hose barb fitting into the outlet pressure tap. b. White-Rodgers 36G22 valve:
Back outlet pressure test screw (outlet pressure boss) out one turn (counterclockwise, not more than one turn).
Gas Line · Gas Shutoff Valve · Manometer Hose

GAS INPUT RATE MEASUREMENT (NATURAL GAS ONLY)
The gas input rate to the furnace must never be greater than that specified on the unit rating plate. To measure natural gas input using the gas meter, use the following procedure.
boss plug. Install an 1/8" NPT hose barb fitting into the outlet pressure tap. b. White-Rodgers 36G54 valve: Back outlet pressure test
1. Turn OFF the gas supply to all other gas-burning appliances except the furnace. 2. While the furnace is operating, time and record one complete revolution of the smallest gas meter dial. 3. Calculate the number of seconds per cubic foot (sec/ ft3) of gas being delivered to the furnace. If the dial is a one cubic foot dial, divide the number of seconds recorded in step 2 by one. If the dial is a two cubic foot dial, divide the number of seconds recorded in step 2 by two. 4. Calculate the furnace input in BTUs per hour (BTU/ hr). Input equals the installation’s gas heating value multiplied by a conversion factor (hours to seconds), divided by the number of seconds per cubic foot. The measured input must not be greater than the input indicated on the unit rating plate. EXAMPLE: Installation’s gas heating (HTG) value: 1,000 BTU/ft3
screw (inlet/outlet pressure boss) out one turn (counterclockwise, not more than one turn). 4. Attach a hose and manometer to the outlet pressure barb fitting (Honeywell valve) or outlet pressure boss (White-Rodgers valve). 5. Turn ON the gas supply. 6. Turn on power and close thermostat “R” and “W1” contacts to provide a call for low stage heat. 7. Measure the gas manifold pressure with burners firing. Adjust manifold pressure using the Manifold Gas Pressure table shown below. 8. Remove regulator cover screw from the low (LO) outlet pressure regulator adjust tower and turn screw clockwise to increase pressure or counterclockwise to decrease pressure. Replace regulator cover screw. 9. Close thermostat “R” and “W2” contacts to provide a call for high stage heat. 10. Remove regulator cover screw from the high (HI) outlet pressure regulator adjust tower and turn screw clockwise to increase pressure or counterclockwise to decrease pressure. Replace regulator cover screw. 11. Turn off all electrical power and gas supply to the system. 12. Remove the manometer hose from the hose barb fitting or outlet pressure boss. 13. Replace outlet pressure tap: a. Honeywell VR9205 valve: Remove the 1/8" NPT hose
(Obtained from gas supplier) Installation’s seconds per cubic foot: 34 sec/ ft3
Conversion Factor (hours to seconds): 3600 sec/hr Input = (Htg. value x 3600) ÷ seconds per cubic foot Input = (1,000 BTU/ft3 x 3600 sec/hr) ÷ 34 sec/ ft3
Input = 106,000 BTU/hr This measured input must not be greater than the input indicated on the unit rating plate. 5. Turn ON gas and relight appliances turned off in step 1. Ensure all the appliances are functioning properly and that all pilot burners are operating.
barb fitting from the outlet pressure tap. Replace the outlet pressure boss plug and seal with a high quality thread sealer. b. White-Rodgers 36G54 valve: Turn outlet pressure test
screw in to seal pressure port (clockwise, 7 in-lb minimum). 14. Turn on electrical power and gas supply to the system. 15. Close thermostat contacts “R” and “W1/W2” to energize the valve.
Air temperature rise is the temperature difference between supply and return air. The proper amount of temperature rise is usu- ally obtained when the unit is operated at the rated input with the “as shipped” blower speed. If the correct amount of tem- perature rise is not obtained, it may be necessary to change the blower speed.
Using a leak detection solution or soap suds, check for leaks at outlet pressure boss plug (Honeywell valve) or screw (White- Rodgers valve). Bubbles forming indicate a leak. SHUT OFF GAS AND REPAIR ALL LEAKS IMMEDIATELY! NOTE: For gas to gas conversion, consult your dealer for appropriate conversion.
An incorrect temperature rise can cause condensing in or over- heating of the heat exchanger. Determine and adjust the tem- perature rise as follows. The temperature rise must be within the range specified on the rating plate or Specification Sheet applicable to your model. (Please contact your distributor or our website for the applicable Specification Sheet referred to in this manual.)
Manifold Gas Pressure Gas
Range Nominal Natural Low Stage 1.6 - 2.2" w .c. 1.9" w .c. High Stage 3.2 - 3.8" w .c. 3.5" w .c. Propane Low Stage 5.7 - 6.3" w .c. 6.0" w .c. High Stage 9.7 - 10.3" w .c. 10.0" w .c.

