
UNVENTED (VENT-FREE) UNIVERSAL FIREBOX OWNER’S OPERATION AND INSTALLATION MANUAL


Non-Circulating Models V32S, VFB32NC, V36S, V36SH, VFB36NC1, V42S, V42SH AND VFB42NC1
Circulating Models V32, V36, V42, CUVF36C, VFB32C, VFB36C1, VFB42C1, V36H and V42H
Outside Air Models V32A, V32AS, VFB32AC, VFB32ANC, V36A, V36AS, V36ASH, V36AH, VFB36AC, VFB36ANC, V42A, V42AS, V42ASH, V42AH,
For use only with a listed gas-fired unvented decorative room heater Not to exceed 40,000 Btu/Hr. Do not build a wood fire.
Carefully review the instructions supplied with the decorative type unvented room heater for the minimum fireplace size requirement. Do not install an appliance in this firebox unless this firebox meets the minimum dimen- sions required for the installation.
This firebox has been tested and approved under ANSI Z21.91 for use with any ANSI Z21.11.2 approved gas logs.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
For more information, visit www.fmiproducts.com

Safety 2 Local Codes 3 Product Features 4 Locating Firebox 4 Product Specifications 5 Air For Combustion and Ventilation 7
Installation 9 Replacement Parts 18 Technical Service 18 Accessories 18 Parts 20 Warranty Back Cover
This appliance may be in- stalled in an aftermarket,* permanently located, manufactured (mobile) home, where not prohib- ited by local codes.
Do not place clothing or other flammable material on or near the appliance. Never place any objects in the firebox or on logs.

Firebox front and screen become very hot when running heater. Keep children and adults away from hot surface to avoid burns or clothing ignition. Firebox will remain hot for a time after shutdown. Allow surface to cool before touching.
Carefully supervise young chil- dren when they are in the room with firebox.
You must operate this fireplace with the provided fireplace screen, hood if provided, in place. Make sure these parts are in place and screens are closed before running firebox. The supplied hood may not be replaced with a hood which may be provided with a log heater.
Keep the fireplace area clear and free from combustible materials, gasoline and other flammable vapors and liquids.
Local Codes Install and use heater with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*. Firebox must be electrically grounded in accordance with the National Electrical Code, ANSI/NFPA70 (latest edition). *Available from: American National Standards Institute, Inc.
State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Mas- sachusetts. Sellers of unvented propane or natural gas-fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit. Vent-free gas products are prohibited for bedroom and bathroom installation in the Commonwealth of Massachusetts.
1430 Broadway New York, NY 10018 National Fire Protection Association, Inc.
Batterymarch Park · Quincy, MA 02269

Product Features Operation This firebox is designed for use with approved ANSI Z21.11.2 decorative type unvented room heaters. (Physical size limitations apply. Refer to minimum firebox requirements supplied with log heater.) It requires no outside vent- ing or chimney making installation easy and inexpensive. When used without the blower, the firebox requires no electricity making it ideal for emergency backup heat.
Refractory brick liner Your firebox may feature a concrete refrac- tory brick liner. As with all concrete liners, this liner may develop slight cracks when exposed to heat. These cracks will not affect the performance of the fireplace or vent-free gas logs.
OUTSIDE AIR KIT ACCESSORY Fireboxes that include “A” in their model number can accept any AK4 series outside air kit accessory. The optional AK4 air kit provides additional outdoor air to improve burner efficiency and reduce build-up of condensation in the living space. Follow the instructions included with the air kit.
Blower Accessory The circulating models will accept either a ro- tary type fan (model BK) or the triple radial fan blower system (model BK3) accessories. The blower circulates heated air from the firebox into the room. Use of blower is optional.
Planning Plan where you will install the firebox. This will save time and money later when you install the firebox. Before installation, consider the following: 1. Where the firebox will be located. Allow for wall and ceiling clearances (see Installa- tion Clearances, page 10). 2. Everything needed to complete installation.


