DIRECT-VENT Fireplace OWNER’S OPERATION AND INSTALLATION MANUAL

FMI CGDV32PR diagram (page 1)
Fig. 1
FMI CGDV32PR diagram (page 1)
Fig. 2

NATURAL GAS “TUDOR” MODELS (V)T32N-A SERIES,

CGDV32NR and CTDV32NR-HA PROPANE/LP GAS “TUDOR” MODELS (V)T32P-A SERIES

— Do not store or use gasoline or other flammable

vapors and liquids in the vicinity of this or any other appliance. — WHAT TO DO IF YOU SMELL GAS

  • Do not try to light any appliance.
  • Do not touch any electrical switch; do not use any phone in your building.
  • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
  • If you cannot reach your gas supplier, call the fire department. — Installation and service must be performed by a quali-

fied installer, service agency or the gas supplier.

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.

For more information, visit www.fmiproducts.com

and CGDV32PR

Page 2 of the FMI CGDV32PR user manual — DANGER: Carbon monoxide poisoning may lead to death!
Page 2 · click to enlarge
Page 2

Table of Contents

Safety 2 Product Identification 4 Local Codes 4 Product Features 4 Pre-Installation Preparation 5 Location of Termination Cap 7 Venting Installation 8 Fireplace Installation 17 Operation 26 Inspecting Burners 29

Cleaning and Maintenance 30 Troubleshooting 32 Replacement Parts 36 Service Hints 36 Technical Service 36 Specifications 36 Accessories 37 Parts 38 Warranty Back Cover

Safety

State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts.

This appliance may be in- stalled in an aftermarket,* permanently located, manufactured (mobile) home, where not prohib- ited by local codes.

This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.

DANGER: Carbon monoxide poisoning may lead to death!

This fireplace must be installed by a qualified (certified or licensed) service person. It has a sealed gas combustion chamber that uses a coaxial pipe (pipe within a pipe and having the same center) venting system. It brings in fresh air for combustion through the outer pipe and combustion gases are exhausted through the inner pipe. If the glass door assembly and venting pipe are not properly seated, con- nected and sealed, carbon monoxide leakage (spillage) can occur.

* AftermarketCompletion of sale, not for purpose of resale, from the manufacturer
Page 3 of the FMI CGDV32PR user manual — Safety
Page 3 · click to enlarge
Page 3

Safety

Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning resemble the flu, with headaches, dizziness or nausea. If you have these signs, the fireplace may not be working properly. Get fresh air at once! Have fireplace serviced. Some people are more af- fected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influ- ence of alcohol and those at high altitudes. Natural and Propane/LP Gas: Natural and propane/LP gases are odorless. An odor- making agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists. Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this fireplace.

Keep the appliance area clear and free from combustible ma- terials, gasoline and other flam- mable vapors and liquids.

Do not place clothing or other flammable material on or near fireplace. Never place any ob- jects on fireplace.

  • 1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless a certified kit is used. 2. For propane/LP fireplace, do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors. To prevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. capacity. 3. If you smell gas
  • shut off gas supply
  • do not try to light any appliance
  • do not touch any electrical switch; do not use any phone in your building
  • immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions
  • if you cannot reach your gas supplier, call the fire department 4. Never install the fireplace
  • in a recreational vehicle
  • in windy or drafty areas where curtains or other combustible (flammable) objects can make contact with the fireplace front
  • in high traffic areas 5. Do not modify this fireplace under any circumstances. Any parts removed for servicing must be replaced prior to operating fireplace. 6. Turn fireplace off and let cool before servicing, installing or repairing. Only a qualified service person should install, service or repair this fireplace. Have fireplace inspected annually by a qualified service person. 7. You must keep control compartments, burners and circulating air passages clean. More frequent cleaning may be needed due to excessive lint and dust from carpeting, bedding material, etc. Turn off the gas valve and pilot light before cleaning fireplace.

Do not use any solid fuels (wood, coal, paper, cardboard, etc.) in this fireplace. Use only the gas type in- dicated on fireplace name plate.

Carefully supervise young chil- dren when they are in the room with fireplace.

This fireplace reaches high tem- peratures. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Fireplace will remain hot for a time after shutdown. Allow sur- faces to cool before touching.

Do not operate fireplace with glass door removed, cracked or broken.

Page 4 of the FMI CGDV32PR user manual — Local Codes
Page 4 · click to enlarge
Page 4

SAFETY Continued 8. Have venting system inspected annually by a qualified service person. If needed, have venting system cleaned or repaired. See Cleaning and Maintenance, page 30. 9. Do not use this fireplace to cook food or burn paper or other objects. 10. This appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local

codes, with the National Electrical Code, ANSI/NFPA 70. 11. Do not use fireplace if any part has been under water. Immediately call a qualified service person to arrange for replacement of the unit. 12. Do not operate fireplace if log is broken. 13. Provide adequate clearances around air openings. Product Identification

FMI CGDV32PR — Product Identification diagram (page 4)
Fig. 3 · Product Identification

ON/OFF/REMOTE Switch (Optional Installation)

Blower Switch (Optional Installation)

Figure 1 - Direct-Vent Fireplace with Millivolt Ignition

Local Codes

Install and use fireplace with care. Follow all local codes. In the absence to local codes, use the current National Fuel Gas Code ANSI Z223.1/NFPA 54*. *Available from:

American National Standards Institute, Inc.

1430 Broadway New York, NY 10018 National Fire Protection Association, Inc.

  • Quincy, MA 02269 Product Features These are a few facts that can help you understand and enjoy your direct-vent fireplace:
  • The venting system may be routed to the outside of your home in several ways. It may vent through the roof (vertical) or it may vent to an outside/exterior wall (horizontal). The vent pipe installation is very important to allow for proper operation. You must follow the venting instructions very carefully for either vertical or horizontal applications.
  • This fireplace may be installed in any room of your house provided all local codes and these installation instructions are followed.
  • This fireplace does not require electricity to operate.
  • Only the blower requires electricity if installed. If you plan to install the blower at a later date, outlet must be wired at the bottom of the fireplace when framing.
  • A piezo ignitor and ceramic electrode create sparks to ignite the pilot light. It does not require any matches, batteries or any other sources of ignition to light the pilot.
  • Each time you turn on your fireplace, you may notice some amount of condensation on the inside of the fireplace glass. This is normal and will disappear after 10-20 minutes of operation.
  • Your direct-vent gas fireplace system (fireplace and venting) is a balanced and
Show 9 more labels / short text on this page
Upper Louver Panel · Glass Door Assembly · Piezo Ignitor · Log Set · Control Valve · Lower Louver Panel · Lava Rock · Grate Assembly · Batterymarch Park
Page 5 of the FMI CGDV32PR user manual — D
Page 5 · click to enlarge
Page 5

Product Features Continued

sealed gas operating unit. It requires ap- proximately 10-20 minutes of operating time before the flame pattern stabilizes.

  • Fireplaces with the suffix of -HA have been designed to operate at altitudes of 4000 feet and above. Pre-Installation Preparation
  • Location and space requirements Determine the safest and most efficient location for your FMI PRODUCTS, LLC direct-vent fireplace. Make sure that rafters and wall studs are not in the way of the venting system. Choose a location where the heat output is not affected by drafts, air conditioning ducts, windows or doors. Figure 2 shows some common locations. Be aware of all restrictions and precautions before deciding the exact location for your fireplace and termination cap. When deciding the location of your fireplace, follow these rules:
  • Do not connect this fireplace venting to a chimney flue serving a separate solid-fuel burning fireplace or appliance.
  • Due to high temperatures, do not locate this fireplace in high traffic areas, windy or drafty areas or near furniture or draperies.
  • Proper clearances must be maintained.
  • If your fireplace is to be installed directly on carpeting, vinyl tile or any combustible material other than wood, it must be installed on a metal or wood panel extending the full width and depth of the fireplace. See Figure 3.
  • Your fireplace is designed to be used in zero clearance installations. Wall or framing material can be placed directly against any exterior surface on the back, sides or top of your fireplace, except where standoff spacers are integrally attached. If standoff spacers are attached to your fireplace, these spacers can be placed directly against wall or framing material. See framing details on page 6.
  • If you plan on installing a television or entertainment center recessed above your fireplace, it is recommended that you maintain a minimum 18" above top of louver opening.
  • When locating termination cap, it is important to observe the minimum clearances shown in Figure 7, page 7.
  • If recessing into a wall, you can avoid extra framing by positioning your fireplace against an already existing framing member.
  • Do not recess termination cap into a wall or siding.
  • You may paint the termination cap with 450º F heat-resistant paint to coordinate with the exterior finish.
  • There must not be any obstruction such as bushes, garden sheds, fences, decks or utility buildings within 24" from the front
  • of the termination cap.
  • Do not locate termination cap where excessive snow or ice build up may occur. Be sure to clear vent termination area after snow falls to prevent accidental blockage of venting system. When using snow blowers, do not direct snow towards vent termination area.
  • For horizontal installations above 2,000 feet, it is recommended that a 12" extension pipe be added before starter elbow and a round horizontal termination be used (see High Altitude Installation , page 16).

Flush with a wall

Through exterior wall enclosed in a chase

Figure 2 - Common Fireplace Locations

22 1/2"

RW

16 5/8"

D

FW

34 3/8"

Figure 3 - Fireplace Bottom Dimensions

Clearances Minimum clearances to combustibles for the fireplace are as follows: *Back and sides 0" Perpendicular walls 6" Floor 0" Ceiling to louver opening 42" Front 36" Top 0" Vent (See venting instructions for specific venting clearances.) Combustible material with a maximum thickness of 5/8" may be flush with top front of fireplace. * For back and sides of fireplace, do not pack with insulation or other materials. 0" clearance to com- bustible materials are for framing purpose only.

Corner installation

Page 6 of the FMI CGDV32PR user manual — A
Page 6 · click to enlarge
Page 6

Pre-Installation Preparation

NOTICE: This fireplace is in- tended for use as supplemental heat. Use this fireplace along with your primary heating sys- tem. Do not install this fireplace as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using fireplace. This will help circulate the heat throughout the house. In the event of a power outage, you can use this fireplace as a heat source.

13 5/8" 39 3/8" 9 1/2"

D C

B

28 1/2"

A

E

97/8" 343/8"

F

345/8"

G

541/8"

H

Figure 5 - Framing Clearances for Corner

1 2 3 4 Wall B 5 C 6 D E 7 F G Top of Louver Opening Mantel fromWall Mantel from Mantel Ref. DepthT Ref.op of Louv Openinger 1 14"A16" 2 12"B14" 3 10"C12" 4 8"D10" 5 6"E8" 6 4"F6" 7 2"G4"

A

framing and finishing Figure 4 shows typical framing of this fireplace. Figure 5 shows framing for corner installation. All minimum clearances must be met. For available accessories for this fireplace, see Accessories on page 37. If you are using a separate combustible mantel piece, refer to Figure 6 for proper installation height. You can install noncombustible mantels at any height above the fireplace. Note: Noncombustible mantels may discolor!