3. Relocate desired motor leads to the circulator blower heat and cool speed terminals on the integrated control module. (Terminals are identified as LO HEAT, HI HEAT and COOL (hot)) for *(M,D)H8 models and HEAT and COOL for *(M,H,D)S8 models). If a heating speed and the cooling speed are the same, a jumper wire must be used between the heat and cool terminals. 4. Connect all unused blower motor leads to the “PARK” terminals on the integrated control module. Any leads not connected to the “PARK” terminals must be taped. 5. Turn ON power to furnace. 6. Verify proper temperature rise as outlined in Temperature Rise section.
RETURN AIR
Temperature Rise Measurement
C IRCULATOR B LOWER F AN T IMING A DJUSTMENT
1. Operate furnace with burners firing approximately 15 minutes. Ensure all registers are open and all duct dampers are in their final (fully or partially open) position. 2. Place thermometers in the return and supply ducts as close to the furnace as possible. Thermometers must not be influenced by radiant heat by being able to “see” the heat exchanger. 3. Subtract the return air temperature from the supply air temperature to determine the air temperature rise. Allow adequate time for thermometer readings to stabilize. 4. Adjust temperature rise by adjusting the circulator blower speed. Increase blower speed to reduce temperature rise. Decrease blower speed to increase temperature rise. Refer to the following section for speed changing details.
As shipped, the circulator blower fan will remain on for 150 seconds after the gas valve closes. When a call for cooling occurs, the circulator fan comes on and remains on for 45 sec- onds after the call for cooling ends. During normal heating op- eration, the circulator fan will come on approximately 34 sec- onds after the gas valve opens.
100 SECOND
ON
OFF
C IRCULATOR B LOWER S PEED A DJUSTMENT
ON
OFF
DELAY
DELAY
Switch viewed in an upflow installation.
Adjustment Switch
TURN OFF POWER TO THE FURNACE BEFORE CHANGING SPEED TAPS.
SETTING FURNACE OPERATING MODE (*DH8, *ME8, AND *MH8 MODELS ONLY) This furnace is designed to operate with either a single gas input rate or with two discrete gas input rates. The Mode DIP switch is used to select the single gas input rate or two discrete input rates.
This furnace is equipped with a PSC circulator blower motor. This blower provides ease in adjusting blower speeds. Refer to the Blower Performance Data in the back of the manual for proper selection of heating and cooling speeds. The cooling blower speed is shipped set on HIGH. High heat ships on MEDIUM and low heat is shipped on MEDIUM-LO. These blower speeds should be adjusted by the installer to match the instal- lation requirements so as to provide the correct heating tem- perature rise and the correct cooling CFM.
Setting the Mode switch to “1 STG” forces the furnace to operate at the furnace’s highest input rate only. Operation is as described under Sequence of Operation (Integrated Ignition Control) – Mode DIP Switch is set to “1 STG” position.
To adjust the circulator blower speed, proceed as follows:

Setting the Mode switch to “2 STG” allows the furnace to operate at the furnace’s highest input AND at an input rate that is 75% of the highest input rate. For this mode of operation, the furnace operates at the low input rate for a pre-determined time period then steps to the high input rate. Operation is as described under Sequence of Operation (Integrated Ignition Control) – Mode DIP Switch is set to “2 STG” position.
Auto reset limits are located on or near the blower. To access this auxiliary limit, disconnect the electrical power and remove the blower door. The auxiliary limit control is designed to pre- vent furnace operation in case of main blower failure on hori- zontal installations. It may also open if the power supply is interrupted while the furnace is firing. The auxiliary limit control is suitable for both horizontal right and horizontal left installa- tions. Regardless of airflow direction, it does not need to be relocated.
The time period is determined by the 2nd Stg Dly DIP switch. Setting the 2nd Stg Dly DIP switch to 5 minutes fixes the delay period at 5 minutes. Setting the 2nd Stg Dly DIP switch to Auto enables an algorithm that calculates a delay period based on the heating cycle time and the total cycle time. The delay period can range from 1 minute to 12 minutes.

INTERNAL COMPARTMENT COVERS OR ATTEMPT ANY ADJUSTMENT. ELECTRICAL COMPONENTS ARE CONTAINED IN BOTH COMPARTMENTS. CONTACT A QUALIFIED SERVICE AGENT AT ONCE IF AN ABNORMAL
2 STG M
1 STG
S AFETY C IRCUIT D ESCRIPTION
2 ND STG DLY
5 MIN
AUTO
G ENERAL
O PERATIONAL C HECKS
A number of safety circuits are employed to ensure safe and proper furnace operation. These circuits serve to control any potential safety hazards and serve as inputs in the monitoring and diagnosis of abnormal function. These circuits are con- tinuously monitored during furnace operation by the integrated control module.

TO AVOID PERSONAL INJURY OR DEATH, DO NOT REMOVE ANY INTERNAL
COMPONENTS ARE CONTAINED IN BOTH COMPARTMENTS. CONTACT A
QUALIFIED SERVICE AGENT AT ONCE IF AN ABNORMAL FLAME APPEARANCE
The integrated control module is an electronic device which controls all furnace operations. Responding to the thermostat, the module initiates and controls normal furnace operation, and monitors and addresses all safety circuits. If a potential safety concern is detected, the module will take the necessary pre- cautions and provide diagnostic information through an LED.
The burner flames should be inspected with the burner com- partment door installed. Flames should be stable, quiet, soft, and blue (dust may cause orange tips but they must not be yellow). Flames should extend directly outward from the burn- ers without curling, floating, or lifting off. Flames must not impinge on the sides of the heat exchanger firing tubes.
The primary limit control is located on the partition panel and monitors heat exchanger compartment temperatures. It is an automatic reset, temperature sensor. The limit guards against the overheating resulting from insufficient air passing over the heat exchanger.
Check the burner flames for: 1. Good adjustment 2. Stable, soft and blue 3. Not curling, floating, or lifting off.
The auxiliary limit control is located either on or near the circu- lator blower and monitors heat exchanger compartment tem- peratures. The control is an automatic reset, temperature sensor. It guards against overheating resulting from insufficient air passing over the heat exchanger.

