PFS ®
US C
ICC-ES #ESR-2542
(V)GM36, (V)GM42 AND (V)GM50 Series and WCM-36G,
WCM-42G and WCM-50G Wood Burning Masonry Fireplaces with Insulation
SAVE THIS BOOK This book is valuable. In addition to instructing you on how to install and maintain your appliance, it also contains information that will enable you to obtain re- placement parts or accessory items when needed. Keep it with your other important papers.
This fireplace is approved for use as a wood burning fire- place or for use with a vented gas log approved to ANS Z21.60 or Z21.84 standards or for use with a vent-free gas log heater approved to ANS Z21.11.2 standard.
This wood burning fireplace complies with UL127-CN/ ULC-S610-N87 standard as a FACTORY BUILT APPLI- ANCE.
FOR CANADA: The authority having jurisdiction (such as the municipal building department, fire department, etc.) should be contacted before installation to deter- mine the need to obtain a permit.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
For more information, visit www.fmiproducts.com

Table of Contents Safety 2 Specifications 3 Fireplace Installation 6 Venting Installation 8 Optional Gas Line Installation 13 Brick Installation 14
Glass Door Installation 29 Operation and Maintenance Guidelines 31 Technical Service 33 Replacement Parts 33 Parts 34 Accessories 37 Safety
ponents, doors, air inlet system and damper control. b. Use of any component part not manu-
factured or approved by FMI PROD- UCTS, LLC in combination with a FMI PRODUCTS, LLC fireplace system. Proper installation is the most important step in ensuring safe and continuous operation of the fireplace. Consult the local building codes as to the particular requirements concerned with the installation of all factory built fireplaces.
This fireplace is not intended to be used as a substitute for a furnace to heat an entire home. Use for supplemental heat only.


14 1/2" 22 1/2"
19 13/16" (Ref.)
3 1/2" 9 1/2" 10 1/2"
7 1/4" 11" 15 1/4"


22 3/4" 30 1/2"
23 13/16" (Ref.)
1 5/16" 41 3/8"
3 1/2" 9 1/2" 10 1/2"
42" 51 1/8" 4 1/2"



23 13/16" (Ref.)
3 1/2" 9 1/2" 10 1/2"

selecting location To determine the safest and most efficient location for the fireplace, you must take into consideration the following guidelines: 1. The location must allow for proper clear- ances (see Figures 4 and 5). 2. Consider a location where fireplace will not be affected by drafts, air conditioning ducts, windows or doors. 3. A location that avoids cutting of joists or roof rafters will make installation easier. 4. An outside air kit is available with this fireplace (see Optional Outside Air Kit on page 8).
Framing 1. Frame opening for fireplace using dimen- sions shown in Figures 4 and 5. 2. If fireplace is to be installed directly on carpeting, tile (other than ceramic) or any combustible material other than wood flooring, fireplace must be installed upon a metal or wood panel extending full width and depth of fireplace. 3. Set fireplace directly in front of this open- ing and slide unit back until nailing flanges touch side framing. 4. Check level of the fireplace and shim with sheet metal if necessary. 5. Before securing fireplace to prepared framing, ember protector (provided) must be placed between hearth extension (not supplied) and under bottom front edge of fireplace to protect against glowing embers falling through. If fireplace is to be installed on a raised platform, a Z-type ember pro- tector (not supplied) must be fabricated to fit your required platform height. Ember protector should extend under fireplace a minimum of 1 1/2". Ember protector should be made of galvanized sheet metal (28 gauge minimum to prevent corrosion. 6. Using screws or nails, secure fireplace to framing through flanges located on sides of fireplace.
Minimum clearance to combustibles Back and sides of fireplace 1 1/2" min.* Front of fireplace 48" min. Floor** 0" min. Perpendicular wall to opening 18" min. 36" Models 12" min. Top spacers 0" min. Mantel clearances see Mantels, page 7 Chimney outer pipe surface 2" min. 36" Model 1" min. * Not required at nailing flanges ** See step 2 of Framing
Minimum/Maximum Chimney Height for Residential Installation Minimum height of chimney, measured from base of fireplace to flue gas outlet of termina- tion, is 16 feet for straight flue or a flue with one elbow set. Maximum distance between elbows is 6 feet. For systems with two elbow sets, minimum height is 22 feet. Maximum height of any system is 50 feet. This measure- ment includes fireplace, chimney sections and height of termination assembly at level of the flue gas outlet (see Figure 15, page 11).
67.125"
58.125"
51.25" (42" Models) 45.25" (36" Models)
30.125"
28.250" (36" Models)
61" (36" Models) Maintain 1 1/2" Clearance at Sides and Back of Fireplace
1 1/2" Clearance Not Required at Nailing Flanges
92" (42" Models) 86.5" (36" Models)

