Air Conditioners
Zoneline ®
Safety Instructions 2
Operating Instructions Air Direction 4 Auxiliary Controls 5–9 Controls 3 To Remove the Room Cabinet . .4 Vent Control 4
Heat/Cool Model 2800 Heat Pump Model 3800
Care and Cleaning Air Filters 11 Base Pan 10 Outdoor Coils 10 Room Cabinet and Case 10 Vent Filter 10
For a Spanish version of this manual, visit our Website at ge.com.
Para consultar una version en español de este manual de instrucciones, visite nuestro sitio de internet www.GEAppliances.com Française
Installation Instructions Electrical Supply 14–17 Installing the Zoneline 18, 19 Optional Drain Kit 20 Preparation 12 Replacing an Existing Unit? . . .13
For a French version of this manual, visit our Website at www.GEAppliances.com
Pour une version française de ce manuel d’utilisation, veuillez visiter notre site web à l’adresse www.GEAppliances.com
Troubleshooting Tips 21, 22 Normal Operating Sounds 23
Consumer Support Consumer Support . . .Back Cover Product Registration 25, 26 Warranty 27
Write the model and serial numbers here:
Find these numbers on a label behind the room cabinet on the base pan.
Model # · Serial #

I This Zoneline must be properly
installed in accordance with the Installation Instructions before it is used. See the Installation Instructions in the back of this manual.
For details, see the Installation Instructions in this manual.
I Replace immediately all electric service
cords that have become frayed or otherwise damaged. A damaged power supply cord must be replaced with a new power supply cord obtained from the manufacturer and not repaired. Do not use a cord that shows cracks or abrasion damage along its length or at either the plug or connector end.
I Unplug or disconnect the Zoneline at
the fuse box or circuit breaker before making any repairs.

TEMP CONTROL MODE CONTROL
Controls
Temp Control The temp control is used to maintain the room temperature. The compressor will cycle on and off to keep the room at the same comfort level. When you turn the knob to COOLER (blue), the indoor air will become cooler. Turn the knob to WARMER (red) and the indoor air will become warmer.
Mode Control HIGH COOL and LOW COOL provide cooling with different fan speeds.
HIGH HEAT and LOW HEAT provide heating with different fan speeds.
LOW FAN or HIGH FAN provides air circulation and filtering without cooling or heating.
3800 Series only When the outdoor temperature is lower than 20°F, heat is provided by the electric heater in the air conditioner instead of by the heat pump.
Heat pumps can save money by removing heat from the outside air—even when the outside temperature is below freezing—and releasing that heat indoors.
There is a three minute minimum compressor run time at any setting to prevent short cycling.
The indoor fan motor starts before the compressor and stops after the compressor cycles off.
To get the best performance from your heat pump, don’t change the room thermostat very often. Raising the heat setting 2–3 degrees will cause the Zoneline to use its electric heating elements in order to reach the new temperature setting quickly.
The electric heating elements use much more electricity than heat pumps and cost more to operate.

Other features of your Zoneline.
Ventilation Control
The ventilation control lever is located at the upper left side of the Zoneline unit, behind the room cabinet.
When set at the closed position, only the air inside the room is circulated and filtered.
When set at the open position, some outdoor air will be drawn into the room. This will reduce the heating or cooling efficiency.
Energy Tip: Keep the vent control at the closed position. The room air will be filtered and circulated.
Vent control (shown in
Additional controls are located behind the room cabinet.
To remove: Pull out at the bottom to release it from the tabs (1). Then lift up (2).
To replace: Place the tabs over the top rail (1). Push inward at the bottom until it snaps into place (2).
To adjust the air direction, remove the room cabinet. Remove the 7 louver screws that hold the louver insert in place. Flip the louver insert 180°, replace the screws and the room cabinet.
Remove the room cabinet and flip the louver
insert to change the air direction.