D IAGNOSTIC C HART
The rollout limit controls are mounted on the burner/manifold assembly and monitor the burner flame. They are manual- reset, temperature sensors. This limit guards against burner flames not being properly drawn into the heat exchanger.
Refer to the troubleshooting chart in the Appendix for assis- tance in determining the source of unit operational problems. The red diagnostic LED blinks to assist in troubleshooting the unit. The number of blinks refer to a specific code.
The pressure switches are normally-open, negative air pres- sure-activated switches. They monitor the airflow (combustion air and flue products) through the heat exchanger via pressure taps located on the induced draft blower. These switches guard against insufficient airflow (combustion air and flue products) through the heat exchanger.
The ignition control is equipped with a momentary push button switch that can be used to display on the diagnostic LED the last five faults detected by the control. The control must be in Standby Mode (no thermostat inputs) to use the feature. De- press the pushbutton switch for approximately 2 seconds. Re- lease the switch when the LED is turned off. The diagnostic LED will then display the flash codes associated with the last five detected faults. The order of display is the most recent fault to the least recent fault.
The flame sensor is a probe mounted to the burner/manifold assembly which uses the principle of flame rectification to de- termine the presence or absence of flame.
T ROUBLESHOOTING
Furnace lockout results when a furnace is unable to achieve ignition after three attempts. It is characterized by a non-func- tioning furnace and a one flash diagnostic LED code from the red LED. If the furnace is in “lockout”, it will (or can be) reset in any of the following ways.
Use the following precautions during furnace installation and servicing to protect the integrated control module from dam- age. By putting the furnace, the control, and the person at the same electrostatic potential, these steps will help avoid expos- ing the integrated control module to electrostatic discharge. This procedure is applicable to both installed and uninstalled (ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch the integrated control module or any wire connected to the control prior to discharging your body’s electrostatic charge to ground. 2. Firmly touch a clean, unpainted, metal surface of the furnace away from the control. Any tools held in a person’s hand during grounding will be discharged. 3. Service integrated control module or connecting wiring following the discharge process in step 2. Use caution not to recharge your body with static electricity; (i.e., do not move or shuffle your feet, do not touch ungrounded objects, etc.). If you come in contact with an ungrounded object, repeat step 2 before touching control or wires. 4. Discharge your body to ground before removing a new control from its container. Follow steps 1 through 3 if installing the control on a furnace. Return any old or new controls to their containers before touching any ungrounded object.
ELECTRICAL POWER BEFORE PERFORMING ANY MAINTENANCE . I F YOU
MUST HANDLE THE IGNITER , HANDLE WITH CARE . T OUCHING THE
IGNITER ELEMENT WITH BARE FINGERS , ROUGH HANDLING , OR
VIBRATION COULD DAMAGE THE IGNITER RESULTING IN PREMATURE
FAILURE . O NLY A QUALIFIED SERVICER SHOULD EVER HANDLE THE
IGNITER.

F ILTER R EMOVAL
The furnace should be inspected by a qualified installer, or ser- vice agency at least once per year. This check should be per- formed at the beginning of the heating season. This will ensure that all furnace components are in proper working order and that the heating system functions appropriately. Pay particular attention to the following items. Repair or service as neces- sary.
Depending on the installation, differing filter arrangements can be applied. Filters can be installed in either the central return register or a side panel external filter rack (upflow only). A media air filter or electronic air cleaner can be used as an alter- nate filter. Follow the filter sizes given in the Recommended Minimum Filter size table or instruction provided by the media or electronic air cleaner manufacturer to ensure proper unit performance.
To remove filters from an external filter rack in an upright upflow installation, follow the directions provided with external filter rack kit. For further details, see your distributor.
The bearings in the induced draft blower and circulator blower motors are permanently lubricated by the manufacturer. No fur- ther lubrication is required. Check motor windings for accumu- lation of dust which may cause overheating. Clean as neces- sary.
F LAME S ENSOR (Q UALIFIED S ERVICER O NLY )
Under some conditions, the fuel or air supply can create a nearly invisible coating on the flame sensor. This coating acts as an insulator causing a drop in the flame sense signal. If the flame sense signal drops too low the furnace will not sense flame and will lock out. The flame sensor should be carefully cleaned by a qualified servicer using emery cloth or steel wool. Following cleaning, the flame sense signal should be 1 to 6 microamps at 115 volts.
DISCONNECT ELECTRICAL POWER BEFORE REMOVING FILTERS . N EVER
OPERATE FURNACE WITHOUT A FILTER INSTALLED BECAUSE DUST AND
LINT WILL BUILD UP ON INTERNAL PARTS RESULTING IN LOSS OF
EFFICIENCY, EQUIPMENT DAMAGE AND POSSIBLE FIRE.
A return air filter is not supplied with this furnace; however, there must be a means of filtering all of the return air. The in- staller will supply filter(s) at the time of installation.
F ILTER M AINTENANCE
If the igniter and the surrounding air are at about 70°F and the igniter wires are not connected to any other electrical compo- nents, the resistance of the igniter should not exceed 75 ohms. If it does, the igniter should be replaced.
Improper filter maintenance is the most common cause of in- adequate heating or cooling performance. Filters should be cleaned (permanent) or replaced (disposable) every two months or as required. When replacing a filter, it must be replaced with a filter of the same type and size.
HIGH VOLTAGE! T O PREVENT PROPERTY DAMAGE , PERSONAL INJURY OR
INTERNAL COMPARTMENT COVERS OR ATTEMPT ANY ADJUSTMENT. ELECTRICAL COMPONENTS ARE CONTAINED IN BOTH COMPARTMENTS. CONTACT A QUALIFIED SERVICE AGENT AT ONCE IF AN ABNORMAL
ELECTRICAL POWER TO THE FURNACE BEFORE
FLAME APPEARANCE SHOULD DEVELOP.
Periodically during the heating season, make a visual check of the burner flames. Turn the furnace on at the thermostat. Wait a few minutes, since any dislodged dust will alter the normal flame appearance. Flames should be stable, quiet, soft and blue with slightly orange tips. They should not be yellow. They should extend directly outward from the burner ports without curling downward, floating or lifting off the ports.
MAINTENANCE.
Become familiar with filter location and procedures for removal, cleaning and replacing them. If help is needed, contact the installer of the furnace or a qualified servicer.