Hearth Extension A hearth extension projecting a minimum of 20" in front of and a minimum of 12" beyond each side of fireplace opening is required to protect combustible floor construction in front of fireplace. Fabricate a hearth extension using a material which meets the following specifications: a layer of noncombustible, inorganic material having a thermal conduc- tivity of K=0.84 BTU IN/FT, HR. F (or less) at 1" thick. For example, if the material selected has a K factor of 0.25, such as glass fiber, the following formula would apply: 0.25 x 1.0" = 0.30" thickness required 0.84 Thermal conductivity "K" of materials can be obtained from manufacturer or supplier of noncombustible material. If hearth extension is to be covered, use noncombustible mate- rial such as tile, slate, brick, concrete, metal, glass, marble, stone, etc. Provide a means to prevent hearth extension from shifting and seal gap between fireplace frame and hearth extension with a noncombustible material (see Figure 6).
Mantels A mantel may be installed if desired (see Figure 7). Woodwork such as wood trims, mantels or any other combustible material projecting from front face must not be placed within 12" (36" Models) or 18" (42/50" Models) of fireplace opening. Combustible materials above 12" (36" Models) or 18" (42/50" Models) and projecting more than 1 1/2" from fireplace must not be placed less than 15" (36" Models) or 21" (42/50" Models) from the top opening of the fireplace (NFPA STD 211, Sec. 7-3.3.3). Mantels or any other combustible material also may come up to side edge of black metal face of fireplace as long as projections from front face fall within limit shown in Figure 7.

33° Combustible Material Must Not Overlap Front Face 12" - 36" Models 18" - 42/50" Models
Combustible Material

Optional Outside air Kit (Model ak4/ak4f) The installation of an outside air kit should be performed during the rough framing of the fireplace due to the nature of it's location. Outside combustion air is accessed through a vented crawl space (AK4F) or through a sidewall (AK4).
The maximum height for the air vent can not exceed 3 feet below the flue gas outlet of the termination.
Secure to Collars with Metal Tape, Screws or Straps (Min. of 1/4" x 20" in size)
Air Inlet Location Must Allow For Bushes or Snow
* The lineal gain for the terminations is mea- sured to the flue gas outlet height.
15" Galvanized Outer Pipe
Hemmed End 12 3/8" Stainless Inner Pipe
Vent Hood Required for Wall Installation
Vented Crawl Space (Check Local Codes Before Installing in a Vented Crawl Space)
Figure 8 - Outside Air Kit
Chimney Pipe The FMI PRODUCTS, LLC chimney system consists of 12", 18", 24", 36" and 48" snap- lock, double-wall pipe segments, planned for maximum adaptability to individual site requirements. Actual lengths gained after fitting overlaps must be taken into consider- ation (lineal gain) and are given in the lineal gain chart (see Figure 9). Lineal Gain is the actual measurable length of a part after two or more parts are connected. For Canada, use chimney parts designated "HT".
Assembly and installation of double wall chimney system Each double wall chimney section consists of a galvanized outer pipe, a stainless steel inner flue pipe and a wire spacer. The pipe sections must be assembled independently as the chimney is installed. When connecting chimney directly to the fireplace, the inner flue pipe section must be installed first with the lanced side up. The outer pipe section can then be installed over 5 the flue pipe section with the hemmed end up. Press down on each pipe section until the lances securely engage the hem on the fireplace starter. The wire will assure the proper spacing between the inner and outer pipe sections.
Air Inlet Eyebrow

