Instructions

FMI MM63 — Instructions diagram (page 1)
Fig. 1 · Instructions

Masonry Firebox

Models MM33, MM39, MM44, MM49 and MM63

IF FIREPLACE IS TO BE INSTALLED DIRECTLY ON ANY COMBUSTIBLE MATERIAL, A METAL BASE IS REQUIRED.

SAVE THIS BOOK This book is valuable. In addition to instructing you on how to install and maintain your appliance, it also contains information that will enable you to obtain replacement parts or accessory items when needed. Keep it with your other important papers.

This fireplace is approved for use as a wood burning fireplace or for use with a vented gas log approved to ANS Z21.60 or Z21.84 standards. It has not been tested or approved for unvented gas logs.

This wood burning fireplace complies with UL127 standard as a FACTORY BUILT APPLIANCE.

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.

FMI MM63 — Masonry Firebox diagram (page 1)
Fig. 2 · Masonry Firebox

Report No. 08-154

Do not store gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

ICC Evaluation Services Report No. 2401

For more information, visit www.fmiproducts.com

Page 4 of the FMI MM63 user manual — A A
Page 4 · click to enlarge
Page 4

specifications

FMI MM63 — specifications diagram (page 4)
Fig. 3 · specifications

Ø4" OUTSIDE AIR ACCESS CAN BE INSTALLED ON THE LEFT SIDE ALSO

A A

Figure 1MM33 Fireplace Overall Dimensions
FMI MM63 — A A diagram (page 4)
Fig. 4

A A

Figure 2MM63 Fireplace Overall Dimensions
Page 5 of the FMI MM63 user manual — specifications
Page 5 · click to enlarge
Page 5

specifications

FMI MM63 — specifications diagram (page 5)
Fig. 5 · specifications
E4" 21 10" 23" 4 ¼" C B A
FMI MM63 — specifications diagram (page 5)
Fig. 6 · specifications
Fireplace Overall Dimensions ModelABCDEF MM3943″39″29¼″27¾″38¾″Ø12″ MM4448″44″34¼″32¾″43¾″Ø12″ MM4953″49″39¼”37¾″48¾″Ø12″
Figure 3MM39/44/49 Fireplace Overall Dimensions
Page 6 of the FMI MM63 user manual — product overview
Page 6 · click to enlarge
Page 6

product overview

Introduction We extend a warm welcome from all of us at FMI PRODUCTS, LLC, proud manufacturers of the Grand Meridian Fireplaces. Thank you for choosing FMI. You may have thought long and hard before you chose the fireplace which would grace your home. Rest assured that every component of the Fireplace has been tested to ensure long-term durability.

Wall Installation Corner Installation

Flush Installation Full Projection Installation

Product Overview The Grand Meridian Fireplaces are designed as factory-built blocks to be assembled on-site. These fireplaces may be installed on either combustible or non-combustible floors. In order for the fireplace to be installed on a combustible floor though, it is nec essary that the fireplace be supported on a platform or sub-floor that is non-combustible.

Figure 4Typical Installations

The Four Components of the Grand Meridian Fireplace:

Combustible or Non-Combustible Floor •

Non-Combustible Raised Platform •

Firebox and Smoke Dome •

FMI PRODUCTS, LLC chimney system • required. Important: Follow the chimney pipe manufacturer’s instructions on the installation of their specific flue system. Careful step-by-step instructions for each phase of the installation procedure will be given for the Grand Meridian conventional radiant heat fireplaces. Those instructions generally fall into the following categories:

Attention: You may need a residential building permit to install a Grand Meridian Fireplace. Consult local jurisdictions before you get started! If asked, advise the local authorities that the FMI Fireplace is designed for installation per the National Fire Protection Association Standard for Chimneys, Fireplaces, Vents and Solid Fuel-Burning Appliances (NFPA211). When choosing the location of your FMI Fireplace, keep in mind you must maintain 2" minimum clearance from left, right and rear of Fireplace to surrounding structure. Also, when choosing a location, consider outside air requirements to determine if it will be on the left or right side of the Fireplace. In the case of an island installation, outside air accessibility may be obtained through sub flooring, see Optional Outside Air Kit on page 12.

Spacing and clearance as it relates to combustible • materials.

Familiarity of installation for all components. •

The strength of the floor on which it rests. •

Chimney system measurements. •

Choice of materials and craftsmanship in fireplace • and hearth finishing.

Internal

Page 7 of the FMI MM63 user manual — pre-Installation preparation
Page 7 · click to enlarge
Page 7

pre-Installation preparation

selecting location To determine the safest and most efficient location for the fireplace, you must take into consideration the following guidelines: 1. The location must allow for proper clearances (see Figures 6 and 7). 2. Consider a location where fireplace will not be af fected by drafts, air conditioning ducts, windows or doors. 3. A location that avoids cutting of joists or roof raf ters will make installation easier. 4. An outside air kit is available with this fireplace (see Optional Outside Air Kit on page 12).

Minimum/Maximum Chimney Height for Residential Installation Minimum height of chimney, measured from base of fireplace to flue gas outlet of termination, is 14 feet for straight flue or 17 feet for a flue with one elbow set. Maximum distance between elbows is 6 feet. For systems with two elbow sets, minimum height is 22 feet. Maximum height of any system is 40 feet. This measurement includes fireplace, chimney sections and height of termination assembly at level of the flue gas outlet (see Figure 20, page 16).

Minimum clearance to combustibles The distance to be maintained from the surfaces of the fireplace to combustibles must be observed. Below is a list of the most common combustible materials to name a few: Drywall Wood Flooring Plywood Sub-Flooring Wood Framing Mill Board Particle Board Plywood Paneling

Framing 1. Frame opening for fireplace using dimensions shown in Figures 6 and 7. 2. If fireplace is to be installed directly on carpeting, tile (other than ceramic) or any combustible material other than wood flooring, fireplace must be installed upon a metal extending full width and depth of fire place. 3. Set fireplace directly in front of this opening and slide unit back until nailing flanges touch side fram ing. 4. Check level of the fireplace and shim with sheet metal if necessary. 5. Before securing fireplace to prepared framing, ember protector (provided) must be placed between hearth extension (not supplied) and under bottom front edge of fireplace to protect against glowing em bers falling through. If fireplace is to be installed on a raised platform, a Z-type ember protector (not sup plied) must be fabricated to fit your required platform height. Ember protector should extend under fireplace a minimum of 1 1/2". Ember protector should be made of galvanized sheet metal (26 gauge minimum to pre vent corrosion. 6. Using screws or nails, secure fireplace to framing through flanges located on sides of fireplace.

Maintain the following clearances: Unit sides, rear, Dome sides, rear & top 2" min. Combustible Floors (MM33,39,44,49) 6" min. Combustible Floors (MM63 only) 8" min. Combustible Sheathing above opening top..18" min. Sheathing or trim to opening sides 8" min. Mantel above opening see Figure 5 Opening to sidewall 24" Hearth extension beyond front 20" Hearth extension beyond sides 12" Insulation from firebox 2"

Figure 5Mantel Clearances to Combustible

Material

Page 8 of the FMI MM63 user manual — FIREPLACE DOME
Page 8 · click to enlarge
Page 8

pre-Installation preparation

Maintain the 2" clearance to combustibles above the dome. DO NOT attach combustible materials on top of the dome.

18" MIN*

H**

8" MIN*

Non-combustible facing (not supplied).

Condition Dim. H**

with 6" platform 10"

with 8" platform 12"

* MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS. ** MEASURED FROM FLOOR TO TOP OF FIREBRICK LINER.

Figure 6Framing Dimensions for Combustible Floor Systems

**IF METAL FRAMING IS USED MAINTAIN A ½ INCH MIN. AIR SPACE FROM TOP OF LINTEL.

*IF WOOD FRAMING IS UTILIZED IT MUST BE HELD 18" MIN. FROM TOP OF LINTEL AND 2" MIN.CLEARANCE MUST BE MAINTAINED ALL AROUND FIREPLACE DOME.

Maintain the 2" clearance to combustibles above the dome. DO NOT attach combustible materials on top of the dome.

18" MIN*

ModelW MM3341” MM3947” MM4452” MM4957” MM6371”

½" MIN**

2" MIN. CLEARANCE TO COMBUSTIBLES AROUND SIDES, REAR AND TOP OF

FIREPLACE DOME

W

Figure 7Framing Dimensions for Non-Combustible Floor Systems

without platform 3"

Page 9 of the FMI MM63 user manual — pre-Installation preparation
Page 9 · click to enlarge
Page 9

pre-Installation preparation

FMI MM63 — pre-Installation preparation diagram (page 9)
Fig. 7 · pre-Installation preparation

* Not provided as part of fireplace or sold by FMI PRODUCTS, LLC.