C LEANING (Q UALIFIED S ERVICER O NLY )
R EPAIR AND R EPLACEMENT P ARTS
L ABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING
CONTROLS . W IRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS
OPERATION. VERIFY PROPER OPERATION AFTER SERVICING.
Gas Valve Blower/Collector Box Gasket Natural Gas Orifice Primary Limit Switch Propane Gas Orifice Rollout Limit Switch Burner Auxiliary Limit Switch Hot Surface Igniter Heat Exchanger Flame Sensor Door Switch Gas Manifold Transformer Ignition Control Blower Wheel Blower Mounting Bracket Blower Housing Pressure Switch Blower Cutoff Pressure Switch Hose Blower Motor Induced Draft Blower Motor Mount Bracket Collector Box Capacitor
THE IGNITER IS FRAGILE AND CAN BE EASILY DAMAGED. USE EXTREME


1 Tubular Heat Exchanger 2 Pressure Switch 3 Flue Pipe Connection 4 Induced Draft Blower 5 Gas Line Entrance 6 Gas Valve 7 Rollout Limit 8 Junction Box
9 Wiring Harness Grommet 10 Gas Manifold 11 Inshot Burner 12 Transformer 13 Integrated Control Module 14 Blower Door Interlock Switch 15 Circulator Blower 16 Gas Line Entrance (Alternate)


Flue Pipe Connection (Chimney Transition Top Shipped Loose)
1 Tubular Heat Exchanger 2 Pressure Switch 3 Flue Pipe Connection 4 Induced Draft Blower 5 Gas Line Entrance 6 Gas Valve 7 Rollout Limit 8 Junction Box
9 Wiring Harness Grommet 10 Gas Manifold 11 Inshot Burner 12 Transformer 13 Integrated Control Module 14 Blower Door Interlock Switch 15 Circulator Blower 16 Gas Line Entrance (Alternate)
Inshot Burner · Circulator Blower

Causes Fault Description(s) Symptoms of Abnormal Operation
1 Integrated control module will automatically attempt to reset from lockout after one hour.
2 LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.

& Notes Corrective Action Possible Causes Fault Description(s) Symptoms of Abnormal Operation
2 LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.

& Notes Corrective Action Possible Causes Fault Description(s) Symptoms of Abnormal Operation
2 LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.

