GE Digital Energy
NetPro 19"
Uninterruptible Power Supply 600 - 1500 VA

Manufactured by:
GE Digital Energy General Electric Company Telephone +41 (0)91 / 850 51 51 CH – 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44 Switzerland Website www.gedigitalenergy.com

USER MANUAL
NetPro 19" Uninterruptible Power Supply Uninterruptible Power Supply Uninterruptible Power Supply Uninterruptible Power Supply
Please read these instructions carefully before installation and start-up of the NetPro 19” UPS. Keep this manual in a safe place for future reference.
1 INTRODUCTION 2 1.1 Introduction 1.2 Safety Rules 1.3 Transport / Storage
2 INSTALLATION 2 2.1 Installation Rules 2.2 Installation Procedure
3 OPERATION 4 3.1 Start-up 3.1.1 Start-up, mains available 3.1.2 Start-up, mains not available (‘battery start’) 3.2 Use: Normal Operation 3.2.1 Normal operation conditions 3.2.2 Load indication 3.2.3 Auto-off (no-load shutdown) 3.2.4 Automatic bypass switch 3.2.5 Switching off 3.3 Use: Status and Alarm Indications 3.3.1 Charger on 3.3.2 On-line: normal operation 3.3.3 On battery 3.3.4 Battery low (end of runtime) 3.3.5 On bypass 3.3.6 Bypass out of limits 3.3.7 Overload 3.3.8 Overtemperature 3.3.9 Replace battery 3.3.10 Programmed shutdown 3.4 Use: Setup Mode 3.5 Battery Management
4 COMMUNICATION 9 4.1 RS232 Port 4.2 Relay Interface Card (option) 4.3 SNMP Interface Card (option)
5 OPTIONAL FEATURES 10 5.1 Extended Runtime (NetPro 19” 1000) 5.2 PowerFLAG SerVICe Box for Modem Connection
6 MAINTENANCE 10 6.1 General 6.2 Batteries 6.2.1 General 6.2.2 Battery Replacement
8 SPECIFICATIONS ........................................................................................13
© GE Digital Energy. All rights reserved; reproduction in whole or in parts without permission is prohibited. This manual may be subject to change; no liability can be accepted for any error or omission.
OPM_NPE_19X_600_1K5_2GB_V030 1 GE DE NetPro 19” 600-1500: User manual 3.0 (GB)

The General Electric (GE) Digital Energy NetPro 19” UPS, a truly on-line uninterruptible power supply, protects your equipment from all forms of power interference, including complete power failures.
x CAUTION: RISK OF ELECTRICAL SHOCK. The UPS contains batteries. The appliance outlets may be electrically live, even when the UPS is disconnected from the mains. x The UPS contains potentially hazardous voltages. Do not open the UPS, there are no user serviceable parts inside. x All maintenance and service work, except for replacement of the batteries, should be performed by qualified service personnel.
x No liability can be accepted for any transport damage when the equipment is shipped in non- original packaging. x During transport the battery drawer must either be removed or fixed with two screws at the rear side of the UPS (A, fig. 1). x Store the UPS in a dry location with the batteries in a fully charged state. Storage temperature must be within -20 +45 qC. If the unit is stored for a period exceeding 3 months, optimal battery lifetime is obtained if the storage temperature does not exceed 25°C. x If the unit is stored for an extended period of time, the batteries must be recharged periodically. Be sure that the battery drawer is connected to the UPS. Subsequently connect the unit to a wall outlet and recharge the batteries for 24 hours: - if the storage temperature is within -20 and +30°C: every 3 months, - if the storage temperature is within -20 and +45°C: every month. Please note that with completely discharged batteries the UPS will not start at all. External charging or replacement of the batteries will be necessary.
The shipping box contains a NetPro 19” UPS, two IEC male-female power cords, a data cable, a CD ROM and this manual. Inspect the UPS for damage after unpacking. If any damage is present please immediately notify the carrier and place of purchase.
Before making any connection and switching on the NetPro 19” UPS, please check the following conditions: x your mains supply is 220 - 240 Volts and 50 Hz (if the mains frequency is 60Hz, the output frequency of the UPS can be changed, see section 3.4), and x the total power demand of the connected equipment does not exceed the rated output power of the NetPro 19” UPS (indicated on the rating label).
x The UPS is intended to be used in normal domestic and office situations. x Protect the UPS, according to the wiring rules, with a 16A D-type fuse. x The UPS must be powered from a single phase grounded wall outlet. Do not use extension cords. x Avoid locations that are excessively humid, near water, near heat sources or in direct sunlight. x The ambient temperature should not exceed 40qC. Optimal battery lifetime is obtained if the ambient temperature does not exceed 30qC. x It is important that ventilation air can move freely around and through the unit. Do not block the air vents. x Do not plug appliances such as electric heaters, toasters and vacuum cleaners into the UPS. x Be careful when connecting laser printers: be sure that the demanded power does not exceed the capacity of the UPS. x The sum of the leakage currents of the UPS and the connected loads should not exceed 3.5mA.
OPM_NPE_19X_600_1K5_2GB_V030 2 GE DE NetPro 19” 600-1500: User manual 3.0 (GB)