Figure 8Corner Installation for Combustible Floor Systems
FMI MM63 — pre-Installation preparation diagram (page 9)
Fig. 8 · pre-Installation preparation
Figure 9Top View for Combustible Floor Systems
Page 10 of the FMI MM63 user manual — pre-Installation preparation
Page 10 · click to enlarge
Page 10

pre-Installation preparation

Mantel and mantel shelf clearances As with any radiant heat fireplace, the Grand Merid ian fireplaces must comply with building code safety clearances, per units that have openings of 6 sq. ft. or greater. For Mantel clearances see Figure 5, page 7. Walls that Adjoin – Safety codes and all practical outlooks insist that your fireplace cannot be installed closer than 2 ft. to any walls in the room the fireplace is housed in or to any walls of adjoining rooms. Caution in Regards to Combustibles – If any part of the fireplace or objects in the room (curtains, rugs, paint, cushions, etc.) start to show warping or dis coloration due to heat from the fireplace, it is time to take immediate action. Do not use the fireplace until you have figured out how to address the problem. You are facing a potential fire hazard. FMI PROD UCTS, LLC cannot be responsible for the make-up of material on the exterior of the fireplace you have chosen, nor can FMI PRODUCTS, LLC be held re sponsible for the materials in a room that may be responding negatively to heat. However, in almost all cases, there is a solution to the problem, either by making adjustments to airflow or the modifications to the room itself. Hearth Extension Where the flooring material at the opening of the fireplace is combustible, it is required that the hearth extension be covered with a non-combustible material. All hearth extensions must be made of code- rated, non-combustible materials such as tile, brick, marble, concrete or stone. The extension should be set flush against the front of the fireplace front and measure 20" minimum at the front and 12" minimum beyond the sides of the fireplace opening as shown in Figures 8 and 9 (page 9). These relative dimensions are also covered by code.

Attention: You will note that there will be a gap between the fireplace front and the extension of the non-combustible hearth material. Be certain that you seal this with non-combustible material. These Grand Meridian Fireplaces have been designed with clearance to combustible floors as indicated in Page 8. Cover any part of the combustible floor system left exposed with 1” (one inch) thick ceramic fiber insulation rated up to 2,100° F. Attention: It is critical to abide by the clearances listed in this manual for all components specified as it allows for movement of hot air from the fireplace into interior areas of the chimney chase. Also, be certain that the chimney system be installed as stated below. Prior to starting the installation, check with local, re gional or state codes for any restrictions or required permits regarding your fireplace installation. NOTE: It is required that ember protector strips must be laid on the fiber of the non-combustible raised plat form (see Figure 10). These are included with the Metal Base accessory.

Seal Gap Fireplace Front

Fireplace Front Raised Hearth

If a raised hearth extension is being installed, it must be constructed of non-combustible material and any material under the structure must also be non- combustible.

If using a raised hearth or metal base plate, note that a combustible wood header must be no closer than 2" to the top of the dome (see Figure 6, page 8).

Figure 10 - Hearth Extension

Show 8 more labels / short text on this page
Hearth Extension · Ember Protector · Seal Gap · Ember Protector · Hearth Extension · Hearth Extension · Fireplace Front Elevated · Ember Protector
Page 11 of the FMI MM63 user manual — pre-Installation preparation
Page 11 · click to enlarge
Page 11

pre-Installation preparation

FMI MM63 — pre-Installation preparation diagram (page 11)
Fig. 9 · pre-Installation preparation
FMI MM63 — pre-Installation preparation diagram (page 11)
Fig. 10 · pre-Installation preparation

2” AIRSPACE CLEARANCE TO COMBUSTIBLES ON REAR AND SIDES OF UNIT.

Figure 11Non Combustible Floor Figure 12: Combustible Floor
Page 12 of the FMI MM63 user manual — Factory built chimney systems
Page 12 · click to enlarge
Page 12

Venting Installation

Optional Outside air Kit (Model MM4AK) The Grand Meridian Fireplace needs enough re placement air to function properly and some local building codes may require outside combustion air to be provided. If no replacement air is provided, improper flue drafting may occur, creating negative pressure whereby smoke may enter the home, es pecially in homes that are very well insulated and tightly sealed. Check local building codes for specific requirements. The installation of an outside air kit should be per formed during the rough framing of the fireplace due to the nature of it's location. Outside combustion air is accessed through a vented crawl space or through a sidewall (Figure 13). If crawl space is used, check local codes for proper termination. Be sure that you carefully check the source of the outside air before you choose the site for your air in take. You don’t want a place where snow will collect, where bushes or trees will be growing or a location that is too close to any other structure. Install Combustion Air Kit into the firebox through the side wall opening provided. A 4" dia. hole will also be required through the firebrick side lining (see Figure 12). The tubing that goes out of the firebox wall must feed into a flexible metal conduit as the source for outside combustible air. Install a screened termina tion cap to keep out small animals.

Secure to Collars with Metal Tape, Screws or Straps (Min. of 1/4" x 20" in size)

FMI MM63 — Venting Installation diagram (page 12)
Fig. 11 · Venting Installation

Air Inlet Location Must Allow For Bushes or Snow

Vented Crawl Space (Check Local Codes Before Installing in a Vented Crawl Space)

Vent Hood Required for Wall Installation

Figure 13 - Outside Air Kit Venting

FMI MM63 — Venting Installation diagram (page 12)
Fig. 12 · Venting Installation

The maximum height for the air vent can not exceed 3 feet below the flue gas outlet of the termination.

Factory built chimney systems

The Grand Meridian is designed to be installed with 1) FMI PRODUCTS, LLC Metal Chimney System.

This Grand Meridian fireplace is intended as a 2) supplemental heat source only. It is not intended as a primary heat source.

It is the responsibility of the contractor/installer 3) (not the manufacturer) to ensure that adequate combustion air is provided for proper function of this fireplace. Fireplaces take up a large volume of replacement air from outside the house and if the house is of airtight construction, smoke spillage may occur if proper draft is not achieved.

There are many conditions beyond the 4) manufacturer’s control regarding improper fireplace operation. The manufacturer cannot ensure “smoke free” operation, nor can the manufacturer take on the responsibility for problems with surrounding construction; chimneys that have not

Figure 12 - Outside Air Kit Installation

Page 13 of the FMI MM63 user manual — venting installation
Page 13 · click to enlarge
Page 13

venting installation

been built at the correct heights; system drafts caused by faulty mechanical systems; adverse weather conditions or any other environmental situations over which the manufacturer has no control.

FMI MM63 — venting installation diagram (page 13)
Fig. 13 · venting installation

Inspect all fireplace & chimney components for 5) evidence of damage prior to starting installation. Consult your local distributor for replacement parts if necessary.

Under no circumstances should you make any 6) adjustments or modifications to the chimney system during the installation procedure. If you do, you are not only liable for negating the warranty, but you could very well cause a serious malfunction of the fireplace. You must follow these chimney instructions.

Caution is urged if it is decided to add insulation 7) material to any part of the Grand Meridian Fireplace or Chimney system, be certain that the insulation material is kept at least 2” away from any part of the system. When using insulation or vapor barrier materials, cover with a layer of plywood, particle board or gypsum board to maintain the specified 2” clearance.

RLT-12D Round Termination 7 3/4"*

Air spaces around firebox must remain open. 8) DO NOT fill these open spaces with insulation or packing material of any kind.

* The lineal gain for the terminations is measured to the flue gas outlet height.

Chimney Pipe The FMI PRODUCTS, LLC chimney system consists of 12", 18", 24", 36" and 48" snap-lock, double-wall pipe segments, planned for maximum adaptability to individual site requirements. Actual lengths gained after fitting overlaps must be taken into consideration (lineal gain) and are given in the lineal gain chart (see Figure 14). Lineal Gain is the actual measurable length of a part after two or more parts are connected.

15" Galvanized Outer Pipe

FMI MM63 — venting installation diagram (page 13)
Fig. 14 · venting installation

12 3/8" Stainless Inner Pipe

FMI MM63 — venting installation diagram (page 13)
Fig. 15 · venting installation

Figure 14 - Lineal Gain

Hemmed End

Page 14 of the FMI MM63 user manual — B
Page 14 · click to enlarge
Page 14

venting installation

Assembly and installation of double wall chimney system Each double wall chimney section consists of a gal vanized outer pipe, a stainless steel inner flue pipe and a wire spacer. The pipe sections must be as sembled independently as the chimney is installed. When connecting chimney directly to the fireplace, the inner flue pipe section must be installed first with the lanced side up. The outer pipe section can then be installed over the flue pipe section with the hemmed end up. Press down on each pipe section until the lances securely engage the hem on the fire place starter. The wire will assure the proper spacing between the inner and outer pipe sections. Continue to assemble chimney sections as outlined above, making sure that both the inner and outer pipe sections are locked together. When installing double wall snap-lock chimney together, it is impor tant to assure the joint between the chimney sections is locked. Check by pulling chimney upward after locking. The chimney will not come apart if properly locked. It is not necessary to add screws to keep the chimney together (exception, see Figure 15).