323/8"

345/8" 17" Horiz. Vent 20" Vert. Vent

Figure 4 - Framing Clearances for Installation Against an Exterior Wall

Figure 6 - Clearances for Combustible

Show 4 more labels / short text on this page
Nailing Tabs · Naili · Installation · Mantels
Page 7 of the FMI CGDV32PR user manual — Location of Termination Cap
Page 7 · click to enlarge
Page 7
FMI CGDV32PR — Location of Termination Cap diagram (page 7)
Fig. 4 · Location of Termination Cap

TERMINATION CAP AIR SUPPLY INLET GAS METER RESTRICTED AREA (TERMINATION PROHIBITED) A = clearance above grade, veranda, porch, deck, or balcony [*12" (30.5 cm) minimum] B = clearance to window or door that may be opened [6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US if between 10,000 and 50,000, 12" (30 cm) in Canada if between 10,000 and 100,000; 12" (30 cm) in US if greater than 50,000, 36" (91 cm) in Canada if greater than 100,000] C = clearance to permanently closed window [minimum 12" (30.5 cm) recommended to prevent condensation on window] D = vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24" (61 cm) from the center-line of the terminal [18" (45.7 cm) minimum] E = clearance to unventilated soffit [12" (30.5 cm) minimum] F = clearance to outside corner (see below) G = clearance to inside corner (see below) H = *not to be installed above a meter/regulator assembly within 36" (91.4 cm) horizontally from the center line of the regulator

I = clearance to service regulator vent outlet [*72" (182.9 cm) minimum] J = clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other fireplace [6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US if between 10,000 and 50,000, 12" (30 cm) in Canada if between 10,000 and 100,000; 12" (30 cm) in US if greater than 50,000, 36" (91 cm) in Canada if greater than 100,000] K = clearance to a mechanical air supply inlet [*In Canada, 6 ft. (1.83m) minimum; In US 3 ft. (91 cm) above if within 10 ft. (3 m) horizontally] L = † clearance above paved side-walk or a paved driveway located on public property [*84" (213.3 cm) minimum] M = clearance under veranda, porch, deck [*12" (30.5 cm) minimum ‡] N = clearance above a roof shall extend a minimum of 24" (61 cm) above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18" (45.7 cm) † vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves both dwellings* ‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor* * as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A. Note: Local codes or regulations may require different clearances

Termination Clearances for Buildings with Combustible and Noncombustible Exteriors

Outside Corner Recessed Location

FMI CGDV32PR — Location of Termination Cap diagram (page 7)
Fig. 5 · Location of Termination Cap

C = Maximum depth of 48" (121.9 cm) for recessed location D = Minimum width for back wall of recessed location - Combustible - 38" (965 mm) Noncombustible - 24" (61 cm) E = Clearance from corner in recessed location- Combustible - 6" (15.2 cm) Noncombustible - 2" (5.1 cm)

Combustible & Noncombustible H = 24" (61 cm) J = 20" (50.8 cm)

Figure 7 - Minimum Clearances for Termination Cap

Inside Corner

Page 8 of the FMI CGDV32PR user manual — Venting Installation
Page 8 · click to enlarge
Page 8

Venting Installation

  • These models are tested and approved for use with FMI PRODUCTS, LLC (direct-vent) pipe components and terminations. The venting system must terminate on the outside of the structure and can not be attached to a chimney or flue system serving a separate solid fuel or gas burning appliance. A direct-vent appliance must have its own venting system. DO NOT common vent this appliance. These models are approved to be vented either horizontally through an outside wall or vertically through a roof or chase enclosure using the following guidelines:
  • When venting system terminates horizontally on an outside wall, you may install a standoff if the termination cap is to be installed directly on a combustible finish such as vinyl, wood, stucco, etc.
  • Never run the vent downward as this may cause excessive temperatures which could cause a fire.
  • Vent pipe air space clearances to combustibles are 1" on all sides except on the horizontal sections, which requires 2" clearance from the top of the pipe. Where the termination cap penetrates a combustible wall, 1" air space clearance is required.
  • Snorkel terminations are required when minimum clearance to grade cannot be met (see Figure 16 on page 12).
  • Have fireplace and selected vent components on hand to help determine the exact measurements when elbowing or offsetting. Always use wall firestops when penetrating walls and firestops when penetrating ceilings or attic spaces.
  • If using a venting configuration of only horizontal venting with no vertical run, a 1/4" rise for every 12" of run toward the termination is required.
  • For installation of fireplace at elevations of 4000 feet or greater, pay special attention to venting requirement recommendations.
  • Installation Precautions
  • Wear gloves and safety glasses for protection
  • Use extreme caution when using ladders or when on roof tops
  • Be aware of electrical wiring locations in walls and ceilings The following actions will void the warranty on your venting system:
  • Installation of any damaged venting component
  • Unauthorized modification of the venting system (Do not cut or alter vent components)
  • Installation of any component part not manufactured or approved by FMI PRODUCTS, LLC
  • Installation other than as instructed by these instructions
Page 9 of the FMI CGDV32PR user manual — Venting Installation
Page 9 · click to enlarge
Page 9

Venting Installation

  • INSTALLATION PLANNING There are two basic types of direct-vent installation:
  • Horizontal Termination
  • Vertical Termination

5. Carefully determine location where vent pipe assembly will penetrate the outside wall. The center of hole should line up with center line of horizontal vent pipe. Mark wall for a 11 1/2" x 11 1/2" square hole. Cut and frame the square hole in exterior wall where vent will be terminated. If wall being penetrated is constructed of noncombus- tible material, such as masonry block or concrete, a 8 1/2" hole with zero clearance is acceptable (see Figure 9).

Horizontal Termination Installation IMPORTANT: Horizontal square terminations require only inner portion of wall firestop. Horizontal installations using round termina- tion require exterior portion of wall firestop available only in vent kit HTK (see Figure 14, page 11). 1. Set fireplace in its desired location and determine the route your horizontal venting will take. Do not secure fireplace until all venting has been installed. Some installa- tions require sliding fireplace in and out of position to make final venting connections. Figures 14 through 18 on pages 11 through 13 show different configurations for venting with horizontal termination that will help you decide which application best suits your installation. Check to see if wall studs or roof rafters are in the path of your desired venting route. If they are, you may want to adjust the location of the fireplace. 2. Direct vent pipe sections and components are designed with special twist-lock con- nections. Twist-Lock Procedure: Female ends of pipes have locking lugs (indentations). These lugs will slide straight into match- ing slots on male ends of adjacent pipes. Push pipe sections together and twist one section clockwise approximately one- quarter turn until sections are fully locked (see Figure 8). Note: Horizontal runs of vent must be supported every three feet. Use wall straps for this purpose. 3. Use a 45° elbow to connect venting sys- tem to fireplace flue collar. The elbow is designed to be twist-locked onto flue collar as described in step 2. IMPORTANT: Do not attempt to alter configuration of elbow by cutting, twisting, bending, etc. 4. Assemble desired combination of pipe and elbows to fireplace flue collar. If there are long portions of venting run, preas- sembled pipe sections may be installed as subassemblies for convenience.

Figure 8 - Vent Pipe Connections

Vent Opening Combustible Wall

11 1/2" Inside Framing

11 1/2"

11 1/2"

Vent Opening Noncombustible Wall

8 1/2"

Figure 9 - Vent Opening Requirements

Show 5 more labels / short text on this page
Female Locking Lugs · Male Slots · (Framing · Detail) · Center of Hole
Page 10 of the FMI CGDV32PR user manual — Venting Installation
Page 10 · click to enlarge
Page 10

Venting Installation

6. Noncombustible Exterior Wall: Position horizontal vent cap in center of the 8 1/2" round hole and attach to exterior wall with four screws (see Figure 10). Note: The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete or other types of sidings. Before attaching vent cap to exterior wall, run a bead of non-hardening mastic (pliable sealant) around outside edges to make a seal between it and outside wall. Combustible Exterior Wall: For vinyl siding, stucco or wood exteriors, a siding standoff may be installed between vent cap and exterior wall. Siding standoff prevents excessive heat from damaging siding materials. Siding material must be cut to accommodate standoff. Bolt vent cap to standoff. Apply non-hardening mastic around outside edge of standoff. Position standoff/cap assembly in center of the 11 1/2" square hole and attach to exterior wall with wood screws provided (see Figure 11). Siding standoff must sit flush against exterior fascia material. 7. Connecting Vent Cap with Horizontal Vent Pipe: Slide wall firestop over vent pipe before connecting horizontal run to vent cap (see Figure 12). Carefully move fireplace, with vent as- sembly attached, toward wall and insert vent pipe into horizontal termination. The pipe overlap should be a minimum of 1 1/4" (see Figure 13, page 11).

Slide wall firestop against interior wall surface and attach with screws provided (see Figure 12). See Figure 13, page 11, for horizontal termination details. Place fireplace into position and shim with noncombustible material if needed. Nail or screw side flanges to framing to secure unit in place. IMPORTANT: Make sure fire- place is level before securing. If fireplace is not level it will not work properly.

FMI CGDV32PR — Venting Installation diagram (page 10)
Fig. 6 · Venting Installation

Apply Mastic to All Four Sides

Figure 11 - Installing Siding Standoff

FMI CGDV32PR — Venting Installation diagram (page 10)
Fig. 7 · Venting Installation
FMI CGDV32PR — Venting Installation diagram (page 10)
Fig. 8 · Venting Installation

Figure 10 - Installing Horizontal Vent Cap

Figure 12 - Connecting Vent Cap with

Show 9 more labels / short text on this page
Vent Cap · Screws · (Combustible Exterior) · Interior Wall Surface · Wood Screw · Screw · Horizontal Vent Pipe · (Noncombustible Exterior) · Horizontal Vent Pipe
Page 11 of the FMI CGDV32PR user manual — Venting Installation
Page 11 · click to enlarge
Page 11

Venting Installation

FMI CGDV32PR — Venting Installation diagram (page 11)
Fig. 9 · Venting Installation
  • GROUND FLOOR INSTALLATION Recommended Applications:
  • Installation using cabinet surrounds
  • Through the wall using round or square termination (up to 12") adjustable pipe)
  • NOT FOR CORNER INSTALLATION

Maintain 1" Minimum Air Space Around Outer Pipe When Penetrating a Wall

Vertical (V) Horizontal (H) 29 3/4" 17" max.