*M(H/S)8
EXTERNAL STATIC PRESSURE (Inches Water Column)
at 0.5" 0.6 0.7 0.8
0.1 0.2 0.3 0.4 0.5
ESP CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM
HIGH 3.0 1521 1466 1414 1373 1298 1243 1164 1075
*M(H/S)80403A*** MED 2.5 1160 26 1160 26 1132 26 1121 26 1082 27 1042 997 925
(MEDIUM) MED-LO 2.0 961 31 955 31 948 31 932 32 913 33 882 821 803
LOW 1.5 781 38 785 38 781 38 773 38 761 32 745 716 668
HIGH 3.0 1422 31 1352 33 1307 34 1197 37 1157 38 1092 1075 983
*M(H/S)80603A*** MED 2.5 1098 40 1081 41 1051 42 1039 43 1021 44 983 924 868
(MEDIUM) MED-LO 2.0 919 48 913 49 892 50 847 829 818 792 728
LOW 1.5 758 741 741 733 699 677 649 626
HIGH 4.0 2134 21 2100 21 2042 22 1975 23 1883 24 1786 1700 1601
*M(H/S)80604B*** MED 3.5 1668 27 1663 27 1656 27 1645 27 1616 28 1549 1492 1391
(MEDIUM) MED-LO 3.0 1419 31 1426 31 1426 31 1432 31 1419 31 1378 1328 1261
LOW 2.5 1134 39 1145 39 1166 38 1171 38 1160 38 1144 1111 1071
HIGH 3.0 1607 37 1572 38 1547 39 1498 40 1448 41 1390 1302 1222
*M(H/S)80803B*** MED 2.5 1159 51 1156 51 1145 52 1127 53 1108 53 1075 1033 957
(MEDIUM) MED-LO 2.0 938 63 916 65 916 65 900 889 865 829 785
LOW 1.5 785 766 743 730 709 683 666 604
HIGH 4.0 2051 1983 1895 1812 1725 1627 1530 1439
*M(H/S)80804B*** MED 3.5 1736 1708 35 1652 36 1611 37 1540 38 1475 1394 1307
(MEDIUM) MED-LO 3.0 1693 35 1668 36 1459 41 1429 41 1389 43 1339 1274 1204
LOW 2.5 1200 49 1185 50 1180 50 1173 51 1158 51 1125 1125 1080
HIGH 5.0 2290 2229 2155 2047 1960 1837 1712 1584
*M(H/S)80805C*** MED 4.0 1852 1820 1777 1719 --- 1641 36 1567 1469 1382
(MEDIUM) MED-LO 3.5 1615 37 1592 37 1556 38 1516 39 1470 40 1405 1346 1235
LOW 3.0 1290 46 1285 46 1265 47 1235 48 1214 49 1174 1044 904
HIGH 5.0 2323 2225 2120 35 2040 36 1974 38 1801 1688 1577
*M(H/S)81005C*** MED 4.0 1858 40 1847 40 1799 41 1744 42 1674 44 1577 1493 1399
(MEDIUM) MED-LO 3.5 1596 46 1587 47 1571 47 1552 48 1493 50 1397 1326 1217
LOW 3.0 1291 57 1272 58 1261 59 1257 59 1205 61 1168 1118 1060
HIGH 5.0 2469 2389 2300 2223 40 2131 42 2027 1902 1786
*M(H/S)81205D*** MED 4.0 1575 56 1558 57 1545 58 1513 59 1500 59 1419 1354 1271
(MEDIUM) MED-LO 3.5 1402 63 1380 64 1343 66 1319 67 1296 69 1245 1183 1106
LOW 3.0 1200 1186 1161 1127 1082 1042 995 926
HIGH 5.0 2469 42 2389 43 2300 45 2223 47 2131 49 2027 1902 1786
*M(H/S)81405D*** MED 4.0 1575 66 1558 67 1545 67 1513 69 1500 69 1419 1354 1271
(MEDIUM) MED-LO 3.5 1402 1380 1343 1319 1296 1245 1183 1106
LOW 3.0 1200 1186 1161 1127 1082 1042 995 926

*(D/H)S8
EXTERNAL STATIC PRESSURE (Inches Water Column)
at 0.5" 0.6 0.7 0.8
0.1 0.2 0.3 0.4 0.5
ESP CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM
HIGH 3.0 1353 1290 1246 1199 25 1149 26 1116 1116 1099
GDS80403A*** MED 2.5 1183 25 1113 27 1098 27 1052 28 1039 29 1006 1012 969
(MEDIUM) MED-LO 2.0 980 30 946 31 920 32 900 33 896 33 885 855 804
LOW 1.5 778 38 762 39 738 40 746 40 738 40 717 696 678
HIGH 3.0 1290 34 1236 36 1194 37 1166 38 1176 38 1166 1108 1029
GDS80603A*** MED 2.5 1139 39 1090 41 1035 43 1063 42 1063 42 1020 962 895
(MEDIUM) MED-LO 2.0 962 46 927 48 925 48 941 47 909 49 877 834 779
LOW 1.5 787 56 776 57 763 58 744 60 723 690 641 581
HIGH 4.0 2128 2063 2001 1927 1824 1726 1628 1529
GDS80804B*** MED 3.5 1840 1788 1745 1689 35 1625 36 1550 1470 1364
(MEDIUM) MED-LO 3.0 1602 37 1558 38 1543 38 1493 40 1455 41 1402 1328 1239
LOW 2.5 1277 46 1252 47 1244 48 1229 48 1214 49 1179 1141 1079
HIGH 5.0 2405 2361 2250 2161 2037 36 1937 1808 1689
GDS81005C*** MED 4.0 1880 39 1838 40 1794 41 1734 43 1677 44 1568 1510 1401
(MEDIUM) MED-LO 3.5 1659 45 1630 45 1587 47 1537 48 1492 50 1445 1368 1287
LOW 3.0 1472 50 1454 51 1404 53 1366 54 1326 56 1300 1228 1139
(CFM & Temperature Rise vs. External Static Pressure)
EXTERNAL STATIC PRESSURE (Inches Water Column)
at 0.5"
0.1 0.2 0.3 0.4 0.5
0.6 0.7 0.8
ESP CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
HIGH 3.0 1739 1656 1601 1551 1513 20 1460 22.8 1413 23.6 1353 24.6
GHS80403A*** MED 2.5 1422 21 1399 21 1378 22 1350 22 1305 23 1275 26.1 1220 27.3 1178 28.3
(MEDIUM) MED-LO 2.0 1207 25 1213 24 1197 25 1169 25 1158 26 1131 29.5 1103 30.2 1068 31.2
LOW 1.5 991 30 980 30 958 31 950 31 937 32 924 36.1 910 36.6 874 38.1
HIGH 4.0 2097 21 2068 21 2012 22 1939 23 1869 24 1795 28.9 1718 30.2 1631 31.8
GHS80604B*** MED 3.5 1596 28 1566 28 1534 29 1492 30 1445 31 1401 37 1354 38.3 1288 40.3
(MEDIUM) MED-LO 3.0 1380 32 1356 33 1328 33 1303 34 1274 35 1239 41.8 1192 43.5 1127 46
LOW 3.0 1239 36 1191 37 1165 37 1133 39 1104 40 1082 47.9 1040 49.9 996 52.1
HIGH 5.0 2382 2315 2234 2158 2078 1971 33.8 1866 35.7 1762 37.8
GHS80805C*** MED 4.0 1622 37 1603 37 1583 37 1556 38 1516 39 1482 45 1422 46.9 1359 49.1
(MEDIUM) MED-LO 3.5 1436 41 1391 43 1387 41 1356 44 1325 45 1279 52.1 1239 53.8 1180 56.5
LOW 3.0 1240 48 1214 49 1191 50 1157 51 1120 53 1083 61.6 1052 63.4 1025 65

