® packaged terminal air conditioners
2007 contract sales architects and engineers data manual


ALL UNITS REQUIRE POWER CONNECTION KIT
Power Connection Kit determines resistance heat output 7000 Btuh units do not activate 5 KW resistance heater
Dry Air 25 2800 Series Cooling with Electric Heat


5800 Series Heat Pump with Backup Electric Heat


*Dual rated 230/208-volt units are shown with ratings separated by “/”.
Units with single rating are 265-volt units.

Power Connection Kits
230/208-Volt Line Cord Connection Units
230/208-Volt Sub-Base and Direct Connected Units

Electric Heat Amps include electric heater and fan motor current draw. Each Line Cord Kit has an integral Leakage Current Detection and Interruption (LCDI) or Arc Fault Current Interrupter (AFCI) device as required by National Electrical Code (NEC) and Underwriters Laboratories (UL) for units manufactured after August 1, 2004.
Electric Heat Amps include electric heater and fan motor current draw. Units connected through sub-base do not require a LCDI or AFCI device since they are not considered to be line-cord connected. Each 230/208-volt sub-base kit consists of sub-base with appropriate receptacle for minimum circuit amperage, chaseway to route power connector from sub-base to chassis, wiring to connect sub-base to building wiring and a short line cord with 9-pin connector to connect to chassis and plug into receptacle in sub-base. Short sub-base line cord may not be used without sub-base. Junction box for 230/208-volt chassis must be purchased separately. RAK4002A for 2800 and 3800 series units RAK4002B for 5800 series units.

Electric Heat Amps include electric heater and fan motor current draw. 265-volt units are to be permanently connected in compliance with National Electrical Code and local codes and have a factory-installed junction box on the chassis. Each 265-volt sub-base kit consists of sub-base with appropriate receptacle for minimum circuit amperage, chaseway to route power connector from sub-base to chassis and wiring to connect sub-base to building wiring. 265-Volt Power Connection Kit must be ordered separately.

Essential Elements Ordering Overview 230/208-volt line cord connected units — order line cord kit 230/208-volt sub-base connected units — order sub-base and junction box 265-volt units — order sub-base and power connection kit
The Zoneline chassis is identified by a model number defining the type of unit, cooling capacity, electrical information and optional features included on the unit. When specifying or ordering the Zoneline chassis, the use of this nomenclature will assure receiving the correct unit.


The Zoneline® 2800, 3800 and 5800 Series have incorporated changes suggested by customers, along with enhancements by GE’s Technology Team and changes necessary to meet new UL and NEC requirements. “L” shaped condenser coil.
The “Partial Open Vent Air” feature was a specific request by a customer.
“Heat Sentinel” is an enhancement developed by GE’s Technology Team to help lodging professionals welcome their guests with a moderate-temperature room and to help lower cooling costs.
Devices have been added on cord-connected units to protect against injury from unsafe power cords.
See the “Features and Benefits” section for in-depth explanation of these changes and the industry-leading features of GE Zoneline retained from the previous series.
The Deluxe 2800 Series Zoneline Models Includes The “Dry Air 25” Models Which Remove 25% More Moisture Than Other Zoneline Models.

When the cold air from the evaporator comes in contact with the re-heat section of the heat pipe, the heat that was removed by the pre-cool section is added back to the air and the refrigerant in the heat pipe condenses and flows back to the indoor coil. The air discharged into the room by this process is much drier, creating a more comfortable room condition.
The Newest Innovation from GE The Dry Air 25 Models center around GE’s exclusive use of the patented Dinh® Dehumidifier Heat Pipe from Heat Pipe Technology, Inc. This innovative NASA spin-off technology enables Dry Air 25 to remove 25% more moisture from the air than other leading manufacturers’ packaged terminal air conditioners. This helps maintain room comfort at a higher room temperature, reducing operating costs. The Dry Air 25 keeps a room cool and dry, and this is the most important benefit when it comes to the occupant of the room — hotel guests, apartment residents, students. In a hot, humid climate, getting away from the humidity is just as important as the heat, and the Dry Air 25 is the perfect solution. The dehumidification of the Dry Air 25 has been verified by the same ARI test conditions that standard units are rated under. A list of customers using Dry Air 25 is available from GE.
GE Dry Air 25
GE 2500 Series Zoneline
*Based on 12,000 BTU Units.

Mini Specs 2800, 3800 and 5800 Series 2
Mini Specs Power Connection Kits and Nomenclature 3
The 2800/3800/5800 and Dry 25 4
Table of Contents 5
Introduction 6
The Zoneline System 7
Features and Benefits
Features Table 8
Features and Benefits 9-11
Auxiliary Control Switches 12-13
Central Desk Control 14
Remote Thermostat Control 15-17
Heat Pumps and Energy Savings 18-19
Installation and Dimensions
Application Comments 20
Case Dimensions 21
Wall Case/Sub-Base Installation 22-33
Condensate Disposal Systems 34-36
Ducted Installations 37-39
Exterior Grilles 40-41
Product Data
Electrical Connection 42
Essential Elements Ordering Overview 43
Maximum Connected Load 44
Cooling/Heat Pump Performance Data 45
Latent System Capacity 46
Normal Yearly Operating Data 47
Schematics 48-50
Product Specifications
Important Notice
Suggested Bid Form Specifications 51-53
Equipment used as a primary source for heating or cooling is an integral part of the building in which it is installed. Proper application is essential for satisfactory performance over a wide range of operating conditions. It is strongly recommended that a professional engineer determine proper application.
Specifications 55
Complete Accessory List 56
General Installation Suggestions 57-58
Warranty 58
Alphabetical Index 59
If this unit is a replacement unit, its specifications and performance may differ from those of the unit it is replacing. For that reason, we again strongly recommend that a professional engineer determine proper application.

This manual is designed to provide product, performance and application information to our customers and their architects and engineers for use in selection and design of a zonal comfort control system utilizing GE Zoneline® Packaged Terminal Air Conditioners (PTAC) and Packaged Terminal Heat Pumps (PTHP). GE Zoneline PTACs and PTHPs are self-contained units designed for through-the-wall installations in hotels, motels, apartments, hospitals, nursing homes, add-on rooms and many other installations. Zonelines provide individual room or zone control in both cooling and heating operation. There is a model for practically every application, ranging in cooling capacity from 7,100 to 14,700 BTUH and heating capacity from 6,400 to 13,400 BTUH in heat pump operation. See pages 33 and 55 for resistance heaters available. Zoneline offers a two-tier lineup: the Deluxe Line and the Premium Line. The Deluxe Line consists of the 2800 Series with electric resistance heat, the 2800 Series Dry Air 25 Models with enhanced dehumidification for hot and humid climates and the 3800 Series heat pump. The 3800 Series heat pump features reverse cycle defrost and simultaneous supplemental resistance heat, when needed, to maintain room comfort. The Premium Line features the 5800 Series heat pump with reverse cycle defrost and supplemental resistance heat, when needed, to maintain room comfort, plus tactile touch controls with digital display and standard corrosion protection.
Advantages of the GE Zoneline System: • Flexible Application —May be installed from flush to finished floor to 3" from
the ceiling —7,100 to 14,700 BTUH units in same physical size —Deluxe 2800 and 3800 Series may be ducted to condition
more than one room —Compatible with Class 2 remote thermostat control —Compatible with 2 wire CDC or many Energy
Management systems • Economical Installation —No ductwork necessary —No mechanical equipment rooms or pipes required for
wall cases • Quiet Operation —Indoor double cut-off scroll: two fan motor 2800 and 3800
Series units —Indoor cross-flow blower: 2 fan motor 5800 Series units • Energy-Saving Operation —Units in unoccupied areas may be turned off —Designed for efficient cooling operation — EERs from 10.0
to 13.0 —Efficient heat pump units — COPs from 3.2 to 3.6 —Extended heat pump operation without sacrificing
room comfort • Ease of Maintenance —Permanently lubricated fan motors —Upfront lift-out interchangeable filters —Air Discharge area is easily accessed for cleaning —Slide-out chassis for easy access for cleaning or if
service is required • Reverse Cycle Heat Pump Operation Both the 3800 and the 5800 Series heat pumps utilize the unique GE PTAC heat pump operation to ensure a comfortable room. The logic used by the units is the same logic used by central system heat pumps to provide greater savings.
standard corrosion protection.

The typical Zoneline installation consists of the wall case (or sleeve), chassis, and exterior grille. Some installations may use a sub-base for support of the unit or for ease of electrical connections. Each of the components should be the standard products offered by GE or, in the case of the exterior grille, approved by GE Applications Engineering. Use of components not specifically designed or approved for use with the Zoneline can result in unsatisfactory operation and can be the cause of failure not covered by the warranty.
Typical Installation (Deluxe Series shown)
Wall Case RAB71A (Steel-Insulated) RAB77 (SMC — Molded) Wall Case Options (See page 22)

Room Cabinet
RAG67 (shown) Grill Options (See page 40)

Power Connection Kit (required on all units) Line Cord Kit shown See pages 42-43
Optional Accessories of the Zoneline System
Chaseway


RAK6052 Duct Adapter (For Deluxe Series)

RAK601/602 (For Deluxe Series) Duct Extension, Register and Trim Flange
See pages 23 and 33 for information on electrical sub-bases and chaseway. See pages 37-39 for information on ducted installations.

AZ AZ AZ 2800 3800 5800 Enhanced Dehumidification — Dry Air 25 Optional N/A N/A
Cooling EER Range (230 Volts/265 Volts) 10.2 - 12.7 10.0 - 12.7 10.2 - 13.0
Heating COP Range (230 Volts/265 Volts) N/A 3.2 - 3.6 3.2 - 3.6
Heat Source — Electric Resistance Heat Standard — —
Heat Source — Heat Pump With Selectable
Full Time or On Demand Simultaneous/ Supplemental Resistance Heat — Standard Standard
Staged Heating — 3 Stage 3 Stage
Universal Heater — UPC* Standard Standard Standard
Unit Controls Rotary Knobs Rotary Knobs Touch Pad
Electronic Temperature Selection (Slews Up & Down) with Digital Display — — Standard
Unit Diagnostics — — Standard
Highly Featured Microprocessor Controls Standard Standard Standard-Plus
Electric Resistance Heat Lock-Out (above 46°F) — Standard Standard
Automatic Emergency Heat — Standard Standard
Heat Pump Defrost System — Reverse Cycle Reverse Cycle
High Temperature Operation Protection — Standard Standard
Quick Heat Recovery — Standard Standard
Temperature Boost Selectable Selectable
Service Indicator — — Temp Display Blinks
Fan Motors — Permanently Lubricated 2 2 2
2-Speed Outdoor Fan Standard Standard Standard
Indoor Fan Speed Selections — HIGH/LOW Standard Standard HIGH/LOW/AUTO
Fan Only Setting — HIGH/LOW Standard Standard Standard
Fan Cycle Switch “Smart Fan” “Smart Fan” “Smart Fan”
Constant-Run Fan Selectable Selectable Selectable
Rotary Compressor Standard Standard Standard
Automatic Compressor Restart Delay Standard Standard Standard
Freeze Sentinel™ Standard Standard Standard
Heat Sentinel Standard Standard Standard
Indoor Coil Frost Control Standard Standard Standard
Transfer Fan Connections Standard Standard Standard
7-Step Electronic Temperature Limiting Standard Standard Standard
Remote Control Capability with Wall Mounted Thermostat Standard Standard Standard
Central Desk Control Capability Standard Standard Standard
Energy Management System Interface with Load Shedding Option Standard Standard Standard
Reversible Indoor Air Louvers 40º/50º Standard Standard Standard
Up-Front Filters Standard Standard Standard
Easy-Clean Air Discharge Area Standard Standard —
Concealed Manual Vent Control Standard Standard Standard
Ducted Installation Capability RAK6052 RAK6052 —
Corrosion Protection (Standard on Dry Air 25) Optional Optional Standard
Internal Condensate Removal (ICR) (Factory Installed Option. Cannot be used in Corrosion Areas.) N/A Optional Optional
*UPC — Universal Power Cord Connection (See pages 42 and 55). 265-volt units must be connected in a manner to meet National Electrical Code and all local codes.

Standard Physical Dimensions GE has maintained the same dimensions since 1961 — 42" wide x 16" high x 13-3/4" deep Replacement of older units is made easy.
Reverse Cycle Heat Pump Defrost System Standard on all Zoneline 3800 and 5800 Series heat pumps. Enables heat pump to operate at lower temperatures when other systems switch to more expensive electric resistance heat. See pages 18 and 19 for discussion of heat pump operation and defrost systems.
Weather-Protected Electrical Components Vital electrical components are protected from the weather by locating them on the indoor side of the weather barrier.
High Temperature Heat Pump Operation Protection Automatically protects the compressor if heat pump is operated with high outdoor temperatures. Power to the outdoor fan is turned off if the indoor coil gets too hot during heat pump operation to prevent damage to the compressor.
Weather-Resistant “Superseal” Properly installed unit in undistorted case keeps air leakage to a minimum. 7 CFM air infiltration with 25 MPH wind on non-ICR units — 10 CFM on units with ICR. Industry specification is 19 CFM of air infiltration.
Quick Heat Recovery – Heat Pump Units When the unit operation is changed from STOP or COOL to HEAT, the electric resistance heaters are used to warm the room to the thermostat set point. This provides faster room temperature increase for greater guest comfort.
Heater Sizes to Meet Room Requirements All units are equipped with a universal heater — the resistance heat output is determined by power connection kit. 230/208-volt — Line Cord Connected Units — 2.55/2.09 KW with RAK3153 — 15-amp circuit; 3.45/2.82 KW with RAK3203 — 20-amp circuit; 5.0/4.09 KW with RAK3303 — 30-amp circuit. 230/208-volt - Sub-Base Connected Units — 2.55/2.09 KW with RAK204D15P — 15-amp circuit; 3.45/2.82 KW with RAK204D20P — 20-amp circuit; 5.0/4.09 KW with RAK204D30P — 30-amp circuit. 265-volt — 2.55 KW with RAK5172 — 15-amp circuit; 3.45 KW with RAK5202 — 20-amp circuit; 5.0 KW with RAK5302 — 30-amp circuit.
Unit Diagnostics The 5800 Series has a dip switch that activates each of the various components of the unit to operate briefly. This enables the technician to determine if individual components are functioning properly.
Service Indicator On the 5800 Series, if the microprocessor detects a compressor malfunction, the digital temperature display will blink. If the malfunction occurs during cooling operation, the indoor fan will continue to operate. If the compressor malfunctions in heating mode, the unit will automatically switch to resistance heat to maintain room temperature set point. GE Service should be called to check the Zoneline.
Unit Controls 2800 and 3800 Series — locked-in-place rotary knobs for temperature and operation selection. 5800 Series — touch pad controls with digital readout of temperature set point.
Fan Motors – Permanently Lubricated All units have two fan motors for quiet operation and maximum operating efficiency. Motors are permanently lubricated to reduce maintenance and totally enclosed to keep dirt and water out of the motor windings.
Highly Featured Microprocessor Controls Microprocessor controls are programmed to interface with the temperature sensors to maximize comfort conditions for the room occupant and provide outstanding features. Thermistors are used to sense small changes in temperature to give excellent room control and allow the microprocessor to monitor and react to changing conditions.
2-Speed Outdoor Fan The unit automatically selects the most efficient speed for the outdoor fan. The operating sound level is lower when the outdoor fan can operate in low speed yet there are situations where it must operate in high speed. The unit changes the fan speed automatically.
Electric Resistance Heat Lock-Out To maximize the savings of the heat pump operation, the Zoneline heat pumps do not utilize the resistance heater when the outdoor temperature is above 46°F during normal operation. The resistance heat is used in the Quick Heat Recovery feature.
Indoor Fan Speed Selections – HIGH/LOW Unit may be operated in HIGH HEAT or LOW HEAT or HIGH COOL or LOW COOL.
Automatic Emergency Heat Automatically uses electric resistance heat if the heat pump output is not sufficient to maintain selected room temperature.