11 1/2" x 11 1/2" Framed Opening

Exterior Wall with Vinyl Siding

Exterior Portion of Wall Firestop (Round Termination Only)

Figure 13 - Typical Horizontal Termination Cap Mounting with Additional Siding Standoff Installed

Horizontal Termination Configurations Figures 14 through 18 show different configura- tions and alternatives for venting with horizontal termination. Each figure includes a chart with critical minimum and maximum dimensions which MUST be met. IMPORTANT: If using a venting configuration of only horizontal venting with no vertical run, a 1/4" rise for every 12" of run toward termination is required.

Slide Ring Over Elbow to Complete Connection

Horizontal Round Termination Round Termination

Figure 14 - Horizontal Termination Configuration for Square or Round

Show 4 more labels / short text on this page
45° Elbow · Wall Firestop · (Kit HTK Shown) · Termination
Page 12 of the FMI CGDV32PR user manual — Venting Installation
Page 12 · click to enlarge
Page 12

Venting Installation

  • CORNER INSTALLATION Recommended Applications:
  • Corner ground floor installation
  • Ground floor installation where pipe vents horizontally through wall (over 12" horizontal pipe)
  • Basement installation where one foot clearance from ground to termination is possible
FMI CGDV32PR — Venting Installation diagram (page 12)
Fig. 10 · Venting Installation

Not to Exceed (H) Limits

FMI CGDV32PR — Venting Installation diagram (page 12)
Fig. 11 · Venting Installation

As Required for (V), See Chart for Pipe Section Required

Vertical (V) Required Vertical (V) Vertical Pipe Horizontal (H) *43 3/4" min. None 30" max. 53 3/4" min. 1 ft. 48" max. 65 3/4" min. 2 ft. 60" max. 77 3/4" min. 3 ft. 84" max. 89 3/4" min. 4 ft. 20' max. * Ground Floor Corner Venting Figure 15 - Horizontal Termination Configuration for Corner Installation Using One

  • SNORKEL TERMINATION INSTALLATION Recommended Applications:
  • Installations requiring a vertical rise on building exterior
  • Any installation using snorkel termination to achieve one foot above ground

Snorkel terminations are available for instal- lations requiring a vertical rise on exterior of building. If installing snorkel termination below grade, you must provide proper drainage to prevent water from entering snorkel termina- tion (see Figure 16). Do not back fill around snorkel termination.

FMI CGDV32PR — Venting Installation diagram (page 12)
Fig. 12 · Venting Installation

Figure 16 - Snorkel Termination Configurations for Below Ground Installation

Show 4 more labels / short text on this page
90° Elbow · Wall Firestop · 90° Elbow · Snorkel Termination
Page 13 of the FMI CGDV32PR user manual — Venting Installation
Page 13 · click to enlarge
Page 13

Venting Installation

HORIZONTAL SYSTEM INSTALLATION USING TWO 90° ELBOWS The following configurations show the minimum vertical rise requirements for a horizontal system using two 90° elbows.

Venting with Two 90° Elbows

Horizontal (H1) + Vertical (V) Horizontal (H1) Horizontal (H2)

FMI CGDV32PR — Venting Installation diagram (page 13)
Fig. 13 · Venting Installation

5' min. 2' max. 6' max. 6' min. 4' max. 12' max. 7' min. 6' max. 18' max. 8' min. 8' max. 20' max. 20' max. 8' max. 20' max.

Figure 17 - Horizontal Termination Configuration for Venting Using Two 90° Elbows

FMI CGDV32PR — Venting Installation diagram (page 13)
Fig. 14 · Venting Installation

Venting with Two 90° Elbows

Horizontal (H1) + Vertical (V) Horizontal (H2)

5' min. 6' max. 6' min. 12' max. 7' min. 18' max. 8' min. 20' max. 20' max. 20' max.

Figure 18 - Horizontal Termination Configuration for Venting Using Two 90° Elbows

with Termination at 90° with Fireplace

Page 14 of the FMI CGDV32PR user manual — Venting Installation
Page 14 · click to enlarge
Page 14

Venting Installation

installation for vertical termination Note: Vertical restrictor must be installed in all vertical installations. 1. Determine route your vertical venting will take. If ceiling joists, roof rafters or other framing will obstruct venting system, consider an offset (see Figure 19) to avoid cutting load bearing members. Note: Pay special attention to these installation instructions for required clearances (air space) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with insulation. Also note maximum vertical rise of venting system and any maximum horizontal offset limitations. 2. Set fireplace in desired location. Drop a plumb line down from ceiling to position of fireplace exit flue. Mark center point where vent will penetrate ceiling. Drill a small locating hole at this point. Drop a plumb line from inside of roof to locating hole in ceiling. Mark center point where vent will penetrate roof. Drill a small locating hole at this point.

Flat Ceiling Installation 1. Cut a 11 1/2" square hole in ceiling using locat- ing hole as a center point. Opening should be framed to 11 1/2" x 11 1/2" inside dimensions, as shown in Figure 9 on page 9 using framing lumber the same size as ceiling joists. If area above the ceiling is an insulated ceiling or an attic, nail firestop from top side. This prevents loose insulation from falling into required clearance space. If area above ceiling is a living space, install firestop below framed hole. Firestop should be installed with no less than 3 nails per side (see Figure 20). 2. Assemble desired lengths of pipe and elbows necessary to reach from fireplace flue up through firestop. Be sure all pipe and elbow connections are fully twist- locked (see Figure 8, page 9). 3. Cut a hole in roof using locating hole as a center point. (Cover any exposed open vent pipes before cutting hole in roof.) The 11 1/2" x 11 1/2" hole must be measured on the horizontal; actual length may be larger depending on pitch of roof. There must be a 1" clearance from vent pipe to combustible materials. Frame opening as shown in Figure 9, page 9. 4. Connect a section of pipe and extend up through hole. Note: If an offset is needed to avoid obstructions, you must support vent pipe every 3 feet. Use wall straps for this pur- pose (see Figure 19). Whenever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less restriction to the flow of flue gases and intake air. 5. Place flashing over pipe section(s) ex- tending through roof. Secure base of flashing to roof and framing with roofing nails. Be sure roofing material overlaps top edge of flashing as shown in Figure 19. There must be a 1" clearance from vent pipe to combustible materials.

If area above is an

If area above is a living space, install firestop below framed

attic or insulated area, install firestop above framed hole.

hole.

Figure 19 - Offset with Wall Strap and 45°

Figure 20 - Installing Firestop

Show 5 more labels / short text on this page
Roof Flashing · Wall Strap · 45° Elbow · Ceiling Firestop · Elbows
Page 15 of the FMI CGDV32PR user manual — Venting Installation
Page 15 · click to enlarge
Page 15

Venting Installation

FMI CGDV32PR — Venting Installation diagram (page 15)
Fig. 15 · Venting Installation

Venting with One 90° Elbow Vertical (V) Horizontal (H) 5' min. 2' max. 6' min. 4' max. 7' min. 6' max. 8' min. 8' max. 20' max. 8' max.

6. Continue to add pipe sections until height of vent cap meets the minimum building code requirements described in Figure 7 on page 7. Note: You must increase vent height for steep roof pitches. Nearby trees, adjoining rooflines, steep pitched roofs and other similar factors may cause poor draft or down-drafting in high winds. Increasing vent height may solve this problem. 7. Twist-lock vent cap onto last section of vent pipe. Note: If vent pipe passes through any occu- pied areas above first floor, including storage spaces and closets, you must enclose pipe. You may frame and sheetrock enclosure with standard construction material. Make sure and meet minimum allowable clearances to combustibles. Do not fill any required air spaces with insulation.

Figure 22 - Vertical Venting Configuration

Using One 90° Elbow (Vertical Round

High Wind Termination Shown)

FMI CGDV32PR — Venting Installation diagram (page 15)
Fig. 16 · Venting Installation

Vertical Termination Configurations Figures 21 through 24 show four different configurations for vertical termination.

Venting with Two 90° Elbows Horizontal (H1) + Vertical (V) Horizontal (H2) 5' min. 2' max. 6' min. 4' max. 7' min. 6' max. 8' min. 8' max. 20' max. 8' max.

Venting with Two 90° Elbows Vertical (V1) Horizontal (H) 5' min. 6' max. 6' min. 12' max. 7' min. 18' max. 8' min. 20' max. Note: Vertical (V1) + Vertical (V2) = 40' max.

Figure 21 - Vertical Venting Configuration Using Two 90° Elbows

with Two Horizontal Runs (Vertical Round High Wind Termination Shown)

Figure 23 - Vertical Venting Configuration

Using Two 90° Elbows (Vertical Round

High Wind Termination Shown)

Page 16 of the FMI CGDV32PR user manual — Venting Installation
Page 16 · click to enlarge
Page 16

Venting Installation

FMI CGDV32PR — Venting Installation diagram (page 16)
Fig. 17 · Venting Installation

starter elbow (see Figure 25) and a round horizontal termination be used.

FMI CGDV32PR — Venting Installation diagram (page 16)
Fig. 18 · Venting Installation

Figure 25 - Recommended 12" Extension

for High Altitude Installation

Parts list for venting kits and components FMI PRODUCTS, LLC (5"/8") Pipe & Vent Kits Number Description P58-6 6" Section Double Wall Pipe, Galvanized P58-12 12" Section Double Wall Pipe,

Galvanized P58-24 24" Section Double Wall Pipe,

Galvanized P58-36 36" Section Double Wall Pipe,

Galvanized P58-48 48" Section Double Wall Pipe,

Galvanized PA58-712 Adjustable 7"-12" Section Double

Figure 24 - Vertical Venting Configuration

Wall Pipe, Galvanized E58-45 45° Elbow, Galvanized E58-90 90° Elbow, Galvanized VKG-58 Ground Floor Vent Kit, Galvanized

With No Horizontal Run (Vertical Round

High Wind Termination Shown)

High Altitude Installation Your FMI PRODUCTS, LLC direct-vent fireplace has been tested and approved for elevations from 0-2000 feet (USA). Fireplaces for High Altitude (models ending in -HA) are for installation above 4000 feet only. These fireplaces are equipped with parts specific for higher altitudes. When installing a non-high altitude fireplace at an elevation above 2000 feet (in the USA), you may need to decrease the input rating by changing the existing burner orifice to a smaller size. Reduce input 4% for each 1000 feet above sea level. Check with your local gas company for proper orifice size identification. IMPORTANT: For horizontal installations above 2,000 feet, it is recommended that a 12" extension pipe be added before

