GE 3900
Table of Contents 80 sections ge.com · Air Conditioners · Zoneline ® · Owner’s Manual and Installation Instructions · … ShowHide
ge.comp.1Air Conditionersp.1Zoneline ®p.1Owner’s Manual and Installation Instructionsp.1Españolp.1TINSEA530JBRZ 49-7592-1 10-08 JRp.1SAFETY PRECAUTIONSp.2Replacing an existing unit?p.2READ AND FOLLOW THIS SAFETY INFORMATION CAREFULLY. SAVE THESE INSTRUCTIONSp.2About the controls on your Zoneline. ge.comp.3HIGHp.3COOLp.3LOWp.3FANp.3AUTOp.3HEATp.3ON STOPp.3MODE TEMP FAN OPERATIONp.3SLEEPp.3TEMP CONTROL FAN, MODE & SLEEP OPERATIONp.3Controlsp.3Fan, Mode & Operation Controlp.3About Your Heat Pump (3900 Series only)p.3Ventilation Controlp.4To Remove the Room Cabinetp.4Air Directionp.4Auxiliary Controls on your Zoneline. ge.comp.5Auxiliary Controls—Dip Switchesp.5UP DOWNp.5All Electric Heatp.5Cooling—Smart Fanp.5Heating—Smart Fanp.5Remote Thermostat—Class 2p.5Load Shedding (Central Desk Control)p.6LOAD SHEDDING (CDC)p.6Freeze Sentinelp.6Constant ON Fanp.6Temperature Limitingp.6Heat Sentinelp.7Auxiliary Controls—Terminal Connectionsp.7External Fan (Obtained locally)p.8Central Desk Controlp.8Remote Thermostatp.8Room Cabinet and Casep.9Ventilation Filterp.9Air Filtersp.10FRONT FRONTp.10Questions? Call 800.GE.CARES (800.432.2737) or Visit our Website at: ge.comp.11BEFORE YOU BEGINp.11IMPORTANT ELECTRICAL SAFETY—READ CAREFULLYp.11CAUTION:p.11TOOLS YOU WILL NEEDp.11ZONELINE COMPONENTSp.11230/208 VOLT ELECTRICAL CONNECTION OPTIONSp.13HOW TO CONNECTp.13POWER CORD CONNECTIONp.13ELECTRICAL SUBBASE CONNECTIONp.1315 RAK204D15Pp.1320 RAK204D20Pp.1330 RAK204D30P*p.13DIRECT CONNECTIONp.1315 RAK4002A RAK4157p.1320 RAK4002A RAK4207p.1315 RAK3153p.1330 RAK4002A RAK4307p.1320 RAK3203p.1330 RAK3303*p.13265 VOLT ELECTRICAL CONNECTION OPTIONSp.14B. FOR DIRECT CONNECTp.1415 RAK5157p.1420 RAK5207p.1430 RAK5307p.1415 RAK204E15 RAK5172p.1420 RAK204E20 RAK5202p.1430 RAK204E30 RAK5302p.14MAKE ELECTRICAL CONNECTION TO THE UNITp.15ATTACH CONDUITp.15POWER CONNECTION CHARTp.16Power Cord Connectionsp.16Direct Connectionsp.16
Page 1 of the GE 3900 user manual — TINSEA530JBRZ 49-7592-1 10-08 JR
Page 1 · click to enlarge
Page 1

ge.com

Air Conditioners

Zoneline ®

Safety Instructions 2

Owner’s Manual and Installation Instructions

Operating Instructions Air Direction 4 Auxiliary Controls 5–8 Controls 3 To Remove the Room Cabinet 4 Vent Control 4

Heat/Cool Model 2900 Heat Pump Model 3900

Español

Care and Cleaning Air Filters 10 Base Pan 9 Outdoor Coils 9 Room Cabinet and Case 9 Vent Filter 9

For a Spanish version of this manual, visit our Website at ge.com.

Para consultar una version en español de este manual de instrucciones, visite nuestro sitio de internet ge.com. Français

Installation Instructions Electrical Connection 13–16 Installing the Zoneline 17, 18 Optional Drain Kit 19 Preparation 11 Replacing an Existing Unit? 12

For a French version of this manual, visit our Website at www.electromenagersge.ca

Pour un version français de ce manuel d'utilisation, veuillez visiter notre site web à l’adresse www.electromenagersge.ca

Troubleshooting Tips 20, 21 Normal Operating Sounds 22

Consumer Support Consumer Support Back Cover Warranty 23

Write the model and serial numbers here:

Find these numbers on a label behind the room cabinet on the base pan.

TINSEA530JBRZ 49-7592-1 10-08 JR

Model # · Serial #

Page 2 of the GE 3900 user manual — READ AND FOLLOW THIS SAFETY INFORMATION CAREFULLY. SAVE THESE INSTRUCTIONS
Page 2 · click to enlarge
Page 2

Consumer Support Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions

SAFETY PRECAUTIONS

  • This Zoneline must be properly

Replacing an existing unit?

installed in accordance with the Installation Instructions before it is used. See the Installation Instructions in the back of this manual.

For details, see the Installation Instructions in this manual.

  • Replace immediately all electric service

cords that have become frayed or otherwise damaged. A damaged power supply cord must be replaced with a new power supply cord obtained from the manufacturer and not repaired. Do not use a cord that shows cracks or abrasion damage along its length or at either the plug or connector end.

  • Unplug or disconnect the Zoneline at

the fuse box or circuit breaker before making any repairs.

