Installation and Start-Up Manual



Thank you for purchasing this quality-built GE home generator. We’re pleased that you’ve placed your confidence in the GE brand. When operated and maintained according to the instructions in the operator’s manual, your home generator will provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with standby generators and how to avoid them. This product is only for use as an optional generator system which provides an alternate source of electric power and to serve loads such as heating, refrigeration systems, and communication systems that, when stopped during any power outage, could cause discomfort or inconvenience. Save these original instructions for future reference.
This generator requires professional installation before use. The installer should follow the instructions completely.
You never have to look far to find support and service for your generator. For quick service when you need it most fill out the information below and keep your original receipt with this manual. You may contact Customer Service at (888) 575-8226, or click on SERVICE & SUPPORT at www.homestandbygeneratorsystems.com which provides a list of authorized dealers.
Please fill out the information below and keep with your receipt to assist in unit identification for future purchase issues.
Generator
Model Number
Model Revision
Serial Number
Engine
Model Number



SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries. Safety Symbols and Meanings
The manufacturer cannot possibly anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and the tags and decals affixed to the unit are, therefore, not all-inclusive. If you use a procedure, work method or operating technique that the manufacturer does not specifically recommend, you must satisfy yourself that it is safe for you and others. You must also make sure that the procedure, work method or operating technique that you choose does not render the generator system unsafe.
Explosion Fire Electrical Shock
Rotating Parts Hot Surface Toxic Fumes
Chemical Burn Explosive Pressure Auto Start
Lift Hazard Read Manual
The safety alert symbol indicates a potential personal injury hazard. A signal word (DANGER, WARNING, or CAUTION) is used with the alert symbol to designate a degree or level of hazard seriousness. A safety symbol may be used to represent the type of hazard. The signal word NOTICE is used to address practices not related to personal injury.

and explosive, which could cause burns, fire or explosion resulting in death or serious injury

or structures resulting in death or serious injury. Contact with muffler area could cause burns resulting in serious injury.
to start at any time without warning resulting in minor or moderate injury.
hands, hair, clothing, or accessories resulting in serious injury.

This product is only for use as an optional generator system which provides an alternate source of electric power and to serve loads such as heating, refrigeration systems, and communication systems that, when stopped during any power outage, could cause discomfort or inconvenience.
Every effort has been made to ensure that information in this manual is accurate and current. However, we reserve the right to change, alter, or otherwise improve the product and this document at any time without prior notice.
Only current licensed electrical and plumbing professionals should attempt home generator system installations. Installations must strictly comply with all applicable codes, industry standards, laws and regulations.

If operating the generator below 30°F (-1°C), it is HIGHLY

RECOMMENDED that a Model 6262 Cold Weather Kit
(includes oil warmer and battery warmer) be installed on the 8kW units and that a Model 6030A Cold Weather Kit
(includes oil warmer and battery warmer) be installed on the 10kW units.
These items are available at your local servicing dealer.
For cold weather areas (below 0°F (-18°C)) it is also recommended that a BCI, Size 26, wet lead-acid battery be used of 630 CCA minimum.
If you need more information on this matter, please call (888) 575-8226, between 8:00 AM and 5:00 PM CT.
Avoid damage from dropping, bumping, collision, etc. Store and unpack carton with the proper side up, as noted on the shipping carton.
After removing the carton, carefully inspect the generator for any damage that may have occurred during shipment.
If loss or damage is noted at time of delivery, have the person(s) making delivery note all damage on the freight bill and affix his signature under the consignor’s memo of loss or damage. If loss or damage is noted after delivery, separate the damaged materials and contact the carrier for claim procedures. Parts damaged in shipping are not warranted.
The home generator system is supplied with:
Not included:

