Operator’s Manual

This generator is rated in accordance with UL (Underwriters Laboratories) 2200 (stationary engine generator assemblies) and CSA (Canadian Standards Association) standard C22.2 No. 100-4 (motors and generators).

Thank you for purchasing this quality-built GE generator. We’re pleased that you’ve placed your confidence in the GE brand. When operated and maintained according to the instructions in this manual, your generator will provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with standby generators and how to avoid them. Because we do not necessarily know all the applications this equipment could be used for, it is important that you read and understand these instructions thoroughly before attempting to start or operate this equipment. Save these instructions for future reference.
This generator requires professional installation before use. Refer to the separate installation manual for full information. Your installer should follow the instructions completely.
You never have to look far to find GE support and service for your generator. For quick service when you need it, keep your original receipt with this manual. You may contact Customer Service at 888‑575-8226 between 8:00 AM and 5:00 PM CT, or click on SERVICE & SUPPORT at www.standbygeneratorsystems.com which provides a list of authorized dealers.



SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries. Safety Symbols and Meanings
The manufacturer cannot possibly anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and the tags and decals affixed to the unit are, therefore, not all-inclusive. If you use a procedure, work method or operating technique that the manufacturer does not specifically recommend, you must satisfy yourself that it is safe for you and others. You must also make sure that the procedure, work method or operating technique that you choose does not render the generator system unsafe. Fire
Hot Surface Rotating Parts
Chemical Burn Auto Start
Exploding Battery Rotating Belt/Pulley

Lift Hazard Read Manual
The safety alert symbol indicates a potential personal injury hazard. A signal word (DANGER, WARNING, or CAUTION) is used with the alert symbol to designate a degree or level of hazard seriousness. A safety symbol may be used to represent the type of hazard. The signal word NOTICE is used to address practices not related to personal injury.

and explosive, which could cause burns, fire or explosion resulting in death or serious injury.

to start at any time without warning resulting in minor or moderate injury.

We sincerely appreciate your patronage. For this reason, we have made every effort to provide for a safe, streamlined and cost-effective installation. Because each installation is unique, it is impossible to know of and advise the trade of all conceivable procedures and methods by which installation might be achieved. Neither could we know of possible hazards and/or the results of each method or procedure. For these reasons,
Only current licensed electrical and plumbing professionals should attempt generator system installations. Installations must strictly comply with all applicable codes, industry standards and regulations.
Your generator is supplied with this “Operator’s Manual” and a separate “Installation Manual”. These are important documents and should be retained by the owner after the installation has been completed.
To help you make informed choices and communicate effectively with your installation contractor(s),
The generator warranty is VOID unless the system is installed by licensed electrical and plumbing professionals.
Read and understand Owner Orientation in this manual before contracting or starting your generator installation.
Every effort has been made to ensure that information in this manual is accurate and current. However, we reserve the right to change, alter, or otherwise improve the product and this document at any time without prior notice.
To arrange for proper installation, contact the store at which you purchased your generator, your dealer, a licensed electrician or your utility power provider.
The Emission Control System for this generator is warranted for standards set by the U.S. Environmental Protection Agency and by the California Air Resources Board (CARB).
If you need more information in this matter, please call 888 575‑8226 between 8:00 AM and 5:00 PM CT.. For most applications, the Installation manual contains all the information required to properly install and start the generator. This Operator’s Manual describes routine operation and owner maintenance procedures.

This section provides generator owners with the information necessary to achieve the most satisfactory and cost effective installation possible.
gaseous fuel supply increases, and the number of 90 degree bends in the fuel supply increases; compensations in piping and wiring materials must be made. This is necessary to comply with local codes and overcome electrical voltage drops and gaseous fuel pressure drops.
The illustrations are for typical circumstances and are meant to familiarize you with the installation options available with your generator. A thorough understanding of these options will provide fundamental control over the cost of your installation, as well as ensure your final satisfaction and security.
The factors mentioned above will have a direct affect on the overall price of your generator installation.
In some areas you may need to acquire electrical permits for installing the generator, building permits for installing gas lines, and permits for noise allowances. Your installer should check your local codes AND obtain the permits before installing the system.
Federal and local codes, appearance, noise levels, fuel types, and distances are the factors that must be considered when negotiating with an installation professional. Remember that as the distance from the existing electrical service and
An important consideration affecting the entire installation is the type of fuel used by your generator. The system was factory tested and adjusted using either natural gas or liquid propane (LP vapor). For proper engine function, factors that are inherent to each of these fuels, your location and the duration of possible utility interruptions are important considerations in the following fuel guidelines:
and explosive, which could cause burns, fire or explosion resulting in death or serious injury.
particulate material. Using fuels outside the following recommended values may cause performance problems.
Air density is less at high altitudes, resulting in less available engine power. Specifically, engine power will decrease 3.5% for each 1,000 feet (300 meters) above sea level and 1% for each 10° F (5.6°C) above 77°F (25°C). Make sure you and your installer consider these factors when determining total generator load.
grade HD5 propane with a minimum fuel energy of 2500 BTUs/ft3 with maximum propylene content of 5% and butane and heavier gas content of 2.5% and minimum propane content of 90%.

