Residential Wood Burning Fireplace OWNER’S OPERATION AND INSTALLATION MANUAL

PFS ®

F48H(I)(R), VF48H(I)(R)

Plantation 48" Wood Burning Fireplace with Herringbone

US C

IF FIREPLACE IS TO BE INSTALLED DIRECTLY ON ANY COMBUSTIBLE MATERIAL, A HEARTH SPACER IS REQUIRED.

SAVE THIS BOOK This book is valuable. In addition to instructing you on how to install and maintain your appliance, it also contains information that will enable you to obtain re- placement parts or accessory items when needed. Keep it with your other important papers.

This fireplace is approved for use as a wood burning fire- place or for use with a vented gas log approved to ANS Z21.60 or Z21.84 standards or for use with a vent-free gas log heater approved to ANS Z21.11.2 standard.

This wood burning fireplace complies with UL127-CAN/ULC- S610-M87 standard as a FACTORY BUILT APPLIANCE.

FOR CANADA: The authority having jurisdiction (such as the municipal building department, fire department, etc.) should be contacted before installation to deter- mine the need to obtain a permit.

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.

For more information, visit www.fmiproducts.com

and WCM-48F · Masonry Brick

Page 2 of the FMI F48H(I)(R) user manual — Safety
Page 2 · click to enlarge
Page 2

Table of Contents Safety 2 Specifications 3 Installation 4

Operation and Maintenance 16 Technical Service 18 Replacement and Accessory Parts 18

Safety

This fireplace is not intended to be used as a substitute for a fur- nace to heat an entire home. Use for supplemental heat only.

  • Before beginning the installation of the fireplace, read these instructions through completely.
  • This FMI PRODUCTS, LLC fireplace and its components are safe when installed according to this installation manual. Unless you use FMI PRODUCTS, LLC components, which have been designed and tested for the fireplace system, you may cause a fire hazard.
  • The FMI PRODUCTS, LLC warranty will be voided by and FMI PRODUCTS, LLC disclaims any responsibility for the following actions. a. Modification of the fireplace, com-
  • FOR YOUR SAFETY
  • Do not store or use gasoline or any other flammable vapors or liquids in the vicinity of this or any other appliance.
  • Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
  • Do not place clothing or other flammable materials on or near the appliance.
  • Never leave children unattended when a fire is burning in the fireplace.

ponents, doors, air inlet system and damper control. b. Use of any component part not manufac-

tured or approved by FMI PRODUCTS, LLC in combination with a FMI PROD- UCTS, LLC fireplace system. Proper installation is the most important step in ensuring safe and continuous operation of the fireplace. Consult the local building codes as to the particular requirements concerned with the installation of all factory built fireplaces.

Page 3 of the FMI F48H(I)(R) user manual — Specifications Models F48H(I)(R) and VF48H(I)(R)
Page 3 · click to enlarge
Page 3

Safety

FMI F48H(I)(R) — Safety diagram (page 3)
Fig. 1 · Safety

Specifications Models F48H(I)(R) and VF48H(I)(R)

FMI F48H(I)(R) — Specifications Models F48H(I)(R) and VF48H(I)(R) diagram (page 3)
Fig. 2 · Specifications Models F48H(I)(R) and VF48H(I)(R)

12.875" Secure Fireplace To Hearth Spacer Using Straps Provided

*With Hearth Spacer

Page 4 of the FMI F48H(I)(R) user manual — Specifications Models F48H(I)(R) and VF48H(I)(R)
Page 4 · click to enlarge
Page 4

selecting Fireplace location To determine the safest and most efficient location for the fireplace, you must take into consideration the following guidelines: 1. The location must allow for proper clear- ances (see Figures 1 and 2). 2. Consider a location where the fireplace will not be affected by drafts, air condition- ing ducts, windows or doors. 3. A location that avoids the cutting of joists or roof rafters will make installation easier. 4. An outside air kit is available with this fireplace (see Optional Outside Air Kit on page 5).

on a hearth spacer designed for use with this fireplace (see Replacement and Ac- cessory Parts, page 18). 3. Set the fireplace directly in front of this opening and slide the unit back until the nailing flanges touch the side framing. 4. Check the level of the fireplace and shim with sheet metal if necessary. 5. Before securing fireplace to prepared fram- ing, the ember protector (provided) must be placed between the hearth extension (not supplied) and under the bottom front edge of the fireplace to protect against glowing embers falling through. If the fireplace is to be installed on a raised platform, a Z- type ember protector (not supplied) must be fabricated to fit your required platform height. The ember protector should extend under the fireplace a minimum of 1 1/2". The ember protector should be made of galva- nized sheet metal (28 gauge minimum to prevent corrosion. 6. Using screws or nails, secure the fireplace to the framing through flanges located on the sides of the fireplace.