Fan-Only Setting – HIGH/LOW The unit provides the option of selecting either HIGH or LOW speed for Fan-Only operation.

Prevents indoor coil from freezing and causing complaints due to lack of cooling. Frost can form on the indoor coil when the unit is operated in cooling when outdoor temperatures are low. The unit automatically shuts the compressor off until the indoor coil temperature warms to the point where frosting will no longer occur.
Fan-Cycle Switch – “SmartFan” Unique “SmartFan” allows unit to operate fan continuous in cooling operation and fan cycle in heating to provide better guest comfort. Eliminates complaint of cold air draft during heating operation. Eliminates need of changing fan-cycle switch seasonally. “SmartFan” settings are controlled by two dip switches on auxiliary control panel.
Transfer Fan Interface 24 VAC terminals are provided to operate a relay to control a fan mounted in a wall to move conditioned air into another space. The electrical power for the operation of the transfer fan itself is not provided by the Zoneline. Transfer fans and their controlling relays are field supplied.
Compressor Random Restart In the event of a power failure, all compressors attempting to restart immediately when power is restored can result in a power surge that can cause another power interruption. The microprocessors in the Zonelines have a random restart logic system that prevents all units from starting at the same time.
Electronic Temperature Limiting Seven independent programmable heating temperature limits and seven independent programmable cooling temperature limits. Eliminates need to reset the limits seasonally.
Rotary Compressor Smoother operation for quiet, dependable service. GE has used rotary compressors since 1961.
Compressor Restart Delay Zonelines are designed to provide a minimum of three minutes of compressor off time to allow refrigerant pressures to equalize before restarting to prevent compressor damage. Zonelines are also designed to provide a minimum of three minutes of compressor run time to prevent room occupant disturbance due to short-cycling of the air conditioner.
Limits are set by dip switches on auxiliary control panel.
Remote Control Capability with Wall-Mounted Thermostat See pages 15-17.
Detects low room temperature and turns on heater to help protect against damage caused by freezing room temperature. Heater turns on at 41°F and warms indoor thermistor temperature to 46°F and shuts off. Freeze Sentinel may be turned off by dip switch on auxiliary control.
Central Desk Control Capability See page 14.
Energy Management System Interface with Load Shedding Option All units have a switch on the auxiliary control panel to allow the indoor fan to continue operating if the unit is connected to an Energy Management System that shuts off compressor or heater operation. By allowing the indoor fan to run when the heater or compressor is shut off by the Energy Management System, the guest is less likely to realize the operation of the unit has been altered. This helps reduce peak energy demand loads without disturbing the room occupant.
Heat Sentinel The property owner may choose to activate the Heat Sentinel feature on the Zoneline. If the Heat Sentinel is activated and room temperature reaches 85°F while the unit is in the “STOP” setting, the unit will automatically start in air conditioning operation and will shut off when the room temperature reaches 80°F. This will help dehumidify the air and lower high temperatures so the guest will not be entering an extremely hot room.
Reversible Indoor Air Louvers Allows air to be directed into room at 40º or 50º angle to provide better air distribution. Angle is changed by removing room front and screws holding louver in place, and rotating louver section.


Up-Front Air Filters Two interchangeable up-front filters, easy to remove and reinstall, may be cleaned without opening or removing the room front. Clean filters by brushing, vacuuming or back- flushing under faucet or shower head.
Corrosion Protection (Optional) 2800 and 3800 Series units may be ordered with special protection to better withstand damage from salt air and salt water in seacoast areas. Corrosion protection is standard on the 5800 Series and on Dry Air 25 models. Heat Pump units with ICR are not available with corrosion protection and should not be installed in seacoast or corrosive environments. Units installed in corrosive areas should be examined and cleaned more frequently than normal installations.
Easy Clean Air Discharge Area 2800 and 3800 Series units have an out-of-sight vertical protective screen over the indoor fan. This allows easy cleaning of air discharge area by simply removing room front and wiping clean. There is no screen directly below discharge louver to trap unsightly dirt and debris where it may be seen by room occupant.
Internal Condensate Removal (ICR) See page 34 for a discussion of the Internal Condensate Removal system available on 3800 and 5800 Series heat pumps.
Enhanced Dehumidification Moisture removal is an important function of an air conditioner. People are more comfortable at higher temperatures when the humidity level is relatively low. Air conditioners operate with less energy consumption when the room temperatures are set higher. The GE Zoneline® 2800 Series with the Dry Air 25 heat pipe application removes 25% more moisture than the base 2800 Series unit. The GE Zoneline Dry Air 25 chassis is the only PTAC available with the application of the patented Dinh® Dehumidifier Heat Pipe under license from Heat Pipe Technology, Inc. Customers who are using the Dry Air 25 report a fresher- smelling room as a result of the lower humidity levels, as well as lower operating costs.
Concealed Manual Vent Control The 3-position manual vent door control may be closed, partially open or fully open.

Locking Door Kit RAK8023 — A door with a lock that replaces the standard control cover door to prevent unauthorized changing of control setting is offered as an accessory.
CFM ratings at 230 volts and 265 volts. Greater amounts of air will be introduced if the room has an exhaust fan. An open vent door brings unconditioned outdoor air into the room, increasing heating and cooling costs. Positive vent door closure prevents accidental opening and unwanted air infiltration.

These switches are located behind the room cabinet under the control panel.
2800 and 3800 Series Switches Description Left Switches (1) ALL I2R Heat pump override — Down — Normal heat pump operation Up — resistance heat only (3800 Series only) (2) C: FAN Fan control for cooling operation — Down — Fan Continuous Up — Fan Cycle (3) H: FAN Fan control for heating operation — Down — Fan Cycle Up — Fan Continuous (4) CLASS 2 Remote Thermostat Mode — Down — Unit Control Up — Remote Thermostat (5) LOAD SHED Load Shedding when connected to Central Desk Control System — Down — Fan shuts off with unit Up — Fan under “Smart Fan” settings (6) FREEZ S Freeze Sentinel™ Override — Down — Freeze Sentinel ON Up — Freeze Sentinel OFF (7) CONST FAN Constant Fan — Down — Fan runs normally Up — Fan runs when unit is in STOP position (8) OCCUPIED Occupancy Sensor Mode — Down – Unit Control Up — Occupancy Sensor Connected Right Switches TL1 – TL3 Cooling temperature limiting (See table at bottom of page) TL4 – TL6 Heating temperature limiting (See table at bottom of page) (7) Heat Sentinel switch — Down — Heat Sentinel OFF Up — Heat Sentinel ON (8) Heat Boost (3800 series only) — Down — Heat Boost OF Up — Heat Boost ON Auxiliary (2800 and 3800 series)

HIGH COOL 1 2 3 4 5 6 1 2 3 4 5 6 7 8
ALLI2R (All Electric Heat) (3800 Series models only) C: FAN CN (Cooling–Smart Fan)
TL1 (H) (Temp. Limit 1–Heat) TL2 (H) (Temp. Limit 2–Heat) TL3 (H) (Temp. Limit 3–Heat)
LOAD SHEDDING (CDC) FREEZ Sen (Freeze Sentinel) CONST FAN (Constant ON Fan) OCCUPIED (Occupancy Sensor)
TL1 (C) (Temp. Limit 1–Cool) TL2 (C) (Temp. Limit 2–Cool) TL3 (C) (Temp. Limit 3–Cool)
Cooling and Heating temperature limits are set independently, temperature limiting switches are in factory-set down position, except as noted.

These switches are located behind the room cabinet under the control panel.
5800 Series Switches Description Left Switches (1) ALL I2R Heat pump override — Down — Normal heat pump operation Up — resistance heat only (2) C: FAN Fan control for cooling operation — Down — Fan Continuous Up — Fan Cycle (3) H: FAN Fan control for heating operation — Down — Fan Cycle Up — Fan Continuous (4) CLASS 2 Remote Thermostat Mode — Down — Unit Control Up — Remote Thermostat (5) LOAD SHED Load Shedding when connected to Central Desk Control System — Down — Fan shuts off with unit Up — fan under “Smart Fan” settings (6) FREEZ S Freeze Sentinel Override — Down — Freeze Sentinel ON Up — Freeze Sentinel OFF (7) CONST FAN Constant Fan — Down — Fan runs normally Up — fan runs when unit is in STOP position (8) OCCUPIED Occupancy Sensor Mode — Down — Unit Control Up — Occupancy Sensor Connected Right Switches TL1 – TL3 Cooling temperature limiting (See table at bottom of page) TL4 – TL6 Heating temperature limiting (See table at bottom of page) (7) Diagnostics Switch (8) Heat Sentinel switch — Down — Heat Sentinel OFF Up — Heat Sentinel ON (9) Heat Boost — Down — Heat Boost OFF Up — Heat Boost ON


HIGH COOL 1 2 3 4 5 6 1 2 3 4 5 6 7 8
ALLI2R (All Electric Heat) (5800 Series models only) C: FAN CN (Cooling–Smart Fan)
LOAD SHEDDING (CDC) FREEZ Sen (Freeze Sentinel) CONST FAN (Constant ON Fan) OCCUPIED (Occupancy Sensor)
TL1 (H) (Temp. Limit 1–Heat) TL2 (H) (Temp. Limit 2–Heat) TL3 (H) (Temp. Limit 3–Heat)
TL1 (C) (Temp. Limit 1–Cool) TL2 (C) (Temp. Limit 2–Cool) TL3 (C) (Temp. Limit 3–Cool)
Cooling and Heating temperature limits are set independently, temperature limiting switches are in factory-set down position, except as noted.
Switches Up NONE 1 1, 2 2 2, 3 1, 2, 3 1, 3 3
Switches Up 6 4, 6 4, 5, 6 5, 6 5 4, 5 4 NONE
65 70 72 74 76 78 80 85

Some installations may want to govern the ability of the unit to operate from a control device remote to the unit or even remote to the room in which the unit is located. The general term given to systems such as this is Central Desk Control. The most common installation of this type of system is a switch mounted at the registration desk and, upon guest check-in, a button is pushed or a switch is moved to allow the air conditioner to operate. Likewise, when the guest checks out the device is put into the “OFF” position so the unit will not operate while the room is vacant. It is not necessary that the controlling device be located at a central desk to employ a device that will control the unit operation. For instance, in some resort areas devices are connected to sliding glass doors and opening the door causes a contact to close, turning the air conditioner off. This prevents energy being wasted by operating the air conditioner when warm, humid air is entering the room. Some systems operate by motion sensors or heat sensing detectors mounted in the room. These types of systems determine occupant presence in the room and allow the unit to operate; if no one is in the room the device signals the air conditioner to turn off. Zoneline® models offer Load-Shedding capabilities on units connected to Central Desk Control Systems. For more information on the models’ Load-Shedding Feature, see page 10. There is a wide variety of devices available, each with its own benefits and constraints. While GE does not offer components that are external to the unit for a Central Desk Control (CDC) system, GE Zonelines are compatible with most CDC and Energy Management systems. Zonelines provide a 24 VAC circuit that powers the Central Desk Control system and no external power is needed. All Zoneline 2800, 3800, and 5800 Series units are compatible with simple on/off 2-wire Central Desk Control systems. Consult with the provider of other energy management systems to be sure they are compatible with the GE Zoneline. Zonelines have standard connectors factory-installed to provide a CDC interface that permits the unit to be connected to most of the energy management systems. The devices connected to the Zoneline units require no power supply or transformers external to the unit. Important CDC Comments (all series applicable)
Wire Size #AWG Maximum Allowable Length #22 600 Ft. #20 900 Ft. #18 1500 Ft. #16 2000 Ft. Freeze Sentinel™ remains operational when the unit is connected to a CDC system. Even if the unit is turned “OFF” at the central location, if the sensor at the unit detects the low temperature, the electric resistance heaters and the fan will automatically turn on. Connecting the Zoneline to a CDC system does not eliminate the ability to connect the unit to a remote thermostat. Once the circuit is “opened,” and control of the unit removed from the CDC system, the selected controls - either the unit mounted control or the remote thermostat - govern the operation of the unit. Please see page 57 for installation recommendations for the Central Desk Control wiring.
CDC Terminal Location and Typical Wiring See page 15 for location of CDC terminals on unit.

1. When the switching device closes the circuit of the CDC conductors, the unit operation stops. 2. Do not use a common buss (at the unit or at the switch panel) in the wiring. Both wires comprising the circuit must connect to the unit connectors and to the controlling switch. Running one wire from one unit to another unit is common bussing and may damage internal components or cause erratic operation of the system. 3. A 24-volt transformer is contained within the Zoneline. No external voltage may be applied to the unit through the CDC terminals. (Voltage on the CDC conductors is 24 volts AC.)

Remote Thermostat Control
In some installations, control of the operation of the unit at a location remote from the unit itself may be desired. A unit mounted high in the wall or over a door, for instance, where the unit-mounted controls are inaccessible, can be connected to a wall-mounted thermostat. Other installations may use remote thermostat control for design or performance enhancement. The unit is connected to the thermostat by low-voltage wiring which permits the operation of the unit to be selected and the temperature sensed at the thermostat. Important Notes: Remote thermostat wiring should not be run through wall case. Thermostat wiring should exit the wall below the unit and enter the unit between room cabinet and chassis. Wire molding may be used to hide thermostat wiring. If a sub-base is used, the thermostat wiring may be concealed by the sub-base. Thermostat wiring should not be run parallel to line voltage wires since induced current may cause erratic operation. All Zoneline 2800, 3800 and 5800 Series units are adaptable to Class 2 remote low-voltage thermostat. The only additional field-supplied components are the remote thermostat and wiring necessary to connect it. The controls on the unit are not functional when the remote control function is used.
The AC voltage may not be compatible with some solid-state thermostats. The fan speed for the 2800 Series in remote thermostat operation is selected by the connection of the fan wire from the thermostat to either the HIGH or LOW terminal on the unit. See the sketch of the unit terminals for the location of the HIGH and LOW fan-speed terminals. Operating the unit in low fan speed reduces the operating sound level of the unit. Freeze Sentinel™ remains operational if the unit is connected to a remote thermostat. The unit may be connected to a Central Desk Control (CDC) system and controlled with a remote thermostat when the CDC system has the unit in operation. See page 14 for additional information on the CDC system. Unit temperature limiting switches are not functional when unit is connected to a remote thermostat. Field Wiring Terminal R — 24V AC GL — Low-Speed Fan GH — High-Speed Fan B — Not Used on 2800 Y — Compressor W — Heater C — Common — Ground
Resistance Heat Models The Zoneline 2800 resistance heat units may be connected to a single-stage thermostat designed for use with cooling with electric heat systems. GE offers three thermostats compatible with the 2800 Series unit.

R
GL
GH
B
Y
W
Common — Ground White — Heater Yellow — Compressor Black — Not Used On 2800 Green — High-Speed Fan Green — Low-Speed Fan Red — 24V AC CDC Terminal
RAK163A1 — a mechanical manual changeover thermostat requiring four connection wires.
RAK164D1 — a solid-state digital manual changeover thermostat requiring five connection wires.
RAK164P1 — a solid-state digital programmable auto-changeover thermostat requiring five connection wires.
RAK806 Universal Control Cover Label When a Zoneline unit is using a remote thermostat control, the RAK806 Universal Control Cover Label is recommended. The RAK806 is only available in a package of 10 labels. The label is placed over the control panel directing the user to the wall thermostat for operation of the Zoneline unit.
The Class 2 Mode Switch (dip switch #4 on the auxiliary control board) must be set to the ON/UP mode to enable remote thermostat control. Refer to installation instructions packaged with the chassis. Please see page 57 for installation recommendations for the remote thermostat wiring. Compatibility of other thermostats considered for use with the GE Zoneline is the responsibility of the customer. The control voltage on the remote control conductors is 24 volts AC.