The actual physical location of your generator has a direct affect on:
Specific location guidelines are discussed in the installation manual. Acquaint yourself with that information and confer with your installer. Be sure to ask how your site might affect installation costs and compliance with local codes and standards.
structures resulting in death or serious injury.
The generator must be installed outdoors. DO NOT install generator where exhaust gas could accumulate and enter inside or be drawn into a potentially occupied building. Ensure exhaust gas is kept away from any windows, doors, ventilation intakes or other openings that can allow exhaust gas to collect in a confined area. Prevailing winds and air currents should be taken into consideration when positioning generator. See the installation manual for full details on safe generator location.
The generator system is supplied with:
Carefully inspect the generator for any damage that may have occurred during shipment.
If loss or damage is noted at time of delivery, have the person(s) making delivery note all damage on the freight bill and affix his signature under the consignor’s memo of loss or damage. If loss or damage is noted after delivery, separate the damaged materials and contact the carrier and your installer for claim procedures. Missing or damaged parts are not warranted.
To be supplied by Installer:

Read this operator’s manual and Important Safety Instructions before operating your generator. Compare the illustrations of this model with your generator to familiarize yourself with the locations of various controls and adjustments. Save this manual for future reference.
B C D E
F
K J P N M
H
G
R
T
S
Generator is pictured with access doors removed for clarity and screen guard open for clarity.
J Oil Fill Cap — Remove to service the engine with
recommended oil. K Coolant Fill — Provides access for filling engine coolant. L Coolant Recovery Bottle — Provides visual indicator of
A Exhaust Port — High-performance muffler lowers engine
noise to comply with most codes. B Engine Label — Identifies engine model and type. C Oil Dip Stick — Used to check the engine oil level. D Roof Access Opening — Provides access to control panel,
engine coolant level. M Fuel Inlet — Fuel supply is connected here.
N ID Label — Identifies unit by serial number.
oil filter, etc. E Circuit Breaker Enclosure — Equipped with removable top
P Rear Access Panel Opening — Provides access to various
components of generator. R Oil Filter — Filters engine oil to prolong system life. S Front Access Panel Opening — Provides access to various
to assist with conduit connection. F Control Panel — Used for various test, operation and
maintenance functions. See System Control Panel. G Air Cleaner — Protects engine by filtering dust and debris
components of generator. T Battery Location — Battery located for convenient access. U Fuel Type Selector — Position selector for Natural Gas (NG)
out of intake air. H Fuel Selection Switch — Select natural gas or liquid
or Liquid Propane (LP vapor) supply.
propane (LP vapor) supply.
A Back Top · Front

The generator is equipped with an enclosure that has several access panels, as shown.
The access panels and the components located behind them are listed below:
A -Roof (Control Panel, internal guard)
B -Front Access Panel (oil drain and oil filter)
C -Internal Guard (air filter, oil dipstick, coolant
D -Rear Access Panel (fuel regulator, fuel selector,
E -Control Panel Cover (field wiring and control wires)

bottle) · and engine starter)

Each generator is shipped with a set of identical keys. These keys fit in the lock on the front and rear removable panels. The roof must be unlocked in order for it to open.
To remove front panel:
To open roof:
A
To secure front panel:
To remove rear panel:
To open internal guard:
B
D
To secure rear panel:
To secure internal guard:

The generator control board, located inside the generator, under the roof, is shown below. Brief descriptions of the controls used during installation are:
A - Menu/Programming Navigation Buttons — See Menu
- “AUTO” LED — LED will light when unit is placed into
AUTO mode. LED will blink if exercise cycle is not set or set to OFF.
B - Mini USB Port — Authorized Dealer Service Use Only
C - Generator Operation Control Buttons —
D – 15 Amp Fuse — Protects the generator DC control
circuits. If the fuse has ‘blown’ (melted open) or was removed, the engine cannot crank or start. Replace the fuse using only an identical ATO 15 Amp fuse. One spare fuse is supplied with the unit.
E - Cover — This protective cover must be opened to
access the fuse and the USB port.
F - Digital Display — Displays generator mode, menu
options, service codes, and service engine indicators
OFF must be pressed and held for more than 5 seconds in order to reset service codes.
More information may be found in Controls in the operator’s manual.
A
E
B
D