Auxiliary Controls—Dip Switches
The auxiliary dip switch controls are located behind the room cabinet, through an opening in the control panel.
Remove the room cabinet. See the To Remove the Room Cabinet section.
The factory settings will be in the DOWN position.
The owner is responsible for checking switches and ensuring they are in the desired position.
HIGH COOL 1 2 3 4 5 6 1 2 3 4 5 6 7 8
ALLI2R (All Electric Heat) (3800 Series models only) C: FAN CN (Cooling–Smart Fan)
HEAT BOOST (3800 Series models only)
H: FAN CY (Heating–Smart Fan)
TL1 (H) (Temp. Limit 1–Heat) TL2 (H) (Temp. Limit 2–Heat) TL3 (H) (Temp. Limit 3–Heat)
CLASS 2 (Remote Thermostat)
LOAD SHEDDING (CDC) FREEZ Sen (Freeze Sentinel) CONST FAN (Constant ON Fan)
TL1 (C) (Temp. Limit 1–Cool) TL2 (C) (Temp. Limit 2–Cool) TL3 (C) (Temp. Limit 3–Cool)
This electric heat option functions only on the 3800 Series models. When this switch is enabled (UP), heat pump operation is locked out, causing the unit to provide only electric resistance heat.
ALLI2R (All Electric Heat)
When this switch is enabled (UP), it allows the indoor fan to cycle on/off with the compressor. When this switch is disabled (DOWN), it allows the indoor fan to run continuously.
C: FAN CN (Cooling–Smart Fan)
When this switch is enabled (UP), it allows the indoor fan to run continuously. When this switch is disabled (DOWN), it allows the indoor fan to cycle on/off with the heat pump or heater operation.
H: FAN CY (Heating–Smart Fan)

Auxiliary controls on your Zoneline.
Remote Thermostat—Class 2
When this switch is enabled (UP), it allows the unit to operate with a Class 2 Remote Control Wall Thermostat. The unit controls are disabled.
CLASS 2 (Remote Thermostat)
This feature is active only if the unit is in CDC mode. When this switch is enabled (UP), the indoor fan can be turned ON or OFF with the unit controls.
Freeze Sentinel
When this switch is enabled (UP), it turns OFF the freeze sentinel protection feature. With the switch disabled (DOWN), the freeze sentinel is activated, which automatically provides heat without user interface. This helps to prevent plumbing damage by turning the heater and indoor fan ON at 41°F and OFF at 46°F.
FREEZE Sen (Freeze Sentinel)
When this switch is enabled (UP), it allows the indoor fan to run continuously, at high speed, even if the unit is in the STOP position.
CONST FAN (Constant ON Fan)
When this switch is enabled (UP), it allows the unit to utilize an infrared motion sensor and a door switch for occupancy detection. This feature allows an energy management system to be installed and operated in conjunction with the unit.
HIGH COOL 1 2 3 4 5 6 1 2 3 4 5 6 7 8
OCCUPIED (Occupancy Sensor)

Temperature Limiting
Temperature limiting can reduce energy costs by limiting the lowest temperature that can be set for cooling and the highest temperature that can be set for heating. Temperature limiting is controlled by the second six auxiliary switches.
The first three switches are used to select the cooling limits, and the remaining three switches are used to control the heating limits. This feature is not available with the Remote Thermostat—Class 2.
HIGH COOL 1 2 3 4 5 6 1 2 3 4 5 6 7 8
7 8 HIGH COOL 1 2 3 4 5 6 1 2 3 4 5 6 7 8
UP DOWN
UP DOWN
TL1 (H) (Temp. Limit 1–Heat) TL2 (H) (Temp. Limit 2–Heat) TL3 (H) (Temp. Limit 3–Heat)
TL1 (C) (Temp. Limit 1–Cool) TL2 (C) (Temp. Limit 2–Cool) TL3 (C) (Temp. Limit 3–Cool)
When this switch is enabled (UP), it turns ON the heat sentinel protection feature. With the switch disabled (DOWN), the heat sentinel is de-activated. This feature automatically provides cooling without user interface. This helps to prevent an excessively hot room by turning the air conditioner ON at 85°F and OFF at 80°F.
Heat Boost (AZ3800 only)
When this switch is enabled (UP) and outdoor temperatures are between 20°F and 46°F, heat pump only operation is locked out. This setting is used to provide supplementary heat to the heat pump operation in conditions where the heat pump only operation is not sufficient to maintain a consistent, comfortable room temperature.
BOOST (Heat Boost Operation)
Heat Sentinel

