PFS ®p.1USp.1NOT FOR USE WITH SOLID FUEL CHECK LOCAL CODES PRIOR TO INSTALLATIONp.2SAVE THIS BOOKp.2TABLE OF CONTENTSp.2Safety Informationp.3DANGER: Carbon monoxide poisoning may lead to death!p.3Dimensionsp.4TOP VIEWp.4SIDE VIEW FRONT VIEWp.4Selecting Locationp.6GAS LINE HOOK-UPp.9Operating Fireplacep.13FOR YOUR SAFETY READ BEFORE LIGHTINGp.13LIGHTING INSTRUCTIONSp.13TO TURN OFF GASp.14Cleaning andp.15Maintenancep.15Specificationsp.15Wiring Diagramsp.16PILOTp.16THERMOPILEp.16IGNITORp.16DO NOT CONNECTp.16TO 120Vp.16N.C.SW HEAT LIMIT SWITCHp.16THp.16TPp.16MAIN GAS INCOMINGp.16TH/TPp.16SUPPLYp.16PILOT SAFETY WIREp.16WALL SWITCHp.16(SUPPLIED)p.16PILOT IGNITORp.16INCOMINGp.16(SUPPLIED) WALL SWITCHp.16MAIN GASp.16SENSORp.16ONp.16OFFp.16BLACKp.16120V AC INCOMINGp.16PV GND PV/MV TR MV TH IGNp.16WHITEp.16(FUSE BOXp.16GREENp.16OR BREAKER)p.16N.C.SW HEAT LIMITp.16EV1p.16SWITCHp.16ELECTRICAL RATING:p.16EV2p.1624V ACp.16STEP DOWN TRANSFORMERp.16120V ACp.16OPTIONAL REMOTE CONTROLp.16TO GAS LINEp.16BURNERp.16Troubleshootingp.17OBSERVED PROBLEMp.17POSSIBLE CAUSEp.17REMEDYp.17Replacement Parts and Accessoriesp.19Millivolt Valve Natural Gas - 14512 Propane/LP Gas - 14513p.19Electronic Valve Natural Gas - 14569 Propane/LP Gas - 14570p.19Millivolt Pilot Assembly Natural Gas - 112784-01 Propane/LP Gas - 112784-02p.19Electronic Pilot Assembly Natural Gas - 108866-01 Propane/LP Gas - 108866-02p.19Cabinet Style Door Kit -p.19Warrantyp.20KEEP THIS WARRANTYp.20FMI PRODUCTS, LLC LIMITED WARRANTIESp.20
Page 1 of the FMI GL36STP user manual — PFS ®
Page 1 · click to enlarge
Page 1

2-SIDED (SEE-THROUGH), VENTED DECORATIVE GAS APPLIANCE OWNER’S OPERATION AND INSTALLATION MANUAL

FMI GL36STP — PFS ® diagram (page 1)
Fig. 1

PFS ®

US

NATURAL GAS MODELS (V)GL36ST AND (V)GL36STE PROPANE/LP GAS MODELS (V)GL36STP AND (V)GL36STEP

FOR YOUR SAFETY — Do not store or use gasoline or any other flammable

vapors or liquids in the vicinity of this or any other appliance. — WHAT TO DO IF YOU SMELL GAS :

  • Do not try to light any appliance.
  • Do not touch any electrical switch;
  • Do not use any phone in your building.
  • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
  • If you cannot reach your gas supplier, call the fire department. — Installation and service must be performed by a quali

fied installer, service agency or the gas supplier.

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.

For more information, visit www.fmiproducts.com

Page 2 of the FMI GL36STP user manual — Table of Contents
Page 2 · Contents
Contents

Contents

PFS ®p.1USp.1NOT FOR USE WITH SOLID FUEL CHECK LOCAL CODES PRIOR TO INSTALLATIONp.2SAVE THIS BOOKp.2TABLE OF CONTENTSp.2Safety Informationp.3DANGER: Carbon monoxide poisoning may lead to death!p.3Dimensionsp.4TOP VIEWp.4SIDE VIEW FRONT VIEWp.4Selecting Locationp.6GAS LINE HOOK-UPp.9Operating Fireplacep.13FOR YOUR SAFETY READ BEFORE LIGHTINGp.13LIGHTING INSTRUCTIONSp.13TO TURN OFF GASp.14Cleaning andp.15Maintenancep.15Specificationsp.15Wiring Diagramsp.16PILOTp.16THERMOPILEp.16IGNITORp.16DO NOT CONNECTp.16TO 120Vp.16N.C.SW HEAT LIMIT SWITCHp.16THp.16TPp.16MAIN GAS INCOMINGp.16TH/TPp.16SUPPLYp.16PILOT SAFETY WIREp.16WALL SWITCHp.16(SUPPLIED)p.16PILOT IGNITORp.16INCOMINGp.16(SUPPLIED) WALL SWITCHp.16MAIN GASp.16SENSORp.16ONp.16OFFp.16BLACKp.16120V AC INCOMINGp.16PV GND PV/MV TR MV TH IGNp.16WHITEp.16(FUSE BOXp.16GREENp.16OR BREAKER)p.16N.C.SW HEAT LIMITp.16EV1p.16SWITCHp.16ELECTRICAL RATING:p.16EV2p.1624V ACp.16STEP DOWN TRANSFORMERp.16120V ACp.16OPTIONAL REMOTE CONTROLp.16TO GAS LINEp.16BURNERp.16Troubleshootingp.17OBSERVED PROBLEMp.17POSSIBLE CAUSEp.17REMEDYp.17Replacement Parts and Accessoriesp.19Millivolt Valve Natural Gas - 14512 Propane/LP Gas - 14513p.19Electronic Valve Natural Gas - 14569 Propane/LP Gas - 14570p.19Millivolt Pilot Assembly Natural Gas - 112784-01 Propane/LP Gas - 112784-02p.19Electronic Pilot Assembly Natural Gas - 108866-01 Propane/LP Gas - 108866-02p.19Cabinet Style Door Kit -p.19Warrantyp.20KEEP THIS WARRANTYp.20FMI PRODUCTS, LLC LIMITED WARRANTIESp.20
Page 3 of the FMI GL36STP user manual — DANGER: Carbon monoxide poisoning may lead to death!
Page 3 · click to enlarge
Page 3