B

A

Figure 15 - Elbow Offset

Using ELBOW offsets (30E-12DM) 1. To achieve desired offset, you may install combi nations of 12”, 18”, 24”, 36” and 48” length of double wall pipe (see offset chart and Figure 15). 2. Chimney weight above offset rests on return elbow. Straps must be securely nailed to rafters or joists (see Figure 16, details A and B). 3. Maximum length of pipe between supports (return elbow or 12S-12DM) is 6’ of angle run. Maximum of two 6’ angle run sections per chimney system (see Figure 17, page 16). 4. All pipe connections between the offset and re turn must be secured with two screws on the outer pipe only (see Figure 15). Do not penetrate the in ner stainless.

OFFSET RISE CHIMNEY LENGTH A B 12" 18" 24" 36" 48" 4 3/8" 16 3/8" ELBOW SET ONLY 9 3/4" 25 1/2" 1 12 3/4" 30 3/4" 1 15" 34 3/4" 1 18" 40" 1 1 21 1/4" 46 1/4" 1 23 3/4" 49 1/4" 1 1 27 3/4" 56 3/4" 1 30" 60 3/4" 1 1 33" 66" 1 36" 71" 1 1 38 1/4" 75" 2 41 1/4" 80 1/4" 1 1 1 45" 86 3/4" 2 46 3/4" 89 1/2" 1 1 1 51" 97" 1 1 53 1/4" 101" 2 56 1/4" 106 1/4" 2 59 1/4" 111 1/2" 1 1 1 61 3/4" 115 1/2" 1 2 64 3/4" 120 3/4" 1 2 68 1/4" 127" 2 1 70" 130" 1 1 2 74 1/4" 137 1/2" 1 2 1 76 3/4" 141 1/2" 1 2 1 79 3/4" 146 3/4" 4 OFFSET CHART (22-50 FT. SYSTEM HEIGHT)

FMI MM63 — B diagram (page 14)
Fig. 16

Detail A Return Elbow

Figure 16 - Ceiling Support Pipe 12S-12DM

Screws

Page 15 of the FMI MM63 user manual — venting installation
Page 15 · click to enlarge
Page 15

venting installation

FMI MM63 — venting installation diagram (page 15)
Fig. 17 · venting installation

Penetrating roof To maintain a 2" clearance to the pipe on a roof with a pitch, a rectangular opening must be cut. 1. Determine center point through which pipe will penetrate roof. 2. Determine center point of roof. Pitch is distance the roof drops over a given span, usually 12". A 6/12 pitch means that roof drops 6" for each 12" measured horizontally down from roof rafters. 3. Use roof opening chart (Figure 20) to determine correct opening length and flashing required. 4. Remove shingles around opening measured. Cut out this section. 5. Add next sections of pipe until end penetrates roof line. Check to see that proper clearances are main tained. Extend chimney by adding sections of double wall pipe until pipe is minimum of 30” above highest point of roof cutout. Termination and chimney must extend a minimum of 36” above highest point where it passes through roof.

Figure 17 - Typical Offset Terminations

Firestop Spacers (FS-10) Firestop spacers are required at each point where the chimney penetrates a floor space. Their purpose is to establish and maintain the required clearance between the chimney and the combustible materials. When the pipe passes through a framed opening into a living space above, the firestop must be placed onto the ceil ing from below as shown in Figure 18. They also provide complete separation from one floor space to another or attic space as required by most codes. When the double wall pipe passes through a framed opening into an attic space, the firestop must be placed into an attic floor as shown in Figure 19.

FMI MM63 — venting installation diagram (page 15)
Fig. 18 · venting installation
FMI MM63 — venting installation diagram (page 15)
Fig. 19 · venting installation

Screws or Staples (Min. of 8)

Figure 18 - Firestop Spacer with Living Space

FMI MM63 — venting installation diagram (page 15)
Fig. 20 · venting installation

Figure 20 - Roof Opening Measurements

Figure 19 - Firestop Spacer with Attic Above

Show 4 more labels / short text on this page
Firestop Spacer · Above Ceiling · Firestop Spacer · Ceiling
Page 16 of the FMI MM63 user manual — venting installation
Page 16 · click to enlarge
Page 16

venting installation

Flashing installation (v6f-10dm or v12f-10dm) Determine the flashing to be used with the roof open ing chart. Slide flashing over pipe until base is flat against roof. Replace as many shingles as needed to cover exposed area and flashing base. Secure in position by nailing through shingles (see Figure 21). DO NOT NAIL THROUGH FLASHING CONE.

Terminations/Spark Arrestor The fireplace system must be terminated with the listed round top or chase terminations. In any case, refer to the installation instructions supplied with the termination.

FMI MM63 — venting installation diagram (page 16)
Fig. 21 · venting installation

Installing Flashing on a Metal Roof When installing the flashing on a metal roof, it is re quired that putty tape be used between the flashing and the roof. The flashing must be secured to the roof using #8 x 3/4" screws and then sealed with roof coating to prevent leakage through the screw holes. A roof coating must also be applied around the pe rimeter of the flashing to provide a proper seal.

FMI MM63 — venting installation diagram (page 16)
Fig. 22 · venting installation
FMI MM63 — venting installation diagram (page 16)
Fig. 23 · venting installation

Figure 23 - Termination

Figure 21 - Flashing Installation

Chase installations Instructions for chase installations are included with the chase style termination chosen. In a multiple chase installation, be sure to provide adequate dis tance between terminations to prevent smoke spill age from one termination to another. We suggest that terminations be separated at least 24", center to center and stacked at a vertical height difference of 18" (see Figure 24, page 17).

Storm Collar Installation (SC2-1) Place storm collar over pipe and slide down until it is snug against the open edge of the flashing (see Figure 22). Apply waterproof caulk around the perimeter of the collar to provide a proper seal.

FMI MM63 — venting installation diagram (page 16)
Fig. 24 · venting installation

Figure 22 - Storm Collar

Storm Collar

Page 17 of the FMI MM63 user manual — OPTIONAL Electrical connection Installation
Page 17 · click to enlarge
Page 17

venting installation

FMI MM63 — venting installation diagram (page 17)
Fig. 25 · venting installation

finishing fireplace Combustible materials, such as wallboard, gypsum board, sheet rock, drywall, plywood, etc. may not make direct contact with sides and top around the fire place face. See clearance requirements in Figures 8 and 9 on page 9. It is important that combustible ma terials do not overlap the face itself. Brick, glass, tile or other noncombustible materials may overlap the front face provided they do not obstruct essential openings. When overlapping with a noncombustible facing ma terial, use only noncombustible mortar or adhesive.

18" Min. Typ.

Masonry (precast) chimney Masonry Chimney may be used instead of the FMI Chimney System. Parts come in 14" Diameter and can be obtained by FMI PRODUCTS, LLC. See Ac cessories on page 35.

Figure 24 - Multiple Chase Installation

10 foot rule All flue gas outlet chimney terminations must extend a minimum of 3 feet in height above the highest point where it passes through the roof and must be at least 2 feet above the highest point of the roof that is within a horizontal distance of 10 feet (see Figure 25).

FMI MM63 — venting installation diagram (page 17)
Fig. 26 · venting installation

Figure 25 - 10 Foot Rule

OPTIONAL GAS LINE Installation

You may elect to add a vented decorative gas appli ance (gas log) to your Grand Meridian Fireplace. If so, follow the installation instructions from the Deco rative Gas Appliance manufacturer. Familiarize your self with requirements for installation as outlined by the National Fuel Gas Code, ANSI Z223.1/NFPA 54. This gas pipe provision should only be used on a decorative gas appliance.

You can route the gas piping practically anywhere in the firebox – the floor, back wall or side walls. You will just need a masonry drill; the instructions from the gas appliance manufacturer will be very straight forward. Fill in the holes you have drilled around the gas pip ing with the regular mortar. Follow the Gas Log manufacturer’s instructions.

OPTIONAL Electrical connection Installation

Like the gas line, electrical feed lines can be run through the floor, back wall, or side walls. Follow local building and electrical code requirements.

Page 18 of the FMI MM63 user manual — Supporting floor system Installation
Page 18 · click to enlarge
Page 18

Supporting floor system Installation

It is the ultimate responsibility of the installer to en sure that proper concrete slab supports are used.

For floors supported by I-Joists, the method of an chorage is illustrated in Figures 27 and 28, page 19. Figure 31, page 20 illustrates the general arrange ment of anchorage to floor framing. It is important to take into consideration that the load for the Grand Meridian Fireplace must be considered as additional dead load that will have to be supported by the floor framing. Additional floor joists or I-joists may be required as determined by the licensed de sign professional. The dead weights for the fireplace are noted in Table I. It is the task and responsibility of the general con tractor/installer to see that the proper reinforcement for weight loads are made by a licensed design pro fessional prior to the fireplace installation. As stated above, it is desirable to place additional framing for alignment of anchor rods. Refer to Figure 29, page 20 for anchor rod locations. Attach the firebox side wall anchors to steel sup port frame by inserting all-thread rods through holes on the bottom flange on the steel support frame as shown in Figure 32 and 33, page 21. Secure with two Ø 2" o.d. x Ø 9/16" i.d. x 0.10" Washers and two 1/2"-13 UNC Nuts.