251/8" 291/2" 347/16" 363/8"
31/2" Built-In Side Nailing Flanges
291/2" 163/4" 187/16"
29/16" 81/8"
6" 815/16" 93/4"
Right Side View

36" and 42" Models Note: If only one dimension is shown, the dimension is the same for both 36" and 42" mod- els.

View

Unusually Tight Construction The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of un- usually tight construction, you must provide additional fresh air. Unusually tight construction is defined as construction where: a. walls and ceilings exposed to the out-
WARNING: This heater shall not be installed in a room or space unless the required vol- ume of indoor combustion air is provided by the method de- scribed in the National Fuel Gas Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code, or applicable local codes. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.
side atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10-11 kg per pa-sec-m2) or less with openings gasketed or sealed and b. weather stripping has been added on
openable windows and doors and c. caulking or sealants are applied to
Today’s homes are built more energy efficient than ever. New materials, increased insulation and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible. While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning ap- pliances need fresh air for proper combustion and ventilation. Exhaust fans, fireboxes, clothes dryers and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appli- ances.
areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines and at other openings. If your home meets all of the three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors, page 9. If your home does not meet all of the three criteria above, proceed to Determining Fresh-Air Flow for Firebox Location, page 8.
Confined and Unconfined Space The National Fuel Gas Code, ANSI Z223.1/ NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the ag- gregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the un- confined space. * Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.
PROVIDING ADEQUATE VENTILATION The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation. All spaces in homes fall into one of the three following ventilation classifications: 1. Unusually Tight Construction 2. Unconfined Space 3. Confined Space The information on page 7 through 9 will help you classify your space and provide adequate ventilation.

Determining if You Have a Confined or Unconfined Space Use this work sheet to determine if you have a confined or unconfined space. Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms. 1. Determine the volume of the space (length x width x height). Length x Width x Height = cu. ft. (volume of space) Example: Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling height) = 3168 cu. ft. (volume of space) If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space. 2. Multiply the space volume by 20 to deter- mine the maximum Btu/Hr the space can support (volume of space) x 20 = (Maxi- mum Btu/Hr the space can support) Example: 3168 cu. ft. (volume of space) x 20 = 63,360 (maximum Btu/Hr the space can support) 3. Add the Btu/Hr of all fuel burning appli- ances in the space. Vent-free heater Btu/Hr Gas water heater* Btu/Hr Gas furnace Btu/Hr Vented gas heater Btu/Hr Gas fireplace logs Btu/Hr Other gas appliances* + Btu/Hr Total = Btu/Hr * Do not include direct-vent gas appli- ances. Direct-vent draws combustion air from the outdoors and vents to the outdoors. Example: Gas water heater Btu/Hr Vent-free heater + Btu/Hr Total = Btu/Hr
space can support) 79,000 Btu/Hr (actual amount of Btu/Hr used) The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can sup- port. You must provide additional fresh air. Your options are as follows: A. Rework worksheet, adding the space
of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 9. B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, page 9. C. Install a lower Btu/Hr heater, if lower Btu/
Hr size makes room unconfined. If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
40,000 39,000 79,000

Ventilation Air From Outdoors Provide extra fresh air by using ventilation grills or ducts. You must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size of ventilation grills or ducts. IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermo- stat-controlled power vent. Heated air entering the attic will activate the power vent.
Ventilation Air From Inside Building This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 4). You can also remove door into adjoining room (see option 3, Figure 3). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size of ventilation grills or ducts.


Figure 4 - Ventilation Air from Outdoors
CAUTION: Log heaters installed in this firebox create warm air currents. These cur- rents move heat to wall surfaces next to firebox. Installing firebox next to vinyl or cloth wall cover- ings or operating firebox where impurities (such as, but not limited to, tobacco smoke, aro- matic candles, cleaning fluids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
Ventilation · Grills Into Adjoining · Room, Option 1