Continue to assemble chimney sections as outlined above, making sure that both the inner and outer pipe sections are locked to- gether. When installing double wall snap-lock chimney together, it is important to assure the joint between the chimney sections is locked. Check by pulling chimney upward after locking. The chimney will not come apart
if properly locked. It is not necessary to add screws to keep the chimney together (excep- tion, see Figure 10).
Using ELBOW offsets (30E-12DM) 1. To achieve desired offset, you may install combinations of 12", 18", 24", 36" and 48" length of double wall pipe (see offset chart and Figure 10). 2. Chimney weight above offset rests on return elbow. Straps must be securely nailed to rafters or joists (see Figure 11, details A and B). 3. Maximum length of pipe between sup- ports (return elbow or 12S-12DM) is 6' of angle run. Maximum of two 6' angle run sections per chimney system (see Figure 12, page 10). 4. All pipe connections between the offset and return must be secured with two screws on the outer pipe only (see Figure 10). Do not penetrate the inner stainless.

Figure 11 - Ceiling Support Pipe
12S-12DM
B
A
Figure 10 - Elbow Offset
Screws


Firestop Spacers (FS-10, 1100EFS-10DM for 36" Models) Firestop spacers are required at each point where the chimney penetrates a floor space. Their purpose is to establish and maintain the required clearance between the chimney and the combustible materials. When the pipe passes through a framed opening into a living space above, the firestop must be placed onto the ceiling from below as shown in Figure 13. They also provide complete separation from one floor space to another or attic space as required by most codes. When the double wall pipe passes through a framed opening into an attic space, the firestop must be placed into an attic floor as shown in Figure 14.

Space Above Ceiling
Penetrating roof To maintain a 1" (36" Models) or 2" (42/50" Models) clearance to the pipe on a roof with a pitch, a rectangular opening must be cut. 1. Determine center point through which pipe will penetrate roof. 2. Determine center point of roof. Pitch is distance the roof drops over a given span, usually 12". A 6/12 pitch means that roof drops 6" for each 12" measured horizon- tally down from roof rafters. 3. Use roof opening chart (Figure 15, page 11) to determine correct opening length and flashing required. 4. Remove shingles around opening mea- sured. Cut out this section.

Screws or Staples (Min. of 8)
Space Above Ceiling
Return Elbow · Existing Ceiling Frame · Firestop Spacer

Flashing installation (v6f-10dm or v12f-10dm) Determine the flashing to be used with the roof opening chart. Slide flashing over pipe until base is flat against roof. Replace as many shingles as needed to cover exposed area and flashing base. Secure in position by nail- ing through shingles (see Figure 16). DO NOT NAIL THROUGH FLASHING CONE.
Installing Flashing on a Metal Roof When installing the flashing on a metal roof, it is required that putty tape be used between the flashing and the roof. The flashing must be secured to the roof using #8 x 3/4" screws and then sealed with roof coating to prevent leak- age through the screw holes. A roof coating must also be applied around the perimeter of the flashing to provide a proper seal.
Overlap Shingles Top and Sides Only
Nail Only Outer Perimeter of Flashing
19.5" Min. 30" Min. 2" Min.
Underlap Shingles at Bottom
2" Min.
2" Min.
Storm Collar Installation (SC2-1) Place storm collar over pipe and slide down until it is snug against the open edge of the flashing (see Figure 17). Apply waterproof caulk around the perimeter of the collar to provide a proper seal.
Figure 15 - Roof Opening Measurements
Figure 17 - Storm Collar