Proper installation of the home generator requires the completion of the following tasks:
Carbon Monoxide (CO) Detector/ Smoke Detector
Carbon Monoxide (CO) detector(s) installed and in working
order.
Smoke detector(s) installed and in working order.
Cold weather kit is installed in temperatures below XX°F
(5°C). See Cold Weather Kit.
Correct battery type is installed and fully charged. See
Required permits have been obtained.
Final Installation Considerations.
Generator placed in an area free from Carbon Monoxide
Generator engine oil level is at full mark. See Final
(CO) buildup. See Placement of Standby Generator to Reduce the Risk of Carbon Monoxide Poisoning.
Installation Considerations.
Circuit breaker is in the ON position.
Generator placed in an area compliant to NFPA 37. See
Placement of Standby Generator to Reduce the Risk of Fire.
Utility was shut off to test the operation of generator and
transfer switch. Note any fault codes and make corrections as required.
Generator placed in an area free from water damage. See
Other General Location Guidelines.
AC Voltage Output
Generator placed in an area free from utility and other
Frequency Output
home systems. See Other General Location Guidelines.
Generator placed in a debris free zone. See Other General
Location Guidelines.
Owner Information Name: Address:
Generator placed on flat ground with provisions for water
drainage.See Other General Location Guidelines.
Generator is connected to fuel source with steel flexible
fuel line, has no fuel leaks and conforms to local codes. See The Gaseous Fuel System.
Phone/e-mail:
Unit Information Generator Model: Generator Serial Number:
Proper fuel pressure has been measured with all gas
appliances operating. See The Gaseous Fuel System.
Fuel system has been configured for the proper fuel
supply: Natural gas (NG) or liquefied petroleum ( LP). See Fuel Conversion.
Installing Contractor Information Name: Address:
See NFPA 54.
Fuel pressure at fuel inlet port with generator on and at
full load and all gas appliances turned on and operating
Phone/FAX:
Electrical Generator neutral is connected to Automatic Transfer
Switch. See Generator AC Connection System.
Generator is grounded. See Grounding the Generator and
NFPA 70,NEC.
Generator is connected to the transfer switch with the
specified wiring. See Utility Circuit Connection and Transfer Switch Communication.
Inspector Information Name: Address: Title: Inspection Date:
Generator is connected to the transfer switch with the
specified wiring. #18AWG twisted pair wiring from the generator control panel to the transfer switch is installed in a separate conduit from high voltage wires unless the insulation rating on all wiring is rated for 600V See Transfer Switch Communication.
This generator has been installed per the manufacturer’s
Dipswitches in most transfer switches must be set to
instructions: Installing Contractor Signature: Date:
correspond to the wattage of the generator. See Transfer Switch Operator/Installation Manual.
Operation · Placement · Fuel

Intentionally Left Blank

Before installing the generator, consult with the homeowner and convey the following requirements, which must be satisfied before the installation is complete.
There are two equally important safety concerns in regards to carbon monoxide poisoning and fire. There are also several general location guidelines that must all be met before the installation is considered complete.
Exhaust Side of the Generator

A Exhaust outlet side of weatherproof enclosure.


The arrows in the figure below point to potential points of entry for Carbon Monoxide Gas.
All fossil fuel burning equipment, such as standby generators, contains carbon monoxide (CO) gas in the engine exhaust. CO gas is odorless, colorless and tasteless and is unlikely to be noticed until a person is overcome. CO gas can kill you so it is required that the following is included as part of the installation:
D
F
crawl spaces or other openings that can allow exhaust gas to enter inside or be drawn into a potentially occupied building or structure.


ENGINE EXHAUST

The National Fire Protection Association (NFPA) standard NFPA 37 establishes criteria for minimizing the hazard of fire during the installation and operation of stationary combustion engines. NFPA 37 limits the spacing of an enclosed generator from openings in walls, structures and combustible materials outside the enclosure.
or structures resulting in death or serious injury.
The placement requirements provided are based on compliance to NFPA 37 2010 section 4.1.4 and a full-scale demonstration fire test. Details of compliance testing can be found in section National Fire Protection Association (NFPA) standard NFPA 37 requirements and testing.
Examples of standby generator locations to reduce the risk of fire:
Vertical Clearances Legend for Generator Locations to reduce the risk of fire.
A Standby weatherproof enclosure must be at least 5 ft
(1.5 m) from windows, doors, any wall opening, shrubs or vegetation over 12 inches (30.5 cm) in height.
B Exhaust outlet side of weatherproof enclosure must
have at least 5 ft (1.5 m) minimum clearance from any structure, shrubs, trees or any kind of vegetation.
C Standby weatherproof enclosure must have a
minimum of 5 feet (1.5 m) overhead clearance from any structure, overhang or trees.
5 ft (1.5 m)
5 ft (1.5 m) B
Center of Exhaust Panel
Structure · Standby · Exhaust Direction





5 ft (1.5 m) min 18 in (45.7 cm) min
A Standby weatherproof enclosure must be at least 5 ft
(1.5 m) from windows, doors, any wall opening, shrubs or vegetation over 12 inches (30.5 cm) in height.
B Exhaust outlet side of weatherproof enclosure must
have at least 5 ft (1.5 m) minimum clearance from any structure, shrubs, trees or any kind of vegetation.
C Standby weatherproof enclosure must have a
minimum of 5 feet (1.5 m) overhead clearance from any structure, overhang or trees.