Minimum clearance to combustibles Back and sides of fireplace 1 1/2" min.* Front of fireplace 48" min. Floor** 0" min. Perpendicular wall to opening 18" min. Top spacers 0" min. Mantel clearance see Mantels, page 5 Chimney outer pipe surface 2" min. * Not required at nailing flanges ** See step 2 of Framing

FMI F48H(I)(R) — Specifications Models F48H(I)(R) and VF48H(I)(R) diagram (page 4)
Fig. 3 · Specifications Models F48H(I)(R) and VF48H(I)(R)

Minimum/Maximum Chimney Height The minimum height of the chimney, mea- sured from the base of the fireplace to the flue gas outlet of the termination, is 16 feet for straight flue or a flue with one elbow set. The maximum distance between elbows is 6 feet. For systems with two elbow sets, the minimum height is 22 feet. The maximum height of any system is 50 feet. This measurement includes the fireplace, chimney sections and the height of the termination assembly at the level of the flue gas outlet (see Figure 15, page 9).

31.625" Secure Fireplace To Hearth Spacer Using Straps Provided (Sides and Rear)

* With Hearth Spacer

Figure 1 - Framing Dimensions

Maintain 1 1/2" Clearance at Sides and

FMI F48H(I)(R) — Specifications Models F48H(I)(R) and VF48H(I)(R) diagram (page 4)
Fig. 4 · Specifications Models F48H(I)(R) and VF48H(I)(R)

1 1/2" Clearance Not Required at Nailing Flanges

Framing 1. Frame the opening for the fireplace using the dimensions shown in Figures 1 and 2. 2. If the fireplace is to be installed directly on carpeting, tile (other than ceramic) or any combustible material including wood flooring, the fireplace must be installed

Figure 2 - Corner Installation

Page 5 of the FMI F48H(I)(R) user manual — Specifications Models F48H(I)(R) and VF48H(I)(R)
Page 5 · click to enlarge
Page 5

Hearth Extension A hearth extension projecting a minimum of 20" in front of and a minimum of 12" beyond each side of the fireplace opening is required to protect combustible floor construction in front of the fireplace. Fabricate a hearth extension using a material which meets the following specifications: a layer of noncom- bustible, inorganic material having a thermal conductivity of K=0.84 BTU IN/FT, HR. F (or less) at 1" thick. For example, if the material selected has a K factor of 0.25, such as glass fiber, the following formula would apply: 0.25 x 1.0" = 0.30" thickness required 0.84 Thermal conductivity "K" of materials can be obtained from the manufacturer or supplier of the noncombustible material. If the hearth ex- tension is to be covered, use noncombustible material such as tile, slate, brick, concrete, metal, glass, marble, stone, etc. Provide a means to prevent the hearth extension from shifting and seal gap between the fireplace frame and hearth extension with a noncom- bustible material (see Figure 3).

Mantels A mantel may be installed if desired (see Figure 4). Woodwork such as wood trims, mantels or any other combustible material projecting from the front face must not be placed within 12" of the fireplace opening. Combustible materials above 12" and pro- jecting more than 1 1/2" from the fireplace must not be placed less than 15" from the top opening of the fireplace (NFPA STD 211, Sec. 7-3.3.3). Mantels or any other combustible material also may come up to the side edge of the black metal face of the fireplace just as long as the projection from the front face fall within the limit shown in Figure 4.

12 1/" Ref. 4 6" Ref. 33° 3" Nom. 15" Min.11/" Max. 2 Min. 12"

Safe Zone for Projection of Combustible Materials

Seal Gap Fireplace Front

Figure 4 - Mantel Clearances to

Fireplace Front Raised Hearth

Optional Outside air Kit (Model ak4/ak4f) Installation of an outside air kit should be per- formed during rough framing of fireplace due to nature of it's location. Outside combustion air is accessed through a vented crawl space (AK4F) or through a sidewall (AK4). This fire- place is equipped with a barometric damper which allow outside air to flow into fireplace automatically when needed.