IMPORTANT: Vent-free gas log heaters add moisture to the air. Although this is beneficial, installing firebox in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventilation, page 7. IMPORTANT: Make sure firebox is level. If firebox is not level, log set will not work properly. Note: Your firebox is designed to be used in zero clearance installations. Wall or framing material can be placed against any exterior surface on the rear, sides, top or bottom of your firebox, except where standoff spacers are integrally attached. If standoff spacers are attached to your firebox, these spacers can be placed directly against wall or framing ma- terials. Use the dimensions shown for rough opening to create the easiest installation. Use dimensions shown for rough openings to create the easiest installation (see Built-In Firebox Installation, page 11).
optional cabinet mantels (see Accessories, page 18) or as a built-in unit. Clearances are the same for either installation method.
*Minimum 16" from Side Wall
Mantel Clearances for Built-In Installation If placing custom mantel above built-in firebox, you must meet the minimum allowable clear- ance between mantel shelf and top of firebox opening shown in Figure 6, page 11. These are the minimum allowable mantel clearances for a safe installation. Use larger clearances wherever possible to minimize the heating of objects and materials placed on the mantel.
Carefully follow these instructions. This will ensure safe installation. Minimum Wall and Ceiling Clearances (see Figure 5) A. Clearances from the side of fireplace
cabinet to any combustible material and wall should follow diagram in Figure 5. Example: The face of a mantel, bookshelf, etc. is made of combustible material and protrudes 3 1/2" from the wall. This com- bustible material must be 4" from the side of the fireplace cabinet (see Figure 5). B. Clearances from the top of firebox opening
to ceiling should not be less than 42". C. When firebox is installed on carpeting or
other combustible material, other than wood flooring, firebox should be installed on a metal or wood panel extending the full width and depth of enclosure. D. Clearances from bottom of firebox to the
floor is 0". These fireboxes can be installed as freestand- ing units against a wall with the approved,
Example · *

Built-In Firebox Installation Built-in installation of this firebox involves installing firebox into a framed-in enclosure. This makes the front of firebox flush with wall. Optional brass trim accessories are available (see Accessories, page 18). The brass trim will extend past sides of firebox approximately 1/2". This will cover the rough edges of the wall opening. If installing a mantel above the firebox, you must follow the clearances shown in Figure 6. Follow the instructions below to install the firebox in this manner. 1. Frame in rough opening. The firebox fram- ing should be constructed of 2 x 4 lumber or heavier. Use dimensions in Table 1 and rough opening layout in Figure 7a. Adjust framing so that firebox flushes with finished wall surface. If installing in a corner, use dimensions in Figures 7b, 7c and 7d for rough opening. 2. Install gas piping to firebox location. See In- stalling Gas Line, page 12 and Connecting to Gas Supply in log set owner’s manual.
0" CLEARANCE
39 3/8"
27 3/4"
*10 1/2" *10 1/2"
34 1/2"
55 5/8"
0" CLEARANCE
50 3/8"
35 5/8"
Wall board or facing material (above firebox) may be of combustible material, including decorative mantel ornaments or other similar projec- tions off of the facing material.
Mantel Shelf Note: Any portion of the mantel shelf must NOT extend beyond this profile.
41 1/2"
*14 1/2"
71 1/4"
6 3/4"
1 1/2"
Noncombustible Material May Project Off this Surface above the Firebox Hood
Supplied Firebox Hood Must Be Used at All Times
* These dimensions allow for min. Clearances to a 45° projected side wall. However, clearances to projected mantel trims and facings are allowed within a min. Of 16" to a perpenducular wall as shown in figure 5, on page 10.
Figure 6 - Minimum Mantel Clearances

IMPORTANT: If installing blower accessory (circulating models with louvers only), see Hard-Wiring Firebox, page 16. 3. Carefully set firebox in front of rough open- ing with back of firebox inside wall open- ing. IMPORTANT: If installing a perimeter trim kit, see instructions included with trim accessory. You must install shoulder screws from trim kit now. 4. Carefully insert firebox into rough opening. 5. Attach firebox to wall studs using nails or wood screws through holes in nailing flange (see Figure 8). 6. If using an optional perimeter trim kit, install the trim after final finishing and/or painting of wall. See instructions included with trim accessory for attaching trim. 7. Install and properly test gas log heater. Follow installation instructions included with the vent-free gas log heater that is being installed. IMPORTANT: When finishing your firebox, combustible materials such as wall board, gypsum board, sheet rock, drywall, plywood, etc. may be butted up next to the sides and top of the firebox. Combustible materials should never overlap the firebox front facing.