(Includes: 45° Elbow, 7"-12" Adjust- able Pipe, Wall Firestop, Horizontal Square Termination, 16 Screws) VKB-58 Basement Vent Kit, Galvanized

(Includes: 45° Elbow, 7"-12" Adjustable Pipe, Wall Firestop, Horizontal Square Termination, 4' Pipe, 90° Elbow, 20 Screws) VKS-58 Snorkel Vent Kit, Galvanized (Includes:

45° Elbow, 7"-12" Adjustable Pipe, Wall Firestop, 36" Snorkel Termination, 4' Pipe, 1' Pipe, 90° Elbow, 26 Screws) VKR-58 Roof Vent Kit, Galvanized (Includes:

45° Elbow, 7"-12" Adjustable Pipe, Flue Restrictor, Vertical High Wind Termination, 2' Pipe, 4' Pipe, Wall Firestop, Storm Collar, Roof Flash- ing [0/12 - 6/12], 26 Screws)

Page 17 of the FMI CGDV32PR user manual — Installing optional blower accessory
Page 17 · click to enlarge
Page 17

Venting Installation

Number Description VKC-58 Corner Vent Kit, Galvanized (Includes 45° Elbow, 7"-12" Adjustable Pipe, Wall Firestop, Horizontal Termination, 6" Pipe, 90° Elbow, 18 Screws) HHTK-58 High Wind Round Horizontal Termi-

Number Description ST-58-14 14" Snorkel Termination, Galva-

nized ST-58-36 36" Snorkel Termination, Galvanized SC-58 Storm Collar, Galvanized WF-58 Wall Firestop, Galvanized RF-58-6 Roof Flashing - 0 to 6/12 Pitch, Galvanized RF-58-12 Roof Flashing - 6/12 to 12/12

nation Kit (Includes Round Termina- tion, Wall Firestop, 45° Elbow) HHT-58 High Wind Round Termination Kit, Galvanized HTK-58 Horizontal Round Termination Kit (Includes Round Termination, Wall Firestop, 45° Elbow) HT-58 Horizontal Round Termination, Galvanized HTS-58 Horizontal Square Termination, Galvanized HTKS-58 Horizontal Square Termination

Pitch, Galvanized VR-58 Vertical Restrictor, Galvanized S-58 Vinyl Siding Standoff, Galvanized WS-58 Wall Strap CS-58 Cathedral Ceiling Support FP-58 Firestop Plate SF-58 Stucco Flashing - For use with HTS-58 RF-58 Flat Roof Flashing PF58-927 Flex Pipe Section 9" to 24" PF58-1236 Flex Pipe Section 12" to 36" PF58-1854 Flex Pipe Section 18" to 54" VKF58-927 Flex Kit (Includes Flex Pipe Wall

Kit (Includes: Square Termina- tion, Wall Firestop, 45° Elbow) HTS-58 Horizontal Square Termination, Galvanized VT-58 Vertical Round Termination, Galvanized

Section 9" to 27", Firestop and Horizontal Square Termination)

Fireplace Installation

CHECK GAS TYPE Use proper gas type for fireplace unit you are installing. If your gas supply is not correct, do not install fireplace. See retailer where you purchased fireplace for proper fireplace ac- cording to your gas type or to purchase gas conversion kit (see Accessories, page 37).

Model BK Installation Follow all instructions provided in blower accessory kit. 1. Attach power cord to blower motor by firmly pushing two female terminals at end of power cord onto two spade terminals on blower motor (see Figure 26). 2. Attach green ground wire from power cord to blower housing using screw provided (see Figure 26). Tighten screws securely. 3. Place blower against lower rear wall of firebox outer wrapper with exhaust port directed upward. Blower will fit inside back opening and be held in position against back wall by magnets (see Figure 26).

Installing optional blower accessory

Figure 26 - Blower Model BK

Show 8 more labels / short text on this page
Side View · Blower Location · Lower Firebox Cavity · Magnetic Strips · Spade Terminals · Green Ground Wire · Screw · Exhaust Port
Page 18 of the FMI CGDV32PR user manual — Fireplace Installation
Page 18 · click to enlarge
Page 18

Fireplace Installation

4. Be certain that all wire terminals are securely attached to terminals on blower motor and that screw retaining green ground wire is tight. 5. Mount speed control box to switch bracket by placing plastic control shaft forward through opening in switch bracket (see Figure 27). 6. While supporting speed control, secure control shaft with lock nut by pushing and turning lock nut with pliers clockwise until it is tight against front panel. Place provided control knob on shaft. 7. Turn on power to duplex outlet if previ- ously turned off per warning in column 2, page 17. 8. Plug in blower power cord. a. If your firebox is installed as a free-

9. Check to make sure that power cord is completely clear of blower wheel and that there are no other foreign objects in blower wheel. Turn blower on and check for operation. Turn blower off by turning knob fully counterclockwise before continuing. 10. Peel off backing paper and stick supplied wiring diagram decal on firebox bottom approximately 12" in front of blower (see Figure 28).
FMI CGDV32PR — Fireplace Installation diagram (page 18)
Fig. 19 · Fireplace Installation

standing unit with an accessory man- tel, determine whether power cord will exit left side or right side of firebox. Route power cord through exit hole and plug power cord into a wall recep- tacle near firebox. b. If your firebox installation is recessed

Figure 28 - Location of Wiring Diagram Decal (Model May Vary From Illustration)

Model BKT Installation Note: When installing BKT thermostati- cally controlled blower, you must first secure thermal switch bracket to blower if it has not already been factory installed. 1. Place green ground wire with ring ter- minal between bottom hole on thermal switch bracket and top ear hole on blower assembly. Insert Phillips screw into all three pieces and tighten securely (see Figure 29, page 19). 2. Connect wire harness and power cord ter- minals. Connect blue jumper wire to blower motor terminal and right side terminal of thermal switch. Connect black wire to left side of thermal switch and white wire to other remaining blower motor terminal. Note: The power cord outer insulation sleeve may have to be stripped slightly to allow enough wire length to reach and make all connections. DO NOT trim excessive length away. Enable just enough to make all con- nections securely.

and/or prewired, plug power cord into duplex outlet provided. Refer to your firebox owner’s manual for instructions on wiring duplex outlet.

Duplex Outlet (Located underneath firebox floor against lower right outside wall)

FMI CGDV32PR — Fireplace Installation diagram (page 18)
Fig. 20 · Fireplace Installation

Control Shaft Locknut Control Knob

Figure 27 - Attaching Speed Control to

Switch Bracket · Speed Control · Firebox

Page 19 of the FMI CGDV32PR user manual — Fireplace Installation
Page 19 · click to enlarge
Page 19

Fireplace Installation

3. Place blower against lower rear wall of firebox outer wrapper with exhaust port di- rected upward and thermodisc positioned up near fireplace bottom. Thermodisc must be oriented near fireplace bottom as shown in Figure 29, in order to sense temperature and properly operate. Blower will be held in position against back wall by magnets incorporated onto blower housing (see Figure 29). 4. Be certain that all wire terminals are securely attached to terminals on blower motor and thermal switch and that screw for thermodisc bracket and green ground wire is tight. 5. Mount speed control box against mount- ing plate provided in lower fireplace cavity by placing plastic control shaft forward through round hole (see Figure 27, page 18). 6. While supporting speed control, secure control shaft with lock nut by pushing and turning lock nut with pliers clockwise until it is tight against mounting plate. Place control knob provided on shaft (see Figure 27, page 18).

7. Check to make sure that power cord is completely clear of blower wheel and that there are no other foreign objects in blower wheel. Also double check all wire leads and make sure wire routing is not pinched or in a precarious position. Cor- rect accordingly. 8. Turn on power to duplex outlet if previ- ously turned off per warning in column 2, page 17. 9. Plug in blower power cord to duplex outlet. 10. Blower will only run when speed control knob is in the ON position and thermal switch senses temperature after fireplace begins to heat up. Blower speed can be adjusted by rotating control knob. To turn off, turn knob fully counterclockwise until it clicks off. If blower is ON and has been running with fireplace operating, blower will continue to run for a short time after fireplace has been turned off. As thermal switch cools down, blower shuts down automatically. 11. Peel off the backing paper and stick the supplied wiring diagram decal on the firebox bottom approximately 12" in front of the blower (see Figure 28, page 18).

FMI CGDV32PR — Fireplace Installation diagram (page 19)
Fig. 21 · Fireplace Installation

Air Flow Direction Route BKT Blower Through This Area

Figure 30 - Blower Wiring Diagram for

Figure 29 - Blower Model BKT

Power Cord · Magnets Blower Location · Thermostat-Controlled Models

Page 20 of the FMI CGDV32PR user manual — Installing Gas Piping to Fireplace Location
Page 20 · click to enlarge
Page 20

Fireplace Installation

Installing Gas Piping to Fireplace Location

fireplace regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 31. Pointing the vent down protects it from freezing rain or sleet.

Installation must include an equipment shutoff valve, union and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 32, page 21). IMPORTANT: Install main gas valve (equip- ment shutoff valve) in an accessible location. The main gas valve is for turning on or shutting off the gas to the appliance. Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces. Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves.

  • Installation Items Needed Before installing fireplace, make sure you have the items listed below.
  • external regulator (supplied by installer)
  • piping (check local codes)
  • sealant (resistant to propane/LP gas)
  • equipment shutoff valve *
  • test gauge connection *
  • sediment trap
  • tee joint
  • pipe wrench
  • approved flexible gas line with gas connector (if allowed by local codes) * An equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the equipment shutoff valve from your retailer. For propane/LP connection only, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11" and 14" of water. If you do not reduce incoming gas pressure, Figure 31 - External Regulator with Vent

Propane/LP Supply Tank External Regulator with Vent Pointing Down

Pointing Down (Propane/LP Only)

Page 21 of the FMI CGDV32PR user manual — CONNECTING FIREPLACE TO GAS SUPPLY
Page 21 · click to enlarge
Page 21

Fireplace Installation

We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 32. Locate sediment trap/drip leg where it is within reach for cleaning. Install in piping sys- tem between fuel supply and fireplace. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into fireplace gas controls. If sedi- ment trap/drip leg is not installed or is installed wrong, fireplace may not run properly.

To Gas Supply (Natural)

FMI CGDV32PR — Fireplace Installation diagram (page 21)
Fig. 22 · Fireplace Installation

Equipment Shutoff Valve with 1/8" NPT Tap*

Figure 33 - Connecting Flexible Gas Line

Natural - From Gas Meter (5.5" W.C. to 10.5" W.C. Pressure) Propane/LP From External Regulator (11" W.C. to 14" W.C. Pressure)

FMI CGDV32PR — Fireplace Installation diagram (page 21)
Fig. 23 · Fireplace Installation

* The equipment shutoff valve may be sup- plied with the appliance or you can purchase it from your retailer.