Figure 3 - Hearth Extension

Show 11 more labels / short text on this page
Combustible Material · Upper Section of · Fireplace · Ember Protector · Fireplace Opening · Combustible Material · Ember Protector · Hearth Extension · Fireplace Front Elevated · Seal Gap · Ember Protector
Page 6 of the FMI F48H(I)(R) user manual — Specifications Models F48H(I)(R) and VF48H(I)(R)
Page 6 · click to enlarge
Page 6
LINEAL GAIN PART NO.DESCRIPTIONGAIN (IN) 48" PlantationFireplace66 1/ 2" 12-12DM 12-12HTPipe Section10 5/ 8" 18-12DM 18-12HTPipe Section16 5/ 8" 24-12DM 24-12HTPipe Section23 5/ 8" 36-12DM 36-12HTPipe Section34 5/ 8" 48-12DM 48-12HTPipe Section46 5/ 8" RLT-12D RLT-12HTRound Termination7 3/ 4"* STL-12DSquare ChaseTop with Slip Section7" to 15"*

The maximum height for the air vent can not exceed 3 feet below the flue gas outlet of the termination.

Secure to Collars with Metal Tape, Screws or Straps (Min. of 1/4" x 20" in size)

Air Inlet Location Must Allow For Bushes or Snow

* The lineal gain for the terminations is mea- sured to the flue gas outlet height.

15" Galvanized Outer Pipe

Hemmed End 12 3/8" Stainless Inner Pipe

Air Inlet Eyebrow Vented Crawl Space (Check Local Codes Before Installing in a Vented Crawl Space)

Vent Hood Required for Wall Installation

Figure 6 - Lineal Gain

Assembly and installation of double wall chimney system Each double wall chimney section consists of a galvanized outer pipe, a stainless steel in- ner flue pipe and a wire spacer. Pipe sections must be assembled independently as chimney is installed. When connecting chimney directly to fireplace, inner flue pipe section must be installed first with lanced side up. Outer pipe section can then be installed over flue pipe section with hemmed end up. Press down on each pipe section until lances securely engage hem on fireplace starter. Wire will assure proper spacing between inner and outer pipe sections. Continue to assemble chimney sections as outlined above, making sure both inner and outer pipe sections are locked together. When installing double wall snap-lock chimney to- gether, it is important to assure joint between chimney sections is locked. Check by pulling chimney upward after locking. Chimney will not come apart if properly locked. It is not necessary to add screws to keep chimney together (exception, see Figure 9, page 8).

Figure 5 - Outside Air Kit

Chimney Pipe FMI PRODUCTS, LLC chimney system consists of 12", 18", 24", 36"' and 48" snap- lock, double-wall pipe segments, planned for maximum adaptability to individual site requirements. Actual lengths gained after fit- ting overlaps must be taken into consideration (lineal gain) and are given in lineal gain chart (see Figure 6). Lineal gain is the actual mea- surable length of a part after two or more parts are connected. For Canada, use chimney parts designated "HT".

FMI F48H(I)(R) — Specifications Models F48H(I)(R) and VF48H(I)(R) diagram (page 6)
Fig. 5 · Specifications Models F48H(I)(R) and VF48H(I)(R)
Page 7 of the FMI F48H(I)(R) user manual — 12S-12DM
Page 7 · click to enlarge
Page 7

Continued Using ELBOW offsets (30E-12DM) 1. To achieve desired offset, you may install combinations of 12", 18", 24", 36" and 48" length of double wall pipe (see offset chart and Figure 7).

2. Chimney weight above offset rests on re- turn elbow. Straps must be securely nailed to rafters or joists (see Figure 8, details A and B). 3. Maximum length of pipe between supports (return elbow or 12S-12DM) is 6' of angle run. Maximum of two 6' angle run sections per chimney system (see Figure 7). 4. All pipe connections between the offset and return must be secured with two screws on the outer pipe only (see Figure 9, page 8). Do not penetrate the inner stainless.

OFFSETRISECHIMNEY LENGTH AB12"18"24"36"48" 4 3/" 816 3/" 8ELBOW SET ONLY 9 3/" 425 1/" 21 12 3/" 430 3/" 41 15"34 3/" 41 18"40"11 21 1/" 446 1/" 41 23 3/" 449 1/" 411 27 3/" 456 3/" 41 30"60 3/" 411 33"66"1 36"71"11 38 1/" 475"2 41 1/" 480 1/" 4111 45"86 3/" 42 46 3/" 489 1/" 2111 51"97"11 53 1/" 4101"2 56 1/" 4106 1/" 42 59 1/" 4111 1/" 2111 61 3/" 4115 1/" 212 64 3/" 4120 3/" 412 68 1/" 4127"21 70"130"112 74 1/" 4137 1/" 2121 76 3/" 4141 1/" 2121 79 3/" 4146 3/" 44
See Detail A 2" Min. Straps Straps Detail B See Detail B Angle Firestop raps StrapsSeeDetail A
FMI F48H(I)(R) — 12S-12DM diagram (page 7)
Fig. 6

Figure 8 - Ceiling Support Pipe

12S-12DM

OFFSET CHART (22-50 FT. SYSTEM HEIGHT)