Safety Information

  • 1. This appliance is only for use with the type of gas indicated on the rating plate. This ap pliance is not convertible for use with other gases. 2. For propane/LP fireplace, do not place propane/ LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors. To prevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. capacity. 3. If you smell gas
  • shut off gas supply
  • do not try to light any appliance
  • do not touch any electrical switch; do not use any phone in your building
  • immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier's instructions
  • if you cannot reach you gas supplier, call the fire department. 4. Never install the fireplace
  • in a recreational vehicle
  • where curtains, furniture, clothing or other flammable objects are less than 42" from the front, top or sides of the fireplace
  • in high traffic areas
  • in windy or drafty areas 5. This fireplace reaches high temperatures. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Fireplace will remain hot for a time after shutdown. Allow surfaces to cool before touching. 6. Carefully supervise young children when they are in the room with fireplace. 7. A hearth extension is not required with this appliance. If one is installed, it is for aesthetic purposes only and does not have to meet the standard requirements. 8. Turn fireplace off and let cool before servicing or repairing. Only a qualified service person should install, service or repair this fireplace. Have fireplace inspected annually by a quali fied service person. 9. You must keep control compartments, burn ers and circulating air passages clean. More frequent cleaning may be needed due to ex cessive lint and dust from carpeting, bedding material, etc. Turn off the gas valve and pilot light before cleaning fireplace. 10. Have venting system inspected annually by a qualified service person. If needed, have vent ing system cleaned or repaired. See Cleaning and Maintenance , page 15.

DANGER: Carbon monoxide poisoning may lead to death!

This fireplace is a vented product. This fireplace will not produce any gas leakage into your home if properly installed. This fireplace must be properly installed by a qualified service person. If this unit is not properly installed by a qualified service person, gas leakage can occur.

Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning resemble the flu, with headaches, dizziness or nausea. If you have these signs, the fireplace may not have been installed properly. Get fresh air at once! Have fireplace inspected and serviced by a qualified service person. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol and those at high altitudes. Propane/LP gas and natural gas are both odorless. An odor-making agent is added to each of these gases. The odor helps you detect a gas leak. How ever, the odor added to these gases can fade. Gas may be present even though no odor exists. Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this fireplace.

Page 4 of the FMI GL36STP user manual — SIDE VIEW FRONT VIEW
Page 4 · click to enlarge
Page 4

Safety information

16. Do not install fireplace directly on carpeting, vinyl tile or any combustible material other than wood. The fireplace must set on a metal or wood panel extending the full width and depth of the fireplace. 17. Do not use fireplace if any part has been ex posed to or under water. Immediately call a qualified service person to arrange for replace ment of the unit. 18. Do not operate fireplace if any log is broken. 19. Do not use a blower insert, heat exchanger insert or other accessory not approved for use with this fireplace. 20. Provide adequate clearances around air openings.

11. Keep the area around your fireplace clear of combustible materials, gasoline and other flammable vapor and liquids. Do not run fire place where these are used or stored. Do not place items such as clothing or decorations on or around fireplace. 12. Do not use this fireplace to cook food or burn paper or other objects. 13. Do not use any solid fuels (wood, coal, paper, cardboard, etc.) in this fireplace. Use only the gas type indicated on fireplace nameplate. 14. This appliance, when installed, must be electri cally grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70. 15. Do not obstruct the flow of combustion and ventilation air in any way. Provide adequate clearances around air openings into the combus tion chamber along with adequate accessibility clearance for servicing and proper operation.

Dimensions

2 1/2" 6"(152 mm)

6" O.D.

9 1/2"

21 1/4"

15 1/4"

(540 mm) (387 mm)

42 1/2"

4 1/2"

TOP VIEW

1 1/2"

7 1/2"

52 1/2"

37 1/2"

20 1/2"

5 1/2"

36 1/2"

(229 mm) (140 mm)

42 1/2"

SIDE VIEW FRONT VIEW

Show 26 more labels / short text on this page
(152 mm) · (64 mm) · 24" · (610 mm) · (241 mm) · (2 1/2") · 19" · (64mm) · (483 mm) · (1080 mm) · (114 mm) · 16" · (406 mm) · 12" · (305 mm) · (38 mm) · (191 mm) · (1334 mm) · (953 mm) · (521 mm) · 9" · (927 mm) · 8"(203 mm) · 13" · (1080 mm) · (330 mm)
Page 5 of the FMI GL36STP user manual — Dimensions
Page 5 · click to enlarge
Page 5

Introduction Models (V)GL36ST/P and (V)GL36STE/EP are decorative gas appliances that use a millivolt gas control and piezo pilot or an electronic gas control valve with an electronic ignition system respectively. These systems require a 6", B-type venting system for operation. The 6" B-type vent is not supplied by FMI PRODUCTS,LLC . For installation guidelines, check your B-vent instructions.

Fuel Gas Code, ANSI Z223.1/NFPA 54. This appliance complies with ANSI Z21.50 as a Vented Gas Appliance and is listed and tested by the PFS Corporation.