3. 1000VA model only: Battery extension module(s) can be installed to increase the battery runtime. Connect the DC connector of the battery module (7, fig. 2) to the DC socket of the UPS (2, fig. 1/2). You will hear a click when the cable is properly installed. Block the DC connector: install the small locking plate (7a, fig. 2) that came with the battery module, and fasten it with the screw provided. Using the DC connector of the battery module (not shown) you can install a second, third, etc. module. See also section 5.1.


OPM_NPE_19X_600_1K5_2GB_V030 3 GE DE NetPro 19” 600-1500: User manual 3.0 (GB)

Please refer to figure 6.
3.1.1 Start-up, mains available 1 Press keypad 'I' (14, fig. 6) briefly; LED ‘on’ (already blinking) will illuminate continuously now. 2 The equipment connected to the UPS can now be switched on.
3.1.2 Start-up, mains not available If the mains input is absent (power cord not connected, or mains failure): 1 Press keypad 'I' until the buzzer sounds. The LEDs 'on' and 'on battery' (13, fig. 6) will illuminate. The UPS operates on battery: it discharges the batteries.
3.2.1 Normal operation conditions: x the mains supply is present, x the UPS is on, x the load does not exceed the capacity of the UPS and x the operating temperature is below alarm level
3.2.2 Load indication (fig. 5) 1 During normal operation, press keypad 'I' briefly. 2 Yellow LEDs will blink during 3 seconds, the number is load dependent (in case of overload LED 'alarm' (9, fig. 6) blinks as well).
3.2.3 Auto-off (no-load shutdown) If this function is activated, the UPS will switch off during a mains failure when the load is less than 5% of the maximum load. In this way unnecessary discharging of the batteries is avoided. The unit will automatically turn on again when mains power is restored. The default setting of the no-load shutdown function is: activated. Changing of the setting is described in 3.4.
3.2.4 Automatic bypass switch The UPS is equipped with an automatic bypass switch. This switch automatically transfers the load to the mains if the UPS is unable to deliver the demanded output power due to overload or overtemperature. The UPS will switch back to normal operation when the overload has been removed or the temperature has dropped below alarm level. If a power failure occurs during bypass operation, the UPS will switch to battery operation and eventually, when the batteries are depleted, output power is lost. If the UPS functions under overload or overtemperature conditions it may not be able to protect the load. See also 3.3.6 and 3.4.
3.2.5 Switching off 1 Press keypad ‘0’ (15, fig. 6) for 1 second. If the UPS is switched off the output will always be absent for a few seconds to ensure that the connected equipment is able to reboot. 2 If electric isolation is required, unplug the power cord from the wall outlet.
OPM_NPE_19X_600_1K5_2GB_V030 4 GE DE NetPro 19” 600-1500: User manual 3.0 (GB)