READ AND FOLLOW THIS SAFETY INFORMATION CAREFULLY. SAVE THESE INSTRUCTIONS

Page 3 of the GE 3900 user manual — About Your Heat Pump (3900 Series only)
Page 3 · click to enlarge
Page 3

About the controls on your Zoneline. ge.com

Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Consumer Support

HIGH

COOL

LOW

FAN

AUTO

HEAT

ON STOP

ON STOP

MODE TEMP FAN OPERATION

SLEEP

TEMP CONTROL FAN, MODE & SLEEP OPERATION

Controls

Temp Control The temp control is used to maintain the room temperature. The compressor will cycle on and off to keep the room at the same level of comfort. Press the + pad to raise the temperature. Press the – pad to lower the temperature. 3900 Series only When the outdoor temperature is lower than 25°F, heat is provided by the electric heater in the air conditioner instead of by the heat pump. Sleep Press to set the air conditioner to run for 8 hours before it automatically returns to the previous setting. When in the cooling mode and the sleep timer is set, the set temperature will automatically increase 2°F after the second hour then 1°F each hour over the next two hours. Also, the fan speed will change to low. When in the heating mode, the set temperature will decrease in the same manner.

Fan, Mode & Operation Control

FAN—sets the fan operation for HIGH, LOW or AUTO speed. When set at AUTO, it automatically switches between LOW and HIGH as room temperature changes.

FAN—For fan-only operation HEAT—For heating

OPERATION—ON/STOP—Turns the unit on or off. Power remains connected to the Zoneline. The Freeze Sentinel feature still functions if switch 6 is enabled (UP). See the Freeze Sentinel section.

Quick Heat Recovery Activates each time the thermostat is switched from STOP or a COOL mode to a HEAT mode. Electric heaters are energized until the thermostat set point is reached. On heat pump models, the heat pump operation will resume at the next call for heat.

To cancel the sleep mode, press the MODE pad or the SLEEP pad a second time.

About Your Heat Pump (3900 Series only)

Heat pumps can save money by removing heat from the outside air—even when the outside temperature is below freezing— and releasing that heat indoors. To get the best performance from your heat pump, don’t change the room thermostat very often. Raising the heat setting 2–3 degrees will cause the Zoneline to use its electric heating elements in order to reach the new temperature setting quickly.

There is a three minute minimum compressor run time at any setting to prevent short cycling. The indoor fan motor starts before the compressor and stops after the compressor cycles off. The electric heating elements use much more electricity than heat pumps and cost more to operate.

MODE—COOL—For cooling

Page 4 of the GE 3900 user manual — Air Direction
Page 4 · click to enlarge
Page 4

Other features of your Zoneline.

Consumer Support Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions

Ventilation Control

The ventilation control lever is located at the upper left side of the Zoneline unit, behind the room cabinet.

When set at the closed position, only the air inside the room is circulated and filtered.

When set at the open position, some outdoor air will be drawn into the room. This will reduce the heating or cooling efficiency.

Energy Tip: Keep the vent control at the closed position. The room air will be filtered and circulated.

Vent control (shown in

To Remove the Room Cabinet

Additional controls are located behind the room cabinet.

To remove: Pull out at the bottom to release it from the tabs (1). Then lift up (2).

To replace: Place the tabs over the top rail (1). Push inward at the bottom until it snaps into place (2).

Air Direction

To adjust the air direction, remove the room cabinet. Remove the 7 louver screws that hold the louver insert in place. Flip the louver insert 180°, replace the screws and the room cabinet.

Remove the room cabinet and flip the louver

insert to change the air direction.

Show 5 more labels / short text on this page
Open position · Closed position · middle position) · Louver screws · Louver screws
Page 5 of the GE 3900 user manual — Remote Thermostat—Class 2
Page 5 · click to enlarge
Page 5

Auxiliary Controls on your Zoneline. ge.com

Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Consumer Support

Auxiliary Controls—Dip Switches

The auxiliary dip switch controls are located behind the room cabinet, through an opening in the control panel.

Remove the room cabinet. See the To Remove the Room Cabinet section.

The owner is responsible for checking switches and ensuring they are in the desired position.

HIGH COOL 1 2 3 4 5 6 1 2 3 4 5 6 7 8

UP DOWN

UP DOWN

ALLI2R (All Electric Heat) (3900 Series models only) C: FAN CN (Cooling–Smart Fan)

HEAT BOOST (3900 Series models only)

H: FAN CY (Heating–Smart Fan)

TL1 (H) (Temp. Limit 1–Heat) TL2 (H) (Temp. Limit 2–Heat) TL3 (H) (Temp. Limit 3–Heat)

CLASS 2 (Remote Thermostat)

LOAD SHEDDING (CDC) FREEZ Sen (Freeze Sentinel) CONST FAN (Constant ON Fan) No Function (Reserved for future use)

TL1 (C) (Temp. Limit 1–Cool) TL2 (C) (Temp. Limit 2–Cool) TL3 (C) (Temp. Limit 3–Cool)

All Electric Heat

This electric heat option functions only on the 3900 Series models. When this switch is enabled (UP), heat pump operation is locked out, causing the unit to provide only electric resistance heat.

ALLI2R (All Electric Heat)

Cooling—Smart Fan

When this switch is enabled (UP), it allows the indoor fan to cycle on/off with the compressor. When this switch is disabled (DOWN), it allows the indoor fan to run continuously.

C: FAN CN (Cooling–Smart Fan)

Heating—Smart Fan

When this switch is enabled (UP), it allows the indoor fan to run continuously. When this switch is disabled (DOWN), it allows the indoor fan to cycle on/off with the heat pump or heater operation.