FMI F48H(I)(R) — 12S-12DM diagram (page 7)
Fig. 7

Figure 7 - Typical Offset Terminations

Return Elbow

Page 8 of the FMI F48H(I)(R) user manual — B
Page 8 · click to enlarge
Page 8

Penetrating roof To maintain a 2" clearance to pipe on roof with a pitch, a rectangular opening must be cut. 1. Determine center point through which pipe will penetrate roof. 2. Determine center point of roof. Pitch is the distance the roof drops over a given span, usually 12". 3. Use roof opening chart (Figure 12) to determine correct opening length and flashing required. 4. Remove shingles around opening mea- sured. Cut out this section. 5. Add next sections of pipe until end penetrates roof line. Check to see that proper clearances are maintained. Extend chimney by adding sections of double wall pipe until pipe is minimum of 30" above highest point of roof cutout. Termination and chimney must extend a minimum of 36" above highest point where it passes through roof.

B

A

Figure 9 - Elbow Offset

Firestop Spacers (FS-10) Firestop spacers are required at each point where chimney penetrates a floor space. Their purpose is to establish and maintain required clearance between chimney and combustible materials. When pipe passes through a framed opening into a living space above, firestop must be placed onto ceiling from below as shown in Figure 10. They also provide complete separation from one floor space to another or attic space as required by most codes. When the double wall pipe passes through a framed opening into an attic space, the firestop must be placed into an attic floor as shown in Figure 11.

FMI F48H(I)(R) — B diagram (page 8)
Fig. 8
FMI F48H(I)(R) — B diagram (page 8)
Fig. 9

Screws or Staples (Min. of 8)

PitchSlopeOpening "A" Max.Used Flashing Model No. Flat0°19.5"V6F-10DM 0-6/1226.6°22'V6F-10DM 6/12-12/1245.0°27"V12F-10DM

Figure 10 - Firestop Spacer with Living

Figure 12 - Roof Opening Measurements

FMI F48H(I)(R) — B diagram (page 8)
Fig. 10

Figure 11 - Firestop Spacer with Attic

Show 5 more labels / short text on this page
Screws · Existing Ceiling Frame · Firestop Spacer · Space Above Ceiling · Space Above Ceiling
Page 9 of the FMI F48H(I)(R) user manual — 12S-12DM
Page 9 · click to enlarge
Page 9

Continued Flashing installation (v6f-10dm or v12f-10dm) Determine flashing to be used with roof open- ing chart. Slide flashing over pipe until base is flat against roof. Replace as many shingles as needed to cover exposed area and flashing base. Secure in position by nailing through shingles (see Figure 13). DO NOT NAIL THROUGH FLASHING CONE.

Terminations/Spark Arrestor Fireplace system must be terminated with listed round top or chase terminations. In any case, refer to installation instructions supplied with termination.

FMI F48H(I)(R) — 12S-12DM diagram (page 9)
Fig. 11
FMI F48H(I)(R) — 12S-12DM diagram (page 9)
Fig. 12
FMI F48H(I)(R) — 12S-12DM diagram (page 9)
Fig. 13

Figure 13 - Flashing Installation

Installing Flashing on a Metal Roof When installing the flashing on a metal roof, it is required that putty tape be used between the flashing and the roof. The flashing must be secured to the roof using #8 x 3/4" screws and then sealed with roof coating to prevent leak- age through the screw holes. A roof coating must also be applied around the perimeter of the flashing to provide a proper seal.

Overlap Shingles (Top and Sides of Flashing Base)

Figure 15 - Termination

Chase installations Instructions for chase installations are includ- ed with the chase style termination chosen. In a multiple chase installation, be sure to provide adequate distance between termi- nations to prevent smoke spillage from one termination to another. Terminations must be separated a minimum of 24" center to center and stacked at a minimum vertical height dif- ference of 18" (see Figure 16, page 10). Note: If a decorative shroud is to be installed, contact the manufacturer for specifications.

Storm Collar Installation (SC2-1) Place storm collar over pipe and slide down until it is snug against open edge of flashing (see Figure 14). Apply waterproof caulk around perimeter of collar to provide a proper seal.