The following chart shows the icons for the buttons that control the system control panel.
MENU ENTER THE MENU (VIEW SETTINGS) PRESS TO CONFIRM SELECTION WHEN PROGRAMMING.
RIGHT ARROW TOGGLE THROUGH MENU OPTIONS SETTING SYSTEM PARAMETERS
LEFT ARROW TOGGLE THROUGH MENU OPTIONS SETTING SYSTEM PARAMETERS
MANUAL MODE USED TO MANUALLY START THE GENERATOR. PRESS AND HOLD BUTTON TO START THE GENERATOR.
OFF TURNS OFF RUNNING GENERATOR, PREVENTS UNIT FROM STARTING, AND RESETS ANY DETECTED FAULTS.
NORMAL OPERATING POSITION. PRESS AND HOLD BUTTON TO PUT UNIT INTO AU- TOMATIC MODE. IF A UTILITY POWER OUTAGE IS SENSED, THE SYSTEM WILL START THE GENERATOR. WHEN UTILITY POWER IS RESTORED, AUTO LETS THE ENGINE STABILIZE INTERNAL TEMPERATURES, SHUTS OFF THE GENERATOR, AND WAITS FOR THE NEXT UTILITY POWER OUTAGE.
The following chart describes key sequences for accessing different programming modes;
PRESS AND HOLD [ARROW LEFT AND ARROW RIGHT] FOR THREE SECONDS TO ENTER THE PROGRAM MODE.
PRESS AND HOLD [ARROW LEFT, ARROW RIGHT AND ESC] FOR THREE SEC- ONDS TO ENTER THE ADVANCED SETTINGS MODE.
PRESS AND HOLD [MENU AND ESC] FOR THREE SECONDS TO ENTER THE WIRELESS LINKING MODE.
ok · ok

For general set up, press and hold the left arrow and right arrow for 3 seconds. Follow the prompts as outlined below.
YEAR FLASHING
MONTH FLASHING
DAY## FLASHING
SET TIME HOURS FLASHING
MINUTES FLASHING
AM/PM FLASHING
If set to OFF, display will read:
AM/PM FLASHING SET EXERCISE
DAY OF WEEK
HOURS FLASHING
MINUTES FLASHING
CYCLE
FLASHING
or
EVENT LOG Display will scroll last service code event, date, time, and ambient temperature of when the event occurred. or
IF DURING PROGRAMMING NO BUTTONS ARE PRESSED FOR 30 SECONDS,
THE CONTROL PANEL WILL AUTOMATICALLY EXIT THE PROGRAM MODE.

In Automatic Mode, the display screen will display via scrolling text:
utility power is present.
GENERATOR READY or SERVICE CODE DESCRIPTION
(When Generator NOT Running - Auto Mode)
power is not present.
To view general system parameters, press the MENU button.
The following will scroll across the digital display and then move to the next item:
The user can press the LEFT ARROW or RIGHT ARROW at any time to move to the next item.
The user can press ESCAPE to go back to Generating set READY.
If no user inputs are made for 10 seconds after all the items have been displayed, the control board will reset to
Generating set READY.
EXERCISE CYCLE

Advanced setting parameters are preset at the factory for a typical installation. To view Advanced Settings items and/or to change items, follow the instructions listed below.
For advanced menu items, press and hold the left arrow, right arrow, and escape key for 3 seconds. Follow the prompts as outlined below.
PHASE
VOLTS VOLTS FLASHING
SOFTWARE
VERSION DISPLAYED

Battery
The installer must supply a valve-regulated, rechargeable 12 volt DC starting battery. See Battery in Final Installation Considerations in the installation manual.
The engine is shipped from the factory pre-run and filled with synthetic oil (API SJ/CF 5W-30). This allows for system operation in a wide range of temperature and climate conditions. Before starting the engine, check oil level and ensure that engine is serviced as described in the Maintenance section. Coolant System
With the battery installed, all wiring to transfer switch and generator completed, utility power supplied to the automatic transfer switch, and the unit in AUTO mode, the battery receives a trickle charge while the engine is not running. The trickle charge cannot be used to recharge a battery that is completely discharged. 15 Amp Fuse
This engine is shipped from the factory filled with a 50‑50 mix of automotive (Ethylene glycol) anti-freeze and water. This will provide optimum year round protection against freezing, boiling and corrosion. The coolant system incorporates an optional water heater that operates when ambient temperature is below 80ºF AND utility power is present at the transfer switch. Before starting the engine, check coolant level as described in the Maintenance section
The generator’s 15 Amp fuse is critical to correct system operation. Your installer will ensure the fuse is properly installed upon completion of the installation.
Utility Voltage Pickup Sensor
The generator’s control board constantly monitors utility voltage. Should utility voltage drop below a preset level, the control board will signal the engine to crank and start.
This sensor monitors utility voltage. When utility voltage is restored above 80 percent of the nominal source voltage, a time delay starts timing and the engine will go to engine cool-down.
When utility voltage is restored above a preset voltage level, the engine is signaled to shut down.
The actual system operation is not adjustable and is sequenced by sensors and timers on the control board, as follows:
When utility power is sensed and the load transfers back to the utility source, the engine will go into a cool down period as described below:
Utility Voltage Dropout Sensor
once the utility transfer occurs, the engine will continue to run for about 1 minute before shutting down.
of the nominal supply voltage, the sensor energizes a 3 second timer. The timer is used to ‘sense’ brown‑outs.
the utility transfer occurs, the engine will continue to run until 5 minutes has elapsed before shutting down.
and start.
Engine Cool-down Timer

The generator is equipped with an exercise timer. During the exercise period, the unit runs for approximately 20 minutes and then shuts down. Electrical load transfer DOES NOT occur during the exercise cycle (unless an utility power outage occurs).
through the days of the week, Once the day is selected, hit the “OK” button.
The generator will only enter the exercise cycle if the unit is in the AUTO mode and this exact procedure is followed.
through between 1 and 12. Choose the hour of day you want the generator to exercise then hit the “OK” button.
To set the exercise timer:
between :00 and :59. Choose the minute of the day you want the generator to exercise then hit the “OK” button.
between AM and PM. Once chosen, hit the “OK” button.
If you want to change the day and time the unit exercises, simply perform the procedure again.
To turn off the generator exercise cycle, go to the OFF selection within the day of the week menu and press OK. The display will then scroll: EXERCISE CYCLE OFF.