FMI MM63 — Supporting floor system Installation diagram (page 18)
Fig. 27 · Supporting floor system Installation

For fireplace support foundations installed on con crete refer to Appendix I and II (pages 42 & 43) for specific instructions.

Rebar locations Lay-out the position of the fireplace and drill holes where the rebar will be located. Secure the #3 rebar 4 inches into the concrete foundation with ITW Epoxy or Simpson Epoxy. Follow manufacturer’s instruc tions for installation of rebar into slab.

Wood Floor Anchorage of fireplace to wood floor construction is required. Refer to Figure 29 on page 20 for anchor age dimensions. Four anchors are required to attach to the sub-flooring framing.

FMI MM63 — Supporting floor system Installation diagram (page 18)
Fig. 28 · Supporting floor system Installation

Crawl Space or Upper Floor: For installation of firebox over combustible crawl spaces or upper floors, anchorage of the firebox is required. Illustrations of examples of possible an chorage methods are shown in Figures 26 thru 28 depending upon the type of floor framing. Final meth od of anchorage is to be determined by licensed de sign professional. For conventional framing, where the floor joists are parallel with the sides of the firebox, the addition of floor joists to align with the anchor brackets allows the brackets to be directly connected to the floor joists. Note: Additional floor joists may be required to sup port the weight of the firebox and chimney. Where the floor joists run parallel to the front of the firebox, anchorage can be accomplished in like manner as shown in Figure 26 using blocking between the floor joist.

Figure 26 - Floor Joist Installation

Page 19 of the FMI MM63 user manual — Weight Determination
Page 19 · click to enlarge
Page 19

Supporting floor systems installation

FMI MM63 — Supporting floor systems installation diagram (page 19)
Fig. 29 · Supporting floor systems installation
FMI MM63 — Supporting floor systems installation diagram (page 19)
Fig. 30 · Supporting floor systems installation

Figure 27 - Floor Joist Installation Figure 28 - Floor Joist Installation

Weight Determination

The following are dead load weight estimates for the Grand Meridian Fireplace.

FMI MM63 — Weight Determination diagram (page 19)
Fig. 31 · Weight Determination

Table I Fireplace Model MM33 MM39 MM44 MM49 MM63 Fireplace Weight 835 lbs. 1,194 lbs. 1,250 lbs. 1,359 lbs. 1,704 lbs. Mortar, Rebar & Ready Mix Concrete 200 lbs. 350 lbs. 357 lbs. 364 lbs. 370 lbs.

Firebrick Lining 290 lbs. 333 lbs. 345 lbs. 356 lbs. 435 lbs.

Damper/Anchor Plate 17 lbs. 17 lbs. 17 lbs. 17 lbs. 21 lbs.

Steel Platform 89 lbs. 94 lbs. 96 lbs. 100 lbs. 132 lbs.

Other Weight Considerations: 1) Fireplace finished facing (surround): This information needs to be obtained from the contractor. 2) Weight of metal flue or Masonry Chimney System: See chimney manufacturer’s weight specifications. Some chimney systems can weigh up to 50 lbs per lineal foot.

FMI MM63 — Weight Determination diagram (page 19)
Fig. 32 · Weight Determination

Table II - Deflection Limits Construction L S or W D +L1

1 For wood structural members having a moisture content of less than 16 per cent at time of installation and used under dry conditions, the deflection resulting from L + 0.5D is permitted to be substituted for the deflection resulting from L + D. Note that FMI PRODUCTS, LLC cannot accept responsibility for structural floor support details. All drawings are presented as mere illustrations to indicate the presence of the underlying floor system. It is the responsibility of the general contractor/installer to consult with a local licensed design professional for guidance in building a proper floor support system.

Example Only

Page 20 of the FMI MM63 user manual — MM63 67" 28" 60" 23"
Page 20 · click to enlarge
Page 20

Supporting floor systems installation

FMI MM63 — Supporting floor systems installation diagram (page 20)
Fig. 33 · Supporting floor systems installation

Figure 29 - Anchorage Dimensions Figure 30 - Hardware

FMI MM63 — Supporting floor systems installation diagram (page 20)
Fig. 34 · Supporting floor systems installation

Figure 31 - Typical Anchorage Layout

combustible floor Installation

8" Metal Base (MMB63) The Metal Base (MMB63) ensures the minimum 8" clearance above combustible flooring is main tained with Grand Meridian Model MM63. A layer of 1/2" minimum Cement Board (Not Includ ed) is required on the top and mid section below as shown in Figure 32, page 21. The required sizes are shown in the table below.

Ember protector strips: Ember protector strips (included with Metal Base Kit) are required between the front of the Fireplace Hearth and Hearth Extension. A minimum thickness of 26 gauge metal strip at least 4" wide can be used. The length needs to extend 2 inches beyond each side of the fireplace opening. If two strips are used, make sure they overlap at least two inches in the middle. The strip is placed about 2" into the underside of the platform at the front (Figure 10, page 10). Note: When using an on-site constructed hearth ex tension, you may use a sand-cement grout between the hearth and extension instead.

1/2" Thick Cement Board Dimensions

Model A1 A2 B1 B2

MM63 67" 28" 60" 23"

Page 21 of the FMI MM63 user manual — A2
Page 21 · click to enlarge
Page 21

combustible floor installation

Materials included:

A layer of 1" thick Insulation Blanket (Included) is re quired on the top and mid-section of the Metal Base as shown in Figure 33. The required sizes are shown in the following table:

  • 8 - ⅜" Rebar x 12" Long
  • 4 - ⅜” Rebar x 6” Long
  • 4 - ⅜” Bolts x 2½” Long
  • 28 - Washer
  • 28 - Nuts
  • 4 - Floor Joist Brackets
  • 2 - Ember Protector Strips
  • 1 - Insulation Blanket

1/2" Thick Cement Board Dimensions Model A1 A2 MM33 37" 28" MM39 43" 28" MM44 48" 28" MM49 53" 28"

Place 1/2" cement board on top rails of platform (Not Included).

A1

Place 1” Insulation Blanket on top of cross members (Included).

Place Cement Board on top rails of platform (Not Included).

A2

A1

Place Insulation Blanket on top of cross-members (Included).

A2

Ember Protector Strips 26 ga. Sheet Metal

Ten (10) All-Thread Rods are secured to the top flange of the Metal Base with twenty (20) flat washers (2"OD x 9/16"ID x 0.10") and twenty (20) 1/2-13 UNC Nuts.

Anchor Bracket All-Thread Rods are secured to the bottom flange of the Metal Base with eight (8) flat washers (2”OD x 9/16”ID x 0.10") and eight (8) 1/2-13 UNC Nuts.

Ember Protector Strips 26 ga. Sheet Metal

Figure 32 - MMB63 Metal Base Assembly

Eight (8) All-Thread Rods are secured to the top flange of the Metal Base with sixteen (16) flat washers (2"OD x 9/16"ID x 0.10") and sixteen (16) 1/2"-13 UNC Nuts.

6" Metal Base (MMB33,MMB39, MMB44, and MMB49) The Metal Base ensures the minimum 6" clearance above combustible flooring is maintained.

Anchor Bracket All-Thread Rods are secured to the bottom flange of the Metal Base with eight (8) flat washers (2"OD x 9/16"ID x 0.10") and eight (8) 1/2-13 UNC Nuts.

Figure 33 - MMB33, MMB39, MMB44 and MMB49

Model MM33 MMB33 MM39 MMB39 MM44 MMB44 MM49 MMB49

Show 4 more labels / short text on this page
Grand Meridian · Use Metal Base · Metal Base Assembly · Model
Page 22 of the FMI MM63 user manual — Materials needed for installation:
Page 22 · click to enlarge
Page 22

Fireplace Installation

You will find that the Grand Meridian Fireplace is de signed to be completely assembled on-site, consist ing of interlocking precast parts. Included is a thin- set type mortar for bonding. The parts of the fireplace are made of FMI’s incredibly strong blend of specialty cement and a light weight aggregate.

Materials included:

MM33, MM39, MM44, MM49:

  • 8 - ⅜" Rebar x 28" Long
  • 8 - ⅜" Rebar x 12" Long
  • 1 - 50 lb. bucket Mortar
  • 20 - Small Wood Shims

MM63:

  • 10 - ⅜" Rebar x 36" Long
  • 10 - ⅜" Rebar x 12" Long
  • 2 - 50 lb. bucket Mortar
  • 20 - Small Wood Shims

The installation of an anchor plate/damper for either masonry chimney or pre-fabricated chimney is re quired but not supplied. See Accessories on page 33. The installation of a seismic strap kit is required but not supplied. See Accessories on page 33. An optional outside air kit can be used. See Acces sories on page 33. Refractory Firebrick Liners also need to be installed. These should be a minimum of 1⅛" thick. The liner will be applied within the walls and hearth area of the firebox. See Accessories on page 33.