H: FAN CY (Heating–Smart Fan)

Remote Thermostat—Class 2

When this switch is enabled (UP), it allows the unit to operate with a Class 2 Remote Control Wall Thermostat. The unit controls are disabled.

CLASS 2 (Remote Thermostat)

Dip Switches · Access Cover · Heat Sentinel

Page 6 of the GE 3900 user manual — UP DOWN
Page 6 · click to enlarge
Page 6

Auxiliary controls on your Zoneline.

Consumer Support Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions

Load Shedding (Central Desk Control)

This feature is active only if the unit is in CDC mode. When this switch is enabled (UP), the indoor fan can be turned ON or OFF with the unit controls.

LOAD SHEDDING (CDC)

Freeze Sentinel

When this switch is enabled (UP), it turns OFF the freeze sentinel protection feature. With the switch disabled (DOWN), the freeze sentinel is activated, which automatically provides heat without user interface. This helps to prevent plumbing damage by turning the heater and indoor fan ON at 41°F and OFF at 46°F.

FREEZE Sen (Freeze Sentinel)

Constant ON Fan

When this switch is enabled (UP), it allows the indoor fan to run continuously, at high speed, even if the unit is in the STOP position.

CONST FAN (Constant ON Fan)

Temperature Limiting

Temperature limiting can reduce energy costs by limiting the lowest temperature that can be set for cooling and the highest temperature that can be set for heating. Temperature limiting is controlled by the second six auxiliary switches.

The first three switches are used to select the cooling limits, and the remaining three switches are used to control the heating limits. This feature is not available with the Remote Thermostat—Class 2.

UP DOWN

HIGH COOL 1 2 3 4 5 6 1 2 3 4 5 6 7 8

7 8 HIGH COOL 1 2 3 4 5 6 1 2 3 4 5 6 7 8

UP DOWN

UP DOWN

UP DOWN

TL1 (C) (Temp. Limit 1–Cool) TL2 (C) (Temp. Limit 2–Cool) TL3 (C) (Temp. Limit 3–Cool)

TL1 (H) (Temp. Limit 1–Heat) TL2 (H) (Temp. Limit 2–Heat) TL3 (H) (Temp. Limit 3–Heat)

Temperature limiting during COOL mode (all temperatures shown in °F) UP DOWN Minimum Maximum NONE 1, 2, 3 60° 85° 1 2, 3 64° 85° 1, 2 3 66° 85° 2 1, 3 68° 85° 2, 3 1 70° 85° 1, 2, 3 NONE 72° 85° 1, 3 2 74° 85° 3 1, 2 76° 85° DOWNMinimumMaximum 1, 2, 360°85° 2, 364°85° 366°85° 1, 368°85° 170°85° NONE72°85° 274°85° 1, 276°85°
Temperature limiting during HEAT mode (all temperatures shown in °F) UPDOWNMinimumMaximum NONE 4, 5, 660°85° 45, 660°80° 4, 5660°78° 54, 660°76° 5, 6460°74° 4, 5,6 NONE60°72° 4, 6560°70° 64, 560°65°
Page 7 of the GE 3900 user manual — Auxiliary Controls—Terminal Connections
Page 7 · click to enlarge
Page 7

ge.com

Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Consumer Support

Heat Sentinel

When this switch is enabled (UP), it turns ON the heat sentinel protection feature. With the switch disabled (DOWN), the heat sentinel is de-activated. This feature automatically provides cooling without user interface. This helps to prevent an excessively hot room by turning the air conditioner ON at 85°F and OFF at 80°F.

Heat Boost (AZ3900 only)

When this switch is enabled (UP) and outdoor temperatures are between 25°F and 46°F, heat pump only operation is locked out. This setting is used to provide supplementary heat to the heat pump operation in conditions where the heat pump only operation is not sufficient to maintain a consistent, comfortable room temperature.

BOOST (Heat Boost Operation)

Auxiliary Controls—Terminal Connections

The auxiliary controls are located behind the room cabinet beneath the access cover.

The owner is responsible for making all connections and setting the appropriate dip switches.

Remove the room cabinet. See the To Remove the Room Cabinet section.

Remove the screw from the access cover.

To make wiring connections, insert the wires into the bottom of the terminals and tighten screws securely.

After all desired connections have been made, replace the access cover and room cabinet.

Common - Ground White - Heater Yellow - Compressor Black - Solenoid Green - High Speed Fan Green - Low Speed Fan Red - 24 V AC only

External Fan Central Desk Control

Heat Sentinel

Page 8 of the GE 3900 user manual — Remote Thermostat
Page 8 · click to enlarge
Page 8

Auxiliary controls on your Zoneline.

Consumer Support Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions

External Fan (Obtained locally)

When connected, an auxiliary or external fan can be controlled with the indoor fan motor on the Zoneline. Connections provide 24 V AC to energize a remote relay, turning on the external fan.

Central Desk Control

When connected, the unit can be turned ON or OFF with a switch located at the Central Control Panel. A separate wire pair must be run from each separate controlling switch to each individual Zoneline.

Remote Thermostat

When connected, the unit will be controlled by a remote thermostat.

Red - 24 V AC only

Green - Low Speed Fan

Black - Solenoid Green - High Speed Fan

White - Heater Yellow - Compressor

If using a digital/electronic wall thermostat, you must set it to the 24 V AC setting. See the Installation Instructions for the wall thermostat.