FMI F48H(I)(R) — 12S-12DM diagram (page 9)
Fig. 14

Flashing · Underlap Shingles · Chimney Pipe

Page 10 of the FMI F48H(I)(R) user manual — 12S-12DM
Page 10 · click to enlarge
Page 10

Optional Gas Line Installation Gas line hook up should be done by your sup- plier or a qualified service person. Note: Before you proceed, make sure your gas supply is turned off. Use only a 1/2" black iron pipe and appropriate fittings. 1. Remove gas line cover plate located on either side of fireplace and pull out insula- tion from gas line conduit sleeve. Save insulation for reuse. Replace screws. 2. Run a 1/2" black iron gas line into fireplace through rear at gas line conduit sleeve (if us- ing a raised platform, add height). Provide sufficient gas line into fireplace chamber for fitting connection (see Figure 18). Note: Secure incoming gas line to wood framing to provide rigidity for threaded end. 3. Repack insulation around gas line and into sleeve opening. Seal any gaps between gas line and refractory knockout hole with refractory cement or commercial furnace cement, Install the gas appliance or cap-off gas line if desired.

FMI F48H(I)(R) — 12S-12DM diagram (page 10)
Fig. 15

18" Min. Typ.

Figure 16 - Multiple Chase Installation

10 foot rule All flue gas outlet chimney terminations must extend a minimum of 3 feet in height above highest point where it passes through the roof and must be at least 2 feet above highest point of the roof that is within a horizontal distance of 10 feet (see Figure 17).

FMI F48H(I)(R) — 12S-12DM diagram (page 10)
Fig. 16
FMI F48H(I)(R) — 12S-12DM diagram (page 10)
Fig. 17

Figure 17 - 10 Foot Rule

finishing fireplace Combustible materials, such as wallboard, gypsum board, sheet rock, drywall, plywood, etc. may make direct contact with sides and top around the fireplace face. It is important that combustible materials do not overlap face itself. Brick, glass, tile or other noncombustible materials may overlap front face provided they do not obstruct essential openings like louvered slots or any other opening. When overlapping with a noncombustible facing material, use only noncombustible mortar or adhesive.

Provide Enough Threaded End for Fitting Connection Figure 18 - Gas Line Installation

Outside of Fireplace

Page 11 of the FMI F48H(I)(R) user manual — Brick Installation
Page 11 · click to enlarge
Page 11

Brick Installation

CAUTION: All gas piping and connections must be tested for leaks after the installation is completed. After ensuring that the gas valve is on, apply soap and water solution to all connections and joints. Bubbles forming show a leak. Correct all leaks at once. DO NOT USE AN OPEN FLAME FOR LEAK TESTING AND DO NOT OPER- ATE ANY APPLIANCE IF A LEAK IS DETECTED. LEAK TESTING SHOULD BE DONE BY A QUALI- FIED SERVICE PERSON.

Each brick housing is stamped with a number (full size bricks are not stamped). These num- bers will help identify the brick when installing. It is important to install these bricks exactly as instructed. Press brick firmly into brick housing until it snaps. Groove line on side of brick will come in contact with flange on brick housing. This secures brick into housing (see Figure 24). Smaller bricks may require a small portion of furnace cement applied to back of brick to secure it until grouting has been completed. Bricks are packaged in separate boxes. Brick matrixes on pages 12 through 15 show how bricks are packaged and placed for each size fireplace and number of bricks per box. There are 2 extra full bricks included in Hearth Brick package. Bricks in brick matrixes are labeled "I" for ivory and "R" for red. Install bricks one section at a time starting with hearth panel followed by the rear panel, left panel and right panel. It is important to install the bricks in sequence. Please note, full size bricks are NOT stamped.

If you install a decorative gas appliance (vented gas log), the decorative gas appliance must comply with the Standard for Decorative Gas Appliance for Installation in Solid Fuel Burning Fireplaces, ANS Z21.60 or Z21.84 and shall also be installed in accordance with the National Fuel Gas Code, ANSI Z223.1/ NFPA 54 latest edition.

Brick Stamped Number Location

Figure 19 - Installing Brick

Flanges · Brick Housing

Page 12 of the FMI F48H(I)(R) user manual — F061 F061
Page 12 · click to enlarge
Page 12

Herringbone Brick Installation

F054 F054 F054 S011

FMI F48H(I)(R) — Herringbone Brick Installation diagram (page 12)
Fig. 18 · Herringbone Brick Installation

S007 S007 S018 S018 S018

S007

S001 S003

S001 S003

S022

FMI F48H(I)(R) — S007 S007 S018 S018 S018 diagram (page 12)
Fig. 19

S015 FULL

S020

FULL

If using Ash Lip Kit, this row of bricks will be replaced.