Requirements:
To comply with condition 2, the weatherproof enclosure has been constructed completely of non-combustible materials and full-scale fire tests have been conducted to demonstrate that a fire within the enclosure will not ignite combustible materials outside the enclosure.
NFPA 37 2010, section 4. 1. 4, Engines Located Outdoors. Engines, and their weatherproof housings if provided, that are installed outdoors shall be located at least 1.5m (5 ft) from openings in walls and at least 1.5 m (5 ft) from structures having combustible walls. A minimum separation shall not be required where either of the following conditions exist:
Annex A Explanatory Material
A.4.1.4 (2) Means of demonstrating compliance are by means of full-scale fire tests or by calculation procedures, such as those given in NFPA 555, Guide on Methods for Evaluating Potential for Room Flashover.

The 3/4 inch N.P.T. fuel inlet connector A and electrical inlet location B is shown below.
The home generator is supplied with a base that, unless mandated by local code, does not require a concrete slab.
A ½ inch knock-out is provided for the electrical inlet. This inlet may be enlarged or supplemented to accommodate a maximum conduit size of 1 ½ inches. Ensure that the installed conduit(s) enter the unit in the zone shown in the drawing such that they properly enter the electrical box and do not interfere with the fully opened roof.


The generator weighs more than 330 pounds (150 kg). Proper tools, equipment and qualified personnel should be used in all phases of handling and moving the generator.
Two 60” lengths of 3/4” nominal minimum scheduled 40 steel pipe A, supplied by the installer, are required to lift the generator manually. Insert pipes through the lifting holes B located near the unit’s base.
You may also lift the unit using a “hook and hoist” method attached to the lifting pipes, provided that you use a spreader bar to ensure that the chains or cables DO NOT touch the generator’s roof.

In areas determined to be hurricane prone, it is recommended to anchor the standby generator to concrete. The concrete anchors must be rated to hold 800 lbs ( kg). There are three 7/16 inch hole locations in the base of the generator in which to anchor the unit.

The generator is equipped with an enclosure that has several access panels, as shown.
A Each generator is shipped with a set of identical keys.
Front Panel that is used to access:

To remove roof:

To remove front panel:
To secure front panel:

The information below is provided to assist gaseous fuel system technicians in planning installations. In no way should this information be interpreted to override applicable fuel gas codes. Consult with your local fuel supplier or Fire Marshall if questions or problems arise.


and explosive, which could cause burns, fire or explosion resulting in death or serious injury.
TO THE INSTALLER: Consult with the generator owner(s) and convey any technical considerations that might affect their installation plans before applying these general guidelines.
The following general rules apply to gaseous fuel system piping:

and explosive, which could cause burns, fire or explosion resulting in death or serious injury.

An important consideration affecting the entire installation is the type of fuel used by your generator. The system was factory tested and adjusted using natural gas, but can be converted to use LP vapor. For proper engine function, factors that are inherent to each of these fuels, your location and the duration of possible utility interruptions are important considerations in the following fuel guidelines:
Both LP vapor and natural gas fuel supply pressure at the generator’s fuel inlet port should be between the following levels at full load with all gas appliances turned on and operating.
Ensure that all gas line shutoff valves are OPEN and that adequate fuel pressure is available whenever automatic operation is desired.
Air density is less at high altitudes, resulting in less available engine power. Specifically, engine power will decrease 3.5% for each 1,000 feet (300 m) above sea level and 1% for each 10° F (5.6°C) above 77°F (25°C). Generators located in these conditions must have their transfer switch adjusted appropriately for this power decrease. See Automatic Transfer Switch manual on how to adjust for the power decrease.
Natural gas rating will depend on specific fuel but typical derates are between 10 to 20% off the LP gas rating.
Natural gas or LP engines are certified to operate on natural or liquid propane gas. The emissions control system for this engine is EM (Engine Modifications).
There are numerous on-line or otherwise-published references for fuel pipe sizing. For example, NFPA 54 - National Fuel Gas Code, 2006 (Item #: 320-6031-06) is a common resource.
and explosive, which could cause burns, fire or explosion resulting in death or serious injury.
The installer should consider the specific gravity of gas and compensate for a nominal amount of restriction from bends, fittings, etc. If an unusual number of fittings, bends, or other restrictions are used, refer to federal and local codes for guidance.