Auxiliary controls on your Zoneline.
Auxiliary Controls—Terminal Connections
The auxiliary controls are located behind the room cabinet beneath the access cover.
The owner is responsible for making all connections and setting the appropriate dip switches.
Remove the room cabinet. See the To Remove the Room Cabinet section.
Remove the screw from the access cover.
To make wiring connections, insert the wires into the bottom of the terminals and tighten screws securely.
After all desired connections have been made, replace the access cover and room cabinet.
Common - Ground White - Heater Yellow - Compressor Black - Solenoid Green - High Speed Fan Green - Low Speed Fan Red - 24 V AC only
Door Sensor External Fan Central Desk Control
When connected, the wall mounted motion sensor will detect motion in the room and automatically set back the room temperature.
The door and motion sensors work together to automatically set back the room temperature.
The appropriate dip switch must be enabled. Motion Sensor
Motion Sensor

Door Sensor (Obtained locally)
When connected, the door sensor will detect when the door in the room was opened or closed. This feature must be used in conjunction with the motion sensor.
The door and motion sensors work together to automatically set back the room temperature.
When connected, an auxiliary or external fan can be controlled with the indoor fan motor on the Zoneline. Connections provide 24 V AC to energize a remote relay, turning on the external fan.
When connected, the unit can be turned ON or OFF with a switch located at the Central Control Panel. A separate wire pair must be run from each separate controlling switch to each individual Zoneline.
When connected, the unit will be controlled by a remote thermostat.
Red - 24 V AC only
Green - Low Speed Fan
Black - Solenoid Green - High Speed Fan
White - Heater Yellow - Compressor
If using a digital/electronic wall thermostat, you must set it to the 24 V AC setting. See the Installation Instructions for the wall thermostat.

Care and cleaning.
Room Cabinet and Case
Turn the Zoneline off and disconnect the power supply.
To clean, use water and a mild detergent. Do not use bleach or abrasives. Some commercial cleaners may damage the plastic parts.
The coils on the outdoor side of the Zoneline should be checked regularly. If they are clogged with dirt or soot, they may be professionally steam cleaned, a service available through your GE service outlet. You will need to remove the unit to inspect the coils because the dirt buildup occurs on the inside.
Clean the outside coils regularly.
In some installations, dirt or other debris may be blown into the unit from the outside and settle in the base pan (the bottom of the unit).
In some areas of the United States, a “gel-like” or “slime-like” substance may be seen in the base pan.
Check it periodically and clean, if necessary.
If the vent door is open, clean the vent filter twice a year or as required.
Turn the Zoneline off before cleaning.
back side.
I Dry thoroughly before replacing.
the Room Cabinet section.
I Remove the four screws securing the unit
flanges to the case.
I Slide the unit from the wall case.
I Grasp the vent filter tab and pull the filter out
by sliding it to the right.
Coils · Grille

To maintain optimum performance, clean the filters at least every 30 days.
To remove the air filters:
Dirty filter—Needs cleaning Clogged filter—Greatly reduces cooling, heating and airflow.
Turn the Zoneline off before cleaning.
The most important thing you can do to maintain the Zoneline is to clean the filter at least every 30 days. Clogged filters reduce cooling, heating and air flow.
To replace the air filters:
Keeping these filters clean will:
I Decrease cost of operation.
I Save energy.
I Prevent clogged heat exchanger coils.
I Reduce the risk of premature component
failure.
To clean the air filters:
I Vacuum off the heavy soil.
I Run water through the filters from the
back side.
I Dry thoroughly before replacing.
Operating without the filters in place or with damaged filters will allow dirt and dust to reach the indoor coil and reduce the cooling, heating, airflow and efficiency of the unit.
Replacement filters are available from your salesperson, GE dealer, GE Service and Parts Center or authorized Customer Care® servicers.
2 Air filters · Pull up · Push down


BEFORE YOU BEGIN
IMPORTANT ELECTRICAL SAFETY—READ CAREFULLY
Read these instructions completely and carefully.
ZONELINE COMPONENTS
** Shipped with the Zoneline unit ** Check the “Essential Elements” list on the unit

Replacing a ducted unit New ducted installation: If this unit is to be installed in a new ducted application using a duct adapter kit, the kit must be installed before the unit is placed in the wall case. The installation instructions are packed with the kit.
Check the “Essential Elements” label for important information.
Use the correct wall case This unit is designed to be installed in a GE plastic or insulated metal wall case. This minimizes condensation from forming on the room side of the case. If the current wall case is not insulated, you can reduce the possibility of condensation forming by installing insulation kit RAK901L, available where you purchased the unit. NOTE: There are several extra holes in the unit side flanges for installation in wall cases other than GE. To avoid damaging the flange insulation, the installer should use an awl or other sharp tool to puncture the insulation in the appropriate holes before installing the attachment screws.
Existing ducted installation: Replacement of an existing ducted unit may require different components. Request this information from your sales representative.
Use the correct power cord Local codes may require the use of arc fault or leakage current detection devices on 230/208 volt installations.
Mounting · plate Duct · Case