This firebox may be installed using a cabinet mantel accessory against a wall in your home. The firebox and cabinet mantel can be installed directly on the floor. A trim kit is included with the mantel accessories. Follow instructions with mantel for installation.

Figure 9 - Installing Gas Line and Equipment Shutoff Valve (Model May
Vary From Illustration)

installing optional blower accessories
IMPORTANT: See Connecting to Gas Supply in your log set owner’s manual for details on gas hookup. You may run the gas line from either side of the firebox (see Figure 9). Decide which side you want to run the gas line from. Note: This is one option for installing shutoff valve. Check local codes for equipment shut- off valve location requirements. Locate the recessed knockout in one of the firebrick sidewall liners (see Figure 9 on page 12 and Figure 10). Firmly tap the center of the knockout with a chisel until it is released. Carefully chisel the rough edges of the hole you have made to smooth edges. This hole will line up with the hole in the outer casing. Locate the recessed knockout in one of the firebrick sidewall liners (see Figure 9 on page 12 and Figure 10). Firmly tap the center of the knockout with a chisel until it is released. Carefully chisel the rough edges of the hole to smooth edges. This hole will line up with the hole in the outer casing.
Note: Appearance of firebox may vary de- pending on model. There are two (2) blower accessory options for use in the vent-free fireboxes. Blower acces- sory models are BK and BK3. Model BK is a rotary squirrel cage type blower with magnetic attachment and variable speed control. The BK3 is a triple fan blower system with an on/ off rocker switch. On 32" models only, the blower must be installed by removing the lower face panel and placing blower into its proper mounting position. The 36" and 42" models can use this method or remove the bottom front re- fractory brick liner and access panel to allow installation through the firebox bottom (see Figure 11).
Figure 11 - Accessing Blower Compartment
Figure 10 - Location of Knockout for
(Controls Not Shown for Clarity)

Decide which way you intend to gain access into the bottom rear of the firebox to install the blower accessory. The lower front panel can be removed easily by snapping out the front with a flat blade screwdriver. Use cau- tion not to scratch any surfaces. Models with louvered front panels can also be removed by inserting fingertips between slots and gently pulling out. DO NOT FORCE. The panels are actually held in place by means of a retention dimple embossed on the edge of removable panels. Accessibility to the bottom on 36" and 42" models only, can also be gained through the access panel underneath the bottom front refractory brick liner. Lift the bottom front refractory brick liner up and out of the firebox floor, exposing the rectangular shaped access panel (see Figure 11, page 13). The sides and back refractory brick liner pieces do not have to be removed. Lift access panel out by using finger holes. Blower accessory BK or BK3 can now be installed.
Model BK Installation 1. Attach the power cord to blower motor by firmly pushing two female terminals at end of power cord onto two spade terminals on blower motor (see Figure 13). 2. Attach green ground wire from power cord to blower housing using screw provided (see Figure 13). Tighten screws securely with a phillips screwdriver. 3. Place blower against lower rear wall of firebox outer wrapper with exhaust port di- rected upward. Depending on your model, you may have to carefully route the blower assembly past controls and brackets and position blower inside back opening. The blower will be held in position against the back wall by magnets incorporated onto blower housing (see Figure 13). 4. Be certain that all wire terminals are securely attached to terminals on blower motor and that the screw retaining the green ground wire is tight. 5. Position speed control bracket over flange on hearth pan by sliding it up between firebox face and hearth pan flange, then down until seated onto lower flange of lou- ver opening (see Figure 14, page 15). 6. Mount speed control box by placing plas- tic control shaft through bottom hole on speed control bracket. Top screw head on control box will fit inside top hole on