External Fan · Central Desk Control · Common - Ground

Page 9 of the GE 3900 user manual — Ventilation Filter
Page 9 · click to enlarge
Page 9

Care and cleaning.

Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Consumer Support

Room Cabinet and Case

Turn the Zoneline off and disconnect the To clean, use water and a mild detergent. power supply. Do not use bleach or abrasives. Some commercial cleaners may damage the plastic parts.Turn the Zoneline off and disconnect the To clean, use water and a mild detergent. power supply. Do not use bleach or abrasives. Some commercial cleaners may damage the plastic parts. Outdoor Coils The coils on the outdoor side of the Zoneline should be checked regularly. If they are clogged with dirt or soot, they may be professionally steam cleaned, a service available through your GE service outlet. You will need to remove the unit to inspect the coils because the dirt buildup occurs on the inside. Coils Grille Clean the outside coils regularly. The coils on the outdoor side of the Zoneline should be checked regularly. If they are clogged with dirt or soot, they may be professionally steam cleaned, a service available through your GE service outlet. You will need to remove the unit to inspect the coils because the dirt buildup occurs on the inside. Coils Grille Clean the outside coils regularly. Base Pan In some installations, dirt or other debris may be In some areas of the United States, a “g blown into the unit from the outside and settle in “slime-like” substance may be seen in thel-like” or e base pan.

Check it periodically and clean, if necessary.

Ventilation Filter

If the vent door is open, clean the vent filter twice a year or as required.

To clean the vent filter■ Run water through the filter from the

Turn the Zoneline off before cleaning.

back side.

To remove the vent filter■ Remove the room cabinet. See the To Remove
  • Dry thoroughly before replacing.

the Room Cabinet section.

  • Remove the four screws securing the unit

flanges to the case.

  • Slide the unit from the wall case.
  • Grasp the vent filter tab and pull the filter out

by sliding it to the right.

Page 10 of the GE 3900 user manual — FRONT FRONT
Page 10 · click to enlarge
Page 10

Care and cleaning.

Consumer Support Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions

To maintain optimum performance, clean the filters at least every 30 days.

Air Filters

To remove the air filters:

FRONT FRONT

Dirty filter—Needs cleaning Clogged filter—Greatly reduces cooling, heating and airflow.

Turn the Zoneline off before cleaning.

The most important thing you can do to maintain the Zoneline is to clean the filter at least every 30 days. Clogged filters reduce cooling, heating and air flow.

To replace the air filters:

Keeping these filters clean will:

  • Decrease cost of operation.
  • Save energy.
  • Prevent clogged heat exchanger coils.
  • Reduce the risk of premature component

failure.

To clean the air filters:

  • Vacuum off the heavy soil.
  • Run water through the filters from the

back side.

  • Dry thoroughly before replacing.

Operating without the filters in place or with damaged filters will allow dirt and dust to reach the indoor coil and reduce the cooling, heating, airflow and efficiency of the unit.

Replacement filters are available from your salesperson, GE dealer, GE Service and Parts Center or authorized Customer Care® servicers.

2 Air filters · Pull up · Push down

Page 11 of the GE 3900 user manual — TOOLS YOU WILL NEED
Page 11 · click to enlarge
Page 11
GE 3900 — Questions? Call 800.GE.CARES (800.432.2737) or Visit our Website at: ge.com diagram (page 11)
Fig. 1 · Questions? Call 800.GE.CARES (800.432.2737) or Visit…

Questions? Call 800.GE.CARES (800.432.2737) or Visit our Website at: ge.com

BEFORE YOU BEGIN

IMPORTANT ELECTRICAL SAFETY—READ CAREFULLY

Read these instructions completely and carefully.

  • IMPORTANT – Save these instructions for local inspector’s use.

CAUTION:

  • IMPORTANT – Observe all governing codes and ordinances.
  • Note to Installer – Be sure to leave these instructions with the owner.
  • Note to Owner – Keep these instructions for future reference.
  • Proper installation is the responsibility of the installer.
  • Product failure due to improper installation is not covered under the Warranty.
  • Follow the National Electrical Code (NEC) or local codes and ordinances.
  • For personal safety, this Zoneline must be properly grounded.
  • Protective devices (fuses or circuit breakers) acceptable for Zoneline installations are specified on the nameplate of each unit.
  • Do not use an extension cord with this unit.
  • Aluminum building wiring may present special problems—consult a qualified electrician.
  • When the unit is in the OFF position, there is still voltage to the electrical controls.
  • Disconnect the power to the unit before servicing by: 1 Removing the power cord (if it has one) from the wall receptacle. OR 2 Removing the branch circuit fuses or turning the circuit breakers off at the panel.

TOOLS YOU WILL NEED

ZONELINE COMPONENTS

** Shipped with the Zoneline unit ** Check the “Essential Elements” list on the unit

Show 6 more labels / short text on this page
Phillips screwdriver · Zoneline unit · Room cabinet* · Power supply kit** · Exterior grille/louver** · Wall case**
Page 12 of the GE 3900 user manual — REPLACING AN EXISTING UNIT?
Page 12 · click to enlarge
Page 12

REPLACING AN EXISTING UNIT?

Replacing a ducted unit New ducted installation: If this unit is to be installed in a new ducted application using a duct adapter kit, the kit must be installed before the unit is placed in the wall case. The installation instructions are packed with the kit.

Check the “Essential Elements” label for important information.