HOW TO CONNECT
Power cords may include an arc fault interruption or a leakage current detection interruption device. A test and reset button is provided on the plug case or the inline case. The device should be tested on a periodic basis by first pressing the TEST button and then the RESET button. If the TEST button does not trip or if the RESET button will not stay engaged, discontinue use of the Zoneline and contact a qualified service technician.
1 Remove the room cabinet. 2 Connect to electrical power. 3 See the special instructions below for applicable supply voltages. 4 Reinstall the room cabinet.
A power supply kit must be used to supply power to the Zoneline unit. The appropriate kit is determined by the voltage, the means of electrical connection and the amperage of the branch circuit.
Order Kit RAK4002A for 230/208 volt direct connection.
230/208 volt models may be installed using one of the following electrical subbases:
Branch Circuit and Proper GE Unit Amperage Rating Subbase Kit
Connections of 208 or 230 volt circuits may be with a power supply kit or a junction box kit.
20 RAK204D20P
All wiring, including installation of the receptacle, must be in accordance with the NEC and local codes, ordinances and regulations. Local codes may require the use of an arc fault or leakage current detection device on the power cord. Be sure to select the correct cord for your installation.
*Not approved for use on 7000 BTU models.
Electrical subbases provide an enclosure for direct connection or enclosed receptacles. The subbase kit includes the power cord.
The instructions provided with the selected subbase kit must be carefully followed. It is the responsibility of the installer to ensure the connection of components is done in accordance with these instructions and all electrical codes.
Tandem 15 Amp.
20 Amp. Large Tandem
30 Amp.
230/208 volt receptacle configuration.
Branch Circuit and Proper GE Power Cord Unit Amperage Rating with LCDI Device
20 RAK3203
30 RAK3303*
*Not approved for use on 7000 BTU models.
Power supply kit · Perpendicular

WARNING: Connection of this 265 V AC product to a branch circuit MUST be done by direct connection in accordance with the National Electrical Code. Plugging this unit into a building mounted exposed receptacle is not permitted by code. These models must be installed using the appropriate GE power supply kit for the branch circuit amperage and the electrical resistance heater wattage desired. Use the POWER CONNECTION CHART on page 17 to determine the correct kit required. One of the following installation methods (A or B) must be used.
1 Remove the junction box cover by removing the front two screws. 2 Remove the junction box by removing the top and bottom rear screws. Note how the tabs on the lower left side of the junction box serve to hold the side in place. This will help when the box is being reinstalled.
1 Remove the room cabinet. 2 Connect to electrical power. 3 See the special instructions below for applicable supply voltages. 4 Reinstall the room cabinet.
CUT AND STRIP THE CORDSET 1 Remove the cordset from the power supply kit. Measure 6″ down the cord from where it emerges from the back of the nylon plastic connector and cut the cord through at this point. 2 Carefully remove 3″ of the cordset insulation so as to expose the three insulated wires. 3 Strip 3/4″ of the insulation away at the end of each of the three wires (L1, Neutral and Ground). Plug the connector fully into place in the unit mating connector. Be sure the locking tabs at the sides are engaged.
A. FOR SUBBASE INSTALLATION Electrical subbase kits are available to provide a flexible enclosure for direct connection.
Branch Circuit and Proper GE Power Unit Amperage Rating Subbase Kit Supply Kit
20 RAK204E20 RAK5202
30 RAK204E30 RAK5302
The instructions provided with the selected subbase kit must be carefully followed. It is the responsibility of the installer to ensure the connection of components is done in accordance with these instructions and all electrical codes.
INSTALLATION If an electrical subbase is not used, direct connection to branch circuit wiring inside the provided junction box must be done in accordance with the following steps.