Models (V)GL36ST and (V)GL36STE are smooth face units for natural gas only. The (V)GL36STP and (V)GL36STEP are smooth face units for propane/LP gas only. To determine which type of gas your unit is approved and tested for, check the rating plate on the lift-out plate located inside the firebox under the access panel.

Selecting Location To determine the safest and most efficient location for your appliance, you must take into consider ation the following guidelines: 1. The location must allow for proper clearances (see Clearances, page 6). Note: This decora tive appliance is not designed for outdoor installation. 2. The location should be in a place where drafts, air conditioning ducts, windows or doors will not affect fireplace heat output. 3. A location that avoids the cutting of joists or roof rafters will make installation easier. Figure 2 shows a typical two-sided fireplace installation. IMPORTANT: All fireplace openings must be located at least 3 feet from facing wall or com bustible material.

BEFORE YOU BEGIN Before beginning the installation of your appli ance, read these instructions through completely. This appliance and its approved components are safe when installed according to this installation manual and are operated as recommended by FMI PRODUCTS, LLC. Unless you use FMI PRODUCTS,LL approved components tested for this appliance, YOU MAY CAUSE A FIRE HAZARD! The FMI PRODUCTS,LLC warranty will be voided by and FMI PRODUCTS,LLC disclaims any respon sibility for the following actions : A) Modification of the appliance or any of

the components manufactured by FMI PRODUCTS,LLC unless otherwise permitted by FMI PRODUCTS,LLC. B) Use of any component part not approved by

FMI PRODUCTS,LLC in combination with this appliance. C) Installation and/or operation in a manner other

than instructed in this manual. D) The burning of anything other than the type of

gas approved for use in this gas appliance. This appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70. The installation must conform with local codes or, in the absence of local codes, with the current National

4" From Opening to Perpendicular Wall

Figure 2 - Typical Two-Sided Fireplace

Projected Wall · Existing Side Wall · Installation

Page 6 of the FMI GL36STP user manual — Selecting Location
Page 6 · click to enlarge
Page 6

Selecting Location

1" (22 mm) Minimum Clearance to Combustibles

1" (22 mm) Minimum Clearance from Pipes to Combustibles

In selecting a location, the following precautions must be observed: 1. Do not connect this appliance to a chimney system used for a solid fuel burning fire place. 2. Install in an area providing ventilation and adequate combustion air. 3. Due to high temperatures, do not locate this appliance in high traffic areas or near furniture and draperies. 4. Never obstruct the front opening of the appli ance or the flow of combustion and ventilation air. Keep control compartments accessible. 5. DO NOT locate in the vicinity where gasoline or other flammable liquids may be stored. The appliance area must be kept clear and free from these combustible materials.

22 3/4" (578 mm)

11 3/8" (289 mm)

22 1/4" (565 mm)

6" O.D. (152 mm)

4" (102 mm) Min. from the Perpendicular Side Wall to the Fireplace Opening (Typ.)

Figure 3 - Clearances from Top View

1" (25 mm) Min. Clearance from Pipes to Combustibles

35" (889 mm) Min. to Effective Opening to Ceiling

Do Not Pack Space Between Spacer with Any Type of Insulation

  • CLEARANCES Minimum clearances to combustibles are:
  • Fireplace flanges to studs. . . . . . . . . . . . . . 0"
  • Fireplace back/sides. . . . . . . . . . . . . . . . . . 1"
  • Fireplace spacers to framing. . . . . . . . . . . . 0"
  • Openings to perpendicular wall. . . . . . . . . 4"
  • End glass to facing wall. . . . . . . . . . . . . . 12"
  • Side glass to facing wall. . . . . . . . . . . . . . 36"
  • Bottom of fireplace to floor or platform. . . 0"
  • “B” vent surfaces. . . . . . . . . . . . . . . . . . . . 1"
  • Top of fireplace opening to ceiling. . . . . . 35" See Figures 3 and 4.

Figure 4 - Clearances from Side View

Mantel Clearances Woodwork, such as wood trims, mantels and other combustible materials, should not be placed within 7" of the opening of this appliance (see Figure 5). Combustible material above the fireplace projecting more than 1 1/2" from the appliance’s front face must not be less than 12" from the ap pliance opening.

33° 6" (Ref12 1/4" (Ref.)Header Fireplace Drywall Combustible .) Materials in. 7" Min. to Effective Opening Note: Mantel clearances app to both sides of the applliacn

Figure 5 - Mantel Clearances

19" (483 mm) · Doublewall 6" B-Vent · 0" to Floor

Page 7 of the FMI GL36STP user manual — Selecting Location
Page 7 · click to enlarge
Page 7
FMI GL36STP — Selecting Location diagram (page 7)
Fig. 2 · Selecting Location

framing Construct framing using dimensions shown if Figures 6, 7 and 8. (Use the figure applicable to your application.) Figure 6 shows the framing dimensions prior to having the appliance in place. Once the unit has been fitted, bring studs in against nailing flanges located on the side of the appliance making sure a 1" clearance is maintained as shown in Figure 7. If the fireplace is to be installed directly on carpet ing, tile (other than ceramic) or any combustible material other than wood flooring the fireplace must be installed upon a metal or wood panel extending the full width and depth of the fireplace (see Figure 8). The platform must be solid, flat and fully supported.