PRessure Testing Gas Supply Piping System Test Pressures In Excess Of 1/2 PSIG (3.5 kPa) 1. Disconnect fireplace and its individual equip- ment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage fireplace gas regulator. 2. Cap off open end of gas pipe where equip- ment shutoff valve was connected. 3. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace or using compressed air. 4. Check all joints of gas supply piping sys- tem. Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once. 5. Reconnect fireplace and equipment shutoff valve to gas supply. Check recon- nected fittings for leaks.

CONNECTING FIREPLACE TO GAS SUPPLY

  • Installation Items Needed
  • 5/16" hex socket wrench or nut-driver
  • sealant (resistant to propane/LP gas, not provided) 1. Open lower louver door panel by gently pulling forward. 2. Route flexible gas line (provided by installer) from equipment shutoff valve to fireplace. Route flexible gas supply line through one of the access holes on side of fireplace. 3. Attach flexible gas line from gas supply to control valve (see Figure 33). 4. Check all gas connections for leaks. See Checking Gas Connections .
Page 22 of the FMI CGDV32PR user manual — Fireplace Installation
Page 22 · click to enlarge
Page 22

Fireplace Installation

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa) 1. Close equipment shutoff valve (see Fig- ure 34). 2. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace or using compressed air. 3. Check all joints from propane/LP supply tank for propane/LP or gas meter for natural gas to equipment shutoff valve (see Figure 35 or Figure 36). Apply non- corrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Fireplace Gas Connections 1. Open equipment shutoff valve (see Fig- ure 34). 2. Open main gas valve located on or near gas meter for natural gas or open supply tank valve for propane/LP gas. 3. Make sure control knob of fireplace is in the OFF position. 4. Check all joints from equipment shutoff valve to gas valve (see Figure 35 or Figure 36). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once. 5. Light fireplace (see Operation, page 26). Check all other internal joints for leaks. 6. Turn off fireplace (see To Turn Off Gas to Appliance, page 27).

Installing optional wall Mount Switch - gwmS2 1. Connect one terminal of 25 ft. wire for wall switch to TPTH terminal on valve. Connect remaining wire terminal to TH terminal on valve. Make sure that wire ter- minals are in positions on unit as pictured in Figure 37. If wires are not connected as shown the switch will not work. 2. Route 25 ft. wire through openings pro- vided on sides of burner system to a con- venient location to mount your switch. 3. Connect one bare wire end to each of the terminals of the GWMS2 wall switch. 4. Install wall switch and cover in wall.

Figure 34 - Equipment Shutoff Valve

To Wall Switch Accessory

Figure 35 - Checking Gas Joints for

Figure 37 - Connecting Wall Switch to

Figure 36 - Checking Gas Joints for

Show 12 more labels / short text on this page
Equipment Shutoff Valve · Open · Closed · Equipment Shutoff Valve · Propane/LP Supply Tank · Gas Valve · Propane/LP Gas Fireplace · Equipment Shutoff Valve · Gas Meter · Control Valve · Gas Valve · Natural Gas Fireplace
Page 23 of the FMI CGDV32PR user manual — Removing/Replacing Glass Door
Page 23 · click to enlarge
Page 23

Fireplace Installation

FMI CGDV32PR — Fireplace Installation diagram (page 23)
Fig. 24 · Fireplace Installation

Installing Optional Wireless hand-held REMOTE CONTROL HRC100 and HRC200 Series

Figure 40 - Installing Battery in Hand-

Installing Remote Receiver 1. Open bottom louver and locate switch bracket on the left. 2. Unscrew switch bracket. Lean bracket forward so you are able to access the back of remote receiver. 3. Locate battery clip mounted on back of receiver. Slide a 9-volt alkaline battery (not included) through the clip (see Figure 38). 4. Attach terminal wires to battery. 5. Connect wires from receiver to TH and TPTH to control valve (see Figure 39). 6. Replace switch bracket.

Held Remote Control Unit

Removing/Replacing Glass Door

Figure 38 - Attaching Alkaline Battery to

Removing Louver Panels Remove top and bottom louver panels by simultaneously pulling both top end spring latches towards center of appliance until they are disengaged from locating holes (see Figure 41). Repeat for bottom spring latches and pull louvers outward. To install or replace items removed, simply reverse procedures above.

To Optional Remote Accessory

Figure 39 - Control Valve Terminals

Installing 9-Volt Alkaline Battery in Hand- Held Remote Control Unit 1. Remove battery cover on back of remote control unit (see Figure 40). 2. Attach terminal wires to battery. Place battery into battery housing. 3. Replace battery cover onto remote control unit.

Figure 41 - Removing Louver Panel

Show 10 more labels / short text on this page
Battery Cover · Remote Control Unit · 9-Volt Battery · Receiver · 9-Volt Alkaline Battery · Terminal Wires · Battery Clip · Receiver · Spring Latch · Louver Panel
Page 24 of the FMI CGDV32PR user manual — Installing Optional Brick liner Model BL32D
Page 24 · click to enlarge
Page 24

Fireplace Installation

Removing Glass Door If replacement of glass is necessary, the entire assembly, glass and frame, must be replaced. If glass is broken, wear gloves and tape remaining fragments onto frame. 1. Remove screen/rod assembly from fire- box, push rod either left or right and then down and forward. Set assembly aside. 2. Lift up on latches to unlock. There are two on top of firebox and two below firebox that hold glass door in place (see Figure 42). 3. While holding glass door to prevent it from falling and causing injury, remove the five screws from hinge located on left side of door frame assembly (see Figure 42). 4. Remount new frame at hinge with five new screws before closing door. This will ensure seating of gasket. 5. Close glass door frame. Lock latches by placing bar under tab on door and pushing down and back on latch (see Figure 42). 6. Replace screen/rod assembly by revers- ing step 1. 7. Replace louvers by reversing procedure under Removing Louver Panels, page 23.

Installing Optional Brick liner Model BL32D

FMI CGDV32PR — Installing Optional Brick liner Model BL32D diagram (page 24)
Fig. 25 · Installing Optional Brick liner Model BL32D

This brick liner kit is optional. You may pur- chase brick liner from your local retailer or see page 37.

FMI CGDV32PR — Installing Optional Brick liner Model BL32D diagram (page 24)
Fig. 26 · Installing Optional Brick liner Model BL32D

1. Remove top and bottom louvers to allow access to door latches. 2. Unlock door latches and open glass door. See steps 1 and 2 of Removing/Replacing Glass Door, page 23. 3. If installing brick liner in new fireplace, go to step 4. If installing brick liner in an existing fireplace, carefully remove logs, lava rock and ember material. 4. Remove three screws from deflector shield on the inside top of firebox. Set shield and screws aside. 5. Install rear brick panel first. Rest bottom edge of panel on back edge of grate (see Figure 43). 6. Install left side brick panel by sliding it between grate and side of firebox (see Figure 43).

FMI CGDV32PR — Installing Optional Brick liner Model BL32D diagram (page 24)
Fig. 27 · Installing Optional Brick liner Model BL32D
FMI CGDV32PR — Installing Optional Brick liner Model BL32D diagram (page 24)
Fig. 28 · Installing Optional Brick liner Model BL32D

Figure 42 - Removing/Replacing Glass

Cleaning Glass Door See Cleaning and Maintenance on page 31.

Figure 43 - Installing Rear Brick Panel

Latch · Hinge · Door

Page 25 of the FMI CGDV32PR user manual — Fireplace Installation
Page 25 · click to enlarge
Page 25

Fireplace Installation

7. Install right brick panel using the same method described in step 5 for left brick panel. 8. Replace deflector shield using screws removed in step 4. 9. Follow instructions below to install logs, lava rock and ember material. 10. Close glass door, lock latches on top and bottom of door and replace screen (see steps 5 and 6 of Removing Glass Door , page 24). 11. Close top and bottom louvers.
5. Place log #5 (base log) onto front left part of grate making sure notches fit over prongs of grate). See Figure 49, page 26.
FMI CGDV32PR — Fireplace Installation diagram (page 25)
Fig. 29 · Fireplace Installation
FMI CGDV32PR — Fireplace Installation diagram (page 25)
Fig. 30 · Fireplace Installation

Figure 45 - Installing Log No. 1

FMI CGDV32PR — Fireplace Installation diagram (page 25)
Fig. 31 · Fireplace Installation

Left Side Brick Panel

Figure 44 - Installing Side Brick Panels

Installing logs, lava rock and glowing embers Each log is marked with a number. These numbers will help you identify the log when installing. It is very important to install these logs exactly as instructed. Do not modify logs. Only use logs supplied with fireplace. Open louvers, remove screen, unlock door latches and open glass door. See steps 1 and 2 of Removing Glass Door, page 24. Install logs according to instructions for fireplace model numbers. 1. Place log #1 (rear log) on top of grate. Make sure notches in bottom of log fit over grate (see Figure 45). 2. Rest log #2 (large front log) on pins on front part of grate (see Figure 46). 3. Place log #3 (crossover log) onto rear and front logs. Make sure it is seated properly on smooth surface on front log and on pin on back log as shown in Figure 47. 4. Place log #4 (right log) on pin on right side of front log as shown in Figure 48, page 26.

Figure 46 - Installing Log No. 2

FMI CGDV32PR — Fireplace Installation diagram (page 25)
Fig. 32 · Fireplace Installation

Figure 47 - Installing Log No. 3

Page 26 of the FMI CGDV32PR user manual — Burner Operation
Page 26 · click to enlarge
Page 26

Fireplace Installation

Continued 6. Place log #6 (left log) onto two pins on left side of back and front log. See Figure 49. 7. Place lava rock along sides and front of firebox bottom in areas that are visible only. It is not necessary to use all of the lava rock provided. 8. Pull ember material apart into pieces no larger than a dime. Place these pieces loosely and sparingly directly onto ex- posed section of front burner and along space between burner and grate prongs (see Figure 50). This will create the glowing ember appearance as the flame touches the ember material. Do not block air slots by using too much ember material

in one area. Do not block pilot ports with embers. It is not necessary to use all of the ember material provided. 9. Close glass door, lock door latches, replace screen and close louvers (see steps 5 and 7 of Removing Glass Door, page 24).