Use the correct wall case This unit is designed to be installed in a GE plastic or insulated metal wall case. This minimizes condensation from forming on the room side of the case. If the current wall case is not insulated, you can reduce the possibility of condensation forming by installing insulation kit RAK901L, available where you purchased the unit. NOTE: There are several extra holes in the unit side flanges for installation in wall cases other than GE. To avoid damaging the flange insulation, the installer should use an awl or other sharp tool to puncture the insulation in the appropriate holes before installing the attachment screws.

Existing ducted installation: Replacement of an existing ducted unit may require different components. Request this information from your sales representative.

  • Replacing 230/208 volt units: See page 13.
  • Replacing 265 volt units: See page 14.
  • Use the correct outdoor grille You should use the outdoor grilles shown on the “Essential Elements” label on the top of the unit.
  • If an existing grille is not replaced, capacity and efficiency will be reduced and the unit may fail to operate properly or fail prematurely. A deflector kit, RAK40, may be used with grilles that were not designed for your new GE Zonelines. The RAK40 contains air deflectors and gaskets that mount to the unit to direct the hot exhaust air away from the air intake to allow the unit to function properly. The grille must have a 65% minimum free area.
  • Any vertical deflectors in the existing rear grille should be removed to decrease condenser air recirculation that can cause the unit to “short-cycle” and lead to premature component failure.

Use the correct power cord Local codes may require the use of arc fault or leakage current detection devices on 230/208-volt installations.

Mounting · plate Duct · Case

Page 13 of the GE 3900 user manual — 30 RAK3303*
Page 13 · click to enlarge
Page 13

230/208 VOLT ELECTRICAL CONNECTION OPTIONS

HOW TO CONNECT

Power cords may include an arc fault interruption or a leakage current detection interruption device. A test and reset button is provided on the plug case or the inline case. The device should be tested on a periodic basis by first pressing the TEST button and then the RESET button. If the TEST button does not trip or if the RESET button will not stay engaged, discontinue use of the Zoneline and contact a qualified service technician.

1 Remove the room cabinet. 2 Connect to electrical power. 3 Review the following steps for applicable supply voltages. 4 Reinstall the room cabinet.

POWER CORD CONNECTION

ELECTRICAL SUBBASE CONNECTION

A power supply kit must be used to supply power to the Zoneline unit. The appropriate kit is determined by the voltage, the means of electrical connection and the amperage of the branch circuit.

230/208-volt models may be installed using one of the following electrical subbases:

Branch Circuit and Proper GE Unit Amperage Rating Subbase Kit

15 RAK204D15P

20 RAK204D20P

30 RAK204D30P*

*Not approved for use on 7000 BTU models.

Electrical subbases provide an enclosure for direct connection or enclosed receptacles. The subbase kit includes the power cord.

Connections of 208 or 230-volt circuits may be with a power supply kit or a junction box kit.

All wiring, including installation of the receptacle, must be in accordance with the NEC and local codes, ordinances and regulations. Local codes may require the use of an arc fault or leakage current detection device on the power cord. Be sure to select the correct cord for your installation.

The instructions provided with the selected subbase kit must be carefully followed. It is the responsibility of the installer to ensure the connection of components is done in accordance with these instructions and all electrical codes.

DIRECT CONNECTION

Order the following Kit for 230/208-volt direct connection as required:

Tandem 15 Amp.

20 Amp. Large Tandem

30 Amp.

Branch Circuit and Power Supply Power Unit Amperage Rating Accessory Supply Kit

230/208-volt receptacle configuration.

Branch Circuit and Proper GE Power Cord Unit Amperage Rating with LCDI Device

15 RAK4002A RAK4157

20 RAK4002A RAK4207

15 RAK3153

30 RAK4002A RAK4307

20 RAK3203

Skip to the “MAKE ELECTRICAL CONNECTION TO THE UNIT” section.

30 RAK3303*

*Not approved for use on 7000 BTU models.

Power supply kit · Perpendicular

Page 14 of the GE 3900 user manual — 15 RAK204E15 RAK5172
Page 14 · click to enlarge
Page 14

265 VOLT ELECTRICAL CONNECTION OPTIONS

WARNING: Connection of this 265 V AC product to a branch circuit MUST be done by direct connection in accordance with the National Electrical Code. Plugging this unit into a building mounted exposed receptacle is not permitted by code. These models must be installed using the appropriate GE power supply kit for the branch circuit amperage and the electrical resistance heater wattage desired. Use the POWER CONNECTION CHART on page 16 to determine the correct kit required. One of the following installation methods (A or B) must be used.

B. FOR DIRECT CONNECT

INSTALLATION If an electrical subbase is not used, direct connection to branch circuit wiring inside the provided junction box must be done in accordance with the following steps. Order the following Kit for 265-volt direct connection as required:

Branch Circuit and Power Unit Amperage Rating Supply Kit

15 RAK5157

20 RAK5207

30 RAK5307

A. FOR SUBBASE INSTALLATION Electrical subbase kits are available to provide a flexible enclosure for direct connection.

Proceed to the “MAKE ELECTRICAL CONNECTION TO THE UNIT” section.

Branch Circuit and Proper GE Power Unit Amperage Rating Subbase Kit Supply Kit

15 RAK204E15 RAK5172

20 RAK204E20 RAK5202

30 RAK204E30 RAK5302

The instructions provided with the selected subbase kit must be carefully followed. It is the responsibility of the installer to ensure the connection of components is done in accordance with these instructions and all electrical codes.