REINSTALL JUNCTION BOX • Reinstall the junction box by engaging the left tabs on the lower right face of the unit, aligning the screw holes at the top and bottom and driving the two screws until secure. Be sure that all wire leads are inside the box and not pinched between the box and the unit. The green insulated ground wire from the unit MUST be connected to the branch circuit ground wire. Make all wire connections by using appropriate UL-listed electrical connectors and techniques (black to black, white to white and green to green).
1 Use the round knockout at the bottom of the junction box to attach conduit coming from the branch circuit. Remove the knockout, attach the conduit and bring wires into the junction box. Leave 6″ of wire free at the end of the conduit to allow connections to be made.
REINSTALL JUNCTION BOX COVER 1 Carefully tuck all wires and connections back inside the junction box. Be sure there are no loose connections or stray uninsulated wires exposed. 2 Place the junction box cover in place. Replace the two screws removed earlier and tighten securely.
2 If a fuse and fuseholder are to be used, the knockout at the top of the box is for mounting a Buss Fuseholder. Be sure the fuse and fuseholder are of the same rating as the branch circuit. Leadwires at the fuse can be either soldered in place or attached using UL-listed 1/4″ female (receptacle) crimp connectors.
3 Discard the unused portion of the plug and the cordset.
Conduit

with Leakage Current Detection Wall Plug Heater Wattage Device Configuration Circuit Protective Device @ 230/208 Volts
RAK3153* Tandem 15 Amp Time Delay Fuse or Breaker 2.55/2.09 KW RAK3203* Perpendicular 20 Amp Time Delay Fuse or Breaker 3.45/2.82 KW RAK3303* Large Tandem 30 Amp Time Delay Fuse or Breaker 5.00/4.10 KW
265 Volt Power Wall Plug Heater Wattage Supply Kits Configuration Circuit Protective Device @ 265 Volts
RAK5172* Does Not Apply 15 Amp Time Delay Fuse or Breaker 2.55 KW RAK5202* Does Not Apply 20 Amp Time Delay Fuse or Breaker 3.45 KW RAK5302* Does Not Apply 30 Amp Time Delay Fuse or Breaker 5.0 KW
*Not approved for use on 7000 BTU models.


INSTALL THE WALL CASE AND EXTERIOR GRILLE The RAB71 series or RAB77 wall case must be properly installed per instructions packed with the case. • Remove the corrugated stiffener and the outdoor protective panel. Use the slit in the outdoor panel as a handhold and push out.
PREPARE THE UNIT • Carefully remove shipping tape and foam shipping blocks from the room cabinet, compressor and vent door. There may be multiple blocks and pieces of shipping tape that need to be removed.
Insulated Wall Case This unit is designed to be installed in a GE plastic or an insulated steel wall case. This minimizes condensation from forming on the room side of the case. The RAB71 series wall cases are insulated. Insulation kit RAK901L is available for use with RAB77 or existing uninsulated wall cases when needed. NOTE: For installation with a subbase or duct adapter, see the instructions packed with those kits.

3 REPLACE THE ROOM CABINET Reinstall the room cabinet by hooking the top over the rail along the unit top (1), then pushing it in at the bottom (2).
INSTALL THE UNIT INTO THE WALL CASE Slide the unit into the wall case and secure with four screws through the unit flange holes.

Dry Air 25 Series models are designed to improve dehumidification by 25%. Since more moisture will be removed from the air, there is a greater possibility that water will drip from the wall case than with a standard unit. To prevent this water from dripping onto external building walls, we recommend the use of RAD10 Drain Kit.

External Drain See the Installation Instructions in the RAD10 kit.
Type “A” screw for metal case or Type “B” screw for molded case

Internal Drain See the Installation Instructions in the RAD10 kit.
Type “A” screw for metal case or Type “B” screw for molded case

Troubleshooting Tips Save time and money! Review the charts on the following pages first and you may not need to call for service.
Zoneline does The unit is • Make sure the Zoneline plug is pushed completely not start unplugged. into the outlet.
The power cord is not • Remove the room cabinet and make sure that the firmly attached. yellow connector on the end of the power cord is firmly engaged.
The fuse is blown/circuit • Check the house fuse/circuit breaker box and replace breaker is tripped. the fuse or reset the breaker.
The unit is waiting for • This is normal. The Zoneline will start again after the compressor overload it resets. protector to reset.
Power failure. • If power failure occurs, set the mode control to STOP. When power is restored, set the mode control to the desired setting.
The current interrupter • Press the RESET button located on the power cord plug device is tripped. or the box near the plug.
Zoneline does not cool Indoor airflow • Make sure there are no curtains, blinds or furniture or heat as it should is restricted. blocking the front of the Zoneline.
Outdoor airflow is • Make sure the rear grille is not restricted. This can restricted or recirculated. cause the unit to cycle off due to the compressor overload protector.
The temp control may • Turn the control to a lower or higher setting. not be set properly. NOTE: The temperature limiter may be limiting the temperature range.
The air filter is dirty. • Clean the filter at least every 30 days. See the Operating Instructions section.
The room may have • When the Zoneline is first turned on you need to been hot or cold. allow time for the room to cool down or warm up.
Outdoor air is • Set the vent control to the closed position. entering the room.
Burning odor at the start Dust is on the surface • This can cause a “burning” odor at the beginning of of heating operation of the heating element. the heating operation. This odor should quickly fade.