F061 F061

Glass Door Kit available for this fireplace CAN NOT be used with Ash Lip Kit

Rear Upper · Refractory

Page 13 of the FMI F48H(I)(R) user manual — HEARTH RED IVORY QTY FULL (112140-01)
Page 13 · click to enlarge
Page 13

REAR UPPER REFRACTORY

REAR LOWER REFRACTORY

RED IVORY QTY FULL (112140-02)

RED IVORY QTY FULL (112140-02)

FULL (112140-06) 24 F054R F054W 3 S002R S002W 1 S005R S005W 2 S006R S006W 2 S007R S007W 3 S008R S008W 1 S011R S011W 1 S013R S013W 1 S014R S014W 8 S015R S015W 2 S016R S016W 2 S017R S017W 1 S018R S018W 3 S020R S020W 6

FULL (112140-06) 10 F055R F055W 3 S001R S001W 2 S002R S002W 8 S003R S003W 2 S004R S004W 2 S005R S005W 2 S006R S006W 2 S008R S008W 1 S010R S010W 1 S011R S011W 1 S022R S022W 1

LEFT REFRACTORY RED IVORY QTY FULL (112140-02)

RIGHT REFRACTORY RED IVORY QTY FULL (112140-02)

FULL (112140-06) 21 F049R F049W 9 F050R F050W 1 F052R F052W 1 F054R F054W 1 F055R F055W 1 S005R S005W 1 S006R S006W 1 S012R S012W 1 S015R S015W 1 S016R S016W 1 S020R S020W 11 S031R S031W 3 S032R S032W 1 S033R S033W 1 S034R S034W 1 S035R S035W 1 S036R S036W 1 S037R S037W 1 S038R S038W 1 S039R S039W 1 S040R S040W 1 S041R S041W 1 S042R S042W 1

FULL (112140-06) 21 F049R F049W 9 F050R F050W 1 F051R F051W 1 F053R F053W 1 F054R F054W 1 F055R F055W 1 F056R F056W 1 S005R S005W 1 S006R S006W 1 S014R S014W 1 S015R S015W 1 S016R S016W 1 S019R S019W 3 S020R S020W 11 S021R S021W 1 S023R S023W 1 S024R S024W 1 S025R S025W 1 S026R S026W 1 S027R S027W 1 S028R S028W 1 S029R S029W 1 S030R S030W 1

HEARTH RED IVORY QTY FULL (112140-01)

FULL (112140-05) 21* F007R F007W 2 F008R F008W 2 F023R F023W 2 F025R F025W 2 F061R F061W 2 *Includes 2 Extra Bricks

Page 14 of the FMI F48H(I)(R) user manual — REAR UPPER REFRACTORY
Page 14 · click to enlarge
Page 14

Grouting instructions Material provided: 1 or 2 - 10 lb. bags of cement (depending on model) 1 or 2 - 10 lb. bags of sand (depending on model) Material required: 1 - Piping bag 1 - Joints striker 1 - Heavy duty mixing bucket 1 - Trowel 1. Moisten brick surface with damp sponge or spray bottle just prior to application. When bricks are wet, any excess grout mixture on bricks will easily wipe off. 2. In a heavy duty mixing bucket, pour 4 ½ cups of water. Add 5 lbs. (half of a bag) of sand and 5 lbs (half of a bag) of cement. Mix together well using a power drill with mixing wand attachment to a yogurt like consistency. Not adding enough was can lead to grout falling out after burning. 3. The overall length of piping bag should be about 16". If the bag is longer than 16", cut it down to size by removing end with larger opening. This will make the bag easier to handle. 4. Put 2 to 3 cups of grout mixture into piping bag making sure the smaller opening is downward and over a moist towel to avoid spilling. Place a wet towel over the bucket making sure it is directly on the surface of grout mixture. This will keep the mixture moist and it will not dry out before use. 5. Begin grouting by first doing a “Filler Pass”. This is done by filling the joint about 3/4 full with grout mixture. It is important to work with only 6 bricks at a time so grout doesn't have time to set up before striking. 6. Complete a “Finishing Pass” around 6 bricks you just put filler pass around. This is done by slowly filling in remainder of the joint with a thick amount of grout mixture. Mixture should be a little higher than the brick surface. 7. Using a trowel, remove excess grout mix- ture by moving trowel in the direction of the joint. Grout mixture in the joint should now be flush with brick surface. If not enough grout is applied into each space,

grout may fall out after burning. 8. Using a joint striker, force grout mixture into joint and sweep back and forth until grout is smooth and round. If grout becomes too shallow, add more grout mixture with piping bag and strike again. 9. Continue procedure around each group of 6 bricks until an entire panel is finished. 10. Using trowel, scrape in direction of joints to remove any grout that may have col- lected around bricks during striking. If desired, take a moist sponge and lightly sweep over bricks to remove any grout that may have gotten on bricks. DO NO PRESS HARD OR RUB IN A CIRCULAR MOTION. This will press the grout into brick and turn brick a different color.

Allow 72 hours before operating fireplace.