FMI CGDV32PR — Fireplace Installation diagram (page 26)
Fig. 33 · Fireplace Installation
FMI CGDV32PR — Fireplace Installation diagram (page 26)
Fig. 34 · Fireplace Installation

Figure 49 - Installing Logs No. 5 and No. 6

Figure 50 - Placing Ember Material on

Figure 48 - Installing Log No. 4

Burner Operation

FMI CGDV32PR — Burner Operation diagram (page 26)
Fig. 35 · Burner Operation
  • WHAT TO DO IF YOU SMELL GAS
  • Do not try to light any appliance.
  • Do not touch any electric switch.
  • Do not use any phone in your building.
  • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
  • If you cannot reach your gas supplier, call the fire department. C. Use only your hand to push in or turn

A. This appliance is equipped with an

the gas control knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion. D. Do not use this appliance if any part

ignition device which automatically lights the pilot. Do not try to light the pilot by hand. B. BEFORE LIGHTING smell all around

the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

Page 27 of the FMI CGDV32PR user manual — P
Page 27 · click to enlarge
Page 27

Operation

  • LIGHTING INSTRUCTIONS 1. STOP! Read the safety information on page 26. 2. Open lower louver panel. 3. Turn off all electric power to fireplace. 4. Push in gas control knob slightly and turn clockwise to OFF. 5. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety information on page 26. If you don't smell gas, go to the next step. 6. The pilot is located by the main burner and should not require accessing for lighting. 7. Turn gas control knob counterclockwise to PILOT (see Figure 51). 8. Push in gas control knob all the way and hold. Immediately light the pilot by repeatedly pressing the piezo spark ignitor until a flame appears. Continue to hold for about 1 minute after pilot is lit. Release gas control knob and it will pop back. Pilot should remain lit. If it goes out, repeat steps 4 through 8.
  • If gas control knob does not pop up when released, stop and immediately call your service technician or gas supplier.
  • If pilot will not stay lit after several tries, turn gas control knob to OFF and call your service technician or gas supplier. 9. Turn on all electric power to fireplace. 10. Turn gas control knob counterclockwise to ON. 11. This valve is equipped with a HI/LO feature. Set fireplace input as desired. 12. To leave pilot lit and shut off burners only, turn control knob clockwise to the PILOT position or set selector switch in the OFF position. 13. Close lower louver panel.

TO TURN OFF GAS

TO APPLIANCE 1. Open lower louver panel. 2. Set selector switch in the OFF position to prevent draining battery. 3. Turn off all electrical power to appliance if service is to be performed. 4. Push in gas control knob slightly and turn clockwise to OFF. 5. Close lower louver panel.

MANUAL LIGHTING

PROCEDURE 1. Remove glass door (see Removing/Re- placing Glass Door, page 24). 2. Follow steps 1 through 8 under Lighting Instructions. 3. Press gas control knob and light pilot with match. 4. Keep gas control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release gas control knob. Fol- low steps 10 through 13 under Lighting Instructions. 5. Replace glass door (see Removing/Re- placing Glass Door, page 23).

optional Hand-Held

REMOTE OPERATION Note: All remote control accessories must be purchased separately (see Accessories, page 37). Follow instructions included with the remote control.

After lighting, let pilot flame burn for about one minute. Turn control knob to ON posi- tion. Adjust flame adjustment knob anywhere between HI and LO. Slide selector switch to the REMOTE position (see Figure 52, page 28). Note: The burner may light if hand-held remote was on when selector switch was last turned off. You can now turn the burner on and off with the hand-held remote control unit. IMPORTANT: Do not leave selector switch in the REMOTE or ON position when the pilot is not lit. This will drain the battery.

P

O

T

H

O

F

F

O

N

O

Figure 51 - Control Valve

Gas Control Knob · Variable Control Knob · Piezo Ignitor

Page 28 of the FMI CGDV32PR user manual — MANU AUTO ºC/ºF
Page 28 · click to enlarge
Page 28

Operation

Blower Control Knob (Optional Accessory) Variable Control Knob

Manual Mode 1. Press the POWER and LOCK buttons together to turn on the hand-held remote control. 2. Press the MANU button to turn on the fireplace. 3. Press the POWER and LOCK buttons together to turn off the fireplace.

ON OFF

O

N

REMOTE

T

O

O

O

H

OFF

P

F

F

ON

Gas Control Knob in ON Position

Auto (Thermostatic) Mode 1. Press the POWER and LOCK buttons together to turn on the hand-held remote control. 2. Press AUTO button to select this mode. 3. Set the desired room temperature by pressing the TEMP + or - buttons. 4. Press the POWER and LOCK buttons together to turn off the fireplace. Note: Do not leave the hand-held remote in the AUTO mode close to the fireplace. The radiant heat from the fireplace will turn off the fireplace. Ideally, place the hand-held remote in the center of the room facing towards the fireplace. Note: Do not hold the hand-held remote for a long time. Body temperature will affect its operation in the AUTO mode.

Selector Switch in Remote Position

Figure 52 - Setting Selector Switch, Gas Control Knob and Variable Control Knob

On/Off Series (Model HRC100 and HRC101) Hold control button on hand-held remote until burner turns on. Hold control button again until burner turns off (see Figure 53). To Lock press both buttons on hand-held remote control until light stops flashing. Hand- held remote control is now locked. If the fire is on it will be turned off automatically. In the locked state, the light will not light up when any button is pressed. To Unlock press both buttons together on hand-held remote control until the light stops flashing. The hand-held remote is now unlocked.

Safety Features When away from home for an extended period of time or as a child safety feature to prevent accidental ignition of the fireplace, the receiver ON/OFF/REMOTE switch should be in the OFF position.

Digital Display Shows Temperature and Settings

Locks System to Prevent Accidental Ignition

AUTO Turns Hand-Held Remote On or Off and Allows You to Choose the Manual Setting

ROOM TEMP

SET TEMP

Figure 53 - On/Off Hand-Held Remote

LOCK

TEMP POWER

Turns Burners On or Off

Thermostat Series (Model HRC200 and HRC201) The hand-held remote can be operated using either the manual mode (MANU) or thermo- static mode (AUTO) (see Figure 54). To select Fahrenheit/Centigrade mode display, carefully press the ˚C/˚F mode button with the end of a paper clip or similar blunt object.

MANU AUTO ºC/ºF

Increases or Decreases Room Temperature in AUTO Mode

Figure 54 - Thermostat Hand-Held Remote Control Unit (HRC200/HRC201)

Show 6 more labels / short text on this page
for Remote Operation · Indicator Light · Control Button · Control Unit (HRC100/HRC101) · Selects AUTO Mode · °C/°F Mode Button
Page 29 of the FMI CGDV32PR user manual — operating optional GWMT1 Wall Mounted
Page 29 · click to enlarge
Page 29

Operation

Auto Shutoff Feature 1. If the average room temperature reaches a range of 82° F (28° C) to 92° F (33° C), the hand-held remote control will perform a safety override and shut the fireplace off. This feature is not available in the MANU mode. 2. The receiver continuously receives sig- nals from the hand-held remote to control the room temperature. If the hand-held remote is misplaced, obstructed or for any reason cannot transmit to the receiver, the receiver will shut off the fireplace. This will occur in 8 or more minutes depending upon location of remote transmitter and strength of batteries.

This thermostat has been electronically cali- brated at the factory and requires no adjust- ment or leveling. Upon installation, thermostat must be allowed to stabilize at room temperature for a mini- mum of 30 minutes for proper operation. To turn fireplace off, adjust thermostat to the lowest setting and turn gas control knob back to PILOT. The pilot will remain lit. IMPORTANT: To turn pilot off, turn gas control knob on heater to the OFF position.

Operating optional

blower accessory Locate blower controls by opening lower louver panel on fireplace. Blower controls are located on the right side of switch bracket to the left just inside louver panel. The BK manual blower and BKT thermostati- cally-controlled blower have an ON setting and an OFF setting. Blower will only run when the switch is in the ON position. In the OFF position, blower will not operate. Note for BKT Only: If you are using BKT blower with optional thermostat (wall mounted or remote control) for the fireplace, your fire- place and blower will not turn on and off at the same time. Fireplace may run for several minutes before blower turns on. After heater modulates to the pilot position, blower will continue to run. Blower will shut off after firebox temperature decreases. The blower helps distribute heated air from the fireplace. Periodically check louvers of firebox and remove any dust, dirt or other obstruc- tions that will hinder the flow of air.

Key Pad Lock Feature This feature allows the user to lock/unlock the keypad on the hand-held remote in the MANU or AUTO mode to prevent inadvertent op- eration (i.e. children operating the hand-held remote control, etc.). The keypad is locked in either on or off. Press the POWER and LOCK buttons together to turn the unit on or off.

operating optional GWMT1 Wall Mounted

Thermostat

Light the fireplace as instructed in Lighting Instructions on page 27. Set wall thermostat to desired temperature.

Inspecting Burners Check pilot flame pattern and burner flame patterns often. PILOT Assembly The pilot assembly is factory preset for the proper flame height. Alterations may have occurred during shipping and handling. Call a qualified service person to readjust the pilot if necessary. The height of the thermopile must be 3/8" to 1/2" above pilot flame as shown in Figure 55. The thermocouple must be at a height of about 1/8" above pilot flame. The flame from

pilot burner must extend beyond both the thermocouple and thermopile.

Figure 55 - Pilot Assembly

Show 6 more labels / short text on this page
Pilot Burner · Thermopile · 3/8" to 1/2" · 1/8" · Piezo Ignitor · Thermocouple
Page 30 of the FMI CGDV32PR user manual — GLASS DOOR
Page 30 · click to enlarge
Page 30

Inspecting Burners

  • If you pilot assembly does not meet these requirements:
  • turn fireplace off (see To Turn Off Gas to Appliance , page 27)
  • see Troubleshooting , page 32
  • Figure 56 shows a typical flame pattern. If burner flame pattern differs from that described:
  • turn fireplace off (see To Turn Off Gas to Appliance, page 27)
  • see Troubleshooting , page 32

BURNER FLAME PATTERN Burner flames will be steady, not lifting or float- ing. Flame patterns will be different from unit to unit and will vary depending on installation type and weather conditions. If the vent configuration is installed incorrectly, flames will lift or "ghost". This can be danger- ous. Inspect flames after installation to ensure proper installation and performance.

Figure 56 - Typical Flame Pattern

Cleaning and Maintenance

Glass must be cleaned periodically. Dur- ing start up it is normal for condensation to form on the inside of glass causing lint, dust and other airborne particles to cling to glass surface. During initial start up a slight film may form on glass due to paint curing. Glass should be cleaned several times with a non- ammonia, nonabrasive household cleaner and warm water after the first two weeks of operation. Afterwards, clean glass two or three times during each heating season, depend- ing on the usage and circumstances present. Refer to Removing/Replacing Glass Door on page 24 of this manual when removing glass door for cleaning.