Field Assembly Procedures Mixing the mortar – The mortar comes pre-mixed and should be dry. Be sure to use clean water and work it up into a mixture that is pasty but not lumpy. If it’s too thin and the surfaces don’t stay moist, the components will not adhere. Load the mixture into a standard grout bag. When applying, use about ½" thread of mortar. The mortar bead should be approximately ½" away from all edges. The mortar has a considerable amount of holding power so do not overload the components with too much mortar. Keep the components moist at all times by wiping them down with a clean wet sponge. Some mortar will “ooze out” when placing compo nents together, this is normal. Wipe excess away with a trowel. Do not cover component surfaces com pletely with mortar. Do not apply the mortar in thick bands even if the component you are working with is larger than the rest. You will want to apply “stripes” of mortar in these situations. Make sure components are level. Checking lev elness after each layer. It’s extremely important that you pay careful attention to how you are as sembling the Grand Meridian Fireplace since ev ery component builds on the next. If you have to make any kind of an adjustment, do not try to do it “by loading an opening” with mortar, this will only result in a fireplace that will not be plumb or level. Use wood shims instead. You will find these small wood shims supplied with the Fireplace and

Tools needed for installation:

One 4 ft. level •

  • Roto-hammer with ½" drill bit
  • Drill motor with mixer blade to mix Mortar
  • Two empty 5 gallon buckets to mix Mortar
  • One wheelbarrow
  • and shovel to mix concrete Grout bag
  • Triangular masonry trowel
  • Rubber hammer

Sponge and 2 water buckets to wipe down and • moisten parts prior to applying mortar

Materials needed for installation:

Epoxy for securing rebar in footing / foundation •

Three (3) - 90 lb. bags of ready mix concrete with • ¼" or smaller aggregate

Page 23 of the FMI MM63 user manual — MM33,39,44,49
Page 23 · click to enlarge
Page 23

fireplace installation

you can nudge them in between openings to achieve the precision you need in making component adjust ments. Once you have removed any shims, you will want to cover any gaps that may have resulted with the mortar.

FMI MM63 — fireplace installation diagram (page 23)
Fig. 35 · fireplace installation

Assembly Instructions 1) Place the hearth base on top of your non-combus tible floor or metal base. For concrete slabs, support ing floor needs to be rated at ASTM 90.

a) Combustible Floor Installations: Mix up a batch of mortar and adhere hearth slabs to the cement board (see Figure 32 & 33, page 21). All- thread rods should stick up through the holes on the hearth slabs. b) Non-combustible Floor Installations: Draw an outline of the hearth area based on the dimen sions shown in pages 4 and 5. Position Hearth slabs and mark rebar center locations. Drill 4 inches using Roto-hammer into concrete slab and secure the 8 pieces (10 pieces for MM63) of 12" long rebar with epoxy. See Figure 34 & 35. 2) Mix a batch of mortar and prepare Right Side Hearth bottom surface to be bonded as shown in Fig ure 36. 3) Align Right Side Hearth to the outline created. The overall width should allow for an approximate gap of 1/8" between slabs for the additional mortar to unite the remaining slab. Check for surface flatness, level if necessary.

Figure 35 - Positioning Hearth Base for MM63

FMI MM63 — fireplace installation diagram (page 23)
Fig. 36 · fireplace installation

1/2" MORTAR BEAD TYPICAL

Figure 36 - Preparing Hearth Base

4. Repeat step 3 for Left Side Hearth. 5) Before installing side walls, confirm placement of outside air kit (if required). This can be installed ei ther side depending on which side is accessible to outside combustion air (all diagrams in this manual show the combustion air inlet hole on the right side). Prepare side wall and rear wall mating surfaces with the prepared mortar and begin assembly as shown in Figure 37.
FMI MM63 — 1/2" MORTAR BEAD TYPICAL diagram (page 23)
Fig. 37

Side Wall shown prepared for Right Side Air Access. For Left Side, bead opposite side.

FMI MM63 — 1/2" MORTAR BEAD TYPICAL diagram (page 23)
Fig. 38

Figure 34 - Positioning Hearth Base For

MM33,39,44,49

Figure 37 - Preparing Side and Rear Wall Pieces

Page 24 of the FMI MM63 user manual — MM33,39,44,49
Page 24 · click to enlarge
Page 24

fireplace installation

6) Assemble the first layer as shown in Figure 38 and 39. Continue to the next layer sides and rear pieces, keeping components moist, mixing mortar as you need it and threading the mortar appropriately as you stack each section, one onto the next. Constant ly check for squareness and levelness while building each course of block. As you complete each piece, make certain that you adhere the mortar at each and every joint. See chart below for the number of layers for need for this step.

Begin with the smallest rear wall to the right side as shown below.

Layers MM33 2 MM39 3 MM44 3 MM49 3 MM63 3

Combustion Air Access Right or Left (Right shown).

Figure 39 - Layering walls and sides for MM63

MM63: Rear Walls are staggered on every row as shown in Figures 40.

Combustion Air Access Right or Left (Right shown).

Stagger positions of rear wall

Figure 38 - Layering walls and sides for

MM33,39,44,49

Figure 40 - Staggering walls and sides for MM63

Show 15 more labels / short text on this page
Apply mortar · Apply mortar · Grand Meridian · Number of · Model · Rear Wall (short) · Apply mortar · Rear Wall · Rear Wall (long) · Side Wall · Side Wall · Apply mortar · Apply mortar · Rear Wall (short) · Rear Wall (long)
Page 25 of the FMI MM63 user manual — fireplace installation
Page 25 · click to enlarge
Page 25

fireplace installation

7. Insert 28" long rebar (8 total, included with fire place) vertically through the cells, into the holes in the hearth, adjacent to the rebar and/or all-thread sticking up from the hearth (Figure 42). Mix approxi mately 2 cu. ft. of Ready-Mix Concrete (not included) and fill all cells in walls and rear of firebox completely (Figure 41).

Add rebar and fill all cells with concrete mix

Figure 43 - Attaching Downdraft Diverter and

10. Set the Lintel and Lower Rear Dome in place as shown in Figures 44. Check that all is level. If you need to make adjustments, use shims. Place one or more of these shims between the lowest wall com ponent and the top surface of the base plate. Once you are satisfied with the degree of levelness, you can address any gap that may have occurred with an appropriate amount of mortar.

Figure 41- Inserting Rebar and adding Ready

8. Attach Lower Seismic Straps to rebar closest to the front as shown in Figure 42.

12 inch rebar or all-thread

Figure 44 - Attaching Lower Rear Dome and

Figure 42 - Attaching Lower Seismic Straps

9. Install Downdraft Diverter and final row of Side Walls (Figure 43). All components must be level. Mix approximately 2 cu. ft. of Ready-Mix Concrete and fill all cells with Ready Mix Concrete mix.
Show 8 more labels / short text on this page
Downdraft Diverter · Final Side Walls · Side walls · Mix Concrete · Lower Rear Dome · Lintel · Lower Seismic Straps · Lintel
Page 26 of the FMI MM63 user manual — fireplace installation
Page 26 · click to enlarge
Page 26

fireplace installation

Note: Although you are cautioned to use mortar sparingly because it does have such holding power, you should look over the firebox assembly at the end and fill in any gaps, especially joint connections, with the mortar. Important: Adjustments can only be made while the mortar is still wet when correcting for squareness and leveling. 11) Assemble Lower Dome Sides as shown in Figure 46. The beveled face lines up with the inward angles of the lintel sides. Top surfaces should be level.

13. MM63 ONLY: Position Middle Domes so that outer faces are flush to the lower dome as shown in Figure 46. Carefully install Dome Middle Sides as shown in Figure 46.

Lower Dome Sides (Rating Plate faces inside)

Figure 46 - Attaching Middle Dome

Figure 45 - Attaching Lower Dome Sides As you are connecting each component, be certain you are following the instructions given previously for using mortar. Stop to look at the smoke dome side, front and rear walls to see that they are aligning cor rectly and that the surfaces are smooth and uniform. Make sure connections are covered with an adequate amount of mortar. Remember that you have the op tion of using shims but they must be removed and any holes filled. Make any adjustments to the fire place alignment before continuing to the next step. 12) Assemble Upper Dome and Dome Sides as shown in Figure 46. Check your assembly here. If things are proceeding as they should be, the finished top surface should be flat and level.

14) Finally, set the Dome Top into position (Figure 47, page 27). Be sure that it is flush in every direc tion as you place it on the crest of the smoke dome wall assembly. After this is done, proceed to section on Installing Damper and Chimney System on page 28. Note: The chimney hole on the Dome Top is not centered from front to back - it should be offset closest to the rear of the fireplace (see Figure 46).

Figure 45 - Attaching Upper Dome & Sides

Show 4 more labels / short text on this page
Upper Dome · Dome Side · Upper Dome Sides · Upper Dome Front/Rear
Page 27 of the FMI MM63 user manual — MM63
Page 27 · click to enlarge
Page 27

fireplace installation

Dome Top center of chimney hole is offset towards the rear.

MM33

Center of chimney hole is offset towards the rear.

MM39,44,49

Center of chimney holes are offset towards the rear.