Terminations/Spark Arrestor The fireplace system must be terminated with the listed round top or chase terminations. In any case, refer to the installation instructions supplied with the termination.
18" Min. Typ.
24" Min.
24" Min.
Stainless Inner Flue Pipe
Level of Flue Gas Outlet
10 foot rule All flue gas outlet chimney terminations must extend a minimum of 3 feet in height above the highest point where it passes through the roof and must be at least 2 feet above the high- est point of the roof that is within a horizontal distance of 10 feet (see Figure 20).
Secure Termination to Outer Pipe with 3 Screws
Level of Flue Gas Outlet
2' Min.
3' Min.
Overlap Shingles (Top and Sides of Flashing Base)
2' Min. 3' Min.
Chase installations Instructions for chase installations are included with the chase style termination chosen. In a multiple chase installation, be sure to provide adequate distance between terminations to prevent smoke spillage from one termination to another. We suggest that terminations be separated at least 24", center to center and stacked at a vertical height dif- ference of 18" (see Figure 19). Note: If a decorative shroud is to be installed, contact the manufacturer for specifications.
finishing fireplace Combustible materials, such as wallboard, gypsum board, sheet rock, drywall, plywood, etc. may make direct contact with sides and top around the fireplace face. It is important that combustible materials do not overlap the face itself. Brick, glass, tile or other noncombustible materials may overlap the front face provided they do not obstruct essential openings like louvered slots or any other opening. When overlapping with a noncombustible facing material, use only noncombustible mortar or adhesive.

Gas line hook up should be done by your supplier or a qualified service person. Note: Before you proceed, make sure your gas supply is turned off. Use only a 1/2" black iron pipe and appropri- ate fittings. 1. Remove knockout indentation on refrac- tory or firebrick wall located above refrac- tory hearth floor. Knockout indentation must be firmly tapped with any solid object such as a 1/2" dowel until it is released. Remove fragmented portions of refractory (see Figure 21). 2. Remove gas line cover plate located on either side of fireplace and pull out insula- tion from gas line conduit sleeve. Save insulation for reuse. Replace screws. 3. Run a 1/2" black iron gas line into fireplace through the rear at gas line conduit sleeve (if using a raised platform, add height). Provide sufficient gas line into fireplace chamber for fitting connection (see Figure 22). Note: Secure incoming gas line to wood framing to provide rigidity for threaded end. 4. Repack insulation around gas line and into sleeve opening. Seal any gaps between gas line and refractory knockout hole with refractory cement or commercial furnace cement, Install the gas appliance or cap-off gas line if desired.
If you install a decorative gas appliance (vented gas log), the decorative gas appliance must comply with the Standard for Decorative Gas Appliance for Installation in Solid Fuel Burning Fireplaces, ANS Z21.60 or Z21.84 and shall also be installed in accordance with the National Fuel Gas Code, ANSI 7223NFPA 54 latest edition.
Side Firebrick Finished Side
CAUTION: All gas piping and connections must be tested for leaks after the installation is completed. After ensuring that the gas valve is on, apply soap and water solution to all connections and joints. Bubbles forming show a leak. Correct all leaks at once. DO NOT USE AN OPEN FLAME FOR LEAK TESTING AND DO NOT OPER- ATE ANY APPLIANCE IF A LEAK IS DETECTED. LEAK TESTING SHOULD BE DONE BY A QUALI- FIED SERVICE PERSON.
Brick with Access Hole
Side Firebrick Finished Side
Incoming 1/2" Black Iron Pipe
Seal Opening with Refractory Cement
Provide Enough Threaded End for Fitting Connection

Brick Installation Each brick housing is stamped with a number (full size bricks are not stamped). These num- bers will help identify the brick when installing. It is important to install these bricks exactly as instructed. Press brick firmly into brick housing until it snaps. Groove line on side of brick will come in contact with flange on the brick hous- ing. This secures brick into housing (see Figure 24). Smaller bricks may require a small portion of furnace cement applied to back of brick to secure it until grouting has been completed. Bricks are packaged in separate boxes. The brick matrixes on pages 15 through 27 show how bricks are packaged and placed for each size fireplace and the number of bricks per box. There are 2 extra full bricks included in Hearth Brick package. Install bricks one section at a time starting with hearth panel followed by the rear panel, left panel and right panel. It is important to install the bricks in sequence. Please note, full size bricks are NOT stamped.
The brick housings are already installed on the panels. When installing brick housing panels into fireplace, wear gloves as edges may be sharp. 1. Beginning with left side panel, place panel, bottom edge first, at an angle into fireplace. Secure to bottom of fireplace with screws provided. 2. Install right side as left side in step 1 using screws provided. 3. Install back panel and secure back to sides and bottom of firebox with screws provided. 4. Using self-tapping screws and a drill, place screws into large holes in back and side panels (see Parts, page 34), through wire mesh and into firebox wrapper to secure.
Brick Stamped Letter Location
Hole in Side Panel
to Firebox Wrapper
Figure 24 - Installing Brick
Flanges · Brick Housing