Before performing any generator maintenance, always perform the following steps:
The generator may have to run for long periods of time with no operator present. For that reason, the system is equipped with sensors that automatically shut down the generator in the event of potentially damaging conditions, such as low oil pressure, high temperature, over speed, and other conditions.
The operator must reset the service code detection system each time it activates. To do so, press the control board OFF button for 5 seconds. Once the display turns off, leave it off for at least 30 seconds. Remedy the service code condition, then return the generator to service by pressing and holding the control board AUTO button and installing the 15 Amp fuse (if removed). Low Battery Voltage
The generator’s control board shows service code descriptions scrolling across the digital display. The service code descriptions are listed below:
This service code is indicated by Low Battery Voltage scrolling across the digital display and a single flash on the wireless monitor. This condition occurs if the battery voltage drops below the preset value. Causes for this problem may be a service code battery or battery charge circuit. See Battery Charge Circuit,
Remove the 15 Amp fuse and disconnect the battery from the generator. Test the battery voltage. If voltage meets specifications, take the battery to a local battery store for analysis. Or contact your local service center for assistance.
Reinstall the battery (replace if necessary - see Battery in Final Installation Considerations in the installation manual). Then reset the service code detection system, as described earlier. Low Oil Pressure
This service code is indicated by Low Oil Pressure scrolling across the digital display and two flashes on the wireless monitor. The unit is equipped with an oil pressure sensor that is monitored by the engine ECU. Should oil pressure drop below the 50 psi range, the engine will shut down. To remedy the low oil pressure condition, add the recommended oil to the FULL mark on the dipstick. If the low oil pressure condition still exists, the engine will start, then shut down again. The service code will appear. In this case, contact an authorized dealer.

High Coolant Temperature
This service code is indicated by Under Voltage scrolling across the digital display and three flashes on the wireless monitor. This condition is caused by a restriction in the fuel flow, the electronic governing system not functioning properly, a broken or disconnected signal lead, a failed alternator winding, the control board circuit breaker is open, or the generator is overloaded. To remedy the problem, contact your installer or an authorized dealer. Over Voltage
This service code is indicated by High Coolant Temperature scrolling across the digital display and seven flashes on the wireless monitor. The contacts of the temperature switch are normally open. If the engine temperature exceeds a predetermined temperature, the service code is detected and the engine shuts down. Common causes for this condition include running the unit with an access doors removed, obstructed air inlet or exhaust port, or debris in the engine compartment or running unit with roof open. To resolve the problem, let the engine cool down and remove any accumulated debris and obstructions. Ensure that the access doors are installed and the roof is closed whenever the unit is running. If problem persists, contact your installer or an authorized dealer. Transfer Switch Service code
This service code is indicated by Over Voltage scrolling across the digital display and three flashes on the wireless monitor. This feature protects devices connected to the transfer switch by shutting the generator down if the generator output voltage happens to increase above the preset limit. This condition is most likely caused by a failed voltage regulator, alternator excitation circuit or a load imbalance. To remedy the problem, contact your installer or an authorized dealer. Engine Does Not Start
This service code is indicated by Transfer Switch Service code scrolling across the digital display (if transfer switch is equipped with service code detection) and eight flashes on the wireless monitor. The most likely cause of this service code is a blown fuse in the transfer switch. To remedy the problem, contact your installer or an authorized dealer. No Wireless Communication
This service code is indicated by Engine Does Not Start scrolling across the digital display and four flashes on the wireless monitor. This feature prevents the generator from damaging itself if it continually attempts to start in spite of another problem, such as no fuel supply. Each time the system is directed to start, the unit will crank for 10 seconds, pause for 10 seconds, and repeat. If the system does not begin producing electricity after approximately 2 minutes, the unit will stop cranking. The most likely cause of this problem is no fuel supply or incorrect fuel selector setting. See Fuel Selection Switch in the installation manual. Check the internal and external fuel shut off valves to ensure they are fully open. Other causes could be failed spark plug(s), a loose electronic governor connection, a failed engine ignition, or the engine air filter is clogged. You may need to contact your installer for assistance if you can’t remedy these problems. Low Frequency
This service code is indicated by No Monitor Communication scrolling across the digital display. The SERVICE NEEDED red LED on the wireless monitor will flash 20 fast pulses, pause 5 seconds, and repeat if there is a loss in communication between the wireless monitor and the generator. To resolve the problem, move the wireless monitor closer to generator. Re-link if necessary. Battery Charge Circuit
This service code is indicated by Battery Charge Circuit scrolling across the digital display. The most likely cause is an electrical problem with the control panel. To remedy the problem, contact your installer or an authorized dealer. Service Engine
This service code is indicated by Low Frequency scrolling across the digital display and five flashes on the wireless monitor. This feature protects devices connected to the transfer switch by shutting the generator down if the engine runs slower than 55 Hz for three seconds. This condition is caused by a failed engine component, electronic governor system, or by excessive loads on the generator. To resolve the problem, contact your installer or an authorized dealer. Engine Overspeed
The engine is equipped with on-board diagnostics that monitor the operation of emission related components. If an emission related problem has been detected, the system control panel will display Service Engine. If Service Engine displays while the generator is running, a diagnostic trouble code may be set or a problem may exist in the system which has caused the engine emissions to go outside the standards certified by the Environmental Protection Agency. It is the responsibility of the operator to contact an authorized service technician to repair this condition.
This service code is indicated by Engine Overspeed scrolling across the digital display and six flashes on the wireless monitor. This condition can be caused by a problem within the electronic governor system. To resolve the problem, contact your installer or an authorized dealer.