MM63

Figure 46 - Attaching Middle Dome

Show 6 more labels / short text on this page
10" · 13 ½" · 10" · 12 ½" · 10" · 12 ½"
Page 28 of the FMI MM63 user manual — fireplace installation
Page 28 · click to enlarge
Page 28

fireplace installation

Installing DampeR / Anchor Plate (MM12AP) for pre-fabricated chimney system All chimney systems must be installed with an inte grated Damper System / Anchor Plate installed on top of the fireplace. Installers are cautioned to put the chimney system together exactly as instructed in the Venting Installation on page 12. Any variations may have serious consequences resulting in an accident or malfunction. If instructions are not followed, the warranty on the product will become null and void. Apply a 1" thick ceramic fiber blanket (Included) to the bottom of the anchor plate. Apply balance of gasket cement in a ¼" bead on top of smoke dome approximately 1½" around periphery of chimney hole. Install damper assembly on top of unit pressing damper and insulation blanket into ce ment (Figure 47). Secure with four 3/16" X 1¾" ma sonry screws (included).

Place chimney adapter onto top of damper plate and center in opening using gasket supplied with adapt er. Attach adapter with screws supplied by carefully drill ing holes into damper plate. Attach damper chain stop on center rear of lintel 3” (three inch) vertical from opening using (3) #8 ce ment fasteners.

Secure with four 1/4" x 1-1/4"masonry fastener.

1" ceramic fiber blanket under Anchor Plate.

1/4" bead of gasket cement

Figure 47 - Installing Anchor Plate

Page 29 of the FMI MM63 user manual — firebrick installation
Page 29 · click to enlarge
Page 29

firebrick installation

er edge. The space behind does not have to be filled (Figure 48).

Refractory Firebrick lining must be installed. There are two options. You can obtain pre-fabricated Modu lar Firebrick Liner from FMI PRODUCTS, LLC (see Accessories on page 33) or custom firebrick lining can be installed.

Custom Firebrick Lining Custom Firebrick lining is can be obtained by FMI PRODUCTS, LLC. If a custom firebrick pattern is desired, it is required that the masonry fire rated bricks be a minimum of 1⅛" thick. The pattern for the firebrick lining is exclusively your choice. Before you install the lining, remember to consider any holes your contractor may need to drill for gas, electrical or combustion air kit access holes. Please use a certified mason to lay-in the brick. He will follow the proper instructions from the fireplace liner manufacturer and also understand the type of adhesive or cement he is to use. Make sure the fireplace is installed with the finished firebrick floor of the fireplace so that it is at least 11" above the combustible floor system. Disclaimer: FMI PRODUCTS, LLC wishes to ex press that as the manufacturer of the Grand Merid ian Fireplaces, they cannot take any liability or re sponsibility for the way the firebrick or the firebrick mortar performs. It is not unusual in the course of the life of the firebrick, or the firebrick mortar, for heat stress cracks to appear. FMI PRODUCTS, LLC cannot be responsible for this and other wear and tear to the firebrick and mortar.

Modular Firebrick Lining If using FMI PRODUCTS, LLC Module Firebrick Lin ers, simply use an extra bag of the mortar we sup ply. Install Hearth panel first, rear panel next and side panels last. Consider if brackets for grates will be required also if pre-drilling is required for gas lines, electrical or if the outside combustion air kit is to be installed. The rear Liner Panel is straight from the bottom to the top front edge of the Downdraft Divert

Area behind Rear Firebrick Liner Panel can remain empty

Figure 48 - Postion of Rear Panel

Page 30 of the FMI MM63 user manual — Owner’s Operation & Precautions
Page 30 · click to enlarge
Page 30

Operation and maintenance guidlines

Fireplace Grates To complete your fireplace installation, a fireplace grate will be required for safe operation. The fireplace grate can be obtained from FMI PRODUCTS, LLC (see Accessories on page 33) or if choosing an alter nate, it must be sized to 50% of the hearth maximum. Additionally. A fireplace screen must be installed for safety. Screens

Glass DoorS IMPORTANT: Only Crown-Breckinridge or McKenzie-Pendelton Doors by Portland-Willamette (www.portwill.com) are approved for use with this fireplace. For installation Instructions, see separate instruc tions included with doors. Glass doors are optional with the fireplace. When fireplace is in operation, doors must be fully opened or fully closed position only or a fire hazard may be created (see Figure 49). A fireplace equipped with glass doors operates much differently than a fireplace with an open front. A fire place with glass doors has a limited amount of air for combustion. Excessive heat within the fireplace can result if too large a fire is built or if combustion air gate is not completely open. The following tips should be fol lowed to assure that both the fireplace and glass door retain their beauty and function properly. Both the flue damper and glass doors must be fully opened before starting fire. This will provide sufficient combustion air and maintain safe temperatures in firebox. IMPORTANT: The glass must be allowed to warm slowly and evenly. The tempered glass will withstand a gradual temperature rise to 375 °F, without sustaining any damage. Termperatures as high as this or higher are not likely to occur with normal use. Such materials as pitch/wax laden logs, very dry mill end lumber and large amounts of paper or cardboard boxes can create an excessively hot fire and should not be burned in this fireplace. Always keep the fire well back from the doors and never allow flames to contact the glass.

Figure 49 - Bi-Fold Glass Doors

Cleaning Glass Clean glass with any commercial glass cleaner or soap and water. Do not use any abrasive material to clean glass. Do not clean glass with any cool water if glass is still hot from the fire and smoke.

Owner’s Operation & Precautions

First Lighting of the Grand Meridian – After con struction is completed, all elements of the fire place and chimney system must be complete ly dry. This means that the unit must stand without any firing for a minimum of 28 days. Only after that period of time can a first lighting take place. The first fire must be small and well-controlled, started with a small amount of kindling. Add no more than eight pounds of wood, preferably small logs not more than 3” (three inches) in diameter. You will probably burn no more than three to four of these small logs. Do not let the fire burn for more than one hour. After this first lighting – when the fireplace has started to “cure” Do not set another fire for at least 24 hours.

Show 4 more labels / short text on this page
Doors Fully Closed · Fireplace Front · Doors Fully Opened · Fireplace Front
Page 31 of the FMI MM63 user manual — Operation and maintenance guidlines
Page 31 · click to enlarge
Page 31

Operation and maintenance guidlines

Second Lighting – Start the fire slowly and gradually as you did with the first lighting, but this time you can burn up to ten pounds of firewood, probably four to five logs that are 3" in diameter. With the second light ing you can let the fire burn two hours – no more. After First and Second Lighting – When the fireplace has been properly cured with 1st and 2nd lighting, you will be able to add a full fuel load to the fire place which is about 10 to 15 pounds of firewood at any given time. Consider that this typical fuel load is three to four dry hardwood logs that are about 6" ) to 8" in diameter. Without a grate for your firewood to rest on, you can not get the air flow you need under the fire which makes for a hotter, more satisfying fire. Do not “over burn” – Always remember, your Grand Meridian fireplace is an elegant addition to your home. It is not an indoor incinerator! If you start to use the fireplace and begin a routine of “over burning,” you can permanently and unalterably damage the unit. Under no circumstances should you be burning household trash, including chemicals and combus tibles, cardboard boxes, your office papers, scrap lumber or stray branches from your yard, particularly pine.

kindling, then the softer wood and finally, the harder wood logs. As the fire burns, you can carefully lay ad ditional logs on the flame, but make sure you place them gently without forcing them into the opening.

Annual Fireplace Maintenance Your fireplace and chimney require seasonal and monthly tune-ups”. Like any piece of well-built equip ment, the Grand Meridian Fireplace and chimney needs routine maintenance. The manufacturer recommends that inspection of the fireplace and chimney take place on a monthly basis during the heating season. Start at the top, looking for birds’ nests, leaves or any other obstruc tions. Also check the spark arrestor, for creosote or soot build-up. Twice a year, you will want to clean the firebox and chimney yourself or hire a professional chimney sweep to do the job for you. If you elect to do it yourself, use a plastic, wood or steel brush for the inside of the chimney. For the spark arrestor, scrub with a wire brush. To dismantle the chimney cap for cleaning of the flue, unscrew the four screws that hold it in place. For cleaning access from below, open the damper in the firebox. It is best to use a flexible handle chimney cleaning brush made especially for the job. If your fireplace system has any offset chimney sec tions, start cleaning with the flexible brush from the top of the section downward to the elbow. Then clean from the firebox up to the offset/return section. Be sure that you have covered the floor of the fire place and out to the hearth with a damp sheet that has been taped securely in place. When all the soot has settled, remove the sheet and vacuum up – don’t sweep the excess soot. Good old-fashioned “elbow grease” is enough to re move the extraneous matter from the inside of the firebox and chimney. Never use any chemical clean ers as their residue could introduce a fire hazard af ter the task is completed. Outside Inspection – During your once a month in spection of the firebox and chimney, make it a point to also check the outside of the chimney, the metal

Starting a Fire and Basic Operation Before starting a fire in your fireplace, open the damp er to its’ fully open position. Crumple some paper and place it on the log grate. Use some soft, dry wood as kindling and put it on top of the paper. Place some small logs or split logs atop the paper and kindling. Finish off the fuel load with a couple of hardwood logs or split logs – oak or hickory. Check to see that you’re stacking the logs so that they will fall inside the grate as they burn. To get the most out of your wood, it is recommend ed that you let it set and completely dry out for nine months to a year. When you are satisfied with the arrangement of your wood load, light the paper which in turn will ignite the

Page 32 of the FMI MM63 user manual — Replacement Parts
Page 32 · click to enlarge
Page 32

Operation and maintenance guidlines

Continued flashing and weather seals that surround it. If you find any cracks or openings around screws or nails, seal them to avoid any roof or chimney chase leaks.