!! high priority alarms : situations in which the actual output voltage of the UPS is no longer guaranteed; immediate action should be taken
11 12 13 14 15
Indicators on front panel
on alarm on by-
progr. shutd.
repl. batt.
on batt. buzzer*
o Charger on (3.3.1) -
o Normal operation (3.3.2)
! On battery (3.3.3) - 1x/8 s.
!! Battery low (3.3.4) - -
1x/s.
!! On bypass (3.3.5) -
1x/s.
! Bypass out of limits (3.3.6) - 1x/8s.
!! Overload (3.3.7) -
1x/s.
!! High temperature (3.3.8) -
1x/s.
! Replace battery (3.3.9)
o Progr. shutdown pending (3.3.10) -
- 1x/8s.
o Progr. shutdown in progress (3.3.10) -
Operating modes and corresponding indications, see 3.3.1. – 3.3.10.
- = intermitting = continuous * = resettable: press push button ‘I’ > 2 secs.
OPM_NPE_19X_600_1K5_2GB_V030 5 GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
pass · Situation

3.3.1 Charger on The batteries are charging, see 2.2 step 7.
3.3.2 On line: normal operation See 3.2.1.
3.3.3 On battery The UPS uses the energy stored in the batteries: see chapter 7 ‘Batteries - runtime’. The UPS will shutdown x after the batteries have been discharged (automatic restart), or x if keypad 'O' is pressed (restart via front panel required) or x if a 'UPS shutdown' command is given by the computer (restart via front panel required).
Runtime indication (fig. 7) During battery operation, press keypad 'I' briefly. The 4 yellow LEDs indicate during 3 seconds the remaining runtime for the actual load.
3.3.4 Battery low (end of runtime) The batteries are nearly discharged: the remaining runtime is less than 2 minutes. Controlled shutdown of any computer equipment is absolutely necessary at this point. If the UPS operates at 100% load, the shutdown procedure should be completed within 2 minutes after the 'battery low' alarm started. If only part of the output capacity of the UPS is used this period can be longer, with aged batteries this period can be shorter. When the batteries are fully discharged, the UPS is no longer able to power the connected equipment.
3.3.5 On bypass The bypass switch connected the load directly to the mains supply due to either overload or overtemperature. If keypad 'I' is momentarily pressed, the 4 yellow LEDs function during 3 seconds as a load indication. See also 3.2.2. If 4 yellow LEDs and the red LED illuminate, bypass operation is caused by an overload. If only yellow LEDs illuminate (the red LED is off) during load indication, bypass operation is caused by overtemperature. Take appropriate measures: reduce load and/or temperature.
3.3.6 Bypass out of limits The mains voltage or mains frequency are outside bypass input tolerance but inside UPS input tolerance (see chapter 7). Bypass operation is inhibited: if for whatever reason the UPS is not able to deliver the required output, output power is lost. If the input frequency is often out of tolerance – during which bypass operation is inhibited and an alarm is generated – it may be useful to disable the bypass function after which the unit operates as a UPS without automatic bypass switch. See 3.4.
3.3.7 Overload The demanded power exceeds the normal capacity of the UPS. If keypad 'I' is momentarily pressed to obtain a load indication all yellow LEDs will blink, and the red LED will remain blinking. The alarm occurs when the load is > 100%. If the load exceeds 150% the UPS will immediately switch to bypass, assuming that the conditions for a transfer to bypass are fulfilled. If an overload condition between 110-150% persists, the UPS will eventually also switch to bypass operation. During an overload the UPS may automatically switch off within a few minutes (load dependent) and output power is lost: x if a transfer to bypass is inhibited (see 3.3.6), or x if the bypass function has been disabled (see 3.4), or x if the UPS operates on battery (see 3.3.3). To avoid these problems, be absolutely certain that the power demands of the protected equipment are within the limits of the UPS.
OPM_NPE_19X_600_1K5_2GB_V030 6 GE DE NetPro 19” 600-1500: User manual 3.0 (GB)