As Required by Design as Long as Ceiling Clearances are Maintained

Figure 8 - Appliance Must Be Installed

on a Wood or Metal Panel if Being Installed on Any Combustible Material

vent pipe installation A 6", B-1 type gas vent pipe is a double-wall, vent ing system (not supplied) which must be installed during rough framing of the appliance. Any B-1 type gas vent system may be used for proper vent ing as long as the vent system is installed per the vent manufacturer’s recommendations. FMI PRODUCTS,LLC supplies this appliance with a tapered starter pipe for a snug fit. Slide B-1 type vent pipe over this starter pipe until vent pipe is fully seated. Secure this first section of B-vent pipe by strapping the connector around the vent pipe and then tightening the strap (not supplied) with any 1/8" nut and bolt (see Figure 9). Note: Visually inspect for proper vent connection by looking inside top of appliance. If connection does not appear to be correct, contact your local service technician.

22 3/4" (578 mm)

52 3/4" (1340 mm)

Min.

Figure 6 - Framing Dimensions Prior to

B-1 Type Vent (Not Supplied)

1" Min. to Combustibles

Strap (Not Supplied) (Fasten with #6 Screw or Bolt)

Figure 7 - Securing Appliance with

Figure 9 - Installing B-Vent Pipe

Show 7 more labels / short text on this page
Other Than Wood · 46" (11688 mm) · Placing Appliance · Nailing Flanges · Prepared Framing · Nails or Screws · Nailing Flanges
Page 8 of the FMI GL36STP user manual — Selecting Location
Page 8 · click to enlarge
Page 8
FMI GL36STP — Selecting Location diagram (page 8)
Fig. 3 · Selecting Location

Optional Outside air Kit (Model ak-4) The installation of an outside air kit should be completed during the rough framing of the fire place due to the nature of it's location. Outside combustion air is accessed through a vented crawl space.

Wall Switch Installation 1. Remove the J-box cover plate from side of appliance’s outer surround. 2. Using the 18 ga. millivolt wire and wall switch (both supplied), connect wiring per wiring diagram (see Figure 11). For more detail, see Wiring Diagrams on page 16. Note: If any of the original 10 feet supplied wire must be replaced, use Thermostat Millivolt Wire 18 AWG Type CL2-105 C or equivalent only. IMPORTANT: Do not hook up to standard 120 VAC household wiring.

Avoid installing outside air eyebrow in areas where inlet opening may be blocked by snow, bushes or other obstacles (see Figure 10). The maximum height for the air inlet termination cannot exceed 3 feet below the B-vent termination exhaust height.

FMI GL36STP — Selecting Location diagram (page 8)
Fig. 4 · Selecting Location

Secure to Collars with Duct Tape or Screws

FMI GL36STP — Selecting Location diagram (page 8)
Fig. 5 · Selecting Location

Air Inlet Location Must Allow For Bushes or Snow

Route Millivolt Wires (Supplied) Through Electrical Conduit Bushing

Figure 11 - Wall Switch Installation

Electronic models (gl36ste/ep) This appliance must be properly wired to stan dard 120v household current through the FMI PRODUCTS,LLC provided wall switch before its remote control unit can be used to activate the auto matic pilot ignition (turn fireplace flames ON).

Vent Hood Required for Wall Installation

Vented Crawl Space (Check Local Codes Before Installing in a Vented Crawl Space)

Wall Switch Installation 1. Remove the J-box cover plate from side of appliance’s outer surround. 2. Using the 18 ga. wires coming through strain relief grommet on side of appliance’s outer wall to standard household 120 VAC current through the wall switch provided, as shown in Figure 12, page 9. For more detail, see Wiring Diagrams, page 16. Note: If any of the original 10 feet supplied wire must be replaced, use 20 AWG electrical wire or equivalent only.

Figure 10 - Outside Air Kit

Millivolt Models (GL36ST/STP) The installation of a wall switch in this millivolt control appliance allows you to activate the gas control valve without the use of normal current.

Wall Switch · (Supplied) · To Thermopile

Page 9 of the FMI GL36STP user manual — GAS LINE HOOK-UP
Page 9 · click to enlarge
Page 9

assembly underneath the front ledge. A 1/8" NPT plugged tapping is provided on the gas control valve for a test gauge connection immediately upstream of the gas supply connection to the ap pliance (see Figures 13 and 14).

FMI GL36STP — GAS LINE HOOK-UP diagram (page 9)
Fig. 6

Pilot Gas Line Do Not Kink

FMI GL36STP — GAS LINE HOOK-UP diagram (page 9)
Fig. 7

Figure 12 - Wiring Through Outer Surround

Figure 13 - Millivolt Control Valve

GAS SUPPLY TESTING Note: This section is intended as a guide for quali fied technicians installing gas to this appliance.

FMI GL36STP — GAS LINE HOOK-UP diagram (page 9)
Fig. 8

E A From Gas Supply

Figure 14 - Electronic Control Valve

The appliance and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The appliance must be isolated from the gas sup ply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa). This unit has been tested for installation at high altitude. Higher altitudes affect the atmospheric pressure and heat valve of gaseous fuels. When installing this unit at high altitudes, the rated input will be lower than at sea level. The lowered oxygen content in the air and the lowered gas density require installation of a different size orifice in order to achieve clean combustion of the unit. Consult the unit data plate for the proper high-altitude orifice size. Fill out the information sticker attached to the unit when field converting. See Specifications, page 15, when derating. The gas control valve is secured to the burner pan

GAS LINE HOOK-UP

FMI GL36STP — GAS LINE HOOK-UP diagram (page 9)
Fig. 9

A manual shutoff valve has been included in the appliance’s gas supply system. You may consider installing an extra gas shutoff valve outside the ap pliance’s enclosure (check with local codes) where it can be accessed more conveniently with a key through a wall as shown in Figure 15, page 10. A 30" long, 1/2" NPT SCHD 40 flexible gas line (supplied) may be used between the incoming 1/2" NPT black iron gas line and the fireplace regulator (located inside the firebox, under the access plate). The incoming gas line may be routed toward the appliance from either the left or right hand side of fireplace outer surround.