Heat Pump Models The Zoneline® 3800 and 5800 Series heat pump units may be connected to a single-stage cooling/two-stage heating thermostat designed for use with heat pump systems. GE offers 3 thermostats compatible with the 3800 and 5800 series units:
Temperature Boost option should not be used with remote thermostat operation since this will cause the unit to switch to resistance heat when outdoor temperatures are below 46ºF.
Feature Heat Pump Electric Heat Indoor Frost Control Yes Yes Freeze Sentinel Yes Yes Auto Fan Speed No No Electronic Temperature Limiting No No Switch to Resistance Heat Based On Indoor Temperature
Determined by Remote Thermostat N/A Switch to Resistance Heat Based On Outdoor Temperature Yes N/A Reverse Cycle Defrost Yes N/A Simultaneous Resistance Heat with Heat Pump No N/A Resistance Heat Lockout Yes N/A “Smart Fan” Fan Cycle
RAK147 — mechanical manual changeover thermostat requiring 6 connection wires.
RAK148D1 — solid-state digital manual changeover thermostat requiring 6 connection wires.
RAK148P1 — solid-state digital programmable auto-changeover thermostat requiring 6 connection wires.
Please see page 57 for installation recommendations for the remote thermostat wiring. Compatibility of other thermostats considered for use with the GE Zoneline® is the responsibility of the customer. The control voltage on the remote control conductors is 24 VAC. The Class 2 Mode Switch, dip switch #4 on the auxiliary control board on both the 3800 series and the 5800 series, must be set to the ON/UP mode to enable remote thermostat control. Refer to installation instructions packaged with the chassis. The fan speed for the 3800 and 5800 series in remote thermostat operation is selected by the connection of the fan wire from the thermostat to either the HIGH or LOW terminal on the unit. See the sketch of the unit terminals for the location of the HIGH and LOW fan speed terminals. Operating the unit in low fan speed reduces the operating sound level of the unit. When connected to a remote thermostat, the indoor air temperature sensing is shifted from the unit to the remote thermostat. For this reason, the units will operate slightly differently when connected to a remote thermostat. The following chart shows the unit operation when connected to a remote thermostat.
Fan ON/AUTO Set On Remote Thermostat Central Desk Control Yes Yes
Fan ON/AUTO Set On Remote Thermostat
Field Wiring Terminal R — 24V AC GL — Low-Speed Fan GH — High-Speed Fan B — Reversing Valve Y — Compressor W — Heater C — Common - Ground
GL
GH
B
Y
W
Common — Ground White — Heater Yellow — Compressor Black — Reversing Valve Green — High-Speed Fan Green — Low-Speed Fan Red — 24V AC

3800 and 5800 RAK147 Mechanical
Single Stage Cooling –
RAK148P1 Digital Programmable 6
Thermostat wire size – up to 60 feet AWG20 – up to 66 feet AWG18
RAK148D1 Digital 6 · 2 Stage Heating

integral transformer, direct wiring can result in a “bucking” or boosting” voltage condition, and is in violation of the National Electric Code. The diagram below shows the correct wiring for such an installation through the use of field supplied isolation relays.
One remote control thermostat may be used to control multiple resistance heat Zoneline units, however the units may not be wired direct. Since each Zoneline unit has an

Remote Control (Low Voltage) Wiring One stage Thermostat Controlling Three Zoneline Units Resistance Heat Zoneline 2800 Series Units (Not Applicable on Heat Pump Units)

MORE THAN 4 USE COMBINATION OF RELAYS SPECIFIED ABOVE

Balance Point An important consideration of the selection of a heat pump unit is the “balance point” of the installation. Virtually every room is unique — with different insulation — different sizes and types of windows — different types of construction — different directional exposures. All of these variables, as well as geographical location, must be considered in order to determine the balance point, the point at which the heat pump is unable to produce enough heat to compensate for the heat loss of the room or area being heated. For these reasons a consulting engineer should be engaged to calculate the heat loss and specify the heat pump unit required. GE offers two series of Zoneline Heat Pump units — the 3800 Series with Standard Microprocessor controls and the 5800 Series with Highly Featured Microprocessor controls — and both series react to the indoor temperature as well as the outdoor temperature in determining the heat source to provide comfortable room conditions and energy savings. This determination of the heat source based on the indoor temperature helps provide a more comfortable room.

Heat Pump Operation — Zoneline 3800 and 5800 Series Heat sources: Heat pump, heat pump and simultaneous electric resistance heat or electric resistance heat. Zoneline heat pumps employ a highly featured microprocessor control system interfaced with thermistors to accurately measure indoor air temperature, outdoor air temperature, indoor coil temperature and outdoor coil temperature. This system allows the microprocessor to precisely and predictably react to changing conditions in order to provide a very advanced Packaged Terminal Heat Pump operating system. The Zoneline heat pumps are designed to help ensure a comfortable room. When “HEAT” is selected, the unit will determine if the room air is warm enough to satisfy the thermostat setting. If the temperature at the unit sensor is below the desired temperature, the electric resistance heater will be utilized to warm the room to the point where the thermostat is satisfied. This feature is designed to allow the temperature of an unoccupied room to be maintained at an energy-saving level without inconveniencing the room occupant. Once the thermostat has been satisfied, the resistance heater will turn off and the heat pump will operate as shown in the Heat Source Logic chart until the thermostat calls for heat again. The unit will operate in this manner even if connected to a Central Desk Control.
The Quick Heat Recovery feature is not affected by the Heat Source Logic shown in the chart above. For more information about the Quick Heat Recovery Feature, see page 9. The full heat output of the resistance heater is dependent upon circuit amperage and the power connection kit used. See pages 3 and 42-43 for information on power connection kits and available heater capacities. A heat pump switch is provided in the auxiliary controls to allow the unit to operate only in resistance heat. The use of this option significantly increases the cost for heating.
Heat pump defrost — Zoneline 3800 and 5800 Series Zoneline heat pumps utilize a reverse-cycle demand defrost system to extend heat pump operation and increase savings from extended operation. The microprocessor determines the need for defrosting by criteria based on continuous compressor running time, outdoor air temperature, outdoor coil temperature and the rate of temperature change of the outdoor coil. When defrosting is required, the unit reverses the flow of refrigerant to direct the hot gas into the outdoor coil to melt the frost build-up. Before and after the reverse-cycle defrosting, the unit shuts off the compressor to allow the refrigerant pressures to equalize throughout the system. This eliminates the possibility of a loud reversing noise. During these periods of pressure equalization, the full resistance heat capacity of the unit is activated to help ensure room comfort conditions during the defrost cycle. The unit remains in the defrost cycle for a minimum of two minutes up to a maximum of nine minutes. The defrost cycle terminates when the outdoor coil reaches a temperature of 68°F or the maximum time has been reached. Heat pump condensate See page 34 for information on heat pump condensate. The Zoneline 3800 Series heat pumps may be ordered with a factory-installed Internal Condensate Removal (ICR) system to minimize the amount of condensate water draining from the unit during heat pump operation. The ICR system has proven to be an effective means of minimizing the amount of heat pump condensate dripping from the unit. However, if the requirements of a particular installation will allow no dripping of condensate water from the wall case, the installation of an internal or external drain system is recommended. Units with ICR may not be installed in seacoast or corrosive environment applications.
25°F
SET POINT
Less Than 1.8°F Below Heat Pump Heat Pump* Full Resistance
Heat Pump + Supplemental
1.8°F to 2.7°F Below Heat Pump
More than 2.7°F
Below Heat Pump Full Resistance
*If the “Temperature Boost” switch (dip switch #8) is in the “ON” position the supplemental simultaneous heater will be used with heat pump operation. Simultaneous supplemental heater: 1.0 KW @ 230 V; 0.8 KW @ 208V; 1.0 KW @ 265V. The “Temperature Boost” option utilizes the supplemental simultaneous heater simultaneously with heat pump operation when the outdoor temperature is below 46°F regardless of the indoor air temperature. The chart above indicates the heat source of the heat pump under various indoor and outdoor conditions. The unit is designed to provide heat pump savings without sacrificing room comfort.

Use and Care Manual and installation instructions are shipped with Zoneline® units. It is important that any air conditioning system be properly sized and applied in order to achieve the desired temperature and humidity levels with the space to be conditioned. Air conditioners are designed primarily to provide heating and cooling with the additional benefit that during operation in the cooling mode, the units also remove some moisture from the conditioned space. The following are some brief application comments on undersizing, oversizing, heating, wall coverings, and air infiltration: all are important in the proper matching of the heating/air conditioning system to the building structure. Undersizing: If an air conditioner is undersized (cooling capacity is less than required for a specific application), the unit will typically not be able to cool the space down to the desired temperature (thermostat set point), nor be able to remove enough moisture from the air. A result could be a warm and humid or warm and dry conditioned space. Oversizing: If an air conditioner is oversized (cooling capacity is greater than required for the specific application), the unit will typically cool the space down to the desired temperature (thermostat set point) too quickly. The compressor then begins to cycle on and off. Dehumidification only takes place when the compressor is operating. A typical result in a hot/ humid climate could be a cool but excessively humid space. Heating: Undersizing can result in not being able to maintain the desired temperature level within the conditioned space. Wall Covering: Use of a non-permeable wall covering (some paints, some wallpapers, and other types of coverings) which severely restricts passage of air or water vapor can cause a severe moisture problem. Typical results could be staining of room surfaces, wall damage, as well as mold and mildew growth in hot/humid climates. Air Infiltration: Excessive air infiltration can magnify problems associated with undersizing or oversizing of an air conditioner unit and can be the root cause of insufficient cooling, dehumidification, or heating. Some sources of air infiltration include vents, gaps around windows and doors, and improperly sealed floor, ceiling and wall joints. Recommendation: For the above reasons it is strongly recommended that a professional engineer be retained to match the Zoneline unit with the building structure.
High Wall Mount — For units mounted high in the wall, the discharge louvers should be at a setting that provides the most horizontal air discharge. Recommended installation is at least 3" below the ceiling. In installations where units are close to the ceiling, the most horizontal discharge angle can be obtained by removing the discharge grill from the room cabinet. Supply Air Throw — One Zoneline unit should not be required to do a job obviously requiring two or more units. Units should be located around large rooms according to calculated loads or in such fashion as to achieve balanced air distribution in all parts of the room. The single unit in the “Incorrect” illustration below obviously cannot condition the entire room. Add a second unit as shown in the “Correct” illustration.
40°

Air Distribution Zoneline packaged terminal air conditioners and heat pumps discharge air from the top of the unit through reversible 2-position discharge louvers. Unit discharge louvers are reversed by removing the room cabinet from the unit, removing seven screws that hold the louver section in place, removing the louver section and rotating it end for end, reinstalling the louver section in the room cabinet with the seven screws, and reinstalling the room cabinet on the unit. The unit is shipped from the factory with the discharge louvers at an angle of 50° off vertical. In the alternate position, the louvers will be at an angle of 40° off vertical. All room cabinets return air through the front of the unit.

Additional Wall Case Depths RAB7116 - 16" RAB7124 - 24" RAB7128 - 28" RAB7131 - 31"

SEE PAGE 32 FOR KNOCKOUT LOCATION DIMENSIONS.
*SHOWN WITH ACCESS COVERS REMOVED. NOTE: CAUTION - REMOVE KNOCKOUTS FROM INSIDE OUT.
Installation Instructions Packed With Wall Case . . . See Page 25 For Additional Information Concerning Outdoor Weather Panel and Case Stiffener.

“Permanent Connection” generally means wiring to the unit must be contained in an enclosed “chaseway,” where access to the wiring connections is more restrictive than a normal line cord plugged into a receptacle. NEC requirements may be met by using flexible or rigid conduit to contain the wiring between the unit and a junction box that contains the wiring connections. The conduit is connected to the unit and to the junction box with connectors to hold the conduit in place. The junction box may be located in the floor or the wall of the structure but only approved connectors may be used outside the unit or the junction box. The sub-base is UL® listed as a junction box for permanent connection of a Zoneline. Using a sub-base in an installation requiring permanent connection provides a convenient, consistent location for unit wiring to be connected to building wiring. The use of a sub-base is not required, but the convenience and the improved aesthetics it offers makes the use of a sub-base a viable means of permanent connection. RAK204U — The RAK204U Series of sub-bases provides a variety of designs that fit the site needs and are available for use with Zoneline PTAC/PTHP units. The RAK204U will most likely be used for support of the wall case and unit. The RAK204U is the same physically as the other sub-bases except there is no receptacle installed. Receptacles and wiring can be field installed and, by using the RAK205CW chaseway and the RAK4002 junction box perform the same function as any of the other sub-base kits by selecting the correct receptacle and installing it in the interior mounting plate inside the RAK204U. 208/230-volt receptacles can also be mounted in the cover plate for easy access when direct connect wiring is not required. 265-volt units are to be “Permanently (or Direct) Connected” and the external receptacle (when wiring is not enclosed in a chaseway) does not meet this requirement. A knockout for a fuseholder or a disconnect is also provided in the cover plate. RAK204U — No receptacle, no wiring, will accept any 15-, 20-, 30-amp receptacle and wiring. No chaseway is included. RAK205CW chaseway must be ordered separately. The 230/208-volt sub-bases below include a short, sub-base power connection kit. Since sub-base connected units are not considered to be line-cord connected, a Leakage Current Detection and Interruption or Arc Fault Current Interrupter device is not necessary. The junction box (RAK4002A for 2800 and 3800 Series units; RAK4002B for 5800 Series units) that mounts on the chassis of 230/208-volt sub-base connected units must be purchased separately. RAK204D15P 208/230-volt 15-amp receptacle. Receptacle is NEMA6-20R with 18" of #12AWG wires attached to the receptacle. Short power connection kit included. Chaseway included. RAK204D20P 208/230-volt 20-amp receptacle. Receptacle is NEMA6-20R with 18" of #12AWG wires attached to the receptacle. Short power connection kit included. Chaseway included.
The sub-base is an optional accessory for the Zoneline and is presented with the wall case information since the decision to use or not to use a sub-base in the installation is a factor in the location of the wall opening for the unit. National Electrical Code® requires that air conditioning units connected to voltages in excess of 250 volts be “permanently connected.” There are also some installations where units connected to voltage sources under 250 volts may also need to be “permanently connected.” If you are in doubt about the requirements for a particular installation, consult Article 440 of the NEC or the local electrical inspector. These requirements are designed to protect personal safety and should be strictly followed. Although NEC is cited here as a reference, all electrical wiring and installations must conform to any and all local electrical codes and regulations.