GLASS DOOR

Page 31 of the FMI CGDV32PR user manual — Cleaning and Maintenance
Page 31 · click to enlarge
Page 31

Cleaning and Maintenance

  • logs
  • If you remove logs for cleaning, refer to Installing Logs, Lava Rock and Glowing Embers , page 25, to properly replace logs.
  • Use a vacuum cleaner to remove any carbon buildup on logs.
  • Replace log(s) if broken. See Replacement Parts on page 36.
  • Replace ember material periodically as needed. See Replacement Parts on page 36.

If glass has been broken, carefully remove glass door (see Removing/Replacing Glass Door, page 23). Vacuum all glass pieces with a shop vac.

venting system Conduct annual inspection of venting system following these guidelines: 1. Check areas of venting system that are exposed to the weather for corrosion (rust spots or streaks and, in extreme cases, holes). Have these items replaced im- mediately by a qualified service person. 2. Remove the vent cap and shine a flash- light into the vent. Remove any foreign material. 3. Check for evidence of excessive con- densation. Continuous condensation can cause corrosion of caps, pipes and fittings and can be caused by having excessive lateral runs, too many elbows or exterior portions of the system being exposed to cold weather. 4. Inspect joints to verify that no pipe section or fitting has been disturbed and loos- ened. Check mechanical supports such as wall straps for rigidity.

Use only the tempered glass door replace- ment intended for this fireplace (see Replace- ment Parts, page 36 for detail on ordering). No substitutions may be made. See Remov- ing/Replacing Glass Door, page 23 for instruc- tions for replacing glass door.

  • pilot and burners
  • Remove ember material before cleaning burners and replace when cleaning is complete.
  • Burner and controls should be cleaned with compressed air to remove dust, dirt or lint.
  • Use a vacuum cleaner or small, soft bristled brush to remove excess dust, dirt or lint.
Page 32 of the FMI CGDV32PR user manual — OBSERVED PROBLEM
Page 32 · click to enlarge
Page 32

Troubleshooting

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

When ignitor button is pressed, there is no spark at pilot

1. Ignitor electrode not connected to ignitor cable 2. Ignitor cable pinched or wet
1. Reconnect ignitor cable
2. Free ignitor cable if pinched by any metal or tubing. Keep ignitor cable dry 3. Tighten nut holding piezo ignitor. Nut is located behind the mounting bracket 4. Replace ignitor cable 5. Replace piezo ignitor 6. Replace pilot assembly 7. Tighten electrode. Replace if necessary
3. Piezo ignitor nut is loose
4. Broken ignitor cable 5. Bad piezo ignitor 6. Ignitor electrode broken 7. Ignitor electrode positioned wrong

When ignitor button is pressed, there is spark at pilot but no ignition

1. Gas supply turned off or equipment shutoff valve closed 2. Gas control knob not in PILOT position 3. Gas control knob not pressed in while in PILOT position 4. Air in gas lines when installed
1. Turn on gas supply or open equipment shutoff valve
2. Turn gas control knob to PILOT position 3. Press in gas control knob while in PILOT position
4. Continue holding down control knob. Repeat igniting operation until air is removed 5. Contact local propane/LP gas company 6. Clean pilot (see Cleaning and Maintenance , page 30) or replace pilot assembly 7. Replace gas regulator
5. Depleted gas supply (propane/LP models only) 6. Pilot is clogged
7. Gas regulator setting is not correct
Page 33 of the FMI CGDV32PR user manual — OBSERVED PROBLEM
Page 33 · click to enlarge
Page 33

TROUBLESHOOTING

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

Pilot lights but flame goes out when control knob is released

1. Gas control knob not fully pressed in 2. Gas control knob not pressed in long enough
1. Press in gas control knob fully 2. After pilot lights, keep gas control knob pressed in 30 seconds 3. Fully open equipment shutoff valve 4. A) Contact local natural or propane/LP gas company B) Clean pilot (see Cleaning and Maintenance , page 30) or replace pilot assembly
3. Equipment shutoff valve not fully open 4. Pilot flame not touching thermocouple, which allows thermocouple to cool, causing pilot flame to go out. This problem could be caused by one or both of the following: A) Low gas pressure B) Dirty or partially clogged pilot 5. Thermocouple connection loose at control valve 6. Thermocouple damaged 7. Control valve damaged
5. Hand tighten until snug, then tighten 1/4 turn more 6. Replace pilot assembly 7. Replace control valve

Burner does not light after pilot is lit

1. Burner orifice clogged
1. Clean burner (see Cleaning and Maintenance , page 30) or replace burner orifice 2. Contact local propane/LP or natural gas company 3. Reconnect leads
2. Inlet gas pressure is too low 3. Thermopile leads disconnected or improperly connected 4. Thermopile is defective
4. Replace thermopile
1. Manifold pressure is too low 2. Burner porting or orifice clogged
1. Contact local propane/LP or natural gas company 2. Clean burner (see Cleaning and Maintenance , page 30) or replace burner orifice
1. Burner orifice is clogged or damaged

Burner backfiring during com- bustion

1. Clean burner (see Cleaning and Maintenance , page 30) or replace burner orifice 2. Replace damaged burner 3. Replace gas control
2. Damaged burner 3. Gas regulator defective

Slight smoke or odor during initial operation

1. Residues from manufacturing processes and logs curing
1. Problem will stop after a few hours of operation

Delayed ignition burner

Page 34 of the FMI CGDV32PR user manual — OBSERVED PROBLEM
Page 34 · click to enlarge
Page 34

TROUBLESHOOTING

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

Heater produces a whistling noise when burner is lit

1. Turning gas control knob to HI position when burner is cold 2. Air in gas line
1. Turn gas control knob to LO position and let warm up for a minute 2. Operate burner until air is removed from line. Have gas line checked by local propane/LP or natural gas company 3. Clean burner (see Cleaning and Maintenance, page 30) or replace burner orifice
3. Dirty or partially clogged burner orifice
1. Flame impingement on logs
1. Adjust log set so that the flame does not excessively impinge in it 2. Inspect the opening at the base of the burner to see that it is NOT packed with any type of material
2. Debris around burner air mixer

Fireplace produces a clicking/ ticking noise just after burners are lit or shut off

1. Metal expanding while heating or contracting while cooling
1. This is normal. If noise is excessive, contact qualified service person

Remote does not function

1. Battery is not installed or battery power is low
1. Replace 9-volt batteries in receiver and remote control

Fireplace shuts off in use

1. High or gusting winds
1. Fireplace has been tested for up to 40 mph winds. However, extreme conditions may occur. See Lighting Instructions on page 27 2. Contact local propane/LP or natural gas company 3. Clean pilot (see Cleaning and Maintenance, page 30) 4. Locate and correct all leaks (see Checking Gas Connections , page 21) 5. Tighten glass
2. Low line pressure
3. Pilot is partially clogged
4. Inner vent pipe leaking exhaust gasses into system
5. Glass too loose and air tight gasket leaks in corners after usage 6. Bad thermopile or thermocouple 7. Improper vent cap installation
6. Replace faulty component
7. Check for proper installation and freedom from debris or blockage

Glass soots

Page 35 of the FMI CGDV32PR user manual — OBSERVED PROBLEM
Page 35 · click to enlarge
Page 35

TROUBLESHOOTING Continued

  • WARNING: If you smell gas
  • Shut off gas supply.
  • Do not try to light any appliance.
  • Do not touch any electrical switch; do not use any phone in your building.
  • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
  • If you cannot reach your gas supplier, call the fire department.

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

Fireplace produces unwant- ed odors

1. Gas leak. See Warning statement above
1. Locate and correct all leaks (see Checking Gas Connections , page 21)

Gas odor even when control knob is in OFF position

1. Gas leak. See Warning statement above
1. Locate and correct all leaks (see Checking Gas Connections , page 21) 2. Replace control valve
2. Control valve defective

Gas odor during combustion

1. Gas leak. See Warning statement above
1. Locate and correct all leaks (see Checking Gas Connections , page 21)

Dark residue on logs or inside of fireplace

1. Improper log placement
1. Properly locate logs (see Installing Logs, Lava Rock and Glowing Embers , page 25) 2. Clean out air holes at burner inlets. Periodically repeat as needed 3. Remove blockage or replace burner 4. Have the vent system inspected, including the termination cap. Remove any restrictions or obstruction 5. Clear excess embers until a minimum gap of 1/2" remains under the grate
2. Air holes at burner inlet blocked
3. B u r n e r f l a m e h o l e s blocked 4. Improper venting or excessive blockage
5. Excessive amounts of embers and pan material
Page 36 of the FMI CGDV32PR user manual — Specifications
Page 36 · click to enlarge
Page 36

Replacement Parts

  • When calling, have ready:
  • your name
  • your address
  • model and serial numbers of your heater
  • how heater was malfunctioning
  • purchase date Usually, we will ask you to return the part to the factory.
  • Service Hints When Gas Pressure Is Too Low
  • pilot will not stay lit
  • burners will have delayed ignition
  • fireplace will not produce specified heat
  • propane/LP gas supply might be low (propane/LP units only) You may feel your gas pressure is too low. If so, contact your local gas supplier.

Technical Service You may have further questions about installation, operation, or troubleshooting. If so, contact FMI PRODUCTS, LLC at 1-866-328-4537. When calling please have your model and serial numbers of your heater ready. You can also visit FMI PRODUCTS, LLC’s web site at www.fmiproducts.com.

Specifications

  • (V)T32N-A Series, (V)T32N-A-HA Series, CGDV32NR and CTDV32NR-HA
  • Rating: 12,000/18,000 Btu/Hr
  • Type Gas: Natural Gas Only
  • Ignition: Piezo
  • Manifold Pressure: Models (V)T32N-A Series and CGDV32NR 3.5" W.C. Models (V)T32N-A-HA series and CTDV32NR-HA 3.8" W.C.
  • Minimum Inlet Gas Pressure (W.C.): 5.5"
  • Dimensions (H x W x D) (Firebox only. Does not include nailing flanges or standoffs): 32 1 / 4 " x 34 1 / 2 " x 16 5 / 8 "
  • Fireplace Weight*: 80 lb
  • Shipping Weight*: 83 lb *For refractory lined models add 45 lb
  • (V)T32P-A Series and CGDV32PR
  • Rating: 11,000/17,000 Btu/Hr
  • Type Gas: Propane/LP Gas Only
  • Ignition: Piezo
  • Manifold Pressure: 10" W.C.
  • Minimum Inlet Gas Pressure (W.C.): 11"
  • Dimensions (H x W x D) (Firebox only. Does not include nailing flanges or standoffs): 32 1 / 4 " x 34 1 / 2 " x 16 5 / 8 "
  • Fireplace Weight*: 80 lb
  • Shipping Weight*: 83 lb *For refractory lined models add 45 lb
Page 37 of the FMI CGDV32PR user manual — Receiver and Hand-Held on/off Remote Control Kit - mlcr
Page 37 · click to enlarge
Page 37

Accessories

Purchase these accessories from your local dealer. If they can not supply these accessories call FMI PRODUCTS, LLC at 1-866-328-4537 for information. You can also write to the ad- dress listed on the back page of this manual.