3.3.8 High temperature The LED Indication is the same as during overload (see 3.3.7), but if keypad 'I' is momentarily pressed to obtain a load indication the red LED will go out. Overtemperature can be caused by: x extreme environmental temperature, x lack of proper ventilation, x overload situation. Take appropriate measures; if the temperature is allowed to rise further the UPS will switch to bypass operation (if allowed). If bypass operation is inhibited, the unit will switch off and output power is lost.
3.3.9 Replace battery Either the batteries are almost chemically worn out or the battery wiring, including the battery fuse, is faulty. If the batteries are aged, they must be replaced as soon as possible to ensure full protection for your equipment (see 6.2). Perhaps the 'replace battery' alarm occurs after a test which you started immediately after installation or after a power failure. In this case the alarm may be incorrect as the batteries have been (partly) discharged during transport or storage or during the power failure. Allow the UPS to recharge the batteries. See also 3.5.
3.3.10 Programmed shutdown The UPS monitoring software allows you to program a 'sleep period' of the UPS by sending two commands to the UPS: x shut down after # minutes (blinking LED), and subsequently: x shut down during # hours (continuous LED). During the 'sleep period' the UPS is not completely switched off as it has to keep track of the remaining sleep time. However, if a mains failure occurs during the sleep period and the battery capacity eventually drops below 80% of the normal capacity, the UPS will automatically switch off in order to save battery power. When the mains returns the UPS will start up automatically. The programmed sleep time however is lost. The programmed shutdown in progress can be cancelled: x press keypad 'I' for at least 5 seconds to cancel shutdown and switch UPS on. x press keypad '0' for at least 5 seconds to cancel shutdown and switch UPS off.
The setup mode can only be entered if the UPS is connected to a live wall outlet and switched off (LED 'on' blinks). Press keypads 'O' and 'I' simultaneously. Press 'O' before 'I', otherwise the unit will be switched on. Three yellow LEDs can illuminate:
LED is LED indicating on* off
'on bypass' : the bypass switch is active not active 'progr. shutdown' : the no-load shutdown is active not active 'replace battery' : the output frequency is 50 Hz 60Hz
1 Scroll through the three functions with keypad 'I', the one selected blinks. 2 Toggle the setting of the selected function by pressing 'O' during approx 1 sec. (LED does not blink anymore) 3 Store the new settings and leave the setup mode by pressing 'O' and 'I' simultaneously.
OPM_NPE_19X_600_1K5_2GB_V030 7 GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
* = default

Maximum battery life and reliability are obtained by the following features:
x Quick battery test The quick battery test checks whether the batteries and their wiring are healthy. If a quick battery test shows that the batteries are close to being worn out, a 'replace battery' alarm will be generated (see 3.3.9). The batteries must be replaced as soon as possible (see 6.2).
Automatic battery test The NetPro 19” UPS conducts periodic automatic battery tests:
x 5 hours after manual switch-on x 5 hours after return of mains following any power failure, and x 30 days from the last battery test
Manual battery test A quick battery test can be initiated manually through UPS software, via the RS232 Interface Port. For details please refer to the manual of your monitoring software. NOTE: If the test is started manually immediately after installation or after a power failure, the UPS may generate a false 'replace battery' alarm as the batteries have been (partly) discharged during transport/storage or during the power failure.
x Deep battery test A deep battery test, to be initiated through the UPS software via the RS232 port, checks the actual battery capacity in order to ensure accurate runtime prediction. During a deep battery test the batteries will be discharged until 'battery low' alarm level. Please note that immediately after a deep battery test the expected runtime is very short: allow the UPS to recharge its batteries. For details please refer to the manual of your UPS software.
x Temperature compensated battery charging This feature adjusts the battery charge voltage to the ambient temperature. As a result poor charging of the batteries under low temperature conditions and overcharging of the batteries under high temperature conditions are avoided.
x Load dependent battery-end-voltage The allowable final battery voltage depends on the discharge current: the higher the current, the lower the 'end-of-discharge' battery voltage. In this way maximum battery capacity is obtained without overdischarging. Overdischarging would result in shortened service life and failure to recover normal capacity.
x Charger off at end of charge Only charging when necessary, increases battery lifetime.
x Automatic boost charge This feature reduces the battery recharge time considerably: totally depleted batteries will be recharged to 90% in approx. 1.5 hours, provided that discharging took place at 100% load.
OPM_NPE_19X_600_1K5_2GB_V030 8 GE DE NetPro 19” 600-1500: User manual 3.0 (GB)