RAK204D30P 208/230 volt 30-amp receptacle. Receptacle is NEMA6-30R with 18" of #12AWG wires attached to the receptacle. Short power connection kit included. Chaseway included. The junction box (RAK4002A for 2800 and 3800 Series units; RAK4002B for 5800 Series units) that mounts on the chassis of 230/208 volt sub-base connected units must be purchased separately. Sub-bases for the 265 volt units: RAK204E15 265-volt 15-amp receptacle. Receptacle is NEMA7-15R with 18" of #12AWG wires attached to the receptacle. Chaseway included. RAK204E20 265-volt 20-amp receptacle. Receptacle is NEMA7-20R with 18" of #12AWG wires attached to the receptacle. Chaseway included. RAK204E30 265-volt 30-amp receptacle. Receptacle is NEMA7-30R with 18" of #12AWG wires attached to the receptacle. Chaseway included. The junction box for 265-volt units is shipped with the chassis since all 265-volt units are to be “Permanently (or Direct) Connected.” The Power Connection Kit is not included There are separate internal compartments to permit separation of low voltage (Class 2) connections from line voltage connections as required by NEC. Conduit containing building wiring enters the sub-base through knockouts located in the rear or bottom of the sub-base and is not accessible when the wall case is installed. The sub-base attaches to the RAB71 wall case with two clips (field-assembled) that are screwed into pre-drilled holes in the bottom front flange of the wall case. It attaches to the RAB77 wall case with clips that fit over molded ribs without requiring the use of screws into the wall case. See page 33 for illustration. Since the sub-base extends under the wall case, clearance from the inner edge of the wall case to the finished wall must be 2-3/8" or greater. The sub-base has 4 leveling legs and adjustable side channels to enable the area under the wall case to be enclosed. Clearance from the bottom edge of the wall case to the finished floor must be between 3" and 5". The sub-base may be used as support for the chassis and wall case in installations where the wall is of insufficient thickness to provide secure mounting of the wall case.
exterior wall. See pages 30 and 31 for information on this type of installation. The unit may be installed high in the wall and these installations usually require a remote thermostat and are discussed on pages 15 and 16. Regardless of the installation, there are several things to consider when selecting a location for installing the unit. For instance, drapery location could interfere with air discharge, and placement of furniture may have an impact on the performance of the unit. The following information is intended to minimize installation problems and assure you of trouble-free installation. Refer to page 21 for required wall opening dimensions. Minimum recommended interior and exterior case projection for standard wall thicknesses are shown in the drawings in this manual. The case may be installed flush with the finished indoor wall. Special attention must be paid to room-side case projection when the unit is installed in a ducted application as shown on page 39. In walls thicker than 13-1/2" for line cord-connected units and 11-1/8" for sub-base installations, it may be necessary to install a field-fabricated case extension or use one of the special order RAB71 deep wall cases. If you are unable to locate a local source for case extensions, please contact your salesperson for a possible supplier. Such extension must be carefully flashed and sealed both to the wall case and to the wall to ensure water integrity. This is necessary to ensure that any water entering the wall case, either from operation of the unit or from other sources, such as rain storms or from washing the exterior of the building, will drain from the case without the possibility of capillary action drawing the water into either the room or the wall cavity. In an installation where the case is recessed less than 3" from the outside surface, flashing and sealing may be all the modification necessary. In such an installation, the sides and top of the wall opening must be waterproof to prevent moisture from seeping into and damaging the walls. See pages 30 and 31 for suggested detail. Since the installation of a case extension requires a considerable amount of attention, we recommend using one of the deep wall cases if the standard case is not of sufficient depth. Mounting an outdoor grille or louver section to the building face may cause a space between the outdoor coil and the louver section. Air splitters, aligned with the ends of the outdoor coil, must be installed between the outdoor coil inlet and outlet air streams. Gaps between the outdoor coil and the louver section may allow condenser air recirculation and affect the operation of the unit. See page 41 for requirements for custom louver sections.
Generally, Zoneline units are installed 3" to 5" above the floor (flush to finished floor installation is possible) as near to the center of the room as possible; underneath a window or a glass panel is typical. Normal installation of the wall case allows installation flexibility; from flush with the finished interior wall to a minimum of 1/4" of the wall case extending beyond the finished exterior of the building. Special consideration must be given to installations where the wall case does not extend a minimum of 1/4" beyond the finished
The wall case should be level from side to side and from level to 1/4 bubble tilt to the outdoors. The condensate disposal system in the unit is designed to dissipate the condensate water generated during cooling operation in accordance with ARI standards and actually uses this water for maximum unit efficiency. A level unit will also ensure proper performance of the Internal Condensate Removal (ICR) system optional on heat pump units.

Masonry Wall Construction
For new construction, early planning with the architect is necessary. Unit location, electrical connection locations, and wall openings of the proper dimensions are essential to avoid the necessity of rework, fillers, framing, moving electrical outlets, and other expensive modifications. For existing construction it is important that carpentry, masonry and electrical work be performed by competent, qualified personnel. Since installations in existing construction may involve removal of building material from the structure, locating the wall case must be done correctly.
The wall case should be installed during construction and lintels should be used to support the blocks above the wall case. The wall case will not support the concrete block. The installation instructions show how the wall case must be secured to the masonry and caulked. Do not remove the cardboard stiffener supplied with the wall case until ready to install the chassis. See page 29 for details of installation in masonry wall. For existing masonry construction, wall openings must be made by removing concrete blocks to achieve the proper size opening. Consult the builder, architect, or owner to determine the necessity for lintels to support the block above the wall case. Anchor bolts are normally required to secure the case to the wall and shims may be required to prevent distortion of the wall case when securing the wall case to the wall. Field supplied case angles can be used to position and secure the wall case to the wall and to cover oversized wall openings.
Many installations utilize an architectural window/louver combination to enhance the exterior appearance of the building. The exterior grille for the air conditioner is built as an integral part of the window frame. An internal drain system is highly recommended for these installations (see page 36). When this type of installation is made, there must be provision in the grille work for condensate water to drain to the exterior and not be routed back into the interior of the building or into the wall cavity. Failure to allow for the drainage of condensate water can cause extensive damage to structural components. The problems associated with the lack of condensate drain consideration often show up shortly after the air conditioners are turned on in a new building. New buildings that have been virtually wide open during construction have a significant amount of moisture in the air and in the building components that the air conditioners start removing as they operate. The free area in the louver section must also comply with the requirements shown on page 41. The wall case should be anchored to the architectural window/louver section to reduce air infiltration and excessive vibration of the chassis and wall case during unit operation. Field-fabricated and installed case angles are the recommended method of securing the wall case to the window/louver framework.
For new construction, the opening for the wall case should be framed and the wall case inserted into the opening during construction. Lintels should be used when the building material is heavy and is not self-supporting (such as brick). The wall case will fit an opening of six courses of standard brick or five courses of jumbo brick. Wall framing in this type construction is normally on 16" centers and the wall case will fit a framed opening spanning three 16" O.C. 2" x 4" stud spaces. For existing construction the indoor and outdoor wall will need to be cut out, allowing for clearances of 1/8" on all sides of the wall case. Work should begin on the inside wall. Cut the correct dimensions and mark (using drill holes) the outside wall from each corner of the inside cutout. Studding that interferes with the opening must be removed and a suitable frame constructed to secure the wall case and provide adequate support for case and chassis. As shipped, the RAB71 Series or RAB77 is ready for installation.
With this type of construction, provision for support of the unit, other than by the wall itself, is often required. Such support may be in the form of wood or metallic material of the proper thickness to maintain a level case. This additional support should be located both near the wall and at the front of the wall case. Sub-base (RAK204 Series) with four leveling legs provides an excellent support for the unit in this type of installation. See page 28 for details of this type of installation. In existing construction, common practice is to remove a pane of glass, metal, wood, or other construction material and build a frame around the wall case. Similar filler panel material may be installed around the case for appearance and weather seal.

Preparation of the Wall Case for All Types of Construction
Case Angles
In some installations such as curtain walls, window walls, or where the structural material of the wall is insufficient to support or fasten wall case to, the use of case angles may be used. Case angles are pieces of steel or other material of similar structural strength that are formed to a 90° angle, with holes to fasten the case angle to the wall case and to the structural component of the wall surrounding the wall case. The following describes the procedure when field fabricated and installed case angles are applied. 1. Position case angles around top and sides of wall case at the desired location. Position case angles vertically on each side of wall case to provide a level installation. 2. Mark wall case through holes in case angles. The lowest hole on the sides of the wall case must be a minimum of 2" above the bottom of the case. 3. For RAB71 wall case drill 5/32" diameter holes at locations marked on wall case in Step 2, and assemble angles to wall case using #10 x 1/2" self tapping screws. For RAB77 wall case follow the same procedure except use a #10 x 1/2" bolt, washer and nut to attach case angles to case. Install screws or bolts from outside wall case. 4. Do not drill any holes in bottom of wall case. Do not distort wall case. 5. Do not use case angles for a lintel.
Do not remove the stiffener from inside the wall case or the weather closure panel from the outside face of the wall case until the outdoor grille and chassis are ready to be installed. Installation of Wall Case in Wall Opening 1. Position the wall case into the wall. The room side edge of the RAB71 or RAB77 wall case should be at least flush with the finished wall for line cord installations and permanent connection installations when no sub-base is used, and should project into the room at least 2-3/8" when a sub- base is used. If the minimum exterior dimensions are not met, refer to page 27 and 28. The outside edge of the wall case should extend at least 1/4" beyond the outside wall. This is necessary for proper caulking, to prevent sealing the drain holes in the rear flange of the wall case, and to facilitate the installation of an accessory drain, if used.
The wall case should be level from side to side and from level to 1/4 bubble tilt to the outdoors. The condensate disposal system in the unit is designed to dissipate the condensate water generated during cooling operation in accordance with ARI standards and actually uses this water for maximum unit efficiency. A level unit will also ensure proper performance of the Internal Condensate Removal (ICR) system optional on heat pump units.


shown in Figure 1. Note use of lintel under
case. Do not use the case as a lintel.
16-1/4" MIN. RAB71 16-1/2" MIN. RAB77 ADJUSTABLE FRAMING TO SECURE


*Caulk around perimeter of wall case all four sides where it joins the building - Interior and Exterior.


Window, 2" curtain or panel wall installation with rag rear grille extended beyond outer wall surface
SCREWS IN
USE NO
CASE
OUTDOOR
GRILLE


Allow For Electrical Wiring 0" Min. (See page 27)
0" Minimum 2" Recommended See pages 38-39 for ducted application.
*Caulk around perimeter of wall case all four sides where it joins the building - Interior and Exterior.
16-1/4" x 42-1/4" MIN. FOR RAB71 16-1/2" x 42-3/8" MIN. FOR RAB77

1/4" MIN.
SECTION A-A
SEE DETAIL
EXTENSION ALL 4 FLANGES
FLASHING ALL 4
SIDES
*Caulk around perimeter of wall case all four sides where it joins the building - Interior and Exterior.
EXT.
SHOWING SEALANT LOCATIONS.
BASEPAN/FLANGE DESIGN
WALL
Field fabricated – ge recommends the use of one of the deeper RAB71 wall cases offered as special order items.
RAB71/77 ROOM
WALL CASE
ANY
material: Galvanized G-90 painted.
METAL CASE EXTENSION FOR WALLS DEEPER THAN 13-1/8" (11-1/8" WITH SUB-BASE)
CAULK*
CAULK*
HOLES IN RAB71/77
CUT DRAIN SLOTS
IN BOTH FLANGES
(FOUR REQUIRED)
TO MATCH DRAIN
ALL 4
SIDES
6-1/4" ± 1/4" AS REQ'D.
grade sealant should be applied to all four (4) butting
flanges. Use bolts and nuts or oversized self tapping
to attach the two assemblies. Clean all drain holes of
See diagrams below. The assembly should be sealed
screws (driven from the wall case to the extension)
excess sealant. The assembly must be free draining.
or caulked to the wall around all four sides both
SAME AS ON
DRAIN HOLE
LOCATIONS
WALL CASE
FOUR (4) FLANGES
outdoors and indoors.
SEALANT - ALL
be level.
SUPPLIED)
(FIELD
application procedure. It involves the field fabrication of
a case extension. Since the wall case is a water bearing
watertight. The case extension must contain splitters to
between the completed wall case/extension assembly
depth than the wall case. Where the case recession is
less than 3" and where it is possible to waterproof the
exposed sides and top of the opening, the suggested
wall case as shown on page 31. Where waterproofing
bearing and the connection between the two must be
to apply sealant or caulking for a tight weather seal
procedure is to apply a flashing to the bottom of the
is questionable or not possible, or for installations in
walls of greater depth, the following is a suggested
container, the extension likewise must also be water
clearance to the finished wall and ample surfaces
and the wall opening. It is recommended that the
extension be painted and corner and lap joints be
additionally sealed with a quality grade sealant.
Zoneline units can be installed in walls of greater
projection of 1/4". This allows for room cabinet
prevent recirculation of the outdoor air circuit.
13-3/4" + D"
AIR INTAKE AND
WALL CASE
RAB71/77
DISCHARGE
2" MIN.
10-5/8" ± 1/4"

ALTERNATE – CASE RECESSION LESS THAN 3" WITH SIDES AND TOP OF WALL OPENING WATERPROOF, FLASHING ON BOTTOM ONLY
OUTDOOR
GRILLE
FLASHING
*Caulk around perimeter of wall case all four sides where it joins the building - Interior and Exterior.
CAULK*
CASE
IF GRILLE IS TO BE MOUNTED TO WALL SURFACE A SPLITTERS MUST BE USED, SEE PAGE 30.
A. DISTANCE FROM GRILLE OR CASE TO OUTSIDE SURFACE OF WALL PLUS 2" TO 4"
C. 42" PLUS - SUFFICIENT TO FIT SNUGGLY UNDER AND UP AROUND THE CASE.
A
(TO INSERT UNDER CASE).
D
D. 2" MINIMUM
DIMENSIONS:
A
For an installation that will
of one of the deeper RAB71
against water infiltration,
provide better protection
GE recommends the use
wall cases offered as
special order items.
See page 23.


0" Minimum 2" Recommended See pages 38-39 for ducted application.
Example: frame & brick veneer - dimensional data and comments
*SHOWN WITH ACCESS COVERS REMOVED. NOTE: CAUTION - REMOVE KNOCKOUTS FROM INSIDE OUT.

CASE
MOUNTING CLIP
Knockout holes in the sub-base access plate may accommodate a receptacle, which allows the use of a power cord (if permitted by code for the particular installation).
TYPE “E”
“D” USE WITH
“E” USE WITH
RAB71
RAB77
A knockout for a circuit breaker, fuseholder or a disconnect is also provided. See pages 22 and 23 for description of electrical contents of these sub-bases.
TYPE
(Shown Without Chassis and Wall Case for Installation Location Only.)
BE USED WITH MOLDED
NOTE: TYPE “E”
RAK4002B
TYPE “A” TYPE “B” TYPE “C”
6 REQ’D. 2 REQ’D. 8 REQ’D.
Electrical wiring may enter the sub-base through any of the knockout holes provided in the sub-base.
BE DRILLED 6" FROM EACH SIDE IN FRONT FLANGE. (SEE INSERT).
TO SECURE
TYPE “A”
METAL CASE
SCREW
GREEN
GROUND
(TYPE “C”)
SCREW CLIP
SCREW
TYPE “D”
TYPE “C”
SCREW
ACCESS PLATES
5/32" DIA. HOLE (SEE NOTE)
FOR SECURING TYPE “D”
CLIPS TO SLEEVE USING
TYPE “B” SCREW
TYPE “A” SCREWS 6"
TYPE “C”
SCREW
BY BREAKING OFF SECTIONS OF SIDE
SIDE CHANNELS ARE ADJUSTABLE
FROM 13-3/4" TO 2-3/8" IN LENGTH
TYPE “A”
SCREW
6"

Cooling Condensate Air conditioners produce condensate water as a result of lowering the humidity of the area being conditioned. When the indoor coil temperature is below the dew point, moisture in the air condenses into water droplets on the coil. This water drains to a pan located under the indoor coil and is routed through the barrier, the partition separating the indoor and outdoor sides of the unit, to the base pan on the outdoor side. It is then picked up and dispersed against the outdoor coil, which is hot when the unit is in the air conditioning mode. The water is evaporated into the atmosphere by contact with the hot outdoor coil. This evaporation process also helps lower the temperature of the outdoor coil and improves the operating efficiency of the unit.
Heat Pump Condensate Disposal Since the outdoor coil is cold during heat pump operation, the condensate water cannot be deposited on the outdoor coil as the water would cause frost to form on the coil. This frost would block the airflow through the coil and greatly reduce the outdoor air. Rather than allow this problem to occur, heat pump units must dispose of the condensate in another manner.
The most widely used method of disposing of heat pump condensate is with a “Temperature-Activated Drain Valve.” This is a device mounted in the base pan of a heat pump unit with a bellows that expands on temperature rise and contracts with temperature drop. A shaft with a rubber plug on the end is connected to the bellows. When the outdoor temperature remains above a certain temperature, the bellows is expanded and the plug fits tightly into a hole in the bottom, or base pan, of the unit. When the plug is blocking the hole, as it should be during cooling operation, the condensate water is contained in the base pan. At temperatures when heating is required, the bellows contracts, the rubber plug is retracted from the hole and the heat pump condensate water is allowed to drain into the wall case. The valve is fully open at 49°F.