RED IVORY QTY FULL (112140-01)

ASH BRICK (120848-01)
ASH BRICK (120848-03)
F012R F012W 2 F124R F124W 2 F125R F125W 2 F126R F126W 2 F128R F128W 2 * Includes 2 extra bricks.
FULL (112140-05)

ASH BRICK (120848-03)
F011R F011W 1 F059R F059W 4 F123R F123W 2 F124R F124W 2 F126R F126W 2 F132R F132W 2 F133R F133W 2 * Includes 2 extra bricks.

ASH BRICK (120848-01)
ASH BRICK (120848-03)
F011R F011W 3 F012R F012W 2 F021R F021W 2 F024R F024W 2 F025R F025W 2 F059R F059W 2 F126R F126W 2 F134R F134W 2 F135R F135W 2 * Includes 2 extra bricks.
F025

F147
F148 F148
LEFT REFRACTORY RED IVORY QTY FULL (112140-01)
F036 F158
FULL
FULL (112140-05)
F143 F143 F144
FULL FULL
F036R F036W 3 F143R F143W 2 F144R F144W 1 F147R F147W 1 F148R F148W 2 F158R F158W 3 F185R F185W 1 F191R F191W 1 F192R F192W 1
FULL
F158
FULL FULL
FULL F036
F158
F191 F192
F148 F150 F150
F159 F159 F159
F159 F159 F159
REAR REFRACTORY RED IVORY QTY FULL (112140-01)
FULL FULL
FULL (112140-05)
F160
FULL
F160
F148R F148W 1 F150R F150W 2 F152R F152W 1 F153R F153W 2 F159R F159W 6 F160R F160W 4
F160
FULL
F160
FULL FULL
F153
F153 F152
F147
F148 F148
RIGHT REFRACTORY RED IVORY QTY FULL (112140-01)
F036 F158
FULL
FULL (112140-05)
F143 F143 F144
FULL FULL
F036R F036W 3 F143R F143W 2 F144R F144W 1 F147R F147W 1 F148R F148W 2 F158R F158W 3 F185R F185W 1 F191R F195W 1 F192R F192W 1
FULL
F036
FULL FULL
F158
FULL F036
F192
F191
F185 or · F185 or


F017R F017W 1 F032R F032W 3 F033R F033W 3 F143R F143W 3 F151R F151W 1 F155R F155W 1 F156R F156W 1 F158R F158W 2 F186R F186W 1 F190R F190W 1

FULL (112140-05)
F017R F017W 2 F032R F032W 6 F033R F033W 4 F152R F152W 2 F154R F154W 2 F157R F157W 2
FULL (112140-05)
F017R F017W 1 F032R F032W 3 F033R F033W 3 F143R F143W 3 F151R F151W 1 F155R F155W 1 F156R F156W 1 F158R F158W 2 F186R F186W 1 F190R F190W 1

LEFT REFRACTORY RED IVORY QTY FULL (112140-01)

F032R F032W 3 F033R F033W 3 F143R F143W 2 F144R F144W 1 F145R F145W 1 F146R F146W 1 F147R F147W 1 F148R F148W 2 F149R F149W 1
F158R F158W 3 F191R F191W 1 F192R F191W 1

FULL (112140-05)
F148R F148W 2 F150R F150W 2 F152R F152W 2 F153R F153W 2 F159R F159W 6 F160R F160W 4
FULL (112140-05)
F032R F032W 3 F033R F033W 3 F143R F143W 2 F144R F144W 1 F145R F145W 1 F146R F146W 1 F147R F147W 1 F148R F148W 2 F149R F149W 1 F158R F158W 3 F191R F191W 1 F192R F192W 1

F074 F074
LEFT REFRACTORY RED IVORY QTY FULL (112140-01)

F068R F068W 1 F071R F071W 1 F072R F072W 5 F074R F074W 2 F113R F113W 3 F115R F115W 1 F165R F165W 1 F181R F181W 1 F189R F189W 1 S011R S011W 1