Show 6 more labels / short text on this page
Common Ground Wire · Inlet Pressure · Outlet Pressure · To Main Burner · Outlet Pressure · Inlet Pressure
Page 10 of the FMI GL36STP user manual — GAS LINE HOOK-UP
Page 10 · click to enlarge
Page 10
FMI GL36STP — GAS LINE HOOK-UP diagram (page 10)
Fig. 10

To install: 1. Remove gas line cover plate from appliance’s outer surround at the location to be used. 2. Remove insulation from inside the gas line conduit sleeve. 3. Run gas line through sleeve. 4. Prepare incoming black iron gas line with Teflon tape or pipe joint compound. (Check local codes as to the use of Teflon tape.)

Typical Exterior Wall Gas Shutoff Installation

Figure 15 - Typical Exterior Wall Gas

FMI GL36STP — GAS LINE HOOK-UP diagram (page 10)
Fig. 11

Log Set Placement Carefully remove log set from packaging. Place the two bottom logs over grate and align with pins. Place three loose logs, or twigs, onto alignment pins on two bottom logs (see Figure 16).

FMI GL36STP — GAS LINE HOOK-UP diagram (page 10)
Fig. 12
5. Connect incoming gas line to regulator. Secure all joints tightly with wrench, but do not over tighten. If a flexible gas line is used, take care not to kink the connector. 6. Re-pack insulation in and around the conduit sleeve and flexible gas line.
FMI GL36STP — GAS LINE HOOK-UP diagram (page 10)
Fig. 13

WARNING: All gas piping and connections must be tested for leaks after the installation is completed. After ensuring that the gas valve is on, apply a commercial leak detection solution to all con nections and joints. If bubbles appear, leaks can be detected and corrected. Do not use an open flame for leak testing and do not operate any appliance if a leak is detected.

Figure 16 - Log Placement

Fireplace Facing Any non-combustible material may be used for facing (glass, tile, brick, etc.) as long as the proper clearances are adhered to and the fireplace open ings are not blocked or obstructed in any way. See Clearances, page 6, and Figure 17 on page 11. Use only heat-resistant, noncombustible mortar or adhesive when securing facing material to the front of the fireplace.

Shut-Off Installation · Bottom Logs · Top Logs (Twigs)

Page 11 of the FMI GL36STP user manual — GAS LINE HOOK-UP
Page 11 · click to enlarge
Page 11

1/8" to 1/4" Pilot Burner Ignitor Flame

FMI GL36STP — GAS LINE HOOK-UP diagram (page 11)
Fig. 14

Do Not Block Effective Opening "L" Shaped Metal Support

Burner Flame Adjustment The air shutter, located at the base of the main burner tube, has been factory preset to the proper air to bas ratio which results in a long, blue, cleaner burning flame (see Figure 20). If readjustment is necessary, loosen the air shut ter screw and rotate air shutter until proper flame setting is achieved, retighten air shutter screw. See Figure 20 for air shutter location. Closing the air shutter reduces the air-to-gas mix, resulting in a longer, yellow flame wihich produces excessive carbon monoxide (CO) and could also cause sooting.

Figure 17 - Fireplace Facing Material

Mantels Mantels, combustible or non-combustible, may be constructed as long as proper clearances are observed (see Figure 2, page 6 and Clearances, page 6).

Pilot Assembly Adjustment The pilot assembly is factory preset for the proper flame height. Alteration to factory settings may have occurred during shipping. If this is the case, some minor readjustments may be necessary and should be done by a qualified technician. The pilot assembly is located behind the burner next to the rear refractory piece at the right-hand side. The thermopile (in millivolt models) or the sensor (in electronic models) should be engulfed with the pilot flame approximately 3/8" to 1/2" in order for the regulator to receive proper signal (see Figures 18 and 19).

FMI GL36STP — GAS LINE HOOK-UP diagram (page 11)
Fig. 15
FMI GL36STP — GAS LINE HOOK-UP diagram (page 11)
Fig. 16

Figure 20 - Air Shutter Adjustment

3/8" to 1/2" (10 mm - 13 mm) 1/8" (3 mm)

Figure 18 - Correct Pilot Flame Pattern -

Show 4 more labels / short text on this page
Burner Pan · Ignitor Pilot Burner · Thermopile · Millivolt Assembly
Page 12 of the FMI GL36STP user manual — GAS LINE HOOK-UP
Page 12 · click to enlarge
Page 12

Top Slot Under Frame

Optional Glass Door Glass doors are optional with this gas appliance (see Replacement Parts and Accessories, page 19).

Installing Glass Door 1. Be sure top spring clip hole is aligned with hole in fireplace frame (see Figure 21). Fit glass door top pin into aligned holes. 2. Swing inner end of bottom clip out away from fireplace frame. Fit door bottom pin into clip. Push clip into frame until bottom door pin slips into hole in frame. 3. Check door alignment. If doors do not align with each other, use top spring clip to align. a. Use Phillips screwdriver to loosen screw

Figure 21 - Installing Glass Doors

that holds top spring clip in place. b. Push spring clip left or right in its align

ment slot until door is at proper angle (aligned with opposing door). Moving spring clip to the LEFT (your left as you face the fireplace) moves glass door’s top, inner corner UP; moving spring clip to the RIGHT moves glass door’s top, inner corner DOWN. c. When door alignment is satisfactory, use

Phillips screwdriver to retighten spring clip screw.