Generator maintenance consists of keeping the unit clean. Operate the unit in an environment where it will not be exposed to excessive dust, moisture or any corrosive vapors. Cooling air louvers on the enclosure must not become clogged with snow, leaves, or any other foreign material. To prevent generator damage caused by overheating, keep the enclosure cooling inlets and outlets clean and unobstructed at all times.
Check the cleanliness of the unit frequently and clean when dust, dirt, oil, moisture or other foreign substances are visible on its exterior/interior surface. Inspect the air inlet and outlet openings inside and outside the enclosure to ensure air flow is not blocked.
DO NOT use direct spray from a garden hose to clean generator. Water can enter the engine and generator and cause problems.
away dirt. Inspect cooling air slots and openings on the generator. These openings must be kept clean and unobstructed.
The maintenance of an engine and related components are critical to its operating performance and lifespan. Industrial engines operate in an environment that often include hot and cold temperatures and extreme dust. The recommended maintenance schedule is listed in this section, however, environmental operating conditions and additional installed equipment may require more frequent inspection and servicing.
The owner and/or authorized service technician should review the operating conditions of the equipment to determine the inspection and maintenance intervals. Proper engine cooling and lubrication are very important, so pay particular attention to these matters.
The engine is shipped from the factory pre-run and filled with synthetic oil (API SJ/CF 5W-30). This allows for system operation in a wide range of temperature and climate conditions.
Synthetic oils have been available for use in industrial engines for a relatively long period of time and may offer advantages in cold and hot temperatures. However, it is not known if synthetic oils provided operational or economic benefits over conventional petroleum-based oils in industrial engines.
Use of synthetic oils does not permit the extension of oil change intervals.

The oil must meet GM specification 9986231. Motor oils meeting this specification receive the API (American Petroleum Institute) starburst symbol.
Select an engine oil viscosity that will best match the prevailing daytime temperature.
It is noted that the GF-4 oils are also “backwards compatible” and are equal or better that previous grades of oil in all aspects.
FOR THE BEST FUEL ECONOMY AND COLD STARTING, SELECT THE LOWEST SAE
HOT WEATHER
IF SAE 15W-30 GRADE OIL IS NOT AVAILABLE, SAE 30 GRADE MAY BE USED AT TEMPERATURES

ABOVE 40°F (4°C).
SAE 5W-30 PREFERRED
COLD WEATHER
Checking Engine Oil Level

KEEP OUT OF REACH OF CHILDREN. DON’T POLLUTE. CONSERVE RESOURCES. RETURN USED OIL TO COLLECTION CENTERS.
Change oil while the engine is still warm from running.
The engine installed in this equipment uses drive belt(s) that drive the water pump and alternator. The drive belt(s) are an integral part of the cooling and charging system and should be inspected according to the maintenance schedule.
When inspecting the belts, check for:
If any of these conditions exist, the belt should be replaced.

It is important that the cooling system of the engine be maintained properly to ensure proper performance and longevity.
The cooling system must be maintained according to the recommended maintenance schedule and inspection should include:
radiator core and fan shroud.
especially at the radiator hose connections. Tighten hose clamps if necessary.
hardening, cracks, or any type of deterioration.
With the engine cold, check the coolant level in the coolant recovery bottle (see Controls). Specifications for the coolant system can be found in the Maintenance chart of this manual. Coolant Specification - ethylene-glycol 50-50 mixture with distilled water.
Once each year service the air cleaner, as follows. If operating in a dusty environment, service more often.
NEVER use the service cover to push the filter into
place! Using the cover to push the filter in could cause damage to the housing, cover, or fasteners and will void the warranty. If the service cover hits the filter before it is fully in place, remove the cover and push the filter (by hand) further into the air cleaner and try again. The cover should go on with no extra force.
Visually check and physically squeeze Vacuator valve
attached to service cover to make sure it is flexible and not inverted, damaged or plugged.