REAR REFRACTORY RED IVORY QTY FULL (112140-01)
F074
FULL (112140-05)
F068R F068W 1 F072R F072W 1 F074R F074W 6 F084R F084W 3 F107R F107W 3 F108R F108W 1 F117R F117W 1 F161R F161W 1 F168R F168W 2 F179R F179W 1 F187R F187W 1
F074
F074
F187
RIGHT REFRACTORY RED IVORY QTY FULL (112140-01)
FULL (112140-05)
F122
F068R F068W 4 F071R F071W 1 F072R F072W 1 F074R F074W 2 F110R F110W 3 F112R F112W 1 F120R F120W 4 F122R F122W 4 F180R F180W 1 F181R F181W 1 F188R F188W 1
F122
F122
F074
F181 or F071 · F181 or F071

F074 F074
LEFT REFRACTORY RED IVORY QTY FULL (112140-01)

FULL (112140-05)
F120
F064R F064W 4 F068R F068W 4 F072R F072W 2 F074R F074W 2 F120R F120W 4 F163R F163W 1 F169R F169W 1 F175R F175W 1 F176R F176W 1 F177R F177W 1 F182R F182W 1
F120
F176
F177
F074 F074

FULL (112140-05)
F063R F063W 3 F068R F068W 1 F072R F072W 6 F074R F074W 2 F089R F089W 1 F161R F161W 2
F171R F171W 1
F178R F178W 1
F171
F074
RIGHT REFRACTORY RED IVORY QTY FULL (112140-01)

F068R F068W 1 F071R F071W 4 F072R F072W 2 F074R F074W 1 F100R F100W 3 F101R F101W 1 F162R F162W 1 F164R F164W 1 F165R F165W 1 F174R F174W 1
F175 or F182 · F162 or F184

LEFT REFRACTORY RED IVORY QTY FULL (112140-01)
F074 F074

FULL (112140-05)
F064R F064W 4 F068R F068W 4 F072R F072W 2
F074R F074W 2 F120R F120W 4 F163R F163W 1 F169R F169W 1 F175R F175W 1 F176R F176W 1
F120
F176
F177R F177W 1 F182R F182W 1
F177
REAR REFRACTORY RED IVORY QTY FULL (112140-01)
F074
F074

F063R F063W 3 F065R F065W 3 F068R F068W 2 F072R F072W 2 F074R F074W 2 F082R F082W 1
F161R F161W 2
F168R F168W 2
F170R F170W 1
F178R F178W 1
F178
RIGHT REFRACTORY RED IVORY QTY FULL (112140-01)
F093 F074 F074

F068R F068W 2 F072R F072W 1 F074R F074W 2 F083R F083W 3 F084R F084W 4 F085R F085W 1 F093R F093W 1 F166R F166W 1 F167R F167W 1 F172R F172W 1 F173R F173W 1 F183R F183W 1
F175 or F182

Grouting instructions Material provided: 1 or 2 - 10 lb. bags of cement (depending on model) 1 or 2 - 10 lb. bags of sand (depending on model) Material required: 1 - Piping bag 1 - Joints striker 1 - Heavy duty mixing bucket 1 - Trowel 1. Moisten brick surface with damp sponge or spray bottle just prior to application. When bricks are wet, any excess grout mixture on bricks will easily wipe off. 2. In a heavy duty mixing bucket, pour 4 ½ cups of water. Add 5 lbs. (half of a bag) of sand and 5 lbs (half of a bag) of cement. Mix together well using a power drill with mixing wand attachment to a yogurt like consistency. Not adding enough water can lead to grout falling out after burning. 3. The overall length of piping bag should be about 16". If the bag is longer than 16", cut it down to size by removing end with larger opening. This will make the bag easier to handle. 4. Put 2 to 3 cups of grout mixture into piping bag making sure the smaller opening is downward and over a moist towel to avoid spilling. Place a wet towel over the bucket making sure it is directly on the surface of grout mixture. This will keep the mixture moist and it will not dry out before use. 5. Begin grouting by first doing a “Filler Pass”. This is done by filling the joint about 3/4 full with grout mixture. It is important to work with only 6 bricks at a time so grout doesn't have time to set up before striking. 6. Complete a “Finishing Pass” around 6 bricks you just put filler pass around. This is done by slowly filling in remainder of the joint with a thick amount of grout mixture.
Mixture should be a little higher than the brick surface. 7. Using a trowel, remove excess grout mix- ture by moving trowel in the direction of the joint. Grout mixture in the joint should now be flush with brick surface. If not enough grout is applied into each space, grout may fall out after burning. 8. Using a joint striker, force grout mixture into joint and sweep back and forth until grout is smooth and round. If grout becomes too shallow, add more grout mixture with piping bag and strike again. 9. Continue procedure around each group of 6 bricks until an entire panel is finished. 10. Using trowel, scrape in direction of joints to remove any grout that may have col- lected around bricks during striking. If desired, take a moist sponge and lightly sweep over bricks to remove any grout that may have gotten on bricks. DO NO PRESS HARD OR RUB IN A CIRCULAR MOTION. This will press the grout into brick and turn brick a different color.
operating fireplace.