Glass Doors Must be Fully Open (as Shown) or Fully Closed when Appliance is in Operation

Figure 22 - Glass Doors Shown Fully

Only doors certified with this appliance may be used. When operating doors, do not slam or abuse them. Always keep area below bottom edge of doors clear of obstacles or debris. Do not operate this appliance if glass doors are broken or dam aged. See Figure 22.

Show 7 more labels / short text on this page
Adjustment Clip · Adjustment Screw · Long Pivot Pin · Bottom Pin · Bottom Slot · Adjustment Clip · Open
Page 13 of the FMI GL36STP user manual — LIGHTING INSTRUCTIONS
Page 13 · click to enlarge
Page 13

Operating Fireplace

1. STOP! Read the safety information, column 1. 2. Turn wall switch to the OFF position. 3. Turn off all electric power to the appliance. 4. Open control access panel. 5. Push in gas control knob and turn clock wise to the OFF position (see Figure 23). Note: It is recommended that you maintain the gas control knob in the full OFF position during lengthy periods of seasonal non usage. 6. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety information above. If you don’t smell gas, go to the next step.

FOR YOUR SAFETY READ BEFORE LIGHTING

A. This appliance has a pilot which must be

lighted by hand. When lighting the pilot, follow these instructions exactly. B. BEFORE LIGHTING smell all around the

  • 7. Turn control knob counterclockwise to the PILOT position. 8. Push in control knob all the way and hold in. Immediately light the pilot by pressing the red ignitor button until a flame ap pears. Continue to hold the control knob in for about (1) minute after the pilot is lit. Release knob and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 5 through 8.
  • If knob does not pop up when released, stop and immediately call your service technician or gas supplier.
  • If the pilot will not stay lit after sev eral tries, turn the gas control knob to “OFF” and call your service technician or gas supplier. 9. Turn gas control knob counterclockwise to “ON”. Knob can be turned to “ON” only if the control knob is popped out. 10. Replace control access panel. 11. Turn on all electric power to the appliance.
  • appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS
  • Do not try to light any appliance.
  • Do not touch any electric switch; do not use any phone in your building.
  • Immediately call your gas supplier from a neighbor’s phone. Follow the gas sup plier’s instructions.
  • If you cannot reach your gas supplier, call the fire department. C. Use only your hand to push in or turn the

gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service tech nician or gas supplier. Force or attempted repair may result in a fire or explosion. D. Do not use this appliance if any part has

been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

LIGHTING INSTRUCTIONS

Figure 23 - Millivolt Control Valve

Millivolt models · Gas Control Knob · Position Indicator

Page 14 of the FMI GL36STP user manual — FOR YOUR SAFETY READ BEFORE LIGHTING
Page 14 · click to enlarge
Page 14

OPERATING FIREPLACE

C. Use only your hand to push in or turn the

gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service tech nician or gas supplier. Force or attempted repair may result in a fire or explosion. D. Do not use this appliance if any part has

TO TURN OFF GAS

TO APPLIANCE 1. Turn off the wall switch. 2. Turn off all electric power to the appliance if service is to be performed. 3. Remove control access panel. 4. Push in gas control knob and turn clockwise to “OFF”. Do not force. 5. Replace control access panel.

been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

LIGHTING INSTRUCTIONS

1. STOP! Read the safety information, column 1. 2. Set the thermostat to lowest setting (if applicable). 3. Turn off wall switch. 4. Open control access panel or louver. 5. Smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety information in column 1. If you don’t smell gas, go to the next step. 6. Turn the main burner wall switch to the ON position for ignition. There will be a spark at the electrode. 7. Replace control access panel or louver once there is a flame at the burner. 8. If burner will not stay lit after several tries, flip the wall switch to OFF and call your service technician or gas supplier.

Figure 24 - Pilot

FOR YOUR SAFETY READ BEFORE LIGHTING

A. This appliance has a pilot which must be

lighted by hand. When lighting the pilot, follow these instructions exactly. B. BEFORE LIGHTING smell all around the

  • appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS
  • Do not try to light any appliance.
  • Do not touch any electric switch; do not use any phone in your building.
  • Immediately call your gas supplier from a neighbor’s phone. Follow the gas sup plier’s instructions.
  • If you cannot reach your gas supplier, call the fire department.

E A From Gas Supply

Figure 25 - Electronic Control Valve

Show 7 more labels / short text on this page
Pilot Burner · Thermopile · Ignitor · Electronic models · To Main Burner · Outlet Pressure · Inlet Pressure
Page 15 of the FMI GL36STP user manual — Specifications
Page 15 · click to enlarge
Page 15

OPERATING FIREPLACE

Figure 26 - Pilot

TO TURN OFF GAS

Keep control compartment, logs, burner and area surrounding logs clean by vacuuming or brushing at least twice a year. Take care not to alter the set tings on the pilot assembly. Do not use abrasive liquids or cleaners for cleaning glass doors and trims. Any household glass cleaner should suffice. Do not clean doors when hot. Allow appliance to cool before cleaning.

TO APPLIANCE 1. Turn off all electric power to the appliance if service is to be performed. 2. Remove control access panel. 3. Close the gas valve.

Cleaning and

Maintenance

Technical Service You may have further questions about installation, operation or troubleshooting. If so, contact FMI PRODUCTS, LLC’s Technical Service Depart ment at 1-866-328-4537. When calling please have your model and serial numbers of your heater ready. You can also visit our web site at www.fmiproducts.com.

WARNING: Installation and repair should be done by a qualified service person. The appliance should be inspected before each use and at least annually by a qualified service person. More frequent clean ing may be required due to excessive lint from carpeting, bedding material, pet hair, etc. It is imperative that the control compartments, burners and circulating air system be kept clean.