Blower Installed After Lower Panel Removed
Figure 12 - Accessing Duplex Electrical Outlet Installed in Bottom Right Side of
Figure 13 - Blower Model BK
Spade Terminals · Green Ground Wire

bracket (see Figure 14). Secure speed control to bracket with lock nut by pushing and turning lock nut with pliers clockwise until it is tight against bracket. 7. Remove knockout plug from louver panel by pressing top and bottom retaining clips (see Figure 11, page 13). 8. Place louver panel, louvers pointing up, back into framed opening. Align control shaft with rectangular opening by sliding control bracket along flange (see Figure 14). 9. Fully seat louver panel into frame open- ing by gently pressing along ends until all dimpled retainers have snapped in place. 10. Place control knob, provided, onto control shaft (see Figure 14). 11. Check to make sure power cord is com- pletely clear of blower wheel and there are no foreign objects in blower wheel. Also, double check all wire leads and make sure wire routing is not pinched or in a precarious position. Correct accordingly.
Variable Fan Switch Fan Switch
110/115 V.A.C.
Wiring Diagram Decal 12" in Front of Blower
Figure 15 - Location of Wiring Diagram Decal (Model May Vary From Illustration)
Model BK3 Installation 1. Remove knockout plug from louver panel by pressing top and bottom retaining clips (see Figure 11, page 13). 2. Place BK3 fan assembly between two leg stands with fan blades pointing toward rear of fireplace (see Figure 16).


BK3 Blower Leg Stands
Figure 14 - Attaching Speed Control to
Firebox with Panel Louvers
Figure 16 - Mounting BK3 Blower

3. Using screws provided, fasten upper flange of blower bracket to hearth pan and end flanges to leg stands (see Figure 16, page 15). Note: The wire assembly must be ar- ranged in front of and away from fan blades to reach power receptacle plug. 4. Remove 2 connectors from ON/OFF rocker switch located on wiring harness (see Figure 17). 5. Insert rocker switch into lower lover panel with switch lever pointing outward. 6. Reconnect previously removed wire con- nectors onto switch terminals. 7. Check to make sure power cord is com- pletely clear of blower and that there are no foreign objects in blower. Also, double check all wire leads and make sure wire routing is not pinched or in a precarious position. Correct accordingly. 8. Turn on power to duplex outlet if previ- ously turned off per warning in column 1, page 14. 9. Plug in blower power cord to duplex outlet (see Figure 12, page 14). 10. Using ON/OFF rocker switch to turn blower on and check for operation. Turn blower off before continuing. 11. Peel off backing paper and stick supplied wiring diagram decal on firebox bottom approximately 12" in from of blower (see Figure 18).
110/115 V.A.C.
Motor No. 1
Motor No. 2
Motor No. 3
Figure 18 - BK3 Wiring Diagram

The “Handy Box” with duplex outlet is pro- vided in the firebox located in the lower right base area. 1. Remove screw holding duplex outlet cover to handy box. Remove duplex outlet. 2. Route electrical cable through strain relief and handy box (see Figure 19). 3. Connect electrical cable to duplex outlet. Match wire colors to those on duplex out- let. Be sure to connect the ground wire. 4. Place duplex outlet back into handy box and secure with screws. Replace outlet cover.


Duplex Box/ Handy Box
Figure 19 - Hard-Wiring Firebox
Figure 17 - Connecting Rocker Switch

COMBUSTION AIR KIT MODEL AK4 (OPTIONAL) The outside air kit may be installed on the left side of the fireplace only. The vent can be installed through any outside wall a minimum of three feet below fireplace termination cap. The handle to operate the damper door for the outside air inlet will be located inside the left “screen pocket” of the firebox (see Figure 20). Pull the handle to open or push to close.
INSTALLING FIREPLACE HOOD AND SCREEN 1. Attach hood to firebox using screws pro- vided (see Figure 21). 2. Insert each rod through all rings located at top of screen. 3. Insert first rod into rear hole in left side of firebox. Fasten rod to rear hole near center of firebox using #10 x 3/8" Phillips screw provided (see Figure 22). 4. Insert other rod into front hole on right side of firebox and fasten using remaining Phillips screw.