Slinger Ring Systems Packaged Terminal units employ various means of dispersing the condensate water against the outdoor coil. One of the most popular, and most effective, means is by the use of a “slinger ring.” A “slinger ring” is a ring around the circumference of the outdoor fan. The design of the unit positions the slinger ring very close to the bottom of the base pan so water in the base pan is lifted by the rotating ring. Water picked up by the slinger ring will be dispersed into the air stream and deposited on the hot outdoor coil where it evaporates. All Zoneline Series Packaged Terminal Air Conditioners and Packaged Terminal Heat Pumps utilize a slinger ring for cooling condensate disposal.
Certification Test Requirements ARI (Air Conditioning & Refrigerating Institute) requires that all certified Packaged Terminal Air Conditioners and Packaged Terminal Heat Pumps pass a cooling condensate disposal test. One stipulation of the ARI test is that “the test start with condensate collection pan brimful.” In order to pass the ARI Condensate Disposal Test the unit must operate continuously for four hours without condensed water blowing, dripping, or running off the unit casing during the test or after the unit has been turned off. Under extremely high outdoor humidity conditions or extreme operating conditions, such as exceptionally high air infiltration (a door or window left open while the unit is running, for instance) it is possible for any air conditioner to be unable to dissipate all the cooling condensate generated. All Zoneline® Series Packaged Terminal Air Conditioners and Packaged Terminal Heat Pumps meet the condensate disposal requirements of ARI standards 310-93 and 380-93.
Drain Kits Although the Zoneline units are designed to dissipate all of the condensate generated during normal cooling operation, there may be times when abnormal operating conditions cause more condensate than the unit can dissipate. Heat pumps also generate condensate that the unit may not be designed to dissipate. For these reasons, if condensate dripping from the wall case is objectionable, an internal or external drain system should be installed. See pages 35 and 36 for information covering the drain systems and the RAD10 kit available to connect to the wall case.
Internal Condensate Removal (ICR) System GE has developed an Internal Condensate Removal (ICR) System for Packaged Terminal Heat Pumps. This system has been offered as an option on Zoneline Packaged Terminal Heat Pumps since 1982, and thousands of them are in use. During heat pump operation the ICR system utilizes a small pump to lift the water from the base pan and pump it into a collector tray positioned above the indoor coil. The water drains from the collector tray and drips onto the warm indoor coil where it is evaporated into the room atmosphere. If an excess amount of water is pumped to the indoor side, it is routed back to the outdoor portion of the base pan. The ICR system has proven to be an effective means of minimizing the amount of heat pump condensate dripping from the unit. However, if the restrictions of a particular installation will allow absolutely no drippage of condensate water from the wall case, the installation of an internal or external drain system is recommended. Units with ICR may not be installed in seacoast or corrosive environment applications.
Heat Pump Condensate During the operation of a unit in the heat pump, or “reverse cycle,” mode the outdoor coil becomes the cold coil and the indoor coil becomes the hot coil due to reversing the flow of the refrigerant. When the temperature of the outdoor coil is below the dew point, condensation will form on the outdoor coil just as it does on the indoor coil during cooling operation. Since the dew point is humidity- as well as temperature- related, there may be more condensate on days when the relative humidity is high.

NOTE : SHADED PARTS AND
WITH RAD10 DRAIN
KIT. USE EITHER THE
90° ELBOW TUBE OR THE STRAIGHT TUBE
THE REQUIREMENTS
OF THE PARTICULAR
DEPENDING UPON
INSTALLATION.
CABINET
WALL CASE ROOM
CASE ANGLES (FIELD SUPPLIED)
FIELD SUPPLIED FLOOR
6" long, 1/2" O.D. straight
copper tube.
GRILLE
90° ELBOW DRAIN TUBE
BEYOND WALL
the building.
PROJECTION
CASE
External Drain. See page 36 for internal drain.
precipitation, to flow into the wall case and drain through two drain holes in the rear of the wall case. If there is more
For those installations where water draining from the drain holes is objectionable or where positive drainage is desired,
the RAD10 drain kit is available with either a 90° elbow or a 6" straight tube to be used either to connect to a field sup-
through RAG66 exterior grilles. Modification must be made to the RAG61 through RAG66 exterior grilles when using the
straight tube. Modification must be made to the RAG67 grille if using either the 90° elbow tube or the straight tube (see
WATER DRAINAGE - Precipitation entering the unit through the outdoor louver may not be removed entirely by the
water in the wall case than can be drained through these holes it will drain through the three overflow drain holes.
RAG60 exterior grille. Drain kit using the 90° elbow tube may be installed without modification when using RAG61
condensate removal system. The base pan flange is designed to allow excess water, either condensate water or
NEOPRENE SPONGE GASKET
plied drain line or to allow the water to drip free rather than drain down the surface of the building.
These drain holes must not be blocked when mounting or caulking the wall case.
USE TYPE “A” SCREW FOR METAL CASE (RAB71)
installation instructions with the RAG67 grille).
METAL “B”
SCREWS
“A”

For these the drain should be at least 3" from the indoor edge of the case so as to adequately
BELOW
OVERFLOW RELIEF DRAIN
SQUARE DRAIN HOLES
SEE NOTE 6
NEOPRENE SPONGE GASKET
Internal Drain. See page 35 for external drain.
clear the sub-base.
(See details at left)
CABINET BOTTOM
AND TYPE “B” SCREW FOR MOLDED CASE (RAB77)
USE TYPE “A” SCREW FOR METAL CASE (RAB71)
USE TYPE “A” SCREWS FOR BOTH RAB71 AND RAB77
NOTE : SHADED PARTS AND SCREWS
INCLUDED WITH RAD10 DRAIN
KIT. THE 90° ELBOW TUBE IS
DRAIN INSTALLATION.
PLATE
TUBE
1/2" OD
DETAIL GASKET
PLASTIC
METAL “B”
(MOLDED CASE (RAB77) ONLY)
SCREWS
NUT
“A”

2800 and 3800 Series Zoneline units may be used in ducted installations. With a ducted installation it is possible to condition the air in two areas that have a common wall separating them. A special adapter mounts on the wall case and a transition piece directs the air from the unit into the adapter. Instructions for mounting the adapter to the wall case are included with the duct adapter. The adapter contains a grille that allows air from the unit to be discharged into the primary room and the adapter connects to a duct extension that allows the air to flow to the adjoining room. Ducting a unit may allow a single unit to be used rather than a separate unit in each room, providing a means of reducing initial equipment cost. The duct may extend a total of 15 feet (with a field fabricated insulated duct extension) in one direction, either to the right or to the left of the unit. A baffle in the adapter allows up to 50% of the discharge air to be delivered to the secondary room. The installation of the wall case and sub-base, if used, is the same for units being ducted as for free-standing units. The duct adapter support bracket overlaps the wall case by 1" and the bracket and mounting screws add approximately 3/8" (3/16" on each side) to the width of the wall case. If less than 1" of the wall case projects into the room it will be necessary to allow for the additional width in the opening for the wall case. The duct adapter mounting brackets should be mounted prior to installing the case in the wall. Refer to pages 38 and 39 for drawings of ducted installations. Prior to the installation of the transition from the room cabinet to the adapter, it will be necessary to remove the discharge grille from the room cabinet. Instructions for this modification are included with the duct adapter.

one end of the duct to accept the collar and supply register. Mounting Collar and Supply Register RAK602 —These components are included in the Duct Extension Kit RAK601. They may be ordered separately for installations where two duct extensions are made from one RAK601.
When designing a ducted application some application considerations to be made include: 1. Do not exceed the 15-foot length maximum for the duct extension. Field supplied duct extension must be completely insulated with minimum of 1/2" insulation 2. The duct must be a straight run. Turns or bends in the duct extension create air pressure drops that the unit is not designed to overcome. 3. Minimum recommended clearance between the unit and the adjacent wall is 2". 4. Provisions for return air must be made to allow air circulation from secondary room. Doors in both secondary and primary rooms may be undercut or a return grille may be installed through a common wall. 5. When calculating the heat gain/heat loss take both areas into consideration.
Since the design of the Zoneline chassis has changed over the years to provide better performance and appearance, some of the components used in ducted applications have changed. Select the proper components from the information below. The best procedure in determining the correct kit is to measure duct extension cross section.

Flat Top-Discharge Units (Zoneline Units Built Prior to 1988) Existing Duct Extension Cross Section Measurements: 8-3/8" height x 6-1/2" width Duct Adapter RAK7012 — This duct adapter will allow the replacement of a new chassis (2800 or 3800 Series unit) into an existing ducted application. This adapter will align properly with the duct extension and will eliminate the need to modify the wall opening. In order to minimize replacement costs, some of the components of the old duct adapter must be removed and used in the new installation. Consult the Installation Instructions of the RAK7012 before removing and discarding the old duct adapter. See additional notes page 58.
Components Duct Adapter RAK6052 — The duct adapter is secured to each side of the wall case and requires the drilling of mounting holes in the wall case during installation. A template for the hole location is in the installation instructions. By securing the duct adapter to the wall case, the chassis retains the slide-out feature for servicing after the transition piece is removed. Duct Extension RAK601 — This kit contains a 44"-long insulated duct, a register mounting collar, and an air supply register. It can be secured to the duct adapter at either end of the adapter. This duct may be cut at any dimension and used in two applications providing the sum of the two duct lengths necessary do not exceed the 44" length. Even in single applications the mounting flange must be cut off
Slope-Front Discharge Units (Models With AZC, AZR, AZW, or AZ21 or AZ31 Prefix) Existing Duct Extension Cross Section Measurements: 7-3/32" height x 6-1/2" width Duct Transition RAK7022 — This duct transition will allow the replacement of a new slope-front discharge Zoneline chassis (2800 or 3800 Series unit) into a previous design slope-front ducted installation. See additional notes page 58.

RECOMMENDED
2" TO SIDE WALL
DUCTED APPLICATION (AZ2800/3800 SERIES)
CLEARANCE
MINIMUM
44" LENGTH
RAK601
installations may be made from one kit if the combined ducted length is less than 44".
duct extension must be insulated to prevent condensation from forming on exterior.
installations where length of duct exceeds length of RAK601 (44"). Field fabricated
RAK602 kit contains mounting collar, discharge grille and mounting hardware
RAK6052
ADAPTER
Duct extension may not contain bends or turns.
may be installed through common wall.
necessary for second installation.


*Caulk around perimeter of wall case all four sides where it joins the building - Interior and Exterior.

Four styles of outdoor grilles are available for exterior treatments. The standard stamped aluminum grille (RAG60), the molded architectural louvered exterior grilles (RAG61-63), the molded architectural louvered exterior grilles with flange (RAG64-66), and the extruded aluminum architectural louvered grille (RAG67). All grilles include air deflectors and gaskets to prevent condenser air recirculation.


RAG67 Extruded Aluminum Grille — The RAG67 is made from extruded anodized aluminum for use where an aluminum architectural grille is preferred. The RAG67 is available in a clear finish and may be special ordered from GE in other colors. Minimum order quantities may be required. Contact your General Electric salesperson for details. All grilles are installed and secured to the wall case from the inside. Keyhole slots in the rear flange of the case allow the grille to be placed in position before securing it firmly to the wall case.
RAG60 Outdoor Grille — The standard exterior grille is made of durable aluminum to protect chassis components and prevent air recirculation.

Replacement of existing units: If an existing grille is not replaced, capacity and efficiency will be reduced and the unit may fail to operate properly or fail prematurely. A deflector kit, RAK40, may be used with grilles that were not designed for current AZ Series GE Zoneline units. The RAK40 contains air deflectors and gaskets that mount to the chassis to direct the hot exhaust air away from the air intake to allow the unit to function properly. All grilles used with GE Zoneline® units must comply with requirements of Exterior Architectural Treatments and Special Outdoor Grilles as follows.
RAG61, 62, 63 Architectural Grille — One-piece optional molded grille and frame assembly provides improved appearance, protection and weatherability. Molded of durable polycarbonate, the surfaces of the grille have a colorfast, slightly textured finish which blends well with most types of wall surfaces. The grilles can be painted in the field to match the building for improved aesthetics.

RAG64, 65, 66 Architectural Grille with Flange — Identical to RAG61-63 grilles with the addition of a 1/2" flange around the top and sides to help conceal the juncture of the RAB71 wall case and the wall opening. The best appearance is achieved with this grille when the wall case extends minimally (between 1/4" and 1/2") beyond the exterior face of the building. Colors: RAG61 and 64 — Beige; RAG62 and 65 — Dark Maple RAG63 and 66 — Bittersweet Chocolate.

Exterior Architectural Treatments and Special Outdoor Grilles
The architectural design of a building may dictate the use of special or oversized louvers for aesthetic reasons. Louvers other than standard Zoneline exterior grilles may be used on the Zoneline unit, however, these special louvers, or any special exterior architectural treatments of the building facade that may restrict the free circulation of condenser airflow, should be referred to GE Application Engineering for evaluation and approval. The following guidelines should be followed in selecting a louver: 1. The louver must have a minimum of 65% free area. ASHRAE defines free area as the minimum area of the opening in an air inlet or outlet through which air can pass. Percent (%) free area equals the X dimension divided by the Y dimension. 2. The louver should be attached to the wall case in a manner that will prevent recirculation of condenser discharge air into the air inlet. If the louver is not attached directly to the wall case, a field supplied splitter or gasket is required between the chassis and the louver to prevent recirculation. It is important that the above criteria be followed since a louver that is too restrictive or allows recirculation will reduce the unit’s capacity and efficiency, increase the electrical current draw, cause intermittent operation due to the compressor overload protector shutting the compressor off, and cause failure of the compressor overload and shorten compressor life. Using the unit with a grille that is too restrictive or allows recirculation may constitute improper installation. A scale drawing of the louver section should be sent to GE Application Engineering. To assure the proper performance of the Zoneline unit and comply with Underwriters Laboratories requirements, it may be necessary to send a sample louver section (at least 16" x 42") to GE to be tested with the Zoneline unit.
Sample Calculations Free Area (%) = x
y x 100 x = 1" y = 1.5"
1.5 x 100 = 66.7%

All 2800, 3800, and 5800 Series Zonelines are equipped with universal heaters allowing chassis installation flexibility. The Zoneline® units are connected to the building power supply by a unique power connection kit. By utilizing a separate universal power connection (UPC) kit, each unit is capable of providing various outputs of electric resistance heat to more closely meet the heating requirements of the particular room, thereby increasing the installation flexibility of the particular chassis. This power connection kit is the only means of supplying power to the Zoneline chassis. The appropriate kit is determined by the voltage, the means of electrical connection, either line cord connected or permanently connected, and the desired resistance heat output that may be supported by the branch circuit.
For 2800 and 3800 Series 230/208-volt units where a permanent installation using flexible conduit is desired, the RAK4002A forms an enclosed junction box on the chassis. The RAK4002A has a 7/8" diameter hole to allow conduit to be connected to the junction box. A line cord kit, shown above under Line-Cord Connected units, must be purchased and modified to allow direct connection to the building wiring. The line cord kit should be cut about 8" from the nine-pin connector. Strip insulation off 5/8" of each conductor to expose wires for field connection. These wires are then connected to the building wiring by field-supplied connectors. For 5800 Series 230/208-volt units, the permanent installation using flexible conduit procedure is the same as for the 2800 and 3800 Series units, except the junction box kit is RAK4002B.
230/208-Volt Line-Cord Connected Units Line Cord Kits consist of a self-aligning nine-pin molded connector that plugs into a mating connector on the Zoneline chassis and insulated line cord with an electrical plug on the end. The configuration of the electrical plug conforms to NEC standards for the circuit amperage and the position of the wires in the nine-pin connector determines the heater wattage and current requirements when it is plugged into the Zoneline chassis. The power connection kit is selected by the amperage of the circuit where it will be installed. Each line cord kit has an integral Leakage Current Detection and Interruption (LCDI) or Arc Fault Current Interrupter (AFCI) device as required by the National Electrical Code (NEC) and Underwriters Laboratory (UL) for line-cord connected air conditioners manufactured on or after August 1, 2004. The line-cord power connection kits are shown in the table below.