Thermostatically- controlled blower kit - BKT Provides better heat distribution. Blower turns off and on automatically, as needed. Com- plete installation and operation instructions included in this manual.

Refractory Brick Liner Kit BL32DS This brick liner adds a touch of style to your direct-vent fireplace. Complete installation instructions included in this manual.

Propane/natural gas conversion kit PCDM-32T - Propane/LP Gas Conversion Kit NCDM-32T - Natural Gas Conversion Kit

Receiver and Hand-Held Thermostat Remote Control Kit - TLCR

Face/Louver Panel kit RLD32 - Rolled Louver Panels, Black

Louver trim kit (Rolled Louvers Only) LT32B - Brushed Brass LT32P - Platinum

For all Remote-Ready Models. Allows the fireplace to be operated in a manually or thermostatically-controlled mode. You can adjust your heat settings and turn the fireplace on or off without leaving the comfort of your easy chair.

Deflection hood HD32 - Hood - Black (2" Brow)

Perimeter Trim kit PT32 - Black PT32B - Brushed Brass PT32P - Platinum

Receiver and Hand-Held on/off Remote Control Kit - mlcr

For all Remote-Ready Models. Allows the fireplace to be turned on and off conveniently.

Wall mounted thermostat control kit - gwmt1 Allows easy wall access for thermostatic opera- tion of your fireplace.

Manual blower Kit - BK Manual variable control blower accessory provides better heat distribution. Complete in- stallation and operation instructions included in this manual.

Wall mounted on/off switch gwmS2 Allows burner system to be turned on and off with a wall switch.

Page 38 of the FMI CGDV32PR user manual — Parts
Page 38 · click to enlarge
Page 38

Parts

Models (V)T32N-A, (V)T32NB-A, (V)T32NR-A, (V)T32NRB-A, (V)T32P-A, (V)T32PB-A, (V)T32PR-A, (V)T32PRB-A, CGDV32NR, CGDV32PR and CTDV32NR-HA

FMI CGDV32PR — Parts diagram (page 38)
Fig. 36 · Parts

22-4 22-5 22-3

Page 39 of the FMI CGDV32PR user manual — (V)T32N-A (V)T32P-A (V)T32NB-A (V)T32PB-A
Page 39 · click to enlarge
Page 39

PARTS This list contains replaceable parts used in your fireplace. When ordering parts, follow the instructions listed under Replacement Parts on page 36 of this manual.

PART NUMBER

CGDV32NR CGDV32PR CTDV32NR-HA (V)T32NR-A (V)T32PR-A (V)T32NRB-A (V)T32PRB-A DESCRIPTION QTY. 1 ** ** Firebox Assembly 1 2 ** ** Face Weldment 1 3 108892-01 108892-01 Door Assembly (T & CGDV Models Only) 1 108892-02 108892-02 Door Assembly (VT Models Only) 1 4 109155-01 108903-01 Top Louver/Panel Assembly 5 109155-02 108903-02 Bottom Louver/Panel Assembly 1 6 ** ** Fireplace Top 1 7 ** ** Fireplace Top Insulation 1 8 ** ** Fireplace Surround 1 9 108885-01 108885-01 Burner Assembly (Natural Gas) 1 108885-02 108885-02 Burner Assembly (Propane/LP Gas) (See page 40 & 41)

(V)T32N-A (V)T32P-A (V)T32NB-A (V)T32PB-A

KEY NO.

10 108890-01 108890-01 Burner Base Gasket 1 11 109082-03 109082-03 Heat Shield 1 12 108897-01 108897-01 Rear Refractory Brick Panel (B Models Only) 1 13 108901-01 108901-01 Right Refractory Brick Panel (B Models Only) 1 14 108901-02 108901-02 Left Refractory Brick Panel (B Models Only) 1 15 11418 11418 Push-On Nut 2 16 12125 12125 Screen 2 17 109479-01 109479-01 Screen Rod 1 18 14123 14123 Strain Relief 1 19 21171 21171 Gas Knock-Out Cover 2 20 24353 24353 Handy Box Assembly 1 21 24460 24460 Gas Conduit Assembly 1 22 109222-01 109222-01 Log Set 1 22-1 109403-01 109403-01 Front Log (No. 1) 1 22-2 109404-01 109404-01 Rear Log (No. 2) 1 22-3 109407-01 109407-01 Base Log (No. 3) 1 22-4 109406-01 109406-01 Crossover Log (No. 4) 1 22-5 109405-01 109405-01 Left Top Log (No. 5) 1 22-6 109408-01 109408-01 Right Top Log (No. 6) 1 PARTS AVAILABLE - NOT SHOWN 25487 25487 Lava Rock/Bag Assembly 1 PCDM-32T Propane/LP Gas Conversion Kit (model CTDV32NR-HA only)

** Not a field replaceable part.

Page 40 of the FMI CGDV32PR user manual — PARTS
Page 40 · click to enlarge
Page 40

PARTS

Burner assembly Models (V)T32N-A, (V)T32NB-A, (V)T32NR-A, (V) T32NRB-A, (V)T32P-A, (V)T32PB-A, (V)T32PR-A, (V)T32PRB-A, CGDV32NR, CGDV32PR and CTDV32NR-HA

FMI CGDV32PR — PARTS diagram (page 40)
Fig. 37
Page 41 of the FMI CGDV32PR user manual — PARTS
Page 41 · click to enlarge
Page 41

PARTS

Burner assembly Models (V)T32N-A, (V)T32NB-A, (V)T32NR-A, (V) T32NRB-A, (V)T32P-A, (V)T32PB-A, (V)T32PR-A, (V)T32PRB-A, CGDV32NR, CGDV32PR and CTDV32NR-HA This list contains replaceable parts used in your fireplace. When ordering parts, follow the instructions listed under Replacement Parts on page 36 of this manual.

KEY NO. PART NO. DESCRIPTION QTY. 1 11102 Screw #8-32 x 3/8 PPH Zinc 2 2 11105 Screw #10 x 1/2 Zinc 9 3 11179 Screw #10-24 x 1/4 Zinc 4 4 11237 Screw, Trilab M4 x 8 mm 1 5 14389 Millivolt Valve (Natural Gas) 1 14390 Millivolt Valve (Propane/LP Gas) 1 117370-01 Millivolt Valve (NG-High Altitude) 1 6 14492 Piezo Ignitor 1 7 14500 Brass Fitting 2 8 14253 Flexible Connector 1 9 14511 Ignitor Bracket 1 10 14528 Brass Elbow Fitting 1 11 104506-25 Orifice (Natural #47) 1 104506-02 Orifice (Propane/LP #55) 1 12 104509-02 Aluminum Tubing Assy 1 13 26808 Valve Bracket 1 14 26827 Switch Bracket 1 15 108886-01 Base Grate Assembly 1 16 108891-01 Burner 1 17 108084-02 Pilot Assembly (Natural) 1 108084-03 Pilot Assembly (Propane/LP) 1 108084-05 Pilot Assembly (NG-High Altitude) 1 18 ** Burner Base Assembly 1 19 27113 Air Deflector 1 ** Not a field replaceable part.

Page 42 of the FMI CGDV32PR user manual — NOTES
Page 42 · click to enlarge
Page 42

NOTES

Page 43 of the FMI CGDV32PR user manual — NOTES
Page 43 · click to enlarge
Page 43

NOTES

Page 44 of the FMI CGDV32PR user manual — FMI PRODUCTS, LLC LIMITED WARRANTIES
Page 44 · click to enlarge
Page 44

Warranty

KEEP THIS WARRANTY

Model (located on product or identification tag)

Serial No. (located on product or identification tag)

Keep receipt for warranty verification.

FMI PRODUCTS, LLC LIMITED WARRANTIES

New Products Standard Warranty: FMI PRODUCTS, LLC warrants this new product and any parts thereof to be free from defects in material and workmanship for a period of four (4) years from the date of first purchase from an authorized dealer provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s warnings and instructions.

For products purchased for commercial, industrial or rental usage, this warranty is limited to 90 days from the date of first purchase.

Factory Reconditioned Products Limited Warranty: FMI PRODUCTS, LLC warrants factory reconditioned products and any parts thereof to be free from defects in material and workmanship for 30 days from the date of first purchase from an authorized dealer provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s warnings and instructions.

Terms Common to All Warranties The following terms apply to all of the above warranties:

Always specify model number and serial number when contacting the manufacturer. To make a claim under this warranty the bill of sale or other proof of purchase must be presented.

This warranty is extended only to the original retail purchaser when purchased from an authorized dealer, and only when installed by a qualified installer in accordance with all local codes and instructions furnished with this product.

This warranty covers the cost of part(s) required to restore this product to proper operating condition and an allow- ance for labor when provided by a FMI PRODUCTS, LLC Authorized Service Center or a provider approved by FMI PRODUCTS, LLC. Warranty parts must be obtained through authorized dealers of this product and/or FMI PRODUCTS, LLC who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty.

Travel, handling, transportation, diagnostic, material, labor and incidental costs associated with warranty repairs, unless expressly covered by this warranty, are not reimbursable under this warranty and are the responsibility of the owner.

Excluded from this warranty are products or parts that fail or become damaged due to misuse, accidents, improper installation, lack of proper maintenance, tampering, or alteration(s).

This is FMI PRODUCTS, LLC’s exclusive warranty, and to the full extent allowed by law; this express warranty excludes any and all other warranties, express or implied, written or verbal and limits the duration of any and all implied warranties, including warranties of merchantability and fitness for a particular purpose to four (4) years on new products and 30 days on factory reconditioned products from the date of first purchase. FMI PRODUCTS, LLC makes no other warranties regarding this product.

FMI PRODUCTS, LLC’s liability is limited to the purchase price of the product, and FMI PRODUCTS, LLC shall not be liable for any other damages whatsoever under any circumstances including indirect, incidental, or consequential damages.

Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.

This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

For information about this warranty contact:

2701 S. Harbor Blvd. Santa Ana, CA 92704

116646-01 Rev. J 10/09

1-866-328-4537 www.fmiproducts.com

Date Purchased

Ask about the FMI CGDV32PR

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the FMI CGDV32PR

Be the first to ask — other owners or our team will answer.

Original document

FMI CGDV32PR manual PDF

44 pages·2 MB·Indoor Fireplace·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…