Specifications

  • (V)GL36ST, (V)GL36STE
  • Maximum Input Rating at Altitudes: 2,000 ft. - 42,000 Btu/hr., 2,000 ft. to 4,000 ft. - 37,800 Btu/hr.
  • Manifold Pressure: 3.5 W.C. (.87 kPa)
  • Supply Pressure (in. of water): Minimum* - 4.5" (1.12 kPa), Maximum - 11.0" (2.74 kPa)
  • Orifice Size at Altitudes: 2,000 ft. - #30, 2,000 ft. to 4,000 ft. - #31
  • (V)GL36STP, (V)GL36STEP
  • Maximum Input Rating at Altitudes: 2,000 ft. - 42,000 Btu/hr., 2,000 ft. to 4,000 ft. - 37,800 Btu/hr.
  • Manifold Pressure: 11.0 W.C. (2.74 kPa)
  • Supply Pressure (in. of water): Minimum* - 12.0" (2.89 kPa), Maximum - 13.0" (3.23 kPa)
  • Orifice Size at Altitudes: 2,000 ft. - #49, 2,000 ft. to 4,000 ft. - #51 * For the purpose of input adjustment
Page 16 of the FMI GL36STP user manual — EV2
Page 16 · click to enlarge
Page 16

Wiring Diagrams

PILOT

THERMOPILE

IGNITOR

DO NOT CONNECT

TO 120V

N.C.SW HEAT LIMIT SWITCH

O

T

O

N

TH

P

TP

F

F

O

MAIN GAS INCOMING

TH/TP

SUPPLY

PILOT SAFETY WIRE

WALL SWITCH

(SUPPLIED)

PILOT IGNITOR

INCOMING

(SUPPLIED) WALL SWITCH

MAIN GAS

SUPPLY

SENSOR

ON

OFF

BLACK

120V AC INCOMING

PV GND PV/MV TR MV TH IGN

WHITE

(FUSE BOX

GREEN

OR BREAKER)

N.C.SW HEAT LIMIT

EV1

GREEN

SWITCH

BLACK

WHITE

ELECTRICAL RATING:

120v, 60Hz, 0.7A

EV2

24V AC

STEP DOWN TRANSFORMER

120V AC

OPTIONAL REMOTE CONTROL

TO GAS LINE

BURNER

millivolt wiring diagram · Electronic wiring diagram

Page 17 of the FMI GL36STP user manual — OBSERVED PROBLEM
Page 17 · click to enlarge
Page 17

Troubleshooting

Millivolt system Note: Before troubleshooting the system, make sure the gas shutoff valve is ON. The two most common causes of a malfunctioning gas appliance are: 1. Loose wiring connections 2. Construction debris clogging the pilot and/or gas control valve filter

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

Pilot will not light

1. No gas supply or shutoff valve is OFF 2. Air in gas line

1. Check to see if you have gas supply 2. Hold regulator control valve in the PILOT position for 2 to 3 minutes to purge air. If you smell gas stop and wait for a few minutes before trying to light the fireplace 3. Remove debris and dirt, in spect and clean any other possible obstructions 4. Contact your gas supplier 5. Refer to section on pilot lighting 6. Have a qualified technician replace pilot line 7. Replace control valve (see Replacement Parts, page 19)

3. Construction debris clog ging pilot orifice
4. Low gas pressure 5. Control valve knob is not on the PILOT position 6. Kinked pilot line
7. Bad valve

Pilot will not stay lit

1. Loose wiring on thermopile to control valve.
1. Check wiring connections. Refer to wiring diagrams on page 15 2. Have a qualified technician check millivolts 3. Have a qualified technician replace valve (see Replace ment Parts and Accessories , page 19)
2. No millivolt current is being sent back to regulator 3. If valve knob and wall switch are in the ON position, prob able defective control valve

No gas to burner, although wall switch and valve are set to the ON position

1. Wall switch wires defective
1. Check electrical connections and wires for continuity 2. See Pilot will not stay lit , above
2. Thermopile or sensor not generating sufficient voltage
1. Pilot flame may be too low, causing safety pilot to “drop out”
1. Clean and adjust pilot flame for maximum flame impinge ment on thermopile

Pilot goes out when wall switch is ON

1. Millivolt output on thermo pile too high
1. Have a qualified technician replace thermopile

Frequent pilot outage

Page 18 of the FMI GL36STP user manual — OBSERVED PROBLEM
Page 18 · click to enlarge
Page 18

Troubleshooting

Electronic ignition system Note: Before troubleshooting the system, make sure the gas shutoff valve is ON. The two most common causes of a malfunctioning gas appliance are: 1. Loose wiring connections 2. Construction debris clogging the pilot and/or gas control valve filter

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

Pilot will not light

1. No gas supply or shutoff valve is OFF 2. Construction debris clog ging pilot orifice
1. Check to see if you have gas supply 2. Remove debris and dirt, in spect and clean any other possible obstructions 3. Contact your gas supplier 4. Refer to section on pilot lighting 5. Have a qualified technician replace pilot line 6. Replace control valve (see Replacement Parts and Acces sories , page 19)
3. Low gas pressure 4. Control valve knob is not on the PILOT position 5. Kinked pilot line
6. Bad valve

Pilot will not stay lit

1. Loose wiring on thermopile to regulator valve. No mil livolt current is being sent back to regulator 2. If valve knob and wall switch are in the ON position, prob able defective control valve
1. Check wiring connections. Refer to wiring diagrams on page 16
2. Have a qualified technician replace valve (see Replace ment Parts and Accessories , page 19)