RAK204D15P RAK4157 8600/7100 2550/2090 11.6/10.6 15 RAK204D20P RAK4207 11700/9600 3450/2820 15.5/14.1 20 RAK204D30P RAK4307 170100/13900 5000/4090 22.3/20.3 30
Electric Heat Amps include electric heater and fan motor current draw.
265- or 277-Volt Unit Installation — Permanently Connected Units National Electric Code (Article 440 Section G) requires permanent connection for units connected to power sources over 250 volts; therefore these units must be permanently connected (direct wired) with field-supplied connectors. Units connected using a sub-base meet the requirement for permanent connection since all wiring is internal wiring between the sub-base and the chassis. Since 265-volt units may not be line cord connected, an LCDI device is not required.

RAK3153 8600/7100 2550/2090 11.6/10.6 15 RAK3203 11700/9600 3450/2820 15.5/14.1 20 RAK3303 17000/13900 5000/4090 22.3/20.3 30

Electric Heat Amps include electric heater and fan motor current draw.
230/208-Volt — Permanently Connected Units Permanently connected units do not require the LCDI or AFCI device. Permanent connection is usually made through the use of a sub-base. Each 230/208-volt sub-base consists of a sub-base with appropriate receptacle for minimum circuit amperage, a chaseway to route power connector from the sub-base to the chassis, wiring to connect the sub-base to building wiring and a short-line cord with a self-aligning nine-pin connector to connect to chassis and plug into the receptacle in the sub-base. Permanent, or direct wired, installation of a 230/208-volt unit requires a junction box kit, RAK4002A, which attaches to the chassis to form an enclosed junction box. The short sub-base line cord may not be used without the sub-base.
(Amps) RAK204E15 RAK5172 RAK5157 8600 2550 9.6 15 RAK204E20 RAK5202 RAK5207 11700 3450 13.0 20 RAK204E30 RAK5302 RAK5307 17000 5000 18.9 30
Electric Heat Amps include electric heater and fan motor current draw. Each 265-volt sub-base kit consists of a sub-base with appropriate receptacle for minimum circuit amperage, a chaseway to route the power connector from the sub-base to the chassis and wiring to connect the sub-base to the building wiring. The 265-volt power connection kit must be ordered separately.
All wiring must conform to local electrical regulations and codes.

Essential Elements Ordering Overview
230/208-volt line-cord connected units — order line cord kit. 230/208-volt sub-base connected units — order sub-base (includes power connection kit) and junction box for chassis. 265-volt units — order sub-base and power connection kit separately.
Permanent Connected Units With Sub-Base If the existing unit is connected to a sub-base the installation of the new unit may involve modifying the existing installation slightly. It is recommended these modifications be made by a qualified electrician. If the existing sub-base is the full width of the wall case, RAK201 sub-base access plate may be ordered and used to replace the cover on the old sub-base. Field-supplied wiring, conduit and conduit connectors should be used to make a connection between the new chassis and the center knockout of the RAK201. The wiring connections should be made inside the sub-base and the RAK201 attached to the sub-base with the two screws provided. If the existing sub-base is not the full width of the wall case, the electrician will have to modify the existing cover plate to allow field-supplied wiring, conduit and conduit connectors to be run from the permanent connection kit to the sub-base.
All Zonelines are single-phase 60 hertz units. For all installations, the feeder, sub-feeder, branch circuit and electrical protective devices and selection must conform to the National Electrical Code and to local codes. Maximum connected load in amperes, including demands for the electric heater and the fan motor, are shown on page 44. Branch circuit ampacity and electrical protective device sizing are shown on page 42 for 230/208-volt units and on this page for 265-volt units. More than one unit per branch circuit is not recommended. When in doubt, consult the National Electrical Code. All wiring, including installation of receptacle, must conform to local electrical regulations and codes.

230/208-Volt and 265-Volt Units There have been changes to NEC and improvements and modifications to the Zoneline chassis and sub-bases since the unit was first introduced. Some of these changes require alterations to be made when replacing an older unit with a new chassis.
Line-Cord Connected Units The plug configuration of new line cord connected units complies with the current NEC standards. Older installations may have wall receptacles that conformed to NEC standards at the time the building was constructed and may not match the configuration of the plug on the new line cord. The recommended solution is to change the wall receptacle to conform to current standard plug configuration. See chart on this page for current receptacle configuration.
Enclosure cover removed.
RAK4002A Wiring harness can be ordered separately as RAK4002CW.
Type Mfg Part No Configuration
15 AMP Tandem NEMA6-15R

P&S
NEMA6-20R
30 AMP Large Tandem
Maximum Cord Extension
P&S

The maximum connected load of a Zoneline® unit occurs when the unit is in resistance heating operation. The maximum amperage shown in the tables below is the combined total of the resistance heater and the indoor fan motor.
RAK3303 RAK4307 RAK204D30P MODEL NUMBER 230 V 208 V 230 V 208 V 230 V 208 V
AZ28E07DA* 11.5 10.5 15.5 14.1 N/A N/A AZ28E09DA* 11.5 10.5 15.5 14.1 22.3 20.3 AZ28E12DA* 11.6 10.6 15.5 14.1 22.3 20.3 AZ28E15DA* 11.6 10.6 15.6 14.2 22.4 20.4 AZ38H07DA* 11.5 10.5 15.5 14.1 N/A N/A AZ38H09DA* 11.5 10.5 15.5 14.1 22.3 20.3 AZ38H12DA* 11.6 10.6 15.5 14.1 22.3 20.3 AZ38H15DA* 11.6 10.6 15.6 14.2 22.4 20.4 AZ58H07DA* 11.5 10.5 15.5 14.1 N/A N/A AZ58H09DA* 11.5 10.5 15.5 14.1 22.3 20.3 AZ58H12DA* 11.6 10.6 15.5 14.1 22.3 20.3 AZ58H15DA* 11.6 10.6 15.6 14.2 22.4 20.4
*All versions Electric Heat Amps include electric heater and fan motor current draw. Values shown in table above are also the total connected loads for units installed with sub-bases. RAK204D15P — same as RAK3153 RAK204D20P — same as RAK3203 RAK204D30P — same as RAK3303 265-Volt Units

RAK5302 RAK5307 MODEL NUMBER 265 V 265 V 265 V
AZ28E07EA 10.2 13.7 N/A AZ28E09EA* 10.2 13.7 19.6 AZ28E12EA* 10.3 13.7 19.6 AZ28E15EA* 10.3 13.7 19.6 AZ38H07EA* 10.2 13.7 N/A AZ38H09EA* 10.2 13.7 19.6 AZ38H12EA* 10.3 13.7 19.6 AZ38H15EA* 10.3 13.7 19.6 AZ58H07EA* 10.2 13.7 N/A AZ58H09EA* 10.2 13.7 19.6 AZ58H12EA* 10.3 13.7 19.6 AZ58H15DA* 10.3 13.7 19.6
*All versions Electric Heat Amps include electric heater and fan motor current draw.
Power Connector Kit · RAK3153 rak4157 rak204d15p

BTUH at 80º F D.B. - 67º F W.B.
Zoneline 2800 & 3800 Series Zoneline 2800 Dry Air 25 Zoneline 5800 Series Nominal Capacity Nominal Capacity Nominal Capacity Temperature of Air Entering Condenser 7000 9000 12000 15000 7000 9000 12000 7000 9000 12000 15000
75 7750 9950 12950 15850 7400 9500 12250 7750 9950 12950 15850 82 7500 9700 12600 15500 7200 9200 11900 7500 9700 12600 15500 85 7400 9500 12350 15300 6950 9050 11750 7400 9500 12350 15300 95 7100 9000 11700 14600 6800 8600 11200 7100 9000 11700 14600 105 6700 8400 11000 13600 6400 8100 10600 6700 8400 11000 13600 115 6300 7800 10400 12300 6000 7650 10000 6300 7800 10400 12300
BTUH at 70º F Indoor Temperature

Zoneline 3800 Series Outdoor Temperature F 7000 9000 12000 15000
65 7500 3.85 10000 3.85 12950 3.65 15950 3.45 60 7200 3.80 9600 3.80 12500 3.60 15300 3.40 55 6900 3.75 9100 3.75 11850 3.55 14650 3.35 50 6600 3.65 8700 3.65 11300 3.45 13850 3.25 47 6400 3.60 8400 3.60 10900 3.40 13400 3.20 45 6250 3.55 8200 3.55 10600 3.35 13050 3.15 40 5950 3.45 7700 3.45 9800 3.20 12250 3.05 35 5600 3.35 7100 3.35 9200 3.10 11300 2.95 30 5250 3.20 6500 3.20 8300 3.00 10300 2.85 25 4700 3.05 5900 3.05 7500 2.85 9250 2.75 All data at 230 volts and 265 volts.

Zoneline 5800 Series Outdoor Temperature F 7000 9000 12000 15000
65 7500 3.85 10000 3.85 12950 3.65 15950 3.45 60 7200 3.80 9600 3.80 12500 3.60 15300 3.40 55 6900 3.75 9100 3.75 11850 3.55 14650 3.35 50 6600 3.65 8700 3.65 11300 3.45 13850 3.25 47 6400 3.60 8400 3.60 10900 3.40 13400 3.20 45 6250 3.55 8200 3.55 10600 3.35 13050 3.15 40 5950 3.45 7700 3.45 9800 3.20 12250 3.05 35 5600 3.35 7100 3.35 9200 3.10 11300 2.95 30 5250 3.20 6500 3.20 8300 3.00 10300 2.85 25 4700 3.05 5900 3.05 7500 2.85 9250 2.75 All data at 230 volts and 265 volts.

The total capacity of an air conditioner is made up of the Sensible capacity, the output of the unit used to remove heat from the air in the area being conditioned, and the Latent capacity, the output of the unit used to dehumidify the air in the area being conditioned. For humid climates and applications, the Sensible/Latent capacity split of the unit should be considered. The Sensible capacity listed in the specification charts on page 55 is at a standard rating condition of 95°F dry bulb/75°F wet bulb outdoors; 80°F dry bulb/67°F wet bulb indoors. The Latent system capacity is
1.00 minus the Sensible capacity. (If the Sensible capacity is listed at .74 the Latent capacity is .26. This means that 74% of the capacity of the unit is used to remove heat from the air and 26% is used to remove moisture form the air at standard test conditions.) In some applications information about the Sensible/Latent split, or ratio, at conditions other than the standard rating conditions is needed. The chart below provides data at various indoor conditions.
Indoor Ambient DB Temperature (F) 60 65 70 75 80 85 90 95 100 All 7000 BTUH 59 0.51 0.67 0.83 0.99 1.00 units except 63 0.46 0.62 0.77 0.92 1.00 Dry Air 25 67 0.42 0.60 0.75 0.88 1.00 1.00 1.00 71 0.42 0.54 0.66 0.78 0.90 1.00 AZ28E07DAP/EAP 59 0.38 0.49 0.65 0.80 0.95 1.00 (Dry Air 25) 63 0.38 0.54 0.68 0.80 1.00 67 0.35 0.52 0.66 0.79 0.92 1.00 1.00 71 0.32 0.45 0.58 0.73 0.85 1.00 All 9000 BTUH 59 0.42 0.59 0.77 0.93 1.00 units except 63 0.40 0.55 0.70 0.83 0.96 1.00 1.00 1.00 Dry Air 25 67 0.42 0.55 0.68 0.81 0.93 1.00 1.00 71 0.38 0.49 0.60 0.71 0.82 0.93 AZ28E09DAP/EAP 59 0.30 0.45 0.60 0.75 0.92 1.00 (Dry Air 25) 63 0.32 0.42 0.57 0.73 0.90 1.00 1.00 1.00 67 0.32 0.45 0.58 0.70 0.85 1.00 1.00 71 0.30 0.38 0.48 0.61 0.74 0.85 All 12000 BTUH 59 0.38 0.54 0.71 0.88 1.00 units except 63 0.40 0.54 0.68 0.81 0.93 1.00 1.00 1.00 Dry Air 25 67 0.41 0.54 0.67 0.80 0.93 1.00 1.00 71 0.36 0.47 0.58 0.71 0.82 0.93 AZ28E12DAP/EAP 59 0.30 0.45 0.60 0.75 0.92 1.00 (Dry Air 25) 63 0.30 0.41 0.56 0.72 0.89 1.00 1.00 1.00 67 0.31 0.44 0.57 0.70 0.84 0.99 1.00 71 0.31 0.40 0.50 0.61 0.73 0.84 All 15000 BTUH 59 0.38 0.54 0.71 0.88 1.00 units except 63 0.40 0.54 0.68 0.81 93.00 1.00 1.00 1.00 Dry Air 25 67 0.41 0.54 0.67 0.80 0.93 1.00 1.00 71 0.36 0.47 0.58 0.71 0.82 0.93 Capacities are nominal capacity
MODEL Indoor WB

Normal Yearly Operating Data
(Cooling Hours based on 75°F indoor temperature with air conditioner sized to meet the design conditions.)
ASHRAE Heating Estimated Degree Cooling Location Days Hours
ASHRAE Heating Estimated Degree Cooling Location Days Hours
ASHRAE Heating Estimated Degree Cooling Location Days Hours
ALABAMA Birmingham 2,551 1,390 Huntsville 3,070 1,340 Mobile 1,560 1,640 Montgomery 2,291 1,580 ARIZONA Flagstaff 7,152 310 Phoenix 1,765 2,280 Tucson 1,800 1,920 Yuma 974 2,520 ARKANSAS Fort Smith 3,292 1,410 Little Rock 3,219 1,330 CALIFORNIA Bakersfield 2,122 1,530 Fresno 2,611 1,210 Los Angeles 2,061 310 Sacramento 2,502 1,030 San Diego 1,458 390 San Francisco 3,015 110 COLORADO Colorado Springs 6,423 520 Denver 6,283 550 Grand Junction 5,641 910 CONNECTICUT Hartford 6,235 480 DISTRICT of COLUMBIA Washington 4,224 1,010 DELAWARE Wilmington 4,930 770 FLORIDA Jacksonville 1,239 1,690 Miami 214 2,850 Orlando 766 1,930 Tallahassee 1,485 1,500 Tampa 683 2,350 GEORGIA Atlanta 2,961 1,130 Augusta 2,397 1,400 Macon 2,136 1,440 Savannah 1,819 1,510 IDAHO Boise 5,809 670 Lewiston 5,542 600 Pocatello 7,033 570 ILLINOIS Chicago 6,155 780 Moline 6,408 760 Springfield 5,429 890 INDIANA Evansville 4,435 1,090 Fort Wayne 6,205 710 Indianapolis 5,699 820 South Bend 6,439 600 IOWA Burlington 6,114 730 Des Moines 6,588 710 Sioux City 6,951 770 KANSAS Dodge City 4,986 1,020 Goodland 6,141 800 Topeka 5,182 880 Wichita 4,620 1,070
KENTUCKY Lexington 4,683 830 Louisville 4,660 1,130 LOUISIANA Alexandria 1,921 1,670 Baton Rouge 1,560 1,860 New Orleans 1,385 1,790 Shreveport 2,184 1,470 MAINE Portland 7,511 290 MARYLAND Baltimore 4,654 850 MASSACHUSETTS Boston 5,634 500 MICHIGAN Detroit 6,293 590 Flint 7,377 440 Grand Rapids 6,894 530 MINNESOTA Duluth 10,000 200 Minneapolis 8,382 550 MISSISSIPPI Jackson 2,239 1,560 MISSOURI Columbia 5,046 960 Kansas City 4,711 1,210 Springfield 4,900 970 St. Louis 4,900 1,080 MONTANA Billings 7,049 520 Glasgow 8,996 410 Great Falls 7,750 420 Missoula 8,125 350 NEBRASKA Grand Island 6,530 770 Omaha 6,612 750 NEVADA Ely 7,733 500 Las Vegas 2,709 1,980 Reno 6,332 520 NEW JERSEY Newark 4,589 710 NEW MEXICO Albuquerque 4,348 1,040 Clayton 5,158 720 Silver City 3,705 1,260 NEW YORK Albany 6,875 480 Binghamton 7,286 310 Buffalo 7,062 450 New York 4,811 790 Rochester 6,748 470 Syracuse 6,756 500 NORTH CAROLINA Asheville 4,042 690 Charlotte 3,191 1,230 Raleigh 3,393 1,070 Winston-Salem 3,595 960 NORTH DAKOTA Bismarck 8,851 510 Fargo 9,226 490 Williston 9,243 580
OHIO Cincinnati 5,265 840 Cleveland 6,351 610 Columbus 5,660 810 Dayton 5,622 740 Toledo 6,494 590 OKLAHOMA Oklahoma City 3,725 1,200 Tulsa 3,860 1,410 OREGON Medford 5,008 620 Pendleton 5,127 590 Portland 4,635 270 PENNSYLVANIA Harrisburg 5,251 730 Philadelphia 5,144 810 Pittsburgh 5,987 590 Scranton 6,254 440 Williamsport 5,934 600 RHODE ISLAND Providence 5,954 470 SOUTH CAROLINA Charleston 2,033 1,390 Columbia 2,484 1,440 Greenville 2,980 1,120 SOUTH DAKOTA Rapid City 7,345 580 Sioux Falls 7,839 610 TENNESSEE Chattanooga 3,254 1,180 Knoxville 3,494 1,070 Memphis 3,232 1,320 Nashville 3,578 1,220 TEXAS Corpus Christi 914 2,380 Dallas 2,363 1,900 El Paso 2,700 1,580 Houston 1,396 1,850 Lubbock 3,578 1,310 San Antonio 1,546 1,920 UTAH Milford 6,497 910 Salt Lake City 6,052 830 VERMONT Burlington 8,269 130 VIRGINIA Norfolk 3,421 1,010 Richmond 3,865 1,020 Roanoke 4,150 870 WASHINGTON Seattle 5,145 180 Spokane 6,655 430 Yakima 5,941 530 WEST VIRGINIA Charleston 4,476 860 Huntington 4,446 820 WISCONSIN Madison 7,863 530 Milwaukee 7,635 450 WYOMING Casper 7,410 600 Cheyenne 7,381 420 Sheridan 7,680 530
Heating* — Heat Loss KW x Heating Degree Days x “C” x Cost Per KWH = Operating Cost Outdoor Design Temperature Difference
*The above formula is for electric resistance heating only. Power consumption using the Zoneline Heat Pumps should be adjusted by Seasonal Performance Factor (SPF).
The local power supplier should be consulted for recommended value of “C.” This factor will vary between 17 and 24.
Cooling — Calculated Heat Gain (BTUH) x = Unit Cooling Watts x Cooling Hours x Cost per KWH = Operating Cost Installed unit capacity (BTUH) 1000 Watts/KW