The RS 232 Port is a plug-in interface port (9-pin, Sub-D, male) which enables advanced communication between the UPS and the computer (UPS software required). The interface port is operative as soon as the mains power cord is plugged into a live wall outlet, even if the UPS is switched off. We strongly recommend to use only original GE Digital Energy software products in combination with the interface port.
Pin # Function 1 RS232 input (UPS shutdown) 2 RS232 output 3 General alarm1)
4 Plug and Play 5 Common 6 Bypass active 7 Battery low 8 UPS connected 9 Mains failure
The card is equipped with potential free change-over contacts for the following alarms:
This card allows the data interface to be connected directly to an Ethernet network. For more information please refer to the user manual that comes with the interface card.
OPM_NPE_19X_600_1K5_2GB_V030 9 GE DE NetPro 19” 600-1500: User manual 3.0 (GB)

Apart from the options described in 4.2 and 4.3 the following options are possible:
Extended runtime can be obtained by connecting a separate battery extension pack to the UPS. In this case the UPS must be informed about the new total battery capacity to allow a reliable recalculation of the available runtime (please contact your dealer). Dependent of the charge condition of the new batteries the new runtime calculations may temporarily be unreliable. The additional batteries increase the recharging time for the unit, all other operational information is the same as for standard models. It is not allowed to connect an external charger to the UPS!
If you connect the PowerFLAG SerVICe Box between the communication port of the UPS and a modem, a programmed number can be dialed in case of a UPS alarm. It also allows service personnel to dial in and check the status of the UPS to perform remote diagnostics. This way service costs, specially in remote areas, can be reduced considerably.
The UPS is virtually maintenance free: take care of proper environmental conditions and keep air inlets/outlets free of dust. Please read 2.1.
6.2.1 General The service life of the battery is from 3 to 6 years, depending on the operating temperature and on the number of discharge cycles. As a healthy battery is critical to the performance of the UPS, an automatic quick battery test is performed regularly to ensure failsafe operation (see section 3.5). When the condition of the battery is critical, a 'replace battery' alarm will be activated (see 3.3.9). Replace the batteries as soon as possible. See 6.6.2. NOTE: under certain circumstances a manual battery test can result in a false alarm: please see 3.5 'quick battery test'.
6.2.2 Battery replacement - WARNING: first read the safety rules in section 1.2. - When replacing the batteries, use the same number and voltage(V)/capacity(Ah). - Proper disposal or recycling of the batteries is required. Refer to your local codes for disposal requirements. - Never dispose of batteries in a fire: they may explode. - Do not open or mutilate batteries: their contents (electrolyte) may be extremely toxic. If exposed to electrolyte, wash immediately with plenty of water. - Avoid charging in a sealed container. - Never short circuit batteries. When working with batteries, remove watches, rings or other metal objects, and only use insulated tools.
OPM_NPE_19X_600_1K5_2GB_V030 10 GE DE NetPro 19” 600-1500: User manual 3.0 (GB)

Refer to the label on the battery drawer.

OPM_NPE_19X_600_1K5_2GB_V030 11 GE DE NetPro 19” 600-1500: User manual 3.0 (GB)
Battery replacement procedure

Whenever a malfunction occurs, first check external factors (e.g connections, temperature, humidity or load) to determine whether the problem is caused by the unit itself or by its environment. Subsequently check the thermal circuit breaker: it may be tripped. If so: reset it (see 4, fig.1) and be sure that the UPS is not overloaded. The following chart is a simple troubleshooting checklist only. If the suggested solution does not succeed, or if the information is insufficient to solve the problem, please contact your dealer or consult www.gedigitalenergy.com