The engine of your home generator system is factory calibrated to run on natural gas (NG). It may also be operated on liquefied petroleum (LP) vapor.
To configure the 8 kW fuel system for LP use:
The system is now ready to operate automatically using LP vapor fuel.
To configure the 10 kW fuel system for LP use:
The system is now ready to operate automatically using LP vapor fuel.

Estimated fuel supply requirements at half and full load for natural gas and LP vapor fuels are shown here.




Low Voltage connections to signal fault contacts, transfer switch communication and auxiliary 12VDC power are made via a field connection terminal block in control board area. Compare this illustration with your generator to familiarize yourself with the location of these connections.
A - Two Pin Terminal Block — Used to connect
utility 240 VAC from fuse block in ATS to the control board. Connect only one wire per terminal. B - Fault Contacts — Use NO, COM and NC to hook
up a siren, light, etc. to alert you in case of a fault. Contacts reverse state (NO goes to NC and vice versa) upon a fault condition. C – Transfer Switch Communication (TxRx and
TxRx GND) — Connect to transfer switch control board for communication interface using 18AWG twisted pair wire. D – +LED and GND Connection — Not required for
wireless monitor included with unit. Available for optional hardwired remote system status panel accessory, #6154. E - Eight Pin Terminal Block — Used to connect
UTILITY 2
+LED
GND
N.O.
N.C.
]
] ]
signal wires to the control board. Connect only one wire per terminal. F - Power Connection (Line 1 and Line 2) — Power
D
]
G
GROUND
connection to transfer switch. G - Neutral and Ground Connection — Connect to
transfer switch neutral and ground
F
LINE 2
NEUTRAL
G
TxRxGND · TxRx

A single-phase, three-wire AC connection system is used in the home generator. The stator assembly consists of a pair of stationary windings with two leads brought out of each winding. The junction of leads 22 and 33 forms the neutral lead, as shown schematically and as a wiring diagram. A complete schematic and wiring diagram can be found later in this manual.
11 22 33 44 0
Ground Neutral Line 2 Line 1
The home generator must be installed as part of a system that includes a listed transfer switch, with neutral to ground bonding at the transfer switch in accordance with installation instructions. Unless mandated by local code, additional grounding to earth at the generator is not required. Any grounding at generator must use metal piercing lock washers (or equal), UL listed terminals installed per terminal supplier’s instructions, and comply with national electrical codes and local requirements.

Using installer-supplied minimum 300V, 14 AWG wire, connect each control circuit terminal in the generator (Utility A and Utility B) to the fuse block in the automatic transfer switch.
“240V Utility” leads must be routed in conduit. The “240V Utility” leads deliver power to the generator’s circuit board, optional battery warmer and optional oil warmer. This power also charges the battery. When power on these leads is lost, the generator will start.
Reference illustration on page 26 for further information.
For 10kW Units: Using installer supplied minimum 300V, 90°, 8 AWG copper wire, or 300V, 90°, 6 AWG aluminum wire*, connect generator power output Line 1, Line 2, neutral and ground to the corresponding Line 1, Line 2, neutral and ground in the transfer switch.
For 8kW Units: Using installer supplied minimum 300V, 90°, 10 AWG copper wire, or 300V, 90°, 8 AWG aluminum wire*, connect generator power output Line 1, Line 2, neutral and ground to the corresponding Line 1, Line 2, neutral and ground in the transfer switch.
*Use National Electric Code for correction factors and wire size calculations.
*Use National Electric Code for correction factors and wire size calculations.
When making connections, obey wire type and torque specifications printed on the circuit breaker and neutral/ ground connectors.
Using installer supplied #18 AWG twisted pair conductors, no greater than 200 ft in length, connect Tx Rx and Tx Rx GND from the generator terminal block A to T/R and GND on the transfer switch control board B.