The generator’s electrical system incorporates computers to control various related components. The electrical system connections and ground circuits require good connections. Follow the recommended maintenance schedule located in the Maintenance section of this manual.
correctly locked in.
chafing, burning, separation, and split boot covers.
When inspecting the electrical system, check the following:
chafing, burning, separation, and split boot covers.
corrosion, rubbing, chafing, burning, and ensure tight connections at both ends.
recommended maintenance schedule.
mounted to the engine or chassis.
Replace as necessary.
by the owner are properly installed in the system.
pinching, burning, and crack or breaks in the wiring.
Servicing of batteries is to be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
If it is necessary to service the battery, proceed as follows:
DON’T POLLUTE. CONSERVE RESOURCES, RETURN USED BATTERY TO RECYCLING COLLECTION CENTER.

If it is necessary to charge the battery, proceed as follows:
crank and start at any time without warning, resulting in minor or moderate injury.
The fuel system installed on this industrial engine has been designed to various standards to ensure performance and reliability. To ensure compliance to these standards, follow the recommended maintenance schedule contained in this section.
When inspecting the regulator, check for the following items:
If the regulator fails to operate or develops a leak, it should be repaired or replaced with the OEM recommended replacement parts.
and the mounting bolts are tight.

recommended maintenance schedule found in this section.
Replace if any of these conditions exist.
When inspecting the mixer and throttle body, check for the following items:
manifold.
mounted.
When inspecting the exhaust system, check for the following items:
connector is seated and locker, check wires to ensure there is no cracking, splitting, chaffing, or burning. Replace as necessary.
and that all retaining bolts and shields (if used) are in place.
necessary.
they are tight and that there are not exhaust leaks. Repair as necessary.
Periodically inspect the engine exterior for contamination and potential damage from dirt, leaves, rodents, spider webs, insects, etc. and remove.
You must have the following information at hand if it is necessary to contact a local service center regarding service or repair of this unit:
The generator is designed for long term service as a backup generator. There is no need to take any storage precautions. However, if it becomes necessary to take the system out of service for an extended period, call Technical Services at 888 575-8226, between 8:00 AM and 5:00 PM CT for specific recommendations.

This maintenance schedule represents the manufacturer’s recommended maintenance intervals to maintain proper engine/ equipment function. Federal, State, or Local regulations may require additional or more frequent inspection or maintenance intervals than those specified above. Check with the authority having jurisdiction for details.
Perform the following maintenance on the engine at the hours indicated and at equivalent hour intervals thereafter.

1000 1500 2000 2500 3000 3500 4000 4500 5000
Change engine oil and oil filter Every 100 hours or Annually
Check fuel system for leaks Before and after any service or maintenance activity
Inspect accessory drive belts X
Clean debris from radiator core Every 100 hours or 60 days of operation
Change coolant - ethylene glycol 50-50 mixture w/ distilled water X
Replace coolant hoses and accessory drive belt Every 2,000 Hours or two years, whichever occurs first
Inspect battery case for leaks/damage X
Inspect all electrical connector retainer locks X
Inspect crank sensor timing wheel Every 100 hours or Annually
Clean secondary ignition coil tower x
Inspect air cleaner Every 200 hours (or every 100 hours in severe

Engine is running, but no AC output is available.
Engine runs good at no-load but “bogs down” when loads are connected.
Engine will not start; or starts and runs rough.
Engine shuts down during operation.
Loss of power on circuits.

U.S. EPA, and Briggs & Stratton Corporation Emissions Control Warranty Statement for Emergency Standby Engines
Your Warranty Rights And Obligations February 2013
General Information The U.S. EPA, and Briggs & Stratton (B&S) are pleased to explain the emissions control system warranty on your Model Year 2013 - 2014 engine / equipment. In the U.S., new Emergency Standby Engines must be designed, built, and equipped to meet stringent emission standards. Engines less than 25 Hp must meet requirements of 40 CFR Part 1054. Engines greater than 25 Hp and less than 130 Hp must meet requirements of 40 CFR Part 1048. B&S must warrant the emissions control system on your engine / equipment. See Definition of appropriate use of Emergency Standby below. The emission-related warranty covers all components whose failure would increase an engine’s non-evaporative emissions of any regulated pollutant referenced below.
Manufacturer’s Warranty Coverage: Briggs & Stratton warrants that the engine is free from defects in material and workmanship, and is also designed, built, and equipped to conform to applicable regulations under Section 213 of the Clean Air Act, from the time the engine is sold, until the expiration of its warranty period. This warranty applies to all emission related engine components whose failure would cause engine exhaust emissions to be out of EPA compliance. Further, this warranty also applies to other engine components damaged due to the failure of any of these emissions related components. If a warrantable emissions related component on your engine is defective, the part will be repaired or replaced by B&S at no cost to you including diagnosis, parts, and labor. Warranty coverage period is five years from date of original purchase, and is offered to the original purchaser and each subsequent purchaser so long as Owner’s Warranty Responsibilities are adhered to.
CHONGQING PANDA MACHINERY is the Manufacturer of Record for all Environmental Protection Agency (EPA) compliance issues related to the use and performance of the engine.
Emergency Stationary Engine Definition
An Emergency Stationary Engine is defined as any stationary internal combustion engine whose operation is limited to emergency situations and required testing and maintenance. Examples include stationary engines used to produce power for critical networks or equipment (including power supplied to portions of a facility) when electric power from the local utility (or the normal power source, if the facility runs on its own power production) is interrupted, or stationary engines used to pump water in the case of fire or flood, etc. Stationary engines used for peak shaving are not considered emergency stationary engines. Stationary engines used to supply power to an electric grid or that supply power as part of a financial arrangement with another entity are not considered to be emergency engines. Emergency stationary ICE may be operated for the purpose of maintenance checks and readiness testing, provided that the tests are recommended by Federal, State or local government, the manufacturer, the vendor, or the insurance company associated with the engine. Maintenance checks and readiness testing of such units is limited to 100 hours per year. There is no time limit on the use of emergency stationary engines in emergency situations. The owner or operator may petition the Administrator for approval of additional hours to be used for maintenance checks and readiness testing, but a petition is not required if the owner or operator maintains records indicating that Federal, State, or local standards require maintenance and testing of emergency ICE beyond 100 hours per year. Emergency stationary ICE may operate up to 50 hours per year in non-emergency situations, but those 50 hours are counted towards the 100 hours per year provided for maintenance and testing. The 50 hours per year for non-emergency situations cannot be used for peak shaving or to generate income for a facility to supply power to an electric grid or otherwise supply power as part of a financial arrangement with another entity. For owners and operators of emergency engines, any operation other than emergency operation, maintenance and testing, and operation in non-emergency situations for 50 hours per year, as permitted above is prohibited.
Form NO. 80005429 Rev. A