Figure 21 - Screw and Hood Placement
(Model May Vary From Illustration)
Top View of Rod Layout

Figure 22 - Installing Fireplace Screen
(Model May Vary From Illustration)
Hood · Screws

Technical Service You may have further questions about instal- lation, operation, or troubleshooting. If so, contact FMI PRODUCTS, LLC at 1-866-328- 4537. When calling please have your model and serial numbers of your heater ready.
You can also visit our web site at www.fmiproducts.com.
OUTSIDE AIR KIT AK4 - Complete Kit w/ Collar, Hood & 3' of Flex Tube AK4X - Collar and Hood (accepts any length of 4" flex tube) AK4B - 50 pc. Bulk Collar Only Kits
Purchase these accessories from your local dealer. If they can not supply these accessories call FMI PRODUCTS, LLC at 1-866-328-4537 for information. You can also write to the ad- dress listed on the back page of this manual.
Optional kits provide additional air to reduce build-up of condensation that occurs in today’s tightly constructed homes. For optional use on models with an “A” included in the model number.
Fire Crackle - CF6-a Creates the sound of a real burning fire.
Refractory brick liner Kit BL36H - 36" Textured Herringbone BL42H - 42" Textured Herringbone BL36HS - 36" Smooth Herringbone BL42HS - 42" Smooth Herringbone
Blower Kit BK - Squirrel Cage Blower With Speed Control BK3 - Triple Fan Blower System
Hoods H36B - 36" Brushed Brass H36P - 36" Platinum H42B - 42" Brushed Brass H42P - 42" Platinum

Face/Louver Panel Kits Smooth Faced - Black SP32 - 32" Model, SP36 - 36" Model, SP42 - 42" Model Stamped Louver - Black SL32 - 32" Model, SL36 - 36" Model, SL42 - 42" Model Rolled - Black RL32 - 32" Model, RL36 - 36" Model, RL42 - 42" Model Filigree - Black FP32 - 32" Model, FP36 - 36" Model, FP42 - 42" Model Filigree - Brushed Brass FP32B - 32" Model, FP36B - 36" Model, FP42B - 42" Model Filigree- Platinum FP32P - 32" Model, FP36P - 36" Model, FP42P - 42" Model Extruded- Black ELK32 - 32" Model, ELK36 - 36" Model, ELK42 - 42" Model Extruded- Brushed Brass ELK32B - 32" Model, ELK36B - 36" Model, ELK42B - 42" Model Extruded- Platinum ELK32P - 32" Model, ELK36P - 36" Model, ELK42P - 42" Model
32" WALL Mantels W32TU - 32" Unfinished, Traditional W32TO - 32" Oak Stain, Traditional W32CO - 32" Oak Stain, Classic W32DO - 32" Oak Stain, Dentil W32GO - 32" Oak Stain, Georgian
32" CORNER Mantels C32TU - 32" Unfinished, Traditional C32TO - 32" Oak Stain, Traditional C32CO - 32" Oak Stain, Classic C32GO - 32" Oak Stain, Georgian
36" WALL Mantels W36TU - 36" Unfinished, Traditional W36TO - 36" Oak Stain, Traditional
36" CORNER Mantels C36TU - 36" Unfinished, Traditional C36TO - 36" Oak Stain, Traditional
Louver Trim (Rolled Louvers Only) LT32B - 32" Brushed Brass LT32P - 32" Platinum LT36B - 36" Brushed Brass LT36P - 36" Platinum LT42B - 42" Brushed Brass LT42P - 42" Platinum
Perimeter Trim PT32 - 32" Black PT32B - 32" Brushed Brass PT32P - 32" Platinum PT36 - 36" Black PT36B - 36" Brushed Brass PT36P - 36" Platinum PT42 - 42" Black PT42B - 42" Brushed Brass PT42P - 42" Platinum