Page 15 of the GE 3900 user manual — ATTACH CONDUIT
Page 15 · click to enlarge
Page 15

MAKE ELECTRICAL CONNECTION TO THE UNIT

GE 3900 — MAKE ELECTRICAL CONNECTION TO THE UNIT diagram (page 15)
Fig. 2

ATTACH CONDUIT

1 Remove the junction box cover by removing the front two screws. 2 Remove the junction box by removing the top and bottom rear screws. Note how the tabs on the lower left side of the junction box serve to hold the side in place. This will help when the box is being reinstalled.

1 Use the round knockout at the bottom of the junction box to attach conduit coming from the branch circuit. Remove the knockout, attach the conduit and bring wires into the junction box. Leave 6″ of wire free at the end of the conduit to allow connections to be made.

2 If a fuse and fuseholder are to be used, the knockout at the top of the box is for mounting a Buss Fuseholder. Be sure the fuse and fuseholder are of the same rating as the branch circuit. Leadwires at the fuse can be either soldered in place or attached using UL-listed 1/4″ female (receptacle) crimp connectors. Follow local codes.

CONNECT THE CORDSET Plug the connector, provided in the Direct Connect Kit, fully into place in the unit mating connector. Be sure the locking tabs at the sides are engaged.

REINSTALL JUNCTION BOX • Reinstall the junction box by engaging the left tabs on the lower right face of the unit, aligning the screw holes at the top and bottom and driving the two screws until secure. Be sure that all wire leads are inside the box and not pinched between the box and the unit. The green insulated ground wire from the unit MUST be connected to the branch circuit ground wire. Make all wire connections by using appropriate UL-listed electrical connectors and techniques (black to black, white to white and green to green).

REINSTALL JUNCTION BOX COVER 1 Carefully tuck all wires and connections back inside the junction box. Be sure there are no loose connections or stray uninsulated wires exposed. 2 Place the junction box cover in place. Replace the two screws removed earlier and tighten securely.

Conduit

Page 16 of the GE 3900 user manual — Direct Connections
Page 16 · click to enlarge
Page 16

POWER CONNECTION CHART

Power Cord Connections

230/208 Volt Power Supply Kits with Current Leakage Wall Plug Heater Wattage Detection Device Configuration Circuit Protective Device @ 230/208 Volts

RAK3153 Tandem 15-Amp Time-Delay Fuse or Breaker 2.55/2.09 KW RAK3203 Perpendicular 20-Amp Time-Delay Fuse or Breaker 3.45/2.82 KW RAK3303* Large Tandem 30-Amp Time-Delay Fuse or Breaker 5.00/4.10 KW

Direct Connections

230/208 Volt Heater Wattage Power Supply Kits @ 230/208 Volts Circuit Protective Device

RAK4157 2.55 KW/2.09 KW 15-Amp Time-Delay Fuse or Breaker RAK4207 3.45 KW/2.82 KW 20-Amp Time-Delay Fuse or Breaker RAK4307 5.00 KW/4.10 KW 30-Amp Time-Delay Fuse or Breaker

265 Volt Heater Wattage Power Supply Kits @ 265 Volts Circuit Protective Device

RAK5172 2.55 KW 15-Amp Time-Delay Fuse or Breaker RAK5202 3.45 KW 20-Amp Time-Delay Fuse or Breaker RAK5302* 5.00 KW 30-Amp Time-Delay Fuse or Breaker

* Not approved for use on 7000 BTUH units.

Page 17 of the GE 3900 user manual — INSTALLING THE ZONELINE
Page 17 · click to enlarge
Page 17

INSTALLING THE ZONELINE

GE 3900 — INSTALLING THE ZONELINE diagram (page 17)
Fig. 3

INSTALL THE WALL CASE AND EXTERIOR GRILLE The RAB71 series or RAB77 wall case must be properly installed per instructions packed with the case. • Remove the corrugated stiffener and the outdoor protective panel. Use the slit in the outdoor panel as a handhold and push out.

PREPARE THE UNIT • Carefully remove shipping tape and foam shipping blocks from the room cabinet, compressor and vent door. There may be multiple blocks and pieces of shipping tape that need to be removed.

  • Remove the room cabinet by pulling it out at the bottom to release it (1), then lift it up to clear the rail along the unit top (2).
  • Install the exterior grille from the room side following instructions packed with the grille.

Insulated Wall Case This unit is designed to be installed in a GE plastic or an insulated steel wall case. This minimizes condensation from forming on the room side of the case. The RAB71 series wall cases are insulated. Insulation kit RAK901L is available for use with RAB77 or existing uninsulated wall cases when needed. NOTE: For installation with a subbase or duct adapter, see the instructions packed with those kits.

  • If vent door is to be operational, remove shipping screws from the front side of the vent door, if present.
Show 4 more labels / short text on this page
Protective · Slit · panel · Stiffener
Page 18 of the GE 3900 user manual — POWER CONNECTION CHART
Page 18 · click to enlarge
Page 18

3 REPLACE THE ROOM CABINET Reinstall the room cabinet by hooking the top over the rail along the unit top (1), then pushing it in at the bottom (2).

INSTALL THE UNIT INTO THE WALL CASE Slide the unit into the wall case and secure with four screws through the unit flange holes.

Page 19 of the GE 3900 user manual — OPTIONAL—DRAIN KIT INSTALLATION
Page 19 · click to enlarge
Page 19

OPTIONAL—DRAIN KIT INSTALLATION

Dry Air 25 Series models are designed to improve dehumidification by 25%. Since more moisture will be removed from the air, there is a greater possibility that water will drip from the wall case than with a standard unit. To prevent this water from dripping onto external building walls, we recommend the use of RAD10 Drain Kit.