GME8
EXTERNAL STATIC PRESSURE (Inches Water Column)
at 0.5" 0.6 0.7 0.8
0.1 0.2 0.3 0.4 0.5
ESP CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM
T1 - YELLOW 1.5 875 793 736 674 592 556 509 460
T2 - RED 2.0 1032 43 965 46 914 49 861 810 756 712 659
T3 - ORANGE 2.5 1217 37 1153 39 1098 40 1051 42 1009 44 964 918 877
T4 - BLUE 3.0 1365 33 1313 34 1268 35 1221 36 1172 38 1129 1086 1054
T5 - BLACK 3.5 1549 29 1505 30 1460 30 1420 31 1378 32 1350 1305 1268
T1 - YELLOW 2.5 1268 47 1198 49 1151 51 1092 54 1041 57 988 932 883
T2 - RED 3.0 1362 44 1305 45 1261 47 1212 49 1170 51 1121 1074 1021
T3 - ORANGE 3.5 1576 38 1519 39 1473 40 1426 42 1398 42 1341 1290 1252
T4 - BLUE 4.0 1755 1711 35 1657 36 1627 36 1579 38 1548 1502 1463
T5 - BLACK 5.0 2183 2128 2094 2060 2014 1992 1944 1847
T1 - YELLOW 3.0 1466 51 1415 52 1357 55 1306 57 1248 59 1202 1144 1088
T2 - RED 3.5 1642 45 1596 46 1552 48 1499 49 1449 51 1388 1352 1306
T3 - ORANGE 4.0 1750 42 1750 42 1707 43 1667 44 1610 46 1574 1531 1486
T4 - BLUE 4.0 1870 40 1805 41 1782 42 1737 43 1701 44 1656 1606 1571
T5 - BLACK 5.0 2297 2297 2224 2106 35 2014 37 1896 1813 1669


DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT.
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY
CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