Coverage *
Briggs & Stratton Power Products Group, LLC will repair or replace, free of charge, any part(s) of the equipment that is defective in material or workmanship or both. This warranty is effective for the time periods and subject to the conditions stated below. For all warranty service, find the nearest Authorized Service Dealer in our dealer locator map at BRIGGSandSTRATTON.COM. THERE IS NO OTHER EXPRESS WARRANTY. WARRANTY COVERAGE FOR IMPLIED WARRANTIES, INCLUDING THOSE OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED TO THE WARRANTY PERIOD SET FORTH BELOW, OR TO THE EXTENT PERMITTED BY LAW. LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES ARE EXCLUDED TO THE EXTENT PERMITTED BY LAW.
Some states or countries do not allow limitations on how long an implied warranty lasts, and some states or countries do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation and/or the above exclusion may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from state to state or country to country.*
* In Australia - Our goods come with guarantees that cannot be excluded under the Australian Consumer Law. You are entitled to a replacement or refund for a major failure and for compensation for any other reasonably foreseeable loss or damage. You are also entitled to have the goods repaired or replaced if the goods fail to be of acceptable quality and the failure does not amount to a major failure. For warranty service, find the nearest Authorized Service Dealer in our dealer locator map at BRIGGSandSTRATTON.COM, or by calling 1300 274 447, or by emailing or writing to salesenquires@ briggsandstratton.com.au, Briggs & Stratton Australia Pty Ltd, 1 Moorebank Avenue, NSW, Australia, 2170.
PARTS 5 years †
LABOR 5 years †
TRAVEL 5 years † ‡
† Enclosure is warranted against surface rust and corrosion for the first year
The warranty period begins on the date of purchase by the first retail or commercial customer. In order to ensure prompt and complete warranty coverage, REGISTER YOUR PRODUCT IN ONE OF THREE WAYS: 1. ONLINE AT BRIGGSANDSTRATTON.COM, OR 2. MAIL THE COMPLETED REGISTRATION CARD, OR 3. CALL 888-575-8226 SAVE YOUR PROOF OF PURCHASE RECEIPT. IF YOU DO NOT PROVIDE PROOF OF THE INITIAL PURCHASE DATE AT THE TIME WARRANTY SERVICE IS REQUESTED, THE MANUFACTURING DATE OF THE PRODUCT WILL BE USED TO DETERMINE THE WARRANTY PERIOD. Registration is not required to obtain warranty service.
of the warranty period. Surface rust and corrosion is defined as any rust or corrosion that has penetrated the paint but has not penetrated through the metal substructure. Enclosure is warranted against rust-through for the first two years of the warranty period. Rust-through is defined as rust or corrosion that has penetrated completely through the paint and metal substructure. † Accessory parts have a separate warranty. Refer to the warranty included
with the accessory part at purchase. ‡ Travel expenses are reimbursed as specified under the Briggs & Stratton
Warranty Guidelines document to authorized Briggs & Stratton dealers for performing applicable warranty repair work.
Warranty terms continue on next page.
is a trademark of General Electric Company and is under license by Briggs & Stratton Power Products Group, LLC.
Copyright © 2013. All rights reserved. No part of this material may be reproduced or transmitted in any form without the express written permission of Briggs & Stratton Power Products Group, LLC.