UPS overload Reduce load, reset TCB (4, fig. 1) Thermal Circuit Breaker (TCB) tripped
System failure Contact your dealer or consult www. gedigitalenergy.com.
Most probably an overload See 3.3.7, reduce the load LED 'on bypass' blinks
Overtemperature See 3.3.8 Allow the UPS to cool down
UPS will not switch on (without using 'battery start') and the output has been off for a few secs. (see also 3.2.5)
Line cord not connected Read 2.2 Connect line cord
Dead wall socket outlet, or mains voltage out of limits
UPS overtemperature See 3.3.8 Allow UPS to cool down
UPS will not switch on after installation, LED 'on' remains off
Batteries have been discharged too deep during transport and/or storage
UPS overtemperature See 3.3.8 Allow UPS to cool down
UPS received shut down command from computer during mains failure
The load is < 5% of the max. load and no mains power is present. (No-load shutdown function is active, see 3.2.3)
Allow the UPS to recharge the batteries LED ‘replace battery’ illuminates, buzzer is silent
Battery test shows weak battery Read 6.2, replace batteries
OPM_NPE_19X_600_1K5_2GB_V030 12 GE DE NetPro 19” 600-1500: User manual 3.0 (GB)

Ratings Voltage Amperes (VA) : 600 1000 1500 with computer type load Watts (W) : 360 600 900 with resistive load Input thermal circuit breaker (A) : 5 5 7 Input fuse (A) : 8 8 10
Input converter AC input voltage : 220 - 240 V AC input voltage range : 100% load: 187 - 264 V 70% load: 120 - 264 V input >264 Vac: UPS switches to battery operation input >312 Vac: UPS shuts down, manual restart required Minimum start-up AC voltage : 187 V (at any load) Input current waveform : sinusoidal conform or better than EN 61000-3-2 (IEC 555-2) Input current (A) at nom. inp. volt. : 2.0 3.3 5.0 Input power factor : 1 Input frequency range : 45 - 66 Hz Inrush current : none
Output converter AC output voltage : 230 V (suitable for 220 - 240 V loads) AC output voltage tolerance : ± 2% Output frequency : 50 or 60 Hz, front selectable Output frequency range : nominal ± 0.15% unless synchronized to the mains Output waveform : sine wave Harmonic distortion : < 2% (typical 1.5%) with linear load Power factor : 0.6 (0.7 at 90% load) Crest factor (peak to RMS current) : suitable for loads with c.f. up to 6:1 Capacity appliance outlets : max. 10 A per outlet
Bypass AC input voltage range : 195 - 264 V Frequency tracking rate : 2 Hz/sec. Frequency tracking range : nominal ± 10% Phase difference : < 7º Typical transfer time, msec : 4
Overload capability: Fully protected against overload and short circuits Overload behaviour (battery operation) : 110% during 5 minutes; 150% during 5 seconds
Overload behaviour during : depends on rating of thermal circuit breaker bypass operation typical: 125% of TCB value for 200 seconds 200% of TCB value for 10 seconds 300% of TCB value for 4 seconds
Batteries (ratings given for 25ºC) Nominal voltage (Vdc) : 24 36 48 Number of 7 Ah batteries : 2 3 4 Type : sealed lead acid, maintenance free Service life : up to 6 years (depending on use) Recharge current : 1.5 A Battery recharge time (batt. discharged at 100% load) : 1.5 hours for 90% capacity, std battery Runtime in minutes at typical load (75%) : 12 12 10 VA/Watts 100/60 : 64 104 124 200/120 : 34 54 71 400/240 : 15 27 36 600/360 : 9 15 24 1000/600 : - 9 12 1500/900 : - - 6
General Weight without battery drawer (kg) : 14 14 14 Weight with battery drawer (kg) : 19 22 24 Dimensions (hxwxd, mm) : 133.5 (3HU) x 450 (19”) x 440 Depth required in 19” rack (mm) : 420 (without connectors) Enclosure / protection : steel - plastic / IP20
Environment Safety : EN 50091-1-1, EN 60950, IEC 950 Electromagnetic compatibility : EN 50091-2 Ambient temperature : -10 to +40ºC Audible noise at 1 meter : < 45 dB(A), load and temperature dependent Max. relative humidity : 95% (non-condensing)
OPM_NPE_19X_600_1K5_2GB_V030 13 GE DE NetPro 19” 600-1500: User manual 3.0 (GB)