PROPERLY POLARIZED AND GROUNDED. SERVICING.WIRING TO UNIT MUST BE WARNING:DISCONNECT POWER BEFORE
HUMIDIFIER
XFMR (6) GND
GND (8)
24 VAC HUMIDIFIER
MVC (9)
GAS C2
HI MVH (12)
VALVE
MVL (2)
M1
SWITCH PRESSURE ID BLOWER
AUXILIARY LIMIT CONTROLS
C G R W Y
2ND STG DLY
24V THERMOSTAT CONNECTIONS
G
PS (10)
NO
5 MIN 2 STG 100 SEC 1 STG AUTO
Y TO MICRO
PSO (4)
HT OFF DLY
HLI (7)
WH
W
BL
HLO (1)
DIAGNOSTIC LED LO HEAT-H
AUTO RESET PRIMARY
FUSE
R
SEE NOTE 6
RO2 (11) LIMIT
BR
AUXILIARY
CONTROL
LIMITS
RO1 (5)
CONTROL MODULE
INTEGRATED
MANUAL RESET ROLLOUT LIMIT CONTROL(S)
COOL-H HI HEAT-H
XFMR (3)
(SINGLE CONTROL ON SOME MODELS)
FS
24 VAC
RD
RD
BR
TRANSFORMER 40 VA
BL RD
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT.
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY
XFMR-H
115 VAC
XFMR-N
FLAME SENSOR
OR
YL
YL
FP
HOT SURFACE
IGNITER
WH
EAC-H LINE-H XFMR-H
IGN
IGN-N
PU
PARK
RD (MED LOW)
INTEGRATED CONTROL MODULE
CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
BK (HI)
INTEGRATED CONTROL MODULE
WH (N)
YL (LOW)
OR(MED)
ID BLWR
BK
IND
IND-N
LO HEAT-H
BK
BR
BLOWER
CIRCULATOR
WH BL
COOL-H
CIRCULATOR
HEAT-H
HI
BLWR
CIR-N
XFMR
WH
BK
AIR CLEANER ELECTRONIC
GR
15 PIN PLUG
EAC-N EAC-H
ON SOME MODELS
BLOWER COMPARTMENT
LINE-H
LINE-N
BURNER COMPARTMENT
JUNCTION BOX
DOOR
WH WH
BK
DOOR SWITCH
HUMIDIFIER
24 VAC
SWITCH
SWITCH LOCATED IN BLOWER COMPARTMENT ON SOME MODELS
C NO
OR
RD
RD
WIRING TO UNIT BEFORE SERVICING. DISCONNECT POWER
HIGH VOLTAGE!
WH
YL
SWITCH PRESSURE
YL
DISCONNECT
PRIMARY LIMIT
RD
MUST BE
YL YL
AND GROUNDED. POLARIZED PROPERLY
WH
BK
L GND
N
BR
BL
OVERCURRENT PROTECTION DEVICE
WH
PM
1 HI C
BK
JUNCTION
IGNITER SURFACE HOT
WH
BOX
2 STAGE GAS VALVE (HONEY WELL)
GND LINE-N
LINE H
PU
INDUCED DRAFT
BLOWER
OVERCURRENT PROTECTION POWER SUPPLY WITH TO 115 VAC/ 1/60HZ
PU
SENSOR FLAME
DEVICE
ROLLOUT LIMITS
(SINGLE CONTROL ON SOME MODELS)
STEADY ON = NORMAL OPERATION
LOW VOLTAGE (24V)
EQUIPMENT GND
OFF = CONTROL FAILURE
1 FLASH =
SYSTEM LOCKOUT (RETRIES/RECYCLES EXCEEDED)
LOW VOLTAGE FIELD
FIELD GND
2 FLASHES = PRESSURE SWITCH STUCK CLOSED
HI VOLTAGE (115V)
FIELD SPLICE
3 FLASHES = PRESSURE SWITCH STUCK OPEN
HI VOLTAGE FIELD
4 FLASHES = OPEN HIGH LIMIT
SWITCH (TEMP.)
JUNCTION
5 FLASHES = FLAME SENSE WITHOUT GAS VALVE
IGNITER
6 FLASHES = OPEN ROLLOUT OR OPEN FUSE
TERMINAL
INTEGRATED CONTROL INTERNAL TO
SWITCH (PRESS.)
7 FLASHES = LOW FLAME SIGNAL
8 FLASHES = CHECK IGNITER OR IMPROPER GROUND
PROT. DEVICE OVERCURRENT
RAPID FLASHES = REVERSED 115 VAC POLARITY/VERIFY GND
PLUG CONNECTION
NOTES: 1. SET HEAT ANTICIPATOR ON ROOM THERMOSTAT AT 0.7 AMPS. 2. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING. 3. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105 °C. USE COPPER CONDUCTORS ONLY. 4. BLOWER SPEEDS SHOULD BE ADJUSTED BY INSTALLER TO MATCH THE INSTALLATION REQUIREMENTS SO AS TO PROVIDE THE CORRECT HEATING TEMPERATURE RISE AND THE CORRECT COOLING CFM. (SEE SPEC SHEET FOR AIR FLOW CHART) 5. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C. AND LOCAL CODES. 6. TO RECALL THE LAST 5 FAULTS, MOST RECENT TO LEAST RECENT, DEPRESS SWITCH FOR MORE THAN 2 SECONDS WHILE IN STANDBY(NO THERMOSTAT INPUTS).
BR BROWN PK PINK
PU PURPLE OR ORANGE YL YELLOW
RD RED GY GRAY BL BLUE WH WHITE
BK BLACK GR GREEN
0140F00658 REV. A
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