BL : BLUE BR : BROWN GR : GREEN GY : GRAY OR : ORANGE RD : RED WH : WHITE
1 2 3 4 5 6 7 8 9 10


Suggested Bid Form Specifications

Additional specifications for GE Zoneline® 3800 or 5800 Series Packaged Terminal Heat Pump Heat pump units shall provide operation that will either: A) automatically phase-in partial electric resistance heat, if outdoor temperature is below 46°F, simultaneously with heat pump if heat pump alone is unable to maintain room temperature; or B) use partial electric resistance heat simultaneous with heat pump operation any time the outdoor temperature is below 45°F. Selection of A or B operation is made by means of a selector switch concealed from room occupant. In either A or B operation, the unit will switch to full resistance heat if room temperature continues to decline or the outdoor temperature falls below 25°F. If the outdoor temperature is above 46°F, unit will lock-out electric resistance heat and operate on heat pump only. Heat pump unit shall include Reverse Cycle Defrost that automatically begins a defrost cycle when microprocessor determines criteria for defrosting has been met. Defrosting shall be accomplished by systematically ceasing heat pump operation, pausing to allow internal refrigerant pressures to equalize, then operating the compressor with the flow of refrigerant reversed to allow the hot gas to flow through the outdoor coil melting the accumulated frost. The unit shall automatically resume heat pump operation, after pausing to allow refrigerant pressures to equalize, at conclusion of defrost cycle. The unit shall be equipped with a temperature-activated drain valve to allow water generated in heat pump operation and defrost cycles to drain into the wall case rather than being deposited on the outdoor coil. In the event of compressor failure during heat pump operation, The unit shall automatically switch to electric resistance heat to maintain selected room temperature regardless of outdoor temperatures. The unit shall have a switch concealed from room occupant to allow heat pump operation to be overridden and heat provided by electric resistance heat regardless of outdoor temperature. In the event of compressor failure during heat pump operation, unit shall automatically switch to electric resistance heat to maintain selected room temperature regardless of outdoor temperatures. Specifications for Optional Internal Condensate Removal (ICR) system for 3800 or 5800 series heat pump units. The unit shall have a factory-installed Internal Condensate Removal (ICR) system to permit unit to automatically dispose of heat pump generated condensate water with no overflow to outdoors during heating under outdoor ambient of 55°F Dry Bulb, 90% Relative Humidity; indoor ambient 70°F Dry Bulb, 52% Relative Humidity, for four hours of continuous run time.
(Wall Cases and Grilles are needed for new installations.) (Alternate specification for steel wall case.) Wall Case. The wall case shall be constructed of heavy-gauge, insulated, zinc-coated phosphated steel with a protective baked-on enamel finish. Bottom critical points of the steel wall case shall be coated with petroleum microcrystalline wax for added corrosion protection and shall meet ASTM B-117, 1800-hour hot air aerated salt spray test. (Alternate specification for molded wall case.) Wall Case. The wall case shall be constructed of a non-corroding fiberglass-reinforced polyester compound. Cases shall be installed through exterior walls where shown on the plans and shall be installed per manufacturer’s installation instructions. In no instance shall fasteners be used through the bottom in order to retain the water integrity of the bottom of the wall case. Outside weather panels shipped with the cases shall remain in place until the outdoor air louvers and chassis are installed, at which time they are to be removed and discarded by the installer. Outside Grille. Each unit shall be equipped with a standard exterior grille that has been designed to allow unit operation in high ambient conditions. Grilles shall be of material and design specified. Special grilles or customer louver sections to be supplied by others will conform to a minimum of 65% free area to allow for proper unit operation and shall be submitted to the PTAC/ PTHP manufacturer, if requested, for feasibility and airflow characteristics. Specifications for Sub-Base (if required) Sub-Base. Each unit shall have a field-installed UL-listed electrical sub-base. The sub-base shall be attached to the lower inside flange of the wall case prior to installation in the exterior wall. It shall include adjustable screws at the bottom corners to permit exact leveling of the wall case. The sub-base shall have a factory-installed receptacle to allow unit line cord to plug into mating receptacle and shall have a chaseway to contain and conceal the line cord. The sub-base shall have side panels adjustable from a minimum of 2-3/8" to a maximum of 13-3/4" to enclose the area under the wall case.

Weather Resistance. Complete unit including outside louver shall be submitted to an independent agency for weather resistance and water infiltration tests. Air infiltration test to be conducted in accordance with ASTM E283-91. With static air pressure differential of 1.57 lb./ft.2 (.3" H2O) equivalent to 25 mph wind, allowable air infiltration shall not exceed 7 ft.3/min. Water infiltration test to be conducted in accordance with ASTM E331-86 with static air pressure differential of 10.0 lb./ft2 (1.93" H2O) equivalent to 63 mph wind, 5.0 gal./ft.2 (8" rain/ft.2/hr.) for 15 minutes and there shall be no leakage into the room. Approvals. Units shall be certified under the ARI and cUL certification program and listed by UL. Service. Submit complete information with bid covering service availability to whom service on units will be assigned, along with complete address and phone number, including phone number of emergency service personnel. Start-Up, Adjust, Demonstrate. Contractor shall be responsible for the initial starting of units, adjustments thereto, etc., to place the units in required operating condition. Contractor shall demonstrate to the owner or his representative the operation of units for both summer and winter functions. Warranty. The warranty shall be a full one-year parts and labor on the entire unit, plus an additional full four years parts and labor for the sealed refrigerating system, including service call for diagnosis and transportation to and from service shop (if necessary) at no charge to the customer. The warranty shall also include a limited second through fifth year parts only warranty for fan motors, switches, thermostat, heater, heater protectors, compressor overload, solenoids, circuit boards, auxiliary controls, thermistors, frost controls, ICR pump, capacitors, varistors and indoor blower bearing. Installation Responsibility. Units shall be installed according to the manufacturer’s recommendations and the manufacturer shall not be responsible for unit failure as a result of improper installation, or unit performance when installed with accessories not approved by the manufacturer.

The Zoneline chassis is identified by a model number defining the type of unit, cooling capacity, electrical information and optional features included on the unit. When specifying or ordering the Zoneline chassis use of this nomenclature will assure receiving the correct unit.

Chassis series 28=deluxe line cool/ electric heat 38=deluxe line heat pump 58=premium line heat pump
Nominal cooling capacity 07=7,000 BTUH cooling 09=9,000 BTUH cooling 12=12,000 BTUH cooling 15=15,000 BTUH cooling Special Features B=base unit C=corrosion treated D=internal
condensate removal (ICR) system (heat pump models only) (not for coastal areas) P=Dry Air 25

230/208-Volt sub-bases include appropriate power cord kit. 265-Volt units are to be direct connected. Cordset through enclosed chaseway into interior sub-base receptacle meets the NEC requirements.
Power connection kits are required on all Zoneline chassis (see chart below).
Power connection kits required on all models. See specification sheet for heater KW and branch circuit ampacity.

The correct kit for the installation is determined by the voltage and amperage of the electrical circuit and the means of connecting the unit to the building wiring. If the unit is to be plugged into a receptacle, a line cord kit would be used; if the unit is to be permanently connected, a permanent connection kit would be used. 265-volt cord set units must be installed in compliance with National Electrical Code.
RAK3153 and RAK3203 230/208-volt line cord connection kit
RAK3303 230/208-volt line cord connection kit


15-amp 20-amp 30-amp time-delay time-delay time-delay fuse or breaker fuse or breaker fuse or breaker
15-amp 20-amp 30-amp time-delay fuse time-delay fuse time-delay fuse
*To be used with sub-base

Deluxe series – cooling & electric heat Dry Air 25
2800 series units Dry Air 25 230/208V Models AZ28E07D AZ28E09D AZ28E12D AZ28E15D AZ28E07DAP AZ28E09DAP AZ28E12DAP Capacity Cooling BTUH 7,100/6,900 9,300/8,900 11,800/11,500 14,600/14,300 6,800/6,600 8,600/8,400 11,200/11,000 EER (BTU/Watt) 12.7/12.7 12.0/12.0 11.5/11.5 10.2/10.2 12.1/12.1 11.5/11.5 11.0/11.0 Dehumidification Pts/Hr 1.7 2.7 3.6 4.5 2.2 3.4 4.5 Sensible heat ratio @ 230 volts 75% 68% 67% 67% 66% 58% 57% CFM, indoor fan high 250 275 300 310 210 230 240 CFM, indoor fan low 215 235 240 260 175 200 210 Vent CFM (full open/partial open) 50/40 70/45 75/45 75/45 50/40 70/45 75/45 Power/Ratings Power factor 86/87 86/86 91/91 89/90 87/87 86/86 91/91 Watts 560/545 750/735 1020 1430/1400 560/545 750/730 1020 Amperes, F.L. 2.8/3.0 3.8/4.1 4.9/5.3 7.0/7.5 2.8/3.0 3.6/3.9 4.9/5.3 Amperes, L.R. 19.0 21.0 31.0 38.0 19.0 21.0 31.0 Weight (Net/Ship) 100/115 101/116 105/120 115/130 100/115 101/116 105/120 Sound Transmission Class (STC) 29
265V Models AZ28E07E AZ28E09E AZ28E12E AZ28E15E AZ28E07EAP AZ28E09EAP AZ28E12EAP Capacity Cooling BTUH 7,100 9,000 11,700 14,600 6,800 8,600 11,200 EER (BTU/Watt) 12.7 12.0 11.5 10.2 12.1 11.5 11.0 Dehumidification Pts/Hr 1.7 2.7 3.6 4.5 2.2 3.4 4.5 Sensible heat ratio @ 265 volts 75% 68% 67% 67% 66% 58% 57% CFM, indoor fan high 250 270 290 310 210 235 240 CFM, indoor fan low 215 235 240 260 175 200 210 Vent CFM (full open/partial open) 50/40 70/45 75/45 75/45 50/40 70/45 75/45 Power/Ratings Power factor 87 86 87 90 88 86 87 Watts 560/545 750 1020 1431 560 750 1020 Amperes, F.L. 2.4/3.0 3.3 4.4 6.0 2.4 3.3 4.4 Amperes, L.R. 16.0 18.0 24.0 31.0 16.0 18.0 24.0 Weight (Net/Ship) 100/115 101/116 105/120 115/130 100/115 101/116 105/120 Sound Transmission Class (STC) 29
Deluxe series – heat pump units Premium series – heat pump units
3800 series units 5800 series units 230/208V Models AZ38H07D AZ38H09D AZ38H12D AZ38H15D AZ58H07D AZ58H09D AZ58H12D AZ58H15D Capacity Cooling BTUH 7,100/6,900 9,000/8,800 11,700/11,500 14,600/14,300 7,100/7,000 9,000/8,800 11,800/11,600 14,700/14,400 EER (BTU/Watt) 12.7/12.7 12.0/12.0 11.5/11.5 10.0/10.0 13.0/13.0 12.0/12.0 11.5/11.5 10.2/10.2 Dehumidification Pts/Hr 1.7 2.7 3.6 4.5 1.7 2.8 3.6 4.8 Sensible heat ratio @ 230 volts 75% 68% 67% 67% 75% 67% 68% 65% CFM, indoor fan high 250 270 300 310 240 290 330 350 CFM, indoor fan low 215 2350 260 260 220 270 310 330 Vent CFM (full open/partial open) 50/40 70/45 75/45 75/45 50/40 70/45 75/45 75/45 Power/Ratings Power factor 86/87 96 97 94 95 96 94 95 Watts 560/545 750/735 1020/1000 1460/1430 560/540 760/735 1010/990 1425/1400 Amperes, F.L. 2.8/3.0 3.8/4.1 4.9/5.3 7.0/7.5 2.7/2.8 3.6/3.8 4.6/5.0 6.5/7.0 Amperes, L.R. 19.0 21.0 31.0 38.0 19.0 21.0 33.0 38.0 Reverse cycle heat BTUH 6400/6200 8400/8200 10900/10700 13400/13200 6,400/6,200 8,400/8,200 10,900/10,700 13,800/13,800 COP 3.6 3.6 3.4 3.2 3.7/3.7 3.6/3.6 3.4/3.4 3.2/3.2 Watts 520/505 685/670 940/925 1230/1210 505/490 685/670 940/920 1,265/1,235 Amps 2.4/2.6 3.2/3.5 4.3/4.7 5.8/6.3 2.4/2.5 3.2/3.4 4.3/4.7 5.7/6.2 Weight (Net/Ship) 102/117 109/124 113/128 13/138 108/122 113/128 118/133 127/142 Sound Transmission Class (STC) 29
265V Models AZ38H07E AZ38H09E AZ38H12E AZ38H15E AZ58H07E AZ58H09E AZ58H12E AZ58H15E Capacity Cooling BTUH 7,100 9,000 11,700 14,600 7,100 9,000 11,800 14,700 EER (BTU/Watt) 12.7 12.0 11.5 10.0 13.0 12.0 11.5 10.2 Dehumidification Pts/Hr 1.7 2.7 3.6 4.5 1.7 2.8 3.6 4.8 Sensible heat ratio @ 265 volts 75% 68% 67% 67% 75% 67% 68% 65% CFM, indoor fan high 250 270 300 310 240 290 330 350 CFM, indoor fan low 215 235 260 260 220 270 310 330 Vent CFM (full open/partial open) 50/40 70/45 75/45 75/45 50/40 70/45 75/45 75/45 Power/Ratings Power factor 96 94 94 96 96 94 94 96 Watts 560 750 1020 1460 570 760 1010 1425 Amperes, F.L. 2.4 3.2 4.4 6.0 2.2 3.2 4.4 5.8 Amperes, L.R. 16.0 18.0 24.0 31.0 16.0 18.0 24.0 31.0 Reverse cycle heat BTUH 6,400 8,400 10,900 13,400 6,400 8,400 10,900 13,800 COP 3.6 3.6 3.4 3.2 3.7 3.6 3.4 3.2 Watts 520 685 940 1230 505 685 940 1,265 Amps 2.2 2.8 3.9 5.0 2.2 2.7 3.9 5.0 Weight (Net/Ship)* 102/117 109/124 113/128 123/138 108/122 113/128 118/133 127/142 Sound Transmission Class (STC) 29
*ICR adds 3 pounds to unit weight