GE 3900 — OPTIONAL—DRAIN KIT INSTALLATION diagram (page 19)
Fig. 4

External Drain See the Installation Instructions in the RAD10 kit.

Alternate6 ″ long, 1/2 ″ O.D. straight copper tube

Type “A” screw for metal case or Type “B” screw for molded case

GE 3900 — OPTIONAL—DRAIN KIT INSTALLATION diagram (page 19)
Fig. 5

Internal Drain See the Installation Instructions in the RAD10 kit.

Type “A” screw for metal case or Type “B” screw for molded case

Page 20 of the GE 3900 user manual — Problem Possible Causes What To Do
Page 20 · click to enlarge
Page 20

Before you call for service…

Consumer Support Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions

Troubleshooting Tips Save time and money! Review the charts on the following pages first and you may not need to call for service.

Problem Possible Causes What To Do

Zoneline does The unit is • Make sure the Zoneline plug is pushed completely not start unplugged. into the outlet.

The power cord is not • Remove the room cabinet and make sure that the firmly attached. yellow connector on the end of the power cord is firmly engaged.

The fuse is blown/circuit • Check the house fuse/circuit breaker box and replace breaker is tripped. the fuse or reset the breaker.

The unit is waiting for • This is normal. The Zoneline will start again after the compressor overload it resets. protector to reset.

Power failure. • If power failure occurs, set the mode control to STOP. When power is restored, set the mode control to the desired setting.

  • There is a protective time delay (up to 3 minutes) to prevent tripping of the compressor overload. For this reason, the unit may not start normal heating or cooling for 3 minutes after it is turned back on.

The current interrupter • Press the RESET button located on the power cord plug device is tripped. or the box near the plug.

  • If the RESET button will not stay engaged, discontinue use of the Zoneline and contact a qualified service technician.

Zoneline does not cool Indoor airflow • Make sure there are no curtains, blinds or furniture or heat as it should is restricted. blocking the front of the Zoneline.

Outdoor airflow is • Make sure the rear grille is not restricted. This can restricted or recirculated. cause the unit to cycle off due to the compressor overload protector.

  • Outdoor grille must have a minimum of 65% free area. Non-GE grilles may be too restrictive for proper performance. Consult your salesperson for assistance.

The temp control may • Turn the control to a lower or higher setting. not be set properly. NOTE: The temperature limiter may be limiting the temperature range.

The air filter is dirty. • Clean the filter at least every 30 days. See the Operating Instructions section.

The room may have • When the Zoneline is first turned on you need to been hot or cold. allow time for the room to cool down or warm up.

Outdoor air is • Set the vent control to the closed position. entering the room.

Burning odor at the start Dust is on the surface • This can cause a “burning” odor at the beginning of of heating operation of the heating element. the heating operation. This odor should quickly fade.

Page 21 of the GE 3900 user manual — Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Consumer Support
Page 21 · click to enlarge
Page 21

Before you call for service… ge.com

Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Consumer Support

Problem Possible Causes What To Do

The air is not always The heat pump is not • This is normal. The heat pump will produce warm air cool or hot during producing hot air. but not as hot as air produced when the higher-cost operation electric heat is used.

The fan switches may be • This causes the fan to blow room temperature air set at continuous fan. even when the compressor or heater cycles off. The continuous air movement provides better overall temperature control in the cool mode.

  • There is one switch for cooling and one switch for heating.

The air does not feel The heat pump alone • Use the Electric Heat Option. This turns off the warm enough during produces air that feels heat pump and warms with electric heat only. heating operation cooler than desired. NOTE: Use of this option will result in increased energy consumption.

The unit is not The fan dip switch may • See the Auxiliary Controls section. blowing out air be set to CYCLE.

The electric heating The power cord is not • Remove the room cabinet and make sure that the feature does not work firmly attached. yellow connector on the end of the power cord is firmly engaged.

Temperature display The compressor may • Set the operation control to STOP and then restart flashes have failed. the unit. If the flashing light reappears within 30 minutes, call for service.

Page 22 of the GE 3900 user manual — PROTECTION
Page 22 · click to enlarge
Page 22

Things that are normal.

Consumer Support Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions

Normal Operating Sounds

You may hear a pinging noise caused by water being picked up and thrown against the condenser on rainy days or when the humidity is high. This design feature helps remove moisture and improve efficiency.

“CLICK”

You may hear relays click when the controls cycle on and off or are adjusted to change the room temperature.

Water will collect in the base pan during high humidity or on rainy days. The water may overflow and drip from the outdoor side of the unit.

The indoor fan runs continuously when the unit is operating in the cooling mode, unless the fan switch behind the room cabinet is set at fan cycle (up). This will cause the fan to cycle on and off with the compressor. You may also hear a fan noise stop and start.

3-Minute Delay

You may notice a few minutes delay in starting if you try to restart the Zoneline too soon after turning it off or if you adjust the thermostat right after the compressor has shut off. This is due to a built-in restart protector for the compressor that causes a 3-minute delay.

During the defrost cycle, both indoor and outdoor fans stop and the compressor will operate in the cooling mode to remove frost from the outdoor coil. After defrost, the unit will restart in electric heat to quickly warm the room to the desired comfort level.

S I L E N C E

COMPRESSOR

To protect the compressor and prevent short cycling, the unit is designed to run for a minimum of 3 minutes after the compressor starts at any thermostat setting.

PROTECTION

Page 23 of the GE 3900 user manual — Warrantor: General Electric Company. Louisville, KY 40225
Page 23 · click to enlarge
Page 23

Zoneline Warranty.

Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Consumer Support

All warranty service provided by our Factory Service Centers, or an authorized Customer Care® technician. To schedule service, on-line, visit us at ge.com, or call 800.GE.CARES (800.432.2737). For service in Canada, call 1.800.561.3344. Please have serial number and model number availa ble when calling for service.

Staple your receipt here. Proof of the original purchase date is needed to obtain service

under the warranty.

For The Period Of: GE Will Replace:

One Year Any part of the Zoneline which fails due to a defect in materials or workmanship. During this From the date of the limited one-year warranty, GE will also provide, free of charge, all labor and related service to original purchase replace the defective part.

Five Years Any part of the sealed refrigerating system (the compressor, condenser, evaporator and all From the date of the connecting tubing) which fails due to a defect in materials or workmanship. During this original purchase four-year limited additional warranty, GE will also provide, free of charge, all labor and related service to replace the defective part.

Five Years For the second through the fifth year from the date of original purchase, GE will replace From the date of the certain parts that fail due to a defect in materials or workmanship. Parts covered are fan original purchase motors, switches, thermostats, heater, heater protectors, compressor overload, solenoids, circuit boards, auxiliary controls, thermistors, frost controls, ICR pump, capacitors, varistors and indoor blower bearing. During this four-year limited additional warranty, you will be responsible for any labor or on-site service costs.

What GE Will Not Cover:

  • Service trips to your site to teach you how to use
  • Replacement of fuses or resetting of circuit breakers.
  • Failure of the product resulting from modifications
  • the product.
  • Improper installation, delivery or maintenance.
  • If you have an installation problem, or if the air

to the product or due to unreasonable use, including failure to provide reasonable and necessary maintenance. ■Failure or damage resulting from corrosion due to

conditioner is of improper cooling capacity for the intended use, contact your dealer or installer. You are responsible for providing adequate electrical connecting facilities. ■In commercial locations, labor necessary to move the

installation in a coastal environment, except for models treated with special factory-applied anti-corrosion protection as designated in the model number. ■Damage to product caused by improper power supply

unit to a location where it is accessible for service by an individual technician. ■Failure or damage resulting from corrosion due to

voltage, accident, fire, floods or acts of God. ■Incidental or consequential damage to personal property

  • caused by possible defects with this air conditioner.
  • Damage caused after delivery.
  • Product not accessible to provide required service.

installation in an environment containing corrosive chemicals.

EXCLUSION OF IMPLIED WARRANTIES—Your sole and exclusive remedy is product repair as provided in this Limited Warranty. Any implied warranties, including the implied warranties of merchantability or fitness for a particular purpose, are limited to one year or the shortest period allowed by law.

This warranty is extended to the original purchaser and any succeeding owner for products purchased for use within the USA and Canada. If the product is located in an area where service by a GE Authorized Servicer is not available, you may be responsible for a trip charge or you may be required to bring the product to an Authorized GE Service location for service. In Alaska, the warranty excludes the cost of shipping or service calls to your site.

Some states or provinces do not allow the exclusion or limitation of incidental or consequential damages. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state or province to province. To know what your legal rights are, consult your local, state or provincial consumer affairs office or your state’s Attorney General.

Warrantor: General Electric Company. Louisville, KY 40225

Page 24 of the GE 3900 user manual — POWER CONNECTION CHART
Page 24 · click to enlarge
Page 24

Consumer Support.

GE 3900 — POWER CONNECTION CHART diagram (page 24)
Fig. 6

Have a question or need assistance with your appliance? Try the GE Appliances Website 24 hours a day, any day of the year! For greater convenience and faster service, you can now download Owner’s Manuals, order parts or even schedule service on-line.

GE 3900 — POWER CONNECTION CHART diagram (page 24)
Fig. 7

Expert GE repair service is only one step away from your door. Get on-line and schedule your service at your convenience any day of the year! Or call 800.GE.CARES (800.432.2737) during normal business hours.

GE 3900 — POWER CONNECTION CHART diagram (page 24)
Fig. 8

GE supports the Universal Design concept—products, services and environments that can be used by people of all ages, sizes and capabilities. We recognize the need to design for a wide range of physical and mental abilities and impairments. For details of GE’s Universal Design applications, including kitchen design ideas for people with disabilities, check out our Website today. For the hearing impaired, please call 800.TDD.GEAC (800.833.4322).

GE 3900 — POWER CONNECTION CHART diagram (page 24)
Fig. 9

Individuals qualified to service their own appliances can have parts or accessories sent directly to their homes (VISA, MasterCard and Discover cards are accepted). Order on-line today, 24 hours every day or by phone at 800.626.2002 during normal business hours.

Instructions contained in this manual cover procedures to be performed by any user. Other servicing generally should be referred to qualified service personnel. Caution must be exercised, since improper servicing may cause unsafe operation.

GE 3900 — POWER CONNECTION CHART diagram (page 24)
Fig. 10

If you are not satisfied with the service you receive from GE, contact us on our Website with all the details including your phone number, or write to: General Manager, Customer Relations

GE 3900 — POWER CONNECTION CHART diagram (page 24)
Fig. 11

Register your new appliance on-line—at your convenience! Timely product registration will allow for enhanced communication and prompt service under the terms of your warranty, should the need arise. You may also mail in the pre-printed registration card included in the packing material, or detach and use the form in this Owner’s Manual.

Printed in China

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the GE 3900

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the GE 3900

Be the first to ask — other owners or our team will answer.

Original document

GE 3900 manual PDF

24 pages·1.2 MB·Air Conditioner·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…