Problem Possible Causes What To Do
The air is not always The heat pump is not • This is normal. The heat pump will produce warm air cool or hot during producing hot air. but not as hot as air produced when the higher-cost operation electric heat is used.
The fan switches may be • This causes the fan to blow room temperature air set at continuous fan. even when the compressor or heater cycles off. The continuous air movement provides better overall temperature control in the cool mode.
The air does not feel The heat pump alone • Use the Electric Heat Option. This turns off the warm enough during produces air that feels heat pump and warms with electric heat only. heating operation cooler than desired. NOTE: Use of this option will result in increased energy consumption.
The unit is not The fan dip switch may • See the Auxiliary Controls section. blowing out air be set to CYCLE.
The electric heating The power cord is not • Remove the room cabinet and make sure that the feature does not work firmly attached. yellow connector on the end of the power cord is firmly engaged.

Normal Operating Sounds
You may hear a pinging noise caused by water being picked up and thrown against the condenser on rainy days or when the humidity is high. This design feature helps remove moisture and improve efficiency.
You may hear relays click when the controls cycle on and off or are adjusted to change the room temperature.
Water will collect in the base pan during high humidity or on rainy days. The water may overflow and drip from the outdoor side of the unit.
The indoor fan runs continuously when the unit is operating in the cooling mode, unless the fan switch behind the room cabinet is set at fan cycle (up). This will cause the fan to cycle on and off with the compressor. You may also hear a fan noise stop and start.
You may notice a few minutes delay in starting if you try to restart the Zoneline too soon after turning it off or if you adjust the thermostat right after the compressor has shut off. This is due to a built-in restart protector for the compressor that causes a 3-minute delay.
During the defrost cycle, both indoor and outdoor fans stop and the compressor will operate in the cooling mode to remove frost from the outdoor coil. After defrost, the unit will restart in electric heat to quickly warm the room to the desired comfort level.
COMPRESSOR
To protect the compressor and prevent short cycling, the unit is designed to run for a minimum of 3 minutes after the compressor starts at any thermostat setting.


Please place in envelope and mail to:

Dear Customer: Thank you for purchasing our product and thank you for placing your confidence in us. We are proud to have you as a customer!
product, detach and return the form below to ensure that your product is registered, or register online at ge.com. 1 2 3
Complete and mail your Consumer Product Ownership Registration today. Have the peace of mind of knowing we can contact you in the unlikely event of a safety modification.
After mailing the registration below, store this document in a safe place. It contains information you will need should you require service. Our service number is 800.GE.CARES (800.432.2737).
Read your Owner’s Manual carefully. It will help you operate your new appliance properly.
Important: If you did not get a registration card with your
✁ Cut here
Consumer Product Ownership Registration
Mr. I Ms. I Mrs. I Miss I
Apt. #
In Use Month Day Year
Phone Number _ _
* Please provide your e-mail address to receive, via e-mail, discounts, special offers and other important communications from GE Appliances (GEA).
GE Consumer & Industrial Appliances General Electric Company Louisville, KY 40225 ge.com
I Check here if you do not want to receive communications from GEA’s carefully selected
partners.
FAILURE TO COMPLETE AND RETURN THIS CARD DOES NOT DIMINISH YOUR WARRANTY RIGHTS.
For more information about GEA’s privacy and data usage policy, go to ge.com and click on “Privacy Policy” or call 800.626.2224.