Kit Number Description For Additional Information Refer to Page
RAA63 Spare Filters for AZ2800, AZ3800 and AZ5800 Series units (10 pairs per box) 11
RAB71A Steel Wall Case – 13 3/4" deep 22
RAB7116 Steel Wall Case – 16" deep 22
RAB7124 Steel Wall Case – 24" deep 22
RAB7128 Steel Wall Case – 28" deep 22
RAB7131 Steel Wall Case – 31" deep 22
RAB77 Molded Wall Case 22
RAD10 Interior/Exterior Drain kit 35
RAF453 Room Front for AZ2800, AZ3800 and AZ5800 Series units (included with chassis) 11
RAG60 Stamped Aluminum Exterior Grille 40
RAG61 Architectural Exterior Grille, Beige Molded High-Impact Plastic 40
RAG62 Architectural Exterior Grille, Maple Molded High-Impact Plastic 40
RAG63 Architectural Exterior Grille, Bittersweet Chocolate Molded High-Impact Plastic 40
RAG64 Architectural Exterior Grille w/Flange, Beige Molded High-Impact Plastic 40
RAG65 Architectural Exterior Grille w/Flange, Maple Molded High-Impact Plastic 40
RAG66 Architectural Exterior Grille w/Flange, Bittersweet Chocolate Molded High-Impact Plastic 40
RAG67 Aluminum Architectural Grille (Custom Colors Available by Special Order) 40
RAK40 Condenser Air Deflector Kit 40
RAK147 Wall Thermostat For Heat Pump Models – Mechanical 16
RAK148D1 Wall Thermostat For Heat Pump Models - Electronic Digital 16
RAK148P1 Wall Thermostat For Heat Pump Models – Electronic Digital Programmable 16
RAK163A1 Wall Thermostat For Resistance Heat Models – Mechanical 15
RAK164D1 Wall Thermostat For Resistance Heat Models – Electronic Digital 15
RAK164P1 Wall Thermostat For Resistance Heat Models – Electronic Digital Programmable 15
RAK201 Sub-Base Cover Plate with Knockouts 43
RAK204D15P Sub-Base - 208/230-Volt with NEMA 6-20R 15/20 Amp Receptacle – power cord and Chaseway included 22
RAK204D20P Sub-Base - 208/230-Volt with NEMA 6-20R 15/20 Amp Receptacle – power cord and Chaseway included 22
RAK204D30P Sub-Base - 208/230-Volt with NEMA 6-30R 30 Amp Receptacle –power cord and Chaseway included 23
RAK204E15 Sub-Base – 265-Volt with NEMA 7-15R 15 Amp Receptacle – Chaseway included 23
RAK204E20 Sub-Base – 265-Volt with NEMA 7-20R 20 Amp Receptacle – Chaseway included 23
RAK204E30 Sub-Base – 265-Volt with NEMA 7-30R 30 Amp Receptacle – Chaseway included 23
RAK204U Sub-Base – non-electrical Chaseway not included 22
RAK205CW Chaseway for Sub-Base 22
RAK3153 Universal Power Cord – 2800/3800/5800 series – 15-Amp 230/208 V – 2.55/2.09 kW heat 42
RAK3203 Universal Power Cord – 2800/3800/5800 – 20-Amp 230/208 V – 3.45/2.82 kW heat 42
RAK3303 Universal Power Cord – 2800/3800/5800 – 30-Amp 230/208 V – 5.0/4.09 kW heat 42
RAK4002A Direct Connect Junction Box – 230/208-volt units 2800/3800 Series 42
RAK4002B Direct Connect Junction Box – 230/208-volt units 5800 Series 42
RAK4002CW Wiring Harness w/ Inline Connector - Adapt Line Cord to Direct Connection 43
RAK4157 208/230V Universal Power Supply, 15 Amp for 2800, 3800, 5500, 5800, 7500 only 42
RAK4207 208/230V Universal Power Supply, 20 Amp for 2800, 3800, 5500, 5800, 7500 only 42
RAK4307 208/230V Universal Power Supply, 30 Amp for 2800, 3800, 5500, 5800, 7500 only 42
RAK5157 265/275V Universal Power Supply, 15 Amp for 2800, 3800, 5500, 5800, 7500 only 42
RAK5207 265/275V Universal Power Supply, 20 Amp for 2800, 3800, 5500, 5800, 7500 only 42
RAK5307 265/275V Universal Power Supply, 30 Amp for 2800, 3800, 5800, 7500 only 42
RAK5172 Universal Connection Kit – 265V – 15 Amp – Use w/ RAK204E15 Sub-Base – 2.55 kW heat 42
RAK5202 Universal Connection Kit – 265V – 20 Amp – Use w/ RAK204E20 Sub-Base – 3.45 kW heat 42
RAK5302 Universal Connection Kit – 265V – 30 Amp – Use w/ RAK204E30 Sub-Base – 5.0 kW heat 42
RAK601 Duct extension – Insulated – 44" long – includes Register and Mounting Flange 37
RAK602 Register and Trim Flange (Included with RAK601) 37
RAK6052 Duct Adapter for New Installation (or older non-GE Duct Adapter Installation) 37
RAK7012 Duct Transition for 2800/3800 Replacing Existing Chassis (Original Installation Pre-1988) 37
RAK7022 Duct Transition for 2800/3800 Replacing Existing Chassis (1988–1998 Original Installation) 37
RAK8023 Locking Door Kit 11
RAK806 Control Panel Cover (for use with remote thermostat) 15
RAK901L Wall Case Insulation Kit 22

Many times poor or non-existent caulking around the exterior of the wall case results in air infiltration causing the unit to run excessively. One way to check for air infiltration is to look under and around the unit to the outdoors. If you can see light, there is air infiltration. The first floor of a building is where this problem most frequently occurs since caulking the bottom of the wall case may require lying outside in the dirt while working. This has been the cause of many complaints about the “short cycling” of the Freeze Sentinel™. Curtains, furniture or other obstructions interfering with the discharge air circulation will make the unit cycle turn off too soon since the cooled (or heated) discharge air is pulled back into the unit. This results in a room that is not adequately heated or cooled. Blocking the discharge air on the left side during heating operation can result in the air getting hot enough to distort the plastic room front. If you have a property where this may occur we recommend a “tent card” advising room occupants not to put anything on the unit.
visible to someone standing or sitting in the room. Do not run the low-voltage wiring in conduits with line-voltage wiring or near uninsulated line-voltage wiring since induced current can interrupt the low-voltage controls. Consult the electrical inspector early in the project, especially if the power to the air conditioner is to be 265 volts, to understand what is required to comply with local electrical codes.
Wall Case/Exterior Grille When making an installation where the exterior grille is flush with the exterior wall, or part of a custom window/louver section, make sure the installer caulks the wall case to the exterior wall, especially the bottom of the case. Many times the air conditioners are run during construction and the building is not closed. This can result in excessive humidity from the warm humid air entering the building, or from the “drying out” of the building materials. Many problems have been caused by condensate water or rainwater running back into the building where proper caulking has not been done.
Capacity Considerations A unit that has a greater cooling capacity than required will cool the room quickly but will usually not run long enough under normal operation to adequately dehumidify the room. Most musty odors in rooms are due to excess humidity. Using a smaller capacity unit or using Dry Air 25 units will provide better dehumidification. The largest factor in causing mold and mildew in the room is excess moisture, and a smaller unit running longer or a Dry Air 25 model can remove more moisture. Mold behind wall coverings that do not allow water vapor to pass through — vinyl wallpaper or oil-base paints, for example — is not a problem of excessive moisture in the room, but rather is caused by moisture trapped in the walls. Using a resistance heater larger than required — using a 5 kW heater when a 3.45 kW heater would suffice for example — may not cost any more in electrical consumption since the larger heater will operate for less time. The “Demand Charge” portion of the utility bill — which is based on the highest electrical load for a period of time — may be a significant portion of the utility bill. Some customers have reported the “Demand Charge” actually being more than the usage charge. In a 100-room property it would be possible for the demand of the 5.0 kW heater versus a 3.45 kW heater to be 155 kW more than the demand charge if the lower wattage heaters were used. Working with the utility companies to understand their method of billing and taking advantage of any rebates they may offer can reduce the utility bill.
Electrical Wiring Installation Do not allow the installer to drill a hole in the wall case to run the electrical wiring. If this is done, the wiring will have to be run between the chassis and the edge of the wall case so it can be connected to the unit wiring on the room side of the wall case. When the chassis is removed for servicing or cleaning, the insulation on the wires can be cut and can create a safety hazard. If the electrical connection on a 230-volt or 208-volt installation is to be made by the line cord plugged into a wall-mounted receptacle, the receptacle should be located in the wall under the case or close to the side of the wall case. This installation makes a much neater appearance than a line cord running a foot or more across the floor. The electrician may want to place the receptacle as far from the unit as possible to save a few feet of wiring without considering how the installation may appear.
Central Desk Control and Remote Thermostat Wiring Do not allow the installer to drill a hole in the wall case to run Central Desk Control wiring or remote thermostat wiring to the unit terminals. CDC and remote thermostat wiring is classified as low-voltage wiring and does not have to be run in conduit unless required by local code. CDC and remote thermostat wiring should be run in the walls and exit the wall under the wall case about 2" from the right-hand side. The base pan is designed with a clearance for the line cord and the low-voltage wiring can be run to the chassis in this area also. Wire molding can be used to hold the wiring close to the bottom of the wall case. If a sub-base is used, the wiring can be run through the sub-base, entering the rear and exiting through one of the front panels. When the room cabinet is in place the CDC or remote thermostat wiring is usually not
Exterior Grilles When replacing an older unit the existing outdoor grille may need to be changed or modified. Outdoor airflow patterns have changed and this may dictate the need for outdoor grille replacement or modification.

Ducted Installation Comments New Installations The GE Zoneline® 2800 and 3800 series are approved for ducted installation using the GE Duct Adapter model RAK6052 and the GE Duct Extension RAK601. A field-fabricated duct extension with the same interior measurements as the RAK601 may be used with the RAK6052 duct adapter. GE does not recommend ducting in more than one direction. The use of a duct adapter other than the RAK6052 is not approved by GE and may cause problems such as inadequate airflow to the secondary room or the unit shutting off on one of the overload devices. Failure to allow for adequate air return from the secondary room is often the cause of less than satisfactory performance of a ducted installation.
If the chassis is a slope-front discharge and the duct dimensions are 8-3/8" high by 6-1/2" wide then the chassis has already been replaced and the purchase of a new duct adapter is not required. The only piece that needs to be replaced in this installation is the transition piece, model RAK7022, which fits between the chassis and the duct adapter. If the chassis being replaced has a model number that begins with AZ22E, AZ22, AZ25, AZ32, AZ32H or AZ35, the new 2800 or 3800 Series unit can be installed using the same components that were used for the 2200 or 3200 Series unit. If the existing chassis is a slope-front discharge and the duct dimensions are 7-3/32" high by 6-1/2" wide only the RAK7022 transition piece is required to install a 2800 or 3800 Series unit in the ducted installation. There were a number of Zoneline units installed in ducted installations that did not use a GE duct adapter. The easiest way to determine if the existing duct adapter is a GE duct adapter is to compare the duct adapter dimensions to the dimensions above. If the dimensions are different than the dimensions above or it the duct adapter is not made of sheet metal, it is not a GE duct adapter. In such installations GE recommends the removal of the old duct adapter and duct extension and the installation of a RAK6052 duct adapter and a RAK601 duct extension. Zoneline units installed in installations not using GE duct adapters and an extension with the same cross-section dimensions as the duct adapter may not be covered by the warranty.
GE offers duct adapters to allow for easy replacements of previous design chassis in ducted installations where a GE duct adapter was used in the original installation. A duct adapter is available that will align with the duct extension when GE-built components were used in the original installation. The duct extension used from the early 1960s until late 1987 was 8-3/8" high by 6-1/2" wide. If the chassis to be replaced is the flat-top discharge (design until late 1987) the duct adapter model RAK7012 will align with the existing duct extension. This means the duct extension will not have to be changed. However, to keep the cost of the replacement to a minimum there are components that will need to be taken off the existing installation and used on the RAK7012 duct adapter. The wall case mounting brackets, screws, discharge grille, damper, and end cap will need to be retained.
What is covered
Limited 2nd through 5th year parts warranty For the second through the fifth year from date of original purchase, GE will provide, free of charge, parts that fail as a result of a manufactur- ing defect. Parts covered are fan motors, switches, thermostat, heater, heater protectors, compressor overload, solenoids, circuit boards, auxiliary controls, thermistors, frost controls, icr pump, capacitors, varistors, and indoor blower bearing. This is a limited parts-only warranty, and does not include labor or transportation to and from the service shop.
Limited one-year warranty For one year from date of original purchase, we will provide, free of charge, parts and service labor on-site to repair or replace any part of the Zoneline that fails because of a manufacturing defect.
Limited five-year warranty For five years from the date of original purchase, we will provide, free of charge, parts and on-site service labor to repair or replace any part of the sealed refrigerating system (the compressor, condenser, evaporator and all connecting tubing) that fails because of a manufacturing defect.
All warranty service will be provided by our factory service centers or by our authorized customer care® servicers during normal working hours.
*See written warranty for details

Alphabetical Index
Category Page No.
Application Comments 20
Auxiliary Control Switches 12-13
Case Dimensions 21
Central Desk Control 14
Condensate Disposal Systems 34-36
Cooling/Heat Pump Performance Data 45
Warm Gray Beige
Ducted Installations 37-39
Dry Air 4
Electrical Connection 42
Essential Elements Ordering Overview 43
Exterior Grilles 40-41
Features and Benefits 9-11
Features Table 8
General Installation Suggestions 57-58
Heat Pumps and Energy Savings 18-19
Maple
Introduction to Zoneline ® 6
Latent System Capacity 46
Maximum Connected Load 44
Mini Specs 2800 2
Mini Specs 3800 2
Mini Specs 5800 2
Mini Specs Power Connection Kits and Nomenclature 3
Normal Yearly Operating Data 47
Remote Thermostat Control 15-17
Bittersweet Chocolate
Schematics 48-50
Specifications 55
Suggested Big Form Specifications 51-53
Colors may vary slightly due to printing process.
Wall Case/Sub Base Installation 22-33
Warranty 58
Zoneline System 7

A century of quality and innovation For more than a century, GE has been committed to producing innovative products that change the way people live. The result of thorough research and rigorous testing, GE appliances are designed for years of dependable performance. Today, the GE tradition of quality and innovation continues.
Before purchasing an appliance, read important information about its estimated annual energy consumption or energy efficiency rating that is available from your retailer or ge.com
GE has a policy of continuous improvement of its products and reserves the right to change materials and specifications without notice.
© 2007 GE Company Pub. No. 20-S087 PC48947