FMI F48H(I)(R) — REAR UPPER REFRACTORY diagram (page 14)
Fig. 20

Figure 20 - Grouting Brick

INSTALLING SCREEN 1. Mount screen rod brackets on left and right side of firebox with #8 x 1/2" screws provided (see Figure 21, page 15). 2. Slide round end of screen rod into rings at top of screen. Attach one push-on nut to end of rod before attaching last ring of screen. 3. Insert round end of rod into rod bracket on left side of fireplace. 4. Mount flat end of screen rod with #10 x 5/8" to center of smoke shelf (see Figure 21, page 15). 5. Install other screen rod in same manner.

Page 15 of the FMI F48H(I)(R) user manual — Installing Glass Door and Rail
Page 15 · click to enlarge
Page 15
FMI F48H(I)(R) — Installing Glass Door and Rail diagram (page 15)
Fig. 21 · Installing Glass Door and Rail
FMI F48H(I)(R) — Installing Glass Door and Rail diagram (page 15)
Fig. 22 · Installing Glass Door and Rail

Figure 21 - Installing Fireplace Screen

Installing Glass Door and Rail

Figure 22 - Securing Door Rails to

FMI F48H(I)(R) — Installing Glass Door and Rail diagram (page 15)
Fig. 23 · Installing Glass Door and Rail

Rail installation 1. Remove screws securing top face to firebox (see Figure 22). 2. Align holes on rail to be installed at top and replace screws. Note: Door rails are identical until spring clips are in place. 3. Using remaining door rail as a template, place along front row of bricks at bottom making sure rail front surface is flush with fireplace bottom face surface. Mark hole centers and remove rail (see Figure 22). 4. Drill 9 - 5/32" diameter holes about 1" deep directly into bricks using a 5/32" concrete drill bit (not provided). 5. Place rail back on bricks and align holes. Secure using 9 concrete screws provided with glass door kit. 6. Secure retaining clips to top and bottom rails (see Figure 23).

Figure 23 - Mounting Door Retaining

Fireplace · Clips

Page 16 of the FMI F48H(I)(R) user manual — Installing Glass Door and Rail
Page 16 · click to enlarge
Page 16

Installing Glass Doors After spring clips have been installed some adjustments may be needed. Install the doors using the following steps: 1. With bi-fold doors completely folded, insert bottom pivot pin into bottom retaining clip located at far left and far right side of bot- tom rail. Swing door to vertical position making sure top pins slide into top door rail. Door is installed when top door pin snaps into spring clip (see Figure 24).

2. Repeat step 1 for remaining door. If you find the doors do not close properly or do not appear level or straight, proceed with section on door adjustment.

Door Adjustment Remove doors and slightly loosen upper spring clips. Replace and fully close doors. Use 1/8" shims (any material) to level doors. Once proper setting is achieved, carefully open doors enough to access top retaining clips with a phillips screwdriver. Tighten screws. See Figure 25.

FMI F48H(I)(R) — Installing Glass Door and Rail diagram (page 16)
Fig. 24 · Installing Glass Door and Rail
FMI F48H(I)(R) — Installing Glass Door and Rail diagram (page 16)
Fig. 25 · Installing Glass Door and Rail

Figure 25 - Adjusting Bi-Fold Doors

Figure 24 - Installing Doors

Operation and Maintenance Glass Doors Glass doors are optional with fireplace. When fireplace is in operation, doors must be fully opened or fully closed position only or a fire hazard may be created (see Figure 26). A fireplace equipped with glass doors oper- ates much differently than a fireplace with an open front. A fireplace with glass doors has a limited amount of air for combustion. Excessive heat within the fireplace can result if too large a fire is built or if combustion air gate is not completely open. The following tips should be followed to assure that both the fireplace and glass door retain their beauty and func- tion properly. Both the flue damper and glass doors must be fully opened before starting fire. This will provide sufficient combustion air and maintain safe temperatures in firebox.

FMI F48H(I)(R) — Installing Glass Door and Rail diagram (page 16)
Fig. 26 · Installing Glass Door and Rail

Figure 26 - Bi-Fold Glass Doors

Partially Opened Door · Bottom Retaining Clip

Page 17 of the FMI F48H(I)(R) user manual — FULLY OPEN POSITION
Page 17 · click to enlarge
Page 17

Operation and maintenance

IMPORTANT: The glass must be allowed to warm slowly and evenly. Such materials as pitch/wax laden logs, very dry mill end lumber and large amounts of paper or cardboard boxes can create an excessively hot fire and should not be burned in this fireplace. Always keep the fire well back from the doors and never allow flames to contact the glass.