Utility Circuit Connection · Generator Power Connection · Transfer Switch Communication

The generator control board, located inside the generator, under the roof, is shown below. Brief descriptions of the controls used during installation are:
A - Menu/Programming Navigation Buttons — See Menu
- “AUTO” LED — LED will light when unit is placed into
section for details B - Mini USB Port — Authorized Dealer Service Use Only C - Generator Operation Control Buttons —
Auto mode. LED will blink if exercise cycle is not set or set to OFF. D – 15 Amp Fuse — Protects the home generator DC
control circuits. If the fuse has ‘blown’ (melted open) or was removed, the engine cannot crank or start. Replace the fuse using only an identical ATO 15A fuse. One spare fuse is supplied with the unit. E - Cover — This protective cover must be opened to
access the fuse and the USB port. F - Digital Display — Displays generator mode, menu
options, service codes, and service engine indicators
OFF must be pressed and held for more than 5 seconds in order to reset service codes.
More information may be found in Controls in the operator’s manual.
E
B
D

The following chart shows the icons for the buttons that control the system control panel.
MENU ENTER THE MENU (VIEW SETTINGS) PRESS TO CONFIRM SELECTION WHEN PROGRAMMING.
RIGHT ARROW TOGGLE THROUGH MENU OPTIONS SETTING SYSTEM PARAMETERS
LEFT ARROW TOGGLE THROUGH MENU OPTIONS SETTING SYSTEM PARAMETERS
MANUAL MODE USED TO MANUALLY START THE GENERATOR. PRESS AND HOLD BUTTON TO START THE GENERATOR.
OFF TURNS OFF RUNNING GENERATOR, PREVENTS UNIT FROM STARTING, AND RESETS ANY DETECTED FAULTS.
NORMAL OPERATING POSITION. PRESS AND HOLD BUTTON TO PUT UNIT INTO AUTOMATIC MODE. IF A UTILITY POWER OUTAGE IS SENSED, THE SYSTEM WILL START THE GENERATOR. WHEN UTILITY POWER IS RESTORED, AUTO LETS THE ENGINE STABILIZE INTERNAL TEMPERATURES, SHUTS OFF THE GENERA- TOR, AND WAITS FOR THE NEXT UTILITY POWER OUTAGE.
The following chart describes key sequences for accessing different programming modes;
PRESS AND HOLD [ARROW LEFT AND ARROW RIGHT] FOR THREE SECONDS TO ENTER THE PROGRAM MODE.
PRESS AND HOLD [ARROW LEFT, ARROW RIGHT AND ESC] FOR THREE SECONDS TO ENTER THE ADVANCED SETTINGS MODE.
PRESS AND HOLD [MENU AND ESC] FOR THREE SECONDS TO ENTER THE WIRELESS LINKING MODE. (ONLY APPLICABLE ON SOME MODELS).
ok · ok

For general set up, press and hold the left arrow and right arrow for 3 seconds. Follow the prompts as outlined below.
SET DATE ok MONTH FLASHING ok ok ok
SET TIME ok HOURS FLASHING ok ok ok
AM/PM FLASHING
OFF If set to OFF, display will read: EXERCISE CYCLE OFF ok or
MIN FLASHING ok DAY OF WEEK
EVENT
LOG ok Display will scroll last service code event, date, time, and temperature of when the event occured. ok

In Automatic Mode, the display screen will display via scrolling text:
GENERATOR READY or SERVICE CODE DESCRIPTION
(When Generator NOT Running - Auto Mode)
(When Generator Running - Auto Mode)
To view general system parameters, press the MENU button.
The following will scroll across the digital display and then move to the next item:
The user can press the LEFT ARROW or RIGHT ARROW at any time to move to the next item.
The user can press ESCAPE to go back to GENERATOR READY.
If no user inputs are made for 10 seconds after all the items have been displayed, the control board will reset to
GENERATOR READY.
EXERCISE CYCLE

Advanced setting parameters are preset at the factory for a typical installation. To view Advanced Settings items and/or to change items, follow the instructions listed below.
For advanced menu items, press and hold the left arrow, right arrow, and escape key for 3 seconds. Follow the prompts as outlined below.
50/60 Hz FLASHING ok
PHASE
VOLTS FLASHING
Stepper Motor will sweep through throttle
range for dealer visual verification

Refer to Service Code Detection System in the operator’s manual for more detailed information.
The generator may have to run for long periods of time with no operator present. For that reason, the system is equipped with sensors that automatically shut down the generator in the event of potentially damaging conditions, such as low oil pressure, high temperature, over speed, and other conditions.
This engine is shipped from the factory pre-run and filled with synthetic oil (API SJ/CF 5W-30). This allows for system operation in a wide range of temperature and climate conditions. Before starting the engine, check oil level as described in Maintenance of the Operator’s Manual.
The use of synthetic oil does not alter the required oil change intervals described in the Operator’s Manual.
For operation of temperatures below 30°F (-1°C), the use of fully synthetic oil (minimum API SJ) of viscosity 5W30 is required.
The installer must supply and install a rechargeable 12 volt starting battery. The starting battery MUST conform to the specifications shown in this chart.