No gas to burner, although wall switch and valve are set to the ON position

1. Wall switch wires defective
1. Check electrical connections and wires for continuity 2. See Pilot will not stay lit , above
2. Thermocouple generator or sensor not generating suf ficient voltage
1. Pilot flame may be too low, causing safety pilot to “drop out”
1. Clean and adjust pilot flame for maximum flame impinge ment on thermopile

Pilot goes out when wall switch is ON

1. Output on flame sensor too high
1. Replace flame sensor

Frequent pilot outage

Page 19 of the FMI GL36STP user manual — Cabinet Style Door Kit -
Page 19 · click to enlarge
Page 19

Replacement Parts and Accessories

Purchase these fireplace replacement parts and accessories from your local dealer. If they can not supply these parts, call FMI PRODUCTS, LLC at 1-866-328-4537 for referral information. You can also write to the address listed on the back page of this manual. Before ordering, please have your appliance’s model name or number and part number of the item(s) you are ordering ready. The model name or number for your particular appliance may be found on the rating label located inside the appliance.

Burner Assembly - 23439 For use with all models.

ON/OFF Remote Control Kit - MLCR For Millivolt Units Only - Batteries required for receiver and transmitter.

Vent Hood - AK4 For use with all models.

Millivolt Valve Natural Gas - 14512 Propane/LP Gas - 14513

Refractory Side Refractory - 23519 Bottom Refractory - 23516 Face - 112139-01 For use with all models.

Electronic Valve Natural Gas - 14569 Propane/LP Gas - 14570

Grate Assembly - 11159 For use with all models.

Millivolt Pilot Assembly Natural Gas - 112784-01 Propane/LP Gas - 112784-02

Log Set Assembly - 25793 Bottom Rear Log - 25795 Bottom Front Log - 25794 Top Left Log - 25797 Top Center Log - 25672 Top Right Log - 25796 For use with all models.

Electronic Pilot Assembly Natural Gas - 108866-01 Propane/LP Gas - 108866-02

Transformer - 14129 For use with all models.

"B-1 Type" Vent Pipe For use with all models. Any B-1 type, 6" diam eter, gas vent pipe may be purchased from your local vent manufacturer.

piezo igniter - 14261 For use with all models.

orifice Natural Gas - 23105 Propane/LP Gas - 23106 For use with all models.

Cabinet Style Door Kit -

Wall Switch Kit - 22180 Wall Switch - 14112 Cover Plate - 14113 For use with all models.

DBGL36ST Black For use with all models.

Ignition Control - 110286-01 For use with all models.

Gas Valve Conversion Kit Millivolt Propane/LP Gas - PC-GL36 Millivolt Natural Gas - NC-GL36 Electronic Propane/LP Gas - PC-GL36E Electronic Natural Gas - NC-GL36E

DBBGL36ST Brushed Brass · DCGL36ST Platinum

Page 20 of the FMI GL36STP user manual — FMI PRODUCTS, LLC LIMITED WARRANTIES
Page 20 · click to enlarge
Page 20

Warranty

KEEP THIS WARRANTY

Model (located on product or identification tag)

Serial No. (located on product or identification tag)

Keep receipt for warranty verification.

FMI PRODUCTS, LLC LIMITED WARRANTIES

New Products Standard Warranty: FMI PRODUCTS, LLC warrants this new product and any parts thereof to be free from defects in material and workmanship for a period of two (2) year from the date of first purchase from an authorized dealer provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s warnings and instructions. For products purchased for commercial, industrial or rental usage, this warranty is limited to 90 days from the date of first purchase.

Factory Reconditioned Products Limited Warranty: FMI PRODUCTS, LLC warrants factory reconditioned products and any parts thereof to be free from defects in material and workmanship for 30 days from the date of first purchase from an authorized dealer provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s warnings and instructions.

Terms Common to All Warranties The following terms apply to all of the above warranties: Always specify model number and serial number when contacting the manufacturer. To make a claim under this warranty the bill of sale or other proof of purchase must be presented. This warranty is extended only to the original retail purchaser when purchased from an authorized dealer, and only when installed by a qualified installer in accordance with all local codes and instructions furnished with this product. This warranty covers the cost of part(s) required to restore this product to proper operating condition and an allowance for labor when provided by a FMI PRODUCTS, LLC Authorized Service Center or a provider approved by FMI PRODUCTS, LLC. Warranty parts must be obtained through authorized dealers of this product and/or FMI PRODUCTS, LLC who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty. Travel, handling, transportation, diagnostic, material, labor and incidental costs associated with warranty repairs, unless expressly covered by this warranty, are not reimbursable under this warranty and are the responsibility of the owner. Excluded from this warranty are products or parts that fail or become damaged due to misuse, accidents, improper installation, lack of proper maintenance, tampering, or alteration(s). This is FMI PRODUCTS, LLC’s exclusive warranty, and to the full extent allowed by law; this express war ranty excludes any and all other warranties, express or implied, written or verbal and limits the duration of any and all implied warranties, including warranties of merchantability and fitness for a particular purpose to two (2) year on new products and 30 days on factory reconditioned products from the date of first purchase. FMI PRODUCTS, LLC makes no other warranties regarding this product. FMI PRODUCTS, LLC’s liability is limited to the purchase price of the product, and FMI PRODUCTS, LLC shall not be liable for any other damages whatsoever under any circumstances including indirect, incidental, or consequential damages. Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. For information about this warranty contact:

2701 S. Harbor Blvd. Santa Ana, CA 92704

55173 Rev. H 09/09

1-866-328-4537 www.fmiproducts.com

Date Purchased

Ask about the FMI GL36STP

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the FMI GL36STP

Be the first to ask — other owners or our team will answer.