Digital Energy ™ ML Series Uninterruptible Power Supply 350-500-700-1000 VA Manufactured by: GE Digital Energy General Electric Company Telephone +41 (0)91 / 850 51 51 CH – 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44 Switzerland Website www.gedigitalenergy.com Technology for the Digital World. ver 1.1 - GB ML Series UPS



GB
Digital Energy ™ ML Series
350-500-700-1000 VA 1000 VA 1000 VA 1000 VA Please read these instructions carefully before installation and start-up of the Digital Energy™ ML Series UPS. Keep this manual in a safe place for future reference.
CONTENTS 1 INTRODUCTION 2 1.1 Introduction 1.2 Safety Rules 1.3 Transport / Storage 2 INSTALLATION 2 2.1 Installation Rules 2.2 Installation Procedure 3 OPERATION 4 3.1 Start-up 3.1.1 Start-up, mains available 3.1.2 Start-up, mains not available (‘battery start’) 3.2 Use: Normal Operation 3.2.1 Normal operating conditions 3.2.2 Self test 3.2.3 Auto-off (no-load shutdown) 3.2.4 Switching off 3.3 Use: Status and Alarm Indications 3.3.1 Charger on 3.3.2 Normal operation 3.3.3 On battery 3.3.4 Battery low 3.3.5 Replace battery 3.3.6 Overload 3.3.7 Self test 4 COMMUNICATION 6 5 MAINTENANCE 7 5.1 General 5.2 Fuses 5.3 Batteries 5.3.1 General 5.3.2 Battery replacement 6 TROUBLESHOOTING 8 7 SPECIFICATIONS 9 © General Electric. All rights reserved; reproduction without permission prohibited. This manual may be subject to change; no liability can be accepted for any error or omission.
OPM_MLE_LTE_350_1K0_1GB_V011 1 DE ML Series: user manual 1.1 (GB)

2 - Installation
OPM_MLE_LTE_350_1K0_1GB_V011 2 DE ML Series: user manual 1.1 (GB)

2.2 Installation Procedure 1. Switch off your computer, and unplug it from the socket-outlet. 2. Disconnect the power cord from the computer (rating 250Vac/10A) and connect this cord to the male input socket (2) at the rear of the UPS (figures on the right show simplified ML 350-700 model). 3. Using the output cord provided, connect the computer to the appliance outlets (3) of the unit. 4. Connect the mains cord of the UPS to a working, grounded AC wall socket outlet. The green LED 'LINE' will blink now: mains power is available and the batteries are charging. 5. For best results, allow the UPS to recharge the batteries for a period of approx. 10 hours. It is acceptable to use the UPS without first charging the battery, but the runtime may be reduced. 6. For advanced communication possibilities, the RS232 interface port (4) can be connected to a computer system. See chapter 4.


OPM_MLE_LTE_350_1K0_1GB_V011 3 DE ML Series: user manual 1.1 (GB)

OPM_MLE_LTE_350_1K0_1GB_V011 4 DE ML Series: user manual 1.1 (GB)

o status indications the operating mode ! low priority alarms abnormal operating situations !! high priority alarms situations in which the actual output voltage of the UPS is no longer guaranteed; immediate action should be taken

Operating modes and corresponding indications, see 3.3.1 – 3.3.7. * Reset Buzzer alarm: Press keypad ‘ON’ for 2 seconds. Only the actual buzzer is muted; a next alarm re-activates the buzzer. A buzzer reset does not affect the computer interface alarm. 3.3.1 Charger on Mains on, UPS output off, the batteries are charging. 3.3.2 Normal operation Mains on, UPS output on, see also 3.2.1.
OPM_MLE_LTE_350_1K0_1GB_V011 5 DE ML Series: user manual 1.1 (GB)




ML 350-700 ML 1000
OPM_MLE_LTE_350_1K0_1GB_V011 6 DE ML Series: user manual 1.1 (GB)

OPM_MLE_LTE_350_1K0_1GB_V011 7 DE ML Series: user manual 1.1 (GB)