PARTS This list contains replaceable parts used in your firebox. When ordering parts, follow the instructions listed under Replacement Parts on page 18 of this manual.
V32AS, V32S
V32, V32A
KEY NO.
VFB32C VFB32AC 1 108441-01 108441-01 Screen 1 2 108700-01 108700-01 Screen Rod 2 3 11418 11418 Push-On Nut 2 4 108414-01 108414-01 Deflector Hood 1 5 108423-01 108423-04 Face Top Panel (VFB32NC Smooth Faced) 1 6 108423-01 108423-07 Face Bottom Panel (VFB32NC Smooth Faced) 1 7 ** ** Face Weldment 2 8 106683-01 106683-01 Firebox Support Leg 2 9 108434-01 108434-01 Left Refractory 1 10 108430-01 108430-01 Rear Refractory 1 11 108432-01 108432-01 Right Refractory 1 12 108426-01 108426-01 Bottom Rear Refractory 1 13 108428-01 108428-01 Bottom Front Refractory 1 14 ** ** Firebox Bottom 1 15 ** ** Firebox Surround 1 16 20027 20027 Refractory Retainer 2 17 ** ** Fireplace Top Insulation 1 18 ** ** Firebox Top 1 19 108415-01 108415-01 Starter Pipe Collar 1 20 ** ** Insulation Pan 1 21 108403-03 108403-03 Fireplace Top 1 22 20280 20280 Top Spacer 4 23 ** ** Fireplace Surround 1 24 24353 24353 Handy Box Assembly 2 25 108654-01 108654-01 Gas Conduit Left and Right Assembly 2 26 21171 21171 Gas Knock-Out Cover 4 27 14123 14123 Strain Relief 1 28 106703-02* 106703-02* Air Kit Door Assembly 1 29 108425-01* 108425-01* Air Rod Retainer 1
DESCRIPTION QTY.
* Part for “A” models only. ** Not a field replaceable part.

Models CUVF36C, V36, V36A, V36S, V36AS, V36ASH, V36H, V36AH, V36SH, VFB36AC, VFB36ANC V42, V42A, V42S, V42AS, V42ASH, V42H, V42AH, V42SH, VFB42AC, VFB42ANC, VFB36NC1, VFB42NC1, VFB36C1, VFB42C1

24/25

PARTS This list contains replaceable parts used in your firebox. When ordering parts, follow the instructions listed under Replacement Parts on page 18 of this manual.
CUVF36C V36, V36A V36H, V36AH, VFB36C1 VFB36AC
V42S, V42AS V42ASH V42SH, VFB42NC1 VFB42ANC
V36S, V36AS V36ASH V36SH, VFB36NC1 VFB36ANC
V42, V42A, V42H, V42AH VFB42C1 VFB42AC 1 12116 12116 107981-01 107981-01 Screen 2 2 106691-01 106691-01 107839-01 107839-01 Screen Rod 2 3 11418 Push-On Nut 2 4 107944-01 107944-01 107979-01 107979-01 Deflector Hood 1 5 106651-01 106684-01 107805-01 107805-02 Closure Top Panel 1 — Extruded Louver 1 6 106651-01 106650-01 107805-01 107805-03 Closure Bottom Panel 1 — Extruded Louver 1 7 ** Face Weldment 1 8 106683-01 Firebox Support Leg 2 9 ** Firebox Bottom 1 10 107775-01 Access Panel 1 11 20027 Refractory Retainer 2 12 ** Firebox Surround 1 13 ** Firebox Top Shield 1 14 ** Firebox Top 1 15 106687-01 Damper Can Collar 1 16 ** Insulation Pan 1 17 ** Fireplace Top Insulation 1 18 ** Fireplace Top 1 19 20280 Top Spacer 4 20 ** Fireplace Surround 1 21 110037-01 Handy Box Assembly 1 22 106642-01* Air Rod Retainer 1 23 21171 Gas Knock-Out Cover 4 24 21379 21379 24460 24460 Gas Conduit 1 25 21380 21380 — — Gas Conduit 1 26 106703-01* Air Kit Door Assembly 1
KEY NO.
DESCRIPTION QTY.
* Part for “A” models only. **Not a field replaceable part.
KEY NO.
V36H, V36AH V36SH, V36ASH DESCRIPTION QTY 28 106658-01 106658-02 108164-01 108164-02 Left Refractory 1 29 106660-01 106660-02 108166-01 108166-02 Rear Refractory 1 30 106659-01 106659-02 108165-01 108165-02 Right Refractory 1 31 106661-01 106661-02 108167-01 108167-02 Bottom Rear Refractory 1 32 106662-01 106662-02 108168-01 108168-02 Bottom Front Refractory 1
V36, V36A V36S, V36AS CUVF36C
V42H, V42AH V42SH, V42ASH DESCRIPTION QTY 28 107812-01 107812-02 108169-02 Left Refractory 1 29 107816-01 107816-02 108171-02 Rear Refractory 1 30 107814-01 107814-02 108170-02 Right Refractory 1 31 107818-01 107818-02 108172-02 Bottom Rear Refractory 1 32 107820-01 107820-02 108173-02 Bottom Front Refractory 1
KEY NO.
V42, V42A V42S, V42AS