INSTALLING FIREPLACE HOOD AND SCREEN 1. Mount screen rod brackets on left and right side of smoke shelf with #8 x 1/2" screws provided (see Figure 27, page 29). 2. Slide round end of screen rod into rings at top of screen. Attach one push-on nut to end of rod before attaching last ring of screen. 3. Insert round end of rod into rod bracket on left side of fireplace. 4. Mount flat end of screen rod with #10 x 5/8" to center of smoke shelf (see Figure 26). 5. Install other screen rod in same manner.

Glass Door Installation
Installation To install glass door frame, construct an opening (see table) on the front face of the fireplace. Insert door frame into face opening and tighten screws (see Figure 28).

Assembly Insert L-shaped gussets starting at the left top portion of door frame. Gusset holes should align with screw holes on the frame. Secure using flat head screws.
MODEL A B 36" 37"±1/4" 34"±1/4" 42" 43"±1/4" 34"±1/4" 50" 51"±1/4" 34"±1/4"
Figure 28 - Installing Door Frame

Installing glass doors Spring clips have been installed but some adjustments may be needed. Install the doors using the following steps: 1. With bifold doors completely folded, insert bottom pivot pin into pivot hole located near bottom corner of front face opening and swing door to vertical position making sure top pins slide into door track. Door is installed when top door pin snaps into spring clip. 2. Repeat step 1 for remaining door. If you find the doors do not close properly or do not appear level or straight, proceed with section on door adjustment,
Installation 1. Remove screws from smoke shelf (see Figure 29). 2. Mount top door frame and secure with screws provided (see Figure 29). 3. Place bottom door frame on top of ash lip at front of fireplace (see Figure 30). 4. Secure bottom door frame to brick with two hex screws provided as shown in Figure 31 using a 7/16" open end or adjustable wrench.

Fold Door and Slide Top Pins Into Track

Insert Pin into Spring Clip
Insert Bottom Pivot Pin into Hole
Door Adjustment Remove doors and slightly loosen lower pivot clips and upper spring clips. Replace doors and fully close them. Use 1/8" shims (any material) to level doors. Once proper setting is achieved, carefully open doors enough so that you can access spring clips with a phillips screwdriver. Tighten screws. See Figure 32.

Spring Clip · Pivot Hole

Cleaning Glass Clean glass with any commercial glass cleaner or soap and water. Do not use any abrasive material to clean glass. Do not clean glass with any cool water if glass is still hot from the fire and smoke. A gas line or gas log lighter may be installed for the purpose of installing a vented or vent- free decorative gas appliance incorporating an automatic shutoff device and complying with the Standard for Decorative Gas Appliances for Installation in Vented Fireplaces, ANSI Z21.60 or American Gas Association draft requirements for Gas Fired Log Lighters for Wood Burning Fireplaces, Draft NO. 4 dated August, 1993. If you wish to install an unvented (vent-free) gas log set, only unvented gas log sets which have been found to comply with the standard for unvented room heaters, ANSI Z21.11.2 are to be installed in this fireplace.
Glass Doors Glass doors are optional with the fireplace. When fireplace is in operation, doors must be fully opened or fully closed position only or a fire hazard may be created (see Figure 33). A fireplace equipped with glass doors oper- ates much differently than a fireplace with an open front. A fireplace with glass doors has a limited amount of air for combustion. Excessive heat within the fireplace can result if too large a fire is built or if combustion air gate is not completely open. The following tips should be followed to assure that both the fireplace and glass door retain their beauty and function properly. Both the flue damper and glass doors must be fully opened before starting fire. This will provide sufficient com- bustion air and maintain safe temperatures in firebox. IMPORTANT: The glass must be allowed to warm slowly and evenly. The tempered glass will withstand a gradual temperature rise to 550° F, which is more than a normal fire will generate. Such materials as pitch/wax laden logs, very dry mill end lumber and large amounts of paper or cardboard boxes can create an excessively hot fire and should not be burned in this fireplace. Always keep the fire well back from the doors and never allow flames to contact the glass.