Whenever a malfunction occurs, first check external factors (e.g. connections, temperature, humidity or load) to determine whether the problem is caused by the unit itself or by its environment. Subsequently check the input fuse: it may be blown. If so: replace the fuse (see 5.2) and be sure that the UPS is not overloaded. The following chart is a simple troubleshooting checklist only. If the suggested solution does not succeed, or if the information is insufficient to solve the problem, please contact your dealer or consult www.gedigitalenergy.com
Blown input fuse Output overload Reduce load, replace fuse
System failure Please contact your dealer or consult www.gedigitalenergy.com
No output voltage during self test (3.2.2)
System failure Please contact your dealer or consult www.gedigitalenergy.com
Only battery start possible Blown input fuse See above
No communication between computer and UPS
Computer interface problem Check interface cable and attached computer.
Blown input fuse See above UPS operates on battery though mains is present Very high, low or distorted mains voltage
Check mains voltage, contact qualified electrician
Continuously sounding buzzer mains present
UPS overload Reduce load
Continuously sounding buzzer mains not present
UPS overload in battery mode Reduce load
UPS does not provide the expected back-up time, no alarm ‘replace battery’
Charge the battery. If the battery is near the end of its service life, consider replacing the battery even if the ‘replace battery’ alarm is not yet active.
Allow the UPS to recharge the batteries Blinking LED ‘BAT’, intermittent buzzer
Battery test just after installation or mains failure
Weak battery Read 5.3
UPS output switches OFF Battery depleted during mains failure: end of runtime
Wait until mains returns
Wait until mains returns
Load is less than 5% of rated output and no mains power is present (no-load shutdown function is active)
Load is more than 150% of rated output
OPM_MLE_LTE_350_1K0_1GB_V011 8 DE ML Series: user manual 1.1 (GB)
Reduce load

ML Series model : 350 500 700 1000 Ratings Voltage Amperes (VA) / Watts (W) : 350 / 210 500 / 300 700 / 420 1000 / 600 Input AC input voltage (Vac) : 220 - 240 AC input voltage window (Vac) (mains) : 140 - 300V 140 - 300V 140 - 300V 160 - 265V Maximum AC input voltage (Vac) : 350 Minimum start-up AC voltage (Vac) : 150 150 150 170 Input frequency (Hz) : 50 Input frequency range : nominal ± 10 % Typical no-load power consumption, normal operation (W) : 12 12 27 27 AC input current (A) : 2.5 3.6 5 6.3 AC input fuse (A) : 5 5 6.3 10 Output AC output voltage (Vac) : 230 (suitable for 220-240 Vac loads) AC output voltage tolerance : nominal ± 5% (before battery low) Output frequency (Hz) : 50 Output frequency stability (Hz) : < ± 0.1 (battery operation) Output waveform : step sine wave Power factor : 0.6 (0.7 at 90% load) Transfer time (ms) : typically 4, max 10 Buck/Boost voltage regulation : if the input voltage is within the input voltage window, the output voltage varies between 198-265Vac Batteries (ratings given for 25°C) Nominal voltage (Vdc) : 12 12 24 24 Number x capacity (Ah) of batteries : 1x5 1x7 2x5 2x7 Type : 12Vdc, sealed lead acid, maintenance free Service life : up to 6 years (depending on use) Recharge current (A) : 0.5 0.7 0.5 0.7 Battery recharge time for 80% capacity (hours, approximation) : 3 Runtime in minutes VA / Watts 100/ 60 25 40 60 85 350/210 3 8 14 24 500/300 - 3 7 11 700/420 - - 3 7 1000/600 - - - 3 General Weight (kg) : 6.5 7.5 11 13 Dimensions (hxwxd, mm) : 150x110x300 150x110x420 150x110x450 Enclosure / protection : steel-plastic / IP20 Colour (operating panel / case) : RAL 9006 (aluminium) / RAL 7035 (light grey) Environment Safety : EN 50091-1-1 (EN 60950) Electromagnetic compatibility : EN 50091-2 Ambient temperature : -10 to +40°C; Sound at 1 meter : < 35 dB(A) Maximum relative humidity : 95% (non-condensing)
OPM_MLE_LTE_350_1K0_1GB_V011 9 DE ML Series: user manual 1.1 (GB)