FULLY CLOSED POSITION

Retaining Bracket (Holds Damper Door Closed)

Cleaning Glass Clean glass with any commercial glass cleaner or soap and water. Do not use any abrasive material to clean glass. Do not clean glass with any cool water if glass is still hot from the fire and smoke. A gas line or gas log lighter may be installed for the purpose of installing a vented or vent- free decorative gas appliance incorporating an automatic shutoff device and complying with the Standard for Decorative Gas Appliances for Installation in Vented Fireplaces, ANSI Z21.60 or American Gas Association draft requirements for Gas Fired Log Lighters for Wood Burning Fireplaces, Draft NO. 4 dated August, 1993. If you wish to install an unvented (vent-free) gas log set, only unvented gas log sets which have been found to comply with the standard for unvented room heaters, ANSI Z21.11.2 are to be installed in this fireplace.

Swing Door Down to Open

FULLY OPEN POSITION

Secondary Retaining Bracket (Holds Damper Door Open)

damper handle operation The damper handle opens and closes the damper blade and is located in the upper rear side of fireplace just above rear bricks. Rotate handle counterclockwise slightly to disengage from retaining bracket. Swing slowly toward opening of fireplace. Engage handle to sec- ondary bracket located at front of fireplace inner wall (see Figure 27).

Swing Door Up to Close

Figure 27 - Operating Damper Handle

Damper Handle

Page 18 of the FMI F48H(I)(R) user manual — Ember Protector - 20093
Page 18 · click to enlarge
Page 18

Technical Service

You may have further questions about in- stallation, operation, or troubleshooting. If so, contact FMI PRODUCTS, LLC at 1-866-328-4537. When calling please have your model and serial numbers of your heater ready.

You can also visit our web site at www.fmiproducts.com

Replacement and Accessory Parts

FMI F48H(I)(R) — Replacement and Accessory Parts diagram (page 18)
Fig. 27 · Replacement and Accessory Parts

Optional Outside air kit for floor installation - ak4f

Bi-Fold Glass Masonry Door BDMO48E - 48" Ebony BDMO48G - 48" Pewter BDMO48C - 48" Oiled Bronze

FMI F48H(I)(R) — Optional Outside air kit for floor installation - ak4f diagram (page 18)
Fig. 28 · Optional Outside air kit for floor installation - ak…

Optional Outside Air Kit for Sidewall Installation - AK4

Double Wall Pipe - 12-12DM, 18-12DM, 24-12DM, 36-12DM, 48-12DM, 12-12HT, 18-12HT, 24-12HT, 36-12HT and 48-12HT

Storm Collar - SC2-1

30° Offset and Return 30E-12DM and 30E-12HT

FMI F48H(I)(R) — Storm Collar - SC2-1 diagram (page 18)
Fig. 29 · Storm Collar - SC2-1

Firestop Spacer - FS-10

Grate 109496-01 (for F48 Series) 123277-01 (for WCM-48F Series)

Roof Flashing V6F-10DM - 0 to 6/12 Pitch V12F-10DM - 6/12 to 12/12 Pitch

Ember Protector - 20093

Page 19 of the FMI F48H(I)(R) user manual — Round ToP TErminations RLT-12D and RLT-12HT
Page 19 · click to enlarge
Page 19

Replacement and Accessory Parts

FMI F48H(I)(R) — Replacement and Accessory Parts diagram (page 19)
Fig. 30 · Replacement and Accessory Parts

SQUARE CHASE-TOP TERMINATION - STL-12D

Optional Hearth Spacer HS48

FMI F48H(I)(R) — SQUARE CHASE-TOP TERMINATION - STL-12D diagram (page 19)
Fig. 31

Round ToP TErminations RLT-12D and RLT-12HT

24" Round Woodnook - DHR-24

FMI F48H(I)(R) — Round ToP TErminations RLT-12D and RLT-12HT diagram (page 19)
Fig. 32 · Round ToP TErminations RLT-12D and RLT-12HT
FMI F48H(I)(R) — Round ToP TErminations RLT-12D and RLT-12HT diagram (page 19)
Fig. 33 · Round ToP TErminations RLT-12D and RLT-12HT

Optional ASH LIP KIT (Bricks) AL48 - Red Brick AL48I - Ivory Brick

Page 20 of the FMI F48H(I)(R) user manual — SQUARE CHASE-TOP TERMINATION - STL-12D
Page 20 · click to enlarge
Page 20

2701 S. Harbor Blvd. Santa Ana, CA 92704

122272-01 Rev. D 01/10

1-866-328-4537 www.fmiproducts.com

Ask about the FMI F48H(I)(R)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the FMI F48H(I)(R)

Be the first to ask — other owners or our team will answer.