outside air and damper handle operation The damper handle, which opens and closes the damper blade, is located in the upper front face of the fireplace. Pushing the handle for- ward and up through the keyway slot will free damper blade to automatically open. Pushing the handle forward and down will lock damper blade closed (see Figure 34).
The outside air kit lever is located at the left and right hand sides of fireplace (see Figure 35). Lifting lever up will free the outside air door to open. Pulling lever down will lock the door.
Open Position Closed Position
Figure 34 - Operating Damper Handle

You may have further questions about in- stallation, operation, or troubleshooting. If so, contact FMI PRODUCTS, LLC at 1-866-328-4537.
When calling please have your model and se- rial numbers of your heater ready. You can also visit our web site at www.fmiproducts.com
If this product is missing a part or has a broken component, please do not return it to the store. Call FMI PRODUCTS, LLC at 1-866-328-4537 to answer questions and replace parts under warranty. Note: Use only original replacement parts. This will protect your warranty coverage for parts replaced under warranty.
When calling or writing, please have your model and serial numbers of your fireplace ready. Model and serial number information are in the fireplace's rating plate located on the fireplace bottom. You can access the rating plate by lift- ing out the ash brick within hearth panel and removing the ash dump box.



Parts This list contains replaceable parts used in your firebox. When ordering parts, follow the instructions listed under Replacement Parts on page 33 of this manual.
(V)GM42, WCM-42G
(V)GM50, WCM-50G
• • • 1
Housings (1 each, right, left, rear)
** Not a field replaceable part.

Models (V)Gm36(Sr,SI,HR,HI), (V)Gm42(Sr,SI,HR,HI), (V)Gm50(Sr,SI,HR,HI) This list contains replaceable parts used in your firebox. When ordering parts, follow the instructions listed under Replacement Parts on page 33 of this manual.
(V)GM36S(R)(I)
(V)GM42H(R)(I)
(V)GM42S(R)(I)
(V)GM50H(R)(I)
(V)GM50S(R)(I)
All parts are Housing Panel Assemblies. For Brick part numbers see pages 15 thru 27.
MK-36SH-(R)(I)
MK-42SS-(R)(I)
MK-42SH-(R)(I)
MK-50SS-(R)(I)
MK-50SH-(R)(I)

BDMO36E - 36" Ebony BDMO36G - 36" Pewter BDMO36C - 36" Oiled Bronze BDMO42E - 42" Ebony BDMO42G - 42" Pewter BDMO42C - 42" Oiled Bronze BDMO50E - 50" Ebony BDMO50G - 50" Pewter BDMO50C - 50" Oiled Bronze
Double Wall Pipe - 12-12DM, 18-12DM, 24-12DM, 36-12DM, 48-12DM, 12-12HT, 18-12HT, 24-12HT, 36-12HT and 48-12HT
Storm Collar - SC2-1
30° Offset and Return 30E-12DM and 30E-12HT
Firestop Spacer - FS-10

Roof Flashing V6F-10DM - 0 to 6/12 Pitch V12F-10DM - 6/12 to 12/12 Pitch
SQUARE CHASE-TOP TERMINATION - STL-12D AND STL-12DMP BLACK


2701 S. Harbor Blvd. Santa Ana, CA 92704
122271-01 Rev. D 01/10
1-866-328-4537 www.fmiproducts.com