Removal of Creosote and Soot Formation – Creo sote vapors are known to form in the relatively cool chimney flues of slow burning fires, hence, creosote residue collects on the flue lining. Because of soot and creosote build-up, it is recommended that the fireplace and chimney cleaning be done twice a year. In colder climates, cleaning should be done more of ten. Always allow the fireplace to completely cool before you work on it, which means, of course, shutting off all gas and electrical connections, also. Be certain that you use only solid fuel in your fire place. You may use a natural or LP gas log lighter as a method to start your wood fire. The flue damper must be in the OPEN position when ever there is heat in the fireplace.

SURFACE CRACKS The Grand Meridian fireplaces are manufactured us ing high quality materials. During the drying process, surface cracking may occur. These small cracks (un der 1/16” will not effect the fireplace safety or per formance). During the assembly process, fill surface cracks with thin-set mortar and brush when drying for a smooth surface finish.

Technical Service You may have further questions about installation, op eration, or troubleshooting. If so, contact FMI PROD UCTS, LLC at 1-866-328-4537.

When calling please have your model and serial num bers of your fireplace ready. You can also visit our web site at www.fmiproducts.com

Replacement Parts

If this product is missing a part or has a broken com ponent, please do not return it to the store. Call FMI PRODUCTS, LLC at 1-866-328-4537 to answer questions and replace parts under warranty. Note: Use only original replacement parts. This will protect your warranty coverage for parts replaced under warranty.

  • When calling, have ready:
  • your name
  • your address
  • model and serial numbers of your fireplace
  • how fireplace was malfunctioning
  • purchase date
Page 33 of the FMI MM63 user manual — accessories
Page 33 · click to enlarge
Page 33

accessories

Purchase these accessories from your local dealer. If they can not supply these accessories, call FMI PRODUCTS, LLC at 1-866-328-4537 for referral information. You can also write to the address listed on the back page of this manual.

Mortar - 50 lb bucket MM525

4" outside air kit MM4ak

damper / anchor plate kit mm12ap - For use with FMI Chimney Systems

Brick Panels MM33SHBL - Herringbone MM33FRBL - RunnING bonD MM39SHBL - Herringbone MM39FRBL - RunnING bonD MM44SHBL - Herringbone MM44FRBL - RunnING bonD MM49SHBL - Herringbone MM49FRBL - RunnING bonD MM63SHBL - Herringbone MM63FRBL - RunnING bonD

Grates MMG3 - fits MM33 & MM39 MMG4 - Fits MM44 MMG5 - Fits MM49 MMG6 - Fits MM63

screen Assemblies MMS1 - Fits MM39 & MM44 MMS2 - Fits MM49 & MM63 MMS3 - Fits MM33

Seismic strap kit MM115

metal base kit MMB33 MMB39 MMB44 MMB49 MMB63

Show 4 more labels / short text on this page
Herringbone · Running Bond · Masonry Arch MMARC · ember protector 20093
Page 34 of the FMI MM63 user manual — accessories
Page 34 · click to enlarge
Page 34

accessories

Double Wall Pipe 12-12DM, 18-12DM, 24-12DM, 36-12DM AND 48-12DM

30° Offset and Return 30E-12DM

Roof Flashing V6F-10DM - 0 to 6/12 Pitch V12F-10DM - 6/12 to 12/12 Pitch

Round ToP TErminations RLT-12D

SQUARE CHASE-TOP TERMINATION STL-12D STL-12DMP - Black

Storm Collar SC2-1 · Firestop Spacer FS-10 · Chimney support 12S-12dm

Page 35 of the FMI MM63 user manual — accessories
Page 35 · click to enlarge
Page 35

accessories

Continued Masonry (Precast) Chimney 14" Diameter MCLS814K - 12 Sections, 8" each (8 ft total) MCLs814P - 6 Sections, 8” each (4 ft total) MCL814 - Inner Liner MCS814 - Outer Liner MCL414 - Inner Liner, 4" High (Starter) mcsbl814 - Brick Ledge mcsos814 - Offset Elbow Section mc14ap - Anchor Plate / Damper

Page 36 of the FMI MM63 user manual — Parts Models MM39, MM44 and MM49
Page 36 · click to enlarge
Page 36

Parts Models MM39, MM44 and MM49

FMI MM63 — Parts Models MM39, MM44 and MM49 diagram (page 36)
Fig. 39 · Parts Models MM39, MM44 and MM49

See Page 16 thru 18 for combustible floor and framing anchoring

Page 37 of the FMI MM63 user manual — † ITEMS INCLUDED IN THE MM12AP*
Page 37 · click to enlarge
Page 37

Parts This list contains replaceable parts used in your firebox. When ordering parts, follow the instructions listed under Replacement Parts on page 32 of this manual.

FMI MM63 — † ITEMS INCLUDED IN THE MM12AP* diagram (page 37)
Fig. 40
FMI MM63 — † ITEMS INCLUDED IN THE MM12AP* diagram (page 37)
Fig. 41

11 125086-01 RATING PLATE 1 12 125179-01† INSULATION BLANKET

SIDE WALL (with Ø4" Outside Combus tion Air Hole)

† ITEMS INCLUDED IN THE MM12AP*

# items included in the MM115* § items included in METAL BASE KIT (iTEM 16)* * ITEMS NOTED ARE SOLD SEPARATELY

ITEMS INDICATED AS “NOT SUPPLIED” CAN BE OBTAINED FROM YOUR LOCAL HARDWARE STORE.

Page 38 of the FMI MM63 user manual — Parts Models MM33
Page 38 · click to enlarge
Page 38

Parts Models MM33

Combustible Floor Systems Non-Combustible Floor Systems

FMI MM63 — Parts Models MM33 diagram (page 38)
Fig. 42 · Parts Models MM33
FMI MM63 — Parts Models MM33 diagram (page 38)
Fig. 43 · Parts Models MM33

See Page 16 thru 18 for combustible

floor and framing anchoring

illustrations.

Page 39 of the FMI MM63 user manual — 125178-01 § INSULATION BLANKET 1
Page 39 · click to enlarge
Page 39

Parts This list contains replaceable parts used in your firebox. When ordering parts, follow the instructions listed under Replacement Parts on page 32 of this manual.

ITEM PART NUMBER DESCRIPTION QTY 1 MFP33-1 HEARTH (Left or Right) 2 2 MFP33-2 REAR WALL 2 3 MFP33-3 SIDE WALL 5 3A MFP33-3A SIDE WALL (with Ø4″ Outside Combustion Air Hole) 1 4 MFP33-4 DowNDRaFT DIVERTER 1 5 MFP33-5 DOME REAR - LOWER 1 6 MFP33-6 LINTEL 1 7 MFP33-7 DOME SIDE - LOWER 2 8 MFP33-8 DOME SIDE - MIDDLE 2 9 MFP33-9 DOME TOP FOR 12″ FMI PIPE 1 10 MFP33-10 DOME FRONT/REAR - MIDDLE 2 12 125086-01 RATING PLATE 1 13 MM12AP* Ø12″ DAMPER / ANCHOR PLATE --- 14 125179-01† INSULATION BLANKET --- 15 MM4AK* Ø4″ OUTSIDE AIR KIT --- 16 MMB33* STEEL SUPPORT PLATFORM 6″ HIGH 1 17 NOT SUPPLIED CEMENT BOARD --- NOT SHOWN

125178-01 § INSULATION BLANKET 1

† ITEMS INCLUDED IN THE MM12AP * ITEMS NOTED ARE SOLD SEPARATELY § items included in METAL BASE KIT (iTEM 16)*

ITEMS INDICATED AS “NOT SUPPLIED” CAN BE OBTAINED FROM YOUR LOCAL HARDWARE STORE.

Page 40 of the FMI MM63 user manual — Parts Models MM63
Page 40 · click to enlarge
Page 40

Parts Models MM63

Combustible Floor Systems Non-Combustible Floor Systems

FMI MM63 — Parts Models MM63 diagram (page 40)
Fig. 44 · Parts Models MM63

See Page 16 thru 18 for combustible

floor and framing anchoring

illustrations.

Page 41 of the FMI MM63 user manual — 125178-05 INSULATION BLANKET 1
Page 41 · click to enlarge
Page 41

Parts This list contains replaceable parts used in your firebox. When ordering parts, follow the instructions listed under Replacement Parts on page 32 of this manual.