Terminal Type Top post type battery Top post type battery
Install the battery as described in Servicing the Battery in the Maintenance section of the operator’s manual. Always make sure the NEGATIVE cable is connected last and that the red POSITIVE terminal insulator is fully in place.

Use the supplied tie-down strap to secure the battery to the unit. Each end of the strap should be attached to the existing tabs in the base of the unit.

The unit has been set-up for NG operation at the factory. Fuel conversion, if needed, must be completed prior to performing these steps. See Fuel Conversion.
Before operating the home generator or placing it into service, inspect the entire installation carefully. Then begin testing the system without any electrical loads connected, as follows:
When the generator is started for the very first time, it will require that air in the gaseous fuel lines be purged. This may cause the engine to run roughly for a few minutes.
to start at any time without warning resulting in minor or moderate injury.

The generator’s control board constantly monitors utility voltage. Should utility voltage drop below a preset level, the control board will signal the engine to crank and start.
Utility Voltage Pickup Sensor
This sensor monitors utility power voltage. When utility voltage is restored above 80 percent of the nominal source voltage, a time delay starts timing and the engine will go to engine cool-down.
When utility voltage is restored above a preset voltage level, the engine is signaled to shut down.
The actual system operation is not adjustable and is sequenced by sensors and timers on the control board, as follows:
When utility power is sensed and the load transfers to the utility source, the engine will go into a cool down period as described below:
Utility Voltage Dropout Sensor
The generator is equipped with an exercise timer. During the exercise period, the unit runs for approximately 20 minutes and then shuts down. Electrical load transfer DOES NOT occur during the exercise cycle (unless an utility power outage occurs).
through the days of the week, Once the day is selected, hit the “OK” button.
through between 1 and 12. Choose the hour of day you want the generator to exercise then hit the “OK” button.
The generator will only enter the exercise cycle if the unit is in the AUTO mode and this exact procedure is followed.
between :00 and :59. Choose the minute of the day you want the generator to exercise then hit the “OK” button.
To set the exercise timer: NOTICE The generator is set with a default exercise cycle setting of Tuesday at 2:00 P.M, Central Time. To change the cycle setting, proceed to the following steps: 1. Choose the day and time you want your generator to exercise.
between AM and PM. Once chosen, hit the “OK” button.
If you want to change the day and time the unit exercises, simply perform the procedure again.
To turn off the generator exercise cycle, go to the OFF selection within the day of the week menu and press OK. The display will then scroll: EXERCISE CYCLE OFF.
Engine Cool-down Timer

The generator is supplied with a battery-powered, wireless monitor.
Compare the illustration below with your monitor to familiarize yourself with these important components.
The monitor communicates wirelessly with the generator control panel. The monitor may be placed in a suitable location in the home. The system has a line-of-sight range of about 200 feet, but this distance will decrease if the signal has to pass through walls or other objects.
The wireless monitor communicates with the generator, every 10 minutes and will display the status via LED lights on the front of the monitor.
B
1 low battery voltage 2 low fluid level 3 under/over voltage 4 engine does not start
# of flashes service needed
5 low frequency 6 engine overspeed 7 high temperature 8 transfer switch
G
DEALER NAME
F
DEALER PHONE

The wireless monitor includes an antenna that was installed at the factory.
Before shipping, the magnetic-backed antenna was moved to the side of the generator to prevent damage (A).
Before starting the wireless monitor, mount the antenna on the top of the unit (B).



Standard Operation:
Wireless Monitor Status LED’s
Other:
Before placing the generator system into service, inspect the entire installation carefully, utilizing the Installation Checklist on page 9.
This completes the installation and start-up instructions. The operator’s manual provides full details on Operation, Maintenance and Troubleshooting for this generator system.
LED Lighting Codes


Schematic Diagram - 10kW


Wiring Diagram - 10 kW


Schematic Diagram - 8kW


Wiring Diagram - 8kW

is a trademark of General Electric Company and is under license by Briggs & Stratton Corporation.
Copyright © 2013. All rights reserved. No part of this material may be reproduced or transmitted in any form without the express written permission of Briggs & Stratton Power Products Group, LLC.