Only authorized service dealers may perform warranty repairs. Most warranty repairs are handled routinely, but sometimes requests for warranty service may not be appropriate. For example, warranty service would not apply if equipment damage occurred because of misuse, lack of routine maintenance, and shipping, handling, warehousing or improper installation. Similarly, warranty coverage will not be provided if the manufacturing date or serial number(s) on the equipment has been removed or the equipment has been altered or modified. During the warranty period, the authorized service dealer, at its option, will repair or replace any part that, upon examination, is found to be defective under normal use and service. This warranty will not cover the following repairs due to:
This warranty will not cover equipment used in: 1. Equipment used for prime power. For purposes of this warranty, Prime Power is defined as an application in which the generator is a source of power where no electrical power service is available from the UTILITY POWER GRID. If no UTILITY power is available, the generator is considered the prime power source. 2. Used, reconditioned, and demonstration equipment, or rental equipment. Rental use means any use of this product in a temporary or semi-permanently installed rental application. Once equipment has experienced rental use, it shall thereafter be considered rental equipment for purposes of this warranty. 3. Equipment used in life support applications. 4. Failures caused by any force majeure event or external force beyond the manufacturer’s control or Act of God such as, but not limited to freezing, theft, fire, collision, wars or riots, hail, water or flood damage, tornados, hurricanes, or terrorist acts. 5. Use of non-original parts and non-authorized installation or warranty service by unauthorized dealers. 6. Rodent and/or insect infestations.
1. Normal Wear and Maintenance: Outdoor Power Equipment and engines, like all mechanical devices, need periodic parts and service to perform well. This warranty does not cover repair when normal use has exhausted the life of a part or the equipment. Typical wear items include engine oil, oil gauges, o-rings, filters, fuses, spark plugs, anti-freeze, starting batteries, etc. Normal maintenance such as: adjustments, loose or leaking clamps or connections, installation or start- up operations, fuel system cleaning and obstruction due to contamination. 2. Installation, Operation, Maintenance and Storage: This warranty does not apply to equipment or parts that have been subjected to improper or unauthorized installation or alteration and modification, abuse, misuse, negligence, accident, overloading, overspeeding, improper maintenance, repair or storage so as to adversely affect its performance and reliability. 3. Enclosure is not warranted for surface rust or corrosion or complete rust-through that may result due to improper installation, damage to painted surfaces that compromise the paint’s corrosion prevention properties, or if the unit is installed in environments that expose the generator to high levels of corrosive agents.
This warranty also does not include: 1. Any and all expenses incurred investigating performance complaints unless defective Briggs & Stratton materials and/ or workmanship were the direct cause of the problem. 2. The cost of rental equipment used while warranty repairs are being performed (i.e., generators, pumps, etc.)
Warranty terms effective October 1, 2013.
80006513, Rev. A, 1 October 2013

Rated Maximum Load Current (at 40°C/104°F, LP or NG):
125 Amps at 1.0pf
Rated AC Voltage 120/240 Volts
Rated Frequency 60 Hertz
Normal Operating Range -20°F (-28.8°C) to 104°F (40°C)
Output Sound Level per ISO 3744 69 dB(A) at 23 ft. (7 m) at no load
70 dB(A) at 23 ft. (7 m) at normal load
Shipping Weight 1,086 lb (493 kg)
This generator is rated in accordance with UL (Underwriters Laboratories) 2200 (stationary engine generator assemblies) and CSA (Canadian Standards Association) standard C22.2 No. 100-4 (motors and generators).
Phase Single phase


is a trademark of General Electric Company and is under license by Briggs & Stratton Power Products Group, LLC.
Copyright © 2013. All rights reserved. No part of this material may be reproduced or transmitted in any form without the express written permission of Briggs & Stratton Power Products Group, LLC.
80005277 Rev. B
Pages referenced in this manual — manufacturer, support and downloads.
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| Engine is running, but no AC output is available. | 1. Circuit breaker open or defective. 2. Fault in generator control panel. 3. Poor wiring connections or defective transfer switch. | 1. Reset or replace circuit breaker. 2. Contact local service facility. 3. Check and repair. | p.30 |
| Engine runs good at no-load but “bogs down” when loads are connected. | 1. Short circuit in a connected load. 2. Generator is overloaded. 3. Shorted generator circuit. 4. Fuel pressure or mixture is incorrect. 5. Kinked fuel line. i | 1. Disconnect shorted electrical load. 2. Turn off one or more loads. 3. Contact local service facility. n 4. See Gaseous Fuel System in the installation manual. o 5. Remove kink. Replace if necessary. | p.30 |
| Engine will not start; or starts and runs rough. o N | t c r 1. 15 Amp fuse missing or blown. o u f d 2. Fuel supply turned off or depleted. t o 3. Failed battery. r p 4. Fuel pressure is incorrect | 1. Install (new) 15 Amp fuse. See System Control Panel. 2. Open fuel valve(s); check propane tank. 3. Replace battery. 4. See Gaseous Fuel System in the installation manual. | p.30 |
| Engine shuts down during operation. | e 1. Fuel supply turned off or depleted. R 2. Fault code displayed on controller. | 1. Check fuel valves, fill propane tank. 2. Count blinks and refer to Fault Detection System. | p.30 |
| Loss of power on circuits. | 1. Generator circuit breaker is open. 2. Transfer switch problems. | 1. Reset circuit breaker. 2. See transfer switch manual. | p.30 |