Zoneline Warranty.
All warranty service provided by our Factory Service Centers, or an authorized Customer Care® technician. To schedule service, on-line, 24 hours a day, visit us at ge.com, or call 800.GE.CARES (800.432.2737). For service in Canada, call 1.800.361.3400. Please have serial number and model number available when calling for service.
Staple your receipt here. Proof of the original purchase date is needed to obtain service
under the warranty.
One Year Any part of the Zoneline which fails due to a defect in materials or workmanship. During this From the date of the limited one-year warranty, GE will also provide, free of charge, all labor and related service to original purchase replace the defective part.
Five Years Any part of the sealed refrigerating system (the compressor, condenser, evaporator and all From the date of the connecting tubing) which fails due to a defect in materials or workmanship. During this original purchase four-year limited additional warranty, GE will also provide, free of charge, all labor and related service to replace the defective part.
Five Years For the second through the fifth year from the date of original purchase, GE will replace From the date of the certain parts that fail due to a defect in materials or workmanship. Parts covered are fan original purchase motors, switches, thermostats, heater, heater protectors, compressor overload, solenoids, circuit boards, auxiliary controls, thermistors, frost controls, ICR pump, capacitors, varistors and indoor blower bearing. During this four-year limited additional warranty, you will be responsible for any labor or on-site service costs.
I Service trips to your site to teach you how to use
I Replacement of fuses or resetting of circuit breakers. I Failure of the product resulting from modifications
the product. I Improper installation, delivery or maintenance. I If you have an installation problem, or if the air
to the product or due to unreasonable use, including failure to provide reasonable and necessary maintenance. I Failure or damage resulting from corrosion due to
conditioner is of improper cooling capacity for the intended use, contact your dealer or installer. You are responsible for providing adequate electrical connecting facilities. I In commercial locations, labor necessary to move the
installation in a coastal environment, except for models treated with special factory-applied anti-corrosion protection as designated in the model number. I Damage to product caused by improper power supply
unit to a location where it is accessible for service by an individual technician. I Failure or damage resulting from corrosion due to
voltage, accident, fire, floods or acts of God. I Incidental or consequential damage to personal property
caused by possible defects with this air conditioner. I Damage caused after delivery. I Product not accessible to provide required service.
installation in an environment containing corrosive chemicals.
EXCLUSION OF IMPLIED WARRANTIES—Your sole and exclusive remedy is product repair as provided in this Limited Warranty. Any implied warranties, including the implied warranties of merchantability or fitness for a particular purpose, are limited to one year or the shortest period allowed by law.
This warranty is extended to the original purchaser and any succeeding owner for products purchased for use within the USA and Canada. If the product is located in an area where service by a GE Authorized Servicer is not available, you may be responsible for a trip charge or you may be required to bring the product to an Authorized GE Service location for service. In Alaska, the warranty excludes the cost of shipping or service calls to your site.
Some states or provinces do not allow the exclusion or limitation of incidental or consequential damages. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state or province to province. To know what your legal rights are, consult your local, state or provincial consumer affairs office or your state’s Attorney General.

Consumer Support.
Have a question or need assistance with your appliance? Try the GE Appliances Website 24 hours a day, any day of the year! For greater convenience and faster service, you can now download Owner’s Manuals, order parts, catalogs, or even schedule service on-line. You can also “Ask Our Team of Experts™” your questions, and so much more...
Expert GE repair service is only one step away from your door. Get on-line and schedule your service at your convenience 24 hours any day of the year! Or call 800.GE.CARES (800.432.2737) during normal business hours.
GE supports the Universal Design concept—products, services and environments that can be used by people of all ages, sizes and capabilities. We recognize the need to design for a wide range of physical and mental abilities and impairments. For details of GE’s Universal Design applications, including kitchen design ideas for people with disabilities, check out our Website today. For the hearing impaired, please call 800.TDD.GEAC (800.833.4322).
Individuals qualified to service their own appliances can have parts or accessories sent directly to their homes (VISA, MasterCard and Discover cards are accepted). Order on-line today, 24 hours every day or by phone at 800.626.2002 during normal business hours.
Instructions contained in this manual cover procedures to be performed by any user. Other servicing generally should be referred to qualified service personnel. Caution must be exercised, since improper servicing may cause unsafe operation.
If you are not satisfied with the service you receive from GE, contact us on our Website with all the details including your phone number, or write to: General Manager, Customer Relations
GE Appliances, Appliance Park Louisville, KY 40225
Register your new appliance on-line—at your convenience! Timely product registration will allow for enhanced communication and prompt service under the terms of your warranty, should the need arise. You may also mail in the pre-printed registration card included in the packing material, or detach and use the form in this Owner’s Manual.
Printed in China