PROPERLY POLARIZED AND GROUNDED. SERVICING.WIRING TO UNIT MUST BE WARNING:DISCONNECT POWER BEFORE
CONTROL MODULE INTEGRATED
XFMR (6) GND
24 VAC HUMIDIFIER
GND (8)
GAS C2
MVC (9)
HI MVH (12)
VALVE
M1
MVL (2)
SWITCH PRESSURE ID BLOWER
AUXILIARY LIMIT CONTROLS
C G R W Y
2NDSTGDLY
24VTHERMOSTATCONNECTIONS
G
NO
5 MIN 2 STG 100 SEC 1 STG AUTO
150 SEC MODE
HTOFFDLY
Y TO MICRO
PSO (4)
HLI (7)
WH
W
BL
HLO (1)
DIAGNOSTIC LED LOHEAT-H
AUTO RESET PRIMARY
FUSE
SEE NOTE 6
R
RO2 (11) LIMIT
AUXILIARY
CONTROL
BR
LIMITS
RO1 (5)
INTEGRATED
CONTROL MODULE
COOL-H HIHEAT-H
MANUAL RESET ROLLOUT LIMIT CONTROL(S)
(SINGLE CONTROL ON SOME MODELS)
FS
XFMR (3)
24 VAC
TRANSFORMER 40 VA
RD
RD
BL RD
BR
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT.
XFMR-H
115 VAC
XFMR-N
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY
OR
FLAME SENSOR
YL
YL
FP
HOT SURFACE
IGNITER
WH
EAC-H LINE-H XFMR-H
IGN
IGN-N
PU
PARK
OR(MEDLOW)
INTEGRATEDCONTROLMODULE
CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
BL(MED)
INTEGRATEDCONTROLMODULE
WH(N)
BK(HI)
ID BLWR
BK
IND
IND-N
LO HEAT-H
BK
BR
CICULATOR
BLOWER
COOL-H
CIRCULATOR
WH BL
BLWR
CIR-N
XFMR
BR BR
HEAT-H
HI
WH
CAP
BK
AIR CLEANER ELECTRONIC
GR
15 PIN PLUG
EAC-N EAC-H
ON SOME MODELS
BLOWER COMPARTMENT
LINE-H
LINE-N
BURNER COMPARTMENT
JUNCTION BOX
WH WH
BK
DOOR SWITCH
HUMIDIFIER
24 VAC
SWITCH
DOOR
SWITCH LOCATED IN BLOWER COMPARTMENT ON SOME MODELS
C NO
HIGH VOLTAGE!
RD
RD
OR
YL
SWITCH PRESSURE
YL
WIRING TO UNIT BEFORE SERVICING. DISCONNECT POWER
DISCONNECT
WH
PRIMARY LIMIT
RD
YL YL
MUST BE
AND GROUNDED. POLARIZED PROPERLY
WH
BK
L GND
N
BR
BL
OVERCURRENT PROTECTION DEVICE
WH
PM
1 HI C
BK
JUNCTION
IGNITER SURFACE HOT
WH
BOX
2 STAGE GAS VALVE (HONEY WELL)
GND LINE-N
LINE H
PU
INDUCED DRAFT
BLOWER
OVERCURRENT PROTECTION POWER SUPPLY WITH TO 115 VAC/ 1/60HZ
PU
SENSOR FLAME
ROLLOUT LIMITS
DEVICE
(SINGLE CONTROL ON SOME MODELS)
STEADY ON = NORMAL OPERATION
OFF = CONTROL FAILURE
LOW VOLTAGE (24V)
EQUIPMENT GND
LOW VOLTAGE FIELD
1 FLASH =
SYSTEM LOCKOUT (RETRIES/RECYCLES EXCEEDED)
FIELD GND
2 FLASHES = PRESSURE SWITCH STUCK CLOSED
HI VOLTAGE (115V)
FIELD SPLICE
3 FLASHES = PRESSURE SWITCH STUCK OPEN
HI VOLTAGE FIELD
4 FLASHES = OPEN HIGH LIMIT
SWITCH (TEMP.)
JUNCTION
5 FLASHES = FLAME SENSE WITHOUT GAS VALVE
IGNITER
6 FLASHES = OPEN ROLLOUT OR OPEN FUSE
TERMINAL
SWITCH (PRESS.)
7 FLASHES = LOW FLAME SIGNAL
INTEGRATED CONTROL INTERNAL TO
8 FLASHES = CHECK IGNITER OR IMPROPER GROUND
PROT. DEVICE OVERCURRENT
PLUG CONNECTION
RAPID FLASHES = REVERSED 115 VAC POLARITY/VERIFY GND
NOTES:
COLOR CODES:
BR BROWN PK PINK
REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE 3. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE
RATING OF AT LEAST 105
°C. USE COPPER CONDUCTORS ONLY.
CORRECT COOLING CFM. (SEE SPEC SHEET FOR AIR FLOW CHART) REQUIREMENTS SO AS TO PROVIDE THE CORRECT HEATING TEMPERATURE RISE AND THE 4. BLOWER SPEEDS SHOULD BE ADJUSTED BY INSTALLER TO MATCH THE INSTALLATION



Goodman Manufacturing Company, L.P. 5151 San Felipe, Suite 500, Houston, TX 77056 www.goodmanmfg.com © 2009-2010 Goodman Manufacturing Company, L.P.
Pages referenced in this manual — manufacturer, support and downloads.
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| • Furnace fails to operate. • Integrated control module diagnostic LED provides no signal. • Furnace fails to operate. | p.37 | ||
| • Induced draft blower runs continuously with no further furnace operation. • Integrated control module diagnostic LED is flashing THREE (3) flashes. | p.37 | ||
| • Circulator blower runs continuously. No furnace operation. • Integrated control module diagnostic LED is flashing FOUR (4) flashes. | • Check primary limit. Replace if necessary. • Check filters and ductwork for blockage. Clean filters or remove obstruction. • Check circulator blower speed and performance. Correct speed or replace blower if necessary. • Tighten or correct wiring connection. | p.38 | |
| • Induced draft blower and circulator blower runs continuously. No furnace operation. • Integrated control module diagnostic LED is flashing FIVE (5) flashes. | • Correct short at flame sensor or in flame sensor wiring. | p.38 | |
| • Furnace fails to operate. • Integrated control module diagnostic LED is flashing SIX (6) flashes. • No furnace operation. | • Check burners for proper alignment. • Check flue and air inlet piping for blockage, proper length, elbows, and termination. Correct as necessary. • Check rollout limit. Replace if necessary. • Check induced draft blower for proper performance. Replace, if necessary. • Tighten or correct wiring connection. • Repair short in 24 volt AC control/safety circuit(s). • Replace integrated control module fuse (3A). | p.38 | |
| • Normal furnace operation. • Integrated control module diagnostic LED is flashing SEVEN (7) flashes. | • Sand flame sensor. • Inspect for proper sensor alignment. • Compare current gas pressure to rating plate info. Adjust as needed. | p.38 | |
| • Furnace not operating. • Integrated control module diagnostic LED is flashing EIGHT (8) flashes. | p.39 | ||
| • LED is steady on | p.39 |