ITEM PART NUMBER DESCRIPTION QTY 1 MFP63-1 HEARTH (Left or Right) 2 1A MFP63-1A HEARTH CENTER 1 2 MFP63-2 REAR WALL (2 PIECES) 3 sets 3 MFP63-3 SIDE WALL 7 3A MFP63-3A SIDE WALL (with Ø4″ Outside Combustion Air Hole) 1 4 MFP63-4 DOWNDRAFT DIVERTER (2 PIECES) 1 set 5 MFP63-5 DOME REAR - LOWER 1 6 MFP63-6 LINTEL 1 7 MFP63-7 DOME SIDE - LOWER & UPPER 4 8 MFP63-8 DOME SIDE - MIDDLE 2 9 MFP63-9F DOME TOP FOR DUAL 12″ FMI PIPE (2 PIECES) 1 set 10 MFP63-10 DOME FRONT/REAR - MIDDLE 2 11 MFP63-11 DOME FRONT/REAR - UPPER 2 12 125086-01 RATING PLATE 1 13 MM12AP* Ø12″ DAMPER / ANCHOR PLATE 2 14 125179-01† INSULATION BLANKET 2 15 MM4AK* 4 INCH DIA. OUTSIDE AIR KIT 1 16 MMB63* STEEL SUPPORT PLATFORM 8″ HIGH 1 17 NOT SUPPLIED CEMENT BOARD 1 NOT SHOWN

125178-05 INSULATION BLANKET 1

† ITEMS INCLUDED IN THE MM12AP* * ITEMS NOTED ARE SOLD SEPARATELY § items included in METAL BASE KIT (iTEM 16)*

ITEMS INDICATED AS “NOT SUPPLIED” CAN BE OBTAINED FROM YOUR LOCAL HARDWARE STORE.

Page 42 of the FMI MM63 user manual — Appendix I
Page 42 · click to enlarge
Page 42

MINIMUM SPECIFIED COMPRESSIVE STRENGTHa (f’c)

Porches, carport slabs and steps exposed to the weather, and garage floor slabs 2,500 3,000d,e,f 3,500d,e,f

shall consist of a minimum of 6 inches thick reinforced concrete slab. The concrete strength and durability shall comply with Sections

TYPE OR LOCATION OF CONCRETE CONSTRUCTION Negligible Moderate Severe

Basement walls, foundations and other concrete not exposed to the weather 2,500 2,500 2,500c

Basement slabs and interior slabs on grade, except garage floor slabs 2,500 2,500 2,500c

work exposed to the weather 2,500 3,000d 3,000d

required in Table R402.2 of the International Residential Code (IRC). Concrete subject to moderate or severe weathering as indicated

in Figure R301.2(3) of the International Residential Code (IRC) shall be air entrained as specified in Table R402.2 of the International

d. Concrete shall be air-entrained. Total air content (percent by volume of concrete) shall be not less than 5 percent or more than

f. For garage floors with a steel troweled finish, reduction of the total air content (percent by volume of concrete) to not less than

c. Concrete in these locations that may be subject to freezing and thawing during construction shall be air-entrained concrete in

For installations regulated by the International Residential Code, the support foundation for the fireplace installed on concrete shall

Residential Code (IRC). The maximum weight of fly ash, other pozzolans, silica fume, slag or blended cements that is included in

concrete mixtures for garage floor slabs and for exterior porches, carport slabs and steps that will be exposed to deicing chemicals

For installations regulated by the International Building Code (IBC), the support foundation for the fireplace installed on concrete

f’c, shall be as

shall not exceed the percentages of the total weight of cementitious materials specified in Section 4.2.3 of ACI 318. Materials

3 percent is permitted if the specified compressive strength of the concrete is increased to not less than 4,000 psi.

TABLE R402.2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE

consist of a minimum of 6 inches thick reinforced concrete slab. The minimum specified compressive strength of

produce concrete and testing thereof shall comply with the applicable standards listed in Chapter 3 of ACI 318.

Appendix I

e. See Section R402.2 for maximum cementitious materials content.

Basement walls, foundation walls, exterior walls and other vertical concrete

1903, 1904 and 1905 of the International Building Code (IBC).

b. See Figure R301.2(3) for weathering potential.

accordance with Footnote d.

a. Strength at 28 days psi.

7 percent.

used to · Weathering Potentialb

Page 43 of the FMI MM63 user manual — Appendix II
Page 43 · click to enlarge
Page 43

b. Lines defining areas are approximate only. Local conditions may be more or less severe than indicated by region classification. A

severe classification is where weather conditions result in significant snowfall combined with extended periods during which there is

FMI MM63 — FIGURE R301.2(3) WEATHERING PROBABILITY MAP FOR CONCRETE diagram (page 43)
Fig. 45

FIGURE R301.2(3) WEATHERING PROBABILITY MAP FOR CONCRETE

a. Alaska and Hawaii are classified as severe and negligible, respectively.

Appendix II

little or no natural thawing causing deicing salts to be used extensively.

Page 44 of the FMI MM63 user manual — FMI PRODUCTS, LLC LIMITED WARRANTIES
Page 44 · click to enlarge
Page 44

Warranty

KEEP THIS WARRANTY

Model (located on product or identification tag)

Serial No. (located on product or identification tag)

Keep receipt for warranty verification.

FMI PRODUCTS, LLC LIMITED WARRANTIES

New Products FMI PRODUCTS, LLC warrants all Grand Meridian Fireplaces to be free from defects in materials that adversely affect fireplace performance for a period of ten (10) years from the date of purchase, subject to the terms and conditions of this limited warranty. FMI PRODUCTS, LLC does not warrant accessory chimney, outside air ducts, gas control or burner system, ceramic logs, and devices not manufactured by FMI PRODUCTS, LLC. Valves and electronic parts are only covered for one year parts and labor per the log set manufacturer’s warranty. This warranty covers only products manufactured by FMI PRODUCTS, LLC, specifically the modular concrete firebox, and NO WARRANTY, EXPRESS OR IMPLIED, EXTENDS TO ANY OF THE HARDWARE, FOUNDATION, VENTING, DUCTS, OR ACCESSORIES. THIS WARRANTY DOES NOT COVER DRAFTING, SMOKING, OR SOOTING OF THE FIREPLACE SYSTEM. Factors beyond the manufacturer’s control may affect drafting, smoking, and sooting, FMI PRODUCTS, LLC cannot guarantee these aspects of performance. If a component is found to be defective under the terms of this warranty, the party this warranty is extended to shall notify FMI PRODUCTS, LLC, 2701 S. Harbor Blvd. Santa Ana, CA 92704 in writing, by registered mail, within thirty (30) days following the discovery of the defect within the warranty period. The letter shall contain (1) the date of purchase; (2) place of purchase; (3) address of installation; (4) name, address and phone number of the homeowner; and (5) a brief description of the defect. FMI PRODUCTS, LLC, or any entity thereof, is not responsible for any labor costs or indirect costs incurred for the replacement of defective components. FMI PRODUCTS, LLC is not responsible for misuse or mishandling of component parts. Nothing in this warranty makes FMI PRODUCTS, LLC, or any entity thereof, liable in any respect for any injury or damage to the building or structure in which the fireplace has been installed or to the persons or property therein arising out of the use, misuse, or installation of properly manufactured FMI PRODUCTS, LLC product. FMI PRODUCTS, LLC, OR ANY ENTITY THEREOF, SHALL NOT BE HELD LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES OR EXPENSES ARISING OUT OF THE USE OF THE FIREPLACE. ALL SUCH DAMAGES AND EXPENSES ARE HEREBY EXCLUDED. This warranty is null and void when the fireplaces are not installed pursuant to the installation instructions provided by FMI PRODUCTS, LLC and local building codes have not been followed completely. This warranty applies only to those fireplaces installed in the continental United States, Hawaii, Alaska and Canada. If any part of this warranty is found to be unenforceable,, the remaining parts shall remain in force and effect. FMI PRODUCTS, LLC HEREBY DISCLAIMS ALL GUARANTEES AND WARRANTIES, EXPRESS OR IMPLIED, BEYOND THE WARRANTIES SET FORTH HEREIN. CUSTOMER SERVICE & PARTS REPLACEMENT: Parts and accessories may be purchased from your local dealer. Additional information is available from FMI PRODUCTS, LLC. Accessory orders will be accepted by mail, or you may call to order Monday through Friday from 8:00 a.m. to 5:00 p.m. (Central Standard Time) at: (800) 328-4537.

Please complete the following information for future reference and warranty verification:

2701 S. Harbor Blvd. Santa Ana, CA 92704

125160-01 Rev. A 12/09

1-866-328-4537 www.fmiproducts.com

Date Purchased

Ask about the FMI MM63

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the FMI MM63

Be the first to ask — other owners or our team will answer.

Original document

FMI MM63 manual PDF

44 pages·2.6 MB·Indoor Fireplace·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…