Model (located on product or identification tag)
Serial No. (located on product or identification tag)
Keep receipt for warranty verification.
New Products Standard Warranty: FMI PRODUCTS, LLC warrants this new product and any parts thereof to be free from defects in material and workmanship for a period of four (4) year from the date of first purchase from an authorized dealer provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s warnings and instructions. For products purchased for commercial, industrial or rental usage, this warranty is limited to 90 days from the date of first purchase.
Factory Reconditioned Products Limited Warranty: FMI PRODUCTS, LLC warrants factory reconditioned products and any parts thereof to be free from defects in material and workmanship for 30 days from the date of first purchase from an authorized dealer provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s warnings and instructions.
Terms Common to All Warranties The following terms apply to all of the above warranties: Always specify model number and serial number when contacting the manufacturer. To make a claim under this warranty the bill of sale or other proof of purchase must be presented. This warranty is extended only to the original retail purchaser when purchased from an authorized dealer, and only when installed by a qualified installer in accordance with all local codes and instructions furnished with this product. This warranty covers the cost of part(s) required to restore this product to proper operating condition and an allowance for labor when provided by a FMI PRODUCTS, LLC Authorized Service Center or a provider approved by FMI PRODUCTS, LLC. Warranty parts must be obtained through authorized dealers of this product and/or FMI PRODUCTS, LLC who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty. Travel, handling, transportation, diagnostic, material, labor and incidental costs associated with warranty repairs, unless expressly covered by this warranty, are not reimbursable under this warranty and are the responsibility of the owner. Excluded from this warranty are products or parts that fail or become damaged due to misuse, accidents, improper installation, lack of proper maintenance, tampering, or alteration(s). This is FMI PRODUCTS, LLC’s exclusive warranty, and to the full extent allowed by law; this express war- ranty excludes any and all other warranties, express or implied, written or verbal and limits the duration of any and all implied warranties, including warranties of merchantability and fitness for a particular purpose to four (4) year on new products and 30 days on factory reconditioned products from the date of first purchase. FMI PRODUCTS, LLC makes no other warranties regarding this product. FMI PRODUCTS, LLC’s liability is limited to the purchase price of the product, and FMI PRODUCTS, LLC shall not be liable for any other damages whatsoever under any circumstances including indirect, incidental, or consequential damages. Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. For information about this warranty contact:
2701 S. Harbor Blvd. Santa Ana, CA 92704
108662-01 Rev. L 09/09
1-866-328-4537 www.fmiproducts.com
Date Purchased
What the fault codes shown on the display mean and how to clear them.
| Code | Meaning | Fix | |
|---|---|---|---|
| BK3 | Triple Fan Blower System | p.18 | |
| AK4 | Complete Kit w/ Collar, Hood & 3' of | p.18 | |
| AK4X | Collar and Hood (accepts any | p.18 | |
| AK4B | 50 pc. Bulk Collar Only Kits | p.18 | |
| BL36H | 36" Textured Herringbone | p.18 | |
| BL42H | 42" Textured Herringbone | p.18 | |
| H36B | 36" Brushed Brass | p.18 | |
| H36P | 36" Platinum | p.18 | |
| H42B | 42" Brushed Brass | p.18 | |
| H42P | 42" Platinum | p.18 |
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.